White Rodgers Furnace 50A55 143 User Manual

50A55-143  
Integrated Furnace Control  
WHITE-RODGERS  
INSTALLATION INSTRUCTIONS  
Operator: Save these instructions for future use!  
FAILURETOREADANDFOLLOWALLINSTRUCTIONSCAREFULLYBEFORE  
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL  
INJURY AND/OR PROPERTY DAMAGE.  
DESCRIPTION  
The 50A55-143 is an automatic gas interrupted ignition  
control that employs a microprocessor to continually  
monitor, analyze, and control the proper operation of the  
gas burner, inducer, and fan.  
Signals interpreted during continual surveillance of the  
thermostat and flame sensing element initiate automatic  
ignition of the burner, sensing of the flame, and system  
shut-off during normal operation.  
Thesecontrolsincorporatesystemfaultanalysisforquick  
gas flow shut-off, coupled with automatic ignition retry  
upon sensing a fault correction.  
PRECAUTIONS  
CAUTION  
GENERAL PRECAUTION  
!
!
To prevent electrical shock and/or equipment  
damage, disconnect electric power to system at  
main fuse or circuit breaker box until installation  
is complete.  
Application of this type of control may cause  
flame rollout on initial start-up and could cause  
personal injury and/or property damage.  
Replace only with exact model number, includ-  
ing dash number. Failure to use exact replace-  
ment control could cause personal injury and/or  
property damage.  
Label all wires prior to disconnection when ser-  
vicing controls. Wiring errors can cause im-  
proper and dangerous operation.  
This control is not intended for use in locations  
where it may come in contact with water. Suit-  
able protection must be provided to shield the  
control from exposure to water (dripping, spray-  
ing, rain, etc.).  
Ifindoubtaboutwhetheryourwiringismillivolt,line,orlow  
voltage, have it inspected by a qualified heating and air  
conditioning contractor or licensed electrician.  
Do not exceed the specification ratings.  
All wiring must conform to local and national electrical  
codes and ordinances.  
WARNING  
!
Do not use on circuits exceeding specified volt-  
age. Higher voltage will damage control and  
could cause shock or fire hazard.  
This control is a precision instrument, and should be  
handled carefully. Rough handling or distorting compo-  
nents could cause the control to malfunction.  
CONTENTS  
Do not short out terminals on gas valve or pri-  
marycontroltotest. Shortorincorrectwiringwill  
damage thermostat and could cause personal  
injury and/or property damage.  
Description ......................................................... 1  
Precautions ........................................................ 1  
Specifications..................................................... 2  
Installation.......................................................... 3  
Mounting & Wiring  
Operation ........................................................... 6  
WHITE-RODGERS DIVISION  
EMERSON ELECTRIC CO.  
9797 REAVIS ROAD  
PART NO. 37-6095A  
Printed in U.S.A.  
ST. LOUIS, MISSOURI 63123-5398  
9919  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
MOUNTING AND WIRING  
WARNING  
NOTE  
All wiring should be installed according to local and  
national electrical codes and ordinances.  
!
Do not use on circuits exceeding specified  
voltage. Higher voltage will damage control  
and could cause shock or fire hazard.  
The control must be secured to an area that will experi-  
ence a minimum of vibration and remain below the maxi-  
mum ambient temperature rating of 175°F. The control is  
approved for minimum ambient temperatures of -40°F.  
CAUTION  
!
Whenmountingthecontrol, anyorientationisacceptable.  
Choose a location that will not damage, obstruct or place  
stress on the control’s terminations, system wiring har-  
ness or system components. After finding a suitable  
To prevent electrical shock and/or equipment  
damage, disconnect electric power to system at  
main fuse or circuit breaker box until installation  
is complete. Failure to earth ground the appli-  
ance or reversing the neutral and hot wire con-  
nection to the line can cause shock hazard.  
1
location, drill four (4) 8” holes for mounting control. To  
ensurepropermountingholelocations, thereisa mount-  
ing hole template on page 8 of this instruction sheet.  
Detach the page with the template from the instruction  
sheet and apply it to the mounting location. When drilling  
the holes, take care so that the transformer, wiring har-  
ness or other system components are not damaged. Four  
(4) #8 sheet metal screws are provided to complete the  
installation.  
Shut off main gas to heating system until instal-  
lation is complete.  
Route and secure all wiring as far from flame  
as practical to prevent fire and/or equipment  
damage.  
Refer to the wiring diagram and wiring table when con-  
necting the 50A55 control to other components of the  
system.  
UL approved, 105°C rated 18 gauge, stranded, 264” thick  
insulation wire is recommended for all low voltage safety  
circuit connections. Refer to 50A55 specification sheet  
for recommended terminals to mate with those on the  
control.  
To prevent damage to the transformer, system  
components or wiring harness, take care when  
drillingnewmountingholes.Failuretodosomay  
result in electrical shock, fire hazard or equip-  
ment damage.  
UL approved 105°C rated 16 gauge min., stranded, 464”  
thick insulation wire is recommended for all line voltage  
connections. Refer to 50A55 specification sheet for rec-  
ommended terminals to mate with those on the control.  
After installation or replacement, follow appliance  
manufacturer’s recommended installation or service in-  
structions to ensure proper operation.  
The 50A55 has only one serviceable part–an automotive  
typefuse,whichprotectsthelowvoltagetransformerfrom  
damage if its output is short-circuited. If the fuse has  
opened up, remove whatever caused the short circuit and  
replace the fuse with only a 3 Amp automotive type fuse.  
If the fuse is not the cause of the control’s problem,  
replace the entire 50A55 control. There are no other user  
serviceable parts.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL SYSTEM WIRING DIAGRAM  
HOT  
(LINE)  
NEUTRAL  
(LINE)  
120 VAC  
24 VAC CLASS II  
TRANSFORMER  
TH  
24 VAC  
50A55  
TR  
COOL  
HEAT  
PARK  
PARK  
LINE  
CIRCULATOR  
BLOWER  
XFMR  
EAC  
HUM  
INDUCER  
IGNITOR  
IND  
IGN  
HUMIDIFIER  
CIR N  
LINE N  
XFMR N  
HUM N  
EAC N  
ELECTRONIC  
AIR CLEANER  
Y
W
G
R
C
Y
W
G
R
COMPRESSOR  
CONTACTOR  
50A55-143  
IN OTHER  
FURNACES  
TWINNING  
APPLICATIONS  
ONLY  
THERMOSTAT  
TWIN*  
TWIN*  
PRESSURE SWITCH (N. O.)  
PS  
HLI  
HLO  
FP  
RO1  
GND  
RO2  
MV  
FLAME  
SENSOR  
PROBE  
HIGH LIMIT  
(N. C.)  
AUX. HIGH  
LIMIT (N. C.)  
ROLLOUT  
(N. C.)  
GAS  
VALVE  
MV  
TR  
TH  
LEGEND  
Low Voltage (24 VAC)  
Line Voltage (120 VAC)  
N. C. = Normally closed switch  
N. O. = Normally open switch  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL SYSTEM WIRING TABLE  
50A55  
TERMINAL  
TERMINAL  
SYSTEM COMPONENT  
CONNECTION  
TYPE  
W
G
R
Y
low voltage thermostat W terminal (or equivalent)  
low voltage thermostat G terminal (or equivalent)  
low voltage thermostat R terminal (or equivalent)  
low voltage thermostat Y terminal (or equivalent)  
(2nd wire from Y terminal goes to 24 VAC HOT side of  
compressor contactor coil)  
Terminal  
block with  
captive  
screws  
TWIN  
one wire twinning terminal  
C
24 VAC COMMON side of compressor contactor coil  
gas valve (both gas solenoids are connected in parallel)  
24 VAC transformer (low voltage COMMON side)  
24 VAC transformer (low voltage HIGH side)  
rollout switch OUTPUT  
MV (2 terminals)  
TR  
TH  
RO1  
RO2  
12-pin  
rollout switch INPUT  
FP  
connector  
& harness  
flame sensor probe*  
PS  
pressure switch INPUT  
HLI  
high limit INPUT  
HLO  
high limit OUTPUT  
GND  
MUST BE RELIABLY GROUNDED TO CHASSIS  
(unused terminal)  
2-pin  
connector  
& harness  
IND  
IGN  
inducer HOT side  
ignitor HOT side  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
spade terminal  
COOL  
circulator blower COOL SPEED terminal  
circulator blower HEAT SPEED terminal  
unused circulator blower terminals  
input voltage (120 VAC) HOT side  
24 VAC transformer line voltage HOT side  
electronic air cleaner HOT side  
HEAT  
PARK (2 terminals)  
LINE  
XFMR  
EAC (optional)  
HUM (optional)  
CIR N  
humidifier HOT side  
circulator blower NEUTRAL terminal  
input voltage (120 VAC) NEUTRAL side  
24 VAC transformer line voltage NEUTRAL side  
electronic air cleaner NEUTRAL side  
humidifier NEUTRAL side  
LINE N  
XFMR N  
EAC N (optional)  
HUM N (optional)  
* maximum recommended flame probe wire length is 36 inches.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
OPTION SWITCHES  
At the end of the ignitor warm-up time, both valves in the  
36E manifold gas valve are opened. Flame must be  
Theoptionswitchesonthe50A55-143controlareusedto detected within 4 seconds.  
determine the length of the heat delay-to-fan-off periods.  
If flame is detected, the delay-to-fan-on period begins.  
The following table shows the time periods that will result  
from the various switch positions.  
After the delay-to-fan-on period ends, the optional elec-  
tronic air cleaner is energized and the circulator fan is  
energized at heat speed. When the thermostat is satis-  
fied, the gas valve is de-energized. After proof of flame  
loss, the heat delay-to-fan-off period begins and the  
inducerblowerremainsenergizedtopurgethesystemfor  
5 seconds. When the purge is complete, the inducer  
blower and humidifier are de-energized. After the delay-  
to-fan-off period ends, the circulator fan and electronic air  
cleaner are de-energized.  
OPTION SWITCH POSITIONS  
HEAT delay-  
to-fan-on:  
Set switch  
#1  
#2  
15 sec.  
30 sec.  
45 sec.  
60 sec.  
Off  
Off  
On  
On  
Off  
On  
Off  
On  
If flame is not detected, both valves are de-energized, the  
ignitor is turned off, and the 50A55 control goes into the  
“retry” sequence. The “retry” sequence provides a 60-  
second wait following an unsuccessful ignition attempt  
(flame not detected). After this wait, the ignition sequence  
is restarted with an additional 2 seconds of ignitor warm-  
up time. If this ignition attempt is unsuccessful, one more  
retry will be made before the control goes into system  
lockout.  
HEAT delay-  
to-fan-off:  
Set switch  
#3  
#4  
60 sec.  
90 sec.  
120 sec.  
180 sec.  
On  
Off  
On  
Off  
On  
On  
Off  
Off  
Ifflameisdetected,thenlost,the50A55controlwillrepeat  
the initial ignition sequence for a total of four “recycles”.  
After four unsuccessful “recycle” attempts, the control will  
go into system lockout.  
HEAT MODE  
In a typical system, a call for heat is initiated by closing the  
thermostat contacts. This starts the 50A55 control’s heat-  
ing sequence. The inducer blower and optional humidifier  
are energized, and after the 30-second prepurge the  
ignitor is powered within one second.  
If flame is established for more than 10 seconds after  
ignition, the50A55controllerwillcleartheignitionattempt  
(or retry) counter. If flame is lost after 10 seconds, it will  
restart the ignition sequence. This can occur a maximum  
of five times before system lockout.  
This controller has an adaptive algorithm that adjusts the  
durationoftheignitorwarm-up,toextendignitorlife.Upon  
initial application of power, the warm-up time is 17 sec-  
onds. The ignitor on-time will then be increased or de-  
creased depending on whether or not flame is achieved.  
The warm-up time is limited to a maximum of 21 seconds.  
During the first 64 warm-up periods following power-up,  
the warm-up time may not be less than 17 seconds.  
Duringburneroperation, amomentarylossofpowerof50  
milliseconds or longer will de-energize the main gas  
valve. When power is restored, the gas valve will remain  
de-energized and a restart of the ignition sequence will  
begin immediately.  
A momentary loss of gas supply, flame blowout, or a  
shorted or open condition in the flame probe circuit will be  
sensed within 2.0 seconds. The gas valve will de-ener-  
gize and the control will restart the ignition sequence.  
Recycles will begin and the burner will operate normally  
ifthegassupplyreturns,orthefaultconditioniscorrected,  
before the last ignition attempt. Otherwise, the control will  
go into system lockout.  
Upon a call for heat, if the warm-up time has not been  
locked, it will be decreased by one second. This reduction  
of the ignitor on-time will continue until flame fails to be  
achieved (resulting in a retry).  
In the event of a retry, the warm-up time will be increased  
by two seconds and locked in at that duration. Once the  
warm-up time is locked, it remains fixed until another call  
for heat results in a retry, in which case the warm-up time  
is again increased by two seconds and remains locked.  
If the control has gone into system lockout, it may be  
possible to reset the control by a momentary power  
interruption of one second or longer. Refer to SYSTEM  
LOCKOUT FEATURES.  
In the event of two successive retry attempts, the warm-  
up time will be unlocked and set to 21 seconds. If flame is  
then achieved, the warm-up time will begin adapting  
again with the next call for heat. If, however, this third  
attempt fails to achieve flame, the control will go into  
system lockout.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOL MODE  
SYSTEM LOCKOUT AND  
DIAGNOSTIC FEATURES  
In a typical system, a call for cool is initiated by closing the  
thermostat contacts. This energizes the 50A55 control  
and the compressor. The cool delay-to-fan-on period  
begins. After the delay period ends, the optional elec-  
tronic air cleaner is energized, and the circulator fan is  
energized at cool speed. After the thermostat is satisfied,  
thecompressorisde-energizedandthecoolmodedelay-  
to-fan-off period begins. After the delay-to-fan-off period  
ends, the circulator fan and electronic air cleaner (op-  
tional) are de-energized.  
SYSTEM LOCKOUT FEATURES  
When system lockout occurs, the gas valve is de-ener-  
gized, the circulator blower is energized at heat speed,  
and, if flame is sensed, the inducer blower is energized.  
The diagnostic indicator light will flash or glow continu-  
ously to indicate system status. (System lockout will  
never override the precautionary features.)  
Toresetthecontrolaftersystemlockout, dooneofthe  
following:  
MANUAL FAN ON MODE  
1. Interrupt the call for heat or cool at the thermostat for  
at least one second but less than 20 seconds (if flame  
is sensed with the gas valve de-energized, interrupt-  
ing the call for heat at the thermostat will not reset the  
control).  
If the thermostat fan switch is moved to the ON position,  
the circulator fan (cool speed) and optional electronic air  
cleaner are energized. When the fan switch is returned to  
the AUTO position, the circulator fan and electronic air  
cleaner (optional) are de-energized.  
2. Interrupt the 24 VAC power at the control for at least  
one second. You may also need to reset the flame  
rollout sensor switch.  
TWINNING INTERFACE  
If the control has six screw terminals, one of which is  
designated TWIN, the control is equipped with a single  
wire twinning interface. If twinning is used, either control  
willprocessacallforheat, coolorfanasdescribedabove.  
However, after the heat-, cool-, or fan-on delay time  
expires, both units will energize the circulator blowers at  
the same time. Likewise, after the heat-, cool-, or fan-off  
delay time expires, both units will de-energize the circula-  
torblowersatthesametime.Thisallowsforproperairflow  
to be obtained. To assure proper control operation, both  
controls must share a common transformer ground (TR).  
3. Afteronehourinlockout,thecontrolwillautomatically  
reset itself.  
DIAGNOSTIC FEATURES  
The 50A55 control continuously monitors its own opera-  
tionandtheoperationofthesystem.Ifafailureoccurs,the  
LED will indicate a failure code as shown below. If the  
failure is internal to the control, the light will stay on  
continuously. In this case, the entire control should  
be replaced, as the control is not field-repairable.  
To enable twinning, do the following.  
If the sensed failure is in the system (external to the  
control), the LED will flash in the following flash-pause  
sequences to indicate failure status (each flash will last  
approximately 0.25 seconds, and each pause will last  
approximately 2 seconds).  
1. Power supplied to both furnaces must be from the  
same phase of the incoming 120 VAC power.  
2. ConnecttheTWINscrewterminalsonthe50A55-143  
of the furnaces to be twinned to each other using a  
single wire (14-22 AWG.).  
1 flash, then pause  
System lockout  
2 flashes, then pause Pressure switch stuck closed  
3 flashes, then pause Pressure switch stuck open  
4 flashes, then pause Open limit switch  
5 flashes, then pause Open rollout switch  
6 flashes, then pause 115 Volt AC power reversed/  
improper ground  
7 flashes, then pause Low flame sense signal  
Continuous flashing  
(no pause)  
Flame has been sensed when  
no flame should be present (no  
call for heat)  
The LED will also flash once at power-up.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOUNTING HOLE TEMPLATE  
FOR MOUNTING HOLE LOCATIONS  
4.172 ± .007  
(2 plcs.)  
6.402 ± .010  
(2 plcs.)  
Refer to page 3 of the installation instructions for proper installation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Weider Home Gym WESY49202 User Manual
Whirlpool Ice Maker 2180633 User Manual
Whirlpool Range 76724CO 4320880 User Manual
Whirlpool Range W10204320B User Manual
Winegard TV Converter Box RC DT09 User Manual
Wyse Technology Computer Monitor 2510SE User Manual
Xantech Network Router RS2321X8 User Manual
Xerox All in One Printer 130 B 141 User Manual
Yamaha DJ Equipment FX500B User Manual
Zanussi Refrigerator ZC2450R User Manual