Harman Stove Company Stove Advance Pellet Stove User Manual

Installation & Operating Manual  
The Harman Advance Pellet Stove  
R8  
“Ce manuelest disponibleen Françaissur demande”  
SAFETY NOTICE  
PLEASE READ THIS ENTIRE MANUALBEFORE YOUINSTALL AND USE YOURNEW ROOM HEATER. FAILURE TO  
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTYDAMAGE, BODILYINJURY, OR EVEN DEATH.  
FOR USE IN THE U.S.AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES  
IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED,AHOUSEFIREMAYRESULT. FORYOURSAFETY, FOLLOW  
INSTALLATIONDIRECTIONS.  
CONTACT LOCAL BUILDING OR FIRE OFFICIALSABOUT RESTRICTIONSAND INSTALLATIONINSPECTION  
REQUIREMENTS INYOUR AREA.  
CONTACT YOUR LOCAL AUTHORITY (SUCHAS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE  
PREVENTION BUREAU,ETC.) TO DETERMINE THENEED FORA PERMIT.  
CETTEGUIDE D'UTILISATIONEST DISPONIBLEENFRANCAIS.CHEZVOTRECONCESSIONNAIRE DEHARMANSTOVE  
COMPANY.  
SAVETHESEINSTRUCTIONS.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Automatic Ignition/Operation  
TheAdvance pelletstove is more thanjust automatic ignition, itis also automatic temperature  
control. The automatic system will allow the fire size to be adjusted to match the heating  
needs and even put the fire out if necessary. If heat is needed after the fire is out, the  
Advance will automatically re-ignite and adjust the fire size to match the heating need. The  
totally automatic room sensor mode is recommended because of its efficiency.  
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.  
Igniter switch to "AUTO"  
Room Temperature Mode  
In "Room Temp Mode" heat output is controlled au-  
tomatically by the Room Sensing Probe. When the Room  
Sensing Probe calls for heat, the stove will increase out-  
put. When the Room Sensing Probe is getting close to  
the set temperature, the stove will begin to level off out-  
put and keep the fire burning at just the right temperature  
to maintain that setting.  
High output is determined by the feed rate set-  
ting. This setting, generally on #4, can be increased if  
higher burn rates are necessary. The unit's maximum  
burn rate should not create less than 1" of ash on the  
burn pot front edge. See Fig.2, Page 4. Overfeeding is  
not a safety concern, but fuel may be wasted if unburned  
Room Temperature Mode: This setting will producea room  
temperature of 70 degrees with the distribution blower at  
medium speed.  
pellets fall into the ash pan.  
In "Room Temp Mode" a constant fuel consumption  
rate is sacrificed for exact room temperature. Therefore,  
as it gets colder more pellets will be burned automati-  
cally.  
Stove Temperature Mode  
The distribution blower speed will vary according to  
the position of the mode selector pointer, and fire size.  
Igniter switch to "AUTO"  
Stove Temperature Mode  
This allows for automatic ignition upon start-up only.  
The unit can then be set at any desired setting. The heat  
output and fuel consumption will remain constant regard-  
less of room temperature. The unit's maximum feed rate  
should not create less than 1" of ash on the burn pot front  
adge. See Fig 2, Page 4.  
This setting will produce medium heatwith the  
distribution blower on "low".  
The unit's low burn or maintenance setting is as  
low as it will go. It will not go out unless it runs out of  
fuel or is turned off.  
Shut-Down Procedure  
To kill the fire or stop burning the stove, turn the Mode Selector to  
"OFF". This will causethefiretodiminishand burnout. Whenthe fireburns  
out andthestovecoolsdowneverythingwill stop.  
If you pull the plug toshut down the stove, all motors will stop. This  
may causeincompletecombustionandsmokeinthefirebox. If theloaddoor  
isopened thesmokemayescape.  
Thebest waytoshut downthestoveis simplylet it runout of pellets,  
thenthe stove will shut down automatically.  
This setting willproduce continuous maximum heat  
output with the distribution blower atfull speed.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Automatic Start Up  
Starting First Fire  
Igniter Switch to"AUTO"(up position)  
Make sure the unit is plugged into a 120 VAC,  
60 HZ electrical source. The power light should be the  
only light lit.  
1. Turn Mode Selector to "OFF".  
2. Fill hopper with pellets.1  
See Note 7.  
1"  
Fig. 1  
3. Clean burn pot with scraper, if necessary.5  
4. If starting after an empty hopper, turn Feed  
Adjuster to "TEST" (for one 60 second cycle).2 This  
will purge pellets into the auger tube and also allow  
you to check the motors for operation. NOTE: The  
auger motor will not operate with the view door or  
ash pan door open.3  
Fig. 2  
4
5. Turn Feed Adjuster to #4.  
6. Flip theIgniter Switch up into the"AUTO" position.  
7. Turn the Temperature Dial to desired room  
temperature.  
1.Fines are small pieces ofbroken pellets (sawdust). Finesdo not  
flow easily and often build upon the hopper funnelbottom angles.  
These fines can be pushed into the feeder opening and then fill  
the hopperwith pellets. As the system works,they will be burned.  
2. The "TEST" cycle will operate the feeder motor forexactly one  
minute. Turning to "TEST" again and again may purge too much  
fuel into the burn potcausing excessive smoke on start-up.  
3.Thefirebox low pressure switch will notallow theauger motoror  
the igniter elementto operate if the view door orthe ash pan door  
are open.  
8. Turn Mode Selector toRoomTemperatureor Stove  
Temperature.  
9. Fill hopper with pellets and remove ashes as  
required.6  
4.Adjust Feed Rate.If this isyour first fire or youare trying different  
pellets, set the feed adjuster to #4, Fig. 1. This is a conservative  
number andwill probably need to be increased. Afteryou know a  
feed rate setting that works well, use that setting. Remember, if  
your feed rate is too high you may waste fuel.  
5. This is usually a weekly maintence procedure. Cleaning the  
burn pot with the scraper with a small amount of new fuel in the  
bottom is nota problem. First, scrape the ashes on the frontof the  
burn potinto the ash pan.Then scrape the holed surface downward  
into theburn pot.When the stove is ignited these scrapings will be  
pushed out by the feeder.  
Battery Back Up  
If a power outage is expected, switch the toggle switch  
to Manual Mode. The Harman 502H Battery Back Up  
is incapable of powering the igniter. If an automatic  
ignition is attempted while the stove is being powered  
by the battery back up, it may cause damage to both  
the stove and the battery back up unit.  
CAUTION  
6. The ash pan can hold the ashes from approximately 1 ton of  
premium fuel.This means the asheswill only need to be emptied  
a few times a year.  
The stove is hot while in operation.  
Keep children, clothing and furniture away.  
Contact may cause skin burns.  
7. Setting the feed adjuster # for maximum burn: With the unit  
burning in "AUTO",turn to "Stove Mode"and putthe fan on "H". Set  
the Temperature Dial to #7. Allow the unit to burn for about 30  
minutes andcheck ash on frontof burn pot. Fig.2.If the ash line is  
larger than 1", turn the feed adjuster from #4 to #5. Allow another  
30 minutes of burn time and check again.If , at #6 setting, a 1" or  
less ash bed is notobtainable, itis not a problem. The 1" ash bed  
is only a maximum burn rate and at most normal settings the ash  
bed will be larger.  
Warning  
"NEVERUSE GASOLINE,GASOLINE-TYPE LANTERN  
FUEL, KEROSENE,CHARCOAL LIGHTER FLUID, OR  
SIMILAR LIQUIDS TO START OR "FRESHEN UP " A  
FIRE IN THIS HEATER. KEEP ALL SUCH LIQUIDS  
WELL AWAY FROM THE HEATER WHILE IN USE".  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Manual Ignition/Operation  
The Advance Pellet Stove is capable of manual operation. This also allows the operator  
to manually control operation during an emergency (i.e. igniter failure, when using a 502H  
battery backup, or when using certain generators.)  
The unit can be switched between "AUTO" and "MANUAL" at any time during operation.  
NOTE: When starting the unit in the "AUTO"  
mode and switching to "MANUAL", the fire must be  
large enough to start the distribution blower. The  
starting of the blower is a signal that the start cycle  
is completed and the fire will not go out.  
Igniter Switch to "MANUAL"  
Room Temperature Mode  
The fire will have to be lit with starting gel and a  
match, or started automatically, see "Automatic Opera-  
tion". Turn to "Manual" position when the fire is estab-  
lished.  
The difference between "AUTO" Room Tempera-  
ture Mode and "Manual" Room Temperature Mode is  
that the fire willnot go out as the roomtemperature goes  
above the control board setting. The unit can only go to  
Room Temperature Mode: This setting will produce a  
low burn and will remain there until it runs out of fuel or  
until more heat is needed and the feed rate increases.  
Feed rate adjustments and dial settings are the same  
as "AUTO" settings.  
roomtemperature of70 degrees with thedistribution blower  
atmedium speed.  
Manual Stove Temperature Mode  
Igniter Switch to "MANUAL"  
Stove Temperature Mode  
The advantage of this mode is to allow the opera-  
tor to have a large viewing fire without blowingextra heat  
into the room.  
During operation, with the temperature dial set at  
#5 or less, the distribution fan will not operate. A #5 on  
the temperature dial and a #5 on the feed adjuster is  
approximately 80% output. It is not necessary to oper-  
ate the distribution blower below this point. Therefore,  
there can be a higher feed rate ( a larger viewing fire)  
without an excess of hot air blowing into the room.  
An example of when to use the Manual Stove Tem-  
perature Mode is if you want to watch a large fire and  
the room is aleady up to temperature. The Stove Tem-  
perature Mode allows you to have a larger fire and a  
lower sound level, without the distribution blower.  
NOTE: During the useof this mode, if you keep  
increasing the temperature dial setting to increase  
the fire size, the distribution blower will automati-  
cally come on when the ESP Temperature reaches  
350o F, or 81%output.  
This setting will producea largeviewing firewithouta  
distribution blower operating.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Manual Start Up  
Starting First Fire  
Igniter Switch to"MANUAL"  
Fig. 4  
(down position)  
Make sure the unit is plugged into a 120 VAC, 60 HZ  
electrical source. The power light should be the only  
light lit.  
Fig. 3  
See Note  
7.  
1"  
1. Turn FEED ADJUSTER to desired feed rate.  
4
No. 4 is good for most pellets.  
2. Turn the MODE SELECTOR to “OFF” and  
then to the desired mode. This will reset con-  
trol and start the combustion motor.  
3. Turn the TEMPERATURE DIAL to the desired  
setting.  
Fig. 5  
5
4. Clean burn pot with scraper if necessary.  
5. Fill burn pot with pellets, only level with front  
edge. (Do Not Over Fill).  
1.Fines are small pieces ofbroken pellets (sawdust). Finesdo not  
flow easily and often build upon the hopper funnelbottom angles.  
These fines can be pushed into the feeder opening and then fill  
the hopperwith pellets. As the system works,they will be burned.  
2. The "TEST" cycle will operate the feeder motor forexactly one  
minute. Turning to "TEST" again and again may purge too much  
fuel into the burn potcausing excessive smoke on start-up.  
3.Thefirebox low pressure switch will notallow theauger motoror  
the igniter elementto operate if the view door orthe ash pan door  
are open.  
4.Adjust Feed Rate.If this isyour first fire or youare trying different  
pellets, set the feed adjuster to #4, Fig. 3. This is a conservative  
number andwill probably need to be increased. Afteryou know a  
feed rate setting that works well, use that setting. Remember, if  
your feed rate is too high you may waste fuel.  
6. Add starting gel on top of the pellets.Stir gel  
into pellets for fast lighting.  
7. Light starting gel with a match, and close the  
door. Operation will begin when the fire reaches  
the proper temperature.3  
8. Fill hopper with pellets and remove ashes as  
required.1, 6  
5. This is usually a weekly maintence procedure. Cleaning the  
burn pot with the scraper with a small amount of new fuel in the  
bottom is nota problem. First, scrape the ashes on the frontof the  
burn potinto the ash pan.Then scrape the holed surface downward  
into theburn pot.When the stove is ignited these scrapings will be  
pushed out by the feeder.  
6. The ash pan can hold the ashes from approximately 1 ton of  
premium fuel.This means the asheswill only need to be emptied  
a few times a year.  
7. Setting the feed adjuster # for maximum burn: With the unit  
burning in "AUTO",turn to "Stove Mode"and putthe fan on "H". Set  
the Temperature Dial to #7. Allow the unit to burn for about 30  
minutes andcheck ash on frontof burn pot. Fig.5.If the ash line is  
larger than 1", turn the feed adjuster from #4 to #5. Allow another  
30 minutes of burn time and check again.If , at #6 setting, a 1" or  
less ash bed is notobtainable, itis not a problem. The 1" ash bed  
is only a maximum burn rate and at most normal settings the ash  
bed will be larger.  
CAUTION  
The stove is hot while in operation.  
Keep children, clothing and furniture away.  
Contact may cause skin burns.  
Warning  
"NEVERUSE GASOLINE, GASOLINE-TYPE LANTERN  
FUEL, KEROSENE,CHARCOAL LIGHTER FLUID, OR  
SIMILAR LIQUIDS TO START OR "FRESHEN UP " A  
FIRE IN THIS HEATER. KEEP ALL SUCH LIQUIDS  
WELL AWAY FROM THE HEATER WHILE IN USE".  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
ESP Control  
Power Light  
Indicates power to the  
control.  
Feed adjuster  
Sets the maximum  
feed rate  
Test  
Runsallmotorsatfull  
speed forone minute  
to check operation.  
After twominutes the  
stove will go to  
minimum burn and  
the blowers will  
alternate fromhigh to  
low every minute to  
remind you that you  
are still in "Test  
Mode".  
Status Light  
Will be lit in either stove  
orroom tempmode when  
pointer is notwithin off  
positionband except  
after normalshutdown.  
Blinks to indicate errors  
listed below.  
Indicates power to  
distribution blower.  
Igniter switch  
Setto appropriate  
Start-Up mode.  
Indicates power to  
combustion blower  
Distribution Blower  
speedadjustmentrange.  
L = low  
H = high  
Indicates power to the  
feed motor.  
Variablespeedanywhere  
between L and H;  
although as the stove  
temp. goes up ,so does  
the lowend ofthe scale.  
Indicates power to the  
igniter.  
Mode Selector  
Temp dial  
Dealer Diagnostic Port  
Allows you to choose between  
RoomTemp Mode,StoveTemp  
Mode, orOFF.Alsoallows you  
to vary the distribution blower  
speed by turning the knob to  
the high or low side of each  
mode.  
Allows you to adjustthe room temperature in Room  
For dealermaintenance only.  
Requires specialDDMmonitor  
supplied to Harman Dealers  
exclusively.  
Temp Mode using the outerscale markedin degrees  
Fahrenheit. It also allows you to adjustthe stove  
temperature while in StoveTemp Mode using the  
inner scale marked from 1 to 7.  
Status light error messages:  
1 Blink: Indicates control board self diagnostic failure.  
This requires a manual reset*.  
3 Blinks: Indicates ESP (Exhaust Sensing Probe) fail-  
6 Blinks : Indicates that the control has calculated poor or  
incomplete combustion occurring for more than 50 min-  
utes. See Troubleshooting section for more details.  
A six blink status may be set if the stove is allowed to run  
out of pellets. To reset, turn mode selector to "OFF" then  
back on to the desired mode. If the unit was not out of pel-  
lets, see Troubleshooting section for more details.  
* Manual reset- disconnectpower cord for a fewseconds  
and reconnect. If error still occurs call your Dealer.  
NOTICE: Whenpower is givento the stove, the controlboard  
willblinkafewtimestoindicate currentversionofcontrolboard.  
This should not be confused with error messages.  
ure. This requires a manual reset*.  
4 Blinks: Can occur only in Room Temp Mode and indi-  
cates Room Sensing Probe failed or not installed. If a  
Room Sensing Probe is then installed, the status light  
will automatically reset.  
NOTE: Unit will not start in "AUTO" with this status error.  
5 Blinks (In Igniter Auto. Mode Only): Indicatesthatthe  
unithas failedto light after 4 consecutive igniter cycles, 32  
minutes total. To reset-TurnMode Selector to "OFF", then  
turn to either mode again.)  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
WheninstallingandoperatingyourHarmanAdvance  
Pellet Stove, respect basic safety standards. Read these  
instructions carefullybefore youattempt to installor oper-  
ate the Advance. Failure to do so may result in damage to  
property or personal injuryand mayvoid the product war-  
ranty.  
7"  
Consult with your local building code agency and in-  
surance representative before you begin your installation  
to ensure compliance with local codes, including the need  
for permits and follow-up inspections.  
7"  
Several issues must be addressed when selecting  
a suitable location for yourAdvance Pellet Stove. Observ-  
ingrequiredclearances tocombustible materials,the prox-  
imity to a safe chimneyor venting system, andthe acces-  
sibility of electrical supply must all be considered. In addi-  
tion, selecting a location that takes advantage of the  
building's natural air flow is also desirable to maximize  
the heating effectiveness of the heater. In many cases,  
this is a central location within the building.  
Fig.6  
1"  
Adequate combustionandventilationair mustbe pro-  
vided.  
Place the stove ona noncombustible floor or UL ap-  
provedfloor protector that extends 6 inches to the front, 6  
inches to the sides and1 inch to the rear of the stove. Fig.  
8.  
10"  
Place the stove awayfrom combustible walls at least  
as far as shown in figures 6, and 7.  
FLOOR PROTECTOR  
Note that the clearances shown are minimum for  
safetybutdonotleave muchroomfor accesswhenclean-  
ing or servicing. Please take this into account when plac-  
ing the stove.  
Fig.7  
Mobile Home Installation  
1"  
When installing this stove in a mobile home several  
requirements must be followed:  
1. The unit must be bolted to the floor. This can be  
done with 1/4" lag screws throught the 2 holes in  
the base plate shown in Fig. 13, Page 9.  
2. The unit must also be connected for the outside  
air. See page 12.  
3. Floor protection andclearances must be followed  
as shown above.  
4. Unit must be grounded to the metal frame of the  
mobile home.  
6"  
6"  
FLOOR  
PROTECTOR  
6"  
Fig.8  
Installationandrepair of this stove should be done by  
a qualified service person. The appliance should be in-  
spected before use and at least annually by a qualified  
service person. More frequent cleaning will be required. It  
is imperative that control compartments, burners, and cir-  
culating air passageways of the stove be kept clean.  
CAUTION: This appliance must be vented to the  
outside.  
Dueto hightemperatures, thestove shouldbe placed  
out of traffic and away from furniture and draperies.  
Children and adults should be alertedto the hazards  
of high surface temperatures and should stay away to  
avoid burn to skin and/or clothing.  
Young children should be carefully supervised when  
they are in the same room as the stove.  
Clothing and other flammable materials should not  
AFTER THE INSTALLATION IS COMPLETED  
Before the first fire is lit, check and record  
the high and low draft reading numbers on page  
10. Make adjustments to the low draft at this time,  
if necessary. See page 10.  
be placed on or near the stove.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removing Side Doors for Installation  
Removing Side Doors  
Figure 9  
Use hand hole to swing open side doors to at least  
90o.  
Figure 10  
Side  
Door  
Remove side doors by lifting upward on the door until  
the bottom pin is out of its hole. Move the bottom of  
the door out and away from the pedestal base about  
1/2". Allow the door to slide downward until the top  
door pin is out of its top hole.  
Fig. 9  
NOTE: Always remove the side doors and rear  
shields to move theunit. This will keep them from  
getting damaged.  
Removing the Rear Motor Shield Sheet Metal.  
Side Door  
Magnets  
NOTE: Disconnect power to the unit before  
removing the motor shields. Danger of electrical  
shock. Hot and moving parts could cause injury.  
Figure 11  
There are (2) #10 hex head screws holding each rear  
shield. Using a 5/16" nut driver or socket, loosen the  
(2) screws about 4 or 5 turns.  
Fig.10  
Figure 12  
Slide the rear shields straight outward until the ends  
come out of the rear retaining clips, as seen in Fig.13.  
Rear  
Shield  
Rear  
Shield  
Placing Rear Shields Back on Unit  
1. When replacing the shields, always insert the top  
and bottom ends of the sheet metal into the retaining  
clips first.  
2. Slide the shields straight inward until the (2) hex  
head screws are fully inserted into the stove slots.  
3. Make sure the top edges of the shield are against  
the hopper bottom and tighten screws.  
Fig.12  
Fig.11  
Rear ShieldRetaining clip  
Rear Shields are split around the Flue Tail pipe and  
outside Air Hole Knockout. This will allow removal and  
installation of the rear shields with the unit completely  
installed.  
Rear  
Shield  
Fig.13  
Outside Air  
Flex Hole  
Knockout  
SkidHold Down  
Screws  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Low Draft Voltage Adjustment  
Combustion  
Motor Speed  
Control  
Low draft only  
set point.  
The small straight  
screwdriver slot is  
plastic;therefore,  
the unit can be  
adjustedwhile in  
operation.  
Fig.15:  
Draft Meterbolt hole location  
Fig.14  
A simple draft test should be performed after  
completing the flue pipe installation. To record the  
results for future reference:  
1. Plug unit into a 120VAC, 60 HZ outlet.  
2. Close the hopper lid, front view door, and the ash  
pan. Neither pellets or a fire are required for this test.  
3. With the mode selector in the "OFF" position, turn  
the feed adjuster to "TEST".  
These units are pre-tested at the factory with  
Fig.1  
exactly 120 Volts A.C., 60 Hz. They are checked and  
adjusted for firebox tightness, gasket leakage, motor  
operation and igniter operation. The Advance is then  
factory set at a mid-point adjustment and in most cases  
will not need any adjustments. NOTE: The factory low  
draft setting may not be correct for the unit's  
permanent installation conditions.  
4. Record the high draft_____in W.C. (Normal is -.50  
to -.60) The control will be on the High Draft for a total  
of 2 minutes.  
5. After 2 minutes is up, the combustion motor will go  
down to low draft and the distribution blower will go on  
high. Allow approximately 15 seconds to pass for the  
combustion motor to slow before checking the low  
draft.  
The control board on the Advance is equipped  
with a low draft adjustment port. Located on the control  
face just to the right of the igniter light. See Figure 14.  
This voltage adjustment is provided to allow the unit to  
be adjusted for the household voltage where the unit is  
going to be in permanent operation. NOTE: The line  
voltage varies from area to area and often home to  
home.  
6. If the low draft is between .35 and .45, record the  
reading _____ in W.C. If the reading is higher, slowly  
turn the set screw counter-clockwise until the draft  
lowers. If the reading is lower, very slowly turn the set  
screw clockwise until the draft increases.  
NOTE: The test mode alternates from high to low  
draft every 60 seconds. If more time is needed  
for draft adjustment, wait until the next low draft  
cycle.  
The low draft voltage should be adjusted to  
achieve the most efficient burn on low burn or  
"maintenance". This voltage adjustment allows the  
installer to change the lowvoltage setpoint approximately  
15 volts. This adjustment should be done by the installer  
during set up because a draft meter reading isrequired  
to insure proper set up.  
If the unit is not adjusted properly, it does not  
cause a safety concern. If the unit is adjusted too high,  
only effiency is lost. If the unit is adjusted too low, the low  
draft pressure switch will not allow the feeder motor or  
the igniter to operate.  
NOTE: In some cases, the draft may not go as low  
as .35 even with the set screw completelycounter-  
clockwise.  
MODIFICATIONS  
High Altitude(7,000- 10,000ft.)A combustion  
fan blade change can be made by an authorized  
Harman Dealer. These changes must be done with  
the use of a draft meter. These changes affect the low  
and high burn rate air to fuel ratios.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Room Sensor and Air Grill Installation  
Gold Air Grill Installation  
Room Sensor Installation  
Fig. 17  
Fig. 16  
The room sensor is a small temperature sensor  
on the end of a 60" gray wire. This sensor is installed  
much like a standard wall thermostat. Because it is so  
small, it can be hidden along the trim of a doorway or  
even up the leg of a coffee table. There is a remote  
room sensor porton the rear of the unitfor easy exter-  
nal connection. Use standard 18-2 thermostat wire to  
extend the distance to the desired location (100' maxi-  
mum). The room sensor should be installed in the lo-  
cation where you want to control the temperature.  
NOTE: Distances of more than 25 feet from the  
unit or in another room are not recommended. It is  
recommended that the room sensor be installed, even  
if only installed on the rear of the unit as a return air  
sensor. The roomsensor isessential for the Advance's  
excellent efficiency.  
Insert the two tail end hooks of the Air Grill Assembly  
up under the stove top edge. Insert inward until the  
two center hooks drop into the stove body slots in the  
front of the unit.  
REMINDERS  
Hopper Lid  
Foam Gaskets  
Fig. 18  
Do not allow pellets or sawdust to build up on the  
hopper lid gasket.  
Inspectthe hopper lid gasket for damage. A good  
hopper lid seal is very important for proper  
operation.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
Acombustion blower is usedto extractthe com-  
bustion gases from the firebox. This causes a nega-  
tive pressure in the firebox and a positive pressure  
in the venting system as shown in fig. 19. The longer  
the vent pipe and more elbows used in the system,  
the greater the flow resistance. Because of these  
facts we recommend using as few elbows as pos-  
sible and 15 feet or less of vent pipe. The maximum  
horizontal run should not exceed 48". If more than  
15 feet of pipe is needed, the diameter should be  
increasedfrom3" to4" becausea larger pipe causes  
less flow resistance. Be sure to use approved  
pellet vent pipe wall and ceiling pass- through  
fittings to go through combustible walls and  
ceilings. Be sure to use a starting collar to attach  
the venting system to the stove. The starting col-  
lar must be sealed to the stove with high temp  
silicone caulking.  
Vent Pipe  
Pellet venting pipe ( also known as PL vent ) is  
constructed of two layers with air space between  
the layers. This air space acts as an insulator and  
reduces the outside surface temperature to allow a  
clearance to combustibles of only 3 inches. The  
sections of pipe lock together to form an air tight  
seal in most cases; however, in some cases a per-  
fect seal is not achieved. For this reason and the  
fact that the Advance operates with a positive vent  
pressure, we specify that the joints also be  
sealed with clear silicone.  
Fig.19  
+ = Positive static pressure  
= Negative static pressure  
Outside Air  
Outside air is optional except in mobile homes  
and where building codes require. The benefit of  
outside air is mainly noticed in small, very tight  
houses.  
Room Sensor  
Connection Ports  
To install outside air use 2 3/8" I.D. flex pipe  
partnumber 2-00-08543. There is abreak-awayhole  
on the rear panel which must be removed before  
connecting the flex pipe. The pipe should be run out-  
side and terminate to the side or below the vent pipe  
outlet so the flue outlet is more than 12" from the  
inlet cover. The maximum length run of this pipe is  
15 feet. If a longer run is needed, the size must be  
increased to 3". Inlet cover part number 1-10-08542  
should be used to keep birds, rodents, etc. out of  
pipe.  
Outside airflex pipe  
goes here  
Flex pipe part#  
2-00-08543  
HRV  
Wheninstalling ina house with a Heat Reclaim-  
ing Ventilation System (HRV) be sure the system is  
balanced and is not creating a negative pressure in  
InletCover part#  
1-10-08542  
12 the house.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
#1 Preferred method  
This method provides excellent venting for nor-  
mal operation and allows the stove to be installed clos-  
est to the wall. One inch from the wall is safe; how-  
ever, two or three inches allows better access to re-  
move the rear panel. The vertical portion of the vent  
should be three to five feet high. This vertical section  
will provide natural draft in the event of a power failure.  
3 ft.  
to  
combustibles  
Fig.20  
#2 Preferred method  
This method also provides excellent venting for  
normal operation but requires the stove to be installed  
farther from the wall. The vertical portion of the vent  
shouldbethree tofive feethighandatleastthree inches  
from a combustible wall. This vertical section will pro-  
vide natural draft in the event of a power failure.  
CAUTION  
KEEP COMBUSTIBLES (SUCH AS  
GRASS, LEAVES, ETC.) AT LEAST 3  
FEET AWAY FROM THE FLUE OUTLET  
ON THE OUTSIDE OF THE BUILDING.  
3 ft.  
to  
Fig.21  
combustibles  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
#3 Installing into an existing  
chimney ( US only )  
This method can be used for normal operation.  
This method also provides natural draft in the event  
of a power failure. If the chimney condition is ques-  
tionable you may want to install a liner as in method  
#6.  
Fig.22  
#4 Installing into an existing  
fireplace chimney ( US only )  
This method can be used for normal operation.  
This method also provides natural draft in the event  
of a power failure.  
The damper area must be sealed with a steel  
plate or fiberglass. A cap should be installed on the  
chimney to keep out rain. If the chimney condition is  
questionable you may want to install a liner all the  
way to the top as in Method #5.  
Fig.23  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
#5 Installing into an existing fireplace  
chimney ( US and Canada)  
This method provides excellent venting for nor-  
mal operation. This method also provides natural draft  
in the event of a power failure.  
In Canada and some places in the US it is re-  
quired that the vent pipe extend all the way to the top  
of the chimney.  
In this method a cap should also be installed on  
the chimney to keep out rain. Be sure to use approved  
pellet vent pipe fittings. Seal pipe joints with silicone in  
addition to the sealing system used by the manufac-  
turer. Pipe size should be increased to 4" using this  
method.  
Fig.24  
#6 Installing into an existing  
chimney ( US and Canada )  
This method provides excellent venting for nor-  
mal operation. This method also provides natural  
draft in the event of a power failure.  
In Canada and some places in the US it is re-  
quired that the vent pipe extend all the way to the top  
of the chimney. The pipe or liner inside the chimney  
should be 4"diameter.  
In this method a cap should also be installed  
on the chimney to keep out rain.  
Fig.25  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
Stormcollar  
Flashing  
12" min.  
3" min.  
3" min.  
3" min.  
PLvent manufacturer's  
firestop spacer and  
support.  
No insulation or other  
combustible materials  
areallowedwithin3" of  
the PL vent pipe.  
Fig. 27  
Fig. 26  
#7 Installing through the ceiling vent  
Minimum flue vent configuration  
Through the ceiling vent, follow PL vent  
manufacturer's recommendations when using wall  
and ceiling pass through.  
It is recommended that outside air be installed with  
this venting configuration.  
Fig. 28  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
I. The clearance to service regulator vent outlet  
must be a minimum of 6 feet.  
Requirements for Terminating the  
Venting  
WARNING: Venting terminals must not be re-  
cessed into a wall or siding.  
1
J. The clearance to a non-mechanical air sup-  
ply inlet to the building or the combustion air inlet to  
1
any other appliance must be a minimum of 48”.  
NOTE:Only PL vent pipe wall pass-throughs and  
fire stops should be used when venting through com-  
bustible materials.  
NOTE: Always take into consideration the effect  
the prevailing wind direction or other wind currents will  
cause with flyash and /or smoke when placing the ter-  
mination.  
In addition, the following must be observed:  
A. The clearance above grade must be a mini-  
mum of 18".1  
B. The clearance to a window or door that may  
be opened must be a minimum of 48" to the side, 48"  
below the window/door, and 12" above the window/  
door.1  
K. The clearance to a mechanical air supply  
inlet must be a minimum of 10 feet.  
(with outside air installed, 6 feet )  
L. The clearance above a paved sidewalk or a  
paved driveway located on public property must be  
a minimum of 7 feet.1,2  
1
M. The clearance under a veranda, porch,deck  
1,3  
or balcony must be a minimum of 12 inches.  
NOTE: The clearance to vegetation and other  
exterior combustibles such as mulch is 36” as mea-  
sured from the center of the outlet or cap. This 36”  
radius continues to grade or a minimum of 7 feet  
below the outlet.  
1CertainCanadian andor Local codes or regu-  
lations may require different clearances.  
2Avent shallnot terminate directly above a side-  
walk or paved driveway which is located between  
two single family dwellings and serves both dwell-  
ings.  
( with outsideair installed,18)  
C. A12" clearance to a permanently closed win-  
dow is recommended to prevent condensation on  
the window.  
D. The vertical clearance to a ventilated soffit lo-  
cated above the terminal within a horizontal distance  
3Only permitted if veranda, porch, deck, or bal-  
of 2 feet (60 cm) from the center-line of the terminal cony is fully open on a minimum of 2 sides beneath  
the floor.  
must be a minimum of 18".  
E. The clearance to an unventilated soffit must  
be a minimum of 12".  
F. The clearance to anoutside corner is 11" from  
center of pipe.  
NOTE: Where passage through a w all, or  
partition of combustible construction is desired,  
the installation shall conformto CAN/CSA-B365.  
(if in Canada)  
G. The clearance to an inside corner is 12".  
H. A vent must not be installed within 3 feet (90  
cm) abovea gasmeter/regulator assemblywhenmea-  
1
sured from the horizontal center-line of the regulator.  
Inside  
Corner  
Detail  
Fixed  
Closed  
Fixed  
Closed  
Openable  
Openable  
= Vent terminal  
= Air supply inlet  
= Area where terminal is not permitted  
A
V
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Venting  
DO NOT INSTALL A FLUE DAMPER IN THE  
EXHAUST VENTING SYSTEM OF THIS UNIT.  
WARNING  
DO NOT INSTALL IN SLEEPING ROOM  
DO NOT CONNECT THIS UNIT TO A  
CHIMNEY FLUE SERVING ANOTHER  
APPLIANCE.  
CAUTION  
THE STRUCTURAL INTEGRITY OF THE  
MOBILE HOME FLOOR, WALL, AND  
CEILING/ROOF MUST BE MAINTAINED.  
INSTALL VENT AT CLEARANCES  
SPECIFIED BY THE MANUFACTURER  
CAUTION  
KEEP COMBUSTIBLES AWAY  
FROM FLUE OUTLET.  
Mobile home installation should be done in  
accordance with the Manufactured Home  
and Safety Standard (HUD), CFR 3280,  
Part 24.  
WARNING  
3'  
Keepcombustible materials such as  
grass, leaves,etc. atleast 3 feetaway  
fromthe pointdirectly under the vent  
termination.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance - Emptying Ashes  
Ash Pan Removal and Reattachment  
Figure 29  
Open side doors.  
Figure 30  
Release spring latches on the right and left side of the ash  
pan.  
Fig. 29  
Figure 31  
Slide ash pan forward enough to lift with center handle.  
Empty ashes and reinstall ash pan.  
Ashes should be placed in a metal container with a  
tight fitting lid. The closed container of ashes should  
be placed on a noncombustible floor or on the ground,  
well awayfrom all combustible materials, pending final  
disposal. If ashes are disposed of by burial in soil or  
otherwise locallydispersed, theyshould be retained in  
the closed container until all cinders have thoroughly  
cooled.  
Fig. 30  
Figure 32  
Inspect the gasket rope for damage. Replace if necessary.  
Figure 33  
Insert spring latch front hooks into the ash pan side slots.  
Push both latches to the rear at the same time to latch.  
Fig. 31  
Fig. 32  
Fig. 33  
Soot and Fly Ash  
The products of combustion will contain small particles  
of fly ash. The fly ash will collect in the exhaust venting sys-  
tem and restrict the flow of the flue gases. Incomplete com-  
bustion, such as occurs during startup, shutdown, or incor-  
rect operation of the room heater, will lead to some soot for-  
mation which will collect in the exhaust venting system. The  
exhaust venting system should be inspected at least once  
each year to determine if cleaning is necessary.  
When removing the ash pan to empty ashes, you will  
note a build up of ash fines behind the ash pan. This space  
behind the ash pan was designed to allow the fines to fall out  
of the vertical heat exchangers and collect where they are  
easily cleaned out, rather than going into the flue pipe where  
it would be difficult to clean. These fines should not be al-  
lowed to build up. They may not allow the ash pan to be  
seated into its gasketproperly.NOTE: If an extreme amount  
of force is required to snap the latch on one or both  
sides of the ash pan, thearea behind the ash pan should  
be checked for ash fine build up.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance - Cleaning Glass on View Door  
WARNING  
Door latch may  
Opening and Closing the View Door  
Opening:  
be hot!  
The view door must be opened for cleaning of  
the glass and scraping of the burn pot. This should be  
done with the unit off and cool, in most cases. Although  
the glass can be cleaned and burn pot scraped while  
Receiving Bolt  
the unit is at low burn.  
1. Using scraper as shown in Fig. 34and 35, lift the  
door latch forward and up.  
2. Swing the door open to the left, stopping the swing  
when resistance is felt. Forcing the door open further  
then was designed may cause damage to the door or  
Fig. 34  
it's hinges.  
CAUTION  
Do not put excessive downward pressure on the  
latch end of the door while in the open position.  
If thedoor is goingto be openedfor anextendedperiod  
of time, it is suggested that it be removed (see Fig. 36)  
and set safely aside.  
3. Inspect the door gasket and glass gaskets for worn  
or missing pieces. Replace if necessary. (Fig. 37)  
Closing:  
When closing the door, always hold the door  
latch all the way up until it has caught the receiving  
bolt. Then push the latch downward and back until the  
door is fully seated. See Fig. 35.  
Fig. 35  
Fig. 36  
Fig. 37  
Removing View Door:  
To remove the view door from the stove, hold  
the door by the bottom and lift upward off of the hinge  
pins.See Fig. 36.  
Inspect the door gasket.See Fig. 37.  
REPLACE GLASS WITH  
CERAMIC GLASS ONLY.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance - Burn Pot  
Burn Pot Cleaning and  
Maintenance  
1. Scrape the top holed surface and sides of the  
burn pot.(Fig 38) It is not necessary to completely  
remove all material from the burn pot. The excess  
will be pushed out during the next use.  
2. Loosen the (2) wing thumb screws on the lower  
front angle of the burn pot. (Fig. 38)  
3. Lift off the clean-out cover (Fig.39) to open the  
bottom clean-out chamber. (Fig.40)  
DANGER  
Disconnect the power to the unit before  
removing cover.  
Fig. 38  
4. Clean ashbuildup frominside the chamber while  
cover is off. Use the scraper to tap on the top front  
edge of the burn pot. This will help knock pieces of  
ash, loosened by the scraping process, down  
through the holes. It also helps knock scale off of  
the igniter element.  
Figure 40  
The igniter is made to be removable for  
service by insulated male/female wire connectors.  
These connections between the hot leads (the  
wires inside the burn pot) and the cold leads (the  
wires from the control board) are always pulled to  
the rear of the feeder body.(Not coiled inside the  
burn pot.)  
It is very important that these connections  
are to the inside rear of the feeder body. Also, the  
extra wire of the igniter wire service loop must be  
pulled out through the rear of the feeder and tied  
up so that it will not be damaged by any moving  
parts. See page 25.  
Fig. 39  
Burn pot igniter  
DANGER  
Disconnect the power to the unit before  
removing cover.  
Warning  
Use caution when cleaning burn pot clean-  
out chamber. Do not damage the high  
temperature igniter wires.  
Igniter hot leadwires  
(high temperature)  
Note: The hot lead/cold lead connection  
must always be pulled to the rear of the  
feeder body before operation.  
Fig. 40  
Viewed from below through the ash pan  
opening.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance - Flame Guide and Brick Panel  
Firebox Brick Panel  
Flame Guide and Brick Panel  
Flame Guide/  
Brick panel  
holder  
Removal for Cleaning  
Burn pot  
Fig. 41  
Figure 42  
Slidebrick panelstraightupwardwith bothhands.  
Fig. 42  
Figure 43  
While holding the brick panel up with one hand,  
remove theflame guidefrom the top of theburn  
pot.  
Fig. 43  
Figure 44  
Slide the brick panel into the left corner of the  
fireboxwiththe panel resting on the top edges of  
theburnpot. Rotatetheright sideofthebrick panel  
throughthe dooropening.  
Fig. 44  
Reversethis operationto reinstall the brick panel  
aftercleaning.  
Fig. 45  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance - Combustion Intake Cover  
CoverRetainer Handle  
Cleaning and Maintenance for the  
Combustion Intake Cover  
You will need to remove the combustion  
intake coverto cleanthe fanblades and rearflue  
tube.  
Figure 46  
Rotatetheretainercoverhandlecounter-clockwise  
o
upward as far as itwill go (approximately90 ).  
Fig. 46  
Combustion  
Intake Cover  
These surfaces mustbe even to  
closeretainer handle.  
Figure 47  
Holdtheintake coverhandleandpull until theside  
ofthecover attheretainerhandle endcomes away  
o
from the stove body, approximately 15-20 , slide  
therightside tab outof the retaining slot.  
Figure 48  
Clean and inspect the fully exposed combustion  
fan bladeand fluetube.  
Fig. 47  
RightSide Tab  
Reinstall the combustion intake cover by  
firstsliding the right side tab into the retainer slot  
seenin Figure 47.  
IntakeCover Handle  
Right Side Retaining Slot  
Rotate the cover inward until the cover fits  
intoits hole.  
Make sure the two faces (Fig.46) of the  
coverandretainer spacerareevenand rotatethe  
retainerhandle clockwise until it stops.  
ESP Probe  
(in rear of flue  
tube)  
CAUTION  
Excessive cleaning force could bend the  
small stainless steel ESP Probe, causing  
damage.  
Fig.48  
Combustion Fan Blade  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance - Heat Exchanger  
Cleaning the Heat Exchanger  
System  
Slot  
1.Removebrickpanelandflameguide. SeePg22.  
2. Remove the ash pan. See Page 19.  
3. Remove flue baffles located on each side of  
theburnpot, seeFig. 49& 50. The baffleis heldin  
place by inserting the tab into the slot (located  
towardtheoutside ofthefirebox)and restingiton  
thehook tablocated beside theburnpot.  
4. Pull the pointed end of the baffle slightly front  
with onehand whilepushing upfrom below with  
the other hand. See Fig. 50.  
Tab  
Hook Tab  
Fig. 49  
5. With the baffle released from the tabs, rotate  
the pointed end toward the door opening. Lift  
baffle up andout.  
The right andleft baffle areinterchangeable.  
6. Now remove the heat exchanger baffleplates.  
See Fig. 51 & 52. To remove the left plate, slide  
the center lock to the right. To remove the right  
plate, slide the center lock to the left. (The right  
and leftplates areinterchangeable.)  
Fig. 50  
Center Lock  
This will allow access toall oftherearvertical heat  
exchangersurfaces.  
7. Withall fourbaffleplates removed, cleaningcan  
be performed with the arrow end of the scraper.  
See Fig. 53.  
Fig. 51  
8. Scrape all of the heat exchanger surfaces.(Be  
sure to clean any internal ledges where fly ash  
could have collected.)  
Center Lock  
Fig. 52  
TopAccordian  
Heat Exchangers  
Rear Firewall  
Heat Exchanger  
Fig. 53  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble-Shooting  
FEEDER DOES NOT FEED  
4. Feed motor or draft motor has failed.  
5. Power failure or blown fuse.  
1. No pellets in hopper.  
2. Firebox draft may be too low for low draft pres-  
sure switch in feeder circuit to operate.Check for  
closed doors, loose or missing gasket on doors  
or hopper lid, faulty pressure switch.  
3. Feed motor will not run until ESP  
senses 165 deg. F. Maybe you did not put  
enough pellets in the burn pot before lighting the  
fire.  
SMOKE IS VISIBLE COMING OUT OF VENT  
1. Air-fuel ratio is too rich.  
A. Feed rate too high.  
B. Draft too low caused by a gasket leak.  
LOW HEAT OUTPUT  
1. Feed rate too low  
4. Something is restricting flow in the hopper or  
causing the slide plate to stick.  
5. Feed motor has failed.  
2. Draft too low because of gasket leak.  
3. Poor quality or damp pellets  
4. Combination of 1. and 2.  
Helpful Hints  
PARTIALLY BURNED PELLETS  
1. Feed rate too high.  
Cleaning Burn Pot  
2. Draft too low. (Check burn pot clean out slide  
and door gasket).  
3. Burn pot or heat exchanger may need to be  
cleaned.  
Whenever your stove is not burning, take the op-  
portunity to scrape the burn pot to remove carbon  
buildup. A vacuum cleaner is handy to remove the resi-  
due. Be sure the stove is cold if you use a vacuum.  
Carbon buildup can be scraped loose with the fire  
burning using the special tool provided with your stove.  
Scrape the floor and sides of the burn pot. The carbon  
will be pushed out by the incoming fuel. Always wear  
gloves to do this.  
4. Combination of all the above.  
5. #6 status blink: A 6 blink control board status  
indication is caused by poor or incomplete com-  
bustion. The Advance Automatic Ignition circuit  
boardhas the abilityto track the combustion through  
feed settings and ESP temperatures. When the  
control board has calculated poor or incomplete  
combustion it will shut down the unit as a safety  
feature. (Poor or incomplete combustion is a con-  
tributor of creosote which may cause a chimney  
fire)  
A 6 blink status may be caused by several things:  
1. Blocked or partially blocked flue.  
2. Blocked or partially blocked inlet air.  
a. backdraft damper on the inlet pipe may be  
stuck closed.  
Removing Ashes  
Turn the Temp Dial to number 1 approximately 30  
minutes before removing ashes. This will result in a  
cooler stove and ash pan.  
Maximum Feed Adjuster settings are not needed  
in most cases. Operating in the normal range (#4) is  
recommended when maximum heat output is not re-  
quired. The ESP probe prevents the stove from being  
over-fired.  
Keep the stove free of dust and dirt.  
b. if outside air is installed the inlet cover may be  
blocked.  
3. The air chamber under the burnpot may be filled  
with fines and small bits of ash.  
4. The holes in the burnpot may be getting filled  
with ash or carbon buildup.  
5. Combustion blower fan blades may need  
cleaned.  
Fuel  
Pellet fuels are put into 3 categories in terms of ash  
content. Premium at 1% or less, Standard at 3% or less  
and all others at 3% or more.  
TheAdvance is capable of burning all3 categories of  
pellets due to a patented feeder and burn pot system.  
It should be noted, however, that higher ash content  
will require more frequent ash removal and may provide  
less BTU's per pound. Normally, standard and high ash  
pellets cost less than premium pellets and can be cost  
effective when burned in the Advance.  
The moisture content must not exceed 8%. Higher  
moisture will rob BTU's and may not burn properly.  
Higher moisture contentinthe fuelmay showas con-  
densation on hopper lid and possibly form rust inside the  
hopper.  
6. No fuel in hopper.  
SMOKE SMELL  
Seal the vent pipe joints and connection to stove  
with silicone.  
FIRE HAS GONE OUT  
1. No pellets in hopper.  
2. Draft setting is too low.  
3. Something is restricting fuel flow.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
20.5"  
7.750"  
7.750"  
5.250"  
26.625"  
C
L
Weight  
250 lbs.  
Blower  
Hopper Capacity  
Fuel  
135 cfm  
60 lbs.  
Wood Pellets  
Outside Air Size  
Fuse Rating  
BTU Range  
Feed Rate  
2 3/8 inches  
6 amp  
0 to 48,000  
1.0 lbs./hr. on minimum  
6 lbs./ hr. on maximum  
3 inch Pellet Vent Pipe  
Flue Size  
Maximum Wattage  
Start Cycle Wattage  
Normal Run Wattage  
480 Watts (Start cycle and test)  
340 Watts  
275 Watts  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advance Wiring Diagram  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advance Feeder Assembly  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advance Parts List  
Description  
Part Number  
3-44-375501  
2-00-06610-1  
2-00-06610-2  
1-10-06620  
3-20-08727  
1-10-08736  
2-00-06616  
2-00-06617  
Hopper Gasket (6')  
Left Side Door Assembly  
Right Side Door Assembly  
Igniter Element Assembly  
Wiring Harness Assembly  
Burn Pot Weldment  
Right Rear Shield  
Left Rear Shield  
Flue Baffle (2)  
2-00-06632  
Arrow Scraper  
Flame Guide  
2-00-773850  
3-00-06644  
Thermister Probe  
3-20-00744  
Room Sensor  
3-20-00906  
Circuit Board  
3-20-05374  
3" White CCW Fan Blade  
Differential Switch  
4-3/4" Single Fan Blade  
Combustion Blower  
Distribution Blower  
Spring Latches (2)  
White/Black Control Knob  
Control Knob Shaft  
Round Magnet (4)  
Brick Panel  
3-20-08789  
3-20-9301  
3-21-00661  
3-21-08639  
3-21-22647  
3-31-00927  
3-31-605  
3-31-015  
3-31-08569  
3-00-06641  
Front Glass  
3-40-08728  
SideGlass (2)  
3-40-08729  
Hopper Lid Knob  
3-43-02000  
View Door Frame  
Grill  
Glass Divider Trim - Black only (2)  
Burn Pot Gasket  
3-43-06613 (Gold -4, Black Nickel -5)  
3-43-06642 (Gold -4, Black Nickel -5)  
3-43-08754  
3-44-00409  
3/8" Rope for Ash Pan Assembly (5')  
Tailpipe Gasket  
3-44-00888  
3-44-06179  
Black Glass Gasket (6')  
Tadpole Rope for View Door (1)  
Wiring Diagram  
3-44-2312  
2-00-71611  
3-89-06653  
Control Panel Sticker  
Owner's Manual  
3-90-06655A  
3-90-09730  
Hopper Lid Label  
3-90-09416  
Combustion Intake Weldment  
Ash Pan Assembly  
Ball Plunger  
1-10-07574  
1-10-07581  
3-31-5500  
Hopper Lid Glass  
3-40-06693  
Top Gasket (5')  
Combustion Blower Studs (3)  
3-44-375501  
3-31-54383208  
Options:  
Outside Air Assembly  
3' Flex Pipe  
5" Single Fan Blade for High Altitude  
3 Piece Ceramic Top Inserts  
45o Tailpipe Weldment  
1-10-08542  
2-00-08543  
3-20-40985  
3-43-03000  
See page 29 for  
1-10-247129  
Feeder Part Numbers  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Harman Gold Warranty  
HARMAN GOLD WARRANTY  
6 YEAR TRANSFERABLE LIMITED WARRANTY  
(Residential)  
1 YEAR LIMITED WARRANTY (Commercial)  
Harman Stove Company warrants its products to be free from defects in material or workmanship, in normal use and  
service, for a period of 6 years from the date of sales invoice and for mechanical and electrical failures, in normal use and  
service, for a period of 3 years from the date of sales invoice.  
If defective in material or workmanship, during the warranty period, Harman Stove Company will, at its option, repair  
or replace the product as described below.  
The warranty above constitutes the entire warranty with respect to Harman Stove Company products. HARMAN  
STOVE COMPANY MAKES NO OTHER WARRANTY, EXPRESSED OR IMPLIED, INCLUDING “ANY” WAR-  
RANTY OF MERCHANTABILITY, OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. No employee,  
agent, dealer, or other person is authorized to give any warranty on behalf of Harman Stove Company. This warranty does  
not apply if the product has been altered in any way after leaving the factory. Harman Stove Company and its agents assume  
no liability for “resultant damages of any kind” arising from the use of its products. In addition, the manufacturer and its  
warranty administrator shall be held free and harmless from liability from damage to property related to the operation, proper  
or improper, of the equipment.  
THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF.  
THESE WARRANTIES APPLY only if the device is installed and operated as recommended in the user’s manual.  
THESE WARRANTIES WILL NOT APPLY if abuse, accident, improper installation, negligence, or use beyond rated  
capacity causes damage.  
HOW TO MAKE A CLAIM - Any claim under this warranty should be made to the dealer from whom this appliance  
was purchased. Then contact is made with manufacturer, giving the model and serial numbers, the date of purchase, your  
dealer’s name and address, plus a simple explanation of the nature of the defect. Extra costs such as mileage and overtime  
are not covered. Nuisance calls are not covered by these warranties.  
THIS WARRANTY IS LIMITED TO DEFECTIVE PARTS - REPAIR AND/OR REPLACEMENT AT  
HARMAN STOVE COMPANY’S OPTION AND EXCLUDES ANY INCIDENTAL AND CONSEQUENTIAL  
DAMAGES CONNECTED THEREWITH.  
WARRANTY EXCLUSIONS: Failure due, but not limited to, fire, lightning, acts of God, power failures and/or surges,  
rust, corrosion and venting problems are not covered. Damage and/or repairs including but not limited to; remote controls,  
filters, fuses, knobs, glass, ceramic brick panels, ceramic fiber afterburners, door packing, tile, ceramic log sets, paint,  
batteries or battery back-up and related duct work are not covered. Also excluded from this warranty are consumable or  
normal wear items including but not limited to; flame guides, grates, coal bars, afterburner hoods, fire brick, gaskets.  
Additional exclusions for corn stoves are burnpot housing weldment, burnpot grate weldment (pellet or corn), burnpot front  
plate (pellet or corn), burnpot front plate lock, corn auger extension, ceramic insert, and ceramic insert plate. Additional or  
unusual utility bills incurred due to any malfunction or defect inequipment and the labor cost of gaining access to or removal  
of a unit that requires special tools or equipment are not covered. Maintenance needed to keep the stove in “good operating  
condition” is not covered. This includes, but is not limited to, cleaning, adjustment of customer controls and customer  
education. Labor, materials, expenses and/or equipment needed to comply with law and/or regulations set forth by any  
governmental agencies are not covered.  
This Warranty provides specific legal rights and the consumer may have other rights that vary from state to state.  
In the event of change in ownership, the remaining portion of this warranty may be transferred to the new owner by  
sending the new owner information and a transfer fee of $25.00 US to the Harman Stove Company.  
PLEASE READ THE LITERATURE BY THE MANUFACTURER FOR THE VARIOUS ACCESSORY DEVICES.  
THE MANUFACTURER WARRANTS THESE ACCESSORY DEVICES, NOT HARMAN STOVE COMPANY OR  
THEIR WARRANTY ADMINISTRATOR. FURTHERMORE, THESE ACCESSORY DEVICES MUST BE INSTALLED  
AND USED ACCORDING TO THE RECOMMENDATIONS OF THE MANUFACTURER.  
REMEDIES - The remedies set forth herein are exclusive and the liability of seller with respect to any contract or sale  
or anything done in connection therewith, whether in Contract, in tort, under any warranty, or otherwise, shall not, except  
as herein expressly provided, exceed the price of the equipment or part of which such liability is based.  
CLARIFY - The above represents the complete warranty, which is given in connection with stoves, manufactured by  
Harman Stove Company. No other commitments, verbal or otherwise, shall apply except by a written addendum to this  
warranty.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Baby Playpen PD243033A User Manual
Hasselblad Digital Camera 503CW CFV User Manual
Honeywell All in One Printer VG1250 QS Rev B User Manual
Honeywell Cooktop Central Heating Cooker Natural Gas User Manual
Honeywell Thermostat 8162 User Manual
Hotpoint Refrigerator HTS18ICP User Manual
HP Hewlett Packard Projector Projectors User Manual
Huawei Cell Phone MC850 User Manual
Hypertec Carrying Case 3901 User Manual
IMC Networks Switch PD Switch User Manual