Vermont Casting Fire Pit 36CDVRRN User Manual

INSTALLER/CONSUMER  
SAFETY INFORMATION  
Builder Direct Vent  
Models:  
PLEASE READ THIS MANUAL  
BEFORE INSTALLING AND  
USING APPLIANCE  
WARNING!  
36CDVRRN (Rear Vent)  
36CDVTRN (Top Vent)  
IF THE INFORMATION IN THIS  
MANUAL IS NOT FOLLOWED  
EXACTLY, A FIRE OR EXPLO-  
SION MAY RESULT CAUSING  
PROPERTY DAMAGE, PER-  
SONAL INJURY OR LOSS OF  
LIFE.  
FOR YOUR SAFETY  
Installation and service must  
be performed by a qualified  
installer, service agency or  
the gas supplier.  
WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not touch any electric switch;  
do not use any phone in your  
building.  
Immediately call your gas  
supplier from your neighbor’s  
phone. Follow the gas suppliers  
instructions.  
If you cannot reach your gas  
supplier call the fire department.  
Installation Instructions and  
Homeowner’s Manual  
DO NOT STORE OR USE  
GASOLINE OR OTHER  
FLAMMABLE VAPORS AND  
LIQUIDS IN THE VICINITY OF  
THIS OR ANY OTHER  
APPLIANCE.  
S
CERTIFIED  
C
I
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
20010175 6/06 Rev. 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Installation & Operating Instructions  
This gas appliance should be installed by a qualified  
installer in accordance with local building codes and with  
current CSA-B149.1 Installation codes for Gas Burning  
Appliances and Equipment. For USA Installations follow  
local codes and/or the current National Fuel Gas Code.  
ANSI Z223.1/NFPA 54.  
In the Commonwealth of Massachusetts, all gas fitting  
and installation of this heater shall only be done by a  
licensed gas fitter or licensed plumber.  
Proposition 65 Warning: Fuels used in gas, wood-  
burning or oil fired appliances, and the products of  
combustion of such fuels, contain chemicals known to  
the State of California to cause cancer, birth defects  
and other reproductive harm.  
California Health & Safety Code Sec. 25249.6  
WARNING: Check with your electronics manufacturer  
before installing a television or other electronic de-  
vice above this fireplace.  
FOR SAFE INSTALLATION AND OPERATION PLEASE  
NOTE THE FOLLOWING:  
1. This fireplace gives off high temperatures and should be  
located out of high traffic areas and away from furniture  
and draperies.  
2. Children and adults should be alerted to the hazards of  
high surface temperatures of this fireplace and should stay  
away to avoid burns or ignition of clothing.  
3. CAUTION: Due to high glass surface temperature chil-  
dren should be carefully supervised when in the same  
room as fireplace.  
4. Under no circumstances should this fireplace be modified.  
Parts removed for servicing should be replaced prior to  
operating this fireplace again.  
5. Installation and any repairs to this fireplace must be  
performed by a qualified installer, service agency or gas  
supplier. A professional service person should be contacted  
to inspect this fireplace annually. Make it a practice to have  
all of your gas fireplaces checked annually. More frequent  
cleaning may be required due to excess lint and dust from  
carpeting, bedding material, etc.  
IMPORTANT:  
PLEASE REVIEW THE FOLLOWING CAREFULLY  
Removeanyplasticfromtrimpartsbeforeturningthereplace  
ON.  
It is normal for fireplaces fabricated of steel to give off some  
expansionand/orcontractionnoisesduringthestartuporcool  
down cycle. Similar noises are found with your furnace heat  
exchanger or car engine.  
It is not unusual for your gas fireplace to give off some odor  
the first time it is burned. This is due to the curing of the paint  
and any undetected oil from the manufacturing process.  
Please ensure that your room is well ventilated - open  
all windows.  
It is recommended that you burn your fireplace for at least  
ten (10) hours the first time you use it. If the optional fan kit  
has been installed, place the fan switch in the “OFF” position  
during this time.  
6. Control compartments, burners and air passages in this  
fireplace should be kept clean and free of dust and lint.  
Make sure the gas valve and pilot light are turned off before  
you attempt to clean this fireplace.  
Locating Your Fireplace  
7. The venting system (chimney) of this fireplace should be  
checked at least once a year and if needed your venting  
system should be cleaned.  
8. Keep the area around your fireplace clear of combustible  
materials, gasoline and other flammable vapor and liquids.  
This fireplace should not be used as a drying rack for cloth-  
ing, nor should Christmas stockings or decorations be hung  
on or around the fireplace.  
E
A
B
Y
Y
X
C
D
B
X
F
9. Under no circumstances should any solid fuels (wood, coal,  
paper or cardboard etc.) be used in this fireplace.  
10. The flow of combustion and ventilation air must not be  
obstructed in any way.  
11. When fireplace is installed directly on carpeting, vinyl tile  
or any combustible material other than wood, the fireplace  
must be installed on a metal or wood panel extending the  
full width and depth of the fireplace.  
LU584-R  
Fig. 1 Locate gas fireplace.  
A) Flat on wall  
B) Cross corner  
C) **Island  
D) *Room divider E) *Flat on wall corner F) Chase installation  
Y) 6” minimum  
NOTE: (Fig. 1)  
** Island (C) and Room Divider (D) installation is possible as  
long as the horizontal portion of the vent system (X) does not  
exceed 20’ (6 m) with a minimum vertical of 4’ (122 cm). See  
details in Venting Section.  
12. This fireplace requires adequate ventilation and combustion  
air to operate properly.  
13. This fireplace must not be connected to a chimney flue  
serving a separate solid fuel burning fireplace.  
* When you install your fireplace in(D) Room divider or (E) Flat  
on wall corner positions (Y), a minimum of 6” (153 mm) clear-  
ance must be maintained from the perpendicular wall and the  
front side edge of the fireplace.  
14. When the fireplace is not in use it is recommended that the  
gas valve be left in the OFF position.  
15. These units have been approved for bedroom use.  
Refer to (Y) in Figure 1.  
3
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Fireplace Dimensions - Rear Vent  
Rough  
Opening  
Depth  
G
*
U
W
F
*
V
X - Rough Opening Width  
U*  
*
T
Rough  
Opening  
Height  
Centerline of  
7" Collar  
C
Electrical  
Access  
L
Gas Line  
Access  
C
Y
I
B
E
D
Gas Line  
Access  
H
K
L
J
Q
R
S
P
A
O
N
M
Low  
Voltage  
Access  
Low Voltage  
Electrical  
Fig. 2 Fireplace specifications and framing dimensions.  
Ref.  
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
36CDVR  
35¹⁄₄”  
(895 mm)  
(892 mm)  
(816 mm)  
(838 mm)  
(537 mm)  
(422 mm)  
(635 mm)  
(470 mm)  
(559 mm)  
(83 mm)  
(73 mm)  
(35 mm)  
(356 mm)  
(216 mm)  
(187 mm)  
(35 mm)  
35¹⁄₈”  
32¹⁄₈”  
33”  
21¹⁄₈”  
16⁵⁄₈”  
25”  
18¹⁄₂”  
22”  
3¹⁄₄”  
2⁷⁄₈”  
1³⁄₈”  
14”  
8¹⁄₂”  
7³⁄₈”  
1³⁄₈”  
3¹⁄₄”  
7³⁄₈”  
8¹⁄₂”  
(83 mm)  
(187 mm)  
(216 mm)  
Framing Dimensions  
T*  
U*  
V*  
W
X
68¹⁄₄“  
48¹⁄₄“  
34¹⁄₈”  
17¹⁄₈”  
36¹⁄₄”  
35³⁄₈”  
(1734 mm)  
(1226 mm)  
(867 mm)  
(435 mm)  
(921 mm)  
(899 mm)  
Y
* Must be adhered to!  
4
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Fireplace Dimensions - Top Vent  
Rough  
Opening  
Depth  
G
U
H
W
F
V
X - Rough Opening Width  
U
T
Rough  
Opening  
Height  
Electrical  
Access  
Gas Line  
Access  
C
Y
B
E
D
Gas Line  
Access  
K
J
Q
R
S
P
A
O
N
M
Low  
Voltage  
Access  
L
Low Voltage  
Electrical  
Access  
Fig. 2 Fireplace specifications and framing dimensions.  
Ref.  
A
B
C
D
E
36CDVT  
35¹⁄₄”  
(895 mm)  
(883 mm)  
(816 mm)  
(838 mm)  
(537 mm)  
(422 mm)  
(635 mm)  
(203 mm)  
(83 mm)  
(73 mm)  
(35 mm)  
(356 mm)  
(216 mm)  
(187 mm)  
(35 mm)  
35³⁄₄”  
32¹⁄₈”  
33”  
21¹⁄₈”  
16⁵⁄₈”  
25”  
F
G
H
J
K
L
M
N
O
P
Q
R
S
8”  
3¹⁄₄”  
2⁷⁄₈”  
1³⁄₈”  
14”  
8¹⁄₂”  
7³⁄₈”  
1³⁄₈”  
3¹⁄₄”  
7³⁄₈”  
8¹⁄₂”  
(83 mm)  
(187 mm)  
(216 mm)  
Framing Dimensions  
T
U
V
W
X
58³⁄₈“  
41³⁄₈“  
29¹⁄₈”  
17¹⁄₈”  
36¹⁄₄”  
35”  
(1483 mm)  
(1051 mm)  
(740 mm)  
(435 mm)  
(921 mm)  
(889 mm)  
Y
5
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Clearance to Combustibles  
Top of Unit to Ceiling ............................... 36” (914 mm)  
Front of Unit to Combustibles.................. 36” (914 mm)  
Appliance  
Top .......................................................... 0” (0 mm)  
Bottom..................................................... 0” (0 mm)  
Side......................................................... 0” (0 mm)  
Back........................................................ 0” (0 mm)  
Venting  
J
I
H
Black  
G
Surround  
Face  
F
Mantel  
Leg  
Concentric sections of DV Vent  
CFM164a  
Top, bottom & sides .............................. 1” (25 mm)  
K
L
NOTE: Hood must be permanently installed with  
three (3) sheet metal screws supplied in fireplace.  
Side of  
Combustion Chamber  
M
N
O
Mantels  
The height that a combustible mantel is fitted above the  
fireplace is dependent on the depth of the mantel. This  
also applies to the distance between the mantel leg (if  
fitted) and the fireplace.  
For the correct mounting height and widths refer to  
Figs. 3a and 3b, and the following Mantel Charts.  
The fitting of a bay window trim kit does not effect  
the distances and reference points referred to in the  
diagram and chart.  
CFM170  
Noncombustible mantels and legs may be installed at  
any height and width around the appliance.  
Mantel  
Leg Depth  
Mantel Leg FromSide  
Ref. of Comb. Opening  
Ref.  
F
G
H
I
J
When using paint or lacquer to finish the mantel, such  
paint or lacquer must be heat resistant to prevent  
discoloration.  
10” (254 mm)  
8” (203 mm)  
6” (152 mm)  
4” (101 mm)  
2” (51 mm)  
K
L
M
N
O
11¹⁄₂” (292 mm)  
9¹⁄₂” (241 mm)  
7¹⁄₂” (191 mm)  
5¹⁄₂” (140 mm)  
3¹⁄₂” (89 mm)  
V
Finish Wall  
W
X
Y
Fig. 3b Combustible mantel leg minimum installation.  
Z
Hearth  
Standoff  
A hearth is not mandatory but is recommended for  
aesthetic purposes. We recommend a noncombustible  
hearth which projects out 12” (305 mm) or more from  
the front of the fireplace.  
Noncombustible  
A
B
C
D
E
Material  
Hood  
Cold climate installation recommendation:  
Fireplace  
When installing this unit against a  
non-insulated exterior wall or chase,  
it is mandatory that the outer walls  
be insulated to conform to applicable  
insulation codes.  
Top of Combustion  
Chamber  
CFM146  
Mantel Chart  
This appliance may be installed in an aftermarket  
permanently located, manufactured home or mobile  
home, where not prohibited by local codes.  
Thisapplianceisonlyforusewiththetypeofgasindicated  
on the rating plate. This appliance is not convertible for  
use with other gases, unless a certified kit is used.  
The CDVR has been approved for mobile home  
installations.  
Mantel Shelf or  
Ref. Breast Plate Depth Ref. Combustion Chamber  
Mantel from Top of  
V
W
X
Y
Z
10” (254 mm)  
A
B
C
D
E
17” (432 mm)  
15” (381 mm)  
13” (330 mm)  
11” (279 mm)  
8”  
6”  
4”  
2”  
(203 mm)  
(152 mm)  
(101 mm)  
(51 mm)  
9”  
(229 mm)  
Fig. 3a Combustible mantel minimum installation.  
6
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Framing and Finishing  
Hood Installation  
CAUTION: Hood MUST be permanently installed.  
Check fireplace to make sure it is levelled  
and properly positioned.  
1. Remove top louvre. Carefully remove hood from  
inside top louvre opening.  
2. Remove three (3) sheet metal screws in bottom  
flange of fireplace surround top.  
To mount the appliance:  
1. Choose the location.  
2. This unit comes with four (4) flanges pre-mounted  
on both sides of the fireplace to allow two different  
drywall thicknesses to be used. Flange “A” is for 1/2”  
drywall while flange “B” is for 5/8” drywall.  
3. Install the hood by aligning the three holes in bottom  
flange of fireplace surround top. (Fig. 4a)  
4. Secure hood to bottom flange of fireplace surround  
top using three screws removed in Step 2. (Fig. 4a)  
3. Bend the desired flanges out 90° on both sides of  
the fireplace. Slide the fireplace into the framed  
opening until the flanges contact the front surfaces  
of the framing. Level the unit and secure it firmly in  
place.  
5. Carefully remove protectors under the relief plates  
on top of the firebox.  
6. Replace top louvre.  
4. The standoffs are adjustable for different drywall  
thicknesses. The unit is shipped from the factory at  
1/2” (13 mm). Loosen the four (4) screws securing  
each standoff to the top of the fireplace. Slide the  
standoff back. Tighten the screws. This yields a 5/8”  
(16 mm) thick drywall space. Removing the standoff  
and having the tabs on the standoff face the rear of  
the unit yields a 3/4” (19 mm) drywall space. (Fig. 4)  
Hood  
Sheet  
Metal  
Screws  
NOTE: Drywall must stop at standoffs and not touch  
top of unit.  
FP1609  
Flange  
Position  
Drywall  
Depth  
Flange Location for Desired  
Drywall Depth at Header  
Fig. 4a Secure hood to fireplace with sheet metal screws.  
A
B
1/2” / 13 mm  
5/8” / 16 mm  
Final Finishing  
Noncombustible materials such as brick or tile may be  
extended over the edges of the face of the fireplace.  
DO NOT cover any vent or grille panels.  
If a Trim Kit is going to be installed on the fireplace, the  
brick or tile will have to be installed flush with the edges  
of the fireplace.  
A
B
36CDVR / 36CDVT  
Certified To  
ANSI Z21.88b-2003 / CSA 2.33b-2003  
Vented Gas Fireplace Heaters  
FP1603  
36CDVRRN Units: GFRL1J0  
36CDVTRN Units: GFTN1J0  
Standoff Location for Desired Drywall Depth at Header  
Screws  
Gas Specifications  
Tabs  
Max.  
Input  
Min.  
Input  
Model  
Fuel Gas Control BTU/h BTU/h  
36CDVRRN Nat  
36CDVRRP* Prop  
36CDVTRN Nat  
36CDVTRP* Prop  
Millivolt  
Millivolt  
Millivolt  
Millivolt  
21,000 14,700  
21,000 15,750  
21,000 14,700  
21,000 15,750  
FP1603a  
Fig. 4 Nailing flanges and standoffs.  
20010175  
*Using conversion kit  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
The gas control is equipped with a captured screw type  
pressure test point, therefore it is not necessary to pro-  
vide a 1/8” test point up stream of the control.  
Gas Inlet and Manifold Pressures  
Natural  
LP (Propane)  
11.0” w.c.  
When using copper or flex connector use only approved  
fittings. Always provide a union when using black iron  
pipe so the gas line can be easily disconnected for  
burner or fan servicing. See gas specification for pres-  
sure details and ratings.  
Inlet Minimum  
5.5” w.c.  
Inlet Maximum  
Manifold Pressure  
14.0” w.c.  
3.5” w.c.  
14.0” w.c.  
10.0” w.c.  
High Elevations  
The fireplace valve must not be subjected to any test  
pressures exceeding 1/2 psi. Isolate or disconnect this  
and any other gas appliance control from the gas line  
when pressure testing.  
Input ratings are shown in BTU per hour and are  
certified without deration for elevations up to  
4,500 feet (1,370 m) above sea level.  
Remote ON/OFF Switch  
For elevations above 4,500 feet (1,370 m) in USA,  
installations must be in accordance with the cur-  
rent ANSI Z223.1/NFPA 54 and/or local codes hav-  
ing jurisdiction.  
Installation  
1. Carefully unwrap the remote wire that is attached to  
the valve. There are two 1/2” (13 mm) knockouts,  
one on each side of the outer casing.  
2. Remove the knockout desired and insert the plastic  
snap bushing on the remote wire in the 1/2” hole.  
Feed the remote wire through the outer casing.  
3. Attach the wire to an ON/OFF switch and install the  
switch into the receptacle box. (Fig. 6)  
In Canada, please consult provincial and/or local  
authorities having jurisdiction for installations at  
elevations above 4,500 feet (1,370 m).  
Gas Line Installation  
When purging the gas lines, the front win-  
dow frame assembly must be removed.  
Remote ON/OFF Switch  
or Thermostat  
or Remote Control  
The gas pipeline can be brought in through the rear  
of the appliance as well as the bottom. Knockouts are  
provided on the bottom behind the valve to allow for the  
gas pipe installation and testing of any gas connection.  
It is most convenient to bring the gas line in from the  
rear right side of the valve as this allows fan installation  
or removal without disconnecting the gas line.  
TP  
TH  
Gas  
Control  
Valve  
TP  
The gas line connection can be made with properly  
tinned 3/8” copper tubing, 3/8” rigid pipe or an ap-  
proved flex connector. Since some municipalities have  
additional local codes, it is always best to consult your  
local authority and the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 in the USA or the CSA-B149.1 installa-  
tion code.  
TH  
FP1224  
Fig. 6 Remote switch wiring diagram.  
Do not wire the remote ON/OFF wall switch  
for the gas fireplace to the 120 volt power  
supply.  
1/2” Gas Supply  
120V Electrical Hook Up  
1/2” NPT x 1/2” Flare Shut-  
off Valve  
The fireplace, when installed, must be  
electrically connected and grounded in  
accordance with local codes or, in the ab-  
sence of local codes, with the current CSA  
C22.1 Canadian Electrical Code.  
3/8” Flex Line  
(From Valve)  
FP297A  
For USA installations follow local codes  
and the national electrical code ANSI/  
NFPA No. 70.  
Fig. 5 Typical gas supply installation.  
Always check for gas leaks with a mild  
soap and water solution. Do not use an  
open flame for leak testing.  
It is strongly suggested that wiring of the  
Electrical Junction Box be carried out by a  
licensed electrician.  
8
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Ensure that the power to the supply line  
has been disconnected before commenc-  
ing this procedure.  
INSIDE  
Electric Receptacle  
The electrical junction box has been fitted standard on  
this model to allow for the easy connection of an op-  
tional fan kit.  
To connect the electric box to the house electrical sup-  
ply follow the steps below.  
1. Unscrew the retaining screw holding the electric  
cover to the outside of the unit. (Fig. 7)  
OUTSIDE  
2. Remove the knockout from the electric cover plate.  
3. Insert the wire connector through the hole in the  
electric cover plate and secure.  
Electric Receptacle  
Cover Plate  
4. Insert the house wire through the connector on the  
cover plate.  
5. Secure the wires from the receptacle to the incoming  
line.  
BACK OF UNIT  
FP1597  
Fig. 7 Electric receptacle.  
6. The receptacle has four wires connected to it. The  
receptacle is set up for a split system. The top plug  
of the receptacle is wired separately from the bottom  
one.  
7. Green is ground. White is neutral, Black and red are  
line voltage to each plug on the receptacle.  
General Venting  
There must not be any obstruction such as bushes,  
garden sheds, fences, decks or utility buildings within  
24” (610mm) from the front of the termination hood.  
Your fireplace is approved to be vented either through  
the side wall, or vertically through the roof.  
Only CFM Corporation venting components specifi-  
cally approved and labelled for this fireplace may be  
used.  
Do not locate termination hood where excessive snow  
or ice build up may occur. Be sure to check vent termi-  
nation area after snow falls, and clear to prevent ac-  
cidental blockage of venting system. When using snow  
blowers, make sure snow is not directed towards vent  
termination area.  
Vent terminations shall not be recessed into a wall or  
siding.  
Horizontal venting which incorporates the twist lock  
pipe must be installed on a level plane without an  
inclining or declining slope.  
Location of Vent Termination  
It is imperative the vent termination be located observ-  
ing the minimum clearances as shown on the next  
page.  
Horizontal venting which incorporates the use of flex  
venting shall have an inclining slope from the unit of  
1” (25 mm) per 24” (610 mm).  
*Check with local codes or in absence of same with  
CSAB149.1 Installation Codes (1991) for Canada or fol-  
low the current National Fuel Gas Code, ANSI Z223.1/  
NFPA 54 for installations in the USA.  
9
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
General Venting Information - Termination Location  
INSIDE  
CORNER DETAIL  
G
V
N
H
N
A
D
E
V
B
C
B
V
B
 
�  
L
V
V
B
V
V
 
�  
G
�  
F
V
V
B
M
V
J
G
A
X
B
I
K
X
V
A
AREA WHERE TERMINAL IS NOT PERMITTED  
VENT TERMINATION  
X
AIR SUPPLY INLET  
V
CFM145a  
Canadian Installations1  
US Installations2  
A = Clearance above grade, veranda, porch,  
deck, or balcony  
12” (30 cm)  
12” (30 cm)  
B = Clearance to window or door that may be  
opened  
6” (15 cm) for appliances  
6” (15 cm) for appliances  
< 10,000 Btuh (3kW), 9”  
(23 cm) for appliances > 10,000  
Btuh (3kW) and < 50,000 Btuh  
(15kW), 12” (30 cm) for  
< 10,000Btuh (3kW), 12” (30 cm)  
for appliances > 10,000 Btuh (3kW) and  
< 100,000 Btuh (30kW), 36” (91 cm)  
for appliances > 100,000 Btuh (30kW)  
appliances > 50,000 Btuh (15kW)  
12” (305 mm) recommended to  
prevent window condensation  
C = Clearance to permanently closed window  
12” (305 mm) recommended to  
prevent window condensation  
D = Vertical clearance to ventilated soffit located  
above the terminal within a horizontal  
distance of 2’ (610mm) from the center  
line of the terminal  
18” (458 mm)  
18” (458 mm)  
E = Clearance to unventilated soffit  
F = Clearance to outside corner  
12” (305 mm)  
see next page  
12” (305 mm)  
see next page  
G = Clearance to inside corner (see next page)  
H = Clearance to each inside of center line  
extended above meter/regulator assembly  
see next page  
3’ (91 cm) within a height of 15’ (5 m)  
above the meter/regulator assembly  
see next page  
3’ (91 cm) within a height of 15’  
(5 m) above the meter/regulator  
assy  
I = Clearance to service regulator vent outlet  
3’ (91 cm)  
3’ (91 cm)  
J = Clearance to nonmechanical air supply inlet 6” (15 cm) for appliances < 10,000  
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for  
6” (15 cm) for appliances  
< 10,000 Btuh (3kW), 9”  
(23 cm) for appliances > 10,000  
Btuh (3kW) and < 50,000 Btuh  
(15kW), 12” (30 cm) for  
appliances > 50,000 Btuh (15kW)  
3’ (91 cm) above if within 10  
feet (3 m) horizontally  
7’ (2.13 m)†  
other appliances  
appliances > 10,000 Btuh (3kW) and  
< 100,000 Btuh (30kW), 36” (91cm)  
for appliances > 100,000 Btuh (30kW)  
K = Clearance to a mechanical air supply inlet  
6’ (1.83 m)  
L = Clearance above paved sidewalk or paved 7’ (2.13 m)†  
driveway located on public property  
M = Clearance under veranda, porch, deck or  
balcony  
12” (30 cm)‡  
12” (30 cm)‡  
N = Clearance above a roof shall extend a minimum of 24” (610 mm) above the highest point when it passes through the roof  
surface, and any other obstruction within a horizontal distance of 18” (450 mm).  
1 In accordance with the current CSA-B149 Installation Codes  
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes  
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and  
serves both dwellings  
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:  
NOTE: 1. Local codes or regulations may require different clearances.  
2. The special venting system used on Direct Vent fireplaces are certified as part of the appliance, with clearances tested and  
approved by the listing agency.  
10  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Termination Clearances  
Termination clearances for buildings with combustible and noncombustible exteriors.  
Inside Corner  
Recessed Location  
Outside Corner  
D
B =  
Combustible  
6"(152mm)  
C
C
A =  
E
Combustible  
6"(152mm)  
A
Noncombustible  
2"(50mm)  
V
V
Noncombustible  
2"(50mm)  
V
B
Balcony -  
Balcony -  
with no side wall  
with perpendicular side wall  
C = Maximum depth of 48"  
(1219mm) for recessed  
location.  
H
G
V
V
D = Minimum width for back wall  
of a recessed location.  
Combustible 38"(965mm)  
Noncombustible 24"(610mm)  
J
Combustible &  
Noncombustible  
G =  
Combustible &  
Noncombustible  
12"(305mm)  
E = Clearance from corner in  
recessed location.  
H = 24"(610mm)  
Combustible 6"(152mm)  
Noncombustible 2"(50mm)  
J = 20"(508mm)  
584-15  
Fig. 8 Termination clearances.  
General Information Assembling Vent Pipes  
* Be sure the vent is actually crushed before proceed-  
ing. Apply a tug to be sure the vent will not slip off the  
collars.  
Canadian Installations:  
Venting system must be installed in accordance with the  
current CSA-B149.1 installation code.  
Repeat process with 7” flex vent pipe. The same proce-  
dure must be performed on the vent side.  
USA Installations:  
The venting system must conform with local codes and/  
or the current National Fuel Gas code ANSI Z223.1/  
NFPA 54.  
Only venting components manufactured by CFM Corpo-  
ration can be used in Direct Vent systems.  
Hose Clamp  
Apply High Tempera-  
ture Sealant  
Flex Vent Pipes  
Before joining the flex vent pipe to the unit, apply a  
bead of high temperature sealant* (provided) to the 4”  
pipe exiting the fireplace. Secure flex vent pipe in place  
with a hose clamp (provided).  
FP1471a  
*Be sure the flex pipe overlaps at least 1” (25 mm) onto  
the collars of the fireplace and termination. If the ter-  
mination has an internal bead, be sure to overlap and  
secure 1” (25 mm) past the bead.  
Fig. 9 Apply high temperature sealant to 4” and 7” pipes.  
11  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
15  
14  
13  
12  
11  
10  
9
Twist Lock Pipes  
When using CFM Corporation twist-lock pipe, it is not  
necessary to use sealant on the joints. The only areas  
of the venting system that need to be sealed with high  
temperature silicone sealant are the sliding joint of any  
telescopic vent section used in the system.  
To join the twist lock pipes together, simply align the  
beads of the male end with the grooves of the female  
end, then while bringing the pipe together, twist the pipe  
until the flange on the female end contacts the external  
flange on the male end. It is recommended that you  
secure the joints with three (3) sheet metal screws,  
however this is not mandatory with twist lock pipe.  
To make it easier to assemble the joints we suggest  
putting a lubricant (Vaseline or similar) on the male end  
of the twist lock pipe prior to assembly.  
eg: A  
Male End  
Female End  
8
7
eg: B  
6
5
4
3
TWL100  
Screw Holes  
Fig. 10 Twist-lock pipe joints.  
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20  
Horizontal dimension from the outside face of the  
wall to the center of the fireplace vent flange  
36CDVR Venting  
How to Use the Vent Graph  
Sidewall vent graph showing the relationship between vertical  
and horizontal dimensions for a Direct Vent flue system.  
The vent chart should be read in conjunction with the  
following vent installation instructions to determine the  
relationship of the vertical and horizontal dimensions of  
the vent system.  
Fig. 11 Sidewall venting graph. (Dimensions in feet)  
Rear Wall Venting Applications  
* Exterior Outside Wall  
7” (178 mm) to 13” (330 mm)  
From Rear of Unit *  
1. Determine the height of the center of the horizontal  
vent pipe exiting through the outer wall. Using this  
dimension on the Sidewall Vent Graph (Fig. 11)  
locate the point intersecting with slanted graph line.  
When installed as a rear vent unit this appliance may  
be vented directly to a termination located on the rear  
wall behind the appliance.  
2. From the point of this intersection, draw a vertical  
line to the bottom of the graph.  
3. Select the indicated dimension, and position the  
fireplace in accordance with same.  
Only CFM Corporation venting components are  
approved to be used in these applications. (Refer to  
“Venting Components” listed for different installation  
requirements)  
Example A:  
If the vertical dimension from the floor of the  
fireplace is 11’ (3.4 m) the horizontal run to the face  
of the outer wall must not exceed 14’ (4.3 m).  
The maximum straight horizontal distance be-  
tween the rear of the appliance and the outside  
face of the rear wall is 13” (330 mm). The mini-  
mum is 7” (178 mm). (Fig. 12)  
Example B:  
If the vertical dimension from the floor of the unit is  
7’ (2.14 m), the horizontal run to the face of the outer  
wall must not exceed 8¹⁄₂’ (2.6 m).  
Minimum clearances between vent pipe and com-  
bustible materials are as follows:  
Top - 1” (25 mm)  
Sides - 1” (25 mm)  
Bottom - 1” (25 mm)  
12  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
13"  
(330 mm)  
Max.  
Bend Tab  
Top View  
Straight Venting  
FP1598  
Fig. 12 Rear vent applications.  
Firestop  
FP1600  
Rear Wall Installation  
Twist Lock Pipe  
Fig. 14 Install firestop.  
STEP 5  
STEP 1  
Twist the termination collar so it locks onto fireplace col-  
lars. Run screw through tab to keep collar from turning.  
(Fig. 15)  
Locate vent opening on the wall. To locate hole center  
consult with appropriate fireplace dimensions, Page 4.  
Frame as shown below.  
STEP 6  
Combustible Walls (Fig. 13): Cut a 9³⁄₈”H x 9³⁄₈” W  
(240 x 240 mm) hole through the exterior wall and  
frame as shown.  
Slide fireplace into position.  
STEP 7  
From the outside of the house, slide the termination  
onto the collars.  
Noncombustible Walls (Fig. 13): Hole opening must  
be 7¹⁄₂” (190 mm) in diameter.  
STEP 8  
Vent Opening for Combustible Wall  
Secure the termination to the house with the four (4)  
screws provided.  
9³⁄₈”  
(240 mm)  
Framing  
Detail  
Finished  
Wall  
9³⁄₈”  
(240 mm)  
Secure with Screw  
Vent Termination  
Fireplace Hearth  
C
L
Opening for Noncombustible Wall  
22”  
(559 mm)  
7¹⁄₂”  
(190 mm)  
Firestop  
VO584-100  
Fig. 13 Locate vent opening on wall.  
STEP 2  
Install interior firestop as shown in Figure 14.  
STEP 3  
FP1005a  
Fig. 15 Side view of final unit location.  
Remove telescoping collar from termination.  
STEP 4  
Bend tab on outer casing up and insert collar onto fire-  
place collars. (Fig. 14)  
13  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Rear Wall Vent Installations -  
45° Flex Vent Pipe  
Termination  
Flex Section  
NOTE: Under no circumstances can ridged pipe or  
a rigid 45° elbow be used. The 7TCDV45KT must be  
used in a corner installation. The corner placement  
dimensions on Page 4 of the manual must be ad-  
hered to! Figures 16 & 18 show general installations.  
Refer to instructions below for a detailed description  
of installation.  
C
L
to Floor  
Appliance  
Collars  
29”  
(749 mm)  
1. Determine where the termination is to be in-  
stalled. Locate the center of the hole 29¹⁄₂”  
(749 mm) off the floor. (Fig. 16)  
NOTE: The location of the termination hole must be  
adhered to!  
FP1473  
2. Install the firestop as shown on Page 12.  
Fig. 16 Grasp the vent pipe close to the collar and bend to  
45° angle. Do not exceed 45°.  
3. Remove the flex vent and extend the flex vent out  
to its longest length.  
4. Bend the tab on the back of the fireplace up. (Fig.  
14)  
5. Insert the collar on the flex vent that has the twist  
lock embosses on it onto the collar of the fire-  
place. Twist the collar to “lock it” onto the fire-  
place. Run a screw through the tab and into the  
collar to secure the collar onto the fireplace.  
6. Bend the flex pipe up 90° as close to the fireplace  
as possible. (Fig. 17)  
7. Slide the fireplace partially into the corner and,  
while holding the vertical portion of the flex vent  
pipe, grab the exposed end collar and bend it  
down to the height of the opening in the wall.  
FP1604  
8. While pushing the unit in place, slide the collar  
through the firestop. NOTE: It may be necessary  
to trim some material off of the collar. The col-  
lar is made long to accommodate brick finished  
houses. (Fig. 19)  
Fig. 17 Bend flex pipe up 90° as close to fireplace as pos-  
sible.  
Corner  
Do Not Exceed  
Framing  
45° Bend  
9. Secure the collar in place by running a screw  
through the tab in the firestop and through the  
collar.  
10. Slide the termination into the collar and secure  
with the 4 screws provided. (Fig. 19)  
Termination  
FP1606  
Fig. 18 Rear view of corner installation.  
14  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Vertical Sidewall Applications  
Screw  
Since it is very important that the vent-  
ing system maintain its balance between  
the combustion air intake and the flue  
gas exhaust, certain limitations as to vent  
configurations apply and must be strictly  
adhered to.  
Screws  
Flex Vent  
Collar  
The Vent Graph shows the relationship between vertical  
and horizontal side wall venting and will help to deter-  
mine the various dimensions allowable.  
FP1605  
Fig. 19 Secure collar in place, slide termination into collar.  
Rear Wall Vent Application  
* Exterior Outside Wall  
20” - 32” (508 - 813 mm)  
From Rear of Unit *  
Minimum clearance between vent pipes  
and combustible materials is 1”(25 mm)  
on top, bottom and sides unless otherwise  
noted.  
When vent termination exits through foundations less  
than 20” below siding outcrop, the vent pipe must  
flush up with the siding. It is always best to locate the  
fireplace in such a way that minimizes the number of  
offsets and horizontal vent length.  
1. Determine where the termination is to be installed.  
(Fig. 20)  
2. Locate the hole 27¹⁄₄” (692 mm) off the floor. This  
is the center line of the termination. Refer to “Rear  
Wall Installation Twist Lock Pipe” section.  
The horizontal vent run refers to the total length of vent  
pipe from the flue collar of the fireplace to the face of  
the outer wall.  
Screw  
Screws  
Horizontal plane means no vertical rise exists on this  
portion of the vent assembly.  
The maximum horizontal vent run is 20 ft. (6.1 m)  
Flex Vent  
when the vertical vent rise is 7¹⁄₂ ft. (2.3 m). (Fig. 21)  
Collar  
27”  
(692 mm)  
The maximum number of 90° elbows per side wall  
installation is three (3).  
Maximum  
20 ft. (6.1m)  
Vertical Dimension  
20” - 32”  
(508 - 813 mm)  
7¹⁄₂’ Minimum When  
48"  
(1.2m)  
Horizontal Run is  
20’  
FP1605a  
12"  
(305mm)  
15 ft.  
(4572mm)  
Fig. 20 The centerline of the termination must be 27¹⁄₄”  
(692 mm) off the floor.  
3. Mount the flex pipe assembly to the fireplace collars  
and twist the collar that the flex pipe is attached to  
onto the fireplace.  
4. Once the collar is twisted onto the fireplace collar,  
secure with a screw through the tab. (Fig. 15)  
7.5'  
(2.3m)  
7TCDV90  
or  
7TDV90  
5. While sliding the fireplace into position, lift up the end  
of the flex pipe and slip it through the firestop. *Be  
careful not to extend the flex too much. The flex pipe  
needs to have an immediate rise before going hori-  
zontal. NOTE: Be careful not to distort the outer flex  
as this will affect the performance of the fireplace.  
CFM141  
Fig. 21 Maximum number of 90° elbows is three (3).  
If a 90° elbow is used in the horizontal vent run  
(level height maintained) the maximum horizontal  
vent length is reduced by 36” (914 mm). (Fig. 22)  
This does not apply if the 90° elbows are used to  
increase or redirect a vertical rise. (Fig. 23)  
6. Secure the collar to the firestop by bending the tab  
out on the firestop and running a screw through the  
tab and collar.  
7. From outside the house, slide the termination onto  
the collars sticking through the firestop.  
Example: According to the chart the maximum hori-  
zontal vent length in a system with a 7.5’ (2.3 m) ver-  
tical rise is 20’ (6 m) and if a 90° elbow is required in  
8. Secure the termination to the house with the four (4)  
screws provided. Be sure to seal around the termi-  
nation and house cladding.  
15  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
the horizontal vent it must be reduced to 17’ (5.2 m).  
In Figure 23 Dimension A plus B must not be greater  
than 17’ (5.2 m).  
Example:  
Elbow 1  
Elbow 2  
Elbow 3  
Elbow 4  
=
=
=
=
90˚  
45˚  
45˚  
90˚  
4
Maximum  
3' (914mm)  
Total angular variation = 270˚  
1 + 2 + 3 + 4 = 270o  
3
2
1
7TCDV90  
CFM142  
CFM132  
Fig. 22 Maximum horizontal vent run.  
7 ft.  
(2134 mm)  
Fig. 24 Maximum number of elbows.  
Only CFM Corporation venting components specifically  
approved and labelled for this fireplace may be used.  
10 ft.  
(3048 mm)  
90° Elbow = 3 ft.  
Vertical Sidewall Installation  
STEP 1  
Locate vent opening on the wall. It may be necessary  
to first position the fireplace and measure to obtain hole  
location. Depending on whether the wall is combustible  
or noncombustible, cut opening to size. (Fig. 25)  
A + B = 17 ft. (Max.)  
7 ft. 6 in.  
(2286 mm)  
For combustible walls first frame in opening.  
Combustible Walls (Fig. 25): Cut a 9³⁄₈”H x 9³⁄₈” W  
(240 x 240 mm) hole through the exterior wall and  
frame.  
CFM147  
Fig. 23 Maximum vent run with elbows.  
Noncombustible Walls (Fig. 25): Hole opening must  
be 7.5” (190 mm) in diameter.  
The maximum number of 45° elbows permitted per  
side wall installation is two (2). These elbows can be  
installed in either the vertical or horizontal run.  
Vent Opening for Combustible Wall  
9³⁄₈”  
(240mm)  
For each 45° elbow installed in the horizontal run,  
the length of the horizontal run MUST be reduced by  
18” (45 cm). This does not apply if the 45° elbows  
are installed on the vertical part of the vent system.  
9³⁄₈”  
(240mm)  
The maximum number of elbow degrees in a system  
is 270°. (Fig. 24)  
•IMPORTANT• Minimum clearance between vent  
pipes and combustible materials is one (1”) inch (25 mm)  
on bottom, sides and top.  
Framing Detail  
Fireplace Hearth  
Twist Lock Vent Starter Kit 7TCRVT, plus  
Elbow 7TCDV90 must be used in Vertical  
Sidewall installations.  
Opening for Noncombustible Wall  
Canadian & USA Installations:  
7¹⁄₂”  
(190mm)  
The venting system must conform with local codes, or  
in the absence of local codes, with National Fuel Gas  
Code, ANSI Z223.1/NFPA 54 - latest edition, or CSA  
B149.1 Installation Code.  
VO584-100  
Fig. 25 Locate vent opening on wall.  
16  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
STEP 2  
STEP 5  
Slide venting component on collar of fireplace. Secure  
component to fireplace by running a screw (self-tap-  
ping) through tab & into outer casing. (Fig. 26)  
Guide the vent termination’s 4” and 7” collars into their  
respective vent pipes. Double check that the vent pipes  
overlap the collars by 2” (51 mm). Secure the termination  
to the wall with screws provided and caulk around the  
wall plate to weatherproof. (Fig. 29)  
STEP 3  
Measure the horizontal length requirement including a  
2” (51 mm) overlap, i.e. from the elbow to the outside  
wall finish plus 2”, or the distance required if installing a  
second 90° elbow. (Fig. 27)  
STEP 6  
Support the horizontal pipes every 36” (914 mm) with  
metal pipe straps. Make sure that the horizontal vent  
pipe is installed on a level horizontal plane.  
X
High  
Temperature Sealant  
Ensure Pipes are  
Concentric  
7TCDV90  
CFM143a  
Fig. 26 Always start vertical run with 7TCDV90 on 36CDVR  
unts.  
CFM137  
X
Always install hori-  
zontal venting on a  
level plane.  
Fig. 28 Apply high temperature sealant.  
X
X
CFM136  
Fig. 27 Measure horizontal length including 2” overlap.  
STEP 4  
CFM138  
Use appropriate length of pipe section - telescopic or  
fixed - and install the horizontal vent sections. A starter  
section of pipe which goes through the wall is packaged  
with the 7TCRVT kit, and can be cut to suit if necessary.  
(Fig. 28)  
Fig. 29 Horizontal length requirement.  
STEP 7  
Re-check the fireplace to make sure that it is levelled,  
properly positioned, and nailed or screwed to the floor.  
If applied, the fireplaces adjustable frame drywall strips  
(nailing flanges) should be fastened. Refer to “Framing  
& Finishing”.  
Sealing vent pipe and firestop gaps with  
high temperature sealant will restrict cold  
air being drawn in around fireplace.  
17  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Do not back fill around snorkel. A  
clearance of at least 4” (102 mm) must be  
maintained between the snorkel and the  
soil.  
Below Grade Installations  
When it is not possible to meet the required vent ter-  
minal clearances of 12” (305 mm) above grade level  
a snorkel vent kit #7TDVSNORK is required. It allows  
installation depth of down to 7” (178 mm) below grade  
level. The 7” is measured from the center of the hori-  
zontal vent pipe as it penetrates through the wall.  
If the foundation is recessed, use recess brackets (not  
supplied) for securing lower portion of the snorkel.  
Fasten brackets to wall first, then secure to snorkel  
with self drilling #8 x 1/2 sheet metal screws. It will be  
necessary to extend vent pipes out as far as protruding  
wall face. (Fig. 31)  
If venting system is installed below  
ground, we recommend a window well with  
adequate and proper drainage.  
Ensure sidewall venting clearances are observed.  
The maximum horizontal run with 24”  
vertical rise is 36” (914 mm) from the  
back of the fireplace to the face of the  
exterior wall. See vent graph (Page 12) for  
extended horizontal run if the vertical rise  
exceeds 24” (610 mm).  
Snorkel  
Foundation Recess  
Wall Screws  
Recess Brackets  
1. Establish vent hole through the wall. (Fig. 13)  
Watertight Seal  
Sheet Metal  
Around Pipe  
2. Remove soil to a depth of approximately 16”  
(406mm) below base of snorkel. Install window  
well (not supplied). Refill hole with 12” (305 mm) of  
coarse gravel leaving a clearance of approximately  
4” (102 mm) below snorkel. (Fig. 30)  
Screws  
BG401  
Fig. 31 Snorkel installation, recessed foundation.  
Vertical Through-the-Roof Applications  
3. Install vent system. See Page 12, Steps 2 through 5.  
4. Ensure a watertight seal is made around the vent  
pipe coming through the wall.  
5. Apply high temperature sealant caulking (supplied)  
around the 4” and 7” snorkel collars.  
6. Slide into the vent pipe and secure to the wall.  
7. Level the soil to maintain a 4” (102 mm) clearance  
below snorkel. (Fig. 30)  
This Gas Fireplace has been approved for:  
1. Vertical installations up to 40’ (12 m) in height. Up to  
10’ (3 m) horizontal vent run can be installed within  
the vent system using a maximum of three 90°  
elbows.  
7TDVSNORK  
(Snorkel)  
Maximum  
10’  
(3 m)  
Firestop  
4” (102mm)  
Clearance  
Min.  
7” Pipe  
Minimum  
8’ (2.4 m) /  
Maximum  
40’ (12 m) Vertical  
Rise  
Window  
Well  
24" (610mm)  
Minimum*  
Pipe Straps Every  
3’ (914 mm)  
Gravel  
Drain  
Foundation Wall  
CFM148  
Fig. 32 Support straps for horizontal runs.  
*A minimum of 24” (608mm)  
vertical pipe must be installed  
when using 7TDVSNORK Kit.  
2. Up to two 45° elbows may be used within the  
horizontal run. For each 45° elbow used on the  
horizontal level the maximum horizontal length must  
be reduced by 18” (457 mm).  
BG400  
Fig. 30 Below grade installation.  
18  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Example: Maximum horizontal length  
Attic Insulation  
Shield  
0 x 45° elbows = 10’ (3 m)  
1 x 45° elbows = 8¹⁄₂’ (2.6 m)  
2 x 45° elbows = 7’ (2.1 m)  
3. A minimum of an 8’ vertical rise.  
4. Two sets of 45° elbows offsets within these vertical  
installations. From 0 to a maximum of 8’ (2.4 m) of  
vent pipe can be used between elbows. (Fig. 33)  
Joist  
5. 7DVCS must be used to support offsets. (Fig. 33)  
This application will require that you first determine  
the roof pitch and use the appropriate 7DVSKV (A, B  
or F). (Refer to Venting Components List, Page 27)  
Ceiling  
11"  
Installation  
Upper Floor  
11"  
Max.  
8’  
(2.4 m)  
Joist  
Typical  
Ceiling  
Support  
45°  
Firestop Spacer  
Nails (4)  
50’  
(15 m)  
Max.  
8’  
(2.4 m)  
Application  
CFM100  
Fig. 34 Place firestop spacer(s) and secure.  
45°  
If there is room above ceiling level,  
firestop spacer must be installed on both  
the bottom and the top side of the ceiling  
joists. If an attic is above ceiling level a  
7DVAIS (Attic Insulation Shield) must be  
installed. (Fig. 34)  
Typical Roof  
Support Ap-  
plication  
7. Install roof support (Fig. 35 & 36) and roof flashing  
making sure upper flange is below the shingles. (Fig.  
35)  
8. Install appropriate pipe sections until the venting is  
above the flashing. (Fig. 35)  
Typical Offset Installation  
FP1021  
Fig. 33 Typical vertical roof applications.  
The enlarged ends of the vent section  
always face downward. (Fig. 35)  
Vertical Through-the-Roof Installation  
1. Locate your fireplace.  
2. Plumb to center of the (4”) flue collar from ceiling  
above and mark position.  
3. Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).  
4. Proceed to plumb for additional openings through  
the roof. In all cases, the opening must provide a  
minimum of 1 inch clearance to the vent pipe, i.e.,  
the hole must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm).  
3 #5 Sheet Metal  
Screws per Joint  
Sealant  
Storm Collar  
5. Place fireplace into position.  
6. Place firestop(s) #7DVFS or Attic Insulation Shield  
#7DVAIS into position and secure. (Fig. 34)  
TWL101a  
Fig. 35 Roof flashing.  
19  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Vent  
36CDVT Vertical Venting  
Termination  
Roof  
How to Use the Vent Graph  
Storm Collar  
2’ Min.  
The vent chart should be read in conjunction with the  
following vent installation instructions to determine the  
relationship of the vertical and horizontal dimensions of  
the vent system.  
Roof Flash-  
ing  
Roof Support  
Attic Insulation  
Shield  
Attic  
Insulation  
Joists  
50’  
(15 m)  
1. Determine the height of the center of the horizontal  
vent pipe exiting through the outer wall. Using this  
dimension on the Sidewall Vent Graph (Fig. 38),  
locate the point intersecting with the slanted graph  
line.  
Joists  
2. From the point of this intersection, draw a vertical  
line to the bottom of the graph.  
3. Select the indicated dimension, and position the  
fireplace in accordance with same.  
Example A:  
If the vertical dimension from the floor of the fireplace  
is 11’ (3.4 m) the horizontal run to the face of the outer  
wall must not exceed 14’ (4.3 m).  
Example B:  
FP1022  
If the vertical dimension from the floor of the unit is 7’  
(2.14 m), the horizontal run to the face of the outer wall  
must not exceed 8¹⁄₂’ (2.6 m).  
Fig. 36 Typical straight-up installation.  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
15  
14  
13  
Min.  
2' (610 mm)  
FP1185  
Fig. 37 Minimum termination to roof clearance.  
9. Install storm collar and seal around the pipe.  
10. Add additional vent lengths for proper height. (Fig  
37)  
12  
eg: A  
11  
10  
9
11. Apply high temperature sealant to 4” and 7” collars  
of vertical vent termination and install.  
8
7
eg: B  
6
5
4
3
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20  
Horizontal dimension from the outside face of the  
wall to the center of the fireplace vent flange  
Sidewall vent graph showing the relationship between vertical  
and horizontal dimensions for a Direct Vent flue system.  
Fig. 38 Sidewall venting graph. (Dimensions in feet)  
20  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
3'  
Vertical Sidewall Applications  
(914mm)  
Since it is very important that the vent-  
ing system maintain its balance between  
the combustion air intake and the flue  
gas exhaust, certain limitations as to vent  
configurations apply and must be strictly  
adhered to.  
The vent graph showing the relationship between verti-  
cal and horizontal side wall venting will help to deter-  
mine the various dimensions allowable.  
Minimum clearance between vent pipes and  
combustible materials is one 1” (25 mm)  
on top, bottom and sides unless otherwise  
noted.  
FP1237  
Fig. 40 Maximum horizontal vent run.  
When the vent termination exits through foundations  
less than 20” (508 mm) below siding outcrop, the vent  
pipe must flush up with the siding.  
A
B
It is always best to locate the fireplace in such a way  
that minimizes the number of offsets and horizontal  
vent length of vent pipe from the flue collar of the fire-  
place to the face of the outer wall.  
7.5'  
(2.3m)  
1 x 90° elbow in horizontal plane = 3’ (914mm)  
A + B = 17' (5.2m) Max.  
20' (6m)  
FP1238  
Pipe  
Straps Every  
3’ (914mm)  
Fig. 41 Maximum vent run with elbows.  
The maximum number of 45° elbows permitted per  
side wall installation is two (2). These elbows can be  
installed in either the vertical or horizontal run.  
Pipe Straps  
Every 3’ (914mm)  
Firestop/Zero  
Clearance Sleeve  
For each 45° elbow installed in the horizontal run,  
the length of the horizontal run MUST be reduced by  
18” (457 mm). This does not apply if the 45° elbows  
are installed on the vertical part of the vent system.  
FP1012  
Fig. 39 Support straps for horizontal runs.  
Horizontal plane means no vertical rise exists on this  
portion of the vent assembly.  
The maximum number of elbow degrees in a system  
is 270°. (Fig. 42)  
The maximum number of 90° elbows per side wall  
installations is three (3).  
If a 90° elbow is fitted directly onto the fireplace  
flange the maximum horizontal vent run before the  
termination or a vertical rise is 36” (914 mm).  
If a 90° elbow is used in the horizontal vent run  
(level height maintained) the maximum horizontal  
vent length is reduced by 36” (914 mm). This does  
not apply if the 90° elbows are used to increase or  
redirect a vertical rise.  
Example: According to the chart the maximum  
horizontal vent length in a system with a 7.5’ (2.3 m)  
vertical rise is 20’ (6 m) and if a 90° is required in  
the horizontal vent it must be reduced to 17’ (5.2 m).  
In Figure 41, Dimension A plus B must not be  
greater than 17’ (5.2 m).  
21  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
STEP 2  
Example:  
Place fireplace into position. (Fig. 44) Measure the verti-  
cal height (X) required from the base of the flue collars  
to the center of the wall opening.  
Elbow 1  
Elbow 2  
Elbow 3  
Elbow 4  
=
=
=
=
90°  
45°  
45°  
90°  
4
Total angular variation = 270°  
1 + 2 + 3 + 4 = 270°  
X
3
2
1
FP1240  
Fig. 44 Vertical height requirement.  
FP1239  
STEP 3  
Fig. 42 Maximum number of elbow degrees.  
Vertical Sidewall Installations  
STEP 1  
Using appropriate venting component(s) attach to  
fireplace with three (3) screws. (Fig. 45) Follow with the  
installation of the inner and outer elbow. Again secure  
joints with three (3) sheet metal screws.  
Locate vent opening on the wall. It may be necessary  
to first position the fireplace and measure to obtain hole  
location. Depending on whether the wall is combustible  
or noncombustible, cut opening to size. (Fig. 43)  
STEP 4  
Measure the horizontal length requirement including  
a 2” (51 mm) overlap, ie from the elbow to the outside  
wall face plus 2” (51 mm) (or the distance required if  
installing a second 90° elbow). (Fig. 45)  
For combustible walls first frame in opening.  
Combustible Walls: (Fig. 43) Cut a 9³⁄₈”H x 9³⁄₈”W (240  
x 240 mm) hole through the exterior wall and frame as  
shown.  
Always install horizontal venting on a level  
plane.  
Noncombustible Walls: (Fig. 43) Hole opening must  
be 7¹⁄₂” (190 mm) in diameter.  
X
Vent Opening for Combustible Wall  
9³⁄₈”  
(240mm)  
Framing  
Detail  
9³⁄₈”  
(240mm)  
Fireplace Hearth  
Opening for Noncombustible Wall  
FP1241  
7¹⁄₂”  
(190mm)  
Fig. 45 Horizontal length requirement.  
VO584-100  
Fig. 43 Locate vent opening on wall.  
22  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
STEP 5  
Use appropriate length of pipe sections - telescopic or  
fixed - and install the horizontal vent sections. The sec-  
tions which go through the wall are packaged with the  
starter kit, and can be cut to suit if necessary. (Fig. 46)  
Sealing vent pipe and firestop gaps with  
high temperature sealant will restrict cold  
air being drawn in around fireplace.  
FP1243  
Fig. 47 Apply high temperature sealant to collars or termina-  
tions.  
Below Grade Installations  
When it is not possible to meet the required vent ter-  
minal clearances of 12” (305 mm) above grade level a  
snorkel vent kit is recommended. It allows installation  
depth of down to 7” (178 mm) below grade level. The  
7” is measured from the center of the horizontal vent  
pipe as it penetrates through the wall.  
FP1242  
If venting system is installed below  
ground, we recommend a window well with  
adequate and proper drainage.  
Fig. 46 Through the wall.  
STEP 6  
Guide the vent terminations 4” and 7” collars into their  
respective vent pipes. Double check that the vent pipes  
overlap the collars by 2” (51mm). Secure the termina-  
tion to the wall with screws provided and caulk around  
the wall plate to weatherproof. (Fig. 23) As an alterna-  
tive to screwing the termination directly to the wall you  
may also use expanding plugs or an approved exterior  
construction adhesive. You may also attach the termi-  
nation with screws through the inner body into the 4”  
(102 mm) vent pipe however for this method you must  
extend the 4” (102 mm) pipe approximately 6” (152 mm)  
beyond the outer face of the wall.  
Ensure sidewall venting clearances are observed.  
If installing a snorkel a minimum 24” (610 mm) vertical  
rise is necessary. The maximum horizontal run with  
the 24” (610 mm) vertical pipe is 36” (914 mm). This  
measurement is taken from the collar of the fireplace  
(or transition elbow) to the face of the exterior wall.  
Refer to the Sidewall Vent Graph for extended  
horizontal run if the vertical rise exceeds 24” (610 mm).  
1. Establish vent hole through the wall. (Fig. 43)  
2. Remove soil to a depth of approximately 16” (406  
mm) below base of snorkel. Install drain pipe. Install  
window well (not supplied). Refill hole with 12”  
(305mm) of coarse gravel leaving a clearance of ap-  
proximately 4” (102 mm) below snorkel. (Fig. 48)  
Support horizontal pipes every 3’ (914 mm) with metal  
pipe straps. Make sure the horizontal vent pipe is in-  
stalled on a level horizontal plane.  
3. Install vent system.  
4. Ensure a watertight seal is made around the vent  
pipe coming through the wall.  
5. Apply high temperature sealant caulking (supplied)  
around the 4” and 7 “ snorkel collars.  
6. Slide the snorkel into the vent pipes and secure to  
the wall.  
7. Level the soil to maintain a 4” (102 mm) clearance  
below snorkel. (Fig. 48)  
23  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Vertical Through-the-Roof Applications  
Zero Clearance Sleeve  
(if required)  
Screws  
7TDVSNORK  
(Snorkel)  
This Gas Fireplace has been approved for:  
Firestop  
7” Pipe  
Vertical installations up to 40’ (12 m) in height. Up  
to a 10’ (3 m) horizontal vent run can be installed  
within the vent system using a maximum of two 90°  
elbows. (Fig. 50)  
4” (102mm)  
Clearance  
Min.  
Window  
Well  
24” (610mm)  
Minimum*  
Gravel  
Drain  
Foundation Wall  
Max. 10' (3m)  
*A minimum of 24” (610mm) ver-  
tical pipe must be installed when  
using the 7TDVSNORK Kit.  
Max. Height  
40' (12m)  
*The 22” (559mm) vertical rise  
(center to center) of the snorkel  
may be included for calculationof  
max. horizontal run.  
Min. Height  
7' (2.3m)  
BG402  
Fig. 48 Below grade installation.  
Do not back fill around snorkel. A clearance  
of at least 4” (102 mm) must be maintained  
between snorkel and the soil.  
Pipe Straps Every  
3’ (914mm)  
If the foundation is recessed, use recess brackets (not  
supplied) for securing lower portion of the snorkel.  
Fasten brackets to wall first, then secure to snorkel  
with self drilling #8 x 1/2 sheet metal screws. It will be  
necessary to extend vent pipes out as far as protruding  
wall face. (Fig. 49)  
FP1244  
Fig. 50 Support straps for horizontal runs.  
Up to two 45° elbows may be used within the  
horizontal run. For each 45° elbow used on the  
horizontal level the maximum horizontal length must  
be reduced by 18” (457 mm).  
Snorkel  
Foundation Recess  
Wall Screws  
Example: Maximum horizontal length  
0 x 45° elbows = 10’ 93 m)  
Recess Brackets  
1 x 45° elbows = 8¹⁄₂’ (2.6 m)  
2 x 45° elbows = 7’ (2.1 m)  
Watertight Seal  
Sheet Metal  
Around Pipe  
Screws  
A minimum of an 8’ (2.4 m) vertical rise.  
Two sets of 45° elbows offsets within these vertical  
installations. From 0 to a maximum of 8’ (2.m) of  
vent pipe can be used between elbows. (Fig. 51)  
7DVCS must be used to support offsets. (Fig. 53)  
This application will require that you first determine  
the roof pitch and use the appropriate starter kit.  
(Refer to Venting Components List)  
BG401  
Fig. 49 Snorkel installation, recessed foundation.  
The minimum height of the vent above the highest  
point of penetration through the roof is 2’ (610 mm).  
(Fig. 55)  
24  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Attic Insulation  
Shield  
Max. 8' (2.4m)  
Joist  
4
1 + 2 + 3 + 4 = 270°  
Upper Floor  
Joist  
11"  
Ceiling In-  
stallation  
11"  
3
2
Firestop Spacer  
Nails (4)  
1
CFM100a  
Fig. 52 Place firestop spacer(s) and secure.  
FP1245  
Fig. 51 Typical offset application.  
Typical Roof Support  
Typical Ceiling Sup-  
port Application  
Application  
Vertical Through-the-Roof Installation  
CFM110  
Fig. 53 Roof and ceiling supports.  
1. Locate your fireplace.  
2. Plumb to center of the (4” (102 mm) flue collar from  
ceiling above and mark position.  
3. Cut opening equal to 9³⁄₈” x 9³⁄₈” (240 x 240 mm).  
4. Proceed to plumb for additional openings through the  
roof. In all cases, the opening must provide a minimum  
of 1” (25 mm) clearance to the vent pipe, i.e., the hole  
must be at least 9³⁄₈” x 9³⁄₈” (240 x 240 mm).  
#8 Sheet Metal Screws  
(3 per joint)  
Sealant  
Storm Collar  
5. Place fireplace into position.  
6. Place firestop(s) #7DVFS or Attic Insulation Shield  
#7DVAIS into position and secure. (Fig. 52)  
7. Install roof support (Fig. 53) and roof flashing making  
sure upper flange of flashing is below the shingles.  
(Fig. 53)  
TWL101a  
Fig. 54 Roof flashing.  
8. Install appropriate pipe sections until the venting is  
above the flashing. (Fig. 53)  
10. Add additional vent lengths for proper height. (Fig.  
55)  
9. Install storm collar and seal around the pipe.  
11. Apply high temperature sealant to 4” and 7” collars.  
25  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
If there is a room above ceiling level,  
firestop spacer must be installed on both  
the bottom and the top side of the ceiling  
joists. If an attic is above ceiling level a  
7DVAIS (Attic Insulation Shield) must be  
installed.  
Min.  
2' (610 mm)  
The enlarged ends of the vent section  
always face downward. (Fig. 54)  
CFM190  
Fig. 55 Minimum termination to roof clearance.  
26  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Venting Components  
20010581 - Straight Out the Back Termination  
10001953 - Through-the-Wall Termination  
(for other than straight out the back on rear vent)  
Starter Kit -  
Model 7TCRVT: Straight thru Rear Vent for 7” - 13” Vent  
Application  
Model 7TCD45KT: Vent Kit for 45° Installation or 13” - 32”  
Rear Vent application  
Starter Kit* - Model 7TDVSKV - Vertical Venting  
for 7TDVSKV-A order 1/12 to 6/12 roof pitch  
for 7TDVSKV-B order 7/12 to 12/12 roof pitch  
for 7TDVSKV-F order flat roof  
Starter Kit for Below Grade Installation  
Model 7TDVSKS -Snorkel Kit (Twist Lock Pipe)  
Model 7FDVSKS -Snorkel Kit (Flex Vent Pipe)  
*NOTE: Must order a 7TCDV90 elbow  
for rear vent to vertical application only.  
90o Elbow  
7TCDV90 - For Rear to Vertical  
7TDV90 - For Extended Run  
Telescopic vent sections  
7TDVP1117 -11” to 17” adjustable length  
7TDVP3567 -35” to 67” adjustable length  
Pipe sections for vertical or horizontal venting  
Model 7TDVP8”  
Model 7TDVP12”  
Model 7TDVP24”  
Model 7TDVP36”  
Model 7TDVP48”  
-
-
-
4 per box  
4 per box  
4 per box  
Firestop Spacer  
Model 7DVFS  
Attic Insulation Shield  
Model 7DVAIS  
Vertical/Horizontal Combination Offset Support  
Model 7DVCS  
27  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Operating Instructions  
Glass Information  
Only glass approved by CFM Corporation  
should be used on this fireplace.  
The use of any non-approved replacement glass will  
void all product warranties.  
Care must be taken to avoid breakage of the glass.  
Do not operate appliance with glass front  
Lower Clamps  
removed, cracked or broken.  
Replacement glass (complete with gasket) is  
available through your CFM Corporation dealer  
and should only be installed by a licensed  
qualified service person.  
Window  
Frame  
Assembly  
Window  
Frame  
Pull Clamp  
Hook  
Assembly  
Louvre Removal  
Push  
Clamp  
Handle  
The top louvre panel  
is removed by lifting  
FP1228  
Fig. 57 Window frame assembly removal.  
2.  
the panel vertically and  
pulling it away from the  
appliance. (Fig. 56) The  
lower access door is  
removed in the same  
manner.  
Glass Cleaning  
Louvre  
1.  
It is necessary to periodically clean glass. During start-  
up condensation, which is normal, forms on the inside  
of the glass. This condensation causes lint, dust and  
other airborne particles to cling to glass surface.  
Also initial paint curing may deposit a slight film on  
the glass. It is therefore recommended the glass be  
cleaned two or three times with a non-ammonia based  
household cleaner and warm water (We recommend  
gas fireplace glass cleaner) within the first few weeks of  
operation.  
Glass Panel  
FP1602  
Fig. 56 Remove top louvre  
assembly.  
Window Frame Assembly Removal  
After the initial cleaning process the glass should be  
cleaned two or three times during each operating  
season depending on the environment in the house.  
1. Turn the fireplace OFF (including the pilot)  
2. If the unit has been operating allow time for the  
components to cool.  
3. Remove the top louvre assembly.  
4. Remove the lower louvre panel.  
Clean glass after first two weeks of  
operation.  
5. Release the two clamps securing the lower edge of  
the window frame assembly by pulling down on the  
handles. (Fig. 57)  
6. Tilt the window frame assembly out slightly at the  
bottom, lift the window frame assembly up and away  
from the fireplace.  
Do not clean glass when hot.  
Do not use abrasive cleaners.  
Do not strike or slam the glass.  
7. To replace the window frame assembly reverse  
the procedure.  
28  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Logs  
The 36CDV logs are shipped in place. If a log is bro-  
ken, refer to the replacement parts list for a replace-  
ment. Figure 58 shows where the logs are secured to  
the fireplace.  
Log Rear  
The log rear is  
secured to the back  
of the fireplace.  
Log Front  
The log front is se-  
cured to the bottom  
of the fireplace.  
Ceramic  
Hearth  
Ember  
LG441  
Fig. 58 36CDV logs.  
Flame Characteristics  
Flame & Temperature Adjustment  
It is important to periodically perform a visual check  
of the pilot and burner flames. Compare them to the  
illustrations. (Figs. 60 & 61)  
RN/RP & EN/EP Models  
For units equipped with “HI/LO” valves the flame  
adjustment is accomplished by rotating the “HI/LO”  
adjustment knob located near the center of the gas  
control valve. (Figs. 59)  
If the flame patterns appear abnormal contact a  
qualified service provider for service and adjustment.  
SIT 820 Valve  
SIT RN/RP  
Turn  
counterclockwise  
Turn clockwise  
to decrease  
to increase  
flame height  
flame height  
FP1541  
Fig. 59 Flame adjustment knob for SIT valve.  
Fig. 60 Correct pilot flame appearance.  
Yellow Flame  
Red Glow,  
Yellow Tips  
LG442  
Fig. 61 36CDV burner flame appearance.  
29  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Lighting and Operating Instructions  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING:If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
A. This heater has a pilot which must be lit manu-  
ally. When lighting the pilot follow these instruc-  
tions exactly.  
Follow the gas supplier’s instructions.  
If you cannot reach your gas supplier, call  
the Fire Department  
B. BEFORE LIGHTING smell all around the  
heater area for gas. Be sure to smell next to  
the floor because some gas is heavier than air  
and will settle on the floor.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will not  
push in or turn by hand, do not try to repair it, call a  
qualified service technician. Applying force or any  
attempted repair may result in a fire or explosion.  
D. Do not use this fireplace if any part has been under  
water. Immediately call a qualified service techni-  
cian to inspect the heater and to replace any part of  
the control system and any gas control which has  
been under water.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any fireplace  
Do not touch any electric switch  
Do not use any phone in your building  
Immediately call your gas supplier from a  
neighbor’s phone.  
Lighting Instructions  
1. STOP! Read the safety information above.  
2. Turn off all electrical power to the fireplace.  
3. For MN/MP/TN/TP appliances ONLY, go on to  
Step 4. For RN/RP appliances turn the ON/OFF  
switch to “OFF” position or set thermostat to  
lowest level.  
10. Push the control knob all the way in and hold.  
Immediately light the pilot by repeatedly depress-  
ing the piezo spark ignitor until a flame appears.  
Continue to hold the control knob in for about one  
(1) minute after the pilot is lit. Release knob and it  
will pop back up. Pilot should remain lit. If it goes  
out, repeat steps 5 through 8.  
4. Open control access panel.  
5. Push in gas control knob slightly and turn clock-  
wise  
to “OFF”.  
3/8" - 1/2"  
��  
2
F
Honeywell  
Euro SIT  
SIT NOVA  
If knob does not pop up when released, stop  
and immediately call your service technician or  
gas supplier.  
6. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you  
smell gas, STOP! Follow “B” in the safety infor-  
mation above. If you do not smell gas, go to the  
next step.  
7. Remove glass door before lighting pilot. (See  
Glass Frame Removal section).  
8. Visibly locate pilot by the main burner.  
9. Turn knob on gas control counterclockwise  
to “PILOT”.  
If after several tries, the pilot will not stay lit,  
turn the gas control knob to “OFF” and call your  
service technician or gas supplier.  
11. Replace glass door.  
12. Turn gas control knob to “ON” position.  
13. For RN/RP appliances turn the ON/OFF switch to  
“ON” position or set thermostat to desired setting.  
14. Turn on all electrical power to the fireplace.  
To Turn Off Gas to Fireplace  
1. Turn the ON/OFF switch to Off position or set  
the thermostat to lowest setting.  
3. Open control access panel.  
4. Push in gas control knob slightly and turn clock-  
2. Turn off all electric power to the fireplace if  
service is to be performed.  
wise  
to “OFF”. Do not force.  
5. Close control access panel.  
30  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Lighting and Operating Instructions  
For Fireplaces equipped with SIT822 Gas Valve (EN or EP)  
Warning:If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury and loss of life.  
FOR YOUR SAFETY READ THE FOLLOWING WARNINGS  
BEFORE LIGHTING THE APPLIANCE  
Follow the gas suppliers instructions.  
A. This fireplace is equipped with an ignition device  
which automatically lights the pilot. DO NOT try to  
light the pilot by hand.  
If you cannot contact your gas supplier call  
the Fire Department  
B. BEFORE OPERATING, smell all around the  
appliance area for gas. Be sure to smell next to  
the floor because some gas is heavier than the air  
and will settle on the floor.  
C. Use only your hand to push in or turn the gas control  
knob. Never use tools. If the knob will not push in  
or turn by hand do not try to repair it, call a qualified  
service technician. Force or attempting repair may  
result in a fire or explosion.  
What to do if you smell gas  
D. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician  
to inspect the appliance and replace any part of the  
control system and any gas control that has been  
under water.  
Do not try to light any appliance  
Do not operate any electrical switch.  
Do not use any phone in your building.  
Immediately call your gas supplier from a  
neighbor’s phone.  
Lighting Instructions  
1. STOP! Read the safety information above before  
5. Turn the remote switch, if used, OFF. Turn the  
wireless remote, if used, OFF.  
continuing.  
2. Turn off all electrical power to the appliance.  
6. Wait five (5) minutes to clear out any gas. Then  
smell for gas, including near the floor. If you smell  
gas STOP. Follow instructions B in the safety  
warnings above. If you do not smell gas go onto the  
next step.  
3. This appliance is equipped with an ignition device  
which automatically lights the pilot. DO NOT try to  
light the pilot by hand.  
4. Access the gas control by lowering the lower  
access door (louvre assembly).  
7. Close the access door.  
8. Turn ON all electrical power to the appliance.  
9. Turn remote switch or wireless remote to “ON”.  
10. If the appliance will not operate, follow the  
instructions TURNING OFF THE GAS TO THE  
APPLIANCE and call your service technician or  
gas supplier.  
HI  
Turning Off the Gas to the Appliance  
1/2” Gas Supply  
1. Turn the remote switch to the “OFF” position.  
2. Turn OFF all electrical power to the fireplace if  
service is required.  
1/2” NPT x 1/2” Flare Shut-Off  
Valve  
3/8” Flex Line  
(From Valve)  
3 Open the lower access panel.  
4. Turn the shut-off valve on the flexible gas line to  
the “OFF” position.  
Valve in the on position  
31  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Troubleshooting the Gas Control System  
SIT NOVA 820 MILLIVOLT VALVE  
NOTE: Before trouble shooting the gas control system, be sure external gas shut off is in the “On” position.  
WARNING: BEFORE DOING ANY GAS CONTROL SERVICE WORK, REMOVE GLASS FRONT.  
SYMPTOM  
POSSIBLE CAUSES  
CORRECTIVE ACTION  
1. Spark ignitor will not light  
A. Defective or misaligned  
electrode at pilot.  
Using a match, light pilot. If pilot lights, turn off  
pilot and push the red button again. If pilot will not  
light - check gap at electrode and pilot-should be  
1/8” to have a strong spark.  
B. Defective ignitor (Push Button)  
Push Piezo Ignitor Button. Check for spark at  
electrode and pilot. If no spark to pilot, and elec  
trode wire is properly connected, replace ignitor.  
2. Pilot will not stay lit after  
carefully following lighting  
instructions.  
A. Defective pilot generator  
(thermocouple), remote wall  
switch.  
Check pilot flame. Must impinge on thermo  
couple/thermopile. Note: this pilot burner assem  
bly utilizes both-a thermocouple and a thermopile.  
The thermocouple operates the main valve  
operation (On and Off). Clean and or adjust pilot for  
maximum flame impingement on thermopile and  
thermocouple.  
B. Defective automatic valve  
Turn valve knob to “Pilot”. Maintain flow to pilot;  
milivolt meter should read greater than 10 mV. If  
the reading is okay and the pilot does not stay on,  
replace the gas valve. Note: An interrupter block  
(not supplied) must be used to conduct this test.  
3. Pilot burning, no gas to  
main burner  
A. Wall switch or wires defective  
Check wall switch and wires for proper connec  
tions. Jumper wire accross terminals at wall  
switch, if burner comes on, replace defective wall  
switch. If okay, jumper wires across wall switch  
wires at valve, if burner comes on, wires are faulty  
or connections are bad.  
B. Thermopile may not be  
generating sufficient  
millivoltage.  
1. Be sure wire connections from thermopile at  
gas valve terminals are tight and thermopile is fully  
inserted into pilot bracket.  
2. One of the wall switch wires may be grounded.  
Remove wall switch wires from valve terminals if  
pilot now stays lit, trace wall switch wiring for  
ground. May be grounded to fireplace or gas  
supply.  
3. Check thermopile with millivolt meter. Take  
reading at thermopile terminals of gas valve.  
Should read 250-300 millivolts (minimum 150)  
while holding valve knob depressed in pilot  
position and wall switch “Off”. Replace faulty  
thermopile if reading is below specified minimum.  
C. Plugged burner orifice.  
Check burner orifices for debris and remove.  
D. Defective automatic valve  
operator.  
Turn valve knob to “On”, place wall switch to “On”  
millivolt meter should read greater than 100 mV. If  
the reading is okay and the burner does not come  
on, replace the gas valve.  
4. Frequent pilot outage  
problem.  
A. Pilot flame may be too low  
or blowing (high) causing the  
pilot safety to drop out.  
Clean and/or adjust pilot flame for maximum flame  
impingement on thermopile and thermocouple.  
B. Possible blockage of the vent  
terminal.  
Check the vent terminal for blockage (recycling the  
flue gases)  
32  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Fuel Conversion Instructions  
A
E
The conversion of this appliance from one  
gas to another must be carried out by an  
authorized service provider.  
B
C
1. Disconnect power to the unit and shut off the gas sup-  
ply.  
2. Remove window frame assembly.  
3. Carefully remove the logs & lava rock material.  
4. Remove the screws that are holding the burner hous-  
ing in place.  
O
FF  
P
L
O
T
O
D
5. Remove the burner housing assembly. Depending on  
the model of the appliance you may have to loosen  
the pilot bracket retaining screw/nut to allow the pilot  
and bracket assembly to tilt and give enough clear-  
ance to remove the burner housing assembly.  
6. Remove the main burner orifice and replace it with the  
orifice supplied in the conversion kit.  
F
FC107/108  
Fig. 62 Nova SIT820 Gas Valve.  
The procedure for converting from one gas to  
another is the same regardless of the initial  
gas used. The only variation is in the orifice  
sizes and component part numbers. Your  
authorized service provider will ensure the  
correct parts are used.  
7. SIT top Convertible Pilot  
Gently lift off the pilot hood from the pilot. (Do not re-  
move the spring clip holding the hood in place). Using  
a 5/32” Allen key, unscrew the exposed orifice. Insert  
the new orifice supplied in the kit, do not over tighten  
the orifice. Replace the pilot hood ensuring the index  
tab aligns with the notch on the hood.  
8. SIT 820 NOVA Gas Control Valve (Fig. 62)  
a. Using a Torx T20 or slotted screwdriver, remove  
and save the three pressure regulator mounting  
screws (A), pressure regulator tower (B) and  
diaphram (C).  
b. Ensure the rubber gasket (D) is properly positioned  
and install the new HI/LO pressure regulator to the  
valve using the new screws (E) supplied with the  
kit. Tighten screws securely. (Reference torque - 25  
in.LB)  
c. Install the enclosed identification label (F) to the  
valve body where it can be easily seen.  
9. Reassemble the fireplace in the reverse order, except  
for the window frame assembly. Leave this off until  
after the unit has been checked for leaks and the gas  
supply has been bled.  
10. After bleeding the gas line and checking for leaks with  
a soap solution, replace the window frame assembly.  
Fire up the unit, check for flame impingement on the  
logs, adjusting them if necessary. Check the manifold  
and supply pressures against the appliance specifica-  
tions.  
33  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Maintenance  
Burner and Burner Compartment  
To obtain proper operation, it is imperative that the pilot  
and burner’s flame characteristics are steady, not lifting  
or floating.  
It is important to keep the burner and the burner  
compartment clean. At least once per year the logs and  
lava rock/ember material should be removed and the  
burner compartment vacuumed and wiped out. Remove  
and refit the logs as per the instructions in this manual.  
Typically, the top 3/8” to 1/2” of the thermopile should  
be engulfed in the pilot flame. (Refer to Page 59, Figure  
60)  
To adjust pilot burner: (by qualified service technician)  
1. Remove pilot adjustment cap  
Always handle the logs with care as they  
are fragile and may also be hot if the  
fireplace has been in use.  
2. Adjust pilot screw to provide properly sized flame.  
3. Replace pilot adjustment cap.  
FK12 Fan Assembly  
The primary air shutter is set at factory and should  
only be adjusted, if necessary, by a qualified service  
technician.  
The fan unit requires periodic cleaning. At least once  
per month in the operating season open the lower  
louvre panels and wipe or vacuum the area around the  
fan to remove any build up of dust or lint.  
Cleaning the Standing  
Pilot Control System  
The burner and control system consist of:  
burner  
pilot assembly  
millivolt gas valve  
gas orifice  
thermopile  
Most of these components may require only an  
occasional checkup and cleaning and some may  
require adjustment. If repair is necessary, it should  
be performed by a qualified technician.  
1. Turn off pilot light at gas valve.  
2. Allow fireplace to cool if it has been operating.  
3. Remove window frame assembly. (Refer to Window  
Frame Assembly Removal section.)  
4. Remove logs.  
5. Vacuum burner compartment especially around  
orifice primary air openings.  
6. Visually inspect pilot. Brush or blow away any dust  
or lint accumulation.  
7. Reinstall logs.  
8. Ignite pilot - Refer to Lighting Instructions.  
9. Reinstall window frame assembly.  
34  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
2
1a  
8
12  
11  
10  
6a,b  
3
1b  
1c  
7
14a,b  
17  
15  
13  
23  
16  
19  
21  
26  
24  
25  
22  
20  
18  
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,  
without notice.  
CDV  
Ref. Description  
36CDV  
20010340  
20010341  
20010342  
20010312  
20010333  
72386  
10002268  
10002269  
20010203  
20010202  
10001296  
10002385  
20010162  
53373  
1a. Log Rear Assy  
1b. Log Middle Assy  
1c. Ceramic Hearth Ember  
2. Hood  
3. Burner Tube  
4. Orifice Burner - Natural (not shown)  
5a. Orifice Pilot - Natural (not shown)  
5b. Orifice Pilot - Propane (not shown)  
6a. PIlot Assy SIT - RN  
6b. Pilot Assy SIT - RP  
7. Pilot Tubing w/Fittings SIT  
8. Pilot Hood  
9. Manifold Tubing (not shown)  
10. Thermocouple - RN/RP  
11. Thermopile - RN/RP  
12. Electrode Ignitor w/Cable RN/RP  
13. Ignitor Piezo SIT 820 Valve  
14a. Valve SIT 820 - RN  
14b. Valve SIT 820 - RP  
51827  
10001297  
52464  
52677  
52678  
35  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
CDV (continued)  
Ref. Description  
36CDV  
15. Flexible Gas Line w/ON/Off Shut-Off Valve  
16. Fan Assy (FK12 Option)  
17. Electrical Cord (6 ft.)  
18. Door Assy  
19. Glass w/Gasket  
20. Gasket Glass  
21. Frame Window  
22. Clamp Frame Window  
23. Top Louvre Assy  
24. Bottom Louvre Assy  
25. ON/OFF Switch  
20002500  
ZA1110  
51865  
20010207  
10010206  
10000992  
20010320  
10000949  
20010179  
20010179  
51842  
26. Grommet  
27. Wire/Bushing Assy (not shown)  
20010348  
20010346  
Fuel Conversion Kits  
Conversion Kit, NG to LP  
36CDV  
Kit # 20010507  
36  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
Optional Accessories Available  
Fan Kits  
Wiring Instructions  
FK12  
The fireplace, when installed, must be  
electrically connected and grounded in  
accordance with local codes or, in the  
absence of local codes, with the current  
CSA C22.1 Canadian Electric Code.  
This auxiliary fan system increases the efficiency of the  
circulation of the heating air.  
The FK12 Fan Assembly is a fixed speed fan system  
and does not allow for variable speed control.  
For USA installations follow the local codes  
and the national electrical code ANSI/NFPA  
No. 70.  
Specifications  
115 Volts / 60 Hz / 56 Watts.  
Maintenance  
Should this fan require servicing or repair  
the power supply must be disconnected.  
The fan itself does not require regular maintenance,  
however periodic cleaning of the fan and the  
surrounding area is required.  
Any electrical rewiring of this fan must be  
done by a licensed electrician.  
Check the area under the control door (lower louvre  
assembly) and in front of the fan and wipe or vacuum  
this area at least once a month during the operating  
season.  
Remote Controls  
Optional remote control units are available to control  
different functions of the appliances  
Installation  
The fan assembly is supplied fully wired eliminating  
the need for a licensed electrician to carry out the  
installation.  
Model  
RCI  
Function/s Controlled  
ON/OFF  
RC2  
MRC3  
ON/OFF and Temperature  
ON/OFF and Temperature  
control with a digital display  
and programmable 24 hour clock  
Wall mounted thermostat control  
1. Remove the lower Louvre assembly. Move the  
fan & bracket assembly around the gas valve and  
lines to locate the unit against the back wall of the  
appliance, resting on the base.  
IMT  
2. With the protective cover removed from the self-  
adhesive ‘Velcro’ strips apply mild pressure to the  
fan & bracket unit to secure the strips to the metal  
panels. No further securing is required.  
(must be used in bedroom installations)  
3. Power to the fan can be supplied by plugging the  
supplied lead into a conveniently located wall socket  
or by using the receptacle in the bottom of the unit.  
Fan  
Receptacle  
Valve  
Gas Lines  
FP1602  
Fig. 63 FK12 fan placement.  
37  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CDV Series Direct Vent Gas Fireplace  
38  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED LIFETIME WARRANTY  
PRODUCT COVERED BY THIS WARRANTY  
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic or Northern Flame brand gas fireplaces  
equipped with an Insta-Flame Ceramic Burner, or standard steel tube burner.  
BASIC WARRANTY  
Any part and/or component replaced under the provisions of this  
warranty is covered for six months or the remainder of the original  
warranty, whichever is longest.  
CFM Corporation (hereinafter referred to collectively as the Company)  
warrants that your new Vermont Castings or Majestic Gas Fireplace/  
Stove is free from manufacturing and material defects for a period of  
one year from the date of purchase, subject to the following conditions  
and limitations.  
This warranty is limited to the repair of or replacement of part(s) found  
to be defective in material or workmanship, provided that such part(s)  
have been subjected to normal conditions of use and service, after  
said defect is confirmed by the Company’s inspection.  
EXTENDED LIFETIME WARRANTY  
The company may, at its discretion, fully discharge all obligations  
with respect to this warranty by refunding the wholesale price of the  
defective part(s)  
The heat exchanger, where applicable, and combustion chamber  
of every Vermont Castings or Majestic gas product is warranted for  
life against through wall perforation. All appliances equipped with an  
Insta-Flame Ceramic Burner have limited lifetime coverage on the  
ceramic burner plaque. Warrantees are made to the original owner  
subject to proof of purchase and the conditions and limitations listed  
on this Warranty Document  
Any installation, labor, construction, transportation, or other related  
costs/expenses arising from defective part(s), repair, replacement,  
or otherwise of same, will not be covered by this warranty, nor shall  
the Company assume responsibility for same. Further, the Company  
will not be responsible for any incidental, indirect, or consequential  
damages except as provided by law.  
COMPONENT WARRANTY  
CAST IRON: All external and internal cast iron parts are warranted for a  
period of three years.  
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR  
LIMITATIONS OF INCIDENTALAND CONSEQUENTIAL DAMAGES  
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY  
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR  
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC  
RIGHTSANDYOUMAYHAVEOTHERRIGHTSWHICHVARYFROM  
STATE TO STATE.  
Note:OnporcelainenamelnishedexternalpartsandaccessoriesThe  
Company offers no Warranty on chipping of enamel surfaces. Inspect  
all product prior to accepting it for any damage to the enamel.  
Thesaltairenvironmentofcoastalareasorahighhumidityenvironment  
can be corrosive to the porcelain enamel finish. These conditions can  
cause rusting of the cast iron beneath the porcelain enamel finish,  
which will cause the finish to flake off.  
All other warranties-expressed or implied- with respect to the product,  
its components and accessories, or any obligations/liabilities on the  
part of the Company are hereby expressly excluded.  
Dyelotvariationswithreplacementpartsand/oraccessoriescanoccur  
and are not covered by warranty.  
The Company neither assumes, nor authorizes any third party to  
assume on its behalf, any other liabilities with respect to the sale of  
this Vermont Castings or Majestic product  
GLASS DOORS: Glass doors are covered for a period of one year.  
Glass doors are not warranted for breakage due to misuse or accident.  
Glass doors are not covered for discoloration or burned in stains due to  
environmental issues, or improper cleaning and maintenance.  
The warranties as outlined within this document do not apply to  
chimney components or other non CFM Corporation accessories used  
in conjunction with the installation of this product..  
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be  
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar  
mix and masonry cleaners may corrode the brass finish. The Company  
will not be responsible for, nor will it warrant any brass parts which are  
damaged by external chemicals or down draft conditions.  
Damage to the unit while in transit is not covered by this warranty but  
is subject to claim against the common carrier. Contact the dealer  
from whom you purchased your fireplace/stove (do not operate the  
appliance as this might negate the ability to process the claim with the  
carrier).  
GAS VALVES: Gas valves are covered for a period of one year  
The Company will not be responsible for:  
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and  
mechanical components of the burner assembly are covered for one year.  
All steel tube burners are warranted for one year.  
a) Down drafts or spillage caused by environmental conditions such  
as near-by trees, buildings, roof tops, hills, or mountains.  
b) Inadequate ventilation or negative air pressure caused by  
mechanical systems such as furnaces, fans, clothes dryers, etc.  
ACCESSORIES: Unless otherwise noted all components and CFM  
Corporation company supplied accessories are covered for a period of  
one year.  
This warranty is void if:  
a) The fireplace has been operated in atmospheres contaminated by  
chlorine, fluorine, or other damaging chemicals.  
CONDITIONS AND LIMITATIONS  
b) Thereplacehasbeensubjectedtoprolongedperiodsofdampness  
or condensation  
c) Anydamagestothereplace,combustionchamber,heatexchanger  
orothercomponentsduetowater, orweatherdamage, whichisthe  
result of but not limited to, improper chimney/venting installation.  
d) Any alteration, willful abuse, accident, or misuse of the product  
This new Vermont Castings or Majestic product must be installed by  
a competent, authorized, service contractor. A licensed technician, as  
prescribedbythelocaljurisdictionmustperformanyinstallation/service  
work. It must be installed and operated at all times in accordance with  
the Installation and Operating instructions furnished with the product.  
Any alteration, willful abuse, accident, or misuse of the product shall  
nullify this warranty.  
has occurred.  
This warranty is non-transferable, and is made to the original owner,  
provided that the purchase was made through an authorized supplier  
of the Company.  
IF WARRANTY SERVICE IS NEEDED…  
1) Contact your supplier. Make sure you have your warranty,  
your sales receipt, and the model/serial number of your CFM  
Corporation product.  
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK  
YOURSELF.  
The customer must pay for anyAuthorized Dealer in-home travel fees  
or service charges for in-home repair work. It is the dealers option  
whether the repair work will be done in the customer’s home or in the  
dealer’s shop.  
Ifuponinspection,thedamageisfoundtobethefaultofthemanufacturer,  
repairs will be authorized at no charge to the customer parts and/or  
labor.  
39  
20010175  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Efficiency Ratings  
Model  
EnerGuide Ratings  
Fireplace Efficiency (%) Fan-OFF  
Steady State (%)  
D.O.E.  
(AFUE%)  
63  
Fan-ON  
76.5  
78  
36CDVRRN  
36CDVRRP  
66.9  
66.9  
76  
77  
63  
CFM Corporation  
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taylor Freezer 345 346 349 355 User Manual
Texas Instruments Network Card TPS2330 User Manual
Timex Watch 170 095004 NA User Manual
Topcom Telephone COCOON 300 User Manual
Toshiba All in One Printer e STUDIO163 User Manual
Toshiba Cash Register MA 1060 User Manual
Tricity Bendix Cooktop SIE305 User Manual
Tripp Lite Universal Remote PR PRO3 User Manual
Verilux Indoor Furnishings VC01HH1 User Manual
Weed Eater Lawn Mower 96114000409 User Manual