Friedrich A SERIES User Manual

INSTALLATION &  
OPERATION GUIDE  
VERT-I-PAK® A-SERIES  
SINGLE PACKAGE  
VERTICAL AIR  
CONDITIONING SYSTEM  
9,000 - 18,000 BTU/h  
920-075-08 (10-06)  
920-075-08  
Vert-I-Pak Installation Recommendations  
For proper unit performance and maximum operating life please refer to the minimum installation clearances below.  
Figure 1  
VERT-I-PAK® units must be installed on an outside wall. Conned spaces and/or covered areas should be  
avoided. Units should be installed no closer than 12" apart when two units are side by side. If three of more  
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical  
clearance of 60" should be maintained between units. Units installed on the bottom oor should be mounted  
at least 6" off of the ground.  
B
6"  
A
60" 60"  
SMALL RECESS OK  
LARGER RECESS OK. IF A> 5xB  
60"  
60"  
60"  
60"  
60"  
60"  
60"  
60"  
60"  
6"  
6"  
12"  
Figure 2  
BUILDING  
Any time obstructions are present use  
the following guidelines for proper  
spacing from the VERT-I-PAK louver:  
60"  
24"  
VPAK  
VPAK  
VPAK  
12"  
• For minor obstructions such as lamp  
poles or small shrubbery a clearance  
of 24" from the outdoor louver should  
be maintained.  
24"  
72"  
• For major obstructions such as a solid  
fence, wall or other heat rejecting  
device like a condensing unit, a mini-  
mum distance of 72" should be kept.  
SHRUB  
POLE  
OUTDOOR  
CONDENSING  
UNIT  
FENCE  
MAJOR OBSTRUCTION  
The above suggestions are for reference only and do not represent all possible installations. Please contact the factory  
for information regarding affects of other installation arrangements.  
By following these simple recommendations you can be condent that your Friedrich Vert-I-Pak® will provide years  
of worry-free operation.  
3
920-075-08  
Section I. General Specications  
Vert-I-Pak® Model Identication Guide  
MODEL NUMBER  
V
E
A
09  
K
34 RT H  
ENGINEERING CODE  
SERIES  
V=Vertical Series  
OPTIONS  
RT = Standard Remote Operation  
E =Cooling with electric heat  
H =Heat Pump  
ELECTRIC HEATER SIZE  
DESIGN SERIES  
A = 32"/47" Cabinet  
A Series  
25 = 2.5 KW  
34 = 3.4 KW  
50 = 5.0 KW*  
75 = 7.5 KW**  
NOMINAL CAPACITY  
A Series (Btu/h)  
09 = 9,000  
12 = 12,000  
18 = 18,000  
24 = 24,000  
Refer to electrical data chart for heater/unit compatibility.  
* Not available on 9000 BTU models.  
** 24000 BTU only.  
VOLTAGE  
K = 208/230V-1Ph-60Hz  
Vert-I-Pak® Chassis Specications  
MODEL:  
V(E,H)A09  
230 / 208  
R-22  
V(E,H)A12  
230 / 208  
R-22  
V(E,H)A18  
230 / 208  
R-22  
Voltage (V)  
Refrigerant  
Chassis Width  
23.125"  
23.125"  
32.25"  
23.125"  
23.125"  
32.25"  
23.125"  
Chassis Depth  
23.125"  
Chassis Height **  
32.25"  
Shipping W x D x H  
Supply Duct Collar ***  
Drain Connection  
Min. Circuit Amps  
CFM Indoor  
26.00" x 28.50" x 35.00"  
26.00" x 28.50" x 35.00"  
10"  
26.00" x 28.50" x 35.00"  
10"  
10"  
3/4" FPT  
3/4" FPT  
3/4" FPT  
See Chassis Nameplate  
See Charts 2 & 3 (Page 10)  
.3 in. water  
Max. Duct ESP  
.3 in. water  
.3 in. water  
NOTES:  
** Height includes 2" duct collar & isolators under unit.  
*** Factory collar accepts 10" ex duct.  
4
920-075-08  
II. Installation  
1) Utility Closet Dimensions  
Recommended utility closet dimensions and a typical indoor installation are illustrated in Figure 3. Three inches minimum clearance on  
three sides of the unit must be allowed for return airow, installation access and service access. See Figures 3 and 4 for clearances  
and reference dimensions.  
Uy os
Figure 3  
Chassis Shown in Closet, on Optional Platform  
25" x 20" Filter  
(Field Supplied)  
Rigid Ductwork  
Electrical  
Connection  
Exterior Wall  
Flexible Ductwork  
VPAWP1-8/1-14  
Wall Plenum  
Plenum Divider  
Thermostat  
Wiring  
VPRG4 Access Panel and  
Return Air Filter Grille  
Power  
Disconnect  
See Figure 8, Page 10  
for return air options  
3/4" FPT Drain  
Connection  
Optional eld  
installed dran pan  
(refer to local codes)  
• Vert-I-Pak Chassis dimensions:  
1
1
1
8
8
4
23 / " wide x 23 / " deep x 32 / " high.  
Chassis installs  
• VPAWP1-8/1-14 Wall Plenum cut-out  
3
8
2 / " into Plenum  
5
7
8
8
dimensions 24 / " wide x 30 / " high.  
• VPRG4 Access Panel cutout dimensions:  
Optional  
Platform  
3
4
27" wide by 55 / " high.  
3" Clearance on all three sides  
minimum for service and installation.  
• See Figure 9 (Pg 11) for proper chassis  
installation.  
Figure 4  
Top View  
Outside Wall  
5
920-075-08  
2) Wall Plenum and Architectural Louver Installation  
A. Install the wall plenum (VPAWP1-8/1-14) components in accordance with the installation instructions provided with each accessory.  
IMPORTANT REMINDER: FRIEDRICH WALL PLENUM IS NOT DESIGNED TO CARRY STRUCTURAL  
LOADS. PROPER WALL HEADER CONSTRUCTION IS REQUIRED. THE PLENUM REQUIRES  
PROPER FLASHING, SHIM AND CAULK FOR A WEATHER RESISTANT INSTALLATION.  
B. Ensure that the divider is adjusted properly for the depth of the wall in accordance with the accessory installation manual  
.
Figure 5  
Wall Plenum & Outdoor Louver Installation  
Proper Header  
Caulk all 8  
ange corners  
Proper Flashing  
Proper Caulking  
Inside Wall Plenum  
(Part B)  
Outside Wall  
Proper Caulking  
Architectural louver VPAL2 mounted  
on the outside wall plenum (Part A)  
Proper Flashing  
• Rough opening dimension 24 5/8" wide x 30 7/8" high.  
• Ensure that the bottom of the plenum is 3/4" from the oor of the closet.  
• For proper airow, maintain a minimum distance of 12" between Vert-I-Pak units (see Figure 1, page 3).  
Consult the factory for any installation or application questions.  
6
920-075-08  
3) Electrical Data  
Electrical Data  
Model  
Voltage ( V) 230/208 230/208 230/208 230/208 230/208 230/208 230/208 230/208 230/208  
LRA - Comp. (A)  
21  
21  
21  
4.4/4.9  
30  
24.0  
5.5/6.1  
15  
24.0  
24.0  
47  
47  
47  
Cooling Current (A) 4.4/4. 9 4.4/4. 9  
5.5/6.1 5.5/6.1 9.2/10.2 9.2/10.2 9.2/10.2  
MIN. Ckt. Amps (A)  
Power Connection  
15  
20  
20  
30  
15  
20  
30  
HARD WIRED  
HARD WIRED  
HARD WIRED  
Sample Nameplate (see your chassis nameplate)  
MODEL NO 1  
SERIAL NO *  
FRIEDRICH AIR CONDITIONING CO.  
SAN ANTONIO, TEXAS  
LISTED  
120524  
WARNING  
HEATING AND  
VOLTS: 24,33,34  
COOLING EQUIPMENT  
VOLTAGE RANGE: 255-197  
REFRIG CHARGE: 7 OZS. R22  
DESIGN PRESSURE: 575 PSIG HS / 150 PSIG LS  
COOLING: BTU/HR 8  
SEER: 10  
HEAT PUMP BTU/HR: 14  
TOTAL COOLING AMPS: 9  
TOTAL ELEC. HEAT AMPS: 15  
ELECTRIC HEAT WATTS: 18  
ELECTRICAL SHOCK AND  
MOVING PARTS HAZARD  
CAN CAUSE INJURY OR  
DEATH  
PULL OUT DNECT  
HEALOCATD ON THE  
ONT F THIS UNIT TO  
ISABLE POWER BEFORE  
SERVICING.  
APPLICABLE PATENTS:  
US 6,065,296  
COP: 16  
NY MEA NO.: 295-00-E  
USE ONE OF THE  
FOLLOWING ITEMS  
FROM EACH CATEGORY  
TO COMPLETE THE  
ASSEMBLY  
FOR PERMANENTLY CONNECTED UNITS ONLY:  
COMP'. PLA 11 LRA 12  
MOTOR: FLA 13 HP 19  
HEATER AMPS: 17  
MIN. CKT AMP ~0 USE ~1 MAX. TIME DELAY FUS
OR HACR TYPE CIRCUIT BREAKER.  
WALL PLENUM:  
VPAWP1 -8  
VPAWP1 -14  
OUTDOOR GRILLE  
VPAL2  
GENERAL UNIT INFORMATION:  
MAX OUTLET AIR TEMPERATURE: 2OO'F  
MAX EXTERNAL STATIC PRESSURE ELECTRIC  
HEAT'..5 IN. WATER  
INDOOR GRILLE  
VPRG1  
"O" CLEARANCE TO COMBUSTIBLE MATERIAL  
VPRG2  
VPRG5  
USE ON SINGLE OUTLET CIRCUIT ONLY  
Important: all 208/230v chassis must be hard wired with properly sized breaker. See nameplate for specic chassis  
electrical requirements. See page 8 - Figure 5 for unit wiring and wall thermostat wiring. See page 8 for wire size. Use  
HACR type breakers to avoid nuisance trips. All eld wiring must be done in accordance with nec and local codes.  
7
920-075-08  
3) Electrical Data (continued)  
Electrical Rating Tables  
Figure 6  
NOTE: Use copper conductors ONLY. Wire sizes are per  
NEC. Check local codes for overseas applications  
Electrical Requirements  
Note: All eld wiring must comply with NEC and local codes. It  
is the responsibility of the installer to insure that the electrical  
codes are met.  
Recommended branch circuit wire sizes*  
AWG Wire size**  
Nameplate  
maximum circuit  
breaker size  
Use ONLY wiring size recommended for single  
outlet branch circuit.  
Wire Size  
15A  
20A  
30A  
14  
12  
10  
Use ONLY type and size fuse or HACR circuit  
breaker indicated on unit's rating plate (See sample  
on page 6). Proper current protection to the unit is  
the responsibility of the owner.  
Fuse/Circuit  
Breaker  
AWG — American Wire Gauge  
* Single circuit from main box  
** Based on copper wire, single insulated conductor at 60°C  
Unit MUST be grounded from branch circuit to  
unit, or through separate ground wire provided on  
permanently connected units. Be sure that branch  
circuit or general purpose outlet is grounded.  
Grounding  
Wire Sizing  
Use recommended wire size given in tables and  
install a single branch circuit. All wiring must comply  
with local and national codes. NOTE: Use copper  
conductors only.  
CAUTION  
Electric shock hazard.  
Turn OFF electric power before service  
or installation.  
All electrical connections and wiring MUST  
be installed by a qualied electrician and  
conformtotheNationalElectricalCodeand  
all local codes which have jurisdiction.  
Failure to do so can result in property  
damage, personal injury and/or death.  
8
920-075-08  
3) Electrical Data (continued)  
Figure 7  
Electrical & Thermostat Wiring Diagrams  
208V 240V  
RT4  
THERMOSTAT  
(FRONT)  
Note: the diagram above illustrates the typical thermostat wiring and 208 volt transformer wiring.  
See the unit control panel for the actual unit wiring diagram and schematic.  
9
920-075-08  
4) Indoor Return Air Grille Installation  
There are two Indoor Return Air Grille options as shown in Figure 8. Choose the option that best suits your needs. Use the installation  
instructions provided with accessories for installation details.  
Figure 8  
Return Air Grille Options  
Option 1  
VPRG4  
Return Air Grille with Access Panel  
A eld-supplied (25" x 20") lter is  
mounted inside the hinged access door.  
Option 2  
All Vert-I-Pak chassis are shipped with a  
14 x 20 lter installed. If an accessory lter  
holder is to be used, you MUST remove the  
factory shipped lter from the chassis. Do  
Field Supplied  
Return Air Grille  
NOT use two lters  
Must have a minumum of  
220 square inches of free  
area.  
Notes:  
A. These are the Friedrich recommended return air grille / lter / access panel arrangements. Consult the factory on other  
arrangements. Improper return air arrangements will cause performance problems.  
B. Return air arrangements are shown from the front, but can also be installed from the right or left side of the unit.  
10  
920-075-08  
5) Ductwork Preparation  
6) Chassis Installation  
1) Duct ESP:  
Install the following components as shown in Figure 5.  
To determine your system's indoor external static pressure  
(ESP, in inches of water) use a duct calculator (as provided  
by your duct supplier). Include all ex duct transitions and  
discharge grille(s). If ex duct is used, be sure all the slack  
is pulled out of the ex duct. Flex duct ESP can increase  
considerably when not fully extended. DO NOT EXCEED a  
total of .30 ESP, as this is the MAXIMUM design limit for the  
VERT-I-PAK A-Series unit.  
A. Ensure that the wall plenum is installed in accordance with  
the VPAWP1-8/1-14 Installation Manual.  
B. Place the chassis into the closet with the outdoor side  
facing the wall plenum opening.  
C. Slide the chassis into the wall plenum until the plenum  
divider seal is established. (See Figure 9)  
2) Determining the Indoor CFM: Chart A – CFM  
Figure 9  
ESP (")  
BTU/h  
.00  
Capacity  
Slide-in View / Chassis Installation  
18000  
12000 / 9000  
520  
510  
500  
490  
420  
410  
370  
330  
.10  
.20  
.30  
3) Correct CFM (if needed):  
Chart B – Correction Multipliers  
Correction Multipliers for:  
The Vert-I-Pak chassis must be inserted into the wall plenum so that the  
plenum divider gasket makes contact with the plastic condenser bafe on  
230V  
208V  
1.00  
0.97  
1.00  
0.95  
3
8
the unit. The chassis will t approximately 2 / " into the wall plenum.  
Heating  
Cooling  
11  
920-075-08  
7) Chassis Final Connections  
With the chassis in place, you are now ready to begin chassis  
connections:  
A. Move the thermostat switches to "OFF" and "AUTO." This  
will keep the thermostat from cycling the chassis until nal  
connections are complete.  
Electrical shock and moving parts hazard can cause injury  
or death. If you have not done so, pull out the disconnect  
head found on the front of chassis before continuing instal-  
lation! Disconnect external power at the breaker.  
B. Connect the ductwork onto the 10" collar. Plastic wireties (eld  
supplied) are suggested to secure the ductwork in place. Use  
2 wire ties, one for each inner and outer ex duct sleeve.  
C. Using the two 3/4" plugs supplied with the unit, plug two of  
the condensate drain holes. Connect a drain to the third  
condensate exit location. Be sure to use teon tape or  
approved pipe sealant on all drain connections and plugs.  
(See Figure 10.)  
D. For 208 Volt power only: you must move the transformer wire  
as shown in Figure 7, Page 9.  
E. Review the Final Installation Checklist on Page 12 before  
replacing the power quick disconnect, reconnecting power  
to the chassis, plugging in the remote thermostat harness, or  
operating the chassis.  
RT4 Digital Thermostat  
8) Final Installation Checklist  
Figure 10  
Drain Conn
and Locatio
Correct line voltage?  
Chassis deck level?  
Plenum divider bafe installed?  
Wall plenum caulked? Level? Flashing?  
1
8
7 /  
3"  
7
8
8 / "  
HACR type breaker/fuse?  
1
8
17 x 2 /  
CAUTION  
Single circuit only?  
The unit ba
rear) for connecting an external condensate drain.  
Ductwork connected?  
A eld supplied condensate drain system must be  
connected to one of the three (left, right, or rear) 3/4"  
FPT connections on the unit basepan. Use of rear tting  
may result in staining of the outside wall.  
Chassis weather seal in place?  
The remaining two connections must be plugged using  
the two 3/4" pipe plugs (provided) and eld supplied  
teon tape or pipe joint compound.  
Wall thermostat wired correctly?  
Chassis inserted into plenum?  
The addition of a secondary drain pan may be required.  
Follow all applicable codes.  
Failure to follow these procedures may result in serious  
property damage.  
A eld supplied secondary condensate pan may be  
applied. Check with local codes.  
12  
920-075-08  
Follow all codes when working with the condensate drain  
III. Chassis Operation  
9) Remote Thermostat Control  
system. A secondary drain pan may be placed beneath the  
chassis to prevent condensated spillage due to improper  
installation or unit malfunction.  
The chassis requires a simple single stage heat-cool wall thermostat.  
Each chassis comes with a terminal strip located in the electrical  
control box. All internal chassis wiring (low & high voltage) is factory  
ready for 230 Volt operation. For 208 Volt operation a single wire  
MUST BE CHANGED ON THE TRANSFORMER. Refer to Figure  
7 on page 9.  
IV. Service & Warranty  
14) Servicing / Chassis Quick Changeouts  
The chassis is designed for quick disconnect and change out. For  
minor electrical service, the control box cover lifts straight up after  
the screws & disconnect head are removed. For major electrical,  
refrigeration and fan service the chassis must be removed from  
utility closet.  
10) Low Ambient Protection  
Each chassis is equipped with Low Ambient Protection in the form of  
a suction line thermostat. This thermostat will prevent compressor  
operation at low suction line temperatures. Each chassis is also  
equipped with a factory installed bellows that will drain water from  
the base pan to prevent the fan slinger from freezing during winter  
weather.  
To Remove the Chassis from the Closet:  
A Switch the wall thermostat off.  
B Pull the power disconnect located in the front of the chassis.  
11) Heating Defrost (Heat Pump Models Only)  
C Turn off all power to the unit at the main breaker or  
disconnect.  
All Heat Pumps have a passive heating defrost system. Defrost  
occurs as needed and automatically switches to electric heat during  
defrost. When the outdoor ambient temperature drops below a 45°F  
factory setting, the chassis automatically switches to electric heat.  
As outdoor ambient temperatures rise above 45°F, the chassis  
returns to the heat pump mode. The changeover temperature is user  
adjustable from approximately 32°F - 55°F. The defrost thermostat  
may also be used to lock out the compressor in an emergency  
heat situation.  
D Disconnect the thermostat wiring.  
E Disconnect the electrical connection.  
F Disconnect the ductwork.  
G Disconnect the drain connection.  
H Slide the chassis out of the wall plenum.  
I Lift the chassis out of the utility closet.  
12) Fresh Air Door  
15) Warranty  
The Fresh Air Door is an "intake" system. The fresh air door is  
opened via a slide on the front of the chassis located just above  
the indoor coil. Move the slide left to open and right to close the  
fresh air door. The system is capable of up to 60 CFM of fresh air  
@ ~.3" H20 internal static pressure.  
All service work must be done by a qualified servicer. See  
Warranty on the next page, and consult your dealer or contractor  
for details.  
13) Condensate Disposal System  
The internal drain connections are 3/4" FPT ttings on the right, left  
and outdoor side of the unit. See Figure 10 on page 12. The chassis  
is designed with a condensate drain system that has 3 parts. The  
three parts work as follows:  
Electrical shock and moving parts hazard can cause injury  
or death. Pull out the disconnect head found on the front  
of the chassis before servicing.  
Part 1: The system’s rst stage increases energy efciency  
utilizing a factory installed fan that slings the cold  
condensate onto the hot outdoor coil.  
Part 2: When high outdoor humidity prevents the slinger from  
disposing of all the condensate, the excess condensate  
overows into the internal drain connection.  
Part 3: If Parts 1 & 2 fail for any reason, excess condensate  
overows from a spillway directly into the wall plenum  
to the outside of the building. IF THIS OCCURS, THIS  
IS YOUR WARNING THAT THE CHASSIS OR DRAIN  
NEEDS SERVICING.  
13  
920-075-08  
Friedrich Air Conditioning Company  
P.O. Box 1540  
San Antonio, TX 78295  
210.357.4400  
VERT-I-PAK® A SERIES  
SINGLE PACKAGE VERTICAL AIR CONDITIONERS  
LIMITED WARRANTY  
SAVE THIS CERTIFICATE. It gives you specific rights, you may also have other rights which may vary from state to state and province to  
province.  
In the event that your unit needs servicing, contact your nearest authorized service center. If you do not know the nearest service center,  
ask the company that installed your unit or contact us - see address and telephone number above. To obtain service and/or warranty parts  
replacement, you must notify an authorized FRIEDRICH Air Conditioning Co. service center, distributor, dealer, or contractor of any defect  
within the applicable warranty period.  
When requesting service: please have the model and serial number from your unit readily available.  
Unless specified otherwise herein, the following applies:  
FRIEDRICH VERT-I-PAK A SERIES VERTICAL AIR CONDITIONERS AND HEAT PUMPS  
LIMITED WARRANTY - FIRST YEAR (Twelve (12) months from the date of installation). Any part found to be defective in the material  
or workmanship will be repaired or replaced free of charge by our authorized service center during the normal working hours; and  
LIMITED WARRANTY - SECOND THROUGH FIFTH YEAR (Sixty (60) months from the date of installation). ON THE SEALED  
REFRIGERATION SYSTEM. Any part of the sealed refrigeration system that is defective in material or workmanship will be repaired or  
replaced free of charge (excluding freight charges) by our authorized service center during normal working hours. The sealed refrigeration  
system consists of the compressor, metering device, evaporator, condenser, reversing valve, check valve, and the interconnecting tubing.  
These warranties apply only while the unit remains at the original site and only to units installed inside the continental United  
States, Alaska, Hawaii, Puerto Rico and Canada. The warranty applies only if the unit is installed and operated in accordance with  
the printed instructions and in compliance with applicable local installation and building codes and good trade practices. For  
international warranty information, contact the Friedrich Air Conditioning Company - International Division.  
Any defective part to be replaced must be made available to FRIEDRICH in exchange for the replacement part. Reasonable proof must be  
presented to establish the date of install, otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty  
days. Replacement parts can be new or remanufactured. Replacement parts and labor are only warranted for any unused portion of the  
unit’s warranty.  
We will not be responsible for and the user will pay for:  
1. Service calls to:  
A) Instruct on unit operation. B) Replace house fuses or correct house wiring. C) Clean or replace air filters. D) Remove the unit  
from its installed location when not accessible for service required. E) Correct improper installations.  
2. Parts or labor provided by anyone other than an authorized service center.  
3. Damage caused by:  
A) Accident, abuse, negligence, misuse, riot, fire, flood, or acts of God. B) Operating the unit where there is a corrosive atmosphere  
containing chlorine, fluorine, or any damaging chemicals (other than in a normal residential environment). C) Unauthorized  
alteration or repair of the unit, which in turn affects its stability or performance. D) Failing to provide proper maintenance and  
service. E) Using an incorrect power source. F) Faulty installation or application of the unit.  
We shall not be liable for any incidental, consequential, or special damages or expenses in connection with any use or failure of  
this unit. We have not made and do not make any representation or warranty of fitness for a particular use or purpose and there  
is no implied condition of fitness for a particular use or purpose. We make no expressed warranties except as stated in this  
certificate. No one is authorized to change this certificate or to create for us any other obligation or liability in connection with  
this unit. Any implied warranties shall last for one year after the original purchase date. Some states and provinces do not allow  
limitations on how long an implied warranty or condition lasts, so the above limitations or exclusions may not apply to you. The provisions of  
this warranty are in addition to and not a modification of or subtraction from the statutory warranties and other rights and remedies provided  
by law.  
In case of any questions regarding the provisions of this warranty, the English version will govern.  
(10-06)  
14  
920-075-08  
V. Vert-I-Pak Accessories  
MODEL  
DESCRIPTION  
PHOTO  
WALL PLENUM Two-part sleeve that telescopes in and out  
from 5 1/2" to 8" in depth. The wall plenum sits inside the  
exterior wall penetration.  
VPAWP1-8  
DIMENSIONS: 30 3/8" high x 24 1/8" wide.  
CUTOUT DIMENSIONS: 30 7/8" high x 24 5/8" wide.  
VPAWP1-14  
Same as VPAWP1-8, but telescopes 8" to 14" as required.  
ARCHITECTURAL LOUVER Extruded aluminum louver  
that attaches to the outdoor section of the wall plenum.  
DIMENSIONS: 31 1/16" high x 25 9/16" wide.  
VPAL2  
VPSC2  
Same as VPAL2 but can be ordered in a special color to  
match the exterior wall.  
DIGITAL THERMOSTAT Single stage, wall-mounted  
digital thermostat for control of Friedrich VERT-I-PAK.  
RT4  
ACCESS PANEL / RETURN AIR GRILLE – Serves as an  
access panel to chassis and interior return air grille. A  
eld-supplied (25" x 20") lter is mounted inside the hinged  
access door.  
VPRG4  
DIMENSIONS: 58" high x 29" wide.  
CUTOUT DIMENSIONS: 55 3/4" high x 27" wide.  
15  
FRIEDRICH AIR CONDITIONING CO. INC.  
Post Office Box 1540 · San Antonio, Texas 78295-1540  
4200 N. Pan Am Expressway · San Antonio, Texas 78218-5212  
(210) 357-4400 · FAX (210) 357-4480  
920-075-08 (10-06)  
Printed in the U.S.A.  

Carrier EEZ 40MVC User Manual
Cornelius Remcor C106 User Manual
Creda NP150 75 772903 User Manual
Epson STYLUS SX400 User Manual
Fisher Price R4743 User Manual
Friedrich Air Conditioner WS15 User Manual
Fujitsu ASYA24LCC User Manual
GE General Electric Air Conditioner AQV06 User Manual
Heat Glo LifeStyle 6000G LP User Manual
Honeywell Air Conditioner MM14CHCS User Manual