SERVICE HANDBOOK FOR
STANDARD RESIDENTIAL
FVIR GAS WATER HEATERS
MODELS: GPX, GS6, GSX – SERIES 200/201
GS6, GSX (40-Gallon Short) SERIES 202/203
06/09
316876-000
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE HANDBOOK
Your safety and the safety of others is extremely important in the servicing of this water heater. Many safety-
related messages and instructions have been provided in this handbook and on your water heater to warn you
and others of a potential hazard. Read and obey all safety messages and instructions throughout this handbook.
It is very important that the meaning of each safety message is understood by you and others who service this
water heater.
The information contained in this handbook is designed to answer commonly faced situations encountered
in the operation of the standard Residential Gas product line and is not meant to be all-inclusive. If you are
experiencing a problem not covered in this handbook, please contact the Technical Information Center listed on
the cover of this handbook for further assistance. Additional information is also available on the web site listed on
the cover of this handbook. This handbook is intended for use by licensed plumbing professionals and reference
should be made to the Installation Instructions and Use & Care Guide accompanying the product. This handbook
contains supplemental information to the Installation Instructions and Use & Care Guide.
When servicing residential water heaters, it is essential that you return the unit to a safe condition before you
leave the site. All original components must be re-installed and all safety measures must be implemented. In
addition, the recommended water temperature setting is 120° F.
IMPORTANT: It is recommend that on every service call an inspection & cleaning of the base ring filter
and flame arrestor be performed. See page 19.
Tools Required (for servicing gas models):
• Phillips head screw driver
• 3/8, 7/16, & 3/4 inch open end wrenches
• 3/16 inch Allen wrench
• 11/16 inch – 6 point – socket – for anode removal
• electrical multimeter (with alligator leads)
• digital or analog manometer
• gas pressure gauge
• water pressure gauge
• thermometer
• tubing cutter if pilot tube is to be replaced
• hose – to drain tank
• container – to measure gallons per minute flow
Digital manometer shown.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Fire or Explosion Harzard
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell Natural or LP gas.
Do not expose water heater control to excessive gas
pressure.
Use only gas shown on rating plate.
Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended
period of non-use.
Read instruction manual before
installing, using or servicing
water heater.
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING QUICK REFERENCE
IMPORTANT: Before performing any test, check the area around the water heater for any source of a flammable
vapor (i.e gasoline, paint thinners, etc.) If any sources are found do not proceed until they are removed.
PROBLEM
POSSIBLE CAUSE
TEST / CORRECTIVE ACTION
NO HOT WATER:
Insufficient Combustion Air or Venting
Issues – combustion chamber thermal
cut off tripped.
Follow the steps on pp 18 – 19. Always check
and clean the base ring filter and the flame
arrestor.
Pilot will not light
Check gas supply/Bleed air from gas line/turn
gas on.
Pilot will not remain lit when top gas
control knob is released
Test thermocouple and gas control valve/
thermostat as described on pp 20-21.
Burner will not light or remain lit.
Low gas pressure – check as described on p
18. Insufficient combustion air – follow steps
on pp 18 -19.
INSUFFICIENT HOT
WATER:
Water heater improperly sized to meet
hot water demands
Compare hot water requirements with the
capacity of the water heater. See sizing guide
on p. 25. You may also use the volume test
on page 34 to analyze your hot water needs.
If necessary, install a water heater with greater
capacity.
Gas Control Valve/Thermostat set
too low
Turn temperature dial to desired temperature
as described on p. 24
Sediment or lime in the tank
Drain (p. 17). Determine if water treatment is
needed (p. 29).
WATER LEAKAGE:
Condensation
Adjust the thermostat setting (p 24).
Dripping Temperature & Pressure Relief Check water supply pressure.
Valve
In closed systems, the supply pressure should
not exceed 80 psi (in a 24 hour cycle). If the
pressure exceeds 80 psi, install a pressure
reducing valve in combination with a properly
sized thermal expansion tank (pp. 35-36 & 37).
Download from Www.Somanuals.com. All Manuals Search And Download.
PROBLEM
POSSIBLE CAUSE
TEST / CORRECTIVE ACTION
WATER LEAKAGE:
Thermostat does not shut-off
Drain valve dripping/leaking
Tank Leak
Check the Gas Control Valve/Thermostat as
described on p. 20-21.
Back flush to clean- out sediment, replace if
necessary
Check Leakage Checkpoints described on
p. 25.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
BASIC INSTALLATION ...................................................................................................................................... 8-16
DRAINING AND FILLING THE WATER HEATER..................................................................................................17
Draining the Water Heater ................................................................................................................................17
Filling the Water Heater ....................................................................................................................................17
CHECKING THE GAS SUPPLY FOR PRESSURE................................................................................................18
CHECKING FOR SUFFICIENT COMBUSTION AIR OR VENTING ISSUES .................................................. 18-19
Combustion Air Test..........................................................................................................................................18
Draft Test...........................................................................................................................................................19
External Inspection & Cleaning of the Base Ring Filter ....................................................................................19
Cleaning the Combustion Chamber and Flame Arrestor ..................................................................................19
TESTING THE THERMOCOUPLE AND GAS CONTROL VALVE/THERMOSTAT...............................................20
Thermocouple Output Test................................................................................................................................20
Gas Control Valve/Thermostat (Thermal Switch Models).................................................................................20
REPLACING THE THERMOCOUPLE AND GAS CONTROL VALVE/THERMOSTAT ................................... 21-23
Removing the Manifold/Burner Assembly.........................................................................................................21
Removing the Burner from the Manifold/Burner Assembly...............................................................................21
Replacing the Thermocouple............................................................................................................................21
Replacing the Manifold/Burner Assembly .........................................................................................................22
Removing and Replacing the Gas Control Valve/Thermostat...........................................................................23
ADJUSTING THE TEMPERATURE ON THE GAS CONTROL VALVE/THERMOSTAT .......................................24
GAS WATER HEATER SIZING GUIDE..................................................................................................................25
LEAKAGE CHECKPOINTS....................................................................................................................................25
TECHNICAL SERVICE BULLETINS................................................................................................................ 26-38
Water Hammer..................................................................................................................................................27
Mineral Buildup .................................................................................................................................................28
Aluminum Hydroxide.........................................................................................................................................29
Condensation....................................................................................................................................................30
Discolored Water...............................................................................................................................................31
Smelly Water.....................................................................................................................................................32
Chlorination Procedure .....................................................................................................................................33
Not Enough Hot Water......................................................................................................................................34
Thermal Expansion..................................................................................................................................... 35-36
Leaking Temperature and Pressure Relief Valve..............................................................................................37
Insulation Blanket..............................................................................................................................................38
GENERAL INFORMATION............................................................................................................................... 39-40
7
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
INSTALLATION OF RESIDENTIAL GAS WATER HEATER
Water
Supply- Cold*
Water
Shut-Off
Valve
Exhaust Vent to
Ouside of Building
See Labels and
Installation Instructions
and Use & Care Guide
for clearances.
*Massachusett: Install
a vacuum relief in cold
water line per section
19 MGL 142.
Union
Union
Expansion Tank
Pressurize to Equal
Supply Water Pressure*
(Relieve water pressure
on the expansion tank
before adjusting air
pressure.)
To Fixtures - Hot
Tempered Water
To Fixtures
Temperature-Pressure Relief Valve
with discharge piped to an
adequate drain. Do not cap or plug.
Untempered
Hot Water
Gas Supply
Cold
Water
Inlet
Manual Gas
Shut-off Valve
Hot
Gas Control Valve/Thermostat
Recommended setting of 120°F.*
Water
Outlet
Mixing Valve
(Set to 120°F)
Do not cap or plug.
Follow the Mixing
Valve Manufacturer’s
Instructions
6” Maximum Air Gap
NOTE: Local codes
may vary.
Union
Sediment Trap
(Drip Leg) 3” Minimum.
Drain
Metal Drain Pan piped to an adequate drai
NOTE: Drain pan diameter must be at leas
2 inches wider than the diameter of the
water heater.
Air is drawn in for combustion.
Keep area clean and free from
flammables and flammable vapors.
The water heater must be installed according to all local and state codes or in the absence of local
and state codes, the “National Fuel Gas Code”’ ANSI Z223.1(NFPA 54)- current edition.
*
NOTE: If on a well system the expansion tank should be set to the maximum pressure of the pump tank.
** White-Rodgers® gas control valve/thermostat shown in this figure. The valve may vary according to model and year.
Figure 1
8
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
This portion of this handbook applies to the Operations and Servicing of Residential Gas, Tank Type, Water
Heaters, which are vented atmospherically and use a thermocouple as their electrical source.
Control: There are two gas control valve/thermostat configurations available. Both valves have similar control
elements such as the Gas Control Knob & Water Temperature Dial. Both valves have high water temperature limit
safety. Please note the location of the control elements on the following figures.
Draft Hood
Jacket
Foam Fill
Hole
Temperature-Pressure
Relief Valve
Anode Rod
Draft Hood
Anode
Rod
Hot Water
Outlet
Dip Tube
Cold Water
Inlet
Flue Baffle
Gas Control Valve
/Thermostat
Flue
Tube
Flue Baffle
Drain Valve
Gas Control Knob
On|Pilot|Off
Temperature Probe
/High Limit Probe
Reset
Button
Gas Control Knob
Off|Pilot|On
Gas
Supply
- Inlet
Gas Supply- Inlet
White-Rodgers®
Gas Control Valve/
Thermostat
Robertshaw®
Gas Control Valve/
Thermostat
Setting Indicator
(Index Bar)
**Manifold Gas
Pressure Tap
Water
Temperature
Water
Temperature
Dial
Dial
**Manifold Gas
Pressure Tap
Thermal Switch
Wire Leads
with Connectors
(some models)*
*NOTE: Some models do not have thermal switch wire leads as shown in this figure.
** Manifold Gas Pressure Taps are located on the underside of the gas control valve/thermostat.
Figure 2
9
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
Burner/Manifold Door Assembly: The burner/manifold assembly consists of several components such as:
main burner, burner orifice, manifold tube, pilot burner, pilot orifice, pilot tube, igniter, and thermocouple. See the
figure below for the complete list of components.
The pilot burner remains on once it is manually lit. When incoming cold water activates the thermostat, gas flows
to the main burner. The pilot flame ignites this gas. The main flame burns until the tank reaches set temperature
then the thermostat interrupts this main gas flow.
Figure 3
Igniter Wire
Pilot Assembly View
Piezo Igniter Tip
Pilot (Burner)
Pilot Tube
Manifold Door
Main Burner
Pilot Bracket
Pilot Orifice*
NOTE: The base of the
Thermocouple must be
flush with the base of
the pilot bracket.
Burner Orifice*
Manifold Tube
Pilot (Burner)
TCO (Thermal Cut
Off) Switch
Ferrule
Thermocouple
View Port
Pilot Nut
Igniter Wire
TCO (Thermal Cut
Off) Sensor
Thermocouple
Pilot Tube
TCO Reset
Button
Burner Screws
Door Gasket
Front View
*DO NOT operate the water heater without the pilot and burner orifices installed.
Normal Operation
Figure 4
Reset
Gas Control Knob
Button
Pilot: The pilot flame heats the end of a thermocouple.
As the thermocouple gets hotter, it generates a small
(cannot be detected without an electrical meter)
electrical current to the bottom of the gas control valve/
thermostat. This current powers the electromagnet
and holds open the main gas interrupter as long as the
pilot flame is heating the thermocouple. The normal
voltage for a properly working thermocouple is between
20 and 30 mv. DANGER! If the pilot is extinguished,
it can take up to 180 seconds for the thermocouple to
cool sufficiently to close the safety valve.
Safety Valve
Safety Valve
Pilot
Flame
RobertShaw Gas Control Valve/Thermostat Shown.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
Energy Cut Off (ECO): A metal tube (Temperature
Figure 5
Gas Control Knob
Reset Button
Probe) mounted onto the back of the gas control
valve/thermostat is immersed inside the tank water.
The probe acts as a temperature high limit. If water
gets excessively hot, an Energy Cut Off (ECO) switch
within the probe opens, interrupting the small electrical
current to the gas valve, and gas flow through the
control is interrupted. NOTE: If this safety sensor opens,
the entire control must be replaced. The ECO is NOT
resettable.
Gas Inlet
Protective
Plastic Sleeve
Temperature
Probe
Temperature
Sensor
Thermal Cut Off Switch (TCO): The water heater
is also equipped with a resettable thermal switch,
designed to shut off the gas supply in the event the
water heater has been exposed to high combustion
chamber temperatures caused by flammable vapors
(e.g. spilled gasoline), poor combustion caused by a
blocked vent or insufficient combustion air.
ECO
Thermocouple
Gas Control Valve/Thermostat - Side View
TCO (Thermal
TCO (Thermal
Cut Off) Switch
Cut Off) Sensor
TCO Reset
Button
Gas: When you prepare to light the pilot, you are
instructed to turn the gas control knob to the pilot
position and depress the gas control knob (Reset button
on Robertshaw Gas Valves). When depressed gas will
flow to the pilot burner only. You then have to (manually)
NOTE: RobertShaw® Gas Control
Valve/Thermostat shown.
ignite this pilot gas using the piezo igniter button. When the pilot is lit, the flame must heat the thermocouple until
it generates sufficient voltage to the gas valve to allow you to release the knob while gas continues to flow to
the pilot. When the gas control knob is turned to the “ON” position, gas is also available to the main burner if the
thermostat calls for heat.
Water Flow: When a hot water faucet is opened, water pressure from the well tank or street main forces cold
water into the water heater through the dip tube. This pushes hot water out of the tank.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
Thermostat Operation: Standard residential water heaters use mechanical thermostats. With a mechanical
thermostat, a dial setting of 120° F may shut the burner down at a tank temperature between 110° and 130° F.
The heater will consistently shut off at this same temperature. For this same reason, water temperature may drop
15° F - 25° F, around the temperature probe, before the main burner is activated. Keep in mind that hot water in
the upper part of the tank will probably be very near the “shut off” temperature of the control while incoming cold
water drops the water temperature around the thermostat probe. Also short, repeating heating cycles caused by
small hot water uses can cause temperatures at the point of use to exceed the thermostat setting by up to 30° F.
Gas Control Knob
Gas Control Knob
Off|Pilot|On
On|Pilot|Off
Reset Button
130°F
120°F Mark
130°F
140°F
150°F
140°F
150°F
Water
Temperature
Dial
Robertshaw®
Gas Control Valve/
Thermostat
White-Rodgers®
Gas Control Valve/
Thermostat
Note: Temperature marks noted above are approximate and may vary due to various factors.
Water Temperature
Time to Produce 2nd & 3rd
Degree Burns on Adult Skin
160°F (71°C)
About 1/2 second
150°F (66°C)
140°F (60°C)
130°F (54°C)
120°F (49°C)
80°F (27°C)
About 1-1/2 seconds
Less than 5 seconds
About 30 seconds
More than 5 minutes
- - - - - - - - - - - - - - - -
Figure 6
12
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
Combustion Air Requirements:
Table 1:
BTUH Input
Minimum Square
Feet with
Typical Room
with 8’ Ceiling
WARNING
Carbon Monoxide Warning
8’ Ceiling
30,000
45,000
60,000
75,000
90,000
105,000
120,000
135,000
188
281
375
469
563
657
750
844
9 x 21
14 x 20
15 x 25
15 x 31
20 x 28
20 x 33
25 x 30
28 x 30
Water heater must be vented to outdoors.
Vent must be installed by a qualified technician using
the local and state codes or, in the absence of local
and state codes, the National Fuel Gas Code,
ANSI Z223.1 (NFPA 54) - current edition, and/or the
installation instructions.
Examples of a qualified technican include: gas
technicians, authorized gas company personel, and
authorized service persons.
IMPORTANT:
•
The area must be open and be able to provide
the proper air requirements to the water heater.
Areas that are being used for storage or contain
large objects may not be suitable for water heater
installation.
Water heaters installed in open spaces in buildings
with unusually tight construction may still require
outdoor air to function properly. In this situation,
outside air openings should be sized the same as
for a confined space.
Failure to so do can result in death or carbon monoxide
poisoning.
IMPORTANT: Air for combustion and ventilation must
not come from a flammable or corrosive atmosphere.
Any failure due to flammable or corrosive elements in
the atmosphere is excluded from warranty coverage.
•
The following types of installation (not limited to the
following) will require outdoor air for combustion due to
chemical exposure and may reduce but not eliminate
the presence of corrosive chemicals in the air:
•
•
Modern home construction usually requires
supplying outside air into the water heater area.
Room exhaust fans may effect air requirements.
Confined Space: For the correct and proper operation
of this water heater, ample air must be supplied for
the combustion, ventilation, and dilution of flue gases.
Small enclosures and confined areas must have two
permanent openings so that sufficient fresh air can be
drawn from outside of the enclosure. One opening shall
be within 12 inches of the top and one within 12 inches
of the bottom of the enclosure.
•
•
•
•
beauty shops
photo processing labs
buildings with indoor pools
water heaters installed in laundry, hobby, or craft
rooms
water heaters installed near chemical storage areas
water softeners
•
•
Combustion air must be free of acid-forming chemicals
such as sulfur, fluorine, and chlorine. These elements
are found in aerosol sprays, detergents, bleaches,
cleaning solvents, air fresheners, paint, and varnish
removers, refrigerants, and many other commercial
and household products. When burned, vapors from
these products form highly corrosive acid compounds.
These products should not be stored or used near the
water heater, air inlet, or air intake path.
The size of each opening (free area) is determined by
the total BTUH input of all gas utilization equipment
(i.e., water heaters, furnaces, clothes dryers, etc.) and
the method by which the air is provided. The BTUH
input can be found on the water heater rating plate.
Additional air can be provided by two methods:
1. All air from inside the building.
2. All air from outdoors.
12” MAXIMUM
Combustion and ventilation air requirements are
determined by the location of the water heater.
The water heater may be located in either an open
(unconfined) area or in a confined area or small
enclosure such as a closet or small room. Confined
spaces are areas with less than 50 cubic feet for
each 1,000 BTUH of the total input for all gas-using
appliances.
CLOSET
OR
OTHER
CONFINED
SPACE
PERMANENT
OPENINGS TO
THE OUTSIDE OR
ADDITIONAL
ROOMS WITHIN
THE BUILDING
Unconfined Space: A water heater in an unconfined
space uses indoor air for combustion and requires at
least 50 cubic feet for each 1,000 BTUH of the total
input for all gas appliances. The table below shows a
few examples of the minimum square footage (area)
required for various BTUH inputs.
12” MAXIMUM
Figure 7
13
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
All Air from Inside the Building: When additional air
Minimum Free Area of Permanent Openings for
Ventilation and Combustion Air Supply - All Air from
Outdoors Only.
is to be provided to the confined area from additional
room(s) within the building, the total volume of the
room(s) must be of sufficient size to properly provide
the necessary amount of fresh air to the water heater
and other gas utilization equipment in the area. Each
of the two openings shall have a minimum free area of
1 square inch per 1,000 BTUH of the total input rating
of all gas utilization equipment in the confined area, but
not less than 100 square inches for each opening.
Based on total BTUH input rating for all utilizing
equipment within the confined space.
Minimum Free Area
Per Opening (sq. in.)
Reference
Drawing
Opening Source
*Direct to outdoors 1 sq. in, per 4000 BTUH
Figure 9
Figure 10
Figure 11
Figure 12
Vertical Ducts
Horizontal Ducts
Single Opening
1 sq. in, per 4000 BTUH
1 sq. in, per 2000 BTUH
1 sq. in, per 3000 BTUH
CONFINED
SPACE
Example: A water heater with an input rating of 50,000 BTUH
using horizontal ducts would require each opening to have a
minimum free area of 25 square inches.
Minimum free area = 50,000 BTUH x 1 sq. in. / 2000 BTUH = 25
sq. in.
These openings connect directly with the outdoors
through a ventilated attic, a ventilated crawl space, or
through an outside wall.
*
PERMANENT
OPENINGS
1 SQUARE
INCH/1000
BTUH
(MINIMUM
100 SQ. IN.
FOR EACH
OPENING)
Consult the local codes of your area for specific
ventilation and combustion air requirements
ABLE VENT
TO OUTDOORS
INSTALL ABOVE
INSULATION
Figure 8
All Air from Outdoors: Outdoor fresh air can be
provided to a confined area either directly or by the use
of vertical and horizontal ducts. The fresh air can be
taken from the outdoors or from crawl or attic spaces
that freely communicate with the outdoors. Attic or
crawl spaces cannot be closed and must be properly
ventilated to the outside.
CONFINED
OUTLET
SPACE
AIR TO
ATTIC 1 SQ.
INCH PER
4000 BTUH
INLET AIR FROM
THE CRAWL SPACE
ALTERNATE
AIR INLET
Ductwork must be of the same cross-sectional area
as the free area of the opening to which they connect.
The minimum dimension of rectangular air ducts
cannot be less than three inches.
1 SQ. INCH PER
4000 BTUH
100 SQ. INCH MINIMUM (EACH)
OPEN
FOUNDATION
VENT
The size of each of the two openings is determined by
the method in which the air is to be provided. Refer to
the table below to calculate the minimum free area for
each opening.
ALL AIR FROM OUTDOORS: INLET AIR FROM VENTILATED
CRAWL SPACE/OUTLET AIR TO VENTILATED ATTIC
Figure 9
Louvers and Grilles: In calculating free area for
ventilation and combustion air supply openings,
consideration must be given to the blocking effect of
protection louvers, grilles, and screens. These devices
can reduce airflow, which in turn may require larger
openings to achieve the required minimum free area.
Screens must not be smaller than 1/4” mesh. If the
free area through a particular design of louver or grille
is known, it should be used in calculating the specified
free area of the opening. If the design and free area
are not known, it can be assumed that most wood
louvers will allow 20 - 25% of free area while metal
louvers and grilles will allow 60 - 75% of free area.
Louvers and grilles must be locked open or
GABLE VENT
TO OUTDOORS
INSTALL ABOVE
INSULATION
OUTLET AIR TO
ATTIC 1 SQ. INCH
PER 4000 BTUH -
100 SQ. INCH MIN.
(EACH)
CONFINED
SPACE
INLET AIR DUCT
1 SQ. INCH PER
4000 BTUH - 100
SQ. INCH MIN.
(EACH)
interconnected with the equipment so that they are
opened automatically during equipment operation.
Keep louvers and grilles clean and free of debris or
other obstructions.
12” MAXIMUM
ALL AIR FROM OUTDOORS THROUGH VENTILATED ATTIC
Figure 10
14
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
Vent Connectors:
1 SQ. INCH PER
2000 BTUH
100 SQ. INCH
MINIMUM (EACH)
1. Type B, Double wall, U.L. Listed Vent Pipe.
2. Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum
clearance from combustible materials when using type
B double wall vent pipe.
OUTLET
CONFINED
SPACE
OUTDOOR
AIR DUCTS
Vent connectors made of type B, double wall vent
pipe material may pass through walls or partitions
constructed of combustible material if the minimum
listed clearance is maintained.
INLET
Maintain a one inch minimum clearance from all
1 SQ. INCH PER
2000 BTUH 100 SQ. INCH
MINIMUM (EACH)
combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used
for water heaters located in attics and may not pass
through attic spaces, crawl spaces or any confined
or inaccessible location. A single wall metal vent
connector cannot pass through any interior wall.
ALL AIR FROM OUTDOORS USING HORIZONTAL DUCTS
Figure 11
ALTERNATIVE
OPENING
LOCATION
When installing a vent connector, please note the
following
•
Install the vent connector avoiding unnecessary
bends, which create resistance to the flow of vent
gases.
1 SQ. INCH
PER 3000 BTUH
CONFINED
SPACE
100 SQ. INCH
MINIMUM (EACH)
•
•
Install without dips or sags with an upward slope of
at least 1/4-inch per foot.
Joints must be fastened by sheet metal screws
or other approved means. It must be supported
to maintain clearances and prevent separation of
joints and damage.
ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT OPENING
•
•
•
•
The length of the vent connector cannot exceed
75% of the vertical vent height.
The vent connector must be accessible for clean-
ing, inspection, and replacement.
Vent connectors cannot pass through any ceiling,
floor, firewall, or fire partition.
It is recommended (but not mandatory) that
a minimum 12 inches of vertical vent pipe be
installed on the draft hood prior to any elbow in the
vent system.
Figure 12
Vent Pipe System: This water heater must be
properly vented for the removal of exhaust gases to
the outside atmosphere. Correct installation of the vent
pipe system is mandatory for the proper and efficient
operation of this water heater and is an important
factor in the life of the unit.
The vent pipe must be installed according to all
local and state codes or, in the absence of local and
state codes, the “National Fuel Gas Code”, ANSI
Z223.1(NFPA 54)-current edition. The vent pipe
installation must not be obstructed so as to prevent the
removal of exhaust gases to the outside atmosphere.
IMPORTANT: Existing vent systems must be inspected
for obstructions, corrosion, and proper installation.
Chimney Connection: IMPORTANT: Before
connecting a gas vent to a chimney, make sure the
chimney passageway is clear and free of obstructions.
The chimney must be cleaned if previously used for
venting solid fuel appliances or fireplaces. Also consult
local and state codes for proper chimney sizing and
application or, in the absence of local and state codes,
the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition.
U.L. recognized fuel gas and carbon monoxide
(CO) detectors are recommended in all applications
and should be installed using the manufacturer’s
instructions and local codes, rules, or regulations.
Vent Pipe Size: It is important that you follow the
guidelines in these instructions for sizing a vent pipe
system. If a transition to a larger vent size is required,
the vent transition connection must be made at the
draft hood outlet. DO NOT reduce the vent size to less
than the draft hood outlet diameter.
•
The connector must be installed above the
extreme bottom of the chimney to prevent
potentially blocking the flue gases.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
BASIC INSTALLATION & OPERATION
The following figures are examples of vent pipe system
•
•
•
The connector must be firmly attached and sealed
to prevent it from falling out.
installations and may or may not be typical for your
specific application. Consult the “National Fuel Gas
Code”, NFPA 54, ANSI Z223.1-current edition and the
guidelines set forth by prevailing local codes.
To aid in removing the connector, a thimble or slip
joint may be used.
The connector must not extend beyond the inner
edge of the chimney as it may restrict the space
between it and the opposite wall of the chimney
LOWEST DISCHARGE OPENING
LISTED VENT CAP
LISTED GAS VENT
x
LISTED LINED
CHIMNEY
12
SUPPORT
STRAP
ROOF PITCH IS x/12
*MAINTAIN
CLEARANCE
2 FT. MINIMUM ABOVE ANY OBJECT
WITHIN 10FT. HORIZONTALLY
3 FT. MINIMUM
SUPPORT
STRAP
MAINTAIN
CLEARANCE*
H (MINIMUM) - MINIMUM HEIGHT FROM
ROOF TO LOWEST DISCHARGE OPENING
TYPE B DOUBLE
WALL VENT PIPE
SEAL
**MAINTAIN
SPECIFIED
CLEARANCE
DO NOT EXTEND
VENT BEYOND EDGE
OF CHIMNEY
VENT
CONNECTOR
SLOPE UP
1/4 IN. PER FT.
MINIMUM
SLOPE
UP 1/4 IN.
PER FT.
VENT
CONNECTOR
MINIMUM
VERTICAL GAS VENT SYSTEM WITH
TYPE B DOUBLE WALL VENT PIPE.
CHIMNEY TERMINATION VENT SYSTEM
Figure 14
Figure 13
Consult the table found in the “National Fuel Gas
Code”, NFPA 54, ANSI Z223.1-current edition to
determine the minimum height from roof to lowest
discharge opening.
Do not reduce the vent to less than the draft hood
outlet diameter. Do not terminate the vent connector in
a chimney that has not been certified for this purpose.
Some local codes may prohibit the termination of vent
connectors in a masonry chimney.
LISTED VENT CAP
MAINTAIN MANUFACTURER’S
SPECIFIED MINIMUM CLEARANCE
Vertical Exhaust Gas Vent: Vertical exhaust gas
vents must be installed with U.L. listed type B vent pipe
according to the vent manufacturer’s instructions and the
terms of its listing.
**MAINTAIN
SPECIFIED
CLEARANCE
SUPPORT
STRAP
*MAINTAIN
CLEARANCE
SEAL
It must be connected to the water heater’s draft hood by a
listed vent connector or by directly originating at the draft
hood opening.
Vertical gas vents must terminate with a listed cap or
other roof assembly and be installed according to their
manufacturer’s instructions.
VENT CONNECTOR
VENT
CONNECTOR
UNUSED CHIMNEY
SLOPE UP
FLUE OR MASONRY
1/4 IN. PER FT.
ENCLOSURE
MINIMUM
Gas vents must be supported to prevent damage, joint
separation, and maintain clearances to combustible
materials.
VENTING THROUGH A CHIMNEY WITH
TYPE B DOUBLE WALL VENT PIPE.
IMPORTANT: This gas vent must be terminated in a
vertical position to facilitate the removal of the burnt
gases.
Figure 15
Maintain vent pipe clearance requirements to local, state
and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA
54)-current edition.
*
An unused chimney flue or masonry enclosure may be
used as a passageway for the installation of a gas vent.
NOTE: The chimney flue or masonry enclosure size may
be too large to allow proper venting.
** NFPA 211, Standard for Chimneys, Fireplaces, Vents, and
Solid Fuel-Burning Appliances states that these chimneys are
intended to be installed in accordance with the installation
instructions provided with each chimney support assembly.
Minimum air space clearance to combustible materials should be
maintained as marked on the chimney sections.
Common (combined) venting is allowable with vertical
type B vent systems and lined masonry chimneys as long
as proper draft for the water heater is established under
all conditions of operation. CAUTION: DO NOT common
vent this water heater with any power vented appliance.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
DRAINING AND FILLING THE WATER HEATER
Filling the Water Heater
Draining the Water Heater
Never use this water heater unless it is completely full
of water. To prevent damage, the tank must be filled
with water. Water must flow from the hot water faucet
before lighting the water heater. NOTE: The hot water
faucet used should be the one furthest from the water
heater.
The water heater should be drained if being shut down
during freezing temperatures. Also, periodic draining
and cleaning of sediment from the tank may be
necessary.
To fill the water heater with water:
1. Turn off the gas to the water heater at the manual
gas shut-off valve.
1. Close the water heater drain valve.
2. Open the cold water supply shut off valve to the
water heater.
2. Open a nearby hot water faucet until the water is
no longer hot.
3. To ensure complete filling of the tank, allow air to
exit by opening the furthest hot water faucet. Allow
water to run until a constant flow is obtained. This
will let air out of the water heater and the piping.
3. Close the cold water inlet valve.
4. Connect a hose to the drain valve and terminate
it to an adequate drain or external to the building.
(Make sure all connections are tight and that the
water flow is directed away from people.)
4. Check all new water piping for leaks. Repair as
needed.
5. Open the water heater drain valve and allow all the
water to drain from the tank. Flush the tank with
water as needed to remove sediment.
6. Close the drain valve, refill the tank, and restart the
heater as directed by the lighting instructions on
the front of the water heater.
If the water heater is going to be shut down for an
extended period, the drain valve should be left open.
IMPORTANT: Condensation may occur when the cold
tank is first heated and should not be confused with a
tank leak.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECKING THE GAS SUPPLY PRESSURE
Checking the Gas Supply Pressure
Gas pressure checks are done with flowing gas using
a gas pressure gauge capable of reading pressure in
inches of water column.
GAS PRESSURE LABEL
WHITE RODGERS GAS CONTROL
VALVE/THERMOSTAT SHOWN
GAS
PRESSURE
GAUGE
CONNECTED AT
PRESSURE TAP
•
Supply gas pressure checks are measured before
the gas control valve/thermostat and as close to
the water heater as possible.
•
Manifold (main burner) gas pressure is measured
at the pressure tap on the bottom of the gas
control valve/thermostat. Use an Allen wrench to
remove the plug then attach the gas gauge.
MANIFOLD GAS PRESSURE TEST
NOTE: Desired gas pressures will be noted on the
gas valve label located on the gas control valve/
thermostat.
Figure 16
IF . . .
. . . THEN
supply gas pressure is under desired pressure
requirement
•
increase supply gas pressure regulator setting
and,
•
•
•
•
•
increase supply gas piping size.
supply gas pressure is over desired pressure
add gas pressure regulator.
reduce setting on existing regulator.
ensure there is adequate supply gas pressure
manifold gas pressure is more than +/- .3 inch
W.C. from values indicated on gas valve
ensure the main burner orifice is the correct size
for the water heater model being tested.
•
if the above tests have been performed and the
results were correct replace the gas control valve.
CHECKING FOR SUFFICIENT COMBUSTION AIR OR VENTING ISSUES
Combustion Air Test
The Installation Instructions and Use & Care Guide
gives guidelines under “Air Requirements” and
“Unconfined “ or “Confined Space” sections. If you
want to test for a lack of air:
1. Turn on every appliance and fan that exhausts
air from the utility room and/or house. Make
sure all windows and doors are closed, as well
as chimney dampers.
EXHAUST FAN
2. Open a hot water faucet so that the main
burner will ignite
VENT
3. Remove the outer door of the water heater –
not the inner door
4. Monitor the flame characteristics for several
minutes
REVERSE FLOW
OF VENT PRODUCTS
If the flame begins to “yellow” open a door or window,
to the outdoors, to see if additional air corrects this
back to blue. If it does, the room needs more air
supply.
Figure 17
18
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECKING FOR SUFFICIENT COMBUSTION AIR OR VENTING ISSUES
Draft Test
External Inspection & Cleaning of
the Base-Ring Filter
1. At least annually check the base-ring filter for any
dust or debris that may have accumulated on the
filter screen. NOTE: If the water heater is located
in an area that is subjected to lint and dirt, it may
be necessary to check the base-ring filter more
frequently.
After successfully lighting the water heater, allow the
unit to operate for 15 minutes and check the draft
hood relief opening for proper draft. Make sure all
other appliances in the area are operating and all
doors/windows are closed when performing the draft
test. Pass a match flame or smoke around the relief
opening of the draft hood. A steady flame or smoke
drawn into the opening indicates proper draft.
2. Follow the Lighting Instructions to turn off the water
heater and allow it to cool for 10 minutes before
attempting to clean the base-ring filter.
If the flame flutters or is blown out, combustion
products are escaping from the relief opening. If this
occurs, do not operate the water heater until proper
adjustments or repairs are made to the vent pipe
system and/or air supply requirements.
3. Use a vacuum cleaner with a hose attachment
to remove any dust or debris that may have
accumulated on the filter. NOTE: If unable to
inspect or clean the base-ring filter, follow the
“Cleaning the Combustion Chamber and Flame-
arrestor” instructions below.
Flue Products Vented
to Ouside of Building
4. After the base-ring filter has been cleaned, follow
the Lighting Instructions to return the water heater to
service.
Dilution Air
Dilution Air
Cleaning the Combustion Chamber
and Flame-arrestor
Draft Hood
Match
1. Follow procedure outlined in “Removing the
Manifold/Burner Assembly” (See page 22).
Dilution Air
(Relief Opening)
2. Use a vacuum cleaner/shop vac to remove all
loose debris in the combustion chamber. Use
compressed air to clear any dust or debris that
may have accumulated in the flame-arrestor.
COMBUSTION CHAMBER
FLAME ARRESTOR
DOOR GASKET
BASE-RING
FILTER
Outer Door
Air is drawn in for combustion.
Keep area clean and free from
Figure 19
3. Reassemble following the procedure under
“Replacing the Manifold/Burner Assembly” (See
page 21).
combustibles and flammable vapors.
Figure 18
19
Download from Www.Somanuals.com. All Manuals Search And Download.
TESTING THE THERMOCOUPLE AND GAS CONTROL VALVE/THERMOSTAT
IMPORTANT: Before performing any test, check the area around the water heater for any source of a Flammable
Vapor (i.e gasoline, paint thinners, etc.) If any sources are found do not proceed until they are removed.
Thermocouple Output Test
The following test will check the DC voltage generated
by the thermocouple when the pilot light is lit.
1. Disconnect the thermocouple from the gas control
valve/thermostat as shown in the adjacent figure.
2. Using a multimeter with alligator clips leads,
attach the red lead to the body (copper part) of the
thermocouple. Attach the black lead to the end
(silver part) of the thermocouple. Reference the
adjacent image for placement of the leads.
3. Follow the lighting instructions on the front of the
water heater to light the pilot and watch the voltage
readings on the multimeter. NOTE: You will have
to hold the button down to keep the pilot lit for the
duration of the test. After 45 seconds the meter
should read 20-30 millivolts DC or more.
Figure 20
IF . . .
. . . THEN
the multimeter voltage reads
at least 20-30 millivolts DC
•
•
check the positioning of the thermocouple tip to the pilot flame. If
necessary position the thermocouple to ensure the flame contacts the
thermocouple’s tip. Re-test the thermocouple, and if it fails replace the
thermocouple. (See p. 22)
the multimeter voltage reads
more than 20-30 millivolts DC
the thermocouple is working properly. Proceed to the gas control valve/
thermostat test.
Gas Control Valve/Thermostat Test
(Thermal Switch Models)
GAS CONTROL
KNOB
The following test will check the gas control valve/
thermostat’s ECO & TCO (Energy Cut Off & Thermal Cut
Off). NOTE: This test applies to gas valves with wire leads
that attach to the thermal switch on the manifold door.
TCO
WIRE LEADS
TCO
WIRE LEADS
(JUMPERED)
1. Remove both wire leads from the TCO (thermal cut
off switch) and jumper the two leads to complete
the circuit. Once the test is complete, remove the
jumper and reconnect the wire leads.
TCO
SWITCH
2. Follow the lighting instructions on the front of the
water heater to light the pilot.
3. Release the knob and check to see if the pilot
remains lit.
Figure 21
IF . . .
. . . THEN
the pilot lights and remains lit
•
•
the TCO (thermal switch sensor) has tripped OR the TCO is not
working (OPEN). Reattach the wire leads and press the TCO reset
button. Relight the water heater. If the pilot will not remain lit, replace
the TCO. If the pilot does remain lit, the TCO was tripped-possibly
due to a lack of combustion air (see pp 13-16 & 18-19) OR because
of a Flammable Vapor event. Check around the water heater for any
source of flammable vapors (i.e. gasoline, paint thinner, etc.).
the pilot will not light or remain
lit with the wire leads jumpered
replace the gas control valve/thermostat.
(See p. 24)
20
Download from Www.Somanuals.com. All Manuals Search And Download.
REPLACING THE THERMOCOUPLE AND GAS CONTROL VALVE/THERMOSTAT
Removing the Manifold/Burner Assembly
Removing the Burner from the Manifold/
Burner Assembly
1. Turn off the gas supply to the water heater at the
manual gas shut-off valve. This valve is typically
located beside the water heater. Note the position
of the shut-off valve in the open/on position then
proceed to turn it off.
2. On the lower front of the water heater locate the gas
control valve/thermostat. Before performing any
maintenance, it is important to turn the temperature
dial on the gas control valve/thermostat to its lowest
setting.
Natural Gas (Low Nox) & L.P. Gas Burner
1. Take off the burner by removing the two (2) screws
located underneath the burner.
2. Check the burner to see if it is dirty or clogged. The
burner may be cleaned with soap and hot water.
3. On top of the gas control valve/thermostat turn the
gas control knob to the “OFF” position. NOTE: On
the White-Rodgers® gas control valve/thermostat
the knob stop must first be depressed before turning
the gas control knob. See Lighting Instructions on
the water heater.
PILOT ASSEMBLY
(BOTTOM VIEW)
SCREWS
WHITE RODGERS GAS VALVE
ROBERTSHAW GAS VALVE
BURNER
(BOTTOM VIEW)
PILOT
TUBE
PILOT
TUBE
THERMOCOUPLE
MANIFOLD TUBE
THERMOCOUPLE
MANIFOLD TUBE
Figure 24
Replacing the Thermocouple
Figure 22
4. Remove the outer door.
1. Remove the manifold/burner assembly as directed
previously.
5. Remove the two screws securing the manifold
door assembly to the combustion chamber.
GAS CONTROL VALVE/
THERMOSTAT
PIEZO
2. Lift the retainer clip straight up from the back of
the two piece wire connector (using a flat-blade
screwdriver), then remove the two piece wire
connector from the manifold door.
IGNITER
BUTTON
MANIFOLD
TUBE
PILOT
TUBE
THERMOCOUPLE
3. Remove the burner, see Removing the Burner from
the Manifold/Burner Assembly.
TCO
SWITCH
VIEW PORT
4. Pull the thermocouple from the pilot assembly.
MANIFOLD
DOOR
IMPORTANT: Be careful not to bend or alter the
position of the pilot assembly components.
MANIFOLD
SCREWS (2)
TWO PIECE
WIRE CONNECTOR
5. Insert the thermocouple tip into the holes provided
in the pilot bracket until it clicks into place. NOTE:
The base of the thermocouple must be flush with
the base of the pilot bracket.
Figure 23
6. Disconnect the thermocouple (right-hand thread), pilot
tube, the igniter wire from the igniter button, the two
connectors attached to the TCO switch, and manifold
tube at the gas control valve/thermostat. NOTE: L.P.
Gas systems use reverse (left-hand) threads on the
manifold tube.
6. Position the new thermocouple through the bottom
opening of the two piece wire connector. Be
sure igniter wire is positioned through the middle
opening of the two piece wire connector.
7. Grasp the manifold tube and push down slightly to
free the manifold, pilot tube, and thermocouple.
7. Re-attach the burner. Note the orientation of the
burner.
8. Carefully remove the manifold/burner assembly from
the burner compartment. NOTE: Be sure not to
damage internal parts.
8. See Replacing the Manifold/Burner Assembly.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
REPLACING THE THERMOCOUPLE AND GAS CONTROL VALVE/THERMOSTAT
5. Replace the two screws, which secure the
FERRULE NUT
THERMOCOUPLE
manifold/burner assembly door to the combustion
IGNITER WIRE
chamber and tighten securely. Once the manifold/
burner assembly door is tightened, visually inspect
PILOT
PILOT BRACKET
the door gasket between the manifold/burner
assembly door and the combustion chamber
OTHER FITTINGS
NOT SHOWN
FOR CLARITY
for spaces or gaps that would prevent a seal.
IMPORTANT: Do not operate the water heater if
the door gasket does not create a seal between
RETAINER
CLIP
the manifold door and the combustion chamber.
6. During the following procedure, do not cross-
MANIFOLD TUBE
PILOT TUBE
MANIFOLD/BURNER
DOOR OPENING
thread or apply any thread sealant to any of the
TWO PIECE
fittings listed below. First, reconnect the manifold
tubing to the gas control valve/thermostat. NOTE:
L.P. gas systems use reverse (left-hand) threads
on the manifold tube.
WIRE CONNECTOR
NOTE: If a ferrule nut needs to be installed for the
pilot tube, locate the one provided with your parts
kit. Install it in the gas control valve/thermostat at
the pilot location, hand tight only. Next, insert the
pilot tube into the ferrule nut until it bottoms out.
NOTE: Hold the tube in this position. Tighten the
ferrule nut with a wrench until the crimp connection
seals to the pilot tube. Continue to tighten until
the nut is tight in the gas control valve/thermostat.
Finally, start the thermocouple nut and turn it all the
way in by hand. An additional quarter turn with a
3/8” open-end wrench will then be sufficient to seat
the lockwasher. When you are finished, connect
the two wire leads that go to the thermal switch.
Figure 25
Replacing the Manifold/Burner Assembly
WARNING
7. Reconnect the igniter wire.
Explosion Hazard
8. Turn gas supply on and refer to the Lighting
Instructions.
•
•
Tighten both manifold door screws securely.
9. With the burner lit, check the gas control valve/
thermostat supply line, two piece wire connector,
manifold tube, and pilot tube connections for
leaks. Check for leaks by brushing on an approved
noncorrosive leak detection solution. Bubbles
forming indicate a leak. Correct any leak found.
IMPORTANT: All leaks must be fixed immediately.
10. Replace the outer door.
Remove any fiberglass between gasket and
combustion chamber.
•
•
Replace viewport if glass is missing or damaged.
Replace two piece wire connector if missing or
removed.
•
•
Replace door gasket if damaged.
BRACKET
FLAME ARRESTOR
Failure to follow these instructions can result in
death, explosion, or fire.
DOOR GASKET
1. Check the door gasket for damage or imbedded
debris prior to installation.
2. Inspect the view port for damage and replace as
required.
3. Insert the manifold/burner assembly into the
burner compartment making sure that the tip of the
manifold tube engages in the slot of the bracket
inside the combustion chamber (Figures 32 & 33).
4. Inspect the door gasket and make sure there is no
fiberglass insulation between the gasket and the
combustion chamber.
TIP
(MANIFOLD TUBE)
Figure 26
22
Download from Www.Somanuals.com. All Manuals Search And Download.
REPLACING THE THERMOCOUPLE AND GAS CONTROL VALVE/THERMOSTAT
7. To remove the gas control valve/thermostat, thread
CLOSE-UP INSIDE VIEW OF
THE COMBUSTION CHAMBER.
a correctly sized pipe into the inlet and use it to turn
the gas control valve/thermostat (counterclockwise.)
Do not use pipe wrench or equivalent to grip body.
Damage may result, causing leaks.
SLOT
Do not insert any sharp objects into the inlet or outlet
TIP
BRACKET
MANIFOLD TUBE
connections. Damage to the gas control valve/
thermostat may result.
Figure 27
Replacing the Gas Valve:
Removing and Replacing the Gas Control
Valve/Thermostat
1. To replace the gas control valve/thermostat,
reassemble in reverse order. When replacing
the gas control valve/ thermostat, thread a
correctly sized pipe into the inlet and use it to
turn the gas valve (clockwise.) DO NOT OVER
TIGHTEN or damage may result. NOTE: Use an
approved TEFLON® tape or pipe compound only
on the threaded section of the gas control valve/
thermostat that screws into the tank.
IMPORTANT: This water heater has a resettable
thermal switch installed. Do not attempt to disable
or modify this feature in any way. Use only factory
authorized replacement parts.
Removing the Gas Valve:
1. Turn off the gas supply to the water heater at the
manual gas shut-off valve. This valve is typically
located beside the water heater. Note the position
of the shut-off valve in the open/on position then
proceed to turn it off.
2. Reconnect the gas piping to the gas control valve/
thermostat. NOTE: Use an approved Teflon tape or
pipe compound on the gas piping connections.
3. Attach the igniter and bracket to the new gas control
valve/thermostat, clipping it at the back edge of
thermostat and snapping it into place. NOTE: Do not
use the (pilot) ferrule nut supplied with the new gas
control valve/thermostat, unless the existing nut is
not usable. Reconnect the pilot tube, manifold tube,
igniter wire, and thermal switch wires. NOTE: L.P.
gas systems use reverse (left-hand) threads on the
manifold tube.
2. On the lower front of the water heater locate
the gas control valve/thermostat. Before
performing any maintenance, it is important to
turn the temperature dial on the gas control valve/
thermostat to its lowest setting.
3. On top of the gas control valve/thermostat turn the
gas control knob to the “OFF” position. NOTE: On
the White-Rodgers® gas control valve/thermostat
the knob stop must first be depressed before turning
the gas control knob. See Lighting Instructions on
the water heater.
4. Fill the tank completely with water. NOTE: To purge
the lines of any excess air, keep the hot water
faucet open for 3 minutes after a constant flow of
water is obtained.
4. Drain the water heater. Refer to the section of
“Draining and Flushing” section and follow the
procedure.
5. Turn on the gas supply and test the gas supply
connections by brushing on an approved
noncorrosive leak detection solution. Bubbles
forming indicate a leak. Correct any leak found.
6. Check the operation of the burner by following the
lighting instructions on the front of the water heater.
With the burner lit, check the gas control valve/
thermostat supply line, manifold tube and pilot tube
connections for leaks.
5. Disconnect the piezo igniter wire from the piezo
igniter button. NOTE: There are two types of
igniters. If you have the square igniter, slide the
igniter bracket backwards away from the gas valve
to remove it. If you have the round igniter, first
remove the igniter from the bracket by depressing
front and rear holding tabs and lift. Next remove
igniter bracket from the gas valve. Disconnect
the thermocouple, pilot tube, the two connectors
attached to the thermal switch, and manifold tube
at the gas control valve/thermostat. NOTE: L.P.
gas systems use reverse (left-hand) threads on the
manifold tube.
7. Verify proper operation and then replace the outer
door.
8. If additional information is required, contact Residential
Technical Assistance by referencing the phone
number on the water heater.
6. Refer to “Gas Piping” section and disconnect the
ground joint union in the gas piping. Disconnect
the remaining pipe from the gas control valve/
thermostat.
TEFLON® is a registered trademark of E.I. Du Pont De Nemours and Company
23
Download from Www.Somanuals.com. All Manuals Search And Download.
ADJUSTING THE TEMPERATURE ON THE GAS CONTROL VALVE THERMOSTAT
reset to the desired temperature setting to reduce
the risk of scald injury. The index bar (Robsertshaw)
Water temperature over 125°F (52°C)
can cause servere burns instantly
and mark (White-Rodgers®) are indicative of
approximately 120°F (49°C) and are the preferred
starting points, see the figure below. Some states have
a requirement for a lower setting.
resulting in severe injury or death.
Children, the elderly, and the
physically or mentally disabled are at
highest risk for scald injury.
White-Rodgers® Valves:
Feel water before bathing or
showering.
Turn the water temperature dial clockwise (
decrease the temperature, or counterclockwise (
to increase the temperature.
) to
Temperature limiting valves are
available.
)
Read instruction manual for safe
temperature setting.
Robertshaw® Valves:
Turn the water temperature dial clockwise (
increase the temperature, or counterclockwise (
decrease the temperature.
) to
) to
Due to the nature of the typical gas water heater, the
water temperature in certain situations may vary up to
30°F (16.7 °C) higher or lower at the point of use such
as, bathtubs, showers, sink, etc.
Should overheating occur or the gas supply fail to
shut off, turn off the manual gas control valve to the
appliance.
HOTTER WATER CAN SCALD: Water heaters are
intended to produce hot water. Water heated to a
temperature which will satisfy space heating, clothes
washing, dish washing, and other sanitizing needs
can scald and permanently injure you upon contact.
Some people are more likely to be permanently injured
by hot water than others. These include the elderly,
children, the infirm, or physically/mentally handicapped.
If anyone using hot water in your home fits into one
of these groups or if there is a local code or state
law requiring a certain temperature water at the hot
water tap, then you must take special precautions.
In addition to using the lowest possible temperature
setting that satisfies your hot water needs, a means
such as a mixing valve should be used at the hot water
taps used by these people or at the water heater.
Mixing valves are available at plumbing supply or
hardware stores. Follow manufacturer’s instructions
for installation of the valves. Before changing the
factory setting on the thermostat see following figure.
Using the lowest hot water temperature that meets
your needs will also provide the most energy efficient
operation of the water heater.
WHITE RODGERS GAS VALVE
GAS CONTROL KNOB
(OFF-PILOT-ON)
160°F
150°F
INDEX BAR
140°F
120°F
130°F
TEMPERATURE DIAL
ROBERTSHAW GAS VALVE
GAS CONTROL KNOB
DIAL
STOP
120°F
RESET
BUTTON
130°F
140°F
150°F
W
A
R
M
INDEX
BARS
T
I
O
U
N
A
C
T
O
H
160°F
V
W
T
H
S
A
A
T
R
E
O
Y
H
E
T
T
E
E
S
R
E
C
R
A
U
I
R
N
R
C
J
A
I
S
N
I
K
T
D
O
L
F
A
S
C
I
O
N
TEMPERATURE DIAL
Water
Temperature
Time to Produce 2nd & 3rd
Degree Burns on Adult Skin
Never allow small children to use a hot water tap, or
to draw their own bath water. Never leave a child
or handicapped person unattended in a bathtub or
shower.
160°F (71°C)
150°F (66°C)
140°F (60°C)
130°F (54°C)
120°F (49°C)
80°F (27°C)
About 1/2 second
About 1-1/2 seconds
Less than 5 seconds
About 30 seconds
NOTE: A water temperature range of 120°F-140°F
(49°C-60°C) is recommended by most dishwasher
manufacturers.
More than 5 minutes
- - - - - - - - - - - - - - - -
The thermostat of this water heater has been factory
set at its lowest position. It is adjustable and must be
Figure 28
24
Download from Www.Somanuals.com. All Manuals Search And Download.
GAS WATER HEATER SIZING GUIDE
Use the following information as a guide to approximate the correct size water heater for the residence:
•
•
•
•
30 gallon size (21 gallon draw) for one bath residence.
40 gallon size (28 gallon draw) for two bath residence -or one bath with an automatic clothes washer.
50 gallon size (35 gallon draw) for three bath residence - or two baths with an automatic clothes washer.
When a whirlpool tub is part of the home equipment, it is suggested that the water heater storage tank
capacity be selected based on the needs of the whirlpool tub. This method of tank sizing, will in most cases,
cancel all statements above concerning tank sizing.
•
High flow or multiple shower head installations must be sized for at least a 20 minute draw.
Table 2:
Tub Capacity to
Overflow Outlet at:
80 gal.
80 gal.
65 gal.
54 gal.
90 gal.
90 gal.
71 gal.
59 gal.
100 gal.
100 gal.
80 gal.
110 gal.
110 gal.
89 gal.
74 gal.
120 gal.
120 gal.
98 gal.
130 gal.
130 gal.
108 gal.
90 gal.
140 gal.
140 gal.
117 gal.
97 gal.
150 gal.
150 gal.
125 gal.
104 gal.
(120ºF Water) Min. Stored
Water Capacity**
(140ºF Water*) Min.
Stored Water Capacity**
(@ 160ºF Water*) Min.
Stored Water Capacity**
66 gal.
82 gal.
*A thermostatic mixing valve set for a maximum temperature of 120° F is recommended to be installed to prevent a scalding
hazard.
**Based on tub water temperature of 105º
Note: Because the desired fill time is normally 10 minutes, recovery capacity is not used for this calculation. All water used
is supplied by storage.
NOTE: The draw efficiency of a gas or electric water heater storage tank is considered to be 70%.
LEAKAGE CHECKPOINTS
A. Water at the draft hood is water vapor which has
condensed out of the combustion products. This is
caused by a problem in the vent.
B. *Condensation may be seen on pipes in humid
weather or pipe connections may be leaking.
C. *The anode rod fitting may be leaking.
D. Small amounts of water from temperature-pressure
relief valve may be due to thermal expansion or
high water pressure in your area.
E. *The temperature-pressure relief valve may be
leaking at the tank fitting.
F. Water from a drain valve may be due to the valve
being slightly opened.
*
To check where threaded portion enters tank,
insert cotton swab between jacket opening and
fitting. If cotton is wet, follow draining instructions
in the “Draining the Water Heater” section and then
remove fitting. Put pipe dope or Teflon® tape on the
threads and replace. When you are finished, follow
the steps in “Filling the Water Heater” section.
A
C
B
E
D
G. *The drain valve may be leaking at the tank fitting.
H. Combustion products contain water vapor which
can condense on the cooler surfaces of the tank.
Droplets form and drip onto the burner or run on
the floor. This is common at the time of start-up
after installation and when incoming water is cold.
I. Water in the water heater bottom or on the floor
may be from condensation, loose connections, or
the relief valve. DO NOT replace the water heater
until a full inspection of all possible water sources
is made and necessary corrective steps taken.
H
G
I
Leakage from other appliances, water lines, or ground
seepage should also be checked.
F
6” (152.4 mm)
MAXIMUM AIR GAP
Figure 29
25
Download from Www.Somanuals.com. All Manuals Search And Download.
TECHNICAL BULLETINS
WATER HAMMER ..................................................................................................................................................27
MINERAL BUILD-UP..............................................................................................................................................28
ALUMINUM HYDROXIDE ......................................................................................................................................29
CONDENSATION ...................................................................................................................................................30
DISCOLORED WATER...........................................................................................................................................31
SMELLY WATER ....................................................................................................................................................32
CHLORINATION PROCEDURE ............................................................................................................................33
NOT ENOUGH HOT WATER .................................................................................................................................34
THERMAL EXPANSION................................................................................................................................... 35-36
LEAKING TEMPERATURE AND PRESSURE RELIEF VALVE ............................................................................37
INSULATION BLANKETS ......................................................................................................................................38
26
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 11
WATER HAMMER
GENERAL
Water hammer is the destructive force, pounding noise and vibration in a piping system
when water flowing through a pipeline is stopped abruptly. When water hammer
occurs, a high intensity pressure wave travels back through the piping system until it
reaches a point of some relief. The shock wave will then surge back and forth between
the point of relief and the point of stoppage until the destructive energy is dissipated in
the piping system. The violent action accounts for “banging”, “thumping”, and/or intense
vibration in the pipe line. Although noise is generally associated with the occurrence
of water hammer, it can occur without audible sound or noise. Quick closure of valves
always causes some degree of shock with or without noise. The common cause of
water hammer is single lever faucets (sinks/lavatories) or automatic solenoid valves
dishwashers, washing machines, etc.). The speed of the valve closure time is directly
related to the intensity of the surge pressure.
EFFECTS
The damage from water hammer can manifest itself in a number of ways. The most
common are:
•
Expanded Tank Shell - This can be demonstrated by measuring the circumference
at various locations along the shell. Pressures in excess of the maximum design
working pressure can cause permanent deformation of the shell. NOTE: The
continuous expansion of the tank shell may cause the tank to rupture at a welded
seam.
•
•
Collapsed Flue Tube - This will choke off the ability to vent the products of
combustion causing the flame and/or combustion to spill out from the combustion
chamber. Often this will occur where thinning of the flue tube walls has occurred
due to contamination of the combustion air or because of excessive condensation.
Inverted or Deformed Tank Heads - Often this accompanies collapsed flues, but
one or both heads can be deformed.
THE FIX
NOTES
The only effective means of control is to install water hammer arrestors. These
devices have diaphragms which separate an air chamber from the water in the
piping system. As the shock wave reaches this device, the air chamber absorbs the
shock. Arrestors should be located as close as possible to the source of the shock
wave.
Since water hammer exposes the equipment to pressures in excess of its design
limits, failures caused by water hammer are not eligible for warranty consideration.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 13
MINERAL BUILD-UP
SYMPTOMS
CAUSE
• Rumbling
• Crackling
• Popping
With the increase in fuel costs and hot water consumption, deliming has become a
necessity of modern maintenance. Lime (CaCO3), is the most notable factor when
discussing water hardness. Lime is present in every water system to some degree.
Since lime is inversely soluble [the more you heat, the more lime comes out], higher
usage, excessive hardness, and increased heating surface can lead to a high
incidence of “limed-up” heaters.
Symptoms often include a popping of water trapped under lime deposits or the sizzling
of water trapped next to elements, boiling it to steam.
THE FIX
Treatment of a “ limed-up“ heater is relatively simple. Since CaCO3 is a base, the
easiest way to dissolve it so it can be flushed from the heater is with an acid. The most
commonly used is phosphoric acid at a food-grade level.
Two available treatments are Mag-Erad® and Un-Lime®. Any well stocked plumbing
supply house should have a deliming solution available.
The directions on the product should be followed explicitly.
NOTES
For additional information and instructions in deliming water heaters and boilers, please
refer to the following pamphlets available from the Technical Information Center listed
on the cover of this handbook:
•
•
•
Why? When & How: To Remove Water Scale from Tank Type Water Heaters
The Mag-Erad® Method of Cleaning Gas Fired Water Heaters
Up-N-Down Transfer Kit
28
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 14
ALUMINUM HYDROXIDE
SYMPTOMS
CAUSE
“Crackling”, “gurgling”, or “popping” noises from new water heaters (installed less than
six months).
In a few isolated parts of the United States where the water supply has a relatively
high pH (8+), water conditions will react with the aluminum anode to form excessive
amounts of aluminum hydroxide on the anode and in the bottom of the tank. Aluminum
hydroxide looks like “jelly beads” or a green, blue or gray gel like substance in the
heater drain or at faucet aerators.
THE FIX
This procedure should only be performed by someone with abilities equal to a licensed
tradesman. Aluminum hydroxide can be removed by using one of the methods outlined.
If tank is new with no lime build-up to any degree:
1
2
3
Turn off the heater.
Remove the anode.
Flush the tank thoroughly with water.
Replace the aluminum anode (identifiable by smooth surface on plug) with
magnesium anode (identifiable by weld bead on plug).
4
If tank is new with lime build-up to any degree:
1
2
3
4
Turn off the heater.
Drain the heater.
Remove the anode.
Add UN-LIME to the tank.
20-40 gallon models (use 3 gallons of UN-LIME)
41-65 gallon models (use 5 gallons of UN-LIME)
66-100 gallon models (use 7 gallons of UN-LIME)
5
Heat the UN-LIME to a temperature between 140°F to 160°F.
•
GAS - Heat for 7 to 10 minutes.
6
7
Shut off the water heater.
Allow the heated UN-LIME to stand for up to 12 minutes.
Drain and flush the tank. Caution: UN-LIME will still be hot.
Replace the original aluminum anode with a magnesium anode.
Fill the system with water.
8
9
10
11
Turn heater fuel “ON”.
NOTES
Since aluminum hydroxide is a product of a chemical reaction dependent on the water
condition, any treatment is not considered warranty related.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 15
CONDENSATION
SYMPTOMS
CAUSES
The water heater appears to be releasing water while the main burner is on or water
is found surrounding the heater shortly after the water heater has been used. This
bulletin explains why flue gases condense and how you can differentiate between
condensation and leaking.
Condensate is the result of air borne water vapor being chilled below the dew point.
The dew point is the temperature at which water vapor turns into liquid. Low incoming
water temperatures cool the piping and the heat transfer surfaces of the water heater.
When the main burner comes on, the hot flue gases turn into condensate upon contact
with these surfaces. The typical home water heater will produce about one-half gallon
of water vapor during every hour of operation. Condensate is often mistaken for
leaking.
Newer heaters will condensate more than older heaters because modern water heaters
are much more efficient than their predecessors. The newer heaters utilize as much of
the energy out of the main burner flame as possible. This lowers the flue gas and tank
storage temperature and closer to the dew point temperature.
DIAGNOSIS
To distinguish between a condensating water heater and a leaking water heater:
1. Wipe up any water under the heater.
2. Turn the knob on the thermostat to the pilot position.
3. Wait 8 hours, check for water accumulation under the heater.
4. Condensation should stop when the entire tank water is heated above
approximately 115 degrees.
•
•
If no water is under the heater, the water heater was condensating.
If water is under the heater, check further for a loose fitting. If all fittings are
tight and the tank is leaking, replace the water heater. Leaking heaters cannot
be “repaired”.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 21
DISCOLORED WATER
SYMPTOMS
CAUSES
Rusty, brown, black, or yellow water appearing in the hot water.
Complaints of discolored water are commonly blamed on water heaters and storage
tanks, but in fact, it is a rare occurrence for today’s high quality glass lined tanks to
have a lining failure significant enough to allow water to contact enough bare metal to
discolor the contents of even a small tank.
The most common cause of “rusty” water is a non-toxic iron reducing bacteria,
scientifically termed Crenothrix, Leptothrix, and Gallionella. Iron bacteria is commonly
found in soil, water wells, water treatment plants and water distribution piping systems
where soluble iron exceeds 0.2 ppm, higher levels make conditions even more
favorable. Soluble iron in the water provides food for the bacteria. Rusty discolored
water is the end result of the bacteria feeding process. Water heaters and storage
tanks usually require new anode rods as presence of iron bacteria contributes to
premature anode failure.
The requirements for the bacteria to thrive are:
•
•
•
Elevated levels of iron and manganese in the water
Water with little or no dissolved oxygen
Temperatures below 138°F
Items that can increase the potential for this bacteria are:
•
•
•
Water softeners
Well water
Long periods of no water movement
TREATMENT
The simplest treatment available is shock-chlorination of the system. This is a
surface treatment, and often requires repeated trials in heavily infected systems. The
chlorination of a system requires that you follow each step explicitly to avoid an un-
treated portion of the piping system from reinfecting another part. See Bulletin 23 for
the chlorination procedure.
NOTES
Since rusty water is caused by a bacteria presence and is not caused by the
water heater, any treatment would not be considered warranty related.
31
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 22
SMELLY WATER
CAUSES
The most common cause of “smelly water” is a non-toxic sulfate reducing bacteria,
scientifically termed Divibrio Sulfurcans. This bacteria often enters the water system
through construction or a break in ground piping. The bacteria creates the energy it
needs to survive by converting sulfate (SO4) to hydrogen sulfide(H2S) gas you smell in
the water.
Hydrogen sulfide gas is distinctive because of its rotten egg-like stench. Its presence
can severely affect the taste as well as the odor of the water. Occasionally this bacteria
can be accompanied by black deposits, the result of pipe and fitting corrosion. In
extremely high concentrations, hydrogen sulfide gas can be toxic though the gas is
detectable long before harmful levels are reached.
The requirements for the bacteria to thrive are: a) an elevated level of sulfur in the
water, b) activated hydrogen from cathodic reactions within the tank, c) water with little
or no dissolved oxygen, d) and temperatures below 138°F.
Items that can increase the potential for this bacteria are: a) water softeners, b) well
water, c) and long periods of no water movement.
Other factors that may contribute to smelly water:
•
•
•
•
•
Chlorides of Magnesium and Calcium leave a bitter taste.
Chloride of Sodium produces a salty taste.
Sulfates (50 ppm) gives a medicinal taste.
Carbon Dioxide in a low pH water gives fizzy water.
Iron and tannic waters also give a bad taste and odor.
TREATMENT
The simplest treatment available is the shock-chlorination of the system. This
is a surface treatment, and often requires repeated trials in heavily infected
systems. The chlorination of a system requires that you follow each step
explicitly to avoid an un-treated portion of the piping system from reinfecting
another part. See Bulletin 23 for the chlorination procedure. Longer lasting
solutions include chlorination or aeration of the water supply.
NOTES
Since rusty water is caused by a bacteria presence and is not caused by the
water heater, any treatment would not be considered warranty related.
32
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 23
CHLORINATION PROCEDURE
CAUSES
The chlorination procedure is used to eliminate various bacteria that accumulate and grow
in water heaters. These bacteria often cause odorous or discolored water conditions.
PROCEDURE Please read the steps of the chlorination procedure prior to beginning. If you feel
uncomfortable performing any of these steps, contact a service person to perform this
procedure for you.
STEP 1
STEP 2
STEP 3
STEP 4
STEP 5
STEP 6
Turn off the gas or electric supply to the tank.
Turn off the cold water supply valve to the tank.
Open a nearby hot water faucet to relieve the vacuum.
Drain all the water from the tank (a water-hose may be needed).
Remove the anode rod(s), and close the drain valve.
Using a funnel in the anode opening add one gallon of household chlorine bleach for every
25 gallons of tank capacity.
STEP 7
STEP 8
Reinstall anode rod(s) after inspecting and replacing as needed.
Open cold water supply valve and refill the system. Then draw the water to every hot
water fixture, until the smell of chlorine is detected. Operate dish and clothes washers until
a noticeable amount of the chlorine is detected as well. All hot water lines must receive
treatment.
STEP 9
Leave the chlorine solution undisturbed for one hour or more.
STEP 10
STEP 11
After the contact time has elapsed, drain the tank according to steps #2, #3, & #4.
Close the drain valve and refill the tank. Allow the tank to sit for 15 minutes. Repeat steps
#2, #3, and #4. Continue to flush the tank if the water is discolored or contains a chlorine
odor.
STEP 12
STEP 13
Close the drain valve and refill the tank. Flush all chlorine from the piping by opening every
hot water outlet/ appliance.
Return hot water heating system to service by following the recommended start-up
procedure posted on the unit or in the manual.
33
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 35
NOT ENOUGH HOT WATER - GAS
CAUSES
Complaints regarding an insufficient supply of hot water are typically the result of
a water heater that cannot meet the demands of the residence (both people and
appliances). The demand for sufficient hot water may also be exceeded if additional
people and/or appliances are added to the residence. Another factor that may reduce
the hot water output is mineral build-up. Reference Bulletin 13 to determine if mineral
build-up may be effecting your hot water output. The following test will help determine if
a water heater is supplying the intended amount of hot water.
TEST
Please read all the steps of the test prior to beginning. NOTE: This test is based on
140° F storage temperature and these amounts are approximate.
STEP 1
Do not use any hot water for two hours to ensure the accuracy of this test. Turn on the
cold water at full flow using a double handle faucet and time how long it takes to fill a
one-gallon jug. Calculate the Gallons Per Minute (GPM) flow rate as follows.
One-gallon Jug filled in:
5 seconds = 12 gallons per minute
10 seconds = 6 gallons per minute
15 seconds = 4 gallons per minute
20 seconds = 3 gallons per minute
30 seconds = 2 gallons per minute
STEP 2
Using a thermometer, turn on the hot water and time how long it takes for the water
temperature to drop 30 degrees.
Gallons Per Minute (GPM) Flow Rate
1.5
2
2.5
3
3.5
4
5
6
30 Gallon Tank
40 Gallon Tank
50 Gallon Tank
65 Gallon Tank
75 Gallon Tank
100 Gallon Tank
119 Gallon Tank
14 min. 10 min. 8 min.
18 min. 14 min. 11 min.
7 min.
9 min.
6 min.
8 min.
5 min.
7 min.
4 min.
5 min.
8 min.
9 min.
3 min.
4 min.
6 min.
8 min.
23 min. 17 min. 14 min. 12 min. 10 min. 9 min.
30 min. 22 min. 18 min. 15 min. 13 min. 11 min.
35 min. 26 min. 21 min. 17 min. 15 min. 13 min. 10 min. 8 min.
47 min. 35 min. 28 min. 23 min. 20 min. 17 min. 14 min. 11 min.
56 min. 42 min. 33 min. 28 min. 24 min. 21 min. 17 min. 14 min.
Minutes to drop 30° F
Example: 10 seconds to fill the one-gallon jug equals 6 gallons per minute flow rate.
If the temperature drops 30 degrees in 6 minutes that equals 36 gallons of hot water.
This is normal for a 50 gallon water heater. The amount will be about 70% of the
capacity of the heater.
RESULTS
If the test performed above results in a 70% (+ /- 10 %) capacity, then the heater is
performing per specifications and a larger water heater should be considered in order
to meet the demand.
34
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 45
THERMAL EXPANSION
SYMPTOMS
•
•
•
•
•
Effects are only noticeable after hot water use followed by periods of no water use.
Relief valve drips during any recovery cycle when no hot or cold water is used.
Hot water pipes creak while heater is recovering and all valves are closed.
Tanks or other components of the water supply system fail prematurely.
A metallic creaking noise might actually be heard in the location of the heater as
the pressure is relieved and the stretched tank returns to a natural shape.
Faucet drips during any recovery cycle when no hot or cold water is used.
Water surges when a faucet is first opened and then pressure drops.
•
•
CAUSE
The water in a water heating system expands when it is heated and increases in
volume. Since water will not compress (like air), system designers must include
provisions for thermal expansion. (Water in a closed tank at 50 psi, when heated just
10 degrees, will reach a pressure of 250 psi).
Many water supply systems have check valves or backflow preventers at the water
meter to prevent any possible contamination of the public water supply by the
accidental back-flow of contaminated water into the supply mains. These check valves
are often required by code, and some cities are even installing the check valves. They
serve a useful purpose. Do not remove them!
The use of pressure reducing valves (PRV) is another cause. PRVs are designed to
conserve water and prolong fixture life. Many PRVs also act as very effective check
valves. Again, do not remove them!
Water softeners in the system may also act as back-flow preventers.
TEST
Follow these easy steps to diagnose thermal expansion:
•
Turn the heater thermostat all the way down, and install a water pressure gauge
with dead hand on the drain valve. Open the drain valve, so the gauge reads
system pressure.
•
Open a hot water tap and allow 15% to 20% of the tanks volume to run out. Shut
off the drain valve and make sure that no other fixture in the system, hot or cold, is
open. Make sure that outside fixtures, if they are on the same system, are turned
off too. Any water leaks or use will make the test meaningless.
•
•
Check the water pressure gauge, and turn the pointer so it lines up with the
pressure indicating needle. Turn the thermostat back up to its normal position, so
the heater cycles on. Watch the pressure gauge.
If the system is closed, the pressure will start to climb steadily and rapidly. A
small amount of thermal expansion control may be built into the system because
of trapped air pockets or a water hammer arrestor. In that case the pressure
will increase slightly, hold steady for a short time and then rapidly increase. The
temperature and pressure relief valve (T&P) or PRV should open and release
water once the pressure reaches the maximum setting on the valve. The valve will
close once the pressure falls below the pressure setting of the valve.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
THERMAL EXPANSION
THE FIX
The ideal fix involves the use of a pressure reducing valve if supply pressures are
above 60 to 70 psi, and a properly sized expansion tank. The PRV reduces supply
pressures to 40 to 60 psi allowing an economically priced and sized expansion tank
to be used. The PRV also offers the benefit of saving water and prolonging the life of
water flow valves. The PRV is not required if the system already has one or if high
supply pressures are desired. A supply water pressure of 80 PSI is a maximum set by
many local or state codes.
The PRV is installed between the check valve and the water heating system. The
expansion tank is installed between the PRV and the water heating system. Follow the
manufacturers instructions for installing the expansion tank.
Run the thermal expansion check again. The pressure should increase only slightly
then hold steady throughout the recovery cycle. The expanded water is flowing back
from the heater and into the pressurized storage bladder of the expansion tank. Air
pressure will force this water out of the expansion tank into the supply once usage
resumes.
DO NOT DEPEND ON THE TEMPERATURE & PRESSURE VALVE (T&P VALVE) TO
HANDLE THERMAL EXPANSION! The T&P valve manufacturers designed the valve
to be an emergency relief device only. The T&P Valve could be subject to reduced
effectiveness or failure.
FIGURE
IN A CLOSED SYSTEM USE A
THERMAL EXPANSION TANK
COLD WATER SUPPLY TO FIXTURES
PRESSURE REDUCING VALVE
WITH BYPASS
COLD WATER
INLET
HOT WATER
OUTLET
COLD WATER INLET VALVE
(SHUT-OFF VALVE)
WARNING
Thermal expansion of water, if not compensated for in system design, will lead to the
early failure of components. These failures are not covered by the manufacturer’s
warranty, so it is extremely important that everyone be aware of the causes, symptoms
and solutions to thermal expansion in a closed water heating system.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 52
LEAKING TEMPERATURE AND PRESSURE RELIEF VALVE
SYMPTOMS
GENERAL
•
•
•
•
Water seeping around the relief valve tank connection
Leakage at the threaded portion of the relief valve connection
Intermittent weeping and/or dribbling from the relief valve
Large volume of hot water sporadically discharged from the relief valve
The temperature and pressure relief valve (T & P) is a safety device limiting
temperature and pressure levels in a water heater. Each T & P has both a temperature
and pressure rating.
Normally, the temperature and pressure relief valve will have a temperature rating of
210°F. A probe (part of the relief valve) extends into the tank measuring the stored
water temperature. This probe must be within the top six inches of the water heater.
If the water heater’s thermostat malfunctions, higher than normal water temperatures
could be produced. Once the probe senses a temperature approaching its temperature
rating, the relief valve will open to full capacity releasing “very hot” water until the
temperature is below its reset temperature.
The pressure rating on the relief valve should be the same or less than the certified
working pressure of the tank (generally 150 psi) and be below the lowest maximum
working pressure rating of any system components. Once the pressure in the tank
reaches the valve’s pressure rating, it will slightly open relieving the pressure. Relieving
of pressure can be noted as “dribbling” or “weeping” water from the relief valve.
If an incorrectly sized temperature and pressure relief valve is installed, the warranty
will be void.
THE FIX
Follow these easy steps to diagnose thermal expansion:
•
Intermittent weeping and/or dribbling at the relief valve - The relief valve
relieves water slowly when actuating on pressure. A closed system can cause
pressure to increase in the system. This condition is called thermal expansion. For
additional information regarding thermal expansion please see Bulletin 45.
•
•
•
Leaking at the spud of the water heater - Spuds are welded to the tank and are
not repairable. The heater should be replaced.
Leakage at the threaded relief valve connection - Remove relief valve and
reseal connection.
Large volume of hot water sporadically discharged from the relief valve - The
relief valve relieves water quickly when actuating on temperature. The only cause
of this problem is a malfunctioning thermostat.
37
Download from Www.Somanuals.com. All Manuals Search And Download.
BULLETIN 60
INSULATION BLANKETS
GENERAL
The purpose of an insulation blanket is to reduce the standby heat loss encountered
with storage tank heaters.
Most modern water heaters have adequate factory installed insulation, the use of an
after market insulation blanket is no longer recommended by most experts. While
the use of an external insulation blanket will not void the warranty, the water heater
manufacturer explicitly disclaims any liability for problems associated with the use of
insulation blankets.
NOTE: A few local energy codes may still require the use of insulation blankets on
waters heaters. Be sure to follow all installation instructions, cautions, and warnings for
the insulation blanket as well as the cautions and warning of the water heaters owners
manual.
NOTES
Should you choose to apply an insulation blanket to this heater, you should follow these
instructions. Failure to follow these instructions can restrict the air flow required for
proper combustion, resulting in fire, asphyxiation, serious personal injury or death.
•
•
Do not cover the outer door, thermostat or temperature & pressure relief valve.
When installed the insulation blanket will cover important safety and operation
labels. Obtain new warning and instruction labels from the Technical
Information Center listed in the owners manual. The replacement labels must
be placed on the blanket in the location of the original labels on the water
heater jacket.
•
•
•
Do not cover the instruction manual. Keep it on the side of the water heater or
nearby for future reference.
Do not apply insulation to the top of the water heater, as this will interfere with
safe operation of the draft hood.
Do not allow insulation to come within 2” of the base of the water heater to
prevent blockage of combustion air flow to the burner. The combustion air
openings in the base of the water heater must NOT be obstructed.
•
Inspect the insulation blanket frequently to make certain it does not sag,
thereby obstructing combustion air flow.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
GENERAL INFORMATION
Draw efficiency is the quantity of hot water available to the consumer before the outlet water temperature
decreases 25 degrees F. A 40 gallon water heater will typically provide 70% (28 gallons) of this “usable” hot
water (60% is the minimum). The burner or elements are allowed to operate during this test. Incoming, cold
water mixes the remaining stored water below this 25 degree limitation.
Energy Factor is an indicator of the combined thermal efficiency and standby efficiency of a water heater. The
higher the energy factor, the more efficient the water heater will be.
Minerals and gases will separate from water as temperature increases.
“R” Value is a measure of the resistance of a substance to heat flow.
Recovery rate is the amount of water that is heated to a set temperature, per hour. An example might be that a
water heater has a recovery rate of 30 gallons of water per hour at 80 degree F. (Fahrenheit) temperature rise.
Standby efficiency – the water heater’s ability to contain heat in the tank. A minimum of tank water heat loss
per hour is desired.
Sample: temperature change
“R” value
= Btu/h loss/ square foot of tank surface
Temperature rise is the increase in the temperature from its coldest “inlet” water temperature to the desired hot
(outlet) setting. Typically this is assumed to be 40 degrees entering water, 120 degrees desired stored water or
80 degrees “temperature rise.”
Thermal efficiency is approximately the amount of generated BTU (British Thermal Units), which enters the
water. A percentage of the total BTU passes out through the vent piping.
Water cannot (for all practical purposes) be compressed.
Water expands when it is heated.
Formulas and Conversions:
BTU (British Thermal Unit) is the heat required to raise 1 pound of water 1°F
1 BTU = 252 cal = 0.252 kcal
1 cal = 4.187 Joules
BTU X 1.055 = Kilo Joules
BTU divided by 3,413 = Kilowatts
To convert from Fahrenheit to Centigrade: (° F – 32) times 5/9, or .556, equals degrees C.
One gallon of (120 ° F, 49 ° C) water weighs approximately 8.25 pounds.
Pounds X .45359 = Kilogram
Gallons X 3.7854 = Liters
% of Hot = (Mixed Temp. – Cold) divided by (Hot Temp. – Cold)
% Thermal Efficiency = (GPH X 8.25 X Temp. Rise X 1.0) divided by BTU/H Input
BTU Output = GPH X 8.25 X Temp. Rise X 1.0
GPH = (BTU/H Input X % Eff.) divided by (Temp. Rise X 8.25)
One cubic foot of Natural Gas contains about 1000 BTU of heat.
One “therm” is equal to 100,000 BTU
One cubic foot of Propane Gas contains about 2500 BTU of heat.
One gallon of Propane gas contains about 91,250 BTU of heat.
One pound of Propane gas contains about 21,600 BTU of heat.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
GENERAL INFORMATION
One pound of gas pressure is equal to 27.7 inches water column pressure
Inches of Water Column X .036091 = PSI
Inches of Water Column X .073483 = Inches of Mercury (Hg.)
Centimeters = Inches X 2.54
MM (millimeters) =Inches X 25.4
Meters = Inches X .0254
Doubling the diameter of a pipe will increase its flow capacity (approximately) 5.3 times.
Construction: Tank is constructed of steel.
The inside of the tank is constructed of a glass lining bonded to the steel. This prevents water to metal contact
and rusting of the tank.
An anode rod will be installed within the tank. The hex-head plug end of the anode is visible on the top of the
water heater. This metal rod offers secondary protection of the tank against corrosion where the application of
glass is not possible (threaded tank openings). These areas will have small areas of water to metal contact.
All water heaters will contain at least one thermostat (to operate the heater) and one high limit (to prevent
water temperatures approaching the “steam” level).
40
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
41
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
42
Download from Www.Somanuals.com. All Manuals Search And Download.
43
Download from Www.Somanuals.com. All Manuals Search And Download.
ALL TECHNICALAND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED. IF YOU
ARE UNSUCCESSFUL, CONTACT STATE WATER HEATERS RESIDENTIALTECHNICALASSISTANCE 1-800-365-0024 OR WWW.STATEWATERHEATERS.COM.
44
Download from Www.Somanuals.com. All Manuals Search And Download.
|