Powerware Power Supply 15 KVA User Manual

®
Powerware 9355 UPS  
10/15 kVA  
User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Requesting a Declaration of Conformity  
Units that are labeled with a CE mark comply with the following harmonized standards and EU directives:  
S
S
Harmonized Standards: IEC 62040-1-1 and IEC 62040-2; IEC 60950 Third Edition  
EU Directives:  
73/23/EEC, Council Directive on equipment designed for use within certain  
voltage limits  
93/68/EEC, Amending Directive 73/23/EEC  
89/336/EEC, Council Directive relating to electromagnetic compatibility  
92/31/EEC, Amending Directive 89/336/EEC relating to EMC  
The EC Declaration of Conformity is available upon request for products with a CE mark. For copies of the EC  
Declaration of Conformity, contact:  
Eaton Power Quality Oy  
Koskelontie 13  
FIN-02920 Espoo  
Finland  
Phone: +358-9-452 661  
Fax: +358-9-452 665 68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Special Symbols  
The following are examples of symbols used on the UPS to alert you to important information:  
RISK OF ELECTRIC SHOCK - Indicates that a risk of electric shock is present and the associated  
warning should be observed.  
CAUTION: REFER TO OPERATOR’S MANUAL - Refer to your operator’s manual for additional  
information, such as important operating and maintenance instructions.  
This symbol indicates that you should not discard the UPS or the UPS batteries in the trash. This  
product contains sealed, lead-acid batteries and must be disposed of properly. For more information,  
contact your local recycling/reuse or hazardous waste center.  
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE) in  
the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.  
ON - Indicates that the switch is in the ON position.  
OFF - Indicates that the switch is in the OFF position.  
PHASE - The word “phase.”  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
1
2
3
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
1
5
9
UPS Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Inspecting the Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
9
Floor Loading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
Unloading the Cabinet(s) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Three-High Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11  
Two-High UPS Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14  
Selecting an Installation Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
4
5
6
7
8
UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
Wall-Mounted Bypass Switch Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Stabilizing the Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Extended Battery Module Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47  
Installing Communication Options and Control Terminals . . . . . . . . . . . . . . . . . . . . . . . 48  
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
DB-9 Communication Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
X-Slot Cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52  
Remote Monitor Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54  
Industrial Relay Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58  
Powerware LanSafe Power Management Software . . . . . . . . . . . . . . . . . . . . . . . . . 59  
Control Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60  
Remote Emergency Power-off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61  
Relay Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
Programmable Signal Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
9
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
Control Panel Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65  
Changing the Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66  
Display Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66  
User Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68  
Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
UPS Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Maintenance Bypass Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
Internal Bypass Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71  
Normal Mode Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72  
Starting the UPS on Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73  
Configuring the UPS for EBMs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73  
UPS Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75  
10 UPS Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
UPS and Battery Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
Storing the UPS and Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
When to Replace Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
Recycling the Used Battery or UPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
Using the UPS Maintenance Bypass Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79  
11 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81  
12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87  
Typical Alarms and Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87  
Silencing the Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88  
Service and Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89  
13 Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 1  
Introduction  
®
The Powerware 9355 uninterruptible power supply (UPS) is a true  
online, double-conversion three-phase system that can be used to  
prevent loss of valuable electronic information and minimize equipment  
downtime. It is ideal for protecting essential information technology and  
electrical engineering infrastructure in corporate, telecom, health care,  
banking, and industrial applications.  
The Powerware 9355 UPS continually monitors incoming electrical  
power and removes the surges, spikes, sags, and other irregularities  
that are inherent in commercial utility power. Working with a building’s  
electrical system, the UPS supplies clean, consistent power that  
sensitive electronic equipment requires for reliable operation. During  
brownouts, blackouts, and other power interruptions, batteries provide  
emergency power to safeguard operation.  
With the Powerware 9355 UPS, you can safely eliminate the effects of  
electrical line disturbances and guard the integrity of your systems and  
equipment. Figure 1 shows the Powerware 9355 UPS and an optional  
Extended Battery Module (EBM).  
Figure 1. The Powerware 9355 UPS and EBM (3-High Cabinets Shown)  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
Providing outstanding performance and reliability, the Powerware 9355  
UPS’s unique benefits including the following:  
S Online UPS design with pure sine wave output. The UPS filters and  
regulates incoming AC power and provides consistent power to your  
equipment without draining the battery.  
S More wattage in less space with a 0.9 power factor – protecting more  
equipment and leaving more room for expansion.  
S A UPS maintenance bypass switch provides a Make-Before-Break  
(MBB) wrap-around bypass for UPS maintenance or service without  
shutting down the load.  
®
S Support for Powerware Hot Sync paralleling of multiple modules for  
redundancy or extra capacity.  
S Input current total harmonic distortion (THD) of less than five percent,  
using active input power factor correction.  
®
S ABM technology that uses advanced battery management to  
increase battery service life, optimize recharge time, and provide a  
warning before the end of useful battery life.  
S Up to three hours of extended runtime with added EBMs.  
S Advanced power management with the Software Suite CD for  
graceful shutdowns and power monitoring.  
S Emergency shutdown control through the Remote Emergency  
Power-off (REPO) port.  
S Start-on-battery capability for powering up the UPS even if utility  
power is not available.  
S Standard communication options with a DB-9 serial port, relay output  
contacts, and programmable signal inputs.  
S Optional X-Slott cards enhance communication capabilities for  
increased power protection and control.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
The following options for the Powerware 9355 are available:  
S Remote Monitor Panel (RMP)  
The optional RMP provides monitoring of the operational status and  
alarm condition of the UPS from virtually any location within the  
facility. You can install multiple RMPs at remote locations to increase  
your monitoring capabilities.  
S Power Distribution Module (PDM)  
The optional PDM comes equipped with several different types of  
output receptacles.  
S Parallel Tie Cabinet  
An optional parallel system with up to four UPSs can be installed to  
provide a parallel capacity and/or redundant system. This load sharing  
system provides more capacity than a single UPS and can provide  
backup, depending on the load and configuration. In addition, when  
one UPS is taken out of service for maintenance or is not operating  
properly, a redundant UPS continues to supply uninterrupted power  
to the critical load. A parallel Powerware Hot Sync Computer Area  
Network (CAN) Bridge Card provides connectivity for system  
metering and operational mode control. The parallel system consists  
of two to four UPSs, each with a parallel CAN Bridge Card, and a parallel  
tie cabinet. Refer to the Powerware 9355 Parallel UPS (10/15 kVA)  
User’s Guide for more information.  
S Wall-Mounted Bypass Switch  
The optional wall-mounted bypass switch is used to bypass the UPS  
during maintenance or servicing, providing wrap-around bypass for  
UPS service without shutting down the load.  
S Input Isolation Transformer  
The optional input isolation transformer is located at the bottom of a  
3-high UPS model. The isolation transformer allows operation from a  
480V or 600V 60-Hz source.  
S Seismic Kit  
The optional seismic kit secures the UPS and optional EBMs for  
Zone 4 seismic installations.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTRODUCTION  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 2  
Safety Warnings  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important instructions that you should follow during installation and  
maintenance of the UPS and batteries. Please read all instructions before operating the  
equipment and save this manual for future reference.  
DANGER  
This UPS contains LETHAL VOLTAGES. All repairs and service should be performed by  
AUTHORIZED SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS  
inside the UPS.  
WARNING  
S This UPS contains its own energy source (batteries). The UPS output may carry live  
voltage even when the UPS is not connected to an AC supply.  
S To reduce the risk of fire or electric shock, install this UPS in a temperature and humidity  
controlled, indoor environment, free of conductive contaminants. Ambient temperature  
must not exceed 40°C (104°F). Do not operate near water or excessive humidity (95%  
maximum).  
S To reduce the risk of fire, connect only to a circuit provided with 100 amperes maximum  
branch circuit overcurrent protection in accordance with the National Electrical Code,  
ANSI/NFPA 70.  
S Output overcurrent protection and disconnect switch must be provided by others.  
CAUTION  
S Batteries can present a risk of electrical shock or burn from high short circuit current.  
Observe proper precautions. Servicing should be performed by qualified service  
personnel knowledgeable of batteries and required precautions. Keep unauthorized  
personnel away from batteries.  
S Proper disposal of batteries is required. Refer to your local codes for disposal  
requirements.  
S Never dispose of batteries in a fire. Batteries may explode when exposed to flame.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
Consignes de Sécurité  
CONSIGNES DE SÉCURITÉ IMPORTANTES  
CONSERVER CES INSTRUCTIONS  
CE MANUEL CONTIENT DES CONSIGNES DE SÉCURITÉ  
IMPORTANTES  
DANGER!  
Cet onduleur contient des TENSIONS MORTELLES. Toute opération d’entretien et de  
réparation doit être EXCLUSIVEMENT CONFIÉE A UN PERSONNEL QUALIFIÉ AGRÉÉ.  
AUCUNE PIÈCE RÉPARABLE PAR L’UTILISATEUR ne se trouve dans l’onduleur.  
WARNING  
S Cet onduleur renferme sa propre source d’énergie (batteries). Les prises de sortie  
peuvent être sous tension même lorsque l’onduleur n’est pas branché sur le secteur.  
S Pour réduire les risques d’incendie et de décharge électrique, installer l’onduleur  
uniquement à l’intérieur, dans un lieu dépourvu de matériaux conducteurs, où la  
température et l’humidité ambiantes sont contrôlées. La température ambiante ne doit  
pas dépasser 40 °C. Ne pas utiliser à proximité d’eau ou dans une atmosphère  
excessivement humide (95 % maximum).  
S La protection contre une surintensité pour le(s) circuit(s) de sortie de courant alternatif  
doit être fournie par un autre fournisseur.  
S Les interrupteurs de déconnexion convenables pour le(s) circuit(s) de sortie de courant  
alternatif doivent être fournie par un autre fournisseur.  
ATTENTION!  
S Les batteries peuvent présenter un risque de décharge électrique ou de brûlure par des  
courts-circuits de haute intensité. Prendre les précautions nécessaires.  
S Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements  
en vigueur dans votre localité.  
S Ne jamais jeter les batteries au feu. L’exposition aux flammes risque de les faire  
exploser.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
Advertencias de Seguridad  
INSTRUCCIONES DE SEGURIDAD IMPORTANTES  
GUARDE ESTAS INSTRUCCIONES  
ESTE MANUAL CONTIENE INSTRUCCIONES DE SEGURIDAD  
IMPORTANTES  
PELIGRO  
Este SIE contiene VOLTAJES MORTALES. Todas las reparaciones y el servicio técnico deben  
ser efectuados SOLAMENTE POR PERSONAL DE SERVICIO TÉCNICO AUTORIZADO. No hay  
NINGUNA PARTE QUE EL USUARIO PUEDA REPARAR dentro del SIE.  
WARNING  
S Este SIE contiene su propia fuente de energía (las baterías). Los receptáculos de salida  
pueden transmitir corriente eléctrica aun cuando el SIE no esté conectado a un  
suministro de corriente alterna (c.a.).  
S Para reducir el riesgo de incendio o de choque eléctrico, instale este SIE en un lugar  
cubierto, con temperatura y humedad controladas, libre de contaminantes conductores.  
La temperatura ambiente no debe exceder los 40°C. No trabaje cerca del agua o con  
humedad excesiva (95% máximo).  
S La protección contra exceso de corriente para el/los circuito(s) de CA de salida será  
suministrada por terceros.  
S Los interruptores de desconexión debidamente clasificados para el/los circuito(s) de CA  
de salida serán suministrados por terceros.  
PRECAUCIÓN  
S Las baterías pueden presentar un riesgo de descargas eléctricas o de quemaduras  
debido a la alta corriente de cortocircuito. Preste atención a las instrucciones  
correspondientes.  
S Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales  
para conocer los requisitos pertinentes.  
S Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a  
la llama.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY WARNINGS  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 3  
UPS Setup  
This chapter describes:  
S Equipment inspection  
S Floor loading and clearances  
S Unloading the cabinet(s)  
The instructions are intended for the chief operator/system supervisor,  
electrical consultants, and installation electricians. Local regulations and  
electrical code must be followed during the UPS installation.  
Inspecting the Equipment  
If any equipment has been damaged during shipment, keep the shipping  
and packing materials for the carrier or place of purchase and file a claim  
for shipping damage. If you discover damage after acceptance, file a  
claim for concealed damage.  
To file a claim for shipping damage or concealed damage: 1) File with  
the carrier within 15 days of receipt of the equipment; 2) Send a copy of  
the damage claim within 15 days to your service representative.  
NOTE Check the battery recharge date on the packaging label. If the date has expired and  
the batteries were never recharged, do not use the UPS. Contact your service representative.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
Floor Loading  
When planning the installation, consider the UPS weight for floor  
loading. The strength of the installation surface must be adequate for  
point and distributed loadings. The approximate weights are shown in  
the following table.  
Standard Model Floor Loadings  
Maximum  
Point Loading  
lb/in2 (kg/cm2)  
Powerware 9355  
2-High UPS  
Weight (lb)  
381 lb (173 kg)  
587 lb (266 kg)  
619 lb (281 kg)  
480 lb (218 kg)  
710 lb (322 kg)  
95 (6.7)  
147 (10.3)  
155 (10.9)  
120 (8.4)  
178 (12.5)  
3-High UPS-32  
3-High UPS-64  
2-High EBM  
3-High EBM  
Clearances  
The following clearances are recommended for the Powerware 9355  
UPS:  
From Front of Cabinet  
From Back of Cabinet  
36(91.4 cm) working space  
6(15.2 cm) without PDM installed; with PDM installed,  
clearance determined by customer-supplied mating plug  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
Unloading the Cabinet(s)  
The following tools are required for unloading the cabinet(s):  
S 15 mm wrench or socket  
S 7 mm nut driver or socket  
CAUTION  
The UPS and EBM are heavy (see page 10). Unloading the cabinets requires at least two  
people to safely remove the cabinets from the pallet.  
Three-High Cabinets  
To remove a three-high UPS or EBM from the shipping pallet:  
1. Remove the two M10 bolts securing the stabilizing bracket to the  
pallet (see Figure 2).  
M10 Bolts  
Figure 2. Removing the Stabilizing Bracket Bolts  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
2. Remove the four M4 screws securing the stabilizing bracket to the  
cabinet rear panel and remove the bracket (see Figure 3). Retain the  
hardware for later use.  
NOTE Be sure to retain the stabilizing bracket and hardware for later re-assembly onto the  
cabinet.  
3. Remove the three M10 bolts securing the rear shipping pad to the  
pallet and remove the shipping pad.  
NOTE Hold the back of the cabinet so that the bolts can be removed easily without the  
cabinet rolling backward.  
4. Remove the two M10 bolts securing the front shipping bracket and  
remove the bracket.  
Front Shipping  
Bracket  
M10 Bolts  
Stabilizing Bracket  
M10 Bolts  
M4 Screws  
Shipping Pad  
Figure 3. Removing the Brackets and Shipping Pad  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
NOTE Be sure to support the front and back of the cabinet when rolling it off the pallet to  
prevent tipping.  
5. Slowly roll the cabinet toward the rear of the pallet. Once the pallet  
tilts, continue rolling the cabinet down the pallet until the cabinet  
touches the floor (see Figure 4).  
Figure 4. Unloading the Cabinet  
6. With the UPS supported, slowly pull the pallet away from the UPS  
(see Figure 5).  
Figure 5. Removing the Pallet  
7. Roll the cabinet to the desired location.  
8. Continue to “Selecting an Installation Option” on page 17.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
Two-High UPS Cabinet  
To remove a two-high UPS from the shipping pallet:  
1. Remove the M10 bolt securing the vertical bracket to the pallet (see  
Figure 6).  
2. Remove and retain the three M4 screws securing the vertical  
bracket to the UPS. Remove the vertical bracket.  
M4 Screws  
M10 Bolt  
Figure 6. Removing the Vertical Bracket  
3. Reinstall the M4 screws to the UPS (see Figure 7).  
M4 Screws  
Figure 7. Reinstalling the M4 Screws  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
4. Repeat Steps 1 through 3 to remove the vertical bracket on the  
other side.  
5. Remove the three M10 bolts securing the rear shipping pad to the  
pallet and remove the shipping pad (see Figure 8).  
NOTE Hold the back of the cabinet so that the bolts can be removed easily without the  
cabinet rolling backward.  
6. Remove the two M10 bolts securing the front shipping bracket and  
remove the bracket.  
Front Shipping  
Bracket  
M10 Bolts  
M10 Bolts  
Shipping Pad  
Figure 8. Removing the Front Bracket and Shipping Pad  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
NOTE Be sure to support the front and back of the cabinet when rolling it off the pallet to  
prevent tipping.  
7. Slowly roll the cabinet toward the rear of the pallet. Once the pallet  
tilts, continue rolling the cabinet down the pallet until the cabinet  
touches the floor (see Figure 9).  
Figure 9. Unloading the Cabinet  
8. With the UPS supported, slowly pull the pallet away from the UPS  
(see Figure 10).  
Figure 10. Removing the Pallet  
9. Roll the cabinet to the desired location.  
10. Continue to the following section, “Selecting an Installation  
Option.”  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
Selecting an Installation Option  
You are now ready to install the Powerware 9355 UPS. Select one of the  
following installation options according to your UPS configuration:  
UPS Configuration  
Installation Chapter  
UPS only  
Chapter 4, “UPS Only Installation” on page 19  
UPS with an optional input isolation transformer  
UPS with an optional wall-mounted bypass switch Chapter 5, “Wall-Mounted Bypass Switch Installation” on page 29  
Chapter 4, “Input Isolation Transformer Installation” on page 19  
Parallel UPS configuration  
Refer to the Powerware 9355 Parallel UPS (10/15 kVA) User’s  
Guide.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS SETUP  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 4  
UPS Installation  
The Powerware 9355 has the following power connections:  
S 3-phase (L1, L2, and L3), neutral, and ground connection for  
rectifier/bypass input  
S 3-phase (L1, L2, and L3), neutral, and ground connection for load  
output  
The nominal input/output voltages are:  
S 120/208 or 127/220 Vac with 120° phase displacement  
S 480V or 600V 60-Hz input is available using the optional input isolation  
transformer module  
Output overcurrent protection and disconnect switch must be provided  
by others.  
Figure 15 through Figure 17 beginning on page 25 show the oneline  
diagrams.  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the UPS  
installation and initial startup. Risk of electrical shock.  
Use the following procedure to hardwire the UPS:  
1. Verify that the electrical connections to the installation site have  
been properly installed.  
2. A wall-mounted, user-supplied, readily-accessible disconnection  
device must be incorporated in the input wiring.  
Compare the circuit breaker ratings to the ones in Table 1 on  
page 22.  
3. Switch off utility power to the distribution point where the UPS will  
be connected. Be absolutely sure there is no power.  
4. Determine your equipment’s grounding requirements according to  
your local electrical code.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
5. Verify that the UPS battery circuit breaker is in the OFF position  
(see Figure 11).  
Battery Circuit Breaker  
UPS Wiring  
Access Cover  
Conduit Landing Plates  
Figure 11. UPS Rear View (3-High Shown)  
6. For UPS only installations, continue to Step 7; for UPS installations  
with an input isolation transformer, proceed to Step 10.  
7. Remove the UPS wiring access cover and one of the conduit  
landing plates and retain (see Figure 11).  
8. Punch two holes in the conduit landing plate for the input and  
®
output conduit using a Greenlee punch or similar device.  
9. Proceed to Step 12.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
10. Verify that the input circuit breaker is in the OFF position (see  
Figure 12).  
11. Remove the input isolation transformer wiring access cover and  
retain.  
Battery Circuit Breaker  
Input Isolation  
Transformer  
Wiring Access Cover  
Input Circuit Breaker  
Figure 12. UPS with Input Isolation Transformer Rear View  
12. Hardwire the input, output, and ground terminations for the UPS or  
input isolation transformer. See Table 1 for wiring specifications.  
For a detailed view of the terminal block, see Figure 13 or Figure 14  
on page 23.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral  
will void the warranty.  
NOTE The Powerware 9355 UPS is a single-feed UPS only.  
Table 1. Terminal Block Wiring  
10 kVA  
Input Voltage  
Wire  
Function  
Input Circuit  
Breaker Size  
L1, L2, L3, N  
Ground  
Tightening  
Torque  
Conduit Size2, 3  
(Number of Conduits)  
Wire Size1 Wire Size1  
208  
220  
Input  
45A  
45A  
20A  
20A  
6 AWG  
8 AWG  
10 AWG  
10 AWG  
12 AWG  
14 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
Ground  
120 lb in  
(13.5 Nm)  
1.00conduit (1)  
480 (with transformer)  
600 (with transformer)  
208  
12 AWG  
12 AWG  
8 AWG  
Output  
220  
8 AWG  
120 lb in  
(13.5 Nm)  
1.00conduit (1)  
480 (with transformer)  
600 (with transformer)  
8 AWG  
8 AWG  
15 kVA  
Input Voltage  
Wire  
Function  
Input Circuit  
Breaker Size  
L1, L2, L3, N  
Tightening  
Torque  
Conduit Size2, 3  
(Number of Conduits)  
Wire Size1 Wire Size1  
208  
Input  
60A  
60A  
30A  
25A  
4 AWG  
4 AWG  
10 AWG  
10 AWG  
6 AWG  
6 AWG  
6 AWG  
6 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
1.25conduit (1)  
1.25conduit (1)  
1.00conduit (1)  
1.00conduit (1)  
220  
120 lb in  
(13.5 Nm)  
480 (with transformer)  
600 (with transformer)  
208  
Output  
220  
120 lb in  
(13.5 Nm)  
1.00conduit (1)  
480 (with transformer)  
600 (with transformer)  
1 Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table  
310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in  
the conduit, or long service runs. Follow local requirements.  
2 Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be  
run in the same conduit as the phase conductors.  
3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG  
ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the  
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.  
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
Ground  
Figure 13. UPS Terminal Block (3-High Shown)  
L1 L2 L3  
INPUT  
N
L1 L2 L3  
OUPUT  
N
N
Figure 14. Input Isolation Transformer Terminal Block  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
13. For UPS only installations, replace the UPS wiring access cover and  
conduit landing plate.  
For UPS installations with an input isolation transformer, replace the  
transformer’s wiring access cover.  
14. Continue to “Stabilizing the Cabinet” on page 39 to complete the  
UPS installation.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
Figure 15. UPS Wiring Diagram  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
Figure 16. UPS with Extended Battery Modules Wiring Diagram  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
Figure 17. UPS with Input Isolation Transformer Wiring Diagram  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS INSTALLATION  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 5  
Wall-Mounted Bypass Switch Installation  
This chapter describes installing the wall-mounted bypass switch with  
the UPS. The wall-mounted bypass switch is a Make-Before-Break  
maintenance bypass switch.  
NOTE The input isolation transformer cannot be used with the wall-mounted bypass  
switch.  
The Powerware 9355 has the following power connections:  
S 3-phase (L1, L2, and L3), neutral, and ground connection for  
rectifier/bypass input  
S 3-phase (L1, L2, and L3), neutral, and ground connection for load  
output  
The nominal input/output voltages are:  
S 120/208 or 127/220 Vac with 120° phase displacement  
Output overcurrent protection and disconnect switch must be provided  
by others.  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the UPS  
installation and initial startup. Risk of electrical shock.  
Use the following procedure to hardwire the bypass cabinet:  
1. Verify that the electrical connections to the installation site have  
been properly installed.  
2. A wall-mounted, user-supplied, readily-accessible disconnection  
device must be incorporated in the input wiring.  
Compare the circuit breaker ratings to the ones in Table 2 on  
page 33.  
3. Switch off utility power to the distribution point where the bypass  
cabinet and UPS will be connected. Be absolutely sure there is no  
power.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
4. Determine your equipment’s grounding requirements according to  
your local electrical code.  
5. Remove the bypass cabinet front cover (see Figure 18).  
Figure 18. Bypass Cabinet Front Cover  
6. Remove the internal cover to gain access to the breakers (see  
Figure 19).  
Internal  
Cover  
Figure 19. Internal Cover  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
7. Punch holes for the conduit (AC input, UPS output, load connection,  
and maintenance bypass contact wires) using a Greenlee punch or  
similar device.  
8. Verify that the bypass breaker is in the OFF position (see Figure 20).  
9. Mount the bypass cabinet to the wall and install the conduit.  
Figure 20. Bypass Breaker  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
10. Verify that the UPS battery circuit breaker is in the OFF position  
(see Figure 21).  
11. Remove the UPS wiring access cover and one of the conduit  
landing plates and retain.  
Battery Circuit Breaker  
UPS Wiring  
Access Cover  
Conduit Landing Plates  
Figure 21. UPS Rear View (3-High Shown)  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
12. Hardwire the UPS input terminations.  
See Table 2 for specifications and Figure 22 for a detailed view of  
the UPS terminal block.  
NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral  
will void the warranty.  
NOTE The Powerware 9355 UPS is a single-feed UPS only.  
Table 2. UPS Terminal Block Wiring  
10 kVA  
Input Voltage  
Wire  
Function  
Input Circuit  
Breaker Size  
L1, L2, L3, N  
Ground  
Tightening  
Torque  
Conduit Size2, 3  
(Number of Conduits)  
Wire Size1 Wire Size1  
208  
220  
208  
220  
Input  
45A  
45A  
6 AWG  
8 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
Ground  
120 lb in  
(13.5 Nm)  
1.00conduit (1)  
Output  
8 AWG  
120 lb in  
(13.5 Nm)  
1.00conduit (1)  
8 AWG  
15 kVA  
Input Voltage  
Wire  
Function  
Input Circuit  
Breaker Size  
L1, L2, L3, N  
Tightening  
Torque  
Conduit Size2, 3  
(Number of Conduits)  
Wire Size1 Wire Size1  
208  
220  
208  
220  
Input  
60A  
60A  
4 AWG  
4 AWG  
6 AWG  
6 AWG  
10 AWG  
10 AWG  
10 AWG  
10 AWG  
1.25conduit (1)  
120 lb in  
(13.5 Nm)  
1.25conduit (1)  
Output  
120 lb in  
(13.5 Nm)  
1.00conduit (1)  
1 Use only 90°C-rated copper wire. Minimum wire size is based on 120/208 full load ratings applied to NEC Code Table  
310-16. Code may require a larger AWG size than shown in this table because of temperature, number of conductors in  
the conduit, or long service runs. Follow local requirements.  
2 Per NEC article 300-20(a), all three-phase conductors must be run in the same conduit. Neutral and ground must be  
run in the same conduit as the phase conductors.  
3 Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one #8 AWG  
ground conductor. If two neutral conductors or an oversized neutral conductor are to be installed, check the size of the  
conduit needed to accommodate the extra wire or size and use that conduit size in place of the conduit size listed.  
Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW-2, TW, THW, THHW, THW-2.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
Maintenance  
Bypass  
Contacts  
TB2  
Ground  
Figure 22. UPS Terminal Block (3-High Shown)  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
13. Hardwire the output terminations from the UPS to the bypass  
cabinet (see Figure 23).  
Ground  
Neutral  
Line 1  
Line 2  
Line 3  
Figure 23. UPS Output to Bypass Cabinet Wiring  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
14. Hardwire the load to the bypass cabinet (see Figure 24).  
15. Route the maintenance bypass wires through the conduit to the  
UPS terminal block (see Figure 22 on page 36).  
Connect the black wire to TB2-2 and the blue wire to TB2-3. Cap  
the red wire.  
NOTE The maintenance bypass contacts are normally-closed. To ensure proper bypass  
operation, DO NOT use the red wire (it is normally-open).  
16. Replace the UPS wiring access cover and conduit landing plate.  
Maintenance Bypass  
Wiring to UPS TB2  
Ground  
Neutral  
Line 1  
Line 2  
Line 3  
Figure 24. Load Connections  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
17. Wire the AC input to the bypass breaker (see Figure 25).  
Line 2  
Line 3  
Line 1  
Figure 25. Bypass AC Input Wiring  
18. Verify the bypass input.  
19. Reinstall the internal cover.  
20. Reinstall the bypass cabinet front cover.  
21. Continue to “Stabilizing the Cabinet” on page 39 to complete the  
UPS installation.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL-MOUNTED BYPASS SWITCH INSTALLATION  
Red Wire  
(open when breaker is open)  
Black Wire  
(common)  
Blue Wire  
(closed when breaker is open)  
225A  
Bypass Input  
80A (4X)  
LOAD  
From UPS 1 Output  
Not Used  
Not Used  
Not Used  
Figure 26. Bypass Wiring Diagram  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 6  
Stabilizing the Cabinet  
NOTE For seismic installations, you MUST order and install a Powerware 9355 UPS  
seismic kit; do not use the following instructions.  
NOTE For non-seismic installations, you MUST install the stabilizing bracket on all 3-high  
cabinets. The stabilizing bracket is optional for 2-high cabinets.  
1. Lower the leveling feet to prevent the cabinet from rolling.  
Figure 27. Lowering the Leveling Feet  
2. Attach the stabilizing bracket to the bottom of the cabinet rear panel  
using the retained hardware from the shipping pallet according to  
the cabinet configuration:  
S For one cabinet, see Figure 28.  
S For two cabinets, see Figure 29.  
S For three cabinets, see Figure 30.  
NOTE No more than three cabinets can be attached together. For four cabinets, use two of  
the two-cabinet installations. For five cabinets, use one three-cabinet and one two-cabinet  
installation.  
3. Use the holes and slots in the bottom of the bracket to attach the  
cabinet to the flooring if desired.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STABILIZING THE CABINET  
4. Continue to one of the following sections:  
S “Extended Battery Module Installation” on page 43 to install  
optional EBMs.  
S “Communication” on page 47 to install UPS communication  
options, such as X-Slot cards or Remote Emergency Power-off.  
S “Operation” on page 65 to start up the UPS.  
M4 Screws  
Figure 28. Stabilizing Bracket with One Cabinet  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STABILIZING THE CABINET  
M4 Screws  
Figure 29. Stabilizing Bracket with Two Cabinets  
M4 Screws  
Figure 30. Stabilizing Bracket with Three Cabinets  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STABILIZING THE CABINET  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 7  
Extended Battery Module Installation  
NOTE A maximum of 22 battery strings can be installed in one configuration, including  
UPS batteries (4 EBM-64 models or 3 EBM-96 models). UPS-32 models contain 2 strings;  
UPS-64 models contain 4 strings; EBM-64 models contain 4 strings; and EBM-96 models  
contain 6 strings.  
NOTE For non-seismic installations, you MUST install the stabilizing bracket on all 3-high  
cabinets. The stabilizing bracket is optional for 2-high cabinets.  
If you are installing an optional EBM(s), use the following steps:  
1. Position the EBM adjacent to the next cabinet.  
2. Verify that all battery circuit breakers are in the OFF position (see  
Figure 31).  
3. Remove the two ground straps from the EBM rear panel(s).  
4. Install one ground strap between the UPS and the EBM rear panels  
as shown in Figure 31.  
5. If additional EBMs are installed, attach another ground strap  
between the first and second EBM as shown in Figure 31. Repeat  
for each additional EBM.  
6. Plug the EBM cable into the UPS battery connector.  
7. If additional EBMs are installed, plug the EBM cable of the second  
cabinet into the battery connector on the first EBM. Repeat for each  
additional EBM.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTENDED BATTERY MODULE INSTALLATION  
EBM Battery  
Circuit Breaker  
Rear Ground Strap  
UPS Battery Connector  
EBM Battery Connector  
UPS Battery Circuit Breaker  
EBM Cable  
Figure 31. Typical EBM Installation (2-High Cabinets Shown)  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTENDED BATTERY MODULE INSTALLATION  
8. Remove the top front covers of all cabinets.  
9. Install the remaining ground straps between each cabinet (see  
Figure 32).  
Front Ground Strap  
Figure 32. Front Ground Strap Installation (2-High Cabinets Shown)  
10. Continue to one of the following sections:  
S “Communication” on page 47 to install UPS communication  
options, such as X-Slot cards or Remote Emergency Power-off.  
S “Operation” on page 65 to start up the UPS.  
NOTE After UPS startup, ensure maximum battery runtime by configuring the UPS for the  
correct number of EBMs (see page 73).  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXTENDED BATTERY MODULE INSTALLATION  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 8  
Communication  
This section describes the:  
S DB-9 communication port  
S X-Slot cards  
S Remote Monitor Panel and Industrial Relay Card (IRC)  
S Powerware LanSafe Power Management Software  
S Remote Emergency Power-off  
S Relay output contacts  
S Programmable signal inputs  
Figure 33 shows the location of the communication options and control  
terminals on the UPS.  
X-Slot Communication Bay #1  
Signal Input 1  
X-Slot Communication Bay #2  
Signal Input 2  
REPO (normally open)  
REPO (normally closed)  
DB-9 Communication Port  
Relay Contact  
Figure 33. Communication Options and Control Terminals  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Installing Communication Options and Control Terminals  
To access and install the communication options and control terminals:  
1. Remove the front covers of all cabinets, starting with the top  
cabinet. Press and release the handle latch at the bottom of each  
cover and then lift the cover up and off the cabinet (see Figure 34).  
Figure 34. Removing the Front Covers  
2. Install the appropriate X-Slot card and/or necessary cable(s) into the  
top cabinet (see Figure 33 and Figure 35).  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Figure 35. Installing Communication Cables  
3. On the bottom cover (and also the middle cover if 3-high), remove a  
knockout tab in the top edge of the cover for each cable:  
With wire cutters, cut either side of the tab and twist down to  
remove the tab (see Figure 36).  
Figure 36. Removing Knockout Tabs  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
4. Route the cable(s) to the approximate location of the cover access  
holes.  
5. Connect the cables to the appropriate location.  
See “Communication Options” on page 51 or “Control Terminals”  
on page 60 for detailed information.  
6. Reinstall the front covers, starting with the bottom cabinet (see  
Figure 37).  
Hang the top edge of the cover on the cabinet first, then lower the  
bottom edge and snap into place. Be sure the cables fit in the  
access holes in the covers.  
Figure 37. Reinstalling the Front Covers  
7. Continue to “Operation” on page 65 to start up the UPS.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Communication Options  
The Powerware 9355 has serial communication capabilities through the  
DB-9 communication port or through an X-Slot card in one of the  
available bays. In addition, the Powerware LanSafe Power Management  
Software can be installed and used to communicate with the UPS via  
one of the serial communication connections.  
The UPS supports two serial communication devices according to the  
following table:  
Independent  
Multiplexed  
X-Slot 1  
X-Slot 2  
DB-9 Communication Port  
Any X-Slot card  
Any X-Slot card except the Modem  
Card  
Not in use  
Any X-Slot card  
Any X-Slot card  
Powerware Relay Interface Card  
Powerware Hot Sync CAN Bridge Card  
Available  
Available  
Not in use  
NOTE You can configure relays, signal inputs, and the serial port baud rate through the  
front panel menus (see Table 8 on page 68).  
DB-9 Communication Port  
To establish communication between the UPS and a computer, connect  
your computer to the UPS communication port using the supplied  
communication cable.  
When the communication cable is installed, power management  
software can exchange data with the UPS. The software polls the UPS  
for detailed information on the status of the power environment. If a  
power emergency occurs, the software initiates the saving of all data  
and an orderly shutdown of the equipment.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
The cable pins are identified in Figure 38 and the pin functions are  
described in Table 3. See Figure 33 on page 47 for serial port location.  
5
9
4
8
3
7
2
6
1
Figure 38. Communication Port  
Table 3. Communication Port Pin Assignment  
Pin Number Signal Name Function  
Direction from the UPS  
2
3
5
TxD  
RxD  
GND  
Transmit to external device  
Receive from external device  
Signal common (tied to chassis)  
Out  
In  
X-Slot Cards  
X-Slot cards allow the UPS to communicate in a variety of networking  
environments and with different types of devices. The Powerware 9355  
has two available communication bays for any X-Slot card, including:  
t
S ConnectUPS -X Web/SNMP Card - has SNMP and HTTP capabilities  
as well as monitoring through a Web browser interface; connects to a  
twisted-pair Ethernet (10/100BaseT) network. It has a built-in  
switching hub that allows three additional network devices to be  
connected to the network without the requirement of additional  
network drops. In addition, a Powerware Environmental Monitoring  
Probe can be attached to obtain humidity, temperature, smoke alarm,  
and security information.  
S Relay Interface Card - has isolated dry contact (Form-C) relay outputs  
for UPS status: Utility failure, Low battery, UPS alarm/OK, or On  
bypass.  
®
S Modbus Card - allows you to continuously and reliably monitor the  
UPSs in your Building Management System (BMS).  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
S Industrial Relay Card - is used to indicate the operating status of the  
UPS using the customer’s monitoring equipment and to connect an  
optional RMP. The IRC uses four isolated normally-open or  
normally-closed dry relay contacts to indicate the UPS status. Normal,  
Bypass, Battery, and Alarm mode can be monitored (see page 58 for  
more information).  
S Multi-Server Card - has six serial communication ports that can  
communicate simultaneously with other computers using Powerware  
LanSafe Power Management Software (provided on the Software  
Suite CD).  
S Modem Card - provides out-of-band remote notification and  
monitoring using modem communication directly to cell phones and  
pagers.  
S Single-Port Card - connects to the Powerware Expansion Chassis to  
enable multiple communication options or to a PC for power  
management control.  
S ConnectUPS-MX SNMP Card - has Ethernet, modem, and SNMP  
capabilities.  
S USB Card - connects to a USB port on your computer.  
NOTE The Powerware 9355 does not detect plug-and-play hardware. Before installing the  
USB Card, set the UPS baud rate to 1200 through the front panel (see Table 8 on page 68).  
See Figure 33 on page 47 for the location of the two X-Slot  
communication bays.  
ConnectUPS-X Web/SNMP Card  
Multi-Server Card  
Modem Card  
Relay Interface Card  
Modbus Card  
Single-Port Card  
ConnectUPS-MX SNMP Card  
USB Card  
Industrial Relay Card  
Figure 39. Optional X-Slot Cards  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Remote Monitor Panel  
The optional RMP can be installed to monitor the operation of the UPS  
from virtually any location within your facility, up to 152.4m (500 ft) from  
the UPS. You can surface-mount an RMP on a desktop or on a wall,  
wherever you have a serial interface line. Figure 40 shows an RMP.  
Figure 41 shows the enclosure dimensions and cable exit openings.  
Cable Exit Opening for 1/2” Conduit  
or Provided Strain Relief  
Horn Silence Button  
Figure 40. Remote Monitor Panel  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Cable Exit Openings  
for 1/2” Conduit or  
Provided Strain Relief  
(3 places)  
Mounting Slots  
(6 places)  
NOTE Matches mounting holes on a single- or  
double-gang electrical box.  
Dimensions are in mm [inches]  
Figure 41. RMP Dimensions  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
To install an RMP:  
NOTE If mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud  
within the wall. Do not use hollow wall anchors. The RMP can also be mounted to a single-  
or double-gang electrical box.  
1. If wall mounting, securely mount the RMP. Continue to Step 2.  
If desk mounting, install the provided bumpers to the bottom of the  
RMP enclosure. Proceed to Step 3.  
2. Install 1/2conduit from the RMP to the IRC through the cable exit  
openings (see Figure 41). Proceed to Step 4.  
3. Install wiring from the RMP to the IRC using the cable listed in  
Table 4 and the provided strain relief bushings in the cable exit  
openings in the IRC (see Figure 43) and the RMP.  
4. Connect the wiring between the RMP and the IRC plug-in terminal  
blocks using terminations shown in Table 4. See Figure 42 and  
Figure 43 for plug-in terminal block locations.  
Table 4. RMP Wire Terminations  
From RMP Terminal  
To IRC Terminal  
Remarks  
J1-1  
J1-3  
J1-4  
J1-5  
J1-6  
J1-1  
J1-3  
J1-4  
J1-5  
J1-6  
Use Beldon 8690 060 or  
equivalent cable  
5. Install the IRC into an open X-Slot communication bay (see  
page 48).  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
6. To check the operation of the RMP, ensure that the UPS is  
supplying the load via the inverter or bypass. If the indicators on the  
RMP show the appropriate status, then it is operating correctly.  
If the RMP is not operating correctly, check the wiring, the fuse on  
the IRC, and the plug-in terminal blocks for proper seating. If all  
connections are secure but the RMP still does not operate  
correctly, replace the fuse. If this does not correct the problem,  
contact your service representative for verification that the RMP is  
working correctly.  
Plug-in Terminal Block J1  
to Industrial Relay Card  
NOTE Conduit and wiring  
supplied by the customer. The  
maximum distance between  
the RMP and the UPS is not to  
exceed 152.4m (500 ft).  
Figure 42. RMP Top Internal View  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Industrial Relay Card  
The IRC uses normally-open or normally-closed dry relay contacts to  
indicate the UPS status as listed in Table 5. Figure 43 shows an IRC.  
Plug-in Terminal Block J1 to RMP  
Plug-in Terminal Block J2  
Cable Exit Opening for 1/2” Conduit  
or Provided Strain Relief  
from Relay Contacts  
to Customer Monitoring Equipment  
Figure 43. Industrial Relay Card  
1. Verify that the UPS is turned off and all power sources are  
removed.  
2. Install wiring from the IRC to the monitoring equipment using 1/2”  
conduit through the cable exit opening in the IRC (see Figure 43).  
3. Connect wiring between the IRC and the monitoring equipment  
using terminations shown in Table 5. See Figure 43 for plug-in  
terminal block locations.  
4. Install the IRC into an open X-Slot communication bay (see  
page 48).  
5. To check the operation of the IRC, ensure that the UPS is supplying  
the load via the inverter or bypass. If the indicators on the  
customer’s monitoring equipment show the appropriate status,  
then it is operating correctly.  
If the IRC is not operating correctly, check the wiring, the fuse on  
the IRC, and the plug-in terminal blocks for proper seating. If all  
connections are secure but the IRC still does not operate correctly,  
replace the fuse. If this does not correct the problem, contact your  
service representative for verification that the IRC is working  
correctly.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Table 5. IRC Wire Terminations  
IRC Terminal  
J2-1  
Function  
NC  
Remarks  
J2-2  
COM  
NO  
Normal mode  
J2-3  
J2-4  
NC  
J2-5  
COM  
NO  
Bypass mode  
Battery mode  
Alarm mode  
J2-6  
J2-7  
NC  
J2-8  
COM  
NO  
J2-9  
J2-10  
J2-11  
J2-12  
NC  
COM  
NO  
NOTE Maximum contact rating: 250 Vac, 30 Vdc @ 5A; Wire range: 16–24 AWG  
Powerware LanSafe Power Management Software  
Each Powerware 9355 UPS ships with Powerware LanSafe Power  
Management Software and an interface cable. To begin installing  
Powerware LanSafe software, see the instructions accompanying the  
Software Suite CD.  
NOTE Use only the supplied communication cable to connect the UPS to your computer.  
Powerware LanSafe software provides up-to-date graphics of UPS  
power and system data and power flow. It also gives you a complete  
record of critical power events, and it notifies you of important UPS or  
power information. If there is a power outage and the Powerware 9355  
UPS battery power becomes low, Powerware LanSafe software can  
automatically shut down your computer system to protect your data  
before the UPS shutdown occurs.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Control Terminals  
The cables should be connected to the control terminals with a mating  
connector. Input and output terminals have a functional isolation from  
terminal to terminal. They are connected to the UPS chassis through  
individual 1 Mresistors.  
2
1
+ Polarity  
– Polarity  
Signal Input 1 (programmable)  
Signal Input 2 (programmable)  
2
1
+ Polarity  
– Polarity  
UPS  
Connectors  
(see Figure 33 on  
page 47)  
2
1
REPO Normally Open  
REPO Normally Closed  
2
1
Common  
3
2
1
Normally Closed  
Normally Open  
Relay Output  
Figure 44. External Control Terminal Connections  
NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or  
other mechanical control is preferred.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Remote Emergency Power-off  
REPO is used to shut down the UPS from a distance. This feature can  
be used for shutting down the load and the UPS by thermal relay, for  
instance in the event of room overtemperature. When REPO is  
activated, the UPS shuts down all converters, de-energizes all system  
relays, and fully powers down within 10-15 seconds.  
There are two REPO positions that may be used, normally-open or  
normally-closed.  
The pins on the normally-closed REPO connector are connected  
together. When this connection is open, the logic circuitry completely  
shuts down the UPS, thus preventing the power from supplying the  
load.  
If the use of normally-closed REPO operation is desired, replace the  
connector with a normally-closed external switch (see Figure 33 on  
page 47).  
If the use of normally-open REPO operation is desired, connect a  
normally-open external switch (see Figure 33 on page 47).  
NOTE To restart the UPS, reconnect the REPO connector pins and turn on the UPS  
manually. The pins must be shorted to keep the UPS running. Maximum resistance is 10 ohm.  
NOTE Leave the REPO connector installed in the REPO port on the UPS rear panel even if  
the REPO function is not needed.  
CAUTION  
The REPO must not be connected to any utility connected circuits. Reinforced insulation to  
the utility is required. The REPO switch must have a minimum rating of 24 Vdc and 20 mA.  
To ensure the UPS stops supplying power to the load during any mode of operation, the  
input power must be disconnected from the UPS when the emergency power-off function is  
activated.  
REPO Connections  
Wire Function  
Terminal Wire Size Rating  
Suggested Wire Size  
REPO  
L1  
L2  
12–22 AWG  
18 AWG (0.82 mm2)  
(4–0.32 mm2)  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Relay Output Contacts  
The UPS incorporates a programmable relay output with potential free  
contacts for remote alarm indications (see Figure 33 on page 47). An  
additional four relay outputs can be obtained with the X-Slot compatible  
Relay Interface Card.  
WARNING  
The relay contacts must not be connected to any utility connected circuits. Reinforced  
insulation to the utility is required. The relay contacts must have a maximum rating of  
30 Vdc/1A and 60 Vdc/2A nominal values.  
Programmable Signal Inputs  
The UPS incorporates two programmable signal inputs (see Figure 33 on  
page 47). Use of non-polar (relay) control input is recommended. The  
pins must be shorted with maximum resistance of 10 ohm in order to  
activate the specific input.  
NOTE See Figure 44 on page 60 for the polarity and verify these connections if polarity  
control is required.  
The default and programmable settings for the signal inputs are shown  
in Table 6.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
Table 6. Programmable Signal Inputs  
Signal  
Description  
Disable Bypass Operation  
Charger Off  
If active, the automatic transfer to the static bypass is prevented.  
If active, the battery charge function is disabled. In a utility power outage, the  
discharge of batteries is supported.  
Remote ON/OFF  
If active, the UPS output turns off regardless of the mode of operation.  
Auxiliary power, fan, communication, and rectifier/battery charger remain  
functional. Restart is initiated immediately when this signal is inactive.  
Request Bypass  
Request Normal  
Force Bypass  
If active, the UPS transfers to bypass if the bypass voltage, frequency, and  
synchronization are all okay.  
If active, the UPS transfers to inverter operation if not prohibited by REPO or an  
alarm condition.  
If active, the UPS is forced to static bypass operation regardless of the bypass  
status.  
External Battery Breaker Status  
Building Alarm 1–6  
If active, the UPS knows that the batteries are disconnected.  
These alarms can be activated separately or at the same time with other  
building alarms.  
Not in Use  
Default  
Shutdown  
If active, the UPS shuts down immediately.  
Delayed Shutdown  
If active, the UPS shuts down after a user-configured delay time. Default  
shutdown delay is 120 seconds. The UPS automatically restarts when the  
signal changes to inactive.  
Normal/Bypass  
On Generator  
If active, the UPS transfers to bypass if okay. If inactive, the UPS transfers to  
the inverter when possible.  
If active, the UPS knows that input is fed from the generator. Bypass is  
disabled; the automatic battery test is disabled.  
External Transformer  
Overtemperature  
This option is not used.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMUNICATION  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 9  
Operation  
This chapter contains information on how to use the Powerware 9355,  
including front panel operation, UPS startup and shutdown, and  
configuring the UPS for Extended Battery Modules.  
Control Panel Functions  
The UPS has a four-button graphical LCD with backlight. It provides  
useful information about the UPS itself, load status, events,  
measurements, and settings (see Figure 45).  
Power On Indicator (Green)  
On Battery Indicator (Yellow)  
Bypass Indicator (Yellow)  
Alarm Indicator (Red)  
Control Buttons  
for the LCD Menu Options  
Figure 45. Powerware 9355 Control Panel  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
The following table shows the indicator status and description.  
Indicator  
Status  
On  
Description  
The UPS is operating normally.  
Flashing  
S The UPS is starting up or is shut down and waiting for power to return.  
S A new information message is active.  
Green  
S Bypass is not available.  
Off  
On  
The UPS is turned off and will not turn on automatically.  
The UPS is in Battery mode.  
Yellow  
Yellow  
On  
The UPS is in Bypass mode.  
The UPS has an active alarm.  
On  
Flashing  
There is a new UPS alarm condition. See “Troubleshooting” on page 87 for  
additional information.  
Red  
Changing the Language  
Press and hold the first button on the left for approximately five seconds  
to select the language menu. This action is possible from any LCD menu  
screen.  
Display Functions  
As the default or after 15 minutes of inactivity, the LCD displays the  
selectable startup screen. The default is the Eaton Powerware logo and  
can be changed to the Mimic screen in the User Settings menu.  
The backlit LCD automatically dims after a long period of inactivity. Press  
any button to restore the screen.  
Use the two middle buttons ( and ) to scroll through the menu  
structure. Press the  
to select an option. Press the  
previous menu.  
button to enter a submenu. Press the  
button  
ESC  
button to cancel or return to the  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
The following table shows the basic menu structure.  
Table 7. Menu Map for Display Functions  
Main Menu  
Submenu  
Display Information or Menu Function  
UPS Status  
UPS off / System normal / UPS supporting load / UPS on  
battery / UPS on bypass / Active alarm list / Battery status  
Event Log  
Displays up to 100 events and alarms  
L-N and L-L / Current / Frequency / Power  
Voltage / Current / Runtime  
Measurements  
Output  
Battery  
Input  
L-N and L-L / Current / Frequency  
L-N and L-L / Frequency  
Bypass  
Control  
Go to Bypass Mode  
Forces the UPS to go to Bypass.  
When this command is active, the option changes to Go to  
Normal Mode.  
Start Battery Test  
Display Test  
Initiates a battery test  
Four different selectable tests for the front panel  
functions: the LEDs cycle through, the alarm beep sounds,  
the backlight turns off and on, and the pixels scroll  
through to test the LCD.  
Settings  
User Settings  
See Table 8 for detail.  
Service Settings  
This screen is password-protected.  
Identification  
UPS Type / Part Number / Serial Number / Firmware /  
Display / CAN Bridge  
Turn UPS ON/OFF  
ON and OFF Options  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
User Settings  
The following table displays the options that can be changed by the  
user.  
NOTE Changes to the output voltage or frequency options should be made before turning  
on the UPS; otherwise, the changes do not take effect.  
Table 8. User Settings  
Description  
Available Settings  
Default Setting  
Set Date and Time  
Set Month  
Date: mm/dd/yyyy  
Time: 24:00  
01/01/2003  
00:00  
Display Contrast  
Adjust contrast with up/down arrow  
buttons  
Moderate  
Change Language  
Set Nominal Input Voltage  
Relay Config  
Select Language:  
<English> or <Spanish>  
English  
Output:  
[120V/208V] [127V/220V]  
120V/208V  
Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or  
[X-Slot 2-1/2/3/4]  
Setup: [Battery Low] [On Battery] [On  
Bypass] [UPS ok] [custom] [empty]  
Alarm 1: empty  
X-Slots (1 or 2)  
#1: UPS ok  
#2: On Bypass  
#3: Summary Alarm  
#4: On Battery  
Signal Inputs  
[empty] [Logic]  
Empty  
(see “Programmable Signal Inputs”  
on page 62)  
Serial Port Config  
Start Screen  
Port: [X-Slot-1] [X-Slot-2/Serv]  
Speed: [19200] [9600] [2400] [1200]  
19200  
Eaton Powerware logo  
Mimic Screen  
Eaton Powerware logo  
Disabled  
User Password  
Enabled/Disabled  
If Enabled is selected, the password is  
USER.  
Audible Alarms  
Normal Sound/Disabled  
ABM cycling/constant  
Normal Sound  
ABM cycling  
Battery Charging  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
Table 8. User Settings (continued)  
Description  
Available Settings  
Default Setting  
Automatic Battery Tests  
Enabled/Disabled  
Enabled  
Enabled automatically runs the  
battery test once a month.  
Full Power Battery Test  
Enabled/Disabled  
Enabled  
Number of Battery Strings  
0 through 22  
2 strings for UPS-32 models  
(see “Configuring the UPS for EBMs” 4 strings for UPS-64 models  
on page 73)  
Battery Capacity  
1 through 65535 watts per cell  
1.750 through 1.950 volts per cell  
+1 through +20% (1% increments)  
-1 through -20% (1% increments)  
50 Hz or 60 Hz  
34 W/cell  
1.880 V/cell  
120V +10%  
120V -15%  
60 Hz  
Battery Low Alarm Level  
Bypass Voltage High Limit  
Bypass Voltage Low Limit  
Nominal Output Frequency  
Synchronization  
Enabled/Disabled  
Enabled  
2.0 Hz  
Synchronization Window  
0.5 through 3.0 Hz  
(0.1 Hz increments)  
Unsynchronized Transfer to Bypass  
Usage of Bypass  
Allowed/Not Allowed  
Enabled/Disabled  
Not Allowed  
Enabled  
After a delay  
0s  
Transfer to Bypass When Overload  
Automatic Start Delay  
After a delay/Immediately  
-1 through 32767 seconds  
(-1 means disabled)  
Control Commands from X-Slot1  
Allowed/Disabled  
Allowed  
Allowed  
5s  
Control Commands from X-Slot2/Serv Allowed/Disabled  
X-Slot Signal Input Activation Delay  
Input signal delayed shutdown delay  
Site Wiring Fault Notice  
0 through 65 seconds  
1 through 65535 seconds  
Enabled/Disabled  
0 through 32  
120s  
Enabled  
Empty  
Reset Custom Event Settings  
Auto Output Configuration  
Enabled/Disabled  
Enabled for initial startup  
Disabled after initial startup  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
Initial Startup  
Startup and operational checks must be performed by an authorized  
Eaton Customer Service Engineer, or the warranty terms as specified on  
page 91 become void. This service is offered as part of the sales  
contract for the UPS. Contact service in advance (usually a two-week  
notice is required) to reserve a preferred startup date.  
UPS Startup  
WARNING  
Only qualified service personnel (such as a licensed electrician) should perform the UPS  
installation and initial startup. Risk of electrical shock.  
Verify that UPS installation has been carried out correctly and the UPS  
ground has been connected.  
Maintenance Bypass Startup  
To start up the UPS in maintenance bypass:  
1. Verify that the maintenance bypass switch is in the BYPASS  
position (see Figure 46 on page 79).  
2. Switch on utility power where the UPS is connected. The load is  
now powered by utility power.  
To switch to Normal mode from maintenance bypass:  
1. If an optional isolation transformer is installed, switch the input  
circuit breaker to the ON position.  
2. Turn the maintenance bypass switch to the SERVICE position.  
The UPS starts up in Bypass mode, with the load still powered by  
utility power.  
3. Remove the breaker tie from all battery circuit breakers.  
4. Switch all battery circuit breakers to the ON position.  
NOTE Wait until the  
indicator illuminates before proceeding to Step 5; otherwise,  
power to the load may be lost.  
5. Turn the maintenance bypass switch to the UPS position to return  
to Normal mode. The UPS is now powering the load.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
Internal Bypass Startup  
To start up the UPS in Bypass mode:  
1. Verify that the maintenance bypass switch is in the UPS position  
(see Figure 46 on page 79).  
2. If an optional isolation transformer is installed, switch the input  
circuit breaker to the ON position.  
3. Switch on utility power where the UPS is connected.  
4. Wait for the front panel LCD to illuminate.  
The  
indicator flashes.  
5. Remove the breaker tie from all battery circuit breakers.  
6. Switch all battery circuit breakers to the ON position.  
The  
indicator stops flashing.  
7. Press any button on the front panel display to activate the menu  
options.  
8. Using the button on the front panel display, scroll to the Control  
menu option and press the  
button.  
9. Press the  
The and  
button to select the Go to Bypass Mode option.  
indicators illuminate, indicating the UPS is  
μ
operating in Bypass mode. The load is now powered by utility  
power.  
To switch to Normal mode from internal Bypass mode:  
1. Press the  
button to select the Go To Normal Mode option.  
ESC  
2. Press the  
button until the Eaton Powerware logo appears.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
Normal Mode Startup  
To start up the UPS:  
1. Verify that the maintenance bypass switch is in the UPS position  
(see Figure 46 on page 79).  
2. If an optional isolation transformer is installed, switch the input  
circuit breaker to the ON position.  
3. Switch on utility power where the UPS is connected.  
4. Wait for the front panel LCD to illuminate.  
The  
indicator flashes.  
5. Remove the breaker tie from all battery circuit breakers.  
6. Switch all battery circuit breakers to the ON position.  
The  
indicator stops flashing.  
7. Press any button on the front panel display to activate the menu  
options.  
8. Press the button on the front panel display and then press the  
button to select the TURN UPS ON/OFF menu.  
9. Select the ON option. Press and hold the  
button for three  
seconds, until the UPS stops beeping.  
The  
indicator illuminates. The UPS is now powering the load.  
μ
If the  
indicator is flashing, check the UPS status from the front  
panel to view the active alarms. Correct the alarms and restart if  
necessary.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
Starting the UPS on Battery  
NOTE Before using this feature, the UPS must have been powered by utility power at least  
once.  
To start the UPS on battery:  
1. Verify that the maintenance bypass switch is in the UPS position  
(see Figure 46 on page 79).  
2. Switch all battery circuit breakers to the ON position.  
NOTE Leave the battery circuit breaker(s) in the ON position during this operation. If you  
need to cancel this operation, wait until the front panel LCD illuminates before switching the  
battery circuit breaker(s) off.  
3. Wait for the front panel LCD to illuminate.  
4. Press any button on the front panel display to activate the menu  
options.  
5. Within three minutes, press the button on the front panel display  
and then press the  
menu.  
button to select the TURN UPS ON/OFF  
6. Select the ON option. Press and hold the  
button for three  
seconds, until the UPS stops beeping.  
The UPS starts within two minutes. The UPS supplies power to  
your equipment and goes into Battery mode.  
Configuring the UPS for EBMs  
To ensure maximum battery runtime, configure the UPS for the correct  
number of EBMs:  
1. Press any button on the front panel display to activate the menu  
options.  
2. Using the button, scroll to the Settings menu.  
3. Press the  
button twice to select the User Settings menu.  
4. Using the button, scroll to the Number of Battery Strings option  
and press the button.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
5. Use the or arrow buttons to select the number of strings  
according to your UPS configuration:  
All 2-High UPS and EBM Cabinets*  
Number of Strings  
UPS + 1 EBM  
6
UPS + 2 EBMs  
10  
UPS + 3 EBMs  
14  
UPS + 4 EBMs  
18  
All 3-High UPS and EBM Cabinets*  
UPS + 1 EBM  
Number of Strings  
10  
16  
22  
UPS + 2 EBMs  
UPS + 3 EBMs  
*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.  
UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.  
6. Press the  
button to save the setting.  
ESC  
7. Press the  
button until the Eaton Powerware logo appears.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
UPS Shutdown  
To shut down the UPS:  
1. Press any button on the front panel display to activate the menu  
options.  
2. Press the button on the front panel display and then press the  
button to select the TURN UPS ON/OFF menu.  
3. Select the OFF option; press the  
button.  
button.  
4. Confirm the selection; press the  
5. Press and hold the  
button for three seconds, until the UPS stops  
beeping.  
The input contactor opens.  
6. Switch the UPS battery circuit breaker to the OFF position.  
The UPS is disconnected from the batteries and is on logic power  
only.  
7. Switch off utility power where the UPS is connected.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATION  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 10 UPS Maintenance  
This section explains how to:  
S Care for the UPS and batteries  
S Recycle used batteries  
S Use the maintenance bypass switch  
UPS and Battery Care  
For the best preventive maintenance, keep the area around the UPS  
clean and dust-free. If the atmosphere is very dusty, clean the outside of  
the system with a vacuum cleaner.  
For full battery life, keep the UPS at an ambient temperature of  
77°F (25°C).  
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of  
service life varies, depending on the frequency of usage and ambient temperature.  
Batteries used beyond expected service life will often have severely reduced runtimes.  
Replace batteries at least every 5 years to keep units running at peak efficiency.  
Storing the UPS and Batteries  
When storing the UPS and optional cabinets, the following requirements  
should be met:  
S Verify that the battery circuit breaker is in the OFF position.  
S Avoid temperature and humidity extremes. To maximize battery life,  
the recommended storage temperature is 59°F (15°C) to 77°F (25°C).  
S If you store the UPS for a long period, recharge the batteries every  
10 months by applying utility power. The batteries charge to 80%  
capacity in approximately 3 hours. However, it is recommended that  
the batteries charge for 48 hours after long-term storage.  
S Check the battery recharge date on the shipping carton label. If the  
date has expired and the batteries were never recharged, do not use  
the UPS. Contact your service representative.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS MAINTENANCE  
When to Replace Batteries  
When the  
indicator flashes and the LCD panel displays Battery  
Failure, the batteries may need replacing. Contact your service  
representative to order new batteries.  
Change the batteries approximately every five years.  
Recycling the Used Battery or UPS  
Contact your local recycling or hazardous waste center for information  
on proper disposal of the used battery or UPS.  
WARNING  
S Do not dispose of the battery or batteries in a fire. Batteries may explode. Proper  
disposal of batteries is required. Refer to your local codes for disposal requirements.  
S Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the  
skin and eyes. It may be toxic.  
CAUTION  
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,  
lead-acid batteries and must be disposed of properly. For more information, contact your  
local recycling/reuse or hazardous waste center.  
CAUTION  
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper  
disposal, contact your local recycling/reuse or hazardous waste center.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS MAINTENANCE  
Using the UPS Maintenance Bypass Switch  
The UPS maintenance bypass switch is located on the back of the UPS  
(see Figure 46).  
The maintenance bypass switch is used to bypass the UPS during  
maintenance or servicing. The switch provides a wrap-around bypass  
without shutting down the load. The SERVICE position on the switch  
allows a service engineer to apply power to the UPS input and verify its  
operation while the load is powered through bypass.  
Figure 46. Maintenance Bypass Switch  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS MAINTENANCE  
To switch the UPS to maintenance bypass from Normal mode:  
1. Turn the maintenance bypass switch through the SERVICE position  
to the BYPASS position.  
The battery circuit breaker trips, and the UPS is now bypassed, with  
the load powered by utility power.  
2. The UPS automatically shuts down.  
To return to Normal mode from maintenance bypass:  
1. Turn the maintenance bypass switch to the SERVICE position.  
The UPS starts up in Bypass mode, with the load still powered by  
utility power.  
2. Switch the UPS battery circuit breaker to the ON position.  
NOTE Wait until the  
indicator illuminates before proceeding to Step 3; otherwise,  
power to the load may be lost.  
3. Turn the maintenance bypass switch to the UPS position to return  
to Normal mode. The UPS is now powering the load.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 11 Specifications  
This section provides the following specifications for the Powerware  
9355 models:  
S Model list  
S Dimensions and weights  
S Environmental and safety specifications  
S Technical specifications  
S Model specifications  
S Battery specifications  
S Battery runtimes  
Table 9. Model List  
UPS  
Description  
Power Rating  
PW9355-10-32  
2-high: UPS with one battery section  
10 kVA, 9 kW  
3-high: UPS with one battery and one isolation transformer section  
PW9355-10-64  
PW9355-15-32  
3-high: UPS with two battery sections  
10 kVA, 9 kW  
2-high: UPS with one battery section  
15 kVA, 13.5 kW  
3-high: UPS with one battery and one isolation transformer section  
PW9355-15-64  
3-high: UPS with two battery sections  
15 kVA, 13.5 kW  
EBM  
Description  
EBM-64  
EBM-96  
2-high: two battery sections  
3-high: three battery sections  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Table 10. Dimensions and Weights  
Weight  
Dimensions (H × W × D)  
2-High UPS  
381 lb (173 kg)  
32.2× 12× 33.5”  
(81 × 30 × 85 cm)  
3-High UPS-32  
3-High UPS-64  
2-High EBM  
3-High EBM  
587 lb (266 kg)  
619 lb (281 kg)  
480 lb (218 kg)  
710 lb (322 kg)  
47.8× 12× 33.5”  
(121.5 × 30 × 85 cm)  
47.8× 12× 33.5”  
(121.5 × 30 × 85 cm)  
32.2× 12× 30.3”  
(81 × 30 × 77 cm)  
47.8× 12× 30.3”  
(121.5 × 30 × 77 cm)  
Table 11. Environmental and Safety Specifications  
Operating Temperature  
10°C to 40°C (50°F to 104°F)  
Optimal battery performance: 25°C (77°F)  
Transit Temperature  
Storage Temperature  
-25°C to 55°C (-13°F to 131°F)  
0°C to 25°C (32°F to 77°F)  
Recommended battery storage: 15°C to 25°C (59°F to 77°F)  
Ventilation  
Altitude  
Front air intake, forced air, two fans, positive pressurization,  
temperature UPS-monitored  
9,843 ft (3,000m) operating without derating  
32,810 ft (10,000m) during transportation  
Relative Humidity  
Audible Noise  
5–95% noncondensing  
<56 dBA at 1 meter distance, typical loads  
<62 dBA for heavy load, high ambient or high altitude, on battery  
Surge Suppression  
Safety Conformance  
ANSI C62.41 Category B3  
NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;  
EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1  
Agency Markings  
EMC (Class A)  
UL, cUL, CE (pending)  
IEC 62040-2, FCC Part 15, ICES-003  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Table 12. Technical Specifications  
Technology  
Online, double-conversion topology with static bypass switch and 3-position  
maintenance bypass switch.  
Frequency independent operation.  
Input Voltage Range  
Input Power Factor  
Input Rated Voltage  
75/130–144/249 Vac per phase  
>0.99 at full load nominal line conditions  
120/208 or 127/220 Vac three-phase  
Isolation Transformer Input  
Voltage Range  
480V or 600V 20%  
60 Hz only  
Input Frequency Range  
Input Rated Frequency  
Output Voltage Regulation  
45–65 Hz  
50/60-Hz selectable, auto-configuring  
1% static, Phase to Neutral  
2% static, Phase to Phase  
5% dynamic at 100% resistive load change  
Response time <1 ms  
Output Voltage Distortion  
Output Frequency  
<2% THD linear load  
<5% THD non-linear load  
50/60-Hz selectable or auto-configuring  
Synchronization to line  
Output Frequency  
Regulation  
Output Overload  
101–110% for 10 minutes  
111–125% for 60 seconds  
126–149% for 5 seconds  
>150% for 300 milliseconds  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Table 13. Model Specifications  
10 kVA Model  
Output Voltage (Line–Line)  
Output Voltage (Line–Neutral)  
Input Voltage  
208  
120  
208  
208  
120  
208  
120  
220  
127  
220  
480 (with input 600V (with input  
isolation  
isolation  
transformer)  
transformer)  
Input Current  
32.2A  
27.8A  
10  
16A  
27.8A  
10  
13.3A  
27.8A  
10  
30.5A  
26.2A  
10  
Output Current  
Output kVA  
Output kW  
9
9
9
9
Efficiency (Minimum)  
Heat Rejection [BTU/hr (kg-cal/hr)]  
89%  
83%  
83%  
89%  
3798 (956)  
6294 (1585)  
6294 (1585)  
3798 (956)  
15 kVA Model  
Output Voltage (Line–Line)  
Output Voltage (Line–Neutral)  
Input Voltage  
208  
120  
208  
208  
120  
208  
120  
220  
127  
220  
480 (with input  
isolation  
600 (with input  
isolation  
transformer)  
transformer)  
Input Current  
48A  
41.6A  
15  
24A  
41.6A  
15  
20A  
41.6A  
15  
45.7A  
39.4A  
15  
Output Current  
Output kVA  
Output kW  
13.5  
13.5  
13.5  
13.5  
Efficiency (Minimum)  
Heat Rejection [BTU/hr (kg-cal/hr)]  
90%  
85%  
85%  
90%  
5122 (1290)  
8134 (2048)  
8134 (2048)  
5122 (1290)  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
Table 14. Battery Specifications  
Battery Type  
9 Ah sealed, valve-regulated lead acid (VRLA), maintenance-free, minimum 3-year float  
service life at 25°C (77°F), voltage 192 Vdc (96 cells per string)  
Number of Strings  
Maximum of 22 strings per full configuration, including UPS batteries  
(4 EBM-64 cabinets or 3 EBM-96 cabinets, plus UPS batteries)  
UPS-32: 2 strings; UPS-64: 4 strings  
EBM-64: 4 strings; EBM-96: 6 strings  
Battery Replacement  
Charger  
Must be replaced by a qualified service technician  
Service configurable 0.5–34A per string, with overall maximum of 34A (limited by input  
current). Default: 3.4A per string  
Charging  
Internal battery: approximately 3 hours to 80% usable capacity at nominal line voltage  
after full load discharge  
External battery: no more than 10x discharge time to 90% usable capacity at nominal line  
voltage after full load discharge  
Start-on-Battery  
Performance  
Allows start of UPS without utility input  
ABM technology increases battery service life, optimizes recharge time, and provides a  
warning before the end of useful battery life  
Protection  
Extended Battery Module output protected by 100A circuit breaker  
Table 15. Battery Runtimes (in Minutes) at Full Load  
2-High Cabinets  
32 Internal UPS  
Batteries  
Load  
(1) EBM-64  
(2) EBM-64  
(3) EBM-64  
(4) EBM-64  
15 kVA/13.5 kW  
10 kVA/9 kW  
4
8
23  
43  
69  
65  
88  
37  
106  
144  
3-High Cabinets  
64 Internal UPS  
Batteries  
Load  
(1) EBM-96  
(2) EBM-96  
(3) EBM-96  
15 kVA/13.5 kW  
10 kVA/9 kW  
13  
22  
43  
69  
76  
113  
184  
124  
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SPECIFICATIONS  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 12 Troubleshooting  
The Powerware 9355 is designed for durable, automatic operation and  
also alerts you whenever potential operating problems may occur.  
Usually the alarms shown by the control panel do not mean that the  
output power is affected. Instead, they are preventive alarms intended  
to alert the user. Use the following troubleshooting chart to determine  
the UPS alarm condition.  
Typical Alarms and Conditions  
The following table describes typical alarms and conditions; check the  
Event Log through the control panel for a list of active alarms. If an alarm  
appears with a service code, please contact the Help Desk (see  
page 89).  
Alarm or Condition  
Possible Cause  
Action  
On Battery  
A utility failure has occurred and the  
UPS is in Battery mode.  
The UPS is powering the equipment with battery  
power. Prepare your equipment for shutdown.  
LED is on.  
1 beep every second.  
Battery Low  
The battery is running low.  
Five minutes or less of battery power remains  
(depending on load configuration and battery  
charge). Save your work and turn off your  
equipment.  
When utility power is restored, the UPS restarts  
automatically, provides power to the load, and  
charges the battery.  
LED is on.  
Continuous beep for  
10 seconds.  
Battery Breaker  
The UPS does not recognize the  
internal batteries.  
Verify the battery circuit breaker is in the ON  
position. If the condition persists, contact your  
service representative.  
LED is on.  
1 beep every second.  
Overload  
Power requirements exceed the UPS Remove some of the equipment from the UPS. The  
capacity (greater than 100% of  
nominal; see page 83 for specific  
output overload ranges).  
UPS continues to operate, but may switch to  
Bypass mode if the load increases. The alarm  
resets when the condition becomes inactive.  
LED is on.  
1 beep every second.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Alarm or Condition  
Possible Cause  
Action  
Overtemperature  
UPS internal temperature is too high  
or the fan has failed.  
Turn the maintenance bypass switch to the  
SERVICE position. Otherwise, shut down the UPS.  
Clear vents and remove any heat sources. Allow  
the UPS to cool. Ensure the airflow around the UPS  
is not restricted.  
If the alarm disappears, turn the maintenance  
bypass switch back to the UPS position.  
If the condition persists, contact your service  
representative.  
LED is on.  
1 beep every second.  
Battery test failed  
The batteries need service.  
Contact your service representative.  
Verify that the main utility breaker is on.  
The UPS does not start. The main utility breaker is off.  
If an optional isolation transformer is Verify that the isolation transformer input circuit  
installed, the input circuit breaker is  
off.  
breaker is on.  
The Remote Emergency Power-off  
switch is active or the REPO  
connector is missing.  
Reset the REPO switch and restart the UPS. Verify  
that the REPO connector is present.  
Power is not available to The UPS is in Standby mode.  
the UPS output.  
Supply power to the connected equipment: Press  
any button on the front panel display to activate the  
menu options. Press the button on the front panel  
display and then press  
the  
button to select the TURN UPS ON/OFF  
menu. Select the ON option. Press and hold the  
button for three seconds, until the UPS stops  
beeping.  
The UPS does not  
provide the expected  
backup time.  
The batteries need charging or  
service.  
Apply utility power for 48 hours to charge the  
batteries. If the condition persists, contact your  
service representative.  
Battery circuit breakers are in the OFF Switch all battery circuit breakers to the ON  
position. position.  
Silencing the Alarm  
Before silencing an alarm, check the alarm condition and perform the  
applicable action to resolve the condition.  
Press any button on the front panel display to silence the alarm. If the  
alarm status changes, the alarm beeps again, overriding the previous  
alarm silencing.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
Service and Support  
If you have any questions or problems with the UPS, call your Local  
Distributor or the Help Desk at one of the following telephone numbers  
and ask for a UPS technical representative.  
United States:  
Canada:  
1-800-843-9433 or 1-919-870-3028  
1-800-461-9166 ext 260  
All other countries:  
Call your local service representative  
Please have the following information ready when you call for service:  
S Model number  
S Serial number  
S Firmware version number  
S Date of failure or problem  
S Symptoms of failure or problem  
S Customer return address and contact information  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLESHOOTING  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chapter 13 Limited Warranty  
WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Power Quality Corporation, a  
Delaware Corporation (“Eaton”).  
LIMITED WARRANTY: This limited warranty (this “Warranty”) applies only to the original end-user (the “End-User”)  
of the Powerware 3 Phase UPS Products (the “Product”) and cannot be transferred. This Warranty applies even in  
the event that the Product is initially sold by Eaton for resale to an End-User.  
LIMITED WARRANTY PERIOD: The period covered by this Warranty for Product installed [and currently located] in  
the fifty (50) United States and the District of Columbia is twelve (12) months from the date of Product start-up or  
eighteen (18) months from date of Product shipment, whichever occurs first. The period covered by this Warranty  
for Product installed [and currently located] outside of the fifty (50) United States and the District of Columbia is  
twelve (12) months from the date of Product start-up or eighteen (18) months from date of Product shipment,  
whichever occurs first.  
WHAT THIS LIMITED WARRANTY COVERS: The warrantor warrants that the Powerware three-phase UPS  
electronics, Eaton-built accessories, and Powerware-built battery cabinets, (individually and collectively, the  
“Warranted Items”) are free from defects in material and workmanship. If, in the opinion of Eaton, a Warranted  
Item is defective and the defect is within the terms of this Warranty, Eaton’s sole obligation will be to repair or  
replace such defective item (including by providing service, parts and labor, as applicable), at the option of Eaton.  
The Warranted Item will be repaired or replaced onsite at the End-User’s location or such other location as  
determined by Eaton. Any parts that are replaced may be new or reconditioned. All parts replaced by Eaton shall  
become the property of Eaton.  
WHAT THIS LIMITED WARRANTY DOES NOT COVER: This Warranty does not cover any defects or damages  
caused by: (a) failure to properly store the Product before installation, including the “trickle charge” of batteries no  
later than the date indicated on the packaging; (b) shipping and delivery of the Product if shipping is FOB Factory; (c)  
neglect, accident, abuse, misuse, misapplication, incorrect installation; (d) repair or alteration, not authorized in  
writing by Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent; or (e)  
improper testing, operation, maintenance, adjustment, or any modification of any kind not authorized in writing by  
Eaton personnel or performed by an authorized Eaton Customer Service Engineer or Agent.  
This Warranty is not valid: (a) unless an authorized Eaton Customer Service Engineer (in USA) or Agent (outside of  
USA) performs start-up and commissioning of the Product; (b) if the Product is moved to a new location by  
someone other than an authorized Eaton Customer Service Engineer (in USA) or Agent (outside of USA); or (c) if the  
Product’s serial numbers have been removed or are illegible. Any Warranted Items repaired or replaced pursuant to  
this Warranty will be warranted for the remaining portion of the original Warranty subject to all the terms thereof.  
Labor warranty is not provided for Product located outside of the fifty (50) United States or the District of Columbia.  
Any equipment, parts or materials included in the Product and not manufactured by Eaton are warranted solely by  
the manufacturer of such equipment, parts or materials and are not included as part of this warranty. Batteries  
are not warranted by Eaton.  
THIS WARRANTY IS THE END-USER’S SOLE REMEDY AND IS EXPRESSLY IN LIEU OF, AND THERE ARE NO OTHER,  
EXPRESSED OR IMPLIED GUARANTEES OR WARRANTIES (INCLUDING ANY IMPLIED WARRANTY OF  
MERCHANTABILITY OR FITNESS FOR ANY PURPOSE, WHICH ARE EXPRESSLY DISCLAIMED).  
LIMITATION OF LIABILITY: In no event shall Eaton be liable for any indirect, incidental, special or consequential  
damages of any kind or type whatsoever, or based on any claim or cause of action, however denominated. Eaton  
shall not be responsible for failure to provide service or parts due to causes beyond Eaton’s reasonable control. In  
no case will Eaton’s liability under this Warranty exceed the replacement value of the Warranted Items.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED WARRANTY  
END-USER’S OBLIGATIONS: In order to receive the benefits of this Warranty, the End-User must use the Product  
in a normal way; follow the Product’s operators and maintenance manual; and protect against further damage to the  
Product if there is a covered defect.  
OTHER LIMITATIONS: Eaton’s obligations under this Warranty are expressly conditioned upon receipt by Eaton of  
all payments due to it (including interest charges, if any). During such time as Eaton has not received payment of  
any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton  
shall have no obligation under this Warranty. Also during such time, the period of this Warranty shall continue to run  
and the expiration of this Warranty shall not be extended upon payment of any overdue or unpaid amounts.  
COSTS NOT RELATED TO WARRANTY: The End-User shall be invoiced for, and shall pay for, all services not  
expressly provided for by the terms of this Warranty, including without limitation, site calls involving an inspection  
that determines no corrective maintenance is required. Any costs for replacement equipment, installation,  
materials, freight charges, travel expenses or labor of Eaton representatives outside the terms of this Warranty will  
be borne by the End-User.  
OBTAINING WARRANTY SERVICE: In the USA, call the Eaton Customer Reliability Center 7x24 at 800-843-9433.  
Outside of the USA, call your local Eaton sales or service representative, or call the Eaton Customer Reliability  
Center in the USA at 919-870-3028. For comment or questions about this Limited Factory Warranty, write to the  
Customer Quality Representative, 3301 Spring Forest Road, Raleigh, North Carolina 27616 USA.  
EATON Powerware® 9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev B www.powerware.com  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Peavey Musical Instrument Amplifier Special 150 User Manual
Pelco Security Camera TW3001P User Manual
Pitco Frialator Fryer 35C+ User Manual
Planar Car Video System PLL1900W User Manual
Planet Technology Network Card NAS 7201 User Manual
Planet Technology Network Router WAP 4000 User Manual
PLUS Vision Projector V 1100Z User Manual
Porter Cable Air Compressor CLFRP350 User Manual
Poulan Trimmer RTE113 User Manual
ProForm Home Gym PFSY29250 User Manual