| 	
		 COMPACT L.P.& NATURAL   
					GAS VENT-FREE STOVE   
					’ 
					OWNER S OPERATION AND INSTALLATION MANUAL   
					WARNING: If the information in this   
					manual is not followed exactly,a fire or   
					explosion may result causing property   
					damage, personal injury, or loss of life.   
					QN300RYLA   
					QL300RYLA   
					Do not store or use gasoline or other flammable   
					vapors and liquids in the vicinity of this or any   
					other appliance.   
					QN300RYLA-W QL300RYLA-W   
					WHAT TO DO IF YOU SMELL GAS   
					ꢀ 
					Do not try to light any appliance.   
					WARNING: Improper installation,   
					adjustment, alteration, service or main-   
					tenance can cause injury or property   
					damage. Refer to this manual for correct   
					installation and operational procedures.   
					For assistance or additional informa-   
					tion consult a qualified installer, service   
					agency, or local gas supplier.   
					ꢀ 
					Do not touch any electrical switch; do not   
					use any phone in your building.   
					Immediately call your gas supplier from a   
					neighbor’s phone. Follow the gas supplier’s   
					instructions.   
					ꢀ 
					ꢀ 
					If you cannot reach your gas supplier, call   
					the fire department.   
					Installation and service must be performed by a   
					qualified installer, service agency, or local gas   
					supplier.   
					WARNING: This is an unvented   
					gas-fired heater. It uses air (oxygen)   
					from the room in which it is installed. This appliance may be installed in an   
					Provisions for adequate combustion and aftermarket*, permanently located manufactured   
					ventilation air must be provided. Refer (mobile) home, where not prohibited by local   
					to Air For Combustion and Ventilation codes.This appliance is only for use with the   
					section on page 5 of this manual.   
					type of gas indicated on the rating plate. This   
					appliance is not convertible for use with other   
					gases.   
					Continental Appliance Inc./U.S. Office   
					5 Musick   
					4600 Highlands Parkway S.E.   
					WATER VAPOR:ABY-PRODUCT OF UNVENTED ROOM   
					Irvine   
					Suite# D/E   
					HEATERS   
					CA 92618   
					Smyrna GA 30080   
					Water vaporis a by-product of gas combustion.An   
					unvented room heater produces approximately one   
					(1)ounce (30)ml   
					of water for every 1,000BTU’S (.3KW’S) OF gas input   
					per hour,Refer to papg 7.   
					Nanjing PRO-COM Electric Appliance Co.,Ltd.   
					#6 Chuangye Road,High New Tech.Zone,   
					Great Bridge Road North,Nanjing,210061,China.   
					Consumer : please retain these instruction   
					for future use.   
					Installer:Please leave these instructions with the   
					consumer.   
					*Aftermarket: Completion of sale, not for purpose of resale,   
					from the manufacturer.   
					TOLL-FREENUMBER:1-877-886-5989   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 
				SAFETY INFORMATION WARNINGS   
					1. This appliance is only for use   
					IMPORTANT:   
					Read   
					this   
					WARNING: Do not allow fans to   
					with the type of gas indicated   
					on the rating plate. This   
					appliance is not convertible for   
					use with other gases.   
					owner’s manual carefully and   
					completely before trying to   
					assemble, operate, or service   
					this heater. Improper use of   
					this heater can cause serious   
					injury or death from burns,   
					fire, explosion, electrical   
					shock, and carbon monoxide   
					poisoning.   
					blow directly into the heater. Avoid any   
					drafts that alter burner flame patterns.   
					Ceiling fans can create drafts that   
					alter burner flame patterns. Altered   
					burner patterns can cause sooting.   
					2. Do not place Propane/LP   
					supply tank(s) inside any   
					structure. Locate Propane/LP   
					supply tank(s) outdoors.   
					WARNING: Do not use a blower   
					insert, heat exchanger insert, or other   
					accessory not approved for use with   
					this heater.   
					3. If you smell gas   
					ꢀ 
					ꢀ 
					ꢀ 
					Shut off gas supply.   
					Do not try to light any appliance.   
					Do not touch any electrical switch:   
					do not use any phone in your   
					building.   
					DANGER: Carbon monoxide   
					poisoning may lead to death!   
					Due to high temperatures, the   
					appliance should be located out of   
					traffic and away from furniture   
					and draperies.   
					Carbon Monoxide Poisoning:   
					Early signs of carbon monoxide   
					poisoning resemble the flu, with   
					headaches, dizziness, or nausea.   
					If you have these signs, the heater   
					may not be working properly. Get   
					fresh air at once! Have heater   
					serviced. Some people are more   
					affected by carbon monoxide than   
					others. These include pregnant   
					women, people with heart or lung   
					disease, anemia, those under the   
					influence of alcohol, and those   
					at high altitudes.   
					ꢀ 
					ꢀ 
					Immediately call your gas supplier   
					from a neighbor’s phone. Follow   
					the gas supplier’s instructions.   
					If you cannot reach your gas   
					supplier, call the fire department.   
					Do not place clothing or other   
					flammable material on or near the   
					appliance. Never place any objects   
					in the fireplace.   
					4. This heater shall not be installed   
					in a bedroom or bathroom.   
					5. Do not use this heater as a   
					wood-burning heater. Use only   
					the logs provided with the heater.   
					6. Do not add extra logs or ornaments   
					such as pine cones, vermiculite, or   
					rock wool.Using these added items   
					can cause sooting. Do not add lava   
					rock around base. Rock and debris   
					could fall into the control area of   
					heater. After servicing, always   
					replace screen before operating   
					heater.   
					Heater becomes very hot when   
					running fireplace. Keep children and   
					adults away from hot surfaces to   
					avoid burns or clothing ignition.   
					Fireplace will remain hot for a   
					time after shutoff. Allow surfaces   
					to cool before touching.   
					Propane/LP Gas: Propane/LP gas   
					is odorless. An odor-making agent   
					is added to Propane/LP gas. The   
					odor helps you detect   
					a 
					Carefully supervise young children   
					Propane/LP gas leak. However,   
					the odor added to Propane/LP gas   
					can fade. Propane/LP gas may be   
					present even though no odor   
					exists.   
					Natural Gas: Natural gas is odorless.   
					An odor-making agent is added to   
					natural gas. The odor helps you   
					detect a natural gas leak. However, the   
					odor added to natural gas can   
					fade. Natural gas may be present   
					even though no odor exists.   
					Make certain you read and   
					understand all warnings. Keep this   
					manual for reference. It is your guide   
					to safe and proper operation   
					of this heater.   
					when they are in the room with the 7. You must operate this heater with   
					the heater screen in place. Make   
					sure heater screen is in place   
					before running heater.   
					fireplace.   
					You must operate this heater with   
					the heater screen in place. Make   
					sure the heater screen is in place   
					before running heater.   
					8. This heater is designed to be   
					smokeless. If logs ever appear to   
					smoke, turn heater off and call a   
					qualified service person. Note:   
					During initial operation, slight   
					smoking could occur due to log   
					c u r i n g a n d h e a t e r b u r n i n g   
					manufacturing residues.   
					Keep the appliance area clear and   
					free from combustible materials,   
					gasoline, and other flammable   
					vapors and liquids.   
					9. To prevent the creation of soot,   
					follow the instructions in Cleaning   
					and Maintenance   
					WARNING: Any change to   
					this fireplace or its controls can   
					be dangerous.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					3 
				SAFETY INFORMATION   
					LOCAL CODES   
					C.ontinued   
					15. Turn off and unplug heater and let   
					cool before servicing. Only a   
					qualified service person should   
					service and repair heater.   
					16. Operating heater above elevations   
					of 4,500 feet could cause pilot   
					outage.   
					17. Do not operate heater if any log is   
					broken. Do not operate heater if a   
					log is chipped (dime-sized or   
					larger).   
					18. To prevent performance problems,   
					do not use Propane/LP fuel tank of   
					less than 100 lbs. capacity.   
					lnstall and use heater with care.   
					Follow all local codes. In the   
					absence of local codes, use the   
					latest edition of The National Fuel   
					Gas Code, ANSZ 223.1, also known   
					as NFPA 54*.   
					*Available from:   
					American National Standards   
					lnstitute, lnc.   
					1430 Broadway   
					New York, NY 10018   
					National Fire Protection   
					Association, lnc.   
					Batterymarch Park   
					Quincy. MA 02269   
					This heater is designed for vent-free   
					operation. State and local codes in   
					some areas prohibit the use of   
					vent-free heaters.   
					10. Before using furniture polish, wax,   
					carpet cleaner, or similar products,   
					turn heater off. If heated, the   
					vapors from these products may   
					create a white powder residue   
					within burner box or on adjacent   
					walls or furniture.   
					11. This heater needs fresh air   
					ventilation to run properly. This   
					heater has an Oxygen Depletion   
					Sensing (ODS) safety shutoff   
					system. The ODS shuts down the   
					heater if not enough fresh air is   
					available. See Air for Combustion   
					and Ventilation, pages 5through 6.   
					If heater keeps shutting off, see   
					Troubleshooting, pages 16   
					through 17.   
					PRODUCT FEATURES   
					SAFETY PILOT   
					12. Do not run heater:   
					This heater has a pilot with an   
					Oxygen Depletion Sensing (ODS)   
					safety shutoff system. The ODS/pilot   
					is a required feature for vent-free   
					room heaters. The ODS/pilot shuts off   
					the heater if there is not enough   
					fresh air.   
					ꢀ 
					Where flammable liquids or vapors   
					are used or stored.   
					Under dusty conditions.   
					UNPACKING   
					ꢀ 
					1. Remove top inner pack.   
					2. Tilt carton so that stove is upright.   
					3. Remove protective side packaging.   
					4. Slide stove out of carton.   
					5. Remove protective plastic wrap.   
					6. Remove two self-tapping screws   
					on the screw , then lift and   
					pulling forward.   
					13.Do not use this heater to cook   
					food or burn paper or other objects.   
					14. Do not use heater if any part has   
					been under water. lmmediately call   
					a qualified service technician to   
					inspect the room heater and to   
					replace any part of the control   
					system and any gas control which   
					has been under water.   
					Remote control SYSTEM   
					This fireplace has a remote transimit-   
					ter.This system requires three   
					batteries, and provides electric   
					power outlet to operate.   
					7. Remove log set by cutting plastic   
					ties.   
					8. Carefully unwrap log.   
					9. Check for any shipping damage. If   
					stove or log is damaged, promptly   
					inform dealer where you bought   
					stove.   
					PRODUCT IDENTIFICATION   
					Stove Cabinet   
					Screen   
					Log   
					Heater Control   
					Figure1- Vent Free LP/NG Gas Stove   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					4 
				AIR FOR COMBUSTION AND VENTILATION   
					Confined and Unconfined Space   
					Unusually Tight Construction   
					WARNING: This heater   
					shall not be installed in a confined   
					space or unusually tight con-   
					struction unless provisions are   
					provided for adequate combus-   
					tion and ventilation air. Read the   
					following instructions to insure   
					proper fresh air for this and other   
					fuel-burning appliances in your   
					home.   
					The National Fuel Gas Code, ANS The air that leaks around doors and   
					Z223.1 defines a confined space as a windows may provide enough fresh   
					space whose volume is less than 50 air for combustion and ventilation.   
					cubic feet per 1,000 Btu per hour However, in buildings of unusually tight   
					(4.8 m3 per kw) of the aggregate construction, you must provide   
					input rating of all appliances installed additional fresh air.   
					in that space and an unconfining Unusually tight construction is   
					space as a space whose volume is defined as construction where:   
					not less than 50 cubic feet per 1,000 a) walls and ceilings exposed to the   
					Btu per hour (4.8 m3 per kw) of the   
					aggregate input rating of all appliances   
					installed in that space. Rooms   
					communicating directly with the space   
					in which the appliances are installed*,   
					outside atmosphere have a   
					continuous water vapor retarder   
					with a rating of one perm (6×10-11kg   
					per pa-sec-m2) or less with   
					openings gasketed or sealed and   
					PROVIDING ADEQUATE   
					VENTILATION   
					through openings not furnished with b) weather stripping has been added   
					The following are excerpts from   
					National Fuel Gas Code, NFPA 54/   
					ANSZ 223.1,Section 5.3, Air for   
					Combustion and Ventilation.   
					All spaces in homes fall into one of   
					the three following ventilation   
					classifications:   
					1. Unusually Tight Construction   
					2. Unconfined Space   
					3. Confined Space   
					doors, are considered a part of the   
					unconfined space.   
					on openable windows and doors   
					and   
					c) caulking or sealants are applied to   
					areas such as joints around window   
					and door frames, between sole   
					plates and floors, between   
					wall-ceiling joints, between wall   
					panels, at penetrations for plumbing,   
					electrical, and gas lines, and at   
					other openings.   
					This heater shall not be installed in   
					a confined space or unusually tight   
					construction unless provisions are   
					provided for adequate combustion   
					and ventilation air.   
					* Adjoining rooms are communicating   
					The information on pages 5 through 6   
					will help you classify your space and   
					provide adequate ventilation.   
					only if there are doorless passage- If your home meets all of the three   
					ways or ventilation grills between criteria above, you must provide   
					them.   
					additional fresh air. See Ventilation Air   
					From Outdoors.   
					If your home does not meet all of the   
					three criteria above, proceed to   
					Determining Fresh-Air Flow For   
					Heater Location.   
					DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION   
					Determining if You Have a Confined or Unconfined Space   
					Use this worksheet to determine if you have a confined or unconfined space.   
					Space: Includes the room in which you will install heater plus any adjoining rooms with doorless passageways   
					or ventilation grills between the rooms.   
					1. Determine the volume of the space (length width height).   
					× 
					× 
					Length Width Height=   
					cu.ft. (volume of space)   
					× 
					× 
					Example: Space size 20ft. (length) 16ft.(width) 8ft. (ceiling height)=2560cu. ft. (volume of space)   
					If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these   
					rooms to the total volume of the space.   
					× 
					× 
					2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.   
					(volume of space)÷50 cu. ft.=(Maximum Btu/Hr the space can support)   
					Example: 2560 cu. ft. (volume of space)÷50 cu.ft.=51.2 or 51,200(maximum Btu/Hr the space can support)   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					5 
				3. Add the Btu/Hr of all fuel burning appliances in the space.   
					Vent-free heater   
					Gas water heater*   
					Gas furnace   
					Vented gas heater   
					Gas heater logs   
					Other gas appliances* +   
					Total   
					Btu/Hr   
					Btu/Hr   
					Btu/Hr   
					Btu/Hr   
					Btu/Hr   
					Btu/Hr   
					Btu/Hr   
					Example:   
					Gas water heater   
					Vent-free heater   
					Total   
					30,000   
					26,000   
					56,000   
					Btu/Hr   
					Btu/Hr   
					Btu/Hr   
					+ 
					= 
					= 
					*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and   
					vents to the outdoors.   
					4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.   
					Btu/Hr (maximum the space can support)   
					Btu/Hr (actual amount of Btu/Hr used)   
					Example : 51,200 Btu/Hr(maximum the space can support)   
					56,000 Btu/Hr(actual amount of Btu/Hr used)   
					The space in the above example is a confined space because the actual Btu/Hr used is more than the   
					maximum Btu/Hr the space can support.   
					You must provide additional fresh air. Your options are as follows:   
					A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined   
					space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From   
					Inside Building.   
					B. Vent room directly to the outdoors. See Ventilation Air From Outdoors .   
					C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.   
					If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an   
					unconfined space. You will need no additional fresh air ventilation.   
					WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined   
					space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one   
					of the methods described in the National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.   
					Ventilation Air From lnside Building   
					This fresh air would come from an adjoining unconfined   
					space. When ventilating to an adjoining unconfined   
					space, you must provide two permanent openings: one   
					within 12" of the ceiling and one within 12" of the floor   
					on the wall connecting the two spaces (see options 1   
					and 2, Figure 2). You can also remove door into   
					adjoining room (see option 3, Figure 2). Follow the   
					National Fuel Gas Code. NFPA 54/ANS Z223.1, Sec-   
					tion 5.3, Air for Combustion and Ventilation for re-   
					quired size of ventilation grills or ducts.   
					Ventilation Air From Outdoors   
					Provide extra fresh air by using ventilation grills or ducts.   
					You must provide two permanent openings: one within   
					12" of the ceiling and one within 12" of the floor. Connect   
					these items directly to the outdoors or spaces open to the   
					Figure 2 -Ventilation Air from Inside Building   
					outdoors. These spaces include attics and crawl spaces.   
					Follow the National Fuel Gas Code, NFPA 54/ANS   
					Z223.1, Section 5.3, Air for Combustion and Ventilation   
					for required size of ventilation grills or ducts.   
					IMPORTANT: Do not provide openings for inlet or outlet   
					air into attic if attic has a thermostat-controlled power vent.   
					Heated air entering the attic will activate the power vent.   
					WARNING: Rework worksheet, adding   
					the space of the adjoining unconfined   
					space. The combined spaces must have   
					outle 
					enough fresh air to supply all appliances in   
					both spaces.   
					Figure 3 -Ventilation Air from Outdoors   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					6 
				INSTALLATION   
					WATERVAPOR:ABY-PRODUCTOF   
					UNVENTEDROOMHEATERS   
					Water vapor is by-product of gas   
					combustion.an unvented room   
					heater prodrces approximately one   
					(1) ounce (30ml) of water for every 1,   
					000BTU’s (.3kw’s) of gas input per   
					hour.   
					12   
					Unvented room heaters are recom-   
					mended as supplemtal heat (a   
					room) rather that a primary heat   
					source(an entire house) in most   
					supplemental heat applications,the   
					water vapor does not create a   
					problem ,in most applications the   
					water vapor enhances the low   
					humidity atmosphers experienced   
					during cold weather.   
					The following steps will help insure   
					that water vapor does not become a   
					problem.   
					12   
					1. Besure the heater is sized prop-   
					erly for the application,including   
					ample combustion air and circula-   
					tion of the air.   
					2.If high humidity is experienced, a   
					dehumidifier may be used to help   
					lower the water vapor content of the   
					air.   
					3.Do not use an unvented room   
					heater as the primary heat source.   
					WARNING: A qualified service   
					person must install heater. Follow   
					all local codes.   
					WARNING: Never install the   
					heater   
					Figure 4 -Minimum Clearance to Wall and Ceiling   
					ꢀin a bedroom or bathroom   
					ꢀ in a recreational vehicle   
					CHECK GAS TYPE   
					CAUTION: This heater creates   
					warm air currents. These currents   
					move heat to wall surfaces next to   
					heater. Installing heater next to vinyl   
					or cloth wall coverings or operating   
					heater where impurities (such as   
					tobacco smoke, aromatic candles,   
					cleaning fluids, oil or kerosene lamps,   
					etc.) in the air exist, may discolor   
					walls.   
					Be sure your gas supply is right for   
					your heater. Otherwise, call dealer   
					where you bought the heater for proper   
					type heater.   
					ꢀ where curtains, furniture, clothing,   
					or other flammable objects are less   
					than 42 inches from the front, top, or   
					sides of the heater   
					ꢀ in high traffic areas   
					ꢀin windy or drafty areas   
					WARNING: Maintain the   
					minimum clearances. If you can,   
					provide greater clearances from   
					floor, ceiling, and adjoining side and   
					back walls.   
					IMPORTANT: Vent-free heaters add   
					moisture to the air. Although this is   
					beneficial, installing heater in rooms   
					without enough ventilation air may   
					cause mildew to form from too much   
					moisture. See Air for Combustion and   
					Ventilation, pages 5 through 6.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					7 
				CLEARANCESTOCOMBUSTIBLES   
					(Vent-Free Operation Only)   
					Carefully follow the instructions below.   
					This stove is a freestanding unit   
					designed to set directly on the floor.   
					The installer must supply an external regulator.   
					The external regulator will reduce incoming gas   
					pressure. You must reduce incoming gas pressure   
					to rating inches of water. If you do not reduce   
					incoming gas pressure, heater regulator damage   
					could occur. lnstall external regulator with the vent   
					pointing down as shown in Figure 6. Pointing the   
					vent down protects it from freezing rain or sleet.   
					IMPORTANT: You must maintain   
					minimum wall and ceiling clearances   
					during installation. The minimum   
					clearances are shown in Figure 4.   
					Measure from outermost point of stove   
					top.   
					Minimum Wall and Ceiling Clearances   
					(see Figure 4)   
					A. Clearances from outermost point   
					of stove top to any combustible side   
					wall should not be less than 24   
					inches.   
					B. Clearances from outermost point of   
					stove top to any combustible back   
					wall should not be less than 10   
					i n c h e s ( l n c l u d e s   
					installations).   
					C. Clearances from the stove top to   
					the ceiling should not be less than   
					48 inches.   
					c o r n e r   
					Figure 5 -Gas Regulator Location and Gas   
					Line Access Into Stove Cabinet   
					Propane/LP   
					Supply Tank   
					CONNECTING TO GAS   
					SUPPLY   
					WARNING: A qualified ser-   
					vice person must connect heater   
					to gas supply. Follow all local   
					codes.   
					Figure 6 -External Regulator With   
					Vent Pointing Down   
					CAUTION: Never   
					connect   
					heater directly to the gas supply.   
					This heater requires an external   
					regulator (not supplied). lnstall the   
					external regulator between the heater   
					and gas supply.   
					NG Models:   
					5”-10.5” W.C.   
					Gas supplier provides external regulator for natural gas.   
					INSTALLATION ITEMS NEEDED   
					Before installing heater, make sure   
					you have the items listed below.   
					ꢀ piping (check local codes)   
					ꢀ sealant (resistant to propane/LP gas)   
					ꢀ equipment shutoff valve*   
					ꢀ test gauge connection*   
					purchase   
					ꢀ sediment trap   
					ꢀ tee joint   
					ꢀ pipe wrench   
					ꢀflexible gas hose.(check local codes)   
					*A CSA design-certified equipment   
					shutoff valve with 1/8" NPT tap is   
					an acceptable alternative to test   
					gauge connection. Purchase the   
					optional CSA design-certified   
					equipment shutoff valve from your   
					dealer. See Accessories.   
					Figure 7 -Gas Connection   
					* Purchase the optional CSA design-certified equipment shutoff valve   
					from your dealer. See Accessories.   
					** Minimum inlet pressure for purpose of input adjustment.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					8 
				WARNING: Never connect   
					heater to private (non-utility) gas   
					wells. This gas is commonly known   
					as wellhead gas.   
					Pressure Testing Gas   
					Supply Piping System   
					CAUTION: Avoid damage to   
					regulator. Hold gas regulator with   
					wrench when connecting into gas   
					piping and/or fittings.   
					Test Pressures In Excess Of 1/2   
					PSIG(3.5kPa)   
					1. Disconnect heater with its   
					appliance main gas valve (control   
					valve) and equipment shutoff valve   
					from gas supply piping system.   
					Pressures in excess of 1/2 PSIG   
					will damage heater regulator.   
					2. Cap off open end of gas pipe   
					where equipment shutoff valve   
					was connected.   
					3. Pressurize supply piping system   
					by either using compressed air or   
					opening gas supply tank valve.   
					4. Check all joints of gas supply   
					piping system. Apply mixture of   
					liquid soap and water to gas   
					joints. Bubbles forming show a   
					leak.   
					CAUTION: Use only new, black   
					iron or steel pipe. Internally-tinned   
					copper tubing may be used in   
					certain areas. Check your local   
					CHECKING GAS   
					CONNECTIONS   
					WARNING: Test all gas piping   
					and connections for leaks after   
					installing or servicing. Correct all   
					leaks at once.   
					codes. Use pipe of 1/2" diameter or   
					greater to allow proper volume gas   
					to heater. If pipe is too small, undue   
					loss of pressure will occur.   
					WARNING: Never use an   
					open flame to check for a leak.   
					Apply a mixture of liquid soap and   
					water to all joints. Bubbles forming   
					show a leak. Correct all leaks at   
					once.   
					Installation must include an equip-   
					ment shutoff valve, union, and   
					plugged 1/8" NPT tap. Locate NPT   
					tap within reach for test gauge hook   
					up. NPT tap must be upstream   
					from heater (see Figure 7).   
					CAUTION: Make sure external   
					regulator has been installed be-   
					tween gas supply and heater. See   
					guidelines under Connecting to Gas   
					Supply.   
					IMPORTANT: Install equipment   
					shutoff valve in an accessible   
					location. The equipment shutoff   
					valve is for turning on or shutting   
					off the gas to the appliance. Apply   
					pipe joint sealant lightly to male   
					threads.This will prevent excess   
					sealant from going into pipe. Excess   
					sealant in pipe could result in   
					clogged heater valves.   
					5. Correct all leaks at once.   
					6. Reconnect heater and equipment   
					shutoff valve to gas supply. Check   
					reconnected fittings for leaks.   
					Pressure Testing Heater   
					Gas Connections   
					1. Open equipment shutoff valve   
					(see Figure 8).   
					CAUTION: Use pipe joint   
					sealant that is resistant to gas   
					(PROPANE or NG).   
					Figure 8 -Equipment Shutoff Valve   
					Extemal Regulotor   
					We recommend that you install a   
					sediment trap in supply line as shown   
					in Figure 7. Locate sediment trap   
					where it is within reach for cleaning.   
					Install in piping system between fuel   
					supply and heater. Locate sediment   
					trap where trapped matter is not likely   
					to freeze. A sediment trap traps   
					moisture and contaminants. This   
					keeps them from going into heater   
					controls. If sediment trap is not   
					installed or is installed incorrectly,   
					heater may not run properly.   
					Propane/LP   
					Supply Tank   
					Equipment Shut   
					Figure 9.1 -Checking Gas Joints   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					9 
				2. Open gas supply tank valve.   
					3. Make sure control knob of heater is   
					in the OFF position.   
					4. Check all joints from equipment   
					shutoff valve to control valve   
					(LP GAS see Figure 9.1 NATURAL   
					GAS see Figure 9.2). Apply   
					mixture of liquid soap and water   
					to gas joints. Bubbles forming   
					show a leak.   
					5. Correct all leaks at once.   
					6. Light heater (see Operating   
					Heater). Check all other internal   
					joints for leaks.   
					7. Turn off heater (see To Turn Off   
					Gas Appliance).   
					WARNING: Failure to position   
					the parts in accordance with these   
					diagrams or failure to use only parts   
					specifically approved with this heater   
					may result in property damage or   
					personal injury.   
					It is very important to install the logs   
					exactly as instructed. Do not modify   
					logs. Only use logs supplied with   
					heater.   
					Place log set on grate to fit as   
					illustrated in Figure 10.   
					Make sure log sits flat on firebox   
					floor (see Figure 10).   
					CAUTION: After installation   
					and periodically thereafter, check to   
					ensure that no flame comes in   
					contact with any log. With the heater   
					set to High, check to see if flames   
					contact any log. If so, reposition logs   
					according to the log installation   
					instructions in this manual. Flames   
					contacting logs will create soot.   
					IMPORTANT: Make sure log does   
					not cover any burner ports (see Fig-   
					ure 11).   
					Also, see log placing instructions.   
					Test Pressures Equal To or   
					Less Than 1/2 PSIG(3.5 kPa)   
					1. Close equipment shutoff valve   
					(see Figure 8).   
					2. Pressurize supply piping system   
					by either using compressed air or   
					opening natural supply tank   
					valve.   
					3. Check all joints from gas meter to   
					equipment shutoff valve(see   
					Figure 9). Apply mixture of liquid   
					soap and water to gas joints.   
					Bubbles forming show a leak.   
					4. Correct all leaks at once.   
					Figure 10 -Installing Log Set   
					Figure 11 -Installing Log Set (Top View)   
					Figure 9.2 -Checking Gas Joints   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					10   
				OPERATING HEATER   
					FOR YOUR SAFETY   
					OPERATING INSTRUTIONOF   
					REMOTE-CONTROLLEDBUNER   
					READ BEFORE LIGHTING   
					WARNING: If you do not   
					follow these instructions exactly, a   
					fire or explosion may result causing   
					property damage, personal injury or   
					loss of life.   
					LIGHTING INSTRUCTIONS   
					1. STOP! Read the safety information,   
					page 2.   
					2. Make sure equipment shutoff   
					valve is fully open.   
					A. This appliance has a pilot which   
					must be lighted by control system,   
					When lighting the pilot, follow   
					these instructions exactly.   
					Figure 12-1 Emergency Button   
					location   
					NOTICE: During initial opera-   
					tion of new fireplace, burning logs   
					will give off a paper-burning smell.   
					Orange flame will also be present.   
					Open a window to vent smell. This   
					will only last a few hours.   
					B. BEFORE LIGHTING smell all   
					around the appliance area for   
					gas. Be sure to smell next to the   
					floor because some gas is   
					heavier than air and will settle   
					on the floor.   
					If you didn’t receive or mis-place your   
					remote transimitter,you can press the   
					emergency button by a pitch rod to   
					operate remote automatically on or off   
					(see fig 12-2)   
					WHAT TO DO IF YOU SMELL GAS   
					SEE WARNING in Page 1 for proper   
					instructiors.   
					CAUTION: Do not try to adjust   
					heating levels by using the   
					equipment shutoff valve.   
					C. Use only your hand to push in   
					control knob. Never use tools. If the   
					the appli ance could not operate , don't   
					try to repair it, Call a qualified service   
					technician or gas supplier.Forced or at-   
					tempted re-pair may result in a fire or   
					explosion.   
					D. Do not use this appliance if any   
					part has been under water. Imme-   
					diately call a qualified service techni-   
					cian to inspect the appliance and to   
					replace any part of the control system   
					and any gas control which has been   
					under water.   
					Figure 12-2 On/Off Switch   
					TO TURN OFF GAS TO APPLIANCE   
					Shut off heater   
					1. Press the IGN/OFF button of   
					transmitter.   
					2.Set the Switch on OFF location.(See   
					Figure12-2)   
					Shutting off burner only( pilot stay lit)   
					1.press the BURNER to set flame OFF   
					select   
					Fig 13 Front of the Transmitter   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 1   
				(Note: on the auto select of main   
					burner, the main burner does not   
					respond imm-ediately to the set tempera-   
					ture until about one minute later.)   
					OPERATING   
					HEATER   
					Continued   
					b.manual select of main   
					burner:   
					Press BURNER button, the flame   
					is   
					on “MAN” select. At this selection, the   
					main burner will keep working no matter   
					what the temperature is set at. If there is   
					a need to shut off the main burner, just   
					press the “BURNER” button to make the   
					Fig16 Control board   
					ꢀOPERATIONS OFꢀ   
					BURNER   
					1.Plug-in 110V electrical outlet, you will   
					hear a high pitch sound and power light   
					(red) on the front will be lit that indicates   
					that the burner is ready to be operated.   
					Before plugging in the outlet make sure that   
					the appliance is connected to the gas   
					supply, then continue to the next step.   
					2.Point directly the remote transmitter to the   
					burner. Press IGN/OFF button, the electric   
					spark starts igniting the pilot and operation   
					light (green) on the front will be lit. Wait five   
					(5) minutes to clear out any air. If you   
					smell gas. STOP! Please check the gas   
					connection.   
					burner   
					on the “OFF” select.   
					c.shut off the main burner:   
					the main burner is on “OFF” selection,.   
					The main burner will shut off.   
					Fig 14 Back of the Transmitter   
					ꢀOPERATIONS OFꢀ   
					ꢀOPERATIONS OFꢀ   
					TIMING   
					REMOTE TRANSMITTER   
					1.Auto on:   
					when the burner is in a state of   
					1.Install three AAA SIZE batteries in the bat-   
					tery holder.   
					readiness. Transmitter and burner is off.   
					Press TIMER button. Then press ¡øor ¨‹   
					change to the scheduled time, then press   
					the TIMER button again, the TIMER starts   
					timing and the TIMER is flashing and the   
					operation light(green) begin flashing.   
					When the timer goes on the scheduled   
					time, the burner opens automatically.   
					There are three selections: “AUTO” “MAN”   
					and “OFF”   
					The initial start-up on the LCD is: SET TEMP   
					is 77°F, ROOM TEMP is 77°F, clock is AM12:   
					00, burner is on “OFF” select, and fan is on   
					“AUTO” select. Divide Points of hour and   
					minute are flashing (i.e. the timer is operating).   
					a.auto select of main burner:   
					Press BURNER button, the flame   
					is   
					on “AUTO” select. Press ¡øor ¨‹to set   
					temperature. If the room temperature is two   
					degree lower than the set temperature on   
					the remote, the main burner will turn on   
					until the surrouding temperature is two   
					degree higher than the set temperature.   
					Once it reaches temperature on the   
					remoter, the main burner will automatically   
					shut off.   
					2.Auto off:   
					when the burner is in operation, press   
					TIMER button. Then press ¡øor¨‹to   
					change to the scheduled time, then press   
					the TIMER button again, the TIMER starts   
					timing and the TIMER is flashing and the   
					operation light begin flashing. When the   
					timer goes on the scheduled time, the   
					burner closes automatically.(See Fig 14)   
					Fig 25 Initial start-up on the LCD   
					2.Clock setting: Press CLOCK button on the   
					remote transmitter panel to select item (hour,   
					minute). The selected item is flashing. Press   
					¡øor¨‹to change to the correct actual hour   
					(s); Press ¡ø or¨‹ tochange to the cor-   
					rect minute(s), then press CLOCK button   
					again, time setting is finished.   
					ꢀOPERATIONS OFꢀ   
					TURN-OFF   
					1.Manual turn-off: when the heater is in   
					operation, press the IGN/OFF button to   
					shut off the heater.   
					3. When in operation, point the remote trans-   
					mitter to the remote receiver on the burner in   
					a maximum distance of 20 feet without any   
					obstruction between them.   
					2.Auto turn-off: refer to the second step   
					of “Operations of Timing”   
					Fig17 “AUTO” select   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					12   
				3.After completion of the above-   
					mentioned two steps, the transmitter   
					is kept in a state of readiness. If the   
					appliance doesn’t working for a   
					period time, just pull out the plug   
					from the 110V electrical outlet.   
					sensing bulb from the clip, then disco-   
					nnect the wires to free to control   
					module from its mounting location .   
					Note: Do not confuse the mark on   
					the each wire.   
					2. Remove two screws and hex nuts,   
					ꢀOPERATIONS OFꢀ   
					take out the control module. When in-   
					stalling , reverse the steps above.   
					(See Figure 22 and Figure 26)   
					Figure 19 -Incorrect Pilot Flame   
					Pattern   
					KEY-PRESS LOCKING   
					1.Key press locking:   
					BURNER FLAME PATTERN   
					when the burner is in operation or the   
					transmitter is in a state of readiness,   
					just press LOCK button on the   
					operating   
					panel, there will be a “ ” symbol on   
					the LCD. If any button is pressed   
					now, the burner will not react at all.   
					2.Key-press unlocking:   
					when the burner is in a state of key-   
					press locking, first press ¨‹, then   
					press LOCK button to unlock it (Child   
					proof-See Fig17)   
					Figure 20 shows a correct burner   
					flame pattern. Figure 21 shows an   
					incorrect burner flame pattern. If   
					burner flame is incorrect:   
					ꢀ 
					Turn heater off (see TO TURN   
					OFF GAS TO APPLIANCE)   
					See troubleshooting   
					ꢀ 
					Figure 22- Control Model   
					DISCONNECT FAN   
					1. Remove screws from the fan   
					bracket panel , pull the fan bracket   
					panel out to remove. Then disconne-   
					ct two wires free to fan.   
					ꢀOPERATIONS OFꢀ   
					FAN   
					2. Mark or tag each wire removed   
					for its exact reconnection. Remove   
					the four screws from the fan .when   
					installing , reverse the steps above.   
					(See Figure 23 and Figure 26)   
					There are three selections: “AUTO”   
					“MAN” and “OFF”.When pushing the   
					“FAN” button on the “AUTO” select,   
					the fan will be controlled by the   
					thermostat on the fan blower unit. On   
					the “MAN” select, the fan will be kept   
					in operation.To stop the operation,   
					push the “FAN”button to “OFF”select.   
					(See Fig17)   
					Figure 20-Correct Flame Pattern   
					with Control Knob Set to High Flame   
					INSPECTING BURNERS   
					Figure 23- Fan   
					Check pilot flame pattern and   
					burner flame patterns often.   
					Figure 21 -Incorrect Flame Pattern   
					with Control Knob Set to High Flame   
					CLEANING BURNER INJECTOR   
					HOLDER AND PILOT AIR INLET HOLE   
					PILOT FLAME PATTERN   
					CLEANING AND   
					CAUTION: You must keep   
					Figure 18 shows a correct pilot   
					c o n t r o l a r e a s , b u r n e r , a n d   
					circulating air passageways of   
					heater clean. Inspect these   
					areas of heater before each   
					use. Have heater inspected   
					yearly by a qualified service person.   
					H e a t e r m a y n e e d m o r e   
					f r e q u e n t c l e a n i n g d u e t o   
					excessive lint from carpeting,   
					bedding material, pet hair, etc.   
					flame pattern. Figure 19 shows an   
					incorrect pilot flame pattern. The   
					incorrect pilot flame is not touching   
					the thermocouple.This will cause the   
					thermocouple to cool. When the   
					thermocouple cools, the heater   
					will shut down. If pilot flame pattern   
					is incorrect, as shown in Figure 19.   
					ꢀ Turn heater off (see TO TURN   
					OFF GAS TO APPLIANCE)   
					MAINTENANCE   
					WARNING: Disconnect power be-   
					fore attempting any maintenance or   
					cleaning to reduce the risk of fire , elec-   
					tric shook or personal injury. Turn off   
					heater and let cool before cleaning.   
					Label all wires prior to   
					CAUTION:   
					The primary air inlet holes allow the   
					proper amount of air to mix with the   
					gas. This provides a clean burning   
					flame. Keep these holes clear of dust,   
					dirt, lint, and pet hair. Clean these air   
					inlet holes prior to each heating season.   
					Blocked air holes will create soot. We   
					recommend that you clean the unit   
					every three months during operation   
					and have heater inspected yearly by a   
					qualified service person.   
					disconnection   
					controls   
					improper and dangerous operation.   
					when servicing   
					Wiring errors can cause   
					ꢀ see troubleshooting   
					. 
					Verify proper operation after servicing.   
					DISCONNECTWIRNGORCONTROL   
					MODULE   
					1. Remove screws from the rear   
					control panel , take out thermostat   
					Figure 18 -Correct Pilot Flame   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 3   
					Pattern   
				We also recommend that you keep   
					the burner tube and pilot assembly   
					clean and free of dust and dirt. To   
					clean these parts we recommend   
					using compressed air no greater   
					than 30 PSI. Your local computer   
					store, hardware store, or home   
					center may carry compressed air in   
					a can. You can use a vacuum   
					cleaner in the blow position. If   
					using compressed air in a can,   
					please follow the directions on the   
					can. If you don't follow directions   
					on the can, you could damage the   
					pilot assembly.   
					1. Shut off the unit, including the   
					pilot. Allow the unit to cool for   
					at least thirty minutes.   
					2. Inspect burner, pilot and   
					primary air inlet holes on   
					injector holder for dust and dirt   
					(See Figure 24).   
					3 . B l o w a i r t h r o u g h t h e   
					ports/slots and holes in the   
					burner.   
					4. Check the injector holder   
					located at the end of the   
					burner tube again. Remove   
					any large particles of dust, dirt,   
					lint, or pet hair with a soft cloth   
					or vacuum cleaner nozzle.   
					5. Blow air into the primary air   
					holes on the injector holder.   
					6. In case any large clumps of   
					dust have now been pushed   
					into the burner repeat steps 3   
					and 4.   
					Clean the pilot assembly also. A   
					yellow tip on the pilot flame   
					indicates dust and dirt in the pilot   
					assembly. There is a small pilot air   
					inlet hole about two inches from   
					where the pilot flame comes out of   
					the pilot assembly (see Figure 25).   
					With the unit off, lightly blow air   
					through the air inlet hole. You may   
					blow through a drinking straw if   
					compressed air is not available.   
					Burner   
					CABINET   
					Air Passageways   
					ꢀ 
					Use   
					pressurized air to clean.   
					Exterior   
					Use a soft cloth dampened with a   
					a 
					vacuum cleaner or   
					ꢀ 
					mild soap and water mixture. Wipe   
					the cabinet to remove dust.   
					LOGS   
					ꢀ 
					If you remove logs for cleaning,   
					refer to Installing Logs to properly   
					replace logs.   
					Figure 25-Pilot Inlet Air Hole   
					ꢀ 
					Replace logs if broken or chipped   
					(dimesized or larger).   
					MAIN BURNER   
					REPLACEMENTPARTS NOTE:   
					Use only original replacement   
					parts. This will protect your warranty   
					coverage for parts replaced under   
					warranty.   
					Periodically inspect all burner flame   
					holes with the heater running. All   
					slotted burner flame holes should   
					be open with yellow flame present. All   
					round burner flame holes should be   
					open with a small blue flame   
					present. Some burner flame holes   
					may become blocked by debris or   
					rust, with no flame present. If so,   
					turn off heater and let cool. Either   
					remove blockage or replace burner.   
					Blocked burner flame holes will   
					create soot.   
					PARTS UNDER WARRANTY   
					Contact authorized dealers of this   
					product. If they can't supply original   
					replacement part(s) call the number   
					on the back of manual. when   
					contacting your dealer or PRO-COM,   
					have ready:   
					ꢀ 
					ꢀ 
					ꢀ 
					Your name   
					Your address   
					Model and serial numbers   
					of your heater   
					ꢀ 
					ꢀ 
					How heater was malfunctioning   
					Type of gas used (propane/LP or   
					NG)   
					Figure 26-   
					Figure 24 -Injector Holder on Outlet   
					Burner Tube   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					14   
				ACCESSORIES   
					FLEXILBE HOSE   
					ꢀ 
					ꢀ 
					Purchase date   
					Purchase these heater accessories   
					from your local dealer or Parts   
					Central. This part is not currently   
					available from PRO-COM.   
					Usually, we will ask you to   
					return the defective part to the   
					factory.   
					Flexibe gas hose is used for connect-   
					ing the heater to gas supply.   
					the flex hose must approved by CSA .   
					ꢀ 
					Warranty card.   
					PARTS NOT UNDER   
					WARRANTY   
					Contact authorized dealers of this   
					product or Parts Central. If they can’t   
					supply original replacement part(s)   
					call PRO-COM’s toll-free number on   
					the front page.   
					EQUIPMENT SHUTOFFVALVE-   
					Equipment shutoff valve with 1/8"   
					NPT tap.   
					SPECIFICATIONS   
					QL300RYLA   
					QN300RYLA   
					QL300RYLA-W   
					QN300RYLA-W   
					Btu(Variable)   
					Gas Type   
					Ignition   
					Manifold Pressure   
					Inlet Gas Pressure   
					(In. of water)*   
					Maximum   
					LP Gas   
					Automatic   
					8"W.C.   
					Natural Gas   
					Automatic   
					3"W.C.   
					14"   
					11"   
					10.5"   
					5"   
					Minimum   
					Dimensions, Inches (H W D)   
					× ×   
					Heater   
					Carton   
					25 4/5" 32 1/4” 13"   
					25 4/5" 32 1/4” 13"   
					× 
					× 
					× 
					× 
					25 1/8" 34 1/8” 12 7/8”   
					25 1/8" 34 1/8” 12 7/8”   
					× 
					× 
					× 
					× 
					Weight, lbs   
					Stove   
					74   
					83   
					120   
					74   
					83   
					120   
					Shipping   
					voltage   
					watt   
					32   
					32   
					*For purposes of input adjustment   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 5   
				TROUBLESHOOTING   
					CAUTION: Never use a wire,   
					needle, or similar object to clean   
					ODS/pilot. This can damage ODS/   
					pilot unit.   
					WARNING:Make sure that power   
					is turn off before proceeding....   
					WARNING: Turn off and let cool   
					before servicing. Only a qualified   
					service person should service and   
					repair fireplace.   
					REMEDY   
					OBSERVED PROBLEM   
					POSSIBLECAUSE   
					1. No power to heater   
					2. No battery in transmitter or battery   
					isn’t correctly assembly   
					1. Check the electric power   
					2. Place or replace the battery.   
					No spark when press in ignition button   
					1. Gas supply turned off or equip-   
					ment shut off valve closed   
					2. Air in gas lines when installed.   
					When pressing the button of ignitor   
					button is pressed, there is spark at   
					ODS/pilot but no ignition   
					1. Turn on gas supply or open   
					equipment shutoff valve   
					2 
					Press ON/OFF button again   
					until air is removed .   
					. 
					3. Contact local propane/LP gas   
					company   
					3. Depleted gas supply   
					4. ODS/pilot is clogged   
					4 
					Clean ODS/pilot (see Cleaning   
					and   
					Maintenance,page 13 ) or replace   
					ODS/pilot assembly   
					5. Gas regulator setting is not correct   
					6. Pilot electrude position is not   
					correct   
					5.   
					Replace gas control   
					6. Replace Pilot   
					7. Wire is not correct or loosen   
					8 Gas valve is damage   
					7. Check the wine and make wine   
					correct.   
					8. Replace gas valve   
					1. Hand tighten until snug, then   
					tighten 1/4 turn more.   
					2. A) Contact local propane/LP gas   
					company.   
					B) Clean ODS/pilot (see Cleaning   
					and Maintenance, page 13) or   
					replace   
					1. Thermocouple connection loose   
					at control board   
					ODS/pilot lights but flame is   
					continuous igniting and the main   
					burner couldn’t be lit.   
					2. Pilot flame not touching   
					thermcouple which allows thermo-   
					couple to cool, causing pilot   
					flame to go out. This problem   
					could be caused by one or both of   
					the following   
					ODS/pilot assembly   
					3. Replace thermocouple   
					4. Replace control valve   
					A) Low gas pressure   
					B) Dirty or partially clogged   
					ODS/ pilot   
					3. Thermocouple damaged   
					4. Control valve damaged   
					Burner does not light after ODS/pilot   
					is lit   
					1. Burner orifice clogged   
					2. Inlet gas pressure is too low   
					3. Burner orifice diameter is too   
					small   
					4. Thermocouple leads discon-   
					nected or improperly connected   
					5. Burners will not come in   
					remote position   
					1.Clean burner (see Cleaning   
					and Maintenance, page 13) or   
					replace burner orifice.   
					2. Contact local propane/LP   
					gas company   
					3. Replace burner orifice   
					4. Reconnect leads (see wiring   
					diagram)   
					5. Replace battery in transmitter   
					and receiver   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					16   
				TROUBLESHOOTING   
					Continued   
					POSSIBLECAUSE   
					OBSERVED PROBLEM   
					REMEDY   
					Delayed ignition burner   
					1. Contact local gas company   
					2. Clean burner (see Cleaning and   
					Maintenance, page 13)   
					1. Manifold pressure is too low   
					2. Burner orifice clogged   
					Burner backfiring during combustion   
					1. Damaged burner   
					2. Gas regulator defective   
					1. Clean burner orifice (see   
					Cleaning and Maintenance, page   
					13)   
					2. Replace gas regulator   
					1. Residues from manufacturing   
					processes   
					Slight smoke or odor during initial   
					operation   
					1. Problem will stop after a few   
					hours of operation   
					2. Not enough air   
					3. Gas regulator defective   
					2. Check burner for dirt and debris.   
					If found, clean burner (see   
					Cleaning and Maintenance, page   
					13)   
					3. Replace gas regulator   
					1. Improper log placement   
					2. Air holes at burner inlet blocked   
					3. Burner flame holes blocked   
					1. Properly locate logs (see installing   
					logs, page 26)   
					2. Clean out air holes at burner inlet.   
					Periodically repeat as needed.   
					3. Remove blockage or replace burner   
					Dark residue on logs or inside of   
					fireplace   
					1. Metal expanding while heating   
					or contracting while cooling   
					1. This is common with most   
					heaters. If noise is excessive,   
					contact qualified service person   
					Heater produces a clicking/ticking   
					noise just after burner is lit or   
					shut off   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 7   
				ILLUSTRATED   
					PARTS BREAKDOWN   
					QL300RYLA   
					QN300RYLA   
					QL300RYLA-W   
					QN300RYLA-W   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					18   
				PARTS LIST   
					QL300RYLA   
					QN300RYLA   
					QL300RYLA-W   
					QN300RYLA-W   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 9   
				ILLUSTRATED   
					PARTS BREAKDOWN   
					QL300RYLA   
					QN300RYLA   
					QL300RYLA-W   
					QN300RYLA-W   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					20   
				PARTS LIST   
					QL300RYLA   
					QN300RYLA   
					QL300RYLA-W   
					QN300RYLA-W   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					2 1   
				PLACING INSTRUCTION   
					Follow the procedures below and the instruction drawings to put log sets in   
					place to the gas stove(indoor vent-free).   
					THEN REMOVE SCREEN AND TAKE   
					THE LOG’S PACKAGE IS   
					OUT THE LOG’S PACKAGE   
					LOCATED INSIDE THE UNIT   
					FIRST REMOVE TWO TOP SCREWS   
					FROM SCREEN   
					BOTTOM PANEL   
					NOTICE: THE CORRECT POSITION OF THE LOGS SHOULD NOT IM-   
					PINGE ON THE FLAME.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					22   
				Q SERIES LOG SET   
					INSTALLATION INSTRUCTIONS   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					INSTALLATION INSTRUCTIONS FOR LOG SETS   
					1. All logs   
					FIG(2)   
					FIG(1)   
					STEP 1: Install the log 1 on the left rear angle iron.   
					see FIG(2)   
					FIG(4)   
					FIG(3)   
					STEP 2: Install the log 2 on the right rear angle iron.   
					see FIG(3)   
					STEP 3: Install the log 3 on the front angle iron. See FIG(4).   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					1 
					STEP 4: Insert the pinhole on the upper part of log 4 into the pin on   
					the left side of log 1. Place the lower part of log 4 on the flat roof at   
					the left side of log 3   
					See FIG(5).   
					FIG(5)   
					FIG(6)   
					STEP 4: Insert the pinhole on the upper part of log 5 into the pin on   
					the log 2. Place the lower part of log 5 on the flat roof at the left side   
					of log 3 . See FIG(6).   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
					2   
					 |