ADC Telephone FPL Series User Manual

ADCP-90-328 • Issue 2 • November 2005  
FPL Series Termination/Splice Panel  
User Manual)  
2
3
4
5
6
8
9
1
1
1
1
1
4
5
6
7
8
2
2
2
2
2
0
1
2
3
4
2
2
2
2
3
6
7
8
9
0
3
3
3
3
3
2
3
4
5
6
3
3
4
4
4
8
9
0
1
2
4
4
4
4
4
4
5
6
7
8
5
5
5
5
5
0
1
2
3
4
5
5
5
5
6
6
7
8
9
0
6
6
6
6
6
2
3
4
5
6
1
0
1
2
6
6
7
7
7
8
9
0
1
2
1
1
17807-A  
FPL Termination/Splice Panel  
Content  
Page  
(continued)  
1345101 Rev A  
Page 1  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADCP-90-328 • Issue 2 • November 2005  
Figure 1 shows an example of a termination only panel, the 72 position model. Other models  
have analogous features.  
ADJUSTABLE  
MOUNTING  
BRACKET  
FPL  
CHASSIS  
ADJUSTABLE  
MOUNTING  
BRACKET  
ANGLED  
ADAPTERS  
CABLE CLAMP  
ASSEMBLY  
VERTICAL  
CABLE GUIDE  
2
8
1
1
1
1
1
4
5
6
7
8
2
2
2
2
2
0
1
2
3
4
2
2
2
2
3
6
7
8
9
0
3
3
3
3
3
3
2
3
4
5
6
9
3
3
4
4
4
8
9
0
1
2
4
4
4
4
4
4
5
6
7
8
5
5
5
5
5
0
1
2
3
4
5
5
5
5
6
6
7
8
9
0
4
6
6
6
6
6
2
3
4
5
6
1
0
6
6
7
7
7
8
9
0
1
2
5
6
1
1
1
2
TERMINATION  
BULKHEAD  
CABLE  
CLAMP  
COVER  
REMOVABLE  
FRONT DOOR  
VERTICAL  
CABLE GUIDE  
OPTIONAL  
LOCK MOUNT  
17816-A  
PATCH CORD  
DESIGNATION  
CARD  
Figure 1. 72 Position Termination Only Panel  
The features called out are as follows (from top center clockwise):  
FPL Chassis—is the boxlike, solid metal frame on which the panel is built. The chassis  
shown is 8.7 inches (22.1 cm) high, 16.4 inches (41.7 cm) wide, and 12.0 inches (30.5 cm)  
deep. This same chassis is also used for the 48 and 96 position panels, as well as for the  
48, 72, and 96 position termination and splice panels. Shorter-height chassis are used for  
the 12 and 24 position panels and a deeper chassis is used for the 144 position high density  
panel. For details, refer to Table 1 on Page 8.  
Adjustable Mounting Bracket—(one on each side) can be oriented to provide either 19-  
inch or 23-inch WECO or EIA rack mounting with either a 4-inch or 5-inch recess. The  
panel is shipped with the mounting brackets positioned for installation in a 19-inch rack  
with a 5-inch recess.  
Cable Clamp Assembly—is a kit used to clamp a cable to the panel. Two cable clamp  
assemblies are provided with every FPL panel. Each clamp can accommodate a maximum  
cable diameter of 0.80 inch (2.03 cm). A grounding lug is included with each cable clamp  
for use if needed.  
Page 3  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
Cable Clamp Cover—protects cable at entry to the panel (not present on 12 and 24  
position panels).  
Vertical Cable Guide—(one on each side) is a metal cable retainer designed to provide  
cable management by confining and directing patch cords to and from the panel and along  
the frame on which the panel is installed.  
Patch Cord Designation Card—is a laminated card fastened to the inside of the panel  
front door. The designation card is used to record the near-end and far-end termination  
locations of each patch cord installed on the panel.  
Optional Lock Mount—provides ability to lock front door.  
Removable Front Door—protects the termination bulkhead and can be removed to  
provide access to the bulkhead for connecting patch cords.  
Termination Bulkhead—provides a location for connecting patch cords. The bulkhead  
shown has 72 holes for 72 adapters. Other bulkheads for the chassis size shown provide 48  
or 96 locations for mounting connectors.  
Angled Adapters—are pass-through receptacles for connectors. They are angled to either  
left or right to hold terminated fibers at an angle with respect to the bulkhead. The purpose  
of the angle is prevent fiber bend.  
Figure 2 and Figure 3 show the 48 and 96 position panels, respectively. Figure 4 shows the three  
rack unit 24 position panel. Figure 5 shows the one rack unit 12/24 position panel.  
0
0
0
2
3
4
0
0
1
8
9
0
1
1
1
4
5
6
2
2
2
0
1
2
2
2
2
6
7
8
3
3
3
2
3
4
3
3
4
8
9
0
4
4
4
4
5
6
0
0
5
6
1
1
1
2
1
1
7
8
2
2
3
4
2
3
9
0
3
3
5
6
4
4
1
2
4
4
7
8
17808-A  
Figure 2. 48 Position FPL Termination Panel  
Page 4  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
2
3
4
5
6
8
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
2
6
50  
51  
52  
53  
54  
9
56  
57  
58  
59  
60  
62  
63  
64  
68  
69  
70  
71  
72  
27  
28  
29  
74  
75  
76  
77  
78  
80  
81  
82  
83  
84  
10  
11  
12  
86  
87  
88  
89  
90  
92  
93  
94  
95  
96  
3
0
6
5
66  
17815-A  
Figure 3. 96 Position FPL Termination Panel  
0
0
2
3
0
0
5
6
0
0
8
9
1
1
1
2
1
1
4
5
1
1
7
8
2
2
0
1
2
2
3
4
17820-A  
Figure 4. 24 Position FPL Termination Panel (3RU)  
Page 5  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
20973-A  
Figure 5. 12/24 Position FPL Termination Panel (1RU)  
Figure 6 shows a rear view of a termination and splice panel. The panel shown is the 72 position  
termination and splice panel.  
SPLICE  
AREA  
INTERNAL  
PIGTAIL  
17819-A  
SPLICE  
TRAY  
REMOVABLE  
REAR ACCESS  
DOOR  
OPTIONAL  
LOCK MOUNT  
Figure 6. FPL Termination and Splice Panel  
Page 6  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
The front side of the 72 position termination and splice panel is identical to the termination only  
panel shown in Figure 1. In general, the termination components of any FPL termination and  
splice panel are identical to the termination components of the panel’s termination and splice  
panel counterpart. Only the splice components are different.  
Figure 6 on the preceding page shows the typical components unique to the splice function of a  
termination and splice panel. They are as follows (from left to right in the figure):  
Splice Area—is a protected chamber within the chassis intended for splice trays. In  
termination only panels, this area can be used for cable storage.  
Internal Pigtail—is a factory-installed fiber optic cable with a connector at one end and a  
bare fiber on the other end. The connector end of the pigtail is terminated on the rear side  
of the termination bulkhead. The bare end of the pigtail is available for splicing to a bare  
fiber at the customer site. The cable from which the bare fibers are broken out for splicing  
may be either Outside Plant (OSP) or Intra Facility Cable (IFC).  
Splice Tray—is a tray installed in the splice area. Each tray holds one or more splice chips  
of a selected type.  
Removable Rear Access Door—provides access to the splice area.  
Optional Lock Mount—provides ability to lock rear access door.  
Figure 7 shows the 144 position high density termination and splice panel. Additional features  
called out here are the split termination bulkhead, which provides the room required for the  
greater number of adapters, and the splice area access door, which opens into a locked  
horizontal position to serve as a splice deck.  
SPLICE AREA  
ACCESS DOOR  
SPLIT  
TERMINATION  
BULKHEAD  
17906-A  
Figure 7. 144 Position High Density Termination and Splice Panel  
Page 7  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
2 ACCESSORIES  
The following accessory items may be ordered separately for FPL panels:  
• Single and dual splice trays (for types, see Splice Type in Table 1 below)  
• Additional kits for clamping and grounding cables  
• Key locks for front and rear doors  
• Buildout attenuators (ST and biconic)  
• Bulkhead attenuators (ST, SC, D4, FC, and biconic)  
3 SPECIFICATIONS AND DIMENSIONS  
Table 1 lists specifications for the FPL modules.  
Table 1. FPL Modules Specifications  
PARAMETER  
SPECIFICATION  
Common to All Panels  
Rack mounting  
Hole spacing  
19-inch (48.26 cm) or 23-inch (58.42 cm)  
EIA or WECO  
Recess options  
Connector types  
4-inch (10.16 cm) or 5-inch (12.7 cm) recess  
Multimode SC, SC duplex, ST©, LX.5©, and LC;  
Singlemode FC, FC (zirconia adapter), FC (8o polish), SC, SC (zirco-  
nia adapter), SC (8o polish), SC duplex, ST©, ST© (zirconia adapter),  
E-2000 (8o polish), E-2000 (flat polish), LX.5©, LC  
Pigtail type  
Splice type  
Stranded or ribbon  
Bare fusion, heat shrink fusion, mechanical, rotary, FibrLok, Raychem  
Universal (R), Nortel, AFL  
Pre-termination (optional) cable types  
Multimode IFC stranded 62.5/125;  
Singlemode IFC stranded, IFC plenum stranded, OSP single armor  
stranded, indoor-outdoor, OSP dielectric stranded, IFC Maxi-Strip,  
IFC ribbon, OSP single armor ribbon, OSP dielectric ribbon  
12/24 Position Panel (1RU)  
Dimensions (H x W x D)  
1.72 inch x 17.0 in. x 11.48 in.  
(4.4 cm x 43.2 cm x 29.2 cm)  
Capacity  
12 or 24 termination positions  
LX.5© and LC connectors double the termination capacity  
24 Position Panel (3RU)  
Dimensions (H x W x D)  
5.0 inch x 16.4 in. x 12.0 in.  
(12.7 cm x 41.7 cm x 30.5 cm)  
Capacity  
24 termination positions  
LX.5© and LC connectors double the termination capacity  
Page 8  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ADCP-90-328 • Issue 2 • November 2005  
Table 1. FPL Modules Specifications  
SPECIFICATION  
PARAMETER  
48/72/96 Position Panel (5RU)  
Dimensions (H x W x D)  
8.7.0 inch x 21.9 in. x 12.0 in.  
(22.1 cm x 56.7 cm x 30.5 cm)  
Capacity  
48, 72, or 96 termination positions  
LX.5© and LC connectors double the termination capacity  
144 Position High Density Panel (5RU)  
Dimensions (H x W x D)  
8.7.0 inch x 21.9 in. x 15.0 in.  
(22.1 cm x 56.7 cm x 38.1 cm)  
23.0 inch (58.42 cm)  
Depth with rear door splice deck open  
Capacity  
144 termination positions  
Figure 8 shows dimensions for the 12/24 position 1RU panel.  
11.48 IN.  
(29.2 CM)  
4.86 IN.  
(12.3 CM)  
TOP VIEW  
17.0 IN.  
(43.2 CM)  
20.24 IN.  
(51.4 CM)  
22.32 IN. (56.7 CM)  
23-IN. RACK MOUNT (58.4 CM)  
1.72 IN.  
(4.4 CM)  
18.32 IN. (46.5 CM)  
19-IN. RACK MOUNT (48.3 CM)  
20959-A  
FRONT VIEW  
1.25 IN.  
(3.2 CM)  
Figure 8. 12/24 Position 1RU Panel  
Page 9  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
Figure 9 shows dimensions of the 24 position 3RU panel.  
12.0 IN.  
(30.5 CM)  
5.0 IN.  
(12.7 CM)  
TOP VIEW  
16.4 IN.  
(41.7 CM)  
21.9 IN.  
(55.5 CM)  
22.32 IN. (56.7 CM)  
23-IN. RACK MOUNT (58.4 CM)  
18.32 IN. (46.5 CM)  
19-IN. RACK MOUNT (48.3 CM)  
4.0 IN.  
(10.2 CM)  
2.25 IN.  
(5.7 CM)  
5.0 IN.  
(12.7 CM)  
17822-A  
FRONT VIEW  
Figure 9. Panel Dimensions (24 Position 3RU)  
Page 10  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
Figure 10 shows dimensions of the 48/72/96 position panel.  
12.0 IN.  
(30.5 CM)  
5.0 IN.  
(12.7 CM)  
TOP VIEW  
16.4 IN.  
(41.7 CM)  
21.9 IN.  
(55.5 CM)  
22.32 IN. (56.7 CM)  
23-IN. RACK MOUNT (58.4 CM)  
18.32 IN. (46.5 CM)  
19-IN. RACK MOUNT (48.3 CM)  
8.7 IN.  
(22.1 CM)  
4.0 IN.  
(10.2 CM)  
2.25 IN.  
(5.7 CM)  
5.0 IN.  
(12.7 CM)  
17821-A  
FRONT VIEW  
Figure 10. Panel Dimensions (48/72/96 Position)  
Page 11  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
Figure 11 shows dimensions of the 144 position high density panel  
15.0 IN.  
(38.1 CM)  
5.0 IN.  
(12.7 CM)  
TOP VIEW  
16.4 IN.  
(41.7 CM)  
21.9 IN.  
(55.5 CM)  
22.32 IN. (56.7 CM)  
23-IN. RACK MOUNT (58.4 CM)  
18.32 IN. (46.5 CM)  
19-IN. RACK MOUNT (48.3 CM)  
8.7 IN.  
(22.1 CM)  
4.0 IN.  
(10.2 CM)  
2.25 IN.  
(5.7 CM)  
5.0 IN.  
(12.7 CM)  
17824-A  
FRONT VIEW  
Figure 11. Panel Dimensions (144 Position)  
Page 12  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
4 APPLICATION  
The FPL Series Termination/Splice Panel is designed for use in central offices, remote offices,  
and in local area networks (LANs) that use a fiber optic cable system. The panel provides a  
common point for performing any of the following functions:  
• Terminating OSP or IFC cables  
• Terminating Fiber Optic Terminal (FOT) equipment patch cords  
• Storing excess FOT equipment patch cord length  
• Connecting FOT equipment with OSP cables  
• Mounting and protecting splices  
When used with OSP cable, the FPL panel may be used for either interconnect or cross-connect  
applications. Figure 12 and Figure 13 provide a pictorial comparison of these two types of  
applications. As shown, in both interconnect and cross-connect applications, the OSP cable is  
terminated on the rear side of the panel and spliced to the internal pigtails within the panel.  
Also, in both applications, the pigtails are connected to the rear side of the adapters on the  
termination bulkhead. The applications differ in what occurs on the front side of the panel.  
• In an interconnect application, shown in Figure 12, patch cords from the FOT equipment  
are connected directly to fibers spliced and terminated on the rear side of the same panel.  
• In a cross-connect application, shown in Figure 13, patch cords from the FOT equipment  
are terminated on one panel and the fibers are spliced and terminated on a second panel,  
with cross-connect patch cords providing links between the two panels. This two-panel  
arrangement provides more flexibility in testing and patching optical circuits than is  
provided by a single panel arrangement.  
OSP  
CABLE  
FOT EQUIPMENT  
OSP CONNECTOR PANEL  
FOT EQUIPMENT  
PATCH CORDS  
FOT EQUIPMENT  
PIGTAIL  
SPLICE  
BULKHEAD  
ADAPTER  
FOT EQUIPMENT  
2762-B  
Figure 12. Interconnect Application  
Page 13  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
FOT EQUIPMENT  
FOT EQUIPMENT  
CONNECTOR PANEL  
FOT EQUIPMENT  
PATCH CORDS  
FOT EQUIPMENT  
FOT EQUIPMENT  
BULKHEAD  
ADAPTER  
CROSS-CONNECT  
PATCH CORDS  
OSP  
CABLE  
OSP CONNECTOR PANEL  
PIGTAIL  
SPLICE  
BULKHEAD  
ADAPTER  
2763-B  
Figure 13. Cross-Connect Application  
5 INSTALLATION  
Installation will vary depending on how the panel was outfitted in the factory and how it will be  
used. Installation may include any of the following tasks: installing adapters; installing internal  
pigtails; mounting the panel on the rack; installing OSP or IFC cable (either connectorized or  
bare fiber); installing FOT patch cords; and installing cross-connect patch cords (in a cross-  
connect application only). For step by step instructions, refer to the following subsections.  
5.1 Installing Adapters  
FPL panels are usually shipped with adapters already installed; however, in some case, you may  
need to install adapters. The exact procedure to be used depends on the adapter type. Figure 14  
shows an example. For specific instructions, refer to the installation drawing that came with the  
adapters.  
Note: To avoid getting dirt into the adapter, leave the dust covers in place on the adapters  
when mounting them on the retainers. If dirt does enter the adapter, use the ADC Fiber  
Connector/Adapter Cleaning Kit (sold separately) to clean the adapter. Follow the  
cleaning instructions provided with the kit.  
Page 14  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ADCP-90-328 • Issue 2 • November 2005  
COMPRESS  
RELEASE  
TABS  
COMPRESS  
RELEASE  
TABS  
ROTATE AND  
SNAP INTO  
SLOT  
ROTATE AND  
SNAP INTO  
SLOT  
COMPRESS  
RELEASE  
TABS  
COMPRESS  
RELEASE  
TABS  
17846-A  
1
2
Figure 14. Example of Installing Adapters  
5.2 Installing Pigtails  
Pigtails may be installed in any FPL panel (including termination only panels) to utilize the rear  
area of the panel for splicing. Pigtails are installed with the connectorized end connected to the  
adapters on the rear side of the termination panel and with the bare fiber ends positioned within  
a splice tray (for an illustration, see Figure 6 on Page 6). 3m pigtails are used with the excess  
slack coiled within the chassis to provide a service loop for future use if needed.  
Use the following procedure to install pigtails:  
1. Separate out 12 pigtails. Apply a pair of designation tags to each pigtail for identification.  
Attach one tag next to the connector and the other tag near the bare fiber end.  
2. Working from the rear side of the panel, connect the pigtails to the interior side of  
adapters/receptacles marked with the corresponding numbers. The connector numbers are  
silk-screened on the interior side of the bulkhead, as shown in Figure 15 for the 72  
position panel.  
3. Group the 12 pigtails into a bundle and use the twist-lock fiber retainers provided to hold  
the bundle together.  
Page 15  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
17825-A  
Figure 15. Connector Numbers on Rear of 72 Position Bulkhead  
4. Route the pigtails within the panel as shown in Figure 16 (12/24 position 1RU panel),  
Figure 17 (24 position 3RU panel), Figure 18 (48/72/96 position panel), or Figure 19 (144  
position panel).  
5. Continue installing the pigtails in groups of 12 until all of the pigtails are labeled,  
connected, and routed to the splice area.  
OSP CABLE  
CLAMP  
20961-A  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
Figure 16. Pigtail Routing (12/24 Position 1RU Panel)  
Page 16  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
LEFT SIDE  
PIGTAILS  
RIGHT SIDE  
PIGTAILS  
(AS VIEWED  
FROM REAR)  
(AS VIEWED  
FROM REAR)  
KURLYLOCKS  
OR FANNING TREE  
(ATTACHED TO  
OSP CABLE  
CLAMP  
TOP OF CHASSIS)  
17920-A  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
Figure 17. Pigtail Routing (24 Position 3RU Panel)  
LEFT SIDE  
PIGTAILS  
RIGHT SIDE  
PIGTAILS  
(AS VIEWED  
FROM REAR)  
(AS VIEWED  
FROM REAR)  
KURLYLOCKS  
OR FANNING TREE  
(ATTACHED TO  
OSP CABLE  
CLAMP  
TOP OF CHASSIS)  
17919-A  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
Figure 18. Pigtail Routing (48/72/96 Position Panel)  
Page 17  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
RIGHT SIDE PIGTAILS  
(AS VIEWED FROM REAR)  
LEFT SIDE PIGTAILS  
(AS VIEWED FROM REAR)  
PIGTAILS  
17910-A  
Figure 19. Pigtail Routing (144 Position High Density Panel Shown)  
5.3 Mounting the Panel on the Rack  
Installation always requires mounting the panel on a rack.  
Page 18  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
The panel can be mounted in either a 19- or 23-inch EIA or WECO equipment rack with either  
a 4-inch or 5-inch recess. The panel is shipped with the mounting brackets positioned for  
installation in a 19-inch rack with a 5-inch recess. For other mounting configurations, the  
brackets must be removed and reinstalled in a different orientation.  
Use the following procedure to mount the panel on the rack:  
1. If installing the FPL panel in a 23-inch equipment rack, or if changing from a 5-inch to a  
4-inch recess:  
a. Remove the screws that secure each mounting bracket to the sides of the chassis and  
then remove each bracket from the chassis.  
b. Orient each bracket for the required mounting position as shown in Figure 20.  
c. Refasten the mounting brackets to the chassis using the original mounting screws.  
5-INCH  
5-INCH  
RECESS  
RECESS  
4-INCH  
4-INCH  
RECESS  
RECESS  
56  
62  
68  
56  
62  
68  
57  
63  
69  
57  
63  
69  
58  
64  
70  
58  
64  
70  
59  
65  
71  
59  
65  
71  
60  
66  
72  
60  
66  
72  
19-INCH  
23-INCH  
MOUNTING  
MOUNTING  
17827-A  
Figure 20. Mounting Bracket Installation  
2. Align the bracket holes with the holes in the rack channel.  
3. Secure the mounting brackets to the rack channel using the #12 machine screws and flat  
washers provided.  
5.4 Installing OSP or IFC Cable  
Cable installation should occur after the panel is mounted in the equipment rack, as described in  
Section 5.3. Installation consists of routing the cable to the panel, stripping back the outside  
sheath of the cable to expose the optical fibers, installing a cable clamp to secure the cable to the  
panel, and routing the fibers to the splice tray. The cable must also be grounded if it has a  
metallic sheath or metallic strength member.  
The cable clamp used in cable installation is shipped with the panel. Two clamps are provided  
since two cables may be installed on a single panel if desired. Each clamp can accommodate  
one cable with an outside diameter of 0.4 to 0.8 inches (1.02 to 2.03 cm).  
Page 19  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
Typically, only one cable is installed per panel. The cable clamp can be installed on either side.  
A grounding lug is included with each clamp for grounding OSP cables that have metallic  
strength members or metallic sheaths.  
Allow a fiber service loop of at least 8 feet (2.5 meters) when stripping the sheath off the cable.  
This will provide sufficient length for routing the buffer tubes within the FPL panel and for  
splicing. After entry, the buffer tubes are routed to the splice tray. The splice tray mounts on the  
bottom of the FPL panel.  
Use the following procedure to secure the OSP cable at the fiber entry point and to route the  
optical fibers into the FPL panel:  
1. Route the OSP cable to the selected entry opening at the side of the FPL panel.  
Note: Cables may enter the FPL panel from either the top or bottom and may be clamped  
to either the left or right side  
2. Strip back the cable sheath approximately 96 inches (2.5 meters) to expose the optical  
fibers. Follow the cable manufacturer’s recommendations when stripping the sheath.  
Note: If the cable is filled with water blocking compound, the cable end must be sealed to  
prevent leakage. A blocking kit (accessory item) is required for sealing the cable end.  
Install the kit according to the instructions provided with the kit.  
Note: If cable has a metallic sheath, a special connector is provided with the cable  
grounding kit (accessory item FIP-ACC-GK) for grounding the sheath. Refer to Appendix  
A for the installation procedures for ScotchLok 4460 Shield Connectors which are  
manufactured by the 3M Company.  
3. Determine the correct clamp and grommet combination required to secure the cable to the  
panel. A rubber clamp and three grommets of various sizes are provided. Select a grommet  
that when placed around the cable, has a gap of nearly zero to 0.30 inches (0.76 cm). If the  
cable diameter is greater than 0.70 inches (1.78 cm), only the rubber clamp is required.  
4. Use the rubber clamp, clamp cover, grommet (if required), and two screws to secure the  
cable end to the side of the FPL panel chassis, as shown in Figure 21 for a top entry cable  
and in Figure 22 for a bottom entry cable.  
Note: The Rear Protective Plate, identified in the figures, is not used with the 24 position  
panel. The plate is not included in the cable clamp kit.  
Page 20  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ADCP-90-328 • Issue 2 • November 2005  
OUTSIDE  
PLANT  
CABLE  
GROMMET  
5
5
5
5
6
6
7
8
9
0
6
6
6
6
6
YOKES  
CABLE  
2
3
4
5
6
6
6
7
7
7
8
9
0
1
2
CLAMP  
COVER  
#6 - 32 x  
1.375-IN.  
SCREWS  
REAR  
PROTECTIVE  
PLATE  
17828-A  
#6 - 32 x  
0.25-IN.  
SCREWS  
Figure 21. Cable Clamp Assembly (Top Entry)  
Note: Rear Protective Plate shown in these figures is not used on 24 position panel.  
5
5
5
5
6
6
7
8
9
0
6
6
6
6
6
2
3
4
5
6
6
6
7
7
7
8
9
0
1
2
#6 - 32 x  
0.25-IN.  
SCREWS  
CABLE  
CLAMP  
COVER  
YOKES  
REAR  
PROTECTIVE  
PLATE  
GROMMET  
OUTSIDE  
PLANT  
CABLE  
#6 - 32 x  
1.375-IN.  
SCREWS  
17829-A  
Figure 22. Cable Clamp Assembly (Bottom Entry)  
Page 21  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
5. A grounding lug is provided for grounding metallic sheaths and metallic core members.  
Use the nut and screw provided to fasten the grounding lug to the chassis at the point  
shown in Figure 23. If the sheath bonding kit was installed, connect a bonding wire  
between the connector stud and the lug. If the cable has a metallic core member, insert the  
core member into the lug and tighten.  
6. If splicing will not be done at this time, coil the buffer tubes around the radius limiters on  
the bottom of the FPL panel and close the rear cover. If splicing will be done immediately,  
proceed to the section that covers splicing.  
OUTSIDE  
PLANT  
CABLE  
SHEATH BONDING  
KIT CONNECTOR  
5
5
5
5
6
6
7
8
9
0
6
6
6
6
6
2
3
4
5
6
6
6
7
7
7
8
9
0
1
2
BONDING  
WIRE  
REAR  
PROTECTIVE  
PLATE  
GROUNDING  
LUG  
17830-A  
Figure 23. Grounding the OSP Cable  
5.5 Splicing  
If you are installing a termination and splicing panel, and have just finished installing your OSP  
or IFC cable, you can now proceed to the splicing procedure provided in this section. You will  
be doing one splice tray at a time to completion, then going on to complete the next splice tray  
(if the panel has more than one). For each splice tray, you will assign paired fibers and cable  
subunits bundles of 12, measure for correct service loop length, remove the splice tray to a  
working surface for splicing, and return the splice tray to the panel.  
The purpose of a splice tray is to protect the splices. The splice tray mounts on the bottom of the  
FPL panel, within the chassis in the mid-size models and on the splice area access door in the  
high density model. A rubber strap is used to secure the splice tray to the bottom of the FPL  
panel or to the splice area access door.  
Page 22  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
In a typical installation, the methods and procedures that will be used for splicing are  
determined by local practice. Use the following procedure to organize the pigtails and buffer  
tubes for splicing and to store completed splices:  
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not  
look into the optical bulkhead of an operational transmitter or into the receiver end of an active  
fiber. A protective cap or hood MUST be immediately placed over any radiating bulkhead  
adapter/receptacle or optical fiber connector to avoid potential exposure to dangerous infrared  
optical radiation. The protective cover also prevents dirt particles from entering the connector.  
1. Uncoil all the pigtail bundles and buffer tubes from the radius limiters within the FPL  
panel.  
2. Group the pigtails and buffer tubes for fibers 1 - 12 into a single common bundle. Use the  
twist-lock retainers provided to hold the pigtail and buffer tube bundle together.  
3. Group the remaining pigtails and buffer tubes into similar bundles with one bundle for  
each group of 12 pigtails and buffer tubes. Secure the bundles together using twist-lock  
retainers.  
4. Identify the first splice tray and the one or two bundles to be assigned to it. For a single  
height tray, assign one bundle. For a dual height tray, assign two bundles.  
5. Place the splice tray in its correct location in the panel and coil the one or two bundles  
assigned to it around the radius limiters as shown in Figure 24 (12/24 position 1RU panel),  
Figure 25 (right cable exit, 24/48/72/96 position panel), Figure 26 (left cable exit, 48/72/  
96 position panel), Figure 27 (right cable exit, 144 position panel), or Figure 28 (left cable  
exit, 144 position panel).  
OSP CABLE  
CLAMP  
20961-A  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
Figure 24. Pigtail Routing (12/24 Position 1RU Panel)  
Page 23  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
LEFT SIDE  
PIGTAILS  
RIGHT SIDE  
PIGTAILS  
(AS VIEWED  
FROM REAR)  
(AS VIEWED  
FROM REAR)  
KURLYLOCKS  
OR FANNING TREE  
(ATTACHED TO  
OSP CABLE  
CLAMP  
TOP OF CHASSIS)  
17920-A  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
Figure 25. Right Cable Exit (Left as Viewed from Rear), 24/48/72/96 Position Panel  
LEFT SIDE  
PIGTAILS  
RIGHT SIDE  
PIGTAILS  
(AS VIEWED  
FROM REAR)  
(AS VIEWED  
FROM REAR)  
KURLYLOCKS  
OR FANNING TREE  
(ATTACHED TO  
OSP CABLE  
CLAMP  
TOP OF CHASSIS)  
17919-A  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
Figure 26. Left Cable Exit (Right as Viewed from Rear), 24/48/72/96 Position Panel  
Page 24  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
RIGHT SIDE PIGTAILS  
(AS VIEWED FROM REAR)  
LEFT SIDE PIGTAILS  
(AS VIEWED FROM REAR)  
OSP CABLE  
CLAMP  
PIGTAILS  
BUFFER  
TUBES  
17909-A  
Figure 27. Right Cable Exit (Left as Viewed from Rear), 144 Position Panel  
Page 25  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
TOP VIEW  
(SHOWN WITH TOP OF CHASSIS REMOVED)  
RIGHT SIDE PIGTAILS  
(AS VIEWED FROM REAR)  
LEFT SIDE PIGTAILS  
(AS VIEWED FROM REAR)  
OSP CABLE  
CLAMP  
PIGTAILS  
BUFFER  
TUBES  
17918-A  
Figure 28. Left Cable Exit (Right as Viewed from Rear),144 Position Panel  
6. Lay the bundle(s) across the top of the splice tray as shown in the figures and determine  
the point at which each pigtail and cable subunit should be attached to the splice tray.  
Note: All fibers must enter the splice tray from the same side as shown in Figure 29.  
Page 26  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
BUFFER TUBES  
SECURE PIGTAILS AND BUFFER TUBES  
TO SPLICE TRAY WITH TIE WRAPS  
2776-A  
Figure 29. Routing Bundles into Splice Tray  
7. Mark each buffer tube and pigtail to indicate the attachment point to the splice tray. Make  
sure approximately 2 feet (61 cm) of fiber are left beyond the attachment point for  
splicing.  
8. Remove the splice tray from the FPL panel and uncoil the bundles from the radius limiters.  
9. Beginning at the points marked in step 7, remove the buffer tubes and pigtail jackets to  
expose the optical fibers. Clean fibers as recommended by cable manufacturer.  
10. Secure the cable subunits and pigtails to the splice tray using tie wraps. The tie wraps  
should be tight enough to secure the pigtail jackets and cable subunits but should not pinch  
the fibers inside.  
11. Complete each splice according to local splicing practice. Note that the numbered tag that  
is attached to each pigtail corresponds to the number on the bulkhead connector plate.  
12. Carefully secure each completed splice to the splice chip on the inside of the splice tray.  
13. When all splices are complete, place the clear plastic cover over the splice tray to protect  
the finished splices.  
14. Coil up the bundles around the radius limiters (in the same direction as coiled in step 5)  
and place the splice tray on the bottom of the FPL panel.  
15. Secure the splice tray(s) to the bottom of the FPL panel using the rubber strap provided.  
An example of a splice tray mounted in a FPL panel is shown in Figure 30.  
16. Record all terminations on the front designation cards as required by local practice.  
17. Repeat steps 4 through 16 for the next splice tray, if any remains. Continue until all the  
splice trays have been installed.  
Page 27  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
17832-A  
Figure 30. Splice Tray Mounted in 24 Position FPL Panel  
18. Close and latch front and rear covers.  
5.6 Installing FOT Patch Cords  
In both interconnect and cross-connect applications, FOT equipment patch cords are installed  
between the FOT equipment and the FLP panel. The following sections describe the installation  
procedure to use based on the application.  
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not  
look into the optical bulkhead of an operational transmitter or into the receiver end of an active  
fiber. A protective cap or hood MUST be immediately placed over any radiating bulkhead  
adapter/receptacle or optical fiber connector to avoid the potential exposure to dangerous  
infrared optical radiation. The protective cover also prevents dirt particles from entering the  
connector.  
5.6.1 Interconnect Application  
In an interconnect application, the FOT equipment patch cords are connected to the appropriate  
bulkhead adapters/receptacles at the OSP-dedicated FPL panel and then routed to the FOT  
equipment. Any excess patch cord slack must be stored at the FOT equipment or in a separate  
storage panel.  
Use the following procedure to install FOT equipment patch cords in interconnect applications:  
Page 28  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ADCP-90-328 • Issue 2 • November 2005  
1. Connect the FOT equipment patch cord to the appropriate bulkhead adapter/receptacle at  
the front side of the FPL panel as shown in Figure 31.  
Note: If using biconic or ST receptacles, install a 0 dB build-out to permit installation of  
the patch cord.  
2. Use the retainers at the left and right sides of the FPL panel to route patch cords away from  
the front side of the FPL panel.  
3. Route patch cord from the FPL panel to the FOT equipment.  
4. Connect the FOT equipment patch cord to the FOT equipment.  
5. When all FOT patch cords have been connected, install the patch cord shields at the front  
of the FPL panel. (For better access to the vertical cable guides, the patch cord shield may  
optionally be removed during installation, as shown in Figure 31.)  
6. Close FPL panel front cover and latch.  
PATCH  
CORDS  
PATCH  
2
8
9
CORDS  
1
1
1
1
1
4
5
6
7
8
2
2
2
2
2
0
1
2
3
4
2
2
2
2
3
6
7
8
9
0
3
4
5
6
3
3
3
3
3
2
3
4
5
6
3
3
4
4
4
8
9
0
1
2
4
4
4
4
4
4
5
6
7
8
5
5
5
5
5
0
1
2
3
4
5
5
5
5
6
6
7
8
9
0
6
6
6
6
6
2
3
4
5
6
1
0
1
2
6
6
7
7
7
8
9
0
1
2
1
1
PATCH  
CORD  
SHIELD  
PATCH  
CORD  
17836-A  
SHIELD  
Figure 31. Connecting FOT Equipment Patch Cords — Interconnect Application  
5.6.2 Cross-Connect Application  
In a cross-connect application, the FOT equipment patch cords are connected to the FOT  
equipment and then routed to the FOT equipment FPL panel. Some of the excess patch cord  
slack may be stored on the bottom of the FPL panel.  
Use the following procedure to install FOT equipment patch cords in cross-connect  
applications:  
1. Connect the FOT equipment patch cord to the FOT equipment.  
Page 29  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
2. Route the patch cord from the FOT equipment to the rear side of the FPL panel.  
3. Connect the FOT equipment patch cord to the appropriate bulkhead adapter/receptacle  
within the FPL panel as shown in Figure 32.  
Note: If using biconic or ST receptacles, install a 0 dB build-out to permit installation of  
the patch cord.  
4. Coil excess patch cord slack around the radius limiters on the bottom of the FPL panel.  
5. Use the retainers at the top, left, and right sides of the FPL panel to route patch cords away  
from the rear side of the panel.  
6. When all FOT patch cords have been connected, close the rear cover and latch.  
FROM FOT  
EQUIPMENT  
FROM FOT  
EQUIPMENT  
17835-A  
Figure 32. Connecting FOT Equipment Patch Cords — Cross-Connect Application  
6 OPERATION (CROSS-CONNECT PATCH CORDS)  
Cross-connect patch cords are routed between FPL panels by way of vertical cable guides and  
horizontal troughs. Any excess patch cord length must be taken up within the guideways or  
stored using Interbay Management Panels or a separate storage panel.  
Use the following procedure for routing and connecting each cross-connect patch cord:  
Page 30  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
ADCP-90-328 • Issue 2 • November 2005  
1. Open the front cover of both the FOT equipment and OSP-dedicated FPL panel.  
Danger: Infrared radiation is invisible and can seriously damage the retina of the eye. Do not  
look into the optical bulkhead of an operational transmitter or into the receiver end of an active  
fiber. A protective cap or hood MUST be immediately placed over any radiating bulkhead  
adapter/receptacle or optical fiber connector to avoid the potential exposure to dangerous  
infrared optical radiation. The protective cover also prevents dirt particles from entering the  
connector.  
2. Connect the cross-connect jumper to the appropriate bulkhead adapter/receptacle at the  
front side of the first FPL panel as shown in Figure 33.  
Note: If using biconic or ST receptacles, install a 0 dB build-out to permit installation of  
the patch cord.  
3. Use the retainers at the left and right sides of the FPL panel to route patch cords away from  
the front side of the FPL panel.  
4. Route patch cord from the first FPL panel to the second FPL panel.  
5. Connect the cross-connect jumper to the appropriate bulkhead adapter/receptacle at the  
front side of the second FPL panel as shown in Figure 33.  
Note: For better access to the vertical cable guides, the patch cord shield may optionally  
be removed during installation, as shown in Figure 33.  
6. Close the front covers on both FPL panels and latch.  
PATCH  
CORDS  
PATCH  
2
CORDS  
8
14  
20  
26  
3
4
5
6
32  
33  
34  
35  
36  
9
38  
39  
40  
41  
42  
15  
16  
17  
18  
44  
45  
46  
47  
48  
21  
22  
23  
24  
50  
51  
52  
53  
54  
27  
28  
29  
30  
56  
57  
58  
59  
60  
62  
63  
64  
65  
66  
10  
11  
12  
68  
69  
70  
71  
72  
PATCH  
CORD  
SHIELD  
PATCH  
CORD  
17836-A  
SHIELD  
Figure 33. Connecting Cross-Connect Patch Cords  
Page 31  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
7 CUSTOMER INFORMATION AND ASSISTANCE  
PHONE:  
U.S.A. OR CANADA  
Sales: 1-800-366-3891 Extension 73000  
Technical Assistance: 1-800-366-3891  
Connectivity Extension 73475  
Wireless Extension 73476  
EUROPE  
Sales Administration: +32-2-712-65 00  
Technical Assistance: +32-2-712-65 42  
EUROPEAN TOLL FREE NUMBERS  
Germany:  
UK:  
Spain:  
France:  
Italy:  
0180 2232923  
0800 960236  
900 983291  
0800 914032  
0800 782374  
ASIA/PACIFIC  
Sales Administration: +65-6294-9948  
Technical Assistance: +65-6393-0739  
ELSEWHERE  
Sales Administration: +1-952-938-8080  
Technical Assistance: +1-952-917-3475  
WRITE:  
ADC TELECOMMUNICATIONS, INC  
PO BOX 1101,  
MINNEAPOLIS, MN 55440-1101, USA  
ADC TELECOMMUNICATIONS (S'PORE) PTE. LTD.  
100 BEACH ROAD, #18-01, SHAW TOWERS.  
SINGAPORE 189702.  
ADC EUROPEAN CUSTOMER SERVICE, INC  
BELGICASTRAAT 2,  
1930 ZAVENTEM, BELGIUM  
PRODUCT INFORMATION AND TECHNICAL ASSISTANCE:  
13944-RM  
Contents herein are current as of the date of publication. ADC reserves the right to change the contents without prior notice.  
In no event shall ADC be liable for any damages resulting from loss of data, loss of use, or loss of profits and ADC further  
disclaims any and all liability for indirect, incidental, special, consequential or other similar damages.This disclaimer of  
liability applies to all products, publications and services during and after the warranty period.This publication may be  
verified at any time by contacting ADC's Technical Assistance Center.  
© 2005, ADC Telecommunications, Inc.  
All Rights Reserved  
Printed in U.S.A  
Page 32  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
ADCP-90-328 • Issue 2 • November 2005  
APPENDIX A: SHIELD CONNECTOR INSTALLATION  
This appendix provides the procedures for installing Scotchlok 4460 Shield Connectors, which  
are manufactured by the 3M Company and utilized in the Fiber Management Panel. The shield  
connector kit provides a means for grounding cables that have a metallic shield. Use the  
following procedure to install each kit:  
1. The shield connector kit is comprised of the components shown in Figure 34.  
2 SECURING NUTS  
TOP  
BASE  
9172-A  
Figure 34. Kit Components  
2. Prepare the cable by cutting the shield flush with the outer cable sheath as shown in Figure 35.  
If the cable has a double sheath, cut only the outer sheath and shield leaving the inner sheath  
intact as shown.  
SINGLE SHEATH CABLE  
CABLE  
SHEATH  
CORE  
WRAP  
.75 IN. (19 mm)  
DOUBLE SHEATH CABLE  
OUTER  
SHEATH  
INNER  
SHEATH  
0.13 IN  
(3mm)  
.75 IN. (19 mm)  
9173-A  
CORE  
WRAP  
Figure 35. Cable Preparation  
Page 33  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
ADCP-90-328 • Issue 2 • November 2005  
Reproduced by permission of 3M Company, from 3M Instruction Bulletin, Issue 1, dated February 1985, Number 43-7018-2209-9.  
3. Make a one-inch cut in the cable sheath opposite the point at which the connector will be  
attached as shown in Figure 36.  
1.0 IN. (25 mm)  
9174-A  
Figure 36. Cutting Cable Sheath  
4. If installing single shield cable, insert connector base between shield and core wrap. If  
installing double shield cable, insert connector base between shield and inner sheath.  
5. Slide connector into cable until stops contact outer sheath. Tap on shield above connector  
at point shown in Figure 37 to set teeth.  
TAP HERE  
9175-A  
Figure 37. Setting Connector Teeth  
6. Install bonding wire on stud and place connector top over bonding wire. Do not tap on  
connector top.  
7. Install both nuts on connector as shown in Figure 38 and tighten.  
9176-A  
Figure 38. Bonding Wire Installation  
Page 34  
© 2005, ADC Telecommunications, Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     

Abocom Headphones BSH203 User Manual
Acer Computer Monitor AL1715 User Manual
Adcom Stereo Amplifier GFA 555se User Manual
Alamo Compact Loader 7214 MSL User Manual
Allied Telesis Switch AT GS950 48 User Manual
American Standard Bathroom Aids 255102 User Manual
Atlona Marine Radio AT HDWP RSNET User Manual
ATN Inc Microscope Magnifier 10x65Z User Manual
Axis Communications Security Camera P5414 E User Manual
Beko Refrigerator CN 142220 DS User Manual