Heat Glo LifeStyle Fire Pit 8000TRD User Manual

Model:  
8000TRD  
Installers Guide  
Underwriters  
Laboratories Listed  
READ THIS MANUAL BEFORE INSTALLING OR  
OPERATING THIS APPLIANCE. THIS INSTALLERS  
GUIDE MUST BE LEFT WITH APPLIANCE FOR  
FUTURE REFERENCE.  
WARNING: IF THE INFORMATION  
IN THESE INSTRUCTIONS IS NOT  
FOLLOWED EXACTLY, AFIRE OR  
EXPLOSION MAY RESULT CAUS-  
ING PROPERTY DAMAGE, PER-  
SONAL INJURY, OR DEATH.  
WARNING: IMPROPER INSTALLA-  
TION, ADJUSTMENT, ALTERATION,  
SERVICE OR MAINTENANCE CAN  
CAUSE INJURY OR PROPERTY DAM-  
AGE. REFER TO THIS MANUAL. FOR  
ASSISTANCE OR ADDITIONAL INFOR-  
MATION CONSULT A QUALIFIED IN-  
STALLER, SERVICE AGENCY, OR THE  
GAS SUPPLIER.  
- Do not store or use gasoline or other flam-  
mable vapors and liquids in the vicinity of this  
or any other appliance.  
- What to do if you smell gas  
• Do not try to light any appliance.  
• Do not touch any electrical switch.  
• Do not use any phone in your building.  
1. This appliance may be installed in an af-  
termarket, permanently located, manufac-  
tured (mobile) home, where not prohibited  
by local codes.  
• Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's  
instructions.  
• If you cannot reach your gas supplier, call  
the fire department.  
2. This appliance is only for use with the type  
of gas indicated on the rating plate. This  
appliance is not convertible for use with  
other gases, unless a certified kit is used.  
- Installation and service must be performed by a  
qualified installer, service agency, or the gas  
supplier.  
Printed in U.S.A. Copyright 2003,  
Please contact your Heat-N-Glo dealer for any questions  
or concerns. For the number of your nearest Heat-N-  
Glo dealer, please call 1-888-427-3973.  
Heat-N-Glo, a brand of Hearth & Home Technologies Inc.  
20802 Kensington Boulevard, Lakeville, MN 55044  
This product is covered by one or more of the following patents: (United States) 4,112,913; 4,408,594; 4,422,426; 4,424,792; 4,520,791; 4,793,322;  
4,852,548; 4,875,464; 5,000,162; 5,016,609; 5,076,254 5,191,877; 5,218,953; 5,328,356; 5,429,495; 5,452,708; 5,542,407; 5,613,487; (Australia)  
543790; 586383; (Canada) 1,123,296; 1,297,746; 2,195,264; (Mexico) 97-0457; (New Zealand) 200265; or other U.S. and foreign patents pending.  
380-900J 3/03  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Safety and Warning Information ............................................... 2  
Service Parts Lists.................................................................... 4  
Section 1: Approvals and Codes .............................................. 6  
Appliance Certification ................................................................. 6  
Installation Codes ........................................................................ 6  
HighAltitude Installations.............................................................. 6  
u
Section 2: Getting Started ........................................................ 7  
Introducing the Heat-N-Glo Gas Fireplaces .................................. 7  
Pre-installation Preparation .......................................................... 7  
Section 3: Installing the Fireplace ........................................... 9  
Constructing the Fireplace Chase................................................ 9  
Step 1 Locating the Fireplace .................................................. 9  
Step 2 Framing the Fireplace................................................. 10  
Step 3 Installing the Vent System ........................................... 12  
A. Vent System Approvals .......................................... 12  
B. Installing Vent Components ................................... 20  
C. Vent Termination.................................................... 23  
Step 4 Positioning, Leveling, and  
u
Securing the Fireplace................................................ 26  
Step 5 The Gas Control Systems .......................................... 26  
Step 6 The Gas Supply Line .................................................. 27  
Step 7 Gas Pressure Requirements ...................................... 27  
Step 8 Wiring the Fireplace.................................................... 28  
Step 9 Finishing ..................................................................... 30  
Step 10 Installing Trim, Logs, and Ember Material..................... 31  
Installing the Trim........................................................ 31  
Positioning the Logs ................................................... 31  
Shutter Settings .......................................................... 31  
Placing the Ember Material ......................................... 31  
Glass Specifications ................................................... 32  
Step 11 Before Lighting the Fireplace ...................................... 32  
Step 12 Lighting the Fireplace.................................................. 32  
After the Installation.................................................................... 32  
u
u
u
Section 4: Maintaining and Servicing Your Fireplace......... 33  
u = Contains updated information.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
8000TRD  
Service Parts  
8000TRD Beginning Manufacturing Date: 6-01  
8000TRD-IPI Beginning Manufacturing Date: 8-01  
Ending Manufacturing Date: ________________  
(NG, LP) Exploded Parts Diagram  
(GN, PL) Vue éclatée des pièces  
u
19  
4
6
8
1
7
5
2
3
18  
9 Log Set Assembly  
10  
17  
12  
11  
14  
15  
Part number list on following page.  
La liste des numéros de pièce se  
trouve à la page suivante.  
*
*
13  
16  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
8000TRD  
Service Parts List / Liste des pièces de rechange  
IMPORTANT: THIS IS DATED INFORMATION. The most current information is located on your dealers VIP site. When ordering,  
supply serial and model numbers to ensure correct service parts. / IMPORTANT : L'information fournie dans cette brochure  
n'est valide que pendant une courte période. Les sites VIP des distributeurs disposent des renseignements les plus récents.  
Lors d'une commande, veuillez fournir les numéros de série et de modèles pour un remplacement adéquat des pièces.  
ITEM /  
PIÈCE  
SERIAL # /  
N° DE SÉRIE  
PART NUMBER  
/ N° DE PIÈCE  
ENGLISH / FRENCH DESCRIPTION  
COMMON PARTS / PIÉCES COMMUNES  
ON/OFF Rocker Switch / Interrupteur à bascule marche/arrêt  
Burner Orifice NG (#31) / Orifice de brûleur GN (#31)  
Burner Orifice LP (1.8mm) / Orifice de brûleur PL (1.8mm)  
Burner / Brûleur  
060-511  
582-831  
582-818  
380-378A-UM  
GLA-8TRD  
2
3
4
Glass Door Assembly / Porte en verre  
Log Grate / Grille de Bûche  
582-360A  
5
6
7
8
Refractory Base / Réfractaire Base  
Refractory Left Base / Réfractaire  
Refractory Right Base / Réfractaire  
Hood / Hotte  
Log Set Assembly / Jeu de Bûches  
Log 1 / Bûche 1  
Log 2 / Bûche 2  
Log 3 / Bûche 3  
Log 4 / Bûche 4  
Log 5 / Bûche 5  
Log 6 / Bûche 6  
Log 7 / Bûche 7  
Log 8 / Bûche 8  
Surround / Entourage  
Insulation Board / Conseil d'Isolation  
Flue Restrictor / Restricteur de conduite de cheminée  
Flex Ball Valve Assembly / Fléchir l'Assemblée de Soupape de Balle  
Tube Assembly / Module de Tube  
STANDING PILOT IGNITION / D’ALLUMAGE PAR VEILLEUSE  
Piezo Ignitor / Allumage Piézo  
Junction Box - Pilot / Boîtier de raccordement - de veilleuse  
Valve NG / Valve GN  
Valve LP / Valve PL  
SRV582-370-UM  
SRV582-376-UM  
SRV582-377-UM  
SRV560-175  
LOGS-8TRC  
SRV582-701  
SRV582-703  
SRV582-702  
SRV582-704  
SRV402-701  
SRV582-706  
SRV582-707  
SRV582-705  
380-130  
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
u
380-401  
385-128  
302-320A  
477-301A  
418-513  
100-250A  
060-522  
060-523  
485-510A  
485-511A  
446-505  
446-517  
446-511  
060-512  
570-530  
570-531  
1
Pilot Assembly NG / Module de veilleuse GN  
Pilot Assembly PL / Module de veilleuse PL  
Pilot Orifice NG / Orifice de veilleuse GN  
Pilot Orifice PL / Orifice de veilleuse PL  
Thermocouple / Thermocouple  
Thermopile / Thermopile  
Pilot Control Knob / Piloter le Bouton de Contrôle  
Flame Control Knob / Flamber le Bouton de Contrôle  
u
u
Pre 2300  
Post 2300  
NGK-8TRD  
NGK-8TRD-A  
Conversion Kit NG / Module de conversion GN  
Pre 1326  
Post 1326  
LPK-8TRD  
LPK-8TRD-A  
Conversion Kit LP / Module de conversion PL  
IPI IGNITION / ALLUMAGE IPI  
Junction Box / Boîtier de dérivation  
Valve NG / Valve GN  
1
383-250A  
750-500  
Valve LP / Valve PL  
750-501  
Pilot Assembly NG / Module de veilleuse GN  
Pilot Assembly LP / Module de veilleuse PL  
Module / Module  
385-510A  
385-511A  
593-592  
Conversion Kit - IPI LP / Module de conversion - IPI PL  
Wire Assembly / Module de fil  
3V Transformer / 3V Transformateur  
Battery Pack / Paquet de Batterie(Pile)  
LPK-8TRD-IPI  
593-590A  
593-593A  
593-594A  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Approvals and  
Codes  
High Altitude Installations  
Appliance Certification  
u
U.L. Listed gas appliances are tested and approved with-  
out requiring changes for elevations from 0 to 2,000 feet in  
the U. S. A. and in Canada.  
The Heat-N-Glo fireplace models discussed in this Installers  
Guide have been tested to certification standards and listed  
by the applicable laboratories.  
When installing this appliance at an elevation above 2,000  
feet, it may be necessary to decrease the input rating by  
changing the existing burner orifice to a smaller size. Input  
rate should be reduced by 4% for each 1000 feet above a  
2000 foot elevation in the U.S.A. or 10% for elevations  
between 2000 and 4500 feet in Canada. If the heating value  
of the gas has been reduced, these rules do not apply. To  
identify the proper orifice size, check with the local gas  
utility.  
Certification  
MODEL: 8000TRD  
LABORATORY: Underwriters Laboratories  
TYPE: Direct Vent Gas Fireplace  
STANDARD:  
ANSI Z21.50b-2000•CSA2.22b-2000•UL307B  
Installation Codes  
If installing this appliance at an elevation above 4,500 feet  
(in Canada), check with local authorities.  
The fireplace installation must conform to local codes. Before  
installing the fireplace, consult the local building code  
agency to ensure that you are in compliance with all  
applicable codes, including permits and inspections.  
In the absence of local codes, the fireplace installation must  
conform to the National Fuel Gas Code ANSI Z223.1 (in  
the United States) or the CAN/CGA-B149 Installation Codes  
(in Canada). The appliance must be electrically grounded  
in accordance with local codes or, in the absence of local  
codes with the National Electric Code ANSI/NFPA No. 70  
(in the United States), or to the CSA C22.1 Canadian Electric  
Code (in Canada).  
These models may be installed in a bedroom or bed-sitting  
room in the U.S.A. and Canada.  
Heat-N-Glo Quality  
Systems registered  
by SGS ICS  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Getting Started  
Introducing the Heat-N-Glo Gas Fireplaces  
Heat-N-Glo direct vent gas fireplaces are designed to oper-  
ate with all combustion air siphoned from outside of the  
building and all exhaust gases expelled to the outside.  
The Heat-N-Glo Warranty will be voided by, and Heat-N-Glo  
disclaims any responsibility for, the following actions:  
Installation of any damaged fireplace or vent system  
component.  
Modification of the fireplace or direct vent system.  
Installation other than as instructed by Heat-N-Glo.  
Improper positioning of the gas logs or the glass door.  
The information contained in this Installers Guide, unless  
noted otherwise, applies to all models and gas control  
systems. Gas fireplace diagrams, including the dimensions,  
are shown in this section.  
Installation and/or use of any component part not manu-  
factured and approved by Heat-N-Glo, not withstanding  
any independent testing laboratory or other party approval  
of such component part or accessory.  
Pre-install Preparation  
This gas fireplace and its components are tested and safe  
when installed in accordance with this Installers Guide.  
Report to your dealer any parts damaged in shipment,  
particularly the condition of the glass. Do not install any  
unit with damaged, incomplete, or substitute parts.  
ANY SUCH ACTION MAY POSSIBLY CAUSE A FIRE  
HAZARD.  
When planning a fireplace installation, it’s necessary to  
determine:  
The vent system components are shipped in separate  
packages. The gas logs may be packaged separately and  
must be field installed.  
Where the unit is to be installed.  
The vent system configuration to be used.  
Gas supply piping.  
Read all of the instructions before starting the  
installation. Follow these instructions carefully during  
the installation to ensure maximum safety and benefit.  
Failure to follow these instructions will void the  
owner’s warranty and may present a fire hazard.  
Electrical wiring.  
Framing and finishing details.  
Whether optional accessories—devices such as a fan,  
wall switch, or remote control—are desired.  
If the fireplace is to be installed on carpeting or tile, or on  
any combustible material other than wood flooring, the  
fireplace should be installed on a metal or wood panel that  
extends the full width and depth of the fireplace.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
35 1/2 (902mm)  
17 3/4 (450mm)  
21 1/2 (548mm)  
Ø8Ø5/8 (219mm)  
11 3/4 (297mm)  
Ø8 5/8  
(219mm)  
GAS LINE  
ACCESS  
ELECTRICAL  
ACCESS  
40 3/8  
(1026mm)  
36 3/4  
(932mm)  
26 7/8  
(681mm)  
29 1/8  
2 1/4  
(56mm)  
(740mm)  
3 1/2  
(89mm)  
43 (1091mm)  
8 3/8  
(212mm)  
9 1/8  
(233mm)  
48 3/8 (1229mm)  
TOP STANDOFFS  
TOP VENT  
COLLARS  
HOOD  
RATING PLATE  
AND LABELS  
GAS CONTROLS  
ELECTRICAL  
ACCESS  
GAS LINE ACCESS  
Figure 1. Diagram of the 8000TRD  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
1” MIN. (25mm)  
B
A
Installing the Fireplace  
Constructing the Fireplace Chase  
A chase is a vertical box-like structure built to enclose the  
gas fireplace and/or its vent system. Vertical vents that run  
on the outside of a building may be, but are not required to  
be, installed inside a chase.  
D
E
CAUTION: TREATMENT OF FIRESTOP SPACERS AND  
CONSTRUCTION OF THE CHASE MAY VARY WITH THE  
TYPE OF BUILDING. THESE INSTRUCTIONS ARE NOT  
SUBSTITUTES FOR THE REQUIREMENTS OF LOCAL  
BUILDING CODES. THEREFORE, YOUR LOCAL BUILD-  
ING CODES MUST BE CHECKED TO DETERMINE THE  
REQUIREMENTS FOR THESE STEPS.  
C
1/2” MIN. (13mm)  
A
49”  
B
22”  
C
D
56”  
E
79”  
39 1/2”  
Figure 2. Fireplace Dimensions, Locations,  
and Space Requirements  
Factory-built fireplace chases should be constructed in the  
manner of all outside walls of the home to prevent cold air  
drafting problems. The chase should not break the outside  
building envelope in any manner.  
Minimum Clearances  
from the Fireplace to Combustible Materials  
Inches  
mm  
This means that the walls, ceiling, base plate and cantilever  
floor of the chase should be insulated. Vapor and air infiltra-  
tion barriers should be installed in the chase as per regional  
codes for the rest of the home.Additionally, Heat-N-Glo rec-  
ommends that the inside surfaces be sheetrocked and taped  
for maximum air tightness.  
Glass Front ........................ 36 ..................... 914  
Floor ....................................0........................ 0  
Rear ................................... 1/2 ..................... 13  
Sides ................................. 1/2 ..................... 13  
Top ....................................3 1/2.................... 89  
Ceiling**.............................. 31 ..................... 787  
To further prevent drafts, the firestops should be caulked to  
seal gaps. Gas line holes and other openings should be  
caulked or stuffed with insulation. If the unit is being in-  
stalled on a cement slab, we recommend that a layer of  
plywood be placed underneath to prevent conducting cold  
up into the room. Be sure to include spark arrestors for  
woodburning units if they are required.  
* See Figure 3.  
**The clearance to the ceiling is measured from the top  
of the unit, excluding the standoffs (see Figure 40).  
The distance from the unit to combustible construction  
is to be measured from the unit outer wrap surface to  
the combustible construction, NOT from the screw heads  
that secure the unit together.  
THE CHASE SHOULD BE CONSTRUCTED SO THATALL  
CLEARANCES TO THE FIREPLACE ARE MAINTAINED  
AS SPECIFIED WITHIN THIS INSTALLERS GUIDE.  
Minimum Clearances  
from the Vent Pipe to Combustible Materials  
Step 1.  
Locating the Fireplace  
Inches  
mm  
Vertical Sections............... 1................. 25  
The following diagram shows space and clearance require-  
ments for locating a fireplace within a room.  
Horizontal Sections  
Top ...................................... 3................. 75  
Bottom ................................ 1................. 25  
Sides .................................. 1................. 25  
Clearance Requirements  
The top, back, and sides of the fireplace are defined by  
stand-offs. The minimum clearance to a perpendicular wall  
extending past the face of the fireplace is one inch (25 mm).  
The back of the fireplace may be recessed 21 1/2 inches  
(546 mm) into combustible construction.  
At Wall Firestops  
Top ................................... 2 1/2.............63.7  
Bottom .............................. 1/2 ............... 13  
Sides .................................. 1................. 25  
For minimum clearances, see the direct vent termination  
clearance diagrams on pages 23 and 24 in this manual.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 2. Framing the Fireplace  
Fireplace framing can be built before or after the fireplace is  
set in place. Framing should be positioned to accommo-  
date wall coverings and fireplace facing material. The dia-  
gram below shows framing reference dimensions.  
CAUTION: MEASURE FIREPLACE DIMENSIONS AND  
VERIFY FRAMING METHODS AND WALL COVERING  
DETAILS BEFORE FRAMING.  
Shows center of 12” x 12” vent framing  
holes for top and rear venting. The center  
of the hole is one (1) inch (25.4mm) above  
the center of the horizontal vent pipe.  
B
u
C
E
D
A
1/2” CLEARANCE FROM BACK OF FIREPLACE TO COMBUSTIBLE  
A. ............. 49”*  
B. .........40 1/2”  
C. ............... 22”  
D. .........43 1/8”  
E. .........30 1/8”  
1/2” CLEARANCE  
FROM BOTH SIDES  
OF FIREPLACE  
TO COMBUSTIBLE  
FRAMING  
MEMBER  
Framing should be  
constructed of 2 X 4  
lumber or heavier.  
0” CLEARANCE TO  
FRAMING MEMBER  
0” CLEARANCE  
Figure 3. Framing Dimensions  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 7/16”  
(164mm)  
8 1/2”  
(216mm)  
8 1/2”  
11 5/8”  
(216mm)  
(295mm)  
11 1/16”  
(281mm)  
5 7/8”  
(149mm)  
7 3/8”  
(187mm)  
6 1/2”  
(165mm)  
5 1/16”  
(129mm)  
8 5/8”  
(220mm)  
8 5/8”  
(220mm)  
11 15/16”  
(303mm)  
5D  
DV-4  
DV-90D  
DV-48D  
DV-36D  
11 3/4”  
(298mm)  
DV-12D  
35 3/4”  
(908mm)  
8 3/4”  
(222mm)  
47 3/4”  
(1.2m)  
DV-09D  
5 3/4”  
(146mm)  
DV-06D  
NOTE: PIPES OVERLAP 1-3/8 INCHES (34.93mm) AT EACH JOINT.  
Figure 4. D-Series Direct Vent Component Specifications  
(5-inch inner pipe / 8 5/8-inch outer pipe)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 3. Installing the Vent System  
A. Vent System Approvals  
Identifying Vent Components  
The vent systems installed on this gas fireplace may in-  
clude one, two, or three 90° elbow assemblies. The rela-  
tionships of vertical rise to horizontal run in vent configura-  
tions using 90° elbows MUST BE strictly adhered to. The  
rise to run relationships are shown in the venting drawings  
and tables. Refer to the diagrams on the next several pages.  
These models are approved to use D-series direct vent pipe  
components and terminations (see Figures 4 and 5). Ap-  
proved vent system components are labeled for identifica-  
tion. This pipe is tested and listed as an approved compo-  
nent of the fireplace. The pipe is tested to be run inside an  
enclosed wall. There is no requirement for inspection open-  
ings at each joint within the wall. There is no required pitch  
for horizontal vent runs. NO OTHER VENTING SYSTEMS  
OR COMPONENTS MAY BE USED.  
NOTE: Two 45° elbows may be used in place of one  
90° elbow. Rise to run ratios in the vent system must  
be followed if 45° elbows are used.  
Detailed installation instructions are included with each vent  
termination kit and should be used in conjunction with this  
Installers Guide.  
This model has vent starting collars on both the top and the  
back of the unit. Depending upon the installation, decide  
which ONE set of starting collars will be used to attach the  
vent system. The starting collar sealing cap must remain  
on the starting collar NOT used.  
The flame and ember appearance may vary based on the type  
of fuel burned and the venting configuration used.  
VERTICAL  
TERMINATION  
STORM COLLAR  
ROOF FLASHING  
HORIZONTAL  
TERMINATION  
HORIZONTAL PIPE  
SUPPORT  
PIPE LENGTH  
WALL FIRESTOP  
CEILING  
FIRESTOP  
WALL BRACKET  
90 DEGREE  
ELBOW  
Terminations Kits  
DVK-01TRD  
DVK-SNKD  
DVK-TVCD DVK-FLEX3-02D  
PVK-80  
Figure 5. Vent System Components and Termination Kits  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Flue Restrictor Instructions  
1. Remove Exhaust Shield using a 1/4” nut driver by  
removing the four screws securing it in place (see  
Figure 7).  
EXHAUST  
SHIELD  
STRAIGHT UP  
VERTICAL VENTING  
FLUE  
RESTRICTOR  
V (FT.)  
40' MAX. (12.4 M)  
Figure 7  
2. Break the Flue Restrictor into two pieces. Do this  
by bending the part back and forth until it breaks  
(see Figure 8).  
BREAK  
HERE  
Figure 8. Flue Restrictor  
Figure 6. Straight Up Vertical Venting  
NOTE: On vertical venting configurations you may want to  
install the vertical baffle (385-128). See flue restrictor in-  
stallation instructions.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Center the Flue Restrictor on vent and secure in  
place by using two self-tapping screws (see Fig-  
ure 9).  
HORIZONTAL VENTING  
Kit No. H Max. Run  
DVK-01D  
5. Reinstall the Exhaust Shield.  
DVK-01TRD 24" (610 mm)  
1
2
3
4
5
SETTINGS  
1
2
3
4
5
H
Figure 9  
90-DEGREE  
ELBOWS  
3. Match the amount of vertical you have in the sys-  
tem with the chart to find the appropriate position  
to set the Flue Restrictor.  
45-DEGREE  
ELBOW  
- CHART -  
Top Vent  
NG  
Top Vent  
LP  
Rear Vent  
NG  
Rear Vent  
LP  
Vertical  
4'  
No  
Restrictor  
No  
Restrictor  
No  
Restrictor  
1-1  
2-2  
3-3  
3-4  
3-4  
4-4  
4-4  
5-4  
No  
Restrictor  
8'  
1-2  
3-2  
3-3  
3-3  
3-4  
3-4  
4-4  
1-1  
2-2  
3-3  
3-3  
3-4  
3-4  
4-4  
15'  
20'  
25'  
30'  
35'  
40'  
1-2  
2-3  
2-3  
3-3  
3-3  
3-4  
NOTE: 8000TRD model is tested and approved  
to use 45° elbows in corner installations.  
However, 90° elbows will result in better per-  
formance.  
Figure 10. Corner Installation  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH ONE (1) 90° ELBOW  
V
H
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6' MAX. (1.86m)  
8' MAX. (2.4m)  
V+H=40' MAX. (12.4m)  
H = 8' MAX. (2.4m)  
NOTE: On vertical venting configurations where  
the vertical component is over 10 feet, you may  
want to install the vertical baffle included in the  
manual bag assembly to improve flame  
appearance.  
Figure 11. Venting with One 90° Elbow  
VENTING WITH ONE (1) 90° ELBOW  
V (FT.)  
H (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5' MAX. (1.52m)  
10' MAX. (3.1m)  
15' MAX. (4.65m)  
20' MAX. (6.2m)  
V+H= 40’ MAX. (12.4MM) H = 20' MAX. (6.2m)  
H
V
NOTE: For corner installations:A 6-inch (152mm)  
section of straight pipe may need to be attached to  
the fireplace before a 90o elbow, to allow the vent  
pipe to clear the top standoffs.  
NOTE: If a 90o elbow is first attached to the unit,  
the maximum horizontal run is 3-feet (914mm).  
Figure 12. Venting with One 90° Elbow  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH TWO (2)  
90° ELBOWS  
V
H
H + H1  
1´ MIN. (305 mm)  
2´ MIN. (610 mm)  
3´ MIN. (914 mm)  
4´ MIN. (1.22 m)  
2´ MAX. (610 mm)  
4´ MAX. (1.22 m)  
6´ MAX. (1.86 m)  
8´ MAX. (2.48 m)  
5´ MAX. (1.52m)  
10´ MAX. (3.1m)  
15´ MAX. (4.65m)  
20´ MAX. (6.2m)  
V+H+H1 = 40´ MAX. (12.4 m) H = 8´ MAX. (2.48 m) H+H = 20´ MAX. (6.2m)  
1
Figure 13. Venting with Two 90° Elbows  
VENTING WITH TWO (2) 90o ELBOWS  
V FT.  
H + H1 (FT.)  
5´ MAX. (1.52m)  
10´ MAX. (3.1m)  
15´ MAX. (4.65m)  
20´ MAX. (6.2m)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
V+H+H1= 40' MAX.(12.4m) H+H1 = 20´ MAX. (6.2m)  
V+V1+H= 40' MAX.(12.4m)  
Figure 14. Venting with Two 90° Elbows  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH TWO (2) 90o ELBOWS  
V FT.  
H + H1 (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
2' MAX. (610mm)  
4' MAX. (1.22m)  
6' MAX. (1.86m)  
8' MAX. (2.4m)  
V+H+H1= 40' MAX. (12.4m)  
H+H1= 8' MAX. (2.4m)  
Figure 15. Venting with Two 90° Elbows  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH THREE (3) 90° ELBOWS  
V
H
H + H1  
1´MIN. (305mm)  
2´MIN. (610mm)  
3´MIN. (914mm)  
4´MIN. (1.22m)  
2´MAX. (610mm)  
4´MAX. (1.22m)  
6´MAX. (1.86m)  
8´MAX. (2.48m)  
5´MAX. (1.52m)  
10´MAX. (3.1m)  
15´MAX. (4.65m)  
20´MAX. (6.2m)  
V1+V+H+H1 = 40  
´
MAX.(12.4 m) H = 8´MAX.(2.48 m) H+H1 = 20´MAX.(6.2 m)  
V
H
H + H1 + H2  
1´MIN. (305mm)  
2´MIN. (610mm)  
3´MIN. (914mm)  
4´MIN. (1.22m)  
2´MAX. (610mm)  
4´MAX. (1.22m)  
6´MAX. (1.86m)  
8´MAX. (2.48m)  
5´MAX. (1.52m)  
10´MAX. (3.1m)  
15´MAX. (4.65m)  
20´MAX. (6.2m)  
1
2
V+H+H +H = 40  
´
MAX. (12.4 m)  
H = 8´ MAX. (2.48 m)  
H+H 1+H2 = 20´ MAX. (6.2 m)  
Figure 16. Venting with three 90° elbows  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING WITH THREE (3) 90° ELBOWS  
V (FT.)  
H (FT.)  
H
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5' MAX. (1.52m)  
10' MAX. (3.1m)  
15' MAX. (4.65m)  
20' MAX. (6.2m)  
NOTE: H + H1 = 20' MAX. (6.2m)  
V + V1 + H + H1= 40' MAX. (12.4m)  
H1  
V1  
V
V (FT.)  
H + H1 (FT.)  
1' MIN. (305mm)  
2' MIN. (610mm)  
3' MIN. (914mm)  
4' MIN. (1.22m)  
5' MAX. (1.52m)  
10' MAX. (3.1m)  
15' MAX. (4.65m)  
20' MAX. (6.2m)  
H +H1 = 20' MAX. (6.2m)  
NOTE: V+V1+H +H1 = 40' MAX. (12.4m)  
Figure 17. Venting with three 90° elbows  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Attach the First Vent Component to Starting Collars  
B. Installing Vent Components  
After determining which set of starting collars will be used  
(top or rear), follow venting instructions accordingly.  
To attach the first vent component to the starting collars of  
the fireplace:  
Venting Out the Rear Vent  
• Apply a 3/8 inch (9.5mm) bead of stove cement around  
the 5 inch (127mm) fireplace starting collar.  
Remove the installed rear seal cap from the rear starting  
collars by cutting the strap at each end. (see Figure 18).  
Follow the vent configuration tables accordingly.  
• Make sure that the fiberglass gasket supplied in the man-  
ual bag seals between the first 8-5/8 inch (219mm) vent  
component and the outer fireplace wrap. Using 2 self-  
tapping screws from the manual bag, secure that gasket  
to the outer wrap (see Figure 19).  
Remove the insulation from the REAR five inch flue, pull  
the heat shield out from outside of the firebox.  
WARNING: THE TOP HEAT SHIELD (INSIDE  
THE FIREBOX) MUST REMAIN ATTACHED IF  
THE VENT SYSTEM IS ATTACHED TO THE  
REAR STARTING COLLARS. SEE FIGURE 18.  
!
OUTER  
FIRST VENT  
WRAP  
COMPONENT  
FIBERGLASS  
GASKET  
Venting Out the Top Vent  
Remove the top vent collar seal cap and two pieces of  
insulation inside the top two starting collars (See Fig-  
ure 18).  
Remove the heat shield from inside the TOP five inch flue  
from outside of the firebox.  
WARNING: THE REAR VENT COLLAR SEAL  
CAP MUST REMAINATTACHED TO THE REAR  
VENT COLLARS IF THE VENT SYSTEM IS AT-  
!
TACHED TO THE TOP STARTING COLLARS.  
Figure 19. Fiberglass Gasket  
WARNING: FAILURE TO REMOVE INSULATION  
!
IN THE SET OF COLLARS YOU ARE USING  
COULD CAUSE A FIRE.  
• Lock the vent components into place by sliding the con-  
centric pipe sections with four (4) equally spaced interior  
beads into the fireplace collar or previously installed com-  
ponent end with four (4) equally spaced indented sections.  
WARNING:YOU MUST LEAVE THE INSULATION  
IN PLACE IN THE SET OF COLLARS YOU ARE  
NOT USING.  
!
• When the internal beads of each 8-5/8 inch (219mm)  
outer pipe line up, rotate the pipe section clockwise about  
one-quarter (1/4) turn. The vent pipe is now locked together.  
If your vertical vent component is over 10 feet, you may  
want to install the vertical baffle (located in the bag containing  
the install manual) to improve flame appearance. Center  
the vertical baffle on the 5” flue being used, and with self  
tapping screws secure the baffle to the inside of the firebox.  
• The first 90° elbow installed in the vent system of a rear  
venting fireplace MUST BE in a vertical position.  
STARTING  
COLLAR  
Venting Out Top  
Venting Out Rear  
SEAL  
CAP  
SEAL  
CAP  
HEAT  
SHIELD  
STOVE  
SEALANT  
BEAD  
INSULATION  
DISCARD BOTH  
PIECES and  
HEAT SHIELD  
HEAT  
SHIELD  
DISCARD  
INSULATION  
and  
FIRST VENT  
COMPONENT  
HEAT SHIELD  
1 INCH  
(25.4mm)  
Figure 20.  
Attaching First Vent Component to Starting Collars  
CUT  
HERE  
WARNING: A 3/8 INCH (9.5 MM) BEAD OF  
STOVE CEMENT MUST BE PLACED AROUND  
!
Cut the seal cap  
strap and remove white  
gasket material.  
THE 5 INCH (127 MM) FIREPLACE STARTING COL-  
LAR BEFORE ATTACHING THE FIRST VENT COM-  
PONENT. FAILURE TO SEAL THIS JOINT MAY  
CAUSETHEFIREPLACETO OPERATE IMPROPERLY.  
Figure 18  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
bag secure the heat shield to the pipe maintaining 3” to  
4” between the pipe and shield.  
WARNING: ENSURE THAT THE FIBERGLASS  
GASKET SUPPLIED WITH THE FIREPLACE  
!
SEALS BETWEEN THE FIRST VENT COMPONENT  
AND THE OUTER FIREPLACE WRAP.  
SCREW  
If the installation is for a termination cap attached directly  
to the fireplace, skip to the sections, Install Firestops and  
Vent Termination.  
3”  
(76mm)  
2. Continue Adding Vent Components  
WARNING: INSTALLATION OF THIS FIRE-  
!
PLACE REQUIRES THE USE OF HEAT  
SHIELD 570-290 ABOVE THE FIRST 900 ELBOW IN  
THE VENTING SYSTEM.  
To Install the Heat Shield:  
1. Determine if the heat shield is required. Do so by mea-  
suring the vertical distance between the top horizontal  
surface of the elbow to any combustible surface above.  
If the distance is more than 4 inches, the heat shield is  
NOT required. If it is 4 inches or less, the heat shield IS  
REQUIRED. Install per the following steps. See Figure 21.  
Figure 23  
• Continue adding vent components, locking each succeed-  
ing component into place.  
• Ensure that each succeeding vent component is secure-  
ly fitted and locked into the preceding component in the  
vent system.  
COMBUSTIBLE  
Figure 21  
SURFACE  
• 90° elbows may be installed and rotated to any point  
around the preceding component’s vertical axis. If an el-  
bow does not end up in a locked position with the pre-  
ceding component, attach with a minimum of two (2)  
sheet metal screws.  
3” MIN.  
(76mm)  
HEAT  
SHIELD  
2. Fasten the shield in place using the four pilot holes pro-  
vided in the part. The shield should be oriented such that  
the 13 1/8 inch dimension (longest dimension) is run-  
ning in the same direction the elbow is pointing. The  
shield should be centered directly above the elbow, and  
positioned so that it creates a 1/2 inch airspace between  
the shield and the combustible surface. See Figure 22.  
Figure 24. Adding Venting Components  
3. Install Support Brackets  
COMBUSTIBLE SURFACE  
CORRECT  
INCORRECT  
DIRECTION  
UP  
For Horizontal Runs - The vent system must be supported  
every five (5) feet of horizontal run by a horizontal pipe support.  
To install support brackets for horizontal runs:  
• Place the pipe supports around the vent pipe.  
• Nail the pipe supports to the framing members.  
HEAT SHIELD  
900ELBOW  
For Vertical Runs - The vent system must be supported  
every eight (8) feet (2.4m) above the fireplace flue outlet by  
wall brackets.  
Figure 22  
• If the combustible materials are not in place at the time  
of install the elbow heat shield may be screwed to the  
exhaust pipe (see Figure 23). Cut the tabs as shown  
and bend down. Using the screws found in the manual  
To install support brackets for vertical runs:  
• Attach wall brackets to the vent pipe and secure the wall  
bracket to the framing members with nails or screws.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: There must be NO INSULATION or other  
combustibles inside the framed firestop opening.  
WALL BRACKET  
WALL STUD  
HEAT SHIELD  
TRIM HEAT  
SHIELD IF TOO  
LONG, ADD TO  
SHIELD IF TOO  
SHORT  
EXTERIOR  
FIRESTOP  
8 FT. (2.4m)  
INTERIOR  
FIRESTOP  
FLUE  
OUTLET  
1 INCH MIN.  
(25.4mm)  
Figure 27. Heat Shield, Interior & Exterior Firestops  
Figure 25. Installing Support Brackets  
4. Install Firestops  
For Vertical Runs - One ceiling firestop is REQUIRED at  
the hole in each ceiling through which the vent passes.  
To install firestops for vertical runs that pass through ceilings:  
For Horizontal Runs - Firestops are REQUIRED on both  
sides of a combustible wall through which the vent passes.  
• Position a plumb bob directly over the center of the verti-  
cal vent component.  
NOTE: Model DVK-01TRD does not need an exterior  
firestop on an exterior combustible wall.  
• Mark the ceiling to establish the centerpoint of the vent.  
• Drill a hole or drive a nail through this centerpoint.  
To install firestops for horizontal runs that pass through  
either interior or exterior walls:  
• Check the floor above for any obstructions, such as wir-  
ing or plumbing runs.  
• Cut a 12” x 12” (305mm x 305mm) hole through the wall.  
NOTE: The center of the hole is one (1) inch (25.4mm)  
above the center of the horizontal vent pipe.  
• Reposition the fireplace and vent system, if necessary,  
to accommodate the ceiling joists and/or obstructions.  
• Position the firestops on both sides of the hole previ-  
ously cut and secure the firestops with nails or screws.  
• Cut an 11-inch X 11-inch (280mm X 280mm) hole through  
the ceiling, using the centerpoint previously marked.  
• The heat shields of the firestops MUST BE placed to-  
• Frame the hole with framing lumber the same size as the  
ceiling joists.  
wards the top of the hole.  
• Continue the vent run through the firestops.  
12"  
(305mm)  
11" (280 mm)  
11" (280mm)  
CHIMNEY  
HOLE  
12"  
(305mm)  
1" (25.4 mm)  
EXISTING CEILING  
JOISTS  
NEW  
FRAMING  
MEMBERS  
CEILING  
VENT PIPE  
Figure 28. 11" x 11" Hole & New Framing Members  
Figure 26. 12" x 12" Hole and Vent Pipe  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C. Vent Termination  
If the area above the ceiling is NOT an attic, position and  
secure the ceiling firestop on the ceiling side of the previously  
cut and framed hole.  
For Horizontal Terminations - To attach and secure the  
termination to the last section of horizontal vent:  
• Rotate and interlock the ends as described at the begin-  
ning of the Installing Vent Components section.  
• The termination kit should pass through the wall firestops  
from the exterior of the building.  
JOIST  
• Adjust the termination cap to its final exterior position on  
the building.  
WARNING: THE TERMINATION CAP MUST BE  
POSITIONED SO THAT THE ARROW IS  
POINTING UP.  
!
CEILING  
For trapezoidal cap termination kits:  
NAILS (4 REQUIRED)  
CEILING FIRESTOP  
• Using screws secure the cap to the exterior wall through  
the flanges in the cap.  
Figure 29. Ceiling Firestop (Ceiling Side)  
WARNING: THE BOTTOM OF THE VENT  
TERMINATION CAP MUST BE A MINIMUM  
!
If the area above the ceiling IS an attic, position and secure  
the firestop on top of the previously framed hole.  
OF 12 INCHES (305 MM) ABOVE GROUND LEVEL  
(GRADE). THE TOP OF THE CAP MUST BE A MIN-  
IMUM OF 18 INCHES (457 MM) BELOW COMBUS-  
TIBLE MATERIAL, SUCH AS A DECK. THE SIDE  
OF THE CAP MUST BE A MINIMUM OF 6 INCHES  
(152 MM) AWAY FROM A PARALLEL OUTSIDE  
WALL. VENTING TERMINALS SHALL NOT BE RE-  
CESSED INTO AWALL OR SIDING. SEE THE FOL-  
LOWING DIAGRAM FOR VENT TERMINATION  
CLEARANCES.  
NOTE: Keep insulation away from the vent pipe at least  
1 inch (25mm).  
NOTE: There must be NO INSULATION or other  
combustibles inside the framed firestop opening.  
NAILS (4 REQUIRED)  
TRAPEZOID CAP TERMINATION  
RAFTER  
CEILING  
CEILING FIRESTOP  
7 1/4"  
(184mm)  
Figure 30. Attic Firestop  
Figure 31. Trapezoid Termination Caps  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
O
N
P
R
G
v
A
H
Q
D
(See Note 2)  
E
v
B
L
U.S.  
(3 FT)  
B
v
v
v
B
v
F
v
M
I
v
X
A
J or K  
X
= VENT TERMINAL  
=AIRSUPPLY INLET  
= AREA WHERE TERMINAL IS NOT PERMITTED  
V
J
= 9" (U.S.A.)  
A
B
= 12" ....................... clearances above grade, veran-  
12" (Canada)......... clearance to non-mechani-  
cal air supply inlet to build-  
ing or the combustion air in-  
let to any other appliance  
= 3 ft. (U.S.A.)  
(See Note 1)  
da, porch, deck or balcony  
= 12" ....................... clearances to window or door  
that may be opened, or to per-  
K
manently closed window.  
6 ft. (Canada) ......... clearance to a mechanical  
air supply inlet  
D*  
= 18" ....................... vertical clearance to ventilated  
soffit located above the terminal  
within a horizontal distance of 2  
feet (60 cm) from the center-line  
of the terminal  
L** = 7 ft. ......................... clearance above paved  
(See Note 1)  
sidewalk or a paved driveway  
located on public property  
M*** = 18" ......................... clearance under veranda,  
porch, deck or balcony  
E*  
F
= 18" ....................... clearance to unventilated soffit  
N
O
P
= 6” ........................... non-vinyl sidewalls  
12” ......................... vinyl sidewalls  
=
9"......................... clearance to outside corner  
G
H
= 6".......................... clearance to inside corner  
= 18......................... non-vinyl soffit and overhang  
= 3 ft. (Canada)....... not to be installed above a gas  
meter/regulator assembly within  
42” ......................... vinyl soffit and overhang  
= 8 ft.  
3 feet (90cm) horizontally from the  
center-line of the regulator  
______________________________Q___M_I_N___________________________________  
_____1___c_a__p__________________3___f_e_e__t_________________2__x___Q___A_C_T_U_A_L____  
______2__c__a_p__s________________6___f_e_e__t_________________1__x___Q___A_C_T_U_A_L____  
______3__c__a_p__s________________9___f_e_e__t______________2__/_3__x___Q___A_C_T_U_A__L___  
4 caps 12 feet 1/2 x Q ACTUAL  
RMAX  
I
= 3 ft. (U.S.A.)  
6 ft. (Canada) ....... clearance to service regulator  
vent outlet and electric service  
* 30” minimum for vinyl clad soffits.  
QMIN = # termination caps x 3  
RMAX = (2 / # termination caps) x QACTUAL  
** a vent shall not terminate directly above a sidewalk or paved  
driveway which is located between two single family dwellings  
and serves both dwellings.  
NOTE 3: Local codes or regulations may require different  
clearances.  
*** only permitted if veranda, porch, deck or balcony is fully open on  
a minimum of 2 sides beneath the floor.  
NOTE 4: Termination caps may be hot. Consider their proximity to  
doors or other traffic areas.  
NOTE 1: On private property where termination is less than 7 feet  
above a sidewalk, driveway, deck, porch, veranda or balcony, use of  
a listed cap shield is suggested.  
WARNING: In the U.S: Vent system termination is NOT permitted  
in screened porches. You must follow side wall, overhang and  
ground clearances as stated in the instructions.  
NOTE 2: Termination in an alcove space (spaces open only on one side  
and with an overhang) are permitted with the dimensions specified for  
vinyl or non-vinyl siding and soffits. 1. There must be 3 feet minimum  
between termination caps. 2. All mechanical air intakes within 10 feet  
of a termination cap must be a minimum of 3 feet below the termination  
cap. 3. All gravity air intakes within 3 feet of a termination cap must be  
a minimum of 1 foot below the termination cap.  
In Canada: Vent system termination is NOT permitted in screened  
porches. Vent system termination is permitted in porch areas  
with two or more sides open. You must follow all side walls,  
overhang and ground clearances as stated in the instructions.  
Heat-N-Glo assumes no responsibility for the improper perfor-  
mance of the fireplace when the venting system does not meet  
these requirements.  
Figure 32. Vent Termination Minimum Clearances  
CAUTION: IF EXTERIOR WALLS ARE FINISHED WITH VINYL SIDING, IT IS NECESSARY TO INSTALL THE VINYL PROTECTOR  
KIT TO THE TOP OF THE EXTERIOR FIRESTOP (FOR ALL ROUND TERMINATION CAPS). IT IS STRONGLY RECOMMENDED  
WHENEVER POSSIBLE TO USE THE VINYL PROTECTOR KIT.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To seal the roof hole, and to divert rain and snow from the  
vent system:  
For Vertical Terminations - To locate the vent and install  
the vent sections:  
• Locate and mark the vent centerpoint on the underside  
of the roof, and drive a nail through the centerpoint.  
• Attach a flashing to the roof using nails, and use a non-  
hardening mastic around the edges of the flashing base  
where it meets the roof.  
• Make the outline of the roof hole around the centerpoint  
nail.  
• Attach a storm collar over the flashing joint to form a  
water-tight seal. Place non-hardening mastic around the  
joint, between the storm collar and the vertical pipe.  
• The size of the roof hole framing dimensions depend on the  
pitch of the roof. There MUST BE a 1-inch (25.4mm) clear-  
ance from the vertical vent pipe to combustible materials.  
• Slide the termination cap over the end of the vent pipe  
and rotate the pipe clockwise 1/4 turn.  
• Mark the roof hole accordingly.  
HORIZONTAL  
OVERHANG  
• Cover the opening of the installed vent pipes.  
• Cut and frame the roof hole.  
2 FT.  
MIN.  
2 FT. MIN.  
VERTICAL  
WALL  
• Use framing lumber the same size as the roof rafters  
and install the frame securely. Flashing anchored to the  
frame must withstand heavy winds.  
LOWEST  
DISCHARGE  
OPENING  
TERMINATION  
CAP  
• Continue to install concentric vent sections up through  
the roof hole (for inside vent installations) or up past the  
roof line until you reach the appropriate distance above  
the roof (for outside terminations).  
X
12  
ROOF PITCH  
IS X/ 12  
H (MIN.) - MINIMUM HEIGHT FROM ROOF  
TO LOWEST DISCHARGE OPENING  
WARNING: MAJOR U.S. BUILDING CODES  
SPECIFY MINIMUM CHIMNEY AND/OR  
!
VENT HEIGHTABOVE THE ROOF TOP. THESE MIN-  
IMUM HEIGHTS ARE NECESSARY IN THE INTER-  
EST OF SAFETY. SEE THE FOLLOWING DIAGRAM  
FOR MINIMUM HEIGHTS, PROVIDED THE TERMI-  
NATION CAP IS AT LEAST TWO (2) FEET FROM A  
VERTICAL WALLAND 2-FEET BELOW AHORIZON-  
TAL OVERHANG.  
Roof Pitch  
H (min.) ft.  
flat to 6/12  
6/12 to 7/12  
over 7/12 to 8/12  
over 8/12 to 9/12  
over 9/12 to 10/12  
over 10/12 to 11/12  
over 11/12 to 12/12  
over 12/12 to 14/12  
over 14/12 to 16/12  
over 16/12 to 18/12  
over 18/12 to 20/12  
over 20/12 to 21/12  
1.0  
1.25  
1.5  
2.0  
2.5  
3.25  
4.0  
5.0  
6.0  
7.0  
7.5  
8.0  
NOTE: This also pertains to vertical vent systems in-  
stalled on the outside of the building.  
Figure 33. Minimum Height from Roof to  
Lowest Discharge Opening  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 4. Positioning, Leveling, and  
Securing the Fireplace  
Step 5. The Gas Control Systems  
WARNING: THIS UNIT IS NOT FOR USE WITH  
SOLID FUEL.  
!
The diagram below shows how to properly position, level,  
and secure the fireplace.  
Two types of gas control systems are used with these models:  
Standing Pilot Ignition and Intermittent Pilot Ignition (IPI).  
Standing Pilot Ignition System  
This system includes millivolt control valve, standing pilot,  
thermopile/thermocouple flame sensor, and piezo ignitor.  
WARNING: 110-120 VAC MUST NEVER BE  
CONNECTED TO A CONTROL VALVE IN A  
MILLIVOLT SYSTEM.  
!
Intermittent Pilot Ignition (IPI) System  
This system includes a 3V control valve, electronic module  
and intermittent pilot.  
NAILING TABS  
(BOTH SIDES)  
WARNING: CONTINUOUS 110-120 VAC SER-  
VICE MUST BE WIRED DIRECTLYTO THE FIRE-  
!
PLACE JUNCTION BOX.  
Figure 34. Proper Positioning,  
Leveling and Securing of a Fireplace  
STANDING PILOT  
• Place the fireplace into position.  
• Level the fireplace from side to side and front to back.  
• Shim the fireplace with non-combustible material, such  
as sheet metal, as necessary.  
• Secure the fireplace to the framing by nailing or screwing.  
IPI IGNITION  
FLAME SENSOR  
u
ROD  
NOTE:  
Flames too close to the ceramic insu-  
lators can cause nuisance lockouts  
and electrode failure.  
Figure 35. Gas Control Systems  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 6. The Gas Supply Line  
NOTE: Have the gas supply line installed in accordance  
with local building codes by a qualified installer ap-  
proved and/or licensed as required by the locality. (In  
the state of Massachusetts installation must be performed  
by a licensed plumber or gas fitter).  
Use a wrench on  
shut-off valve when  
tightening gas line.  
NOTE: Before the first firing of the fireplace, the gas  
supply line should be purged of any trapped air.  
MANUAL  
SHUT-OFF  
VALVE  
NOTE: Consult local building codes to properly size  
the gas supply line leading to the 1/2 inch (13mm)  
hook-up at the unit.  
GAS  
VALVE  
This gas fireplace is designed to accept a 1/2 inch  
(13 mm) gas supply line. To install the gas supply line:  
CONTROL  
VALVE  
• A listed (and State of Massachusetts approved) 1/2 inch  
(13mm) tee-handle manual shut-off valve and a listed  
flexible gas connector are connected to the 1/2 inch  
(13mm) inlet of the control valve. NOTE: If substituting  
for these components, please consult local codes for  
compliance.  
FLEX  
CONNECTOR  
GAS LINE  
ACCESS HOLE  
Figure 36. Gas Supply Line  
Step 7. Gas Pressure Requirements  
• Locate the gas line access hole in the outer casing of  
the fireplace.  
Pressure requirements for Heat-N-Glo gas fireplaces  
are shown in the table below.  
• The gas line may be run from either side of the fireplace  
provided the hole in the outer wrap does not exceed 2 1/2”  
in diameter and it does not penetrate the actual firebox.  
Pressure  
Natural Gas  
Propane  
Minimum  
Inlet Pressure  
5.0 inches  
w.c.  
11.0 inches  
w.c.  
• The gap between the supply piping and gas access hole  
can be plugged with non-combustible insulation to pre-  
vent cold air infiltration.  
Maximum Inlet  
Gas Pressure  
14.0 inches  
w.c.  
14.0 inches  
w.c.  
• Open the fireplace lower grille, insert the gas supply line  
through the gas line hole, and connect it to the shut-off valve.  
Manifold  
Pressure  
3.5 inches  
w.c.  
10.0 inches  
w.c.  
• When attaching the pipe, support the control so that the  
lines are not bent or torn.  
A one-eighth (1/8) inch (3 mm) N.P.T. plugged tapping is  
provided on the inlet and outlet side of the gas control for a  
test gauge connection to measure the manifold pressure.  
Use a small flat blade screwdriver to crack open the screw  
in the center of the tap. Position a rubber hose over the tap  
to obtain the pressure reading.  
• After the gas line installation is complete, use a soap  
solution to carefully check all gas connections for leaks.  
WARNING: DO NOT USE AN OPEN FLAME TO  
CHECK FOR GAS LEAKS.  
!
• At the gas line access hole, use insulation to re-pack  
the space around the gas pipe.  
The fireplace and its individual shut-off valve must be  
disconnected from the gas supply piping system during  
any pressure testing of the system at test pressures in  
excess of one-half (1/2) psig (3.5 kPa).  
• Insert insulation from the outside of the fireplace and  
pack the insulation tightly to totally seal between the  
pipe and the outer casing.  
The fireplace must be isolated from the gas supply piping  
system by closing its individual shut-off valve during any  
pressure testing of the gas supply piping system at test  
pressures equal to or less than one-half (1/2) psig (3.5 kPa).  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLACK S2  
REMOTE SWITCH  
PIGTAIL  
3/16” PIGGYBACK CONNECTOR  
ON  
OFF  
ON/OFF  
SWITCH  
WHITE T2  
GAS VALUE  
RED T1  
THERMOPILE  
THERMOCOUPLE  
OPTIONAL WALL SWITCH,  
THERMOSTAT OR REMOTE  
BLACK S1  
Figure 37. Standing Pilot Ignition Wiring Diagram  
Step 8. Wiring the Fireplace  
Optional Accessories  
Optional fan and remote control kits require that 110-120  
VAC be wired to the factory installed junction box before  
the fireplace is permanently installed.  
NOTE: Electrical wiring must be installed by a licensed  
electrician.  
CAUTION: DISCONNECT REMOTE CONTROLS IF AB-  
SENT FOR EXTENDED TIME PERIODS TO PREVENT  
ACCIDENTAL FIREPLACE OPERATION.  
Wall Switch  
Position the wall switch in the desired position on a wall.  
Run a maximum of 25 feet (7.8 m) or less length of 18  
A.W.G. minimum wire and connect it to the fireplace ON/  
OFF switch pigtails.  
For Standing Pilot Ignition Wiring  
Appliance Requirements  
This appliance DOES NOT require 110-120 VAC to operate.  
WARNING: DO NOT CONNECT 110-120 VAC  
!
TO THE WALL SWITCH OR THE CONTROL  
VALVE WILL BE DESTROYED.  
WARNING: DO NOT CONNECT 110-120 VAC  
TO THE GAS CONTROL VALVE OR THE AP-  
!
PLIANCE WILL MALFUNCTION AND THE  
VALVE WILL BE DESTROYED.  
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-  
TION WHEN SERVICING CONTROLS. WIRING ERRORS  
CAN CAUSE IMPROPERAND DANGEROUS OPERATION.  
VERIFY PROPER OPERATION AFTER SERVICING.  
VARIABLE SPEED CONTROL  
NOTE: IF ANY OF THE ORIGINAL WIRE  
AS SUPPLIED WITH THE APPLIANCE  
MUST BE REPLACED, IT MUST BE  
BLK  
BLK  
REPLACED WITH TYPE 105OC RATED WIRE.  
JUNCTION BOX  
BLOWER RECEPTACLE  
BLK  
BLK  
BLK  
BLK  
BLK  
WHT  
GROUND  
WHT  
BLK  
TEMPERATURE  
SENSOR SWITCH  
BLOWER  
GRN  
BLK  
WHT  
TEMPERATURE  
SENSOR SWITCH  
JUNCTION BOX  
110-120 VAC  
FAN  
SPEED CONTROL  
(RHEOSTAT)  
Figure 38. Fan Wiring Diagram  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TRANSFORMER  
3V  
SPARK TO  
PILOT IGNITOR  
TRANSFORMER OUTLET  
120 VAC  
JUNCTION BOX  
IGNITOR  
MODULE  
3V  
BLACK (IGNITOR)  
PLUG-IN  
3V TRANSFORMER  
REM  
FAN  
BLACK (SENSOR)  
BLACK  
LOW VOLTAGE  
SEE NOTE 1  
PILOT ASSEMBLY  
FLAME SPARKER /  
SENSOR  
AND VALVE ASSEMBLY  
MUST BE GROUNDED  
(COMMON GROUND  
WITH FIREPLACE  
CHASSIS)  
GROUND TO  
FIREPLACE  
CHASSIS  
IGNITION  
MODULE  
(3V)  
BLACK  
OPTIONAL  
OPTIONAL  
BATTERY  
BACK-UP  
BATTERY  
BACK-UP  
ORANGE  
ON/OFF  
WALL SWITCH  
RED  
ON/OFF  
SWITCH  
VALVE  
LOW VOLTAGE  
SEE NOTE 1  
BROWN  
BROWN  
REMOTE  
CONTROL  
GROUND  
GREEN  
NEUTRAL  
HOT  
NOTE 1: Ignition module, valve, pilot and wall switch operate on 3 volts.  
120 VAC is required at junction box unless equipped with battery back-up.  
Figure 39. Intermittent Pilot Ignition (IPI) Wiring Diagram  
simply connect red and black wire leads to activate battery  
power (connect red to red, black to black). The fireplace  
can be used as necessary. Once power (110 VAC) is re-  
stored, disconnect red and black wire leads to extend bat-  
tery life.  
Intermittent Pilot Ignition (IPI) Wiring  
3 Volt Transformer  
This appliance comes with a 3 volt transformer found in the  
manual bag. Plug the transformer leads to the green con-  
trol module (see Figure 39). Then plug the transformer into  
the side outlet on the junction box.  
Optional Accessories  
Optional remote control kits require that 110-120 VAC be  
wired to the factory installed junction box before the fire-  
place is permanently installed.  
Appliance Requirements  
This appliance requires that 110-120 VAC be wired to the  
factory installed junction box. Maintain correct polarity when  
wiring the junction box.  
Wall Switch  
Position the wall switch in the desired position on a wall.  
Run a maximum of 25 feet (7.8 m) or less length of 18  
A.W.G. minimum wire and connect it to the fireplace ON/  
OFF switch pigtails.  
WARNING: DO NOT CONNECT 110-120 VAC  
!
TO THE GAS CONTROL VALVE OR THE AP-  
PLIANCE WILL MALFUNCTION AND THE  
VALVE WILL BE DESTROYED.  
WARNING: DO NOT CONNECT 110-120 VAC  
TO THE WALL SWITCH OR THE CONTROL  
!
VALVE WILL BE DESTROYED.  
Operation using Battery Power  
This fireplace has an optional battery operation. The sys-  
tem is fully functional with the use of two “D” size batteries  
without ordinary 110-120 VAC power.  
CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-  
TION WHEN SERVICING CONTROLS. WIRING ERRORS  
CAN CAUSE IMPROPER AND DANGEROUS OPERA-  
TION. VERIFY PROPER OPERATIONAFTER SERVICING.  
Wiring to the battery pack should be left disconnected in  
order to conserve battery life. In the case of a loss of power,  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAUTION: IF JOINTS BETWEEN THE FINISHED WALLS  
AND THE FIREPLACE SURROUND (TOP AND SIDES)  
ARE SEALED, A 300° F. MINIMUM SEALANT MATE-  
RIAL MUST BE USED. THESE JOINTS ARE NOT RE-  
QUIRED TO BE SEALED. ONLY NON-COMBUSTIBLE  
MATERIAL (USING 300° F. MINIMUM ADHESIVE, IF  
NEEDED) CAN BE APPLIED AS FACING TO THE FIRE-  
PLACE SURROUND. SEE THE DIAGRAM BELOW.  
Step 9. Finishing  
Figure 40 shows the minimum vertical and corresponding  
maximum horizontal dimensions of fireplace mantels or other  
combustible projections above the top front edge of the  
fireplace. See Figures 2 and 3 for other fireplace clearances.  
Only non-combustible materials may be used to cover the  
black fireplace front.  
WARNING: WHEN FINISHING THE FIREPLACE,  
NEVER OBSTRUCT OR MODIFY THE AIR IN-  
LET/OUTLET GRILLES IN ANY MANNER.  
FINISH WALL MATERIAL MAY BE COMBUSTIBLE  
- TOP AND SIDES  
!
NON-COMBUSTIBLE  
BOARD  
0”  
CEILING  
12"  
11"  
10"  
9"  
31”  
8"  
7"  
6"  
12”  
11”  
5"  
10”  
4"  
2”  
9”  
3"  
8”  
7”  
2"  
1”  
6”  
5”  
4"  
3”  
1”  
0”  
0”  
00  
HIGH TEMPERATURE (300F /149C MIN.)  
TOP & SIDE SEAL JOINT  
TOP FRONT EDGE  
OF FIREPLACE  
Figure 41. Sealant Material  
Hearth Extensions  
A hearth extension may be desirable for aesthetic reasons.  
However,ANSI or CAN/CGA testing standards do not require  
hearth extensions for gas fireplace appliances.  
Figure 40.  
Minimum Vertical and Maximum Horizontal  
Dimensions of Combustibles above Fireplace  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 10. Installing Trim, Logs,  
and Ember Material  
Installing the Trim  
Combustible materials may be brought up to the specified  
clearances on the side and top front edges of the fireplace,  
but MUST NEVER overlap onto the front face. The joints  
between the finished wall and the fireplace top and sides  
can only be sealed with a 300° F. (149° C) minimum sealant.  
LATCHES  
(BOTH BOTTOM  
AND TOP)  
WARNING: WHEN FINISHING THE FIREPLACE,  
NEVER OBSTRUCT OR MODIFY THE AIR INLET/  
GLASS  
ASSEMBLY  
!
OUTLET GRILLES IN ANY MANNER.  
Install optional marble and brass trim surround kits as  
desired. Marble, brass, brick, tile, or other non-combustible  
materials can be used to cover up the gap between the  
finish wall material (usually sheetrock or wood) and the  
fireplace.  
Figure 42. Glass Assembly  
Do not obstruct or modify the air inlet/outlet grilles. When  
overlapping on both sides, leave enough space so that the  
bottom grille can be lowered and the trim door removed.  
Positioning the Logs  
If the gas logs have been factory installed they should not  
need to be positioned. If the logs have been packaged  
separately, refer to the instructions that accompany the  
logs. Save the log instructions with this manual.  
If sooting occurs, the logs might need to be repositioned  
slightly to avoid excessive flame impingement.  
PLACE EMBER MATERIAL  
IN THIS AREA  
Shutter Settings  
NG  
LP  
___________________________________________  
Figure 43. Placement of the Ember Material  
Burner  
3/8”  
5/8”  
Placing the Ember Material  
Ember material is shipped with this gas fireplace. To place  
the ember material:  
• Pull the four glass latches off of the tabs on the glass  
frame. Remove glass door from the unit (see Figure 42).  
• Embers CANNOT be placed directly over ports. Care  
should be taken not to cover the lighting trail of ports  
(from back to front).  
• When placing Glowing embers onto the burner care  
should be taken so that the ports are not covered. Place  
the embers along side the port trail, but not on or in  
between the ports. Failure to follow this procedure will  
likely cause lighting and sooting problems.  
• Save the remaining ember materials for use during fire-  
place servicing.  
• Replace the glass door and a front trim door on the unit.  
• Pull out and latch the glass clips onto the tabs on the  
glass frame.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glass Specifications:  
Double-check for faulty components  
8000TRD:  
26 1/2 X 42 1/2 TEMPERED  
• Any component that is found to be faulty MUST BE re-  
placed with an approved component. Tampering with the  
fireplace components is DANGEROUS and voids all war-  
ranties.  
Heat-N-Glo fireplaces manufactured with tempered glass may  
be installed in hazardous locations such as bathtub enclo-  
sures as defined by the CPSC. The tempered glass has  
been tested and certified to the requirements ofANSI Z97.1-  
1984 and CPSC 16 CFR 1202. (Safety Glazing Certification  
Council SGCC # 1595 and 1597. Architectural Testing, Inc.  
Reports 02-31919.01 and 02-31917.01.)  
A small amount of air will be in the gas supply lines. When  
first lighting the fireplace, it will take a few minutes for the  
lines to purge themselves of this air. Once the purging is  
complete, the fireplace will light and will operate normally.  
Subsequent lightings of the fireplace will not require this  
purging of air from the gas supply lines, unless the gas  
valve has been turned to the OFF position, in which  
case the air would have to be purged.  
This statement is in compliance with SPCS 16 CFR Sec-  
tion 1201.5 “Certification and labeling requirements” which  
refers to 15 USC 2063 stating “…Such certificate shall ac-  
company the product or shall otherwise be furnished to any  
distributor or retailer to whom the product is delivered.”  
NOTE: The fireplace should be run 3 to 4 hours on the  
initial start-up. Turn it off and let it cool completely. Remove  
and clean the glass. Replace the glass and run the fireplace  
for an additional 8 hours. This will help to cure the products  
used in the paint and logs.  
Some local building codes require the use of tempered glass  
with permanent marking in such locations. Glass meeting  
this requirement is available from the factory. Please con-  
tact your dealer or distributor to order.  
u
During this break-in period it is recommended that some  
windows in the house be opened for air circulation. This will  
help avoid setting off smoke detectors, and help eliminate  
any odors associated with the fireplace’s initial burning.  
Step 11. Before Lighting the Fireplace  
Before lighting the fireplace, be sure to do the following:  
Remove all paperwork from underneath the fireplace.  
Review safety warnings and cautions  
• Read the Safety and Warning Information section at  
the beginning of this Installers Guide.  
Step 12. Lighting the Fireplace  
Double-check for gas leaks  
• Before lighting the fireplace, double-check the unit for  
possible gas leaks.  
You’ve reviewed all safety warnings, you’ve checked the  
fireplace for gas leaks, you know the vent system is  
unobstructed, and you’ve checked for faulty components.  
Now you’re ready to light the fireplace.  
Double-check vent terminations and front grilles for  
obstructions.  
• Before lighting the fireplace, double-check the unit for  
possible obstructions that could be blocking the vent ter-  
minations or the front grilles.  
WARNING: PLEASE REFER TO THE USER’S  
MANUAL FOR ALL CAUTIONS, SAFETY, AND  
!
WARNING INFORMATION PERTAINING TO THE  
LIGHTING AND OPERATION OF THE FIREPLACE.  
After the Installation  
LEAVE THIS INSTALLATION MANUAL WITH  
THE APPLIANCE FOR FUTURE REFERENCE.  
!
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintaining and Servicing Your Fireplace  
Fireplace Maintenance  
Although the frequency of your fireplace servicing and main-  
tenance will depend on use and the type of installation, you  
should have a qualified service technician perform an appli-  
ance check-up at the beginning of each heating season.  
See the table below for specific guidelines regarding each  
fireplace maintenance task.  
IMPORTANT: TURN OFF THE GAS BEFORE SERVICING  
YOUR FIREPLACE.  
Replacing old ember material  
Frequency: Once annually, during the checkup.  
By: Qualified service technician.  
Task: Brush away loose ember material near the burner.  
Replace old ember material. New ember material should  
be placed alternately on top of the burner. Save the remaining  
ember material and repeat this procedure at your next  
servicing. For more information, see Placing Ember  
Material.  
MAKE SURE THE FLAMES  
ARE STEADY—NOT  
LIFTING OR FLOATING.  
Figure 44. Burner Flame Patterns  
Cleaning Burner and Controls  
Frequency: Once annually.  
By: Qualified service technician.  
Task: Brush or vacuum the control compartment, fireplace  
logs and burner areas surrounding the logs.  
Checking Vent System  
Frequency: Before initial use and at least annually  
thereafter, more frequently if possible.  
By: Qualified service technician/Home owner.  
Task: Inspect the external vent cap on a regular basis to  
ensure that no debris is interfering with the flow of air. Inspect  
entire vent system for proper function.  
u Cleaning Flame Sensor Rod (IPI Systems)  
Frequency: Periodically.  
By: Qualified service technician.  
Task: Make a visual check of the straight flame sensor rod  
(see Figure 35). Use steel wool or fine sandpaper to carefully  
remove any existing white deposits.  
Cleaning Glass Door  
Frequency: After the first 3 to 4 hours of use. As neces-  
sary after initial cleaning.  
By: Home owner.  
Checking Flame Patterns, Flame Height  
Task: Remove and clean glass after the first 3 to 4 hours of  
use. After the initial cleaning, clean as necessary, particu-  
larly after adding new ember (flame colorant) material. Film  
deposits on the inside of the glass door should be cleaned  
off using a household glass cleaner. NOTE: DO NOT handle  
or attempt to clean the door when it is hot and DO  
NOT use abrasive cleaners.  
Frequency: Periodically.  
By: Qualified service technician/Home owner.  
Task: Make a visual check of your fireplace’s flame patterns.  
Make sure the flames are steady - not lifting or floating.  
See Figure 44. The flame sensor (IPI) or thermopile/  
thermocouple (standing pilot) tips should be covered with  
flame. See Figure 35.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Camcorder 310664D User Manual
Graco Marine Sanitation System TI1962A User Manual
Groupe SEB USA T FAL Electric Pressure Cooker Pressure Cooker User Manual
HannsG Car Video System HSG 1085 User Manual
Honeywell Network Hardware HEMS II User Manual
Honeywell Portable Generator HW7000EH User Manual
Hotpoint Washer WML 560 P G A K User Manual
Iluv MP3 Docking Station iVM153 User Manual
Image Hot Tub IMSW73910 User Manual
Image Treadmill IMTL19901 User Manual