| 	
		 MODEL 94NC   
					NON-CATALYTIC UNIT   
					Buck Stove   
					FIREPLACE INSERT & FREESTANDING   
					FEATURES   
					PREPARATIONS   
					INSTALLATION   
					OPERATION MAINTENANCE   
					SAFETY   
					SAFETY NOTICE   
					IF THIS HEATER IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY   
					RESULT. FOR YOUR SAFETY, FOLLOW THE INSTALLATION INSTRUCTIONS.   
					CONTACT THE AUTHORITY HAVING JURISDICTION (SUCH AS MUNICIPAL   
					BUILDING DEPARTMENT,   
					FIRE   
					DEPARTMENT,   
					FIRE   
					PREVENTION   
					BUREAU, etc.) CONSULT BEFORE INSTALLATION TO DETERMINE THE NEED   
					TO OBTAIN A PERMIT. KEEP THESE INSTRUCTIONS FOR FUTURE USE.   
					TESTED AND LISTED BY:   
					ITS/WARNOCK HERSEY, MIDDLETON, WI   
					MANUFACTURED BY NEW BUCK CORPORATION   
					200 ETHAN ALLEN DRIVE   
					P.O. BOX 69   
					SPRUCE PINE, N.C. 28777   
					
					Revised August 2010   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TABLE OF CONTENTS   
					Important Instructions ............................................................................2   
					SECTION I: Introduction.......................................................................3   
					Type of wood and loading procedures ...................................................3   
					Parts List.................................................................................................4   
					SECTION II: Masonry Insert Installation ..............................................5   
					Installation Preparation-Fireplace ..........................................................6   
					Mounting Trim Panels............................................................................7   
					SECTION III: Residential Freestanding Installation............................11   
					Floor Protection....................................................................................12   
					Installing thimble through combustible wall.......................................14   
					Final Check ..........................................................................................18   
					Clearances: Residential / Single Wall pipe...........................................19   
					SECTION IV: Wood Heater Safety......................................................20   
					SECTION VI: Operation......................................................................21   
					Room Air Blower Operation ................................................................22   
					SECTION VII: Troubleshooting ..........................................................23   
					Warranty...............................................................................................26   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION, OPERATION, AND   
					MAINTENANCE INSTRUCTIONS   
					MODEL 94NC   
					BEFORE INSTALLING YOUR NEW BUCK STOVE,   
					READ THE ENTIRE INSTRUCTION MANUAL   
					IMPORTANT INSTRUCTIONS   
					WARNING   
					THIS UNIT GENERATES A LOT OF HEAT, SO TREAT IT WITH CARE. HOT   
					WHILE IN OPERATION! KEEP CHILDREN, CLOTHING AND FURNITURE AWAY.   
					CONTACT MAY CAUSE SKIN BURNS.”DO NOT USE CHEMICALS OR FLUIDS TO   
					START THE FIRE.” “DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS.” DO   
					NOT CONNECT TO ANY DISTRIBUTION DUCT OR SYSTEM. READ ALL   
					INSTRUCTIONS BEFORE INSTALLING AND USING THE APPLIANCE. FAILURE   
					TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY   
					INJURY OR EVEN DEATH.   
					REFERENCES.   
					SAVE THESE INSTRUCTIONS FOR FUTURE   
					 The New Buck Corp. non-catalytic Model 94NC has been tested and listed by ITS,   
					(Warnock Hersey) to ANSI/UL Standards, :UL1482(2000) :UL1482(2006) :UL1482   
					(2010) Standard for Room Heaters, Solid Fuel Type.   
					 Install and operate your unit according to instructions provided in this manual. Local   
					building codes may apply; therefore, contact your local building inspector or fire marshal   
					for necessary installation requirements and permits which may go beyond these   
					instructions. Contact your insurance company for coverage and installation inspection.   
					 “DO NOT INSTALL IN SLEEPING ROOMS.”   
					 NOTE: When burning any unit or appliance that combusts fuel for heat, such as   
					coal, oil, wood or natural and (L.P.) liquid petroleum gas. We highly recommend the   
					use of smoke and carbon monoxide detectors in your home.   
					 Examine the masonry fireplace and chimney prior to installation of fireplace accessory to   
					determine that construction meets the minimum fireplace construction requirements   
					illustrated in instructions, that it is free from cracks, loose mortar, creosote deposits and   
					other blockage or other signs of deterioration.   
					CAUTION   
					DO NOT USE MORE THAN ONE STOVE TO A CHIMNEY. DO NOT USE A FLUE   
					INTENDED FOR A GAS APPLIANCE.   
					Page 2   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CAUTION   
					YOUR CHIMNEY OR FLUE MUST BE CORRECTLY SIZED. A CHIMNEY OR FLUE   
					THAT IS TOO SMALL OR LARGE IN DIAMETER OR TOO SHORT, CAN CAUSE   
					YOUR STOVE TO SPILL SMOKE WHEN THE DOOR IS OPENED.   
					SECTION I   
					INTRODUCTION   
					Your new MODEL 94NC is a non-catalytic unit designed to meet the most stringent emissions   
					standards without use of a catalytic combustor. This effect is achieved through use of   
					secondary air which is mixed with primary air in unit’s firebox.   
					For peak performance, we suggest the use of natural seasoned hard wood, loading wood   
					length way from front to rear.   
					NOTE: Soft woods such as pine, create more creosote, clogging of chimney and produce a less   
					efficient burn performance.   
					You should not burn trash or garbage, artificial or paper logs, gift wrapping, treated or   
					painted wood or any type of coal or flammable fluids.   
					The primary air, which is controlled by user, burns the wood. Secondary air is admitted into   
					firebox through secondary air tubes at top of the firebox. This secondary air burns impurities   
					in smoke released from initial wood burning. The temperature necessary for this combustion   
					is maintained through firebrick refractory. If any more technical information is necessary,   
					contact your local dealer.   
					Under specific test conditions this heater has been shown to deliver heat at rates ranging from   
					approximately :   
					11,900 BTU/HR. on Low   
					42,100 BTU/HR. on High   
					This unit is equipped with a standard room air blower.   
					Page 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EPA COMPLIANCE STATUS   
					The Model 94NC heater meets U.S. Environmental Protection Agency’s Emission limits for non-   
					cat wood heaters sold after July 1, 1992. Under specific conditions this heater has been shown to   
					deliver heat at rates ranging from approximately11,900to42,000BTU/hr for the Model 94NC.   
					MODEL 94NC   
					WOOD STOVE   
					(4)   
					(39)   
					(15)   
					(41)   
					(5)   
					(16)   
					(7)   
					(1)   
					(32)   
					(37) & (38)   
					(22)   
					(42)   
					(20)   
					(33)   
					(17)   
					(21)   
					(30)   
					(31)   
					(18)   
					(14)   
					(23)   
					(19)   
					(40)   
					(3)   
					(10)   
					(27)   
					(25)   
					(13) (28) (34)   
					(9)   
					(26)   
					(8)   
					(36)   
					(29)   
					(11)   
					(24)   
					(2)   
					(35)   
					(12)   
					1. Secondary air tubes   
					15. Pipe stop   
					16. Outer top   
					17. Door glass   
					18. Glass clips   
					19. Hearth   
					20. Door gasket   
					21. Side glass   
					22. Side glass gasket   
					23. Firebrick   
					29. Ash pan   
					30. Bay side overlay   
					31. Door handle & spring handle   
					32. Top air wash   
					33. Cast door glass gasket   
					34. Cover door hinge   
					35. Magnet holder   
					36. Cover door Magnet   
					37. Door latch   
					2. Blower control (rheostat)   
					3. Primary air control   
					4. Warm air outlets   
					5. Baffles (interior of stove)   
					6. Air inlet   
					7. Cast Door   
					8. Hearth extension   
					9. Power cord   
					10. Disc thermostat   
					11. Motor guard screen   
					12. Automatic/off/man. switch   
					24. Motor   
					25. Motor mount bracket   
					26. Cover Door   
					38. Door latch screw   
					39. Top baffle board   
					40. Hinge pins   
					13. Bottom secondary air channel 27. Cover door screws   
					14. Hinge Block   
					28. Shot gun air box   
					41. 8" Flue exit   
					42. Hinge cap   
					Page 4   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SECTION II   
					MASONRY INSERT INSTALLATION   
					The Model 94NC may be installed using an all masonry fireplace built in accordance with   
					Uniform Building Code and National Fire Protection Association (NFPA). The first step in   
					this type of installation is to determine acceptability of fireplace and chimney for use with   
					a woodstove.   
					Both   
					construction and condition of fireplace are important consid-   
					erations when installing a woodstove. The chimney should extend at least 3' above roof and   
					at least 2' above any point of roof within 10'.   
					CAUTION   
					REMEMBER TO HAVE YOUR CHIMNEY INSPECTED FOR LEAKS AND BLOCKAGE   
					BEFORE YOU INSTALL YOUR STOVE. “DO NOT CONNECT THIS UNIT TO A   
					CHIMNEY FLUE SERVING ANOTHER APPLIANCE.”   
					MINIMUM CLEARANCE MASONRY INSERT   
					MODEL 94NC   
					E 
					F 
					A. Side Wall Combustible   
					B. Front Floor Protector   
					C. Side Floor Protector   
					D. Side Wood Trim   
					E. Top Wood Trim   
					F. Mantel or Brackets   
					12"   
					16"   
					8"   
					10"   
					18"   
					24"   
					D 
					B 
					C 
					A 
					1. The hearth must be of masonry construction and must extend a minimum of 16" in front of   
					firebox opening and a minimum of 8" to either side of firebox opening.   
					Minimum floor protection under unit must have an R-value of 0.30.   
					2. If there is not minimum hearth protection from front of firebox opening and front of   
					masonry hearth, a floor protector must be used in front of hearth to protect combustible   
					materials. The floor protector must be 3/8" minimum thickness non-combustible material   
					or equivalent.(See Page 12,13).   
					Page 5   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				POSSIBLE TOOLS NEEDED FOR INSTALLATION   
					If you decide to install your own stove, there are several hand tools you may need to do the job.   
					If you do not already have them, they are readily available at most hardware stores.   
					Caulking gun   
					Large adjustable wrench (may not be needed)   
					Drop cloths or newspapers   
					Vacuum cleaner or whisk broom   
					Flashlight   
					1 tube of RTV silicone, Code 103 or 106, or high temperature rubber cement rated between 450o   
					F- 600o F   
					7/32" drill bit and drill   
					Socket/Ratchet Set   
					INSTALLATION PREPARATION   
					Fireplace:   
					1. Locate furniture and other materials away from front of fireplace to allow free access to   
					fireplace.   
					2. Cover hearth and adjacent floor areas with a drop cloths to protect from soiling or marring   
					surface.   
					3. Remove existing fireplace damper plate.   
					4. Thoroughly clean fireplace of ashes and soot.   
					5. Check chimney and smoke chamber for excessive buildup of creosote or soot. Also, check   
					for obstructions, such as bird’s nests. If chimney is excessively dirty, clean it or have   
					someone clean it professionally BEFORE installing or using room heater.   
					6. If fireplace has an ash dump or outside air provision, these must be sealed off with metal or   
					tightly packed non-combustible insulation to prevent cold air from entering fireplace   
					chamber.   
					MASONRY INSERT INSTALLATION   
					INSTALLATION OPTIONS   
					This unit (appliance) may be installed into an all masonry fireplace, built in accordance with   
					Uniform Building Code and National Fire Protection Association (NFPA 211).   
					NOTE: Check with local building officials for any permits required for installation of this unit   
					and notify your insurance company before proceeding with installation   
					Improperly drawing fireplaces, oversize flue liners or to meet codes in certain areas it is recom-   
					mended that one of the flowing procedures be followed.   
					A. A Chimney Connector be installed from appliance flue exit through damper with an air   
					-tight face seal. See option (A) Figure 2, page 7.   
					B. A listed Direct Connect be installed from appliance flue exit through damper into first   
					section of flue liner with an air-tight seal. See option (B) Figure 3, page 7.   
					C. A Positive Connect be installed from appliance flue exit continuing up through entire   
					chimney and exiting at top of the chimney. See option (C) Figure 4, page 7.   
					Page 6   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				OPTION (A) Figure 2,   
					AIRTIGHT INSU-   
					LATED CLEAN-   
					STARTER PIPE   
					OUT   
					SEAL TRIM PANELS AND UNDER   
					FRONT OF STOVE UNIT WITH   
					INSULATION OR HIGH   
					TEMPERATURE CAULK   
					REMOVE   
					DAMPER   
					OR WIRE   
					IT OPEN   
					NOTE: New Buck Corporation grants no war-   
					ranty, implied or stated, for the installation or   
					maintenance of your appliance, and assumes no   
					responsibility of any consequential damage(s).   
					OPTION (C) Figure 4,   
					OPTION (B) Figure 3,   
					CAP(PREVENTS   
					WATER FROM   
					ENTERING)   
					NOTE: Follow installation   
					instruction with Positive   
					Connection Kit.   
					(Kit sold separately)   
					NOTE: Follow installation instruction   
					with Direct Connection Kit.   
					(Kit sold separately)   
					FLUE   
					LINER   
					INSTALL A NON-COMBUSTIBLE   
					COVER PLATE TO PREVENT   
					WATER FROM ENTERING THE   
					CHIMNEY   
					THE LINER MUST   
					BE STAINLESS   
					STEEL CONNEC-   
					TOR OR FLEXIBLE   
					VENT. FOLLOW   
					THE LINER MANU-   
					FACTURER’S IN-   
					STRUCTIONS FOR   
					INSTALLATION   
					AND SUPPORT.   
					STAINLESS   
					STEEL   
					CHIMNEY   
					CONNEC-   
					TOR MUST   
					EXTEND 1’   
					PAST THE   
					BLOCK-OFF   
					PLATE OR   
					TO THE   
					SEAL TRIM PANELS   
					WITH INSULATION   
					OR HIGH   
					AIRTIGHT   
					INSULATED   
					CLEAN-OUT   
					FLUE LINER   
					TEMPERATURE   
					CAULK   
					AIRTIGHT   
					TRIM PANELS   
					INSULATED   
					CLEAN-OUT   
					REMOVE   
					DAMPER   
					OR WIRE IT   
					OPEN   
					REMOVE   
					DAMPER   
					OR WIRE   
					IT OPEN   
					BLOCK-OFF PLATE   
					OR DAMPER   
					ADAPTER   
					Page 7   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				INSTALLATION PROCEDURE   
					(Use a chimney connector or a Listed Direct or Positive Connect) (See Page 6).   
					POSITIONING HEATER   
					FRONT OF FIREPLACE   
					When positioning heater, the following conditions   
					MUST be met! (See Figure 5).   
					FLUE OPENING   
					1. The front of flue opening must be positioned   
					BEHIND rear edge of the lintel to ensure proper   
					draft. (See Figure 5).   
					2. Center heater in fireplace opening.   
					FIGURE 5   
					POSITIONING   
					MOUNTING TRIM PANELS   
					NOTE: Mount top trim panel so that it sits in front of   
					top of side trim panels.   
					After unit is positioned, mark mounting position of trim   
					panels as follows:   
					1. Place side trim panels flat against face of fireplace.   
					Mark down front edge of trim panel with a pencil to   
					make a vertical reference line. (See Figure 6).   
					2. Set top (long) trim panel in place on top of unit.   
					The panel should be flat against the outside face   
					of fireplace, and standing vertically. Mark along   
					lower edge of trim panel with a pencil to make a   
					reference line for mounting.   
					3. Slide unit out of fireplace far enough to work   
					FIGURE 6   
					MOUNTING TRIM PANELS   
					behind trim panel reference lines.   
					4. Mount side trim panels. (See Figure 6).   
					a. Position trim panel on reference line.   
					b. Drill mounting holes in center of trim panel mounting brackets to allow for adjustment in and out if neces-   
					sary.   
					c. Mount trim panel using self-tapping screws provided.   
					5. Place top panel back on reference mark. Take top trim panel mounting bracket supplied with unit. Position   
					bracket so it overlaps rear lip of top trim panel. Drill mounting holes in top of stove using holes in bracket as   
					guide. Tighten down screws.   
					6. Now, follow installation procedures in listed direct connect or positive connect kit you are using and install   
					heater and connect kit in fireplace. If not using one of installation methods shown on (Page 7), continue.   
					7. Slide unit back into fireplace. Check to be sure that trim panels are properly positioned and lie flat against   
					front of fireplace. If one or more of panels is out of position, slide unit out and reset by loosening the   
					mounting screws and repositioning in the slot. Reinstall top trim panel by sliding rear lip of top trim panel   
					underneath front lip of mounting bracket already secured to top of unit.   
					Page 8   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				8. Obtain outer trim kit provided with insert kit and slip over top and sides of trim panels.(See Figure 7). (Top   
					ends of outer trim may need to be trimmed to fit).   
					9. Using insulation provided, peel and stick to back of panels overlapping fireplace dimensions by 1" on each   
					side and top. (See Figure 8).   
					10. Next using high heat silicone or furnace cement run heavy bead of caulking around where back of panels meet   
					stove. (See Figure 8).   
					11. Slide unit back into fireplace. Check to be sure that trim panels (and outer trim) are properly positioned and   
					lie flat against front of fireplace. If panels are out of position, slide unit out and reset by loosening mounting   
					screws and repositioning in slot. With bar lift stove up in front. Place insulation across front at bottom and   
					surface of hearth or bottom of fireplace to make complete seal.   
					12. To check seal of panels, use candle flame and go around entire area sealed by silicone and insulation. If flame   
					leans toward inside of fireplace, add additional insulation. This ensures an airtight seal.   
					Outer Trim   
					FIGURE 7   
					FIGURE 8   
					Top Trim Panel   
					INSULATION   
					Buck Stove   
					Side Trim Panel   
					Primary Air Control   
					FINAL CHECK   
					1. Recheck specified clearances.   
					2. Remove all foreign material from firebox area.   
					3. Open primary air control.   
					Primary Air Control: The primary air intake draft control is located at right bottom side of hearth. It is   
					operated by moving handle out to open (to allow air into firebox) or in (to control or close off) air into   
					firebox. (See Figure 7).   
					4. Plug power cord into a 115V AC outlet. “Do not run cord under unit or in high traffic areas.   
					5. Place crumpled pieces of newspaper in stove. Light it and close door. Ensure that stove draws properly   
					through primary draft.   
					NOTE: “Do not use grate or elevate fire. Build wood fire directly on fire box bottom.”   
					6. Check for smoke leaks around door.   
					7. Open door and check for smoke escaping from front of stove. Smoking usually indicates a defective or poorly   
					positioned chimney. Some chimneys with a marginal draft can be pre-heated by lighting newspaper and   
					holding it near open damper with a poker or fire tong. Once chimney heats up, a proper draft can usually be   
					obtained.   
					If a thorough review of Troubleshooting Guide in rear of manual does not reveal   
					problem, contact your dealer for assistance.   
					Page 9   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CAUTION   
					THE UNIT IS PAINTED WITH   
					A 
					SPECIALLY FORMULATED HIGH   
					TEMPERATURE PAINT THAT CURES DURING THE FIRST TWO OR THREE   
					FIRINGS. YOU MAY NOTICE A SLIGHT SMOKING EFFECT AND AN ODOR OF   
					BURNING PAINT WHEN YOU BUILD THE FIRST FIRES. THIS IS NORMAL AND   
					IS NOT A CAUSE FOR ALARM. IN SOME CASES, THESE FUMES WILL   
					ACTIVATE A SMOKE ALARM. OPENING A WINDOW NEAR THE UNIT WILL   
					ALLOW THESE FUMES TO ESCAPE. DO NOT BUILD A LARGE, ROARING FIRE   
					UNTIL THIS CURING IS COMPLETE OR THE HEATER FINISH MAY BE   
					DAMAGED.   
					The connector and/or chimney should be inspected at least once a month during the heating   
					season to determine if a creosote buildup has occurred.   
					CAUTION   
					NEVER USE GASOLINE, GASOLINE-TYPE LANTERN FUEL, KEROSENE,   
					CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR "FRESHEN   
					UP" A FIRE IN THE HEATER. KEEP ALL SUCH LIQUIDS WELL AWAY FROM   
					THE STOVE WHEN IT IS IN USE. ALL FLUIDS OF THIS TYPE GIVE OFF   
					VOLATILE FUMES AND CAN AND WILL EXPLODE!! DON'T TAKE A CHANCE   
					WITH THE SAFETY OF YOUR HOME AND FAMILY.   
					Page 10   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SECTION IV   
					RESIDENTIAL FREESTANDING   
					INSTALLATION   
					Select an installation location that will give best airflow from front of heater to   
					remainder of home.   
					PREPARING STOVE FOR INSTALLATION   
					1. Inspect unit for any obvious physical damage.   
					2. Plug power cord into a 115V AC outlet to test motor. “Do not run power cord under unit or   
					in high traffic areas”.   
					3. Check primary air and control to ensure that it slides freely.   
					4. Remove any items from within firebox. Spread a dropcloth on floor behind heater.   
					Next, tilt heater so that back is on drop cloth.   
					5. If leg kit is to be used follow steps 1-4.   
					6. Then obtain four legs, attach legs to holes in bottom of unit with bolts and washers supplied   
					with leg kit. (See Figure 9).   
					7. Reposition heater to upright position.   
					Figure 9   
					Page 11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Chimney   
					This model is designed for connection to any listed 2100º UL103 HT chimneys and parts.   
					Follow chimneys manufacturer's instructions carefully.   
					This room heater must be converted to (1) a chimney complying with the requirements for   
					Type HT chimneys in the Standard for chimneys, Factory-Built, Residential, Type and   
					Building Heating Appliance, UL 103, or (2) a code approved masonry chimney with a flue   
					liner. The chimney size should not be less than or more than three times greater than the cross-   
					sectional area of the flue collar.   
					Floor Protection:   
					Floor protection must be 3/8” minimum thickness non-combustible material or equivalent, and   
					have an R-value of 0.30.   
					How to use alternate materials and how to calculate equivalent thickness   
					An easy means of determining if a proposed alternate floor protector meets requirements listed   
					in the appliance manual is to follow this procedure:   
					1. Convert specification to R-value:   
					R-value is given—no conversion is needed.   
					K-factor is given with a required thickness (T) in inches:   
					C-factor is given: R=1/C   
					2. Determine the R-value of the proposed alternate floor protector.   
					Use the formula in step (1) to convert values not expressed as “R”   
					For multiple layers, add R-values of each layer to determine the overall R-value.   
					3. If the overall R-value of the system is greater than the R-value of the specified floor   
					protector, the alternate is acceptable.   
					Example:   
					The specified floor protector should be 3/4” thick material with a K-factor of 0.84.   
					The proposed alternate is 4” brick with a C-factor of 1.25 over 1/8” mineral board with a   
					K-factor of 0.29.   
					Step (a): Use formula above to convert specification to R-value. R= 1/K x T = 1/0.84 x .75 =   
					0.893   
					(Continued on next page)   
					Page 12   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Step (b): Calculate R of proposed system. 4” brick of C=1.25, therefore Rbrick = 1/C = 1/1.25   
					=0.80 1/8” mineral board of K = 0.29, therefore Rmin.bd. =1/029 x0.125 = 0.431   
					Step (c): Compare proposed system R of 1.231 to specified R of 0.893. Since proposed   
					system R is greater than required , the system is acceptable.   
					Definitions:   
					Btu   
					(hr)(ft²)(°F)   
					W 
					(m²)(°K)   
					= 
					= 
					= 
					Thermal conductance = C =   
					Thermal conductance = K =   
					Thermal conductance = R =   
					(Btu)(inch)   
					(hr)(ft²)(°F)   
					W 
					(m)(°K)   
					(Btu)   
					(hr)(ft)(°F)   
					= 
					(ft²)(hr)(°F)   
					Btu   
					(m²)(°K)   
					W 
					Install in accordance with 24 CFR, Part 3280 (HUD).   
					CAUTION   
					SPECIAL METHODS ARE REQUIRED WHEN PASSING THROUGH A   
					WALL OR CEILING. SEE INSTRUCTIONS AND BUILDING CODES.   
					“DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING   
					ANOTHER APPLIANCE.”   
					DETERMINING CHIMNEY LOCATION   
					A. CEILINGEXIT (Using 8” inch Diameter Residential Single Wall (minimum 24-ga.)   
					Black Chimney Connector and any listed 2100 UL 103 HT type Chimney System ).   
					(See Page 14).   
					1. Suspend a plumb bob from ceiling above unit so that weight is hanging in center of   
					flue exit. (A small weight on a string will serve as a plumb bob). Mark ceiling where   
					string is suspended to locate center of chimney.   
					2. After locating center of hole, install ceiling support box, chimney flashing and rain   
					cap per chimney manufacturer’s instructions.   
					Now connect stove and ceiling support box using #24 ga. minimum blue or black steel   
					connector pipe (DO NOT USE GALVANIZED PIPE). Connect each section so crimped   
					end faces downward, and secure each section to each other using at least three (3) sheet   
					metal screws or rivets. Also use three (3) sheet metal screws to fasten pipe to collar on heater.   
					(See Figure 10. Page 15).   
					Page 13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installing a thimble through combustible wall   
					Chimney Connector Systems and Clearances from Combustible Walls for Residential Heating Appliances   
					a) Minimum 3.5-in thick brick masonry all framed into   
					combustible wall with a minimum of 12-in brick   
					separation from clay liner to combustibles. The   
					fireclay liner shall run from outer surface of brick wall   
					to, but not beyond , the inner surface of chimney flue   
					liner and shall be firmly cemented in place.   
					b) Solid-insulated factory-built chimney length of the   
					same inside diameter as chimney connector and   
					having 1-in. or more of insulation with a minimum 9-in.   
					air space between outer wall of chimney length and   
					combustibles.   
					c) Sheet steel chimney connector, minimum 24 gauge in   
					thickness, with a ventilated thimble, minimum 24   
					gauge in thickness, having two 1-in. air channels,   
					separated from combustibles. by a minimum of 6-in. of   
					fiber insulation. Opening shall be covered, and thimble   
					supported with a sheet steel support, minimum 24   
					gauge in thickness.   
					d) Solid insulated, listed factory-built chimney length with   
					an inside diameter 2-in. larger than chimney   
					connector and having 1-in. or more of insulation,   
					serving as a pass-through for a single wall sheet steel   
					chimney connector of minimum 24 gauge thickness,   
					with a minimum 2-in. air space between outer wall of   
					chimney section and combustibles. Minimum length of   
					chimney section shall be 12-in. chimney section   
					spaced 1-in. away from connector using sheet steel   
					support plates on both ends of chimney section.   
					Opening shall be covered, and chimney section   
					supported on both sides with sheet steel supports   
					securely fastened to wall surface of minimum 24   
					gauge thickness. Fasteners used to secure chimney   
					section shall not penetrate chimney flue liner.   
					Page 14   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				ROOF   
					CEILING   
					COLLAR   
					3 SHEET METAL SCREWS OR RIVETS   
					3 SHEET METAL SCREWS   
					Figure 10   
					ATTIC   
					18" MIN.   
					CEILING   
					TEE BOX ASSEM.   
					CENTER LINE   
					OF ELBOW   
					CLEAN OUT ACCESS   
					WALL PASS-THROUGH CONNECTOR   
					MARK PLUMB LINE   
					WALL   
					FLOOR PROTECTOR   
					Figure 11   
					B. Wall Exit Into Metal Tee-Box   
					1. Mark plumb line on wall directly behind center of heater. (See Figure 11).   
					NOTE: When using 24# ga. minimum blue or black steel pipe, maintain 18" between   
					pipe and ceiling.   
					NOTE: Floor protector must be under horizontal pipe exit (See Figure 13. Page 19).   
					2. Place vertical portion of heater pipe and elbow in position and project a point onto   
					plumb line level with center of elbow.   
					Page 15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				3. Measure up so there will be at least 1/4" rise per foot of horizontal connector pipe,   
					maintaining clearances to ceiling as noted in (Figure 12). This will give you center   
					of hole for chimney penetration.   
					4. After locating center of penetration, install tee-box and chimney as per chimney   
					manufacturer's specifications.   
					5. Connect chimney connector to tee-box using #24 ga. minimum blue or black steel   
					connector pipe. DO NOT use galvanized pipe. Connect each section so crimped end   
					faces downward, and secure each section to each other using three (3) sheet metal screws or   
					rivets. (See Figure 10. Page 15).   
					C. Wall Exit Into Masonry Flue (Using Single Wall Pipe)   
					1. Before connecting these units to a masonry chimney, determine that masonry flue pass-   
					through connector thimble meets NFPA-211 Code and local building codes and is   
					a minimum of 18" from ceiling. If connector thimble does not meet these codes, pass   
					-through connector must be modified.   
					NOTE: Floor protector must be under horizontal pipe exit (See Figure 13. Page 19).   
					CEILING   
					CENTER LINE   
					OF ELBOW   
					1/4” RISE PER FT’   
					MARK PLUM LINE   
					SECURE WITH (3)   
					SHEET METAL SCREWS   
					SEAL AROUND PIPE TO   
					THIMBLE OR PASS-   
					THROUGH CONNECTOR   
					WITH NON-COMBUSTIBLE   
					MATERIAL   
					MASONRY   
					FLUE   
					LINERS   
					WALL   
					CLEAN OUT   
					DOOR   
					Figure 12   
					FLOOR PROTECTOR   
					See Figure 13. Page 17.   
					MASONRY CHIMNEY   
					Page 16   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Connectors may pass through walls or partitions constructed of combustible material if   
					connector is:   
					(a) Either listed for wall pass-through or is routed through a device listed for wall pass-   
					through and is installed in accordance with conditions of listing.   
					(b) Selected or fabricated in accordance with conditions and clearances as stated   
					in NFPA-211 Code. Any unexposed metal that is used as part of a wall pass-through   
					system and is exposed to flue gases shall be constructed of stainless steel or other   
					equivalent material that will resist corrosion, softening or cracking from flue gases at   
					temperatures up to 1800o F.   
					In addition, a connector to a masonry chimney shall extend through wall to the inner face   
					or liner but not beyond, and shall be firmly cemented to masonry.   
					EXCEPTION: A thimble may be used to facilitate removal of the chimney connector for   
					cleaning, in which case the thimble shall be permanently cemented in place   
					with high-temperature cement.   
					2. Once through-the-wall thimble codes are met, simply connect chimney collar to wall pass-   
					through connector using #24 ga. minimum, blue or black steel connector pipe as follows:   
					(a) Maintain 1/4" rise per foot (horizontal length) from appliance to chimney.   
					(b) Connect each section so crimped end faces downward.   
					(c) Secure each section to each other using at least three (3) sheet metal screws or rivets   
					(See Figure 10. Page 15).   
					(d) Use three (3) sheet metal screws to fasten pipe to connector collar on heater.   
					(See Figure 10. Page 15).   
					Page 17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				FINAL CHECK   
					1. Recheck specified clearances.   
					2. Remove all foreign material from firebox area.   
					3. Open primary air control. Primary Air Controls: The primary air intake control is located   
					at right bottom side of hearth. It is operated by moving the handle out to open (to allow   
					air into the firebox) or in (to control or close off) air into the firebox.   
					4. Plug power cord into a 115V AC outlet when to see if motor and blower works. “Do not   
					run power cord under unit or in high traffic areas”.   
					5. Place crumpled pieces of newspaper in stove. Light it and close   
					that stove draws properly through primary draft.   
					door. Ensure   
					6. Check for smoke leaks around door.   
					CAUTION   
					Open door and check for smoke escaping from front of the stove. Smoking usually   
					indicates a defective or poorly positioned chimney. Some chimneys with a marginal draft   
					can be preheated by lighting newspaper and holding it near open damper with a poker or   
					fire tong. Once chimney heats up, a proper draft can usually be obtained.   
					If a thorough review of Troubleshooting Guide in rear of manual does not reveal problem,   
					contact your dealer for assistance.   
					CAUTION   
					The unit is painted with a specially formulated high temperature paint that cures during   
					the first two or three firings. You may notice a slight smoking effect and an odor of   
					burning paint when you build the first fires. This is normal and is not a cause for   
					alarm. In some cases, these fumes will activate a smoke alarm. Opening a window near   
					unit will allow these fumes to escape. DO NOT build a large, roaring fire until this curing   
					is complete or heater finish may be damaged.   
					Page 18   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				CLEARANCES FOR MODEL 94NC   
					MINIMUM CLEARANCES TO COMBUSTIBLES   
					RESIDENTIAL SINGLE WALL CONNECTOR   
					BACK WALL   
					F 
					B 
					C 
					H 
					D 
					D 
					E 
					G 
					A 
					A 
					Figure 13   
					A 
					B 
					C 
					D 
					E 
					F 
					G 
					H 
					MODEL 94NC   
					22”   
					23”   
					26” 23”   
					8”   
					6”   
					16” 12”   
					NOTE: All clearances are to combustibles using single wall pipe, minimum floor protector.   
					Minimum floor protection under unit must have an R-value of 0.30. (see page 12, 13)   
					NOTE: The clearances above may be reduced, follow NFPA-211 codes.   
					For wall exit, Floor protector must be under horizontal pipe the length between stove   
					and exit. Must be 2” on each side of pipe. Maintain 18" between pipe and ceiling.   
					(See Figure 13, measurements F & H ).   
					Page 19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SECTION VI   
					WOOD HEATER SAFETY   
					Certain safety hazards are inherent in any wood heater installation. You should be aware of   
					these so that a safe and proper installation can be made.   
					1. FAULTY CHIMNEY: An older masonry chimney should be thoroughly checked to be sure   
					there are no holes or weak spots which could allow sparks or hot gases to escape.   
					2. HEAT CONDUCTION: Placing combustible materials too close to a heater or chimney can   
					be a fire hazard.   
					By keeping these particular hazards in mind as you install and use your room heater you can   
					ensure a safe, reliable installation.   
					The chimney and chimney connector should be inspected once every two months. Any build-   
					up of soot should be removed to prevent the risk of a chimney fire. To remove chimney or   
					chimney connector: Remove screws or fasteners. Remove pipe and clean with steel brush.   
					Replace chimney or chimney connector, and replace screws and/or fasteners.   
					CAUTION   
					NEVER USE GASOLINE, GASOLINE TYPE LANTERN FUEL, KEROSENE,   
					CHARCOAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR "FRESHEN   
					UP" A FIRE IN THE HEATER. KEEP ALL SUCH LIQUIDS WELL AWAY FROM   
					THE STOVE WHEN IT IS IN USE. ALL FLUIDS OF THIS TYPE GIVE OFF   
					VOLATILE FUMES AND CAN AND WILL EXPLODE!! DON'T TAKE A CHANCE   
					WITH THE SAFETY OF YOUR HOME AND FAMILY.   
					CAUTION: Never remove ashes from heater with blower running.   
					DISPOSAL OF ASHES: Ashes should be placed in a metal container with a tight fitting lid.   
					The closed container of ashes should be placed on a non-combustible floor or on ground, well   
					away from all combustible materials pending final disposal. If ashes are disposed of by burial   
					in soil or otherwise locally dispersed, they should be retained in closed container until all   
					cinders have thoroughly cooled.   
					CREOSOTE-FORMATION AND NEED FOR REMOVAL: When wood is burned slowly,   
					it produces tar and other organic vapors, which combine with expelled moisture to form   
					creosote. The creosote vapors condense in the relatively cool chimney flue of a slow-burning   
					fire. As a result, creosote residue accumulates on flue lining. When ignited this creosote   
					makes an extremely hot fire.   
					Page 20   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SECTION VII OPERATION   
					This section of the manual is to help you get maximum efficiency and maximum smoke   
					(particulate) reduction from your heater. If you should experience any difficulty or have any   
					questions concerning your heater, contact your dealer for assistance. NOTE: The   
					manufacturer recommends that for maximum performance burn natural seasoned   
					hard wood.   
					Build a fire for maximum efficiency. This model burns wood and extracts heat so efficiently,   
					a large fire is not necessary. A large fire not only wastes energy, it usually results in home   
					being too warm for comfort.   
					The following steps will serve as a guide for operating your stove.   
					BUILDING A FIRE   
					1. Open door.   
					2. Open primary air control. Primary Air Controls: The primary air intake draft control is   
					located at right bottom side of hearth. It is operated by moving handle out to open (to   
					allow air into firebox) or in (to control or close off) air into firebox.   
					3. Twist two pieces of non-colored newspaper into a roll and place them on floor of firebox.   
					NOTE: “Do not use grate or elevate fire. Build wood fire directly on inner bottom of fire box.”   
					4. This model is not designed for use of grates, andirons or other methods of supporting fuel.   
					5. Lay several pieces of dry kindling on top of newspaper.   
					6. Place three or four small pieces of firewood, 2"-3" in diameter, on top of kindling.   
					7. Light newspaper in front. Close and latch door. Don't leave fire unattended at this point.   
					The draft system of heater should start quickly. It may be necessary to preheat chimney   
					to get draft started. To do this, open door and add newspaper to top rear of wood. Light   
					or let this paper ignite and allow to burn while holding the door slightly cracked. Once   
					draft has started, close and lock door. You are over- heating the unit if the chimney and or   
					connector glows red.   
					8. NOTE: After embers and a coal bed have been established, load heater with seasoned   
					natural hard wood, placing it length way front to rear.   
					NOTE: THE FUELING DOOR MUST REMAIN CLOSED DURING OPERATION.   
					BURN RATE:   
					LOW   
					1/32”   
					MED-LOW   
					5/32”   
					MED-HI   
					9/32”   
					HI   
					AIR SETTINGS:   
					WIDE OPEN   
					Your stove is equipped with a automatic thermostat. When stove gets hot enough,   
					thermostat will activate room air blower. Set fan speed on low, when burn on low, med-   
					low, med-high. Set fan speed on high when burn on high.   
					NOTE: When refueling or removing ashes turn “OFF” room air blower. Be sure to turn   
					room air blower back on when finished.   
					NOTE: Do not run power cord underneath heater or in walk way or heavy traffic areas.   
					Page 21   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				ROOM AIR BLOWER OPERATION   
					Your heater is equipped with a room air blower. For operation and wiring see figure 14.   
					For your convenience your heater is equipped with a rheostat with which you are able to select   
					air flow. The auto and manual switch will allow you to select the position at which thermostat   
					will function.   
					Figure 14   
					Auto-position: After heater has warmed up and Auto-Manual switch is placed in “Auto”   
					position and rheostat is in desired position, then fan will automatically come on. When stove   
					cools off fan will automatically shut-off.   
					Manual position: You must turn room air blower on and off.   
					NOTE: Plug power cord into a 115V AC outlet. Set switch to “Manual” and rheostat to   
					“High” position to ensure motor operates properly. Route cord to prevent damage to   
					cord insulation from heat and sharp objects. Keep cord out of the way of traffic to   
					prevent damage caused by tripping, etc.   
					Page 22   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				SECTION VIII   
					TROUBLESHOOTING   
					PROBLEM   
					POSSIBLE CAUSE   
					SOLUTION   
					Sluggish Heater   
					Obstruction in chimney   
					Check for and remove   
					obstruction   
					Improperly sealed trim kit or (a) Check trim kit gasketing   
					direct connect kit   
					seal to fireplace and   
					gasket as necessary to   
					seal unit. Gasket under   
					front bottom of stove if   
					needed.   
					(b) Check seal if using direct   
					connect and correct.   
					Manual damper in chimney is Open manual damper and   
					closed   
					wire shut with stainless steel   
					wire or remove damper   
					Wet or unseasoned wood   
					being burned   
					Burn dry, natural seasoned   
					hard wood   
					Poor chimney draft   
					Improper chimney height or   
					wrong size flue is being used.   
					Cooler temperatures caused   
					by external chimney   
					Improper wood loading   
					Load wood length way from   
					front to rear   
					Page 23   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				TROUBLESHOOTING   
					(Continued)   
					PROBLEM   
					POSSIBLE CAUSE   
					SOLUTION   
					High fuel consumption   
					Improper regulation of draft   
					or inlet air   
					(a) Close inlet air control as   
					much as possible to   
					maintain desired heat   
					output   
					(b) Check gaskets, reinstall   
					fiberglass gasketing   
					round doors and glass as   
					necessary   
					Improper door fitting   
					Gusts of Wind   
					Check door gasket, check   
					adjustment of door latch   
					Backpuffing   
					(a) Smoke shelf in chimney   
					is filled with creosote &   
					ash   
					(b) Chimney may need wind   
					diverter. Raise chimney   
					for better draft   
					Smoke rollout when heater   
					door is opened   
					Wind gusts blowing down the (a) Smoke shelf in chimney   
					chimney   
					is filled with creosote &   
					ash   
					(b) Chimney may need wind   
					diverter. Raise chimney   
					for better draft   
					Opening heater door too fast   
					Crack door for 15 seconds   
					before fully opening door   
					Page 24   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				REPLACEMENT PARTS   
					FOR MODEL 94NC   
					Description   
					1. Primary Air Handle   
					2. Door Handle Assembly   
					3. Door Latch   
					Part Number   
					PS 94NC040   
					PA 910096   
					PC 910098   
					4. Door Handle Washer   
					5. Front Door Bushing   
					6. Door   
					PO 91WASH   
					PO 910102   
					PC 912651   
					7. Carling Fan Auto/Man Switch   
					8. Thermostat 110° Disc   
					9. Power Cord   
					PE RC211RB   
					PE 400132   
					PE 400240   
					10. Strain Relief   
					PE 400320   
					11. Motor   
					PE 910714   
					12. Rheostat   
					PE BC204   
					13. Rheostat Knob   
					14. Glass   
					PE BC204A   
					PG 265191GL   
					PG 27BSGL   
					PO 910454G   
					PO 912651   
					15. Glass (Bay Side)   
					16. Bay Glass Overlay   
					17. Glass Clip   
					18. Glass Clip Screws   
					19. Spring Handle   
					PH 103212HWSPS5   
					PO 100150B   
					20. “U” Drive Screw (5/16” x 1/2”) PO 516U   
					21. Front Secondary Air Tube   
					22. Rear Secondary Air Tube   
					23. Primary Shotgun & Air Block   
					24. Top Baffle Board   
					PO 94NC010   
					PO 94NC012   
					MF 910080   
					PO BPFB94   
					PO DM841   
					PR 900050   
					PS 910105   
					25. 1” x 1” x 1/8” Thick Magnet   
					26. Firebrick   
					27. Motor Guard Screen   
					Page 25   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				NEW BUCK CORPORATION (NBC)   
					"LIMITED WARRANTY" FOR THE BUCK STOVE   
					PLEASE READ THIS WARRANTY CAREFULLY   
					PRODUCTS COVERED   
					This warranty covers the new Buck Stove heating unit, so long as it is owned by the original   
					purchaser, including optional and standard accessories purchased at the same time, subject to   
					terms, limitations, and conditions herein set out.   
					PRODUCTS NOT COVERED   
					This warranty does not cover the following:   
					Glass, Refractory material or firebrick, Gaskets.   
					This Warranty will not cover any damage and/or failure caused by abuse or improper   
					installation of the products covered.   
					WARRANTY TIME PERIODS   
					(A)Period I   
					For one year from the date of purchase, NBC will replace or repair, at its option, any   
					part defective in materials or workmanship. The costs of parts only are included. The   
					customer pays any labor or transportation charges required.   
					Thereafter,   
					(B) Period II   
					For the period after the first year from the date of purchase and extending for five years as   
					long as the Buck Stove is owned by the original purchaser, NBC will repair or replace, at   
					its option, any part defective in materials or workmanship, with the exception of:   
					electrical motors, wiring, switches, and components: optional and standard accessories;   
					and all parts not permanently attached to the heating unit. Parts not permanently attached to   
					the heating unit are defined as those items designed to be removed from the stove,   
					including those removable with common hand tools. The costs of parts only are   
					included. The customer pays any labor or transportation charges required.   
					. 
					PROCEDURE   
					Should you feel that your BUCK STOVE is defective, you should contact any Buck Stove   
					dealer for the name of your nearest authorized Buck Stove service representative, who will   
					instruct you on the proper procedure, depending on which Warranty Time Period (Period I or   
					Period II) applies.   
					Page 26   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				If for any reason you are dissatisfied with the suggested procedures, you may contact us   
					in writing at:   
					New Buck Corporation   
					Customer Service Department   
					P. O. Box 69   
					Spruce Pine, NC 28777   
					CONDITIONS AND EXCLUSIONS   
					(A) Replacement of parts may be in the form of new or fully reconditioned parts, at NBC's   
					option.   
					(B) There is no other express warranty. All implied warranties of merchantability and fitness   
					for use are limited to the duration of the Express Warranty.   
					(C) New Buck Corporation is not liable for indirect, incidental, or consequential damages in   
					connection with the use of the product including any cost or expense of providing substitute   
					equipment or service during periods of malfunction or non-use.   
					Some states do not allow the exclusion of incidental or consequential damages, so the   
					above exclusion may not apply to you.   
					(D) All warranty repairs under this warranty must be performed by an authorized Buck Stove   
					service representative. Repairs or attempted repairs by anyone other than an authorized   
					service representative are not covered under this warranty. In addition, these unauthorized   
					repairs may result in additional malfunctions, the correction of which is not covered by   
					warranty.   
					OTHER RIGHTS   
					This warranty gives you specific legal rights, and you may also have other rights, which vary   
					from state to state.   
					OWNER REGISTRATION CARD   
					The attached Owner Registration Card must be completed in its entirety and mailed within 30   
					days from the date of purchase or from the date of installation, if installed by a factory certified   
					installer, to New Buck Corporation in order for warranty coverage to begin.   
					PLEASE NOTE: The Owner Registration Card must contain the Authorized Buck Stove   
					Dealer Code Number and the Certified Installer's number (if applicable) for warranty coverage   
					to begin.   
					Warranty Card Not Available On Web And Replacement Manuals   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |