Nordyne E3 User Manual

Downflow, Upflow Electric Furnaces  
Owners Manual/Installation Instructions  
E3 Series (Air Conditioner/Heat Pump Air Handler)  
IMPORTANT: Read this owner information  
to become familiar with the capabilities and  
use of your heating appliance. Keep this  
literature where you will have easy access  
to it in the future. If a problem occurs, check  
the instructions and follow recommenda-  
tions given. If these suggestions don’t  
eliminate your problem, call the appropriate  
NORDYNE distributor. A distributor service  
list is included with this appliance.  
WARNING:  
Do not store or use gasoline or other  
flammable vapors and liquids in the  
vicinity of this or any other appliance.  
Improper installation, adjustment,  
alteration, service or maintenance  
can cause injury, property damage,  
or death. Refer to this manual. For  
assistance or additional information  
consult a qualified dealer or service  
agency. To avoid personal injury or  
property damage, ask a service  
techniciantoinspectthefurnaceandto  
replaceanypartofthecontrolsystem  
which has been under water.  
• Circuit breakers are in “ON” position.  
• All power supply switches for furnace and  
SECTION 1. OWNER INFORMATION  
outside unit (if installed) are turned on.  
OPERATING INSTRUCTIONS  
Before Operating System  
• Furnace door is closed and properly  
latched.  
Before operating your heating/cooling system  
(see Figure 1), make sure that:  
Refer to the owner’s manual supplied with the  
optional heat pump or air conditioner for further  
information.  
• Control panel covers are closed.  
• Blower and/or relay control plugs are  
plugged in.  
• Fan switch is set to “AUTO” (E3EH units  
only).  
CAUTION:  
For optional A/C or H/P systems,  
always wait at least five minutes after  
the system shuts off before restarting  
the system. Observe this procedure  
when operating the system per the  
following instructions.  
CAUTION:  
No user serviceable parts inside  
control panel. DO NOT OPEN.  
Temperature Selector  
10  
20  
30  
Temperature  
Scales  
50 60 70 80 90  
Fan Switch  
(optional sub-base)  
System Switch  
(optional sub-base)  
Indoor Coil  
(optional)  
SYSTEM  
HEAT OFF COOL  
VENTILATE  
ON AUTO  
Coil Air Filters  
(used with indoor coil)  
Furnace Air Filter  
(NOT used with  
coil air filters)  
Blower  
Circuit Breakers  
Data Label  
Control Panel  
Cover (left)  
Control Panel Cover (right)  
Figure 1. Furnace Parts Identification  
E 3 EB - 010 H  
Product Type  
E - Electric Furnace  
Electrical Code  
H - 240-1-60  
Generation  
3 - Third Series  
Primary Capacity  
010 - 10 kw  
015 - 15 kw  
020 - 20 kw  
012 - 12 kw  
017 - 17 kw  
023 - 23 kw  
Product Identifier  
EB - A/C Blower Equipped Relay  
EX - Multi-Speed, X13 Motor  
Used with Platinum Series  
Model Identification  
3
To Operate System in Cooling Mode  
To Shut Off System  
1. Make sure blower selector switch is on  
NOTE: The “FAN ON/FAN AUTO” (fan switch)  
and “HEAT/OFF/COOL(system switch) are  
located either on your thermostat (if it’s supplied  
with a sub-base) or on the relay box added to  
your furnace.  
“Auto”.  
2. Set thermostat temperature selector to  
lowest temperature setting, OR...  
3. Forthermostatswithoptionalsub-base(see  
Figure 1), or for systems with relay box, set  
system switch to “OFF.”  
1. Make sure blower selector switch is on  
“Auto.”  
2. Set fan switch to “AUTO.”  
3. Set system switch to “COOL.”  
4. Set thermostat temperature selector to  
desired comfort level.  
WARNING:  
To prevent hazard of electrical shock  
and injury from moving parts, be  
certain the thermostat is off and the  
furnace circuit breaker(s) are in the  
“OFF”positionbeforeservicing.Close  
andproperlylatchtheouterdoorafter  
doing the following recommended  
maintenance.  
To Operate System in Heating Mode  
1. Make sure blower selector switch is on  
“Auto.”  
2. Set fan switch to “AUTO.”  
3. Set system switch to “HEAT.”  
4. Setthermostattemperatureselectorswitch  
to desired comfort level.  
MAINTENANCE INSTRUCTIONS  
NOTE: Allowatleastonehourfortheroomtem-  
perature to stabilize before you make a second  
adjustment to the thermostat setting. Once the  
desired comfort level is established, make only  
small adjustments to the thermostat setting to  
meet changing temperature conditions.  
Regularly  
NOTE: If a cooling coil is installed, furnace  
filter is not used.  
1. Replace furnace air filter (see Figure 1),  
OR...  
2. Remove coil filters, wash, and allow to dry.  
Re-install coil filters to original positions.  
3. Vacuum or wipe clean interior of furnace  
cabinet.  
4. Clean all lint and dust from around fur-  
nace.  
To Operate Blower Continuously  
1. Setblowerselectorswitchto“ON”forsummer  
air circulation only (see Figure 1),  
OR  
2. If thermostat is equipped with optional  
heating/cooling sub-base or relay box (see  
Figure 1), set fan switch to “ON.”  
Every Six Months  
1. Vacuum or wipe away any dust or lint on  
blower motor.  
To Balance Air Distribution  
1. On a typical day, set thermostat selector to  
desiredcomfortlevelandoperatesystemfor  
several hours with all air registers open.  
2. With system on, check temperature in all  
rooms.  
Before Each Heating Season  
NOTE: If a cooling coil is installed, furnace  
filter is not used.  
1. Replace furnace air filter (see Figure 1),  
OR  
3. Partially close registers in rooms that are  
too warm (in heating mode) or too cool  
(in cooling mode) and in rooms that are  
infrequently occupied.  
4. Re-check room temperature and adjust  
registers as needed.  
2. Remove coil filters, wash, and allow to dry.  
Re-install coil filters to original positions.  
3. Have a qualified serviceman inspect all  
furnace components and field wiring and  
clean and service heating system as  
needed. If this furnace was installed with  
aluminum power supply wiring, have ser-  
viceman periodically check all connections  
topreventpossibleequipmentfailureand/or  
fire hazard. Do not attempt any service  
function yourself which requires opening  
furnace control panel covers.  
4
SECTION 2.  
BEFORE YOU CALL A SERVICEMAN  
1. Makesurethermostattemperatureselector  
is set above room temperature for heating  
or below room temperature for cooling. If  
thermostat is equipped with heating/cool-  
ing sub-base, make sure system switch  
(see Figure 1) is set to “HEAT” for furnace  
operation or set to “COOLfor optional air-  
conditioning operation.  
2. Check main household service panel to  
see if appropriate circuit disconnect(s) for  
appliance power supply is on.  
3. RefertoinstructionsunderBeforeOperating  
System for pre-operation checks.  
4. Refer to instructions under Before Each  
Heating Season for maintenance proce-  
dures and recommended service checks.  
5. Refer to owner’s manual provided with  
optional air conditioner or heat pump (if  
installed) for service and maintenance.  
INSTALLER INFORMATION  
GENERAL  
These instructions and specifications are pri-  
marily intended to assist qualified individuals  
experienced in the proper installation of home  
heating and air conditioning appliances. Some  
local codes require licensed personnel for the  
installation and service of this type of equip-  
ment. Approved installation, operation, and  
maintenance of this central heating system  
appliance must be in accordance with the listed  
specifications contained in these instructions  
and other documents supplied with the furnace  
and/oroptionalairconditioningequipment. Refer  
to local authorities having jurisdiction for further  
information.  
Beforebeginninginstallation,readtheseinstruc-  
tionsthoroughly. Followallwarningsandcautions  
in the instructions and on the unit.  
NOTE: All servicing of this heating appliance  
otherthanthenormalmaintenancedescribedin  
this section must be done by authorized trained  
service personnel. Do not open the control  
panels (see Figure 1) at any time.  
Improper installation, service adjustment, or  
maintenance can cause explosion, fire, electri-  
cal shock or other conditions which may result  
in personal injury or property damage. Unless  
otherwise noted in these instructions, use only  
factory-authorized kits and accessories when  
modifying this product.  
Please specify the complete model and serial  
numbers shown on the furnace data label (see  
Figure 1) for all warranty service and when or-  
deringreplacementpartsoroptionalequipment.  
Refer to the replacement parts list provided with  
the furnace for part numbers.  
Overview of E3 Furnace  
E3E(-) Series electric furnaces are available in  
twomodels.E3EHmodelsareequippedwiththe  
standard two-speed blower. E3EH models can  
beeasilyconvertedforusewithNORDYNEsplit-  
system air conditioners and heat pumps. E3EB  
models are air-conditioning ready; that is, they  
are equipped with a multi-speed (four-speed)  
blower, blower relay, and cabinet insulation kit.  
SeeTable3forcoolingandheatpumpavailability  
with factory installed blower.  
OPTIONAL AIR CONDITIONER  
AND HEAT PUMP  
Your E3 Series electric furnace is approved for  
use with an optional central air conditioner or a  
heat pump. To adapt this heating appliance to  
a “total comfort system,contact your nearest  
NORDYNE distributor.  
Optional air conditioners and heat pumps are  
listed by Underwriters’ Laboratories (UL) or  
Environmental Testing Laboratories (ETL) and  
certified by ARI and the Canadian Standards  
Association(CSA),orWarnockHerseyorETLC.  
These cooling systems include energy-sav-  
ing components to provide maximum cooling  
performance at electrical energy usage levels  
established by federal standards. Refer to the  
operation instruction label on your furnace for  
theoptionalairconditioningequipmentapproved  
for your heating appliance.  
Fortypicalunductedreturnairdownflowapplica-  
tions,anair-conditionerorheat-pumpcoilcanbe  
installed by mounting the coil directly on top of  
the furnace without adding sheet metal cavities  
or cutting and trimming wood panels.  
Areturnairgrilleforclosetoralcoveinstallations  
is available. For downflow alcove installations,  
the grille (with frame provided) may be attached  
to the top of the furnace and all paneling and  
trim flushed to it. This installation provides an  
access door for future installation of NORDYNE  
air conditioning or heat pump coils on top of  
the furnace.  
5
Powerentranceforallmodelsmaybethroughthe  
rightsideorthroughthebottomoftheunit(when  
viewing the unit in a downflow position).  
• AmericanNationalStandards(ANSI)A119.11,  
C1-NFPA 7 (National Electrical Code)  
• CANADIANSTANDARDS(C.S.A.)Z240.6.1,  
and Z240.9.1.  
UNIT CHECKOUT  
Before installing this furnace:  
All local codes having jurisdiction shall also  
apply.  
1. Inspect unit for possible shipping damage.  
If shipping damage is found, file claim with  
transportation company.  
2. Record furnace model number and serial  
number (see furnace data label) for future  
reference.  
3. Carefully read all instructions supplied with  
optional equipment to be installed with  
furnace.  
Air Duct Codes and Specifications  
Air ducts must be installed in accordance with  
National Fire Protection Association standards  
NFPA 90A and NFPA 90B, these instructions,  
and all applicable local codes.  
• Materials: Air ducts must be aluminum,  
tin plate, galvanized sheet steel, or other  
approved materials for outlet or return air  
ducts.  
• Construction: Snap-Lock or Pittsburgh-Lock  
seamsarepreferred. Allothertypesofseams  
must be made tight to prevent leakage.  
• Sizing:Supplyductsystemmustbedesigned  
for proper air distribution. Static pressure  
measured externally to furnace shall not ex-  
ceed static pressure rating listed on furnace  
nameplate.  
CODES, SPECIFICATIONS, AND  
REQUIREMENTS  
Furnace Codes  
Installation and wiring of this furnace, as well as  
the design and construction of the home duct  
system,mustbeinaccordancewithoneormore  
of the following codes:  
• HUDMANUFACTUREDHOMECONSTRUC-  
TION AND SAFETY STANDARD (Title 24,  
Part 3280)  
• Location of Openings: Duct system must be  
designed so that no supply registers are lo-  
cated in duct system directly below furnace.  
May vary by model, check the unit data label for  
applicable agency listing mark.  
Listing agency(s)  
Approved for: single/multistory residential or mobile/  
Approved Installation Congurations modular/manufactured structures. Upow, downow,  
(freestanding/closet/alcove)  
Accessibility for Servicing  
Minimum of 18"(46cm) required in front of unit.  
0" from all surfaces of furnace cabinet, ducts, optional  
coil housing and plenum connector. No separate  
subbase required for installations on combustible  
ooring.  
Minimum Clearance to  
Combustibles  
200 in (1290 cm ) heating only*  
235 in (1516 cm ) A/C or H/P up to 4 ton installed  
250 in (1613 cm ) A/C or H/P up to 4 ton w/1" clearanced  
installed  
390 in (2516 cm ) A/C or H/P up to 5 ton installed  
*or return air grille and frame assembly p/n 902989 or  
wall mount grille p/n 902999  
Minimum return air opening  
required (total free area)  
Use return air grille and frame assembly P/N 902989 or  
equivalent for alcove installation.  
Return air grille (closet or alcove  
installation)  
Use wall mount return air grilled P/N 902999 or  
equivalent for closet installation.  
155 in (1000 cm ) must be added for 5 ton A/C or H/P  
system.  
Table 1. Miscellaneous Listings & Installation Requirements  
6
Return Air Codes and Requirements  
Unducted return air systems may be used for  
closet or alcove installations.  
Return Air Grille  
Areturnairgrilleandframeassembly(seeFigure  
2)isavailableforuseinunductedreturnairinstal-  
lations.Indownflowalcoveinstallations,thegrille  
and frame assembly may be mounted directly  
to the top of the furnace. In closet installations,  
a wall mount grille is available for attachment  
to a door or wall.  
NOTE:Applicableinstallationcodesmaylimitthe  
furnacetoinstallationinasingle-storyresidence  
only. Furnace installations other than closet or  
alcove installations require ducted return air  
systems.  
Optional Automatic Furnace  
Damper #901083 -  
Air return to the furnace must have a minimum  
free area opening (see Table 1).  
Furnace may (not required) be equipped with  
theoptionalautomaticdamperwhenapackaged  
air conditioner is installed and connected to the  
warm air duct system. This damper prevents  
cooled air from discharging through the furnace  
cabinet,causingexcessivecoolingoftheimmedi-  
ate area. Refer to instructions supplied with the  
damper for details.  
Acceptable floor or ceiling return air systems  
for closet installations with return air entering  
through an opening in the closet floor or ceiling  
must meet all of the following requirements:  
• Return air opening into closet, regardless of  
its location, must not be smaller than size  
specified on unit data label.  
• If located in floor of closet, return air opening  
must be provided with means of preventing  
its inadvertent closure by a flat object placed  
over opening.  
• Materials located in return air duct system  
must have a flame-spread classification of  
200 or less.  
Multi-Speed Blower Conversion  
Package (4 or 5 ton):  
Upgrade blower packages are available for  
adding air conditioning or heat pump systems.  
See furnace “Options and Compatibility” label  
for systems available.  
• Noncombustible pans having 1” upturned  
flanges must be located beneath openings  
in a floor-return duct system.  
• Wiringmaterialslocatedinreturnductsystem  
must conform to NEC Article 300-22(c).  
• Gas piping must not run in or through return  
air duct system.  
• If return air opening is located below top  
of furnace, a minimum clearance must be  
provided between opening and furnace (see  
“Accessibility for servicing” in Table 1).  
TYPICAL INSTALLATION OF  
DOWNFLOW SYSTEMS OR  
PLATINUM SYSTEM  
Thefollowingstepsdescribeinstallationinstruc-  
tions for an under-the-floor supply duct system  
with a return air system that can be either  
unducted or ducted. Duct connectors (Table 4)  
are recommended for this application.  
NOTE:Beforeinstallingthisfurnace,considerall  
clearancesfortheinstallationandfutureservicing  
of the furnace. Refer to Table 1.  
Closed-Off Space Requirements  
Return Air and Filtering Systems  
Living space not served by, and closed off from,  
thereturnairductstothefurnacebydoors,sliding  
partitions, and other means must be provided  
with permanent, uncloseable openings in the  
doors or partitions to allow air to return to the  
furnace from all parts of the home. Return air  
grilles, with a minimum open area of one square  
inch for every five square feet of living space  
closed off from the furnace, must be provided  
in the door or room partition.  
Furnaces may be installed with unducted or  
ducted return air. For unducted return air  
systems, either the optional grille and frame  
assembly or the optional wall mount grille is rec-  
ommended. For ducted return air systems with  
air conditioners or heat pumps, either providing  
an access panel in the duct or using the optional  
coil cabinet is recommended. The duct system  
must be properly sized so as to account for any  
additionalexternalstaticpressureproducedfrom  
the chosen filtering method.  
OPTIONAL EQUIPMENT  
ContactyournearestNORDYNEdistributorfora  
complete list of electric furnace accessories.  
7
8
Item Number  
(See Figure)  
Description  
4-Speed Blower  
7
1
4 Ton - See notes: 1 & 5  
5 Ton - See Note: 1  
4
27"  
(686 mm)  
A.C./H.P. Relay Control  
See Note: 1  
Cabinet insulation Kit  
See Notes: 1 & 5  
A-Coil Conversion Kit  
See Note: 2  
2
3
4
1
2
Coil Cabinet  
See Note: 3  
5
29"  
(737 mm)  
Upow Stand  
See Note: 4  
6
7
8
3
A/C and H/P Indoor Coils  
Return Air Grille and  
Frame  
Notes:  
1) For A/C and H/P use.  
2) Includes coil filters.  
3) For upflow or downflow installations.  
4) For upflow A/C or H/P installations (includes one filter; use  
filter from furnace to complete filtering system in this acces-  
sory).  
20" (508 mm)  
Cabinet  
Insulation  
5) Standard in EB models.  
Table 2. Optional Air Conditioning and  
Heat Pump Equipment  
29"  
(737 mm)  
11/16"  
(17 mm)  
20-1/8"  
(511 mm)  
3"  
(76 mm)  
23 3/4" (603 mm)  
Upflow Coil Cabinet  
24 3/4” (628 mm)  
Figure 3. Optional Rear Mounting Plate  
(P/N 389080)  
20”  
(508 mm)  
20” (508 mm)  
Upflow Stand  
NOTE: See Table 2 for descriptions  
and notes  
Figure 2. Optional Accessories  
8
Table 3. Unit Specifications  
E3EH  
Electric Furnace Models  
010H  
012H  
015H  
017H  
020H  
023H  
Rated Heating Output, Btuh  
(see note 1)  
35,000  
41,000  
53,000  
57,000  
70,000  
75,000  
Watts (Total kw, Heating  
Elements and Blower)  
10.4  
12.0  
15.4  
16.6  
20.4  
22.0  
Supply Voltage  
240 Volts/60Hz/1-Phase  
3 (15.0) 3 (16.2)  
Heating Elements,  
No.(Total kw)  
2 (10.0)  
2 (11.6)  
4 (20.0)  
4 (21.6)  
Blower Wheel Size  
Motor Speed,  
H.P. Rating, Amps  
10.5" Dia., 8" Wide  
2 Speed, 1/5 HP, 2.0  
0.3  
Test ESP, in. w.c. Max  
Optional Cooling Available with  
factory installed blower  
2.0 - 3.0 Ton (see note 3)  
Optional Heat Pump Available  
with factory installed blower  
2.0 - 3.0 Ton (see note 3)  
16" x 20" x 1" (nominal)  
n/a (see note 3)  
Air Filter (Standard)  
Furnace Dimensions Width-20" (508mm), Height-29" (737mm) (see note 2), Depth-24 1/2" (623mm)  
E3EB  
017H  
Electric Furnace Models  
010H  
012H  
015H  
020H  
023H  
023H 5-Ton  
75,000  
Rated Heating Output, Btuh  
(see note 1)  
35,000  
41,000  
53,000  
57,000  
70,000  
75,000  
Watts (Total kw, Heating  
Elements and Blower)  
10.4  
12.0  
15.4  
16.6  
20.4  
22.0  
22.0  
Supply Voltage  
240 Volts/60Hz/1-Phase  
Heating Elements,  
No.(Total kw)  
2 (10.0)  
2 (11.6)  
3 (15.0)  
3 (16.2)  
4 (20.0)  
4 (21.6)  
4 (21.6)  
11" Dia.,  
Blower Wheel Size  
8" W  
4 Spd,  
Motor Speed,  
H.P. Rating, Amps  
4 Speed, 1/3 HP, 2.9  
3/4HP 3.8  
Amps  
Test ESP, in. w.c. Max  
0.3  
Optional Cooling Available with  
factory installed blower  
2.0 - 4.0 Ton (see note 4)  
2.0 - 5.0 Ton  
Optional Heat Pump Available  
with factory installed blower  
2.0 - 4.0 Ton  
Air Filter (Standard)  
Furnace Dimensions  
16" x 20" x 1" (nominal)  
Width-20" (508mm), Height-29" (737mm) (see note 2), Depth-24 1/2" (623mm)  
E3EX  
017H  
Electric Furnace Models  
010H  
012H  
015H  
020H  
Rated Heating Output, Btuh  
(see note 1)  
35,000  
41,000  
53,000  
57,000  
70,000  
Watts (Total kw, Heating  
Elements and Blower)  
11.4  
13.0  
16.4  
17.6  
21.4  
Supply Voltage  
240 Volts/60Hz/1-Phase  
Heating Elements,  
No.(Total kw)  
2 (10.0)  
2 (11.6)  
3 (15.0)  
10.5" Dia., 8" Wide  
Multi-Speed, 3/4 HP, 6.0  
0.3  
3 (16.2)  
4 (20.0)  
Blower Wheel Size  
Motor Speed,  
H.P. Rating, Amps  
Test ESP, in. w.c. Max  
Optional Cooling Available with  
factory installed blower  
2.0 - 4.0 Ton  
Optional Heat Pump Available  
with factory installed blower  
2.0 - 4.0 Ton  
Air Filter (Standard)  
16" x 20" x 1" (nominal)  
Width-20" (508mm), Height-29" (737mm) (see note 2)  
Depth-24 1/2" (623mm)  
Furnace Dimensions  
1. Heating output rated at listed voltage.For outputs at voltages other than 240V, multiply Btuh rating by the following  
factors: x 0.92 (230V), x 0.84 (220V), x 0.75 (208V)  
2. Height is 56” with return air grille installed, 58” with coil cabinet and 72” with coil cabinet and upflow stand.  
3. The factory installed blower for the EH models can be replaced with a multi-speed blower allowing the units to  
accept up to 5 tons of air conditioning or 4 tons heat pump.  
4. The factory installed blower for the EB models can be replaced with a multi-speed blower allowing the units to  
accept up to 5 tons of air conditioning.  
9
(see Figure 3) supplied with the duct connec-  
tors is recommended for use with this type of  
installation.  
NOTE: Refer to the instructions supplied with  
any additional accessories for further installa-  
tion details.  
Filtering Methods - Non-Ducted Return Air  
1. Without A/C or H/P uncased coil:  
- use the filter supplied with the furnace;  
ensure that the filter is installed mat side  
downbetweenthelterretainerandfurnace  
top (see Figure 4).  
2. With A/C or H/P uncased coil:  
- use the optional coil filters; the filter sup-  
pliedwiththefurnaceisnotused;REMOVE  
AND DISCARD THIS FILTER.  
Selecting Duct Connector  
Non Platinum Duct Connector  
1. Determinedepthofoorcavityfromsurface  
of floor to top of supply air duct (see Figure  
5).  
2. Select appropriate model from Table 4  
which matches X-dimension of floor cavity.  
To maximize air delivery, remove reducer  
(C in Figure 5) to obtain largest open area  
that will fit duct/floor construction.  
3. With optional coil housing:  
NOTE:  
Duct connectors may be  
- see coil cabinet instructions for specific  
filtering methods.  
installed in any one of four positions.  
Platinum Duct Connector  
Filtering Methods - Ducted Return Air  
1. Without optional coil housing:  
- install a filter with a minimum unrestricted  
medium area of 324 square inches in the  
duct above the coil that is accessible for  
monthly cleaning or replacement by hom-  
eowner.  
1. The 14” round duct connector (903896) is  
designed to connect directly to a 14” flex-  
duct.  
Frame  
2. With optional coil housing:  
-install a filter with a minimum unrestricted  
medium area of 324 square inches in the  
duct above the coil that is accessible for  
monthly cleaning or replacement by hom-  
eowner.  
Fasteners (4)  
Top of  
Furnace  
Optional Duct Connectors for  
Downflow Systems  
Duct connectors are recommended for heated  
air distribution in under-the-floor duct systems.  
With this system, furnaces may be installed on  
combustible flooring without a separate sub-  
base. Also, the furnace rear mounting plate  
Grille  
Furnace Filter  
(not used with  
A/C or H/P)  
Figure 4. Grille Support Frame and Grille  
Assembly  
FLOOR CAVITY  
x
SUPPLY AIR DUCT  
*OPENING TO DUCT  
A= 13-1/4" (337 mm)  
B= 10-3/4" (274 mm)  
WITH PLATE (C) REMOVED  
OPENING BECOMES  
13-1/4” x 13-1/4”  
TOP VIEW  
19”  
Reducer  
(483 mm)  
*Felt Seal  
C
A
B
Corner  
Spacers  
X
*Indicates only applicable for Finger Tab Duct Connector  
Figure 5. Duct Connector Selection (Non-Platinum)  
10  
Preparing Floor Opening(s)  
If "X"  
oor cavity is:  
Use Duct Connector  
Model Part Number  
1. Mark floor opening(s) as shown in Figure  
6. Provide minimum clearances at rear  
and right side walls of closet or alcove for  
installation of furnace and wiring.  
2. Cutooropeningonoutsideedgeofmarked  
line so that opening is slightly larger than  
area marked.  
3. Additional provisions may be necessary  
for optional air conditioning or heat pump  
if refrigerant lines are installed elsewhere  
than at the front of the furnace.  
4. Therefrigerantandentrancesupplyopening  
dimensions may be adjusted 1/2”.  
Metric  
(mm)  
Finger  
Tab  
Screw  
Down  
English  
7/8"  
2"  
22  
51  
901987  
901988  
901989  
901990  
901991  
901992  
901993  
904008  
904009  
904010  
904011  
904012  
904013  
904014  
4 1/4"  
6 1/4"  
8 1/4"  
10 1/4"  
12 1/4"  
108  
159  
210  
260  
311  
Table 4. Floor Cavity Sizes  
cases, use Method C or D.For screw down duct  
connector use method E. For Platinum models  
always use method A.  
Installing Duct Connector  
NOTE: The duct connector is designed for use  
on ducts down to 12” wide. On typical ducts,  
the finger tab duct connector may be installed  
using Method B.On narrow ducts, there may be  
insufficient clearance to bend the tabs on two  
sides of the finger tab duct connector. In such  
Method A - Platinum Series  
NOTE: Flex duct used must have a minimum  
temperature rating of 200° F and meet all  
other applicable codes and standards.  
1. Place duct connector through opening in  
floor. See Figure 9.  
2. Connect 14” supply duct.  
REAR WALL OF ENCLOSURE  
Center Line  
2-3/8" MIN  
(60 mm)  
Furnace  
Outline  
14-1/2"  
(368 mm)  
17"  
(432 mm)  
14-1/2"  
(368 mm)  
16-5/8"  
(422 mm)  
23-3/4"  
(603 mm)  
Optional Supply Wire  
Entrance  
A/C Or HP  
3" (76 mm)  
3-3/4"  
(95 mm)  
(Not required  
for Platinum)  
Optional  
Refrigerant  
Line  
3/4"  
(19 mm)  
4-1/4"  
5"  
3-3/8"  
(127 mm)  
10"  
(108 mm)  
(86 mm)  
6-1/4  
"
Furnace Outer  
Door  
(254 mm)  
(159 mm)  
20  
"
(508 mm)  
Figure 6. Downflow Floor Cutout Locations (nominal dimensions)  
11  
Rear Wall  
Mounting  
Plate  
Floor  
Opening  
Optional Supply  
Entrance  
Cut-out Area  
Refrigerant  
Line  
Opening  
Supply Air Duct  
Cut Duct Opening  
1/16th. Larger Than  
Plenum Connector  
Figure 7. Rear Mounting Plate  
Secure Duct Connector &  
Mtg Plate With 2 Flat Head Screws  
or Nails At Dimpled Locations  
Mounting  
Plate  
Rear Wall  
Plenum  
Bend Connector Tabs  
Under Duct Opening  
Refrigerant  
Line  
Opening  
Supply Air Duct  
Figure 8. Duct Connector (Non Platinum)  
Method B  
4. Secure duct connector to floor with two  
flat-head fasteners at dimpled locations  
(see Figure 8).  
5. Secureconnectortoductbybendingbottom  
tabs under and up against duct surfaces  
(see Figure 10).  
1. Placeductconnectorthroughooropening  
with bottom tabs resting on top of supply  
air duct. Mark cutout area around inside of  
tabs.  
2. Remove duct connector and cut out duct  
opening slightly larger than area marked.  
3. If using optional rear mounting plate (sup-  
plied with duct connector), install it to back  
edge of floor opening (see Figure 7). Re-  
install duct connector in floor opening. A  
shim may be used, if necessary, to ensure  
the furnace is level.  
Method C  
1. Attach tabs to sides of duct (one on each  
side) using sheet metal fasteners or other  
method, ensuringthattheductconnectoris  
secure and sealed to the duct (see Figure  
11).  
2. Seal the duct flap edges with an approved  
tape or compound for a leak-free joint.  
12  
Secure Duct Connector and Mounting  
Plate with 2 Flat-Head Screws or Nails  
Mounting Plate  
Duct  
Connector  
14" Supply Connection  
Figure 9. Platinum Duct Connector  
Method D  
5. Fold/form the duct flap against the side of  
1. Scoreandcuttopofmetalductasindicated  
in Figure 12, Step 1 or Step 2. If using Step  
1, also cut out metal from the shaded area  
“A”.  
2. Fold the duct flap “B” up (see Figure 12,  
Step 3).  
3. At the front-to-back of duct run (see Figure  
12, area “A”), bend the duct connector tabs  
and secure them directly to the duct.  
4. AtareaB”,bendtheductconnectortabsup  
and back over, around the duct connector  
(see Figure 12, step 3).  
the duct connector and attach as shown  
(see Figure 12, Step 4). Use at least three  
staples on each duct flap OR... if a 2X  
block/joist is not provided, use at least two  
sheet metal fasteners on each duct flap.  
6. Seal the duct flap edges with an approved  
tape or compound for a leak-free joint.  
Method E  
1. Apply a bead of caulking, mastic, or other  
approved sealant around bottom side of  
1/2” flange and restrictor plate, when ap-  
plicable.  
TABS  
DUCT  
TABS  
DUCT  
2. BEND BOTTOM TABS OVER  
AND ONTO THE UNDER-  
NEATH DUCT SURFACE  
1. INSERT DUCT CONNECTOR  
INTO DUCT CUT-OUT  
Figure 10. Duct Connector Installation B  
13  
2. Locate the duct connector over duct and  
carefully lower screw down duct connector  
into place.  
Alcove Installation  
1. Cut alcove rough openings to minimum  
dimensions shown in Figure 13.  
3. Once duct connector is located on duct,  
temporarily hold in place while fastening  
duct connector to the floor using flat head  
screws or nails. Be sure flanges of duct  
connector stay in contact with the duct.  
4. Screw duct connector to duct making sure  
a seal is made between the duct and the  
duct connector. Additional screws may be  
added if required.  
5. Cutawayductalongedgeofductconnector  
flange allowing the center to drop into the  
duct. Remove section of duct with caution,  
as edges will be sharp.  
2. Attach frame assembly with four fasteners  
(provided or equivalent) into pre-punched  
holes on top of furnace (see Figure 5).  
3. At manufacturers discretion, if additional  
securing is required attach each side of  
frame assembly to alcove opening using  
holes provided.  
4. Attach return air grille to frame assembly by  
hooking grille over flange on top of frame  
and into channel on bottom.  
Closet Installation  
NOTE: For closet installations, the return air  
grille mounting frame is not used since the  
furnace is located inside the closet (see Figure  
14 and 15).  
Duct Connector  
1. Cut return air opening in desired position  
in door or wall, preferably above top of fur-  
nace.Refer toTable 1 for return air opening  
requirements.  
2. Insert four fasteners, securing grille to door  
or wall.  
Narrow Duct  
Duct  
Furnace Installation  
1. Install 240V supply circuit(s) and 24V wir-  
ing to closet or alcove (see Figure 16 for  
appropriate locations).  
Figure 11. Alternate Duct  
Connector Installation C  
STEP 1.  
STEP 2.  
Fold Back Flap "B"  
Fold Back Flap"B"  
Cut  
Lines  
Duct  
Cut- Out  
Area "A"  
"B"  
Cut- Out  
Area"A"  
"B"  
"B"  
"A"  
"A"  
"B"  
Top of Duct  
Fold Back Flap"B"  
Fold Back Flap "B"  
STEP 4.  
STEP 3.  
Bend Duct Connector Tabs Up  
and Over- (along length of duct)  
Staple Folded Duct  
Flap (typ) to side of  
Duct Connector  
Duct  
Duct  
Flap "B"  
Duct  
Figure 12. Alternate Duct Connector Installation D  
14  
Holes (4)  
Wall  
Panel  
Return  
Air  
Grille  
Coil Air  
Filters  
27"  
(686 mm)  
56"  
(1423 mm)  
A/C or H/P  
Coil  
29"  
( 737 mm)  
Wall-Mount  
Return Air Grille  
24 3/4"  
(629 mm)  
Furnace  
Front  
Closet  
Door  
18"  
Nearest  
Wall or  
20"  
(508 mm)  
Floor  
Partition  
Figure 13. Typical Alcove Installation  
Figure 14. Typical Closet Installation  
2. Remove refrigerant line knockouts in fur-  
nace only when installing indoor coil of an  
air conditioner or heat pump system, or for  
hook-up of a VentilAire accessory when  
the furnace is used in the upflow position.  
Refertoinstructionssuppliedwithaccessory  
equipment.  
Provide min. 235  
sq. in. (1516 cm )  
open free area in  
front or side wall  
or in top of  
closet door  
3. Remove unit front door and slide back until  
bottomslotsinrearofunitengagewithboth  
tabs of optional rear mounting plate, OR...  
If mounting plate is not used, an equivalent  
method of securing the rear of the unit may  
beusedaslongasitpreventsdisplacement  
during transport if used in a manufactured  
home.  
0" Side  
Clearance  
to Furnace  
Cabinet  
CLOSET DOOR  
Standard Closet Installation  
NOTE: The furnace does not need to be hard  
up against the rear mounting plate.The tabs will  
engage into the slots and allow approximately  
1/2” of furnace adjustment front to back and  
right to left.  
Provide min. 250  
sq. in. (1613 cm2 )  
open free area in  
front or side wall  
or in top of  
closet door  
4. Secure front of unit with one or more fas-  
teners at mounting hole(s) provided or at  
tie-down tab (see Figure 16).  
5. See Electrical System Installation to com-  
plete furnace installation.  
0" Side  
Clearance  
to Furnace  
Cabinet  
CLOSET DOOR  
TYPICAL INSTALLATION OF  
UPFLOW SYSTEMS  
Thefollowingstepsdescribeinstallationinstruc-  
tions for an overhead supply duct system with a  
returnairsystemthatcanbeeitherovertheoor  
(unducted) or through the floor (ducted).  
Special 1" Clearance  
Figure 15. Closet Installation  
15  
Power  
Supply  
Wire  
Refrigerant  
Line  
Knockouts  
Entrances  
Power  
Supply  
Wire  
Entrances  
Blower Selector  
Switch (EH Only)  
Refrigerant  
Line Knockouts  
Tie Down Tab  
Blower Selector  
Switch (EH Only)  
Tie-Down Tab  
(See Inset)  
Low Voltage  
Wire Entrances  
DOWNFLOW INSTALLATION  
UPFLOW INSTALLATION  
Figure 16. Downflow and Upflow Installations  
NOTES:  
Return Air and Filtering Systems  
• Before installing this furnace, consider all  
clearances for the installation and future  
servicing of the furnace. Refer to Table 1.  
• The 2 Wire Relay Control is NOT recom-  
mended for upflow applications, instead, the  
AC/HPRelayControl(4-7wire)shouldbeused  
when converting some models to accept an  
airconditioner. SeeRelayControlinstallation  
instructions for further details.  
Furnaces may be installed with unducted or  
ducted return air. For unducted systems with  
air conditioners or heat pumps, the following  
optional equipment is recommended: upflow  
stand, coil cabinet, upflow duct connector, and  
wall mount grille. For ducted systems with air  
conditionersorheatpumps,thefollowingoptional  
equipment is recommended: coil cabinet and  
upflow duct connector.  
NOTE: Refer to the instructions supplied with  
any additional accessories for further installa-  
tion details.  
Upflow Duct  
Connector  
Filtering Methods - Non-Ducted Return Air  
1. Without optional upflow stand: (see Figure  
18)  
Furnace  
-install a filter with a minimum unrestricted  
medium area of 324 square inches below  
the coil cabinet/furnace assembly that is  
accessibleformonthlycleaningorreplace-  
ment by the homeowner  
Filter  
2. With optional upflow stand: (see Figure 17)  
Stand must use two filters; one is supplied  
with the stand and the other MUST be  
removed from the furnace and placed in  
the stand - see upflow stand instructions  
for additional details.  
(one obtained  
from furnace)  
Upflow Stand  
Filtering Methods - Ducted Return Air  
1. Install a filter with a minimum unrestricted  
medium area of 324 square inches below  
the coil cabinet/furnace assembly that is  
accessible for monthly cleaning or replace-  
ment by the homeowner  
Figure 17. Over-the-Floor Return Air Sys-  
tem with Upflow Stand  
16  
3. Install 240V supply circuit(s) and 24V wir-  
ing to closet (see Figure 16 for appropriate  
locations).  
4. Positionoptionalcoilcabinetoveroorcutout  
and secure with three or more fasteners.  
5. Positionfurnaceontocoilcabinetandsecure  
with two or more fasteners.  
6. Use optional upflow duct connector or field  
supplied connector to attach furnace to  
overhead supply duct (see Figure 17).  
Applications and Furnace  
Installation  
NOTE: Remove refrigerant line knockouts in  
furnace only when installing indoor coil of an  
air conditioning or heat pump system.  
Refer to instructions supplied with accessory  
equipment.  
Over-the-Floor Return Air System  
(Non-Ducted)  
ELECTRICAL SYSTEM  
INSTALLATION  
1. If floor underneath furnace is made of com-  
bustible material, locate a pan fabricated of  
non-combustible material with 1” upturned  
flangesunderfurnacereturnairopening(see  
Figure 18).  
2. Useoptionalupflowstandwithltersorcon-  
struct a suitably braced mounting platform  
in closet (see Figure 17 or 18).  
3. Install 240V supply circuit(s) and 24V wir-  
ing to closet (see Figure 16 for appropriate  
locations).  
4. Position optional coil cabinet onto upflow  
stand or mounting platform and secure with  
three or more fasteners.  
5. Positionfurnaceinupflowmodeontocoilcabi-  
net and secure with two or more fasteners.  
6. Use optional upflow duct connector or field  
supplied connector to attach furnace to  
overhead supply duct. (see Figure 17)  
7. Install return air grille in closet preferably  
at same level as upflow stand or below  
mounting platform (see Figure 18).  
WARNING:  
To avoid the risk of electrical shock,  
personal injury or death, disconnect  
all electrical power to the unit before  
performing any maintenance or  
service.The unit may have more than  
one electrical power supply.  
Codes, Specifications, and Re-  
quirements  
The wiring, installation, and electrical hookup  
of this furnace must comply with the National  
ElectricalCode(ortheCanadianElectricalCode)  
and all regulations of local authorities having  
jurisdiction.SeeTable9a&9bforminimumcircuit  
ampacity,maximumover-currentprotection,and  
recommended wire size. See the unit wiring  
diagram for other wiring details.  
NOTE: Be certain to provide an adequate free  
return air area as described under Return Air  
CodesandRequirementsandClosed-OffSpace  
Requirements.  
Supply-circuit requirements are as follows:  
Coil Cabinet  
Through-the-Floor Return Air System  
(Ducted)  
1. Prepare Floor Opening(s):  
Air Filter  
a. Markooropening(s)asshowninFigure  
19. Provide minimum clearances at rear  
andleftsidewallsofclosetforinstallation  
of furnace and wiring.  
Braced  
Mounting  
Platform  
WALL  
b. Cut floor opening on outside edge of  
marked line so that opening is slightly  
larger than area marked.  
Front  
Grille  
c. Additional provisions may be necessary  
for optional air conditioning if refrigerant  
lines are installed other than at the front  
of the furnace.  
FLOOR  
Non-combustible  
Pan or  
Enclosure  
2. If return air duct is made of combustible  
material, locate a pan fabricated of non-  
combustible material with 1” upturned  
flanges under furnace return air opening.  
Figure 18. Over-the-Floor Return Air  
System  
17  
REAR WALL OF ENCLOSURE  
CENTER LINE  
1 3/4" MIN  
(45 mm)  
17 1/2"  
(445 mm)  
Furnace  
Outline  
18 5/8"  
(474 mm)  
14"  
(356 mm)  
23 3/4"  
(604 mm)  
3 1/8"  
(80 mm)  
For Optional  
A/C Or H/P  
3/4"  
(20 mm)  
5 3/4"  
(147 mm)  
3"  
(73 mm)  
20"  
(508 mm)  
Furnace  
Outer Door  
Figure 19. Upflow Floor Cutout Locations (nominal dimensions)  
• -010 model is factory-wired for single-branch  
Connecting Supply Service Wires  
1. Remove right-hand control panel (when  
supply circuit only.  
• -012 models are factory-wired for single-  
branch supply circuit (single-circuit kit in-  
stalled). Dual-branch circuit can be used by  
removing factory-installed single-circuit kit  
(see Figures 20 and 21).  
• -015, -017, -020 and -023 models are  
factory-wired for dual-branch supply circuit.  
Single-branch circuit can be used by  
installing optional single-circuit kit .  
viewing in downflow position).  
2. Locate power supply hole plugs in side  
of unit and in bottom of unit. Remove  
appropriate plug(s) or knockout opening  
applicable to recommended wire size(s).  
3. Installlistedcableconnector(s)inopening(s).  
Ifmetal-sheathedconduitisusedforincom-  
ingpowerline(s),provideanapprovedmetal  
clamp on conduit and secure it in entrance  
knockout.  
4. Insert supply service wire(s) through cable  
connector(s) and connect wires to circuit  
breakers (Figures 20 and 21).  
IMPORTANT:  
Note:Circuitbreakersinstalledwithin  
this unit are for short-circuit  
protection of the internal wiring  
and to serve as a disconnect. Circuit  
breakers installed within this unit DO  
NOT provide over-current protection  
ofthesupplywiringandthereforemay  
be sized larger than the branch circuit  
protection.  
NOTE: To install single-circuit kit, perform  
step 5. If single-circuit kit installation is not  
necessary, go to step 6.  
5. To install single-circuit kit:  
a. Loosen lugs at supply side of circuit  
breakers.  
b. Remove cover from single-circuit kit (if  
supplied).  
c. Insert metal buss bars of kit into lugs of  
circuit breaker.  
d. Tightenlugssecurely(45in.-lbs.recom-  
mended).  
18  
6. Connectservicegroundwire(s)togrounding  
lug(s) provided. One ground is required for  
each supply circuit used.  
5. Installnewblowerensuringthesideanges  
engage under side mounting tabs (three on  
one side, one on the other) and the long tab  
in the rear.  
6. Replace screws previously removed from  
blower.  
7. Connect the motor plug to the control panel  
receptacle.  
8. Switch circuit breaker(s) to “ON”, reinstall  
furnace front door, and turn on electrical  
supply circuits to the furnace.  
WARNING:  
To avoid personal injury or property  
damage, make certain that the motor  
leads cannot come into contact with  
non-insulated metal components of  
the unit.  
Selecting Blower Speed  
See Table 5 for the lowest speed approved for  
the heating output of the unit. Since the blower  
leads connect to the control box, blower speed  
selection is accomplished through use of the  
proper color-coded blower lead located inside  
the control box. The speed(s) set by the factory  
may be different from that shown on the wiring  
diagrams. See the unit control box for blower  
speed(s) set at factory.  
Blower Installation:  
1. Turn off all electrical supply circuits to the  
furnace at the main service panel.  
2. Remove furnace front door and switch  
furnace circuit breaker(s) to “OFF”.  
3. Disconnect the motor plug from the control  
panel receptacle.  
4. Remove one screw from left side of blower  
and three screws from right side of blower;  
slide blower forward and remove.  
Circuit Breaker  
Bracket  
Optional  
Single Circuit  
Adaptor Kit  
Circuit  
Breaker  
Wire  
Assemblies  
(Factory  
Installed)  
Supply Service  
Wire Connection  
With Single Circuit  
Adaptor Kit  
Figure 20. Installation of Optional Single Circuit Adaptor Kit  
Circuit Breaker  
Bracket  
Circuit  
Breaker  
Wire  
Assemblies  
(Factory  
Installed)  
Supply Service  
Wire Connection  
Without Single  
Circuit Adaptor Kit  
Figure 21. Installation of Supply Service Wires  
19  
terminal 4 on blower relay and is the blue wire  
attached to the motor pin terminals 1-3.  
IMPORTANT:  
a. Remove heating and cooling leads from  
motor terminals 1-5.  
b. Choose desired speeds and seat terminal  
back into motor terminals 1-5.  
If a relay box is installed, blower  
speedsforheatingandcoolingareset  
inside the relay box (see instructions  
included with relay box). The blower  
speed inside the furnace control box  
must be set to low or medium-low.  
Neverchangetoaheatingspeedlower  
than that shown in Table 5.  
Same Speed, Heating and A/C: Use loose  
white jumper wire supplied with unit and jumper  
between terminals 5 & 2 on blower relay. On  
E3EX, remove one wire from motor terminals  
1-5, while leaving one wire on the required  
blower speed.  
Changing Blower Speed  
E3EH: The selected heating blower lead is at-  
tached to the wire lead attached to terminal 2  
of the blower selector switch.  
a. Remove blower lead from the wire lead off  
of terminal 2.  
b. Choose desired speed.  
c. Attach new blower lead to wire lead off  
terminal 2 of blower selector switch.  
See Table 6 for blower performance data.  
Installing Control Circuit Wiring  
NOTE: Installation of a five-wire thermostat  
circuit is recommended to provide for future  
addition of a heat/cool thermostat.  
1. Install the 24V control-circuit cable through  
plastic bushing at either side of furnace.  
a. For models without a relay box, connect  
wires to furnace at blower plug pigtails (see  
wiring diagrams). Secure all connections  
with wire nuts.  
E2EB: The selected heating blower lead is at-  
tachedtoterminal6onblowerrelay.Theselected  
cooling blower lead is attached to terminal 4 on  
blower relay.  
b. For units with a relay box installed, make  
wiring connections at relay box low-voltage  
terminal board. (See relay box installation  
instructions.)  
2. Route control circuit wiring to wall  
thermostat and outdoor section, if installed.  
(See relay box installation instructions if  
applicable.)  
a. Remove heating blower lead from terminal  
6 on blower relay.  
b. Choose desired speed and install new  
blower lead onto terminal 6 of blower relay  
for new heating speed.  
c. Remove cooling blower lead from terminal  
4 on blower relay.  
d. Install new blower lead onto terminal 4 of  
blower relay for new cooling speed.  
3. Set anticipator per Table 7 or per the mark-  
ing on the unit.  
4. See Figure 31 (non-Platinum) and Figure  
32 (Platinum) for E3EB thermostat connec-  
tions.  
E3EX: The selected heating blower lead is at-  
tached to terminal 6 on blower relay and is the  
red wire attached to the motor pin terminals 1-3.  
The selected cooling blower lead is attached to  
Plug/Receptacle Position  
2 Speed Blower  
Pin1  
Low  
Pin2  
Pin3  
Pin4  
-
Pin5  
High  
-
-
-
-
4 Speed Blower  
Low Med-LO Med-Hi  
High  
Black  
Control Box Blower Lead  
Red  
Yellow  
Blue  
Minimum approved speed  
for 010 and 012 models  
Minimum approved speed  
for 015, 017, 020, 023  
models  
Multi-Speed, E3EX  
Low  
Med-Lo  
Med  
Med-Hi High  
Table 5. Furnace Blower Speed Data  
20  
SYSTEM CHECKOUT  
Checking Installation  
Furnace  
Model  
Thermostat  
Anticipator Setting  
1. Refer to appropriate wiring diagram and  
recheckallwiringconnections. Ensurethat  
all connections are tight.  
010, 012  
0.2  
0.4  
015, 017, 020, 023  
2. Check blower motor and relay box con-  
nectors for proper connection.  
Table 7. Anticipator Settings  
3. Reinstall control box cover(s).  
4. Switch circuit breaker(s) to “ON” position.  
5. Set furnace blower selector switch (see  
Figure 16) to “AUTO” (EH Units only).  
6. Replace outer furnace door.  
ALL MODELS  
CLOSET ALCOVE  
Front **  
6"  
0"  
18"  
0"  
Back  
Sides  
0" *  
0"  
0" *  
0"  
7. Check all duct connections and tape for air  
leakage.  
Top  
Top and Sides of Duct  
0"  
0"  
Standard E3EH Blower  
with Filter, @ 0.3" ESP  
Bottom of Duct  
0"  
0"  
** Service Clearance  
*
For upflow application using upflow stand, 1” minimum per  
side.  
Pin No.  
#1  
Speed  
Low  
CFM  
840  
Table 8. Clearances  
#2  
High  
1160  
4-Ton Blower with Coil and  
Coil and Filters, @ 0.3" ESP  
Pin No.  
#1  
Speed  
Low  
CFM  
880  
#2  
Med.-Low  
Med.-High  
High  
1170  
1310  
1460  
#3  
#4  
5-Ton Blower, with Coil and  
Coil Filters, @ 0.3" ESP  
Pin No.  
#1  
Speed  
Low  
CFM  
990  
#2  
Med.-Low  
Med.-High  
High  
1320  
1620  
1790  
#3  
#4  
Multi-Speed, X13, Blower, with  
Coil and Filters, @ 0.3" ESP  
Pin No.  
#1  
Speed  
Low  
CFM  
880  
#2  
Med.-Low  
Med  
1000  
1170  
1260  
1460  
#3  
#4  
Med.-High  
High  
#5  
Table 6. Blower Performance  
21  
Copper Wire Size - See  
Caution Below  
Low  
Voltage  
Thermostat  
Wire Size  
Model  
Number  
E3E(*)  
Maximum  
Over-current  
Rating  
Minimum  
Circuit  
Ampacity  
Ground  
Wire  
Size  
Supply  
Circuit  
Total  
Amperes  
60°C  
90°C  
(e.g., Romex) (e.g., SEU)  
-010H  
-012H  
Single  
Single  
Dual "A"  
Dual "B"  
Single  
Dual "A"  
Dual "B"  
Single  
Dual "A"  
Dual "B"  
Single  
Dual "A"  
Dual "B"  
Single  
Dual "A"  
Dual "B"  
45.5  
52.1  
28.0  
24.2  
66.3  
45.5  
20.8  
71.3  
48.8  
22.5  
87.1  
45.5  
41.7  
93.8  
52.1  
41.7  
60  
70  
40  
30  
90  
60  
30  
90  
60  
30  
125  
60  
60  
125  
60  
60  
57  
65  
35  
30  
83  
56  
26  
89  
60  
28  
109  
57  
52  
117  
60  
56  
4
4
8
10  
2
4
10  
2
4
10  
0
4
4
0
4
4
6
6
8
10  
4
6
10  
4
6
10  
2
6
6
2
6
6
10  
8
10  
10  
8
10  
10  
8
10  
10  
6
10  
10  
6
10  
10  
2-Wire system  
maximum wire  
lengths:  
24 Ga.= 55'  
22 Ga.= 90'  
20 Ga.= 140'  
18 Ga.= 225'  
-015H  
-017H  
-020H  
-023H  
4 or more  
Wire systems  
maximum wire  
lengths:  
24 Ga.= 25'  
22 Ga.= 45'  
20 Ga.= 70'  
18 Ga= 110'  
Copper Wire Size - See  
Caution Below  
Low  
Voltage  
Thermostat  
Wire Size  
Model  
Number  
E3EX  
Maximum  
Over-current  
Rating  
Minimum  
Circuit  
Ampacity  
Ground  
Wire  
Size  
Supply  
Circuit  
Total  
Amperes  
60°C  
90°C  
(e.g., Romex) (e.g., SEU)  
-010  
-012  
Single  
Single  
Dual "A"  
Dual "B"  
Single  
47.7  
54.3  
30.2  
24.2  
66.0  
46.0  
60  
70  
40  
30  
90  
60  
57  
67  
35  
30  
83  
57  
4
4
8
10  
2
6
6
8
10  
4
10  
8
10  
10  
8
2-Wire system  
maximum wire  
lengths:  
24 Ga.= 55'  
22 Ga.= 90'  
20 Ga.= 140'  
18 Ga.= 225'  
Dual "A"  
4
6
10  
-015  
Dual "B"  
20.0  
30  
25  
10  
10  
10  
4 or more  
Wire systems  
maximum wire  
lengths:  
24 Ga.= 25'  
22 Ga.= 45'  
Single  
Dual "A"  
Dual "B"  
Single  
Dual "A"  
Dual "B"  
71.5  
51.0  
22.5  
86.0  
46.0  
40.0  
90  
60  
30  
125  
60  
60  
89  
60  
28  
109  
57  
50  
2
4
10  
0
4
4
6
10  
2
6
8
-017  
-020  
10  
10  
6
10  
10  
4
6
Replacement furnace for E2E(*)-015HB  
Single  
Dual "A"  
Dual "B"  
67.1  
35.5  
31.7  
90  
50  
40  
83  
44  
39  
2
6
8
4
8
8
8
10  
10  
Replacement  
furnace for  
E2E(*)-015HB  
E2E(*)-  
015HBR  
* Can be H or B  
CAUTION: When sizing the wire, you must follow the guidelines of the  
latest revision of the NEC. NM-B wire is equivalent to “Romex” cable. SEU  
is equivalent to service entry cable. For NEC type NM-B wire, you must  
size the wire using 60C ratings per NEC article 326.  
* MinimumovercurrentprotectionperNEC424-3bnottobelessthan125%  
of total amps for fixed resistance heat.  
Table 9a. Electrical Specifications  
Circuit "A"  
Circuit "B"  
Model Number  
E3E(*)  
Wire Gauge  
Breaker  
Size  
Wire Gauge  
Breaker  
Size  
and Type  
#8 NM-B  
#6 SEU  
#6 SEU  
#6 SEU  
#6 SEU  
and Type  
#10 NM-B  
#10 NM-B  
#10 NM-B  
#6 SEU  
-012H  
-015H  
-017H  
-020H  
40 amp  
60 amp  
60 amp  
60 amp  
60 amp  
30 amp  
30 amp  
30 amp  
60 amp  
60 amp  
-023H  
#6 SEU  
Replacement furnace for E2E(*)-015HB  
E2E(*)-015HBR #8 SEU  
50 amp  
#8 NM-B  
40 amp  
Table 9b. Recommended Electrical Application Guide  
for Dual Circuit Installations**  
** Alternate wiring combinations can be used. Refer to the latest revision of the NEC for these  
appropriate alternate combinations.  
22  
ON  
60A  
OFF  
O R A N G E  
R E D  
Y E L L O  
B L U E  
C K B L A  
W
R E D  
W
Y E L L O  
B L U E  
V I O L E T  
G R E Y  
C K B L A  
G R E E N  
Figure 26. E3EB 010H Wiring Diagrams  
23  
ON  
ON  
ON  
ON  
60A  
60A  
60A  
60A  
OFF  
OFF  
OFF  
OFF  
O R A N G E  
B L U E  
Y E L L O  
R E D  
W
R E D  
W
Y E L L O  
C K B L A  
B L U E  
V I O L E T  
G R E Y  
B L U E  
G R E Y  
Figure 27. E3EB 012H Wiring Diagrams  
24  
ON  
ON  
ON  
ON  
60A  
60A  
60A  
60A  
OFF  
OFF  
OFF  
OFF  
O R A N G E  
B L U E  
R E D  
W H I T E  
R E D  
Y E L L O  
K C B L A  
Y E L L O  
W
W
B L U E  
G R E Y  
V I O L E T  
K C B L A  
C K B L A  
G R E Y  
Figure 28. E3EB 015H, E3EB 017H Wiring Diagrams  
25  
ON  
ON  
ON  
ON  
60A  
60A  
60A  
60A  
OFF  
OFF  
OFF  
OFF  
C K B L A  
C K B L A  
O R A N G E  
R E D  
Y E L L O  
B L U E  
C K B L A  
R E D  
W
W
Y E L L O  
B L U E  
V I O L E T  
G R E Y  
C K B L A  
C K B L A  
G R E Y  
Figure 29. E3EB 020H, 023H, and 023H - 5 Ton, E2EB-015HBR Wiring Diagrams  
26  
Notes :  
1) See unit data label for recommended supply wire sizes.  
2) Thermostat anticipator setting : 0.40 Amps  
3) To change blower speed on units without a relay box installed refer to installation instructions  
4) Refer to furnace and/or relay box installation instructions for thermostat connections.  
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.  
6) Not suitable for use on systems exceeding 120V to ground.  
7) Refer to Installation Instructions for complete wiring diagram.  
8) Heating and cooling may be wired on the same speed using the provided jumper wire.  
GREEN  
RED  
GREEN  
T1  
G
C
T2  
T3  
T4  
N
L
X13  
1
3
5
2
RED  
BLOWER  
RELAY  
1
4
2
5
3
6
BLUE  
T5  
6
4
BLACK  
WHITE  
1
4
2
5
3
6
ORANGE  
FUSE  
ORANGE  
WHITE  
BLUE  
VIOLET  
RED  
GRAY  
WHITE  
BLACK  
24V  
240V COM  
BLACK  
RED  
RED  
RED  
CONTACTOR  
"A" (BOTTOM)  
BLACK  
RED  
RED  
BLACK  
ELEMENTS  
LIMIT  
BLACK  
BLACK  
Figure 30. E3EX 010H  
Notes :  
1) See unit data label for recommended supply wire sizes.  
2) Thermostat anticipator setting : 0.40 Amps  
3) To change blower speed on units without a relay box installed refer to installation instructions  
4) Refer to furnace and/or relay box installation instructions for thermostat connections.  
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.  
6) Not suitable for use on systems exceeding 120V to ground.  
7) Refer to Installation Instructions for complete wiring diagram.  
8) Heating and cooling may be wired on the same speed using the provided jumper wire.  
GREEN  
GREEN  
T1  
G
C
T2  
T3  
T4  
N
L
RED  
X13  
1
3
5
2
RED  
BLOWER  
RELAY  
4
1
4
2
5
3
6
BLUE  
T5  
6
BLACK  
WHITE  
1
4
2
5
3
6
ORANGE  
ORANGE  
WHITE  
BLUE  
VIOLET  
RED  
BLACK  
FUSE  
GRAY  
WHITE  
24V  
RED  
"B" (TOP)  
240V COM  
BLACK  
RED  
CONTACTOR  
RED  
BLACK  
BLACK  
RED  
RED  
"A" (BOTTOM)  
ELEMENTS  
LIMIT  
BLACK  
BLACK  
Figure 31. E3EX 012H  
27  
Notes :  
1) See unit data label for recommended supply wire sizes.  
2) Thermostat anticipator setting : 0.40 Amps  
3) To change blower speed on units without a relay box installed refer to installation instructions  
4) Refer to furnace and/or relay box installation instructions for thermostat connections.  
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.  
6) Not suitable for use on systems exceeding 120V to ground.  
7) Refer to Installation Instructions for complete wiring diagram.  
8) Heating and cooling may be wired on the same speed using the provided jumper wire.  
GREEN  
GREEN  
T1  
1
5
2
G
(11)  
T2  
T3  
T4  
RED  
BLOWER  
RELAY  
1
4
2
5
3
6
N
L
RED  
X13  
3
6
4
BLACK  
BLUE  
C
T5  
WHITE  
ORANGE  
1
4
2
5
3
6
BLUE  
VIOLET  
RED  
ORANGE  
WHITE  
FUSE  
GREY  
BLACK  
WHITE  
24V  
RED  
"B" (TOP)  
240V  
COM  
BLACK  
RED  
RED  
"A" (BOTTOM)  
RED  
CONTACTOR  
BLACK  
RED  
BLACK  
RED  
ELEMENTS  
LIMIT  
WHITE  
WHITE  
BLACK  
RED  
ELEMENTS  
LIMIT  
BLACK  
BLACK  
BLACK  
Figure 32. E3EX 015/017H  
Notes :  
1) See unit data label for recommended supply wire sizes.  
2) Thermostat anticipator setting : 0.40 Amps  
3) To change blower speed on units without a relay box installed refer to installation instructions  
4) Refer to furnace and/or relay box installation instructions for thermostat connections.  
5) If any wire in this unit is to be replaced it must be replaced with 105° C thermoplastic copper wire of the same gauge.  
6) Not suitable for use on systems exceeding 120V to ground.  
7) Refer to Installation Instructions for complete wiring diagram.  
8) Heating and cooling may be wired on the same speed using the provided jumper wire.  
GREEN  
GREEN  
T1  
1
3
5
2
G
(11)  
T2  
T3  
T4  
RED  
BLOWER  
RELAY  
1
4
2
5
3
6
N
L
RED  
X13  
6
4
BLACK  
BLUE  
C
T5  
WHITE  
ORANGE  
1
4
2
5
3
6
BLUE  
VIOLET  
RED  
ORANGE  
WHITE  
FUSE  
GRAY  
BLACK  
WHITE  
24V  
RED  
RED  
"B" (TOP)  
240V  
COM  
BLACK  
RED  
RED  
RED  
"A" (BOTTOM)  
CONTACTOR  
BLACK  
RED  
BLACK  
RED  
ELEMENTS  
LIMIT  
WHITE  
WHITE  
BLACK  
BLACK  
RED  
RED  
ELEMENTS  
LIMIT  
BLACK  
BLACK  
BLACK  
BLACK  
Figure 33. E3EX 020H  
28  
5-WireThermostat  
RC RH  
4-WireThermostat  
W
Y
R
G
W
Y
G
Wire  
nuts  
Wire  
nuts  
To A/C  
To A/C  
n
Gree  
E3EB FURNACE Control Wiring  
E3EB FURNACE Control Wiring  
Heat Pump Thermostat  
2-WireThermostat  
W
R
G
R
W2  
C
E
O
Y
Unstripped  
Wires  
Wire  
nuts  
To  
H/P  
Wire  
nuts  
E3EB FURNACE Control Wiring  
E3EB FURNACE Control Wiring  
Figure 34. E3EB Thermostat Connection  
Wire from furnace to Platinum unit  
Typical AC  
PLATINUM  
Black  
Green  
White  
Red  
Yellow or Blue  
FURNACE  
Grey  
White  
Red  
Red and white  
t-stat wire  
connected by  
OEM  
Yellow  
Green  
Yellow or Blue  
White  
Y
W G R  
Green  
Red  
THERMOSTAT  
Wire from thermostat  
to furnace  
Platinum installer  
disconnects  
Typical HP  
Wire from furnace to  
Platinum unit  
white and red  
t-stat wires  
Green  
White  
PLATINUM  
Grey or Green  
White  
Orange or Red  
Yellow  
Red  
Yellow or Blue  
FURNACE  
Grey  
White  
Red  
Green  
Yellow or Blue  
White  
Green  
Y
W G  
R
THERMOSTAT  
Red  
Wire from thermostat  
to furnace  
Figure 35. E3 Furnace Low Voltage Wiring if Installed with Platinum Series Models  
29  
Furnace Inspection Report  
Please Write In Appropriate  
Response  
Electrical Wiring (If single circuit, write “N/A” in circuit B)  
Breaker Size?  
Circuit A Circuit B  
Furnace Wire Size?  
Thermostat Wire Size?  
Please Circle Appropriate  
Response  
Electrical  
Is the furnace grounded properly?  
Is wiring routed safely with approved connectors?  
Yes  
Yes  
No  
No  
N/A  
N/A  
Closet Installation  
Is front clearance a minimum of 6 inches?  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Is return air opening a minimum of 235 sq. inches?  
Is front clearance less than 6 inches (minimum of 1 inch)?  
Is return air opening a minimum of 250 sq. inches?  
Does the furnace have the 5-ton AC coil installed?  
Is the return air opening a minimum of 390 sq inches?  
Plenum (Base) Connector  
Is mounting plate secured properly?  
Is furnace locked and secured in front?  
Is plenum free of debris?  
Yes  
Yes  
Yes  
No  
No  
No  
N/A  
N/A  
N/A  
Has plenum opening been reduced in size to accommodate  
offset?  
Has plenum spacer been removed if duct size is large enough?  
Yes  
Yes  
No  
No  
N/A  
N/A  
Testing  
Is someone in the plant trained to perform duct tests?  
Yes  
No  
N/A  
VentilAire III __ IV__  
Is VentilAire duct connected properly to furnace?  
Is depressurization vent (if required) installed properly?  
Is roof assembly installed properly?  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
N/A  
N/A  
N/A  
N/A  
Is roof assembly a minimum of 3 inches from any other vents?  
General  
Is lter in place?  
Is owner’s packet included?  
Yes  
Yes  
No  
No  
N/A  
N/A  
Checked storage area for damage to product and proper  
storage?  
Is installation in accordance with installation instructions?  
Yes  
Yes  
No  
No  
N/A  
N/A  
Comments:  
30  
31  
INSTALLER: Do Not Discard These Instructions  
After completing the installation, return these instructions  
to the Homeowner’s Package for owner-user’s future reference.  
Complies with H.U.D. Manufactured Home Construction & Safety Standards.  
¢708827H¤  
7088270  
7088270  
Specifications and illustrations subject to change  
without notice and without incurring obligations.  
Printed in U.S.A. (07/08)  
O’Fallon, MO  

Schumacher 5216a Pe User Manual
Samsung Sh12zpga User Manual
Quantum Lc 5500 User Manual
Panasonic Cw 1773sr User Manual
Lanier Ldd030 User Manual
KENWOOD JE570 User Manual
DELL S2721HSX User Manual
CRAFTSMAN 919.174212 User Manual
CRAFTSMAN 315.CRS1000 User Manual
BROTHER HL L2380DW User Manual