DESCRIPTION
YORK Sunline 2000™ units are convertible single package
air conditioners with a common cabinet and a common roof
curb for the 3, 4, 5 and 6 ton sizes. The units were designed
for light commercial and commercial applications. They can
easily be installed on a roof curb, slab, roof jack or frame.
TECHNICAL GUIDE
All units include:
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
•
Powder Paint finish that meets ASTM-B-117 750 hour
salt spray standards
•
•
Permanently lubricated motors
AIR CONDITIONERS
Bottom or side air discharge configuration capability
(field convertible)
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
•
Manufactured under the quality standards of ISO9001
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)
TM
•
•
•
•
•
•
•
•
Control Board
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in base rails for lifting
Fork lift slots on three sides
Single point power connection
Complete factory package - tested, charged and wired
CSA agency listing on all units
WARRANTY
•
•
•
Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21502-002-A-0303
PRODUCT NOMENCLATURE
3-6 Ton Sunline Model Number Nomenclature
D M 048 N04 A 2 A AA 1
Product Generation
Product Catagory
1 = First Generation
D = Air Cond., Single Package
B = Heat Pump, Single Package
Voltage
Product Identifier
1 = 208/230-1-60
M = R-22 Standard Efficiency (DCG/DCE)
F = R-22 Medium Efficiency (DEG/DEE)
H = R-22 High Efficiency (DHG/DHE)
Q = R-22 Std. Effic Heat Pump (BCH)
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Nominal Cooling
Capacity - MBH
Installation Options
Additional Options
(See Next Page)
A = No Options Installed
B = Option 1
C = Option 2
036 = 3 Ton
048 = 4 Ton
060 = 5 Ton
072 = 6 Ton
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel (036)
N06 = 60 MBH Output Aluminized Steel (048)
N08 = 79 MBH Output Aluminized Steel (036,060,072)
N10 = 99 MBH Output Aluminized Steel (048,060,072)
S04 = 40 MBH Output Stainless Steel (036)
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4, & 5
S06 = 60 MBH Output Stainless Steel (048)
S08 = 79 MBH Output Stainless Steel (036,060,072)
S10 = 99 MBH Output Stainless Steel (048,060,072)
Electric Heat Options
E05 = 5 kW Electric Heat
E07 = 7 kW Electric Heat
E10 = 10 kW Electric Heat
E15 = 15 kW Electric Heat
E20 = 20 kW Electric Heat
E30 = 30 kW Electric Heat
Options
1 = Disconnect
2 = Non-Pwr'd Conv Oultet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Airflow
A= Direct Drive
B = Direct Drive/Single Input Econo
D = Direct Drive/Motorized Damper
L = Direct Drive/BAS Ready Econ (No BAS Controller)/2" Pleated Filters/Extra xfrmr & circuit bkr.
N = Belt Drive
P = Belt Drive/Single Input Econo
R = Belt Drive/Motorized Damper
Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Unitary Products Group
3
036-21502-002-A-0303
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Additional Options
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
AS Bottom Condensate Pan
BA Hinged Filter Door & Toolless Access Panels
BB Phase Monitor, Hinged Filter Door & Toolless Access Panels
BC Coil Guard, Hinged Filter Door & Toolless Access Panels
BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BE Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
BF Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DJ CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
DK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
4
Unitary Products Group
036-21502-002-A-0303
Additional Options
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Unitary Products Group
5
036-21502-002-A-0303
Additional Options
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
PK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
6
Unitary Products Group
036-21502-002-A-0303
Additional Options
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
7
036-21502-002-A-0303
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
•
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for over-
head rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizon-
tal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
All units have long lasting powder paint cabinets with 750
hour salt spray test approval under ASTM-B117 procedures.
•
•
Single enthalpy economizer
Motorized outdoor air damper
All models are CSA listed.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact require-
ments of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system compo-
nents.
•
Gas Heat Operation - All gas heat units have a mini-
mum AFUE of 80%. Each section includes a durable
heat exchanger with aluminized steel or optional stain-
less steel tubes, a redundant gas valve, spark ignition,
power venting, an ignition module for 100% shut-off and
all of the safety controls required to meet the latest ANSI
standards.
•
™ Controls -
™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
the unit.
•
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uni-
form distribution of air across the heating elements.
Every element is fully protected against excessive tem-
perature by thermal limit switches.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
•
BAS Controls - York’s Sunline™ series units offer fac-
tory mounted BAS controls such as Novar, Honeywell,
Johnson, and CPC.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
8
Unitary Products Group
036-21502-002-A-0303
FIGURE 1: UNIT CUTAWAY
•
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
•
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
•
•
BAS - See “Additional Options” section in the product
nomenclature.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
TM
Technicoat 10-1 processes. Coating is applied by total
immersion of the complete coil for maximum protection.
Unitary Products Group
9
036-21502-002-A-0303
•
•
•
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•
•
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
•
LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the condi-
tioned space from being over-pressurized during econo-
mizer operation.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
The power exhaust option can only be used on bot-
tom duct configurations.
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
•
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
•
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
•
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
•
CO SENSOR - Senses CO levels and automatically
2
2
overrides the economizer when levels rise above the
present limits.
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the fin-
ished roof. These full perimeter curbs meet the require-
ments of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assem-
bly.
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
10
Unitary Products Group
036-21502-002-A-0303
1
TABLE 1: SOUND POWER RATING
-12
SOUND POWER (db 10
Watts)
ESP
BLOWER
UNIT
SIZE
Octave Band Centerline Frequency (Hz)
dB(A)
@
10Ft.2
CFM
SWL
dB(A)
IWG SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
036
048
060
072
1,200
1,600
2,000
2,200
0.6
0.55
0.45
0.3
LOW
HIGH
HIGH
HIGH
0.60
0.80
1.00
1.35
84
85
86
87
84
85
86
87
74
75
76
77
67
68
69
70
69
70
71
72
62
63
64
65
57
58
59
60
52
53
54
55
74
75
76
77
41
42
43
44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran-
tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
1
TABLE 2: CAPACITY RATINGS - (ARI 210/240)
EER2
SEER3
10.0
10.0
10.0
-
MODEL
MBH
DM036
DM048
DM060
DM072
36.0
47.4
59.0
72.0
9.1
9.0
9.1
9.0
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
1
TABLE 3: GAS HEAT RATINGS
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
MODEL
DM036N04
DM036N08
50
100
40
79
80.9
80.5
15 - 45
40 - 70
DM048N06
DM048N10
75
125
59
99
80.9
80.3
25 - 55
45 - 75
DM060N08
DM060N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
DM072N08
DM072N10
100
125
79
99
80.5
80.3
25 - 55
35 - 65
1. All units are single-stage heating.
Unitary Products Group
11
036-21502-002-A-0303
TABLE 4: DM036 COOLING CAPACITIES (3 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
95°F
SENSIBLE CAPACITY1
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
ENTERING DRY BULB, °F
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
45
43
39
40
44
41
38
39
42
40
36
37
41
38
35
36
39
37
34
34
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
3.1
3.0
3.0
2.9
35
43
39
40
31
39
38
39
28
35
36
37
26
32
35
36
24
30
34
34
30
38
39
40
28
35
38
39
25
32
36
37
23
30
35
36
21
27
33
34
26
34
39
40
24
31
37
39
22
28
35
37
20
27
33
35
19
25
30
33
21
29
34
35
20
27
33
35
18
25
31
34
17
24
30
32
16
22
28
30
17
25
30
31
16
23
29
31
15
22
28
31
14
21
27
29
14
20
25
27
-
-
43
41
36
38
42
39
36
37
41
38
35
36
39
37
33
34
38
36
32
33
3.3
3.3
3.3
3.2
3.3
3.3
3.3
3.2
3.3
3.2
3.3
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.1
35
41
36
38
31
37
36
37
28
34
35
36
26
32
33
34
23
29
32
33
30
38
36
38
27
35
36
37
24
31
35
36
23
29
33
34
21
26
31
33
26
34
36
38
23
31
35
36
21
28
34
35
20
26
31
32
18
24
29
30
21
29
32
33
20
27
31
32
18
25
30
32
17
23
28
30
16
21
26
27
17
25
27
29
16
23
27
28
14
21
27
28
14
20
25
27
13
19
24
25
-
-
20
25
26
-
16
21
22
-
21
23
24
-
16
18
20
-
1750
19
25
27
-
16
21
23
-
19
23
25
-
15
19
21
-
1475
1200
1050
900
18
25
27
-
15
21
24
-
18
24
25
-
15
20
22
-
18
24
26
-
15
21
23
-
17
22
24
-
14
20
21
-
17
23
25
15
20
22
16
21
22
14
19
20
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
105°F
115°F
EVAPORATOR
COIL
SENSIBLE CAPACITY1
SENSIBLE CAPACITY1
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
41
38
34
35
40
37
33
34
39
36
32
33
37
35
31
32
36
33
30
31
3.7
3.7
3.7
3.6
3.7
3.6
3.7
3.6
3.7
3.6
3.6
3.6
3.6
3.6
3.6
3.5
3.6
3.6
3.6
3.5
34
38
34
35
30
36
33
34
27
34
32
33
25
31
31
32
22
28
30
31
29
37
34
35
26
34
33
34
24
30
32
33
22
28
31
32
20
25
29
30
25
33
34
35
23
30
33
34
20
27
32
33
19
25
29
30
17
23
27
28
20
28
30
31
19
26
29
30
17
24
29
29
16
22
27
27
15
20
24
25
16
24
25
26
15
22
25
26
14
20
25
26
13
19
24
24
12
18
22
22
-
-
39
36
32
33
38
35
31
32
37
34
30
31
36
32
29
30
34
31
28
28
4.1
4.0
4.0
4.0
4.1
4.0
4.0
4.0
4.1
4.0
4.0
3.9
4.1
4.0
4.0
3.9
4.0
4.0
4.0
3.9
33
36
32
33
30
34
31
32
26
33
30
31
24
30
29
30
21
27
28
28
28
36
32
33
26
33
31
32
23
30
30
31
21
27
29
29
19
24
28
28
24
32
32
33
22
29
31
32
20
26
30
31
18
24
28
28
16
22
25
25
19
27
27
28
18
25
27
28
16
23
27
27
15
21
25
25
14
19
22
23
15
23
23
24
14
21
23
24
13
20
24
24
12
18
22
22
11
17
20
20
-
-
19
21
22
-
15
16
17
-
18
18
19
-
14
14
15
-
1750
18
21
22
-
14
17
18
-
17
19
20
-
13
15
16
-
1475
1200
1050
900
17
22
23
-
14
19
19
-
16
20
21
-
13
17
17
-
16
21
21
-
13
18
18
-
15
19
19
-
12
16
16
-
15
19
20
13
17
17
14
17
17
11
15
15
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
12
Unitary Products Group
036-21502-002-A-0303
TABLE 5: DM048 COOLING CAPACITIES (4 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
60
55
51
49
58
53
49
47
56
51
47
46
54
49
45
44
52
47
43
42
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
4.1
4.1
4.0
3.9
44
53
51
49
41
49
49
47
38
46
47
46
35
42
45
44
32
39
43
42
39
48
51
49
36
45
49
47
34
41
47
46
31
38
45
44
29
35
43
42
33
42
51
49
31
40
48
47
29
37
45
46
27
34
42
43
25
32
39
39
28
37
45
44
26
35
43
43
25
32
41
41
23
30
38
39
22
28
36
36
23
32
40
39
21
30
38
38
20
28
36
37
19
26
34
35
18
25
32
32
-
-
60
52
48
47
57
50
46
45
55
48
44
44
53
47
43
42
51
45
41
41
4.5
4.5
4.4
4.3
4.5
4.5
4.4
4.3
4.6
4.5
4.4
4.4
4.5
4.5
4.4
4.3
4.5
4.4
4.3
4.3
44
52
48
47
41
49
46
45
38
45
44
44
35
41
43
42
32
38
41
41
39
47
48
47
36
44
46
45
33
40
44
44
31
38
43
42
28
35
41
41
33
42
48
47
31
39
46
45
29
36
44
44
27
34
41
41
25
31
38
38
28
36
42
42
26
34
41
40
24
31
40
39
23
30
37
37
21
28
35
34
23
31
37
36
21
29
36
36
20
27
35
35
19
26
33
33
18
24
31
31
-
-
26
34
33
-
21
29
28
-
25
32
31
-
20
26
26
-
2000
25
33
33
-
20
28
28
-
24
31
31
-
19
26
26
-
1800
1600
1400
1200
24
32
32
-
19
27
28
-
23
31
30
-
18
26
26
-
22
30
31
-
19
26
27
-
22
29
29
-
18
25
25
-
21
29
29
18
25
25
21
28
27
17
24
24
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
105°F
115°F
EVAPORATOR
COIL
SENSIBLE CAPACITY1
SENSIBLE CAPACITY1
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
56
49
45
44
55
48
43
43
53
46
42
41
51
44
40
40
49
42
38
38
5.1
5.0
4.9
4.9
5.0
5.0
4.9
4.9
5.0
4.9
4.9
4.8
5.0
4.9
4.8
4.8
4.9
4.9
4.8
4.8
42
49
45
44
39
47
43
43
36
44
42
41
33
41
40
40
30
37
38
38
37
46
45
44
34
43
43
43
32
40
42
41
29
37
40
40
27
34
38
38
31
40
45
44
29
38
43
43
28
35
42
41
26
33
39
38
23
30
36
35
26
35
39
39
24
33
38
38
23
31
37
37
22
29
35
34
20
27
32
32
21
29
34
33
20
28
33
33
19
26
33
32
18
25
31
30
16
23
29
28
-
-
53
46
41
41
52
45
40
40
51
44
39
39
48
42
37
37
46
39
35
35
5.6
5.5
5.4
5.4
5.5
5.4
5.4
5.4
5.5
5.4
5.3
5.3
5.5
5.3
5.3
5.3
5.4
5.3
5.3
5.3
40
46
41
41
38
45
40
40
35
44
39
39
32
40
37
37
29
36
35
35
35
44
41
41
33
42
40
40
31
39
39
39
28
36
37
37
26
33
35
35
29
39
41
41
28
37
40
40
26
35
39
39
24
32
36
36
22
29
33
33
24
33
36
35
23
32
35
35
22
30
35
34
20
28
32
32
19
26
29
29
19
28
30
30
18
27
30
30
17
26
30
30
16
24
28
28
15
22
26
26
-
-
24
28
28
-
19
23
22
-
23
25
25
-
17
20
19
-
2000
23
28
28
-
18
23
23
-
22
26
25
-
17
21
20
-
1800
1600
1400
1200
22
28
28
-
17
24
23
-
21
26
25
-
17
21
21
-
21
27
26
-
17
23
22
-
20
24
24
-
16
20
20
-
20
25
25
16
22
21
19
22
22
15
19
19
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
13
036-21502-002-A-0303
TABLE 6: DM060 COOLING CAPACITIES (5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
95°F
SENSIBLE CAPACITY1
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
ENTERING DRY BULB, °F
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
68
62
57
55
67
62
56
54
66
61
55
53
63
58
53
51
60
56
51
49
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.7
4.9
4.8
4.7
4.6
4.8
4.7
4.6
4.6
4.8
4.7
4.6
4.6
50
62
57
55
48
59
56
54
45
55
55
53
41
51
53
51
37
46
51
49
44
56
57
55
42
53
56
54
39
50
55
53
36
46
53
51
33
42
51
49
38
50
57
55
36
47
56
54
34
44
55
53
31
41
51
49
29
38
47
45
32
43
51
48
30
41
50
48
29
39
50
48
27
36
47
44
25
34
43
41
25
37
44
42
24
35
45
42
23
34
45
42
22
32
42
40
21
30
39
37
-
-
65
60
53
51
65
59
53
50
64
58
52
50
61
56
50
47
58
53
47
45
5.6
5.3
5.3
5.4
5.4
5.2
5.2
5.3
5.3
5.1
5.1
5.2
5.4
5.1
5.2
5.2
5.4
5.2
5.2
5.3
50
60
53
51
47
57
53
50
44
54
52
50
40
49
50
47
36
44
47
45
43
54
53
51
41
51
53
50
39
48
52
50
35
44
50
47
32
40
47
45
37
48
53
51
35
45
53
50
33
43
52
50
31
39
48
46
28
36
44
42
31
42
47
44
29
40
47
44
28
38
47
44
26
35
43
41
24
32
40
38
24
35
41
38
23
34
41
39
22
32
42
39
21
30
39
36
20
28
36
34
-
-
31
38
36
-
24
32
29
-
29
34
32
-
23
28
25
-
2500
30
39
36
-
24
33
31
-
28
35
33
-
22
29
27
-
2250
2000
1750
1500
28
39
37
-
23
34
32
-
27
36
34
-
22
31
28
-
27
37
35
-
22
32
30
-
25
34
32
-
21
29
27
-
26
35
33
21
31
29
24
32
29
20
27
25
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
105°F
115°F
EVAPORATOR
COIL
SENSIBLE CAPACITY1
SENSIBLE CAPACITY1
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
61
55
49
47
61
54
48
46
60
54
48
46
57
51
45
43
54
48
43
41
6.1
5.9
5.9
5.9
6.0
5.9
5.8
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
6.0
5.8
5.7
5.8
48
55
49
47
45
53
48
46
42
52
48
46
38
47
45
43
34
42
43
41
41
52
49
47
39
49
48
46
37
47
48
46
34
42
45
43
30
38
43
41
35
46
49
47
33
44
48
46
32
41
48
46
29
38
44
42
26
34
39
38
29
39
42
40
28
38
42
40
26
36
43
41
24
33
39
37
22
30
35
34
22
33
36
34
22
32
37
35
21
31
37
35
19
28
34
32
18
26
31
30
-
-
57
50
44
42
57
50
44
42
57
50
44
42
53
46
41
39
49
43
38
37
6.7
6.6
6.5
6.5
6.6
6.5
6.4
6.4
6.6
6.5
6.4
6.3
6.5
6.4
6.3
6.3
6.5
6.4
6.3
6.2
46
50
44
42
43
50
44
42
41
50
44
42
37
45
41
39
33
40
38
37
39
50
44
42
38
47
44
42
36
45
44
42
32
41
41
39
28
36
38
37
33
43
44
42
32
42
44
42
30
40
44
42
27
36
39
38
24
32
35
34
27
37
38
36
26
36
38
36
25
34
38
37
23
31
35
33
20
28
31
30
20
31
31
30
20
30
32
31
20
29
33
32
18
26
30
29
16
24
27
26
-
-
27
30
28
-
20
23
21
-
24
25
23
-
18
19
17
-
2500
26
31
29
-
20
25
23
-
24
26
25
-
18
20
19
-
2250
2000
1750
1500
25
32
30
-
20
27
25
-
24
28
26
-
18
22
21
-
24
30
28
-
19
25
23
-
22
25
24
-
17
21
19
-
22
27
26
18
23
21
20
23
22
16
19
18
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
14
Unitary Products Group
036-21502-002-A-0303
TABLE 7: DM072 COOLING CAPACITIES (6 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
80
80
70
68
82
82
71
69
83
83
73
71
79
79
69
67
74
74
65
63
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.7
5.7
5.5
5.6
5.6
5.6
5.4
5.5
63
76
70
68
60
73
71
69
58
70
73
71
54
65
69
67
50
60
65
63
55
68
70
68
53
65
71
69
51
63
73
71
48
59
69
67
44
55
65
63
47
60
70
68
46
58
70
69
44
56
70
71
41
53
66
67
39
50
62
63
40
53
62
60
38
51
62
62
37
49
63
64
35
47
60
61
34
44
57
58
32
45
55
52
31
43
55
55
30
42
56
57
29
40
54
54
28
39
51
52
-
-
77
77
71
71
76
76
70
70
75
75
69
69
73
73
67
67
71
71
65
65
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.3
6.2
6.3
63
75
71
71
60
73
70
70
58
70
69
69
53
65
67
67
49
59
65
65
55
68
71
71
53
66
70
70
51
64
69
69
47
59
66
66
43
54
63
63
47
60
71
71
46
58
69
70
44
57
68
68
41
52
63
63
38
48
58
58
40
53
63
63
39
51
62
62
37
50
61
61
35
46
57
57
33
43
53
53
32
45
56
56
31
44
55
55
30
43
54
54
29
40
51
51
27
38
47
47
-
-
37
47
45
-
30
39
37
-
37
48
48
-
30
40
40
-
2700
36
48
47
-
29
41
40
-
36
48
48
-
29
40
40
-
2550
2400
2100
1800
35
49
50
-
28
42
43
-
36
47
47
-
29
40
40
-
34
47
48
-
28
41
42
-
34
45
45
-
28
38
39
-
34
46
47
28
41
42
32
42
42
27
37
37
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
105°F
115°F
EVAPORATOR
COIL
SENSIBLE CAPACITY1
SENSIBLE CAPACITY1
TOTAL
CAP.1
TOTAL
CAP.1
POWER
INPUT2 kW
POWER
INPUT2 kW
ENTERING DRY BULB, °F
ENTERING DRY BULB, °F
MBH
MBH
CFM
WB °F
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
76
71
64
64
76
71
64
64
75
70
64
64
73
68
61
61
70
65
59
59
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.1
7.0
7.0
7.1
7.0
7.0
6.9
61
70
64
64
59
69
64
64
56
68
64
64
52
63
61
61
47
57
59
59
53
66
64
64
51
64
64
64
49
61
64
64
45
56
61
61
41
51
58
58
45
58
64
64
44
56
64
64
43
54
63
63
39
50
58
58
36
46
54
53
38
50
56
56
37
49
56
56
36
48
56
56
33
44
52
52
31
41
48
48
30
43
49
49
29
42
49
49
29
41
49
49
27
38
46
46
25
35
43
43
-
-
75
65
57
57
76
66
58
58
76
66
59
59
73
63
56
56
69
60
53
53
7.9
7.8
7.8
7.7
7.9
7.9
7.8
7.7
8.0
7.9
7.8
7.7
7.9
7.8
7.7
7.7
7.8
7.8
7.7
7.6
59
65
57
57
57
66
58
58
55
66
59
59
50
61
56
56
45
55
53
53
51
64
57
57
49
61
58
58
48
59
59
59
44
54
56
56
40
49
53
53
43
56
57
57
42
54
58
58
41
52
59
58
37
48
54
53
34
44
49
49
36
48
50
50
35
47
51
50
34
45
52
51
31
42
48
47
29
39
44
44
28
41
42
42
27
40
43
43
27
38
45
44
25
36
42
41
23
33
39
38
-
-
35
41
41
-
27
34
34
-
33
34
34
-
25
27
27
-
2700
34
42
42
-
27
35
34
-
32
36
36
-
25
29
29
-
2550
2400
2100
1800
34
42
42
-
27
35
35
-
32
38
37
-
25
31
30
-
32
40
40
-
26
34
34
-
30
35
35
-
24
29
29
-
30
38
37
25
32
32
28
33
33
23
28
27
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
15
036-21502-002-A-0303
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.40 0.50 0.60
WATTS RPM WATTS RPM WATTS RPM
UNIT
SIZE
AIR
FLOW
CFM
0.20
WATTS RPM
0.30
WATTS RPM
0.70
WATTS RPM
0.80
WATTS
(MBH)
RPM
1700
1600
1500
1400
1300
1200
1100
1000
900
835
705
880
745
923
898
871
844
816
-
795
740
685
640
590
-
969
942
917
889
862
834
809
782
-
860
790
730
680
635
585
550
510
-
1013
986
960
932
907
881
855
829
797
970
840
775
720
675
630
590
545
500
-
-
-
-
811
655
854
695
1029
1003
975
951
927
900
872
843
900
825
765
715
665
625
858
540
-
-
782
610
827
650
1046
1018
995
970
942
919
890
905
790
750
705
665
625
580
-
-
-
-
-
-
-
-
-
-
-
-
798
595
0361 2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
1.10 1.20 1.30
WATTS RPM WATTS RPM WATTS RPM
UNIT
SIZE
AIR
FLOW
CFM
0.90
WATTS RPM
1.00
WATTS RPM
1.40
WATTS RPM
1.50
(MBH)
RPM
-
WATTS
1700
1600
1500
1400
1300
1200
1100
1000
900
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1055
1036
1011
987
963
936
875
780
735
690
655
615
-
-
-
-
-
-
-
-
-
0361 2
1066
1047
1028
1005
980
850
765
720
680
645
-
-
-
-
-
-
-
-
-
1075
1060
1040
1020
800
750
695
660
-
-
-
-
-
1084
1068
1050
775
715
670
-
-
-
-
-
-
1089
1053
735
680
1090
690
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table
for resistance values on applications other than gas / electric units with side duct airflows.
16
Unitary Products Group
036-21502-002-A-0303
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT
SIZE
AIR
FLOW
CFM
0.20
WATTS RPM
0.30
WATTS RPM
0.40
WATTS RPM
0.50
WATTS RPM
0.60
WATTS RPM
0.70
WATTS RPM
0.80
WATTS
(MBH)
RPM
2000
1900
1800
1700
1600
1500
1400
1300
1200
843
860
880
925
919
893
867
840
818
-
1005
956
930
906
881
858
842
833
-
1065
993
970
944
920
898
882
867
858
847
1145
1030
1008
985
961
940
922
904
893
880
1195
1067
1046
1025
1001
980
1235
1170
1100
1030
950
817
775
854
850
920
995
905
815
740
695
650
-
1065
980
900
820
755
705
665
640
1125
1040
970
890
835
765
725
680
790
700
828
760
840
-
-
-
-
-
-
-
-
-
-
-
-
802
670
745
0481 2
-
-
-
-
-
-
-
-
-
-
665
-
-
-
-
962
895
-
942
820
-
932
785
-
-
-
916
730
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT
SIZE
AIR
FLOW
CFM
0.90
WATTS RPM
1.00
WATTS RPM
1.10
WATTS RPM
1.20
WATTS RPM
1.30
WATTS RPM
1.40
WATTS RPM
1.50
(MBH)
RPM
1103
1085
1064
1040
1020
1003
982
WATTS
2000
1900
1800
1700
1600
1500
1400
1300
1200
1270
1210
1145
1075
1005
945
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1102
1081
1060
1044
1024
1010
992
1180
1115
1050
995
920
870
815
-
-
1121
1100
1086
1067
1053
1034
1140
1085
1035
965
-
0481 2
-
-
880
1107
1099
1080
1000
960
970
835
920
953
780
855
905
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
17
036-21502-002-A-0303
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.40 0.50 0.60
WATTS RPM WATTS RPM WATTS RPM
UNIT
SIZE
AIR
FLOW
CFM
0.20
WATTS RPM
0.30
WATTS RPM
0.70
WATTS RPM
0.80
WATTS
(MBH)
RPM
1059
1032
1005
980
930
877
-
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
1560
1077
1590
1095
1074
1049
1022
983
941
894
855
-
1630
1114
1094
1069
1044
1010
976
940
903
884
864
-
1650
1134
1116
1090
1066
1039
1009
980
1660
1595
1475
1350
1160
1050
980
1158
1140
1116
1090
1064
1040
1014
988
1685
1181
1167
1142
1117
1092
1070
1047
1022
1001
987
1720
1640
1535
1440
1340
1225
1095
970
1405
1054
1470
1525
1370
1190
1080
1000
885
815
-
1560
1440
1250
1100
1020
940
860
815
770
-
1620
1505
1410
1260
1100
1020
940
1260
1024
1275
1160
1002
1170
1060
957
1070
0601 2
950
908
975
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
950
905
-
925
850
964
880
910
-
-
-
908
805
948
835
870
-
-
-
882
740
926
780
965
830
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT
SIZE
AIR
FLOW
CFM
0.90
WATTS RPM
1.00
WATTS RPM
1.10
WATTS RPM
1.20
WATTS RPM
1.30
WATTS RPM
1.40
WATTS RPM
1.50
(MBH)
RPM
-
WATTS
2500
2400
2300
2200
2100
2000
1900
1800
1700
1600
1500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1193
1170
1148
1121
1100
1079
1058
1035
1020
1004
1665
1580
1480
1385
1285
1180
1060
960
-
-
-
-
-
-
-
-
-
-
-
-
1202
1180
1155
1133
1110
1090
1071
1056
1038
1620
1530
1425
1340
1240
1135
1030
965
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1190
1169
1143
1122
1103
1088
1070
1475
1385
1280
1190
1100
1035
925
-
-
-
-
-
-
-
0601 2
1205
1178
1158
1134
1118
1101
1445
1330
1240
1140
1065
980
-
-
-
-
-
-
1222
1196
1164
1145
1130
1375
1295
1175
1105
1045
-
-
-
-
-
-
-
-
1197
1170
1158
1205
1130
1075
-
-
900
1198
1184
1150
1110
860
880
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
18
Unitary Products Group
036-21502-002-A-0303
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BELT DRIVE) - SIDE DUCT APPLICATION
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT
SIZE
AIR
FLOW
CFM
0.20
WATTS RPM
0.30
WATTS RPM
0.40
WATTS RPM
0.50
WATTS RPM
0.60
WATTS RPM
0.70
WATTS RPM
0.80
WATTS
(MBH)
RPM
1150
1100
1045
985
930
-
3200
3000
2800
2600
2400
2200
2000
1800
2325
1182
1129
1074
1015
958
905
-
2425
1212
1157
1102
1045
990
933
-
2525
-
-
-
-
-
-
-
-
2010
2090
1780
1475
1300
1070
-
2150
1850
1540
1350
1160
-
1185
1131
1075
1020
965
919
-
2225
1940
1630
1400
1210
1025
-
1215
1160
1103
1051
997
2290
2025
1715
1430
1250
1100
925
1242
1190
1135
1081
1028
982
2360
2075
1760
1490
1285
1130
1005
-
-
1700
1217
1163
1111
1060
1014
968
2130
1825
1600
1325
1160
1030
1425
0721 2
1240
-
-
-
-
950
-
-
-
-
-
909
939
3
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT
SIZE
AIR
FLOW
CFM
0.90
WATTS RPM
1.00
WATTS RPM
1.10
WATTS RPM
1.20
WATTS RPM
1.30
WATTS RPM
1.40
WATTS RPM
1.50
(MBH)
RPM
-
WATTS
3200
3000
2800
2600
2400
2200
2000
1800
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1245
1193
1142
1090
1045
998
2190
1920
1675
1380
1175
1050
-
-
-
-
-
-
-
-
-
-
1222
1173
1124
1077
1028
1990
1730
1450
1200
1060
1250
1205
1155
1109
1058
2060
1800
1550
1275
1060
-
-
-
-
-
-
-
0721 2
1234
1186
1140
1087
1885
1640
1360
1075
-
-
-
-
-
-
1217
1170
1118
1710
1460
1150
1249
1205
1148
1775
1545
1250
-
-
1235
1176
1600
1360
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
19
036-21502-002-A-0303
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT SIZE
MOTOR SPEED
0.20
0.30
0.40
0.50
0.60
(MBH)
CFM
-
WATTS
-
CFM
-
WATTS
-
CFM
1699
1582
1421
1868
1714
1604
2274
2145
2029
2361
WATTS
825
CFM
1650
1524
1367
1795
1650
1541
2167
2071
1965
2260
WATTS
785
CFM
1570
1410
1315
1722
1589
1490
2096
1990
1905
2178
WATTS
755
HI
MED
LOW
HI
0361
1684
1487
1996
1804
1681
2400
2290
2150
2461
800
1631
1464
1933
1765
1640
2338
2214
2100
2402
780
750
720
690
710
690
670
650
620
960
936
910
880
845
0481
MED
LOW
HI
838
810
785
765
735
760
738
715
695
670
1155
1105
1020
1480
1125
1065
990
1095
1030
950
1045
990
1010
950
0601
0721
MED
LOW
HI
910
880
1440
1395
1350
1305
2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
UNIT SIZE
(MBH)
MOTOR SPEED
0.70
0.80 0.90
1.00
CFM
1430
1324
1246
1635
1508
1416
1990
1911
1816
2101
WATTS
725
CFM
1360
1260
1185
1544
1407
1337
1887
1828
1724
2000
WATTS
700
CFM
1280
1185
1110
1419
1306
1230
1771
1724
1644
1914
WATTS
680
CFM
1180
1100
1020
1300
1195
1120
1629
1604
1531
1830
WATTS
655
HI
MED
LOW
HI
0361
0481
650
630
610
590
605
590
570
545
820
790
765
740
MED
LOW
HI
705
675
645
625
645
620
595
575
980
945
905
855
0601
0721
MED
LOW
HI
920
885
835
798
838
800
770
710
1260
1205
1155
1110
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values
TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
MOTOR1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
BLOWER
RANGE
(RPM)
MODEL
SIZE
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
PITCH
LENGTH QTY.
DESIG-
NATION
BORE DESIG-
(IN.)
BORE DESIG-
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
NATION
(IN.)
NATION
(IN.)
37.3
37.3
37.3
37.3
3 TON
4 TON
5 TON
6 TON
790/1120 1 1/2
790/1120 1 1/2
850/1220 1 1/2
900/1250 1 1/2
56
56
56
56
1VL40
1VL40
1VL40
1VL44
2.7-3.7
2.7-3.7
2.7-3.7
3.1-4.1
2.4-3.4
2.4-3.4
2.4-3.4
2.8-3.8
5/8
5/8
5/8
7/8
AK61
AK61
AK56
AK56
5.9
5.9
5.4
5.4
5.7
5.7
5.2
5.2
1
1
1
1
A36
A36
A36
A36
1
1
1
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
20
Unitary Products Group
036-21502-002-A-0303
TABLE 14: STATIC RESISTANCES
RESISTANCE, IWG
CFM
DESCRIPTION
1000
1200
0.08
0.05
0.07
0.07
0.10
1400
0.09
0.06
0.08
0.08
0.12
1600
0.11
0.07
0.09
0.09
0.14
1800
2000
0.15
0.10
0.13
0.11
0.18
2200
2400
0.20
0.14
0.17
0.14
0.23
2600
0.23
0.16
0.20
0.16
0.26
2800
0.26
0.19
0.23
0.19
0.29
3000
0.30
0.22
0.26
0.22
0.32
ECONOMIZER1 2
0.07
0.13
0.08
0.11
0.10
0.16
0.17
0.12
0.15
0.12
0.20
ELECTRIC
HEATERS3
5-15KW
0.04
0.06
0.06
0.08
20-30KW
BOTTOM DUCT CONNECTIONS1
COOLING ONLY2
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
3. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
TABLE 15: ELECTRIC HEATER CFM LIMITATIONS
MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE NOMINAL
VOLTAGE
HEATER SIZE NOMINAL KW
TONS
5
7
10
15
20
30
208/230-1-60
208/230-3-60
460-3-60
1100
1100
1100
1100
-
1200
1200
1200
1200
1300
1300
1300
1300
1600
1600
1600
1600
1800
1800
1800
1800
1200
1200
1200
1200
1300
1300
1300
1300
1600
1600
1600
1600
1800
1800
1800
1800
1300
1300
1300
1300
1300
1300
1300
1400
1600
1600
1600
1600
1800
1800
1800
1800
-
1100
-
3
-
-
575-3-60
-
-
208/230-1-60
208/230-3-60
460-3-60
1300
1300
1300
1300
-
-
1300
-
4
5
6
-
-
575-3-60
-
-
208/230-1-60
208/230-3-60
460-3-60
1600
1600
1600
1600
-
1600
1600
1600
1800
1800
1800
1800
1800
1600
-
575-3-60
-
208/230-1-60
208/230-3-60
460-3-60
1800
1800
1800
1800
-
1800
-
-
575-3-60
Unitary Products Group
21
036-21502-002-A-0303
TABLE 16: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Minimum
Compressors
OD Fan ID Blower Conv
Max Fuse /
BRKR1 Size
Amps
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
0.0
30.7
30.7
39.2
53.6
77.0
101.1
30.7
33.1
44.6
60.7
88.3
115.9
24.3
24.3
24.9
33.3
46.8
60.7
24.3
24.3
28.1
37.4
53.3
69.2
12.4
13.0
17.9
23.2
32.1
10.1
14.9
21.3
27.7
38.5
38.5
39.9
54.3
77.8
101.8
38.5
38.5
45.3
61.5
89.1
116.7
25.7
25.7
25.7
34.0
47.5
61.4
25.7
25.7
28.8
38.1
54.1
70.0
13.1
13.1
17.9
23.2
32.1
10.8
14.9
21.3
27.7
45
45
45
60
80
110
45
45
45
70
90
125
35
35
35
35
50
70
35
35
35
40
60
70
15
15
20
25
35
15
15
25
30
60
60
60
60
80
110
60
60
60
70
90
125
40
40
40
40
50
70
40
40
40
40
60
70
20
20
20
25
35
15
15
25
30
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
5.6
8.0
208-1-60
19.2
19.2
14.1
14.1
87
87
2.3
2.3
2.3
2.3
4.4
4.4
4.4
4.4
0.0
0.0
0.0
0.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
110
110
8.0
11.9
15.9
0.0
3
2CE04510525
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
2CE045105252
2CE045107252
2CE04511525
2CE04512025
NONE
10.6
15.9
21.2
0.0
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
6.8
8.2
460-3-60
575-3-60
7.1
5.8
54
44
1.3
1.3
2.2
2.2
0.0
0.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
NONE
10.6
15.9
21.2
0.0
10.2
15.3
20.4
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
4.0
5.6
19.2
26.9
38.5
57.2
76.4
0.0
208-1-60
230-1-60
208-3-60
230-3-60
25.0
25.0
14.7
14.7
135
135
130
130
2.3
2.3
2.3
2.3
5.0
5.0
5.0
5.0
0.0
0.0
0.0
0.0
8.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
4
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
7.7
6.4
64
52
1.3
1.3
2.2
2.2
0.0
0.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
10.6
15.9
21.2
10.2
15.3
20.4
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
22
Unitary Products Group
036-21502-002-A-0303
TABLE 17: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Minimum
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
44.0
44.0
44.0
56.3
79.8
103.8
141.7
44.0
44.0
47.3
63.5
91.1
118.7
162.4
27.9
27.9
27.9
36.0
49.5
63.4
85.3
27.9
27.9
30.8
40.1
56.1
72.0
97.3
14.1
14.3
19.3
24.6
33.4
47.4
11.3
16.0
22.4
28.8
39.9
31.7
31.7
31.7
36.3
49.8
63.7
85.5
31.7
31.7
31.7
40.4
56.3
72.2
97.5
16.3
16.3
19.7
24.9
33.8
47.8
13.0
16.3
22.7
29.1
40.2
70
70
70
70
80
110
150
70
70
70
70
100
125
175
40
40
40
40
50
70
90
40
40
40
45
60
80
100
20
20
20
25
35
50
15
20
25
30
40
50
50
50
50
50
70
90
50
50
50
50
60
80
100
25
25
25
25
35
50
15
20
25
30
40
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
5.6
8.0
208-1-60
28.9
28.9
16.0
16.0
165
165
125
125
1.3
1.3
1.3
1.3
6.6
6.6
6.6
6.6
0.0
0.0
0.0
0.0
11.9
15.9
22.2
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
123.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
29.6
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
8.0
11.9
15.9
22.2
0.0
5
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
10.6
15.9
21.2
29.6
0.0
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
8.0
6.4
66.5
0.8
0.8
3.3
3.3
0.0
0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
10.6
15.9
21.2
30.4
0.0
10.2
15.3
20.4
29.3
0.0
50
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
208-3-60
18.9
146
1.3
6.8
0.0
8.0
11.9
15.9
22.2
0.0
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
230-3-60
18.9
146
1.3
6.8
0.0
10.6
15.9
21.2
29.6
0.0
6
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
9.5
7.6
73
0.8
0.8
3.6
3.6
0.0
0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
10.2
15.3
20.4
29.3
58.4
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
23
036-21502-002-A-0303
TABLE 18: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Minimum
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
0.0
31.4
33.5
43.2
57.6
81.0
105.1
31.4
37.1
48.6
64.7
92.3
119.9
20.8
20.8
25.9
34.3
47.8
61.7
20.8
22.4
29.1
38.4
54.3
70.2
11.1
13.5
18.4
23.7
32.6
8.5
45
45
45
60
90
110
45
45
50
70
100
125
30
30
30
35
50
70
30
30
30
40
60
80
15
15
20
25
35
15
15
25
30
60
60
60
60
90
110
60
60
60
70
100
125
35
35
35
35
50
70
35
35
35
40
60
80
15
15
20
25
35
15
15
25
30
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
5.6
8.0
208-1-60
18.0
18.0
11.4
11.4
105
105
90
1.3
1.3
1.3
1.3
7.6
7.6
5.2
5.2
0.0
0.0
0.0
0.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
3
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
90
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
6.2
5.0
45
36
0.8
0.8
2.6
2
0.0
0.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
NONE
10.6
15.9
21.2
0.0
10.2
15.3
20.4
0.0
14.7
21.1
27.5
39.4
39.4
43.2
57.6
81.0
105.1
39.4
39.4
48.6
64.7
92.3
119.9
24.1
24.1
25.9
34.3
47.8
61.7
24.1
24.1
29.1
38.4
54.3
70.2
12.3
13.5
18.4
23.7
32.6
9.5
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
4.0
5.6
19.2
26.9
38.5
57.2
76.4
0.0
208-1-60
230-1-60
208-3-60
230-3-60
24.4
24.4
14.1
14.1
140
140
105
105
1.3
1.3
1.3
1.3
7.6
7.6
5.2
5.2
0.0
0.0
0.0
0.0
8.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
4
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
7.1
5.8
55
44
0.8
0.8
2.6
2
0.0
0.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
10.6
15.9
21.2
10.2
15.3
20.4
14.7
21.1
27.5
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
24
Unitary Products Group
036-21502-002-A-0303
TABLE 19: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Minimum
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
45.0
45.0
45.0
57.6
81.0
105.1
142.9
45.0
45.0
48.6
64.7
92.3
119.9
163.7
26.5
26.5
26.5
34.3
47.8
61.7
83.5
26.5
26.5
29.1
38.4
54.3
70.2
95.5
13.4
13.5
18.4
23.7
32.6
46.6
10.2
14.7
21.1
27.5
38.6
29.9
29.9
29.9
34.0
47.5
61.4
83.3
29.9
29.9
29.9
38.1
54.1
70.0
95.3
15.2
15.2
18.3
23.6
32.4
46.4
11.7
14.7
21.1
27.5
38.6
70
70
70
70
90
110
150
70
70
70
70
100
125
175
40
40
40
40
50
70
90
40
40
40
40
60
80
100
20
20
20
25
35
50
15
15
25
30
40
45
45
45
45
50
70
90
45
45
45
45
60
70
100
20
20
20
25
35
50
15
15
25
30
40
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
5.6
8.0
208-1-60
28.9
28.9
16.0
16.0
165
165
125
125
1.3
1.3
1.3
1.3
7.6
7.6
5.2
5.2
0.0
0.0
0.0
0.0
11.9
15.9
22.2
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
123.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
29.6
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
8.0
11.9
15.9
22.2
0.0
5
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
10.6
15.9
21.2
29.6
0.0
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
8.0
6.4
66.5
0.8
0.8
2.6
0.0
0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
10.6
15.9
21.2
30.4
0.0
10.2
15.3
20.4
29.3
0.0
50
2
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
208-3-60
18.9
146
1.3
5.0
0.0
8.0
11.9
15.9
22.2
0.0
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
230-3-60
18.9
146
1.3
5.0
0.0
10.6
15.9
21.2
29.6
0.0
6
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
9.5
7.6
73
0.8
0.8
2.5
0.0
0.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
10.2
15.3
20.4
29.3
58.4
2
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
25
036-21502-002-A-0303
TABLE 20: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Minimum
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
0.0
38.2
42.0
51.7
66.1
89.5
113.6
38.2
45.6
57.1
73.2
100.8
128.4
29.9
31.9
37.4
45.8
59.3
73.2
29.9
33.9
40.6
49.9
65.8
81.7
15.8
19.2
24.2
29.4
38.3
12.7
19.9
26.3
32.7
46.8
46.8
52.4
66.8
90.3
114.3
46.8
46.8
57.8
74.0
101.6
129.2
33.9
33.9
38.2
46.5
60.0
73.9
33.9
34.7
41.3
50.6
66.6
82.5
16.9
19.2
24.2
29.4
38.3
13.7
19.9
26.3
32.7
50
50
60
70
90
125
50
50
60
80
110
150
40
40
40
50
60
80
40
40
45
50
70
90
20
20
25
30
40
15
20
30
35
70
70
70
70
100
125
70
70
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
5.6
8.0
208-1-60
18.0
18.0
11.4
11.4
105
105
90
1.3
1.3
1.3
1.3
4.4
4.4
4.4
4.4
10.0
10.0
10.0
10.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
3
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
90
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
6.2
5.0
45
36
0.8
0.8
2.2
2.2
5.0
4.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
NONE
10.6
15.9
21.2
0.0
10.2
15.3
20.4
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
4.0
5.6
19.2
26.9
38.5
57.2
76.4
0.0
208-1-60
230-1-60
208-3-60
230-3-60
24.4
24.4
14.1
14.1
140
140
105
105
1.3
1.3
1.3
1.3
5.0
5.0
5.0
5.0
10.0
10.0
10.0
10.0
8.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
4
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
7.1
5.8
55
44
0.8
0.8
2.2
2.2
5.0
4.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
10.6
15.9
21.2
10.2
15.3
20.4
2CE04512058
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
26
Unitary Products Group
036-21502-002-A-0303
TABLE 21: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Minimum
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
54.0
54.0
54.4
68.8
92.3
116.3
154.2
54.0
54.0
59.8
76.0
103.6
131.2
174.9
37.9
37.9
40.2
48.5
62.0
75.9
97.8
37.9
37.9
43.3
52.6
68.6
84.5
109.8
19.1
20.6
25.6
30.8
39.7
53.7
15.3
21.0
27.4
33.8
44.9
41.7
41.7
41.7
48.8
62.3
76.2
98.0
41.7
41.7
43.6
52.9
68.8
84.7
110.0
21.3
21.3
25.9
31.2
40.1
54.1
17.0
21.3
27.7
34.1
45.2
80
80
80
80
100
125
175
80
80
80
80
110
150
175
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
30
35
40
60
20
25
30
35
45
60
60
60
60
70
80
100
60
60
60
60
70
90
125
30
30
30
35
45
60
20
25
30
35
45
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
5.6
8.0
208-1-60
28.9
28.9
16.0
16.0
165
165
125
125
1.3
1.3
1.3
1.3
6.6
6.6
6.6
6.6
10.0
10.0
10.0
10.0
11.9
15.9
22.2
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
123.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
29.6
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
8.0
11.9
15.9
22.2
0.0
5
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
10.6
15.9
21.2
29.6
0.0
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
8.0
6.4
66.5
0.8
0.8
3.3
3.3
5.0
4.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
10.6
15.9
21.2
30.4
0.0
10.2
15.3
20.4
29.3
0.0
50
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
208-3-60
18.9
146
1.3
6.8
10.0
8.0
11.9
15.9
22.2
0.0
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
230-3-60
18.9
146
1.3
6.8
10.0
10.6
15.9
21.2
29.6
0.0
6
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
9.5
7.6
73
0.8
0.8
3.6
3.6
5.0
4.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
10.2
15.3
20.4
29.3
58.4
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
27
036-21502-002-A-0303
TABLE 22: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Minimum
Circuit
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
Ampacity
Amps
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
0.0
41.4
46.0
55.7
70.1
93.5
117.6
41.4
49.6
61.1
77.2
104.8
132.4
30.8
32.9
38.4
46.8
60.3
74.2
30.8
34.9
41.6
50.9
66.8
82.7
16.1
19.7
24.7
29.9
38.8
12.5
19.7
26.1
32.5
49.4
49.4
55.7
70.1
93.5
117.6
49.4
49.6
61.1
77.2
104.8
132.4
34.1
34.1
38.4
46.8
60.3
74.2
34.1
34.9
41.6
50.9
66.8
82.7
17.3
19.7
24.7
29.9
38.8
13.5
19.7
26.1
32.5
50
50
60
80
100
125
50
50
70
80
110
150
40
40
40
50
70
80
40
40
45
60
70
90
20
20
25
30
40
15
20
30
35
70
70
70
80
100
125
70
70
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
5.6
8.0
208-1-60
18.0
18.0
11.4
11.4
105
105
90
1.3
1.3
1.3
1.3
7.6
7.6
5.2
5.2
10.0
10.0
10.0
10.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
3
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
90
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
6.2
5.0
45
36
0.8
0.8
2.6
2
5.0
4.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
NONE
10.6
15.9
21.2
0.0
10.2
15.3
20.4
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
4.0
5.6
19.2
26.9
38.5
57.2
76.4
0.0
208-1-60
230-1-60
208-3-60
230-3-60
24.4
24.4
14.1
14.1
140
140
105
105
1.3
1.3
1.3
1.3
7.6
7.6
5.2
5.2
10.0
10.0
10.0
10.0
8.0
11.9
15.9
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
0.0
10.6
15.9
21.2
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
0.0
8.0
11.9
15.9
0.0
4
5.3
7.5
12.7
18.0
25.5
38.2
51.0
0.0
10.6
15.9
21.2
0.0
6.8
8.2
460-3-60
575-3-60
7.1
5.8
55
44
0.8
0.8
2.6
2
5.0
4.0
10.1
13.6
19.5
0.0
12.1
16.4
23.5
0.0
2CE04511058
2CE04511558
2CE04512058
10.6
15.9
21.2
10.2
15.3
20.4
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
28
Unitary Products Group
036-21502-002-A-0303
TABLE 23: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Minimum
Max Fuse /
BRKR1 Size
Compressors
OD Fan ID Blower Conv
Model
Electric Heater
Model No.
Heater
kW
Heater
Amps
Circuit
Ampacity
Amps
Voltage
Motor
FLA
Motor
FLA
Outlet
Amps
Tonnage
RLA
LRA
Amps
Each
Each
NONE
0.0
4.0
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
55.0
55.0
55.7
70.1
93.5
117.6
155.4
55.0
55.0
61.1
77.2
104.8
132.4
176.2
36.5
36.5
38.4
46.8
60.3
74.2
96.0
36.5
36.5
41.6
50.9
66.8
82.7
108.0
18.4
19.7
24.7
29.9
38.8
52.8
14.2
19.7
26.1
32.5
43.6
39.9
39.9
39.9
46.5
60.0
73.9
95.8
39.9
39.9
41.3
50.6
66.6
82.5
107.8
20.2
20.2
24.6
29.8
38.7
52.7
15.7
19.7
26.1
32.5
43.6
80
80
80
80
100
125
175
80
80
80
80
110
150
200
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
5.6
8.0
208-1-60
28.9
28.9
16.0
16.0
165
165
125
125
1.3
1.3
1.3
1.3
7.6
7.6
5.2
5.2
10.0
10.0
10.0
10.0
11.9
15.9
22.2
0.0
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
5.3
7.5
22.1
31.3
44.2
66.3
88.3
123.3
0.0
230-1-60
208-3-60
230-3-60
10.6
15.9
21.2
29.6
0.0
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
8.0
11.9
15.9
22.2
0.0
5
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
10.6
15.9
21.2
29.6
0.0
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
8.0
6.4
66.5
0.8
0.8
2.6
5.0
4.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
2CE045130462
NONE
10.6
15.9
21.2
30.4
0.0
10.2
15.3
20.4
29.3
0.0
50
2
4.0
5.6
11.1
15.5
22.2
33.0
44.1
61.6
0.0
208-3-60
18.9
146
1.3
5.0
10.0
8.0
11.9
15.9
22.2
0.0
5.3
7.5
12.7
18.0
25.5
38.2
51.0
71.2
0.0
230-3-60
18.9
146
1.3
5.0
10.0
10.6
15.9
21.2
29.6
0.0
6
6.8
8.2
10.1
13.6
19.5
28.8
0.0
12.1
16.4
23.5
34.6
0.0
460-3-60
575-3-60
9.5
7.6
73
0.8
0.8
2.5
5.0
4.0
2CE04511058
2CE04511558
2CE04512058
2CE04513058
10.6
15.9
21.2
30.4
10.2
15.3
20.4
29.3
58.4
2
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
29
036-21502-002-A-0303
TABLE 24: PHYSICAL DATA
DM
MODELS
Centrifugal Blower (Dia. x Wd. in.)
036
12 X 10
1/2
048
12 X 10
3/4
060
12 X 10
1
072
12 X 11
1
EVAPORATOR
BLOWER
Fan Motor HP (Direct Drive)
Fan Motor HP (Belt Drive)
Rows Deep
1 1/2
3
1 1/2
3
1 1/2
3
1 1/2
4
EVAPORATOR
COIL
Fins Per Inch
13
13
13
13
Face Area (Sq. Ft.)
Propeller Dia. (in.)
Fan Motor Hp
3.6
4.3
5.1
5.1
24
24
24
24
CONDENSER
FANS
1/4
1/4
1/4
1/4
Nom. CFM
3400
1
3400
1
3400
1
3400
2
Rows Deep
CONDENSER
COILS
Fins Per Inch
16
16
22
16
Face Area (Sq. Ft.)
17.1
17.1
17.1
16.7
COMPRESSOR
(Qty. Per Unit)
Scroll Type
1
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)
Quantity Per Unit (14” X 25” X 1” or 2“)
Total Face Area (sq. ft.)
2
1
2
1
2
1
2
1
AIR
FILTERS
6.3
6.3
6.3
6.3
Refrigerant 22
(lbs./oz.)
CHARGE
5/8
6/8
6/8
10/0
1
TABLE 25: ELECTRIC HEAT CORRECTION FACTORS
kW CAP. MULTI-
TABLE 26: VOLTAGE LIMITATIONS
VOLTAGE
NOMINAL VOLTAGE
VOLTAGE
POWER SUPPLY
PLIER
MIN.
MAX.
208
230
460
575
1.00
0.92
0.92
0.92
208
240
480
600
208/230-3-60
187
253
460-3-60
575-3-60
414
518
506
506
1. Utilization Range “A” in accordance with ARI Standard
110.
30
Unitary Products Group
036-21502-002-A-0303
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
UNIT TERMINAL
STRIP TB1
UNIT TERMINAL
STRIP TB1
RH
ADD
JUMPER
RV
YC
R
R
RC
Y
24 VOLT
TRANSFORMER
Y1
Y1
Y2
24 VOLT
TRANSFORMER
Y2
G
W1
W2
G
W
G
GF
C
1 24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
C
1 24 VOLT THEROMSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THEROMSTAT)
SINGLE STAGE
COOLING / HEATING (ELECTRONIC THEROMSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
THERMOSTAT1
TERMINALS
UNIT TERMINAL
STRIP TB1
UNIT TERMINAL
STRIP TB1
RH
RC
Y
RC
RH
Y1
24 VOLT
TRANSFORMER
ADD
JUMPER
R
R
Y1
W1
G
Y1
ADD
JUMPER
Y2
W1
W2
G
W
Y2
2
3
W1
G
4
W2
G
C
24 VOLT
TRANSFORMER
C
B
1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
LED 1
LED 2
COM
A1
X
NOT
USED
OCC
4
ADD
JUMPER
A2
TO REMOTE SENSOR
2TH040702224 IF USED
T
T
1 ELECTRONIC PROGRAMMABLE THEROMSTAT 2TH04700224 (INCLUDES SUBBASE).
2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER.
FIGURE 2: TYPICAL FIELD POWER & CONTROL WIRING
Unitary Products Group
31
036-21502-002-A-0303
FIGURE 3: UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4: UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
32
Unitary Products Group
036-21502-002-A-0303
DETAIL “A”
FIGURE 5: UNIT WITH ECONOMIZER RAINHOOD
DETAIL “B”
FIGURE 6: UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unitary Products Group
33
036-21502-002-A-0303
FIGURE 7: UNIT DIMENSIONS (REAR VIEW)
TABLE 28: MINIMUM CLEARANCES
CLEARANCE
LOCATION
24” (Cooling/Electric Heat)
32” (Gas Heat)
Front
FILTER
ACCESS
12” (Less Economizer)
36” (With Economizer or Fixed
Air/Motorized Damper)
BLOWER MOTOR
ACCESS
Back
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
24” (Less Economizer)
36” (With Economizer)
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit1
24”
0”
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
A,B
WIRING ENTRY
CONTROL BOX
72” (For
Condenser Air Discharge)
the blower compartment)
Above Unit2
(See Detail “B”)
ACCESS
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc-
tures or shrubs should not obstruct condenser air dis-
charge outlet.
FIGURE 8: DISCONNECT/BLOWER ACCESS
LOCATION
TABLE 27: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
Side
Bottom
Side
1
2
A
7/8” KO
Control Wiring
Power Wiring
1
B
2” KO
Bottom
C
D
1-5/8” KO
1-1/2” KO
Gas Piping (Front)
Gas Piping (Bottom)
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
34
Unitary Products Group
036-21502-002-A-0303
FIGURE 9: TYPICAL APPLICATIONS
Unitary Products Group
35
036-21502-002-A-0303
BACK OF UNIT
BACK OF UNIT
821/4
A
A
447/8
447/8
821/4
B
D
F
X
X
B
C
E
APPROXIMATE
APPROXIMATE
CENTER OF GRAVITY
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
CONDENSER COIL
END OF UNIT
C
D
FRONT OF UNIT
FRONT OF UNIT
Y
Y
FIGURE 10: FOUR AND SIX POINT LOADING
TABLE 29: DM 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
A
B
C
D
DM036 Cooling/ Electric
565
125
123
157
160
DM036N04
625
635
615
675
685
640
700
710
720
775
785
140
140
137
152
152
143
158
158
164
179
179
133
138
135
145
150
140
150
155
189
201
206
172
177
170
185
190
177
192
197
196
209
214
180
180
173
193
193
180
200
200
171
186
186
DM036N08
DM048 Cooling/ Electric
DM048N06
DM048N10
DM060 Cooling/ Electric
DM060N08
DM060N10
DM072 Cooling/ Electric
DM072N08
DM072N10
TABLE 30: DM 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
A
B
C
D
E
F
DM036 Cooling/ Electric
565
84
83
82
104
105
107
DM036N04
625
635
615
675
685
640
700
710
720
775
785
93
94
92
93
91
92
115
117
113
124
126
118
129
131
134
144
146
117
119
115
126
128
119
131
133
122
131
133
118
120
116
128
129
121
132
134
111
120
121
DM036N08
DM048 Cooling/ Electric
DM048N06
91
90
89
100
102
95
99
98
DM048N10
100
94
99
DM060 Cooling/ Electric
DM060N08
93
104
105
107
115
117
103
104
117
126
128
101
103
129
139
141
DM060N10
DM072 Cooling/ Electric
DM072N08
DM072N10
TABLE 31: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
6 TON
X
Y
40-¾”
44”
22”
19-¾”
36
Unitary Products Group
036-21502-002-A-0303
TABLE 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE
3 TON
4 TON
615
-
5 TON
6 TON
DM (Cooling Only)
565
625
-
640
-
720
-
N04
N06
N08
N10
BASIC
UNIT
675
-
-
-
DM
(Gas/Electric)
635
-
700
710
775
785
685
Economizer
Motorized Damper
50
26
18
23
28
92
10
5
OPTIONS
ACCY.
5 - 7 kW
10 - 15 kW
20 - 30 kW
Electric Heater
Roof Curb
Barometric Relief / Fixed Air Damper
Belt-Drive Blower
FIGURE 11: ROOF CURB DIMENSIONS
Unitary Products Group
37
036-21502-002-A-0303
UNIT CABINET
GUIDE SPECIFICATIONS
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 750 hours salt spray test per
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
ASTMB117 standards. Indoor blower section shall be insu-
lated with a minimum 1/2” thick insulation, coated on the air-
side. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan perfor-
mance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air by-
pass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Con-
densate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
TM
York's Sunline 2000 units are convertible single package-
units. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at ground
level or set on steel beams above a finished roof. Cooling
only, cooling with gas heat and cooling with electric heat
models are available with a wide variety of factory-mounted
options and field-installed accessories to make them suitable
for almost every application. All units are self-contained and
assembled on full perimeter base rails with holes in the four
corners for overhead rigging. Every unit is completely piped,
wired, charged and tested at the factory to simplify the field
installation and to provide years of dependable operation. All
models (including those with an economizer) are suitable for
either bottom or horizontal duct connections. Models with
power exhaust are suitable for bottom duct connections only.
For bottom duct, remove the sheet metal panels from the
supply and return air openings through the base of the unit.
For horizontal duct, remove the supply and return air panels
on the rear of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected (B.H.P.) brake horsepower
shall not exceed the motors nameplate horsepower rating,
plus the service factor. Units shall be designed not to operate
above service factor. Fan wheel shall be double-inlet type
with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no mainte-
nance.
All non-Scroll compressors include crankcase heaters and all
compressors have internal pressure relief. Every refrigerant
circuit includes a liquid line filter-drier, a discharge line high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch.The unit control circuit
includes a 75 VA transformer, a 24-volt circuit breaker and a
relay board with a compressor lockout circuit, a terminal strip
for thermostat wiring, plus an additional set of pin connectors
to simplify the interface of additional field controls. All units
have long lasting powder paint cabinets with 750 hour salt
spray test approval under ASTMB117 procedures. All models
are CSA listed. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater ele-
ments carry a 5-year warranty. Aluminized steel and Stainless
steel tubular heat exchangers carry a 10-year warranty.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and
staged independently.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
REFRIGERANT COMPONENTS
The 3 thru 5 ton units shall have minimum SEER ratings of
10.0 and the 6 ton units shall have minimum EER ratings of
9.0. They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge sup-
ply/return, and be available with factory installed options or
field installed accessories. The units shall be factory wired,
piped, charged with R-22 refrigerant and factory tested prior
to shipment. All unit wiring shall be both numbered and color
coded. All units the cooling performance shall be rated in
accordance with DOE and ARI test procedures. Units shall be
CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236
standards.
Compressor:
a. Shall be internally protected with internal high-pres-
sure relief and over temperature protection.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent
mounting.
Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
38
Unitary Products Group
036-21502-002-A-0303
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
dant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice expansion devices.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
a. Primary and auxiliary high-temperature limit
switches.
c. Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
b. Induced draft motor speed sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
d. The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
ELECTRIC HEATING SECTION
UNIT CONTROLS
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heat-
ers and 20 KW and above on 460 and 575 volt heaters. The
heating section shall have a primary limit control(s) and auto-
matic reset to prevent the heating element system from oper-
ating at an excessive temperature. The heating section
assembly shall slide out of the unit for easy maintenance and
service. Units with Electric Heating shall be wired for a single
point power supply with branch circuit fusing (where
required).
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
d. High-pressure switch.
e. Freeze-protection thermostat, evaporator coil.
UNIT OPERATING CHARACTERISTICS
f. If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
a. Unit shall be capable of starting and running at
125°F outdoor temperature, exceeding maximum
load criteria of ARI Standard 210/240. The compres-
sor, with standard controls, shall be capable of oper-
ation down to 0°F outdoor temperature. Unit shall be
provided with fan time delay to prevent cold air
delivery before heat exchanger warms up (Gas heat
only).
g. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.
Unit control board shall have on-board diagnostics
and fault code display.
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
j.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
k. Control board shall monitor each refrigerant safety
switch independently.
STANDARD LIMITED WARRANTIES
l.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
•
•
•
•
Compressor 5 Years
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
GAS HEATING SECTION
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redun-
Unitary Products Group
39
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER- Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
•
•
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assem-
bling.
•
•
•
•
MANUAL OUTDOOR AIR DAMPER
COIL GUARD KIT - Guard for cooling coil.
HAIL GUARD
FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the out-
door air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pres-
sure differential of 0.5 IWG. A unit-mounted potentiome-
ter shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
•
STAINLESS STEEL HEAT EXCHANGER
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
•
•
•
•
•
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
BAS CONTROLS (CPC, JOHNSON, HONEYWELL,
NOVAR)
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
•
•
•
•
2" PLEATED FILTERS
DISCONNECT SWITCH
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
Subject to change without notice. Printed in U.S.A.