Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS CON’T
Page
Refrigeration
Leak Testing
Evacuation
Temperature Control
Evaporator Fan Motors
11
12
12
13
13
Trouble Shooting Charts
GSVM Accessories
14 – 16
16 – 17
17
Warranty and Parts Information
Wiring Diagrams
18 – 21
This GSVM case was manufactured in Gloversville, New York. Our phone #’s are (518)
725-0644 for New York State residents and our toll free #800-753-7790 for outside New
York – should you have further questions.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
INTRODUCTION –
Save all packaging materials and
move the cabinet as little as possible prior
The Hussmann Model GSVM open to inspection.
vertical merchandiser offers versatility in
the display of medium temperature (35-
41ºF) products such as diary products,
prepared salads, pizza and fresh entrees
that are pre-chilled in a cooler.
LOCATION and CLEARANCE –
It is important that careful
consideration be given to locating the
cabinet away from an area where direct
sunlight would shine into the fixture, or
where drafts from air conditioning grilles,
fans, and open doors could affect its
operation.
So that you can realize maximum
benefit from this fine piece of equipment
we urge both you and your installer to
carefully read and follow this brief set of
instructions prior to installation of the
equipment.
The GSVM4060 and 4072 have
front condenser air intake and discharge.
A minimum distance of two feet must be
left open in front of the case so that air
discharge and intake to the condensing
unit is not obstructed.
INSPECTION –
The equipment has been skidded
and crated prior to shipment from the
factory. It is the carrier’s responsibility to
deliver it to you in good condition until
such time as you sign for it.
The GSVM5272 model requires a
5" minimum clearance behind the case
and clear above the case since it has
straight through condenser air flow.
Upon receipt of the cabinet,
examine the packaging for damage. If the Brackets are provided for field
packaging is damaged, make specific
notation on the delivery ticket as to the
location and extent of damage prior to
signing for the piece.
attachment to obtain the 5" spacing.
SKID –
The skid should be left on the
cabinet until it is near its final location.
The skid provides protection for both case
and floor.
Carefully remove packaging and
examine the cabinet for damage. If
damage is found, contact the delivering
carrier immediately and request that his
agent prepare an inspection report for the
The skid is removed by raising one
purpose of filing a claim. THIS IS YOUR end of the case approx. 6", block securely
RESPONSIBILITY, NOT THE
FACTORY’S.
and remove the 2 skid bolts on the raised
end – then screw back into the holes 2 leg
levelers.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
The procedure is repeated on the op- DRAINS –
posite end. When the leg levelers are in
place, the case may be slid off the skid and
placed in its final location.
Remote draining is not required in
self-contained models. The condensate
water from the evaporator drains out
through the bottom of the cabinet,
LEVELING –
through a copper trap attached to the un-
The cabinet must be leveled properly derside and into the condensing unit com-
to insure full drainage of condensate water partment to a heated condensate pan.
from the evaporator coil. Level the case
from front to rear and end to end. Stan-
Until this trap gets filled with wa-
dard levelers, packed inside the case, or op- ter from the initi al defrost, there may be a
tional legs can be provided for this purpose. small frost buildup in the coil area on
startup, which should disappear after the
SEALING –
first defrost. The pan uses a thermistor to
sense the presence of water in the pan and
Once the case is properly leveled, the adjusts the amount of heat required to
case should be sealed to the floor as shown
in the following drawing, using an NSF ap-
proved material such as General Electric
RTV-102 silicone sealer or equivalent.
evaporate the water.
LEGS (OPTIONAL) -
If required by Health Inspectors
the levelers can be removed and replaced
with NSF Approved legs to raise the cas e 6
inches for cleaning purposes. An optional
skirt kit can be provided to clip on to the
legs.
Silicone Sealant
Floor
ACCESS PANEL REMOVAL –
The louvered access panel on the
lower front of the case provides access to
the condensing unit, electrical box and con-
densate pan. Remove panel by removing
screw at bottom and lifting up and pulling
forward.
SERIAL PLATE –
The serial plate is located on the in-
terior top wall of the cabinet towards the
left end. It contains all pertinent informa-
tion such as model, cabinet serial number,
amperage rating, refrigerant type and
charge, etc. This information will be
needed to install, service, or order parts
for this piece of equipment.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
AIR DISTRIBUTION and PRODUCT
LOADING –
ELECTRICAL BOX –
The electrical box is located behind
This cabinet has a forced-air
circulation system. Air flows through the
back wall over the product on the shelves,
as well as out the honeycomb diffuser
located above the product, across the face
of the product (air curtain) and into the
return air grill.
the louvered access panel. The box is
capable of sliding out for service after the
hold down screw is removed.
The box contains the power switch
and defrost time clock.
POWER SWITCH –
Do not load product so that it
extends over the shelf edges or over the
return air grille.
The main power switch is located
behind the front louvered access panel on
the side of the electrical box. This power
switch controls all power to the case. THE
CABINET POWER SWITCH MUST BE
IN THE OFF POSITION BEFORE
STARTING ANY CLEANING OR
SERVICE WORK ON THE
POWER REQUIREMENTS –
The GSVM Models are equipped
for operation on a 115/60/1 power supply.
See chart in specifications for
requirements.
EQUIPMENT.
DEFROST TIME CLOCK –
It is very important for the safety of
both you and your customer to have each
circuit properly grounded. A qualified
electrician should perform all wiring in
accordance with the National Electrical
Code and/or all local codes. Separate
circuits are recommended for each case in
order to prevent product loss due to
overloading or malfunction of other
The time clock, located in the
electrical box, provides a definite off-time
so that the evaporator will clear itself of
frost.
The clock is provided with pins to
initiate defrost. The failsafe setting sets
the length of defrost (from 2 minutes
equipment on the same circuit. For proper minimum to 110 maximum).
operation of equipment, voltage as
measured at the compressor must not vary
The clock is factory pre-set for 3
more than 5% from the cabinet serial plate defrosts (at 6 a.m. , 2 p.m. and 10 p.m.)
rating. If either a high or low voltage
condition exists, contact your electrician,
local power company, or equipment
manufacturer.
on the 4060 and 4072 at 20 minutes
6
Download from Www.Somanuals.com. All Manuals Search And Download.
each. There are 4 defrost on the 5272 (2
a.m., 8 a.m., 2 p.m., and 8 p.m.) at 30
minutes each
b. Inspect the refrigeration lines for any
visible damage or chafing.
Additional defrost may be re-
quired for cases located in high humidity
or high usage cases. If possible, avoid
setting a defrost during the day, or peak
usage periods. THE CLOCK TIME
POINTER SHOULD BE SET TO THE
CORRECT TIME OF DAY WHEN
THE CABINET IS READY TO BE
STARTED.
c. Replace electrical box cover.
d. Replace the louvered access panel.
e. Start the cabinet and allow to pull
down to operating temperature before
loading.
Setting the timer – Extra pins are pro-
vided with the timer.
♦
♦
♦
Put pin in hole of dial face at the time
you wish the cabinet to defrost. Note
that there is an AM and PM section
on the dial face. Be sure the pin is
tight.
Set the length of time for the defrost
(failsafe). Push down on the adjust-
ment and slide it to the length of time.
Do not set the time longer than 60
minutes.
Set the time pointer to the proper
time of day and start cabinet.
CONNECTIONS -
a. Check cabinet thoroughly for loose
nuts and bolts and electrical connec-
tions.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
SPECIFICATIONS –
DIMENSIONS
Exterior
Width
30 5/8"
30 5/8"
30 5/8"
Model
Length
Height
60"
72"
GSVM-4060
GSVM-4072
GSVM-5272
40"
40"
52"
72"
ELECTRICAL
MODEL NO. Volts/Hz/Phase
REFRIGERANT
TYPE
RUN FUSE POWER
AMPS AMPS CORD
GSVM4060 115/60/1
GSVM4072 115/60/1
GSVM5272 115/60/1
GSVM5272 115/60/1
R-134a
R-134a
R-134a
R-404A
15
17
20
20
25
25
YES
NO
NO
17.25 25
NO **
** The GSVM-5272 changed to R404A in January 2000. Check the Serial Plate to verify
the correct refrigerant.
Note: Applies to the GSVM4072 & 5272 Models Only-Drain Plumbing hookup
recommended. Optional condensate is available if there is no access to drain plumbing.
Condensate pan must be field installed and requires a dedicated 15 amp, 120-volt circuit.
See page 15 for optional drain pan specifications.
BTU CAPACITY
RATING TEMPERATURE ºF
BTU/HR
EVAP
COND
AMBIENT
GSVM-4060
GSVM-4072
GSVM-5272
6200
6250
6300
20
20
20
110
110
110
90
90
90
Cabinets use R-134A or R-404A
SHELVING MAXIMUM WEIGHT CAPACITY (LBS) -
The following is a tabulation of the maximum evenly distributed weights that can be
applied on the respective shelves. They greatly exceed most normal food products that
could be displayed in the case
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Flat 1 1/2
Upslope
250#
17ºTilt
N/A
250#
30ºTilt
N/A
75#
Bottom Sheet Metal Area
Stand. 13”/15” shelves
250#
Stand. 13”/15” shelves w/optional
upslope 6º adapters
Optional Wire Baskets
125#
200#
N/A
100#
N/A
30#
See SHELVES for the special
loading instructions. Air flows out of the
honeycomb diffuser located above the
product, across the product, and into the
return duct. The honeycomb can be
removed for cleaning.
OPERATION and MAINTENANCE -
It is important that the two
previous sections of this installation
booklet have been read and followed
carefully before attempting to start up
the equipment.
TEMPERATURE CONTROL –
Interior cabinet temperatures are
controlled through the use of a bulb and
capillary type temperature control. The
control is located in the electrical box.
A thorough inspection should be
made prior to start up to assure that
there are no loose nuts, bolts, electrical
connections or refrigeration lines
rubbing or chafing. Turn the power
switch to the ON position. ALLOW
system to reach normal operating
temp.prior to
The sensing bulb is mounted on the
top of the evaporator coil on the 4060 and
4072. On the 5272 it is located on the rear
wall behind the evaporator coil. Be sure
to disconnect power supply prior to any
service work on the control.
loading any
product.
This cabinet
has a
forced-air
curtain that
flows over the
top of the
product.
The control is factory pre-set
between 19º and 21ºF for the GSVM4060,
4072 and - 26º to 28ºF on the GSVM5272 to
maintain between 35º and 40ºF interior
cabinet average temperatures.
The differential is set at 8-10ºF or
alittle over halfway towards “MAX”.
Donot adjust lower or evap. icing will
occur. It can be adjusted to other desired
temperatures by turning the dial to the
corresponding dial face temperatures. The
indicated dial temperature will not directly
Download from Www.Somanuals.com. All Manuals Search And Download.
correspond to the actual cabinet tempera-
ture due to the bulb location and depend-
has an additional 13” shelf as standard
which should be located above the 15”
ing on various conditions, a certain amount shelf also.
of time lag will be noticed between the new
setting and the resulting temperature.
The shelves should be positioned so
they do not protrude into the front (top to
bottom) air curtain. Do not use deeper
shelves or allow product to protrude over
CONDENSING UNIT –
A regular program should be set up the shelves into the air curtain.
for cleaning the fin-and-tube condenser.
Normally, this cleaning is required every 3 THERMOMETER –
to 4 months, but the individual store appli-
cation may shorten or lengthen this time
period. Dust and dirt accumulation can
cause serious efficiency loss.
A solar thermometer is provided
that registers degrees ºF. The thermome-
ter is located in the front center.
Access is gained to the unit area by
removing the louvered grille. Before at-
tempting to slide out condensing unit you
A solar powered thermometer is
equipped with each cabinet. The ther-
mometer is located in the top front center
must first remove the screws from the con- of the cabinet interior. Temperature is dis-
denser unit baffles. The unit slides for- played in Fahrenheit degrees as standard.
ward to facilitate cleaning and for service. Celsius display is available as an option.
Care should be taken when pushing the
unit back in, to insure that the pullout coil
does not become kinked or damaged in
some way. The baffle screws must be re-
placed after sliding the condensing unit
back into position. Double check to make
sure the drain hose is in the drain pan be-
fore putting the access grille back on. The
rear access panel is also removable if it is
necessary to work at the back of the case.
The thermometer may be replaced
by removing the two s crews securing the
thermometer to is mounting bracket. Re-
move the sensing element from the clip.
Install the new thermometer in reverse or-
der.
To clean the sensing element of the
thermometer, follow the same procedure
as replacement. Cleaning of the element is
accomplished by using water and mild de-
tergent. Be sure to wipe the element clean
SHELVES –
The GSVM4060 cabinet is equipped of any residues so proper temperatures are
with 2 standard shelves for the display of
your product. The 13” shelf should be lo-
cated at the top and 15” shelf should be lo-
cated below it. The GSVM5272 and 4072
displayed.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
LIGHTING –
Interior lighting is provided by a
cool white fluorescent bulb under the top
header (standard), and additional lights
under each shelf. The tubes are sleeved to
maintain proper heat around the bulb for
maximum light intensity and to protect the
product in case of breakage.
CLEANING EXTERIOR –
When cleaning the exterior of the
cabinet, use a soft cloth or sponges with
water and a mild detergent. Rinse and
wipe dry. Do not use an abrasive cleanser
on the painted surfaces as this will mar the
finish.
For plexiglass windows, use an ap-
proved plexiglass cleaner such as Craftics
20/20 Plasti-Cleaner.
The tubes can be replaced without
removing shelves or product. To replace
the bulb, twist the bulb and slide the
prongs clear of the lampholder. When re-
installing this type of bulb, be sure the
prongs on the bulb twist and lock into
place.
CLEANING INTERIOR –
For cleaning the interior of the
product compartment, remove the product,
disconnect the electrical power, and allow
cabinet to warm to room temperature. Use
a soft cloth or sponge with a mild detergent
to wash the interior.
LIGHT SWITCH (es) -
The standard case has one upper
light with a switch located under the top
left end behind the honeycomb. Addition-
ally, the lighting on each shelf has a sepa-
rate switch located under the center of
each shelf.
The drainage area and drain should
be checked to insure that they have not be-
come clogged. If the condensate drain hose
is removed from the electric condensate
pan for cleaning, it must be reinstalled
prior to operating the case. Do not use an
BALLAST (s) -
abrasive cleanser on the painted surfaces
The ballast for the top standard
light is located in the electrical box. Access
is gained by removing the access panel.
GSVM-4060 only has Electric Condensate Pan as Standard
Wipe dry before restarting the cabi-
net. The time clock (see Defrost Time
Clock section) should be reset to the correct
time of day. Allow the cabinet to cool down
to proper temperature before reloading
product.
Access to the shelving ballasts is gained by
removing the respective shelf (after un-
plugging the harness), and removing the
three screws from the ballast cover.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
CLEANING STAINLESS STEEL
SURFACES –
If it should become necessary to leak
test the system, please adhere to the follow-
ing notice:
Generally soap and water will be
sufficient for most cleanings when done of-
ten and regularly. When necessary, sev-
eral cleaning agents can be used. Some of
themare Comet, Bab-O, Liquid NuSteel,
Cooper’s Stainless Steel Cleaner, and Al-
len’s Stainless Steel Cleaner.
BECAUSE OF THE CFC ATMOS-
PHERIC CONSIDERATIONS BEING
TAKEN TODAY, WE ASK THAT LEAK
TESTING BE DONE WITH REFRIGER-
ANT 22 MIXED WITH NITROGEN
LEAK TESTING –
REFRIGERATION –
The test gas cylinder must be
equipped with a pressure gauge and regu-
lator so that system test pressures do not
exceed maximum allowable limits. Do not
ever use anything other than a R-22/
Nitrogen mixture for leak testing.
The GSVM models employ a refrig-
eration system using a hermetic compres-
sor. The GSVM4060 and GSVM4072 sys-
tems employ a capillary tube for refriger-
ant flow control. The capillary tube is sol-
dered to the suction line pull-out coil for
proper heat exchange. If the capillary
should become plugged or damaged for
some reason it is best to replace the whole
heat exchanger with a new one. Consult
the factory for the proper replacement.
Attach a refrigerant test gas cylin-
der to your service manifold and connect
the manifold to the charging port on the
liquid line valve.
Charge an R-22/Nitrogen mixture
into the system, raising the pressure to the
unit’s nameplate for the low side and high
side pressures. Using an electronic detec-
tor, carefully check the entire system for
leaks. Take special care to inspect all
brazed and flare connections.
The GSVM-5272 employs a bleed
port type expansion valve for proper re-
frigerant control.
As stated previously, these cases are self-
contained with the condensing unit
mounted at the bottom. They are
equipped with a hermetic compressor and
a capillary tube. The condenser is of fin
and tube construction and SHOULD BE
PERIODICALLY CLEANED TO MAIN-
TAIN EFFICIENT OPERATION.
EVACUATION –
After the system is proven leak
tig ht, thor oughly ev acu ate the syst em ac-
cording to the following procedure:
If for any reason the cabinet must
be recharged, consult the serial plate found
inside the cabinet for the proper refriger-
ant charge and weight.
a. Discharge the refrigerant-nitrogen mix-
ture, allowing it to blow from the sys-
tem as rapidly as possible, into any
empty cylinder.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Be sure that all service valves are open to al- into the system through a new drier in the
low all of the mixture to be discharged.
charging manifold line. A 16 cubic inch
drier is sufficient for this purpose.
b. Connect a deep-drain vacuum pump to
both the high and low side of the system. d. Repeat steps 2 and 3 two more times, the
Pull a vacuum on the system to at least
15 00 microns.
third time evacuating the system to 500
microns.
c. Break the vacuum by adding refrigerant
The following pressures are optimum
into the system until the pressure is above when the cas e in a 75º to 80ºF ambient and is
0 psig. Always charge the refrigerant line running from 35º to 40ºF cabinet tempera-
ture and are for reference only:
MODEL NO.
GSVM4060
REFRIGERANT SUCTION PRESSURE
HEAD PRESSURE
(psig)
TYPE
(psig)
12-15
R-134a
130-150
GSVM4072
R-134a
12-15
130-150
GSVM5272
GSVM5272
R-134a
R-404A
14-18
40-50
130-150
310-320
Consult the serial plate for the correct refrigerant charge. This charge is critical and
should be weighed in.
TEMPERATURE CONTROL –
The control also has an adjustable differen-
tial that determines the difference between
The temperature control is located in
the cut-in and cut-out temperature. This is
the electrical box. The sensing bulb is lo-
adjustable from 5 to 20º. The factory set-
cated on the left hand end of the lower back
ting is from 8-10º to insure proper off time
wall.
to keep the evaporator from icing.
When replacing make sure the bulb
is in the proper location and that the hole in
EVAPORATOR FAN MOTORS –
the liner is properly sealed after the replace-
To replace an evaporator fan motor,
ment has been made.
the product must be removed from the
cabinet and the bottom shelf also removed.
The control is adjustable from –30º to 50ºF
(dial face marking). The actual cabinet tem-
Next, remove the plate covering the
perature is approximately 6 to 9º warmer
fans by removing the 2 screws, and 4 bolts
than the control setting so this must be
holding this in place. The fans are now ac-
taken into consideration.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLE SHOOTING CHARTS
PROBABLE CAUSE
TROUBLE
SOLUTION
Compressor will not start no 1. Power disconnected
noise
1. Check service cord or
wiring connection.
2. Blown fuse or breaker
2. Replace fuse or reset
breaker
3. Defective or broken
wiring
3. Repair or replace
4. Defective overload
4. Replace
5. Replace
5. Defective temperature
control
Compressor will not start, 1. Low voltage
cuts out on overload
1. Check voltage at cabinet,
should not be more than 5%
below rating.
2. Defective compressor
3. Defective relay
2. Replace
3. Replace
4. Restriction (pinched cap 4. Repair or replace
tube)
5. Restriction (moisture)
5. Leak check, replace drier
evacuate and recharge
6. Condenser blocked with 6. Clean condenser
dust and dirt
7. Defective condenser fan 7. Replace
motor
Warm storage temperature 1. Temperature control not 1. Reset control
set properly
2. Short of refrigerant
2. Leak check, replace drier
evacuate and recharge
3. Cabinet location too
warm
3. Move to cooler location or
correct excessive heat source.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Refrigerant overcharge 4. Purge system, evacuate
and recharge.
5. Low voltage, compressor 5. Check voltage at
cycling on overload
compressor should not be
more than 5% below rating
Compressor runs
continuously. Product too
warm
1. Short of refrigerant
1. Leak check, replace drier,
evacuate and recharge
2. Inefficient compressor
1. Defective control
2. Replace
1. Replace
Compressor runs
continuously. Product too
cold
2. Control sensing element 2. Assure proper contact
not in positive contact
3. Short on refrigerant
3. Leak check, replace drier,
evacuate and recharge.
TROUBLE SHOOTING LIGHT CHART
PROBLEM
Lights won’t start
SOLUTION
1. Check light switch
2. Check continuity to ballast
3. Check to see if bulbs inserted properly in sockets
4. Check voltage
Lights flicker
1. Allow lamps to warm up
2. Check lamp sleeve for cracks
3. Check sockets for moisture and proper contact
4. Bulb replacement may be necessary
5. Check voltage
6. New bulbs tend to flicker until used
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Ballast Hums
1. Check voltage
2. Replace ballast
GSVM ACCESSORIES
The following is a description of the various accessories available for the GSVM,
including sketches, where applicable of the many shelving/wire goods items available.
CASTER KIT – Consists of 5" braking casters, which screw in to the standard threaded
holes in the four corners under the case occupied by the standard leg levelers, which will
have to be removed. The kit will add 5 5/8" to the height of the case.
LEG KIT – The legs also go into the same holes as the standard levelers, which will have to
be removed. The legs are adjustable and will add 5 5/16 to the height of the case. The skirt
kit requires the use of these legs.
4-SIDED SKIRT KIT – As stated, this is a 4-sided skirt that will enclose the open area
under the case when the leg kit is used. It clamps onto the legs.
NIGHT COVER – This is a clear, 5 mil. thick, polyester shade type of cover that will cover
the face of the case. It will fasten to the top of the case and be drawn to a snap fastener in
the area above the front bumper. The cover, although loose fitting on the ends, will
conserve energy during periods when the store is not open. The cover is standard on the
GSVM5272 effective August ’96.
WRAP-AROUND BUMPER KIT – This bumper replaces the standard front bumper and
warps around both sides of the case at the standard height of 22" to the centerline of the 2
1/4" wide bumper.
COLORED ACCENT PANEL – This panel can be (a) the top front panel over the product
or (b) the panel behind the bumper or (c) the access panel below the bumper panel, or any
combination of these.
SHELF END TRIM KIT – Consists of (4) painted steel ends for the standard 13" and 15"
shelves. This trim conceals and protects the exposed ends of the shelves, and attaches by
two snap fasteners supplied with each trim piece for the 4060. The 4072 and 5272 need 6.
HIGH HUMIDITY CONDENSATE PAN – (For GSVM4072 & 5272) This is a 1,000 watt,9
amp pan with a 6ft-9 in 115v power cord attached. Dedicated circuit required.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
SHELF UPSLOPE ADAPTER KIT – This kit consists of (4) zinc coated wire adapters to
increase the two standard shelves’ upslope from 1 1/2º to 6º.
PRICE TAG MOLDING KIT – This kit consists of aluminum price tag molding for the
standard shelves. This molding will hold both 1" and 1.235" standard price tags. (Note
that the standard shelves accept 1.235” tags).
WIRE PRODUCT STOP KIT – This kit consists of a 2” high chrome plated open wire
stops for the standard shelf. This stop is mounted under tension and should not be
confused with the wire front in the partition kit.
WIRE PARTITION KIT – This is a free standing wire system, which attaches to the
standard shelves, and consists of a wire front (different from the Product Stop), two wire
sides, and two partitions from the front to back, all chrome plated and 3" high.
WIRE CROSS DIVIDER – This is a 3" high x 4" long divider that could be ordered to be
used with the Wire Partition Kit above, in whatever quantities are desired.
WIRE BASKET KITS – One kit is available to replace the top 13" shelf (s) and another is
available to replace the bottom 15" shelf. Each kit consists of a wire basket, (2) brackets,
and two dividers, which could also be used as ends. These parts are zinc plated. The
baskets have an 8" high back and a 4" sloped front.
WIRE BASKET DIVIDERS – These are additional dividers which can be used with the
Wire Basket Kit to obtain additional partitioned areas in the baskets.
ADDITIONAL LIGHTED SHELF – This consists of an additional 13" lighted shelf that
can be positioned between the two standard shelves. It is the same construction as the top
standard 13" shelf.
WARRANTY AND PARTS INFORMATION
IMPORTANT – Please read carefully to assure prompt and accurate service.
ORDERING PARTS REPLACEMENT –
Contact your nearest Hussmann Distributor.
Always specify model and serial number of cabinet.
If correct part number is not know, give a clear description of part itself and its function in the cabinet or
remote unit.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
WARRANTY PARTS PROCEDURE
Same as first three items in Ordering Replacement Parts Procedure.
Give original installation date of cabinet and, if possible, forward a copy of the original invoice or delivery
receipt.
All shipments of in-warranty replacement parts will be invoiced from the factory until such time as the
defective part is returned and proved to be defective by our Quality Control Department.
Contact your Hussmann Distributor for instructions on returning in-warranty parts.
Warranty parts must be returned to the factory within 30 days of date of failure to assure proper disposition.
Lack of any of the above information may result in the shipment of the wrong part, or a delay in shipment.
COMPRESSOR REPLACEMENT PROCEDURE –
Replacement compressors will not be shipped from the Hussmann factory. They may be
obtained from you nearest Copeland Wholesaler.
Your wholesaler will replace, free of charge, any compressor found to be defective within
twelve months of installation, not to exceed twenty months from the date of
manufacture – as determined by the compressor serial number on the compressor serial
plate.
For any defective compressor beyond the twelve or twenty month time period, a salvage
value credit will be given too partially offset the invoice for the replacement.
To obtain reimbursement forward to: Hussmann Corporation
140 East State Street
Gloversville, NY
12078
the following information:
The cabinet model and serial number
2. A copy of the wholesaler’s invoice, along with a copy of the salvage value credit.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
UPPER LIGHT
LAMP
RED
WIRE HARNESS
RED
BLK
BLK
EVAP. FANS
LIGHT SWITCH
OPTIONAL
SHELF
COMPRESSOR
PROTECTOR
S
RED
C
BLK
LIGHT
2
1
#1 RELAY
LAMP
TEMP. CONTROL
TIME CLOCK
COND.
FAN
T
BALLAST
LIGHT SWITCH
BLK
STARTER
WHT
S
2
N
1
BLK
GRN
BLU
BLU
4
3
X
S
STD.
SHELF
LIGHT
WHT
BLK
LAMP
BALLAST
LIGHT SWITCH
BLK
WHT
WHT
WHT
BLK
BLK
WHT
S
STD.
SHELF
LIGHT
GRD
CONDENSATEPAN
LAMP
BLK
115 V
60 Hz
1 Ph
BALLAST
S3
S1
BLK
LIGHT SWITCH
BLK
POWER SWITCH
WHT
GRN
WHT
POWER CORD
ONE LIGHTED SHELF
GSVM 4060
TOLERANCESUNLESS
R
SHEET
SIZE
MATERIAL:
XXXXXX-XX
SIZE
OTHERWISE SPECIFIED.
FRACTIONAL
DECIMAL
1/32"
Gloversville,N.Y. 12078
0.031"
C
TITLE
ANGULAR
1ü
WIRING DIAGRAM
HOLE LOCATION
& SPACING
1/64"
XXXXXXXXXX
DWG. NUMBER
REV.
DRAWN
TYPE
CODE
JWL
2/11/94
XXX
SCALE:
FINISH
DATE
DIE NO.
X
M100-1938
REV.
BY
E.C.N.
DATE
XXXX-XXXX
X
CHECKED
XXXXXXXXXX
Download from Www.Somanuals.com. All Manuals Search And Download.
UPPER LIGHT
LAMP
RED
WIRE HARNESS
RED
BLK
BLK
EVAP. FANS
OPTIONAL
SHELF
LIGHT SWITCH
S
LIGHT
LAMP
COMPRESSOR
PROTECTOR
BALLAST
RED
C
BLK
2
LIGHT SWITCH
BLK
1
#1 RELAY
TEMP. CONTROL
TIME CLOCK
T
WHT
COND.
FAN
STD.
SHELF
LIGHT
S
STARTER
S
2
N
1
BLK
GRN
BLU
BLU
LAMP
4
3
X
WHT
BALLAST
BLK
LIGHT SWITCH
BLK
WHT
S
STD.
SHELF
LIGHT
WHT
LAMP
WHT
BLK
BLK
WHT
BALLAST
LIGHT SWITCH
BLK
WHT
BLK
115 V
60 Hz
1 Ph
S3
S1
BLK
GRN
OPTIONAL
CONDENSATE PAN
(1,000W,9A,120V)
S
POWER SWITCH
STD.
SHELF
LIGHT
WHT
LAMP
GSVM 4072
BALLAST
TOLERANCES UNLESS
OTHERWISE SPECIFIED.
R
SHEET
SIZE
MATERIAL:
XXXXXX-XX
SIZE
LIGHT SWITCH
BLK
FRACTIONAL
1/32"
Gloversville, N.Y. 12078
DECIMAL
ANGULAR
f
C
TITLE
f
WHT
WIRING DIAGRAM
HOLE LOCATION
& SPACING
f
XXXXXXXXXX
DWG. NUMBER
DRAWN
REV.
TYPE
CODE
JWL
2/11/94
XXX
-
SCALE:
FINISH
A
11/7/95
DATE
JWL
BY
DATE
DIE NO.
REV.
E.C.N.
M100-1935-1
XXXX-XXXX
X
CHECKED
XXXXXXXXXX
Download from Www.Somanuals.com. All Manuals Search And Download.
UPPER LIGHT
LAMP
RED
WIRE HARNESS
RED
EVAP. FANS
BLK
BLK
LIGHT SWITCH
OPTIONAL
SHELF
S
LIGHT
LAMP
COND.
FANS
PROTECTOR
#1 RELAY
RED
BLK
C
WHT
BLU
BALLAST
2
1
TEMP. CONTROL
TIME CLOCK
LIGHT SWITCH
BLK
COMPRESSOR
WHT
T
S
STARTER
STD.
S
SHELF
LIGHT
2
N
1
BLK
GRN
BLU
BLU
LAMP
4
3
X
WHT
BLU
WHT
BALLAST
BLK
LIGHT SWITCH
BLK
WHT
WHT
S
STD.
WHT
SHELF
BLK
BLK
LIGHT
LAMP
WHT
GRD
WHT
BLU
BALLAST
CONDENSATE PAN
LIGHT SWITCH
BLK
BLK
WHT
POWER SWITCH
S3
115 V
60 Hz
1 Ph
S1
BLK
GRN
WHT
S
STD.
SHELF
LIGHT
GSVM5272
LAMP
FIELD WIRING
USE COPPER CONDUCTORSONLY
WHT
BLU
TOLERANCES UNLESS
OTHERWISE SPECIFIED.
R
SHEET
SIZE
MATERIAL:
XXXXXX-XX
SIZE
BALLAST
FRACTIONAL
DECIMAL
1/32"
Gloversville,N.Y. 12078
0.031"
LIGHT SWITCH
C
TITLE
ANGULAR
1ü
BLK
WHT
WIRING DIAGRAM
HOLE LOCATION
& SPACING
1/64"
XXXXXXXXXX
DWG. NUMBER
REV.
DRAWN
TYPE
CODE
JWL
SCALE:
FINISH
A
5/18/94
DATE
JWL
BY
-
DATE
3/2/94
DIE NO.
A
M100-1872
REV.
E.C.N.
XXXX-XXXX
E
CHECKED
XXXXXXXXXX
XXX
Download from Www.Somanuals.com. All Manuals Search And Download.
UPPER LIGHT
LAMP
RED
WIRE HARNESS
RED
BLK
BLK
EVAP. FANS
OPTIONAL
SHELF
LIGHT SWITCH
S
LIGHT
LAMP
COND.
FANS
COMPRESSOR
R
BALLAST
RED
BLK
LIGHT SWITCH
BLK
C
TEMP. CONTROL
TIME CLOCK
T
1
WHT
STD.
SHELF
LIGHT
S
STARTER
S
2
N
1
BLK
GRN
BLU
BLU
LAMP
4
3
X
WHT
BALLAST
BLK
LIGHT SWITCH
BLK
WHT
S
STD.
SHELF
LIGHT
WHT
LAMP
WHT
BLK
BLK
WHT
BALLAST
LIGHT SWITCH
BLK
WHT
BLK
115 V
60 Hz
1 Ph
S3
S1
BLK
GRN
OPTIONAL
CONDENSATE PAN
(1,000W,9A,120V)
S
POWER SWITCH
STD.
SHELF
LIGHT
WHT
LAMP
GSVM 52072 (R-404A)
BALLAST
TOLERANCES UNLESS
OTHERWISE SPECIFIED.
R
SHEET
SIZE
MATERIAL:
XXXXXX-XX
SIZE
LIGHT SWITCH
BLK
FRACTIONAL
1/32"
Gloversville, N.Y. 12078
DECIMAL
ANGULAR
f
C
TITLE
f
WHT
WIRING DIAGRAM
DWG. NUMBER
HOLE LOCATION
& SPACING
f
XXXXXXXXXX
DRAWN
REV.
TYPE
CODE
JJH
-
SCALE:
FINISH
A
11/7/95
DATE
JWL
BY
DATE
12/19/07
DIE NO.
REV.
E.C.N.
M100-2185-1
XXXX-XXXX
X
CHECKED
XXXXXXXXXX
XXX
Download from Www.Somanuals.com. All Manuals Search And Download.
|