Master Lock Heating System RADIANT PANEL SYSTEM User Manual

5A. RADIANT PANEL SYSTEM®  
PLANNING & INSTALLATION MANUAL (rev)  
ROTH HEATING SYSTEMS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5A. INSTALLATION INSTRUCTIONS  
5A.1 Planning  
Roth Radiant Panel Systems® can be installed on all types of sub-floors, which comply with the  
current building regulations for load-bearing structures. If the system is going to be installed upon an  
existing surface material (e.g. vinyl mat, ceramic tiles, etc.), it must be approved by the flooring  
contractor.  
The floor panel system has a normal operating range of 60-140°F (15-60°C), depending on the  
radiant heating system design and finished floor material. Underlayment, vapor barriers, water-  
proof membranes, etc. should be selected with the actual operating temperatures in mind. Be  
sure to discuss the design parameters with the flooring contractor prior to installation.  
Before starting the installation, you need to plan your loop layout and manifold locations. We also  
recommend installing tubing in every track to achieve the best heat distribution.  
Try to plan the pattern so that the Master Panels are aligned to allow the loop supply to run along  
the outer wall. If installing a wood floor over the panel, align the panel so the loops are running in  
the opposite direction of the wood flooring material.  
In wet areas, such as bathrooms, etc., where a water-tight layer is requested, the membrane  
should be installed above the panel system. Always coordinate these installations with the  
flooring contractor.  
5A.2 Delivery Content  
The Roth Radiant Panel System® is delivered in one box consisting of:  
Master Panels,  
10 pcs., 24" x 48"  
PLEASE NOTE:  
Panel System for ” tubing is ¾” thick.  
Panel System for ½” tubing is 1” thick.  
Radius Panels,  
3 pcs., 16" x 24"  
Each panel is perforated and can easily be  
snapped into 2 pieces (total of 6 pieces).  
Transition Panels,  
3 pcs. 16" x 24"  
Each panel is perforated and can easily be  
snapped into 4 pieces (total of 12 pieces).  
5A1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5A. INSTALLATION INSTRUCTIONS  
5A.3 Installation of the Panel  
The sub-floor must be smooth, clean and level. Surface irregularities should not exceed more  
than 0.02" per foot. The Roth Radiant Panel System® should be secured to the subfloor with  
countersunk screws or a foam board compatible adhesive. Apply the adhesive according to the  
manufacturer’s instructions.  
Start the installation by laying the radius panel first. If you need an extra track you can start with a  
transition panel. A strip of plywood can be installed on the perimeter for tack strip when carpet is  
the finished floor material. It is important to plan the installation in advance to be sure that you  
have the correct number of tracks when installing the tubing. Transition and radius panels can  
be installed upside down as filler pieces.  
When securing the panels to a wood subfloor, we recommend using at least eight (8) countersunk screws spaced 12” (30 cm)  
apart and 6” (15 cm) from the edges. When installing over concrete, you can use countersunk concrete fasteners in the same  
pattern. Be aware that floor conditions may require use of additional fasteners. The panels can also be secured with latex base  
adhesives compatible with foam board products. These are applied with either a caulking gun or notched trowel. Follow the  
manufacturer’s instructions for application. Curing time can vary widely between brands of adhesive and with the temperature  
and humidity conditions at the time of installation.  
5A 2  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5A. INSTALLATION INSTRUCTIONS  
Continue to lay the master panels. When  
cutting the master panels, mark the plate and  
saw it with EPS side up. You can use any  
saw with a fine-toothed metal blade. After  
cutting the panel, remove any burrs. When  
cutting the last master panel in the first row,  
use the rest of the panel to start the next  
row. This will provide staggered joints for the  
field panels.  
After completion of the panel installation in an area, use a vacuum to clean up thoroughly  
before installing the tubing. Dirt and debris in the tracks can create noise when the system is  
put into operation.  
5A 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5A. INSTALLATION INSTRUCTIONS  
5A.4 Installation of PEX-tubing  
Start the tubing installation by connecting  
the PEX tubing to the manifold. Loops can  
be pre-cut if you have figured the correct  
leader length (from the manifold to the  
actual heated area) when designing the  
system with our software. The Radiant  
Heating Tubing Requirements Report will  
give you the information to cut the loops  
from full rolls of tubing with the least  
amount of waste.  
Install the tubes by unrolling the coil and  
stepping the tubes into the tracks in the  
panels. Use hard shoes or a wooden piece  
on top of the tubes in order to fasten the  
tubes in the tracks. Be sure to use a block  
when using a hammer or mallet to set the  
tubing to avoid denting the aluminum  
surface. Follow the loop layout you have  
planned and connect the return tube to the  
manifold. It is very important that the tubes are snapped down completely into the tracks.  
When installing the tubing in the radius panels it is important to pull the tubing tightly around the  
bends. This will allow a space for tubing expansion during operation and greatly decrease the  
chance of noise during operation. When laying the tubing into the transition pieces we  
recommend using a bead of silicone adhesive to secure the tubing because the tubing is loose  
in these pieces. We recommend installation of the panel and tubing when ambient  
temperatures are above 40°F (4.5°C).  
5A 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5A. INSTALLATION INSTRUCTIONS  
5A.5 Pressure Test/Start-up  
After installation of the panel and tubing, but before laying the finished floor, you need to perform a pressure test. Fill the  
system with air or water and maintain a pressure of 2 to 3 times the working pressure of the system, about 25 to 50 psi (1.7  
to 3.4 bar) for 6 hours. Use a leak detection solution (if testing with air) to locate and repair any leaks in the system. A small  
leak can take a long time to register on a 60 psi (4 bar) gauge. Please note: If the system cannot be started up after the  
pressure test and there is a danger of freeze, you must use air or a glycol solution! Do not use plain water! Run the system at  
normal operating pressure at about 140°F (60°C) for 30 minutes to allow the tubing to relax and settle into the tracks. Noise can  
occur at this time but will reduce as the tubing settles. If the noise persists, locate the source and apply some silicone  
adhesive to the tubing at that location. After the start-up is complete, the finished flooring can be installed.  
5A.6 Sample Flooring Installations  
Tile/Stone: Roth recommends using a tile underlayment product in all ceramic tile installations. Underlayment should be  
secured and seams finished per manufacturer’s instructions. It is also a good idea to use plasticizer additives with the  
mastic and grout for more flexibility during operation of the heating system.  
Laminate Wood Flooring: Thin laminate flooring may require the use of an underlayment material to provide additional  
support above the tubing/grooves. This should be discussed with the flooring contractor during the planning phase.  
Carpeting/Vinyl Flooring: Never use untempered hardboard as an underlayment. Underlayment should be stable under  
the temperature and humidity conditions expected for your project. Untempered hardboard may swell with humidity.  
Hardwood: Nail strips may not be needed if the flooring contractor uses longer nails/staples. This should be discussed  
with the flooring contractor prior to installation of the panel. Never use an asphalt impregnated paper, or any impregnated  
paper that can produce odors when exposed to heat between the panel and the hardwood.  
These are sample installations only!  
It is always important to coordinate any radiant heating with the flooring contractor prior to panel installation!  
The flooring contractor will then be able to incorporate any special requirements felt needed for the installation.  
5A 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Roth's success is the result of flexibility in products, targeted investments  
and theme oriented solutions. Our growth stems from continuous research  
and development of new and innovative products. Manufacturing keys to  
success are combinations of know-how, modern production sites and  
equipment, latest production technologies, and motivated personnel.  
Listed by:  
Roth Industries, Inc.  
77 Circuit Drive  
North Kingstown, RI 02852  
Phone: 401-267-9044; Fax: -9048  
Roth Canada  
1607 rue de l'Industrie  
Beloeil, QC J3G 4S5  
Phone: 450-464-1329; Fax: -7950  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Lennox Hearth Indoor Fireplace Cambria User Manual
LG Electronics DVD Player GSA 5120D User Manual
Liebert Power Supply NX UPS System User Manual
Lincoln Electric Welding Consumables MC 439 User Manual
Logitech Headphones 350vi User Manual
Makita Impact Driver 6933FD User Manual
Marmitek Indoor Furnishings 20061012 User Manual
Martin Audio Portable Speaker AQ215 User Manual
Mellerware Convection Oven 24825 User Manual
Metz Camera Flash 36 AF 3C User Manual