ROOM AIR CONDITIONER
SP06A10 SP08A10
SP10A10 SP12A10
SERVICE Manual
AIR CONDITIONER
CONTENTS
11. Precautions
12. Product Specifications
13. Installation and Operating
Instructions
14. Disassembly and Reassembly
15. Troubleshooting
16. Exploded Views and Parts List
17. Block Diagram
18. PCB Diagram
19. Wiring Diagram
10. Schematic Diagram
2.Product Specifications
2-1 Table
Unit of
SP06A10
SP08A10
SP10A10
SP12A10
Item
Measure
WINDOW
Type
Dimension:
mm
520×345×485
600×394×595
(Width×Height×Depth)
Volt
-
115
SINGLE
60
Voltage
Phase
Hz
Frequency
A
5.4
6.6
9.3
10.5
Operation Current
Power Consumption
Refrigerant Type
Refrigerant Change
Capacity
W
610
740
1000
1170
FREON
g
R22
300
6500
10.8
26
470
8000
10.8
29
450
10800
10.8
635
12600
10.8
BTU/h
BTU/h.W
Kg
EER
43
45
Net Weight
Row
Type
Row
Type
MODEL
MODEL
2×15
3×15
2×17
3×17
Condenser
Propeller Fan
Condenser Fan
Evaporator
2×11
2×11
2×12
2×10
Blower
Evaporator Fan
Fan Motor
YSLA-40-6-0002
39A062HS1EA
MRA12146-120
08
YSLA-40-6-0003
44A076HU1EB
MRA12083-120
08
YGN60-6B
YGN60-6B
44B098HX1EF
44B117HX1EL
Compressor(Rotary)
MRA12132-12007
MRA12053-12007
-
Overload Protect
Compressor Capacitor
Fan Motor Capacitor
Fan Speed
μF/VAC
μF/VAC
RPM
40/370
35/370
45/370
15/250
50/370
15/250
8/450
8/450
920/850/800
1050/1010/970
890/850/800
890/860/750
-
THERMISTOR
Thermo Control
FRIEDRICH AIR CONDITIONING CO.
2-1
MEMO
2-3
FRIEDRICH AIR CONDITIONING CO.
2-2 Dimensions
2-2-1 Main Unit
(Unit : mm)
MODEL
SP06A10
SP08A10
W
H
D
520
345
485
SP10A10
SP12A10
600
394
595
Front view
Side view
W
2-2-2 Remote Control
Remote control
transmission indicator
Mode selection button
(Cool, Fan, Dry)
Operating mode
(
Cool,
Dry,
Fan)
Temperature adjustment
buttons
Temperature setting
Sleep mode
Sleep timer setting button
Energy Saving mode
Fan speed adjustment
button
Fan speed
Energy Saving button
On Timer setting
Timer setting button
Off Timer setting
Timer Set/Cancel button
On/Off button
Battery discharge indicator
2-4
FRIEDRICH AIR CONDITIONING CO.
3. Installation and Operating Instructions
3-1 Installation
3-1-1 Selecting Area for Installation
1. Make sure that you install the unit in an area
providing good ventilation. The air conditioner
must not be blocked by any obstacle affecting the
air flow near the air inlet and air outlet.
6. Make sure that you install the unit in an area
which provides easy drainage for condensed
water.
7. Make sure that you install the unit in an area not
exposed to rain or direct sunlight.
(Install a separate sunblind if exposed to direct
sunlight.)
2. Make sure that you install the unit in an area that
allow good air handling. The installation area
must be able to endure vibration from the unit.
3. Make sure that you install the unit away from
heat or vapor.
8. Make sure that you install the unit in an area
allowing good air movement. Do not install it in
a space that would cause noise amplification of
noise.
4. Make sure that you install the unit in an area
which is cool and has adequate space.
9. Fix the unit firmly if mounted in a high place.
5. Make sure that you install the unit in an area
away from TVs, audio units, cordless phones,
fluorescent lighting fixtures and other electrical
appliances (obtain a clearance of at least one
meter).
Ca u t io n :
Do not use the air conditioner in the following environm ents : greasy areas (including areas near
m achines), or m arine areas. Contact your local dealer for advice.
FRIEDRICH AIR CONDITIONING CO.
3-1
3-2 Function Description
Timer indicator
Temperature/Timer
settings
Energy Saver indicator
Remote control
sensor
Dry adjustment indicator
On/Off button
Fan speed
adjustment button
Mode selection button
(Cool, Fan, Dry)
Temperature
adjustment buttons
3-2-1 Cooling operation mode
The compressor is turned on and off according to the ambient temperature and set temperature.
1) Compressor on and off control
• Compressor on and off control according to the ambient temperature
The compressor is turned off when "ambient temperature = set temperature
The compressor is turned on when "ambient temperature = set temperature +1˚C"
2) Default value after power reset ➔ set temperature = 75˚F
Fan speed = High
*
*
3) Set temperature indicating (setting) range : 1˚F interval from 64˚F to 86˚F.
3-2-2 Fan operation mode
1) If "Fan operation mode" signal is received from remocon or panel.
➔➔ the compressor is immediately turned off and only fan motor is operated at set blowing speed.
➔➔ it changes such as "High ➔ Med ➔ Low ➔➔High"( if Fan speed is selected).
2) The initial Fan motor speed is set to "High".
3) The set temperature can not be indicated and set.
3-2-3 Energy saver operation mode
If the compressor turn off at the cooling operation, the fan motor turn off after operation during the fixation
*
time only, and operation that energy saver by turn off the fixation time only, and operation that energy saver
by turn off the motor continuously before the condition of the compressor on.
The fan motor is not operated at flow wind operation.
Energy saver operation specification at the cooling operation.
*
*
1) Fan motor control in compressor on : operate with setting wind speed
2) Fan motor control in compressor off : After compressor off, the fan motor is operated breeze for 2 minutes
and then it turn off.
3) After the fan motor off, the compressor and fan motor is operated normally when the compressor on.
3-2
FRIEDRICH AIR CONDITIONING CO.
Installation and Operating Instructions
3-2-4 Sleep operation mode
1) Enable to sleep operation only when cooling operation.
2) First, 7-SEG LED DISPLAY "SLEEP" while 15 second, Second, 7-SEG LED DISPLAY "8Hr"
And, automatically SET OFF after operated while 8 Hour
3) If sleep operation, setting Temperature rise 1˚C after 1 Hour
4) ON TIMER operation, not operation, ENERGY SAVER operation, not sleep operation.
3-2-5 Dry operation mode
If the atmosphere in the room is very humid or damp,use this operation mode. It can remove excess humidity
without lowering the room temperature too much.
1) The quantity of air is adjusted automatically.
3-2-6 LED display indication in case of error detection
7-SEG
LED DISPLAY
ERROR OPERATION
ROOM THERMISTOR
E1 displayed
(OPEN or SHORT)
1) Set operation in case of error occurrence.
• Malfunction of each temperature sensor (open, short)
- Error mode display, warning sound.
- The operation status is off.
FRIEDRICH AIR CONDITIONING CO.
3-3
MEMO
3-4
FRIEDRICH AIR CONDITIONING CO.
4. Disassembly and Reassembly
4-1 Compressor Replacement Flow Chart
Locate cause of defect
Release refrigerant
Disconnect electrical wiring
from compressor
Cut refrigerant lines
from compressor
Plug disconnected lines
Replace compressor
Solder discharge line
Solder suction line
Use nitrogen gas
Inspect electrical
wiring for defects,
and terminals for
correct and secure
connections
Perform soldering function
Y
Problem?
Fill system with
nitrogen gas
N
Check for leakage
Y
Corrective action
Leakage?
Check refrigerant oil level
N
Release nitrogen gas?
Y
N
Low oil level?
Evacuate system
Recharge system
Add oil as necessary
Pinch and braze filling tube
FRIEDRICH AIR CONDITIONING CO.
4-1
4-2 Checking the oil
Fill the transparent container with 10cc of oil, and then conduct the test.
4-2-1 Oil quality
Oil Condition
Condition of
Refrigerant Cycle
Remarks
Color
Odor
No Odor
-
Normal
Straw Yellow
Brown Color
Dark Brown
Return with the system
Change the oil
Over-heated
Compressor Damage
Pungent oil
Change the oil
4-2-2 Replacing and refilling the refrigerant oil
1. Change the compressor - DO NOT recharge the oil as the compressor itself is
already charged.
2. Change the condenser .... add 50cc
3. Change the evaporator .... add 50cc
4. When the refrigerant is replaced .... add 30cc oil.
5. After vacuum is completed, the oil is filled through the high pressure side.
6. In the event of a refrigerant leak, generally it is not necessary to add oil.
(Unless the oil has leaked significantly.)
4-2
FRIEDRICH AIR CONDITIONING CO.
4-3.Disassembly and Reassembly Procedure(SP10A10/SP12A10)
Stop operating the air conditioner, and pull out the power cord before repair.
No.
Part Name
Procedures
Remarks
1.Pull the Grille air inlet and Guard air filter out.
1
Ass’y Grille
2.Remove the screw on the panel front.
3.Hold the lower part of panel with two hands
while pressing down on both sides of the lower
part of the cabinet, pull it forward by about
30mm,and then lift it up carefully for
removal.(Must un-connect the Displayer with
the controller inside.)
1.Remove 2 screws on the both side of the
cabinet.
2
Ass’y Cabinet
2.Pull the front part both side, and remove the
unit from the cabinet.
1.Remove the earth screw fixed on the cabinet.
3
Ass’y Control
2.Remove 3 screws fixed on the partition and
frame up.
3.Remove the screw fixed for the power cord.
4.Un-connect the motor wire and comp lead
wire, then take out the control box upward.
FRIEDRICH AIR CONDITIONING CO.
4-3
Disassembly and Reassembly Procedure(SP10A10/SP12A10)
No.
Part Name
Procedures
Remarks
1..Remove 4 screws on the partition and case
cond.
4
Plate reinf&
Case evap up
2.Remove the plate reinf. (The shape maybe
different depend on models)
3.Remove the seal sticked on the case evap up
carefully.
4.Pull the case evap up upward.
1.Remove the cover on the evaporator.
2.Remove all screws on the evaporator.
3.Pull the evaporator forward carefully.
5
Plate evap
casing &
Blower
4.Remove all screws fixed on plate evap
casing, then pull it out completely.
3.Remove the nut and remove the Blower.
1.Remove 2 screws on the rear side of the
base pan, and all screws fixed on case cond.
6
Case Cond &
Fan Propeller
& Motor Fan
2.Pull up the condenser from the base pan.
3.Remove the nut and remove the Propeller
fan.
4.Remove 4 screw(fixed on the mounter ), then
take out the motor.
4-4
FRIEDRICH AIR CONDITIONING CO.
4-5.Disassembly and Reassembly Procedure(SP06A10/SP08A10)
Stop operating the air conditioner, and pull out the power cord before repair.
No.
Part Name
Procedures
Remarks
1.Pull the Grille air inlet and Guard air filter out.
1
Ass’y Grille
2.Remove the screw on the panel front.
3.Hold the lower part of panel with two hands
while pressing down on both sides of the lower
part of the cabinet, pull it forward by about
30mm,and then lift it up carefully for
removal.(Must un-connect the Displayer with
the controller inside.)
1.Remove 2 screws on the both side of the
cabinet.
2
Ass’y Cabinet
2.Pull the front part both side, and remove the
unit from the cabinet.
1.Remove the earth screw fixed on the cabinet.
3
Ass’y Control
2.Remove 3 screws fixed on the partition and
frame up.
3.Remove the screw fixed for the power cord.
4.Un-connect the motor wire and comp lead
wire, then take out the control box upward.
FRIEDRICH AIR CONDITIONING CO.
4-5
Disassembly and Reassembly Procedure(SP06A10/SP08A10)
No.
Part Name
Procedures
Remarks
1..Remove 2 screws on the frame up and case
cond.
4
Frame up
2.Remove all the screws on the frame up.
3.Pull the frame up upward.
1.Remove 3 screws on the evaporator.
2.Pull the evaporator from frame low carefully.
3.Remove the nut and remove the Blower.
5
Blower
1.Remove 2 screws on the rear side of the
base pan, and all screws fixed on case cond.
6
Case Cond &
Fan Propeller
& Motor Fan
2.Pull up the condenser from the base pan.
3.Remove the nut and remove the Propeller
fan.
4.Remove the earth screw(fix the motor earth
wire), then take out the motor upward.
4-6
FRIEDRICH AIR CONDITIONING CO.
5. Troubleshooting
Check the basic checkpoints first to determine whether it is machine trouble or a problem
in the operation method. When it is not related to the basic checkpoints, perform checking
in accordance with the procedures of troubleshooting by symptom.
5-1 Basic Checkpoints for Troubleshooting
1) Is the voltage of the power source appropriate ?
(1) It should be within the rating voltage ±10% range.
(2) The air conditioner may not operate properly when the voltage is out of this range.
2) Is the connection with the fan motor, compressor wire, and starting condenser
appropriately made ?
3) The symptoms listed in the table below are not indicative of machine trouble.
Symptom
Cause and check
No operation
• Check whether there is power failure or the power plug is pulled out.
• Check whether the unit is stopped as a result of completion
of the sleep time.
• Pull out the power plug for ten seconds, and then insert it again.
Air flows, but
no cooling
• Check whether the Air filter is clogged with dust or is dirty.
• Check whether the desired temperature is too high. Set the desired
temperature to a lower level than the current temperature.
• Check whether it is in "FAN" mode.
The remocon does
not operate
• Check whether battery is completely depleted.
• Check whether the battery is properly inserted.
• Check whether the receiving window of the remocon for the assembly
main PCB is blinded.
• Check whether the remocon is affected by jamming due to a neon sign.
No temperature
setting
• Check whether the unit is in "FAN" mode.
(In "FAN" mode, only the current temperature is displayed, and the
desired temperature is not set.)
❈Checking and Display of Fault Area
ERROR OPERATION
ERROR OPERATION
ROOM THERMISTOR (OPEN OR SHORT)
E1 displayed
FRIEDRICH AIR CONDITIONING CO.
5-1
5-2 Troubleshooting by Symptom
5-2-1 No power
1) Check points
(1) Is the voltage of the power source normal ? (the rating voltage ±10% range.)
(2) Is the electric wire in good contact ?(CN 71, RY 71)
(3) Is the output voltage of the IC01(KA 7812) normal ?(DC 11.5V ~ DC 12.5V)
(4) Is the output voltage of the IC02(KA 7805) normal ?(DC 4.5V ~ DC 5.5V)
Turn off the power, and then turn it on again five
seconds later.
Y
Dose the buzzer sound, when the power on?
Normal operation.
Normal operation.
N
Check whether the "COOLING ICON" LED lamp is
on, and the operation starts when pressing the
ON/OFF button of the remocon.
Y
N
Y
Is the F701(3.15A) fuse blown?
N
Replace the fuse.
N
N
Is the primary voltage of the transformer normal?
(the rating voltage ±10% range.)
Check the power cord and electric wire.
Check and replace the trans.
Y
Is the secondary voltage of the transformer normal?
(AC 13V ~ AC 17V)
Y
N
• Check the BD61 for cold
soldering.
Is the rectifier diode bridge(BD61) normal?
• Replace the rectifier diode
Y
- Is the voltage of DC 17V ~ DC 23V applied at both
ends of the C101 electrolytic condenser?
- Is the voltage of DC 12V applied at both ends of
the C102 electrolytic condenser?
- Is the voltage of DC 5V applied at both ends of
the C103 electrolytic condenser?
• Check both ends of the C101 for
short and cold soldering.
• Check the +12V for a short.
• Check the +5V for a short.
• Check and replace the C101~104.
N
N
Y
• Check the IC01 or IC02 for cold
soldering and a short.
Are the IC01(KA7812) or IC02(KA7805) normal?
• Replace the IC01 or IC02.
Y
Replace the assembly main PCB.
5-2
FRIEDRICH AIR CONDITIONING CO.
Troubleshooting
5-2-2 When the Touch Key pad and Led Display
1) Check points
(1) Is the voltage of the power source normal ? (the rating voltage ±10% range.)
(2) Is the electric wire in good contact ?(CN71, RY71)
(3) Is the connection of the assembly main PCB, and TOUCH KEY PAD in good
contact? (SW01-SW05)
Turn off the power, and then turn it on again
five seconds later.
N
N
When the membrane key is
not operated.
When the LED display is
not operated.
Normal operation
Normal operation
Y
Y
Check the micom
(IC05) for a short,
and replace it.
Is the voltage of the micom
(IC05) No.1, 2, 38~43 port a
square wave?
Check the micom
(IC05) for a short,
and replace it.
Is the voltage of the
micom (IC05) No.13, 14 port
a square wave?
N
N
N
N
N
Y
Y
Is the voltage of the micom
(IC05) No.3, 4, 10, 11, 44
port a square wave?
Check the micom
(IC05) for a short,
and replace it.
Check the micom
(IC05) for a short,
and replace it.
Is the voltage of the micom
(IC05) No.3, 4, 10, 11, 44 port
a square wave?
Y
Y
Check the Q901~
Q905 for a short,
and replace it.
Replace the membrane
key pad.
Is the voltage of the
Q901 ~ Q905 square wave?
Y
Check the IC06
for a short, and
replace it.
Is the voltage of the
IC06 No. 10~16 a square
value?
N
Y
Replace the membrane key pad
FRIEDRICH AIR CONDITIONING CO.
5-3
Troubleshooting
5-2-3 When the remocon is not operated
1) Check points
(1) Is the voltage of the power source normal ? (the rating voltage ±10% range. )
(2) Is the electric wire in good contact ? (CN71, RY71)
(3) Is the assembly main PCB in good contact with the TOUCH KEY PAD(SW01-SW05)
(4) Is the battery voltage of the remocon above DC 2.7V?
Turn off the power, and then turn it on
again five seconds later.
N
Dose the Buzzer sound, when the power on?
Y
Go to the clause "No power".
Check whether the "COOLING ICON" LED lamp is on
and th operation starts when pressing the
on/off button of the remocon.
Y
The remocon is normally operated.
N
N
Is the battery voltage of the remocon above
DC 2.7V?
Replace the battery.
Y
• Check the X-TAL for cold soldering
and a short.
• Replace relevant components.
N
N
Does the X-TAL(RJ 455JB) oscillate normally?
Y
• Check the micom(ICT1) Q1, and
Q2 for cold soldering and a short.
• Replace relevant components.
Is the collector voltage of the remocon Q1, Q2
a square wave?
Y
• Check the R415 components.
• Check the assembly main PCB
micom(IC05).
N
Is the input voltage of the micom(IC05) No.15
pin of the assembly main PCB a aquare wave?
Y
Replace the assembly main PCB.
5-4
FRIEDRICH AIR CONDITIONING CO.
Troubleshooting
5-2-4 When the compressor is not operated
1) Check points
(1) Is the voltage of the power source normal ? (the rating voltage ±10% range. )
(2) Is the desired temperature lower than the indoor temperature in the “COOL” mode?
(Compressor stopped)
(3) Is the starting condenser in good contact?
(4) Is the electric wire in good contact ? (CN71, RY71)
(5) Is the output voltage of the IC01(KA7812) and IC02(KA7805) normal ?
Turn off the power, and then turn it on again five
seconds later.
N
Go to the clause "No power".
Dose the Buzzer sound, when the power on?
Y
N
Y
Check whether the "COOLING ICON" LED lamp is on
and the operation starts when pressing the on/off
button of the remocon.
• Go to the clause "when he remocon
does not operate".
Y
Check whether the compressor is activated in three
minutes after turning on the power with the "CoolING
ICON" LED lamp being switched on when selecting the
cool mode of the remocon.
Normal operation.
N
N
Is the IC03 output normal?
- When the compressor is on, IC03
No. 13 pin → Low.
• Check the IC03 for short and cold
soldering.
• Replace the IC03.
Y
N
N
• Check the relay coil resistance.
(resistance : About 150Ω±20Ω)
• Replace the relay.
Does the relay(RY71) operate normally?
- When the compressor is ON, the RY71 should operate.
Y
• Check the operation of the O.L.P,
and replace it if necessary.
• Check the compressor
Is the compressor normal?
Y
resistance.(0Ω : short, ∞Ω : open)
Replace the compressor.
FRIEDRICH AIR CONDITIONING CO.
5-5
Troubleshooting
5-2-5 When the fan motor does not operated
1) Check points
(1) Is the voltage of the power source normal ? (the rating voltage ±10% range. )
(2) Is the electric wire in good contact ?(CN71, RY71)
(3) Is the starting condenser(FAN MOTOR) in good contact?
(4) Is the fan motor connector in good contact?(CN73)
(5) Is the output voltage of the IC01(KA7812) and IC02(KA7805) normal ?
Turn off the power, and then turn it on again five
seconds later.
N
Go to the clause "No power".
Dose the buzzer sound, when the power on?
Y
Check whether the "COOLING ICON" LED lamp is on
and the operation starts when pressing the
on/off button of the remocon.
N
N
• Go to the clause of "when the
remocon does not operated".
Y
Is the IC03 output normal?
• Check the IC03 for a short and cold
soldering.
• Replace the IC03.
- When the fan motor is High, IC03 No. 12 pin → Low.
- When the fan motor is Med, IC03 NO. 14 pin → LOW.
- When the fan motor is Low, IC03 No. 15 pin →Low.
Y
• Check the relay coil resistance.
(Normal: About 400Ω)
N
N
Does the relay(RY 72, 73,74) operate normally?
- When the fan motor is High, RY74 should operate.
- When the fan motor is Med, RY73 should operate.
- When the fan motor is Low, RY72 should operate.
• Replace the relay.
Y
• Check the fan motor resistance.
(0Ω : short, ∞Ω : open)
• Check the fan motor thermal fuse?
Is the fan motor normal?
Y
Replace the fan motor.
FRIEDRICH AIR CONDITIONING CO.
5-7
6. Exploded View and Parts List
6-1 Main unit
You can search for the updated part code
number through the ITSELF.
FRIEDRICH AIR CONDITIONING CO.
6-1
Exploded View and Parts List
■Part List
Q'TY
No
1
Description
Code No.
Specification
ASSY,HIPS
SP06A10
SP08A10
ASSY PANEL FRONT
DB92-00398B
DB64-00566A
DB64-00567B
DB66-00349A
DB66-00165A
DB61-01009A
DB63-00513A
DB96-01028A
DB90-00328A
DB60-30004A
DB67-00099A
DB31-00149B
DB31-00149A
DB67-50077A
DB60-30020A
DB66-00430A
DB90-00293A
DB92-00395A
DB63-00514A
DB64-00565A
DB64-00564A
DB63-00512A
DB93-01493A
DB32-10051D
DB90-00337A
DB90-20212F
DB96-00995A
DB96-01027A
DB90-00133P
DB92-00113A
DB92-00112A
DB64-00048B
DB61-30219F
DB60-30001A
39A062HS1EA
44A076HU1EB
DB63-10026A
DB35-00006G
DB47-20066B
DB63-20003A
DB60-30028A
DB73-00016A
DB62-01374A
DB62-00484A
DB62-00675A
DB62-00483A
DB93-01633A
DB93-01633B
DB61-00669A
DB61-00670A
DB61-00676A
DB26-00006G
2301-001448
DB39-00343D
2501-001229
2501-001228
DB65-00031A
DB93-01492A
DB63-00511A
DB62-01316A
DB62-01288A
DB97-30156C
DB93-01364X
1
1
1
4
2
1
1
1
1
1
1
1
-
1
1
1
4
2
1
1
1
1
1
1
-
1-1 PANEL FRONT
1-2 GRILLE AIR INLET
1-3 BLADE V
HIPS,-,W343
SEA,HIPS
HIPS,T2.5
1-4 LINK BLADE
1-5 FRAME BLADE
PE,L97.5,T1.3
HIPS
2
3
4
5
6
7
FILTER
HIPS,-,W212
2R×11S,FP1.2
ASSY
EVAPORATOR
ASSY FRAME LOW
NUT-FRANGE
BLOWER
2C M6 SM20C NTR
ABS
MOTER FAN
80/75/70
1.12/1.05/0.99
ABS
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
8
9
FAN-PROPELLER
NUT-FRANGE
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
M6,LEFT
10 LEVER DAMPER
11 ASSY FRAME UP
12 ASSY PANEL CONTROL
12-1 COVER PANEL CONTROL
12-2 PANEL DISPLAY
12-3 PANEL BUTTON
12-4 COVER MODULE
12-5 ASSY PCB PANEL
12-6 THERMISTOR
SC-97471R
ASSY
ASSY
ABS(V5)
ABS(V5)
ABS,-,W18,L90
PC,T1,W23
SEA-PJT,RAC PANEL
10K/25,-,3425K
PP
13 CASE COND
14 ASSY BASE
SGCC-M,SC94445T
2R×15S,FP1.5
3R×15S,FP1.5
ASSY
15 ASSY COND
1
1
1
1
1
2
1
-
16 ASSY CABINET
1
1
1
1
2
1
1
-
17 ASSY SHUTTER-LF
18 ASSY SHUTTER-RH
19 SHUTTER-ANGLE UP
20 BRACKET-INSTALL
21 NUT-TERMINAL COVER
22 COMPRESSOR
SPS-P/J,ASSY
SPS-P/J,ASSY
ASV08FAS2,HIPS,T3.0
SGCC-A
M5,-,SM20C
6200BTU,115V
115V 1PHASE 60HZ 7600
GE,-,NORYL,-,SEI-701
MRA12146-12008
MRA12083-12008
EPDM,T0.8
1
1
-
23 COVER-TERMINAL
24 O.L.P
1
1
-
1
1
3
3
-
25 GASKET
1
3
3
1
-
26 NUT WASHER
27 GROMMET-ISOLATOR
28 TUBE SUCTION
M8,ZPC
EPDM,-,BLK,OK-PJT
C1220T-0
C1220T-0
1
-
29 TUBE DISCHARGE
OD7.93
1
-
C1220T-0
1
-
30 ASSY CONTROL BOX
TOP,ELEC
1
-
TOP,ELEC
1
1
1
1
1
1
1
-
30-1 CASE CONTROL-LOW
30-2 CASE CONTROL-UP
30-3 BRACKET-CONTROL
30-4 TRANSFORMER
30-5 C-FILM
SGCC-M,T0.7
SGCC-M,T0.7
SGCC-M,T0.7
AC115V,50/60HZ,DC17V
8µF,450VAC
125V,13A
1
1
1
1
1
1
1
-
30-6 POWER CORD
30-7 C-OIL
40µF,370VAC
35µF,370VAC
SGCC-M,T0.7
SEA-PJT
1
1
1
1
-
30-8 CLIP CAPACITOR
30-10 ASSY MIAN PCB
30-11 PANEL BONTROL
33 TUBE CAPILLARY
1
1
1
1
-
ABS(V5),-,W140,L98
ID1.3×L600
ID1.42×L900
ASSY
1
1
1
34 ASSY-SCREW
1
1
35 ASSY REMOCON
AS-K410/K610
6-2
FRIEDRICH AIR CONDITIONING CO.
6. Exploded view and part list
6-3 Main unit
FRIEDRICH AIR CONDITIONING CO.
6-3
Exploded View and Parts List
■Part List
Q'TY
No
1
Description
Code No.
Specification
SP10A10
SP12A10
ASSY PANEL FRONT
DB92-00397B ASSY,HIPS
DB64-00694A HIPS,T2.5
DB64-00693B HIPS
1
1
1
4
2
1
1
1
-
1
1
1
4
2
1
1
-
1-1 PANEL FRONT
1-2 GRILLE AIR INLET
1-3 BLADE V
DB66-00369A HIPS,T2.5
DB66-00259A PP,97.5,T1.3
DB61-01174A HIPS
1-4 LINK BLADE
1-5 FRAME BLADE
2
3
FILTER
DB63-00617A HIPS,T2.5
DB96-01001A 2R×12S,FP1.3
DB96-02439A ASSY
EVAPORATOR
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
4
5
6
7
8
9
ASSY PLATE EVAP CASING DB90-00509A ASSY,PP,T2.0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
-
CASE EVAP UP
LEVER DAMPER
CASE EVAP
DB61-00641A 30F0-PS,T15
DB66-00258A HIPS,T2.0
DB61-00640A 30FO-PS
NUT-FRANGE
BLOWER
DB60-30004A 2C M6 SM20C NTR
DB67-50073A ABS,200
10 PLATE PARTITION
11 MOTOR MOUNTER
12 PLATE-REINF
13 MOTOR FAN
DB71-00077B SGCC-M,T0.8
DB61-00650A SGCC-M
DB71-00081A SGCC-M,T1.0
DB31-00122A YGN60-6B
DB67-00139A ABS+G.F20%,D352
DB60-30020A M6,LEFT
14 FAN-PROPELLER
15 NUT-FRANGE
16 CASE COND
DB61-00647A PP,T2,515.6,450
DB96-00982A 2R×17S,FP1.5
DB96-00979A 3R×17S,FP1.4
DB90-00514A ASSY
17 ASSY COND
1
1
1
1
1
1
2
-
18 ASSY BASE
1
1
1
1
1
2
1
-
19 ASSY CABINET
DB90-00364B ASSY
20 SHUTTER ANGLE UP
21 ASSY SHUTTER LF
22 ASSY SHUTTER RH
23 BRACKET-INSTALL
24 COMPRESSOR
DB64-00048C HIPS,T3.0
DB92-00111A ASSY
DB92-00110A ASSY
DB61-30219F SGCC-A
44B098HX1EF 115V,1Ph,60Hz
44B124HX1EL 115V,1Ph,60Hz
44B117HX1EL 115V,1Ph,60Hz
DB62-00712A OD12.7
-
-
1
-
25 TUBE SUCTION
1
-
DB62-00692A OD12.7
1
1
-
26 TUBE DISCHARGE
27 TUBE CAPILLARY
DB62-00327A C1220T-0,OD9.52,T0.7
DB62-00688B OD2.75
1
1
-
DB62-01563A ID1.3×L1100
DB60-30001A M5,-,SM20C
DB63-10026A GE,-,NORYL,-,SEI-701
DB35-00011D MRA12132-12007
DB35-00011M MRA12053-12007
DB63-20003A EPDM,T0.8
DB60-30028A M8,ZPC
1
1
1
-
28 NUT-TERMINAL COVER
29 COVER-TERMINAL
30 O.L.P
1
1
1
-
1
1
3
3
-
31 GASKET
1
3
3
1
-
32 NUT WASHER
33 GROMMET-ISOLATOR
34 ASSY CONTROL BOX
DB73-00016A EPDM,-,BLK,OK-PJT
DB93-01633D ASSY
DB93-01633E ASSY
1
1
1
1
1
1
1
-
34-1 CASE CONTROL-LOW
34-2 CASE CONTROL-UP
34-3 BRACKET-CONTROL
34-4 TRANSFORMER
34-5 C-FILM
DB61-00669A SGCC-M,T0.7
DB61-00670A SGCC-M,T0.7
DB61-00676A SGCC-M,T0.7
1
1
1
1
1
1
1
-
AC115V,50/60HZ,DC17V
DB26-00006G
2301-001452 15µF,250VAC
DB39-00343E 125V,13A,AWG16
2501-001230 45µF,370VAC
2501-001231 50µF,370VAC
DB65-00031A SGCC-M,T0.45
DB93-01492A SEA-PJT
34-6 POWER CORD
34-7 C-OIL
1
1
1
1
1
1
1
1
1
1
1
1
1
34-8 CLIP CAPACITOR
34-10 ASSY MIAN PCB
34-11 PANEL BONTROL
35 ASSY PANEL CONTROL
35-1 COVER PANEL CONTROL
35-2 PANEL DISPLAY
35-3 PANEL BUTTON
35-4 COVER MODULE
35-5 ASSY PCB PANEL
35-6 THERMISTOR
1
1
1
1
1
1
1
1
1
1
1
1
DB63-00511A ABS(V5),-,W140,L98
DB92-00395A ASSY
DB63-00514A ABS(V5)
DB64-00565A ABS(V5)
DB64-00564A ABS,-,W18,L90
DB63-00512A PC,T1,W23
DB93-01493A SEA-PJT,RAC PANEL
DB32-10051D 10K/25,-,3425K
DB97-30156C ASSY
37 ASSY-SCREW
38 ASSY REMOCON
DB93-01364X AS-K410/K610
6-4
FRIEDRICH AIR CONDITIONING CO.
7. Block Diagram
7-1 Refrigerating Cycle Block Diagram
PINCH PIPE
SUCTION LINE
DISCHARGE LINE
(SERVICE VALVE)
ACCUMULATOR/COMPRESSOR
EVAPORATOR
CONDENSER
CAPILLARY TUBE
PINCH PIPE
(SERVICE VALVE)
7-2 Basic Structure
7-2-1 Micom Control Diagram
MAIN MICOM
A/D converter
Membrane Pad control
(Key operation)
Room Temperature sensor
Receiving Unit of Remocon
• Energe saver
↑, ↓
• Temp.set(
)
• Operation, Mode
• Swing, Sleep
• Fan select, Timer
(Remote Control)
Led display control
(Remocon control)
• Remocon single contro
Operation
l
Dry
Remocon Single
Receiving
Timer
Sleep
Compressor
Fan motor
Fan speed (high)
Fan speed (med)
Fan speed (low)
Fan
• Compressor control
• Buzzer control
• Temperature control
• Fan motor control
Power circuit (DC 5V)
Powercircuit (DC 12V)
Cool
Energy saver
Temp.setting(↑)
Temp.setting(↓)
Down Trans (AC15V)
Power input (AC220V)
Reset Circuit
Oscillation Circuit
FRIEDRICH AIR CONDITIONING CO.
7-1
Block Diagram
7-2-2 Micom pin assignment
KS88C4716
1
2
3
4
5
6
7
8
9
P0.1
P4.4
P0.2
P0.3
P0.4
P0.5
P0.6
P0.7
P1.0
P1.1
P1.2
P1.3
P1.4
P1.5
P3.7
P3.6
P3.5
P3.4
P3.3
P3.2
P3.1
P3.0
AVss
44
43
42
41
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
SEG-DATA(c)
SEG-DATA(b)
GRID4
GRID5
P0.0
P4.3
P4.2
VDD
VSS
Xout
Xin
SEG-DATA(d)
SEG-DATA(e)
SEG-DATA(f)
SEG-DATA(g)
SEG-DATA(h)
SEG-DATA(a)
EEPROM CLK
EEPROM IN
EEPROM OUT
BUZZER
GRID3
Vcc
Vss
10MHz RESONATOR
10MHz RESONATOR
TEST
TEST
10 P4.1
11 P4.0
12 RESET
13 P2.0
14 P2.1
15 P2.2
16 P2.3
17 P2.4
18 P2.5
19 P2.6
20 P2.7
21 P4.5
22 AVref
GRID2
GRDI1
RESET IC OUTPUT
KEY-IN1
OPTION
JIG OUTPUT
OPTION
KEY-IN2
REMOCON
EEPROM CS
LOW FAN
SENSOR THERMIS-
TOR(103AT)
OPTION
COMPERSSOR
MIDDLE FAN
HIGH FAN
4-WAY VALVE
Vcc
OPTION
OPTION
OPTION
SAVE OPTION
SWING MOTOR
GND
7-2
FRIEDRICH AIR CONDITIONING CO.
MEMO
FRIEDRICH AIR CONDITIONING CO.
7-3
8. PCB Diagram
8-1 ASS’Y Main PCB
Main PCB
DB93-01493A
DB93-01493B
Power PCB
DB93-01492A
8-1
FRIEDRICH AIR CONDITIONING CO.
PCB Diagram
I Part List
Q'TY
NO.
DESCRIPTION
SPECIFICATION
REMARK
DB93-01492A
1 CHIP IC
ULN2003AD
DF06S
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
4
1
3
1
1
1
IC03
BD61
IC02
IC01
C105
C101
C106
C103
2 BRIDGE DIODE
3 REGULATOR
4 REGULATOR
5 C-AL
KA7805
KA7812
100µF/10V
1000µF/35V
22µF/15V
2200µF/25V
6 C-AL
7 C-AL
8 C-AL
9 C-CHIP
104Z 0805 50V
1/2W(SMALL
PZ-227125
C102,C104
10 R-CARBON
11 BUZZER
R601
BZ61
12 HEAR SINK
13 CONNECTOR
14 CONNECTOR
15 CONNECTOR
16 HARNESS
17 FUSE
-
L15 W15,H25
RED
CN12
CN11
VH-4A WHT
VH-5A WHT
DB39-00807A
250V T3 15A TIME DELAY
250V F1A,FAST ACTING
HF-004/J
CN51
CN91
F701
18 FUSE
F702
19 FUSE HOLDER
20 RELAY POWER
21 RELAY POWER
22 SCREW TAPPING
23 JUMP WIRE
24 PCB-MAIN
-
DI1U 12VDC
RY71
JQ1A-12V
RY72-RY74
-
PH3 L10
J1
-
PH0.6 L7.5MM
FR-1
FRIEDRICH AIR CONDITIONING CO.
8-2
PCB PARTS
■Part List
Q'TY
NO.
DESCRIPTION
SPECIFICATION
REMARK
DB93-01493A DB93-01493B
1
2
3
4
5
6
7
8
9
CHIP IC
ULN2003AD
1
1
4
3
4
1
1
3
3
3
1
1
2
3
8
3
1
1
-
1
1
4
3
4
1
1
3
3
3
1
1
2
3
8
3
1
-
IC06
IC04
IC
RA7533OZ
DIODE-SWITCHING
LED
1N4148(SMALL),DO-35
B5054D3,GREEN
KRA226S
D901-D904
LED01-LED03
Q901-Q904
Q905
CHIP TRANSISTOR
CHIP TRANSISTOR
C-CHIP
KRC246S
101k,0805,50V
102k,0805,50V
104z,0805,50V
223z,0805,50V
1.74k,0805,1%
1206,5%
C401
C-CHIP
C301,C302,C402
C-CHIP
C701,C702,C801
10 C-CHIP
C201-C203
11 R-CHIP
R704
12 JUMP WIRE
13 R-CHIP
J5
1k,0805,5%
R101,R102
14 R-CHIP
10k,0805,5%
R403,R501,R701
15 R-CHIP
180,1206,5%
330,0805,5%
10k,0805,1%
R901-R908
16 R-CHIP
R401,R402,R802
17 R-CHIP
R702
18 R-CHIP
4.7k,0805,5%
10k,0805,5%
R703
R-CHIP
1
1
5
1
1
10
5
1
1
1
1
1
R703
19 R-CHIP
6.8k,0805,5%
TSTB-2,160GF
SMAW250-02,RED
DB39-00806A
PH0.6,L7.5mm
PH0.6,L10mm
FR-1,124*65*1mm
CSD-322GLH
FRP-4021H6
1
5
1
1
10
5
1
1
1
1
1
R801
20 SWITCH-TACT
21 CONNECTOR
22 HARNESS
23 JUMP WIRE
24 JUMP WIRE
25 PCB-MAIN
26 LED DISPLAY
27 REMOCON MODULE
28 CHIP MCU
SW01-SW05
CN41
CN92
J1,J2,J4,J6,J9,J10,J13-J16
J3,J7,J8,J11,J12
-
LED04
RM41
IC05
X501
3P8475*ZZ-OZR5
29 CERAMIC RESOATOR 10MHZ,0.5%
8-3
FRIEDRICH AIR CONDITIONING CO.
9. Wiring Diagram
FRIEDRICH AIR CONDITIONING CO.
9-1
10. Schematic Diagrams
10-1 PCB
TN71
TRANS
AC230V/115V
AC INPUT
CN12
SMW250-03
(RED)
CN11
VH-4A
(WHT)
+
12V
5V
+
IC01
BD61
DF06S
3
1
3
1
2
1
2
IC02
F701
T3.15A 250V
KA7812
KA7812
COMPRESSOR
CAPACITOR
F702
1A 250V
C105
100uF
10V
C106
22uF
16V
C101
1000uF
35V
C102
104
C103
2200uF
25V
C104
104
3
4
3
4
1
S
RY71
DI1U-DC12V
R
C.M
O.L.P
C
COMPERSSOR
1
RY72
12
13
5
+
12V
2
3
HIGH
FAN MOTOR
CAPACITOR
4
RY71
RY73
COMP
14
15
16
11
3
2
1
6
4
5
MID
FAN MOTOR
S
RY74
LOW
BZ61
PZ-227125
JQ1a-12V RY72
JQ1a-12V RY73
HIGH
HIGH
6
7
8
1
3
5
R601
1/2W 620-J
MID
MID
F.M
JQ1a-12V RY74
10
9
7
8
LOW
LOW
M
+
12V
PCB POWER
PCB MAIN
+5V
R101
1K-J
1/8W
IC04
KA7533Z
1
RM41
17
12
RESET
P2.4/INT4
P2.5/INT5
2
3
4
5
6
REMOCON
MODULE
FRP-4021H6
R402
330-J
1/8W
C201
223
R102
1K-J
1/8W
18
19
20
34
+5V
VCC
OUT
GRD
P2.6/INT6
P2.7/INT7
P1.3/BUZ
15
P2.2/INT2
R402
10K-J
1/8W
R402
330-J
1/8W
C401
101
C402
102
P2.1/INT1
P2.0/INT0
14
13
7
8
SW94
TEMP.SET.
Sw90
TEMP.SET.
1N4148*5
D901
C301
101
C302
102
IC05
SW91
OPERATION
D903
D902
D901
S
3
C
8
4
7
5
22
5
Vdd
Avr
SW96
MODE
+5V
+5V
SW95
FAN
Test
Avss
Vss
9
C301
102
C202
23 223
6
+5V
R501
10K-J
1/8W
32
11
P1.5/Tx0
P4.0
KRA226S*4
Q901
+5V
1
3
7
Xout
Xin
10
4
30PF
30PF
P4.1
P4.2
2
+5V
Q903
CN41
SMAW250-02
(RED)
8
P4.3
P4.4
3
R801
6.8K-F
1/8W
Q902
44
X501
10.0MHZ
D2
Q904
D1
31
IC06
VLN2003
P3.7/ADC7
2
1
2
1
103AT
100-J 1/4W*8
R907
R802
330-J
1/8W
2b
P0.0
P0.1
P0.2
1b
1c
2
1
1
2
16
15
C801
104
R906
2c
SENSOR
THERMISTOR
R905
R904
R903
2d
2e
2f
1d
1e
1f
43
3
4
5
6
14
13
12
11
LED01
SAVE
+5V
P0.3 42
R701
10K-J
1/8W
R702
10K-F
1/8W
41
P0.4
P0.5
25
26
P3.1/ADC1
P3.2/ADC2
R902
R901
2g
2a
1g
1a
40
38
P0.7
P0.8
7
8
10
9
R703
4.7K-J
1/8W
R704
OPTION
C702
104
C701
104
39
LED01
HR
LED01
HR
R908
Q905
KRC246
LED04
CSD-322GLH
10-1
FRIEDRICH AIR CONDITIONING CO.
FRIEDRICH AIR CONDITIONING CO.
Post Office Box 1540 l San Antonio, Texas 78295-1540
4200 N. Pan Am Expressway l San Antonio, Texas 78218-5212
(210) 357-4400 l FAX (210) 357-4480
Printed in China
|