HOT WATER STORAGE TANK
ASME CODE
175 GALLONS
APPLICATION
Thetankcanbeinstalledwheneverthedemandutilizesstoredwaterfrom175gallonsormore. Installedindividuallyor
as several tanks in parallel, this tank can provide 80% draw without an appreciable temperature decrease in single
temperatureapplication.
FEATURES
•
•
•
•
•
•
175 - Gallon storage
ASME constructed
150 PSI maximum working pressure
Twomagnesiumanodes
Meets ASHRAE 90.1
Los Angeles city approval
applicationno.M-880057
Insulatedandjacketed
R-16valueinsulation
Foaminsulation
Handhole
Fitsthrough36”doorway
Labelsforeachopening
Large 1" drain port
•
•
•
•
•
•
•
•
Approx. Shipping Weight: 596 lbs.
CONSTRUCTIONCODE
•
•
Steel Jacket - Complete unit is enclosed in baked
enamel steel jacket. With minimum care, the jacket
will remain attractive and colorful for years.
Tank Openings - Circulating tank connections and
hot water outlets are 2-1/2” NPT. Other openings
are for T and P valve, tankstat, thermometer and
drainport.(Drainvalvenotprovided.)
Handhole - Equipped with 3" x 4-1/8" handhole for
easy cleanout and inspection.
Labels-Openingsareindividuallylabeled
for easy identification.
•
Storage Tank - The tank is lined with a double
coating of a high-temperature glass formula. It is
built for long life under any water conditions. Two
magnesium anode rods are factory installed.
R-FoamInsulation-Rigidpolyurethanefoaminsu-
lation for improved economy and fuel savings. The
insulation is R-16 value and complies to ASHRAE
90.1.
•
•
•
SAMPLESPECIFICATION
The hot water storage tank shall be a Raypak 175-gallon factory insulated and jacketed tank.
Thetankshallhaveadoublecoatingofahightemperatureglassliningandbeequippedwithtwo(2)magnesiumanode
rods. The tank shall be ASME constructed and designed for 150 PSI working pressure and equipped with a handhole
for cleaning and inspection.
The tank shall be insulated with rigid polyurethane foam that completely surrounds the tank and shall be enclosed in
abakedenamelsteeljacket. ThetankinsulationmustbeR-16valueandmustmeetorexceedASHRAEstandard90.1.
The tank shall be covered by a five (5) year limited warranty against corrosion.