D1255RB, D1256RB, and D1257RB
1.0
Introduction.......................................................4
Internal Arrangement................................. 5
Releasing the Enclosure Base.................... 6
Lifting the Keypad from the Enclosure
Base............................................................... 6
Removing the Enclosure Base................... 6
Lifting the Red Cover................................. 6
Removing the Red Cover.......................... 7
Removing the Faceplate............................. 7
Setting the Address Switches..................... 7
Address DIP Switches ................................ 7
2.0
2.1
Overview ...........................................................4
D1255RB/D1256RB/D1257RB Features........4
D1255RB.............................................................4
D1256RB.............................................................4
D1257RB.............................................................4
Description ..........................................................4
Display.................................................................4
Audible Tones.....................................................4
Switch Settings ....................................................5
Installation.........................................................5
Figure 2:
Figure 3:
2.1.1
2.1.2
2.1.3
2.2
2.2.1
2.2.2
2.2.3
3.0
Figure 4:
Figure 5:
Figure 6:
Figure 7:
Figure 8:
Figure 9:
Figure 10: Mounting the Enclosure Base.................... 8
3.1
Mounting Information (D1255RB,
D1256RB, and D1257RB).................................5
Figure 11: Wiring Harness Connection to Keypad
or Annunciator............................................ 8
3.2
Wiring Information (D1255RB, D1256RB,
and D1257RB) ....................................................5
Installation Procedure ........................................6
D1256RB Programming Requirements.......9
Keypad (COMMAND CENTER)
Assignments.........................................................9
Figure 12: Installing the Enclosure Base − Top......... 8
Figure 13: Closing the Enclosure Base – Bottom ...... 8
Figure 14: Example – Area Text for Fire
Applications................................................. 9
3.3
4.0
4.1
Figure 15: Example – Custom Functions
Recommended for UL864 9th Edition .... 10
4.2
4.3
4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.4.5
5.0
Area Text.............................................................9
Custom Functions.............................................10
Function List......................................................10
Menu Item and Function.................................11
CC Address # ...................................................11
Passcode Worksheet.........................................11
Passcode.............................................................11
Keypad (Command Center) Functions..........12
Specifications ..................................................13
Figure 16: Example – Function List.......................... 10
Figure 17: Example – Fire Passcode Worksheet ..... 11
Figure 18: Example – Keypad Functions ................. 12
Figure 19: Custom Functions..................................... 13
Tables
Table 1:
Table 2:
Table 3:
Table 4:
DIP Switch Address Settings ..................... 7
Keypad or Annunciator Connections....... 8
Function List Description......................... 11
Specifications for the D1255RB and
D1256RB Keypads and the D1257RB
Annunciator............................................... 13
Bosch Security Systems, Inc. | 8/06 | F01U011791B
3
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 1.0 Introduction
2.1.2 D1256RB
The D1256RB provides annunciation and system
control. Four function keys on the D1256RB provide
quick execution of alarm silencing, trouble silencing,
annunciator display reset, and sensor reset functions.
1.0 Introduction
Before installing the D1255RB, D1256RB, or
D1257RB, you should be familiar with the operation
and installation guide and the program entry guide for
the control panel you are using. Before proceeding
with the installation instructions in this manual, be sure
that you are familiar with the programming
recommendations in the Guide to UL 864 9th Edition
Programming Requirements section of the Introduction in
the D9412GV2/D7412GV2 Program Entry Guide
(P/N F01U003636).
The D1256RB should be mounted in a
secure area or locked inside an approved
clear plastic enclosure.
2.1.3
D1257RB
The D1257RB provides remote annunciation without
system control capability. It can be mounted in public
access locations.
2.0 Overview
Two keys on the D1257RB allow the user to select
forward or backward through a list of system events.
2.1
D1255RB/D1256RB/D1257RB
Features
2.2
Description
2.2.1
Display
The D1255RB and D1256RB Fire Keypads and the
D1257RB Fire Alarm Annunciator are 4-wire serial
devices used with the following Bosch Security Systems
control panels with firmware version 7.04 or higher:
The D1255RB, D1256RB and D1257RB use a
16-character display with custom programmable text.
The custom text programmed at the control panel
appears in the vacuum fluorescent display (VFD).
Refer to Figure 1, Item 1.
•
•
•
D9412GV2
D7412GV2
D7212GV2
The keypads and annunciator show the latest status
conditions of the fire system using words, numbers, and
symbols. When an alarm occurs, a message remains in
the display until the user acknowledges the event at a
keypad or annunciator. When a series of events
affecting the system occurs, each event appears in
order of its priority.
The D7212GV2 is not approved for
commercial fire applications.
Each of these control panels supervises up to eight
keypads or annunciators. You can connect a total of 32
keypads or annunciators to the system. The number of
supervised keypads or annunciators, number of areas,
and the available power affect the total number of
keypads or annunciators you can connect to the
system.
2.2.2
Audible Tones
The D1255RB, D1256RB and D1257RB have a built-
in speaker that produces several distinct warning tones.
To change the speaker volume, adjust the
potentiometer (Figure 1, Item 3). Turn the potentiometer
clockwise to increase and counterclockwise to decrease
the volume.
2.1.1
D1255RB
The D1255RB has number keys (0 to 9) and function
or menu keys, including [COMMAND] and [ENTER].
The D1255RB can be used as a system controller and
an annunciator.
You cannot connect external annunciation
devices to the D1255RB, D1256RB, and
D1257RB.
Because a passcode is required to use the keypad, it is
usually installed in building entrances and areas with
unrestricted access. Near an exterior door in a hotel or
in a business lobby is an ideal mounting location,
allowing a responding agency or persons evacuating
the building to identify quickly the type and location of
the emergency from outside without being in danger.
•
•
•
Fire Signal – Pulsed, high pitched bell tone when
the system is in alarm
Invalid Key Buzz – Flat buzz tone when an
invalid key, or sequence of keys, is pressed
Keypad Encoding Tone – Muted beep tone as
each key is pressed to indicate that the entry has
been accepted. To disable the keypad encoding
tone, refer to Section 2.2.3 Switch Settings.
4
Bosch Security Systems, Inc. | 8/06 | F01U011791B
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 3.0 Installation
.
Figure 1: D1255RB, D1256RB, and D1257RB Internal Arrangement
1
2
5
1
2
3
4
5
6
7
3
6
4
1 - Vacuum fluorescent display (VFD)
2 - Keypad
3 - Speaker volume control (potentiometer)
4- Address DIP switches
5 - Status LEDs
6 - Wiring harness connector
7 - Speaker for sounder
•
Trouble Buzzer – Two-tone warble when a
trouble event occurs, such as a service alert. To
stop the signal on a D1255RB Keypad, press
3.0 Installation
3.1
Mounting Information (D1255RB,
D1256RB, and D1257RB)
[COMMAND][4]. To stop the tone on a D1256RB,
press the [TROUBLE SILENCE] key.
The D1255RB, D1256RB, and D1257RB are low-
profile, surface-mounted units molded in durable red
plastic. Use the D56 Keypad Conduit Box (protected
surface or flush mount) for mounting the units.
The D1257RB does not have a manual
method of stopping the trouble buzzer.
Mounting Locations
Refer to the Fire System User’s Guide
(P/N: F01U011793) for information about silencing the
signals.
•
Do not mount the keypads and
annunciators in locations where they are
exposed to direct sunlight. Direct
sunlight can interfere with the display
screen’s visibility and damage internal
components.
•
Lost Communication – Single trouble tone
followed by a 30-second silence when a keypad or
annunciator loses communication from the control
panel. To stop the tone, restore communication or
remove power from the keypad or annunciator.
•
Do not mount the units in wet or moist
locations.
2.2.3
Switch Settings
3.2
Wiring Information (D1255RB,
D1256RB, and D1257RB)
A 6-position DIP switch (Figure 1, Item 4) located under
the cover allows you to select the address of each
keypad or annunciator and silence the keypad
encoding tones.
A four-wire flying lead is required for the data and
power connections between the keypad or annunciator
and the control panel. The unit includes a wiring
harness with four color-coded flying leads at one end
and a female four-pin connector at the other end.
For information on accessing the switches, refer to
Section 3.3 Installation Procedure on page 6.
Refer to Figure 10 and Figure 11 on page 8 to wire the
D1255RB, D1256RB, or D1257RB.
For supervised keypads, assign only one
keypad to each address.
Bosch Security Systems, Inc. | 8/06 | F01U011791B
5
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 3.0 Installation
4. Gently pull the keypad apart from the enclosure
base at the top hinges.
3.3
Installation Procedure
1. Power down the control panel.
2. Using a small flat-bladed screwdriver, gently push
the two bottom tabs up and in to release the
enclosure base. Refer to Figure 2.
Figure 4: Removing the Enclosure Base
Use caution to avoid damage to the tabs
and hinges.
Figure 2: Releasing the Enclosure Base
1 - Enclosure base
2- Top hinges
5. Lift and remove the red cover.
1 - Screwdriver
2 - Tabs
Figure 5: Lifting the Red Cover
3 - Enclosure base
3. Gently lift the unit from the enclosure base as the
tabs are pushed in.
Figure 3: Lifting the Keypad from the Enclosure
Base
1 - Enclosure base
2 - Tabs
6
Bosch Security Systems, Inc. | 8/06 | F01U011791B
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 3.0 Installation
.
7. Set the address switches. Refer to Figure 8, Figure 9,,
and Table 1.
Figure 6: Removing the Red Cover
Figure 8: Setting the Address Switches
1 - Red cover
6. Remove the faceplate.
1 - Faceplate
2 - Address switches
Figure 7: Removing the Faceplate
Figure 9: Address DIP Switches
N
O
1
2
3
4
5
6
Table 1:
DIP Switch Address Settings
Switch Number
Address
Number
1
2
3
4
ON
ON
ON
ON
ON
ON
ON
ON
6
5
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
1
2
3
4
5
6
7
8
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
ON
1 - Faceplate
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
Switch 5 toggles the encoding tone ON and OFF. With the
encoding tone turned on, the keypad sounds a beep each
time a key is pressed.
Bosch Security Systems, Inc. | 8/06 | F01U011791B
7
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 3.0 Installation
Figure 11: Wiring Harness Connection to Keypad
or Annunciator
Warning: Avoid injury. Do not wire the
D1255RB, D1256RB, or D1257RB if
power is applied to the control panel.
8. Connect the flying leads on the wiring harness
(Figure 10) to the wiring terminals on the control
panel. Refer to Table 2.
1
Table 2:
Keypad or Annunciator Connections
D9412GV2/
D7412GV2
Terminal
Keypad
Wire Color Function
Function
1 - Connector
12. Replace the faceplate.
13. Replace the cover. Align and insert the top two
tabs of the cover into the top two tab slots on the
front of the keypad.
32*
31
30
29
POWER +
DATA BUS A
DATA BUS B
COMMON
Red
12 VDC
Data
Yellow
Green
Black
Data
Common
* Connect with at least 1.5 m (5 ft.) of 0.8 mm (22 AWG) wire
(4.3 m [14 ft.] of 1.2 mm [18 AWG] wire).
14. Install the enclosure base:
a. Hold the unit at an angle to the enclosure base
and snap the hinges on the top edge of the unit
into place first.
9. Feed the connector end of the wiring harness
through the opening in the back of the enclosure
base (Figure 10).
10. Secure the keypad or annunciator to its mounting
location from inside the enclosure base by inserting
screws through the mounting holes (Figure 10).
Figure 12: Installing the Enclosure Base − Top
Figure 10: Mounting the Enclosure Base
1
1
2
1 - Hinges
3
b. Press the bottom edge of the unit toward the
enclosure base until the tabs snap into the
openings in the base.
1
4
1
Figure 13: Closing the Enclosure Base – Bottom
5
1 - Mounting hole
2 - Flying leads
3 - Wiring harness
4 - Opening
5 - Connector
11. Connect the wiring harness to the connector on the
back of the keypad or annunciator (Figure 11).
1 - Enclosure base
2
Tabs
8
Bosch Security Systems, Inc. | 8/06 | F01U011791B
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
.
4.1
Keypad (COMMAND CENTER)
Assignments
4.0 D1256RB Programming
Requirements
•
Keypad Text: The D1256RB can be assigned to
any one of the eight addresses in the control panel.
Refer to Sections 4.2 Area Text, 4.3 Custom Functions
on page 10, and 4.4 Function List on page 10 for
programming descriptions for one D1256RB
assigned to Keypad 1, Area 1.
For D1255RB and D1257RB programming
information, refer to the appropriate
program entry guide and program record
sheet for the control panel.
•
Supervised: Certain local jurisdictions might
require supervision of fire system annunciators. If
your area has that requirement, set the supervision
to YES for the addresses that use fire alarm
annunciators.
Scope: The D1256RB acknowledges fire alarms
and troubles, not burglar alarms and troubles. Set
the scope to include fire areas only.
Important programming recommendations and
requirements are described in this section. For
information about the displays and functions available
from the D1256RB, refer to Keypad (Command Center),
User Interface, and Function List in the GV2MAIN section,
and User (Passcode) Worksheet in the RADXUSR1 Handler
or RADXUSR1/RADXUSR2 Handlers section of the
program record sheet for the control panel.
•
•
Area: Program the area number of the fire area(s)
as normal.
4.2
Area Text
Figure 14: Example – Area Text for Fire Applications
Area 1
Area 2
Area # is On
Area # Not Ready
Area # is Off
P R E S S A L A R M S I L
C H E C K F I R E S Y S
* F I R E S Y S T E M *
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Area # Acct is On
P R E S S A L A R M S I L
Area # is On − PRESS ALARM SIL
Fire area should remain in the OFF state at all times. If the authority level is not programmed correctly, and the
fire alarm area arms, PRESS ALARM SILshows on the display. Pressing the [ALARM SILENCE] key silences
any alarms(s) and disarms the area.
The idle text, * FIRE SYSTEM *, appears on the display when the area is disarmed.
Area # Not Ready − CHECK FIRE SYS
Most fire alarm areas consist of all 24-hour points and the Area # Not Ready display is not used. If a controlled
point type is used for some type of fire supervision device, and the device becomes off-normal, CHECK FIRE
SYSappears on the fire keypad.
Area # is Off − * FIRE SYSTEM *
This is the normal idle text for the fire keypad and annunciator.
Area # Acct is On − PRESS ALARM SIL
Fire area should remain in the OFF state at all times. If the authority level is not programmed correctly, and the
fire alarm area arms, PRESS ALARM SILshows on the display. Pressing the [ALARM SILENCE] key silences
any alarms(s) and disarms the area.
The idle text, * FIRE SYSTEM *, appears on the display when the area is disarmed.
Bosch Security Systems, Inc. | 8/06 | F01U011791B
9
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
4.3
Custom Functions
Figure 15: Example – Custom Functions Recommended for UL864 9th Edition
Custom Function Text
Custom Function Keystrokes
CF 128
CF 129
CF 130
CF 131
A L A R M S I L E N C E ?
T R O U B L E S I L E N C E ? A 4 C C _ _ _ _ _ _ _ _ _ _ _ _
D E T E C T O R R E S E T ? A 4 7 _ _ _ _ _ _ _ _ _ _ _ _ _
A N U N C I A T O R R E S E T 1 2 5 6 0 0 C A 4 7 _ _ _ _ _ _
1 2 5 6 0 0 E _ _ _ _ _ _ _ _ _
In Figure 15, C = [ESC], E = [ENT], A = [Command].
In the D1256RB, Custom Functions must be programmed as indicated in Figure 15. Refer to Keypad (Command
Center), Custom Functions in the program record sheet for your control panel for information on making the
function keys operational.
The passcode 125600 is used in the following examples. You can use any passcode.
CF 128 − ALARM SILENCE ?
Keystrokes: [1] [2] [5] [6] [0] [0] [ENT]. Program this custom function as the first Menu item in the D1256RB
display. The Alarm Silence function is executed when the [ALARM SILENCE] key is pressed on the D1256RB.
The control panel sees the keystroke entry as a valid passcode having the authority to silence a ringing fire bell in
the area. The [ENT] key has the enter function.
CF 129 − TROUBLE SILENCE ?
Keystrokes: [A] [4] [ESC][ESC]. Program this custom function as the second item in the Menu. The function is
executed whenever the [TROUBLE SILENCE] key is pressed on the D1256RB. This entry is the equivalent to
executing a [COMMAND] [4] on the D1256RB.
CF 130 − DETECTOR RESET ?
Keystrokes: [A] [4] [7]. Program this custom function as the third item in the Menu. The function is executed
whenever the [DETECTOR RESET] key is pressed on the D1256RB. This entry is the equivalent to executing a
[COMMAND] [4][7] on the D1256RB.
CF 131 − ANNUNCIATOR RESET ?
Keystrokes: [1] [2] [5] [6] [0] [0] [ESC] [Command] [4] [7]. Program this custom function as the fourth command
item in the Menu. The function is executed whenever the [ANNUNCIATOR RESET] key is pressed on the
D1256RB. Executing this function clears the “View Memory” buffer, but does not clear the event out of the event
log contained with the control panel.
4.4
Function List
Figure 16: Example – Function List
Menu
Item
1
2
3
4
5
6
7
8
9
10
11
CC
CC
CC
CC
CC
CC
CC
CC
Function
Address 1
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 2
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 3
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 4
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 5
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 6
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 7
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Address 8
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
Yes / No
1 2 8
1 2 9
1 3 0
1 3 1
_ _ 9
_ 1 0
_ 1 2
_ 2 1
_ 2 9
_ 3 2
_ _ _
Refer to Function List in the program record sheet for the control panel.
10
Bosch Security Systems, Inc. | 8/06 | F01U011791B
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
.
4.4.1
Menu Item and Function
Table 3:
Function List Description
Program the first ten menu items as indicated in
Table 3. This programming is necessary for the
D1256RB to operate properly. The first four keys on
the D1256RB execute the first four menu items
enabled at the keypad address. Menu items five
through ten are optional features that can be
programmed into the D1256RB system. Refer to the
Fire System User’s Guide (P/N: F01U011793) for further
explanation of these optional programmable items.
Menu Item
Function
128
129
130
131
9
Description
ALARM SILENCE?
TROUBLE SILENCE?
DETECTOR RESET?
ANNUNCIATOR RESET
VIEW MEMORY?
VIEW PT STATUS?
FIRE TEST?
1
2
3
4
5
6
10
7
12
Ensure that CF 128 through CF 131 are
programmed E (enabled) and not P
(passcode required).
VIEW LOG?
8
21
REMOTE PROGRAM?
DISPLAY REV?
9
29
10
32
4.4.2
CC Address #
CC = command center = keypad
Program the keypad (command center) addresses as
Yes for the first four menu items and for the optionally
programmed menu items five through ten.
4.4.3
Passcode Worksheet
Figure 17: Example – Fire Passcode Worksheet
User (Passcode) Worksheet (Users 000 to 029)
User
Area Authority
User
##
#
Passcode
1
2
3
4
5
6
7
8
User Name
Group
SERVICE
PASSCODE
123 __ __ __ __ __ __
000
001
____
15
14
15
__
15
__
15
__
15
__
15
__
15
__
15
__
USER 1
1 2 5 6 0 0
____
Refer to User (Passcode) Worksheet in the program record sheet for the control panel.
4.4.4 Passcode
A special passcode must be programmed as a valid passcode for the system to work properly. This passcode is
used in Custom Functions 128 through 131. Use any user number to establish this mandatory valid passcode. You
must also create it as a valid passcode in the area to which the D1256RB is assigned. Use Authority Level 14
together with the passcode you select. Ensure that Passcode Arm is disabled (blank) for the Authority Level.
Refer to Authority Level Selections in the program record sheet for the control panel.
Bosch Security Systems, Inc. | 8/06 | F01U011791B
11
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 4.0 D1256RB Programming Requirements
4.4.5
Keypad (Command Center) Functions
Figure 18: Example – Keypad Functions
The following keypad function must be enabled or
passcode required to enable the [DETECTOR RESET]
key.
Keypad Functions
#
Functions
Command
E/P*
P
P
•
#27 Reset Sensors
1
2
3
4
5
6
7
8
9
Disarm ?
Include the following items in the menu:
Master Arm Delay ?
Master Arm Instant ?
Perimeter Instant ?
Perimeter Delay ?
Watch Mode ?
Perimeter Part ?
View Area Status ?
View Memory ?
View Pt Status ?
Walk Test ?
CMD 1
CMD 11
CMD 2
CMD 3
CMD 6
CMD 8
•
•
•
•
•
•
#9 View Event Memory
#10 View Point Status
#12 Fire Test
#21 View Log
#29 Remote Program
#32 Display Rev
P
P
E
P
P
E
E
E
P
P
P
E
E
E
P
E
E
P
P
P
P
E
P
P
P
P
P
E
P
P
P
E
P
P
P
P
Refer to Figure 18.
CMD 40
For the D9412GV2 Control Panel, program
each of the keypad functions with E
(enabled) and not P (passcode required). If
restricting any of the keypad functions with
a passcode is required, those functions
must be executed from a custom function
that includes an authorized passcode.
10
11
12
13
14
CMD 44
CMD 58
CMD 41/42
CMD 46
Fire Test ?
Send Report ?
Door Control ?
Cycle Door ?
Unlock Door ?
Secure Door ?
Example (Refer to Figure 18.): If the
keypad function View Memory is
programmed as P (passcode required), and
the passcode 125600 has authority to
execute it, the keystrokes would be:
37
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
32
33
34
35
36
*
Access Control Level?
Change Display ?
Change Time/Date ?
Change Passcode ?
Add User ?
CMD 49
CMD 45
CMD 55
CMD 56
CMD 53
CMD 51
[A] [4] [0] [1] [2] [5] [6] [0] [0] [E]
When creating a Menu Function List for a
keypad address, consider that the
D1256RB Keypad does not have numeric
keys. Ensure that:
Del User ?
Extend Close ?
View Log ?
Print Log ?
•
no passcode-protected keypad functions
are in a Menu Function List enabled at
an address that coincides with the
installed address for a D1256RB
Keypad.
User Command 7 ?
User Command 9 ?
Bypass a Point ?
Unbypass a Point ?
Reset Sensors ?
Change Relays ?
Remote Program ?
Move To Area ?
Display Rev ?
CMD 7
CMD 9
CMD 0
CMD 00
CMD 47
CMD 54
CMD 43
CMD 50
CMD 59
•
the CC# Menu Key Lock prompt is set
to No for the D1256RB address.
Service Walk ?
Default Text ?
CMD 57
CMD 52
Change Skeds ?
Invisible Walk ?
Keypad Function options: P = Passcode;
E = Enabled (no passcode required);
Blank = Disabled
12
Bosch Security Systems, Inc. | 8/06 | F01U011791B
Download from Www.Somanuals.com. All Manuals Search And Download.
D1255RB/D1256RB/D1257RB | Installation Instructions | 5.0 Specifications
Ensure that CF 128 through CF 131, and
.
any other functions you are using in the
menu, are programmed E (enabled), not P
(passcode required). Refer to Figure 19.
Figure 19: Custom Functions
Keypad Functions
#
Custom Functions
E/P*
E
128 Custom Function 128
129 Custom Function 129
130 Custom Function 130
131 Custom Function 131
132 Custom Function 132**
133 Custom Function 133**
134 Custom Function 134**
135 Custom Function 135**
136 Custom Function 136**
137 Custom Function 137**
138 Custom Function 138**
139 Custom Function 139**
140 Custom Function 140**
141 Custom Function 141**
142 Custom Function 142**
143 Custom Function 143**
E
E
E
5.0 Specifications
Table 4:
Specifications for the D1255RB and D1256RB Keypads and the D1257RB Annunciator
Nominal 12 VDC supplied by the control panel
Power
Current Required
Wiring
Idle:
104 mA
Maximum:
225 mA, with annunciator lit, all 4 Status LEDs on, and warning tone on
4-wire supplies Data In, Data Out, + 12 VDC, and Common.
Maximum data loop resistance is 10 Ω.
Dimensions (H x W x D)
Base (HxW):
Cover :
4.6 in. x 8.2 in. (11.6 cm x 20.7 cm)
4.3 in. x 8.12 in. x 0.8 in. (10.9 cm x 20.6 cm x 2.9 cm)
Red
Color
16-character vacuum fluorescent display (VSD).
Each character is a 14-segment unit.
Display
Operating Temperature
Relative Humidity
+32°F to +122°F (0° C to +15° C)
5% to 85% at +86°F (+30° C)
Bosch Security Systems, Inc. | 8/06 | F01U011791B
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, NY 14450-9199
Customer Service: (800) 289-0096
Technical Support: (888) 886-6189
© 2006 Bosch Security Systems, Inc.
F01U011791B
Download from Www.Somanuals.com. All Manuals Search And Download.
|