Greenheck Fan Ventilation Hood PN 458294 User Manual

PN 458294  
Model Proximity (Backshelf)  
Kitchen Hoods  
®
Installation, Operation and Maintenance Manual  
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the  
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions  
could result in personal injury and/or property damage! Retain instructions for future reference.  
Please record the Serial, Model #, and Mark for the hood and other equipment for future reference.  
Serial #: _______________________  
Serial #: _______________________  
Serial #: _______________________  
Serial #: _______________________  
Serial #: _______________________  
Serial #: _______________________  
Serial #: _______________________  
Serial #: _______________________  
Model #: ______________________  
Model #: ______________________  
Model #: ______________________  
Model #: ______________________  
Model #: ______________________  
Model #: ______________________  
Model #: ______________________  
Model #: ______________________  
Mark: _________________  
Mark: _________________  
Mark: _________________  
Mark: _________________  
Mark: _________________  
Mark: _________________  
Mark: _________________  
Mark: _________________  
Proximity Hood  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Receiving and Handling  
Upon receiving the equipment, check for both obvious and hidden damage. If damage is found, record all  
necessary information on the bill of lading and file a claim with the final carrier. Check to be sure that all parts of  
the shipment, including accessories, are accounted for.  
STORAGE  
If a kitchen hood must be stored prior to installation it must be protected from dirt and moisture. Indoor storage  
is recommended. For outdoor storage, cover the hood with a tarp to keep it clean, dry, and protected from UV  
(Ultra Violet) Radiation damage.  
Improper storage which results in damage to the unit will void the warranty.  
Hood Weights  
Hood weight is determined using a simple formula. Select the figures provided in columns A and B (see tables)  
from the three respective categories—Hood Width, Filter Type and Hood Height—based on the hood received.  
Total the three numbers in column A and the three numbers in column B. Place the sum for column A and the  
sum for column B in the Hood Weight equation where shown and solve for the total Hood Weight.  
IMPERIAL  
Category 1:  
A
B
Hood Width (in.)  
Example:  
A
B
28  
0
23 - 25  
26 - 28  
29 - 32  
33 - 36  
1.3  
1.35  
1.4  
28  
30  
31.5  
33.5  
Category 1: Hood Width  
Category 2: Filter Type  
Category 3: Hood Height  
23 - 25  
Baffle  
24 - 27  
Total:  
1.3  
0.3  
0
0
1.45  
1.6  
28  
Category 2:  
Baffle  
GX or Cartridge  
Grease Grabber™  
Category 3:  
24 - 27  
Filter Type  
0.3  
0
0
0
0.4  
1
Hood Weight Equation (lb.)  
Hood Height (in.)  
0
0
5
10  
15  
A
x
x
Length (in.)  
48  
+
+
B
=
Weight (lb.)  
104.8 lb.  
28 - 33  
34 - 38  
39 - 42  
0.08  
0.16  
0.24  
1.6  
28  
=
METRIC  
A
B
Category 1:  
Hood Width (cm)  
Example:  
A
B
12.68  
0
58.42 - 63.50  
66.04 - 71.12  
73.66 - 81.28  
83.82 - 91.44  
0.232  
0.241  
0.250  
0.259  
12.68  
13.59  
14.27  
15.18  
Category 1: Hood Width  
Category 2: Filter Type  
58.42 - 63.50 0.232  
Baffle  
0.054  
0
Category 3: Hood Height 60.96 - 68.58  
0
Total:  
1.6  
28  
Category 2:  
Filter Type  
Baffle  
GX or Cartridge  
Grease Grabber™  
0.054  
0.071  
0.178  
0
0
0
Hood Weight Equation (kg.)  
Category 3:  
60.96 - 68.58  
71.12 - 83.82  
Hood Height (cm)  
0.000  
0.014  
0.029  
0.043  
0
A
x Length (cm.) +  
121.92  
B
=
=
Weight (kg.)  
47.5 kg.  
2.27  
4.53  
6.80  
0.286  
x
+
12.68  
86.36 - 96.52  
99.06 - 106.68  
Proximity Hood  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
NOTE: If you have a Back Supply  
Plenum, this must be installed before  
the hood. Please see page 8 now.  
Fig. 1  
Prior to installation, check with local  
authorities having jurisdiction on  
clearances to combustible surfaces.  
With the hood still inside its packing  
crate, position the unit beneath its  
installation location.  
Carefully remove the packing crate.  
Place some protective material on  
the floor next to the crate to avoid  
damaging the hood as it is tipped on its side (Fig. 1). Tip the hood carefully onto the protective  
material. If you have filler panels, see Fig. 2 below. If you have integral filler panels, no additional  
installation is needed.  
Hood Installation Overview  
If a Back Supply Plenum is provided, install first. Before raising hood, insert 1/2 in. (12.7 mm) diameter  
threaded rod (by others) into hanger brackets on hood top. Check the engineering drawings or UL  
label located on the inside of the hood for proper hood height above finished floor. Install filler panels  
if needed. Raise and hang hood from adequate roof or ceiling supports and secure mounting flange  
to the wall using lag bolts, or fasten to the Back Supply Plenum if provided. All hanger brackets must  
be used and the hood must be properly supported while lifting to prevent damage or distortion to the  
hood. The hood must be hung level to operate properly. After hood is secured, make the exhaust duct  
connections. The fire system distributer must be contacted at this time. After the fire system has been  
installed, mount the enclosures, then the supply plenums. If a Horizontal Supply Plenum is provided, it  
should be installed according to the external supply plenum installation section found on page 7. The  
hood and accessories are now installed. Finally, make the electrical connections from switches to fans  
and complete the fire system circuits as required by the job specification.  
Rear Filler Panel Installation Instructions  
Rear filler panels may be shipped loose for field  
installaton or are integral to the hood. If fillers are  
Hood Front  
integral to hood, skip this section.  
1. Uncrate the hood and lay it on the floor with  
protective material between the hood and the floor.  
Hood Top  
2. Bolt the filler panels together with 5/16 in. bolts  
from the hardware package.  
Hood Back  
Backshelf  
3. Position the filler panels on the hood, and tack-  
weld them to the hood back.  
4. To allow for ease of cleaning, caulk the external  
Bottom Filler Panel  
seams with NSF Approved silicone caulk  
(GE SCS1009, or its equivalent). The caulk is  
not provided.  
Fig. 2  
5/16 x 3/4 in. (8 x 19 mm)  
Bolts with Washers and Nuts  
Hood Front  
Proximity Hood  
4
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
End Filler Panel Installation Instructions  
End filler panels may be shipped loose for field installaton or are facory mounted to the hood. If fillers  
are factory mounted to hood, skip this section.  
1. Uncrate the hood and lay it on the floor with protective material between the hood and the floor.  
2. Bolt the filler panels together with 5/16 in. bolts from the hardware package.  
3. Position the filler panels on the  
hood and tack-weld them to the  
appropriate side of the hood.  
4. To allow for ease of cleaning,  
caulk the external seams with  
NSF Approved silicone caulk  
(GE SCS1009, or its equivalent).  
The caulk is not provided.  
Note: Hood may be furnished with  
finished end fillers when mounting  
against a partial wall.  
End Filler Panels  
Fig. 3  
Hood Hanging Height  
The hood hanging height is critical, hanging the hood at the  
incorrect height may significantly reduce the ability for the  
hood to function properly and may be in violation of codes.  
The hood hanging height is given on the UL label located  
on the inside of the hood on the end panel. The distance  
given is from the front lip of the hood (shown in Fig. 4) to  
the surface of the cooking equipment.  
UL Vertical Distance  
Above Cooking Surface  
Fig. 4  
Continuous Capture Plenum Hoods  
Use the installation procedure described on  
page 4 for single island hoods; install and  
level both hoods. After leveling, secure the  
hoods together. Fasten the hoods together  
using u-clips and bolts. (Fig. 6) Caulk this  
joint with NSF Approved silicone caulk (GE  
SCS1009 or its equivalent). The caulk is not  
provided.  
Fig. 5  
HOOD  
CAULK  
BOLT  
ACORN NUT  
U-CLIP  
Fig. 6  
Proximity Hood  
5
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ductwork  
Exhaust  
As specified in NFPA 96, Ch. 7.5 (latest edition), exhaust duct systems must be constructed in the  
following manner:  
Materials. Ducts shall be constructed of and supported by carbon steel not less than 1.37 mm  
(0.054 in.) (No. 16 MSG) in thickness or stainless steel not less than 1.09 mm (0.043 in.) (No. 18 MSG) in  
thickness.  
Installation. All seams, joints, penetrations, and duct-to-hood collar connections shall have a  
liquid-tight continuous external weld.  
Supply  
Supply ductwork (where applicable) should be connected to the hood in a manner approved by the  
local code authorities.  
Note: For hoods with fire dampers in the exhaust and supply duct collars, an access panel for cleaning  
and inspection shall be provided in the duct. This panel shall be as close to the hood as possible but  
should not exceed 18 in. (45.72 cm).  
For proper installation of duct collars when they are shipped unattached, see page 14  
Electrical Connections  
Access for wiring the hood control panel (when applicable) is provided by a junction box located on  
top of the hood when the control panel is mounted in the hood, or by the switch junction box when the  
control panel is mounted in the fire protection cabinet. The box is labeled “Control Voltage Wiring to  
Roof Top Fan Package”. Use minimum 14 AWG copper wire.  
Standard light switches for remote mounting are rated for 15 amps and shall not have more than 14  
lights connected to them. Higher amperage switches are available upon special request.  
External Supply Plenum Weights, Dimensions, and Supply Rates  
Length per  
Weight  
Width  
(mm)  
Height  
(in) (mm)  
section  
External Supply  
Plenum Type  
Recommended  
Supply Rate  
(lbs/ft)  
(kg/ft)  
(in)  
(ft)  
(m)  
.91 to  
4.88  
145 cfm/ft  
35.0  
9.5  
15.878  
6
152.4  
355.6  
Variable Variable  
3 to 16  
Back Supply  
(246.36 m3/hr)  
Air CurtainSupply  
• 14 inch  
.91 to  
4.88  
110 cfm/ft  
4.31  
14  
10  
254  
3 to 16  
(186.89 m3/hr)  
Air Curtain Supply  
• 24 inch  
.91 to  
4.88  
145 cfm/ft  
12.5  
16.0  
14.0  
5.67  
7.26  
6.35  
24  
12  
12  
609.6  
304.8  
304.8  
10  
18  
18  
254  
3 to 16  
3 to 16  
3 to 16  
(246.36 m3/hr)  
.91 to  
4.88  
80-160 cfm/ft  
457.20  
457.20  
face  
Variable Supply  
(135.92 -271.84 m3/hr)  
.91 to  
4.88  
150 cfm/ft  
Horizontal Supply  
(254.85 m3/hr)  
Proximity Hood  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
External Supply Plenum Installation  
The purpose of the external supply plenum is to provide make-up air to an exhaust hood to maintain  
the air balance in the space. The external supply plenum must be hung independent of the hood.  
Follow the instructions for hanging the following supply plenums: Horizontal, Air Curtain and Variable.  
See page 8 for Back Supply Plenum. If an external supply plenum is not provided, skip this section.  
Installation Instructions  
Support plenum from all  
hangers provided  
1. If duct collar(s) is shipped loose,  
place the duct collar(s) over the  
opening, fastening with tack-  
welds at 1 to 2 in. (2.54 to 5.08 cm)  
intervals, or sheet metal screws  
at 3 to 6 in. (7.62 to 15.24 cm)  
intervals.  
2. Insert 1/2 in. (12.7 mm) diameter  
threaded rod (by others) into all  
of the hanger brackets on the  
supply plenum top. Raise external  
Fig. 7  
supply plenum and hang level from  
adequate roof or ceiling supports.  
(Horizontal Supply Plenum shown  
in Fig. 7, must be below finished  
ceiling. Air Curtain Supply Plenum  
Bolt back of  
plenum to  
may be fit into drop ceiling.)  
enclosures  
3. Remove perforated panel from  
plenum and bolt to enclosures  
through back of plenum (Fig. 8).  
This will draw plenum tight to the  
enclosures. Fasteners are not  
intended to support the plenum;  
for alignment purposes only.  
Fig. 8  
4. Caulk mating joints with  
NSF Approved silicone caulk  
(GE SCS1009, or its equivalent).  
The caulk is not provided.  
Proximity Hood  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installing the Back Supply Plenum  
Installing the Supply Duct Collar  
L (MODULE WIDTH)  
1. Find the center of the Back Supply Plenum.  
2. If the Back Supply Plenum is less than 9 ft. 10 in. (299.72 cm) long,  
cut opening at the suggested location, centering the opening over  
the center of the Back Supply Plenum. (Fig. 9)  
L/2  
L/2  
3. If the Back Supply Plenum is greater than 9 ft. 10 in. (299.72 cm)  
long, divide the length of the back supply by four. This will give you  
the center of each half. Cut openings at the suggested location,  
centering the duct collar over the center measurement of each  
half. (Fig. 10)  
4. Place the duct collar(s) over the opening, fastening with screws or  
tack-welds every 4 to 6 in. (10.16 to 15.24 cm). (Fig. 11)  
Fig. 9  
• The 4 in. (10.16 cm)  
high duct collar is to be  
attached to the back  
L (MODULE WIDTH)  
L/4  
supply.  
L/2  
L/2  
Fig. 10  
Fig. 11  
Hanging the Back Supply Plenum  
5. Hang the Back Supply Plenum from the ceiling.  
The Back Supply Plenum needs to be mounted 31.25 in.  
(79.375 cm) above the finished floor. This is measured  
from the lowest rear edge of the Back Supply Plenum to  
the finished floor.  
6. Fasten the Back Supply to the wall, going through the  
lower Back Supply wall. (Fig. 12)  
These fasteners are to help maintain the location of  
the Back Supply and are not intended to hold the  
weight of the Back Supply Unit.  
FASTENERS HOLDING THE  
BACK SUPPLY TO THE WALL  
The fasteners should not interfere with the removable  
air diffusers.  
32 in. (813 mm)  
CRITICAL  
DIMENSION  
Fig. 12  
Proximity Hood  
8
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hanging the Hood with Back Supply Plenum  
Before hanging the hood according to the hood  
installation instructions, please check the following:  
1. Make sure the back supply unit is properly  
secured, as described in steps 5 and 6, page 8.  
2. Any filler panels should be attached to the hood  
before the hood installation.  
To hang the hood:  
1. Lift the hood and position it so the top of the  
hood is even with the back supply (Fig. 13). This  
height should correspond to the UL hanging  
height of the hood.  
2. After the hood is hung from the ceiling, a hood  
mounting flange may be fastened to the back  
supply using sheet metal screws (by others).  
Pilot holes are recommended.  
3. Connect the remaining ductwork for the back  
supply and the hood. Caulk all mating seams  
and surfaces of the back supply, the hood, and  
the wall.  
Fig. 13  
Hood Mounting Instructions  
Fig. 14 shows the locations where the  
hood must be fastened. If a Back Supply  
Plenum is part of the hood system,  
please see pages 8-9, Back Supply  
Plenum/Hood Installation.  
Mounting Flange  
To hang the hood:  
1) Locate the studs in the wall.  
2) Drill 1/2 in. (13 mm) diameter holes in  
the hood mouting flange. Be sure to  
align to wall studs.  
3) Lift hood into a level position and  
lag bolt hood to wall (fasteners by  
others).  
Hanger Brackets  
4) Bolt 1/2 in. (13 mm) threaded rod into  
the hanger brackets.  
5) Fasten threaded rod to ceiling  
supports then level the hood.  
Fig. 14  
Note: The installation of the hoods shall be in accordance with NFPA 96 (latest edition), Standard for  
Ventilation Control and Fire Protection of Commercial Cooking Operations.  
Proximity Hood  
9
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Full Enclosure Panels  
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork  
attached and fire system connections completed.  
1. Tack-weld or clamp end enclosure panels onto standing seam (clamps provided).  
2. Attach the end enclosure panels to the wall (fasteners by others).  
3. Position the front enclosure panel(s) on the hood and bolt to the end enclosure panels with the  
5/16 in. bolts provided.  
4. Tack-weld or clamp the front enclosure panel(s) to the standing seam. If clamps are used, they  
must be positioned 4 in. (100 mm) from the ends and in the center of the front enclosure panel.  
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk.  
(GE SCS1009, or its equivalent). The caulk is not provided.  
6. Installation instructions may not be applicable for concrete ceilings.  
End Enclosures  
Bolt Here  
Front Enclosure(s)  
Standing Seams  
Fig. 15  
Proximity Hood  
ꢀ0  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Plate Shelf with Duct Enclosure Panels  
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork  
attached and the fire system connections completed. Plate shelf will be factory mounted to hood  
(shown loose).  
1. Tack-weld or clamp end enclosure panels into place (clamps provided).  
2. Attach the end enclosure panels to the wall (fasteners are not provided).  
3. Position the front enclosure panel(s) on the hood and bolt to the end enclosure panels with the  
5/16 in. bolts provided.  
4. Tack-weld or clamp the front enclosure panel(s) to the hood. If clamps are used, they must be  
positioned 4 in. (100 mm) from the ends and in the center of the front enclosure panel.  
5. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk.  
(GE SCS1009, or its equivalent). The caulk is not provided.  
6. Installation instructions may not be applicable for concrete ceilings.  
End Enclosures  
Front Enclosure(s)  
Plate Shelf  
Standing Seams  
Fig. 16  
Proximity Hood  
ꢀꢀ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Passover Shelf with Duct Enclosure Panels  
Before installing the enclosure panels, make sure the hood is hung in position with all the ductwork  
attached and fire system connections completed.  
1. Attach mounting channels to the wall in the correct location.  
2. Fasten end and front enclosure panels to Passover shelf with fasteners provided.  
3. Bolt front and end enclosure panels together with the 5/16 in. bolts provided in the hardware  
package.  
4. Place enclosure assembly on hood top, tack-weld shelf to hood in rear corners.  
5. Attach the end enclosure panels to mounting channels (fasteners provided).  
6. To allow for ease of cleaning, caulk the external seams with NSF Approved silicone caulk.  
(GE SCS1009, or its equivalent). The caulk is not provided.  
7. Installation instructions may not be applicable for concrete ceilings.  
End Enclosures  
Mounting Channels  
Front Enclosure  
Passover Shelf  
Fig. 17  
Proximity Hood  
ꢀ2  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Backsplash Panel Installation Instructions  
1. Layout backsplash panels  
FLAT BACKSPLASH PANEL  
according to Fig. 18  
MATERIAL GAUGE — STAINLESS  
Note offset in panel for overlap.  
If the backsplash panel length  
is greater than 46 in. (1168.4  
mm), it will be shipped in  
multiple pieces. Be sure offsets  
match up to other panels.  
LENGTH  
QTY  
WALL  
Inches  
<= 48  
Millimeters  
<= 1219.2  
1
2
3
4
5
>48<=94  
>94<=141  
>1219.2<=2387.6  
>2387.6<=3581.4  
HEIGHT  
>141<=188 >3581.4<=4775.2  
>188<=235  
>4775.2<=5969  
2. Insulated Panels extend  
1 inch from the wall  
(Fig. 19). Bottom edge of  
hood must mount tight to  
top of panel. Check hood  
mounting height before  
panel installation.  
LENGTH  
3. After the backsplash  
panel has been  
positioned, drill holes  
in the panel and fasten  
to the wall. (fasteners  
provided by others).  
Fig. 18  
NOTE: PANELS UP TO 48 IN. (1219.2 MM) WIDE SHIP IN ONE PIECE; OVER 48 IN. (1219.2 MM) IN MULTIPLE PIECES.  
4. Caulk the joints between  
the hood and the  
backsplash panel with  
NSF Approved silicone  
caulk. (GE SCS1009,  
or its equivalent). The  
caulk is not provided.  
When multiple panels  
are required, caulk  
the joint between the  
backsplash panels with  
NSF approved silicone  
caulk (GE SCS1009, or its  
equivalent). The caulk is  
not provided.  
1 IN. (25.4 MM)  
INSULATED BACKSPLASH PANEL  
MATERIAL GAUGE — STAINLESS  
INSULATION — 1 IN. (25.4 MM)  
LENGTH  
WALL  
QTY  
Inches  
<= 46  
Millimeters  
<= 1168.4  
1
2
3
4
5
>46<=91  
>91<=136  
>1168.4<=2311.4  
>2311.4<=3454.4  
HEIGHT  
>136<=181 >3454.4<=4597.4  
>181<=226 >4597.4<=5740.4  
LENGTH  
Fig. 19  
NOTE: PANELS UP TO 46 IN. (1168.4 MM) WIDE SHIP IN ONE PIECE; OVER 46 IN. (1168.4 MM) IN MULTIPLE PIECES.  
Proximity Hood  
ꢀꢁ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Duct Collar Installation  
Exhaust Ducts  
1. If the exhaust duct has been factory mounted, skip this section.  
2. The exhaust duct must be located within the shaded region of Fig. 20. Note dimensions.  
Dimension Y assumes a 3 in. (76.2 mm) integral airspace on the hood back. When no 3 in.  
(76.2 mm) integral airspace is present, Y=0 in. (0 mm).  
3. Cut out appropriate size hole to match the duct collar provided.  
4. The exhaust duct connection is to be a continuous liquid-tight weld.  
x
HANGER BRACKET  
DUCT CUT OUT AREA  
y
EXHAUST PLENUM  
FRONT OF HOOD  
Fig. 20  
X= 12 in. (304.8 mm)  
Y= 3 in. (76.2 mm)  
Supply Ducts  
Proximity hoods do not have integral supply plenums. Reference External Supply Plenums (Page 7).  
Fire System Installation  
The final fire system hook-up must be completed at this time. Unobstructed access is required for the  
fire system installer to make plumbing connections to various locations on the hood top. Do not install  
any enclosures until the fire system installation is complete.  
Proximity Hood  
ꢀ4  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Exhaust Air Balancing Baffles (EABB)  
This is a guide to assist in determining if multiple hoods on one fan can be balanced to have equal  
static pressure. For multiple hoods on one fan to achieve their designed exhaust flow, all of the hoods  
must have equal static pressure at their designed exhaust flow.  
The laws of physics force the static pressure for each branch of a duct system on one fan to always be  
equal. This will happen by the flow rate increasing in low static branches and decreasing in high static  
branches until the static pressure is equal in all branches.  
Checking for Balance  
Every hood with Exhaust Air Balancing Baffles (EABB) has a range for its static pressure. The low  
number in this range is given by the standard calculation for hood static. (Static that is printed with  
the CAPS submittal). The maximum increase above the low number can be calculated from the duct  
velocity at the low static, (also given on CAPS submittal). This is then added to the low number to get  
the highest static pressure possible with an EABB.  
The maximum potential increase in static is given in the graph, or can be calculated from:  
2
Maximum Increase in Static Pressure for Exhaust Air Balancing Baffle  
Max. Increase = 0.00000036 x (Duct velocity)  
(Fully Closed)  
4.5  
After the range for each hood is calculated, it  
4
should be compared to the hood with the highest  
3.5  
static pressure. If the highest hood falls inside of  
the range, then the hoods can be balanced with  
the EABB. If it is higher than the range, the hoods  
cannot be balanced.  
3
2.5  
2
1.5  
Example 1:  
1
Hood 1:  
Ps = 0.58 in. wg  
0.5  
0
Duct Velocity = 1900 FPM  
Ps = 0.44 in. wg.  
500  
1000  
1500  
2000  
2500  
3000  
3500  
Duct Velocity FPM  
Hood 2:  
Duct Velocity = 1800 FPM  
Hood 2 has the lower Ps, at 1800 FPM the maximum increase in Ps is 1.17. The range for Hood 2 is  
0.44 to 1.61. Hood 1 is less than 1.61 so these hoods can be balanced.  
Example 2:  
Hood 3:  
Ps = 2.00 in. wg  
Duct Velocity = 2000 FPM  
Ps = 0.44 in. wg  
Hood 4:  
Duct Velocity = 1500 FPM  
Hood 4 has the lower Ps, at 1500 FPM the maximum increase in Ps is .81. The range for Hood 4 is 0.44  
to 1.25. Hood 3 is higher than 1.25 so these hoods cannot be balanced.  
Note 1: For many systems, an EABB may not be needed on the hood that has the highest static pressure. The  
exception to this is if the individual ductwork has uneven static pressures.  
Note 2: When sizing the fan, use the static pressure from the highest hood and sum the CFM from all the hoods.  
Proximity Hood  
ꢀ5  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Balancing the Kitchen Exhaust System  
A. To determine the proper dining room air balance:  
1. Refer to engineering drawings to determine total exhaust CFM from dining areas.  
(Exhaust fans, heating and air conditioning units, restrooms, etc.)  
2. Determine the total CFM of make-up air supplied to dining area.  
3. Subtract #1 from #2 above. If the result is a negative number, a negative pressure is present  
in the dining area. In this case, kitchen exhaust odors could be drawn from the kitchen to the  
dining area. Therefore, exhaust or supply air should be adjusted to provide a slight positive  
pressure in the dining area.  
B. To determine proper kitchen air balance:  
1. Refer to engineering drawings to determine total exhaust from the kitchen area.  
(Exhaust hoods, dishwasher hoods, etc.)  
2. Determine total CFM of make-up air supplied to kitchen area.  
(Make-up air hoods, heating and air conditioning units, etc.)  
3. Subtract #1 from #2 above. The result should be a negative number. If the result is a positive  
number, a positive pressure is present in the kitchen area. Kitchen odors could be forced into  
the dining area. Also, a positively balanced kitchen area can adversely affect the performance  
of the exhaust hood.  
Caution: According to NFPA 96, Ch. 8-3 Replacement Air: Replacement air quantity shall be adequate  
to prevent negative pressures in the commercial cooking area(s) from exceeding 4.98 kPa (0.02 in.  
water column).  
Testing Hood Air Volume  
Baffle Filter Style Hoods  
A. Exhaust:  
With all the filters in place, determine the  
total hood exhaust volume with a rotating  
vane anemometer as follows:  
H/4  
x
x
x
x
1. All cooking equipment should be on.  
2. Measure the velocities  
H
x
Velocity measurements should be  
taken at five locations per filter. These  
must be over a filter slot as in Fig. 21.  
H/2  
H/4  
Fig. 21  
Proximity Hood  
ꢀꢂ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Measure the velocity of each location.  
A digital 2.75 in. (70 mm) rotating  
vane anemometer or equivalent  
is suggested. The center of the  
anemometer should be held 2 in.  
(50 mm) from the face of the filters  
as shown in Fig. 22. It is helpful  
to make a bracket to keep the  
anemometer at the 2 in. (50 mm)  
distance and parallel to the filter.  
Both squareness and distance are  
very important for accuracy.  
Rotating Vane Anemometer  
2 in.  
Fig. 22  
Calculate the average velocity for the filter.  
3. Determine the filter’s conversion factor from the table.  
4. Calculate the filter’s volume in CFM (m3/hr) by multiplying the average velocity by the  
conversion factor.  
5. Calculate the hood’s volume by repeating the process for the remaining filters and summing the  
individual filter volumes.  
Nominal Filter Size (H x L)  
Imperial  
Metric  
Conversion Factor  
Conversion Factor  
Inches  
Millimeters  
400 x 400  
500 x 400  
400 x 500  
500 x 500  
16 x 16  
16 x 20  
20 x 16  
20 x 20  
1.63  
2.13  
1.90  
2.48  
.157  
.198  
.177  
.230  
255  
250  
Example: Exhaust Only Hood with three 20 x 16 Filters  
Measured velocities in fpm for one 20 x 16 Filter  
Sum of Velocity Readings  
(4663.44 m/h)  
(4572 m/h)  
256  
(4681.73 m/h)  
Average Velocity  
=
=
=
248  
240  
Number of Readings  
(4535.42 m/h)  
(4389.12 m/h)  
255 + 250 + 256 + 248 + 240  
5
(Imperial)  
= 249.8 fpm  
4663 + 4572 + 4681 + 4535 + 4389  
5
(Metric)  
= 4568 m/hr  
For a nominal filter size of 20 x 16, the conversion factor is 1.90 Imperial (.177 Metric)  
Volume for one filter = Conversion Factor x Average Velocity  
=
=
1.90  
.177  
x
x
249.8 fpm  
4568 m/hr  
=
=
474.6 cfm  
809 m3/hr  
Total hood volume  
= (Filter 1 Volume) + (Filter 2 Volume) + (Filter 3 Volume)  
=
=
474.6  
809  
+
+
455.4  
880  
+
+
470.1  
799  
= 1400.1 cfm  
= 2488 m3/hr  
Proximity Hood  
ꢀꢃ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Supply (If Applicable):  
Example for Perforated Face Supply  
1. Hood set up  
If the make-up air unit has a temperature control, it should be used to keep the supply air at the  
desired room discharge air temperature.  
2. Measure Velocities  
Divide the perforated face panel into a grid of equal areas, each approximately 4 in. (100 mm)  
square.  
Measure the velocity at the center of each grid area. A digital 2.75 in. (70 mm) rotating vane  
anemometer or equivalent is suggested. The center of the anemometer should be held tight to  
the face of the panel, and parallel to the filter. Both squareness and distance are important for  
accuracy. Calculate the average velocity of the panel.  
3. Measure the length, height, and width of the perforated face panel.  
4. Calculate the perforated face panel volume in CFM by using the following formula:  
Volume  
Volume  
=
=
Avg. Velocity  
Avg. Velocity  
Length (in.)  
Length (m)  
Height (in.) 0.005  
*
*
*
*
*
Height (m)  
0.72  
*
5. Calculate the system’s volume by repeating the process for the remaining panels and adding  
the individual panel volumes together.  
Filter Readings (fpm)  
Filter Readings (m/hr)  
260 250 255 260 250 255 265  
270 275 270 280 265 265 270  
290 285 280 280 275 290 295  
285 275 280 260 270 265 260  
4755 4572 4663 4755 4572 4663 4846  
4938 5029 4938 5121 4846 4846 4938  
5304 5212 5121 5121 5029 5304 5395  
5212 5029 5121 4755 4938 4846 4755  
Example: Face Supply Hood with three 28 in. (.711 m) Perforated Panels  
Measured velocities in FPM for one perforated panel  
Sum of Velocity Readings  
Average Velocity  
=
=
=
Number of Readings  
260 + 250 + … + 265 + 260  
28  
(Imperial)  
= 270.7 fpm  
4755 + 4572 + … + 4846 + 4755  
28  
(Metric)  
= 4951 m/hr  
Measure Length and Height = 28 in. (.711 m) long perforated panels x 16 in. (.406 m) high  
Conversion  
Factor  
Average  
Velocity  
Volume for one panel =  
x
x Length x Height  
=
=
0.005  
0.72  
x
x
270.7 fpm  
4951 m/hr  
x
x
28  
x
x
16  
=
=
606.4 cfm  
1029 m3/hr  
.711  
.406  
Total system volume = (Panel 1 Volume) + (Panel 2 Volume) + (Panel 3 Volume)  
=
=
606.4  
1029  
+
+
614.3  
1044  
+
+
593.8  
1009  
=
1814.5 cfm  
3082 m3/hr  
=
Proximity Hood  
ꢀ8  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Testing Hood Air Volume  
Baffle Filters Style Hoods with the Shortridge Meter  
A. Exhaust  
With all the filters in place, determine the total hood exhaust  
volume with a shortridge meter as follows:  
1. All cooking equipment should be on. If the hood has  
internal short circuit make-up air, it should be turned off.  
2. Measuring Velocities  
• Set up the shortridge meter.  
• For 20 in. (500 mm) wide filters, position the grid as  
shown in Fig. 24 and 25. Average two measurements.  
• For 16 in. (400 mm) wide filters position the grid as  
shown in Fig. 26.  
Take velocity readings for each filter.  
3. *Calculate each filter’s volumetric flow rate by summing  
the flow rate of each individual filter in the hood.  
4. *Calculate the total hood’s volumetric flow rate by  
summing the flow rate of each individual filter in the hood.  
*Note: For best accuracy multiply the velocity of each filter by its  
conversion factor and sum the flow rates Averaging the velocity  
measured for all filters may cause error.  
Fig. 23  
Nominal Filter Size (H x L)  
Imperial  
Metric  
Conversion Factor  
Conversion Factor  
Inches  
Millimeters  
400 x 400  
400 x 500  
500 x 400  
500 x 500  
16 x 16  
16 x 20  
20 x 16  
20 x 20  
1.66  
2.10  
1.96  
2.40  
.154  
.195  
.182  
.223  
14 in.  
2.75 in.  
10 in.  
Example: Measured velocities for 20 x 20 filter = 185 and 189 fpm  
Sum of Velocity Readings  
Average Velocity  
(Imperial)  
=
=
=
Fig. 24  
Fig. 25  
Fig. 26  
Number of Readings  
17.25 in.  
185 + 189  
6 in.  
= 187.0 fpm  
2
10 in.  
3383 + 3456  
2
=
(Metric)  
3420 m/hr  
Conversion  
Factor  
Average  
Velocity  
Flow rate for one filter =  
x
=
=
2.40  
.223  
x
x
187.0 fpm  
3420 m/hr  
=
=
448.8 cfm  
763 m3/hr  
14 in.  
2.75 in.  
(Filter 1  
Flow Rate)  
(Filter X  
Flow Rate)  
10 in.  
Total hood flow rate  
=
+ … +  
= 448.8 + 457.8 + 437.5 + 444.8 = 1788.9 cfm  
= 763 + 778 + 743 + 756  
= 3040 m3/hr  
Proximity Hood  
ꢀ9  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
High Velocity Cartridge Filters  
A. Exhaust  
With all the filters in place, determine the total hood exhaust  
volume with a rotating vane anemometer as follows:  
1/2 Width  
1/4 Width  
1/4 Width  
1. All cooking equipment should be on. If the hood has  
internal short circuit make-up air, it should be turned off.  
2. Measuring Velocities  
• Velocity measurement should be taken at three locations per filter.  
These must be over the inlet opening as shown in Fig. 27.  
Fig. 27  
2 in.  
• Measure the velocity of each location. A digital 2.75 in. (70 mm)  
rotating vane anemometer or its equivalent is suggested. The center  
of the anemometer should be held 2 in. (50 mm) from the face of  
the filters as in Fig. 28. It is helpful to make brackets to keep the  
anemometer at the 2 in. (50 mm) distance and parallel to the filter.  
Both squareness and distance are important for accuracy.  
Rotating Vane  
Anemometer  
3. Calculate the average slot velocity.  
4. Calculate the CFM per linear foot by dividing the average velocity by a  
conversion factor listed in the following table.  
5. Calculate the hood’s exhaust volume by multiplying the CFM per linear  
foot by the length of hood.  
Fig. 28  
Imperial  
Cartridge Filter Size  
Metric  
Conversion Factor  
Conversion Factor  
3
1.63 1/ft3  
16 in. (400 mm) high with 4 in. (100 mm) high inlet  
5.35 1/m  
3
2.15 1/ft3  
20 in. (500 mm) high with 4 in. (100 mm) high inlet  
7.05 1/m  
3
1.24 1/ft3  
16 in. (400 mm) high with 7 in. (120 mm) high inlet  
4.07 1/m  
3
1.58 1/ft3  
20 in. (500 mm) high with 7 in. (120 mm) high inlet  
5.18 1/m  
Example:  
Measure the slot velocities in fpm for a 9 ft. (2.74 m) hood with four 20 x 20 in. (500 x 500 mm)  
filters with standard opening, three readings per filter.  
Filter Readings (fpm)  
Sum of Velocity Readings  
Number of Readings  
470  
440  
430  
431  
439  
425  
Average slot velocity  
(Imperial)  
=
482  
455  
399  
453  
441  
465  
5330  
=
=
= 444.2 fpm  
12  
97474  
Filter Readings (m/hr)  
(Metric)  
= 8123 m/hr  
12  
8595  
8047  
7864  
7882  
8028  
7772  
8815  
8321  
7297  
8284  
8065  
8504  
Average Slot Velocity  
Conversion Factor  
CFM per linear foot  
=
=
=
444.2 fpm  
= 206.6 cfm/linear foot  
2.15  
8123 m/hr  
7.05  
=
1152 m3/hr  
Hood exhaust volume  
=
=
=
CFM/linear foot (or m3/hr / m) x Hood Length  
206.6  
1152  
x
x
9 ft.  
2.74 m  
= 1859.4 cfm  
= 3156 m3/hr  
Proximity Hood  
20  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
High Velocity Cartridge Filters  
A. Exhaust  
With all the filters in place, determine the total hood exhaust  
volume with a shortridge meter as follows:  
1. All cooking equipment should be on. If the hood has  
internal short circuit make-up air, it should be turned off.  
2. Measuring Velocities  
• Set up the shortridge meter. Leave all holes of  
Velgrid open. Do NOT tape over holes that are not  
over openings. The conversion factor takes this into  
account.  
• Position the grid over each filter as shown.  
Take velocity readings for each filter.  
3. *Calculate each filter’s volumetric flow rate by summing  
the flow rate of each individual filter in the hood.  
4. *Calculate the total hood’s volumetric flow rate by  
summing the flow rate of each individual filter in the hood.  
Fig. 29  
*Note: For best accuracy multiply the velocity of each filter by  
its conversion factor and sum the flow rates. Averaging the velocity  
measured for all filters may cause error.  
Nominal Filter Size (H x L)  
Imperial  
Metric  
Conversion Factor  
Conversion Factor  
Inches  
Millimeters  
400 x 400  
400 x 500  
500 x 400  
500 x 500  
2
2
16 x 16  
16 x 20  
20 x 16  
20 x 20  
1.22 ft  
.113 m  
2
2
1.67 ft  
.155 m  
2
2
1.21 ft  
.112 m  
2
2
1.50 ft  
.139 m  
1/2 width  
Example: Measured velocities for 20 x 20 filter = 282 fpm (5157 m/hr)  
1/2 height  
Conversion  
Factor  
Average  
Velocity  
Flow rate for one filter  
=
x
x
(Imperial)  
(Metric)  
=
=
1.50  
.139  
282 fpm  
=
423.0 cfm  
717 m3/hr  
x 5157 m/hr =  
Total hood flow rate  
= (Filter 1 Flow Rate) + … + (Filter X Flow Rate)  
= 423.0 + 421.8 + 420.7 + 418.2 = 1683.7 cfm  
Fig. 30  
= 717 + 717 + 715 + 711  
= 2860 m3/hr  
Proximity Hood  
2ꢀ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Grease-X-Tractor™ High Efficiency Filters or Grease Grabber™ Multi-Filtration System  
A. Exhaust  
1/2 Width  
With all the filters in place, determine the total hood exhaust  
volume with a rotating vane anemometer as follows:  
1/4 Width  
1/4 Width  
1/2 Height  
1. All cooking equipment should be off. If the hood has internal  
short circuit make-up air, it should be turned off.  
2. Measuring Velocities  
• Measurement should be taken at six locations per filter.  
They must be over the inlet opening as shown in Fig. 31.  
• Measure the velocity of each location. A digital 2.75 in.  
Fig. 31  
(70 mm) rotating vane anemometer or its equivalent is  
suggested. The center of the anemometer should be held  
2 in. (50 mm) from the face of the filters as in Fig. 32. It is helpful to make brackets to keep the  
anemometer at the 2 in. (50 mm) distance and parallel to the filter. Both squareness and distance  
are important for accuracy.  
2 in.  
3. Calculate the average velocity for the filter.  
4. Determine the filter’s conversion factor from the table.  
Rotating Vane  
5. Calculate each filters volume in CFM by multiplying the average velocity  
by the conversion factor.  
Anemometer  
Nominal Filter Size (H x L)  
Imperial  
Metric  
Conversion Factor  
Conversion Factor  
Inches  
Millimeters  
400 x 400  
400 x 500  
500 x 400  
500 x 500  
2
2
16 x 16  
16 x 20  
20 x 16  
20 x 20  
1.31 ft  
.122 m  
2
2
1.65 ft  
.153 m  
Fig. 32  
2
2
1.23 ft  
.114 m  
2
2
1.65 ft  
.153 m  
Example: (Imperial)  
Example: (Metric)  
Hood Length = 7 feet 0 inches with four 20 x 20 filters.  
Hood Length = 2.13 meters, with four 500 x 500 mm filters.  
Measure the velocities in fpm for each 20 x 20 filter  
(six readings per filter)  
Measure the velocities in m/hr for each 500 x 500 mm filter  
(six readings per filter)  
225  
210  
228  
237  
230  
250  
225  
245  
201  
238  
222  
240  
245  
223  
265  
221  
187  
197  
226  
220  
240  
219  
219  
200  
4114.80  
3840.48  
4169.66  
4334.26  
4420.12  
4572.00  
4114.80  
4480.56  
3675.88  
4352.54  
4059.94  
4389.21  
4480.56  
4078.22  
4846.52  
4041.65  
3419.86  
3602.74  
4133.08  
4023.36  
4389.12  
4005.07  
4005.07  
3657.60  
Filter 1  
Filter 2  
Filter 3  
Filter 4  
Filter 1  
Filter 2  
Filter 3  
Filter 4  
Sum of Velocity Readings  
Number of Readings  
1258  
Sum of Velocity Readings  
Number of Readings  
23006  
Average slot velocity for Filter 1  
=
=
Average slot velocity for Filter 1  
=
=
=
209.7 fpm  
=
3834 m/hr  
6
6
(repeat for each filter)  
(repeat for each filter)  
For a nominal filter size of 20 x 20, the conversion factor is 1.65  
For a nominal filter size of 500 x 500, the conversion factor is .153  
Volume for Filter 1  
Total hood volume  
= Conversion Factor x Average Velocity  
1.65 ft2  
209.7 ft./min.  
= 346.0 cfm (repeat for each filter)  
Volume for Filter 1  
Total hood volume  
= Conversion Factor x Average Velocity  
.153 m2  
3834 m/hr  
= 586.7 m3/hr (repeat for each filter)  
=
x
=
x
Filter 1  
Volume  
346.0  
Filter 2  
Volume  
377.6  
Filter 3  
Volume  
386.9  
Filter 4  
Volume  
378.1  
Filter 1  
Volume  
587  
Filter 2  
Volume  
642  
Filter 3  
Volume  
657  
Filter 4  
Volume  
642  
=
=
+
+
+
+
+
+
=
=
+
+
+
+
+
+
=
1488.6 cfm  
=
2528 m3/hr  
Proximity Hood  
22  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Grease-X-Tractor™ High Efficiency Filters or Grease Grabber™ Multi-Filtration System  
A. Exhaust  
With all the filters in place, determine the total hood exhaust  
volume with a shortridge meter as follows:  
1. All cooking equipment should be on. If the hood has  
internal short circuit make-up air, it should be turned off.  
2. Measuring Velocities  
• Set up the shortridge meter. Leave all holes of  
Velgrid open. Do NOT tape over holes that are not  
over openings. The conversion factor takes this into  
account.  
• For 20 in. (500 mm) high filters, position the grid  
as shown in Fig. 34 and 35. Average the two  
measurements.  
• For 16 in. (400 mm) high filters position the grid as  
shown in Fig. 36.  
• For 20 in. (500 mm) wide filters, position the grid over  
the left and right side of the filter. Average the two  
measurements.  
Fig. 33  
Take velocity readings for each filter.  
3. *Calculate each filter’s volumetric flow rate by summing the  
flow rate of each individual filter in the hood.  
4. *Calculate the total hood’s volumetric flow rate by summing  
the flow rate of each individual filter in the hood.  
*Note: For best accuracy multiply the velocity of each filter by its  
conversion factor and sum the flow rates. Averaging the velocity  
measured for all filters may cause error.  
Nominal Filter Size (H x L)  
Imperial  
Metric  
Conversion Factor  
Conversion Factor  
Inches  
Millimeters  
400 x 400  
400 x 500  
500 x 400  
500 x 500  
14.25 in.  
2.75 in.  
Fig. 34  
2
2
16 x 16  
16 x 20  
20 x 16  
20 x 20  
1.53 ft  
.142 m  
2.75 in.  
2
2
2.00 ft  
.185 m  
2
2
2.25 ft  
.209 m  
2
2
3.00 ft  
.279 m  
Example:  
Measured velocities for 20 x 20 in. (500 x 500 mm) filter.  
Fig. 35  
Sum of Velocity Readings  
Number of Readings  
Average slot velocity  
(Imperial)  
=
198 + 205  
=
=
= 201.5 fpm  
2
3021 + 3749  
2
2.5 in.  
(Metric)  
= 3385 m/hr  
3.25 in.  
14.75 in.  
Flow rate for one filter  
=
=
Conversion Factor  
3.0  
x
x
Average Velocity  
14.25 in.  
2.75 in.  
201.5 fpm  
3385 m/hr  
=
604.5 cfm  
944 m3/hr  
Fig. 36  
=
.279  
x
=
2.75 in.  
Filter 1  
Flow Rate  
Filter X  
Flow Rate  
Total hood flow rate  
=
=
+
+
+
604.5  
+
+
600.3  
1020  
592.4  
1006  
+
+
2410.5 cfm  
4012 m3/hr  
613.3  
1042  
=
=
944  
Proximity Hood  
2ꢁ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Amerex Wiring Plan View  
POWER SOURCE  
MANUAL RESET RELAY  
PRM  
ELECTRIC GAS VALVE  
MICROSWITCH  
INSTALLER PROVIDED JUNCTION BOXES  
BASIC WIRING DIAGRAM  
POWER SOURCE  
MANUAL RESET RELAY  
RED (COMMON)  
YELLOW (N.O)  
BLACK (N.C.)  
GAS VALVE  
NOTE: DO NOT USE YELLOW WIRE ON MICROSWITCH IN NORMAL  
INSTALLATION. THE YELLOW WIRE IS TO BE USED ONLY FOR  
EXTINGUISHER ALARM, LIGHTS, CIRCUITS, ETC.  
MICROSWITCH  
BASIC WIRING DIAGRAM  
MANUAL RESET RELAY  
L1  
RED (COMMON)  
120V/60HZ  
L2  
K1  
Ka  
PUSHBUTTON SWITCH  
YELLOW (N.O)  
K1b  
BLACK (N.C.)  
MICROSWITCH  
CURRENT DRAW MAX:  
8A RESISTIVE  
8A INDUCTIVE  
120VAC  
GAS VALVE  
SEE NOTE 3  
NOTES:  
1.  
2.  
DENOTES FIELD INSTALLATION  
DENOTES FACTORY INSTALLATION  
3. GAS VALVE: UL LISTED ELECTRICALLY-OPERATED SAFETY VALVE FOR NATURAL OR LP GAS AS NEEDED OF  
APPROPRIATE PRESSURE AND TEMPERATURE RATING, 110V/60HZ OR AMEREX GAS VALVES, PN 12870, 12871,  
12872, 12873, 12874, 12875 and 12876.  
4. K1a and K1b ARE N.0. WHEN K1 IS DE-ENERGIZED.  
Fig. 37  
Proximity Hood  
24  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ansul Wiring Plan View  
2 Snap-Action Switches provided by Greenheck  
Option A  
Relay Part No. 14702  
may be wired as shown.  
Four typical examples shown  
* K1a and K1b are N.O. when K1 is de-energized  
Manual Reset Relay  
L1  
1
Equipment  
Part No. 14702  
Power to cooking  
equipment  
110V/60HZ  
2
Black  
Red  
L2  
K1*  
3
Shunt Trip Breaker  
NO  
NC  
Brown  
K1a  
N.O.  
Snap-Action Switch  
Part No. 423878  
5
6
120 VAC  
Input  
K1b N.O.  
Push Button  
Switch  
N
Gas Valve  
See Note 3  
7
8
Electric gas valve - If reset relay is  
used, see option A or B at right.  
Mechanical gas shut off valve does not  
require electrical connection.  
Alarms  
NO  
NO  
NC  
Ansul Snap-Action Switch  
(Switch contacts shown with Ansul  
Automan in the cocked position)  
Voltage Free  
Option B  
Relay Part No. 426151  
Input  
NC  
Contacts for  
Building Alarm(s)  
Black  
Red  
Snap-Action Switch  
Part No. 423878  
Reset  
Power  
Indicator  
Brown  
GND  
Power to  
A
B
Screw 5  
4
Fan(s)  
L2 Neutral  
L1 Hot  
Waterwash  
Fan  
Starter  
Relay Coil  
110 VAC/60HZ  
3
6
9
3
4
3
2
1
NO  
NC  
4
7
1
Terminal strip in  
Waterwash Control Panel  
5
Manual Reset Relay  
(Part No. 426151)  
Electrical Rating  
1/3 HP, 10 AMP, 120 VAC  
1/2 HP, 10 AMP, 240 VAC  
13 AMP, 28 VDC  
Gas Valve  
See Note 3  
6
Fans  
Note:  
1.  
2.  
NO  
NC  
Denotes field installation.  
Denotes factory installation.  
120 VAC  
Power to  
3. Gas Valves: “UL Listed electrically-operated safety valve for natural or LP gas  
as needed of appropriate pressure and temperature rating, 110V/60HZ”  
or Ansul gas valves.  
4. Do not use black wire on snap-action switch in normal installation. Black  
wire may only be used for extraneous alarm, light circuits, etc.  
Input  
fan(s)  
N
Fan Starter  
Manual Switch  
If prohibited by local codes, do not shut down  
exhaust fans with this method of wiring.  
Fig. 38  
Proximity Hood  
25  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Overall Wiring Plan View  
C O N T R O L C E N T E R  
T O M A K E - U P A I R  
R
Y P O W S E U P P L  
Fig. 39  
Proximity Hood  
2ꢂ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Wiring for Switch Panels  
The diagrams below show a typical hood switch panel remote mounted. For hood mounted switches  
refer to the wiring connection decal on the cover of the junction box on the hood top.  
The diagram below shows how to wire the exhaust and supply fans with a control panel to a fire  
suppression contact (FSC1). When wired properly, the suppy fan will be turned off if the fire system is  
activated and allow the exhaust fan to continue to operate.  
The fire suppression contact (FSC1) is provided as part of the fire suppression system and is normally  
mounted in the fire system control box.  
COMBINED EXHAUST & SUPPLY SWITCHING  
EXHAUST FAN CONTACT  
OPTIONAL  
SUP FAN  
JUNCTION BOX  
OL  
FSC1  
ON TOP OF HOOD  
FOR FIELD  
115VOLT  
CONTROL  
OL  
EXH  
FAN  
STR  
SUP  
FAN  
STR  
SUP  
HTR  
CTRL  
SUPPLY FAN CONTACT  
CONNECTION OF  
120 VOLT  
H
N
SUPPLY POWER  
HOOD SWITCH  
PANEL DETAIL  
HOOD  
LIGHTS  
LIGHT  
SWITCH  
EXHAUST & SUPPLY  
SWITCH  
HEATER  
SWITCH  
SEPARATE EXHAUST & SUPPLY SWITCHING  
EXHAUST FAN CONTACT  
OL  
SUPPLY FAN CONTACT  
OL  
CONTROL  
VOLTAGE  
JUNCTION BOX  
ON TOP OF HOOD  
FOR FIELD  
EXH  
FAN  
STR  
SUP  
FAN  
STR  
SUP  
HTR  
CTRL  
H
N
CONNECTION OF  
120 VOLT  
SUPPLY POWER  
LIGHT  
SWITCH  
EXHAUST  
SWITCH  
SUPPLY  
SWITCH  
HEATER  
SWITCH  
HOOD  
LIGHTS  
Fig. 40  
Proximity Hood  
2ꢃ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance  
Daily Maintenance  
1. Wipe grease from exposed metal surfaces on the hood interior using a clean, dry cloth.  
2. Visually inspect the filters for grease accumulation. Wash as needed.  
3. Remove grease cup, empty contents, and replace cup.  
Weekly Maintenance  
1. Remove the grease filters and wash in dishwasher or pot sink.  
Note: Filters installed over heavy grease producing equipment may require more frequent cleaning.  
2. Before replacing filters, clean the interior plenum surfaces of any residual grease accumulations.  
Periodic Maintenance  
Stainless steel hood exterior surfaces should be cleaned with a mild detergent and then polished with  
a good grade stainless steel polish to preserve the original luster.  
Note: Never use abrasive cleaners or chemicals on hood surfaces. Never use chlorine based cleaners  
or iron wool pads to clean the hood. They may scratch or mar the material and promote corrosion.  
Always rub with the grain of the stainless.  
Proximity Hood  
28  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Grease Grabber™ Multi-Stage Filtration System  
For use in Model GG__ Canopy Hoods Only  
Installation  
Note: Never install the Second Stage filter in the front filter channel. The Second Stage filter  
must be installed behind a UL Classified Grease-X-Tractor™ primary filter Model HE or GX.  
1. Slide the top edge of the Second Stage filter into the top rear filter channel; Fig. 41.  
2. Lifting the lower edge of the filter past the grease trough, continue to push the top of the filter into  
the channel.  
3. When the filter is even with the bottom rear filter channel, set the filter into the channel; Fig. 42.  
4. Slide the filter to one end of the hood and repeat until all the filters are installed. Make sure the  
filters are placed tightly together with no visible gaps.  
5. Latch filters together by connecting hooks to handle on next filte; Fig. 43.  
6. Install the Grease-X-Tractor™ primary filters in the same manner using the front filter channel.  
Fig. 41  
Fig. 42  
Fig. 43  
Proximity Hood  
29  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Grease Grabber™ Filter Cleaning  
Step 1 Remove the front GX filters: (1A) Remove middle filters first, (1B) slide ends toward middle and remove.  
GG Filters, second row of filters  
GX Filters, first row of filters  
1A  
1B  
1C  
Step 2 Release the hooks that hold the filters together. Slide the top hook upward and the bottom hook downward until the  
hook releases. Do this to all filters.  
Slide  
hooks  
2A  
2B  
2C  
Step 3 Remove the GG filters, starting in the middle of the hood: (3A) Grab the handles on either side and lift the filter up,  
(3B) Pull the bottom of the filter toward yourself, (3C) Lower the filter out of the hood. Repeat this process for each  
filter. The filters that are on the ends will have to be slid toward the middle and then lifted out.  
Pull filter down  
Slide  
filter up  
Pull bottom of  
filter towards yourself  
3A  
Step 4 Frequent Maintenance:  
3B  
3C  
Note: Required washing frequency is dependent on type of cooking and quantity of food cooked.  
- Remove filters from hood and place each filter in a whirlpool sink or dishwasher.  
- If using a whirlpool sink, cycle for 10 minutes. Use standard dishwash soap. (4A)  
- If using a dishwasher, cycle it three times to ensure all grease is removed. (4B)  
- If using standard sink, cover with hot water and degreaser and soak for two hours. Rinse after soaking.  
Note: For hoods with large quantities of filters, it is acceptable to wash 3 to 4 filters each day, cycling all of the filters in three days.  
Note: The beads will discolor. Standard cooking will turn the beads yellow in color. Open flame cooking will cause the beads to  
blacken. Neither affects the performance of the filters.  
Periodic Inspection:  
- Each filter may be soaked in hot soapy water for two hours once a month prior to washing if grease build-up is found.  
- Inspect the filters by holding it up to a light. Light shining through more than six holes in a group indicates filter  
damage.  
- For filter replacement, call 1-800-337-7400  
4A  
4B  
Step 5 Replace GG filters in hood. Do Step 3 in reverse order. (3C, then 3B, then 3A)  
Step 6 Latch filters together by connecting the hooks to the handle on the next filter. Slide hook on from the top and bottom  
of the handle. Do not try to snap the hooks into place. Do Step 2 in reverse.  
Step 7 Replace the front GX filters. Do Step 1 in reverse. Be sure to install filters in the ends of the hood first, then install the  
filters in the middle of the hood (1B, then 1A)  
Caution: To prevent damage to filter media, do not wash second stage filters in detergents that contain  
hydroxides such as sodium hydroxide or potassium hydroxide.  
Proximity Hood  
ꢁ0  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Filter Washing Frequency Guide  
NOTE: Standard cooking will turn the beads yellow in color. Open flame cooking will cause the beads to  
blacken. Neither affects the performance of the beads.  
Caution: To prevent damage to filter media, do not wash second stage filters in detergents that contain  
hydroxides such as sodium hydroxide or potassium hydroxide.  
Time  
or  
Cycles  
Baffle Filter or  
Grease-X-Tractor™  
Wash Frequency  
Washing Equipment  
Cooking  
Equipment  
Frequency  
Required  
Preference  
Chemical  
Type  
Temp  
Every 3 days  
2 Cycles  
Twice a week  
1 Cycle  
Daily  
2 Cycles  
Griddle  
Fryer  
Every 3 days  
Weekly  
Daily  
2 Cycles  
2 Cycles  
Commercial  
Grade Dish  
Washer  
Dish  
Washer  
Detergent  
1
Best  
180º F  
Min  
Charbroiler  
Wok  
2 Cycles  
Daily  
Daily  
2 Cycles  
2 Cycles  
Every 3 days  
2 Cycles  
Twice a week  
2 Cycles  
Daily  
Griddle  
Fryer  
Every 3 days  
Weekly  
Daily  
3 Cycles  
Low Temp.  
Dish Washer  
(Chemical  
Sanitizer)  
3 Cycles  
Dish  
Washer  
Detergent  
2
3
4
140º F  
Charbroiler  
Wok  
4 Cycles  
2 Cycles  
Daily  
Daily  
4 Cycles  
2 Cycles  
Every 3 days  
5 minutes  
Twice a week  
5 minutes  
Daily  
Griddle  
Fryer  
Every 3 days  
Weekly  
Daily  
10 Minutes  
10 Minutes  
15 Minutes  
15 Minutes  
15 Minutes  
15 Minutes  
25 Minutes  
25 Minutes  
Power  
Wash Sink  
(Whirlpool)  
with Heater  
180º F  
Min  
Pot & Pan  
Detergent  
Charbroiler  
Wok  
5 minutes  
Daily  
Daily  
5 minutes  
Daily  
5 minutes  
Twice a week  
5 minutes  
Daily  
Griddle  
Fryer  
Every 3 days  
Weekly  
Daily  
Power  
Wash Sink  
(Whirlpool)  
no Heater  
Pot & Pan  
Detergent  
140º F  
Charbroiler  
Wok  
10 minutes  
Daily  
10 minutes  
Daily  
Daily  
Griddle  
Fryer  
Every 2 days  
Every 2 days  
1 Hour  
1 Hour  
Soak 10 min., then scrub with  
scour pad and bottle brush  
Daily  
Pot Sink  
with Heater  
Pot & Pan  
Detergent  
and/or  
Soak 5 min., then scrub with  
scour pad and bottle brush  
5
180º F  
(rinse with  
sprayer after  
soaking)  
Degreaser  
Charbroiler  
Wok  
Daily  
Daily  
2 Hours  
2 Hours  
Daily  
Soak 10 min., then scrub with  
scour pad and bottle brush  
2 Hours  
Griddle  
Fryer  
Daily  
Change hot water  
every 30 minutes  
Pot Sink  
Commercial  
Grade  
Kitchen  
no Heater  
2 Hours  
Every 2 days Change hot water  
every 30 minutes  
Daily  
6
140º F  
Soak 10 minutes then scrub  
with scour pad & bottle brush  
(rinse with  
sprayer after  
soaking)  
Worst  
Degreaser  
Charbroiler  
Wok  
Not Recommended  
Not Recommended  
Proximity Hood  
ꢁꢀ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Problem: Exhaust fan is not operating or is not operating at design levels.  
Is the fan receiving power?  
Replace fuses, reset circuit breakers, check disconnect.  
Is the belt loose or broken?  
Replace or tighten belt.  
Is the fan rotating in correct direction?  
Have the electrician correctly wire the fan.  
Problems with make-up air may interfere with the exhaust fan -  
check the manufacturers installation manual.  
Is the make-up air operating?  
Does the airflow need to be increased?  
Adjust or replace pulleys to increase fan RPM, install a larger motor.  
Clean the fan wheel/blade, replace fan wheel if damaged, check for  
loose bolts, check for broken or damaged components, check for  
rags and other foreign objects.  
Does the fan vibrate?  
Problem: Hood is full of smoke. There is smoke coming out of the edges of the hood.  
Is the fan operating at design levels?  
See exhaust fan troubleshooting section.  
Refer to test and balance report, design specifications and fan  
curves; have an electrician check the motor amperage; try removing  
the filter temporarily to see if capture improves. (Make sure to  
replace filter to prevent risk of fire!); switch to different filters with  
lower static pressure.  
Is the fan correctly sized?  
Are the filters in good condition?  
Clean filters, replace damaged filters, properly position filters.  
Is there sufficient make-up air?  
(Kitchen should be in a slight negative  
but not excessive. Check to see if there  
is a strong draft through an open door).  
Check make-up air unit, increase make-up air, make-up air should be  
evenly distributed throughout the kitchen.  
Does the current cooking equipment  
match the original design?  
Adjust or replace fan to match the cooking equipment load.  
One hood may be over exhausting and the other hood not drawing  
enough. Restrict second hood to help problem hood.  
Are there multiple hoods on one fan?  
Are there closed dampers in the duct?  
Is the ductwork complex or to small?  
Is the ductwork obstructed?  
Open dampers.  
Change to a higher static fan, modify the ductwork.  
Clear obstruction.  
Is this a short circuit hood?  
Turn off or reduce the amount of air supplied to short circuit.  
Problem: Smoke blows away before reaching the bottom of the hood.  
Are there cooling fans directed at the  
hood or cooking equipment?  
Turn off or redirect fans.  
Are there ceiling diffusers directing air at Move diffusers to more neutral area or replace with a diffuser that  
the hood?  
directs air away from the hood.  
Are there open windows or doors?  
Close windows and doors.  
Find source of the draft and eliminate, add side skirts to hood (test  
with cardboard – use stainless for permanent side skirts); increase  
the amount of overhang on the spillage side; add a 6 in. lip around  
the base of the hood (test with cardboard – use stainless for  
permanent side skirts); make-up air should be spread out evenly  
through the kitchen.  
Are there cross drafts or other drafts in  
the kitchen?  
Add side skirts to hood (test with cardboard first); increase the  
amount of overhang on spillage side.  
Is the hood near a main walkway?  
Proximity Hood  
ꢁ2  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Troubleshooting  
Problem: Smoke blows away before reaching the bottom of the hood.  
Are there pass-thru windows near  
the hood?  
Adjust amount and locations of make-up air to eliminate drafts  
through the pass-thru windows.  
Is this an air curtain hood?  
Turn off or reduce the amount of make-up air.  
Try turning off or reducing the amount of make-up air; block off  
portions of the supply to direct air away from the problem area (test  
with cardboard).  
Is the make-up air part of the hood  
or an attached plenum?  
Problem: Pilot lights are being blown out or cooking equipment is being cooled by make-up air.  
Try turning off or reducing the amount of make-up air; block off  
portions of the supply to direct air away from the problem area (test  
with cardboard first); remove any obstructions in front of supply that  
Are there drafts from make-up air?  
directs air toward cooking equipment.  
Problem: Cold air can be felt by the cook at the hood.  
Is this a short circuit hood?  
Turn off or reduce the amount of air supplied to short circuit.  
Turn off or reduce the amount of air supplied to the air curtain; heat  
the supply air.  
Is this an air curtain hood?  
Is the make-up air part of the hood  
or an attached plenum?  
Try turning off or reducing the amount of make-up air; heat the  
supply air.  
Problem: The kitchen gets hot.  
Is the hood capturing?  
Hood is not drawing enough air, see sections above on fan  
performance and hood capture.  
Is this an air curtain hood?  
Turn off or reduce the amount of air supplied to the air curtain.  
Is the make-up air part of the hood  
or an attached plenum?  
Try turning off or reducing the amount of make-up air; cool the  
supply air.  
Problem: Cooking odors in the dining area.  
Hood is not drawing enough air, see sections above on fan  
performance and hood capture.  
Is the hood capturing?  
Is there a draft through doors between  
the kitchen and dining area?  
Decrease make-up air in the kitchen; increase exhaust air through  
hood.  
Problem: Grease is running off the hood.  
Is there grease on top of the hood?  
Is the caulk missing or damaged?  
Is the grease cup inserted properly?  
Exhaust duct is not correctly welded.  
Clean problem area and re-caulk.  
Put grease cup back in place.  
Problem: Hood is noisy.  
Is the fan running in the correct direction? See exhaust fan troubleshooting section.  
Are the filters in place?  
Replace missing filters.  
Is the hood over exhausting?  
Slow down fan (see exhaust fan troubleshooting section)  
Proximity Hood  
ꢁꢁ  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Before calling your manufacturers representative to report a problem, have the following  
information available:  
1. Review / summary of troubleshooting section in installation operation manual.  
2. Hood model and serial number.  
3. Current cooking equipment line-up.  
4. Size of hood (length, width and height).  
5. Island or wall configuration.  
6. Multiple hoods on one fan.  
7. Nature of spillage (one end; all around the edges).  
8. Does the smoke make it to the hood?  
9. Height hood is mounted above finished floor.  
10. How make-up air is brought into the kitchen (hood, ceiling diffusers, separate plenum).  
11. Is exhaust system controlled by a variable volume system?  
12. Is the fan noisy?  
REPLACEMENT PARTS  
GREENHECK  
PART NUMBER  
FILTER DESCRIPTION  
(HEIGHT x WIDTH x DEPTH)  
457627  
457629  
851656  
851657  
851709  
851710  
852388  
852389  
850551  
851776  
851777  
851778  
851779  
851780  
851781  
851782  
851783  
851784  
851510  
851511  
851512  
851618  
451131  
470674  
16X16 SS Baffle Filters  
16x20 SS Baffle Filters  
16x16 High Velocity Cartridge Filters  
16x20 High Velocity Cartridge Filters  
16x16 Grease-X-Tractor™ Filters  
16x20 Grease-X-Tractor™ Filters  
16x16 Grease Grabber™ Filters  
16x20 Grease Grabber™ Filters  
Lights Only  
Fans Only  
Lights and Fan (2 switches)  
Fan and Heat (2 switches)  
Exhaust and Supply Fan (2 switches)  
Light, Fan and Heat (3 switches)  
Light, Exhaust, Supply separate switch (3 switches)  
Exhaust, Supply, and Heat separate switch (3 switches)  
Light, Exhaust, Supply, Heat separate switch (4 switches)  
Fan and Temper (3 positions) (2 switches)  
Light, Fan and Temper (3 positions) (3 switches)  
Exhaust, Supply, and Temper (3 positions) (3 switches)  
Light, Exhaust, Supply and Temper (3 positions) (4 switches)  
Automatic Fire Damper Test Switch  
Grease Cup  
Replacement Filters Handles  
Proximity Hood  
ꢁ4  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Maintenance Log  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Date __________________ Time _____________ AM/PM  
Notes:___________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
_________________________________________________  
Proximity Hood  
ꢁ5  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from  
the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option  
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of  
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the  
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications  
without notice.  
Contact Greenheck Fan Corporation:  
®
458294 • Proximity Hood, Rev. 3, March 2008  
Copyright 2008 © Greenheck Fan Corp.  
ꢁꢂ  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Hamilton Beach Blender 56409 User Manual
Hamilton Beach Blender 58148 User Manual
Hamilton Beach Can Opener 76607 User Manual
Hamilton Beach Toaster 24669 User Manual
HANNspree Flat Panel Television ST02 15U1 User Manual
Hayter Mowers Trimmer 407D User Manual
Honeywell DVD Recorder L User Manual
HP Hewlett Packard Water Dispenser 8568B User Manual
Hughes Kettner Stereo Amplifier Bass Kick 101 User Manual
Hunter Fan Fan 21888 User Manual