POWER AVAILABILITY
USER MANUAL
PowerSure PSI™
1000 - 3000VA
230V
Version française, : reportez-vous au CD du guide d'utilisateur Liebert.
Para español, consulte el CD del Manual del Usuario de Liebert.
Die deutsche Fassung finden Sie auf der CD des Liebert-Benutzerhandbuchs.
Per l'Italiano, consultare il CD contenente il Manuale dell'utente Liebert.
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
GLOSSARY OF SYMBOLS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
MAJOR COMPONENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters. . . . . . . . . . . . . . . . . . . . 6
Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Automatic Voltage Regulator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inverter—1000/1440 Models Only. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
DC-to-DC Converter—2200/3000 Models Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Bi-Directional Converter—2200/3000 Models Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
WHAT’S INCLUDED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Preparation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Tower UPS Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Rack-Mount UPS Conversion and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
External Battery Cabinet Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
CONTROLS AND INDICATORS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
ON/Alarm Silence/Battery Test Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
OFF Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Voltage Programming Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Load Level Indicators—4 green, 1 amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Battery Level Indicators—5 green . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
AC Input Indicator—Green . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Buck/Boost Indicator—Green . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Battery Indicator—Green/Amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Over Temp Indicator—Amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
6.10 Fault Indicator—Red . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
MODES OF OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Normal Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Buck/Boost Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Battery Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Battery Recharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
COMMUNICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Remote Shutdown Via the DB-9 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2.1 Any Mode Shutdown—Via Pins 5 & 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.2.2 Battery Mode Shutdown—Via Pins 4 & 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
8.5
USB Interface Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Data Line Protection Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
UPS Intelligent Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
i
Download from Www.Somanuals.com. All Manuals Search And Download.
VOLTAGE PROGRAMMING PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
10.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
10.1 Cleaning the UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.2 Maintaining Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.3 Battery Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
10.3.1 Internal Battery Replacement Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
11.0 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
12.0 SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
FIGURES
Figure 1
Front view of UPS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1000 and 1440VA PSI—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2200 and 3000VA PSI—rear view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Line diagram of PowerSure PSI 1000VA & 1440VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Line diagram of PowerSure PSI 2200VA & 3000VA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Support base for tower configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Rack mount handles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Fixed rails with inner members extended. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Rack mounting rails and slide assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Figure 10 REPO switch connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Figure 11 Load level indicators—4 green, 1 amber . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 12 Battery level indicators—5 green. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Figure 13 Normal mode operation with 26-50% load. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Figure 14 Buck/Boost mode operation with 51-75% load and 21-40% battery capacity . . . . . . . . . . . . . . . . 17
Figure 15 Battery mode at 61 – 80% battery capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 16 Low Battery mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Figure 17 Load Level Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 18 Battery replacement procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 19 Status indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
TABLES
Table 1
DB-9 pin assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Troubleshooting chart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
UPS specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Battery cabinet specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Battery run times . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions that should be followed during the installation
and maintenance of the UPS and batteries. Please read this manual thoroughly before attempting to
install or operate this UPS.
WARNING
!
SAFETY PRECAUTIONS
To prevent the risk of fire or electric shock, install the UPS in a temperature and humidity
controlled room, free of conductive contaminants, moisture, flammable liquids, gases and
corrosive substances.
Operate the UPS only from a properly grounded (earthed) 220-240 VAC, 50Hz or 60Hz AC
supply.
To reduce the risk of electric shock, do not remove the cover—it has no user-serviceable parts
inside except the internal battery pack. Some components are live, even when AC power is
disconnected. For internal battery pack servicing, follow the instructions provided in 10.3 -
Battery Replacement. For other service, contact a qualified technician.
WARNING
!
ELECTRICAL PRECAUTIONS
• This UPS should not be supplied from electrical power systems of the IT (Impedance á
Terre) type (IEC 364 - Electrical Installation of Buildings).
• The UPS must be earthed/grounded at all times during operation. Connect only to a mains
supply socket outlet with an earth/ground connection.
CAUTION
!
Although your UPS has been designed and manufactured to ensure personal safety, improper
use can result in electrical shock or fire. To ensure safety, please observe the following rules:
• Turn Off and unplug your UPS before cleaning. Do not use liquid or aerosol cleaners. A dry
cloth is recommended to remove dust from the surface of your UPS.
• Do not install or operate your UPS in or near water.
• Do not place UPS on an unstable cart, stand or table.
• Do not place UPS under direct sunlight or close to heat emitting sources.
• Never block or insert any objects into the ventilation holes or other openings of the UPS.
Keep all vents free of dust accumulation that could restrict air flow.
• Do not place UPS power cord in any area where it may get damaged by heavy objects.
WARNING
!
If your UPS demonstrates any of the following conditions, turn Off and unplug your UPS from
the outlet and contact your local dealer, Liebert representative or Liebert Worldwide Support
Group:
• The power cord or plug is damaged.
• Liquid has been spilled on the UPS.
• The circuit protector trips frequently.
• The UPS does not operate in accordance with the user manual.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
CONDITIONS OF USE: The mains supply socket must be within 2m (6.5 ft.) of the UPS and be eas-
ily accessible.
Your UPS provides conditioned power to connected equipment. This product is designed for Commer-
cial use only. It is not intended for use with life support and other designated “critical” devices. Maxi-
mum load must not exceed that shown on the UPS rating label. If uncertain, consult your local dealer,
Liebert representative or the Liebert Worldwide Support Group.
The PSI 1000 VA, and 1440 VA models are not supplied with an input power cable for connection to
the mains supply socket. Use the input mains supply power cable from your data processing equip-
ment to connect the UPS to the mains supply.
For the 2200 VA and 3000VA models, use the supplied 16A-rated input mains supply cables. For UK
supply systems, consult a qualified electrician to connect the lead supplied for the 2200 VA and
3000VA models to the mains supply.
CAUTION
!
The UPS and connected load total earth leakage current must not exceed 3.5mA. If the
connected load earth leakage current is likely to exceed 2.5mA or you are unsure, then convert
the input cable attachment to either a fixed wiring installation or an industrial plug/socket
(e.g., CEE 17 connector). This alteration should be carried out by a competent electrical
engineer who is conversant with local electrical codes and regulations.
When installing the UPS or making input and output connections, comply with relevant safety codes
and standards (e.g. IEC60950, VDE0805, EN62040-1).
Placing magnetic storage media on top of the UPS may result in data corruption.
The equipment can be installed and operated by individuals without previous training.
CAUTION
!
DO NOT CONNECT equipment that could overload the UPS or demand half-wave
rectification from the UPS, for example: electric drills, vacuum cleaners, laserjet/inkjet
printers, hair dryers, overhead projectors.
CAUTION
!
Servicing of batteries should be performed or supervised by personnel knowledgeable of
batteries and required precautions. Keep unauthorized personnel away from the batteries.
A battery can present a risk of electrical shock and high short-circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
• Do not dispose battery or batteries in a fire. The battery may explode.
• Do not open or mutilate the battery or batteries. Released electrolyte is harmful to skin and
eyes. It is toxic.
• When replacing the battery, use same number and type of battery as the suitable recom-
• Handle, transport and recycle batteries in accordance with local regulations.
Electromagnetic Compatibility—The PowerSure™ PSI series complies with the requirements of
the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires
installation in accordance with these instructions and use of Liebert-approved accessories only.
Environmental-Operate the UPS in an indoor environment only in an ambient temperature range of
0°C to 40°C (32°F to 104°F). Install in a clean environment, free from conductive contaminants, mois-
ture, flammable liquids, gases, or corrosive substances.
Provided are a Liebert MultiLink cable and a USB cable for connection to a computer. Do not use the
Liebert MultiLink cable for other applications. Store in a safe place if not required at this time.
When using the communication features on this UPS, ensure the cabling connected to the DB-9 or
UPS communications ports are kept separated from the power leads to the UPS input and output.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Glossary of Symbols.
1.0 GLOSSARY OF SYMBOLS.
Risk of electrical shock
Indicates caution followed by important instructions
Requests the user to consult the manual
i
Indicates the unit contains a valve-regulated lead acid battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON/Alarm Silence/Battery Test
OFF
Voltage Programming Button
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
2.0 INTRODUCTION
Congratulations on your choice of the Liebert PowerSure™ PSI Uninterruptible Power Supply (UPS).
It provides conditioned power to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during transmission it may be subject to
voltage sags, spikes, or complete power failure which may interrupt computer operations, cause data
loss, or even damage equipment. The PowerSure PSI protects equipment from these disturbances.
The PowerSure PSI comes in nominal power ratings of 1000, 1440, 2200, or 3000 VA. Refer to 12.0 -
Specifications for details.
The PowerSure PSI is a 2U, line-interactive UPS that may be installed in a rack or used in a tower
configuration. A line-interactive UPS continuously conditions and regulates its output voltage,
whether mains power is present or not. It supplies connected equipment with clean, sinewave power
to simulate the power generated by the mains. Sensitive electronic equipment operates best from
sinewave power.
For ease of use, the PowerSure PSI contains Status Indicators to display Load Level, Battery Level,
Buck/Boost, Over Temperature and Battery. It also provides self-diagnostic tests, a combination ON/
Alarm Silence/Battery Test button, an OFF button and Voltage Programming button.
The PowerSure PSI has USB, DB-9 (RS232/contact closure) and Intellislot interface ports for commu-
nications between the UPS and a LAN server or other computer systems. The DB-9 port provides
detailed operating information including voltages, currents, and alarm status to the host system
when used in conjunction with Liebert’s MultiLink software. MultiLink software can also remotely
control UPS operation. The USB port provides detailed operating information and alarm status to the
host system when used in conjunction with the Liebert Human Interface Device (HID) and Microsoft
Power Manager software.
Figure 1 Front view of UPS
Fault
Indicator
OFF Button
Load Level
Indicators
ON/Alarm Silence/
Battery Test Button
Battery Level
Indicators
Voltage
Programming
Button
UPS Status
Indicators
UPS Display
(bezel removed)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
Figure 2 1000 and 1440VA PSI—rear view
Output
Receptacles
Data Line
Connectors
Circuit Breaker
Intellislot Port
REPO
INPUT
IN
OUT
BREAKER
PUSH TO RESET
1
2
3
4
LOAD 1
BATTERY
PHONE / FAX / MODEM / NETWORK
PROTECTION
CONNECTOR
1440VA/DC 48V/30A
1000VA/DC 48V/20A
+
-
INPUT
LOAD 2
INTELLISLOT
External Battery
Cabinet Connector
AC Input
USB Port
RS232 (DB-9)
Port
Figure 3 2200 and 3000VA PSI—rear view
Output Circuit
Breaker 1
Data Line
Connectors
Intellislot
Port
Output
Receptacles
Input Circuit
Breaker
REPO
PHONE / FAX /
MODEM / NETWORK
PROTECTION
LOAD 1
BREAKER
BATTERY
CONNECTOR
1
2
2200V/A/DC 72V30A
3000V/A/DC 72V40A
3
4
10A/260VAC
IN
OUT
REPO
LOAD 2
BREAKER
INTELLISLOT
INPUT
+
-
RS-232
INPUT
BREAKER
PUSH TO
RESET
LOAD 3
Output
Receptacle
AC Input
USB
Output Circuit
Breaker 2
External Battery
Cabinet Connector
Port
RS232 (DB-9)
Port
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Major Components
3.0 MAJOR COMPONENTS
Figure 4 Line diagram of PowerSure PSI 1000VA & 1440VA
Input
Output
EMI/RFI
Relay
Filter
AVR
Transformer
Charger
Battery
Inverter
G
G
Figure 5 Line diagram of PowerSure PSI 2200VA & 3000VA
Input
Output
EMI/RFI
Relay
AVR
Transformer
Filter
DC-to-DC
Converter
Bi-Directional
Converter
Charger
Battery
G
3.1
3.2
G
Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters
These UPS components provide surge protection and filter both electromagnetic interference (EMI)
and radio frequency interference (RFI). They minimize surges or interference present in the mains
line and keep the sensitive equipment protected.
Relay
In Normal mode the Relay passes mains AC power to the connected load. When input mains voltage
or frequency is outside acceptable limits, the Relay activates and transfers the UPS to battery.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Major Components
3.3
Automatic Voltage Regulator
The Automatic Voltage Regulator (AVR) protects connected equipment from power spikes, sags and
other abnormalities by raising (boosting) or lowering (bucking) the output voltage as needed. This
keeps the UPS output voltage within the connected equipment’s tolerance and accommodates wide
mains voltage fluctuations without utilizing the batteries.
3.4
3.5
Battery Charger
In Normal mode, the Battery Charger converts mains AC power into regulated DC power to float
charge the battery. It is continuously charging the battery whenever the UPS is plugged into a power
outlet and mains power is within acceptable limits - even if the UPS is turned Off.
Battery
The PowerSure PSI utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery
design life, operate the UPS in an ambient temperature of 20°C to 25°C (68°F to 77°F). Optional
external battery cabinets are available to extend battery run times.
3.6
3.7
Inverter—1000/1440 Models Only
In battery mode operation, the inverter utilizes the DC output of the battery and inverts it into pre-
cise, regulated, sinewave AC power.
DC-to-DC Converter—2200/3000 Models Only
The DC-to-DC Converter utilizes energy from the battery system and raises the DC voltage to the
optimum operating voltage for the Bi-Directional Converter. This allows the Bi-Directional Converter
to operate continuously at its optimum efficiency and voltage, thus increasing reliability.
3.8
Bi-Directional Converter—2200/3000 Models Only
In normal operation, the Bi-Directional Converter changes mains AC power into regulated DC power
to “float charge” the battery system. This converter is continuously charging the battery whenever the
UPS is plugged into a power outlet and mains power is within acceptable limits—even if the UPS is
turned Off. When mains power fails, the Bi-Directional Converter draws energy from the battery
through the DC-to-DC Converter and inverts it into a regulated sinewave supplying power to con-
nected equipment.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
What’s Included
4.0 WHAT’S INCLUDED
The PowerSure PSI is shipped with the following items:
• PowerSure PSI user manual
• MultiLink software CD
• MultiLink serial cable, 3m (10 ft)
• USB cable, 1.8m (6 ft)
• RJ-11 cord, 2.1m (7 ft)
• Rack mount handles
• Support base
• Fixed rails
• Mounting hardware (screws/washers)
• Front bezel
• Vertical display overlay
• Two (2) 10A output power cords, 2.0m (6.6 ft.)
• Input power cords, 2200 and 3000 VA models only
MultiLink
serial cable
3m (10 ft)
Vertical
display
overlay
MultiLink
software CD
USB cable
1.8m (6 ft)
RJ-11 cord
2.1m (7 ft)
Rack mount
handles
Mounting hardware
(screws & washers)
Fixed rails
Support base
Front bezel
10A output
power cords,
2.0m (6.6 ft.)
Input power cords,
2200 & 3000 VA models only;
one cord with 230 model;
two cords with 230E model
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
5.0 INSTALLATION
5.1 Preparation
1. Visually inspect the UPS for freight damage. Report damage to the carrier and your local dealer
or Liebert representative.
CAUTION
!
when lifting or moving it.
2. Decide where to place the PowerSure PSI. Install the UPS indoors in a controlled environment
where it cannot be accidentally turned Off. Place it in an area of unrestricted airflow around the
unit, away from water, flammable liquids, gases, corrosives, and conductive contaminants.
Maintain a minimum clearance of 100mm (4 inches) in the front and rear of the UPS. Maintain an
ambient temperature range of 0°C to 40°C (32°F to 104°F).
NOTE
UPS operation in temperatures above 25°C (77°F) reduces battery life.
3. The PowerSure PSI may be installed in either a tower configuration or in a rack, depending on
available space and use considerations. Determine the type of installation and follow the
appropriate instructions in either Tower UPS Installation or Rack-Mount UPS Conversion
and Installation.
5.2
Tower UPS Installation
When using the PowerSure PSI in a tower configuration, use the included support base (shown below,
left) to stabilize the UPS. If two or more battery cabinets are added, the spacers—included with the
battery cabinets—should be used to accommodate the additional cabinets.
Figure 6 Support base for tower configuration
Tower Stand - Fully Extended
Spacers Can be Added to Accommodate External Battery Cabinets
Connectors Snap into Slots on Base
1. To orient the display for vertical viewing, remove the front plastic bezel by pulling forward evenly
on both sides.
2. Peel the backing from the vertical display overlay and apply to the existing display.
3. Snap the front bezel back into place.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
5.3
Rack-Mount UPS Conversion and Installation
NOTE
When rack mounted, the UPS must be supported by a shelf, slide rails, brackets or fixed rails
on each side. The rack mount handles WILL NOT support the weight of the UPS. They are
used to move the UPS into and out of the rack.
1. For fixed rail installations, install the rack mount handles using four (4) M4x6 screws (see
Figure 7).
Figure 7 Rack mount handles
Two (2) M4x6
Flat Head Screws
Two (2) M4x6
Flat Head Screws
M4x6 Flat Screw
Rack Mount Handles
2. Unpack the two fixed rail assemblies and mounting hardware. Loosen the wing nuts and extend
Figure 8 Fixed rails with inner members extended
Wing Nuts for
Adjustment
Adjustable Slide
Assembly
Adjustable Length
Maximum 800 mm
Minimum 485 mm
CAUTION
!
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the
lowest possible rack position.
3. Determine the height position inside the rack enclosure where you want to mount the UPS or
battery cabinet. Make sure fixed rails are at the same mounting height on each of the four (4) rack
mounting rails.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
4. Attach the two (2) fixed rails to the racks mounting rails. The fixed rail assemblies fit on the
inside of the rack mounting rails.
5. Insert two (2) M5 flat head screws loosely (finger-tight) into the top and bottom holes on the front
6. Extend fixed rail by sliding inner member backward until it touches the rear rack mounting rail.
7. Insert two (2) M5 screws loosely (finger-tight) into top and bottom holes on the rear of the fixed
rail assembly.
8. Check alignment of fixed rails and tighten all screws to ensure locking action.
Figure 9 Rack mounting rails and slide assemblies
B
B
A
A
A - Washer
B - M5x12 Flat Screw
A
A
B
B
9. Lay the UPS in rack-mounting position on the fixed rails. The UPS should move smoothly forward
and backward on the fixed rails. If not, recheck alignment.
CAUTION
!
Lifting equipment into rack may be a two-person job, depending on weight of equipment.
10. Use the extra M5 screws provided, secure front of the UPS to rack mounting rails to prevent the
UPS from sliding out of position.
11. PowerSure PSI 230 VAC models are not supplied with an input power lead for connection to the
mains supply. Additional input/output cords may be obtained from your dealer. The input power
2
cord must have a minimal cross-sectional area of 1mm .
12. Shut down the load equipment and turn off the mains
supply. Unplug the load equipment's power input
cable from the mains supply socket and plug it into the
UPS input socket.
Vertical
overlay
for tower
UPS
Plug the power input cable into the mains supply
socket. Connect the supplied IEC-320-C14 output
power cable between the load equipment input socket
and one of the UPS AC output sockets.
13. Connect all load equipment to the UPS in this
manner.
14. Turn On the UPS by pressing the ON button. Check
that the AC Input Indicator is not flashing. If it is
Horizontal
overlay for
rack UPS
On the connected equipment. The UPS is now providing conditioned power to your equipment.
CAUTION
!
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should
be segregated and run separately from power cables.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
15. Connect Phone/Fax/DSL/Network/Modem devices to data line connectors.
RJ11/RJ45
connection
INPUT
IN
OUT
BREAKER
PUSH TO RESET
1
2
3
4
LOAD
1
BATTERY
PHONE
/
FAX MODEM NETWORK
/
/
CONNECTOR
PROTECTION
1440VA/DC 48V/30A
1000VA/DC 48V/20A
INPUT
+
-
LOAD
2
INTELLISLOT
Option 1 - Serial Communications
Serial communications provides parametric data, for example, input voltage and battery voltage.
a. Connect MultiLink serial cable included with the UPS to communications port.
b. Install the MultiLink software. The software and installation instructions, as well as the user
manual, are on the CD included in the PowerSure PSI package.
Option 2 - Contact Closure Communications
Contact Closure communications provides on-battery and low-battery signals for orderly shut-
down.
a. Refer to the MultiLink user manual for instructions on making your own contact closure
cable.
b. Install the MultiLink software. The software and installation instructions, as well as the user
manual, are on the CD included in the PowerSure PSI package.
Option 3 - USB Communications
a. Connect USB cable provided with the UPS to the PSI’s USB port and the USB port on your
computer. The PSI will work automatically with your built-in power management software on
Option 4 – Intellislot
The UPS contains one communication slot, called “Intellislot™,” to allow the operator to field
install optional communication cards. These optional cards allow the UPS to communicate via
either OpenComms Web Card (OCWEBCARD), connected directly to the LAN; or Intellislot Relay
Interface card (RELAYCARD-INT) communication card. Once the OCWEBCARD is installed, the
Serial communication via the RS232 is disabled. The USB, Intellislot, and Contact Closure com-
munications operate in parallel.
17. REPO Switch—The PowerSure PSI is equipped with a Remote Emergency Power Off (REPO)
switch.
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the
UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to
comply with national and local wiring codes and regulations.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 10 REPO switch connections
REPO Connector
REPO Switch
as shipped
REPO connections
for normally open
switch system
REPO connections
for normally closed
switch system (fail-safe)
1
2
3
4
1
2
3
4
1
2
3
4
Key to REPO switch connections
1. 24 VDC,
2. Sense
3. Sense
4. Ground
5.4
External Battery Cabinet Installation
Optional Liebert external battery cabinets may be connected to the UPS to provide additional battery
run time. External battery cabinets are designed to be placed all on one side of the UPS or stacked
beneath the UPS. The run time is limited to a maximum of four (4) hours.
CAUTION
!
cabinets can be used in rack-mount or tower configuration. Take proper precautions when
lifting them.
1. Visually inspect the external battery cabinet for freight damage. Report damage to the carrier
and your local dealer or Liebert representative.
2. The rack-mount handles are shipped with the external battery cabinet and may be installed at
3. Fixed rails and securing hardware ship with the external battery cabinet. Fasten the fixed rails
into position with the screws per the instructions included with the UPS. Repeat
4. Use the support bases included with the UPS for the tower option to prevent tip-over. One
additional set of support base spacers ships with each external battery cabinet.
5. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet,
then to the rear of the UPS, as shown at right.
6. The UPS is now equipped with additional backup battery run time. For approximate battery run
BATTERY
CONNECTOR
BATTERY
C
INPUT
BREAKER
PUSHTO RESET
OUT
IN
1
2
3
4
BATTERY
LOAD
1
CONNECTOR
1440VA/DC 48V/30A
1000VA/DC 48V/20A
PHONE
/
FAX
/
MODEM
/
NETWORK
PROTECTION
+
-
INPUT
LOAD 2
INTELLISLOT
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
6.0 CONTROLS AND INDICATORS
All indicators illuminated
for illustrative purposes only.
6.1
ON/Alarm Silence/Battery Test Button
This button controls output power to connected load(s) and has three functions:
• On
• Alarm Silence
• Battery Test
ON—When the UPS is Off, pressing the ON/Alarm Silence/Battery Test button for more than one
(1) second will start the UPS, and an audible alarm sounds briefly. The UPS is capable of starting on
battery (battery start).
Alarm Silence—When a UPS audible alarm is active, pressing and releasing the ON/Alarm Silence/
Battery Test button will silence the active audible alarm, whether mains power is present or not.
Once the alarm silence function has been activated, all active audible alarms will remain silenced
until a new alarm condition is detected.
NOTE
The LOW BATTERY, OVER TEMP and OVERLOAD warning
audible alarms CANNOT be silenced.
Battery Test—To initiate a manual battery test, press the ON/Alarm Silence/Battery Test button for
at least one second while operating from mains power with no alarm conditions present.
• If all five (5) Battery indicators are not illuminated, allow the UPS to recharge the batteries for
24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if all five (5) Battery indicators are not illuminated, con-
tact your local dealer, Liebert representative or Liebert Worldwide Support Group.
6.2
OFF Button
When the UPS is on (in either Normal or Battery mode), pressing the OFF button for more
than one (1) second will shut down the UPS. An audible alarm sounds briefly.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
6.3
6.4
Voltage Programming Button
The PowerSure PSI contains a Voltage Programming button that allows the operator to select
the nominal mains voltage. This setting changes the mains transfer points (low and high) of
the UPS and the nominal output voltage when operating in Battery mode. The operator can
select between 220, 230 and 240VAC output. The factory-default setting is 230VAC.
The Voltage Programming button is a push button type and is behind the plastic bezel on
the front panel of the UPS. To access the button, the front bezel must be removed.
Load Level Indicators—4 green, 1 amber
The Load Level Indicators display the approximate electrical load placed upon the UPS.
Figure 11 Load level indicators—4 green, 1 amber
Upon detection of an output overload condition, the amber overload (>100%) indicator flashes and an
audible alarm activates. If the UPS shuts down due to an overload condition, the amber overload
6.5
Battery Level Indicators—5 green
The Battery Level Indicators display the approximate battery capacity.
The approximate battery capacity is displayed when the UPS is operating in Normal, Buck/Boost, or
Battery mode.
Figure 12 Battery level indicators—5 green
The PowerSure PSI is equipped with automatic and remote battery test features. The automatic test
occurs every 14 days if mains has not been interrupted; this option may be configured by the user.
Should the battery fail this test, the amber Battery Indicator will be illuminated and an alarm will
The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery
test.
6.6
6.7
AC Input Indicator—Green
The AC Input Indicator illuminates when mains power is available and within the input specifica-
tions.
Buck/Boost Indicator—Green
The Buck/Boost Indicator illuminates when the UPS is operating in Boost mode to compensate for a
low mains voltage condition. This indicator flashes when the UPS is operating in Buck mode to com-
6.8
Battery Indicator—Green/Amber
The Battery Indicator illuminates green when the UPS is operating on battery and flashes green
when a low battery condition occurs. The Battery Indicator illuminates amber when a bad battery is
detected, indicating that the batteries need to be replaced (see 11.0 - Troubleshooting for details).
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
6.9
Over Temp Indicator—Amber
The Over Temp Indicator flashes when the UPS detects an over temperature condition. This indicator
illuminates when the UPS shuts down due to an over temperature condition (see 11.0 - Trouble-
shooting for details).
6.10 Fault Indicator—Red
The Fault Indicator illuminates when the UPS detects an internal problem (see 11.0 - Trou-
bleshooting for details).
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Modes of Operation
7.0 MODES OF OPERATION
7.1 Normal Mode
During Normal mode operation, the PowerSure PSI supplies conditioned, computer-grade power to
the connected equipment: mains power passes through the TVSS circuitry and the EMI/RFI filters
and then through the Inverter (1000VA & 1440VA) / Bi-Directional Converter (2200VA & 3000VA) to
connected equipment.
When the UPS is in Normal mode, the AC Input Indicator illuminates green. The UPS display in
Figure 13 shows the UPS operating in Normal mode with 26% - 50% load connected to the output.
Figure 13 Normal mode operation with 26-50% load
Mains power present ...
... and within operational limits
The PowerSure PSI continuously monitors the batteries to maintain them in a fully charged state.
The battery charger operates whenever AC power is present, even if the UPS is switched Off. By
default, the UPS is set to perform an automatic battery test after it has been operating continuously
for two (2) weeks. The automatic battery test can be disabled via MultiLink.
7.2
Buck/Boost Mode
The Automatic Voltage Regulator (AVR) circuitry compensates for fluctuations in mains power, such
as voltage surges and sags. When the PowerSure PSI detects an abnormality, it raises the undervolt-
age (boost) or lowers the overvoltage (buck) as needed. The AVR operates automatically and main-
tains the output voltage to the connected critical equipment, without utilizing the batteries.
The Buck/Boost Indicator flashes green when the UPS is operating in Buck mode and illuminates
Figure 14 Buck/Boost mode operation with 51-75% load and 21-40% battery capacity
Indicator shows
UPS in Boost Mode
(solid green)
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Modes of Operation
7.3
Battery Mode
The UPS switches to Battery mode in the event of an extreme input voltage/frequency condition or
complete mains failure. The battery system supplies power through the Inverter (1000VA & 1440VA)
or through the DC-to-DC converter to the Bi-Directional Converter (2200VA & 3000VA) to generate
power for the connected equipment.
When the UPS is in Battery mode, the Battery Indicator illuminates green and an alarm sounds
UPS in Battery mode with 61% - 80% battery capacity remaining.
Figure 15 Battery mode at 61 – 80% battery capacity
Battery Indicator
illuminated
When a low battery condition occurs, the Battery Indicator flashes green and the alarm sounds every
half-second. The default low battery warning is two (2) minutes but can be configured via MultiLink.
Figure 16 Low Battery mode
Battery Indicator
flashes green
approximates based on resistive load and an ambient temperature of 25°C (77°F). To increase this
time, turn Off non-essential pieces of equipment, such as idle computers and monitors, or add exter-
nal battery cabinets.
CAUTION
!
Turning Off the UPS while it is in battery mode will result in loss of output power.
7.4
Battery Recharge Operation
Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger
begins recharging.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Communications
8.0 COMMUNICATIONS
8.1 DB-9 Connector
The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a
computer system running MultiLink software. The DB-9 is capable of supplying serial communica-
tion, on battery and low battery signals. MultiLink, Liebert’s UPS monitoring and shutdown soft-
ware, is shipped with the UPS, along with a 3m (10 ft) DB-9 cable required for running MultiLink.
When MultiLink is installed on the host computer, the UPS can signal “on battery” and “low battery”
using opto-couplers. When the UPS is operating in Battery mode, it can receive a signal from the host
computer system that will shut down the UPS (after gracefully shutting down the operating system
on the host computer system) when the remaining battery run time is low. The timing of the signal
depends on MultiLink’s configuration settings. This shutdown signal (5-12VDC) must have a dura-
tion of at least 2 seconds for the UPS to be shut down. The UPS communicates via serial communica-
tions using Liebert ESP II protocol.
Table 1
DB-9 pin assignment
DB-9 Pin Assignment Description
1
2
3
4
5
6
7
8
9
Low Battery (open collector)
UPS TxD
UPS RxD
Battery Mode Shutdown (5-12V)
Common
Any Mode Shutdown (short to pin 5)
Low Battery (open emitter)
Mains Fail (open emitter)
Mains Fail (open collector)
Pin Assignment
Collector to Emitter*
Open
Collector
6
7
8
9
(+)
330 Ohms
Open
Emitter
(-)
1
2
3
4
5
8.2
Remote Shutdown Via the DB-9 Connector
The PowerSure PSI can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the
DB-9 connector.
8.2.1 Any Mode Shutdown—Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut Off regardless of what mode the UPS is oper-
ating in. The UPS cannot be started as long as the pins are shorted. When the short is removed, the
UPS output can be enabled by pressing the ON/Alarm Silence/Battery Test button.
8.2.2 Battery Mode Shutdown—Via Pins 4 & 5
While the UPS is operating on battery (with no battery test in progress), a 5-12VDC signal for 2 sec-
onds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer inside the UPS begins a count-
down. The timer cannot be stopped. If mains power returns during the 2-minute timer countdown, the
shutdown timer continues until the end of 2 minutes and then the UPS turns Off. By default, autore-
start is enabled so the UPS will restart after 10 seconds. If autorestart is disabled via MultiLink soft-
ware, the UPS remains Off until a manual restart.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Communications
8.3
USB Interface Port
The PowerSure PSI has a USB interface port for communication that will work with the built-in
Microsoft Power Manger software on the user’s PC, if so equipped. It will provide UPS status and
manages the automatic orderly shutdown of the computer. The UPS’s USB communications meet
HID standard, version 1.11. All USB models are compatible with Microsoft Windows 2000,
Windows XP and Mac OS 10.2 or later. All USB models ship with a 1.8m (6 ft) USB cable.
Microsoft, Windows, and the Windows logo
are trademarks, or registered trademarks of
Microsoft Corporation in the United States
and/or other countries.
8.4
8.5
Data Line Protection Connectors
Data line (in and out) connectors are on the rear of the UPS and provide transient voltage surge sup-
pression (TVSS) for Phone/Fax/DSL/Internet/Modem devices.
UPS Intelligent Communications
The PowerSure PSI is equipped with an Intellislot port to provide advanced communication and
®
monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can shut down your computer or
server in the event of an extended power failure.
is installed in the UPS. Additionally, MultiLink can be configured to coordinate shutdown across the
more information about the Intellislot OCWEBCARD and MultiLink License Kits, visit our Web site
Several option cards are available for use in the Intellislot port of the PowerSure PSI. The Intellislot
OCWEBCARD provides SNMP and Web-based monitoring and control of the UPS across the network.
The Intellislot MultiPort 4 Card allows you to install MultiLink software on four computers and coor-
dinate shutdown in the event of a power failure.
The RELAYCARD-INT provides dry contact relay outputs for custom-wired applications and delivers
support for built-in shutdown for AS/400 systems.
NOTE
The USB, Intellislot and Contact Closure communications operate in parallel. Using the
OCWEBCARD disables the Serial Communications of the DB-9.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables
should be segregated and run separate from all other power cables, where applicable.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Voltage Programming Procedure
9.0 VOLTAGE PROGRAMMING PROCEDURE
Figure 17 Load Level Indicators
Load Level
Indicators
Voltage
Programming
Button
1. Remove the front bezel from the UPS.
2. UPS must be operating in Normal (AC) mode.
NOTE
Mains power will be applied to the connected load.
3. The AC Input, Load, and Battery Level Indicators should be lit.
4. Press the Voltage Programming button for at least 5 seconds to enter the Configuration mode.
The UPS will beep and all of the indicators on the front panel display will flash on and off for
approximately 5 seconds. The next cycle will display the current configuration, either 220, 230 or
240 VAC. One of the Load Level Indicators will be flashing. Initially, the 0%-25% Load Level
5. Press the ON button to step through the voltage settings until the appropriate Load Level
Indicator is flashing.
6. Press the Voltage Programming button. The UPS will return to Normal mode operation.
The Voltage Programming button allows the operator to select the mains transfer voltage at which
the UPS will switch to battery power. This also changes the inverter voltages. The voltage settings
are as follows:
Input Voltage
Range
Output Voltage
(Battery Mode)
Setting
166 - 272VAC
(default)
120V (230V)
230VAC
110V (220V)
127V (240V)
158 - 260VAC
172 - 283VAC
220VAC
240VAC
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
10.0 MAINTENANCE
The PowerSure PSI UPS requires very little maintenance. Follow these practices to prevent prob-
lems.
10.1 Cleaning the UPS
The following will help ensure trouble-free operation for years:
• Vacuum dust from the ventilation intake occasionally.
• Wipe the cover periodically with a dry cloth.
10.2 Maintaining Batteries
The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their
design life. The UPS continuously charges the batteries when connected to the mains supply, even
while the UPS is switched Off.
When storing the UPS, it is recommended to plug in the UPS for at least 24 hours every four to six
months to ensure full recharge of the batteries.
The PowerSure PSI is designed to allow the user to replace the internal batteries safely. Read the
safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the
appropriate replacement battery kit part number and pricing.
10.3 Battery Replacement
CAUTION
!
A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed before replacing the batteries:
• Remove rings, watches, and other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Liebert representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
• Dispose of old batteries according to local codes.
for battery information.
• Do not open or mutilate the batteries. Released electrolyte is harmful to skin and eyes. It is
toxic.
NOTE
This UPS is equipped with internal “hot swappable” batteries that the user can replace without
shutting down the UPS or connected loads. Caution should be exercised when replacing the
batteries because the load is unprotected from disturbances and power outages during this
procedure.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
10.3.1 Internal Battery Replacement Procedure
1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the five (5) screws on the front cover plate. Lay the cover plate aside for
reassembly.
3. Loosen and remove four (4) screws on battery bracket.
4. Disconnect the two (2) slotted, red and black battery connectors.
5. Grasp the battery pack assembly by the pull tab and pull it out of the front of the UPS.
6. Unpack the new battery assembly, taking care not to destroy the packing. Compare new and old
and contact your local dealer, Liebert representative, or the Liebert Worldwide Support Group.
7. Slide in the new replacement battery pack.
8. Reattach the battery bracket with the four (4) screws.
9. Reconnect the two (2) slotted red and black battery connectors.
10. Reattach the front battery door with the five (5) screws.
11. Reattach the front plastic bezel cover to the UPS.
Figure 18 Battery replacement procedure
0 3 0 2 0 1 0 0
Battery
Bracket
Battery
Connectors
Battery
Pull Tab
Cover
Plate
Front Plastic Bezel
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
11.0 TROUBLESHOOTING
The information below indicates various symptoms a user may encounter in the event the PowerSure
PSI experiences a problem. Use this information to determine whether external factors caused the
1. An alarm sounds, alerting that the UPS requires attention. The alarm can be silenced except for
low battery, overload warning and over-temperature warning conditions.
2. One or more additional indicators will be illuminated to provide a diagnostic aid to the operator,
as described below:
Figure 19 Status indicators
All indicators illuminated
for illustrative purposes only.
If the UPS fails to operate properly, turn Off the unit and repeat the steps in 5.0 - Installation. If the
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table 2
Troubleshooting chart
Problem
Cause
Solution
Check the circuit protector on the rear of the UPS.
If it is tripped, reset it and restart the UPS. For
further help, contact your local dealer, Liebert
representative or the Liebert Worldwide Support
Group.
Short circuit
UPS will not start
Battery disconnected or is
completely discharged
Check for proper connection of battery or
batteries.
UPS not plugged in
Plug in the power cord securely.
Circuit protector tripped
Reset the circuit protector and restart the UPS.
Wait until the voltage rises to an appropriate level
or have the mains power checked by a qualified
electrician.
UPS starts on battery, but will not
switch to AC
Input voltage below threshold
AC overvoltage
Wait until voltage lowers to an appropriate level
or have the mains power checked by a qualified
electrician.
Check load level display and remove non-
essential loads. Recalculate the load and reduce
number of loads connected to UPS - the total
wattage of your equipment must not exceed the
capacity of the UPS.
Load exceeded UPS capacity
(110%), All Load Level Indicators
are illuminated; continuous beep
Over temperature shutdown, Over
Temp Indicator lit; continuous
beep
Make sure that the UPS is operating in 0°C to
40°C (32°F to 104°F) and that it has adequate
ventilation.
Consult the MultiLink user manual or contact your
LAN administrator.
UPS shuts down
MultiLink shutdown
Internal UPS fault, Fault Indicator
Lit; continuous beep
Contact your local dealer, Liebert representative
or the Liebert Worldwide Support Group.
Your UPS has received a signal or command
from the attached computer. If this was
inadvertent, ensure the communication cable
used is correct for your system. For assistance,
contact your local dealer, Liebert representative
or the Liebert Worldwide Support Group.
UPS shutdown due to a command
from the communications port(s),
Load Level 0-25% Indicator
illuminated
Check battery connections,
UPS is unable to perform manual
or remote battery test; beep every
half second for five seconds
completely power down and restart UPS.
NOTE: If the battery circuit opens while the UPS
is running, it will be detected when the next
battery test is performed.
All Battery Level Indicators
flashing
UPS failed battery test
Batteries weak
Initiate battery test again.
Recharge batteries.
Replace batteries.
Battery Indicator illuminated
amber; long beep every minute
Batteries need to be replaced
Make sure that the UPS is operating in 0°C to
40°C (32°F to 104°F) and that it has adequate
ventilation.
Over temperature warning; beep
every half second
Over Temp Indicator flashing
Fault Indicator lit but UPS is On
Fault warning; beep every half
second
Reset UPS.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
12.0 SPECIFICATIONS
Table 3
UPS specifications
PS2200RT2-230
PS2200RT2-230E
PS3000RT2-230
PS3000RT2-230E
PS1000RT2-230
PS1440RT2-230
Model Number
Power Rating, VA/W
1000VA/750W
1440VA/1080W
2200VA/1650W
3000VA/2250W
Dimensions, W x D x H, mm (in)
87 x 557 x 430
(3.43 x 22 x 17)
87 x 557 x 430
(3.43 x 22 x 17)
87 x 612 x 430
(3.43 x 24.1 x 17)
87 x 612 x 430
(3.43 x 24.1 x 17)
Unit
300 x 706 x 598
(11.8 x 27.8 x 23.5) (11.8 x 27.8 x 23.5)
300 x 706 x 598
333 x 864 x 598
(13.1 x 34 x 23.5)
333 x 864 x 598
(13.1 x 34 x 23.5)
Shipping
Weight, kg (lbs)
Unit
28 (61.7)
31.0 (68.2)
39.0 (85.8)
35.0 (77.0)
43.6 (95.9)
37.0 (81.6)
Shipping
36.6 (80.7)
45.6 (100.5)
Input AC Parameters
Rated Input Voltage
Surge Protection
220/230/240VAC
660J
Voltage Range Without
Battery Operation
158VAC - 283VAC, configurable
Frequency Range
Input AC Inlet
45 - 65 Hz (±0.1 Hz)
IEC-320-C14
IEC-320-C14
IEC-320-C20
IEC-320-C20
Output AC Parameters
(8) IEC-320-C13
(1) IEC-320-C19
(8) IEC-320-C13
(1) IEC-320-C19
Output Receptacles
Voltage (Normal mode)
Voltage (Battery Mode)
(8) IEC-320-C13
(8) IEC-320-C13
220/230/240VAC (configurable) ±10%
220/230/240VAC (configurable);
±5% before low battery warning; ±8% after low battery warning
Transfer Time
Waveform
4-6 ms typical
Sinewave
Frequency (Normal Mode)
Frequency (Battery Mode)
Overload Warning
Overload Shutdown
Battery Parameters
Type
45 - 65 Hz (±0.1 Hz)
50 or 60 Hz (±0.5 Hz); auto sensing
>100 - 110%
>200% - short circuit; after 15 cycles (normal mode)
Valve-regulated, nonspillable, lead acid
QuantityxVoltagexRating
Battery Manufacturers
Backup Time
4 x 12V x 7Ah
4 x 12V x 7Ah
6 x 12V x 7Ah
6 x 12V x 9Ah
CSB, B&B Battery, and EnerSys
Full Load
11
26
5
5
6
Half Load
16
16
16
Recharge Time
4 hours to 90% of rated capacity, after full discharge into resistive load
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
0°C to + 40°C (+32°F to + 104°F)
-15°C to + 40°C (+5°F to + 104°F)
0% to 95%, non-condensing
Up to 2,000m (6,500 ft) at 35°C (95°F)
Up to 3,000m (10,000 ft) at 35°C (95°F)
without derating
Operating Altitude
Audible Noise
without derating
<40 dBA, internal fan(s) Off
<50 dBA, internal fan(s) On
<40 dBA, internal fan(s) Off
<60 dBA, internal fan(s) On
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 3
UPS specifications (continued)
PS2200RT2-230
PS2200RT2-230E
PS3000RT2-230
PS3000RT2-230E
PS1000RT2-230
PS1440RT2-230
Model Number
Agency
Safety
Surge
ESD
EN 62040-1-1; TUV/GS listed; CE compliance mark
EN61000-4-5, Level 3, Criteria B
EN61000-4-2, Level 3, Criteria B
EN61000-4-3, Level 3, Criteria A
EN61000-4-4, Level 4, Criteria A
EN 50091-2, Class B
Susceptibility
Electrical Fast Transient
Emissions
Conducted Immunity
Harmonics
EN61000-4-6
EN61000-3-2
Flicker
EN61000-3-3
Transportation
ISTA Procedure 1A Certification
Table 4
Battery cabinet specifications
PS2-48VBATT
PS2-72VBATT
Model Number
PS1000RT2-230
PS1440RT2-230
PS2200RT2-230
PS3000RT2-230
Used w/UPS Model
Dimensions, W x D x H, mm (in)
Unit
87 x 557 x 430 (3.43 x 22 x 17)
87 x 612 x 430 (3.43 x 24.1 x 17)
300 x 706 x 598
(11.8 x 27.8 x 23.5)
333 x 864 x 598
(13.1 x 34 x 23.5)
Shipping
Weight, kg (lbs)
Unit
30 (66.1)
46 (101.4)
Shipping
38.6 (85.1)
53.6 (118.1)
Battery Parameter
Type
Valve-regulated, nonspillable, lead acid
Quantity x Voltage x Rating
Battery Manufacturers
Backup Time
2 strings of 4 x 12V x 7Ah
2 strings of 6 x 12V x 9Ah
CSB, B&B Battery and EnerSys
Environmental
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Agency
0°C to + 40°C (+32°F to + 104°F)
-15°C to + 40°C (+5°F to + 104°F)
0% to 95%, non-condensing
Up to 3,000m (10,000 ft) at 35°C (95°F) without derating
Safety
EN 62040-1-1; TUV/GS listed; CE compliance mark
EN 50091-2, Class B
Emissions
Transportation
ISTA Procedure 1A Certification
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Table 5
Battery run times
Load%
5%
1000VA
174
118
65
1440VA
138
79
2200VA
171
73
3000VA
177
91
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
5%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
5%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
5%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
5%
45
28
24
16
14
10
9
6
47
26
23
16
13
10
8
6
47
28
22
16
14
10
9
7
41
37
26
24
18
16
12
11
513
305
248
177
139
119
98
75
63
53
46
1001
565
409
283
248
209
166
136
127
110
98
1174
1001
565
409
305
274
248
209
188
145
136
—
1174
828
513
461
305
283
257
239
209
188
Internal
Battery
(minutes)
5
5
6
409
265
188
125
104
72
59
45
40
35
542
266
185
135
122
99
75
55
49
44
542
257
148
141
99
67
53
45
39
34
29
—
444
249
168
148
129
114
92
Internal
Battery + 1
External
Battery
Cabinet
(minutes)
30
40
—
828
461
283
219
177
133
122
98
493
291
222
194
150
137
122
107
92
Internal
Battery + 2
External
Battery
Cabinet
(minutes)
84
64
56
71
56
52
—
77
—
—
1001
655
409
283
257
209
166
136
125
110
95
1174
828
565
357
292
257
230
188
156
136
125
590
300
240
213
168
144
129
116
101
88
493
283
266
222
185
156
141
131
120
—
Internal
Battery + 3
External
Battery
Cabinet
(minutes)
—
—
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
—
590
395
300
274
240
203
173
156
144
444
283
266
222
179
150
139
129
118
Internal
Battery + 4
External
Battery
Cabinet
(minutes)
NOTE
Approximate discharge times are in minutes and at 25°C (77°F) with resistive load.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
POWER AVAILABILITY
PowerSure PSI™
USER MANUAL
The Company Behind the Products
Technical Support/Service
Web Site
With over a million installations around the globe,
Liebert is the world leader in computer protection
systems. Since its founding in 1965, Liebert has
developed a complete range of support and
protection systems for sensitive electronics:
Monitoring
800-222-5877
Outside the US: 614-841-6755
•
•
•
Environmental systems—close-control air
conditioning from 1 to 60 tons
Single-Phase UPS
800-222-5877
Power conditioning and UPS with power
ranges from 300 VA to more than 1000 kVA
Integrated systems that provide both
environmental and power protection in a
single, flexible package
Monitoring and control—from systems of any
size or location, on-site or remote
Service and support through more than 100
service centers around the world and a 24/7
Customer Response Center
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
•
•
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
While every precaution has been taken to ensure
the accuracy and completeness of this literature,
Liebert Corporation assumes no responsibility and
disclaims all liability for damages resulting from
use of this information or for any errors or
omissions.
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
© 2003 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
SLI-23290 (3/04) Rev. 1
Download from Www.Somanuals.com. All Manuals Search And Download.
|