Liebert Power Supply NX UPS System User Manual

AC Power  
For Business-Critical Continuity  
Liebert NX UPS  
User Manual–10-30kVA, 400V, 50/60Hz  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9.1  
iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure i  
iv  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLES  
Table 1  
v
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure i Model number nomenclature  
NXe  
0
A0  
010  
U
Feature Set for Region  
A0 - EMEA  
Input &  
Output  
Voltage  
50/60Hz  
Voltage  
Code  
F
B0 - Aust/NZ  
C0 - Japan  
Output kVA  
220/380  
230/400  
240/415  
U
010  
015  
020  
D0 - China  
G
Revision  
to Base  
Unit  
E0 - Latin Amer  
F0 - Other  
NX Product Line  
UPS Single Module  
Liebert NXe UPS module ratings:  
10, 15, 20, 30kVA (with internal battery)  
Example: NXE0A0010U =  
10kVA module for Europe and Middle East, 400V/230V  
output  
Options  
Model  
Identification  
Note  
Battery cabinet  
NXE0NBCS  
Battery Ground Fault detection kit  
Battery temperature probe (for external battery)  
Maintenance bypass cabinet (separate bypass input)  
Fan Redundancy kit  
NXA0UFXBGF  
NXA0UFXBTS  
NXE0NMBX  
NXE0UFXRF  
NXA0UFXSAN  
NXA0UFXD  
Specify total system kVA  
Specify UPS kVA rating  
Seismic Anchor kit  
Dual bus control cable 05-10-15 metres  
Parallel control cable kit 05-10-15 metres  
Specify length in metres  
NXA0UFXP  
Relay Card (On Bat, Bat Low, On Byp, Sum, UPS Fail)  
MultiPort4 (4 sets On Bat, bat Low)  
Web browser/TCPIP/SNMP Card  
Jbus/Modbus Card  
RELAYCARD-INT  
MULTIPORT 4  
OCWEB-LB  
These are Intellislot plug-in cards (3 slots  
available).  
OC485CARD  
RAM - Remote Alarm Monitor  
Modem card  
NXA0CFXRAM  
NXA0CFXMOD  
NXA0UFXLBS  
NXA0UFXARF  
Requires RELAYCARD-INT  
Extended LBS box  
Air Filter  
One filter  
(XXX: 050 or 150) - Specify length in  
meters. Used for extension in length or  
dual bus arrangement between Nx and  
non-Nx sources'  
Dual Bus Extension Kit 50-150 Meters  
Individual Battery Monitoring  
NXXXXMLBSKIT  
Specify number of blocks. Consult  
Emerson Network Power representatives  
for complete configuration  
BDS 40 or  
BDS 256  
vi  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SAFETY PRECAUTIONS  
This manual contains information concerning the installation and operation of this Emerson Network  
Power Liebert NX Uninterruptible Power System (UPS).  
This manual should be read before commencing installation.  
The UPS must be commissioned and serviced by an engineer approved by the manufacturer (or  
agent).  
Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of war-  
ranty.  
The Liebert NX has been designed for Commercial/Industrial use only, and is not recommended for  
use in life support applications.  
This is a low emission CLASS A Uninterruptible Power System (UPS) product. In a residential envi-  
ronment, this product may nevertheless cause radio interference, in which case, the user may be  
required to take additional measures.  
Conformity and Standards  
This equipment complies with CE directives 73/23 & 93/68 (LV Safety) and 89/336 (EMC), with Aus-  
tralia and New Zealand EMC Framework (C-Tick) and with the following product standards for Unin-  
terruptible Power System (UPS).  
• EN / IEC / AS 62040-1-1—General and safety requirements for use in operator access area  
• EN / IEC / AS 62040-2—EMC requirements; Class A compliant  
• EN / IEC / AS 62040-3—Performance requirements and test methods  
For more details, see 9.0 - Technical Specifications  
Continued compliance requires installation in accordance with these instructions and the use of man-  
ufacturer approved accessories only.  
WARNING  
!
High Leakage Current  
EARTH CONNECTION IS ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.  
Earth leakage current exceeds 3.5 mA and is less than 860 mA.  
Transient and steady-state earth leakage currents, which may occur when starting the  
equipment, should be taken into account when selecting instantaneous RCCB or RCD devices.  
Residual Current Circuit Breakers (RCCBs) must be selected sensitive to DC unidirectional  
pulses (class A) and insensitive to transient current pulses.  
Note also that the earth leakage currents of the load will be carried by this RCCB or RCD.  
This equipment must be earthed in accordance with the local electrical code of practice.  
WARNING  
!
Back-Feed Protection Notice  
This UPS is fitted with a voltage-free contact closure signal for use with an external  
automatic disconnect device (supplied by others) to protect against back-feeding voltage into  
the bypass input. If this signal is not used by the installer, a label must be added at the  
external bypass input disconnect device to warn service personnel that the circuit is  
connected to a UPS.  
The text to use is the following or equivalent:  
ISOLATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE WORKING ON THIS  
CIRCUIT.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
User-Serviceable Parts  
All equipment maintenance and servicing procedures involving internal access requires the use of a  
tool and should be carried out only by trained personnel. There are no user-serviceable parts behind  
covers requiring a tool for removal.  
This UPS is fully compliant with safety regulations for equipment located in an operator accessible  
area. Hazardous voltage is present within the UPS and battery enclosure but out of reach of non-ser-  
vice personnel. Contact with hazardous voltage is minimized by housing live parts behind safety pan-  
els that require a tool for their removal. No risk exists to any personnel when operating the  
equipment in the normal manner, following the recommended operating procedures.  
Battery Voltage Exceeds 400VDC  
All physical battery maintenance and servicing requires the use of a tool or a key and should be car-  
ried out only by trained personnel.  
WARNING  
!
Special care should be taken when working with the batteries associated with this equipment.  
When connected together, the battery terminal voltage will exceed 400VDC and is potentially  
lethal.  
Battery manufacturers supply details of the necessary precautions to be observed when working on,  
or in the vicinity of, a large bank of battery cells. These precautions should be followed implicitly at all  
times.  
Attention should be paid to the recommendations concerning local environmental conditions and the  
provision of protective clothing, first aid and fire-fighting facilities.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single Module UPS Installation  
1.0 SINGLE MODULE UPS INSTALLATION  
1.1  
Introduction  
This following section describes the requirements that must be taken into account when planning the  
positioning and cabling of the Liebert NX uninterruptible power supply and related equipment.  
This chapter is a guide as to general procedures and practices that should be observed by the install-  
ing engineer. The particular conditions of each site will determine the applicability of such proce-  
dures.  
WARNING  
!
Professional Installation Required  
Do not apply electrical power to the UPS equipment before being authorised to do so by the  
commissioning engineer.  
The UPS equipment shall be installed by a qualified electrical tradesperson in accordance  
with the information contained in this manual. All equipment not referred to this manual is  
shipped with details of its own mechanical and electrical installation.  
NOTE  
Three-phase, 4-wire input supply required.  
The standard Liebert NX UPS is suitable for connection to 3-phase, 4-wire (+ Earth) TN, TT  
and IT AC power distribution systems (IEC60364-3). Optional 3-wire to 4-wire conversion  
transformers are available. If it is used in IT AC power distribution systems, a 4-pole circuit  
breaker must be used on the input and refer to the relative IT Systems’ standard  
WARNING  
!
Battery Hazards  
Special care should be taken when working with the batteries associated with this equipment.  
When connected together, the battery terminal voltage will exceed 400VDC and is hazardous.  
Eye protection should be worn to prevent injury from accidental electrical arcs.  
Remove rings, watches and all other metal objects.  
Use only tools with insulated handles.  
Wear rubber gloves.  
If a battery leaks electrolyte or is otherwise physically damaged, it must be replaced, stored in  
a container resistant to sulfuric acid and disposed of in accordance with local regulations.  
If electrolyte comes into contact with the skin, the affected area should be washed  
immediately with water.  
1.2  
Preliminary Checks  
Before installing the UPS, please carry out the following preliminary checks:  
1. Visually examine the UPS and battery equipment for transit damage, both internally and  
externally. Report any damage to the shipper immediately.  
2. Verify that the correct equipment is being installed. The equipment supplied has an identification  
tag on the back of the main door reporting: the type, size and main calibration parameters of the  
UPS.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Single Module UPS Installation  
1.3  
Location  
1.3.1 UPS Room  
The UPS and its internal battery is intended for indoor installation and should be located in an envi-  
ronment with clean air and with adequate ventilation to keep the ambient temperature within the  
specified operating range (see Table 30).  
All models in the Liebert NX UPS range are air-cooled with the aid of internal fans. Cold air enters  
through ventilation grilles at the front of the cabinet and hot air is released through the grilles at the  
back. Do not cover the ventilation openings.  
If necessary to avoid room temperature build-up, install a system of room extractor fans. Optional air  
filters are available if the UPS is to operate in a dusty environment.  
The UPS heat dissipation detailed in Table 31 can be used as a guide for air conditioning sizing,  
depending on the selected mode of operation:  
• Normal Mode (VFI SS 111 Double Conversion UPS)  
• ECO Mode (VFD SS 311 Stand By UPS)  
If in doubt use Normal Mode figures.  
NOTE  
The UPS is suitable for mounting on concrete or other non-combustible surface only.  
1.3.2 External Battery Room  
Batteries should be mounted in an environment where the temperature is consistent and even over  
the whole battery. Temperature is a major factor in determining the battery life and capacity. Typical  
battery manufacturer performance data are quoted for an operating temperature between 20 and  
25°C (68 and 77°F). Operating above this range will reduce the battery life while operation below this  
range will reduce the battery capacity. In a normal installation the battery temperature is main-  
tained between 15°C and 25°C (59 and 77°F). Keep batteries away from main heat sources or main air  
inlets etc.  
Where the batteries are located externally to the main UPS cabinet, a battery protection device  
(e.g., fuses or circuit breakers) must be mounted as close as possible to the batteries themselves, and  
connected using the most direct route possible.  
1.3.3 Storage  
Should the equipment not be installed immediately, it must be stored in a room for protection against  
excessive humidity and or heat sources (see Table 30).  
CAUTION  
!
An unused battery must be recharged periodically per battery manufacturer  
recommendation. Temporarily connecting the UPS to a suitable AC supply mains and  
activating it for the time required for recharging the batteries can achieve this.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Single Module UPS Installation  
1.4  
Positioning  
The cabinet is mounted on four castor-wheels for ease of positioning and for short distance movement.  
Jacking feet are provided to prevent the UPS from moving once it has been wheeled to its final posi-  
tion.  
For optimal design life, the place chosen must offer:  
• Easy connection  
• Enough space to easily work on the UPS  
• Sufficient air exchange of enough to dispel heat produced by UPS  
• Protection against atmospheric agents  
• Protection against excessive humidity and very high heat sources  
• Protection against dust  
• Compliance with the current fire prevention requirements  
• Operating environment temperature between 20°C and 25°C (68 and 77°F). The batteries are at  
maximum efficiency in this temperature range (see Table 30).  
The UPS cabinet is constructed around a steel chassis with removable panels. The top and side panels  
are secured to the chassis by screws.  
Access to the power terminals, auxiliary terminals blocks and power switches is from the front. Oper-  
ational status and alarm information is provided through the front door operator control panel. Mod-  
els 30kVA and below house both the power components and an internal battery. Cooling air enters  
the front of the NX and is exhausted out the rear.  
1.4.1 System Cabinets  
A UPS may comprise a number of cabinets, depending on the design requirements (e.g., UPS cabinet,  
external battery cabinet, external bypass cabinet). In general, all the Liebert cabinets used in a particu-  
lar installation are of the same height and designed to be positioned side-by-side to form a matching  
array.  
Refer to 4.0 - Installation Drawings for assistance on positioning the cabinets described below.  
1.4.2 10 to 30kVA UPS  
The UPS consist of a single cabinet, which uses typically forty (40) 12V battery blocks, fitted inter-  
nally and connected in series to provide a nominal battery voltage. The UPS may be shipped without  
the batteries fitted.  
An extended battery option is available. This comprises a separate cabinet containing additional bat-  
teries that can be connected to the UPS to increase its battery run time.  
1.4.3 Moving the Cabinets  
WARNING  
!
Ensure that any equipment used to move the UPS cabinet has sufficient lifting capacity.  
The UPS is fitted with casters. Take care to prevent the NX from moving when unbolting the  
unit from its shipping pallet. Ensure that adequate personnel and lifting aids are available  
when removing the shipping pallet.  
Ensure that the UPS weight is within the designated surface weight loading of any handling equip-  
ment. See Table 32.  
UPS and optional cabinets (battery cabinets, top cable entry cabinets, etc.) can be handled by means  
of a forklift or similar equipment.  
The UPS cabinet also can be moved short distances by its casters.  
NOTE  
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a  
minimum.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Single Module UPS Installation  
1.4.4 Clearances  
The Liebert NX has no ventilation grilles at either side of the UPS. To enable routine tightening of  
power terminations within the UPS, in addition to meeting any local regulations, Liebert recom-  
mends providing adequate clearance in the front of the equipment for unimpeded passage of person-  
nel with the doors fully opened. It is important to leave of 150mm (5.9") clearance behind the UPS to  
permit adequate circulation of air coming out of the unit.  
1.4.5 Access  
The component layout of the UPS supports front and top access while servicing, diagnosing and  
repairing the UPS, thus reducing the space requirement for side and rear access.  
1.4.6 Final Positioning  
The UPS cabinets are fitted with casters on the base to allow ease of movement and positioning.  
WARNING  
!
Casters are strong enough for movement across even surfaces only. Caster failure could occur  
if they are subjected to shock loading.  
When the equipment has been finally positioned, ensure the adjustable feet are set so that the UPS  
will remain stationary and stable.  
1.4.7 Floor Anchoring  
Diagrams in 4.0 - Installation Drawings show the location of the holes in the base plate through  
which the equipment may be bolted to the floor. If the equipment is to be installed on a raised floor it  
should be mounted on a pedestal suitably designed to accept the equipment point loading. Refer to the  
base view Figure 21 to design this pedestal.  
1.4.8 Cable Entry  
Cables can enter the Liebert NX UPS and battery cabinet from below. Cable entry is made possible by  
removing a blanking piece fitted at the bottom of equipment to reveal the cable entry hole.  
1.5  
External Protective Devices  
Circuit breakers or other protective devices must be installed in the AC supply, external to the UPS.  
This chapter provides guidelines for qualified installers who must have knowledge of local wiring  
practices pertaining to the equipment to be installed.  
1.5.1 Rectifier and Bypass Input  
Overcurrent protection must be installed at the distribution panel of the incoming main supply. The  
protection must discriminate with the power cables current capacity and with the overload capacity of  
the system (see Table 35). As a guideline, a thermomagnetic circuit breaker, with an IEC 60947-2  
trip curve C (normal) for 125% of the current listed in Table 1 is suitable.  
Split-Bypass—If a split-bypass is used, install separate protective devices for the rectifier and for  
the bypass in the incoming mains distribution panel.  
NOTE  
Rectifier and bypass input sources must be referenced to the same neutral potential.  
NOTE  
For IT power systems, four-pole protective devices must be used, external to the UPS, both  
upstream of the input distribution panel and downstream (toward the load).  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Single Module UPS Installation  
Earth Leakage (RCD):  
Any residual current detector (RCD) installed upstream of the UPS input supply must be:  
• sensitive to DC unidirectional pulses (Class A)  
• insensitive to transient current pulses, and  
• must have an average sensitivity, adjustable between 0.3 and 1A.  
Figure 1 Residual current circuit breakers (RCCB) symbols  
To avoid false alarms, earth leakage monitoring devices when used in systems with split-bypass input  
or when used in paralleled UPS configurations, must be located upstream of the common neutral  
sinking point. Alternatively, the device must monitor the combined four-wire rectifier and split-  
bypass input currents.  
The residual earth current introduced by the RFI suppression filter inside the UPS is greater than  
3.5mA and less than 860mA. Liebert recommends verifying the selectivity with all other differential  
devices both upstream of the input distribution board and downstream (toward the load).  
1.5.2 External Battery  
The UPS and its associated batteries are protected against overcurrents through a DC compatible dis-  
connect device.  
1.5.3 UPS Output  
Any external distribution board used for load distribution shall be fitted with protective devices that  
discriminate with those used at the bypass input to the UPS and with the UPS overload characteris-  
tics (see Table 35).  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Single Module UPS Installation  
1.6  
Power Cables  
The cable design must comply with the voltages and currents provided in this section, follow local wir-  
ing practices and take into consideration the environmental conditions (temperature and physical  
support media).  
For cable entry terminal, refer to Figure 22.  
WARNING  
!
Before starting the UPS, ensure that you are aware of the location and operation of the  
external isolators that connect the ups input/bypass supply to the mains distribution panel.  
Check that these supplies are electrically isolated and post any necessary warning signs to  
prevent their inadvertent operation.  
WARNING  
!
Failure to follow adequate earthing procedures may result in electromagnetic interference or  
in hazards involving electric shock and fire.  
Table 1  
Maximum steady state AC and DC currents  
Nominal Current, Amps  
Busbar Stud Size  
Input/Output/  
1,2  
Input Mains Current  
2
With Full Battery  
Output Current  
at Full Load  
3ph + N  
Recharge  
3ph + N  
Bypass  
Cables  
External  
battery  
Cables  
(Bolts)  
UPS  
Rating  
(kVA)  
Battery at  
End of  
Hole  
Dia.  
(mm)  
Torque  
Load  
(Nm)  
380V  
400V  
21  
415V  
380V 400V 415V Discharge Bolt  
10  
15  
20  
30  
22  
33  
44  
63  
20  
31  
42  
61  
15  
22  
30  
45  
14  
21  
29  
44  
13  
20  
28  
42  
22  
33  
44  
66  
32  
M6  
6
M6  
5
43  
62  
1. Input mains current listed for common rectifier and bypass AC input. For split input the rectifier current is 94% of the currents  
listed.  
2. Non-linear loads (switch mode power supplies) affect the design of the output and bypass neutral cables. The current  
circulating in the neutral cable may exceed the nominal phase current. A typical value is 1.5 In.  
3. Protective earth cable: Connect each cabinet to the main ground system must follow the most direct route possible.  
The earth conductor shall be sized in accordance with the AC supply fault rating, cable lengths and type of protection. Typical  
cross sectional areas are 2.5mm2 (10kVA), 6mm2 (15kVA), 10mm2 (20kVA), 16mm2 (30kVA), as per AS / IEC 60950-1  
4. When sizing battery cables, a maximum volt drop of 4 VDC is permissible at the current ratings given in Table 1. The load  
equipment is generally connected to a distribution board containing individually protected busbars rather than connected  
directly to the UPS output. The output cables from paralleled units to the parallel distribution bus should be of same length so  
as to optimise the sharing of current. Do not form coils, so as to minimise the formation of electromagnetic interference.  
5. For terminal location – refer to 4.0 - Installation Drawings)  
Table 2  
Distance from floor to connection point on the equipment  
Minimum Distance  
UPS  
mm (in.)  
Rectifier A.C. Input supply  
Bypass A.C. Input supply  
UPS Output A.C.  
284 (11-1/5)  
284 (11-1/5)  
369 (14-1/2)  
369 (14-1/2)  
1104 (43-1/2)  
Battery Power  
Auxiliary cables: Monitor board (U2)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Single Module UPS Installation  
1.6.1 Cable Termination  
NOTE  
The operations described in this section must be performed by authorised electricians or  
qualified technical personnel. If you have any difficulties, do not hesitate to contact our  
Customer Service and Support Department. See the back page of this manual for contact  
information.  
Once the equipment has been finally positioned and secured, connect the power cables as described in  
the following procedure.  
Refer to the appropriate cable connection drawing in 4.0 - Installation Drawings.  
1. Verify that the UPS equipment is isolated from its external power source and all the UPS power  
isolators are open. Check that these supplies are electrically isolated and post any necessary  
warning signs to prevent their inadvertent operation.  
2. Open the door to the UPS cabinet and remove the front protective cover to gain access to the  
connections bars.  
3. Connect the safety earth and any necessary bonding earth cables to the copper earth busbar  
located on the floor of the equipment below the power connections. All cabinets in the UPS must  
be connected to the user’s ground connection.  
NOTE  
The earthing and neutral bonding arrangement must be in accordance with local and national  
codes of practice.  
Identify and make power connections for incoming cables according to one of the two procedures  
below, depending on the type of installation.  
Common Input Connections  
4. For common bypass and rectifier inputs, connect the AC input supply cables between the mains  
distribution panel and the UPS input (mA-mB-mC-N terminals) and tighten the connections to  
5Nm (M6 Bolt). Ensure correct phase rotation.  
Split-Bypass Connections  
5. If a split-bypass configuration is used, connect the AC input supply cables to the rectifier input  
busbars (mA-mB-mC-N terminals) and the AC bypass supply cables to the bypass input  
(bA-bB-bC-N terminals) and tighten the connections to 5 Nm (M6 Bolt). Ensure correct phase  
rotation.  
NOTE  
For split-bypass operation, ensure that the linking busbars between bypass and rectifier input  
are removed.  
The AC input and the AC bypass supplies must be referenced to the same neutral point.  
Frequency Converter Mode  
If a frequency converter configuration is used, connect the AC input supply cables to the rectifier  
input busbars (U1-V1-W1-N terminals) to 5Nm for M6 bolts, to 13Nm for M8 bolts or to 26Nm (M10  
bolt). Ensure correct phase rotation and tighten the connections. There will not be any AC  
bypass supply cables to the bypass input (U3-V3-W3-N terminals).  
NOTE  
For frequency converter operation, ensure that the linking busbars between bypass and rectifier  
input are removed.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Single Module UPS Installation  
Output System Connections  
6. Connect the system output cables between the UPS output (oA-oB-oC-N terminals) and the  
critical load and tighten the connections to 5 Nm (M6 Bolt). Ensure correct phase rotation.  
WARNING  
!
If the load equipment will not be ready to accept power on the arrival of the commissioning  
engineer, ensure that the system output cables are safely isolated at their ends.  
Internal UPS Battery Connection  
7. The battery consists of a series string connection of 5 x 8 (or 10) x 12V 6-cell battery blocks.  
a. Ensure that the 8 (or 10) battery blocks in each tier (tray) are interconnected.  
b. Connect the positive, neutral and negative cables to the UPS terminals.  
c. Plug in the cables between the tiers.  
d. Ensure correct polarity battery string series connections (i.e., intertier and  
interblock connections are from positive to negative terminals.  
WARNING  
!
Hazardous Battery Terminal Voltage 480VDC  
Ensure correct polarity of string end connections to the UPS terminals, i.e., positive to  
positive, negative to negative and neutral to neutral, but leave these UPS terminal cables  
disconnected until connection is authorised by the commissioning engineer.  
Ensure correct polarity of string end connections to the battery circuit breaker and from the  
battery circuit breaker to the UPS terminals, i.e., positive to positive and negative to negative,  
but disconnect one or more battery cell links in each tier.  
Do not reconnect these links and do not close the battery circuit breaker before authorised by  
the commissioning engineer.  
8. Refit all protective covers removed for cable installation.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single Module UPS Installation  
1.7  
Control Cables and Communication  
1.7.1 Monitor Board Features  
Based on your site’s specific needs, the UPS may require auxiliary connections to manage the battery  
system (external battery circuit breaker, battery temperature sensor), communicate with a personal  
computer or provide alarm signaling to external devices or for Remote Emergency Power Off (REPO).  
The monitor board, arranged for this purpose, is located on the rear of the operator access door. The  
main features are:  
• Input and Output dry contacts signal (one pair of contacts of relay)  
• Emergency Power Off control (EPO)  
• Environmental parameter input interface  
• User communication (for data setting and user background monitor)  
• Intellislot™ interface  
• Modem interface  
• Temperature detect interface  
Figure 2 Auxiliary terminal block detail monitoring board (U2)  
J8  
J3  
J1  
X7  
X6  
J22  
J23  
LCD  
J12  
J9  
J2  
PWR  
Modem  
SNMP Card  
J15  
J16  
X5  
J17  
X4  
Intellislot 2  
Intellislot 1  
Intellislot 3  
X4  
J24  
J21  
J25  
J28  
J4  
J26  
J30 J10  
J13  
EPO  
X2  
Dry In  
MBC  
X3  
BCB  
BFP  
INV  
X1  
ACF  
The black square (  
on each slot indicates Pin 1.  
)
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Single Module UPS Installation  
1.8  
Dry Contacts  
The UPS provides input dry contacts and output dry contacts.  
1.8.1 Input Dry Contacts  
There are several input dry contacts at the X3 slot.  
Figure 3 Input dry contacts  
12V  
12V  
12V  
12V  
X3  
J4  
J26  
J30  
J10  
X3 Ancillary Control and Alarms  
X3 IN DRY: Environmental, Battery Ground Fault and Generator Contacts  
The UPS accepts external signalling from voltage-free (dry) contacts connected to finger-proof, push-in ter-  
minal X3 IN DRY. Subject to prior software programming, the signalling is accepted by the UPS when  
connection between the relevant terminal and the +12V terminal is altered. Cables connected to X3 IN  
DRY must be segregated from power circuits (for screening purposes), double insulated and of a typical 0.5  
2
to 1mm cross-section area for maximum runs between 25 and 50 meters (82-164 ft), respectively.  
Table 3  
Input dry contacts at X3  
Name  
Position  
J4.1  
Description  
3
ENV  
Battery Room Alarm (NC)  
Battery Ground Fault Detection (NC)  
On Generator (NO)  
J4.2  
BtG  
1,2  
J4.3  
GEN  
J4.4  
+12V  
+12V Power  
1 - Must be configured by configuration software before becoming active.  
2 - When activated, the charger current can be limited, via software, to a percentage of the full charger current (0-100%).  
3 - Activating this feature turns the battery charger off.  
1.8.2 Maintenance Bypass Cabinet Interface  
J26 and J30 are the MBC interface.  
Table 4  
Maintenance bypass cabinet interface  
Name  
Position  
J26.1  
J26.2  
J26.3  
J26.4  
J30.1  
J30.2  
J30.3  
J30.4  
Description  
1
T_IT  
Input transformer overtemperature (NC)  
Reserved  
AUX_I  
+12V  
GND  
+12V Power  
Power Ground  
FUSE  
Reserved  
F_FAN Fan Fail Alarm (NC)  
1
T_OT  
Output Transformer Overtemperature (NC)  
AUX_O Reserved  
1 - Must be configured by software before becoming active  
NOTE  
2
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm  
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Single Module UPS Installation  
1.8.3 External Circuit-Breaker Interface  
J10 is the interface to any external battery circuit breaker (BCB).  
Table 5  
External circuit-breaker interface  
Name  
DRV  
FB  
Position  
J10.1  
Description  
BCB Driver Signal - (reserved)  
J10.2  
BCB Contact State -(reserved)  
J10.3  
GND  
OL  
Power Ground  
J10.4  
BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.)  
NOTE  
2
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm  
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.  
Figure 4 Jumper connection for BCB interface  
UPS Monitoring Board  
J10  
Aux – N.O.  
Aux – N.O.  
Battery Circuit Breaker  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Single Module UPS Installation  
1.8.4 Output Dry Contacts  
There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)  
Figure 5 Output dry contacts and EPO wiring  
+12V  
X1  
X2  
J13  
J21  
J25  
J28  
EPO - NO  
EPO - NC  
Table 6  
Output dry contact relays  
Name  
BFP_O  
BFP_S  
BFP_C  
INV_O  
INV_S  
INV_C  
ACF_O  
ACF_S  
ACF_C  
Position  
J13.2  
J13.3  
J13.4  
J21.2  
J21.3  
J21.4  
J25.2  
J25.3  
J25.4  
Description  
Bypass feedback protection relay; normally open; closed when bypass SCR is shorted  
Bypass feedback protection relay center  
Bypass feedback protection relay; normally closed; open when bypass SCR is shorted  
Inverter mode relay; normally open; closed when UPS is in inverter mode  
Inverter mode relay center  
Inverter mode relay; normally closed. Opened when UPS is in inverter mode  
Main input fault relay; normally open. Closed when main input is in fault  
Main input fault relay center  
Main input fault relay; normally closed. Open when main input is in fault  
NOTE  
2
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm  
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Single Module UPS Installation  
1.8.5 Emergency Power Off Input  
The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel  
or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.  
The X2 slot, shown in Figure 5, is the remote EPO input interface. The EPO has an NO/NC contact  
point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1  
If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the  
auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop  
switch between these two terminals using shielded cable (see Figure 5 and Table 7). If this function  
is not used, terminals X2: 3&4 must be opened and X2: 1&2 must be closed.  
Table 7  
EPO input contact relays  
Position  
J28.1  
Name  
Description  
EPO_NC  
EPO_NC  
EPO_NO  
EPO_NO  
EPO activated when opened to J28.2  
EPO activated when opened to J28.1  
EPO activated when shorted to J28.4  
EPO activated when shorted to J28.3  
J28.2  
J28.3  
J28.4  
NOTE  
The emergency stop action within the UPS shuts down the rectifier, inverter and static bypass.  
It does not internally disconnect the input power supply. To disconnect ALL power to the UPS,  
open the upstream feeder breaker(s) when the remote EPO is activated.  
NOTE  
Normally closed EPO – X2: 1,2, these terminals are supplied factory-linked on the monitor  
board and must remain installed if using NC contacts.  
NOTE  
2
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm  
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.  
X5: Auxiliary DC Power Output  
Auxiliary DC power for modem or external SNMP card. The voltage is between 9V to 12V. The maxi-  
mum current is 500mA.  
X6: Analog Input Interface  
Two analog signal channels with an input range is from 0 to +12V. The precision of detection is ÷3%.  
• X6 pin 1: Not used  
• X6 pin 2: +12V  
• X6 pin 3: ENV-T – environment temperature detection  
• X6 pin 4: GND  
X7: External Battery Temperature Detector Interface  
Interface for TMP12Z temperature detector, normally connected to an external battery cabinet (see  
Pin reference:  
• X7 pin 1: Not used  
• X7 pin 2: +12V (Power supply for Temperature Monitoring Probe)  
• X7 pin 3: BAT-T (Battery Temperature signal)  
• X7 pin 4: GND  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Single Module UPS Installation  
Serial Ports RS232-1 and RS232-2  
RS232-1 provides serial data and is intended for direct use with Liebert MultiLink monitoring and  
server shutdown software.  
RS232-2 provides serial data and is intended for use by authorized commissioning and service person-  
nel.  
These serial ports are shared with the optional Web browser, SNMP, ModBus and relay cards. Refer  
to Table 28 regarding compatibility of simultaneous use.  
Intellislot Web Browser, SNMP, ModBus and Relay Cards Interface  
There are three interface slots available for optional Web browser, SNMP, ModBus and Relay cards  
1.8.6 External Bypass Switch Interlock  
EXT-Maint X3-1&2 on UPS Parallel Board M3 (leave open if no external bypass switch is used)  
Provides external maintenance bypass interlock protection for the UPS. Short circuit means external  
bypass closed.  
EXT-Out (X3-3&4) on UPS Parallel Board (leave shorted if no external output switch is used). Pro-  
vides external output interlock protection for paralleled UPS modules. Short circuit means external  
output switch closed.  
NOTE  
UPS Parallel Board M3 is located behind protective covers accessible after opening the UPS  
front door – removal of this barrier requires the use of a tool and is restricted to service  
personnel.  
NOTE  
Jumper JP1 (located next to X3) needs to be removed for X3:3&4 to work properly.  
1.8.7 Battery Start Facility  
1. Rotate the switch to Normal Mode.  
2. Verify that the batteries are connected.  
3. Press Battery Start Button.  
The LCD begins to show startup screens. The rectifier indicator flashes green while the rectifier is  
starting up. It stops flashing and becomes solid green about 30 seconds after the rectifier enters  
the normal operation state.  
4. After UPS has initialized, press Inverter On  
Figure 6 Battery start for UPS  
Battery Start Button  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Battery Installation  
2.0 BATTERY INSTALLATION  
2.1  
Introduction  
The UPS battery bank consists of battery blocks connected in series to provide a D.C. string voltage as  
required by the UPS converter. The 'AUTONOMY TIME' (the time during which the battery can  
maintain supply to the load in the event of a mains failure) is limited by the ampere-hour capacity of  
the battery blocks and in some cases this results in several strings being connected in parallel.  
The NX usually has internal batteries, but longer run time is available by using an external battery  
cabinet.  
The battery cabinet will be supplied in one of the following forms:  
1. Complete installation, comprising the battery cabinet, batteries and protective device.  
2. Battery cabinets and protective device only—batteries supplied by others  
NOTE  
10kVA to 30kVA UPS models contain an internal battery compartment that can accommodate  
up to 44 blocks of batteries for 12Ah/12V; 80 blocks of batteries for 7.2Ah/12V  
The battery bank may be disconnected from the UPS for maintenance or service.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Battery Installation  
2.2  
Safety  
Special care should be taken when working with the batteries associated with the Liebert NX UPS  
system. When all the cells are connected together, the battery terminal voltage is potentially hazard-  
ous. The battery installation must be segregated from all but appropriately qualified maintenance  
personnel by locating the cells in a key-lockable cabinet or in a purpose-designed, dedicated battery  
room. When the batteries require maintenance, these precautions must be taken:  
• The rotary switch must be turned to Maint. position.  
• The input circuit breaker (CB1) must be opened.  
• The ANDERSON connector must be disconnected..  
NOTE  
The fuse on the battery EMI board (UHA241A2-10kkVA, UHK241A2-15/20kVA,  
UHS242A2-30kVA) is 600VDC/30A, High Speed Fuse.  
NOTE  
Full safety instructions concerning the use and maintenance of UPS batteries are provided in  
the appropriate battery manufacturers manuals. The battery safety information contained in  
this section relates to key considerations that must be taken into account during the  
installation design process and might affect the design outcome depending on localised  
conditions.  
WARNING  
!
Hazardous battery voltage present behind covers  
No user-serviceable parts are located behind covers that require a tool for their removal. Only  
qualified service personnel are authorised to remove such covers.  
When using internal batteries in 10 to 30kVA units, the batteries are always connected  
through power fuses to the UPS and to the segregated terminal bars available for connection  
to an external battery.  
Isolate any internal battery connections before attempting to access the segregated terminal  
bars available for connection to an external battery.  
The following general battery safety precautions and warnings should be observed at all  
times:  
• A battery can present risk of electric shock or burn from high- short-circuit currents.  
• The full nominal string voltage, when the battery blocks are interconnected, is 480VDC,  
which is hazardous  
• Only qualified personnel should install or service batteries.  
• Eye protection should be worn to prevent injury from electrical arcs.  
• Remove rings, watches, necklaces, bracelets and all other metal objects.  
• Use only tools with insulated handles.  
• Wear rubber gloves and a rubber apron when handling batteries.  
• If a battery leaks electrolyte or is otherwise damaged, it should be placed in a container  
resistant to sulfuric acid and disposed of in accordance with local regulations.  
• If electrolyte comes into contact with the skin the affected area should be washed immedi-  
ately with plenty of clean water.  
• Batteries must always be disposed of according to local environmental laws.  
• When replacing batteries, use the same number and type that were originally fitted.  
• Disconnect charging source before connecting or disconnecting battery terminals.  
• Determine whether the battery is inadvertently grounded. If it is inadvertently grounded,  
remove the source of the ground. Contact with any part of a grounded battery can result in  
electrical shock.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Battery Installation  
2.3  
Battery Cabinet  
2.3.1 Introduction  
This cabinet can also be used in conjunction additional cabinets, to provide the necessary accommoda-  
tion required by the larger cells associated with system’s having a long autonomy time.  
Where two (or more) cabinets are used they are positioned alongside each other and secured and  
bonded together. If the cabinet(s) is located immediately adjacent to the main UPS equipment the two  
units are bolted together.  
2.3.2 Temperature Considerations  
Valve-regulated, lead acid battery cells are sensitive to ambient temperature and should be operated  
between 15°C and 25°C (59-77°F). Battery capacity is increased by 1% for every 1°C (2°F) increase in  
temperature up to 25°C (77°F). Battery life is reduced at temperatures above 25°C (77°F).  
When batteries are mounted in the same room as the UPS unit, it is the battery that dictates the  
designed maximum ambient temperature, not the UPS. — i.e. in the case of valve-regulated cells, the  
ambient room temperature should be kept between 15°C and 25°C (59-77°F), and not between 0°C  
and 40°C (32-104°F) (which is the specified main equipment operating temperature range). Tempera-  
ture deviations are permissible for short periods, provided the average temperature does not exceed  
25°C (77°F).  
2.3.3 Dimensions  
The external dimensions are shown in Table 8. These are the same height and depth as the UPS  
module and provide a matching appearance when bolted together. All cabinets are fitted with doors,  
which must be fully opened in order to fit or remove the batteries. The door swing must therefore be  
taken into consideration when planning the positioning of the cabinets.  
2.3.4 Weight  
The unladen weight is shown below in Table 8. When designing the battery installation the weight of  
the batteries and cables must be added to the unladen weight. This is particularly important when  
placing the NX on a raised floor.  
Table 8  
Dimensions and weight  
Optional  
Circuit Breaker  
Amperes  
Maximum  
Discharge Current  
(at EOD)  
Cabinet Weight  
Without Batteries  
kg (lb)  
External Cabinet  
WxDxH mm (in)  
Model  
10kVA 22A  
15kVA 33A  
20kVA 44A  
50A  
820x700x1400  
(32-1/4x27-5/8x55)  
Battery Cabinet  
170 (375)  
80A  
30kVA 66A  
2.3.5 Circuit Isolator Features  
The UPS is fitted with Anderson connectors and fuses for connection and disconnection of internal  
batteries. External battery banks require battery fuses or circuit breaker (with optional status con-  
tacts). Refer to 1.8.3 - External Circuit-Breaker Interface for details.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
             
Battery Installation  
2.3.6 Battery Temperature Sensor (Optional)  
The optional external battery temperature sensor kit contains one probe and one temperature trans-  
port board as illustrated in Figure 7. It is connected to the UPS Monitor Board.  
Figure 7 Single temperature sensor and monitor board-U2  
Name: W2 L=5m  
Temperature  
Sensor  
Monitor  
Board  
– U2  
Name: W1 L=30m  
X7  
NC  
+
IN  
-
-12V  
BAT-T  
GND  
12V  
OUT  
GND  
TMP-2  
UPS  
Cable W2 is packed with the temperature sensor.  
2.3.7 Moving the Battery Cabinets  
WARNING  
!
Ensure any lifting equipment used in moving the cabinet has sufficient lifting capacity.  
Ensure that the weight is within the designated surface weight loading of any handling equipment.  
See Table 8 for weight details.  
Battery cabinets can be handled by means of a fork lift or similar equipment.  
NOTE  
Care must be taken when maneuvering units fitted with batteries. Keep such moves to a  
minimum.  
When the equipment has been finally positioned ensure the adjustable feet are set so that the  
battery cabinet will remain stationary and stable.  
Seismic anchors option is available for anchoring the unit to a concrete floor.  
2.3.8 Cable Entry  
Cables enter the battery cabinet from the bottom. Cable entry is made possible by removing a blank-  
ing piece fitted at the bottom to reveal the cable entry hole.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Battery Installation  
2.3.9 General Arrangement Drawings  
Refer to Figures 8 and 10 for general arrangement of battery cabinet models.  
Figure 8 Battery cabinet bottom cable entry location  
Bottom View  
700  
250  
82,5  
100  
83  
1400  
620  
828  
All dimensions are  
expressed in millimeters.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Battery Installation  
Figure 9 Battery cabinet with fuse or optional circuit breaker locations  
Bottom cable entry  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Battery Installation  
Figure 10 Battery cabinet internal layout  
Positions of captive nuts for grille mounting  
Minimum service space 65mm  
B
Captive nut M6  
43  
29  
15  
1.  
Hex flange  
screw M6x16  
Detail B  
3 Layers:  
1 Layer:  
Largest battery dimensions:  
201x170x190 (LxWxH)  
170 10 170 10 170 10 170  
Largest battery dimensions:  
201x170x190 (LxWxH)  
170 10 170  
5
15  
368  
738  
All measurements are in millimeters.  
AMNXE0NBCSL4BT  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Battery Installation  
Figure 11 Battery cabinet, bottom entry  
12  
11  
13  
4
6
1
7
8
4
6
13  
12  
8
9
5
AMNXE0NBCSL4BT  
3
10  
2
Item #  
Item Name  
Grille steel  
Grille steel  
Middle pillar  
1
2
3
4
Cover module BC Small NXe  
Ground bus  
5
6
Captive nut M4  
7
Captive nut M6  
8
Screw flange M6x16  
Nut flange M6  
9
10  
11  
12  
13  
Screw M6x16 countersink  
Spring washer M4  
Flat washer M4  
Screw mushroom head cross M4x12  
2.4  
Battery Power Cables  
2.4.1 Connection Principles  
The following notes, in conjunction with the diagrams, illustrate the broad principles to be followed  
when fitting and connecting the majority of battery installations.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Battery Installation  
2.4.2 Fitting the Batteries  
1. In general, at least 10mm (3/8") must be left unobstructed on all vertical sides of the battery  
blocks to permit free air movement around the cells.  
2. Clearance should be allowed between the top of the cells and the underside of the shelf above (this  
is necessary for monitoring and servicing the cells).  
3. When installing the batteries on racks always work from the bottom shelf upwards to prevent  
raising the centre of gravity.  
2.4.3 Connecting the Battery  
1. When the battery cabinet is installed on a raised floor the battery power cables and optional circuit  
breaker control cables can be routed to the UPS cabinet via the floor of the cabinet. If the UPS and  
battery cabinet are located adjacent to each other and located on a solid floor these cables can be  
passed between the cabinets via the lifting apertures located in the lower sides of the cabinets.  
2. In general it is recommended that the inter-connecting cables be fitted to the batteries within  
their particular level before fitting the inter-level connecting cables, followed finally by the cables  
to the circuit breaker.  
3. An insulating shroud should be fitted to each terminal after its connection has been made.  
4. When connecting the cables between the battery string ends to the optional circuit breaker always  
connect the circuit breaker end of the cable first.  
2.4.4 Battery Room Design  
Whatever the type of mounting system selected, the following conditions should be noted:  
• Cell Layout—1  
Whichever battery mounting system is used, the batteries should be arranged to prevent the pos-  
sibility of simultaneous contact with two exposed live parts having a potential greater an 150V.  
Where this is not possible, insulated terminal shields must be installed and insulated cables must  
be used for connections.  
• Service Platform—2  
The service platform (or duckboard) must be slip-proof, insulated from the floor and at least one  
metre (39 in.) wide.  
• Connections—3  
All connections must be as short as possible.  
• Battery Protection Fuses/Circuit Breaker4  
The battery circuit breaker is generally installed at the front of the battery room. See 2.5 - Bat-  
tery Control for details on connecting the circuit breaker box available for the Liebert NX.  
Figure 12 Battery room design  
4
1
3
2
2.5  
Battery Control  
Battery temperature sensor cables are connected between UPS auxiliary terminal block X3 BCB, the  
Battery Temperature sensor and the battery as shown in Figure 7.  
Cables connected to X3 BCB must contain a protective earth wire or a shield, be segregated from  
power circuits, double insulated and of a typical 0.5 to 1mm2 cross section area for maximum runs  
between 25 and 50 meters respectively. The shield should be connected to the protective earth of the  
battery cabinet or battery breaker, not at the UPS  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
UPS Multi-Module Installation  
3.0 UPS MULTI-MODULE INSTALLATION  
3.1  
General  
The installation of a multi-module UPS configuration must follow the installation procedure for a sin-  
gle UPS module with the additional requirements detailed in this chapter.  
In addition to the local EPO push button on the front panel of the UPS module (that stops operation of  
that module), the UPS supports also a remote emergency stop to permit simultaneous multi-module  
shutdown.  
NOTES  
1. The remote emergency power off switch must be voltage-free and Normally Open or  
Normally Closed.  
2. The open voltage supplied is 12VDC, < 20mA  
3. This external emergency stop may be supplied with a second set of contacts that can be used  
to trip incoming mains or bypass supply circuit breakers supplied by others and fitted with  
remote trip units.  
4. Normally Closed EPO - X2: 1&2, these terminals are supplied factory-linked on the monitor  
board.  
Figure 13 Emergency power off connections  
UPS2  
X2:3  
Monitor Board  
X2:4  
X2:3  
X2:4  
Monitor Board  
UPS1  
EPO  
UPS2  
X2:1  
X2:2  
Monitor Board  
X2:1  
X2:2  
Monitor Board  
UPS1  
EPO  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
UPS Multi-Module Installation  
3.2  
Paralleled UPS Modules  
The basic installation procedure of a parallel system comprising two or more UPS modules is the  
same as that of single module system. The following sections only introduce the installation proce-  
dures specific to the parallel system.  
3.2.1 Cabinet Installation  
Place the UPS modules side by side and interconnect as shown in Figure 14. The distribution panel  
(external bypass cabinet) is optional but recommended for ease of maintenance and system testing.  
Figure 14 Typical 1+N system block diagram with common input supply, with separate batteries and  
optional output / bypass distribution panel  
SUPPLIED BY OTHERS  
INPUT MAINS  
INPUT MAINS  
SUPPLY L1, L2, L3, N  
SUPPLY L1, L2, L3, N  
CB1  
CB1  
UPS1  
UPS2  
RECTIFER  
RECTIFER  
SW1-C  
SW1-C  
FUSES  
FUSES  
STATIC  
SWITCH  
STATIC  
SWITCH  
CHARGER  
CHARGER  
BATTERY 2  
BATTERY 1  
INVERTER  
INVERTER  
SW1-D  
SW1-A  
SW1-A  
L1, L2, L3, N  
L1, L2, L3, N  
Q2EXT  
Q1EXT  
QBYP  
QUPS  
Distribution Cabinet  
TO LOAD  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
UPS Multi-Module Installation  
Figure 15 Dry contacts, multiple UPS modules with distribution panel  
Input Distribution  
UPS 1  
UPS 2  
UPS N  
M3 Board  
M3 Board  
M3 Board  
X3  
X3  
X3  
Ext. Maint. Ext. Out  
Ext. Maint. Ext. Out  
Ext. Maint. Ext. Out  
1 2 3 4  
1 2 3 4  
1 2 3 4  
Q1Ext  
Q2Ext  
QnExt  
QByp  
Distribution Panel  
QUPS  
To Load  
3.2.2 External Protective Devices  
Refer to the instructions in 1.0 - Single Module UPS Installation.  
3.2.3 Power Cables  
The wiring of power cables is similar to that of single module system. The Bypass and the Main input  
sources must be referenced to the same neutral potential and input earth leakage monitoring devices,  
if installed, must be located upstream of the common neutral sinking point. Refer to the instructions  
NOTE  
The length and specification of power cables including the bypass input cables and UPS output  
cables should be the same. This facilitates load sharing when operating in bypass mode.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
UPS Multi-Module Installation  
3.2.4 Control Cables  
Intermodule Control  
Shielded and double insulated control cables available in lengths of 5, 10 and 15 meters must be must  
be interconnected in a ring configuration between UPS modules as shown below. The parallel control  
board is mounted on the top, behind protective cover of each UPS module (refer to Figure 23). The  
ring configuration ensures high reliability of the control. Refer to Figure 16.  
Figure 16 Connection of 1+N system parallel control cables  
UPS  
1
2
3
4
5
6
Parallel Board  
Parallel Board  
Parallel Board  
Parallel Board  
Parallel Board  
Parallel Board  
X3  
X3  
X3  
X3  
X3  
X3  
P5  
X4  
P5  
X4  
P5  
X4  
P5  
X4  
P5  
X4  
P5  
X4  
X2-2 X2-1  
X2-2 X2-1  
X2-2 X2-1  
X2-2 X2-1  
X2-2 X2-1  
X2-2 X2-1  
X1-1 X1-2  
X1-1 X1-2  
X1-1 X1-2  
X1-1 X1-2  
X1-1 X1-2  
X1-1 X1-2  
3.3  
Hot-Standby UPS Modules  
3.3.1 Cabinet Installation  
Place the UPS modules side by side and interconnect as shown below.  
The hot standby mode comprises two series connected UPS modules of the same rating. One module  
is designated as the hot standby master (downstream), and the other module is designated as the hot  
standby slave (upstream). Their roles are determined by power connection and configuration soft-  
ware. In normal operation, both slave and master operate in normal mode and the output from one  
upstream (slave) UPS feeds the bypass input to the other (downstream/master) UPS. The output of  
the downstream (master) UPS is connected to the critical load and is always synchronised to the out-  
put of the upstream (slave) UPS. If the inverter of the UPS connected to the load fails, the inverter of  
the upstream (slave) UPS supplies the load through the downstream (master) UPS bypass circuit.  
The system can be programmed to cycle the downstream (master) UPS between normal mode and  
bypass mode so that both ups are equally exercised.  
NOTE  
If it is a hot-standby system, the master (downstream) must be turned on first.  
3.3.2 External Protective Devices  
Refer to the instructions in 1.0 - Single Module UPS Installation.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
UPS Multi-Module Installation  
3.3.3 Power Cables  
The wiring of power cables is similar to that of single module system except that the output of the  
upstream UPS is fed into the bypass input of the downstream UPS, and the load is fed by the down-  
stream UPS through its inverter or bypass. The bypass and the main input sources must be refer-  
enced to the same neutral potential and input earth leakage monitoring devices, if installed, must be  
located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Mod-  
No control wires other than those specified for the single module configuration are required.  
Figure 17 Hot standby configuration  
INPUT DISTRIBUTION  
UPSTREAM  
DOWNSTREAM  
Bypass L1,  
L2, L3, N  
Bypass L1,  
L2, L3, N  
Mains L1,  
L2, L3, N  
Mains L1,  
L2, L3, N  
CB1  
CB1  
RECTIFIER  
STATIC  
SWITCH  
INVERTER  
L1, L2, L3, N  
L1, L2, L3, N  
UPS1  
OUTPUT  
TO LOAD  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
UPS Multi-Module Installation  
3.4  
Dual Bus System  
3.4.1 Cabinet Installation  
The Dual Bus System consists of two independent UPS configurations each consisting of one or more  
UPS modules. Dual Bus Systems are high availability configurations suitable for loads with multiple  
input terminals. For single input loads an optional Static Transfer Switch may be added and the stan-  
dard Load Bus Synchroniser activated. Depending on the configuration, follow the appropriate instal-  
lation instructions for each system.  
Place the UPS modules side by side and interconnect as shown below.  
The objective of the Dual-bus Synchronizer (DBS) is to keep the output of two independent UPS sys-  
tems (or parallel systems) in synchronization. One system is designated as the master; the other is  
designated as the slave. The operating modes covered comprise master and or slave operating  
inverter or bypass mode.  
Figure 18 Typical dual bus system configuration with static transfer switch and Load Bus Synch  
Bypass  
supply  
Bypass  
supply  
Input  
Input  
Rectifier  
Input  
Input  
Rectifier  
Rectifier  
Rectifier  
UPS1  
UPS1  
UPS 6  
UPS 6  
LBS  
Intermodule  
control cable  
Intermodule  
control cable  
STS  
Load  
3.4.2 External Protective Devices  
Refer to the instructions supplied in 1.0 - Single Module UPS Installation.  
3.4.3 Power Cables  
The wiring of power cables is similar to that of single module system. The Bypass and the Main input  
sources must be referenced to the same neutral potential and input earth leakage monitoring devices,  
if installed, must be located upstream of the common neutral sinking point. Refer to the instructions  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
UPS Multi-Module Installation  
3.4.4 Control Wires  
For Liebert NX to NX dual bus configuration, interconnect the optional DBS cable between any DBS  
ports of two parallel systems as illustrated in Figure 19.  
Figure 19 Connections of a typical dual bus system utilising Load Bus Synch  
UPS  
UPS  
Parallel Board  
Parallel Board  
Parallel Board  
Parallel Board  
X3  
X3  
X3  
X3  
P5  
X4  
P5  
X4  
P5  
X4  
P5  
X4  
DBS Cable  
X2-2 X2-1  
X2-2 X2-1  
X2-2 X2-1  
X2-2 X2-1  
X1-1 X1-2  
X1-1 X1-2  
X1-1 X1-2  
X1-1 X1-2  
8
8
Parallel System I  
Parallel System II  
A
B
NOTE  
Example shown with ring control cables ("8") for DSB applied to two 1+1 paralleled systems.  
3.4.5 Extended Dual Bus Synchronization Option (DBS Interface Box)  
For Liebert NX to non- NX (whether another Liebert UPS range or not) dual bus configuration, one  
DBS interface box shall be mounted on the non- Liebert NX UPS. In this situation, the other UPS sys-  
tem is always treated as a master and the following conditions are covered:  
• Master and slave are both on inverter  
• Master on bypass, slave on inverter  
NOTE  
Extended DBS interface box is also used for extending DBS cable length up to  
150 meters (490ft) for DBS configuration between two groups of NX UPS systems.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Installation Drawings  
4.0 INSTALLATION DRAWINGS  
Figure 20 Electrical connections  
Earth  
To Customer’s Safety  
Earth  
UPS  
A
B
C
N
Ext. Maint.  
Parallel Board  
X3  
To Critical Load  
Ext. Out  
Power  
Cables  
A
B
C
N
Main/Bypass Input  
Supply  
Modem-  
SNMP  
Monitor Board  
X5  
RS-485  
X4  
J4  
Input  
MBC  
J13  
Gen  
X3  
BPS  
AFC  
X1  
J21  
J25  
J26  
J30  
J28-1  
J28-2  
J28-3  
J28-4  
X2 Ext EPO  
External Battery  
X7  
X3  
-
N
+
BCB  
Batt  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Drawings  
Figure 21 General arrangement—10-30kVA UPS module  
600  
700  
10mm dia threaded  
mounting holes  
2
7
86.5  
1
Leve  
Detail A, rear of unit  
shown without side panel  
Leveling feet  
90  
LEFT SIDE VIEW  
FRONT VIEW  
420  
180  
5
4
3
867.5  
708  
572  
6
1380  
166  
210  
236  
346  
520  
625  
BOTTOM VIEW  
1) Air inlet grille  
2) Air outlet grille  
TOP VIEW  
3) Adjustable fixing feet  
4) Castors for maneuvering  
5) Seismic anchors (option)  
6) Cable entry  
All dimensions are in mm.  
7) Operator control and display panel  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Drawings  
Figure 22 10-30kVA NX front view with doors open  
1) Main/Bypass Input terminal (T1)  
2) Battery /Output terminal (T2)  
3) Input circuit breaker (CB1)  
4) Rotary switch (SW1)  
5
5) Monitor board (U2)  
4
3
2
1
T2  
External Battery Input  
Output  
T1  
Main Input  
Bypass Input  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Drawings  
Figure 23 Location of parallel logic board M3  
Battery  
Start  
Interface  
Parallel  
Logic  
Board  
NXe 10-30kVA Top View  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation Drawings  
Figure 24 Internal battery layout and connecting—GP12120 F2 (12AH/12V)  
BOTTOM LAYER  
TOP LAYER  
Layer 1  
Layer 5  
Layer 4  
Layer 3  
Layer 2  
43  
41  
44  
42  
W501 4pcs  
W500  
34Pcs  
7 7  
5 5  
3 3  
1 1  
W503  
W502  
W511  
W510  
W515  
W514  
W513  
W512  
BLK  
BLK  
BLK  
BLK  
W506  
W508  
W509 W505  
W507  
J2  
+BATT IN  
J4  
J6  
-BATT IN  
NIN  
NOTE 1. TYPICAL USED FOR:GP 12120 F2 (12AH/12V)  
BATTERY INTERCONNECT  
WIRING DIAGRAM  
A2 BOARD  
UPS MODULE  
2. REMOVE 43&44 WHEN 42 JARS ARE USED.  
REMOVE 41~44 WHEN 40 JARS ARE USED.  
Figure 25 Internal battery layout and connecting—LC-R127R2PG1 (7.2AH/12V)  
BOTTOM LAYER  
TOP LAYER  
Layer 1  
Layer 5  
Layer 4  
Layer 3  
Layer 2  
W520  
W517  
W501 4Pcs  
W500  
68Pcs  
W516  
W518  
W519  
W521  
7 7  
5 5  
BLK W510  
3 3  
1 1  
W513 BLK W512  
W502  
W503  
W511  
W514  
W515  
BLK  
BLK  
W506  
W508  
W509  
W507  
W505  
J2  
J4  
J6  
-BATT IN  
NIN  
BATTERY INTERCONNECT  
WIRING DIAGRAM  
+BATT IN  
A2 BOARD  
UPS MODULE  
NOTE  
1
TYPICAL USED FOR: LC-R127R2PG1 (7.2AH/12V)  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Installation Drawings  
Figure 26 Internal battery layout  
347mm  
151mm  
160mm  
562mm  
160mm  
160mm  
160mm  
136mm  
Battery  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operation  
5.0 OPERATION  
WARNING  
!
Hazardous Mains and / or Battery Voltage present behind covers.  
No user-serviceable parts are located behind covers that require a tool for their removal. Only  
qualified service personnel are authorised to remove such covers.  
5.1  
Introduction  
Liebert’s NX™ Uninterruptible Power System system provides continuous, high-quality AC power to  
your business-critical equipment, such as telecommunications and data processing equipment. The  
NX UPS supplies power that is free of the disturbances and variations in voltage and frequency com-  
mon to utility power, which is subject to brownouts, blackouts, surges and sags.  
The NX utilizes the latest in high frequency, double-conversion pulse width modulation (PWM) tech-  
nology and fully digital controls to enhance its reliability and increase the ease of use.  
The standard NX consists of the UPS and internal batteries in a compact, single cabinet.  
As shown in Figure 27, the AC utility source is input at CB1 and the rectifier converts the AC utility  
into DC power. The inverter converts that DC power from the utility—or DC power from the batteries  
—into AC power for the load. The batteries power the load through the inverter in the event of a  
power failure. The utility source can also power the load through the static bypass.  
If maintenance or repair of the UPS is necessary, the load can be switched without interruption in  
service to the maintenance bypass.  
Figure 27 Single unit block diagram with split-bypass input  
SW1/D  
Maintenance Bypass  
Static Swich  
Bypass  
SW1/C  
Input  
UPS  
Output  
AC Utility  
Input  
SW1/A  
SW1/B  
CB1  
Static Swich  
Rectifier  
Inverter  
Discharge  
Neutral  
Wire  
Battery  
Charger  
Neutral  
Wire  
Battery  
5.1.1 Split-Bypass Input  
Figure 27 illustrates the Liebert NX UPS in what is known as the split-bypass configuration wherein  
a separate power switch to a dedicated bypass power source that also feeds the maintenance bypass  
line connects the static bypass line. Where a separate power source is not available, the bypass and  
rectifier input supply connections are linked.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operation  
5.1.2 Static Transfer Switch  
The circuit blocks labeled Static Switch in Figure 27 contain electronically controlled switching cir-  
cuits that enable the critical load to be connected to either the inverter output or to a bypass power  
source via the static bypass line. During normal system operation the load is connected to the  
inverter; but in the event of a UPS overload or inverter failure, the load is automatically transferred  
to the static bypass line.  
To provide a clean (no-break) load transfer between the inverter output and static bypass line, the  
static switch activates, connecting the load to bypass. To achieve this, the inverter output and bypass  
supply must be fully synchronized during normal operating conditions. This is achieved through the  
inverter control electronics, which make the inverter frequency track that of the static bypass supply,  
provided that the bypass remains within an acceptable frequency window.  
A manually controlled, maintenance bypass supply is incorporated into the UPS design. It enables the  
critical load to be powered from the utility (bypass) supply while the UPS is shut down for routine  
maintenance.  
NOTE  
When the UPS is operating in bypass mode or on maintenance bypass, the connected  
equipment is not protected from power failures or surges and sags.  
5.1.3 Battery Temperature Compensation  
For 10-30kVA UPS with internal batteries, a standard temperature probe is installed to measure the  
internal battery temperature to optimize battery management. The measured temperature can be  
displayed from the UPS front panel.  
For UPS with external batteries, an optional battery temperature interface equally optimises the  
external battery management by connecting up to four external temperature sensors from the battery  
cabinet(s) to a control unit inside the UPS.  
Figure 28 Multiple battery temperature sensors  
Temperature  
Sensor  
X103  
NC  
+
IN  
-
12V  
OUT  
GND  
TMP-2  
Temperature  
Sensor  
X104  
NC  
+
IN  
-
12V  
OUT  
GND  
TMP-2  
Monitor  
Board  
– U2  
X7  
X108  
+12V  
OUT  
Temperature  
Sensor  
-12V  
BAT-T  
GND  
GND  
X105  
NC  
UPS  
+
IN  
-
12V  
OUT  
GND  
TMP-2  
BCB Control  
Board – C2  
Temperature  
Sensor  
X106  
NC  
+
IN  
-
12V  
OUT  
GND  
TMP-2  
BCB Box  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operation  
5.1.4 Redundant Control Power Supply Board  
The UPS is equipped with two identical and fully redundant control power supply boards. Each of  
them takes inputs from the AC and DC sources. When one of the sources or even if one of the control  
power boards fails, the UPS system can still operate normally. This feature further enhances the reli-  
ability of the system.  
5.1.5 Socket Outlet  
One single-phase Shuko-type universal outlet of 3A current handling capability provides nominal  
UPS output voltage of up to 3A current capacity for the ease of testing, commissioning & servicing of  
the UPS.  
5.2  
Multi Module UPS—1+N  
Multi-module UPS are formed by several “single unit” UPS modules to constitute “1+N”system where  
groups of one or more, up to six, single units operate together for the purpose of providing additional  
power or reliability or both. The load is equally shared between any paralleled UPS.  
Figure 29 1+N multi-module UPS with external maintenance bypass switch  
Qin UPS1  
Qin UPS2  
Qin UPS3  
Qin Ext  
Byp  
Supplied by Others  
Input Mains Supply  
Input Mains Supply  
Bypass Mains Supply  
L1,L2,L3,N  
Input Mains Supply  
Bypass Mains Supply  
L1,L2,L3,N  
L1,L2,L3,N  
L1,L2,L3,N  
L1,L2,L3,N  
L1,L2,L3,N  
CB1  
CB1  
CB1  
RECTIFIER  
RECTIFIER  
RECTIFIER  
STATIC  
SWITCH  
STATIC  
SWITCH  
STATIC  
SWITCH  
INVERTER  
INVERTER  
INVERTER  
UPS3  
OUTPUT  
UPS1  
OUTPUT  
UPS2  
OUTPUT  
L1,L2,L3,N  
L1,L2,L3,N  
L1,L2,L3,N  
Qout UPS3  
Qout UPS1  
Qout UPS2  
Qout all UPS  
Distribution Cabinet  
Qout Byp  
Further, single unit or 1+N groups may be configured as “distributed redundant” systems with inde-  
pendent outputs that nevertheless are synchronised through a Load Bus Synchroniser (LBS) so that  
critical loads can be seamlessly transferred from one system to another. See 5.3 - Modes of Opera-  
tion for more information.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operation  
5.2.1 Features of NX Multi-Module UPS Configurations  
1. The hardware and firmware of single module UPS units is completely compatible with the  
requirements of a multi-module system. Multi-module configuration is achieved merely through  
settings in configuration software.  
2. Parallel control cables are connected in a ring, providing both performance and redundancy.  
Dual-bus control cables are connected between any two UPS modules of each bus. The intelligent  
paralleling logic provides the user with maximum flexibility. For example, shutting down or  
starting up UPS modules in a parallel system can be done in any sequence. Transfers between  
Normal and Bypass modes of operation are synchronised and self –recovering e.g. following  
overloads and their clearance.  
3. The total load of the multi-module system can be queried from each module’s LCD display.  
5.2.2 Requirements for Paralleling of UPS Modules  
A group of paralleled modules behave as if it were one large UPS with the advantage of presenting  
higher reliability. In order to assure that all modules are equally utilised and to comply with relevant  
wiring rules, the following requirements apply:  
1. All UPS modules must be of the same rating and must be connected to the same bypass source.  
2. The bypass and the main input sources must be referenced to the same neutral potential.  
3. Any RCD, Residual Current monitoring device, if installed, must be of an appropriate setting and  
located upstream of the common neutral bonding point. Alternatively, the device must monitor  
the combined 4-wire rectifier and split-bypass input currents of the system. Refer to the High  
4. The outputs of all UPS modules must be connected to a common output bus.  
NOTE  
Optional isolation transformers are available for applications where sources do not share the  
same neutral reference or where the neutral is not available.  
5.3  
Modes of Operation  
The NX UPS is an on-line, double-conversion, reverse-transfer UPS that permits operation in these  
modes:  
• Normal Mode  
• Battery Mode (Stored Energy Mode)  
• Auto-Restart Mode  
• Bypass Mode  
• Maintenance Mode (Manual Bypass)  
• ECO Mode  
• Parallel Redundancy Mode  
• Hot-Standby Mode  
• Frequency Converter Mode  
5.3.1 Normal Mode  
The UPS inverter continuously supplies the critical AC load. The rectifier/charger derives power from  
the AC mains input source and supplies DC power to the inverter while simultaneously FLOAT or  
BOOST charging its associated backup battery.  
5.3.2 Battery Mode (Stored Energy Mode)  
Upon failure of the AC mains input power; the inverter, which obtains power from the battery, sup-  
plies the critical AC load. There is no interruption in power to the critical load upon failure or restora-  
tion of the AC mains input power after which the “Normal Mode” operation will continue without the  
necessity of user intervention.  
5.3.3 Auto-Restart Mode  
The battery may become exhausted following an extended AC mains failure. The inverter shuts down  
when the battery reaches the End Of Discharge voltage (EOD). The UPS may be programmed to  
“Auto Recovery after EOD” after a delay time. This mode and any delay time are programmed by the  
commissioning engineer.  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Operation  
5.3.4 Bypass Mode  
If the inverter overload capacity is exceeded, or if the inverter becomes unavailable for any reason,  
the static transfer switch will perform a transfer of the load from the inverter to the bypass source,  
with no interruption in power to the critical AC load. Should the inverter be asynchronous with the  
bypass, the static switch will perform a transfer of the load from the inverter to the bypass with inter-  
ruption in power to critical AC load. This is to avoid paralleling of unsynchronised AC sources. This  
interruption is programmable but typically set to be less than 3/4 of an electrical cycle, e.g., less than  
15ms (50Hz) or less than 12.5ms (60Hz).  
5.3.5 Maintenance Mode (Manual Bypass)  
A manual bypass switch is available to ensure continuity of supply to the critical load when the UPS  
becomes unavailable e.g. during a maintenance procedure. This manual bypass switch is fitted in all  
UPS modules and rated for full load of one module.  
5.3.6 ECO Mode (Single UPS Only)  
IF ECO mode is selected, the double-conversion UPS operation is inhibited at most times for the pur-  
pose of saving energy. In this mode of operation, not unlike UPS of line-interactive or stand-by tech-  
nology, the bypass is the preferred source and only when the voltage and / or frequency of the bypass  
supply are beyond pre-defined and adjustable limits the critical AC load is transferred to the inverter.  
This transfer takes place with an interruption of less than 3/4 of an electrical cycle, e.g., less than  
15ms (50Hz) or less than 12.5ms (60Hz).  
5.3.7 Parallel Redundancy Mode (System Expansion)  
For higher capacity or higher reliability or both, the outputs of up to six UPS modules can pro-  
grammed for directly paralleling while a built-in parallel controller in each UPS ensures automatic  
load sharing.  
5.3.8 Hot-Standby Mode  
This is an alternative 1+1 redundancy application that ensures higher availability or better usage  
control or both. Two UPS are connected in Hot Stand By mode as follows: UPS 1connects to the criti-  
cal load, and UPS 2 connects to the bypass of UPS 1. The remaining AC inputs are connected to the  
incoming AC mains supply. UPS 1 synchronises to the output of the UPS 2 ensuring uninterrupted  
load transfer from UPS 1 to UPS 2 or vice versa. This ensures that any specified load is supplied by a  
UPS while still providing a bypass path to cater for overloads. Further, the system can also be pro-  
grammed to reverse UPS1 between Normal and Bypass Modes so that each UPS is equally utilised.  
This interval is programmable from 1 to 4,320 hours (180 days).  
5.3.9 Frequency Converter Mode  
The NX UPS can be programmed into frequency converter mode for either 50Hz or 60Hz stable out-  
put frequency. The input frequency may vary from 40Hz to 70Hz. In this mode the static bypass oper-  
ation is disabled, and the battery becomes optional depending on any requirement to operate in  
battery mode (stored energy mode).  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Operation  
5.4  
Battery Management—Set During Commissioning  
5.4.1 Normal Function  
Constant charging current—Current can be set up to limit charging power.  
Constant boost voltage boost (if applicable)Voltage of boost charging can be set as required  
by the type of battery.  
For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not  
exceed 2.4V / cell.  
Float Charge—Voltage of float charging can be set as required by the type of battery.  
For VRLA, float charge voltage should be between 2.2V to 2.3V.  
Float Charge Temperature Compensation (optional)—A coefficient of temperature compen-  
sation can be as required by the type of battery.  
End of discharge protection (EOD)—If the battery voltage is lower than the EOD, the battery  
converter will shut down and the battery is isolated to avoid further battery discharge. EOD is  
settable from 1.6V to 1.75V per cell (VRLA) or 0.9 to 1.1 V per cell (NiCd).  
Battery Low Warning Time—Settable between 3 and 60 minutes. The default is 5 minutes.  
5.4.2 Advanced Functions (Software Settings Performed by the Commissioning Engineer)  
Battery Self-Test and Self-Service  
At periodic intervals 20% of the rated capacity of the battery will be discharged automatically. The  
minimum amount of load must exceed 20% of the nominal rating of the UPS module. If the load is less  
than 20%, auto-discharge cannot be executed. The periodic interval can be set from 30 to 360 days.  
The periodic testing can also be inhibited.  
Conditions—Battery float charge for at least 5 hours, load 20~100% of rated UPS capacity  
Trigger—Manually through through the command of Battery Maintenance Test in the LCD  
panel or automatically  
Battery Self-Test Interval—30-360 days (default setting is 60 days)  
5.5  
Battery Protection (settings by commissioning engineer)  
Battery Undervoltage Pre-warning  
The battery undervoltage pre-warning occurs before the end of discharge. After this pre-warning, the  
battery should have the capacity for 3 remaining minutes discharging with full load. The time is user  
configured from 3 to 60 minutes.  
Battery End of Discharging (EOD) Protection  
If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is settable  
from 1.6V to 1.75V per VRLA cell (or 1.0 to 1.1V per NiCd cell).  
Battery Isolator Open Warning  
If the battery isolator is open, this warning will occur.  
The external battery to the UPS through an external battery isolator, which is manually closed and  
electronically tripped via the UPS control circuits.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operating Procedures  
6.0 OPERATING PROCEDURES  
WARNING  
!
Hazardous mains and / or battery voltage present behind covers.  
No user-serviceable parts are located behind covers that require a tool for their removal. Only  
qualified service personnel are authorised to remove such covers.  
6.1  
Introduction  
The NX can operate in any of four modes, as shown in Table 9. This section provides instructions on  
switching between modes, resetting the UPS, switching the inverter On and Off and performing other  
operations.  
Table 9  
UPS operating modes  
Rotary Switch  
Position  
Operating Mode  
Description  
Normal Operation  
NORMAL  
The UPS is powering the load.  
The load power is supplied through the static bypass line. This may be  
considered as a temporary mode during load transfers between inverter  
and maintenance bypass or supply under abnormal operating conditions.  
BYPASS or  
NORMAL  
On Static Bypass  
On Test  
No load power is supplied by the UPS. The load is connected to utility  
power via the Maintenance Bypass Supply line. NOTE: The load is not  
protected against disturbances in AC input power in this mode.  
TEST  
The UPS is shut down but the load is connected to utility power via the  
Maintenance Bypass Supply line. NOTE: The load is not protected  
against disturbances in AC input power in this mode.  
On Maintenance  
Bypass  
MAINT  
NOTE  
1. The user controls and indicators mentioned in these procedures are identified in 7.0 -  
2. The audible alarm may sound at various points during these procedures. It can be canceled  
at any time by pressing the SILENCE ON/OFF push button.  
NOTE  
This unit refers to some modes and conditions that are set or adjusted using proprietary service  
software. To take advantage of all the available features for the NX, the unit must be  
commissioned by a Liebert factory-trained service engineer.  
6.1.1 Power Switches  
The UPS unit power switches are CB1 and SW1.  
• CB1-Input Current Breaker. Connects the utility supply to the UPS input.  
• SW1 - Rotary switch. Has four positions—NORMAL, BYPASS, TEST and MAINT—that corre-  
spond to different positions of the SW1-A/B/C/D.  
The positions of the rotary switch (SW1) are:  
• SW1-A—Output Isolator. Connects the output of the UPS to the load.  
• SW1-B—Neutral Isolator. Connects neutral to the UPS.  
• SW1-C—Bypass Isolator. Connects the UPS with the bypass supply.  
• SW1-D—Maintenance Bypass Isolator. Permits supply of the load directly by the bypass line for  
maintenance of the UPS unit.  
The functions of the rotary switch are shown in Table 10.  
Table 10  
Rotary switch configurations  
Rotary Switch  
Position  
MAINT  
(SW1-D)  
OUTPUT (SW1-A) BYPASS (SW1-C)  
NEUTRAL (SW1-B)  
NORMAL  
BYPASS  
TEST  
MAINT  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Operating Procedures  
6.2  
UPS Startup  
The NX must be fully installed and commissioned before startup, and external power isolators must  
be closed. Once those general conditions are met, the UPS may be started.  
6.2.1 Start-Up Procedure  
To start the UPS from a fully powered-down condition:  
1. Open the UPS door to gain access to the main power switches.  
WARNING  
!
During this procedure the output terminals will become live.  
If any load equipment is connected to the UPS output terminals, please check with the load  
user and ascertain whether it is safe to apply power to the load. If the load is not ready to  
receive power, then ensure that it is safely isolated from the UPS output terminals.  
CAUTION  
!
Do not operate the rotary switch too fast. Always wait at least 30 seconds when rotating the  
switch from one position to another  
2. Close CB1.  
3. Turn the rotary switch to TEST.  
The bypass static SCR (M2) closes automatically and the LCD begins to show start-up screens.  
The rectifier indicator flashes green while the rectifier is starting up. It stops flashing and  
becomes solid green about 30 seconds after the rectifier enters the normal operation state. After  
initialization, the bypass static switch closes.  
Because output switch SW1-A is still open, the UPS channels power through Maintenance Bypass  
Supply line (SW1-D). The bypass indicator extinguishes, provided that the bypass is normal.  
The UPS mimic display indicators will be:  
State  
Off  
Indicator  
Rectifier indicator  
Battery indicator  
Bypass indicator  
Inverter indicator  
Load indicator  
Status indicator  
Off  
Off  
Off  
Off  
Off  
WARNING  
!
Do NOT turn the rotary switch until the rectifier indicator stops flashing green.  
4. Turn the rotary switch to BYPASS.  
State  
Green  
Off  
Indicator  
Rectifier indicator  
Battery indicator  
Bypass indicator  
Inverter indicator  
Load indicator  
Status indicator  
Green  
Off  
Green  
Amber  
The maintenance switch SW1-D opens and output switch SW1-A closes. The UPS powers from  
static bypass instead of from maintenance bypass. The bypass and load indicators turn on. The  
design of the rotary switch ensures uninterrupted output.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operating Procedures  
5. Turn the rotary switch to NORMAL, then press the INVERTER ON control button for 2 seconds.  
The inverter will start and the inverter indicator will flash green. After the inverter is ready, the  
UPS transfers from bypass to inverter, the bypass indicator turns off and the inverter and load  
indicators turn on.  
The UPS is operating normally. The UPS mimic display indicators will:  
State  
Green  
Off  
Indicator  
Rectifier indicator  
Battery indicator  
Bypass indicator  
Inverter indicator  
Output indicator  
Status indicator  
Off  
Green  
Green  
Green  
6.2.2 Verify Switching Between Operation Modes  
Switch from normal mode to battery mode  
• Open CB1 to enter battery mode. This breaks the utility connection to the NX.  
To return to normal mode, wait a few seconds and close CB1. The rectifier will restart automati-  
cally after 10 seconds and resume feeding power to the inverter.  
Switch from Normal Mode to Bypass Mode  
• Press INVERTER OFF button to switch to bypass mode.  
NOTE  
In bypass mode, the load is being powered by the utility and is not receiving conditioned power  
through the inverter.  
Switch from Bypass Mode to Normal Mode  
• Turn the rotary switch to NORMAL.  
• In bypass mode, press the INVERTER ON button. When the inverter is ready, the UPS will  
switch to normal mode.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operating Procedures  
6.3  
Switching the UPS from Normal to Maintenance Bypass  
Follow the procedure below to transfer the load from the inverter output to the Maintenance Bypass  
line of the UPS.  
CAUTION  
!
Before performing this operation, read the messages on the LCD to be sure that bypass supply  
is regular and the inverter is synchronous with it. If those conditions are not present, there is  
a risk of a short interruption in powering the load.  
This procedure assumes that UPS is operating normally.  
1. Press the INVERTER OFF button on the right side of the operator control panel for longer than 2  
seconds.  
The Inverter indicator will turn off and the status indicator (6) will turn amber and an audible  
alarm will sound. The load will transfer to static bypass and the inverter will shut off.  
NOTE  
Pressing the Alarm Silence Switch cancels the audible alarm, but leaves the warning message  
displayed until the appropriate condition is rectified.  
2. Open the UPS door to gain access to the main power switches, SW1 and CB1.  
3. Turn the rotary switch to BYPASS position. The UPS Bypass Static Switch still supply power to  
load.  
4. Turn the rotary switch to TEST. The load is now on maintenance bypass.  
5. Turn the rotary switch to MAINT.  
6. Open rectifier switch CB1. All operator indicators and messages will turn off as the utility driven  
internal power supplies decay. The unit will power down, but the load will continue to be supplied  
by the manual maintenance bypass.  
WARNING  
!
Wait 5 minutes for the internal DC busbar capacitors to discharge before attempting to  
remove the internal protective barriers.  
WARNING  
!
Even with the UPS rotary switch in maintenance bypass position portions of the unit are still  
energized. Service is to be performed by qualified personnel only.  
CAUTION  
!
The load equipment is not protected from normal supply aberrations when operating in the  
maintenance bypass mode.  
6.4  
Powering Down the UPS  
To power down the UPS completely, follow the procedures in 6.3 - Switching the UPS from Nor-  
To completely isolate the UPS from the AC supplies, the main external power input isolator (both iso-  
lators, where separate supplies are provided for rectifier and bypass) should be opened (see  
WARNING  
!
To prevent injury to personnel, lockout or tagout the service supplies.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operating Procedures  
6.5  
Powering Down the UPS and Maintaining Power to Load  
NOTE  
An external Maintenance Bypass Cabinet must be installed before attempting to perform the  
following procedure  
If the UPS needs to be shut down completely while maintaining power to the load, follow these steps:  
Bypass.  
2. Close the external maintenance bypass rotary switch to Maint position.  
WARNING  
!
On the primary input distribution panel, which is often located distant from the UPS area, a  
label should be posted advising service personnel that the UPS circuit is under maintenance.  
WARNING  
!
Wait 5 minutes for the internal DC busbar capacitors to discharge.  
The UPS is now completely powered down.  
NOTE  
The maintenance bypass power switch may be operated at any time while the UPS is powered  
down to connect the load to the maintenance bypass supply if required  
The procedure can be performed only after the installation has been completed (which includes the  
maintenance bypass cabinet), after the system has been placed in operation by authorized personnel.  
See Figure 30 for more information.  
Figure 30 Example of configuration for single UPS with external maintenance bypass cabinet.  
CB1  
SW  
CB2  
3P  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operating Procedures  
6.6  
Emergency Shutdown With EPO  
This circuit has been designed to switch off the UPS in emergency conditions (i.e., fire, flood, etc.). The  
system will turn off the rectifier, inverter and stop powering the load immediately (including the  
inverter and bypass), and the battery stops charging or discharging.  
If the input utility is present, the UPS’s controls will remain active; however, the output will be  
turned off. To remove all power from the UPS, the external feeder breaker should be opened.  
6.7  
Auto Restart  
When the main and bypass sources fail, the UPS draws power from the battery system to supply the  
load until the batteries are depleted. When the UPS reaches its end of discharge (EOD) threshold, it  
will shut down.  
The UPS will automatically restart and enable output power:  
• After utility power is restored  
• If “Auto Recovery after EOD Enabling” is enabled  
• After the “Auto Recovery after EOD Delay Time” expires (the default delay is 10 minutes).  
If the “Auto Recovery after EOD Enabling” feature is disabled, the user may restart the system man-  
ually by pressing “Fault Clear” button.  
6.8  
Reset After Shutdown for Emergency Stop (EPO Action) or Other Conditions  
Once all appropriate measures have been taken to correct the problem indicated by the alarm mes-  
sage appearing on the operator control panel display, carry out this procedure to restore the UPS to  
regular operation following an EPO action or for the following reasons: Inverter Overtemperature,  
Cut-off Overload, Battery Overvoltage, excessive switching (BYP: XFER COUNT BLOCK), etc.  
When the user confirms that the fault is cleared:  
1. Press the FAULT CLEAR button to let the system exit the Emergency Off state.  
2. Press the INVERTER ON button on the right side of the operator control panel for longer than  
2 seconds.  
NOTE  
The rectifier will start again, and the bypass will begin to power the load (for units with  
internal battery contactor installed, the battery contactor will close). The Rectifier indicator  
flashes while the rectifier is starting up. When the rectifier enters the normal operation state  
(about 30 seconds), the rectifier indicator turns green.  
NOTE  
The rectifier will be turned On automatically when the overtemperature fault disappears at  
5 minutes after the disappearance of overtemperature signals.  
After the EPO button is pressed, if the input utility is removed, the UPS will shut down completely.  
When input utility is returned, if the rotary switch (SW1) is in either Bypass or in Normal position,  
the UPS will start up on Bypass. There will be power at the output terminals of the UPS.  
WARNING  
!
If the rotary switch is in the Maint. position and input utility is present, there will be power at  
the output terminals of the UPS.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operating Procedures  
6.9  
Language Selection  
The LCD menus and data display are available in 12 languages: Chinese, Dutch, English, French,  
German, Italian, Japanese, Polish, Portuguese, Russian, Spanish and Swedish.To select a different  
language than the one being displayed:  
1. From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the  
screen.  
2. Press F2 and F3 (left and right arrows) as needed to select the Language menu.  
3. Press F1 (shift) to move the cursor to the data and settings area of the LCD.  
4. Use F2 and F3 (up and down) to select the required language.  
5. Press the F4 (enter) key to accept the language selection.  
6. Return to the main menu by repeatedly pressing F1 (ESC) as needed; all text on the LCD will now  
be displayed in the selected language.  
6.10 Changing the Current Date and Time  
To change the system date and time:  
1. From the main menu, press the F1 (shift) key to move the cursor to the menu at the top of the  
screen.  
2. Press F2 and F3 (left and right arrows) as needed to select the Settings menu.  
3. Press F1 (shift) to move the cursor to the data and settings area of the LCD.  
4. Use F2 and F3 (up and down) to select the Date & Time option, then press F4 (enter).  
5. Position the cursor on the row in which the date and time are displayed, then press F4 (enter).  
6. Using the F2 and F3 (up and down) keys, enter the current time and date information.  
7. Press F4 (enter) to save the settings, then press F1 (ESC) to return to the main menu.  
6.11 Command Password  
Password protection is used to limit the control functions accessible to the operator. The default pass-  
word is 12345. This password provides access to UPS and battery test functions.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operating Procedures  
6.12 Isolating One Module in a Multi-Module System  
NOTE  
The Multi-Module system must have at least one UPS module redundant in the system and  
have an external output breaker installed with interlocking cables connected to the UPS  
module. The inverter firmware in each UPS in the system must be I140 or greater.  
1. With all UPS modules in the system in Normal mode, open the external output isolator.  
NOTE  
Opening the external output isolator under these condtions puts the UPS module into Standby  
mode. This is indicated by a flashing inverter LED and the message “Check UPS output.”  
An “Inverter asynchronous” alarm is also normal. The remaining UPS modules will remain on  
line and “Parallel comm fail” will annunciate.  
2. Press the UPS EPO to isolate the batteries.  
3. Open the UPS door to gain access to the main power switches SW1 and CB1.  
4. Turn the rotary switch (SW1) to the Bypass position then continue to rotate to Test.  
NOTE  
With the UPS external output breaker open and auxiliary switches closed the UPS control will  
enable the UPS switch to be rotated through “Bypass” without initiating the remaining on line  
UPS modules to transfer to Bypass.  
5. Open rectifier input breaker CB1.  
WARNING  
!
Hazardous Battery Voltage  
No operator serviceable parts are located behind covers that require a tool for their removal.  
Only qualified service personnel are authorised to remove such covers.  
The UPS battery and connecting terminals remains energized at hazardous voltage levels at  
all times. The battery is located behind protective covers that require a tool for their removal:  
inside the UPS cabinet, inside a free-standing battery cabinet or on open racks inside a  
dedicated battery room that may be locked.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operating Procedures  
6.13 Inserting One Module into a Multi-Module System  
This procedure is indicated to reintegrate a UPS module that has been previously isolated from other  
modules of a group of paralleled UPS modules. It is assumed that the installation is complete, the sys-  
tem has been commissioned by authorized personnel and the external power isolators are open.  
WARNING  
!
Mains voltage will be applied to UPS output terminals.  
No operator serviceable parts are located behind covers that require a tool for their removal.  
Only qualified service personnel are authorised to remove such covers.  
1. Open the UPS door to gain access to the main power switches.  
2. Rotate the switch to Test position. The LCD display becomes active.  
3. Close the Input breaker CB1  
The Rectifier indicator flashes on the UPS mimic panel during the startup of rectifier and  
becomes steady green once the rectifier reaches normal operation state after about 30s.  
4. Close external battery circuit breaker QF1 (where an external battery is used). This breaker is  
located inside the battery cabinet (if used) or is otherwise adjacent to the battery racks  
5. Following battery availability being detected by the UPS, the red battery indicator extinguishes  
moments after when the battery charger starts operation.  
6. Rotate switch to Bypass position  
7. Turn the rotary switch to NORMAL.  
8. Close external output power isolators.  
9. Press the INVERTER ON control button for 2 seconds.  
The inverter will startup and the inverter indicator will flash while it synchronizes to the load  
voltage and frequency. After the inverter is ready, the UPS connects to the load, the inverter indi-  
cator becomes steady green and the output indicator becomes green.  
10. Check that no “Warning” message is displayed in the top right corner of the LCD Monitor and the  
status of the indicators as follows:  
# LED LED Function  
Status  
1
2
3
4
5
6
Rectifier indicator green  
Battery indicator  
Bypass indicator  
Inverter indicator  
Output indicator  
Alarm indicator  
off  
off  
green  
green  
off  
The UPS is now operating in NORMAL mode.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operator Control Panel and Display  
7.0 OPERATOR CONTROL PANEL AND DISPLAY  
7.1  
Introduction  
The operator control panel and display is located on the front door of the UPS. The panel is the access  
point for operator control and monitoring of all measured parameters, UPS and battery status and of  
event and alarm logs.  
Figure 31 UPS control and display panel  
The operator control panel is divided into three functional areas  
Mimic Power Flow Chart  
Graphic LCD monitor with menu keys  
Direct Access keys  
6
3
Liebert NX  
020kVA 3X3  
2005-10-22  
Single  
17:32:20  
Normal  
Status  
8
1
4
5
Bypass  
Output  
Load  
L1-N/L2  
L1-N/L2 voltage(V) 229.5  
L2-N/L3  
229.5  
24.5  
49.97  
397.5  
1.00  
L3-N/L1  
229.5  
24.5  
49.97  
397.5  
0.99  
EPO  
2
L-N current (A)  
Frequency(Hz)  
L-L voltage(V)  
Power Factor  
24.5  
49.97  
397.5  
0.99  
INVERTER ON  
INVERTER OFF  
7
Rotary SW. normal pos.  
Manual turn on  
07-07  
07-07  
17:24  
17:29  
07-07  
17:30  
Normal mode  
?
FAULT CLEAR  
SILENCE ON/OFF  
F1  
F2  
F3  
F4  
HELP  
Table 11  
UPS control and display panel components  
Component #  
Button  
Function  
Function  
1
2
3
4
5
6
7
8
Rectifier (Input AC to DC)  
Battery (DC Back-up)  
Bypass Input  
EPO  
Emergency Power Off button  
Inverter start button  
Inverter shutdown button  
Reset button  
Inverter ON  
Inverter OFF  
Fault Clear  
Silence On/Off  
Inverter (DC to AC)  
Load (AC Output)  
Audible Alarm Mute  
UPS Status and Alarm indicator  
Audible Alarm (Buzzer)_  
Emergency Power Off Button cover  
F1-F4, Help  
LCD Menu keys  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operator Control Panel and Display  
7.1.1 Mimic Power Flow  
The LEDs mounted on the mimic flow chart represent the various power paths and current UPS oper-  
ational status.  
Table 12 Rectifier indicator—1  
Green  
Rectifier in Normal Operation  
Flashing  
Green  
Input AC Normal, but rectifier not operating  
Red  
Off  
Rectifier Failed  
Rectifier Not operating, Input AC Not Available or out of normal range  
Table 13 Battery indicator—2  
Green  
Battery Normal, but discharging and powering the load  
Flashing  
Green  
Battery End of Discharge pre-warning  
Battery abnormal (Failed, Absent or Polarity Reversed) or Battery  
Converter abnormal  
(Failed, overcurrent, overtemperature)  
Red  
Off  
Battery and Converter Normal, Battery charging.  
Table 14 Bypass indicator—3  
Green  
Red  
Load on Bypass power  
Bypass not available, out of normal range or Static bypass switch fault.  
Bypass Normal, load not on bypass  
Off  
Table 15 Inverter indicator—4  
Green  
Inverter Normal and powering the load  
Flashing  
Green  
Inverter ON, starting up, synchronising,  
or standing by (ECO mode)  
Red  
Off  
Inverter failed  
Inverter not operating  
Table 16 Load indicator—5  
Green  
Red  
UPS output ON and Normal  
UPS output ON and Overloaded  
UPS output OFF.  
Off  
Table 17 Status (Alarm) indicator—6  
Green  
Yellow  
Red  
Normal Operation  
UPS Warning e.g. AC Input Failure  
UPS fault e.g. Fuse or Hardware failure  
7.1.2 Audible Alarm (Buzzer)  
UPS activity is accompanied by the following sounds  
Table 18 Audible alarm key  
Single beep Direct Access key acknowledgement  
One beep  
UPS Warning e.g. AC Input Failure  
per second  
Continuous Fault e.g. Fuse or Hardware failure  
beep  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
                 
Operator Control Panel and Display  
7.1.3 Direct Access Push Buttons (Keys)  
Disconnects Power to the Load. Disables rectifier, inverter, static bypass  
and battery operation.  
Emergency Power Off (EPO)  
Inverter ON  
Inverter OFF  
Fault clear  
Enables Inverter Operation  
Disables Inverter Operation  
Resets blocked UPS functions (subject to any fault being cleared)  
Toggle type buzzer mute. Any new fault re-enables the buzzer.  
Silence ON/OFF  
Press and hold Direct Access key briefly until acknowledged by a single beep.  
7.1.4 LCD Monitor and Menu keys  
The user-friendly and menu-driven 320 x 240 dot graphic LCD monitor displays real time data and at  
the same time stores 512 historical records that can retrieve for reference and diagnosis.  
The user can perform commands or easily browse through the input, output, load and battery param-  
eters. For quick reference, the UPS status and any warnings are always highlighted without the need  
of navigating through the menu. The versions of converter firmware, inverter firmware and internal  
monitor firmware can also be displayed on the LCD.  
Menu keys F1 to F4 are used to navigate within the graphic LCD monitor windows.  
Table 19 Menu key Icons and their meaning  
Key  
F1  
F2  
F3  
F4  
Help  
Window Type 1  
?
LEFT  
RIGHT  
HELP  
ENTER  
Next Data Window  
ESC  
Window Type 2  
Escape  
UP  
DOWN  
Figure 32 Graphic LCD monitor windows and keypad  
Liebert NX  
20kVA 3X3  
2005-10-22  
Unit #1  
17:32:20  
Normal  
1 - UPS System  
Window  
Bypass  
Output  
2 - UPS Menu  
Window  
Main  
A(AB)  
B(BC)  
220  
C(CA)  
220  
Vphase V  
Iphase A  
Freq. Hz  
Vline V  
P.F.  
220  
20.5  
50.1  
380  
20.5  
50.1  
380  
20.5  
50.1  
380  
3 - UPS Data  
Window  
0.99  
0.99  
0.99  
Input breaker closed  
Manual turn on  
UPS in normal mode  
01-12 12:28:16  
01-12 12:30:06  
01-22 12:30:16  
4 - Current Record  
Window  
?
5 - Keypad Window  
F1  
F2  
F3  
F4  
HELP  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operator Control Panel and Display  
The function of keys F1 to F4 is shown by a self-explanatory icon as appropriate for the particular  
window. As shown in Figure 32 above, pressing F1 moves the cursor (resting in “OUTPUT”) from the  
UPS Menu Window (2) to current record window (4) where it would first rest in “Input breaker closed’.  
In a similar manner, pressing F2 would move the cursor from the Output data window to the Bypass  
data window.  
The summary menu tree is shown below. Refer to 7.2 - All Status and Event Messages Displayed  
on the UPS Front Panel for a detailed description of each menu item.  
Figure 33 Menu tree  
Mains (input)  
TX Input *  
Bypass  
Output  
TX Output **  
L-N voltage (V)  
L-N current (A)  
Frequency (Hz)  
L-L voltage (V)  
Power factor  
L-N voltage (V)  
L-L voltage (V)  
L-N voltage (V)  
Frequency (Hz)  
L-L voltage (V)  
L-N voltage (V)  
L-N current (A)  
Frequency (Hz)  
L-L voltage (V)  
Power factor  
L-N voltage (V)  
L-L voltage (V)  
System  
Battery  
Records  
Load  
Sout (kVA)  
Pout (kW)  
Qout (kVAR)  
Single unit, no  
parallel data  
Battery voltage (V)  
Battery current (A)  
(history log)  
Sout (kVA)  
Pout (kW)  
Qout (kVAR)  
Loadlevel %  
Crest factor  
Battery temperature (°C)  
Remain Time Min.  
Battery capacity (%)  
Battery boost charging  
Battery float charging  
Battery disconnected  
Language  
Settings  
Command  
Version  
(Choices for  
display)  
Display contrast  
Date format set  
Date & time  
Battery maintenance test  
Battery capacity test  
System test  
UPS version  
UPS model  
Comm1 baud rate  
Comm2 baud rate  
Comm3 baud rate  
Communication address  
Communication mode  
Callback times  
Phone No.1  
Phone No.2  
Phone No.3  
Command password  
Stop testing  
Freshening Charge  
Stop Freshening  
Charge  
* When configured, input transformer voltages are  
displayed on the front LCD. When not activated, the  
values are hidden.  
** When configured, output transformer voltages are  
displayed on the front LCD. When not activated, the  
values are hidden.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operator Control Panel and Display  
7.1.5 Detailed Description of Menu Items  
The description that follows refers to the graphic LCD monitor window shown on Figure 32.  
UPS System Window: This fixed-pane window displays current time and date and identifies the UPS,  
its configuration and its status.  
Table 20 UPS system window  
Description  
Liebert NX  
2005-10-22  
12:30:36  
Explanation  
UPS family name  
YYYY-MM-DD (see Settings menu for other date formats)  
Current Time (24 hr HH:MM:SS format)  
30kVA = UPS rated output, 3 x 3 = 3-phase input and output  
30kVA-3x3  
(Configuration)  
Single = single double-conversion unit  
ECO = single stand-by unit with double-conversion fall-back  
Single, ECO, Master, Slave or Unit # 1 Master = master in a 1+1 Hot Stand By system  
Slave = slave in a 1+1 Hot Stand By system  
Unit # 1 = of max 6 double-conversion units in a parallel system  
(Status)  
Normal, Warning or Fault  
Normal = UPS operating Normal  
Warning = System attention required, e.g. AC Input Failure  
Fault = UPS Fuse or Hardware Failure  
Menu and Data Window  
Use the horizontal arrow keys to navigate between any of the selectable menu and data windows.  
Table 21 Descriptions of UPS menus and data window items  
Menu  
Type  
Item Type  
Explanation  
L-N voltage (V)  
L-N current (A)  
Frequency (Hz)  
L-L voltage (v  
Power factor  
L-N voltage (V)  
L-L voltage (V)  
L-N voltage (V)  
Frequency (Hz)  
L-L voltage (A)  
L-N voltage (V)  
L-N current (A)  
Frequency (Hz)  
L-L voltage (V)  
Power factor  
L-N voltage (V)  
L-L voltage (V)  
Sout (kVA)  
Phase voltage  
Phase current  
Mains  
(input)  
Input frequency  
Line-line voltage  
Power factor  
Phase voltage  
TX Input  
Bypass  
Line-line voltage  
Phase voltage  
Bypass frequency  
Line-line voltage  
Phase voltage  
Phase current  
Output  
TX Output  
Load  
Input frequency  
Line-line voltage  
Power factor  
Phase voltage  
Line-line voltage  
Sout: Apparent power  
Pout: Active power  
Qout: Reactive power  
The percent of the UPS rating load  
Output current Crest Factor  
Pout (kW)  
Qout (kVAR)  
Loadlevel %  
Crest factor  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Operator Control Panel and Display  
Table 21 Descriptions of UPS menus and data window items (continued)  
Menu  
Type  
Item Type  
Sout (kVA)  
Pout (kW)  
Explanation  
Sout: Apparent power  
Pout: Active power  
Qout: Reactive power  
System  
Qout (kVAR)  
When configured as a single unit, UPS has only native load, no system  
load.  
Single unit, no parallel data  
Battery voltage (V)  
Battery current (A)  
Battery temperature (°C)  
Remain Time Min.  
Battery boost charging  
Battery float charging  
Battery disconnected  
(history log)  
Battery bus voltage  
Battery bus current  
Internal battery temperature °C  
Battery run time remaining  
Battery is boost charging  
Battery is float charging  
Battery is not connected  
Displays all records in the history log  
Battery  
Records  
Language  
(choices for text displayed) User may select any of 12 languages for LCD text.  
Display contrast  
Adjust the LCD display contrast  
Date format set  
Choose the format for date display: M/D/Y, D/M/Y, M/D/Y, Y/M/D  
Set the date and time  
Date & time  
Comm1 baud rate  
Comm2 baud rate  
Comm3 baud rate  
Communication address  
Communication mode  
Communication baud rate setting for Intellislot 1  
Communication baud rate setting for Intellislot 2  
Communication baud rate setting for Intellislot 3  
This setting is applicable to RS485 communication mode  
Communication Mode Setting  
Settings  
When Intellislot 1 Communication mode is Modem, this parameter sets  
the number of times a number is redialed to send an alarm notification.  
Callback times  
Phone No.1  
Phone No.2  
When Intellislot 1 Communication mode is Modem, this is the first phone  
number to be dialed (to send an alarm notification).  
When Intellislot 1 Communication mode is Modem, this is the second  
phone number to be dialed (to send an alarm notification).  
When Intellislot 1 Communication mode is Modem, this is the third phone  
number to be dialed (to send an alarm notification).  
Phone No.3  
Command password  
Battery maintenance test  
User can modify the command password.  
This test performs a partial discharge of the battery to obtain a rough  
estimate of the battery capacity. Load must be between 20% and 100%.  
This test performs a full discharge of the battery to obtain a precise  
measure of the battery capacity. Load must be between 20% and 100%.  
Battery capacity test  
System test  
Command  
(start/stop  
battery &  
system  
This is a self-test of the UPS. When the user activates this function, a pop-  
up window appears about 5 seconds later to show the results.  
Manually stops a battery maintenance test, battery capacity test or system  
test.  
Stop testing  
tests)  
This command will allow a temporary Equalize charge for the batteries.  
This charge is configurable for 1 to 36 hours  
Freshening Charge  
Stop Freshening Charge  
UPS version  
Manually stop a Freshening Charge  
Provides UPS firmware version numbers for the inverter, rectifier and  
software display board.  
Version  
UPS model  
Provides UPS model information—for example, 400V-50Hz.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operator Control Panel and Display  
Current Record Window  
Keeps a log the events that resulted in the current mode of operation. Ignores transient conditions  
that have been resolved.  
Use “page” (F1) and up / down arrow to read the events.  
For a complete history log, refer to the Records tab of the Menu and Data Window.  
Refer to Table 22 for a complete list of supported status messages.  
7.2  
All Status and Event Messages Displayed on the UPS Front Panel  
This is the complete list of UPS events and status messages supported for display in either the Record  
window (Historic data) or in the Current window (Prevailing data) as described in 7.1.4 - LCD Moni-  
Table 22  
Message  
UPS messages  
Description / Suggested Action (if any)  
Inverter Comm. Fail  
Rectifier Comm. Fail  
Internal RS485 communication failure between monitor and inverter  
Internal RS485 communication failure between monitor and rectifier  
The CAN communication between different UPSs within a parallel system fails.  
1.Check if there are some UPSs not powered on in the parallel system. If so, power on these  
UPSs and check if the alarm disappears.  
Parallel Comm. Fail  
2. Press Fault Clear push button.  
Battery Overtemp.  
Ambient Overtemp.  
Battery Fault  
The Battery temperature is over limit. Check the battery temperature and ventilation  
The Ambient temperature is over limit. Check the ventilation of UPS room.  
Battery detected faulty (Reserved)  
Replace Battery  
Battery test failed, Battery should be replaced.  
Before the end of discharge, battery undervoltage pre-warning should occur. After this pre-  
warning, battery should have the capacity for 3 minutes discharging with full load. The time is  
user-configured from 3 to 60 minutes.  
Battery Low Pre-warning  
Shut down the load in time.  
Battery End of Discharge  
Mains Volt. Abnormal  
Inverter turned off due to low battery voltage. Check the utility failure and try to recover it.  
Mains Voltage exceeds the upper or lower limit and results in rectifier shutdown.  
Check the input line-to-neutral voltage amplitude of rectifier.  
Mains Voltage is undervoltage with derated load.  
Check the input line-to-line voltage amplitude of rectifier  
Mains Undervoltage  
Mains frequency is out of limit range and results in rectifier shutdown.  
Check the rectifier’s input voltage frequency  
Mains Freq. Abnormal  
Rectifier Fault  
Rectifier detected faulty. Rectifier shuts down. Battery discharges.  
The temperature of heat sink is too high to keep the rectifier running.  
The UPS can recover automatically. Check the environment and ventilation.  
Rectifier Overtemp.  
Batt. Contactor Fail  
Batt. Charger Fault  
Control Power 1 Fail  
Mains Phase Reversed  
Rectifier Overcurrent  
Soft Start Fail  
Battery contactor or circuit breaker not responding to control signals.  
The voltage of the battery charger is too high.  
UPS operates but Redundant Control Power is not available.  
AC Input phase sequence is reversed.  
Rectifier is overloaded.  
Rectifier could not start due to low DC bus voltage  
This alarm is triggered by an inverter software routine when the amplitude or frequency of  
bypass voltage is beyond the normal range.  
The amplitude threshold is fixed for positive and negative 10% rating.  
This alarm automatically resets once the bypass voltage goes normal.  
1. First verify that the bypass voltage and frequency displayed on the panel is within the  
selected range. Note here the rated voltage and frequency are specified by “Output voltage  
level” and “Output frequency level” respectively.  
Bypass Unable to Trace  
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and  
frequency presented to the UPS. Check the external supply if it is found to be faulty.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Operator Control Panel and Display  
Table 22  
Message  
UPS messages (continued)  
Description / Suggested Action (if any)  
This alarm is triggered by an inverter software routine when the amplitude or frequency of  
bypass voltage exceeds the limit.  
This alarm automatically resets once the bypass voltage goes normal.  
First check if there are some relevant alarms such as “Bypass disconnect open”, “Bypass phase  
reverse” and “Mains neutral lost”. If they appear, solve them first.  
1. Then verify that the bypass voltage and frequency displayed on the panel is within the bypass  
limit. Note here the rated voltage and frequency are specified by “Output voltage level” and  
“Output frequency level” respectively.  
Bypass Abnormal  
2. If the displayed voltage is believed to be abnormal, then verify the bypass voltage and  
frequency presented to the UPS. Check the external bypass supply if it is found to be faulty. If  
the utility is likely to trigger this alarm frequently, the bypass limit can be changed a little larger  
through the configuration software according to the customer’s agreement.  
This alarm is triggered by an inverter software routine when the inverter and bypass waveforms  
are misaligned by more than 6 degrees in phase. This alarm resets automatically once the  
condition is no longer true.  
1. First check if the alarm “Bypass unable to trace” or “Bypass abnormal” occurs. If so, solve it  
first.  
Inverter Asynchronous  
Inverter Fault  
2. Verify the waveform of the bypass voltage. If it is too distorted, ask the customer to verify and  
seek any possible measurements.  
Inverter output voltage beyond limits. Load transfers to bypass.  
The temperature of the inverter heat sink is too high to keep inverter running.  
This alarm is triggered by the signal from a temperature monitoring thermostat on the inverter  
bridge heat sink.  
The UPS will recover automatically after a 5 minute delay from the disappearance of the  
overtemperature signal.  
If the overtemperature condition is true, then check for and verify:  
1. high ambient air temperature.  
Inverter Overtemp.  
2. blocked cooling airway.  
3. any fan failure.  
4. prolonged inverter overload  
Fan Fault  
At least one of the cooling fans has failed  
At least one of the static switches of inverter side is open or short circuit. This fault is locked until  
power off.  
Inverter STS Fail  
At least one of the static switches of bypass side is open or short circuit. This fault is locked until  
power off  
Bypass STS Fail  
Operation Invalid  
Output Fuse Fail  
Control Power 2 Fail  
This record is registered following an incorrect operation:  
At least one of the inverter output fuses is blown. Inverter shuts down. Load transfers to bypass.  
UPS operates but Redundant Control Power is not available.  
The UPS is confirmed to be overload when the load arises above 105% nominal rating.  
The alarm automatically resets once the overload condition is removed.  
1. Confirm that the alarm is true by checking the load percent indicated on the LCD panel to  
determine which phase is being overloaded.  
Unit Over load  
2. If the alarm is true, measure the actual output current to verify that the indications are valid.  
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing  
error can also leads to the alarm.  
The UPS parallel system is confirmed to overload when the total load arises above 105%  
nominal rating for the set basic number of UPSs. The alarm automatically resets once the  
overload condition is removed.  
1. Confirm that the alarm is true by checking the system load percent indicated on the LCD  
panel to determine which phase is being overloaded.  
System Over load  
2. If the alarm is true, measure the actual output current to verify that the indications are valid.  
Disconnect unnecessary load and ensure the safety. In a parallel system, a severe load sharing  
error can also leads to the alarm.  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operator Control Panel and Display  
Table 22  
Message  
UPS messages (continued)  
Description / Suggested Action (if any)  
The UPS is confirmed to overload and the overload times out.  
Note 1: the highest loaded phase will indicate overload timing-out first.  
Note 2: When the timer is active then alarm “unit overload” should also be active as the load is  
above nominal.  
Note 3: When the timer has expired, the inverter Static Switch is opened and the load  
transferred to bypass. The inverter shutdown and will restart after 10 seconds.  
Note 4: If the load decreases lower than 95% after 5 minutes, the system will transfer back to  
inverter mode.  
Unit Over load Timeout  
Confirm that the alarm is genuine by checking the load percent indicated on the LCD. If an  
overload is indicated then check the load, and investigate any additional load connected prior to  
the alarm (if applicable).  
Byp. Abnormal Shutdown  
Inverter Over Current  
Both bypass and inverter voltages unavailable. Load interruption  
Inverter Pulse Width Modulation module overloaded.  
The phase sequence direction of bypass voltage is reversed.  
Normally, the phase of phase B lags 120 degrees behind phase A, and the phase of phase C  
lags 120 degrees behind phase B.  
Bypass Phase Reversed  
Verify that the phase rotation of the bypass supply presented to the UPS is correct, and rectify it  
if it is found to be in error  
A transfer to bypass occurred due to a large step load. The UPS should recover automatically.  
Turn on connected equipment in sequential order to reduce the step loading of the inverter.  
Load Impact Transfer  
Transfer Time-out  
The load is on bypass power due to excessive number of transfers that occurred within the last  
hour.  
The UPS will recover automatically and will transfer the load back to inverter power within an  
hour.  
Load Sharing Fault  
DC Bus Abnormal  
UPS modules within a parallel system are not sharing the load current equally.  
DC input voltage to inverter beyond limits. Inverter shuts down. Load transfers to bypass.  
The whole paralleled UPS system transferred to bypass at the same time. This message will  
appear on the UPS which passive transfer to bypass  
System Transfer  
Malfunction of the paralleling control circuits of this UPS module. Can cause “System Transfer”  
to bypass.  
Parallel Board Fault  
Rectifier, inverter and battery converter were shutdown because DC bus voltage is too high.  
Check whether there is a fault in rectifier side. If no, then check whether overload occurs.  
Restart the inverter after resetting the fault  
DC Bus Over Voltage  
Parallel Connect Fault  
The parallel cables are not connected correctly in a parallel system.  
Reset the fault by pressing the “fault clear” button, then restart the inverter by pressing the  
“inverter on” button.  
Bypass Over Current  
LBS Active  
Bypass current is over limit above 135% rating. The UPS just alarms and does nothing.  
Load Bus Synchronisation is active. The UPS is acting as an LBS master or slave in a dual bus  
configuration.  
Setting Save Error  
Mains Neutral Lost  
Protocol version clash  
Battery ground fault  
Inv. Turned On Manually  
Inv. Turned Off Manually  
EPO  
History records not saved. (Reserved)  
AC Input mains reference neutral not detected.  
Firmware incompatibility between Monitor Board and Digital Signal Processor Board.  
Battery leakage to ground detected (option)  
Manual Turn On via front panel  
Manual Turn Off via front panel  
Emergency Power Off direct access key pressed or external command received  
Prompt to press “enter” key to acknowledge that an interrupted load transfer to bypass will  
happen.  
Transfer Confirm  
Transfer Cancel  
Unit Off Confirm  
Prompt to press “ESC” key to avoid that an interrupted load transfer to bypass will happen.  
Prompt to press “enter” key to acknowledge that the UPS will be disconnected from other  
paralleled UPS modules.  
Prompt to press “enter” key to acknowledge that the all paralleled UPS will be disconnected  
from the load.  
System Off Confirm  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operator Control Panel and Display  
Table 22  
UPS messages (continued)  
Message  
Description / Suggested Action (if any)  
Fault clear direct access key pressed  
Silence On/Off direct access key pressed  
Fault Reset  
Alarm Silence  
Inverter failed to turn on when Inverter On direct access key was pressed. This may be as a  
result of Invalid Operation (Maintenance bypass on) or DC bus or rectifier not ready.  
Turn On Fail  
Alarm Reset  
Bypass Mode  
Normal Mode  
Battery Mode  
Fault clear or Silence On/Off direct access key pressed  
Load supplied from AC input bypass supply.  
Load supplied from Inverter output through double conversion of the AC mains input supply.  
Load supplied from Inverter output through double conversion of the Battery supply.  
Load supplied from Inverter output through shared double conversion of the AC mains input  
supply and of the Battery supply.  
Source share mode  
UPS Shutdown  
UPS Shutdown, output power-down  
Check UPS Output  
Generator Connected  
BCB open  
Inverter off during normal startup (diagnostics information only)  
Generator active signal received. Source share mode may be activated pending UPS settings.  
Battery Circuit Breaker status (open)  
BCB closed  
Battery Circuit Breaker status (closed)  
Battery Float Charging  
Battery Boost Charging  
Battery Discharging  
Battery Period Testing  
Batt. Capacity Testing  
Batt. Maint. Testing  
UPS System Testing  
Inverter in Setting  
Battery status (Float charge mode)  
Battery status (Boost charge mode)  
Battery status (discharge mode)  
Automatic periodic battery maintenance discharge test (20% capacity discharge)  
User initiated battery capacity discharge test (100% capacity discharge)  
User initiated maintenance discharge test (20% capacity discharge)  
User initiated UPS self test  
Inverter starting up and synchronising  
Rectifier in Setting  
MBP-T cabinet Fan Fault  
Ext Input TX Overtemp  
Ext Output TX Overtemp  
Battery Room Alarm  
Rotary Sw. Test Pos.  
Rotary Sw. Normal Pos.  
Rotary Sw. Bypass Pos.  
Rotary Sw. Maint. Pos.  
Battery Contactor Open  
Battery Contactor Close  
Battery Reverse  
Rectifier starting up and synchronising  
Maintenance bypass cabinet fans fault.  
External Input Isolation Transformer Over Temperature  
External Output Isolation Transformer Over Temperature  
Environment in Battery Room Needs Attention  
Rotary switch is in test position.  
Rotary switch is in normal position.  
Rotary switch is in bypass position.  
Rotary switch is in maintenance position.  
Battery Contactor Open  
Battery Contactor Closed  
Connect the battery again and check the wiring of batteries  
Check the battery and the wiring of batteries  
After UPS was shutdown at EOD, inverter auto starts when utility restore  
Rectifier firmware is being update  
No Battery  
Auto start  
Rec. Flash Update  
Inv. Flash Update  
Inverter firmware is being update  
Monitor Flash Update  
Input contactor fault  
Contactor P.S. 1 fault  
Contactor P.S. 2 fault  
LBS abnormal  
Monitor firmware is being update  
Input contactor is in fault  
Contactor Power Supply board 1 Fault  
Contactor Power Supply board 2 Fault  
LBS is abnormal  
DSP firmware error  
The inverter firmware does not match with the rectifier firmware.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operator Control Panel and Display  
7.3  
Prompt (Pop-Up) Windows  
The prompt window is displayed during the operation of the system to alert the user to certain condi-  
tions and / or to require user confirmation of a command.  
Table 23 Prompt windows, meanings  
Prompt  
Meaning  
Inverter and Bypass supplies are not synchronised and  
any load transfer between the supplies will cause a brief  
load interruption.  
Transfer with interrupt, please confirm or cancel  
The total load must be less than the capacity of one unit  
to allow a parallel system to perform an interrupted  
transfer from bypass to inverter.  
The load is too high to be transferred with interrupt  
This Operation Leads to Output Shutdown, Confirm or  
Cancel  
No alternative supply is available and any Inverter Off  
operation will cause the load to be de-energised.  
This operation leads to inverter overload, confirm or  
cancel  
The turn-off this inverter will lead to the overload of  
remaining inverter(s) in a parallel system.  
The number of paralleled inverters already turned on is  
insufficient to carry the existing load.  
Turn on more UPS to carry current load  
Battery will be depleted, confirm  
Battery Capacity test discharges the battery 100%  
No action required  
System self test finished - everything is ok.  
System self test finished - Please check the current  
warnings.  
Check “Current Records” window  
Enter control password  
Required for Battery or UPS test (default = 12345)  
Battery self-test condition is not enough. User should  
check whether battery state is boost charging and  
whether load level is greater than 20 percent.  
Battery Self Test aborted, condition not met  
Boost charging condition is not enough, such as (No  
battery, charger has failed, etc.).  
Battery Refresh Charge aborted, condition not met  
7.4  
Dynamic Energy Flow Chart and UPS Help Screen  
This screen displays a mimic diagram of the UPS that includes energy flow and status of isolation and  
transfer switches. Press the “Help” key to activate this screen. Press again to toggle between this  
screen and the main screen.  
Figure 34 Help screen  
Help information  
Select the current record window  
Select the previous menu item  
Press help key back to main menu  
F1  
F2  
F3  
F4  
HELP  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Operator Control Panel and Display  
7.5  
Default Screen Saver  
This default screen is displayed following at least 2 minutes of operation with no new alarm. After  
another delay, the backlight turns off. Press any key (F1-F4 or Help) to reactivate the screen.  
Figure 35 Default screen  
Liebert NX  
20 kVA-3x3  
2005-05-22  
UNIT #1  
12:30:36  
NORMAL  
Press any key, back to main menu  
F1  
F2  
F3  
F4  
HELP  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Options—For Assembly Inside the UPS Cabinet  
8.0 OPTIONS—FOR ASSEMBLY INSIDE THE UPS CABINET  
Several items of optional equipment are available for connection to the Liebert NX UPS. These are  
described in this section of the manual and should be fitted prior to installation.  
8.1  
Protection  
8.1.1 Battery Ground Fault Detection  
In addition to any residual current device mounted externally and upstream the UPS or when  
optional isolation transformers are fitted to the UPS, an optional residual battery current device can  
be fitted to detect leakage current from the battery into the PE (Protective Earth) Residual current  
range monitored: 30~3000mA.  
Power supply voltage for the set: AC230V (L-N);  
When a battery ground fault is detected, an alarm will appear on the UPS display panel.  
An additional Dry contact fault Alarm signal is available for remote monitoring:  
Table 24 Dry contact fault alarm signal is available for remote monitoring  
Terminal Name  
Definition  
Battery Ground Fault Detection – can be  
programmed as Alarm or Pre-Alarm  
21  
Common  
22  
24  
NC  
NO  
The Battery ground fault detection set contains one CT (current transformer) and one DC sensitive  
residual current monitor. The connection of this set for UPS is illustrated as follows.  
Figure 36 Battery ground fault detection set connections  
Current Transformer  
W1-A358 (installed  
externally only)  
BCB or  
Contactor  
Battery  
X
Batt +  
Batt-N  
X
Batt -  
Monitor Board  
K1 K2 I2  
I2  
-U2  
Socket  
Output  
Phase  
4 +12V  
A1  
11  
14  
IN DRY-X3  
A2  
2
Output  
Neutral  
BtG  
Battery Ground  
Fault Detection  
Resys B470  
(AC230)  
UPS  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Options—For Assembly Inside the UPS Cabinet  
8.1.2 Redundant Fan for Power Module  
In addition, to ensure sufficient cooling power at various operation modes with 100% rated load, a  
redundant power module fan set can be supplied, thus ensuring continuity of UPS operation even  
with the failure of some fans. No extra footprint is required.  
Figure 37 Redundant power module fan set  
Redundant AC Fan  
Standard AC Fan  
(AC Fan 1-1)  
(AC Fan 1-2)  
(AC Fan 1-3)  
(AC Fan 1-4)  
Fan120  
Fan120  
Fan120  
Fan120  
TOP VIEW  
Figure 38 Communication bays and cable location  
Preferred Device This Location  
Location  
RS-232-1 DB-9 (COM Port 1) - Serial MultiLink Software  
(Port Setting 2400 Baud)  
RS-232-2 DB-9 (COM Port 2 - Service Access Software  
(Port Setting 9600 Baud)  
DB-9  
Monitor  
Board  
Location  
Preferred Device This Location  
Top Bay  
Mid Bay  
Bottom Bay  
Relay Card (no port setting required)  
Multiport4 (no port setting required)  
OCWeb LB / OC485 (port setting 2400 Baud)  
Top  
Mid  
Bottom  
Suggested routing of customer-supplied  
communication cables  
Notes:  
a) All Intellislot cards are supported in any bay.  
b) Port sharing is:  
- PERMITTED between RS232-x DB9 devices and Relay /  
Multiport4 Intellislot cards (i.e., Serial Multilink software  
will work from RS232-1 DB9 also when relay card is  
inserted in the top bay.  
- NOT PERMITTED between RS-232-x D-B9 devices and  
OCWeb / OC485 cards (i.e., Serial MultiLink software will  
not work from RS232-1 DB-9 when OCWeb card is inserted  
in the top bay.  
Gland plate for cable exit  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Options—For Assembly Inside the UPS Cabinet  
8.1.3 OC Web Card - SNMP/HTTP Network Interface Card  
This network interface card provides all real-time data and status information as SNMPv1 traps for  
connection to a 10/100-baseT Ethernet network and in addition the same card will also transmit the  
same status information and all measured parameters for display via a Web browser.  
This card is supported in the top, middle and bottom Intellislot bays.  
Figure 39 OC Web Card data summary window  
Figure 40 OC Web Card battery data summary  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Options—For Assembly Inside the UPS Cabinet  
8.1.4 Relay Card  
The Relay card provides voltage-free contact closures for remote monitoring of alarm conditions.  
Delivering On Battery, On Bypass, Low Battery, Summary Alarm, UPS Fault and On UPS signals,  
the easy-to-install card integrates with AS/400 computers (additional cable required) and other relay  
contact monitoring systems.  
The Relay card is rated for 24 VAC/VDC at 1A and supported in any of the three NX Intellislot bays.  
Table 25 Relay Card pin configuration  
Pin  
1
Function  
Operation  
UPS Fault  
Closed if no UPS failure  
2-3  
4
Not Used  
UPS Fault  
Closed if UPS fails  
5
Summary Alarm**  
Summary Alarm**  
Any Mode Shutdown return  
Not Used  
Closed if SUMMARY ALARM** occurs  
Closed if no alarm conditions are present  
Not Supported– use External EPO terminal  
6
7
8
9
Common - Low Battery  
Low Battery  
10  
11  
12-13  
14  
15  
16  
17  
Closed if battery is OK  
Low Battery  
Closed if LOW BATTERY point occurs.  
Not Used  
UPS Any Mode Shutdown  
On UPS  
Not supported– use External EPO terminal  
Closed if ON UPS (inverter) power  
On Battery  
Closed if ON BATTERY power (Utility failure)  
Common - UPS Fault, Summary Alarm,  
On UPS, On Battery, On Bypass  
18  
On Battery  
Closed if not ON Battery power (Utility OK)  
Closed if ON BYPASS  
19 ÷ 23 Not Used  
24  
25  
On Bypass  
Not Used  
**A Summary Alarm occurs when any of the following conditions exist:  
• Utility power is out of the acceptable range (voltage and/or frequency)  
• UPS is in BYPASS MODE (load not on Inverter power)  
• UPS Battery is LOW  
• UPS fault has occurred  
Table 26 Relay card jumpers  
#
Connection  
Description  
JP01 Pin 9 to Pin 17  
JP02 Pin 7 to Pin 17  
Allows all relay COMMONS to be tied together.  
Irrelevant for NX - (Interconnects all relay COMMONS and the (not  
supported) ANY MODE SHUTDOWN Return.  
8.1.5 Multiport-4 Card  
The Multiport-4 card provides 4 sets of voltage-free contact closures for remote monitoring of alarm  
conditions UPS operation On Battery and battery low condition. A typical application is to allows a  
maximum of four computer systems to simultaneously monitor the status (e.g., utility power failure /  
low battery) of a single UPS.  
This card is supported in any of the three NX Intellislot bays.  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Options—For Assembly Inside the UPS Cabinet  
Figure 41 SiteNet MultiPort4 Intellislot pin configuration  
CPU  
CPU  
CPU  
CPU  
UPS  
Table 27 SiteNet MultiPort4 Intellislot pin assignment  
Assignment  
Pin  
Description  
1
Low Battery  
2
Not Used  
3
Not Used  
4
Not Used  
5
Not Used  
6
Not Used  
7
Low Battery Common  
Utility Fail Common  
Utility Fail  
8
9
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Options—For Assembly Inside the UPS Cabinet  
8.2  
OC485 Web Card – Modbus, Jbus, IGM Net  
The OpenComms 485 Card facilitates SiteScan Web or Building Management Systems monitoring.  
The RS232 port is used for connection to a personal computer for setting up.  
The RS-485 port supports IGM Net and Modbus/JBus protocols and maps the operation of the UPS  
including status, alarms and data (voltages, currents, frequency, power, power factor, temperatures  
etc.)  
Figure 42 OC485 Web card  
Table 28 NX communication options  
On the UPS  
LCD screen,  
under Settings,  
Physical  
description  
of port  
Labeled  
ID Name  
of Port  
Monitoring  
Devices  
supported  
Baud  
rate  
controlled by:  
Comments  
Multiport 4  
any  
any  
Relaycard-int  
OCWEB-LB  
Top  
Intellislot  
Intellislot 2  
(On Monitor Board)  
Comm 1  
Not simultaneous with  
Multilink in RS232-1  
2400  
Modbus/Jbus  
Multiport 4  
2400  
any  
Relaycard-int  
OCWEB-LB  
any  
Middle  
Intellislot  
Intellislot 1  
(On Monitor Board)  
Comm 2  
Comm 3  
Not simultaneous with  
Multilink in RS232-2  
2400  
Modbus/Jbus  
Multiport 4  
2400  
any  
Relaycard-int  
OCWEB-LB  
Modbus/Jbus  
Multilink Serial  
any  
Bottom  
Intellislot  
Intellislot 3  
(On Monitor Board)  
2400  
2400  
Top  
DB9 port  
Not simultaneous with Web  
card in top Intellislot.  
RS232-1  
RS232-2  
Comm 1  
Comm 2  
9600  
9600  
Bottom  
DB9 port  
Service Software  
(Reserved)  
Not simultaneous with Web  
card in middle Intellislot.  
8.2.1 Remote Alarm Monitor  
Status and alarm conditions are available on an optional remote alarm monitor (RAM) panel that is  
driven by volt-free alarm status contacts from an optional relay alarm board.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Options—For Assembly Inside the UPS Cabinet  
8.2.2 Dust Filter for 10-30kVA  
Installing the two dust filters in the Liebert NX requires only a Phillips screwdriver. Each filter is  
held in place by a bracket on either side of each filter. To install each filter:  
1. Open the UPS door and locate the filters (on the back side of the front door; see Figure 43).  
2. Remove one bracket and loosen the screw on the second bracket. The second bracket need not be  
removed (see Figure 43).  
3. Remove the dust filter to be replaced.  
4. Insert the clean filter.  
5. Reinstall the bracket, tightening the screw securely.  
6. Tighten the screw on the second bracket.  
Figure 43 Dust filter replacement  
Bracket  
Sems screw  
Bracket  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Technical Specifications  
9.0 TECHNICAL SPECIFICATIONS  
9.1  
Conformity and Standards  
The UPS has been designed to conform to the following European and international standards:  
Table 29 Compliance with European, international standards  
Description  
Normative reference  
General and safety requirements for UPS used in  
operator access areas  
EN 50091-1-1 /IEC 62040-1-1 / AS 62040-1-1  
Electromagnetic compatibility (EMC) requirements for  
UPS  
EN 50091-2 / IEC 62040-2 / AS 62040-2 (Class A)  
EN 50091-3 / IEC 62040-3 / AS 62040-3 (VFI SS 111)  
Method of specifying the performance and test  
requirements of UPS  
The product standards in Table 29 incorporate relevant compliance clauses with generic IEC and EN  
standards for safety (IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000  
series) and construction (IEC/EN/AS60146 series and 60529).  
Table 30 Environmental characteristics  
Unit of  
Measurement  
10  
15  
20  
30  
Rated power, kVA  
Acoustic Noise Level at 1 Meter (39 in)  
dBa  
51.0  
51.5  
51.6  
56  
1000m (3280 ft) above sea level  
Altitude of Operation  
m (ft)  
-
de-rate power by 1% per 100m(328 ft) between  
1000 and 2000 m (3280 and 6560 ft)  
Relative Humidity  
0 to 95% non condensing  
0 to 40 (32-104°)  
Battery life is halved for every 10° (18°) increase  
above 20° (68°)  
Operating Temperature  
°C (°F)  
Storage-Transport Temperature for UPS  
°C (°F)  
°C (°F)  
-20 to 70 (-4 to 158)  
Recommended Battery Storage  
Temperature  
-20 to 30 (-4 to 86)°F)  
(20°C [68°F] for optimum battery storage)  
Table 31 Overall efficiency, heat losses and air exchange  
Unit of  
Measurement  
10  
15  
20  
30  
Rated Power, kVA  
Normal Mode (dual conversion)  
ECO Mode  
%
%
90.4  
93.2  
91.2  
94.2  
91.3  
94.7  
91.9  
96.6  
Inverter Efficiency (DC/AC)  
(battery at nominal voltage 480VDC and full-rated linear load)  
Rated Power,  
kVA  
%
10  
15  
20  
30  
Battery Mode  
91.3  
91.7  
92.0  
92.5  
Heat Loss & Air Exchange (Ventilation)  
Rated Power  
Normal Mode  
ECO Mode  
No Load  
kVA  
kW  
kW  
kW  
10  
1.6  
1.3  
1.3  
15  
1.8  
1.4  
1.3  
20  
2.2  
1.4  
1.3  
30  
2.6  
1.5  
1.3  
119  
(428)  
3
Maximum Forced Air Cooling (front intake, back exhaust)  
L/sec (m /hr)  
239 (860)  
Input and output voltage 400VAC, battery charged, full rated linear load  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Technical Specifications  
Table 32 Mechanical characteristics  
Unit of  
Measurement  
10  
15  
20  
30  
Rated Power, kVA  
Dimensions, WxDxH  
Mass  
600x700x1400  
(23-9/16x27-5/8x55)  
mm (in)  
Mass without batteries  
kg (lb)  
N/A  
180 (397)  
204 (450)  
204 (450)  
210 (463)  
Pantone 877 (Silver grey)  
Finish  
equivalent Becker Silver epoxy polyester powder 041-37-2  
Protection Degree, IEC (60529)  
N/A  
IP20 (finger-proof with front doors open or closed)  
Table 33 Rectifier AC input (mains)  
Unit of  
Measurement  
10  
15  
20  
30  
Rated Power, kVA  
380/400/415  
Rated AC Input Voltage  
VAC  
(3-phase and sharing neutral with the bypass input)  
305V to 477V  
304V to 208V (output derated below 70%)  
2
Input Voltage Tolerance  
VAC  
Hz  
Frequency  
50/60Hz (tolerance 40Hz to 70Hz)  
0.99 (0.98)  
kW/kVA, full  
load  
Power Factor  
(half load)  
kVA rated  
Input Power  
8.9 (11.7)  
13.3 (18.9)  
17.8 (23.3)  
26.6 (35.0)  
(maximum )  
A rated  
Input Current  
12.9 (16.9)  
3
19.3 (27.4)  
3
25.8 (33.8)  
3
38.6 (50.7)  
3
(maximum )  
Harmonic Current Distortion  
THDI % FL  
Duration of Progressive  
Power Walk-In  
10 seconds to reach full rated current  
(selectable 5 through 30 seconds in 5-second intervals)  
sec  
1. Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.  
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged  
battery  
3. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charged  
4. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Technical Specifications  
Table 34 Battery  
Intermediate DC Circuit  
10 15  
Rated Power,  
kVA  
Unit of  
Measurement  
20  
30  
Battery Bus  
Voltage  
Nominal: 480V (VRLA Float charge is 540V)  
Range: 400V - 616V  
VDC  
Number of Lead-Acid Cells  
Nominal  
Maximum  
240 = [40 x 6-cell (12V) blocks]  
264 = [44 x 6-cell (12V) blocks]  
2.25 V/cell (selectable from 2.2 –2.3V/cell)  
Constant current and constant voltage (IU) charge mode  
Float Voltage  
V/cell (VRLA)  
Temperature  
Compensation  
Ripple Voltage  
Ripple Current  
mV/°C/cl  
% V float  
- 3.0 (selectable 0 to – 5.0 around 25°C or 30°C. or inhibit)  
1  
5  
% C  
10  
2.35 V/cell (selectable from 2.30-2.40V/cell)  
Constant current and constant voltage (IU) charge mode  
Boost Voltage  
V/cell (VRLA)  
- float-boost current trigger 0.050 C (selectable 0.030-0.070)  
10  
- boost-float current trigger 0.010 C (selectable 0.005-0.025) with  
10  
Boost Control  
24 hr safety timeout (selectable 8-30 hr)  
- boost mode inhibit also selectable  
1.63 V/cell (selectable from 1.60~1.75 V/cell  
Auto Inverse EOD voltage x discharge current mode  
(The end of discharge voltage increases at low discharge currents).  
End Of  
Discharge  
V/cell (VRLA)  
V/cell  
2.4 V/cell (selectable from 2.3-2.4V/cell)  
Constant current and constant voltage (IU) charge mode  
Programmable auto trigger or inhibit of boost mode  
Battery Charge  
Battery  
kW  
A
2.5  
5
5
7.5  
12  
*
Charging Power  
max current  
(adjustable) 1  
3.75  
7.5  
7.5  
* At low input voltage the UPS recharge capability increases with load decrease (up to the maximum capacity indicated)  
1. Max currents listed are for EOD voltage of 1.67 V/cell for 240 cells.  
Table 35 Inverter output to critical load  
Unit of  
Rated Power, kVA (kW)  
Measurement  
10 (8)  
15 (12)  
20 (16)  
30 (24)  
380/400/415 V (three-phase, four-wire with neutral  
1
Rated AC Voltage  
VAC  
Hz  
referenced to the bypass neutral)  
2
Frequency  
50 / 60  
110% for 60 min  
125% for 10 min  
150% for 1 min  
Overload  
% Rated  
>150% for 200 msec  
Fault Current  
% Rated  
% Rated  
% Rated  
%
340% current limitation for 200 msec  
3
Non linear load capability  
Neutral current capability  
Steady state voltage stability  
100%  
170%  
±1 (balanced load), ±2 (100% unbalanced load),  
± 5  
4
Transient voltage response  
%
Total Harmonic Voltage  
Distortion (THDV)  
3
%
< 1 (linear load), < 4 (non linear load )  
Synchronisation - Window  
Rated frequency ± 2Hz (selectable ± 0.5 to ± 3Hz)  
1 Hz/sec  
Slew Rate (Max change rate  
of synch frequency)  
Hz sec  
selectable 0.1 to 3Hz/s (single UPS)  
0.2Hz/sec (paralleled UPS)  
Inverter Voltage Tolerance  
%V (AC)  
±5  
1. Factory set to 400V – 380 or 415V selectable by commissioning engineer.  
2. Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Frequency converter operation also selectable.  
3. EN 50091-3 (1.4.58) crest factor 3:1  
4. IEC 62040-3 / EN 50091-3 also for 0-100-0% load transient. Transient recovery time: return to within 5% of steady state  
output voltage within half a cycle.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Technical Specifications  
Table 36 Bypass mains input  
Rated power, kVA  
Unit of  
Measurement  
10  
15  
20  
30  
380/400/415 V  
1
Rated AC Voltage  
VAC  
three-phase four-wire, sharing neutral with the rectifier input  
and providing neutral reference to the output  
Rated Current  
380V  
A
A
A
15  
15  
14  
23  
22  
21  
30  
29  
28  
45  
43  
42  
400V  
415V  
135% long term  
170% 10 min  
Overload Capacity  
%
1000% 100 ms  
Upstream Protection,  
Bypass Line (by others)  
Thermomagnetic circuit breaker, rated up to 125%  
of nominal output current. IEC 60947-2 curve C.  
N/A  
Current Rating of Neutral Cable  
A
1.7 x In  
50 / 60  
2
Frequency  
Hz  
Synchronous transfer: 1ms  
Asynchronous transfer (default): 15 ms (50 Hz), 13.3 ms (60 Hz)  
or 40, 60, 80, 100 ms, selectable  
Transfer Time (between  
bypass and inverter)  
ms  
Upper limit: +10, +15 or +20, default +15  
Lower limit –10, -20, -30 or -40, default: -20  
(delay time to accept steady bypass voltage: 10 sec)  
Bypass Voltage Tolerance  
% VAC  
Bypass Frequency Tolerance  
Synchronisation - Window  
%
± 2.5 ± 5 ± 10 or ± 20 default ±10  
Hz  
Rated frequency ±2Hz (selectable ± 0.5 to ±3Hz)  
1. Factory set to 400V – 380 or 415V selectable by commissioning engineer.  
2. Factory set to 50Hz; 60 Hz selectable by commissioning engineer. Bypass condition ignored when UPS set as frequency converter.  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Technical Specifications  
NOTES  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Technical Specifications  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ensuring The High Availability  
0f Mission-Critical Data And Applications.  
Technical Support / Service  
Web Site  
Emerson Network Power, the global leader in enabling business-critical  
continuity, ensures network resiliency and adaptability through  
a family of technologies—including Liebert power and cooling  
technologies—that protect and support business-critical systems.  
Liebert solutions employ an adaptive architecture that responds  
to changes in criticality, density and capacity. Enterprises benefit  
from greater IT system availability, operational flexibility and  
reduced capital equipment and operating costs.  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Single-Phase UPS  
800-222-5877  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Europe  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD) Italy  
+39 049 9719 111  
Fax: +39 049 5841 257  
Asia  
7/F, Dah Sing Financial Centre  
108 Gloucester Road, Wanchai  
Hong Kong  
While every precaution has been taken to ensure the accuracy  
and completeness of this literature, Liebert Corporation assumes no  
responsibility and disclaims all liability for damages resulting from use of  
this information or for any errors or omissions.  
© 2006 Liebert Corporation  
All rights reserved throughout the world. Specifications subject to change  
without notice.  
852 2572220  
Fax: 852 28029250  
® Liebert and the Liebert logo are registered trademarks of Liebert  
Corporation. All names referred to are trademarks  
or registered trademarks of their respective owners.  
SL-25410_REV2_08-06  
Emerson Network Power.  
The global leader in enabling Business-Critical Continuity.  
EmersonNetworkPower.com  
Services  
AC Power Systems  
Connectivity  
Embedded Computing  
Embedded Power  
Outside Plant  
Power Switching & Control  
Precision Cooling  
Site Monitoring  
DC Power Systems  
Integrated Cabinet Solutions  
Surge Protection  
Business-Critical Continuity, Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co.  
©2006 Emerson Electric Co.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Krell Industries Stereo Amplifier Stereo Preamplifie User Manual
Krups Coffeemaker Aroma Control 229 User Manual
Kyocera Printer FS 1900 User Manual
Lanier Printer Accessories FX 071 User Manual
LG Electronics Clothes Dryer X0002TM User Manual
Liebert Power Supply 1500 User Manual
Lincoln Automobile 2011 MKS User Manual
LOREX Technology VCR SG 7960 User Manual
Makita Cordless Sander 9227C User Manual
Memorex Car Video System MM1920 User Manual