Hoshizaki Ice Maker DCM 300BAH OS User Manual

Hoshizaki America, Inc.  
Hoshizaki  
Cubelet Icemaker/Dispenser  
Models  
DCM-300BAH(-OS)  
SERVICE MANUAL  
“A Superior Degree  
of Reliability”  
Number: 73189  
Issued: 1-5-2012  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT  
This manual should be read carefully before the icemaker is serviced. Read  
the warnings and guidelines contained in this booklet carefully as they provide  
essential information for the continued safe use, service, and maintenance of the  
icemaker. Retain this booklet for any further reference that may be necessary.  
CONTENTS  
Important Safety Information ................................................................................................. 5  
I. Specifications...................................................................................................................... 7  
A. Icemaker ....................................................................................................................... 7  
II. General Information........................................................................................................... 8  
A. Construction.................................................................................................................. 8  
1. Icemaker .................................................................................................................. 8  
2. Icemaking Unit......................................................................................................... 9  
B. Sequence of Operation ............................................................................................... 10  
1. Sequence Cycles and Shutdown ........................................................................... 10  
a) Fill Cycle .......................................................................................................... 10  
b) Ice Purge Cycle................................................................................................ 10  
c) Freeze Cycle .................................................................................................... 10  
d) Drain Cycle ...................................................................................................... 10  
e) Shutdown......................................................................................................... 10  
2. Sequence Flow Chart.............................................................................................11  
C. Control Board.............................................................................................................. 12  
1. Control Board Layout ............................................................................................. 13  
a) DCM-300BAH................................................................................................... 13  
b) DCM-300BAH-OS............................................................................................. 14  
2. LED Lights and Components................................................................................. 15  
D. Power Switch, Control Switch, and Dispense Mode Switch ........................................ 15  
1. Power Switch.......................................................................................................... 15  
2. Control Switch........................................................................................................ 16  
a) ICE.................................................................................................................... 16  
b) DRAIN .............................................................................................................. 16  
3. Dispense Mode Switch ......................................................................................... 16  
a) CONTINUOUS.................................................................................................. 16  
b) PORTION ......................................................................................................... 16  
III. Technical Information...................................................................................................... 17  
A. Water Circuit and Refrigeration Circuit........................................................................ 17  
B. Wiring Diagrams.......................................................................................................... 18  
1. DCM-300BAH ....................................................................................................... 18  
2. DCM-300BAH-OS ................................................................................................ 19  
C. Performance Data ....................................................................................................... 20  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. Service Diagnosis........................................................................................................... 21  
A. Ice Production Check .................................................................................................. 21  
B. Diagnostic Procedure.................................................................................................. 21  
C. Control Board Check................................................................................................... 26  
D. Bin Control Check ....................................................................................................... 31  
E. Float Switch Check and Cleaning ............................................................................... 32  
1. Float Switch Check ................................................................................................ 32  
2. Float Switch Cleaning............................................................................................ 33  
F. Diagnostic Charts ........................................................................................................ 34  
V. Removal and Replacement of Components .................................................................... 38  
A. Service for Refrigerant Lines....................................................................................... 38  
1. Refrigerant Recovery ............................................................................................. 39  
2. Brazing .................................................................................................................. 39  
3. Evacuation and Recharge (R-404A)...................................................................... 39  
B. Important Notes for Component Replacement............................................................ 40  
1. Upper Bearing Wear Check .................................................................................. 42  
2. Removal and Replacement of Extruding Head...................................................... 42  
3. Removal and Replacement of Auger ..................................................................... 43  
4. Removal and Replacement of Evaporator............................................................. 43  
5. Removal and Replacement of Mechanical Seal and Lower Housing ................... 45  
6. Removal and Replacement of Gear Motor ............................................................ 46  
7. Dispense Auger and Agitator.................................................................................. 47  
8. Dispense or Agitating Motor................................................................................... 47  
VI. Cleaning and Maintenance............................................................................................. 48  
A. Cleaning and Sanitizing Instructions........................................................................... 49  
1. Water System......................................................................................................... 49  
a) Cleaning Solution............................................................................................. 49  
b) Cleaning Procedure ......................................................................................... 49  
c) Sanitizing Solution ........................................................................................... 50  
d) Sanitizing Procedure - Following Cleaning Procedure .................................... 50  
2. Dispense Components .......................................................................................... 51  
a) Cleaning Solution............................................................................................. 51  
b) Sanitizing Solution ........................................................................................... 51  
c) Cleaning and Sanitizing Procedure.................................................................. 51  
B. Maintenance................................................................................................................ 53  
C. Preparing the Icemaker for Periods of Non-Use.......................................................... 54  
VII. Disposal......................................................................................................................... 55  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important Safety Information  
Throughout this manual, notices appear to bring your attention to situations which could  
result in death, serious injury, damage to the appliance, or damage to property.  
WARNING  
NOTICE  
IMPORTANT  
Indicates a hazardous situation which could result in death or  
serious injury.  
Indicates a situation which could result in damage to the  
appliance or property.  
Indicates important information about the use and care of the  
appliance.  
WARNING  
This icemaker should be destined only to the use for which it has been expressly  
conceived. Any other use should be considered improper and therefore dangerous.  
The manufacturer cannot be held responsible for injury or damage resulting from  
improper, incorrect, and unreasonable use. Failure to service and maintain the  
appliance in accordance with this manual will adversely affect safety, performance,  
component life, and warranty coverage and may result in costly water damage.  
To reduce the risk of death, electric shock, serious injury, or fire, follow basic  
precautions including the following:  
• Only qualified service technicians should install and service this icemaker.  
To reduce the risk of electric shock, do not touch the control switch or power switch  
with damp hands.  
• Before Servicing: To reduce the risk of electric shock, move the control switch to  
the "OFF" position, then move the power switch to the "OFF" position. Turn off the  
power supply. Lockout/Tagout to prevent the power supply from being turned back  
on inadvertently.  
• This icemaker must be installed in accordance with applicable national, state, and  
local codes and regulations. Failure to meet these code requirements could result  
in death, electric shock, serious injury, re, or severe damage to equipment.  
• This icemaker requires an independent power supply of proper capacity. See the  
nameplate for electrical specifications. Failure to use an independent power supply  
of proper capacity can result in a tripped breaker, blown fuse, damage to existing  
wiring, or component failure. This could lead to heat generation or fire.  
THIS ICEMAKER MUST BE GROUNDED. Failure to properly ground the icemaker  
could result in death or serious injury.  
• Do not make any alterations to the icemaker. Alterations could result in electric  
shock, injury, re, or damage to the icemaker.  
• Do not place fingers or any other objects into the ice discharge opening.  
• This appliance is not intended for use by persons (including children) with reduced  
physical, sensory, or mental capabilities, or lack of experience and knowledge,  
unless they have been given supervision or instruction concerning use of the  
appliance by a person responsible for their safety.  
• Children should be properly supervised around this appliance.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTICE  
• Follow the instructions in this manual carefully to reduce the risk of costly water  
damage.  
• In areas where water damage is a concern, install in a contained area with a floor  
drain.  
• Install the icemaker in a location that stays above freezing. Normal operating  
ambient temperature must be within 45°F to 100°F (7°C to 38°C).  
• Do not leave the icemaker on during extended periods of non-use, extended  
absences, or in sub-freezing temperatures. To properly prepare the icemaker for  
these occasions, follow the instructions in "VI.C. Preparing the Icemaker for Periods  
of Non-Use."  
• Keep ventilation openings, in the appliance enclosure or in the built-in structure,  
clear of obstruction.  
• Do not place objects on top of the icemaker.  
• The storage bin is for ice use only. Do not store anything else in the storage bin.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
I. Specifications  
A. Icemaker  
1. DCM-300BAH(-OS)  
AC SUPPLY VOLTAGE  
COMPRESSOR  
GEAR MOTOR  
115-120/60/1  
115 V  
6.0 RLA  
29 LRA  
80 W  
16 W  
55 W  
55 W  
120 V  
115 V  
115 V  
115 V  
120 V  
20 A  
1.45 FLA  
0.8 FLA  
0.9 FLA  
0.9 FLA  
0.2 A  
FAN MOTOR  
AGITATING MOTOR  
DISPENSING MOTOR  
OTHER  
MAXIMUM FUSE SIZE  
MAX. HACR BREAKER (USA ONLY)  
MAX. CIRC. BREAKER (CANADA ONLY)  
MINIMUM CIRCUIT AMPACITY  
APPROXIMATE ICE PRODUCTION  
PER 24 HR.  
20 A  
20 A  
20 A  
Ambient  
Temp.(°F)  
70  
WATER TEMP. (°F)  
70  
50  
90  
lbs./day (kg/day)  
Reference without *marks  
*321 (146) 307 (139)  
277 (125) 263 (119)  
237 (107) *232 (105)  
203 (92) 193 (87)  
291 (132)  
249 (113)  
214 (97)  
*181 (82)  
80  
90  
100  
SHAPE OF ICE  
Cubelet (Compressed Flake Ice)  
88% (90/70°F, Conductivity 200 µS/cm)  
40 lbs.  
ICE HARDNESS FACTOR  
APPROXIMATE STORAGE CAPACITY  
ELECTRIC & WATER CONSUMPTION  
ELECTRIC W (kWH/100 lbs.)  
POTABLE WATER  
90/70°F  
661 (6.84)  
29 (12.5)  
70/50°F  
653 (4.88)  
40 (12.5)  
gal./24HR (gal./100 lbs.)  
EXTERIOR DIMENSIONS (WxDxH)  
EXTERIOR FINISH  
26"x22-1/2"x40" (661x571x1016)  
Stainless Steel; Galvanized Steel (Rear)  
WEIGHT  
CONNECTIONS - ELECTRIC  
- WATER SUPPLY  
Net 215 lbs. (98 kg), Shipping 240 lbs. (109 kg)  
Permanent Connection  
Inlet 1/2" FPT  
- DRAIN  
Drain Pan 3/4" FPT  
Bin Drain 3/4" FPT  
ICE MAKING SYSTEM  
Auger Type  
HARVESTING SYSTEM  
ICE MAKING WATER CONTROL  
COOLING WATER CONTROL  
BIN CONTROL SYSTEM  
COMPRESSOR  
Direct Driven Auger (80 W Gear Motor)  
Float Switch  
N/A  
Mechanical Bin Control (Proximity Switch)  
Hermetic, Model ASE24C3E-IAA-257  
Air-Cooled, Fin and Tube Type  
Copper Tube on Cylinder  
Thermostatic Expansion Valve  
R-404A, 15.9 oz. (450 g)  
High 460 PSIG, Low 290 PSIG  
High Voltage Cut-Out (Internal)  
Auto-Reset External Protector  
Manual Reset Circuit Breaker  
Auto-Reset High-Pressure Switch  
Float Switch and Timer  
Spare Fuse  
CONDENSER  
EVAPORATOR  
REFRIGERANT CONTROL  
REFRIGERANT CHARGE  
DESIGN PRESSURE  
P.C. BOARD CIRCUIT PROTECTION  
COMPRESSOR PROTECTION  
GEAR MOTOR PROTECTION  
REFRIGERANT CIRCUIT PROTECTION  
LOW WATER PROTECTION  
ACCESSORIES - SUPPLIED  
- OPTIONAL  
Legs  
OPERATING CONDITIONS  
VOLTAGE RANGE  
104-127VAC  
AMBIENT TEMP.  
WATER SUPPLY TEMP.  
WATER SUPPLY PRESSURE  
45-100°F  
45-90°F  
10-113 PSIG  
Note: We reserve the right to make changes in specifications and design without prior  
notice.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
II. General Information  
A. Construction  
1. Icemaker  
Thermostatic Expansion Valve  
Spout A  
Evaporator Assembly  
Inlet Water Valve  
Spout B  
Bin Control Actuator  
Storage Bin  
Bin Control  
Proximity Switch  
Float Switch  
Reservoir  
Agitator  
Control Box  
Power Switch  
Gear Motor  
Ice Dispense  
Auger  
4A1038-014  
CONTROL  
ICE  
Agitating Motor  
OFF  
DISPENSE MODE  
PORTION  
DRAIN  
CONTINUOUS  
Dispense Motor  
Compressor  
Air-Cooled Condenser  
Shutter Assembly  
Safety Switch  
Spout Cover  
Dispense Water Valve  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Icemaking Unit  
Cutter  
Extruding Head and  
Upper Bearing  
Seal Bolts and Washers  
Auger  
Evaporator  
Socket Head Cap Screw  
and Split Lock Washer  
Mechanical Seal  
Housing and Lower  
Bearing  
O-Ring  
Spline Coupling  
Hex Bolt and Washer  
Gear Motor  
Socket Head Cap Screw  
and Split Lock Washer  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Sequence of Operation  
1. Sequence Cycles and Shutdown  
The steps in the sequence are as outlined below. When power is supplied, power switch  
is in the "ON" position, safety switch is engaged, and the control switch is in the "ICE"  
position, CB "POWER" LED turns on. The "POWER" LED indicates control voltage and  
will remain on unless a control voltage problem occurs. If icemaker does not start, BC  
actuator and proximity switch may be engaged. Move the dispense mode switch to the  
"CONTINUOUS" position, then dispense ice to lower the level of ice in the storage bin.  
a) Fill Cycle  
Reservoir is empty. LF/S and UF/S are open. WV energizes and fill cycle starts.  
LF/S closes. Nothing happens at this time. Reservoir continues to fill until UF/S closes.  
When UF/S closes, WCR energizes, closing low water safety circuit and de-energizing  
WV. GM energizes once UF/S closes.  
b) Ice Purge Cycle  
"GM" LED is on. GM energizes. 60-sec. ice purge timer starts. Note: GM cannot  
energize unless UF/S is closed.  
c) Freeze Cycle  
"COMP" and "GM" LEDs are on. 60-sec. ice purge timer terminates. GM continues.  
CB confirms GM operation through GMPR terminal #3 (BR wire) and terminal  
#5 (DBU wire), then Comp and FM energize. Ice production starts 4 to 6 min. after Comp  
energizes depending on ambient and water temperature conditions. UF/S and LF/S  
operate WV as needed to continue the icemaking process. Refill: As ice is produced the  
water level in the reservoir drops. UF/S opens. Nothing happens at this time. LF/S opens.  
FT starts. WCR de-energizes, energizing WV. As water fills the reservoir, LF/S closes.  
Nothing happens at this time. Water continues to fill and UF/S closes. FT terminates and  
WCR energizes, closing low water safety circuit and de-energizing WV. If UF/S remains  
open longer than 90 sec. after LF/S opens (FT exceeded), Comp and FM de-energize.  
GM de-energizes 60 sec. later. WV remains energized until UF/S closes. The freeze cycle  
continues until BC shuts the icemaker down, a drain cycle occurs, or power is turned off  
to the icemaker.  
d) Drain Cycle  
"FLUSH" LED is on. The drain cycle occurs once every 12 hrs. for 20 min.  
12-hr. DCT terminates, DVT starts. Comp and FM de-energize. GM de-energizes 60 sec.  
later. DV energizes. DV remains energized for the remainder of the drain cycle.  
e) Shutdown  
BC activates, 150-sec. shutdown sequence starts. After 90 sec., Comp and FM  
de-energize, AM energizes for 0.6 seconds, 60 sec. later, GM de-energizes.  
Legend: AM–agitating motor; BC–bin control; CB–control board; Comp–compressor;  
DCT–drain cycle timer (12-hr. timer); DV–drain valve; DVT–drain valve  
timer (20-min. timer); FM–fan motor; FT–fill timer (90-sec. low water safety);  
GM–gear motor; GMPR–gear motor protect relay; LF/S–lower float switch;  
UF/S–upper float switch; WCR–water control relay; WV–inlet water valve  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Sequence Flow Chart  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Control Board  
A Hoshizaki exclusive control board is employed in Hoshizaki icemakers.  
All models are pre-tested and factory adjusted.  
For a control board check procedure, see "IV.C. Control Board Check Procedure."  
NOTICE  
• The control board is fragile; handle very carefully.  
• The control board contains integrated circuits, which are susceptible to failure  
due to static discharge. It is especially important to touch the metal part of the  
icemaker before handling or replacing the control board.  
• Do not touch the electronic devices on the control board or the back of the control  
board.  
• Do not change wiring and connections. Do not misconnect terminals.  
• Do not short out power supply to test for voltage.  
• Always replace the whole control board assembly if it goes bad.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Control Board Layout  
a) DCM-300BAH  
"DCM-PB" Push Button Model Control Board  
• Ice Dispense Time Control • Counter Reset Button  
(not used in this application)  
• Relay LEDs (red)  
• "FLUSH" (drain) Switch  
(indicate which relays  
and connector pins are  
energized)  
(Do not adjust)  
K3 Connector  
#3 24VAC Output to  
Control Switch,  
• "FLUSH" (drain) LED  
(X5 Relay)  
K2 Connector Pin #8  
12-hr. Drain Timer  
K3 Connector Pin #3  
Control Switch  
"DRAIN" Position  
• "DM" LED (X4 Relay)  
K2 Connector Pin #6  
Inlet Water Valve,  
Water Control Relay,  
and Drain Valve  
• K2 Connector  
#1, 2 Gear Motor  
Protect Relay Circuit  
(5VDC)  
#3 Power Supply Input  
(115VAC)  
• "AM" LED (X3 Relay)  
#4 "AM" LED: Agitating Motor  
(115VAC)  
#5 Power Supply Input  
(115VAC)  
K2 Connector Pin #4  
• "COMP" LED (X2 Relay)  
X2 Relay Terminals (115VAC)  
#6 "DM" LED: Ice Dispense  
Solenoid and Motor  
(115VAC)  
• "GM" LED (X1 Relay)  
K1 Connector Pin "NO"  
#7 Control Transformer  
(24VAC)  
#8 "FLUSH" (drain) LED:  
Drain Valve (After 12-hr.  
timer terminates) (24VAC)  
• K4 Connector  
#1, 2 Control Transformer  
(10.5VAC)  
#3, 4 Bin Control,  
Control Switch "ICE",  
and Water Control  
Relay Circuit (5VDC)  
#5 Ice Dispense Continuous  
Operation (5VDC)  
#6, 8 Ice Dispense Switch  
and Dispense Mode  
Switch (5VDC)  
#7 Ice Dispense Portion  
Operation (5VDC)  
#9, 10, High-Pressure Switch  
(5VDC)  
• "POWER" LED (green)  
(lights when 10.5VAC is  
supplied to K4 connector  
pins #1 & #2)  
K1 Connector  
"COM" Power Supply Input  
(115VAC)  
"NO" "GM" LED: Gear Motor  
and Gear Motor  
Control Board  
Protect Relay  
Part Number 2A1592-01  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b) DCM-300BAH-OS  
"DCM-OS" Opti-Serve Model Control Board  
• Relay LEDs (red)  
(indicate which relays  
and connector pins are  
energized)  
• Ice Dispense Time Control  
• "FLUSH" (drain) LED  
(X6 Relay)  
K2 Connector Pin #10  
12-hr. Drain Timer  
K3 Connector Pin #3  
Control Switch  
"DRAIN" Position  
• "WTR" LED (X5 Relay)  
K2 Connector Pin #8  
K3 Connector  
#3 24VAC Output to  
Control Switch,  
Inlet Water Valve,  
Water Control Relay,  
and Drain Valve  
• "COUNTER RESET" Button  
(not used in this application)  
• "ICE" LED (X4 Relay)  
K2 Connector Pin #6  
• "FLUSH" (drain) Switch  
(Do not adjust)  
• "AM" LED (X3 Relay)  
K2 Connector Pin #4  
• K2 Connector  
#1, 2 Gear Motor  
Protect Relay Circuit  
(5VDC)  
#3 Power Supply Input  
(115VAC)  
• "COMP" LED (X2 Relay)  
X2 Relay Terminals (115VAC)  
• "GM" LED (X1 Relay)  
K1 Connector Pin "NO"  
#4 "AM" LED: Agitating Motor  
(115VAC)  
#5 Power Supply Input  
(115VAC)  
#6 "ICE" LED: Ice Dispense  
Solenoid and Motor  
(115VAC)  
• K5 Connector  
#1, 2, 3 Ice Dispense  
Mode Switch, Portion  
Operation (5VDC)  
#4, 5, 6 Ice Dispense  
Mode Switch, Continuous  
Operation (5VDC)  
#7, 9 Control Transformer  
(24VAC)  
#8 "WTR" LED:  
#7, 8, 9 Water Dispense  
Sensor (5VDC)  
Water Dispense Valve  
(24VAC)  
• K4 Connector  
#1, 2 Control Transformer  
K1 Connector  
"COM" Power Supply Input  
(115VAC)  
"NO" "GM" LED: Gear Motor  
and Gear Motor  
#10 "FLUSH" (drain) LED:  
Drain Valve (After 12-hr.  
timer terminates) (24VAC)  
• "POWER" LED (green)  
(lights when 10.5VAC is  
supplied to K4 connector  
pins #1 & #2)  
(10.5VAC)  
#3, 4 Bin Control,  
Control Switch "ICE",  
and Water Control  
Relay Circuit (5VDC)  
#5, 6 High-Pressure Switch  
(5VDC)  
Protect Relay  
Control Board  
Part Number 2A2649-01  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. LED Lights and Components  
The "POWER" LED indicates control voltage and will remain on unless a control voltage  
problem occurs. For further details, see "II.B. Sequence of Operation."  
Icemaking  
Energized  
Components  
Time LEDs are Frequency LEDs are  
On On  
Cycle (Relay)  
LED  
Fill  
-
WV  
GM  
N/A  
60 sec.  
N/A  
N/A  
N/A  
N/A  
Ice Purge (X1)  
Freeze (X1, X2)  
GM  
GM, COMP  
GM, Comp, FM  
Drain  
(X5 push button)  
(X6 OS)  
FLUSH (drain) DV  
20 min.  
Every 12 hr.  
Ice/Water Dispense  
Energized  
Component  
Time LEDs are Frequency LEDs are  
Relay  
LED  
On  
On  
Push Button  
DM  
Opti-Serve  
Ice Dispense (X4)  
DM, DS  
60 sec. max.  
N/A  
ICE  
Every 12 sec. of  
accumulative dispense  
time  
Agitating Motor (X3) AM  
AM  
0.6 sec.  
N/A  
Water Dispense (X5)  
WTR  
DispWV  
N/A  
(Opti-Serve Only)  
Legend: AM–agitating motor; Comp–compressor; DispWV–dispense water valve  
("WTR" LED on DCM-300BAH-OS); DM–dispense motor; DS–dispense  
solenoid; DV–drain valve; FM–fan motor; GM–gear motor; WV–inlet water valve  
D. Power Switch, Control Switch, and Dispense Mode Switch  
The power switch, control switch, and dispense mode switch are used to control the  
operation of this icemaker.  
1. Power Switch  
The power switch has 2 positions, "OFF" and "ON." WARNING! 115VAC power supply  
is present on control board K1 connector pin "COM" and the control board  
X2 relay (gear motor) (BR wire) when the power switch is in the "OFF" position.  
When the power switch is in the "OFF" position, no power is  
supplied to the control transformer or control board K2 connector  
pin #3 and the K2 connector pin #5.  
When the power switch is in the "ON" position, 115VAC power supply is directed  
to the control transformer and control board K2 connector pin #3 (BK wire) and  
pin #5 (BK wire). The control board then directs 24VAC from the K3 connector  
pin #3 (DBU wire) to one side of the double-pole double-throw control switch, at the  
same time, the control board directs 5VDC from the K4 connector pin #4 (V wire) to the  
other side of the control switch.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Control Switch  
The control switch is a double-pole double-throw switch with 3 positions, "ICE," "OFF,"  
and "DRAIN."  
a) ICE  
When the control switch is in the "ICE" position, the control switch directs 5VDC from  
control board K4 connector pin #3 to control board K4 connector pin #4. When the  
control board receives 5VDC on K4 connector pin #4, the icemaking process starts.  
b) DRAIN  
When the control switch is in the "DRAIN" position, the control switch directs  
24VAC power supply to the drain valve and breaks the 5VDC to the control board  
K4 connector pin #4.  
CONTROL  
ICE  
OFF  
DRAIN  
3. Dispense Mode Switch  
The dispense mode switch has 2 positions, "CONTINUOUS" and "PORTION."  
a) CONTINUOUS  
When the dispense mode switch is in the "CONTINUOUS" position, ice dispenses  
continuously for a maximum of 60 seconds per activation.  
b) PORTION  
When the dispense mode switch is in the "PORTION" position, ice dispenses for the  
amount of time determined by the ice dispense time setting.  
DISPENSE MODE  
PORTION  
CONTINUOUS  
The ice dispense time control is located on the control board. The dial indicates  
dispense time in seconds and is adjustable between 0.6 and 20 seconds. When  
shipped, the ice dispense time control is set to the minimum dispense time of 0.6 sec.  
(approximately 0.72 oz.).  
Ice Dispense Time Control  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III.Technical Information  
A. Water Circuit and Refrigeration Circuit  
Inlet  
Spout  
Water  
Valve  
Water Supply  
Float Switch  
Water Level  
Reservoir  
Overflow  
Evaporator  
Drier  
Expansion  
Valve  
To Drain  
Drain  
Valve  
Gear Motor  
Dispense  
Water Valve  
Fan Motor  
Condenser  
High-Pressure Switch  
Access  
Valve  
Access  
Valve  
Compressor  
Refrigeration Circuit  
Water Circuit  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Wiring Diagrams  
1. DCM-300BAH  
*
* High-Pressure Switch  
412 21 PSIG  
Cut-out  
Cut-in  
0
327 21 PSIG  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. DCM-300BAH-OS  
*
* High-Pressure Switch  
412 21 PSIG  
Cut-out  
Cut-in  
0
327 21 PSIG  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Performance Data  
1. DCM-300BAH(-OS)  
APPROXIMATE  
ICE PRODUCTION  
PER 24 HR.  
Ambient  
Temp. (°F)  
Water Temp. (°F)  
70  
50  
90  
70  
80  
90  
100  
70  
80  
321  
277  
237  
203  
653  
656  
660  
146  
125  
107  
92  
--  
307  
263  
232  
193  
654  
658  
661  
139  
119  
105  
87  
--  
291  
249  
214  
181  
655  
659  
666  
132  
113  
97  
82  
--  
lbs./day kg/day  
APPROXIMATE ELECTRIC  
CONSUMPTION  
--  
--  
--  
--  
--  
--  
90  
watts  
100  
70  
671  
40  
35  
30  
25  
19  
19  
23  
--  
675  
38  
33  
29  
24  
19  
23  
23  
--  
680  
36  
31  
27  
23  
19  
23  
25  
--  
APPROXIMATE WATER  
CONSUMPTION PER 24 HR.  
152  
131  
112  
96  
145  
124  
110  
91  
138  
118  
101  
86  
80  
90  
gal./day l/day  
100  
70  
EVAPORATOR OUTLET TEMP  
-7  
-7  
-7  
80  
-7  
-5  
-5  
90  
-5  
-5  
-4  
°F °C  
100  
25  
-4  
25  
-4  
25  
-4  
HEAD PRESSURE  
70  
80  
90  
100  
70  
200  
237  
273  
315  
37  
14.1  
16.6  
19.2  
22.1  
2.6  
200  
237  
273  
315  
37  
14.1  
16.6  
19.2  
22.1  
2.6  
200  
237  
273  
315  
37  
14.1  
16.6  
19.2  
22.1  
2.6  
PSIG kg/cm²G  
SUCTION PRESSURE  
80  
39  
2.7  
39  
2.7  
39  
2.7  
90  
41  
2.9  
41  
2.9  
41  
2.9  
PSIG kg/cm²G  
100  
45  
3.2  
45  
3.2  
45  
3.2  
TOTAL HEAT OF REJECTION 3,500 BTU/h (AT 90°F /WT 70°F)  
Note:  
1. Pressure data is recorded at 5 minutes into freezing cycle. The data not in bold  
should be used for reference only.  
2. We reserve the right to make changes in specifications and design without prior  
notice.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IV. Service Diagnosis  
WARNING  
• This icemaker should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
• Risk of electric shock. Use extreme caution and exercise safe electrical practices.  
• Moving parts (e.g., fan blade) can crush and cut. Keep hands clear.  
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are  
securely in place after the icemaker is serviced. Make sure that none have fallen  
into the storage bin.  
• Make sure all food zones in the icemaker and storage bin are clean after  
the icemaker is serviced. For cleaning procedures, see "VI. Cleaning and  
Maintenance."  
A. Ice Production Check  
To check production, prepare a bucket or pan to catch the ice and a set of scales  
to weigh the ice. After the icemaker has operated for 10 to 20 minutes, catch the ice  
production for 10 minutes. Weigh the ice to establish the batch weight. Multiply the batch  
weight by 144 for the total production in 24 hr.  
B. Diagnostic Procedure  
This diagnostic procedure is a sequence check that allows you to diagnose the electrical  
system and components. Before proceeding, check for correct installation, adequate  
water pressure (10 to 113 PSIG), and proper voltage per unit nameplate. Check that  
the 24VAC 1A fuse and the 10.5VAC 0.5A fuse are good. When checking high-voltage  
(115VAC), always choose a neutral (W wire) to establish a good neutral connection.  
When checking low-voltage (24VAC and 10.5VAC), always choose a neutral (LBU wire)  
from CT to establish a good neutral connection. WARNING! LBU wires are used  
in both high-voltage and low-voltage applications. When checking low-voltage  
(24VAC and 10.5VAC) confirm that the neutral (LBU wire) being used is the LBU  
wire from CT, not the 115VAC power LBU wire used for Comp/FM operation or the  
24VAC LBU wire on the control switch to GMPR (DV operation).  
When checking DC-voltage (5VDC), use CB K3 connector pin #1 for DC ground (GND).  
CB "POWER" LED remains on unless power supply is interrupted. IMPORTANT!  
Icemaker will not start unless the front panel safety switch is engaged.  
1) Turn on the power supply. Remove the front panel. Move the power switch to the "ON"  
position, then move the control switch to the "DRAIN" position. Engage the safety  
switch.  
2) Allow the water system to drain for 5 minutes. If water does not drain from the icemaker,  
see step 12 Drain Cycle below.  
3) Disengage the safety switch, then move the control switch to the "OFF" position.  
4) Move the power switch to the "OFF" position.  
5) Remove the control box cover.  
6) Engage the safety switch.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7) Startup – Move the power switch to the "ON" position, then move the control switch to  
the "ICE" position to start the automatic icemaking process. Diagnosis: Check that CB  
"POWER" LED is on. If not, check for proper power supply voltage (115VAC) input to  
CT. If 115VAC is not present, check the breaker, power switch, and front panel safety  
switch. Next, check that the power protect relay is de-energized and contacts between  
terminals #6 (BR wire) and #2 (BK wire) are closed. Check for proper control voltage  
(10.5VAC) output from CT to CB K4 connector pin #1 (BR wire) to CB K4 connector pin  
#2 (LBU wire). If 10.5VAC is not present and 10.5VAC 0.5A fuse is good, replace CT. If  
10.5VAC is present and "POWER" LED is off, replace CB.  
8) Fill Cycle – Reservoir is empty. LF/S and UF/S are open. WV energizes and fill cycle  
starts. LF/S closes. Nothing happens at this time. Reservoir continues to fill. UF/S  
closes. WCR energizes, closing low water safety circuit (WCR terminals #6 (GY wire)  
and #4 (O wire)) and de-energizing WV. GM energizes. Diagnosis: If reservoir is empty  
and WV is off, confirm LF/S status. See "IV.E. Float Switch Check and Cleaning." Check  
that WV energizes and water fills the reservoir. If not, check that the water supply line  
shut-off valve is open, possible clogged water filters, and clogged WV screen. If LF/S  
is open and WV is off, check for 24VAC at CB K2 connector pin #7 (R wire) to CB  
K2 connector pin #8 (LBU wire). If 24VAC is not present and the 24VAC 1A fuse is  
good, replace CT. If 24VAC is present, check for 24VAC at K3 connector pin #3 (DBU  
wire) to a neutral (LBU wire). If 24VAC is not present, replace CB. If 24VAC is present,  
check for 24VAC at the control switch (R wire) to a neutral (LBU wire). If 24VAC is not  
present, make sure the control switch is in the "ICE" position. Replace the control switch  
if defective. If 24VAC is present, check for 24VAC at WCR terminal #1 (BR wire) to WCR  
terminal #5 (R wire). If 24VAC is present, WCR is energized or defective. If energized,  
check that UF/S is open. See "IV.E. Float Switch Check and Cleaning." If not energized,  
replace WCR. If 24VAC is not present, check WCR terminal #1 (BR wire) to a neutral  
(LBU wire). If 24VAC is present, check WV solenoid wire connections and continuity.  
If WV is energized and refill exceeds FT with no water in the reservoir, check for DV  
leaking. If reservoir is full and overflowing check for open UF/S. See "IV.E. Float Switch  
Check and Cleaning." If UF/S is closed, check that WCR energizes, de-energizing WV.  
If not, check for 24VAC at WCR terminal #7 (BK wire) to WCR terminal #8 (LBU wire). If  
24VAC is present and WV does not de-energize, replace WCR. If WV de-energizes and  
water continues to fill the reservoir, replace WV.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9) Ice Purge Cycle "GM" LED is on. GM and GMPR energize. 60-sec. ice purge timer  
starts. GM runs for 60 sec. to clear any ice from the evaporator. Note: GM cannot  
energize unless UF/S is closed, WCR is energized, and WCR terminals #4 (O wire)  
and #6 (GY wire) are closed. Diagnosis: If "GM" LED is off, check control switch and  
BC continuity. If either are open, CB "GM" LED will not turn on. If both are closed  
and CB "GM" LED does not turn on, replace CB. If "GM" LED turns on and GM does  
not energize, check for 115VAC at CB K1 connector NO pin (DBU wire) to a neutral  
(W wire). If 115VAC is not present, replace CB. If 115VAC is present, check GM external  
protector (overload), GM windings continuity, and GM capacitor. If GM external protector  
or GM internal protector is open, allow to cool and reset. If reset does not occur, replace  
as needed. If GM winding is open, replace GM. If GM energizes, but auger does not  
turn, check coupling between auger and GM. If Comp energizes at the same time GM  
energizes, check CB. See "IV.C. Control Board Check."  
10) Freeze Cycle "COMP" and "GM" LEDs are on. 60-sec. ice purge timer terminates.  
GM continues. CB confirms GM operation through GMPR terminal #3 (BR wire) and  
terminal #5 (DBU wire). Comp and FM energize. Ice production begins 4 to 6 min.  
after Comp and FM energize depending on ambient and water temperature conditions.  
Diagnosis: 60 sec. after GM energizes, confirm Comp LED turns on and Comp and  
FM energize. If not, check that GMPR is energized (115VAC). Next, check continuity  
between GMPR terminal #3 (BR wire) and terminal #5 (DBU wire). If open, GMPR  
is de-energized or contacts are stuck open. If closed, and "COMP" LED, Comp, and  
FM do not energize, replace CB. If "COMP" LED turns on and Comp and FM do not  
energize, confirm 115VAC at CB X2 relay (BR wire) to a neutral (W wire). If 115VAC is  
not present, check connections. If 115VAC is present, confirm 115VAC at CB X2 relay  
light blue (LBU wire) to a neutral (W wire). If 115VAC is not present and "COMP" LED is  
on, replace CB. If 115VAC is present, check Comp external protector (overload), allow to  
cool and reset. If reset does not occur, replace as needed. Check Comp motor windings  
continuity and Comp capacitor. Check FM for binding and FM winding continuity.  
11) Refill /Low Water Safety – As ice is produced the water level in the reservoir drops.  
UF/S opens. Nothing happens at this time. LF/S opens. FT starts. WCR de-energizes,  
energizing WV. Comp, FM and GM continue. As water fills the reservoir, LF/S closes.  
Nothing happens at this time. UF/S closes. FT terminates. WCR energizes, closing  
low water safety circuit and de-energizing WV. This continues until BC shuts the  
icemaker down, a drain cycle occurs, or power is turned off to the icemaker.  
Diagnosis: Confirm that the water level has dropped and UF/S and LF/S are open.  
See "IV.E. Float Switch Check and Cleaning." Check that the reservoir fills. If not, check  
for water supply line shut-off valve closed, clogged water filters, dirty or sticking F/S,  
clogged WV screen, defective WCR, defective WV coil, and DV leaking by. For further  
information, see "IV.B.8) Fill Cycle." If UF/S remains open longer than 90 sec. after LF/S  
opens (FT exceeded), Comp and FM de-energize. GM de-energizes 60 sec. later. WV  
continues until UF/S closes.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12) Drain Cycle "FLUSH" (drain) LED is on. The icemaker drains the evaporator and  
reservoir once every 12 hr. A manual drain is provided when cleaning the icemaker by  
moving the control switch from the "ICE" position to the "DRAIN" position.  
a) Automatic Drain Cycle: A drain cycle occurs once every 12 hr. for 20 min.  
DCT terminates and DVT starts. If the icemaker is not running when DCT terminates,  
DV energizes immediately. If the icemaker is running when DCT terminates, Comp  
and FM de-energize. GM de-energizes 60 sec. later, then DV energizes. Once  
DVT terminates, DCT resets and DV de-energizes. Fill cycle starts. DCT resets  
every time the power supply is turned off and on again. Diagnosis: Once GM  
de-energizes, DV energizes. If not, check for 24VAC at the control switch (LBU wire)  
to a neutral (LBU wire). If 24VAC is not present, replace CB. If 24VAC is present,  
check for 24VAC at GMPR terminal #2 (P wire) to a neutral (LBU wire). If 24VAC is  
not present, GMPR is energized or defective. If GMPR is energized, confirm GM is  
off. If not, DCT has not terminated or 60-sec. shutdown sequence is not complete.  
If 60-sec. shutdown is complete and GM is still energized, replace CB. If 24VAC is  
present, check for 24VAC on DV. If 24VAC is present and DV does not energize,  
check DV solenoid continuity.  
b1) Manual Drain: 150-sec. shutdown sequence: Move the control switch to the  
"DRAIN" position. The 150-sec. shutdown sequence starts. 90 sec. after moving  
the control switch to the "DRAIN" position, Comp and FM de-energize, 60 sec.  
later GM de-energizes and DV energizes. DV continues until the control switch is  
moved to the "OFF" or "ICE" position or power is turned off. Diagnosis: Once GM  
de-energizes, DV energizes. If not, check for 24VAC at CB K3 connector pin #3 (DBU  
wire) to a neutral (LBU wire). If 24VAC is not present, confirm 24VAC power supply  
to CB K2 connector pin #7 (R wire) on push button model and pin #9 (R wire) on  
Opti-Serve model to a neutral (LBU wire). If 24VAC is present on CB K2 pin #7 (push  
button model) or pin #9 (Opti-Serve model) and not on CB K3 connector pin #3 (DBU  
wire), replace CB. If 24VAC is present at CB K3 connector pin #3 (DBU wire), check  
for 24VAC at control switch (LBU wire) to a neutral (LBU wire). If 24VAC is not  
present, check continuity of the control switch. Replace the control switch if defective.  
If 24VAC is not present, GMPR is energized or defective. If 24VAC is present, check  
for 24VAC at GMPR terminal #2 (P wire) to a neutral (LBU wire). If 24VAC is not  
present, check GMPR continuity between terminals #2 (P wire) and #6 (LBU wire). If  
open, replace GMPR. Next, check for 24VAC at DV. If 24VAC is present and DV does  
not energize, check DV solenoid continuity.  
b2) Manual Drain: 150-sec. shutdown sequence bypass: To bypass the 150-sec.  
shutdown sequence, remove the front panel, then move the power switch to the  
"OFF" position. Next, move the control switch to the "DRAIN" position, then move  
the power switch to the "ON" position. DV energizes. IMPORTANT! Drain valve  
will not energize unless the front panel safety switch is engaged.  
Diagnosis: If DV does not energize, check for 24VAC at CB K3 connector pin  
#3 (DBU wire) to a neutral (LBU wire). If 24VAC is not present, confirm 24VAC power  
supply to CB K2 connector pin #7 (R wire) on push button model and pin #9 (R wire)  
on Opti-Serve model to a neutral (LBU wire). If 24VAC is present at CB K2 pin  
#7 (push button model) or pin #9 (Opti-Serve model) and not on CB K3 connector  
pin #3 (DBU wire), replace CB. If 24VAC is present at CB K3 connector pin #3 (DBU  
wire), check for 24VAC at control switch (LBU wire) to a neutral (LBU wire). If 24VAC  
is not present, check continuity of the control switch. Replace the control switch  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
if defective. If 24VAC is present, check for 24VAC at GMPR terminal #2 (P wire)  
to a neutral (LBU wire). If 24VAC is not present, check GMPR continuity between  
terminals #2 (P wire) and #6 (LBU wire). If open, replace GMPR. Next, check for  
24VAC at DV. If 24VAC is present and DV does not energize, check DV solenoid  
continuity.  
13) Shutdown – Bin fills with ice and activates BC actuator paddle. 150-sec. shutdown  
sequence begins. 90 sec. after BC opens, Comp and FM de-energize, AM energizes for  
0.6 sec., 60 sec. later, GM de-energizes. Diagnosis: Check that BC actuator paddle is  
activated and not sticking. Check BC proximity switch continuity to confirm BC proximity  
switch is open. If BC actuator is engaged and BC proximity switch is closed, replace  
BC proximity switch. If BC proximity switch is open and Comp, FM, and GM do not  
de-energize, replace CB. See "IV.C. Control Board Check Procedure."  
Legend: AM–agitating motor; BC–bin control; CB–control board; Comp–compressor;  
CT–control transformer; DCT–drain cycle timer (12-hr. timer); DV–drain valve;  
DVT–drain valve timer (20-min. timer); FM–fan motor; FT–fill timer (90-sec.low  
water safety); GM–gear motor; GMPR–gear motor protect relay; LF/S–lower  
float switch; UF/S–upper float switch; WCR–water control relay; WV–inlet  
water valve  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Control Board Check  
Before replacing CB that does not show a visible defect and that you suspect is bad,  
conduct the following CB check. This procedure will help you verify your diagnosis.  
Before proceeding, check for proper voltage per unit nameplate. Check that the 24VAC  
1A fuse, 10.5VAC 0.5A CT fuse are good, and the 115VAC GM external protector is not  
tripped. When checking high-voltage (115VAC), always choose a neutral (W wire) to  
establish a good neutral connection. When checking low-voltage (24VAC and 10.5VAC),  
always choose a neutral (LBU wire) from CT to establish a good neutral connection.  
WARNING! LBU wires are used in both high-voltage and low-voltage applications.  
When checking low-voltage (24VAC and 10.5VAC) confirm that the neutral (LBU  
wire) being used is the CB K4 connector pin #2 (LBU wire) from the CT. Not the  
LBU wire used for GM operation (115VAC) or DV (24VAC power supply) operation.  
When checking CB DC-voltage (5VDC), use CB K3 connector pin #1 for DC ground  
(GND). The "POWER" LED remains on unless power supply is interrupted.  
IMPORTANT! Icemaker will not start unless the front panel safety switch is  
engaged.  
1) Remove the front panel and control box cover.  
2) Turn on the power supply. Move the power switch to the "ON" position.  
3) Startup – "POWER" LED on: Move the control switch to the "ICE" position. Engage the  
safety switch, the "POWER" LED turns on. IMPORTANT! CB "POWER" LED will not  
come on unless the front panel safety switch is engaged. Diagnosis: If "POWER"  
LED does not turn on, check for 10.5VAC at CB K4 connector pin #1 (BR wire) to  
pin #2 (LBU wire). If 10.5VAC is present, and the "POWER" LED is off, replace CB. If  
10.5VAC is not present, see "IV.B.7) Startup."  
4) 5VDC Output Checks:  
There are 6 CB circuits utilizing 5VDC: high-pressure switch, icemaking control circuit,  
freeze protect circuit, ice dispense switch, dispense mode switch ("CONTINUOUS" or  
"PORTION"), and the water dispense switch/water dispense sensor (Opti-Serve model  
only). The high-pressure switch and the icemaking control circuit can prevent CB from  
starting the icemaking process.  
• High-Pressure Switch: CB must have continuity through HPS to start the icemaking  
process. HPS is a normally closed switch. Before proceeding to CB check, confirm  
HPS condition. Turn off the power supply, then remove HPS wires and check continuity  
across HPS. If open, allow to reset. If HPS does not reset, see "IV.B.10) Freeze Cycle."  
a) Push Button Model: If HPS closed, check for 5VDC from CB K4 connector pin  
#10 (V wire) to CB K3 connector pin #1 (open). If 5VDC is not present and "POWER"  
LED is on, replace CB. If 5VDC is present, check for 5VDC from CB K4 connector  
pin #9 (BR wire) to CB K3 connector pin #1 (open). If 5VDC is not present, replace  
HPS or HPS wiring. If 5VDC is present, HPS circuit is good and WV should energize  
and start filling the reservoir. If not, see "IV.C.5) Fill Cycle."  
b) Opti-Serve Model: If HPS closed, check for 5VDC from CB K4 connector pin  
#6 (BR wire) to CB K3 connector pin #1 (open). If 5VDC is not present and  
"POWER" LED is on, replace CB. If 5VDC is present, check for 5VDC from CB  
K4 connector pin #5 (V wire) to CB K3 connector pin #1 (open). If 5VDC is not  
present, replace HPS or HPS wiring. If 5VDC is present, HPS circuit is good and WV  
should energize and start filling the reservoir. If not, see "IV.C.5) Fill Cycle."  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Icemaking Control Circuit: The icemaking control circuit consists of WCR, CS, and  
BC. The icemaking control circuit activates once UF/S closes. Once CB reads a  
closed circuit through WCR, CS, and BC, CB then starts the 60-sec. ice purge cycle  
(GM operation). Once UF/S closes, WCR energizes, closing contacts between WCR  
terminals #4 (GY wire) and #6 (O wire). CS must be in the "ICE" position (O wires).  
BC proximity switch must be closed (O and V wires) to complete the icemaking circuit  
between CB K4 connector pin #3 (GY wire) and #4 (V wire). Diagnosis: Confirm UF/S  
has closed and WCR energizes. Next, check for 5VDC from CB K4 connector pin  
#3 (GY wire) and CB K4 connector pin #4 (V wire) to CB K3 connector pin #1 (open).  
If 5VDC is not present on CB K4 connector pin #3 (GY wire) or pin #4 (V wire), replace  
CB. If 5VDC is present on one and not the other, check continuity on WCR terminals  
#4 and #6, CS, and BC.  
• Freeze Protect Circuit (GMPR): Once 60-sec. ice purge cycle starts, GM and  
GMPR energize, closing GMPR pins #3 (BR wire) and #5 (DBU wire). CB circuit  
K2 connector pin #1 (DBU wire) and #2 (BR wire) is now closed. Once 60-sec. ice  
purge timer terminates, CB energizes Comp. If this circuit is open, Comp cannot  
energize. Diagnosis: Check for 5VDC at CB K2 connector pin #1 (DBU wire) and  
CB K2 connector pin #2 (BR wire) to CB K3 connector pin #1 (open). If 5VDC is not  
present on either pin, replace CB. If 5VDC is present on one and not the other, confirm  
GMPR is energized and terminals #3 and #5 contacts are closed. If 5VDC is present on  
both, once 60-sec. ice purge timer terminates, Comp and FM start. If not, replace CB.  
• Ice Dispense Controls:  
a) Push Button Model – "DM" and "AM" LEDs are on: Ice Dispense Switch, Dispense  
Mode Switch ("CONTINUOUS" or "PORTION")–When the ice dispense mode switch  
is pressed, "DM" LED is on. Circuit is closed between CB K4 connector pin #6 (BK  
wire) and #8 (BK wire) to #7 (GY wire) or #5 (P wire) depending on dispense mode  
switch ("CONTINUOUS" or "PORTION"). Diagnosis: Check for 5VDC from CB  
K4 connector pin #6 (BK wire) or pin #8 (BK wire) to CB K3 connector pin #1 (open).  
If 5VDC is not present, replace CB. If 5VDC is present, press and hold the ice  
dispense button. DS and DM should energize. If not, check for 115VAC at CB K2  
connector pin #6 (LBU wire) to a neutral (W wire). If 115VAC is not present, check  
as outlined below. If 115VAC is present, check DS, DM winding, and DM auger for  
binding.  
(1) "CONTINUOUS" Mode: Engage the ice dispense button, then check for 5VDC  
from CB K4 connector to pin #5 (P wire) to CB K3 connector pin #1 (open). If  
5VDC is not present, check ice dispense switch and DMS continuity.  
(2) "PORTION" Mode: Engage the ice dispense button, then check for 5VDC from  
CB K4 connector pin #7 (GY wire) to CB K3 connector pin #1 (open). If 5VDC is  
not present, check the ice dispense switch and DMS continuity.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b) Opti-Serve Model – "ICE" and "AM" LEDs are on:  
(1) "CONTINUOUS" Mode: Before engaging the ice dispense Opti-Serve sensor,  
check for 5VDC from the locations given in the table below. If VDC is different  
than in the table, replace CB. If VDC is correct, engage the Opti-Serve sensor  
and confirm that VDC matches the table below. If not, see "IV.F.3a. Ice Dispense  
"CONTINUOUS" Mode" to rule out a faulty Opti-Serve sensor. If the Opti-Serve  
sensor checks out, replace CB. If VDC matches the table below when the  
Opti-Serve sensor is engaged and ice is not dispensed, check CB K2 connector  
pin #6 (LBU wire) for 115VAC. If 115VAC is not present, replace CB. If 115VAC is  
present, check DS and DM continuity. Replace as needed.  
Control Board Connector To Control Board DC Ground Disengaged Engaged  
K5 Pin #4 (W/O wire)  
K5 Pin #5 (Y wire)  
K5 Pin #6 (W/BR wire)  
0VDC  
5VDC  
5VDC  
0VDC  
0VDC  
5VDC  
To  
K3 Pin #1 (open)  
(2) "PORTION" Mode: Before engaging the ice dispense Opti-Serve sensor, check  
for 5VDC from the locations given in the table below. If VDC is different than in the  
table, replace CB. If VDC is correct, engage the Opti-Serve sensor and confirm  
that VDC matches the table below. If not, see "IV.F.3b. Ice Dispense "PORTION"  
Mode" to rule out a faulty Opti-Serve sensor. If Opti-Serve sensor checks out,  
replace CB. If the VDC matches the table below when the Opti-Serve sensor is  
engaged and ice is not dispensed, check CB K2 connector pin #6 (LBU wire) for  
115VAC. If 115VAC is not present, replace CB. If 115VAC is present, check DS  
and DM continuity. Replace as needed.  
Control Board Connector To Control Board DC Ground Disengaged Engaged  
K5 Pin #1 (W/R wire)  
K5 Pin #2 (W/BU wire)  
K5 Pin #3 (W/BK wire)  
0VDC  
5VDC  
5VDC  
0VDC  
0VDC  
5VDC  
To  
K3 Pin #1 (open)  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Water Dispense Switch/Water Dispense Sensor  
a) Push Button Model: The water dispense button and DispWV are not associated with  
CB. Engage the water dispense button, then check for 24VAC at DispWV. If 24VAC  
is present and no water is dispensed, check for water supply line shut-off valve  
closed, clogged water filters, clogged WV screen. If the water supply is good, replace  
DispWV. If 24VAC is not present, check water dispense switch continuity and CT  
24VAC fuse, 125VAC power supply, and continuity.  
b) Opti-Serve Model: Before engaging the water dispense Opti-Serve sensor, check for  
5VDC from the locations given in the table below. If VDC is different than in the table,  
replace CB. If 5VDC is present, engage the Opti-Serve sensor and confirm that VDC  
matches the table below. If not, see "IV.F.3c. Water Dispense" to rule out a faulty  
Opti-Serve sensor. If the Opti-Serve sensor checks out, replace CB. If VDC matches  
the table below when the Opti-Serve sensor is engaged, check for 24VAC between  
CB K2 connector pin #8 (DBU wire) to a neutral (LBU wire) with the Opti-Serve  
sensor engaged. If 24VAC is not present, replace CB. If 24VAC is present and no  
water is dispensed, check for water supply line shut-off valve closed, clogged water  
filters, clogged WV screen. If the water supply is good, replace DispWV.  
Control Board Connector To Control Board DC Ground Disengaged  
Engaged  
0VDC  
0VDC  
K5 Pin #7 (R wire)  
K5 Pin #8 (W wire)  
K5 Pin #9 (BK wire)  
0VDC  
5VDC  
5VDC  
To  
K3 Pin #1 (open)  
5VDC  
5) Fill Cycle – CB directs 24VAC power supply to WV from CB K2 connector pin  
#7 (R wire) to CB K3 connector pin #3 (DBU wire). Confirm 24VAC between  
CB K2 connector pin #7 (R wire) and pin #8 (LBU wire). Next, confirm 24VAC between  
CB K3 connector pin #3 (DBU wire) and CB K2 connector pin #8 (LBU) wire. If 24VAC  
is present between CB K2 connector pin #7 (R wire) and #8 (LBU wire), but not  
between CB K3 connector pin #3 (DBU wire) and CB K2 connector pin #8 (LBU wire),  
replace CB. If 24VAC is present between CB K3 connector pin #3 (DBU wire) and CB  
K2 connector pin #8 (LBU wire) and fill cycle does not start, see "IV.B.8) Fill Cycle."  
6) Ice Purge Cycle "GM" LED is on: UF/S closes, WCR relay terminal #6 (LBU  
wire) and #4 (O wire) close. CB K1 connector COM (BR wire) and CB K1 connector  
NO (DBU wire) contacts close, energizing GM and GMPR. 60-sec. ice purge timer  
starts. Check for 115VAC at CB K1 connector NO (DBU wire) to a neutral (W wire). If  
115VAC is not present, confirm continuity between CB connector K4 pin #3 (GY wire)  
and #4 (V wire). Next, confirm 115VAC at CB K1 connector COM (BR wire) to a neutral  
(W wire). If 115VAC is present at CB K1 connector COM (BR wire) but not on NO (DBU  
wire), and CB K4 connector pin #3 (GY wire) and #4 (V wire) are closed, replace CB.  
7) Freeze Cycle "GM" and "COMP" LEDs are on: 60-sec. ice purge timer terminates.  
CB X2 relay energizes, closing X2 relay contacts (BR and LBU wires). Confirm  
continuity between CB K2 connector pin #1 (DBU wire) and #2 (BR wire). After being  
closed for 60 seconds, confirm 115VAC between X2 (BR wire) and a neutral (W wire).  
Next, check for 115VAC between CB X2 (LBU wire) and a neutral (W wire). If 115VAC  
is present on CB X2 (BR wire), but not on CB X2 (LBU wire) and CB K2 connector pin  
#1 (DBU wire) and #2 (BR wire) are closed, replace CB.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8) Drain Cycle "FLUSH" (drain) LED is on: 12-hr. DCT terminates or CS is moved  
to "DRAIN" position. 150-sec. shutdown sequence starts. 90 seconds later, Comp  
de-energizes and Comp LED turns off. 60 seconds after Comp de-energizes, GM  
de-energizes and GM LED turns off. Drain cycle starts. "FLUSH" LED turns on and DV  
energizes. DV de-energizes after 20 minutes when drain cycle is initiated by 12-hr. DCT.  
When the drain cycle is initiated by CS (manual drain), DV de-energizes when CS is  
moved to "OFF" position or "ICE" position.  
Push Button Model: "FLUSH" (drain) LED is on. Confirm 24VAC at CB K2 connector  
pin #8 (LBU wire) (12-hr. DCT) to CB K4 connector pin #2 (LBU wire). If 24VAC is not  
present, confirm 24VAC at CB K2 connector pin #7 (R wire) to CB K4 connector pin  
#2 (LBU wire). If 24VAC is present on CB K4 connector pin #7 (R wire) and not on pin  
#8 (LBU wire), replace CB. If 24VAC is present, DV energizes and allows water from the  
evaporator and reservoir to drain for 20 minutes.  
Opti-Serve Model: "FLUSH" (drain) LED is on. Confirm 24VAC at CB K2 connector  
pin #10 (LBU wire) (12-hr. DCT) to CB K4 connector pin #2 (LBU wire). If 24VAC is not  
present and "FLUSH" LED is on (CS in the "ICE" position), replace CB. If 24VAC is  
present, DV energizes and allows water from the evaporator and reservoir to drain for  
20 minutes.  
Manual Drain: Move CS to the "DRAIN" position. Confirm 24VAC at CB K3 connector  
pin #3 (DBU wire) to CB K4 connector pin #2 (LBU wire). If 24VAC is not present,  
replace CB. If 24VAC is present, check CS (LBU wire) to CB K4 connector pin  
#2 (LBU wire). If 24VAC is not present, replace CS. If 24VAC is present, DV energizes  
and allows water from the evaporator and reservoir to drain.  
9) Shutdown – When BC actuator paddle is activated, BC proximity switch opens, 5VDC  
is interrupted at CB K4 connector pin #3 (GY wire) and #4 (V wire). 150-sec. shutdown  
sequence starts. 90 seconds after BC opens, Comp de-energizes, 60 seconds later,  
GM de-energizes. If 5VDC is present from CB K4 connector pin #3 (GY wire) to CB  
connector pin #4 (V wire), and Comp or GM does not de-energize, replace CB.  
Legend: AM–agitating motor; BC–bin control; CB–control board; Comp–compressor;  
CS–control switch; CT–control transformer; DCT–drain cycle timer (12-hr. timer);  
DispWV–dispense water valve; DM–dispense motor; DMS–dispense mode switch  
("CONTINUOUS," or "PORTION"); DS–dispense solenoid; DVT–drain valve timer  
(20-min. timer); FM–fan motor; GM–gear motor; GMPR–gear motor protect relay;  
LF/S–lower float switch; UF/S–upper float switch; WCR–water control relay;  
WV–inlet water valve  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
D. Bin Control Check  
1) Remove the front and top panels.  
2) Remove the storage bin cover. If necessary, dispense ice so that the BC actuator is not  
engaged or remove the ice manually. WARNING! Care should be taken to avoid the  
agitator during BC testing.  
3) Move the control switch to the "OFF" position.  
4) Move the power switch to the "OFF" position.  
5) Turn off the power supply.  
6) Disconnect red BC connector from the back of the control box.  
7) Check for continuity across BC proximity switch violet (V wire) and orange (O wire).  
If BC actuator is not engaged and BC proximity switch is open, replace BC proximity  
switch.  
8) Press and hold BC actuator paddle. While BC actuator is engaged, check for continuity  
across BC proximity switch violet (V wire) and orange (O wire). If BC actuator is  
engaged and BC proximity switch is closed, replace BC proximity switch.  
9) Disengage BC actuator paddle.  
10) Connect red BC connector.  
11) Turn on the power supply. Move the power switch to the "ON" position.  
12) Move the control switch to the "ICE" position.  
13) Engage the safety switch to start the automatic icemaking process.  
14) When Comp starts, press and hold BC actuator paddle.  
15) The 150-sec. shutdown sequence starts. 90 seconds after BC opens, Comp  
de-energizes, 60 seconds later, GM de-energizes. If 5VDC is present at CB K4  
connector pin #3 (GY wire) to #4 (V wire), and Comp or GM does not de-energize,  
replace CB.  
Legend: BC–bin control; CB–control board; Comp–compressor; GM–gear motor  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E. Float Switch Check and Cleaning  
1. Float Switch Check  
1) Remove the front panel, then make sure the power switch is in the "ON" position.  
2) Move the control switch to the "DRAIN" position.  
3) Engage the safety switch and allow the evaporator and reservoir to drain.  
4) Disengage the safety switch, then move the power switch to the "OFF" position and the  
control switch to the "OFF" position.  
5) Turn off the power supply.  
6) Disconnect F/S connector and check F/S continuity. Both UF/S and LF/S should be  
open. Check continuity between F/S common (BK wire) and UF/S (R wire). Next,  
check continuity between F/S common (BK wire) and LF/S (DBU wire). If both are  
open, continue to step 7. If either are closed, follow the steps in "IV.E.2. Float Switch  
Cleaning." After cleaning F/S, check UF/S and LF/S again. Replace if necessary.  
7) Reconnect F/S connector.  
8) Move the power switch to the "ON" position.  
9) Turn on the power supply.  
10) Move the control switch to the "ICE" position.  
11) Engage the safety switch.  
12) Once the reservoir is full and GM starts, disengage the safety switch, then move the  
power switch to the "OFF" position and the control switch to the "OFF" position.  
13) Turn off the power supply.  
14) Remove F/S connector and check F/S continuity. Both UF/S and LF/S should be closed.  
Check continuity between F/S common (BK wire) and UF/S (R wire). Next, check  
continuity between F/S common (BK wire) and LF/S (DBU wire). If either are open,  
follow the steps in "IV.E.2. Float Switch Cleaning." After cleaning F/S, check UF/S and  
LF/S again. Replace if necessary.  
15) Reconnect F/S connector.  
16) Move the power switch to the "ON" position and the control switch to the "ICE" position.  
17) Replace the front panel in its correct position.  
18) Turn on the power supply to start the automatic icemaking process.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Float Switch Cleaning  
Depending on local water conditions, scale may build up on F/S. Scale on F/S can cause  
inconsistent operation of UF/S and LF/S. In this case, both UF/S and LF/S should be  
cleaned and checked.  
1) Move the control switch to the "OFF" position.  
2) Remove the front panel, then move the power switch to the "OFF" position.  
3) Turn off the power supply.  
4) Remove F/S assembly from the reservoir cover. See Fig. 1.  
5) Wipe down F/S assembly with a mixture of 1 part Hoshizaki "Scale Away" and 25 parts  
warm water. Rinse the assembly thoroughly with clean water.  
6) While not necessary, the floats can be removed from the shaft during cleaning. If you  
remove them, note that the blue float is on top (UF/S) and the white float is on bottom  
(LF/S). The floats must be installed with the magnets inside them towards the top of  
the switch. See Fig. 1. Installing the floats upside down will affect the timing of F/S  
operation.  
7) Rinse F/S assembly thoroughly with clean water and replace in its correct position.  
8) Move the power switch to the "ON" position.  
9) Replace the front panel in its correct position.  
10) Turn on the power supply.  
11) Move the control switch to the "ICE" position to start the automatic icemaking process.  
Legend: F/S–float switch; GM–gear motor; LF/S–lower float switch; UF/S–upper float switch  
Float Switch Assembly  
Red (upper)  
Black (common)  
Dark Blue (lower)  
Magnet (towards top)  
Reservoir Cover  
Upper Float (blue)  
Spring Retainer Clip  
Magnet (towards top)  
Lower Float (white)  
Plastic Retainer Clip  
Reservoir  
Fig. 1  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F. Diagnostic Charts  
Before consulting the diagnostic charts, check for correct installation, proper voltage per  
unit nameplate, and adequate water pressure (10 to 113 PSIG). Check CB using the steps  
in "IV.C. Control Board Check."  
1. No Ice Production  
Startup  
1. Power Supply  
2. Water Supply  
a) Off, blown fuse, or tripped breaker.  
b) Not within specifications.  
a) Water supply off or improper water pressure.  
b) External water filters clogged.  
a) "OFF" position or defective.  
a) Not engaged or defective.  
3. Power Switch  
4. Safety Switch  
5. Power Protect Relay  
a) Voltage not within specifications.  
b) Defective.  
6. Control Transformer  
a) Coil winding open or shorted.  
(115VAC, 24VAC, and 10.5VAC)  
7. 1A Fuse (24VAC Control Board) a) Blown.  
8. .5A Fuse (10.5VAC Control  
Board)  
a) Blown.  
9. Control Board  
a) Defective.  
See "IV.C. Control Board Check"  
10. Control Switch  
11. Bin Control  
a) In "OFF" or "DRAIN" position.  
b) Defective.  
a) Tripped with bin filled with ice.  
b) Proximity switch stuck open.  
c) Actuator paddle does not move freely.  
a) Dirty condenser.  
12. High-Pressure Switch  
b) Ambient temperature too warm.  
c) Fan motor not operating.  
d) Refrigerant overcharged.  
e) Bad contacts.  
f) Refrigerant lines or components restricted.  
Fill Cycle  
1. Water Control Relay  
2. Inlet Water Valve  
a) Energized (upper float switch stuck closed).  
b) Defective.  
a) Screen or orifice clogged.  
b) Coil winding open.  
3. Float Switch  
a) Float does not move freely.  
b) Defective.  
See "IV.E. Float Switch Check  
and Cleaning"  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ice Purge Cycle  
a) No power to gear motor.  
a) External protector (gear motor overload) open.  
b) Internal protector open.  
c) Motor winding open.  
d) Mechanical failure.  
a) Defective.  
1. Control Board  
2. Gear Motor  
3. Coupling  
Freeze Cycle  
1. Control Board  
2. Compressor  
a) Defective.  
a) External protector open.  
b) Motor winding open.  
c) Capacitor defective.  
d) Start relay defective.  
e) Mechanical failure.  
a) Motor winding or internal protector open.  
b) Bearing worn out or locked rotor.  
a) Dirty.  
3. Fan Motor  
4. Evaporator  
b) Damaged or defective.  
a) Bulb loose.  
5. Thermostatic Expansion Valve  
(TXV)  
b) Operating erratically.  
a) Low.  
6. Refrigerant Charge  
7. Drain Valve  
a) Dirty, leaking by.  
b) Defective coil.  
8. Water System  
1. Water Supply  
a) Water leaks.  
Refill  
a) Off.  
2. Float Switch  
a) Float does not move freely.  
b) Defective.  
See "IV.E. Float Switch Check  
and Cleaning."  
3. Water Control Relay  
a) Energized (upper float switch stuck closed).  
b) Defective.  
4. Inlet Water Valve  
a) Screen or orifice clogged.  
b) Coil winding open.  
Shutdown  
1. Bin Control  
a) Not enough ice in bin to trip actuator paddle.  
b) Proximity switch defective.  
c) Actuator paddle does not move freely.  
a) Defective.  
2. Control Board  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Ice/Water Dispense  
Ice Dispense Push Button  
a) See "Startup."  
1. Power Supply  
2. Control Board  
a) Ice dispense switch circuit open or no power.  
b) No power to ice dispense solenoid, ice dispense motor, or agitating  
motor.  
3. Ice Dispense Switch  
4. Dispense Mode Switch  
5. Ice Dispense Motor  
a) Defective.  
a) Defective (open).  
a) Open windings.  
b) Mechanical failure.  
6. Ice Dispense Solenoid  
7. Shutter Assembly  
8. Agitating Motor  
a) Defective or loose connection.  
a) Mechanical failure.  
a) Open windings.  
b) Mechanical failure.  
Ice Dispense Opti-Serve  
a) See "Startup."  
1. Power Supply  
2. Control Board  
a) No power to dispense mode switch.  
b) Dispense mode switch circuit open.  
c) No power to ice dispense solenoid, ice dispense motor or agitating  
motor.  
3. Infrared Sensor  
a) Defective.  
4. Dispense Mode Switch  
5. Ice Dispense Motor  
a) Defective (open).  
a) Open windings.  
b) Mechanical failure.  
a) Defective or loose connection.  
a) Mechanical failure.  
a) Open windings.  
6. Ice Dispense Solenoid  
7. Shutter Assembly  
8. Agitating Motor  
b) Mechanical failure.  
Water Dispense Push Button  
a) See "Startup."  
1. Power Supply  
2. Infrared Sensor  
a) Defective.  
3. Water Dispense Switch  
4. Water Dispense Valve  
a) Defective.  
a) Water supply turned off.  
b) Defective.  
Water Dispense Opti-Serve  
a) See "Startup."  
1. Power Supply  
2. Infrared Sensor  
3. Control Board  
a) Defective.  
a) No power to infrared sensor.  
b) No power to water dispense valve.  
a) Water supply turned off.  
b) Defective.  
4. Water Dispense Valve  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3. Opti-Serve (OS) Sensors  
Be sure to check all items in section "IV.F.2. Ice/Water Dispense" prior to using this chart.  
Use the following charts along with the wiring diagram to troubleshoot the OS sensors.  
Ice Sensor  
1. OS Sensor  
a) Dirty.  
b) Defective. See chart 3a and 3b.  
a) No power to infrared sensor.  
b) Not reading infrared sensor signal.  
Water Sensor  
2. Control Board  
1. OS Sensor  
a) Dirty.  
b) Defective. See chart 3c.  
a) No power to infrared sensor.  
b) Not reading infrared sensor signal.  
2. Control Board  
3a. Ice Dispense "Continuous"  
Component  
Control Board  
Sensor To Control Board /Other Sensor Engaged Disengaged  
Solenoid K2 Pin 6 (LBU wire)  
-
To  
Neutral/GND  
K5 Pin 5 (Y wire)  
K5 Pin 6 (W/BR wire) (BK wire) 5VDC  
-
120VAC  
5VDC  
0VAC  
0VDC  
5VDC  
(W wire)  
Sensor K5 Pin 4 (W/0 wire) (R wire) To  
3b. Ice Dispense "Portion"  
Component  
Control Board  
Sensor To Control Board /Other Sensor Engaged Disengaged  
Solenoid K2 Pin 6 (LBU wire)  
-
To  
Neutral/GND  
K5 Pin 2 (W/BU wire) (W wire)  
K5 Pin 3 (W/BK wire) (BK wire) 5VDC  
-
120VAC  
5VDC  
0VAC  
0VDC  
5VDC  
Sensor K5 Pin 1 (W/R wire) (R wire) To  
3c. Water Dispense  
Component  
Control Board  
To Control Board /Other Engaged Disengaged  
Solenoid K2 Pin 8 (DBU wire) To  
K4 Pin 2 (LBU wire)  
K5 Pin 8 (W wire)  
K5 Pin 9 (BK wire)  
24VAC  
5VDC  
5VDC  
0VAC  
0VDC  
5VDC  
Sensor K5 Pin 7 (R wire) To  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
V. Removal and Replacement of Components  
WARNING  
• This icemaker should be diagnosed and repaired only by qualified service  
personnel to reduce the risk of death, electric shock, serious injury, or fire.  
• Move the power switch to the "OFF" position and turn off the power supply to the  
icemaker before servicing. Lockout/Tagout to prevent the power from being turned  
back on inadvertently.  
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are  
securely in place after the equipment is serviced. Make sure that none have fallen  
into the storage bin.  
• Make sure all food zones in the icemaker and storage bin are clean after  
the icemaker is serviced. For cleaning procedures, see "VI. Cleaning and  
Maintenance."  
• When replacing evaporator assembly and water circuit components, make sure  
there are no water leaks after the repair is complete.  
A. Service for Refrigerant Lines  
WARNING  
• Repairs requiring the refrigeration circuit to be opened must be performed by  
properly trained and EPA-certified service personnel.  
• Always recover the refrigerant and store it in an approved container. Do not  
discharge the refrigerant into the atmosphere.  
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
NOTICE  
• Do not leave the system open for longer than 15 minutes when replacing or  
servicing parts. The Polyol Ester (POE) oils used in R-404A units can absorb  
moisture quickly. Therefore it is important to prevent moisture from entering the  
system when replacing or servicing parts.  
• Always install a new drier every time the sealed refrigeration system is opened.  
• Do not replace the drier until after all other repair or replacement has been made.  
Install the new drier with the arrow on the drier in the direction of the refrigerant  
flow.  
• When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Refrigerant Recovery  
This icemaker is provided with refrigerant access valves. Using proper refrigerant  
practices, recover the refrigerant from the service valves and store it in an approved  
container. Do not discharge the refrigerant into the atmosphere.  
2. Brazing  
WARNING  
• R-404A itself is not flammable at atmospheric pressure and temperatures up to  
176°F (80°C).  
• R-404A itself is not explosive or poisonous. However, when exposed to high  
temperatures (open flames), R-404A can be decomposed to form hydrofluoric  
acid and carbonyl fluoride both of which are hazardous.  
• Do not use silver alloy or copper alloy containing arsenic.  
• Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
1) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
NOTICE  
• Always install a new drier every time the sealed refrigeration system is opened.  
• Do not replace the drier until after all other repair or replacement has been made.  
Install the new drier with the arrow on the drier in the direction of the refrigerant  
flow.  
• When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
2) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
3. Evacuation and Recharge (R-404A)  
1) Attach a vacuum pump to the system. Be sure to connect charging hoses to both high  
and low-side access valves.  
IMPORTANT  
The vacuum level and vacuum pump may be the same as those for current  
refrigerants. However, the rubber hose and gauge manifold to be used for  
evacuation and refrigerant charge should be exclusively for POE oils.  
2) Turn on the vacuum pump. Open the gauge manifold valves. Never allow the oil in the  
vacuum pump to flow backwards.  
3) Allow the vacuum pump to pull down to a 29.9" Hg vacuum. Evacuating period depends  
on pump capacity.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4) Close the low-side valve and high-side valve on the gauge manifold.  
5) Disconnect the gauge manifold hose from the vacuum pump and attach it to a  
refrigerant service cylinder. Remember to loosen the connection and purge the air from  
the hose. See the rating label inside the icemaker for the required refrigerant charge.  
Hoshizaki recommends only virgin refrigerant or reclaimed refrigerant which meets ARI  
Standard 700 (latest edition) be used.  
6) A liquid charge is required for charging an R-404A system (to prevent fractionation).  
Place the service cylinder on the scales: if the service cylinder is not equipped with  
a dip tube, invert the service cylinder, then place it on the scales. Open the high-side  
valve on the gauge manifold.  
7) Allow the system to charge with liquid until the proper charge weight is met.  
8) If necessary, add any remaining charge to the system through the low-side.  
NOTICE! To prevent compressor damage, use a throttling valve or liquid  
dispensing device to add the remaining liquid charge through the low-side  
access valve with the icemaker running.  
9) Close the high and low-side gauge manifold valves, then disconnect the gauge manifold  
hoses.  
10) Cap the access valves to prevent a possible leak.  
B. Important Notes for Component Replacement  
NOTICE  
When replacing a component listed below, see the notes to help ensure proper  
operation.  
Component  
Notes  
Compressor  
Install a new drier, start capacitor, and start relay.  
Expansion Valve • Install a new drier.  
• Attach the expansion valve bulb to the suction line in the same location as the previous  
bulb.  
• The bulb should be between the 10 and 2 o'clock positions on the tube.  
• Secure the bulb with the clamp and holder, then insulate it.  
Upper and  
• Inspect the upper bearing for wear. See "V.B.1. Upper Bearing Wear Check." Replace if  
Lower Bearings  
necessary.  
• When replacing the upper bearing it is advised to also change the lower bearing at the  
same time.  
Evaporator  
Gear Motor  
• Install a new drier.  
• Inspect the mechanical seal and O-ring prior to installing the new evaporator. If worn,  
cracked, or scratched, the mechanical seal should also be replaced.  
Install a new gear motor capacitor.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Evaporator Assembly  
Spout A  
Spout B  
Evaporator Assembly  
Power Switch  
Cutter  
Extruding Head and  
Upper Bearing  
Auger  
Control Switch  
Dispense Mode Switch  
Washer  
Allen Head Cap Screw  
Evaporator  
Allen Head Cap Screw with  
Washer  
Mechanical Seal  
O-Ring  
Ring  
Housing and  
Lower Bearing  
Hex Head Bolt  
with Washer  
Spline Coupling  
Gear Motor  
Fig. 2  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Upper Bearing Wear Check  
To ensure that the bearing inside the extruding head does not exceed the wear tolerance  
of .02", follow the instructions below. See Fig. 3.  
1) Move the control switch to the "OFF" position, then turn off the power supply. Remove  
the front and top panels, then move the power switch to the "OFF" position.  
2) Remove the front cover of the storage bin. Remove spout B,  
then remove spout A and the cutter. See Fig. 2.  
.02" Round Stock  
or Pin Gauge  
3) Grasp the top of the auger and move the  
Auger  
auger towards you, then try to insert a  
.02" round stock or pin gauge in between  
the back side of the auger shaft and the  
bearing surface. Check several locations  
around the auger shaft. If the gauge goes  
between the shaft and the bearing at  
any point or if the bearing is scratched  
or cracked, both the top bearing in the  
extruding head and the lower bearing in the  
housing should be replaced. Instructions for  
removing the extruding head and housing  
are located later in this procedure.  
Extruding  
Head  
Fig. 3  
Note: Replacing the bearing requires a bearing press adaptor. If one is not available,  
replace the whole extruding head and housing.  
4) Replace the cutter, spout A, spout B, and the front cover of the storage bin in their  
correct positions.  
5) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
6) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
2. Removal and Replacement of Extruding Head  
1) Move the control switch to the "DRAIN" position and drain all of the water from the  
evaporator.  
2) After the water has stopped draining, move the control switch to the "OFF" position, then  
turn off the power supply. Remove the front and top panels, then move the power switch  
to the "OFF" position.  
3) Remove the front cover of the storage bin. Remove spout B, then remove spout A and  
the cutter. See Fig. 2.  
4) Remove the apron panel, then remove the left side panel.  
5) Remove the allen head cap screws and lift off the extruding head.  
6) Place the new extruding head in place and tighten down the allen head cap screws.  
7) Replace the cutter in its correct position.  
8) Replace spout A, spout B, and the front cover of the storage bin in their correct  
positions.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
10) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
3. Removal and Replacement of Auger  
1) Move the control switch to the "DRAIN" position and drain all of the water from the  
evaporator.  
2) After the water has stopped draining, move the control switch to the "OFF" position,  
then turn off the power supply. Remove the front and top panels, then move the power  
switch to the "OFF" position.  
3) Remove the front cover of the storage bin. Remove spout B, then remove spout A.  
See Fig. 2.  
4) Remove the apron panel, then remove the left side panel.  
5) Remove the allen head cap screws securing the extruding head. Using the cutter, lift out  
the auger assembly.  
6) Remove the cutter, extruding head, and upper part of the mechanical seal from the  
auger and place them on the new auger. NOTICE! To help prevent water leaks, be  
careful not to damage the surfaces of the O-ring or mechanical seal.  
7) Install the new auger assembly with the upper part of the mechanical seal attached and  
tighten down the allen head cap screws.  
8) Replace spout A, spout B, and the front cover of the storage bin in their correct  
positions.  
9) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
10) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
4. Removal and Replacement of Evaporator  
NOTICE  
• Always install a new drier every time the sealed refrigeration system is opened.  
• Do not replace the drier until after all other repair or replacement has been made.  
Install the new drier with the arrow on the drier in the direction of the refrigerant  
flow.  
• When brazing, protect the drier by using a wet cloth to prevent the drier from  
overheating. Do not allow the drier to exceed 250°F (121°C).  
1) Move the control switch to the "DRAIN" position and drain all of the water from the  
evaporator.  
2) After the water has stopped draining, move the control switch to the "OFF" position,  
then turn off the power supply. Remove the front and top panels, then move the power  
switch to the "OFF" position.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3) Remove the apron panel, then remove the left side panel.  
4) Recover the refrigerant and store it in an approved container.  
5) Remove the front cover of the storage bin. Remove spout B, then remove spout A.  
See Fig. 2.  
6) Remove the allen head cap screws securing the extruding head. Using the cutter, lift out  
the auger assembly.  
7) Remove the evaporator bracket and disconnect the water hoses.  
8) Disconnect the inlet and outlet tubing.  
9) Remove the allen head cap screws securing the evaporator to the lower housing.  
10) Lift off the evaporator.  
11) Inspect the mechanical seal and O-ring prior to installing the new evaporator. The  
mechanical seal consists of two parts. One moves along with the auger, and the other  
is fixed on the lower housing. NOTICE! If the contact surfaces of these two parts  
are worn, cracked, or scratched, the mechanical seal may cause water leaks and  
should be replaced. Instructions for removing the mechanical seal and lower housing  
are located later in this procedure.  
12) Make sure the lower mechanical seal is in place, then place the new evaporator in  
position. Secure the evaporator to the lower housing using the allen head cap screws.  
13) Remove the drier, then place the new drier in position.  
14) Braze all fittings while purging with nitrogen gas flowing at a pressure of 3 to 4 PSIG.  
15) Use an electronic leak detector or soap bubbles to check for leaks. Add a trace of  
refrigerant to the system (if using an electronic leak detector), and then raise the  
pressure using nitrogen gas (140 PSIG). DO NOT use R-404A as a mixture with  
pressurized air for leak testing.  
16) Evacuate the system, and charge it with refrigerant. See the nameplate for the required  
refrigerant charge.  
17) Install the auger assembly with the upper part of the mechanical seal attached and  
tighten down the allen head cap screws.  
18) Replace the evaporator bracket and reconnect the water hoses.  
19) Replace spout A, spout B, and the front cover of the storage bin in their correct  
positions.  
20) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
21) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Removal and Replacement of Mechanical Seal and Lower Housing  
5a. Mechanical Seal  
1) Move the control switch to the "DRAIN" position and drain all of the water from the  
evaporator.  
2) After the water has stopped draining, move the control switch to the "OFF" position, then  
turn off the power supply. Remove the front and top panels, then move the power switch  
to the "OFF" position.  
3) Remove the front cover of the storage bin. Remove spout B, then remove spout A.  
See Fig. 2.  
4) Remove the apron panel, then remove the left side panel.  
5) Remove the extruding head heater and the allen head cap screws securing the  
extruding head.  
6) Using the cutter, lift out the auger assembly, then remove the evaporator bracket.  
7) The mechanical seal consists of two parts. One moves along with the auger, and the  
other is fixed on the lower housing. NOTICE! If the contact surfaces of these two  
parts are worn, cracked, or scratched, the mechanical seal may cause water leaks  
and should be replaced.  
8) Remove the allen head cap screws securing the evaporator to the lower housing.  
9) Raise the evaporator up to access the lower housing.  
10) Remove the mechanical seal from the housing. If only replacing the mechanical seal,  
proceed to step 13. NOTICE! To help prevent water leaks, be careful not to damage  
the surfaces of the O-ring or mechanical seal.  
5b. Lower Housing  
11) Remove the O-ring and the bolts securing the housing to the gear motor and remove  
the housing from the gear motor. If inspection of the upper bearing inside the extruding  
head (see "V.D.1. Upper Bearing Wear Check") indicates that it is out of tolerance,  
replace both it and the bearing inside the lower housing.  
Note: Replacing the bearing requires a bearing press adaptor. If one is not available,  
replace the whole extruding head and housing.  
12) Install the O-ring and mount the lower housing on the gear motor.  
13) Install the lower part of the mechanical seal on the lower housing.  
14) Lower the evaporator down and secure it to the lower housing.  
15) Install the auger assembly with the upper part of the mechanical seal attached.  
16) Replace the evaporator bracket in its correct position.  
17) Replace spout A, spout B, and the front cover of the storage bin in their correct  
positions.  
18) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
19) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Removal and Replacement of Gear Motor  
1) Move the control switch to the "DRAIN" position and drain all of the water from the  
evaporator.  
2) After the water has stopped draining, move the control switch to the "OFF" position, then  
turn off the power supply. Remove the front and top panels, then move the power switch  
to the "OFF" position.  
3) Remove the front cover of the storage bin. Remove spout B, then remove spout A.  
See Fig. 2.  
4) Remove the apron panel, then remove the left side panel.  
5) Remove the evaporator bracket.  
6) Remove the bolts securing the lower housing to the gear motor. Lift the evaporator up  
slightly.  
7) Remove the 3 gear motor bolts.  
8) Disconnect the wiring from the gear motor, then remove the gear motor.  
9) Remove the spline coupling from the old gear motor and attach to the new gear motor.  
10) Place the new gear motor in the drain pan.  
11) Secure the gear motor.  
12) Connect the gear motor wires.  
13) Lower the evaporator down and secure it to the gear motor.  
14) Replace the evaporator bracket in its correct position.  
15) Replace spout A, spout B, and the front cover of the storage bin in their correct  
positions.  
16) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
17) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Dispense Auger and Agitator  
1) Move the control switch to the "OFF" position, then turn off the power supply. Remove  
the front and top panels, then move the power switch to the "OFF" position.  
2) Remove the front cover of the storage bin.  
3) Remove the thumbscrews from the vertical plane, then loosen the thumbscrews from  
the horizontal plane of the motor bracket. Slide the motor back.  
Note: Hold the dispense auger/agitator to prevent it from dropping when sliding back the  
motor. See Fig. 4.  
4) Replace the dispense auger/agitator with the new one.  
5) Assemble the removed parts in the reverse order of which they were removed.  
6) Move the power switch to the "ON" position, then replace the panels in their correct  
positions.  
7) Turn on the power supply, then move the control switch to the "ICE" position to start the  
automatic icemaking process.  
8. Dispense or Agitating Motor  
1) Move the control switch to the "OFF" position, then turn off the power supply. Remove  
the front and top panels, then move the power switch to the "OFF" position.  
2) Remove the storage bin front panel.  
3) Remove the thumbscrews from the vertical plane, then loosen the thumbscrews from  
the horizontal plane of the motor bracket. Slide the motor back.  
Note: Hold the dispense auger/agitator to prevent it from dropping when sliding back the  
motor. See Fig. 4.  
4) Remove the thumbscrews from the horizontal plane of the motor bracket.  
5) Remove the motor from the bracket.  
6) Install the new motor.  
7) Assemble the removed parts in the reverse  
Agitator  
Agitating Motor  
order of which they were removed.  
8) Move the power switch to the "ON" position,  
then replace the panels in their correct  
positions.  
9) Turn on the power supply, then move the  
control switch to the "ICE" position to start  
the automatic icemaking process.  
Dispense Motor  
Dispense Auger  
Fig. 4  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VI. Cleaning and Maintenance  
This icemaker must be cleaned and maintained in accordance with the instruction  
manual and labels provided with the icemaker. Consult with your local distributor  
about cleaning and maintenance service. To obtain the name and phone number of  
1-800-233-1940 in the USA.  
WARNING  
• Only qualified service technicians should service this icemaker.  
CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews are  
securely in place after any cleaning or maintenance is done to the icemaker. Make  
sure that none have fallen into the dispenser unit/storage bin.  
• The storage bin is for ice use only. Do not store anything else in the storage bin.  
Spout A  
Spout B  
Extruding Head  
Reservoir  
Bin Control Assembly  
Agitator  
Power Switch  
Float Switch  
Assembly  
Dispense  
Auger  
Evaporator Assembly  
Agitating Motor  
Dispense Motor  
Storage Bin Cover  
4A0-4  
CONTROL  
ICE  
OFF  
DISPENSE MODE  
Spout Cover  
PORTION  
DRAIN  
CONTINUOUS  
Safety Switch  
Optical Sensors (-OS model)  
Fig. 5  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A. Cleaning and Sanitizing Instructions  
Hoshizaki recommends cleaning and sanitizing this icemaker at least twice a year.  
More frequent cleaning and sanitizing, however, may be required in some existing water  
conditions.  
WARNING  
To prevent injury to individuals and damage to the icemaker, do not use ammonia  
type cleaners.  
• Carefully follow any instructions provided with the bottles of cleaning and  
sanitizing solution.  
• Always wear liquid-proof gloves and goggles to prevent the cleaning and sanitizing  
solutions from coming into contact with skin or eyes.  
• After cleaning and sanitizing, do not use ice made from the cleaning and  
sanitizing solutions. Be careful not to leave any solution on the parts or in the  
dispenser unit/storage bin.  
1. Water System  
a) Cleaning Solution  
Dilute 9.6 fl. oz. (0.29 l) of Hoshizaki "Scale Away" with 1.6 gal. (6.0 l) of warm water.  
b) Cleaning Procedure  
1) Close the icemaker water supply line shut-off valve.  
2) Move the control switch to the "DRAIN" position. See Fig. 5. Allow the water system to  
drain for 5 minutes.  
3) Move the dispense mode switch to the "CONTINUOUS" position, then dispense all of  
the ice from the storage bin.  
Note: Ice dispenses continuously for a maximum of 60 seconds per activation.  
4) Move the control switch to the "OFF" position, then turn off the power supply. Remove  
the front and top panels, then move the power switch to the "OFF" position.  
5) Remove the storage bin cover. Remove spout B, then remove spout A.  
6) Pour the cleaning solution over the extruding head until the evaporator assembly and  
the reservoir are full and the solution starts to overflow into the drain pan.  
Note: If there is excess scale on the extruding head, fill the evaporator assembly and  
reservoir as described above, then use a clamp on the reservoir hose between  
the reservoir and evaporator assembly to block flow. Pour additional cleaning  
solution over the extruding head until the evaporator assembly is completely full.  
7) Replace spout A, spout B, and the storage bin cover in their correct positions.  
8) Allow the icemaker to sit for 10 minutes before operation. If you placed a clamp on the  
reservoir hose in step 6, remove it before operation.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9) In bad or severe water conditions, clean the float switch assembly as described below.  
Otherwise, continue to step 10.  
a. Remove the float switch assembly from the reservoir cover.  
b. Wipe down the float switch assembly with the cleaning solution.  
c. Rinse the float switch assembly thoroughly with clean water.  
d. Replace the float switch assembly in its correct position.  
10) Move the power switch to the "ON" position and replace the panels in their correct  
positions. Turn on the power supply, then move the control switch to the "ICE" position.  
Make ice using the solution until the icemaker stops making ice.  
Note: This icemaker will not run if the safety switch is not engaged.  
11) Move the control switch to the "DRAIN" position. Allow the water system to drain for  
5 minutes.  
12) Move the control switch to the "ICE" position. Open the icemaker water supply line  
shut-off valve to supply water to the reservoir.  
13) After the gear motor starts, move the control switch to the "DRAIN" position. Allow the  
water system to drain for 5 minutes.  
Note: If you do not sanitize the icemaker, move the control switch to the "ICE" position  
after the water system drains. Allow the icemaker to run for 30 minutes, then  
move the control switch to the "OFF" position. Turn off the power supply, then  
remove the front panel and storage bin cover. Move the power switch to the "OFF"  
position. Go to step 12 in "VI.A.2.c) Cleaning and Sanitizing Procedure" under  
"2. Dispense Components."  
14) Move the control switch to the "OFF" position, then turn off the power supply.  
15) Close the icemaker water supply line shut-off valve.  
c) Sanitizing Solution  
Dilute 0.82 fl. oz. (25 ml) of a 5.25% sodium hypochlorite solution (chlorine bleach) with  
1.6 gal. (6.0 l) of warm water.  
d) Sanitizing Procedure - Following Cleaning Procedure  
1) Make sure the control switch is in the "OFF" position, the power supply is off, and the  
icemaker water supply line shut-off valve is closed.  
2) Remove the front and top panels, then move the power switch to the "OFF" position.  
3) Remove the storage bin cover. Remove spout B, then remove spout A.  
4) Pour the sanitizing solution over the extruding head until the evaporator assembly and  
the reservoir are full and the solution starts to overflow into the drain pan.  
5) Replace spout A, spout B, and the storage bin cover in their correct positions.  
6) Allow the icemaker to sit for 10 minutes before operation.  
7) Move the power switch to the "ON" position and replace the panels in their correct  
positions. Turn on the power supply, then move the control switch to the "ICE" position.  
Make ice using the solution until the icemaker stops making ice.  
8) Move the control switch to the "DRAIN" position. Allow the water system to drain for  
5 minutes.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9) Move the control switch to the "ICE" position. Open the icemaker water supply line  
shut-off valve to supply water to the reservoir.  
10) After the gear motor starts, move the control switch to the "DRAIN" position. Allow the  
water system to drain for 5 minutes.  
11) Move the control switch to the "ICE" position. Allow the icemaker to run for 30 minutes,  
then clean and sanitize the dispense components as outlined below.  
2. Dispense Components  
Perform after cleaning and sanitizing the water system as outlined above.  
a) Cleaning Solution  
Dilute 9.6 fl. oz. (0.29 l) of Hoshizaki "Scale Away" with 1.6 gal. (6.0 l) of warm water.  
b) Sanitizing Solution  
Dilute 0.82 fl. oz. (25 ml) of a 5.25% sodium hypochlorite solution (chlorine bleach) with  
1.6 gal. (6.0 l) of warm water.  
c) Cleaning and Sanitizing Procedure  
1) Move the control switch to the "OFF" position, then turn off the power supply.  
2) Remove the front and top panels, then move the power switch to the "OFF" position.  
3) Remove the storage bin cover.  
4) Remove the motor bracket thumbscrews, first from the vertical plane and then from  
the horizontal plane. While holding on to the corresponding agitator or auger, move  
the agitating motor or the dispense motor towards you. Remove the agitator and the  
dispense auger from the storage bin. See Fig. 5.  
5) Remove the bin control assembly. See Fig. 6.  
6) Remove the snap pin, shaft, and actuator.  
7) Remove spout B, spout A, and their gaskets.  
Spout B  
Spout A  
Bin Control Assembly  
Bin Control  
Bracket  
Snap Pin  
Shaft  
Fig. 6  
Actuator  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8) Remove the spout cover, ice dispense spout, and water dispense nozzle. See Fig. 7.  
9) Immerse the agitator, dispense auger, and parts removed in steps 5 through 8 in the  
cleaning solution and then in the sanitizing solution for 15 minutes each. Rinse the parts  
thoroughly with clean water. On Opti-Serve models (-OS), wipe the optical sensors with  
cleaning solution and then with a clean, damp cloth.  
10) Wipe the shutter located above the ice dispense spout thoroughly with a clean cloth.  
11) Reassemble the bin control assembly and replace all parts in the reverse order of which  
they were removed.  
12) Pour warm water into the storage bin and melt any remaining ice. Clean the storage bin  
liner and the storage bin cover using a neutral cleaner. Rinse thoroughly after cleaning.  
Replace the storage bin cover in its correct position.  
13) Move the power switch to the "ON" position, then replace the panels in their correct  
positions. Turn on the power supply, then move the control switch to the "ICE" position  
to start the automatic icemaking process.  
Water Dispense Nozzle  
Ice Dispense Spout  
Spout Cover  
Fig. 7  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Maintenance  
The maintenance schedule below is a guideline. More frequent maintenance may be  
required depending on water quality, the icemaker's environment, and local sanitation  
regulations.  
WARNING  
• Only qualified service technicians should service this icemaker.  
• Move the control switch and the power switch to the "OFF" position and turn off  
the power supply before servicing. Lockout/Tagout to prevent the power supply  
from being turned back on inadvertently.  
Maintenance Schedule  
Frequency Area  
Task  
Every 2  
Weeks  
Air Filter  
Inspect. Wash with warm water and neutral cleaner if dirty.  
Monthly  
External Water  
Filters  
Check for proper pressure and change if necessary.  
Icemaker Exterior Wipe down with a clean, soft cloth. Use a damp cloth containing a neutral  
cleaner to wipe off oil or dirt build up. Clean any chlorine staining (rust  
colored spots) using a non-abrasive cleaner like Zud or Bon Ami.  
Every 6  
Months  
Icemaker and  
Storage Bin  
Clean and sanitize per the cleaning and sanitizing instructions provided in  
this manual.  
Evaporator  
Wipe down with a clean cloth and warm water. Slowly pour one cup of  
Condensate Drain sanitizing solution (prepare as outlined in the sanitizing instructions in  
Pan and Gear  
Motor Drain Pan  
this manual) into the evaporator condensate drain pan. Be careful not to  
overflow the pan. This solution will flow down to the gear motor drain pan  
and out the drain line to sanitize these areas. Repeat with a cup of clean  
water to rinse.  
Icemaker, Storage Check to make sure they are clear.  
Bin, and Drip Tray  
Drains  
Yearly  
Inlet Water Valve  
and Drain Valve  
Close the water supply line shut-off valve and drain the water system. Clean  
the inlet water valve screen and clean and inspect the drain valve.  
Water Hoses  
Condenser  
Icemaker  
Inspect the water hoses and clean/replace if necessary.  
Inspect. Clean if necessary by using a brush or vacuum cleaner.  
Inspect for oil spots, loose components, fasteners, and wires.  
Upper Bearing  
(extruding head)  
Check for wear using .02" round stock or pin gauge. Replace both upper  
bearing and lower bearing if wear exceeds factory recommendations. See  
"V.B.1. Upper Bearing Wear Check".  
After  
3 Years,  
then Yearly Lower Bearing  
and O-Ring  
Upper Bearing  
(extruding head);  
Inspect. Replace both upper bearing and lower bearing if wear exceeds  
factory recommendations. Replace the mechanical seal if the seal's contact  
surfaces are worn, cracked, or scratched.  
(lower housing);  
Mechanical  
Seal; Evaporator  
Cylinder; Auger  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Preparing the Icemaker for Periods of Non-Use  
NOTICE  
When storing the icemaker for an extended time or in sub-freezing temperatures,  
follow the instructions below to prevent damage.  
When the icemaker is not used for two or three days under normal conditions, it  
is sufficient to only move the control switch to the "OFF" position. When storing  
the icemaker for extended time or in sub-freezing temperatures, follow the  
instructions below.  
1) Close the icemaker water supply line shut-off valve and open the icemaker water supply  
line drain valve.  
2) Move the control switch to the "DRAIN" position. Allow the water system to drain for 5  
minutes.  
3) Move the dispense mode switch to the "CONTINUOUS" position, then dispense all of  
the ice from the storage bin.  
Note: Ice dispenses continuously for a maximum of 60 seconds per activation.  
4) Attach a compressed air or carbon dioxide supply to the icemaker water supply line  
drain valve.  
5) While engaging the water dispense switch, blow out the water dispense valve using the  
compressed air or carbon dioxide supply. After blowing out the water dispense valve,  
leave the compressed air or carbon dioxide supply flowing. Move the control switch to  
the "ICE" position to open the inlet water valve and briefly blow out the inlet water valve.  
After blowing out the inlet water valve, move the control switch to the "OFF" position.  
6) Close the icemaker water supply line drain valve.  
7) Turn off the power supply, then remove the front panel and move the power switch to the  
"OFF" position.  
8) Remove the storage bin cover. Clean the storage bin liner and the storage bin cover  
using a neutral cleaner. Rinse thoroughly after cleaning. Replace the storage bin cover  
and the front panel in their correct positions.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VII. Disposal  
This icemaker contains refrigerant and must be disposed of in accordance with  
applicable national, state, and local codes and regulations. Refrigerant must be  
recovered by properly certified service personnel.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Haier Water Heater ES10V M1 User Manual
Harbor Freight Tools Drill 60238 User Manual
Harbor Freight Tools Insect Control Equipment 95500 User Manual
Havis Shields Automobile KR 1531 24 SP KOV User Manual
Heath Zenith Door 598 1123 02 User Manual
Honeywell Water System 4973 Series User Manual
Hotpoint Freezer RZA30 User Manual
HTC Cell Phone SM TP001 0704 User Manual
Hunter Fan Outdoor Ceiling Fan 98000 01 002 User Manual
Ice O Matic Ice Maker MFI0800 User Manual