Greenheck Fan Ventilation Hood PVE 20 User Manual

Part #472846  
®
Heat Recovery Ventilators  
Installation, Operation and Maintenance Manual  
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the  
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions  
could result in personal injury and/or property damage! Retain instructions for future reference.  
Models: PVe-20  
PVe-35  
PVe-45  
PVe-55  
General Safety Information  
Only qualified personnel should install this system.  
Personnel should have a clear understanding of these  
instructions and should be aware of general safety  
precautions. Improper installation can result in electric  
shock, possible injury due to coming in contact with  
moving parts, as well as other potential hazards.  
Other considerations may be required if high winds  
or seismic activity are present. If more information  
is needed, contact a licensed professional engineer  
before moving forward.  
1. Follow all local electrical and safety codes, as well  
as the National Electrical Code (NEC), the National  
Fire Protection Agency (NFPA), where applicable.  
Follow the Canadian Electric Code (CEC) in  
Canada.  
2. All moving parts must be free to rotate without  
striking or rubbing any stationary objects.  
3. Unit must be securely and adequately grounded.  
4. Do not spin fan wheel faster than maximum  
cataloged fan RPM. Adjustments to fan speed  
significantly affects motor load. If the fan RPM is  
changed, the motor current should be checked to  
make sure it is not exceeding the motor nameplate  
amps.  
DANGER  
Always disconnect power before working on or near  
this equipment. Lock and tag the disconnect switch  
or breaker to prevent accidental power up.  
5. Do not allow the power cable to kink or come in  
contact with oil, grease, hot surfaces or chemicals.  
Replace cord immediately if damaged.  
CAUTION  
When servicing the unit, the internal components  
may be hot enough to cause pain or injury. Allow  
time for cooling before servicing.  
6. Verify that the power source is compatible with the  
equipment.  
7. Never open access doors to the unit while it is  
running.  
CAUTION  
Precaution should be taken in explosive  
atmospheres.  
Model PVe Heat Recovery Unit  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
Table of Contents  
Basic Operation  
Basic Operation . . . . . . . . . . . . . . 3  
Installation  
Supplemental Installation, Operation and  
Maintenance Manuals . . . . . . . . . . . 3  
Installation . . . . . . . . . . . . . . . . 3  
Installation Stages . . . . . . . . . . . . . 4  
Lifting with a Crane or Forklift . . . . . . . . 4  
Roof Curb and Rail Mounting  
The PVe brings in fresh outdoor air and removes stale  
exhaust air from the building. Prior to discharging  
the exhaust air, the plate heat exchanger transfers  
energy from the exhaust air to the incoming outdoor  
air. When used in the cooling mode, heat energy is  
transferred from incoming outdoor air to the exhaust  
air. Simply put, this unit preconditions the outdoor air  
to save money on heating and cooling costs.  
Recommended Roof Opening . . . . . . . . 4  
Service Clearances . . . . . . . . . . . . 5  
Roof Curb Mounting . . . . . . . . . . . . 6  
Curb Dimensions and Weights . . . . . . . . 6  
Ductwork Connections . . . . . . . . . . . 6  
Rail Mounting / Layout . . . . . . . . . . . 7  
Access Panel Description and Location . . . 7  
Dimensional Data . . . . . . . . . . . . . 8  
OUTDOOR  
AIR  
Drain Trap   
 
 
 
 
 
 
 
 
 
 
 
 
 
  8  
Electrical Information  
General Electrical Information . . . . . . . . 9  
Control Center Components. . . . . . . . . 10  
Electric Heater Application/Operation . . . . . 10  
Optional Accessories  
SIDE VIEW  
RETURN DUCT  
SUPPLY DUCT  
Frost Control Application/Operation . . . . . 11  
Economizer Application/Operation . . . . . . 11  
Variable Frequency Drives and Wiring . . . . 12-13  
Typical Wiring Diagram . . . . . . . . . . . 14  
Sensors and Lights . . . . . . . . . . . . 15  
Remote Control Panel and Wiring . . . . . . 16  
Sensors Mounted by Factory . . . . . . . . 17  
Sequence of Operation  
Supplemental Installation,  
Operation and Maintenance  
Manuals  
Refer to the following Installation, Operation and  
Maintenance Manuals for additional details:  
Part #462844 — Exhaust Weatherhood  
Start-Up  
Additional manuals are available for each accessory  
used in the PVe. These additional manuals are  
provided by the respective manufacturers and are  
included with unit shipment.  
General Start-Up Information . . . . . . . . 18  
Optional Accessories . . . . . . . . . . . 19  
Unit Start-Up, Fans . . . . . . . . . . 20-21  
Routine Maintenance Checklist  
Overview. . . . . . . . . . . . . . . . . 22  
General . . . . . . . . . . . . . . . . . 23  
Fan Belts. . . . . . . . . . . . . . . . . 23  
Fan Motors . . . . . . . . . . . . . . . . 23  
Fan Wheel and Fasteners . . . . . . . . . . 24  
Fan Bearings . . . . . . . . . . . . . . . 24  
Filters . . . . . . . . . . . . . . . . . . 24  
Door Seal Maintenance. . . . . . . . . . . 24  
Parts List . . . . . . . . . . . . . . . . . 25  
Sequence of Operation . . . . . . . . . . . 25  
Troubleshooting – Airflow. . . . . . . . . . 26  
Troubleshooting – Unit . . . . . . . . . .27-28  
Maintenance Log . . . . . . . . . . . 29-31  
Warranty . . . . . . . . . . . . . Backcover  
Installation  
The system design and installation should follow  
accepted industry practice, such as described in the  
ASHRAE Handbook.  
Adequate space should be left around the unit for  
filter replacement and maintenance. Sufficient space  
should be provided on the side of the unit for routine  
service and component removal should that become  
necessary.  
See Service Clearances and Access Panel Description  
sections for more details.  
WARNING  
All factory provided hoisting and fork lifting points  
must be used when lifting the unit. When rigging for  
hoisting with a crane, spreader bars must be used.  
Failure to comply with this safety precaution could  
result in property damage, serious injury or death.  
See Installation Stages for additional details.  
Model PVe Heat Recovery Unit  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation Stages  
Lifting  
Once the PVe Heat Recovery Ventilator is delivered  
to the jobsite, the actual installation occurs in several  
distinct stages.  
1. Installation location must be carefully considered.  
Service clearances needed for later maintenance  
of the unit must be taken into consideration,  
access to Return Air and Discharge Air ducting  
must be anticipated. And structural support  
of the unit must be taken into consideration.  
See appropriate sections of this manual for  
further information. If electric wiring is going  
to be brought into the cabinet from beneath  
(recommended), preparations for that step must  
be taken during the planning stage. If possible, a  
GKD curb should be installed prior to installation  
of roofing materials so that flashing can be run up  
the sides of the curb.  
Forklift lifting  
points  
Crane hoisting points  
(typical)  
Lifting with a Crane  
2. Hoisting the cabinet can be accomplished with  
either a crane or a fork lift. If a forklift is used, the  
forks must extend all the way through the cabinet  
and project from the far side. The forks should  
be padded with a layer of ¼-inch thick plywood  
or other suitable material. If a forklift is used, the  
cabinet cannot be lowered directly onto the GKD  
curb unit because the forks will be in the way. It  
will be necessary to set the unit onto appropriate  
dunnage for final lowering after the forks are  
removed.  
1. Before lifting, be sure that all shipping material  
has been removed from unit.  
2. To assist in determining rigging requirements,  
weights are shown below.  
3. Unit must be lifted by simultaneously hoisting  
at all four corner lifting points provided on base  
structure, ensuring proper load distribution and  
support at each corner.  
4. Rigger to use suitable mating hardware to attach  
to unit corner lifting points.  
5. Spreader bar(s) must  
If a crane is used, hoisting points are provided at  
each corner of the cabinet. Small, padded hooks  
must be inserted into the hoisting points. There  
is very little internal clearance inside the cabinet  
base and the use of large lifting hooks will either  
dig into the cabinet structure or else interfere with  
the seating of the cabinet on the GKD curb.  
span the unit to  
prevent damage to  
the cabinet by the lift  
cables.  
6. Always test-lift the  
unit to check for  
proper balance  
and rigging before  
hoisting to desired  
location.  
2. Physical installation of the unit should be  
completed prior to installation of electrical wiring.  
Condensate drains should be connected and if  
necessary, heat strips installed on the drains to  
prevent freezing of the traps. A final check should  
be made to ensure that the unit has been installed  
level by using the bottom of the cabinet as a  
reference, not the top (the cabinet roof is sloped  
to the rear). Ensure that all ductwork has been  
properly and permanently assembled.  
7. Never lift units by weatherhoods.  
8. Never lift units in windy conditions.  
9. Preparation of curb and roof openings should be  
completed prior to lifting the unit and setting on  
the curb.  
The weights shown are a  
worst case scenario based  
Unit Weights (lbs.)  
Approx.  
Weight  
on the sheet metal and  
component weights for  
the unit. These weights  
include sheet metal weights  
added together with the  
largest motors, blowers and  
accessories for the units.  
3. Prior to wiring the unit, installer should verify that  
all optional accessories are accounted for. Verify  
that electric components such as motors are rated  
properly for the voltage actually being used. Note  
that some of the illustrations and pictures used in  
this manual show the use of three phase power  
and if the user actually has single phase power,  
there will be minor variations present. The unit  
should be wired according to the supplied wiring  
diagrams and Best Practices. Careful testing  
and balancing of the power source should be  
accomplished at this time.  
Model  
PVe-20  
PVe-35  
PVe-45  
PVe-55  
1300  
1600  
2100  
2700  
Lifting with a Forklift  
Unit base rail includes forklift lifting locations. Use  
weights shown to determine forklift size requirements.  
Model PVe Heat Recovery Unit  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service Clearances  
Roof Curb and Rail Mounting  
When installed on a roof, a typical installation  
will include at least one roof penetration in order  
to deliver return air to the unit from the space.  
Additionally, a second roof penetration may be used  
for supply air discharge to the space.  
B
C
Intake and Discharge Options  
A
D
Option  
OA Intake  
Bottom  
Top  
Side  
X
End  
X
D
SA Discharge  
RA Intake  
X
X
EA Discharge  
OA - Outdoor Air  
X
Model  
A
B
C
D
SA - Supply Air (to the space)  
RA - Return Air (from the space)  
EA - Exhaust Air  
36  
(920)  
36  
(920)  
36  
(920)  
60  
(1530)  
PVe-20  
48  
(1220)  
36  
(920)  
36  
(920)  
60  
(1530)  
PVe-35  
PVe-45  
PVe-55  
EA Discharge  
60  
(1530)  
36  
(920)  
36  
(920)  
60  
(1530)  
B
SA Discharge  
A
72  
(1830)  
36  
(920)  
36  
(920)  
60  
(1530)  
SA Discharge  
D
All dimensions are shown in inches (millimeters). The  
weatherhoods include 2-inch aluminum mesh filters that  
are removed out of the end of the hood as shown in this  
drawing and require extra clearance for removal.  
C
OA Intake  
Do not face the Outdoor Air Intake of the unit into  
prevailing wind and also keep the air intake away  
from any other exhaust fans. Likewise, position the  
Exhaust Air Discharge opening away from any other  
outdoor air intakes of other equipment.  
E
F
RA Intake  
When cutting duct openings, cut opening one inch  
larger (25 mm) than duct size to allow clearance for  
installation. Area enclosed by roof curb must comply  
with clearance to combustible materials. If the roof  
is constructed of combustible materials, area within  
the roof curb must be ventilated, left open or covered  
with non-combustible material which has an “R” value  
of at least five (5). If area within curb is left open,  
higher radiated sound levels may result.  
Duct Dimensions  
Model  
A
B
C
D
E
F
10.7  
(280)  
12.2  
(310)  
10.3  
(270)  
11.8  
(300)  
22.0  
(570)  
14.0  
(360)  
PVe-20  
11.9  
(310)  
13.7  
(350)  
11.4  
(290)  
13.1  
(340)  
14.0  
(360)  
34.0  
(870)  
PVe-35  
PVe-45  
PVe-55  
Where the supply or warm air duct passes through  
a combustible roof, a clearance of one inch must be  
maintained between the outside edges of the duct  
and combustible material in accordance with NFPA  
Standard 90A.  
14.1  
(360)  
16.0  
(410)  
13.3  
(340)  
14.5  
46.0  
14.0  
(370) (1170) (360)  
16.4  
(420)  
19.2  
(490)  
15.9  
(450)  
18.6 60.0 14.0  
(480) (1530) (360)  
All dimensions are shown in inches (millimeters).  
Position the unit roof opening such that the Return Air  
Intake will line up with the corresponding ductwork.  
If applicable, adjust position to also accommodate  
the SA Discharge vent. Make certain that proposed  
positioning of the unit still maintains recommended  
service clearances.  
Model PVe Heat Recovery Unit  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Roof Curb Mounting  
Curb Dimensions and Weights  
Roof curb assembly and mounting instructions are  
contained in the Roof Curb Assembly Instructions  
supplied with Model GKD roof curb.  
Rooftop PVe units require curbs to be mounted first,  
in accordance with their appropriate instructions.  
Curb unit is to be installed and then duct connections  
are to be made prior to setting of the unit.  
1  Factory Supplied Roof Curbs: Roof curbs are  
Model GKD. The GKD ships in a knockdown kit  
(which includes duct adapter) and requires field  
assembly by others. Assembly instructions are  
included with the GKD curbs.  
2  Install Curb: Locate the assembled curb over  
roof opening and verify precise location of curb  
relative to the roof opening, in accordance with  
dimensions given previously. Fasten curb loosely  
in place and then shim as needed to ensure a  
level installation. Tighten roof fastening hardware  
and then re-check for level. Verify that diagonal  
dimensions of installed curb are plus or minus  
1/8-inch of each other.  
3  Install Ductwork: Install needed ductwork in  
accordance with SMACNA and AMCA guidelines.  
Duct adapter is provided to support ducts prior  
to setting the unit.  
L
W
Curb Weight  
(lbs.)  
Unit Size  
L
W
PVe-20  
PVe-35  
PVe-45  
PVe-55  
99.4  
99.4  
36.8  
44.6  
56.3  
71.3  
195  
216  
261  
316  
105.9  
111.7  
All dimensions are shown in inches.  
4  Install Insulation: One-inch deep insulation  
pans are provided with the curb assembly. Set  
the insulation pans per instructions and then  
install insulation in the pans prior to setting  
the unit. Insulation is not provided by the unit  
manufacturer, it is to be supplied by others.  
5  Set the PVe Unit: Lift unit to a point directly  
above the curb and duct openings. Guide unit  
carefully while lowering in order to align with duct  
openings. The roof curb will seat in a recess in  
the base of the PVe unit. Verify that the unit is  
properly seated on the curb and is level.  
Ductwork Connections  
Examples of poor and good fan-to-  
duct connections are  
shown below. Airflow  
out of the fan should  
be directed straight or  
curve the same direction  
as the fan wheel rotates.  
Poor duct  
POOR  
Length of Straight Duct  
installation will  
result in low  
Unit Side  
airflow and other  
system effects.  
Unit Base  
1.895  
GOOD  
Recommended Discharge Duct Size and Length  
Unit Size Blower Size Duct Size Straight Duct Length  
Insulation Pan  
PVe-20  
PVe-35  
PVe-45  
PVe-55  
9
14 x 14  
20 x 20  
20 x 20  
28 x 28  
36  
36  
36  
60  
4.844  
10  
12  
15  
Roof Curb  
All dimensions are shown in inches.  
1.549  
0.775  
Recommended duct sizes are based on velocities across the  
cfm range of each model at approximately 800 feet per minute  
(FPM) at minimum airflow and up to 1600 fpm at maximum  
airflow. Recommended duct sizes are only intended to be a  
guide and may not satisfy the requirements of the project.  
Refer to plans for appropriate job specific duct size and/or  
velocity limitations.  
Dimensions are shown in inches.  
Straight duct lengths were calculated based on 100% effective  
duct length requirements as prescribed in AMCA Publication  
201. Calculated values have been rounded up to nearest foot.  
Curb Cap Details for Factory Supplied Roof Curbs  
Model PVe Heat Recovery Unit  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rail Mounting / Layout  
Access Panel Description and  
Location  
An alternative method of unit installation is to mount  
the unit on rails supplied by others. The purpose of  
mounting the unit on either rails or the GKD curb is to  
elevate the unit away from moisture conditions and  
to provide proper clearance for installation of water  
drain traps.  
5
• Rails should be designed to handle the weight of  
the PVe unit, taking into consideration weight per  
square inch on bearing surfaces. Rails should be  
positioned as shown in the drawing below, taking  
into consideration proper load distribution and  
support by roof support elements.  
4
• Make sure that rail positioning does not interfere  
with either the RA Intake duct or the optional  
straight down SA Discharge duct.  
• Rails should extend beyond the unit a minimum  
of 12 inches.  
3
2
1
• Set unit on rails.  
Filters  
Optional OA Damper  
1
Optional RA Damper  
Optional Face and Bypass Dampers  
Plate Heat Exchanger  
2
Optional Preheater  
3
Plate Heat Exchanger  
4
Control Center  
5
Blowers  
Isometric view of  
PVe on rails  
A
B
C
D
Side view of  
PVe on rails  
B*  
14  
14  
14  
14  
C*  
D
Unit Size  
A
5
5
5
5
PVe-20  
PVe-35  
PVe-45  
PVe-55  
13.25  
12.00  
15.50  
18.75  
7.75  
6.50  
10.5  
13.25  
All dimensions are shown in inches.  
*Zones B and C identify regions/zones where rails may  
not be place due to ductwork.  
Model PVe Heat Recovery Unit  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional Data  
Drain Trap  
The PVe plate heat exchanger is provided with two  
stainless steel drain pans and each is equipped with  
a one inch MPT drain fitting. A drain trap must be  
installed on each drain fitting to allow excess water  
to flow out of the drain pans. More importantly,  
though, due to the negative internal static pressure  
inside the PVe cabinet, installing drain traps prevents  
outdoor air from being pulled into the cabinet and  
consequently causing overfilling of the drain pans or  
misting of PVe components.  
Exhaust  
Air Hood  
E
Bypass  
Damper  
C
Face  
Damper  
Plate Heat  
Exchanger  
To ensure the drain trap works properly, the trap  
height must account for the difference in static  
pressure between ambient conditions outside the  
unit and the negative static pressure inside the PVe  
cabinet. An assumption of 3.0 in. wg differential is  
normally sufficient for all PVe units and this would  
require a trap design as shown. If the internal static is  
believed to be higher, consult the factory.  
Control Center  
Top view  
D
A
Outdoor  
Air Hood  
Plate Heat  
B
Exchanger  
4 in.  
2 in.  
Side view  
Unit  
Size  
A
B
C
D
E
Refer to local codes to determine drainage  
requirements. If draining onto a roof, place a drip pad  
beneath the drain outlet to protect the roof. If draining  
onto a roof is not acceptable, a drain line must be  
attached to the drain trap. The drain line must be  
pitched away from the unit at least 1/8-inch per foot.  
On longer runs, an air break should be incorporated  
to ensure proper drainage. Local codes may require  
drainage into a waste water system.  
104.1  
(2650)  
59.7  
(1520)  
41.5  
(1060)  
20.3  
(520)  
20.7  
(530)  
PVe-20  
104.1  
(2650)  
59.7  
(1520)  
49.2  
(1250)  
25.2  
(640)  
17.7  
(450)  
PVe-35  
PVe-45  
PVe-55  
110.6  
(2810)  
59.7  
(1520)  
61.1  
(1560)  
25.2  
(640)  
19.0  
(490)  
Drainage problems result not only from improper  
drain trap design, but also from lack of maintenance  
in the PVe cabinet. Algae can form in the drain pans  
and traps and cause reduced water flow, which can  
in turn result in a backup in the drain system. Regular  
maintenance and inspection will prevent this from  
occurring. If the drains have a cleanout opening, be  
sure and close the opening after cleaning and refill  
the trap with water.  
116.5  
(2959)  
59.7  
(1520)  
76.1  
(1940)  
25.2  
(640)  
23.8  
(610)  
All dimensions are shown in inches (millimeters).  
Door handles, hinges and other protrusions are not  
included in the dimensions above. Dimensions are  
rounded up to the nearest .1 inch (2.54 millimeters).  
Model PVe Heat Recovery Unit  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical Information  
CAUTION  
The unit must be electrically grounded in accordance  
with the current National Electrical Code, ANSI/  
NFPA 70. In Canada, use current CSA Standard  
C22.1, Canadian Electrical Code, Part 1. In addition,  
the installer should be aware of and comply with  
any local ordinances or electrical power company  
requirements that might apply. System power wiring  
must be properly fused and conform to the local and  
national electrical codes. System power wiring is to  
the main disconnect (door interlocking disconnect  
switch standard on most units) or distribution block  
and must be compatible with the ratings shown on  
the nameplate: supply power voltage, phase, and  
amperage (Minimum Circuit Amps - MCA, Maximum  
Overcurrent Protection - MOP). All wiring beyond this  
point has been done by the manufacturer and cannot  
be modified without affecting the unit’s agency /  
safety certification.  
If any of the original wire as supplied with the  
appliance must be replaced, it must be replaced  
with wiring material having a temperature rating of  
at least 105ºC.  
WARNING  
To prevent injury or death due to electrocution or  
contact with moving parts, lock disconnect switch  
open.  
Most factory supplied electrical components are  
pre-wired. To determine what electrical accessories  
require additional field wiring, refer to the unit-specific  
wiring diagram located on the inside of the unit  
control center access door. The low voltage control  
circuit is 24 VAC and control wiring should not exceed  
0.75 ohms.  
Refer to Field Control Wiring Length/Gauge table for  
wire length maximums for a given wire gauge.  
If field installing an additional disconnect switch, it  
is recommended that there be at least four feet of  
service room between the switch and system access  
panels. When providing or replacing fuses in a fusible  
disconnect, use dual element time delay fuses and  
size according to the rating plate.  
Field Control Wiring Length/Gauge  
Total  
Wire Length  
Minimum  
Wire Gauge  
125 ft.  
200 ft.  
300 ft.  
450 ft.  
18  
16  
14  
12  
If power supply is desired through the bottom of unit,  
run the wiring through the curb, cut properly aligned  
holes in the insulation pan and the bottom of the PVe  
cabinet bottom and wire to the disconnect switch.  
Seal penetrations to prevent leakage or air infiltration.  
Control wires should not be run inside the same  
conduit as that carrying the supply power. Make sure  
that field supplied conduit does not interfere with  
access panel operation.  
The electric supply to the unit must meet stringent  
requirements for the system to operate properly.  
Voltage supply and voltage imbalance between  
phases should be within the following tolerances.  
If the power is not within these voltage tolerances,  
contact the power company prior to operating the  
system.  
If wire resistance exceeds 0.75 ohms, an industrial-  
style, plug-in relay should be added to the unit  
control center and wired in place of the remote  
switch (typically between terminal blocks R and G  
on the terminal strip (refer to Typical Control Center  
Components). The relay must be rated for at least  
5 amps and have a 24 VAC coil. Failure to comply  
with these guidelines may cause motor starters to  
“chatter” or not pull in which can cause contactor  
failures and/or motor failures.  
Voltage Supply: See voltage use range on the rating  
plate. Measure and record each supply leg voltage at  
all line disconnect switches. Readings must fall within  
the allowable range on the rating plate.  
Voltage Imbalance: In a 3-phase system, excessive  
voltage imbalance between the phases will cause  
motors to overheat and eventually fail. Maximum  
allowable imbalance is 2%. To determine voltage  
imbalance, use recorded voltage measurements in  
this formula.  
Key:  
V1, V2, V3 = line voltages as measured  
VA (average) = (V1 + V2 + V3) / 3  
VD = Line voltage (V1, V2 or V3) that  
deviates farthest from average (VA)  
Formula: % Voltage Imbalance = [100 x (VA-VD)] / VA  
Model PVe Heat Recovery Unit  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical Control Center Components  
1. Main Disconnect (non-fusible, lockable)  
2. Motor Starter  
3. Motor Starter  
4. Power Distribution Blocks  
5. 24 VAC Control Transformer  
6. 24 VAC Terminal Strip  
7. Temperature Sensor with Override (used for  
Economizer Mode)  
Electric Heater Application/Operation  
Factory installed electric heaters are optionally  
provided in order to provide preheat frost control.  
An electric preheater warms the outdoor air prior to  
being drawn through the PVe plate heat exchanger.  
Electric heaters are available in 208, 230, or 460 VAC.  
Refer to heater nameplate for voltage rating.  
Preheaters: If an optional preheater is supplied with  
the unit, it is installed as a single stage on/off control.  
Preheaters are single-point wired at the factory. A  
thermocouple type  
8. Dirty Filter Sensor  
9. Dirty Filter Sensor  
temperature sensor  
is mounted in the  
outdoor airstream  
after the preheater and  
5
1
that thermocouple will  
switch the preheater  
on. See Frost Control  
Application/Operation  
6
for typical set points.  
If the temperature falls  
below the set point  
4
and a pressure drop  
sensor is triggered, the  
preheater will turn on.  
7
2
3
8
9
Model PVe Heat Recovery Unit  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Accessories  
Timed exhaust frost control includes a timer in  
addition to the thermostat and pressure sensor. The  
timer is located on the right hand side of the control  
module (low voltage side). When timed exhaust frost  
control is initiated, the timer will turn the supply  
blower on and off to allow the warm exhaust air  
to defrost the cube. Default factory settings are  
5 minutes off and 30 minutes on.  
Frost Control Application/Operation  
Cold climates, in combination with higher indoor  
humidity levels, may cause frost to form on the plate  
heat exchanger. To protect against the formation of  
frost, a temperature sensor is installed to measure  
the temperature of the air leaving the plates in the  
exhaust airstream. There are three different methods  
of frost control that may optionally be used. These  
options are installed, wired and pre-set at the factory.  
To identify specific components, see the included  
unit-specific schematic wiring diagram.  
Plate (cube) bypass. The plate bypass frost control  
function is essentially the same as Economizer  
mode (see below) except that it is initiated by  
temperature sensors for the purpose of frost removal  
or prevention.  
1. Timed Exhaust frost control  
The supply blower cycles on and off based on a  
factory provided and installed timer. The timer is  
located on the right hand side (low voltage side)  
of the control module.  
Electric preheat frost control includes an electric  
heater at the outdoor air intake, an airflow pressure  
switch and a temperature sensor. See also Electric  
Heater Application / Operation. When electric preheat  
frost control is initiated, the electric preheater will  
turn on and warm the incoming air to prevent frost  
accumulation on the cube.  
2. Plate heat exchanger bypass – Open/Closed  
When the exhaust air leaving the exchanger  
(cube) drops below the adjustable set-point, both  
the face and bypass dampers will allow air to  
bypass the cube. This allows warm exhaust air  
to melt any frost on the cube. Once the exhaust  
air temperature rises above the set-point, the unit  
returns to normal operation.  
Economizer Application/Operation  
Under certain conditions, the most efficient use of  
the PVe Heat Recovery Ventilator includes bypassing  
the incoming outdoor air around the plate heat  
exchanger. When cooling air is being called for and  
the outdoor air temperature is below a pre-set point,  
the PVe will switch to Economizer Mode. Integral  
face and bypass dampers will cycle into a bypass  
condition, allowing incoming cool air to flow past  
the cube, rather than flow through it. Economizer  
Mode is strictly temperature initiated and dependent  
on the Temperature Sensor with override located in  
the control center. See component #7 on the Typical  
Control Center Components illustration.  
3. Electric preheat frost control  
An electric preheater can optionally be built into  
the outdoor air intake. When the temperature  
of the exhaust air leaving the plate unit (the  
cube) drops below the adjustable set-point, the  
preheater will switch on. Once the exhaust air  
temperature increases, the preheater will switch  
off.  
Frost Threshold Temperatures  
Indoor RH @ 70°F  
Frost Threshold Temp  
20%  
30%  
40%  
-5º F  
-5º F  
-5º F  
The typical temperature setting corresponds to the  
indoor air relative humidity as shown in the Frost  
Threshold Temperatures table and represents when  
frost can occur. An increase in pressure drop would  
indicate that frost is occurring. Both the pressure  
sensor AND the outdoor air temperature sensor  
must trigger in order to initiate frost control. The  
two sensors together insure that frost control is  
only initiated during a real frost condition. Field  
wiring of a light (or other alarm) between 6 & C in  
the control center will notify personnel when unit is  
in frost control mode (refer to Remote Panel Wiring  
schematics for wiring details). The following explains  
the three options in more detail.  
Model PVe Heat Recovery Unit  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Variable Frequency Drives for Energy Recovery Blowers  
Optional factory installed, wired, and programmed variable frequency drives (VFDs) may have been provided  
for modulating or multispeed control of the blowers. One VFD is provided for each blower (supply air and  
exhaust). The VFD’s provided are either Yaskawa model V1000 or J1000. Refer to the tables in this section for  
factory settings and field wiring requirements. Refer to the unit control center for unit specific wiring diagram (an  
example wiring diagram has been provided in this manual for reference). When making adjustments outside of  
For technical support, contact Yaskawa direct at 1-800-927-5292.  
R+ R- S+ S- IG  
P1 P2 PC A1 A2 +V AC AM AC MP  
S1 S2 S3 S4 S5 S6 S7 HC SC H1 RP MA MB MC  
S1 S2 S3 S4 S5 SC A1 +V AC AM AC  
MA MB MC  
J1000  
V1000  
Factory Set Points  
Variable Frequency Drives (VFDs) for the blowers are  
factory setup to operate in one of the three following  
modes:  
OPTION 1 - 0-10 VDC CONTROL  
USER TO PROVIDE ISOLATION AS REQUIRED  
Modulating: 0-10 VDC signal wired in the field by  
others varies the speed of the blower between 30  
and 60Hz  
0-10 VDC CONTROL SIGNAL (BY OTHERS)  
WIRED TO A1 (+) AND AC (COMMON)  
0 VDC=30 Hz  
A1 AC  
10 VDC=60 Hz  
Multispeed: Digital contact closures by others  
command the VFD to run at multiple speed settings:  
• SC to S4 - Drive runs at 40Hz  
FOR ONE 0-10 SIGNAL, WIRE TO DRIVES IN PARALLEL  
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL  
• SC to S5 - Drive runs at 30Hz  
FOR CONTINUOUS 60Hz OPERATION JUMPER TERMINALS A1 AND +V.  
CO Sensor: A digital contact closure from an  
2
optional factory provided CO sensor sends the  
2
VFD to high or low speed depending on CO ppm  
2
OPTION 2 - MULTI SPEED CONTROL  
levels at the sensor.  
USER TO PROVIDE CONTACTS AND ISOLATION  
AS REQUIRED  
The terminal locations for Modulating (option 1) and  
Multispeed (option 2) are shown on the left. Most  
of the set points in the VFDs are Yaskawa factory  
defaults. However, a few set points are changed at  
Greenheck and are shown in the tables on the next  
page. These settings are based on the VFD mode  
selected.  
To gain access to change set points on the V1000 and  
J1000 drives, parameter A1-01 needs to be set at “2”.  
To prevent access or tampering with drive settings on  
either drive, change parameter A1-01 to “0”.  
NEITHER S4 OR S5 CONTACT CLOSED  
S4 S5 SC  
DRIVE SPEED = 60 Hz.  
S4 TO SC CONTACT CLOSED (BY OTHERS)  
DRIVE SPEED = 40 Hz.  
S5 TO SC CONTACT CLOSED (BY OTHERS)  
DRIVE SPEED = 30 Hz.  
SEE VFD INSTALLATION MANUAL FOR MORE DETAIL  
TO CHANGE THE FACTORY SET Hz CHANGE THE FOLLOWING PARAMETERS.  
PARAMETER A1-01 CHANGE TO 2  
PARAMETER d1-01 FOR NEW 60Hz SETTING  
PARAMETER d1-02 FOR NEW 40Hz SETTING  
PARAMETER d1-03 FOR NEW 30Hz SETTING  
PARAMETER A1-01 CHANGE TO 0  
Drive Operation  
SC to S1 contact for On/Off  
A1 (0-10 VDC) referenced to AC. Can use +15 VDC  
from +V  
Model PVe Heat Recovery Unit  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Factory Set Points - continued  
CO SENSOR CONTROL FOR FAN SPEED  
2
Resetting the V1000 drive to factory defaults  
To reset the V1000 drive back to Greenheck factory  
defaults go to parameter A1-01 and set it to “2”.  
Then go to A1-03 and change it to “1110” and press  
enter. The drive is now reset back to the settings  
programmed at Greenheck. This option is not  
available on the J1000.  
(1/2 SPEED WHEN C0 DROPS bELOW 700 PPM)  
2
(FULL SPEED WHEN C0 RISES AbOVE 800 PPM)  
2
Setting  
Parameter  
V1000  
J1000  
A1-01  
Access Level  
2
0
1
2
0
1
b1-01 Reference Source (Frequency)  
b1-17  
C1-01  
C1-02  
C6-02  
d1-01  
d1-02  
d2-02  
VFD Start-Up Setting  
Acceleration Time  
Deceleration Time  
Carrier Frequency  
30 sec. 30 sec.  
30 sec. 30 sec.  
MODULATING CONTROL FOR FAN SPEED  
(0-10 VDC)  
1
1
Setting  
Parameter  
Frequency Reference 1  
Frequency Reference 2  
Ref Lower Limit  
60 Hz  
30 Hz  
50%  
30 Hz  
60 Hz  
50%  
V1000  
J1000  
A1-01  
b1-17  
C1-01  
C1-02  
C6-02  
d2-02  
Access Level  
VFD Start-Up Setting  
Acceleration Time  
Deceleration Time  
Carrier Frequency  
Ref Lower Limit  
2
1
2
1
Motor  
FLA  
Motor  
FLA  
30 sec. 30 sec.  
30 sec. 30 sec.  
E2-01  
Motor Rated FLA  
H3-10  
A1-01  
A2 Not Used  
Access Level  
F
0
NA  
0
1
1
50%  
Motor  
FLA  
50%  
Motor  
FLA  
E2-01  
Motor Rated FLA  
H3-04  
A1-01  
Terminal A1 Bias  
Access Level  
50%  
50%  
0
0
MULTISPEED CONTROL FOR FAN SPEED  
(1/3 OR 1/2 SPEED REDUCTION)  
Setting  
Parameter  
V1000  
J1000  
A1-01  
Access Level  
2
0
1
2
0
1
b1-01 Reference Source (Frequency)  
b1-17  
C1-01  
C1-02  
C6-02  
d1-01  
d1-02  
d1-03  
d1-04  
d2-02  
VFD Start-Up Setting  
Acceleration Time  
30 sec. 30 sec.  
30 sec. 30 sec.  
Deceleration Time  
Carrier Frequency  
1
1
Frequency Reference 1  
Frequency Reference 2  
Frequency Reference 3  
Frequency Reference 4  
Ref Lower Limit  
60 Hz  
40 Hz  
30 Hz  
60 Hz  
50%  
60 Hz  
40 Hz  
30 Hz  
60 Hz  
50%  
Motor  
FLA  
Motor  
FLA  
E2-01  
H1-04  
H1-05  
H1-06  
Motor Rated FLA  
Multfunction Input Sel 4  
(Terminal S4)  
3
4
5
3
4
Multifunction Input Sel 5  
(Terminal S5)  
Multifunction Input Sel 6  
(Terminal S6)  
NA  
H3-10  
A1-01  
A2 Not Used  
Access Level  
F
0
NA  
0
Model PVe Heat Recovery Unit  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical Wiring Diagram  
Following is an example of a typical wiring diagram for the PVe. It is representative of circuitry that may be  
found in any PVe unit, but it is not intended to be unit-specific. Each PVe unit has a detailed wiring diagram  
located within the control panel. This diagram illustrates typical factory wiring and also illustrates circuits that  
must be field wired. Included with this drawing are 1) variable frequency drives on the blowers, 2) outdoor  
air and exhaust air dirty filter switches, 3) motorized outdoor air and exhaust air intake dampers, 4) electric  
preheater, and 5) timed exhaust frost control. Many other factory installed and wired accessories are available.  
Model PVe Heat Recovery Unit  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dirty Filter Sensor  
CO Sensor  
2
Dirty filter sensors monitor pressure drop across the  
outdoor air filters, exhaust air filters or both. If the  
pressure drop across the filters exceeds the set point,  
the sensor will close a set of contacts in the unit  
control center. Field wiring of a light (or other alarm)  
to these contacts will notify maintenance personnel  
when filters need to be replaced.  
This accessory is often used to provide a modulating  
control signal to a variable frequency drive to raise  
and lower airflow in relationship to the CO levels  
2
in the space. This strategy is often referred to as  
Demand Control Ventilation and provides further  
energy savings to the system. Follow instructions  
supplied with sensor for installation and wiring details.  
The switch has not been set at the factory due to  
external system losses that will affect the switch. This  
switch will need minor field adjustments after the unit  
has been installed with all ductwork complete. The  
dirty filter switch is mounted in the unit control center.  
Service Outlet  
120 VAC GFCI service outlet ships  
loose for field installation. Requires  
separate power source so power is  
available when unit main disconnect is  
turned off for servicing.  
To adjust the switch, the unit must be running with  
all of the access doors in place. The adjusting  
screw is located on the top of the switch. Open the  
filter compartment and place a sheet of plastic or  
cardboard over 50% of the filter media. Replace  
the filter compartment door. Check to see if there  
is power at the alert signal leads (refer to electrical  
diagram).  
Vapor Tight Lights  
Vapor tight lights provide light to each of the  
compartments in the energy  
recovery unit. The lights are wired  
to a junction box mounted on the  
outside of the unit. The switch to  
turn the lights on is located in the  
unit control center. The switch  
requires a separate power source  
to allow for power to the lights  
when the unit main disconnect is  
off for servicing.  
Whether there is power or not, turn the adjustment  
screw on the dirty filter gauge (clockwise if you did  
not have power, counterclockwise if you did have  
power) until the power comes on or just before the  
power goes off. Open the filter compartment and  
remove the obstructing material. Replace the door  
and check to make sure that you do not have power  
at the alert signal leads. The unit is now ready for  
operation.  
Setscrew (on front of switch) must  
be manually adjusted after the  
system is in operation.  
Negative pressure connection  
is toward the ‘front or top’ of  
the switch. (senses blower side  
of filters)  
Positive pressure connection is toward the ‘back or  
bottom’ of the switch. (senses air inlet side of filters)  
Model PVe Heat Recovery Unit  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Indicator Lights powered by the ER Unit  
Remote Control Panel and Wiring  
Schematics  
The remote panel is a series of junction boxes ganged  
together and includes a stainless steel faceplate. The  
remote panel is available with a number of different  
alarm lights and switches to control the unit. The  
remote panel ships loose and requires mounting and  
wiring in the field  
R
C
Unit On/Off  
G
Y1  
Y2  
W1  
Frost Control  
6
Economizer  
7
The remote panel is available with the following  
options:  
12  
• Unit on/off switch  
• Unit on/off light  
• 7-day time clock  
• Hand/off/auto switch  
• Time delay override  
• Economizer light  
PS2  
NC  
C
NO  
Supply Dirty Filter  
Exhaust Dirty Filter  
PS3  
NC  
C
NO  
• Frost control light  
• Exhaust air dirty filter light  
• Outdoor air dirty filter light  
Refer to Electrical Connections section for Field Control  
Wiring recommendations.  
Dirty Filter Indicator (power by others)  
7-Day Timer or On/Off Switch  
PS2  
Supply Dirty Filter  
Exhaust Dirty Filter  
NC  
C
NO  
7-Day Timer  
R
PS3  
Terminal Block  
NC  
C
NO  
C
G
in Unit  
Control Center  
S1 - Unit On/Off  
Hot  
L1  
Refer to Pressure Switch for voltage and load ratings.  
For 7-Day Timer, use blue and black wires.  
Red wires should be capped off.  
Hand/Off/Auto Switch  
R
Terminal Block  
C
G
in unit  
On  
Control Center  
Off  
Auto  
BMS  
Hand/Off/Auto Switch allows the unit to  
“Off” - off  
“On” - Manual Operation  
“Auto” - Unit is controlled by BMS, RTU, etc.  
NOTE: RTU controllers are by others.  
Model PVe Heat Recovery Unit  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sensors Mounted by Factory  
Factory mounted temperature, pressure, and current sensors are available in the locations indicated on the unit  
diagram below. A list of available sensors is shown below. The specific sensors provided on a given unit are  
labeled in the unit control center on the terminal strip. Sensors are wired to the terminal strip to make it easy for  
the controls contractor to connect the Building Management System for monitoring purposes.  
OAF-P  
EAP  
EF-A  
OAI  
OA  
FILTER  
FROM  
OUTSIDE  
TO  
OUTSIDE  
EXHAUST  
BLOWER  
PLATE  
HEAT  
RAF-P  
EXCHANGER  
RAI  
OAAP  
OAF-A  
RA  
FILTER  
FROM  
INSIDE  
TO  
INSIDE  
SUPPLY  
BLOWER  
OAD  
Temperature Sensors - 1K Ohm RTD  
Drawing  
Labels  
OAI  
Terminal Strip Labels  
OA/Supply Inlet Temp  
OA After Plate Temp  
OAAP  
RAI  
RA/Exhaust Inlet Temp  
Exhaust After Plate Temp  
Supply Discharge Temp  
EAP  
OAD  
Pressure Sensors (analog or digital)  
Drawing  
Labels  
OAF-P  
Terminal Strip Labels  
OA Supply Filter Pressure  
RA Exhaust Filter Pressure  
RAF-P  
EP-P  
(2 sensors)  
Exhaust Plate Pressure  
OAP-P  
(2 sensors)  
Outdoor Air Plate Pressure  
Amp - Current Sensors (analog or digital)  
Drawing  
Terminal Strip Labels  
Labels  
EF-A  
Exhaust Fan Amps  
Supply Fan Amps  
OAF-A  
Model PVe Heat Recovery Unit  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
o Rotate the fan wheels by hand and ensure no parts  
are rubbing. If rubbing occurs, refer to Start-Up  
section for more information.  
Start-Up  
DANGER  
o Check the fan belt drives for proper alignment  
and tension (refer to Start-Up section for more  
information).  
Electric shock hazard. Can cause injury or death.  
Before attempting to perform any service or  
maintenance, turn the electrical power to unit  
to OFF at disconnect switch(es). Unit may have  
multiple power supplies.  
o Filters can load up with dirt during building  
construction. Replace any dirty pleated filters and  
clean the aluminum mesh filters in the intake hood  
(refer to Routine Maintenance section).  
WARNING  
Use caution when removing access panels or other  
unit components, especially while standing on a  
ladder or other potentially unsteady base. Access  
panels and unit components can be heavy and  
serious injury may occur.  
o Verify that non-motorized dampers open and close  
properly.  
o Check the tightness of all factory wiring  
connections.  
o Verify control wire gauge (refer to the Electrical  
Do not operate energy recovery ventilator without  
the filters and birdscreens installed. They prevent  
the entry of foreign objects such as leaves, birds,  
etc.  
Connections section).  
o Install exhaust inlet motorized damper (see Unit  
Accessories section)  
SPECIAL TOOLS REQUIRED  
CAUTION  
Do not run unit during construction phase. Damage  
to internal components may result and void  
warranty.  
• Voltage Meter (with wire probes)  
• Amperage Meter  
• Thermometer  
Tachometer  
• Incline manometer or equivalent  
General Start-Up Information  
Every installation requires a comprehensive start-  
up to ensure proper operation of the unit. As part  
of that process, the following checklist must be  
completed and information recorded. Starting up  
the unit in accordance with this checklist will not  
only ensure proper operation, but will also provide  
valuable information to personnel performing future  
maintenance. Should an issue arise which requires  
factory assistance, this completed document  
will allow unit experts to provide quicker resolve.  
Qualified personnel should perform start-up to ensure  
safe and proper practices are followed.  
Start-Up Checklist  
The unit will be in operational mode during start-up.  
Use necessary precautions to avoid injury. All data  
must be collected while the unit is running. In order to  
measure volts & amps, the control center door must  
be open, and the unit energized using a crescent  
wrench to turn the disconnect handle.  
Check line voltage at unit disconnect  
_______ L1-L2 volts  
_______ L2-L3 volts  
_______ L1-L3 volts  
Motor Amp Draw  
Unit Model Number _______________________________  
• Supply Fan  
• Exhaust Fan  
(e.g. PVe-20)  
_______ L1 amps  
_______ L2 amps  
_______ L3 amps  
______ L1 amps  
______ L2 amps  
______ L3 amps  
Unit Serial Number _______________________________  
(e.g. 10111000)  
Start-Up Date  
_______________________________  
Fan RPM  
Start-Up Personnel Name__________________________  
Start-Up Company _______________________________  
_______ Supply Fan ______ Exhaust Fan  
Correct fan rotation direction  
Phone Number  
_______________________________  
Supply Fan  
Exhaust Fan  
Yes / No  
Yes / No  
Pre Start-Up Checklist – check as items are  
completed.  
o Disconnect and lock-out all power switches  
o Remove any foreign objects that are located in the  
energy recovery unit.  
o Check all fasteners, set-screws, and locking collars  
on the fans, bearings, drives, motor bases and  
accessories for tightness.  
Model PVe Heat Recovery Unit  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Optional Accessories Checklist  
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.  
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.  
Provided with Unit? Frost Control Application / Operation section:  
Setting  
Factory Default  
Yes  
Yes  
No  
No  
Frost Control set point  
Differential  
35ºF  
2ºF  
Timer  
Refer to IOM  
Refer to IOM  
Frost Control Modulating  
Economizer Application / Operation section:  
Yes  
No  
Economizer (temperature)  
Set point  
65ºF  
20ºF  
2ºF  
Offset  
Differential  
Yes  
No  
Economizer (enthalpy)  
Set point  
D
Optional Accessories section:  
Operational  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
OA Dirty Filter Sensor  
EA Dirty Filter Sensor  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
No  
No  
No  
No  
No  
No  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
CO Sensor  
2
Service Outlet  
Vapor Tight Lights  
Remote Control Panel  
Variable Frequency Drives section:  
Operational  
Yes  
No  
Blower VFDs  
Yes  
No  
N/A  
Damper section:  
Operational  
Yes  
Yes  
No  
No  
Outdoor Air Damper  
Exhaust Air Damper  
Yes  
Yes  
No  
No  
N/A  
N/A  
Model PVe Heat Recovery Unit  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Place belts over sheaves. Do not pry or force  
belts, as this could result in damage to the cords  
in the belts.  
Unit Start-Up  
Refer to Parts List section for component locations.  
Fans  
6. With the fan off, adjust the belt tension by moving  
the motor base. (See belt tensioning procedures in  
the Routine Maintenance section of this manual).  
When in operation, the tight side of the belts  
should be in a straight line from sheave to sheave  
with a slight bow on the slack side.  
The PVe models contain two  
forward curved (supply &  
exhaust) fans. These forward  
curved fans should be checked  
for free rotation. If any binding  
occurs, check for concealed  
damage and foreign objects  
in the fan housing. Be sure to  
check the belt drives per the  
start-up recommendations in  
the following section.  
Forward Curved  
Exhaust Fan  
WRONG  
WRONG  
WRONG  
CORRECT  
CAUTION  
Direction of Fan Wheel Rotation  
When operating conditions of the fan are to be  
changed (speed, pressure, temperature, etc.),  
consult Greenheck to determine if the unit can  
operate safely at the new conditions.  
Blower access is labeled on unit. Check for proper  
wheel rotation by momentarily energizing the fan.  
Rotation is determined by viewing the wheel from the  
drive side and should match the rotation decal affixed  
to the fan housing (see Rotation Direction figures).  
If the wheel is rotating the wrong way, direction can  
be reversed by interchanging any two of the three  
electrical leads. Check for unusual noise, vibration, or  
overheating of bearings. Refer to the Troubleshooting  
section of this manual if a problem develops.  
Fan Performance Modifications  
Due to job specification revisions, it may be  
necessary to adjust or change the sheave or pulley to  
obtain the desired airflow at the time of installation.  
Start-up technician must check blower amperage  
to ensure that the amperage listed on the motor  
nameplate is not exceeded. Amperage to be tested  
with access doors closed and ductwork installed.  
Airflow  
Fan Belt Drives  
The fan belt drive components, when supplied by  
Greenheck, have been carefully selected for the  
unit’s specific operating condition. Utilizing different  
components than those supplied could result in  
unsafe operating conditions which may cause  
personal injury or failure of the following components:  
Forward Curved  
Fan RPM  
Supply fan and exhaust fan will have an adjustable  
motor pulley (on 15 HP and below) preset at the  
factory to the customer specified RPM. Fan speed  
can be increased or decreased by adjusting the pitch  
diameter of the motor pulley. Multigroove variable  
pitch pulleys must be adjusted an equal number  
of turns open or closed. Any increase in fan speed  
represents a substantial increase in load on the  
motor. Always check the motor amperage reading  
and compare it to the amperage rating shown on the  
motor nameplate when changing fan RPM. All access  
doors must be installed except the control center  
door. Do not operate units with access doors open or  
without proper ductwork in place as the fan motors  
will overload.  
• Fan Shaft  
• Fan Wheel  
• Bearings  
• Belt  
• Motor  
Tighten all fasteners and set screws securely and  
realign drive pulleys after adjustment. Check pulleys  
and belts for proper alignment to avoid unnecessary  
belt wear, noise, vibration and power loss. Motor and  
drive shafts must be parallel and pulleys in line (see  
diagrams in this section).  
Belt Drive Installation  
1. Remove the protective coating from the end of  
the fan shaft and assure that it is free of nicks and  
burrs.  
2. Check fan and motor shafts for  
parallel and angular alignment.  
3. Slide sheaves on shafts. Do not  
drive sheaves on as this may  
result in bearing damage.  
4. Align fan and motor sheaves  
with a straight-edge or  
string and tighten.  
Model PVe Heat Recovery Unit  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Vibration  
Excessive vibration may be experienced during initial  
start-up. Left unchecked, excessive vibration can  
cause a multitude of problems, including structural  
and/or component failure. The most common sources  
of vibration are listed.  
Many of these conditions can be discovered by  
careful observation.  
Wheel Unbalance  
Refer to the  
Drive Pulley Misalignment  
Incorrect Belt Tension  
Bearing Misalignment  
Mechanical Looseness  
Faulty Belts  
Drive Component Unbalance  
Poor Inlet/Outlet Conditions  
Foundation Stiffness  
Troubleshooting  
section of this manual  
for corrective actions.  
If observation cannot  
locate the source of  
vibration, a qualified  
technician using  
vibration analysis  
equipment should be consulted. If the problem is  
wheel unbalance, in-place balancing can be done.  
Generally, fan vibration and noise is transmitted  
to other parts of the building by the ductwork. To  
eliminate this undesirable effect, the use of heavy  
canvas connectors is recommended.  
Model PVe Heat Recovery Unit  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Overview  
The Greenheck PVe Heat Recovery Ventilator is quite  
simply an interface unit that takes in outdoor air and  
either heats or cools that air and then delivers that air  
into the building HVAC system for further heating or  
cooling. The heating and cooling that is done in this  
unit is accomplished by taking heat energy out of the  
air being exhausted to the outdoors and transferring  
that heat energy to the incoming replacement air. If  
the outdoor air is being used for cooling, some of the  
heat energy is transferred from the incoming warm  
outdoor air to the exhaust air.  
Most all the components found in this unit are typical  
of what would normally be found in other air handlers.  
There is an air propulsion system consisting of  
two belt driven blowers; one to draw in outdoor air  
through the Plate Heat Exchanger, and the other to  
draw stale indoor air from the building through the  
Plate Heat Exchanger and then exhaust it. There are  
various optional motorized dampers and sensors that  
may also be found in the unit.  
The heart of the PVe unit is the Plate Heat Exchanger  
and this is the component that actually accomplishes  
heat energy recovery. It has no moving parts and the  
only real maintenance issues are to keep the internal  
surfaces clean and to protect the aluminum plates  
from damage.  
In addition to the typical maintenance issues shown  
in following pages, periodic visual inspection of  
the Plate Heat Exchanger is required. Such visual  
inspections should be recorded and record made of  
any observations.  
The surfaces of the flat aluminum plates within  
the Plate Heat Exchanger permit complete visual  
inspection of both supply and exhaust sides of the  
unit. Small amounts of dust present in either side of  
the Plate Heat Exchanger will not affect performance.  
If appreciable amounts of dust or dirt accumulate,  
the Plate Heat Exchanger can be cleaned with hot  
water (180ºF) or a detergent that does not damage  
aluminum surfaces. Spray water evenly across the  
surfaces at a pressure between 22 and 55 psig. Do  
not force sharp objects against the heat transfer  
surfaces or damage to the flat plates may occur.  
Model PVe Heat Recovery Unit  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fan Belts  
Routine Maintenance  
Belts must be checked on a regular basis for  
wear, tension, alignment, and dirt accumulation.  
Premature or frequent belt failures can be caused by  
improper belt tension (either too loose or too tight)  
or misaligned sheaves. Abnormally high belt tension  
or drive misalignment will cause excessive bearing  
loads and may result in failure of the fan and/or motor  
bearings. Conversely, loose belts will cause squealing  
on start-up, excessive belt flutter, slippage, and  
overheated sheaves. Both loose and tight belts can  
cause fan vibration.  
DANGER  
Electric shock hazard. Can cause injury or death.  
Before attempting to perform any service or  
maintenance, turn the electrical power to unit  
to OFF at disconnect switch(es). Unit may have  
multiple power supplies.  
CAUTION  
Use caution when removing access panels or other  
unit components, especially while standing on a  
ladder or other potentially unsteady base. Access  
panels and unit components can be heavy and  
serious injury may occur.  
When replacing belts on multiple groove drives, all  
belts should be changed to provide uniform drive  
loading. Do not pry belts on or off the sheave. Loosen  
belt tension until belts can be removed by simply  
lifting the belts off the sheaves. After replacing belts,  
insure that slack in each belt is on the same side of  
the drive. Belt dressing should never be used.  
Once the unit has been put into operation, a routine  
maintenance program should be set up to preserve  
reliability and performance. Items to be included in  
this program are:  
Do not install new belts on worn sheaves. If the  
sheaves have grooves worn in them, they must be  
replaced before new belts are installed.  
Lubrication  
Apply lubrication where required  
Dampers  
The proper belt setting is the lowest tension at which  
the belts will not slip under peak load operation. For  
initial tensioning, set the belt deflection at 1/64-inch  
for each inch of belt span (measured halfway between  
sheave centers). For example, if the belt span is  
64 inches, the belt deflection should be one inch  
Check for unobstructed operation  
Fan Belts  
Check for wear, tension, alignment  
Motors  
Check for cleanliness  
(using moderate thumb  
pressure at mid-point  
of the drive). Check  
belt tension two times  
during the first 24 hours  
of operation and  
Belt Span  
Blower Wheel & Fasteners  
Check for cleanliness  
Deflection =  
64  
Check all fasteners for tightness  
Check for fatigue, corrosion, wear  
Bearings  
Check for cleanliness  
Check set screws for tightness  
Lubricate as required  
periodically thereafter.  
Belt Span  
Fan Motors  
External Filter  
Motor maintenance is generally limited to cleaning  
and lubrication. Cleaning should be limited to exterior  
surfaces only. Removing dust and grease buildup  
on the motor housing assists proper motor cooling.  
Never wash-down motor  
Check for cleanliness - clean if required  
Internal Filter  
Check for cleanliness - replace if required  
Door Seal  
with high pressure spray.  
Greasing of motors is  
Check if intact and pliable  
only intended when  
fittings are provided.  
Many fractional motors  
are permanently  
lubricated for life and  
require no further  
lubrication.  
Maintenance Procedures:  
Lubrication  
Check all moving components for proper lubrication.  
Apply lubrication where required. Any components  
showing excessive wear should be replaced to  
maintain the integrity of the unit and ensure proper  
operation.  
Dampers  
Check all dampers to ensure they open and close  
properly and without binding. Backdraft dampers can  
be checked by hand to determine if blades open and  
close freely. Apply power to motorized dampers to  
ensure the actuator opens and closes the damper as  
designed.  
Model PVe Heat Recovery Unit  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fan Wheel & Fasteners  
Filter Size and Quantities  
Pleated Filter Size  
Wheels require very little attention when moving clean  
air. Occasionally oil and dust may accumulate on the  
wheel causing imbalance. When this occurs the wheel  
and housing should be cleaned to assure smooth and  
safe operation. Inspect fan impeller and housing for  
fatigue, corrosion or wear.  
Quantity  
Supply Exhaust  
Unit Size  
Supply and Exhaust  
12 x 25 x 2  
PVe-20  
PVe-35  
PVe-45  
PVe-55  
3
3
3
3
3
3
3
3
16 x 25 x 2  
20 x 25 x 2  
Routinely check all fasteners, set screws and locking  
collars on the fan, bearings, drive, motor base and  
accessories for tightness. A proper maintenance  
program will help preserve the performance and  
reliability designed into the fan.  
24 x 24 x 2  
All dimensions in inches.  
Outdoor Air Filters: Access to the outdoor air filters  
is through the door labeled as “Filter Access” on the  
outdoor air side of the unit.  
Bearings  
Exhaust Air Filters: Access to the exhaust air filters  
is through the door labeled as “Filter Access” on the  
exhaust air side of the unit.  
Most bearings are permanently lubricated and require  
no further lubrication under normal use. Normal use  
being considered -20ºF to 120ºF and in a relatively  
clean environment. Some bearings are relubricatable  
and will need to be regreased depending on fan use.  
Check your bearings for grease zerk fittings to find  
out what type of bearing you have. If your fan is not  
being operated under normal use, bearings should be  
checked monthly for lubrication.  
Refer to Access Door Descriptions section for  
additional information on filter locations.  
Door Seal Maintenance  
Slip-on type seal is installed on the door. Inspect at  
least annually to ensure that seal is still pliable and  
intact.  
External Filter Maintenance  
Aluminum mesh, 2-inch deep filters are located in the  
supply weatherhood (if the weatherhood option was  
purchased). Filters should be checked and cleaned  
on a regular basis for best efficiency. The frequency  
of cleaning depends upon the cleanliness of the  
incoming air. These filters should be cleaned prior to  
start-up.  
Clean filters by rinsing with a mild detergent in warm  
water.  
Internal Filter Maintenance  
The PVe units are always provided with 2-inch,  
pleated filters in the outdoor air and exhaust  
airstreams. These filters should be checked per  
a routine maintenance schedule and replaced as  
necessary to ensure proper airflow through the  
unit. See table for pleated filter size and quantity  
for each unit. Replacement filters shall be of same  
performance and quality as factory installed filters.  
Filter type must be pleated design with integral metal  
grid. Two acceptable filter replacements are Aerostar  
®
Series 400 or Farr 30/30 .  
Model PVe Heat Recovery Unit  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Parts List  
Sequence of Operation  
Basic Unit  
The PVe units are prewired such that when a call for  
outside air is made (via field supplied 24 VAC control  
signal wired to unit control center), the supply and  
exhaust fan are energized and optional motorized  
dampers open. The PVe is normally slaved (24 volt) to  
the roof top air handler. When the roof top air handler  
starts, the auxiliary contactor in the air handler closes  
to start the PVe.  
4
5
8
6
3
1
Summer Operation  
Outdoor air is preconditioned (temperature is  
decreased) by the transfer of energy from the cooler,  
drier, exhaust air via the aluminum heat exchanger.  
The preconditioned air is typically mixed with return  
air going back to the air handler for final conditioning.  
2
1. Supply blower  
Economizer Operation: Refer to Economizer  
Application/Operation section.  
• Forward curved fan  
• Adjustable motor mount for belt tensioning  
• Adjustable sheaves for speed control  
Winter Operation  
Outdoor air is preconditioned (temperature is  
increased) by the transfer of energy from the warmer,  
more humid exhaust air via the aluminum heat  
exchanger. The preconditioned air is typically mixed  
with return air going back to the air handler for final  
conditioning.  
2. Vibration isolators (quantity 4 per blower)  
• Neoprene  
3. Aluminum plate heat exchanger  
4. Supply weatherhood with 2-inch aluminum mesh  
filter  
Frost Control Operation: Refer to Frost Control  
Application/Operation section.  
5. Exhaust weatherhood with birdscreen  
6. Supply and exhaust air filter racks for  
2-inch pleated, 30% efficient filters  
Other Accessories:  
Dirty Filter Sensor: Refer to Optional Accessories  
section  
7. Electrical control box (standard features)  
• Single point power  
CO Sensor: Refer to Optional Accessories section  
2
• Disconnect interlocked with access door  
• Motor starters for the supply and exhaust  
blower  
VFD on Blowers: VFDs on blowers are often used  
as part of a demand control ventilation system. This  
type of system takes advantage of varying occupancy  
through the use of CO sensors to monitor space CO  
• 24 VAC, control circuit with terminal strip  
Not depicted on this image  
2
2
levels. If CO levels are low in the space, the VFD will  
2
8. Exhaust blower  
operate the blowers at minimum airflow required by  
• Forward curved fan  
• Adjustable motor mount for belt tensioning  
• Adjustable sheaves for speed control  
code. As the space occupancy increases and CO  
levels increase, the VFD will increase the amount  
of fresh outdoor air being brought in to offset the  
2
CO levels in the space (exhaust airflow is increased  
2
proportionally as outdoor airflow increases). As CO  
levels come back down, the airflow will decrease  
back to minimum requirements.  
2
Model PVe Heat Recovery Unit  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting – Airflow  
Test and Balance Report  
The Test and Balance Report (TAB) is utilized to determine whether the appropriate amount of outdoor air  
and exhaust air is being supplied and removed from a building, respectively. There are no set rules on what  
information must be included in a TAB report. As such, if a TAB report indicates that the airflow on a unit is low,  
prior to contacting the factory, please determine the following information:  
Unit #1  
Unit #2  
Unit #3  
Unit #4  
Model Number  
Serial Number  
Nameplate Information  
Voltage  
Hertz  
Phase  
Outdoor Air Fan Amps  
Exhaust Fan Amps  
Outdoor Air Fan Horsepower  
Exhaust Fan Horsepower  
Design Airflow  
Outdoor Air  
Exhaust  
Measured Airflow  
Outdoor Air  
Exhaust  
Measured Data  
Blower Rotation  
Outdoor Air Fan RPM  
Exhaust Fan RPM  
Outdoor Air Fan Amp Draw  
Exhaust Fan Amp Draw  
Airflow problems can often be tied back to improper ductwork installation. Be sure to install ductwork in  
accordance with SMACNA and AMCA guidelines.  
Model PVe Heat Recovery Unit  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting – Unit  
Symptom  
Possible Cause  
Corrective Action  
Replace fuse or reset circuit breaker and check  
amps.  
Blown fuse or open circuit breaker.  
Defective motor or capacitor.  
Motor starter overloaded.  
Replace.  
Blower fails to  
Reset starter and check amps.  
operate  
Check for On/Off switches. Check for correct  
supply voltage.  
Electrical.  
Drive.  
Check for broken or loose belts. Tighten loose  
pulleys.  
Shorten wiring run to mechanical room or  
install a relay which will turn unit on/off. Consult  
Factory for relay information.  
Control power (24 VAC) wiring run is too long  
(resistance should not exceed 0.75 ohms).  
Motor starters  
“chatter” or  
do not pull in  
Incoming supply power is less than anticipated.  
Voltage supplied to starter coil must be within  
Need to increase supply power or use a special  
control transformer which is sized for the actual  
+10% / -15% of nominal voltage stated on the coil. supply power.  
CFM too high.  
Check cfm and adjust drives if needed.  
Static pressures are higher or lower than  
design.  
If higher, ductwork should be improved.  
If lower, fan rpm should be lower.  
Blower rotation is incorrect.  
Motor voltage incorrect.  
Check rotation and reverse if necessary.  
Motor over amps  
Check motor nameplate versus supplied  
voltage.  
See specifications and catalog for fan curves to  
determine if horsepower is sufficient.  
Motor horsepower too low.  
Shorted windings in motor.  
Unit damper not fully open.  
Replace motor.  
Adjust damper linkage or replace damper motor.  
Improve ductwork to eliminate losses using  
good duct practices.  
System static pressure too high.  
Blower speed too low.  
Check for correct drives and rpm with catalog  
data.  
For 3-phase, see Direction of Fan Wheel  
Rotation under Unit Start-Up section.  
Fan wheels are operating backwards.  
Low airflow (cfm)  
Follow cleaning procedures in Routine  
Maintenance section.  
Dirty filter.  
Leaks in ductwork.  
Repair.  
Elbows or other obstructions may be  
obstructing fan outlet.  
Correct or improve ductwork.  
Adjust belt tension.  
Belt slippage.  
Check for correct fan rpm. Decrease fan speed  
if necessary.  
Blower fan speed too high.  
Filter(s) not in place.  
Install filters.  
High airflow (cfm)  
Induce Ps into system ductwork. Make sure  
grilles and access doors are installed. Decrease  
fan speed if necessary.  
Insufficient static pressure (Ps) (airflow  
resistance).  
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or  
service information.  
Model PVe Heat Recovery Unit  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting – Unit  
Symptom  
Possible Cause  
Corrective Action  
One or both  
blowers turn off  
intermittently and  
back on after  
Adjust frost temperature sensor set point as  
needed.  
Exhaust Only frost control sensors are tripping.  
about 2 minutes  
Adjust wheel and/or inlet cone. Tighten wheel  
hub or bearing collars on shaft.  
Fan wheel rubbing on inlet.  
Bearings.  
Replace defective bearing(s). Lubricate  
bearings. Tighten collars and fasteners.  
Wheel out of balance.  
Loose wheel on shaft.  
Loose motor or blower sheave.  
Belts too loose.  
Replace or rebalance.  
Tighten wheel setscrew.  
Tighten sheave setscrew.  
Adjust belt tension after 24 hours of operation.  
Excessive noise  
or vibration  
Loosen to maintain a 3/8 inch deflection per  
foot of span between sheaves.  
Belts too tight.  
Worn belt.  
Replace.  
Motor base or blower loose.  
Buildup of material on wheel.  
Bearing and drive misaligned.  
Tighten mounting bolts.  
Clean wheel and housing.  
Realign.  
Make sure ductwork is supported properly.  
Make sure ductwork metal thickness is sized for  
proper stiffness. Check duct size at discharge to  
ensure that air velocities are not too high.  
Noise being transmitted by duct.  
Always have a completed Pre Start-Up Checklist, unit Start-Up Checklist, and Optional Accessories Checklist prior to requesting parts or  
service information.  
Model PVe Heat Recovery Unit  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Log  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Model PVe Heat Recovery Unit  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Log  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Model PVe Heat Recovery Unit  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Log  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Model PVe Heat Recovery Unit  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from  
the shipment date. Any units or parts which prove defective during the warranty period will be replaced at our option  
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of  
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the  
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications  
without notice.  
Greenheck Catalog Heat Recovery Ventilator, Model PVe,  
provides additional information describing the equipment,  
fan performance, available accessories, and specification  
data.  
AMCA Publication 410-96, Safety Practices for Users and  
Installers of Industrial and Commercial Fans, provides  
additional safety information. This publication can be  
®
472846 • Model PVe IOM, Rev. 1, October 2009  
Copyright 2009 © Greenheck Fan Corp.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graham Field Camping Equipment AQ1000 AQ2000 User Manual
Haier Satellite TV System L32A9 AK User Manual
Hans Grohe Outdoor Shower 16320XX1 User Manual
Heath Zenith Work Light 52 4473 6 User Manual
Heath Zenith Work Light HD 5677 User Manual
Honeywell Thermostat TZ 4 User Manual
HP Hewlett Packard Computer Accessories 589256 B21 User Manual
HP Hewlett Packard Network Router Wireless Device User Manual
HP Hewlett Packard Oven 45WDG PLUS User Manual
HP Hewlett Packard Power Supply 6621A User Manual