Tripp Lite Power Supply 200703028 User Manual

Owner’s Manual  
SmartOnline  
Rack/Tower Mount On-Line UPS Systems  
Pure Sine Wave Output • 220/230/240V Input/Output  
Not suitable for mobile applications.  
Important Safety Instructions  
2
Installation  
3
Basic Operation  
Troubleshooting  
Battery Replacement  
Storage and Service  
Español  
7
11  
13  
14  
15  
29  
44  
Français  
Ðóññêèé  
1111 W. 35th Street Chicago, IL 60609 USA  
Customer Support: (773) 869-1234 • www.tripplite.com  
Copyright ©2007 Tripp Lite. All rights reserved. SmartOnline is a trademark of Tripp Lite.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Mounting Rack  
Mount your equipment in either a 4-post or 2-post rack or rack enclosure (see next page for 2-  
post mounting). The user must determine the fitness of hardware and procedures before  
mounting. If hardware and procedures are not suitable for your application, contact the  
manufacturer of your rack or rack enclosure. The procedures described in this manual are for  
common rack and rack enclosure types and may not be appropriate for all applications.  
4-Post Mounting  
All UPS models include hardware required to mount in a 4-post rack. Select models include an  
adjustable rackmount shelf kit to provide additional support. If your UPS model does not  
include an adjustable rackmount shelf kit, skip steps 1 and 2.  
A
. Leave  
Connect the two segments of each shelf  
1
B
B
the screws slightly loose so that the shelves  
using the included screws and nuts  
can be adjusted in the next step.  
Adjust each shelf to fit your rack, then mount  
them in the lowest available space of your  
rack with the screws, nuts and washers  
C
2
A
1
2
3
provided  
. Note that the support ledges  
should face inward. Tighten the screws that  
B
connect the shelf segments  
.
C
D
mounting holes of your equipment  
Attach mounting ears  
to the front  
3
E
. The ears should face  
using  
F
the screws provided  
forward.  
4 Using an assistant if necessary, lift your  
equipment and slide it onto the mounting  
shelves. Attach your equipment to the rack by  
G
B
using the appropriate hardware  
through its  
mounting ears and into the rack rails.  
E
D
F
G
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
(continued)  
Installation  
2-Post (Telecom) Mounting  
If you mount 2U UPS models in 2-post racks, they require the addition of a Tripp Lite 2-Post  
Rackmount Installation Kit (model: 2POSTRMKITWM, sold separately). See Installation Kit  
owner’s manual for installation procedure for 2U UPS models.  
Mounting (Tower)  
Your UPS can be mounted in an upright tower  
position with optional base stands sold separately by  
Tripp Lite (Model # 2-9USTAND). When mounting  
the UPS on adjustable base stands, make sure that the  
control panel is toward the top. The control panel may  
be rotated to make it easier to read. Insert a small  
screwdriver or similar tool in the slots on either side of  
the panel, pop it out, rotate it, and pop it back into  
place as shown.  
WARNING!  
All UPS systems are extremely heavy. Use caution when lifting and mounting. User must  
properly stabilize the UPS when lifting and mounting.  
Connection and Start-Up  
1
Connect a user-supplied power cord  
to the UPS input receptacle.  
The power cord should have a plug appropriate  
for your local site's utility outlets. Plug the cord  
directly into a properly grounded, 3-wire, AC  
outlet that does not share a circuit with a heavy  
electrical load (air conditioner, refrigerator, etc.).  
The outlet must have an amp rating equal to or  
greater than the input breaker rating of the UPS.  
INPUT  
Your model may differ.  
1
Note: Once your UPS is plugged in, the fan and all Indicator  
Lights will turn ON. The LINE and LOAD ACTIVE METER  
LEDs will illuminate and the UPS will beep to indicate normal  
operation. However, power is not supplied to the AC outlets  
until the UPS is turned on.  
2
Using the included power cords,  
connect your equipment to the AC  
outlets of the UPS System.  
ACC. SLOT  
INPUT  
BREAKER  
OUTP  
LOAD  
1
LOAD  
2
RS-232  
USB  
CAUTION  
Risk of electric sh  
See top of unit fo  
cautionary markin  
Connect the female plug to your equipment's  
IN  
PHONE  
OUT  
PROTECTION  
EPO  
/
DA  
T
A
AC input. Connect the male plug to any UPS AC  
2a  
connect all your equipment  
outlet  
. Repeat with additional cords to  
Your model may differ.  
2a  
2b  
.
Note: Additional interconnection cords C13 to C14 and C19 to  
C20) are available from Tripp Lite. For more information, call  
773-869-1234.  
ACC. SLOT  
Caution: Your UPS is designed to support computer equipment  
only. You will overload the UPS if you connect devices with  
high power demands such as household appliances or laser  
printers to UPS AC outlets.  
OUTPUT  
LOAD  
1
LOAD  
2
RS-232  
USB  
WARNING  
CONNECT 48 VDC  
BATTERY SYSTEMS ONL  
CONNECTING OTHER  
SYSTEMS WILL VOID  
WARRANTY  
CAUTION  
Risk of electric shock  
See top of unit for  
Y
cautionary markings  
IN  
OUT  
DATA PROTECTION  
EPO  
PHONE  
/
Your model may differ.  
2b  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
(continued)  
Installation
Connection and Start-Up (continued)  
3
Turn the UPS ON:  
• Press the ON/TEST Switch and hold it for  
several seconds until you hear a beep  
• Release the ON/TEST Switch. The ON  
LINE LED will illuminate, and your UPS  
will begin providing power to its AC outlets  
Note: After initial installation of the UPS or after  
prolonged storage, the internal batteries must charge for 2-  
4 hours before the UPS can support connected equipment  
during a power failure.  
3
Optional Connections  
Your UPS will function properly without these  
connections.  
ACC. SLOT  
1
Phone/Network Line  
Suppression  
O
LOAD  
1
LOAD  
2
RS-232  
USB  
CAUTION  
Risk of elec  
u
See top of  
cautionary  
m
IN  
OUT  
DATA PROTECTION  
EPO  
Your UPS has jacks which protect  
against surges on a telephone line or telephone/  
network data line.* Using appropriate  
telephone or network cords connect your wall  
jack to the UPS jack marked “IN.” Connect  
your equipment to the UPS jack marked  
“OUT.” Make sure the equipment you connect  
to the UPS's jacks is also protected against  
surges on the AC line.  
PHONE  
/
1
Your model may differ.  
* Not compatible with PoE (Power Over Ethernet) applications.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
(continued)  
Installation  
Optional Connections (continued)  
2
USB and RS-232 Serial  
Communications  
Use the included USB cable (see  
2a  
) and/or  
OUTPUT  
LOAD  
1
LOAD  
2
2b  
RS-232  
USB  
DB9 serial cable (see  
) to connect the  
WARNING  
CONNECT 48 VDC  
BATTERY SYSTEMS ONL  
CONNECTING OTHER  
SYSTEMS WILL VOID  
WARRANTY  
CAUTION  
Risk of electric shock  
See top of unit for  
Y
cautionary markings  
IN  
OUT  
DATA PROTECTION  
EPO  
communication port of your computer to the  
communication port of your UPS. Install on  
your computer the Tripp Lite PowerAlert  
Software appropriate to your computer's  
operating system. Your UPS may feature  
additional communications ports; these ports  
may be connected to additional computers that  
have PowerAlert Software installed. Consult  
your PowerAlert manual for more information.  
PHONE  
/
2a  
Your model may differ.  
OUTPUT  
LOAD  
1
LOAD  
2
RS-232  
USB  
WARNING  
CAUTION  
Risk of electric shock  
See top of unit for  
cautionary markings  
CONNECT 48 VDC  
BATTERY SYSTEMS ONL  
CONNECTING OTHER  
SYSTEMS WILL VOID  
WARRANTY  
Y
IN  
PHONE  
OUT  
DATA PROTECTION  
EPO  
/
3
EPO Port Connection  
This optional feature is only for those  
applications that require connection to a  
facility's Emergency Power Off (EPO) circuit.  
When the UPS is connected to this circuit, it  
enables emergency shutdown of the UPS's  
2b  
Your model may differ.  
inverter. Using the cable provided, connect the  
OUTPUT  
LOAD  
1
LOAD  
2
3a  
supplied normally closed or normally open  
EPO port of your UPS (see  
) to a user-  
RS-232  
USB  
CAUTION  
Risk of electric shock  
See top of unit for  
cautionary markings  
IN  
OUT  
DATA PROTECTION  
EPO  
switch according to the circuit diagram (see  
PHONE  
/
3b  
suppressor; do not connect a phone line to  
). The EPO port is not a phone line surge  
3a  
Your model may differ.  
this port.  
4
External Battery Connection  
4-5  
Check to ensure that the external batteries  
you are connecting match the voltage listed  
on your UPS's battery connector. All UPS  
models come with a robust internal battery  
system; select models feature connectors that  
accept optional external battery packs (sold  
separately from Tripp Lite) to provide  
3b  
additional runtime. Adding external batteries  
will increase recharge time as well as  
runtime. See the battery pack owner's manual  
for complete installation instructions. Make  
sure cables are fully inserted into their  
connectors. Small sparks may result during  
battery connection; this is normal. Do not  
connect or disconnect battery packs when the  
UPS is running on battery power.  
OUTPUT  
2
USB  
WARNING  
CAUTION  
Risk of electric shock  
See top of unit for  
cautionary markings  
CONNECT 48 VDC  
BATTERY SYSTEMS ONLY  
CONNECTING OTHER  
SYSTEMS WILL VOID  
WARRANTY  
Your model may differ.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
Basic Operation  
Front Panel Switches  
“ON/TEST” Button: This switch controls four separate UPS functions:  
UPS Power ON  
To turn the UPS on, press this button, hold it for several seconds until  
you hear a beep, then release it. The “ON LINE” LED will illuminate.  
UPS Self-Test  
During normal on-line operation, press this button and hold it until  
you hear a beep. This initiates a 10-second self-test of the battery. The  
UPS will shift to battery power (all LEDs will illuminate) for ten  
seconds.  
Alarm Silence  
To silence the UPS “on-battery” alarm, press this button and hold it  
until you hear a beep.  
UPS Cold Start  
To use your UPS as a stand-alone power source when AC power is  
unavailable (i.e. during a blackout), press this button and hold it until  
you hear a beep. The UPS will then provide battery power to its outlets.*  
* The “ON BATT” Indicator Light will be illuminated since your UPS will be operating  
from battery power.  
“OFF” Button: This button turns power OFF at the UPS receptacles.  
Press this switch, hold it until you hear a beep, then release it. The  
UPS will continue charging and the fan will continue to cool internal  
components even after you turn the UPS receptacles off. To turn the  
UPS OFF completely, including the charger, disconnect the UPS’s  
power cord after pressing the “OFF” switch.  
Front Panel Indicator Lights  
“ON LINE” LED: This green light will illuminate constantly to indicate  
the UPS is performing normal on-line operation (filtering and  
resynthesizing incoming AC line voltage to provide pure sine wave  
output). When this light is illuminated, you can monitor the load level  
of your UPS on the “LOAD ACTIVE METER” LEDs.  
“LINE” LED: This green light will illuminate constantly to indicate  
the utility supplied AC line voltage at your wall outlet is nominal. It  
will flash if the line voltage is outside the nominal range (either too  
low or two high). No action is required on your part when the LED  
flashes; the UPS continuously and automatically filters AC line  
power to provide your equipment with pure sine wave AC power,  
regardless of brownout or overvoltage conditions. If this light is off,  
then AC line voltage is not present (blackout) or is at an extremely  
high voltage, and the UPS will provide connected equipment with  
power from battery.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
(continued)  
Basic Operation  
continued  
Front Panel Indicator Lights  
“BYPASS” LED: This yellow light will flash to indicate that the  
UPS’s DC/AC inverter is deactivated and the UPS is in the “Bypass”  
mode. During normal operation this LED will light briefly when the  
unit is plugged in, but if an internal fault or overload occurs this light  
will flash constantly to show that connected equipment will receive  
filtered AC mains power, but will not receive battery power during a  
blackout. In this case, contact Tripp Lite for service.  
“FAULT” LED (select models only): This red light will flash when  
your UPS detects an internal fault (overheating, overvoltages, etc.). If  
the light persists after restarting the UPS, contact Tripp Lite for  
service.  
“LOAD ACTIVE METER” LED: This green light will illuminate  
when your UPS is receiving AC power to indicate that the set of four  
dual-function LEDs is displaying the load level of your UPS.  
“BATT ACTIVE METER” LED: This green light will illuminate  
when your UPS is operating from battery power to indicate that the  
set of four dual-function LEDs is displaying the battery charge level  
of your UPS. Note: the “ON BATT” LED will also be illuminated.  
“OVERLOAD” LED: This red light will illuminate constantly to indicate  
that your UPS’s capacity has been exceeded while it is in on-line operation.  
The UPS alarm will beep continuously. Immediately remove overload  
until light and alarm go off. If you do not immediately remove the  
overload, the UPS will transfer from on-line to bypass operation.  
“BATT LOW” LED: This yellow light will illuminate when your UPS’s  
battery charge level is low. The UPS alarm will beep until either the  
battery charge is depleted or the batteries are adequately recharged.  
“ON BATT” LED: This green light will illuminate constantly to  
indicate that AC line voltage is not present and your UPS is providing  
your equipment with battery power. The UPS will also beep every two  
seconds, unless silenced by the “ON/TEST” Button. When this light  
is illuminated, you can monitor the battery charge level of your UPS  
on the “BATT ACTIVE METER” LEDs.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
(continued)  
Basic Operation  
continued  
Front Panel Indicator Lights  
“REPLACE BATT” LED: This red light will illuminate constantly  
and the UPS alarm will beep every 2 seconds if your UPS’s  
microprocessor detects a battery fault or if your UPS fails the  
automatic self-test (after you turn your UPS ON) and the UPS battery  
is less than fully charged. Let the UPS system charge for at least 12  
hours and perform a self test using the “ON/TEST Button” as described  
on page 7. If the light continues to stay on, contact Tripp Lite for  
service.  
Rear Panel  
Accessory Slot: Remove the small cover panel from this slot to use  
optional accessories to remotely monitor and control your UPS.  
Contact Tripp Lite Customer Support at (773) 869-1234 for more  
information, including a list of available SNMP, network management  
and connectivity products.  
External Battery Pack Connector (configuration varies by model):  
Use to connect optional Tripp Lite Battery Packs for additional  
runtime. Contact Tripp Lite Customer Support at (773) 869-1234 for  
the appropriate Tripp Lite battery pack to connect. Refer to  
instructions available with the Battery Pack for complete connection  
information and safety warnings.  
Fan: The fan cools the UPS’s internal components. It is always on  
when line power is present.  
Input Circuit Breaker Switch: This resettable breaker prevents high  
input current from damaging the UPS or the attached load. If this  
breaker trips, make sure your UPS is connected to AC power of the  
proper voltage before resetting the circuit breaker by pushing the  
breaker switch in.  
Ground Screw: Use this to connect any equipment that requires a  
chassis ground.  
Output Circuit Breakers Switches: These resettable circuit  
breakers protect your UPS from output overload. If one or both  
breakers trip, remove some of the load on the circuit(s) and allow the  
UPS to cool before pressing the breaker switch(es) in to reset.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
(continued)  
Basic Operation  
continued  
Rear Panel  
Input Cord Connection: This IEC320-C20 or IEC320-C14 inlet  
enables the UPS to be connected to an AC power source via a  
user-supplied cord with country-specific plug. See "Connection and  
Start-Up".  
IEC320-C20  
IEC320-C14  
AC Receptacles (Varied by Model): These receptacles provide your  
connected equipment with pure sine-wave AC output from the AC  
line during normal operation and from battery power during blackouts  
and severe brownouts. Power provided at these outlets is filtered to  
protect connected equipment against damaging surges and line noise.  
Select models feature receptacles arranged in numbered load banks,  
as labelled on the unit. Using PowerAlert software and cabling, load  
banks can be individually turned off and on from a remote location,  
allowing users to reset or reboot connected equipment.  
IEC320-C13  
IEC320-C19  
Telephone/Network Protection Jacks: These jacks protect your  
equipment against surges over a telephone line or telephone/network  
data line. Connecting your equipment to these jacks is optional. Your  
UPS will work properly without this connection. Not compatible with PoE  
(Power Over Ethernet) applications.  
Communications  
Communications Ports (USB or RS-232): These ports connect your  
UPS to any workstation or server. Use with Tripp Lite’s PowerAlert  
Software and included cables to enable your computer to  
automatically save open files and shut down equipment during a  
blackout. Also use PowerAlert Software to monitor a wide variety of  
AC line power and UPS operating conditions. Consult your  
PowerAlert Software manual or contact Tripp Lite Customer Support  
for more information. See “USB and RS-232 Serial  
Communications” in the “Optional Connections” section for  
installation instructions.  
Dry contact communications are simple, but some knowledge of  
electronics is necessary to configure them. The DB9 port's pin  
assignments are shown in the diagram. If the UPS battery is low, the  
UPS sends a signal by bridging pins 1 and 5. If utility power fails, the  
UPS sends a signal by bridging pins 8 and 5. To shut the UPS down  
remotely, short pin 3~pin 9 for at least 3.8 seconds.  
EPO (Emergency Power Off) Port: Your UPS features a EPO port  
that may be used to connect the UPS to a contact closure switch to  
enable emergency inverter shutdown. See "Optional Connections."  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Troubleshooting  
The UPS’s control panel lights will turn on in the sequences below to signal that the UPS is  
having operational difficulties.  
Lights (On/Flashing) and Condition  
Solution  
On: REPLACE BATT  
Condition: Replace Battery  
Let the UPS system charge for at least  
12 hours and perform a self test using  
the "ON/Test Switch" as described on  
page 7. If the light continues to stay on,  
contact Tripp Lite for service.  
On: BATT LOW, ON BATT  
Condition: Battery Low  
Prepare for imminent UPS shutdown.  
On: BYPASS, LINE, LOAD, OVERLOAD  
Condition: On Bypass due to Overload  
Reduce the load the UPS supports.  
Flashing: OVERLOAD  
Condition: Short Circuit  
Remove the cause of the short circuit  
from the UPS output.  
On: FAULT, 100%  
Condition: Battery Voltage too High  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
On: FAULT, BYPASS, LINE, 50%  
Condition: On Bypass due to  
High Output Voltage  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
On: FAULT, BYPASS, LINE  
Flashing: 50%  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
Condition: On Bypass due to  
Low Output Voltage  
On: FAULT, BYPASS, LINE, 25%  
Condition: On Bypass due to High  
Bus Voltage  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
On: FAULT, BYPASS, LINE  
Flashing: 25%  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
Condition: On Bypass due to Low  
Bus Voltage  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
(continued)  
Troubleshooting  
Lights (On/Flashing) and Condition  
Solution  
On: BYPASS, LINE  
Flashing: FAULT  
Condition: On Bypass due to High  
Internal Temperature  
Check the UPS to be sure that there is  
adequate space for air to circulate near  
the vents and that the fan is working  
properly. Restart the UPS.  
Flashing: LINE  
Condition: Input Abnormal  
This indicates that utility power is too high  
or low for the UPS to operate in BYPASS  
mode, so if an inverter failure occurs,  
the UPS will deliver no output.  
On: FAULT, 50%  
Flashing: LINE  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
Condition: No Output due to High  
Output Voltage and Abnormal Input  
On: FAULT  
Flashing: LINE, 50%  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
Condition: No Output due to Low  
Output Voltage and Abnormal Input  
On: FAULT, 25%  
Flashing: LINE  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
Condition: No Output due to High  
Bus Voltage and Abnormal Input  
On: FAULT  
Flashing: LINE, 25%  
Restart the UPS. If the problem persists,  
contact Tripp Lite for repairs.  
Condition: No Output due to Low  
Bus Voltage and Abnormal Input  
Flashing: LINE, FAULT  
Condition: No Output due to High  
Internal Temperature and Abnormal  
Input  
Check the UPS to be sure that there is  
adequate space for air to circulate near  
the vents and that the fan is working  
properly. Restart the UPS. If the problem  
persists, contact Tripp Lite for repairs.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
Battery Replacement  
Under normal conditions, the original batteries in your UPS will last many years. See  
"Important Safety Instructions" before replacing batteries. The batteries are designed for hot-  
swap replacement (i.e. leaving the UPS in ON mode), but some qualified service personnel may  
wish to put the UPS in the OFF mode and disconnect equipment before proceeding.  
Procedure  
1
Remove Front  
Panel  
2
Disconnect  
Batteries  
1
2
6
5
3
Remove/Dispose of  
Batteries  
4
5
Add Batteries  
Connect Batteries  
Attach connectors: black-  
to-black and red-to-red.  
6
Replace Front  
Panel  
3
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
Storage and Service  
Storage  
First turn your UPS OFF: press the “OFF” switch to turn power off at the UPS outlets, then  
disconnect the power cord from the wall outlet. Next, disconnect all equipment to avoid battery  
drain. If you plan on storing your UPS for an extended period of time, fully recharge the UPS  
batteries once every three months by plugging the UPS into a live AC outlet and letting the  
UPS charge for 4-6 hours. If you leave your UPS batteries discharged for an extended period  
of time, they may suffer permanent loss of capacity.  
Service  
If returning your UPS to Tripp Lite, please carefully pack the UPS using the ORIGINAL  
PACKING MATERIAL that came with the unit. Enclose a letter describing the symptoms of the  
problem. If the UPS is within the 2 year warranty period, enclose a copy of your sales receipt.  
Regulatory Compliance Identification Numbers: For the purpose of regulatory compliance certifications and identification, your Tripp  
Lite product has been assigned a unique series number. The series number can be found on the product nameplate label, along with  
all required approval markings and information. When requesting compliance information for this product, always refer to the series  
number. The series number should not be confused with the marking name or model number of the product.  
The policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
1111 W. 35th Street, Chicago, IL 60609 USA  
773.869.1234 (USA) • 773.869.1212 (International)  
200703028 93-2486_EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Teledyne Oxygen Equipment LXT 220 User Manual
Texas Instruments Network Card SLAU245 User Manual
Toshiba Flat Panel Television 26LV61K User Manual
Toshiba Personal Computer PTA42 User Manual
Transcend Information Computer Drive V33p User Manual
TRENDnet Wireless Office Headset 113004 User Manual
Tunturi Tent C401 User Manual
Ultra Start Remote Starter 3295 User Manual
VocoPro DVD Player DVX 680K User Manual
Vulcan Hart Fryer 1GR45M User Manual