Thomas Betts Indoor Furnishings FPS HL User Manual

FPS-HL  
EMERGENCY  
LIGHTING EQUIPMENT  
INSTRUCTION MANUAL  
IMPORTANT SAFEGUARDS  
When using electrical equipment, basic safety precautions should always be followed, including the following:  
READ AND FOLLOW ALL SAFETY INSTRUCTIONS  
1. CAUTION To prevent electrical shock, do not mate unit connector until installation is complete and A.C.  
power is supplied to the unit.  
2. CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electri-  
cal shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by  
disconnecting the unit connector.  
3. CAUTION – The integral, high temperature Ni-Cad battery is replaceable. To replace the battery, discon-  
nect the unit connector and remove both switched and unswitched A.C. power to the fixture. Remove the  
lid screw and open the lid to expose the battery. Unplug the battery connector and replace with part  
number 44900-006 (14.4V Ni-Cad battery only). Recycle the used battery. The EPA certified RBRC®  
Battery Recycling Seal indicates voluntary participation in an industry program to collect and recycle  
these batteries at the end of their useful life, when taken out of service in the United States or Canada.  
The RBRC program provides a convenient alternative to placing used Ni-Cad batteries into the trash or the  
municipal waste stream, which may be illegal in your area. Please call 1-800-822-8837 for information on  
Ni-Cad battery recycling and disposal bans/restrictions in your area. Involvement in this program is part of  
a commitment to preserving the environment and conserving natural resources.  
4. DO NOT USE OUTDOORS. The FPS-HL is for use with grounded, UL Listed, indoor fixtures except in  
heated air outlets or hazardous locations.  
5. The FPS-HL requires an unswitched A.C. power source of either 120 or 277 volts. Properly cap the  
unused A.C. lead.  
6. Do not mount near gas or electric heaters.  
7. The FPS-HL should be mounted in locations and at heights where it will not readily be subjected to  
tampering by unauthorized personnel.  
8. The FPS-HL mounts on top of the fixture or adjacent to the fixture on an optional T-bar mounting bracket.  
9. The FPS-HL will cold strike and operate one 28or two 24instant start, rapid start, U shape or  
circline, T8 through T12 fluorescent lamps, including energy saving and long 4 pin compact lamps for 90  
minutes.  
10. The FPS-HL operates lamps as follows:  
One 28, or two 24lamps for 90 minutes at reduced light output.  
One 24lamp for 90 minutes at full light output.  
11. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.  
12. Do not use this equipment for other than intended use.  
13. Install in accordance with the National Electrical Code and local regulations.  
14. Installation and servicing should be performed by qualified personnel.  
15. Lighting fixture manufacturers, electricians and end users need to ensure product system compatibility  
before final installation.  
SAVE THESE INSTRUCTIONS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. INSTALLING THE TEST SWITCH  
The test switch should be mounted on the ballast channel cover of a recessed troffer, or on the side of a strip fixture,  
preferably adjacent to the charge indicator. Drill or punch a 1/2mounting hole.  
6. WIRING THE A.C. INPUT  
A. The FPS-HL and A.C. ballast must be on the same branch circuit.  
B. The FPS-HL requires an unswitched A.C. power source of either 120 or 277 volts. Select the proper voltage lead and  
cap the unused lead.  
C. When the FPS-HL is used with a switched fixture, the A.C. input to the FPS-HL must be connected ahead of the fixture  
switch. Refer to Illustration 3 for switched and unswitched fixture wiring diagrams.  
Illustration 3  
Switched Fixture  
Unswitched Fixture  
WHITE  
WHITE  
A.C. BALLAST  
A.C. BALLAST  
BLACK  
BLACK  
WALL SWITCH  
(277V) ORG  
(277V) ORG  
HOT A.C. LINE  
COMMON  
HOT A.C. LINE  
COMMON  
(120V) BLK  
(120V) BLK  
FPS-HL  
FPS-HL  
(COMM) WHT  
(COMM) WHT  
TEST SWITCH  
TEST SWITCH  
Select proper voltage lead. Cap unused lead.  
Select proper voltage lead. Cap unused lead.  
7. LABELS  
Attach the appropriate labels adjacent to the Test Switch and Charge Indicator. Annotate Re-lamping label for lamp  
type and wattage. The Caution and the Re-lamping labels must be on the fixture in a readily visible location to anyone  
attempting to service the fixture.  
8. COMPLETING INSTALLATION  
When the installation is complete, switch the A.C. power on and join the FPS-HL unit connector.  
OPERATION  
Normal Mode A.C. power is present. The A.C. ballast operates the fluorescent lamp(s) as intended. The FPS-HL is in the  
standby charging mode. The Charge Indicator will be lit providing a visual indication that the battery is being charged.  
Emergency Mode The A.C. power fails. The FPS-HL senses the A.C. power failure and automatically switches to the Emer-  
gency Mode. One or two lamps are illuminated, at reduced output, for a minimum of 90 minutes. When the A.C. power is re-  
stored, the FPS-HL switches the system back to the Normal Mode and resumes battery charging. See page 1 of the Instruction  
Manual.  
TESTING & MAINTENANCE  
Initial Testing Allow the unit to charge approximately 1 hour, then conduct a short discharge test. Allow a 24 hour charge  
before conducting a one hour test.  
The FPS-HL is a maintenance free unit, however, periodic inspection and testing is required. NFPA 101, Life Safety Code,  
outlines the following schedule:  
Monthly Insure that the Charge Indicator light is illuminated. Conduct a 30 second discharge test by depressing the Test  
Switch. One lamp or two lamps should operate at full or reduced output, depending on your configuration.  
Annually Insure that the Charge Indicator light is illuminated. Conduct a full 11/2 hour discharge test. The unit should operate  
as intended for the duration of the test.  
Written records of testing shall be kept by the owner for inspection by the authority having jurisdiction.”  
SERVICING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.  
Consult Customer Service for current warranty information.  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL WIRING DIAGRAMS  
For wiring diagrams of ballasts not shown, consult our Customer Service.  
1. ONE LAMP RAPID START BALLAST  
5. TWO LAMP INSTANT START BALLAST  
SWITCHED OR  
UNSWITCHED  
LINE  
SWITCHED OR  
UNSWITCHED  
LINE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLACK  
WHITE  
BLUE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
ORG (277V)  
ORG (277V)  
FPS-HL  
A.C.  
Ballast  
A.C.  
Ballast  
BLACK  
WHITE  
UNSWITCHED  
UNSWITCHED  
COMMON  
FPS-HL  
RED  
RED  
BLK (120V)  
WHITE  
BLK (120V)  
WHITE  
RED  
YELLOW  
YELLOW  
COMMON  
LAMP  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
UNIT  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
*LAMP  
*LAMP  
CONNECTOR  
CONNECTOR  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
CHARGE  
INDICATOR  
CHARGE  
INDICATOR  
COMMON  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
COMMON  
*AC / EMERGENCY  
LAMP SELECTION LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
*AC / EMERGENCY  
CONNECT BLU/WHT AND RED/WHT  
WIRES TOGETHER  
2. TWO LAMP RAPID START BALLAST  
6. TWO LAMP INSTANT START BALLAST  
SWITCHED OR  
UNSWITCHED  
LINE  
SWITCHED OR  
UNSWITCHED  
LINE  
BLUE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLACK  
WHITE  
BLACK  
WHITE  
ORG (277V)  
ORG (277V)  
A.C.  
Ballast  
A.C.  
Ballast  
FPS-HL  
UNSWITCHED  
COMMON  
FPS-HL  
UNSWITCHED  
COMMON  
YELLOW  
YELLOW  
RED  
RED  
BLK (120V)  
WHITE  
BLK (120V)  
WHITE  
BLUE  
RED  
YELLOW  
YELLOW  
LAMP  
LAMP  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
*LAMP  
CONNECTOR  
*LAMP  
CONNECTOR  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
CHARGE  
INDICATOR  
CHARGE  
INDICATOR  
COMMON  
COMMON  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
*AC / EMERGENCY  
LAMP SELECTION LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
*AC / EMERGENCY  
CONNECT BLU/WHT AND RED/WHT  
WIRES TOGETHER  
3. THREE LAMP RAPID START BALLAST  
7. THREE LAMP INSTANT START BALLAST  
SWITCHED OR  
UNSWITCHED  
LINE  
SWITCHED OR  
UNSWITCHED  
LINE  
BLACK  
WHITE  
BLUE  
BLUE/WHT  
BLUE/WHT  
BLUE  
BLUE  
BLUE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLACK  
WHITE  
BLUE/WHT  
RED/WHT  
RED  
ORG (277V)  
ORG (277V)  
A.C.  
Ballast  
FPS-HL  
UNSWITCHED  
COMMON  
A.C.  
Ballast  
FPS-HL  
UNSWITCHED  
COMMON  
BLUE  
RED  
RED  
BLK (120V)  
WHITE  
YELLOW  
YELLOW  
BLK (120V)  
WHITE  
RED  
YELLOW  
YELLOW  
LAMP  
*LAMP  
LAMP  
LAMP  
LAMP  
*LAMP  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
UNIT  
CONNECTOR  
CONNECTOR  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
CHARGE  
INDICATOR  
CHARGE  
INDICATOR  
COMMON  
COMMON  
LAMP SELECTION LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
*AC / EMERGENCY  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
*AC / EMERGENCY  
CONNECT BLU/WHT AND RED/WHT  
WIRES TOGETHER  
4. ONE LAMP INSTANT START BALLAST  
8. FOUR LAMP INSTANT START BALLAST  
SWITCHED OR  
UNSWITCHED  
LINE  
SWITCHED OR  
UNSWITCHED  
LINE  
BLACK  
WHITE  
BLUE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLACK  
WHITE  
RED  
ORG (277V)  
ORG (277V)  
A.C.  
A.C.  
Ballast  
UNSWITCHED  
COMMON  
UNSWITCHED  
COMMON  
YELLOW  
YELLOW  
RED  
RED  
BLK (120V)  
WHITE  
FPS-HL  
BLK (120V)  
WHITE  
FPS-HL  
Ballast  
YELLOW  
YELLOW  
LAMP  
LAMP  
LAMP  
*LAMP  
UNIT  
CONNECTOR  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
*LAMP  
CONNECTOR  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
CHARGE  
INDICATOR  
CHARGE  
INDICATOR  
COMMON  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
COMMON  
*AC / EMERGENCY  
*AC / EMERGENCY  
CONNECT BLU/WHT AND RED/WHT  
WIRES TOGETHER  
CONNECT BLU/WHT AND RED/WHT  
WIRES TOGETHER  
9. TWO LAMP RAPID START BALLAST  
W/2 LAMP EMERGENCY OPERATION  
10. TWO LAMP INSTANT START BALLAST  
W/2 LAMP EMERGENCY OPERATION  
SWITCHED OR  
SWITCHED OR  
UNSWITCHED  
UNSWITCHED  
LINE  
LINE  
BLACK  
WHITE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLUE  
BLUE  
BLUE  
BLUE/WHT  
RED/WHT  
RED  
BLACK  
WHITE  
ORG (277V)  
ORG (277V)  
A.C.  
Ballast  
A.C.  
Ballast  
FP  
S
-
H
L
UNSWITCHED  
FPS-HL  
UNSWITCHED  
COMMON  
YELLOW  
YELLOW  
RED  
RED  
BLK (120V)  
WHITE  
BLK (120V)  
WHITE  
RED  
BLUE  
YELLOW  
YELLOW  
COMMON  
*LAMP  
*LAMP  
*LAMP  
*LAMP  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
UNIT  
SELECT PROPER VOLTAGE  
LEAD. CAP UNUSED LEAD.  
CONNECTOR  
CONNECTOR  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
DO NOT MATE CONNECTOR UNTIL  
INSTALLATION IS COMPLETE AND  
AC POWER IS SUPPLIED.  
CHARGE  
INDICATOR  
CHARGE  
INDICATOR  
COMMON  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMP OPERATION SECTION FOR  
VARIOUS OPTIONS.  
COMMON  
LAMP SELECTOR LEADSREFER  
TO INSTALLATION INSTRUCTIONS,  
LAMPS OPERATION SECTION FOR  
VARIOUS OPTIONS  
*AC / EMERGENCY  
*AC / EMERGENCY  
CONNECT BLU/WHT AND RED/WHT  
WIRES TOGETHER  
Rev.021903  
68160-006  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  

TDK Network Card HHM Series HHM2209SA1 User Manual
Texas Instruments Network Router SM320F2812 HT User Manual
Timex Clock 753424T User Manual
Toastess Cooktop DLHG 443 User Manual
Toastmaster Kitchen Grill GR39A User Manual
Trango Broadband Stereo System AD2401 24 User Manual
Tripp Lite Power Supply APSINT Series User Manual
Vivitar Digital Camera F127 User Manual
Vulcan Hart Boiler VIR1BF User Manual
Weed Eater Lawn Mower 186832 User Manual