Superior Indoor Fireplace GHC GRD 5500 User Manual

INSTALLATION  
INSTRUCTIONS  
B-VENT  
GHC-5500/6500 AND  
RETAIN THESE INSTRUCTIONS  
FOR FUTURE REFERENCE  
GRD-5500/6500 SERIES  
B-VENTED GAS FIREPLACES  
This appliance may be installed in an aftermar-  
ket permanently located, manufactured home  
(USA only) or mobile home, where not prohib-  
ited by local codes. This appliance is only for  
use with the type of gas indicated on the rating  
plate. This appliance is not convertible for use  
with other gases, unless a certified kit is used.  
P/N 700,027M REV. E 07/2004  
MODELS  
Millivolt  
Electronic  
Models  
GHC-5500N  
GHC-5500P  
GRD-5500N  
GRD-5500P  
GHC-6500N  
GHC-6500P  
GRD-6500N  
GRD-6500P  
Models  
GHC-5500NE-2  
GHC-5500PE-2  
GRD-5500NE-2  
GRD-5500PE-2  
GHC-6500EN  
GHC-6500EP  
GRD-6500EN  
GRD-6500EP  
For GHC/GRD-5500  
WH Report No. J20046562  
AVERTISSEMENT: ASSUREZ-VOUS DE BIEN SUIVRE  
LESINSTRUCTIONSDONNÉDANSCETTENOTICEPOUR  
RÉDUIRE AU MINIMUM LE RISQUE D'INCENDIE OU  
POUR ÉVITER TOUT DOMMAGE MATÉRIEL, TOUTE  
BLESSURE OU LA MORT.  
For GHC/GRD-6500  
WH Report No. J20046564  
WARNING:IFTHEINFORMATIONINTHISMANUAL  
IS NOT FOLLOWED EXACTLY, A FIRE OR EXPLO-  
SION MAY RESULT CAUSING PROPERTY DAM-  
AGE, PERSONAL INJURY OR LOSS OF LIFE.  
POURVOTRESÉCURITÉ: Nepasentreposerniutiliser  
d'essencenid'autrevaperursouliquidesinflammables  
dans le voisinage de cet appareil ou de tout autre  
appareil.  
FOR YOUR SAFETY: Do not store or use gasoline  
or other flammable vapors or liquids in the vicin-  
ity of this or any other appliance.  
POUR VOTRE SÉCURITÉ: Que faire si vous sentez une  
odeur de gaz:  
FOR YOUR SAFETY: What to do if you smell gas:  
• Ne pas tenter d'allumer d'appareil.  
• Netouchezàaucuninterrupteur. Nepasvousservir  
des téléphones se trouvant dans le batiment où  
vous vous trouvez.  
• Evacuez la piéce, le bâtiment ou la zone.  
• Appeflez immédiatement votre fournisseur de gaz  
depuis un voisin. Suivez les instructions du  
fournisseur.  
• DO NOT light any appliance.  
• DO NOT touch any electrical switches.  
• DO NOT use any phone in your building.  
• Immediately call your gas supplier from a  
neighbor’s phone.  
Follow your gas suppliers instructions.  
• Ifyourgassuppliercannotbereached, callthe  
fire department.  
• Si vous ne pouvez rejoindre le fournisseur de gaz,  
appelez le service dos incendies.  
Installation and service must be performed by a  
qualified installer, service agency or the gas  
supplier.  
L'installationetservicedoitêtreexécutéparunqualifié  
installer, agence de service ou le fournisseur de gaz.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Donotusetheseappliancesifanyparthasbeen  
under water. Immediately call a qualified, pro-  
fessional service technician to inspect the ap-  
pliance and to replace any parts of the control  
system and any gas control which have been  
under water.  
These appliances must not be connected to a  
chimney or flue serving a separate solid fuel  
burning appliance.  
AVERTISSEMENT: SURVEILLER LES  
ENFANTS. GARDER LES VÊTEMENTS,  
LES MEUBLES, L'ESSENCE OU AUTRES  
LIQUIDES À VAPEUR INFLAMMABLES  
LIN DE L'APPAREIL.  
Do not place clothing or other materials on or  
near this appliance.  
Ne pas se servir de cet appareil s'il a été plongé  
dans l'eau, complètement ou en partie. Appeler  
un technicien qualifié pour inspecter l'appareil et  
remplacer toute partie du système de contrôle et  
toute commande qui ont été plongés dans l'lau.  
WARNING: FAILURE TO COMPLY WITH  
THEINSTALLATIONANDOPERATINGIN-  
STRUCTIONS PROVIDED IN THIS DOCU-  
MENTWILLRESULTINANIMPROPERLY  
INSTALLED AND OPERATING APPLI-  
ANCE, VOIDING ITS WARRANTY. ANY  
CHANGE TO THIS APPLIANCE AND/OR  
ITS OPERATING CONTROLS IS DANGER-  
OUS. IMPROPERINSTALLATIONORUSE  
OF THIS APPLIANCE CAN CAUSE SERI-  
OUS INJURY OR DEATH FORM FIRE,  
BURNS, EXPLOSION OR CARBON MON-  
OXIDE POISONING.  
WARNING: THIS APPLIANCE MAY ONLY  
BE FITTED WITH DOORS CERTIFIED FOR  
USE WITH THE APPLIANCE.  
AVERTISSEMENT: POUR UTILISATION  
UNIQUEMENT AVEC LES PORTES EN  
VERRE CERTIFIÊES AVEC L'APPAREIL.  
This appliance may be installed in an af-  
termarket permanently located, manufac-  
tured home (USA only) or mobile home,  
where not prohibited by local codes. This  
appliance is only for use with the type of  
gas indicated on the rating plate. This ap-  
pliance is not convertible for use with  
other gases, unless a certified kit is used.  
These appliances are equipped with an inte-  
gral combustion air door and actuator arm.  
Combustion air kits are optional. Install as  
shown in step 7 on page 11.  
LOCATION  
Cet appareil peut être installé dans un  
maison préfabriquée (É.-U. seulement)  
ou mobile déjà installée à demeure si  
les réglements locaux le permettent.  
Cet appareil doit être utilisé uniquement  
avec les types de gaz indiqués sur la  
plaque signalétique. Ne pas l'utiliser  
avec d'autres gaz sauf si un kit de con-  
version certifié est installé.  
Carbon Monoxide Poisoning: Early signs of  
carbon monoxide poisoning are similar to the  
fluwithheadaches,dizzinessand/ornausea.If  
you have these signs, obtain fresh air immedi-  
ately. Turn off the gas supply to the appliance  
and have it serviced by a qualified profes-  
sional, as it may not be operating correctly.  
WARNING: B-VENTAPPLIANCESARENOT  
DESIGNED TO OPERATE IN NEGATIVELY  
PRESSUREDENVIRONMENTS(PRESSURE  
WITHIN THE HOME IS LESS THAN PRES-  
SURES OUTSIDE). SIGNIFICANT NEGA-  
TIVELY PRESSURED ENVIRONMENTS  
CAUSED BY WEATHER, HOME DESIGN,  
OR OTHER DEVICES MAY IMPACT THE  
OPERATION OF THESE APPLIANCES.  
NEGATIVE PRESSURES MAY RESULT IN  
POOR FLAME APPEARANCE, SOOTING,  
DAMAGE TO PROPERTY AND/OR SEVERE  
PERSONAL INJURY. DO NOT OPERATE  
THESEAPPLIANCESINNEGATIVELYPRES-  
SURED ENVIRONMENTS.  
Millivolt appliances may be fitted at time of  
manufacture with either a Robertshaw millivolt  
gascontrolvalveorRobertshawelectronic gas  
control valve. Both valves have been tested  
with and approved for use with these appli-  
ances and are listed accordingly.  
Typical Locations  
Figure 1  
In selecting the location, the aesthetic and func-  
tional use of the appliance are primary concerns.  
However, ventsystemroutingtotheexteriorand  
access to the fuel supply are also important. Due  
to high temperatures the appliance should be  
locatedoutoftrafficandawayfromfurnitureand  
draperies. Consideration should be given to traf-  
fic ways, furniture, draperies, etc., due to el-  
evatedsurfacetemperatures.Thelocationshould  
also be free of electrical, plumbing or other  
heating/air conditioning ducting.  
A ¹⁄₈" NPT test gage connection is provided on  
either gascontrolvalveadjacenttotheoutletto  
the main burner.  
Minimum inlet gas pressure to the appliance is  
4.5 inches water column (1.12 kPa) for natural  
gas and 11 inches water column (2.74 kPa) for  
propane for the purpose of input adjustment.  
Maximum inlet gas supply pressure to the  
appliance is 10.5 inches water column (2.61  
kPa) for natural gas and 13.0 inches water  
column (3.23 kPa) for propane.  
WARNING: CHILDREN AND ADULTS  
SHOULD BE ALERTED TO THE HAZARDS  
OFHIGHSURFACETEMPERATURES.USE  
CAUTION AROUND THE APPLIANCE TO  
AVOID BURNS OR CLOTHING IGNITION.  
YOUNG CHILDREN SHOULD BE CARE-  
FULLY SUPERVISED WHEN THEY ARE IN  
THE SAME ROOM AS THE APPLIANCE.  
The appliance should be mounted on a fully  
supported base extending the full width and  
depth of the unit. The appliance may be located  
on or near conventional construction materials.  
However, if installed on combustible materials,  
suchascarpeting, vinyltile, etc., ametalorwood  
barrier covering the entire bottom surface must  
be used.  
The appliance must be isolated from the gas  
supply piping system (by closing its individual  
manual shut-off valve) during any pressure test-  
ing of the gas supply piping system at test  
pressuresequaltoorlessthan¹⁄psig(3.5)kPa).  
These appliances may be used for bedroom  
installations in the United States and are listed  
accordingly. These units may not be installed  
in bedrooms in Canada.  
The appliance and its individual shut-off valve must  
bedisconnectedfromthegassupplypipingsystem  
during any pressure testing of that system at pres-  
sures in excess of ¹⁄₂ psig (3.5 kPa).  
WARNING: DO NOT PLACE CLOTHING  
OR OTHER FLAMMABLE MATERIALS  
ON OR NEAR THIS APPLIANCE.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPLIANCE SPECIFICATIONS GHC/GRD-5500  
GHC-5500  
GRD-5500  
4 ¹⁄₄"  
4 ¹⁄₄"  
(108 mm)  
(108 mm)  
6 ¹⁄₂"  
(165 mm)  
21"  
(533 mm)  
33 ¹⁄₄"  
34 ¹⁄₂"  
(845 mm)  
34 ¹⁄₂"  
(876 mm)  
(876 mm)  
21"  
(533 mm)  
33 ¹⁄₄"  
(845 mm)  
1 ¹⁄₂"  
(38 mm)  
7 "  
(178 mm)  
35 ⁷⁄₈" (911 mm)  
35 ⁷⁄₈" (911 mm)  
Front View  
Front View  
Gas Inlet  
Line  
Gas Inlet  
Line  
Combustion  
Air Inlet  
Combustion  
Air Inlet  
38 ³⁄₄"  
38 ³⁄₄"  
10 "  
9 "  
(984 mm)  
(984 mm)  
(254 mm)  
(229 mm)  
10 ¹⁄₂"  
9 ¹⁄₂"  
(267 mm)  
(241 mm)  
4 ¹⁄₂"  
4 ¹⁄₂"  
8 ¹⁄₂"  
8 ¹⁄₂"  
(114 mm)  
(114 mm)  
8 ¹⁄₂"  
8 ¹⁄₂"  
(216 mm)  
(216 mm)  
(216 mm)  
(216 mm)  
16" (406 mm)  
Left View  
15" (381 mm)  
Left View  
16" (406 mm)  
Right View  
15" (381 mm)  
Right View  
Top Spacers (4)  
Top Spacers (4)  
27 ³⁄₄" (705 mm)  
27 ³⁄₄" (705 mm)  
6 ¹⁄₂"  
6 ¹⁄₂"  
(165 mm)  
(165 mm)  
15 "  
15 "  
(381 mm)  
(381 mm)  
1"  
1"  
(25.4 mm)  
(25.4 mm)  
35 ⁷⁄₈" (911 mm)  
35 ⁷⁄₈" (911 mm)  
Top View  
Top View  
Figure 2  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPLIANCE SPECIFICATIONS GHC/GRD-6500  
GHC-6500  
GRD-6500  
4 ¹⁄₄"  
4 ¹⁄₄"  
(108 mm)  
(108 mm)  
6 ³⁄₈"  
6 ¹⁄₂"  
(162 mm)  
(165 mm)  
21 ¹⁄₂"  
21"  
(546 mm)  
(533 mm)  
32" (813 mm)  
36 ¹⁄₄"  
36 ¹⁄₄"  
16 ¹⁄₄"  
21"  
(533 mm)  
(921 mm)  
(921 mm)  
(413 mm)  
37 ³⁄₄" (959 mm)  
39 ⁷⁄₈" (1013 mm)  
32" (813 mm)  
37 ³⁄₄" (959 mm)  
16 ¹⁄₄"  
(413 mm)  
1 ¹⁄₂"  
(38 mm)  
8 ³⁄₄"  
(222 mm)  
40 ⁵⁄₈" (1032 mm)  
40 ⁵⁄₈" (1032 mm)  
Front View  
Front View  
¹⁄₂"  
¹⁄₂"  
¹⁄₂"  
¹⁄₂"  
Nailing Nailing  
Flange Flange  
Nailing Nailing  
Flange Flange  
(13 mm)  
Spacer  
(13 mm)  
Spacer  
(13 mm)  
Spacer  
(13 mm)  
Combustion  
Air Inlet  
Combustion  
Air Inlet  
Spacer  
Gas Inlet  
Line  
Gas Inlet  
Line  
40 ¹⁄₂"  
40 ¹⁄₂"  
(1029 mm)  
(1029 mm)  
7 ¹⁄₂"  
(191 mm)  
7 ¹⁄₂"  
(191 mm)  
6 ¹⁄₂"  
6 ¹⁄₂"  
(165 mm)  
(165 mm)  
4 ¹⁄₈"  
4 ¹⁄₈"  
(105 mm)  
(105 mm)  
10 ¹⁄₂"  
10 ¹⁄₂"  
(267 mm)  
(267 mm)  
5"  
5"  
5"  
5"  
6 ¹⁄₂"  
(165 mm)  
6 ¹⁄₂"  
(127 mm)  
(127 mm)  
(127 mm)  
(127 mm)  
(165 mm)  
20" (508 mm)  
17 ⁷⁄₈"  
17 ⁷⁄₈"  
19" (483 mm)  
(454 mm)  
(454 mm)  
Left View  
Right View  
Left View  
Right View  
Top Spacers (4)  
Top Spacers (4)  
31" (787 mm)  
31" (787 mm)  
7 ³⁄₄"  
7 ³⁄₄"  
¹⁄₂"  
¹⁄₂"  
(197 mm)  
(197 mm)  
(13 mm)  
Spacer  
(13 mm)  
Spacer  
¹⁄₂"  
(13 mm)  
17 ⁷⁄₈"  
¹⁄₂"  
(13 mm)  
17 ⁷⁄₈"  
(454 mm)  
(454 mm)  
⁵⁄₈"  
(16 mm)  
1"  
(25.4 mm)  
40 ⁵⁄₈" (1032 mm)  
40 ⁵⁄₈" (1032 mm)  
1 ⁵⁄₈"  
(41 mm)  
Top View  
Top View  
Figure 3  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPLIANCE CLEARANCES  
Venting  
GasVentRuleGasventcapsarenotpermitted  
within 8 feet (2.4 mm) of a vertical wall or similar  
obstruction. Gas vent caps that are located 8' or  
more from a portion of a building which extends  
at an angle greater than 45° upward from the  
horizontal may terminate in accordance with the  
table in Figure 4, provided that in no case shall  
any discharge opening on the cap be less than 2'  
(610 mm) horizontally from the roof surface  
(National Fuel Gas Code ANSI Z223.1 (NFPA 54)  
7.6.2) (CAN/CGA B149).  
GHC/GRD-5500  
GHC/GRD-6500  
1/2 in. (13mm)  
1/2 in. (13mm)  
0 in. (0 mm) to spacers  
Back  
1/2 in. (13mm)**  
1/2 in. (13mm)**  
0 in. (0 mm) to spacers  
Sides  
Top Spacers  
Floor  
0 in. (0 mm)  
0 in. (0 mm)  
*From  
Bottom of  
Unit to  
65 1/2 in. (1664 mm)  
67 1/2 in. (1715 mm)  
Ceiling  
Vent  
1 in. (25.4 mm)  
SERVICE CLEARANCE  
3 Feet (0.9 meters)  
X
12  
Roof Pitch is X/12  
Front  
* Note: See also Figure 32 on page 14 for an illustration of this clearance, for  
clearances to a sidewall and for mantel clearances.  
Minimum Height from Roof  
to Lowest Discharge Opening  
**Note: The nailing tabs and the area directly behind the nailing tabs are exempt  
from the clearances described in the above table. See Figure 9 on page 8.  
Table 3  
Minimum Height  
from Roof to Lowest  
FRAMING SPECIFICATIONS  
Roof Slope  
Discharge Opening  
Use Only 2x4 or Larger  
Lumber  
Feet  
1' 0"  
2' 0"  
4' 0"  
6' 0"  
8' 0"  
Meters  
0.3  
Flat to 6/12  
Over 7/12 to 9/12  
0.6  
Note: If the Outside Combustion  
Over 10/12 to 12/12  
Over 13/12 to 16/12  
Over 17/12 to 21/12  
1.2  
Air Kit is to be installed, it must  
be installed before the appliance  
is framed and enclosed in the  
finishing walls.  
1.8  
2.4  
B
Header  
E
Note: Venting terminals shall not be recessed  
into a wall or siding.  
Gas Supply Line  
Left or Right Side - 5500  
Right Side Only - 6500  
Figure 4  
D
A
*C  
*Note: The framed depth - dimension C- from a framed wall, must always  
be measured from a finished surface. If a wall covering such as drywall is to  
be attached to the rear wall, then dimension Cmust be measured from the  
drywall surface. It is important that this dimension be exact.  
Model No.  
A
B
C
D
E
in.  
33 1/4 38 3/4 15 1/2 8 1/2 8 1/2  
GHC/GRD-5500  
mm  
in.  
845  
40 3/4 40 3/4  
1035  
984  
394  
18  
216  
6 1/2  
165  
216  
5
GHC/GRD-6500  
mm 1035  
457  
127  
Figure 5  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL INSTALLATION SEQUENCE  
FRAMING SPECIFICATIONS CONTINUED  
The typical sequence of installation follows,  
however, each installation is unique resulting  
in variations to those described.  
Back Wall of Chase/Enclosure  
Including Finishing Materials,  
If Any.  
Note: If the Outside Combustion  
Air Kit is to be installed, it must  
be installed before the appliance  
is framed and enclosed in the  
finishing walls.  
Optional FOAK-4  
or FOAK-4LD  
Outside Air Kit  
C
1. Construct the appliance framing.  
2. Route gas supply line to appliance location.  
3. Position the appliance.  
D
4. Install the vent system and exterior termina-  
tion.  
B
A
Square Housing Not  
Used on 5500 Model  
Rough Framing Face  
(Unfinished Shown)  
5.Fieldwireandinstalloperatingcontrolswitch.  
Install optional Forced Air Kit, if required  
Model No.  
A
B
C
D
6. Make connection to gas supply.  
in.  
57 1/2  
36  
40 3/4  
1035  
29  
GHC/GRD-5500  
7. Install optional Outside Combustion Air Kit,  
if required.  
mm 1461  
in.  
mm 1670  
914  
737  
65 3/4 40 3/4 46 1/2 32 7/8  
GHC/GRD-6500  
8. Install the logs and rockwool.  
1035  
1181  
835  
9. Install the optional glass doors/enclosure  
panel, if required  
Corner Installation  
Figure 6  
10. Checkout appliance operation.  
Note: If the Outside Combustion  
Air Kit is to be installed, it must  
be installed before the appliance  
is framed and enclosed in the  
finishing walls.  
Optional FOAK-4 or FOAK-4LD  
Outside Air Kit  
11. Spillage Test and Safety Limit Switch  
Operation.  
Back Wall of Chase/Enclosure  
Including Finishing Materials, If Any.  
12. Adjust burner to ensure proper flame  
appearance.  
Model No.  
A
36  
B
15 1/2  
394  
18  
in.  
B
GHC/GRD-5500  
GHC/GRD-6500  
PRE-INSTALLATION NOTES  
mm  
in.  
914  
40 3/4  
The fireplace may be installed directly on a  
combustible floor or raised on a platform of an  
appropriate height. Do not place fireplace on  
carpeting, vinyl or other soft floor coverings. It  
may, however, be placed on flat wood, ply-  
wood, particle board or other hard surfaces,  
extending the full depth and width of the appli-  
ance. Be sure fireplace rests on a solid continu-  
ous floor or platform with appropriate framing  
for support and so that no cold air can enter the  
room from under the fireplace.  
A
4 IN.  
(103 MM)  
mm 1035  
457  
4 IN.  
(103 MM)  
Rough  
Square Housing Not  
Used on 5500 Model  
Framing Face  
(Unfinished Shown)  
Inside Chase Installation  
Figure 7  
Note: If the Outside Combustion  
Air Kit is to be installed, it must  
be installed before the appliance  
is framed and enclosed in the  
finishing walls.  
Back Wall of Chase/Enclosure  
Optional FOAK-4  
or FOAK-4LD  
Including Finishing Materials, If Any.  
Outside Air Kit  
The fireplace may be positioned and then the  
framing built around it, or the framing may be  
constructed and the fireplace positioned into  
the opening.  
Model No.  
A
36  
B
15 1/2  
394  
18  
in.  
GHC/GRD-5500  
mm  
B
914  
in.  
40 3/4  
Usually, no special floor support is needed for  
the fireplace, however, to be certain:  
GHC/GRD-6500  
mm 1035  
457  
A
Rough  
Framing Face  
(Unfinished Shown)  
Square Housing Not  
Used on 5500 Model  
1. Estimate the total weight of the fireplace  
system and surround materials such as brick,  
stone, etc., to be installed.  
Outside Chase Installation  
Figure 8  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Measure the square footage of the floor  
space to be occupied by the system, surrounds  
and hearth extensions.  
IMPORTANT: HOLD GAS VALVE SECURELY  
TO PREVENT MOVEMENT WHEN CONNECT-  
ING TO INLET GAS LINE  
See Figure 11 for 5500 series units and  
Figure 12 for 6500 series. Then install the  
remainder of the Type B vent to the outside.  
3. Note the floor construction, i.e. 2 x 6’s, 2 x  
8’s or 2 x 10’s, single or double joists, type and  
thickness of floor boards.  
Minimum overall height of the vent system and  
appliance must be 12' (3.7 m). See Figure 13.  
WARNING: CONNECTING DIRECTLY TO  
AN UNREGULATED PROPANE (L.P.G.)  
TANK MAY CAUSE AN EXPLOSION.  
Maximum overall height of the vent system and  
appliance should not exceed 40 feet (12.19 m).  
4. Use this information and consult your local  
building code to determine if you need addi-  
tional support.  
Step 3. Position the Appliance - Slide the  
fireplace into prepared framing.  
Install the B-vent system in accordance with  
the vent manufacturer's instructions.  
If you plan to raise the fireplace and hearth  
extension, build the platform assembly then  
position fireplace and hearth extension on top.  
Secure the platform to the floor to prevent  
possible shifting.  
(Note: Appliance may be positioned first and  
then the framing constructed around it.)  
5 in.  
Type B-Vent  
Fireplace should be secured to side framing  
members using the full length ¹⁄₂ inch nailing  
flanges that are integral to the appliance at  
each side. Use 8d nails (Figure 9 ).  
Flue Collar  
Assembly  
INSTALLING THE FIREPLACE  
Step 1. Construct the Appliance Framing -  
Frame appliance enclosure as illustrated in  
Figures 5 through 8 on page 6 and 7.  
(Note: Appliance may be positioned first and  
then the framing constructed around it.)  
Securing  
Screws  
Note: The nailing tabs and the area directly  
behind the nailing tabs are exempt from the  
clearances described on the fireplace clear-  
ance label.  
Flue Outlet  
Collar  
Iftheapplianceistobeelevatedabovefloorlevel,  
asolidcontinuousplatformmustbeconstructed.  
Figure 11  
5500 Series Models  
IMPORTANT: UNDER NO CIRCUMSTANCES  
CAN THE FIREPLACE TOP SPACERS (FIGURE  
2 OR 3 ) BE REMOVED OR MODIFIED, NOR  
MAY YOU NOTCH THE HEADER TO FIT  
AROUND OR BE INSTALLED LOWER THAN  
THE SPACERS. THE HEADER MAY BE IN DI-  
RECT CONTACT WITH THE TOP SPACERS  
BUT MAY NOT BE SUPPORTED BY THEM.  
Type B Vent  
Flue Outlet  
Collar  
8d Nail  
Securing  
Screws  
Consult all local codes.  
Step 2. Route Gas Supply Line - Route gas  
line(Figure 5 )using techniques and materials  
prescribed by local and/or national codes. It is  
recommended that a gas line of ¹⁄₂" or greater  
diameter be used to allow full gas volume to  
the fireplace. Undue pressure loss will occur if  
the pipe is too small.  
Figure 9  
Figure 12  
6500 Series Models  
Fireplace may be anchored to floor. Bend down  
four (4) anchor tabs located at the base of the  
fireplace and secure to the floor by nailing with  
8d nails (Figure 10 ).  
CAUTION: THIS APPLIANCE CANNOT BE  
VENTED HORIZONTALLY.  
Note: Refer to the vent manufacturers installa-  
tion instructions for variations of venting tech-  
niques. If common venting of several units is  
contemplated, it should be discussed with an  
architect and the local Building Department.  
The gas line should extend a total of 2 in.  
(51 mm) maximum into the appliance con-  
trol compartment.  
Anchor  
Tab  
When rigid pipe is used, an ANSI approved  
manual shut-off valve and union must be in-  
stalled upstream of the fireplace.  
Ensure that a sediment trap is installed in the  
existing gas line, if not, install a sediment trap  
upstreamtopreventmoistureandcontaminants  
from passing through trap to the appliance con-  
trols and burners. Failure to do so could prevent  
the appliance from operating reliably.  
12 ft.  
Minimum  
Figure 10  
Step 4. Install the Vent System & Exterior  
Termination -  
Connect a 5 in. (127 mm) Type B vent system to  
theappliancefluecollarwithfour,No.8orlarger,  
sheet metal screws.  
An external regulator must be used on all pro-  
pane (L.P.G.) heaters to reduce the supply tank  
pressure to 13" w.c. (maximum). Any copper  
tubing used to supply propane (L.P.G.) from  
the tank must be internally tinned.  
Figure 13  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Control Compartment Access - GRD Units  
5500 Series units  
3 - InstalltheprovidedJboxplateontheJbox  
withinthecontrolcompartmentusingthescrew  
and washer provided with the plate.  
4 - Refer to Figure 17 and 18 and the installa-  
tion instructions provided with the forced  
air kit(s) for blower connections to the  
appliance recepacle and ground.  
5 - Locate and install the millivolt wall switch  
(supplied) in a desired location and con-  
nect it to the millivolt circuit using the 18 ft  
of 2 conductor wire supplied with the unit  
(See Figure 16).  
The lower control compartment access panel  
has been designed to cover the control com-  
partment from view. To attach the panel to the  
appliance, hook both ends of the panel over the  
two brackets mounted on each side of the front  
combustion opening. The cover should hang  
from the brackets with the flared edge at the  
bottom allowing for a small air gap between the  
cover and the appliance.  
6500 Series units  
Louver Pegs  
Louvers  
Note: The supplied 18 feet of 2 conductor  
wire has one end of each conductor con-  
nected to the gas valve circuit and the  
other end of each conductor placed loose  
on top of the unit.  
Thelowercontrolcompartmentaccesspanelis  
attached to each side of the fireplace by pins  
that engage locking slots on the sides of the  
panel(Figure14 ). Toremovethepanelpushin  
on it’s top edge with both thumbs, one on each  
end of the panel. When the bottom edge of the  
access panel swings out, cup it with the finger  
tips of both hands. Lift with the finger tips,  
movingthepanelupandintotheappliance.Pull  
the panel top edge out from the appliance with  
the thumbs to remove it from the lower com-  
partment opening.  
Figure 15  
Note: The supplied 18 feet of 2 conductor wire  
hasoneendofeachconductorconnectedtothe  
gas valve circuit and the other end of each  
conductor placed loose on top of the unit.  
6 - After wiring is complete, replace the appli-  
ance junction box cover into the side ac-  
cess opening, from which it was removed,  
and secure with the hex head screw previ-  
ously removed.  
LEGEND  
Line  
NOTES:  
Limit Switch  
1. If any of the original wire as  
supplied with the appliance  
must be replaced, it must be  
replaced with Type AWM 105°C  
- 18 GA wire or equivalent.  
Voltage  
Thermopile  
2. Motor is thermally overloaded  
protected.  
3. 120V 60 Hz Less than 3  
amps.  
1
Blower Motor  
ON/OFF Wall Switch  
Figure 16  
Grounded to  
Appliance  
CAUTION: DO NOT WIRE THE MILLIVOLT RE-  
MOTE WALL SWITCH TO THE MAIN POWER  
SUPPLY.  
Motor Plug  
Receptacle  
2
Millivolt Wiring (With Forced Air Kit Usage) –  
Figure 14  
GHC-5500 series models may use the optional  
FAB-1500 or FAB-1600 Forced Air Kit; GHC-  
6500 the FAB-1600 Kit.  
Control Compartment Access - GHC Units  
120V  
The GHC lower control compartment access is  
provided by removing the three louvers (5500  
seriesunits)orfourlouvers(6500seriesunits).  
To remove the louvers, pull them straight out  
from the unit. To replace, tilt each of them with  
the top edge over the top of each peg and snap  
the lower edge to lock in place. See Figure 15.  
Appliance Junction Box  
If an optional forced air kit is to be installed now  
or sometime in the future, the appliance must be  
connected to the main power supply at this time.  
ON/OFF Blower  
Wall Switch  
To Fuse  
or Circuit  
Breaker  
Black  
1 - Remove the junction box cover from the  
outside right bottom corner of the unit by  
removingthehexheadscrew.Thejunction  
box cover has a ⁷⁄₈ in. (22 mm) knockout  
hole for a conduit bushing.  
2 - Route a 3 wire 120V 60Hz power supply  
line through a wall switch to the junction  
box and connect the ground wire to the  
junction box ground screw, and the black  
and white supply wires to the appliance  
recptacle as shown in Figure 17.  
Receptacle  
120V  
AC  
White  
}
Step 5. Field Wiring  
A. Millivolt Wiring  
60Hz  
Factory Supplied  
Not Supplied  
Green Ground Screw  
Millivolt Wiring (Without Forced Air Kit Usage) –  
The control tray has been set in place and has  
been pre-wired at the factory. All that is re-  
quired, regarding wiring, is to locate and install  
the wall switch (supplied) in a desired location  
and connect it to the millivolt circuit using the  
18 ft of 2 conductor wire supplied with the unit  
(Figure 16 ).  
Appliance Junction Box  
Forced Air Kit Wiring  
Millivolt System  
Figure 17  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
B. Electronic Wiring  
ElectronicWiring(WithForcedAirKitUsage)–  
GHC/GRD-5500/6500  
Note: These appliances may be equipped with  
either of two ignition control modules:  
Robertshaw or Honeywell. The Robertshaw  
module wiring is shown in Figures 20 and 21;  
the Honeywell, in Figure 22.  
Robertshaw Ignition Control Equipped  
GHC-5500 series models may use the optional  
FAB-1500 or FAB-1600 Forced Air Kit; GHC-  
6500 the FAB-1600 Kit.  
1. If any of the original wire as supplied must be replaced,  
1. it must be replaced with Type AWM 105°C 18 GA. wire.  
2. 120V, 60Hz Less than 3 amps.  
LIMIT SW.  
ON/OFF SW  
120 VAC  
If an optional forced air kit is to be installed now  
or sometime in the future, the appliance must be  
connectedtothemainpowersupplyatthistime.  
1 - Remove the junction box cover from the  
outside right bottom corner of the unit by  
removingthehexheadscrew.Thejunction  
box cover has a ⁷⁄₈ in. (22 mm) knockout  
hole for a conduit bushing.  
2 - Route a 3 wire 120V 60Hz power supply  
line through a wall switch to the junction  
box and connect the ground wire to the  
junction box ground screw, and the black  
and white supply wires to the appliance  
recptacle as shown in Figure 18; and 21  
(Robertshaw Ignition Module) or 22  
(Honeywell Ignition Module).  
BK  
24V  
LOW  
VOLTAGE  
BK  
W
GND  
Green  
Ground  
Screw  
Transformer  
GHC Series Only  
Optional  
Blower  
R
R
BK  
W
Ignitor  
Junction Box  
BK  
W
Transf.  
120 V.  
24 V  
Gas Valve  
C
M
P
Blower  
Electronic  
Millivolt  
Note: Jbox plates are not affixed in place at the factory.  
BL  
BL  
W
BK  
BK  
Figure 18  
GHC-5500/6500  
IMPORTANT:Groundleadmustbeconnected  
to the green screw located on the junction  
box. See Figure 17, 20, 21, or 22. Failure to  
do so will result in a potential safety hazard.  
Theappliancemustbeelectricallygrounded  
in accordance with local codes or, in the  
absence of local codes, the National Electri-  
cal Code, ANSI/NFPA 70-(latest edition). (In  
Canada, the current CSA C22-1 Canadian  
Electrical Code.)  
Note: If a Honeywell ignition control  
module is being used, refer to Figure 22  
for the control wiring and Figure 21 for  
the blower wiring.  
Ignition Control  
Factory Wired  
Field Wired  
3 - InstalltheprovidedJboxplateontheJ”  
box within the control compartment using  
the screw and washer provided with the  
plate.  
4 - Refer to Figure 18 and 21 and the instal-  
lationinstructionsprovidedwiththeforced  
air kit(s) for blower connections to the  
appliance receptacle and ground.  
5 - Locate and install the low voltage wall  
switch (supplied) in a desired location and  
connect it to the millivolt circuit using the  
18 ft of 2 conductor wire supplied with the  
unit (See Figure 21).  
Electronic System Wiring  
(Without Forced Air Kit)  
Figure 20  
Electronic Wiring (Without Forced Air Kit Usage)  
1 - Remove the junction box cover from the  
outside right bottom corner of the unit by  
removingthehexheadscrew.Thejunction  
box cover has a ⁷⁄₈ in. (22 mm) knockout  
hole for a conduit bushing.  
2 - Route a 3 wire 120V 60Hz power supply line  
throughawallswitchtothejunctionboxand  
connect the ground wire to the junction box  
ground screw, and the black and white  
supply wires to the appliance recptacle as  
shown in Figures 18, 19; and 20  
(Robertshaw Ignition Module) or 22  
(Honeywell Ignition Module).  
GHC-5500/6500  
Robertshaw Ignition Control Equipped  
1. If any of the original wire as supplied must be replaced,  
1. it must be replaced with Type AWM 105°C 18 GA. wire.  
2. 120V, 60Hz Less than 3 amps.  
LIMIT SW  
ON/OFF SW  
WALL BLOWER SW  
120 VAC  
BK  
BK  
W
24V  
LOW  
VOLTAGE  
GND  
Note: The supplied 18 feet of 2 conductor  
wire has one end of each conductor con-  
nected to the gas valve circuit and the  
other end of each conductor placed loose  
on top of the unit.  
Appliance  
Ground  
Screw  
BK  
Green  
Opt  
Blower  
Ground  
Screw  
W
6 - After wiring is complete, replace the appli-  
ance junction box cover into the side ac-  
cess opening, from which it was removed,  
and secure with the hex head screw previ-  
ously removed.  
R
BK  
Ignitor  
3 - InstalltheprovidedJboxplateontheJ”  
box within the control compartment using  
the screw and washer provided with the  
plate.  
Junction Box  
BK  
W
Transf.  
120 V.  
Gas Valve  
C
M
P
4 - Locateandinstallthelowvoltagewallswitch  
(supplied) in the desired location and con-  
nect it to the low voltage circuit using the 18  
ft of 2 conductor wire supplied with the unit  
as shown in Figure 20.  
R
24 V  
BL  
BL  
W
BK  
BK  
Note: The supplied 18 feet of 2 conductor  
wire has one end of each conductor con-  
nected to the gas valve circuit and the  
other end of each conductor placed loose  
on top of the unit.  
Ignition Control  
Factory Wired  
Field Wired  
Electronic  
120V Receptacle  
Electronic System Wiring  
(With Forced Air Kit)  
Note: Jbox plate is not affixed in place at the factory.  
5- After wiring is complete, replace the appliance  
junction box cover into the side access open-  
ing, from which it was removed, and secure  
with the hex head screw previously removed.  
GRD-5500/6500  
Figure 19  
Figure 21  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 7. Install Optional Outside  
Combustion Air Kit  
Gas Flex Line Connector  
GHC/GRD-5500/6500  
Gas  
³ ₈" NPT x ³ ₈"  
Flare Fitting  
³ ₈" Flare x ¹ ₂" NPT  
Shut-Off Valve  
(Honeywell Ignition Module Equipped)  
Valve  
1. If any of the original wire as supplied must be replaced,  
1. it must be replaced with Type AWM 105°C 18 GA. wire.  
2. 120V, 60Hz Less than 3 amps.  
When outside combustion air is desired, Len-  
nox' Model FOAK-4 or Model FOAK-4LD com-  
bustion air kit should be used. Refer to the  
installation instructions packed with the air kit  
for specific installation information. The outside  
air kit must be installed before the appliance is  
framed and enclosed in the finished walls.  
³ ₈" Flex Tubing  
LIMIT SW  
ON/OFF SW  
³ ₈" Shut-Off Valve  
NEU. W  
BK  
³ ₈" Nipple  
120 VAC. BK  
GND  
24V  
Low Voltage  
³ ₈"Union  
³ ₈" Close Nipple  
Gas Stub  
³ " x¹ "  
Reducer  
Green  
Ground  
Screw  
R
The control lever, located on the left side of the  
appliance front opening, controls the entrance  
of combustion air from the outside. See Figure  
25 for 5500 series units, Figure 26 for GHC-  
6500 series units or Figure 27 for GRD-6500  
series units. The 6500 series units have a cover  
over the control lever fastened by one screw.  
Remove the screw and then the cover and  
discard them.  
W
Figure 23  
BK  
Junction Box  
Ignitor  
BK  
BK  
W
Transf.  
120 V.  
R
Gas Valve  
M
C
P
24 V  
BL  
BL  
W
BK  
If an optional “All-Glass” enclosure panel is to  
be installed on the 6500 Series appliances, an  
extension bar must be attached to the actuator  
lever as illustrated in Figures 26 and 27. Both  
versions of the actuator lever extension bar are  
packaged with the glass enclosure panel.  
Piezo Ignitor  
Ignition Control  
Factory Wired  
Millivolt  
Gas Valve  
Field Wired  
Electronic System Wiring  
(Without Forced Air Kit)  
Figure 24  
Location of Controls  
Secure all joints tightly using appropriate  
tools and sealing compounds (ensure pro-  
pane resistant compounds are used in pro-  
pane applications).  
Figure 22  
Step 6. Connecting Gas Line –  
Make gas line connections. All codes re-  
quire a shut-off valve mounted in the supply  
line. Figure 23 illustrates two methods for  
connecting the gas supply. The flex-line  
method utilizing the gas flex line provided  
with the appliance is acceptable in the U.S.,  
however, Canadian requirements vary de-  
pending on locality. Installation must be in  
compliance with local codes.  
Turn on gas supply and test for gas leaks using  
a soapy water solution. Never use an open  
flame to check for leaks.  
Combustion Air Control Lever  
A. Mix a 50% dish soap, 50% water solution.  
B. Light the appliance (refer to the lighting  
instructionsprovidedintheHomeowner'sCare  
and Operation Instructions).  
GHC/GHR-5500 SERIES  
Figure 25  
The millivolt and electronic control valve have  
³⁄₈" (10 mm) NPT thread inlet ports.  
C. Brush all joints and connections with the  
soapy water solution to check for leaks. If  
bubbles are formed, or gas odor is detected,  
turn the gas control knob to the “OFF” posi-  
tion. Either tighten or refasten the leaking  
connection and retest as described above.  
Actuator Lever  
Phillips Pan  
Head Screw  
#6-32 x ⁷⁄₃₂"  
(6 mm)  
WARNING: TO PREVENT DAMAGE TO  
THEVALVEANDOTHERATTACHEDCOM-  
PONENTS, HOLD VALVE FIRMLY IN  
PLACE WHILE TIGHTENING FITTINGS  
USED IN THE NEXT STEP.  
C
O
D. When the gas lines are tested and leak free,  
observe the individual tongues of flame on the  
burner. Make sure all ports are open and  
producing flame evenly across the burner. If  
any ports are blocked, or partially blocked,  
clean out the ports.  
Extension Bar  
The gas control valve is located in the lower  
control compartment. See Figure 24. To ac-  
cess the valve see page 9, the Control Com-  
partment Access Section.  
Combustion Air Control Lever and  
Extension on GHC-6500 Series Units  
Figure 26  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 9. Optional Glass Doors/Enclosure Panel  
Availablity, Precautions and Instructions –  
Note: Lighting instructions are also found on  
the pull-out label attached near the gas valve in  
the control compartment.  
Actuator  
Lever  
Phillips Pan  
Head Screw  
#6-32 x ⁷⁄₃₂"  
(6 mm)  
See the Homeowner's Care and Operating In-  
structions for a selection of glass doors/enclo-  
sure panels available for installation in these  
appliances. Installation Instructions for the  
doors/enclosurepanelsareprovidedwiththem.  
When first lighting the appliance, it will take a  
few minutes for the line to purge itself of air.  
Once purging is complete, the pilot and burner  
will light and operate as indicated in the in-  
struction manual.  
C
Extension Bar  
Never clean glass when doors or panel are  
O
hot due to operating the appliance.  
Subsequent lightings of the appliance will not  
require such purging. Inspect the pilot flame  
(remove logs, if necessary, handling care-  
fully).  
Combustion Air Control Lever and  
Extension on GRD-6500 Series Units  
Glass and metal frames get hot. Use only  
the wooden handles to open and close the  
doors or to lift out panel.  
Figure 27  
Millivolt Appliance Checkout  
CAUTION: THE APPLIANCE SHOULD ONLY BE  
OPERATED WITH THE GLASS DOORS FULLY  
OPEN OR FULLY CLOSED.  
CAUTION: NEVER LOCATE INLET WHERE IT  
CANBEBLOCKEDBYSHRUBS,SNOWDRIFTS,  
ETC. NEVER LOCATE INLET IN GARAGE OR  
ANY AREA WHERE THERE IS ANOTHER FUEL  
BURNING APPLIANCE OR PRODUCTS EMIT-  
TING COMBUSTIBLE GASES SUCH AS PAINT,  
GASOLINE, ETC. IN COLD CLIMATES, IT IS  
RECOMMENDEDTHECOMBUSTIONAIRDUCT  
BE INSULATED.  
The gas control system on these appliances is  
a millivolt standing pilot type. It consists of a  
pilot burner, a piezo ignitor, a gas control  
valve, a burner assembly and an ON/OFF wall  
switch. A temperature limit switch is wired in  
series with the millivolt wall switch and gas  
control valve. If a higher than normal tempera-  
ture is sensed due to a blocked vent or pro-  
longed downdraft, the limit switch will open  
and cause the burner to shut off.  
Rectangular Housing Not Used on  
5500 Series Units  
Outside combustion air ducting may be run  
upwards or vertically through framing and ceil-  
ing joists, with the hood installed through an  
outside wall and 3' (1 m) below the B-Vent  
termination. Ducting may also be run down-  
wardthroughfloorjoistsandunderthehometo  
a ventilated crawlspace not considered part of  
the living area of the home.  
The pilot flame should be steady, not lifting or  
floating. Flame should be blue in color with  
traces of orange at the outer edge.  
Glass Doors  
Fully Open or  
Fully Closed  
(Twin-Pane Doors)  
The top ³⁄₈" (9 mm) at the pilot generator  
(thermopile) should be engulfed in the pilot  
flame (Figure 30 ).  
Figure 28  
Rectangular Housing Not Used on  
5500 Series Units  
Note: Do not terminate combustion air kit in  
attic space under any circumstances.  
³⁄₈" (10 mm)  
After completing the installation of the op-  
tional combustion air vent system the actua-  
tor arm must be put in service and tested to  
ensure proper operation before completing  
any enclosure around the firebox. Failure to  
do so may result in extensive and costly  
rework.  
Glass Doors  
Fully Open or  
Fully Closed  
(Bi-Fold Doors)  
Operate the actuator through several cycles  
including the closed position. Ensuring proper  
operation and freedom of movement. Return  
the actuator arm to the closed position.  
Figure 29  
APPLIANCE OPERATION  
Step 10. Checking the System –  
Figure 30  
Step 8. Installing Logs and Rockwool –  
Withgaslineinstalled,runinitialsystemcheck-  
out before closing up the front of the unit.  
Follow the pilot lighting instructions provided  
in the Homeowner's Care and Operation In-  
structions. For piezo ignitor location see Fig-  
ure 24 on page 11 (millivolt appliances only).  
If the pilot flame pattern is not as shown in  
Figure 30, adjust it as follows:  
The logs are packaged within the firebox. The  
bag of rockwool is in the lower control com-  
partment. Refer to the Homeowner's Care and  
Operating Instructions for detailed placement  
instructions for the logs and rockwool.  
1. Remove the pilot adjustment cap located on  
the main gas valve.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Adjust the pilot screw to provide properly  
sized pilot flame (Figure 30 ). Turn counter  
clockwise to enlarge pilot flame and clockwise  
to reduce the pilot flame. DO NOT attempt to  
adjust pilot flame more than one half turn.  
Manual Reset Limit Switch  
3. Replace the pilot adjustment cap.  
Replace logs if removed for pilot inspection.  
To light the burner; rotate the gas valve control  
knobcounterclockwisetotheONpositionand  
then turn “ON” the remote wall switch.  
Lintel  
Extention  
Electronic Appliance Checkout  
The gas control system on these appliances is  
an electronic low voltage gas control valve  
with an intermittent ignitor. It consists of a low  
voltage gas control valve, an intermittent igni-  
tion system, an electronic control module,  
transformer and a burner assembly. A tem-  
perature limit switch is wired in series with the  
gas control valve. If a higher than normal  
temperature is sensed, due to a blocked vent  
or prolonged downdraft, the limit switch will  
open and cause the burner to shut off.  
Firebox Wrapper  
Limit Switch Screws  
Figure 31 (GHC/GRD-5500)  
Manual Reset Limit Switch  
The pilot flame should be steady, not lifting or  
floating. Flame should be blue in color with  
traces of orange at the outer edge.  
To light the burner, push the gas control lever  
in and toward the left to the “ON” position.  
Turn ‘ON’ the remote wall switch. Ensure the  
ignitor lights the pilot. The pilot flame should  
engulf the ignitor.  
Limit  
Switch  
Screws  
Step 11. Safety Limit Switch Operation  
MANUALLY-RESET BLOCKED FLUE SAFETY  
SWITCH  
These appliances are equipped with a manu-  
ally-reset blocked flue safety switch. Refer  
to Figures 31 and 32 for their location. If  
during appliance operation, the flame goes  
out (independently of the burner on/off wall  
switch), it may be due to the operation of  
the safety limit switch. First allow the  
appliance to cool. Then reset the safety  
switch by pushing the red reset button on the  
back of the switch.  
Fireplace Front  
Lintel Extention  
Figure 32 (GHC/GRD-6500)  
To access the safety limit switch reset button,  
remove the two screws. Pull out limit switch  
withlowvoltagewiresattached, pushthereset  
button, then reinstall the limit switch. At this  
time turn the electronic appliance back on.  
The appliance should then relight and remain  
lit. If this does not occur, turn off the appli-  
ance and call a qualified service technician.  
CAUTION: THE ELECTRONIC APPLIANCE  
SHOULD BE TURNED OFF BEFORE REMOV-  
ING THE LIMIT SWITCH.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 12. Adjustments The following para-  
graphs address adjustment concerns and pro-  
cedures.  
FINISHING REQUIREMENTS  
Wall Details  
WARNING: AIR SHUTTER ADJUSTMENT  
SHOULD ONLY BE PERFORMED BY A  
QUALIFIED PROFESSIONAL SERVICE  
TECHNICIAN.  
Appliance Facing Flush with Finished Wall -  
Complete finished interior wall. To install the  
appliance facing flush with the finished wall,  
position framework to accommodate the thick-  
ness of the finished wall (Figure 35 and 37 ).  
Flame Appearance and Sooting  
Proper flame appearance is a matter of taste.  
Generally most people prefer the warm glow of  
a yellow to orange flame. Appliances operated  
with air shutter openings that are too large, or  
with long vertical vent runs, will exhibit flames  
that are blue and transparent. These weak, blue  
and transparent flames are termed anemic.  
Adjustment  
To adjust the flame, position the air shutter to  
the nominal setting (Figure 33 ). Allow the  
burner to operate for at least 30 minutes.  
Observe the flame continuously. If it appears  
weak or sooty as previously described, adjust  
the air shutter open or closed until desired  
effect is achieved.  
Surround Materials Relative to Appliance  
Facing-  
Surround materials (noncombustible) can  
be placed around the appliance facing to  
provide a flush surface between the sur-  
round materials and the appliance front fac-  
ing. Do not cover the louvers of the GHC or  
the bottom control compartment access on  
the GRD. (Figures 36 and 38 ).  
If the air shutter opening is too small sooting  
may develop. Sooting is indicated by black  
puffs developing at the tips of very long orange  
flames. Sootingresultsinblackdepositsform-  
ing on the logs, appliance inside surfaces and  
on exterior surfaces adjacent to the vent termi-  
nation. Sooting is caused by incomplete com-  
bustion in the flames and a lack of combustion  
air entering the air shutter opening.  
Orifice  
Air Shutter  
Note: Combustible wall finish materials and/or  
surround materials must not be allowed to  
encroach the area defined by the appliance  
front face (black sheet metal). Never allow  
combustible materials to be positioned in front  
of or overlapping the appliance front face.  
Adjusting  
Set Screw  
To achieve a warm yellow to orange flame with  
an orange body that does not soot, the shutter  
opening must be adjusted between these two  
extremes.  
Hearth Extensions  
Burner Tube  
No smoke or soot should be present. Reposi-  
tion the log set if the flames impinge on any of  
them.  
A hearth extension is not required with this  
appliance. Any hearth extension used is for  
appearance only and does not have to con-  
form to standard hearth extension installa-  
tion requirements.  
Nominal Air Shutter Settings:  
Natural Gas - Closed  
Propane Gas - 1/6 in. (1.59 mm) Open  
Ifsootingconditionsexist,theairshutteropen-  
ing on the main burner can be adjusted. Nor-  
mally, the more offsets in the vent system, the  
greatertheneedfortheairshuttertobeopened  
further.  
Figure 33  
Whensatisfiedthattheapplianceoperatesprop-  
erly, proceed to finish the installation. Leave  
the control knob/lever in “ON” position and  
turn the remote switch “OFF.” Replace the  
refractory access panel.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mantels  
Combustible  
Finished Wall  
Combustible  
Finished Wall  
Combustible  
Mantel  
Framing  
Spacer  
Framing  
Spacer  
See Figure 34 for combustible mantel shelf  
projections from the wall and for the mantel's  
minimum vertical distance from the top of the  
firebox opening.  
Combustible  
Mantel  
Top of  
Noncombustible  
Covering Wall  
Noncombustible  
Covering Wall  
Top of  
Fireplace  
Fireplace  
0" Clearance  
to Combustible  
Side Wall  
Top of  
Top of  
Fireplace  
Opening  
Fireplace  
Opening  
Louvers  
Max. Projection 8 in. (203 mm)  
GHC-5500  
GRD-5500  
Appliance Facing Flush with a Finished Wall  
Figure 35  
Combustible  
Mantel  
Combustible Finished  
Wall Materials  
Combustible Finished  
Framing  
Wall Materials  
Framing  
Spacer  
B
Combustible  
Combustible  
Mantel  
Mantel  
Spacer  
A
Noncombustible  
Covering Wall  
Top of  
Top of  
Noncombustible  
Covering Wall  
Fireplace  
Fireplace  
NonCombustible  
Surround  
Top of  
Fireplace  
Opening  
NonCombustible  
Surround  
Top of  
Fireplace  
Opening  
Model No.  
A
B
Louvers  
in.  
11  
65 1/2  
1664  
67 1/2  
1715  
GHC/GRD-5500  
GHC-5500  
GRD-5500  
mm  
in.  
279  
10  
Figure 36  
NonCombustible Surround Materials Relative to Appliance Facing  
GHC/GRD-6500  
mm  
254  
Combustible Finished  
Wall Materials  
Combustible Finished  
Wall Materials  
Framing  
Spacer  
Figure 34  
Framing  
Spacer  
Combustible  
Combustible  
Mantel  
Mantel  
Top of  
Top of  
Fireplace  
Fireplace  
Top of  
Fireplace  
Opening  
Top of  
Fireplace  
Opening  
Louvers  
GHC-6500  
GRD-6500  
Appliance Facing Flush with a Finished Wall  
Figure 37  
Combustible  
Finished Wall  
Materials  
Combustible  
Finished Wall  
Materials  
Framing  
Spacer  
Combustible  
Combustible  
Framing  
Spacer  
Mantel  
Mantel  
Top of  
Top of  
Fireplace  
Fireplace  
NonCombustible  
Surround  
NonCombustible  
Surround  
Top of  
Fireplace  
Opening  
Top of  
Fireplace  
Opening  
Louvers  
GHC-6500  
NonCombustible Surround Materials Relative to Appliance Facing  
GRD-6500  
Figure 38  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COLD CLIMATE INSULATION  
GAS CONVERSION KITS  
If you live in a cold climate, seal all cracks  
around your appliance with noncombustible  
material and wherever cold air could enter the  
room. It is especially important to insulate  
outside chase cavity between studs and under  
floor on which appliance rests, if floor is above  
groundlevel.Ensurethattheclearancerequire-  
ments for venting are always maintained.  
WARNING: THIS CONVERSION KIT SHALL BE INSTALLED  
BY A QUALIFIED SERVICE AGENCY IN ACCORDANCE WITH  
THE MANUFACTURER'S INSTRUCTIONS AND ALL APPLI-  
CABLE CODES AND REQUIREMENTS OF THE AUTHORIZED  
AGENCYHAVINGJURISDICTION. IFTHEINFORMATIONIN  
THESE INSTRUCTIONS ARE NOT FOLLOWED EXACTLY, A  
FIRE, EXPLOSION OR PRODUCTION OF CARBON MONOX-  
IDE MAY RESULT CAUSING PROPERTY DAMAGE, PER-  
SONAL INJURY OR LOSS OF LIFE. THE INSTALLATION IS  
NOT PROPER AND COMPLETE UNTIL THE OPERATION OF  
THECONVERTEDAPPLIANCEISCHECKEDASSPECIFIEDIN  
THE OWNER INSTRUCTIONS SUPPLIED WITH THE KIT.  
To avoid air intrusion, surround material must  
be caulked where it meets the black metal  
facing of the appliance. Only use a noncom-  
bustible caulking material to seal this area.  
Do not place insulation materials within the 1"  
gas vent system clearance space.  
INSTALLATION ACCESSORIES  
AVERTISSEMENT: CET ÉQUIPEMENT DE CONVERSION  
SERA INSTALLÉ PAR UNE AGENCE QUALIFIÉE DE SER-  
VICE CONFORMÉMENT AUX INSTRUCTIONS DU  
FABRICANT ET TOUTES EXIGENCES ET CODES  
APPLICABLES DE L'AUTORISÉS AVOIR LA JURIDICTION.  
SI L'INFORMATION DANS CETTE INSTRUCTION N'EST  
PASSUIVIEEXACTEMENT,UNFEU,EXPLOSIONOUPRO-  
DUCTIONDEPROTOXYDEDECARBONEPEUTRÉSULTER  
LE DOMMAGES CAUSER DE PROPRIÉTÉ, PERTE OU  
BLESSUREPERSONNELLEDEVIE. L'AGENCEQUALIFIÉE  
DE SERVICE EST ESPONSABLE DE L'INSTALLATION  
PROPRE DE CET ÉQUIPMENT. L'INSTALLATION N'EST  
PAS PROPRE ET COMPLÉTE JUSQU'À L'OPÉRATION DE  
L'APPAREIL CONVERTI EST CHÉQUE SUIVANT LES  
CRITÈRES ÉTABLIS DANS LES INSTRUCTIONS DE  
PROPRIÉTAIRE PROVISIONNÉES AVEC L'ÉQUIPEMENT.  
The following accessory items are available  
for use in the installation of this appliance.  
Outside Air Kits Models FOAK and FOAK-LD  
Outside Air kits are available with duct (FOAK-  
4) and without duct (FOAK-4LD) for use if  
outside combustion air is required or desired.  
If model FOAK-4LD is used it must be used in  
conjunction with locally purchased, non-com-  
bustible Class 1 or Class 0 flexible duct.  
In Canada  
Kit part numbers are listed on the next page  
and the following steps detail the conversion  
procedure.  
THE CONVERSION SHALL BE CARRIED OUT  
IN ACCORDANCE WITH THE REQUIREMENTS  
OF THE PROVINCIAL AUTHORITIES HAVING  
JURISDICTION AND IN ACCORDANCE WITH  
THE REQUIREMENTS OF THE CAN1-B149.1  
AND .2 INSTALLATION CODE.  
Note: These kits contain a main orifice which  
can be used for installation at elevations of  
0-2000 Ft. (610 m.) For elevations greater  
than that, use the correct orifice as shown in  
table 2 on page 2.  
Outside Combustion Air Kits  
(with duct)  
(without duct)  
81L87  
81L88  
FOAK-4  
FOAK-4LD  
LA CONVERSION DEVRA ÊTRE EFFECTUÉE  
CONFORMÉMENT AUX RECOMMANDATIONS  
DES AUTORITÉS PROVINCIALES AYANT  
JURIDICTION ET CONFORMÉMENT AUX  
EXIGENCESDUCODED'INSTALLATIONCAN1-  
B149.1 ET.2.  
Step1.Turnoffthegassupplytotheappliance.  
Open the doors or remove the enclosure panel.  
Step 2. Carefully remove the two (5500 Mod-  
els) or four (6500 Models) smaller logs on top.  
Then remove the two (2) main logs. Exercise  
care as not to break the logs.  
Gas conversion kits are available to adapt your  
appliance from the use of one type of gas to the  
use of another. These kits contain all the neces-  
sary components needed to complete the task  
including labeling that must be affixed to en-  
sure safe operation.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Natural To Propane  
Gas Conversion Kit Application  
Unit  
Models No.  
Kit Model  
Pilot Assembly  
Unit Type  
Part No.  
058092  
063431  
058061  
058069  
(Millivolt Shown)  
No.  
GHC/GRD- GCK-5500-  
5500 MNP  
GHC/GRD- GCK-6500-  
6500 MNP  
GHC/GRD- GCK-5500-  
5500 ENP  
GHC/GRD- GCK-6500-  
millivolt  
millivolt  
Pilot Orifice  
electronic  
electronic  
6500  
ENP  
Propane To Natural  
Gas Conversion Kit Applications  
Units  
Kit Model  
Figure 41  
Unit Type  
Part No.  
058072  
063441  
058051  
058059  
Models No.  
No.  
Step 9. Attach conversion kit label to the  
rating plate on the appliance as shown in  
the Figure 42.  
GHC/GRD- GCK-5500-  
5500 MPN  
GHC/GRD- GCK-6500-  
6500 MPN  
GHC/GRD- GCK-5500-  
5500 EPN  
GHC/GRD- GCK-6500-  
6500 EPN  
millivolt  
millivolt  
LABEL  
LABEL  
LABEL  
A
B
C
LABEL  
LABEL  
LABEL  
D
E
F
electronic  
electronic  
LABEL  
LABEL  
LABEL  
G
H
I
LABEL  
LABEL  
LABEL  
J
K
L
Step3. Removethree(3)screwsfromtheback  
oftheburnertray. Lifttherearoftheburnertray  
up slightly and to the right to disengage the  
burner tube from the manifold and orifice.  
Remove the burner tray.  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
NATURAL GAS  
LABEL B  
GHC/GRD-5500  
INPUT BTU/HR  
24,000  
Step 4. Millivolt Appliances – Remove and  
replace the regulator assembly located on the  
front of the gas valve (Figure 39 ). Ensure that  
the gasket is seated properly and is not kinked.  
MANIFOLD PRESSURE  
ORIFICE SIZE #43  
3.5"  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
NATURAL GAS  
LABEL A  
GCH/GRD-6500  
INPUT BTU/HR  
27,000  
MANIFOLD PRESSURE  
ORIFICE SIZE #41  
3.5"  
Figure 40  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
Step 6. Remove the orifice from the manifold  
and replace it with the one provided in the kit;  
5500 models - #43 for natural gas and #54 for  
propane, 6500 models - #41 for natural gas  
units and #53 for propane.  
PROPANE/LPG  
LABEL L  
GHC/GRD-5500  
INPUT BTU/HR  
24,000  
MANIFOLD PRESSURE  
ORIFICE SIZE #54  
10"  
THIS APPLIANCE HAS BEEN CONVERTED TO:  
PROPANE/LPG  
LABEL G  
Step 7. Replace the pilot orifice with the one  
provided with the kit (Figure 41).  
Gasket  
INPUT BTU/HR  
27,000  
GHC/GRD-6500  
MANIFOLD PRESSURE  
ORIFICE SIZE #53  
10"  
Regulator  
Figure 39  
Step 8. Reassemble all removed components  
by reversing the procedures outlined in the  
preceding steps. Use pipe joint compound or  
Teflon tape on all fittings before installing (en-  
sure propane resistant compounds are used in  
propane applications).  
Figure 42  
Step 5. Electronic Appliances – Mark the  
wires to the gas valve and remove the valve  
(Figure 40). Replace the valve with the one  
provided with the kit.  
Step 10. Turn on gas supply and test for gas  
leaks as described in the gas line connection  
instructions, Step 6 on page 11.  
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The manufacturer reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products.  
Consult your local distributor for fireplace code information.  
Printed in U.S.A. © 2001 by Lennox Hearth Products  
LHP  
P/N 700,027M REV. E 07/2004  
1110 West Taft Avenue Orange, CA 92865  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Silvercrest Hot Beverage Maker SWKD 3000 A16 User Manual
Sony Cell Phone 1261 4174 User Manual
Sony Computer Drive AWG2040 User Manual
Sony Cordless Telephone SPP A946 User Manual
Sony DVD Recorder MZ NH700 User Manual
Sony Stereo System VCA 41 User Manual
SOYO Computer Hardware SY V6BE+ User Manual
StarTechcom Power Supply ATXPOWER250 User Manual
Sylvania TV DVD Combo 6513VD User Manual
Sylvania TV DVD Combo 6720FDG User Manual