Bryant EVOLUTION 577D A User Manual

577D- -A  
EVOLUTIONR  
15 SEER SINGLE-PACKAGED AIR CONDITIONER AND GAS FURNACE  
SYSTEM WITH PURONR (R-410A) REFRIGERANT  
SINGLE PHASE  
2-5 NOMINAL TONS (SIZES 24-60)  
Installation Instructions  
CAUTION  
EQUIPMENT OPERATION HAZARD  
!
Failure to follow this caution may result in improper unit  
operation.  
OAT sensor must be field installed. See Accessory  
Installation for more details.  
!
CAUTION  
EQUIPMENT OPERATION HAZARD  
Failure to follow this caution may result in improper unit  
operation.  
This Evolutionr unit is designed for use with an Evolution  
User Interface.  
A09032  
NOTE: Read the entire instruction manual before starting the  
installation.  
Fig. 1 -- Unit 577D----A  
Checking Cooling and Heating Control Operation . . . . . . 28  
Checking and Adjusting Refrigerant Charge . . . . . . . . . . . 28  
Refrigerant Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
No Charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Low Charge Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
To Use Cooling Charging Charts . . . . . . . . . . . . . . . . . . . . 29  
Non--Communicating Emergency Cooling/Heating Mode . . 29  
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31--34  
Air Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Indoor Fan and Motor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Inducer Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Limit Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Burner Ignition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Main Burners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Inducer Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Outdoor Coil, Indoor Coil, and Condensate Drain Pan . . . . . 32  
Outdoor Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Electrical Controls and Wiring . . . . . . . . . . . . . . . . . . . . . . . 32  
Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
L o s s -- o f -- C h a r g e S w i t c h . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3  
High--Pressure Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
TABLE OF CONTENTS  
PAGE  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 2  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
RECEIVING AND INSTALLATION . . . . . . . . . . . . . . . . . 2--13  
Check Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Identify Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Inspect Shipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Provide Unit Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Slab Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Provide Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Rig and Place Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
Rigging/Lifting of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Select and Install Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . 9  
Configuring Units for Downflow (Vertical) Discharge . . . 10  
Provide for Condensate Disposal . . . . . . . . . . . . . . . . . . . . . 10  
Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Install Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Install Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . 12  
High--Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . 12  
Routing Power Leads Into Unit . . . . . . . . . . . . . . . . . . . . . 12  
Connecting Ground Lead to Ground Screw . . . . . . . . . . . 12  
Routing Control Power Wires . . . . . . . . . . . . . . . . . . . . . 13  
Accessory Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
Special Procedures for 208--v Operation . . . . . . . . . . . . . . 13  
PRE--START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16  
START--UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16--29  
Unit Start--Up and Troubleshooting . . . . . . . . . . . . . . . . . . . 16  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
Check for Refrigerant Leaks . . . . . . . . . . . . . . . . . . . . . . . . . 28  
Start--Up Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
®
Copeland Scroll Compressor (Puron Refrigerant) . . . . . . . . 33  
Refrigerant System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Compressor Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Servicing Systems on Roofs with Synthetic Materials . . . . 33  
Liquid--Line Filter Drier . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Puron (R--410A) Refrigerant Charging . . . . . . . . . . . . . . . 34  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
FINAL CHECKS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
CARE AND MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . 35  
START--UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
1
Provide Clearances  
The required minimum service clearances are shown in Fig. 5 and  
6. Adequate ventilation and outdoor air must be provided. The  
outdoor fan draws air through the outdoor coil and discharges it  
through the top fan grille. Be sure that the fan discharge does not  
recirculate to the outdoor coil. Do not locate the unit in either a  
corner or under an overhead obstruction. The minimum clearance  
under a partial overhang (such as a normal house overhang) is 48  
in. (1219 mm) above the unit top. The maximum horizontal  
extension of a partial overhang must not exceed 48 in. (1219 mm).  
A
C
MAXIMUM ALLOWABLE  
DIFFERENCE in. (mm)  
B
B-C  
(6.35)  
A-B  
(6.35)  
A-C  
IMPORTANT: Do not restrict outdoor airflow. An air restriction  
at either the outdoor--air inlet or the fan discharge may be  
detrimental to compressor life.  
(6.35)  
1/4  
1/4  
1/4  
A07925  
Fig. 2 -- Unit Leveling Tolerances  
Installation on older “G” series roof curbs.  
Do not place the unit where water, ice, or snow from an overhang  
or roof will damage or flood the unit. Do not install the unit on  
carpeting or other combustible materials. Slab--mounted units  
should be at least 4 in. (102 mm) above the highest expected water  
and runoff levels. Do not use unit if it has been under water.  
Two accessory kits are available to aid in installing a new “G”  
series unit on an old “G” roof curb.  
1. Accessory kit number CPADCURB001A00, (small chassis)  
and accessory kit number CPADCURB002A00, (large  
chassis) includes roof curb adapter and gaskets for the  
perimeter seal and duct openings. No additional  
modifications to the curb are required when using this kit.  
2. An alternative to the adapter curb is to modify the existing  
curb by removing the outer horizontal flange and use  
accessory kit number CPGSKTKIT001A00 which includes  
spacer blocks (for easy alignment to existing curb) and  
gaskets for the perimeter seal and duct openings. This kit is  
used when existing curb is modified by removing outer  
horizontal flange.  
Rig and Place Unit  
Rigging and handling of this equipment can be hazardous for  
many reasons due to the installation location (roofs, elevated  
structures, etc.).  
Only trained, qualified crane operators and ground support staff  
should handle and install this equipment.  
When working with this equipment, observe precautions in the  
literature, on tags, stickers, and labels attached to the equipment,  
and any other safety precautions that might apply.  
Training for operators of the lifting equipment should include, but  
not be limited to, the following:  
1. Application of the lifter to the load, and adjustment of the  
lifts to adapt to various sizes or kinds of loads.  
2. Instruction in any special operation or precaution.  
!
CAUTION  
UNIT/STRUCTURAL DAMAGE HAZARD  
3. Condition of the load as it relates to operation of the lifting  
kit, such as balance, temperature, etc.  
Follow all applicable safety codes. Wear safety shoes and work  
gloves.  
Failure to follow this caution may result in property damage.  
Ensure there is sufficient clearance for saw blade when cutting  
the outer horizontal flange of the roof curb so there is no  
damage to the roof or flashing.  
Inspection  
Prior to initial use, and at monthly intervals, all rigging shackles,  
clevis pins, and straps should be visually inspected for any  
damage, evidence of wear, structural deformation, or cracks.  
Particular attention should be paid to excessive wear at hoist  
hooking points and load support areas. Materials showing any kind  
of wear in these areas must not be used and should be discarded.  
OPTIONAL  
RETURN  
AIR  
OPTIONAL  
SUPPLY  
AIR  
OPENING  
OPENING  
!
WARNING  
UNIT FALLING HAZARD  
2˝  
Failure to follow this warning could result in personal  
injury or death.  
(50.8mm)  
Never stand beneath rigged units or lift over people.  
EVAP. COIL  
COND. COIL  
A07926  
!
Fig. 3 -- Slab Mounting Detail  
WARNING  
SLAB MOUNT  
PROPERTY DAMAGE HAZARD  
Place the unit on a solid, level concrete pad that is a minimum of 4  
in. (102 mm) thick with 2 in. (51 mm) above grade. The slab  
should extend approximately 2 in. (51 mm) beyond the casing on  
all 4 sides of the unit (See Fig. 3). Do not secure the unit to the slab  
except when required by local codes.  
Failure to follow this warning could result in personal  
injury/death or property damage.  
When straps are taut, the clevis should be a minimum of 36  
in. (914 mm) above the unit top cover.  
3
Dashed lines show cross support  
location for large basepan units.  
B
G
C
HVAC unit  
basepan  
HVAC unit  
base rails  
Sealing  
Gasket  
Roofcurb  
H
F
A
Anchor screw  
Wood nailer*  
Roofcurb*  
Flashing field  
supplied  
Insulation  
(field supplied)  
Roofing material  
field supplied  
E
D
Cant strip  
field supplied  
A09413  
SMALL/COMMON CURB  
*Provided with roofcurb  
A09090  
ROOF CURB DETAIL  
B
C
SMALL  
BASE  
UNIT  
SUPPLY  
AIR  
G
H
A
LARGE  
BASE  
UNIT  
F
RETURN  
AIR  
E
D
UNIT PLACEMENT ON  
COMMON CURB  
A09094  
A09415  
SMALL OR LARGE BASE UNIT  
LARGE CURB  
A09414  
A
B (small / common  
base)  
B (large  
base)  
IN. (mm)*  
C
D
E
F
UNIT  
SIZE  
CATALOG  
NUMBER  
G
H
IN.  
IN.  
IN.  
IN.  
IN.  
IN. (mm)  
IN. (mm)  
(mm)  
IN. (mm)*  
(mm)  
(mm)  
(mm)  
(mm)  
11  
CPRFCURB010A00  
CPRFCURB011A00  
CPRFCURB012A00  
CPRFCURB013A00  
Small  
or  
(279)  
32.4  
10 (254)  
14 (356)  
30.6 (778)  
(822)  
14  
(356)  
11  
(279)  
14  
(356)  
Large  
16  
(406)  
47.8  
(1214)  
14 (356)  
2.7 (69)  
46.1 (1170)  
43.9  
(1116)  
Large  
42.2 (1072)  
NOTES:  
1. Roof curb must be set up for unit being installed.  
2. Seal strip must be applied, as required, to unit being installed.  
3. Roof curb is made of 16--gauge steel.  
4. Attach ductwork to curb (flanges of duct rest on curb).  
5. Insulated panels: 1--in. (25.4 mm) thick fiberglass 1 lb. density.  
Fig. 4 -- Roof Curb Dimensions  
4
A09556  
Fig. 5 -- 577D----A24--30 Unit Dimensions  
5
A09557  
Fig. 6 -- 577D----A36--60 Unit Dimensions  
6
Table 1 – Physical Data -- Unit 577D----A  
UNIT SIZE  
NOMINAL COOLING CAPACITY (ton)  
NOMINAL HEATING CAPACITY (Btu)  
24040  
2
24060  
30040  
2 --- 1 / 2  
40,000  
30060  
2 --- 1 / 2  
60,000  
36060  
3
36090  
3
42060  
3 --- 1 / 2  
60,000  
42090  
3 --- 1 / 2  
90,000  
2
40,000  
60,000  
60,000  
90,000  
SHIPPING WEIGHT (lb)  
(kg)  
426  
193  
431  
196  
433  
196  
438  
199  
522  
237  
530  
240  
544  
247  
552  
250  
2 --- St a g e Sc r o l l  
COMPRESSORS  
Quantity  
1
REFRIGERANT: PURON (R---410A)  
Quantity (lb)  
(kg)  
10.1  
4.6  
10.1  
4.6  
11.3  
5.1  
11.3  
5.1  
9.5  
4.3  
9.5  
4.3  
13.8  
6.3  
13.8  
6.3  
REFRIGERANT METERING DEVICE  
TXV  
Size  
2 Ton  
2 Ton  
3 Ton  
3 Ton  
3 Ton  
3 Ton  
4 Ton  
4 Ton  
OUTDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
2...21  
13.6  
2...21  
13.6  
2...21  
15.3  
2...21  
15.3  
2...21  
17.5  
2...21  
17.5  
2...21  
19.4  
2...21  
19.4  
OUTDOOR FAN  
Nominal Cfm  
Diameter (in.)  
(mm)  
2700  
22  
2700  
22  
2700  
22  
2700  
22  
2800  
22  
2800  
22  
2800  
22  
2800  
22  
559  
559  
559  
559  
559  
559  
559  
559  
Motor Hp (Rpm)  
1/8 (825)  
1/8 (825)  
1/8 (825)  
1/8 (825)  
1/8 (825)  
1/8 (825)  
1/8 (825)  
1/8 (825)  
INDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
3...17  
3.7  
3...17  
3.7  
3...17  
3.7  
3...17  
3.7  
3...17  
4.7  
3...17  
4.7  
3...17  
4.7  
3...17  
4.7  
INDOOR FAN  
Nominal Airflow (Cfm)  
Comfort  
Variable based on Comfort Roll back (see User Interface instructions for more information).  
Efficiency  
Max  
Furnace (gas ht.) airflow---Low Stage  
Furnace (gas ht.) airflow---High Stage  
700  
800  
475  
844  
700  
800  
727  
875  
1000  
475  
875  
1000  
727  
1050  
1200  
745  
1050  
1200  
875  
1225  
1400  
745  
1225  
1400  
875  
1120  
844  
1120  
1120  
1410  
1120  
1410  
Size (in.)  
(mm)  
10x10  
254x254  
10x10  
254x254  
10x10  
254x254  
10x10  
254x254  
11x10  
279x254  
11x10  
279x254  
11x10  
279x254  
11x10  
279x254  
Motor HP  
1/2  
1/2  
1/2  
1/2  
3/4  
3/4  
3/4  
3/4  
FURNACE SECTION*  
Burner Orifice No. (Qty...Drill Size)  
Natural Gas (Factory Installed)  
Propane Gas  
2...44  
2...55  
3...44  
3...55  
2...44  
2...55  
3...44  
3...55  
3...44  
3...55  
3...38  
3...53  
3...44  
3...55  
3...38  
3...53  
HIGH---PRESSURE SWITCH (psig)  
C u t --- o u t  
Reset (Auto)  
670 ±10  
470 ± 25  
HIGH---PRESSURE SWITCH 2 (psig)  
(Compressor Solenoid)  
C u t --- o u t  
565 ± 15  
455 ± 15  
Reset (Auto)  
L O S S --- O F --- C H A R G E /  
LOW---PRESSURE SWITCH  
(Liquid Line) (psig)  
C u t --- o u t  
23 ± 5  
55 ± 5  
Reset (auto)  
RETURN---AIR FILTERS Throwaway†  
20x24x1  
508x610x25  
24x30x1  
610x762x25  
24x36x1  
610x914x25  
(in.)  
(mm)  
Continued next page.  
7
Table 1—Physical Data (Con’t) -- Unit 577D----A  
UNIT SIZE  
NOMINAL COOLING CAPACITY (ton)  
NOMINAL HEATING CAPACITY (Btu)  
48090  
48115  
48130  
60090  
5
60115  
5
60130  
5
4
4
4
90,000  
115,000  
130,000  
90,000  
115,000  
130,000  
SHIPPING WEIGHT (lb)  
(kg)  
558  
253  
558  
253  
558  
253  
609  
276  
609  
276  
609  
276  
2 --- St a g e Sc r o l l  
COMPRESSORS  
Quantity  
1
REFRIGERANT: PURON (R---410A)  
Quantity (lb)  
(kg)  
15.3  
6.9  
15.3  
6.9  
15.3  
6.9  
15.8  
7.2  
15.8  
7.2  
15.8  
7.2  
REFRIGERANT METERING DEVICE  
TXV  
Size  
4 Ton  
4 Ton  
4 Ton  
5 Ton  
5 Ton  
5 Ton  
OUTDOOR FAN  
Nominal Cfm  
Diameter (in.)  
(mm)  
3300  
22  
3300  
22  
3300  
22  
3300  
22  
3300  
22  
3300  
22  
559  
559  
559  
559  
559  
559  
Motor Hp (Rpm)  
1/4 (1100)  
1/4 (1100)  
1/4 (1100)  
1/3 (1110)  
1/3 (1110)  
1/3 (1110)  
OUTDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
2...21  
19.4  
2...21  
19.4  
2...21  
19.4  
2...21  
23.3  
2...21  
23.3  
2...21  
23.3  
INDOOR COIL  
Rows...Fins/in.  
Face Area (sq ft)  
3...17  
5.7  
3...17  
5.7  
3...17  
5.7  
4...17  
5.7  
4...17  
5.7  
4...17  
5.7  
INDOOR FAN  
Nominal Airflow (Cfm)  
Comfort  
Variable based on Comfort Roll back (see User Interface instructions for more information).  
Efficiency  
1400  
1600  
815  
1400  
1600  
1215  
1885  
1400  
1600  
1255  
1875  
1750  
2000  
845  
1750  
2000  
1215  
1910  
1750  
2000  
1255  
1920  
Max  
Furnace (gas ht.) airflow---Low Stage  
Furnace (gas ht.) airflow---High Stage  
1385  
1300  
Size (in.)  
(mm)  
11x10  
279x254  
11x10  
279x254  
11x10  
279x254  
11x10  
279x254  
11x10  
279x254  
11x10  
279x254  
Motor HP (RPM)  
3/4  
3/4  
3/4  
1
1
1
FURNACE SECTION*  
Burner Orifice No. (Qty...Drill Size)  
Natural Gas (Factory Installed)  
Propane Gas  
3...38  
3...53  
3...33  
3...51  
3...31  
3...49  
3...38  
3...53  
3...33  
3...51  
3...31  
3...49  
HIGH---PRESSURE SWITCH (psig)  
C u t --- o u t  
Reset (Auto)  
670 ± 10  
470 ± 25  
HIGH---PRESSURE SWITCH 2 (psig)  
(Compressor Solenoid)  
C u t --- o u t  
565 ± 15  
455 ± 15  
Reset (Auto)  
L O S S --- O F --- C H A R G E /  
LOW---PRESSURE SWITCH  
(Liquid Line) (psig)  
C u t --- o u t  
23 ± 5  
55 ± 5  
Reset (auto)  
RETURN---AIR FILTERS Throwaway† (in.)  
(mm)  
24x36x1  
610x914x25  
*Based on altitude of 0 to 2000 ft (0 to 610 m).  
{Recommended filter sizes for field---installed air filter grilles mounted on the wall or ceiling of the conditioned structure. Required filter sizes shown are based on  
the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 ft/minute for throwaway  
type or 450 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.  
8
CAUTION - NOTICE TO RIGGERS  
PRUDENCE - AVIS AUX MANIPULATEUR  
ACCESS PANELS MUST BE IN PLACE WHEN RIGGING.  
PANNEAUX D'ACCES DOIT ÊTRE EN PLACE POUR MANIPULATION.  
Use top skid as spreader bar. / Utiliser la palette du haut comme barre de répartition  
DUCTS  
MINIMUM HEIGHT: 36" (914.4 mm)  
HAUTEUR MINIMUM  
BANDE SCELLANT DOIT ÊTRE  
EN PLACE AVANT DE PLACER  
L'UNITÉ SUR LA BASE DE TOIT  
SEAL STRIP MUST BE IN  
PLACE BEFORE PLACING  
UNIT ON ROOF CURB  
UNIT HEIGHT  
HAUTEUR D'UNITÉ  
DETAIL A  
VOIR DÉTAIL A  
SEE DETAIL A  
VOIR DÉTAIL A  
50CY502286 2.0  
A09079  
RIGGING WEIGHT  
CABINET  
MODEL  
lb  
kg  
Small  
Small  
577D--- ---A24  
577D--- ---A30  
426  
433  
193  
196  
577D--- ---A36  
577D--- ---A42  
577D--- ---A48  
577D--- ---A60  
522  
544  
558  
609  
237  
247  
253  
276  
Large  
NOTE: See dimensional drawing for corner weight distribution.  
Fig. 7 -- Suggested Rigging  
Rigging/Lifting of Unit (See Fig. 7)  
Select and Install Ductwork  
The design and installation of the duct system must be in  
accordance with the standards of the NFPA for installation of  
non--residence type air conditioning and ventilating systems,  
NFPA 90A or residence type, NFPA 90B and/or local codes and  
ordinances.  
Select and size ductwork, supply--air registers, and return air grilles  
according to ASHRAE (American Society of Heating,  
Refrigeration, and Air Conditioning Engineers) recommendations.  
!
WARNING  
UNIT FALLING HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Large base units must be secured to common curb before  
allowing full weight of unit to rest on curb. Install screws  
through curb into unit base rails while rigging crane is still  
supporting unit.  
The unit has duct flanges on the supply-- and return--air openings  
on the side of the unit.  
Lifting holes are provided in base rails as shown in Fig. 5 and 6.  
!
WARNING  
1. Leave top shipping skid on the unit for use as a spreader bar  
to prevent the rigging straps from damaging the unit. If the  
skid is not available, use a spreader bar of sufficient length  
to protect the unit from damage.  
2. Attach shackles, clevis pins, and straps to the base rails of  
the unit. Be sure materials are rated to hold the weight of the  
unit (See Fig. 7).  
3. Attach a clevis of sufficient strength in the middle of the  
straps. Adjust the clevis location to ensure unit is lifted level  
with the ground.  
PERSONAL INJURY HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
For vertical supply and return units, tools or parts could  
drop into ductwork, therefore, install a 90 degree turn in the  
return ductwork between the unit and the conditioned space.  
If a 90 degree elbow cannot be installed, then a grille of  
sufficient strength and density should be installed to prevent  
objects from falling into the conditioned space.  
After the unit is placed on the roof curb or mounting pad, remove  
the top skid.  
When designing and installing ductwork, consider the following:  
1. All units should have field--supplied filters or accessory  
filter rack installed in the return--air side of the unit.  
Recommended sizes for filters are shown in Table 1.  
9
2. Avoid abrupt duct size increases and reductions. Abrupt  
change in duct size adversely affects air performance.  
IMPORTANT: Use flexible connectors between ductwork and  
unit to prevent transmission of vibration. Use suitable gaskets to  
ensure weather tight and airtight seal. When electric heat is  
installed, use fireproof canvas (or similar heat resistant material)  
connector between ductwork and unit discharge connection. If  
flexible duct is used, insert a sheet metal sleeve inside duct. Heat  
resistant duct connector (or sheet metal sleeve) must extend 24--in.  
(610 mm) from electric heater element.  
3. Size ductwork for max possible air flow (See Table 1).  
4. Seal, insulate, and weatherproof all external ductwork. Seal,  
insulate and cover with a vapor barrier all ductwork passing  
through conditioned spaces. Follow latest Sheet Metal and  
Air Conditioning Contractors National Association  
(SMACNA) and Air Conditioning Contractors Association  
(ACCA) minimum installation standards for residential  
heating and air conditioning systems.  
Horizontal Duct Covers  
A09076  
5. Secure all ducts to building structure. Flash, weatherproof,  
and vibration--isolate duct openings in wall or roof  
according to good construction practices.  
6. Read unit rating plate for any required clearances around  
ductwork.  
Basepan  
Downflow  
(Vertical)  
Supply  
Basepan  
Downflow  
(Vertical)  
Return  
Knockout  
Configuring Units for Downflow (Vertical) Discharge  
Knockout  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
A09077  
Failure to follow this warning could result in personal  
injury or death.  
Fig. 8 -- Supply and Return Duct Opening  
2. Select and size ductwork, supply--air registers, and  
return--air grilles according to American Society of Heating,  
Refrigeration and Air Conditioning Engineers (ASHRAE)  
recommendations.  
Before installing or servicing system, always turn off main  
power to system and install lockout tag. There may be  
more than one disconnect switch.  
3. Use flexible transition between rigid ductwork and unit to  
prevent transmission of vibration. The transition may be  
screwed or bolted to duct flanges. Use suitable gaskets to  
ensure weather--tight and airtight seal.  
4. All units must have field--supplied filters or accessory filter  
rack installed in the return--air side of the unit.  
Recommended sizes for filters are shown in Table 1.  
1. Open all electrical disconnects before starting any service  
work.  
2. Remove horizontal (metal) duct covers to access vertical  
(downflow) discharge duct knockouts in unit basepan. (See  
Fig. 8.)  
!
CAUTION  
5. Size all ductwork for maximum required airflow (either  
heating or cooling) for unit being installed. Avoid abrupt  
duct size increases or decreases or performance may be  
affected.  
PROPERTY DAMAGE HAZARD  
Failure to follow this caution may result in property damage.  
6. Adequately insulate and weatherproof all ductwork located  
outdoors. Insulate ducts passing through unconditioned  
space, and use vapor barrier in accordance with latest issue  
of Sheet Metal and Air Conditioning Contractors National  
Association (SMACNA) and Air Conditioning Contractors  
of America (ACCA) minimum installation standards for  
heating and air conditioning systems. Secure all ducts to  
building structure.  
Collect ALL screws that were removed. Do not leave screws  
on rooftop as permanent damage to the roof may occur.  
To remove downflow return and supply knockout covers, break  
front and right side connecting tabs with a screwdriver and  
hammer. Push cover down to break rear and left side tabs.  
NOTE: These panels are held in place with tabs similar to an  
electrical knockout. Reinstall horizontal duct covers (see Fig. 8)  
shipped on unit from factory. Insure openings are air and  
watertight.  
7. Flash, weatherproof, and vibration isolate all openings in  
building structure in accordance with local codes and good  
building practices.  
The design and installation of the duct system must be in  
accordance with the standards of the NFPA for installation of  
nonresidence--type air conditioning and ventilating systems, NFPA  
90A or residence--type, NFPA 90B; and/or local codes and  
ordinances.  
Provide for Condensate Disposal  
NOTE: Ensure that condensate--water disposal methods comply  
with local codes, restrictions, and practices.  
The units dispose of condensate through a 3/4 --in. NPT female  
fitting that exits on the compressor end of the unit. Condensate  
water can be drained directly onto the roof in rooftop installations  
(where permitted) or onto a gravel apron in ground level  
installations. Install a field--supplied condensate trap at end of  
condensate connection to ensure proper drainage. Make sure that  
Adhere to the following criteria when selecting, sizing, and  
installing the duct system:  
1. Units are shipped for horizontal duct installation (by  
removing duct covers).  
10  
the outlet of the trap is at least 1 in. (25 mm) lower than the  
drain--pan condensate connection to prevent the pan from  
overflowing. Prime the trap with water. When using a gravel apron,  
make sure it slopes away from the unit.  
NSCNGPIC in Canada. Do not use cast--iron pipe. It is  
recommended that a black iron pipe is used. Check the local utility  
for recommendations concerning existing lines. Size gas supply  
piping for 0.5 IN. W.C. maximum pressure drop. Never use pipe  
smaller than the 1/2--in. FPT gas inlet on the unit gas valve.  
For natural gas applications, the gas pressure at unit gas connection  
must not be less than 4.0 IN. W.C. or greater than 13 IN. W.C.  
while the unit is operating. For propane applications, refer to  
propane conversion kit instructions.  
A 1/8--in. (3.2 mm) NPT plugged tapping, accessible for test gauge  
connection, must be installed immediately upstream of the gas  
supply connection to the gas valve and downstream of manual  
equipment shutoff valve.  
If the installation requires draining the condensate water away from  
the unit, install a field--supplied 2--in. (51 mm) trap at the  
condensate connection to ensure proper drainage. Condensate trap  
is available as an accessory or is field--supplied. Make sure that the  
outlet of the trap is at least 1 in. (25 mm) lower than the unit  
drain--pan condensate connection to prevent the pan from  
overflowing. Connect  
a
drain tube using  
a
minimum of  
field--supplied 3/4 --in. PVC or field--supplied 3/4 --in. copper pipe  
at outlet end of the 2 --in. (51 mm) trap (See Fig. 9). Do not  
undersize the tube. Pitch the drain tube downward at a slope of at  
least 1 in. for every 10 ft. (3 m) of horizontal run. Be sure to check  
the drain trough for leaks. Prime the trap at the beginning of the  
cooling season start--up.  
When installing the gas supply line, observe local codes pertaining  
to gas pipe installations. Refer to the NFPA 54/ANSI Z223.1--2009  
(in Canada, CAN/CSA B149.1).  
NOTE: In the state of Massachusetts:  
Install Flue Hood  
1. Gas supply connections MUST be performed by a licensed  
plumber or gas fitter.  
!
WARNING  
2. When flexible connectors are used, the maximum length  
shall not exceed 36 in. (915 mm).  
CARBON MONOXIDE POISONING HAZARD  
3. When lever handle type manual equipment shutoff valves  
are used, they shall be T--handle valves.  
Failure to follow this warning could result in personal  
injury or death.  
4. The use of copper tubing for gas piping is NOT approved  
by the state of Massachusetts.  
In the absence of local building codes, adhere to the following  
pertinent recommendations:  
The venting system is designed to ensure proper venting.  
The flue hood assembly must be installed as indicated in  
this section of the unit installation instructions.  
Install the flue hood as follows:  
1. Avoid low spots in long runs of pipe. Grade all pipe 1/4 in.  
(6.35 mm) for every 15 ft (4.6 m) of length to prevent traps.  
Grade all horizontal runs downward to risers. Use risers to  
connect to heating section and to meter.  
2. Protect all segments of piping system against physical and  
thermal damage. Support all piping with appropriate straps,  
hangers, etc. Use a minimum of one hanger every 6 ft. (1.8  
m). For pipe sizes larger than 1/2 in., follow  
recommendations of national codes.  
3. Apply joint compound (pipe dope) sparingly and only to  
male threads of joint when making pipe connections. Use  
only pipe dope that is resistant to action of liquefied  
petroleum gases as specified by local and/or national codes.  
Never use Teflon tape.  
4. Install sediment trap in riser leading to heating section (See  
Fig. 10). This drip leg functions as a trap for dirt and  
condensate.  
1. This installation must conform with local building codes  
and with the National Fuel Gas Code (NFGC), NFPA  
54/ANSI Z223.1 (in Canada, CAN/CSA B149.1, and  
B149.2) or latest revision. Refer to provincial and local  
plumbing or wastewater codes and other applicable local  
codes.  
2. Remove flue hood from shipping location (inside the return  
section of the blower compartment--See Fig. 8). Remove the  
return duct cover to locate the flue hood. Remove two  
screws on flue panel. Place flue hood assembly over flue  
panel. Orient screw holes in flue hood with holes in the flue  
panel.  
3. Secure flue hood to flue panel by inserting a single screw on  
the top and the bottom of the hood.  
TRAP  
OUTLET  
5. Install an accessible, external, manual main shutoff valve in  
gas supply pipe within 6 ft (1.8 m) of heating section.  
1-in. (25 mm) min.  
6. Install ground--joint union close to heating section between  
unit manual shutoff and external manual main shut off  
valve.  
2-in. (51 mm) min.  
7. Pressure test all gas piping in accordance with local and  
national plumbing and gas codes before connecting piping  
to unit.  
A09052  
Fig. 9 -- Condensate Trap  
NOTE: Pressure test the gas supply system after the gas supply  
piping is connected to the gas valve. The supply piping must be  
disconnected from the gas valve during the testing of the piping  
systems when test pressure is in excess of 0.5 psig. Pressure test the  
gas supply piping system at pressures equal to or less than 0.5 psig.  
The unit heating section must be isolated from the gas piping  
system by closing the external main manual shutoff valve and  
slightly opening the ground--joint union.  
Install Gas Piping  
The gas supply pipe enters the unit through the access hole  
provided. The gas connection to the unit is made to the 1/2--in.  
FPT gas inlet on the gas valve.  
Install a gas supply line that runs to the heating section. Refer to  
Table 2 and the current edition of NFGC in the U.S. and the current  
11  
Install Electrical Connections  
IN  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
The unit cabinet must have an uninterrupted, unbroken  
electrical ground. This ground may consist of an electrical  
wire connected to the unit ground screw in the control  
compartment, or conduit approved for electrical ground  
when installed in accordance with NEC, NFPA 70 National  
Fire Protection Association (latest edition) (in Canada,  
Canadian Electrical Code CSA C22.1) and local electrical  
codes.  
TEE  
OUT  
NIPPLE  
CAP  
HIGH--VOLTAGE CONNECTIONS  
The unit must have  
a
separate electrical service with  
a
field--supplied, waterproof disconnect switch mounted at, or within  
sight from, the unit. Refer to the unit rating plate, NEC and local  
codes for maximum fuse/circuit breaker size and minimum circuit  
amps (ampacity) for wire sizing.  
C99020  
Fig. 10 -- Sediment Trap  
The field--supplied disconnect may be mounted on the unit over  
the high--voltage inlet hole (See Fig. 5 and 6).  
!
WARNING  
NOTE:  
Field supplied disconnect switch box should be  
FIRE OR EXPLOSION HAZARD  
positioned so that it does not cover up any of the unit gas  
combustion supply air louvers.  
Failure to follow this warning could result in fire, explosion,  
personal injury, death and/or property damage.  
Operation of unit on improper line voltage constitutes abuse and  
may cause unit damage that could affect warranty.  
S Connect gas pipe to unit using a backup wrench to avoid  
damaging gas controls.  
S Never purge a gas line into a combustion chamber. Never  
test for gas leaks with an open flame. Use a commercially  
available soap solution made specifically for the detection  
of leaks to check all connections.  
!
CAUTION  
UNIT COMPONENT DAMAGE HAZARD  
Failure to follow this caution may result in damage to the  
unit being installed.  
S Use proper length of pipe to avoid stress on gas control  
manifold.  
1. Make all electrical connections in accordance with NEC  
NFPA 70 (latest edition) and local electrical codes  
governing such wiring. In Canada, all electrical  
connections must be in accordance with CSA standard  
C22.1 Canadian Electrical Code Part 1 and applicable  
local codes. Refer to unit wiring diagram.  
S If a flexible connector is required or allowed by authority  
having jurisdiction, black iron pipe shall be installed at  
furnace gas valve and extend a minimum of 2 in. (51 mm)  
outside furnace casing.  
S If codes allow a flexible connector, always use a new  
connector. Do not use a connector which has previously  
serviced another gas appliance.  
2. Use only copper conductor for connections between  
field--supplied electrical disconnect switch and unit. DO  
NOT USE ALUMINUM WIRE.  
3. Be sure that high--voltage power to unit is within  
operating voltage range indicated on unit rating plate.  
4. Insulate low--voltage wires for highest voltage contained  
within conduit when low--voltage control wires are in  
same conduit as high--voltage wires.  
8. Check for gas leaks at the field--installed and  
factory--installed gas lines after all piping connections have  
been completed. Use a commercially available soap solution  
made specifically for the detection of leaks (or method  
specified by local codes and/or regulations).  
5. Do not damage internal components when drilling  
through any panel to mount electrical hardware, conduit,  
etc.  
ROUTING POWER LEADS INTO UNIT  
Use only copper wire between disconnect and unit. The high  
voltage leads should be in a conduit until they enter the duct panel;  
conduit termination at the duct panel must be watertight. Run the  
high--voltage leads through the power entry knockout on the  
power entry side panel. See Fig. 5 and 6 for location and size. For  
single--phase units, connect leads to the black and yellow wires.  
CONNECTING GROUND LEAD TO GROUND SCREW  
Connect the ground lead to the chassis using the ground screw on  
the control plate near the inducer switch (See Fig. 12).  
12  
Table 2 – Maximum Gas Flow Capacity*  
LENGTH OF PIPE ft (m)†  
70 80  
(21.3) (24.4)  
NOMINAL  
IRON PIPE  
SIZE (IN.)  
INTERNAL  
DIAMETER  
(IN.)  
10  
20  
30  
40  
50  
60  
(18.3)  
66  
138  
260  
530  
810  
90  
(27.4)  
53  
100  
125  
150  
175  
200  
(3.0)  
(6.1)  
(9.1)  
(12.1)  
(15.2)  
(30.5)  
(38.1)  
(45.7)  
(53.3)  
(61.0)  
1/2  
3/4  
1
1 --- 1 / 4  
1 --- 1 / 2  
.622  
.824  
1.049  
1.380  
1.610  
175  
360  
680  
1400  
2100  
120  
250  
465  
950  
1460  
97  
200  
375  
770  
1180  
82  
73  
61  
57  
50  
44  
93  
175  
360  
550  
40  
84  
160  
325  
500  
77  
145  
300  
460  
72  
135  
280  
430  
170  
320  
600  
990  
151  
285  
580  
900  
125  
240  
490  
750  
118  
220  
460  
690  
110  
205  
430  
650  
103  
195  
400  
620  
*Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5---IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2  
and NFPA 54/ANSI Z223.1.  
{ This length includes an ordinary number of fittings.  
ROUTING CONTROL POWER WIRES  
The OAT input is used to supply outdoor temperature data for  
system level functions and for temperature display on User  
Interface (UI). Using two wires of the field--supplied thermostat  
wire cable, wire the ends of the two black OAT pigtails. Wire the  
opposite ends of these two wires to the OAT provided with the UI.  
There is no polarity to be observed.  
For detailed instruction on the low voltage connections to the User  
Interface (UI), refer to the UI installation guide.  
Form a drip--loop with the control leads before routing them into  
the unit. Route the low voltage control leads through grommeted,  
low--voltage hole provided into unit (See Fig. 5 and 6). Connect  
user interface leads to unit control power leads as shown in Fig. 14.  
The unit transformer supplies 24--v power for complete system  
including accessory electrical heater. Transformer is factory wired  
for 230--v operation. If supply voltage is 208--v, rewire transformer  
primary as described in Special Procedures for 208--v Operation  
section.  
The furnace board is fused by a board--mounted automotive fuse  
placed in series with transformer SEC1 and R circuit. The C circuit  
of transformer circuit is referenced to chassis ground through a  
printed circuit run at SEC2 and gas valve grounding wire. Check to  
be sure control board is mounted securely using both  
factory--installed screws.  
NOTE: Mis--wiring OAT inputs will not cause damage to either  
Evolution control or thermistor. If the thermistor is wired  
incorrectly, no reading will appear at UI. Re--wire thermistor  
correctly for normal operation.  
B. Humidifier Connections  
The furnace control board terminal marked HUM is provided for  
low voltage (24--vac) control of a humidifier. No humidistat is  
required as UI monitors indoor humidity.  
When commanded to operate humidifier, the unit control will  
energize the HUM output to turn humidifier on and de--energize  
HUM output to turn humidifier off. Wire HUM and COM  
terminals directly to humidifier as shown in Fig. 14.  
ACCESSORY INSTALLATION  
C. Electronic Air Cleaner  
A. Outdoor Air Temperature Sensor (OAT)  
Electronic Air Cleaner terminals are provided on the Evolution  
Control Board (EAC--1 and EAC--2). While these terminals can be  
used to power a 230V EAC, it is recommended that any EAC be  
installed per the EAC installation instructions and connected  
separately to a standard 115V or 230V outlet with an airflow  
sensor to control operation of the EAC.  
!
CAUTION  
EQUIPMENT OPERATION HAZARD  
The installation of an outdoor air temperature sensor (OAT)  
using the Evolution control board OAT terminals is  
required. Many Evolution features (auto humidity control,  
comfort rollback, etc.) will be lost if the OAT is not  
connected.  
SPECIAL PROCEDURES FOR 208--V OPERATION  
Be sure unit disconnect switch is open.  
Disconnect the black primary lead from the transformer. See unit  
wiring label (See Fig. 16 and 17).  
For detailed mounting instructions for the OAT sensor,  
please refer installation instructions shipped with the OAT.  
Connect the black primary lead to the transformer terminal labeled  
208--v.  
13  
A09075  
Fig. 11 -- Typical Installation  
GROUND SCREW  
(IN SPLICE BOX)  
GROUND  
LEAD  
BLK  
YEL  
SINGLE-PHASE  
CONNECTIONS  
TO DISCONNECT  
PER NEC  
L1  
L2  
NOTE: Use copper wire only.  
LEGEND  
NEC – National Electrical Code  
Field Wiring  
Splice Connections  
A06299  
Fig. 12 -- Line Power Connections  
14  
HP/AC  
BOARD  
FURNACE BOARD  
A09108  
Fig. 13 -- Control Plate  
A06357  
Fig. 14 -- Control Voltage Wiring Connections  
15  
joint union be loosened, and the supply line be allowed to purge  
until the odor of gas is detected. Never purge gas lines into a  
combustion chamber. Immediately upon detection of gas odor,  
retighten the union. Allow 5 minutes to elapse, then light unit.  
PRE--START--UP  
!
WARNING  
b. Make sure that condenser--fan blade is correctly  
positioned in fan orifice. Top 1/3 of condenser fan blade  
should be within fan orifice venturi.  
FIRE, EXPLOSION, ELECTRICAL SHOCK AND  
ENVIRONMENTAL HAZARD  
Failure to follow this warning could result in personal  
injury or death and/or property damage.  
c. Ensure fan hub is positioned correctly with respect to  
motor housing (See Fig. 27).  
1. Follow recognized safety practices and wear protective  
goggles when checking or servicing refrigerant system.  
2. Do not operate compressor or provide any electric power  
to unit unless compressor terminal cover is in place and  
secured.  
3. Do not remove compressor terminal cover until all  
electrical sources are disconnected and tagged.  
4. Relieve and recover all refrigerant from system before  
touching or disturbing anything inside terminal box if  
refrigerant leak is suspected around compressor  
terminals.  
d. Make sure that air filter(s) is in place.  
e. Make sure that condensate drain trap is filled with water  
to ensure proper drainage.  
f. Make sure that all tools and miscellaneous loose parts  
have been removed.  
5. Compressors are internally spring mounted. Do not loosen  
or remove compressor holddown bolts.  
6. Each unit system has two Schrader--type ports, one  
low--side Schrader fitting located on the suction line, and  
one high--side Schrader fitting located on the compressor  
discharge line. Be sure that caps on the ports are tight.  
5. Never attempt to repair soldered connection while  
refrigerant system is under pressure.  
START--UP  
6. Do not use torch to remove any component. System  
contains oil and refrigerant under pressure.  
Unit Start--Up and Troubleshooting  
NOTE: Always check high-- and low--voltage supply to the unit  
components. Check the integrity of the plug receptacle connections  
and unit wiring harness prior to assuming a component failure.  
7. To remove a component, wear protective goggles and  
proceed as follows:  
a. Shut off gas supply to unit.  
A. LED Description  
b. Shut off electrical power to unit and install  
lockout tag.  
LEDs built into Evolution control boards provide installer or  
service person information concerning operation and/or fault  
condition of the unit controls and ECM motor. This information is  
also available at the system UI in text with basic troubleshooting  
instructions. Careful use of information displayed will reduce the  
need for extensive manual troubleshooting.  
c. Relieve and reclaim all refrigerant from system  
using both high-- and low--pressure ports.  
d. Cut component connecting tubing with tubing  
cutter and remove component from unit.  
Both the furnace and heat pump (HP)/air conditioner (AC) boards  
have an amber LED and a green LED. On the HP/AC board, these  
are located near the System Communications connector (ABCD)  
(lower right corner of the HP/AC board as installed in the unit).  
On the furnace board, these are located at the upper right side,  
adjacent to the fuse, above the terminal block. The amber LED is  
the System Status LED, labeled STATUS. The green LED, labeled  
COMM, is used as an indicator of system communications status  
(See Fig. 15 and 18).  
e. Carefully unsweat remaining tubing stubs when  
necessary. Oil can ignite when exposed to flame.  
Use the Start--Up Checklist supplied at the end of this book and  
proceed as follows to inspect and prepare the unit for initial  
start--up:  
1. Remove all access panels. (See Fig. 24.)  
2. Read and follow instructions on all DANGER, WARNING,  
CAUTION, and INFORMATION labels attached to, or  
shipped with unit.  
Status Codes will be displayed on the STATUS LED using the  
following protocol:  
1. The number of short flashes indicates first digit of code.  
2. The number of long flashes indicates second digit of code.  
3. A short flash is 0.25 seconds on. A long flash is 1 second  
on.  
3. Make the following inspections:  
a. Inspect for shipping and handling damages, such as  
broken lines, loose parts, disconnected wires, etc.  
b. Inspect for oil at all refrigerant tubing connections and  
on unit base. Detecting oil generally indicates a  
refrigerant leak. Leak test all refrigerant tubing  
connections using electronic leak detector, or  
4. The time between flashes is 0.25 seconds.  
5. The time between last short flash and first long flash is 1  
second.  
liquid--soap solution. If a refrigerant leak is detected, see  
following Check for Refrigerant Leaks section.  
6. The LEDs will be off for 2.5 seconds before repeating code.  
7. If multiple status codes are active concurrently, the highest  
priority status code is displayed.  
c. Inspect all field-- and factory--wiring connections. Be  
sure that connections are completed and tight.  
B. Control  
Start--Up  
and  
System Communications  
d. Ensure wires do not touch refrigerant tubing or sharp  
sheet metal edges.  
Troubleshooting  
On power up, green COMM LEDs will be turned off until  
successful system communications are established (this should  
happen within 10 seconds). Once communications with UI are  
successful, both COMM LEDs will be lit and held on. At the same  
time, amber STATUS LEDs will be lit and held continuously on  
until a request for operating mode is received. The STATUS LED  
will be on any time unit is in idle mode.  
e. Inspect coil fins. If damaged during shipping and  
handling, carefully straighten fins with a fin comb.  
4. Verify the following conditions:  
a. Make sure gas line is free of air. Before lighting the unit  
for the first time, perform the following tasks with the  
gas valve in the OFF position.  
NOTE: If the gas supply pipe was not purged before connecting  
the unit, it will be full of air. It is recommended that the ground  
If, at any time, communications are not successful for a period  
exceeding 2 minutes, the Evolution control will only allow  
16  
emergency heating or cooling operation using  
a
common  
operate electric heaters while a fault condition exists. The control  
communicates with the motor at least once every five seconds,  
even when the motor is idle. If, during operation, the control does  
not communicate with the motor for more than 25 seconds, the  
motor will shut itself down and wait for communications to be  
reestablished.  
thermostat and the terminal strip connections on the two control  
boards (See Non--Communicating Emergency Cooling/Heating  
Mode) and will display Status Code 16, System Communication  
Fault, on amber STATUS LED. No further troubleshooting  
information will be available at UI until communications are  
re--established.  
D. Furnace Control Troubleshooting  
If either COMM LED does not light within proper time period and  
status codes are not displayed;  
Furnace control faults indicated by flashing codes on the amber  
system STATUS LED can be resolved using troubleshooting  
information provided below. Codes are listed in order of their  
priority, highest to lowest. Though multiple faults can exist at any  
time, only the highest priority code will be displayed on STATUS  
LED. Clearing the indicated fault when multiple faults exist will  
cause the next highest priority Status Code to be flashed. All  
existing faults, as well as a fault history, can be viewed at UI.  
1. Check system transformer high-- and low--voltage to be sure  
the system is powered.  
2. Check ABCD connection on both boards.  
3. Check fuse on furnace board to be sure it is not blown. If  
fuse is open, check system wiring before replacing it to be  
sure a short does not cause a failure of replacement fuse.  
STATUS CODE CONTINUOUS OFF  
Check for 230 VAC at L1 and L2, and 24 VAC at SEC--1 and  
SEC--2.  
STATUS CODE CONTINUOUS ON  
Control has 24 VAC power.  
If COMM LED does not light within proper time period and status  
code is displayed:  
1. Check system wiring to be sure UI is powered and  
connections are made A to A, B to B, etc. and wiring is not  
shorted. Miswiring or shorting of the ABCD  
communications wiring will not allow successful  
communications.  
STATUS CODE 11 -- NO PREVIOUS CODE  
Stored status codes are erased automatically after 72 hours.  
NOTE: Shorting or miswiring low--voltage system wiring will  
not cause damage to unit control or UI but may cause low voltage  
fuse to open.  
STATUS CODE 12 -- BLOWER ON AFTER POWER UP  
(230 VAC or 24 VAC) Blower runs for 90 seconds if unit is  
powered up during a call for heat (R--W/W1 closed) or (R--W/W1  
opens) during blower on--delay period.  
C. Indoor Fan Motor Troubleshooting  
STATUS CODE 13 -- LIMIT CIRCUIT LOCKOUT  
Lockout occurs if a limit or flame rollout switch is open longer  
than 3 minutes or 10 successive limit trips occurred during high  
heat. Control will auto reset after three hours. Refer to status code  
33.  
The indoor fan is driven by an ECM motor consisting of two parts:  
the control module and the motor winding section. Do not assume  
motor or module is defective if it will not start. Use the  
designed--in LED information aids and follow troubleshooting  
steps described below before replacing motor control module or  
entire motor. Motor control module is available as a replacement  
part.  
STATUS CODE 14 -- IGNITION LOCKOUT  
Control will auto reset after three hours. Refer to status code 34.  
STATUS CODE 15 -- BLOWER MOTOR LOCKOUT  
Indicates the blower failed to reach 250 RPM or the blower failed  
to communicate within 30 seconds after being turned ON in two  
successive heating cycles. Control will auto reset after 3 hours.  
Refer to status code 41.  
VERIFY MOTOR WINDING SECTION  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
After disconnecting power from the ECM motor, wait at  
least 5 minutes before removing the control section. Internal  
capacitors require time to discharge.  
Before proceeding to replace a motor control module:  
1. Check motor winding section to be sure it is functional.  
2. Remove motor control module section and unplug winding  
plug. Motor shaft should turn freely, resistance between any  
two motor leads should be similar and resistance between  
any motor lead and unpainted motor end should exceed  
100,000 ohms.  
3. Failing any of these tests, entire ECM motor must be  
replaced.  
4. Passing all of the tests, motor control module alone can be  
replaced.  
MOTOR TURNS SLOWLY  
1. Low static pressure loading of blower while access panel is  
removed will cause blower to run slowly. Particularly at low  
airflow requests. This is normal, do not assume a fault  
exists.  
2. Recheck airflow and system static pressure using UI service  
screens with access panel in place.  
A06026  
NOTE: Blower motor faults will not cause a lockout of blower  
operation. The fan coil control will attempt to run the blower motor  
as long as UI maintains a demand for airflow. The control will not  
Fig. 15 -- Detail of Furnace Board  
17  
A10217C  
Fig. 16 -- Connection Wiring Schematic--577D----A Single Phase Gas Inputs 040, 060, 090 kBtu/hr  
18  
A10217L  
Fig. 16 Cont. -- Ladder Wiring Schematic--577D----A Single Phase Gas Inputs 040, 060, 090 kBtu/hr  
19  
A10219C  
Fig. 17 -- Connection Wiring Schematic--577D----A Single Phase Gas Inputs 115, 130 kBtu/hr  
20  
A10219L  
Fig. 17 Cont. -- Ladder Wiring Schematic--577D----A Single Phase Gas Inputs 115, 130 kBtu/hr  
21  
UTILITY RELAY  
*
LLS  
Liquid Line Solenoid  
UTILITY SIGNAL  
OPEN RELAY  
*
SUPPLIED BY UTILITY PROVIDER  
A05247  
Fig. 18 -- 2--Stage HP/AC Control Board  
STATUS CODE 21 -- GAS HEATING LOCKOUT  
Control will NOT auto reset. Check for mis--wired gas valve or  
defective control (valve relay).  
shuts off. Check for loose blower wheel, restricted vent, excessive  
wind, dirty filter or restricted duct system, defective switch or  
connections, or inadequate combustion air supply (flame roll--out  
switch open).  
STATUS CODE 22 -- ABNORMAL FLAME--PROVING  
SIGNAL  
STATUS CODE 34 -- IGNITION PROVING FAILURE  
Flame is proved while gas valve is de--energized. Inducer will run  
until fault is cleared. Check for leaky gas valve or stuck--open gas  
valve.  
Control will try three more times before lockout 14 occurs. If flame  
signal lost during blower on--delay period, blower will come on for  
the selected blower off--delay. Check for oxide buildup on flame  
sensor (clean with fine steel wool), proper flame sense microamps  
(.5 microamps D.C. min., 4.0--6.0 nominal), manual valve shutoff,  
low inlet gas pressure, control ground continuity, gas valve  
defective or turned off, flame sensor must not be grounded,  
inadequate flame carryover or rough ignition, or green/yellow wire  
must be connected to unit sheet metal.  
STATUS CODE 41 -- BLOWER MOTOR FAULT  
Indicates the blower failed to reach 250 RPM or the blower failed  
to communicate within the prescribed time limits. Thirty seconds  
after being turned ON or ten seconds during steady--state  
operation.  
STATUS CODE 42 -- INDUCER MOTOR FAULT  
Indicates inducer motor hasn’t started within a prescribed time  
limit. Check inducer motor and wiring.  
STATUS CODE 45 -- CONTROL CIRCUITRY LOCKOUT  
Auto reset after one hour lockout due to gas valve relay stuck open,  
flame sense circuit failure, or software check error. Reset power to  
clear lockout. Replace control if status code repeats.  
STATUS CODE 23 -- PRESSURE SWITCH DID NOT OPEN  
Check for obstructed pressure tubing or pressure switch stuck  
closed.  
STATUS CODE 24 -- SECONDARY VOLTAGE FUSE IS OPEN  
Check for short circuit in secondary voltage (24VAC) wiring.  
STATUS CODE 25 -- INVALID MODEL SELECTION OR  
SETUP ERROR  
Indicates either the model plug is missing or incorrect. If code  
flashes 4 times on power--up, control is defaulting to model  
selection stored in memory. Check for proper model plug number  
and resistance values per wiring diagram.  
STATUS CODE 31, 32 -- PRESSURE SWITCH OR RELAY DID  
NOT CLOSE OR REOPENED  
Control relay may be defective. If open longer than five minutes,  
inducer shuts off for 15 minutes before retry. If open during blower  
on--delay period, blower will come on for the selected blower  
off--delay. Check for excessive wind, restricted vent, defective  
inducer motor, defective pressure switch, lower inducer voltage  
(230VAC), inadequate combustion air supply, disconnected or  
obstructed pressure tubing, or low inlet gas pressure (if LGPS  
used).  
E. HP/AC Control Troubleshooting  
See Table  
4
for HP/AC control board status codes and  
troubleshooting information.  
STATUS CODE 33 -- LIMIT CIRCUIT FAULT  
STATUS CODE 53, OUTDOOR AIR TEMPERATURE  
SENSOR FAULT -- DETAILED DESCRIPTION  
If an OAT sensor is found at power--up, input is constantly checked  
to be within a valid temperature range. If sensor is found to be  
Indicates a limit or flame rollout switch is open. Blower will run  
for 4 minutes or until open switch remakes, whichever is longer. If  
open longer than 3 minutes, code changes to lockout 13. If open  
less than 3 minutes status code 33 continues to flash until blower  
22  
open or shorted at any time after initial validation, Status Code 53  
will be displayed at amber STATUS LED.  
Check for faults in wiring connecting sensor to OAT terminals.  
Using an Ohm meter, check resistance of thermistor for a short or  
open condition.  
NOTE: When two--stage unit is operating at low--stage, system  
vapor (suction) pressure will be higher than a standard single--stage  
system or high--stage operation.  
NOTE:  
Outdoor fan motor will continue to operate for one  
minute after compressor shuts off, when outdoor ambient is greater  
If thermistor is shorted or open, replace it to return the system to  
normal operation. If fault is in the wiring connections, correcting  
the fault will clear the code and return the system to normal  
operation.  
NOTE: If fault condition is an open thermistor or a wiring problem  
that appears to be an open thermistor and the power to the unit is  
cycled off, the fault code will be cleared on the next power--up but  
the fault will remain and system operation will not be as expected.  
This is because on power--up, the unit control cannot discern  
the difference between an open sensor or if a sensor is not  
installed.  
than or equal to 100°F (38°C).  
UTILITY INTERFACE WITH Evolution CONTROL  
The utility curtailment relay should be connected to factory  
supplied pigtails (PINK, connected to R, VIOLET connected to Y2  
on the control board) located in the low voltage splice box (See  
Fig. 16, 18 and 18). This input allows a power utility device to  
interrupt compressor operation during peak load periods. When the  
utility sends a signal to shut the system down, the UI will display  
“Curtailment Active”.  
COMPRESSOR OPERATION  
When the compressor is operating in low stage, the modulating  
ring is deactivated, allowing two internal bypass ports to close off  
33% of the scroll compression area so the system operates at part  
load capacity. The 24--volt solenoid coil is de--energized in  
low--stage operation.  
When the compressor is operating at high stage, the modulating  
ring is activated, sealing the bypass ports, which allows the  
compressor to operate at full load capacity. The 24--volt solenoid  
coil is energized in high stage operation.  
Sequence of Operation  
The 577D----A packaged unit is designed for installation with a  
communicating UI. This unit will not respond to commands  
provided by a common thermostat except under certain emergency  
situations described in Step 1—Start--Up and Troubleshooting.  
The UI uses temperature, humidity and other data supplied from  
indoor and outdoor system components to control heating or  
cooling system for optimum comfort. The unit will be commanded  
by UI to supply airflow. The unit will operate the indoor blower at  
requested airflow for most modes.  
CRANKCASE HEATER OPERATION (IF APPLICABLE)  
The crankcase heater is energized during off cycle below 65_F  
(18_C) outdoor air temperature.  
INDOOR AIRFLOW ADJUSTMENTS  
The nominal requested airflow for air conditioner operations will  
be 350 cfm per ton of nominal cooling capacity as defined by unit  
size. Actual airflow request will be adjusted from nominal using  
indoor and outdoor temperature and indoor humidity data to  
optimize the system operation for occupant comfort and system  
efficiency. Refer to UI literature for further system control details.  
OUTDOOR FAN MOTOR OPERATION  
The outdoor unit control energizes the outdoor fan any time the  
compressor is operating. The outdoor fan remains energized if a  
pressure switch or compressor overload should open. Outdoor fan  
motor will continue to operate for one minute after the compressor  
shuts off when the outdoor ambient is greater than or equal to  
100_F (38°C).  
!
CAUTION  
TIME DELAYS--AIR CONDITIONER OPERATIONS  
The unit time delays include:  
S Five minute time delay to start cooling operation when there is a  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in unit damage.  
call from the thermostat or user interface. To bypass this feature,  
momentarily short and release Forced Defrost pins.  
S Five minute compressor recycle delay on return from a  
brown--out condition.  
For cooling operation, the recommended airflow is 350 to  
450 cfm for each 12,000 Btuh of rated cooling capacity. For  
heating operation, the airflow must produce a temperature  
rise that falls within the range stamped on the unit rating  
plate.  
S Two minute time delay to return to standby operation from last  
valid communication (with Evolution only).  
For gas heat operations, Table 3 shows the temperature rise in each  
gas heating mode. Refer to these tables to determine the desired  
heating airflow for the system being installed.  
NOTE: Be sure that all supply--and return--air grilles are open,  
free from obstructions, and adjusted properly. Airflow can be  
changed using the UI. See UI installation instructions for more  
detail.  
S One minute time delay of outdoor fan at termination of cooling  
mode when outdoor ambient is greater than or equal to 100_F  
(38°C).  
S There is no time delay between air conditioner staging from low  
to high and from high to low capacity; the compressor will change  
from low to high and from high to low capacity as demand  
dictates.  
NOTE: Once the compressor has started and then has stopped, it  
should not be started again until 4 minutes have elapsed. The  
cooling cycle remains “on” until the room temperature drops to  
point that is slightly below the cooling control setting of the UI.  
AIR CONDITIONER SEQUENCE OF OPERATION  
COOLING OPERATION  
With a call for first stage cooling, the outdoor fan, and low stage  
compressor are energized. If low--stage cannot satisfy cooling  
demand, high--stage cooling is energized by the UI. After second  
stage is satisfied, the unit returns to low--stage operation until first  
stage is satisfied or until second stage is required again. When both  
first stage and second stage cooling are satisfied, the compressor  
will shut off.  
23  
Table 3 – Air Delivery and Temperature Rise at Rated Heating Input  
o
o
o
Rated Heating Input (Btu/hr)  
Heating Rise Range F ( C)  
Heating Rise Either Stage, °F ( C)  
Unit  
“Efficiency” “Comfort”  
High Stage  
Low Stage  
High Stage  
Low Stage  
High Stage  
Low Stage  
High Stage  
Low Stage  
577DNWA24040  
577DNWA30040  
20 --- 50  
(11 --- 28)  
15---45  
(8 --- 25)  
35  
(19)  
30  
(17)  
40  
(22)  
35  
(19)  
40,000  
26,000  
577DNWA30060  
577DNWA36060  
577DNWA42060  
577DNWA36090  
577DNWA42090  
577DNWA48090  
577DNWA60090  
25 --- 55  
(14 --- 31)  
25 --- 55  
(14 --- 31)  
40  
50  
60,000  
90,000  
39,000  
58,500  
(22)  
(28)  
35 --- 65  
(19 --- 36)  
35 --- 65  
(19 --- 36)  
50  
(28)  
55  
(31)  
577DNWA48115  
577DNWA60115  
30 --- 60  
(17 --- 33)  
30 --- 60  
(17 --- 33)  
45  
50  
115,000  
130,000  
75,000  
84,500  
(25)  
(28)  
577DNWA48130  
577DNWA60130  
35 --- 65  
(19 --- 36)  
35 --- 65  
(19 --- 36)  
50  
(28)  
55  
(31)  
Airflow delivery values for external static pressure values of up to 1 IN. W.C.  
Table 4 – Heat Pump/Air Conditioner Board Status Codes  
AMBER LED  
FLASH  
CODE  
On solid, no  
flash  
Rapid, con-  
tinuous  
flashing  
OPERATION  
Standby – no call for unit operation  
Emergency Mode  
FAULT  
POSSIBLE CAUSE AND ACTION  
None  
Normal operation.  
Unit being controlled by standard thermostat inputs instead of Evolution  
Control. Only high stage operation is available. This operating mode  
should be used in emergency situations only.  
Standard Thermo-  
stat Control  
Low Stage Cool/Heat Operation  
High Stage Cool/Heat Operation  
None  
None  
System Communica-  
tions Failure  
1, pause  
2, pause  
16  
Normal operation.  
Normal operation.  
Communication with UI lost. Check wiring to UI, indoor and outdoor units.  
Control does not detect a model plug or detects an invalid model plug. Unit  
will not operate without correct model plug.  
High---pressure switch trip. Check refrigerant charge, outdoor fan operation  
and coils for airflow restrictions.  
Invalid Model Plug  
25  
31  
High --- Pr essu r e  
Switch Open  
L ow --- Pr essu r e  
Switch Open  
Control Fault  
32  
45  
46  
Low---pressure switch trip. Check refrigerant charge and indoor air flow.  
Outdoor unit control board has failed. Control board needs to be replaced.  
Line voltage < 187v for at least 4 seconds. Compressor and fan operation  
not allowed until voltage>190v. Verify line voltage.  
Brown Out (230 v)  
There is no 230v at the contactor when indoor unit is powered and cooling/  
heating demand exists. Verify the disconnect is closed and 230v wiring is  
connected to the unit.  
No 230v at Unit  
47  
Outdoor Air Temp  
Sensor Fault  
Outdoor Coil Sensor  
Fault  
Thermistors Out of  
Range  
Outdoor air sensor not reading or out of range. Ohm out sensor and check  
wiring.  
53  
55  
56  
Coil sensor not reading or out of range. Ohm out sensor and check wiring.  
Improper relationship between coil sensor and outdoor air sensor. Ohm out  
sensors and check wiring.  
Compressor voltage sensed, then disappears while cooling or heating de-  
mand exists. Possible causes are internal compressor overload trip or start  
relay not releasing (if installed).  
Compressor voltage sensed, then disappears while cooling or heating de-  
mand exists. Possible causes are internal compressor overload trip or start  
relay not releasing (if installed).  
Low Stage Thermal  
Cutout  
71  
72  
High Stage Thermal  
Cutout  
Compressor voltage sensed when no demand for compressor operation  
exists. Contactor may be stuck closed or there is a wiring error.  
Compressor voltage not sensed when compressor should be starting. Con-  
tactor may be stuck open or there is a wiring error.  
Thermal cutout occurs in three consecutive low/ high stage cycles. Low  
stage locked out for 4 hours or until 24v power recycled.  
Thermal cutout occurs in three consecutive high/low stage cycles. High  
stage locked out for 4 hours or until 24v power recycled.  
Low---pressure switch trip has occurred during 3 consecutive cycles. Unit  
operation locked out for 4 hours or until 24v power recycled.  
High---pressure switch trip has occurred during 3 consecutive cycles. Unit  
operation locked out for 4 hours or until 24v power recycled.  
Contactor Shorted  
73  
74  
81  
82  
83  
84  
No 230V at Com-  
pressor  
Low Stage Thermal  
Lockout  
High Stage Thermal  
Lockout  
Low---Pressure Lock-  
out  
High --- Pr essu r e  
Lockout  
24  
EVOLUTION CONTROLLED LOW AMBIENT COOLING  
period begins. NOTE: The unit always lights on high  
speed inducer and low stage gas valve operation.  
NOTE: When this unit is operating below 55_F (13°C) outdoor  
temperature, provisions must be made for low ambient operation.  
This unit is capable of low ambient cooling down to 0_F (--18°C).  
ONLY when using the Evolution control. A low ambient kit is not  
required, and the outdoor fan motor does not need to be replaced  
for Evolution controlled low ambient operation. Low ambient  
cooling must be enabled in the UI set--up. Fan may not begin to  
cycle until about 40_F (4°C).OAT. Fan will cycle based on coil  
and outdoor air temperature. Evolution controlled low ambient  
mode operates as follows:  
3. Flame--Proving: When the burner flame is proved at the  
flame--proving sensor, the furnace control determines what  
heating stage to run based on feedback from the UI. If the  
UI is asking for low stage gas heat, the ignition control will  
change the inducer speed to low speed and keep the gas  
valve energized on low stage. If the UI is asking for high  
stage gas heat, the ignition control will maintain running the  
inducer on high speed and energize the gas valve’s high  
stage relay to increase gas flow.  
If the burner flame is not proved within 2 seconds, the control will  
close the gas valve and repeat the ignition sequence up to 3 more  
Trials--For--Ignition before going to Ignition--Lockout. Lockout  
will reset automatically after 3 hours, by momentarily interrupting  
230 VAC power, or by interrupting 24 VAC power at SEC1 or  
SEC2 to the furnace board.  
If flame is proved when there should be no flame present, control  
will lock out of Gas--Heating mode and operate the inducer motor  
until flame is no longer proved.  
S In high stage, fan is off when outdoor coil temp is <outdoor air  
temperature plus 3_F (1.7_C) or outdoor fan has been ON for 30  
minutes. (Fan is turned off to allow refrigerant system to  
stabilize.)  
S In low stage, fan is off when outdoor coil temp is <outdoor air  
temperature plus 1_F (.6_C) or outdoor fan has been ON for 30  
minutes. (Fan is turned off to allow refrigerant system to  
stabilize.)  
4. Blower--On Delay:  
If the burner flame is proven,  
S In high stage and low stage, fan is on when outdoor coil temp >  
outdoor air temperature plus 25_F (13.8_C) or outdoor coil temp  
> 80_F (27_C) or if outdoor fan has been OFF for 30 minutes.  
(Fan is turned on to allow refrigerant system to stabilize.)  
S Low--pressure switch is ignored for first 3 minutes during low  
ambient start up. After 3 minutes, if LPS trips, then outdoor fan  
motor is turned off for 10 minutes with the compressor running. If  
LPS closes within 10 minutes then cooling continues with the  
outdoor fan cycling per the coil temperature routine listed above  
for the remainder of the cooling cycle. If the LPS does not close  
within 10 minutes, then the normal LPS trip response (shut down  
cooling operation and generate LPS trip error) will occur.  
approximately 37 seconds after the gas valve is opened the  
Indoor Blower is turned on to the appropriate speed for the  
gas heating stage.  
Simultaneously, the humidifier terminal HUM and electronic air  
cleaner terminal EAC--1 are energized throughout the heating  
cycle.  
NOTE: EAC--2 terminal is common with L2 and will have  
115VAC--to--ground when unit is powered.  
5. Blower--Off Delay: When the call for gas heat is satisfied,  
the gas valve is de--energized, stopping the flow of gas to  
the burners, and de--energizing the HUM terminal. The  
inducer motor will remain on for a 4--second post--purge  
period. The indoor blower and air cleaner terminal EAC--1  
will remain energized for 90, 120, 150, or 180 seconds  
(depending on selection of blower--off delay selected in the  
UI). The factory--set default is 120--second blower--OFF  
delay.  
DEHUMIDIFICATION MODE  
This Evolution system can be used to dehumidify the living space.  
See UI Installation Instructions for more details.  
CHECK GAS INPUT (NATURAL GAS)  
SEQUENCE OF OPERATION--GAS HEAT  
NOTE: Evolution control must be grounded for proper operation  
or control will lock out.  
!
CAUTION  
NOTE: If a power interruption occurs during a call for heat, the  
control will start a 90--second blower only ON period two seconds  
after power is restored, if the UI is still calling for gas heating. The  
amber LED light will flash code 12 during the 90--second period,  
after which the LED will be ON continuously, as long as no faults  
are detected. After the 90--second period, the unit will respond to  
the UI normally.  
UNIT DAMAGE HAZARD  
Failure to follow this caution may result in component  
damage.  
Do not redrill an orifice. Improper drilling (burrs,  
out--of--round holes, etc.) can cause excessive burner noise  
and misdirection of burner flame. If orifice hole appears  
damaged or it is suspected to have been redrilled, check  
orifice hole with a numbered drill bit of correct size.  
GAS HEAT MODE AND ADJUSTMENTS  
When the UI calls for gas heat, the Evolution furnace board  
performs a self--check, verifies the pressure switch is open, and  
starts the inducer on high speed.  
1. Inducer Pre--purge Period: When the inducer motor comes  
up on high speed, the pressure switch closes, and the  
Evolution ignition control on the furnace board begins a 15  
second pre--purge period. If the pressure switch fails to  
remain closed, the inducer will remain running. After the  
pressure switch re--closes, the Evolution ignition control  
will begin a 15 second pre--purge period.  
!
WARNING  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
DO NOT bottom out gas valve regulator adjusting screws.  
This can result in unregulated manifold pressure and result  
in excess overfire and heat exchanger failures.  
2. Trial--For--Ignition Sequence: The spark igniter will spark  
for 3 seconds. The main gas valve relay contact closes to  
energize the gas valve on low stage. After 5 seconds, the  
igniter is de--energized and a 2--second flame--proving  
25  
b. When the gas supply being used has a different heating  
value or specific gravity, refer to national and local  
codes, or contact your distributor to determine the  
required orifice size.  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
2. Adjust manifold pressure to obtain low stage input rate (See  
Fig. 19).  
Failure to follow this warning could result in personal  
injury and/or death.  
a. Turn off gas supply to unit.  
b. Remove pipe plug on manifold (See Fig. 20 and  
connect manometer). Turn on gas supply to unit.  
If the manifold pressure and/or gas rate is not properly  
adjusted on HI and LO stages, excess carbon monoxide can  
be produced.  
c. Turn gas valve switch to ON.  
d. Set unit to run for 20 minutes in low--stage gas heat  
operation using the ”INSTALLER CHECKOUT” menu  
on the User Interface.  
!
WARNING  
FIRE AND UNIT DAMAGE HAZARD  
e. Remove regulator adjustment cap from low stage gas  
valve pressure regulator (See Fig. 19) and turn  
low--stage adjusting screw (3/16 or smaller flat--tipped  
screwdriver) counterclockwise (out) to decrease rate and  
clockwise (in) to increase input rate.  
Failure to follow this warning could result in personal  
injury or death and/or property damage.  
Unsafe operation of the unit may result if manifold pressure  
is outside of the ranges listed in Table 6.  
Gas input rates on rating plate are for installations at altitudes up to  
2000 ft (610 m). Input rate must be within ± 2% of rating plate  
input.  
REGULATOR COVER SCREW  
PLASTIC ADJUST SCREW  
ON/OFF SWITCH  
1. Determine the correct gas input rate.  
REGULATOR SPRING  
a. The rated gas inputs shown in Table 6 are for altitudes  
from sea level to 2000 ft (610 m) above sea level.  
These inputs are based on natural gas with a heating  
value of 1025 Btu/ft3 at .60 specific gravity.  
HIGH STAGE GAS  
PRESSURE REGULATOR  
ADJUSTMENT  
LOW STAGE  
GAS PRESSURE  
REGULATOR ADJUSTMENT  
INLET  
PRESSURE TAP  
IN THE U.S.A.:  
The input rating for altitudes above 2,000 ft (610 m) must be  
reduced by 4 percent for each 1,000 ft (305 m) above sea level.  
For installations below 2,000 ft, (610 m) refer to the unit rating  
plate.  
MANIFOLD  
PRESSURE TAP  
For installations above 2,000 ft, (610 m) multiply the input by on  
the rating plate by the derate multiplier in Table 5 for the correct  
input rate.  
A04167  
Fig. 19 -- Redundant Automatic Gas Control Valve  
NOTE: DO NOT set low stage manifold pressure less than 1.4  
IN. W.C. or more than 2.0 IN. W.C. for natural gas. If manifold  
pressure is outside this range, change main burner orifices.  
Table 5 – Altitude Derate Multiplier for U.S.A*.  
Derate Multiplier  
Altitude ft (m)  
Percent of Derate  
0
Factor{  
f. Re--install low stage regulator adjustment cap.  
g. Leave manometer connected.  
0 -2000  
(0 -610)  
1.00  
2001 -3000*  
(610 -914)  
8--12  
0.90  
0.86  
0.82  
0.78  
0.74  
0.70  
0.66  
0.62  
NOTE: If orifice hole appears damaged or it is suspected to have  
been re--drilled, check orifice hole with a numbered drill bit of the  
correct size. Never re--drill an orifice. A burr--free and squarely  
aligned orifice hole is essential for proper flame characteristics.  
3001 -4000  
(915 -1219)  
12--16  
16--20  
20--24  
24--28  
28--32  
32--36  
36--40  
4001 -5000  
(1220 -1524)  
3. Verify natural gas low stage input rate.  
5001 -6000  
(1524 -1829)  
a. Turn off all other gas appliances and pilots served by  
the gas meter.  
b. If unit is not running, set unit to run for 20 minutes in  
low--stage gas heat operation using the ”INSTALLER  
CHECKOUT” menu on the UI.  
6001 -7000  
(1829 -2134)  
7001 -8000  
(2134 -2438)  
8001 -9000  
(2139 -2743)  
c. Record number of seconds for gas meter to complete  
one revolution.  
9001 -10,000  
(2744 -3048)  
d. Divide number of seconds in step c. into 3600 (number  
of seconds in 1 hour).  
* In Canada see Canadian Altitude Adjustment.  
{Derate multiplier factors are based on midpoint altitude for altitude range.  
e. Multiply result of step d. by the number of cubic feet  
shown for one revolution of test dial to obtain cubic feet  
of gas flow per hour.  
IN CANADA:  
The input rating for altitudes from 2,000 (610 m) to 4,500 ft (1372  
m) above sea level must be derated 10 percent by an authorized  
Gas Conversion Station or Dealer.  
f. Multiply result of step f. by Btu heating value of the gas  
to obtain total measured input shown in Table 6.  
(Consult the local gas supplier if the heating value of  
gas is not known).  
EXAMPLE:  
90,000 Btuh Input Furnace Installed at 4300 ft (1372 m).  
Furnace Input Rate  
at Sea Level  
Altitude  
Derate Multiplier  
Factor  
Furnace Input Rate  
at Installation  
EXAMPLE: Assume a 90,000 high stage input unit is being  
installed. Assume that the size of the dial is 2 cubic ft., one  
revolution takes 129 sec., and the heating value of the gas is 1025  
X
=
3
90,000  
X
0.90  
=
81,000  
Btu/ft . Proceed as follows:  
26  
a. 129 sec. to complete one revolution  
b. 3600/129 = 27.9  
c. 27.9 x 2 = 55.8 ft of gas flow/hr.  
In this example, the nominal input rate for high stage is 90,000  
Btu/hr, so the high stage manifold pressure is correctly set.  
If the measured high stage rate is too low, increase the manifold  
pressure to increase rate. If the measured high stage rate is too  
high, decrease the manifold pressure to decrease rate.  
3
d. 55.8 x 1050 = 58,590 Btuh input.  
In this example, the nominal input rate for low stage is 58,500  
Btu/hr, so the low stage manifold pressure is correctly set.  
If the measured low stage rate is too low, increase the manifold  
pressure to increase rate. If the measured low stage rate is too high,  
decrease the manifold pressure to decrease rate.  
NOTE: Double--check that User Interface is running on high stage  
gas heat while clocking the low stage firing rate.  
7. Verify proper high stage gas heat temperature rise.  
a. Furnace must operate within rise range listed on rating  
plate.  
b. Make sure access panel is re--installed on the unit.  
NOTE: Double--check that UI is running on low stage gas heat  
while clocking the low stage firing rate.  
c. Measure supply and return temperatures as close to the  
unit as possible. Subtract the return temperature from  
the supply temperature to determine rise. Rise should  
fall within the range specified on the rating plate.  
4. Verify proper low stage gas heat temperature rise.  
a. Furnace must operate within rise range listed on rating  
plate.  
b. Select ”COMFORT” or ”EFFICIENCY” mode on UI.  
”COMFORT” mode will provide a warmer supply air  
temperature, while ”EFFICIENCY” will provide lower  
gas consumption.  
NOTE: If the temperature rise is outside the rating plate range,  
first check:  
a. Gas input for low and high stage gas heat operation.  
b. Derate for altitude, if applicable.  
c. Make sure access panel is re--installed on the unit.  
c. Return and supply ducts for excessive restrictions  
causing static pressures in excess of .5 IN. W.C.  
d. Measure supply and return temperatures as close to the  
unit as possible. Subtract the return temperature from  
the supply temperature to determine rise. Rise should  
fall within the range specified on the rating plate.  
d. Make sure model plug is installed.  
8. Final Check  
5. Adjust manifold pressure to obtain high stage input rate  
(See Fig. 19).  
a. Turn off gas to unit  
b. Remove manometer from pressure tap.  
c. Replace pipe plug on manifold (See Fig. 20).  
d. Turn on gas to unit.  
a. Set unit to run for 20 minutes in high--stage gas heat  
operation using the ”INSTALLER CHECKOUT” menu  
on the UI.  
e. Check for leaks.  
CHECK GAS INPUT (PROPANE GAS)  
b. Remove regulator adjustment cap from high stage gas  
valve pressure regulator (See Fig. 19) and turn  
high--stage adjusting screw (3/16 or smaller flat--tipped  
screwdriver) counterclockwise (out) to decrease rate and  
clockwise (in) to increase input rate.  
Refer to propane kit installation instructions for properly checking  
gas input.  
NOTE: For installations below 2,000 ft (610 m), refer to the unit  
rating plate for proper propane conversion kit. For installations  
above 2,000 ft (610 m), contact your distributor for proper propane  
conversion kit.  
NOTE: DO NOT set high stage manifold pressure less than 3.2  
IN. W.C. or more than 3.8 IN. W.C. for natural gas. If manifold  
pressure is outside this range, change main burner orifices.  
c. Re--install high stage regulator adjustment cap.  
d. Leave manometer connected.  
6. Verify natural gas high stage input rate.  
CHECK BURNER FLAME  
With control access panel removed (See Fig. 24), observe the unit  
heating operation. Watch the burner flames to see if they are light  
blue and soft in appearance, and that the flames are approximately  
the same for each burner. Propane will have blue flame (See Fig.  
21). Refer to the Maintenance section for information on burner  
removal.  
a. Turn off all other gas appliances and pilots served by  
the gas meter.  
b. If unit is not running, set unit to run for 20 minutes in  
high stage gas heat operation using the ”INSTALLER  
CHECKOUT” menu on the UI.  
c. Record number of seconds for gas meter to complete 1  
revolution.  
d. Divide number of seconds in step c. into 3600 (number  
of seconds in 1 hour).  
e. Multiply result of step d. by the number of cubic feet  
shown for one revolution of test dial to obtain cubic feet  
of gas flow per hour.  
f. Multiply result of step f. by Btu heating value of the gas  
to obtain total measured input shown in Table 6.  
(Consult the local gas supplier if the heating value of  
gas is not known).  
EXAMPLE: Assume a 90,000 high stage input unit is being  
installed. Assume that the size of the dial is 2 cubic ft., one  
revolution takes 84 sec., and the heating value of the gas is 1025  
Btu/ft3. Proceed as follows:  
a. 84 sec. to complete one revolution  
b. 3600/84 = 42.9  
Pipe Plug  
Manifold  
A09082  
c. 42.9 x 2 = 85.8 ft3 of gas flow/hr.  
d. 85.8 x 1050 = 90,090 Btuh input.  
Fig. 20 -- Burner Assembly  
27  
COMPONENT TEST  
BURNER FLAME  
The Evolution Furnace Board features a gas component test system  
to help diagnose a system problem in the case of a gas component  
failure. To initiate the component test procedure, ensure that there  
are no UI inputs to the control (the ABCD connector can be  
removed from the Evolution control board for this operation) and  
all time delays have expired. Turn on setup switch SW1--6.  
BURNER  
NOTE: The component test feature will not operate if the control  
is receiving any UI signals or until all time delays have expired.  
The component test sequence is as follows:  
MANIFOLD  
1. The control turns the inducer motor ON and keeps it ON  
through step 3.  
2. After waiting 10 seconds, the control turns the igniter ON  
for 15 seconds, then OFF.  
3. The control then turns the indoor fan motor on for 15  
seconds, then OFF.  
4. After shutting the blower motor OFF, the control runs the  
inducer for 10 seconds, then turns it OFF.  
C99021  
Fig. 21 -- Monoport Burner  
LIMIT SWITCHES  
NOTE: The EAC terminals are energized when the blower is  
operating.  
Normally closed limit switch (LS) completes the control circuit.  
Should the leaving--air temperature rise above the maximum  
allowable temperature, the limit switch opens and the control  
circuit “breaks.” Any interruption in the control circuit instantly  
closes the gas valve and stops gas flow to the burners. The blower  
motor continues to run until LS resets. The furnace board STATUS  
LED will display STATUS CODE 33.  
After the component test is completed, one or more status codes  
(11, 25, or 41) will flash. See component test section or Status  
Code Label for explanation of status codes.  
NOTE: To repeat component test, turn setup switch SW1--6 to  
OFF and then back ON.  
When the air temperature at the limit switch drops to the  
low--temperature setting of the limit switch, the switch closes and  
completes the control circuit. The direct--spark ignition system  
cycles and the unit returns to normal heating operation.  
Check for Refrigerant Leaks  
Locate and repair refrigerant leaks and charge the unit as follows:  
1. Use both high-- and low--pressure ports to relieve system  
pressure and reclaim remaining refrigerant.  
ROLLOUT SWITCH  
2. Repair leak following accepted practices.  
The function of the rollout switch is to close the main gas valve in  
the event of flame rollout. The switch is located above the main  
burners. When the temperature at the rollout switch reaches the  
maximum allowable temperature, the control circuit trips, closing  
the gas valve and stopping gas flow to the burners. The indoor fan  
motor (IFM) continues to run until switch is reset. The furnace  
board STATUS LED will display STATUS CODE 33.  
NOTE: Install a filter drier whenever the system has been opened  
for repair.  
3. Check system for leaks using an approved method.  
4. Evacuate refrigerant system and reclaim refrigerant if no  
additional leaks are found.  
5. Charge unit with Puron (R--410A) refrigerant, using an  
accurate scale. Refer to unit rating plate for required charge.  
CONTINUOUS FAN MODE  
When continuous fan operation is requested by the UI indoor fan  
motor will operate at continuous blower airflow. Continuous fan  
operation is programmable. See the UI Owner’s Manual for  
detailed instructions. Terminal EAC--1 is energized as long as the  
indoor fan motor is energized.  
During a call for gas heat, the Evolution control will transition the  
indoor fan motor to continuous blower airflow or gas heat airflow,  
whichever is lowest. The indoor fan motor will remain ON until  
the burners ignite, then shut OFF and remain OFF for the  
blower--ON delay allowing the heat exchangers to heat up more  
quickly, then restarts at the end of the blower--ON delay period.  
Start--Up Adjustments  
Complete the required procedures given in the Pre--Start--Up  
section before starting the unit. Do not jumper any safety devices  
when operating the unit. Do not operate the unit in cooling mode  
when the outdoor temperature is below 40°F (4°C) (unless  
low--ambient operation is enabled in the UI). Do not rapid cycle  
the compressor. Allow 5 min. between “on” cycles to prevent  
compressor damage.  
CHECKING COOLING AND HEATING CONTROL  
OPERATION  
The indoor fan motor will revert to continuous--blower airflow  
after the gas heating cycle is completed.  
See UI Installation Instructions for detailed system CHECKOUT.  
CHECKING AND ADJUSTING REFRIGERANT CHARGE  
When the UI “calls for cooling”, the indoor fan motor will switch  
to operate at cooling airflow. When the call for cooling is satisfied,  
the indoor fan motor will operate an additional 90 seconds at  
cooling airflow before transitioning back to continuous--blower  
airflow.  
The refrigerant system is fully charged with Puron (R--410A)  
refrigerant and is tested and factory sealed.  
NOTE: Any adjustment to refrigerant charge must be done with  
unit operating in HIGH stage.  
NOTE:  
Adjustment of the refrigerant charge is not required  
When the call for continuous fan is removed, the indoor blower  
will continue operating for an additional 5 seconds before shutting  
down, if no other function requires blower motor operation.  
unless the unit is suspected of not having the proper R--410A  
charge. The charging label and the tables shown refer to system  
temperatures and pressures in cooling mode only. A refrigerant  
charging label is attached to the outside of the unit.  
28  
Table 6 – Heating Inputs  
GAS SUPPLY PRESSURE (IN. W.C.)  
Natural  
MANIFOLD PRESSURE (IN. W.C.)  
HEATING INPUT (BTU/HR)*  
NUMBER OF  
ORIFICES  
Natural  
High Stage  
40,000  
Low Stage  
26,000  
39,000  
58,500  
75,000  
84,500  
Min  
4.0  
4.0  
4.0  
4.0  
4.0  
Max  
13.0  
13.0  
13.0  
13.0  
13.0  
High Stage  
3.23.8  
3.23.8  
3.23.8  
3.23.8  
3.23.8  
Low Stage  
1.4 ∼ 2.0  
1.4 ∼ 2.0  
1.4 ∼ 2.0  
1.4 ∼ 2.0  
1.4 ∼ 2.0  
2
3
3
3
3
60,000  
90,000  
115,000  
130,000  
*Cubic ft of natural gas per hour for gas pressures of .5 psig (14 IN. W.C.) or less and a pressure drop of .5 IN. W.C. (based on a .60 specific gravity gas). Ref:  
Table 6.2 (b) NPFA 54 / ANSI Z223.1---2009.  
Table 7 – ECM Wet Coil Pressure Drop (IN. W.C.)  
STANDARD CFM (SCFM)  
UNIT  
SIZE  
600  
0.005  
700  
0.007  
800  
0.010  
900  
0.012  
0.012  
0.019  
1000  
0.015  
0.015  
0.023  
0.014  
1100  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
24  
30  
36  
42  
48  
60  
0.007  
0.010  
0.018  
0.027  
0.017  
0.021  
0.032  
0.020  
0.027  
0.024  
0.037  
0.024  
0.032  
0.042  
0.027  
0.036  
0.047  
0.031  
0.041  
0.029  
0.035  
0.046  
0.032  
0.039  
0.052  
0.036  
0.043  
0.057  
0.040  
0.063  
0.045  
0.068  
0.049  
0.053  
Table 8 – Filter Pressure Drop Table (IN. W.C.)  
CFM  
FILTER SIZE  
in. (mm)  
500  
600  
700  
800  
900  
1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300  
20X20X1  
0.05  
0.07  
0.08  
0.1  
0.12  
0.13  
0.6  
0.14 0.15  
0.07 0.07  
(508x508x25)  
24X30X1  
(610x762x25)  
24X36X1  
(610x914x25)  
0.05  
0.08  
0.07  
0.09  
0.1  
0.06  
0.07 0.08  
0.09  
0.09 0.10  
0.11  
0.12 0.13  
0.14  
0.14  
IMPORTANT: When evaluating the refrigerant charge, an  
indicated adjustment to the specified factory charge must always be  
very minimal. If a substantial adjustment is indicated, an abnormal  
condition exists somewhere in the cooling system, such as  
insufficient airflow across either coil or both coils.  
TO USE COOLING CHARGING CHARTS  
Take the liquid line temperature and read the manifold pressure  
gauges.  
Refer to the chart to determine what the liquid line temperature  
should be.  
REFRIGERANT CHARGE  
NOTE:  
If the problem causing the inaccurate readings is a  
The amount of refrigerant charge is listed on the unit rating plate  
and/or the physical data table. Refer to the Refrigeration Service  
Techniques Manual, Refrigerants Section.  
refrigerant leak, refer to Check for Refrigerant Leaks section.  
NON--COMMUNICATING EMERGENCY  
HEATING MODE: 4--WIRE THERMOSTAT  
COOLING  
/
NO CHARGE  
This mode of operation is provided only in the case where the UI  
has failed or is otherwise unavailable. If communications cannot be  
established with the UI, the Evolution furnace board will enable  
Check for leak. Use standard evacuating techniques. After  
evacuating system, weigh in the specified amount of refrigerant  
(refer to system rating plate).  
the standard thermostat input terminals  
thermostatic control of the 577D----A unit.  
to allow simple  
LOW CHARGE COOLING  
For control with a standard thermostat, disconnect the ABCD  
connectors from both control boards and using No. 18 AWG  
color--coded, insulated type 90°C minimum or equivalent wire,  
make the connections between the standard thermostat, the furnace  
board, and the HP/AC board per Fig. 22. Recommend the use of  
interconnecting wire with 105C, 600V, 2/64” insulation.  
The Evolution control will respond to cooling and heating  
demands with the maximum safe airflow based on gas furnace  
output and unit cooling capacity.  
Use Cooling Charging Chart (Fig. 23). Vary refrigerant until the  
conditions of the chart are met. Note that charging charts are  
different from type normally used. Charts are based on charging  
the units to correct subcooling for the various operating conditions.  
Accurate pressure gauge and temperature sensing devices are  
required. Connect the pressure gauge to the service port on the  
suction line. Mount the temperature sensing device on the suction  
line and insulate it so that the outdoor ambient does not affect the  
reading. Indoor air CFM must be within the normal operating  
range of the unit.  
29  
A06360  
Fig. 22 -- Non--Communicating Emergency Cooling/Heating Wiring Connections  
A09109  
Fig. 23 -- Cooling Charging Table--Subcooling  
30  
7. Inspect all accessories. Perform any service or maintenance  
to the accessories as recommended in the accessory  
instructions.  
MAINTENANCE  
To ensure continuing high performance, and to minimize the  
possibility of premature equipment failure, periodic maintenance  
must be performed on this equipment. This packaged unit should  
be inspected at least once each year by a qualified service person.  
To troubleshoot unit, refer to Table 9 and 10, Troubleshooting  
Chart.  
Air Filter  
IMPORTANT: Never operate the unit without a suitable air filter  
in the return--air duct system. Always replace the filter with the  
same dimensional size and type as originally installed. See Table 1  
for recommended filter sizes.  
NOTE TO EQUIPMENT OWNER: Consult your local dealer  
about the availability of a maintenance contract.  
Inspect air filter(s) at least once each month and replace  
(throwaway--type) or clean (cleanable--type) at least twice during  
each cooling season and twice during the heating season, or  
whenever the filter becomes clogged with dust and lint.  
!
WARNING  
PERSONAL INJURY AND UNIT DAMAGE  
HAZARD  
Indoor Fan and Motor  
NOTE: All motors are pre--lubricated. Do not attempt to lubricate  
these motors.  
Failure to follow this warning could result in personal  
injury or death and possible unit component damage.  
For longer life, operating economy, and continuing efficiency,  
clean accumulated dirt and grease from the blower wheel and  
motor annually.  
The ability to properly perform maintenance on this  
equipment requires certain expertise, mechanical skills,  
tools and equipment. If you do not possess these, do not  
attempt to perform any maintenance on this equipment,  
other than those procedures recommended in the Owner’s  
Manual.  
Inducer Blower  
NOTE: All motors are pre--lubricated. Do not attempt to lubricate  
these motors.  
Clean periodically to assure proper airflow and heating efficiency.  
Inspect blower wheel every fall and periodically during the heating  
season. For the first heating season, inspect blower wheel  
bi--monthly to determine proper cleaning frequency.  
!
WARNING  
Limit Switch  
ELECTRICAL SHOCK HAZARD  
Remove unit access panel to gain access to the limit switch. The  
limit switch is located above the indoor blower housing.  
Failure to follow these warnings could result in personal  
injury or death:  
NOTE: On small chassis units, a second limit switch is located  
beside the indoor blower housing.  
1. Turn off electrical power to the unit and install lockout  
tag before performing any maintenance or service on this  
unit.  
Burner Ignition  
2. Use extreme caution when removing panels and parts.  
Unit is equipped with a direct spark ignition 100 percent lockout  
system. Ignition module is located in the control box. Refer to  
additional information in the Start--Up & Troubleshooting section  
for Status Code information.  
3. Never place anything combustible either on or in contact  
with the unit.  
Main Burners  
At the beginning of each heating season, inspect for deterioration  
or blockage due to corrosion or other causes. Observe the main  
burner flames and adjust, if necessary.  
!
CAUTION  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in equipment  
damage or improper operation.  
CAUTION  
EQUIPMENT DAMAGE HAZARD  
!
Errors made when reconnecting wires may cause improper  
and dangerous operation. Label all wires prior to  
disconnecting when servicing.  
Failure to follow this caution may result in equipment  
damage or improper operation.  
When servicing gas train, do not hit or plug orifice spuds.  
The minimum maintenance requirements for this equipment are as  
follows:  
Removal of Gas Train  
To remove the gas train for servicing:  
1. Shut off main gas valve.  
1. Inspect air filter(s) each month. Clean or replace when  
necessary.  
2. Inspect indoor coil, drain pan, and condensate drain each  
cooling season for cleanliness. Clean when necessary.  
2. Shut off power to unit and install lockout tag.  
3. Remove control access panel (See Fig. 24).  
4. Disconnect gas piping at unit gas valve.  
3. Inspect indoor fan motor and wheel for cleanliness each  
cooling season. Clean when necessary.  
5. Remove fan partition mounting bracket (2 screws located  
on the left side of control compartment on the fan partition  
panel). Slide bracket forward, bottom first, to remove. (See  
Fig. 25.)  
4. Check electrical connections for tightness and controls for  
proper operation each cooling season. Service when  
necessary.  
5. Check for restrictions on inducer outlet. Clean flue hood.  
6. Inspect burner compartment before each heating season for  
rust, corrosion, soot or excessive dust.  
6. Remove wires connected to gas valve. Mark each wire.  
7. Remove the mounting screw that attaches the burner rack to  
the unit base (See Fig. 25).  
31  
8. Partially slide the burner rack out of the unit (see Fig. 25  
and 26). Remove ignitor and sensor wires at the burner as-  
sembly. Remove wires to rollout switch.  
!
WARNING  
9. Slide the burner rack out of the unit (See Fig. 25 and 26).  
10. To reinstall, reverse the procedure outlined above.  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Disconnect and install lockout tag on electrical power to the  
unit before cleaning and lubricating the blower motor and  
wheel.  
Outdoor Coil, Indoor Coil, and Condensate  
Drain Pan  
Inspect the condenser coil, evaporator coil, and condensate drain  
pan at least once each year.  
The coils are easily cleaned when dry; therefore, inspect and clean  
the coils either before or after each cooling season. Remove all  
obstructions, including weeds and shrubs, that interfere with the  
airflow through the condenser coil. Straighten bent fins with a fin  
comb. If coated with dirt or lint, clean the coils with a vacuum  
cleaner, using the soft brush attachment. Be careful not to bend the  
fins. If coated with oil or grease, clean the coils with a mild  
detergent and water solution. Rinse coils with clear water, using a  
garden hose. Be careful not to splash water on motors, insulation,  
wiring, or air filter(s). For best results, spray condenser coil fins  
from inside to outside the unit. On units with an outer and inner  
condenser coil, be sure to clean between the coils. Be sure to flush  
all dirt and debris from the unit base.  
Control  
Access  
Panel  
Blower  
Access  
Panel  
Compressor  
Access Panel  
A09479  
Fig. 24 -- Unit Access Panels  
Inspect the drain pan and condensate drain line when inspecting  
the coils. Clean the drain pan and condensate drain by removing all  
foreign matter from the pan. Flush the pan and drain trough with  
clear water. Do not splash water on the insulation, motor, wiring, or  
air filter(s). If the drain trough is restricted, clear it with a  
“plumbers snake” or similar probe device.  
Integrated  
Gas Unit  
Controller  
(IGC)  
Auto Transformer  
fuses used on 460  
volt units only.  
(Hidden)  
Outdoor Fan  
Interface Fan  
Board (IFB)  
!
CAUTION  
Induced Draft  
Motor  
UNIT OPERATION HAZARD  
Fan Partition  
Mounting  
Bracket  
Flue  
Collector  
Box  
Failure to follow this caution may result in damage to unit  
components.  
Rollout  
Switch  
Inducer  
Blower  
Housing  
Burner  
Rack  
Mounting  
Screw  
Keep the outdoor fan free from all obstructions to ensure  
proper cooling operation. Never place articles on top of the  
unit.  
A09480  
Fig. 25 -- Blower Housing and Flue Collector Box  
1. Remove 4 screws holding outdoor grille and motor to top  
cover.  
2. Turn motor/grille assembly upside down on top cover to  
expose fan blade.  
3. Inspect the fan blades for cracks or bends.  
4. If fan needs to be removed, loosen setscrew and slide fan off  
motor shaft.  
5. When replacing fan blade, position blade according to the  
table shown in Fig. 27.  
6. Ensure that set screw engages the flat area on the motor  
shaft when tightening.  
7. Replace grille.  
Electrical Controls and Wiring  
Inspect and check the electrical controls and wiring annually. Be  
sure to turn off the electrical power to the unit.  
Remove access panel to locate all the electrical controls and wiring.  
Check all electrical connections for tightness. Tighten all screw  
connections. If any smoky or burned connections are noticed,  
disassemble the connection, clean all the parts, re--strip the wire  
end and reassemble the connection properly and securely.  
A07680  
Fig. 26 -- Burner Rack Removed  
Inducer Pressure Switch  
Inspect pressure switch connections. Inspect pressure switch tube  
for cracks or restrictions. Replace if needed.  
32  
After inspecting the electrical controls and wiring, replace all the  
panels. Start the unit, and observe at least one complete cooling  
cycle to ensure proper operation. If discrepancies are observed in  
operating cycle, or if a suspected malfunction has occurred, check  
each electrical component with the proper electrical  
instrumentation. Refer to the unit wiring label when making these  
checks.  
3. Apply ohm meter leads across switch. You should have  
continuity on a good switch.  
NOTE:  
Because these switches are attached to refrigeration  
system under pressure, it is not advisable to remove this device for  
troubleshooting unless you are reasonably certain that a problem  
exists. If switch must be removed, remove and recover all system  
charge so that pressure gauges read 0 psi. Never open system  
without breaking vacuum with dry nitrogen.  
Copeland Scroll Compressor (Puron Refrigerant)  
The compressor used in this product is specifically designed to  
operate with Puron (R--410A) refrigerant and cannot be  
interchanged.  
The compressor is an electrical, as well as mechanical, device.  
Exercise extreme caution when working near compressors. Power  
should be shut off, if possible, for most troubleshooting techniques.  
Refrigerants present additional safety hazards.  
A06132  
UNIT SIZE  
“A” DIM. IN. (MM)  
1 (26)  
!
24  
30  
36  
42  
48  
60  
WARNING  
1 (26)  
1 (26)  
1 (26)  
11/32 (9)  
9/16 (14)  
EXPLOSION, FIRE HAZARD  
Failure to follow this warning could result in personal  
injury or death and/or property damage.  
Wear safety glasses and gloves when handling refrigerants.  
Keep torches and other ignition sources away from  
refrigerants and oils.  
Fig. 27 -- Outdoor Fan Blade Clearance  
Refrigerant Circuit  
The scroll compressor pumps refrigerant throughout the system by  
the interaction of a stationary and an orbiting scroll. The scroll  
compressor has no dynamic suction or discharge valves, and it is  
more tolerant of stresses caused by debris, liquid slugging, and  
flooded starts. The compressor is equipped with noise reducing  
shutdown device and an internal pressure--relief port. The  
pressure--relief port is a safety device, designed to protect against  
extreme high pressure. The relief port has an operating range  
between 550 and 625 psi differential pressure.  
Inspect all refrigerant tubing connections and the unit base for oil  
accumulation annually. Detecting oil generally indicates  
refrigerant leak.  
a
If oil is detected or if low performance is suspected, leak test all  
refrigerant tubing using an electronic leak detector, or liquid--soap  
solution. If a refrigerant leak is detected, refer to Check for  
Refrigerant Leaks section.  
If no refrigerant leaks are found and low performance is suspected,  
refer to Checking and Adjusting Refrigerant Charge section.  
Refrigerant System  
This step covers the refrigerant system of the 577D----A, including  
the compressor oil needed, servicing systems on roofs containing  
synthetic materials, the filter drier, and refrigerant charging.  
Indoor Airflow  
The heating and/or cooling airflow does not require checking  
unless improper performance is suspected. If a problem exists, be  
sure that all supply-- and return--air grilles are open and free from  
obstructions, and that the air filter is clean.  
REFRIGERANT  
Pressure Switches -- Refrigerant Circuit  
!
WARNING  
Pressure switches are protective devices integrated into the control  
circuit (low voltage). They shut off compressor if abnormally high  
or low pressures are present in the refrigeration circuit. These  
pressure switches are specifically designed to operate with Puron  
(R--410A) systems. R--22 pressure switches must not be used as  
replacements for the Puron (R--410A) system.  
UNIT  
OPERATION,  
SAFETY  
AND  
ENVIRONMENTAL HAZARD  
Failure to follow this warning could result in personal  
injury or equipment damage.  
This system uses Puron (R--410A) refrigerant which has  
higher operating pressures than R--22 and other refrigerants.  
No other refrigerant may be used in this system. Gauge set,  
hoses, and recovery system must be designed to handle  
Puron. If you are unsure, consult the equipment  
manufacturer.  
Loss--of--Charge (Low Pressure) Switch  
This switch is located on the liquid line and protects against low  
suction pressures caused by such events as loss of charge, low  
airflow across indoor coil, dirty filters, etc. It opens if the system  
pressure drops to about 20 psig. If system pressure is above this,  
switch should be closed.  
High--Pressure Switches (HPS & HPS2)  
COMPRESSOR OIL  
The high--pressure switches are located on the discharge line and  
protects against excessive condenser coil pressure. HPS opens at  
670 psig shutting down the compressor, while HPS2 opens at 565,  
limiting the compressor to low--stage operation only.  
High pressure may be caused by a dirty outdoor coil, failed fan  
motor, or outdoor air recirculation.  
If additional oil is needed use Uniqema RL32--3MAF. If this oil is  
not available, use Copeland Ultra 32CC or Mobil Artic EAL22CC.  
This oil is extremely hygroscopic, meaning it absorbs water  
readily. POE oils can absorb 15 times as much water as other oils  
designed for HCFC and CFC refrigerants. Take all necessary  
precautions to avoid exposure of the oil to the atmosphere.  
SERVICING SYSTEMS ON ROOFS WITH SYNTHETIC  
MATERIALS  
POE (polyolester) compressor lubricants are known to cause long  
term damage to some synthetic roofing materials.  
To check switches:  
1. Turn off all power to unit.  
2. Disconnect leads on switch.  
33  
Exposure, even if immediately cleaned up, may cause  
embrittlement (leading to cracking) to occur in one year or more.  
When performing any service that may risk exposure of  
compressor oil to the roof, take appropriate precautions to protect  
roofing. Procedures which risk oil leakage include, but are not  
limited to, compressor replacement, repairing refrigerant leaks, and  
replacing refrigerant components such as filter drier, pressure  
switch, metering device, coil, accumulator, or reversing valve.  
-- G a s v a l v e  
-- Inducer motor  
-- Remote sparker module  
-- Pressure switch monitoring (gas)  
SYSTEMS COMMUNICATION FAILURE  
If communication with the Evolution Control is lost with the UI,  
the controls will flash the appropriate fault codes. Check the wiring  
to the UI, indoor and outdoor units.  
Synthetic Roof Precautionary Procedure  
MODEL PLUG  
1. Cover extended roof working area with an impermeable  
polyethylene (plastic) drip cloth or tarp. Cover an  
approximate 10 X 10 ft (3x3 m) area.  
The HP/AC control board must have a valid model plug to operate.  
If a valid model plug is not detected, it will not operate and the  
control will flash the appropriate fault code, shown in Table 4.  
2. Cover area in front of the unit service panel with a terry  
cloth shop towel to absorb lubricant spills and prevent  
run--offs, and protect drop cloth from tears caused by tools  
or components.  
3. Place terry cloth shop towel inside unit immediately under  
component(s) to be serviced and prevent lubricant run--offs  
through the louvered openings in the unit base.  
PRESSURE SWITCH PROTECTION--REFRIGERANT  
The unit is equipped with high-- and low--pressure switches. If the  
control senses the opening of a high-- or low--pressure switch, it  
will respond as follows:  
1. De--energize the compressor contactor (HPS1 & LPS) or the  
compressor solenoid contactor (HPS2).  
4. Perform required service.  
5. Remove and dispose of any oil--contaminated material per  
local codes.  
2. Keep the outdoor fan operating for 15 minutes.  
3. Display the appropriate fault codes.  
4. After a 15 minute delay, if there is still a call for cooling and  
the LPS or HPS is reset, the compressor contactor is  
energized.  
LIQUID--LINE FILTER DRIER  
The filter drier is specifically designed to operate with Puron. Use  
only factory--authorized components. Filter drier must be replaced  
whenever the refrigerant system is opened. When removing a filter  
drier, use a tubing cutter to cut the drier from the system. Do not  
unsweat a filter drier from the system. Heat from unsweating will  
release moisture and contaminants from drier into system.  
5. If LPS or HPS has not closed after a 15 minute delay, the  
outdoor fan is turned off. If the open switch closes anytime  
after the 15--minute delay, then resume operation with a call  
for cooling.  
6. If LPS or HPS trips 3 consecutive cycles, the unit operation  
is locked out for 4 hours.  
PURON (R--410A) REFRIGERANT CHARGING  
Refer to unit information plate and charging chart. Some R--410A  
refrigerant cylinders contain a dip tube to allow liquid  
refrigerant to flow from cylinder in upright position. For  
cylinders equipped with a dip tube, charge Puron units with  
cylinder in upright position and a commercial metering device in  
manifold hose. Charge refrigerant into suction line.  
7. In the event of a high--pressure switch trip or high pressure  
lockout, check the refrigerant charge, outdoor fan operation  
and outdoor coil for airflow restrictions.  
8. In the event of a low--pressure switch trip or low pressure  
lockout, check the refrigerant charge and indoor airflow.  
CONTROL FAULT  
TROUBLESHOOTING  
LED DESCRIPTION  
If the HP/AC control board has failed, the control will flash the  
appropriate fault code (See Table 4). The control board should be  
replaced.  
LEDs built into Evolution control boards provide installer or  
service person information concerning operation and/or fault  
condition of the unit controls and ECM motor. This information is  
also available at the system UI in text with basic troubleshooting  
instructions. Careful use of information displayed will reduce the  
need for extensive manual troubleshooting. See section B in  
Start--Up & Troubleshooting and Table 4, as well as the UI  
BROWN OUT PROTECTION  
If the line voltage is less than 187v for at least 4 seconds, the  
appropriate compressor contactor and fan relay are de--energized.  
Compressor and fan operation are not allowed until voltage is a  
minimum of 190v. The control will flash the appropriate fault  
code (See Table 4).  
instructions,  
for  
additional  
information.  
Additional  
230V LINE (POWER DISCONNECT) DETECTION  
Troubleshooting information can be found in Table 9 and 10.  
If there is no 230v at the compressor contactor when the unit is  
powered and cooling demand exists, the appropriate error code is  
displayed. Verify that the disconnect is closed and 230v wiring is  
connected to the unit.  
MAJOR COMPONENTS  
2--STAGE HP/AC BOARD  
The two--stage HP/AC control board controls the following  
functions:  
COMPRESSOR VOLTAGE SENSING  
-- Low-- and high--stage compressor operation  
-- Outdoor fan motor operation  
-- Reversing valve operation  
-- Defrost operation  
The control board input terminals VS and L2 (See Fig. 18) are  
used to detect compressor voltage status, and alert the user of  
potential problems. The control continuously monitors the high  
voltage on the run capacitor of the compressor motor. Voltage  
should be present any time the compressor contactor is energized,  
and voltage should not be present when the contactor is  
de--energized.  
-- Low ambient cooling  
-- Crankcase heater operation  
-- Compressor external protection  
-- Pressure switch monitoring (refrigerant)  
-- Time delays  
CONTACTOR SHORTED DETECTION  
If there is compressor voltage sensed when there is no demand for  
compressor operation, the contactor may be stuck closed or there is  
a wiring error. The control will flash the appropriate fault code.  
FURNACE BOARD  
COMPRESSOR THERMAL CUTOUT  
If the control senses the compressor voltage after start--up, and is  
then absent for 10 consecutive seconds while cooling demand  
The furnace board controls the following functions:  
-- Indoor blower operation  
34  
exists, the thermal protector is open. The control de--energizes the  
compressor contactor for 15 minutes, but continues to operate the  
outdoor fan. The control Status LED will flash the appropriate  
code shown in Table 4. After 15 minutes, with a call for low or  
high stage cooling, the compressor contactor is energized. If the  
thermal protector has not re--set, the outdoor fan is turned off. If  
the call for cooling continues, the control will energize the  
compressor contactor every 15 minutes. If the thermal protector  
closes (at the next 15 minute interval), check the unit will resume  
operation.  
THERMISTOR SENSOR COMPARISON  
The control continuously monitors and compares the outdoor air  
temperature sensor and outdoor coil temperature sensor to ensure  
proper operating conditions. The comparison is:  
S In cooling mode, if the outdoor air sensor indicates 10 _F  
(5.5_C) warmer than the coil sensor (or) the outdoor air sensor  
indicates 20_F (11.0_C) cooler than the coil sensor, the sensors  
are out of range.  
S In heating if the outdoor air sensor indicates 35_F (19.3_C)  
warmer than the coil sensor (or) the outdoor air sensor indicates  
10_F (5.5_C) cooler than the coil sensor, the sensors are out of  
range.  
If the thermal cutout trips for three consecutive cycles, then unit  
operation is locked out for 4 hours and the appropriate fault code is  
displayed.  
NO 230V AT COMPRESSOR  
If the sensors are out of range, the control will flash the appropriate  
fault code as shown in Table 4.  
The thermistor comparison is not performed during low ambient  
cooling operation.  
If the compressor voltage is not sensed when the compressor  
should be starting, the contactor may be stuck open or there is a  
wiring error. The control will flash the appropriate fault code.  
Check the contactor and control box wiring.  
FAILED THERMISTOR DEFAULT OPERATION  
TROUBLESHOOTING UNIT FOR PROPER SWITCHING  
BETWEEN LOW & HIGH STAGES  
Factory defaults have been provided in the event of failure of  
outdoor air thermistor and/or coil thermistor.  
Check the suction pressures at the service valves. Suction pressure  
should be reduced by 3--10% when switching from low to high  
capacity.  
If the OAT sensor should fail, low ambient cooling will not be  
allowed and the one--minute outdoor fan off delay will not occur.  
Defrost will be initiated based on coil temperature and time.  
NOTE: The liquid pressures are very similar between low and  
high stage operation, so liquid pressure should not be used for  
troubleshooting.  
If the OCT sensor should fail, low ambient cooling will not be  
allowed. Defrost will occur at each time interval during heating  
operation, but will terminate after 5 minutes.  
If there is a thermistor out of range error, defrost will occur at each  
time interval during heating operation, but will terminate after 5  
minutes.  
Compressor current should increase 20--45% when switching from  
low to high stage. The compressor solenoid, when energized in  
high stage, should measure 24vac.  
COMPRESSOR INTERNAL RELIEF  
Refer to the Troubleshooting Chart (Table 9 and 10) for additional  
troubleshooting information.  
The compressor is protected by an internal pressure relief (IPR)  
which relieves discharge gas into compressor shell when  
differential between suction and discharge pressures exceeds 550 --  
625 psi. The compressor is also protected by an internal overload  
attached to motor windings.  
TEMPERATURE THERMISTORS  
Thermistors are electronic devices which sense temperature. As the  
temperature increases, the resistance decreases. Thermistors are  
used to sense outdoor ambient (OAT) and coil temperature (OCT).  
Refer to Fig. 28 for resistance values versus temperature. See Fig.  
29 for OCT location.  
If the outdoor ambient or coil thermistor should fail, the HP/AC  
control will flash the appropriate fault code (See Table 4).  
IMPORTANT: Coil thermistor is factory mounted. Check to  
insure thermistor is mounted properly. Outdoor air thermistor  
(OAT) is field mounted and connected. Verify that the OAT has  
been properly installed.  
THERMISTOR CURVE  
A06311  
90  
80  
Fig. 29 -- Outdoor Coil Thermistor (OCT) Attachment  
70  
60  
50  
40  
30  
20  
FINAL CHECKS  
IMPORTANT: Before leaving job, be sure to do the following:  
1. Ensure that all wiring is routed away from tubing and sheet  
metal edges to prevent rub--through or wire pinching.  
2. Ensure that all wiring and tubing is secure in unit before  
adding panels and covers. Securely fasten all panels and  
covers.  
10  
0
0
20  
40  
60  
80  
100  
120  
TEMPERATURE (DEG. F)  
3. Tighten service valve stem caps to 1/2--turn past finger  
tight.  
A91431  
Fig. 28 -- Resistance Values Versus Temperature  
4. Leave Users Manual with owner. Explain system operation  
and periodic maintenance requirements outlined in manual.  
5. Fill out Start--Up Checklist located at the back of this  
manual and place in customer file.  
35  
CARE AND MAINTENANCE  
For continuing high performance and to minimize possible  
equipment failure, periodic maintenance must be performed on this  
equipment.  
Frequency of maintenance may vary depending upon geographic  
areas, such as coastal applications. See Users Manual for  
information.  
36  
AIR CONDITIONER WITH PURON  
REFRIGERATION SECTION QUICK--REFERENCE GUIDE  
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are  
designed to operate with Puron. Puron refrigerant cylinders are rose colored.  
S Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright  
position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid  
to flow.  
S Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.  
S Puron systems should be charged with liquid refrigerant. Use a commercial--type metering device in the manifold hose.  
S Manifold sets should be minimum 700 psig high side and 180 psig low side with 550 psig low side retard.  
S Use hoses with minimum 700 psig service pressure rating.  
S Leak detectors should be designed to detect HFC refrigerant.  
S Puron, as with other HFCs, is only compatible with POE oils.  
S Vacuum pumps will not remove moisture from oil.  
S Only use factory--specified liquid--line filter driers with rated working pressures no less than 600 psig.  
S Do not install a suction--line filter drier in liquid line.  
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.  
S POE oils may cause damage to certain plastics and roofing materials.  
S Wrap all filter driers and service valves with wet cloth when brazing.  
S A Puron liquid--line filter drier is required on every unit.  
S Do not use an R--22 TXV.  
S Never open system to atmosphere while it is under a vacuum.  
S When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.  
S Do not vent Puron into the atmosphere.  
S Observe all warnings, cautions, and bold text.  
S Do not leave Puron suction line driers in place for more than 72 hrs.  
37  
Table 9 – Troubleshooting Chart -- Cooling  
SYMPTOM  
CAUSE  
Power failure  
REMEDY  
Call power company  
Fuse blown or circuit breaker tripped  
Replace fuse or reset circuit breaker  
Defective contactor, transformer, control relay, or high--  
pressure, loss--of--charge or low--pressure switch  
Replace component  
Insufficient line voltage  
Incorrect or faulty wiring  
UI setting too low/too high  
Determine cause and correct  
Check wiring diagram and rewire correctly  
Reset UI setting  
Compressor and outdoor fan  
will not start  
DO NOT bypass this compressor time  
delay–wait for 5 minutes until time--delay  
relay is de--energized  
Units have a 5--minute time delay  
Faulty wiring or circuit  
Loose connections in compressor  
Check wiring and repair or replace  
Compressor motor burned out, seized, or  
internal overload open  
Defective run capacitor, overload, or PTC (positive  
temperature coefficient) thermistor  
Determine cause  
Replace compressor  
Compressor will not start but condenser fan  
runs  
Determine cause and replace  
Determine cause and correct  
Low input voltage (20 percent low)  
Recover refrigerant, evacuate system, and re-  
charge to capacities shown on rating plate  
Refrigerant overcharge or undercharge  
Defective compressor  
Insufficient line voltage  
Blocked outdoor coil  
Defective run/start capacitor, overload or start relay  
Faulty outdoor fan motor or capacitor  
Restriction in refrigerant system  
Dirty air filter  
Replace and determine cause  
Determine cause and correct  
Determine cause and correct  
Determine cause and replace  
Replace  
Compressor cycles (other than normally sat-  
isfying) cooling/heating calls  
Locate restriction and remove  
Replace filter  
Unit undersized for load  
UI temperature set too low  
Low refrigerant charge  
Decrease load or increase unit size  
Reset UI setting  
Locate leak, repair, and recharge  
Compressor operates continuously  
Recover refrigerant, evacuate system, and re-  
charge  
Air in system  
Outdoor coil dirty or restricted  
Dirty air filter  
Clean coil or remove restriction  
Replace filter  
Dirty indoor or outdoor coil  
Refrigerant overcharged  
Clean coil  
Recover excess refrigerant  
Recover refrigerant, evacuate system, and re-  
charge  
Excessive head pressure  
Air in system  
Indoor or outdoor air restricted or air short--cycling  
Low refrigerant charge  
Restriction in liquid tube  
Determine cause and correct  
Check for leaks, repair and recharge  
Remove restriction  
Head pressure too low  
High heat load  
Reversing valve hung up or leaking internally  
Refrigerant overcharged  
Check for source and eliminate  
Replace valve  
Recover excess refrigerant  
Replace filter  
Excessive suction pressure  
Dirty air filter  
Low refrigerant charge  
Metering device or low side restricted  
Insufficient coil airflow  
Temperature too low in conditioned area  
Outdoor ambient below 55°F (13°C)  
Filter drier restricted  
Check for leaks, repair and recharge  
Remove source of restriction  
Check filter–replace if necessary  
Reset UI setting  
Verify low--ambient cooling enabled in UI  
Replace  
Suction pressure too low  
Blower wheel not secured to shaft  
Insufficient voltage at motor  
Power connectors not properly sealed  
Water dripping into motor  
Properly tighten blower wheel to shaft  
Determine cause and correct  
Connectors should snap easily; do not force  
Verify proper drip loops in connector wires  
IFM does not run  
IFM operation is intermittent  
Gently pull wires individually to be sure they are  
crimped into the housing  
Connectors not firmly sealed  
38  
Table 10 – Troubleshooting Chart -- Gas Furnace Operation  
SYMPTOM  
CAUSE  
REMEDY  
Water in gas line  
No power to unit  
Drain. Install drip leg.  
Check power supply fuses, wiring or circuit  
breaker.  
Check transformer.  
NOTE: Some transformers have internal over--  
current protection that requires a cool--down peri-  
od to reset.  
No 24--v power supply to control circuit  
Mis--wired or loose connections  
Misaligned spark electrodes  
Check all wiring and wire nut connections  
Burners will not ignite  
Check flame ignition and sense electrode posi-  
tioning.  
Adjust as necessary.  
1. Check gas line for air. Purge as necessary.  
NOTE: After purging gas line of air, wait at least 5  
minutes for any gas to dissipate before attempt-  
ing to light unit.  
No gas at main burners  
2. Check gas valve.  
1. Check pressure switch wires, connections,  
and tubing. Repair or replace if necessary.  
Clean or replace filter as necessary  
Inducer pressure switch not closing  
Dirty air filter  
Check gas pressure at manifold match with that  
on unit nameplate  
Gas input to unit too low  
Inadequate heating  
Unit undersized for application  
Restricted airflow  
Replace with proper unit or add additional unit  
Clean or replace filter. Remove any restriction.  
Check rotation of blower, temperature rise of unit.  
Adjust as necessary.  
Limit switch cycles main burners  
1. Tighten all screws around burner compartment  
2. Cracked heat exchanger. Replace.  
3. Unit over--fired. Reduce input (change orifices  
or adjust gas line or manifold pressure).  
4. Check burner alignment.  
5. Inspect heat exchanger for blockage. Clean  
as necessary.  
Incomplete combustion results in: Aldehyde odors,  
carbon monoxide, sooting flame, floating flame  
Poor flame characteristics  
39  
START--UP CHECKLIST  
(Remove and Store in Job Files)  
I. PRELIMINARY INFORMATION  
MODEL NO.:  
SERIAL NO.:  
DATE:  
TECHNICIAN:  
II. PRESTART--UP (Insert check mark in box as each item is completed)  
( ) VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
( ) REMOVE ALL SHIPPING HOLD DOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS  
( ) CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
( ) CHECK GAS PIPING FOR LEAKS (WHERE APPLICABLE)  
( ) CHECK THAT INDOOR (EVAPORATOR) AIR FILTER IS CLEAN AND IN PLACE  
( ) VERIFY THAT UNIT INSTALLATION IS LEVEL  
( ) CHECK FAN WHEEL, AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW TIGHTNESS  
( ) MAKE SURE THAT -- (If Applicable) ON A60 SIZE PURON HEAT PUMP ONLY, THE TWO WIRE TIRES FASTEN TO THE  
OUTDOOR COILS AND REVERSING VALVE/ACCUMULATOR HAVE BEEN REMOVED  
III. START--UP  
ELECTRICAL  
SUPPLY VOLTAGE  
COMPRESSOR AMPS  
INDOOR (EVAPORATOR) FAN AMPS  
TEMPERATURES  
OUTDOOR (CONDENSER) AIR TEMPERATURE  
RETURN--AIR TEMPERATURE  
DB  
DB  
WB  
COOLING SUPPLY AIR  
GAS HEAT SUPPLY AIR  
PRESSURES  
DB  
WB  
GAS INLET PRESSURE  
GAS MANIFOLD PRESSURE  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
IN. W.C.  
IN. W.C.  
PSIG, SUCTION LINE TEMP*  
PSIG, LIQUID TEMP{  
( ) VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS  
GAS HEAT TEMPERATURE RISE  
TEMPERATURE RISE (See Literature) RANGE  
MEASURED TEMPERATURE RISE  
( ) VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PROPERLY  
( ) VERIFY THAT OUTDOOR AIR THERMISTOR (OAT) IS PROPERLY INSTALLED & CONNECTED  
* Measured at suction inlet to compressor  
{
Measured at liquid line leaving condenser.  
E2010 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231  
Edition Date: 04/10  
Catalog No. II577D---06  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Replaces: II577D---05  
40  

Briggs Stratton 190700 User Manual
Carrier 40QNQ User Manual
Carrier 50BK User Manual
Carrier AQUAZONE 50RHE006 060 User Manual
Friedrich 9368987053 User Manual
Friedrich Air Conditioner VPRG4 User Manual
GE JGBP28MEK User Manual
Goldstar LWC061JGMK1 User Manual
Hitachi RAS 35YH6 User Manual
Honda Automobiles Automobile Accessories User Manual