Carrier WEATHERMAKER 48AJ User Manual

WEATHERMAKER®  
48AJ,AK,AW,AY020-060  
Single Package Rooftop Units  
Electric Cooling/Gas Heating  
with Scroll Compressor and  
COMFORTLINK™ Controls  
Installation Instructions  
CONTENTS  
Page  
WARNING  
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1  
1. Improper installation, adjustment, alteration, service,  
or maintenance can cause property damage, personal  
injury, or loss of life. Refer to the User’s Information  
Manual provided with this unit for more details.  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-36  
Step 1 — Provide Unit Support. . . . . . . . . . . . . . . . . . . 1  
• ROOF CURB  
• ALTERNATE UNIT SUPPORT  
Step 2 — Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . 2  
• POSITIONING  
• ROOF MOUNT  
2. Do not store or use gasoline or other flammable va-  
pors and liquids in the vicinity of this or any other  
appliance.  
Step 3 — Field Fabricate Ductwork. . . . . . . . . . . . . . . 2  
Step 4 — Make Unit Duct Connections . . . . . . . . . . . 2  
Step 5 — Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . 19  
Step 6 — Trap Condensate Drain. . . . . . . . . . . . . . . . 19  
Step 7 — Install Gas Piping . . . . . . . . . . . . . . . . . . . . . 19  
Step 8 — Make Electrical Connections . . . . . . . . . . 20  
• POWER WIRING  
What to do if you smell gas:  
1. DO NOT try to light any appliance.  
2. DO NOT touch any electrical switch, or use any  
phone in your building.  
3. IMMEDIATELY call your gas supplier from a neigh-  
bor’s phone. Follow the gas supplier’s instructions.  
• FIELD POWER SUPPLY  
4. If you cannot reach your gas supplier, call the fire  
department.  
• FIELD CONTROL WIRING  
Step 9 — Make Outdoor-Air Inlet  
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
• ECONOMIZER AND FIXED OUTDOOR  
AIR DAMPER  
Step 10 — Position Power Exhaust/Barometric  
Relief Damper Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
WARNING  
Disconnect gas piping from unit when pressure testing at  
pressure greater than 0.5 psig. Pressures greater than  
0.5 psig will cause gas valve damage resulting in hazardous  
condition. If gas valve is subjected to pressure greater than  
0.5 psig, it must be replaced before use. When pressure  
testing field-supplied gas piping at pressures of 0.5 psig or  
less, a unit connected to such piping must be isolated by  
closing the manual gas valve(s).  
Step 11 — Route VAV Static Pressure Sensor . . . 34  
Step 12 — Install All Accessories . . . . . . . . . . . . . . . 35  
Step 13 — Field Modifications. . . . . . . . . . . . . . . . . . . 35  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical compo-  
nents. Only trained and qualified service personnel should in-  
stall, repair, or service air-conditioning equipment.  
Untrained personnel can perform the basic maintenance  
functions of cleaning coils and filters and replacing filters. All  
other operations should be performed by trained service per-  
sonnel. When working on air-conditioning equipment, observe  
precautions in the literature, tags and labels attached to the unit,  
and other safety precautions that may apply.  
Follow all safety codes. Wear safety glasses and work  
gloves. Use quenching cloth for unbrazing operations. Have  
fire extinguishers available for all brazing operations.  
INSTALLATION  
Step 1 — Provide Unit Support  
CAUTION  
1. All panels must be in place when rigging or damage  
to unit may occur.  
2. Unit is not designed for handling by fork truck.  
WARNING  
Before performing service or maintenance operations on  
unit, turn off main power switch to unit. Electrical shock  
could cause personal injury.  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53480067-01 Printed in U.S.A. Form 48A-7SI Pg 1 8-09 Replaces: 48A-5SI  
a48-6715  
3
a48-6716  
4
a48-6717  
5
a48-8235  
6
a48-8236  
7
8
A48-8380  
9
a48-8239  
10  
a48-8240  
11  
a50-8102  
12  
Table 1 — Physical Data — 48AJ,AK,AW,AY Units  
UNIT 48AJ,AK,AW,AY  
020  
025  
027  
030  
NOMINAL CAPACITY (tons)  
20  
25  
27  
30  
BASE UNIT  
OPERATING WEIGHT (lb)  
See Operating Weights Table  
COMPRESSOR  
1…SR*812AT, 1…SR*942AT/  
Quantity ... Type (Ckt 1/Ckt 2)  
2…SR*782AT/1…SR*782AE  
2 ... SR*942AT/1…SR*942AE  
2…SR*782AT/2…SR*812AT  
1…SR*942AE  
2
Number of Refrigerant Circuits  
Oil (oz) (Ckt 1, Ckt 2)  
2
2
2
Precharged  
Precharged  
Precharged  
Precharged  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Circuit 1  
R-22  
26-8  
14-0  
33-8  
17-8  
35-8  
20-0  
29-0  
30-8  
Circuit 2  
CONDENSER COIL*  
Quantity  
Rows ... Fins/in.  
Total Face Area (sq ft)  
Internally Enhanced, 3/8Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins  
1
1
1
1
2 ... 15  
33.3  
3 ... 15  
33.3  
3 ... 15  
33.3  
4 ... 15  
33.3  
CONDENSER FAN  
Nominal Cfm  
Quantity... Diameter (in.)  
Motor Hp  
Propeller Type  
17,200  
2 ... 30  
1
15,850  
2 ... 30  
1
15,850  
2 ... 30  
1
14,500  
2 ... 30  
1
EVAPORATOR COIL  
Tube Size (in.)  
Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits  
3
3
3
3
/
/
/
/
Rows ... Fins/in.  
3 ...815  
31.7  
3 ...815  
4 ...815  
31.7  
4 ...815  
31.7  
Total Face Area (sq ft)  
31.7  
EVAPORATOR FAN  
Centrifugal Type  
15  
Quantity ... Size (in.)  
Type Drive  
2 ... 20 X 15  
Belt  
2 ... 20 X 15  
Belt  
2 ... 20 X 15  
Belt  
2 ... 20 X 15  
Belt  
Nominal Cfm  
8,000  
10  
10,000  
10  
11,000  
15  
12,000  
15  
Motor Hp  
5
15  
5
10  
20  
10  
20  
Motor Frame Size  
184T  
215T  
Ball  
254T  
184T  
215T  
Ball  
254T  
215T  
254T  
Ball  
256T  
215T  
254T  
Ball  
256T  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter (in.)  
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
Nominal Fan Shaft Diameter (in.)  
Belt Quantity  
1200  
4.4  
1200  
6.1  
1200  
4.9  
1200  
5.7  
4.8  
11/8  
12.4  
5.7  
15/8  
9.1  
4.8  
11/8  
12.4  
5.5  
15/8  
8.7  
4.4  
13/8  
9.4  
5.9  
15/8  
8.7  
4.4  
13/8  
9.5  
5.9  
15/8  
8.7  
13/8  
13/8  
15/8  
15/8  
8.6  
11.1  
8.1  
9.1  
115  
/
115  
1
/
115  
/
115  
/
16  
1
116  
BX50  
63  
2
5VX530  
53  
1
2
2
216  
5VX530  
50  
2
5VX530  
53  
2
216  
5VX530  
53  
2
5VX530  
53  
Belt Type  
Belt Length (in.)  
Pulley Center Line Distance (in.)  
Factory Speed Setting (rpm)  
BX56  
56  
BX56  
56  
5VX570  
57  
15.6-18.4  
962  
5VX530  
53  
BX50  
50  
BX50  
50  
16.0-18.7 15.6-18.4 15.0-17.9 15.6-18.4  
15.0-17.9  
1106  
15.6-18.4 15.0-17.9 15.0-17.9 15.6-18.4 15.0-17.9 15.0-17.9  
677  
895  
1096  
677  
819  
1096  
1187  
884  
1096  
1187  
FURNACE SECTION  
Supply Line Pressure Range  
Rollout Switch Cutout  
Temp (F)†  
5.0-in. wg min/13.5-in. wg max.  
225  
225  
225  
225  
Burner Orifice Diameter (in. ...drill size)  
Natural Gas  
Std  
Alt  
.111 ... 34  
.089 ... 43  
.111 ... 34  
.089 ... 43  
.111 ... 34  
.089 ... 43  
.111 ... 34  
.089 ... 43  
Liquid Propane  
Thermostat Heat Anticipator Setting  
Stage 1 (amps)  
0.24  
0.13  
0.24  
0.13  
0.24  
0.13  
0.24  
0.13  
Stage 2 (amps)  
Gas Input (Btuh) Stage 1  
262,500/394,000  
262,500/394,000  
262,500/394,000  
262,500/394,000  
(Low Heat/High Heat)  
Stage 2  
350,000/525,000  
350,000/525,000  
350,000/525,000  
350,000/525,000  
(Low Heat/High Heat)  
Efficiency (Steady State) (%)  
82  
82  
82  
82  
Temperature Rise Range  
Manifold Pressure (in. wg)  
Natural Gas  
15-45/35-65  
15-45/35-65  
15-45/35-65  
15-45/35-65  
Std  
Alt  
3.5  
3.5  
2
3.5  
3.5  
2
3.5  
3.5  
2
3.5  
3.5  
2
Liquid Propane  
Gas Valve Quantity  
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
426  
320  
426  
320  
426  
320  
426  
320  
MIXED-AIR FILTERS  
Quantity ... Size (in.) Standard  
Pleated  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
OUTDOOR-AIR FILTERS  
Quantity...Size (in.)  
8...16 x 25 x 2  
4...20 x 25 x 2  
Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan  
POWER EXHAUST  
Housing  
4...1  
Motor, Quantity...Hp  
Fan, Diameter...Width (in.)  
11 x 10  
LEGEND  
*Sizes 020-040: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper  
portion.  
Al  
Cu  
Aluminum  
Copper  
Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have  
intertwined evaporator coils.  
†Rollout switch is manual reset.  
13  
Table 1 — Physical Data — 48AJ,AK,AW,AY Units (cont)  
UNIT 48AJ,AK,AW,AY  
035  
036  
040  
041  
40  
NOMINAL CAPACITY (tons)  
35  
35  
40  
BASE UNIT  
OPERATING WEIGHT (lb)  
See Operating Weights Table  
COMPRESSOR  
1…SR*812AT,  
1…SR*812AT,  
Quantity ... Type (Ckt 1/Ckt 2)  
2…SR*942AT/2…SM125  
2…SR*942AT/2…SM125  
1…SR*942AT/2…SR*942AT  
1…SR*942AT/2…SR*942AT  
Number of Refrigerant Circuits  
Oil (oz) (Ckt 1, Ckt 2)  
2
2
2
2
Precharged  
Precharged  
Precharged  
Precharged  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Circuit 1  
R-22  
33-0  
38-0  
36-0  
58-0  
36-0  
47-0  
47-0  
47-0  
Circuit 2  
CONDENSER COIL*  
Quantity  
Rows ... Fins/in.  
Total Face Area (sq ft)  
Internally Enhanced, 3/8Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins  
1
2
2
2
4 ... 15  
33.3  
2...15/4…15  
66.7  
2 ... 15 / 4 … 15  
66.7  
4...15/4…15  
66.7  
CONDENSER FAN  
Nominal Cfm  
Quantity... Diameter (in.)  
Motor Hp  
Propeller Type  
14,500  
2 ... 30  
1
30,000  
4...30  
1
30,000  
4 ... 30  
1
30,000  
4...30  
1
EVAPORATOR COIL  
Tube Size (in.)  
Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits  
1
1
1
1
/
/
/
/
Rows ... Fins/in.  
6 ...216  
31.3  
4...217  
4 ...216  
31.3  
4...217  
31.3  
Total Face Area (sq ft)  
31.3  
EVAPORATOR FAN  
Centrifugal Type  
Quantity ... Size (in.)  
Type Drive  
2 ... 20 X 15  
Belt  
2...20 X 15  
Belt  
2 ... 20 X 15  
Belt  
2...20 X 15  
Belt  
Nominal Cfm  
14,000  
20  
14,000  
20  
16,000  
20  
16,000  
20  
Motor Hp  
15  
25  
15  
25  
284T  
15  
254T  
25  
15  
25  
Motor Frame Size  
254T  
256T  
Ball  
284T  
254T  
256T  
Ball  
256T  
Ball  
284T  
254T  
256T  
Ball  
284T  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter (in.)  
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
1300  
5.7  
1300  
5.7  
1300  
5.7  
1300  
5.7  
5.1  
15/8  
8.7  
6.2  
17/8  
8.7  
5.3  
15/8  
9.5  
7.5  
17/8  
11.1  
5.3  
15/8  
9.5  
7.5  
17/8  
11.1  
5.3  
15/8  
9.5  
7.5  
17/8  
11.1  
15/8  
15/8  
15/8  
15/8  
8.7  
9.5  
9.5  
9.5  
115  
/
115/  
2
Nominal Fan Shaft Diameter (in.)  
115  
/
115  
/
16  
16  
Belt Quantity  
2
5VX500  
50  
216  
5VX530  
53  
2
5VX550  
55  
2
5VX530  
53  
2
2
5VX590  
59  
2
5VX530  
53  
216  
5VX550  
55  
2
5VX590  
59  
2
5VX530  
53  
2
5VX590  
59  
Belt Type  
5VX550  
55  
5VX550  
55  
Belt Length (in.)  
Pulley Center Line Distance (in.)  
Factory Speed Setting (rpm)  
15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 15.0-17.9 14.6-17.6 15.0-17.9 15.0-17.9 14.6-17.6  
1005  
1147  
1247  
976  
1050  
1182  
976  
1050  
1182  
976  
1050  
1182  
FURNACE SECTION  
Supply Line Pressure Range  
Rollout Switch Cutout  
Temp (F)†  
5.0-in. wg min/13.5-in. wg max.  
225  
225  
225  
225  
Burner Orifice Diameter (in ...drill size)  
Natural Gas  
Std  
Alt  
.111 ... 34  
.089 ... 43  
.120...31  
.096...41  
.120 ... 31  
.096 ... 41  
.120...31  
.096...41  
Liquid Propane  
Thermostat Heat Anticipator Setting  
Stage 1 (amps)  
0.24  
0.13  
0.1  
0.1  
0.24  
0.13  
0.1  
0.1  
Stage 2 (amps)  
Gas Input (Btuh) Stage 1  
(Low Heat/High Heat)  
Stage 2  
262,500/394,000  
300,000/600,000  
300,000/600,000  
300,000/600,000  
350,000/525,000  
400,000/800,000  
400,000/800,000  
400,000/800,000  
(Low Heat/High Heat)  
Efficiency (Steady State) (%)  
Temperature Rise Range  
Manifold Pressure (in. wg)  
82  
82  
82  
82  
15-45/35-65  
10-40/30-60  
10-40/3 -60  
10-40/30-60  
Natural Gas  
Liquid Propane  
Gas Valve Quantity  
Std  
Alt  
3.5  
3.5  
2
3.5  
3.5  
2
3.5  
3.5  
2
3.5  
3.5  
2
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
426  
320  
426  
320  
426  
320  
426  
320  
MIXED-AIR FILTERS  
Quantity ... Size (in.) Standard  
Pleated  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
10...20 x 24 x 2  
5...20 x 20 x 4  
5...20 x 20 x 4  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
10...20 x 24 x 2  
5...20 x 20 x 4  
5...20 x 20 x 4  
OUTDOOR-AIR FILTERS  
Quantity...Size (in.)  
8...16 x 25 x 2  
4...20 x 25 x 2  
POWER EXHAUST  
Motor, Quantity...Hp  
Fan, Diameter...Width (in.)  
Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan Housing  
4...1  
11 x 10  
LEGEND  
*Sizes 020-040: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper  
portion.  
Al  
Cu  
Aluminum  
Copper  
Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have  
intertwined evaporator coils.  
†Rollout switch is manual reset.  
14  
Table 1 — Physical Data — 48AJ,AK,AW,AY Units (cont)  
UNIT 48AJ,AK,AW,AY  
050  
051  
060  
NOMINAL CAPACITY (tons)  
50  
50  
60  
BASE UNIT  
OPERATING WEIGHT (lb)  
See Operating Weights Table  
COMPRESSOR  
2…SM125/1…SM125,  
1..SM160,1..SM175/  
1..SM160,1..SM175  
2
Quantity ... Type (Ckt 1/Ckt 2)  
2…SM125/2…SM125  
1…SM175  
2
Number of Refrigerant Circuits  
Oil (oz) (Ckt 1, Ckt 2)  
2
Precharged  
Precharged  
Precharged  
REFRIGERANT TYPE  
Operating Charge (lb-oz)  
Circuit 1  
R-22  
64-4  
58-8  
98-0  
98-0  
81-0  
81-0  
Circuit 2  
CONDENSER COIL*  
Quantity  
Rows ... Fins/in.  
Total Face Area (sq ft)  
Internally Enhanced, 3/8Copper Tubes, Aluminum Lanced, Aluminum Pre-Coated, or Copper Plate Fins  
2
2
2
4 ... 15  
66.7  
4…15  
100  
4…15  
100  
CONDENSER FAN  
Nominal Cfm  
Quantity... Diameter (in.)  
Motor Hp  
Propeller Type  
25,600  
4 ... 30  
1
38,400  
6...30  
1
38,400  
6 ... 30  
1
EVAPORATOR COIL  
Tube Size (in.)  
Internally Enhanced Copper Tubes, Aluminum Plate Fins with Intertwined Circuits  
1
1
1
/
/
/
Rows ... Fins/in.  
6 ...216  
31.3  
4...217  
48.1  
4 ...217  
48.1  
Total Face Area (sq ft)  
EVAPORATOR FAN  
Quantity ... Size (in.)  
Type Drive  
Centrifugal Type  
3...20 X 15  
Belt  
2 ... 20 X 15  
Belt  
3 ... 20 X 15  
Belt  
Nominal Cfm  
20,000  
20,000  
24,000  
40  
40  
40  
40  
Motor Hp  
20  
25  
30  
20  
25  
30  
25  
30  
(High Eff.) (Prem. Eff.)  
(High Eff.) (Prem. Eff.)  
Motor Frame Size  
Motor Bearing Type  
Maximum Allowable Rpm  
Motor Pulley Pitch Diameter (in.)  
Nominal Motor Shaft Diameter (in.)  
Fan Pulley Pitch Diameter (in.)  
256T  
284T  
Ball  
1300  
6.2  
286T  
256T  
284T  
286T  
Ball  
1200  
5.9  
324T  
324T  
284T  
286T  
324T  
324T  
Ball  
1200  
5.7  
15/8  
9.5  
6.7  
17/8  
9.5  
5.9  
15/8  
11.1  
5.3  
17/8  
9.1  
6.5  
21/8  
9.5  
9.5  
21/8  
13.7  
5.3  
17/8  
9.1  
5.9  
17/8  
9.5  
6.5  
21/8  
9.5  
9.5  
21/8  
13.7  
17/8  
9.5  
17/8  
9.5  
115  
3
/
Nominal Fan Shaft Diameter (in.)  
115  
/
115/  
16  
16  
Belt Quantity  
2
5VX550  
55  
216  
5VX570  
57  
2
5VX570  
57  
2
5VX560  
56  
3
5VX530  
53  
3
5VX570  
57  
2
3
5VX530  
53  
3
5VX550  
55  
3
5VX570  
57  
2
Belt Type  
5VX550  
55  
5VX650  
65  
5VX650  
65  
Belt Length (in.)  
Pulley Center Line Distance (in.)  
Factory Speed Setting (rpm)  
15.0-17.9 14.6-17.6 14.6-17.6 15.0-17.9 15.2-17.5 14.7-17.2 14.2-17.0  
14.2-17.0  
1214  
15.2-17.5 14.7-17.2 14.2-17.0  
1019 1086 1197  
14.2-17.0  
1214  
1061  
1154  
1249  
930  
1019  
1086  
1197  
FURNACE SECTION  
Supply Line Pressure Range  
Rollout Switch Cutout  
Temp (F)†  
5.0-in. wg min/13.5-in. wg max.  
225  
225  
225  
Burner Orifice Diameter (in ...drill size)  
Natural Gas  
Std  
Alt  
.120 ... 31  
.096 ... 41  
.120...31  
.096...41  
.120 ... 31  
.096 ... 41  
Liquid Propane  
Thermostat Heat Anticipator Setting  
Stage 1 (amps)  
0.24  
0.13  
0.1  
0.1  
0.36  
0.13  
Stage 2 (amps)  
Gas Input (Btuh) Stage 1  
(Low Heat/High Heat)  
Stage 2  
300,000/600,000  
582,000/873,000  
582,000/873,000  
400,000/800,000  
776,000/1,164,000  
776,000/1,164,000  
(Low Heat/High Heat)  
Efficiency (Steady State) (%)  
Temperature Rise Range  
Manifold Pressure (in. wg)  
82  
82  
82  
10-40/30-60  
10-40/30-60  
10-40/30-60  
Natural Gas  
Liquid Propane  
Gas Valve Quantity  
Std  
Alt  
3.5  
3.5  
2
3.3  
3.3  
3
3.3  
3.3  
3
HIGH-PRESSURE SWITCH (psig)  
Cutout  
Reset (Auto.)  
426  
320  
426  
320  
426  
320  
MIXED-AIR FILTERS  
Quantity ... Size (in.) Standard  
Pleated  
10 ... 20 x 24 x 2  
5 ... 20 x 20 x 4  
5 ... 20 x 24 x 4  
16...20 x 24 x 2  
8...20 x 20 x 4  
8...20 x 24 x 4  
16 ... 20 x 24 x 2  
8 ... 20 x 20 x 4  
8 ... 20 x 24 x 4  
OUTDOOR-AIR FILTERS  
Quantity...Size (in.)  
8...16 x 25 x 2  
4...20 x 25 x 2  
12...16 x 25 x 2  
6...20 x 25 x 2  
POWER EXHAUST  
Motor, Quantity...Hp  
Fan, Diameter...Width (in.)  
Direct Drive, Single-Phase Motors (Factory-Wired for High Speed Operation), Forward-Curved Fan Wheels with Backdraft Dampers on Each Fan Housing  
4...1  
6...1  
11 x 10  
11 x 10  
LEGEND  
*Sizes 020-040: Circuit 1 uses the lower portion of condenser coil, Circuit 2 uses the upper  
portion.  
Al  
Cu  
Aluminum  
Copper  
Sizes 041-060: Circuit 1 uses the left condenser coil, Circuit 2 the right. All units have  
intertwined evaporator coils.  
†Rollout switch is manual reset.  
15  
a48-8246  
16  
Table 2 — Unit Operating Weights  
BASE UNIT WEIGHTS — lb  
UNIT  
020  
025  
027  
030  
035  
036  
040  
041  
050  
051  
060  
48AJ/AK Low Heat  
48AJ/AK High Heat  
48AW/AY Low Heat  
48AW/AY High Heat  
3842  
3922  
3882  
3962  
3915  
3995  
3955  
4035  
4032  
4112  
4072  
4152  
4182  
4262  
4222  
4302  
4435  
4595  
4475  
4635  
4815  
4975  
4855  
5015  
4975  
5135  
5015  
5175  
5091  
5251  
5131  
5291  
5446  
5606  
5486  
5646  
7224  
7464  
7264  
7514  
7388  
7628  
7428  
7678  
Table 3 — Option and Accessory Weights  
OPTION/ACCESSORY WEIGHTS — lb  
OPTION/  
ACCESSORY  
020  
300  
450  
500  
220  
45  
025  
300  
450  
500  
220  
45  
027  
300  
450  
500  
220  
45  
030  
300  
450  
500  
220  
45  
035  
300  
450  
500  
285  
45  
036  
300  
450  
500  
380  
45  
040  
300  
450  
500  
285  
45  
041  
300  
450  
500  
380  
45  
050  
051  
450  
675  
725  
651  
45  
060  
Barometric Relief  
Power Exhaust  
Mod. Power Exhaust  
300  
450  
500  
380  
45  
450  
675  
725  
651  
45  
Cu Tubing/Cu Fin Condenser Coil  
Outdoor Air Hood Crate and Packaging  
(Less Hoods' Weight)  
(Packaging Only)  
(Packaging Only)  
Outdoor Air Hoods/Filters  
Hail Guard  
Roof Curb (14-in.)  
170  
73  
365  
170  
73  
365  
170  
73  
365  
170  
73  
365  
170  
73  
410  
170  
146  
410  
170  
146  
410  
170  
146  
410  
170  
146  
410  
255  
219  
540  
255  
219  
585  
Table 4 — Constant Volume Fan Motor Weights  
Table 5 — Variable Volume Fan Motor Weights  
CV MOTOR WEIGHTS — lb  
VAV MOTOR WEIGHTS — lb  
HIGH  
EFFICIENCY  
IFM  
PREMIUM  
EFFICIENCY  
IFM  
HIGH  
EFFICIENCY  
IFM  
PREMIUM  
EFFICIENCY  
IFM  
MOTOR  
HP  
UNIT  
VOLTAGE  
MOTOR  
HP  
UNIT  
VOLTAGE  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
78  
78  
94  
92  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
230/460  
575  
125  
163  
204  
204  
238  
240  
348  
304  
377  
375  
480  
418  
637  
587  
141  
177  
250  
242  
305  
310  
386  
350  
446  
454  
552  
494  
680  
625  
5
5
118  
118  
150  
150  
212  
212  
240  
240  
283  
283  
372  
372  
164  
156  
217  
220  
250  
258  
309  
319  
355  
359  
415  
410  
10  
15  
20  
25  
30  
40  
10  
15  
20  
25  
30  
40  
LEGEND AND NOTES FOR TABLES 2-5  
LEGEND  
Copper  
NOTES:  
1. Base unit weight includes outdoor-air hoods. Base unit weight  
does NOT include indoor-fan motor. ADD indoor-fan motor,  
FIOPs, and accessories for TOTAL operating weight.  
2. The VAV motor weights include indoor fan motor and the VFD  
(variable frequency drive), VFD transducers, and associated  
wiring.  
Cu  
CV  
Constant Volume  
FIOP  
HP  
IFM  
VAV  
VFD  
Factory-Installed Option  
Horsepower  
Indoor Fan Motor  
Variable Air Volume  
Variable Frequency Drive  
17  
Table 6 — Evaporator Fan Motor Data  
MOTOR  
SHEAVE  
PITCH  
DIAMETER  
(in.)  
FAN  
UNIT  
SIZE  
48AJ,AK,  
AW,AY  
FAN  
MOTOR  
SHAFT DIA.  
(in.)  
MOTOR  
SHEAVE  
(P/N)  
BUSHING  
DIAMETER  
(in.)  
FAN  
SHEAVE  
(P/N)  
SHEAVE  
PITCH  
BUSHING  
BELT  
BELT  
TENSION  
(lb at .25 in.)  
MOTOR  
HP  
SHAFT  
SPEED  
(rpm)  
DIAMETER (Quantity)  
DIAMETER  
(in.)  
(in.)  
(P/N)  
5
10  
15  
1.125  
1.375  
1.625  
677  
895  
BK55  
2BK50  
2B5V56  
4.8  
4.4  
5.7  
NONE - 1.125 1B5V124  
12.4  
8.6  
B - 1.9375  
B - 1.9375  
B - 1.9375  
BX56  
BX50  
8
8
9
020  
025  
027  
030  
035  
036  
040  
041  
050  
NONE - 1.375  
B - 1.625  
2B5V86  
2B5V90  
1096  
9.1  
(2) 5VX530  
5
10  
15  
1.125  
1.375  
1.625  
677  
962  
1106  
BK55  
1B5V60  
2B5V54  
4.8  
6.1  
5.5  
NONE - 1.125 1B5V124  
12.4  
11.1  
8.7  
B - 1.9375  
B - 1.9375  
B - 1.9375  
BX56  
5VX570  
(2) 5VX530  
8
11  
9
H - 1.375  
B - 1.625  
1B5V110  
2B5V86  
10  
15  
20  
1.375  
1.625  
1.625  
819  
1096  
1187  
2BK50  
2B5V56  
2B5V58  
4.4  
5.7  
5.9  
NONE - 1.375  
B - 1.625  
B - 1.625  
2B5V94  
2B5V90  
2B5V86  
9.4  
9.1  
8.7  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) BX50  
(2) 5VX530  
(2) 5VX530  
8
10  
11  
10  
15  
20  
1.375  
1.625  
1.625  
884  
1096  
1187  
2BK50  
2B5V56  
2B5V58  
4.4  
5.7  
5.9  
H - 1.375  
B - 1.625  
B - 1.625  
2B5V94  
2B5V90  
2B5V86  
9.5  
9.1  
8.7  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) BX50  
(2) 5VX530  
(2) 5VX530  
8
9
11  
15  
20  
25  
1.625  
1.625  
1.875  
1005  
1147  
1247  
2B5V50  
2B5V56  
2B5V62  
5.1  
5.7  
6.2  
B - 1.625  
B - 1.625  
B - 1.875  
2B5V86  
2B5V86  
2B5V86  
8.7  
8.7  
8.7  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) 5VX500  
(2) 5VX530  
(2) 5VX530  
9
10  
11  
15  
20  
25  
1.625  
1.625  
1.875  
976  
1050  
1182  
2B5V52  
2B5V56  
2B5V74  
5.3  
5.7  
7.5  
B - 1.625  
B - 1.625  
B - 1.875  
2B5V94  
2B5V94  
2B5V110  
9.5  
9.5  
11.1  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) 5VX530  
(2) 5VX550  
(2) 5VX590  
10  
11  
11  
15  
20  
25  
1.625  
1.625  
1.875  
976  
1050  
1182  
2B5V52  
2B5V56  
2B5V74  
5.3  
5.7  
7.5  
B - 1.625  
B - 1.625  
B - 1.875  
2B5V94  
2B5V94  
2B5V110  
9.5  
9.5  
11.1  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) 5VX530  
(2) 5VX550  
(2) 5VX590  
10  
11  
11  
15  
20  
25  
1.625  
1.625  
1.875  
976  
1050  
1182  
2B5V52  
2B5V56  
2B5V74  
5.3  
5.7  
7.5  
B - 1.625  
B - 1.625  
B - 1.875  
2B5V94  
2B5V94  
2B5V110  
9.5  
9.5  
11.1  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) 5VX530  
(2) 5VX550  
(2) 5VX590  
10  
11  
11  
20  
25  
30  
1.625  
1.875  
1.875  
1061  
1154  
1247  
2B5V56  
2B5V62  
2B5V66  
5.7  
6.2  
6.7  
B - 1.625  
B - 1.875  
B - 1.875  
2B5V94  
2B5V94  
2B5V94  
9.5  
9.5  
9.5  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) 5VX550  
(2) 5VX570  
(2) 5VX570  
10  
11  
13  
20  
25  
1.625  
1.875  
1.875  
2.125  
2.125  
930  
1019  
1086  
1197  
1214  
2B5V58  
3B5V52  
3B5V58  
3B5V64  
2B5V94  
5.9  
5.3  
5.9  
6.5  
9.5  
B - 1.625  
B - 1.875  
B - 1.875  
B - 2.125  
B - 2.125  
2B5V110  
3B5V90  
3B5V94  
3B5V94  
2B5V136  
11.1  
9.1  
B - 1.9375  
B - 1.9375  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(2) 5VX560  
(3) 5VX530  
(3) 5VX550  
(3) 5VX570  
(2) 5VX650  
11  
12  
12  
14  
15  
051  
30  
9.5  
40 High  
40 Prem.  
9.5  
13.7  
25  
30  
40 High  
40 Prem.  
1.875  
1.875  
2.125  
2.125  
1019  
1086  
1197  
1214  
3B5V52  
3B5V58  
3B5V64  
2B5V94  
5.3  
5.9  
6.5  
9.5  
B - 1.875  
B - 1.875  
B - 2.125  
B - 2.125  
3B5V90  
3B5V94  
3B5V94  
2B5V136  
9.1  
9.5  
B - 1.9375  
B - 1.9375  
B - 1.9375  
B - 1.9375  
(3) 5VX530  
(3) 5VX550  
(3) 5VX570  
(2) 5VX650  
12  
12  
14  
15  
060  
9.5  
13.7  
NOTES:  
1. Motor shaft speed is 1750 rpm. The fan shaft diameter is 115  
/16 inches.  
2. All indoor fan motors meet the minimum efficiency requirements  
as established by the Energy Policy Act of 1992 (EPACT), effective  
October 24, 1997.  
a48-8241  
a48-8242  
Fig. 12 — Air Distribution — Thru-the-Bottom  
Fig. 13 — Air Distribution — Thru-the-Side  
18  
Step 5 — Install Flue Hood  
48AJ,AK,AW,AY020-050 UNITS — Flue hood is shipped  
inside gas section of unit. To install, secure flue hood to access  
panel. See Fig. 14.  
48AJ,AK,AW,AY051 AND 060 UNITS — Flue hood and  
wind baffle are shipped inside gas section of unit. To install, se-  
cure flue hood to access panel. Install the two pieces of the  
wind baffle over the flue hood. See Fig. 15.  
NOTE: When properly installed, flue hood will line up with  
combustion fan housing. See Fig. 16.  
a48-3823  
Fig. 16 — Combustion Fan Housing Location  
(48AJ,AK,AW,AY020-050 Shown)  
Step 6 — Trap Condensate Drain — See Fig. 4-9  
for drain location. Condensate drain is open to atmosphere and  
must be trapped. Install a trapped drain at the drain location.  
One 1-in. FPT coupling is provided inside the unit evaporator  
section for condensate drain connection. A trap at least 4-in.  
deep must be used. See Fig. 17. Trap must be installed to pre-  
vent freeze-up.  
Condensate pans are sloped so that water will completely  
drain from the condensate pan to comply with indoor air quali-  
ty guidelines. The condensate drain pans are not insulated.  
a48-3712  
Fig. 14 — Flue Hood Location  
(48AJ,AK,AW,AY020-050 Units)  
a48-3714  
GAS SECTION  
ACCESS PANEL  
Fig. 17 — Condensate Drain Trap Piping Details  
(Typical Roof Curb or Slab Mount Shown)  
FLUE HOOD  
Step 7 — Install Gas Piping — Unit is equipped for  
use with natural gas. Installation must conform with local  
building codes or, in the absence of local codes, with the Na-  
tional Fuel Gas Code, ANSI Z223.1.  
WIND  
BAFFLE  
Install manual gas shutoff valve with a 1/8-in. NPT pressure  
tap for test gage connection at unit. Field gas piping must in-  
clude sediment trap and union. See Fig. 18. An 1/8-in. NPT is  
also located on the gas manifold adjacent to the gas valve.  
a48-4076  
TOP VIEW  
SIDE VIEW  
WARNING  
Fig. 15 — Flue Hood Location  
(48AJ,AK,AW,AY051 and 060 Units)  
Do not pressure test gas supply while connected to unit.  
Always disconnect union before servicing. Serious injury  
could result.  
19  
local codes) in branch circuit wiring remote from unit. Observe  
requirements of NEC Article 440. Install service switch  
upstream of remote fuses if required.  
The main power terminal block is suitable for use with  
aluminum or copper wire. See Fig. 19. Units have circuit  
breakers for compressors, fan motors, and control circuit. The  
unit must be electrically grounded in accordance with local  
codes, or in absence of local codes, with NEC, ANSI C1-latest  
year.  
FIELD POWER SUPPLY — Unit is factory wired for volt-  
age shown on unit nameplate. See Tables 8A and 8B for elec-  
trical data.  
Field wiring can be brought into the unit from bottom  
(through basepan and roof curb) or through side of unit (corner  
post next to control box).  
a48-2524  
A 31/2-in. NPT coupling for field power wiring and a 3/4-in.  
NPT coupling for 24-v control wiring are provided in basepan.  
In the side post, there are two 21/2-in. (48A020-035) or 3-in.  
(48A036-060) knockouts for the field power wiring. See  
Fig. 4-9. If control wiring is to be brought in through the side of  
Fig. 18 — Field Gas Piping  
IMPORTANT: Natural gas pressure at unit gas connection  
must not be less than 5 in. wg or greater than 13.5 in. wg.  
7
unit, a /8-in. diameter hole is provided in the condenser side  
post next to the control box.  
Do not route control wiring in the same conduit as power  
wiring.  
If disconnect box is mounted to corner post, be careful not  
to drill or screw into the condenser coil.  
Size gas-supply piping for 0.5-in. wg maximum pressure  
drop. Do not use supply pipe smaller than unit gas connection.  
OPTIONAL STAGED GAS UNITS — See Table 7 for staged  
gas information. Staging pattern is selected during controls  
start-up.  
For complete information and service instructions for  
Staged Gas Control Units, see Control Operation and Trouble-  
shooting literature.  
TB1  
FIELD  
11  
12  
13  
21  
22  
POWER  
SUPPLY  
Table 7 — 48A Series Staged Gas Control  
MODEL NUMBER POSITION  
NUMBER OF  
23  
HEAT SIZE  
STAGES  
5
6,7,8  
020  
025  
027  
030  
035  
036  
040  
041  
050  
035  
036  
040  
041  
050  
020  
025  
027  
030  
051,060  
051,060  
S
Low  
EQUIP GND  
OPTIONAL  
5 stages  
FIELD-INSTALLED DISCONNECT  
FACTORY-INSTALLED  
DISCONNECT  
T
T
High  
High  
11  
12  
13  
21  
22  
7 stages  
23  
T
S
9 stages  
11 stages  
High  
Low  
Step 8 — Make Electrical Connections  
POWER WIRING — Units are factory wired for the voltage  
shown on the unit nameplate.  
GND  
a48-6977  
FACTORY-INSTALLED DISCONNECT  
Provide a unit safety disconnect switch in the main power  
supply to each unit (see Fig. 19). Select switch size and mount-  
ing location in accordance with applicable local codes or  
National Electrical Code (NEC). If combining the functions of  
safety disconnect with maximum overcurrent protection  
(MOCP) fuses (“fused disconnect”), coordinate safety switch  
size with MOCP size data as marked on unit informative plate.  
LEGEND  
GND — Ground  
NEC — National Electrical Code  
TB — Terminal Block  
Fig. 19 — Field Power Wiring Connections  
Unit may be equipped with optional factory-installed non-  
fused disconnect switch (see Fig. 19). Provide maximum  
overcurrent protection devices (fuses or HACR breakers, per  
20  
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER  
FAN MOTOR FAN MOTOR EXHAUST  
UNIT  
SIZE  
48A  
POWER SUPPLY  
VOLTAGE  
3 PH, 60 Hz  
FLA  
Hp  
FLA  
FLA (total) MCA  
MOCP*  
23.6  
104.5  
128.1  
125  
150  
5
16.7  
6.5  
120.5  
144.1  
139.8  
163.4  
103.2  
126.8  
117.2  
140.8  
134.7  
158.3  
47.4  
60.0  
54.7  
67.3  
63.5  
76.1  
40.6  
50.2  
46.0  
55.6  
53.5  
63.1  
109.1  
132.7  
124.5  
148.1  
143.8  
167.4  
107.8  
131.4  
121.2  
144.8  
138.7  
162.3  
55.6  
68.2  
62.1  
74.7  
70.9  
83.5  
43.3  
52.9  
48.4  
58.0  
55.9  
65.5  
128.3  
151.9  
147.6  
171.2  
164.1  
187.7  
125.0  
148.6  
142.5  
166.1  
157.5  
181.1  
64.6  
77.2  
73.4  
86.0  
80.9  
93.5  
150  
150  
175  
200  
125  
150  
125  
150  
175  
200  
50  
70  
60  
80  
80  
90  
50  
60  
50  
60  
70  
80  
125  
150  
150  
175  
175  
200  
125  
150  
125  
150  
175  
200  
60  
80  
70  
80  
90  
100  
50  
60  
50  
60  
70  
80  
150  
175  
175  
200  
200  
225  
150  
175  
175  
200  
200  
225  
70  
90  
208  
230  
460  
575  
208  
230  
460  
575  
208  
230  
460  
575  
187 229  
207 253  
23  
23  
184  
184  
23  
23  
184  
184  
23  
23  
184  
184  
90  
2
2
2
2
2
2
2
2
2
2
2
2
10  
15  
5
30.8  
46.2  
15.2  
28.0  
42.0  
7.6  
(ea)  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
9.6  
9.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
9.6  
9.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
12.6  
6.6  
(ea)  
10  
15  
5
020  
025  
027  
3.3  
(ea)  
414 508 10.2  
90 10.2  
90 10.2  
10  
15  
5
14.0  
21.0  
6.1  
2.6  
(ea)  
518 632  
9
73  
9
73  
9
73  
10  
15  
5
11.0  
17.0  
16.7  
30.8  
46.2  
15.2  
28.0  
42.0  
7.6  
6.5  
(ea)  
187 229 21.8 184 25.6 190 25.6 190  
10  
15  
5
6.6  
(ea)  
207 253 21.8 184 25.6 190 25.6 190  
10  
15  
5
3.3  
(ea)  
414 508  
518 632  
11  
9
90 13.5  
73 10.2  
95 13.5  
75 10.2  
95  
75  
10  
15  
5
14.0  
21.0  
6.1  
2.6  
(ea)  
10  
15  
10  
15  
20  
10  
15  
20  
10  
15  
20  
10  
15  
20  
11.0  
17.0  
30.8  
46.2  
59.4  
28.0  
42.0  
54.0  
14.0  
21.0  
27.0  
11.0  
17.0  
22.0  
6.5  
(ea)  
187 229 25.6 190 25.6 190 25.6 190  
6.6  
(ea)  
207 253 25.6 190 25.6 190 25.6 190  
3.3  
(ea)  
90  
100  
100  
110  
60  
70  
70  
80  
80  
90  
414 508 13.5  
518 632 10.2  
95 13.5  
75 10.2  
95 13.5  
75 10.2  
95  
75  
49.6  
62.6  
57.1  
69.7  
63.3  
75.9  
2.6  
(ea)  
12.6  
12.6  
See Legend and Notes on page 24.  
21  
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER  
FAN MOTOR FAN MOTOR EXHAUST  
UNIT  
SIZE  
48A  
POWER SUPPLY  
VOLTAGE  
3 PH, 60 Hz  
FLA  
Hp  
FLA  
FLA (total) MCA  
MOCP*  
23.6  
141.1  
164.7  
150  
175  
10  
30.8  
6.5  
160.4  
184.0  
176.9  
200.5  
137.8  
161.4  
155.3  
178.9  
170.5  
193.9  
66.5  
79.1  
75.3  
87.9  
82.8  
95.4  
55.0  
68.0  
62.5  
75.1  
68.7  
81.3  
169.4  
193.6  
185.9  
209.5  
205.1  
228.7  
164.3  
187.9  
179.3  
202.9  
196.8  
220.4  
84.4  
97.0  
91.9  
104.5  
100.6  
113.2  
66.1  
78.7  
72.3  
84.9  
78.6  
91.2  
182.4  
206.0  
198.9  
222.5  
218.1  
241.7  
177.5  
201.1  
192.5  
216.1  
210.0  
233.6  
91.0  
103.6  
200  
225  
225  
250  
150  
175  
175  
200  
200  
225  
80  
90  
90  
100  
100  
110  
60  
80  
70  
90  
90  
100  
200  
225  
225  
250  
250  
300  
200  
225  
225  
250  
250  
250  
100  
110  
110  
125  
125  
125  
80  
90  
90  
100  
100  
110  
225  
250  
250  
250  
250  
300  
200  
225  
225  
250  
208  
230  
460  
575  
208  
230  
460  
575  
208  
230  
460  
575  
187 229  
207 253  
23  
23  
184  
184  
23  
23  
184 21.8 184 21.8 184  
2
2
2
2
2
2
2
2
4
4
4
4
15  
20  
10  
15  
20  
10  
15  
20  
10  
15  
20  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
46.2  
59.4  
28.0  
42.0  
54.0  
14.0  
21.0  
27.0  
11.0  
17.0  
22.0  
46.2  
59.4  
74.8  
42.0  
54.0  
68.0  
21.0  
27.0  
34.0  
17.0  
22.0  
27.0  
46.2  
59.4  
74.8  
42.0  
54.0  
68.0  
21.0  
27.0  
34.0  
17.0  
22.0  
27.0  
(ea)  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
12.6  
12.6  
12.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
12.6  
12.6  
12.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
6.6  
(ea)  
184 21.8 184 21.8 184  
030  
3.3  
(ea)  
414 508 10.2  
90 10.2  
90  
73  
11  
9
90  
73  
11  
9
90  
73  
2.6  
(ea)  
518 632  
9
73  
9
6.5  
(ea)  
187 229 21.8 184 25.6 190 25.6 190 25.6 190  
6.6  
(ea)  
207 253 21.8 184 25.6 190 25.6 190 25.6 190  
035  
3.3  
(ea)  
414 508  
518 632  
11  
9
90 13.5  
73 10.2  
95 13.5  
75 10.2  
95 13.5  
75 10.2  
95  
75  
2.6  
(ea)  
6.5  
(ea)  
187 229 21.8 184 25.6 190 25.6 190 25.6 190  
6.6  
(ea)  
207 253 21.8 184 25.6 190 25.6 190 25.6 190  
250  
300  
110  
110  
125  
125  
125  
150  
80  
90  
90  
100  
036  
3.3  
(ea)  
98.5  
111.1  
107.2  
119.8  
71.3  
80.9  
77.5  
87.1  
83.8  
93.4  
414 508  
518 632  
11  
9
90 13.5  
73 10.2  
95 13.5  
75 10.2  
95 13.5  
75 10.2  
95  
75  
2.6  
(ea)  
9.6  
9.6  
110  
110  
See Legend and Notes on page 24.  
22  
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER  
FAN MOTOR FAN MOTOR EXHAUST  
UNIT  
SIZE  
48A  
POWER SUPPLY  
VOLTAGE  
3 PH, 60 Hz  
FLA  
Hp  
FLA  
FLA (total) MCA  
MOCP*  
23.6  
203.6  
227.2  
225  
250  
15  
46.2  
6.5  
220.1  
243.7  
239.3  
262.4  
198.7  
222.3  
213.7  
237.3  
231.2  
254.8  
98.5  
111.1  
106.0  
118.6  
114.7  
127.3  
77.9  
90.5  
84.1  
96.7  
90.4  
103.0  
203.6  
227.2  
220.1  
243.7  
239.3  
262.9  
198.7  
222.3  
213.7  
237.3  
231.2  
254.8  
98.5  
111.1  
106.0  
118.6  
114.7  
127.3  
77.9  
87.5  
84.1  
93.7  
90.4  
100.0  
250.2  
273.8  
269.4  
293.0  
285.9  
309.5  
243.8  
267.4  
250  
300  
300  
300  
225  
250  
250  
250  
250  
300  
110  
125  
125  
125  
125  
150  
90  
100  
100  
110  
110  
125  
225  
250  
250  
300  
300  
300  
225  
250  
250  
250  
250  
300  
110  
125  
125  
125  
125  
150  
90  
100  
100  
110  
110  
125  
300  
300  
300  
350  
350  
350  
250  
300  
300  
300  
350  
350  
208  
230  
460  
575  
187 229 25.6 190 25.6 190 34.3 265 34.3 265  
4
4
4
4
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
20  
25  
30  
20  
25  
30  
20  
25  
30  
20  
25  
30  
59.4  
74.8  
42.0  
54.0  
68.0  
21.0  
27.0  
34.0  
17.0  
22.0  
27.0  
46.2  
59.4  
74.8  
42.0  
54.0  
68.0  
21.0  
27.0  
34.0  
17.0  
22.0  
27.0  
59.4  
74.8  
88.0  
54.0  
68.0  
80.0  
27.0  
34.0  
40.0  
22.0  
27.0  
32.0  
(ea)  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
12.6  
12.6  
12.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
9.6  
9.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
12.6  
6.6  
(ea)  
207 253 25.6 190 25.6 190 34.3 265 34.3 265  
040  
041  
050  
3.3  
(ea)  
414 508 13.5  
518 632 10.2  
95 13.5  
75 10.2  
95  
16  
120  
16  
120  
80  
2.6  
(ea)  
75 12.9  
80 12.9  
6.5  
(ea)  
208  
230  
460  
575  
208  
187 229 25.6 190 25.6 190 34.3 265 34.3 265  
4
4
4
4
4
6.6  
(ea)  
207 253 25.6 190 25.6 190 34.3 265 34.3 265  
3.3  
(ea)  
414 508 13.5  
518 632 10.2  
95 13.5  
75 10.2  
95  
16  
120  
16  
120  
80  
2.6  
(ea)  
75 12.9  
80 12.9  
6.5  
(ea)  
187 229 34.3 265 34.3 265 34.3 265  
47  
47  
380  
6.6  
(ea)  
261.3  
284.9  
276.3  
299.9  
117.4  
130.0  
126.1  
138.7  
133.6  
146.2  
95.2  
107.8  
230  
460  
575  
207 253 34.3 265 34.3 265 34.3 265  
380  
4
4
4
125  
150  
150  
150  
150  
175  
110  
125  
125  
125  
125  
150  
3.3  
(ea)  
414 508  
16  
120  
16  
120  
16  
120 22.4 175  
2.6  
(ea)  
12.6  
12.6  
101.5  
114.1  
107.7  
120.3  
518 632 12.9  
80 12.9  
80 12.9  
80 18.6 140  
See Legend and Notes on page 24.  
23  
Table 8A — Electrical Data — 48AJ,AK,AW,AY Units without Convenience Outlet (cont)  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER  
FAN MOTOR FAN MOTOR EXHAUST  
UNIT  
SIZE  
48A  
POWER SUPPLY  
VOLTAGE  
3 PH, 60 Hz  
FLA  
Hp  
FLA  
FLA (total) MCA  
MOCP*  
35.4  
250.5  
285.9  
300  
300  
20  
59.4  
269.7  
305.1  
286.2  
321.6  
318.7  
354.1  
244.3  
279.7  
261.8  
297.2  
276.8  
312.2  
306.8  
342.2  
117.6  
136.5  
126.3  
145.2  
133.8  
152.7  
148.8  
167.7  
94.7  
109.1  
101.0  
115.4  
107.2  
121.6  
118.5  
132.9  
308.1  
343.5  
324.6  
360.0  
357.1  
392.5  
300.2  
335.6  
315.2  
350.6  
345.2  
380.6  
147.5  
166.4  
155.0  
173.9  
170.0  
188.9  
119.8  
138.7  
126.0  
144.9  
300  
350  
350  
400  
400  
450  
250  
300  
300  
350  
350  
350  
400  
400  
125  
150  
150  
175  
150  
175  
200  
200  
110  
125  
125  
125  
125  
150  
150  
150  
350  
400  
400  
400  
450  
450  
350  
350  
350  
400  
400  
450  
175  
175  
175  
200  
200  
225  
25  
30  
40  
20  
25  
30  
40  
20  
25  
30  
40  
20  
25  
30  
40  
25  
30  
40  
25  
30  
40  
25  
30  
40  
25  
30  
40  
74.8  
88  
35.4  
6.5  
208  
230  
460  
575  
187 229 34.3 265 34.3 265 34.3 265 34.3 265  
6
6
6
6
(ea)  
35.4  
35.4  
35.4  
35.4  
35.4  
35.4  
18.9  
18.9  
18.9  
18.9  
14.4  
14.4  
14.4  
14.4  
35.4  
35.4  
35.4  
35.4  
35.4  
35.4  
18.9  
18.9  
18.9  
18.9  
114  
54  
68  
6.6  
(ea)  
207 253 34.3 265 34.3 265 34.3 265 34.3 265  
80  
104  
27  
051  
34  
3.3  
(ea)  
414 508  
16  
120  
16  
120  
16  
120  
16  
120  
40  
52  
22  
27  
2.6  
(ea)  
518 632 12.9  
80 12.9  
80 12.9  
80 12.9  
80  
32  
41  
75.0  
88.0  
114.0  
68.0  
80.0  
104.0  
34.0  
40.0  
52.0  
27.0  
32.0  
41.0  
6.5  
208  
230  
460  
575  
187 229 40.8 265  
47 380 40.8 265  
47 380  
6
6
6
6
(ea)  
6.6  
(ea)  
207 253 40.8 265  
47 380 40.8 265  
47 380  
060  
3.3  
(ea)  
414 508 20.2 135 22.4 175 20.2 135 22.4 175  
125  
150  
150  
175  
175  
175  
2.6  
(ea)  
18.9  
18.9  
518 632 16.6 120 18.6 140 16.6 120 18.6 140  
137.3  
156.2  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
FLA  
BC = 464 v  
HACR — Heating, Air Conditioning and Refrigeration  
LRA — Locked Rotor Amps  
AC = 455 v  
452 + 464 + 455  
MCA — Minimum Circuit Amps  
Average Voltage =  
MOCP — Maximum Overcurrent Protection  
NEC — National Electrical Code  
RLA — Rated Load Amps  
3
1371  
=
3
= 457  
*Fuse or HACR circuit breaker per NEC.  
NOTES:  
Determine maximum deviation from average voltage.  
(AB) 457 – 452 = 5 v  
1. In compliance with NEC requirements for multimotor and combination  
load equipment (refer to NEC Articles 430 and 440), the overcurrent  
protective device for the unit shall be fuse or HACR breaker. The  
Canadian units may be fuse or circuit breaker.  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
2. Unbalanced 3-Phase Supply Voltage  
Never operate a motor where a phase imbalance in supply voltage is  
greater than 2%. Use the following formula to determine the percent  
of voltage imbalance.  
% Voltage Imbalance = 100 x  
457  
= 1.53%  
This amount of phase imbalance is satisfactory as it is below the max-  
imum allowable 2%.  
% Voltage imbalance  
max voltage deviation from average voltage  
= 100 x  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
average voltage  
24  
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER CONVENIENCE  
POWER SUPPLY  
UNIT  
SIZE  
48A  
FAN MOTOR FAN MOTOR EXHAUST  
OUTLET  
VOLTAGE  
3 PH, 60 Hz  
Fuse or  
MCA  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
FLA  
Hp  
5
FLA FLA (total)  
FLA  
HACR Brkr*  
16.7  
7.0  
7.0  
111.5  
135.2  
125  
150  
23.6  
6.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
127.5  
151.1  
146.8  
170.4  
110.2  
133.9  
124.2  
147.8  
141.7  
165.3  
50.9  
64.1  
58.2  
70.8  
67.0  
79.6  
43.1  
52.8  
48.5  
58.1  
56.0  
65.6  
116.1  
139.7  
131.5  
155.1  
150.8  
174.4  
114.8  
138.4  
128.2  
151.8  
145.7  
169.3  
59.1  
71.7  
65.6  
78.2  
74.4  
87.0  
46.6  
52.7  
50.9  
57.0  
58.4  
64.5  
135.3  
158.9  
154.6  
178.2  
171.1  
194.7  
132.0  
155.6  
149.5  
173.1  
164.5  
188.1  
68.1  
80.7  
76.9  
89.5  
84.4  
97.0  
150  
175  
175  
200  
125  
150  
150  
175  
175  
200  
60  
70  
70  
80  
80  
100  
50  
60  
50  
60  
70  
80  
125  
150  
150  
175  
175  
200  
125  
150  
150  
175  
175  
200  
70  
80  
70  
90  
90  
100  
50  
60  
60  
60  
70  
80  
150  
175  
200  
200  
225  
250  
150  
175  
175  
200  
208  
230  
460  
575  
208  
230  
460  
575  
208  
230  
460  
575  
187 229 23  
207 253 23  
414 508 10.2  
184  
184  
23  
23  
184  
184  
23  
23  
184  
184  
90  
2
2
2
2
2
2
2
2
2
2
2
2
10  
15  
5
30.8  
(ea)  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
46.2  
15.2  
6.6  
(ea)  
10  
15  
5
28.0  
42.0  
020  
025  
027  
7.6  
3.3  
(ea)  
90 10.2  
90 10.2  
10  
15  
5
14.0  
21.0  
6.1  
2.6  
(ea)  
9.6  
9.6  
518 632  
9
73  
9
73  
9
73  
10  
15  
5
11.0  
17.0  
16.7  
23.6  
6.5  
(ea)  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
187 229 21.8 184 25.6 190 25.6 190  
10  
15  
5
30.8  
46.2  
15.2  
6.6  
(ea)  
207 253 21.8 184 25.6 190 25.6 190  
10  
15  
5
28.0  
42.0  
7.6  
3.3  
(ea)  
414 508 11  
90 13.5  
73 10.2  
95 13.5  
75 10.2  
95  
75  
10  
15  
5
14.0  
21.0  
6.9  
6.1  
2.6  
(ea)  
518 632  
9
10  
15  
10  
15  
20  
10  
15  
20  
10  
15  
20  
10  
15  
20  
11.0  
6.1  
17.0  
6.1  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
30.8  
6.5  
(ea)  
187 229 25.6 190 25.6 190 25.6 190  
46.2  
59.4  
28.0  
6.6  
(ea)  
207 253 25.6 190 25.6 190 25.6 190  
42.0  
200  
225  
80  
90  
90  
110  
110  
110  
60  
70  
70  
80  
80  
90  
54.0  
14.0  
3.3  
(ea)  
414 508 13.5  
518 632 10.2  
95 13.5  
75 10.2  
95 13.5  
75 10.2  
95  
75  
21.0  
12.6  
9.6  
9.6  
27.0  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
52.1  
61.7  
59.6  
69.2  
65.8  
75.4  
11.0  
2.6  
(ea)  
17.0  
22.0  
9.6  
See Legend and Notes on page 28.  
25  
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet (cont)  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER CONVENIENCE  
POWER SUPPLY  
UNIT  
SIZE  
48A  
FAN MOTOR FAN MOTOR EXHAUST  
OUTLET  
VOLTAGE  
3 PH, 60 Hz  
Fuse or  
MCA  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
FLA  
Hp  
10  
15  
20  
10  
15  
20  
10  
15  
20  
10  
15  
20  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
FLA FLA (total)  
FLA  
HACR Brkr*  
30.8  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
148.1  
171.7  
167.4  
191.0  
183.9  
207.5  
144.8  
168.4  
162.3  
185.9  
177.3  
200.9  
70.0  
82.6  
78.8  
91.4  
86.3  
98.9  
57.5  
67.1  
65.0  
74.6  
71.2  
80.8  
176.4  
200.0  
192.9  
216.5  
212.1  
235.7  
171.3  
194.9  
186.3  
209.9  
203.8  
227.4  
87.9  
100.5  
95.4  
108.0  
104.1  
116.7  
68.6  
78.2  
74.8  
84.4  
81.1  
90.7  
189.4  
213.0  
205.9  
229.5  
225.1  
248.7  
184.5  
208.1  
199.5  
223.1  
217.0  
240.6  
175  
200  
200  
225  
225  
250  
150  
175  
200  
225  
225  
250  
80  
90  
90  
110  
110  
125  
60  
70  
80  
90  
90  
100  
200  
225  
250  
250  
250  
300  
200  
225  
225  
250  
250  
250  
100  
110  
110  
125  
125  
150  
80  
90  
90  
100  
100  
110  
225  
250  
250  
250  
250  
300  
23.6  
6.5  
23.6  
208  
230  
460  
575  
208  
230  
460  
575  
208  
230  
460  
575  
187 229 23  
207 253 23  
414 508 10.2  
184  
184  
23  
23  
184 21.8 184 21.8 184  
2
2
2
2
2
2
2
2
4
4
4
4
46.2  
(ea)  
23.6  
59.4  
23.6  
28.0  
6.6  
(ea)  
23.6  
184 21.8 184 21.8 184  
42.0  
23.6  
54.0  
030  
035  
036  
12.6  
14.0  
3.3  
(ea)  
12.6  
90 10.2  
90  
73  
11  
9
90  
73  
11  
9
90  
73  
21.0  
12.6  
27.0  
9.6  
11.0  
2.6  
(ea)  
9.6  
518 632  
9
73  
9
17.0  
9.6  
22.0  
46.2  
23.6  
6.5  
(ea)  
23.6  
187 229 21.8 184 25.6 190 25.6 190 25.6 190  
59.4  
23.6  
74.8  
23.6  
42.0  
6.6  
(ea)  
23.6  
207 253 21.8 184 25.6 190 25.6 190 25.6 190  
54.0  
23.6  
68.0  
12.6  
21.0  
3.3  
(ea)  
12.6  
414 508 11  
90 13.5  
73 10.2  
95 13.5  
75 10.2  
95 13.5  
75 10.2  
95  
75  
27.0  
12.6  
34.0  
17.0  
9.6  
2.6  
(ea)  
518 632  
9
22.0  
9.6  
27.0  
9.6  
23.6  
46.2  
6.5  
(ea)  
23.6  
187 229 21.8 184 25.6 190 25.6 190 25.6 190  
59.4  
23.6  
74.8  
23.6  
225  
250  
250  
250  
250  
300  
110  
125  
125  
125  
125  
150  
90  
100  
42.0  
6.6  
(ea)  
23.6  
207 253 21.8 184 25.6 190 25.6 190 25.6 190  
54.0  
23.6  
68.0  
12.6  
94.5  
107.1  
102.0  
114.6  
110.7  
123.3  
73.8  
83.4  
80.0  
89.6  
86.3  
95.9  
21.0  
3.3  
(ea)  
12.6  
414 508 11  
90 13.5 95 13.5  
95 13.5  
75 10.2  
95  
75  
27.0  
12.6  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
34.0  
9.6  
17.0  
2.6  
(ea)  
9.6  
100  
110  
110  
110  
518 632  
9
73 10.2 75 10.2  
22.0  
27.0  
9.6  
See Legend and Notes on page 28.  
26  
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet (cont)  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER CONVENIENCE  
POWER SUPPLY  
UNIT  
SIZE  
48A  
FAN MOTOR FAN MOTOR EXHAUST  
OUTLET  
VOLTAGE  
3 PH, 60 Hz  
Fuse or  
MCA  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
FLA  
Hp  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
15  
20  
25  
20  
25  
30  
20  
25  
30  
20  
25  
30  
20  
25  
30  
FLA  
46.2  
59.4  
74.8  
42.0  
54.0  
68.0  
21.0  
27.0  
34.0  
17.0  
22.0  
27.0  
46.2  
59.4  
74.8  
42.0  
54.0  
68.0  
21.0  
27.0  
34.0  
17.0  
22.0  
27.0  
59.0  
75.0  
88.0  
54.0  
68.0  
80.0  
27.0  
34.0  
40.0  
22.0  
27.0  
32.0  
FLA (total)  
FLA  
HACR Brkr*  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
210.6  
234.2  
227.1  
250.7  
246.3  
269.9  
205.7  
229.3  
220.7  
244.3  
238.2  
261.8  
102.0  
114.6  
109.5  
122.1  
118.2  
130.8  
80.4  
90.0  
86.6  
96.2  
92.9  
102.5  
210.6  
234.2  
227.1  
250.7  
246.3  
269.9  
205.7  
229.3  
220.7  
244.3  
238.2  
261.8  
102.0  
114.6  
109.5  
122.1  
118.2  
130.8  
80.4  
90.0  
86.6  
96.2  
92.9  
102.5  
257.2  
280.8  
276.4  
300.0  
292.9  
316.5  
250.8  
274.4  
250  
250  
250  
300  
300  
300  
225  
250  
250  
250  
300  
300  
110  
125  
125  
125  
150  
150  
90  
100  
100  
110  
110  
125  
250  
250  
250  
300  
300  
300  
225  
250  
250  
250  
300  
300  
110  
125  
125  
125  
150  
150  
90  
100  
100  
110  
110  
125  
300  
300  
350  
350  
350  
400  
300  
300  
23.6  
6.5  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
9.6  
9.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
9.6  
9.6  
9.6  
23.6  
23.6  
23.6  
23.6  
23.6  
23.6  
12.6  
12.6  
12.6  
208  
230  
460  
575  
208  
230  
460  
575  
208  
230  
460  
575  
187 229 25.6 190 25.6 190 34.3 265 34.3 265  
2
2
2
2
4
4
4
4
4
4
4
4
(ea)  
6.6  
(ea)  
207 253 25.6 190 25.6 190 34.3 265 34.3 265  
040  
041  
050  
3.3  
(ea)  
414 508 13.5  
518 632 10.2  
95 13.5  
75 10.2  
95 16.0 120 16.0 120  
2.6  
(ea)  
75 12.9  
80 12.9  
80  
6.5  
(ea)  
187 229 25.6 190 25.6 190 34.3 265 34.3 265  
6.6  
(ea)  
207 253 25.6 190 25.6 190 34.3 265 34.3 265  
3.3  
(ea)  
414 508 13.5 95 13.5 95  
16  
120  
16  
120  
80  
2.6  
(ea)  
518 632 10.2 75 10.2  
75 12.9  
80 12.9  
6.5  
(ea)  
187 229 34.3 265 34.3 265 34.3 265  
47  
47  
380  
380  
6.6  
(ea)  
268.3  
291.9  
283.3  
306.9  
120.9  
133.5  
129.6  
142.2  
137.1  
149.7  
97.7  
107.3  
300  
350  
350  
350  
125  
150  
150  
175  
175  
175  
110  
125  
125  
125  
125  
150  
207 253 34.3 265 34.3 265 34.3 265  
3.3  
(ea)  
414 508 16  
120  
16  
120  
16  
120 22.4 175  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
9.6  
9.6  
9.6  
2.6  
(ea)  
104.0  
113.6  
110.2  
119.8  
518 632 12.9  
80 12.9  
80 12.9  
80 18.6 140  
See Legend and Notes on page 28.  
27  
Table 8B — Electrical Data — 48AJ,AK,AW,AY Units with Convenience Outlet (cont)  
COMPRESSOR  
Cir A, No. 1 Cir A, No. 2 Cir B, No. 1 Cir B, No. 2  
VOLTAGE  
RANGE  
CONDENSER EVAPORATOR POWER CONVENIENCE  
POWER SUPPLY  
UNIT  
SIZE  
48A  
FAN MOTOR FAN MOTOR EXHAUST  
OUTLET  
VOLTAGE  
3 PH, 60 Hz  
Fuse or  
MCA  
Min Max RLA LRA RLA LRA RLA LRA RLA LRA Qty  
FLA  
Hp  
20  
25  
30  
40  
20  
25  
30  
40  
20  
25  
30  
40  
20  
25  
30  
40  
25  
30  
40  
25  
30  
40  
25  
30  
40  
25  
30  
40  
FLA  
59.4  
74.8  
88  
FLA (total)  
FLA  
HACR Brkr*  
35.4  
35.4  
35.4  
35.4  
35.4  
35.4  
35.4  
35.4  
18.9  
18.9  
18.9  
18.9  
14.4  
14.4  
14.4  
14.4  
35.4  
35.4  
35.4  
35.4  
35.4  
35.4  
18.9  
18.9  
18.9  
14.4  
14.4  
14.4  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
7.0  
3.5  
3.5  
3.5  
3.5  
3.5  
3.5  
2.5  
2.5  
2.5  
2.5  
2.5  
2.5  
257.5  
292.9  
300  
350  
276.7  
312.1  
350  
350  
6.5  
(ea)  
208  
230  
460  
575  
187 229 34.3 265 34.3 265 34.3 265 34.3 265  
6
6
6
6
293.2  
328.6  
350  
400  
325.7  
361.1  
400  
450  
114  
54  
251.3  
286.7  
300  
300  
268.8  
304.2  
300  
350  
68  
6.6  
(ea)  
207 253 34.3 265 34.3 265 34.3 265 34.3 265  
283.8  
319.2  
350  
350  
80  
313.8  
349.2  
400  
450  
104  
27  
051  
121.1  
140.0  
125  
150  
129.8  
148.7  
150  
175  
34  
3.3  
(ea)  
414 508 16  
120  
16  
120  
16  
120  
16  
120  
137.3  
156.2  
175  
175  
40  
152.3  
171.2  
200  
200  
52  
97.2  
111.6  
110  
125  
22  
103.5  
117.9  
125  
125  
27  
2.6  
(ea)  
518 632 12.9  
80 12.9  
80 12.9  
80 12.9  
80  
109.7  
124.1  
125  
150  
32  
121.0  
135.4  
150  
175  
41  
315.1  
350.5  
350  
400  
75.0  
88.0  
114.0  
68.0  
80.0  
104.0  
34.0  
40.0  
52.0  
27.0  
32.0  
41.0  
6.5  
(ea)  
331.6  
367.0  
400  
450  
208  
230  
460  
575  
187 229 40.8 265  
47  
47  
380 40.8 265  
47  
47  
380  
380  
6
6
6
6
364.1  
399.5  
450  
500  
307.2  
342.6  
350  
400  
6.6  
(ea)  
322.2  
357.6  
400  
400  
207 253 40.8 265  
380 40.8 265  
352.2  
387.6  
450  
450  
060  
151.0  
169.9  
175  
200  
3.3  
(ea)  
158.5  
177.4  
175  
200  
414 508 20.2 135 22.4 175 20.2 135 22.4 175  
173.5  
192.4  
225  
225  
122.3  
136.7  
125  
150  
2.6  
(ea)  
128.5  
142.9  
150  
150  
518 632 16.6 120 18.6 140 16.6 120 18.6 140  
139.8  
154.2  
175  
175  
LEGEND  
Full Load Amps  
Example: Supply voltage is 460-3-60.  
AB = 452 v  
BC = 464 v  
AC = 455 v  
FLA  
HACR  
LRA  
MCA  
NEC  
RLA  
Heating, Air Conditioning and Refrigeration  
Locked Rotor Amps  
Minimum Circuit Amps  
National Electrical Code  
Rated Load Amps  
452 + 464 + 455  
Average Voltage =  
=
3
1371  
3
*Fuse or HACR circuit breaker per NEC.  
NOTES:  
= 457  
1. In compliance with NEC requirements for multimotor and combination load  
equipment (refer to NEC Articles 430 and 440), the overcurrent protective  
device for the unit shall be fuse or HACR breaker. The Canadian units may  
be fuse or circuit breaker.  
Determine maximum deviation from average voltage.  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
2. Unbalanced 3-Phase Supply Voltage  
(AC) 457 – 455 = 2 v  
Never operate a motor where a phase imbalance in supply voltage is  
greater than 2%. Use the following formula to determine the percent of volt-  
age imbalance.  
Maximum deviation is 7 v.  
Determine percent of voltage imbalance.  
7
% Voltage imbalance  
% Voltage Imbalance  
= 100 x  
457  
max voltage deviation from average voltage  
= 1.53%  
= 100 x  
average voltage  
This amount of phase imbalance is satisfactory as it is below the maximum  
allowable 2%.  
IMPORTANT: If the supply voltage phase imbalance is more than 2%,  
contact your local electric utility company immediately.  
28  
Routing Through Bottom of Unit — If wiring is brought in  
through bottom of unit, use field-supplied watertight conduit to  
route power wiring through the 31/2-in. diameter hole provided  
in the unit basepan.  
IMPORTANT: On 208/230-v units, transformers 1-5 are  
wired for 230-v. If 208/230-v unit is to be run with 208-v  
power supply, the transformers must be rewired as follows:  
Install conduit connector in unit basepan as shown in  
Fig. 4-9. Route power and ground lines through connector to  
terminal connections in unit control box as shown on unit  
wiring diagram and Fig. 19.  
Use strain relief going into control box through 35/8-in.  
diameter hole provided. After wires are in unit control box,  
connect to power terminal block (see Power Wiring section on  
page 20).  
For transformer 1 move the black wires connected to termi-  
nal H2 and connect it to terminal H3.  
For transformers 2-4, that are used for the 24-volt control  
circuits, connect as follows:  
1. Remove cap from red (208 v) wire.  
2. Remove cap from spliced orange (230 v) wire. Discon-  
nect orange wire from black unit power wire.  
3. Cap orange wire.  
4. Splice red wire and black unit power wire. Cap wires.  
Low-voltage wiring must be run in watertight conduit from  
7
the basepan to control box and through /8-in. diameter hole  
provided in bottom of unit control box. Field-supplied strain  
relief must be used going into the box. After wiring is in  
control box, make connections to proper terminals on terminal  
blocks (see Field Control Wiring section on this page).  
Routing Through Side of Unit — Route power wiring in  
field-supplied watertight conduit into unit through 21/2-in. (siz-  
es 020-035) or 3-in. (sizes 036-060) hole.  
Use field-supplied strain relief going into control box  
through 35/8-in. diameter hole provided. After wires are in unit  
control box, connect to power terminal block (see Power Wir-  
ing section on page 20).  
Bring low-voltage control wiring through the 7/8-in. diame-  
ter hole provided in the condenser section side post. Use strain  
relief going into 7/8-in. diameter hole in bottom of unit control  
box.  
If the unit is equipped with the optional convenience outlet  
connect the yellow wire to H2 on transformer 5.  
IMPORTANT: BE CERTAIN UNUSED WIRES ARE  
CAPPED. Failure to do so may damage the transformers.  
FIELD CONTROL WIRING — The 48A Series units sup-  
port a large number of control options that can impact the field  
control wiring.  
The control options that the unit can provide relate to the  
following parameters:  
• CV (constant volume), VAV (variable air volume),  
VVT® (variable volume variable temperature) or  
Carrier TEMP system control operation.  
• Stand-alone with a thermostat (CV) or with a space sen-  
sor (CV and VAV)  
After wiring is in control box, make connection to proper  
terminals on terminal blocks (see Field Control Wiring section  
below).  
• Network application with CCN (Carrier Comfort  
Network®) or other networks  
• Demand ventilation with CO2 sensor  
• Economizer and economizer with changeover control  
• Staged gas heat  
IMPORTANT: The VAV (variable air volume) units use  
variable frequency drives, which generate and can radiate  
radio frequency energy. If units are not installed and used  
in accordance with these instructions, they may cause radio  
interference. They have been tested and found to comply  
with limits of a Class A computing device as defined by  
FCC (Federal Communications Commission) regulations,  
Subpart J of Part 15, which are designed to provide reason-  
able protection against such interference when operated in  
a commercial environment.  
• Building and duct static pressure control  
• Fire shutdown and smoke control  
• Diagnostics and monitoring  
For constant volume applications a thermostat (T-Stat) or  
space temperature sensor (SPT) will be required.  
T-STAT (Conventional Thermostat) — Unit can be con-  
trolled with a Carrier-approved accessory electro-mechanical  
or electronic thermostat that has two stages of cooling, two  
stages of heating control and an output for indoor fan control. It  
may also include time of day scheduling or use the scheduling  
routines built into the ComfortLink™ controls.  
WARNING  
The unit must be electrically grounded in accordance with  
local codes and NEC ANSI/NFPA 70 (National Fire  
Protection Association). Electrical shock could cause per-  
sonal injury.  
Install thermostat according to the installation instructions  
included with accessory thermostat and the unit wiring dia-  
grams. Locate thermostat assembly on a solid interior wall in  
the conditioned space to sense average temperature.  
Route thermostat cable or equivalent single leads of colored  
wire from subbase terminals through conduit into unit to low-  
voltage connection in the main control box. For thermostat  
TB4 connections see Fig. 20.  
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American  
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,  
use no. 16 AWG insulated wire (35 C minimum). For over  
75 ft, use no. 14 AWG insulated wire (35 C Minimum). All  
wire larger than no. 18 AWG cannot be directly connected at  
the thermostat and will require a junction box and splice at the  
thermostat. Set heat anticipator settings as follows:  
Affix crankcase heater sticker (located in the installers  
packet) to unit disconnect switch.  
Voltage to compressor terminals during compressor operation  
must be within the voltage range indicated on the unit name-  
plate. Phases must be balanced within 2%.  
Use the formula in Tables 8A and 8B to determine the per-  
centage of voltage imbalance.  
IMPORTANT: If the supply voltage phase imbalance is  
more than 2%, contact your local electric utility company  
immediately.  
STAGE 1  
(W1) ON  
STAGE 2  
(W1 and W2) ON  
SIZE  
Unit failure as a result of operation on improper line voltage  
or excessive phase imbalance constitutes abuse and may cause  
damage to electrical components.  
020-050  
051, 060  
0.24  
0.36  
0.13  
0.13  
Settings may be changed slightly to provide a greater degree of  
comfort for a particular installation.  
29  
Staged Gas Control Option Thermistors — If the unit is  
equipped with the staged gas heat option, supply-air ther-  
mistors must be installed. Three supply-air thermistors are  
shipped with staged gas units and are inside the heating sec-  
tion. The supply-air thermistors should be located in the supply  
duct with the following criteria:  
FIELD-SUPPLIED THERMOSTAT  
LIGHT  
RC  
Y1  
Y2  
W1  
W1  
W2  
G
C
X
R
Y1  
2
Y2  
W2  
5
G
6
C
7
X
R
1
• Downstream of the heat exchanger cells  
a48-8243  
• Equally spaced as far as possible from the heat  
exchanger cells  
3
4
8
TB4  
• In a duct location where none of the supply-air ther-  
mistors are within sight of the heat exchanger cells  
• In a duct location with good mixed supply-air portion of  
the unit.  
Fig. 20 — Field Control Thermostat Wiring  
T55 SPT  
T56 SPT  
SPT (Space Temperature Sensor) — For constant volume ap-  
plications the ComfortLink™ controls can also be used with  
T55 and T56 space temperature sensors that use a 10K ther-  
mistor. The T56 sensor also has the capability for a config-  
urable temperature set point offset. For variable air volume ap-  
plications only the T55 sensor can be used.  
C
T1  
TH  
T2  
SN  
Install sensor according to the installation instructions  
included with accessory sensor. Locate sensor assembly on a  
solid interior wall in the conditioned space to sense average  
temperature.  
1
13  
14  
11  
12  
3
4
5
6
9
7
8
15  
16  
UNIT  
TB5  
2
10  
Run wiring to the space sensor as shown in Fig. 21.  
a48-6854  
Note that when the remote sensor is used, the red jumper  
wires provided must be connected from TB4 terminal 4 to 5  
and TB4 terminal 5 to 1.  
Fig. 21 — Space Temperature Sensor Wiring  
Both the T55 and T56 have a CCN communications port and  
this should be wired to the CCN Communications TB3 board if  
it is desired to have access to the CCN through the sensor. If  
more than one T-55 sensor is being used and averaged, sensors  
must be wired in multiples of 4 or 9 as shown in Fig. 22.  
TB5  
RED  
3
BLK  
4
SENSOR 4  
SENSOR 3  
SENSOR 1  
SENSOR 2  
SPACE TEMPERATURE AVERAGING (4 SENSOR APPLICATION)  
TB5  
3
4
SENSOR 1  
SENSOR 2  
SENSOR 3  
SENSOR 6  
SENSOR 5  
SENSOR 4  
SENSOR 9  
SPACE TEMPERATURE AVERAGING (9 SENSOR APPLICATION)  
SENSOR 8  
SENSOR 7  
a48-6855  
NOTE: Use T55 sensor only.  
Fig. 22 — Space Temperature Averaging Wiring  
30  
T58 Communicating Thermostat — Carrier also has a fully  
communicating thermostat which, if used, will be wired to the  
CCN communication connections on TB3 as described in the  
Carrier Comfort Network® Interface section below.  
c. Insert and secure the black (–) wire to terminal 3 of  
the 3-pin plug.  
4. Insert the plug into the existing 3-pin mating connector on  
the base module in the main control box.  
Carrier Comfort Network Interface — The rooftop units can  
be connected to the CCN system. The communication bus  
wiring is supplied and installed in the field. Wiring consists of  
shielded, 3-conductor cable with drain wire. The system  
elements are connected to the communication bus in a daisy  
chain arrangement. The positive pin of each system element  
communication connector must be wired to the positive pins of  
the system element on either side of it, the negative pins must be  
wired to the negative pins, and the signal pins must be wired to  
signal ground pins. Wiring connections for CCN should be  
made at the TB3 terminal block using the screw terminals. The  
TB3 board also contains an RJ14 CCN plug that can be used to  
connect a field service computer or other CCN device tempo-  
rarily. There is also an RJ14 LEN (local equipment network)  
connection that is used to connect a Navigatordevice or  
download software.  
Conductors and drain wire must be 20 AWG minimum  
stranded, tinned copper. Individual conductors must be insulat-  
ed with PVC, PVC/nylon, vinyl, Teflon, or polyethylene. An  
aluminum/polyester 100% foil shield and an outer jacket of  
PVC, PVC/nylon, chrome vinyl, or Teflon with a minimum  
operating temperature range of –20 C to 60 C (–4 F to 140 F) is  
required. Table 9 lists cables that meet the requirements.  
VAV Units with Heat — For variable air volume units that  
will use heat, the variable air volume terminals should be  
interlocked with the unit at TB5 terminals 1 and 2.  
Demand Ventilation — The unit can be equipped with a CO2  
sensor for use in demand ventilation. This can be factory  
supplied and will be mounted in the return duct. It can also be  
field supplied and mounted in the return duct or in the space.  
Connect the field-installed 4 to 20 mA sensor to TB5 terminal  
6 and 7. Do not remove the factory-installed 182-ohm resistor.  
If an outdoor air quality sensor is used then it should be  
wired to terminal 11 and 12 on TB6. This will require the use  
of the optional controls expansion module.  
Remote IAQ Override — If the control is being used with non  
Carrier building management system it supports the use of the  
remote IAQ override switch. This should be connected to  
TB6 terminal 13 and 14. Use of this will require the optional  
controls expansion module.  
Remote Economizer Position Control — The ComfortLink™  
controls will normally control the position of the economizer,  
but it can also support field control of the economizer position  
through a 4 to 20 mA signal. If this is used it should be con-  
nected to TB5 terminal 6 and 7. If the signal is a 4 to 20 mA  
signal then leave the 182-ohm resistor in place.  
Remote Economizer Enable — If the control is being used  
with other building management systems and the system will  
control the enabling and disabling of the economizer free cool-  
ing, this switch input can be connected to TB6 terminals 1 and  
2. Note that the controls also support integrated economizer  
changeover using outdoor dry bulb, differential dry bulb,  
outdoor enthalpy and differential enthalpy.  
Table 9 — CCN Connection Approved Shield Cable  
MANUFACTURER  
Alpha  
American  
Belden  
CABLE PART NO.  
2413 or 5463  
A22503  
8772  
Columbia  
02525  
IMPORTANT: When connecting to CCN communi-  
cation bus to system elements, use color coding  
system for the entire network to simplify installation  
and checkout. See Table 10.  
Remote Occupancy Switch — For interface to other building  
management systems the control also supports a switch input  
for remote occupancy signals. This wiring should be connected  
to terminal TB6 terminal 1 and 3.  
Remote Economizer Minimum Position Control — If the  
ComfortLink control is controlling the economizer, but a remote  
minimum position is required, then an external 100K potentiom-  
eter can be connected to TB5 terminal 6 and 7. Remove the  
factory-installed 182-ohm resistor.  
Smoke Sensor Interface — The ComfortLink control includes  
an optional factory-installed return air smoke detector. Remote  
alarm circuits can be wired to TB5 terminal 8 and 9.  
Table 10 — Color Code Recommendations  
CCN BUS CONDUCTOR  
INSULATION COLOR  
CCN PLUG PIN  
NO.  
SIGNAL TYPE  
Positive (+)  
Ground  
Negative (–)  
RED  
WHITE  
BLACK  
1
2
3
If a cable with a different color scheme is selected, a similar  
color code should be adopted for the entire network. At each  
system element, the shields of the communication bus cables  
must be tied together. If the communication bus is entirely  
within one building, the resulting continuous shield must be  
connected to a ground at one point only. If the communication  
bus cable exits from one building and enters another, the  
shields must be connected to grounds at the lightning suppres-  
sor in each building where the cable enters or exits the building  
(one point per building only).  
To connect the unit to the network:  
1. Turn off power to the control box.  
2. Cut the CCN wire and strip the ends of the red (+), white  
(ground), and black (–) conductors. (If a different net-  
work color scheme is used, substitute appropriate colors.)  
Fire Shutdown and Smoke Control — The control supports  
interface to fire and smoke control systems and allows for the  
following system overrides from remote switch inputs.  
Fire Shutdown — Connect to TB6 terminals 8 and 9.  
Smoke Pressurization — Connect to TB6 terminal 12  
and 13. This requires the use of the optional controls  
expansion module.  
Smoke Evacuation — Connect to TB6 terminal 12 and  
14. This requires the use of the optional controls expan-  
sion module.  
Smoke Purge — Connect to TB6 terminal 12 and 15.  
This requires the use of the optional controls expansion  
module.  
Demand Limiting — The control can also be used with demand  
limiting control from remote building management systems. If a  
two stage system is going to be used with Redline Limiting  
where the machine is not allowed to increase load and Load Shed  
where the load is decreased to a configurable limit in capacity  
then these can be connected to TB6 terminals 4 and 5 and 5 and  
6. This requires use of the controls expansion module.  
3. Remove the 3-pin male plug from the base control board  
in the main control box, and connect the wires as follows:  
a. Insert and secure the red (+) wire to terminal 1 of  
the 3-pin plug.  
b. Insert and secure the white (ground) wire to termi-  
nal 2 of the 3-pin plug.  
31  
Step 9 — Make Outdoor-Air Inlet Adjustments  
ECONOMIZER AND FIXED OUTDOOR AIR  
DAMPER — Hoods are used on all units with economizer or  
adjustable self-closing fixed outdoor air damper.  
NOTE: If accessory power exhaust or barometric relief pack-  
ages are being added to the unit, install power exhaust or baro-  
metric relief before installing economizer hoods.  
TOP  
FLANGE  
BLACK  
SEAL  
STRIP  
HOOD SIDE  
Economizer Hood Assembly — The economizer hood is  
shipped in a package secured to the outside of the unit. The  
hood assemblies must be field-assembled. The 48AW,AY units  
are side supply and side return. The return duct limits access to  
economizer filters from below.  
The 48AJ,AK,AW,AY020-050 units have two hoods on ev-  
ery unit. The 48AJ,AK,AW,AY051 and 060 units have 3 hoods  
on every unit.  
NOTE: Before assembly of the economizer hood, check along  
the outer edges of the economizer assembly for any seal strip  
protruding past the flanges. Trim the excess seal strip so that it  
is flush with the economizer assembly flanges.  
Fig. 23 — Adding Seal Strip to Top of Hood Sides  
Perform the following procedure to assemble the economizer  
hood.  
a48-8498  
1. Apply black seal strip (provided) to outside top-edge of  
hood sides. Wrap seal strip over edge to cover top flange  
(6 hood sides). Make sure seal strip covers screw holes.  
Allow strip to overhang 1/8-in. past the end opposite the  
mounting flange. See Fig. 23.  
2. Assemble hood sides, top, and cross member with  
gasketed screws provided. See Fig. 24.  
3. Attach 15 green speed clips (provided) to hood top.  
4. Apply black seal strip (provided) to mounting flanges of  
hood sides being sure to cover mounting holes. See  
Fig. 25.  
5. Apply black seal strip (provided) to back of hood top  
mounting flange. Seal strip of hood top mounting flange  
must press tightly against seal strip of hood side mount-  
ing flanges. See Fig. 26.  
6. Add gray foam strip (provided) to cross members on bot-  
tom tray. See Fig. 27.  
7. Attach gray foam strip (provided) to block-off baffle on  
outer face of flange. See Fig. 28.  
8. Remove the screws on each end and along top of damper  
assembly of unit. Remove top 4 screws on each side of  
filter panel under damper assembly. Set hood assembly in  
place and attach to unit using these screws.  
Fig. 24 — Economizer Hood Assembly  
(Right Side/Center Economizer Hood Shown)  
9. Remove screws along bottom of damper assembly.  
Locate and mount block-off baffle using these screws.  
10. Assemble 2 filter tracks side-by-side with the assembled  
ends together.  
11. Attach one mounting angle to the assembled end of the  
filter track. See Fig. 29.  
MOUNTING  
FLANGE  
12. Attach 9 green speed clips (provided) to hood side panels.  
Engagement section of clip faces up and towards the out-  
side of the hood side panels.  
HOOD SIDE  
13. Attach remaining mounting angle to other end of the filter  
track with no. 10 screws provided.  
14. Place filter track assembly in bottom of hood by attaching  
to hood with speed clips and gasketed screws provided.  
NOTE: Be sure the filters are installed with the airflow in the  
correct direction.  
15. Attach black seal strip (provided) to filter cover. Seal strip  
should be applied centered over the holes of the one  
flange, making sure to fully cover holes and centered over  
the other large flange. See Fig. 30.  
16. Slide two 20 x 25-in. filters into cross members of hood  
assembly. Attach filter cover over filters with screws and  
speed clips provided.  
Fig. 25 — Adding Seal Strip to Sides of Hood Top  
Mounting Flange  
32  
HOOD TOP  
MOUNTING ANGLE  
HOOD SIDE  
FILTER TRACK  
ASSEMBLY  
a48-8499  
Fig. 29 — Mounting Angle Attached  
to Filter Track Assembly  
48-1104  
BLACK SEAL STRIP  
(CENTERED)  
Fig. 26 — Adding Seal Strip to Back of Hood Top  
Mounting Flange  
GRAY FOAM STRIP  
FILTER COVER  
CROSS MEMBER  
48-1110  
Fig. 30 — Attaching Seal Strip to Filter Cover  
Step 10 — Position Power Exhaust/Barometric  
Relief Damper Hood — All units are shipped with the  
hoods folded inside the unit in a shipping position. For 48AJ,  
and AK units the hood must be tilted out once the unit is in-  
stalled. On 48AW, AY units, (designed for horizontal supply  
and return) the assemblies will have to be relocated to return  
ductwork. See Fig. 31 for dimensions and details.  
48-1105  
Fig. 27 — Adding Foam Strip to Cross Member  
All electrical connections have been made and adjusted at  
the factory. The power exhaust blowers and barometric relief  
dampers are shipped assembled and tilted back into the unit for  
shipping. Brackets and extra screws are shipped in shrink wrap  
around the dampers. If ordered, each unit will have 4  
(48AJ,AK,AW,AY020-050 units) or 6 (48AJ,AK,AW,AY051  
and 060 units) power exhaust blowers and motors or baromet-  
ric relief dampers.  
BLOCKOFF BAFFLE  
1. Remove 9 screws holding each damper assembly in  
place. See Fig. 32. Each damper assembly is secured with  
3 screws on each side and 3 screws along the bottom.  
Save screws.  
GRAY FOAM STRIP  
CAUTION  
Be careful when tilting blower assembly. Hoods and blow-  
ers are heavy and can cause injury if dropped.  
2. Pivot each damper assembly outward until edges of  
damper assembly rest against inside wall of unit.  
3. Secure each damper assembly to unit with 6 screws  
across top (3 screws provided) and bottom (3 screws  
from Step 1) of damper.  
a48-4328  
4. With screws saved from Step 1, install brackets on each  
side of damper assembly.  
5. Remove tape from damper blades.  
Fig. 28 — Adding Seal Strip to Block-Off Baffle  
33  
ECONOMIZER  
HOOD  
42.56”  
LOCATION  
BAROMETRIC RELIEF  
OR POWER EXHAUST  
“SIDE #2”  
ECONOMIZER  
HOOD  
23.28”  
TYP  
END #2”  
42MIN.  
12.94  
(UNIT  
OPENING)  
R/A  
S/A  
“SIDE #1”  
END #1”  
J BOX  
23.28”  
42.62”  
PLENUM RATED  
CABLE  
(FIELD SUPPLIED)  
42.62  
TYP  
ALTERNATE  
LOCATION  
(END)  
J BOX  
S/A  
R/A  
NOTE: 020-050 SIZES SHOWN (2 POWER EXHAUST FANS).  
SIZES 051 AND 060 HAVE 3 POWER EXHAUST FANS. ALL  
UNIT SIZES HAVE THE SAME SIZE POWER EXHAUST.  
a48-8244  
Fig. 31 — Power Exhaust Relocated to Side Return Duct  
a48-3808  
NOTES:  
1. Unless otherwise specified, all dimensions are to outside of part.  
2. Dimensions are in inches.  
3. On 48AW,AY units, accessory barometric relief or power exhaust must be mounted in the field-supplied return ductwork.  
Fig. 32 — Barometric Relief Damper and Power Exhaust Mounting Details  
lower inner panel. See Fig. 33. A section of field-supplied  
1/4-in. plastic tubing must be run from the high pressure tap on  
the differential pressure switch to the conditioned space. The  
pressure tube must be terminated in the conditioned space  
where a constant pressure is required. This location is usually  
in an entrance lobby so that the building exterior doors will  
open and close properly. Remove plug button in panel to route  
tubing.  
Step 11 — Route VAV Static Pressure Sensors  
VAV DUCT PRESSURE TRANSDUCER — The VAV duct  
pressure transducer (VAV inverter pressure transducer) is locat-  
ed behind the filter access door on the lower inner panel. See  
Fig. 33. A section of field-supplied 1/4-in. plastic tubing must  
be run from the high pressure tap on the differential pressure  
switch and connected to a field-supplied tap in the supply-air  
duct. The tap is usually located 2/3 of the way out on the main  
supply duct. Remove plug button in panel to route tubing.  
The low pressure tap is factory-routed to the atmosphere.  
For a positive-pressure building, route the high tap to building  
air and low tap to atmosphere. For a negative-pressure  
VAV BUILDING PRESSURE TRANSDUCER — The VAV  
building pressure transducer (modulating power exhaust pres-  
sure transducer) is located behind the filter access door on the  
34  
building, route the high tap to atmosphere and the low tap to  
building air.  
capable of supporting the weight of a person. The return  
ductwork connection locations on the side of the unit are higher  
than normal (31-in. high). Unit-mounted power exhaust or  
barometric relief cannot be used because of return air ductwork  
will cover the power exhaust or barometric relief installation  
locations. Power exhaust or barometric relief may be installed  
in the return air ductwork.  
Step 12 — Install All Accessories — After all the  
factory-installed options have been adjusted, install all field-  
installed accessories. Refer to the accessory installation instruc-  
tions included with each accessory.  
The 48A Series units have a large number of factory-  
installed options which were previously available only as  
accessories. Some of the available options can also be installed  
in the field if needed. In most cases the units have been  
pre-wired so that the accessories can be easily installed.  
Instructions are shipped with each accessory. Configuration of  
the controls for these accessories as well as the factory-installed  
options can be found in the Controls, Start-Up, Operation,  
Service and Troubleshooting Book. The following is a list of  
some of the common accessories:  
To convert the unit, perform the following:  
1. Seal the bottom return openings of the unit with airtight  
panels capable of supporting the weight of a person.  
2. Remove the panels located below the economizer  
outdoor-air dampers. These openings will be used for the  
return-air ductwork. There are 2 panels on 48AJ,AK020-  
050 units. There are 3 panels on 48AJ,AK051 and 060  
and units. These openings are normally used for power  
exhaust or barometric relief.  
3. Run the return air ductwork up to the openings. One  
single duct is recommended to connect to the unit over  
the return air openings. See Fig. 34. The return duct must  
• Thermostats and space temperature sensors  
• LP (liquid propane) conversion kit  
• Accessory barometric relief damper  
• Accessory power exhaust  
• Non-modulating to modulating power exhaust  
• Condenser coil hail guards  
3
incorporate a minimum /4-in. flange for connection to  
the unit cabinet. The unit does not have duct flanges for  
this conversion.  
• Outdoor humidity sensor (used for economizer enthalpy  
changeover)  
• Return air humidity sensors (used for economizer  
differential enthalpy changeover)  
• Return air smoke detector  
• Controls expansion module (used for interface to build-  
ing management systems, not typically needed on  
system with the Carrier Comfort Network® [CCN] sys-  
tem)  
• Plugged filter sensor  
• Motormaster® V low ambient head pressure control  
Side Supply and Return Units (48AW,AY) with Field-  
Installed Power Exhaust in Return Duct — Space must be  
available in the return duct to mount the power exhaust fan  
(gravity relief) modules. Dimensions and suggested locations  
are shown in Fig. 34. These instructions are a guideline and not  
a comprehensive procedure. The design contractor must pro-  
vide some design initiative.  
The wiring harness that is provided with the power exhaust  
accessory is not long enough for the fan modules to be mount-  
ed in the return air duct. Field-supplied wiring must be spliced  
into the harness. Use a junction box at each splice. The wiring  
may be run in the return duct, or externally in conduit. A ser-  
vice access panel will be needed near each power exhaust fan.  
IMPORTANT: Carrier recommends the installation of  
field-fabricated wind baffles on all vertically oriented  
condenser coils when operating in environments with  
prevailing winds of more than 5 MPH and where tem-  
peratures drop below 32 F. See the Motormaster  
accessory installation guide for instructions.  
Step 13 — Field Modifications  
DUCTWORK  
Bottom Return Units (48AJ and AK) Field-Modified for  
Side Return — The 48AJ and AK units with bottom return air  
connections may be field-modified to accommodate side return  
air connections.  
IMPORTANT: The following section is a guideline and not  
a comprehensive procedure to field modify the units. The  
installing contractor must provide some design initiative.  
Field-conversion is complex and is not recommended.  
Units with electric heat must not be converted because of  
potential heating mode operating problems.  
AUXILIARY  
CONTROL BOX  
PRESSURE TRANSDUCERS  
(INSIDE OF PANEL)  
a48-6976  
Fig. 33 — Pressure Transducer Locations  
Conversion to horizontal return requires that the bottom  
return openings of the unit must be sealed with airtight panels  
35  
97.78” (020-050), 150.47(051 AND 060)  
INSIDE DIMENSION  
RA  
31.25”  
INSIDE  
a48-8245  
Fig. 34 — Side Return Air Conversion  
Copyright 2009 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53480067-01 Printed in U.S.A. Form 48A-7SI Pg 36 8-09 Replaces: 48A-5SI  

Brother Printer MFC J835DW User Manual
BT 400 User Manual
Bush Hog 3226QT User Manual
Campbell Hausfeld MP5141 User Manual
Canon PIXMA MP600 User Manual
Cino FUZZYSCAN F400 User Manual
Epson STYLUS 625 User Manual
Frigidaire ROTARY CONTROL AIR CONDITIONER User Manual
Gravely 927062 RM1232 User Manual
HP Hewlett Packard PHOTOSMART C7200 User Manual