Klinkmann Automation Omron Ethernet DAServer  
1
Before You Begin  
About This User Guide  
This user’s guide describes the user interface and functions of the KLINKMANN OMRON  
Ethernet Direct DAServer. It also provides you with the step-by-step procedures on how  
to configure and use the OMRON Ethernet Direct DAServer after it is installed.  
The OMRON Ethernet Direct DAServer user’s guide is organized in the following fashion:  
• Contents  
• Introduction: contains overview information about the OMRON Ethernet Direct  
DAServer and the environment in which it works.  
• Configuration: contains a detailed description of the user interface elements of this  
DAServer in addition to its functionality.  
• Item Names: describes the item naming conventions for targeted devices.  
• Troubleshooting: provides information about error messages, codes, and conditions  
displayed by the OMRON Ethernet Direct DAServer.  
• Reference: describes the DAServer architecture in general.  
• Index  
You can view this document on-line or you can print it, in part or whole, by using the  
Adobe Acrobat Reader’s print facility.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
2
CHAPTER 1  
Introduction  
This chapter provides you with an overview of the KLINKMANN OMRON Ethernet Direct  
DAServer, including the application- and bus-level communications protocols, item  
naming conventions and DAServer features.  
Contents  
Overview  
Communications Protocols  
Accessing Items via the DAServer  
Features  
Demo Mode  
Network Environment and Conditions  
Overview  
The KLINKMANN OMRON Ethernet Direct DAServer (hereafter referred to as the  
“OMRON Ethernet DAServer” or “DAServer” or “DASOmronEth” throughout the  
remainder of this user’s guide) is a Microsoft ® Windows ® application program that acts  
as a FINS message communications protocol server. It allows other Windows application  
programs access to data from OMRON PLCs (also referred to as devices) over the  
OMRON Ethernet FA (Factory Automation) network.  
The OMRON Ethernet Direct DAServer requires an Ethernet card and TCP/IP protocol  
installed on the computer to communicate with the Ethernet network. The OMRON  
Ethernet Direct DAServer can access to data from Controllers connected to the Ethernet  
System directly (with Ethernet Unit installed) or from Controllers interconnected to  
Ethernet System through SYSMAC LINK network or any other OMRON FA network  
(through PC Gateway - an OMRON Controller which has multiple Communications Units  
mounted, including the Ethernet Unit, and therefore that belongs to two networks and can  
thus function as an interface between them). The OMRON Ethernet Direct DAServer  
supports the Controller Memory Areas accessible by FINS commands.  
No additions to Controller’s user program are needed if OMRON Ethernet Direct  
DAServer is used in a poll (normal) mode, i.e. the DAServer sends read or write FINS  
command to Controller and Controller responds with corresponding response. The  
OMRON Ethernet Direct DAServer supports also the possibility to receive “unsolicited”  
data from Controller – in this case some additions in Controller program are needed. The  
DAServer “slave” mode can be established – at communication start-up DAServer  
requests data one time and after it - only unsolicited data can be received from Controller.  
At same time the writing of new values to Controller is still possible.  
The OMRON Ethernet Direct DAServer can access to data from CS1/CJ1, CV-series and  
C200HX/C200HG/C200HE PLCs (directly from Ethernet network or inter-networked from  
other OMRON FA networks) as well as from C-series and CQM1 PLCs (only inter-  
networked from other OMRON FA networks).  
While the OMRON Ethernet Direct DAServer is primarily intended for use with  
Wonderware InTouch ® (Version 7.11 Patch 02 and later), it may be used by any  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
3
Microsoft Windows program capable of acting as a DDE, SuiteLink ™ or OPC client that  
can also coexist with FactorySuite ™ 2000 and greater.  
Communication Protocols  
The OMRON Ethernet Direct DAServer communicates with clients and PLCs using the  
following different communications protocols:  
Application communications protocols such as OPC, DDE and SuiteLink to  
communicate with clients located on either local or remote nodes.  
FINS message communications protocol to communicate with the Omron controllers  
over FA (Factory Automation) networks.  
Important! This DAServer is compliant with the OPC Data Access (DA) 2.05  
specification.  
For more information about the DAServer architecture, see the Reference section.  
Application Communications Protocols  
The DAServer utilizes the following application communications protocols to  
communicate with the clients.  
OPC  
OPC (OLE for Process Control) is a non-proprietary set of standard interfaces based  
upon Microsoft’s OLE/COM technology. This standard makes possible interoperability  
between automation/control applications, field systems/devices and business/office  
applications.  
Avoiding the traditional requirement of software/application developers to write custom  
drivers to exchange data with field devices, OPC defines a common, high-performance  
interface that permits this work to be done once, and then easily reused by HMI, SCADA,  
control and custom applications. Over the network, OPC uses DCOM (Distributed COM)  
for remote communications.  
SuiteLink  
SuiteLink uses a TCP/IP-based protocol and is designed specifically to meet industrial  
needs such as data integrity, high throughput, and easier diagnostics. This TCP/IP  
standard is supported on Windows NT and Windows NT-technology-based operating  
systems (for example, Windows NT, Windows 2000, and Windows XP).  
SuiteLink is not a replacement for DDE, FastDDE, or NetDDE. The protocol used  
between a client and a server depends on your network connections and configurations.  
SuiteLink provides the following features:  
Value Time Quality (VTQ) places a time stamp and quality indicator on all data values  
delivered to VTQ-aware clients.  
Extensive diagnostics of the data throughput, server loading, computer resource  
consumption, and network transport are made accessible through the operating system’s  
performance monitor. This feature is critical for the operation and maintenance of  
distributed industrial networks.  
Consistent high data volumes can be maintained between applications regardless if the  
applications are on a single node or distributed over a large node count.  
The network transport protocol is TCP/IP using Microsoft’s standard WinSock interface.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
4
FastDDE  
FastDDE provides a means of packing many proprietary Wonderware Dynamic Data  
Exchange messages into a single Microsoft DDE message. This packing improves  
efficiency and performance by reducing the total number of DDE transactions required  
between a client and a server.  
Although Wonderware's FastDDE has extended the usefulness of DDE for our industry,  
this extension is being pushed to its performance constraints in distributed environments.  
DDE  
DDE is a communications protocol developed by Microsoft to allow applications in the  
Windows environment to send/receive data and instructions to/from each other. It  
implements a Client/Server relationship between two concurrently running applications.  
The server application provides the data and accepts requests from any other application  
interested in its data. Requesting applications are called clients. Some applications such  
as InTouch and Microsoft Excel can simultaneously be both a client and a server.  
NetDDE  
NetDDE is a communications protocol that extends the standard DDE functionality to  
include communications over local area networks and through serial ports. Network  
extensions are available to allow DDE links between applications running on different  
computers connected via networks or modems.  
For example, NetDDE supports DDE between applications running on IBM-compatible  
computers connected via LAN or modem, and DDE-aware applications running on non-  
IBM-compatible computers under operating environments such as VMS and UNIX.  
FINS Message Communication  
The FINS Messages system is developed by OMRON for its Factory Automation  
networks. FINS Communications allow PLCs on these networks to be controlled by  
reading and/or writing memory area data without the need to program these operations  
into the controller’s user program.  
Accessing Items via the DAServer  
The method for accessing items through the DAServer depends on the communications  
protocol being used.  
OPC  
In the case of OPC communications, the protocol addresses an element of data in a  
conversation with six characteristics: node name, program name, group name, device  
group, link name, and item name.  
The node name (required for remote access) and device group are optional.  
A fully qualified OPC Item name (ItemID) is composed of the link name and item name.  
All other characteristics are specified through separate DAServer means.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
5
To access an OPC item, the OPC client needs to connect to the DAServer (either in-  
process or out-of-process) and create an OPC group defining the data-acquisition  
properties for the collection of items to be added. OPC groups  
can be either public or private. Public OPC groups are shared across multiple clients,  
whereas private OPC groups are local to a single client. Optionally, a device group, which  
indicates the access path to the items for read/write, can  
be specified from the DAServer.  
The following briefly describes each characteristic of the OPC protocol:  
• node name: Computer (host) name identifying a specific node on the network (for  
Remote Access ONLY).  
• program name: The registered OPC server name uniquely identifying a specific server  
(ProgID). For this DAServer, the program name is ArchestrA.OmronEth.1.  
• group name: The OPC group created from the client for organizing a collection of items  
logically with the same data acquisition properties between the client and the server, such  
as update rate.  
• device group: Meaningful names configured in the DAServer under a specific controller  
for the common custom attributes between the DAServer and the device, such as update  
interval. If not specified from the client, the default device group using the global  
configuration attribute values from the DAServer is assumed. Functionally, a device group  
is equivalent to an access path (optional).  
• link name: The set of hierarchy node names, representing the specific devices on a  
communications path link from the hierarchy root to a specific controller as configured for  
this DAServer under the DAServer Manager, separated by delimiters.  
• item name: A specific data element, the leaf of the hierarchy tree of this DAServer,  
within the specified group. For example, when using this DAServer, an item can be a  
relay, timer, counter, register, and so on, in the controller.  
DDE/SuiteLink  
In the case of DDE/SuiteLink communications, the protocol addresses an element of data  
in a conversation that uses a four-part naming convention that includes the node name,  
application name, topic name, and item name. The fully qualified DDE/SuiteLink naming  
convention includes all four parts, although the node name part (required for remote  
access only) is optional. The following briefly describes each portion of this naming  
convention:  
• node name: Computer (host) name identifying a specific node on the network (for  
Remote Access ONLY).  
• application name: The name of the Windows program (this DAServer) that will be  
accessing the data element. In the case of data coming from or going to the Modicon  
devices via the DDE/SuiteLink PlugIn of this DAServer, the application name portion of  
the address is DASOmronEth.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
6
• topic name: Meaningful names are configured in the DAServer to identify specific  
devices. These names are then used as the topic names in all conversations with that  
device. For example, OmronPLC. Topic name maps to a device group defined in the  
DAServer.  
Note: You can define multiple device-group (topic) names for the same device (PLC) to  
poll different points at different rates.  
• item name: A specific data element within the specified topic. For example, when using  
this DAServer, an item can be a relay, timer, counter, register, and so on, in the PLC.  
Note: The term "point" is used interchangeably with the term "item" in this user's guide.  
For more information on item/point names, see the Item Names section of this user's  
guide.  
Features  
The KLINKMANN OMRON Ethernet Direct DAServer provides the following features:  
The ability to communicate over multiple application-level protocols at the same time.  
The ability to add new application-level protocols on the fly.  
The ability to be configured remotely.  
New, robust diagnostic abilities.  
For more in-depth information on the DAServer architecture, see the Reference section.  
Demo Mode  
Demo Mode allows you to test the functionality of the OMRON Ethernet Direct DAServer  
(with all features enabled) for 60 minutes. After that time, you must install HASP key.  
The HASP key is needed for full time running of OMRON Ethernet Direct DAServer. The  
HASP Driver setup is performed during the DAServer setup. Without HASP Driver  
installed the OMRON Ethernet Direct DAServer will run supporting all features only 60  
minutes after which the server stops updating read/write on all device items and reject the  
addition of any new items.  
Clients continue to function normally (for example, you can still add or remove an item,  
but its value is not updated).  
Note: The $SYS$Licensed system item value with OMRON Ethernet Direct DAServer is  
not relevant.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
7
CHAPTER 2  
Before starting the OMRON Ethernet DAServer  
This chapter contains instructions how to configure OMRON PLCs to be accessible by  
Omron Ethernet DAServer in OMRON Ethernet FA network.  
Configuration example deals with local network. If data are to be accessed from remote  
networks then Relay Network Tables must be additionally configured in the PLC.  
Contents  
Preparing the Hardware to be Used with Omron Ethernet DAServer  
Ethernet Unit Configuration Example for CS1 PLC  
Example program for sending “unsolicited” data from PLC  
Preparing the Hardware to be used with OMRON Ethernet  
DAServer  
The Omron Ethernet DAServer requires an Ethernet card and TCP/IP protocol supporting  
Windows Sockets interface to be installed on the computer to communicate with the  
OMRON PLCs over the Ethernet network.  
Each connected OMRON Controller (with Ethernet Unit installed) must be configured to  
allow it to function as a node on the Ethernet network. This setup can be done by  
switches on the module and/or appropriate programming software.  
The OMRON C200HX/C200HG/C200HE PLCs (except CPU11), CV-series PLCs, CS1  
PLCs as well as CJ1 PLCs can be used as nodes on Ethernet network. The  
C200HX/C200HG/C200HE PLCs must be supplied with communication module:  
C200HW-PCS01-EV1 Ethernet Set or C200HW-PCU01 PC Card Unit supplied with the  
Ethernet PC Card (e.g. Kingston T.C. EtheRxEthernet PC Card models: KNE-PCM/M –  
for coaxial and twisted pair connection, KNE-PCM/T – for twisted pair connection).  
The CS1-series PLCs must be supplied with CS1W-ETN01 Ethernet Unit.  
The CJ1-series PLCs must be supplied with CJ1W-ETN11 Ethernet Unit.  
The CV-series PLCs must be supplied with CV500-ETN01 communication module.  
The Ethernet PC Card installed in the C200HW-PCU01 PC Card Unit in the  
C200HX/C200HG/C200HE PLC is configured by software supplied with communication  
hardware.  
Node number and Unit number of CV500-ETN01 (in CV-series PLC) is set by rotary  
switches on the module. Software (CVSS software, SYSWIN or CX-Programmer) is used  
to configure IP Address, Routing tables and IP Address tables.  
Node number and Unit number of CS1W-ETN01 Ethernet Unit (in CS1-series PLC) is set  
by rotary switches on the front side of module. Local IP Address is set by switches SW1,  
SW2, ..., SW8 on the back side of module. Software (CX-Programmer) is used to  
configure Routing tables and IP Address tables.  
Node number and Unit number of CJ1W-ETN11 Ethernet Unit (in CJ1-series PLC) is set  
by rotary switches on the front side of module. Software (CX-Programmer) is used to  
configure Routing tables, local IP Address and IP Address tables.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
8
Configuration software tool, appropriate (and recommended) for all OMRON controllers is  
OMRON CX-Programmer Windows Programing Software (see “OMRON CX-Programmer  
Users Manual”) .  
Ethernet Unit Configuration Example for CS1 PLC  
Connect the computer to the PLC CPU unit with Host Link Cable. Install the CX-  
Programmer software.  
Set IP Address table. Start CX-Programmer (from Start menu: Start/.../CX-  
Programmer/CX-Programmer). Create new project (option "New" in CX-Programmer's  
system menu). The "Change PLC" dialog box appears.  
Enter PLC's name in the project (e.g. default name NewPLC1), PLC's model (e.g. CS1G)  
and set the communication type used to access the configured PLC (SYSMAC WAY - for  
serial communication).  
Press "Work Online" pushbutton (or Ctrl+W) to establish communication to the PLC. (The  
same can be done the following: in treeview (on CX-Programmer main window) select the  
PLC (in example "NewPLC1(CS1G) Offline") and click the mouse right button. The PLC's  
menu appears. Click "Work Online".)  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
9
When CX-Programmer establishes communication with PLC, select "Operating Mode"  
(from PLC's menu) and set "Program" mode.  
Note:  
If you do not know (or have forgotten) the communication settings currently configured in  
the PLC, the Auto Online feature can be useful – from CX-Programmer’s main menu  
select “PLC/Auto Online/Auto Online” and CX-Programmer will search for all possible  
settings until the proper ones are found; after that the current PLC program will be  
automatically uploaded to CX-Programmer and it will go to online state with operating  
mode set "Program" mode.  
Double-click on "IO Table" in treeview. The "PLC IO Table - NewPLC1" dialog box  
appears. Select "Options" and click "Transfer from the PLC":  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
10  
When IO Table is received, display the slot list under Main Rack (press "+" button in the  
"PLC IO Table - NewPLC1" dialog box). Select "Ethernet Unit(ET)(0)" and press the  
mouse right button. The Ethernet Unit menu appears:  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
11  
Click "Unit Setup". The "Ethernet Unit CPU Bus Unit" dialog box appears:  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
12  
Enter Address Conversion type, FINS UDP port number and Sub-net Mask.  
Edit the IP Address Table: the computer where Omron Ethernet DAServer is running  
must be added to the IP Address Table. To add it, press "Insert" button. The "Insert  
Router's IP Address" dialog box appears:  
Enter the Node Number (in example 55) matching to the last octet in IP Address of  
computer where Omron Ethernet DAServer is running. Enter the IP Address of computer  
where Omron Ethernet DAServer is running (in example 195.2.103.55). Press "Ok".  
Insert the Node Number and IP Address of PLC. (In case of CS1-series PLCs the Node  
Number must match with settings on the rotary switch on the front side of Ethernet  
communication unit, IP Address – must match with settings of rotary switches on the back  
side of Ethernet communication unit).  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
13  
To complete the configuration: from the "Ethernet Unit CPU Bus Unit" (or from the "PLC  
IO Table - NewPLC1") dialog box select "Options" and click "Transfer to PLC".  
Example program for sending “unsolicited” data from PLC  
The PLC example program presented in Plcprg.cxp project incorporates the SEND(090)  
instruction for transferring unsolicited data from PLC to the OMRON ETHERNET  
DAServer (for programming details see SYSMAC CS1 Series CS1W-ETN01 Ethernet  
Unit OPERATION MANUAL, section 5).  
The program transfers 10 words of data from D10 (notation in ladder diagram - D00010)  
from the PLC to the OMRON ETHERNET Server (into address D500). The computer  
where Omron Ethernet DAServer is running has the IP Address: 195.2.103.55 and the  
destination node number is assigned to 55 (37 in hex).  
Comments on example program ladder diagram:  
(0) Periodically (once per second) the execution condition flag CIO 000000 turns ON.  
Note: There can be different logic to turn ON execution condition flag in real  
application.  
(1) If the Communication Port Enabled Flag for port 7 is ON, the send execution program  
will start when the execution condition flag CIO 000000 turns ON. Input CIO 120000  
remains ON from the start of SEND execution until completion. Note: The CS1-series  
CPU Unit’s Communication Port Enabled Flags are allocated the following way - in Word  
A202: Bit 0 – is associated with Port 0, Bit 1 – is associated with Port 1, … , Bit 7 – is  
associated with Port 7. Bit’s status OFF - means execution enabled, ON – means  
execution disabled.  
(2) Control data (D0, D1, … D4) creation  
Word  
D0000  
D0001  
Contents  
00 0A  
00 00  
Meaning  
Number of send words = 10  
Destination network number = 0 (local  
network)  
D0002  
D0003  
37 00  
87 05  
Destination node number = 55 (37 hex)  
Destination unit address = 0  
Response not required  
Communication port No = 7  
Number of retries = 5  
D0004  
00 64  
Response monitor time = 10 s  
Ten words with data from D10 from PLC are sent to D500 onwards on the local network,  
node number 55, unit address 0 (the computer where Omron Ethernet DAServer is  
running) – to receive all these data the items with addresses D500…D509 can be  
correspondingly activated for Omron Ethernet DAServer.  
Important! With current example program an application will periodically toggle values of  
areas D500…D509 with values of areas D10…D19. This is because of DAServer time-  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
14  
by-time poll area D500…D509 and time-by-time gets unsolicited command assigning to  
items D500…D509 values of PLCs D10…D19 area. Even if corresponding Controller is  
configured to be processed in slave mode – at communication start-up DAServer process  
several general data reading commands, accessing toggle effect.  
If your application does not need toggling effect – configure SEND(090) instruction so,  
that source area matches to destination area. In example – source data must start at  
D500, if data are sent to D500 onwards.  
(3) Reset the Input creation.  
(4) Turn ON error information flag CIO 001300 if error happens. In this case CIO 001300  
is not mandatory; any other flag may be used. Note: The CS1-series CPU Unit’s  
Communication Port Error Flags are allocated the following - in Word A219: Bit 0 – is  
associated with Port 0, Bit 1 – is associated with Port 1, … , Bit 7 – is associated with  
Port 7. Bit’s status OFF - means Normal completion, ON – means Abnormal completion.  
(5) The end of example program.  
The example program ladder diagram is following:  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
15  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
16  
CHAPTER 3  
Configuration  
Once the KLINKMANN Omron Ethernet DAServer has been installed, a small amount of  
configuration is required. This configuration is performed using the DAServer Manager  
hosted in the System Management Console after it is started through the Programs  
menu of the Windows Start button.  
Before the DAServer is activated, the device hierarchy, simulating the physical hardware  
layout, must first be built to establish communications to each of the controllers. Once the  
Omron Ethernet hierarchy has been built, the respective devices for communications can  
be configured. Finally, the desired Device Groups for each controller may be created.  
Note: To run the Omron Ethernet DAServer as a service, use the context menu on the  
DAServer name and select “Configure As Service”. You can configure it as an auto  
service or manual service. For more information about configuring your DAServer as a  
service, see the “Activation/Deactivation/Service Component” of the DAServer Manager  
documentation.  
Contents  
Getting Started Quickly with the DAServer  
Configuring the DAServer  
Configuring Device Group Definitions  
Configuring Device Item Definitions  
Hot Configuration  
Getting Started Quickly with the DAServer  
This section briefly describes the procedures required to prepare the Omron Ethernet  
DAServer for use. Detailed descriptions of each step can be found in later sections of this  
documentation. This section is intended for people who are familiar with DAServers.  
Note: If you are not familiar with DAServer functionality, please proceed to the more-  
detailed procedures following this section.  
The following procedures assume that you have:  
Configured the PLC with which you wish to communicate.  
To prepare the Omron Ethernet DAServer  
1. Install the KLINKMANN Omron Ethernet DAServer on Windows by running the  
Setup.exe program.  
Note: DAServer installation instructions are included in a separate Help file (.chm  
extension).  
Accept all the default settings during the installation.  
Important! Since there are no default values for security settings, you must take note of  
the user name and password selected during the install.  
2. Start the Wonderware DAServer Manager by selecting the Programs menu from the  
Start button on the taskbar.  
3. Navigate to the Wonderware folder that contains the System Management Console,  
then click System Management Console.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
17  
4. From the System Management Console, find the Omron Ethernet DAServer in the  
DAServer Manager tree, the location in which it is installed.  
Under the Local branch node, the name of the DAServer is  
Archestra.DASOmronEth.1.  
See the DAServer Manager documentation for general information about working in this  
snap-in environment.  
5. The new Omron Ethernet DAServer must now be configured.  
Before proceeding, determine the hierarchical structure of the network/PLC environment  
to which you plan to connect.  
6. Right-click the Configuration object that already exists in the tree, and select Add  
SOCKET Object from the shortcut menu.  
A new SOCKET object is created as a node in the hierarchy tree and is named  
New_SOCKET_000 by default.  
In this step, in addition to Step 7, the hierarchy entry is added in "edit mode," providing a  
convenient place for you to appropriately describe components of your specific hardware  
environment.  
If you do not rename the object at this time, a numeric sequencing system is applied.  
Any hierarchy entry can be renamed at a later time.  
7. Right-click on the new SOCKET object, and from the shortcut menu, select  
Add CONTROLLER Object  
8. Configure the respective device objects, created in the preceding steps, with the  
appropriate parameter values, if applicable.  
Optionally, the desired device groups can be created under the Device Groups tabbed  
page with each of the Controller objects.  
Desired device items can also be optionally created under the Device Items tabbed  
page with each of the Controller objects.  
Note: The hierarchy entry is added in the "edit mode," providing a convenient place for  
you to appropriately describe components of your specific hardware environment. Both  
hierarchy node name and device group name are numerically sequenced by default.  
They can be renamed at any time.  
The DAServer is now ready for use. In order to use the DAServer, you must activate it  
from the DAServer Manager using either the shortcut menu’s Activate Server command  
from the Archestra.DASOmronEth.1 node, or from OPC Client.  
Note: To run the Omron Ethernet DAServer as a service, right-click on the DAServer  
name and select Configure As Service from the shortcut menu. You can configure it as  
an auto service or manual service. For more information about configuring your DAServer  
as a service, see the Activation/Deactivation/Service Component of the DAServer  
Manager documentation.  
Configuring the DAServer  
Note: This DAServer is hosted by DAServer Manager, a Microsoft Management Console  
(MMC) snap-in, which is a part of the ArchestrA System Management Console (SMC)  
suite of utilities. Many high-level functions and user-interface elements of the DAServer  
Manager are universal to all DAServers, and only the documentation for the DAServer  
Manager contains descriptions of those universal functions/UI elements. Therefore,  
reading the documentation for both the MMC and the DAServer Manager is critical to  
understanding this user’s guide. To read the documentation about the MMC and  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
18  
DAServer Manager, click the Help topics on the SMC Help menu. Both the MMC Help  
and the DAServer Manager Help are displayed. An Adobe Acrobat version of the  
DAServer Manager documentation (DAServerManager.pdf) is also available in the CD-  
ROM directory\User Docs\English.  
Note: For better understand how to read and write data to the different OMRON  
controllers, please refer to the chapter Before starting the Omron Ethernet DAServer.  
Note: The shortcut menu items described in this document typically represent only a  
subset of any actual shortcut menu. Most items in each shortcut menu are standard  
Windows commands. For more information about those commands, please see Help, by  
right-clicking the System Management Console icon.  
To prepare the Omron Ethernet DAServer  
1. Install the KLINKMANN Omron Ethernet DAServer on Windows by running the  
Setup.exe program.  
Note: DAServer installation instructions are included in a separate Help file (.chm  
extension).  
2. Accept all the default settings during the installation.  
Important! Since there are no default values for security settings, you must take note of  
the user name and password selected during the install.  
3. After the DAServer has been installed, start the System Manager Console by clicking  
the Start button on the Windows taskbar and pointing to Programs.  
4. Point to the Wonderware folder that contains the System Management Console, then  
click System Management Console.  
5. From the System Management Console tree, click on DAServer Manager.  
6. Click on Default Group, then the Local node.  
Under the Local node, the DAServer name is ArchestrA.DASOmronEth.1  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
19  
Note: See the DAServer Manager documentation for general information about working  
in this snap-in environment.  
7. Before the DAServer is started, you must first build the device hierarchy to establish  
communications to each of the controllers.  
Important! For step-by-step procedures on how to build the device hierarchy, please see  
the following section, "DASOmronEth Hierarchy in the DAServer Manager."  
Note: Selecting the Configuration object of the hierarchy tree displays the Global  
Parameters configuration view for this DAServer. The default Poke Mode settings for the  
DAServer is Optimization mode. Configuration of all other global parameters as required  
for this DAServer. For more information about the Global Parameters dialog box,  
including descriptions of the different Poke Modes, see the DAServer Manager  
documentation. You can access that documentation by clicking the DAServer Manager  
icon and selecting the Help topics on the Help menu, and then navigating through the  
DAServer Manager book.  
Important! Any Global Parameters that appear dimmed are either not supported or  
cannot be configured for this DAServer. Simulation Mode is not supported.  
8. When the DASOmronEth hierarchy build has been completed, you can start  
configuring the respective devices for communications.  
9. You may create the desired Device Groups for each controller by:  
Navigating to the object of interest in the DAServer Manager tree view.  
Clicking on the Device Groups tab.  
Right-clicking in the Device Groups dialog box and selecting the Add command from  
the shortcut menu.  
Important! For step-by-step procedures on configuring Device Groups, please see the  
following section, "Configuring Device Group Definitions."  
10. Finally, you may create the desired Device Items for each controller by:  
Navigating to the object of interest in the DAServer Manager tree view.  
Clicking on the Device Items tab.  
Right-clicking in the Device Items dialog box and selecting the Add command from the  
shortcut menu.  
Important! For step-by-step procedures on configuring Device Items, please see the  
following section, "Configuring Device Item Definitions."  
Note: When any configuration view is in an open state and you open the same server the  
second time, the DAServer locks the second instance of this same-server access for any  
update or configuration activities. Access to this second opening instance will resume  
after the first one has been closed.  
The DAServer is now ready for use. In order to use the DAServer, you must activate it.  
If you are using an OPC Client, the DAServer can be auto-started.  
If you are using DDE/SuiteLink, you must start the DAServer either as a manual or  
automatic service.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
20  
To activate the DAServer, right-click on ArchestrA.DASOmronEth.1 and select  
Activate Server from the shortcut menu.  
Note: To run the Omron Ethernet DAServer as a service, right-click on the DAServer  
name and select Configure As Service from the shortcut menu. You can configure it as  
an auto service or manual service. For more information about configuring your DAServer  
as a service, see the Activation/Deactivation/Service Component of the DAServer  
Manager documentation.  
DASOmronEth Hierarchy in the DAServer Manager  
Note: Before attempting to configure your DAServer, you should determine the  
hierarchical structure of your network/PLC environment.  
The server-specific configuration portion of the DASOmronEth hierarchy tree under the  
DAServer Manager starts at the SOCKET object.  
1. Configure the SOCKET object from the Configuration branch of the hierarchy after  
the DAServer has been installed.  
2. Rename this object as appropriate.  
Important! If you subsequently clear your configuration hierarchy, you must create this  
SOCKET object from the Configuration branch of the hierarchy. From this point, all of  
the following instructions apply.  
To create SOCKET objects from the Configuration branch  
1. Right-click on Configuration.  
2. Select Add SOCKET Object from the shortcut menu.  
A new SOCKET object is created as a node in the hierarchy tree, and it is named  
New_SOCKET_000 by default.  
3. Rename the newly created object as appropriate, for example, “Socket1”.  
The Socket1 configuration view (right pane) is displayed.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
21  
Enter/modify SOCKET parameters.  
Host Name (IP Addr.)  
Enter the Computer’s Internet Address (IP Address) if it has more than one. If there is  
only one Internet Address for computer then you can use default address 0.0.0.0.  
Port Number  
Enter the UDP Port Number used for communication with OMRON Controllers. The Port  
Number must match with Port Number configured in connected OMRON Controllers!  
(OMRON Controllers send responses to Port number, configured in PLC, even if request  
is received from different Port).  
Note: The default port number is 9600.  
From the SOCKET branch of the DAServer hierarchy, the CONTROLLER objects can be  
created. CONTROLLER represents the logical endpoint to the hardware hierarchy.  
To add CONTROLLER to your Omron Ethernet hierarchy  
1. Right-click on the SOCKET branch.  
2. Select Add CONTROLLER Object from the shortcut menu. It is named  
“New_Controller_000” by default.  
3. Rename it as appropriate, e.g. to “CS1” as used in following explanation – this new  
CONTROLLER object name now will be used in the name of “Parameters” configuration  
view.  
The “Parameters” configuration view is displayed:  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
22  
This configuration view has 15 parameters (configuration requires proven network  
information, it can not be validated by the DAServer):  
Enter Controller’s Network Address - to each network in the OMRON system  
can be assigned an unique network address between 0 and 127. When  
communicating with a node on another (remote) network, the entered value must  
be consistent with the network address (non-zero) assigned in the routing tables.  
The network address of 0 indicates the local network. Note: The default Network  
Address is 0.  
Enter Controller’s Node Address - each OMRON Controller in Ethernet network  
must have its own unique node address between 1 and 126 (if Controller is inter-  
networked via other OMRON FA network then Node Address can have different  
range. For example, if inter-networked via SYSMAC LINK network, the Node  
Address range is between 1 and 62. Care should be taken to select a node  
address that will not conflict with other devices in the system.  
Note: If destination node is OMRON PLC with Ethernet Unit installed then Controller  
Node Address must be configured according to following rules:  
- if automatic conversion of Ethernet Unit’s IP address is used (also the node number  
setting rotary switch on the front panel of the Ethernet Unit is used) then Controller  
Node Address must be equal with the fourth byte (octet) of local IP address of  
Ethernet Unit;  
- if automatic conversion of Ethernet Unit’s IP address is not used (IP Address Table  
is used) then Controller Node Address must be equal with the Node number  
configured in the Ethernet Unit’s IP Address Table.  
Enter Controller’s IP Address. The Controller’s IP Address must match with IP  
address configured at corresponding controller Ethernet Unit system setup.  
Enter Controller’s Port Number. Enter the UDP Port Number used for  
communications with this OMRON controller. The Port Number must much with the  
Port Number set in the OMRON controller by appropriate Ethernet Unit  
configuration software. Note: The default port number is 9600.  
Enter Computer’s Network Address - the Local Network Address: the unique  
network address between 1 and 127 is assigned to each OMRON Ethernet  
network in the system. The entered value must be consistent with the network  
address assigned in the routing tables. When communicate only with nodes in the  
local network, you can set this Address to zero (default value).  
Select the Controller Series. The available series are: CS1/CJ1, C200HX/HG/HE,  
CV-series, C/CPM2X and CQM1. To select Controller Series, click on the combo  
box button and make your choice from the list. Note: Only PLCs of CS1/CJ1,  
C200HX/HG/HE and CV series are directly accessible in Ethernet network. All  
other series PLCs must be inter-networked to get data from them.  
Select Controller type. To select Controller type, click on the combo box button  
and make your choice from the list. The available types depends on selection in  
Controller Series combo box: CS1/CJ1 series offers 2 options (CS1 and CJ1),  
C200HX/HG/HE series offers one option (C200HX/HG/HE), CV-series offers 5  
options (CV500, CVM1-CPU01-E, CV1000, CV2000 and CVM1-CPU11-E),  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
23  
C/CPM2x series offers 5 options (C200HS, C200H, C1000H, C2000H, CPM2x)  
and CQM1 series offers 1 option (CQM1).  
Enter Reply Timeout field - the amount of time (in seconds) the PLC will be given  
to reply to commands from the DAServer. Note: The default value of 3 seconds  
should be sufficient for most configurations.  
Enter the value of the Access Delay (in milliseconds). This is a delay what Server  
will make in communication with the selected PLC after each read or write  
command execution. The default value of Access Delay is 0 (zero). Enter non-  
zero value in the Access Delay field only if you consider, that selected PLC is not  
fast enough to correctly react to the Server's frequently sent requests.  
The main timing problems for PLC can cause the writing of separate Bit status into  
Word areas (for C200HX/C200HG/C200HE and CQM1 PLCs - into IR, LR, HR,  
AR, DM and EM areas; for CV-series PLCs - into CIO, G, A, D, E, EA…EH areas;  
for C/CPM2x PLCs - into IR, LR, HR, AR and DM areas; for CS1/CJ1 PLCs - into  
CIO, W, H, A, D, and E areas; (see Item Names section). Writing of the Bit status  
into Word area is performed by executing the following sequential steps:  
- reading of corresponding Word value from PLC memory,  
- setting a Bit to be written into the Word value,  
- writing the changed Word value into PLC memory.  
If Access Delay is 0 milliseconds, then Server tries to execute all steps as fast as  
Omron network can do it (with no pauses between processing steps). It can put the  
selected PLC into hard timing conditions.  
If unsuccessful Bit writing happens time by time (you can recognize it by  
investigating error logging in ArchestrA Log Viewer utility, after checking  
DASProtFail flag in Log Flag Editor utility) - then the possible reason of fault may  
be the hard timing conditions in the accessed PLC. In this case the setting non-  
zero value for Access Delay can make communication processing more reliable.  
Note: By setting the PLC Access Delay to non-zero value you can seriously reduce the  
real data update rate for selected PLC.  
Enter the values of FINS Message Maximum Size for read and write commands.  
Any value from 16 to prompted maximum number of bytes is valid if PLC is  
accessed directly in local Ethernet network. If PLC is not accessed directly within  
local network (the network common to the PC and PLC), but inter-networked from  
other network then the maximum amount of data is limited by any network the data  
passes through, i.e. the network with the smallest capacity will determine the limit.  
The following is a maximum capacity of OMRON FA networks: Ethernet, Controller  
Link and Sysmac Net - 1986 bytes; Sysmac Link and Serial networks – 512 bytes.  
The greater value is configured the faster data update rate can be achieved.  
Therefore reduce the FINS Message Maximum Size value only if selected PLC  
has timing problems to process great amount of data in a short time period. The  
default value is 1986 bytes.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
24  
Check or uncheck the Slave Mode check box to select the principles how to obtain  
data from corresponding controller. If Slave Mode is not checked (Master mode) –  
DAServer polls data from controller all the time. In Slave Mode (if checked) -  
DAServer requests data from Controller only once – at communication start-up -  
and then only waits for unsolicited messages from controller (writing to controller is  
still supported). Communication status is considered as good even if there is no  
unsolicited data received. To get more reliable communication status in Slave  
Mode – activate the Watchdog message processing (details see later in this  
chapter) or time-by-time write values to PLC. With Watchdog activated –  
Controller’s communication status depends on success of Watchdog messages.  
Default processing mode is Master mode.  
Enter the necessary setting in Gateway Count (GCT) field (the default setting is  
2). GCT setting specifies the number of allowed bridge passes in FINS commands  
sent to PLC; for example, GCT=7 is needed to support new CS/CJ-series CPU  
Units with Unit Ver. 2.0 or higher.  
If necessary – configure Watchdog. The Watchdog would be useful in case the  
PLC internal program needs to check, whether there is communication with  
computer where Omron Ethernet DAServer is runnung or not. With Watchdog  
activated, DAServer time-by-time writes some predefined value (e.g. 255) into  
predefined address in PLC’s memory (e.g. into D100). At the same time the PLC  
program must periodically check the current value in this memory address. If value  
is equal to Watchdog’s predefined value, then PLC’s program considers  
communication Status as Good and resets the check address to different (non-  
predefined) value, e.g. to 0. (It will allow to program to check communication state  
the next time.) If value differs from predefined, then PLC’s program considers  
communication Status as Bad.  
Note: Because of time synchronizing problems with PLC and PC it is recommended to  
consider the communication Status as Bad only after few consecutive test value  
mismatch cases, not immediately after the first mismatch.  
To activate the Watchdog processing - set Watchdog Time Interval to non-zero value.  
Value entered in this field indicates the frequency (in seconds) the DAServer sends  
Watchdog message to corresponding PLC. This value must be a bit less as time interval  
the PLC program checks the value in watchdog address in the PLC.  
Enter Address to Write field to indicate the watchdog address in PLCs memory that is  
used as Watchdog check address. Address to Write must be a valid item/point name  
(see Item Names section.)  
Note: Use only Word memory areas for Watchdog. Do not take addresses not presented  
on current PLC configuration. Do not take addresses, used as PLC system areas  
or in PLC’s program logic. Do not use specific areas, such as Step Area Present  
Values in CV-series PLCs, or IR or DR areas in CS1-series. If DAServer does not  
accept memory area for Watchdog – you will see error logging in ArchestrA  
System Management Console’s Log Viewer.  
Enter integer from 0 to 65535 into Value to Write field to set Watchdog predefined value.  
The same value PLC program expects to see in Watchdog check address.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
25  
Note: Default Watchdog state is “non-active”, i.e. Watchdog Time Interval is equal to  
zero.  
Note: In order to use the DAServer, you must activate it. See the DAServer  
Manager documentation for information about how to activate and deactivate  
the DAServer.  
Configuring Device Group Definitions  
The Device Groups tab in the DAServer Manager user interface is used to create a new  
device group or modify or delete existing device group definitions for an object. For  
DDE/SuiteLink communications, one or more device group definitions must exist for each  
PLC that the DAServer will communicate with.  
Each device group (topic) definition should contain a unique name for the PLC associated  
with it.  
Device Group Definitions  
The Device Groups dialog box, which is displayed by clicking the Device Groups tab in  
the Parameters configuration view, is used to perform the following activities:  
Adding, defining, and deleting device groups.  
Note: When you add a new device group, enter a unique name.  
Configuring default update intervals.  
Editing update intervals for the objects.  
Note: When you select another part of the DAServer tree hierarchy, you are prompted to  
save the modifications to the configuration set.  
To create or add device groups  
1. To create or add device groups, right-click in the Device Groups box.  
2. Select the Add command from the shortcut menu.  
When you add a new device group, enter a unique name.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
26  
To make edits on device groups  
Make edits on a device group name or update interval for an object as follows:  
In the Name column, double-click or press F2 on the device group’s name to be edited  
and make the edit.  
Double-click on the device group’s value to be edited in the Update Interval column,  
and make the edit.  
To configure additional Device groups parameters right-click device group name and  
select Edit from the shortcut menu. The Device Group Parameters dialog box will appear:  
The Device Group parameters dialog can be used to configure preferred Read mode and  
Write optimization mode.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
27  
If Memory Area Read is checked (default setting), then Server uses Memory Area Read  
FINS commands and maximum (Read FINS Message Maximum Size – 14) / 2  
consecutive words can be read from this Controller by one read command.  
If Multiple Memory Area Read is checked then Server uses Multiple Memory Area Read  
FINS commands and maximum 128 non-consecutive words (also from different memory  
areas) can be read from this PLC by one read command.  
Note: Even if Multiple Memory Area Read is configured - several memory areas are still  
accessed by general read commands.  
If Single Write option is checked, then for each new write value a separate write  
message is created. The values in the PLC are changed by the DAServer in the same  
sequence as they are changed in the user (client) application. With this option the data  
update rate is low if application changes values very frequently, but sequence of value  
changes are guaranteed.  
If Last Msg Multiple Write option is checked, then the same message can be used for  
the writing of new values into the consecutive memory addresses of the same memory  
area (for example, into D0, D1, D2...). Up to 124 consecutive values can be included in  
the same write command. The new value can be added only to the end of last write  
message. Therefore some values may be written into the PLC memory simultaneously  
even if the client application changes them step-by-step. With this option writing speed  
can be seriously increased, and sequence of value changes are partly guaranteed  
(several new values could be written into PLC memory simultaneously while application  
change it step-by-step). For example, the client application sequentially changes the  
values of following 248 items: D0, D1, ... , D247 and the values of following 248 items:  
500R, 502R, ... , 994R. In this case the DAServer creates only four write messages to  
write the new values for all the changed items. If the values of the same Items are  
changed in the following sequence: DM0, 500R, DM1, 502R, DM2, ... then DAServer  
creates a separate write message for each new write value.  
If Any Msg Multiple Write option is checked, DAServer tries to include the new write  
value into any of previously created messages ignoring the sequence of data changing  
in the client application.  
Important! With this option maximum writing speed is achieved, but this option is not  
recommended if data changing sequence is important for PLC program!  
To delete device groups  
Deleting a device group from the list can be performed as follows:  
1. Right-click on the device group to be deleted.  
2. Select the Delete command from the shortcut menu.  
Note: When you select another part of the Omron Ethernet DAServer tree hierarchy, you  
are prompted to save the modifications to the configuration set.  
To configure default update intervals  
1. To configure a default update interval for the object, right-click in the Device Groups  
box.  
2. Select Config Default Update Interval from the shortcut menu.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
28  
To edit update intervals  
To edit the update interval for an object, double-click its value in the Update Interval  
column and make the edit.  
Update Interval is the frequency (in milliseconds) that the DAServer acquires data from  
the topics associated with that device group.  
Different topics can be polled at different rates in a PLC by defining multiple device-  
group names for the same PLC and setting a different Update Interval for each device  
group.  
Note: When you select another part of the Omron Ethernet DAServer tree hierarchy, you  
are prompted to save the modifications to the configuration set.  
Scan-Based Message Handling  
DAServers are based on the concept of polling a hardware device for information. This  
polling is driven by a need which is expressed in the form of requests from one or more  
clients. Once a particular piece of information has been requested by a client, the  
DAServer formulates its own request and sends that request to the hardware device. The  
DAServer then waits for a response to its request. Once the information has been  
received, the DAServer passes that information back to the client, and repeats the  
process until all clients have ceased requesting information.  
The rate at which the DAServer will poll a particular device for a specific piece of  
information is defined in the device group (topic definition) inside the DAServer, using a  
parameter called the Update Interval. When setting this parameter, there is always a  
trade-off between the update speed of the device group and the resulting decrease in  
system responsiveness.  
Since you more than likely want very fast response, the temptation is to set the Update  
Interval to a value close to 0 seconds. However, if every point is polled at this rate, the  
entire system will suffer due to slow response time. Therefore, you should compromise,  
and set the Update Interval to a more reasonable value. You could also create multiple  
device groups for each device, setting the Update Interval to different values, then  
assigning different items to different device groups depending on how quickly the values  
change and how quickly you want to see an update of those changes.  
Some items, like alarms, change very infrequently but because of their importance  
require very fast updates. For those kinds of items, you should set the Update Interval at  
a very small value. If you desire an immediate response, set the Update Interval at 1.  
Archiving Configuration Sets  
After you have configured your DAServer, you can archive that specific configuration. You  
can archive more than one configuration set, and subsequently choose different  
configurations for different purposes.  
To archive configuration sets  
1. In the DAServer Manager, right-click on the Configuration node in the hierarchy below  
your DAServer.  
2. Select Archive Configuration Set from the shortcut menu.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
29  
3. In the Archive Configuration Set configuration view, provide a Configuration Set  
Name.  
4. Click Archive.  
All current configuration values are saved to the archived set.  
Once you have archived at least one configuration set, you can select it for use.  
To use different configuration sets from the current one  
1. Make sure the DAServer is not running.  
2. In the DAServer Manager, right-click the Configuration node in the hierarchy below  
your DAServer.  
3. Select Use Another Configuration Set from the shortcut menu and click on a  
configuration set in the sub-menu.  
All parameters in the DAServer configuration hierarchy change to the chosen  
configuration set.  
Configuring Device Item Definitions  
The Device Items tab in the Parameters configuration view is used to define aliases to  
actual PLC items. The Device Items dialog box is the place where the following activities  
are performed:  
Creating new device item definitions for PLC items.  
Modifying the existing device items.  
Deleting device items.  
Archiving the created list of device items to a .csv file, a file with values separated by  
commas.  
Bringing a .csv file into the Device Items tab.  
Each device item definition should contain a unique name for the PLC associated with it.  
Device Item Definitions  
The Device Items dialog box, which is displayed by clicking the Device Items tab in the  
CV500 Parameters configuration view, is used to add, clear all, rename, delete, import  
and export device items. The Device Items dialog box has the following two columns:  
• Name: This column defines the alias names to actual PLC items.  
• Item Reference: The actual PLC item names, linked to the created aliases, are defined  
in this column.  
For example, for Data Memory Area D100, the following entries can be created.  
Name  
D100_Unsigned  
Item Reference  
D100  
D100_Signed  
D100S  
Note: When you create or add a new device item, a unique name needs to be entered for  
it.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
30  
To create or add device items  
1. To create or add device items, right-click in the Device Items dialog box.  
2. Select the Add command from the shortcut menu.  
A device item is created, and it is numerically named by default. For example, Item_0,  
Item_1, and so on.  
3. Change the default name by double-clicking on it and entering the new name.  
Enter a unique name for the new device item.  
To add item references  
Item references for each of the device items that have been created can be added as  
follows:  
1. In the Item Reference column, double-click on the area in the same horizontal line as  
the selected device item.  
2. Type in the actual PLC item name in the frame that appears.  
3. Click anywhere in the dialog box or press the Enter key to have the change take effect.  
To rename a device item from the list  
1. Right-click on the device item to be renamed.  
2. Select the Rename command from the shortcut menu and enter the new device item  
name.  
3. Click anywhere in the dialog box or press the Enter key to apply the change.  
To delete a device item from the list  
1. Right-click on the device item to be deleted.  
2. Select the Delete command from the shortcut menu.  
The device item and its corresponding actual PLC item name will be deleted from the  
dialog box.  
Note: When you select another part of the Omron Ethernet DAServer tree hierarchy, you  
are prompted to save the modifications to the configuration set.  
To clear all device items  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
31  
1. Right-click anywhere in the Device Items dialog box.  
2. Select the Clear All command from the shortcut menu.  
All the device items listed in the dialog box, including their corresponding actual PLC  
item names, will be deleted.  
To export device items  
When you have a list of device items that needs to be archived, use the Export feature in  
the Device Items dialog box to archive the list.  
1. To save the list, right-click anywhere in the Device Items dialog box.  
2. Select the Export command from the shortcut menu.  
3. Select the folder into which the list is to be saved.  
4. Name the list to be archived.  
5. Click the Save button.  
The whole list will be saved as a .csv file in Excel.  
To import device items  
The Import feature in the Device Items dialog box is used to bring an archived list of  
device items into the dialog box, when you need to utilize or reconfigure any of the device  
items on the archived list.  
1. To import the list, right-click anywhere in the Device Items dialog box.  
2. Select the Import command from the shortcut menu.  
3. Select the archived list (.csv file) to be imported from the folder in which it is saved.  
4. Click the Open button.  
The whole list will be brought into the Device Items dialog box.  
Note: When the list to be imported contains duplicate names as found in the current list  
but the Item References are different, a dialog box will appear to prompt you to make a  
selection.  
Hot Configuration  
The Omron Ethernet DAServer is hot-configurable. The following hot-configuration  
functionality is incorporated in Omron Ethernet DAServer:  
Modifying Global Configuration parameters.  
Adding, deleting, or modifying device nodes (without affecting any other device nodes,  
excluding the children of the modified device nodes).  
Adding, deleting, or modifying device groups.  
Limited support is provided for the hot configuration for the server-specific configuration  
parameters in this release. You can modify server-specific parameters while the server is  
active. However, to have those changes take effect, you have to restart the DAServer.  
Note: If changes are made to server-specific parameters while the server is active, the  
DAServer will issue a warning message to the logger.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
32  
CHAPTER 4  
Item Names  
The Omron Ethernet DAServer supports item/point names consistent with the point  
naming conventions used by OMRON PLCs and programming software. The Server  
supports almost all memory areas of the following OMRON PLC types: CS1, CJ1,  
C200HX, C200HG, C200HE, CV-series, C-series, CPM2x and CQM1.  
Contents  
Item Name General Format  
OMRON PLC’s Item Naming  
DAServer Standard System Items  
Generic OPC Syntax  
Item Name General Format  
In this section the general Item naming conventions used by OMRON Ethernet DAServer  
are explained.  
Each Integer, Discrete or Floating Point item generally may be described as:  
PnS  
Each item, representing bit in word, may be described as:  
Pn:b (or Pn:bb or Pn.b or Pn.bb)  
Each ASCII string item generally may be described as:  
Pn-PhS  
where:  
n -  
specifies the Memory area word/bit address of the specific word, flag or bit or  
lowest-numbered address of ASCII string.  
b (bb) - specifies the bit number in word (b can be 0…9 and bb can be 00…15). Number  
of digits in bit item name with separator is not relevant (leading zeroes are not  
necessary).  
h -  
Specifies the highest -numbered address of ASCII string.  
P -  
optionally used prefix, one, two or three characters before Memory area address,  
and designates the type of Memory area.  
S -  
optionally used suffix - a letter after address, which is used to change the default  
format of data. The following presents the OMRON Ethernet DAServer supported  
data formats and suffixes, indicating corresponding format.  
Unsigned/Signed Format  
The server interprets 16-bit word in a PLC in 16-bit unsigned format (value limits 0  
to 65535) or signed format (value limits -32768 to 32767). Unsigned quantities may  
be read by one of two methods - by entering item name without suffix or appending  
the suffix 'U' (or 'u') to the item name. For example, channel DM100 in a PLC  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
33  
contains 8000 hex. In this case item name DM100 or DM100U would be displayed  
in client as 32768. Signed quantities may be read from the same channel by  
appending the suffix 'S' (or 's') to the item name. So, item name DM100S would be  
displayed in client as -32768.  
BCD Format  
To read/write data using BCD format - append the suffix ‘B’ (or ‘b’) to the item  
name, e.g. DM100B.  
Long Format (Signed/BCD)  
Two consecutive 16-bit words in a PLC can be interpreted as a 32-bit long integer.  
It can be formatted as either signed (-2,147,483,648 to 2,147,483,648) or BCD (0  
to 99,999,999). To read/write an item in signed long format - append the letter 'L'  
(or 'l') to the item name. To read/write an item in BCD long format - append the  
letter 'M' (or 'm') to the item name. For example, if DM100 contains 0234 hex and  
DM101 contains 1356 hex, DM100L returns 324,403,764 and DM100M returns  
13,560,234.  
Note: Long format is not supported if Multiple Memory Area Read FINS commands  
are used.  
Floating Point Format (IEEE/BCD)  
Two consecutive 16-bit words in a PLC can be interpreted as a single precision  
floating point number. It is formatted as either IEEE (-3.402823 * 1038 to 3.402823  
* 1038) or BCD (0.0000001 * 10-7 to 0.9999999 * 10+7). To read/write an item in  
IEEE floating point format, append one of the following letters to the item name: 'F'  
or 'f’. To read/write an item in BCD floating point format - append the letter 'G' (or  
'g') to the item name. For example, if D100 contains 9620 hex and D101 contains  
2436 hex in a CV500 PLC, D100F returns 3.959212 * 10-17 and D100G returns  
0.4369620 * 102.  
Floating point format is relevant only with items, indicating memory areas word  
contents.  
Note: IEEE format is NOT supported in the C-Series PLC family  
Note: Floating point format is not supported if Multiple Memory Area Read FINS  
commands are used.  
ASCII Strings Format  
Multiple consecutive 16-bit words (block size of 1 to 29) in a PLC can be  
interpreted as a string of ASCII characters. The ASCII string is stored/retrieved  
from the lowest-numbered address to the highest and from the high-order byte to  
the low-order byte with each address. To define a range of words, use '-' (minus  
sign) between the two address locations. For example, DM10-DM12 indicates  
locations from DM10 to DM12. ASCII string characters can be specified to come  
from the high-order byte, low-order byte, or both bytes of the words:  
Low-order Byte  
Only the low-order byte (LSB - least significant 8-bits) of each  
word is used for read. To use this format, append the suffix 'E'  
to the item name.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
34  
High-order Byte  
Both Bytes  
Only the high-order byte (MSB - most significant 8-bits) of each  
word is used for read. To use this format, append the suffix 'D'  
to the item name.  
Both bytes of each word are used for read/write. To use this  
format, append the suffix 'C' to the item name.  
Note: All bytes in the specified memory range will be used. If the string is shorter  
than the range of memory specified, it will be padded with '\0'. If the string is longer  
than the range of memory specified, the string will be truncated.  
For example, assume the following memory contents (numeric values shown in  
hex):  
MSB  
41  
43  
LSB  
42  
44  
DM10  
DM11  
DM12  
"AB"  
"CD"  
"EF"  
45  
46  
Read:  
DM10 – DM12C  
DM10 – DM11D  
DM10 – DM12E  
returns ABCDEF  
returns AC  
returns BDF  
Write:  
DM10 - DM12C  
after written with "ABCD"  
MSB  
LSB  
DM10  
DM11  
DM12  
54  
73  
0
65  
74  
0
"AB"  
"CD"  
" "  
DM10 - DM12E  
after written with "ABCDE"  
MSB  
LSB  
DM10  
DM11  
DM12  
0
0
0
41  
42  
43  
"A"  
"B"  
"C"  
Imortant Note!  
Do not operate with item names, which have addresses outside really existing PLC  
data and memory area! It will lead to communication failures, because the DAServer  
recognizes item name error only if item name goes out of range represented in the item  
names table. Usually the information like following will be logged to logger if some item  
with address in inaccessible memory area is used (MRC:11 and SRC:03 informs about  
"Parameter error: the first address is in an inaccessible area")  
<Socket.Controller>: FINS command 0101 failed (resp. error code 1103). Parameter  
error: the first address is in inaccessible area.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
35  
CS1/CJ1 PLCs  
The following table lists the supported item names for the CS1/CJ1 PLCs:  
Memory Area  
Prefix  
Tag  
Type  
Range  
Value  
Rang  
e
Format  
Suffix  
CIO Area  
(Bit status)  
CIO Area  
Discrete CIO0:00...CIO6143:15  
or 0.00...6143.15  
0, 1  
CIO  
CIO  
W
W
H
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
CIO0... CIO6143  
or 0...6143  
W0:00... W511:15  
(*)  
u s b f g l  
m d e c  
(Word contents)  
Work Area  
(Bit status)  
Work Area  
0, 1  
(*)  
W0... W511  
H0:00... H511:15  
H0... H511  
u s b f g l  
m d e c  
(Word contents)  
Holding Area  
(Bit status)  
0, 1  
(*)  
Holding Area  
(Word contents)  
Auxiliary Area  
(Bit status) (**)  
Auxiliary Area  
(Word contents) (**)  
Data Memory DM  
Area (Bit status)  
Data Memory DM  
Area (Word cont.)  
Expansion Data  
Memory (Bit status)  
(***)  
u s b f g l  
m d e c  
H
A0:00... A959:15  
A0... A959  
0, 1  
(*)  
A
u s b f g l  
m d e c  
A
D0:00...D32767:15  
D0...D32767  
0, 1  
(*)  
D
u s b f g l  
m d e c  
D
E0:00...E32767:15  
0, 1  
E
Expansion Data  
Memory  
(Word cont.) (***)  
Expansion Data  
Memory (Bit status)  
(****)  
Expansion Data  
Memory  
(Word cont.) (****)  
Timer Completion  
Flags (*****)  
Counter Completion  
Flags (*****)  
Integer  
E0... E32767  
(*)  
0, 1  
(*)  
u s b f g l  
m d e c  
E
Discrete Ez0:00...Ez32767:15  
Ez  
(z = A  
to M)  
Ez  
(z = A  
to M)  
T
Integer  
Ez0... Ez32767  
u s b f g l  
m d e c  
Discrete  
Discrete  
Integer  
Integer  
T0... T4095  
C0... C4095  
0, 1  
0, 1  
(*)  
C
Timer PVs  
PVT0... PVT4095  
PVC0... PVC4095  
u s b f g l  
m d e c  
u s b f g l  
m d e c  
m
PVT  
PVC  
Counter PVs  
(*)  
Index Registers  
Data Registers  
(******)  
Long  
Integer  
IR0... IR15  
DR0... DR15  
(*)  
(*)  
IR  
DR  
u s b  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
36  
Item/point names, corresponding to CIO Area, may be without prefix.  
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"  
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with  
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for long or 32-bit  
integer is from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999.  
Default value range for Integer Tag Type is unsigned integer.  
(**) Data cannot be written to addresses A000…A447 in the Auxiliary Area.  
(***) Current bank only (Memory Area code 98 in Hex).  
(****) Extended memory bank 0 to bank C (in Hex), up to 13 banks supported depending  
on CPU type. The prefix Ez can be one of the following: EA, EB, EC, ED, EE, EF, EG,  
EH, EI, EJ, EK, EL or EM. For read operations (both for Bit status and Words) and for  
Word write operations the Memory Area codes A0…AC (in Hex) are used. For Bit writing  
the Memory Area codes 20…2C (in Hex) are used.  
(*****) Read only.  
(******) Not supported on CJ1 controllers.  
The following examples show the correct format for item names for CS1 and CJ1 PLCs:  
CIO2:01  
257  
-
-
CIO area (Bit status), word address 2, bit number 1.  
CIO Area (Word contents), word address 257  
H62.10  
D21  
EA12  
-
-
-
-
Holding Area (Bit), word address 62, bit number 10  
Data Memory Area with word address 21  
Extended Data Memory bank 0 word address 12  
Extended Data Memory bank 2 word address 48, bit number 10  
EC48.10  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
37  
C200HX/C200HG/C200HE PLCs  
The following table lists the supported item names for the C200HX, C200HG and  
C200HE PLCs.  
Memory Area  
Prefix  
Tag  
Address Range  
Value  
Suffix  
Type  
Range  
Internal Relay Area 1, 2  
Special Relay Area 1, 2  
(Bit status)  
Discrete IR0:00...IR511:15  
0, 1  
IR  
or  
0.00...511.15  
Internal Relay Area 1, 2  
Special Relay Area 1, 2  
(Word contents)  
Link Relay Area  
(Bit status)  
Link Relay Area  
(Word contents)  
Holding Relay Area  
(Bit status)  
Holding Relay Area  
(Word contents)  
Auxiliary Relay Area  
(Bit status)  
Integer  
IR0... IR511  
or  
(*)  
u s b f g l  
m d e c  
IR  
0…511  
Discrete LR0:00...LR63:15  
Integer LR0... LR63  
Discrete HR0:00... HR99:15  
Integer HR0... HR99  
Discrete AR0:00... AR27:15  
0, 1  
(*)  
LR  
LR  
HR  
HR  
AR  
AR  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
Auxiliary Relay Area  
(Word contents)  
Integer  
AR0... AR27  
u s b f g l  
m d e c  
Timer/Counter Area  
Completion Flag(****)  
Timer/Counter Area  
(PV)  
Data Memory Area  
(Bit status)(**)  
Data Memory Area  
(Word contents)(**)  
Extended Data Memory  
Area (Bit status)(***)  
Extended Data Memory  
Area Word contents(***)  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
TC0... TC511  
PV0... PV511  
0, 1  
(*)  
TC  
PV  
u s b f g l  
m d e c  
DM0:00...  
DM9999:15  
DM0...  
DM9999  
EM0:00...  
EM6143:15  
EM0... EM6143  
0, 1  
(*)  
DM  
DM  
EM  
EM  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
Item/point names, corresponding to Internal Relay/Special Relay Area may be without  
prefix.  
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"  
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with  
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is  
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default  
value range for Integer Tag Type is unsigned integer.  
(**) Memory area range DM7000…DM9999 is supported only if Expansion DM Area is  
allocated on the PLC.  
(***) Current bank only (Memory Area code 98).  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
38  
(****) Read only  
The following examples show the correct format for item names for C200HX, C200HG,  
C200HE PLCs and SYSMAC Board:  
IR2:01  
257  
LR62.10  
DM21  
-
-
-
-
Internal Relay Area (Bit status), word address 2, bit number 1.  
Special Relay Area (Word contents), word address 257  
Link Relay Area (Bit status), word address 62, bit number 10  
Data Memory Area (Word contents), word address 21  
CV-series PLCs  
The following table lists the supported item names for the CV-series PLCs:  
Memory Area  
Prefix  
Tag  
Address Range  
Value  
Suffix  
Type  
Range  
Input/Output  
register area CIO  
(Bit status)  
Discrete  
CIO0:00...  
CIO2555:15  
or 0.00... 2555.15  
CIO0... CIO2555  
or  
0, 1  
CIO  
Input/Output  
Integer  
(*)  
u s b f g l  
m d e c  
CIO  
register area CIO  
(Word contents)  
Bus Link Area G  
(Bit status)  
Bus Link Area G  
(Word contents)  
Auxiliary Relay  
area A (Bit status)  
Auxiliary Relay  
area A (Words)  
Timer Completion  
flags TIM (**)  
Counter  
0…2555  
Discrete G0:00... G255:15  
Integer G0... G255  
Discrete A0:00... A511:15  
0, 1  
(*)  
G
G
A
A
T
u s b f g l  
m d e c  
0, 1  
(*)  
Integer  
Discrete  
Discrete  
A0... A511  
u s b f g l  
m d e c  
T0...T1023(***)  
C0... C1023(***)  
0, 1  
0, 1  
C
Completion flags  
CNT (**)  
Timer Present  
Value  
Counter Present  
Value  
Data Memory area  
(Bit status)  
Integer  
Integer  
Discrete  
PVT0...  
PVT1023(***)  
PVC0...  
(*)  
(*)  
u s b f g l  
m d e c  
u s b f g l  
m d e c  
PVT  
PVC  
D
PVC1023(***)  
D0:00…  
D24575:15  
(****)  
0, 1  
Data Memory area  
(Word contents)  
Transition Area  
flags (**)  
Step Area Flag  
status (**)  
Integer  
Discrete  
Integer  
D0...D24575(****)  
(*)  
0,1  
u s b f g l  
m d e c  
D
TN0...  
TN1023(***)  
ST0...ST1023  
(***)  
TN  
ST  
0,1,2,3  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
39  
Step Timer  
Present Value  
Expansion area  
Current bank  
Integer  
PVS0...  
PVS1023(***)  
(*)  
u s b f g l  
m d e c  
PVS  
E
Discrete E0:00...E32765:15  
0, 1  
(Bit status)  
Expansion area  
Current bank  
Integer  
E0...E32765  
(*)  
u s b f g l  
m d e c  
E
(Word contents)  
Expansion area A  
(Bit status)  
Expansion area A  
(Word contents)  
Expansion area B  
(Bit status)  
Expansion area B  
(Word contents)  
Expansion area C  
(Bit status)  
Expansion area C  
(Word contents)  
Expansion area D  
(Bit status)  
Expansion area D  
(Word contents)  
Expansion area E  
(Bit status)  
Expansion area E  
(Word contents)  
Expansion area F  
(Bit status)  
Expansion area F  
(Word contents)  
Expansion area G  
(Bit status)  
Expansion area G  
(Word contents)  
Expansion area H  
(Bit status)  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Integer  
EA0:00...  
EA32765:15  
EA0...  
EA32765  
EB0:00...  
EB32765:15  
EB0...  
EB32765  
EC0:00...  
EC32765:15  
EC0...  
EC32765  
ED0:00...  
ED32765:15  
ED0...  
ED32765  
EE0:00...  
EE32765:15  
EE0...  
EE32765  
EF0:00...  
EF32765:15  
EF0...  
EF32765  
EG0:00...  
EG32765:15  
EG0...  
EG32765  
EH0:00...  
EH32765:15  
EH0...  
0, 1  
(*)  
EA  
EA  
EB  
EB  
EC  
EC  
ED  
ED  
EE  
EE  
EF  
EF  
EG  
EG  
EH  
EH  
AC  
IR  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
Expansion area H  
(Word contents)  
Action Area Flag  
(**)  
Register Area  
contents IR (***)  
u s b f g l  
m d e c  
EH32765  
AC0…AC2047  
(*****)  
0, 1  
(*)  
IR0...IR2  
u s b f g l  
m d e c  
u s b f g l  
m d e c  
Register Area  
contents DR (**)  
DR0...DR2  
(***)  
(*)  
DR  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
40  
Item/point names, corresponding to Input/Output register area CIO, may be without  
prefix.  
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"  
("u") or without suffix), for signed integers from 32768 to 32767 (item/point name with  
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is  
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default  
value range for Integer Tag Type is unsigned integer.  
(**) Read only. Note: with DR area item without suffix (or with suffixes u, s, b) are  
Read/Write.  
(***) Represented memory area ranges are for CV1000, CV2000 and CVM1-CPU11-E  
(except Transition Area and Step Area Flag status) type controllers. For models CV500  
and CVM1-CPU01-E (except Transition Area and Step Area Flag status) - accessible  
memory area ranges are 0:00...511:15 for Discrete items and 0...511 - for Integer items.  
Transition Area TN and Step Area Flag status area ST are not supported on CVM1 PLCs.  
(****) Represented memory area ranges are for CV1000, CV2000 and CVM1-CPU11-E  
type controllers. For models CV500 and CVM1-CPU01-E - accessible memory area  
ranges are 0...8191.  
(*****) Represented memory area ranges are for CV1000 and CV2000 type controllers  
only. For model CV500 - accessible memory area ranges are 0...1023. With other CV-  
series PLCs – not supported.  
Expansion area Current bank as well as Expansion areas (from EA to EH) is relevant only  
with CV1000 and CV2000 PLCs.  
Item names IR and DR are valid with following Omron PLC models: CV1000, CV2000  
and CVM1-CPU11-E.  
The configuration of the discrete data can be as follows:  
0: Bit is OFF;  
1: Bit is ON;  
Flag or Bit Status  
0: INACTIVE;  
1: HALT;  
Step Status  
2: PAUSE;  
3: EXECUTE;  
The following examples show the correct format for item names for CV-series PLCs:  
CIO1:15  
211  
TN200  
ST0007  
AC6  
-
-
-
-
-
-
CIO area (Bit status), word address 1, bit number 15.  
CIO area (Word contents), word address 211  
Transition Area flag, address 200  
Step Area Flag status, address 7  
Action Area Flag status, address 6  
D3F  
real (floating point) item, value is taken from words D3 and D4.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
41  
C/CPM2x PLCs  
The following table lists the supported item names for the C-series PLCs:  
Memory Area  
Prefix  
Tag  
Type  
Range  
Value  
Range  
Format  
Suffix  
CIO area  
(Bit status)  
CIO area  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
IR0:00...IR511:15  
or 0.00...511.15 (**)  
IR0... IR511  
or 0...511 (**)  
LR0:00... LR63:15  
0, 1  
IR  
IR  
(*)  
u s b f g l  
m d e c  
(Word contents)  
Latching Relay area  
(Bit status)  
Latching Relay area  
(Word contents)  
Holding Relay area  
(Bit status)  
Holding Relay area  
(Word contents)  
Auxiliary Relay area  
(Bit status)  
Auxiliary Relay area  
(Word contents)  
Completion flags for  
Timers/Counters(***)  
Present Values for  
Timers/Counters  
Data Memory area  
(Bit status)  
0, 1  
(*)  
LR  
LR  
HR  
HR  
AR  
AR  
TC  
PV  
DM  
DM  
LR0... LR63  
HR0:00... HR99:15  
HR0... HR99  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
AR0:00... AR27:15  
AR0... AR27  
0, 1  
(*)  
u s b f g l  
m d e c  
TC0... TC511  
0, 1  
(*)  
PV0... PV511  
u s b f g l  
m d e c  
Discrete DM0:0...DM9999:15  
0, 1  
(*)  
Data Memory area  
(Word contents)  
Integer  
DM0...  
DM9999  
u s b f g l  
m d e c  
Item/point names, corresponding to Input/Output register area CIO, may be without  
prefix.  
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"  
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with  
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is  
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default  
value range for Integer Tag Type is unsigned integer.  
(**) Represented memory area range is for C200HS type controller. For models C200H,  
C1000H and C2000H - accessible memory area ranges are 0:00...255:15 for Discrete  
items and 000...255 for Integer items.  
(***) Read only  
The following table lists the supported item names for the CPM2x PLCs:  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
42  
Memory Area  
Prefix  
Tag  
Type  
Range  
Value  
Range  
Format  
Suffix  
IR & SR areas  
(Bit status)(***)  
IR & SR areas  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
IR0:00...IR255:15  
or 0.00...255.15  
IR0...IR255  
or 0...255  
LR0:00... LR15:15  
0, 1  
IR  
IR  
(*)  
u s b f g l  
m d e c  
(Word contents) (***)  
Latching Relay area  
(Bit status)  
Latching Relay area  
(Word contents)  
Holding Relay area  
(Bit status)  
Holding Relay area  
(Word contents)  
Auxiliary Relay area  
(Bit status)  
Auxiliary Relay area  
(Word contents)  
Completion flags for  
Timers/Counters(**)  
Present Values for  
Timers/Counters  
Data Memory area  
(Bit status) (****)  
Data Memory area  
(Word contents) (****)  
0, 1  
(*)  
LR  
LR  
HR  
HR  
AR  
AR  
TC  
PV  
DM  
DM  
LR0... LR15  
HR0:00... HR19:15  
HR0... HR19  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
AR0:00... AR23:15  
AR0... AR23  
0, 1  
(*)  
u s b f g l  
m d e c  
TC0... TC255  
0, 1  
(*)  
PV0... PV255  
u s b f g l  
m d e c  
Discrete DM0:0...DM6655:15  
0, 1  
(*)  
Integer  
DM0...  
DM6655  
u s b f g l  
m d e c  
Item/point names, corresponding to IR and SR areas, may be without prefix.  
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"  
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with  
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is  
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default  
value range for Integer Tag Type is unsigned integer.  
(**) Read only  
(***) Addresses 50 to 199 in IR & SR area in CPM2A/CPM2C PLCs and 20 to 199 in IR &  
SR area in CPM1/CPM1A/SRM1(-V2) PLCs are read only.  
(****) Addresses DM1024 to DM6143 in CPM1/CPM1A PCs and DM2048 to DM6143 in  
CPM2A/CPM2C/SRM1(-V2) PCs are read only.  
The following examples show the correct format for item names for C/CPM2x PLCs:  
IR2:01 - CIO area (Bit status), word address 2, bit number 1.  
211  
-
CIO area (Word contents), word address 211.  
LR62.10 - Latching Relay area (Bit status), word address 62, bit number 10.  
DM21 - Data Memory area (Word contents), word address 21.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
43  
CQM1 PLCs  
The following table lists the supported item names for the CQM1 PLCs:  
Memory Area  
Prefix  
Tag  
Type  
Range  
Value  
Range  
Format  
Suffix  
IR & SR area  
(Bit status)  
IR & SR area  
(Word contents)  
LR area  
(Bit status)  
LR area  
(Word contents)  
HR area  
(Bit status)  
HR area  
(Word contents)  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
Discrete  
Integer  
IR0:00...IR255:15  
or 0.00... 255.15 (**)  
IR0... IR255  
or 0... 255 (**)  
LR0:00... LR63:15  
0, 1  
IR  
IR  
(*)  
u s b f g l  
m d e c  
0, 1  
(*)  
LR  
LR  
HR  
HR  
AR  
AR  
TC  
PV  
DM  
DM  
EM  
EM  
LR0... LR63  
HR0:00... HR99:15  
HR0... HR99  
u s b f g l  
m d e c  
0, 1  
(*)  
u s b f g l  
m d e c  
AR area  
(Bit status)  
AR area  
AR0:00... AR27:15  
AR0... AR27  
0, 1  
(*)  
u s b f g l  
m d e c  
(Word contents)  
Completion flags for  
Timers/Counters(***)  
Present Values for  
Timers/Counters  
DM area  
TC0... TC511  
0, 1  
(*)  
PV0... PV511  
u s b f g l  
m d e c  
Discrete DM0:0...DM6655:15  
Integer DM0...DM6655  
Discrete EM0:0...EM6143:15  
Integer EM0...EM6143  
0, 1  
(*)  
(Bit status)  
DM area  
(Word contents)  
u s b f g l  
m d e c  
EM area  
(Bit status)  
EM area  
0, 1  
(*)  
u s b f g l  
m d e c  
(Word contents)  
Item/point names, corresponding to IR and SR areas, may be without prefix.  
(*) Value range for unsigned integer is from 0 to 65535 (item/point name with suffix "U"  
("u") or without suffix), for signed integers from –32768 to 32767 (item/point name with  
suffix "S" ("s")) and for 16-bit BCD is from 0 to 9999. The value range for 32-bit integer is  
from -2147483648 to 2147483647 and for 32-bit BCD is from 0 to 99999999. Default  
value range for Integer Tag Type is unsigned integer.  
(**) Represented memory area available in CQM1H-CPU61 CPU.  
(***) Read only  
The following examples show the correct format for item names for CQM1 PLCs:  
IR2:1  
-
IR Input area (Bit status), word address 2, bit number 1.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
44  
102  
LR62.10  
DM21  
-
-
-
IR Output area (Word contents), word address 102  
LR area (Bit status), word address 62, bit number 10  
DM area (Word contents), word address 21  
DAServer Standard System Items  
System Items provide you with easy access to the DAServer status and diagnostics  
information. They are treated just like ordinary items with respect to the client. However,  
in most cases these items are not directly acquired via the communications layer. System  
item values are usually generated through internal calculations, measurements, and the  
tracking of the DAS Engine.  
No DAServer-specific system items are provided in this Omron Ethernet DAServer.  
System items, like ordinary items, are defined by the following properties:  
• Group (client group/OPC group): The arbitrary collection of items, not correlated.  
• Hierarchical location (link name/OPC path. The hierarchical node section of the fully  
qualified OPC item ID.): The device the item is attached to.  
• Device group (OPC access path/topic, or a Scan Group on a hierarchical branch.): A  
collection of items on the same physical location with the same protocol update rate.  
Example:  
To check the status of an external device, the reference might be:  
DASOmronEth.Socket1.$SYS$Status  
Note: This syntax does not refer to the access path/device group. As long as the data  
requested is from the same external device, the value will always be the same.  
Note: For DDE/SuiteLink clients, $SYS$Status always comes from the leaf level of a  
DAServer hierarchy branch, which is the destination PLC node. For OPC clients,  
$SYS$Status can be accessed at all hierarchy levels. $SYS$Status at the root level of  
the whole hierarchy tree is always good, as it represents the quality status of the local  
computer itself. Hence, for practical application, OPC clients should reference  
$SYS$Status at any hierarchy levels other than the root.  
In the ArchestrA context, the device group plays the most important role of identifying the  
scope of any item (the device group defines the hierarchical location implicitly when using  
globally unique device-group names, which is required for DDE/SuiteLink compatibility).  
All system items follow the same naming convention:  
All system items start with $SYS$.  
The DAS Engine scans and parses the name for system items.  
Parsing of the name is case-insensitive.  
All system items can be accessed through subscriptions to a device group. However,  
while some system items return data for that device group, others are server-wide.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
45  
DAServer Global System Item  
The following system item refers to specific information regarding a global condition of the  
DAServer.  
System Item  
Name  
Type/  
Access  
Rights  
Description  
Values  
$SYS$Licensed Boolean/ Binary status indication of the  
RANGE: 0, 1  
Read  
existence of a valid license for the  
DAServer.  
1: Valid license  
exists.  
If FALSE, this item causes the  
DAServer to stop updating existing  
tags, to refuse activation of new tags, 0: No valid  
and to reject write requests in addition license exists.  
to setting quality for all items to BAD.  
If TRUE, the DAServer functions as  
configured.  
All instances have the same value.  
Note: With Omron Ethernet DAServer Global System Item $SYS$Licensed is not  
relevant.  
DAServer Device-Specific System Items  
The following system items refer to specific information regarding the device(s) the  
DAServer is connected to.  
System Item  
Name  
Type/  
Access  
Rights  
Boolean/  
Read  
Description  
Values  
$SYS$Status  
Binary status indication of the  
connection state to the device  
(hierarchy level) the item is  
attached to.  
The device group (OPC access  
path/topic) does not affect the  
value. The status can be good  
even if individual items have  
errors.  
RANGE: 0, 1  
1: DAServer  
connection to the  
device is intact.  
0: Error  
communicating  
with the device.  
For DDE/SuiteLink clients,  
$SYS$Status always comes  
from the leaf level of a DAServer  
hierarchy branch, which is the  
destination PLC node.  
For OPC clients, $SYS$Status  
can be accessed at all hierarchy  
levels. $SYS$Status at the root  
level of the whole hierarchy tree  
is always good, as it represents  
the quality status of the local  
computer itself. Hence, for  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
46  
practical application, OPC clients  
should reference $SYS$Status  
at any hierarchy levels other  
than the root.  
$SYS$ErrorCode  
Longint/  
Read  
Detailed error code of the  
communications state to the  
device. The device group (OPC  
access path/topic) does not  
affect the value.  
>= 0: Good  
status (0 is the  
default state –  
connected.  
>0: is some  
device state like:  
connecting,  
initializing, etc.  
<0: Error status  
(value indicates  
the error).  
$SYS$ErrorText  
String/  
Read  
Detailed error string of the  
communications state of the  
device. The device group (OPC  
access path/topic) does not  
affect the value.  
Descriptive text  
for the  
communications  
state  
corresponding to  
the error code.  
RANGE: -1, 0, 1  
-1: Error  
occurred during  
saving the  
$SYS$StoreSettings Integer/  
Used to make the temporary  
ReadWrite update interval changes via the  
$SYS$UpdateInterval item  
permanent. If the client pokes a  
value of 1 into this system item,  
the currently set update interval  
is written to the server’s  
configuration file.  
0: Read value  
always if status is  
OK.  
configuration file. The value of  
this system item clears to 0 after 1: Persist  
being set, if the configuration file settings (cleared  
write is successful.  
immediately).  
If the write fails, then the value is  
set to -1.  
If the update interval has been  
changed via the  
$SYS$UpdateInterval item and  
this item is not poked to 1, the  
DAServer uses the original  
update interval for that topic the  
next time it is started.  
Reading the item always  
provides 0.  
Read/Write values are persisted  
only if the user sets this system  
item. The values other than this  
persist only for the life of the  
DAServer.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
47  
DAServer Device-Group-Specific System Items  
The following system items refer to specific information regarding device groups that have  
been configured in the DAServer.  
System Item  
Name  
Type/  
Access  
Rights  
Description  
Values  
$SYS$UpdateInterval  
DWord/  
Used to access the currently  
RANGE:  
ReadWrite set update interval. It is the  
current update interval of the  
device group in milliseconds.  
A client can poke new values  
into this item.  
1…2147483647  
0: Topic inactive,  
no items are  
updated. Data  
acquisition is  
stopped.  
>0: Expected  
updated interval  
for the set of all  
items in the  
The value of zero indicates  
that no non-system items on  
that topic are updated (data  
for these items are not  
acquired from the device).  
device group.  
$SYS$MaxInterval  
DWord/  
Read  
Used to access the currently  
measured maximum update  
interval in milliseconds of all  
items of the corresponding  
device group. This item is  
read-only. The value of the  
slowest item is displayed.  
RANGE:  
0…2147483647  
0: If update  
interval is 0 or if  
the status is  
false.  
>0: Measured  
update interval  
RANGE: -1, 0, 1  
$SYS$WriteComplete  
Integer/  
Used to access the state of  
ReadWrite pending write activities on the  
corresponding device group.  
On device group creation  
(adding items to an OPC  
group), the value of this  
1: Write  
complete (no  
writes are  
pending – initial  
state).  
0: Writes are  
pending.  
system item is initially 1,  
indicating all write activities  
are complete – no pokes are  
pending.  
-1: Writes  
If values are poked into any  
completed with  
items of the device group, the errors.  
value of this item changes to  
0, indicating write activity is  
currently in progress.  
If the server has completed all  
write activities, the value of  
this item changes to 1 if all  
pokes were successful or to -1  
if at least one poke has failed.  
If the value of this item is not  
zero, the client can poke 1 or -  
1 to it (poke a 1 to clear errors,  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
48  
or a -1 to test a client reaction  
on write errors).  
If the value of this item is zero,  
it cannot be poked.  
$SYS$ReadComplete  
Integer/  
Used to access the state of  
RANGE: -1, 0, 1  
ReadWrite initial reads on all items in the  
corresponding device group.  
The value is 1 if all active  
1: Read  
complete (all  
values have  
been read).  
0: Not all values  
have been read.  
-1: All values  
have been read  
items in a device group have  
been read at least once. If at  
least one item in the device  
group is activated, this item  
changes to 0. It changes to 1  
if all items have been read  
successfully, or to -1 if at least but some have a  
one item has a non-good  
quality. Poking a 0 to this item  
resets the internal read states  
of all items in this device  
group. This resets this item to  
0. If all items are read again  
after this poke, this item  
non-good quality.  
changes back to 1 or -1.  
$SYS$ItemCount  
DWord/  
Read  
Used to access the number of RANGE:  
items in the corresponding  
device group. This item is  
read-only.  
0…2147483647  
>=0: Number of  
active items.  
$SYS$ActiveItemCoun DWord/  
Used to access the number of RANGE:  
t
Read  
active items in the  
0…2147483647  
corresponding device group.  
This item is read-only.  
>=0: Number of  
active items.  
$SYS$ErrorCount  
DWord/  
Read  
Used to access the number of RANGE:  
all items (active and inactive)  
that have errors (non-good  
OPC quality) in the  
0…2147483647  
>=0: Number of  
all items (active  
and inactive) with  
errors.  
corresponding topic. If the  
communications status of a  
device group is bad, all items  
have errors. This item is read-  
only.  
$SYS$PollNow  
Boolean/  
Poking a 1 to this item forces  
RANGE: 0, 1  
ReadWrite all items in the corresponding  
device group to be read  
immediately (all messages in  
this device group become  
due). This is useful if you want  
to force to get the newest  
values from the device,  
regardless of its update  
interval. This also works on  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
49  
device groups with a zero  
update interval (manual  
protocol triggering).  
Generic OPC Syntax  
DAServer serves as a container for the OPC Groups, which provide the mechanism for  
containing and logically organizing OPC items. Within each OPC Group, an OPC-  
compliant client can register OPC items, which represent connections to data sources in  
the field device. In other words, all access to OPC items is maintained through the OPC  
Group.  
The fully qualified name for an OPC item is called the Item ID (equivalent to Item Name).  
Generally, in OPC data acquisition DAServers, the syntax can be as follows:  
AREA10.VESSEL1.TIC1.PLC.D100  
where each component (delimited by a period) represents a branch or leaf of the field  
device’s hierarchy. In this example:  
PLC is the name of the target PLC.  
D100 is the specific data point (Item) desired.  
An item is typically a single value such as an analog, digital, or string value.  
The syntax for specifying a unique Item ID is DAServer-dependent. With Omron Ethernet  
DAServer Item ID example could be the following:  
Unit1.CV500.D100  
Item ID describes the syntax for defining the desired data point, OPC provides for another  
parameter, called Access Path, that defines optional specifications for obtaining that data.  
In DAServers, Access Paths are equivalent to Device Groups; it is this parameter that is  
used to define the update interval between the DAServer and the field device for  
accessing the values of data points in the PLC.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
50  
CHAPTER 5  
Troubleshooting  
This chapter describes the troubleshooting tools you can use to deal with the Omron  
Ethernet DAServer problems you may encounter.  
The DAServer Manager provides access to diagnostics and other statistical data, and the  
Log Viewer provides access to event messages logged during the operation of a  
DAServer. Also, your client (for example, InTouch) can monitor connectivity with the PLC  
through the $SYS$Status item. Use these tools together with the following information to  
troubleshoot your Omron Ethernet DAServer.  
Note: In order to determine the version of your DAServer, perform the following steps.  
Search for DASOmronEth.dll, right-click on the File Name, select Properties on the  
shortcut menu, and select the Version tab on the Properties dialog box. The version of  
your DAServer is listed under File Version.  
Contents  
Monitoring Connectivity Status with the PLC  
Monitoring the Status of DAS Conversations  
Error Messages and Codes  
Monitoring Connectivity Status with the PLC  
The built-in discrete item, $SYS$Status, can be used to monitor the status of  
communications with the PLC. This item is set to:  
0 (zero) when communications with the PLC fails.  
1 (one) when communications is successful.  
Note: For DDE/SuiteLink clients, $SYS$Status always comes from the leaf level of a  
DAServer hierarchy branch, which is the destination PLC node. For OPC clients,  
$SYS$Status can be accessed at all hierarchy levels. $SYS$Status at the root level of  
the whole hierarchy tree is always good, as it represents the quality status of the local  
computer itself. Hence, for practical application, OPC clients should reference  
$SYS$Status at any hierarchy levels other than the root.  
Enter the following DDE reference formula in the appropriate place in your client:  
=DASOmronEth|PLC!$SYS$Status  
where:  
DASOmronEth is the name of the DAServer application.  
PLC is the exact device group defined in the DAServer for the PLC.  
$SYS$Status is the discrete item used to monitor the status of connectivity with the PLC.  
Enter the following OPC item reference syntax when adding the item in your OPC client:  
YourOPCAccessPath.$SYS$Status  
where:  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
51  
YourOPCAccessPath is the assembly of hierarchy node names leading to a specific  
controller device.  
$SYS$Status is the discrete item used to monitor the status of connectivity with the  
controller device.  
Note: In the case of a PLC disconnect, the DAServer will retry three times before entering  
into slow poll mode. In the case of reply time-out, the DAServer will go into slow poll  
mode immediately.  
Monitoring the Status of DAS Conversations  
The InTouch WindowViewer supports built-in topic names, called DDEStatus and  
IOStatus, that can be used to monitor the status of specific DAS conversations.  
For example, let us assume that WindowViewer (VIEW) is communicating with the  
Omron Ethernet DAServer to a PLC that has been defined in the DAServer with the topic  
name OmronPLC. The discrete items, DDEStatus and IOStatus, are set to:  
0 (zero) when this DAS conversation failed.  
1 (one) when this DAS conversation is successful.  
Using DDEStatus and IOStatus in Excel  
The status of communications between the PLC and InTouch can be read into Excel by  
entering the following DDE reference formula in a cell on a spreadsheet:  
=view|DDEStatus!OmronPLC  
or  
=view|IOStatus!OmronPLC  
where:  
view is the name of the InTouch application.  
[DDE][IO] Status is the built-in topic name used to monitor the status of communications  
between the DAServer and InTouch.  
OmronPLC is the exact topic name defined in the server for the PLC.  
Reading Values from the DAServer into Excel  
Values may be read directly into Excel spreadsheets from the DAServer by entering a  
DDE formula into a cell using the following format:  
=applicationname|<devicegroup>!itemname  
Example formula:  
=DASOmronEth|OmronPLC!'d100'  
where:  
DASOmronEth is the name of the DAServer application.  
OmronPLC is the exact device group name defined in the DAServer for the PLC.  
D100 is the actual location in the PLC that contains the data value. This is the item name.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
52  
In this example, each time the value of <tagname> changes in the PLC, the DAServer  
will automatically send the new value to the cell containing the formula in Excel.  
Note: Refer to the Microsoft Excel manual for complete details on entering Remote  
Reference formulas for cells.  
Writing Values to the DAServer from Excel  
Values may be written to the DAServer from Microsoft Excel by creating an Excel macro  
that uses the POKE command. The proper command is entered in Excel as follows:  
channel=INITIATE("applicationname","topicname")  
=POKE(channel,"itemname", Data_Reference)  
=TERMINATE (channel)  
=RETURN()  
The following describes each of the above POKE macro statements:  
channel=INITIATE("applicationname","topicname")  
Opens a channel to a specific topic name (defined in the DAServer) in a particular  
application name (the executable name less the .exe).  
Assigns the number of that opened channel to channel.  
Note: By using the channel=INITIATE statement, the word channel must be used in the  
=POKE statement instead of the actual cell reference. The "application name" and  
"topic name" portions of the formula must be enclosed in quotation marks.  
=POKE(channel,"itemname", Data_Reference)  
• POKEs the value contained in the Data_Reference to the specified item name (actual  
location in the PLC), via the channel number returned by the previously executed  
INITIATE function.  
• Data_Reference is the row/column ID of the cell containing the data value.  
=TERMINATE(channel)  
Closes the channel at the end of the macro.  
Some applications have a limited number of channels; therefore, they should be closed  
when finished.  
• Channel is the channel number returned by the previously executed INITIATE function.  
=RETURN()  
Marks the end of the macro.  
Note: Refer to the .xlm sample Excel poke macro provided on the DAServer CD. Also  
refer to the Microsoft Excel manual for complete details on entering Remote Reference  
formulas for cells.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
53  
Error Messages and Codes  
Generic DAServer error messages and Omron Ethernet-DAServer-specific messages are  
supported. Use the Log Flag data to customize the messages logged to the Log Viewer.  
See the Log Viewer online documentation for more information about using log flags.  
To troubleshoot DAServer problems, use the following error messages together with the  
DAServer Manager Diagnostics root data.  
DAServer Error Messages  
The following table lists all the generic-DAServer and Omron Ethernet-DAServer-specific  
error messages that are logged to the Log Viewer.  
Error Message  
OmronEthAdapter  
<SockName>: Invalid Sockets API  
Explanation  
Windows  
Probable Cause  
Configured invalid  
Host Name (IP  
Solution  
Enter correct Error  
Host Name or  
Log Flag  
local Host Name (IP  
Address)  
functions do  
not accept Host for SOCKET  
Addr.) parameter  
IP Address.  
<WrongName>.  
Further operate with  
Host name: 0.0.0.0 !!!  
Name (IP  
Address) value.  
<SockName >.  
<Socket_  
Windows  
Configured invalid  
Controller IP  
Address  
<WrongIPAddress  
>
Enter correct Error  
Controller IP  
Address.  
ControllerName>:  
Invalid PLC's  
IPAddress  
Sockets API  
functions do  
not accept  
Controller IP  
Address value.  
<WrongIPAddress>  
Socket <SockName> Failed creating For reason - see  
Solve  
DASProtFail  
::OnMessageToSend Ethernet  
Error description in problems  
, Creating Eth.  
Socket by  
Windows  
Sockets dlls  
the message.  
Most possible  
cause - Ethernet  
Port already  
mentioned in  
Error  
description.  
Avoid  
Socket get Error  
<Error number>:  
<Error description>  
occupied by other  
OMRON Ethernet  
concurrently  
communicatio  
DAServer socket or n through  
other application.  
Sockets with  
equal Port  
numbers.  
<Socket_  
Failed creation Invalid Watchdog  
Enter correct Error  
Watchdog  
Address (right  
ControllerName>:  
Can not create  
Watchdog Message.  
Do not process  
Watchdog.  
of Watchdog  
message.  
Address or Invalid  
Watchdog value.  
Watchdog  
Watchdog Address Item name  
message is not area could be non- representing  
processed until supported by  
2-bytes long  
Word  
memory area  
without  
solving the  
problems.  
current DAServer  
version.  
suffix). Enter  
Watchdog.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
54  
value from 0  
to 65535.  
< Socket_  
Failed creation Invalid Watchdog  
Enter right  
Watchdog  
Address (right  
Item name  
representing  
2-bytes long  
Word  
Error  
ControllerName>:  
Invalid Watchdog  
Address  
<InvalWdAddress> -  
must be valid Item  
name. Do not  
of Watchdog  
message.  
Address  
configured.  
Watchdog  
message is not  
processed until  
solving the  
problems.  
memory area  
without  
process Watchdog.  
suffix).  
HASP key not found! DAServer does No/invalid HASP  
Install valid  
HASP key  
into parallel  
or USB port  
Install valid  
HASP key  
into parallel  
or USB port  
or restart  
DASProtWarn  
DASProtWarn  
not find the  
valid HASP key  
installed  
key  
HASP key not found, DAServer does No/invalid HASP  
demo mode, will quit not find valid key installed  
after 1 hour!  
HASP key  
installed.  
Server will run  
1 hour in demo  
mode.  
Server after  
1-hour demo  
expires.  
HASP key not found! DAServer does No/invalid HASP  
Install valid  
HASP key  
into parallel  
or USB port  
DASProtWarn  
not find valid  
HASP key  
key installed  
installed. If  
demo mode  
has been  
started, the  
Server stops  
communicate.  
Socket <SockName>: Received  
Message with service response  
Problems in  
Ethernet FA  
Configure  
greater  
DASProtFail  
ID <number> not  
found.  
message with  
network or  
communic.  
(reply) time-  
outs. Check  
the network.  
Service ID, that communication  
does not match timing problems.  
with any of sent  
request  
messages ID.  
<Socket_  
The item name Item name does  
Use right Item DASProtFail  
name (see  
Item Names  
section in this  
manual)  
ControllerName>:  
Invalid item name  
<Invalid_ItemName>  
is invalid.  
not correspond to  
Item naming  
conventions for  
OMRON Ethernet  
DAServer.  
<Socket_  
ControllerName>:  
Read message for  
Length of read Usually there  
message for shouldn’t be any  
Item (or length problems creating  
Configure  
satisfactory  
max read  
DASProtFail  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
55  
Item <ItemName>  
(<Pointer to  
of response  
message)  
read messages for message  
such Item types as length for  
Item_Class_Obj.>)  
exceeds max  
discrete, integer,  
long or floating  
point. When poll  
multiple  
Controller  
object, or  
change item  
name  
was not created: max read message  
allowed message's length,  
length <Max_Length> configured for  
is not sufficient.  
Controller  
object.  
consecutive 16-bit  
words as ASCII  
string Item – you  
could face this  
error condition if  
configuring too  
small max read  
message length.  
(decrease  
number of  
words in  
ASCII string  
Item).  
<Socket_  
Creating write  
command  
failed.  
Invalid value poked Check Item’s DASProtFail  
ControllerName>:  
CreatePokeMessage,  
cannot get Item's  
<ItemName>  
or DAServer  
value to  
processing error.  
poke. Repeat  
the poke  
processing.  
(<Pointer to  
Item_Class_Obj.>)  
value, error =  
<Error_Code>  
<Socket_  
Length of write Usually there  
message for shouldn’t be any  
Item (or length problems creating  
Configure  
satisfactory  
max write  
DASProtFail  
ControllerName>:  
Write message for  
Item <ItemName>  
(<Pointer to  
of response  
message)  
write messages for message  
such Item types as length for  
exceeds max.  
write message long or floating  
length,  
configured for  
Controller  
object.  
discrete, integer,  
Controller  
object, or  
change item  
name  
(decrease  
number of  
words in  
Item_Class_Obj.>)  
was not created: max  
allowed message's  
length <Max_Length>  
is not sufficient.  
point. When poke  
multiple  
consecutive 16-bit  
words as ASCII  
string Item – you  
could face this  
error condition if  
configuring too  
small max write  
message length.  
ASCII string  
Item).  
<Socket_  
Writing of new Timing problems or Repeat poke DASProtFail  
ControllerName>:  
Write message for  
Item <ItemName>  
(<Pointer to  
Item_Class_Obj.>)  
was not created.  
Preparing of read  
command for bit  
writing failed.  
value into bit-  
of-word is  
processed in  
two steps: a)  
reading of  
corresponding  
word value, b)  
overwriting bit  
value in word  
DAServer code  
processing  
problems.  
processing.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
56  
and writing  
back modified  
word value into  
PLC’s memory.  
Here the  
processing of  
first step failed.  
<Socket_  
Data, received  
from PLC,  
cannot be  
converted into  
right BCD  
value.  
Assigned value  
19999.  
Data, received  
from PLC,  
Take into  
account,  
when creating  
client  
DASProtWarn  
DASProtWarn  
ControllerName>:  
Item <Pointer to  
Item_Class_Obj.>  
(<ItemName>) read  
illegal BCD value  
<WrongValue> hex,  
returning 19999.  
<Socket_  
ControllerName>:  
Item <Pointer to  
Item_Class_Obj.>  
(<ItemName>) read  
illegal BCD Long  
value <WrongValue>  
hex, returning  
application.  
Take into  
account,  
when creating  
client  
cannot be  
converted into  
right BCD Long  
value.  
Assigned value  
199999999.  
application.  
199999999.  
<Socket_  
Data, received  
from PLC,  
cannot be  
converted into  
right BCD  
Take into  
account,  
when creating  
client  
DASProtWarn  
ControllerName>:  
Item <Pointer to  
Item_Class_Obj.>  
(<ItemName>) read  
illegal BCD Floating  
Point value  
application.  
Floating Point  
value.  
Assigned value  
0.0.  
<WrongValue> hex,  
returning 0.0.  
<Socket_  
Client  
This error  
Avoid writing DASProtWarn  
values out-of-  
ControllerName>:  
Attempting write out-  
of-range value  
<WrongValue> into  
Item <ItemName>  
(<Pointer to  
Item_Class_Obj.>),  
clamp to <Clamped  
Value>.  
application tries conditions could  
to write the  
value, invalid  
for current Item Item, for example,  
happen writing new range.  
value into specific  
type.  
BCD Item, when  
invalid value “path  
through” standard  
clamping methods .  
Note: Please contact Klinkmann Support ([email protected]) if you face any other  
error messages with Log Flag “Error”.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
57  
Server-Specific Error Codes  
There are following server-specific error codes, shown in the table, that augment those  
provided by the DAS Toolkit.  
Error code Logger Message  
Log Flag  
-10002  
-10003  
-10004  
PLC timeout  
No Eth. Socket created DASProtFail  
PLC Fatal Error(*) DASProtFail  
DASProtFail  
Note: Error code can be monitored in client application as Item’s $SYS$ErrorCode  
value, correspondingly Logger Message can be monitored as Item’s $SYS$ErrorText  
value.  
(*) Fatal Error is set, if one of the following occasions permanently take place:  
-
-
mismatch of command codes in DAServer request and PLC’s response messages,  
controller response contains response error code with either Relay Error Flag (bit  
#7 in response’s MRC) set to ON, or PC Fatal Error Flag (bit #7 in response’s SRC) set to  
ON.  
FINS Response Codes  
Additionally, there are FINS command response codes (Main response code MRC and  
Subcode SRC), generated by OMRON controllers, useful for communication  
troubleshooting. The following is example of error logging created by Omron Ethernet  
DAServer:  
FINSSocket1.CV500: FINS command 0101 failed (error code 1101). Parameter error:  
an incorrect memory area or unavailable expansion mem. area has been used.  
In above example FINS command response code (1101) is to be interpreted as following:  
MRC is 11 hex, SRC – 01 hex.  
The accompanying table shows response codes, the server-specific strings generated by  
the DAServer to the logger, as well as recommended remedies. (Suggestions usually  
deals with configuring of OMRON PLC and/or FA network, yet several errors could be  
caused by Omron Ethernet DAServer configuration errors).  
Main Code Sub- Probable Cause  
Remedy  
Log Flag  
(Hex)  
code  
(Hex)  
00  
00  
00  
01  
Normal completion  
-
-
Service was  
interrupted.  
Check transmission  
area.  
DASProtWarn  
01: Local  
node error  
01  
02  
Local node not part of  
network.  
Add to network.  
DASProtFail  
DASProtFail  
Token time-out, node  
Set the local node’s  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
58  
number too large.  
number below the  
maximum node number.  
03  
05  
Send error caused by  
lack of available space Ethernet Unit. Check  
in PLC internal buffers. user application.  
Reduce the traffic on the DASProtFail  
Node number setting  
error.  
Make sure the node  
number is within  
DASProtFail  
specified range and that  
there are no duplicate  
node numbers.  
06  
Node number  
duplication error.  
Make sure that there are DASProtFail  
no duplicate node  
numbers.  
02: Remote 01  
node error  
IP address of remote  
node was not set  
Set IP address of remote DASProtFail  
node into IP address  
correctly in IP address table, and, if  
table or IP router table. internetwork  
transmission is required,  
into IP router table.  
02  
05  
No node with the  
specified unit address. node’s unit address and  
make sure the correct  
Check the remote  
DASProtFail  
DASProtFail  
one is being used in the  
control data.  
Message packet was  
corrupted by  
Check the protocol and  
controller status by  
transmission error or  
response time-out  
(response watchdog  
reading them with FINS  
commands. Increase the  
number of transmit retry  
timer interval too short) attempts.  
or transmission frame  
corrupted or PLC  
Increase the value for  
the response monitor  
internal reception buffer time in the control data.  
full.  
Read out the error log  
and correct as required.  
03:  
01  
02  
Error occured in the  
communications  
controler. ERC  
indicator is lit.  
Take corrective action,  
referring to  
troubleshooting  
procedures in PLC  
manual.  
DASProtFail  
DASProtFail  
Communic.  
Controller  
error  
CPU error occured in  
the PC at the  
destination node.  
Check the CPU  
indicators at remote PLC  
and clear the error in the  
CPU (refer to the PLC’s  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
59  
operation manual)  
04  
01  
Node number setting  
error.  
Make sure the node  
number is within  
specified range and that  
there are no duplicate  
node numbers.  
DASProtFail  
DASProtFail  
04: Not  
An undefined  
Check the command  
executable  
command has been  
code and be sure code  
used, or short frame (4 is supported by Unit to  
bytes) is being used for which command is  
FINS header frame.  
sent.(*)  
05: Routing 01  
error  
Destination node  
number is not set in the the routing tables.  
routing tables.  
Set the remote PLC in  
DASProtFail  
DASProtFail  
DASProtFail  
02  
Routing tables aren't  
registered.  
Set the the routing  
tables at the relay nodes  
and remote node.  
03  
04  
Routing table error.  
Set the the routing  
tables correctly.  
The maximum number Redesign the network to DASProtFail  
of relay nodes (2) was reduce number of relay  
exceeded in the  
command.  
nodes.  
10:  
Command  
format error  
01  
02  
03  
The command is longer Check the command  
DASProtFail  
DASProtFail  
DASProtFail  
than the max.  
permissible length.  
format and set it  
correctly.(*)  
The command is  
shorter than the min.  
permissible length.  
Check the command  
format and set it  
correctly.(*)  
The designated  
number of data items  
differs from the actual  
number.  
Check the number of  
items and data and  
make sure that they  
agree.(*)  
05  
00  
An incorrect header  
has been used. (Data  
for another node was  
received. Attempt was the correct command  
made to send response format is used.(*)  
to broadcast address)  
Check the header  
parameters in the  
command and be sure  
DASProtFail  
DASProtFail  
11:  
Parameter  
error  
The parameter in the  
command data were  
incorrect or the  
Check the parameters  
and be sure the socket  
number is between 1  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
60  
UDP/TCP socket  
number was not within  
the proper range  
and 8.  
01  
An incorrect memory  
area or unavailable  
expansion mem. area  
has been used.  
Check the command’s  
memory area code.  
Check whether right  
controller type  
DASProtFail  
configured in DAServer.  
Check whether controller  
does has polled memory  
areas.  
03  
0F  
The first address is in  
inaccessible area.  
Set the first word that is DASProtFail  
in an accessible area.  
Check whether right  
controller type  
configured in DAServer.  
22: Status  
error  
The same socket  
service is already in  
progress at the  
specified socket  
number.  
Use the socket status  
flag in PC memory to be  
sure that socket service  
has finished before  
DASProtFail  
starting services again.  
(Error deals with  
Ethernet communication  
programming in PLC’s  
user program).  
10  
05  
The specified socket is Open the socket.  
not open.  
DASProtFail  
DASProtFail  
23:  
IP address conversion Check the IP address  
Environmen  
t error  
failed.  
and subnet mask in the  
System Setup and be  
sure that settings are  
correct.  
07  
IP address conversion Check the mode settings DASProtFail  
is set for automatic  
conversion only.  
for System Setup. This  
error will be generated  
for the READ IP  
ADDRESS command  
only.  
25: Unit  
error  
03  
05  
I/O setting error. (The  
I/O table differs from  
the actual Unit  
Either change the actual DASProtFail  
configuration to match  
the registered one or  
configuration).  
generate I/O table again.  
CPU bus error. (An  
error occurred during  
Check the Units and  
cable connection and  
DASProtFail  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
61  
data transfer between  
the CPU unit and a  
CPU Bus Unit).  
issue the ERROR  
CLEAR command  
0A  
An error occured during Check the Units and  
DASProtFail  
CPU Bus Unit data  
transfer.  
cable connection and  
issue the ERROR  
CLEAR command  
Note: Refer to FINS Command’s manual if face FINS error code missed in table.  
(*) If face this type of error – contact Klinkmann Support ([email protected]),  
because reason of problem could be caused by Omron Ethernet DAServer data  
processing problems.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
62  
CHAPTER 6  
Reference  
Contents  
DAServer Architecture  
Component Environments  
DAServer Architecture  
Note: DAServers are supported on Microsoft Windows 2000 and Windows XP only.  
NetDDE protocol is not supported by DAServers.  
This DAServer is a collection of components that work in concert to provide  
communications access with hardware field devices. These components include:  
• DAServer Manager: This is the Microsoft Management Console (MMC) snap-in, that is  
part of the ArchestrA System Management Console suite of utilities, supplied with the  
DAServer. It provides the necessary user-interface  
for diagnostics, configuration, and activation.  
• Client Plug-ins: These are the components that are added to a DAServer to enable  
communications with clients. Examples are: OPC, DDE/Suitelink, and so on.  
• DAS Engine: This is the library that contains all the common logic to drive data access.  
• Device Protocol: This is the custom code provided by this DAServer to define the  
communications with a particular device.  
DAServers  
A DAServer is comprised of three physical parts (see the following figure). They are the  
following:  
• Plug-in Component(s): Responsible for communicating with clients.  
• DAS Engine: This common component is used by all DAServers.  
• PLC Protocol Layer, DAServer-specific: This component is responsible for  
communicating with the hardware.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
63  
Each physical part of a DAServer is comprised of a set of .exe and/or .dll modules.  
Wonderware provides the Plug-ins and the DAS Engine. The DAS Toolkit user creates  
the PLC Protocol Layer (DAServer-specific) modules. All three sets of modules are  
required for a fully functioning DAServer.  
Plug-ins  
Plug-ins provide a protocol-translation function for device integration clients. Typical Plug-  
ins communicate in DDE, SuiteLink, or OPC protocol, and serve as interfaces between  
their clients and the DAS Engine.  
Note: Items of an array are not supported in the DDE/SL plug-in. These arrays are  
converted to HEX strings, which provide legacy behavior for DAServers that support this  
in the DAServer-specific code.  
DAS Engine  
The DAS Engine is a middleware component that exposes two sets of unique interfaces,  
one for communicating with the Plug-ins and the other one for communicating with the  
PLC Protocol Layer components.  
PLC Protocol Layer  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
64  
The PLC Protocol Layer provides a protocol-translation function for specific hardware,  
such as OMRON FinsGateway; and it serves as an interface between the DAS Engine  
and the hardware.  
Component Environments  
Stand-alone DAServers have the following characteristics:  
The DAS Engine is dynamically linked to the other DAServer components. In other  
words, a new DAS Engine (feature enhancement or bug fix) would not require relinking to  
the other components nor re-QA of those other components. When deployed to the  
system, the new DAS Engine would attach to all existing DAServer components.  
Newly deployed Plug-ins (feature enhancements or bug fixes) do not require relinking  
nor re-QA of associated components. Even new Plug-ins (for example, OPC Alarm &  
Events) would not require any development  
changes to the other components, and therefore no relinking in a customer-installed  
base. In fact, it is feasible to implement new functionality in a Plug-in to enhance the  
DAServer without any involvement of the code of  
the other components.  
DAServers can be configured in one stand-alone configuration utility (DAServer  
Manager), and the DAServer Managerand is capable of displaying specific configuration  
views for all DAServers. This utility allows the browsing and editing of DAServers on  
different nodes.  
The DAServer Manager diagnostics tool displays generic diagnostic objects common to  
all DAServers, in addition to the DAServer-specific/DAServer-developer-defined  
diagnostic data. The DAServer data configuration format is XML. Any XML-enabled  
program (for example, XML Editor) can read this format.  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Klinkmann Automation Omron Ethernet DAServer  
65  
KLINKMANN AUTOMATION  
Omron Ethernet Direct DAServer  
Revision History  
Mar 2005  
Dec 2005  
Rev 1.0  
Rev 1.1  
First Release  
“Computer Node” Address removed from  
CONTROLLER Object parameters configuration.  
“Gateway Count (GCT)” field added into  
CONTROLLER Object parameters configuration.  
Support for CS1/CJ1 Extended Memory bank 0 to bank  
C (in Hex), up to 13 banks, added.  
Oct 2007  
May 2009  
Rev 1.2  
Rev 1.3  
Omron Ethernet DAServer Ver 1.x User Manual Rev 1.3  
17014m13  
Download from Www.Somanuals.com. All Manuals Search And Download.  

NetComm Network Router YML O 3G19W User Manual
Niles Audio Stereo Amplifier C5 A2WM User Manual
Niles Audio Universal Remote RCA3 User Manual
Nilfisk Advance America Automobile 56380676 User Manual
Numark Industries DJ Equipment DM1190 User Manual
Oregon Scientific Stud Sensor THGN800 User Manual
Oricom Two Way Radio PMR888 User Manual
Panasonic Marine GPS System KX TD7590CE User Manual
Panasonic Network Card 2SB1462J User Manual
Parker Hannifin Stereo Amplifier EC106 User Manual