		 FOR YOUR SAFETY   
					If you smell gas:   
					1. Open windows.   
					® 
					2. DO NOT try to light any appliance.   
					3. DO NOT use electrical switches.   
					4. DO NOT use any telephone in   
					your building.   
					Combat   
					5. Leave the building.   
					6. Immediately call your local gas   
					supplier after leaving the building.   
					Follow the gas suppliers   
					instructions.   
					7. If you cannot reach your gas   
					supplier, call the Fire Department.   
					UHA-Series   
					Tubular Unit Heaters   
					(Standard Range)   
					WARNING   
					Installation, Operation   
					& Service Manual   
					Models UHA[S]   
					150, 175, 200, 225   
					250, 300, 350, 400   
					Fire Hazard   
					Do not store or use gasoline or other   
					flammable vapors and liquids in the   
					vicinity of this or any other appliance.   
					Some objects will catch fire or explode   
					when placed close to heater.   
					Failure to follow these instructions can   
					result in death, injury or property   
					damage.   
					WARNING   
					Installer   
					Improper installation, adjustment, alteration, service   
					or maintenance can result in death, injury or property   
					damage. Read the Installation, Operation and Service   
					Manual thoroughly before installing or servicing   
					this equipment.   
					Please take the time to read and understand   
					these instructions prior to any installation.   
					Installer must give a copy of this manual to the owner.   
					Owner   
					Installation must be done by a contractor qualified   
					in the installation and service of gas-fired heating   
					equipment or your gas supplier.   
					Keep this manual in a safe place in order to provide   
					your serviceman with necessary information.   
					Roberts-Gordon, LLC   
					1250 William Street   
					P.O. Box 44   
					Buffalo, New York 14240-0044   
					Telephone: 716.852.4400   
					Fax: 716.852.0854   
					Toll Free: 800.828.7450   
					
					Quality in Any Language™   
					© Copyright 2007 Roberts-Gordon, LLC   
					P/N 111101NA 10/07 Rev. D   
				TABLE OF CONTENTS   
					SECTION 1: Heater Safety......................................................1 SECTION 11: User Instructions............................................22   
					
					
					
					
					
					
					
					
					
					
					SECTION 3: Critical Considerations .....................................3 SECTION 12: Servicing.........................................................24   
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					3.9 Separated Combustion Installation..............................3 SECTION 13: Troubleshooting .............................................27   
					
					
					
					
					
					
					
					13.2 Troubleshooting For Automatic Ignition Burner   
					Systems...................................................................28   
					
					
					
					4.6 High Altitude ................................................................5 SECTION 14: Replacement Parts.........................................31   
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					6.5 Vertical Venting............................................................8 SECTION 15: Specifications.................................................37   
					
					
					
					
					15.1 Standard (Models 150 - 400) UHA(S) Series   
					Dimension Data .........................................................37   
					
					
					7.2 Unvented Installation.................................................. 13 SECTION 16: The ROBERTS GORDON® COMBAT®   
					
					
					
					
					
					
					
					
					
					
					
					
					
					
					UHA-Series Warranty.....................................39   
					© 2007 Roberts-Gordon, LLC   
					All rights reserved. No part of this work covered by the copyrights herein may be reproduced   
					or copied in any form or by any means - graphic, electronic, or mechanical, including   
					photocopying, recording, taping or information storage and retrieval systems - without the   
					written permission of Roberts-Gordon, LLC.   
					Printed in U.S.A.   
				TABLE OF FIGURES   
					Figure 1: Installation Clearances and Clearances to   
					Combustibles.............................................................4   
					
					
					Figure 4: Standard Vented Heater - Vertical and   
					Horizontal Vent Termination ......................................9   
					Figure 5: Standard Vented Heater - Common Vertical Vent   
					Termination.............................................................. 10   
					Figure 6: Separated Combustion Heater - Vertical and   
					Horizontal Vent Termination .................................... 11   
					
					Figure 8: Concentric Vertical and Horizontal Vent   
					Termination - Separated Combustion Heater........... 12   
					
					
					
					
				SECTION 1: HEATER SAFETY   
					SECTION 1: HEATER SAFETY   
					Your Safety is Important to Us!   
					This symbol is used throughout   
					the manual to notify you of   
					possible fire, electrical or burn   
					hazards. Please pay special   
					attention when reading and   
					following the warnings in these   
					sections.   
					Installation, Service and Annual   
					Inspection of heater must be done by a contractor   
					qualified in the installation and service of gas-fired   
					heating equipment.   
					Read this manual carefully before installation,   
					operation or service of this equipment.   
					Heaters are not approved for residential installation.   
					These instructions, the layout drawing, local codes   
					and ordinances and applicable standards that apply   
					to gas piping, electrical wiring, venting, etc. must be   
					thoroughly understood before proceeding with the   
					installation.   
					Thin sheet metal parts, including the various venting   
					components, have sharp edges. To prevent injury,   
					the use of work gloves is recommended.   
					Before installation, check that the local distribution   
					conditions, nature of gas and pressure and   
					adjustment of the appliance are compatible.   
					1.1 Manpower Requirements   
					To prevent personal injury and damage to the   
					heater, two persons will be required for installation.   
					1 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					SECTION 2: INSTALLER RESPONSIBILITY   
					The installer is responsible for the following:   
					2.2 Corrosive Chemicals   
					• To install the heater, as well as the gas and   
					electrical supplies, in accordance with applicable   
					specifications and codes. Roberts-Gordon   
					recommends the installer contact a Local   
					Building Inspector or Fire Marshal for guidance.   
					CAUTION   
					Do not use heater in an area containing corrosive   
					chemicals.   
					Avoid the use of corrosive chemicals to ensure a   
					longer life of the burner, heat exchanger and other   
					parts.   
					• To use the information given in a layout drawing   
					and in the manual together with the cited codes   
					and regulations to perform the installation.   
					Failure to follow these instructions can result in   
					property damage.   
					• To install the heater in accordance with the   
					clearances to combustibles.   
					Roberts-Gordon cannot be responsible for ensuring   
					that all appropriate safety measures are undertaken   
					prior to installation; this is entirely the responsibility   
					of the installer. It is essential that the contractor, the   
					sub-contractor, or the owner identifies the presence   
					of combustible materials, corrosive chemicals or   
					halogenated hydrocarbons* anywhere in the   
					premises.   
					• To furnish all needed materials not furnished as   
					standard equipment.   
					• To plan location of supports, vents and air   
					intakes.   
					• To provide access for servicing.   
					• To provide the owner with a copy of this   
					Installation, Operation and Service Manual.   
					• To never use heater as support for a ladder or   
					other access equipment and never hang or   
					suspend anything from heater.   
					* Halogenated Hydrocarbons are a family of chemical   
					compounds characterized by the presence of halogen ele-   
					ments (fluorine, chlorine, bromine, etc.). These compounds are   
					frequently used in refrigerants, cleaning agents, solvents, etc. If   
					these compounds enter the air supply of the burner, the life   
					span of the heater components will be greatly reduced. An out-   
					side air supply must be provided to the burners whenever the   
					presence of these compounds is suspected. Warranty will be   
					invalid if the heater is exposed to halogenated hydrocarbons.   
					• To ensure there is adequate air circulation   
					around the heater and to supply air for   
					combustion, ventilation and distribution in   
					accordance with local codes.   
					2.3 National Standards and Applicable Codes   
					2.1 Wall Tag   
					All appliances must be installed in accordance with   
					the latest revision of the applicable standards and   
					national codes. This refers also to the electric, gas   
					and venting installation. Note: Additional standards   
					for installations in public garages, aircraft hangars,   
					etc. may be applicable.   
					A laminated wall tag is included with the heater as a   
					permanent reminder of the safety instructions and   
					the importance of the required clearances to   
					combustibles. Affix the tag by peeling off the backing   
					of the adhesive strips on the rear surface and   
					position the tag on a wall near the heater.   
					A copy of the wall tag (P/N 91040031) is illustrated   
					on the back cover.   
					Know your model number. Model number is found   
					on the heater and in the Installation, Operation and   
					
					
					2 
					 
					 
					 
					 
				SECTION 3: CRITICAL CONSIDERATIONS   
					SECTION 3: CRITICAL CONSIDERATIONS   
					3.1 Basic Information   
					3.7 Electrical Supply   
					UHA(S) heaters have automatic ignition burners for A permanent 120 V 60 Hz 1 Ø electrical supply is   
					ON/OFF operation only.   
					required for the main electrical power. The heater   
					also requires suitable controls in accordance with   
					
					3.2 Location and Suspension   
					All models:   
					• Must be installed indoors.   
					3.8 Vent   
					Choose heater orientation to allow for the proper   
					location of the vent. Each heater must be fitted with   
					a correctly sized sealed vent system.   
					If vented horizontally, no other appliance may be   
					
					• Must be installed in a level position with   
					horizontal discharge.   
					• May be mounted on a shelf of non-combustible   
					material.   
					
					Figure 2) or from wall brackets of sufficient   
					strength to support the heater as listed in the   
					
					Drop rods must be a minimum of 3/8" diameter   
					mild steel. Four suspension points (3/8" nuts)   
					are located on top of the heater.   
					3.9 Separated Combustion Installation   
					For separated combustion installation, the vent and   
					air intake must be fitted with an individual and   
					correctly sized sealed system and the vent and air   
					intake must terminate at approved wall and roof   
					terminals.   
					• Must be installed in a manner which allows   
					access to all serviceable components.   
					See Page 4, Figure 1 for details.   
					Separated combustion units may not be common   
					
					3.3 Minimum Required Installation Clearances   
					Clearances around the heater and vent must be as   
					
					through Page 12, Figure 8 to ensure access for   
					servicing, and correct operation.   
					3.4 Clearances to Combustibles   
					Clearances must be as indicated on Page 4, Figure   
					1. If clearances to combustibles are not indicated,   
					then installation clearances apply.   
					3.5 Ventilation   
					It is important to ensure that there is adequate air   
					space around the heater to supply air for   
					combustion, ventilation and distribution in   
					accordance with local and national codes.   
					3.6 Gas Supply   
					It is important that the gas supply pipe is sized   
					correctly to provide the inlet pressure as stated on   
					the heater data plate. The gas supply pipe and   
					electrical connections must not support any of the   
					heater's weight.   
					3 
					 
					 
					 
					 
					 
					 
					 
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					WARNING   
					Fire Hazard   
					Some objects will catch fire or explode when placed   
					close to heater.   
					Keep all flammable objects, liquids and vapors the   
					required clearances to combustibles away from heater.   
					Failure to follow these instructions can result in death,   
					injury or property damage.   
					Figure 1: Installation Clearances and Clearances to Combustibles   
					Installation Clearances   
					Clearances to Combustibles   
					Roof Terminal   
					(Optional separated   
					combustion concentric   
					venting shown.)   
					6"   
					(15 cm)   
					Top   
					31"   
					(79 cm)   
					6"**   
					(15 cm)   
					10'   
					(3 m)   
					24" for   
					Wall   
					Terminal   
					adequate   
					air flow access   
					axial fan.   
					3"   
					20' (6.0 m) - 30' (9.1 m)   
					Max. Mounting Height*   
					* Recommended mounting height varies with heater input.   
					Heaters may be mounted at a higher level if destratification   
					Clearance to Vent: 2" (5 cm)   
					fans are installed.   
					Note: Venting directly from top of heater not applicable   
					on Models 150 - 400.   
					**31" (79 cm) minimum is necessary   
					for servicing.   
					The heater must always be installed at least 6' (2 m) above the floor.   
					The vent pipe must have clearance from combustibles by 2" (5 cm).   
					If installed at low levels where individuals can come in contact with hot heat   
					exchanger components, adequate guarding must be provided.   
					4 
					 
				SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES   
					SECTION 4: NATIONAL STANDARDS AND APPLICABLE CODES   
					4.1 Gas Codes   
					4.3 Parking Structures and Repair Garages   
					The type of gas appearing on the nameplate   
					must be the type of gas used. Installation must   
					comply with national and local codes and   
					requirements of the local gas company.   
					Installation in garages must be in accordance   
					with the following codes:   
					United States: Standard for Parking Structures   
					NFPA 88A - latest revision or the Code for Motor   
					Fuel Dispensing Facilities and Repair Garages,   
					NFPA 30A - latest revision. Canada: Refer to   
					CSA B149.1 Natural Gas and Propane   
					Installation Code.   
					United States: Refer to NFPA 54/ANSI Z223.1 -   
					latest revision, National Fuel Gas Code.   
					Canada: Refer to CSA B149.1 Natural Gas and   
					Propane Installation Code.   
					• In accordance with the Standard for Parking   
					Structures NFPA 88A, heaters must be located   
					a minimum of 18" (50 cm) below the floor-ceiling   
					assembly or 18" (50 cm) above the floor.   
					4.2 Aircraft Hangars   
					Installation in aircraft hangars must be in   
					accordance with the following codes:   
					• In accordance with the Code for Motor Fuel   
					Dispensing Facilities and Repair Garages,   
					NFPA 30A - latest revision, heaters must not be   
					installed less than 8' (2.4 m) above the floor.   
					United States: Refer to Standard for Aircraft   
					Hangars, NFPA 409 - latest revision.   
					Canada: Refer to Standard CSA B149.1 Natural   
					Gas and Propane Installation Code.   
					4.4 Electrical   
					• In aircraft storage and servicing areas, heaters   
					shall be installed at least 10' (3 m) above the   
					upper surface of wings or of engine enclosures   
					of the highest aircraft which may be housed in   
					the hangar. The measurement shall be made   
					from the wing or engine enclosure (whichever is   
					higher from the floor) to the bottom of the heater.   
					The heater must be electrically grounded in   
					accordance with the following codes:   
					United States: Refer to National Electrical   
					Code®, NFPA 70 - latest revision. Wiring must   
					conform to the most current National Electrical   
					Code®, local ordinances and any special   
					diagrams furnished.   
					• In shops, offices and other sections of aircraft   
					hangars communicating with aircraft storage or   
					servicing areas, heaters shall be installed not   
					less than 8' (2.4 m) above the floor.   
					Canada: Refer to Canadian Electrical Code,   
					CSA C22.1 Part 1 - latest revision.   
					• Suspended or elevated heaters shall be so   
					located in all spaces of aircraft hangars that they   
					shall not be subject to injury by aircraft, cranes,   
					movable scaffolding or other objects. Provisions   
					shall be made to assure accessibility to   
					suspended heaters for recurrent maintenance   
					purposes.   
					4.5 Venting   
					The venting must be installed in accordance   
					with the requirements within this manual and   
					the following codes:   
					United States: Refer to NFPA 54/ANSI Z223.1 -   
					latest revision, National Fuel Gas Code.   
					Canada: Refer to CSA B149.1 Natural Gas and   
					Propane Installation Code.   
					4.6 High Altitude   
					These heaters are approved for installations up   
					to 2000' (610 m) (US), 4500' (1370 m) (Canada)   
					without modification. Consult factory if US   
					installation is above 2000' (610 m) or Canadian   
					installation is above 4500' (1370 m).   
					5 
					 
					 
					 
					 
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					SECTION 5: MAJOR COMPONENTS   
					5.1 General   
					Heaters are designed for installation above 6'   
					(1.8 m). These heaters must be installed within the   
					heated space. Duct delivery systems are not   
					permitted with axial fan units. When handling or   
					supporting the heater from below, ensure that the   
					weight is taken at the support points.   
					5.2 Suspension   
					WARNING   
					Crush Hazard   
					Use 3/8" threaded rod   
					minimum.   
					Failure of the supports can   
					result in death, injury   
					or property damage.   
					
					Figure 2: Suspension Methods   
					Ensure all suspension   
					hardware is torqued to   
					a minimum of 20 ft lbs.   
					Unistrut   
					Channel Nut   
					Washer   
					Nut   
					3/8"   
					Threaded   
					Rod   
					Cone Point   
					Set Pin   
					Window   
					Clamp   
					3/8"   
					Threaded   
					Rod   
					Unistrut   
					Nut   
					Washer   
					Riv   
					Nut   
					Support Points   
					6 
					 
					 
					 
					 
				SECTION 6: VENTING   
					SECTION 6: VENTING   
					6.1 Venting   
					mechanical air supply inlet to any building.   
					The vent shall not terminate within 3' (.9 m) of a   
					This heater must be vented in accordance with the   
					rules contained in this manual and with the following window or door that can be opened in any building,   
					national codes and any state, provincial or local   
					codes which may apply: United States: Refer to   
					NFPA 54/ANSI Z223.1 - latest revision, National   
					Fuel Gas Code; Canada: Refer to CSA B149.1   
					Natural Gas and Propane Installation Code.   
					Any portion of vent pipe passing through a   
					combustible wall must have an listed thimble to   
					conform with the above codes.   
					any non-mechanical air supply inlet to any building,   
					or of the combustion air inlet of any other appliance.   
					6.2 Vent Installation   
					WARNING   
					The heater may be installed unvented in   
					certain circumstances according to building   
					ventilation codes. Refer to the above codes and   
					Page 8, Section 6.3 for further information.   
					Unvented operation also requires compliance with   
					the clearances to combustibles given on Page 4,   
					
					Fire Hazard   
					Some objects will catch fire or explode when placed   
					close to heater.   
					Keep all flammable objects, liquids and vapors the   
					required clearances to combustibles away from heater.   
					The bottom of the vent or air intake terminal shall not   
					be located less than 1' (.3 m) above grade level.   
					Failure to follow these instructions can result in death,   
					injury or property damage.   
					The vent shall not terminate less than 7' (2.1 m)   
					above grade where located adjacent to public   
					walkways.   
					For vented units, the vent must terminate outside of   
					the building.   
					Vent terminal must be installed at a height sufficient   
					to prevent blockage by snow and building materials   
					protected from degradation by flue gasses.   
					Vents must be fully sealed and correctly sized for   
					the model. If the vent passes through a wall or   
					ceiling of combustible material, it must be enclosed   
					by a listed thimble and be separated from the   
					thimble by at least a 2" (5 cm) air gap.   
					Vent terminal must be beyond any combustible   
					overhang.   
					For separated combustion models, vents and air   
					intakes must be a fully sealed system and correctly   
					sized for the model. Vent should be assembled as   
					
					Figure 8. The joints between the vent terminal and   
					the roof or wall must be properly sealed. If the vent   
					passes through a wall or ceiling of combustible   
					material, it must be enclosed by a listed thimble and   
					be separated from the thimble by at least a 2" (5 cm)   
					air gap.   
					Secure all joints with corrosion resistant #8 x 3/8"   
					sheet metal screws.   
					For single wall venting, pressure sensitive aluminum   
					tape or silicone sealant must be used to seal all   
					joints.   
					Aluminum tape shall have a minimum temperature   
					rating of 400° F (204° C) and meet SMACNA AFTS-   
					100-73 standards. High temperature silicone   
					sealant must have a minimum temperature rating of   
					480° F (250° C).   
					Vents and air intakes must be adequately   
					supported so that the heater does not bear the   
					weight of the pipes.   
					6.1.1 United States Requirements   
					Vent must terminate at least 3' (.9 m) above any   
					forced air inlet located within 10' (3.1 m).   
					
					Vent must terminate at least 4' (1.2 m) below,   
					4' (1.2 m) horizontally from, or 1' (.3 m) above any   
					door, operable window, or gravity air inlet into any   
					building.   
					
					6.2.1 Standard Vented Heaters   
					(Models UHA 150 - 400)   
					NFPA 54/ANSI Z223.1 - latest revision, National   
					Fuel Gas Code specifies a 4' (1.2 m) horizontal vent   
					terminal clearance from gas and electric meters,   
					regulators and relief equipment.   
					The vent must be fitted with a low resistance   
					
					Figure 4. Standard vented heaters do not allow   
					outdoor air intake for combustion air.   
					6.1.2 Canadian Requirements   
					The vent shall not terminate within 6' (1.8 m) of a   
					7 
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					6.2.2 Separated Combustion Heaters   
					(Models UHAS 150 - 400)   
					6.5 Vertical Venting   
					Vertically vented heaters can be common vented   
					(up to 4 heaters).   
					The heaters are designed to be installed as   
					separated combustion heaters. The vent and air   
					intake are run as separate pipes to the wall or roof   
					
					vent and air intake are run as separate pipes to a   
					concentric vent box and a concentric vent/air intake   
					pipe penetrates the wall or roof.   
					For vent lengths greater than 5' (1.5 m),   
					condensation will form. Insulation is recommended   
					and condensation drains may be desired. Vent from   
					the rear of the heater cabinet then run the vent   
					vertically and use a condensate drain at the bottom   
					of the vertical vent.   
					Vent pipe must be sloped 1/4'' (.6 cm) for every   
					1' (.3 m).   
					6.3 Unvented Operation   
					For 4'' (10 cm), an approved vent cap   
					(P/N 90502102) must be used.   
					WARNING   
					Carbon Monoxide Hazard   
					For 6'' (15 cm) common vent, an approved vent cap   
					(P/N 90502103) must be used.   
					Heaters installed unvented must   
					be interlocked with sufficient   
					building exhaust.   
					For common vertical venting of more than two   
					
					Heaters must be installed   
					according to the installation   
					manual.   
					A vent shall not extend less than 2' (.6m) above the   
					highest point where it passes through a flat roof of a   
					building.   
					Failure to follow these   
					instructions can result in death   
					or injury.   
					6.6 Length Requirements   
					For unvented operation in commercial installations,   
					sufficient ventilation must be provided in the amount   
					of 4 cfm per 1000 Btu/h firing rate (United States); 3   
					cfm per 1000 Btu/h firing rate (Canada).   
					If using vent lengths greater than 5' (1.5 m),   
					condensation will form in the vent pipe. Insulation   
					and additional sealing measures (high temperature   
					silicone at all seams) are required.   
					The entire vent should be insulated with foil faced   
					fiberglass insulation (1/2" thick, 1-1/2# density   
					minimum).   
					WARNING: Combustion by-products contain a   
					chemical known to the State of California to cause   
					cancer and birth defects or other reproductive   
					harm.   
					Maximum Vent Lengths Table   
					Model UHA(S)   
					# of Elbows   
					150 - 400   
					40 ft (12.2 m)   
					35 ft (10.7 m)   
					30 ft (9.1 m)   
					25 ft (7.6 m)   
					20 ft (6.1 m)   
					1 
					2 
					3 
					4 
					5 
					6.4 Horizontal Venting   
					Horizontally vented heaters must be individually   
					vented.   
					Vent pipe must be sloped ¼" (.6 cm) for every 1' (.3   
					m). For vent lengths greater than 5' (1.5 m),   
					condensation will form. Insulation is recommended   
					and condensation drains may be desired. For vents   
					pitched up toward the vent terminal, place the   
					condensation drain within 5' (1.5 m) of the heater.   
					In noncombustible walls only, vent terminal   
					(P/N 02537801-1P) may be used.   
					For 4'' (10 cm) vents in either combustible or   
					noncombustible walls, use vent terminal (P/N   
					90502100) or equivalent insulated vent terminal.   
					Follow the manufacturer's instructions for proper   
					installation.   
					Instead of an insulated vent terminal, a listed thimble   
					(with 2" air gap) may be used with a 4" vent cap (P/N   
					90502102).   
					8 
					 
					 
					 
					 
				SECTION 6: VENTING   
					6.7 Vent Material   
					Figure 3: Vent and Roof Detail   
					Vent material may be single wall 26 ga. (minimum)   
					galvanized steel or equal thickness stainless steel.   
					
					6.2.   
					Vent   
					Terminal   
					If penetrating a combustible wall or roof, a listed   
					thimble with 2" (5 cm) clearance must be used.   
					Where local codes permit, a single section of type   
					B-1 vent material may be used at the roof or wall   
					penetration instead of a thimble. Ensure vent   
					manufacturer's clearance from vent material is   
					maintained. Seal annular space of the type B-1 vent   
					as well as all joints in the remaining vent.   
					Flashing   
					or Rain Collar   
					Roof   
					Listed Thimble   
					Vent   
					2" Air Gap to   
					Combustible Material   
					Figure 4: Standard Vented Heater - Vertical and Horizontal Vent Termination   
					Vent Terminal   
					Flashing   
					(By Others)   
					Listed   
					Thimble   
					(2" Clearance)   
					4" Dia.Vent   
					Listed   
					Thimble   
					90°   
					Vertical   
					Option   
					(2" Clearance)   
					Bend   
					Flashing   
					(By Others)   
					Horizontal   
					Option   
					Vent   
					Vent   
					Terminal   
					12" (31 cm)   
					Minimum   
					Condensate   
					Trap to Drain   
					(Optional)   
					Note: Vent supports   
					not shown.   
					Model   
					Vent Diameter   
					Part Number   
					UHA 150 - 400   
					4" (10 cm)   
					90502102   
					9 
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					Figure 5: Standard Vented Heater - Common Vertical Vent Termination   
					Type "B" vent cap   
					(7" or 8") may be used.   
					(These are not available   
					from Roberts-Gordon.)   
					SIDE VIEW   
					Type "B" Vent Pipe   
					18" (46 cm)   
					Min.   
					Roof   
					Flashing   
					Roof   
					The last section of vent pipe   
					Approved   
					Thimble   
					passing through the roof or   
					wall may be Type "B" vent pipe.   
					All other vent materials in the   
					building must be single wall   
					vent pipe.   
					(If Applicable)   
					Single Wall Pipe   
					"D"   
					4" (10 cm)   
					Single Wall Pipe   
					4" (10 cm)   
					Single Wall Pipe   
					"D" Area must equal sum   
					of open area of   
					individual vents.   
					TOP VIEW   
					10   
					 
				SECTION 6: VENTING   
					Figure 6: Separated Combustion Heater - Vertical and Horizontal Vent Termination   
					12" (31 cm)   
					Minimum from air inlet to vent   
					termination (may be horizontal   
					or vertical clearance).   
					Vent   
					Air Intake*   
					Vertical   
					Option   
					12" (31 cm)   
					Minimum from air inlet to vent   
					termination (may be horizontal   
					or vertical clearance).   
					Horizontal   
					Option   
					90°   
					Bend   
					Air Intake   
					Air Intake   
					Termination   
					Vent   
					Termination   
					Vent   
					12" (31 cm)   
					Minimum from wall   
					to vent termination.   
					Condensate   
					Trap to Drain   
					(Optional)   
					Model   
					UHAS 150 - 400   
					Model   
					UHAS 150 - 250   
					UHAS 300 - 400   
					Vent Diameter   
					4" (10 cm)   
					*Air Intake Diameter   
					4" (10 cm)   
					Terminal P/N   
					90502102   
					Terminal P/N   
					90502102   
					Listed Thimble through   
					Combustible Wall   
					5" (13 cm)   
					90502105   
					Note: Vent supports not shown   
					Figure 7: Concentric Vent Box   
					4" (10 cm) or   
					5" (13 cm)   
					Toward   
					Outside   
					Seal joint between single wall   
					and Type B vent with silicone sealant.   
					6" (15 cm) or 8" (20 cm)   
					Single Wall Inlet Air Pipe   
					(By Others)   
					Concentric   
					Vent Box   
					Use 3 sheetmetal   
					screws equally   
					spaced around joint.   
					Toward   
					Heater   
					Use 3 sheetmetal   
					screws equally   
					spaced around collar.   
					4" (10 cm) Single   
					Wall Vent Pipe   
					(By Others)   
					11   
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					Figure 8: Concentric Vertical and Horizontal Vent Termination - Separated Combustion Heater   
					Vent Terminal   
					with Baffle Plate   
					4" Type B-1   
					Vent   
					UHA 150-250:   
					Storm Collar (By Others)   
					(Attach with 3 sheet metal screws.)   
					6" Dia. Single Wall   
					UHA 300-400:   
					8" Dia. Single Wall   
					Combustion   
					Air Terminal   
					Flashing   
					(By Others)   
					Concentric   
					Vent Box   
					6" (16 cm)   
					Minimum   
					Air Intake*   
					12" (31 cm)   
					Maximum   
					Vertical   
					Option   
					Vent   
					Condensate Trap   
					to Drain (Optional)   
					10' (3 m)   
					Maximum   
					Vent Terminal   
					4"   
					with Baffle Plate   
					Type   
					B-1   
					Vent   
					Horizontal   
					Option   
					Air Intake*   
					Concentric   
					Vent Box   
					Storm Collar (By Others)   
					(Attach with 3   
					sheet metal screws.)   
					Combustion   
					Air Terminal   
					Description   
					Part Number   
					UHVK1   
					Qty.   
					Concentric Vent Kit (150 - 250)   
					Concentric Vent Box Top & Side Assembly   
					Concentric Vent Box Bottom Assembly   
					Screw #6 x 3/8 Self Drilling   
					4" Vent Terminal with Baffle Plate   
					6" Combustion Air Terminal   
					90504113   
					90504112   
					91119100   
					90502102R   
					90502103   
					1 
					1 
					14   
					1 
					Model   
					UHAS 150 - 400   
					Model   
					UHAS 150 - 250   
					UHAS 300 - 400   
					Vent Diameter   
					4" (10 cm)   
					*Air Intake Diameter   
					4" (10 cm)   
					1 
					Description   
					Part Number   
					UHVK2   
					Qty.   
					5" (13 cm)   
					Concentric Vent Kit (300 - 400)   
					Concentric Vent Box Top & Side Assembly   
					Concentric Vent Box Bottom Assembly   
					Screw #6 x 3/8 Self Drilling   
					4" Vent Terminal with Baffle Plate   
					8" Combustion Air Terminal   
					90504013   
					90504012   
					91119100   
					90502102R   
					90502104   
					1 
					1 
					14   
					1 
					1 
					12   
					 
				SECTION 7: AIR SUPPLY   
					SECTION 7: AIR SUPPLY   
					7.1 Separated Combustion Installation   
					When installed as a separated combustion heater,   
					the air for combustion is drawn in from outside the   
					building. It is important to ensure that there is   
					adequate space around heater to provide air for the   
					axial air distribution fan.   
					7.2 Unvented Installation   
					It is important to ensure that there is adequate fresh   
					air supply at all times for both combustion and   
					heating requirements in accordance with local and   
					national codes.   
					WARNING: Combustion by-products contain a   
					chemical known to the State of California to cause   
					cancer and birth defects or other reproductive   
					harm.   
					7.3 Building Ventilation   
					Where ventilation is required, air must be taken from   
					an outside point where it is not likely to be   
					contaminated or obstructed.   
					7.4 Outside Combustion Air Supply   
					If outside combustion air supply is required,   
					separated combustion model (UHAS) heaters must   
					be used.   
					IMPORTANT: If the building has a slight negative   
					pressure or corrosive contaminants such as   
					halogenated hydrocarbons are present in the air, an   
					outside combustion air supply to the heater is   
					required. Seal all combustion air pipe joints.   
					The air supply duct may have to be insulated to   
					prevent condensation on the outer surface. The   
					outside air terminal must not be more than 1' (31   
					cm) above the vent terminal.   
					7.4.1 Length Requirements   
					
					13   
					 
					 
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					SECTION 8: GAS PIPING   
					• Meter and service must be large enough to   
					handle all the burners being installed plus any   
					other connected load. The gas pipe which feeds   
					the system must be large enough to supply the   
					required gas with a maximum pressure drop of   
					1/2" w.c. When gas piping is not included in the   
					layout drawing, contact the local gas supplier.   
					WARNING   
					• An isolating valve and union connection should   
					be used and fitted into the supply adjacent to the   
					heater.   
					Fire Hazard   
					Gas can leak if not installed properly.   
					• A minimum 1/8" NPT plugged tapping   
					accessible for test connection must be installed   
					immediately upstream of the gas supply   
					connection to the heater.   
					Failure to follow these instructions can result in death,   
					injury or porperty damage.   
					It is important that the gas supply pipe and the   
					electrical connections do not support any of the   
					heater’s weight.   
					A gas meter is connected to the service pipe by the   
					gas supply company. An existing meter should be   
					checked, preferably by the company, to ensure that   
					the meter is adequate for the rate of gas supply   
					required.   
					• For suspended heaters, an approved metal   
					flexible connection between the isolating valve   
					and the heater may be used. To reduce   
					pressure loss, use one pipe size larger than   
					the heater gas connection.   
					IMPORTANT - The complete installation must be   
					purged and tested for gas soundness in accordance   
					with local and national codes.   
					Installation pipes must be fitted in accordance with   
					local and national codes. Pipes of smaller size than   
					the heater inlet gas connection should not be used.   
					• Do not high pressure (in excess of 1/2 psi   
					[14" w.c.]) test the gas piping with the burner   
					connected. Close manual shut-off valve   
					during any pressure testing equal to or less   
					than 1/2 psi (14" w.c.). Failure to follow these   
					instructions can result in property damage.   
					Check the pipe and tubing ends for leaks before   
					placing heating equipment into service. When   
					checking for gas leaks, use a soap and water   
					solution; never use an open flame.   
					8.1 Connections   
					Connect the heater to the gas supply ensuring that   
					the final connections are as follows:   
					• Gas supply pipe work is run in medium or heavy   
					gauge tubing in compliance with local and   
					national codes.   
					Figure 9: Gas Connection   
					• Hold gas nipple   
					securely with pipe   
					wrench when   
					attaching the flex gas   
					connector.   
					Option A:   
					Stainless Steel   
					Do not bend flexible   
					Flex Gas   
					Connector   
					gas connector   
					sharply.   
					• Do not twist flexible   
					gas connector.   
					• Ensure all   
					joints are   
					gas tight.   
					Option B:   
					Medium or Heavy   
					Gauge Pipe   
					Gas Shut-off Valve   
					Gas Connector   
					Drip Leg   
					Cap   
					Union   
					Connection   
					14   
					 
					 
					 
				SECTION 9: WIRING   
					SECTION 9: WIRING   
					codes in accordance with: United States: refer to   
					National Electrical Code® ANSI/NFPA 70 - latest   
					revision Canada: refer to Canadian Electrical Code   
					CSA C22.1 Part I - latest revision.   
					WARNING   
					9.1 Positioning Thermostats   
					A room thermostat or ROBERTS GORDON®   
					control should be mounted on a vibration-free wall or   
					column at a height of approximately 5' (1.5 m) from   
					the floor to measure the ambient temperature. It   
					should be clear of both cold drafts and the direct   
					path of warm air from the heater.   
					Avoid mounting thermostat on outside walls or in   
					areas directly exposed to radiant heat or sunlight.   
					Install wall tag in a visible location near thermostat.   
					Electrical Shock Hazard   
					Disconnect electrical power and gas supply before   
					servicing.   
					This appliance must be connected to a properly   
					grounded electrical source.   
					Failure to follow these instructions can result in   
					death or electrical shock.   
					All heater models require constant 120 V 60 Hz 1Ø   
					power supply. Check heater(s) rating plate for   
					electrical rating for proper circuit sizing. For   
					servicing, a disconnect switch of proper electrical   
					rating should be installed in the vicinity of the heater.   
					9.1.1 Fan Control   
					The heater’s axial fan can be used during the off-   
					season for air circulation. A low voltage thermostat   
					with fan control must be used. See Page 15, Section   
					9.2 for thermostat connection details.   
					All heaters are equipped with thermostat   
					connections suitable to power a 24 V thermostat.   
					Heater must be wired and electrically grounded in   
					accordance with local codes. In the absence of local   
					9.2 Low Voltage Thermostat with One Heater   
					24 Volt   
					Thermostat   
					Heating Only   
					Terminal   
					Strip   
					R 
					G 
					R 
					W 
					C 
					W 
					Electrical   
					Supply   
					24 Volt   
					Thermostat   
					with Fan Control   
					Terminal   
					Strip   
					R 
					G 
					R 
					G 
					W 
					C 
					W 
					C 
					Electrical   
					Supply   
					15   
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					9.3 UHA(S) Series Internal Wiring Diagram   
					AXIAL FAN   
					AXIAL FAN (UH 300, 350, 400 ONLY)   
					BLACK   
					GREEN   
					WHITE   
					L2 L1   
					WHITE   
					BLACK   
					WHITE   
					GREEN   
					BLACK   
					BLOWER   
					BLACK   
					WHITE   
					GREEN   
					GREEN   
					GAS VALVE   
					3 
					1 
					BLACK   
					TRANSFORMER   
					BLUE   
					WHITE   
					GREEN   
					4 
					5 
					YELLOW   
					YELLOW   
					BLUE   
					BROWN   
					PRESSURE SWITCH   
					3 
					1 
					BLUE   
					2 
					5 
					6 
					4 
					ORANGE   
					ORANGE   
					R 
					G 
					W 
					C 
					LIMIT SWITCH   
					(UH 300, 350,   
					400 ONLY)   
					R = 24 VAC TO THERMOSTAT (RED)   
					G = MANUAL FAN INPUT FROM THERMOSTAT (GREEN)   
					ORANGE   
					ORANGE   
					W= HEAT DEMAND INPUT FROM THERMOSTAT (WHITE)   
					C = COMMON SIDE OF TRANSFORMER   
					LIMIT SWITCH   
					MANUAL RESET LIMIT SWITCH   
					(UH 30 - 125 ONLY)   
					IGNITION MODULE   
					THERMOSTAT INPUT: FIELD SUPPLIED   
					SENSE   
					ELECTRODE   
					BLACK   
					BLACK   
					BLACK   
					BLACK   
					ACC   
					CMB BLOWER   
					BLACK   
					L1   
					BLACK   
					NOTE:   
					For field wiring into service junction box, or if any of the original wire supplied with the heater   
					must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C   
					and 600 volts. For supply connections use No. 14 AWG or larger wires.   
					16   
					 
				SECTION 9: WIRING   
					9.4 UHA(S) Series Ladder Wiring Diagram   
					120 VAC   
					UH 300, 350, 400 Only   
					CIRCULATION FAN   
					CIRCULATION FAN   
					COMBUSTION BLOWER   
					TRANSFORMER   
					GAS VALVE   
					PRESSURE SWITCH   
					2 
					5 
					3 
					1 
					FLAME   
					SENSOR   
					6 
					4 
					FLAME   
					SPARK   
					IGNITION   
					MODULE   
					LIMIT SWITCH (UH 300, 350, 400 ONLY)   
					LIMIT SWITCH   
					ELECTRODE   
					MANUAL RESET LIMIT SWITCH   
					(UH 30 - 125 ONLY)   
					THERMOSTAT CONNECTION   
					NOTE:   
					For field wiring into service junction box, or if any of the original wire supplied with the heater   
					must be replaced, it must be replaced with wiring material having a temperature rating of at least 105°C   
					and 600 volts. For supply connections use No. 14 AWG or larger wires.   
					17   
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					9.5 Electrical Connection to the Heater   
					Flexible Conduit   
					BX Connector   
					Burner   
					L1   
					L2   
					Ground   
					Connect wires together   
					with suitable approved   
					wire connectors.   
					Junction Box   
					Green to Ground   
					White to L2   
					Black   
					White   
					Green   
					Black to L1   
					Note: Junction box is not provided with heater.   
					Conduit can also be attached directly to heater with wire junction made within the heater cabinet.   
					18   
					 
				SECTION 10: OPERATION AND MAINTENANCE   
					SECTION 10: OPERATION AND MAINTENANCE   
					Installation, service, and annual inspection of the   
					heater must be done by a contractor qualified in the   
					installation and service of gas-fired heating   
					10.1.2 Electrical Checks   
					All pre-start-up checks must be carried out before   
					start-up the heater.   
					equipment. Read this manual carefully before   
					installation, operation, or service of this equipment.   
					All components are accessed via the door secured   
					by 4 sheet metal screws. Opening the door exposes   
					live electrical connections and hot components.   
					1. Check that all site wiring is connected in   
					accordance with the appropriate wiring diagram   
					
					10.1.3 Gas Supply   
					All aspects of the gas installation including the gas   
					meter must be inspected, tested for gas tightness   
					and purged in accordance with local and national   
					codes.   
					WARNING   
					Ensure that the air is fully purged from the heater   
					inlet pipe up to the main gas valve inlet test nipple.   
					10.1.4 Mechanical Checks   
					1. Check that the fan is free to run and   
					delivery louvers are turned to give required   
					air deflection.   
					Electrical Shock Hazard   
					2. Check that the flue (and air intake for separated   
					combustion units) is installed in accordance   
					with these instructions and local regulations.   
					Use extreme caution during start-up.   
					Controls compartment contains live electrical   
					connections.   
					Failure to follow these instructions can result in   
					death or electrical shock.   
					10.2 Begin Start-Up   
					10.2.1 Before Operating the Heater   
					To ensure that all the controls are in safe working   
					order, operate the heater for the first time with the   
					isolating gas valve turned off and power supply   
					turned on.   
					10.1 Pre-Start-Up Checks   
					All pre-start-up checks must be carried out   
					before lighting the heater.   
					Ensure that the heater and all controls are suitable   
					for the gas, pressure and electrical supply to which   
					they are to be connected.   
					1. Turn off the isolating gas valve.   
					2. Turn up the thermostat above room   
					temperature. The automatic ignition   
					sequence will now begin as described   
					
					10.1.1 Louvers   
					Where fitted, the air delivery louvers need to be set   
					during start-up to give the required air distribution   
					(optional vertical louvers).   
					There will be no ignition of the burner and lockout   
					will occur, which proves the controls are operating   
					correctly.   
					WARNING   
					Cut Hazard   
					Turn off gas and electrical supply before maintenance.   
					Fan can start automatically at any time.   
					Failure to follow these instructions can result in severe   
					injury or product damage.   
					19   
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					Figure 10: Automatic Burner Control Sequence   
					Burner Sequence for Ignition Control   
					START   
					RUN   
					SHUT DOWN   
					Thermostat 24 V   
					Flue Fan   
					30 Sec. Purge*   
					NO   
					30 Sec. Post Purge   
					P 
					Pressure   
					Switch   
					C 
					NC   
					ts = 10 seconds   
					Ignition Spark   
					Start Gas Valve   
					Flame Signal   
					Axial Fan   
					30 Sec. Delay   
					90 Sec. Delay   
					*Purge time begins at pressure switch change over.   
					Required Incoming Signals   
					If at any stage the flame fails, the control will retry   
					for ignition. The control has four trials for ignition   
					before a one hour lockout.   
					Signals Output By Control   
					Figure 11: Gas Valve for Models UHA(S) 150 - 400   
					Top View   
					Regulator   
					End View   
					C 
					ON   
					OFF   
					Outlet   
					Gas Inlet   
					Pressure   
					Description   
					Part Number   
					Gas Valve 150 - 225 NG   
					Gas Valve 150 - 225 LP   
					Gas Valve 250 - 400 NG   
					Gas Valve 250 - 400 LP   
					90032505   
					90032506   
					90032520   
					90032521   
					Inlet Pressure   
					20   
					 
					 
				SECTION 10: OPERATION AND MAINTENANCE   
					10.2.2 Start-Up the Gas Valve (All Gases)   
					10.2.2.1 Check Burner Gas Pressure   
					1. Remove the plug in the outlet (burner) pressure   
					test point and connect a pressure tap and a   
					manometer.   
					10.2.5 External Controls   
					External controls may include time switch, interlock   
					switch, room thermostat and frost thermostat.   
					Operate each control to ensure that they function   
					correctly. Set the switches (if fitted) and   
					thermostat(s) to the users’ requirements.   
					2. With the burner firing, measure the pressure on   
					the manometer. To adjust the burner pressure,   
					remove the regulator cover from the valve and   
					turn the regulator adjustment screw to set the   
					required burner pressure as stated in the   
					Technical Data Tables for the correct gas and   
					
					10.3 Complete the Start-Up   
					Ensure that all covers are fitted correctly and all test   
					points are properly sealed.   
					10.3.1 Instruction to the User   
					Explain the controls of the heater to the user   
					including how to turn it on and off, using the controls   
					fitted on site.   
					Give this manual to the user.   
					Ensure that the user is shown and understands the   
					importance of maintaining clearances to   
					combustibles and the user instructions on Page 22,   
					
					warnings defined in this manual.   
					NOTE: If the correct burner pressure cannot be   
					reached, then check the inlet pressure to the valve   
					
					Page 38, Section 15.3 for inlet pressure   
					requirement.   
					Do not continue to adjust the regulator if the   
					pressure is not changing.   
					If the inlet pressure is too low to allow correct burner   
					pressure setting, then the gas inlet pressure must be   
					corrected before completing the commission.   
					Check Gas Rate   
					1. After burner pressure adjustment, allow the   
					heater to operate for at least 15 minutes and   
					then re-check settings. Adjust pressure setting   
					if necessary.   
					2. Check gas flow rate at gas meter.   
					3. Turn off heater and electrical supply.   
					4. Remove the manometer and refit all covers to   
					the valve and tighten the screw of the outlet   
					pressure tap.   
					10.2.3 Pressure Switch   
					The pressure switch is factory pre-set for each   
					model and is not adjustable.   
					10.2.4 Turning Off the Heater   
					Set the thermostat to the "OFF" position or lowest   
					setting and the main burner will stop.   
					The fan will run until it is stopped automatically by   
					the fan thermostat.   
					Do not use a disconnect switch for control of   
					heater. Disconnect switch will turn off the fan.   
					Heat exchanger could be damaged. Warranty will   
					not cover damage to the heat exchanger if   
					operated improperly. Only use the disconnect   
					switch for turning off heater for service or during   
					off-season.   
					21   
					 
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					SECTION 11: USER INSTRUCTIONS   
					11.1 User Instructions   
					11.5 Simple Troubleshooting   
					The UHA(S) Series heaters are fully automatic and Some possible reasons for the heater not operating   
					operate from the external controls fitted on site.   
					are:   
					1. Gas supply not "ON".   
					2. Electricity supply not "ON".   
					WARNING   
					3. The time and/or temperature controls are not   
					"ON".   
					4. A limit switch may have operated. This may be   
					caused by an interruption of the electrical   
					supply, failure of the distribution fan or vent or   
					heat exchanger blockage.   
					Electrical Shock Hazard   
					If a temperature limit switch persistently trips, there   
					is a fault which must be investigated by a contractor   
					qualified in the installation and service of gas-fired   
					heating equipment.   
					Disconnect electrical power before servicing.   
					Failure to follow these instructions can result in   
					death or electrical shock.   
					11.2 Heater Operation   
					11.5.1 Simple Troubleshooting (Burner Faults)   
					When the heater has been switched on by the   
					thermostat installed on site, the main burner will   
					automatically turn on.   
					The burner control box will control the safe ignition   
					of the flame.   
					All heaters require a constant gas and electricity   
					supply which must not be interrupted during the   
					normal operation of this heater.   
					If the burner fails to ignite for any reason, it will retry   
					for ignition (4 trials total). After 4 unsuccessful   
					ignition trials, the control will put the heater into   
					lockout for 1 hour.   
					Lockout should not occur during normal operation of   
					the heater and indicates there is a fault condition   
					which must be corrected. There is an LED light on   
					the ignition control that flashes codes to assist in   
					
					codes.   
					11.3 Common User Controls   
					11.4 Lighting Instructions   
					Figure 12: LED Diagnostic Codes   
					11.4.1 To Turn On Heater   
					LED INDICATION FAULT MODE   
					1. Ensure that the electrical and gas supplies to   
					the heater are on. Check that the on site   
					controls are "ON".   
					Slow Flash   
					Fast Flash   
					2 Flashes   
					3 Flashes   
					4 Flashes   
					Normal Operation - No call for heat.   
					Normal Operation - Call for heat.   
					Ignition Lockout - No flame detected.   
					Airflow Fault - Pressure switch open or closed.   
					NOTE: The thermostat setting must be above the   
					ambient temperature for the heater to operate.   
					Temperature Limit or   
					Manual Reset Limit Switch Open   
					5 Flashes   
					Steady On   
					Flame Sense Error - Gas valve not energized.   
					Internal Control Failure   
					2. The automatic firing sequence will begin as   
					
					will now operate automatically under the control   
					of the on site controls.   
					11.4.2 To Turn the Heater Off   
					Set the thermostat to the "OFF" position.   
					The burner will turn off immediately.   
					The fan will continue to run for 90 seconds.   
					To restart, turn the thermostat above room   
					temperature.   
					22   
					 
					 
					 
					 
					 
					 
					 
				SECTION 11: USER INSTRUCTIONS   
					FOR YOUR SAFETY   
					If you smell gas:   
					1. Open windows.   
					2. DO NOT try to light any appliance.   
					3. DO NOT use electrical switches.   
					4. DO NOT use any telephone in   
					your building.   
					5. Leave the building.   
					6. Immediately call your local gas   
					supplier after leaving the building.   
					Follow the gas suppliers   
					instructions.   
					7. If you cannot reach your gas   
					supplier, call the Fire Department.   
					WARNING   
					Fire Hazard   
					Do not store or use petrol or other   
					flammable vapours and liquids in the   
					vicinity of this or any other appliance.   
					Some objects will catch fire or explode   
					when placed close to heater.   
					Failure to follow these instructions can   
					result in death, injury or property   
					damage.   
					23   
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					SECTION 12: SERVICING   
					12.1 Servicing Instructions   
					12.3 Fan/Motor Assembly Maintenance   
					After start-up, the heater will require maintenance to The main fan bearings are permanently sealed and   
					be carried out annually. If the heater is used in a   
					do not need lubrication. Before cleaning, turn off gas   
					dirty or dusty area, more frequent maintenance may and electrical supply. Remove the fan and use a   
					be necessary.   
					small brush or duster to clean the fan blades from   
					each side. Replace fan when done.   
					WARNING   
					12.4 Heat Exchanger Maintenance   
					The heat exchanger will remain clean unless a   
					problem has developed with combustion. Inspect the   
					heat exchanger. Look for signs of overheating at the   
					front tubes which may indicate burner over firing or   
					persistently low air flows.   
					Cut Hazard   
					12.5 Gas Valve Maintenance   
					Turn off gas and electrical supply before maintenance.   
					Fan can start automatically at any time.   
					No regular maintenance is required on this device.   
					
					
					Do not repair or disassemble gas valve.   
					Replace faulty gas valves with genuine   
					ROBERTS GORDON® replacement parts.   
					Failure to follow these instructions can result in severe   
					injury or product damage.   
					NOTE 1: After any maintenance or repair work,   
					always test fire the heater in accordance with the   
					
					
					are in working order before leaving the heater to   
					operate. Minor faults may be traced by using the   
					
					
					12.6 Combustion Fan   
					The combustion fan should not require   
					maintenance. However, if the air pressure switch is   
					causing burner lockout, then remove the combustion   
					fan from the vent box by unscrewing the three   
					screws at the mounting plate. Remove the four   
					screws attaching the mounting plate to the fan inlet   
					
					free to run and that the fan wheel is clean.   
					NOTE 2: Check all gas pipes and pipe joints to   
					ensure there are no cracks or gas leaks. Any cracks   
					in the pipes or pipe joints must be repaired.   
					12.7 Venting and Air Intake Pipe   
					Inspect all venting and air intake pipe. Ensure that   
					all seams are sealed and suspension points secure.   
					Repair suspension points if any part of the venting   
					or combustion air pipe is sagging. Check to make   
					sure any insulation is not missing or in poor   
					condition. Replace as necessary. Check all venting   
					and air intake components to ensure they are in   
					good condition, gas tight and corrosion-free.   
					NOTE 3: Inspect all suspended components and   
					hardware. Ensure that they are in good condition,   
					properly tightened, and corrosion free.   
					12.2 Burner Maintenance   
					1. Open the door and remove the burner compart-   
					
					2. Clean any deposits from the main burner which   
					may have formed in the injectors or venturi of   
					
					3. Remove the ignition electrode and flame probe.   
					Check condition of ignition electrode and flame   
					probe. Clean off any deposits which may have   
					been formed, check condition of ceramic   
					insulators. Replace as necessary.   
					24   
					 
					 
					 
					 
					 
					 
					 
					 
				SECTION 12: SERVICING   
					12.8 Maintenance Checklist   
					Installation Code and Annual Inspections: All   
					installations and service of ROBERTS GORDON®   
					equipment must be performed by a contractor   
					qualified in the installation and service equipment   
					sold and supplied by Roberts-Gordon and conform   
					to all requirements set forth in the ROBERTS   
					GORDON® manuals and all applicable   
					WARNING   
					governmental authorities pertaining to the   
					installation, service and operation of the equipment.   
					Explosion Hazard   
					Service and annual inspection must be done by a   
					contractor qualified in the installation and service of   
					gas-fired heating equipment or your gas supplier.   
					To help facilitate optimum performance and safety,   
					Roberts-Gordon recommends that a qualified   
					contractor annually inspect your ROBERTS   
					GORDON® equipment and perform service where   
					necessary, using only replacement parts sold and   
					Turn off gas and electrical supplies before performing   
					service or maintenance.   
					Failure to follow these instructions can result in death, supplied by Roberts-Gordon.   
					injury or property damage.   
					The Vicinity of the Heater Do not store or use flammable objects, liquids or vapors near the heater.   
					Immediately remove these items if they are present.   
					
					Vehicles and Other   
					Objects   
					Maintain the clearances to combustibles.   
					Do not hang anything from, or place anything on, the heater.   
					Make sure nothing is lodged in between the heat exchanger or in the louvers.   
					Immediately remove objects in violation of the clearances to combustibles.   
					
					Vent Pipe/Terminals   
					Venting must be intact. Using a flashlight, look for obstructions, cracks on the   
					pipe, gaps in the sealed areas or corrosion.   
					The area must be free of dirt and dust.   
					Remove any carbon deposits or scale using a wire brush.   
					If the vent terminal has a screen built in, remove any dirt, dust or deposits   
					from the screen.   
					
					Combustion Air Intake   
					Pipe   
					Intake pipe and inlet must be intact. Look for obstructions, cracks on the pipe,   
					gaps in the sealed areas or corrosion.   
					The area must be free of dirt and dust. Clean and reinstall as required.   
					Heat Exchanger   
					Make sure there are no cracks.   
					
					Make sure there is no sagging, bending or distortion.   
					Clean or replace as required.   
					Gas Line and Shut-off   
					Valves   
					
					25   
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					Burner Observation   
					Window   
					Make sure it is clean and free of cracks or holes.   
					Clean and replace as required.   
					Combustion Fan Scroll,   
					Wheel and Motor   
					Compressed air or a vacuum cleaner may be used to clean dust and dirt.   
					Inshot Burners and   
					Orifices   
					Clear of obstructions (even spider webs will cause problems).   
					Carefully remove any dust and debris from the burner.   
					Direct-Spark Igniter   
					Replace if there are cracked ceramics, excessive carbon residue, or erosion   
					of the electrode.   
					The electrode gap should be 1/8" (3.2 mm).   
					Thermostat   
					There should be no exposed wire or damage to the device or wiring.   
					
					Suspension Points   
					Make sure the heater is hanging securely.   
					Look for signs of wear on the suspension materials or ceiling.   
					
					Silicone Tubing   
					Gas Valve   
					Ensure tight, secure fit on all pressure fittings at pressure switch,   
					burner partition, and blower outlet.   
					Verify that cap covering pressure regulator adjustment screw is secure and   
					has not been tampered with.   
					Verify all wiring connections.   
					Condensate Drain   
					(when installed)   
					Flush drain and clear any obstructions.   
					26   
				SECTION 13: TROUBLESHOOTING   
					SECTION 13: TROUBLESHOOTING   
					13.1 General   
					WARNING   
					Explosion Hazard   
					Installation must be done by a registered installer/   
					contractor qualified in the installation and service of   
					gas-fired heating equipment or your gas supplier.   
					Failure to follow these instructions can result in death,   
					injury or property damage.   
					Start   
					Are gas & electrical   
					supplies on?   
					No   
					Turn on supplies.   
					Yes   
					Wait 10-15 minutes for limit   
					switch to cool. Does fan   
					stop running?   
					Does axial fan run   
					immediately upon supplying   
					power to heater?   
					Fan and limit switch are   
					operating normally.   
					Yes   
					Yes   
					No   
					Replace temperature   
					limit switch.   
					No   
					Burner has locked out due   
					to ignition failure. Use   
					Troubleshooting for Automatic   
					Ignition Burner Systems   
					section to test burner.   
					Is ignition control showing a   
					"2 flashes" led code?   
					Yes   
					No   
					No   
					Use Troubleshooting for   
					Combustion Fan section to   
					test fan.   
					Does the combustion   
					fan run?   
					Yes   
					With external controls (i.e.   
					thermostat) on, does the   
					burner continue through the   
					heating cycle?   
					The limit switch has   
					tripped. See Manual Reset   
					Limit Switch Figure.   
					Has burner Locked Out?   
					Yes   
					No   
					No   
					Replace limit switch.   
					No   
					Yes   
					Use Troubleshooting for   
					Automatic Ignition Burner   
					Systems section to test burner.   
					Ensure proper air flow   
					clearance for axial fan.   
					Open louvers slightly.   
					Replace axial fan if it does   
					not operate.   
					Yes   
					If problems persist, contact   
					Roberts-Gordon, LLC at   
					
					Heater Operating   
					TROUBLESHOOT ENDS.   
					No   
					27   
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					13.2 Troubleshooting For Automatic Ignition Burner Systems   
					WARNING   
					Start   
					Are gas & electrical   
					Turn on supplies.   
					Turn on controls.   
					No   
					No   
					supplies on?   
					Yes   
					Electrical Shock Hazard   
					Are external controls   
					(i.e. Thermostat) on?   
					Do not touch ignition components.   
					Voltage from ignition components is high.   
					Yes   
					Failure to follow these instructions can   
					Press in reset button on   
					manual reset limit switch   
					result in death or electrical shock.   
					Is ignition control showing   
					a "4 flashes" led code?   
					Yes   
					No   
					No   
					Is 120 V supply at fan   
					connections?   
					Does flue fan run?   
					Yes   
					Flue fan faulty; replace   
					No   
					Burner control faulty or wiring   
					connections faulty. Repair   
					or replace as necessary   
					Yes   
					Check for too much vent/air inlet duct. Check for blockage in   
					vent and combustion air circuit. Check for faulty air pressure   
					switch. Check pressure switch hoses for leaks or cracks.   
					Do not attempt to circumvent pressure switch circuit to   
					place unit in operation.See Pressure Switch section for details.   
					Does air pressure switch   
					change over?   
					No   
					Yes   
					Is ignition lead okay and   
					connected?   
					Ignition control faulty;   
					replace.   
					Wait 30 - 40 seconds.   
					No   
					No   
					Yes   
					Yes   
					No   
					Does ignition spark operate?   
					Is spark electrode okay?   
					See Ignition Control section.   
					Yes   
					Is the gas valve operating?   
					To test valve, See   
					Troubleshooting for Gas   
					Valves section.   
					Replace valve.   
					Does the flame light?   
					Yes   
					Trace fault in supervision   
					system. See   
					Troubleshooting   
					for Flame Supervision   
					System section.   
					Is the flame current at   
					least 1 µAmp DC when   
					the flame ignites?   
					Is ignition control showing   
					a "2 flashes" led code?   
					Yes   
					No   
					If problems persist, contact   
					Roberts-Gordon, LLC at   
					
					Heater Operating   
					TROUBLESHOOT ENDS.   
					No   
					For your safety and optimum heater performance,   
					use only ROBERTS GORDON® replacement parts.   
					Conduct start-up procedure as shown on Page   
					
					28   
					 
				SECTION 13: TROUBLESHOOTING   
					13.3 Troubleshooting for Flame Supervision System   
					To measure flame current, connect a 0 - 50 μA DC meter in   
					series with the flame probe. If the meter reads negative   
					values, then reverse the test leads.   
					START   
					Connect a DC ammeter in   
					series with the flame probe.   
					Use General   
					Troubleshooting section to   
					trace the fault.   
					Is the flame present and   
					at least 1 µA DC flame   
					current?   
					No   
					Yes   
					Yes   
					Yes   
					Is the connecting lead   
					damaged? Is the flame probe   
					damaged or touching earthed   
					components?   
					Is there a current flowing in the   
					flame probe circuit with no   
					flame present?   
					Repair or replace as   
					necessary.   
					Yes   
					No   
					Is inlet burner gas pressure   
					correct? Is live and neutral   
					polarity correct? Is   
					Does lockout occur when   
					there is a flame present?   
					Yes Replace ignition control.   
					flame probe circuit correct?   
					No   
					Repair or replace as   
					necessary.   
					No   
					If problems persist, contact   
					Roberts-Gordon, LLC at   
					
					Heater Operating   
					TROUBLESHOOT ENDS.   
					No   
					NOTE: Minimum flame probe current 1 μA DC. Typical flame probe current 3-5 μA DC.   
					29   
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					13.4 Troubleshooting for Gas Valves   
					START   
					Is gas pressure at inlet of the   
					valve correct for gas type?   
					Note pressure found.   
					Fault elsewhere.   
					No   
					No   
					Correct pressure problem.   
					Yes   
					Valve or ignition control   
					faulty. Replace with   
					one of correct type.   
					Does gas pressure at outlet   
					of the valve rise when   
					valve turns on?   
					Yes   
					Does gas pressure at   
					outlet of valve return to zero or   
					lower when valve turns off?   
					Valve faulty.   
					Replace with one of   
					correct type.   
					No   
					No   
					Yes   
					If problems persist, contact   
					Roberts-Gordon, LLC at   
					
					Valve Operating   
					TROUBLESHOOT ENDS.   
					13.5 Troubleshooting for Combustion Fan   
					START   
					Does combustion fan run   
					automatically when there   
					is a call for heat?   
					Correct power   
					supply problem.   
					No   
					Yes   
					Fan motor faulty.   
					Replace with correct type.   
					Yes   
					Does fan turn on and   
					off while burner is firing   
					continously?   
					Check fan motor leads for   
					loose connections.   
					Yes   
					No   
					If problems persist, contact   
					Roberts-Gordon, LLC at   
					
					Fan Operating   
					TROUBLESHOOT ENDS.   
					No   
					For your safety and optimum heater performance,   
					use only genuine ROBERTS GORDON® replacement parts.   
					
					30   
					 
					 
				SECTION 14: REPLACEMENT PARTS   
					SECTION 14: REPLACEMENT PARTS   
					See warnings and notes on Page 24, Section 12   
					before removing or replacing parts.   
					Burner Components   
					All serviceable burner parts are accessed by the   
					door on the side of the heater. Remove the   
					sheetmetal screws.   
					14.1 Gas Valve   
					Remove the gas supply pipe at the heater inlet.   
					C 
					ON   
					OFF   
					Description   
					Part Number   
					Gas Valve, NG (Models UHA[S] 150 - 225)   
					Gas Valve, LP (Models UHA[S] 150 - 225)   
					Gas Valve, NG (Models UHA[S] 250 - 400)   
					Gas Valve, LP (Models UHA[S] 250 - 400)   
					90032505   
					90032506   
					90032520   
					90032521   
					
					remove gas valve/manifold.   
					Replace in reverse order. Verify that the gas flow   
					direction of the valve is correct. Use a minimum   
					amount of gas seal on the thread joint. Check that   
					all the joints are leak free. Reset gas valve. See   
					
					IT IS IMPORTANT THAT ONLY THE CORRECT   
					GAS VALVE IS USED WHEN REPLACING THESE   
					CONTROLS.   
					31   
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					14.2 Burner Compartment   
					The burner compartment is   
					a sealed compartment.   
					Following any work,   
					Burner   
					compartment   
					cover   
					re-seal the compartment   
					with the gas pipe rubber   
					seal fully in place and all   
					screws fitted and tight.   
					Flame probe   
					Viewing port   
					for flame probe   
					Remove flexible   
					air duct from spigot   
					Ignition electrode   
					Viewing port   
					for ignition electrode   
					Remove   
					access plate   
					Rubber Seal   
					Remove screws and   
					pull off burner cover   
					14.2.1 Burner Injectors   
					Ensure gas tight fitting of injectors.   
					Ensure correct alignment with burners.   
					Ensure all pipe joints are gas tight.   
					Manifold   
					Burners   
					Injectors   
					Remove manifold   
					screws and pull   
					out manifold   
					Manifold   
					Unscrew   
					Injectors   
					Burner   
					Screws   
					Marking   
					Folded   
					Hem   
					UHA[S]   
					150   
					UHA[S]   
					175   
					UHA[S]   
					200   
					UHA[S]   
					225   
					UHA[S]   
					250   
					UHA[S]   
					300   
					UHA[S]   
					350   
					UHA[S]   
					400   
					Orifice Quantity   
					Natural Gas (G20)   
					Orifice Marking   
					7 
					8 
					9 
					10   
					11   
					12   
					14   
					14   
					43   
					43   
					2.25 mm   
					2.25 mm   
					2.25 mm   
					40   
					40   
					40   
					RG P/N   
					91930043   
					91930043   
					91930225   
					91930225   
					91930225   
					91930040   
					91930040   
					91930040   
					Propane (G31)   
					Orifice Marking   
					RG P/N   
					1.35 mm   
					1. 35 mm   
					54   
					54   
					54   
					1.45 mm   
					53   
					53   
					91930135   
					91930135   
					91930054   
					91930054   
					91930054   
					91930145   
					91930053   
					91930053   
					32   
					 
					 
				SECTION 14: REPLACEMENT PARTS   
					14.3 Ignition Electrode and Flame Probe   
					Burners   
					Limit   
					Thermostat   
					Flame   
					Probe   
					Flame   
					Probe   
					Remove all   
					burner compartment   
					screws to remove   
					the burner   
					Remove   
					Screw   
					compartment and   
					access the   
					"Front View".   
					Burner Compartment   
					Front Views   
					Ignition   
					Electrode   
					Ignition   
					Electrode   
					.120   
					(3 mm)   
					spark   
					gap   
					Burners   
					To replace the electrode or flame probe, remove the electrical lead and screw.   
					Pull out from mounting. Refit in reverse ensuring that the gap to burner is as shown in the   
					front view of the burner compartment.   
					Description   
					Spark Electrode   
					Part Number   
					90427411   
					90439300   
					92000001   
					92000002   
					90412103   
					90412105   
					Qty.   
					1 
					1 
					1 
					1 
					Automatic Ignition Flame Probe   
					Inshot Burners (150, 175)   
					Inshot Burners (200 - 400)   
					Limit Switch (150 - 400)   
					Limit Switch (300 - 400)   
					1 
					2 
					33   
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					14.4 Combustion Fan Vertical Installation   
					Remove screws securing outlet   
					flange to the flue adapter.   
					Rear Panel   
					Flue Adapter   
					to Flue Fan   
					screws   
					Hole   
					Refit in reverse order.   
					Vent Box   
					Flue   
					Adapter   
					Vent Box   
					Screws   
					Outlet   
					Gasket   
					Flue Fan   
					Disconnect   
					electrical connections   
					at plug in tabs.   
					Remove screws securing flue   
					fan mounting plate to vent box.   
					Remove screws securing   
					mounting plate to fan.   
					Vent Box   
					Mounting   
					Plate   
					Refit in reverse.   
					Mounting Plate   
					to Vent Box   
					Screws   
					Use new gaskets.   
					Ensure sealed joints.   
					Ensure mounting plate orifice is   
					clear and not obstructed.   
					Gasket   
					Gasket   
					Mounting Plate   
					to Flue Fan   
					Screws   
					Air Plate   
					UHA[S]   
					150 - 175   
					UHA[S]   
					200 - 300   
					UHA[S]   
					350 - 400   
					Exhaust Fan P/N   
					90710405   
					90710403   
					90710402   
					IT IS IMPORTANT THAT ONLY THE CORRECT COMBUSTION FAN SPECIFIED FOR EACH MODEL   
					TYPE IS USED WHEN REPLACING THESE ITEMS.   
					
					34   
					 
				SECTION 14: REPLACEMENT PARTS   
					14.5 Pressure Switch   
					Pull off 3 way connector. Spring open plastic clips of   
					mounting cradle. Replace with correct type of   
					pressure switch for model. The pressure switches   
					are color coded for each pressure setting.   
					WARNING   
					Carbon Monoxide Hazard   
					Use correct pressure switch specified for each model.   
					Use of incorrect pressure switch or disabling   
					pressure switch circuit could cause unsafe condition.   
					Failure to follow these instructions can result in   
					death or serious injury.   
					Carry out a commission after working on or   
					changing a pressure switch. See Page 19, Section   
					
					UHA[S]   
					UHA[S]   
					UHA[S]   
					250   
					UHA[S]   
					UHA[S]   
					400   
					P/N   
					150 - 175   
					200 - 225   
					300 - 350   
					90439802   
					yellow   
					.32   
					90439808   
					orange   
					.79   
					90439803   
					gray   
					90439807   
					brown   
					.68   
					90439808   
					orange   
					.79   
					Color Code   
					Set Point in. w.c.   
					.41   
					35   
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					14.6 Ignition Control   
					14.8 Limit Switches   
					The control mounts to the electrical plate. Pull out   
					ignition cable and wiring from board, noting their   
					positions.   
					Release the four mounting standoffs.   
					Refit in reverse. Ensure correct location of ignition   
					cable and all other wiring.   
					14.8.1 Removal and Replacement   
					1. Remove the electrical connections to the   
					switch.   
					2. Unscrew the two screws securing the   
					switch.   
					3. Fit a new switch with two screws.   
					
					14.7 Axial Fan/Guard/Motor Assembly   
					The axial fan unit for the heater is supplied   
					completely assembled and balanced.   
					4. Reconnect the electrical connections and test   
					operation.   
					14.7.1 Fan Removal and Replacement   
					Remove the mounting hardware.   
					Description   
					Part Number   
					Qty.   
					1 
					1 
					Axial Fan UHA[S] 150 - 175   
					Axial Fan UHA[S] 200 - 250   
					Axial Fan UHA[S] 300 - 400   
					90710416   
					90710417   
					90710416   
					2 
					14.7.2 To Replace the Fan Assembly   
					To replace the fan assembly, reverse the procedure   
					shown above.   
					• Check that the fan blades are free to rotate   
					before turning on the power to the fan.   
					• Strictly comply with the color code of the fan   
					wires to ensure correct operation. See Page 16,   
					Section 9.3 wiring diagram.   
					• Use only genuine ROBERTS GORDON®   
					replacement parts.   
					36   
					 
					 
					 
				SECTION 15: SPECIFICATIONS   
					SECTION 15: SPECIFICATIONS   
					15.1 Standard (Models 150 - 400) UHA(S) Series Dimension Data   
					Top View   
					Heater must be supported   
					at these points from above   
					or below.   
					C 
					E 
					D 
					77   
					Support   
					Centers   
					4 x 3/8" Captive Nuts Provided   
					19 3/8"   
					(49 cm)   
					End View   
					25 1/2" (65 cm)   
					I 
					Z 
					Rear View   
					Air Intake   
					(UHAS only)   
					F 
					G 
					B 
					H 
					Flue   
					Lockout Reset   
					Electrical   
					Cable Entry   
					Gas   
					Supply   
					6 1/2"   
					(17 cm)   
					A 
					UHA[S] UHA[S]] UHA[S]   
					UHA[S]   
					225   
					UHA[S]   
					250   
					UHA[S]   
					300   
					UHA[S]   
					350   
					UHA[S]   
					400   
					Model   
					150   
					175   
					200   
					in   
					(cm)   
					in   
					(cm)   
					in   
					(cm)   
					in   
					(cm)   
					in   
					(cm)   
					in   
					(cm)   
					42.4   
					(108)   
					26.9   
					(68)   
					17.7   
					(45)   
					12.3   
					(31)   
					12.4   
					(32)   
					15.5   
					(39)   
					42.4   
					(108)   
					26.9   
					(68)   
					17.7   
					(45)   
					12.3   
					(31)   
					12.4   
					(32)   
					15.5   
					(39)   
					42.4   
					(108)   
					35.2   
					(89)   
					17.7   
					(45)   
					12.3   
					(31)   
					12.4   
					(32)   
					17.5   
					(44)   
					42.4   
					(108)   
					35.2   
					(89)   
					17.7   
					(45)   
					12.3   
					(31)   
					12.4   
					(32)   
					17.5   
					(44)   
					42.4   
					(108)   
					35.2   
					(89)   
					17.7   
					(45)   
					12.3   
					(31)   
					12.4   
					(32)   
					17.5   
					(44)   
					52.3   
					(133)   
					43.5   
					(110)   
					24.7   
					(63)   
					12.3   
					(31)   
					15.3   
					(39)   
					13.8   
					(35)   
					52.3   
					(133)   
					43.5   
					(110)   
					24.7   
					(63)   
					12.3   
					(31)   
					15.3   
					(39)   
					13.8   
					(35)   
					52.3   
					(133)   
					43.5   
					(110)   
					24.7   
					(63)   
					12.3   
					(31)   
					15.3   
					(39)   
					13.8   
					(35)   
					A 
					B 
					C 
					D 
					E 
					F 
					G 
					H 
					I 
					Width   
					Height   
					Support Spacing   
					Support Spacing   
					Support Spacing   
					Centre of Flue   
					Centre of   
					Flue/Air Intake   
					in   
					(cm)   
					5.5   
					(14)   
					5.5   
					(14)   
					6.4   
					(16)   
					6.4   
					(16)   
					6.4   
					(16)   
					7 
					(18)   
					7 
					(18)   
					7 
					(18)   
					in   
					(cm)   
					in   
					(cm)   
					in   
					(cm)   
					8.2   
					(21)   
					5.8   
					(15)   
					34   
					(86)   
					8.2   
					(21)   
					5.8   
					(15)   
					34   
					(86)   
					8.8   
					(22)   
					5.8   
					(15)   
					34   
					(86)   
					8.8   
					(22)   
					5.8   
					(15)   
					34   
					(86)   
					8.8   
					(22)   
					5.8   
					(15)   
					34   
					(86)   
					11   
					(28)   
					5.8   
					(15)   
					34   
					(86)   
					11   
					(28)   
					5.8   
					(15)   
					34   
					(86)   
					11   
					(28)   
					5.8   
					(15)   
					34   
					(86)   
					Position of Flue   
					Gas Inlet Position   
					Length   
					Z 
					37   
					 
					 
				COMBAT® UHA UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL   
					15.2 General Technical Data Table (All Models)   
					UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S]   
					150   
					175   
					200   
					10.6   
					3716   
					225   
					10.6   
					3716   
					250   
					10.6   
					3716   
					300   
					350   
					400   
					Full Load Amps @ 115 V   
					Air Volume   
					A 
					5.8   
					5.8   
					11.6   
					11.6   
					11.6   
					CFM   
					2245   
					2245   
					4663   
					4663   
					4663   
					Flue and AIr Intake   
					Flue Intake Size   
					Air Intake Size   
					in (cm) 4 (10)   
					in (cm) 4 (10)   
					4 (10)   
					4 (10)   
					40 (1)   
					4 (10)   
					4 (10)   
					40 (1)   
					4 (10)   
					4 (10)   
					40 (1)   
					4 (10)   
					4 (10)   
					40 (1)   
					4 (10)   
					5 (13)   
					40 (1)   
					4 (10)   
					5 (13)   
					40 (1)   
					4 (10)   
					5 (13)   
					40 (1)   
					*Maximum Straight Flue/Air Intake ft (m)   
					40 (1)   
					*Do not exceed the maximum length of flue stated or heater may not operate properly.   
					15.3 Technical Data Table (All Models)   
					UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S] UHA[S]   
					150   
					150   
					123   
					82   
					175   
					200   
					200   
					164   
					82   
					225   
					225   
					184.5   
					82   
					250   
					250   
					205   
					82   
					300   
					300   
					246   
					82   
					350   
					350   
					287   
					82   
					400   
					385   
					315.7   
					82   
					Total Input   
					Total Output   
					Efficiency   
					(Btu/h) x (1000)   
					(Btu/h) x (1000)   
					% 
					175   
					143.5   
					82   
					Natural Gas (G20) Data - Inlet Pressure 5.0 in w.c. Min., 14 in w.c. Max.   
					Burner Pressure in. w.c. 3.2 3.4 3.7   
					3.7   
					4.0   
					2.7   
					9.4   
					2.5   
					9.3   
					3.3   
					LPG / Propane (G31) Data - Inlet Pressure Inlet Pressure 12.0 in w.c. Min., 14 in w.c. Max.   
					Burner Pressure in. w.c. 9.9 10.4 10.5 10.7 10.7   
					11.1   
					38   
					 
					 
				SECTION 16: THE ROBERTS GORDON® COMBAT® UHA-SE-   
					SECTION 16: THE ROBERTS GORDON®   
					COMBAT® UHA-SERIES WARRANTY   
					ROBERTS-GORDON WILL PAY FOR:   
					Within 24 months from date of purchase by buyer or 27   
					months from date of shipment by Roberts-Gordon   
					(whichever comes first), replacement parts will be   
					provided free of charge for any part of the product which   
					fails due to a manufacturing or material defect.   
					The data plate and/or serial number are removed,   
					defaced, modified or altered in any way.   
					The ownership of the ROBERTS GORDON® COMBAT®   
					UHA-Series is moved or transferred. This warranty is   
					nontransferable.   
					Roberts-Gordon is not permitted to inspect the damaged   
					controller and/or component parts.   
					READ YOUR INSTALLATION, OPERATION AND   
					SERVICE MANUAL   
					If you have questions about your controller, contact your   
					installing professional. Should you need Replacement   
					Parts or have additional questions, call or write Roberts-   
					Gordon:   
					U.S.A.   
					1250 William Street   
					P. O. B ox 4 4   
					Roberts-Gordon will require the part in question to be   
					returned to the factory. Roberts-Gordon will, at its sole   
					discretion, repair or replace after determining the nature   
					of the defect and disposition of part in question.   
					ROBERTS GORDON® Replacement Parts are warranted   
					for a period of 18 months from date of shipment from   
					Roberts-Gordon or the remaining ROBERTS GORDON®   
					COMBAT® UHA-Series warranty.   
					Buffalo, New York 14240-0044   
					716.852.4400   
					On the web at: www.rg-inc.com   
					ROBERTS-GORDON WILL NOT PAY FOR:   
					Service trips, service calls and labor charges.   
					Shipment of replacement parts.   
					Roberts-Gordon's liability, and your exclusive   
					remedy, under this warranty or any implied warranty   
					(including the implied warranties of merchantability   
					and fitness for a particular purpose) is limited to   
					providing replacement parts during the term of this   
					warranty. Some jurisdictions do not allow limitations on   
					how long an implied warranty lasts, so this limitation may   
					not apply to you. There are no rights, warranties or   
					conditions, expressed or implied, statutory or otherwise,   
					other than those contained in this warranty.   
					Claims where the total price of the goods have not   
					been paid.   
					Damage due to:   
					• Improper installation, operation or maintenance.   
					• Misuse, abuse, neglect, or modification of the   
					ROBERTS GORDON® COMBAT® UHA-Series in any   
					way.   
					• Use of the ROBERTS GORDON® COMBAT® UHA-   
					Series for other than its intended purpose.   
					Roberts-Gordon shall in no event be responsible for   
					incidental or consequential damages or incur liability   
					for damages in excess of the amount paid by you for   
					the ROBERTS GORDON® COMBAT® UHA-Series.   
					Some jurisdictions do not allow the exclusion or limitation   
					of incidental or consequential damages, so this limitation   
					or exclusion may not apply to you. This warranty gives   
					you specific legal rights, and you may also have other   
					rights which vary from jurisdiction to jurisdiction.   
					• Incorrect gas or electrical supply, accident, fire, floods,   
					acts of God, war, terrorism, or other casualty.   
					• Improper service, use of replacement parts or   
					accessories not specified by Roberts-Gordon.   
					• Failure to install or maintain the ROBERTS   
					GORDON® COMBAT® UHA-Series as directed in the   
					Installation, Operation and Service manual.   
					• Relocation of the ROBERTS GORDON® COMBAT®   
					UHA-Series after initial installation   
					• The use of the ROBERTS GORDON® COMBAT®   
					UHA-Series in a corrosive atmosphere containing   
					contaminants.   
					• The use of the ROBERTS GORDON® COMBAT®   
					UHA-Series in the vicinity of a combustible or   
					explosive material.   
					• Any defect in the ROBERTS GORDON® COMBAT®   
					UHA-Series arising from a drawing, design, or   
					specification supplied by or on behalf of the   
					consumer.   
					• Damage incurred during shipment. Claim must be   
					filed with carrier.   
					Roberts-Gordon shall not be responsible for failure to   
					perform under the terms of this warranty if caused by   
					circumstances out of its control, including but not limited   
					to war, fire, flood, strike, government or court orders, acts   
					of God, terrorism, unavailability of supplies, parts or   
					power. No person is authorized to assume for Roberts-   
					Gordon any other warranty, obligation or liability.   
					LIMITATIONS ON AUTHORITY OF   
					REPRESENTATIVES:   
					No representative of Roberts-Gordon, other than an   
					Executive Officer, has authority to change or extend these   
					provisions. Changes or extensions shall be binding only if   
					confirmed in writing by Roberts-Gordon's duly authorized   
					Executive Officer.   
					WARRANTY IS VOID IF:   
					The ROBERTS GORDON® COMBAT® UHA-Series is not   
					installed by an electrician qualified in the installation and   
					service of control systems for heating equipment.   
					You cannot prove original purchase date and required   
					annual maintenance history.   
					39   
					 
				Attach this information to the wall near the ROBERTS GORDON® heater   
					® 
					Read the Installation, Operation and Service Manual thoroughly before installation, operation or service.   
					OPERATING INSTRUCTIONS   
					WARNING   
					1. STOP! Read all safety instructions on this information sheet.   
					2. Open the manual gas valve in the heater supply line.   
					3. Turn on electric power to the heater.   
					4. Set the thermostat to desired setting (above ambient temperature).   
					The automatic starting sequence begins.   
					TO TURN OFF THE HEATER   
					1. Turn the thermostat/time switch to 'OFF' or lowest setting. The burner   
					will turn 'OFF' immediately, but fans will continue to cool heat exchanger   
					until the fan thermostat switches off.   
					Fire Hazard   
					Some objects can catch fire or explode when placed   
					IF THE HEATER WILL NOT OPERATE, TO ENSURE YOUR SAFETY,   
					close to heater.   
					FOLLOW THESE INSTRUCTIONS TO SHUT DOWN YOUR HEATER   
					Keep all flammable objects, liquids and vapors the   
					required clearances to combustibles away from heater.   
					1. Set the thermostat to off or the lowest setting.   
					2. Turn off electric power to the heater.   
					3. Turn off the manual gas valve in the heater supply line.   
					Failure to follow these instructions can result in death,   
					injury or property damage.   
					4. Call your installer/contractor qualified in the installation and service   
					of gas-fired heating equipment.   
					Installation Clearances   
					Clearances to Combustibles   
					Roof Terminal   
					Top   
					Top   
					(Optional separated   
					combustion concentric   
					venting shown.)   
					Left   
					Left   
					Right   
					Right   
					Top*   
					10'   
					(3 m)   
					Bottom   
					Bottom   
					Wall   
					Terminal   
					Rear*   
					Max. Mounting Height*   
					Models 30 - 125   
					Models 150 - 400   
					150 - 400   
					6" (15 cm)   
					3" (8 cm)   
					31" (79 cm)*   
					6" (15 cm)   
					2" (5 cm)   
					30 - 125   
					1" (2.5 cm)   
					0" (0 cm)   
					1" (2.5 cm)   
					18" (46 cm)*   
					2" (5 cm)   
					Models   
					Top   
					Bottom   
					Right   
					Left   
					30 - 125   
					1" (2.5 cm)   
					18" (46 cm)   
					*Models   
					Top   
					150 - 400   
					6" (15 cm)   
					24" (61 cm)   
					Rear   
					Max Mounting Height1   
					12' (3.7 m) - 20' (6 m)   
					20' (6 m) - 30' (9 m)   
					1Heaters can be mounted higher if destratification fans are installed. See Installation, Operation   
					and Service Manual for specific mounting height recommendations.   
					NOTE: Venting directly from top of heater not applicable on Models 150-400.   
					Vent   
					* Clearance needed for servicing.   
					Roberts-Gordon, LLC   
					Telephone: 716.852.4400   
					Fax: 716.852.0854   
					Toll Free: 800.828.7450   
					1250 William Street   
					P.O. Box 44   
					Buffalo, NY 14240-0044 USA   
					Installation Code and Annual Inspections:   
					All installations and service of ROBERTS GORDON® equipment must be performed by a contractor qualified in the installation and service of equipment sold and supplied by Roberts-Gordon and   
					conform to all requirements set forth in the ROBERTS GORDON® manuals and all applicable governmental authorities pertaining to the installation, service and operation of the equipment. To help   
					facilitate optimum performance and safety, Roberts-Gordon recommends that a qualified contractor annually inspect your ROBERTS GORDON® equipment and perform service where necessary,   
					using only replacement parts sold and supplied by Roberts-Gordon.   
					For installations at elevations above 2000' (610 m), the appliance shall be derated 4% for each 1000' (305 m) of elevation above sea level.   
					Further Information:Applications, engineering and detailed guidance on systems design, installation and equipment performance is available through ROBERTS GORDON® representatives. Please   
					contact us for any further information you may require, including the Installation, Operation and Service Manual.   
					Models 100-400 are not for residential use.   
					© 2007 Roberts-Gordon, LLC   
					
					Printed in U.S.A.   
					P/N 91040031 Rev B   
				 |