Honeywell Network Hardware NETAXS 123 User Manual

NetAXS-123  
Access Control Unit  
Installation Guide  
May 2010  
© 2010 Honeywell. All rights reserved.  
800-05779, Revision A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.0 Introduction.......................................................................................................................................... 2  
1.1 Access Control Overview ..................................................................................................2  
1.2 NetAXS-123 Overview......................................................................................................2  
2.0 Panel Components and Descriptions................................................................................................ 3  
2.1 Supervised Input Wiring....................................................................................................5  
2.2 NetAXS-123 Access Control Unit.....................................................................................7  
NetAXS-123 Add-On Board ........................................................................................... 7  
Supported Readers ........................................................................................................... 8  
Real-Time Clock Protection ............................................................................................ 9  
2.3 Power Supply.....................................................................................................................9  
2.4 Battery..............................................................................................................................10  
2.5 Suppressors ......................................................................................................................10  
3.0 Installation.......................................................................................................................................... 11  
3.1 Installing the Compact Enclosure Panel ..........................................................................11  
Installing on a Wall ....................................................................................................... 11  
Installing over a Gang Box ............................................................................................ 15  
Installing on a Flat Surface ............................................................................................ 16  
3.2 Installing the Standard Enclosure Panel ..........................................................................17  
3.3 Installing the Add-On Board............................................................................................26  
3.4 Wiring the Readers ..........................................................................................................29  
3.5 Wiring Door Strikes.........................................................................................................33  
3.6 Setting DIP Switches and Jumpers ..................................................................................35  
Controller Board DIP Switch and Jumper Settings ....................................................... 35  
Add-On Board DIP Switch and Jumper Settings .......................................................... 40  
3.7 Communications ..............................................................................................................42  
USB Communications ................................................................................................... 42  
RS-485 Communications .............................................................................................. 44  
Ethernet TCP/IP Communications ................................................................................ 47  
4.0 System Configuration....................................................................................................................... 48  
4.1 Ethernet Connection ........................................................................................................48  
4.2 USB Connection ..............................................................................................................49  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3 RS-485 Connection via PCI-3 .........................................................................................50  
4.4 RS-485 Connection via NetAXS-123..............................................................................51  
4.6 M-56K Dial-up Modem, RS-485 Connection via Hub (PCI-3) ......................................54  
4.7 Fiber Converter to RS-485 Connection via PCI-3...........................................................55  
4.8 Fiber Converter to RS-485 Connection via NetAXS-123 ...............................................56  
4.11 Mixed Loops..................................................................................................................59  
5.0 Hardware Specifications.................................................................................................................. 60  
5.1 Relay Contacts .................................................................................................................60  
5.2 Reader Interface...............................................................................................................60  
5.3 Maximum Output Loading ..............................................................................................60  
5.4 PoE Power Limitations ....................................................................................................60  
5.5 Mechanical.......................................................................................................................61  
5.6 Environment.....................................................................................................................62  
5.7 Cable ................................................................................................................................62  
6.0 Basic Standalone Operation ............................................................................................................ 63  
6.1 Card Read / Door Lock Operation...................................................................................63  
6.2 Door Egress / Door Lock / Door Status Operation..........................................................63  
7.0 Maintenance....................................................................................................................................... 64  
8.0 Troubleshooting ................................................................................................................................ 65  
9.0 Technical Support............................................................................................................................. 66  
9.1 Normal Support Hours.....................................................................................................66  
9.2 Web..................................................................................................................................66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIST OF TABLES  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
vii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
In this chapter ...  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Introduction  
1.0 Introduction  
This document describes how to install the NetAXS-123 Standard Enclosure access control unit and  
the NetAXS-123 Compact Enclosure access control unit.  
1.1 Access Control Overview  
An access control system protects and preserves an enterprise’s resources by providing authentication,  
authorization, and administration services. Authentication is a process that verifies a user’s identity. If  
the user is verified, the system then either grants or denies access to specific areas and resources.  
Administration includes the creation and modification of user accounts and access privileges.  
An access control system consists of hardware and software, usually configured in a network  
environment over a standard network protocol. Access control units, readers, door strikes, and video  
and other devices, for example, are configured to control and monitor the access to a company site.  
1.2 NetAXS-123 Overview  
A NetAXS-123 access control is a full-featured one-door web-based access control system that  
supports up to three doors when supplemented with an add-on input/output board. The NetAXS-123  
panel includes a built-in web server, built-in Ethernet and USB support, and Power over Ethernet  
(PoE) capability. You can manage the access control system using either a web browser or WIN-PAK.  
For supported configurations, see “System Configuration“ on page 48 to view illustrations of the  
supported NetAXS-123 system configurations.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
2.0 Panel Components and Descriptions  
Note: This device complies with part 15 of the FCC Rules. Operation is subject to the following two  
conditions: (1) This device may not cause harmful interference, and (2) this device must accept any  
interference received, including interference that may cause undesired operation.  
The NetAXS-123 panel consists of a web-browser-enabled controller, a one- or two-door add-on board  
that supports additional inputs and outputs, a power-over-Ethernet (PoE) power supply (NetAXS-123  
Compact only), and a battery (NetAXS-123 Standard only).  
The following figures show the NetAXS-123 panel wiring and components.  
Figure 1: NetAXS-123 Compact Enclosure Wiring and Components  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
Figure 2: NetAXS-123 Standard Enclosure Panel Wiring and Components  
Note: Maintain at least a .25-inch distance between the non-power limited wiring (115 VAC/60 Hz  
input wiring, power line filter wiring, and battery backup/charger wiring) and all other wiring, which is  
power-limited Class 2 wiring.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
Figure 3: NetAXS-123 Add-On Board Wiring and Components  
2.1 Supervised Input Wiring  
The supervised inputs are located on the following terminal blocks:  
Table 1: Supervised Input Terminal Blocks  
Board Configuration  
Terminal Block  
1-Door (Controller Board)  
C-TB2  
C-TB10  
1-Door (Add-On Board)  
2-Door (Add-On Board)  
IO-TB2  
IO-TB2 (as 1-door Add-On  
Board)  
IO-TB6  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
Tampers can also be supervised. They are located on the following terminal blocks:  
Table 2: Supervised Tamper Terminal Blocks  
Board Configuration  
Terminal Block  
1-Door (Controller Board)  
C-TB3/TMPR A  
C-TB4/TMPR B  
1-Door (Add-On Board)  
2-Door (Add-On Board)  
IO-TB3/TMPR A  
IO-TB4/TMPR B  
IO-TB3/TMPR A  
IO-TB4/TMPR B  
IO-TB7/TMPR A  
IO-TB8/TMPR B  
Door Status (STS) and Request to Exit (REX) for all three doors may be configured for Normally  
Open or Normally Closed contacts as supervised or non-supervised. Inputs 5 (generic) and 6 (power)  
are on C-TB10. All seven inputs on the Controller Board and four inputs on the Add-On Board have  
default functions, but they can be configured for general purpose inputs.  
The following figure shows the typical wiring for a supervised input.  
Figure 4: Typical Supervised Input Wiring Diagram  
The figure above shows standard 2,200 ohm resistors. The NetAXS-123 panel accepts 1,000, 2,200,  
4,700, or 10,000 ohm values. Note that both resistors must have the same value.  
In addition, the Reader tampers can be supervised and capable of being used as additional inputs if the  
default functionality is not needed.  
The wire used for the inputs should be shielded and cannot exceed 30 ohms over the entire length of  
the cable. Remember that the distance from the panel to the door must be doubled to determine the  
total resistance.  
Caution: The cable shield should be grounded only at the panel earth ground. Grounding at both ends  
can cause ground loops which can be disruptive.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
Caution: The system has not been verified for compliance with UL1076 Burglar Alarm units and  
systems.  
2.2 NetAXS-123 Access Control Unit  
The NetAXS-123 panel is a one-door access control unit that you can supplement with an add-on  
board that supports second and third doors. The following table shows the NetAXS-123 input/output  
options:  
Table 3: NetAXS-123 Input/Output Options  
Board  
Readers  
Inputs/Outputs  
Controller  
1 door/2 readers  
1 lock output  
1 aux output  
1 status input  
1 Request to Exit  
2 reader tamper/AUX  
inputs  
Add-On (1 Door)  
1 door/2 readers  
1 lock output  
1 aux output  
1 status input  
1 Request to Exit  
2 reader tamper/AUX  
inputs  
Add-On (2 Door)  
2 doors/4 readers  
2 lock outputs  
2 aux outputs  
2 status inputs  
2 Request to Exits  
4 readers tamper/AUX  
inputs  
You can use the NetAXS-123 panel as a standalone panel with independent card and transaction  
storage or, with a host software upgrade, as a fully monitored online access control device.  
Panel inputs are capable of four state supervision: Normal, Alarm, Short and Cut. One input is used for  
request to exit on each door and one input is used for door status on each door. Supervised inputs for  
External Power Fail and Reader Tampers are supplied as well, and they can be used as additional  
inputs when not required for their default purpose.  
2.2.1 NetAXS-123 Add-On Board  
The NetAXS-123 Add-On Board enables you to expand from one door to either two or three doors.  
The board easily connects to the NetAXS-123 controller board (see the NetAXS-123 Add-On Board  
Installation Guide (800-05787).  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
2.2.2 Supported Readers  
Supported readers include the following:  
Table 4: Readers Supported by NetAXS-123  
Series  
Reader Model  
OP-10  
Honeywell Part  
Number  
OmniProx  
OP10GENE  
OP10HONE  
OP-30  
OP30GENE  
OP30HONE  
OP-40  
OP40GENE  
OP40HONE  
OP-45  
OP45GENE  
OP45HONE  
HID  
ProxPoint Plus  
MiniProx  
6005B  
HU/5365EGP00  
Thinline II  
HU/5395CB100  
HU/5395CG100  
HU/5395CK100  
ProxPro  
HU/5355AGN00  
HU/5455BGN00  
HU/5355AGK00  
4045CGNU0  
ProxPro II  
ProxPro K  
EntryProx  
MaxiProx  
OM40  
HU/5375AGN00  
Omni-Class  
OM40BHONB  
OM40GHONB  
OM41  
OM55  
OM70  
OM41BHONB  
OM41GHONB  
OM55BHONB  
OM55GHONB  
OM70BHONB  
OM70GHONB  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
Series  
Reader Model  
Honeywell Part  
Number  
OmniAssure  
OT30  
OT30HONA  
OT31HONA  
OT35HONA  
OT36HONA  
OT70HONA  
OT75HONA  
92042000000  
92042200000  
OT31  
OT35  
OT36  
OT70  
OT75  
NexWatch  
DR 4200K  
DR 4220  
Note: For NetAXS-123 reader specifications, see Hardware Specifications, page 60.  
2.2.3 Real-Time Clock Protection  
The panel RTC is backed up using a super capacitor. The super capacitor will power the real-time  
clock for 24 hours in the absence of primary power or backup battery.  
2.3 Power Supply  
The NetAXS-123 Compact Enclosure is powered by Power Over Ethernet (PoE) injector. This PoE  
injector can supply a total system current of 800mA to 900mA @ 12VDC. However the NetAXS-123  
controller board consumes 400mA of current, and it therefore leaves 450mA of total current for the  
12VDC external power. See Hardware Specifications, page 60, for further details on current limits  
using PoE.  
The Standard Enclosure uses a 12VDC 4A power supply with an international input of 100VAC to  
240VAC. The supply also charges and monitors the condition of the battery. Wire the unswitched  
electrical power to the supply per the National Electrical Code as well as any local electrical codes,  
including the safety ground wire.  
An input power indicator is supplied, and it is illuminated when input voltage is present. If the  
indicator is off, the input voltage is off, or too low to operate the system.  
Caution: Disconnect the battery and AC power before servicing the fuse. For continued protection  
against the risk of electric shock and fire hazard, replace the input fuse with a GMA type fuse with the  
rating of 1A, 250V. The fuse is located in the lower-left corner in the cabinet, as shown below.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Panel Components and Descriptions  
2.4 Battery  
For the NetAXS-123 Standard Enclosure panel, one CASIL CA1270, 12 VDC, 7A-hour sealed  
lead-acid battery (Honeywell order number 3-000066). The battery provides standby backup power,  
depending upon system configuration and activity. When AC is lost, the power supply automatically  
switches to the backup battery for continuous 12VDC power. Replace the battery every 2 to 2.5 years,  
or more often if the system has a high rate of backup use.  
2.5 Suppressors  
Two suppressors (HAS number S-4) are required for each door lock. One suppressor is installed on the  
panel control board, and the second must be installed at the door lock.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Installation  
3.0 Installation  
3.1 Installing the Compact Enclosure Panel  
Perform the following steps to install the NetAXS-123 Compact panel:  
Warning: Use a static strap whenever touching the panel to ensure protection from Electrostatic  
Discharge (ESD).  
3.1.1 Installing on a Wall  
1. Review the panel layout, cable runs, and power needs.  
2. Mount the enclosure’s back at the proper location on the wall:  
a. Drill the screw holes in the wall, using the panel’s back as a template, and then pull the  
power and all I/O wires to the enclosure and through the knockout holes, and properly  
mark each wire for its use.  
b. Screw the back of the panel to the wall, using either drywall screws or threaded wall  
anchors.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Installation  
3. Mount the board onto the back of the panel.  
4. Choose the tamper type (standard or off-the-wall tamper) and wire the tamper.  
Wiring a standard tamper:  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
Wiring an off-the-wall tamper:  
5. Set the tamper, using pliers at the four locations indicated below.  
Warning: Do not apply power at this time.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
6. Connect the Ethernet cable and the Tamper wire, as shown below.  
7. Set DIP switch settings for the panel address, communication termination and biasing. See DIP  
8. Check all wiring at this time.  
Caution: Improper wiring can cause damage to the NetAXS-123 at power up and result in a loss  
of warranty.  
9. Apply power to the panel.  
10.Check for the Run LED for a successful power-up. If the LED is blinking green, the panel is  
powered up successfully.  
11.Close the cover.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
3.1.2 Installing over a Gang Box  
1. Review the panel layout, cable runs, and power needs.  
2. Mount the back of the panel on the gang box.  
3. Pull the wires from the gang box through the knockout holes in the base of the enclosure.  
4. Perform steps 3 through 10 in the preceding section ( Installing on a Wall, page 11) to complete  
the installation of the panel over a gang box.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
3.1.3 Installing on a Flat Surface  
1. Review the panel layout, cable runs, and power needs.  
2. Mount the back of the enclosure on the surface, either with drywall screes or threaded wall  
anchors.  
3. Break off the appropriate plastic wiring tabs, using pliers.  
4. Perform steps 3 through 10 in Installing on a Wall, page 11 to complete the installation of the  
panel over a horizontal surface.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
3.2 Installing the Standard Enclosure Panel  
Perform the following steps to install the NetAXS-123 Standard Enclosure panel:  
Warning: Use a static strap whenever touching the panel to ensure protection from Electrostatic  
Discharge (ESD).  
1. (Optional) Remove the green ground wire and the door.  
2. Partially install the four power supply screws.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
3. Install the power supply.  
a. Fit the power supply screws through the key holes in the left side of the cabinet, and seat  
the power supply by pulling down.  
b. From the outside of the cabinet, tighten the screws to lock the power supply in place.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
c. Inside the cabinet, screw in the two self-tapping screws (supplied in the product box) at  
the top and bottom of the power supply.  
Warning: These screws must be installed to ground the power supply to the enclosure.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
d. Plug the connector that is attached to the blue and brown wires into the power supply.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
4. Select one of the following three possible entry points for the power cable:  
Warning: Do not apply power at this time. Be sure the power cable is disconnected from the  
external power source before following this step.  
• Through the bottom conduit  
knockout, which directly connects  
AC power to the terminal block.  
• Through the side conduit knockout,  
which also directly connects AC  
power to the terminal block.  
• Through the optional AC input  
receptacle. Note: the brown and blue  
wires must be twisted together from  
the point of entry at the AC input  
receptacle to the Terminal Block.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
5. Use a pencil to mark the location of the holes on the wall.  
6. Screw the NetAXS-123 Controller Board with the four captive screws  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
7. Hold the Add-On Board over the Controller Board and seat the board-to-board connector into  
the Controller Board. Secure the Add-On Board onto the Controller Board with the four captive  
finger screws. For more explanation of the Add-On Board installation, see the next section,  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
8. Connect the wiring harness, as shown.  
Warning: DO NOT CONNECT the AC power or the battery wires yet!  
9. Power up the NetAXS-123 Controller Board and configure the system. Refer to the  
NetAXS-123 Startup Guide (800-05780) for instructions.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
10.Connect the battery.  
11.Attach the door to the cabinet.  
12.Re-connect the green ground wire to the cabinet door.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
3.3 Installing the Add-On Board  
Warning: To prevent damage to the NXC1 Controller Board, remove power from the  
NetAXS-123 panel before installing or removing a NetAXS-123 Add-On Board.  
1. On the NetAXS-123 Controller Board, locate the four posts called out in the image shown  
below:  
NetAXS-123 Controller Board  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
2. Pick up the Add-On Board and notice the four posts on the bottom.  
3. Seat the Add-On Board posts into the four posts on the NetAXS-123 Controller Board, aligning  
the terminal-block edge of the Add-On Board with the terminal-block edge of the Controller  
Board.  
4. With your fingers, tighten the posts’screws.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
5. Set the relay jumpers.  
a. Use the following figure to locate the jumpers.  
(12VDC power or external power) and the relay contact position (Normally Open or  
Normally Closed).  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
3.4 Wiring the Readers  
Each reader port supports one or two readers (entry and exit readers) with Wiegand output format. The  
maximum power draw is 500 mA for readers and AUX Power combined.  
To fully utilize each reader port, a shielded 7-conductor cable (18-22 AWG) is required. If you don’t  
need the HOLD LINE feature, you can use the standard 6-conductor cable (HAS part number  
NC186-BL).  
Note: If you are using additional HOLD lines for readers, you will need an 8-conductor cable.  
The cable shield should be grounded at the panel only. Grounding at both ends can cause ground loops  
which can be disruptive. The maximum recommended length of wiring is 500 feet per reader.  
Figure 5 shows a one-door panel, with the readers wired to terminal blocks C-TB3 and C-TB4 on the  
Controller Board, and to terminal blocks IO-TB3, IO-TB4, IO-TB7, and IO-TB8 on the Add-On  
Board. The wires are color-coded to their labeled terminals. If this were a two-door panel, the two  
additional readers would be wired to terminal blocks C-TB1 and C-TB2 on the Controller Board, and  
to terminal blocks IO-TB1 and IO-TB2 on the Add-On Board.  
Figure 5: Wiring Readers to the Controller Board  
Note: Reader A and Reader B share LED, DO, D1, GND, and +12V connections. Each reader has its  
own Tamper and Hold.  
The following three tables list the factory controller board I/O default settings for door-1, door-2, and  
door-3 configurations. These are the mappings for readers, inputs, and outputs. Reader A and Reader B  
share many common connections.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Installation  
Table 5 shows the input/output factory default wiring for a one-door configuration on the Controller  
Board.  
Table 5: Factory Default Configuration Settings for Door 1  
Type  
Purpose  
Web  
Default  
Name  
Terminal  
Block  
Label  
Reader A  
Reader B  
Other  
a
a
Input  
Egress/  
Request to  
Exit (REX)  
Input 1:  
Door 1  
Egress  
C-TB2  
Input 1  
Input 1  
IN1 (REX)  
a
a
Door Status  
Input 2:  
Door 1  
Status  
C-TB2  
Input 2  
Input 2  
IN2 (STS)  
Reader  
Tamper  
Input 3:  
Door  
C-TB3  
TMPR A  
Input 3  
TMPR-A  
Reader  
Tamper  
Input 4:  
Door  
C-TB4  
TMPR B  
Input 4  
TMPR-B  
General  
Input 5:  
GENERAL  
PURPOSE  
C-TB10  
IN5  
Input 5  
Input 6  
Input 20  
Power/  
General  
Input 6:  
POWER  
C-TB10  
IN6 (PWR  
FAIL)  
Panel  
Tamper  
PANEL  
TAMPER  
ALTER_T  
MPR  
a
a
Output  
Lock Relay  
Output #1  
C-TB1  
LOCK  
Output 1  
Output 1  
a
a
Reader LED Output #2  
C-TB3  
LED  
Output 2  
Output 2  
AUX Relay  
Output #3  
C-TB1  
AUX  
Output 3  
a
a
Reader  
Buzzer  
Future  
Feature  
C-TB3  
BZR  
Output 4  
Output 4  
a
Readers A and B share the same connection.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
Notes:  
The Controller Board includes Inputs 7 and 8 but they are reserved for system use.  
The Controller Board also includes Output 5, a general-purpose output, and Output 6, which is  
reserved by the system to control the boards’ RUN LEDs and thus is unavailable for user  
control.  
Reader LED, while it is an output, should never be used to control anything other than its  
associated reader’s LED.  
Table 6 lists the factory I/O board default settings for a door 2. These mappings should be used for the  
readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the board-to-board  
connector on the Controller Board.  
Table 6: Factory Default Configuration Settings for Door 2  
Type  
Purpose  
Web  
Default  
Name  
Terminal  
Block  
Label  
Reader A  
Reader B  
Other  
a
a
Input  
Egress/  
Request to  
Exit (REX)  
Input 9:  
Door 2  
Egress  
IO-TB2  
Input 9  
Input 9  
IN9 (REX)  
a
a
Door Status  
Input 10:  
Door 2  
Status  
IO-TB2  
Input 10  
Input 10  
IN10 (STS)  
Reader  
Tamper  
Input 11:  
Door  
IO-TB3  
TMPR A  
Input 11  
TMPR-A  
Reader  
Tamper  
Input 12:  
Door  
IO-TB4  
TMPR B  
Input 12  
TMPR-B  
a
a
Output  
Lock Relay  
Output #7  
IO-TB1  
LOCK  
Output 7  
Output 7  
a
a
Reader LED Output #8  
IO-TB3  
LED  
Output 8  
Output 8  
AUX Relay  
Output #9  
IO-TB1  
AUX  
Output 9  
a
a
Reader  
Buzzer  
Future  
Feature  
IO-TB3  
BZR  
Output 10  
Output 10  
a
Readers A and B share the same connection.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
Table 7 lists the factory Add-On Board default settings for a door 3. These mappings should be used  
for the readers, inputs, and outputs when either a 1- or 2-door Add-On Board is attached to the  
board-to-board connector on the controller board.  
Table 7: Factory Default Configuration Settings for Door 3  
Type  
Purpose  
Web  
Default  
Name  
Terminal  
Block  
Label  
Reader A  
Reader B  
Other  
a
a
Input  
Egress/  
Request to  
Exit (REX)  
Input 9:  
Door 2  
Egress  
IO-TB2  
Input 9  
Input 9  
IN9 (REX)  
a
a
Door Status  
Input 10:  
Door 2  
Status  
IO-TB2  
Input 10  
Input 10  
IN10 (STS)  
Reader  
Tamper  
Input 11:  
Door  
IO-TB3  
TMPR A  
Input 11  
TMPR-A  
Reader  
Tamper  
Input 12:  
Door  
IO-TB4  
TMPR B  
Input 12  
TMPR-B  
a
a
Output  
Lock Relay  
Output #11  
IO-TB5  
LOCK  
Output 11  
Output 11  
a
a
Reader LED Output #12  
IO-TB7  
LED  
Output 12  
Output 12  
AUX Relay  
Output #13  
IO-TB5  
AUX  
Output 13  
a
a
Reader  
Buzzer  
Future  
Feature  
IO-TB7  
BZR  
Output 14  
Output 14  
a
Readers A and B share the same connection.  
Notes:  
Reader LEDs, while they are outputs, should never be used to control anything other than their  
associated reader LEDs.  
Incorrect wiring of the reader to the panel can cause the panel to abnormally stop operating or  
to operate erratically.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
NetAXS-123 supports a variety of Wiegand reader models. Some readers have only one brown  
wire for LED control; others have two possible LED control inputs--orange for the green LED  
and brown for the red LED. RED is the normal state of the Reader LED operation. The LED  
turns GREEN for two seconds after a valid card read. Although readers operate similarly, LED  
control can vary, depending on the manufacturer. Therefore, your readers may require some  
testing to identify the right LED wire when the reader uses Dual LED wires. If you are using  
Dual Line LED control, it’s recommended that you try the ORANGE-colored wire for a  
GREEN LED.  
• The Reader Buzzer feature is not currently supported on the NetAXS-123 panels.  
3.5 Wiring Door Strikes  
Follow these steps to wire the door strikes to the Controller and Add-On Boards:  
1. Use the following figure to locate the door strike terminals on the board.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
2. Use the following figure to wire the door strike/mag lock according to the power supply used.  
Be sure to use the S4 suppressor kits as shown below.  
On-Board  
+12VDC  
Configuration  
External  
Power Supply  
Configuration  
+ DC  
OR  
S4  
S4  
S4  
S4  
DC  
Locking  
Device  
Locking  
Device  
Notes:  
As shown in the illustration above, the Dry C terminal for the On-Board option should  
not be connected. Similarly on the External Power Supply side, the Return terminal  
should not be connected.  
The On-Board option is used when jumpers are set for 12VDC. The External Power  
Supply options is used when the jumpers are set to External Power (see Jumper Settings,  
page 39 for details).  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
3.6 Setting DIP Switches and Jumpers  
3.6.1 Controller Board DIP Switch and Jumper Settings  
Figure 6 locates the NetAXS-123 DIP switch panel and the output 1 and output 3 relay jumpers.  
Figure 6: Controller Board DIP Switch and Jumper Location  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Installation  
DIP Switch Settings  
Use the following DIP switch configurations to set the panel address.  
Table 8: NetAXS-123 SW1 DIP Switch Settings  
a
b
b
S1  
S2  
S3  
S4  
S5  
S6  
S10 Selection  
S7  
S8  
S9  
ON  
OFF OFF OFF OFF  
Address 1  
(default)  
OFF ON  
ON ON  
OFF OFF OFF  
OFF OFF OFF  
Address 2  
Address 3  
Address 4  
Address 5  
Address 6  
Address 7  
Address 8  
Address 9  
Address 10  
Address 11  
Address 12  
Address 13  
Address 14  
Address 15  
Address 16  
Address 17  
Address 18  
Address 19  
Address 20  
Address 21  
OFF OFF ON  
ON OFF ON  
OFF ON  
ON ON  
OFF OFF  
OFF OFF  
OFF OFF  
OFF OFF  
ON  
ON  
OFF OFF OFF ON  
ON OFF OFF ON  
OFF ON  
ON ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF ON  
OFF ON  
OFF OFF ON  
ON OFF ON  
OFF ON  
ON ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF OFF OFF OFF ON  
ON OFF OFF OFF ON  
OFF ON  
ON ON  
OFF OFF ON  
OFF OFF ON  
OFF OFF ON  
ON OFF ON  
OFF ON  
OFF ON  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Installation  
Table 8: NetAXS-123 SW1 DIP Switch Settings (continued)  
a
b
b
S1  
S2  
S3  
S4  
S5  
S6  
S10 Selection  
S7  
S8  
S9  
OFF ON  
ON ON  
ON  
ON  
OFF ON  
OFF ON  
Address 22  
Address 23  
Address 24  
Address 25  
Address 26  
Address 27  
Address 28  
Address 29  
Address 30  
Address 31  
OFF OFF OFF ON  
ON OFF OFF ON  
OFF ON  
ON ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF ON  
OFF ON  
OFF OFF ON  
ON OFF ON  
OFF ON  
ON ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
Downstream  
Panel  
Gateway Panel  
(Default)  
OFF  
ON  
Uses the User  
Provided  
Ethernet IP  
address (Default)  
Uses the Default  
Ethernet IP  
Address  
(192.168.1.150)  
OFF OFF  
ON ON  
RS-485_1  
termination  
(EOL)  
DISABLED  
(Default)  
RS-485_1  
termination  
(EOL)  
ENABLED  
(Default)  
OFF Future Use  
(Default)  
ON Future Use  
a. DIP Switch 7 does NOT require a panel reboot to take effect. This does not affect  
the USB IP address.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
b. Both DIP Switch 8 and DIP Switch 9 need to be either ON or OFF to be properly  
configured.  
Table 9: NetAXS-123 SW2 DIP Switch Settings  
a
a
Selection  
S1  
S2  
OFF  
ON  
OFF  
ON  
RS-485_2 termination (EOL) DISABLED  
RS-485_2 termination (EOL) ENABLED (FUTURE) (Default)  
a. Both DIP Switch 1 and DIP Switch 2 need to be either ON or OFF to be properly  
configured.  
Note: When you use the DIP switches to reset a panel to the original factory default  
values, the Event History is lost and any customized databases are removed, so the  
panel is reset with the original factory default database. This does not affect the  
Ethernet IP address.  
You can also use this ASCII command:  
_I=pn_R  
This command resets the panel to the original factory default values, but it only  
removes the customized databases and restores the original factory default  
database. The Event History is retained.  
To reset the panel to the factory default values:  
1. Make a note of the existing settings on SW1 DIP switches.  
2. While the panel is powered up, turn all DIP switches to the OFF position.  
3. Power down, then power the panel back up.  
4. Wait for the panel to come up. The RUN LED should flicker fast.  
5. Set the DIP switches back to their original positions.  
6. Power down, then power the panel back up.  
7. After the the panel comes up, the RUN LED should flash normal.  
The panel is now reset to the original factory default values.  
Note: Address 0 is not a valid setting.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
Jumper Settings  
The NetAXS-123 Controller Board provides two jumper sets, one each for output relay 1 and output  
relay 3. Each relay has two 3-pin jumpers associated with it. One jumper selects either external power  
(EXT) or self-whetted (on-board, +12V) power to be applied to the relay contact load. The other  
jumper is used to select Normally Open (NO) or Normally Closed (NC) relay contacts. There is a total  
of four 3-pin jumpers (two per relay) on the Controller Board.  
Figure 7: NetAXS-123 Controller Board Jumpers  
Each relay is associated with two jumpers. As shown below, a relay’s left jumper configures the relay’s  
load source (12VDC or External), and the right relay jumper configures the relay contact type  
(Normally Closed or Normally Open).  
Setting the jumpers to configure the power source:  
12VDC  
External  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Installation  
Note: The power source selected by the jumper settings shown above configure the power source for  
the relay. It does not configure the power source for the panel.  
Setting the jumpers to configure the relay contact type:  
Normally Open  
Normally Closed  
3.6.2 Add-On Board DIP Switch and Jumper Settings  
Figure 8 locates the NetAXS-123 Add-On Board DIP switch panel and the output 1 and output 3 relay  
jumpers.  
Figure 8: Add-On Board DIP Switch and Jumper Location  
Note: The figure above shows a one-door Add-On Board configuration. If you are instead using a  
two-door Add-On Board, you will see an additional two relays (and their corresponding jumper sets) to  
the right of the relays shown. The additional relays and jumpers will configure output 11 and output 13,  
and all of the jumpers are configured in the same manner.  
The NetAXS-123 Controller Board provides two jumper sets, one each for output relay 1 and output  
relay 3. Each relay has two 3-pin jumpers associated with it. One jumper selects either self-whetted  
(on-board, +12V) or external power (EXT) to be applied to the relay contact load. The other jumper is  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Installation  
used to select Normally Open (NO) or Normally Closed (NC) relay contacts. There is a total of four  
3-pin jumpers (two per relay) on the controller board.  
Setting the jumpers to configure the power source:  
12V  
External  
Setting the jumpers to configure the relay position:  
Normally Open  
Normally Closed  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
3.7 Communications  
3.7.1 USB Communications  
The NetAXS-123 Controller Board provides a version 2.0 USB port that connects to the web browser  
or to a WIN-PAK host. The following figure identifies the location of the port on the board.  
Note: USB communication requires the USB A to MicroUSB B cable that is supplied with the panel.  
You will need to install a USB driver to support the connection. Follow these steps:  
Warning: Do NOT connect the USB cable to the panel until AFTER the drivers are installed.  
1. Insert the NetAXS-123 Product CD into your Windows-based computer. The NetAXS-123  
product menu opens in the web browser.  
Note: If the product menu does not open automatically in your browser, right click on the Start button  
and select Explore. In the folder tree, find and click the CD drive that is reading the NetAXS-123  
Product CD.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Installation  
2. Click Install USB Drivers on the product menu to start the USB driver installation wizard.  
3. Click Next to display the Ready to Install the Program screen.  
Note: If confirmation dialog boxes pop up before or during the installation, click the  
appropriate boxes to allow or approve the installation.  
4. Click Install to initiate the installation.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the NetAXS-123 Panels  
Installation  
5. When the installation is complete, the closing screen appears:  
6. Click Finish.  
7. Connect the computer to the NetAXS-123 controller with a USB-A to Micro USB-B cable.  
8. Turn on the power to the NetAXS-123 controller.  
3.7.2 RS-485 Communications  
If a NetAXS-123 panel is to be placed onto a prexisting RS-485 dropline loop (NetAXS) it must be  
setup as the Gateway panel. The interface allows the wiring of a Multidrop communication network of  
up to 4,000 feet (1200 m) in length. Only one host converter device per dropline is supported.  
Note: NetAXS-123 must be the Gateway panel on an existing NetAXS loop. The NetAXS-123 panel  
cannot be placed as a Downstream panel when the Gateway is a NetAXS system.  
DIP switch position 6 on the NetAXS-123 panel selects whether the panel is a Gateway or  
Downstream panel. The switch in the OFF position configures the panel as a Downstream panel; ON  
configures a Gateway. The panel must be power cycled for a new switch setting to be recognized. DIP  
switch positions 1-5 are used to select the panel’s address on the network. Refer to Table 8 for DIP  
switch setting information.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
DIP switch SW1 positions 8 and 9 are provided for supplying biasing and end-of-line termination for  
the RS-485 network. The board ships with the switches active. For a Multidrop RS-485 Line, you must  
turn ON both switch positions 8 and 9 of SW1. (terminated and biased) at the two end-point panels. At  
all other panels, set DIP switches 8 and 9 in the OFF position. Both switches on a given panel must be  
set the same. Note that biasing and termination on both ends are present. Use the SW1 positions 8 and  
9 ON on both ends of the RS-485 network.  
Note: For more information on end of line (EOL) termination, contact Honeywell technical support.  
Note: If an RS-485 network has a NetAXS-123 Gateway panel, no N1000-II, N1000-III, N1000-IV, or  
NS2 are allowed on the same network. If they are added to a network with a NetAXS-123 Gateway  
panel, they will not be able to communicate with the host computer. In order to use these panels, a  
N-485-PCI-3 is required, as shown in Figure 9.  
Figure 9: RS-485 Configuration via N-485-PCI-3  
This configuration supports a combined total of 31 N1000 III, N1000 IV, NetAXS, NetAXS-123, and  
NS2 panels per Multidrop line.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
Figure 10: RS-485 Configuration via NetAXS-123 Gateway  
Reader 1  
Ethernet  
.
.
.
Terminal  
RS-485 Multidrop Line  
.
.
.
.
.
.
.
.
.
Reader 4  
Reader 3  
Reader 4  
This configuration supports a total of 31 NetAXS and NetAXS-123 panels per Multidrop line.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Installation  
3.7.3 Ethernet TCP/IP Communications  
Figure 11: Ethernet TCP/IP Configuration  
Network Interface Card  
inside PC  
Up to 25E5pTteChrPSe/yIrPsntCeemontnections  
Terminal  
Reader 1  
Ethernet 10/100  
.
.
.
NetAXS-123  
Gateway  
RS-485 Multidrop Line  
Reader 3  
Reader 1  
Reader 1  
Reader 1  
.
.
.
.
.
.
.
.
.
NetAXS  
Panel  
NetAXS-123  
Panel  
NetAXS  
Panel  
Reader 4  
Reader 3  
Reader 4  
This configuration supports a total of 31 NetAXS and NetAXS-123 panels per Multidrop line.  
Each NetAXS-123 panel has a port for an Ethernet TCP/IP interface. The Ethernet TCP/IP interface  
provides 10/100 MB Ethernet support for each panel.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.0 System Configuration  
This section provides wiring diagrams for each of the NetAXS-123 system configurations.  
4.1 Ethernet Connection  
Figure 12: Ethernet Connection  
NIC  
100BaseT (CAT 5) 328 Ft. Max.  
EG  
EG  
EG  
EG  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
S7: OFF  
S8-S9: ON: 485 Termination ON  
S7: OFF  
S8-S9: ON: 485 Termination ON  
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
System Configuration  
4.2 USB Connection  
Figure 13: NetAXS-123 USB Connection  
Note: The USB connection is intended to be used for system maintenance and troubleshooting.  
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.3 RS-485 Connection via PCI-3  
This connection supports thirty-one NetAXS-123 panels for each drop line. Note that PCI-3 units can  
also be wired in interior, as well as in endpoint, positions. See Figure 16 on page 52 and Figure 17 on  
Figure 14: RS-485 Connection via PCI-3  
RS-232 (50 Ft. Max.)  
RS-485 (4000 Ft. Max.)  
Terminal  
S2 - ON  
S3 - ON  
See RS-485  
Cable note  
EG  
Only Earth Ground (EG) one side of cable  
EG  
EG  
Note: If you use the PCI-3 connection, you cannot access the web, since the PCI-3 does not support the  
NetAXS-123 web interface.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.4 RS-485 Connection via NetAXS-123  
This connection supports a total of 31 NetAXS-123 panels (including the Gateway) for each drop line.  
Figure 15: RS-485 Connection via NetAXS-123  
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.5 RS-485 Connections with Multidrop Panels at Both Ends of the Cable  
You can connect Multidrop panels at both ends of an RS-485 cable via either a NetAXS-123 panel or a  
PCI-3 device.  
Figure 16: RS-485 Connection via NetAXS-123 with Multidrop Panels at Both Ends  
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
Figure 17: RS-485 Connection via PCI-3 with Multidrop Panels at Both Ends  
See RS-485  
Cable Note  
RS-232 (50 Ft. Max.)  
COM Port  
RS-485 (4,000 Ft.)  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
S7: OFF  
S7: OFF  
S7: OFF  
S7: OFF  
S8-S9: ON: 485  
Termination ON  
S8-S9: OFF: 485  
Termination OFF  
S8-S9: ON: 485  
Termination ON  
S8-S9: OFF: 485  
Termination OFF  
EG  
Only Earth Ground (EG)  
one side of cable  
Only Earth Ground (EG)  
one side of cable  
EG  
EG  
EG  
EG  
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
System Configuration  
4.6 M-56K Dial-up Modem, RS-485 Connection via Hub (PCI-3)  
This configuration supports 31 NetAXS-123 panels for each drop line.  
Figure 18: M-56K Dial-up Modem, RS-485 Connection via Hub  
M-56K  
FAX/MODEM  
COM Port  
Straight Through Cable  
Male 25 Pin  
Analog  
Phone  
Line  
Remote DIP Switch Set
(1, 3, 8 ON) (2, 4, 5, 6, 7
Female 9 Pin  
Terminal  
(RX) 2  
(TX) 3  
3 (RX)  
2 (TX)  
Dedicated  
analog  
phone  
(Comm) 5  
7 (Comm)  
M-56K  
FAX/MODEM  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
DIP Switch Settings  
S1-S5 Panel Address  
S6: OFF  
S7: OFF  
S7: OFF  
S8-S9: ON: 485  
Termination ON  
S8-S9: OFF: 485  
Termination OFF  
Only Earth Ground (EG)  
one side of cable  
EG  
EG  
It is recommended to Earth Ground (EG)  
each NetAXS enclosure Individually  
DB 9 / DB 25 Connectors  
RS-485 Cable  
Female  
Male  
NetAXS-123 Panels  
13  
25  
13  
1
1
C-TB9 - A  
C-TB9 - B  
C-TB9 - COM  
25  
5
14  
14  
1
5
1
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with  
shield, 120 ohm, 23 pf (HAS part no. NCP2441-TN)  
9
6
9
6
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.7 Fiber Converter to RS-485 Connection via PCI-3  
This connection supports 31 NetAXS-123 panels for each drop line.  
Figure 19: Fiber Converter to RS-485 Connection via PCI-3  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.8 Fiber Converter to RS-485 Connection via NetAXS-123  
This connection supports 31 NetAXS-123 panels for each drop line.  
Figure 20: Fiber Converter to RS-485 Connection via NetAXS-123  
Note: You should ground each NetAXS-123 Standard (Metal) Enclosure panel individually with an  
Earth Ground.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.9 N-485-PCI-3/NetAXS-123 Access Controller Panel Connection Detail  
Figure 21: N-485-PCI-3/NetAXS-123 Access Controller Panel Connection Detail  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.10 NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail  
Figure 22: NetAXS-123/NetAXS-123 Access Controller Panel Connection Detail  
DIP Switch Settings  
S1-S5: Panel Address  
S6: ON: GATEWAY  
S7: OFF  
S8-S9 ON: 485 Termination ON  
Ground Shield  
NetAXS-123  
C-TB9  
DO NOT CONNECT or  
X
NetAXS-123  
C-TB9  
GROUND SHIELD  
DC Out  
485 +  
A
NetAXS-123  
C-TB9  
485 -  
B
DC Out  
485 +  
485 Com  
COM  
A
DC Out  
485 -  
485 +  
485 -  
+24VDC in  
B
A
485 Com  
COM  
B
485 Com  
+24VDC in  
COM  
+24VDC in  
DIP Switch Settings  
DIP Switch Settings  
S1-S5: Panel Address  
S6: OFF  
S7: OFF  
S1-S5: Panel Address  
S6: ON: GATEWAY  
S7: OFF  
S8-S9 OFF: 485 Termination OFF  
S8-S9 ON: 485 Termination ON  
Ground only one  
side of cable shield  
Shield  
485 Common  
485 -  
485 +  
4,000 ft.(1,200 m) max,24 AWG,2 twisted pairs with  
shield,120 ohm,23 pf (HAS part no.NCP2441-TN)  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
System Configuration  
4.11 Mixed Loops  
This mixed-loop configuration supports a combined total of 31 N1000 III, N1000 IV, NetAXS,  
NetAXS-123, and NS2 panels per Multidrop line.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Hardware Specifications  
5.0 Hardware Specifications  
The specifications in this section apply to both the Standard Enclosure and Compact Enclosure panels.  
5.1 Relay Contacts  
Maximum of six Form-C SPDT relays, 3A (at dry contact) or 0.5A (at self-whetted) @ 30VDC (PTC  
limited in the self-whetted mode). The Form-C SPDT relays are configured as Normally Open or  
Normally Closed outputs only. Normally Open and Normally Closed contacts cannot be used  
simultaneously.  
5.2 Reader Interface  
Reader Power: 12VDC nominal with 500mA maximum for each reader port.  
Reader LED Output: Open collector driver capable of sinking up to 8mA.  
Reader Tamper: Supervised or non-supervised input.  
Reader Data Input: TTL compatible inputs.  
5.3 Maximum Output Loading  
Use the following guidelines unless you are using Power Over Ethernet (PoE):  
• Maximum current per reader port for any of the three reader outputs is 500mA.  
Maximum current for any of the six relay outputs on the Songchuan 892N-1CH-1F-V is 3A at  
dry contact, or 0.5A at self-whetted.  
• Maximum battery charge current for the battery wired in series is 250mA.  
External power on C-TB9 is limited to 1.5A @ 12VDC.  
5.4 PoE Power Limitations  
If you are using the NetAXS-123 Standard Enclosure and powering the panel with PoE (Power over  
Ethernet), you must comply with these specifications for proper operation:  
• A NetAXS-123 panel powered by PoE is 802.3af compliant, providing a maximum of 15.4W  
of input power to the panel. This input power is split between on-board power consumption and  
external load consumption. A maximum current capacity of 450 mA @ 12VDC is available for  
all external devices combined.  
Notes:  
Two readers per door can still be supported as long as the total current is within the  
external load capacity stated above.  
You can either find the devices’ power consumption amounts by referring to the  
products’ documentation or by using a current meter.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Installing the NetAXS-123 Panels  
Hardware Specifications  
Example:  
Device Element  
Current  
Door strike or magnetic  
lock current  
250 mA  
Reader A maximum  
current  
50 mA  
50 mA  
Reader B maximum  
current  
Buzzer or sounder current  
Door position switch  
Request to exit switch  
20 mA  
20 mA  
30 mA  
420 mA  
Total current for this  
example  
If the total current consumption of your external devices exceeds the 450mA maximum current  
maximum, then use one of the following system configurations:  
Power the panel with an external 12VDC power supply.  
Power some or all of the external devices with an external power supply to lower the  
total external current powered by the NetAXS-123 panel below 450mA.  
The maximum power available in the 802.3af standard is 15.4W. This limit is generally at  
48VDC, and it is measured at the output of the power injector or PoE switch. Line losses cause  
a decrease in the power available at the panel when you use longer Ethernet cable lengths. You  
can minimize these line losses by using either of the following methods:  
Connecting the NetAXS-123 panel to the power injector or PoE switch with the shortest  
possible Ethernet cable length.  
Using a high-power 802.3at power injector or PoE switch with a voltage of 56VDC. This  
reduces line losses and thus increases available power at the NetAXS-123 panel.  
Note: The NetAXS-123 panel will not benefit from the increased power capabilities of a  
high-power 802.3at power injector. Its use only reduces line losses over the Ethernet  
cable.  
5.5 Mechanical  
Standard Enclosure dimensions: Height = 14 inches (355.6 mm), Width = 12 inches (304.8  
mm), and Depth = 5 inches (127 mm).  
Compact Enclosure dimensions: Height = 7.5 inches (190.5 mm), Width = 7.5 inches (190.5  
mm), and Depth = 2.25 inches (57.15 mm).  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Hardware Specifications  
5.6 Environment  
• Temperature: 0C to 49C operating, -55C to +85C storage.  
Humidity: 5% to 85% RHNC.  
5.7 Cable  
Use industry-standard cables that meet the following specifications:  
Table 10: Reader Wiring  
Cable Specifications  
Description  
AWG  
Maximum Distance:  
Feet (Meters)  
Readers  
6 Conductor, Shielded  
Twisted Pair, Shielded  
Twisted Pair, Shielded  
18  
18  
18  
500 (153)  
Alarm Input  
Relay Outputs  
2,000 (610)  
2,000 (610)  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Basic Standalone Operation  
6.0 Basic Standalone Operation  
6.1 Card Read / Door Lock Operation  
1. Present a card to a reader.  
2. The reader sends the card number to a reader input on the panel.  
3. The panel searches its database and:  
If it is a valid card, then energize the door relay associated with the particular reader  
input. The card is valid when it is in the card database on the panel and the current time  
and date conforms to the time zone associated with the card.  
If it is not a valid card, the door relay remains locked.  
6.2 Door Egress / Door Lock / Door Status Operation  
1. Activate the door egress input.  
2. The panel energizes the door relay associated with the particular door egress input for a default  
time of 10 seconds.  
3. If the door status goes from close to open to close again during the 10 second door open period,  
the door relay will be immediately de-energized.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Maintenance  
7.0 Maintenance  
Perform the following maintenance on the NetAXS-123 enclosure:  
• Change the backup battery every two to two-and-a-half years.  
• Oil the lock once per year.  
Use the following procedure to change the 1A, 250V, Bussan type GMA fuse in the fuse  
terminal block Power Supply module.  
Warning: Be sure to disconnect the AC power before replacing the terminal block fuse.  
Warning: To reduce the risk of fire, replace the fuse only with a 1A, 250V, Bussan type GMA  
fuse.  
1. Disconnect the AC power.  
2. Replace the fuse with a new 1A, 250V, Bussan type GMA fuse.  
3. Re-connect the AC power.  
Note: The power supply contains no serviceable parts. There is no replaceable fuse inside the  
power supply.  
• Use the following procedure to change the 1A, 250V, Bussan type GMA fuse in the power inlet  
terminal block.  
Warning: Be sure to disconnect the AC power before removing the fuse holder from the power  
inlet terminal block.  
Warning: To reduce the risk of fire, replace the fuse only with a 1A, 250V, Bussan type GMA  
fuse.  
1. Disconnect the AC power.  
2. Remove the fuse holder from the power inlet terminal block to identify the location of the  
power inlet terminal block).  
3. Replace the blown fuse in the lower section of the fuse holder with the new fuse. The  
upper section of the fuse holder provides a convenient location for a spare fuse.  
4. Slide the fuse holder back into the power inlet terminal block.  
5. Re-connect the AC power.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installing the NetAXS-123 Panels  
Troubleshooting  
8.0 Troubleshooting  
Table 11 Troubleshooting Problems and Solutions  
Problem  
Solution  
The panel  
Ensure that the Address DIP switches are set to a value other than zero.  
powers up, but it Turn off the power (including battery), change the settings, and re-apply  
does not respond the power.  
to any  
communication,  
cards reads, or  
input activation.  
No  
Only a panel set to be a Gateway (DIP switch 6 = ON) will have  
communications communications on the Ethernet port. If you need to use that port to  
exist with the  
Ethernet port.  
access the panel, turn off the power (including the battery), change the  
switch setting, and reapply the power. Note that if the panel is normally  
not a Gateway on a Multidrop communication bus, then the Host  
RS-485 connection (C-TB9) should also be disconnected while DIP  
switch 6 is ON. After completion of the Ethernet session, turn off the  
power (including the battery), change the switch setting, re-connect the  
Host RS-485 terminal block, and re-apply the power.  
The panel  
address is  
unknown.  
Option 1: Set the NetAXS-123 panel’s DIP switch 7 to ON. This will  
default the IP address to 192.168.1.150.  
Option 2: Connect to the panel through the USB port using the provided  
USB A to MicroUSB B cable and the USB driver on the product CD.  
The default USB Ethernet IP address is: 192.168.2.150.  
The N1000 and  
NS2 panels on  
the Multidrop  
bus do not  
N1000 and NS2 panels are not supported downstream from a  
NetAXS-123 panel. To enable the NetAXS-123 to communicate with  
the N1000 and NS2 panels, the loop must be configured with an  
N-485 PCI-3 as the Gateway. However, in this configuration, web  
functionality is lost. It is recommended that the user swap-out N1000  
and NS2 panels with NetAXS-123 panels.  
report.  
Note: The NetAXS-123 EOL network is AC-coupled. There is no resistance  
difference between the RS-485 positive and negative terminals if the EOL network is  
on or off (SW1, switches 8 and 9).  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installing the NetAXS-123 Panels  
Technical Support  
9.0 Technical Support  
9.1 Normal Support Hours  
Monday through Friday, 7:00 a.m. to 7:00 p.m. Central Standard Time (CST), except  
company holidays: (800) 323-4576.  
9.2 Web  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installing the NetAXS-123 Panels  
Technical Support  
This page is left blank for printing purposes.  
NetAXS-123 Access Control Unit Installation Guide, Document 800-05779, Revision A  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Honeywell Access Systems  
135 W. Forest Hill Avenue  
Oak Creek, WI 53154  
United States  
Specifications subject to change  
without notice.  
800-323-4576  
414-766-1798 Fax  
© Honeywell. All rights reserved.  
Document 800-05799, Revision A  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Jumper 1762254 User Manual
Graco Heat Pump 223177 User Manual
Haier Microwave Oven EA 1770EG User Manual
Hamilton Beach Iron 14960 User Manual
Harman Stove Company Stove Advance Pellet Stove User Manual
Heath Zenith Universal Remote UT 6028 BZ User Manual
Hoshizaki Ice Maker F 500BAF C User Manual
Hotpoint Range RGB532BEAAD User Manual
Hunter Fan Outdoor Ceiling Fan ME003 01 User Manual
Husqvarna Chainsaw 1152353 95 User Manual