036-21300-002-A-0905
DESCRIPTION
These completely assembled units include a well-insulated cabinet, a
DX cooling coil with copper tubes and aluminum fins, expansion
valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower
motor, an adjustable belt drive, a blower motor contactor and a small
holding charge of refrigerant-22.
®
The units are shipped in the vertical position ready for field installation.
They can be installed for horizontal operation by reversing the position
of the solid bottom panel with the return air duct flange on the front of
the unit.
Technical Guide
ACCESSORIES—FIELD INSTALLED
SUPPLY AIR PLENUMS
SPLIT-SYSTEM
These fully insulated plenums are available for free standing units
located within the conditioned space, are shipped knocked-down for
easy field assembly, are finished to match the exterior of the basic
unit, and have double deflection grills that can be adjusted to vary the
throw, spread and drop of the supply air.
EVAPORATOR BLOWERS
K2EU060, K4EU090, K3EU120 &
K3EU180
RETURN AIR GRILLS
These expanded metal grills are available for free standing units
located within the conditioned space, are finished to match the exterior
of the basic unit and are shipped in one piece for easy installation.
5 THRU 15 NOMINAL TONS
BASES
Bases are available to raise vertical units above the floor. Outdoor air
may be introduced through these bases by cutting an access opening
to accommodate the outdoor air duct connection. These bases are fin-
ished to match the exterior of the basic unit. They may have to be insu-
lated in the field for certain applications.
THREE-PHASE ELECTRIC HEATERS
Electric heaters are available in several capacities to provide maxi-
mum flexibility. Both the air conditioning unit and the heater can be
selected to precisely match the cooling and heating requirements of
the conditioned space. These heaters are designed for easy field
installation over the supply air opening of the unit. They have been
tested by and will be shipped with a CSA label. Every heater will be
fully protected against excessive current and temperature by fuses
and two high limit thermostats.
Units with electric heat will require only one power supply for both the
heating elements and the supply air blower motor, and the power wir-
ing can be protected by either dual element/time delay fuses or an
inverse time circuit breaker.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21300-002-A-0905
NOMENCLATURE
<RUNꢃ,QGRRUꢃ6SOLWꢃ6\VWHPꢃ3URGXFWꢃ1RPHQFODWXUH
. ꢄ (8 ꢀꢁꢀ $ ꢂꢂ
3URGXFWꢃ&DWHJRU\
.ꢁ ꢁ$LUꢁ+DQGOHUꢊꢁ6SOLWꢁ6\VWHPꢊꢁ$&
9ROWDJHꢃ&RGH
ꢂꢃꢁ ꢁꢆꢂꢇꢈꢆꢅꢂꢉꢍꢉꢃꢂ
ꢅꢅꢁ ꢁꢆꢂꢇꢈꢆꢅꢂꢉꢅꢉꢃꢂꢊꢁꢀꢃꢂꢉꢅꢉꢃꢂ
ꢄꢇꢁ ꢁꢄꢌꢄꢉꢅꢉꢃꢂ
3URGXFWꢃ*HQHUDWLRQ
ꢀꢁ ꢁ)RXUWKꢁ*HQHUDWLRQ
3URGXFWꢃ,GHQWLILHU
(8ꢁ ꢁ5ꢉꢆꢆꢊꢁ6WDQGꢋꢁ(IIꢋꢊꢁꢆꢉ3LSH
+HDWꢃ7\SHꢃ ꢃ1RPLQDOꢃ+HDWꢃ&DSDFLW\
$ꢁ ꢁ&RROLQJꢁ2QO\ꢁꢉꢁ6XLWDEOHꢁIRUꢁILHOGꢁLQVWDOOHGꢁHOHFWULFꢁKHDW
1RPLQDOꢃ&RROLQJꢃ
&DSDFLW\ꢃꢅꢃ0%+
ꢂꢃꢂꢁ ꢁꢄꢁ7RQ
ꢂꢎꢂꢁ ꢁꢌꢉꢍꢈꢆꢁ7RQ
ꢍꢆꢂꢁ ꢁꢍꢂꢁ7RQ
ꢍꢇꢂꢁ ꢁꢍꢄꢁ7RQ
THERMOSTATS
ACCESSORIES-FIELD INSTALLED (CONT.)
Wall-mounted thermostats and subbases (24-volt) with sys-
tem and fan switches are available to control the operation of
these split system air conditioners.
HOT WATER COILS
These drainable coils have 2 rows of 1/2" copper tubes, 12
aluminum fins per inch, a casing that is finished to match the
exterior of the basic unit, but no water control valve. The coils
slide out of their casings for easy field installation. They
should be mounted over the return air opening on 5, 7-1/2
and 10-ton units—between the unit coil and blower sections
on 15-ton units.
APPLICATION FLEXIBILITY
MODELS 5, 7-1/2 & 10 TON
These units are built in a single cabinet with two condensate
drain pans. This allows the units to be installed in either the
vertical or horizontal position for maximum flexibility.
STEAM COILS
On vertical applications, the air velocity across the cooling
coil keeps the condensate from dripping off the finned sur-
face onto the filters.
These non-freeze coils have 1 row of 1" copper tubes, a 5/8"
copper tube inside each 1" tube to distribute the steam evenly
across the entire length of the coil, 8 aluminum fins per inch,
a casing that is finished to match the exterior of the basic unit,
but no steam control valve. The coils slide out of their casings
for easy field installation and are pitched in their casings to
facilitate condensate drainage. They should be mounted over
the return air opening on 5, 7-1/2 and 10-ton units—between
the unit coil and blower sections on 15-ton units.
On horizontal applications, the unit must be installed with the
condensate drain pan under the entire cooling coil.
•
The Supply Air Plenum and the Return Air Grill accesso-
ries can be used on either arrangement.
The Base accessory can only be used on the vertical
arrangement.
•
SUSPENSION KIT
Units installed horizontally are designed for ceiling suspen-
sion. Four 3/8"-16 weld nuts are provided in the angle sup-
ports on the front of the unit (the side with the logo).
Knockouts are provided in the exterior panels for access to
these weld nuts. The hanger rods must be supplied in the
field.
Suspension kit 1HH0451 is available for 15-ton units installed
horizontally. The accessory includes two channel iron sup-
ports and the hardware to secure them to the top of the unit.
The hanger rods must be supplied by the field.
Unitary Products Group
3
036-21300-002-A-0905
MODEL 15 TON
$,5
287
These units have two distinct modules . . . a blower module
and a coil module. Although the unit is always shipped in the
vertical position with a vertical air discharge as shown in illus-
tration (a), the blower module can be repositioned in the field
as shown in illustrations (b) and (c) for maximum flexibility.
%/2:(5
%/2:(5ꢁ02725
&2,/
5(7851ꢁ$,5
'8&7ꢁ)/$1*(
•
•
•
The Supply Air Plenum, Return Air Grill and Base acces-
sories can be applied on arrangement (a).
The Return Air Grill and Base accessories can be
applied on arrangement (b).
The Supply Air Plenum, Return Air Grill and Suspension
accessories can be applied on arrangement (c).
&21'(16$7(
'5$,1
&211(&7,21
$,5ꢁ
,1
&21'(16$7(
'5$,1ꢁ3$1
),/7(56
ꢆ9(57,&$/ꢃ326,7,21ꢇ
),/7(56
&2,/
5(7851
$,5ꢁ'8&7
)/$1*(
%/2:(5
$,5ꢁ
,1
$,5
287
%/2:(5ꢁ02725
&21'(16$7(ꢁ'5$,1ꢁ3$1
&21'(16$7(
'5$,1ꢁ&211(&7,21
ꢆ+25,=217$/ꢃ326,7,21ꢇ
FIGURE 1 - VERTICAL AND HORIZONTAL
APPLICATION KEU060, 090 & 120
ꢏ9(57,&$/ꢁ326,7,21ꢐ
ꢏ+25,=217$/ꢁ326,7,21ꢐ
FIGURE 2 - VERTICAL AND HORIZONTAL APPLICATION KEU180
4
Unitary Products Group
036-21300-002-A-0905
ꢆꢉꢄꢈꢇ
ꢏꢀꢐꢁꢅꢈꢇꢑꢉꢍꢃ
:(/'ꢁ18876
$
ꢀꢋꢂꢉꢄꢃꢈ ꢆ+%5ꢇꢈꢇ
ꢁꢁꢂꢋꢄꢌ ꢆ+%5ꢇꢉꢇꢊ ꢃꢅꢇ
ꢀꢁꢂꢃꢄꢅ ꢆ+%5ꢇꢈꢇ
ꢁꢉꢂꢃꢄꢁ ꢆ+%5ꢇꢉꢇꢊ ꢃꢅꢇ
%
ꢍꢉꢍꢈꢀꢁꢏ.(8ꢂꢃꢂꢐ
ꢍꢉꢅꢈꢇꢁꢏ.(8ꢂꢎꢂꢊꢁꢍꢆꢂꢐ
;
&
'
&(17(5
2)ꢁ*5$9,7<
<
!)2
).
!)2
/54
5(7851ꢁ$,5ꢁ*5,//ꢊꢁ+27ꢁ:$7(5ꢁ&2,/ꢁ
$1'ꢁ67($0ꢁ&2,/ꢁ$&&(6625,(6ꢁ
,167$//('ꢁ217+,6ꢁ(1'ꢁ2)ꢁ7+(ꢁ81,7ꢋ
6833/<ꢁ$,5ꢁ3/(180ꢁ$1'
(/(&75,&ꢁ+($7(5ꢁ$&&(6625,(6
,167$//('ꢁ21ꢁ7+,6ꢁ(1'ꢁ2)ꢁ7+(
81,7ꢋ
FIGURE 3 - SUSPENSION MOUNTING (HORIZONTAL) - KEU060, 090 AND 120
TABLE 1: UNIT SUSPENSION MOUNTING (HORIZONTAL APPLICATION) WEIGHTS
Shipping
Weight
(lb)
Operating
Weight
(lb)
CG (in)
4-Point Loading (lb)
Unit Model
X
Y
A
B
C
D
K*EU060
K*EU090
K*EU120
K*EU180
225
210
22.50
26.50
26.50
26.50
15.00
24.00
24.00
24.00
47
78
51
84
92
77
58
84
53
78
340
235
370
355
86
92
86
440
425
104
104
141
TABLE 2: KEU OPERATING WEIGHTS (LBS.)
MODEL
060
210
45
090
120
180
BASIC UNIT
(Cooling Only)
Base
325
55
325
55
425
65
Return Air Grill
Supply Air Plenum
Hot Water Coil
Steam Coil
10
15
15
20
90
100
105
115
100
105
115
115
135
145
70
80
ACCESSORIES
10 KW
16 KW
26 KW
36 KW
72 KW
66
70
Electric Heater
74
77
125
Unitary Products Group
5
036-21300-002-A-0905
ꢏꢀꢐꢁ+DQJHUꢁ5RGV
ꢏ)LHOGꢁ6XSSOLHGꢐ
ꢅꢑ
ꢒ6XVSHQVLRQ
ꢁ&KDQQHOV
$,5ꢁ,1
&2,/
6(&7,21
ꢍ
5HIHUꢁWRꢁ3DUWꢁ1Rꢋꢁ
%/2:(5
6(&7,21
$,5ꢁ287
ꢂꢅꢄꢉꢍꢃꢃꢆꢆꢉꢂꢂꢍꢁIRU
LQVWDOODWLRQꢁLQVWUXFWLRQVꢁRQ
WKHꢁVXVSHQVLRQꢁDFFHVVRU\
DQGꢁIRUꢁWKHꢁLQGLYLGXDOꢁORDG
RQꢁHDFKꢁKDQJHUꢁURGꢋ
5(7851ꢁ$,5ꢁ*5,//(
$FFHVVRU\ꢁ,QVWDOOHG
2Qꢁ7KLVꢁ(QGꢁ2Iꢁ8QLW
6833/<ꢁ$,5ꢁ3/(180
$QGꢁ(/(&75,&ꢁ+($7(5
$FFHVVRULHVꢁ,QVWDOOHGꢁ2Q
7KLVꢁ(QGꢁ2Iꢁ8QLW
FIGURE 4 - SUSPENSION ACCESSORY (HORIZONTAL) - KEU180
TABLE 3: SOUND POWER RATINGS
SOUND POWER (dB 10-12 WATTS)
ESP
IWG
BLOWER
OCTAVE BAND CENTERLINE FREQUENCY (HZ)
UNIT
MODEL
CFM
dB(A)
@
10 FT.1
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
SWL dB(a)
060
090
120
180
2,000
3,000
4,000
6,000
0.50
0.60
0.70
0.75
940
750
850
750
0.70
1.05
1.75
2.75
88
88
91
95
88
88
91
95
78
78
81
85
71
73
74
80
73
71
76
78
66
66
69
73
61
61
64
68
56
56
59
63
77
77
81
84
44
45
48
52
1. At a distance of 10 feet from the blower.
NOTE:
These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are
for reference only. Calculation of dBA values cover matters of system design and the fan manufacturer has no way of knowing the details of each sys-
tem. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level rat-
ings.
6
Unitary Products Group
036-21300-002-A-0905
TABLE 4: HEATING CAPACITY - ELECTRIC HEAT ACCESSORY
CAPACITY
1ST STAGE 2ND STAGE
NOMINAL RATINGS1
UNIT MODEL
HEATER MODEL
VOLTAGE TEST
KW
10
MBH
34.2
54.7
88.9
KW
10
MBH
34.2
34.2
54.7
KW
-
MBH
-
2HT045010
2HT045016
2HT045026
25
208 / 2402
208 / 2402
208 / 2402
208 / 2402
4803
060
25
25
25
46
58
25
46
58
25
46
58
25
46
58
25
46
58
25
46
58
25
46
58
25
46
58
25
46
58
16
10
6
20.5
34.2
26
16
10
2HS045010
2HS045016
2HS045026
2HS045036
2HS045010
2HS045016
2HS045026
2HS045036
2HS045072
10
16
26
36
10
16
26
36
72
34.2
54.7
88.9
123
10
10
16
16
10
10
16
16
36
34.2
34.2
54.7
54.7
34.2
34.2
54.7
54.7
123
-
-
6004
208 / 2402
4803
6
20.5
34.2
68.3
-
6004
090, 120
208 / 2402
4803
10
20
-
6004
208 / 2402
4803
6004
208 / 2402
2803
34.2
54.7
88.9
123
6004
208 / 2402
2803
6
20.5
34.2
68.3
123
6004
208 / 2402
2803
180
10
20
36
6004
208 / 2402
2803
6004
208 / 2402
2803
246
6004
1. Capacity Ratings do not include the heat generated by the air blower motor.
2. For 208 volts, multiply the MBH and KW by (208/240)² or 0.751.
For 230 volts, multiply the MBH and KW by (230/240)² or 0.918.
3. For 460 volts, multiply the MBH and KW by (460/480)² or 0.918.
4. For 575 volts, multiply the MBH and KW by (575/600)² or 0.918.
Unitary Products Group
7
036-21300-002-A-0905
1
2
TABLE 5: STEAM COIL CAPACITY , MBH@2 PSIG
DRY BULB TEMPERATURE OF AIR ENTERING COIL, ºF
STEAM COIL
UNIT MODEL
CFM
MODEL
10
30
50
70
1600
2000
2400
2400
3000
3600
3200
4000
4800
4800
6000
7200
104.0
115.2
124.9
172.2
191.2
207.5
196.4
217.3
236.1
298.2
329.1
356.4
94.0
83.9
73.9
1NF0450
060
104.0
113.0
155.5
172.6
187.1
177.6
195.3
212.9
268.4
297.0
321.8
93.1
81.9
100.9
139.1
154.3
167.4
158.8
175.3
190.4
236.7
265.6
287.9
89.0
122.4
136.0
147.4
140.0
154.8
167.8
211.5
234.1
254.0
090
120
180
1NF0451
1NF0452
1. These capacities do not include any blower motor heat.
2. Multiply these capacities by the following factors to correct for higher steam pressures.
Steam Pressure, psig
5
10
15
20
25
Capacity correction factor
1.05
1.12
1.19
1.25
1.30
NOTE: Steam rate (lb./hr.) = 1.025 x MBH
CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a steam coil acces-
sory.
1
TABLE 6: HOT WATER CAPACITY , MBH
ENTERING WATER TEMP. MINUS ENTERING AIR TEMP., ºF
WATER COIL MODEL
UNIT MODEL
GPM
CFM
70
90
110
130
150
1600
2000
2400
2400
3000
3600
3200
4000
4800
4800
6000
7200
46.5
60.4
74.6
89.0
101.8
113.4
123.3
169.7
190.4
208.1
196.6
218.6
237.4
294.1
326.6
354.3
1HW0450
060
10
51.7
67.2
83.0
99.2
56.0
73.0
90.4
107.9
148.5
166.6
182.1
172.1
191.3
207.5
257.4
285.9
309.8
78.0
101.3
113.3
124.0
117.1
130.2
140.9
175.1
195.0
210.8
124.7
139.6
153.0
144.6
160.7
174.3
215.8
240.3
260.4
090
120
180
15
15
20
87.7
95.5
1HW0451
1HW0452
90.3
100.2
108.3
135.5
150.0
162.4
1. These capacities do no include any blower motor heat.
0
NOTE: Water Temperature Drop, F = 2 x MBH
CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a hot water coil accessory.
TABLE 7: PRESSURE DROP VS. GPM
TABLE 8: CAPACITY CORRECTION VS. GPM
GPM
Pressure Drop, PSI
GPM
10
.10
15
20
.32
30
30
.67
45
GPM
Capacity Correction
GPM
20
1.12
30
30
1.16
45
1HW0450
1HW0451
1HW0452
1HW0450
1HW0451
1HW0452
Pressure Drop, PSI
GPM
.17
20
.58
40
1.22
60
Capacity Correction
GPM
1.11
40
1.15
60
Pressure Drop, PSI
.20
.67
1.41
Capacity Correction
1.12
1.17
8
Unitary Products Group
036-21300-002-A-0905
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE - KEU060 (5 TON)
EXTERNAL STATIC PRESSURE
CFM
0.2
W
0.4
W
0.6
W
0.8
W
RPM
677
BHP
0.08
0.24
0.39
0.54
0.70
0.88
1.07
1.27
1.50
1.74
RPM
753
BHP
0.19
0.35
0.50
0.65
0.81
0.99
1.17
1.38
1.60
1.85
RPM
831
BHP
0.29
0.45
0.60
0.75
0.91
1.09
1.27
1.48
1.70
1.95
RPM
912
BHP
0.38
0.54
0.69
0.85
1.01
1.18
1.37
1.57
1.80
----
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
74
174
325
466
607
757
918
1094
1286
1495
1721
268
355
506
647
789
938
1100
1276
1468
1677
----
725
225
366
507
657
818
994
1187
1395
1622
801
879
419
959
773
849
927
560
1008
1056
1106
1156
1207
1258
1311
----
822
898
975
701
871
947
1025
1075
1126
1178
1230
1283
851
922
997
1012
1188
1380
1589
1815
972
1048
1100
1152
1205
1024
1076
1129
EXTERNAL STATIC PRESSURE
1.2 1.4
CFM
1.0
W
1.6
W
RPM
997
BHP
0.47
0.63
0.78
0.93
1.09
1.27
1.45
1.66
1.88
----
RPM
1086
1134
1182
1230
1280
1330
1381
1433
1485
----
W
BHP
0.54
0.71
0.86
1.01
1.17
1.34
1.53
1.74
1.96
----
RPM
1181
1228
1276
1325
1375
1425
1476
1527
----
W
BHP
0.61
0.77
0.92
1.08
1.24
1.41
1.60
1.80
----
RPM
1282
1329
1377
1426
1476
1526
1577
1628
----
BHP
0.67
0.83
0.98
1.13
1.29
1.47
1.66
1.86
----
1400
1600
1800
2000
2200
2400
2600
2800
3000
3200
435
586
727
869
1018
1180
1356
1548
1757
----
507
570
622
774
914
1056
1205
1367
1543
1735
----
1044
1092
1141
1191
1241
1292
1343
1395
----
658
721
799
861
940
1003
1153
1314
1490
1682
----
1090
1251
1427
1620
1828
----
----
----
----
----
----
----
Exceeds the BHP limitation.
Unitary Products Group
9
036-21300-002-A-0905
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE - KEU090 (7.5 TON)
EXTERNAL STATIC PRESSURE
CFM
0.2
W
0.4
W
0.6
W
0.8
RPM
561
579
599
619
640
662
684
706
728
750
771
792
813
BHP
0.30
0.44
0.58
0.71
0.84
0.97
1.09
1.20
1.31
1.42
1.52
1.62
1.72
RPM
612
630
649
670
691
713
735
757
779
800
822
843
864
BHP
0.43
0.57
0.71
0.84
0.97
1.10
1.21
1.33
1.44
1.55
1.65
1.75
1.84
RPM
670
688
707
728
749
771
793
815
837
859
880
901
922
BHP
0.57
0.71
0.85
0.98
1.11
1.23
1.35
1.47
1.58
1.69
1.79
1.89
1.98
RPM
734
752
771
792
813
835
857
879
900
922
944
965
986
W
BHP
0.71
0.85
0.99
1.12
1.25
1.37
1.49
1.61
1.72
1.83
1.93
2.03
2.12
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
281
400
530
661
414
533
663
794
542
662
792
922
666
786
916
1047
1166
1282
1393
1500
1603
1702
1798
1890
1979
786
905
1035
1151
1262
1369
1472
1571
1667
1759
1848
901
1021
1132
1239
1342
1441
1537
1629
1718
1013
1120
1223
1322
1418
1510
1599
EXTERNAL STATIC PRESSURE
1.2 1.4
CFM
1.0
1.6
W
RPM
801
819
838
859
880
902
924
945
967
989
1011
1032
1052
W
BHP
0.84
0.98
1.12
1.25
1.38
1.51
1.63
1.74
1.85
1.96
2.06
2.16
2.25
RPM
869
W
BHP
0.95
1.09
1.23
1.36
1.49
1.62
1.74
1.85
1.96
2.07
2.17
2.27
----
RPM
936
W
BHP
1.03
1.17
1.31
1.45
1.57
1.70
1.82
1.93
2.04
2.15
2.25
----
RPM
1000
1018
1038
1058
1079
1101
1123
1145
1167
1189
1210
----
BHP
1.07
1.21
1.35
1.49
1.61
1.74
1.86
1.97
2.08
2.19
2.29
----
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
783
886
962
999
916
887
1019
1148
1272
1392
1507
1618
1725
1828
1928
2023
2116
----
954
1095
1223
1348
1467
1583
1694
1801
1904
2003
2099
----
1132
1261
1385
1505
1620
1731
1838
1941
2041
2136
----
1044
1169
1288
1404
1515
1622
1725
1824
1920
2012
2101
906
973
927
994
948
1015
1037
1059
1081
1103
1124
1146
----
970
992
1014
1036
1057
1079
1100
----
----
----
----
----
----
----
Exceeds the BHP limitation.
10
Unitary Products Group
036-21300-002-A-0905
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - KEU120 (10 TON)
EXTERNAL STATIC PRESSURE
CFM
0.2
W
0.4
W
0.6
0.8
RPM
571
595
619
643
667
692
716
740
765
789
813
837
861
884
907
BHP
0.13
0.37
0.60
0.81
1.01
1.20
1.39
1.57
1.76
1.95
2.14
2.33
2.52
2.72
2.93
RPM
630
654
678
702
726
751
775
799
824
848
872
896
920
943
966
BHP
0.36
0.60
0.82
1.03
1.23
1.43
1.61
1.80
1.99
2.17
2.36
2.55
2.75
2.95
3.15
RPM
682
706
730
754
778
803
827
852
876
900
924
948
972
995
1019
W
BHP
0.52
0.77
0.99
1.20
1.40
1.59
1.78
1.97
2.15
2.34
2.53
2.72
2.92
3.12
3.32
RPM
733
756
780
804
829
853
877
902
926
950
974
998
1022
1045
1069
W
BHP
0.66
0.91
1.13
1.34
1.54
1.73
1.92
2.11
2.29
2.48
2.67
2.86
3.05
3.25
3.46
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
122
332
489
618
349
559
716
845
558
768
925
1054
1249
1435
1614
1790
1963
2136
2310
2486
2665
2847
3033
3224
753
964
1120
1306
1485
1661
1834
2008
2182
2357
2536
2718
2905
3095
939
1149
1329
1504
1678
1851
2025
2201
2380
2562
2748
2939
1119
1294
1468
1641
1815
1991
2169
2352
2538
2728
EXTERNAL STATIC PRESSURE
1.2 1.4
CFM
1.0
1.6
W
RPM
786
W
BHP
0.80
1.04
1.27
1.48
1.67
1.87
2.06
2.24
2.43
2.61
2.80
2.99
3.19
3.39
----
RPM
846
W
BHP
0.96
1.20
1.43
1.64
1.84
2.03
2.22
2.40
2.59
2.77
2.96
3.15
3.35
----
RPM
920
W
BHP
1.17
1.41
1.64
1.85
2.05
2.24
2.43
2.61
2.80
2.99
3.18
3.37
----
RPM
1010
1034
1057
1082
1106
1130
1155
1179
1203
1228
1252
----
BHP
1.46
1.71
1.93
2.14
2.34
2.53
2.72
2.91
3.09
3.28
3.47
----
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
744
893
1092
1319
1528
1723
1909
2088
2264
2437
2610
2784
2960
3139
----
1364
1592
1800
1996
2182
2361
2536
2710
2883
3057
3233
----
809
971
870
1121
1329
1525
1711
1890
2066
2239
2412
2586
2762
2941
3123
----
943
833
1180
1375
1561
1741
1916
2090
2263
2437
2613
2791
2973
3160
----
894
967
857
918
991
882
942
1016
1040
1064
1089
1113
1137
1161
1185
----
906
967
930
991
955
1016
1040
1064
1088
1112
1136
----
979
1003
1027
1051
1075
1098
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
Exceeds the BHP limitation.
Unitary Products Group
11
036-21300-002-A-0905
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE - KEU180 (15 TON)
EXTERNAL STATIC PRESSURE
CFM
0.2
0.4
0.6
0.8
RPM
555
562
569
577
586
595
604
614
624
635
645
656
667
679
690
701
W
BHP
0.41
0.66
0.89
1.10
1.29
1.47
1.64
1.81
1.97
2.14
2.30
2.46
2.62
2.78
2.95
3.13
RPM
594
600
608
616
624
634
643
653
663
673
684
695
706
717
729
740
W
BHP
0.67
0.92
1.14
1.35
1.55
1.73
1.90
2.07
2.23
2.39
2.55
2.71
2.87
3.04
3.21
3.38
RPM
633
640
648
656
664
673
683
693
703
713
724
735
746
757
768
780
W
BHP
0.91
1.16
1.39
1.60
1.79
1.97
2.15
2.31
2.48
2.64
2.80
2.96
3.12
3.29
3.46
3.63
RPM
676
683
690
698
707
716
726
735
745
756
766
777
788
800
811
823
W
BHP
1.16
1.42
1.64
1.85
2.04
2.23
2.40
2.57
2.73
2.89
3.05
3.21
3.37
3.54
3.71
3.88
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
382
620
851
1085
1319
1531
1725
1905
2075
2236
2392
2544
2694
2843
2993
3145
3299
3456
3618
616
854
1085
1297
1491
1671
1841
2002
2158
2310
2459
2609
2759
2910
3064
3222
3384
828
1066
1260
1440
1610
1771
1927
2079
2228
2378
2528
2679
2833
2991
3153
1022
1202
1372
1533
1689
1841
1991
2140
2290
2442
2596
2753
2915
EXTERNAL STATIC PRESSURE
1.2 1.4
CFM
1.0
1.6
RPM
723
729
737
745
754
763
772
782
792
802
813
824
835
846
858
869
W
BHP
1.43
1.68
1.91
2.12
2.31
2.49
2.66
2.83
2.99
3.16
3.32
3.48
3.64
3.80
3.97
4.15
RPM
775
781
789
797
806
815
824
834
844
854
865
876
887
898
910
921
W
BHP
1.72
1.97
2.20
2.41
2.60
2.78
2.96
3.12
3.29
3.45
3.61
3.77
3.93
4.10
4.26
4.44
RPM
833
840
848
856
864
873
883
893
903
913
924
935
946
957
968
980
W
BHP
2.05
2.30
2.53
2.74
2.93
3.11
3.28
3.45
3.61
3.77
3.93
4.10
4.26
4.42
4.59
4.77
RPM
900
W
BHP
2.42
2.67
2.90
3.11
3.30
3.48
3.66
3.82
3.99
4.15
4.31
4.47
4.63
4.80
4.97
5.14
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
1333
1567
1779
1973
2153
2323
2484
2640
2792
2942
3091
3241
3392
3547
3704
3866
1604
1839
2051
2245
2425
2594
2755
2911
3063
3213
3362
3512
3664
3818
3976
4137
1910
2144
2356
2550
2730
2899
3061
3216
3368
3518
3667
3817
3969
4123
4281
4442
2258
2493
2704
2899
3079
3248
3409
3565
3717
3867
4016
4166
4318
4472
4629
4791
907
915
923
931
940
950
960
970
980
991
1002
1013
1024
1035
1047
Exceeds the BHP limitation.
12
Unitary Products Group
036-21300-002-A-0905
TABLE 13: STATIC RESISTANCE FOR UNIT ACCESSORIES (IWG) - KEU060-120
Electric Heat KW
Supply Air
Plenum
Return
Air Grill
Hot Water
Coil
Steam
Coil
CFM
10
16
26
36
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
0.01
0.01
0.01
0.01
0.01
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.01
0.02
0.02
0.03
0.03
0.04
0.04
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.03
0.03
0.04
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.10
0.11
0.12
0.13
0.14
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.21
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.09
0.10
0.10
0.02
0.03
0.03
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.09
0.10
0.10
0.07
0.09
0.10
0.12
0.14
0.16
0.17
0.19
0.22
0.24
0.26
0.28
0.31
0.33
0.36
0.11
0.13
0.15
0.16
0.18
0.20
0.23
0.25
0.27
0.30
0.33
0.36
0.39
0.43
0.46
TABLE 14: STATIC RESISTANCE FOR UNIT ACCESSORIES (IWG) - KEU180
Electric Heat KW
Supply Air
Plenum
Return
Air Grill
Hot Water
Coil
Steam
Coil
CFM
10
16
26
36
72
4600
4800
5000
5200
5400
5600
5800
6000
6200
6400
6600
6800
7000
7200
7400
0.03
0.04
0.04
0.04
0.05
0.05
0.06
0.06
0.07
0.07
0.08
0.08
0.09
0.09
0.10
0.08
0.08
0.09
0.10
0.10
0.11
0.11
0.12
0.13
0.13
0.14
0.15
0.15
0.16
0.17
0.12
0.13
0.14
0.16
0.17
0.18
0.20
0.21
0.22
0.24
0.25
0.27
0.29
0.30
0.32
0.18
0.19
0.21
0.23
0.24
0.26
0.28
0.30
0.32
0.34
0.36
0.38
0.41
0.43
0.45
0.23
0.25
0.27
0.29
0.31
0.34
0.37
0.40
0.43
0.47
0.51
0.55
0.59
0.64
0.68
0.05
0.06
0.06
0.06
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.10
0.11
0.05
0.06
0.06
0.06
0.07
0.07
0.08
0.08
0.08
0.09
0.09
0.10
0.10
0.10
0.11
0.31
0.33
0.36
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.59
0.62
0.66
0.69
0.73
0.39
0.43
0.46
0.50
0.54
0.58
0.62
0.66
0.71
0.75
0.80
0.85
0.90
0.95
1.01
Unitary Products Group
13
036-21300-002-A-0905
TABLE 15: SUPPLY AIR PLENUM PERFORMANCE DATA
Angle of Deflection
Vertical
Horizontal
Vertical
Louvers
(Plan
Horizontal
Vertical
Louvers
(Plan
Horizontal
Louvers
(Elevation
View)
1
2
Louvers
(Elevation
View)
Louvers
(Plan
Louvers
4
S
5
°
2
S
2
-
1
/
2
°
(Elevation
View)
P
R
E
A
D
P
R
E
A
D
Face
Model CFM Velocity
(FPM)
0
S
°
View)
View)
View)
P
R
E
A
D
Spread
Throw
(Feet)
Throw
(Feet)
Spread
(Feet)
Throw
(Feet)
Spread
(Feet)
3
0
S
°
0
S
°
(Feet)
18˚
0
S
°
P
R
E
A
D
18˚
P
R
E
A
D
18˚
P
R
E
A
D
4
Min. Max. Min. Max
Min.
27
30
34
37
41
34
39
42
46
50
45
50
56
62
68
61
68
76
84
92
Max Min. Max
Drop (Feet)
Min. Max. Min. Max.
Drop (Feet)
Drop (Feet)
1600
1800
2000
2200
2400
2400
2700
3000
3300
3600
3200
3600
4000
4400
4800
4800
5400
6000
6600
7200
630
710
38
43
48
52
57
47
53
59
65
71
63
71
78
86
94
84
95
106
116
126
59
67
13
14
16
17
19
20
22
24
26
28
25
28
30
33
35
32
36
39
43
46
20
22
25
27
30
29
32
35
38
41
37
41
45
49
53
48
54
59
65
70
15
16
16
16
17
19
20
21
21
22
21
22
22
23
23
23
24
25
26
27
8
8
9
9
9
9
43
48
12
14
15
17
18
23
25
27
29
32
29
32
35
38
41
38
42
46
50
55
19
22
24
26
29
33
36
40
44
47
43
47
52
57
62
56
63
69
76
83
14
14
14
15
15
17
18
19
19
20
19
20
20
21
21
21
22
23
23
24
7
7
21
23
25
29
30
26
29
32
35
38
34
38
42
47
51
46
52
57
63
68
32
37
40
44
48
39
45
50
55
60
53
60
66
73
80
72
81
89
98
107
33
35
38
44
45
45
48
52
56
60
54
60
67
76
85
73
81
90
99
48
56
8
4
4
5
5
5
5
5
5
5
6
5
6
6
6
6
6
6
7
7
7
8
060
090
120
180
790
74
53
8
60
9
870
81
58
8
66
9
940
89
64
8
72
9
615
74
53
8
65
9
690
83
10
10
10
11
10
11
11
12
12
12
12
13
13
14
59
9
71
10
10
10
11
10
11
11
12
12
12
12
13
13
14
770
92
66
9
78
845
101
110
98
73
9
85
920
79
10
9
91
820
70
82
920
110
123
135
147
132
149
165
182
199
79
10
10
11
11
11
11
12
12
12
91
1025
1130
1230
880
88
102
115
127
112
124
138
152
97
106
95
1000
1110
1220
1330
107
119
131
143
109 166
1. Adjusting the vertical louvers will vary the throw, the spread and the drop.
2. Adjusting the horizontal louvers will only vary the drop.
3. The velocity of the air will be 125 ft./min. at the minimum distance and 80 ft./min. at the maximum distance.
4. The velocity of the conditioned air at the bottom of the drop will be 50 ft./min. Drafts will occur if the drop extends into the occupied
level of the conditioned space.
TABLE 16: BLOWER MOTOR AND DRIVE DATA
MOTOR
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
BELT (NOTCHED)
PITCH
BLOWER
RANGE
(RPM)
OUTSIDE PITCH
MODEL
DESIG-
NATION
BORE DESIG-
BORE DESIG-
(IN.)
HP
FRAME
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
LENGTH QTY.
(IN.)
(IN.)
NATION
NATION
060
090
120
180
810/1110
655/880
700/950
625/810
3/4
1-1/2
2
56
56
56
56
1VL44
1VL44
1VL44
1VM50
3.1-4.1
2.1-4.1
3.1-4.1
3.7-4.7
2.8-3.8
2.8-3.8
2.8-3.8
3.4-4.4
5/8
7/8
7/8
7/8
AL64
AK79
BK80
BK105
6.2
7.9
7.4
9.9
5.8
7.5
7.0
9.5
3/4
1
A32
A36
A36
A57
33.3
37.3
37.3
58.3
1
1
1
1
1
3
1
14
Unitary Products Group
036-21300-002-A-0905
TABLE 17: KEU PHYSICAL DATA
Model
Component
Description
060
090
120
180
Centrifugal Blower (Dia. X Wd. in.)
15 X 15
15 X 15
15 X 15
18 X 18
EVAPORATOR
BLOWER1
Fan Motor HP (Belt Drive)
Rows Deep
3/4
1-1/2
2
3
3
3
3
3
Finned Length (in.)
Fins per Inch
30
46
46
54
EVAPORATOR
COIL
13
13
13
13
Face Area (ft.2)
5.0
8.6
10.2
12.1
Rows Deep
2
2
2
2
Finned Length (in.)
Fins Per Inch
Face Area (ft.2)
30
46
46
54
12
12
12
12
HOT WATER COIL
3.8
5.4
5.4
9.0
Inlet Connection
1” NPTE
1” NPTE
1” NPTE
1-3/8” O.D
Outlet Connection
Rows Deep
1” NPTE
1” NPTE
1” NPTE
1-3/8” O.D
1
1
46
8
1
1
Finned Length (in.)
Fins Per Inch
30
46
54
8
8
8
STEAM COIL
Face Area (ft.2)
3.8
5.4
5.4
9.0
Inlet Connection
1-1/2” NPTE
1-1/2” NPTE
1-1/2” NPTE
1-1/2” NPTE
Outlet Connection
Quantity Per Unit (16” X 25” X 1”)
Quantity Per Unit (20” X 20” X 1”)
Total Face Area (ft.2)
Refrigerant 22 (lbs./oz.)
1-1/2” NPTE
1-1/2” NPTE
1-1/2” NPTE
1-1/2” NPTE
2
4
0
4
0
6
AIR FILTERS
0
0
5.6
0/7
11.1
0/7
11.1
0/10
16.7
0/0
HOLDING CHARGE
1. Refer to Blower Motor and Drive Data table for additional blower and drive information.
All of these 1750 RPM motors are solid base, 56 frame with 1.15 service factor, inherent protection and permanently lubricated ball bearings.
Unitary Products Group
15
036-21300-002-A-0905
ꢋꢄꢌꢎ (/,% 7ꢄ"53().'
). 2%!2 0!.%,
ꢆ&OR ,OW 6OLTAGE
#ONTROL 0ANEL
ꢀꢈꢂꢃꢄꢌ
ꢃꢀꢂꢃꢄꢁ
ꢌꢂꢃꢄꢅ
ꢋꢄꢌꢎ +./#+/54
). 2%!2 0!.%,
ꢆ&OR 0OWER 7IRING
ꢃꢂꢅꢀꢄꢀꢅ +./#+/54
ꢆ2EMOVED ONLY WHEN
%LECTRIC (EAT !CCESSORY
IS USED
!)2
/54
ꢀꢂꢋꢄꢌ
ꢃ
ꢁꢂꢃꢄꢅ
ꢀꢄꢁ
ꢃꢃꢂꢃꢄꢅ
ꢅꢅꢂꢀꢄꢁ
ꢅꢂꢃꢄꢁ
ꢃꢃꢂꢏꢄꢌ
ꢅꢂꢏꢄꢃꢈ
",/7%2 -/4/2
!.$ $2)6%
!##%33 0!.%,
ꢆ4HIS SIDE INLY
&),4%2 !##%33
0!.%,ꢆ4HIS
SIDE ONLY
ꢁꢀꢂꢃꢄꢌ
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
(/,% 7)4( '2/-ꢂ
-%4 &/2 ꢀꢄꢌ /ꢐ$ꢐ
,)15)$ ,).%
ꢅꢇ
ꢀꢂꢋꢄꢌ
(/,% 7)4( '2/-ꢂ
-%4 &/2 ꢋꢄꢌ /ꢐ$ꢐ
35#4)/. ,).%
ꢃꢂꢏꢄꢌ
ꢅ
ꢃꢂꢀꢄꢌ
ꢃꢂꢀꢄꢃꢈ
ꢃꢇꢂꢀꢄꢌ
ꢃꢂꢃꢄꢌ
!)2
).
ꢅ
ꢅꢅ
ꢋꢄꢌ /ꢐ$ꢐ $2!).
#/..ꢐ ꢆ-UST BE
TRAPPED
ꢀꢅ
ꢅ
FIGURE 1 - UNIT DIMENSIONS KEU060
ACCESSORIES
1. Overall dimensions of the unit will vary if an electric
heater, a supply air plenum or a base is used.
2. This dimension is required for removal of the coil. Only
26” is required for normal service.
•
•
•
ELECTRIC HEATER - Add 13” to unit height when used.
SUPPLY AIR PLENUM - Add 24-1/4” to unit height when used.
BASE - Add 20” to unit height when used.
3. Although no clearance is required for service and oper-
ation, some clearance may be required for routing the
power and control wiring.
4. Allow enough clearance to trap the condensate drain
line.
TABLE 18: UNIT CLEARANCES KEU060
MINIMUM CLEARANCES
060
24”
24”
Side with RETURN AIR opening
Side with SUPPLY AIR opening1
Side with PIPING CONNECTIONS2
36”
12”
Side opposite with PIPING CONNECTIONS
Side with access for both POWER & CONTROL
WIRING3,
-
-
Bottom4
16
Unitary Products Group
036-21300-002-A-0905
ꢃꢂꢀꢄꢌꢎ +./#+/54
&/2 0/7%2 7)2).' ꢆ"ACK 0ANEL
$O NOT REMOVE THIS KNOCKOUT WHEN
THE UNIT IS EQUIPPED WITH AN %LECTRIC
(EAT !CCESSORYꢐ 2EFER TO DETAIL OF
THE (EATER !CCESSORY FOR POWER
WIRING ACCESS OPENING
ꢏꢅꢂꢃꢄꢁ
ꢃꢌꢂꢋꢄꢌ
ꢋꢄꢌꢎ (/,% 7ꢄ"53().'
&/2 #/.42/,
7)2).'
ꢃꢏꢂꢀꢄꢌ
ꢆ"ACK 0ANEL
ꢃꢂꢅꢀꢄꢀꢅ +./#+/54
ꢆ2EMOVED ONLY WHEN
%LECTRIC (EAT !CCESSORY
IS USED
!)2
/54
ꢀꢂꢏꢄꢌ
ꢁꢂꢃꢄꢁ
ꢃ
ꢈꢂꢀꢄꢁ
ꢏꢄꢌ
ꢃꢈꢂꢃꢄꢌ
ꢅꢂꢃꢄꢁ
ꢅꢏꢂꢋꢄꢌ
ꢃꢏ
",/7%2 -/4/2
!.$ $2)6%
!##%33 0!.%,
ꢆ4HIS SIDE ONLY
(/,% 7)4( '2/-ꢂ
-%4 &/2 ꢃꢄꢅ /ꢐ$ꢐ
,)15)$ ,).%
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
ꢏꢃꢂꢃꢄꢌ
ꢅꢀ
ꢁ
(/,% 7)4( '2/-ꢂ
-%4 &/2 ꢃꢂꢃꢄꢌ /ꢐ$ꢐ
35#4)/. ,).%
ꢌꢂꢀꢄꢌ
ꢃꢂꢏꢄꢌ
ꢅꢂꢏꢄꢌ
ꢀꢂꢃꢄꢁ
ꢃꢂꢀꢄꢌ
ꢃꢂꢀꢄꢁ
!)2
).
ꢅ
ꢃꢂꢃꢄꢌ
ꢋꢄꢌ /ꢐ$ꢐ $2!).
#/..ꢐ ꢆ-UST BE
TRAPPED
ꢅꢏꢂꢃꢄꢌ
ꢅ
ꢁꢌ
ꢃ
&),4%2 !##%33 0!.%,
ꢆ7HEN UNIT IS INSTALLED IN
A HORIZONTAL POSITIONꢊDO
NOT BLOCK THIS AREA WITH
REFRIGERANT PIPING
FIGURE 2 - UNIT DIMENSIONS KEU090 & 120
ACCESSORIES
1. Overall dimensions of the unit will vary if an electric
heater, a supply air plenum or a base is used.
2. This dimension is required for removal of the coil. Only
26” is required for normal service.
•
•
•
ELECTRIC HEATER - Add 14-1/4” to unit height when used.
SUPPLY AIR PLENUM - Add 27-1/2” to unit height when used.
BASE - Add 20” to unit height when used.
3. Although no clearance is required for service and oper-
ation, some clearance may be required for routing the
power and control wiring.
TABLE 19: UNIT CLEARANCES KEU090 & 120
MINIMUM CLEARANCES
Side with RETURN AIR opening
090-120
4. Allow enough clearance to trap the condensate drain
line.
24”
24”
36”
12”
Side with SUPPLY AIR opening1
Side with PIPING CONNECTIONS2
Side opposite with PIPING CONNECTIONS
Side with access for both POWER & CONTROL
WIRING3,
-
-
Bottom4
Unitary Products Group
17
036-21300-002-A-0905
B
L
O
w
W
E
R
M
O
h
T
O
R
A
N
D
D
R
I
V
E
A
C
C
E
S
S
P
A
t
N
E
L
(
L
s
A
l
a
y
s
d
o
n
t
e
w
i
r
i
n
g
c
o
n
n
e
c
t
i
o
Y
f
n
s
i
d
e
o
f
u
n
i
)
7
/
8
"
K
N
O
C
K
O
U
T
F
O
R
P
O
W
E
R
W
I
R
I
N
G
o
c
a
t
e
o
n
o
p
p
o
s
i
t
o
e
s
i
d
e
O
N
L
w
h
e
n
t
h
e
b
l
o
w
e
r
D
o
n
o
t
r
e
c
m
o
v
e
t
h
i
s
k
n
o
c
k
o
u
t
w
h
e
n
t
h
e
u
n
i
t
i
s
e
q
u
i
p
p
e
d
w
i
t
h
a
n
E
l
e
c
t
r
i
c
e
c
t
i
o
n
h
a
s
b
O
e
e
n
r
t
a
T
t
e
d
1
8
0
r
o
m
p
o
s
i
t
i
o
n
s
h
o
w
n
.
H
w
e
a
i
t
A
c
e
s
s
o
r
y
.
R
e
f
e
r
t
o
d
e
t
a
i
l
o
f
t
h
e
H
e
a
t
e
r
A
c
c
e
s
s
o
r
y
f
o
r
p
o
w
e
r
i
r
n
g
a
c
c
e
s
s
o
p
e
n
i
n
g
1
-
2
3
/
3
2
"
K
N
C
K
O
U
7
C
/
8
"
K
N
O
C
K
O
U
T
F
O
R
R
H
e
e
m
a
o
v
e
o
n
l
s
y
w
h
e
n
E
l
e
c
t
r
i
c
O
N
T
R
O
L
W
I
R
I
N
G
t
A
c
c
e
s
o
r
y
i
s
u
s
e
d
.
6
0
-
3
/
4
2
1
-
7
/
8
A
2
L
T
E
R
N
A
T
E
1
9
-
3
/
8
-
5
/
8
"
K
N
O
C
K
O
U
T
*
A
I
R
5
-
7
/
8
O
U
T
2
-
1
/
8
5
-
1
/
2
1
8
-
7
/
8
7
/
8
3
2
-
3
/
8
6
7
-
1
/
4
1
6
-
1
/
2
B
S
L
E
O
W
E
O
R
3
-
1
/
8
2
-
5
/
8
"
C
T
I
N
1
9
K
N
O
C
K
-
O
1
U
T
F
O
O
R
N
-
5
/
8
"
O
D
1
0
S
U
C
T
I
C
O
N
N
.
*
2
7
-
5
/
8
6
-
1
/
4
3
-
1
/
8
6
2
-
5
/
8
C
S
O
I
L
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
E
C
T
.
3
-
1
/
8
2
-
3
/
8
A
I
R
I
N
1
F
C
-
1
/
4
"
K
N
O
C
K
O
U
T
O
R
7
/
E
8
"
O
D
D
R
A
I
N
2
-
3
/
1
6
O
N
N
C
T
I
O
N
*
(
M
u
s
t
b
e
t
r
a
p
p
e
d
)
5
6
-
3
/
8
F
I
L
T
E
R
A
C
C
E
S
S
P
A
N
E
L
3
1
-
5
/
8
F
t
t
i
l
r
e
t
e
r
s
c
t
a
n
b
e
r
e
m
d
o
v
o
e
d
1
h
h
o
u
g
h
e
i
t
h
e
r
s
i
e
f
u
n
i
.
2
-
3
/
1
6
1
5
-
/
1
/
4
"
K
N
O
C
K
O
U
T
F
O
R
8
"
O
D
L
I
Q
U
I
D
C
O
N
N
E
C
T
I
O
N
*
*
w
R
e
f
e
r
t
o
I
N
S
T
A
L
L
I
N
G
R
E
F
R
I
G
E
R
A
N
T
M
A
I
N
S
i
n
i
n
s
t
a
l
l
a
t
i
o
n
i
n
s
t
r
u
c
t
i
o
n
h
e
n
p
i
p
i
n
g
t
h
r
o
u
g
h
t
h
e
o
p
p
o
s
i
t
e
s
i
d
e
o
f
t
h
e
u
n
i
t
.
FIGURE 3 - UNIT DIMENSIONS KEU180
ACCESSORIES
1. Overall dimension of the unit will vary if an electric
heater, a supply air plenum or a base is used.
2. This dimension is required for removal of the DX coil.
Only 26” is required for normal servicing.
3. If the coil has to be removed, this dimension is required
to loosen screws that secure the coil to the unit frame.
This dimension will also be required for blower motor
access if the piping connections are made on the oppo-
site side of the unit.
•
ELECTRIC HEATER - Add 14-1/4” to unit height when using 10,
16, 26, or 36 KW heater
•
•
•
SUPPLY AIR PLENUM - Add 27” to unit height when used.
BASE - Add 24” to unit height when used.
HOT WATER OR STEAM COIL - Add 6” to unit depth when used.
TABLE 20: UNIT CLEARANCES KEU180
MINIMUM CLEARANCES
180
24”
24”
4. Allow enough clearance to trap the condensate drain
lines.
Side Air with RETURN AIR opening
Side with SUPPLY AIR opening1
Side with PIPING CONNECTIONS2
Side opposite PIPING CONNECTIONS3
Bottom4
61”
26”
-
18
Unitary Products Group
036-21300-002-A-0905
6833/<ꢃ$,5ꢃ3/(180
*
.
ꢅ
(
)
+
&
ꢍꢍꢉꢍꢈꢆ
ꢍꢉꢍꢈꢆ
.
/
ꢈ63ꢀꢄꢉꢌ
ꢈ63ꢀꢄꢉꢈ
'
%
$
ꢈꢍꢀꢃꢅꢃ.12&.2876ꢃ)25ꢃ32:(5ꢃ ꢃ&21752/ꢃ:,5,1*
+
6+,33('ꢁ.12&.('ꢉ'2:1
ꢁꢁꢁ)25ꢁ),(/'ꢁ$66(0%/<
WITH ELECTRIC HEAT - Remove this 2-1/2” knockout and one of the 7/8”
knockouts from the rear panel of the plenum. Remove the 1-23/32” knockout
and one of the 7/8” knockouts from the top panel of the basic unit. Install a 1/
2” squeeze connector in both of the 7/8” openings.
ꢀꢊꢀꢋꢃꢀꢁꢀꢋꢃꢈꢌꢀꢃꢅꢃ.12&.287ꢃ)25ꢃ32:(5ꢃ:,5,1*
WITH ELECTRIC HEAT - Remove this 2-1/2” knockout from the
rear panel of the plenum. Route the power wiring conduit through
this opening and connect it to the field-supplied fitting on the elec-
tric heat accessory. Connect the power wiring to the fuse block in
the heater control box.
Route the power wiring conduit through the 2-1/2” opening and connect it
to the field-supplied fitting on the electric heat accessory. Connect the
power wiring to the fuse block in the heater control box.
Route the control wires through the 7/8” openings and connect them to
the terminals on block TB1. Secure them with the 1/2” squeeze connec-
tors.
Install the control wiring per basic unit Installation Manual.
DO NOT route any field control wiring through the plenum.
Electric Heaters are NOT CSA approved for installation
within a supply air plenum.
Electric Heaters are NOT CSA approved for installation
within a supply air plenum.
WITHOUT ELECTRIC HEAT - Remove both 7/8” knockouts from the rear
panel of the plenum and both 7/8” knockouts from the top panel of the
basic unit. Install a 1/2” squeeze connector in one of the plenum open-
ings and both of the unit openings. Install a 1/2” conduit fitting in the other
opening of the plenum.
WITHOUT ELECTRIC HEAT - Install the power and the control wiring
per basic unit Installation Manual. DO NOT route any wiring through
the plenum and DO NOT remove this knockout.
Connect the power wiring conduit to the fitting on the plenum. Route the
power wiring through the conduit, one of the squeeze connectors on the
unit, and the field-supplied squeeze connector on the blower motor contac-
tor box. Connect the power wiring to the blower motor contactor.
Plenum Dimensions (inches)
Plenum Unit
Model Model
A
B
C
D
E
F
G
H
K
L
2
1SP0450 060
36 25-1/2 34-2/8 31-3/4 15-3/4 7-5/8 7/8 2-1/8 11-1/4
090
1SP0451
120
52-1/8 28-1/4 27-1/2 49-3/8 17-7/8 8-3/4 7/8 1-1/8 15-1/4 1-3/4
Route the control wires through the remaining plenum and unit open-
ings and connect them to the terminals on block TB1. Secure them
with the 1/2” squeeze connectors.
1SP0452 180 60-3/4 31
27 55-3/4 19-7/8 6-1/8 1- 2-1/2 19-1/2 1-3/4
'
ꢍ
/
(
)
$&&(66ꢁ23(1,1*ꢁ)25ꢁ32:(5ꢁ6833/<ꢁ:,5,1*
0
ꢍꢂ.:ꢁ7+58ꢁꢅꢃ.:ꢁꢉꢁ$GGꢁDꢁꢍꢉꢍꢈꢀꢑꢁFRQGXLWꢁILWWLQJ
ꢁꢁꢁWRꢁWKHꢁꢍꢉꢆꢅꢈꢅꢆꢑꢁKROHꢁIRUꢁZLUHꢁVL]HVꢁXSꢁWKURXJK
ꢁꢁꢁꢓꢍꢁ$:*ꢋꢁꢁ5HPRYHꢁWKHꢁNQRFNRXWꢁULQJꢁDQGꢁDGGꢁD
ꢁꢁꢁꢍꢉꢍꢈꢆꢑꢁFRQGXLWꢁILWWLQJꢁWRꢁWKHꢁꢍꢉꢅꢍꢈꢅꢆꢑꢁKROHꢁIRU
ꢁꢁꢁZLUHꢁVL]HVꢁXSꢁWKURXJKꢁꢓꢂꢁ$:*ꢋ
*
&
+($7(5
(/(0(17
&+$0%(5
+
.
ꢌꢆ.:ꢁ7+58ꢁꢅꢃ.:ꢁꢉꢁ$GGꢁDꢁꢍꢉꢍꢈꢀꢑꢁFRQGXLWꢁILWWLQJ
ꢁꢁꢁWRꢁWKHꢁꢍꢉꢆꢅꢈꢅꢆꢑꢁKROHꢁIRUꢁZLUHꢁVL]HVꢁXSꢁWKURXJK
ꢁꢁꢁꢓꢍꢁ$:*ꢋꢁꢁ5HPRYHꢁWKHꢁNQRFNRXWꢁULQJꢁDQGꢁDGGꢁD
ꢁꢁꢁꢆ ꢑꢁFRQGXLWꢁILWWLQJꢁWRꢁWKHꢁꢆꢉꢍꢈꢆꢑꢁKROHꢁIRUꢁZLUHꢁVL]HV
ꢁꢁꢁXSꢁWKURXJKꢁꢓꢂꢂꢁ ꢂꢂ $:*ꢋ
ꢅꢈꢀ
%
$
&21752/ꢁ%2;
$&&(66ꢁ3$1(/
ꢍꢈꢆ
:,5,1*ꢁ+$51(66ꢁ/2&$7,21
7KLVꢁRSHQLQJꢁLQꢁWKHꢁERWWRPꢁRIꢁWKHꢁKHDWHU
FRQWUROꢁER[ꢁLVꢁXVHGꢁIRUꢁWKHꢁZLULQJꢁKDUQHVV
WKDWꢁFRQQHFWVꢁWKHꢁKHDWHUꢁDFFHVVRU\ꢁWRꢁWKH
EDVLFꢁXQLWꢋꢁꢁ,WꢁLVꢁSURYLGHGꢁZLWKꢁDꢁVTXHH]H
FRQQHFWRUꢁIRUꢁVHFXULQJꢁWKHꢁZLULQJꢁKDUQHVVꢊ
DQGꢁLWVꢁORFDWLRQꢁFRUUHVSRQGVꢁWRꢁWKHꢁORFDꢉ
WLRQꢁRIꢁWKHꢁꢍꢉꢆꢅꢈꢅꢆꢑꢁNQRFNRXWꢁLQꢁWKHꢁWRS
SDQHOꢁRIꢁWKHꢁEDVLFꢁXQLWꢋ
FIGURE 5 - ACCESSORY DIMENSIONS
Unitary Products Group
19
036-21300-002-A-0905
TABLE 21: ELECTRIC HEATER DIMENSIONS KEU060, 090, 120 & 180
Heater Dimensions (inches)
Heater
Model
Nom.
kW
Unit
Model
A
B
C
D
E
F
G
H
K
L
M
2HT045010251
2HT045016251
2HT045026251
10
16
26
060
25-1/8 22-1/2
13
7/8
4
1/2 5-1/4 1-11/16 1-3/4 20-1/8 16-7/8
2HS04501025, 46, 58
2HS04501625, 46, 58
2HS04502625, 46, 58
2HS04503625, 46, 58
10
16
26
36
090
120
180
27-1/4 25-1/4 14-1/4
1
4
1/2 5-1/2
1-1/2
2-1/4
1-1/2 22-1/4 19-1/4
2-1/2 22-1/4 19-1/4
2HS04507225, 46, 58
72
180
29-7/8 26-3/8 21-3/4 2-3/8 5-1/4 3/4 6-3/8
1. The 2HT heaters are not CSA approved for 060 units mounted horizontally.
RETURN AIR GRILLE
B
A
S
E
A
C
B
B
A
5/8
FIGURE 7 - BASE ACCESSORY
FIGURE 6 - RETURN AIR GRILL
Grill Dimensions (Inches)
Grill Dimensions (Inches)
Grill Model
Unit Model
Grill Model
Unit Model
A
B
C
A
B
1BS0450
1BS0451
1BS0452
060
36
52
22
20
20
24
1RG0450
1RG0451
1RG0452
060
36
22
090
120
090
120
25-1/8
31-5/8
52
25
31
180
60-3/4
180
60-3/4
20
Unitary Products Group
036-21300-002-A-0905
C
1-1/2" NPTE
CONNS.
B
Steam Coil Dimensions (inches)
Coil
Model
Unit
Model
A
B
21-7/8
25
C
5
5
5
6
D
E
F
1
060
090
120
180
36
52
52
2-1/2
2-1/2
2-1/2
2-5/8 10-5/8
2-5/8 13-5/8
2-5/8 13-5/8
1NF0450
1
1NF0451
F
1
25
1NF0451
E
2
60-3/4 32-1/4
3-5/16 3-1/2 17-1/2
1NF0452
A
1. Installs over the return air opening of the unit-before the filters.
2. Installs between the coil and blower section of the unit.
D
2
FIGURE 8 - STEAM COIL
&
Hot Water Coil Dimensions (inches)
Coil
Unit
Model
Model
%
A
B
C
D
E
F
G
H
*
1”
NPTE
ꢍ³ꢁ137(
&211¶6ꢋ
1
060
090
120
36 21-7/8
5
1-11/16 2-3/4 6-1/4 3-3/8
1-11/16 2-3/4 5-7/8 3-3/8
1-11/16 2-3/4 5-7/8 3-3/8
2-5/32 3-5/16 6-9/16 3-27/32
1HW0450
ꢆ
1”
NPTE
1
52
52
25
25
5
5
6
1HW0451
1”
NPTE
)
(
1
1HW0451
$
1-3/8
NPTE
2
180 60-3/4 32-1/4
1HW0452
1. Installs over the return air opening of the unit-before the filters.
2. Installs between the coil and blower section of the unit.
'
ꢆ
FIGURE 9 - HOT WATER COIL
Unitary Products Group
21
036-21300-002-A-0905
TABLE 22: KEU ELECTRICAL DATA
Min.
Max. Fuse1 /
Power
Supply
Voltage
Indoor
Motor
FLA
Heater
Model
Number
Nominal
Heater
KW
Model
(TONS)
Applied
Heater KW
Electric
Heat Amps
Circuit
Ampacity
(AMPS)
9.5
HACR
Breaker2
(AMPS)
15
None
--
--
--
2HT04501025
2HT04501625
2HT04502625
None
10
16
26
--
7.5
20.8
33.4
54.2
--
35.6
51.2
77.3
8.6
40
208
240
7.6
6.9
12.0
19.5
--
60
3
80
060
(5)
15
2HT04501025
2HT04501625
2HT04502625
None
10
16
26
--
10.0
16.0
26.0
--
24.1
38.5
62.5
--
38.7
56.7
86.8
8.3
40
60
90
15
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
10
16
26
36
--
7.5
20.8
33.4
54.2
75.1
--
34.3
49.9
76.0
102.1
7.5
35
208
240
460
575
208
240
460
575
6.6
6.0
3.0
2.4
7.5
6.8
3.4
2.7
12.0
19.5
27.0
--
50
80
110
15
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
10
16
26
36
--
10.0
16.0
26.0
36.0
--
24.1
38.5
62.5
86.6
--
37.6
55.6
85.7
115.8
3.8
40
60
90
125
15
090
(7.5)
2HS04501046
2HS04501646
2HS04502646
2HS04503646
None
10
16
26
36
--
10.0
16.0
26.0
36.0
--
12.0
19.2
31.3
43.3
--
18.8
27.8
42.8
57.9
3.0
20
30
45
60
15
2HS04501058
2HS04501658
2HS04502658
2HS04503658
None
10
16
26
36
--
10.0
16.0
26.0
36.0
--
9.6
15.0
22.2
34.3
46.3
9.4
20
15.4
25.0
34.6
--
25
35
50
15
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
10
16
26
36
--
7.5
20.8
33.4
54.2
75.1
--
35.4
51.1
77.1
103.2
8.5
40
12.0
19.5
27.0
--
60
80
110
15
2HS04501025
2HS04501625
2HS04502625
2HS04503625
None
10
16
26
36
--
10.0
16.0
26.0
36.0
--
24.1
38.5
62.5
86.6
--
38.6
56.6
86.7
116.8
4.3
40
60
90
125
15
120
(10)
2HS04501046
2HS04501646
2HS04502646
2HS04503646
None
10
16
26
36
--
10.0
16.0
26.0
36.0
--
12.0
19.2
31.3
43.3
--
19.3
28.3
43.3
58.4
3.4
20
30
45
60
15
2HS04501058
2HS04501658
2HS04502658
2HS04503658
10
16
26
36
10.0
16.0
26.0
36.0
9.6
15.4
22.6
34.6
46.7
20
15.4
25.0
34.6
25
35
50
22
Unitary Products Group
036-21300-002-A-0905
TABLE 22: KEU ELECTRICAL DATA (CONTINUED)
Min.
Circuit
Ampacity
(AMPS)
13.3
Max. Fuse1 /
Power
Supply
Voltage
Indoor
Motor
FLA
Heater
Model
Number
Nominal
Heater
KW
Model
(TONS)
Applied
Heater KW
Electric
Heat Amps
HACR
Breaker2
(AMPS)
20
None
--
--
--
2HS04501025
2HS04501625
2HS04502625
2HS04503625
2HS04507225
None
10
16
26
36
72
--
7.5
20.8
33.4
54.2
75.1
150.1
--
39.3
40
12.0
19.5
27.0
54.1
--
54.9
60
208
240
460
575
10.6
9.6
81.0
90
107.1
200.9
12.0
110
225
15
2HS04501025
2HS04501625
2HS04502625
2HS04503625
2HS04507225
None
10
16
26
36
72
--
10.0
16.0
26.0
36.0
72.0
--
24.1
38.5
62.5
86.6
173.2
--
42.1
45
60.1
70
90.2
100
125
250
15
120.3
228.5
6.0
180
(15)
2HS04501046
2HS04501646
2HS04502646
2HS04503646
2HS04507246
None
10
16
26
36
72
--
10.0
16.0
26.0
36.0
72.0
--
12.0
19.2
31.3
43.3
86.6
--
21.0
25
30.1
35
4.8
45.1
50
60.1
70
114.3
4.9
125
15
2HS04501058
2HS04501658
2HS04502658
2HS04503658
2HS04507258
10
16
26
36
72
10.0
16.0
26.0
36.0
72.0
9.6
16.9
20
15.4
25.0
34.6
69.3
24.1
25
3.9
36.1
40
48.2
50
91.5
100
1. Dual element time delay.
2. HACR type per NEC.
3. The K*EU060 indoor motor is single phase. The electrical heaters MUST be supplied with 3-phase voltage only.
Unitary Products Group
23
036-21300-002-A-0905
COOLING ONLY UNITS AND UNITS WITH
UNITS WITH ELECTRIC HEAT ACCESSORY
STEAM OR HOT WATER COIL ACCESSORY
3-PHASE
LINE VOLTAGE
POWER SUPPLY
POWER WIRING,
DESCONNECT
SWITCH
AND FUSING
(OR CIRCUIT
BREAKER)
LINE VOLTAGE
POWER SUPPLY
POWER WIRING,
TERMINALS ON
SUPPLY AIR
BLOWER MOTOR
TERMINALS
ON FUSE HOLDER
IN ELECTRIC HEAR
CONTROL BOX
DESCONNECT SWITCH
AND FUSING TO BE
SUPPLIED BY FIELD
CONTACTOR
10M
GROUND LUG
IN ELECTRIC HEAT
CONTROL BOX
TO BE SUPPLIED
BY FIELD
GROUND
SCREW
NOTE: USE COPPER
CONDUCTORS ONLY
*Not required on 060 (1-Phase
only) All other units are 3-Phase.
WIRE IN ACCORDANCE WITH LOCAL
AND NATIONAL ELECTRICAL CODES
FIGURE 10 - FIELD WIRING FOR POWER SUPPLY
COOLING ONLY UNITS
2-STAGE COOLING FOR HCA180/KEU180**
1-STAGE COOLING
R
R
Y
RC
Y1
Y2
G
R
Y
TO
COND.
UNIT
Y
TO
COND.
UNIT
G
O
G
B
G
B
24-VOLT
CONTROL
WIRING
24-VOLT
CONTROL
WIRING
TERMINALS ON
THERMOSTAT 6TH13700724
WITH SUB-BASE 2TB08700124
TERMINALS ON
THERMOSTAT 6TH04701724
WITH SUB-BASE 2TB04700124
TERMINAL
BLOCK 4TB
ON BLOWER UNIT
TERMINAL BLOCK 4TB
ON BLOWER UNIT
FIGURE 11 - COOLING ONLY UNIT
UNITS WITH STEAM OR HOT WATER COIL ACCESSORY
1-STAGE COOLING
24-VOLT CONTROL WIRING
2-STAGE COOLING FOR HCA180/KEU180**
24-VOLT CONTROL WIRING
R
R
R
R
Y
O
G
B
TO
COND.
UNIT
Y
G
B
Y1
Y2
G
Y
G
W
TO
COND.
UNIT
TERMINALS ON
THERMOSTAT
6TH04701524
WITH SUB-BASE
2TB04700324
W
TO HEATER COIL
CONTROL CIRCUIT
TERMINAL
BLOCK 4TB
ON BLOWER UNIT
TERMINAL
BLOCK 4TB
ON BLOWER UNIT
TO HEATER COIL
CONTROL CIRCUIT
TERMINALS ON THERMOSTAT 6TH13700724
WITH SUB-BASE 2TB17700324
FIGURE 12 - UNIT WITH STEAM OR HOT WATER COIL ACCESSORY
24
Unitary Products Group
036-21300-002-A-0905
U
N
I
T
S
W
I
T
H
E
L
E
C
T
R
I
C
H
E
A
T
A
C
C
E
S
S
O
R
Y
T
O
E
R
M
I
N
A
L
B
L
O
C
K
4
T
B
N
B
L
O
W
E
R
U
N
I
T
2
4
-
V
O
L
T
C
O
N
T
R
O
L
W
I
R
I
N
G
R
O
R
T
C
U
O
Y
Y
1
2
Y
O
N
N
D
.
I
T
1
1
N
O
T
E
S
:
1
W
W
1
2
O
N
n
l
y
r
e
q
u
i
r
e
d
f
o
r
2
-
s
t
a
g
e
c
o
t
o
l
i
n
g
.
*
*
6
6
6
0
2
3
o
t
r
e
q
u
i
r
e
d
o
t
n
1
a
0
K
W
h
e
-
a
e
r
e
s
(
o
n
l
y
o
n
e
u
-
s
s
h
t
a
g
e
h
e
a
t
i
n
g
)
.
T
h
i
s
l
t
h
e
r
m
o
s
a
t
n
d
s
u
b
b
a
s
m
u
s
t
b
e
e
d
w
h
e
n
e
v
e
r
2
a
b
o
w
e
r
u
n
i
t
i
s
e
q
u
i
p
p
e
d
w
i
t
h
a
n
e
l
e
c
t
r
i
c
e
a
t
a
c
c
e
s
s
o
r
y
.
G
5
3
J
U
M
P
u
E
R
A
n
o
t
d
o
o
r
t
t
h
w
e
r
m
o
s
t
a
t
c
a
n
G
T
E
H
R
M
R
I
N
A
L
S
O
N
b
e
3
w
a
i
r
e
d
b
e
e
o
e
o
n
n
v
t
6
e
r
m
i
n
a
l
s
3
T
E
M
O
S
T
A
T
6
T
H
0
4
7
0
1
5
2
4
5
t
7
n
d
6
0
t
o
p
r
i
d
e
a
d
d
i
-
B
W
I
T
H
S
U
B
-
B
A
S
E
2
T
B
0
4
7
0
0
3
2
4
i
o
n
a
l
s
t
a
g
i
n
g
3
a
n
d
2
K
W
h
e
a
t
e
r
s
.
T
h
e
m
f
i
i
e
l
d
w
i
r
i
n
g
c
o
n
n
e
c
b
t
e
d
t
o
t
h
e
s
e
d
u
m
m
f
y
*
W
i
r
e
R
o
n
4
T
B
t
t
e
r
m
i
n
a
l
b
l
5
o
c
k
i
s
n
o
t
r
e
q
e
u
i
r
e
d
o
n
5
t
o
n
u
n
i
t
.
t
t
e
h
r
e
n
a
l
s
o
n
4
T
B
c
a
n
e
r
o
u
e
t
r
e
d
d
i
t
r
e
c
t
f
l
y
r
o
m
*
*
O
n
l
y
a
p
p
l
i
e
w
s
o
H
C
A
1
8
0
/
K
E
U
1
d
8
u
0
s
y
s
t
m
s
w
h
o
e
r
n
t
h
T
e
H
C
A
1
8
0
i
t
s
c
o
n
d
e
n
s
i
o
n
g
u
n
i
t
t
i
o
t
h
e
t
m
o
s
a
t
i
d
e
s
i
r
a
e
d
.
e
w
q
h
h
u
a
i
i
p
p
e
d
i
t
h
t
h
e
c
a
p
a
c
i
.
t
y
r
e
c
t
i
l
o
i
n
a
c
c
e
s
s
y
.
w
o
1
1
5
e
-
v
o
l
N
O
T
E
:
T
e
r
m
i
i
n
a
l
R
n
4
T
h
B
s
n
o
t
a
d
u
m
m
y
t
e
r
m
i
n
l
o
n
i
r
e
s
w
i
l
l
a
l
s
o
u
b
e
r
e
q
u
i
r
e
d
h
f
t
o
h
r
e
t
h
e
q
u
i
d
l
i
e
n
e
s
o
l
e
n
o
i
d
v
e
a
l
s
v
K
e
E
U
0
6
0
u
n
t
s
b
e
c
a
u
s
e
t
e
s
e
u
n
i
t
s
i
n
c
l
u
d
e
a
t
r
a
n
s
f
o
r
m
-
t
t
w
i
l
l
b
e
o
f
r
n
5
i
s
h
e
d
w
i
t
c
a
p
a
i
c
i
t
y
r
d
u
c
t
m
i
o
n
a
o
c
n
c
s
o
r
y
.
r
t
h
a
t
p
o
w
e
r
s
t
r
h
e
c
o
n
t
r
o
l
c
i
r
c
u
i
t
.
O
n
l
a
r
g
e
r
s
y
s
t
e
m
s
,
R
e
f
e
r
a
t
o
F
r
m
5
0
.
1
3
N
1
f
o
r
a
d
d
t
i
o
n
a
l
i
n
f
o
r
a
t
i
o
n
t
h
i
s
t
r
a
n
s
f
o
r
m
e
i
s
s
u
p
p
l
i
e
d
w
i
t
h
t
h
e
c
o
n
d
e
n
s
i
n
g
u
n
i
t
.
t
s
c
c
e
s
s
o
r
.
FIGURE 13 - FIELD WIRING FOR UNITS WITH ELECTRIC HEAT
Unitary Products Group
25
036-21300-002-A-0905
26
Unitary Products Group
036-21300-002-A-0905
Unitary Products Group
27
Subject to change without notice. Printed in U.S.A.
Copyright © by Unitary Products Group 2005. All rights reserved.