Liebert Power Supply PSITM User Manual

POWER AVAILABILITY  
USER MANUAL  
PowerSure PSI™  
1000 - 3000VA  
230V  
Version française, : reportez-vous au CD du guide d'utilisateur Liebert.  
Para español, consulte el CD del Manual del Usuario de Liebert.  
Die deutsche Fassung finden Sie auf der CD des Liebert-Benutzerhandbuchs.  
Per l'Italiano, consultare il CD contenente il Manuale dell'utente Liebert.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
8.5  
i
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIGURES  
Figure 1  
TABLES  
Table 1  
ii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS  
This manual contains important safety instructions that should be followed during the installation  
and maintenance of the UPS and batteries. Please read this manual thoroughly before attempting to  
install or operate this UPS.  
WARNING  
!
SAFETY PRECAUTIONS  
To prevent the risk of fire or electric shock, install the UPS in a temperature and humidity  
controlled room, free of conductive contaminants, moisture, flammable liquids, gases and  
corrosive substances.  
Operate the UPS only from a properly grounded (earthed) 220-240 VAC, 50Hz or 60Hz AC  
supply.  
To reduce the risk of electric shock, do not remove the cover—it has no user-serviceable parts  
inside except the internal battery pack. Some components are live, even when AC power is  
disconnected. For internal battery pack servicing, follow the instructions provided in 10.3 -  
Battery Replacement. For other service, contact a qualified technician.  
WARNING  
!
ELECTRICAL PRECAUTIONS  
• This UPS should not be supplied from electrical power systems of the IT (Impedance á  
Terre) type (IEC 364 - Electrical Installation of Buildings).  
• The UPS must be earthed/grounded at all times during operation. Connect only to a mains  
supply socket outlet with an earth/ground connection.  
CAUTION  
!
Although your UPS has been designed and manufactured to ensure personal safety, improper  
use can result in electrical shock or fire. To ensure safety, please observe the following rules:  
• Turn Off and unplug your UPS before cleaning. Do not use liquid or aerosol cleaners. A dry  
cloth is recommended to remove dust from the surface of your UPS.  
• Do not install or operate your UPS in or near water.  
• Do not place UPS on an unstable cart, stand or table.  
• Do not place UPS under direct sunlight or close to heat emitting sources.  
• Never block or insert any objects into the ventilation holes or other openings of the UPS.  
Keep all vents free of dust accumulation that could restrict air flow.  
• Do not place UPS power cord in any area where it may get damaged by heavy objects.  
WARNING  
!
If your UPS demonstrates any of the following conditions, turn Off and unplug your UPS from  
the outlet and contact your local dealer, Liebert representative or Liebert Worldwide Support  
Group:  
• The power cord or plug is damaged.  
• Liquid has been spilled on the UPS.  
• The circuit protector trips frequently.  
• The UPS does not operate in accordance with the user manual.  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
CONDITIONS OF USE: The mains supply socket must be within 2m (6.5 ft.) of the UPS and be eas-  
ily accessible.  
Your UPS provides conditioned power to connected equipment. This product is designed for Commer-  
cial use only. It is not intended for use with life support and other designated “critical” devices. Maxi-  
mum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer,  
Liebert representative or the Liebert Worldwide Support Group.  
The PSI 1000 VA, and 1440 VA models are not supplied with an input power cable for connection to  
the mains supply socket. Use the input mains supply power cable from your data processing equip-  
ment to connect the UPS to the mains supply.  
For the 2200 VA and 3000VA models, use the supplied 16A-rated input mains supply cables. For UK  
supply systems, consult a qualified electrician to connect the lead supplied for the 2200 VA and  
3000VA models to the mains supply.  
CAUTION  
!
The UPS and connected load total earth leakage current must not exceed 3.5mA. If the  
connected load earth leakage current is likely to exceed 2.5mA or you are unsure, then convert  
the input cable attachment to either a fixed wiring installation or an industrial plug/socket  
(e.g., CEE 17 connector). This alteration should be carried out by a competent electrical  
engineer who is conversant with local electrical codes and regulations.  
When installing the UPS or making input and output connections, comply with relevant safety codes  
and standards (e.g. IEC60950, VDE0805, EN62040-1).  
Placing magnetic storage media on top of the UPS may result in data corruption.  
The equipment can be installed and operated by individuals without previous training.  
CAUTION  
!
DO NOT CONNECT equipment that could overload the UPS or demand half-wave  
rectification from the UPS, for example: electric drills, vacuum cleaners, laserjet/inkjet  
printers, hair dryers, overhead projectors.  
CAUTION  
!
Servicing of batteries should be performed or supervised by personnel knowledgeable of  
batteries and required precautions. Keep unauthorized personnel away from the batteries.  
A battery can present a risk of electrical shock and high short-circuit current. The following  
precautions should be observed when working on batteries:  
• Remove watches, rings, and other metal objects.  
• Use tools with insulated handles.  
• Do not dispose battery or batteries in a fire. The battery may explode.  
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and  
eyes. It is toxic.  
• When replacing the battery, use same number and type of battery as the suitable recom-  
mended type of battery listed in Table 3.  
• Handle, transport and recycle batteries in accordance with local regulations.  
Electromagnetic Compatibility—The PowerSure™ PSI series complies with the requirements of  
the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires  
installation in accordance with these instructions and use of Liebert-approved accessories only.  
Environmental-Operate the UPS in an indoor environment only in an ambient temperature range of  
0°C to 40°C (32°F to 104°F). Install in a clean environment, free from conductive contaminants, mois-  
ture, flammable liquids, gases, or corrosive substances.  
Provided are a Liebert MultiLink cable and a USB cable for connection to a computer. Do not use the  
Liebert MultiLink cable for other applications. Store in a safe place if not required at this time.  
When using the communication features on this UPS, ensure the cabling connected to the DB-9 or  
UPS communications ports are kept separated from the power leads to the UPS input and output.  
2
Download from Www.Somanuals.com. All Manuals Search And Download.  
Glossary of Symbols.  
1.0 GLOSSARY OF SYMBOLS.  
Risk of electrical shock  
Indicates caution followed by important instructions  
Requests the user to consult the manual  
i
Indicates the unit contains a valve-regulated lead acid battery  
Recycle  
DC voltage  
Equipment grounding conductor  
Bonded to ground  
AC voltage  
ON/Alarm Silence/Battery Test  
OFF  
Voltage Programming Button  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Introduction  
2.0 INTRODUCTION  
Congratulations on your choice of the Liebert PowerSure™ PSI Uninterruptible Power Supply (UPS).  
It provides conditioned power to microcomputers and other sensitive electronic equipment.  
Upon generation, AC power is clean and stable. However, during transmission it may be subject to  
voltage sags, spikes, or complete power failure which may interrupt computer operations, cause data  
loss, or even damage equipment. The PowerSure PSI protects equipment from these disturbances.  
The PowerSure PSI comes in nominal power ratings of 1000, 1440, 2200, or 3000 VA. Refer to 12.0 -  
Specifications for details.  
The PowerSure PSI is a 2U, line-interactive UPS that may be installed in a rack or used in a tower  
configuration. A line-interactive UPS continuously conditions and regulates its output voltage,  
whether mains power is present or not. It supplies connected equipment with clean, sinewave power  
to simulate the power generated by the mains. Sensitive electronic equipment operates best from  
sinewave power.  
For ease of use, the PowerSure PSI contains Status Indicators to display Load Level, Battery Level,  
Buck/Boost, Over Temperature and Battery. It also provides self-diagnostic tests, a combination ON/  
Alarm Silence/Battery Test button, an OFF button and Voltage Programming button.  
The PowerSure PSI has USB, DB-9 (RS232/contact closure) and Intellislot interface ports for commu-  
nications between the UPS and a LAN server or other computer systems. The DB-9 port provides  
detailed operating information including voltages, currents, and alarm status to the host system  
when used in conjunction with Liebert’s MultiLinksoftware. MultiLink software can also remotely  
control UPS operation. The USB port provides detailed operating information and alarm status to the  
host system when used in conjunction with the Liebert Human Interface Device (HID) and Microsoft  
Power Manager software.  
Figure 1 Front view of UPS  
Fault  
Indicator  
OFF Button  
Load Level  
Indicators  
ON/Alarm Silence/  
Battery Test Button  
Battery Level  
Indicators  
Voltage  
Programming  
Button  
UPS Status  
Indicators  
UPS Display  
(bezel removed)  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Introduction  
Figure 2 1000 and 1440VA PSI—rear view  
Output  
Receptacles  
Data Line  
Connectors  
Circuit Breaker  
Intellislot Port  
REPO  
INPUT  
IN  
OUT  
BREAKER  
PUSH TO RESET  
1
2
3
4
LOAD 1  
BATTERY  
PHONE / FAX / MODEM / NETWORK  
PROTECTION  
CONNECTOR  
1440VA/DC 48V/30A  
1000VA/DC 48V/20A  
+
-
INPUT  
LOAD 2  
INTELLISLOT  
External Battery  
Cabinet Connector  
AC Input  
USB Port  
RS232 (DB-9)  
Port  
Figure 3 2200 and 3000VA PSI—rear view  
Output Circuit  
Breaker 1  
Data Line  
Connectors  
Intellislot  
Port  
Output  
Receptacles  
Input Circuit  
Breaker  
REPO  
PHONE / FAX /  
MODEM / NETWORK  
PROTECTION  
LOAD 1  
BREAKER  
BATTERY  
CONNECTOR  
1
2
2200V/A/DC 72V30A  
3000V/A/DC 72V40A  
3
4
10A/260VAC  
IN  
OUT  
REPO  
LOAD 2  
BREAKER  
INTELLISLOT  
INPUT  
+
-
RS-232  
INPUT  
BREAKER  
PUSH TO  
RESET  
LOAD 3  
Output  
Receptacle  
AC Input  
USB  
Output Circuit  
Breaker 2  
External Battery  
Cabinet Connector  
Port  
RS232 (DB-9)  
Port  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Major Components  
3.0 MAJOR COMPONENTS  
Figure 4 Line diagram of PowerSure PSI 1000VA & 1440VA  
Input  
Output  
EMI/RFI  
Relay  
Filter  
AVR  
Transformer  
Charger  
Battery  
Inverter  
G
G
Figure 5 Line diagram of PowerSure PSI 2200VA & 3000VA  
Input  
Output  
EMI/RFI  
Relay  
AVR  
Transformer  
Filter  
DC-to-DC  
Converter  
Bi-Directional  
Converter  
Charger  
Battery  
G
3.1  
3.2  
G
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters  
These UPS components provide surge protection and filter both electromagnetic interference (EMI)  
and radio frequency interference (RFI). They minimize surges or interference present in the mains  
line and keep the sensitive equipment protected.  
Relay  
In Normal mode the Relay passes mains AC power to the connected load. When input mains voltage  
or frequency is outside acceptable limits, the Relay activates and transfers the UPS to battery.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Major Components  
3.3  
Automatic Voltage Regulator  
The Automatic Voltage Regulator (AVR) protects connected equipment from power spikes, sags and  
other abnormalities by raising (boosting) or lowering (bucking) the output voltage as needed. This  
keeps the UPS output voltage within the connected equipment’s tolerance and accommodates wide  
mains voltage fluctuations without utilizing the batteries.  
3.4  
3.5  
Battery Charger  
In Normal mode, the Battery Charger converts mains AC power into regulated DC power to float  
charge the battery. It is continuously charging the battery whenever the UPS is plugged into a power  
outlet and mains power is within acceptable limits - even if the UPS is turned Off.  
Battery  
The PowerSure PSI utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery  
design life, operate the UPS in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional  
external battery cabinets are available to extend battery run times.  
3.6  
3.7  
Inverter—1000/1440 Models Only  
In battery mode operation, the inverter utilizes the DC output of the battery and inverts it into pre-  
cise, regulated, sinewave AC power.  
DC-to-DC Converter—2200/3000 Models Only  
The DC-to-DC Converter utilizes energy from the battery system and raises the DC voltage to the  
optimum operating voltage for the Bi-Directional Converter. This allows the Bi-Directional Converter  
to operate continuously at its optimum efficiency and voltage, thus increasing reliability.  
3.8  
Bi-Directional Converter—2200/3000 Models Only  
In normal operation, the Bi-Directional Converter changes mains AC power into regulated DC power  
to “float charge” the battery system. This converter is continuously charging the battery whenever the  
UPS is plugged into a power outlet and mains power is within acceptable limits—even if the UPS is  
turned Off. When mains power fails, the Bi-Directional Converter draws energy from the battery  
through the DC-to-DC Converter and inverts it into a regulated sinewave supplying power to con-  
nected equipment.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
What’s Included  
4.0 WHATS INCLUDED  
The PowerSure PSI is shipped with the following items:  
• PowerSure PSI user manual  
• MultiLink software CD  
• MultiLink serial cable, 3m (10 ft)  
• USB cable, 1.8m (6 ft)  
• RJ-11 cord, 2.1m (7 ft)  
• Rack mount handles  
• Support base  
• Fixed rails  
• Mounting hardware (screws/washers)  
• Front bezel  
• Vertical display overlay  
• Two (2) 10A output power cords, 2.0m (6.6 ft.)  
• Input power cords, 2200 and 3000 VA models only  
MultiLink  
serial cable  
3m (10 ft)  
Vertical  
display  
overlay  
MultiLink  
software CD  
USB cable  
1.8m (6 ft)  
RJ-11 cord  
2.1m (7 ft)  
Rack mount  
handles  
Mounting hardware  
(screws & washers)  
Fixed rails  
Support base  
Front bezel  
10A output  
power cords,  
2.0m (6.6 ft.)  
Input power cords,  
2200 & 3000 VA models only;  
one cord with 230 model;  
two cords with 230E model  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
5.0 INSTALLATION  
5.1 Preparation  
1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer  
or Liebert representative.  
CAUTION  
!
The UPS is heavy (see Table 4 - Battery cabinet specifications). Take proper precautions  
when lifting or moving it.  
2. Decide where to place the PowerSure PSI. Install the UPS indoors in a controlled environment  
where it cannot be accidentally turned Off. Place it in an area of unrestricted airflow around the  
unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants.  
Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an  
ambient temperature range of 0°C to 40°C (32°F to 104°F).  
NOTE  
UPS operation in temperatures above 25°C (77°F) reduces battery life.  
3. The PowerSure PSI may be installed in either a tower configuration or in a rack, depending on  
available space and use considerations. Determine the type of installation and follow the  
appropriate instructions in either Tower UPS Installation or Rack-Mount UPS Conversion  
and Installation.  
5.2  
Tower UPS Installation  
When using the PowerSure PSI in a tower configuration, use the included support base (shown below,  
left) to stabilize the UPS. If two or more battery cabinets are added, the spacers—included with the  
battery cabinets—should be used to accommodate the additional cabinets.  
Figure 6 Support base for tower configuration  
Tower Stand - Fully Extended  
Spacers Can be Added to Accommodate External Battery Cabinets  
Connectors Snap into Slots on Base  
1. To orient the display for vertical viewing, remove the front plastic bezel by pulling forward evenly  
on both sides.  
2. Peel the backing from the vertical display overlay and apply to the existing display.  
3. Snap the front bezel back into place.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
5.3  
Rack-Mount UPS Conversion and Installation  
NOTE  
When rack mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails  
on each side. The rack mount handles WILL NOT support the weight of the UPS. They are  
used to move the UPS into and out of the rack.  
1. For fixed rail installations, install the rack mount handles using four (4) M4x6 screws (see  
Figure 7 Rack mount handles  
Two (2) M4x6  
Flat Head Screws  
Two (2) M4x6  
Flat Head Screws  
M4x6 Flat Screw  
Rack Mount Handles  
2. Unpack the two fixed rail assemblies and mounting hardware. Loosen the wing nuts and extend  
the inner members to their outermost position (see Figure 8).  
Figure 8 Fixed rails with inner members extended  
Wing Nuts for  
Adjustment  
Adjustable Slide  
Assembly  
Adjustable Length  
Maximum 800 mm  
Minimum 485 mm  
CAUTION  
!
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the  
lowest possible rack position.  
3. Determine the height position inside the rack enclosure where you want to mount the UPS or  
battery cabinet. Make sure fixed rails are at the same mounting height on each of the four (4) rack  
mounting rails.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Installation  
4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the  
inside of the rack mounting rails.  
5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front  
of the fixed rail assembly (see Figure 9).  
6. Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail.  
7. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes on the rear of the fixed  
rail assembly.  
8. Check alignment of fixed rails and tighten all screws to ensure locking action.  
Figure 9 Rack mounting rails and slide assemblies  
B
B
A
A
A - Washer  
B - M5x12 Flat Screw  
A
A
B
B
9. Lay the UPS in rack-mounting position on the fixed rails. The UPS should move smoothly forward  
and backward on the fixed rails. If not, recheck alignment.  
CAUTION  
!
Lifting equipment into rack may be a two-person job, depending on weight of equipment.  
10. Use the extra M5 screws provided, secure front of the UPS to rack mounting rails to prevent the  
UPS from sliding out of position.  
11. PowerSure PSI 230 VAC models are not supplied with an input power lead for connection to the  
mains supply. Additional input/output cords may be obtained from your dealer. The input power  
2
cord must have a minimal cross-sectional area of 1mm .  
12. Shut down the load equipment and turn off the mains  
supply. Unplug the load equipment's power input  
cable from the mains supply socket and plug it into the  
UPS input socket.  
Vertical  
overlay  
for tower  
UPS  
Plug the power input cable into the mains supply  
socket. Connect the supplied IEC-320-C14 output  
power cable between the load equipment input socket  
and one of the UPS AC output sockets.  
13. Connect all load equipment to the UPS in this  
manner.  
14. Turn On the UPS by pressing the ON button. Check  
that the AC Input Indicator is not flashing. If it is  
flashing, refer to 11.0 - Troubleshooting. Then turn  
Horizontal  
overlay for  
rack UPS  
On the connected equipment. The UPS is now providing conditioned power to your equipment.  
CAUTION  
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should  
be segregated and run separately from power cables.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Installation  
15. Connect Phone/Fax/DSL/Network/Modem devices to data line connectors.  
RJ11/RJ45  
connection  
INPUT  
IN  
OUT  
BREAKER  
PUSH TO RESET  
1
2
3
4
LOAD  
1
BATTERY  
PHONE  
/
FAX MODEM NETWORK  
/
/
CONNECTOR  
PROTECTION  
1440VA/DC 48V/30A  
1000VA/DC 48V/20A  
INPUT  
+
-
LOAD  
2
INTELLISLOT  
16. Communication options (see 8.0 - Communications for details):  
Option 1 - Serial Communications  
Serial communications provides parametric data, for example, input voltage and battery voltage.  
a. Connect MultiLink serial cable included with the UPS to communications port.  
b. Install the MultiLink software. The software and installation instructions, as well as the user  
manual, are on the CD included in the PowerSure PSI package.  
Option 2 - Contact Closure Communications  
Contact Closure communications provides on-battery and low-battery signals for orderly shut-  
down.  
a. Refer to the MultiLink user manual for instructions on making your own contact closure  
cable.  
b. Install the MultiLink software. The software and installation instructions, as well as the user  
manual, are on the CD included in the PowerSure PSI package.  
Option 3 - USB Communications  
a. Connect USB cable provided with the UPS to the PSI’s USB port and the USB port on your  
computer. The PSI will work automatically with your built-in power management software on  
Windows XP and 2000 and Mac OS 10.2 or later (see 8.3 - USB Interface Port for details).  
Option 4 – Intellislot  
The UPS contains one communication slot, called “Intellislot™,” to allow the operator to field  
install optional communication cards. These optional cards allow the UPS to communicate via  
either OpenComms Web Card (OCWEBCARD), connected directly to the LAN; or Intellislot Relay  
Interface card (RELAYCARD-INT) communication card. Once the OCWEBCARD is installed, the  
Serial communication via the RS232 is disabled. The USB, Intellislot, and Contact Closure com-  
munications operate in parallel.  
17. REPO Switch—The PowerSure PSI is equipped with a Remote Emergency Power Off (REPO)  
switch.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the  
UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to  
comply with national and local wiring codes and regulations.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
Figure 10 REPO switch connections  
REPO Connector  
REPO Switch  
as shipped  
REPO connections  
for normally open  
switch system  
REPO connections  
for normally closed  
switch system (fail-safe)  
1
2
3
4
1
2
3
4
1
2
3
4
Key to REPO switch connections  
1. 24 VDC,  
2. Sense  
3. Sense  
4. Ground  
5.4  
External Battery Cabinet Installation  
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery  
run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked  
beneath the UPS. The run time is limited to a maximum of four (4) hours.  
CAUTION  
!
The external battery cabinet(s) are heavy (see 12.0 - Specifications). External battery  
cabinets can be used in rack-mount or tower configuration. Take proper precautions when  
lifting them.  
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier  
and your local dealer or Liebert representative.  
2. The rack-mount handles are shipped with the external battery cabinet and may be installed at  
3. Fixed rails and securing hardware ship with the external battery cabinet. Fasten the fixed rails  
into position with the screws per the instructions included with the UPS. Repeat  
4. Use the support bases included with the UPS for the tower option to prevent tip-over. One  
additional set of support base spacers ships with each external battery cabinet.  
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,  
then to the rear of the UPS, as shown at right.  
6. The UPS is now equipped with additional backup battery run time. For approximate battery run  
times, refer to Table 5 - Battery run times.  
BATTERY  
CONNECTOR  
BATTERY  
C
INPUT  
BREAKER  
PUSHTO RESET  
OUT  
IN  
1
2
3
4
BATTERY  
LOAD  
1
CONNECTOR  
1440VA/DC 48V/30A  
1000VA/DC 48V/20A  
PHONE  
/
FAX  
/
MODEM  
/
NETWORK  
PROTECTION  
+
-
INPUT  
LOAD 2  
INTELLISLOT  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Controls and Indicators  
6.0 CONTROLS AND INDICATORS  
All indicators illuminated  
for illustrative purposes only.  
6.1  
ON/Alarm Silence/Battery Test Button  
This button controls output power to connected load(s) and has three functions:  
• On  
• Alarm Silence  
• Battery Test  
ON—When the UPS is Off, pressing the ON/Alarm Silence/Battery Test button for more than one  
(1) second will start the UPS, and an audible alarm sounds briefly. The UPS is capable of starting on  
battery (battery start).  
Alarm Silence—When a UPS audible alarm is active, pressing and releasing the ON/Alarm Silence/  
Battery Test button will silence the active audible alarm, whether mains power is present or not.  
Once the alarm silence function has been activated, all active audible alarms will remain silenced  
until a new alarm condition is detected.  
NOTE  
The LOW BATTERY, OVER TEMP and OVERLOAD warning  
audible alarms CANNOT be silenced.  
Battery Test—To initiate a manual battery test, press the ON/Alarm Silence/Battery Test button for  
at least one second while operating from mains power with no alarm conditions present.  
• If all five (5) Battery indicators are not illuminated, allow the UPS to recharge the batteries for  
24 hours.  
• After 24 hours, retest the batteries.  
• After the batteries have been retested, if all five (5) Battery indicators are not illuminated, con-  
tact your local dealer, Liebert representative or Liebert Worldwide Support Group.  
6.2  
OFF Button  
When the UPS is on (in either Normal or Battery mode), pressing the OFF button for more  
than one (1) second will shut down the UPS. An audible alarm sounds briefly.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Controls and Indicators  
6.3  
6.4  
Voltage Programming Button  
The PowerSure PSI contains a Voltage Programming button that allows the operator to select  
the nominal mains voltage. This setting changes the mains transfer points (low and high) of  
the UPS and the nominal output voltage when operating in Battery mode. The operator can  
select between 220, 230 and 240VAC output. The factory-default setting is 230VAC.  
The Voltage Programming button is a push button type and is behind the plastic bezel on  
the front panel of the UPS. To access the button, the front bezel must be removed.  
Load Level Indicators—4 green, 1 amber  
The Load Level Indicators display the approximate electrical load placed upon the UPS.  
The UPS Load Level Indicators are displayed in 25% increments as shown in Figure 11.  
Figure 11 Load level indicators—4 green, 1 amber  
Upon detection of an output overload condition, the amber overload (>100%) indicator flashes and an  
audible alarm activates. If the UPS shuts down due to an overload condition, the amber overload  
(>100%) indicator illuminates (see 11.0 - Troubleshooting for details).  
6.5  
Battery Level Indicators—5 green  
The Battery Level Indicators display the approximate battery capacity.  
The approximate battery capacity is displayed when the UPS is operating in Normal, Buck/Boost, or  
Battery mode.  
The Battery Level Indicators are displayed in 20% increments as shown in Figure 12:  
Figure 12 Battery level indicators—5 green  
The PowerSure PSI is equipped with automatic and remote battery test features. The automatic test  
occurs every 14 days if mains has not been interrupted; this option may be configured by the user.  
Should the battery fail this test, the amber Battery Indicator will be illuminated and an alarm will  
sound (see 11.0 - Troubleshooting for details).  
The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery  
test.  
6.6  
6.7  
AC Input Indicator—Green  
The AC Input Indicator illuminates when mains power is available and within the input specifica-  
tions.  
Buck/Boost Indicator—Green  
The Buck/Boost Indicator illuminates when the UPS is operating in Boost mode to compensate for a  
low mains voltage condition. This indicator flashes when the UPS is operating in Buck mode to com-  
pensate for a high mains voltage condition (see 11.0 - Troubleshooting for details).  
6.8  
Battery Indicator—Green/Amber  
The Battery Indicator illuminates green when the UPS is operating on battery and flashes green  
when a low battery condition occurs. The Battery Indicator illuminates amber when a bad battery is  
detected, indicating that the batteries need to be replaced (see 11.0 - Troubleshooting for details).  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
               
Controls and Indicators  
6.9  
Over Temp Indicator—Amber  
The Over Temp Indicator flashes when the UPS detects an over temperature condition. This indicator  
illuminates when the UPS shuts down due to an over temperature condition (see 11.0 - Trouble-  
shooting for details).  
6.10 Fault Indicator—Red  
The Fault Indicator illuminates when the UPS detects an internal problem (see 11.0 - Trou-  
bleshooting for details).  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Modes of Operation  
7.0 MODES OF OPERATION  
7.1 Normal Mode  
During Normal mode operation, the PowerSure PSI supplies conditioned, computer-grade power to  
the connected equipment: mains power passes through the TVSS circuitry and the EMI/RFI filters  
and then through the Inverter (1000VA & 1440VA) / Bi-Directional Converter (2200VA & 3000VA) to  
connected equipment.  
When the UPS is in Normal mode, the AC Input Indicator illuminates green. The UPS display in  
Figure 13 shows the UPS operating in Normal mode with 26% - 50% load connected to the output.  
Figure 13 Normal mode operation with 26-50% load  
Mains power present ...  
... and within operational limits  
The PowerSure PSI continuously monitors the batteries to maintain them in a fully charged state.  
The battery charger operates whenever AC power is present, even if the UPS is switched Off. By  
default, the UPS is set to perform an automatic battery test after it has been operating continuously  
for two (2) weeks. The automatic battery test can be disabled via MultiLink.  
7.2  
Buck/Boost Mode  
The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in mains power, such  
as voltage surges and sags. When the PowerSure PSI detects an abnormality, it raises the undervolt-  
age (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and main-  
tains the output voltage to the connected critical equipment, without utilizing the batteries.  
The Buck/Boost Indicator flashes green when the UPS is operating in Buck mode and illuminates  
green when the UPS is operating in Boost mode (see 11.0 - Troubleshooting for details).  
Figure 14 Buck/Boost mode operation with 51-75% load and 21-40% battery capacity  
Indicator shows  
UPS in Boost Mode  
(solid green)  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Modes of Operation  
7.3  
Battery Mode  
The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or  
complete mains failure. The battery system supplies power through the Inverter (1000VA & 1440VA)  
or through the DC-to-DC converter to the Bi-Directional Converter (2200VA & 3000VA) to generate  
power for the connected equipment.  
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds  
every 10 seconds. As capacity decreases, fewer indicators remain illuminated. Figure 15 shows the  
UPS in Battery mode with 61% - 80% battery capacity remaining.  
Figure 15 Battery mode at 61 – 80% battery capacity  
Battery Indicator  
illuminated  
When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every  
half-second. The default low battery warning is two (2) minutes but can be configured via MultiLink.  
For more information, refer to 11.0 - Troubleshooting.  
Figure 16 Low Battery mode  
Battery Indicator  
flashes green  
For approximate battery run times, refer to Table 5 - Battery run times. These run times are  
approximates based on resistive load and an ambient temperature of 25°C (77°F). To increase this  
time, turn Off non-essential pieces of equipment, such as idle computers and monitors, or add exter-  
nal battery cabinets.  
CAUTION  
!
Turning Off the UPS while it is in battery mode will result in loss of output power.  
7.4  
Battery Recharge Operation  
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger  
begins recharging.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Communications  
8.0 COMMUNICATIONS  
8.1 DB-9 Connector  
The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a  
computer system running MultiLink software. The DB-9 is capable of supplying serial communica-  
tion, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and shutdown soft-  
ware, is shipped with the UPS, along with a 3m (10 ft) DB-9 cable required for running MultiLink.  
When MultiLink is installed on the host computer, the UPS can signal “on battery” and “low battery”  
using opto-couplers. When the UPS is operating in Battery mode, it can receive a signal from the host  
computer system that will shut down the UPS (after gracefully shutting down the operating system  
on the host computer system) when the remaining battery run time is low. The timing of the signal  
depends on MultiLink’s configuration settings. This shutdown signal (5-12VDC) must have a dura-  
tion of at least 2 seconds for the UPS to be shut down. The UPS communicates via serial communica-  
tions using Liebert ESP II protocol.  
Table 1  
DB-9 pin assignment  
DB-9 Pin Assignment Description  
1
2
3
4
5
6
7
8
9
Low Battery (open collector)  
UPS TxD  
UPS RxD  
Battery Mode Shutdown (5-12V)  
Common  
Any Mode Shutdown (short to pin 5)  
Low Battery (open emitter)  
Mains Fail (open emitter)  
Mains Fail (open collector)  
Pin Assignment  
Collector to Emitter*  
Open  
Collector  
6
7
8
9
(+)  
330 Ohms  
Open  
Emitter  
(-)  
1
2
3
4
5
8.2  
Remote Shutdown Via the DB-9 Connector  
The PowerSure PSI can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the  
DB-9 connector.  
8.2.1 Any Mode Shutdown—Via Pins 5 & 6  
When Pin 6 is shorted to Pin 5, the UPS output is shut Off regardless of what mode the UPS is oper-  
ating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the  
UPS output can be enabled by pressing the ON/Alarm Silence/Battery Test button.  
8.2.2 Battery Mode Shutdown—Via Pins 4 & 5  
While the UPS is operating on battery (with no battery test in progress), a 5-12VDC signal for 2 sec-  
onds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.  
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer inside the UPS begins a count-  
down. The timer cannot be stopped. If mains power returns during the 2-minute timer countdown, the  
shutdown timer continues until the end of 2 minutes and then the UPS turns Off. By default, autore-  
start is enabled so the UPS will restart after 10 seconds. If autorestart is disabled via MultiLink soft-  
ware, the UPS remains Off until a manual restart.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           
Communications  
8.3  
USB Interface Port  
The PowerSure PSI has a USB interface port for communication that will work with the built-in  
Microsoft Power Manger software on the user’s PC, if so equipped. It will provide UPS status and  
manages the automatic orderly shutdown of the computer. The UPS’s USB communications meet  
HID standard, version 1.11. All USB models are compatible with Microsoft Windows 2000,  
Windows XP and Mac OS 10.2 or later. All USB models ship with a 1.8m (6 ft) USB cable.  
Microsoft, Windows, and the Windows logo  
are trademarks, or registered trademarks of  
Microsoft Corporation in the United States  
and/or other countries.  
8.4  
8.5  
Data Line Protection Connectors  
Data line (in and out) connectors are on the rear of the UPS and provide transient voltage surge sup-  
pression (TVSS) for Phone/Fax/DSL/Internet/Modem devices.  
UPS Intelligent Communications  
The PowerSure PSI is equipped with an Intellislot port to provide advanced communication and  
®
monitoring options.  
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or  
server in the event of an extended power failure.  
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the  
more information about the Intellislot OCWEBCARD and MultiLink License Kits, visit our Web site  
(www.liebert.com) or contact your local dealer or Liebert representative.  
Several option cards are available for use in the Intellislot port of the PowerSure PSI. The Intellislot  
OCWEBCARD provides SNMP and Web-based monitoring and control of the UPS across the network.  
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-  
dinate shutdown in the event of a power failure.  
The RELAYCARD-INT provides dry contact relay outputs for custom-wired applications and delivers  
support for built-in shutdown for AS/400 systems.  
NOTE  
The USB, Intellislot and Contact Closure communications operate in parallel. Using the  
OCWEBCARD disables the Serial Communications of the DB-9.  
CAUTION  
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables  
should be segregated and run separate from all other power cables, where applicable.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Voltage Programming Procedure  
9.0 VOLTAGE PROGRAMMING PROCEDURE  
Figure 17 Load Level Indicators  
Load Level  
Indicators  
Voltage  
Programming  
Button  
1. Remove the front bezel from the UPS.  
2. UPS must be operating in Normal (AC) mode.  
NOTE  
Mains power will be applied to the connected load.  
3. The AC Input, Load, and Battery Level Indicators should be lit.  
4. Press the Voltage Programming button for at least 5 seconds to enter the Configuration mode.  
The UPS will beep and all of the indicators on the front panel display will flash on and off for  
approximately 5 seconds. The next cycle will display the current configuration, either 220, 230 or  
240 VAC. One of the Load Level Indicators will be flashing. Initially, the 0%-25% Load Level  
Indicator will be flashing, indicating the default setting of 230V as shown in Figure 17.  
5. Press the ON button to step through the voltage settings until the appropriate Load Level  
Indicator is flashing.  
6. Press the Voltage Programming button. The UPS will return to Normal mode operation.  
The Voltage Programming button allows the operator to select the mains transfer voltage at which  
the UPS will switch to battery power. This also changes the inverter voltages. The voltage settings  
are as follows:  
Input Voltage  
Range  
Output Voltage  
(Battery Mode)  
Setting  
166 - 272VAC  
(default)  
120V (230V)  
230VAC  
110V (220V)  
127V (240V)  
158 - 260VAC  
172 - 283VAC  
220VAC  
240VAC  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Maintenance  
10.0 MAINTENANCE  
The PowerSure PSI UPS requires very little maintenance. Follow these practices to prevent prob-  
lems.  
10.1 Cleaning the UPS  
The following will help ensure trouble-free operation for years:  
• Vacuum dust from the ventilation intake occasionally.  
• Wipe the cover periodically with a dry cloth.  
10.2 Maintaining Batteries  
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their  
design life. The UPS continuously charges the batteries when connected to the mains supply, even  
while the UPS is switched Off.  
When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six  
months to ensure full recharge of the batteries.  
The PowerSure PSI is designed to allow the user to replace the internal batteries safely. Read the  
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the  
appropriate replacement battery kit part number and pricing.  
10.3 Battery Replacement  
CAUTION  
!
A battery can present a risk of electrical shock and high short circuit current. The following  
precautions should be observed before replacing the batteries:  
• Remove rings, watches, and other metal objects.  
• Use a Phillips (crosshead) screwdriver with insulated grips.  
• Do not lay tools or other metal objects on top of the batteries.  
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact  
your local dealer or Liebert representative immediately.  
• Do not dispose of batteries in a fire. The batteries may explode.  
• Dispose of old batteries according to local codes.  
• Risk of explosion if battery is replaced by an incorrect type. Refer to 12.0 - Specifications  
for battery information.  
• Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes. It is  
toxic.  
NOTE  
This UPS is equipped with internal “hot swappable” batteries that the user can replace without  
shutting down the UPS or connected loads. Caution should be exercised when replacing the  
batteries because the load is unprotected from disturbances and power outages during this  
procedure.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Maintenance  
10.3.1 Internal Battery Replacement Procedure  
1. Gently remove the front plastic bezel cover from the UPS.  
2. Loosen and remove the five (5) screws on the front cover plate. Lay the cover plate aside for  
reassembly.  
3. Loosen and remove four (4) screws on battery bracket.  
4. Disconnect the two (2) slotted, red and black battery connectors.  
5. Grasp the battery pack assembly by the pull tab and pull it out of the front of the UPS.  
6. Unpack the new battery assembly, taking care not to destroy the packing. Compare new and old  
battery assemblies to make sure they are the same. If so, proceed with Step 7; otherwise STOP  
and contact your local dealer, Liebert representative, or the Liebert Worldwide Support Group.  
7. Slide in the new replacement battery pack.  
8. Reattach the battery bracket with the four (4) screws.  
9. Reconnect the two (2) slotted red and black battery connectors.  
10. Reattach the front battery door with the five (5) screws.  
11. Reattach the front plastic bezel cover to the UPS.  
Figure 18 Battery replacement procedure  
0 3 0 2 0 1 0 0  
Battery  
Bracket  
Battery  
Connectors  
Battery  
Pull Tab  
Cover  
Plate  
Front Plastic Bezel  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Troubleshooting  
11.0 TROUBLESHOOTING  
The information below indicates various symptoms a user may encounter in the event the PowerSure  
PSI experiences a problem. Use this information to determine whether external factors caused the  
problem. See Table 2 - Troubleshooting chart for suggested remedy.  
1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for  
low battery, overload warning and over-temperature warning conditions.  
2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator,  
as described below:  
Figure 19 Status indicators  
All indicators illuminated  
for illustrative purposes only.  
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 5.0 - Installation. If the  
problem persists, refer to Table 2:  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Troubleshooting  
Table 2  
Troubleshooting chart  
Problem  
Cause  
Solution  
Check the circuit protector on the rear of the UPS.  
If it is tripped, reset it and restart the UPS. For  
further help, contact your local dealer, Liebert  
representative or the Liebert Worldwide Support  
Group.  
Short circuit  
UPS will not start  
Battery disconnected or is  
completely discharged  
Check for proper connection of battery or  
batteries.  
UPS not plugged in  
Plug in the power cord securely.  
Circuit protector tripped  
Reset the circuit protector and restart the UPS.  
Wait until the voltage rises to an appropriate level  
or have the mains power checked by a qualified  
electrician.  
UPS starts on battery, but will not  
switch to AC  
Input voltage below threshold  
AC overvoltage  
Wait until voltage lowers to an appropriate level  
or have the mains power checked by a qualified  
electrician.  
Check load level display and remove non-  
essential loads. Recalculate the load and reduce  
number of loads connected to UPS - the total  
wattage of your equipment must not exceed the  
capacity of the UPS.  
Load exceeded UPS capacity  
(110%), All Load Level Indicators  
are illuminated; continuous beep  
Over temperature shutdown, Over  
Temp Indicator lit; continuous  
beep  
Make sure that the UPS is operating in 0°C to  
40°C (32°F to 104°F) and that it has adequate  
ventilation.  
Consult the MultiLink user manual or contact your  
LAN administrator.  
UPS shuts down  
MultiLink shutdown  
Internal UPS fault, Fault Indicator  
Lit; continuous beep  
Contact your local dealer, Liebert representative  
or the Liebert Worldwide Support Group.  
Your UPS has received a signal or command  
from the attached computer. If this was  
inadvertent, ensure the communication cable  
used is correct for your system. For assistance,  
contact your local dealer, Liebert representative  
or the Liebert Worldwide Support Group.  
UPS shutdown due to a command  
from the communications port(s),  
Load Level 0-25% Indicator  
illuminated  
Check battery connections,  
UPS is unable to perform manual  
or remote battery test; beep every  
half second for five seconds  
completely power down and restart UPS.  
NOTE: If the battery circuit opens while the UPS  
is running, it will be detected when the next  
battery test is performed.  
All Battery Level Indicators  
flashing  
UPS failed battery test  
Batteries weak  
Initiate battery test again.  
Recharge batteries.  
Replace batteries.  
Battery Indicator illuminated  
amber; long beep every minute  
Batteries need to be replaced  
Make sure that the UPS is operating in 0°C to  
40°C (32°F to 104°F) and that it has adequate  
ventilation.  
Over temperature warning; beep  
every half second  
Over Temp Indicator flashing  
Fault Indicator lit but UPS is On  
Fault warning; beep every half  
second  
Reset UPS.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Specifications  
12.0 SPECIFICATIONS  
Table 3  
UPS specifications  
PS2200RT2-230  
PS2200RT2-230E  
PS3000RT2-230  
PS3000RT2-230E  
PS1000RT2-230  
PS1440RT2-230  
Model Number  
Power Rating, VA/W  
1000VA/750W  
1440VA/1080W  
2200VA/1650W  
3000VA/2250W  
Dimensions, W x D x H, mm (in)  
87 x 557 x 430  
(3.43 x 22 x 17)  
87 x 557 x 430  
(3.43 x 22 x 17)  
87 x 612 x 430  
(3.43 x 24.1 x 17)  
87 x 612 x 430  
(3.43 x 24.1 x 17)  
Unit  
300 x 706 x 598  
(11.8 x 27.8 x 23.5) (11.8 x 27.8 x 23.5)  
300 x 706 x 598  
333 x 864 x 598  
(13.1 x 34 x 23.5)  
333 x 864 x 598  
(13.1 x 34 x 23.5)  
Shipping  
Weight, kg (lbs)  
Unit  
28 (61.7)  
31.0 (68.2)  
39.0 (85.8)  
35.0 (77.0)  
43.6 (95.9)  
37.0 (81.6)  
Shipping  
36.6 (80.7)  
45.6 (100.5)  
Input AC Parameters  
Rated Input Voltage  
Surge Protection  
220/230/240VAC  
660J  
Voltage Range Without  
Battery Operation  
158VAC - 283VAC, configurable  
Frequency Range  
Input AC Inlet  
45 - 65 Hz (±0.1 Hz)  
IEC-320-C14  
IEC-320-C14  
IEC-320-C20  
IEC-320-C20  
Output AC Parameters  
(8) IEC-320-C13  
(1) IEC-320-C19  
(8) IEC-320-C13  
(1) IEC-320-C19  
Output Receptacles  
Voltage (Normal mode)  
Voltage (Battery Mode)  
(8) IEC-320-C13  
(8) IEC-320-C13  
220/230/240VAC (configurable) ±10%  
220/230/240VAC (configurable);  
±5% before low battery warning; ±8% after low battery warning  
Transfer Time  
Waveform  
4-6 ms typical  
Sinewave  
Frequency (Normal Mode)  
Frequency (Battery Mode)  
Overload Warning  
Overload Shutdown  
Battery Parameters  
Type  
45 - 65 Hz (±0.1 Hz)  
50 or 60 Hz (±0.5 Hz); auto sensing  
>100 - 110%  
>200% - short circuit; after 15 cycles (normal mode)  
Valve-regulated, nonspillable, lead acid  
QuantityxVoltagexRating  
Battery Manufacturers  
Backup Time  
4 x 12V x 7Ah  
4 x 12V x 7Ah  
6 x 12V x 7Ah  
6 x 12V x 9Ah  
CSB, B&B Battery, and EnerSys  
Full Load  
11  
26  
5
5
6
Half Load  
16  
16  
16  
Recharge Time  
4 hours to 90% of rated capacity, after full discharge into resistive load  
Environmental  
Operating Temperature  
Storage Temperature  
Relative Humidity  
0°C to + 40°C (+32°F to + 104°F)  
-15°C to + 40°C (+5°F to + 104°F)  
0% to 95%, non-condensing  
Up to 2,000m (6,500 ft) at 35°C (95°F)  
Up to 3,000m (10,000 ft) at 35°C (95°F)  
without derating  
Operating Altitude  
Audible Noise  
without derating  
<40 dBA, internal fan(s) Off  
<50 dBA, internal fan(s) On  
<40 dBA, internal fan(s) Off  
<60 dBA, internal fan(s) On  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Specifications  
Table 3  
UPS specifications (continued)  
PS2200RT2-230  
PS2200RT2-230E  
PS3000RT2-230  
PS3000RT2-230E  
PS1000RT2-230  
PS1440RT2-230  
Model Number  
Agency  
Safety  
Surge  
ESD  
EN 62040-1-1; TUV/GS listed; CE compliance mark  
EN61000-4-5, Level 3, Criteria B  
EN61000-4-2, Level 3, Criteria B  
EN61000-4-3, Level 3, Criteria A  
EN61000-4-4, Level 4, Criteria A  
EN 50091-2, Class B  
Susceptibility  
Electrical Fast Transient  
Emissions  
Conducted Immunity  
Harmonics  
EN61000-4-6  
EN61000-3-2  
Flicker  
EN61000-3-3  
Transportation  
ISTA Procedure 1A Certification  
Table 4  
Battery cabinet specifications  
PS2-48VBATT  
PS2-72VBATT  
Model Number  
PS1000RT2-230  
PS1440RT2-230  
PS2200RT2-230  
PS3000RT2-230  
Used w/UPS Model  
Dimensions, W x D x H, mm (in)  
Unit  
87 x 557 x 430 (3.43 x 22 x 17)  
87 x 612 x 430 (3.43 x 24.1 x 17)  
300 x 706 x 598  
(11.8 x 27.8 x 23.5)  
333 x 864 x 598  
(13.1 x 34 x 23.5)  
Shipping  
Weight, kg (lbs)  
Unit  
30 (66.1)  
46 (101.4)  
Shipping  
38.6 (85.1)  
53.6 (118.1)  
Battery Parameter  
Type  
Valve-regulated, nonspillable, lead acid  
Quantity x Voltage x Rating  
Battery Manufacturers  
Backup Time  
2 strings of 4 x 12V x 7Ah  
2 strings of 6 x 12V x 9Ah  
CSB, B&B Battery and EnerSys  
Environmental  
Operating Temperature  
Storage Temperature  
Relative Humidity  
Operating Altitude  
Agency  
0°C to + 40°C (+32°F to + 104°F)  
-15°C to + 40°C (+5°F to + 104°F)  
0% to 95%, non-condensing  
Up to 3,000m (10,000 ft) at 35°C (95°F) without derating  
Safety  
EN 62040-1-1; TUV/GS listed; CE compliance mark  
EN 50091-2, Class B  
Emissions  
Transportation  
ISTA Procedure 1A Certification  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Specifications  
Table 5  
Battery run times  
Load%  
5%  
1000VA  
174  
118  
65  
1440VA  
138  
79  
2200VA  
171  
73  
3000VA  
177  
91  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
5%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
5%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
5%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
5%  
45  
28  
24  
16  
14  
10  
9
6
47  
26  
23  
16  
13  
10  
8
6
47  
28  
22  
16  
14  
10  
9
7
41  
37  
26  
24  
18  
16  
12  
11  
513  
305  
248  
177  
139  
119  
98  
75  
63  
53  
46  
1001  
565  
409  
283  
248  
209  
166  
136  
127  
110  
98  
1174  
1001  
565  
409  
305  
274  
248  
209  
188  
145  
136  
1174  
828  
513  
461  
305  
283  
257  
239  
209  
188  
Internal  
Battery  
(minutes)  
5
5
6
409  
265  
188  
125  
104  
72  
59  
45  
40  
35  
542  
266  
185  
135  
122  
99  
75  
55  
49  
44  
542  
257  
148  
141  
99  
67  
53  
45  
39  
34  
29  
444  
249  
168  
148  
129  
114  
92  
Internal  
Battery + 1  
External  
Battery  
Cabinet  
(minutes)  
30  
40  
828  
461  
283  
219  
177  
133  
122  
98  
493  
291  
222  
194  
150  
137  
122  
107  
92  
Internal  
Battery + 2  
External  
Battery  
Cabinet  
(minutes)  
84  
64  
56  
71  
56  
52  
77  
1001  
655  
409  
283  
257  
209  
166  
136  
125  
110  
95  
1174  
828  
565  
357  
292  
257  
230  
188  
156  
136  
125  
590  
300  
240  
213  
168  
144  
129  
116  
101  
88  
493  
283  
266  
222  
185  
156  
141  
131  
120  
Internal  
Battery + 3  
External  
Battery  
Cabinet  
(minutes)  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
590  
395  
300  
274  
240  
203  
173  
156  
144  
444  
283  
266  
222  
179  
150  
139  
129  
118  
Internal  
Battery + 4  
External  
Battery  
Cabinet  
(minutes)  
NOTE  
Approximate discharge times are in minutes and at 25°C (77°F) with resistive load.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER AVAILABILITY  
PowerSure PSI™  
USER MANUAL  
The Company Behind the Products  
Technical Support/Service  
Web Site  
With over a million installations around the globe,  
Liebert is the world leader in computer protection  
systems. Since its founding in 1965, Liebert has  
developed a complete range of support and  
protection systems for sensitive electronics:  
Monitoring  
800-222-5877  
Outside the US: 614-841-6755  
Environmental systems—close-control air  
conditioning from 1 to 60 tons  
Single-Phase UPS  
800-222-5877  
Power conditioning and UPS with power  
ranges from 300 VA to more than 1000 kVA  
Integrated systems that provide both  
environmental and power protection in a  
single, flexible package  
Monitoring and control—from systems of any  
size or location, on-site or remote  
Service and support through more than 100  
service centers around the world and a 24/7  
Customer Response Center  
Outside the US: 614-841-6755  
Three-Phase UPS  
800-543-2378  
Environmental Systems  
800-543-2778  
Outside the United States  
614-888-0246  
While every precaution has been taken to ensure  
the accuracy and completeness of this literature,  
Liebert Corporation assumes no responsibility and  
disclaims all liability for damages resulting from  
use of this information or for any errors or  
omissions.  
Locations  
United States  
1050 Dearborn Drive  
P.O. Box 29186  
Columbus, OH 43229  
Italy  
Via Leonardo Da Vinci 8  
Zona Industriale Tognana  
35028 Piove Di Sacco (PD)  
+39 049 9719 111  
© 2003 Liebert Corporation  
All rights reserved throughout the world.  
Specifications subject to change without notice.  
® Liebert and the Liebert logo are registered  
trademarks of Liebert Corporation. All names  
referred to are trademarks or registered  
trademarks of their respective owners.  
Fax: +39 049 5841 257  
Asia  
23F, Allied Kajima Bldg.  
138 Gloucester Road  
Wanchai  
Hong Kong  
+852 2 572 2201  
Fax: +852 2 831 0114  
SLI-23290 (3/04) Rev. 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Kuppersbusch USA Water Heater GKS 3240 User Manual
Lantronix Network Hardware EDS1100 User Manual
Lenovo Personal Computer C345 User Manual
LG Electronics TV Antenna 32LV2510 TB User Manual
Mackie Music Mixer D8B User Manual
Magic Chef Oven 9112 Gas User Manual
Makita Drill 6203D User Manual
Maytag Clothes Dryer W10184553C User Manual
Melissa Food Warmer 750 026 User Manual
Mercury Automobile 1999 Mountaineer User Manual