Carrier Indoor Furnishings 48 50HJ004 014 User Manual

COBRA™ Energy Recovery Units  
48/50HJ004-014 with 62AQ060-300  
Single-Package Rooftop Units  
with Energy Recovery Capability  
Installation, Start-Up,  
and Service Supplement  
SAFETY CONSIDERATIONS  
IMPORTANT: This is a supplemental instruction for the  
48/50HJ and the 62AQ Installation, Start-Up and Service  
Instructions. It is not intended to take the place of either  
instruction or to be a complete piece in itself.  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should  
install, repair, or service air-conditioning equipment.  
Untrained personnel can perform basic maintenance func-  
tions of cleaning coils and filters and replacing filters. All other  
operations should be performed by trained service personnel.  
When working on air-conditioning equipment, observe precau-  
tions in the literature, tags and labels attached to the unit, and  
other safety precautions that apply.  
Verify that the power source supplied to the unit matches  
the voltages and amperages listed on the unit rating plate.  
Follow all safety codes. Wear safety glasses and work  
gloves. Use quenching cloth for unbrazing operations. Have  
fire extinguishers available for all brazing operations.  
CONTENTS  
Page  
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1  
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29  
Step 1 — Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . 2  
Step 2 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 2  
• ROOF CURB  
Step 3 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 3  
Step 4 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 6  
POSITIONING  
Step 5 — Install Flue Hood (48HJ Only) . . . . . . . . . 11  
Step 6 — Install Gas Piping (48HJ Only). . . . . . . . . 11  
Step 7 — Install External Trap for Condensate  
Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Step 8 — Make Electrical Connections . . . . . . . . . . 11  
• FIELD POWER SUPPLY  
Disconnect gas piping from unit when leak  
testing at pressure greater than 1/2 psig. Pres-  
1
sures greater than /2 psig will cause gas  
valve damage resulting in hazardous condi-  
tion. If gas valve is subjected to pressure  
• FACTORY-SUPPLIED NON-FUSED  
1
greater than /2 psig, it must be replaced  
DISCONNECT  
before use. When pressure testing field-  
supplied gas piping at pressures of 1/2 psig or  
less, a unit connected to such piping must be  
isolated by manually closing the gas valve.  
• FIELD CONTROL WIRING  
• HEAT ANTICIPATOR SETTINGS  
Step 9 — Assemble and Mount  
Supply-Air Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
Step 10 — Mount the Barometric Relief Damper . . 28  
Step 11 — Set the Outdoor Cooling and  
Heating Thermostats. . . . . . . . . . . . . . . . . . . . . . . . . . 29  
LIGHT COMMERCIAL THERMIDISTAT  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit and install a lock-  
out tag. Electrical shock could cause personal injury.  
ACCESSORY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30-34  
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Dehumidification Equipment and Connections . . . 30  
Step 1 — Select Light Commercial  
GENERAL  
Thermidistat Location . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Step 2 — Set DIP Switches. . . . . . . . . . . . . . . . . . . . . . . 30  
Step 3 — Install Light Commercial Thermidistat . . 31  
Step 4 — Set Light Commercial Thermidistat  
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Step 5 — Conduct Light Commercial  
Carrier’s factory-installed optional COBRA Energy Recov-  
ery units precondition ventilation air for the rooftop unit during  
winter and summer operation and recover energy from the  
building exhaust air. These units are designed to satisfy the  
higher ventilation requirements and other building codes while  
minimizing energy costs.  
Factory installation of the energy recovery section provides  
the benefit of reduced field-installation time, single point pow-  
er connections, and the assurance of a factory test for the com-  
plete COBRA Energy Recovery unit. The energy recovery sec-  
tion requires less maintenance than other energy recovery  
systems and can be serviced by any qualified refrigeration  
technician.  
Thermidistat Start-Up and Checkout . . . . . . . . . . . 33  
Step 6 — Make Final Settings . . . . . . . . . . . . . . . . . . . . 34  
OPERATIONAL INFORMATION . . . . . . . . . . . . . . . . . . 34  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35-37  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 38-41  
NOTE: Because of the location of the energy recovery section,  
the unit nameplate has been moved to the opposite end of the  
rooftop section, on the upper, right-hand part of the panel.  
ROOFTOP UNIT AND ENERGY$RECYCLER2  
START-UP CHECKLIST. . . . . . . . . . . . . . . . CL-1, CL-2  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-80122 Printed in U.S.A. Form 48/50HJ,62AQ-2SIS Pg 1 9-02 Replaces: 48/50HJ,62AQ-1SIS  
Book 1  
1
4
4
Tab 1a 1b 6a 6b  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Deck pans  
2" Return support.  
Only used on some  
applications.  
49 15/16"  
78 1/4"  
3 1/4  
DUCT OPENING SIZES  
R1  
Supply = 15 11/16" x 31 3/8"  
R1 = 15 5/16" x 29 1/16"  
R2 = 15 5/16" x 9"  
Deck pans  
R2  
14"  
Supply  
14"  
2"  
R1 = Return from building to HVAC  
R2 = Return from building to 62AQ  
110 11/16"  
49 15/16"  
SIDE VIEW  
END VIEW  
Fig. 2B COBRAEnergy Recovery Unit Full-Perimeter Roof Curb 48/50HJ008-014 with 62AQ200,300  
If electric control power or gas service is to be routed  
through the basepan, a field-installed accessory thru-the-  
bottom connection must be used. Attach the accessory to the  
basepan per the information in the accessory installation  
instructions. Thru-the-bottom connections must be installed  
before unit is set on roof.  
If the combined unit roof curb is not being used, additional  
support may be desired under the energy recovery section of  
the unit. An accessory support and pad for the energy recovery  
section can be used. See Fig. 4. Place the protective rubber pad  
on the roof so that the edge near the unit is located about 6-in.  
from the end of the energy recovery section. Measure the  
distance from the bottom of energy recovery rails to the pad.  
Adjust the energy recovery equipment support to match the  
measured distance and screw into place with the 4 screws pro-  
vided. See Fig. 4. Place the support underneath the energy re-  
covery unit and on the protective rubber pad. This is done by  
lifting the end of the energy recovery section slightly above  
level and then sliding the support underneath the rails.  
Curb should be level. This is necessary for unit condensate  
drain to function properly. Refer to Accessory Roof Curb  
Installation Instructions for additional information as required.  
Step 3 Field Fabricate Ductwork Secure all  
ducts to roof curb and building structure. Do not connect duct-  
work to unit. Insulate and weatherproof all external ductwork,  
joints, and roof openings with counter flashing and mastic in  
accordance with applicable codes. See Fig. 5A and 5B for duct  
dimensions.  
Ducts passing through an unconditioned space must be  
insulated and covered with a vapor barrier. If a plenum return is  
used, the return should be ducted through the roof deck to com-  
ply with applicable fire codes.  
A minimum clearance is not required around ductwork.  
These units are designed for a minimum continuous heating  
return-air temperature of 50 F (dry bulb), or an intermittent  
operation down to 45 F (dry bulb), such as when used with a  
night set-back thermostat. To operate at lower return-air  
temperatures, a field-supplied outdoor-air temperature control  
must be used to initiate both stages of heat when the tempera-  
ture is below 45 F. Indoor comfort may be compromised when  
these lower air temperatures are used with insufficient heating  
temperature rise.  
IMPORTANT: The gasketing of the unit to the roof curb is  
critical for a watertight seal. Install gasket supplied with the  
roof curb as shown in Fig. 3A and 3B. Improperly applied  
gasket can result in air leaks and poor unit performance.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOF CURB  
ACCESSORY  
CONNECTOR  
PKG. ACCY.  
CRBTMPWR001A00  
CRBTMPWR002A00  
D ALT  
A
UNIT SIZE  
B
C
GAS  
POWER  
CONTROL  
DRAIN HOLE  
3/4[19] NPT  
11/4[31.7]  
3/4[19] NPT  
3/4″  
1/2″  
1-2″  
CRRFCURB001A00  
CRRFCURB002A00  
[356]  
48/50HJ  
004-007  
[19] NPT  
[12.7]  
1-911  
/
1-4″  
13/4″  
2-0″  
1/2″  
[5511]6 [406]  
[44.5]  
CRBTMPWR003A00  
CRBTMPWR004A00  
[610]  
1/2″  
[12.7] NPT  
3/4″  
[12.7]  
11/4[31.7]  
NOTES:  
[19] NPT  
1. Roof curb accessory is shipped disassembled.  
2. Insulated panels.  
3. Dimensions in [ ] are in millimeters.  
4. Roof curb: galvanized steel.  
5. Attach ductwork to curb (flanges of duct rest on curb).  
6. Service clearance: 4 ft on each side.  
7.  
Direction of airflow.  
8. Connector packages CRBTMPWR001A00 and  
002A00 are for thru-the-curb type gas. Packages  
CRBTMPWR003A00 and 004A00 are for thru-the-  
bottom type gas connections.  
TO ENSURE AIRTIGHT CONNECTION.  
PLACE UNIT AS CLOSE TO THIS  
END AS POSSIBLE  
TO ENSURE AIRTIGHT CONNECTION.  
PLACE UNIT AS CLOSE TO THIS  
END AS POSSIBLE  
Fig. 3A Roof Curb Details (48/50HJ004-007 Section Only)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
D ALT  
DRAIN  
HOLE  
ROOF CURB  
ACCESSORY  
UNIT SIZE  
48/50HJ  
CONNECTOR  
PKG. ACCY.  
A”  
B
C
GAS  
POWER  
CONTROL  
CRRFCURB003A00 1-2[356]  
CRRFCURB004A00 2-0[610]  
CRBTMPWR001A00  
CRBTMPWR002A00  
3/4[19] NPT  
11/4[31.7]  
3/4″  
1/2″  
008-014  
[19] NPT  
[12.7] NPT  
2-87/16  
1-1015  
/
13/4″  
1/2″  
[827]  
[583]16  
[44.5]  
CRBTMPWR003A00  
CRBTMPWR004A00  
3/4[19] NPT  
NOTES:  
1/2″  
[12.7] NPT  
1. Roof curb accessory is shipped disassembled.  
2. Insulated panels: 1-in. thick polyurethane foam,  
13/4 lb density.  
3/4″  
[12.7] NPT  
11/4[31.7]  
[19] NPT  
3. Dimensions in [ ] are in millimeters.  
4. Roof curb: 16-gage steel.  
5. Attach ductwork to curb (flanges of duct rest on  
curb).  
6. Service clearance 4 ft on each side.  
7.  
Direction of airflow.  
8. Connector packages CRBTMPWR001A00 and  
2A00 are for thru-the-curb gas type. Packages  
CRBTMPWR003A00 and 4A00 are for thru-  
the-bottom type gas connections.  
TO ENSURE AN AIRTIGHT CONNECTION,  
PLACE UNIT ON CURB AS CLOSE TO  
DUCT END AS POSSIBLE.  
TO ENSURE AN AIRTIGHT CONNECTION,  
PLACE UNIT ON CURB AS CLOSE TO  
DUCT END AS POSSIBLE.  
Fig. 3B Roof Curb Details (48/50HJ008-014 Section Only)  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIMENSIONS (in.)  
EQUIPMENT SUPPORT  
PART NUMBER  
UNIT SIZE  
3-6 Ton  
A
B
C
4”  
CRAQSUPT001A00  
CRAQSUPT002A00  
CRAQSUPT003A00  
CRAQSUPT004A00  
36.9 40 8 to 14  
36.9 40 14 to 24  
49.7 54 8 to 14  
49.7 54 14 to 24  
A
71/2-121/2 Ton  
HVAC UNIT  
ENERGY  
RECOVERY  
SECTION  
C”  
SCREW  
SUPPORT  
IN PLACE  
PAD  
ADJUSTABLE  
EQUIPMENT  
SUPPORT  
CURB  
ROOF  
10x B (SEE CHART)  
PROTECTIVE  
RUBBER PAD  
(EPDM)  
Fig. 4 Supplemental Energy Recovery Section Equipment Support  
Unit may be installed directly on wood flooring or on  
Class A, B, or C roof-covering material when roof curb is used.  
Although unit is weatherproof, guard against water from  
higher level runoff and overhangs.  
Flue vent discharge must have a minimum horizontal clear-  
ance of 4 ft from electric and gas meters, gas regulators, and  
gas relief equipment.  
Minimum distance between unit and other electrically live  
parts is 48 inches.  
Step 4 Rig and Place Unit Keep unit upright  
and do not drop. Spreader bars are not required if top crating is  
left on unit. Rollers may be used to move unit across a roof.  
Remove the bottom wooden skids that are under the unit by  
removing the wooden plates that hold the bottom wooden  
frame to the unit. Level by using unit frame as a reference. Lift-  
ing holes are provided in base rails as shown in Fig. 6A and 6B.  
Refer to rigging instructions on unit.  
Flue gas can deteriorate building materials. Orient unit  
such that flue gas will not affect building materials. Locate  
mechanical draft system flue assembly at least 48 in. from an  
adjacent building or combustible material.  
Adequate combustion- and ventilation-air space must be  
provided for proper operation of this equipment. Be sure that  
installation complies with all local codes and Section 5.3, Air  
for Combustion and Ventilation, NFGC (National Fuel Gas  
Code), and ANSI (American National Standards Institute)  
Z223.1, and NFPA (National Fire Protection Association)  
54 TIA-54-84-1. In Canada, installation must be in accordance  
with the CAN1-B149 installation codes for gas burning  
appliances.  
All panels must be in place when rigging.  
POSITIONING — Maintain clearance around and above unit  
to provide minimum distance from combustible materials,  
proper airflow, and service access. A properly positioned unit  
will have the following clearances between unit and roof curb:  
1/4-in. clearance between roof curb and base rails on each side  
1
and duct end of unit; /4-in. clearance between roof curb and  
condenser coil end of unit.  
Do not install unit in an indoor location. Do not locate unit  
air inlets near exhaust vents or other sources of contaminated  
air.  
Be sure that unit is installed such that snow will not block  
the combustion intake or flue outlet.  
After unit is in position, remove rigging skids and shipping  
materials.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAX WEIGHT  
A
B
C
lb  
890  
905  
900  
915  
920  
935  
995  
1010  
795  
810  
805  
820  
825  
840  
880  
895  
kg  
in.  
mm  
in  
mm  
in.  
mm  
847  
847  
847  
847  
847  
847  
1070  
1070  
847  
847  
847  
847  
847  
847  
1070  
1070  
48HJ004 w/62AQ060  
48HJ004 w/62AQ100  
48HJ005 w/62AQ060  
48HJ005 w/62AQ100  
48HJ006 w/62AQ060  
48HJ006 w/62AQ100  
48HJ007 w/62AQ060  
48HJ007 w/62AQ100  
50HJ004 w/62AQ060  
50HJ004 w/62AQ100  
50HJ005 w/62AQ060  
50HJ005 w/62AQ100  
50HJ006 w/62AQ060  
50HJ006 w/62AQ100  
50HJ007 w/62AQ060  
50HJ007 w/62AQ100  
404  
411  
409  
415  
418  
425  
452  
459  
361  
368  
365  
372  
375  
381  
400  
407  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
95.6  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
2428.20  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
57.38  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
1457.30  
33.35  
33.35  
33.35  
33.35  
33.35  
33.35  
42.12  
42.12  
33.35  
33.35  
33.35  
33.35  
33.35  
33.35  
42.12  
42.12  
Fig. 6A Rigging Label COBRAEnergy Recovery Unit Sizes 48/50HJ004-007  
trap, pitch the line away from the unit at 1-in. per 10-ft of run.  
Do not use a pipe smaller than the connection (3/4-in.).  
Step 5 Install Flue Hood (48HJ Rooftop Sec-  
tions Only) Refer to the 48HJ installation instructions for  
information on installing the flue hood.  
Step 8 Make Electrical Connections  
Step 6 Install Gas Piping (48HJ Rooftop Sec-  
tions Only) Refer to the 48HJ installation instructions for  
information on installing the gas piping.  
Unit cabinet must have an uninterrupted, unbroken electri-  
cal ground to minimize the possibility of personal injury if  
an electrical fault should occur. This ground may consist of  
electrical wire connected to unit ground lug in control com-  
partment, or conduit approved for electrical ground when  
installed in accordance with NEC (National Electrical  
Code), ANSI/NFPA, latest edition, and local electrical  
codes. Do not use gas piping as an electrical ground. Fail-  
ure to follow this warning could result in the installer being  
liable for personal injury of others.  
Step 7 Install External Trap For Condensate  
Drain The condensate from the rooftop unit along with  
condensate from the upper coil of the energy recovery section  
is internally piped to the condensate pan in the lower section of  
the energy recovery section. For this reason, the bottom drain  
on the rooftop unit CANNOT be used for a condensate drain.  
The 3/4-in. drain connection on the energy recovery section is  
located near the bottom left of the exhaust air section. See  
Fig. 5A and 5B. The energy recovery section must have a  
field-fabricated, external, P-trap installed for condensate drain-  
age. Trap must be at least 4-in. deep to protect against freeze-  
up. If the drain line is installed downstream from the external  
FIELD POWER SUPPLY — All units except 208/230-v  
units are factory wired for the voltage shown on the nameplate.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAX WEIGHT  
A
B
C
lb  
kg  
in.  
mm  
in.  
mm  
in.  
mm  
48HJ008 w/62AQ200  
48HJ008 w/62AQ300  
48HJ009 w/62AQ200  
48HJ009 w/62AQ300  
48HJ012 w/62AQ200  
48HJ012 w/62AQ300  
48HJ014 w/62AQ200  
48HJ014 w/62AQ300  
50HJ008 w/62AQ200  
50HJ008 w/62AQ300  
50HJ009 w/62AQ200  
50HJ009 w/62AQ300  
50HJ012 w/62AQ200  
50HJ012 w/62AQ300  
50HJ014 w/62AQ200  
50HJ014 w/62AQ300  
1310  
1355  
1315  
1360  
1400  
1445  
1440  
1485  
1240  
1285  
1245  
1290  
1325  
1370  
1345  
1410  
595  
616  
597  
618  
636  
657  
655  
675  
564  
584  
566  
586  
602  
623  
620  
641  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
77.42  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
1966.5  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
66.50  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
1689.10  
42.12  
42.12  
42.12  
42.12  
50.12  
50.12  
50.12  
50.12  
42.12  
42.12  
42.12  
42.12  
42.12  
42.12  
42.12  
42.12  
1070  
1070  
1070  
1070  
1273  
1273  
1273  
1273  
1070  
1070  
1070  
1070  
1070  
1070  
1070  
1070  
Fig. 6B Rigging Label COBRAEnergy Recovery Unit Sizes 48/50HJ008-014  
If the 208/230-v unit is to be connected to a 208-v power sup-  
ply, the transformer must be rewired by moving the black wire  
with the 1/4-in. female space connector from the 230-volt con-  
nection and moving to the 200-volt 1/4-in. male terminal on the  
primary side of the transformer.  
Refer to unit label diagram for additional information. Pig-  
tails are provided for field wire connections. Use factory-  
supplied splices or UL (Underwriters’ Laboratories) approved  
copper/aluminum connector.  
When installing units, provide a disconnect per the NEC.  
All field wiring must comply with NEC and local  
requirements.  
Install field wiring as follows:  
1. Install conduit through side panel openings. Install con-  
duit between disconnect and control box.  
may cause damage to electrical components. Such operation  
would invalidate any applicable Carrier warranty.  
FACTORY-SUPPLIED NON-FUSED DISCONNECT — The  
factory-supplied disconnect is capable of handling disconnect  
amps up to 80 A for a COBRA Energy Recovery unit. For dis-  
connect amps greater than 80 A, a field-supplied disconnect is  
required.  
FIELD CONTROL WIRING — Install a Carrier-approved  
accessory thermidistat assembly according to installation  
instructions included with the accessory. Locate thermidistat as-  
sembly on a solid wall in the conditioned space to sense average  
temperature in accordance with thermidistat installation instruc-  
tions on page 30. Connect thermidistat wires to terminal board.  
Route thermidistat cable or equivalent single leads of col-  
ored wire from subbase terminals through connector on unit to  
low-voltage connections (shown in Fig. 8). Thermidistat con-  
trol wiring is routed to both the rooftop unit control box and the  
energy recovery section control box.  
2. Install power lines to terminal connections as shown in  
Fig. 7.  
Voltage to compressor terminals during operation must be  
within voltage range indicated on unit nameplate (see  
Tables 1A-1H). On 3-phase units, voltages between phases must  
be balanced within 2% and the current within 10%. Use the for-  
mula shown in the legend for Tables 1A-1H, Note 2 to deter-  
mine the percent of voltage imbalance. Operation on improper  
line voltage or excessive phase imbalance constitutes abuse and  
If a PremierLink™ control is used, a thermidistat does not  
need to be used. A humidistat and a separate room air sensor  
are used. Two extra terminal blocks (TB2 and TB3) are provid-  
ed in the control box for all units with PremierLink controls.  
No wiring should be directly connected to the PremierLink  
control. Wire sensors to TB2 or TB3. Humidistat is wired to  
TB1 and energy recovery section control box.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: For wire runs up 50 ft, use no. 18 AWG (American Wire  
Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no.  
16 AWG insulated wire (35 C minimum). For over 75 ft, use no.  
14 AWG insulated wire (35 C minimum). All wire larger than  
no. 18 AWG cannot be directly connected to the thermostat and  
will require a junction box and splice at the thermostat.  
Pass the control wires through the hole provided in the cor-  
ner post; then feed wires through the raceway built into the  
corner post to the 24-v barrier located on the left side of the  
control box. See Fig. 10. The raceway provides the UL  
required clearance between high- and low-voltage wiring.  
NOTE: A humidistat and a temperature sensor can be used in  
place of a thermidistat for PremierLink™ units.  
HEAT ANTICIPATOR SETTINGS — Set heat anticipator  
settings at .14 amp for the first stage and .14 amp for second-  
stage heating, when available.  
Table 1A Electrical Data (COBRAEnergy Recovery 48HJ004-007 Units with 62AQ060)  
POWER SUPPLY  
DISCONNECT SIZE*  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
MCA  
FLA  
LRA  
HACR BKR  
STD  
STD  
NO  
9.2  
9.2  
34.8/34.8  
40.8/40.8  
40/40  
45/45  
35/35  
41/41  
135/135  
140/140  
208/230-1-60  
208/230-3-60  
YES  
STD  
STD  
HIGH STATIC  
HIGH STATIC  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
27.7/27.7  
33.7/33.7  
28.6/28.6  
34.6/34.6  
35/35  
40/35  
35/35  
40/40  
29/29  
34/34  
30/30  
35/35  
124/124  
129/129  
154/154  
158/158  
48HJ004  
YES  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
13.6  
16.3  
14.0  
16.7  
20  
20  
20  
20  
14  
20  
15  
20  
63  
67  
77  
82  
STD  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
STD  
NO  
9.2  
9.2  
44.4/44.4  
50.4/50.4  
60/60  
60/60  
44/44  
50/50  
173/173  
178/178  
208/230-1-60  
208/230-3-60  
YES  
STD  
STD  
HIGH STATIC  
HIGH STATIC  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
31.7/31.7  
37.7/37.7  
32.6/32.6  
38.6/38.6  
40/40  
40/40  
40/40  
45/45  
33/33  
38/38  
34/34  
39/39  
140/140  
145/145  
170/170  
174/174  
48HJ005  
YES  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
15.2  
17.9  
15.6  
18.3  
20  
20  
20  
20  
16  
21  
16  
22  
70  
75  
84  
89  
STD  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
STD  
NO  
9.2  
9.2  
55.5/55.5  
61.5/61.5  
70/70  
70/70  
56/56  
61/61  
250/250  
255/255  
208/230-1-60  
208/230-3-60  
YES  
STD  
STD  
HIGH STATIC  
HIGH STATIC  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
38.1/38.1  
44.1/44.1  
39.8/39.8  
45.8/45.8  
45/45  
50/50  
45/45  
50/50  
39/39  
44/44  
41/41  
46/46  
202/202  
207/207  
221/221  
226/226  
48HJ006  
48HJ007  
YES  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
19.3  
22.0  
20.1  
22.8  
25  
25  
25  
25  
20  
25  
20  
26  
101  
106  
110  
115  
STD  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
STD  
NO  
YES  
9.2  
9.2  
42.0/42.0  
48.0/48.0  
50/50  
60/60  
42/42  
48/48  
234/234  
239/239  
208/230-3-60  
208/230-3-60  
HIGH STATIC  
HIGH STATIC  
NO  
YES  
9.2  
9.2  
43.7/43.7  
49.7/49.7  
50/50  
60/60  
44/44  
50/50  
253/253  
258/258  
STD  
STD  
HIGH STATIC  
HIGH STATIC  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
19.8  
22.5  
20.6  
23.3  
25  
25  
25  
30  
20  
26  
21  
26  
114  
118  
123  
128  
460-3-60  
YES  
LEGEND  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA  
Full Load Amps  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
MCA  
452 + 464 + 455  
3
Average Voltage =  
=
Minimum Circuit Amps  
MOCP Maximum Overcurrent Protection  
NEC  
UL  
National Electrical Code  
UnderwritersLaboratories  
1371  
3
*Used to determine minimum disconnect per NEC.  
= 457  
Single point box CRSINGLE017A00 is part of base unit.  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective  
device for the unit shall be fuse or HACR breaker. UL, Canada units may be  
fuse or circuit breaker.  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is  
greater than 2%. Use the following formula to determine the percent of volt-  
age imbalance.  
% Voltage Imbalance = 100 x  
457  
= 1.53%  
max voltage deviation from average voltage  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, con-  
tact your local electric utility company immediately.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1B Electrical Data (COBRAEnergy Recovery 50HJ004-007 Units with 62AQ060)  
HEAT  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
FLA  
MCA  
MOCP  
FLA  
LRA  
NONE  
001  
/—  
34.8/ 34.8  
35.7/ 38.8  
45.2/ 49.7  
55.1/ 61.2  
63.2/ 70.5  
74.5/ 83.6  
40/40  
40/45  
50/50  
35/ 35  
35/ 37  
43/ 47  
52/ 58  
60/ 67  
70/ 79  
135/135  
135/135  
135/135  
135/135  
135/135  
135/135  
15.9/18.3  
23.5/27.1  
31.4/36.3  
37.9/43.8  
46.9/54.2  
002  
STD  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
003  
60/ 70  
70/ 80  
80/ 90  
004  
004  
005  
004  
002+002  
208/230-1-60  
NONE  
001  
/—  
40.8/ 40.8  
40.8/ 43.0  
50.0/ 53.9  
59.9/ 65.4  
68.0/ 74.7  
79.3/ 87.8  
27.7/ 27.7  
27.7/ 29.1  
32.8/ 35.4  
38.5/ 42.0  
43.2/ 47.4  
57.5/ 64.0  
33.7/ 33.7  
33.7/ 33.7  
37.6/ 39.6  
43.3/ 46.2  
48.0/ 51.6  
62.3/ 68.2  
28.6/ 28.6  
28.6/ 30.0  
33.7/ 36.3  
39.4/ 42.9  
44.1/ 48.3  
58.4/ 64.9  
45/45  
45/50  
60/60  
41/ 41  
41/ 42  
49/ 52  
58/ 63  
65/ 71  
76/ 83  
29/ 29  
29/ 29  
32/ 34  
37/ 40  
41/ 45  
55/ 60  
34/ 34  
34/ 34  
37/ 39  
43/ 45  
47/ 50  
60/ 65  
30/ 30  
30/ 30  
33/ 35  
38/ 41  
42/ 46  
56/ 62  
140/140  
140/140  
140/140  
140/140  
140/140  
140/140  
124/124  
124/124  
124/124  
124/124  
124/124  
124/124  
129/129  
129/129  
129/129  
129/129  
129/129  
129/129  
154/154  
154/154  
154/154  
154/154  
154/154  
154/154  
15.9/18.3  
23.5/27.1  
31.4/36.3  
37.9/43.8  
46.9/54.2  
002  
003  
60/ 70  
70/ 80  
80/ 90  
004  
005  
005  
004  
002+002  
NONE  
001  
/—  
35/35  
35/35  
40/40  
45/45  
45/50  
40/35  
40/40  
45/45  
50/50  
50/60  
35/35  
35/35  
40/40  
45/45  
50/50  
40/40  
40/40  
45/45  
50/50  
60/60  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
STD  
003  
004  
005  
60/ 70  
002  
NONE  
001  
/—  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
STD  
YES  
NO  
003  
004  
005  
70/ 70  
002  
208/230-3-60  
NONE  
001  
/—  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
HIGH STATIC  
HIGH STATIC  
003  
50HJ004  
004  
005  
60/ 70  
002  
NONE  
001  
/—  
34.6/ 34.6  
34.6/ 34.6  
38.5/ 40.5  
44.2/ 47.1  
48.9/ 52.5  
63.2/ 69.1  
35/ 35  
35/ 35  
38/ 40  
44/ 46  
48/ 51  
61/ 66  
158/158  
158/158  
158/158  
158/158  
158/158  
158/158  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
YES  
003  
004  
005  
70/ 70  
003  
NONE  
006  
13.6  
16.7  
20.9  
25.0  
28.7  
16.3  
18.8  
23.0  
27.1  
30.8  
14.0  
17.1  
21.3  
25.4  
29.1  
16.7  
19.2  
23.4  
27.5  
31.2  
20  
20  
25  
25  
30  
20  
25  
25  
30  
35  
20  
20  
25  
30  
30  
20  
25  
25  
30  
35  
14  
14  
15  
24  
27  
20  
20  
20  
29  
32  
15  
15  
15  
24  
28  
20  
20  
20  
29  
32  
63  
63  
63  
63  
63  
67  
68  
68  
68  
68  
77  
77  
77  
77  
77  
82  
82  
82  
82  
82  
7.2  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
007  
10.6  
13.8  
16.8  
7.2  
10.6  
13.8  
16.8  
7.2  
10.6  
13.8  
16.8  
7.2  
10.6  
13.8  
16.8  
008  
009  
NONE  
006  
STD  
007  
008  
009  
460-3-60  
NONE  
006  
HIGH STATIC  
HIGH STATIC  
007  
008  
009  
NONE  
006  
YES  
007  
008  
009  
NONE  
001  
/—  
44.4/ 44.4  
44.4/ 44.4  
55.1/ 61.2  
74.5/ 83.6  
94.4/106.5  
60/60  
60/60  
44/ 44  
44/ 44  
52/ 58  
70/ 79  
88/100  
103/117  
173/173  
173/173  
173/173  
173/173  
173/173  
173/173  
15.9/18.3  
31.4/36.3  
46.9/54.2  
62.8/72.5  
003  
60/ 70  
80/ 90  
100/110  
125/150  
004  
005  
005  
005  
STD  
STD  
NO  
9.2  
9.2  
002+002  
003+003  
004+004  
75.8/87.5 110.6/125.2  
208/230-1-60  
NONE  
001  
/—  
50.4/ 50.4  
50.4/ 50.4  
59.9/ 65.4  
79.3/ 87.8  
99.2/110.7  
60/60  
60/60  
50/ 50  
50/ 50  
58/ 63  
76/ 83  
94/104  
109/122  
178/178  
178/178  
178/178  
178/178  
178/178  
178/178  
15.9/18.3  
31.4/36.3  
46.9/54.2  
62.8/72.5  
003  
60/ 70  
80/ 90  
100/125  
125/150  
004  
005  
005  
005  
YES  
002+002  
003+003  
004+004  
75.8/87.5 115.4/129.4  
NONE  
002  
/—  
31.7/ 31.7  
32.8/ 35.4  
38.5/ 42.0  
57.5/ 64.0  
70.6/ 79.0  
37.7/ 37.7  
37.7/ 39.6  
43.3/ 46.2  
62.3/ 68.2  
75.4/ 83.2  
32.6/ 32.6  
33.7/ 36.3  
39.4/ 42.9  
58.4/ 64.9  
71.5/ 79.9  
40/40  
40/40  
45/45  
33/ 33  
33/ 34  
37/ 40  
55/ 60  
67/ 74  
38/ 38  
38/ 39  
43/ 45  
60/ 65  
72/ 79  
34/ 34  
34/ 35  
38/ 41  
56/ 62  
68/ 75  
140/140  
140/140  
140/140  
140/140  
140/140  
145/145  
145/145  
145/145  
145/145  
145/145  
170/170  
170/170  
170/170  
170/170  
170/170  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
STD  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
003  
60/ 70  
80/ 80  
005  
004+004  
002  
003  
002  
003  
002  
003  
NONE  
002  
/—  
40/40  
45/45  
50/50  
50HJ005  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
003  
005  
70/ 70  
80/ 90  
004+004  
208/230-3-60  
NONE  
002  
/—  
40/40  
40/40  
45/45  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
HIGH STATIC  
003  
005  
60/ 70  
80/ 80  
004+004  
NONE  
002  
/—  
38.6/ 38.6  
38.6/ 40.5  
44.2/ 47.1  
63.2/ 69.1  
76.3/ 84.1  
15.2  
16.7  
25.0  
28.7  
42.3  
45/45  
45/45  
50/50  
39/ 39  
39/ 40  
44/ 46  
61/ 66  
73/ 80  
16  
16  
18  
27  
40  
174/174  
174/174  
174/174  
174/174  
174/174  
70  
71  
71  
71  
71  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
HIGH STATIC  
STD  
YES  
NO  
9.2  
9.2  
003  
70/ 70  
80/ 90  
005  
004+004  
003  
003  
NONE  
006  
7.2  
13.8  
16.8  
27.7  
20  
20  
25  
30  
45  
460-3-60  
008  
009  
008+008  
025  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1B Electrical Data (COBRAEnergy Recovery 50HJ004-007 Units with 62AQ060) (cont)  
HEAT  
FLA  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
MCA  
MOCP  
FLA  
LRA  
NONE  
006  
17.9  
18.8  
27.1  
30.8  
44.4  
15.6  
17.1  
25.4  
29.1  
42.7  
18.3  
19.2  
27.5  
31.2  
44.8  
20  
25  
30  
35  
45  
20  
20  
30  
30  
45  
20  
25  
30  
35  
45  
21  
21  
21  
32  
44  
16  
16  
19  
28  
40  
22  
22  
22  
32  
45  
75  
75  
75  
75  
75  
84  
85  
85  
85  
85  
89  
90  
90  
90  
90  
7.2  
STD  
YES  
NO  
9.2  
9.2  
9.2  
008  
13.8  
16.8  
27.7  
7.2  
13.8  
16.8  
27.7  
7.2  
009  
008+008  
025  
025  
NONE  
006  
50HJ005  
(cont)  
460-3-60  
HIGH STATIC  
HIGH STATIC  
008  
009  
008+008  
025  
NONE  
006  
025  
025  
YES  
008  
13.8  
16.8  
27.7  
009  
008+008  
NONE  
002  
/—  
55.5/ 55.5  
55.5/ 55.5  
59.5/ 65.5  
78.9/ 87.9  
98.7/110.8  
70/70  
56/ 56  
56/ 56  
57/ 62  
75/ 83  
93/104  
108/121  
250/250  
250/250  
250/250  
250/250  
250/250  
250/250  
23.5/27.1  
31.4/36.3  
46.9/54.2  
62.8/72.5  
70/ 70  
70/ 70  
80/ 90  
100/125  
125/150  
004  
004  
005  
005  
005  
003  
STD  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
002+002  
003+003  
004+004  
75.8/87.5 115.0/129.6  
208/230-1-60  
NONE  
002  
/—  
61.5/ 61.5  
61.5/ 61.5  
64.3/ 69.7  
83.7/ 92.1  
70/70  
61/ 61  
61/ 61  
62/ 67  
80/ 88  
98/109  
113/126  
39/ 39  
39/ 39  
42/ 46  
56/ 62  
68/ 75  
81/ 91  
44/ 44  
44/ 44  
48/ 51  
61/ 66  
73/ 80  
86/ 95  
41/ 41  
41/ 41  
44/ 48  
58/ 63  
70/ 77  
83/ 93  
46/ 46  
46/ 46  
50/ 53  
63/ 68  
75/ 82  
88/ 97  
20  
20  
20  
28  
40  
44  
25  
25  
25  
32  
45  
48  
255/255  
255/255  
255/255  
255/255  
255/255  
255/255  
202/202  
202/202  
202/202  
202/202  
202/202  
202/202  
207/207  
207/207  
207/207  
207/207  
207/207  
207/207  
221/221  
221/221  
221/221  
221/221  
221/221  
221/221  
226/226  
226/226  
226/226  
226/226  
226/226  
226/226  
101  
101  
101  
101  
101  
101  
106  
106  
106  
106  
106  
106  
23.5/27.1  
31.4/36.3  
46.9/54.2  
70/ 70  
70/ 70  
90/100  
110/125  
125/150  
004  
005  
005  
005  
005  
003  
002+002  
003+003  
004+004  
62.8/72.5 103.5/115.0  
75.8/87.5 119.8/133.8  
/—  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
NONE  
002  
38.1/ 38.1  
38.1/ 38.1  
44.1/ 48.3  
58.4/ 64.9  
71.5/ 79.9  
85.8/ 96.4  
44.1/ 44.1  
44.1/ 44.1  
48.9/ 52.5  
63.2/ 69.1  
76.3/ 84.1  
90.6/100.6  
39.8/ 39.8  
39.8/ 39.8  
45.9/ 50.1  
60.3/ 66.7  
73.3/ 81.7  
87.6/ 98.3  
45.8/ 45.8  
45.8/ 45.8  
50.7/ 54.3  
65.1/ 70.9  
78.1/ 85.9  
92.4/102.5  
19.3  
19.3  
25.4  
29.1  
42.7  
46.4  
22.0  
22.0  
27.5  
31.2  
44.8  
48.5  
45/45  
45/45  
50/50  
50/50  
50/50  
60/60  
45/45  
45/45  
50/60  
50/50  
50/50  
60/60  
25  
25  
30  
30  
45  
50  
25  
25  
30  
35  
45  
50  
002  
003  
003  
003  
003  
003  
003  
003  
003  
003  
003  
003  
004  
005  
STD  
60/ 70  
80/ 80  
90/100  
004+004  
004+005  
NONE  
002  
/—  
70/ 70  
80/ 90  
100/110  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
STD  
YES  
NO  
004+004  
004+005  
50HJ006  
208/230-3-60  
NONE  
002  
/—  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
HIGH STATIC  
HIGH STATIC  
STD  
70/ 70  
80/ 90  
90/100  
004+004  
004+005  
NONE  
002  
004  
005  
004+004  
004+005  
/—  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
YES  
NO  
70/ 80  
80/ 90  
100/110  
NONE  
006  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
008  
009  
008+008  
008+009  
025  
025  
460-3-60  
NONE  
006  
025  
025  
025  
008  
009  
STD  
YES  
008+008  
008+009  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
FLA  
BC = 464 v  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
AC = 455 v  
LRA  
MCA  
MOCP  
NEC  
UL  
452 + 464 + 455  
3
Average Voltage =  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
1371  
3
=
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
Single point box CRSINGLE017A00 is part of base unit.  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device  
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-  
cuit breaker.  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent of voltage  
imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the maximum allow-  
able 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact  
your local electric utility company immediately.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1B Electrical Data (COBRAEnergy Recovery 50HJ004-007 Units with 62AQ060) (cont)  
HEAT  
FLA  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
MCA  
MOCP  
FLA  
LRA  
NONE  
006  
20.1  
20.1  
26.2  
29.9  
43.5  
47.2  
25  
25  
30  
30  
45  
50  
20  
20  
20  
29  
41  
44  
110  
111  
111  
111  
111  
111  
7.2  
008  
13.8  
16.8  
27.7  
30.7  
HIGH STATIC  
HIGH STATIC  
STD  
NO  
YES  
NO  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
9.2  
009  
008+008  
008+009  
025  
025  
50HJ006  
(cont)  
460-3-60  
NONE  
006  
22.8  
22.8  
28.3  
32.0  
45.6  
49.3  
42.0/ 42.0  
42.0/ 42.0  
44.1/ 48.3  
58.4/ 64.9  
71.5/ 79.9  
85.8/ 96.4  
48.0/ 48.0  
48.0/ 48.0  
48.9/ 52.5  
63.2/ 69.1  
76.3/ 84.1  
90.6/100.6  
43.7/ 43.7  
43.7/ 43.7  
45.9/ 50.1  
60.3/ 66.7  
73.3/ 81.7  
87.6/ 98.3  
49.7/ 49.7  
49.7/ 49.7  
50.7/ 54.3  
65.1/ 70.9  
78.1/ 85.9  
92.4/102.5  
19.8  
19.8  
25.4  
29.1  
42.7  
46.4  
22.5  
22.5  
27.5  
31.2  
44.8  
48.5  
20.6  
20.6  
26.2  
29.9  
43.5  
47.2  
25  
25  
30  
35  
50  
50  
50/50  
50/50  
50/50  
60/60  
60/60  
60/60  
50/50  
50/50  
50/60  
26  
26  
26  
33  
46  
49  
42/42  
42/42  
42/46  
56/62  
68/75  
81/91  
48/48  
48/48  
48/51  
61/66  
73/80  
86/95  
44/44  
44/44  
44/48  
58/63  
70/77  
83/93  
50/50  
50/50  
50/53  
63/68  
75/82  
88/97  
20  
20  
20  
28  
40  
44  
26  
26  
26  
32  
45  
48  
21  
21  
21  
29  
41  
44  
115  
116  
116  
116  
116  
116  
234/234  
234/234  
234/234  
234/234  
234/234  
234/234  
239/239  
239/239  
239/239  
239/239  
239/239  
239/239  
253/253  
253/253  
253/253  
253/253  
253/253  
253/253  
258/258  
258/258  
258/258  
258/258  
258/258  
258/258  
114  
114  
114  
114  
114  
114  
118  
119  
119  
119  
119  
119  
123  
124  
124  
124  
124  
124  
7.2  
008  
13.8  
16.8  
27.7  
30.7  
009  
008+008  
008+009  
025  
025  
025  
002  
003  
003  
003  
003  
003  
003  
003  
003  
NONE  
002  
/—  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
60/ 70  
80/ 80  
90/100  
004+004  
004+005  
NONE  
002  
/—  
70/ 70  
80/ 90  
100/110  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
STD  
YES  
NO  
004+004  
004+005  
208/230-3-60  
NONE  
002  
/—  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
HIGH STATIC  
HIGH STATIC  
STD  
70/ 70  
80/ 90  
90/100  
004+004  
004+005  
NONE  
002  
004  
005  
004+004  
004+005  
/—  
60/60  
60/60  
60/60  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
YES  
NO  
70/ 80  
80/ 90  
100/110  
003  
003  
003  
50HJ007  
NONE  
006  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
25  
25  
30  
30  
45  
50  
25  
25  
30  
35  
45  
50  
25  
25  
30  
30  
45  
50  
30  
30  
30  
35  
50  
50  
008  
009  
008+008  
008+009  
025  
025  
NONE  
006  
025  
025  
025  
008  
009  
STD  
YES  
NO  
008+008  
008+009  
460-3-60  
NONE  
006  
008  
009  
HIGH STATIC  
HIGH STATIC  
008+008  
008+009  
025  
025  
NONE  
006  
23.3  
23.3  
28.3  
32.0  
45.6  
49.3  
025  
025  
025  
26  
26  
26  
33  
46  
49  
128  
128  
128  
128  
128  
128  
008  
009  
YES  
008+008  
008+009  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
MCA  
MOCP  
NEC  
UL  
452 + 464 + 455  
3
Average Voltage =  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
1371  
3
=
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Single point box CRSINGLE017A00 is part of base unit.  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device  
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-  
cuit breaker.  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
2. Unbalanced 3-Phase Supply Voltage  
7
457  
% Voltage Imbalance = 100 x  
Never operate a motor where a phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent of voltage  
imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the maximum allow-  
able 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact  
your local electric utility company immediately.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1C Electrical Data (COBRAEnergy Recovery 48HJ004-007 Units with 62AQ100)  
POWER SUPPLY  
DISCONNECT SIZE*  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
MCA  
FLA  
LRA  
HACR BKR  
STD  
STD  
STD  
STD  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
40.7/40.7  
46.7/46.7  
33.6/33.6  
39.6/39.6  
34.5/34.5  
40.5/40.5  
45/45  
50/50  
40/40  
45/45  
40/40  
45/45  
42/42  
48/48  
36/36  
41/41  
37/37  
42/42  
161/161  
166/166  
150/150  
155/155  
180/180  
184/184  
208/230-1-60  
208/230-3-60  
YES  
NO  
YES  
NO  
HIGH STATIC  
HIGH STATIC  
48HJ004  
YES  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
16.5  
19.2  
16.9  
19.6  
20  
20  
20  
25  
18  
23  
18  
24  
76  
80  
90  
95  
STD  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
STD  
STD  
STD  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
50.3/50.3  
56.3/56.3  
37.6/37.6  
43.6/43.6  
38.5/38.5  
44.5/44.5  
60/60  
70/70  
45/45  
50/50  
45/45  
50/50  
51/51  
57/57  
39/39  
45/45  
40/40  
46/46  
199/199  
204/204  
166/166  
171/171  
196/196  
200/200  
208/230-1-60  
208/230-3-60  
YES  
NO  
YES  
NO  
HIGH STATIC  
HIGH STATIC  
48HJ005  
YES  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
18.2  
20.9  
18.6  
21.3  
20  
25  
25  
25  
19  
25  
19  
25  
83  
88  
STD  
460-3-60  
HIGH STATIC  
HIGH STATIC  
97  
YES  
102  
STD  
STD  
STD  
STD  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
61.4/61.4  
67.4/67.4  
44.0/44.0  
50.0/50.0  
45.7/45.7  
51.7/51.7  
70/70  
80/80  
50/50  
60/60  
60/60  
60/60  
62/62  
68/68  
46/46  
51/51  
48/48  
53/53  
276/276  
281/281  
228/228  
233/233  
247/247  
252/252  
208/230-1-60  
208/230-3-60  
YES  
NO  
YES  
NO  
HIGH STATIC  
HIGH STATIC  
48HJ006  
48HJ007  
YES  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
22.2  
24.9  
23.0  
25.7  
47.9/47.9  
53.9/53.9  
49.6/49.6  
55.6/55.6  
22.8  
25.5  
23.6  
26.3  
25  
30  
30  
30  
60/60  
60/60  
60/60  
60/60  
30  
30  
30  
30  
23  
28  
24  
29  
49/49  
55/55  
51/51  
57/57  
23  
29  
24  
30  
114  
119  
123  
128  
260/260  
265/265  
279/279  
284/284  
127  
131  
136  
141  
STD  
460-3-60  
HIGH STATIC  
HIGH STATIC  
STD  
STD  
HIGH STATIC  
HIGH STATIC  
STD  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
NO  
YES  
NO  
208/230-3-60  
YES  
NO  
YES  
NO  
460-3-60  
LEGEND  
YES  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA Full Load Amps  
HACR Heating, Air Conditioning and Refrigeration  
IFM  
Indoor (Evaporator) Fan Motor  
LRA Locked Rotor Amps  
452 + 464 + 455  
3
Average Voltage =  
=
MCA Minimum Circuit Amps  
MOCP Maximum Overcurrent Protection  
NEC National Electrical Code  
1371  
3
UL  
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Single point box CRSINGLE017A00 is part of base unit.  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combi-  
nation load equipment (refer to NEC Articles 430 and 440), the  
overcurrent protective device for the unit shall be fuse or HACR  
breaker. UL, Canada units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percent of voltage imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1D Electrical Data (COBRAEnergy Recovery 50HJ004-007 Units with 62AQ100)  
HEAT  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
FLA  
MCA  
MOCP  
FLA  
LRA  
NONE  
001  
/—  
40.7/ 40.7  
42.5/ 45.5  
52.0/ 56.5  
61.9/ 67.9  
70.0/ 77.3  
81.3/ 90.3  
45/45  
50/60  
42/ 42  
42/ 44  
50/ 54  
59/ 65  
67/ 73  
77/ 85  
161/161  
161/161  
161/161  
161/161  
161/161  
161/161  
15.9/18.3  
23.5/27.1  
31.4/36.3  
37.9/43.8  
46.9/54.2  
002  
60/ 70  
70/ 70  
80/ 80  
90/100  
004  
004  
004  
005  
STD  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
003  
004  
002+002  
208/230-1-60  
NONE  
001  
/—  
46.7/ 46.7  
47.3/ 49.7  
56.8/ 60.7  
66.7/ 72.1  
74.8/ 81.5  
86.1/ 94.5  
33.6/ 33.6  
34.1/ 35.9  
39.6/ 42.2  
45.3/ 48.8  
50.0/ 54.2  
64.3/ 70.7  
39.6/ 39.6  
39.6/ 40.1  
44.4/ 46.4  
50.1/ 53.0  
54.8/ 58.4  
69.1/ 74.9  
34.5/ 34.5  
35.0/ 36.8  
40.5/ 43.1  
46.2/ 49.7  
50.9/ 55.1  
65.2/ 71.6  
50/50  
60/60  
48/ 48  
48/ 49  
56/ 59  
65/ 70  
72/ 78  
82/ 90  
36/ 36  
36/ 36  
39/ 41  
44/ 47  
48/ 52  
61/ 67  
41/ 41  
41/ 41  
44/ 46  
49/ 52  
54/ 57  
67/ 72  
37/ 37  
37/ 37  
40/ 42  
45/ 48  
49/ 53  
62/ 68  
166/166  
166/166  
166/166  
166/166  
166/166  
166/166  
150/150  
150/150  
150/150  
150/150  
150/150  
150/150  
155/155  
155/155  
155/155  
155/155  
155/155  
155/155  
180/180  
180/180  
180/180  
180/180  
180/180  
180/180  
15.9/18.3  
23.5/27.1  
31.4/36.3  
37.9/43.8  
46.9/54.2  
002  
70/ 70  
70/ 80  
80/ 90  
90/100  
004  
004  
005  
005  
003  
004  
002+002  
NONE  
001  
/—  
40/40  
45/45  
50/50  
60/60  
60/60  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
STD  
003  
004  
005  
70/ 80  
002  
NONE  
001  
/—  
45/45  
50/50  
60/60  
60/60  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
STD  
YES  
NO  
003  
004  
60/ 70  
80/ 80  
002  
002  
005  
208/230-3-60  
NONE  
001  
/—  
40/40  
45/45  
50/50  
60/60  
60/60  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
HIGH STATIC  
HIGH STATIC  
003  
50HJ004  
004  
005  
70/ 80  
002  
NONE  
001  
/—  
40.5/ 40.5  
40.5/ 41.0  
45.3/ 47.3  
51.0/ 53.9  
55.7/ 59.3  
70.0/ 75.8  
45/45  
50/50  
60/60  
60/60  
42/ 42  
42/ 42  
45/ 47  
50/ 53  
55/ 58  
68/ 73  
184/184  
184/184  
184/184  
184/184  
184/184  
184/184  
9.2/10.6  
13.6/15.6  
18.1/20.9  
21.9/25.3  
33.4/38.5  
002  
YES  
003  
004  
70/ 70  
80/ 80  
002  
003  
005  
NONE  
006  
16.5  
20.1  
24.3  
28.4  
32.1  
19.2  
22.2  
26.4  
30.5  
34.2  
16.9  
20.5  
24.7  
28.8  
32.5  
19.6  
22.6  
26.8  
30.9  
34.6  
20.0  
25.0  
30.0  
35.0  
35.0  
20.0  
30.0  
30.0  
35.0  
40.0  
20.0  
25.0  
30.0  
35.0  
35.0  
25.0  
30.0  
30.0  
35.0  
40.0  
18  
18  
18  
27  
31  
23  
23  
23  
32  
35  
18  
18  
18  
28  
31  
24  
24  
24  
32  
36  
76  
76  
77  
80  
83  
80  
81  
81  
82  
85  
90  
90  
91  
94  
97  
95  
95  
95  
96  
99  
7.2  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
007  
10.6  
13.8  
16.8  
7.2  
10.6  
13.8  
16.8  
7.2  
10.6  
13.8  
16.8  
7.2  
10.6  
13.8  
16.8  
008  
009  
025  
025  
025  
025  
025  
025  
025  
025  
NONE  
006  
STD  
007  
008  
009  
460-3-60  
NONE  
006  
HIGH STATIC  
HIGH STATIC  
007  
008  
009  
NONE  
006  
YES  
007  
008  
009  
NONE  
001  
/—  
50.3/ 50.3  
50.3/ 50.3  
61.9/ 67.9  
81.3/ 90.3  
60/60  
60/60  
51/ 51  
51/ 51  
59/ 65  
77/ 85  
95/106  
110/124  
199/199  
199/199  
199/199  
199/199  
199/199  
199/199  
15.9/18.3  
31.4/36.3  
46.9/54.2  
003  
70 70  
90/100  
110/125  
125/150  
004  
005  
005  
005  
STD  
STD  
NO  
15.1  
15.1  
002+002  
003+003  
004+004  
62.8/72.5 101.2/113.3  
75.8/87.5 117.4/132.0  
208/230-1-60  
NONE  
001  
/—  
56.3/ 56.3  
56.3/ 56.3  
66.7/ 72.1  
86.1/ 94.5  
70/70  
57/ 57  
57/ 57  
65/ 70  
82/ 90  
101/111  
116/128  
204/204  
204/204  
204/204  
204/204  
204/204  
204/204  
15.9/18.3  
31.4/36.3  
46.9/54.2  
70/ 70  
70/ 80  
90/100  
110/125  
125/150  
004  
004  
005  
005  
005  
003  
YES  
002+002  
003+003  
004+004  
62.8/72.5 106.0/117.5  
75.8/87.5 122.2/136.2  
NONE  
002  
/—  
37.6/ 37.6  
39.6/ 42.2  
45.3/ 48.8  
64.3/ 70.7  
77.3/ 85.8  
43.6/ 43.6  
44.4/ 46.4  
50.1/ 53.0  
69.1/ 74.9  
82.1/ 90.0  
38.5/ 38.5  
40.5/ 43.1  
46.2/ 49.7  
65.2/ 71.6  
78.2/ 86.7  
45/45  
50/50  
60/60  
39/ 39  
39/ 41  
44/ 47  
61/ 67  
73/ 81  
45/ 45  
45/ 46  
49/ 52  
67/ 72  
79/ 86  
40/ 40  
40/ 42  
45/ 48  
62/ 68  
74/ 82  
166/166  
166/166  
166/166  
166/166  
166/166  
171/171  
171/171  
171/171  
171/171  
171/171  
196/196  
196/196  
196/196  
196/196  
196/196  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
STD  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
003  
70/ 80  
80/ 90  
005  
004+004  
002  
003  
002  
003  
002  
003  
NONE  
002  
/—  
50/50  
60/60  
60/60  
50HJ005  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
003  
005  
80/ 80  
90/ 90  
004+004  
208/230-3-60  
NONE  
002  
/—  
45/45  
50/50  
60/60  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
HIGH STATIC  
003  
005  
70/ 80  
80/ 90  
004+004  
NONE  
002  
/—  
44.5/ 44.5  
45.3/ 47.3  
51.0/ 53.9  
70.0/ 75.8  
83.0/ 90.9  
18.2  
20.1  
28.4  
32.1  
45.6  
50/50  
60/60  
60/60  
46/ 46  
46/ 47  
50/ 53  
68/ 73  
80/ 87  
19  
19  
19  
31  
43  
200/200  
200/200  
200/200  
200/200  
200/200  
83  
84  
84  
84  
94  
13.6/15.6  
18.1/20.9  
33.4/38.5  
43.8/50.5  
HIGH STATIC  
STD  
YES  
NO  
15.1  
15.1  
003  
80/ 80  
90/100  
005  
004+004  
003  
003  
025  
025  
025  
NONE  
006  
7.2  
13.8  
16.8  
27.7  
20  
25  
35  
30  
50  
460-3-60  
008  
009  
008+008  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1D Electrical Data (COBRAEnergy Recovery 50HJ004-007 Units with 62AQ100) (cont)  
HEAT  
FLA  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
MCA  
MOCP  
FLA  
LRA  
NONE  
006  
20.9  
22.2  
30.5  
34.2  
47.7  
18.6  
20.5  
28.8  
32.5  
46.0  
21.3  
22.6  
30.9  
34.6  
48.1  
25  
30  
35  
40  
50  
25  
25  
35  
35  
50  
25  
30  
35  
40  
50  
25  
25  
25  
35  
48  
19  
19  
19  
31  
43  
25  
25  
25  
36  
48  
88  
88  
88  
88  
96  
7.2  
STD  
YES  
NO  
15.1  
15.1  
15.1  
008  
13.8  
16.8  
27.7  
7.2  
13.8  
16.8  
27.7  
7.2  
025  
025  
025  
025  
025  
025  
009  
008+008  
NONE  
006  
97  
98  
50HJ005  
(cont)  
460-3-60  
HIGH STATIC  
HIGH STATIC  
008  
98  
009  
98  
008+008  
108  
NONE  
006  
102  
103  
103  
103  
110  
YES  
008  
13.8  
16.8  
27.7  
025  
025  
025  
009  
008+008  
NONE  
002  
/—  
61.4/ 61.4  
61.4/ 61.4  
65.8/ 71.8  
85.2/ 94.2  
70/70  
62/ 62  
62/ 62  
64/ 69  
81/ 90  
100/111  
115/128  
276/276  
276/276  
276/276  
276/276  
276/276  
276/276  
23.5/27.1  
31.4/36.3  
46.9/54.2  
70/ 70  
70/ 80  
90/100  
110/125  
125/150  
004  
004  
005  
005  
005  
003  
STD  
STD  
NO  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
002+002  
003+003  
004+004  
62.8/72.5 105.1/117.2  
75.8/87.5 121.3/135.9  
208/230-1-60  
NONE  
002  
/—  
67.4/ 67.4  
67.4/ 67.4  
70.6/ 76.0  
90.0/ 98.4  
80/80  
68/ 68  
68/ 68  
69/ 74  
87/ 95  
105/116  
120/133  
46/ 46  
46/ 46  
49/ 53  
62/ 68  
74/ 82  
88/ 97  
51/ 51  
51/ 51  
55/ 58  
68/ 73  
80/ 87  
93/102  
48/ 48  
48/ 48  
51/ 55  
64/ 70  
76/ 84  
90/ 99  
281/281  
281/281  
281/281  
281/281  
281/281  
281/281  
228/228  
228/228  
228/228  
228/228  
228/228  
228/228  
233/233  
233/233  
233/233  
233/233  
233/233  
233/233  
247/247  
247/247  
247/247  
247/247  
247/247  
247/247  
23.5/27.1  
31.4/36.3  
46.9/54.2  
80/ 80  
80/ 80  
90/100  
110/125  
150/150  
004  
005  
005  
005  
005  
003  
002+002  
003+003  
004+004  
62.8/72.5 109.9/121.4  
75.8/87.5 126.1/140.1  
/—  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
NONE  
002  
44.0/ 44.0  
44.0/ 44.0  
50.9/ 55.1  
65.2/ 71.6  
78.2/ 86.7  
92.6/103.2  
50.0/ 50.0  
50.0/ 50.0  
55.7/ 59.3  
70.0/ 75.8  
83.0/ 90.9  
97.4/107.4  
45.7/ 45.7  
45.7/ 45.7  
52.6/ 56.8  
66.9/ 73.3  
79.9/ 88.4  
94.3/104.9  
51.7/ 51.7  
51.7/ 51.7  
57.4/ 61.0  
71.7/ 77.5  
84.7/ 92.6  
99.1/109.1  
50/50  
50/50  
60/60  
70/ 80  
80/ 90  
100/110  
70/ 70  
80/ 80  
90/100  
100/110  
60/ 70  
70/ 80  
80/ 90  
100/110  
70/ 70  
80/ 80  
90/100  
100/110  
002  
003  
003  
002  
003  
003  
003  
002  
002  
003  
003  
002  
003  
003  
003  
004  
005  
STD  
004+004  
004+005  
NONE  
002  
/—  
60/60  
60/60  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
50HJ006  
STD  
YES  
NO  
004+004  
004+005  
208/230-3-60  
NONE  
002  
/—  
60/60  
60/60  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
004  
005  
HIGH STATIC  
HIGH STATIC  
004+004  
004+005  
NONE  
002  
004  
005  
004+004  
004+005  
/—  
60/60  
60/60  
53/ 53  
53/ 53  
57/ 60  
70/ 75  
82/ 89  
95/104  
252/252  
252/252  
252/252  
252/252  
252/252  
252/252  
13.6/15.6  
21.9/25.3  
33.4/38.5  
43.8/50.5  
55.2/63.8  
YES  
NONE  
006  
22.2  
22.2  
28.8  
32.5  
46.0  
49.8  
25  
25  
35  
35  
50  
50  
23  
23  
23  
31  
43  
47  
114  
114  
114  
114  
114  
114  
7.2  
008  
13.8  
16.8  
27.7  
30.7  
025  
025  
025  
025  
460-3-60  
STD  
NO  
15.1  
009  
008+008  
008+009  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
FLA  
BC = 464 v  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
AC = 455 v  
LRA  
MCA  
MOCP  
NEC  
UL  
452 + 464 + 455  
3
Average Voltage =  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
1371  
3
=
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
Single point box CRSINGLE017A00 is part of base unit.  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device  
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-  
cuit breaker.  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent of voltage  
imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the maximum allow-  
able 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact  
your local electric utility company immediately.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1D Electrical Data (COBRAEnergy Recovery 50HJ004-007 Units with 62AQ100) (cont)  
HEAT  
FLA  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
MCA  
MOCP  
FLA  
LRA  
NONE  
006  
24.9  
24.9  
30.9  
34.6  
48.1  
51.9  
30  
30  
35  
40  
50  
60  
28  
28  
28  
36  
48  
52  
119  
119  
119  
119  
119  
119  
7.2  
008  
13.8  
16.8  
27.7  
30.7  
025  
025  
025  
025  
STD  
HIGH STATIC  
HIGH STATIC  
STD  
YES  
NO  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
15.1  
009  
008+008  
008+009  
NONE  
006  
23.0  
23.0  
29.6  
33.3  
46.8  
50.6  
25.7  
25.7  
31.7  
35.4  
48.9  
52.7  
30  
30  
35  
35  
50  
60  
30  
30  
35  
40  
50  
60  
60/60  
60/60  
60/60  
70/ 80  
80/ 90  
100/110  
70/ 70  
80/ 80  
90/100  
100/110  
60/ 70  
70/ 80  
80/ 90  
100/110  
24  
24  
24  
32  
44  
48  
29  
29  
29  
37  
49  
53  
49/ 49  
49/ 49  
49/ 53  
62/ 68  
74/ 82  
88/ 97  
55/ 55  
55/ 55  
55/ 58  
68/ 73  
80/ 87  
93/102  
51/ 51  
51/ 51  
51/ 55  
64/ 70  
76/ 84  
90/ 99  
57/ 57  
57/ 57  
57/ 60  
70/ 75  
82/ 89  
95/104  
23  
23  
23  
31  
43  
47  
29  
29  
29  
36  
48  
52  
123  
124  
124  
124  
124  
124  
128  
129  
129  
129  
129  
129  
260/260  
260/260  
260/260  
260/260  
260/260  
260/260  
265/265  
265/265  
265/265  
265/265  
265/265  
265/265  
279/279  
279/279  
279/279  
279/279  
279/279  
279/279  
284/284  
284/284  
284/284  
284/284  
284/284  
284/284  
127  
127  
127  
127  
127  
127  
131  
132  
132  
132  
132  
132  
7.2  
50HJ006  
(cont)  
008  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
025  
025  
025  
025  
025  
025  
025  
025  
002  
003  
003  
002  
003  
003  
003  
002  
002  
003  
003  
002  
003  
003  
003  
025  
025  
025  
025  
025  
025  
025  
025  
460-3-60  
009  
008+008  
008+009  
NONE  
006  
008  
009  
YES  
NO  
008+008  
008+009  
NONE  
002  
/—  
47.9/ 47.9  
13.6/15.6 47.9/ 47.9  
21.9/25.3 50.9/ 55.1  
33.4/38.5 65.2/ 71.6  
43.8/50.5 78.2/ 86.7  
55.2/63.8 92.6/103.2  
004  
005  
004+004  
004+005  
NONE  
002  
/—  
53.9/ 53.9  
60/60  
60/60  
13.6/15.6 53.9/ 53.9  
21.9/25.3 55.7/ 59.3  
33.4/38.5 70.0/ 75.8  
43.8/50.5 83.0/ 90.9  
55.2/63.8 97.4/107.4  
004  
005  
STD  
YES  
NO  
004+004  
004+005  
208/230-3-60  
NONE  
002  
004  
005  
004+004  
004+005  
/—  
49.6/ 49.6  
60/60  
60/60  
13.6/15.6 49.6/ 49.6  
21.9/25.3 52.6/ 56.8  
33.4/38.5 66.9/ 73.3  
43.8/50.5 79.9/ 88.4  
55.2/63.8 94.3/104.9  
HIGH STATIC  
HIGH STATIC  
STD  
NONE  
002  
/—  
55.6/ 55.6  
60/60  
60/60  
70/ 70  
80/ 80  
90/100  
100/110  
13.6/15.6 55.6/ 55.6  
21.9/25.3 57.4/ 61.0  
33.4/38.5 71.7/ 77.5  
43.8/50.5 84.7/ 92.6  
55.2/63.8 99.1/109.1  
004  
005  
YES  
NO  
004+004  
004+005  
50HJ007  
NONE  
006  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
7.2  
13.8  
16.8  
27.7  
30.7  
22.8  
22.8  
28.8  
32.5  
46.0  
49.8  
25.5  
25.5  
30.9  
34.6  
48.1  
51.9  
23.6  
23.6  
29.6  
33.3  
46.8  
50.6  
26.3  
26.3  
31.7  
35.4  
48.9  
52.7  
30  
30  
35  
35  
50  
50  
30  
30  
35  
40  
50  
60  
30  
30  
35  
35  
50  
60  
30  
30  
35  
40  
50  
60  
008  
009  
008+008  
008+009  
NONE  
006  
008  
009  
STD  
YES  
NO  
008+008  
008+009  
460-3-60  
NONE  
006  
24  
24  
24  
32  
44  
48  
30  
30  
30  
37  
49  
53  
136  
137  
137  
137  
137  
137  
141  
141  
141  
141  
141  
141  
008  
009  
025  
025  
025  
025  
025  
025  
025  
025  
HIGH STATIC  
HIGH STATIC  
008+008  
008+009  
NONE  
006  
008  
009  
YES  
008+008  
008+009  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
MCA  
MOCP  
NEC  
UL  
452 + 464 + 455  
3
Average Voltage =  
Minimum Circuit Amps  
Maximum Overcurrent Protection  
National Electrical Code  
1371  
3
=
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Single point box CRSINGLE017A00 is part of base unit.  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective device  
for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or cir-  
cuit breaker.  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is greater  
than 2%. Use the following formula to determine the percent of voltage  
imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the maximum allow-  
able 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact  
your local electric utility company immediately.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1E Electrical Data (COBRAEnergy Recovery 48HJ008-014 Units with 62AQ200)  
POWER SUPPLY  
FUSE OR  
DISCONNECT SIZE*  
NOMINAL  
V-PH-HZ  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
MCA  
FLA  
LRA  
HACR BKR  
STD  
NO  
YES  
NO  
21.9  
21.9  
21.9  
21.9  
60.1  
66.1  
63.2  
69.2  
70  
70  
70  
80  
66  
71  
69  
75  
366  
371  
391  
395  
STD  
208/230-3-60  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
48HJ008  
STD  
NO  
YES  
NO  
10.2  
10.2  
10.2  
10.2  
29.4  
32.1  
30.8  
33.5  
35  
35  
35  
35  
32  
34  
34  
36  
184  
186  
197  
199  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
NO  
YES  
NO  
21.9  
21.9  
21.9  
21.9  
62.1  
68.1  
65.2  
65.2  
70  
70  
70  
70  
68  
73  
71  
71  
400  
405  
425  
425  
STD  
208/230-3-60  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
48HJ009  
STD  
NO  
YES  
NO  
10.2  
10.2  
10.2  
10.2  
31.7  
34.4  
33.1  
35.8  
35  
40  
35  
40  
34  
37  
36  
38  
206  
208  
219  
221  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
NO  
YES  
NO  
21.9  
21.9  
21.9  
21.9  
74.9  
80.9  
79.3  
85.3  
80  
90  
90  
90  
81  
87  
86  
92  
465  
469  
488  
493  
STD  
208/230-3-60  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
48HJ012  
48HJ014  
STD  
NO  
YES  
NO  
10.2  
10.2  
10.2  
10.2  
21.9  
21.9  
35.1  
37.8  
37.7  
40.4  
82.5  
88.5  
40  
40  
40  
45  
90  
100  
38  
40  
41  
43  
89  
95  
234  
236  
245  
247  
550  
555  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
STD  
STD  
STD  
NO  
YES  
NO  
YES  
208/230-3-60  
460-3-60  
10.2  
10.2  
39.3  
42.0  
45  
45  
43  
45  
270  
272  
LEGEND  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA Full Load Amps  
HACR Heating, Air Conditioning and Refrigeration  
IFM  
Indoor (Evaporator) Fan Motor  
LRA Locked Rotor Amps  
452 + 464 + 455  
3
Average Voltage =  
=
MCA Minimum Circuit Amps  
MOCP Maximum Overcurrent Protection  
NEC National Electrical Code  
1371  
3
UL  
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Single point box CRSINGLE017A00 is part of base unit.  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combi-  
nation load equipment (refer to NEC Articles 430 and 440), the  
overcurrent protective device for the unit shall be fuse or HACR  
breaker. UL, Canada units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percent of voltage imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1F Electrical Data (COBRAEnergy Recovery 50HJ008-014 Units with 62AQ200)  
HEAT  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
FLA  
MCA  
MOCP  
FLA  
LRA  
NONE  
017  
/—  
60.1/ 60.1  
60.1/ 64.0  
74.5/ 80.9  
97.4/107.4  
70/70  
/—  
66/ 66  
66/ 66  
72/ 78  
93/102  
111/122  
135/151  
366/366  
366/366  
366/366  
366/366  
366/366  
366/366  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7  
70/ 80  
80/ 90  
100/110  
125/150  
150/175  
007  
007  
009  
009  
009  
010  
STD  
STD  
NO  
YES  
NO  
21.9  
21.9  
21.9  
21.9  
10.2  
10.2  
10.2  
10.2  
21.9  
21.9  
21.9  
21.9  
10.2  
10.2  
10.2  
10.2  
011  
012  
66.7/ 77.0 116.2/129.0  
88.4/102.0 143.3/160.3  
012+017  
NONE  
017  
/—  
66.1/ 66.1  
66.1/ 68.2  
79.3/ 85.1  
70/70  
/—  
71/ 71  
71/ 71  
78/ 83  
99/107  
116/127  
141/156  
69/ 69  
69/ 69  
76/ 82  
97/106  
114/126  
139/155  
371/371  
371/371  
371/371  
371/371  
371/371  
371/371  
391/391  
391/391  
391/391  
391/391  
391/391  
391/391  
395/395  
395/395  
395/395  
395/395  
395/395  
395/395  
184.0  
184.0  
184.0  
184.0  
184.0  
184.0  
186.0  
186.0  
186.0  
186.0  
186.0  
186.0  
196.0  
197.0  
197.0  
197.0  
197.0  
197.0  
198.0  
199.0  
199.0  
199.0  
199.0  
199.0  
400/400  
400/400  
400/400  
400/400  
400/400  
400/400  
405/405  
405/405  
405/405  
405/405  
405/405  
405/405  
425/425  
425/425  
425/425  
425/425  
425/425  
425/425  
429/429  
429/429  
429/429  
429/429  
429/429  
429/429  
206.0  
206.0  
206.0  
206.0  
206.0  
206.0  
208.0  
208.0  
208.0  
208.0  
208.0  
208.0  
218.0  
219.0  
219.0  
219.0  
219.0  
219.0  
220.0  
221.0  
221.0  
221.0  
221.0  
221.0  
21.7/ 25.0  
33.4/ 38.5  
80/ 80  
90/ 90  
110/125  
125/150  
150/175  
007  
009  
009  
009  
009  
010  
011  
51.7/ 59.7 102.2/111.6  
66.7/ 77.0 121.0/133.2  
88.4/102.0 148.1/164.5  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 100.5/110.5  
66.7/ 77.0 119.3/132.1  
88.4/102.0 146.4/163.4  
/—  
21.7/ 25.0  
33.4/ 38.5  
012  
012+017  
208/230-3-60  
NONE  
017  
63.2/ 63.2  
63.2/ 67.1  
77.6/ 84.0  
70/70  
/—  
80/ 80  
90/ 90  
110/125  
125/150  
150/175  
007  
009  
009  
009  
009  
010  
HIGH STATIC  
HIGH STATIC  
STD  
011  
012  
012+017  
NONE  
017  
69.2/ 69.2  
69.2/ 71.3  
82.4/ 88.2  
80/80  
/—  
75/ 75  
75/ 75  
81/ 86  
80/ 80  
90/100  
110/125  
125/150  
175/175  
007  
009  
009  
009  
009  
010  
YES  
NO  
011  
51.7/ 59.7 105.3/114.7  
66.7/ 77.0 124.1/136.3  
88.4/102.0 151.2/167.6  
102/111  
120/131  
145/160  
32.0  
35.0  
38.0  
54.0  
61.0  
73.0  
34.0  
37.0  
41.0  
57.0  
64.0  
76.0  
34.0  
36.0  
40.0  
56.0  
63.0  
75.0  
36.0  
39.0  
42.0  
58.0  
65.0  
77.0  
68/ 68  
68/ 68  
72/ 78  
93/102  
111/122  
135/151  
73/ 73  
73/ 73  
78/ 83  
99/107  
116/127  
141/156  
71/ 71  
71/ 71  
76/ 82  
97/106  
114/126  
139/155  
012  
012+017  
50HJ008  
NONE  
016  
29.4  
36.1  
40.0  
57.0  
64.8  
77.9  
32.1  
38.2  
42.1  
59.1  
66.9  
80.0  
30.8  
37.5  
41.4  
58.4  
66.2  
79.3  
33.5  
39.6  
43.5  
60.5  
68.3  
81.4  
35.0  
40.0  
45.0  
60.0  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
006  
008  
010  
013  
014  
015  
70.0  
80.0  
014+016  
NONE  
016  
35.0  
45.0  
45.0  
60.0  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
006  
008  
010  
013  
STD  
YES  
NO  
014  
015  
70.0  
80.0  
014+016  
460-3-60  
NONE  
016  
35.0  
40.0  
45.0  
60.0  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
006  
008  
010  
013  
HIGH STATIC  
HIGH STATIC  
STD  
014  
015  
70.0  
80.0  
014+016  
NONE  
016  
35.0  
45.0  
45.0  
70.0  
70.0  
90.0  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
008  
008  
010  
013  
YES  
NO  
014  
015  
014+016  
NONE  
017  
/—  
62.1/ 62.1  
62.1/ 64.0  
74.5/ 80.9  
97.4/107.4  
70/70  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7  
70/ 80  
80/ 90  
100/110  
125/150  
150/175  
012  
012  
015  
015  
015  
010  
011  
012  
66.7/ 77.0 116.2/129.0  
88.4/102.0 143.3/160.3  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 102.2/111.6  
66.7/ 77.0 121.0/133.2  
88.4/102.0 148.1/164.5  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 100.5/110.5  
66.7/ 77.0 119.3/132.1  
88.4/102.0 146.4/163.4  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 105.3/114.7  
66.7/ 77.0 124.1/136.3  
88.4/102.0 151.2/167.6  
012+017  
NONE  
017  
68.1/ 68.1  
68.1/ 68.2  
79.3/ 85.1  
70/70  
80/ 80  
90/ 90  
110/125  
125/150  
150/175  
012  
015  
015  
015  
015  
010  
STD  
YES  
NO  
011  
012  
012+017  
208/230-3-60  
NONE  
017  
65.2/ 65.2  
65.2/ 67.1  
77.6/ 84.0  
70/70  
/—  
80/ 80  
90/ 90  
110/125  
125/150  
150/175  
012  
015  
015  
015  
015  
010  
HIGH STATIC  
HIGH STATIC  
STD  
011  
012  
012+017  
NONE  
017  
71.2/ 71.2  
71.2/ 71.3  
82.4 /88.2  
80/80  
/—  
77/ 77  
77/ 77  
81/ 86  
80/ 80  
90/100  
110/125  
125/150  
175/175  
012  
015  
015  
015  
015  
010  
YES  
NO  
011  
102/111  
120/131  
145/160  
34.0  
35.0  
38.0  
54.0  
61.0  
73.0  
37.0  
37.0  
41.0  
57.0  
64.0  
76.0  
36.0  
36.0  
40.0  
56.0  
63.0  
75.0  
012  
012+017  
50HJ009  
NONE  
016  
31.7  
36.1  
40.0  
57.0  
64.8  
77.9  
34.4  
38.2  
42.1  
59.1  
66.9  
80.0  
33.1  
37.5  
41.4  
58.4  
66.2  
79.3  
35.8  
39.6  
43.5  
60.5  
68.3  
81.4  
35.0  
40.0  
45.0  
60.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
011  
014  
016  
013  
014  
015  
70.0  
80.0  
014+016  
NONE  
016  
40.0  
45.0  
45.0  
60.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
011  
014  
016  
013  
STD  
YES  
NO  
014  
015  
70.0  
80.0  
014+016  
460-3-60  
NONE  
016  
35.0  
40.0  
45.0  
60.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
011  
014  
016  
013  
HIGH STATIC  
HIGH STATIC  
014  
015  
70.0  
80.0  
014+016  
NONE  
016  
40.0  
45.0  
45.0  
70.0  
70.0  
90.0  
38.0  
39.0  
42.0  
58.0  
65.0  
77.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
014  
014  
016  
013  
YES  
014  
015  
014+016  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1F Electrical Data (COBRAEnergy Recovery 50HJ008-014 Units with 62AQ200) (cont)  
HEAT  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
FLA  
MCA  
MOCP  
FLA  
LRA  
NONE  
017  
/—  
74.9/ 74.9  
74.9/ 74.9  
77.6/ 84.0  
119.3/132.1  
146.4/163.4  
166.2/156.2  
80/ 80  
80/ 80  
81/ 81  
81/ 81  
465/465  
465/465  
465/465  
465/465  
465/465  
465/465  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
90/ 90  
81/ 82  
STD  
STD  
NO  
YES  
NO  
21.9  
21.9  
21.9  
21.9  
10.2  
10.2  
10.2  
10.2  
21.9  
21.9  
10.2  
10.2  
012  
012+017  
010+012  
125/150  
150/175  
175/175  
114/126  
139/155  
157/176  
NONE  
017  
/—  
80.9/ 80.9  
80.9/ 80.9  
82.4/ 88.2  
124.1/136.3  
151.2/167.6  
171.0/160.4  
79.3/ 79.3  
79.3/ 79.3  
82.3/ 88.8  
124.0/136.9  
151.1/168.2  
170.9/160.9  
85.3/ 85.3  
85.3/ 85.3  
87.1/ 93.0  
128.8/141.1  
155.9/172.4  
175.7/165.1  
35.1  
37.5  
41.4  
66.2  
79.3  
76.7  
37.8  
39.6  
43.5  
68.3  
81.4  
78.8  
37.7  
40.3  
44.3  
69.1  
82.1  
79.6  
40.4  
42.4  
46.4  
71.2  
84.2  
81.7  
82.5/ 82.5  
82.5/ 82.5  
82.3/ 88.8  
124.0/136.9  
151.1/168.2  
170.9/160.9  
40.0  
40.0  
45.0  
40.0  
45.0  
45.0  
40.0  
45.0  
50.0  
45.0  
50.0  
50.0  
45.0  
45.0  
50.0  
90/ 90  
90/ 90  
87/ 87  
87/ 87  
469/469  
469/469  
469/469  
469/469  
469/469  
469/469  
488/488  
488/488  
488/488  
488/488  
488/488  
488/488  
493/493  
493/493  
493/493  
493/493  
493/493  
493/493  
233.0  
234.0  
234.0  
234.0  
234.0  
234.0  
235.0  
236.0  
236.0  
236.0  
236.0  
236.0  
245.0  
245.0  
245.0  
245.0  
245.0  
245.0  
247.0  
247.0  
247.0  
247.0  
247.0  
247.0  
550/550  
550/550  
550/550  
550/550  
550/550  
550/550  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
90/100  
87/ 87  
012  
012+017  
010+012  
125/150  
175/175  
175/175  
90/ 90  
90/ 90  
90/100  
125/150  
175/175  
175/200  
90/ 90  
90/ 90  
100/100  
150/150  
175/175  
200/200  
70.0  
80.0  
90.0  
70.0  
90.0  
90.0  
70.0  
90.0  
90.0  
80.0  
90.0  
90.0  
120/131  
145/160  
163/181  
86/ 86  
86/ 86  
86/ 87  
119/131  
144/160  
162/181  
92/ 92  
92/ 92  
92/ 92  
125/136  
150/165  
168/186  
38.0  
38.0  
40.0  
63.0  
75.0  
86.0  
40.0  
40.0  
42.0  
65.0  
77.0  
89.0  
41.0  
41.0  
43.0  
66.0  
78.0  
89.0  
43.0  
43.0  
45.0  
68.0  
80.0  
92.0  
89/ 89  
89/ 89  
89/ 89  
119/131  
144/160  
162/181  
95/ 95  
95/ 95  
95/ 95  
125/136  
150/165  
168/186  
43.0  
43.0  
43.0  
66.0  
78.0  
89.0  
45.0  
45.0  
45.0  
68.0  
80.0  
92.0  
208/230-3-60  
NONE  
017  
/—  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
HIGH STATIC  
HIGH STATIC  
STD  
012+017  
010+012  
NONE  
017  
/—  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
YES  
NO  
012+017  
010+012  
50HJ012  
NONE  
016  
16.7  
19.8  
39.7  
50.2  
60.1  
011  
011  
014  
016  
016  
013  
015  
014+016  
013+015  
NONE  
016  
16.7  
19.8  
39.7  
50.2  
60.1  
011  
011  
014  
016  
016  
013  
015  
STD  
YES  
NO  
014+016  
013+015  
460-3-60  
NONE  
016  
16.7  
19.8  
39.7  
50.2  
60.1  
011  
011  
014  
016  
016  
013  
015  
HIGH STATIC  
HIGH STATIC  
STD  
014+016  
013+015  
NONE  
016  
16.7  
19.8  
39.7  
50.2  
60.1  
011  
011  
014  
016  
016  
013  
015  
YES  
NO  
014+016  
013+015  
NONE  
017  
/—  
90/ 90  
90/ 90  
90/100  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
125/150  
175/175  
175/200  
100/100  
100/100  
100/100  
150/150  
175/175  
200/200  
70.0  
90.0  
90.0  
012+017  
010+012  
208/230-3-60  
NONE  
017  
/—  
88.5/ 88.5  
88.5/ 88.5  
87.1/ 93.0  
128.8/141.1  
155.9/172.4  
175.7/165.1  
39.3  
40.3  
44.3  
69.1  
82.1  
79.6  
42.0  
42.4  
46.4  
71.2  
84.2  
81.7  
555/555  
555/555  
555/555  
555/555  
555/555  
555/555  
260.0  
260.0  
260.0  
260.0  
260.0  
260.0  
262.0  
262.0  
262.0  
262.0  
262.0  
262.0  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
STD  
YES  
NO  
012+017  
010+012  
50HJ014  
NONE  
016  
16.7  
19.8  
39.7  
50.2  
60.1  
011  
011  
016  
016  
016  
013  
015  
STD  
014+016  
013+015  
460-3-60  
NONE  
016  
45.0  
50.0  
50.0  
80.0  
90.0  
90.0  
16.7  
19.8  
39.7  
50.2  
60.1  
011  
011  
016  
016  
016  
013  
015  
STD  
YES  
014+016  
013+015  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
FLA  
AB = 452 v  
BC = 464 v  
AC = 455 v  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
MCA  
MOCP  
NEC  
UL  
452 + 464 + 455  
3
Minimum Circuit Amps  
Average Voltage =  
Maximum Overcurrent Protection  
National Electrical Code  
1371  
3
UnderwritersLaboratories  
=
*Used to determine minimum disconnect per NEC.  
= 457  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
Single point box CRSINGLE017A00 is part of base unit.  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equipment  
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall  
be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
(BC) 464 457 = 7 v  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.  
Use the following formula to determine the percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
max voltage deviation from average voltage  
= 1.53%  
= 100 x  
average voltage  
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your  
local electric utility company immediately.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1G Electrical Data (COBRAEnergy Recovery 48HJ008-014 Units with 62AQ300)  
POWER SUPPLY  
FUSE OR  
DISCONNECT SIZE*  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
MCA  
FLA  
LRA  
HACR BKR  
STD  
NO  
YES  
NO  
29.8  
29.8  
29.8  
29.8  
68.0  
74.0  
71.1  
77.1  
80  
80  
80  
80  
75  
80  
78  
84  
420  
425  
445  
449  
STD  
208/230-3-60  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
48HJ008  
STD  
NO  
YES  
NO  
15.8  
15.8  
15.8  
15.8  
35.0  
37.7  
36.4  
39.1  
40  
40  
40  
45  
38  
41  
40  
43  
211  
213  
224  
226  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
NO  
YES  
NO  
29.8  
29.8  
29.8  
29.8  
70.0  
76.0  
73.1  
79.1  
80  
80  
80  
80  
77  
82  
80  
86  
454  
459  
479  
483  
STD  
208/230-3-60  
460-3-60  
HIGH STATIC  
HIGH STATIC  
YES  
48HJ009  
STD  
NO  
YES  
NO  
15.8  
15.8  
15.8  
15.8  
37.3  
40.0  
38.7  
41.4  
40  
45  
45  
45  
41  
43  
42  
45  
233  
235  
246  
248  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
NO  
YES  
NO  
29.8  
29.8  
29.8  
29.8  
82.8  
88.8  
87.2  
93.2  
90  
100  
100  
100  
90  
96  
519  
523  
542  
547  
STD  
208/230-3-60  
460-3-60  
HIGH STATIC  
HIGH STATIC  
95  
YES  
101  
48HJ012  
48HJ014  
STD  
NO  
YES  
NO  
15.8  
15.8  
15.8  
15.8  
29.8  
29.8  
40.7  
43.4  
43.3  
46.0  
90.4  
96.4  
45  
45  
50  
50  
100  
100  
44  
47  
47  
50  
98  
104  
261  
263  
272  
274  
604  
609  
STD  
HIGH STATIC  
HIGH STATIC  
YES  
STD  
STD  
STD  
STD  
NO  
YES  
NO  
YES  
208/230-3-60  
460-3-60  
15.8  
15.8  
44.9  
47.6  
50  
50  
49  
51  
297  
299  
LEGEND  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA Full Load Amps  
HACR Heating, Air Conditioning and Refrigeration  
IFM  
Indoor (Evaporator) Fan Motor  
LRA Locked Rotor Amps  
452 + 464 + 455  
3
Average Voltage =  
=
MCA Minimum Circuit Amps  
MOCP Maximum Overcurrent Protection  
NEC National Electrical Code  
1371  
3
UL  
UnderwritersLaboratories  
*Used to determine minimum disconnect per NEC.  
= 457  
Single point box CRSINGLE017A00 is part of base unit.  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
(BC) 464 457 = 7 v  
1. In compliance with NEC requirements for multimotor and combi-  
nation load equipment (refer to NEC Articles 430 and 440), the  
overcurrent protective device for the unit shall be fuse or HACR  
breaker. UL, Canada units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
Never operate a motor where a phase imbalance in supply volt-  
age is greater than 2%. Use the following formula to determine  
the percent of voltage imbalance.  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
max voltage deviation from average voltage  
= 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1H Electrical Data (COBRAEnergy Recovery 50HJ008-014 Units with 62AQ300)  
HEAT  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
FLA  
MCA  
MOCP  
FLA  
LRA  
NONE  
017  
/—  
68.0/ 68.0  
68.7/ 72.9  
83.3/ 89.7  
80/80  
75/ 75  
75/ 75  
420/420  
420/420  
420/420  
420/420  
420/420  
420/420  
21.7/ 25.0  
33.4/ 38.5  
90/ 90  
100/100  
125/125  
150/150  
175/175  
007  
007  
009  
009  
009  
010  
81/ 87  
STD  
STD  
NO  
YES  
NO  
29.8  
29.8  
29.8  
29.8  
15.8  
15.8  
15.8  
15.8  
29.8  
29.8  
29.8  
011  
51.7/ 59.7 106.2/116.2  
66.7/ 77.0 125.0/137.8  
88.4/102.0 152.1/169.1  
102/112  
120/131  
145/160  
012  
012+017  
NONE  
017  
/—  
74.0/ 74.0  
74.0/ 77.1  
88.1/ 93.9  
80/80  
80/ 80  
80/ 80  
425/425  
425/425  
425/425  
425/425  
425/425  
425/425  
445/445  
445/445  
445/445  
445/445  
445/445  
445/445  
449/449  
449/449  
449/449  
449/449  
449/449  
449/449  
211.0  
211.0  
211.0  
211.0  
211.0  
211.0  
213.0  
213.0  
213.0  
213.0  
213.0  
213.0  
223.0  
224.0  
224.0  
224.0  
224.0  
224.0  
225.0  
226.0  
226.0  
226.0  
226.0  
226.0  
454/454  
454/454  
454/454  
454/454  
454/454  
454/454  
21.7/ 25.0  
33.4/ 38.5  
90/ 90  
100/110  
125/125  
150/150  
175/175  
007  
009  
009  
009  
009  
010  
87/ 92  
011  
51.7/ 59.7 111.0/120.4  
66.7/ 77.0 129.8/142.0  
88.4/102.0 156.9/173.3  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 109.3/119.3  
66.7/ 77.0 128.1/140.9  
88.4/102.0 155.2/172.2  
/—  
21.7/ 25.0  
33.4/ 38.5  
108/116  
125/136  
150/165  
78/ 78  
78/ 78  
85/ 91  
106/115  
123/135  
148/164  
84/ 84  
84/ 84  
90/ 96  
111/120  
129/140  
154/169  
38.0  
41.0  
45.0  
61.0  
68.0  
80.0  
41.0  
44.0  
47.0  
63.0  
70.0  
82.0  
40.0  
43.0  
47.0  
62.0  
69.0  
81.0  
43.0  
45.0  
49.0  
65.0  
72.0  
84.0  
77/ 77  
77/ 77  
81/ 87  
012  
012+017  
208/230-3-60  
NONE  
017  
71.1/ 71.1  
71.8/ 76.0  
86.4/ 92.8  
80/80  
90/ 90  
100/110  
125/125  
150/150  
175/175  
007  
009  
009  
009  
009  
010  
HIGH STATIC  
HIGH STATIC  
STD  
011  
012  
012+017  
NONE  
017  
77.1/ 77.1  
77.1/ 80.2  
91.2/ 97.0  
80/80  
90/100  
110/110  
125/150  
150/150  
175/200  
007  
009  
009  
009  
009  
010  
YES  
NO  
011  
51.7/ 59.7 114.1/123.5  
66.7/ 77.0 132.9/145.1  
88.4/102.0 160.0/176.4  
012  
012+017  
50HJ008  
NONE  
016  
35.0  
44.4  
48.3  
65.3  
73.1  
86.2  
37.7  
46.5  
50.4  
67.4  
75.2  
88.3  
36.4  
45.8  
49.7  
66.7  
74.5  
87.6  
39.1  
47.9  
51.8  
68.8  
76.6  
89.7  
40.0  
60.0  
60.0  
40.0  
60.0  
60.0  
40.0  
60.0  
60.0  
45.0  
60.0  
60.0  
80.0  
90.0  
100.0  
80.0  
90.0  
100.0  
80.0  
90.0  
100.0  
80.0  
90.0  
100.0  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
008  
008  
010  
013  
014  
015  
014+016  
NONE  
016  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
008  
008  
010  
013  
STD  
YES  
NO  
014  
015  
014+016  
460-3-60  
NONE  
016  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
008  
008  
010  
013  
HIGH STATIC  
HIGH STATIC  
STD  
014  
015  
014+016  
NONE  
016  
16.7  
19.8  
33.4  
39.7  
50.2  
006  
006  
008  
008  
010  
013  
YES  
NO  
014  
015  
014+016  
NONE  
017  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 106.2/116.2  
66.7/ 77.0 125.0/137.8  
88.4/102.0 152.1/169.1  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 111.0/120.4  
66.7/ 77.0 129.8/142.0  
88.4/102.0 156.9/173.3  
/—  
21.7/ 25.0  
33.4/ 38.5  
51.7/ 59.7 109.3/119.3  
66.7/ 77.0 128.1/140.9  
88.4/102.0 155.2/172.2  
70.0/ 70.0  
70.0/ 72.9  
83.3/ 89.7  
80/80  
90/ 90  
100/100  
125/125  
150/150  
175/175  
012  
012  
015  
015  
015  
010  
011  
102/112  
120/131  
145/160  
82/ 82  
82/ 82  
87/ 92  
108/116  
125/136  
150/165  
80/ 80  
80/ 80  
85/ 91  
012  
012+017  
NONE  
017  
76.0/ 76.0  
76.0/ 77.1  
88.1/ 93.9  
80/80  
459/459  
459/459  
459/459  
459/459  
459/459  
459/459  
479/479  
479/479  
479/479  
479/479  
479/479  
479/479  
90/ 90  
100/110  
125/125  
150/150  
175/175  
012  
015  
015  
015  
015  
010  
STD  
YES  
NO  
011  
012  
012+017  
208/230-3-60  
NONE  
017  
73.1/ 73.1  
73.1/ 76.0  
86.4/ 92.8  
80/80  
90/ 90  
100/110  
125/125  
150/150  
175/175  
012  
015  
015  
015  
015  
010  
HIGH STATIC  
011  
106/115  
123/135  
148/164  
012  
012+017  
NONE  
017  
/—  
79.1/ 79.1  
79.1/ 80.2  
91.2/ 97.0  
80/80  
86/ 86  
86/ 86  
483/483  
483/483  
483/483  
483/483  
483/483  
483/483  
21.7/ 25.0  
33.4/ 38.5  
90/100  
110/110  
125/150  
150/150  
175/200  
012  
015  
015  
015  
015  
010  
90/ 96  
HIGH STATIC  
STD  
YES  
NO  
29.8  
15.8  
011  
51.7/ 59.7 114.1/123.5  
66.7/ 77.0 132.9/145.1  
88.4/102.0 160.0/176.4  
111/120  
129/140  
154/169  
012  
012+017  
50HJ009  
NONE  
016  
37.3  
44.4  
48.3  
65.3  
73.1  
86.2  
40.0  
60.0  
60.0  
41.0  
41.0  
45.0  
61.0  
68.0  
80.0  
233.0  
233.0  
233.0  
233.0  
233.0  
233.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
014  
014  
016  
013  
014  
80.0  
90.0  
100.0  
015  
014+016  
NONE  
016  
40.0  
46.5  
50.4  
67.4  
75.2  
88.3  
45.0  
60.0  
60.0  
43.0  
44.0  
47.0  
63.0  
70.0  
82.0  
235.0  
235.0  
235.0  
235.0  
235.0  
235.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
014  
014  
016  
013  
STD  
15.8  
15.8  
15.8  
YES  
NO  
014  
80.0  
90.0  
100.0  
015  
014+016  
460-3-60  
NONE  
016  
38.7  
45.8  
49.7  
66.7  
74.5  
87.6  
45.0  
60.0  
60.0  
42.0  
43.0  
47.0  
62.0  
69.0  
81.0  
245.0  
246.0  
246.0  
246.0  
246.0  
246.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
014  
014  
016  
013  
HIGH STATIC  
HIGH STATIC  
014  
80.0  
90.0  
100.0  
015  
014+016  
NONE  
016  
41.4  
47.9  
51.8  
68.8  
76.6  
89.7  
45.0  
60.0  
60.0  
45.0  
45.0  
49.0  
65.0  
72.0  
84.0  
247.0  
248.0  
248.0  
248.0  
248.0  
248.0  
16.7  
19.8  
33.4  
39.7  
50.2  
011  
011  
014  
014  
016  
013  
YES  
014  
80.0  
90.0  
100.0  
015  
014+016  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1H Electrical Data (COBRAEnergy Recovery 50HJ008-014 Units with 62AQ300) (cont)  
HEAT  
POWER SUPPLY  
SINGLE  
POINT BOX  
CRSINGLE  
---A00  
DISCONNECT SIZE*  
HEATER  
CRHEATER  
---A00  
NOMINAL  
V-PH-Hz  
IFM  
TYPE  
CONV  
OUTLET  
62AQ  
FLA  
UNIT  
FUSE OR  
HACR BKR  
FLA  
MCA  
MOCP  
FLA  
LRA  
NONE  
017  
/—  
82.8/ 82.8  
82.8/ 82.8  
86.4/ 92.8  
128.1/140.9  
155.2/172.2  
175.0/165.0  
90/ 90  
90/ 90  
100/110  
150/150  
175/175  
175/200  
90/ 90  
90/ 90  
519/519  
519/519  
519/519  
519/519  
519/519  
519/519  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
90/ 91  
STD  
STD  
NO  
YES  
NO  
29.8  
29.8  
29.8  
29.8  
15.8  
15.8  
15.8  
15.8  
29.8  
29.8  
15.8  
15.8  
012  
012+017  
010+012  
123/135  
148/164  
166/185  
NONE  
017  
/—  
88.8/ 88.8  
88.8/ 88.8  
91.2/ 97.0  
132.9/145.1  
160.0/176.4  
179.8/169.2  
87.2/ 87.2  
87.2/ 87.2  
90.8/ 97.2  
132.5/145.3  
159.6/176.6  
179.4/169.4  
93.2/ 93.2  
93.2/ 93.2  
95.6/101.4  
137.3/149.5  
164.4/180.8  
184.2/173.6  
40.7  
45.8  
49.7  
66.7  
87.6  
85.0  
43.4  
47.9  
51.8  
68.8  
89.7  
87.1  
43.3  
48.4  
52.3  
69.3  
90.2  
87.6  
46.0  
50.5  
54.4  
71.4  
92.3  
89.7  
90.4/ 90.4  
90.4/ 90.4  
90.8/ 97.2  
132.5/145.3  
159.6/176.6  
179.4/169.4  
45.0  
60.0  
60.0  
45.0  
60.0  
60.0  
50.0  
60.0  
60.0  
50.0  
60.0  
60.0  
50.0  
60.0  
60.0  
100/100  
100/100  
110/110  
150/150  
175/200  
200/200  
100/100  
100/100  
100/110  
150/150  
175/200  
200/200  
100/100  
100/100  
110/110  
150/150  
175/200  
200/200  
80.0  
100.0  
110.0  
80.0  
100.0  
110.0  
80.0  
100.0  
110.0  
90.0  
100.0  
110.0  
100/100  
100/100  
100/110  
150/150  
175/200  
200/200  
100/100  
100/100  
110/110  
150/150  
175/200  
200/200  
96/ 96  
96/ 96  
523/523  
523/523  
523/523  
523/523  
523/523  
523/523  
542/542  
542/542  
542/542  
542/542  
542/542  
542/542  
547/547  
547/547  
547/547  
547/547  
547/547  
547/547  
260.0  
261.0  
261.0  
261.0  
261.0  
261.0  
262.0  
263.0  
263.0  
263.0  
263.0  
263.0  
272.0  
272.0  
272.0  
272.0  
272.0  
272.0  
274.0  
274.0  
274.0  
274.0  
274.0  
274.0  
604/604  
604/604  
604/604  
604/604  
604/604  
604/604  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
96/ 96  
012  
012+017  
010+012  
129/140  
154/169  
172/190  
95/ 95  
95/ 95  
95/ 96  
208/230-3-60  
NONE  
017  
/—  
21.7/ 25.0  
33.4/3 8.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
HIGH STATIC  
HIGH STATIC  
STD  
128/140  
153/169  
171/190  
101/101  
101/101  
101/101  
134/145  
159/174  
177/195  
44.0  
44.0  
47.0  
62.0  
81.0  
93.0  
47.0  
47.0  
49.0  
65.0  
84.0  
95.0  
47.0  
47.0  
50.0  
65.0  
84.0  
96.0  
50.0  
50.0  
52.0  
68.0  
87.0  
98.0  
012+017  
010+012  
NONE  
017  
/—  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
YES  
NO  
012+017  
010+012  
50HJ012  
NONE  
016  
16.7  
19.8  
33.4  
50.2  
60.1  
011  
011  
014  
016  
016  
013  
014  
014+016  
013+015  
NONE  
016  
16.7  
19.8  
33.4  
50.2  
60.1  
014  
011  
014  
016  
016  
013  
014  
STD  
YES  
NO  
014+016  
013+015  
460-3-60  
NONE  
016  
16.7  
19.8  
33.4  
50.2  
60.1  
014  
011  
014  
016  
016  
013  
014  
HIGH STATIC  
HIGH STATIC  
STD  
014+016  
013+015  
NONE  
016  
0.0  
014  
011  
014  
016  
016  
16.7  
19.8  
33.4  
50.2  
60.1  
013  
014  
YES  
NO  
014+016  
013+015  
NONE  
017  
/—  
98/ 98  
98/ 98  
98/ 98  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
128/140  
153/169  
171/190  
104/104  
104/104  
104/104  
134/145  
159/174  
177/195  
49.0  
49.0  
50.0  
49.0  
84.0  
96.0  
51.0  
51.0  
52.0  
51.0  
87.0  
98.0  
012+017  
010+012  
NONE  
017  
/—  
96.4/ 96.4  
96.4/ 96.4  
95.6/101.4  
137.3/149.5  
164.4/180.8  
184.2/173.6  
44.9  
48.4  
52.3  
48.4  
90.2  
87.6  
47.6  
50.5  
54.4  
50.5  
92.3  
89.7  
609/609  
609/609  
609/609  
609/609  
609/609  
609/609  
287.0  
287.0  
287.0  
287.0  
287.0  
287.0  
289.0  
289.0  
289.0  
289.0  
289.0  
289.0  
21.7/ 25.0  
33.4/ 38.5  
66.7/ 77.0  
88.4/102.0  
104.2/120.3  
010  
012  
STD  
YES  
NO  
012+017  
010+012  
50HJ014  
208/230-3-60  
NONE  
016  
70.0  
100.0  
110.0  
70.0  
100.0  
110.0  
16.7  
19.8  
16.7  
50.2  
60.1  
014  
011  
014  
016  
016  
013  
016  
STD  
014+016  
013+015  
NONE  
016  
50.0  
60.0  
60.0  
16.7  
19.8  
16.7  
50.2  
60.1  
014  
011  
014  
016  
016  
013  
016  
STD  
YES  
014+016  
013+015  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
FLA  
AB = 452 v  
BC = 464 v  
AC = 455 v  
HACR  
IFM  
Heating, Air Conditioning and Refrigeration  
Indoor (Evaporator) Fan Motor  
Locked Rotor Amps  
LRA  
MCA  
MOCP  
NEC  
UL  
452 + 464 + 455  
3
Minimum Circuit Amps  
Average Voltage =  
Maximum Overcurrent Protection  
National Electrical Code  
1371  
3
UnderwritersLaboratories  
=
*Used to determine minimum disconnect per NEC.  
Single point box CRSINGLE017A00 is part of base unit.  
= 457  
Determine maximum deviation from average voltage.  
(AB) 457 452 = 5 v  
NOTES:  
1. In compliance with NEC requirements for multimotor and combination load equipment  
(refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall  
be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.  
2. Unbalanced 3-Phase Supply Voltage  
(BC) 464 457 = 7 v  
(AC) 457 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.  
Use the following formula to determine the percent of voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
max voltage deviation from average voltage  
= 1.53%  
= 100 x  
average voltage  
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your  
local electric utility company immediately.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
208/230-3-60  
460-3-60  
(SIZE 007 ONLY)  
208/230-1-60  
575-3-60  
(SIZE 007 ONLY)  
208/230-3-60  
575-3-60, 460-3-60  
(SIZES 004-006)  
208/230-3-60 AND 460-3-60  
(SIZES 008-014)  
575-3-60  
(SIZES 008-014)  
LEGEND  
Contactor  
C
COMP Compressor  
IFC  
NEC  
TB  
Indoor-Fan Contactor  
National Electrical Code  
Terminal Block  
Fig. 7 Power Wiring Connections  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR MOISTUREMI$ER UNITS ONLY  
Step 9 Assemble and Mount Supply-Air  
Hood The hood kit supplied with the energy recovery  
section is needed to complete this installation. See Fig. 11. The  
energy recovery section supply air hood installs around its  
motorized damper inlet.  
NOTE: Mount the hood sides to the energy recovery section  
first, and then the hood top for easier installation. The ther-  
mostats are shipped factory-wired and taped behind the  
damper blade of the energy recovery section. Knobs and  
screws are in hood package.  
LIGHT  
COMMERCIAL  
THERMIDISTAT  
ACCESSORY  
1. Assemble and mount supply air hood as shown in Fig. 11.  
2. Discard the tape that holds the thermostats behind the  
damper plates. Mount thermostats to the hood sides of the  
energy recovery section unit into the holes provided, with  
thermostat terminals facing up. See Fig. 11. Mount out-  
side cooling set point thermostat part number  
HH22HA060 (white label) on the left side of the hood.  
See Fig. 11.  
3. Mount the outside heating thermostat part number  
HH22HA065 (red label) on the right side of the hood. See  
Fig. 11.  
62AQ  
CONNECTION  
BOARD  
OPTIONAL  
HUMIDISTAT  
(HL38MG029)  
4. From the outside of the unit’s side panels fasten the  
thermostat(s) with two mounting screws, with the quick  
connect terminals face up. See Fig. 11.  
5. Install thermostat knobs (provided in kit). See Fig. 11.  
6. Set supply air quantity (on units with optional factory-  
installed supply air fan [GA] or field-installed accessory  
supply air fan kit [CRFANKIT001-006A00]). Select the  
fan speed and damper position to obtain desired cfm.  
Relocate damper stops to the desired position on the  
damper support rail and adjust the fan speed by relocating  
the wire on the supply fan motor terminal block. Factory  
set position is 45 degrees for the damper position, and  
medium speed for the motor. Relocate stops to top hole  
for 30 degrees, bottom hole for 60 degrees, and remove  
stops for 90 degrees (see Fig. 11).  
Fig. 8 Light Commercial Thermidistat  
Accessory Low-Voltage Connections  
DDC CONTROL  
CONNECTION  
BOARD  
TB3  
TB1  
24 VAC  
RMTOCC  
CMPSAFE  
FSD  
R
G
R
R
Y1  
Y2  
W1  
W2  
G
Y1  
Y2  
W1  
W2  
G
Y2  
7. Install the aluminum filter screen and end cap with  
screws along the top, as shown in Fig. 11.  
W1  
SFS  
NOT USED  
Step 10 Mount the Barometric Relief  
Damper The hood kit supplied with the energy recovery  
section is needed to complete this installation. The exhaust air  
hood (that includes the barometric relief damper) must be  
assembled and installed on the energy recovery section per the  
instructions below. See Fig. 12.  
C
X
C
X
C
X
C
Fig. 9 Low Voltage Connections  
(Units with PremierLinkControls)  
1. Install the barometric relief damper onto the  
energy recovery section by mounting the hinge with  
2 screws then sliding in the hinge pin. See Fig. 12.  
RACEWAY  
LOW VOLTAGE  
CONNECTIONS  
INTEGRATED GAS UNIT  
CONTROLLER (IGC)  
2. Install damper limiter for 30, 45, or 60 degree angles.  
Limiter pin not required for 90-degree setting (set to the  
desired position based on CFM requirements and fan  
speed). See Fig. 12. Fan speed is adjusted by relocating  
wires on fan terminal blocks.  
3. Loosen compressor bolts and remove shipping blocks  
from under compressor on the 62AQ060 and 62AQ100  
sizes only.  
4. Install exhaust hood.  
5. Install wire guard as shown in Fig. 12.  
Never operate the unit without the wire guard in place.  
HOLE IN END  
PANEL (HIDDEN)  
PREMERLINK LOCATION  
(OPTIONAL)  
Fig. 10 Field Control Wiring Raceway  
(48HJ Shown)  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING — During the unoccupied period, the economizer  
mode of operation is used as the first stage of cooling. When  
the outside air temperature is below the cooling thermostat set  
point, the outside air will be used for first stage cooling.  
HEATING — The heating thermostat should be adjusted  
to the second stage balance point (heat output of the energy re-  
covery section plus the heat output of the first stage on rooftop  
unit equals building load at this temperature). Above this set-  
ting, first stage heating will be the energy recovery section unit  
and second stage will be the first stage of the rooftop unit.  
Below this point first stage heating will be the energy recovery  
section unit plus first stage heating of the rooftop unit. The sec-  
ond stage will be the second stage of the rooftop unit.  
Step 11 Set the Outdoor Cooling and Heat-  
ing Thermostats  
IMPORTANT: The energy recovery section unit is shipped  
with an outdoor thermostat set at 55 F which locks out  
mechanical cooling on the RTU (rooftop unit) and the  
energy recovery section compressor. If this feature is not  
desirable, the rooftop unit’s compressor can be allowed to  
run by relocating both gray wires to the same side of the  
Low Temperature Lockout Thermostat (LTLO) leaving the  
white wire on the opposite pole, locking out only the energy  
recovery section compressor. The LTLO is also accessible  
by removing the filter access panel and the door of the  
damper mounting bracket. Refer to Troubleshooting section.  
HOOD TOP  
DAMPER BLADE STOP  
SHIPPED WITH UNIT  
IN 45° POSITION  
KNOB  
SCREWS (2)  
HOOD  
SIDE  
LTLO  
MOUNTING  
BRACKET  
HEATING POINT  
THERMOSTAT  
(RED LABEL)  
END CAP  
COOLING SET POINT  
THERMOSTAT (WHITE LABEL)  
TEMPERATURE  
COOLING  
LOCKOUT (LTLO)  
HOOD SIDE  
TEMPERATURE SWITCH  
SHIPPED WITH UNIT  
SCREW INSTALLATION (2)  
KNOB  
ALUMINUM FILTER SCREEN  
Fig. 11 Energy Recovery Section Supply-Air Hood Assembly  
HOOD TOP  
HOOD SIDE  
HINGE  
HINGE PIN  
BAROMETRIC  
RELIEF DAMPER  
60° LOCATION  
45° LOCATION  
HOOD SIDE  
WIRE GUARD  
30° LOCATION  
DAMPER LIMITER  
Fig. 12 Energy Recovery Section Barometric Exhaust Air Hood Assembly  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR MOISTUREMI$ER UNITS ONLY  
LIGHT COMMERCIAL  
THERMIDISTAT ACCESSORY  
General A Light Commercial Thermidistat Accessory  
(part number TSTATCCPLH01-B) or PremierLink™ control-  
ler with humidistat is required for each unit for field installation  
to control the energy recovery section. See Fig. 13.  
LIGHT  
COMMERCIAL  
THERMIDISTAT  
ACCESSORY  
The Light Commercial Thermidistat is a 7-day programma-  
ble, wall-mounted, low-voltage control which combines tem-  
perature and humidity control in a single unit. It provides  
separate set points for heating and cooling, and adds dehumidi-  
fication with separate set points for occupied and unoccupied  
periods. Different heating and cooling set points and times  
are programmable for up to 4 periods per day and 7 days per  
week. The dehumidification output provides direct control of  
humidity. During power loss an internal memory stores pro-  
grams and settings for unlimited time, and the clock continues  
to run for at least 8 hours. Batteries are not used.  
Power Note that this control does not require batteries  
and is not “power stealing.” It does require 24 vac (R and C  
terminals) from the RTU’s low-voltage transformer to be con-  
nected to it for proper operation. The control will not operate  
without these 2 connections. See Fig. 14.  
OPTIONAL  
HUMIDISTAT  
(HL38MG029)  
Dehumidification Equipment and Connec-  
tions The dehumidification output terminals on the Light  
Commercial Thermidistat must be connected to the dehumidify  
input terminals on the energy recovery section. Additionally, if  
the RTU is equipped with optional MoistureMi$er™ Dehumid-  
ification accessory, a relay in the energy recovery section  
energizes the MoistureMi$er solenoid to activate the enhanced  
dehumidification mode.  
Fig. 14 Light Commercial Thermidistat  
Accessory Low-Voltage Connections  
Step 1 Select Light Commercial Thermidis-  
tat Location Light Commercial Thermidistat should be  
mounted:  
Step 2 Set DIP Switches There is a 4-section  
DIP switch within the Light Commercial Thermidistat which  
must be properly set by the installer. It is easiest to set these  
4 switches before the Light Commercial Thermidistat is  
mounted to the wall, so complete the following steps first:  
• Approximately 5 ft (1.5 m) from floor.  
• Close to or in a frequently used room, preferably on an  
inside partitioning wall.  
• On a section of wall without pipes or ductwork.  
1. Open hinged Light Commercial Thermidistat cover.  
The Light Commercial Thermidistat should NOT be mounted:  
• Close to a window, on an outside wall, or next to a door  
leading to the outside.  
• Exposed to direct light and heat from a lamp, sun, fire-  
place, or other temperature-radiating object that may  
cause a false reading.  
• Close to or in direct airflow from supply registers and  
return-air registers.  
2. Remove cover completely by gently snapping it apart at  
the hinge.  
3. Switches are located in upper right corner of circuit  
board. To change switch position, use corner of a small  
screwdriver to slide switch to opposite position.  
4. After switches have been set, do not reassemble the  
2 halves. The rear plastic will be first mounted to wall.  
SWITCH 1 — Not used  
SWITCH 2 — Not used  
• In areas with poor air circulation, such as behind a door  
or in an alcove.  
SWITCH 3 — SMART/CONVENTIONAL RECOVERY —  
Selects between conventional or smart recovery from setback.  
Conventional recovery changes to new set point at prepro-  
grammed time. Smart recovery, which is active in both heating  
and cooling, starts selected cycle 90 minutes earlier and  
smoothly adjusts set point so room will arrive at programmed  
temperature at programmed time.  
NOTE: The occupied output is only energized at the prepro-  
grammed time.  
To Set:  
OFF — for smart recovery. This is factory default.  
ON — for conventional recovery.  
SWITCH 4 — INSTALLER TEST OFF/ON — Selects a  
special installer test mode that assists with checkout and  
troubleshooting. See Step 5 — Conduct Light Commercial  
Thermidistat Start-Up and Checkout.  
HEIGHT (in.)  
WIDTH (in.)  
DEPTH (in.)  
41/4  
71/2  
13/8  
To Set:  
Fig. 13 Light Commercial  
Thermidistat Accessory  
OFF — for normal operation. (Factory default setting.)  
ON — for Installer Test mode.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3 Install Light Commercial Thermidistat  
Step 4 Set Light Commercial Thermidistat  
Configuration (Fig. 15 and 16) Configuration op-  
tions, like DIP switch settings, are intended to be selected at  
installation and normally are not modified by the owner. These  
options must be made as part of the installation. A special  
procedure allows entry into the Configuration mode. While in  
configuration mode, up to 10 selections can be made. A  
description of each selection and how to use the Configuration  
mode are as follows:  
Before installing Light Commercial Thermidistat, turn off  
all power to Weathermaster® COBRA units. There may be  
more than one power disconnect. Electrical shock  
can cause personal injury or death. Install lockout tags on  
disconnects.  
CONFIGURATION OPTIONS — SUMMARY  
Option 1 — Anticipator adjustment  
1. Turn off all power to equipment. Tag disconnect.  
2. If an existing thermostat is being replaced:  
a. Remove existing thermostat from wall.  
Option 2 — Clean filter timer adjustment  
Option 3 — English/Metric selection  
Option 4 — Fan (G) ON with W selection  
Option 9 — Holiday heat set point  
b. Disconnect wires from existing thermostat, one at  
a time.  
c. As each wire is disconnected, record wire color  
and terminal marking.  
d. New or additional wire may be needed to accommo-  
date added humidity outputs transformer common.  
Option 10 — Holiday cool set point  
Option 11 — Holiday humidity set point  
Option 13 — Room temperature offset adjustment  
Option 14 — Heat cool deadband adjustment  
Option 21 — Keyboard lock  
e. Discard or recycle old thermostat.  
TO ENTER CONFIGURATION MODE — Press and hold  
FAN button for approximately 10 seconds until COOL set  
point display indicates a flashing “01”. The Light Commercial  
Thermidistat is now in Configuration mode. It will automati-  
cally exit this mode if no button is pressed for 3 minutes. Press-  
ing HOLD End button will exit the Configuration mode  
immediately.  
WHILE IN CONFIGURATION MODE — The upper small  
(COOL set point) display indicates selected option number and  
large display indicates selection made within that option. One of  
these will be flashing. The up and down set point buttons are  
used both to move between available options and to make selec-  
tion for each option. When option number (small display) is  
flashing, the up and down set point buttons allows for scrolling  
through options moving between available option numbers.  
After desired option number has been selected, press SET  
TIME/TEMP button once. The large display will now flash,  
indicating that up and down set point buttons now control avail-  
able choices within that option. Each press of SET TIME/  
TEMP button switches between available option (small display)  
and available selections within each option (large display).  
Mercury is a hazardous waste and MUST be disposed of  
properly.  
3. Route wires through large hole in rear plastic. Level rear  
plastic (separated from front plastic in Step 2 — Set DIP  
Switches, on page 30). Level rear plastic against wall (for  
aesthetic value only — Light Commercial Thermidistat  
need not be leveled for proper operation) and mark wall  
through 2 mounting holes.  
4. Drill two 3/16-in. mounting holes in wall where marked.  
5. Secure rear plastic to wall with 2 screws and anchors  
provided. Additional mounting holes are available for  
more secure mounting if needed. Make sure all wires  
extend through hole in mounting base.  
6. Adjust length and routing of each wire to reach proper  
connector block and terminal on mounting base with  
1
1/4-in. extra length. Strip only /4 in. of insulation from  
Option 1 — Anticipator Adjustment — This adjustment  
controls sensitivity and cycle rate of Light Commercial Ther-  
midistat. Higher numbers decrease sensitivity and slow cycle  
rate. Lower numbers increase sensitivity and cycle rate. Antici-  
pator values can range from 1 to 9. Factory default is 3. This  
default selection provides optimum performance in nearly all  
installations. Try it first; do not change setting unless there is  
evidence of need to do so.  
each wire to prevent adjacent wires from shorting togeth-  
er when connected.  
7. Match and connect equipment wires to proper terminals  
of each connector block. Remember R and C must be  
connected for proper operation (see Fig. 14).  
Unlike conventional anticipators, this setting is not deter-  
mined by current draw. There is no need to measure, know, or  
compensate for current draw. There is also no droop with this  
Light Commercial Thermidistat. Regardless of setting and  
number of stages, both heating and cooling will control to their  
respective set points.  
Improper wiring or installation may damage Light  
Commercial Thermidistat. Check to make sure wiring is  
correct before proceeding with installation or turning on  
power. Refer to wiring schematic in the Troubleshooting  
section of this manual.  
8. Push any excess wire into wall and against rear plastic.  
Seal hole in wall to prevent air leaks. Leaks can affect  
operation.  
9. Reattach Light Commercial Thermidistat body to mount-  
ing base by first reattaching hinge.  
10. Close Light Commercial Thermidistat assembly, making  
sure pins on back of circuit board align with sockets in  
connector.  
TO ADJUST:  
1. Enter Configuration mode. The upper small (COOL set  
point) display will be flashing 01. If not, use up and down  
set point buttons to move it to 01.  
2. Press SET TIME/TEMP button once to flash current  
selection of 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display.  
Factory default is 3.  
3. Use up and down set point buttons to move to desired  
anticipator setting.  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
11. Turn on power to equipment.  
On power up, all display segments will light for 2 seconds.  
For the next 8 seconds, a 2-digit code appears on LED display  
that identifies Light Commercial Thermidistat configuration:  
CP — Commercial Product  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Option 4 — Fan (G) On With W — This selection deter-  
mines whether fan (G) output is to be ON or OFF when any W  
(furnace or strip heat) output is ON. Most furnaces and fan  
coils manage their own blowers and do not require separate G  
signal. For these applications, select OFF. Some auxiliary heat-  
ers require separate G signal to turn on blower. In this case,  
select ON. Factory default is OF (off).  
PROGRAM  
HUMIDITY  
MODE  
FAN  
COPY PREVIOUS  
DAY  
UP  
TO SELECT:  
CHANGE DAY  
1. Enter Configuration mode. Use up and down set point  
buttons to make small display (now flashing) indicate 04.  
2. Press SET TIME/TEMP button once to flash large  
display.  
3. Use up or down set point buttons to alternate between  
OFF and ON on large display.  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
DOWN  
RESET  
FILTER  
SET TIME/TEMP  
HOLD  
End  
HOLIDAY  
Fig. 15 Light Commercial Thermidistat Keypad  
Mode  
Option 9 — Holiday Heat Set Point — This selection deter-  
mines the heating set point (40 to 90 minus deadband F) when  
the HOLIDAY function is active.  
OC1 UN1 OC2 UN2  
Mo Tu We Th  
Fr Sa Su  
HOLD HOLIDAY  
DEHUM  
OFF  
HEAT  
COOL  
TO SELECT:  
COOL  
HEAT  
PM  
TIME  
AM  
AUTO  
1. Enter Configuration mode. Use up and down buttons to  
make small display (now flashing) indicate 09.  
2. Press SET TIME/TEMP button once to flash large display.  
3. Use up or down set point buttons to select desired  
temperature.  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
Fan  
CLEAN FILTER  
ON**  
AUTO  
PROGRAMMING  
Fig. 16 Light Commercial Thermidistat LCD  
Option 10 — Holiday Cool Set Point — This selection deter-  
mines the cooling set point (40 to 90 minus deadband F) when  
the HOLIDAY function is active.  
on Power Up  
TO SELECT:  
Option 2 — Clean Filter Timer — Select hours of blower  
operation (heating, cooling, or fan) before CLEAN FILTER  
icon is displayed. With OFF selected, icon will never come on,  
disabling this feature. Time selection can range from 400 to  
3600 blower operation hours by selecting numbers 1 through 9.  
(Time is 400 times number selected.) Factory default is 2  
(800 hr). Recommended blower operation hours selections are:  
disposable filter — 400 to 800 hr; media filter — 1200 to  
1600 hr; electronic air cleaner — 1600 to 2400 hr.  
TO SELECT OR ADJUST:  
1. Enter Configuration mode. Use up and down set point  
buttons to make small display (now flashing) indicate 02.  
2. Press SET TIME/TEMP button once to display current  
selection of 1, 2, 3, 4, 5, 6, 7, 8, or 9 on large display.  
Factory default is 2.  
3. Use up and down set point buttons to move between  
available choices.  
1. Enter Configuration mode if not already there. Use up  
and down set point buttons to make small display (now  
flashing) indicate 10.  
2. Press SET TIME/TEMP button once to flash large display.  
3. Use up or down set point buttons to select desired  
temperature.  
4. Press SET TIME/TEMP button again to flash small up-  
per display for selection of another option, or press  
HOLD End to exit Configuration mode.  
Option 11 — Holiday Humidity Set Point — This selection  
determines the humidity set point (50 to 90% rh [relative  
humidity]) when the HOLIDAY function is active.  
NOTE: This value can only be changed in the installer soft-  
ware Configuration mode.  
TO SELECT:  
1. Enter Configuration mode. Use up and down set point  
buttons to make small display (now flashing) indicate 11.  
2. Press SET TIME/TEMP button once to flash large display.  
3. Use up or down buttons to select desired humidity.  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
Option 13 — Room Temperature Offset Adjust — This op-  
tion allows calibration (or deliberate miscalibration) of room  
temperature sensor. There are various reasons why building  
owners may want to have displayed temperature adjusted to a  
higher or lower value. The selected number is number of  
degrees, plus or minus, which will be added to actual  
temperature. The numbers can range between –5 and +5.  
Factory default is 0. This adjusted value will be used as actual  
temperature for both display and control action. For example, if  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
Option 3 — English/Metric — Select between Fahrenheit  
and Celsius operation. Factory default is Fahrenheit.  
TO SELECT OR ADJUST:  
1. Enter Configuration mode. Use up and down set point  
buttons to make small display (now flashing) indicate 03.  
2. Press SET TIME/TEMP button once to flash current se-  
lection of F or C. Factory default is F.  
3. Use up and down set point buttons to move between F  
and C on large display.  
4. Press SET TIME/TEMP button again to flash small up-  
per display for selection of another option, or press  
HOLD End to exit Configuration mode.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 is selected, 72 F actual will read 74 F. If set point is 72 F, the  
room will control to an actual temperature of 70 F which will  
be displayed and acted upon as if it were 72 F. The effect is that  
a positive number selection will make the room temperature  
lower and vice versa. The Light Commercial Thermidistat is  
calibrated within an accuracy of plus or minus 1 degree when  
shipped from the factory, so this adjustment will provide the  
best accuracy when set to 0.  
keypad will be unlocked. The keypad will return to lock  
once the keypad is idle for a 2-minute period or immedi-  
ately if after exiting the Configuration mode.  
4. Press SET TIME/TEMP button again to flash upper  
small display for selection of another option, or press  
HOLD End to exit Configuration mode.  
Step 5 Conduct Light Commercial Thermi-  
distat Start-Up and Checkout The Light Com-  
mercial Thermidistat is designed with a built-in installer test  
capability. It allows easy operation of equipment without  
delays or set point adjustments to force heating or cooling. To  
enable Installer Test mode, move DIP switch no. 4 to ON posi-  
tion. To access this switch, open case as described in Step 2 —  
Set DIP Switches. Use the tip of a small screwdriver to slide  
switch no. 4 to ON position.  
TO SELECT:  
1. Enter Configuration mode. Use up and down set point  
buttons to make small display (now flashing) indicate 13.  
2. Press SET TIME/TEMP button once to flash large display.  
3. Use up or down set point buttons to move between –5,  
–4, –3, –2, –1, 0, 1, 2, 3, 4, or 5 on large display. Factory  
default is 0.  
While in Installer Test mode, clock will display “InSt,” FAN  
button will control fan, and MODE button will control heating  
and cooling.  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
TO TEST FAN:  
NOTE: In the Installer Test mode the fan operation is not  
dependent on the occupied signal.  
Option 14 — Heat/Cool Deadband Adjustment — This op-  
tion selects the minimum difference between heating and cool-  
ing set points. A larger difference saves energy and a smaller  
difference decreases temperature difference between heating  
and cooling. Factory default is 2, which means cooling set  
point must be a minimum of 2 degrees above heating set point.  
An attempt to move them closer will result in one “pushing”  
the other to maintain the required difference.  
Depending on set points, moving deadband closer than  
2 degrees may result in regular cycling between heat and cool  
when AUTO mode is selected. However, this cycling cannot  
occur more often than 1 transition every 10 minutes. The sys-  
tem has a built-in requirement that it cannot switch between  
heat and cool without a 10-minute “off” time between the 2  
operations. Specifically, to switch from one mode to the other,  
there must be no demand for the old mode and a demand for  
the new mode, and this must exist continually for 10 minutes  
before transition to the new mode will occur.  
Fan button switches FAN icon between AUTO and ON.  
While ON is displayed, G output will be on, turning fan on.  
Allow up to 10 seconds after button is pressed for fan to turn on  
and off. On all 3 through 12.5 ton RTUs the fan continues to  
operate for a minimum of 30 seconds after G signal is  
removed.  
NOTE: In other than the Installer Test mode the fan will run  
continuously during the occupied periods. If auto fan is  
selected, the fan will come on with a heating or cooling call  
during the unoccupied periods and run continuously during the  
occupied periods. The fan icon AUTO will be lit if auto fan is  
selected and ON will be lit when the fan is on.  
TO TEST COOLING AND DEHUMIDIFICATION:  
Press MODE button until COOL icon turns on. Y1 cooling  
begins within 10 seconds and remains on for 4 minutes. Two  
minutes after Y1 comes on, the Y2 signal is energized for  
2 minutes. At the end of 4-minute run, cooling stops and  
MODE reverts to OFF. At any time during 4-minute run time,  
cooling may be turned off by pressing MODE button until  
OFF appears. While cooling is on, successive presses of  
HUMIDITY button turns the dehumidify output on and off.  
While this output is active, the “DEHUM” icon will be  
energized.  
TO SELECT:  
1. Enter Configuration mode if not already there. Use up  
and down set point buttons to make small display (now  
flashing) indicate 14.  
2. Press SET TIME/TEMP button once to flash large  
display.  
3. Use up or down set point buttons to move between 0, 1, 2,  
3, 4, 5, or 6 on large display. Factory default is 2.  
TO TEST PRIMARY HEATING:  
4. Press SET TIME/TEMP button again to flash small  
upper display for selection of another option, or press  
HOLD End to exit Configuration mode.  
Option 21 — Keyboard Lock — This option allows the  
installer to disable the thermostat from being changed.  
Press MODE button until HEAT icon turns on. W1 heating  
begins within 10 seconds and remains on for 4 minutes. This  
is the Recycling mode and if the outdoor temperature is below  
the balance point it will also include first stage furnace or  
electric heat in AC system, and heat pump heating in heat  
pump system. W1 will be on for 2 minutes followed by second  
stage W2 for 2 minutes. If the outdoor temperature is above the  
balance point, this second stage call will energize first stage  
furnace or electric heat in AC system and heat pump heating  
in heat pump system. If the outdoor temperature is below  
the balance point this second stage call will energize second  
stage furnace or electric heat in AC system and heat pump  
system. At the end of 4-minute run, heating stops, and MODE  
reverts back to OFF. At any time during 4-minute run time,  
heating may be turned off by pressing MODE button until  
OFF appears. While heating is on, successive presses of  
HUMIDITY button turn Occupied output on and off. While  
this output is active, “OC” appears in cool set point display.  
TO SELECT:  
1. Enter Configuration mode. Use up and down set point  
buttons to make small display (now flashing) indicate 21.  
2. Press SET TIME/TEMP button once to flash large  
display.  
3. Use up and down set point buttons to move between OF  
and ON on large display. Factory default is OF, keyboard  
is active.  
NOTE: Once the keyboard is locked the building manag-  
er can momentarily unlock the keyboard by pressing the  
following keys sequentially, MODE, COPY PREVIOUS  
DAY, SET TIME/TEMP, and HOLD End. The sequence  
must be completed within a 5-second period, and the  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 6 Make Final Settings Be sure to return  
DIP switch no. 4 back to OFF position to exit Installer Test  
mode. Assuming the system is to be left in operation after  
installation is complete, use MODE button to select between  
HEAT, COOL, or AUTO to provide desired operation of heat-  
ing, cooling, or both.  
The default set points and programmed schedule are  
(ONLY ONE PERIOD IS PROGRAMMED):  
OCCUPIED 1 = OCCUPIED 2 = 7:00 AM;  
COOL = 76 F; HEAT = 72 F  
DISPLAY WILL READ OC2  
UNOCCUPIED 1 = UNOCCUPIED 2 = 5:00 PM;  
COOL = 85 F; HEAT = 65 F  
DISPLAY WILL READ UN2  
If programmed schedule is to be used, make sure the HOLD  
icon is off. The schedule is energized or deenergized by push-  
ing the HOLD End button.  
If fixed temperatures are desired, push HOLD End button to  
turn on HOLD icon. This will maintain set points, not allowing  
them to change with programmed schedule.  
During unoccupied periods the FAN button may be used to  
select between AUTO (fan on only with equipment) and FAN  
(fan on continuously) fan modes. During occupied periods the  
fan is on continuously.  
DEHUMIDIFICATION — Dehumidification is done only  
during cooling. A dehumidification set point is available to the  
owner in both occupied and unoccupied times. It can range  
from 50 to 90 percent relative humidity. When actual humidity  
is higher than set point, a dehumidification demand exists. In the  
occupied period, the Light Commercial Thermidistat responds  
by activating its dehumidify output (DEHUM) turning on the  
compressor in the Energy$Recycler2 unit; and when a call for  
cooling exists, energizing the MoistureMi$er™ solenoid in the  
48/50HJ unit (if so equipped). The Energy$Recycler2 compres-  
sor will be started in the Occupied mode even though a call for  
cooling does not exist; thus dehumidifying the outside air before  
it enters the building. In the unoccupied period the humidistat  
will only energize the MoistureMi$er solenoid in the main unit.  
OPERATIONAL INFORMATION  
Five-Minute Compressor Time  
Guard®  
Device This timer prevents compressor from starting  
unless it has been off for at least 5 minutes. It can be defeated  
for 1 cycle by simultaneously pressing FAN and UP buttons  
simultaneously.  
Fifteen-Minute Staging Timer In multistage heat-  
ing or cooling, this timer prevents any higher stage from turn-  
ing on until preceding stage has been on for 15 minutes. This  
timer is not in effect if temperature difference is greater than  
5° F (usually due to a large change in desired temperature).  
Three-Minute Minimum On Time In normal op-  
eration, when a stage turns on, it will not turn off for a mini-  
mum of 3 minutes.  
Heat/Cool Set Points (Desired Tempera-  
ture) A minimum difference of 2° F is enforced between  
heating and cooling desired temperatures. This is done by  
allowing one setting to “push” the other to maintain this  
difference. This difference is adjustable via Configuration  
Option 14.  
Equipment On Indicators When cooling equip-  
ment is on, a COOL icon preceded by a small triangle is  
displayed below cooling set point. While cooling equipment is  
delayed by the Time Guard timer, triangle will flash. The same  
is true for HEAT icon and its preceding triangle located under  
heating set point.  
Dehumidify Output On Indicators The DEHUM  
icon is on when the dehumidification output is energized.  
Auto Changeover When auto changeover mode is  
selected, a change from heat to cool (or vice versa) will not oc-  
cur until an opposite mode demand has existed for 10 minutes.  
If set point is changed, the 10-minute requirement is deleted.  
Power On Check When AC power is first applied, all  
segments of display are turned on for a few seconds. Following  
this, temperature display indicates model/configuration via fol-  
lowing 2-digit code: CP for commercial product. See Fig. 16.  
However, if the humidity is below the set point in the  
unoccupied period, a “mini” economizer mode will be initiated  
bringing in outside air to cool the space as the first stage  
of cooling, provided the outdoor air thermostat in the  
Energy$Recycler2 unit is below its set point.  
Error Codes If Light Commercial Thermidistat cannot  
properly read room temperature, display will indicate two  
dashes (--) and all outputs (except fan, if on) will turn off.  
E4 — If Light Commercial Thermidistat’s internal memory  
fails, “E4” will be displayed. Replace Light Commer-  
cial Thermidistat.  
E5 — If Light Commercial Thermidistat cannot properly  
read humidity, “E5” will be displayed. Replace  
Light Commercial Thermidistat.  
HOLIDAY — A holiday selection is available specifically for  
times where the building will not be occupied for an extended  
period. For convenience, one button selects Holiday mode  
which is indicated by “HOLIDAY” icon on LED display. Holi-  
day mode also has an automatic hold, meaning that set points  
are not affected by the programmed schedule. While in Holi-  
day mode, the system provides temperature and humidity pro-  
tection for the building in all seasons, but not comfort.  
Smart Recovery With Smart Recovery selected (DIP  
SW1 is on), transition out of setback begins a fixed time period  
before selected recovery time and gradually adjusts room tem-  
perature so desired temperature will be achieved at selected  
recovery time. The fixed time period is 1.5 hours. It operates in  
both heating and cooling.  
Holiday Set Points — The settings for HEAT, COOL, and  
DEHUM should have been done in the Configuration mode  
(Options 9,10, and 11).  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Tighten compressor holddown bolts to 5.5 to 6.5 ft-lbs of  
torque.  
PRE-START-UP  
5. Verify the following:  
a. If installed, ensure optional supply and exhaust  
blower wheel set screws are tight and wheels are  
centered within the blower housing.  
b. Make sure supply and exhaust air filters are in  
place.  
c. Make sure the condensate drain is of correct  
dimensions and primed with water to ensure  
proper drainage.  
Failure to observe the following warnings could result in  
serious personal injury.  
1. Follow recognized safety practices and wear protec-  
tive goggles and gloves when checking or servicing  
refrigerant system.  
2. Do not operate compressor or provide any electric  
power to unit unless compressor terminal cover is in  
place and secured.  
3. Do not remove compressor terminal cover until  
all electrical sources are disconnected and tagged  
accordingly.  
d. Reinstall all access panels.  
e. Ensure all tools and miscellaneous parts have been  
removed.  
4. Relieve all pressure from system before touching  
or disturbing any connections inside compressor ter-  
minal box. If refrigerant leak is suspected around  
compressor terminals, use accepted methods to recov-  
er refrigerant.  
5. Never attempt to repair or solder any components  
while refrigerant system is under pressure.  
6. Do not use torch to remove any component. System  
contains oil and refrigerant under pressure. To remove  
a component, wear protective goggles and gloves and  
proceed as follows:  
START-UP  
Refer to the 48/50HJ Installation Instructions for informa-  
tion on Start-Up for the rooftop unit section.  
Unit Preparation Make sure the unit has been in-  
stalled in accordance with installation instructions and applica-  
ble codes.  
Supply and Exhaust Filters Make sure filters are  
correctly installed on unit. Do not operate without filters in  
place.  
a. Shut off electrical power to unit and tag  
disconnect.  
b. Recover refrigerant to relieve all pressure from  
system, using both high- and low-pressure  
ports.  
Outdoor-Air Inlet Screens Outdoor-air inlet screen(s)  
must be in place before operating the unit.  
Compressor Mounting Compressors are internally  
spring-mounted. Ensure wooden shipping block has been  
removed from under the compressor and holddown bolts are in  
place.  
c. Cut component connection tubing with tubing  
cutter, and remove component from unit.  
Internal Wiring Check all low and high voltage con-  
d. Carefully unsweat remaining tubing stubs  
when necessary. Oil can ignite when exposed to  
torch flame.  
nections for proper locations. Ensure connections are tight.  
Cooling Set Light Commercial Thermidistat mode selec-  
tion to Cooling and fan mode to Auto. Ensure thermostat has  
been adjusted to a setting below room temperature. Refer to  
Table 2 for correct unit operation.  
Refer to 48/50HJ Installation Instructions for Pre-Start-Up  
information for the rooftop unit section. Proceed as follows to  
inspect and prepare the unit for initial start-up:  
Heating Set Light Commercial Thermidistat mode se-  
lection to Heating and fan mode to Auto. Ensure thermostat has  
been adjusted to a setting below room temperature. Refer to  
Table 2 for correct unit operation.  
1. Remove filter access panel, blower access panel, and con-  
trol panel access cover on the energy recovery section.  
2. Read and follow instructions on all WARNING, CAU-  
TION, and INFORMATION labels attached to (or  
shipped with) unit.  
Operating Sequence Refer to Step 5 — Conduct  
Light Commercial Thermidistat Start-Up and Checkout on  
page 33, and Table 2 for energy recovery section operating  
sequence. See Fig. 17.  
3. Make the following inspections:  
a. Inspect for shipping or handling damages such as  
broken lines, loose parts, or disconnected wires.  
b. Inspect for oil at all refrigerant tubing connections  
and on unit base. Detecting oil usually indicates a  
refrigerant leak. Leak-test all refrigerant tubing  
connections using an electronic leak detector,  
halide torch, or liquid-soap solution.  
c. Inspect all field and factory wiring connections Be  
sure that connections are completed and tight.  
d. Inspect upper (supply) and lower (exhaust) coils  
for damage and refrigerant leaks. If fin damage is  
noted, carefully straighten fins using a fin comb.  
SERVICE  
Refer to base unit installation instructions or 62AQ Installa-  
tion Instruction for all service information.  
Fuse Box (48HJ012,014 208/230-3-60 Units  
Only) Certain 48HJ units contain a fuses for the power  
supply. The fuse box is located in the compressor section in a  
single point box. See Fig. 18. Replacement fuses are cartridge  
type, non-renewable, time delay FRN type of the appropriate  
size and voltage. Refer to existing fuse size and voltage for  
replacement.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOFTOP UNIT  
ENERGY RECOVERY  
SECTION  
OUTSIDE AIR  
EXHAUST AIR  
MIXED AIR  
ROOF LINE  
ROOM AIR  
SUPPLY AIR  
Fig. 17 Unit Operation Flow Diagram  
Fig. 18 Fuse Box (48HJ012, 014 208/230-3-60 Units Only)  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 Light Commercial Thermidistat (LCT) Operating Sequence and System Response  
UNOCCUPIED  
COOLING  
ER Comp  
ER Fans  
RT Comp 1  
RT Comp 2  
RT Fans  
RT Heat  
Indoor Temperature Above 2nd Stage  
Set Point  
Humidity Low & OAT Low  
Humidity Low & OAT High  
Humidity High & OAT Low  
Humidity High & OAT High  
On  
Off  
Off  
Off  
On (cyc.)  
Off  
On w/o MM  
On w/o MM  
On w MM  
On w MM  
Off  
On (cyc.)  
On (cyc.)  
On (cyc.)  
On (cyc.)  
Off  
Off  
Off  
Off  
w/o MM  
On w MM  
On w MM  
Off  
Off  
Indoor Temperature Between 1st and  
2nd Stage Set Points  
Humidity Low & OAT Low  
Humidity Low & OAT High  
Humidity High & OAT Low  
Humidity High & OAT High  
Off  
Off  
Off  
Off  
On (cyc.)  
Off  
Off  
Off  
Off  
Off  
Off  
On (cyc.)  
On (cyc.)  
On (cyc.)  
On (cyc.)  
Off  
Off  
Off  
Off  
On w/o MM  
On w MM  
On w MM  
Off  
Off  
Indoor Temperature Below 1st Stage  
Set Point  
Off  
Off  
Off  
Off  
Off  
Off  
NOTE: OAT < 55° all compression off*  
HEATING  
ER Comp.  
ER Fans  
RT Comps.  
RT Fans  
RT Heat  
Indoor Temperature Above 1st Set  
Point  
Off  
Off  
Off  
Off  
Off  
Indoor Temperature Between 1st and  
2nd Stage Set Points  
Indoor Temperature Below 2nd Stage  
Set Point  
Off  
Off  
Off  
Off  
Off  
Off  
On (cyc.)  
On (cyc.)  
On, 50%  
On, 100%  
OCCUPIED  
ER Fans  
COOLING  
ER Comp  
RT Comp 1  
RT Comp 2  
RT Fan  
RT Heat  
Indoor Temperature Above 2nd Stage  
Set Point  
Humidity Low & OAT Low  
Humidity Low & OAT High  
Humidity High & OAT Low  
Humidity High & OAT High  
On  
On  
On  
On  
On  
On  
On  
On  
On w/o MM  
On w/o MM  
On w MM  
On w/o MM  
On w/o MM  
On w MM  
On w MM  
On  
On  
On  
On  
Off  
Off  
Off  
Off  
On w MM  
Indoor Temperature Between 1st and  
2nd Stage Set Points  
Humidity Low & OAT Low  
Humidity Low & OAT High  
Humidity High & OAT Low  
Humidity High & OAT High  
Off  
On  
On  
On  
On  
On  
On  
On  
Off  
Off  
Off  
Off  
Off  
On  
On  
On  
On  
Off  
Off  
Off  
Off  
On w/o MM  
On w MM  
On w MM  
Indoor Temperature Below 1st Stage  
Set Point  
Humidity Low  
Off  
On  
On  
On  
Off  
Off  
Off  
Off  
On  
On  
Off  
Off  
Humidity High  
NOTE: OAT < 55° all compression off*  
HEATING  
ER Comp  
ER Fans  
RT Comps  
RT Fans  
RT Heat  
Indoor Temperature Above 1st Stage  
Set Point  
Off  
On  
Off  
On  
Off  
Indoor Temperature Between 1st and  
2nd Stage Set Points  
OAT >Set Pt  
On  
On  
On  
On  
Off  
Off  
On  
On  
Off  
On, 50%  
OAT <Set Pt  
Indoor Temperature Below 2nd Stage  
Set Point  
OAT >Set Pt  
OAT <Set Pt  
On  
On  
On  
On  
Off  
Off  
On  
On  
On, 50%  
On, 100%  
LEGEND  
Comp Compressor  
ER  
Energy Recovery section  
MM  
OAT  
RT  
MoistureMi$erDehumidification Device  
Outdoor-Air Temperature  
Rooftop Unit  
Set Pt Set Point  
*Unless unit compressor has been rewired as described in Step 11 (page 29).  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Use Tables 3 and 4, and Fig. 19 and 20 when troubleshooting this unit.  
NOTES:  
1. If any of the original wire furnished must be replaced, it must be  
replaced with Type 90° C wire or its equivalent.  
2. Three phase motors are protected under primary single phasing  
conditions.  
3. Thermostat: HH07AT170, 172.  
Subbase: HH93AZ176, 177, 178, and 179.  
4. Set heat anticipator at .14 amp for 1st stage and .14 amp for 2nd  
stage.  
5. Use copper conductors only.  
6. TRAN is wired for 230-v unit. If unit is to be run with 208-v power  
supply, disconnect BLK wire from 230-v tap (ORN) and connect  
to 208-v tap (RED). Insulate end of 230-v tap.  
LEGEND  
C
Contactor  
I
Ignitor  
Field Splice  
Marked Wire  
CAP  
CER  
CH  
Capacitor  
IDM  
IFC  
Induced Draft Motor  
Indoor Fan Contactor  
Indoor Fan Motor  
Compressor Energy Recovery section  
Crankcase Heater  
Compressor Lockout  
Cool Changeover Relay  
Heat Changeover Relay  
Compressor Motor  
Cooling Relay  
IFM  
IGC  
LTLO  
LPS  
LS  
Terminal (Marked)  
Terminal (Unmarked)  
CLO  
COC  
COH  
COMP  
CR  
Integrated Gas Unit Control (48HJ only)  
Low Temp Cooling Lockout  
Low-Pressure Switch  
Limit Switch  
Terminal Block  
Splice  
MGV  
OATC  
OATH  
OCR  
OF  
Main Gas Valve  
CTD  
DB  
Compressor Time Delay  
Defrost Board  
Outdoor-Air Thermostat (Cool)  
Outdoor-Air Thermostat (Heat)  
Occupied Relay  
Splice (Marked)  
DFT  
DM  
Defrost Thermostat  
Damper Motor  
Factory Wiring  
Field Control Wiring  
Field Power Wiring  
Accessory or Optional Wiring  
To indicate common potential  
only. Not to represent wiring.  
Outdoor Fan  
DR  
Defrost Relay  
Equipment  
OFM  
OLR  
PL  
Outdoor Fan Motor  
Overload Relay  
EQUIP  
FPT  
FR  
Freeze-Up Protection Thermostat  
Fan Relay  
Plug Assembly  
QT  
RS  
Quadruple Terminal  
Rollout Switch  
FU  
Fuse  
GND  
HM  
Ground  
RVS  
SEN  
TB  
Reversing Valve Solenoid  
Sensor  
Humidity Relay  
HPS  
HR  
High-Pressure Switch  
Heating Relay  
Terminal Block  
Transformer  
TRAN  
HS  
Hall Effect Sensor  
Fig. 19 Typical Wiring Schematic (Standard Controls)  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 19 Typical Wiring Schematic (Standard Controls) (cont)  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLK  
VIO  
RED  
HK50AA039  
TB - 2  
SAT  
BLU  
BLK  
PNK  
VIO  
PNK  
VIO  
BRN  
BRN  
7
6
7
6
BLU  
BRN  
BLK  
1
ORN  
PNK  
BRN  
PremierLink  
2
3
OAT  
11  
10  
8
Space Temp./ Set  
Point Adjustment  
RED  
11  
10  
8
BRN  
BLU  
BRN  
RED  
4
5
6
YEL  
BLU  
GRN  
YEL  
BLU  
2
Indoor Air  
Quality Sensor  
2
BRN  
BLU  
ORN  
WHT  
3
4
1
3
4
1
7
8
PNK  
GRA  
GRA  
BLK  
Outdoor Air  
Quality Sensor  
J7  
PP/MP  
J9  
0-20 mA  
J8  
Relays  
J2  
COMMS  
J1  
PWR  
RED  
BLU  
Power Exhaust/Energy Recycler  
GRA  
ORN  
PNK  
5
5
TB - 3  
PNK  
PNK  
WHT GRA  
ORN ORN  
BRN  
YEL  
ORN  
RED  
9
RMTOCC  
9
GRN  
YEL  
BLU  
WHT  
PNK  
RED  
WHT  
BLK  
1
2
3
GRA  
BLK  
TB - 1  
RED  
WHT  
12  
12  
CMPSAFE  
FSD  
1
R
RED  
GRA  
2
3
Y1  
SFS  
4
5
6
Y2  
ORN  
4
5
6
W1  
ORN  
PNK  
2
3
GRA  
GRA  
TR  
W2  
G
TR1  
CCN  
Comm.  
7
8
WHT  
ACCUSENSOR  
7
8
C
EconomiSer2  
4 - 20mA  
BRN  
X
RTU Terminal  
Board  
LEGEND  
COMMS Communications  
OAT  
PWR  
SAT  
Outdoor Air Temperature Sensor  
Power  
Supply Air Temperature Sensor  
Fig. 20 Typical Wiring Schematic (with PremierLinkControls)  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 Heating and Cooling Troubleshooting  
PROBLEM  
CAUSE  
REMEDY  
Compressor and outdoor fan Power failure.  
Call power company.  
Replace fuse or reset circuit breaker.  
will not start.  
Fuse blown or circuit breaker tripped.  
Defective thermostat, contactor, transformer, con- Replace component.  
trol relay, or capacitor.  
Insufficient line voltage.  
Incorrect or faulty wiring.  
Determine cause and correct.  
Check wiring diagram and rewire correctly.  
Light Commercial Thermidistat program in UC1  
or UC2 mode.  
Check Light Commercial Thermidistat program. See Step 5  
Conduct Light Commercial Thermidistat Start-Up and  
Checkout on page 33.  
Defective fan motor.  
Replace fan motor.  
Compressor will not start but Faulty wiring or loose connection in compressor Check wiring and repair or replace.  
outdoor fan runs.  
circuit.  
Compressor motor burned out, seized, or internal Determine cause. Replace compressor.  
overload open.  
Defective run/start capacitor, overload, start relay, Determine cause and replace.  
Time Guard® device.  
No DEHUM signal from Light Commercial  
Thermidistat.  
Check for DEHUM signal on Light Commercial Thermidistat  
LCD display.  
Time Guard device not timed out.  
Allow time for Time Guard device to recycle unit.  
Compressor cycles (other  
than normally satisfying  
thermostat).  
Refrigerant overcharge or undercharge.  
Recover refrigerant, evacuate system, and recharge to  
nameplate.  
Replace and determine cause.  
Determine cause and correct.  
Determine cause and correct.  
Determine cause and replace.  
Defective compressor.  
Insufficient line voltage.  
Blocked outdoor coil or dirty air filter.  
Defective run/start capacitor, overload, or start  
relay.  
Faulty outdoor-fan (cooling) or indoor-fan (heat-  
ing) motor or capacitor.  
Replace.  
Restriction in refrigerant system.  
Suction pressure greater than Defective TXV.  
Locate restriction and remove.  
Replace TXV.  
100 psig in Cooling mode.  
Excessive head pressure.*  
Dirty air filters.  
Replace filters.  
Dirty coils.  
Clean coils.  
Refrigerant overcharged.  
Air in system.  
Condensing air restricted or air short-cycling.  
Low refrigerant charge.  
Compressor valves leaking.  
Restriction in liquid tube.  
Recover excess refrigerant.  
Recover refrigerant, evacuate system, and recharge.  
Determine cause and correct.  
Check for leaks; repair and recharge.  
Replace compressor.  
Head pressure too low.*  
Remove restriction.  
Excessive suction pressure.* High heat load.  
Compressor valves leaking.  
Check for source and eliminate.  
Replace compressor.  
Refrigerant overcharged.  
Dirty air filters or coils.  
Recover excess refrigerant.  
Replace filter, clean coils.  
Suction pressure too low.*  
Low refrigerant charge.  
Metering device or low side restricted.  
Insufficient indoor airflow.  
Check for leaks; repair and recharge.  
Remove source of restriction.  
Increase air quantity. Check filter and replace if necessary.  
LEGEND  
TXV Thermostatic Expansion Valve  
*Energy recovery section uses TXVs with a 100 psig maximum operating pressure (MOP) feature to limit suction pressure  
in Cooling mode at high temperatures. Always consult charging chart for correct operating pressures.  
Table 4 Supply-Air Damper Troubleshooting  
PROBLEM  
CAUSE  
REMEDY  
Damper does not open; fan(s) off.  
OCR not energized (thermostat in Unoccupied  
mode).  
Check Light Commercial Thermidistat program  
settings (see Step 5 Light Commercial Thermi-  
distat Start-Up and Checkout section, page 33).  
OCR defective.  
Replace OCR.  
Damper jammed.  
Free damper.  
Damper motor defective.  
Loose wiring.  
Damper jammed.  
Replace damper motor.  
Check wiring and correct.  
Free damper.  
Damper will not close.  
Motor return spring broken.  
Replace motor.  
LEGEND  
OCR Occupied Relay  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 2002 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-80122 Printed in U.S.A. Form 48/50HJ,62AQ-2SIS Pg 42 9-02 Replaces: 48/50HJ,62AQ-1SIS  
Book 1  
1
4
4
Tab 1a 1b 6a 6b  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOFTOP UNIT (RTU) AND ENERGY RECOVERY SECTION (62AQ) START-UP CHECKLIST  
(Remove and Store in Job File)  
I. PRELIMINARY INFORMATION  
RTU  
62AQ  
COBRA™ ENERGY RECOVERY UNIT MODEL NO.:  
SERIAL NO.:  
SERIAL NO.:  
TECHNICIAN:  
/
/
/
BASE UNIT MODEL NO.:  
DATE:  
II. PRE-START-UP (insert checkmark in box as each item is completed)  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS  
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
CHECK THAT SUPPLY AND EXHAUST HOODS ARE INSTALLED AND AIR FILTER(S) ARE CLEAN AND IN  
PLACE  
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS  
CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS (62AQ300 BELT  
DRIVE EXHAUST FAN AND SUPPLY FAN)  
III. START-UP  
COMBINED ELECTRICAL (COBRA ENERGY RECOVERY UNIT)  
SUPPLY VOLTAGE  
COMPRESSOR AMPS  
INDOOR FAN AMPS  
L1-L2  
L1  
L2-L3  
L2  
L3-L1  
L3  
L1  
L2  
L3  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
ENTERING SUPPLY-AIR (RTU)  
LEAVING AIR TEMPERATURE (RTU)  
DB  
WB  
WB  
WB  
WB  
DB  
DB  
DB  
PRESSURES (IN COOLING MODE)  
ROOFTOP UNIT  
REFRIGERANT SUCTION  
PSIG TEMP AT COMPRESSOR  
PSIG TEMP AT COMPRESSOR  
F
F
REFRIGERANT DISCHARGE  
VERIFY REFRIGERANT CHARGE USING CHARGING CHART LABEL ON UNIT.  
62AQ  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
PSIG TEMP AT COMPRESSOR  
PSIG TEMP AT COMPRESSOR  
F
F
VERIFY REFRIGERANT CHARGE USING CHARGING CHART LABEL ON UNIT.  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. START-UP (cont)  
AIRFLOWS (62AQ)  
SUPPLY AIR  
CFM  
LOW  
MOTOR SPEED (Circle One)  
MEDIUM  
45  
HIGH  
60 90  
DAMPER SETTING (°) (Circle One)  
30  
EXHAUST AIR  
CFM  
MOTOR SPEED (Circle One)  
DAMPER SETTING (°) (Circle One)  
LOW  
30  
MEDIUM  
60  
HIGH  
45  
90  
IV. LIGHT COMMERCIAL THERMIDISTAT ACCESSORY  
NOTE: To disable Keyboard Lock, press MODE, COPY PREVIOUS DAY, SET TIME/TEMP, and HOLD End buttons in  
sequence within 5 seconds.  
PROGRAMMED  
Yes  
Yes  
No  
No  
KEYBOARD LOCK  
OCCUPIED SETTINGS:  
ROOM TEMP  
ROOM RH  
F
%
TIMES:  
OC1  
ON  
ON  
OFF  
OFF  
OC2  
TIMES:  
UC1  
UC2  
Copyright 2002 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-80122 Printed in U.S.A. Form 48/50HJ,62AQ-2SIS Pg CL-2 9-02 Replaces: 48/50HJ,62AQ-1SIS  
Book 1  
1
4
4
Tab 1a 1b 6a 6b  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blackberry Home Theater Server blackberry enterprise server for microsoft exchange User Manual
Black Box Thermometer Dual Input Thermometer User Manual
Bosch Appliances Camera Accessories LBC1259 00 User Manual
Bosch Appliances Computer Keyboard LTC 8557 Series User Manual
Bradley Smoker Outdoor Shower E19 310DC User Manual
Breville Water Dispenser AF5 User Manual
Campbell Hausfeld Power Roller AL2270 User Manual
Canon Digital Camera SX200IS User Manual
Char Broil Gas Grill 463210510 User Manual
Chauvet Speaker 360Z LED User Manual