Installation Manual of Room Air Conditioner
Read this manual before installation
Explain sufficiently the operating means to the user
according to this manual.
Necessary Tools for Installation
1.Driver
5.Torque wrench(17mm,22mm,26mm)
9.Nipper
12.Reamer
2.Hacksaw
3.Hole core drill
4.Spanner(17,19 and 26mm)
6.Pipe cutter
7.Flaring tool
8.Knife
10.Gas leakage detector or
soap-and-water solution
11.Measuring tape
Drawing for the installation of indoor and outdoor units
The models adopt HFC free refrigerant R410A
Accessory parts
Number
of
No. Accessory parts
articles
Optional parts for piping
Remote controller
1
2
1
2
1
Mark
A
Parts name
Non-adhesive tape
Adhesive tape
R-03 dry battery
B
C
D
Saddle(L.S) with screws
Connecting electric cable
for indoor and outdoor
3
4
Mounting plate
Drain hose
E
F
Heating insulating material
Piping hole cover
4
4X25
Screw
Plastic cap
Drain-elbow
G
Attention must be paid to
the rising up of drain hose
1
1
5
6
A
Pipe supporting plate
Arrangement of piping directions
Rear left
Rear
right
Left
C
Right
Below
D
A
G
The marks from to in the figure are the parts numbers.
The distance between the indoor unit and the floor should be
more than 2m.
No.001051
Indoor unit
1.Fitting of the Mounting Plate and Positioning of the wall Hole
When the mounting plate is first fixed
1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be
fixed against the wall, then temporarily fasten the plate with one steel nail.
2. Make sure once more the proper level of the plate, by hanging a thread with a weight from
the central top of the plate, then fasten securely the plate with the attachment steel nail.
3. Find the wall hole location A using a measuring tape
60mm
B=
A=145mm
When the mounting plate is fixed side bar and lintel
Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten
the plate to the fixed mounting bar.
Refer to the previous article, " When the mounting plate is first fixed ", for the
position of wall hole.
2.Making a Hole on the Wall and Fitting the Piping Hole Cover
Make a hole of 60 mm in diameter,
slightly descending to outside the wall.
Install piping hole cover and seal it
off with putty after installation
Indoor side
Wall hole
60mm
Outdoor side
Thickness
of wall
Piping hole pipe
(Section of wall hole)
3
Indoor unit
3.Installation of the Indoor Unit
Drawing of pipe
Rear piping
Draw pipes and the drain hose, then fasten them with the adhesive tape
Left Left-rear piping
In case of left side piping, cut away, with a nipper, the lid for left piping.
In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear
piping which is marked on heat insulation materials.
1. Insert the drain hose into the dent of heat insulation materials of indoor unit.
2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then
connect them.
3. Coat the flaring seal face with refrigerant oil and connect pipes.
Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape
Heat insulation
Piping
material
Pipe supporting plate
Drain hose
Lid for right piping
Indoor/outdoor
electric cable
Lid for left piping
Lid for under piping pipe
Fix with adhesive tape
Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape.
Other direction piping
Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according
to the position of wall hole. When bending, be careful not to crash pipes.
Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation
of connecting part specially.
Fixing the indoor unit body
Hang surely the unit body onto the upper notches of the
mounting plate. Move the body from side to side to verify
its secure fixing.
In order to fix the body onto the mounting plate,hold up
the body aslant from the underside and then put it down
perpendicularly.
4.Connecting the indoor/outdoor Electric Cable
Removing the wiring cover
Remove terminal cover at right bottom corner of indoor unit, then
take off wiring cover by removing its screws.
4
Indoor unit
When connecting the cable after installing the indoor unit
1. Insert from outside the room cable into left side of the wall hole, in which
the pipe has already existed.
2. Pull out the cable on the front side, and connect the cable making a loop.
When connecting the cable before installing the indoor unit
Insert the cable from the back side of the unit, then pull it out on the front side.
Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws.
Pull the cable slightly to make sure the cables have been properly inserted and tightened.
After the cable connection, never fail to fasten the connected cable with the wiring cover.
Note: When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring
is not correct, proper operation can not be carried out and will cause defect.
1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar
qualified person. The type of connecting wire is H05RN-F or H07RN-F.
2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V.
3. The wiring method should be in line with the local wiring standard.
4. After installation, the power plug should be easily reached.
5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the
distance between its two contacts should be not less than 3mm.
Indoor unit
Outdoor unit
Power cable: ≥3G1.5mm2
≥5G1.5mm 2
Connecting wiring:
5
Outdoor unit
1.Installation of Outdoor Unit
Drawing for the installation of indoor and outdoor units
Install according to
2.Connection of pipes
To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius
should be 30 to 40 mm or longer.
Connecting the pipe of gas side first makes working easier.
The connection pipe is specialized for R410A.
Forced fastening without careful
centering may damage the
threads and cause a leakage of
gas.
Half union
Flare nut
Fastening torque
Pipe Diameter
Liquid side 6.35mm(1/4")
18N.m
Gas side 9.52mm(3/8")
Gas side 12.7mm(1/2")
42N.m
55N.m
Spanner
Torque wrench
Be careful that matters, such as wastes of sands, etc. shall not enter the pipe.
The standard pipe length is 5m. If it is over 5m, the function of the unit will be affected. If the pipe has
to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant
must be conducted by professional air conditioner engineer. Before adding additional refrigerant,
perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge
additional refrigerant.
Outdoor unit
Outdoor unit
Oil trap
A
Indoor unit
Max. Length:A=20m
CAUTION
Indoor unit
In case more than 5m
Oil trap shoud be installed every 5~7m
Max.Elevation:10m
no more gas if the length of connecting pipe is less than35m
3.Connection
Use the same method on indoor unit. Loosen
the screws on terminal block and insert the
plugs fully into terminal block, then tighten the
screws.
If wiring is not correct, proper operation can
not be carried out and controller may be
damaged.
Fix the cable with a clamp.
Insert the cable according to terminal number
in the same manner as the indoor unit.
4.Attaching Drain-Elbow
If the drain-elbow is used, please attach it as
figure.
Drain hose
Note: Only for heat pump unit.
Drain elbow
6
Outdoor unit
Liquid Side
6.35mm(1/4")
5.Purging Method:To use vacuum pump
Gas Side
9.52mm(3/8")
12.7mm(1/2")
3-way valve
2-way valve
Detach the service port's cap of 3-way valve, the
valve rod's cap for 2-way valve and 3-way's, connect
the service port into the projection of charge hose
(low) for gaugemanifold. Then connect the projection
of charge hose (center) for gaugemanifold into
vacuum pump.
Gaugemanifold(for R410A)
Anti countercurrent joint
Vacuum pump(for R410A)
Tube(for R410A)
Open the handle at low in gaugemanifold, operate
vacuum pump. If the scale-moves of gause (low)
Open
reach vacuum condition in a moment, check
again.
Vacuumize for over 15min. And check the level gauge
which should read -0.1 MPa (-76 cm Hg) at low
pressure side. After the completion of vacuumizing,
close the handle 'Lo' in gaugemanifold and stop the
operation of the vacuum pump.
Close
Check the condition of the scale and hold it for 1-2min.
If the scale-moves back in spite of tightening, make
flaring work again, the return to the beginning of
.
Open the valve rod for the 2-way valve to an angle of
anticlockwise 90 degrees.
3-way valve
Service port
90ofor 6 sec.
2-way valve
After 6 seconds, close the 2-way valve and make
the inspection of gas leakage.
Open
90o
If it does not stop gas leakage, discharge
whole refrigerants from the service port.
After flaring work again and vacuumize,
fill up prescribed refrigerant from the gas
cylinder
In case of gas leakage, tighten
parts of pipe connection. If
leakage stops, then proceed
steps.
No gas leakage?
Liquid Side
6.35mm(1/4")
2-way valve
Detach the charge hose from the service port, open
2-way valve and 3-way. Turn the valve rod anticlockwise
until hitting lightly.
3-way valve
2-way valve
Gas Side
9.52mm(3/8")
3-way valve
To prevent the gas leakage, turn the service port's
cap, the valve rod's cap for 2-way valve and 3-way's
a little more than the point where the torque increases
suddenly.
3-way valve
2-way valve
Valve rod cap
Valve rod cap
Service port cap
After attaching the each caps, check the gas leakage
around the caps.
CAUTION:
1.If the refrigerant of the air conditioner leaks, it is necessary to
discharge all the refrigerant. Vacuumize first, then charge the liquid
refrigerant into air conditioner according to the amount marked on
the name plate.
2.Please do not let other cooling medium, except specified one (R410A),
or air enter into the cooling circulation system. Otherwise, there will be
abnormal high pressure in the system to make it crack and lead to
personal injuries.
7
1.Power Source Installation
The power source must be exclusively used for air conditioner. (Over I0A)
In the case of installing an air conditioner in a moist place, please install an
earth leakage breaker.
For installation in other places, use a circuit breaker as far as possible.
2.Cutting and Flaring Work of Piping
Pipe cutting is carried out with a pipe cutter and burs must be removed.
After inserting the flare nut, flaring work is carried out.
A
Flare tool for R410A
Clutch-type
Conventional flare tool
Flare tooling die
2.Remove burs
clutch-type(Rigid-type)
Wing-nut type (Imperial-type)
1.Cut pipe
0~0.5mm
1.0~1.5mm
1.5~2.0mm
3.Insert the flare nut
4.Flare pipe
Incorrect
Correct
Lean Damage of flareCrack
Partial Too outside
3.On Drainage
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.
Less than 5cm
The end is immersed
in water.
It waves.
The gap with the ground
is too small
There is the bad smell
from a ditch
It becomes high
midway.
Please pour water in the drain pan of the indoor unit, and confirm that drainage is
carried out surely to outdoor.
In case that the attached drain hose is in a room, please apply heat insulation
to it without fail.
Check for Installation and Test Run
Please kindly explain to our customers how to operate through the instruction manual.
Check Items for Test Run
Put check mark
in boxes
Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of
indoor and outdoor firmly inserted
to the terminal block?
Is drainage securely carried out?
Is the earth line securely
connected?
Is the indoor unit securely fixed?
Is power source voltage abided
by the code?
Is the lamp normally lighting?
Are cooling and heating (when
in heat pump) performed normally?
Is the operation of room temperature
regulator normal?
Is the connecting wiring of indoor
and outdoor firmly fixed?
Is there any noise?
8
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China
IT CONFORMITÀ ALLE DIRETTIVE EUROPEE PER I MODELLI:
CE
SPECIFICHE DI SMALTIMENTO:
Il climatizzatore è contrassegnato con questo simbolo,
Tutti i prodotti sono conformi alle seguenti normative europee:
- Direttiva 73/23/EEC Basso Voltaggio
- Direttiva 2006/95/EC Basso Voltaggio
- Direttiva 89/336/EEC Compatibilità elettromagnetica
- Direttiva 2004/108/EC Compatibilità elettromagnetica
ciò significa che i prodotti elettrici ed elettronici non
possono essere smaltiti insieme ai rifiuti domestici non
differenziati. Non cercare di demolire il sistema da soli:
la demolizioni dei sistemi di condizionamento, nonché il
recupero del refrigerante, dell’olio e di qualsiasi altra
ROHS
parte devono essere eseguiti da un installatore qualifi-
Il prodotto è conforme alla normativa 2002/95/EEC sulla restrizione d’uso di
cato in conformità alla legislazione locale e nazionale
sostanze inquinanti negli apparecchi elettrici ed elettronici.
vigente in materia.I climatizzatori devo essere trattati presso una struttura spe-
cializzata nel riutilizzo, riciclaggio e recupero dei materiali. Il corretto smaltimen-
to del prodotto eviterà le possibili conseguenze negative all’ambiente e alla
salute dell’uomo. Per maggiori informazioni contattare l’installatore o le autori-
tà locali. Le batterie devono essere tolte dal telecomando e smaltite separata-
mente conformemente alla legislazione locale e nazionale vigente in materia.
WEEE
Informativa al consumatore come previsto dalla normativa europea
2002/96/CE riguardante i rifiuti di apparecchiature elettriche ed elettroniche.
EN EUROPEAN REGULATIONS CONFORMITY FOR THE MODELS:
CE
DISPOSAL REQUIREMENTS:
All the products are in conformity with the following European provision:
Your air conditioning product is marked with this sym-
- Low Voltage Directive 73/23/EEC
bol. This means that electrical and electronic products
- Low Voltage Directive 2006/95/EC
shall not be mixed with unsorted household waste.
- Electromagnetic CompatibilitY 89/336/EEC
- Electromagnetic CompatibilitY 2004/108/EC
Do not try to dismantle the system yourself: the dis-
mantling of the air conditioning system, treatment of
the refrigerant, of oil and of other part must be done
by a qualified installer in accordance with relevant
local and national legislation. Air conditioners must be
ROHS
The products are fulfilled with the requirements in the directive 2002/95/EEC of the
European parliament and of the council on the Restriction of the use of Certain Haz-
ardous Substances in Electrical and Electronic Equipment (EU RoHS Directive)
treated at a specialized treatment facility for re-use, recycling and recovery.
By ensuring this product is disposed of correctly, you will help to prevent
potential negative consequences for the environment and human health.
Please contact the installer or local authority for more information. Battery
must be removed from the remote controller and disposed of separately in
accordance with relevant local and national legislation.
.
WEEE
In accordance with the directive 2002/96/CE of the European parliament,
herewith we inform the consumer about the disposal requirements of the
electrical and electronic products.
FR CONFORMITÉ AUX DIRECTIVES EUROPÉENNES POUR LES MODÈLES:
CE
SPECIFICATIONS POUR L'ELIMINATION:
Tous les produits sont conformes aux directives européennes suivantes:
Ce pictogramme, apposé sur le climatiseur, signifie
- Directive 73/23/CEE Basse tension
que les équipements électriques et électroniques ne
- Directive 2006/95/CE Basse tension
peuvent pas être éliminés avec les déchets ménagers
- Directive 89/336/CEE Compatibilité électromagnétique
- Directive 2004/108/CE Compatibilité électromagnétique
non triés. Ne pas essayer de démanteler l'équipement
soi-même: le démantèlement des systèmes de clima-
tisation, ainsi que la récupération du frigorigène, de
ROHS
l'huile et de toute autre partie doivent être effectués
L'appareil est conforme à la directive 2002/95/CEE relative à la limitation de
l'utilisation de certains substances dangereuses dans les équipements élec-
triques et électroniques.
par un installateur qualifié conformément à la législa-
tion locale et nationale en vigueur en la matière. Les climatiseurs doivent être
traités dans un centre spécialisé dans la réutilisation, le recyclage et la valo-
risation des matériaux. L'élimination correcte de ces appareils permet d'évi-
ter les effets nocifs sur l'environnement et la santé humaine. Pour plus de
renseignements contacter l'installateur ou les autorités locales. Les piles doi-
vent être retirées de la télécommande et éliminées séparément, conformé-
ment à la législation locale et nationale en vigueur en la matière.
DEEE (WEEE)
Information au consommateur comme le prévoit la directive européenne
2002/96/CE relative aux déchets d'équipements électriques et électro-
niques.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China
ES CONFORMIDAD EUROPEA DE LAS REGULACIONES PARA LOS MODELOS:
CE
REQUISITOS PARA LA ELIMINACIÓN:
Su acondicionador de aire está marcado con este
Todos los productos están en conformidad con las siguientes Normativas
Europeas:
- Bajo Voltaje directiva 73/23/EEC
símbolo. Esto significa que los productos eléctricos y
electrónicos no deben mezclarse con el resto de resi-
- Bajo Voltaje directiva 2006/95/EC
duos domésticos no clasificados.
- Compatibilidad electromagnética 89/336/EEC
- Compatibilidad electromagnética 2004/108/EC
No intente desmontar el sistema usted mismo: El des-
mantelamiento del acondicionador de aire, así como
el tratamiento del refrigerante, aceite y otros compo-
ROHS
nentes, debe ser efectuado por un instalador compe-
Los productos cumplen los requisitos de la directiva 2002/95/EEC del parla-
mento Europeo y el consejo regulador Del uso de materiales peligrosos en
equipamientos eléctricos Y electrónicos. (EU RoHS Directiva).
tente de acuerdo con las normas locales y nacionales aplicables. Los acon-
dicionadores de aire deben ser tratados en instalaciones especializadas para
su reutilización, reciclaje y recuperación. Al asegurarse de desechar este pro-
ducto de la forma correcta, està contribuyendo a evitar posibles consecuen-
cias negativas para el entorno y para la salud de las personas. Contacte, por
favor, con el instalador o con las autoridades locales para obtener más infor-
mación. Las pilas del control remoto deben extraerse y eliminarse por sepa-
rado y de acuerdo con la normativa local y nacional aplicable.
WEEE
De acuerdo con la directiva 2002/96/CE del parlamento Europeo, Informa-
mos al consumidor acerca del reciclage de los productos Electrónicos y
eléctricos.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
A
1=
kg
kg
R410A
B
C
2
2=
1
1+2=
kg
D
F
E
IT INFORMAZIONI IMPORTANTI SUL REFRIGERANTE UTILIZZATO
Questo prodotto contiene gas fluorurati ad effetto serra inclusi nel Protocollo
di Kyoto. Non liberare tali gas nell’atmosfera.
L’etichetta compilata deve essere collocata in prossimità della portata di cari-
ca del prodotto (ad esempio, nell’interno del coperchio della valvola d’inter-
cettazione).
Tipo di refrigerante: R410A
Valore GWP*: 1975
*GWP = potenziale di riscaldamento globale
A
B
contiene gas fluorurati ad effetto serra inclusi nel protocollo di Kyoto
carica di refrigerante di fabbrica del prodotto: vedi targhetta con il nome
dell’unità
Compilare con inchiostro indelebile,
C
D
E
F
quantità di refrigerante aggiuntiva nel campo
carica di refrigerante totale
unità esterna
• 1
• 2
la carica di refrigerante di fabbrica del prodotto
la quantità di refrigerante aggiuntiva nel campo e
• 1+2 la carica di refrigerante totale
cilindro del refrigerante e collettore di carica
sull’etichetta di carica del refrigerante fornita con il prodotto
EN IMPORTANT INFORMATION REGARDING THE REFRIGERANT USED
This product contains fluorinated greenhouse gases covered by the Kyoto
Protocol. Do not vent into the atmosphere.
The filled out label must be adhered in the proximity of the product charging
port (e.g. onto the inside of the stop valve cover).
Refrigerant type: R410A
GWP* value: 1975
*GWP = global warming potential
A
B
C
D
E
F
contains fluorinated greenhouse gases covered by the Kyoto Protocol
factory refrigerant charge of the product: see unit name plate
additional refrigerant amount charged in the field
total refrigerant charge
outdoor unit
refrigerant cylinder and manifold for charging
Please fill in with indelible ink,
• 1
• 2
the factory refrigerant charge of the product
the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge
on the refrigerant charge label supplied with the product.
FR INFORMATION IMPORTANTE RELATIVE AU RÉFRIGÉRANT UTILISÉ
Ce produit contient des gaz à effet de serre fluorés encadrés par le protoco-
le de Kyoto. Ne pas laisser les gaz s’échapper dans l’atmosphère.
L’étiquette complétée doit être apposée à proximité de l’orifice de recharge
du produit (par ex. à l’intérieur du couvercle de la vanne d’arrêt).
Type de réfrigérant: R410A
Valeur GWP*: 1975
*GWP = potentiel de réchauffement global
A
B
contient des gaz à effet de serre fluorés encadrés par le protocole de
Kyoto
charge de réfrigérant d’usine du produit: voir plaquette signalétique de
l’unité
Prière de compléter à l’encre indélébile,
C
D
E
F
quantité de réfrigérant supplémentaire chargée sur place
charge de réfrigérant totale
unité extérieure
• 1
• 2
la charge de réfrigérant d’usine du produit
la quantité de réfrigérant supplémentaire chargée sur place et
• 1+2 la charge de réfrigérant totale
cylindre de réfrigérant et collecteur de recharge
sur l’étiquette de charge de réfrigérant fournie avec le produit.
Haier Industrial Park, No.1 Haier Road, Qingdao, P.R.China
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
A
1=
kg
kg
R410A
B
C
2
2=
1
1+2=
kg
D
F
E
ES INFORMACIÓN IMPORTANTE EN RELACIÓN AL REFRIGERANTE UTILIZADO
Este producto contiene los gases fluorados de efecto invernadora regulados
por el Protocolo de Kioto. No vierta gases a la atmósfera.
La etiqueta rellenada debe pegarse cerca de la conexión de carga del pro-
ducto (p.ej. en el interior de la cubierta de la válvula de tope).
Tipo de refrigerante: R410A
Valor GWP*: 1975
*GWP = Potencial de calentamiento global
A
B
Contiene los gases fluorados de efecto invernadora regulados por el
Protocolo de Kioto
Carga de refrigerante de fábrica del producto: véase placa de especifi-
caciones técnicas de la unidad
Rellene con tinta indeleble,
C
D
E
F
Cantidad adicional de refrigerante cargado en campo
Carga total de refrigerante
Unidad exterior
• 1
• 2
la carga de refrigerante de fábrica del producto
la cantidad adicional de refrigerante cargado en campo y
• 1+2 la carga total de refrigerante
Cilindro del refrigerante y dosificador de carga
En la etiqueta de carga de refrigerante suministrada con el producto.
|