Schneider Electric Water Dispenser ACRC500 User Guide

Operation and Maintenance Manual  
InRow® Chilled Water Cooling Units  
InRow® RC  
ACRC500, ACRC501, ACRC502  
990-3237B-001  
Publication Date: November 2014  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
InRow RC Operation and Maintenance Manual  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
InRow RC Operation and Maintenance Manual  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
InRow RC Operation and Maintenance Manual  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General Information  
Important Safety Information  
Read the instructions carefully to become familiar with the equipment before trying to install, operate, service,  
or maintain it. The following special messages may appear throughout this manual or on the equipment to warn  
of potential hazards or to call attention to information that clarifies or simplifies a procedure.  
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard  
exists which will result in personal injury if the instructions are not followed.  
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all  
safety messages that follow this symbol to avoid possible injury or death.  
DANGER  
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death  
or serious injury.  
WARNING  
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death  
or serious injury.  
CAUTION  
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in minor  
or moderate injury.  
NOTICE  
NOTICE addresses practices not related to physical injury including certain environmental  
hazards, potential damage or loss of data.  
InRow RC Operation and Maintenance Manual  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Safety Notices During Operation  
Read and adhere to the following important safety considerations when working with this equipment. Follow all  
local and national regulations when handling refrigerants. Service to the components in the refrigeration loop  
should be performed only by a certified HVAC technician.  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work  
practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced by qualified personnel only.  
• Turn off all power supplying this equipment before working on or inside the equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors, and covers before turning on power to this equipment.  
Failure to follow these instructions will result in death or serious injury.  
WARNING  
HAZARD FROM MOVING PARTS  
Keep hands, clothing, and jewelry away from moving parts. Check the equipment for  
foreign objects before closing the doors and starting the equipment.  
Failure to follow these instructions can result in death, serious injury, or  
equipment damage.  
WARNING  
HAZARD TO EQUIPMENT OR PERSONNEL  
All work must be performed by Schneider Electric qualified personnel.  
Failure to follow these instructions can result in death, serious injury, or  
equipment damage.  
CAUTION  
HAZARD TO EQUIPMENT OR PERSONNEL  
Ensure that all spare parts and tools are removed from the equipment before operating it  
Failure to follow these instructions can result in injury or equipment damage.  
2
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTICE  
STATIC ELECTRICITY HAZARD  
Circuit boards contained within this unit are sensitive to static electricity. Use one or more  
electrostatic-discharge device while handling the boards.  
Failure to follow these instructions can result in equipment damage.  
InRow RC Operation and Maintenance Manual  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Commissioning  
After installation, complete the following checklists to verify that all components are working properly and that  
the equipment is ready to begin operation.  
Checklists  
Initial inspection checklist  
The initial inspection ensures that the equipment has been properly installed, the location of the cooling unit has  
been properly prepared and the cooling unit is free of damage.  
WARNING  
DAMAGE TO EQUIPMENT OR PERSONNEL  
Do not run service utilities in front of the fan outlet.  
Failure to follow these instructions can result in death, serious injury, or  
equipment damage.  
NOTE: The vapor barrier minimizes moisture infiltration. Without a vapor barrier, it will be difficult to maintain  
the humidity in the room. Do not introduce unconditioned outside air into the space.  
Ensure that:  
The installation procedure is complete according to the requirements of this installation manual.  
The walls, floor, and ceiling of the room where the cooling unit is located are sealed with a vapor barrier.  
There is no evidence of damage to the cooling unit.  
The clearance around the equipment is in accordance with local and national codes and regulations as well  
as this installation manual.  
The cooling unit is level and joined to the adjacent racks  
The cooling unit is not installed at the open end of a row.  
4
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Electrical inspection checklist  
The electrical inspection verifies that all electrical connections are secure and correct and that the equipment is  
properly grounded.  
WARNING  
ELECTRICAL HAZARD  
• Electrical service must conform to local and national electrical codes and regulations.  
• The equipment must be grounded.  
Failure to follow these instructions can result in death, serious injury, or  
equipment damage.  
Ensure that:  
Incoming voltages match the phase and voltage listing on the nameplate.  
Electrical wiring complies with local and national codes and regulations.  
Equipment is properly grounded.  
Front door is properly grounded.  
Electrical connections are tight, including contactors, terminal blocks, controllers, switches, relays, auxiliary  
devices, and field connections.  
Circuit breakers are properly connected and securely attached to the DIN rail.  
InRow RC Operation and Maintenance Manual  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Mechanical inspection checklist  
The mechanical inspection verifies that all mechanical components and connections are secure.  
CAUTION  
PIPING INSTALLATION  
Failure to properly install piping may result in improper cooling unit operation or possible  
damage to the cooling unit or surrounding equipment.  
Failure to follow these instructions can result in equipment damage.  
Ensure that:  
Condensate drain line is at least the size of the drain connection.  
Mechanical connections are tight.  
Fans are turning freely and the blades are not distorted or bent.  
Pipe fittings are tight.  
Air is bled from the water system. If air remains in the system, bleed it out now.  
Supply chilled water temperature is recorded.  
Chilled water flow is correct based on the performance requirements of the cooling unit.  
Field-installed traps and piping are in accordance with the installation manual. Strainers are in place in the  
chilled water supply loop. Proper piping practices have been followed.  
Piping is adequately supported and isolated when necessary.  
Field-installed service valves are open.  
Water outlet temperature sensor is positioned correctly. For top-connected cooling units, the wire with only a  
green wire tie is positioned in connector J23. For bottom-connected cooling units, the wire with both green  
and white wire ties is positioned in connector J23.  
Piping in the building and on the roof is properly insulated.  
Covers and guards are in place.  
6
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
User interface inspection checklist  
The user interface inspection verifies that the sensors and internal communication links are installed properly.  
Check that the outdoor heat exchanger is connected to the cooling unit and to the other cooling units in the  
room if you are using cooling group controls.  
Ensure that:  
An A-Link bus is connected to each cooling unit and a terminator is plugged into all unused A-Link  
connectors.  
The input contacts and output relays are connected correctly.  
The building management system is connected correctly and a terminator is wired into the final cooling unit.  
The temperature sensors located on the front of the equipment are connected correctly.  
The rack temperature sensors are installed correctly.  
The network port is connected correctly and an IP address has been assigned to the cooling unit.  
The optional rope water detection device is installed properly.  
Start-up inspection checklist  
The start-up inspection ensures that the equipment is operating properly after the initial start-up. This inspection  
verifies that all modes of operation are working correctly and that the cooling unit is ready for normal operation.  
While the equipment is operating, ensure that:  
The cooling unit is free from malfunctions, including chilled water leaks, unusual vibrations, or other  
irregularities, in each mode of operation.  
The current draw of fan motors and transformers for the cooling operation is within the ratings of the  
respective circuit breakers.  
Record the current at the main power connection of the main circuit breaker.  
Record all current draws on the load side of any circuit breakers used for each device.  
Compare the circuit breaker setting for each device to the actual current measured and the full load amps of  
the device to verify that the current draws are acceptable.  
Feed B can supply power to all functions in the equipment.  
The cool cycle engages.  
The correct water outlet temperature sensor is positioned in connector J23.  
Air filters are clean and free of debris. Replace air filters as needed.  
The clogged filter alarm is operating properly.  
Cover 1/3 of the filter area to initiate the alarm.  
Final inspection checklist  
The final inspection verifies that the system is clean, and the start-up form has been sent to Schneider Electric.  
Ensure that:  
The system is clean and free from debris.  
Packaging materials are disposed of properly.  
The start-up form was completed and sent to Schneider Electric.  
InRow RC Operation and Maintenance Manual  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
Display Interface  
Status  
ESC  
?
Check  
Log  
Warning  
Critical  
Item Description  
Function  
Critical Alarm LED (red)  
When lit, a critical alarm condition exists and requires your  
immediate attention.  
Warning Alarm LED (yellow)  
Check Log LED (yellow)  
When lit, a warning alarm condition exists. Failure to correct this  
condition could cause a critical alarm.  
When lit, at least one new event has been logged since the last time  
the log was checked. Only events that pertain to the operation of the  
cooling unit will activate the LED.  
Status LED (green)  
When lit, the cooling unit is receiving electrical power. When flashing  
green, the cooling unit is downloading firmware for the controller.  
This takes several minutes.  
Liquid Crystal Display (LCD)  
View alarms, status data, context-sensitive help, and modify  
configurable items.  
UP and DOWN arrow keys  
ESC key  
Select menu items and access information.  
Return to previous screen or cancel current operation.  
ENTER key  
Open menu items and input changes to cooling group level and  
cooling unit level settings.  
HELP key  
Display context-sensitive help. Press the HELP key for information  
about each option on the screen and for instructions on performing  
tasks.  
8
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Using the Display  
Every time you apply power to the cooling unit, the display interface initializes, causing the LEDs to cycle and  
the alarm-tone to activate.  
Scrolling status screens  
After start-up, the interface displays the firmware revision number of the display interface. The display interface  
then scrolls automatically and continuously through screens of status information. Press the up or down arrow  
key to interrupt the automatic scrolling and view a specific status screen. To return to the scrolling status  
screens, press ESC from one of the main menu screens.  
Status Screen Name  
Status Information Displayed  
InRow RC  
• On/Standby  
• Unit identifier  
• Cooling Unit name  
• Cooling Unit location  
Group  
Unit  
• Alarms/No Alarms  
• Cool Outpt (Cool Output) kW  
• Cool Setpt (Cool Setpoint) °C (or °F)  
• Max Rack (Maximum Rack Temperature) °C (or °F)  
• Alarms/No Alarms  
• Cool Output kW  
• Max Rack In (Maximum Rack Inlet Temperature) °C (or °F)  
• Air Flow l/s (liters per second) or CFM (cubic feet per minute)  
Main menu screens  
On any top-level status screen, press the ENTER or ESC key to open the first  
main menu screen.  
NOTE: Once a period of inactivity (at the keys of the display interface)  
exceeds the Password Timeout setting, the display interface returns to  
the scrolling status screens.  
On/Standby  
View Alarms  
Clear Alarms  
View Event Log  
Clear Event Log  
Configure Modbus  
Set Date & Time  
Set Password  
For information on setting the time-out duration, see  
Set Display Units  
Configure Display  
Configure Network  
All main menu choices are displayed on a series of six main menu screens.  
Navigating the main menu  
About InRow RC  
Set Identification  
Service Intervals  
Selector arrow: Press the up or down arrow key to move the selector arrow  
to a main menu option. Press the ENTER key to view the selected sub-menu  
screen. In the example shown below, the selector arrow points to the Set Date  
and Time setting. To select that item, press the ENTER key.  
View Run Hours  
Configure Unit  
Configure Group  
Set Group PIDs  
Time: 13:15:23  
Date: 18-Nov-2010  
Format: dd/mm/yyyy  
View Group Status  
View Unit Status  
Set Group Setpoints  
Set Unit Threshlds  
NOTE: If the selector arrow is on the top line of a main menu screen, press the  
up arrow key to move the selector arrow to the top line of the previous screen.  
InRow RC Operation and Maintenance Manual  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Continue arrows: Continue arrows indicate that additional options or settings are available on a menu or  
status screen. Press the up or down arrow key to view the additional items.  
Clear Event Log  
Configure Modbus  
Set Date & Time  
Set Password  
Navigating sub-menus  
Selecting a option displays the sub-menu screen for that option. In this example, the selector arrow is on the  
top line of the Set Date and Time sub-menu screen.  
Time: 13:15:23  
Date: 18-Nov-2010  
Format: dd/mm/yyyy  
Use the up or down arrow key to move the selector arrow to an option, and press the ENTER key.  
List of choices: If the setting is a list of choices, an input arrow displays next to the setting. Press the  
up or down arrow key to select the menu option to change. Then press the ENTER key to exit the input  
mode and save the setting. Press the ESC key to exit without saving.  
Numbers or text fields: If the setting is a number or text field, use the arrow keys to select the value of  
the first character, and press the ENTER key to move to the next character. Press the ENTER key after  
the last character is set to exit the input mode and save the setting. Press the ESC key to exit without  
saving. If an invalid value is entered, the display interface beeps and restores the previous valid value to  
the field.  
Input arrows: Input arrows next to a selected setting indicate that the setting can be modified by pressing  
the up or down arrow key. Press the ENTER key to save the change or the ESC key to cancel the change.  
Time: 13:15:23  
Date: 18-Nov-2010  
Format: dd/mm/yyyy  
Using the Path statement  
Select the main- and sub-menu options specified in the path statement to view or configure a setting. The path  
statement lists the main- and sub-menu items you select to navigate to the item to view or modify. The parts of  
the path statement are defined below:  
Path: Main > Set Password > Change Passwords  
Main >: Your starting point is the main menu.  
Set Password >: Scroll to and select this option from the main menu.  
Change Passwords >: Scroll to and select this option from the sub-menu.  
Subsequent options are listed and defined under the path statement.  
10  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Password entry  
The cooling unit has two levels of password protection:  
Device password allows Device Users to change basic and environmental settings.  
Admin password allows all privileges granted for Device Users, and also allows the Administrator to  
modify settings that control the components in the cooling unit or change advanced options.  
When you try to change a setting, the display interface prompts you to enter your Admin password. The default  
value for both the Device and Admin password is apc (lowercase). To enter your password, use the up or down  
arrow key to scroll through the available character set. Press the ENTER key to select the current character  
and move the cursor to the next character position. After selecting the last character of your password, press  
the ENTER key once more to submit your password.  
Once the password is entered, it remains in effect until the period of inactivity exceeds the Password Timeout  
setting.  
NOTE: Passwords are case sensitive.  
Start the cooling unit  
Path: Main > On/Standby  
1. To start the cooling unit, press the ENTER key until the cursor is on the Operation > On/Standby menu  
item.  
2. Press the ENTER key again to show the toggle state arrow to the right of Operation.  
3. Use the up and down arrow keys to change from Standby to On.  
See “Path: Main > Operation > Limit Access” below if you are prompted to enter a password  
before changing the On/Standby setting.  
4. Press the ENTER key again to set the On position.  
a. The fans will start.  
b. The cooling unit will run according to the configured settings.  
NOTE: On/Standby only affects the local cooling unit. You must set the On/Standby option for each  
cooling unit in the cooling group.  
Path: Main > Operation > Limit Access  
The default setting for the Limit Access password protection option is No. If the Limit Access option has been  
set to Yes, you will be prompted to enter the Device password before a change can be made to the On/  
Standby setting.  
InRow RC Operation and Maintenance Manual  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Stop the cooling unit  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work  
practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced by qualified personnel only.  
• Turn off all power supplying this equipment before working on or inside the equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors, and covers before turning on power to this equipment.  
Failure to follow these instructions will result in death or serious injury.  
CAUTION  
STANDBY OPTION  
The Standby option does not remove power from the cooling unit. You must disconnect  
power at the mains to remove power from the cooling unit.  
Failure to follow these instructions can result in equipment damage.  
1. To stop the cooling unit, press the ENTER key until the cursor is on the Operation > On/Standby menu  
item.  
2. Press the ENTER key again to show the toggle state arrow to the right of Operation.  
3. Use the up and down arrow keys to change from On to Standby.  
See “Path: Main > Operation > Limit Access” on page 11 if you are prompted to enter a  
password before changing the On/Standby setting.  
4. Press the ENTER key again to change the setting to Standby. The cooling unit will enter the standby  
mode.  
12  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
General Configuration  
The configuration options are set during the commissioning of the cooling units in the cooling group.  
NOTE: All changes to settings must be performed by qualified personnel.  
Cooling unit configuration  
Path: Main > Configure Unit > General  
Capacity: Set the cooling capacity of the cooling unit:  
Auto: The cooling unit automatically controls its output under normal (default) conditions.  
Max: The cooling unit runs at full capacity.  
NOTE: Normal checks for cooling failures are disabled in the Max mode.  
Start-up Dly: Enter a value for the delay. The start-up delay begins when the cooling unit is started and  
initialized. The cooling unit cannot begin operation until this delay expires. Use the start-up delay to restart  
equipment sequentially in your room after a scheduled downtime or a power outage.  
Idle on Fail: When set to Yes, the cooling unit will enter idle mode if the cooling unit is unable to supply  
conditioned air. Set to No to disable the cooling unit from entering idle mode if a Cooling Failure is detected.  
Idle On Leak: When set to Yes, the cooling unit will enter idle mode if a Water Detection Fault activates. Set to  
No to disable the cooling unit from entering idle mode if a leak is detected.  
NOTE: The leak sensor (part number AP9325) is optional.  
NOTE: There are three alarms that will cause the cooling unit to enter idle mode:  
• Water Detection Fault (when Idle On Leak is set to Yes)  
• Condensate Pan Full  
• Cooling Failure (when Idle On Fail is set to Yes)  
Bypass Vlve (Bypass Valve): Select the setting that matches the physical status of the bypass valve (open or  
closed).  
Fluid Cal: Causes the input valve to stay fully open to facilitate adjusting water flow through multiple cooling  
units.  
Role Override: Set to ON, forces the cooling unit to be the Primary cooling unit in the group. Set to Auto,  
allows the system to choose the role of the cooling unit. Choose ON if you have Runtime Balancing enabled  
InRow RC Operation and Maintenance Manual  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Contacts  
View the state of input and output contacts  
Path: Main > Configure Unit > Discrete I/O  
Each cooling unit supports a user-defined input contact and a user-defined output contact. Each contact  
monitors a sensor and responds to changes in the state of the sensor (open or closed).  
Input State: Indicates the actual state of the input contact (open or closed). A cooling unit is On when the state  
is normal and in Standby when the state is not normal.  
Output State: Indicates the actual state of the output contact (open or closed). An alarm will cause the output  
contact to change from the normal state.  
Edit the normal state of input and output contacts  
Path: Main > Configure Unit > Discrete I/O > Normal State  
You can set input contacts to cause alarm conditions based on a user-defined normal state. Output contacts  
can map internal alarms and events to outside devices.  
Input Norm: Set the normal state of the contact (open or closed). The cooling unit changes its operating mode  
to Standby when the actual state differs from the normal state.  
Output Norm: Set the normal state of the contact (open or closed). If the state of an alarm or event mapped to  
this contact changes from the normal state, the contact also changes state.  
Output Src: Define the type of output alarm, either Any Alrm or Critical, that causes the output to change  
from its normal state.  
14  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Cooling Group Configuration  
Use the configuration settings to add cooling units to the group and to define group operation. The system  
automatically assigns the state of Backup to units in the group. A unit whose Role Override setting is set to ON  
will automatically be set as a Primary cooling unit. A unit in the Standby or Failed state is not considered a  
potential backup unit. The system periodically reviews the state of the units to maintain the proper number of  
ON and Backup units. If no units are available to assign to the Backup role, then the No Backup Units Available  
alarm is initiated.  
NOTE: All changes to settings must be performed by qualified personnel.  
Configure the cooling group  
Path: Main > Configure Group  
The Configure Group menu contains settings that identify the number of cooling units installed in this cooling  
group and the physical arrangement of those cooling units.  
Num Units: Enter the number of cooling units in this cooling group. Up to 12 cooling units can be joined  
together to work as a single cooling group.  
Type: Set the rack deployment strategy for the cooling units of this cooling group.  
In-Row: Air flow is not ducted. Hot aisle air is cooled, then shared by all loads in the row.  
RACS: (Rack Air Containment System). Air flow in the enclosure is controlled by a ducting system fitted  
to the enclosure.  
HACS: (Hot Aisle Containment System). Air flow in the room is controlled by enclosing the hot air aisle.  
The loads share an enclosed common hot aisle.  
%Glycol: The percentage of glycol used by the Cooling Group to cool the environment. Only qualified service  
personnel should make changes to this setting.  
Fan Cntrl: This selection allows air flow to be controlled automatically by the cooling unit or manually by user-  
selected fan speed preference.  
Auto: Air flow is automatically controlled by the cooling unit.  
Manual: The air flow is fixed to the value of the Fan Speed Preference property. See “Fan Spd: Set the  
fan speed preference that will give you the desired temperature difference (DT). Each fan speed  
provides an approximate DT between the supply air from the Rack PDU and the air returned from the  
rack.” on page 18 for more information.  
InRow RC Operation and Maintenance Manual  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Identify the cooling unit  
Path: Main > Set Identification  
The Set Identification menu contains settings that identify the name and location of the cooling unit.  
Unit Id: Assign a unique identification number to this cooling unit. Range: 1 through 12.  
Name: Assign a Name, up to 40 alpha-numeric characters, to the cooling unit.  
Location: Enter the Location, up to 40 alpha-numeric characters, of the cooling unit.  
NOTE: Only the first 19 characters (of the 40 that are possible to enter) will display on the display interface.  
You must use Telnet, the Control console or the Web to access all 40 characters. See “Web interface” on  
Configure Modbus  
Path: Main > Configure Modbus  
Use the Configure Modbus menu to set up communications between the cooling unit and the building  
management system.  
Modbus: Enable or disable Modbus communication protocol.  
Target Id: Each Modbus device must have a unique target identification number. Enter a unique number for  
this cooling unit.  
Baud Rate: Set either 9600 bps or 19200 bps.  
Fixed settings: 8 data bits, no parity, 1 stop bit. These settings cannot be modified.  
16  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Control the Environment  
The primary function of the cooling unit is to cool air from the hot aisle and deliver it to the cold aisle at the  
temperature setpoint. The control strategies employed by the cooling unit depend upon the deployment  
strategy of the cooling group.  
In an in-row environment, the cooling unit supplies constant-temperature supply air to the common cold aisle.  
The fan speed is modulated to ensure that the desired volume of air reaches the IT equipment. The fan speed  
is determined by the difference between the cooling setpoint and the maximum rack air inlet temperature.  
In a HACS or RACS environment, the cooling unit neutralizes the heat accumulated in the common hot aisle  
and expels it back into the surrounding environmental space while maintaining the desired temperature in the  
cold aisle.  
How the Cool mode works  
Cool: Cooling control is varied based on configuration:  
• InRow: The equipment maintains the supply air temperature setpoint by regulating the flow of chilled  
water through the cooling coil. The evaporator fan speed is controlled by comparing the rack inlet  
temperature to the cooling setpoint. As the rack temperature increases compared to the cooling setpoint,  
the fans increase output to maintain the setpoint. As rack temperature decreases compared to the  
cooling setpoint, the fans decrease output to maintain the setpoint.  
• RACS/HACS: The supply air setpoint is maintained the same way as with the InRow configuration. The  
fan speed is controlled by the fan speed preference setting. The fan speed can be selected based on the  
temperature differential across the cooling unit. As actual supply and return temperatures deviate from  
the fan speed preference setting, the fan speed increases to bring the temperature difference back down  
to the setpoint or decreases fan output to increase the unit temperature differential.  
Fluid Calibration Mode: Runs the cooling unit with the valve fully open and at minimum fan speed. This  
special mode is typically used to balance the fluid flow in multiple units or in one unit. This mode generates a  
critical alarm. The cooling unit will take some time to return to normal operation once the Fluid Calibration Mode  
is turned off.  
See Supply Air and Return Air on page 24 for more information.  
Setpoints  
Path: Main > Set Group Setpoints  
A setpoint is the target value that a cooling group tries to maintain in the rack. The default setpoints are  
appropriate for most cooling applications.  
The setpoints for each mode must be within the following ranges:  
Cool: 18.0–25.0°C (64.4–90.0°F)  
Supply Air: 17.0–23.0°C (59.0–86.4°F)  
NOTE: The Supply Air setting is defined when the cooling group is commissioned. This task is  
performed by authorized personnel only.  
InRow RC Operation and Maintenance Manual  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
NOTE: If the Supply Air setpoint is greater than the Cool setpoint, the cooling unit triggers an alarm  
and resets the Supply Air setpoint to equal the Cool setpoint.  
Fan Spd: Set the fan speed preference that will give you the desired temperature difference (DT). Each  
fan speed provides an approximate DT between the supply air from the Rack PDU and the air returned  
from the rack.  
–Low = 16.7°C (30°F) DT (60% of maximum fan speed)  
– Med-Low = 13.9°C (25°F) DT (70% of maximum fan speed)  
– Med = 11.1°C (20°F) DT (80% of maximum fan speed)  
– Med-High = 6.3°C (15°F) DT (90% of maximum fan speed)  
– High = 5.6°C (10°F) DT (100% of maximum fan speed)  
NOTE: The cooling group will automatically override this fan speed setting and adjust the fan speed  
to provide optimum cooling for the environment as needed.  
PID settings  
Path: Main > Set Group PIDs  
The Proportional plus Integral plus Derivative (PID) loop controls the output of the fans.  
NOTE: All changes to settings must be performed by qualified personnel.  
Gain (P): The proportional multiplier (gain) for this mode or actuator. The proportional multiplier adjusts for the  
difference (error) between the measured value and the setpoint.  
Rate (I): The integral multiplier (reset rate) for this mode or actuator. The integral multiplier adjusts for error  
measurement and the amount of time that the error has existed. The integral multiplier adds to or subtracts  
from the output in small increments to correct for the offset error caused by the proportional contribution.  
Deriv (D): The derivative multiplier (derivative) for this mode or actuator. The derivative multiplier adjusts the  
output for rapid changes in the error, correcting for the rate of change of the error over time.  
18  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Tune the PID loop  
Tune the PID loop to optimize the performance of the cooling group.  
NOTE: This procedure is to be performed by Schneider Electric authorized personnel only. The PID loop must  
be tuned after the equipment in the room is installed and running. The loop should be tuned periodically to  
account for changes in the room load.  
1. Adjust the integral and derivative constants to zero and the proportional constant to 1.0.  
2. Set the temperature setpoint value and start the cooling group.  
3. When the temperature reaches a stable value, increase the proportional constant by 0.5. If the  
temperature does not respond to this change, adjust the setpoint.  
4. Repeat step 3 until the temperature value starts to oscillate and the peak amplitude of the oscillations is  
constant.  
5. Note the time, in minutes, between the peaks of the oscillations. This is the Ultimate Period, P  
U.  
6. Note the value of the proportional constant. This is the Ultimate Gain, G  
U.  
7. Compute the PID constants using the table below. Use the equations for that control method in the row  
to compute the values for each constant.  
Control Method Proportional  
Integral  
Derivative  
P
0.5*G  
U
P + I  
P + I + D  
0.45*G  
0.54*G /P  
U
U
U
0.6*G  
1.2*G /P  
U U  
0.075*G *P  
U
U
U
8. Set each constant according to these calculations.  
You may need to further tune the PID loop in the following ways to account for changes in the room load:  
Loop Behavior  
Slow response to temperature changes  
PID Tuning Correction  
Increase the proportional multiplier or increase the  
derivative multiplier.  
Overcooling/undercooling after changes in the room Increase the derivative or the proportional multiplier.  
load or changes in setpoint  
Environmental temperature never reaches the  
setpoint  
Increase the integral multiplier.  
Overcooling/undercooling on constant room load  
Decrease the integral multiplier.  
InRow RC Operation and Maintenance Manual  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Run hours  
The cooling unit records the number of hours each of its components has operated. When a component is  
replaced, use the Reset Run Hours option to reset the run hours for the displayed component to zero.  
Path: Main > View Run Hours  
Components:  
• Air Filter  
– Reset Run Hours  
NOTE: Replace air filters with Schneider Electric air filters only.  
• Fans  
– Fan Number  
• Reset Run Hours  
• Condensate Pump  
– Reset Run Hours  
Thresholds  
Set alarms to alert you to threshold violations.  
Path: Main > Set Unit Thresholds  
When the monitored input violates the unit threshold, an alarm will occur. Set thresholds for the following  
sensors:  
Rack Inlet: The temperature of the air entering the rack at the rack inlet sensor.  
Supply Air: The average temperature of the air output from the cooling unit, measured by the upper and  
lower supply air temperature sensors.  
Return Air: The temperature of the air entering the cooling unit at the temperature sensor.  
Inlet Fluid: The temperature of the chilled water entering the cooling unit  
Service intervals  
Path: Main > Service Intervals  
The service interval depends on environmental cleanliness. Each component interval setting has an alarm. If  
enabled, the alarm will sound when the component interval has elapsed. The alarm is cleared by selecting  
Clear Alarms in the main menu. Set the number of weeks to service the following:  
• Air Filter Interval: The default is 18 weeks.  
Condensate Pump Interval: The default is 52 weeks.  
Fan Interval: The default is 52 weeks.  
NOTE: The Air Filter interval alarm is enabled by default. The Condensate Pump and Fan interval  
alarms are disabled by default.  
20  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Display Settings  
Set display interface settings, including time and date, units, passwords, and time-out. You can also adjust the  
contrast, key click, beeper volume, and beep on alarm settings.  
Password & timeout  
Path: Main > Set Password  
NOTE: The default user password is apc (lowercase). See “Password entry” on page 11 for more information  
on how to enter the password.  
Change passwords: Set the Admin and Device passwords.  
1. Move the selector arrow next to the Change Passwords option and press the ENTER key.  
2. Select the password to change (either Admin or Device).  
3. Enter a new password (up to 8 characters).  
4. Press the ENTER key to confirm.  
Timeout: Set the length of time which can elapse when no keys are pressed before the display interface  
returns to the scrolling screen status. The password must then be entered to regain access.  
Invalidate: Override the password timeout and require password entry immediately.  
Date & time  
Path: Main > Set Date & Time  
Set the time: Enter the correct time, and press the ENTER key. The Time is displayed on some status screens  
and is also used in the alarm and event logs to time-stamp events.  
Set the date: Enter the day, month, and year, and press the ENTER key. The Date is displayed on some status  
screens and is also used in the alarm and event logs to date-stamp events.  
Set the format: Use the up or down arrow key to select the date Format setting.  
• mm/dd/yyyy (11/16/2007) (Default)  
• yyyy-mm-dd (2007-11-16)  
• dd-mmm-yy (16-Nov-07)  
• mmm-dd-yy (Nov-16-07)  
• dd.mm.yyyy (16.11.2007)  
Adjust display  
Path: Main Menu > Configure Display  
Contrast: Adjust the visibility of the screen text. Lower numbered settings provide darker text; higher numbers  
provide lighter text. Settings range from 0–7.  
Key Click: Enable or disable an audible tone every time a key is pressed on the display interface.  
Beeper Volume: Set the volume of the display interface alarm tone, and for the audible tone that sounds every  
time a key is pressed on the display interface.  
Beep On Alarm: Set the cooling unit to sound an audible tone every 30 seconds when a new alarm occurs.  
Silence the audible tone by pressing any key on the display interface. When the alarm clears itself, the tone will  
stop on its own.  
InRow RC Operation and Maintenance Manual  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Display units  
Path: Main Menu > Set Display Units  
Set the units of measure for the cooling unit to either US or Metric.  
22  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Network Configuration  
The cooling unit is shipped with a Network Management Card (NMC) that enables you to manage the cooling  
unit over your network. Configure the network settings for the Network Management Card from the display  
interface. The management card allows remote control and configuration of the cooling unit.  
Configure the network  
Path: Main > Configure Network  
MAC Address: Displays the unique network identifier assigned to the Network Management Card of the  
cooling unit installed in the cooling unit at the factory.  
IP Address: You will be prompted to enter an Admin password. Enter the password and press ENTER to  
return to the IP screen. Press ENTER again to change the following settings for Manual boot mode only.  
IP: Enter the IP address assigned to the Network Management Card of the cooling unit.  
SM: Enter the subnet mask for the Network Management Card of the cooling unit.  
GW: Enter the default gateway for the Network Management Card of the cooling unit.  
Boot Mode: Set the method by which the Network Management Card of the cooling unit will acquire its network  
settings.  
Manual: Enter the IP Address, subnet mask, and default gateway using the IP Address menu.  
BOOTP: Set the Network Management Card of the cooling unit to obtain its network settings from a  
BOOTP server.  
DHCP: Set the Network Management Card of the cooling unit to obtain its network settings from a DHCP  
server.  
By default, DHCP requires an Schneider Electric cookie before it will accept an IP address.  
See “DHCP:” on page 32 for more information.  
BOOTPDHCP: Set the Network Management Card of the cooling unit to search for its network settings  
from either a BOOTP or a DHCP server.  
InRow RC Operation and Maintenance Manual  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
View Status Readings  
The display interface has several options for viewing the status of the cooling unit, the cooling group to which  
the cooling unit belongs, and the environment being controlled. The status readings for the cooling unit are  
available under the View Unit Status option in the main menu, and status readings for the cooling group are  
available under the View Group Status option on the main menu or on the scrolling status screens.  
Scrolling status screens  
When the display interface is idle, it scrolls through screens of status information. Press the up or down arrow  
key to interrupt the automatic scrolling and view a specific status screen.  
Cooling unit status  
Path: Main > View Unit Status  
View information specific to this cooling unit.  
Op Mode (Operating): The cooling unit is in one of the following modes:  
On: The cooling unit is cooling.  
PreStart: The cooling unit is initializing and establishing communication with the controller. During  
PreStart, the valve of the cooling unit opens at 35%. The fans will start at 30% and stay on at that rate for  
10 minutes.  
Standby: The cooling unit is receiving power but not enabled for cooling.  
Idle: The cooling unit is not operating in normal mode due to active alarms.  
For more information, see “Idle On Leak:” on page 13.  
Cool Outpt (Output): The actual cooling output of the cooling unit.  
Cool Demnd (Demand): The amount of cooling that the heat load currently requires.  
Supply Air: The average temperature of the air leaving the cooling unit, as measured by the upper and lower  
supply air temperature sensors.  
Return Air: The temperature of the air entering the cooling unit.  
Max Rack In (Maximum): The highest reading of the three rack inlet temperature sensors determines the rack  
temperature.  
Power Source: The source of power to the cooling unit.  
Rack In #n: The temperature of the air entering the rack at the remote temperature sensor.  
Fluid In: The temperature of the chilled water as it enters the cooling coil.  
Fluid Out: The temperature of the chilled water as it leaves the cooling coil.  
Fluid Flow: The amount of chilled water that flows through the cooling unit.  
Fluid Vlv Pos (Fluid Valve Position): The position of the valve that controls how much chilled water enters  
the cooling unit.  
Air Flow: The amount of air required to maintain the setpoint temperature.  
Fan Speed: The speed of the fans that regulate the air flow through the cooling unit.  
Filter DP (Differential Pressure): The filter differential pressure displayed in the Water column in inches or in  
pascals.  
Sply Humid (Supply Humidity): The humidity of the air leaving the cooling unit.  
24  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Cooling group status  
Path: Main > View Group Status  
View information about the cooling group.  
Max Rack (Maximum): The highest rack temperature reported by any cooling unit in the cooling group.  
Min Rack (Minimum): The lowest rack temperature reported by any cooling unit in the cooling group.  
Air Flow: The combined airflow output of the cooling units in the cooling group.  
Cool Output: The combined output of the cooling group.  
Cool Demnd (Demand): The cooling output required to meet the current heat load of the conditioned space.  
Cool Setpt (Setpoint): The temperature you set to maintain the room environment.  
About the cooling unit  
Path: Main > About InRow RC  
View identifying information that is helpful when obtaining service:  
Model: Model number  
S/N: Serial number  
F/W: Display interface firmware revision  
H/W: Hardware revision  
Made: Date of manufacture  
RP APP: Application version  
AOS Ver: Operating system version  
InRow RC Operation and Maintenance Manual  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Event Log  
The event log saves status information and a message each time a change in the cooling group is detected.  
Alarms and events are recorded in the log and displayed on the active alarms screen. Status events  
(informational) and system configuration changes are only displayed in the event log.  
View event log  
Path: Main > View Event Log  
The event log keeps a record of all alarms and events. The screen displays the following:  
• The name of the event.  
• The time and date the event occurred.  
Use the arrow keys to scroll through the list of events and display the date and time for each event.  
Clear event log  
Path: Main > Clear Event Log  
A confirmation screen is displayed when you select this option. Enter the Admin password to erase the log.  
Select YES to erase all of the events in the log. Select NO to return to the main screen.  
26  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Respond to Alarms  
When an alarm is triggered, the cooling unit alerts you through the display by the following methods:  
• Active alarm screen entry on scrolling status screens  
• LEDs on the front panel display  
• An optional audible alarm every 30 seconds, if enabled  
View active alarms  
Path: Main > View Alarms  
The View Alarms screen provides the number of alarms, the severity, and a brief description of the alarm.  
Press the arrow keys to view the rest of the list.  
Clear active alarms  
Path: Main > Clear Alarms  
A confirmation screen is displayed when you select this option. Enter the Admin password to clear the alarm  
list. Select YES to clear all of the alarms in the list. Select NO to return to the main screen. If the conditions that  
caused the alarm still exist, those conditions cause the alarm to be regenerated.  
Alarm messages and suggested actions  
Alarm Message  
Severity  
Warning • A hardware failure exists.  
• For assistance, contact Customer Support.  
Warning • Clean or replace the air filter.  
• If the problem persists, contact Customer Support.  
Action Required  
Air Containment Pressure  
Sensor Fault  
Air Filter Clogged  
Air Filter Run Hours Violation  
Warning • Reset the Air Filter Run Hours after the air filter is cleaned or  
replaced.  
A-Link Isolation Relay Fault  
Coil Fluid Valve Actuator Fault  
Critical • For assistance, contact Customer Support.  
Critical • A hardware failure exists.  
• For assistance, contact Customer Support.  
Check Condensate  
Management System Exists  
Warning • The condensate pump is running.  
• For assistance, contact Customer Support.  
Condensate Pan Full  
Critical • Make sure the floats are operating correctly.  
• Clear debris from the condensate pan and drain lines.  
• Replace the sensor.  
• For assistance, contact Customer Support.  
Condensate Pump Run Hours  
Violation  
Warning • At the display interface, reset the Condensate Pump Run Hours in  
the View Run Hours screen after the appropriate maintenance for the  
device has been performed.  
Containment Differential  
Pressure High Alarm  
Warning • Check the cooling unit airflow for obstruction.  
• Clean or replace the air filter and reset the Air Filter run hours in the  
View Run Hours screen.  
• If the problem persists, contact Customer Support.  
Cooling Failure  
Critical • Make sure the chiller is operating properly.  
• For assistance, contact Customer Support.  
Entering Fluid High  
Temperature Violation  
Warning • Make sure the chiller is operating properly.  
• At the display interface, make sure the Inlet Fluid threshold is set  
correctly in the Set Unit Threshlds screen.  
• If the problem persists, contact Customer Support.  
Entering Fluid Temperature  
Sensor Fault  
Warning • Make sure the sensor is connected properly.  
• If the problem persists, contact Customer Support.  
InRow RC Operation and Maintenance Manual  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Alarm Message  
Severity  
Critical • A hardware failure exists.  
• For assistance, contact Customer Support.  
Warning • A hardware failure exists.  
• For assistance, contact Customer Support.  
Action Required  
External Communication Fault  
Fan #n Fault  
Fan #n Run Hours Violation  
Warning • At the display interface, reset the Fans run hours in the View Run  
Hours screen after the appropriate maintenance for the device has  
been performed.  
Filter Sensor Fault  
Warning • A hardware failure exists.  
• For assistance, contact Customer Support.  
Fluid Calibration Active  
Fluid Flowmeter Comm Fault  
Fluid Flowmeter Fault  
Critical • The cooling unit is in fluid calibration mode. See “Fluid Calibration  
Mode:” on page 17 for more information.  
Warning • Make sure the sensor is connected properly.  
• If the problem persists, contact Customer Service.  
Critical • If a leak exists, fix the problem.  
• Make sure the supply and return chilled water pipes are connected  
properly, fluid is flowing from the chiller to the unit, and the electrical  
connections to the flowmeter are correct.  
• If the problem persists, contact Customer Support.  
Group Communication Lost  
Internal Communication Fault  
Warning • Make sure the number of cooling units in the group is configured  
properly, and the A-Link connections between cooling units are correct.  
• Make sure the system is receiving power and is connected properly.  
• If the problem persists, contact Customer Support.  
Critical • A hardware failure exists.  
• For assistance, contact Customer Support.  
Leaving Fluid Temperature  
Sensor Fault  
Warning • Make sure the sensor is connected properly.  
• If the problem persists, contact Customer Support.  
No Backup Units Available  
Warning • Check to make sure cooling units in the group are set to  
Configure Unit > General > Role Override > Auto and that cooling  
units are available (not in a failed state).  
• For assistance, contact Customer Support.  
On Standby: Input Contact  
Fault  
Warning • At the display interface, make sure the Input Normal State is defined  
correctly in the Set Unit Threshlds screen.  
• Clear the problem that caused the input contact switch to change from  
its normal state.  
• If the problem persists, contact Customer Support.  
Power Supply Feed A Fault  
Warning • Make sure the power source is connected properly and the power is  
on.  
• If the problem persists, contact Customer Support.  
Rack Inlet #n High  
Temperature Violation  
Critical • Make sure the temperature sensor is connected and placed properly.  
• Make sure the Rack Inlet threshold is set correctly in the Set Unit  
Threshlds screen.  
• If the problem persists, contact Customer Support.  
Rack Inlet #n Temperature  
Sensor Fault  
Critical • Make sure the sensors are connected properly.  
• If the problem persists, replace the sensor, or contact Customer  
Support.  
Return Air High Temperature  
Violation  
Warning • Make sure the Return Air threshold is set correctly in the Set Unit  
Threshlds screen.  
• If the problem persists, contact Customer Support.  
Return Air Sensor Fault  
Critical • Make sure the sensor is connected properly.  
• Replace the sensor.  
• If the problem persists, contact Customer Support.  
28  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm Message  
Severity  
Action Required  
Supply Air High Temperature  
Violation  
Warning • Make sure the temperature sensor is connected properly.  
• Make sure the Supply Air threshold is set correctly in the Set Unit  
Threshlds screen.  
• If the problem persists, contact Customer Support.  
Supply Air Sensor Fault (upper  
or lower)  
Critical • Make sure the faulty sensor is connected properly.  
• Replace the sensor.  
• If the problem persists, contact Customer Support.  
Supply Humidity Sensor Fault  
Water Detection Fault  
Critical • Make sure the sensor is connected properly.  
• Replace the sensor.  
• If the problem persists, contact Customer Support.  
Warning • Identify and isolate the source of the leak.  
• For assistance, contact Customer Support.  
InRow RC Operation and Maintenance Manual  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Network Management Card  
Quick Configuration  
The cooling unit is shipped with a Network Management Card that enables the cooling unit to be managed over  
a network. Configure the Network Management Card to control this cooling unit through a network.  
Overview  
You must configure the following TCP/IP settings before the Network Management Card can operate on a  
network:  
• IP address of the Network Management Card  
• Subnet mask  
• Default gateway  
NOTE: Never use the loopback address (127.0.0.1) as the default gateway for the Network Management Card.  
Doing so will disable the card and will require you to reset TCP/IP settings to their defaults using a local serial  
login.  
NOTE: If a default gateway is unavailable, use the IP address of a computer that is located on the same subnet  
as the Network Management Card and that is usually running. The Network Management Card uses the default  
gateway to test the network when traffic is very light.  
See “Watchdog Features” in the “Introduction” of the User Guide for more information about  
the watchdog role of the default gateway.  
TCP/IP configuration methods  
Use one of the following methods to define the TCP/IP settings needed by the Network Management Card:  
Schneider Electric Device IP Configuration Wizard  
®
You can use the Schneider Electric Device IP Configuration Wizard at a computer running Microsoft  
®
®
®
Windows 2000, Windows Server 2003, or Windows XP to configure a Network Management Card.  
NOTE: Most software firewalls must be temporarily disabled for the Wizard to discover unconfigured Network  
Management Cards.  
To configure one or more Network Management Cards from a user configuration file, see the User  
1. Insert the Utility CD into a computer on your network.  
2. If autorun is enabled, the user interface of the CD starts when you insert the CD. If autorun is not  
enabled, open the file contents.htm on the CD.  
3. Select the Device IP Configuration Wizard from the main menu.  
30  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
4. When the Wizard discovers the unconfigured Network Management Card, follow the on-screen  
instructions.  
NOTE: If you leave the Start a Web browser when finished option enabled, you can use Schneider  
Electric for both the user name and password to access the Network Management Card through your  
browser.  
.ini file utility  
You can use the .ini file export utility to export .ini file settings from configured Network Management Cards to  
one or more unconfigured Network Management Cards.  
InRow RC Operation and Maintenance Manual  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
BOOTP & DHCP configuration  
The default TCP/IP configuration setting, BOOTP & DHCP, assumes that a properly configured BOOTP or  
DHCP server is available to provide TCP/IP settings to Network Management Cards. The Network  
Management Card first attempts to discover a properly configured BOOTP server, and then a DHCP server. It  
repeats this pattern until it discovers a BOOTP or DHCP server.  
A user configuration (.ini) file can function as a BOOTP or DHCP boot file. For more information, see  
the TCP/IP configuration section of the User Guide, available from the Utility CD or the Schneider  
Electric Web site, www.schneider-electric.com.  
BOOTP: For the Network Management Card to use a BOOTP server to configure its TCP/IP settings, it must  
find a properly configured RFC951-compliant BOOTP server.  
1. In the BOOTPTAB file of the BOOTP server, enter the MAC address of the Network Management Card,  
and the IP addresses of the subnet mask, and default gateway, and an optional bootup file name. Look  
for the MAC address on the display interface (Path: Main > Configure Network) or on the label on the  
back of the Network Management Card.  
2. When the Network Management Card reboots, the BOOTP server provides it with the TCP/IP settings.  
– If you specified a bootup file name, the Network Management Card attempts to transfer that file from  
the BOOTP server using TFTP or FTP. The Network Management Card assumes all settings  
specified in the bootup file.  
– If you did not specify a bootup file name, you can configure the other settings of the Network  
Management Card remotely through its Web interface or control console; user name and password  
are both Schneider Electric, by default.  
See your BOOTP server documentation to create a bootup file.  
DHCP: You can use a RFC2131/RFC2132-compliant DHCP server to configure the TCP/IP settings for the  
Network Management Card.  
This section summarizes communication between the Network Management Card and a DHCP  
server. For more details about how a DHCP server can configure the network settings for a Network  
Management Card, see “DHCP Configuration” in the User Guide.  
1. A Network Management Card sends out a DHCP request that uses the following to identify itself:  
– A Vendor Class Identifier (APC by default)  
– A Client Identifier (by default, the MAC address value of the Network Management Card)  
– A User Class Identifier (by default, the identification of the application firmware of the Network  
Management Card)  
2. A properly configured DHCP server responds with a DHCP offer that includes all of the settings that the  
Network Management Card needs for network communication. The DHCP offer also includes the  
Vendor Specific Information option (DHCP option 43). By default, the Network Management Card will  
ignore DHCP offers that do not encapsulate the Schneider Electric cookie in the Vendor Specific  
Information option using the following hexadecimal format:  
32  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Option 43 = 01 04 31 41 50 43  
where  
– the first byte (01) is the code  
– the second byte (04) is the length  
– the remaining bytes (31 41 50 43) are the Schneider Electric cookie  
See your DHCP server documentation to add code to the Vendor Specific Information  
option.  
To change the control console DHCP Cookie Is setting, use the Advanced option in the  
To disable the requirement that a DHCP offer include the Schneider Electric cookie, use  
the DHCP Cookie Is setting in the control console:  
Network > TCP/IP > Boot Mode > DHCP only > Advanced > DHCP Cookie Is.  
Local access to the control console  
You can use a computer connected to the serial port on the main board holding the Network Management Card  
to access the control console.  
1. Select a serial port at the local computer, and disable any service that uses that port.  
2. Use the configuration cable to connect the selected port to the serial port on the main board holding the  
Network Management Card. Use either 940-0103, the 6-ft (1.8-m) cable that came with your UPS, or  
AP9804 (990-1524), the 15-ft (4.6-m) cable available from Schneider Electric.  
3. Run a terminal program (such as HyperTerminal) and configure the selected port for 9600 or 19200 bps,  
8 data bits, no parity, 1 stop bit, and no flow control. Save the changes.  
4. Press ENTER to display the User Name prompt.  
5. Use apc for the user name and password.  
Remote access to the control console  
From any computer on the same subnet as the Network Management Card, you can use ARP and Ping to  
assign an IP address to a Network Management Card, and then use Telnet to access the control console of that  
Network Management Card and configure the needed TCP/IP settings.  
NOTE: After the IP address of the Network Management Card is configured, you can use Telnet without first  
using ARP and Ping to access that Network Management Card.  
1. Use the MAC address for the Network Management Card in the ARP command to define the IP  
address. For example, to define an IP address of 156.205.14.141 for a Network Management Card that  
has a MAC address of 00 c0 b7 63 9f 67, use one of the following commands:  
– Windows command format:  
arp -s 156.205.14.141 00-c0-b7-63-9f-67  
– LINUX command format:  
arp -s 156.205.14.141 00:c0:b7:63:9f:67  
NOTE: The MAC address is available on the display interface at:  
Path: Main > Configure Network or look at the label on the back of the Network Management  
Card for the MAC address.  
2. Use Ping with a size of 113 bytes to assign the IP address defined by the ARP command. For the IP  
address defined in step 1, use one of the following Ping commands:  
InRow RC Operation and Maintenance Manual  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
– Windows command format:  
ping 156.205.14.141 -l 113  
– LINUX command format:  
ping 156.205.14.141 -s 113  
3. Use Telnet to access the Network Management Card at its newly assigned IP address. For example:  
telnet 156.205.14.141  
4. Use apc for both user name and password.  
Control console  
1. Choose Network from the Control Console menu.  
2. Choose TCP/IP from the Network menu.  
3. If you are not using a BOOTP or DHCP server to configure the TCP/IP settings, select the Boot Mode  
menu and then select Manual boot mode.  
4. Set the System IP, Subnet Mask, and Default Gateway address values. (Changes will take effect  
when you log out.)  
5. Press ENTER to return to the TCP/IP menu.  
6. Press CTRL+C to exit to the Control Console menu.  
7. Log out (option 4 in the Control Console menu).  
34  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Access a Configured Network Management Card  
Overview  
After the Network Management Card is running on your network, you can access the configured Network  
Management Card through the following interfaces:  
• Web interface (HTTP or HTTPS protocol)  
Telnet or Secure SHell (SSH)  
• SNMP  
• FTP or Secure CoPy (SCP) to upgrade firmware  
• Modbus  
For more information on the interfaces, see the User Guide.  
Web interface  
®
®
®
Use Microsoft Internet Explorer (IE) 5.5 and higher (on Windows operating systems only), Mozilla-based  
®
®
browsers that support Firefox 1.x (on all operating systems), or Netscape 7.x and higher (on all operating  
systems) to access the Web interface of the cooling unit. Other commonly available browsers also may work  
but have not been fully tested by Schneider Electric.  
You can use either of the following protocols when you use the Web interface:  
• The HTTP protocol (enabled by default), which provides authentication by user name and password but  
no encryption.  
• The HTTPS protocol, which provides extra security through Secure Sockets Layer (SSL); encrypts user  
names, passwords, and data being transmitted; and authenticates the Network Management Card by  
means of digital certificates.  
To access the Web interface and configure the security of your device on the network:  
1. Address the Network Management Card by its IP address or DNS name (if configured).  
2. Enter the user name and password (by default, apc and apc for an Administrator).  
3. To enable or disable the HTTP or HTTPS protocols, use the Network menu on the Administration tab,  
and select the access option under the Web heading on the left navigation menu.  
For more information on selecting and configuring network security, see the Security  
Handbook, available on the Utility CD or from the Schneider Electric Web site,  
Telnet and SSH  
You can access the control console through Telnet or Secure SHell (SSH), depending on which is enabled.  
Select the Administration tab, the Network option on the top menu bar, and then the access option under  
Console on the left navigation menu. By default, Telnet is enabled. Enabling SSH automatically disables  
Telnet.  
Telnet for basic access: Telnet provides the basic security of authentication by user name and password, but  
not the high-security benefits of encryption. To use Telnet to access the control console of the Network  
Management Card:  
1. At a command prompt, use the following command line, and press ENTER:  
telnet address  
InRow RC Operation and Maintenance Manual  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
As address, use the IP address of the Network Management Card or DNS name (if configured).  
2. Enter the user name and password (by default, apc and apc for an Administrator, or device and apc for  
a Device User).  
SSH for high-security access: If you use the high security of SSL for the Web interface, use Secure SHell  
(SSH) for access to the control console. SSH encrypts user names, passwords, and transmitted data.  
The interface, user accounts, and user access rights are the same whether you access the control console  
through SSH or Telnet, but to use SSH, you must first configure SSH and have an SSH client program installed  
on your computer.  
See the User Guide for more information on configuring and using SSH.  
Simple Network Management Protocol (SNMP)  
®
SNMPv1 only: After you add the PowerNet MIB to a standard SNMP MIB browser, you can use that browser  
to access the Network Management Card. All user names, passwords, and community names for SNMP are  
transferred over the network as plain text. The default read community name is public; the default read/write  
community name is private.  
SNMPv3 only: For SNMP GETs, SETs, and trap receivers, SNMPv3 uses a system of user profiles to identify  
users. An SNMPv3 user must have a user profile assigned in the MIB software program to perform GETs and  
SETs, browse the MIB, and receive traps. The default settings are no authentication and no privacy.  
NOTE: To use SNMPv3, you must have a MIB program that supports SNMPv3.  
NOTE: The Network Management Card supports only MD5 authentication and DES encryption.  
SNMPv1 and SNMPv3: To use StruxureWare Data Center Expert to manage the Network Management Card,  
you must have SNMPv1 enabled in the unit interface. Read access allows InfraStruXure devices to receive  
traps. Write access is required while you set the InfraStruXure device as a trap receiver.  
To enable or disable SNMP access, you must be an Administrator. Select the Administration tab, select the  
Network menu on the top menu bar, and use the access option under SNMPv1 or SNMPv3 on the left  
navigation menu.  
FTP/SCP  
You can use FTP (enabled by default) or Secure CoPy (SCP) to transfer downloaded firmware to the Network  
Management Card, or to access a copy of the event or data logs of the cooling unit. SCP provides the higher  
security of encrypted data transmission and is enabled automatically when you enable SSH.  
To use StruxureWare Data Center Expert to manage the Network Management Card, you must have the FTP  
Server enabled in the Network Management Card. To enable or disable FTP Server access, you must be an  
Administrator. On the Administration tab, select the Network menu on the top menu bar, and use the FTP  
server option on the left navigation menu.  
In the User Guide, see the following sections:  
To transfer firmware, see “File Transfers.”  
To retrieve a copy of the event or data log, see “Use FTP or SCP to retrieve log files.”  
Modbus  
Modbus lets you view the Network Management Card through the interface of your building management  
system. The Modbus interface supports 2-wire RS-485, plus ground.  
NOTE: Modbus can be configured to run at either 9600 or 19200 bps. It is already configured for 8 data bits, no  
parity, and 1 stop bit, which are not changeable.  
36  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
To access the Modbus register map, go to the Schneider Electric Web site, www.schneider-  
InRow RC Operation and Maintenance Manual  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Recover From a Lost Password  
You can use a local computer (a computer that connects to the Network Management Card through the serial  
port) to access the control console.  
1. Select a serial port at the local computer, and disable any service that uses that port.  
2. Connect the provided RS-232 configuration cable to the selected port on the computer and to the RS-  
232 console port at the Network Management Card.  
3. Run a terminal program (such as HyperTerminal) on your computer and configure the selected port for  
9600 bps, 8 data bits, no parity, 1 stop bit, and no flow control.  
4. Press ENTER, repeatedly if necessary, to display the User Name prompt. If you are unable to display  
the User Name prompt, verify the following:  
– The serial port is not in use by another application.  
– The terminal settings are correct as specified in step 3.  
– The correct cable is being used as specified in step 2.  
5. Press the RESET switch. The Status LED will flash alternately orange and green. Press the RESET  
button a second time immediately while the LED is flashing to reset the user name and password to  
their defaults temporarily.  
6. Press ENTER as many times as necessary to redisplay the User Name prompt, then use the default,  
apc, for the user name and password. (If you take longer than 30 seconds to log on after the User  
Name prompt is redisplayed, you must repeat step 5 and log on again.)  
7. From the Control Console menu, select System, then User Manager.  
8. Select Administrator, and change the User Name and Password settings, both of which are now  
defined as apc.  
9. Press Ctrl+C, log off, reconnect any serial cable you disconnected, and restart any service you disabled.  
38  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Maintenance  
Monthly Preventive Maintenance  
Photocopy the following pages and use them during the maintenance procedures. After they have been  
completed, save them for future reference.  
Prepared By: ________________________________  
Model Number: ______________________________  
Serial Number: ______________________________  
Date: ______________________________________  
Environment  
In what type of room is the cooling unit located?  
___________________________________________________  
Is the cooling unit maintaining the temperature setpoint?  
___________________________________________________  
Temperature setpoint __________________________________  
Is there visible damage to the cooling unit (dents, scratches)?  
________________________________________________________________________  
________________________________________________________________________  
________________________________________________________________________  
Check the environmental damage (dirt, dust, debris, liquid stains) around the cooling unit installation area?  
________________________________________________________________________  
________________________________________________________________________  
Record the room temperature near the return of the cooling unit.  
Temperature: ________________________________________  
Record the alarm history for the last month.  
________________________________________________________________________  
________________________________________________________________________  
________________________________________________________________________  
Cleanliness  
Check the condition of the air filters. Change if necessary.  
Check for accumulation of debris in the drain pan. Clean as required.  
InRow RC Operation and Maintenance Manual  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Mechanical  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work  
practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced by qualified personnel only.  
• Turn off all power supplying this equipment before working on or inside the equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors, and covers before turning on power to this equipment.  
Failure to follow these instructions will result in death or serious injury.  
Check the fans. All components should be moving freely with no signs of binding or damages.  
Verify that the condensate line is flowing freely.  
Electrical  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work  
practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced by qualified personnel only.  
• Turn off all power supplying this equipment before working on or inside the equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors, and covers before turning on power to this equipment.  
Failure to follow these instructions will result in death or serious injury.  
Inspect the electrical panel for tight connections and for overheated connections from loose contact terminals.  
Confirm the incoming main voltage matches the cooling unit nameplate. The measurement should be within 10%  
of the nameplate listing.  
40  
InRow RC Operation and Maintenance Manual  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Quarterly Preventive Maintenance  
* Perform all the Monthly Preventive Maintenance items and the items below.  
Prepared By: _________________________________  
Model Number: _______________________________  
Serial Number: _______________________________  
Date: ______________________________________  
Mechanical  
DANGER  
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH  
• Apply appropriate personal protective equipment (PPE) and follow safe electrical work  
practices. See NFPA 70E or CSA Z462.  
• This equipment must be installed and serviced by qualified personnel only.  
• Turn off all power supplying this equipment before working on or inside the equipment.  
• Always use a properly rated voltage sensing device to confirm power is off.  
• Replace all devices, doors, and covers before turning on power to this equipment.  
Failure to follow these instructions will result in death or serious injury.  
Verify that the fan hardware is tight.  
Clean the condensate drain line.  
Clean the dust from door perforations.  
Clean the dust from fan bezels.  
Functional  
Verify that the cooling operation mode is functioning properly.  
Semi-Annual Preventive Maintenance  
* Perform all the Monthly Preventive Maintenance items and the items below.  
Prepared By: _________________________________  
Model Number: _______________________________  
Serial Number: _______________________________  
Date: ______________________________________  
Cleanliness  
Check the cleanliness of the evaporator coil. Clean if required.  
InRow RC Operation and Maintenance Manual  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Troubleshooting  
Problem  
Possible Cause  
Corrective Action  
Controls erratic or  
inoperative  
• Inlet temperature to cooling  
unit is higher than rated  
maximum temperature  
• Reduce the load or add additional cooling equipment.  
Fans fail to start  
• Cooling unit shutdown due to Temporarily remove the input contact cable, if it is  
an external command  
connected.  
• Single fan fails to start  
• Verify that the fan circuit breaker is ON.  
Cooling unit cannot • Improper placement of remote • Verify that the remote temperature sensor is properly  
obtain setpoint  
temperature sensor  
located in the cold aisle.  
• Dirty filter  
• Clean the filter.  
• Dirty coil  
• Clean the coil.  
• Valve/actuator malfunction  
• Application error  
• Fully open the valve.  
• Contact Schneider Electric Technical Support.  
• Entering water temperature is • Verify that the temperature of the Cooling Unit water supply  
too high  
is within the specified range.  
• Heat load is too far away  
• Place the cooling unit closer to the heat load.  
Water carryover  
• Improper fan speed selected • RACS and HACS modes only: Select the next-highest fan  
speed setting. For example, change the fan speed setting  
from Low to Med/Low.  
• Inlet water temperature is too • Verify that the temperature of the inlet water is within the  
low  
specified range.  
• Room humidity is too  
high/low  
• Improve room sealing.  
Temperature control • Improper placement of remote • Verify that the remote temperature sensor is properly  
not tight enough temperature sensor located in the cold aisle.  
Water on outside of • Condensate drain hose is not • Verify that the condensate drain hose is properly connected  
cooling unit  
connected or not properly  
to the pump and properly routed outside of the cooling unit.  
routed outside the cooling unit • Verify that the condensate drain line does not exceed 5.4 m  
(18 ft) lift and 18.3 m (60.0 ft) horizontal run.  
• Leak in drain system  
• Locate and repair the leak.  
• Cooling unit not leveled  
properly  
• Adjust the leveling feet of the cooling unit.  
• Damaged piping insulation  
• Identify damaged area and repair the insulation.  
• Verify that the actuator is connected properly.  
Fluid valve not  
responsive  
• Actuator not connected  
properly  
• Actuator and shaft not rotating • Tighten the linkage screw on the actuator shaft.  
together  
• Rotary switch on the bottom of • Confirm that the rotary switch is pointing toward the front of  
the actuator is set incorrectly  
the cooling unit.  
Display interface not • Display interface not  
• Verify that the display interface cable is connected properly.  
operational, but  
connected properly  
cooling unit operates  
Incorrect air pressure • False filter clogs  
• Verify that the ends of the clear plastic air tubes are not  
obstructed.  
• Verify that the clear plastic air tubes are connected to the  
controller.  
• Verify that the clear plastic air tubes are not pinched.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Problem  
Alarms do not show • External monitoring equipment • Confirm that power, if required, is being supplied to the  
up on monitoring is not receiving power or is not external equipment.  
Possible Cause  
Corrective Action  
equipment (Customer functioning properly  
Output Contact)  
• If the cooling unit (+12 V or +24 V) is providing power to the  
external equipment, verify that the external equipment is  
<50 mA.  
Test the external equipment by bypassing the customer  
output contact.  
Cooling unit does not • Drive voltage  
shut down on  
command  
• Verify that there is a drive voltage entering the input of the  
cooling unit. You may use the available +12 V or +24 V. You  
must also use the ground.  
No communication  
with building  
• Improper connection  
• Confirm that the cooling unit is connected to the BMS port  
and not to the Control port.  
management system  
(BMS) port  
• Make sure that the wire polarity is correct. Using a DC  
voltmeter, test the signal with no transmissions in progress.  
Expect the voltage at pin 2 to be greater than at pin 1 by at  
least 200 mV. Measure the cooling unit with the cable  
disconnected, and then measure it again with the cable  
connected. If the signal is less than 200 mV, the cooling unit  
may be reverse-wired.  
• Make sure that every cooling unit has either two sets of  
wires in its connector or one set of wires and a terminating  
resistor of 100 to 120 ohms.  
Cooling units are not • A-Link failure  
communicating with  
• Verify that the first and last cooling units have one cable and  
a terminator.  
each other  
• Verify that every other cooling unit has two cables.  
• Confirm that the A-Link cables are connected to the A-Link  
ports and that a network cable is connected to the network  
port.  
• Verify that the number of cooling units in the cooling group  
matches the group number setting.  
Output air is 17°C  
(62°F) and fans are  
running at a very high  
rate of speed.  
• Upper or lower supply air  
sensor  
• Either upper or lower supply air temperature sensor has a  
fault. Verify that both supply air temperature sensors are  
installed and working properly.  
InRow RC Operation and Maintenance Manual  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Worldwide Customer Support  
Customer support for this or any other product is available at no charge in any of the following ways:  
• Visit the Schneider Electric Web site to access documents in the Schneider Electric Knowledge Base  
and to submit customer support requests.  
www.schneider-electric.com (Corporate Headquarters)  
Connect to localized Schneider Electric Web sites for specific countries, each of which provides  
customer support information.  
Global support searching Schneider Electric Knowledge Base and using e-support.  
• Contact the Schneider Electric Customer Support Center by telephone or e-mail.  
– Local, country-specific centers: go to www.schneider-electric.com > Support > Operations  
around the world for contact information.  
For information on how to obtain local customer support, contact the representative or other distributors  
from whom you purchased your product.  
As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication.  
© 2014 Schneider Electric. All Rights Reserved.  
The Schneider Electric logo and InRow are trademarks owned by Schneider Electric Industries S.A.S., or its affiliated companies. All other  
trademarks are the property of their respective owners.  
990-3237B-001  
11/2014  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Pyramid Technologies TV Mount PA 1000DJ User Guide
Radica Games Games 71023UK User Guide
RayTek Thermometer FA User Guide
RCA TV Converter Box DTA800B1 User Guide
Renesas Computer Hardware REG10J0083 0100 User Guide
Rival Electric Steamer CKRVSTLM20 User Guide
Samson Musical Instrument Rs15s User Guide
Samsung Blu ray Player BD C6900 User Guide
Samsung DVD Player DVD C601 User Guide
Sears Automobile Battery Charger 608718571 User Guide