Greenheck Fan Furnace IGX HV User Manual

Modular Heating & Ventilating Unit  
Model IGX-HV  
• Indirect Gas-Fired Heating  
• Evaporative • Chilled Water • DX Cooling  
October  
2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
controL oPtIons  
Heating and Ventilating control  
Three heating and ventilating options are available to provide proper tempering and fulfill varying requirements for  
fresh outdoor air. In all cases, heating and cooling functions are controlled by a Greenheck room thermostat or a  
DDC system (by others).  
HV1: 0%-30% Minimum outdoor air  
HV1 is the most common among  
heating and ventilating units, allowing  
you to set the minimum outdoor air  
volume between 0 and 30% of the total  
supply air volume. With the relatively  
low percentage of outdoor air, mixed  
air temperatures are mild and stable.  
1-stage heating and/or cooling is  
recommended. (2-stage or electronic  
modulation is optional).  
HV2: 30%-75% Minimum outdoor air  
The HV2 option is required when the minimum outdoor air volume  
exceeds 30% of the total supply air volume. With higher outdoor air  
volumes, mixed air temperatures  
can vary greatly. Accordingly,  
2-stage heating and/or cooling is  
recommended. Also, an airstream  
override thermostat is standard  
with HV2 to prevent cold air  
discharge (below 55˚ F) when the  
Outdoor Air  
30% - 75%  
Return Air  
25% - 100%  
Supply  
thermostat is satisfied. (electronic  
modulation is optional).  
HV3: 100% return air  
The HV3 option is available when no  
outdoor air is needed. With relatively  
stable return air conditions, 1-stage  
heating and/or cooling is strongly  
recommended. (2-stage or electronic  
modulation is optional).  
Outdoor Air  
0% - 30%  
Return Air  
70% - 100%  
Supply  
Return Air  
100%  
Supply  
thermostat options  
Basic bimetal thermostats with mercury switches or fully programmable electronic thermostats are available as  
part of your IGX-HV system. Match your heating, cooling, staging, and operational requirements to the appropriate  
thermostat.  
tc1: 1-stage Heating / cooling  
TC1 is a coiled bimetal thermostat  
used for single-stage heating, cooling  
or heating-cooling systems.  
tc4: Programmable  
TC4 has full seven-day program  
capability. The thermostat can  
be set for four times and eight  
temperature settings each day of  
the week. It can control up to two  
stages of heating and two stages  
of cooling.  
tc2: 2-stage Heating  
TC2 is a coiled bimetal  
thermostat used for 2-stage  
heating systems.  
tc5: deluxe Programmable  
TC5 has full seven-day program  
capability. The thermostat can  
be set for two occupied and two  
unoccupied times with adjustable  
temperature settings for each day  
of the week. It can control up to  
three stages of heating and two  
stages of cooling. The Intelligent Fan™ feature energizes the  
fan continuously during occupied mode and intermittently  
with a call for heating or cooling in unoccupied mode.  
tc3: 2-stage Heating / 2-stage cooling  
TC3 is a coiled bimetal  
thermostat used for 2-stage  
heating, cooling or heating-  
cooling systems. It includes  
an adjustable heat anticipator,  
stops, and a locking cover.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
MIXInG BoX controLs  
The mixing box (shown at right) includes  
outdoor air and return air low leakage  
control dampers in a face and bypass  
configuration. Either two inch pleated  
or aluminum mesh filters are available  
within the mixing box section. Double wall  
construction is optional.  
A mixing box control option must be  
specified for every IGX-HV unit. Greenheck  
offers eight mixing box control options  
that accommodate a wide variety of  
applications. The four EC and four MB  
options are described below. Specify only  
one control box option per unit.  
Mixing Box controls with economizer cooling  
The economizer controls package enables free cooling using outdoor air. All EC options include a modulating  
actuator for controlling outdoor and return air dampers, and a minimum outdoor air positioner. During a call for  
heating the economizer is locked out and the outdoor air damper holds at the minimum position.  
ec1: outdoor temperature reference  
The economizer controller positions the mixing box  
dampers to achieve 55° F mixed temperature when  
the thermostat calls for cooling AND the outdoor air  
temperature is below the economizer  
setpoint. If outdoor air temperature is  
between 55° F and the economizer  
ec3: airstream temperature reference  
The economizer controller compares the temperatures  
of the outdoor air and return air when the thermostat  
calls for cooling. The mixing box dampers are then  
positioned to maximize the  
airflow of the cooler airstream.  
When outdoor air temperature  
setpoint, the dampers will modulate  
is sufficiently cool, the mixing  
to the 100% outdoor air position.  
box dampers will modulate to  
Above the setpoint, the outdoor  
air damper is held at the minimum  
provide 55° F mixed air. The  
outdoor air sensor is factory  
Outdoor Air  
position. The setpoint is field  
adjustable and the outdoor air sensor  
is factory mounted.  
mounted. The return air sensors  
are field installed.  
Return Air  
Supply  
ec4: airstream enthalpy reference  
Same as EC3, except airstream enthalpy values are  
compared.  
ec2: outdoor enthalpy reference  
Same as EC1, except economizer setpoint is based on  
outdoor air enthalpy.  
Mixing Box controls (no economizer)  
In addition to the EC options described above, Greenheck offers four MB mixing box control options for  
applications where a factory provided economizer package is not desired.  
MB1: Minimum outdoor air Positioner  
The MB1 option includes a modulating  
automation system that will control the mixing box  
dampers.  
actuator and potentiometer that control  
the outdoor air and return air damper  
MB3: 4-20 ma external signal  
The MB3 option includes a modulating actuator that is  
controlled by an external 4-20 mA signal. Like the MB2  
option, this option is appropriate for applications that  
call for a building automation system that will control the  
mixing box dampers.  
positions. When the unit is energized,  
the dampers will travel to the position  
corresponding to the potentiometer  
setting, providing the desired amount of outdoor air.  
When the unit is powered off, the outdoor air damper  
closes to prevent backdrafting. To adjust the damper  
settings, simply dial the potentiometer (shown above) to  
desired operating position of the outdoor air damper.  
MB4: Manual Quadrant  
The MB4 option consists of a manual  
quadrant that enables the outdoor air  
and return air dampers to be secured  
into a single position. The primary  
function is to introduce the specified minimum outdoor  
air volume during operation. Dampers remain in the  
same position when the unit is powered off.  
MB2: 2-10 Volt external signal  
The MB2 option includes a modulating actuator that is  
controlled by an external 2-10 volt signal. This option  
is appropriate for applications that call for a building  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
cooLInG oPtIons  
evaporative cooling  
An evaporative cooling section includes a galvanized  
steel housing with a louvered intake, two inch aluminum  
mesh filters and a stainless steel evaporative cooling  
media housing. The evaporative cooling media is  
Munters CELdek or GLASdek and has a depth of  
12 inches for 90% cooling effectiveness.  
with evaporative  
cooling. On a call  
for cooling when  
the outdoor air  
temperature is below  
the economizer  
setpoint, the  
dampers modulate  
to provide cool  
mixed temperatures  
Drain and overflow lines are conveniently stubbed  
through the side of the cooling section. The supply line  
connection is field located where convenient.  
down to 55° F. When  
the outdoor air is  
above the economizer setpoint, the evaporative cooling  
section is energized and the dampers travel to the 100%  
outdoor air position.  
IGX-HV airflow capacity for evaporative cooling is up  
to 14,000 cfm. Below 9,000 cfm, evaporative cooling  
modules ship attached and factory wired. Field  
attachment is required for airflow above 9,000 cfm.  
Mixing Box controls:  
Mixing box control option EC1 is recommended for use  
The MB mixing box options are NOT recommended in  
conjunction with evaporative cooling.  
cooling coils  
Model IGX-HV boasts the flexibility of Chilled Water or  
Direct Expansion (DX) cooling with capacity to 11,000  
CFM. The cooling section includes the cooling coil,  
stainless steel drain pan and insulated double wall  
construction. Drain and coil connections are stubbed  
through the wall for convenience.  
For economizer  
climates, the  
EC1 option is  
recommended.  
Mixing box options  
operate as described  
on page 4.  
For proper coil sizing, use Greenheck’s Computer Aided  
Product Selection (CAPS) program or contact your local thermostats:  
representative. Four and six row coils are available.  
The cooling coil  
and MB mixing box  
control options may  
use a 1-stage (chilled  
water or single stage DX) or 2-stage (dual stage DX)  
cooling thermostat.  
Cooling coil sections are installed downstream of the  
mixing box section for a draw through arrangement.  
This provides a streamlined transition to adjacent  
IGX-HV sections. DX coils require remote condensing  
units.  
The cooling coil and EC mixing box control options  
require a 2-stage cooling thermostat. Economizer  
represents the first stage of cooling and a single DX  
stage or chilled water coil represents the second stage  
of cooling.  
Mixing Box controls:  
All MB and EC mixing box control options are available  
with chilled water or DX cooling coils.  
Mixing Box selection Guide  
ec options  
MB options  
ec1  
ec2  
ec3  
ec4  
MB1 MB2 MB3  
MB4  
no cooling  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Yes  
Not  
Not  
evaporative  
cooling  
Yes  
Yes  
No  
No  
No  
No  
Recommended  
Recommended  
chilled Water or  
dX cooling  
Yes*  
Yes*  
Yes*  
Yes*  
Yes  
Yes  
Yes  
Yes  
*Two-stage cooling thermostat required. Boldface type indicates factory recommended options.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
aIr PerForMance  
Housing size 12  
Maximum  
Furnace size  
(Input MBH)  
totaL statIc Pressure in inches of WG  
ModeL  
cFM  
0.50  
0.75  
1.00  
1.25  
1.50  
1.75  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BPH  
RPM  
BHP  
993  
.21  
1112  
.34  
1238  
.51  
880  
.36  
1004  
.65  
1154  
1.1  
805  
.48  
906  
.79  
1109  
.26  
1228  
.41  
1347  
.59  
1014  
.45  
1113  
.77  
1244  
1.2  
912  
.59  
995  
.93  
1216  
.31  
1325  
.47  
1445  
.68  
1140  
.54  
1219  
.90  
1329  
1.4  
1013  
.71  
1082  
1.07  
1172  
1.55  
1311  
.35  
1415  
.53  
1530  
.75  
1255  
.63  
1321  
1.0  
1419  
1.6  
1110  
.84  
1166  
1.21  
1244  
1.72  
1399  
.40  
1500  
.59  
800  
100  
150  
150  
200  
250  
250  
250  
250  
250  
1579  
.65  
IGX-HV-108  
1,000  
1,200  
1,500  
2,000  
2,500  
2,000  
2,500  
3,000  
1361  
.73  
1417  
1.1  
1503  
1.7  
1199  
.96  
1247  
1.36  
1315  
1.88  
1460  
.84  
1510  
1.3  
1587  
1.9  
IGX-HV-109  
IGX-HV-110  
1325  
1.51  
1386  
2.05  
1014  
1.22  
1097  
1.39  
Housing size 22  
Maximum  
Furnace size  
(Input MBH)  
totaL statIc Pressure in inches of WG  
ModeL  
cFM  
0.50  
0.75  
1.00  
1.25  
1.50  
1.75  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
662  
.58  
756  
1.0  
871  
1.8  
671  
1.7  
749  
2.6  
833  
3.7  
761  
.72  
839  
1.3  
939  
2.1  
741  
2.0  
812  
2.9  
889  
4.2  
853  
.86  
920  
1.5  
1006  
2.4  
808  
2.3  
870  
3.3  
943  
4.6  
934  
1.0  
993  
1.7  
1073  
2.6  
871  
2.6  
929  
3.7  
994  
5.0  
1009  
1.2  
1065  
1.9  
1137  
2.9  
931  
2.9  
982  
4.0  
1044  
5.5  
2,600  
3,500  
4,400  
5,000  
6,000  
7,000  
350  
500  
600  
600  
600  
600  
1133  
2.1  
1197  
3.1  
986  
3.2  
1035  
4.4  
IGX-HV-112  
IGX-HV-115  
1093  
5.9  
Housing size 32  
Maximum  
Furnace size  
(Input MBH)  
totaL statIc Pressure in inches of WG  
ModeL  
cFM  
0.50  
0.75  
1.00  
1.25  
1.50  
1.75  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
566  
2.1  
636  
3.3  
712  
5.0  
542  
3.6  
633  
6.3  
731  
10.2  
627  
2.5  
690  
3.8  
759  
5.5  
590  
4.0  
672  
6.9  
763  
10.9  
685  
2.8  
740  
4.2  
805  
6.1  
634  
4.5  
711  
7.5  
795  
11.6  
738  
3.2  
790  
4.7  
849  
6.6  
678  
5.0  
748  
8.1  
829  
12.3  
790  
3.6  
836  
5.1  
891  
7.1  
723  
5.6  
784  
8.7  
861  
13.1  
839  
4.0  
880  
5.6  
933  
7.7  
765  
6.1  
820  
9.3  
892  
13.8  
7,000  
8,500  
1,050  
1,200  
1,200  
1,200  
1,200  
1,200  
IGX-HV-118  
10,000  
10,000  
12,500  
15,000  
IGX-HV-120  
Note: The air performance data shown does not include internal static pressure losses due to items such as  
filters, dampers and furnaces. For exact air performance data based on specific unit configuration, use the  
Greenheck CAPS selection program.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
accessorIes  
air Filter Gauge  
Propane Gas conversion Kit  
Indicates when filters become  
dirty. An indicator light may be  
wall/beam mounted or provided  
with a remote control panel.  
Greenheck’s indirect gas furnaces are ETL listed for  
both Natural Gas or LP.  
duct adapter  
Duct adapters are optional with factory supplied curbs  
and provide an easy method for attaching ductwork to  
the curb.  
Motorized dampers  
Discharge dampers are available  
to prevent backdrafts when  
the fan is not in operation.  
Mixing box dampers are factory  
mounted and wired.  
double Wall construction  
An interior metal liner is available to isolate insulation  
from the airstream. One-inch thick insulation is included  
with this option.  
Fan spring Vibration Isolation  
Spring vibration isolators are available in lieu of  
neoprene isolators for housing sizes H22 and H32  
(fan sizes 112 and larger).  
Gas Pressure regulator  
Required if building gas line pressure  
exceeds IGX-HV maximum inlet gas  
pressure of 14 in. wg.  
115 Volt service receptacle  
A 115 volt GFCI outlet is mounted externally in a NEMA  
3R box for the convenience of field service personnel. A  
separate 115 volt power source is required.  
smoke detector  
A 12/24 VDC Photoelectric smoke detector is available  
for duct mounting. Typical operating temperature range  
is 32°F to 131°F (0°C to 55°C).  
roof curbs  
Factory provided roof  
curbs are available to  
ensure compatibility  
between make-up air  
unit and roof curb.  
Standard construction is  
discharge diffuser  
Available as either 3-way  
diffuser for horizontal  
discharge or 4-way  
diffuser for downblast  
discharge.  
galvanized steel.  
G90  
special coatings  
3-Way Diffuser  
Greenheck’s Permatector powder paint is available if a  
painted look is desired and recommended for outdoor  
installations near salt water shorelines. Decorative  
baked enamel paints are also available in a variety of  
colors to match existing building fixtures. Consult your  
Greenheck representative for paint selections.  
airstream override  
This option prevents the discharge air temperature  
from dropping below 55°F after the call for heating has  
ended.  
Warm-up control  
Available with the TC5  
Weatherhood  
A galvanized steel mist eliminating intake hood  
is standard on outdoor IGX-HV models. The mist  
eliminating intake hood provides a double layer of  
protection against moisture entering the mixing box  
section.  
thermostat. The thermostat  
may be programmed to  
provide a warm-up cycle prior  
to the occupied start time. This  
ensures immediate comfort  
and proper air quality as people enter the occupied  
areas.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Specifications  
General: Heating and Ventilating unit shall be as  
manufactured by Greenheck or approved equal provided  
all specifications are met. Greenheck Model IGX-HV is  
used as the basis of design. Performance shall be as  
scheduled on plans.  
Electrical: All internal electrical  
components shall be prewired for  
single point power connection. All  
electrical components shall be UL  
listed, recognized or classified where  
applicable and wired in compliance  
with the National Electrical Code.  
Control center shall include motor  
starter, control circuit fusing, control  
transformer for 24 VAC circuit,  
integral disconnect switch with  
separate motor fusing and terminal  
strip. Contactors, Class 20 adjustable  
overload protection and single phase  
protection shall be standard.  
Furnace: Indirect gas fired furnace shall be 80% efficient,  
ETL Listed and have a blow through fan design. Furnace  
shall be capable of operation with Natural or LP gas and  
have a power venting system with post purge cycle. The  
heat exchanger shall be constructed of aluminized steel  
or stainless steel. Standard furnace features shall include  
main gas pressure regulator, main gas valve, electronic  
staged controls, direct spark ignition system, high limit and  
a 24 volt control transformer. Furnace shall be insulated  
and have double wall construction.  
Filter Section: Filters shall be  
mounted in a V-bank arrangement  
such that velocities across the filters  
do not exceed 550 feet per minute. Filters shall be easily  
accessible through a removable access panel.  
Temperature Control: Heating and cooling output shall  
be controlled by a room thermostat to maintain desired  
room temperature. Economizer control shall provide the  
first stage of cooling, where specified. Furnaces shall  
provide one or two stages of heat output control.  
Weatherhood: Weatherhood shall be mist eliminating  
type, constructed of G90 galvanized steel. The  
weatherhood shall contain drainable blade louvers, backed  
by mist eliminating filters to prevent moisture intake.  
Unit Casing and Frames: All frames and panels shall  
be G90 galvanized steel. Where top panels are joined  
there shall be a standing seam to insure positive weather  
protection. All metal-to-metal surfaces exposed to the  
weather shall be sealed, requiring no caulking at job  
site. All components shall be easily accessible through  
removable doors.  
Mixing Box: Mixing box shall contain outside air and  
return air dampers with low leak, pressure activated,  
extruded vinyl blade seals, aluminum jamb seals, Belimo  
actuator and 30% efficient pleated filters in a V-bank  
arrangement. The mixing box shall modulate the amount  
of outdoor and return air by use of dampers. Input signal  
for return damper shall be from potentiometer, 2-10 volt  
signal, 4-20 mA signal or manual quadrant controller.  
Insulation: Models provided with a mixing box shall be  
insulated from the return section through to the supply  
discharge. Insulation shall be in accordance with NFPA  
90A and tested to meet UL 181 erosion requirements.  
Double wall shall be provided if specified.  
Evaporative Cooling Section: Evaporative cooling  
section shall include a galvanized steel housing with  
louvered intake, two inch aluminum mesh filters and a  
stainless steel evaporative cooling module all provided  
by the make-up air unit manufacturer. The louver shall  
be stationary type with drainable blades, designed to  
withstand wind loads of 25 PSF and bear the AMCA seal.  
Evaporative cooling media shall be Munters CELdek with  
a depth of 12 inches for a cooling effectiveness of 90%.  
Drain and overflow connections shall be piped through the  
side of the evaporative cooling section.  
Fan Section: Centrifugal fans shall be double width,  
double inlet. Fan and motor shall be mounted on a  
common base and shall be internally isolated. All blower  
wheels shall be statically and dynamically balanced.  
Ground and polished steel fan shafts shall be mounted in  
permanently lubricated ball bearings (up to size 118) or  
ball bearing pillow blocks (size 120 and larger). Bearings  
shall be selected for a minimum (L10) life in excess of  
100,000 hours at maximum cataloged speeds.  
Motors and Drives: Motors shall be energy efficient,  
complying with EPACT standards, for single speed  
ODP and TE enclosures. Motors shall be permanently  
lubricated, heavy duty type, matched to the fan load and  
furnished at the specified voltage, phase and enclosure.  
Drives shall be sized for a minimum of 150% of driven  
horsepower. Pulleys shall be cast and have machined  
surfaces, 10 horsepower and less shall be supplied with  
an adjustable drive pulley.  
Cooling Coil: Direct expansion (DX) or chilled water  
coil shall be factory tested and rated in accordance with  
ARI 410. Coils shall have copper tubes with permanently  
expanded aluminum fins, 12 fpi or less. DX coils shall be  
equipped with distributors to receive expansion valves at  
the liquid connections. Drain pans shall extend at least  
12 inches downstream of coil and be sloped to drain  
connection.  
Copyright © 2008 Greenheck Fan Corp. • IGX-HV Rev. 2 October 2008 SN  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Heat Pump 3D150 User Manual
Grizzly Kitchen Utensil G5938 User Manual
Haier Refrigerator ZHBCN05FVS User Manual
HannsG Computer Monitor HW223DP User Manual
Harbor Freight Tools Automobile Parts 37792 User Manual
Heath Zenith Indoor Furnishings 598 1306 02 User Manual
Hotpoint Dishwasher DWF70 User Manual
Hotpoint Washer AQ113D 697 E User Manual
HP Hewlett Packard Nail Gun 7 SNMP User Manual
Husqvarna Trimmer 250PS User Manual