Xantrex Technology Marine Instruments LINK 10 User Manual

i4.25  
Link 10  
Owner's Manual  
Xantrex  
Link 10  
Battery Monitor  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
DO NOT INSTALL OR USE THIS PRODUCT UNTIL YOU HAVE READ THE ENTIRE  
OWNER’S MANUAL. IMPROPER INSTALLATION OF THIS UNIT MAY BE HAZARD-  
OUS AND VOIDS YOUR WARRANTY.  
Quick Reference Guide..................................................................................................5–6  
Introduction.........................................................................................................................7  
Battery Basics.....................................................................................................................8  
Installation......................................................................................................................9–15  
Startup................................................................................................................................16  
Synchronizing the Link 10................................................................................................17  
Operation......................................................................................................................18–24  
Setting Battery Capacity....................................................................................................21  
Temperature Sensor (optional)...........................................................................................25  
Setting Peukert's Exponent...............................................................................................26  
Low Battery Alarm.................................................................................................27, 35–38  
Reset and Lock...................................................................................................................28  
Historical Data...................................................................................................................29  
Advanced Functions.....................................................................................................30–34  
Peukert’s Equation.......................................................................................................39–42  
Troubleshooting.................................................................................................................43  
Options and Versions.........................................................................................................44  
High Voltage Prescaler (optional)......................................................................................45  
Electric Vehicles...........................................................................................................46–47  
Lift Truck Installations......................................................................................................48  
Serial Port, RS-232 (optional)............................................................................................49  
High Voltage Notes............................................................................................................50  
CE Declaration of Conformity..........................................................................................51  
Limited Warranty..........................................................................................................52–54  
Index...................................................................................................................................58  
Specifications.....................................................................................................................59  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Basic Wiring Diagram  
+
-
+
-
The 500 A 50 mV  
shuntsensescurrent  
in or out of your  
battery.  
The Xantrex Link 10  
works with flooded or  
gel lead-acid batteries  
2 amp  
Fuses  
Twisted pair wire is used for shunt  
sensing leads for noise immunity.  
Battery Compartment  
Meter Location  
Top Rear View of Meter  
-DC Meter Negative (BLACK) [1]  
Shunt Sense Lead Load Side (GREEN) [2]  
Shunt Sense Lead Battery Side (ORANGE) [3]  
Battery Volt Sense (0–50 V DC1) (BLUE) [4]  
+DC Meter Power (9.5–40 V DC) (RED) [5]  
Optional Temperature Sensor Input [6]  
Optional Low Battery Alarm [7]  
4
Optional Temperature Sensor Ground [8]  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference  
The Light Bar  
The light bar shows state-of-charge at a glance.  
Here's what the lights mean:  
FULL  
EMPTY  
Full  
80–99%+  
60–79%+  
40–59%+  
20–39%+  
0–19%+  
Status Lights  
For shortest charging times,  
lead acid battery in marine or  
RV service is normally dis-  
charged 50% then recharged  
to 85–90% of full. Restoring  
thelast10–15%of afullcharge  
requiresalongtime—typically  
2–3 hours. This means only  
35–40% of your battery ca-  
pacity is actually available  
for normal use. Occasionally  
discharging a battery more  
deeply is perfectly acceptable.  
Shows what number is  
being displayed  
The Button  
When you press the  
button, you  
SELect a numeric display. In normal  
operation, each press illuminates a sta-  
tus light. The light indicates volts are  
being displayed, the  
light indicates  
amps, indicates amp hours, and  
indicates time. We’ll explain these terms  
on the next page.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quick Reference  
Amps  
Amp hours  
Amp hours consumed  
represents the amount  
of energy removed  
from the battery. If you  
run a 10-amp load for  
one hour, the Link 10  
will show -10.0 in the  
display.  
Amps is the present flow  
of current in or out of your  
battery. For example, a re-  
frigerator may draw 6.2  
amps of current. This is  
displayed as -06.2 (6.2  
amps are being con-  
sumed).  
Volts  
Volts is electricity’s poten-  
tial to do work. Voltage  
helps assess approximate  
state-of-charge and to  
check for proper charging.  
A 12 V battery is consid-  
ered 100% discharged  
whenitdropsbelow10.5 V.  
Time  
Time is an estimate of  
how long your battery  
will sustain a load. A  
Time display of 3.7  
hours means you have  
approximately 3 hours  
42 minutes of operating  
time remaining.  
Advanced Functions  
Press and hold the  
SET button for 3 sec-  
ondstoentertheSetup  
and Advanced Func-  
tions mode. SEL  
appearsinthedisplay.  
Setup Features  
Key Advanced Functions  
Advanced  
Functions:  
Customizes the  
Link 10's functions.  
For details read  
pages 29–30 and  
pages 34–37.  
Locks front  
panel.  
Shows charging  
efficiency and  
historical data.  
F01 Scanning  
F02 Sleep Mode  
F09 Discharge Floor  
F15 S/WVersion  
F17 Test Lights  
Resets amp hours (AH) or  
(ALL) defaults.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
Congratulations! The Xantrex Link 10 is the most advanced (Patents  
Pending) DC power measurement instrument available. It shows you:  
Battery State-of-Charge on a multicolor light bar.  
System voltage accurate to 1/20th of a volt (<20 VDC).  
System current accurate to 1/10th of an amp (<40 amps).  
Amp hours removed from, or put into, your battery.  
Time of operation remaining until recharging is required.  
For installation and operation questions, please contact Xantrex at 1-800-  
670-0707 (toll free) or 1-604-422-2777 (direct). You can also email Xantrex  
at [email protected]. For warranty and technical support  
please follow the process outlined on page 52.  
If you wish the Link 10 to support an external Low Battery Alarm, such as  
a bell or buzzer, or if you need the Link 10 to report data to a computer or  
data logging unit, these options must be included at the time of manufac-  
ture and cannot be retrofitted in the field.  
The installation of the Link 10 is simple, as is its operation. However, there  
are many advanced features and functions, so please take the time to read  
and thoroughly understand this manual.  
Installer's Note: This manual contains operating  
instructions. Please leave it with the meter!  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Basics  
Why monitor a battery?  
Batteries can be ruined by excessive discharge. They may also be dam-  
aged by under-charging. A battery (or bank of batteries) may be storing  
less energy than you think. The Link 10 provides all the key data you, or  
your technician, need to make decisions about battery use and charging.  
How does the Link 10 work?  
The Link 10 uses sophisticated microprocessor technology to report all  
significant battery information. The Link 10 monitors battery voltage and  
current over time to report amp hours consumed and time remaining—  
precisely the information necessary to maximize system performance.  
What's an amp hour?  
Batteries are rated by amp hour capacity. A battery that delivers one amp  
for one hour has delivered one amp hour. Marine and RV deep-cycle bat-  
tery capacity is based on their 20-hour discharge rate. A battery that delivers  
10 amps to a load for 20 hours before battery voltage drops to 10.5 volts,  
is considered a "200 amp hour" battery. 10 amps times 20 hours equals 200  
amp hours (200 Ah).  
For maximum life you should never discharge more than half the rated  
capacity of a battery. Therefore, if you have a 200 amp hour battery, you  
should recharge when the Link 10 shows -100 in the amp hour display. The  
-100 means 100 amp hours have been removed from your battery.  
FOR MAXIMUM BATTERY LIFE, RECHARGE YOUR  
BATTERIES WHEN YOU HAVE DISCHARGED 50%  
OF THEIR AMP HOUR CAPACITY.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Basic installation of the Link 10 on a 12 or 24 volt system involves only  
five wires. Because the Link 10 will work on systems up to 500 volts,  
special high voltage installation techniques are discussed beginning on page  
44. You need to read this section if you're working on an electric vehicle or  
system where more than 50 volts is encountered. If your installation is on  
a 12 or 24 volt system, let's get to work!  
Installation Planning  
First, gather all the tools you'll need for installation. We recommend:  
* A 2" or 2 1/16" (52 mm) hole saw to make the panel cutout.  
* A 3/8" drill with bits to run power and shunt wiring.  
* An adjustable 9/16" wrench for shunt bolt connections.  
* Wire stripper/crimper and a small flat blade screwdriver.  
Make sure you have all the parts you'll need to complete the job:  
* A 500 A–50 mV shunt (included)  
* #18 or #16 twisted pair shunt wire long enough to reach  
from the battery to the meter location. Ask your dealer for  
Xantrex Technology PN 84-2014-00 - 25' 4 twisted pair cable  
or PN 84-2015-00 - 50' 4 twisted pair cable (not included).  
* 2 in-line fuse holders with 2-amp fuses.  
CAUTION: DO NOT INSTALL FUSES UNTIL YOU  
COMPLETE INSTRUCTIONS ON PAGES 10–15.  
* A short heavy-duty battery cable to run from one shunt bolt  
to the battery. Cable is available at auto and marine shops.  
* Assorted small-gauge crimp type terminals for connecting  
the power, shunt, fuses, and voltage sense leads.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mounting  
Our Patent Pending "Ratchet Ring" makes mounting easy and fast.  
TIP: When installing from the front of a  
panel or dashboard slide the Ratchet Ring  
onto cable with correct orientation  
and then connnect  
the wires.  
CAUTION!  
Orient ring so the ratchet  
teethwillengageproperly.  
Practice installing and re-  
moving ring before final  
assembly. Considerable  
force is required—this  
ensures the ring will not  
loosen over time.  
Install the meter from the front of your  
panel. Thepanelthicknessmayrangefrom  
1/16" to 1 1/2". Slip the locking ring on  
from the rear and press forward until its  
teeth hold the meter securely in place.  
Push Ratchet Ring on  
until firmly in contact  
with panel.  
The gasket around the ring  
of the Link 10 should pro-  
vide an adequate seal  
against moisture. If a sealant  
is used be sure it is silicone  
so that the Link 10 may be  
removed without damage.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removing  
Removing the Link 10 is the reverse of mounting with a  
TWIST as shown in the following diagrams.  
Twist 1/8th turn to  
unlock teeth.  
Then pull lock ring  
straight back as shown  
below.  
Pull both  
sides of  
the lock  
ring equally  
Patented  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring Overview  
This drawing is for 12 V & 24 V systems.  
For higher voltages see Prescaler use on page 44.  
DC+  
+
Fuses  
-
Shunt  
DC-  
(system ground)  
Twisted pair cable  
See Detail page 13  
Terminal Strip  
Connections  
See Detail page 14  
INSTALLATION TIP:  
Use appropriate strain relief to  
avoid damage to the connector  
and terminal strip on the rear of  
the Link 10.  
Mounting Page 10  
Removing page 11  
TIP: For a neat and professional looking installation use plenty of:  
* Nylon wire wraps  
* Wire wrap anchor points.  
NOTE: To limit Voltage measurement error do not exceed wire lengths shown  
below. Error assumes 16 AWG wire and max. power consumption.  
0.5% Error 72 Feet Maximum  
1.0% Error 150 Feet Maximum  
3.0% Error 450 Feet Maximum  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Shunt & Battery Wires  
The shunt is the current sensor for the Link 10. Its 500 A, 50 mV rating  
means that when 500 amps flows through it there is 50 mV generated  
across it. The millivolt signal is translated into an amps display in the Link  
10. For example: a 50 A load would generate 5 mV across the shunt and  
would be displayed as 50 amps. Caution: in the diagram below, the darker  
wires represent primary wiring and should be able to carry full battery  
load current. Size appropriately!  
+
-
Connect NO  
other wires di-  
rectly to battery  
negative! All  
current must  
flowthroughthe  
shunt!  
500 A 50 mV  
BATTERY  
SIDE  
SHUNT  
LOAD  
SIDE  
BLACK  
These wires ORANGE  
must be a  
twisted pair!!  
RED  
GREEN  
BLUE  
2 amp Fuses  
(mount within 7"  
of battery)  
4 Twisted pair  
cable. See page 14  
for part numbers.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Meter Wiring Detail  
Make the necessary wire connections to the Link 10 as  
shown in the following diagram:  
Color code shown for  
Xantrex 4 twisted pair  
cable. P/Ns below:  
P/N 84-2014-00 -25'  
P/N 84-2015-00 -50'  
CAUTION  
Use correct sized screwdriver for  
terminal screws. Tighten firmly  
but do not over-tighten to avoid  
damage  
Top Rear View  
DC - Meter Negative (BLACK) [1]  
Shunt Sense Lead Load Side (GREEN) [2]  
Shunt Sense Lead Battery Side (ORANGE) [3]  
Battery Volt Sense (0–50 V DC1)(BLUE) [4]  
DC + Meter Power (9.5–40 V DC) (RED) [5]  
Optional Temperature Sensor Input [6]  
Optional Low Battery Alarm [7]  
Optional Temperature Sensor Ground [8]  
1) For Voltages above 50 V a Prescaler must be used. See page 44.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wire by Wire Check  
Most failures and problems are due to wiring errors. Please double check  
the wiring. (Color code shown is for Xantrex wire P/Ns on page 14.)  
#1 - DC Power (Black Wire). Start at terminal #1 of the Link 10 and  
follow it to the big bolt on the Load side of the shunt. Do not connect this  
wire to the small screw terminal with the Green shunt sense lead.  
#2 Shunt Sense Lead Load Side (Green Wire). This wire connects to  
the small screw on the Load side of the shunt. This wire must be a  
twisted pair with the Orange wire described below. To check this wire  
start at terminal #2 and follow it to the small screw on the Load side of  
the shunt. There should be no other wires connected to this screw.  
NOTE: Also check the primary wiring from the shunt to the battery.  
There should be only one heavy cable from the Battery side of the shunt to  
the battery. All loads and sources must be connected on the other side of  
the shunt. Only the shunt may be connected directly to battery negative!  
#3 Battery Side of Shunt (Orange Wire). This wire must be a twisted  
pair with the Green wire described above. To check this wire start at  
terminal #3 and follow it to the small screw on the Battery side of the  
shunt. There should be no other wires connected to this screw.  
#4 Voltage Sense Wire (Bat.+) (Blue Wire). From terminal #4 this wire  
should run to a 2 amp fuse holder, located within 7" of the battery. The  
other side of the fuse holder should go to the positive (+) battery post.  
If Voltage is greater than 50 V, see High Voltage Prescaler, page 44.  
#5 + DC Power (Red Wire). This wire should run from terminal #5 to a  
2 amp fuse holder located within 7" of the battery. The fuse should not  
yet be installed. The other side of the fuse holder goes to the battery. If  
power supply voltage is above 24 V, see the Electric Vehicles section,  
page 46.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Startup  
Once you have completed ALL instructions on page 15, insert the voltage  
sense wire fuse, then the meter power fuse. (BLUE wire fuse first, RED  
wire fuse last!) The fuse should be in a fuse holder and should be con-  
nected in a smooth motion. A "ragged" power-up may cause a meter lockup.  
Both the bar graph and digital display should come on.  
Factory Default Settings  
The Link 10 comes on in the  
(Volts) mode with the display flashing to  
indicate that it has been powered up from the de-powered state (see page  
26). Left untouched for 10 minutes, the Link 10 will go to "sleep," turning  
off the digital display leaving only the bar graph on. (This is a power-  
saving feature.) Touching either the SEL or SET buttons will return the  
Link 10 to the function the Link 10 was in when it went to "sleep."  
The Link 10 is designed to work "out of the box." The factory default  
values are appropriate for a moderate capacity 12 V liquid lead acid bat-  
tery and a typical user display and function setup. Often the only change  
that must be made is setting the battery capacity. You may also have to  
set the appropriate Peukert's exponent for your battery (see page 26).  
Special functions and display options are described beginning on page 27.  
The Link 10's Factory Default Settings Are:  
1. Automatic Scanning of V, A, amp hours, and time will be OFF.  
2. Sleep Mode is ON. Turns digital display off after 10 minutes.  
3. Charge Efficiency Factor (CEF) equals 90% and learn CEF mode is on.  
4. Charged Parameters: Voltage =13.2, Charged Current =2%. The  
battery must exceed 13.2 V and the current must be less, in amps,  
than 2% of declared capacity for five minutes for the Link 10 to consider  
the battery full.  
5. Battery capacity set to 200 amp hours.  
6. Peukert Exponent = 1.25.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Synchronizing the Link 10  
Synchronize the Link 10 to a Full Battery  
After installing the Link 10, charge the battery until the far right Green  
LED begins flashing, which indicates the Charged Parameters have been  
met. Amp hours will have started at 0 and counted up as a positive num-  
ber. As you begin discharging the battery, the LED will stop flashing and  
the numeric amp hour display resets to 0. The Link 10 is shipped from the  
factory assuming a 200 amp hour battery. Your battery may be a different  
size. To change battery size, see page 21.  
StayinginSync,RemovingAccumulatedNegativeAmpHours  
Should the Link 10 ever become out of sync with the battery state-of-  
charge simply charge until the far right LED flashes Green. You may also  
get back in sync by charging until the battery is full and then resetting the  
amp hours to zero through the RESET function.  
If the Link 10 should accumulate a negative number in the amp hour dis-  
play you will have to charge until you meet the conditions for a recalculation  
of the Charging Efficiency (CEF) as described on pages 22 & 23. If you do  
not meet all five of the conditions listed below you will not get a recalcu-  
lation of the CEF and a reset to zero amp hours consumed.  
CONDITIONS TO RESET TO ZERO  
1) Discharge 10% of declared battery capacity to trigger algorithm.  
2) Recharge until 100% of the kWh removed have been returned.  
3) The voltage must be above the Charged Voltage Parameter.  
4) The current must be below the Charge Current Parameter.  
5) Conditions 3 & 4 must be met for 5 minutes (1 min. for AE default)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation  
Although the Link 10 is a very sophisticated device, obtaining basic battery  
information from it is simple. With the unit turned on and the (Volts) LED on,  
let's learn how to display the four most important DC system parameters.  
When you touch the  
button, you  
are SELecting the display you wish.  
Each time you touch SEL in normal  
operation, you will toggle to the next  
i4.25  
item to the right  
(volts) goes to  
(amps) to (amp hours) to (time).  
Now press SEL to bring up these functions.  
Volts is the electric potential to do work. Voltage is useful to assess the  
approximate state-of-charge and to check for proper charging. Examples:  
An at-rest, fully charged battery will show about 12.8 V. A 12 V battery  
is 100% discharged when it reaches 10.5 volts with a 20-hour rated load  
applied. A typical charging voltage would be 14.2 V.  
Amps is the present flow of current in or out of the battery. For example,  
a refrigerator may draw 6 amps of current. This is displayed as - 6.0 (6  
amps are being consumed). Discharge is shown as a negative number and  
charging is shown as a positive number (unsigned).  
Amp hours consumed represents the amount of energy removed from  
the battery. If you run a 10-amp load for one hour then ten amp hours are  
consumed. The Link 10 will show -I0 in the display. During charging  
the Link 10 will compensate for charging efficiency and count back up  
toward 0.  
Time is an estimate of how long (in hours) the battery will sustain a load.  
It is based on a selectable, time averaged, rate of discharge. Default is the  
average of the last four minutes of use (see page 24).  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reading the Bar Graph  
Above the digital display are four LEDs. They tell you the battery's state-  
of-charge at a glance. Four green LEDs means your battery is full. One  
flashing red light means it is nearly discharged. The table below shows the  
six different displays indicating battery state-of-charge. Under certain light  
conditions green may appear yellow.  
EMPTY FULL  
BATTERY STATE-OF-CHARGE  
Full (Charged Parameters Met)  
80–99%+  
60–79%+  
40–59%+  
20–39%+  
0–19%+  
Under the LED bar graph are the words RESET, DATA, LOCK, and  
FUNC. These words are ignored during normal operation. They are used  
to indicate programming and advanced function modes which are explained  
beginning on page 28.  
Setting Battery Capacity is Important  
The LED bar graph display shows how much of your battery has been con-  
sumed. If you do not set your battery capacity correctly, your bar graph will not  
give you an accurate indication of battery state-of-charge. The Link 10 also  
uses declared capacity to calculate the Time Remaining, the charged current for  
Charge Efficiency Factor calculations, and other control functions.  
Setting capacity correctly is very important—see page 21  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Using the Buttons  
Pressing and holding the SET button for three seconds enters the Setup and  
AdvancedFunctionsmode.ThewordSELapppearsinthedisplay,promptingyou  
to press the SEL button to choose what function you want to SELect.  
Pressing SELchooses a variable or function. The SETUP mode always begins  
atthe  
(Volts)function. EachpressoftheSELbuttonscrollstothenextitem.  
When a variable or function is selected, its LED is on and its present value is  
displayed. To change an item press the SET button until the value appears that  
you wish. The order displayed and brief descriptions are below.  
LIGHT  
DESCRIPTION  
Charged Voltage (the voltage above which the battery must rise to be full)  
ChargedCurrent% (chargingcurrentmustbebelowthispercentagetimes  
the battery capacity to be considered full. See page 22–23)  
Battery Capacity in amp hours  
Time interval over which current is averaged for time remaining function.  
Each LED is lit in sequence to indicate function.  
Advanced Functions. See page 30.  
Locks out SET button & Advanced Functions. See  
page 28.  
Displays: CEF, # CEF Recalcs, Average Depth of  
Discharge, Deepest Discharge, Average Rate of  
Discharge. See page 29.  
Resets A-hrs & allows Reset to Factory values. See  
page 28.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setting Battery Capacity  
The first time you use the Link 10, itassumes you have 200 amp-hour lead acid  
batteries. If your battery capacity is different you must change the declared  
battery capacity. Follow these instructions to declare a new capacity:  
1) Press and hold the SET button for three seconds to enter SETUP (and  
Advanced Functions) menu. SEL appears in the display. Press SEL and notice  
that the green  
LED is on.  
2) Press SELagain and note that the  
light comes on. Press again and now  
LED is on and 200 appears in the display. This is the default battery  
the  
capacity.  
3) Now press and hold the SET button to scroll through battery size options.  
The display will show 1 amp-hour increments from 20–40 amp hours of capac-  
ity, 5 amp-hour steps from 40–100 amp hours capacity and 20 amp-hour steps  
over 100 amp hours of capacity. If you continue to hold SET, after four incre-  
ments the display scrolls faster. When the value you want appears, release the  
SET button. If you overshoot your capacity you will have to scroll all the way  
to 1980 amp hours, after which the display will roll over and begin scrolling up  
starting from 10 amp hours. NOTE: Versions of the Link 10 prior to serial  
number 05000 increment only in 20 amp-hour steps from 20–1980 amp hours.  
4) After 10 seconds the meter exits the Setup mode and the selected value is  
stored as the new battery capacity and the display returns to  
(Volts).  
TIP: All SETUP and ADVANCED FUNCTIONS begin with the SET button.  
SETUP is normally done at installation. The SET button may be LOCKed to  
prevent unauthorized personnel from tampering with the SET functions. See  
"LOCK" on page 28.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Charged Parameters  
The Link 10 depends on the Charged Parameters to stay in sync with the  
battery state-of-charge, to automatically reset to zero, and to automatically  
calculate the CEF. The default settings are for 12 V lead acid (liquid or  
gelled) batteries. They have been carefully chosen to work on most  
systems, including constant voltage and multiple step charging systems.  
The factory Charged Parameters are 13.2 volts and 2% of battery capacity  
as a charged current. (2% of the default battery capacity of 200 Ah equals  
4 amps). Several conditions must be met for a recalculation of the CEF and  
a reset to zero: First 100% of the energy removed from the battery must be  
returned, additionally the battery must be above 13.2 volts and the current  
must fall below 4 amps for five minutes. When all these conditions are met  
the battery is considered full.  
CAUTION:Ifyourbatteryvoltageisotherthan12VyouMUSTsetup  
an appropriate Charged Voltage.  
If the charged parameters are not set correctly,  
The Link 10 will never recalculate the CEF!  
Pleaseconsiderchangingonlythebatterycapacityunlessyoursystemfalls  
into one of the following categories:  
1) Battery chemistry other than lead acid.  
12VoltNiCad(andNiFe)systemswouldnormallyuse15.5to15.7as the  
ChargedVoltage.Seeyourbatteryspecificationsforguidance.TheCharged  
Current % can probably stay at 2% of declared battery capacity.  
2) Charging normally ends before current drops below 2%.  
If the charging system is normally shut down before charging current  
drops below 2%, the Charged Current % will have to be changed.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Charged Parameters & CEF  
If you change the Charged Parameters please use the following rules:  
1) The Charged Voltage Parameter MUST BE AT LEAST 0.1V  
BELOW thevoltageatwhichthechargingsystemfinishescharging.  
Example: If your charging system finishes the battery at 13.8 volts, a  
Charged Voltage Parameter of 14.0 volts will not work. Lower the  
Charged Voltage Parameter to 13.7 volts or less.  
2) The ChargedCurrent%timesdeclaredBatteryCapacity MUST  
be GREATER than the minimum current at which the charging  
system maintains the battery, or turns off.  
If the Charged Current % times the Battery Capacity is less than the  
current at which the charging system switches off, the Charged  
CurrentParametercannotbemet. Forexample, ifthechargingsystem  
shuts off when the current is 10 amps, using the factory default value of  
4 amps (2% of 200 Ah), will not work. Changing the Charged Current  
%to6%wouldgiveaChargedCurrentof12amps,whichwouldwork.  
WHYTHECHARGEEFFICIENCYFACTOR(CEF)ISIMPORTANT:  
The CEF determines the rate at which the meter counts back up during  
charging to compensate for the inefficiency of the charging process. The  
CEF has a factory default value of 90%. This means that you must return  
10.0 amp hours to store 9.0 Ah in the battery.  
If you have a charging system that cannot satisfy the Charged Parameters,  
the CEF will not be recalculated and the meter will use the default CEF of  
90%. Thiswillworkfineinmostsystems. Youmaynoticeanaccumulation  
of negative amp hours. If so, set up appropriate Charged Parameters or  
resynchronizeperiodically.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setting Up  
Five different displays are available in the Time function. You may select  
present consumption level, a 4-minute average, a 16-minute, or a 32-minute  
average, or display the percent of rate compensated capacity remaining.  
Which method is best for you depends on your installation. Most installations  
will find four-minute averaging appropriate. To SET UP  
follow the  
procedure outlined on page 20. As you press the SET button the following  
values will appear. Use the table below to choose the appropriate averag-  
ing period.  
Instantaneous:  
4-Minute Average:  
Time Remaining Setup Display: 000  
Time Remaining Setup Display: 00I  
16-Minute Average: Time Remaining Setup Display: 002  
32-Minute Average: Time Remaining Setup Display: 003  
Percent Remaining: Time Remaining Setup Display: 04P  
Operating Tips: Use the longest period of time you can to ensure long-term load  
variations are considered. For instant feedback, use the 000 (no averaging) dis-  
play. Time is in hours and 1/10ths of hours. In the Percent of Capacity Remaining  
mode, a full battery is displayed as 100P and counts down as your discharge. The  
Percent of Battery Capacity Remaining is referenced to the selected discharge  
floor and uses the instantaneous (not averaged) rate of discharge. The percent of  
capacity remaining display shows the percent number which drives the Bar  
Graph. This function is very useful on electric vehicles.  
CAUTION: Time displays are an estimate of how long your battery will  
sustain a load (to your selected discharge floor; default: 100% discharge).  
Variations in discharge current, incorrectly set battery capacity, Peukert's  
exponent, temperature, and prior battery history may affect the accuracy of  
this estimate. Please use Time displays only as a guide. Use all displays  
(volts, amps, amp hours, and time) to make an informed decision about  
battery state-of-charge. Do not rely on a single value!  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(optional)  
Temperature Sensor  
The Link 10 may support an optional two wire temperature sensor. The  
temperature sensor is activated by turning Advanced Function F16 ON.  
With F16 ON, F03 shows battery temperature in degrees Celsius. When  
activated, F03 will continue to display temperature after exiting the Setup  
mode until one of the two front panel buttons, SET or SEL, is pressed.  
The limits of the temperature sensor are 0 °C (32 °F) to 99 °C (210 °F).  
Versions of the Link 10 prior to Serial Number 005000 do not support this  
function.  
Introduction to Peukert Exponent  
The Link 10 shows true amp hours consumed in the amp hour display.  
However, the light bar shows how much of the available battery has been  
consumed. In 1897 a scientist named Peukert demonstrated that as you  
discharge a battery more quickly, its effective size temporarily decreases.  
A battery is considered fully discharged when it is no longer able to main-  
tain 10.5 volts under load. As you'll see in the following table showing the  
effect on a typical liquid cell battery, the faster the discharge rate, the  
smaller its effective capacity:  
Hours to Discharge  
Capacity as percent of 20 hr rating  
20  
10  
5
2
1
100%  
84%  
67%  
56%  
47%  
In other words, a 100 amp-hour battery, discharged completely in one hour  
will only supply 47 amp hours before dropping below 10.5 V!  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Puekert's Exponent  
Peukert's Exponent is a number which describes how battery capacity  
shrinks as the rate of discharge is increased. The Link 10 uses a number  
between 1.00 and 1.50 to describe how fast a particular battery will "shrink"  
when a heavy load is connected. A more complete technical discussion of  
the Peukert Exponent, and typical value tables is included on pages 39–41.  
The Peukert Exponent set at the factory, 1.25, will be satisfactory for  
many liquid cell batteries. Gel cell batteries, or liquid cells with atypical  
plate structures, may require a different Peukert Exponent. To change the  
Peukert Exponent, proceed as follows:  
1) Press and hold the SET button for three seconds to enter SETUP  
(and Advanced Functions) menu. SEL appears in the display. Press SEL  
and notice that the green  
LED is on.  
2) Press SEL again and note that the  
light comes on. Continue to  
press the SEL button until F8 appears in the display. This will require 18  
presses of the SEL button. The FUNC LED will be lit.  
3) Now press and hold the SET button. The default value of 1.25 (or the  
previously programed value) will appear in the display. The range of values  
is from 1.0 to 1.50. Holding down the SET button will cause the display to  
increment in 0.01 steps, after four increments the display scrolls faster.  
When the value you want appears, release the SET button. If you over-  
shoot your capacity you will have to scroll all the way to 1.50 after which  
the display will roll over to 1.00 and continue incrementing. You also have  
to scroll all the way through to declare exponents between 1.00 and 1.25.  
4) After 10 seconds the meter exits the Setup mode and the selected  
value is stored as the new Peukert's exponent and the display returns to  
(Volts).  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarms  
Two Types of Alarms  
The Link 10 is equipped with both a visual Power Loss Alarm and a visual  
Low Battery Alarm. It is important that you understand the difference  
between these functions.  
Power Loss Alarm: Shows when power being supplied to the Link 10 has  
dropped to an unsafe level. Certain display features are turned off as meter  
power drops below internally set levels.  
Low Battery Alarm: Shows when the battery being monitored has reached  
either a predetermined depth of discharge or has encountered at least 15  
seconds of continuous low voltage below a settable level. The Low Bat-  
tery Alarm is controlled by functions F10, F11 and F12 in the Advanced  
Functions Section.  
Power Loss Alarm & Reset Annunciation  
If the voltage-supplying terminal #5 falls too low an automatic shutdown  
occurs. This voltage varies from a low of 7.2 V to about 9.2 volts depending  
on how fast the voltage drops. When power is restored, the display defaults  
to the  
function and the digital display flashes. Pressing either the SEL  
or SET buttons cancels the flashing display. If the meter is in the sleep  
mode when power loss occurs, the display will flash for 10 minutes and  
then go to sleep if no buttons are pressed. Once asleep, the first button  
press will wake the display in the flashing mode to annunciate the power  
loss. The second button press will cancel the flashing display.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Reset and Lock  
In addition to reporting primary system values, the Link 10 is capable of  
many other front panel functions and will also display important historical  
battery data. The words below the bar graph display indicate which of  
these functions you are accessing. To use these functions you must read  
and understand the following section of this manual.  
Resetting the Link 10  
RESET  
DATA  
LOCK  
FUNC  
RESET Resets amp hours to zero and resets the Link 10 to factory values.  
To RESET the amp-hour display to zero, SELect the RESET function as  
previously described. The letters AH will appear in the display. Press and  
hold the SET button. After five seconds the amp-hour display will be reset  
to zero and the letters ALL will appear. If you continue to hold down the  
SET for another five seconds all variables and functions are reset to the  
factory defaults.  
Front Panel Locking  
FUNC  
RESET  
DATA  
LOCK  
LOCK Prevents user access to Set Up and Advanced Functions.  
To LOCKthe Link 10,SELecttheLOCKfunctionaspreviouslydescribed.  
The letters LOC will appear in the display, indicating you are in the LOCK  
function. Press SET and the letters off appear, indicating the front panel  
is not locked. Press SET again and the letters on will appear, indicating the  
front panel is locked. Repeating this procedure toggles the lock off and on.  
The display will report off or on, indicating Lock off or on.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Historical Data  
Key Battery Data Displayed  
RESET  
DATA  
LOCK  
FUNC  
DATA Key historical battery information is available through this function.  
Each time the SEL button is pressed while in the DATA mode the next  
piece of data is displayed. To see DATA, select DATA as previously  
described.  
CEF (Displayed as E99): The Charging Efficiency Factor (CEF) is  
displayed. A display of E99 indicates a 99% CEF. This number sets the  
rate at which amp hours are counted back up during charging. This is an  
amp-hour CEF, not kWh efficiency. The Default setting is 90%. NOTE: If  
the CEF display has a u in front of it, this means the CEF has been  
selected by the user. See Advanced Function F06 for details.  
#CEF Recalculations (Displayed as +I999): This is the number of times  
that the battery has been discharged more than 10% and then recharged  
until the Charged Parameters have been met. May be considered as the  
number of charge/discharge cycles the battery has experienced.  
Deepest Discharge (Displayed as -i999): Shows the deepest discharge  
in amp hours recorded by the meter since its last RESET to factory  
defaults.  
Average Discharge (Displayed as i999): The running average of all  
discharges as an amp-hour value since last RESET to factory defaults.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advanced Functions  
Advanced Functions  
RESET  
DATA  
LOCK  
FUNC  
FUNC Allows setup of Advanced Functions.  
To access the FUNC mode, SELect the FUNC mode as previously de-  
scribed. The letters F0i will appear in the display and the FUNC LED will  
be lit, indicating you are in the FUNC mode. Continue pressing the SEL  
button until the function you wish to set up appears. Now press SET until  
the desired value or mode appears. Repeat this procedure until you have set  
up all of the desired advanced functions. Whatever functions you have set  
up will become active when the display reverts to its normal mode.  
F01 AUTODISPLAYSCANNING  
Automatically scans V, A, Ah, and T. Each value is displayed for four  
seconds. DEFAULT: OFF RANGE: OFF or ON  
F02 ENHANCED SLEEP MODES  
DEFAULT: ON  
RANGE: ON, OFF, AU (AUTOMATIC)  
When the Sleep Mode is ON, the Link 10's numeric display turns off  
after 10 minutes in order to reduce power consumption. Pressing either  
SET or SEL buttons returns the numeric display to operation.  
When the Sleep Mode is OFF, the numeric display stays on at all times.  
Inthespecialautomaticsleepmode(displayedasAu),thenumericsare  
on whenever charging or discharging exceeds 1 amp. When the rate of  
chargeordischargeremainslessthan1ampfor10minutes,thenumeric  
display is turned off to conserve power. When asleep, pressing either  
SET or SEL reactivates the numeric display. The numeric display  
automatically wakes up when the rate of charge or discharge exceeds  
1 amp. The Automatic Sleep Mode is ideal for electric vehicles.  
DEFAULT: ON  
RANGE: OFF or ON  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advanced Functions  
F03 DISPLAYORSETBATTERYTEMPERATURE  
If there is no external temp sensor and F16 is OFF (factory default),  
this function sets ambient battery temperature used to caluculate rate  
corrected battery capacity which drives the LED bar graph and the  
Time remaining display. Feature not available on units with serial  
numbers prior to 05000.  
DEFAULT: 20 °C  
RANGE: 0–40 °C  
STEP: 1 °C  
If F16 is ON and an optional external temperature sensor is connected  
between Pin 6 and Pin 8 (ground), F03 will display temperature  
(0–99 °C). Temperature will continue to be displayed until one of the  
two front panel buttons is pressed. Active Temperature display is  
annunciated by the absence of front panel status indicators. If 0 is  
displayed at normal (~ 20 °C) temperatures, an open temperature  
probe should be assumed. If >99 is displayed at normal temperatures,  
a shorted probe should be suspected.  
F04 TURNONKWHRSDISPLAY  
KilowatthoursaredisplayedintheAhmode. (Note:ThekWhdisplay  
does not take into account Charging Efficiency. As a condition for a  
recalculation of the CEF and an automatic reset of amp hours to zero,  
100% of the energy removed from the battery must be returned. The  
number in the kWh display must be zero or positive to allow a  
recalculation of the CEF and an automatic reset to zero. You may use  
this function to verify that this condition has been met.)  
DEFAULT: OFF RANGE: OFF or ON  
F05 USEALTERNATIVEENERGY(AE)DEFAULTS  
Changes time to meet Charged Parameters to one minute from the  
normalfiveminutes. (AlsoconsiderchangingChargedCurrentto4%.)  
DEFAULT: OFF RANGE: OFF or ON  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advanced Functions  
F06 MANUALLY SET CEF (Not Recommended)  
Allows manual setup of CEF. Displayed as two digits. Default display  
A90 indicates automatic CEF recalculation feature active. Returning  
to A90 from a user CEF turns the automatic CEF feature back on. A  
user-set CEF will appear as a UXX in the DATA mode. See page 29.  
DEFAULT:A90  
RANGE: 65–99  
STEP: 1  
F07 SETTEMPERATURECOEFFICIENT  
Compensates for capacity change with temp. ~ 0.5% Cap/°C. This  
coefficient must be supplied by the battery manufacturer. The default  
value is typical for lead acid liquid or gelled batteries.  
DEFAULT: 0.5  
RANGE: 0.1–0.9  
STEP:0.1  
F08 SETPEUKERTEXPONENT  
Sets exponent for Peukert’s equation. A setting of 1.0 defeats Peukert's  
calculation. See pages 39–42 for a discussion of Peukert's equation and  
typical values for various batteries.  
F09 SETDISCHARGEFLOOR  
Sets the discharge floor used to calculate bar graph status and time of  
operation remaining functions. The factory default is to calculate time  
remaining, and bar graph based on a rate-corrected discharge of 100%  
of declared amp-hour capacity. In other words, the bar graph will flash  
red when less than 20% of your rate-corrected (Peukert amp hour)  
capacity remains. Default time remaining is essentially "time till  
dead battery."  
To ensure a margin of safety you may wish to set a different discharge  
floor. You may wish to set 80% or some other discharge floor for your  
bar graph.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advanced Functions  
CAUTION: If you set the discharge floor high, such as 50%, and  
continue to discharge well beyond this point, you will notice that the  
bar graph does not "fill up" until you have charged the battery above  
the discharge floor. In other words, if you set the discharge floor at  
50% and discharge 75%, you must recharge back up to the 50% level  
before your bar graph and time of operation will again give you  
meaningfulinformation.  
DEFAULT: 100%  
RANGE: 50–100%  
Step: 5%  
F10–F12 SEE LOW BATTERY ALARM, PAGES 35–38  
F13 SEEHIGHVOLTAGENOTES,PAGE50  
F14 ENABLELOWBATTERYALARM  
In versions of the Link 10 equipped with the Low Alarm Switch, this  
function allows the Low Battery Alarm to be disabled.  
DEFAULT: OFF  
RANGE: ON, OFF  
F15 SOFTWARE REVISION  
Displays revision of software.  
Please note that the software enhancements to the Link 10 may not be  
retrofitted into earlier versions of this product. If the Link 10 has serial  
number 005000 or larger, it will come with software version E1.3 or  
greater installed. Earlier versions of the Link 10 do not support  
temperature sensing, small amp-hour increments, separate alarms for  
meter power and low battery conditions. Early versions display 255  
instead of CCC when the battery is being charged.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Advanced Functions  
F16 TEMPERATURESENSORON/OFF  
This function turns the optional external temperature sensor on or off.  
This feature is only operable when a temperature sensor has been  
connected between Pin 6 and Pin 8 of the Link 10.  
To fully understand this feature, please refer to F03 on page 31. Not  
available prior to Serial Number 005000.  
DEFAULT: OFF RANGE: ON, OFF  
F17 LIGHTTEST  
This function confirms proper operation of the Link 10's front panel  
display. When the SET button is pressed in the F17 mode, the two top  
left lights on the Light Bar will display orange/yellow color, the  
numericdisplaywillread188.8andallfourstatuslightswillbeon.The  
display returns to normal when the SET button is released. Operation  
of the two top-right green lights on the Light Bar is confirmed when  
power is initially applied to the Link 10.  
DEFAULT: OFF RANGE: ON only while F17 is active.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Low Battery Alarm  
Units with serial numbers greater than 005000 allow access to an enhanced  
Low Battery Alarm feature. To activate this feature, change Function F14  
to ON. When F14 is ON, the Link 10 displays a visual alarm when the  
monitored battery meets either of two conditions:  
1) A settable rated compensated (Peukert) amp-hour depth of  
discharge is exceeded or,  
2) Voltage remains below a settable level for 15 seconds or longer.  
When operating the Link 10 with the visual Low Battery Alarm function  
ON, three additional software functions are active. Two of these functions,  
F11 and F12, set the low amp-hours and low voltage levels which turn the  
visual alarm ON. Function F10 is the Low Battery Alarm OFF (Recharge)  
Set Point.  
Visual Alarm Indication  
There are two levels of visual alarm.  
Level 1: The normal display alternates with a blank Bar Graph and LO  
appears in the numeric display.  
Level 2: Once the Level 1 alarm display is acknowledged by the operator  
by pressing either SET or SEL once, the Level 2 Alarm flashes the amp-  
hours function light while dimming the presently displayed function light.  
In the event amp hours are displayed, the amp-hours light will go off at  
half-second intervals. Once the battery alarm feature is activated, a visual  
alarm display (Level 1 or Level 2) will continue until amp hours are above  
the Low Battery Alarm OFF (Recharge) Set Point (F10) and voltage is  
above the Low Voltage Alarm Threshold F12 for at least 15 seconds.  
Alarm Circuit  
Special versions of the Link 10 close a circuit to ground when either Visual  
Alarm level is active. This circuit may be used for audible alarms, generator  
staring, and so forth. Because additional internal circuitry is included, this  
option may not be retrofitted to the Link 10 in the field.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm Functions  
Refer to F14 in the Owner's Manual  
Functions F10, F11, and F12 define operation of the Visual Low Battery  
Alarm as follows:  
F11  
F10  
TURNS ON Low Battery  
Alarm at a set % of rate-  
compensated amp hours  
discharged  
TURNS OFF Low  
Battery Alarm when  
amp hours are restored  
0% Discharged  
ALARM OFF  
Settable Range  
10% Discharged  
Amp-Hour  
Capacity of  
Battery  
ALARM ON  
Settable Range  
70% Discharged  
E.G. 100 Ah  
80% Discharged  
F10 LOWBATTERYALARM OFF (RECHARGE)SETPOINT  
Once the Low Battery Alarm is activated, recharging the battery to  
this point turns the alarm OFF. This recharged point must always be at  
least 10% higher than Low Battery Line closure point.  
DEFAULT: 70% RANGE: 0%–70%  
STEP: 5%  
F11 LOW BATTERY ALARM ON SET POINT  
Sets when the Low Battery Alarm goes ON point based on percent of  
amp hours discharged. F11 is displayed as a percentage: i.e. 10 is 10%  
discharged. F11 may set anywhere in its range but at least 10% below  
the F10 Low Battery Alarm OFF Set Point set point.  
DEFAULT: 80% RANGE: 10%–80%  
STEP: 5%  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE:TheLowBatteryAlarmONandOFFpointsoperate  
on rate compensated (Peukert) amp hours consumed. Once the  
alarm is activated, the battery must be charged until Alarm OFF Set  
Point is reached to turn the alarm off.  
F12 LOWVOLTAGEALARMTHRESHOLD  
F12 sets the voltage below which the Low Battery Alarm is activated.  
But the voltage must remain below this set point for a full 15 seconds  
before the Low Battery Alarm goes ON. Dropping below the Low  
Voltage Alarm Threshold for less than a full 15 seconds will not  
activate the alarm.  
IflowvoltageactivatesthealarmwhilethebatteryisabovetheAlarm  
OFF (amp hour) Set Point, the alarm goes OFF as soon as voltage  
remains above the low voltage threshold for 15 seconds. If the battery  
is below the Alarm OFF (amp hour) Set Point when low voltages  
turn the Alarm ON, the alarm stays on until the battery is recharged to  
above the Alarm OFF (amp hour) Set Point.  
RANGE: 5.0–40 V (0–50 V Scaling) STEP: 0.1 V Default 10.5 V  
RANGE: 5.0–80 V (0–100 V Scaling) STEP: 0.1 V Default 10.5 V  
RANGE: 50–400 V (0–500 V Scaling) STEP: 1.0 V Default 105 V  
THINGS TO REMEMBER:  
1) The Low Battery Alarm may be activated by either a low Voltage OR  
a low amp-hour condition.  
2) There must be a 10% difference between the Low Battery Alarm ON  
set point and Low Battery Alarm OFF (Recharge) Set Point.  
3) Because Low Battery Alarm ON may be triggered by rated compen-  
sated (Peukert) amp hours, you may see fewer amp hours removed in  
the numeric display than expected. The more rapidly you have  
discharged your battery, the more pronounced this variance will be.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Alarm Switch  
Special versions of the Link 10 are available, for additional charge, which  
include a solid state Alarm Switch to ground via rear panel terminal strip  
Pin #7. This option is used in a variety of settings such as lift pump lock out  
on fork lifts, two wire generator start/stop, audible low battery alarms, and  
charge controllers. The additional circuitry of the switch may not be retrofitted  
to the Link 10 in the field. It must be included at the time of manufacture.  
The Low Battery Alarm Switch goes low to meter ground when the alarm  
is activated. In other words, a sinking FET switch to the meter's negative  
power lead is completed while the alarm is active. This lead is protected  
against polarity reversal so the "switch" connection has about 1 ohm of  
resistance. This should be taken into account when sizing relays or  
designing logic interfaces. The maximum amount of current that may be  
controlled by this circuit is 150 mA (0.150 A) at no more than 50 V. Below  
are two typical applications for the optional Low Battery Alarm Switch:  
RELAY DRIVER DIAGRAM  
AUDIBLE ALARM  
+ DC Alarm Power.  
Negative must be common  
to the Link 10.  
Controlled Circuit  
RELAY COIL  
12 V or 24 V  
Piezo alarm  
<150 mA.  
To Pin 7, the Link 10  
rear panel term. strip.  
>
+ -  
Alarm Defeat  
Switch On-Off  
+ DC Relay Power (<50 V). Nega-  
>
tive must be common to the Link 10.  
To Pin #7  
The Link 10  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Peukert's Equation  
Peukert's Equation describes the effect of different discharge rates on battery  
capacity. As the discharge rate increases, the available battery capacity  
decreases. The table and examples on the following page illustrate this  
effect and how to use the table to estimate the exponent "n". The tables on  
pages 40 and 41 have typical values of "n" for common batteries.  
Making two discharge tests, one at a high discharge rate and one at a low  
rate, that bracket your normal range of operation, allows you to calculate  
an "n" that will describe this varying effect. The Link 10 uses an "n" equal  
to 1.25, which is typical for many batteries.  
At some low to moderate discharge rate, typically a battery's 20-hour rate,  
the logrithmic effect of Peukert's Equation is greatly reduced. The effect  
of discharge rates smaller than this is nearly linear. Battery manufacturer  
specifications of battery capacity in amp hours is typically given at the 20-  
hour rate. From this description, if a battery is discharged at this rate for  
the period of time called out, you will be able to remove the rated capacity.  
The equation for Peukert's Capacity (C ) is:  
p
log t2 - log t1  
n
n =  
C = I t where  
p
log I1 - log I2  
By doing two discharge tests and knowing I1 & I2 (discharge current in  
amps of the two tests), and t1 & t2 (time in hours for the two tests) you can  
calculate n (the Peukert coefficient). You will need a calculator that has a  
Log function to solve the equation above. See example on page 42. After  
you solve for your Peukert's coefficient you may enter it using Advanced  
Function F8.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Peukert's Equation  
The table below may be used to understand the effect of high rates of  
discharge on available battery capacity. It may also be used to estimate the  
exponent "n" for a battery after a single discharge test. The table is based  
on a 100-Ah battery but may be used for any capacity battery by using an  
appropriately scaled current. See the examples below:  
PERCENTAGE OF AVAILABLE CAPACITY FROM A  
100 Ah BATTERY AT DIFFERENT DISCHARGE RATES  
USING DIFFERENT PEUKERT'S EXPONENTS  
DISCHARGE RATE IN AMPS  
n
1
5 10 16.7 25 50 75 100 150 200 250 300 400 500  
100 100 100 100 100 100 100 100 100 100 100 100 100  
1.1 100 93 88 85 79 76 74 71 69 67 66 64 63  
1.2 100 87 78 72 63 58 55 51 48 46 44 42 40  
1.25 100 84 74 67 56 51 47 42 40 37 36 33 32  
1.3 100 81 69 62 50 44 41 36 33 31 30 27 25  
1.4 100 76 61 52 40 34 30 26 23 21 20 17 16  
1.5 100 71 55 45 32 26 22 18 16 14 13 11 10  
Example #1: Suppose you have a 200 Ah Example #2: A 100 Ah battery  
battery. Now discharge at a 50-amp with a Peukert's exponent of 1.3  
rate until the battery reaches 1.75 V will deliver only 41% of its  
per cell (10.5 V for a 12 V battery). capacity when supplying a 100-  
This would be equivalent to a discharge amp load.  
rate of 25 A for a 100 Ah battery. If the  
battery delivered 67% (134 Ah) the  
appropriate Peukert's exponent would  
be 1.25.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Peukert's Exponent  
Typical Values for Peukert's Exponent "n"  
This table contains values for the exponent "n" for various batteries and  
manufacturers. They are calculated from the 20-hour rating and the  
Reserve Minutes @ 25 A as supplied by the manufacturer. They should be  
considered only a guide for selecting "n."  
Prevailer & SeaGel Batteries  
Model Volts Res. Min. 20-Hr. rating "n"  
8GGC  
8GU1  
8GU24  
8GU27  
8GU30H 12  
84D  
6
375  
43  
180  
43  
70  
86  
95  
1.14  
1.20  
1.13  
1.12  
1.12  
1.11  
1.10  
12  
12  
12  
130  
167  
188  
388  
500  
12  
12  
180  
225  
8G8D  
Trojan Batteries  
Model Volts Res. Min. 20-Hr. rating "n"  
T-105  
T-125  
T-145  
J250  
J305  
L16  
24TM  
27TM  
30XHS  
SCS225  
EV8D  
6
6
6
6
6
6
12  
12  
12  
12  
12  
447  
488  
530  
535  
660  
760  
135  
160  
225  
225  
450  
225  
235  
244  
250  
305  
350  
85  
105  
130  
130  
216  
1.24  
1.19  
1.14  
1.17  
1.21  
1.28  
1.23  
1.28  
1.27  
1.27  
Peukert's Equati1o.17n  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Peukert's Exponent  
Surrette and Rolls Batteries  
Model Volts Res. Min. 20-Hr. rating "n"  
EHG-208 6  
345  
350  
395  
165  
190  
230  
348  
450  
208  
225  
262  
90  
112  
108  
170  
221  
1.42  
1.54*  
1.72*  
1.16  
1.23  
1.08  
1.15  
1.20  
EIG-225  
EIG-262  
24/90  
6
6
12  
12  
12  
12  
12  
27/12M  
30H/108  
HT/4D  
HT/8D  
*Use Max allowed "n" of 1.50  
Example of using Reserve Minutes @ 25 amps  
and the 20-hour rate to calculate "n".  
First convert Reserve Minutes to hours, then find the discharge current at  
for the 20-hour rating. Finally, use a calculator to solve the arithmetic.  
Trojan T-105:  
Reserve Minutes = 447 min @ 25 amps.  
t1 = 447 min = 447/60 = 7.45 hrs  
I1 = 25 amps  
20-hour rating = 225 Ah  
t2 = 20 hours  
I1 = 225 amp hours/20 hours = 11.25 amps  
log t2 - log t1  
log 20 - log 7.45  
1.301 - 0.872  
=
n =  
= 1.24  
=
log I1 - log I2  
log 25 - log 11.25  
1.398 - 1.051  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Problem  
No lights or display  
Suggestion  
Check Power Connections  
Reset meter (page 28)  
No keyboard response  
Check Lock is not invoked  
Reset meter (page 28)  
Time Remaining Not  
Accurate  
Check Battery Capacity (page 21)  
Check Temperature Coefficient (page 32)  
Check Peukert Exponent (page 26)  
Clean front panel photo-sensor  
(Between A and Ah lights)  
Digital Display Dim  
Current Polarity Reversed Current Shunt leads reversed (page 13)  
Intermittent Operation  
Corrosion or loose wires. Loosen and  
reconnect all rear panel connections.  
Check voltage sense and shunt wiring  
at battery location.  
Accumulates Negative  
Amp-hour reading  
Charge Parameters not met. Check  
Charged Parameter values—has 100% of  
kWh been returned? Charging Current is  
not passing through shunt (pages 13, 22,  
23, and Function F04).  
Xantrex Technology, Inc. warrants that the Link 10 will measure voltage,  
amperage, and amp hours within the published specifications. The Time  
Remaining and LED bar graph functions are complicated and require  
appropriate user setup and are therefore beyond the control of Xantrex  
and are not covered by warranty. Similarly, installation wiring and specific  
applications are beyond our control and are not covered by warranty.  
See page 52.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Options & Versions  
User-installable OPTIONS available include:  
Prescalers: Extend the voltage range covered by the Link 10  
to either 0–100 V (Xantrex P/N 84-6000-0) or  
0–500 V (Xantrex P/N 84-6000-05).  
Temperature Sensor: Reports battery temperature in Degrees Celsius  
(Xantrex P/N 84-2024-00)  
All other options must be installed at the time the Link 10 is manufactured,  
as additional circuitry is involved.  
Special order VERSIONS of the Link 10  
RS-232  
(9600, 8, N, 1 ASCII computer port)  
Alarm Switch  
Switch closure when Low Battery Alarm is active.  
RS-232 + Alarm Switch  
(Both options above)  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
High Voltage Prescaler  
CAUTION!  
1. Installation of the Prescaler Option involves work with poten-  
tially fatal voltages. NEVER work alone—have at least one person  
present who can render assistance and CPR in the event of an  
accident. If you have any doubt about your qualifications to  
work on a high-voltage system, DON'T DO IT!  
2. When working with any DC system, even so-called ungrounded  
("floating") systems with no planned chassis connection, disconnect  
the negative battery terminal first.  
Use a Prescaler if system voltage EVER exceeds 50 V!  
Then set voltage scaling with F13 (see page 50).  
2 A Fuse. Above 250 V  
use 500 V rated fuse.  
+
Prescaler Part Numbers:  
0–100 V  
0–500 V  
84-6000-00  
84-6000-05  
+
Red  
(Tagged)  
HV  
Black  
Battery  
To Link 10  
Prescaler  
Red  
(Tagged)  
-
Black  
To Link 10  
Warning: Reversing input  
voltage destroys Prescaler  
and voids warranty.  
Shunt  
-
Note: Black wires are common within Prescaler.45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electric Vehicles (EVs)  
The Link 10 is the ideal energy meter for EV instrumentation. It not only  
provides volts, amps, amp hours and time remaining, it adds two important  
bonuses: kilowatt hours and optional serial computer output.  
If you design or work with electric vehicles or battery-powered equipment  
of any type, you should realize that kilowatt hours are a more accurate  
measure of energy used than are amp hours. Here's why:  
The term "amp hour" defines current (amps) multiplied by time (hours).  
Amp hours is one way to state battery capacity. Amp hours is not a measure  
of energy consumed by a vehicle. Energy is defined as:  
Energy in watt hours = voltage x amperage x time.  
Consider two examples: First, assume we have a 120-volt battery that  
supplies a 100-amp load for 1 hour. At the end of one hour, 12,000 watt-  
hours (12.00 kWh) will have been consumed. In the same period of time,  
100 amp hours will be used.  
But now suppose we have a 240-volt battery supplying a 100-amp load  
for one hour. What happens to the math? Well, 24,000 watt hours (24.00  
kWh) of power have been consumed. The amp hours consumed is the  
same as the first example, 100 amp hours, but twice the energy has been  
consumed!  
That's why electric vehicle efficiency is judged on kilowatt hours. A kilo-  
watt hour is a 1,000-watt load for a period of one hour. You buy kilowatt  
hours from the power company (to keep the lights on in your home) at a  
typical cost of $0.05 to $0.15 per kWh. By comparing the cost of kilowatt  
hours from the electric company with kilowatt-hour consumption of an  
electric vehicle, you can accurately judge EV operating costs.  
Refer to the Owner's Manual for instructions on use of the kWh display.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EV Installations  
The negative of the Link 10's power supply must be common to the nega-  
tive of the battery (motive pack) which you are measuring. This may pose  
difficulty if your electric vehicle uses an "unbonded" or "floating" (no  
connection to the chassis) motive pack and a "bonded" (connected to the  
chassis) accessory battery. In these instances, the use of a DC-DC con-  
verter, or a separate battery with a common negative with the motive  
battery is required. This device provides power for the Link 10 without  
electrically connecting the motive battery negative to the chassis. The  
diagram shown is for a typical DC-DC converter. If you use a different  
DC-DC converter, the pin-out may be different:  
+
Warning: Reversing  
2 A Fuse. Above 250 V  
input voltage destroys  
use 500 V rated fuse.  
Prescaler and voids  
+
warranty.  
Red (Tagged)  
HV  
Black  
Battery  
-
Prescaler  
Red  
(Tagged)  
+HV scaled  
voltages goes  
to Pin #4  
Black  
Shunt  
-
Link 10  
DC - DC  
Converter  
+12 V Meter  
power goes  
to Pin #5  
1
5 6 7 8  
2 3 4  
4
3
-
5
6
Acces.  
12V  
Battery  
+
7
2
1
DC-DC Converter pin outs vary.  
8
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Lift Truck Installations  
Installation of the Link 10 in lift trucks, which have the motive pack bonded  
to the chassis and also have a 12 V accessory battery bonded to the chassis,  
may use the diagram below for proper wiring of the appropriate Prescaler.  
The 0–100 V Prescaler is used where system voltage does not exceed  
100 V at any time, including during onboard charging. In any other instance,  
a 500 V Prescaler must be used. If possible, install separate Anderson (SMH)  
connector so pack can be charged in truck if batteries are not changed.  
This way, battery cycles will be counted.  
2 A fuse. Above 250 V  
use 500 V rated fuse.  
+
Warning: Reversing input  
voltage destroys Prescaler  
and voids warranty.  
Red  
(Tagged)  
+
HV  
Battery  
Black  
Prescaler  
-
Red  
(Tagged)  
Black  
Shunt  
-
Link 10  
1
5 6 7 8  
2 3 4  
-
12 V  
or  
24 V  
Acces.  
(-)  
(-)  
Optional  
DC-DC  
Battery  
+
Converter  
(+)  
This line is not used  
if DC-DC converter is installed.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(optional) Serial Port, RS-232  
The Link 10 may be equipped to transmit serial communications data to a  
personal computer or a data logging device. When equipped with the  
optional RS-232 port, the Link 10 will transmit a data message once a  
second. The structure of this data is as follows:  
Data Rate:  
Stop Bits:  
Word:  
9600  
1
Data Bits:  
Parity Bits: None  
8
ASCII Characters, comma delimited  
OutputFormat:  
Time, kWh, amps, volts, amp hours, Peukert amp hours, Peukert amps,  
time remaining, bar graph state, temperature (degrees C).  
Time is elapsed seconds since last amp hour reset. Kilowatt hours are signed  
+ or -, amp hours are signed + or -, amps are signed + or -, volts are  
positive, time remaining is in hours or tenths of hours.  
Peukert amps and Peukert amp hours are compensated for Peukert's equa-  
tion. These numbers are primarily intended for our development and trouble-  
shooting. Please do not attempt to interpret these numbers.  
The Bar Graph state is indicated by the following integers:  
1<20%, 2<40%, 3<60%, 4<80%, 5<100%, 6 = Full (Charged Params met)  
If the Low Battery Output is activated, the Bar Graph state is indicated as:  
A<20%, B<40%, C<60%, D<80%, E<100%, F = Full (Charged Params met)  
Pin Out:  
The serial connection is via the DB-9 connector on the rear deck of the  
Link 10. See additional notes on page 11. The pin connections are as follows:  
Pin 2Receive Data line  
Pin 3Transmit Data line  
Pin 5Ground. This is connected to battery pack (-).  
The shell of the DB-9 is NOT grounded.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
High Voltage Notes  
HOW TO SET VOLTAGE SCALING WHEN  
USING A HIGH VOLTAGE PRESCALER  
F13 SETVOLTAGESCALING  
Sets proper voltage scaling when used with an external Voltage  
Prescaler. NOTE: If you use a Prescaler, you need to change the  
Charged Voltage to an appropriate value for your application. See  
"Charged Parameters" on pages 22 and 23.  
DEFAULT: 0= 0–50 V. Options: 1= 0–100 V, 2= 0–500 V  
IF YOU USE MOTIVE BATTERIES TO POWER  
THE LINK 10:  
If the HV battery is "tapped" to provide meter power, it is recommended  
that a 24 V tap, not a 12 V tap, be used. The reason for this is that under  
heavy acceleration under low battery conditions, voltage may fall to levels  
low enough to cause the meter display to turn off momentarily. Under  
extreme circumstances, historical data may also be lost.  
AVOID DATA LINE SHOCK HAZARD:  
If you have a floating ground system and the Link 10 is equipped with the  
RS-232 Serial Computer Port option and is being used to record data into a  
laptop computer, we strongly recommend use of an optical isolator such as  
Omega Cat #268 to eliminate danger of a HV short to ground or personal  
shock hazard. Use caution in connecting wires to the DB-9 on the rear of  
the Link 10 as Pin #5 is connected directly to motive battery (-).  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EC Declaration of  
Conformity  
C E  
Manufacturer:  
XANTREX TECHNOLOGY, INC.  
Address:  
Xantrex Technology, Inc.  
8999 Nelson Way  
Burnaby, BC  
Canada V5A 4B5  
Herewith declares that the Xantrex Link 10 is in conformity with  
the provision of the EEC Directive EMC 89/336/EEC and amend-  
ments 92/31/EEC, 93/68/EEC.  
The following harmonized standards have been applied:  
EN 50081-1: 1992  
EN 50082-1: 1992  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
What does this warranty cover?  
This Limited Warranty is provided by Xantrex Technology, Inc. (“Xantrex”) and covers defects in workmanship and materials in your Xantrex Link  
10 Battery Monitor. This warranty lasts for a Warranty Period of 12 months from the date of purchase at point of sale to you, the original end user  
customer.  
This Limited Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty Period.  
What will Xantrex do?  
Xantrex will, at its option, repair or replace the defective product free of charge, provided that you notify Xantrex of the product defect within the  
Warranty Period, and provided that Xantrex through inspection establishes the existence of such a defect and that it is covered by this Limited  
Warranty.  
Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and building replacement products. Xantrex reserves the  
right to use parts or products of original or improved design in the repair or replacement. If Xantrex repairs or replaces a product, its warranty  
continues for the remaining portion of the original Warranty Period or 90 days from the date of the return shipment to the customer, whichever is  
greater. All replaced products and all parts removed from repaired products become the property of Xantrex.  
Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer via a Xantrex-selected non-expedited surface  
freight within the contiguous United States and Canada. Alaska and Hawaii are excluded. Contact Xantrex Customer Service for details on freight  
policy for return shipments outside of the contiguous United States and Canada.  
How do you get service?  
If your product requires troubleshooting or warranty service, contact your merchant. If you are unable to contact your merchant, or the merchant is  
unable to provide service, contact Xantrex directly at:  
Phone: 1-800-670-0707 (toll free in North America) 1-604-422-2777 (direct)  
Fax: 1-604-420-2145  
Direct returns may be performed according to the Xantrex Return Material Authorization Policy described in your product manual. For some  
products, Xantrex maintains a network of regional Authorized Service Centers. Call Xantrex or check our website to see if your product can be  
repaired at one of these facilities.  
In any warranty claim, dated proof of purchase must accompany the product and the product must not have been disassembled or modified without  
prior written authorization by Xantrex.  
Proof of purchase may be in any one of the following forms:  
The dated purchase receipt from the original purchase of the product at point of sale to the end user, or  
The dated dealer invoice or purchase receipt showing original equipment manufacturer (OEM) status, or  
The dated invoice or purchase receipt showing the product exchanged under warranty  
What does this warranty not cover?  
This Limited Warranty does not cover normal wear and tear of the product or costs related to the removal, installation, or troubleshooting of the  
customer’s electrical systems. This warranty does not apply to and Xantrex will not be responsible for any defect in or damage to:  
a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either internally or externally, or damaged  
from improper use or use in an unsuitable environment;  
b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input voltage that creates operating  
conditions beyond the maximum or minimum limits listed in the Xantrex product specifications including high input voltage from  
generators and lightning strikes;  
c) the product if repairs have been done to it other than by Xantrex or its authorized service centers (hereafter “ASCs”);  
d) the product if it is used as a component part of a product expressly warranted by another manufacturer;  
the product if its original identification (trade-mark, serial number) markings have been defaced, altered, or removed.  
Disclaimer  
Product  
THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN CONNECTION WITH YOUR  
XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS, GUARANTEES,  
REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE IN CONNECTION WITH  
THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER’S LIABILITY,  
OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT RESTRICTION ANY IMPLIED WARRANTY OR  
CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY IMPLIED WARRANTY OF  
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO  
THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD STIPULATED UNDER THIS LIMITED WARRANTY.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Limited Warranty  
IN NO EVENT WILL XANTREX BE LIABLE FOR ANY SPECIAL, DIRECT, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES,  
LOSSES, COSTS OR EXPENSES HOWEVER ARISING WHETHER IN CONTRACT OR TORT INCLUDING WITHOUT RESTRICTION ANY  
ECONOMIC LOSSES OF ANY KIND, ANY LOSS OR DAMAGE TO PROPERTY, ANY PERSONAL INJURY, ANY DAMAGE OR INJURY  
ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION, INTEGRATION OR OPERATION OF  
THE PRODUCT.  
Exclusions  
If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To the extent you are entitled to implied  
warranties under federal law, to the extent permitted by applicable law they are limited to the duration of this Limited Warranty. Some states and  
provinces do not allow limitations or exclusions on implied warranties or on the duration of an implied warranty or on the limitation or exclusion of  
incidental or consequential damages, so the above limitation(s) or exclusion(s) may not apply to you. This Limited Warranty gives you specific legal  
rights. You may have other rights which may vary from state to state or province to province.  
Warning: Limitations On Use  
Please refer to your product user manual for limitations on uses of the product. Specifically, please note that the Xantrex Link 10 Battery Monitor is  
not intended for use in connection with life support systems and Xantrex makes no warranty or representation in connection with any use of the  
product for such purposes.  
Return Material Authorization Policy  
Before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA) number and the correct factory “Ship To”  
address. Products must also be shipped prepaid. Product shipments will be refused and returned at your expense if they are unauthorized, returned  
without an RMA number clearly marked on the outside of the shipping box, if they are shipped collect, or if they are shipped to the wrong location.  
When you contact Xantrex to obtain service, please have your instruction manual ready for reference and be prepared to supply:  
The serial number of your product  
Information about the installation and use of the unit  
Information about the failure and/or reason for the return  
A copy of your dated proof of purchase  
Return Procedure  
1. Package the unit safely, preferably using the original box and packing materials. Please ensure that your product is shipped fully insured in the  
original packaging or equivalent. This warranty will not apply where the product is damaged due to improper packaging.  
2. Include the following:  
The RMA number supplied by Xantrex Technology Inc clearly marked on the outside of the box.  
A return address where the unit can be shipped. Post office boxes are not acceptable.  
A contact telephone number where you can be reached during work hours  
A brief description of the problem  
3. Ship the unit prepaid to the address provided by your Xantrex customer service representative.  
If you are returning a product from outside of the USA or Canada  
In addition to the above, you MUST include return freight funds and are fully responsible for all documents, duties, tariffs, and deposits.  
If you are returning a product to a Xantrex Authorized Service Center (ASC)  
A Xantrex return material authorization (RMA) number is not required. However, you must contact the ASC prior to returning the product or  
presenting the unit to verify any return procedures that may apply to that particular facility.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RS-232 Warning  
When using an RS-232-equipped version of the Link 10 in an electric  
vehicle which has a floating motive battery negative, remember that Pin  
#5 of the DB-9 connector coming out of the back of the Link 10 is con-  
nected to the motive battery negative.  
This normally causes no problem when used with laptop computers.  
However, if you plug the DB-9 RS-232 output into a computer with a  
metal chassis then motive battery negative will be connected to the  
chassis of the computer.  
THIS EXPOSED BATTERY NEGATIVE MAY BE  
HAZARDOUS, AND POSSIBLY FATAL IF YOU HAVE A  
HIGH SIDE MOTIVE PACK FAULT.  
We strongly recommend that when using a computer to log data, you  
minimize the hazard by installing an RS-232 Opto-Isolation Module. One  
such module is available through Omega Engineering, Inc. (Model 268  
costs $126). Call 1-800-872-9436 (phone), 1-800-848-4271 (fax), or  
Please note you will also have to purchase DB-25 to DB-9 adapters as  
the Model 268 uses DB-25 connectors. Be certain you purchase straight-  
through adapters, not the null modem type!  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Software History  
Software Enhancement Rev. E 1.5  
The Link 10 now includes the following additional functions:  
F02 - ENHANCED SLEEP MODES  
DEFAULT: ON  
Range: ON, OFF, AUTOMATIC  
When the Sleep Mode is ON, the Link 10's numeric display turns off  
after 10 minutes in order to reduce power consumption. Pressing either  
SET or SEL buttons returns the numeric display to operation.  
When the Sleep Mode is OFF, the numeric display stays on at all times.  
In the AUTOMATIC sleep mode (displayed as AUt), the numerics are  
on whenever charging or discharging exceeds 1 amp. When the rate of  
chargeordischargeremainslessthan1ampfor10minutes,thenumeric  
display is turned off to conserve power. When asleep, pressing either  
SET or SEL reactivates the numeric display. The numeric display  
automatically wakes up when the rate of charge or discharge exceeds  
1 amp. The Automatic Sleep Mode is ideal for electric vehicles.  
TIME REMAINING DISPLAY  
DEFAULT: 001  
Range: 000  
,
001  
,
002,003  
,
P
When  
P
is selected, an averaged Time Remaining number is not  
displayed. Instead, the Link 10 reports rate compensated percent of  
(declared) Battery Capacity Remaining. A full battery is displayed as  
100Pandthedisplaydecrementsduringdischargeto00P  
.
If you have selected a discharge floor other than 100%, the percent of  
battery capacity remaining is referenced to the selected discharge floor  
and uses the instantaneous (not averaged) rate of discharge.  
This function is useful on electric vehicles where time remaining  
numbersareoflittlevalue. NOTE:Thisdisplayshowstheratecompen-  
sated capacity percentage which drives the bar graph.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Software Addendum  
Software Enhancement  
This version of the Link 10 includes special software.  
F18 - SMALL BATTERY SENSING  
DEFAULT: OFF  
Range: OFF, ON  
When this function is OFF, the meter operates as described elsewhere  
inthismanual.WhenthisfunctionisON,theamp-hourcapacityrange  
allows capacities as low as 2 amp-hours to be declared. When ON,  
capacity may be set from 2–200 amp hours, and small capacity  
increments are allowed as follows:  
From2–40amphours, 1amp-hourcapacityincrementsarepermitted.  
Above 40 (to 198 amp hours), 2 amp-hour capacity increments are  
permitted.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Advanced Functions, 30–34  
Reading the Bar Graph, 19  
Battery Basics, 8  
Removing, 11  
CE Declaration of Conformity, 51 Reset and Lock, 28  
Charge Efficiency Factor, 23  
Serial Port, RS-232 (optional), 49  
Charged Parameters, 22–23  
High Voltage Notes, 50  
Historical Data, 29  
Setting Battery Capacity, 21  
Setting Peukert's Exponent, 26  
Setting Up t , 24  
Installation (General), 9–15  
Introduction, 7  
Shunt & Battery Wires, 13  
Specifications, 59  
Low Battery Alarm, 27, 35–38 Startup, 16  
Low Voltage, 27  
Synchronizing the Link 10, 17  
Meter Wiring Detail, 14  
Mounting, 10  
Temperature Sensor (optional), 25  
Troubleshooting, 43  
Operation (Basic), 18–24  
Options and Versions, 44  
Peukert’s Equation, 26, 39–42  
Prescaler (optional), 45  
Quick Reference Guide, 5–6  
Using the  
Buttons, 20  
Warranty Support, 52  
Wire by Wire Check, 15  
Wiring Overview, 12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
Voltage: For 12 V–24 V systems. Optional Prescalers extend voltage range.  
StandardModel:TwoAuto-ranges: 0to19.95V(0.05Vresolution)  
V
20.0to50.0V(0.1Vresolution)  
Optional Prescalers: 0–100 V, 0–500 V (Used with standard model)  
Amperage:  
Low Range: + 0–40.0 amps (0.1 amp resolution)  
High Range: + 500 amps (1 amp resolution)  
A
Amp-hours:  
Low Range: +0–199.9 amp hours (0.1 amp hour resolution)  
High Range: + 200–1999 amp hours (1 amp hour resolution)  
TimeRemaining:  
Low Range: 0 to 199.9 hours (0.1 hour resolution)  
High Range: 0 to 255 hours (1.0 hour resolution)  
PowerRequirements:  
9.5–40 volts DC  
Ah  
t
Current: 50–150mA(Dependsonambientlight.Displayautodims.)  
28mA (SleepMode—BarGraphDisplayOnly)  
Shunt type required: 50 mV @ 500 amp  
Accuracy:  
Voltage: + (0.6% of reading + 1 least count of resolution)  
Amperage: + (0.8% of reading + 1 least count of resolution)  
Amphours:AhError~(Timeofmeasurementxcurrenterror)  
Physical:  
Max. Outer Bezel Diameter: 2.5'' (63.5 mm)  
Max. Barrel diameter: 1.95" (50 mm)  
Max. Depth: (from back of bezel) 3.15'' (80 mm)  
Hole Cutout Size: Use 2" or 2 1/16" hole saw (52 mm)  
WaterResistance:Splashprooffrontpanel.  
Weight: 8 Ounces (227 g)  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Xantrex Technology Inc.  
Toll free 1 800 670 0707  
Direct 1 604 422 2777  
Fax 1 604 420 2145  
445-0195-01-01 Rev.1  
Printed in the U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Westinghouse Saw Digtrip RMS 500 User Manual
Whirlpool Cooktop W10545672A User Manual
Whirlpool Freezer EH101FXRQ00 User Manual
White Rodgers Furnace 50A55 143 User Manual
Williams Sound TV Video Accessories model wir 240 250 User Manual
Winix Dehumidifier WDH 871 User Manual
Xantech Speaker XA65C User Manual
Zanussi Microwave Oven 641 User Manual
Zanussi Refrigerator DF 78 30 FF User Manual
Zhone Technologies Network Card ADSL2+ Reach High Performance User Manual