Installation & Operating Manual
The Harman Advance Pellet Stove
R8
“Ce manuelest disponibleen Françaissur demande”
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUALBEFORE YOUINSTALL AND USE YOURNEW ROOM HEATER. FAILURE TO
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTYDAMAGE, BODILYINJURY, OR EVEN DEATH.
FOR USE IN THE U.S.AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES
IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED,AHOUSEFIREMAYRESULT. FORYOURSAFETY, FOLLOW
INSTALLATIONDIRECTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION
REQUIREMENTS INYOUR AREA.
CONTACT YOUR LOCAL AUTHORITY (SUCHAS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE
PREVENTION BUREAU,ETC.) TO DETERMINE THENEED FORA PERMIT.
CETTEGUIDE D'UTILISATIONEST DISPONIBLEENFRANCAIS.CHEZVOTRECONCESSIONNAIRE DEHARMANSTOVE
COMPANY.
SAVETHESEINSTRUCTIONS.
Download from Www.Somanuals.com. All Manuals Search And Download.
Automatic Ignition/Operation
TheAdvance pelletstove is more thanjust automatic ignition, itis also automatic temperature
control. The automatic system will allow the fire size to be adjusted to match the heating
needs and even put the fire out if necessary. If heat is needed after the fire is out, the
Advance will automatically re-ignite and adjust the fire size to match the heating need. The
totally automatic room sensor mode is recommended because of its efficiency.
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.
Igniter switch to "AUTO"
Room Temperature Mode
In "Room Temp Mode" heat output is controlled au-
tomatically by the Room Sensing Probe. When the Room
Sensing Probe calls for heat, the stove will increase out-
put. When the Room Sensing Probe is getting close to
the set temperature, the stove will begin to level off out-
put and keep the fire burning at just the right temperature
to maintain that setting.
High output is determined by the feed rate set-
ting. This setting, generally on #4, can be increased if
higher burn rates are necessary. The unit's maximum
burn rate should not create less than 1" of ash on the
burn pot front edge. See Fig.2, Page 4. Overfeeding is
not a safety concern, but fuel may be wasted if unburned
Room Temperature Mode: This setting will producea room
temperature of 70 degrees with the distribution blower at
medium speed.
pellets fall into the ash pan.
In "Room Temp Mode" a constant fuel consumption
rate is sacrificed for exact room temperature. Therefore,
as it gets colder more pellets will be burned automati-
cally.
Stove Temperature Mode
The distribution blower speed will vary according to
the position of the mode selector pointer, and fire size.
Igniter switch to "AUTO"
Stove Temperature Mode
This allows for automatic ignition upon start-up only.
The unit can then be set at any desired setting. The heat
output and fuel consumption will remain constant regard-
less of room temperature. The unit's maximum feed rate
should not create less than 1" of ash on the burn pot front
adge. See Fig 2, Page 4.
This setting will produce medium heatwith the
distribution blower on "low".
The unit's low burn or maintenance setting is as
low as it will go. It will not go out unless it runs out of
fuel or is turned off.
Shut-Down Procedure
To kill the fire or stop burning the stove, turn the Mode Selector to
"OFF". This will causethefiretodiminishand burnout. Whenthe fireburns
out andthestovecoolsdowneverythingwill stop.
If you pull the plug toshut down the stove, all motors will stop. This
may causeincompletecombustionandsmokeinthefirebox. If theloaddoor
isopened thesmokemayescape.
Thebest waytoshut downthestoveis simplylet it runout of pellets,
thenthe stove will shut down automatically.
This setting willproduce continuous maximum heat
output with the distribution blower atfull speed.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Automatic Start Up
Starting First Fire
Igniter Switch to"AUTO"(up position)
Make sure the unit is plugged into a 120 VAC,
60 HZ electrical source. The power light should be the
only light lit.
1. Turn Mode Selector to "OFF".
2. Fill hopper with pellets.1
See Note 7.
1"
Fig. 1
3. Clean burn pot with scraper, if necessary.5
4. If starting after an empty hopper, turn Feed
Adjuster to "TEST" (for one 60 second cycle).2 This
will purge pellets into the auger tube and also allow
you to check the motors for operation. NOTE: The
auger motor will not operate with the view door or
ash pan door open.3
Fig. 2
4
5. Turn Feed Adjuster to #4.
6. Flip theIgniter Switch up into the"AUTO" position.
7. Turn the Temperature Dial to desired room
temperature.
1.Fines are small pieces ofbroken pellets (sawdust). Finesdo not
flow easily and often build upon the hopper funnelbottom angles.
These fines can be pushed into the feeder opening and then fill
the hopperwith pellets. As the system works,they will be burned.
2. The "TEST" cycle will operate the feeder motor forexactly one
minute. Turning to "TEST" again and again may purge too much
fuel into the burn potcausing excessive smoke on start-up.
3.Thefirebox low pressure switch will notallow theauger motoror
the igniter elementto operate if the view door orthe ash pan door
are open.
8. Turn Mode Selector toRoomTemperatureor Stove
Temperature.
9. Fill hopper with pellets and remove ashes as
required.6
4.Adjust Feed Rate.If this isyour first fire or youare trying different
pellets, set the feed adjuster to #4, Fig. 1. This is a conservative
number andwill probably need to be increased. Afteryou know a
feed rate setting that works well, use that setting. Remember, if
your feed rate is too high you may waste fuel.
5. This is usually a weekly maintence procedure. Cleaning the
burn pot with the scraper with a small amount of new fuel in the
bottom is nota problem. First, scrape the ashes on the frontof the
burn potinto the ash pan.Then scrape the holed surface downward
into theburn pot.When the stove is ignited these scrapings will be
pushed out by the feeder.
Battery Back Up
If a power outage is expected, switch the toggle switch
to Manual Mode. The Harman 502H Battery Back Up
is incapable of powering the igniter. If an automatic
ignition is attempted while the stove is being powered
by the battery back up, it may cause damage to both
the stove and the battery back up unit.
CAUTION
6. The ash pan can hold the ashes from approximately 1 ton of
premium fuel.This means the asheswill only need to be emptied
a few times a year.
The stove is hot while in operation.
Keep children, clothing and furniture away.
Contact may cause skin burns.
7. Setting the feed adjuster # for maximum burn: With the unit
burning in "AUTO",turn to "Stove Mode"and putthe fan on "H". Set
the Temperature Dial to #7. Allow the unit to burn for about 30
minutes andcheck ash on frontof burn pot. Fig.2.If the ash line is
larger than 1", turn the feed adjuster from #4 to #5. Allow another
30 minutes of burn time and check again.If , at #6 setting, a 1" or
less ash bed is notobtainable, itis not a problem. The 1" ash bed
is only a maximum burn rate and at most normal settings the ash
bed will be larger.
Warning
"NEVERUSE GASOLINE,GASOLINE-TYPE LANTERN
FUEL, KEROSENE,CHARCOAL LIGHTER FLUID, OR
SIMILAR LIQUIDS TO START OR "FRESHEN UP " A
FIRE IN THIS HEATER. KEEP ALL SUCH LIQUIDS
WELL AWAY FROM THE HEATER WHILE IN USE".
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Manual Ignition/Operation
The Advance Pellet Stove is capable of manual operation. This also allows the operator
to manually control operation during an emergency (i.e. igniter failure, when using a 502H
battery backup, or when using certain generators.)
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.
NOTE: When starting the unit in the "AUTO"
mode and switching to "MANUAL", the fire must be
large enough to start the distribution blower. The
starting of the blower is a signal that the start cycle
is completed and the fire will not go out.
Igniter Switch to "MANUAL"
Room Temperature Mode
The fire will have to be lit with starting gel and a
match, or started automatically, see "Automatic Opera-
tion". Turn to "Manual" position when the fire is estab-
lished.
The difference between "AUTO" Room Tempera-
ture Mode and "Manual" Room Temperature Mode is
that the fire willnot go out as the roomtemperature goes
above the control board setting. The unit can only go to
Room Temperature Mode: This setting will produce a
low burn and will remain there until it runs out of fuel or
until more heat is needed and the feed rate increases.
Feed rate adjustments and dial settings are the same
as "AUTO" settings.
roomtemperature of70 degrees with thedistribution blower
atmedium speed.
Manual Stove Temperature Mode
Igniter Switch to "MANUAL"
Stove Temperature Mode
The advantage of this mode is to allow the opera-
tor to have a large viewing fire without blowingextra heat
into the room.
During operation, with the temperature dial set at
#5 or less, the distribution fan will not operate. A #5 on
the temperature dial and a #5 on the feed adjuster is
approximately 80% output. It is not necessary to oper-
ate the distribution blower below this point. Therefore,
there can be a higher feed rate ( a larger viewing fire)
without an excess of hot air blowing into the room.
An example of when to use the Manual Stove Tem-
perature Mode is if you want to watch a large fire and
the room is aleady up to temperature. The Stove Tem-
perature Mode allows you to have a larger fire and a
lower sound level, without the distribution blower.
NOTE: During the useof this mode, if you keep
increasing the temperature dial setting to increase
the fire size, the distribution blower will automati-
cally come on when the ESP Temperature reaches
350o F, or 81%output.
This setting will producea largeviewing firewithouta
distribution blower operating.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Manual Start Up
Starting First Fire
Igniter Switch to"MANUAL"
Fig. 4
(down position)
Make sure the unit is plugged into a 120 VAC, 60 HZ
electrical source. The power light should be the only
light lit.
Fig. 3
See Note
7.
1"
1. Turn FEED ADJUSTER to desired feed rate.
4
No. 4 is good for most pellets.
2. Turn the MODE SELECTOR to “OFF” and
then to the desired mode. This will reset con-
trol and start the combustion motor.
3. Turn the TEMPERATURE DIAL to the desired
setting.
Fig. 5
5
4. Clean burn pot with scraper if necessary.
5. Fill burn pot with pellets, only level with front
edge. (Do Not Over Fill).
1.Fines are small pieces ofbroken pellets (sawdust). Finesdo not
flow easily and often build upon the hopper funnelbottom angles.
These fines can be pushed into the feeder opening and then fill
the hopperwith pellets. As the system works,they will be burned.
2. The "TEST" cycle will operate the feeder motor forexactly one
minute. Turning to "TEST" again and again may purge too much
fuel into the burn potcausing excessive smoke on start-up.
3.Thefirebox low pressure switch will notallow theauger motoror
the igniter elementto operate if the view door orthe ash pan door
are open.
4.Adjust Feed Rate.If this isyour first fire or youare trying different
pellets, set the feed adjuster to #4, Fig. 3. This is a conservative
number andwill probably need to be increased. Afteryou know a
feed rate setting that works well, use that setting. Remember, if
your feed rate is too high you may waste fuel.
6. Add starting gel on top of the pellets.Stir gel
into pellets for fast lighting.
7. Light starting gel with a match, and close the
door. Operation will begin when the fire reaches
the proper temperature.3
8. Fill hopper with pellets and remove ashes as
required.1, 6
5. This is usually a weekly maintence procedure. Cleaning the
burn pot with the scraper with a small amount of new fuel in the
bottom is nota problem. First, scrape the ashes on the frontof the
burn potinto the ash pan.Then scrape the holed surface downward
into theburn pot.When the stove is ignited these scrapings will be
pushed out by the feeder.
6. The ash pan can hold the ashes from approximately 1 ton of
premium fuel.This means the asheswill only need to be emptied
a few times a year.
7. Setting the feed adjuster # for maximum burn: With the unit
burning in "AUTO",turn to "Stove Mode"and putthe fan on "H". Set
the Temperature Dial to #7. Allow the unit to burn for about 30
minutes andcheck ash on frontof burn pot. Fig.5.If the ash line is
larger than 1", turn the feed adjuster from #4 to #5. Allow another
30 minutes of burn time and check again.If , at #6 setting, a 1" or
less ash bed is notobtainable, itis not a problem. The 1" ash bed
is only a maximum burn rate and at most normal settings the ash
bed will be larger.
CAUTION
The stove is hot while in operation.
Keep children, clothing and furniture away.
Contact may cause skin burns.
Warning
"NEVERUSE GASOLINE, GASOLINE-TYPE LANTERN
FUEL, KEROSENE,CHARCOAL LIGHTER FLUID, OR
SIMILAR LIQUIDS TO START OR "FRESHEN UP " A
FIRE IN THIS HEATER. KEEP ALL SUCH LIQUIDS
WELL AWAY FROM THE HEATER WHILE IN USE".
6
Download from Www.Somanuals.com. All Manuals Search And Download.
ESP Control
Power Light
Indicates power to the
control.
Feed adjuster
Sets the maximum
feed rate
Test
Runsallmotorsatfull
speed forone minute
to check operation.
After twominutes the
stove will go to
minimum burn and
the blowers will
alternate fromhigh to
low every minute to
remind you that you
are still in "Test
Mode".
Status Light
Will be lit in either stove
orroom tempmode when
pointer is notwithin off
positionband except
after normalshutdown.
Blinks to indicate errors
listed below.
Indicates power to
distribution blower.
Igniter switch
Setto appropriate
Start-Up mode.
Indicates power to
combustion blower
Distribution Blower
speedadjustmentrange.
L = low
H = high
Indicates power to the
feed motor.
Variablespeedanywhere
between L and H;
although as the stove
temp. goes up ,so does
the lowend ofthe scale.
Indicates power to the
igniter.
Mode Selector
Temp dial
Dealer Diagnostic Port
Allows you to choose between
RoomTemp Mode,StoveTemp
Mode, orOFF.Alsoallows you
to vary the distribution blower
speed by turning the knob to
the high or low side of each
mode.
Allows you to adjustthe room temperature in Room
For dealermaintenance only.
Requires specialDDMmonitor
supplied to Harman Dealers
exclusively.
Temp Mode using the outerscale markedin degrees
Fahrenheit. It also allows you to adjustthe stove
temperature while in StoveTemp Mode using the
inner scale marked from 1 to 7.
Status light error messages:
1 Blink: Indicates control board self diagnostic failure.
This requires a manual reset*.
3 Blinks: Indicates ESP (Exhaust Sensing Probe) fail-
6 Blinks : Indicates that the control has calculated poor or
incomplete combustion occurring for more than 50 min-
utes. See Troubleshooting section for more details.
A six blink status may be set if the stove is allowed to run
out of pellets. To reset, turn mode selector to "OFF" then
back on to the desired mode. If the unit was not out of pel-
lets, see Troubleshooting section for more details.
* Manual reset- disconnectpower cord for a fewseconds
and reconnect. If error still occurs call your Dealer.
NOTICE: Whenpower is givento the stove, the controlboard
willblinkafewtimestoindicate currentversionofcontrolboard.
This should not be confused with error messages.
ure. This requires a manual reset*.
4 Blinks: Can occur only in Room Temp Mode and indi-
cates Room Sensing Probe failed or not installed. If a
Room Sensing Probe is then installed, the status light
will automatically reset.
NOTE: Unit will not start in "AUTO" with this status error.
5 Blinks (In Igniter Auto. Mode Only): Indicatesthatthe
unithas failedto light after 4 consecutive igniter cycles, 32
minutes total. To reset-TurnMode Selector to "OFF", then
turn to either mode again.)
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
WheninstallingandoperatingyourHarmanAdvance
Pellet Stove, respect basic safety standards. Read these
instructions carefullybefore youattempt to installor oper-
ate the Advance. Failure to do so may result in damage to
property or personal injuryand mayvoid the product war-
ranty.
7"
Consult with your local building code agency and in-
surance representative before you begin your installation
to ensure compliance with local codes, including the need
for permits and follow-up inspections.
7"
Several issues must be addressed when selecting
a suitable location for yourAdvance Pellet Stove. Observ-
ingrequiredclearances tocombustible materials,the prox-
imity to a safe chimneyor venting system, andthe acces-
sibility of electrical supply must all be considered. In addi-
tion, selecting a location that takes advantage of the
building's natural air flow is also desirable to maximize
the heating effectiveness of the heater. In many cases,
this is a central location within the building.
Fig.6
1"
Adequate combustionandventilationair mustbe pro-
vided.
Place the stove ona noncombustible floor or UL ap-
provedfloor protector that extends 6 inches to the front, 6
inches to the sides and1 inch to the rear of the stove. Fig.
8.
10"
Place the stove awayfrom combustible walls at least
as far as shown in figures 6, and 7.
FLOOR PROTECTOR
Note that the clearances shown are minimum for
safetybutdonotleave muchroomfor accesswhenclean-
ing or servicing. Please take this into account when plac-
ing the stove.
Fig.7
Mobile Home Installation
1"
When installing this stove in a mobile home several
requirements must be followed:
1. The unit must be bolted to the floor. This can be
done with 1/4" lag screws throught the 2 holes in
the base plate shown in Fig. 13, Page 9.
2. The unit must also be connected for the outside
air. See page 12.
3. Floor protection andclearances must be followed
as shown above.
4. Unit must be grounded to the metal frame of the
mobile home.
6"
6"
FLOOR
PROTECTOR
6"
Fig.8
Installationandrepair of this stove should be done by
a qualified service person. The appliance should be in-
spected before use and at least annually by a qualified
service person. More frequent cleaning will be required. It
is imperative that control compartments, burners, and cir-
culating air passageways of the stove be kept clean.
CAUTION: This appliance must be vented to the
outside.
Dueto hightemperatures, thestove shouldbe placed
out of traffic and away from furniture and draperies.
Children and adults should be alertedto the hazards
of high surface temperatures and should stay away to
avoid burn to skin and/or clothing.
Young children should be carefully supervised when
they are in the same room as the stove.
Clothing and other flammable materials should not
AFTER THE INSTALLATION IS COMPLETED
Before the first fire is lit, check and record
the high and low draft reading numbers on page
10. Make adjustments to the low draft at this time,
if necessary. See page 10.
be placed on or near the stove.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Removing Side Doors for Installation
Removing Side Doors
Figure 9
Use hand hole to swing open side doors to at least
90o.
Figure 10
Side
Door
Remove side doors by lifting upward on the door until
the bottom pin is out of its hole. Move the bottom of
the door out and away from the pedestal base about
1/2". Allow the door to slide downward until the top
door pin is out of its top hole.
Fig. 9
NOTE: Always remove the side doors and rear
shields to move theunit. This will keep them from
getting damaged.
Removing the Rear Motor Shield Sheet Metal.
Side Door
Magnets
NOTE: Disconnect power to the unit before
removing the motor shields. Danger of electrical
shock. Hot and moving parts could cause injury.
Figure 11
There are (2) #10 hex head screws holding each rear
shield. Using a 5/16" nut driver or socket, loosen the
(2) screws about 4 or 5 turns.
Fig.10
Figure 12
Slide the rear shields straight outward until the ends
come out of the rear retaining clips, as seen in Fig.13.
Rear
Shield
Rear
Shield
Placing Rear Shields Back on Unit
1. When replacing the shields, always insert the top
and bottom ends of the sheet metal into the retaining
clips first.
2. Slide the shields straight inward until the (2) hex
head screws are fully inserted into the stove slots.
3. Make sure the top edges of the shield are against
the hopper bottom and tighten screws.
Fig.12
Fig.11
Rear ShieldRetaining clip
Rear Shields are split around the Flue Tail pipe and
outside Air Hole Knockout. This will allow removal and
installation of the rear shields with the unit completely
installed.
Rear
Shield
Fig.13
Outside Air
Flex Hole
Knockout
SkidHold Down
Screws
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Low Draft Voltage Adjustment
Combustion
Motor Speed
Control
Low draft only
set point.
The small straight
screwdriver slot is
plastic;therefore,
the unit can be
adjustedwhile in
operation.
Fig.15:
Draft Meterbolt hole location
Fig.14
A simple draft test should be performed after
completing the flue pipe installation. To record the
results for future reference:
1. Plug unit into a 120VAC, 60 HZ outlet.
2. Close the hopper lid, front view door, and the ash
pan. Neither pellets or a fire are required for this test.
3. With the mode selector in the "OFF" position, turn
the feed adjuster to "TEST".
These units are pre-tested at the factory with
Fig.1
exactly 120 Volts A.C., 60 Hz. They are checked and
adjusted for firebox tightness, gasket leakage, motor
operation and igniter operation. The Advance is then
factory set at a mid-point adjustment and in most cases
will not need any adjustments. NOTE: The factory low
draft setting may not be correct for the unit's
permanent installation conditions.
4. Record the high draft_____in W.C. (Normal is -.50
to -.60) The control will be on the High Draft for a total
of 2 minutes.
5. After 2 minutes is up, the combustion motor will go
down to low draft and the distribution blower will go on
high. Allow approximately 15 seconds to pass for the
combustion motor to slow before checking the low
draft.
The control board on the Advance is equipped
with a low draft adjustment port. Located on the control
face just to the right of the igniter light. See Figure 14.
This voltage adjustment is provided to allow the unit to
be adjusted for the household voltage where the unit is
going to be in permanent operation. NOTE: The line
voltage varies from area to area and often home to
home.
6. If the low draft is between .35 and .45, record the
reading _____ in W.C. If the reading is higher, slowly
turn the set screw counter-clockwise until the draft
lowers. If the reading is lower, very slowly turn the set
screw clockwise until the draft increases.
NOTE: The test mode alternates from high to low
draft every 60 seconds. If more time is needed
for draft adjustment, wait until the next low draft
cycle.
The low draft voltage should be adjusted to
achieve the most efficient burn on low burn or
"maintenance". This voltage adjustment allows the
installer to change the lowvoltage setpoint approximately
15 volts. This adjustment should be done by the installer
during set up because a draft meter reading isrequired
to insure proper set up.
If the unit is not adjusted properly, it does not
cause a safety concern. If the unit is adjusted too high,
only effiency is lost. If the unit is adjusted too low, the low
draft pressure switch will not allow the feeder motor or
the igniter to operate.
NOTE: In some cases, the draft may not go as low
as .35 even with the set screw completelycounter-
clockwise.
MODIFICATIONS
High Altitude(7,000- 10,000ft.)A combustion
fan blade change can be made by an authorized
Harman Dealer. These changes must be done with
the use of a draft meter. These changes affect the low
and high burn rate air to fuel ratios.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Room Sensor and Air Grill Installation
Gold Air Grill Installation
Room Sensor Installation
Fig. 17
Fig. 16
The room sensor is a small temperature sensor
on the end of a 60" gray wire. This sensor is installed
much like a standard wall thermostat. Because it is so
small, it can be hidden along the trim of a doorway or
even up the leg of a coffee table. There is a remote
room sensor porton the rear of the unitfor easy exter-
nal connection. Use standard 18-2 thermostat wire to
extend the distance to the desired location (100' maxi-
mum). The room sensor should be installed in the lo-
cation where you want to control the temperature.
NOTE: Distances of more than 25 feet from the
unit or in another room are not recommended. It is
recommended that the room sensor be installed, even
if only installed on the rear of the unit as a return air
sensor. The roomsensor isessential for the Advance's
excellent efficiency.
Insert the two tail end hooks of the Air Grill Assembly
up under the stove top edge. Insert inward until the
two center hooks drop into the stove body slots in the
front of the unit.
REMINDERS
Hopper Lid
Foam Gaskets
Fig. 18
Do not allow pellets or sawdust to build up on the
hopper lid gasket.
Inspectthe hopper lid gasket for damage. A good
hopper lid seal is very important for proper
operation.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
Acombustion blower is usedto extractthe com-
bustion gases from the firebox. This causes a nega-
tive pressure in the firebox and a positive pressure
in the venting system as shown in fig. 19. The longer
the vent pipe and more elbows used in the system,
the greater the flow resistance. Because of these
facts we recommend using as few elbows as pos-
sible and 15 feet or less of vent pipe. The maximum
horizontal run should not exceed 48". If more than
15 feet of pipe is needed, the diameter should be
increasedfrom3" to4" becausea larger pipe causes
less flow resistance. Be sure to use approved
pellet vent pipe wall and ceiling pass- through
fittings to go through combustible walls and
ceilings. Be sure to use a starting collar to attach
the venting system to the stove. The starting col-
lar must be sealed to the stove with high temp
silicone caulking.
Vent Pipe
Pellet venting pipe ( also known as PL vent ) is
constructed of two layers with air space between
the layers. This air space acts as an insulator and
reduces the outside surface temperature to allow a
clearance to combustibles of only 3 inches. The
sections of pipe lock together to form an air tight
seal in most cases; however, in some cases a per-
fect seal is not achieved. For this reason and the
fact that the Advance operates with a positive vent
pressure, we specify that the joints also be
sealed with clear silicone.
Fig.19
+ = Positive static pressure
= Negative static pressure
Outside Air
Outside air is optional except in mobile homes
and where building codes require. The benefit of
outside air is mainly noticed in small, very tight
houses.
Room Sensor
Connection Ports
To install outside air use 2 3/8" I.D. flex pipe
partnumber 2-00-08543. There is abreak-awayhole
on the rear panel which must be removed before
connecting the flex pipe. The pipe should be run out-
side and terminate to the side or below the vent pipe
outlet so the flue outlet is more than 12" from the
inlet cover. The maximum length run of this pipe is
15 feet. If a longer run is needed, the size must be
increased to 3". Inlet cover part number 1-10-08542
should be used to keep birds, rodents, etc. out of
pipe.
Outside airflex pipe
goes here
Flex pipe part#
2-00-08543
HRV
Wheninstalling ina house with a Heat Reclaim-
ing Ventilation System (HRV) be sure the system is
balanced and is not creating a negative pressure in
InletCover part#
1-10-08542
12 the house.
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
#1 Preferred method
This method provides excellent venting for nor-
mal operation and allows the stove to be installed clos-
est to the wall. One inch from the wall is safe; how-
ever, two or three inches allows better access to re-
move the rear panel. The vertical portion of the vent
should be three to five feet high. This vertical section
will provide natural draft in the event of a power failure.
3 ft.
to
combustibles
Fig.20
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
shouldbethree tofive feethighandatleastthree inches
from a combustible wall. This vertical section will pro-
vide natural draft in the event of a power failure.
CAUTION
KEEP COMBUSTIBLES (SUCH AS
GRASS, LEAVES, ETC.) AT LEAST 3
FEET AWAY FROM THE FLUE OUTLET
ON THE OUTSIDE OF THE BUILDING.
3 ft.
to
Fig.21
combustibles
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
#3 Installing into an existing
chimney ( US only )
This method can be used for normal operation.
This method also provides natural draft in the event
of a power failure. If the chimney condition is ques-
tionable you may want to install a liner as in method
#6.
Fig.22
#4 Installing into an existing
fireplace chimney ( US only )
This method can be used for normal operation.
This method also provides natural draft in the event
of a power failure.
The damper area must be sealed with a steel
plate or fiberglass. A cap should be installed on the
chimney to keep out rain. If the chimney condition is
questionable you may want to install a liner all the
way to the top as in Method #5.
Fig.23
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
#5 Installing into an existing fireplace
chimney ( US and Canada)
This method provides excellent venting for nor-
mal operation. This method also provides natural draft
in the event of a power failure.
In Canada and some places in the US it is re-
quired that the vent pipe extend all the way to the top
of the chimney.
In this method a cap should also be installed on
the chimney to keep out rain. Be sure to use approved
pellet vent pipe fittings. Seal pipe joints with silicone in
addition to the sealing system used by the manufac-
turer. Pipe size should be increased to 4" using this
method.
Fig.24
#6 Installing into an existing
chimney ( US and Canada )
This method provides excellent venting for nor-
mal operation. This method also provides natural
draft in the event of a power failure.
In Canada and some places in the US it is re-
quired that the vent pipe extend all the way to the top
of the chimney. The pipe or liner inside the chimney
should be 4"diameter.
In this method a cap should also be installed
on the chimney to keep out rain.
Fig.25
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
Stormcollar
Flashing
12" min.
3" min.
3" min.
3" min.
PLvent manufacturer's
firestop spacer and
support.
No insulation or other
combustible materials
areallowedwithin3" of
the PL vent pipe.
Fig. 27
Fig. 26
#7 Installing through the ceiling vent
Minimum flue vent configuration
Through the ceiling vent, follow PL vent
manufacturer's recommendations when using wall
and ceiling pass through.
It is recommended that outside air be installed with
this venting configuration.
Fig. 28
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
I. The clearance to service regulator vent outlet
must be a minimum of 6 feet.
Requirements for Terminating the
Venting
WARNING: Venting terminals must not be re-
cessed into a wall or siding.
1
J. The clearance to a non-mechanical air sup-
ply inlet to the building or the combustion air inlet to
1
any other appliance must be a minimum of 48”.
NOTE:Only PL vent pipe wall pass-throughs and
fire stops should be used when venting through com-
bustible materials.
NOTE: Always take into consideration the effect
the prevailing wind direction or other wind currents will
cause with flyash and /or smoke when placing the ter-
mination.
In addition, the following must be observed:
A. The clearance above grade must be a mini-
mum of 18".1
B. The clearance to a window or door that may
be opened must be a minimum of 48" to the side, 48"
below the window/door, and 12" above the window/
door.1
K. The clearance to a mechanical air supply
inlet must be a minimum of 10 feet.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a
paved driveway located on public property must be
a minimum of 7 feet.1,2
1
M. The clearance under a veranda, porch,deck
1,3
or balcony must be a minimum of 12 inches.
NOTE: The clearance to vegetation and other
exterior combustibles such as mulch is 36” as mea-
sured from the center of the outlet or cap. This 36”
radius continues to grade or a minimum of 7 feet
below the outlet.
1CertainCanadian andor Local codes or regu-
lations may require different clearances.
2Avent shallnot terminate directly above a side-
walk or paved driveway which is located between
two single family dwellings and serves both dwell-
ings.
( with outsideair installed,18”)
C. A12" clearance to a permanently closed win-
dow is recommended to prevent condensation on
the window.
D. The vertical clearance to a ventilated soffit lo-
cated above the terminal within a horizontal distance
3Only permitted if veranda, porch, deck, or bal-
of 2 feet (60 cm) from the center-line of the terminal cony is fully open on a minimum of 2 sides beneath
the floor.
must be a minimum of 18".
E. The clearance to an unventilated soffit must
be a minimum of 12".
F. The clearance to anoutside corner is 11" from
center of pipe.
NOTE: Where passage through a w all, or
partition of combustible construction is desired,
the installation shall conformto CAN/CSA-B365.
(if in Canada)
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90
cm) abovea gasmeter/regulator assemblywhenmea-
1
sured from the horizontal center-line of the regulator.
Inside
Corner
Detail
Fixed
Closed
Fixed
Closed
Openable
Openable
= Vent terminal
= Air supply inlet
= Area where terminal is not permitted
A
V
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Venting
DO NOT INSTALL A FLUE DAMPER IN THE
EXHAUST VENTING SYSTEM OF THIS UNIT.
WARNING
DO NOT INSTALL IN SLEEPING ROOM
DO NOT CONNECT THIS UNIT TO A
CHIMNEY FLUE SERVING ANOTHER
APPLIANCE.
CAUTION
THE STRUCTURAL INTEGRITY OF THE
MOBILE HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
INSTALL VENT AT CLEARANCES
SPECIFIED BY THE MANUFACTURER
CAUTION
KEEP COMBUSTIBLES AWAY
FROM FLUE OUTLET.
Mobile home installation should be done in
accordance with the Manufactured Home
and Safety Standard (HUD), CFR 3280,
Part 24.
WARNING
3'
Keepcombustible materials such as
grass, leaves,etc. atleast 3 feetaway
fromthe pointdirectly under the vent
termination.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Emptying Ashes
Ash Pan Removal and Reattachment
Figure 29
Open side doors.
Figure 30
Release spring latches on the right and left side of the ash
pan.
Fig. 29
Figure 31
Slide ash pan forward enough to lift with center handle.
Empty ashes and reinstall ash pan.
Ashes should be placed in a metal container with a
tight fitting lid. The closed container of ashes should
be placed on a noncombustible floor or on the ground,
well awayfrom all combustible materials, pending final
disposal. If ashes are disposed of by burial in soil or
otherwise locallydispersed, theyshould be retained in
the closed container until all cinders have thoroughly
cooled.
Fig. 30
Figure 32
Inspect the gasket rope for damage. Replace if necessary.
Figure 33
Insert spring latch front hooks into the ash pan side slots.
Push both latches to the rear at the same time to latch.
Fig. 31
Fig. 32
Fig. 33
Soot and Fly Ash
The products of combustion will contain small particles
of fly ash. The fly ash will collect in the exhaust venting sys-
tem and restrict the flow of the flue gases. Incomplete com-
bustion, such as occurs during startup, shutdown, or incor-
rect operation of the room heater, will lead to some soot for-
mation which will collect in the exhaust venting system. The
exhaust venting system should be inspected at least once
each year to determine if cleaning is necessary.
When removing the ash pan to empty ashes, you will
note a build up of ash fines behind the ash pan. This space
behind the ash pan was designed to allow the fines to fall out
of the vertical heat exchangers and collect where they are
easily cleaned out, rather than going into the flue pipe where
it would be difficult to clean. These fines should not be al-
lowed to build up. They may not allow the ash pan to be
seated into its gasketproperly.NOTE: If an extreme amount
of force is required to snap the latch on one or both
sides of the ash pan, thearea behind the ash pan should
be checked for ash fine build up.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Cleaning Glass on View Door
WARNING
Door latch may
Opening and Closing the View Door
Opening:
be hot!
The view door must be opened for cleaning of
the glass and scraping of the burn pot. This should be
done with the unit off and cool, in most cases. Although
the glass can be cleaned and burn pot scraped while
Receiving Bolt
the unit is at low burn.
1. Using scraper as shown in Fig. 34and 35, lift the
door latch forward and up.
2. Swing the door open to the left, stopping the swing
when resistance is felt. Forcing the door open further
then was designed may cause damage to the door or
Fig. 34
it's hinges.
CAUTION
Do not put excessive downward pressure on the
latch end of the door while in the open position.
If thedoor is goingto be openedfor anextendedperiod
of time, it is suggested that it be removed (see Fig. 36)
and set safely aside.
3. Inspect the door gasket and glass gaskets for worn
or missing pieces. Replace if necessary. (Fig. 37)
Closing:
When closing the door, always hold the door
latch all the way up until it has caught the receiving
bolt. Then push the latch downward and back until the
door is fully seated. See Fig. 35.
Fig. 35
Fig. 36
Fig. 37
Removing View Door:
To remove the view door from the stove, hold
the door by the bottom and lift upward off of the hinge
pins.See Fig. 36.
Inspect the door gasket.See Fig. 37.
REPLACE GLASS WITH
CERAMIC GLASS ONLY.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Burn Pot
Burn Pot Cleaning and
Maintenance
1. Scrape the top holed surface and sides of the
burn pot.(Fig 38) It is not necessary to completely
remove all material from the burn pot. The excess
will be pushed out during the next use.
2. Loosen the (2) wing thumb screws on the lower
front angle of the burn pot. (Fig. 38)
3. Lift off the clean-out cover (Fig.39) to open the
bottom clean-out chamber. (Fig.40)
DANGER
Disconnect the power to the unit before
removing cover.
Fig. 38
4. Clean ashbuildup frominside the chamber while
cover is off. Use the scraper to tap on the top front
edge of the burn pot. This will help knock pieces of
ash, loosened by the scraping process, down
through the holes. It also helps knock scale off of
the igniter element.
Figure 40
The igniter is made to be removable for
service by insulated male/female wire connectors.
These connections between the hot leads (the
wires inside the burn pot) and the cold leads (the
wires from the control board) are always pulled to
the rear of the feeder body.(Not coiled inside the
burn pot.)
It is very important that these connections
are to the inside rear of the feeder body. Also, the
extra wire of the igniter wire service loop must be
pulled out through the rear of the feeder and tied
up so that it will not be damaged by any moving
parts. See page 25.
Fig. 39
Burn pot igniter
DANGER
Disconnect the power to the unit before
removing cover.
Warning
Use caution when cleaning burn pot clean-
out chamber. Do not damage the high
temperature igniter wires.
Igniter hot leadwires
(high temperature)
Note: The hot lead/cold lead connection
must always be pulled to the rear of the
feeder body before operation.
Fig. 40
Viewed from below through the ash pan
opening.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Flame Guide and Brick Panel
Firebox Brick Panel
Flame Guide and Brick Panel
Flame Guide/
Brick panel
holder
Removal for Cleaning
Burn pot
Fig. 41
Figure 42
Slidebrick panelstraightupwardwith bothhands.
Fig. 42
Figure 43
While holding the brick panel up with one hand,
remove theflame guidefrom the top of theburn
pot.
Fig. 43
Figure 44
Slide the brick panel into the left corner of the
fireboxwiththe panel resting on the top edges of
theburnpot. Rotatetheright sideofthebrick panel
throughthe dooropening.
Fig. 44
Reversethis operationto reinstall the brick panel
aftercleaning.
Fig. 45
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Combustion Intake Cover
CoverRetainer Handle
Cleaning and Maintenance for the
Combustion Intake Cover
You will need to remove the combustion
intake coverto cleanthe fanblades and rearflue
tube.
Figure 46
Rotatetheretainercoverhandlecounter-clockwise
o
upward as far as itwill go (approximately90 ).
Fig. 46
Combustion
Intake Cover
These surfaces mustbe even to
closeretainer handle.
Figure 47
Holdtheintake coverhandleandpull until theside
ofthecover attheretainerhandle endcomes away
o
from the stove body, approximately 15-20 , slide
therightside tab outof the retaining slot.
Figure 48
Clean and inspect the fully exposed combustion
fan bladeand fluetube.
Fig. 47
RightSide Tab
Reinstall the combustion intake cover by
firstsliding the right side tab into the retainer slot
seenin Figure 47.
IntakeCover Handle
Right Side Retaining Slot
Rotate the cover inward until the cover fits
intoits hole.
Make sure the two faces (Fig.46) of the
coverandretainer spacerareevenand rotatethe
retainerhandle clockwise until it stops.
ESP Probe
(in rear of flue
tube)
CAUTION
Excessive cleaning force could bend the
small stainless steel ESP Probe, causing
damage.
Fig.48
Combustion Fan Blade
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance - Heat Exchanger
Cleaning the Heat Exchanger
System
Slot
1.Removebrickpanelandflameguide. SeePg22.
2. Remove the ash pan. See Page 19.
3. Remove flue baffles located on each side of
theburnpot, seeFig. 49& 50. The baffleis heldin
place by inserting the tab into the slot (located
towardtheoutside ofthefirebox)and restingiton
thehook tablocated beside theburnpot.
4. Pull the pointed end of the baffle slightly front
with onehand whilepushing upfrom below with
the other hand. See Fig. 50.
Tab
Hook Tab
Fig. 49
5. With the baffle released from the tabs, rotate
the pointed end toward the door opening. Lift
baffle up andout.
The right andleft baffle areinterchangeable.
6. Now remove the heat exchanger baffleplates.
See Fig. 51 & 52. To remove the left plate, slide
the center lock to the right. To remove the right
plate, slide the center lock to the left. (The right
and leftplates areinterchangeable.)
Fig. 50
Center Lock
This will allow access toall oftherearvertical heat
exchangersurfaces.
7. Withall fourbaffleplates removed, cleaningcan
be performed with the arrow end of the scraper.
See Fig. 53.
Fig. 51
8. Scrape all of the heat exchanger surfaces.(Be
sure to clean any internal ledges where fly ash
could have collected.)
Center Lock
Fig. 52
TopAccordian
Heat Exchangers
Rear Firewall
Heat Exchanger
Fig. 53
24
Download from Www.Somanuals.com. All Manuals Search And Download.
25
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Trouble-Shooting
FEEDER DOES NOT FEED
4. Feed motor or draft motor has failed.
5. Power failure or blown fuse.
1. No pellets in hopper.
2. Firebox draft may be too low for low draft pres-
sure switch in feeder circuit to operate.Check for
closed doors, loose or missing gasket on doors
or hopper lid, faulty pressure switch.
3. Feed motor will not run until ESP
senses 165 deg. F. Maybe you did not put
enough pellets in the burn pot before lighting the
fire.
SMOKE IS VISIBLE COMING OUT OF VENT
1. Air-fuel ratio is too rich.
A. Feed rate too high.
B. Draft too low caused by a gasket leak.
LOW HEAT OUTPUT
1. Feed rate too low
4. Something is restricting flow in the hopper or
causing the slide plate to stick.
5. Feed motor has failed.
2. Draft too low because of gasket leak.
3. Poor quality or damp pellets
4. Combination of 1. and 2.
Helpful Hints
PARTIALLY BURNED PELLETS
1. Feed rate too high.
Cleaning Burn Pot
2. Draft too low. (Check burn pot clean out slide
and door gasket).
3. Burn pot or heat exchanger may need to be
cleaned.
Whenever your stove is not burning, take the op-
portunity to scrape the burn pot to remove carbon
buildup. A vacuum cleaner is handy to remove the resi-
due. Be sure the stove is cold if you use a vacuum.
Carbon buildup can be scraped loose with the fire
burning using the special tool provided with your stove.
Scrape the floor and sides of the burn pot. The carbon
will be pushed out by the incoming fuel. Always wear
gloves to do this.
4. Combination of all the above.
5. #6 status blink: A 6 blink control board status
indication is caused by poor or incomplete com-
bustion. The Advance Automatic Ignition circuit
boardhas the abilityto track the combustion through
feed settings and ESP temperatures. When the
control board has calculated poor or incomplete
combustion it will shut down the unit as a safety
feature. (Poor or incomplete combustion is a con-
tributor of creosote which may cause a chimney
fire)
A 6 blink status may be caused by several things:
1. Blocked or partially blocked flue.
2. Blocked or partially blocked inlet air.
a. backdraft damper on the inlet pipe may be
stuck closed.
Removing Ashes
Turn the Temp Dial to number 1 approximately 30
minutes before removing ashes. This will result in a
cooler stove and ash pan.
Maximum Feed Adjuster settings are not needed
in most cases. Operating in the normal range (#4) is
recommended when maximum heat output is not re-
quired. The ESP probe prevents the stove from being
over-fired.
Keep the stove free of dust and dirt.
b. if outside air is installed the inlet cover may be
blocked.
3. The air chamber under the burnpot may be filled
with fines and small bits of ash.
4. The holes in the burnpot may be getting filled
with ash or carbon buildup.
5. Combustion blower fan blades may need
cleaned.
Fuel
Pellet fuels are put into 3 categories in terms of ash
content. Premium at 1% or less, Standard at 3% or less
and all others at 3% or more.
TheAdvance is capable of burning all3 categories of
pellets due to a patented feeder and burn pot system.
It should be noted, however, that higher ash content
will require more frequent ash removal and may provide
less BTU's per pound. Normally, standard and high ash
pellets cost less than premium pellets and can be cost
effective when burned in the Advance.
The moisture content must not exceed 8%. Higher
moisture will rob BTU's and may not burn properly.
Higher moisture contentinthe fuelmay showas con-
densation on hopper lid and possibly form rust inside the
hopper.
6. No fuel in hopper.
SMOKE SMELL
Seal the vent pipe joints and connection to stove
with silicone.
FIRE HAS GONE OUT
1. No pellets in hopper.
2. Draft setting is too low.
3. Something is restricting fuel flow.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
20.5"
7.750"
7.750"
5.250"
26.625"
C
L
Weight
250 lbs.
Blower
Hopper Capacity
Fuel
135 cfm
60 lbs.
Wood Pellets
Outside Air Size
Fuse Rating
BTU Range
Feed Rate
2 3/8 inches
6 amp
0 to 48,000
1.0 lbs./hr. on minimum
6 lbs./ hr. on maximum
3 inch Pellet Vent Pipe
Flue Size
Maximum Wattage
Start Cycle Wattage
Normal Run Wattage
480 Watts (Start cycle and test)
340 Watts
275 Watts
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Advance Wiring Diagram
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Advance Feeder Assembly
Download from Www.Somanuals.com. All Manuals Search And Download.
Advance Parts List
Description
Part Number
3-44-375501
2-00-06610-1
2-00-06610-2
1-10-06620
3-20-08727
1-10-08736
2-00-06616
2-00-06617
Hopper Gasket (6')
Left Side Door Assembly
Right Side Door Assembly
Igniter Element Assembly
Wiring Harness Assembly
Burn Pot Weldment
Right Rear Shield
Left Rear Shield
Flue Baffle (2)
2-00-06632
Arrow Scraper
Flame Guide
2-00-773850
3-00-06644
Thermister Probe
3-20-00744
Room Sensor
3-20-00906
Circuit Board
3-20-05374
3" White CCW Fan Blade
Differential Switch
4-3/4" Single Fan Blade
Combustion Blower
Distribution Blower
Spring Latches (2)
White/Black Control Knob
Control Knob Shaft
Round Magnet (4)
Brick Panel
3-20-08789
3-20-9301
3-21-00661
3-21-08639
3-21-22647
3-31-00927
3-31-605
3-31-015
3-31-08569
3-00-06641
Front Glass
3-40-08728
SideGlass (2)
3-40-08729
Hopper Lid Knob
3-43-02000
View Door Frame
Grill
Glass Divider Trim - Black only (2)
Burn Pot Gasket
3-43-06613 (Gold -4, Black Nickel -5)
3-43-06642 (Gold -4, Black Nickel -5)
3-43-08754
3-44-00409
3/8" Rope for Ash Pan Assembly (5')
Tailpipe Gasket
3-44-00888
3-44-06179
Black Glass Gasket (6')
Tadpole Rope for View Door (1)
Wiring Diagram
3-44-2312
2-00-71611
3-89-06653
Control Panel Sticker
Owner's Manual
3-90-06655A
3-90-09730
Hopper Lid Label
3-90-09416
Combustion Intake Weldment
Ash Pan Assembly
Ball Plunger
1-10-07574
1-10-07581
3-31-5500
Hopper Lid Glass
3-40-06693
Top Gasket (5')
Combustion Blower Studs (3)
3-44-375501
3-31-54383208
Options:
Outside Air Assembly
3' Flex Pipe
5" Single Fan Blade for High Altitude
3 Piece Ceramic Top Inserts
45o Tailpipe Weldment
1-10-08542
2-00-08543
3-20-40985
3-43-03000
See page 29 for
1-10-247129
Feeder Part Numbers
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Harman Gold Warranty
HARMAN GOLD WARRANTY
6 YEAR TRANSFERABLE LIMITED WARRANTY
(Residential)
1 YEAR LIMITED WARRANTY (Commercial)
Harman Stove Company warrants its products to be free from defects in material or workmanship, in normal use and
service, for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in normal use and
service, for a period of 3 years from the date of sales invoice.
If defective in material or workmanship, during the warranty period, Harman Stove Company will, at its option, repair
or replace the product as described below.
The warranty above constitutes the entire warranty with respect to Harman Stove Company products. HARMAN
STOVE COMPANY MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANY” WAR-
RANTY OF MERCHANTABILITY, OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee,
agent, dealer, or other person is authorized to give any warranty on behalf of Harman Stove Company. This warranty does
not apply if the product has been altered in any way after leaving the factory. Harman Stove Company and its agents assume
no liability for “resultant damages of any kind” arising from the use of its products. In addition, the manufacturer and its
warranty administrator shall be held free and harmless from liability from damage to property related to the operation, proper
or improper, of the equipment.
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user’s manual.
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond rated
capacity causes damage.
HOW TO MAKE A CLAIM - Any claim under this warranty should be made to the dealer from whom this appliance
was purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date of purchase, your
dealer’s name and address, plus a simple explanation of the nature of the defect. Extra costs such as mileage and overtime
are not covered. Nuisance calls are not covered by these warranties.
THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS - REPAIR AND/OR REPLACEMENT AT
HARMAN STOVE COMPANY’S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL
DAMAGES CONNECTED THEREWITH.
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of God, power failures and/or surges,
rust, corrosion and venting problems are not covered. Damage and/or repairs including but not limited to; remote controls,
filters, fuses, knobs, glass, ceramic brick panels, ceramic fiber afterburners, door packing, tile, ceramic log sets, paint,
batteries or battery back-up and related duct work are not covered. Also excluded from this warranty are consumable or
normal wear items including but not limited to; flame guides, grates, coal bars, afterburner hoods, fire brick, gaskets.
Additional exclusions for corn stoves are burnpot housing weldment, burnpot grate weldment (pellet or corn), burnpot front
plate (pellet or corn), burnpot front plate lock, corn auger extension, ceramic insert, and ceramic insert plate. Additional or
unusual utility bills incurred due to any malfunction or defect inequipment and the labor cost of gaining access to or removal
of a unit that requires special tools or equipment are not covered. Maintenance needed to keep the stove in “good operating
condition” is not covered. This includes, but is not limited to, cleaning, adjustment of customer controls and customer
education. Labor, materials, expenses and/or equipment needed to comply with law and/or regulations set forth by any
governmental agencies are not covered.
This Warranty provides specific legal rights and the consumer may have other rights that vary from state to state.
In the event of change in ownership, the remaining portion of this warranty may be transferred to the new owner by
sending the new owner information and a transfer fee of $25.00 US to the Harman Stove Company.
PLEASE READ THE LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DEVICES.
THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES, NOT HARMAN STOVE COMPANY OR
THEIR WARRANTY ADMINISTRATOR. FURTHERMORE, THESE ACCESSORY DEVICES MUST BE INSTALLED
AND USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER.
REMEDIES - The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale
or anything done in connection therewith, whether in Contract, in tort, under any warranty, or otherwise, shall not, except
as herein expressly provided, exceed the price of the equipment or part of which such liability is based.
CLARIFY - The above represents the complete warranty, which is given in connection with stoves, manufactured by
Harman Stove Company. No other commitments, verbal or otherwise, shall apply except by a written addendum to this
warranty.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
|