Goodman Mfg Air Conditioner A GPG13 M User Manual

INSTALLATION & OPERATING  
INSTRUCTIONS for  
A/GPG13 M SERIES W/R410A  
SINGLE PACKAGE GAS-ELECTRIC  
HEATING& COOLINGUNIT  
Affix this manual and Users Information Manual adjacent to the unit.  
®
US  
C
This Forced Air Central Unit Design Complies With  
Requirements Embodied in The American National  
Standard / National Standard of Canada Shown Below.  
ANSI Z21.47•CSA-2.3 Central Furnaces  
RECOGNIZE THIS SYMBOL AS A SAFETY PRECAUTION.  
ATTENTION INSTALLING PERSONNEL  
Prior to installation, thoroughly familiarize yourself with this Installation Manual. Observe all safety warnings. During  
installation or repair, caution is to be observed.  
It is your responsibility to install the product safely and to educate the customer on its safe use.  
These installation instructions cover the outdoor  
*NOTE: Please contact your distributor or  
installation of single package gas electric heating and  
our website for the applicable  
cooling units. See the Specification Sheet or Technical  
Specification Sheet or Technical Manual  
Manual applicable to your model* for information  
referred to in this manual.  
regarding accessories.  
Goodman Manufacturing Company, L.P.  
IO-357A  
3/10  
5151 San Felipe, Suite 500, Houston, TX 77056  
© 2009 - 2010 Goodman Manufacturing Company, L.P.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REPLACEMENT PARTS  
WARNING  
ORDERING PARTS  
DO NOT CONNECT TO OR USE ANY DEVICE THAT IS NOT DESIGN CERTIFIED  
BY GOODMAN FOR USE WITH THIS UNIT. SERIOUS PROPERTY DAMAGE,  
PERSONAL INJURY, REDUCED UNIT PERFORMANCE AND/OR HAZARDOUS  
CONDITIONS MAY RESULT FROM THE USE OF SUCH NON-APPROVED DEVICES.  
When reporting shortages or damages, or ordering repair  
parts, give the complete unit model and serial numbers as  
stamped on the unit’s nameplate.  
Replacement parts for this appliance are available through your  
contractor or local distributor. For the location of your nearest  
distributor, consult the white business pages, the yellow page  
section of the local telephone book or contact:  
SERVICE PARTS DEPARTMENT  
GOODMAN MANUFACTURING COMPANY, L.P.  
5151 SAN FELIPE, SUITE 500  
HOUSTON, TEXAS 77056  
(713) 861 – 2500  
SAFETY INSTRUCTIONS  
TO THE INSTALLER  
Before installing this unit, please read this manual to  
familiarize yourself on the specific items which must be  
adhered to, including maximum external static pressure to  
unit, air temperature rise, minimum or maximum CFM and  
motor speed connections.  
WARNING  
IMPORTANT NOTETO THE OWNERREGARDING PRODUCT WARRANTY  
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL TO SHUT OFF, TURN  
OFF THE MANUAL GAS SHUTOFF VALVE EXTERNAL TO THE FURNACE BEFORE  
TURNING OFF THE ELECTRICAL SUPPLY.  
Your warranty certificate is supplied as a separate document with  
the unit installed by your contractor. Read the limited warranty cer-  
tificate carefully to determine what is and is not covered and keep  
the warranty certificate in a safe place. If you are unable to locate  
the warranty certificate please contact your installing contractor or  
contact customer service (877-254-4729) to obtain a copy.  
IMPORTANT NOTICE TO GOODMAN® BRAND OWNERS:To receive  
the 10 Year Parts Limited Warranty, online registration must be  
completed within 60 days of installation. Online registration is not  
required in California or Quebec. Full warranty details available at  
WARNING  
THIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH  
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE  
STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER  
REPRODUCTIVE HARM.  
IMPORTANT NOTICE TOAMANA® BRAND OWNERS:To receive the  
Lifetime Heat Exchanger Limited Warranty and the 10 Years Parts  
Limited Warranty, online registration must be completed within 60  
days of installation. Online registration is not required in California  
To register your Goodman® brand unit, go to www.goodmanmfg.com.  
Click on the word “Warranty” located on the left side of the home  
page. Next, click on the word “Product Registration” located on the  
left side of the Warranty page and complete the forms in the man-  
ner indicated on the Product Registration page.  
To register your Amana® brand unit, go to www.amana-hac.com.  
Click on the word “Warranty” located on the top right of the home  
page. Next, click on the word “Product Registration” located on the  
left side of the Warranty page and complete the forms in the man-  
ner indicated on the Product Registration page.  
WARNING  
Product limited warranty certificates can be viewed at  
overview page contains a Product Warranty link; by clicking on it  
you will be able to view the limited warranty coverage for that spe-  
cific product. To view warranty registration information, click on the  
Product Warranty text on the left navigation panel on the home  
page of each website. The Online Product Registration pages are  
located in this same section.  
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DO NOT USE  
THIS UNIT IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A  
QUALIFIED SERVICE TECHNICIAN TO INSPECT THE FURNACE AND TO REPLACE  
ANY PART OF THE CONTROL SYSTEM AND ANY GAS CONTROL HAVING BEEN  
UNDER WATER.  
Keep this literature in a safe place for future reference.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT LOCATION  
WARNING  
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL  
T
INJURY OR DEATH, THE FOLLOWING BULLET POINTS MUST BE OBSERVED  
WHEN INSTALLING THE UNIT.  
ALL INSTALLATIONS:  
For proper flame pattern within the heat exchanger and  
proper condensate drainage, the unit must be mounted  
level.  
The flue outlet hood must be at least 12 inches from any  
opening through which flue gases could enter a building,  
and at least three feet above any forced air inlet located  
within ten feet. The economizer/manual fresh air intake/  
motorized fresh air intake and combustion air inlet  
mounted on the unit are not affected by this restriction.  
WARNING  
To avoid possible corrosion of the heat exchanger, do not  
locate the unit in an area where the outdoor air (i.e.  
combustion air for the unit) will be frequently contaminated  
by compounds containing chlorine or fluorine. Common  
sources of such compounds include swimming pool  
chemicals and chlorine bleaches, paint stripper,  
adhesives, paints, varnishes, sealers, waxes (which are  
not yet dried) and solvents used during construction and  
remodeling. Various commercial and industrial processes  
may also be sources of chlorine/fluorine compounds.  
TO PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,  
DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER  
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.  
To avoid possible illness or death of the building occupants,  
do NOT locate outside air intake device (economizer,  
manual fresh air intake, motorized fresh air intake) too close  
to an exhaust outlet, gas vent termination, or plumbing vent  
outlet. For specific distances required, consult local codes.  
Allow minimum clearances from the enclosure for fire  
protection, proper operation, and service access (see  
appendix). These clearances must be permanently  
maintained.  
The combustion air inlet and flue outlet hoods on the unit  
must never be obstructed. If used, do not allow the  
economizer/manual fresh air damper/ motorized fresh air  
damper to become blocked by snow or debris. In some  
climates or locations, it may be necessary to elevate the  
unit to avoid these problems.  
When the unit is heating, the temperature of the return air  
entering the unit must be between 50° F and 100° F.  
CARBON MONOXIDE POISONING HAZARD  
GROUND LEVEL INSTALLATIONS ONLY:  
Special Warning for Installation of Furnaces or Air Handling Units in  
Enclosed Areas such as Garages, Utility Rooms or Parking Areas  
When the unit is installed on the ground adjacent to the  
building, a level concrete (or equal) base is recommended.  
Prepare a base that is 3” larger than the package unit  
footprint and a minimum of 3” thick.  
Carbon monoxide producing devices (such as an automobile, space  
heater, gas water heater, etc.) should not be operated in enclosed areas  
such as unventilated garages, utility rooms or parking areas because of  
the danger of carbon monoxide (CO) poisoning resulting from the exhaust  
emissions. If a furnace or air handler is installed in an enclosed area such  
as a garage, utility room or parking area and a carbon monoxide producing  
device is operated therein, there must be adequate, direct outside  
ventilation.  
The base should also be located where no runoff of water  
from higher ground can collect in the unit.  
This ventilation is necessary to avoid the danger of CO poisoning which  
can occur if a carbon monoxide producing device continues to operate in  
the enclosed area. Carbon monoxide emissions can be (re)circulated  
throughout the structure if the furnace or air handler is operating in any  
mode.  
CO can cause serious illness including permanent brain damage or death.  
B10259-216  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOF CURB INSTALLATIONS ONLY:  
Sufficient structural support must be determined prior to  
locating and mounting the curb and package unit.  
Ductwork must be constructed using industry guidelines.  
The duct work must be placed into the roof curb before  
mounting the package unit.  
Curb insulation, cant strips, flashing and general roofing  
material are furnished by the contractor.  
OutsideSlabInstallation  
ROOFTOP INSTALLATIONS ONLY:  
NOTE: To ensure proper condensate drainage, unit must be  
installed in a level position.  
To avoid possible property damage or personal injury, the  
roof must have sufficient structural strength to carry the  
weight of the unit(s) and snow or water loads as required  
by local codes. Consult a structural engineer to determine  
the weight capabilities of the roof.  
RoofCurbInstallation  
GENERAL INFORMATION  
WARNING  
TO PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH, DUE TO FIRE,  
EXPLOSIONS, SMOKE, SOOT, CONDENSATION, ELECTRIC SHOCK OR CARBON  
MONOXIDE, THIS UNIT MUST BE PROPERLY INSTALLED, REPAIRED, OPERATED,  
AND MAINTAINED.  
This unit is approved for outdoor installation ONLY. To assure  
that your unit operates safely and efficiently, it must be installed,  
operated, and maintained in accordance with these installation  
and operating instructions, all local building codes and ordinances,  
or in their absence, with the latest edition of the National Fuel Gas  
Code NFPA54/ANSI Z223.1 and National Standard of Canada  
CAN/CSA B149 Installation Codes.  
RooftopInstallation  
The unit may be installed directly on wood floors or on  
Class A, Class B, or Class C roof covering material.  
To avoid possible personal injury, a safe, flat surface for  
service personnel should be provided.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
The heating and cooling capacities of the unit should be greater  
than or equal to the design heating and cooling loads of the area to  
be conditioned. The loads should be calculated by an approved  
method or in accordance with A.S.H.R.A.E. Guide or Manual J -  
Load Calculations published by the Air Conditioning Contractors  
of America.  
Obtain from:  
American National Standards Institute  
1430 Broadway  
New York, NY 10018  
TRANSPORTATION DAMAGE  
Check the carton upon arrival for external damage. If damage is  
found, a request for inspection by carrier agent should be made in  
writing immediately.  
Carefully inspect the unit for damage including damage to the  
cabinetry. Any bolts or screws which may have loosened in transit  
must be retightened. In the event of damage, the receiver should:  
1. Make notation on delivery receipt of any visible damage to  
shipment or container.  
Rigging  
2. Notify carrier promptly and request an inspection.  
3. In case of concealed damage, carrier should be notified  
as soon as possible-preferably within 5 days.  
4. File the claim with the following supporting documents:  
a. Original Bill of Lading, certified copy, or indemnity bond.  
b. Original paid freight bill or indemnity in lieu thereof.  
c. Original invoice or certified copy thereof, showing trade  
and other discounts or reductions.  
d. Copy of the inspection report issued by carrier  
representative at the time damage is reported to the  
carrier. The carrier is responsible for making prompt  
inspection of damage and for a thorough investigation of  
each claim. The distributor or manufacturer will not accept  
claims from dealers for transportation damage.  
GAS PIPING  
IMPORTANT NOTE: This unit is factory set to operate on natural  
gas at the altitudes shown on the rating plate.  
WARNING  
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH WHEN EITHER  
USING PROPANE GAS ALONE OR AT HIGHER ALTITUDES, OBTAIN AND INSTALL  
THE PROPER CONVERSION KIT(S). FAILURE TO DO SO CAN RESULT IN  
UNSATISFACTORY OPERATION AND/OR EQUIPMENT DAMAGE. HIGH ALTITUDE  
KITS ARE FOR U.S. INSTALLATIONS ONLY AND ARE NOT APPROVED FOR USE  
IN CANADA.  
The rating plate is stamped with the model number, type of gas and  
gas input rating. Make sure the unit is equipped to operate on the  
type of gas available. Conversion to LP gas is permitted with the  
use of the factory authorized conversion kit LPT-03. (LPT-00A may  
be used on models with AA revisions. LPT-03 is compatible with  
both the White Rodgers and the Honeywell gas valves.)  
NOTE: When inspecting the unit for transportation damage, remove  
all packaging materials. Recycle or dispose of the packaging ma-  
terial according to local codes.  
RIGGING DETAILS  
Inlet Gas Pressure  
Min. 5.0" W.C., Max. 10.0" W.C.  
WARNING  
Natural  
Propane  
Min. 11.0" W.C., Max. 13.0" W.C.  
TO PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT  
POSITION DURING ALL RIGGING AND MOVING OPERATIONS. TO FACILITATE  
LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN  
ADEQUATE CABLE SLING.  
Inlet Gas Pressure Must Not Exceed the Maximum Value Shown in Table  
Above.  
The minimum supply pressure should not vary from that shown in  
the table above because this could prevent the unit from having  
dependable ignition. In addition, gas input to the burners must not  
exceed the rated input shown on the rating plate. Overfiring of the  
unit could result in premature heat exchanger failure.  
Important: If using bottom discharge with roof curb, ductwork should  
be attached to the curb prior to installing the unit. Ductwork dimen-  
sions are shown in roof curb installation instructions.  
Refer to the Roof Curb Installation Instructions for proper curb in-  
stallation. Curbing must be installed in compliance with the National  
Roofing Contractors Association Manual.  
HIGH ALTITUDE DERATE (U.S. INSTALLATIONS ONLY)  
IMPORTANT NOTE: The gas/electric units naturally derate with al-  
titude. Do not attempt to increase the firing rate by changing ori-  
fices or increasing the manifold pressure. This can cause poor com-  
bustion and equipment failure. At all altitudes, the manifold pres-  
sure must be within 0.3 inches W.C. of that listed on the nameplate  
for the fuel used. At all altitudes and with either fuel, the air tempera-  
ture rise must be within the range listed on the unit nameplate.  
Refer to the Installation Manual provided with the LP kit for conver-  
sion from natural gas to propane gas and for altitude adjustments.  
NOTE: Up to 7,000 feet, no changes are required; above 7,000 feet,  
refer to High Altitude Kit HA-02.  
Lower unit carefully onto roof mounting curb. While rigging unit,  
center of gravity will cause condenser end to be lower than supply  
air end.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
PIPING  
IMPORTANT NOTE: To avoid possible unsatisfactory operation or  
equipment damage due to under firing of equipment, do not un-  
dersize the natural/propane gas piping from the meter/tank to the  
unit. When sizing a trunk line, include all appliances on that line  
that could be operated simultaneously.  
MANUAL  
SHUT-OFF  
VALVE  
The rating plate is stamped with the model number, type of gas  
and gas input rating. Make sure the unit is equipped to operate on  
the type of gas available. The gas line installation must comply  
with local codes, or in the absence of local codes, with the latest  
edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.  
DRIP LEG  
NaturalGasConnection  
Natural Gas Capacity of Pipe  
in Cubic Feet of Gas Per Hour (CFH)  
GROUND JOINT UNION  
(INSTALLED AHEAD OF GAS VALVE)  
Nominal Black Pipe Size (inches)  
Length of  
GROMMET  
Pipe in Feet  
1
1/2  
132  
92  
73  
63  
56  
50  
46  
43  
40  
38  
3/4  
278  
190  
152  
130  
115  
105  
96  
1
1/4  
1050  
730  
590  
500  
440  
400  
370  
350  
320  
305  
1
1/2  
1600  
1100  
980  
760  
670  
610  
560  
530  
490  
460  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
Proper Piping Practice  
NOTE: The unit gas supply entrance is factory sealed with plugs.  
Keep plugs in place until gas supply is ready to be installed. Once  
ready, replace the plugs with the supplied grommets and install gas  
supply line.  
90  
84  
79  
Pressure = .50 PSIG or less and Pressure Drop of 0.3" W.C. (Based  
on 0.60 Specific Gravity Gas)  
GAS PIPING CHECKS  
BTUH Furnace Input  
CFH =  
Heating Value of Gas (BTU/Cubic Foot)  
CAUTION  
Refer to the Proper Piping Practice drawing for the general layout  
at the unit. The following rules apply:  
1. Use black iron pipe and fittings for the supply piping. The  
use of a flex connector and/or copper piping is permitted  
as long as it is in agreement with local codes.  
2. Use pipe joint compound on male threads only. Pipe joint  
compound must be resistant to the action of the fuel used.  
3. Use ground joint unions.  
4. Install a drip leg to trap dirt and moisture before it can enter  
the gas valve. The drip leg must be a minimum of three  
inches long.  
5. Use two pipe wrenches when making connection to the gas  
valve to keep it from turning.  
6. Install a manual shut-off valve in a convenient location  
(within six feet of unit) between the meter and the unit.  
7. Tighten all joints securely.  
TO PREVENT PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, THE  
FOLLOWING INSTRUCTIONS MUST BE PERFORMED REGARDING GAS  
CONNECTIONS AND PRESSURE TESTING:  
THE UNIT AND ITS GAS CONNECTIONS MUST BE LEAK TESTED BEFORE  
PLACING IN OPERATION. BECAUSE OF THE DANGER OF EXPLOSION OR  
FIRE, NEVER USE A MATCH OR OPEN FLAME TO TEST FOR LEAKS. NEVER  
EXCEED SPECIFIED PRESSURES FOR TESTING. HIGHER PRESSURE MAY  
DAMAGE GAS VALVE AND CAUSE OVERFIRING WHICH MAY RESULT IN  
PREMATURE HEAT EXCHANGE FAILURE.  
THIS UNIT AND ITS SHUT-OFF VALVE MUST BE DISCONNECTED FROM  
THE GAS SUPPLY DURING ANY PRESSURE TESTING OF THAT SYSTEM AT  
TEST PRESSURES IN EXCESS OF 1/2 PSIG (3.48 KPA).  
THIS UNIT MUST BE ISOLATED FROM THE GAS SUPPLY SYSTEM BY  
CLOSING ITS MANUAL SHUT-OFF VALVE DURING ANY PRESSURE  
TESTING OF THE GAS SUPPLY PIPING SYSTEM AT TEST PRESSURES  
EQUAL TO OR LESS THAN 1/2 PSIG (3.48 KPA).  
8. The unit must be connected to the building piping by one  
of the following methods:  
WARNING  
Rigid metallic pipe and fittings  
Semirigid metallic tubing and metallic fittings (Aluminum  
alloy tubing must not be used in exterior locations)  
, BE SURE THERE IS  
TO AVOID PROPERTY DAMAGE OR PERSONAL INJURY  
NO OPEN FLAME IN THE VICINITY DURING AIR BLEEDING.  
Listed gas appliance connectors used in accordance with  
the terms of their listing that are completely in the same  
room as the equipment  
In the prior two methods above the connector or tubing  
must be protected from physical and thermal damage.  
Aluminum alloy tubing and connectors must be coated to  
protect against external corrosion when in contact with  
masonry, plaster or insulation or are subject to repeated  
wettings by liquids (water - not rain water, detergents or  
sewage)  
There will be air in the gas supply line after testing for leaks  
on a new installation. Therefore, the air must be bled from the  
line by loosening the ground joint union until pure gas is  
expelled. Tighten union and wait for five minutes until all gas  
has been dissipated in the air. Be certain there is no open  
flame in the vicinity during air bleeding procedure. The unit is  
placed in operation by closing the main electrical disconnect  
switch for the unit.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Sizing Between First and Second Stage Regulator  
Maximum Propane Capacities listed are based on 1 PSIG Pressure Drop at 10  
PSIG Setting. Capacities in 1,000 BTU/HR  
PROPANE GAS INSTALLATIONS  
PIPE OR  
NOMINAL PIPE SIZE,  
SCHEDULE 40  
WARNING  
TUBING  
LENGTH,  
FEET  
TUBING SIZE, O.D., TYPE L  
3/8"  
1/2"  
5/8"  
3/4"  
7/8"  
1/2"  
3/4"  
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE  
30  
40  
309  
700  
1,303  
2,205  
3,394  
1,843  
3,854  
OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS  
265  
235  
213  
196  
182  
171  
161  
130  
111  
90  
599  
531  
481  
446  
412  
386  
365  
293  
251  
222  
201  
185  
172  
1,115  
988  
896  
824  
767  
719  
679  
546  
467  
414  
378  
345  
321  
1,887  
1,672  
1,515  
1,394  
1,297  
1,217  
1,149  
923  
2,904  
2,574  
2,332  
2,146  
1,996  
1,873  
1,769  
1,421  
1,216  
1,078  
976  
1,577  
1,398  
1,267  
1,165  
1,084  
1,017  
961  
3,298  
2,923  
2,649  
2,437  
2,267  
2,127  
2,009  
1,613  
1,381  
1,224  
1,109  
1,020  
949  
DETECTING WARNING DEVICE. INCE RUST CAN REDUCE THE LEVEL  
S
50  
OF ODORANT IN PROPANE GAS, A GAS DETECTING WARNING DEVICE  
60  
IS THE ONLY RELIABLE WAY TO DETECT A PROPANE GAS LEAK.  
70  
ONTACT A LOCAL PROPANE GAS SUPPLIER ABOUT INSTALLING A  
C
80  
GAS DETECTING WARNING DEVICE.  
90  
100  
150  
200  
250  
300  
350  
400  
IMPORTANT NOTE: Propane gas conversion kits must be  
installed to convert units to propane gas.  
772  
790  
660  
All propane gas equipment must conform to the safety  
standards of the National Board of Fire Underwriters (See NBFU  
Manual 58).  
For satisfactory operation, propane gas supply pressure must  
be within 9.7 - 10.3 inches W.C. at the manifold with all gas  
appliances in operation. Maintaining proper gas pressure  
depends on three main factors:  
1. Vaporization rate, which depends on (a) temperature of the  
liquid, and (b) wetted surface area of the container or  
containers.  
700  
585  
89  
634  
530  
82  
584  
898  
488  
76  
543  
836  
454  
To convert to Capacities at 15 PSIG Settings -- Multiply by 1.130  
To convert to Capacities at 5 PSIG Settings -- Multiply by 0.879  
Sizing Between Single or Second Stage Regulator and Appliance*  
Maximum Propane Capacities Listed are Based on 1/2" W.C. Pressure Drop at  
11" W.C. Setting. Capacities in 1,000 BTU/HR  
PIPE OR  
NOMINAL PIPE SIZE,  
SCHEDULE 40  
TUBING SIZE, O.D., TYPE L  
TUBING  
LENGTH,  
FEET  
2. Proper pressure regulation.  
3/8"  
1/2"  
5/8"  
3/4"  
7/8"  
1/2"  
3/4"  
1"  
1-1/4"  
1-1/2"  
3. Pressure drop in lines between regulators, and between  
second stage regulator and the appliance. Pipe size  
required will depend on length of pipe run and total load of  
all appliances.  
10  
20  
49  
110  
206  
348  
539  
291  
608  
1,146  
2,353  
3,525  
34  
27  
23  
20  
19  
16  
14  
12  
11  
10  
9
76  
61  
52  
46  
42  
36  
32  
28  
26  
22  
19  
18  
16  
15  
141  
114  
97  
86  
78  
67  
59  
52  
48  
41  
36  
33  
30  
28  
239  
192  
164  
146  
132  
113  
100  
89  
368  
296  
253  
224  
203  
174  
154  
137  
124  
106  
94  
200  
161  
137  
122  
110  
94  
418  
336  
284  
255  
231  
198  
175  
155  
141  
120  
107  
97  
788  
632  
541  
480  
436  
372  
330  
292  
265  
227  
201  
182  
167  
156  
1,617  
1,299  
1,111  
985  
2,423  
1,946  
1,665  
1,476  
1,337  
1,144  
1,014  
899  
30  
40  
50  
TANKS AND PIPING  
60  
892  
80  
764  
Complete information regarding tank sizing for vaporization,  
recommended regulator settings and pipe sizing is available  
from most regulator manufacturers and propane gas suppliers.  
100  
125  
150  
200  
250  
300  
350  
400  
84  
677  
74  
600  
80  
67  
544  
815  
Since propane gas will quickly dissolve white lead or most  
standard commercial compounds, special pipe dope must be  
used. Shellac base compounds resistant to the actions of  
liquefied petroleum gases such as Gasolac®, Stalactic®,  
Clyde’s® or John Crane® are satisfactory.  
69  
58  
465  
697  
61  
51  
412  
618  
8
55  
85  
46  
374  
560  
7
51  
78  
43  
89  
344  
515  
7
47  
73  
40  
83  
320  
479  
*DATA IN ACCORDANCE WITH NFPA PAMPHLET NO. 54  
See below for typical propane gas piping.  
Table 3 - Propane Gas Pipe Sizing  
WARNING  
5 to 15 PSIG  
First Stage  
Regulator  
(20 PSIG Max.)  
Continuous  
11" W.C.  
TO PREVENT PROPERTY DAMAGE OR SERIOUS PERSONAL INJURY DUE TO  
FIRE OR EXPLOSION CAUSED BY A PROPANE GAS LEAK, INSTALL A GAS  
DETECTING WARNING DEVICE.  
200 PSIG  
Maximum  
Second Stage  
Regulator  
IF THE PROPANE GAS UNIT IS INSTALLED IN AN EXCAVATED AREA OR A  
CONFINED SPACE, A WARNING DEVICE IS REQUIRED DUE TO:  
PROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN  
SETTLE IN ANY LOW AREAS OR CONFINED SPACES.  
PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE  
EXCEPT WITH A WARNING DEVICE.  
Typical Propane Gas Piping  
ELECTRICAL WIRING  
THERMOSTAT LOCATION  
Mount the thermostat approximately five feet above the floor,  
in an area that has an inside, vibration-free wall and has good  
air circulation.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Movement of air must not be obstructed by furniture, door,  
draperies, etc. The thermostat must not be mounted where it  
will be affected by drafts, hot or cold water pipes or air ducts in  
walls, radiant heat from fireplace, lamps, the sun, television,  
etc. Consult the Instruction Sheet packaged with thermostat  
for mounting instructions.  
CAUTION  
TO PREVENT IMPROPER AND DANGEROUS OPERATION DUE TO WIRING ERRORS,  
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.  
VERIFY PROPER OPERATION AFTER SERVICING.  
All units have one stage of heating and one stage of  
mechanical cooling. Units which will have economizers may  
use thermostats with one or two stages of cooling.  
For unit protection, use a time delay fuse or HACR circuit  
breaker that is in excess of the circuit ampacity, but less than  
or equal to the maximum overcurrent protection device. DO  
NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE  
SHOWN ON UNIT DATAPLATE.  
All line voltage connections must be made through  
weatherproof fittings. All exterior power supply and ground  
wiring must be in approved weatherproof conduit. Low voltage  
wiring from the unit control panel to the thermostat requires  
coded cable. See below for ground level and rooftop wiring.  
Note:Junction box location  
shown is optional and is  
for illustration purposes only.  
The units are designed for operation on 60 hertz current and  
at voltages as shown on the rating plate. All internal wiring in  
the unit is complete. It is necessary to bring in the power supply  
to the contactor as shown on the unit wiring diagram which is  
supplied with each unit. 24 volt wiring must be connected  
between the unit control panel and the room thermostat.  
JUNCTION BOX  
0 0 4 - A 3 8 - 6 8 1 0  
1 8 9 - 1 8 B 0 9  
K4  
K3  
Electrical Power Directly To Junction Box  
K2  
K1  
R
C R Y W G  
Y
W
LOW VOLTAGE  
CONNECTOR  
F1  
G
FUSE 3 AMPMAX  
120  
135  
150  
P3  
P2  
T2  
T1  
C22  
Low Voltage Wiring  
Electrical Power Routed Through Bottom of Unit  
Typical Electrical Wiring Unit Voltage  
Refer to the unit wiring diagram for electrical connections.  
When installed, the unit must be electrically grounded in  
accordance with local codes or in the absence of local codes,  
with the National Electrical Code, ANSI/NFPA No. 70, and/or  
the CSA C22.1 Electrical Code. Ensure low voltage  
connections are waterproof.  
UNIT VOLTAGE  
The unit transformer is factory connected for 230V operation.  
If the unit is to operate on 208V, reconnect the transformer  
primary lead as shown on the unit wiring diagram.  
HEAT ANTICIPATOR SETTING  
WARNING  
The heat anticipator is to be set by measuring the load  
(amperage) at the “R” circuit. Follow the instructions provided  
by the thermostat for more details.  
TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE  
POLARIZED AND GROUNDED.  
CAUTION  
O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE  
T
ONLY COPPER CONDUCTORS.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
DownDischargeApplications  
Cut insulation around bottom openings and remove panels  
from the bottom of the unit, saving the screws holding the  
panels in place.  
NOTE: Single phase models require installation of horizontal  
duct kit #20464501PDGK (medium chassis) and  
#20464502PDGK (large chassis).  
G
Y
R
W
DUCTWORK  
Duct systems and register sizes must be properly designed  
for the C.F.M. and external static pressure rating of the unit.  
Ductwork should be designed in accordance with the  
recommended methods of Air Conditioning Contractors of  
America Manual D (Residential) or Manual Q (Commercial).  
All ductwork exposed to the outdoors must include a  
weatherproof barrier and adequate insulation.  
A duct system should be installed in accordance with  
Standards of the National Board of Fire Underwriters for the  
Installation of Air Conditioning, Warm Air Heating and  
Ventilating Systems. Pamphlets No. 90A and 90B.  
The supply duct from the unit through a wall may be installed  
without clearance. However, minimum unit clearances as  
shown in the appendix must be maintained. The supply duct  
should be provided with an access panel large enough to  
inspect the air chamber downstream of the heat exchanger.  
A cover should be tightly attached to prevent air leaks.  
R
W
From  
Unit  
Y
G
Typical Thermostat and Unit 24 V Wiring Hookup  
CIRCULATING AIR AND FILTERS  
AIRFLOW CONVERSION  
Units can easily be converted from horizontal to down-  
discharge airflow delivery. In down-discharge or high static  
installations, the installer should measure the total external  
static and review the blower performance charts before  
performing the installation. In some installations it will be  
necessary to change the blower speed to provide proper air  
flow.  
For duct flange dimensions on the unit refer to the Unit  
Dimension illustration in the appendix.  
For down-discharge applications, the ductwork should be  
attached to the roof curb prior to installing the unit. Ductwork  
dimensions are shown in the roof curb installation manual.  
Horizontal Air Flow (Applies to 3 phase models)  
Single phase models are shipped without horizontal duct  
covers. If needed, these kits may be ordered through  
Goodman’s Service Parts department.  
Remove supply and return duct covers which are attached to  
the unit as shown below.  
If desired, supply and return duct connections to the unit may  
be made with flexible connections to reduce possible unit  
operating sound transmission.  
FILTERS  
CAUTION  
TO PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF  
EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT  
BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR  
FILTER INSTALLED IN THE RETURN AIR SYSTEM.  
Even though a return air filter is not supplied with this unit,  
there must be a means of filtering all return air. All units may  
be externally filtered.  
Remove these covers  
for horizontal duct  
applications  
Refer to the unit filter size chart in the appendix for filter size  
information.  
Filters installed external to the unit should be sized in  
accordance with their manufacturer recommendations. A  
throwaway filter must be sized for a maximum face velocity of  
300 feet per minute.  
FilterInstallation  
Important: When installing a filter, the air flow arrows on the  
filter must point toward the circulator blower.  
DuctCoverInstallation  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENTING  
2. The spark igniter and gas valve energizes for 7 seconds.  
NOTE: The igniter produces a very intense electrical spark  
that ignites the gas.  
3. The 30-second HEAT FAN ON delay time begins.  
4. The unit delivers heat to the conditioned space until the  
thermostat is satisfied.  
5. The gas valve deenergizes. The induced draft blower  
continues operation for a 29-second post-purge.  
6. Ignition control begins timing the HEAT FAN OFF delay.  
There is an adjustable HEAT FAN OFF delay of  
approximately 120/135/150 seconds (factory set at 150).  
After the HEAT FAN OFF delay time has elapsed, the blower  
will deenergize. This allows any additional heat in the  
heat exchanger to be transferred to the conditioned space.  
NOTE: Venting is self-contained. Do not modify or block.  
FLUE HOOD INSTALLATION  
Install the exhaust flue hood and combustion air intake hood  
prior to operation of the unit.  
To install the flue hood cover, please refer to IO-653*, included  
in the flue hood assembly box located in the blower  
compartment.  
COOLING  
1. Thermostat calls for cooling. The compressor and outdoor  
fan are energized.  
2. Approximately seven seconds later, the indoor fan starts.  
3. The unit will deliver cooling to the conditioned space until  
the thermostat is satisfied.  
4. The compressor and outdoor fan will be de-energized  
when the thermostat opens.  
5. The indoor fan continues to run for approximately 60  
seconds after the thermostat is satisfied. This allows  
additional cooling from the indoor coil to be transferred to  
the conditioned space. Then, the indoor fan stops.  
NOTE: A 180-second anti-short cycle is integral to the control and  
prevents recycling of the compressor.  
FAN ONLY  
1. Thermostat calls for FAN ONLY by energizing “G”.  
2. Approximately seven seconds later, the indoor fan starts.  
3. The indoor fan continues to run for approximately 60  
seconds after “G” is de-energized.  
FlueHoodandBugScreenInstallation  
CONDENSATE DRAIN  
STARTUP, ADJUSTMENTS, AND CHECKS  
CONDENSATE DRAIN CONNECTION  
A 3/4” NPT drain connection is supplied for condensate piping. An  
external trap must be installed for proper condensate drainage.  
NOTE: Maximum torque is 10 in-lbs.  
HEATING STARTUP  
This unit is equipped with an electronic ignition device to  
automatically light the main burners. It also has a power vent  
blower to exhaust combustion products.  
DRAIN  
CONNECTION  
On new installations, or if a major component has been  
replaced, the operation of the unit must be checked.  
UNIT  
2" MINIMUM  
Check unit operation as outlined in the following instructions.  
If any sparking, odors, or unusual sounds are encountered,  
shut off electrical power and recheck for wiring errors, or  
obstructions in or near the blower motors. Duct covers must  
be removed before operating unit.  
FLEXIBLE  
TUBING-HOSE  
OR PIPE  
3" MINIMUM  
A POSITIVE LIQUID  
SEAL IS REQUIRED  
HeatAnticipatorSetting  
Set the heat anticipator on the room thermostat to 0.4 amps  
to obtain the proper number of heating cycles per hour and to  
prevent the room temperature from overshooting the room  
thermostat setting.  
DrainConnection  
NORMAL SEQUENCES OF OPERATION  
RolloutProtectionControl  
HEATING  
The rollout protection device opens, cutting power to the gas  
valve, if the flames from the burners are not properly drawn  
into the heat exchanger. The rollout protection device is located  
on the burner bracket. The reason for elevated temperatures  
at the control should be determined and repaired prior to  
resetting this manual reset control.  
This unit is equipped with an ignition control that automatically  
lights the main burner. DO NOT attempt to light the main  
burners by any other method.  
1. Thermostat calls for heat. The induced draft blower  
energizes for a 15-second pre-purge.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Smell for gas, including near the ground. This is important  
because some types of gas are heavier than air. If you  
have waited five minutes and you do smell gas,  
immediately follow the warnings on page 3 of this manual.  
If having waited for five minutes and no gas smell is noted,  
move the gas control valve switch to the ON position.  
9. Replace the heat exchanger door on the side of the unit.  
10. Open the manual gas valve external to the unit.  
11. Turn on the electrical power supply to the unit.  
12. Set the thermostat to desired setting.  
WARNING  
TO AVOID PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE  
OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIGATE THE REASON FOR  
THE ROLLOUT PROTECTION DEVICE TO OPEN BEFORE MANUALLY RESETTING  
THE ROLLOUT PROTECTION DEVICE.  
Rollout Protection  
OUTLET  
INLET  
Gas Valve  
On/Off  
Selector  
Switch  
Rollout Protection on Burner Bracket  
SecondaryLimitControl  
The secondary limit control is located on the top of the blower  
scroll assembly. This control opens when elevated  
temperatures are sensed. Elevated temperatures at the  
control are normally caused by blower failure. The reason for  
the opening should be determined and repaired prior to  
resetting.  
If the power to the unit is interrupted during the heating cycle,  
it may cause the secondary limit to trip. Once the blower  
compartment temperature drops below the limit reset  
temperature, the limit will automatically reset.  
White-Rodgers 36G22  
Pressure Regulator  
(under cap screw)  
Inlet  
Pressure  
Tap  
Outlet  
Pressure  
Tap  
Secondary  
Control Limit  
Gas Valve On/Off  
Selector Switch  
Honeywell Model VR8215 (Single-Stage)  
GasSupplyAndManifoldCheck  
Gas supply pressure and manifold pressure with the burners  
operating must be as specified on the rating plate.  
GAS SUPPLY PRESSURE MEASUREMENT  
Back of Unit  
CAUTION  
SecondaryLimitControl  
Pre-Operation Checks  
TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE  
INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT  
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES  
OPERATING.  
1. Close the manual gas valve external to the unit.  
2. Turn off the electrical power supply to the unit.  
3. Set the room thermostat to its lowest possible setting.  
4. Remove the heat exchanger door on the side of the unit by  
removing screws.  
5. This unit is equipped with an ignition device which  
automatically lights the main burner. DO NOT try to light  
burner by any other method.  
6. Move the gas control valve switch to the OFF position. Do  
not force.  
7. Wait five minutes to clear out any gas.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The line pressure supplied to the gas valve must be within the  
range specified in the chart on the next page. The supply pressure  
can be measured at the gas valve inlet pressure tap or at a hose  
fitting installed in the gas piping drip leg. The supply pressure  
must be measured with the unit OFF. To measure inlet pressure,  
use the following procedure.  
8. Measure the gas supply pressure with burners firing. Adjust  
supply pressure using the Inlet Gas Supply Pressure table  
shown below. If supply pressure reading differs from the  
table, make necessary adjustments to pressure regulator,  
gas piping size, etc., and/or consult with local gas utility.  
Inlet Gas Supply Pressure  
Gas Valve  
On/Off  
Selector  
Natural Gas  
Minimum:5.0" W.C. Maximum :10.0" W.C.  
Propane Gas Minimum:11.0" W.C. Maximum :13.0" W.C.  
Inlet Pressure  
Switch  
9. Turn OFF all electrical power and gas supply to the system.  
10.Remove the manometer hose from the hose barb fitting  
or inlet pressure boss.  
Tap  
11. Replace inlet pressure tap:  
a. Honeywell VR8215 valve:  
INLET  
OUTLET  
Remove the 1/8” NPT hose barb fitting from the inlet  
pressure tap. Replace the inlet pressure boss plug and  
seal with a high quality thread sealer.  
Pressure Regulator  
Adjustment  
(Under Cap Screw)  
b. White-Rodgers 36G22 valve:  
Outlet Pressure  
Tap  
Turn inlet pressure test screw in to seal pressure port  
(clockwise, 7 in-lb minimum).  
12.Retest for leaks. If bubbles form, SHUT DOWN GAS AND  
REPAIR LEAKS IMMEDIATELY.  
White-Rodgers Model 36G22  
13.Turn ON electrical power and gas supply to the system.  
14.Turn valve switch ON.  
Pressure Regulator  
(under cap screw)  
Inlet  
Pressure  
Tap  
Outlet  
Pressure  
Tap  
GAS MANIFOLD PRESSURE MEASUREMENT AND ADJUSTMENT  
CAUTION  
TO PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE, THE  
INLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT  
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES  
OPERATING.  
Gas Valve On/Off  
Selector Switch  
Honeywell Model VR8215 (Single-Stage)  
1. Turn OFF gas to furnace at the manual gas shutoff valve  
external to the furnace.  
2. Turn OFF all electrical power to the system.  
3. Inlet pressure tap connections:  
a. Honeywell VR8215 Valve:  
Remove the inlet pressure boss plug. Install an 1/8” NPT  
hose barb fitting into the outlet pressure tap.  
b. White-Rodgers 36G22 valve:  
This valve is shipped from the factory with the regulator preset  
(see control label).  
Consult the appliance rating plate to ensure burner manifold pres-  
sure is as specified. If another outlet pressure is required, follow  
these steps.  
Back inlet pressure test screw (inlet pressure boss) out  
one turn (counterclockwise, not more than one turn).  
4. Attach a hose and manometer to the outlet pressure barb  
fitting (Honeywell valve) or inlet pressure boss (White-  
Rodgers valve).  
1. Turn OFF gas to furnace at the manual gas shutoff valve  
external to the furnace.  
2. Turn OFF all electrical power to the system.  
3. Outlet pressure tap connections:  
a. Honeywell VR8215 valve:  
Remove the outlet pressure boss plug. Install an 1/8”  
NPT hose barb fitting into the outlet pressure tap.  
b. White-Rodgers 36G22 valve:  
Back outlet pressure test screw (outlet pressure boss)  
out one turn (counterclockwise, not more than one turn).  
4. Attach a hose and manometer to the outlet pressure barb  
fitting (Honeywell valve) or outlet pressure boss (White-  
Rodgers valve).  
5. Turn ON the gas supply.  
6. Turn On power and close thermostat “R” and “W” contacts  
to provide a call for heat.  
7. Using a leak detection solution or soap suds, check for  
leaks at outlet pressure boss plug (Honeywell valve) or  
screw (White-Rodgers valve). Bubbles forming indicate a  
leak. SHUT OFF GAS AND REPAIR ALL LEAKS  
IMMEDIATELY!  
5. Turn ON the gas supply.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Turn ON power and close thermostat “R” and “W” contacts  
to provide a call for heat.  
Temperature Rise Check  
Check the temperature rise through the unit by placing  
thermometers in supply and return air registers as close to  
the unit as possible. Thermometers must not be able to  
sample temperature directly from the unit heat exchangers,  
or false readings could be obtained.  
1. All registers must be open; all duct dampers must be in  
their final (fully or partially open) position and the unit  
operated for 15 minutes before taking readings.  
2. The temperature rise must be within the range specified  
on the rating plate.  
NOTE: Air temperature rise is the temperature difference between  
supply and return air.  
With a properly designed system, the proper amount of  
temperature rise will normally be obtained when the unit is  
operated at rated input with the recommended blower speed.  
If the correct amount of temperature rise is not obtained, it  
may be necessary to change the blower speed. A higher  
blower speed will lower the temperature rise. A slower blower  
speed will increase the temperature rise.  
NOTE: Blower speed MUST be set to give the correct air tempera-  
ture rise through the unit as marked on the rating plate.  
7. Using a leak detection solution or soap suds, check for  
leaks at outlet pressure boss plug (Honeywell valve) or  
screw (White-Rodgers valve). Bubbles forming indicate a  
leak. SHUT OFF GAS AND REPAIR ALL LEAKS  
IMMEDIATELY!  
8. Measure the gas manifold pressure with burners firing.  
Adjust manifold pressure using the Manifold Gas Pressure  
table shown below.  
Manifold Gas Pressure  
Natural Gas  
3.5" w.c.  
Propane Gas  
10.0" w.c.  
9. Remove regulator cover screw from the outlet pressure  
regulator and turn screw clockwise to increase pressure  
or counterclockwise to decrease pressure. Replace  
regulator cover screw.  
10.Turn OFF all electrical power and gas supply to the system.  
11. Remove the manometer hose from the hose barb fitting  
or outlet pressure boss.  
12.Replace outlet pressure tap:  
a. Honeywell VR8215 valve:  
External Static Pressure Check  
Remove the 1/8” NPT hose barb fitting from the outlet  
pressure tap. Replace the outlet pressure boss plug and  
seal with a high quality thread sealer.  
The total external static pressure must be checked on this  
unit to determine if the airflow is proper.  
Blower Speed Adjustments  
b. White-Rodgers 36G22 valve: Turn outlet pressure test  
screw in to seal pressure port (clockwise, 7 in-lb  
minimum).  
WARNING  
13.Turn ON electrical power and gas supply to the system.  
14.Close thermostat contacts to provide a call for heat.  
15.Retest for leaks. If bubbles form, SHUT OFF GAS AND  
REPAIRALLLEAKS IMMEDIATELY!  
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK, REMOVE  
ELECTRICAL POWER FROM THE UNIT BEFORE CHANGING SPEED TAPS ON THE  
BLOWER MOTOR.  
Refer to the wiring diagram in the appendix to verify speed tap  
settings.  
Gas Input (Natural Gas Only) Check  
For models equipped with PSC type motors, blower speeds  
are to be changed at the ignition control board. Both heat  
speed and cool speed terminals are supplied on the board  
along with two unused motor lead terminals.  
To measure the gas input use a gas meter and proceed as  
follows:  
1. Turn off gas supply to all other appliances except the unit.  
2. With the unit operating, time the smallest dial on the meter  
for one complete revolution. If this is a 2 cubic foot dial,  
divide the seconds by 2; if it is a 1 cubic foot dial, use the  
seconds as is. This gives the seconds per cubic foot of  
gas being delivered to the unit.  
3. INPUT=GAS HTG VALUE x 3600 / SEC. PER CUBIC FOOT  
Example: Natural gas with a heating value of 1000 BTU per cubic  
foot and 34 seconds per cubic foot as determined by Step 2, then:  
Input = 1000 x 3600 / 34 = 106,000 BTU per Hour. NOTE:  
BTU content of the gas should be obtained from the gas  
supplier. This measured input must not be greater than  
shown on the unit rating plate.  
Some models are equipped with X-13 motors. X-13 motors  
are constant torque motors with very low power consumption.  
This motor is energized by 24V. Adjust the CFM for the unit by  
changing the 24V low voltage leads to the speed terminal  
block on the motor.  
Heating-White Lead  
T1 - Low Speed  
Cooling-Yellow Lead  
T4 - Low Speed  
T2 - Medium Speed  
T3 - High Speed  
T5 - High Speed  
4. Relight all other appliances turned off in step 1. Be sure all  
pilot burners are operating.  
NOTE: Heating airflow must be adjusted to provide the tempera-  
ture rise shown on rating plate.  
Main Burner Flame Check  
Flames should be stable, soft and blue (dust may cause  
orange tips but they must not be yellow) and extending directly  
outward from the burner without curling, floating or lifting off.  
Limit Check  
Check limit control operation after 15 minutes of operation  
by blocking the return air grille(s).  
1. After several minutes the main burners must go OFF.  
Blower will continue to run.  
2. Remove air restrictions and main burners will relight  
after a cool down period of a few minutes.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Adjust the thermostat setting below room temperature.  
1. Main burners must go OFF.  
2. Circulating Air Blower will continue to run for 120, 135 or  
150 seconds, depending on the setting.  
To ensure the unit is properly charged for the intended  
application, check the unit refrigerant superheat at the  
compressor. The refrigerant superheat is a function of outdoor  
ambient temperature and return air temperature of the  
conditioned space. It is the installing contractors responsibility  
to ensure the proper refrigerant superheat at the compressor  
is adjusted for each application. For example, 10 degree  
refrigerant superheat level is adequate for a 95 degree outdoor  
ambient temperature and a 78 - 80 degree for indoor return  
air temperature. As the outdoor ambient temperature rises  
the superheat decreases and as the outdoor ambient  
temperature lowers the superheat increases. Proper  
superheat adjustment optimizes cooling performance.  
1
R 3  
K 1  
7
C 2  
D 7  
D 5  
R 2  
0
R 1  
R 8  
5
D 3  
R 3  
K 2  
3
C 1  
8
2
9
R 2  
D 9  
D 1  
R 2  
Z1  
0
4
R 3  
R 3  
5
R 3  
0
C 2  
K 3  
K 4  
CoolingOperation  
4
D 1  
R 4  
1
R 1  
R 4  
2
2
6
D 1  
1
D 1  
NOTE: Mechanical cooling cannot be reliably provided at ambient  
R 3  
temperatures below 50° F.  
D
L E  
1068-83-400A  
1. Turn on the electrical power supply to the unit.  
2. Place the room thermostat selector switch in the COOL  
position (or AUTO if available, and if automatic changeover  
from cooling to heating is desired).  
ControlBoard(Top)  
NOTE: If necessary, adjust fan OFF delay settings to obtain satis-  
factory comfort level.  
3. Set the room thermostat to the desired temperature.  
TROUBLESHOOTING  
IGNITION CONTROL ERROR CODES  
The following presents probable causes of questionable unit  
operation. Refer to Diagnostic Indicator Chart for an  
interpretation of the signal and to this section for an explanation.  
UnitShutdown  
Remove the control box access panel and note the number of  
diagnostic LED flashes. Refer to Diagnostic Indicator Chart  
for an interpretation of the signal and to this section for an  
explanation.  
1. Set the thermostat to lowest setting.  
2. Turn off the electrical power supply to the unit.  
3. Remove the heat exchanger door on the side of the unit by  
removing screws.  
4. Move the gas control valve switch to the OFF position. Do  
not force.  
ABNORMAL OPERATION - HEATING  
InternalControlFailure  
5. Close manual gas shutoff valve external to the unit.  
6. Replace the heat exchanger door on the unit.  
7. If cooling and/or air circulation will be desired, turn ON the  
electrical power.  
If the integrated ignition control in this unit encounters an  
internal fault, it will go into a “hard” lockout and turn off the  
diagnostic LED. If diagnostic LED indicates an internal fault,  
check power supply to unit for proper voltage, check all fuses,  
circuit breakers and wiring. Disconnect electric power for five  
seconds. If LED remains off after restoring power, replace  
control.  
COOLING STARTUP  
NOTE: Check all manual reset limit controls in heating circuit if  
cooling mode does not operate.  
External Lockout  
Compressor Protection Devices  
An external lockout occurs if the integrated ignition control  
determines that a measurable combustion cannot be  
established within three (3) consecutive ignition attempts. If  
flame is not established within the seven (7) second trial for  
ignition, the gas valve is de-energized, 15 second inter-purge  
cycle is completed, and ignition is reattempted. The control  
will repeat this routine three times if a measurable combustion  
is not established. The control will then shut off the induced  
draft blower and go into a lockout state.  
If flame is established but lost, the control will energize the  
circulator blower at the heat speed and then begin a new ignition  
sequence. If flame is established then lost on subsequent  
attempts, the control will recycle for four (4) consecutive  
ignition attempts (five attempts total) before locking out.  
The compressor includes components which are designed  
to protect the compressor against abnormal operating  
conditions.  
WARNING  
O PREVENT PERSONAL INJURY OR DEATH, ALWAYS DISCONNECT ELECTRICAL  
T
POWER BEFORE INSPECTING OR SERVICING THE UNIT. ALL COMPRESSOR  
PROTECTION DEVICES RESET AUTOMATICALLY, ENERGIZING THE CONTACTOR  
AND OUTDOOR FAN.  
CoolingRefrigerantCharging  
Check unit charge before putting the cooling section into full  
operation. The unit is factory charged with R-410A for nominal  
air flow and static pressure conditions. The unit has a piston  
flowrator expansion device.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The diagnostic fault code is 1 flash for a lockout due to failed  
ignition attempts or flame dropouts. The integrated control  
will automatically reset after one hour, or it can be reset by  
removing the thermostat signal or disconnecting the electrical  
power supply for over five seconds. If the diagnostic LED  
indicates an external lockout, perform the following checks:  
Flame Detected with Gas Valve Closed  
If flame is detected with the gas valve de-energized, the  
combustion and air circulator blowers are energized. The  
diagnostic fault code is five (5) flashes for this condition. The  
control can be reset by removing the power supply to the unit  
or it will automatically reset after one hour. Miswiring is the  
probable cause for this fault.  
Check the supply and manifold pressures  
Check the gas orifices for debris  
Check gas valve for proper operation  
ABNORMAL OPERATION - COOLING  
Check secondary limit  
A dirty filter, excessive duct static, insufficient air flow, a  
faulty limit, or a failed circulator blower can cause this  
limit to open. Check filters, total external duct static,  
circulator blower motor, blower motor speed tap (see  
wiring diagram), and limit. An interruption in electrical  
power during a heating cycle may also cause the  
auxiliary limit to open. The automatic reset secondary  
limit is located on top of the circulator blower assembly.  
Check rollout limit  
If the burner flames are not properly drawn into the heat  
exchanger, the flame rollout protection device will open.  
Possible causes are restricted or blocked flue passages,  
blocked or cracked heat exchanger, a failed induced  
draft blower, or insufficient combustion air. The rollout  
protection device is a manual reset limit located on the  
burner bracket. The cause of the flame rollout must be  
determined and corrected before resetting the limit.  
Check flame sensor  
Short Cycle Compressor Delay  
The automatic ignition control has a built-in feature that  
prevents damage to the compressor in short cycling  
situations. In the event of intermittent power losses or  
intermittent thermostat operation, the ignition control will delay  
output to the compressor contactor for three minutes from the  
time power is restored. (Compressor is off a total of three  
minutes). The diagnostic LED will flash six (6) times to indicate  
the compressor contactor output is being delayed.  
NOTE: Some electronic thermostats also have a built-in  
compressor short cycle timer that may be longer than the three  
minute delay given above. If you are using an electronic thermostat  
and the compressor has not started after three minutes, wait an  
additional five minutes to allow the thermostat to complete its short  
cycle delay time.  
MAINTENANCE  
A drop in flame signal can be caused by nearly invisible  
coating on the sensor. Remove the sensor and carefully  
clean with steel wool.  
Check wiring  
Check wiring for opens/shorts and miswiring.  
Important: If you have to frequently reset your gas/electric  
package unit, it means that a problem exists that should be  
corrected. Contact a qualified servicer for further  
information.  
Pressure Switch Stuck Open  
Have the gas heating section of the unit checked at least  
once a year before the heating season begins, to be sure that  
the combustion air inlet and flue outlet hoods are not blocked  
by debris, which would prevent adequate combustion air and  
a properly operating vent system.  
A pressure switch stuck open can be caused by a faulty  
pressure switch, faulty wiring, a disconnected or damaged  
hose, a blocked or restricted flue, or a faulty induced draft  
blower.  
If the control senses an open pressure switch during the pre-  
purge cycle, the induced draft blower only will be energized. If  
the pressure switch opens after ignition has begun the gas  
valve is de-energized, the circulator blower heat off cycle  
begins, and the induced draft blower remains on. The  
diagnostic fault code is two flashes.  
FILTER REPLACEMENT OR CLEANING  
A return air filter is not supplied with this unit; however, there  
must be a means of filtering all of the return air. The filter(s)  
may be located in the return air duct(s), or return air filter  
grille(s). Consult with your installing dealer for the actual  
location of the return air filter(s) for your unit.  
Pressure Switch Stuck Closed  
A stuck closed pressure switch can be caused by a faulty  
pressure switch or faulty wiring. If the control encounters a  
pressure switch stuck closed, the induced draft blower remains  
off. The diagnostic LED code for this fault is three (3) flashes.  
Dirty filters are the most common cause of inadequate heating  
or cooling performance. Filter inspection should be made at  
least every two months; more often if necessary because of  
local conditions and usage.  
Dirty throwaway filters should be discarded and replaced with  
a new, clean filter. Dirty permanent filters should be washed  
with water, thoroughly dried and sprayed with a filter adhesive  
before being reinstalled. (Filter adhesives may be found at  
many hardware stores.) Permanent filters should last several  
years. However, should one become torn or uncleanable, it  
should be replaced.  
Open Thermal Protection Device  
If the primary limit switch opens, the gas valve is immediately  
de-energized, the induced draft and air circulating blowers  
are energized. The induced draft and air circulator blowers  
remain energized until the limit switch recloses. The  
diagnostic fault code for an open limit is four (4) flashes.  
A primary limit will open due to excessive supply air  
temperatures. This can be caused by a dirty filter, excessive  
duct static, insufficient air flow, or a faulty limit. Check filters,  
total external duct static, blower motor, blower motor speed  
tap (see wiring diagram), and limit. This limit will automatically  
reset once the temperature falls below a preset level.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. When all heat exchanger tubes have been cleaned, replace  
the parts in the reverse order in which they were removed.  
6. To reduce the chances of repeated fouling of the heat  
exchanger, perform the steps listed in “Startup,  
Adjustments, and Checks”.  
CABINET FINISH MAINTENANCE  
Use a fine grade automotive wax on the cabinet finish to  
maintain the finish’s original high luster. This is especially  
important in installations with extended periods of direct  
sunlight.  
MAIN BURNER FLAME (QUALIFIED SERVICER ONLY)  
CLEAN OUTSIDE COIL (QUALIFIED SERVICER ONLY)  
Flames should be stable, soft and blue (dust may cause  
orange tips but must not be yellow). The flames must extend  
directly outward from the burner without curling, floating or  
lifting off.  
The coil with the outside air flowing over it should be inspected  
annually and cleaned as frequently as necessary to keep the  
finned areas free of lint, hair and debris.  
CONDENSER, EVAPORATOR, AND INDUCED DRAFT MOTORS  
Bearings on the air circulating blower motor, condenser motor  
and the combustion fan motor are permanently lubricated.  
No additional oiling is required.  
FLAME SENSOR (QUALIFIED SERVICER ONLY)  
Check the burner flames for:  
1. Good adjustment  
2. Stable, soft and blue  
A drop in the flame current can be caused by a nearly invisible  
coating on the flame sensor. This coating, created by the fuel  
or combustion air supply, can be removed by carefully  
cleaning the flame sensor with steel wool.  
3. Not curling, floating, or lifting off.  
NOTE: After cleaning, the microamp signal should be stable and  
in the range of 4 - 6 microamps DC.  
Burner Flame  
WARNING  
Flame  
Sensor  
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK,  
DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS OR ATTEMPT ANY  
ADJUSTMENT. CONTACT A QUALIFIED SERVICER AT ONCE IF AN ABNORMAL  
FLAME SHOULD DEVELOP.  
At least once a year, prior to or during the heating season,  
make a visual check of the burner flames.  
NOTE: This will involve removing and reinstalling the heat exchanger  
door on the unit, which is held by two screws. If you are uncertain  
about your ability to do this, contact a qualified servicer.  
If a strong wind is blowing, it may alter the airflow pattern within the  
unit enough that an inspection of the burner flames is not pos-  
sible.  
Flame Sensor  
CLEANING BURNERS  
FLUE PASSAGES (QUALIFIED SERVICER ONLY)  
1. Shut off electric power and gas supply to the unit.  
2. Remove the screws securing the manifold to the burner  
retention bracket. Remove the manifold and rotate each  
burner counterclockwise to remove.  
At the start of each heating season, inspect and, if necessary,  
clean the unit flue passage.  
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)  
Burner  
1. Shut off electric power and gas supply to the unit.  
2. Remove burner assembly by disconnecting the gas line  
and removing the manifold bracket from the partition  
panel.  
3. Remove the flue from the induced draft blower and the  
collector box cover from the partition panel.  
Burner  
Bracket  
4. The primary heat exchanger tubes can be cleaned using  
a round wire brush attached to a length of high grade  
stainless steel cable, such as drain cleanout cable. Attach  
a variable speed reversible drill to the other end of the  
spring cable. Slowly rotate the cable with the drill and  
insert it into one of the primary heat exchanger tubes.  
While reversing the drill, work the cable in and out several  
times to obtain sufficient cleaning. Use a large cable for  
the large tube, and then repeat the operation with a small  
cable for the smaller tube. Repeat for each tube.  
Manifold  
ManifoldAssembly  
3. Remove the burners.  
4. Use a bottle brush to clean burner insert and inside of the  
burners.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Replace burners and manifold, inspect the burner  
assembly for proper seating of burners in retention slots.  
FUNCTIONAL PARTS  
6. Reconnect electrical power and gas supply.  
FUNCTIONAL PARTS  
Auxiliary Limit Switch  
Blower Housing  
Circulator Blower Motor  
Blower Wheel  
Flame Roll-out Switch  
Flame Sensor  
Gas Orifice  
CAUTION  
LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.  
WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION.  
Gas Valve  
Burner  
Capacitor  
Compressor  
Heat Exchanger  
High Limit Switch  
Igniter  
CAUTION  
Condenser Coil  
Condenser Fan Blade  
Condenser Fan Motor  
Contactor  
Gas Manifold  
Evaporator Coil  
Ignition Control  
Induced Draft Blower  
Pressure Switch  
Pressure Switch Hose  
Transformer  
ALWAYS VERIFY PROPER OPERATION AFTER SERVICING.  
For further information on the yearly inspection, consult the  
User Manual. It is recommended that a qualified servicer  
inspect and service the unit at least once each year.  
Turn the unit on at the thermostat. Wait a few minutes, since  
any dislodged dust will alter the normal flame appearance.  
Flames should be predominantly blue and directed into the  
tubes. They should not be yellow. They should extend directly  
outward from the burner ports without curling downward,  
floating or lifting off the ports.  
Functional Parts List  
GENERAL INFORMATION  
1. Refer to the description in Functional Parts List when  
ordering any of the listed functional parts. Be sure to provide  
the unit model and serial numbers with the order.  
2. Although only functional parts are shown, all sheet metal  
parts, doors, etc. may be ordered by description.  
ACCESSORIES AND FUNCTIONAL PARTS  
SHEET METAL ACCESSORIES  
Additional accessories can be purchased to fit specific application  
needs. Parts and instructions are available from your distributor.  
3. Parts are available from your distributor.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA - SINGLE PHASE  
*PG1324045M41A* - Rise Range: 30° - 60°  
MEDIUM  
Unit  
Static  
LOW  
WATTS  
HIGH  
WATTS  
CFM  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
600  
570  
510  
450  
380  
150  
140  
130  
125  
120  
--------  
--------  
--------  
0.67  
0.65  
0.63  
0.61  
0.58  
57  
60  
850  
830  
765  
715  
660  
610  
--------  
--------  
230  
220  
215  
210  
205  
195  
--------  
--------  
1.02  
1.00  
0.97  
0.94  
0.90  
0.88  
--------  
40  
41  
45  
48  
52  
56  
NR  
1,190  
1,140  
1,080  
1,025  
975  
920  
830  
730  
380  
360  
350  
340  
330  
310  
300  
1.67  
1.62  
1.58  
1.54  
1.38  
1.37  
1.35  
NR  
NR  
32  
33  
35  
37  
41  
NR  
NR  
NR  
NR  
NR  
--------  
--------  
--------  
--------  
--------  
CFM  
--------  
AMPS  
NR  
--------  
NR  
290  
1.32  
47  
*PG1324070M41A* - Rise Range: 35° - 65°  
MEDIUM  
RISE  
Unit  
Static  
LOW  
HIGH  
WATTS  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
600  
570  
510  
450  
380  
--------  
--------  
--------  
150  
140  
130  
125  
120  
--------  
--------  
--------  
0.67  
0.65  
0.63  
0.61  
0.58  
--------  
--------  
--------  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
850  
830  
765  
715  
660  
610  
--------  
--------  
230  
220  
215  
210  
205  
195  
--------  
--------  
1.02  
1.00  
0.97  
0.94  
0.90  
0.88  
--------  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
1,190  
1,140  
1,080  
1,025  
975  
920  
830  
730  
380  
360  
350  
340  
330  
310  
300  
1.67  
1.62  
1.58  
1.54  
1.38  
1.37  
1.35  
43  
45  
47  
50  
52  
56  
62  
NR  
--------  
NR  
290  
1.32  
NR  
*PG1330045M41A* - Rise Range: 30° - 60°  
MEDIUM  
Unit  
LOW  
HIGH  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,056  
1,010  
971  
937  
878  
811  
723  
545  
350  
339  
343  
329  
318  
306  
291  
1.51  
1.43  
1.45  
1.41  
1.27  
1.29  
1.21  
33  
34  
36  
37  
39  
43  
48  
1,261  
1,221  
1,174  
1,125  
1,063  
1,004  
919  
452  
442  
428  
414  
398  
380  
368  
1.95  
1.90  
1.84  
1.80  
1.70  
1.66  
1.59  
NR  
NR  
NR  
31  
32  
34  
1,370  
1,310  
1,262  
1,208  
1,140  
1,081  
1,006  
509  
492  
489  
475  
453  
440  
425  
2.23  
2.13  
2.09  
2.06  
1.93  
1.90  
1.88  
NR  
NR  
NR  
NR  
30  
32  
34  
39  
38  
43  
259  
1.10  
NR  
796  
371  
1.46  
879  
403  
1.74  
*PG133070M41A* - Rise Range: 35° -65°  
MEDIUM  
LOW  
HIGH  
Unit  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,056  
1,010  
971  
937  
878  
811  
723  
545  
350  
339  
343  
329  
318  
306  
291  
259  
1.51  
1.43  
1.45  
1.41  
1.27  
1.29  
1.21  
1.10  
49  
51  
53  
55  
59  
64  
NR  
NR  
1,261  
1,221  
1,174  
1,125  
1,063  
1,004  
919  
452  
442  
428  
414  
398  
380  
368  
371  
1.95  
1.90  
1.84  
1.80  
1.70  
1.66  
1.59  
1.46  
41  
42  
44  
46  
49  
52  
56  
65  
1,370  
1,310  
1,262  
1,208  
1,140  
1,081  
1,006  
879  
509  
492  
489  
475  
453  
440  
425  
403  
2.23  
2.13  
2.09  
2.06  
1.93  
1.90  
1.88  
1.74  
38  
40  
41  
43  
45  
48  
NR  
NR  
796  
NR = Heating Temperature Rise Not Recommended.  
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,  
external static pressure should not exceed 0.5" w.c.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA - SINGLE PHASE  
*PG1336045M41A* - Rise Range: 30 -60°  
Unit  
Static  
LOW  
WATTS  
MEDIUM  
HIGH  
CFM  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,029  
982  
946  
888  
823  
750  
668  
346  
334  
329  
313  
304  
287  
271  
1.51  
1.46  
1.40  
1.38  
1.29  
1.23  
1.16  
34  
35  
36  
39  
42  
46  
52  
1,337  
1,265  
1,227  
1,159  
1,073  
1,008  
895  
471  
452  
448  
429  
405  
393  
371  
2.08  
2.01  
1.97  
1.87  
1.73  
1.71  
1.61  
NR  
NR  
NR  
30  
32  
34  
1,462  
1,398  
1,326  
1,260  
1,188  
1,090  
997  
596  
563  
550  
534  
513  
496  
478  
2.64  
2.58  
2.50  
2.42  
2.34  
2.22  
2.18  
NR  
NR  
NR  
NR  
NR  
32  
39  
45  
35  
40  
454  
238  
1.00  
NR  
760  
346  
1.49  
852  
454  
2.12  
*PG1336070M41A* - Rise Range: 35° -65°  
MEDIUM  
Unit  
LOW  
HIGH  
Static  
CFM  
1,029  
982  
946  
888  
823  
750  
668  
454  
WATTS  
346  
334  
329  
313  
304  
287  
271  
238  
AMPS  
1.51  
1.46  
1.40  
1.38  
1.29  
1.23  
1.16  
1.00  
RISE  
50  
53  
55  
58  
CFM  
1,337  
1,265  
1,227  
1,159  
1,073  
1,008  
WATTS  
471  
452  
448  
429  
405  
393  
371  
346  
AMPS  
2.08  
2.01  
1.97  
1.87  
1.73  
1.71  
RISE  
39  
41  
42  
45  
48  
51  
58  
68  
CFM  
1,462  
1,398  
1,326  
1,260  
1,188  
WATTS  
596  
563  
550  
534  
513  
496  
478  
454  
AMPS  
2.64  
2.58  
2.50  
2.42  
2.34  
2.22  
2.18  
2.12  
RISE  
35  
37  
39  
41  
44  
47  
52  
61  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
63  
NR 1,090  
NR  
NR  
895  
760  
1.61  
1.49  
997  
852  
*PG1336090M41A* - Rise Range: 45° -75°  
MEDIUM  
Unit  
LOW  
HIGH  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,029  
982  
946  
888  
823  
750  
668  
346  
334  
329  
313  
304  
287  
271  
1.51  
1.46  
1.40  
1.38  
1.29  
1.23  
1.16  
50  
53  
55  
58  
63  
69  
NR  
1,337  
1,265  
1,227  
1,159  
1,073  
1,008  
895  
471  
452  
448  
429  
405  
393  
371  
2.08  
2.01  
1.97  
1.87  
1.73  
1.71  
1.61  
NR  
NR  
NR  
45  
48  
51  
1,462  
1,398  
1,326  
1,260  
1,188  
1,090  
997  
596  
563  
550  
534  
513  
496  
478  
2.64  
2.58  
2.50  
2.42  
2.34  
2.22  
2.18  
NR  
NR  
NR  
NR  
NR  
47  
58  
68  
52  
61  
454  
238  
1.00  
NR  
760  
346  
1.49  
852  
454  
2.12  
*PG1342070M41A* - Rise Range: 35° - 65°  
MEDIUM  
Unit  
Static  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
LOW  
HIGH  
CFM  
1,100  
1,040  
1,000  
925  
860  
800  
690  
--------  
WATTS  
340  
AMPS  
1.55  
RISE  
46  
CFM  
1,450  
1,390  
1,300  
1,215  
1,115  
1,030  
945  
WATTS  
480  
AMPS  
2.15  
2.06  
1.98  
1.89  
1.79  
1.71  
1.60  
1.54  
RISE  
35  
CFM  
1,575  
1,515  
1,430  
1,340  
1,240  
1,130  
1,010  
910  
WATTS  
585  
AMPS  
2.64  
2.58  
2.50  
2.42  
2.34  
2.22  
2.18  
2.12  
RISE  
NR  
NR  
36  
38  
41  
45  
51  
56  
325  
320  
305  
290  
275  
255  
--------  
1.49  
1.44  
1.38  
1.32  
1.22  
1.16  
--------  
49  
460  
37  
565  
550  
525  
505  
465  
450  
430  
51  
445  
39  
42  
55  
425  
46  
59  
395  
64  
375  
50  
NR  
NR  
350  
335  
54  
59  
0.8  
860  
*PG1342090M41A* - Rise Range: 45° - 75°  
MEDIUM  
Unit  
LOW  
HIGH  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,100  
1,040  
1,000  
925  
860  
800  
340  
325  
320  
305  
290  
275  
255  
1.55  
1.49  
1.44  
1.38  
1.32  
1.22  
1.16  
62  
66  
68  
1,450  
1,390  
1,300  
1,215  
1,115  
1,030  
945  
480  
460  
445  
425  
395  
375  
350  
2.15  
2.06  
1.98  
1.89  
1.79  
1.71  
1.60  
47  
49  
52  
56  
61  
66  
72  
NR  
1,575  
1,515  
1,430  
1,340  
1,240  
1,130  
1,010  
585  
565  
550  
525  
505  
465  
450  
2.64  
2.58  
2.50  
2.42  
2.34  
2.22  
2.18  
NR  
45  
48  
51  
55  
60  
67  
75  
74  
NR  
NR  
NR  
690  
--------  
--------  
--------  
NR  
860  
335  
1.54  
910  
430  
2.12  
NR = Heating Temperature Rise Not Recommended.  
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,  
external static pressure should not exceed 0.5" w.c.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA - SINGLE PHASE  
*PG1348070M41A* - Rise Range: 35° - 65°  
T2 HEATING SPEED  
Unit  
T1 HEATING SPEED  
T3 HEATING SPEED  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
914  
822  
733  
664  
606  
584  
--------  
125  
134  
140  
150  
154  
162  
--------  
1.07  
1.14  
1.20  
1.26  
1.28  
1.32  
--------  
56  
62  
--------  
1,105  
1,024  
967  
884  
816  
--------  
186  
193  
202  
214  
220  
230  
--------  
1.56  
1.60  
1.65  
1.76  
1.75  
1.85  
--------  
46  
50  
53  
58  
62  
66  
73  
--------  
1,397  
1,346  
1,288  
1,273  
1,178  
1,120  
--------  
323  
331  
342  
352  
359  
369  
--------  
2.57  
2.67  
2.76  
2.82  
2.88  
2.97  
--------  
NR  
NR  
NR  
NR  
NR  
45  
69  
NR  
NR  
NR  
769  
698  
48  
551  
164  
1.34  
NR  
236  
1.89  
1,057  
381  
3.09  
Unit  
T4 COOLING SPEED  
T5 COOLING SPEED  
Static  
CFM  
WATTS  
AMPS  
CFM  
WATTS  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
1,593  
1,545  
1,506  
1,448  
1,400  
1,341  
--------  
449  
463  
476  
481  
493  
502  
--------  
3.55  
3.69  
3.82  
3.87  
3.95  
4.00  
--------  
1,669  
1,654  
1,610  
1,545  
1,512  
1,433  
--------  
532  
239  
551  
557  
566  
578  
--------  
4.22  
4.25  
4.30  
4.36  
4.41  
4.59  
1289  
511  
4.11  
1,392  
591  
4.65  
*PG1348090M41A* - Rise Range: 45° - 75°  
T2 HEATING SPEED  
Unit  
T1 HEATING SPEED  
T3 HEATING SPEED  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
914  
822  
733  
664  
606  
584  
--------  
125  
134  
140  
150  
154  
162  
--------  
1.07  
1.14  
1.20  
1.26  
1.28  
1.32  
--------  
75  
--------  
1,105  
1,024  
967  
884  
816  
--------  
186  
193  
202  
214  
220  
230  
--------  
1.56  
1.60  
1.65  
1.76  
1.75  
1.85  
--------  
62  
67  
--------  
1,397  
1,346  
1,288  
1,273  
1,178  
1,120  
--------  
323  
331  
342  
352  
359  
369  
--------  
2.57  
2.67  
2.76  
2.82  
2.88  
2.97  
--------  
49  
51  
53  
54  
58  
61  
65  
NR  
NR  
NR  
NR  
NR  
71  
NR  
NR  
NR  
NR  
769  
698  
551  
164  
1.34  
NR  
236  
1.89  
1,057  
381  
3.09  
Unit  
T4 COOLING SPEED  
T5 COOLING SPEED  
Static  
CFM  
WATTS  
--------  
449  
463  
476  
481  
493  
502  
511  
AMPS  
CFM  
WATTS  
--------  
532  
239  
551  
557  
566  
578  
591  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
1,593  
1,545  
1,506  
1,448  
1,400  
1,341  
1289  
--------  
3.55  
3.69  
3.82  
3.87  
3.95  
4.00  
4.11  
--------  
1,669  
1,654  
1,610  
1,545  
1,512  
1,433  
1,392  
--------  
4.22  
4.25  
4.30  
4.36  
4.41  
4.59  
4.65  
*PG13480115M41A* - Rise Range: 45° - 75°  
T2 HEATING SPEED  
Unit  
T1 HEATING SPEED  
T3 HEATING SPEED  
Static  
CFM  
--------  
914  
822  
733  
664  
606  
584  
551  
WATTS  
--------  
125  
134  
140  
150  
154  
162  
164  
AMPS  
--------  
1.07  
1.14  
1.20  
1.26  
1.28  
1.32  
1.34  
RISE  
--------  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
CFM  
--------  
1,105  
1,024  
967  
884  
816  
769  
698  
WATTS  
--------  
186  
193  
202  
214  
220  
230  
236  
AMPS  
--------  
1.56  
1.60  
1.65  
1.76  
1.75  
1.85  
1.89  
RISE  
--------  
77  
NR  
NR  
NR  
NR  
NR  
NR  
CFM  
--------  
1,397  
1,346  
1,288  
1,273  
1,178  
1,120  
1,057  
WATTS  
--------  
323  
331  
342  
352  
359  
369  
381  
AMPS  
--------  
2.57  
2.67  
2.76  
2.82  
2.88  
2.97  
3.09  
RISE  
--------  
61  
63  
66  
67  
72  
NR  
NR  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
Unit  
T4 COOLING SPEED  
T5 COOLING SPEED  
Static  
CFM  
WATTS  
--------  
449  
463  
476  
481  
493  
502  
511  
AMPS  
CFM  
WATTS  
--------  
532  
239  
551  
557  
566  
578  
591  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
1,593  
1,545  
1,506  
1,448  
1,400  
1,341  
1289  
--------  
3.55  
3.69  
3.82  
3.87  
3.95  
4.00  
4.11  
--------  
1,669  
1,654  
1,610  
1,545  
1,512  
1,433  
1,392  
--------  
4.22  
4.25  
4.30  
4.36  
4.41  
4.59  
4.65  
NR = Heating Temperature Rise Not Recommended.  
NOTE: The shaded area indicates ranges in excess of  
maximum external static pressure allowable when  
heating. For satisfactory operation, external static  
pressure should not exceed 0.5" w.c.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA - SINGLE PHASE  
*PG136090M41A* - Rise Range: 45° - 75°  
T2 HEATING SPEED  
Unit  
T1 HEATING SPEED  
T3 HEATING SPEED  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,125  
1,049  
1,000  
910  
857  
809  
162  
168  
178  
184  
197  
201  
207  
1.44  
1.53  
1.60  
1.64  
1.75  
1.83  
1.86  
61  
65  
69  
1,466  
1,384  
1,347  
1,291  
1,237  
1,185  
1,134  
315  
322  
329  
341  
350  
362  
369  
2.67  
2.74  
2.78  
2.83  
2.90  
3.05  
3.09  
47  
50  
51  
53  
55  
58  
60  
63  
1,780  
1,730  
1,664  
1,608  
1,568  
1,515  
1,477  
496  
506  
520  
526  
532  
546  
552  
3.33  
3.89  
4.01  
4.03  
4.12  
4.14  
4.18  
NR  
NR  
NR  
NR  
NR  
45  
75  
NR  
NR  
NR  
739  
703  
46  
48  
218  
1.96  
NR  
1,087  
382  
3.21  
1,422  
562  
4.23  
Unit  
T4 COOLING SPEED  
T5 COOLING SPEED  
Static  
CFM  
WATTS  
649  
657  
670  
675  
683  
693  
703  
705  
AMPS  
CFM  
WATTS  
792  
811  
814  
808  
798  
772  
763  
732  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,942  
1,883  
1,859  
1,827  
1,749  
1,706  
1,655  
1,588  
4.83  
4.87  
4.96  
4.97  
4.99  
5.10  
5.12  
5.11  
2,067  
2,030  
1,982  
1,909  
1,842  
1,789  
1,703  
1,618  
5.81  
5.85  
5.88  
5.86  
5.85  
5.65  
5.58  
5.29  
*PG1360115M41A* - Rise Range: 45° - 75°  
T2 HEATING SPEED  
Unit  
T1 HEATING SPEED  
T3 HEATING SPEED  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,125  
1,049  
1,000  
910  
857  
809  
162  
168  
178  
184  
197  
201  
207  
1.44  
1.53  
1.60  
1.64  
1.75  
1.83  
1.86  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
1,466  
1,384  
1,347  
1,291  
1,237  
1,185  
1,134  
315  
322  
329  
341  
350  
362  
369  
2.67  
2.74  
2.78  
2.83  
2.90  
3.05  
3.09  
58  
62  
63  
66  
69  
72  
NR  
NR  
1,780  
1,730  
1,664  
1,608  
1,568  
1,515  
1,477  
496  
506  
520  
526  
532  
546  
552  
3.33  
3.89  
4.01  
4.03  
4.12  
4.14  
4.18  
48  
49  
51  
53  
54  
56  
58  
60  
739  
703  
218  
1.96  
NR  
1,087  
382  
3.21  
1,422  
562  
4.23  
Unit  
T4 COOLING SPEED  
T5 COOLING SPEED  
Static  
CFM  
WATTS  
649  
657  
670  
675  
683  
693  
703  
705  
AMPS  
CFM  
WATTS  
792  
811  
814  
808  
798  
772  
763  
732  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,942  
1,883  
1,859  
1,827  
1,749  
1,706  
1,655  
1,588  
4.83  
4.87  
4.96  
4.97  
4.99  
5.10  
5.12  
5.11  
2,067  
2,030  
1,982  
1,909  
1,842  
1,789  
1,703  
1,618  
5.81  
5.85  
5.88  
5.86  
5.85  
5.65  
5.58  
5.29  
*PG1360140M41A* - Rise Range: 45° - 75°  
T2 HEATING SPEED  
Unit  
T1 HEATING SPEED  
T3 HEATING SPEED  
Static  
CFM  
1,125  
1,049  
1,000  
910  
857  
809  
739  
703  
WATTS  
162  
168  
178  
184  
197  
201  
207  
218  
AMPS  
1.44  
1.53  
1.60  
1.64  
1.75  
1.83  
1.86  
1.96  
RISE  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
CFM  
1,466  
1,384  
1,347  
1,291  
1,237  
1,185  
1,134  
1,087  
WATTS  
315  
322  
329  
341  
350  
362  
369  
382  
AMPS  
2.67  
2.74  
2.78  
2.83  
2.90  
3.05  
3.09  
3.21  
RISE  
71  
CFM  
1,780  
1,730  
1,664  
1,608  
1,568  
1,515  
1,477  
1,422  
WATTS  
496  
506  
520  
526  
532  
546  
552  
562  
AMPS  
3.33  
3.89  
4.01  
4.03  
4.12  
4.14  
4.18  
4.23  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
59  
60  
63  
65  
67  
69  
71  
74  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
Unit  
T4 COOLING SPEED  
T5 COOLING SPEED  
Static  
CFM  
WATTS  
649  
657  
670  
675  
683  
693  
703  
705  
AMPS  
CFM  
WATTS  
792  
811  
814  
808  
798  
772  
763  
732  
AMPS  
NR = Heating Temperature Rise Not Recommended.  
NOTE: The shaded area indicates ranges in excess of  
maximum external static pressure allowable when  
heating. For satisfactory operation, external static  
pressure should not exceed 0.5" w.c.  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,942  
1,883  
1,859  
1,827  
1,749  
1,706  
1,655  
1,588  
4.83  
4.87  
4.96  
4.97  
4.99  
5.10  
5.12  
5.11  
2,067  
2,030  
1,982  
1,909  
1,842  
1,789  
1,703  
1,618  
5.81  
5.85  
5.88  
5.86  
5.85  
5.65  
5.58  
5.29  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA - HEATING SPEEDS THREE PHASE  
GPG1336090M43A* - Rise Range: 45° - 75°  
Unit  
Static  
LOW  
WATTS  
MEDIUM  
HIGH  
CFM  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1100  
1037  
991  
926  
831  
773  
669  
-
342  
335  
320  
308  
290  
279  
260  
-
1.57  
1.52  
1.45  
1.39  
1.32  
1.25  
1.17  
-
62  
66  
69  
74  
NR  
NR  
NR  
-
1469  
1409  
1327  
1257  
1163  
1094  
942  
494  
480  
459  
442  
419  
398  
363  
-
2.24  
2.15  
2.08  
2.00  
1.89  
1.80  
1.65  
-
47  
49  
52  
55  
59  
63  
73  
-
1655  
1579  
1483  
1407  
1329  
1210  
1036  
-
604  
587  
567  
547  
522  
498  
464  
-
2.67  
2.68  
2.62  
2.53  
2.44  
2.35  
2.24  
-
NR  
NR  
46  
49  
52  
57  
66  
-
-
GPG1348090M43A* - Rise Range: 45° - 75°  
T2 HEATING SPEED  
T1 HEATING SPEED  
T3 HEATING SPEED  
Unit  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
914  
822  
733  
664  
606  
584  
551  
--------  
125  
134  
140  
150  
154  
162  
164  
--------  
1.07  
1.14  
1.20  
1.26  
1.28  
1.32  
1.34  
--------  
75  
--------  
1,105  
1,024  
967  
884  
816  
--------  
186  
193  
202  
214  
220  
230  
236  
--------  
1.56  
1.60  
1.65  
1.76  
1.75  
1.85  
1.89  
--------  
62  
67  
--------  
1,397  
1,346  
1,288  
1,273  
1,178  
1,120  
1,057  
--------  
323  
331  
342  
352  
359  
369  
381  
--------  
2.57  
2.67  
2.76  
2.82  
2.88  
2.97  
3.09  
--------  
49  
51  
53  
54  
58  
61  
65  
NR  
NR  
NR  
NR  
NR  
NR  
71  
NR  
NR  
NR  
NR  
769  
698  
GPG1360090M43A* - Rise Range: 45° - 75°  
MEDIUM - T2  
Unit  
LOW - T1  
HIGH - T3  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1125  
1049  
1000  
910  
857  
809  
162  
168  
178  
184  
197  
201  
207  
218  
1.44  
1.53  
1.60  
1.64  
1.75  
1.83  
1.86  
1.96  
61  
65  
69  
75  
80  
85  
93  
1466  
1384  
1347  
1291  
1237  
1185  
1134  
1087  
315  
322  
329  
341  
350  
362  
369  
382  
2.67  
2.74  
2.78  
2.83  
2.9  
3.05  
3.09  
3.21  
47  
50  
51  
53  
55  
58  
60  
1780  
1730  
1664  
1608  
1568  
1515  
1477  
1422  
496  
506  
520  
526  
532  
546  
552  
562  
3.33  
3.89  
4.01  
4.03  
4.12  
4.14  
4.18  
4.23  
NR  
NR  
NR  
NR  
NR  
45  
739  
703  
46  
48  
97  
63  
GPG1360140M43A* - Rise Range: 45° - 75°  
MEDIUM - T2  
Unit  
LOW - T1  
HIGH - T3  
Static  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
CFM  
WATTS  
AMPS  
RISE  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1125  
1049  
1000  
910  
857  
809  
162  
168  
178  
184  
197  
201  
207  
218  
1.44  
1.53  
1.6  
1.64  
1.75  
1.83  
1.86  
1.96  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
1466  
1384  
1347  
1291  
1237  
1185  
1134  
1087  
315  
322  
329  
341  
350  
362  
369  
382  
2.67  
2.74  
2.78  
2.83  
2.9  
3.05  
3.09  
3.21  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
1780  
1730  
1664  
1608  
1568  
1515  
1477  
1422  
496  
506  
520  
526  
532  
546  
552  
562  
3.33  
3.89  
4.01  
4.03  
4.12  
4.14  
4.18  
4.23  
59  
60  
63  
65  
67  
69  
71  
739  
703  
NR  
NR  
72  
NR = Heating Temperature Rise Not Recommended.  
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,  
external static pressure should not exceed 0.5" w.c.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER PERFORMANCE DATA - COOLING SPEEDS THREE PHASE  
GPG1336***M43A* - COOLING SPEEDS  
Unit  
HIGH (Cooling Speed)  
MEDIUM (Cooling Speed)  
LOW (Cooling Speed)  
Static  
CFM  
Watts  
RPM  
Amps  
CFM  
Watts  
RPM  
Amps  
CFM  
Watts  
RPM  
Amps  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1,655  
1,579  
1,483  
1,407  
1,329  
1,210  
1,036  
-
604  
587  
567  
547  
522  
498  
464  
-
878  
903  
925  
953  
980  
1,004  
1,033  
-
2.67  
2.68  
2.62  
2.53  
2.44  
2.35  
2.24  
-
1,469  
1,409  
1,327  
1,257  
1,163  
1,094  
942  
494  
480  
459  
442  
419  
398  
363  
-
804  
833  
866  
903  
942  
968  
1,002  
-
2.24  
2.15  
2.08  
2
1.89  
1.8  
1.65  
-
1,100  
1,037  
991  
926  
831  
773  
669  
-
342  
335  
320  
308  
290  
279  
260  
-
665  
697  
760  
818  
872  
902  
945  
-
1.57  
1.52  
1.45  
1.39  
1.32  
1.25  
1.17  
-
-
GPG1348***M43A* - Rise Range: 45° - 75°  
T4 COOLING SPEED T5 COOLING SPEED  
Unit  
Static  
CFM  
WATTS  
AMPS  
CFM  
WATTS  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
--------  
1,593  
1,545  
1,506  
1,448  
1,400  
1,341  
1289  
--------  
449  
463  
476  
481  
493  
502  
511  
--------  
3.55  
3.69  
3.82  
3.87  
3.95  
4.00  
4.11  
--------  
1,669  
1,654  
1,610  
1,545  
1,512  
1,433  
1,392  
--------  
532  
239  
551  
557  
566  
578  
591  
--------  
4.22  
4.25  
4.30  
4.36  
4.41  
4.59  
4.65  
GPG1360***M43A* - COOLING SPEEDS  
T4 (Cooling Speed) T5 (Cooling Speed)  
Unit  
Static  
CFM  
WATTS  
RPM  
AMPS  
CFM  
WATTS  
RPM  
AMPS  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
1942  
1883  
1859  
1827  
1749  
1706  
1655  
1588  
649  
657  
670  
675  
683  
693  
703  
705  
993  
4.83  
4.87  
4.96  
4.97  
4.99  
5.10  
5.12  
5.11  
2067  
2030  
1982  
1909  
1842  
1789  
1703  
1618  
792  
811  
814  
808  
798  
772  
763  
732  
1054  
1077  
1088  
1101  
1110  
1117  
1129  
1135  
5.81  
5.85  
5.88  
5.86  
5.85  
5.65  
5.58  
5.29  
1010  
1029  
1047  
1069  
1083  
1104  
1120  
NR = Heating Temperature Rise Not Recommended.  
NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation,  
external static pressure should not exceed 0.5" w.c.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IGNITION CONTROL DIAGNOSTIC INDICATOR CHART  
Light Signal  
Off  
Refer to Abnormal Heating or Cooling Operation Sections of this Manual  
Internal Control Failure  
1 Flash  
External Lockout  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
Pressure Switch Stuck Open  
Pressure Switch Stuck Closed  
Thermal Protection Device Open  
Flame Detected with Gas Valve Closed  
Short Cycle Compressor Delay (Cooling Only)  
HEATING TIMING CHART  
100 %  
Circulator  
Blower  
OFF  
ON  
Gas Valve  
Igniter  
OFF  
ON  
OFF  
ON  
OFF  
Induced  
Draft  
Blower  
ON  
OFF  
Thermostat  
0
15  
22  
45  
52  
0
29  
120, 135,150  
Seconds  
COOLING TIMING CHART  
ON  
OFF  
100%  
Circulator  
Blower  
Outdoor Fan  
and  
Compressor  
ON  
OFF  
ON  
OFF  
Thermostat  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX  
UNIT DIMENSIONS  
FLUE EXHAUST  
HOOD  
A
FLUE EXHAUST  
B
B
HEAT EXCHANGE ACCESS PANEL  
POWER WIRE ENTRANCE  
CONTROL WIRE ENTRANCE  
EXHAUST FLUE HOOD  
BLOWER ACCESS PANEL  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG13(24,30,36,42)1** WIRING DIAGRAM  
P
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
R
B
R
Y
PU  
GRD  
B
S
R
C
T1  
L1  
T2  
L2  
BL  
BL  
BL  
R
Y
BL  
B
COMP  
CC  
B
B
B
B
CH OPTIONAL  
CONNECTED AT L1, L2  
NOTE 3  
CH OPTIONAL  
PU  
POWER SUPPLY  
208-230/1/60  
SEE NOTE 6  
BR  
B
1
2
3
B
PU  
208  
C
240  
NOTE 2  
TRANS  
24V  
CM  
BL/PK  
BL/PK  
R
R
PU  
NOTE 4  
BL  
R
CAP2  
BR BR  
LS  
GR  
PU(L2)  
R
BL  
B
LOW  
MEDIUM  
EM  
Y
HIGH  
2 3 4 5  
1
PU  
EM  
3 SPEED  
OPTIONAL  
BR  
R
Y
CAP.2  
BL  
B
ALT. 3 SPEED  
MOTOR  
Y
PU  
4 SPEED  
MOTOR  
BL  
Y
Y
R
ALS  
PU  
B
B
PS  
Y
Y
PU  
G
ECON  
NOTE 5  
RS  
Y
Y
3
2
1
6
BL  
5
4
PL  
PU  
PU  
SEE NOTE 5  
Y
FS  
W. R.  
(ALT.) HONEYWELL  
GAS VALVE  
IIC  
GAS VALVE  
PU  
BL  
R
R
W
MV  
GV  
MV  
PU  
BL  
G
G
Y
O
GV  
BL  
Y
BL  
Y1 C  
W
Y/Y2  
R
R
B
R
TO THC  
(SEE THC FIELD WIRING BELOW)  
O
VM  
PU  
IGN  
FS  
PU  
NOTE 4  
R
CAP  
H
PU  
F
C
R
R
PU  
BR  
Y
0140G01233 REV. A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG13(24,30,36,42)1** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
L2  
L1  
L1  
SUPPLY VOLTAGE  
208-230/1/60  
COMPONENT LEGEND  
WIRE SPLICE  
ALS AUXILIARY LIMIT SWITCH  
CAP CAPACITOR  
CH  
NOTE 3  
MARKED TERMINAL  
UNMARKED TERMINAL  
COMP COMPRESSOR  
T2  
CC  
R
S
L2  
T1  
CM CONDENSER MOTOR  
WIRING  
C
C
CAP1  
F
COMP  
CC  
CM  
CC CONTACTOR  
CH CRANKCASE HEATER  
LINE VOLTAGE  
H
CAP 2  
LOW VOLTAGE  
FIELD INSTALLED POWER  
FIELD INSTALLED CONTROL  
EM EVAPORATOR MOTOR  
FS FLAME SENSOR  
GV GAS VALVE  
NOTE 4  
(HIGH)  
(LOW)  
IIC INTEGRATED IGNITION CONTROL  
IGN IGNITOR  
WIRE CODE  
C
H
L1  
L1  
L2  
EM  
B
BLACK  
LS LIMIT SWITCH  
PL PLUG  
BL BLUE  
BR BROWN  
L1  
D1  
VM  
L2  
L2  
TRANS  
PS PRESSURE SWITCH  
G
O
GREEN  
L1  
1
ORANGE  
RS ROLLOUT SWITCH  
PK PINK  
PU PURPLE  
NOTE 2  
THC THERMOSTAT HEAT & COOL  
TRANS TRANSFORMER  
VM VENT MOTOR  
2
R
RED  
IGN  
FS  
W
Y
WHITE  
YELLOW  
HPS HIGH PRESSURE SWITCH  
FUSE  
FS  
BL/PK BLUE/PINK  
NOTES  
4
5
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF  
INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).  
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE  
LS  
ALS  
RS  
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
3. CRANKCASE HEATER (OPTIONAL).  
3
6
8
GV  
IIC  
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING  
SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT  
TERMINAL (IIC)  
PS  
ECON  
7
9
10  
12  
11  
4 SPEED MOTOR  
3 SPEED MOTOR  
- HIGH SPEED  
BL - MEDIUM SPEED  
- LOW SPEED  
B - HIGH SPEED  
B
CC  
HPS  
BL - MEDIUM HIGH SPEED  
Y - MEDIUM LOW SPEED  
R - LOW SPEED  
R
NOTE 5  
PL  
6
3
5
2
4
5. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING  
IN RETURN AIR COMPARMENT.  
1
R
G
W
Y1  
Y/Y2  
C
6. USE COPPER WIRE  
TO THC  
208-230/1/60  
INSTALLER/SERVICEMAN  
THC-FIELD WIRING  
THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS AGUIDE TO  
TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:  
EQUIP. STATUS  
CHECK  
-
STATUS LIGHT  
ON  
NORMAL OPERATION  
2 STAGE COOLING WITH ECONOMIZER  
THC-NO ECONOMIZER  
NO POWER OR  
INTERNAL CONTROL  
FAULT  
CHECK INPUT POWER  
CHECK FUSE ON CONTROL  
REPLACE CONTROL  
OFF  
W
G
W
G
W
G
W
G
R
Y
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
OR  
OPEN AUX. LIMIT  
SWITCH  
GAS FLOW  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
1 BLINK  
R
R
R
PU  
Y
Y1  
Y2  
C
Y
AUX. LIMIT OPEN  
BL  
C
PRESSURE SWITCH  
OPEN  
CHECK  
PRESSURE SWITCH  
2 BLINKS  
3 BLINKS  
4 BLINKS  
BL  
PRESSURE SWITCH CLOSED  
WITHOUT INDUCER ON  
CHECK  
PRESSURE SWITCH  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
STICKING GAS VALVE  
3 MIN. COMP.  
ANTI-CYCLE TIMER  
0140G01233 REV. A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG13(48,60)1** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
YL  
RD  
RD  
BK  
PU  
BK  
S R C  
COMP  
T1  
L1  
T2  
L2  
GND  
BL  
YL  
BL  
BK  
BK  
C
CH OPTIONAL  
CONNECTED AT L1, L2  
NOTE 3  
CH OPTIONAL  
PU  
BK  
POWER SUPPLY  
208-230/1/60  
SEE NOTE 6  
BR  
PU  
BK  
CM  
BL/PK  
BL/PK  
1
C
2
208  
3
240  
3
1
BK  
4
TR  
24V  
PU  
2
LS  
RD  
RD  
BL  
GR  
BL  
VMR  
YL RD YL  
C L G N  
EM  
BL BL BL  
RD RD  
RD  
WH  
RD  
WH  
YL  
NOTE 4  
YL  
OR  
ALS  
YL  
PU  
PS  
RS  
YL  
YL  
YL  
PU  
Y
GR  
BR  
WH  
YL  
YL  
BL  
PU  
SEE  
NOTE 5  
3
2
6
5
4
BL  
BL  
BL  
1
PLF  
SEE  
PU  
YL  
IIC  
NOTE 7  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
MV  
PU  
GV  
MV  
GV  
BL  
Y/Y2  
Y1 C R W G  
BL  
RD  
PU  
RD  
OR  
FS  
YL WH  
VM  
IGN  
RD  
PU  
BL  
RCCF  
RD  
YL  
F
H
C
YL  
WH  
BR  
BR  
0140G01234 REV A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
*PG13(48,60)1** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
L1  
SUPPLY VOLTAGE  
208-230/1/60  
CH  
L2  
COMPONENT LEGEND  
FACTORY WIRING  
AUXILIARY LIMIT SWITCH  
LINE VOLTAGE  
LOW VOLTAGE  
OPTIONAL HIGH VOLTAGE  
ALS  
NOTE 3  
COMP  
CM  
C
COMPRESSOR  
CONDENSER MOTOR  
CONTACTOR  
C
T2  
C
T1  
R
S
C
CH  
EM  
F
CRANKCASE HEATER  
EVAPORATOR MOTOR  
FUSE  
H
C
FIELD WIRING  
F
HIGH VOLTAGE  
LOW VOLTAGE  
CM  
FS  
FLAME SENSOR  
GND  
GV  
IIC  
IGN  
LS  
EQUIPMENT GROUND  
GAS VALVE  
INTEGRATED IGNITION CONTROL  
IGNITOR  
LIMIT SWITCH  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
WIRE CODE  
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
L
N
EM  
VMR  
4
VM  
2
NOTE 2  
2
PLF  
PS  
3
1
RCCF RUN CAPACITOR FOR COMPRESSOR/FAN  
TR  
RS  
TR  
ROLLOUT SWITCH  
TRANSFORMER  
NOTE 7  
NOTE 7  
L1  
IIC  
IGN  
WH WHITE  
YL YELLOW  
VM  
VENT MOTOR  
FS  
FS  
F
VMR  
HPS  
VENT MOTOR RELAY  
HIGH PRESSURE SWITCH  
C
H
BL/PK BLUE/PINK  
EM  
C
1
3
NOTES  
D1  
4
5
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF  
INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).  
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE  
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.  
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING  
SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING  
SPEED AT MOTOR T1, T2 AND T3 TERMINALS.  
VMR  
LS  
ALS  
RS  
IIC  
3
6
GV  
PS  
8
9
7
10  
12  
11  
COOLING SPEED (YELLOW WIRE)  
T4 - LOW SPEED  
T5 - HIGH SPEED  
HEATING SPEED (WHITE WIRE)  
C
T1 - LOW SPEED  
T2 - MED. SPEED  
T3 - HIGH SPEED  
HPS  
NOTE  
5
6
3
5
2
4
5. ACCESSORY ECONOMIZER PLUG ADJACENT TO BLOWER HOUSING  
IN RETURN AIR COMPARMENT.  
PLF  
1
Y/Y2  
R
G
W
Y1  
C
6. USE COOPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
TO THERMOSTAT  
208-230/1/60  
INSTALLER/SERVICEMAN  
THERMOSTAT FIELD WIRING  
EQUIP. STATUS  
CHECK  
STATUS LIGHT  
ON  
-
NORMAL OPERATION  
2 STAGE COOLING WITH ECONOMIZER  
NO POWER OR  
INTERNAL CONTROL  
FAULT  
NO ECONOMIZER  
OFF  
WH  
GR  
RD  
PU  
YL  
BL  
W
G
R
WH  
GR  
RD  
YL  
BL  
W
G
R
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
GAS FLOW  
1 BLINK  
GAS PRESSURE  
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
OR  
Y1  
Y2  
C
Y
C
OPEN AUX. LIMIT  
SWITCH  
PRESSURE SWITCH  
OPEN  
2 BLINKS  
3 BLINKS  
CHECK  
PRESSURE SWITCH  
WITHOUT INDUCER ON  
OPEN LIMIT SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
4 BLINKS  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
3 MIN. COMP.  
0140G01234 REV A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPG13(36)3** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
YL  
RD  
PU  
RD  
BK  
BK  
T3 T2 T1  
COMP  
T1  
L1  
T2  
L2  
T3  
L3  
GND  
BL  
BL  
BL  
BL  
YL  
BK  
BK  
C
BK  
BK  
BK  
CH OPTIONAL  
SEE NOTE 3  
CH OPTIONAL  
CONNECTED AT L1, L2  
NOTE 3  
POWER SUPPLY  
208-230/3/60  
PU  
BR  
BK  
SEE NOTE 6  
1
C
2
3
240  
BK  
PU  
208  
TR  
24V  
CM  
NOTE 2  
R
D
PU  
BL  
RD  
NOTE 4  
EM  
LS  
R
D
PU  
BL/PK  
BL/PK  
3 SPEED  
MOTOR  
BR  
FC  
PU  
RD  
BK  
BL  
BK  
YL  
RD  
ALS  
BL  
YL  
PU  
BK  
PS  
RS  
YL  
YL  
BR BL PU  
GR  
YL  
ECON  
YL  
PU  
3
2
1
6
5
4
BL  
NOTE 5  
PLF  
PU  
PU  
YL  
FS  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
IIC  
RD  
WH  
MV  
GV  
PU  
BL  
YL BL  
C R  
GR  
W G  
PU  
Y1  
OR  
GV  
BK  
RD  
BL  
MV  
Y/Y2  
RD  
RD  
PU  
BK  
BL  
C
O
R
VM  
IGN  
FS  
NOTE 4  
RD  
FC  
PU  
PU  
RD  
PU  
F
RD  
BR  
0140G01001 REV. A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPG13(36)3** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
L1  
SUPPLY VOLTAGE  
208-230/3/60  
CH  
L2  
L3  
COMPONENT LEGEND  
FACTORY WIRING  
LINE VOLTAGE  
ALS  
AUXILIARY LIMIT SWITCH  
NOTE 3  
LOW VOLTAGE  
OPTIONAL HIGH VOLTAGE  
COMP  
COMPRESSOR  
C
T3  
CONDENSER MOTOR  
CONTACTOR  
CM  
C
T2  
C
C
T1  
T2  
T3  
FIELD WIRING  
CRANKCASE HEATER  
EVAPORATOR MOTOR  
FUSE  
CH  
EM  
F
T1  
C
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
F
CM  
FC  
FAN CAPACITOR  
FLAME SENSOR  
EQUIPMENT GROUND  
IIC  
WIRE CODE  
FS  
GND  
(MED)  
NOTE 4  
E
M
BK BLACK  
BL BLUE  
BR BROWN  
GR GREEN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
WH WHITE  
YL YELLOW  
C
H
GV  
IIC  
IGN  
LS  
PLF  
PS  
RS  
TR  
VM  
GAS VALVE  
INTEGRATED IGNITION CONTROL  
IGNITOR  
V
M
LIMIT SWITCH  
2
L1  
1
3
1
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
TRANSFORMER  
NOTE 2  
T
R
2
IG  
N
VENT MOTOR  
F
BL/PK BLUE/PINK  
HIGH PRESSURE SWITCH  
FS  
FS  
HPS  
4
5
NOTES  
LS  
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF  
INSULATION AS ORIGINAL.(USE COPPER CONDUCTOR ONLY).  
AL  
S
RS  
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE  
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
G
V
3
6
8
IIC  
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.  
PS  
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING  
SPEED AT COOL TERMINAL (IIC). CHANGE HEATING SPEED AT HEAT  
TERMINAL (IIC)  
9
7
10  
12  
11  
HPS  
3 SPEED MOTOR  
BK - HIGH SPEED  
BL - MEDIUM SPEED  
RD - LOW SPEED  
C
NOTE 5  
6
3
5
2
4
PLF  
5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT  
TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.  
6. USE COOPER CONDUCTORS ONLY.  
1
R
G
W
Y1  
Y/Y2  
C
USE NEC CLASS 2 WIRE.  
208-230/3/60  
INSTALLER/SERVICEMAN  
THERMOSTAT FIELD WIRING  
NO  
2 STAGE COOLING WITH ECONOMIZER  
OPTION  
ECONOMIZER  
CHECK  
-
EQUIP. STATUS  
STATUS LIGHT  
WH  
GR  
RD  
YL  
W
G
R
Y
W
G
R
WH  
GR  
RD  
PU  
ON  
NORMAL OPERATION  
NO POWER OR  
INTERNAL CONTROL  
FAULT  
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
OFF  
GAS FLOW  
1 BLINK  
Y1  
Y2  
C
GAS PRESSURE  
GAS VALVE  
C
BL  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
OR  
BL  
OPEN AUX. LIMIT  
AUX. LIMIT OPEN  
SWITCH  
PRESSURE SWITCH  
OPEN  
CHECK  
2 BLINKS  
3 BLINKS  
4 BLINKS  
PRESSURE SWITCH  
CHECK  
PRESSURE SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
WITHOUT INDUCER ON  
OPEN LIMIT SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
3 MIN. COMP.  
0140G01001 REV. A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPG13(48,60)3** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
YL  
RD  
BK  
PU  
RD  
BK  
T1  
L1  
T2  
L2  
T3  
L3  
GND  
BL  
YL  
BL  
BK  
BK  
COMP  
C
BK  
CH OPTIONAL  
CONNECTED AT L1, L2  
CH OPTIONAL  
BL  
NOTE 3  
POWER SUPPLY  
208-230/3/60  
SEE NOTE 6  
PU  
BK  
BR  
CM  
BK  
1
2
208  
3
240  
3
1
C
BK  
4
TR  
24V  
PU  
GR  
2
LS  
RD  
BL  
VMR  
BL  
YL RD  
RD  
BL BL BL  
RD RD  
RD  
WH  
C
L G N  
EM  
RD  
WH  
YL  
NOTE 4  
OR  
ALS  
PU  
BL/PK  
BL/PK  
PS  
YL  
YL  
YL  
PU  
GR  
YL  
BR WH  
RS  
YL  
BL  
PU  
3
2
6
5
4
YL  
BL  
BL  
BL  
1
NOTE 5  
PLF  
SEE  
NOTE 7  
YL  
PU  
IIC  
W. R.  
GAS VALVE  
(ALT.) HONEYWELL  
GAS VALVE  
MV  
PU  
GV  
MV  
GV  
BL  
Y/Y2  
R
W G  
C
Y1  
BL  
RD  
RD  
OR  
FS  
YL WH  
VM  
IGN  
RD  
PU  
BL  
FC  
RD  
YL  
WH  
BR  
BR  
0140G01002 REV. A  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GPG13(48,60)3** WIRING DIAGRAM  
HIGH VOLTAGE!  
DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS  
UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO  
DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.  
L1  
SUPPLY VOLTAGE  
208-230/3/60  
L2  
L3  
L3  
COMPONENT LEGEND  
FACTORY WIRING  
LINE VOLTAGE  
LOW VOLTAGE  
AUXILIARY LIMIT SWITCH  
ALS  
CH  
NOTE 3  
T2  
COMP  
COMPRESSOR  
OPTIONAL HIGH VOLTAGE  
CONDENSER MOTOR  
CONTACTOR  
CM  
C
C
C
T1  
T2  
T3  
CH  
EM  
CRANKCASE HEATER  
EVAPORATOR MOTOR  
FUSE  
T1  
FIELD WIRING  
T3  
C
F
HIGH VOLTAGE  
LOW VOLTAGE  
FC  
FC  
FAN CAPACITOR  
CM  
FS  
FLAME SENSOR  
GND  
GV  
IIC  
EQUIPMENT GROUND  
GAS VALVE  
INTEGRATED IGNITION CONTROL  
IGNITOR  
WIRE CODE  
BK BLACK  
L
N
VMR  
EM  
BL BLUE  
IGN  
VM  
4
BR BROWN  
GR GREEN  
OR ORANGE  
PK PINK  
PU PURPLE  
RD RED  
LS  
PLF  
PS  
RS  
TR  
LIMIT SWITCH  
FEMALE PLUG/CONNECTOR  
PRESSURE SWITCH  
ROLLOUT SWITCH  
TRANSFORMER  
2
3
1
TR  
IGN  
NOTE 7  
NOTE 7  
1
2
IIC  
VM  
VMR  
VENT MOTOR  
VENT MOTOR RELAY  
WH WHITE  
YL YELLOW  
FS  
FS  
F
C
H
EM  
C
BL/PK BLUE/PINK  
HPS  
HIGH PRESSURE SWITCH  
D1  
1
3
NOTES  
4
5
VMR  
1. REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF  
INSULATION AS ORIGINAL .(USE COPPER CONDUCTOR ONLY).  
2. FOR 208 VOLT TRANSFORMER OPERATION MOVE BLACK WIRE  
FROM TERMINAL 3 TO TERMINAL 2 ON TRANSFORMER.  
3. CRANKCASE HEATER NOT SUPPLIED ON ALL UNITS.  
4. FOR DIFFERENT THAN FACTORY SPEED TAP. CHANGE COOLING  
SPEED AT MOTOR T4 AND T5 TERMINALS. CHANGE HEATING  
SPEED AT MOTOR T1, T2 AND T3 TERMINALS.  
LS  
ALS  
PS  
RS  
IIC  
3
6
GV  
8
9
7
10  
12  
COOLING SPEED (YELLOW WIRE)  
HEATING SPEED (WHITE WIRE)  
HPS  
C
11  
T4 - LOW SPEED  
T5 - HIGH SPEED  
T1 - LOW SPEED  
T2 - MED. SPEED  
T3 - HIGH SPEED  
5
NOTE  
6
5
2
4
1
5. ACCESSORY ECONOMIZER PLUG (ON SELECT MODELS) ADJACENT  
TO BLOWER HOUSING IN RETURN AIR COMPARTMENT.  
PLF  
3
R
G
W
Y1  
C
Y/Y2  
6. USE COOPER CONDUCTORS ONLY.  
USE NEC CLASS 2 WIRE.  
TO THERMOSTAT  
7. L1 AND L2 ON ICC CONTROL IS 24V INPUT.  
208-230/3/60  
INSTALLER/SERVICEMAN  
THERMOSTAT FIELD WIRING  
2 STAGE COOLING WITH ECONOMIZER  
OPTION  
CHECK  
EQUIP. STATUS  
STATUS LIGHT  
ON  
NORMAL OPERATION  
-
NO ECONOMIZER  
NO POWER OR  
INTERNAL CONTROL  
FAULT  
IGNITION FAILURE  
OR  
OPEN ROLLOUT  
SWITCH  
OFF  
WH  
GR  
RD  
PU  
YL  
BL  
W
G
W
G
R
WH  
GR  
RD  
YL  
GAS FLOW  
1 BLINK  
GAS PRESSURE  
R
GAS VALVE  
FLAME SENSOR  
FLAME ROLLOUT  
BAD SWITCH  
AUX. LIMIT OPEN  
CHECK  
PRESSURE SWITCH  
Y1  
Y2  
C
OR  
OPEN AUX. LIMIT  
Y
C
SWITCH  
PRESSURE SWITCH  
OPEN  
BL  
2 BLINKS  
3 BLINKS  
4 BLINKS  
CHECK  
PRESSURE SWITCH  
MAIN LIMIT OPEN  
BAD SWITCH  
WITHOUT INDUCER ON  
OPEN LIMIT SWITCH  
5 BLINKS  
6 BLINKS  
FALSE FLAME SENSED  
COMPRESSOR  
OUTPUT DELAY  
0140G01002 REV. A  
3 MIN. COMP.  
Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MINIMUM CLEARANCES  
48" MIN  
12" MIN  
3"  
MIN  
.
12" MIN  
36" MIN  
(FOR SERVICE)  
NOTE: Roof overhang should be no more than 36".  
-
UNIT  
2 Ton  
2 1/2 Ton  
3 Ton  
3 1/2 4 Ton  
5 Ton  
Min. Filter Size  
(1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1  
RECOMMENDED FILTER SIZES  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: SPECIFICATIONSAND PERFORMANCE DATALISTED HEREINARE SUBJECT TO CHANGE WITHOUT NOTICE  
Quality Makes the Difference!  
All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency. We have  
designed these units to significantly reduce the most frequent causes of product failure. They are simple to service and forgiving to  
operate. We use quality materials and components. Finally, every unit is run tested before it leaves the factory.  
That’s why we know. . .There’s No Better Quality.  
Products  
Warranties  
Customer Services  
Parts  
Contractor Programs and Training  
Financing Options  
© 2009 - 2010 Goodman Manufacturing Company, L.P.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Echo Chainsaw CS 280E User Manual
Eizo Computer Monitor RadiForce R12 User Manual
Electro Voice Microphone N D257A User Manual
Euro Pro Carpet Cleaner EP961 User Manual
Extron electronic Stereo Receiver HFX 100 RX User Manual
Flymo Trimmer PN 248722 User Manual
Furuno Radar Detector FCR 1040 User Manual
GE Fax Machine UX CL 220 User Manual
GE Monogram Ventilation Hood ZV30TSFSS User Manual
Gianni Industries Door LZ GL600 User Manual