| 	
		 w w w. m g e u p s . c o m   
					EX 5RT / EX 7RT/ EX 11RT System   
					Installation and User Manual   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Safety of Persons   
					◗ 
					The UPS has its own internal power source (the battery). Consequently, the power outlets may be energized even if the UPS is disconnected from   
					the AC power source.   
					◗ 
					◗ 
					The UPS must be properly grounded.   
					The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the directives listed below must be observed:   
					- 
					- 
					- 
					- 
					Never burn the battery (risk of explosion).   
					Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).   
					Comply with all applicable regulations for the disposal of the battery.   
					Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high. Precautions must be taken for all handling:   
					remove watches, rings, bracelets and any other metal objects, use tools with insulated handles.   
					- 
					Do not lay tools or metal parts on top of batteries.   
					Product Safety   
					◗ 
					◗ 
					◗ 
					◗ 
					◗ 
					A protection circuit breaker must be installed upstream and be easily accessible..   
					The UPS can be disconnected from the AC power source by opening the input circuit breaker.   
					UPS must be connected to a nearby power source that is easily accessible.   
					Never block the ventilation grates of the UPS.   
					The UPS must be installed in a controlled environment.   
					Special Precautions   
					◗ 
					◗ 
					The UPS connection instructions and operation described in the manual must be followed in the indicated order.   
					Check that the indications on the rating plate correspond to your AC powered system and to the actual electrical consumption of all the equipment   
					to be connected to the UPS.   
					◗ 
					Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be energized for a period of 24 hours, at least   
					once every 6 months (for a normal storage temperature less than 25°C). This charges the battery, thus avoiding possible irreversible damage.   
					How to use this manual and Symbol Usage   
					This manual is designed for ease of use and easy location of information.   
					Typographical conventions use “< >” angle brackets in procedures to denote a prompt for User action:   
					For example: 1. After the selections are complete, click on the <Save> button.   
					This manual uses four icon symbols with text to convey important information and tips.   
					WARNING   
					CAUTION   
					Indicates information provided to protect the user and service personnel against safety   
					hazards and/or possible equipment damage.   
					Indicates information provided to protect the user and service personnel against possible   
					equipment damage.   
					IMPORTANT   
					NOTE   
					Indicates information provided as an operating instruction, or as an operating tip.   
					Indicates information provided as an operating tip or an equipment feature.   
					86-86000-00 A01   
					Safety of Persons   
					iii   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					CAUTION: Record All Serial Numbers!   
					RECORD ALL SERIAL NUMBERS FOR EX 5/7/11 RT AND ACCESSORIES.   
					THESE SERIAL NUMBERS WILL BE REQUIRED IF YOUR SYSTEM NEEDS SERVICE.   
					KEEP THIS MANUAL IN A PLACE WHERE YOU CAN REFERENCE THE SERIAL   
					NUMBERS IF SERVICE IS REQUIRED!   
					EX 5RT System   
					EX 7RT System   
					EX 11RT System   
					Power Module SERIAL NUMBER: ___________________________________________________   
					Battery Module SERIAL NUMBER: ____________________________________________________   
					Transformer SERIAL NUMBER: ______________________________________________________   
					ADDITIONAL MODULES SERIAL NUMBERS:   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					____________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					______________________________   
					iv   
					CAUTION: Record all serial numbers!   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					EX 5/7/11 RT System   
					Installation and User Manual   
					Revision History   
					EX 5RT / EX 7RT / EX 11RT System Installation and User Manual 86-86000-00   
					Revision: A00 Initial Release 07/2004   
					Copyright © 2004 MGE UPS SYSTEMS, INC.   
					All rights reserved. Printed in U.S.A.   
					MGE UPS SYSTEMS, INC.   
					1660 Scenic Avenue   
					Costa Mesa, CA 92626   
					(714) 557-1636   
					For Service Call:   
					1 (800) 438-7373   
					86-86000-00 A01   
					v 
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					(This page left blank intentionally)   
					86-86000-00 A01   
					vi   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Contents   
					section   
					description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . .ii   
					Certification Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii   
					Safety of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii   
					How to use this manual and Symbol Usage . . . . . . . . . . . . . . . . . . . .iii   
					CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . . .iv   
					Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .v   
					Section 1 Introduction   
					section   
					description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					1.0   
					1.1   
					1.2   
					Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1   
					System Electrical Characteristics . . . . . . . . . . . . . . . . . . . . . . . .1 — 4   
					Standard Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4   
					1.2.1 Tower Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4   
					1.2.2 Rack Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5   
					Rear Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6   
					1.3.1 Power Module EX 5/7/11 RT . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6   
					1.3.2 Battery Module EXB 5/7/11 RT With Emergency   
					1.3   
					Power Off (EPO) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6   
					1.3.3 EX RT Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7   
					Display and Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7   
					Optional Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8   
					1.5.1 Power Module Rail Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8   
					1.5.2 Battery/ Transformer/CLA Module Rail Kit . . . . . . . . . . . . . . . . . .1 — 8   
					1.5.3 Battery Module with Remote Emergency   
					1.4   
					1.5   
					Power Off (REPO) Function . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9   
					1.5.4 Battery Extension Cable Kit . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 9   
					1.5.5 Battery Integration Kit with Casters . . . . . . . . . . . . . . . . . . . . . .1 — 10   
					1.5.6 Input/Output Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10   
					1.5.7 Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 11   
					1.5.8 CLA Module (Long backup time charger) . . . . . . . . . . . . . . . .1 — 12   
					86-86000-00 A01   
					Contents   
					c i   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Section 2 Setup and Installation   
					section   
					description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					2.0   
					2.1   
					2.2   
					2.3   
					2.4   
					Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1   
					Unpacking and Parts Check . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1   
					Contents of EX 5/7/11 RT System . . . . . . . . . . . . . . . . . . . . . . .2 — 2   
					Installation in Tower Configuration . . . . . . . . . . . . . . . . . . . . . . . .2 — 4   
					Installation in Rack Mounting Configuration . . . . . . . . . . . . . . . .2 — 5   
					2.4.1 Adjustment of Front Panel Logo and control panel for   
					Rack Orientation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5   
					Prepare Battery Module for Rack Mounting . . . . . . . . . . . . . . . .2 — 6   
					Power or Battery Module Rack Mounting . . . . . . . . . . . . . . . . . .2 — 7   
					2.6.1 Rear Support Brackets Installation . . . . . . . . . . . . . . . . . . . . . . .2 — 8   
					2.6.2 Input/Output Box Bracket System Installation . . . . . . . . . . . . . . .2 — 8   
					Communication Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 9   
					2.7.1 Connecting the RS232 Communication Port . . . . . . . . . . . . . . .2 — 9   
					2.7.2 Connecting the Dry (Relay) Contact Communication Port . . . .2 — 10   
					2.7.3 Installation of Optional Network Management Card . . . . . . . .2 — 10   
					2.7.4 Remote Emergency Power Off (REPO) Communication Port .2 — 12   
					Connecting the Input and Output Power Cables to the   
					2.5   
					2.6   
					2.7   
					2.8   
					Input/Output Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 13   
					2.8.1 Flexible Cordage and Conduit Installations . . . . . . . . . . . . . . .2 — 13   
					2.8.2 System Connections with Common Normal and   
					Bypass AC Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 15   
					2.8.3 Connecting EX RT Transformer . . . . . . . . . . . . . . . . . . . . . . . .2 — 16   
					2.8.4 System Connections with Separate Normal and   
					Bypass AC Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 17   
					2.8.5 System Connections as Frequency Converter   
					(without Bypass AC Source) . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 18   
					Connection of Battery Module, EXB . . . . . . . . . . . . . . . . . . . . .2 — 19   
					Connection of CLA Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 20   
					2.9   
					2.10   
					Section 3 Operation   
					section   
					description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					3.0   
					3.1   
					3.2   
					Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1   
					Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1   
					UPS Personalization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 2   
					3.2.1 Accessing personalization with front panel buttons . . . . . . . . . .3 — 2   
					3.2.2 Accessing personalization through external software . . . . . . . . .3 — 4   
					3.2.3 Final startup sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4   
					Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5   
					3.3.1 Normal (double conversion) Mode . . . . . . . . . . . . . . . . . . . . . . .3 — 5   
					3.3.2 ECO Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6   
					Operation on battery power . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7   
					3.4.1 Transfer to Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7   
					Return of Normal AC source . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8   
					Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8   
					3.3   
					3.4   
					3.5   
					3.6   
					c ii   
					Contents   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Section 4 Maintenance   
					section   
					description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					4.0   
					4.1   
					Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1   
					Information Technology (IT) Network and Industrial   
					Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1   
					Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2   
					Hot Swapping the Power Module . . . . . . . . . . . . . . . . . . . . . . . .4 — 4   
					Re-connecting the power module . . . . . . . . . . . . . . . . . . . . . . . .4 — 5   
					Hot Swapping the Battery Module . . . . . . . . . . . . . . . . . . . . . . . .4 — 6   
					4.5.1 Disconnecting the Battery Module . . . . . . . . . . . . . . . . . . . . . . .4 — 6   
					4.5.2 Re-connecting the Battery Module . . . . . . . . . . . . . . . . . . . . . . .4 — 6   
					4.2   
					4.3   
					4.4   
					4.5   
					Section 5 Appendix   
					section   
					description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					5.0   
					5.1   
					5.2   
					5.3   
					5.4   
					5.5   
					5.6   
					5.7   
					Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1   
					System Input/Output Power Ratings . . . . . . . . . . . . . . . . . . . . . .5 — 1   
					System Overload Characteristics . . . . . . . . . . . . . . . . . . . . . . . .5 — 1   
					System Backup Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1   
					System Short Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2   
					Accessories Electrical Characteristics . . . . . . . . . . . . . . . . . . . . .5 — 2   
					Heat Rejection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2   
					Environmental Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2   
					MGE Warranty & Propriety Rights   
					MGE Warranty   
					Proprietary Rights Statement   
					Warranty and Product Registration   
					User Information   
					Product information   
					Warranty Extension (Warranty+) not available on products   
					Technical Support and Field Service   
					MGE Service and Repair   
					Who to Contact   
					Scheduling Field Service Engineer Support   
					Return for Repair (RMA)   
					Glossary   
					G — 1   
					Reorder Form RO — 1   
					86-86000-00 A01   
					Contents   
					c iii   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Figures   
					figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					1-1: Tower Configurations with Power Module, Battery Module,   
					and optional Transformer Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4   
					1-2: Rack Configurations with Power Module, Battery Module, and   
					Transformer Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5   
					1-3: Rear panel of the Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6   
					1-4: Rear Panel of the Battery Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6   
					1-5: Rear Panel of the optional Transformer Module. (PN 86003) . . . . . . . . .1 — 7   
					1-6: View of typical control panel interface. . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7   
					1-7: Power Module Rack Mounting Kit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8   
					1-8: Telescopic rails for the Battery/Transformer/CLA module   
					Rack mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8   
					1-9: Typical back-up time with multiple EXB’s at full load. . . . . . . . . . . . . . . . .1 — 9   
					1-10: Typical Battery Integration kit with casters setup. . . . . . . . . . . . . . . . . .1 — 10   
					1-11: Typical Transformer Module contents and connections. . . . . . . . . . . . .1 — 11   
					1-12: Connection for CLA Module and EX 5/7/11 RT. . . . . . . . . . . . . . . . . . .1 — 12   
					2-1: Contents of Standard HV EX 5RT (PN 86050)   
					/ EX 7RT (PN 86070) / EX 11RT (PN 86110) System. . . . . . . . . . . . . .2 — 3   
					2-2: Tower Configuration of Standard System and Optional   
					Transformer Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4   
					2-3: Typical orientation of the logo and control panel.   
					(Power Module shown) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5   
					2-4: Accessing Battery Pack. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 6   
					2-6: Rack mounting of the power module onto the rails. . . . . . . . . . . . . . . . .2 — 7   
					2-7a: Rear Support Brackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8   
					2-7b: Input/Output Box Bracket System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 8   
					2-8: RS232 Communication Cable Connection. . . . . . . . . . . . . . . . . . . . . . . .2 — 9   
					2-9: Relay Pin Connections for Communication Port. . . . . . . . . . . . . . . . . .2 — 10   
					2-10: Communication Card Slot with SNMP/Web Network   
					Management Card installed. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 10   
					2-10a: Activation of remote power off function using a contact   
					normally open switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 12   
					2-10b: Activation of remote power off function using a contact   
					normally closed switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 12   
					2-12a: Step 1 & 2; Typical plastic and metal coupling installations. . . . . . . . . .2 — 13   
					2-12b: Step 3; Typical Straight Metal Conduit installation. . . . . . . . . . . . . . . .2 — 14   
					2-12c: I/O Box Terminal Block Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 14   
					2-13: Normal AC Input and Output Cables installation. . . . . . . . . . . . . . . . . .2 — 15   
					2-14: View of EX RT transformer connected downstream for   
					120/208/240 Vac outputs (shown with one EXB). . . . . . . . . . . . . . . . . .2 — 16   
					2-15: Normal AC Input, Bypass AC, and Output Cables Installation. . . . . . .2 — 17   
					2-16: Accessing Terminal Blocks for Input and Output power cables. . . . . . .2 — 18   
					2-17: Rear view of battery module cable connections. . . . . . . . . . . . . . . . . .2 — 19   
					2-18: Rear view of CLA module cable battery and AC input connections. . .2 — 20   
					c iv   
					Contents   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Figures (continued)   
					figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					3-1: Initial Startup Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1   
					3-2: Control Panel with scroll up and down buttons. . . . . . . . . . . . . . . . . . . .3 — 2   
					3-3: Configuration used to provide full redundancy (2N) to critical loads. . . .3 — 3   
					3-4: Normal (double conversion) mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5   
					3-5: ECO mode display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6   
					3-6: Transfer, Threshold and End of backup time. . . . . . . . . . . . . . . . . . . . . .3 — 7   
					3-7: Shutdown display, circuit breaker, and AC source switch. . . . . . . . . . . .3 — 8   
					4-1: Disconnecting the power module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 4   
					4-2: Reconnect the power module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 5   
					4-3: Rear view of the battery module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 6   
					5-1: Power supplied as a function of input voltage (left), and   
					Permissible UPS overloads as a function of time (right). . . . . . . . . . . . . .5— 1   
					Tables   
					table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page   
					1:   
					2:   
					3:   
					4:   
					5:   
					EX RT Model Descriptions and Contents . . . . . . . . . . . . . . . . . . . . . . . .1 — 2   
					Optional Accessories (See section 1.5 for description) . . . . . . . . . . . . .1 — 3   
					Power Module Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4   
					Battery Module Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4   
					Battery backup time chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 12   
					3-1: Local Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 3   
					3-2: Output features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 3   
					3-3: ON/OFF features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4   
					3-4: Battery features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 4   
					4-1: Network and Industrial Modes of Operation. . . . . . . . . . . . . . . . . . . . . . .4 — 1   
					4-2: Troubleshooting not requiring MGE after-sales support. . . . . . . . . . . . . .4 — 2   
					4-3: Troubleshooting requiring MGE after-sales support. . . . . . . . . . . . . . . . .4 — 3   
					5-1: EX 5/7/11 RT Input and Output Characteristics. . . . . . . . . . . . . . . . . . . .5 — 1   
					5-2: Back-up Time ( in minutes). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 1   
					5-3: Battery Recharge time to recover 90% of the rated backup time   
					after discharge at full load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2   
					5-4: Full load heat rejection in BTU’s/hr. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 — 2   
					86-86000-00 A01   
					Contents   
					c v   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					(This page left blank intentionally)   
					86-86000-00 A01   
					c vi   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Introduction   
					1.0   
					Scope   
					Thank you for selecting an MGE UPS SYSTEMS, INC. (MGE) product to protect your electrical equipment.   
					The product you selected is a part of the EX RT series.The EX RT series is a family of Uninterruptible Power Supply   
					(UPS) designed to provide safe, and reliable AC power backup for sensitive electrical equipment. To discover the   
					
					at (800) 523-0142.   
					This manual describes the installation and operation of standard HV EX 5/7/11RT systems within the EX RT product   
					family. For a complete description of the EX RT product family and its available options, please refer to the tables   
					below:   
					1 
					Introduction   
					Introduction is a general description of system configurations of the EX 5/7/11 RT, and its mechanical   
					,electrical characteristics. Additionally there is an optional accessories section with important information on MGE   
					products that will enhance the performance of the EX 5/7/11RT. Please contact your MGE representative for   
					detailed information on these options.   
					2 
					Setup and Installation   
					Setup and Installation guides the user through tools and equipment required for connecting the EX 5/7/11 RT and   
					battery installation or replacement. Included are assembly instructions, power cable connections with wire diagrams   
					for configuring the product to hardware specifications.   
					3 
					Operation   
					Operation describes the EX 5/7/11RT system characteristics of indicators and controls, modes and specifications.   
					The user procedures include performing software programming that will maintain optimal performance.   
					4 
					Maintenance   
					Maintenance includes a troubleshooting guide of symptoms and possible solutions, hot swapping the power module,   
					battery module, and testing scenarios.   
					5 
					Appendix   
					Electrical and Mechanical specifications for the EX 5/7/11 RT.   
					A Glossary provides definitions of abbreviations and terms used in this manual.   
					86-86000-00 A01   
					Introduction   
					1 — 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Table 1: EX RT Model Descriptions and Contents   
					System Description   
					Contents   
					Model   
					Part   
					Power Module   
					Battery Module   
					Transformer   
					Module   
					Power Module Battery Module SNMP/Web   
					Number   
					86055 86075 86115 86079 86119   
					Rail Kit 86001   
					Rail Kit 86002   
					Network   
					Mgt. Card   
					66074   
					(120/208/240Vac)   
					86003   
					5kVA   
					HV EX 5RT   
					86050   
					86052   
					X 
					X 
					X 
					X 
					5kVA   
					X 
					X 
					X 
					X 
					X 
					X 
					X 
					X 
					HV EX 5RT   
					Network Pack   
					5kVA   
					LV EX 5RT   
					86050-01   
					86052-01   
					X 
					X 
					X 
					X 
					X 
					X 
					5kVA   
					X 
					X 
					X 
					X 
					X 
					X (x2)   
					LV EX 5RT   
					Network Pack   
					7kVA   
					HV EX 7RT   
					86070   
					86072   
					X 
					X 
					X 
					7kVA   
					X 
					X 
					HV EX 7RT   
					Network Pack   
					7kVA   
					LV EX 7RT   
					86070-01   
					86072-01   
					X 
					X 
					X 
					X 
					X 
					7kVA   
					X 
					X (x2)   
					LV EX 7RT   
					Network Pack   
					11kVA   
					HV EX 11RT   
					86110   
					86112   
					X 
					X 
					X 
					X 
					11kVA   
					X 
					HV EX 11RT   
					Network Pack   
					11kVA   
					LV EX 11RT   
					86110-01   
					86112-01   
					X 
					X 
					X 
					X 
					X 
					X 
					11kVA   
					X (x2)   
					LV EX 11RT   
					Network Pack   
					1 — 2   
					Introduction   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Table 2: Optional Accessories (See section 1.5 for description)   
					Part Number   
					86001   
					Description   
					Rail Kit for Power Module EX 5/7/11 RT   
					86002   
					Rail Kit for Battery/Transformer/CLA Module   
					Battery Integration Kit with Casters   
					Battery Extension Cable Kit   
					Battery Chassis Empty EXB RT W/EPO   
					I/O Box 5/7kVA UL/US   
					86005   
					86006   
					86008   
					86009   
					86010   
					I/O Box 11kVA UL/US   
					86012   
					I/O Box Bracket System   
					86013   
					Rear Bracket Supports   
					86-86000-00 A01   
					Introduction   
					1 — 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					1.1   
					System Electrical Characteristics   
					Table 3: Power Module Ratings   
					Part Number   
					86055   
					86075   
					86115   
					Apparent Power, kVA   
					5 
					7 
					10@ 200/208/250 VAC Output   
					11@ 220/230/240 VAC Output   
					Active Power, kW   
					Input Current, A   
					4 
					4.9   
					8@ 200/208/250 VAC Output   
					7.3@ 220/230/240 VAC Output   
					25/24/23/   
					22/21/20   
					35/34/32   
					31/30/28   
					50/48/50/48/46/40   
					Input Voltage, VAC   
					Output Current, A   
					Output Voltage, VAC   
					200/208/220/   
					230/240/250   
					200/208/220/   
					230/240/250   
					200/208/220/230/240/250   
					50/48/50/48/46/40   
					25/24/23/   
					22/21/20   
					35/34/32   
					31/30/28   
					200/208/220/   
					230/240/250   
					200/208/220/   
					230/240/250   
					200/208/220/230/240/250   
					CAUTION   
					Power Module is factory configured at 208Vac, 60 Hz input and output.   
					Input and Output of the UPS must always be the same.   
					Table 4: Battery Module Ratings   
					Part Number   
					86079   
					86119   
					Battery Type   
					12VDC/7Ah   
					12VDC/9Ah   
					240VDC   
					Battery Output Voltage 240VDC   
					1.2   
					Standard Configurations   
					The EX 5/7/11 RT systems can be set up in tower and rack configurations.   
					1.2.1 Tower Configuration   
					Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.   
					Standard Configuration   
					Configuration with Transformer   
					BATTERY MODULE   
					(EXB 5/7/11 RT)   
					BATTERY MODULE   
					T 
					R 
					B 
					X 
					E 
					T 
					R 
					B 
					X 
					T 
					E 
					R 
					1 
					1 
					X 
					E 
					T 
					r 
					e 
					R 
					1 
					m 
					r 
					1 
					X 
					f 
					o 
					s 
					E 
					n 
					ra   
					T 
					T 
					R 
					X 
					E 
					ON   
					F 
					OF   
					ON   
					F 
					OF   
					om   
					s.c   
					up   
					mge   
					w.   
					ww   
					om   
					s.c   
					up   
					ge   
					w.m   
					ww   
					m 
					.co   
					ps   
					geu   
					w.m   
					ww   
					m 
					s.co   
					up   
					ge   
					w.m   
					ww   
					om   
					.c   
					ups   
					ge   
					w.m   
					ww   
					POWER MODULE   
					(EX 5/7/11 RT)   
					EX RT Transformer   
					POWER   
					MODULE   
					1 — 4   
					Introduction   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					1.2.2 Rack Configuration   
					Figure 1-2: Rack Configurations with Power Module, Battery Module, and Transformer Module.   
					Standard Configuration   
					POWER MODULE   
					Configuration with Transformer   
					(EX 5/7/11 RT)   
					EX RT Transformer   
					r 
					e 
					rm   
					sfo   
					n 
					a 
					Tr   
					T 
					R 
					EX   
					om   
					ps.c   
					geu   
					w.m   
					ww   
					T 
					R 
					11   
					EX   
					POWER MODULE   
					(EX 5/7/11 RT)   
					ON   
					F 
					OF   
					om   
					ps.c   
					geu   
					w.m   
					ww   
					RT   
					XB   
					E 
					BATTERY MODULE   
					(EXB 5/7/11 RT)   
					om   
					ps.c   
					geu   
					w.m   
					ww   
					BATTERY MODULE   
					(EXB 5/7/11 RT)   
					Model   
					Dimensions   
					Weights   
					EX 5RT/7RT   
					(3U) 5.16” x 17.49” x 25”   
					(131 x 444 x 635mm)   
					49.6 lbs (22.5 kg)   
					60.6 lbs (27.6 kg)   
					142 lbs (64.5 kg)   
					151 lbs (68.5 kg)   
					173 lbs (78.5 kg)   
					EX 11RT   
					(3U) 5.16” x 17.49” x 25”   
					(131 x 444 x 635mm)   
					EXB 5 RT/ 7 RT   
					EXB 11RT   
					(3U) 5.16” x 17.49” x 25”   
					(131 x 444 x 635mm)   
					(3U) 5.16” x 17.49” x 25”   
					(131 x 444 x 635mm)   
					EX RT   
					Transformer   
					(3U) 5.16” x 17.49” x 25”   
					(131 x 444 x 635mm)   
					86-86000-00 A01   
					Introduction   
					1 — 5   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					1.3   
					Rear Panels   
					1.3.1 Power Module EX 5/7/11 RT   
					EX 5RT Power Module part number 86055   
					EX 7RT Power Module part number 86075   
					EX 11RT Power Module part number 86115   
					Figure 1-3: Rear panel of the Power Module.   
					1 
					2 
					3 
					Slot for optional communication cards.   
					1 
					4 
					5 
					Communication port by relays (Dry contacts).   
					2 
					3 
					Remote Emergency Power Off communication port   
					(REPO).   
					4 
					5 
					Connectors for automatic detection of battery module(s).   
					RS232 communication port.   
					6 
					Battery/CLA module power connector.   
					Manual Bypass switch.   
					6 
					7 
					7 
					8 
					9 
					8 
					Normal AC source circuit breaker.   
					10   
					11   
					9 
					Knockout for entry of AC Output conduit.   
					Knockout for entry of Normal AC source conduit.   
					Knockout for entry of Bypass AC source conduit.   
					10   
					11   
					1.3.2 Battery Module EXB 5/7/11 RT With Emergency Power Off (EPO) Function   
					Figure 1-4: Rear Panel of the Battery Module.   
					12   
					12   
					13   
					14   
					Connectors for automatic detection of additional battery   
					module(s) (to the UPS or to other battery modules).   
					Battery power connectors (to the UPS or to other   
					battery modules).   
					Battery Circuit Breaker with Remote Emergency Power   
					Off (REPO) shunt trip.   
					EXB 5RT with EPO part number 86079   
					EXB 7RT with EPO part number 86079   
					EXB 11RT with EPO part number 86119   
					13   
					14   
					1 — 6   
					Introduction   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					1.3.3 EX RT Transformer Module   
					Figure 1-5: Rear Panel of the optional Transformer Module. (PN 86003)   
					Load 3: 1 NEMA L6-30R   
					Load 2: 4 NEMA 5-15/20R   
					Load 3 Circuit Breaker   
					Load 4: 4 NEMA 5-15/20R   
					Load 4 Circuit Breaker   
					Load 2 Circuit Breaker   
					Main Output Circuit Breaker   
					AC Input   
					Transformer I/O Box   
					AC Output   
					Load 1 Circuit Breaker   
					Load 1: 1 NEMA L6-30R   
					Transformer Protect   
					Breaker   
					1.4   
					Display and Control Panel   
					Figure 1-6: View of typical control panel interface.   
					15   
					16   
					17   
					18   
					15   
					16   
					17   
					18   
					19   
					20   
					21   
					23   
					Load protected / On-line Operation LED.   
					Operation on battery LED.   
					Operation on bypass LED.   
					Fault LED.   
					E X 1 1 R T   
					19   
					Alphanumeric display.   
					UPS OFF button.   
					OFF   
					ON   
					22   
					Function buttons (scroll up / scroll down).   
					UPS ON button (or function button in personalization   
					mode).   
					20   
					21   
					22   
					23   
					86-86000-00 A01   
					Introduction   
					1 — 7   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					1.5   
					Optional Accessories   
					Optional Accessories describes the options available for upgrades and enhancement of the EX 5/7/11RT system.   
					Detailed installation of the unit is described in following sections.   
					To ensure a successful installation, all procedures should be followed in their correct sequence. Note that any   
					unauthorized installation may cause damage to the UPS(s) and void the MGE warranty.   
					1.5.1 Power Module Rail Kit   
					(Part Number 86001)   
					This kit is for rack mounting the power module in a 19" enclosure. See section 2.6 for rack installation of power   
					module.   
					Figure 1-7: Power Module Rack Mounting Kit.   
					24   
					25   
					26   
					Front mounting brackets.   
					27   
					24   
					25   
					Rear support brackets, part number   
					86013.   
					Telescopic rails, 695 mm to 1015 mm   
					length (27.36" to 39.96").   
					26   
					Input/Output Box bracket system, part   
					number 86012.   
					27   
					1.5.2 Battery/ Transformer/CLA Module Rail Kit   
					(Part number 86002)   
					This kit is for rack mounting of the battery/step-down transformer/CLA module in 19" enclosure. See section 2.6 for   
					rack installation of power module.   
					Figure 1-8: Telescopic rails for the Battery/Transformer/CLA module Rack mounting.   
					24   
					25   
					24   
					25   
					Front mounting brackets.   
					Rear support brackets, part number   
					86013.   
					26   
					26   
					Telescopic rails, 695 mm to 1015 mm   
					length (27.36" to 39.96").   
					1 — 8   
					Introduction   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					1.5.3 Battery Module with Remote Emergency Power Off (REPO) Function   
					(EXB 5/7 RT; PN 86079, EXB 11RT; PN 86119)   
					Standard HV EX 5/7/11RT system (one Power Module, EX 5/7/11 RT, and one Battery Module, EXB 5/7/11RT)   
					offers a standard backup time of 5 to 12 minutes at full load.   
					To increase backup time, it is possible to connect up to 5 additional EXB 5/7/11 RT modules to the EX 5/7/11 RT   
					module. See section 2.10 for connections between Power Module (EX 5/7/11 RT) and Battery Module (EXB 5/7/11   
					RT)   
					Figure 1-9: Typical back-up time with multiple EXB’s at full load.   
					Optional   
					Standard   
					Configurations   
					HV EX 5/7/11RT system   
					EXB 5 RT   
					EXB 7 RT   
					/ 
					EXB 5 RT   
					EXB 7 RT   
					/ 
					EXB 5 RT   
					EXB 7 RT   
					/ 
					EXB 5 RT   
					EXB 7 RT   
					/ 
					EXB 5 RT   
					EXB 7 RT   
					/ 
					EX 5/7/11RT EXB 5/7/11RT   
					+ 
					+ 
					+ 
					+ 
					+ 
					EXB 11 RT   
					EXB 11 RT   
					EXB 11 RT   
					EXB 11 RT   
					EXB 11 RT   
					5 kVA   
					7 kVA   
					: 
					12 min   
					7 min   
					30 min   
					20 min   
					14 min   
					55 min   
					32 min   
					75 min   
					45 min   
					98 min   
					57 min   
					42 min   
					118 min   
					70 min   
					53 min   
					: 
					11 kVA:   
					5 min   
					22 min   
					30 min   
					See Appendix for additional Back-up time information.   
					1.5.4 Battery Extension Cable Kit   
					( 6 ft / 1.8 m, Part number 86006)   
					This extended battery cable kit will be used instead of the standard battery cable when battery modules (EXBs) are   
					distant from each other (located in two different enclosures, for instance).   
					The battery extension cable kit includes a 6 ft long, straight connector battery power cable and a 6 ft. long battery   
					detection cable.   
					86-86000-00 A01   
					Introduction   
					1 — 9   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					1.5.5 Battery Integration Kit with Casters   
					(Part number 86005)   
					Battery Integration Kit is a cart, designed to hold up to 8 modules. It has swivel wheels with brakes, leveling feet,   
					seismic floor mount panels, plates to lock modules and hardware included. Modules not included.   
					Figure 1-10: Typical Battery Integration kit with casters setup.   
					TRANSFORMER MODULE   
					(optional)   
					POWER MODULE   
					BATTERY MODULES   
					(up to 6)   
					(Modules Not Included In Kit)   
					1.5.6 Input/Output Box   
					Shipped with ferrules for stranded wire application.   
					FF   
					O 
					O 
					- I/O Box 5/7kVA Part number 86009   
					- I/O Box 11kVA Part number 86010   
					1 — 10   
					Introduction   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					1.5.7 Transformer Module   
					This module provides isolated 120/208/240Vac output.   
					Figure 1-12: Typical Transformer Module contents and connections.   
					EX RT Transformer Module Contents   
					Transformer User Manual   
					Tower Stand Expanders   
					r 
					rme   
					fo   
					s 
					n 
					ra   
					T 
					T 
					R 
					X 
					E 
					Stabilizer Bracket   
					(4 screws included)   
					om   
					s.c   
					up   
					ge   
					.m   
					www   
					BATTERY MODULE   
					EXB RT   
					POWER MODULE   
					EX 5/7/11 RT   
					TRANSFORMER   
					MODULE EX RT   
					STEP-DOWN   
					TRANSFORMER   
					OUTPUT TO LOAD   
					AC NORMAL   
					INPUT   
					86-86000-00 A01   
					Introduction   
					1 — 11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					1.5.8 CLA Module (Long backup time charger)   
					(Part number 86004)   
					Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX   
					5/7/11RT via the CLA module.   
					IMPORTANT   
					The CLA can not be used to charge the battery module (EXB). It is designed to charge the   
					customer provided high power battery cabinet.   
					Figure 1-12: Connection for CLA Module and EX 5/7/11 RT.   
					CLA Module Contents   
					CLA Documentation   
					Tower Stand Expanders   
					Battery Power Cable   
					er   
					m 
					or   
					nsf   
					ra   
					T 
					T 
					R 
					X 
					E 
					Stabilizer Bracket   
					(4 screws included)   
					Battery Detection Cable   
					m 
					s.co   
					up   
					ge   
					w.m   
					ww   
					Typical High Power   
					CLA   
					Battery Cabinet   
					(not included)   
					EX 5RT /   
					EX 7RT /   
					EX 11RT   
					0A   
					5 
					Utility   
					~ 
					AC Source   
					(cable not included)   
					(see section 2.10 for cable   
					connection information)   
					(cable not included)   
					Table 5: Battery backup time chart.   
					Battery Backup Time   
					Recommended Batteries   
					EX 5RT   
					50 Ah   
					EX 7RT   
					65 Ah   
					EX 11RT   
					100 Ah   
					2 hours   
					4 hours   
					8 hours   
					100 Ah   
					200 Ah   
					130 Ah   
					200 Ah   
					200 Ah   
					400 Ah   
					Total battery voltage : 240 VDC (20 x 12VDC, one string).   
					The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization section 3.2.   
					1 — 12   
					Introduction   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Setup and Installation   
					2.0   
					2.1   
					Scope   
					Installation guides the user through tools and equipment required for making input/output power and communica-   
					tion cable connections, and battery installation and replacement. It provides assembly instructions, power cable   
					connections with wire diagrams for configuring the product to hardware specifications.   
					Unpacking and Parts Check   
					Once the EX 5/7/11RT system has been inspected and received from the shipping courier, the unit should be moved   
					to a position as close to the final installation location as possible. See Figures 2-1on page 2-3.   
					All Modules are shipped in separate boxes.   
					Prior to any installation, the following items should be observed upon receipt of the EX 5/7/11 RT.   
					1. Inspect shipment for any damage prior to receipt. Damage claims should be filed directly with the courier.   
					Replacements for damaged components should be ordered through MGE Customer Support Services at   
					1-800-438-7373.   
					2. Remove wrapping and foam corners to verify that the equipment nameplate (located on the rear of the units)   
					details a system that corresponds with the equipment ordered.   
					86-86000-00 A01   
					Installation   
					2 — 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.2   
					Contents of EX 5/7/11 RT System   
					Contents of Power Module:   
					Contents of Battery Module:   
					30   
					31   
					32   
					29   
					38   
					39   
					EX 5RT /EX 7RT/ EX 11RT.   
					Stabilizer Bracket and hardware.   
					Two sets of tower stands.   
					EXB 5/7/11 RT.   
					RS232 communication cable.   
					Product documentation.   
					Tower stand expanders.   
					Battery Power cable.   
					33   
					34   
					40   
					41   
					Input/Output Box. (With 9 insulated ferrules for   
					stranded wires.)   
					Battery/EX RT transformer/CLA   
					module rack mounting kit, PN 86002.   
					(PN 86009 for EX 5/7RT; 86010 for EX 11RT)   
					42   
					43   
					44   
					Battery detection cable.   
					EXB Documentation.   
					Bezel hex drive.   
					35   
					36   
					Solution-Pac CD.   
					Power Module rack mounting kit, PN 86001   
					(optional, but standard with Network Pack version).   
					37   
					SNMP/Web Network Management Card, PN 66074.   
					(optional, or standard with Network Pack version)   
					IMPORTANT   
					Packaging must be destroyed according to waste management standards.   
					Recycling icons are displayed for easy selection.   
					2 — 2   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Figure 2-1: Contents of Standard HV EX 5RT (PN 86050) / EX 7RT (PN 86070) / EX 11RT (PN 86110) System.   
					- EX 5RT Power Module Part number 86055   
					- EX 7RT Power Module Part number 86075   
					- EX 11RT Power Module Part number 86115   
					30   
					31   
					32   
					34   
					FF   
					O 
					O 
					T 
					R 
					1 
					1 
					X 
					E 
					33   
					35   
					- I/O Box 5/7kVA Part number 86009   
					- I/O Box 11kVA Part number 86010   
					37   
					36 (see 1.5.1)   
					IP=   
					MAC=00E0D8FF855E   
					Card Settings   
					100   
					10   
					UPS   
					data   
					eset   
					1 
					2 
					ON   
					RS232 Download   
					ETHERNET   
					RS232   
					66074   
					Standard only with Network Pack option.   
					- EX 5RT network Pack Part number 86052-01   
					- EX 7RT network Pack Part number 86072-01   
					- EX 11RT network Pack Part number 86112-01   
					38   
					39   
					40   
					42   
					T 
					R 
					B 
					X 
					E 
					29   
					41   
					43   
					44   
					(not to scale)   
					- EXB 5RT Battery Module Part number 86079   
					- EXB 7RT Battery Module Part number 86079   
					- EXB 11RT Battery Module Part number 86119   
					Standard only with   
					Network Pack version.   
					See 1.5.2.   
					86-86000-00 A01   
					Installation   
					2 — 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.3   
					Installation in Tower Configuration   
					Follow the numerical sequence to assemble tower stands and tower stand expanders, shown in Figure 2-2.   
					Figure 2-2: Tower Configuration of Standard System and Optional Transformer Module.   
					Tower Configuration with Standard System   
					5 
					R 
					T 
					E 
					X 
					B 
					R 
					T 
					1 
					1 
					E 
					X 
					Battery Module   
					Power Module   
					ON   
					F 
					OF   
					m 
					s.co   
					eup   
					.mg   
					www   
					m 
					s.co   
					eup   
					.mg   
					www   
					3 
					4 
					3 
					4 
					4 
					4 
					2 
					1 
					2 
					1 
					Tower Configuration with Optional Transformer Module   
					Use the same procedure   
					for tower mounting multiple   
					battery modules, if applicable.   
					5 
					R 
					T 
					E 
					X 
					B 
					R 
					T 
					1 
					1 
					E 
					X 
					Battery Modules   
					Power Module   
					ON   
					OFF   
					m 
					s.co   
					eup   
					.mg   
					www   
					m 
					s.co   
					eup   
					.mg   
					www   
					Transformer Module   
					.com   
					eups   
					.mg   
					www   
					3 
					4 
					3 
					4 
					4 
					4 
					2 
					1 
					2 
					1 
					2 — 4   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.4   
					Installation in Rack Mounting Configuration   
					2.4.1 Adjustment of Front Panel Logo and control panel for Rack Orientation.   
					NOTE   
					If system includes the transformer module, we recommend to mount the battery module   
					on the bottom, then mount the power module above the battery module and mount the   
					transformer on top for optimum stability.   
					To prepare the front panel logo and LCD display for rack orientation, of all modules. (including transformer or CLA   
					module, if equipped).   
					Proceed as follows:   
					1. Unclip logo plate, and pull the LCD display from front panel.   
					2. Rotate them 90 degree counter clockwise as shown.   
					3. Place items back onto the panel.   
					Figure 2-3: Typical orientation of the logo and control panel. (Power Module shown)   
					T 
					R 
					1 
					1 
					X 
					E 
					E 
					X 
					O 
					F 
					1 
					F 
					1 
					R 
					T 
					ON   
					F 
					OF   
					w 
					com   
					ps.   
					geu   
					w.m   
					w 
					ww   
					w 
					O 
					. 
					N 
					m 
					g 
					e 
					u 
					p 
					s.   
					c 
					o 
					m 
					FINISHED PANEL   
					(rack orientation)   
					E 
					X 
					O 
					F 
					1 
					F 
					1 
					R 
					1 
					T 
					1 
					w 
					w 
					w 
					. 
					m 
					O 
					g 
					e 
					N 
					u 
					p 
					s 
					. 
					c 
					o 
					m 
					2 
					2 
					T 
					R 
					om   
					1 
					s.c   
					eup   
					1 
					w 
					.mg   
					E 
					X 
					ww   
					ON   
					3 
					F 
					OF   
					3 
					86-86000-00 A01   
					Installation   
					2 — 5   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.5   
					Prepare Battery Module for Rack Mounting   
					(optional rails required, part number: 86002)   
					The battery module is very heavy. To ease its rack mounting, we strongly recommend to remove the battery pack   
					from the battery module, as explained below. See Section 1.2.2 for battery module weight.   
					Proceed as follows:   
					44   
					1. Unscrew the six screws securing front panel using Bezel Hex Driver   
					2. Unscrew the brackets securing the battery connectors.   
					3. Disconnect Battery plugs.   
					. 
					4. Unscrew the brackets securing the battery pack. Remove battery bracket pack covers.   
					5. Pull the left and right battery packs out and set aside for reinstalling after the battery module cabinet has been   
					rack mounted.   
					6. Mount battery module cabinet on rack.   
					7. Re-install the battery pack in reverse order.   
					Figure 2-4: Accessing Battery Pack.   
					3 
					3 
					2 
					T 
					R 
					B 
					X 
					E 
					2 
					4 
					4 
					com   
					ps.   
					geu   
					w.m   
					ww   
					1 
					1 
					x 6   
					44   
					(not to scale)   
					1 
					5 
					2 — 6   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.6   
					Power or Battery Module Rack Mounting   
					(optional rack mounting kits required, part number: 86001 and 86002)   
					The rails and necessary mounting hardware are supplied by MGE UPS SYSTEMS, INC.   
					Proceed as follows:   
					24   
					1. Attach both front mounting ear brackets   
					to power module or battery module with supplied screws. (For this   
					step, it is possible to adjust the position of both front mounting ears.)   
					26   
					2. Attach rails   
					together and secure with wing nuts, and finger tighten.   
					3. Attach both rails to rear and front of rack chassis with supplied screws (as shown).   
					4. Use caution when sliding unit into rack mount, secure unit to rack with supplied screws. (For this step, it is   
					possible to adjust the position of both front mounting brackets.)   
					Figure 2-6: Rack mounting of the power module onto the rails.   
					3 
					3 
					3 
					3 
					1 
					2 
					4 
					4 
					1 
					86-86000-00 A01   
					Installation   
					2 — 7   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.6.1 Rear Support Brackets Installation   
					(Part number 86013, included with rack mounting kits, part numbers: 86001 and 86002)   
					These brackets prevent the power module from moving when the entire rack enclosure is moved.   
					Proceed as follows:   
					25   
					1. Attach the brackets   
					to the I/O Box and power module.   
					2. Secure brackets to rails.   
					Figure 2-7a: Rear Support Brackets.   
					1 
					2 
					2 
					1 
					2.6.2 Input/Output Box Bracket System Installation   
					(Part number 86012 included with power module rack mounting kit, part numbers: 86001)   
					This bracket system keeps the I/O Box stationary while hot swapping the power module. It will then be easier to slide   
					the replacement module into the connectors of the I/O Box.   
					NOTE:   
					The rear support brackets must be removed prior to   
					installing I/O Box bracket system.   
					27   
					1. Secure small bracket to larger bracket from the underside   
					. 
					27   
					2 & 3. Secure large bracket   
					(with supplied screws) to rails at the rear of module.   
					4. Secure small attached bracket (with supplied screws) to the I/O Box.   
					Figure 2-7b: Input/Output Box Bracket System.   
					1 
					2 
					4 
					3 
					3 
					4 
					2 — 8   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.7   
					Communication Ports   
					EX 5/7/11RT provides 3 communication methods that can be used simultaneously:   
					5 
					◗ 
					The COM port   
					provides RS232 communications using MGE Serial HID UPS Transfer (SHUT)protocol.   
					This COM Port is compatible with Personal Solution Pac (PSP) to shutdown one computer. Personal Solution   
					Pac is included in the Solution Pac CD-Rom. For Network Management or multiple computer shutdowns an   
					optional network card must be purchased.   
					2 
					◗ 
					◗ 
					The Dry Contact Port   
					AS400) and more.   
					is used for basic signaling or for protection of IT systems like IBM iSeries (formerly   
					1 
					The slot   
					
					web site for the complete list of compatible cards)   
					2.7.1 Connecting the RS232 Communication Port   
					32   
					1. Connect the RS 232   
					communications cable to the serial port on the computer.   
					32   
					5 
					2. Connect the other end of the communications cable   
					EX 5/7/11 RT.   
					to the RS 232   
					communications port on the   
					The EX 5/7/11 RT System can now communicate with Personal Solution Pac for power management. UPS config-   
					uration settings are done by Personal Solution Pac for Windows.   
					Figure 2-8: RS232 Communication Cable Connection.   
					32   
					5 
					86-86000-00 A01   
					Installation   
					2 — 9   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2 
					2.7.2 Connecting the Dry (Relay) Contact Communication Port   
					The system status is indicated by the connection of common pin (Pin 5) to the appropriate pins. Refer to the pin   
					explanations below for details.   
					Figure 2-9: Relay Pin Connections for Communication Port.   
					Pin 1, 2: not used.   
					Pin 3: Remote Power Off signal (5 to 27 VDC, 10 mA max).   
					Pin 4: Operation on mains (not on battery). (48VDC, 2A max.)   
					5 
					4 
					3 
					2 
					1 
					Pin 5: User common.   
					Pin 6: Operation on automatic bypass.   
					Pin 7: Low battery.   
					9 
					8 
					7 
					6 
					Pin 8: Load protected   
					Pin 9: Operation on battery.   
					Legend:   
					NO   
					NC   
					common   
					NO   
					NO   
					NO   
					NO:   
					NC:   
					contact normally open.   
					contact normally closed.   
					2.7.3 Installation of Optional Network Management Card   
					It is not necessary to shut down the UPS to install the optional communications card, except for USB card. Following   
					is a typical installation of the Network Management Card, (PN 66074, standard with the network pack option.)   
					Proceed as follows:   
					1. Remove the slot cover secured by two screws.   
					37   
					2. Insert the card   
					into the slot.   
					3. Secure the card with both screws.   
					Figure 2-10: Communication Card Slot with SNMP/Web Network Management Card installed.   
					37   
					2 — 10   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					A wide range of optional cards will allow your UPS to talk to nearly all equipment management systems, making   
					integration faster and easier. All these cards can plug directly into the UPS, saving time and money on your next   
					UPS project. (Meta UPS Card and U-Talk /Basic Acquisition Cards are used exclusively with Multi-slot.)   
					Dual U-Talk/Basic Card   
					(66060) Provides two communications ports that may be configured   
					for serial link or AS/400 type dry contacts.   
					ModBus Card   
					(66061) Interface your UPS with a Building Management System.   
					Dual COM Ports Card   
					(66066) This card has two independent RS232 communication ports   
					on which it can be connected. One for connecting monitoring software   
					(included) and one for remote control panel UPS control.   
					USB Card   
					(66067) Take advantage of the latest and fastest communication   
					protocol for Microsoft Windows 2000/XP or Mac OSX.   
					Dual Volt Free Contacts   
					Card for AS/400   
					(66068) The two ports are used to supply UPS status information   
					or one port can be used as a Remote Power Off (REPO) port.   
					Alarm Relay Card   
					(66069) Six output relays show UPS status and two status inputs are   
					used with the Galaxy 3000 UPS.   
					XML-Web Card   
					SNMP-Web Card   
					(66073) XML-Web Card acts as a web page for your UPS information.   
					Used along with XML-ClientTM software, up to 50 servers or workstations will   
					be protected and can monitor the UPS with a simple web browser.   
					Security is handled with the SSL protocol, used by many websites to   
					safeguard sensitive password information.   
					(66074) The SNMP/Web 10/100BT communications card is   
					both an SNMP agent and an HTTP/Web server. Therefore, it   
					enables UPS supervision from any Network Monitoring   
					System using SNMP traps or simply from any web   
					browser (Internet Explorer, Netscape Navigator, etc.)   
					Orderly system shutdown of up to 32 protected servers can   
					be established using MGE’s Solution-Pac/WAN software   
					suite.   
					86-86000-00 A01   
					Installation   
					2 — 11   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					3 
					2.7.4 Remote Emergency Power Off (REPO) Communication Port   
					The end user is responsible for the installation of an emergency power off function. Installation must be carried out   
					in compliance with local code regulations.   
					To shutdown the entire system completely in case of emergency:   
					Disconnect the AC input to the power module.   
					Turn off the circuit breaker of the battery module connecting to the power module.   
					Turn off the circuit breaker of the subsequent battery modules, if applicable.   
					All these steps above should be performed via a single device.   
					To simplify the last two steps above, the power module provides an RJ-45 connector on the back panel, called   
					Remote Emergency Power Off (REPO) port. Upon applying a voltage source (5-27VDC, 10mA max.) to pins 2, 4 of   
					this port, the power module will send a signal to trip off the shunt trip on each circuit breaker of all battery modules   
					via the battery detection cable simultaneously. Refer to the diagram below for details.   
					Figure 2-10a: Activation of remote power off function using a contact normally open switch.   
					RJ11   
					3 
					6 5 4 3 2 1   
					Figure 2-10b: Activation of remote power off function using a contact normally closed switch.   
					RJ11   
					3 
					6 5 4 3 2 1   
					Signal:   
					Activation voltage: 5VDC to 27VDC   
					Current 10 mA (max)   
					NOTE   
					Both AC and DC sources must be present for normal start-up of EX 5/7/11RT   
					system. If the system is configured for cold start, the AC and DC sources are   
					required for initial start-up only.   
					2 — 12   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.8   
					Connecting the Input and Output Power Cables to the Input/Output Box   
					WARNING   
					This type of connection must be carried out by qualified electrical personnel.   
					14   
					Before carrying out any connections, check that battery circuit breaker   
					and that the upstream protection devices (Normal and Bypass AC   
					sources) are open (OFF).   
					is OFF   
					EX 5/7/11 RT UPS always comes from factory with Normal and Bypass AC inputs   
					already connected together, using a shunt.   
					2.8.1 Flexible Cordage and Conduit Installations   
					Figure 2-12a: Step 1 & 2; Typical plastic and metal coupling installations.   
					1. Knockout die stamp circles.   
					NOTE   
					1 
					Terminal cable capacity:   
					Outer circle is for   
					Plastic strain relief   
					Max. 4 AWG (11kVA), 6 AWG   
					(5/7kVA).   
					FF   
					O 
					O 
					I/O BOX   
					Inner circle is for   
					Metal strain relief   
					Knockout die stamp   
					circles (on terminal block   
					cover) have two sizes that fit   
					either plastic or metal   
					Terminal Block Cover   
					coupling. Plastic coupling is for   
					flexible cordage   
					and metal coupling is for solid   
					wires. Knock out appropriate   
					circle for your application.   
					F 
					OF   
					O 
					2. Remove bottom cover plate as shown.   
					3. Typical plastic strain relief installation:   
					2 
					a) Secure strain relief body onto the   
					knockout plate.   
					3. Typical Flexible Cordage Installation   
					OFF   
					0 
					OFF   
					0 
					b) Strip the jacket back to expose the   
					three wires. Strip the insulation of   
					each wire back 1/2”. Insert the   
					ferrules as shown to each wire.   
					(b)   
					F 
					OF   
					O 
					(c)   
					CAUTION:   
					Always connect the   
					earth ground wire first.   
					(a)   
					(d)   
					NOTE: Place lug ring inside   
					the terminal block cover.   
					Screw coupling into lug ring.   
					c) Slide the cordage into the strain relief   
					and secure the wires into the   
					terminal blocks using the guide   
					printed on bottom of I/O box.   
					4. Typical 90° Metal Conduit Installation   
					d) Secure the cordage retainer nut.   
					F 
					OF   
					O 
					OFF   
					O 
					4. Typical 90° metal conduit installation.   
					(c)   
					a) Secure strain relief body to knockout   
					plate as shown.   
					(b)   
					(a)   
					(d)   
					b) Insert three wires through flexible   
					conduit and bend 90°.   
					NOTE: Place lug ring inside   
					the terminal block cover.   
					Screw coupling into lug ring.   
					c) Strip the insulation back 1/2” to   
					expose solid wire and secure three   
					wires into the terminal block using   
					guide printed on bottom of I/O box.   
					CAUTION: Always connect the   
					earth ground wire first.   
					d) Install strain relief cover using two   
					screws.   
					86-86000-00 A01   
					Installation   
					2 — 13   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Figure 2-12b: Step 3; Typical Straight Metal Conduit installation.   
					5. Typical straight metal conduit   
					Installation.   
					5. Typical Straight Conduit Installation   
					F 
					OF   
					O 
					F 
					OF   
					O 
					a) Secure strain relief onto the   
					terminal block cover as shown.   
					(c)   
					(e)   
					b) Insert three wire through flexible   
					conduit.   
					(d)   
					(a)   
					(b)   
					c) Strip the insulation of each wire   
					back 1/2” to expose solid wire.   
					NOTE: Place lug ring inside   
					the terminal block cover.   
					Screw coupling into lug ring.   
					CAUTION: Always connect the   
					earth ground wire first.   
					d) Secure three wires into the terminal   
					block using guide printed on bottom   
					of I/O box.   
					e) Twist the conduit onto the coupling   
					body as shown.   
					Figure 2-12c: I/O Box Terminal Block Diagram.   
					Output   
					200/208/220/230/240Vac   
					Normal AC Source   
					200/208/220/230/240Vac   
					Bypass AC Source   
					200/208/220/230/240Vac   
					L6   
					L5   
					L2   
					L1   
					L1   
					L4   
					L3   
					Jumper   
					2 — 14   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.8.2 System Connections with Common Normal and Bypass AC Sources   
					Figure 2-13: Normal AC Input and Output Cables installation.   
					Proceed as follows:   
					1. Remove the I/O box from EX 5/7/11RT by   
					loosening three screws. Knockout appro-   
					priate circle for your wire style.   
					FF   
					O 
					O 
					1 
					CAUTION: Always connect the   
					earth ground wire first.   
					1. See section 2.8.1 to install normal AC   
					source and output wires per I/O Box   
					Terminal diagram. Re-install the cover plate   
					under the I/O Box.   
					2 
					2. Install the I/O Box with three screws.   
					FF   
					O 
					O 
					6704   
					CradSetings   
					dat   
					USP   
					HNRET   
					10   
					Rest   
					ON   
					12   
					R3S2Dwnload   
					MCA=0DF85E   
					I=P   
					To Step-Down   
					Transformer   
					(if applicable)   
					Simplified Connection Diagram   
					UPSTREAM   
					CIRCUIT   
					BREAKER   
					Bypass AC   
					Normal AC   
					(NOT SUPPLIED)   
					AC INPUT   
					Load to   
					Transformer Module   
					8 
					NOTE:   
					The power module factory default is for the common normal and bypass   
					AC source (single Main). AC input connections must be made to L1, L2,   
					and   
					terminals.   
					86-86000-00 A01   
					Installation   
					2 — 15   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.8.3 Connecting EX RT Transformer   
					(Part number 86003)   
					This module is to provide isolated 120/208/240 VAC outputs to the protected loads.   
					Figure 2-14: View of EX RT transformer connected downstream for 120/208/240 Vac outputs (shown with one EXB).   
					POWER MODULE   
					EX 5/7/11 RT   
					BATTERY MODULE   
					EXB 5/7/11 RT   
					TRANSFORMER   
					MODULE EX RT   
					Follow connection diagram for   
					appropriate input/output voltages.   
					AC NORMAL   
					INPUT   
					STEP-DOWN   
					TRANSFORMER   
					OUTPUT TO LOAD   
					Terminal Block Transformer Module Connection diagram   
					(located on bottom of Transformer I/O Box)   
					L3   
					L2   
					L1   
					Lb   
					Ld   
					N 
					Lc   
					La   
					Terminal Block capability :   
					120Vac   
					120Vac   
					208Vac   
					240Vac   
					AWG 4 solid or stranded wire.   
					208Vac   
					240Vac   
					AC Output   
					AC Input   
					Simplified Connection Diagram   
					Bypass AC   
					UPSTREAM   
					CIRCUIT   
					Transformer Module   
					BREAKER   
					(NOT SUPPLIED)   
					8 
					AC INPUT   
					Normal AC   
					To Load   
					2 — 16   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.8.4 System Connections with Separate Normal and Bypass AC Sources   
					CAUTION:   
					This installation requires 2 AC input source with Line, Neutral plus Ground,   
					(200-240VAC). Neutral points are connected together inside the UPS.   
					Figure 2-15: Normal AC Input, Bypass AC, and Output Cables Installation.   
					Proceed as follows:   
					1. Remove the cover plate under the I/O Box. Loosen   
					the terminal blocks L1 and L3, and remove the   
					jumper.   
					FF   
					O 
					O 
					1 
					L1   
					L3   
					CAUTION: Always connect the   
					earth ground wire first.   
					2. See section 2.8.1 and I/O Box terminal diagram for   
					installation of Normal AC Input, Bypass AC   
					source, and Output cable with different wire style.   
					3. Reinstall the cover plate under the I/O Box with   
					four screws.   
					FF   
					O 
					O 
					2 
					4. Secure the I/O Box to the power module using   
					three screws.   
					Bypass   
					Normal   
					Output   
					See section 2.8.3 for connecting EX RT   
					Transformer, if applicable.   
					3 
					4 
					FF   
					O 
					O 
					6074   
					s 
					g 
					CardSetin   
					dta   
					UPS   
					HRNET   
					10   
					5E   
					8 
					Rset   
					F 
					8 
					ON   
					12   
					RS32Dwnload   
					MAC=E0D   
					IP=   
					To Step-Down   
					Transformer   
					(if applicable)   
					86-86000-00 A01   
					Installation   
					2 — 17   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.8.5 System Connections as Frequency Converter (without Bypass AC Source)   
					Figure 2-16: Accessing Terminal Blocks for Input and Output power cables.   
					FF   
					O 
					CAUTION: Always connect the   
					earth ground wire first.   
					O 
					1. Remove the cover plate under the I/O Box.   
					Remove the jumper connecting L3 and L1.   
					1 
					CAUTION:   
					Do not connect anything to the   
					Bypass AC terminal block.   
					F 
					OF   
					O 
					2. Refer to section 2.8.1 to install normal AC source   
					and output wires per I/O Box Terminal diagram. Re-   
					install the cover plate under the I/O Box.   
					2 
					3. Secure the I/O Box to power module with three   
					screws.   
					See section 2.8.3 for connecting EX RT   
					Transformer, if necessary.   
					3 
					F 
					OF   
					O 
					6074   
					s 
					g 
					CardSetin   
					dta   
					UPS   
					HRNET   
					10   
					5E   
					8 
					Rset   
					F 
					8 
					ON   
					12   
					RS32Dwnload   
					MAC=E0D   
					IP=   
					To Step-Down   
					Transformer   
					2 — 18   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					2.9   
					Connection of Battery Module, EXB   
					14   
					1. Check that the battery circuit breaker   
					is OFF (“0”) position.   
					40   
					6 
					13   
					2. Connect the battery power cable   
					modules.   
					to the connectors   
					and   
					of the power and battery   
					12   
					of the power and battery   
					42   
					4 
					3. Connect the battery detection cable   
					modules.   
					between connectors   
					and   
					Figure 2-17: Rear view of battery module cable connections.   
					12   
					4 
					42   
					40   
					13   
					6 
					14   
					86-86000-00 A01   
					Installation   
					2 — 19   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					2.10   
					Connection of CLA Module   
					40   
					42   
					1. Connect the battery power cable   
					and battery detection cable   
					(provided with the CLA module)   
					between the power module and the CLA module.   
					2. Connect the DC Input of the CLA to high power battery cabinet.   
					◗ 
					DC Input Cable cross-section (not provided): maximum 4 AWG solid or stranded wire.   
					3. Connect the AC input cable of the CLA module to the utility AC input:   
					AC input cable cross-section (not provided): maximum 16 AWG solid or stranded wires.   
					◗ 
					Figure 2-18: Rear view of CLA module cable battery and AC input connections.   
					Connection Diagram   
					(inside CLA Module)   
					42   
					N 
					(L2)   
					L 
					(L1)   
					- 
					+ 
					DC INPUT   
					AC INPUT   
					156-280Vac   
					40   
					240Vdc   
					To High   
					Power Battery   
					Cabinet   
					Utility AC Source   
					2 — 20   
					Installation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Operation   
					3.0   
					3.1   
					Scope   
					Operation describes EX 5/7/11RT system characteristics of indicators and controls, modes and specifications and   
					theory of operating the EX 5/7/11RT. The user procedures include performing software programming that will   
					maintain smooth performance. Refer to Figure 1.6 for descriptions of circled numbers.   
					Initial Startup   
					7 
					1. Check that the manual bypass switch   
					is on Normal position.   
					8 
					2. Set the normal AC source circuit breaker   
					to the ON position.   
					14   
					3. Set the battery circuit breaker   
					to the ON position.   
					The load is powered via the bypass AC source, but not protected by the UPS.   
					Batteries are recharging, an eight-hour recharge period is necessary to get full backup time.   
					17   
					LED   
					is ON.   
					Figure 3-1: Initial Startup Display.   
					17   
					OFF   
					ON   
					86-86000-00 A01   
					Operation   
					3 — 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					3.2   
					UPS Personalization   
					IMPORTANT   
					If specific settings are required, it is recommended to   
					enter the UPS personalization mode at this stage.   
					It is possible to enter this mode through the front panel   
					buttons or the Personal Solution-Pac software for   
					Windows included in the MGE UPS SYSTEMS, INC. Solution-   
					Pac power management suite CD-ROM.   
					3.2.1 Accessing personalization with front panel buttons   
					20   
					21   
					function buttons together for more than 3 sec-   
					◗ 
					◗ 
					Press "scroll up"   
					onds.   
					and "scroll down"   
					21   
					Press the function button   
					placed under the “ENT” word to enter the set up mode and   
					follow the LCD messages using the buttons now defined as select keys. See Tables: 3-1,   
					3-2, 3-3, and 3-4 for settings.   
					Figure 3-2: Control Panel with scroll up and down buttons.   
					UPS SET UP   
					EXIT ENT   
					OFF   
					ON   
					20   
					21   
					3 — 2   
					Operation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Table 3-1: Local Settings.   
					Display   
					Factory setting   
					Options   
					Language   
					English   
					French, Spanish, German, Italian   
					Date / time format   
					International format   
					US format   
					(DD-MM-YYYY/HH:MM)   
					(MM-DD-YYYY/HH:MM AM/PM)   
					Date / time change   
					Audible alarm   
					GMT (Greenwich Mean Time)   
					Quick beeps   
					MM-DD-YYYY/HH:MM adjustable   
					Slow beeps   
					Table 3-2: Output features.   
					Display   
					Factory setting   
					Options   
					Comments   
					Output voltage   
					208 Volts AC   
					Disabled   
					200/208/220/230/240/250   
					Enabled   
					Frequency converter   
					Output frequency   
					Bypass AC source disabled   
					Auto ranging   
					50/60 Hz   
					User selectable under   
					frequency converter mode   
					Eco mode   
					Disabled   
					Enabled   
					See glossary   
					Hot standby   
					Operating mode   
					Disabled   
					Enabled   
					Full redundancy (see Figure 3-3)   
					IT Network   
					Industrial   
					(*) See Section 4.1   
					(*)   
					Bypass   
					Transfer   
					When bypass OK (**)   
					When bypass NOK (**)   
					Interrupt time   
					10 ms   
					10 to 200 ms   
					(by steps of 10 ms)   
					Interrupt time calibration during   
					during load transfer on   
					Bypass AC source   
					out of tolerances   
					Overload level   
					102%   
					50/70%   
					(*) : - Select "IT Network" for computer loads.   
					- Select "Industrial" when bypass NOK in case of absolute need for service continuity (with potential   
					10 ms interrupt).   
					(**) UPS will switch to Bypass AC Source if it is within the set tolerances.   
					Figure 3-3: Configuration used to provide full redundancy (2N) to critical loads.   
					BYPASS AC   
					Full redundancy configuration   
					offers better protection to   
					Protective Device   
					critical load, whereas the first   
					UPS acts as the Bypass AC   
					NORMAL AC   
					Source for the second UPS.   
					Utility   
					AC Source   
					Protective Device   
					NORMAL AC   
					LOAD   
					86-86000-00 A01   
					Operation   
					3 — 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Table 3-3: ON/OFF features.   
					Display   
					Factory setting   
					Options   
					Enabled   
					Disabled   
					Comments   
					Cold start   
					Disabled   
					Enabled   
					Start on battery.   
					Forced reboot   
					Enables automatic restart of   
					the system even if normal AC   
					source is restored before the   
					end of the shutdown sequence.   
					Automatic restart   
					Enabled   
					Disabled   
					UPS restarts automatically   
					when normal AC source   
					is restored.   
					Sleep mode   
					Disabled   
					Enabled   
					Enabled   
					Disabled   
					Automatic shutdown on battery   
					if output load level <10%   
					Remote Command   
					Enables shutdown or restart   
					orders from software.   
					Table 3-4: Battery features.   
					Display   
					Factory setting   
					Every week   
					20%   
					Options   
					Comments   
					Battery test   
					No test/daily/monthly   
					0 to 100%   
					Pre-Alarm   
					Low battery signal;1% increment   
					Runtime choice   
					UPS reads # and type   
					of battery   
					modules connected.   
					From 65 to 400 Ah   
					Requires EX 5/7/11RT CLA if   
					using options (see section 1.5.4   
					“Battery extensions cable kit”)   
					Battery deep discharge   
					protection   
					Enabled   
					Disabled   
					If disabled, loss of   
					MGE UPS SYSTEMS,INC.   
					warranty.   
					3.2.2 Accessing personalization through external software   
					Insert the Solution-Pac CD ROM in your CD drive.   
					◗ 
					At the first Navigator Screen, select "Installation" and follow the instructions to install Personal   
					Solution-Pac for Windows.   
					◗ 
					If nothing appears, launch startup.exe   
					Then go to "Advanced settings" and "UPS settings".   
					◗ 
					Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.   
					3.2.3 Final startup sequence   
					Press the <ON> button more than 3 seconds.   
					15   
					goes on.   
					◗ 
					After UPS internal test sequence, the green LED   
					CAUTION   
					During the restart, if the Bypass AC source is out of   
					tolerance, the UPS will generate an output   
					calibrated 10 msec output interrupt.   
					3 — 4   
					Operation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					3.3   
					Operating Modes   
					3.3.1 Normal (double conversion) Mode   
					Figure 3-4: Normal (double conversion) mode.   
					This is the standard operating mode, set by the   
					factory.   
					15   
					Two possible cases.   
					1. If Normal AC source available:   
					15   
					LED is ON.   
					LOAD LEVEL   
					4kW / 5 kVA   
					The load is protected by the UPS.   
					OFF   
					ON   
					21   
					22   
					function buttons   
					Scroll up   
					and scroll down   
					allow you to read the UPS measurements (Normal AC   
					source voltage, Bypass AC source voltage, operating   
					mode, battery capacity and UPS Serial Number).   
					15   
					16   
					2. If Normal AC source not available:   
					CAUTION:   
					Do not operate the Manual Bypass switch   
					when the UPS is in Normal mode.   
					REMAINING TIME   
					10 minutes   
					15   
					16   
					LED flashes.   
					LED is ON.   
					OFF   
					ON   
					The audible alarm sounds intermittently.   
					The load is now powered by the UPS battery.   
					This display shows remaining back-up time.   
					86-86000-00 A01   
					Operation   
					3 — 5   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					3.3.2 ECO Modes   
					Figure 3-5: ECO mode display.   
					The main advantage of the ECO mode (see glossary)   
					is that it reduces the consumption of electrical power.   
					15   
					17   
					Three possible cases:   
					1. If Bypass AC source available:   
					15   
					17   
					and   
					LED are ON.   
					The load is supplied with AC power but not protected   
					in ECO mode.   
					15   
					2. If Bypass AC source not available:   
					15   
					LED is ON.   
					The audio alarm sounds intermittently.   
					The load is automatically supplied in Normal   
					mode via the Normal AC input.   
					15   
					16   
					3. Both Normal and Bypass AC sources not   
					available or out of tolerance:   
					15   
					16   
					LED is ON.   
					LED is ON.   
					The audio alarm sounds intermittently.   
					The load is powered by the battery power from the   
					UPS.   
					The display indicates the battery remaining   
					backup time.   
					3 — 6   
					Operation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					3.4   
					Operation on battery power   
					Figure 3-6: Transfer, Threshold and End of backup time.   
					3.4.1 Transfer to Battery Power   
					15   
					16   
					The load continues to be protected by the UPS when   
					the Normal AC source is not available. Power is   
					supplied by the battery.   
					There are three possible cases:   
					REMAINING TIME   
					10 minutes   
					First Case:   
					15   
					16   
					LED is ON.   
					LED is ON.   
					OFF   
					ON   
					The audio alarm beeps every 10 seconds.   
					15   
					16   
					◗ 
					◗ 
					This indicate the load is supplied by the battery.   
					The display indicates the battery remaining   
					backup time.   
					Second Case:   
					REMAINING TIME   
					2 minutes   
					15   
					16   
					LED is ON.   
					LED is ON.   
					OFF   
					ON   
					The audio alarm beeps every 3 seconds.   
					◗ 
					Low battery warning on display. There is very little   
					remaining battery backup time. Close all appli-   
					cations because UPS automatic shutdown is   
					pending.   
					15   
					16   
					17   
					Third Case:   
					15   
					16   
					LED is OFF.   
					LED is OFF.   
					SHUTDOWN DUE   
					TO DEPLETED BATTERY   
					The audio alarm is stopped.   
					OFF   
					ON   
					◗ 
					The load is transferred to the Bypass AC source if   
					available. In this case:   
					17   
					LED is ON.   
					86-86000-00 A01   
					Operation   
					3 — 7   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					3.5   
					Return of Normal AC source   
					After an outage, the UPS restarts automatically when AC power is restored (unless this function has been disabled   
					via UPS personalization).   
					3.6   
					Shutdown   
					Figure 3-7: Shutdown display, circuit breaker, and AC source switch.   
					19   
					1. Press the OFF button   
					seconds.   
					more than 3   
					17   
					The load is no longer protected by the UPS. It is   
					powered via the bypass AC source. If the UPS is   
					set in frequency converter mode, the load will not   
					be powered.   
					If the bypass AC source is out of tolerance, the   
					UPS will generate a calibrated 10msec output   
					interrupt.   
					OFF   
					ON   
					14   
					2. Set the battery circuit breaker(s)   
					OFF position.   
					to the   
					19   
					14   
					3. Set the Normal AC source circuit breaker   
					8 
					to the OFF position.   
					8 
					4. For a full shutdown of UPS and connected   
					load, the upstream circuit breaker (not   
					included) should be set to the OFF position.   
					3 — 8   
					Operation   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Maintenance   
					4.0   
					4.1   
					Scope   
					Maintenance includes a troubleshooting guide of symptoms and possible solutions, Hot swapping the power module   
					and Battery Module, and testing scenarios.   
					Information Technology (IT) Network and Industrial Operating Modes   
					Table 4-1: Network and Industrial Modes of Operation.   
					Symptoms   
					IT network mode   
					Industrial mode   
					Overload, and Bypass   
					source in tolerance.   
					Load is transferred to Bypass AC source.   
					UPS returns to normal mode if overload   
					is removed.   
					Same as I/T network mode, but AC   
					to the UPS does not return to   
					normal mode if overload   
					is removed.   
					Overload, and Bypass   
					AC source not in tolerance.   
					The UPS shuts down and load is not   
					transferred to Bypass AC source.   
					Load is transferred to Bypass   
					AC source with 10 milli-   
					seconds output break.   
					The UPS does not return to   
					normal mode if overload   
					is removed.   
					Output short circuit and Bypass The load remains powered by the UPS.   
					Load is transferred to Bypass   
					AC source, the UPS returns to   
					normal mode if the short circuit   
					is removed.   
					AC source in tolerance.   
					The UPS shuts down after 3 minutes   
					if the short circuit remains   
					Output short circuit and Bypass The load remains powered by the UPS.   
					The load is transferred to   
					Bypass AC source with   
					10 milliseconds output break.   
					The UPS does not return to   
					normal mode if the short circuit   
					is removed.   
					AC source not in tolerance.   
					The UPS shuts down after 3 minutes   
					if the short circuit remains.   
					86-86000-00 A01   
					Maintenance   
					4 — 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					4.2   
					Troubleshooting   
					17   
					18   
					is on, there is an operating anomaly or an alarm.   
					◗ 
					◗ 
					◗ 
					If any of LED's   
					or   
					Use "scroll up" or "scroll down" function button to reset the audible alarm.   
					Troubleshooting not requiring MGE UPS SYSTEMS, INC. after-sales support:   
					Table 4-2: Troubleshooting not requiring MGE after-sales support.   
					Symptom   
					Indication   
					Correction   
					17   
					LED   
					is on, and Bypass AC   
					AC source is not connected   
					to the correct terminals.   
					Rewire correctly the normal AC   
					source.   
					source is present   
					the alphanumeric display shows   
					BAD CONNECTION   
					REWIRE AC NORMAL   
					17   
					LED   
					is on,   
					Load supplied by bypass AC source.   
					UPS overload   
					Push the ON button for more than 3   
					seconds.   
					the alphanumeric display shows:   
					LOAD LEVEL   
					XX kW / XX KVA   
					17   
					LED   
					is on, and Bypass AC   
					Check if any device is shorted or failed.   
					source is present   
					the alphanumeric display shows:   
					THERMAL OVERLOAD   
					1XX%   
					18   
					LED   
					is on,   
					Short circuit conditions on output   
					devices.   
					Check if any device is shorted or   
					failed.   
					the alphanumeric display shows:   
					CURRENT OVERLOAD   
					15   
					LED   
					is on,   
					180° degree phase shift between   
					bypass and normal AC source.   
					Check if bypass source is correctly   
					wired   
					but the alphanumeric display shows:   
					BYPASS REVERSE   
					(in case of upstream transformer use).   
					REWIRE BYPASS   
					Audible alarm is on,   
					the alphanumeric display shows:   
					I/O BOX REMOVED   
					Input/Output box not   
					installed correctly.   
					Check if the Input/Output box   
					is correctly installed. See section 2.8.   
					4 — 2   
					Maintenance   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					Table 4-3: Troubleshooting requiring MGE after-sales support.   
					Symptom   
					Indication   
					Correction   
					17   
					18   
					LED   
					and   
					are on,   
					Internal fault   
					Call the after sales support department.   
					Bypass AC Source is present   
					and audible alarm is on.   
					the alphanumeric display shows:   
					xxx FAULT   
					and transfer of load   
					on bypass AC source   
					17   
					LED   
					is on, and audible alarm   
					Battery fault during the battery test.   
					Call the after sales support department.   
					Call the after sales support department.   
					is on, the alphanumeric display   
					shows   
					BATTERY FAULT   
					17   
					LED   
					is on,   
					Static switch failure   
					the alphanumeric display shows:   
					SHUTDOWN   
					STATIC SW FAILED   
					Audible alarm is on,   
					the alphanumeric display shows:   
					END OF WARRANTY   
					Batteries may have exceeded   
					their rated life period. Battery   
					capacity is severely reduced.   
					Follow the battery replacement procedure   
					in section 4.5.   
					21   
					22   
					for more than 3 seconds.   
					NOTE: To reset the alarm permanently, press both function buttons   
					and   
					86-86000-00 A01   
					Maintenance   
					4 — 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					4.3   
					Hot Swapping the Power Module   
					This operation can be performed without interrupting the load.   
					Figure 4-1: Disconnecting the power module.   
					17   
					19   
					1. Stop the UPS with the OFF button   
					more than 3 seconds).   
					(press   
					Check if UPS is on bypass AC source:   
					17   
					17   
					is not on, do not   
					LED   
					is on (If LED   
					XXX FAULT   
					1CXXXXXXX   
					turn the manual bypass and call the after sales   
					support department).   
					OFF   
					ON   
					7 
					2. Turn the manual bypass switch   
					BYPASS position.   
					to the   
					19   
					14   
					3. Switch the battery circuit breaker(s)   
					OFF position.   
					to the   
					Tower configuration   
					gs   
					tin   
					et   
					S 
					rd   
					Ca   
					CAUTION: Do not switch the Normal AC   
					S 
					a 
					10   
					UP   
					E 
					0 
					8 
					55   
					10   
					dat   
					8FF   
					74   
					660   
					= 
					MA   
					E0D   
					IP   
					2 
					23   
					C=00   
					RS   
					set   
					Re   
					2 
					1 
					T 
					RNE   
					THE   
					ON   
					E 
					ad   
					nlo   
					Dow   
					232   
					RS   
					8 
					source circuit-breaker   
					to   
					42   
					40   
					the OFF position. Doing so   
					7 
					will disconnect power to the   
					load.   
					φ 
					4. Loosen three screws to remove the   
					P 
					B 
					A 
					Y 
					S 
					S 
					Input/Output box.   
					8 
					40   
					42   
					5. Disconnect the battery cables   
					from the power module.   
					and   
					12   
					Rack configuration   
					The power module can be replaced.   
					The connected equipment is powered by the   
					Bypass AC source.   
					4 — 4   
					Maintenance   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					4.4   
					Re-connecting the power module   
					This operation can be performed without interrupting the load.   
					Figure 4-2: Reconnect the power module.   
					1. Secure the Input/Output junction box using the   
					three screws.   
					15   
					17   
					40   
					42   
					2. Reconnect the cables   
					power module.   
					and   
					to the   
					to the   
					14   
					3. Switch the battery circuit breaker(s)   
					ON position.   
					LOAD LEVEL   
					4 kW/ 5 kVA   
					OFF   
					ON   
					4. Check if Normal AC source circuit breaker   
					8 
					is on the ON position.   
					22   
					17   
					5. Check that the LED   
					is on.   
					6. Turn the manual bypass switch from the   
					BYPASS to the NORMAL position.   
					7. Follow initial start up sequence (see section   
					3.1) in order to personalize the UPS.   
					22   
					8. Push the ON button   
					seconds.   
					for more than 3   
					15   
					The green LED   
					is on, and the connected   
					equipment is now protected by the UPS.   
					86-86000-00 A01   
					Maintenance   
					4 — 5   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					4.5   
					Hot Swapping the Battery Module   
					Figure 4-3: Rear view of the battery module.   
					4.5.1 Disconnecting the Battery Module   
					Battery Module Power Module   
					14   
					1. Switch the battery circuit breaker(s)   
					OFF position.   
					to the   
					40   
					42   
					40   
					42   
					from the   
					2. Disconnect the cables   
					power module.   
					and   
					The battery module can be replaced.   
					The connected equipment is powered by the UPS,   
					but not protected.   
					It is also possible to replace battery pack instead of   
					battery module.   
					Contact your nearest after sales support service.   
					CAUTION: Always replace both battery   
					packs with new ones.   
					To remove battery pack:   
					1. First, switch the battery circuit breaker(s) to the   
					OFF position.   
					See section 2.5 and follow instructions for battery   
					pack replacement.   
					14   
					4.5.2 Re-connecting the Battery Module   
					40   
					42   
					1. Reconnect the battery cables   
					the power module.   
					and   
					to   
					14   
					2. Switch the battery circuit breaker(s)   
					ON position.   
					to the   
					4 — 6   
					Maintenance   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Appendix   
					5.0   
					5.1   
					Electrical Specifications   
					System Input/Output Power Ratings   
					Table 5-1: EX 5/7/11 RT Input and Output Characteristics.   
					Source   
					Voltage   
					Frequency   
					Normal AC Source   
					Bypass AC Source   
					Load Output   
					208 to 240 Volts AC   
					208 to 240 Volts AC*   
					40 to 70 Hz   
					48 to 52 Hz**   
					120/240Vac Volts AC   
					(120/208/240Vac   
					are possible with   
					transformer module)   
					50/60 Hz autoranging   
					(or frequency converter)   
					(*): depends on output voltage setting, can be modified by software.   
					(**): set to +/- 4% by default, (1,2,4,8% are possible values), can be modified by software.   
					5.2   
					System Overload Characteristics   
					Figure 5-1: Power supplied as a function of input voltage (left), and Permissible UPS overloads as a function of time (right).   
					Load Percentage   
					Load Percentage   
					1.5   
					100%   
					70%   
					1.25   
					1.1   
					1.02   
					t 
					U 
					0.5s   
					30s   
					60s   
					120s   
					120V 160V   
					280V   
					5.3   
					System Backup Characteristics   
					Table 5-2: Back-up Time ( in minutes).   
					System   
					Load Percentage   
					30%   
					25   
					50%   
					14   
					70%   
					9 
					100%   
					5 
					Standard 11kVA   
					Standard 11kVA + 1 EXB   
					Standard 11kVA + 2 EXB   
					Standard 11kVA + 3 EXB   
					Standard 11kVA + 4 EXB   
					Standard 11kVA + 5 EXB   
					Standard 7kVA   
					Standard 7kVA + 1 EXB   
					Standard 7kVA + 2 EXB   
					Standard 7kVA + 3 EXB   
					Standard 7kVA + 4 EXB   
					Standard 7kVA + 5 EXB   
					Standard 5kVA   
					Standard 5kVA + 1 EXB   
					Standard 5kVA + 2 EXB   
					Standard 5kVA + 3 EXB   
					Standard 5kVA + 4 EXB   
					Standard 5kVA + 5 EXB   
					61   
					96   
					135   
					172   
					201   
					37   
					30   
					53   
					84   
					102   
					113   
					21   
					53   
					83   
					108   
					132   
					164   
					31   
					20   
					34   
					51   
					67   
					87   
					12   
					30   
					55   
					75   
					98   
					118   
					21   
					53   
					83   
					108   
					132   
					164   
					14   
					22   
					30   
					42   
					53   
					7 
					20   
					32   
					45   
					57   
					72   
					12   
					30   
					55   
					75   
					98   
					118   
					80   
					124   
					185   
					245   
					287   
					37   
					90   
					70   
					140   
					185   
					255   
					306   
					112   
					156   
					207   
					260   
					86-86000-00 A01   
					Appendix   
					5 — 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Table 5-3: Battery Recharge time to recover 90% of the rated backup time after discharge at full load.   
					Configuration for   
					2 hours backup time   
					Configuration for   
					4 hours backup time   
					Configuration for   
					8 hours backup time   
					EX 5   
					EX 7   
					7 hours   
					5 hours   
					7 hours   
					15 hours   
					12 hours   
					15 hours   
					24 hours   
					20 hours   
					24 hours   
					EX 11   
					5.4   
					5.5   
					System Short Circuit Protection   
					Short circuit current provided by EX 5/7/11RT in normal or battery mode:   
					EX5/7 RT   
					EX11 RT   
					110A for 80ms   
					190A for 80ms   
					Accessories Electrical Characteristics   
					EX RT Transformer   
					Nominal power   
					11 kVA   
					Nominal current   
					63 A   
					Input voltage   
					Output Voltage   
					Frequency   
					Isolation (EN 61558-1-2-4)   
					Operating temperature   
					Max. operating rel. humidity   
					Derating / altitude   
					Dimensions HxWxD (tower)   
					Dimensions HxWxD (rack 3U)   
					Weight   
					208-240Vac   
					120/208/240Vac   
					50/60 Hz (+/-10%)   
					3.75 kV / 5 M ohms   
					From 0° to +40°C   
					95%   
					Pn-10% > 1000 m   
					17.5 x 5.15 x 25 inches (444 x 131 x 635 mm)   
					5.15 x 17.5 x 25 inches (131 x 444 x 635 mm)   
					151 lbs. (68.5 kg)   
					EX RT CLA module   
					AC input voltage   
					Input frequency   
					156-280 Volts AC   
					40-70 Hz   
					Battery charge current   
					6 A DC   
					5.6   
					Heat Rejection   
					Table 5-4: Full load heat rejection in BTU’s/hr.   
					System   
					Operation Mode   
					On-line   
					1327   
					On Battery   
					1944   
					5kVA   
					7kVA   
					11kVA   
					1858   
					2722   
					2919   
					4278   
					5.7   
					Environmental Characteristics   
					◗ 
					The operating temperature is 0 to 40°C (8 hours at 45°C), however optimum operation is within the +20 to +25°C   
					range and at 5-95% humidity, non-condensing at altitude up to 3280ft without de-rating.   
					◗ 
					◗ 
					The storage temperature : -20 to 40°C. Humidity : 5-95%, non condensing.   
					Battery backup time is adversely affected by high and low temperatures. It is significantly reduced at tempera-   
					tures under 10°C. Above 25°C, battery service life is cut in half every 10°C. Above 40°C, battery manufacturers   
					no longer guarantee operation due to the risk of thermal runaway.   
					◗ 
					Air enters through the front air vent grills and exits through the back. Always keep air vent grills unobstructed.   
					5 — 2   
					Appendix   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				MGE Warranty & Proprietary Rights for Single Phase Products   
					MGE Warranty   
					The liability of MGE UPS SYSTEMS, INC. hereunder is limited to replacing or repairing at MGE UPS SYSTEMS,   
					INC.’s factory or on the job site at MGE UPS SYSTEMS, INC.’s option, any part or parts which are defective, including   
					labor, for a period of 24 months from the date of purchase. The MGE UPS SYSTEMS, INC. shall have the sole right   
					to determine if the parts are to be repaired at the job site or whether they are to be returned to the factory for repair   
					or replacement. All items returned to MGE UPS SYSTEMS, INC. for repair or replacement must be sent freight   
					prepaid to its factory. Purchaser must obtain MGE UPS SYSTEMS, INC.’s Return Materials Authorization prior to   
					returning items. The above conditions must be met if warranty is to be valid. MGE UPS SYSTEMS, INC. will not be   
					liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misapplication of   
					the item, or for damage due to accident, abuse, or Act of God.   
					In no event shall the MGE UPS SYSTEMS, INC. be liable for loss, damage, or expense directly or indirectly arising   
					from the use of the units, or from any other cause, except as expressly stated in this warranty. MGE UPS SYSTEMS,   
					INC. makes no warranties, express or implied, including any warranty as to merchantability or fitness for a particular   
					purpose or use. MGE UPS SYSTEMS, INC. is not liable for and Purchaser waives any right of action it has or may   
					have against MGE UPS SYSTEMS, INC. for any consequential or special damages arising out of any breach of   
					warranty, and for any damages Purchaser may claim for damage to any property or injury or death to any person   
					arising out of its purchase of the use, operation or maintenance of the product. MGE UPS SYSTEMS, INC. will not   
					be liable for any labor subcontracted or performed by Purchaser for preparation of warranted item for return to MGE   
					UPS SYSTEMS, INC.’s factory or for preparation work for field repair or replacement. Invoicing of MGE UPS   
					SYSTEMS, INC. for labor either performed or subcontracted by Purchaser will not be considered as a liability by the   
					MGE UPS SYSTEMS, INC.   
					This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a   
					writing signed by an officer of the MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser but to no   
					one else. Accessories supplied by MGE UPS SYSTEMS, INC., but manufactured by others, carry any warranty the   
					manufacturers have made to MGE UPS SYSTEMS, INC. and which can be passed on to Purchaser.   
					MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any   
					patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent.   
					Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any patent   
					claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to Purchaser’s   
					specific design.   
					Purchaser has not relied and shall not rely on any oral representation regarding the Product sold hereunder and any   
					oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.   
					There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS   
					SYSTEMS, INC. be responsible for consequential damages or for any damages except as expressly stated herein.   
					Proprietary Rights Statement   
					The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in   
					which MGE UPS SYSTEMS, INC., retains any and all patent rights, including exclusive rights of use and/or manufac-   
					ture and/or sale. Possession of this information does not convey any permission to reproduce, print, or manufacture   
					the article or articles shown herein. Such permission may be granted only by specific written authorization, signed by   
					an officer of MGE UPS SYSTEMS, INC.   
					IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and MGE   
					UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein are owned   
					by their respective companies and are referred to in an editorial fashion only.   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Warranty and Product Registration   
					Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality   
					requirements. We are pleased to have you join our increasing family of users.   
					In order to maximize the value you receive from this product, and to ensure that you are kept informed of   
					product or software updates, we recommend that you take a few minutes to register your new purchase.   
					You may register online at the URL noted below. Should you not have Internet access, you may mail or fax   
					this form back (attn: Warranty Registration) as indicated at the bottom of the page.   
					
					Please be prepared with the following information to register and validate your UPS warranty, keep   
					informed on software and product updates, and register your extension "Warranty+" if purchased with the   
					UPS.   
					User Information   
					Last name   
					First name   
					Company name   
					Address   
					Zip code   
					City   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					________________________________________   
					State/Province   
					Country   
					Tel   
					Fax *   
					Email*   
					Product information   
					Model   
					________________________________________   
					________________________________________   
					Serial Number   
					Date of purchase ________________________________________   
					Warranty Extension (Warranty+) not available on products   
					I have purchased a warranty extension (Warranty+)   
					Reference: _____________________ Contract Number: _________________   
					Thank you from all of us at MGE.   
					MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA   
					Tel: 714-557-1636   
					Fax: 714-557-9788   
					41-000154-53 Rev B00 9/2003   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				MGE Customer Care Center   
					Technical Support and Product Services   
					Technical questions? If you encounter a problem while following the instructions in this manual, or have   
					questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS   
					? 
					SYSTEMS, INC. Customer Care Center or visit our web site www.mgeups.com for complete service information.   
					To insure that your questions are correctly answered, please obtain the part number, assembly number, and serial   
					number of the unit and include them in any discussions or correspondence.   
					Part Number:   
					_____________________________________________________________________   
					Assembly Number: _____________________________________________________________________   
					Serial number:   
					_____________________________________________________________________   
					Who To Contact   
					Customer Care Center:   
					Field Service Engineer:   
					1-800-523-0142, extension 1113 (USA and Canada Only)   
					1-800-438-7373 (USA and Canada Only)   
					Customer FAQ   
					or International calls:   
					1-714-557-1636 (Ask for Technical Support Group, TSG)   
					Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that will   
					provide responses to any questions that you might have.   
					Scheduling Field Service Engineer Support   
					Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are   
					required on-site. If the startup of the UPS is critical to maintaining your schedule, please call the MGE   
					toll free telephone number at 1-800-438-7373, to insure a safe installation and startup that will maintain   
					the MGE warranty and insure smooth performance   
					Return Policy for Repair (RMA)   
					Should you require factory service for your equipment, contact MGE’s Customer Support Services and obtain a Return   
					Materials Authorization (RMA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RMA.   
					Date:   
					______________________________________________________   
					RMA Number: ______________________________________________________   
					Contact Name: ______________________________________________________   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					(This page left blank intentionally)   
					86-86000-00 A01   
					W—4   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Glossary   
					Term used   
					Definition / Meaning   
					@ 
					/ 
					At.   
					And/or.   
					+/-   
					Plus or Minus.   
					≤ 
					Equal to or less than.   
					Number.   
					# 
					°C   
					Degree Celsius.   
					°F   
					Degree Fahrenheit.   
					Ø 
					Phase angle.   
					Ω 
					Ohm; unit of resistance.   
					Trade Mark.   
					® 
					2nd   
					Second.   
					AC or ac   
					Ambient Temp.   
					Ambient noise   
					ANSI   
					Alternating current, also implies root-mean-square (rms).   
					Temperature of surrounding air.   
					Acoustical noise of surrounding environment.   
					American National Standard Institute.   
					American Wire Gauge.   
					AWG   
					Breaker   
					BTU or Btu   
					Electrical circuit interrupter.   
					British thermal unit. Defined as the amount of heat required to raise the tempera-   
					ture of one pound of water by 1°F.   
					BYPASS   
					See “Static Transfer switch”.   
					BYPASS mode   
					See “off-line mode”.   
					Carrier   
					C 
					The company or individual responsible for delivering goods from one location to another.   
					Common.   
					CB   
					Circuit breaker.   
					cm   
					Centimeter.   
					dB   
					Decibels.   
					DC   
					Direct current.   
					Conduit   
					A flexible or rigid tube enclosing electrical conductors.   
					C.S.S.   
					Customer Support Service.   
					86-86000-00 A01   
					Glossary   
					G — 1   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					Current rating   
					dBA   
					The maximum current that a conductor or equipment can carry reliably without damage.   
					Decibel Adjusted.   
					dBrnC   
					Decibel above reference noise.   
					DC or dc   
					Direct current, or voltage.   
					Digital Meter   
					Earth ground   
					ECO Mode   
					The LCD display on the front panel of inverter system.   
					A ground circuit that has contact with the earth.   
					Operating mode by which the load is supplied directly by the AC source if it is within the   
					tolerances defined by the user. This mode reduces the consumption of electrical power.   
					Electrician   
					Refers to an installation electrician qualified to install heavy-duty electrical components in   
					accordance with local codes and regulations. Not necessarily qualified to maintain or repair   
					electrical or electronic equipment.   
					FET   
					Field effect transistor.   
					Frequency.   
					Freq.   
					Frequency slew rate   
					The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).   
					Ground (safety).   
					GND   
					Hz   
					Hertz, frequency measurement unit, 1Hz is one cycle per second.   
					See “on-line” mode.   
					Inverter mode   
					I 
					Current.   
					IEC   
					International Electrotechnical Commission.   
					IEEE   
					Institute of Electrical and Electronic Engineers.   
					The input circuit from the building power panel to the equipment.   
					An electrical circuit that generates an AC voltage source from a DC voltage source.   
					Input branch circuit   
					Inverter   
					IGBT   
					I/O   
					Insulated gate bipolar transistors.   
					Input/Output.   
					I/T or IT   
					Information Technology.   
					KiloVolt-Ampere; is equal to 1000 Volt-Ampere.   
					Line.   
					kVA   
					L 
					LCD   
					Liquid-Crystal Display unit.   
					Light Emitting Diode.   
					Main AC input source.   
					Bypass AC input source.   
					Milliampere.   
					LED   
					Mains or Mains 1   
					Mains 2   
					mA   
					MAX.   
					Maximum.   
					MCM   
					Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in   
					diameter. M is from Roman numerical system indicating 1000.   
					Module   
					N 
					Refers to individual power inverter module.   
					Neutral.   
					G — 2   
					Glossary   
					86-86000-00 A01   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Installation and User Manual   
					NC   
					Normally closed.   
					NO   
					Normally open.   
					NEC   
					National Electrical Code.   
					National Fire Protection Association.   
					Part number.   
					NFPA   
					PN   
					On-line mode   
					Off-line mode   
					Inverter output power is the primary energy source to load.   
					Inverter output is off, and the load connected at the inverter output receives power   
					from utility line via a static transfer switch or maintenance bypass relay.   
					OSHA   
					Occupational Safety and Health Agency.   
					PCA   
					PCB   
					PWM   
					SCR   
					Printed circuit assembly.   
					Printed circuit board.   
					Pulse Width Modulation.   
					Silicon controlled rectifier.   
					Shipping damage   
					SPDT   
					Any damage done to an article while it is in transit.   
					Single Pole Double Throw.   
					Static Transfer   
					An solid state switching mechanism electronically controlled to pass AC power   
					directly from the utility to an output load.   
					Technician   
					Refers to an electronic technician qualified to maintain and repair electronic   
					equipment. Not necessarily qualified to install electrical wiring.   
					Test connector   
					DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer   
					Support Service technician to access programmable and diagnostic features of the   
					system.   
					V 
					Volts   
					VA   
					VA   
					Volt amperes   
					Volt-amps, unit for apparent power measurement, equal V x I.   
					VAC or Vac   
					VDC or Vdc   
					Voltage of AC type.   
					Voltage of DC type.   
					ve   
					Battery voltage.   
					By way of.   
					Via   
					86-86000-00 A01   
					Glossary   
					G — 3   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				EX 5/7/11 RT System   
					(This page left blank intentionally)   
					86-86000-00 A01   
					G — 4   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Reorder Form   
					1660 Scenic Avenue   
					Costa Mesa, CA 92626   
					Use this form to report any errors, omissions, or other problems you have experienced, or to order   
					additional hardcopies of this document. A free copy of this document may be downloaded from the   
					proprietary MGE Rep Web site. Please contact your MGE UPS SYSTEMS,INC. Representative for assistance.   
					NAME _____________________________________________________________________________________   
					COMPANY ___________________________________________________________________________________   
					STREET ADDRESS ____________________________________________________________________________   
					CITY ________________________________________ STATE __________________ ZIP ___________________   
					I would like to order______ (quantity @ $75.00 each) additional copies of the:   
					EX 5/7/11 RT System   
					Installation and User Manual   
					86-86000-00 A01   
					I would like to report the following problems with this document:   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				Download from Www.Somanuals.com. All Manuals Search And Download.   
				w w w . m g e u p s . c o m   
					Contact MGE   
					United States   
					MGE UPS SYSTEMS   
					1660 Scenic Ave.   
					Costa Mesa, CA 92626   
					Tel: (714) 557-1636   
					(800) 523-0142   
					Fax: (714) 557-9788   
					email: [email protected]   
					www: mgeups.com   
					Canada   
					MGE UPS SYSTEMS   
					#9, 2789 Thamesgate Drive   
					Mississauga, ON L4T 4E8   
					Tel: (905) 672-0990   
					(877) 672-0990   
					Fax: (905) 672-7667   
					email: [email protected]   
					www: mgeups.com   
					Latin America and   
					Other International   
					MGE UPS SYSTEMS   
					1660 Scenic Ave.   
					Costa Mesa, CA 92626   
					Tel: (714) 513-7831   
					(800) 523-0142 ext. 7831   
					Fax: (714) 434-0199   
					email: [email protected]   
					www: mgeups.com   
					1660 Scenic Avenue, Costa Mesa, California 92626 • (714) 557-1636   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |