E6581402c
TOSVERT VF-FS1 series
®
BACnet option unit
Instruction Manual
NOTICE
1. Make sure that this instruction manual is delivered to the end user of BACnet® option
unit.
2. Read this manual before installing or operating the BACnet® option unit. Keep it in a
safe place for reference.
3. All information contained in this manual are subject to change without notice. Please
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
Limitation of use
Safety precaution
Never use this unit with any device other than TOSVERT VF-FS1 series inverters. Doing so may cause
an accident.
Handling in general
Danger
Never disassemble, modify or repair the product.
Disassembling the product may cause electric shocks, fire or injuries.
For repairs, call your sales/repair agency.
Disassemble
Never
Do not open the front cover on the inverter while the inverter power is on.
It may lead to electric shocks.
Do not remove this option from VF-FS1 while the power is on.
It may lead to electric shocks.
Do not put or insert foreign objects such as waste cable, bars or wires into the product.
Prohibited
It may lead to electric shocks or fire.
Do not splash water over the product, and do not wipe the body with a wet cloth.
It may lead to electric shocks or fire.
Turn off the power immediately in case of any abnormalities such as smoke, smell or
abnormal noise.
Neglect of these conditions may lead to fire.
For repairs, call your sales/repair agency.
Mandatory
Mandatory
Do not touch the sharp portions (such as leads of parts on the board, the corner of board,
or etc.) on this option.
It may lead to injuries.
Warning
This option is an electrostatic discharge sensitive device. Handle it, where the
environment is protected against electrostatic electricity.
Otherwise, permanent damage to device will result.
Transportation and installation
Danger
Do not apply a dropping shock or other physical shocks.
Otherwise, damage or malfunction will result.
Do not install or operate the inverter if it is damaged or any part of it is missing.
Operating a defective inverter may lead to electric shocks or fire.
For repairs, call your sales/repair agency.
Prohibited
Do not put any flammable material near the product.
It may catch fire due to the product sparking in the case of a malfunction.
Use this product under the environmental conditions prescribed in the instruction manual.
Usage it under any other conditions may result in malfunction.
An emergency stop device must be installed that fits with system specifications
(e.g. shut off input power then engage mechanical brake).
Operation cannot be stopped immediately by the inverter or this unit alone, thus risking an
accident or injuries.
Install this option into VF-FS1 and secure it by tightening the terminal board fixing
screws to the specified torque. Otherwise, it may cause the product falling, the damage,
or malfunctions.
Mandatory
When installing this option, do not touch its sharp portions such as leads of parts on the
board, the corner of board or etc.
It may lead to injuries.
- 2 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
Wiring
Warning
Electrical construction work must be done by a qualified expert.
Connection of input power by someone who does not have expert knowledge may result
in electric shocks or fire.
Turn off input power before wiring.
Wait at least 10 minutes and make sure that the charge lamp (on the inverter unit) is no
longer lit. Otherwise, it may lead to electric shocks.
Tighten the screws on the terminal blocks to the specified torque when connecting cables
to terminal blocks.
Mandatory
Otherwise, it may lead to fire.
Operations
Danger
Do not pull on the cable and connector.
It may cause damage or malfunctions.
Prohibited
Mandatory
Use this option under the environment specified in the instruction manual.
Usage under the environment other than them may cause damages or malfunctions or
an accident.
Use an additional safety device with your inverter or system to prevent a serious
accident due to the unit malfunctions.
Usage without an additional safety device may cause an accident.
Warning
Set up ³Communication error trip function (see below)´ to stop the inverter when the
option unit is deactivated by an unusual event such as an operating error, power outage,
failure, etc.
- Communication error trip time (Between the inverter and option board) (f803)
- Network timeout (f892)
®
(See the VF-FS1 BACnet Communication Function Manual for details)
Mandatory
Disposal
Deactivated option unit may cause an accident, if the ³Communication error trip
function´ is not properly set up.
Make sure that the operation signals are STOP before resetting inverter¶s fault. The
motor may suddenly start and that may result in injuries.
Warning
If you dispose off this unit, have it done by a specialist in industrial waste disposal*.
Improper disposal may result in explosion of capacitors or produce noxious gases,
resulting in injuries.
(*) Persons who specialize in the processing of waste and known as ³Industrial Waste
Product Collectors and Transporters´ or ³Industrial Waste Disposal Persons.´ If the
collection, transport and disposal of industrial waste is done by someone who is not
licensed for that job, it is a punishable violation of the law (Laws in regard to cleaning and
processing of waste materials).
Mandatory
Notes on operation
Notes
Avoidꢀinstalling in a place where ambient temperature or/and humidity change sharply.
Keep the transmission cable separate from the power cable of the inverter to prevent the
inverter from malfunctioning due to electromagnetic noise.
Ground of SCR terminal on this option at the grounding terminal separated from those of
inverters and motors. It may cause malfunction due to noise.
- 3 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
Preface
®
Thank you for purchasing the ³BACnet option (BCN002Z)´ for TOSVERT VF-FS1 inverter. By
Installing this board into the VF-FS1, data communication can be made with a host computer or
other device via BACnet network.
Before using this unit, carefully read this instruction manual in order to completely and correctly
®
utilize excellent performance of this unit. Besides this instruction manual, the ³VF-FS1 BACnet
®
Communication Function Manual´ which includes the contents to install into BACnet network is
prepared. If it is required, please contact with our branch offices, sales offices or web site
(³VF-FS1 BACnet® Communication Function Manual´: E6581404)
After reading this instruction manual, please keep it handy for future reference.
*
BACnet is a registered trademark of ASHRAE.
- Part numbering
BCN
002
Z
0
±
Revision number
Cable length ( ³Z´ means ³without cable´ )
Model number of BACnet option
Symbol of BACnet option
- Accessory check list
BACnet communication option is shipped together with the following accessories. On opening the
packing case, check to see if the following accessories are contained or not.
(1) BACnet option board (BCN002Z)
Board (BCN002Z) ............................................1 pcs
Connector: MSTB2.5/4-ST-5.08
Manufactured by PHOENIX CONTACT
(2) Instruction manual
English (E6581402).......................................1 copy (This book)
Instruction
Manual
(3) Cabling label & Name plate ............................1 sheet
(1 cabling label and 2 name plates)
(4) Insulating sheet ...............................................1 sheet
- 4 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
Table of Contents
1. Overview 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6
2. Names and functions㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6
2.1. Outline㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6
2.2. Use of RS485 communication port㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 6
2.3. LED indicator 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 7
3. Installation and Setup 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 8
3.1. Installation method 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 8
3.2. Description of terminals 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 9
3.3. Network cable connection 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 10
3.4. Network configuration㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 10
3.5. Wiring of a control terminal 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 11
4. Parameters 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 12
4.1. Communication parameters 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 12
5. Specifications 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 13
6. Warranty 㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯㨯 14
- 5 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
1. Overview
The BACnet (BCN002Z) interface allows the VF-FS1 inverter to be connected into a BACnet network.
BACnet MS/TP supports a maximum of 32 nodes for one segment.
2. Names and functions
The drawing below shows names and functions of main parts.
2.1. Outline
Connector
Input terminal
SINK/SOURCE
VIB/PTC select SW
Terminal board fixing
screw hole
(M3 screw)
Termination
resistor SW
Communication
condition monitor LED
B
A
GND SCR
Optional RS485 communication port
RS485 communication option can be
used. However it makes BACnet
Communication be disabled.
Detachable terminal
Network
communication
2.2. Use of RS485 communication port
Serial communication (2-wire RS485) option can be used. However, while it is connected, the
internal communication line is switched to RS485 then the communication via BACnet network is
disabled. In this case, communication error trip time (f803) is also active. Use RS485 serial
communication option specified by Toshiba.
- 6 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
2.3. LED indicator
The option has two LEDs. Those functions are below table.
COM
Green
OFF
OFF
ON
ERR
Red
OFF
2s
1s
A
2s
1s
1s
1s
B
C
D
E
F
State
A
Comment
LEDs
Green LED : OFF
BACnet board failure
Red LED : Flashing 5 times in 1 second
Green LED : OFF
Red LED
:
Communication loss detected. Confirm the
network condition and connection of the cable.
B
C
D
Flashing 3 times in 2 seconds, Off for 1
second
Green LED : ON
Red LED : OFF 0.5s, ON 0.5s
Green LED :
Invalid configuration detected (ADR > max
master), or an option is connected to RJ45.
Flashing 3 times in 2 seconds, Off for 1
second
Waiting for Auto baud rate detection
Red LED : OFF
Green LED : Flashing Intermittent Green
Red LED : ---
Green LED : ---
E
F
Valid message received for this node
Invalid message received (any node)
Red LED : Flashing Intermittent Red
- 7 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
3. Installation and Setup
3.1. Installation method
Install the BACnet communication option to VF-FS1 as follows.
(1) Turn off the input power of VF-FS1 and wait for at least 10 minutes and then check that the
CHARGE lamp on VF-FS1 is no longer lit.
(2) Open the VF-FS1 front cover, remove the terminal board fixing screw and take off the VF-FS1
standard terminal board.
(Be careful not to lose the terminal board fixing screw when removed since it may be used again.)
(3) Perform wiring an inverter before installing BACnet communication option.
(4) Please attach the insulating sheet in VF-FS1.
(Fix to the terminal board fixing screw hole and PWB catch pin.)
(5) Install the BACnet communication option over the insulating sheet and secure it with the board
fixing screw (tightening torque of M3 tapping screw: 0.7 to 0.8Nm).
(6) Set up the SW of the board with the input terminal for sink or source.
(7) Stick the cabling label for BACnet communication option on the standard cabling label stuck on
the reverse side of the VF-FS1 front cover. And stick the BACnet communication option
nameplate near the standard nameplate. (Be careful not to cover slits on the VF-FS1 enclosure.
N.B.: To install or remove the terminal board, make it slide in or out in parallel with board.
VF-FS1 unit
Board catching pin
Cabling label position
Terminal board fixing screw
(M3 screw tightening torque: 0.7 to 0.8Nm)
Board fixing screw hole
Stick the BCN002Z nameplate
like bellow figure.
BCN002Z
Example
VF-FS1 name plate
Insulating seat
(attached)
BACnet communication option
(BCN002Z)
VF-FS1 Standard terminal board
- 8 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
3.2. Description of terminals
<Control terminals specification>
Terminal
Function
symbol
Electrical specifications
Internal circuits
B
A
GND
Communication signal (+)
Communication signal (-)
Signal common
47k
4.7k
B
A
BACnet communication
4.7k
47k
signal
EIA-485
Shield terminal.
Connect to network ground.
SCR
TERM
GND
SCR
120
SW4
P24
SINK SOURCE
Multifunctional programmable
contact input.
F
P24
No voltage contact input
24VDC, 5mA or less
PTC
SINK/SOURCE can be
selected with SW.
820
4.7k
N.B. Use contact parts for low
current.
F, R
CC
R
0 to 10VDC input
15k
15k
3.3k
Multifunction programmable
analog input.
with internal pull-up resistor
for PTC
Using this terminal as PTC
input, set SW2 to PTC side
and set the parameters
(f645 and f646) to
proper value.
P10
VIB
VIB
VIB
PTC
Control circuit¶s equipotential
terminal
CC
P24
PTC
P24
P24
24 VDC power supply output
24VDC-50mA
FLA
FLB
1c contact
30VDC-0.5A
250VAC-1A (cosIꢀ=1㧕
250VAC-0.5A (cosIꢀ=0.4)
FLA
FLB
FLC
Multifunctional programmable
relay contact outputs
Ry
FLC
Danger
Do not change switches settings while the power is on.
It may lead to electric shocks or damage.
Prohibited
Mandatory
Turn off the motor operation signals before setting the parameter and the switch
(SW), when changing the VIB function. Otherwise, the motor may suddenly start
and that may result in injuries.
- 9 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
3.3. Network cable connection
Connect the BACnet network cable to communication option as follows.
Title
Wire type
Description
Shielded twisted cable
Characteristic impedance
Distributed impedance between
conductors
Between 100 and 130 ohm
Less than 100pF per meter
Distributed impedance between Less than 200pF per meter
conductors and shield
Foil or braided shields are acceptable.
1200 meters with AWG18 (0.8mm2)
Length of an MSTP segment
Cable sheath should be peeled off by about 7mm.
For wiring work, use a flat blade screwdriver with a 0.6mm thick and
3.5mm width blade.
mm
⿆
Tightening torque for the terminal block is 0.5Nm.
* Fix a cable so that a communication connector may be not taken the weight of wire.
3.4. Network configuration
Make up the network as follows.
- Transmission/reception signals (A, B)
Make up the communication path by connecting all transmission/reception data cables.
- Signal common (GND)
GND is the signal common.
- Grounding the shield of cable (SCR)
Connect the all shield lines of network cable. The shield shall be grounded at one end only prevent
currents from being created.
- Termination resistor
A termination resistance of 120 ohms plus or minus 5% shall be connected at each of the two ends
of the segment medium. This option has a termination resistor, so if use, set up the termination
resistor SW. (Refer to 2.1 Outline)
At least one set, and no more than two sets, of network bias resistors shall exist for each segment.
This option has local bias resistors.
TERM
SW4
B
B
B
A
A
A
120
120
Termination
GND
SCR
GND
SCR
GND
SCR
Termination
4.7k
4.7k
Communication
cable
Communication
cable
+5
+5
510
510
47k
47k
Node with network
bias resistors
Node without
bias resistors
Node with local bias resistors
This option board
N.B.:Do not connect the SCR terminal to the power ground of inverters or other units.
Keep the network cables 20cm or more separate from the power cables to prevent from
malfunctioning due to electromagnetic noise.
- 10 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
3.5. Wiring of a control terminal
Observe the following when wiring.
- Use 0.3 to 1.5mm2 solid/stranded wire (AWG 22 to 16) for control cables.
- Remove the sheath of a cable about 7mm (6mm for FLA, FLB, FLC and G/E) from the end of cable.
- Use a flat-headed screwdriver with its blade 0.6mm in thickness and 3.5mm in width.
- Screw tightening torque for the terminal block screws should be 0.5 to 0.6Nm.
N.B.: Keep the control signal cables 20cm or more separate from the power cables to prevent from
malfunctioning due to electromagnetic noise.
N.B.: Provide an inter-lock system stated in below, when using a programmable controller that has
the open collector output.
When the programmable controller is turned off with the inverter is on, the difference between
each control power potential will cause wrong signals to the inverter as shown in below figure.
Provide an inter-lock so that the programmable controller cannot be turned off when the
inverter power is alive.
Programmable controller
VF-FS1 + BCN002Z
+24V
Input terminal
External
+24V supply
Fuse blowout
detection
circuit
Inverter
internal +24V
COM
Fuse
- 11 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
4. Parameters
4.1. Communication parameters
Set up the inverter parameters as follows. To update, reset the power of inverter. If these
parameters are not set to correct value, this unit can not work normally.
Shipment
setting
Title
Function
Description
0: Terminal board
BACnet
2
cmod Command mode selection 1: Operation panel
0
2: Serial communication
1: VIA
2: VIB
3: Operation panel
4: Serial communication
Frequency setting mode
selection 1
fmod
1
4
5: UP/DOWN from external contact
Set ³1: 19200bps´ (default).
Set ³1: Even´ (default).
f800 Communication rate
f801 Parity
1
1
1
1
Set communication time out period.
The way of stop is selected by f603.
Set ³4: BACnet protocol´
f803 Communication error trip time
0
0
---
4
f829 Communication protocol
0: Inverter stop, communication command,
frequency mode open (by cmod,
fmod)
Operation at communication 1: None (continued operation)
f851
0
---
error by disconnection
2: Deceleration stop
3: Coast stop
4: Communication error (err5 trip)
or Network error (err8 trip)
f890 Address
Set node address
0
0
---
---
0: AUTO adaptive
1: 9600
2: 19.2kbps
f891 Network baud rate
3: 38.4kbps
4: 76.8kbps
Over 5 is AUTO adaptive.
0: No action
Unit 0.1sec, Setting range : 1 to 65535
f892 Network Time-Out
0
---
f893
0
0
---
---
Instance number
f894
Instance No.= f893 x 1000 + f894
Setting range : 0 to 127
Over 127 is limited 127.
Setting range : 0 to 100
Over 100 is limited 100.
f895 MaxMaster
0
0
---
---
f896 MaxInfoFrame
Warning
Set up ³Communication error trip function (f803, see the inverter instruction
manual for details)´ to stop the inverter when this option unit is deactivated by an
unusual event such as tripping, an operating error, power outage, failure, etc.
Deactivated option unit may cause an accident, if the ³Communication error trip
function´ is not properly set up.
Mandatory
- 12 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
5. Specifications
< Environmental specification >
Item
Specification
Service environment
Operation temperature
Storage temperature
Relative humidity
Vibration
Conforms to VF-FS1
Conforms to VF-FS1
-25 to +65㷄
20 to 93% (free from condensation and vapor)
5.9m/s2 (0.6G) or less (10 to 55 Hz) (To be complied with JIS C0040.)
< BACnet option terminal specification >
Item
Specification
Note
Communication between
inverter
Applicable model
Only one board connection is
available.
VF-FS1
Communication method MODBUS-RTU
Set the inverter parameter
(refer to section 4.1)
Baud rate
Parity
19200bps
Even number
Control power supply
5 VDC
2 circuits (F,R)
Slide switch (SW) enable to select
logical configurations (Source/Sink).
Nothing
Supplied from inverter
Not isolated
Logic input terminal
Logic output terminal
1 circuit (FL):30VDC-0.5A
250VAC-1A (cosIꢀ=1㧕
250VAC-0.5A (cosIꢀ=0.4)
1 circuit (VIB): 10VDC (RIN = 30kohm)
Nothing
Relay contact output
terminal
Isolated
Analog input terminals
Analog output terminals
Power supply output
Not isolated
24VDC-50mA
Current limit function
< BACnet option network specification >
Item
Specification
Data link / Physical layers
Node type
Master-Slave / Token Passing (MS/TP)
Master node
Maximum node
32 nodes per segment
9600bps, 19.2kbps, 38.4kbps, 76.8kbps
supports auto-baud detection
Local bias resistors are mounted.
Termination resistor (120 ohm) can be select by SW.
Detachable terminal block 4-pole (5.08mm pitch)
Manufacturer: PHOENIX CONTACT
Communication baud rate
Bias resistor and termination
Terminal block
Type-Form : MSTB 2,5/4-ST-5.08
- 13 -
Download from Www.Somanuals.com. All Manuals Search And Download.
E6581402c
6. Warranty
Any part of BACnet communication option that is proved to be defective will be repaired free of
charge under the following conditions:
1. This product will be repaired free of charge, if problem/fault occurs under normal handling
within one year of delivery and is caused obviously by a design or manufacturing defect.
2. The warranty applies only to the delivered product.
3. For the following kinds of failure or damage, the repair cost shall be borne by the customer
even within the warranty period.
i) Failure or damage caused by improper or incorrect use or handling, or unauthorized repair
or modification of the inverter.
ii) Failure or damage caused by the unit falling or an accident during transportation after the
purchase.
iii) Failure or damage caused by fire, salty water or wind, corrosive gas, earthquake, storm or
flood, lightning, abnormal voltage supply, or other natural disasters.
iv) Damage due to the use of BACnet communication option for non-intended purposes.
4. If an additional warranty is provided then those conditions will also apply.
- 14E -