Honeywell DVD Recorder L User Manual

R7140G,L,M  
Burner Control Modules  
INSTALLATION INSTRUCTIONS  
FEATURES  
Device status available to ModBus™ through S7810M  
card or S7800A1001 Series 5 Keyboard Display.  
Safety features:  
Interlock check.  
Closed loop logic test.  
Dynamic AMPLI-CHECK™.  
Dynamic input check.  
Dynamic safety relay test.  
Dynamic self-check logic.  
Expanded safe-start check.  
High Fire Purge Switch test (R7140L only).  
Internal hardware status monitoring.  
Low Fire Start Switch test.  
Tamper resistant timing and logic.  
Application flexibility.  
0.8 or 3.0 second Flame Failure Response Time (FFRT),  
depending on amplifier selected.  
Dependable, long-term operation provided by  
microcomputer technology.  
Five LEDs for sequence information. See Fig. 1.  
Five function Run/Test Switch.  
APPLICATION  
The Honeywell R7140G,L,M Burner Control Modules are  
microprocessor-based integrated burner controls for  
automatically fired gas, oil or combination fuel single burner  
applications. The Burner Control Module system consists of a  
Relay Module, Q520A Subbase, Amplifier and Purge Card.  
Options include S7800 Keyboard Display Modules (KDM).  
Interchangeable plug-in flame amplifiers.  
Nonvolatile memory; history files and sequencing  
status are retained after loss of power and can be  
viewed using the Keyboard Display Module  
S7800A1001 (sold separately).  
Report generation (optional) through modbus™.  
The R7140 Burner Control Modules directly replace many  
BC7000 PM720G,L,M, and many R4150G,L,M and  
R4140G,L,M units using the existing Q520A 20-terminal  
Wiring Subbase.  
NOTE: Check Service Notes on page 7 and Static Check-  
out on page 26 prior to installation of R7140.  
Burner controller data (optional):  
Lockout/alarm status.  
Total cycles of operation.  
Total hours of operation.  
The R7140 can be demonstrated or tested on the FSP5004  
tester. Note that the R7849 UV Amplifier or the R7851 Optical  
Flame Amplifier cannot be tested.  
The R7140G,L,M is programmed to provide a level of safety,  
functional capability and features beyond the capacity of  
conventional controls.  
Status of configuration jumpers.  
Status of Run/Test Switch.  
Functions provided by the R7140G,L,M include automatic  
burner sequencing, flame supervision, system status  
indication, system or self-diagnostics and troubleshooting.  
66-1153-03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Table 1. Flame Detection Systems.  
Plug-in Flame Signal Amplifiers  
Applicable Flame Detectors  
Flame  
Failure  
Response  
a
Type  
Color Self-Checking  
Model  
Time (sec)  
Fuel  
Type  
Models  
C7024E,F  
b,c,h  
Rectification Green Dymanic Self-  
Check  
3
Gas, oil, Ultraviolet (Purple  
coal Peeper®)  
R7824C  
g
No  
0.8/1 or 2/3 Gas  
Rectifying Flame Rod C7004, C7007, C7011  
R7847A  
i
Complete Assemblies:  
C7008, C7009, Q179  
Holders  
g
No  
2/3  
Gas, oil, Ultraviolet (Purple  
C7012A,C.  
R7847A  
R7847B  
coal  
Peeper®)  
d,g  
Dynamic Ampli-  
Check®  
0.8/1 or  
2/3  
Gas  
Rectifying Flame Rod C7004, C7007, C7011  
Holders  
i
Complete Assemblies:  
C7008, C7009, Q179  
d,g  
c,h  
Dynamic Ampli-  
Check®  
2/3  
3
Gas, oil, Ultraviolet (Purple  
coal Peeper®)  
C7012A,C  
R7847B  
Dynamic Self  
Check  
Gas, oil, Ultraviolet (Purple  
coal Peeper®)  
C7012E,F  
R7847C  
Infrared  
Ultraviolet  
Optical  
Red  
No  
R7848A  
2/3  
2/3  
2/3  
2/3  
Gas, oil, Infrared (Lead Sulfide) C7015  
coal  
d
b
Dynamic Ampli-  
Check®  
Gas, oil, Infrared (Lead Sulfide) C7015  
coal  
R7848B  
Red/  
White  
No  
R7852A  
Gas, oil, Infrared (Lead Sulfide) C7915  
coal  
Dynamic Ampli-  
Check®  
Gas, oil, Infrared (Lead Sulfide) C7915  
coal  
R7852B  
R7849A  
f
f
Purple No  
0.8/1 or  
2/3  
Gas, oil Ultraviolet  
(Minipeeper)  
C7027, C7035, C7044  
d
Dynamic Ampli-  
Check®  
0.8/1 or  
2/3  
Gas, oil Ultraviolet  
(Minipeeper)  
R7849B  
R7861A  
R7886A  
C7027, C7035, C7044  
C7061  
c,e  
c,e  
Dynamic Self-  
Check  
0.8/1 or  
2/3  
Gas, oil, Ultraviolet  
coal  
Blue  
Dynamic Self-  
Check  
2/3  
Gas, oil, Ultraviolet (Adjustable C7076  
coal Sensitivity)  
White Dymanic Ampli- R7851B  
Check®  
0.8/1 or 2/3 Gas, oil, Optical (UV, Visible  
coal Light)  
C7927, C7962  
c
Dynamic Self-  
Check  
2/3  
Gas, oil, Optical (UV only)  
coal  
C7961  
R7851C  
a
b
c
Flame Failure Response Time (FFRT) depends on selection of amplifier and 7800 SERIES and R7140 Relay Module.  
R7824C is used only with the 24 Vdc RM7824 Relay Module and C7024E,F Flame Detectors.  
Circuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burner  
operation and shuts down burner if detection system fails.  
Circuitry tests flame signal amplifier 12 times a minute during burner operation and shuts down burner if amplifier fails.  
200/220/240 Vac applications require a 120 Vac, 10 VA minimum stepdown transformer (not provided) to drive the shutter.  
Applies to R7886A series 2 or greater; R7861 series 1 or greater. Fig. 2 shows flame detector wiring.  
Use C7027, C7035 and C7044 Flame Detectors only on burners that cycle on-off at least once every twenty-four hours. Use  
C7061A Ultraviolet Detector with R7861A Amplifier or C7076A Flame Detector with R7886A Amplifier as ultraviolet flame detec-  
tion system for appliances with burners that remain on continuously for twenty-four hours or longer.  
R7847A,B Amplifiers with 0.8/1 second FFRT should NOT be used with C7012A,C Solid State Ultraviolet Detectors.  
R7824C Series 2 and greater and R7847C Series 4 or greater, check flame detector system when flame reaches 1.5 Vdc or at  
4.5 seconds, whichever occurs first.  
d
e
f
g
h
NOTE: R7824C Series 2 or greater and R7847C Series 4 or greater, pulse the shutter when signal of 1.5 Vdc is sensed. Display  
readings of 0.7 to 2.4 Vdc are common.  
i
Order flame rod separately; see flame detector Instructions for holder.  
3
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R7140G,L,M BURNER CONTROL MODULES  
S7800A1068 Spanish language.  
Table 2. Plug-in Purge Timer Cards.  
S7800A1118 Katakana (Japanese) language.  
S7800A1126 Portuguese language.  
S7800A1142 English language.  
Pre-Purge Timing  
Product Number  
ST7800A1013  
ST7800A1039  
ST7800A1047  
ST7800A1054  
ST7800A1062  
7
Communications:  
30  
40  
60  
90  
S7810A1009 Data ControlBus Module™ (if no KDM is  
used).  
S7810M1003 ModBus™ Module.  
Miscellaneous:  
S7820A1007 Remote Reset Module.  
S7830A1005 Expanded Annunciator, 120 Vac, 50/60 Hz.  
203541 Data ControlBus Connector, 5-wire.  
203765 Remote Display Mounting Bracket.  
221729 Dust cover, Relay Module.  
50023821-001 Keyboard Display Module Cover, NEMA 4,  
clear.  
50023821-002 Keyboard Display Module Cover, NEMA 4,  
clear with reset button.  
205321 Flush Display mounting kit.  
221818A Extension Cable, display, 5 ft. (1524 mm).  
221818C Extension Cable, display, 10 ft. (3048 mm).  
FSP5004 Tester.  
Above times cover the Purge timings of the R4140/50 Pro-  
grammers and PM720.  
Other timings exist—consult the Tradeline catalog for com-  
plete list of ST7800 Purge timers.  
Accessories:  
The following accessories enhance the R7140 Burner Control  
Module and are available through local 7800 SERIES  
distributors.  
Keyboard Display Modules (KDM):  
S7800A1001 English language.  
S7800A1035 French language.  
S7800A1043 German language.  
S7800A1050 Italian language.  
123514A Rectification Flame Simulator.  
203659 Ultraviolet Flame Simulator.  
BURNER CONTROL  
5
(127)  
6-5/32  
(156)  
POWER  
PILOT  
FLAME  
MAIN  
ALARM  
RESET  
_
S
+
5
1-1/4  
(32)  
(127)  
7
(177)  
5-3/4 (146)  
M22604  
Fig. 2. Mounting dimensions of R7140G,L,M Burner Control Module with Q520A Subbase, in in. (mm).  
66-1153—03  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Table 3. Terminal Ratings.  
Description  
Terminal No.  
Ratings  
a
G
Flame Sensor Earth Ground  
a
Earth G  
Earth Ground  
L2(N)  
L1  
3
Line Voltage Common  
Line Voltage Supply (L1)  
Lockout/Running Interlock  
Pre-Ignition Interlock Input  
Pilot Valve/Ignition  
120 Vac (+10/-15%), 50 or 60 Hz (±10%).  
120 Vac, 8A run, 43A inrush.  
120 Vac, 1 mA.  
4
5
120 Vac. See Table 4.  
6
Interrupted/Intermittent Pilot Valve/First Stage Oil Valve 120 Vac. See Table 4.  
7
Main Fuel Valve  
Burner Motor  
120 Vac. See Table 4.  
120 Vac, 9.8 AFL, 58.8 ALR (inrush).  
120 Vac, 1A pilot duty.  
120 Vac, 75 VA pilot duty.  
120 Vac, 75 VA pilot duty.  
120 Vac, 75 VA pilot duty.  
120 Vac, 1 mA.  
8
9
Alarm  
10  
11  
12  
13  
14  
15  
16  
17  
18  
Firing Rate High Fire  
Firing Rate Common  
Firing Rate Modulate  
Low Fire Switch Input  
Firing Rate Low Fire  
High Fire Switch Input  
Burner Controller and Limits  
Shutter  
120 Vac, 75 VA pilot duty.  
120 Vac, 1 mA.  
120 Vac, 1 mA.  
120 Vac, 0.5A.  
Ignition  
120 Vac, 4.5A ignition.  
F
Flame Sensor  
60 to 220 Vac, current limited.  
a
The R7140 must have an earth ground providing a connection between the subbase and the control panel or the equipment. The earth  
ground wire must be capable of conducting the current to blow the 15A fast blow fuse (or breaker) in the event of an internal short  
circuit. The R7140 needs a low impedance ground connection to the equipment frame, which, in turn, needs a low impedance  
connection to earth ground.  
Table 4. Terminal Ratings.  
Terminal  
Typical Load  
Maximum Rating at 120 Vac, 60 Hz  
4.5A ignition and 50 VA pilot duty, or  
2.5A ignition and 75 VA pilot duty.  
5 or 6  
Ignition  
Transformer/Pilot  
Valve/First Stage Fuel Valve  
7
Main Fuel Valve(s) (solenoid/ 250 VA pilot duty or 65 VA pilot duty in parallel with motorized valve(s) using a total of  
motorized/diaphragm) and  
Vent Valve, if required  
1150 VA locked rotor (inrush), 460 VA to open, and 250 VA to hold or motorized valve(s)  
using a total of 1500 VA locked rotor (inrush), 600 VA to open, and 250 VA to hold.  
5
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Table 5. Sequence Timing for Normal Operation.  
Flame  
Establishing  
Period  
Post  
Firing  
Rate  
Energy  
Saving  
Approval  
Code  
Purge  
Device Initiate Standby Purge Pilot  
Main  
Run Timing Interlock Circuits Circuit Pre-Purge Bodies  
R7140G 10 sec.  
*
** 4 or 10 10, 15  
*
15 sec. Pre-Ignition,  
4-wire  
No  
UL/CSA  
Modulating  
a
sec.  
Running, Low Fire modulating  
sec. or  
intermittent.  
R7140L  
R7140M  
10 or 15  
sec.  
Pre-Ignition,  
Lockout High and  
Low Fire  
FM/IRI  
a
Modulating  
10 sec. or  
intermittent  
Pre-Ignition,  
Running, isolated isolated  
Low Fire. On-Off-On  
contacts  
2-wire  
UL/CSA  
On-Off.  
a
30 seconds with JR2 clipped and jumper from terminal 8 to terminal 15.  
* STANDBY and RUN can be an infinite time period.  
** PURGE will be determined by which ST7800A purge card is selected; 15 timings are available from 2 seconds to 30 minutes.  
NOTE: Allowable inrush can be up to ten times the pilot  
duty rating.  
IMPORTANT  
1. Wiring connections for the relay modules are unique;  
therefore, refer to Fig. 4–11 or the correct  
Specifications for proper subbase wiring, and  
sequence charts.  
EXAMPLE: Pilot duty rating = 50 VA.  
At 120 V, running current is:  
50/120 = 0.42A.  
2. Wiring must comply with all applicable codes,  
ordinances and regulations.  
3. Wiring must comply with NEC Class 1 (Line Voltage)  
wiring.  
Maximum allowable inrush is ten times 0.42A = 4.2A.  
4. Loads connected to the R7140 must not exceed  
those listed in the Specifications; see Table 3 and 4.  
5. Limits and interlocks must be rated to simultaneously  
carry and break current to the ignition transformer,  
pilot valve, and main fuel valve(s).  
INSTALLATION  
6. All external timers must be listed or component  
recognized by authorities who have jurisdiction for  
the specific purpose for which they are used.  
7. For on-off gas-fired systems, some authorities who  
have jurisdiction prohibit the wiring of any limit or  
operating contacts in series between the flame  
safeguard control and the main fuel valve(s).  
8. Two Flame Detectors can be connected in parallel  
with the exception of flame detectors C7927, C7915,  
C7961, and C7962.  
9. This equipment generates, uses and can radiate  
radio frequency energy and, if not installed and used  
in accordance with the instructions, may cause  
interference to radio communications. It has been  
tested and found to comply with the limits for a  
Class A computing device of Part 15 of FCC rules  
which are designed to provide reasonable protection  
against such interference when operated in a  
commercial environment. Operation of this  
equipment in a residential area may cause  
interference; in which case, the users at their own  
expense may be required to take whatever measures  
are required to correct this interference.  
When Installing this Product...  
1. Read these instructions carefully. Failure to follow  
them could damage the product or cause a hazardous  
condition.  
2. Check the ratings given in the instructions and marked  
on the product to make sure the product is suitable for  
the application.  
3. Installer must be a trained, experienced, flame  
safeguard service technician.  
4. After installation is complete, check out the product  
operation as provided in these instructions.  
WARNING  
Fire or Explosion Hazard.  
Can cause property damage, severe injury,  
or death.  
To prevent possible hazardous burner operation, verify  
safety requirements each time a control is installed on  
a burner.  
10.This digital apparatus does not exceed the Class A  
limits for radio noise for digital apparatus set out in  
the Radio Interference Regulations of the Canadian  
Department of Communications.  
WARNING  
Electrical Shock Hazard.  
Can cause serious injury or death.  
Disconnect the power supply before beginning  
installation. More than one power supply disconnect  
may be required.  
66-1153—03  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Make sure the wiring subbase of the old device is a  
20-terminal Q520 (four rows of 5 terminals).  
Location  
Make sure the system Controller is connected to the correct  
terminal on the Q520 wiring subbase. It may be in a wire nut  
tucked into the subbase. It needs to be connected to a  
terminal (like terminal 4 or 16).  
Humidity  
Install the relay module where the relative humidity never  
reaches the saturation point. The relay module is designed to  
operate in a maximum 85 percent relative humidity  
continuous, noncondensing moisture environment.  
Condensing moisture may cause a safety shutdown.  
Make sure there is an electrical service ground wire  
connection to the G terminal in the wiring subbase.  
R4140G or BC7000 with PM720G replacement.  
Vibration  
If the application was a dual burner ignition, check the  
Q520 subbase for a jumper between terminals 6 to 7,  
discard the jumper and move the main valve connec-  
tion (terminal 7) to terminal 6.  
Do not install the relay module where it could be subjected to  
vibration in excess of 0.5G continuous maximum vibration.  
Weather  
Replacing GP201 or GP301 devices:  
High Fire (or Purge Rate) Switch may be connected to  
terminal D.  
The relay module is not designed to be weathertight.  
When installed outdoors, protect the relay module using an  
approved weathertight enclosure.  
Identify, remove, and connect to terminal M.  
Replacing GP101 devices:  
Check wiring subbase. If D is jumpered to 8, remove  
the jumper.  
Final Wiring Check  
1. Check the power supply circuit. The voltage and  
frequency tolerance must match those of the R7140. A  
separate power supply circuit may be required for the  
R7140. Add the required disconnect means and  
overload protection.  
Replacing R4140 programmers on Carlin 1050 and 1150  
burners:  
Remove jumper from 6 to 7.  
Remove jumper from L2 to 12 and wire nut the wires  
together. Note: There will be no wire on terminal 12.  
2. Check all wiring circuits and complete the Static  
Checkout, Table 8, before installing the R7140 on the  
subbase.  
3. Install all electrical connectors.  
4. Restore power to the panel.  
R4140M replacements:  
Check terminal 13 of the Q520 wiring subbase.  
If nothing is on 13, install the new R7140M1007.  
If 13 is jumpered to 8, remove the jumper and install  
R7140M1007.  
Service Notes:  
If 13 goes somewhere (assume a low fire switch  
because the system has a damper motor), remove J1  
and J2 from the back of the R7140M1007.  
Per industry standards, a conduit seal or a cable type that is  
sealed is required to be installed in a device that can result in  
flammable gas or flammable liquid flow through a conduit or  
cable to an electrical ignition source in the event of a seal  
leakage or diaphragm failure. This could be on the gas valves,  
or gas or oil pressure regulators.  
NOTE: J1 and J2 provide an input for the R7140M when  
the system does not have a spring return damper  
with a low fire switch.  
Leaving J1 and J2 in place with either 13 jump-  
ered to 8 or with the low fire switch will cause the  
blower motor to come on after the R7140M is  
installed and power is supplied to the system.  
Check the Q520 Wiring Subbase terminals against the typical  
wiring drawings, Figures 7, 8, 12, 13, 17, or 18.  
If wires are attached to terminals that are unused in the  
figures, DO NOT INSTALL THE R7140 until you have  
identified the connections’ functions. Most likely the old  
subbase terminals were used as tie points, so removing the  
wires, capping with a wire nut, and tucking the wire down into  
the subbase is all that needs to be done.  
Generally, the following table will apply to select  
the R7140M1007 model and the status of jumpers  
J1 and J2.  
7
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Table 6. J1/J2 Jumper Configuration for R4140M/PM720M.  
Model  
R4140M1004/M1012  
R4140M1020/M1038  
R4140M1046/M1053  
R4140M1079 (GP101)  
R4140M1103/M1111  
R4140M1145/M1152  
R4140M1160/M1178  
R4140M1186  
Purge Timer  
A1039  
Leave J1 & J2  
Remove J1 and J2  
X
A1047  
X
X
A1062  
A1062  
X
X
A1039  
A1047  
X
X
X
A1062  
A1047  
R4140M1194  
ST7800A1062  
BC7000L1000 w/PM720M2002 ST7800A1062  
BC7000L1000 w/PM720M2036  
X
*
X
* Check terminal 8 and 15.  
If jumpered, ST7800A1031 (7 second purge).  
If not jumpered, ST7800A1039 (30 second purge).  
Removing the Programmer  
1. Open the master switch.  
Mounting R7140 Relay Module  
2. Loosen the chassis retaining screw.  
3. Pull outward on the top of the chassis.  
4. Disengage the chassis hinge brackets from the subbase  
pivot pins.  
Installing the Programmer (Fig. 3)  
WARNING  
KNIFE-BLADE  
CONTACTS (20)  
Electrical Shock Hazard.  
SPRING  
CONNECTORS  
CHASSIS  
RETAINING  
SCREW  
Can cause severe injury, death or property  
damage.  
Disconnect power before installation to prevent  
electrical shock. More than one disconnect may be  
involved.  
1. Open the master switch.  
2. Make sure no subbase wiring is projecting out beyond  
the terminal blocks. Tuck in wiring against the back of  
the subbase so it does not interfere with the contacts.  
3. Grasp the programmer chassis and engage the chassis  
hinge brackets with the pivot pins at the bottom of the  
subbase.  
4. Swing the chassis inward until the spring connectors  
engage the knifeblade contacts. Push in until the  
contacts are fully engaged.  
5. Tighten the chassis retaining screw securely.  
6. Close the master switch to restore power.  
PROGRAMMER  
CHASSIS  
WIRING  
SUBBASE  
PIVOT PIN (2)  
HINGE  
BRACKET (2)  
M22605  
Fig. 3. Mounting the programmer on the subbase.  
66-1153—03  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
R7140G  
INITIATE  
(INITIAL  
POWERUP  
ONLY)  
PREPURGE PFEP  
HOLD  
10 SEC.  
00  
(4 SEC. IF  
00  
00  
10  
20 25  
MFEP  
00  
15  
TIMED  
DRIVE TO  
PREPURGE  
STANDBY  
POWER  
LOW FIRE JR1 CLIPPED  
RUN  
POSTPURGE STANDBY  
POWER  
POWER  
POWER  
POWER  
POWER  
PILOT  
POWER  
PILOT  
POWER  
POWER  
LED  
DISPLAY  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
FLAME  
MAIN  
FLAME  
MAIN  
ALARM  
ALARM  
ALARM  
ALARM  
ALARM  
BURNER/BLOWER MOTOR  
18 IGN.  
10 SEC. IGN./PILOT  
15 SEC. INTERRUPTED PILOT VALVE  
MAIN VALVE  
8
BURNER  
5 SEC.  
5
6
1
7
OPERATING  
CONTROLS  
AND  
TO  
TO  
LIMITS AND BURNER CONTROLLER CLOSED L1  
16  
16  
3
3
3
INTERLOCK. CHECK  
RUNNING INTERLOCKS CLOSED  
IC  
INTERLOCKS  
16  
PII CLOSED  
4
TO  
2
13  
8
LOW FIRE SW.  
TO  
FLAME PROVING  
10  
FLAME  
SIGNAL  
SSC  
SAFE START CHECK  
R7140G SWITCHING  
11  
TO  
TO  
11  
14  
11  
14  
TO  
10  
11  
TO  
FIRING  
RATE  
MOTOR  
MOTOR ACTION  
1
TERMINAL 6 HAS THE FOLLOWING OPTIONS:  
AS RECEIVED - INTERMITTENT PILOT  
JR2 CLIPPED - 15 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)  
JR2 CLIPPED PLUS TERMINALS 8 - 15 JUMPERED - 30 SECOND MAIN FLAME ESTABLISHING PERIOD (INTERRUPTED PILOT)  
M23319  
PII MEANS PRE-IGNITION INTERLOCK.  
2
3
FOR R7140G1000:  
L1 TO 4  
4 TO 3  
Fig. 4. Operating sequence, R7140G1000/R7140G2008.  
9
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
L1  
(HOT) L2  
1
L1  
120 Vac,  
50/60 Hz  
PLUG-IN PURGE  
TIMER CARD  
CONFIGURATION  
JUMPERS  
TEST  
JACK  
FLAME SIGNAL  
RUN/TEST  
SWITCH  
F
G
PLUG-IN  
FLAME  
AMPLIFIER  
MICROCOMPUTER  
TEST  
RESET  
PUSHBUTTON  
17  
2K  
3K  
4K  
RELAY  
5K  
6K  
7K  
8K  
DRIVE  
RELAY  
STATUS  
CIRCUIT  
FEEDBACK  
AND LINE  
VOLTAGE  
INPUTS  
9K  
SAFETY RELAY  
CIRCUIT  
1K  
STATUS LEDs  
CONTROL  
POWER  
POWER SUPPLY  
R1  
R1  
RUNNING/  
LOCKOUT  
INTERLOCK  
L2  
PRE-IGNITION  
INTERLOCK  
LIMITS CONTROLLER  
1K1  
2K1 5K1  
IGNITION  
3
4
16  
18  
5
4K1  
7K1  
2K2  
PILOT  
6
PILOT/V2  
LOW FIRE SWITCH  
13  
7
MAIN VALVE  
BLOWER  
ALARM  
6K1  
3K1  
8
9
HIGH FIRE  
10  
KEYBOARD  
8K1  
8K2  
9K2  
DISPLAY MODULE  
DDL  
COMMON  
INDICATES FEEDBACK SENSING  
OF RELAY CONTACT STATUS  
AND LINE VOLT INPUTS  
11  
12  
14  
RS485  
MODULATE  
1
9K1  
LOW FIRE  
DDL  
COMMUNICATIONS  
2
3
FIELD WIRING  
INTERNAL WIRING  
REMOTE  
RESET  
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
M23320  
Fig. 5. Internal block diagram of the R7140G1000. (See Fig. 8 for detailed wiring.)  
66-1153—03  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
L1  
(HOT)  
L2  
1
L1  
L2  
120 Vac,  
50/60 Hz  
PLUG-IN PURGE  
TIMER CARD  
CONFIGURATION  
JUMPERS  
TEST  
JACK  
FLAME SIGNAL  
RUN/TEST  
SWITCH  
F
PLUG-IN  
G
FLAME  
MICROCOMPUTER  
AMPLIFIER  
TEST  
17  
CONTROL  
POWER  
POWER SUPPLY  
PRE-IGNITION  
INTERLOCK  
4
RUNNING/  
LOCKOUT  
INTERLOCK  
CONTROLLER  
LIMITS  
1K1  
2K1 5K1  
16  
3
IGNITION  
18  
5
4K1  
7K1  
2K2  
PILOT  
6
PILOT/V2  
MAIN VALVE  
BLOWER  
ALARM  
LOW FIRE SWITCH  
13  
7
8
9
6K1  
3K1  
HIGH FIRE  
12  
8K1  
8K2  
9K2  
COMMON  
INDICATES FEEDBACK SENSING  
OF RELAY CONTACT STATUS  
AND LINE VOLT INPUTS  
13  
15  
14  
MODULATE  
9K1  
LOW FIRE  
FIELD WIRING  
INTERNAL WIRING  
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
M23321  
Fig. 6. Internal block diagram of the R7140G2008. (See Fig. 7 for detailed wiring.)  
11  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
IGNITION  
TRANSFORMER  
5
1ST STAGE  
FUEL VALVE  
6
7
TO  
L2  
2ND STAGE  
FUEL VALVE  
(OPTIONAL)  
5 SECOND IGNITION  
(EARLY SPARK  
2
WIRING  
SUBBASE  
TERMINAL  
STRIP (4)  
TERMINATION)  
RUNNING  
INTERLOCKS  
(INCLUDING  
AIRFLOW SWITCH)  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
6
3
4
PREIGNITION  
INTERLOCK(S)  
3
18  
4
BURNER  
CONTROLLER  
PILOT/IGNITION  
LIMITS  
L1  
L2  
12  
MAIN FUEL  
VALVE(S)  
17  
16  
7
8
120V ALARM  
9
BURNER MOTOR  
(BLOWER)  
HIGH FIRE  
10  
11  
LOW FIRE  
START SWITCH  
15  
14  
COMMON  
G
13  
F
4
RECTIFYING FLAME  
ROD, OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
B
R
B
R
MODULATE  
LOW FIRE  
OR  
W
W
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
WHITE  
BLUE  
BLUE  
SERIES 90  
FIRING RATE  
MOTOR  
SERIES 90  
CONTROLLER  
OR  
YELLOW  
5
C7012A, C, C7061, OR  
C7076A ULTRAVIOLET  
FLAME DETECTOR  
1
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
WHITE  
WHITE  
MASTER  
SWITCH  
L2  
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
3
4
USE ALL NEC CLASS 1 WIRING.  
START INTERLOCKS IF USED BECOME PREIGNITION INTERLOCKS - (MUST REMAIN CLOSED UNTIL IGNITION TRIALS BEGIN.)  
TERMINAL 6 HAS THE FOLLOWING OPTIONS:  
AS RECEIVED - INTERMITTENT PILOT  
JR2 CLIPPED - 15 SECOND MAIN FLAME ESTABLISHING PERIOD  
JR2 CLIPPED AND JUMPER FROM 8-15 - 30 SECOND MAIN FLAME ESTABLISHING PERIOD.  
C7012E.F NEEDS TO BE UPDATED TO C7061.  
M22607B  
5
Fig. 7. Wiring diagram for R7140G2008 for application replacing R4140G with start Interlock or BC7000L1000 with  
PM720G.  
66-1153—03  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
5
IGNITION  
JUMPER  
TO  
L2  
6
7
MAIN OIL VALVE  
SOLENOID  
4
2
WIRING  
SUBBASE  
TERMINAL  
STRIP (4)  
RUNNING  
INTERLOCKS  
(INCLUDING  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
AIRFLOW SWITCH)  
5
3
PREIGNITION  
INTERLOCK(S)  
3
6
18  
6
BURNER  
PILOT/IGNITION  
LIMITS  
L1  
L2  
12  
4
CONTROLLER  
MAIN FUEL  
VALVE(S)  
17  
16  
7
8
120V ALARM  
9
BURNER  
MOTOR  
HIGH FIRE  
10  
11  
15  
14  
LOW FIRE  
SWITCH  
6
COMMON  
G
13  
F
RECTIFYING FLAME  
ROD, OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
B
R
B
R
5
MODULATE  
LOW FIRE  
OR  
W
W
C7027A, C7035A, C7927 OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
WHITE  
BLUE  
BLUE  
SERIES 90  
FIRING RATE  
MOTOR  
SERIES 90  
CONTROLLER  
OR  
C7067A,D OR  
C7061 ULTRAVIOLET  
FLAME  
YELLOW  
1
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
5
DETECTOR  
WHITE  
WHITE  
MASTER  
SWITCH  
L2  
FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER  
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A  
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE  
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION  
60-2306 FOR DETAILED INSTRUCTIONS.)  
4
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
3
USE ALL NEC CLASS 1 WIRING.  
C7012 MUST BE UPDATED TO C7061.  
5
6
FOR DIRECT SPARK IGNITION OF OIL, CONNECT IGNITION TO  
TERMINAL 5 AND MAIN OIL VALVE SOLENOID TO TERMINAL 7; JUMPER  
TERMINAL 7 T0 TERMINAL 6. SEE INSET.  
TERMINAL 6 HAS THE FOLLOWING OPTIONS:  
AS RECEIVED—INTERMITTENT PILOT.  
JR2 CLIPPED—15 SECOND INTERRUPTED PILOT.  
JR2 CLIPPED, TERMINALS 8-15 JUMPERED— 30 SECOND  
INTERRUPTED PILOT.  
SOLENOID MUST NOT EXCEED THE ELECTRICAL RATINGS OF TERMINAL 7.  
4
M22608B  
Fig. 8. Field wiring for R7140G1000 used for replacing R4140G Programmers with pre-ignition interlocks.  
13  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
R7140L  
INITIATE  
(INITIAL  
POWERUP  
ONLY)  
PREPURGE  
HOLD  
PREPURGE PFEP  
HOLD  
10 SEC.  
00  
(4 SEC. IF  
JR1 CLIPPED  
00  
00  
00  
10  
20 25  
MFEP  
00  
POSTPURGE STANDBY  
POWER POWER  
15  
TIMED  
DRIVE TO  
HIGH FIRE  
DRIVE TO  
LOW FIRE  
PREPURGE  
STANDBY  
POWER  
RUN  
POWER  
POWER  
POWER  
POWER  
POWER  
POWER  
PILOT  
POWER  
PILOT  
LED  
DISPLAY  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
FLAME  
MAIN  
FLAME  
MAIN  
ALARM  
ALARM  
ALARM  
ALARM  
ALARM  
BURNER/BLOWER MOTOR  
IGN.  
8
BURNER  
5 SEC.  
18  
10 SEC. IGN./PILOT  
15 SEC. PILOT  
5
6
MAIN VALVE  
7
OPERATING  
CONTROLS  
AND  
TO  
LIMITS AND BURNER CONTROLLER CLOSED  
LOCKOUT INTERLOCKS CLOSED  
L1  
16  
3
1
1
16 TO  
INTERLOCKS  
PII CLOSED  
TO 15 HIGH FIRE SW.  
4
TO 16  
2
13  
8
8
LOW FIRE SW.  
TO  
FLAME  
SIGNAL  
FLAME PROVING  
10  
SSC  
SAFE START CHECK  
SWITCHING  
11  
TO  
TO  
14  
10  
14  
10  
TO  
10  
11  
TO  
FIRING  
RATE  
MOTOR  
MOTOR ACTION  
M23322  
FOR R7140L1009:  
L1 TO 4.  
1
2
4 TO 3.  
PII MEANS PRE-IGNITION INTERLOCK.  
Fig. 9. Operating sequence, R7140L1009 and R7140L2007.  
66-1153—03  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
L1  
(HOT) L2  
1
L1  
120 Vac,  
50/60 Hz  
PLUG-IN PURGE  
TIMER CARD  
CONFIGURATION  
JUMPERS  
TEST  
JACK  
FLAME SIGNAL  
RUN/TEST  
SWITCH  
F
PLUG-IN  
FLAME  
G
MICROCOMPUTER  
AMPLIFIER  
TEST  
RESET  
17  
PUSHBUTTON  
2K  
3K  
4K  
RELAY  
DRIVE  
5K  
RELAY  
STATUS  
FEEDBACK  
AND LINE  
VOLTAGE  
INPUTS  
6K  
7K  
8K  
CIRCUIT  
9K  
SAFETY RELAY  
CIRCUIT  
1K  
STATUS LEDs  
CONTROL  
POWER  
POWER SUPPLY  
R1  
R1  
PII  
RUNNING/  
LOCKOUT  
LIMITS CONTROLLER  
INTERLOCK  
L2  
1K1  
2K1  
5K1  
18  
IGNITION  
4
16  
(3)  
4K1  
7K1  
2K2  
LOW FIRE SWITCH  
13  
(D)  
5
6
7
PILOT  
PILOT/V2  
MAIN VALVE  
BLOWER  
ALARM  
HIGH FIRE SWITCH  
15  
(8)  
6K1  
8
(M)  
9
3K1  
(A)  
HIGH FIRE  
10  
(X)  
11  
(10)  
12  
(11)  
14(  
12)  
KEYBOARD  
DISPLAY MODULE  
8K1  
8K2  
9K2  
DDL  
COMMON  
INDICATES FEEDBACK SENSING  
OF RELAY CONTACT STATUS  
AND LINE VOLT INPUTS  
RS485  
MODULATE  
1
2
9K1  
LOW FIRE  
DDL  
COMMUNICATIONS  
FIELD WIRING  
INTERNAL WIRING  
REMOTE  
RESET  
3
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
NOTE: ( ) NUMBERS ON GP201, GP301 SUBBASE.  
M23323  
Fig. 10. Internal block diagram of the R7140L1009. (See Fig. 12 for detailed wiring.)  
15  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
L1  
(HOT) L2  
1
L1  
L2  
120 Vac,  
50/60 Hz  
PLUG-IN PURGE  
TIMER CARD  
CONFIGURATION  
JUMPERS  
TEST  
JACK  
FLAME SIGNAL  
RUN/TEST  
SWITCH  
F
PLUG-IN  
FLAME  
G
MICROCOMPUTER  
AMPLIFIER  
TEST  
RESET  
17  
PUSHBUTTON  
2K  
3K  
4K  
RELAY  
DRIVE  
5K  
RELAY  
STATUS  
FEEDBACK  
AND LINE  
VOLTAGE  
INPUTS  
6K  
7K  
8K  
CIRCUIT  
9K  
SAFETY RELAY  
CIRCUIT  
1K  
STATUS LEDs  
CONTROL  
POWER  
POWER SUPPLY  
PRE-IGNITION  
INTERLOCK  
4
3
RUNNING/  
LOCKOUT  
INTERLOCK  
LIMITS CONTROLLER  
1K1  
2K1 5K1  
18  
5
IGNITION  
16  
4K1  
7K1  
2K2  
LOW FIRE SWITCH  
13  
PILOT  
6
PILOT/V2  
HIGH FIRE SWITCH  
15  
MAIN VALVE  
7
8
9
6K1  
3K1  
BLOWER  
ALARM  
HIGH FIRE  
10  
11  
12  
14  
KEYBOARD  
DISPLAY MODULE  
8K1  
DDL  
COMMON  
INDICATES FEEDBACK SENSING  
OF RELAY CONTACT STATUS  
AND LINE VOLT INPUTS  
RS485  
8K2  
9K2  
MODULATE  
1
9K1  
DDL  
COMMUNICATIONS  
2
3
FIELD WIRING  
INTERNAL WIRING  
REMOTE  
RESET  
LOW FIRE  
M23329  
1
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  
Fig. 11. Internal block diagram of the R7140L2007. (See Fig. 13 for detailed wiring.)  
66-1153—03  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
IGNITION  
5
TRANSFORMER  
6
TO  
L2  
JUMPER  
7
MAIN FUEL VALVE  
5 SECOND IGNITION  
(EARLY SPARK  
TERMINATION)  
2
WIRING  
SUBBASE  
TERMINAL  
STRIP (4)  
LOCKOUT  
INTERLOCKS  
(INCLUDING  
AIRFLOW SWITCH)  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
3
PREIGNITION  
INTERLOCKS  
4
6
15 SECOND  
INTERRUPTED  
PILOT/IGNITION  
18  
BURNER  
CONTROLLER  
LIMITS  
L1  
L2  
12  
4
MAIN FUEL  
VALVE(S)  
17  
16  
7
8
7
120V ALARM  
9
BURNER MOTOR  
(BLOWER)  
LOW FIRE  
SWITCH  
HIGH FIRE  
10  
11  
15  
14  
HIGH FIRE  
SWITCH  
COMMON  
G
13  
F
RECTIFYING FLAME  
ROD,OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
B
B
4
R
R
MODULATE  
LOW FIRE  
OR  
W
W
WHITE  
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
BLUE  
SERIES 90  
CONTROLLER  
SERIES 90  
FIRING RATE  
MOTOR  
OR  
C7061, C7927 OR  
C7076A, D  
ULTRAVIOLET  
YELLOW  
BLUE  
1
5
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
FLAME DETECTOR  
WHITE  
MASTER  
SWITCH  
6
WHITE  
L2  
C7061 OR C7076 MUST BE RATED FOR 120 V, 60Hz. TWO DETECTORS  
WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO  
THE SAME TERMINALS. C7076A, D DOES NOT HAVE LEADWIRES. (FOR  
INSTRUCTIONS, SEE FORM NUMBERS: 60-2046 FOR C7012A, C MODELS  
WITH ELECTRON TUBES; 60-2044 FOR C7012A,C,E,F SOLID STATE  
MODELS; 95-8269 FOR THE C7076A.)  
5
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
1
2
3
USE ALL NEC CLASS 1 WIRING.  
FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION  
TRANSFORMER AND MAIN FUEL VALVE(S) AS SHOWN IN INSET.  
WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7061A, E  
ULTRAVIOLET FLAME DETECTORS; C7076A, D ADJUSTABLE SENSITIVITY  
ULTRAVIOLET FLAME DETECTORS DO NOT HAVE LEADWIRES.  
6
7
4
FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER  
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A  
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE  
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION  
60-2306 FOR DETAILED INSTRUCTIONS.)  
TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING  
C7061A, E, F OR C7076A, D FLAME DETECTORS.  
M22610  
Fig. 12. Sample block diagram of field wiring for the R7140L1009, used for  
replacing R4140L Programmers with pre-ignition interlocks.  
17  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
IGNITION  
5
TRANSFORMER  
6
TO  
L2  
JUMPER  
7
MAIN FUEL VALVE (S)  
5 SECOND IGNITION  
2
WIRING  
(EARLY SPARK  
TERMINATION)  
SUBBASE  
LOCKOUT  
TERMINAL  
STRIP (4)  
INTERLOCKS  
(INCLUDING  
AIRFLOW SWITCH)  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
6
3
4
PREIGNITION  
INTERLOCKS  
15 SECOND  
INTERRUPTED  
PILOT  
18  
BURNER  
CONTROLLER  
L1  
L2  
12  
LIMITS  
MAIN FUEL  
VALVE(S)  
17  
16  
7
8
120V ALARM  
9
BURNER MOTOR  
(BLOWER)  
LOW FIRE START  
SWITCH  
HIGH FIRE  
3
10  
11  
15  
14  
HIGH FIRE  
PURGE SWITCH  
COMMON  
G
13  
F
RECTIFYING FLAME  
ROD, RECTIFYING  
PHOTOCELL, OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
B
R
B
R
MODULATE  
LOW FIRE  
OR  
W
W
WHITE  
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
BLUE  
BLUE  
SERIES 90  
FIRING RATE  
MOTOR  
SERIES 90  
CONTROLLER  
OR  
C7012A, C, C7076A, OR  
C7061  
ULTRAVIOLET  
FLAME DETECTOR  
YELLOW  
1
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
WHITE  
WHITE  
MASTER  
SWITCH  
L2  
BLACK  
BLACK  
L1  
L2  
PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
1
2
4
M22611B  
USE ALL NEC CLASS 1 WIRING.  
IN SOME INSTALLATIONS THE LOW FIRE INTERLOCK IS BETWEEN  
TERMINALS L1 AND 13.  
3
C7076 COMES WITHOUT LEADWIRES; C7061 DOES NOT HAVE BLACK LEADWIRES.  
4
Fig. 13. Block diagram of field wiring for the R7140L2007, used for replacing  
BC7000L1000 with PM720L.  
66-1153—03  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
R7140M  
INITIATE  
(INITIAL  
POWERUP  
ONLY)  
PREPURGE PFEP  
HOLD  
DRIVE TO  
LOW FIRE  
10 SEC.  
00  
(4 SEC. IF  
00  
00  
10  
20 25  
MFEP  
00  
POSTPURGE STANDBY  
POWER POWER  
15  
TIMED  
PREPURGE  
STANDBY  
POWER  
JR1 CLIPPED  
RUN  
POWER  
POWER  
POWER  
POWER  
POWER  
PILOT  
POWER  
PILOT  
LED  
DISPLAY  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
PILOT  
FLAME  
MAIN  
FLAME  
MAIN  
FLAME  
MAIN  
ALARM  
ALARM  
ALARM  
ALARM  
ALARM  
BURNER/BLOWER MOTOR  
18 IGN.  
10 SEC. IGN./PILOT  
8
BURNER  
5 SEC.  
5
INTERMITTENT PILOT VALVE  
MAIN VALVE  
6
7
OPERATING  
CONTROLS  
AND  
TO  
LIMITS AND BURNER CONTROLLER CLOSED L1  
RUNNING INTERLOCKS CLOSED  
16 TO  
PII CLOSED TO 16  
LOW FIRE SW.  
4
3
3
3
INTERLOCKS  
4
2
13  
8
TO  
FLAME PROVING  
11  
FLAME  
SIGNAL  
SSC  
SAFE START CHECK  
R7140M SWITCHING  
12  
TO  
1
TO  
14  
11  
14  
11  
TO  
10  
12  
TO  
MOTOR ACTION  
DAMPER  
MOTOR  
1
2
3
WHEN USING A SPRING RETURN ACTUATOR MOTOR, REMOVE J1 AND J2 JUMPERS LOCATED ON R7140M SUBBASE.  
PII MEANS PRE-IGNITION INTERLOCK.  
R7140M WHEN USED AS BC7000 REPLACEMENT ON R4140 WITH START INTERLOCKS L1 TO 16.  
M23331B  
Fig. 14. Operating sequence, R7140M.  
19  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
L1  
L2  
L2  
L1  
CONFIGURATION  
JUMPERS  
PURGE  
TIMER  
17  
F
FLAME  
AMPLIFIER  
G
INTERNAL  
ELECTRONICS  
3K1  
ALARM  
9
8
1R1  
6K1  
LF  
BLOWER  
START  
INTERLOCKS  
13  
4
LIMITS  
1R1  
16  
CONTROLLER  
2K1  
5K1  
4K1  
AIRFLOW  
1K1  
3
18  
5
IGN XFMR  
INTERMITTENT  
PILOT  
11  
12  
J1  
7K1  
2K2  
15 SECOND  
INTERMITTENT  
PILOT VALVE  
8K2  
9K2  
6
7
9K1  
J2  
10  
14  
MAIN VALVE  
M23335  
Fig. 15. Internal block diagram of the R7140M1007 with start interlocks. (See Fig. 17 for detailed wiring.)  
L1  
L1  
L2  
L2  
CONFIGURATION  
JUMPERS  
PURGE  
TIMER  
17  
F
FLAME  
AMPLIFIER  
G
INTERNAL  
ELECTRONICS  
3K1  
ALARM  
9
8
1R1  
6K1  
LF  
BLOWER  
PRE-  
IGNITION  
13  
16  
LIMITS  
1R1  
4
CONTROLLER  
AIRFLOW  
2K1  
5K1  
4K1  
1K1  
3
18  
5
IGN XFMR  
INTERMITTENT  
PILOT  
11  
J1  
7K1  
2K2  
15 SECOND  
12  
INTERMITTENT  
PILOT VALVE  
8K2  
9K2  
6
7
9K1  
J2  
10  
14  
MAIN VALVE  
M23336  
Fig. 16. Internal block diagram of the R7140M1007 with pre-ignition interlocks. (See Fig. 18 for detailed wiring.)  
66-1153—03  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
FOR DIRECT SPARK IGNITION OF OIL OR GAS  
5
IGNITION  
1ST STAGE  
FUEL VALVE  
6
7
TO  
L2  
2ND STAGE  
FUEL VALVE  
(OPTIONAL)  
2
WIRING  
SUBBASE  
RUNNING  
TERMINAL  
STRIP (4)  
INTERLOCKS  
(INCLUDING  
AIRFLOW SWITCH)  
5 SECOND IGNITION  
(EARLY SPARK  
TERMINATION)  
3
4
4
3
10 SECOND  
18  
5
INTERRUPTED  
PILOT/IGNITION  
BURNER  
CONTROLLER  
LIMITS  
L1  
L2  
12  
INTERMITTENT  
PILOT  
6
7
17  
16  
120V ALARM  
DAMPER  
9
10  
11  
1
MAIN FUEL  
VALVE(S)  
7
BURNER MOTOR  
CONTROL  
5
8
15  
LOW FIRE  
START SWITCH  
8
13  
F
RECTIFYING FLAME  
ROD, RECTIFYING  
PHOTOCELL, OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
14  
G
120V, 60 HZ  
POWER  
SUPPLY  
L1 (HOT)  
L2  
MASTER  
SWITCH  
OR  
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
BLUE  
WHITE  
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND  
OVERLOAD PROTECTION AS REQUIRED.  
1
OR  
2
3
USE ALL NEC CLASS 1 WIRING.  
YELLOW  
BLUE  
C7012A, C, E, OR F  
ULTRAVIOLET  
FLAME DETECTOR  
START INTERLOCKS IF USED BECOME PRE-IGNITION  
INTERLOCKS (MUST REMAIN CLOSED UNTIL IGNITION TRIALS BEGIN.)  
WHITE  
WHITE  
4
5
6
PM720M 16 TO 4 IS A PRE-IGNITION INTERLOCK.  
6
USE 2 POSITION SPRING RETURN MOTOR.  
L2  
WHITE LEADWIRES ON C7012 U.V. FLAME DETECTORS. REPLACE C7012  
WITH C7061 UV DETECTOR AND R7861A1026 AMPLIFIER.  
BLACK  
BLACK  
L1  
L2  
7
8
MAKE SURE CONNECTOR IS ON TERMINAL 16.  
REMOVE J1 AND J2 JUMPERS ON R7140M IF LOW FIRE SWITCH OR A JUMPER  
IS CONNECTED BETWEEN 8 AND 13.  
Fig. 17. R7140M1007 used on applications replacing R4140M Programmers with Start Interlocks or BC7000 with  
PM720M.  
21  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
4
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
IGNITION  
TRANSFORMER  
5
1ST STAGE  
FUEL VALVE  
6
7
TO  
L2  
2ND STAGE  
FUEL VALVE  
(OPTIONAL)  
2
5 SECOND IGNITION  
WIRING  
(EARLY SPARK  
TERMINATION)  
SUBBASE  
TERMINAL  
STRIP (4)  
RUNNING  
INTERLOCKS  
(INCLUDING  
AIRFLOW SWITCH)  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
7
PREIGNITION  
INTERLOCKS  
5
4
6
3
(P)  
INTERMITTENT  
PILOT/IGNITION  
BURNER  
LIMITS  
L1  
L2  
18  
17  
4
CONTROLLER  
(13)  
MAIN FUEL  
VALVE(S)  
7
ALARM  
9
(A)  
6
BURNER  
MOTOR  
8
DAMPER  
CONTROL  
3
12  
16  
(3)  
10  
(M)  
(11)  
(X)  
LOW FIRE  
SWITCH  
G
13  
15  
(8)  
11  
(S2)  
(D)  
(10)  
RECTIFYING FLAME  
ROD OR  
1
14  
F
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
INFRARED  
(12)  
(S1)  
5
(LEAD SULFIDE)  
FLAME DETECTOR  
MASTER  
SWITCH  
OR  
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
WHITE  
BLUE  
BLUE  
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS  
AND OVERLOAD PROTECTION AS REQUIRED.  
2
3
USE ALL NEC CLASS 1 WIRING.  
OR  
YELLOW  
WHEN USING A 2-POSITION SPRING DAMPER MOTOR, CLIP  
AND REMOVE J1 AND J2, LOCATED ON R7140 SUBBASE.  
C7061, C7012A, C,  
ULTRAVIOLET  
FLAME DETECTOR  
4
5
FOR DIRECT SPARK IGNITION (OIL OR GAS), CONNECT THE IGNITION  
AND MAIN FUEL VALVE(S) AS SHOWN IN THE INSET.  
WHITE  
WHITE  
6
L2  
FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER  
LEADWIRE MAY BE CONNECTED TO THE F TERMINAL. RUN THE C7015A  
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE  
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION  
60-2306 FOR DETAILED INSTRUCTIONS.)  
NOTE: ( ) NUMBERS ON GP101 SUBBASE.  
6
7
WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7061A OR F OR  
C7961 E, OR F ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING  
FEATURE; TERMINAL 17 IS NOT USED FOR OTHER DETECTORS. (REFER  
TO PUBLICATION 60-2358 FOR DETAILED INSTRUCTIONS.)  
M23338  
REPLACEMENT R7140M. START INTERLOCK BECOMES PRE-IGNITION INTERLOCK.  
Fig. 18. Block diagram of field wiring for the R7140M1007, used for replacing R4140M Programmers with Pre-Ignition  
Interlocks.  
66-1153—03  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
c. Ignition/pilot valve/intermittent pilot valve terminal is  
not energized.  
d. Main valve terminal is not energized.  
e. No flame is present at the end of MFEP.  
f. Internal system fault occurs.  
g. Purge card is removed.  
SAFETY SHUTDOWN  
Safety Shutdown (Lockout) occurs if  
any of the following occur during the  
indicated period:  
h. Purge card is bad.  
6. RUN Period:  
a. No flame is present.  
1. INITIATE Period:  
b. Lockout Interlock opens (R7140L).  
c. Interrupted pilot valve terminal is energized  
(R7140G,M).  
d. Main valve terminal is not energized.  
e. Internal system fault occurs.  
f. Purge card is removed.  
a. Purge card is not installed or is removed.  
b. Purge card is bad.  
c. Configuration jumpers are changed (after 200 hours  
of operation).  
d. AC line power errors occur; see Operation section.  
e. Four minute INITIATE period has been exceeded.  
2. STANDBY Period:  
g. Purge card is bad.  
7. POSTPURGE Period:  
a. Flame signal is present after 240 seconds.  
b. Pre-Ignition Interlock is open an accumulative time  
of 30 seconds.  
c. Interlock check feature is enabled and the  
Interlock String (including airflow switch) is closed  
for 120 seconds with controller closed.  
d. Ignition/pilot valve/intermittent pilot valve terminal is  
energized.  
a. Pre-Ignition Interlock does not close in five seconds  
and opens after five-second time period.  
b. Ignition/pilot valve/intermittent pilot valve terminal is  
energized.  
c. Main valve terminal is energized.  
d. Internal system fault occurs.  
e. Purge card is removed.  
f. Purge card is bad.  
e. Main valve terminal is energized.  
f. Internal system fault occurs.  
g. Purge card is not installed or is removed.  
h. Purge card is bad.  
3. PREPURGE Period:  
OPERATION  
a. Pre-Ignition Interlock opens anytime during PRE-  
PURGE period (R7140L).  
b. Flame signal is detected after first ten seconds  
during PREPURGE (R7140L).  
c. High Fire Switch fails to close within 4 minutes and  
15 seconds after the firing rate motor is commanded  
to drive to the high fire position at the start of PRE-  
PURGE (R7140L).  
Sequence of Operation  
The R7140 has the following operating sequences; see Fig. 4,  
9, and 14. The R7140 LED provides positive visual indication  
of the program sequence: POWER, PILOT, FLAME, MAIN  
and ALARM. (Note: The Power LED is lit for 4 1/2 seconds  
and off for 1/2 seconds, to indicate normal operation.)  
d. Low Fire Switch fails to close within 4 minutes and  
15 seconds after the firing rate motor is commanded  
to drive to the low fire position at the end of PRE-  
PURGE.  
e. Running Interlock does not close within 30 seconds  
(R7140G,M).  
f. Lockout Interlock does not close within 10 seconds  
(R7140L).  
g. Lockout Interlock opens during PREPURGE (R7140L).  
h. Ignition/pilot valve/intermittent pilot valve terminal is  
energized.  
Initiate  
The R7140 enters the INITIATE sequence when the Relay  
Module is powered. The R7140 can also enter the INITIATE  
sequence if the Relay Module verifies voltage fluctuations of  
+10/-15 percent or frequency fluctuations of ±10 percent  
during any part of the operating sequence. The INITIATE  
sequence lasts for ten seconds unless the voltage or  
frequency tolerances are not met. When the tolerances are  
not met, a hold condition is initiated for at least five seconds.  
When the tolerances are met, the INITIATE sequence  
restarts. If the condition is not corrected and the hold condition  
exists for four minutes, the R7140 locks out. Causes for hold  
conditions in the INITIATE sequence:  
i. Main valve terminal is energized.  
j. Internal system fault occurs.  
k. Purge card is removed.  
l. Purge card is bad.  
4. PILOT FLAME ESTABLISHING Period (PFEP):  
a. Low Fire Switch opens.  
a. AC line dropout is detected.  
b. AC line noise prevents a sufficient reading of the line  
voltage inputs.  
b. Lockout Interlock opens (RM7140L).  
c. Ignition/pilot valve/intermittent pilot valve terminal is  
not energized.  
d. Early spark termination terminal is energized after  
five seconds.  
c. Low line voltage brownouts occur.  
The INITIATE sequence also delays the burner motor starter  
from being energized and de-energized from an intermittent  
AC line input or control input.  
e. No flame is present at the end of PFEP.  
f. Main valve terminal is energized (R7140G,M).  
g. Internal system fault occurs.  
h. Purge card is removed.  
i. Purge card is bad.  
Standby  
The R7140 is ready to start an operating sequence when the  
operating control determines a call for heat is present. The  
burner switch, limits, operating control and all microcomputer  
monitored circuits must be in the correct state for the R7140 to  
continue into the PREPURGE sequence.  
5. MAIN FLAME ESTABLISHING Period (MFEP):  
a. Low Fire Switch Opens.  
b. Lockout Interlock opens (R7140L).  
23  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
2. Main Flame Establishing Period (MFEP):  
a. Terminal 7 is energized when the presence of flame is  
verified at the end of a 10-second Pilot Flame Estab-  
lishing Period (PFEP) (four seconds if JR1 is clipped).  
b. Terminal 5 is turned off 10 seconds after terminal 7  
is energized.  
Normal Start-Up Pre-Purge  
The R7140 provides a pre-purge timing selectable from two  
seconds to 30 minutes with power applied and the R7140  
operating control indicating a call for heat:  
a. Running Interlocks, Pre-Ignition Interlocks, Burner  
Switch, Run/Test Switch, Lockout Interlocks and all  
microcomputer monitored circuits must be in the  
correct operating state.  
b. The blower motor output, terminal 8, is powered to  
start the PREPURGE sequence. The PREPURGE  
timing for the R7140L does not begin until the High  
Fire Switch is closed.  
c. Terminal 6 action:  
(1) R7140L: De-energized 15 seconds after terminal  
7 is energized.  
(2) R7140G:  
(a)Not turned off, or  
(b)15 seconds after terminal 7 is energized and  
JR2 is clipped, or  
(c)30 seconds after terminal 7 is energized and  
terminals 8 and 15 are jumpered and jumper  
JR2 is clipped.  
NOTE: A jumpered High Fire Switch adds a 30-second  
hold before the purge time starts.  
(3) R7140M: Remain energized as long as call for  
heat is present.  
c. The Pre-Ignition Interlock input must remain closed  
throughout PREPURGE; otherwise, control returns to  
the STANDBY state and holds (30 seconds) for the  
R7140G,M or safety shutdown for the R7140L occurs.  
d. The Lockout Interlock or Running Interlock inputs  
(interlock circuit including Airflow Switch) must close  
by ten seconds into PREPURGE; otherwise, a  
recycle to the beginning of PREPURGE for the  
R7140G,M will happen or a safety shutdown for the  
R7140L occurs.  
e. When PREPURGE timing is complete, the firing rate  
motor drives to the low fire position. If a damper  
motor is used (R7140M), jumpers J1 and J2 should  
be removed from R7140 subbase.  
Run  
1. Fifteen seconds after the main valve terminal 7 is  
energized and flame is maintained, the R7140 goes to  
Run.  
2. The firing rate motor releases to modulation  
(R7140G,L). Damper motor is energized (R7140M).  
3. The R7140 is now in RUN and remains in RUN until the  
controller input, terminal 16 or 4 (model dependent),  
opens, indicating that the demand is satisfied or a limit  
opened.  
Postpurge  
f. When the firing rate motor reaches low fire position,  
the Low Fire Switch, terminal 13, is energized to  
enter the Ignition Trial state.  
The R7140 provides a 15-second POSTPURGE following the  
completion of the RUN period (call for heat ends). The blower  
motor output remains powered to drive all products of  
combustion and any unburned fuel from the combustion  
chamber. It also supplies combustion air to burn fuel being  
purged from the fuel line downstream of the fuel shutoff valve.  
NOTE: A 30-second hold occurs for a jumpered Low Fire  
Switch before the ignition trial period begins.  
Ignition Trials  
1. The main fuel valve and intermittent pilot valve,  
terminals 7 and 6, are de-energized and the firing rate  
motor is commanded to the low fire position to begin the  
POSTPURGE period.  
2. After the 15-second POSTPURGE period is completed,  
the blower motor (terminal 8) is de-energized and the  
R7140 reenters Standby.  
1. Pilot Flame Establishing Period (PFEP):  
a. With the firing rate motor at the low fire position:  
(1) The pilot valve and ignition transformer,  
terminals 5, 6, and 18, are energized.  
(a)The R7140G has an interrupted or intermit-  
tent pilot valve, terminal 6, depending on the  
selection of configuration jumper 2.  
(b) The R7140L has a 15-second interrupted  
pilot valve, terminal 6.  
(c)The R7140M has an intermittent pilot valve,  
terminal 6.  
Run/Test Switch  
NOTE: All of the R7140s have a ten-second interrupted  
pilot valve/ignition, terminal 5.  
WARNING  
Explosion Hazard.  
Can cause serious injury or death.  
(2) During PFEP, the Low Fire Switch must remain  
closed. If it opens, a safety shutdown occurs.  
(3) The Pre-Ignition Interlock input is ignored  
throughout the Ignition Trial state.  
Do not use the Run/Test switch during the Pilot Flame  
Establishing Period for the R7140 when using Direct  
Spark Function, because it turns on the main gas  
valve, causing an accumulation of fuel in the burner.  
b. Flame must be proven by the end of the 10-second  
PFEP (four if JR1 is clipped) to allow the sequence  
to continue. If flame is not proven by the end of  
PFEP, a safety shutdown occurs.  
c. After five seconds, the ignition, terminal 18, is  
de-energized for early spark termination.  
The Run/Test Switch is located on the top side of the R7140,  
see Fig. 1. The Run/Test Switch allows the burner sequence  
to be altered as follows:  
66-1153—03  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
1. In Pre-Purge Drive To High Fire Position (R7140L), the  
Run/Test Switch, when placed in the TEST position,  
holds in PREPURGE with the firing rate motor in the  
High Fire position.  
2. In the measured PREPURGE sequence, the Run/Test  
Switch, when placed in the TEST position, causes the  
PREPURGE timing to stop. The firing rate motor is in  
the High Fire position.  
3. In Pre-Purge Drive to Low Fire position, the Run/Test  
Switch, when placed in the TEST position, holds the  
burner sequence in PREPURGE with the firing rate  
motor in the Low Fire position.  
4. In PFEP, the Run/Test Switch, when placed in the TEST  
position, stops the timer during the first 8 seconds when a  
10-second PFEP is selected or during the first 3 seconds  
when a 4-second PFEP is selected, allowing pilot-turn-  
down test and other burner adjustments to be made. This  
activates a 15-second flameout timer that permits pilot  
flame adjustment without nuisance safety shutdowns. The  
Run/Test Switch is ignored during PFEP for the R7140L if  
terminals 5 and 7 or 7 and 6 are jumpered.  
SETTINGS AND ADJUSTMENTS  
Selectable Site-Configurable  
Jumpers  
The R7140 has three site-configurable jumper options; see  
Fig. 19 and Table 7. If necessary, clip the site-configurable  
jumpers with side cutters and remove the resistors from the  
Relay Module.  
The R7140M has two additional jumpers located on the back  
of the chassis. These must be cut if a spring return damper  
motor is used.  
SELECTABLE CONFIGURATION JUMPERS  
RUN/TEST SWITCH  
5. During Run, the Run/Test Switch, when placed in the  
TEST position, drives the firing rate motor to the Low  
Fire position.  
NOTE: When R7140 is switched to the Test mode, it stops  
and holds at the next Run/Test Switch point in the  
operating sequence. Make sure that the Run/Test  
Switch is in the RUN position before leaving the  
installation.  
NOTE: CONFIGURATION JUMPERS SHOWN FOR RM7800G/RM7840G.  
M12301  
Fig. 19. Selectable site-configurable jumpers.  
Table 7. Site Configurable Jumper Options.  
Jumper Number  
JR1  
Description  
Intact  
Clipped  
RM7800/RM7840 Type  
Pilot Flame Establishing  
Period (PFEP)  
10 seconds  
4 seconds  
All  
a
b
JR2  
10 seconds  
Intermittent  
R7140G  
All  
Pilot Valve /Main Flame  
15 or 30 seconds Interrupted  
Establishing Period (MFEP)  
JR3  
Start-up Interlock Check  
Disabled  
Enabled  
a
b
Pilot Valve/First Stage Oil Valve (Valve/Start) terminal 6.  
A 30 second MFEP can be accomplished by adding a jumper wire between terminals 15 and 8.  
SERVICE NOTE: Clipping and removing these site-configurable jumpers enhances the level of safety. Removal after 200 hours of  
main valve operation will result in a hard lockout, Code 110.  
25  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
3. When jumpered to Ignition, Pilot and Main Valves, use  
STATIC CHECKOUT  
ammeter in series and verify proper current draw.  
After checking all wiring, perform this checkout before  
installing the R7140 on the subbase. These tests verify the  
Q520A Wiring Subbase is wired correctly, and the external  
controllers, limits, interlocks, actuators, valves, transformers,  
motors and other devices are operating properly.  
General Instructions  
1. Perform all applicable tests listed in Static Checkout,  
Table 8, in the order listed.  
2. Make sure all manual fuel shutoff valve(s) are closed.  
3. Perform only those tests designated for the specific  
R7140 model being tested.  
WARNING  
4. Raise the setpoint of the operating controller to simulate  
a call for heat.  
5. For each test, open the master switch and install the  
jumper wire(s) between the subbase wiring terminals  
listed in the Test Jumpers column.  
6. Close the master switch before observing operation.  
7. Read the voltage between the subbase wiring terminals  
listed in the Voltmeter column.  
8. If there is no voltage or the operation is abnormal, check  
the circuits and external devices as described in the last  
column.  
9. Check all wiring for correct connections, tight terminal  
screws, correct wire, and proper wiring techniques.  
Replace all damaged or incorrectly sized wires.  
10. Replace faulty controllers, limits, interlocks, actuators,  
valves, transformers, motors and other devices as  
required.  
Explosion and Electrical Shock Hazard.  
Can cause serious injury, death, or equipment  
damage.  
1. Close all manual fuel shutoff valve(s) before starting  
these tests.  
2. Use extreme care while testing the system. Line  
voltage is present on most terminal connections  
when power is on.  
3. Open the master switch before installing or  
removing a jumper on the subbase.  
4. Before continuing to the next test, be sure to  
remove test jumper(s) used in the previous test.  
5. Replace all limits and interlocks that are not operating  
properly. Do not bypass limits and interlocks.  
11. Make sure normal operation is obtained for each  
required test before continuing the checkout.  
12. After completing each test, be sure to remove the test  
jumper(s).  
CAUTION  
Equipment Damage Hazard.  
Improper testing can damage equipment.  
Internal surge protectors can break down and conduct  
a current, causing the R7140 to fail the dielectric test  
or possibly destroy the internal lightning and high  
current protection. Do not perform a dielectric test with  
the R7140 installed.  
WARNING  
Explosion Hazard.  
Can cause serious injury or death.  
Make sure all manual fuel shutoff valves are closed  
before performing static checkout.  
Equipment Recommended  
1. Voltmeter (1M ohm/volt minimum sensitivity) set on the  
0-300 Vac scale.  
2. Two jumper wires; no. 14 wire, insulated, 12 inches  
(304.8 mm) long with insulated alligator clips at both ends.  
Table 8. Static Checkout.  
Test  
Test  
If Operation is Abnormal,  
Check the Items Listed Below  
No. R7140 Models Jumpers Voltmeter  
Normal Operation  
1
2
All  
None  
L1-L2  
16-L2  
Line voltage at terminal L1.  
1. Master Switch.  
2. Power connected to the Master Switch.  
3. Overload protection (fuse, circuit breaker,  
etc.) has not opened the power line.  
Line voltage at terminal 16 (4 on 1. Limits.  
Pre-Ignition Interlock devices).  
2. Burner Controller.  
3
4
4-L2  
3-L2  
Line voltage at terminal 16.  
1. Pre-Ignition interlocks.  
L1-8  
1. Burner motor (fan or  
blower) starts.  
2. Line voltage at terminal 3  
within 10 seconds.  
1. Burner motor circuit.  
a. Manual switch of burner motor.  
b. Burner motor power supply, overload  
protection, and starter.  
c. Burner motor.  
2. Running or Lockout Interlocks (including  
Airflow Switch).  
5
L1-18  
Ignition spark (if ignition  
transformer is connected to  
terminal 18).  
1. Watch for spark or listen for buzz.  
a. Ignition electrodes are clean.  
b. Ignition transformer is okay.  
66-1153—03  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
R7140G,L,M BURNER CONTROL MODULES  
Table 8. Static Checkout. (Continued)  
Test  
Test  
If Operation is Abnormal,  
Check the Items Listed Below  
No. R7140 Models Jumpers Voltmeter  
Normal Operation  
6
All  
L1-5  
1. Ignition spark (if ignition  
transformer is connected to  
terminal 5).  
1. Watch for spark or listen for buzz.  
a. Ignition electrodes are clean.  
b. Ignition transformer is okay.  
2. Automatic pilot valve opens (if 2. Listen for click or feel head of valve for  
connected to terminal 5).  
activation.  
a. Actuator, if used.  
b. Pilot valve.  
NOTE: Refer to wiring dia-  
gram of system being  
tested.  
7
8
L1-6  
L1-7  
Same as test no. 6 for  
connections to terminal 5. If  
using direct spark ignition, check instead of the pilot valve.  
the first stage fuel valve(s)  
instead of the pilot valve.  
Same as test no. 6. If using direct spark  
ignition, check the first stage fuel valve(s)  
Automatic main fuel valve(s)  
open.  
1. Listen for and observe operation of the  
main fuel valve(s) and actuator(s).  
If using direct spark ignition on a 2. Valve(s) and actuator(s).  
model with intermittent pilot on  
terminal 6, check the optional  
second stage fuel valve, if used.  
9
L1-9  
Alarm (if used) turns on.  
1. Alarm.  
10  
R7140G,L  
R7140G,L  
R7140G,L  
R7140L  
L1-8  
and  
10-11  
13-L2  
Firing rate motor drives open;  
zero volts at terminal 13 after  
motor starts driving open.  
1. Low Fire Start Switch.  
2. Firing rate motor and transformer.  
11  
12  
13  
14  
L1-8  
and  
14-11  
13-L2  
15-L2  
15-L2  
Firing rate motor drives closed; 1. Low Fire Start Switch.  
line voltage at terminal 13 after 2. Firing rate motor and transformer.  
motor is in Low Fire position.  
L1-8  
and  
10-11  
Firing rate motor drives open;  
line voltage at terminal 15 after 2. Firing rate motor and transformer.  
motor is in High Fire position.  
1. High Fire Purge Switch.  
L1-8  
and  
14-11  
Firing rate motor drives closed; 1. Low Fire Start Switch.  
zero volts at terminal 15 after  
motor starts driving closed.  
2. Firing rate motor and transformer.  
R7140G,L  
11-12  
1. Raise setpoint of Series 90  
controller—firing rate motor  
should drive toward open.  
2. Lower setpoint of Series 90  
controller—firing rate motor  
should drive toward closed.  
1. Series 90 Controller.  
2. Firing rate motor and transformer.  
15  
16  
R7140M with  
open damper  
contacts.  
14-11  
L1-8  
If damper motor is used, motor Damper motor.  
drives damper open.  
R7140M with  
open damper  
contacts.  
13-L2  
If damper motor is used, motor 1. Low Fire Start Switch.  
drives open; line voltage at  
terminal 13 after motor is in Low  
Fire position.  
2. Damper motor.  
17  
R7140M with  
open damper and  
contacts. L1-11  
L1-8  
13-L2  
If damper motor is used, motor 1. Low Fire Start Switch.  
drives open; zero volts at  
terminal 13.  
2. Damper motor.  
Final All  
CAUTION  
Equipment Damage Hazard.  
Improper wiring can damage equipment.  
On completing these tests, open the master switch and remove all test jumpers from the  
subbase terminal. Also remove bypass jumpers from the low fuel pressure limits (if used) to  
prevent equipment damage.  
27  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Limit trial for pilot to ten seconds. Limit the attempt to light  
main burner to two seconds after fuel reaches burner nozzle.  
Do not exceed manufacturer nominal lightoff time.  
SYSTEM CHECKOUT  
IMPORTANT  
Perform all Static Checkout Procedures for the  
applicable relay module shown in Table 8 before  
starting these procedures.  
CAUTION  
Equipment Malfunction or Damage Hazard.  
Incorrect wiring can cause equipment damage.  
Each relay module type is unique. Using existing  
wiring on a relay module change can cause equipment  
damage.  
WARNING  
Explosion Hazard.  
Can cause serious injury or death.  
Do not allow fuel to accumulate in the combustion  
chamber for longer than a few seconds without igniting  
to prevent danger of forming explosive mixture.  
Close manual fuel shutoff valve(s) if flame is not  
burning at end of specified time.  
IMPORTANT  
1. If the system fails to perform properly, refer to the  
Troubleshooting section.  
2. Repeat all required Checkout tests after all  
adjustments are made. All tests must be satisfied  
with the flame detector(s) in their final position.  
WARNING  
Equipment Recommended  
Electric Shock Hazard.  
S7800A Keyboard Display Module  
Can cause serious injury or death.  
1. Use extreme care while testing system. Line voltage  
is present on most terminal connections when  
power is on.  
Volt-ohmmeter (1M ohm/volt minimum sensitivity) with:  
0-300 Vac capability.  
0-6000 ohm capability.  
0-10 Vdc capability.  
2. Open master switch before removing or installing  
R7140 Relay Module.  
Make sure all manual fuel shutoff valve(s) are closed before  
starting initial lightoff check and Pilot Turndown tests.  
Checkout Summary  
Table 9 provides an overview of checkout steps performed for  
each applicable system.  
Do not put the system in service until you have satisfactorily  
completed all applicable tests in this section and any others  
recommended by the original equipment manufacturer.  
See Installation Instructions for location of component parts  
and terminal locations.  
Table 9. Checkout Steps and Applicable Detection Systems.  
Piloted  
Infrared Flame Flame Rod  
Ultraviolet  
Checkout Step  
Preliminary Inspection  
Systems DSI Systems  
Detectors  
Systems Flame Detectors  
X
X
X
X
X
X
X
X
X
X
X
Flame Signal Measurement  
Initial Lightoff Check for Proved Pilot  
Initial Lightoff Check for Direct Spark Ignition  
Pilot Turndown Test  
X
X
X
X
Ignition Interference Test  
X
X
Hot Refractory Saturation Test  
Hot Refractory Hold-in Test  
X
X
X
X
X
X
X
Ignition Spark Pickup  
Response to Other Ultraviolet Sources  
Flame Signal with Hot Combustion Chamber  
Safety Shutdown Tests  
X
X
X
X
X
X
X
X
3. Combination of amplifier and flame detector(s) is  
correctly used. See the amplifier specifications.  
4. Plug-in amplifier and purge card (if required) are  
securely in place.  
Preliminary Inspection  
Perform the following inspections to avoid common problems.  
Make certain that:  
5. Burner is completely installed and ready to fire; consult  
equipment manufacturer instructions. Fuel lines are  
purged of air.  
6. Combustion chamber and flues are clear of fuel and fuel  
vapor.  
1. Wiring connections are correct and all terminal screws  
are tight.  
2. Flame detector(s) is clean, installed and positioned  
properly. Consult the applicable Instructions.  
66-1153—03  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
7. Power is connected to the system disconnect switch  
(master switch).  
8. Lockout is reset (reset button) only if the Relay Module  
is powered.  
9. Run/Test Switch (if present) is in RUN position.  
10. System is in STANDBY condition. STANDBY message  
is displayed in the S7800 Keyboard Display Module.  
11. All limits and interlocks are reset.  
g. After a continuous spark is obtained, open the  
master switch and add a jumper on the subbase  
from terminal L1 power to the pilot terminal 5 or 6.  
Reconnect the leadwire from the pilot valve if it was  
disconnected in step b.  
h. Close the master switch to energize both the ignition  
transformer and the pilot valve.  
i. If the pilot does not ignite and if the ignition spark is  
still continuous, adjust the pressure regulator until a  
pilot is established.  
j. When the pilot ignites properly and stays ignited,  
open the master switch and remove the jumper(s)  
from the terminals of the subbase.  
Flame Signal Measurement  
See instructions provided with the amplifier.  
k. Check for adequate bleeding of the fuel line.  
l. Reinstall the R7140 Relay Module on the subbase,  
close the master switch, and then return to step 4.  
7. When pilot ignites, measure the flame signal. If the pilot  
flame signal is unsteady or approaching the 1.25 Vdc  
minimum value, adjust the pilot flame size or detector  
sighting to provide a maximum and steady flame signal.  
8. Recycle the system to recheck lightoff and pilot flame  
signal.  
9. When the MAIN LED turns on, make sure the automatic  
main fuel valve is open; then smoothly open the manual  
main fuel shutoff valve(s) and watch for main burner  
flame ignition. When the main burner flame is  
established, go to step 16.  
10. If the main burner flame is not established within five  
seconds or the normal lightoff time as specified by the  
equipment manufacturer, close the manual main fuel  
shutoff valve(s).  
11. Recycle the system to recheck the lightoff and pilot  
flame signal.  
12. Smoothly open the manual fuel shutoff valve(s) and try  
lightoff again. (The first re-attempt may have been  
required to purge the lines and bring sufficient fuel to the  
burner.)  
13. If the main burner flame is not established within five  
seconds or the normal lightoff time specified by the  
equipment manufacturer, close the manual main fuel  
shutoff valves(s). Check all burner adjustments.  
14. If the main burner flame is not established after two  
attempts:  
INITIAL LIGHTOFF CHECKS  
Proved Pilot Systems  
Perform this check on all installations that use a pilot. It should  
immediately follow the preliminary inspection.  
NOTE: Low fuel pressure limits, if used, could be open.  
If so, bypass them with jumpers during this  
check.  
1. Open the master switch.  
2. Make sure that the manual main fuel shutoff valve(s) is  
closed. Open the manual pilot shutoff valve. If the pilot  
takeoff is downstream from the manual main fuel shutoff  
valve(s), slightly open the manual main valve to supply  
pilot gas flow. Make sure the main fuel is shut off just  
upstream from the burner inlet, or disconnect power  
from the automatic main fuel valve(s).  
3. Close the master switch and start the system with a call  
for heat by raising the setpoint of the operating  
controller; see the relay module sequence. The R7140  
Relay Module should start a ten-second INITIATE  
sequence.  
4. Let the sequence advance to PILOT IGN (status is  
displayed on the Keyboard Display Module, if used),  
PILOT LED turns on, ignition spark should occur and  
the pilot should light. If the pilot ignites, the FLAME LED  
is energized. Go to step 7.  
5. If the pilot flame is not established in ten seconds (four  
seconds if configuration jumper JR1 is clipped), safety  
shutdown occurs. Let the sequence complete its cycle.  
6. Push the reset push button, and let the system recycle  
once. If the pilot still does not ignite, make the following  
ignition/pilot adjustments:  
a. Check for improper pilot size.  
b. Check for excess combustion air at Low Fire.  
c. Check for adequate Low Fire fuel flow.  
d. Check for proper gas supply pressure.  
e. Check for proper valve operation.  
f. Check for proper pilot flame positioning.  
15. Repeat steps 8 and 9 to establish the main burner  
flame; then go to step 16.  
16. With the sequence in RUN, make burner adjustments  
for flame stability and Btu input rating.  
a. Open the master switch and remove the R7140  
Relay Module from the subbase.  
b. On the subbase, jumper L1 to the ignition terminal;  
refer to the appropriate wiring diagram to determine  
the proper terminal. Disconnect the leadwire to the  
pilot valve if it is connected to the same terminal.  
c. Close the master switch to energize only the ignition  
transformer.  
d. If the ignition spark is not strong and continuous,  
open the master switch and adjust the ignition  
electrode spark gap setting to the manufacturer  
recommendation.  
17. Shut down the system by opening the burner switch or  
by lowering the setpoint of the operating controller.  
Make sure the main flame goes out. There may be a  
delay due to gas trapped between the valve(s) and  
burner. Make sure all automatic fuel valve(s) close.  
18. Restart the system by closing the burner switch and/or  
raising the setpoint of the operating controller. Observe  
that the pilot is established during PILOT IGN and the  
main burner flame is established during MAIN IGN  
within the normal lightoff time.  
19. Measure the flame signal. Continue to check for the  
proper signal through the RUN period. Check the signal  
at both High and Low Firing Rate positions and while  
modulating, if applicable.  
e. Make sure the ignition electrodes are clean.  
f. Close the master switch and observe the spark.  
29  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
20. Run the burner through another sequence, observing  
the flame signal for:  
16. Shut down the system by opening the burner switch or  
by lowering the setpoint of the operating controller.  
Make sure the burner flame goes out and all automatic  
fuel valves close.  
a. Pilot flame alone.  
b. Pilot and main flame together.  
c. Main flame alone (unless monitoring an intermittent  
pilot). Also observe the time it takes to light the main  
flame. Ignition of main flame should be smooth.  
21. Make sure all readings are in the required ranges before  
proceeding.  
17. If used, remove the bypass jumpers from the low fuel  
pressure limit and subbase.  
18. If a second stage is used, make sure the automatic  
second stage fuel valve(s) opened. Check the lightoff as  
follows (or go to step 19):  
22. Return the system to normal operation.  
a. Open the manual second stage fuel valve(s).  
b. Restart the system by raising the setpoint of the  
operating controller.  
c. When the first stage burner flame is established, watch  
for the automatic second stage fuel valve(s) to open.  
Observe that the second stage lights off properly.  
d. Make burner adjustments for flame stability and  
input rating.  
NOTE: After completing these tests, open the master  
switch and remove all test jumpers from the  
subbase terminals, limits/controls or switches.  
Direct Spark Ignition Systems  
This check applies to gas and oil burners not using a pilot. It  
should immediately follow the preliminary inspection. Refer to  
the appropriate sample block diagram of field wiring for the  
ignition transformer and fuel valve(s) hookup.  
e. Shut down the system by lowering the setpoint of  
the operating controller. Make sure the burner flame  
goes out and all automatic fuel valves close.  
f. Go to step 19.  
19. Restart the system by closing the burner switch and/or  
raising the setpoint of the operating controller. Observe  
that the burner flame is established during PILOT IGN,  
within the normal lightoff time specified by the  
equipment manufacturer.  
20. Measure the flame signal. Continue to check for the proper  
signal through the RUN period. Check the signal at both  
high and low firing rate positions and while modulating. Any  
pulsating or unsteady readings require further attention.  
21. Make sure all readings are in the required ranges before  
proceeding.  
NOTE:Low fuel pressure limits, if used, could be open. If so,  
bypass them with jumpers during this check.  
1. Open the master switch.  
2. Complete the normal ready-to-fire checkout of the fuel  
supply and equipment as recommended by the  
equipment manufacturer.  
3. Close all manual main fuel shutoff valve(s). Check that  
the automatic fuel valve(s) is closed. Make sure fuel is  
not entering the combustion chamber.  
4. Close the master switch and start the system with a call  
for heat by raising the setpoint of the operating  
controller; see the relay module sequencing. The  
program sequence should start the INITIATE sequence.  
5. Let the sequence advance through PREPURGE (if  
applicable). Ignition spark should occur when the PILOT  
LED turns on. Listen for the click of the first stage fuel  
solenoid valve(s). The relay module locks out and the  
ALARM LED turns on.  
NOTE: On completing these tests, open the master  
switch and remove all test jumpers from the  
subbase terminals, limits/controls or switches.  
22. Return the system to normal operation.  
PILOT TURNDOWN TEST (ALL  
INSTALLATIONS USING A  
PILOT)  
Perform this check on all installations that use a pilot. The  
purpose of this test is to verify that the main burner can be lit  
by the smallest pilot flame that can hold in the flame amplifier  
and energize the FLAME LED. Clean the flame detector(s) to  
make sure that it detects the smallest acceptable pilot flame. If  
using AMPLI-CHECK™ or self-checking amplifier and 1M  
ohm/volt meter, the flame signal fluctuates every time the  
amplifier does a self-check or a shutter check.  
6. Let the R7140 Relay Module complete its cycle.  
7. Open the manual fuel shutoff valve(s).  
8. Push the reset button and the relay module recycles the  
program sequence through PREPURGE (if applicable).  
9. When the PILOT LED turns on, make sure that the first  
stage burner flame is established. If it is, go to step 15.  
10. If the first stage burner flame is not established within  
four seconds, or within the normal lightoff time specified  
by the equipment manufacturer, close the manual fuel  
shutoff valve(s), and open the master switch.  
11. Check all burner adjustments.  
12. Wait about three minutes. Close the master switch,  
open the manual fuel shutoff valve(s), and try to light off  
the burner again. The first attempt may be required to  
purge the lines and bring sufficient fuel to the burner.  
13. If the first stage burner flame is not established within  
four seconds, or within the normal lightoff time specified  
by the equipment manufacturer, close the manual fuel  
shutoff valve(s), and open the master switch.  
NOTE: Low fuel pressure limits, if used, could be open.  
If so, bypass them with jumpers during this test.  
1. Open the master switch.  
2. Close the manual main fuel shutoff valve(s).  
3. Connect a manometer (or pressure gauge) to measure  
pilot gas pressure during the turndown test.  
4. Open the manual pilot shutoff valve(s).  
5. Close the master switch and start the system with a call  
for heat. Raise the setpoint of the operating controller.  
The 7800 Series sequence should start, and PRE-  
PURGE (if applicable) should begin.  
14. If necessary, repeat steps 11 through 13 to establish the  
first stage burner flame. Then go to step 15.  
15. When the first stage burner flame is established, the  
sequence advances to RUN. Make burner adjustments  
for flame stability and input rating. If a second stage is  
used, go to step 18.  
66-1153—03  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
6. After the PILOT LED turns on in interrupted pilot  
applications, set the Run/Test Switch to the TEST  
position to stop the sequence. The FLAME LED comes  
on when the pilot ignites.  
IGNITION INTERFERENCE TEST  
(ALL FLAME RODS)  
Ignition interference can subtract from (decrease) or add to  
(increase) the flame signal. If it decreases the flame signal  
enough, it causes a safety shutdown. If it increases the flame  
signal, it could cause the FLAME LED to come on when the  
true flame signal is below the minimum acceptable value.  
NOTE: If the sequence does not stop, reset the system  
and make sure you set the Run/Test Switch to  
TEST within the first eight seconds of the PILOT  
IGN sequence.  
IMPORTANT  
Start the burner and measure the flame signal with both  
ignition and pilot (or main burner) on, and then with only the  
pilot (or main burner) on. Any significant difference (greater  
than 0.5 Vdc) indicates ignition interference.  
You have 0.8 second or three seconds, depending on  
PFEP selected, to position the Run/Test Switch to  
the TEST position to stop the sequence after the  
start of the PILOT IGN period.  
7. Turn down the pilot pressure very slowly, reading the  
manometer (or pressure gauge) as it drops. Stop instantly  
when the FLAME LED goes out. Note the pressure. The  
pilot is at the minimum turndown position. Immediately  
turn up the pilot pressure until the FLAME LED comes on  
again or the flame signal increases to 1.25 Vdc.  
To Eliminate Ignition Interference  
1. Make sure there is enough ground area.  
2. Be sure the ignition electrode and the flame rod are on  
opposite sides of the ground area.  
3. Check for correct spacing on the ignition electrode:  
a. 6000V systems—1/16 to 3/32 in. (1.6 to 2.4 mm).  
b. 10,000V systems—1/8 in. (3.2 mm).  
4. Make sure the leadwires from the flame rod and ignition  
electrode are not too close together.  
NOTE: If there is no flame for 15 seconds with the  
RUN/TEST switch in the TEST position, the relay  
module locks out.  
5. Replace any deteriorated leadwires.  
6. Try wrapping the ignition wire with an insulated wire (No.  
18 stranded, for example). See Fig. 13.  
7. Strip the insulation nearest the ignitor and ground it;  
also, strip the insulation nearest the ignition transformer  
and ground it.  
8. If the problem cannot be eliminated, consider changing  
the system to an ultraviolet flame detection system.  
8. Repeat step 7 to verify the pilot gas pressure reading at  
the exact point the FLAME LED light goes out.  
9. Increase the pilot pressure immediately until the FLAME  
LED comes on, and then turn it down slowly to obtain a  
pressure reading just above the dropout point or until  
the flame signal increases to 1.25 Vdc.  
10. Set the Run/Test Switch in the RUN position (if used)  
and let the sequence proceed. When the MAIN LED  
turns on, make sure the automatic main fuel valve(s)  
opens; then smoothly open the manual main fuel shutoff  
valve(s) (or any other manually-opened safety shutoff  
valve(s), if used) and watch for main burner ignition. If  
the main burner flame is established, go to step 18.  
IGNITION  
TRANSFORMER  
NOTE: This step requires two people, one to open the  
manual valve(s) and one to watch for ignition.  
BURNER ASSEMBLY  
IGNITION  
LEAD  
11. If the main burner flame is not established within five  
seconds, or within the normal lightoff time specified by  
the equipment manufacturer, close the manual main fuel  
shutoff valve(s) and open the master switch. If the light-  
off is rough, the pilot flame size is too small.  
12. Close the master switch to recycle the burner and stop  
the sequence in the PILOT period by using the Run/Test  
Switch.  
BURNER  
MODULE  
13. Increase the pilot flame size by increasing its fuel flow  
until a smooth main flame is accomplished.  
14. Reposition the flame scanner sight tube or use orifices  
until the pilot flame signal voltage is in the range of 1.25  
to 1.50 Vdc.  
15. When the main burner lights reliably with the pilot at  
turndown, disconnect the manometer (or pressure  
gauge) and turn up the pilot gas flow to that recom-  
mended by the equipment manufacturer.  
16. If used, remove the bypass jumpers from the subbase  
terminals, limits/controls, or switches.  
17. Run the system through another cycle to check for  
normal operation.  
FLAME ROD  
LEAD  
M19423B  
Fig. 20. Eliminating ignition interference.  
Hot Refractory Saturation Test  
(All Infrared Detectors)  
Start the burner and monitor the flame signal during the  
warm-up period. A decrease in signal strength as the  
refractory heats up indicates hot refractory saturation. If  
saturation is extreme, the flame signal drops below 1.25 Vdc  
and the system shuts down as though a flame failure occurred.  
18. Return the system to normal operation.  
31  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
If hot refractory saturation occurs, the condition must be  
corrected. Add an orifice plate in front of the cell to restrict the  
viewing area, lengthen the sight pipe or decrease the pipe  
size (diameter). Continue adjustments until hot refractory  
saturation is eliminated.  
IGNITION SPARK RESPONSE  
TEST (ALL ULTRAVIOLET  
DETECTORS)  
Test to make certain that the ignition spark is not actuating the  
FLAME LED:  
Hot Refractory Hold-in Test  
(Rectifying Photocell, Infrared  
Detectors, Ultraviolet Detectors)  
1. Close the pilot and main burner manual fuel shut-off  
valve(s).  
2. Start the burner and use the Run/Test Switch (if  
available) to stop the sequence in the PILOT IGN  
period. Ignition spark should occur, but the flame signal  
should not be more than 0.5 Vdc.  
This condition can delay response to flame failure and also  
can prevent a system restart if hot refractory is detected.  
3. If the flame signal is higher than 0.5 Vdc and the FLAME  
LED does come on, consult the equipment operating  
manual and resight the detector farther out from the  
spark, or away from possible reflection. It may be neces-  
sary to construct a barrier to block the ignition spark  
from the detector view. Continue adjustments until the  
flame signal due to ignition spark is less than 0.5 Vdc.  
Infrared (lead sulfide) detectors can respond to infrared rays  
emitted by a hot refractory, even when the refractory has  
visibly ceased to glow. Infrared radiation from a hot refractory  
is steady, but radiation from a flame has a flickering  
characteristic. The infrared detection system responds only to  
flickering infrared radiation; it can reject a steady signal from  
hot refractory. The refractory steady signal can be made to  
fluctuate if it is reflected, bent or blocked by smoke or fuel mist  
within the combustion chamber. Be careful when applying an  
infrared system to verify its response to flame only.  
NOTE: The Honeywell Q624A and Q652B Solid State  
Spark Generators prevent detection of ignition  
spark when properly applied with C7027, C7035,  
C7044 or C7061 Ultraviolet Flame Detectors. The  
Q624A and Q652B are only for use with gas  
pilots.  
The ultraviolet detector can respond to hot refractory above  
2300°F (1371°C).  
1. Operate the burner until the refractory reaches its  
maximum temperature (Infrared Only). If the installation  
has a multi-fuel burner, burn the heavier fuel that is most  
likely to reflect, bend or obscure the hot refractory  
steady infrared radiation.  
2. When the maximum refractory temperature is reached,  
close all manual fuel shutoff valves, or open the  
electrical circuits of all automatic fuel valves.  
3. Visually observe when the burner flame or FLAME LED  
goes out. If this takes more than three seconds, the  
infrared detector is sensing hot refractory.  
4. Immediately terminate the firing cycle. Lower the  
setpoint to the operating controller, or set the Fuel  
Selector Switch to OFF. Do not open the master switch.  
Response To Other Ultraviolet  
Sources  
Some sources of artificial light (such as incandescent or  
fluorescent bulbs, mercury sodium vapor lamps and daylight)  
produce small amounts of ultraviolet radiation. Under certain  
conditions, an ultraviolet detector responds to these sources as  
if it is sensing a flame. To check for proper detector operation,  
check the Flame Failure Response Time (FFRT) and conduct  
Safety Shutdown Tests under all operating conditions.  
Flame Signal With Hot Combustion  
Chamber (All Installations)  
1. With all initial start-up tests and burner adjustments com-  
pleted, operate the burner until the combustion chamber  
is at the maximum expected temperature.  
NOTE: Some burners continue to purge oil lines  
between the valves and nozzles even though the  
fuel valves are closed. Terminating the firing  
cycle (instead of opening the master switch)  
allows purging the combustion chamber. This  
reduces a buildup of fuel vapors in the  
2. Observe the equipment manufacturer warm-up  
instructions.  
combustion chamber caused by oil line purging.  
3. Recycle the burner under these hot conditions and  
measure the flame signal. Check the pilot alone, the main  
burner flame alone, and both together (unless monitoring  
only the pilot flame when using an intermittent pilot, or  
only the main burner flame when using DSI). Check the  
signal at both High and Low Firing Rate positions and  
while modulating, if applicable.  
4. Check the FFRT of the flame amplifier and relay module.  
5. Lower the setpoint of the operating controller and observe  
the time it takes for the burner flame to go out. This  
should be within the maximum FFRT.  
5. If the detector is sensing hot refractory, correct the  
condition by one or more of the following procedures:  
a. Add an orifice plate in front of the cell to restrict the  
viewing area of the detector.  
b. Resight the detector at a cooler, more distant part of  
the combustion chamber. Make sure the detector  
properly sights the flame.  
c. Try lengthening the sight pipe or decreasing the pipe  
size (diameter).  
6. If the flame signal is too low or unsteady, check the flame  
detector temperature. Relocate the detector if the temper-  
ature is too high.  
7. If necessary, realign the sighting to obtain the proper sig-  
nal and response time.  
For details, refer to the detector Instructions and the  
equipment Operating Manual. Continue adjustments until hot  
refractory hold-in is eliminated.  
66-1153—03  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
8. If the response time is still too slow, replace the Plug-in  
Flame Signal Amplifier.  
9. If the detector is relocated or resighted, or the amplifier is  
replaced, repeat all required Checkout tests.  
d. The pilot should ignite and the flame signal should be  
at least 1.25 Vdc but the main burner cannot light.  
e. The flame signal should drop below 1.25 Vdc within  
the FFRT of the amplifier and the relay module after  
the interrupted pilot goes out.  
f. Safety shutdown occurs.  
6. Loss of flame during RUN.  
SAFETY SHUTDOWN TESTS  
(ALL INSTALLATIONS)  
a. Open the main fuel manual shutoff valve(s) and open  
manual pilot shutoff valve(s).  
b. Depress the reset button.  
Perform these tests at the end of Checkout, after all other tests  
are completed. If used, the external alarm should turn on. Press  
the RESET pushbutton on the relay module to restart the system.  
c. Start the system. Start-up should be normal and the  
main burner should light normally.  
d. After the sequence is in the normal RUN period for at  
least ten seconds with the main burner firing, close  
the manual main fuel shutoff valve(s) to extinguish the  
main burner flame. (On intermittent pilot applications,  
also, close the pilot manual shutoff valve.)  
e. The flame signal should drop below 1.25 Vdc within  
the FFRT of the amplifier and the relay module after  
the main flame and/or pilot goes out.  
1. Opening a Preignition Interlock during the STANDBY or  
PREPURGE period (R7140L - Lockout; R7140G and M -  
Standby Hold 40 seconds, then Lockout).  
a. Safety shutdown occurs.  
2. Opening a Lockout Interlock during PREPURGE, PILOT  
IGN, MAIN IGN or RUN period (R7140L Only).  
a. R7140G and R7140M go to Standby.  
b. Safety shutdown occurs.  
f. R7140L goes to Safety Shutdown; R7140G, M  
recycle after 15-second postpurge.  
3. Detection of flame 40 seconds after entry to STANDBY  
from RUN. Detection of flame from ten seconds up to 30  
seconds into PREPURGE time.  
g. Safety shutdown occurs. (R7140L only.)  
7. Opening a Preignition Interlock after the first five seconds  
of POSTPURGE.  
a. Simulate a flame to cause the flame signal voltage  
level to be at least 1.25 Vdc for 40 seconds after entry  
to STANDBY from RUN and also simulate a flame sig-  
nal for 10 seconds to 30 seconds for PREPURGE.  
b. Flame LED is on.  
a. Open the main fuel manual shutoff valve(s) and open  
manual pilot shutoff valve(s).  
b. Depress the reset button.  
c. *Preignition ILK* fault is displayed on the Keyboard  
Display Module. Fault code 33 is displayed to denote  
the fault.  
c. Safety shutdown occurs after 40 seconds.  
4. Failure to ignite pilot.  
d. Safety shutdown occurs.  
a. Close pilot and main fuel manual shutoff valve(s).  
b. Cycle burner on.  
c. Automatic pilot valve(s) should be energized but the  
pilot cannot ignite.  
IMPORTANT  
1. If the relay module fails to shut down on any of these  
tests, take corrective action; refer to Troubleshooting  
and the relay module diagnostics and return to the  
beginning of all Checkout tests.  
2. When all Checkout tests are completed, reset all  
switches to the original status.  
d. Safety shutdown occurs.  
5. Failure to ignite main (only interrupted pilot application).  
a. Open the manual pilot valve(s); leave the main fuel  
manual shutoff valve(s) closed.  
b. Depress the reset button.  
c. Start the system.  
33  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
66-1153—03  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
35  
66-1153—03  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R7140G,L,M BURNER CONTROL MODULES  
Automation and Control Solutions  
Honeywell International Inc.  
1985 Douglas Drive North  
® U.S. Registered Trademark  
© 2013 Honeywell International Inc.  
66-1153—03 M.S. Rev. 01-13  
Printed in United States  
Golden Valley, MN 55422  
customer.honeywell.com  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Car Seat 447 4 02 User Manual
Graco Humidifier ISPD023AB User Manual
Hague Quality Water Intl Home Dialysis Equipment 63BEQ User Manual
HANNspree Flat Panel Television ST48 12A1 User Manual
Harbor Freight Tools Dust Collector 31810 User Manual
Hotpoint Refrigerator AFAA 52 x AI User Manual
Hunter Fan Electric Heater H1500RC BLK User Manual
Hyundai Car Stereo System H CMDN6000 User Manual
IBM All in One Printer q5 44 3974 04 User Manual
Impex Home Gym MD 1559 User Manual