POWER AVAILABILITY
USER MANUAL
UPStation GXT 2U™
500-3000VA
120V
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE OF CONTENTS
5.9
i
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLES
Table 1
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
WARNING
!
Opening or removing the cover may expose you to lethal
voltages within this unit even when it is apparently not
operating and the input wiring is disconnected from the
electrical source. Observe all cautions and warnings in this
manual. Failure to do so MAY result in serious injury or
death. Refer all UPS and battery service to qualified service
personnel. Do not attempt to service this product yourself.
Never work alone.
SAVE THESE INSTRUCTIONS
This manual contains important safety instructions. Read all safety,
installation, and operating instructions before operating the Uninter-
ruptible Power System (UPS). Adhere to all warnings on the unit and
in this manual. Follow all operating and user instructions. Individuals
without previous training can install and operate this equipment.
It is not intended for use with life support and other designated “criti-
cal” devices. Maximum load must not exceed that shown on the UPS
rating label. The UPS is designed for data processing equipment. If
uncertain, consult your local dealer or Liebert representative.
This UPS is designed for use on a properly grounded (earthed), 50Hz
or 60Hz, 120V supply (programmable for 100, 110, 115, 120 and
127VAC output). Installation instructions and warning notices are
located in this manual.
ELECTROMAGNETIC COMPATIBILITY—The GXT 2U™ Series
complies with the limits for a CLASS A DIGITAL DEVICE, PURSU-
ANT TO Part 15 of FCC rules. Operation is subject to the following
two conditions: (1) This device may not cause harmful interference,
and (2) this device must accept any interference received, including
interference that may cause undesired operation. Operating this
device in a residential area is likely to cause harmful interference that
users must correct at their own expense.
Operate the UPS in an indoor environment only in an ambient tem-
perature range of 32°F to +104°F (0°C to +40°C). Install it in a clean
environment, free from moisture, flammable liquids, gases and corro-
sive substances.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
This UPS contains no user serviceable parts except the internal bat-
tery pack. The UPS ON/Standby push buttons do not electrically iso-
late internal parts. Under no circumstances attempt to gain access
internally other than to replace the batteries due to risk of electric
shock or burn. Do not continue to use the UPS if the front panel indi-
cations are not in accordance with these operating instructions or if
the UPS performance alters in use. Refer all faults to your local
dealer, Liebert representative or the Liebert Worldwide Support
Group.
Servicing of batteries should be performed or supervised by personnel
knowledgeable of batteries and the required precautions. Keep unau-
thorized personnel away from the batteries. PROPER DISPOSAL OF
BATTERIES IS REQUIRED. REFER TO YOUR LOCAL LAWS AND
REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS.
Never block or insert any object into the ventilation holes or other
openings of the UPS.
DO NOT CONNECT equipment that could overload the UPS or
demand half-wave rectification from the UPS, for example: electric
drills, vacuum cleaners, laser printers or hairdryers.
Storing magnetic media on top of the UPS may result in data loss or
corruption.
Turn the UPS off and isolate the UPS before cleaning; use only a soft
cloth, never liquid or aerosol cleaners. Keep the front and rear vents
free of dust accumulation that could restrict airflow.
When replacing batteries, replace with the same Liebert authorized
replacement battery kits.
CAUTION
!
Do not dispose of battery or batteries in a fire. The battery
may explode.
Do not open or mutilate the battery or batteries. Released
electrolyte is harmful to skin and eyes. It may be toxic.
CAUTION
!
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
when working on batteries:
• Remove watches, rings, and other metal objects.
• Use tools with insulated handles.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
Glossary of Symbols
1.0 GLOSSARY OF SYMBOLS
Risk of electrical shock
Indicates caution followed by important instructions
AC input
AC output
Requests the user to consult the manual
i
Indicates the unit contains a valve-regulated lead acid
battery
Recycle
DC voltage
Equipment grounding conductor
Bonded to ground
AC voltage
ON
Standby
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Introduction
2.0 INTRODUCTION
Congratulations on your choice of the Liebert UPStation GXT 2U™
Uninterruptible Power System (UPS). It provides conditioned power
to microcomputers and other sensitive electronic equipment.
Upon generation, AC power is clean and stable. However, during
transmission and distribution it may be subject to voltage sags,
spikes, or complete power failure that may interrupt computer opera-
tions, cause data loss, or even damage equipment. The UPStation
GXT 2U protects equipment from these disturbances.
The UPStation GXT 2U comes in nominal power ratings of 500, 700,
1000, 1500, 2000 and 3000 VA. Complete model specifications appear
at the end of this manual.
The UPStation GXT 2U is a compact, “on-line” UPS. An on-line UPS
continuously conditions and regulates its output voltage, whether util-
ity power is present or not. It supplies connected equipment with
clean sinewave power. Sensitive electronic equipment operates best
from sinewave power.
For ease of use, the UPStation GXT 2U features a light-emitting diode
(LED) display to indicate either load percentage or battery capacity
depending upon the mode of operation. It also provides self-diagnostic
tests, a combination ON/Alarm Silence/Manual Battery Test button, a
Standby button, user configurable program, and two levels of alarms
when the unit is operating on battery.
The UPStation GXT 2U has an interface port for communication
between the UPS and a network server or other computer systems.
This port provides detailed operating information including voltages,
currents, and alarm status to the host system when used in conjunc-
tion with Liebert MultiLink™ software. MultiLink software can also
remotely control UPS operation.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Major Components
3.0 MAJOR COMPONENTS
Input
Output
Dynamic
Bypass
TVSS &
EMI/RFI
Filters
Rectifier
/PFC
Inverter
L1
L1
DC to DC
Converter
Battery
Charger
Battery
L2
G
L2
G
3.1
TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS)
AND EMI/RFI FILTERS
These UPS components provide surge protection and filter both elec-
tromagnetic interference (EMI) and radio frequency interference
(RFI). They minimize any surges or interference present in the utility
line and keep the sensitive equipment protected.
3.2
RECTIFIER/POWER FACTOR CORRECTION (PFC) CIRCUIT
In normal operation, the rectifier/power factor correction (PFC) circuit
converts utility AC power to regulated DC power for use by the
inverter while ensuring that the waveshape of the input current used
by the UPS is near ideal. Extracting this sinewave input current
achieves two objectives:
• The utility power is used as efficiently as possible by the UPS.
• The amount of distortion reflected on the utility is reduced.
This results in cleaner power being available to other devices in the
building not being protected by the UPStation GXT 2U.
3.3
INVERTER
In normal operation, the inverter utilizes the DC output of the power
factor correction circuit and inverts it into precise, regulated sinewave
AC power. Upon a utility power failure, the inverter receives its
required energy from the battery through the DC to DC converter. In
both modes of operation, the UPS inverter is on-line and continuously
generating clean, precise, regulated AC output power.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Major Components
3.4
BATTERY CHARGER
The battery charger utilizes energy from the utility power and pre-
cisely regulates it to continuously “float charge” the batteries. The bat-
teries are being charged whenever the UPStation GXT 2U is plugged
in, even when the UPS is not turned on.
3.5
DC TO DC CONVERTER
The DC to DC converter utilizes energy from the battery system and
raises the DC voltage to the optimum operating voltage for the
inverter. This allows the inverter to operate continuously at its opti-
mum efficiency and voltage, thus increasing reliability.
3.6
BATTERY
The UPStation GXT 2U utilizes valve-regulated, nonspillable, flame
retardant, lead acid batteries. To maintain battery design life, operate
the UPS in an ambient temperature of 68°F to 77°F (20°C to 25°C).
Optional external battery cabinets are available to extend battery run
times.
3.7
DYNAMIC BYPASS
The UPStation GXT 2U provides an alternate path for utility power to
the connected load in the unlikely event of a UPS malfunction. Should
the UPS have an overload, overtemperature, or UPS failure condition,
the UPS automatically transfers the connected load to bypass. Bypass
operation is indicated by an audible alarm and illuminated amber
Bypass LED (other LEDs may be illuminated to indicate the diag-
nosed problem). To manually transfer the connected load from the
inverter to bypass, press the Standby button once.
NOTE
The bypass power path does NOT protect the connected
equipment from disturbances on the utility supply.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
4.0 INSTALLATION
4.1
PREPARATION
1. Visually inspect the UPS for freight damage. Report damage to
the carrier and your local dealer or Liebert representative.
CAUTION
!
precautions when lifting or moving it.
2. Decide where to place the GXT 2U. Install the UPS indoors in a
controlled environment, where it cannot be accidentally turned off.
Place it in an area of unrestricted airflow around the unit, away
from water, flammable liquids, gases, corrosives, and conductive
contaminants. Maintain a minimum clearance of 4 in. (100mm) in
the front and rear of the UPS. Maintain an ambient temperature
range of 32°F to 104°F (0°C to 40°C).
NOTE
UPS operation in temperatures above 77°F (25°C) reduces
battery life.
3. The GXT 2U may be installed in either a tower configuration or in
a rack, depending on available space and use considerations.
Determine the type of installation and follow the appropriate
4.2
TOWER UPS INSTALLATION
When using the GXT 2U in a tower configuration, use the included
support base (shown below, left) to stabilize the UPS.
If any battery cabinets are added, they will include spacers to accom-
modate the additional cabinets (shown below, right).
Support base
Spacers added to support
base to accommodate
additional battery cabinets
8
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
4.3
RACK-MOUNT UPS CONVERSION AND INSTALLATION
NOTE
When rack mounted, the UPS must be supported by a shelf,
brackets or slide rails on each side. The rack mount handles
WILL NOT support the weight of the UPS. They are used to
move the UPS into and out of the rack.
1. For slide rail installations, first remove the top/side fin. Slide the
top/side fin forward, then lift it up to remove. If desired, install the
optional rack mount handles that were shipped with the UPS.
UPStation GXT
–
+
AC INPUT
BATTERY
UPS
ON
BYPASS
Optional rack mount handles
Securing hardware and slide rails are sold separately. Contact
your local dealer or Liebert representative for these additional
options and any assistance needed.
2. Unpack the two (2) rack-
Return
mounting bracket assemblies
and mounting hardware
from the rack-mounting kit
(P/N: RMKIT18-32). Bracket
assemblies are
flanges
Retaining
latches
interchangeable between
left-hand or right-hand.
Remove inner member of
each bracket assembly as
shown at right by extending
it to its outermost position,
depressing the retaining
latch and then pulling inner
member from bracket
Rear
members
Front
members
Inner
members
assembly.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
3. Determine the height position inside the rack enclosure where you
want to mount the UPS or battery cabinet.
CAUTION
!
Reduce risk of tipping the rack enclosure by placing UPS or
battery cabinet in the lowest possible rack position.
Install rear member of each
M5 screws
bracket assembly into rack
enclosure with two (2) M5
screws provided in this kit.
(See figure at right.) Return
flanges on bracket assembly
fit to the inside of rack
Front rack
mounting rails
mounting rails. Insert screws
loosely (finger-tight) into top
and bottom holes of return
flange on rear member.
Extend bracket assembly by
sliding front member for-
Rear rack
mounting
rails
M5 screws
ward until it touches the front rack mounting rail. Insert two (2) M5
screws loosely (finger-tight) into top and bottom holes of return
flange on each front member. Make sure bracket assemblies are at
the same mounting height on all four (4) rack mounting rails.
4. Locate eight (8) M4 screws
and eight (8) M4 nuts from
hardware pack in this kit.
Each nut has a locking, nylon
insert that begins gripping
the screw when it is halfway
tight. Make sure to tighten
nut and screw completely to
assure locking action. Fasten
rear member and front
M4 nuts
M4
screws
18" rack
depth
M4 nuts
M4
member together using four
(4) screws and four (4) nuts
per bracket assembly as
shown in the figures at right.
For maximum support,
locate fasteners for each
bracket assembly as far
M4 nuts
screws
apart as possible, depending
on rack depth, while still
joining both members (See
32" rack
depth
M4 nuts
figures at right). Check alignment of bracket assemblies and
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
5. Prepare the UPS or battery
cabinet (the “equipment”) for
rack mounting by following
instructions in the equipment’s
user manual. The equipment
may require additional parts to
be added or parts to be removed
for rack mounting. After it is
prepared, lay equipment in
rack-mounting position. Fasten
inner members from Step 2 to
the equipment on both sides as
shown in the figure at right
with (8) M4 screws provided in
this kit. Make sure retaining
M4
screws
Retaining
latch
UPS or battery
cabinet
Front
M4
screws
latch is near the rear of the equipment (also shown in figure).
6. Open grease packet provided
in this kit. Apply a 1" long
bead of grease four (4) places
inside the bottom, curved
tracks of front members as
shown at right. The grease
will allow the equipment to
slide into the bracket
Apply grease
UPS or
battery
cabinet
Apply
grease
(inside)
assemblies more easily.
CAUTION
!
Lifting equipment into rack may be a two-person job, depending
on weight of equipment. See equipment’s user manual.
into bracket assemblies by inserting top and bottom edges of inner
members into the top and bottom, curved tracks of front members
and sliding the equipment into rack (see figure in Step 6). Ends of
inner members are tapered to allow rear of the equipment to be
angled upward before insertion, if space allows.
Then the rear, bottom edges of inner
members can be placed into front
edge of bottom tracks, and the front of
the equipment can be tipped up into
horizontal position to insert the top
edges of inner members before sliding
the equipment into rack (see figure at
right). The equipment should move smoothly into bracket assem-
blies. If not, recheck alignment of front and rear members from
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
8. Secure front of the equipment to rack mounting rails to prevent
the equipment from sliding out of position. If securing holes are
provided on front of the equipment that align with the center holes
on return flange of front members, you can use the four (4) extra
M5 screws provided in this kit to secure the equipment.
Otherwise, the equipment should be secured to front of rack
mounting rails with four (4) customer-supplied fasteners.
9. To orient the display for
Horizontal overlay
for rack UPS
Vertical
overlay
for
tower
UPS
horizontal viewing, remove the
front plastic bezel by pulling
forward evenly on both sides.
The unit has two front panel
overlays. Remove the outer
overlay (used for tower
installation). This reveals a
horizontally oriented front
panel overlay for rack
mounting. Snap the front bezel
back into place.
BPYAS
USPON
BPYAS
+
–
BTAERY
10. Once the UPS is installed in
the rack, the load may be
connected. Ensure the load
equipment is turned off; plug
all loads into the output
receptacles on the rear of the
UPS.
UPSON
USPationGXT
ACINPUT
+
–
BTAERY
USPationGXT
ACINPUT
11. Plug the UPS into a dedicated
wall receptacle properly
protected by a circuit breaker
or fuse in accordance with national and local electrical codes. Use
a 15 amp rated device for the 500, 700, 1000, or 1500 VA units,
20 amp for the 2000 VA, and 30 amp for the 3000 VA. The wall
receptacle must be grounded.
12. Turn ON the UPS by pressing the ON button; then turn on the
connected load equipment. The UPS is now providing conditioned
power to your equipment.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
4.4
EXTERNAL BATTERY CABINET INSTALLATION
Optional Liebert external battery cabinets may be connected to the UPS
to provide additional battery run time. External battery cabinets are
designed to be placed all on one side of the UPS or stacked beneath the
UPS. There is no limit to the number of external battery cabinets that
can be used but each cabinet will increase the battery recharge time.
CAUTION
!
The external battery cabinet(s) are heavy (see 11.0 -
Specifications). External battery cabinets can be used in
rack-mount or tower configuration. Take proper precautions
when lifting them.
1. Visually inspect the external battery cabinet for freight damage.
Report damage to the carrier and your local dealer or Liebert
representative.
2. For slide rail installations, first remove the top/side fin. Top/side
fin slides forward and then lift up to remove. Optional rack-mount
handles are shipped with the external battery cabinet and may be
installed at this time if desired.
3. Securing hardware and slide rails are sold separately. Contact
your local dealer or Liebert representative for these additional
options and any assistance needed. Fasten the slides into position
with the screws per the instructions included with the slide rails.
4. Use the enclosed support bases for the
tower option to prevent tip-over. One
additional set of support base extensions
ships with each external battery cabinet.
5. Connect the supplied external battery
cabinet cable to the rear of the external
battery cabinet, then to the rear of the
UPS.
6. Turn ON the battery breaker on the
rear of the external battery cabinet.
7. The UPS is now equipped with
additional backup battery run time.
For approximate battery run times,
NOTE
You must use the included Configuration Program to specify
the number of external battery cabinets connected to the UPS.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
5.0 CONTROLS AND INDICATORS
All LEDs illuminated
for illustrative purposes only.
5.1
ON/ALARM SILENCE/MANUAL BATTERY TEST BUTTON
This button controls output power to connected load(s) and has
three functions:
• ON
• Alarm Silence
• Manual Battery Test
ON - Pressing this button will start up the UPS in order to
provide conditioned and protected power.
Alarm Silence - To silence alarms, press this button for at least
one second. After the alarm is silenced, the UPStation GXT 2U
will reactivate the alarm system to alert of additional problems.
NOTE
The LOW BATTERY and BYPASS reminder alarms
CANNOT be silenced.
Manual Battery Test - To initiate a manual battery test,
press the ON button for at least one second while operating
from utility power with no alarm conditions present.
• If only three of the five Battery LEDs illuminate, allow the
UPS to recharge the batteries for 24 hours.
• After 24 hours, retest the batteries.
• After the batteries have been retested, if only three of the
five Battery LEDs illuminate, contact your local dealer, Lie-
bert representative or Liebert Worldwide Support Group.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
5.2
STANDBY/MANUAL BYPASS BUTTON
This button controls output power to connected load(s) and has
dual functions: Standby and Manual Bypass.
CAUTION
!
While the UPS is in Normal Mode operation, pressing
the Standby/ Manual Bypass button once will put the
UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press the
Standby/ Manual Bypass button two distinct times (for
about one second each time) to turn off the UPS.
Perform all necessary shutdown procedures on
connected loads before turning off the UPS.
5.3
LOAD/BATTERY LEVEL INDICATORS (4 GREEN, 1 AMBER)
The load/battery level indicators have dual functions. During normal
mode operation LED indicators display the approximate electrical
load placed upon the UPS; and during battery mode operation LED
indicators display approximate battery capacity.
The UPStation GXT 2U is equipped with automatic and remote bat-
tery test features. The automatic test occurs every 14 days (this option
is user configurable) if utility has not been interrupted. Should the
battery fail this test, the red Fault indicator LED along with the A and
C diagnostic LEDs will illuminate and an alarm will sound (refer to
10.0 - Troubleshooting). The remote test feature functions with
MultiLink 3 software and can remotely initiate the battery test.
5.4
FAULT INDICATOR LED (RED)
The Fault indicator LED is illuminated if the UPS has detected a
problem. Also, one or more of the load/battery level indicators may be
5.5
BYPASS INDICATOR LED (AMBER)
The Bypass indicator LED is illuminated when the UPS is operating
from bypass power. An alarm will sound indicating the UPS detected
a problem, or the manual bypass function has been activated.
5.6
UPS ON INDICATOR LED (GREEN)
The UPS ON indicator LED is illuminated when the UPS inverter is
operating and supplying power to your connected loads.
5.7
BATTERY INDICATOR LED (AMBER)
The Battery indicator LED is illuminated when the UPS is operating
on battery.
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls and Indicators
5.8
AC INPUT INDICATOR LED (GREEN)
The AC Input indicator LED is illuminated when utility power is
available and within the input specifications.
5.9
OUTPUT VOLTAGE SELECTION
The Output Voltage is user configurable and is designed to allow
selecting or changing the desired output voltage to match the utility
via the GXT 2U Configuration Program provided with the UPS. The
settings to choose from are 100, 110, 115, 120, and 127 VAC output.
The factory default setting is 120 VAC.
CAUTION
!
Never change the voltage settings while the UPS is ON and
powering connected loads.
NOTE
Setting output voltage to 100 VAC will cause the
UPS unit to be derated (500/700/1000 VA to 90%,
1500/2000/3000 VA to 80% of the VA and Watt
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
6.0 OPERATING INSTRUCTIONS
6.1
NORMAL MODE OPERATION
During normal operation,
utility power provides energy
to the UPS. The filters, power
factor correction circuit and
the inverter process this
power to provide computer
grade power to connected
loads. The UPS maintains
the batteries in a fully
AC INPUT BATTERY UPS ON BYPASS
Normal Mode Operation at 26-50%
charged state.
The four green load level LEDs indicate an approximate level of load
in 25% increments. If the UPS becomes loaded beyond full rating, the
fifth (amber) LED indicator will illuminate and the UPS will sound an
audible alarm. The display template indicates the percentage of load
(26-50% of load shown in the example above) on the UPS output.
6.2
BYPASS MODE OPERATION
Bypass mode occurs when
the OFF button is pressed
once while the UPS is in
Normal Mode. During bypass
operation, utility power
provides energy to the UPS.
The utility power bypasses
the inverter and provides
power for the connected load.
AC INPUT BATTERY UPS ON BYPASS
Bypass Mode Operation at 26-50%
The four green load level LEDs indicate an approximate level of load
in 25% increments. If the UPS becomes loaded beyond full rating, the
fifth (amber) LED indicator will illuminate and the UPS will sound an
audible alarm. The display template indicates the percentage of load
(26-50% of load shown in the example above) on the UPS output.
CAUTION
!
Turning OFF the UPS while in bypass mode will result in loss
of output power.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Operating Instructions
6.3
BATTERY MODE OPERATION
Battery mode occurs in
event of an extreme input
voltage condition or com-
plete utility failure. The
battery system supplies
power through the DC to
DC converter to the
AC INPUT BATTERY UPS ON BYPASS
inverter to generate power
for the connected load.
Battery Mode Operation at 80-61%
During battery mode an alarm sounds every 10 seconds. This will
change to two beeps every 5 seconds when the battery runs low
(approximately 2 minutes remaining, but this is user configurable).
The AC Input LED will extinguish, and the Battery LED will illumi-
nate to warn that a utility problem has occurred. Each battery level
indicator represents a 20% capacity level. As capacity decreases, fewer
For approximate battery run times, refer to 13.0 - Battery Run
Times. The times listed in these tables are approximate based on
resistive load and an ambient temperature of 77°F (25°C). To increase
this time, turn off non-essential pieces of equipment (such as idle com-
puters and monitors) or add the optional external battery cabinet.
CAUTION
!
Turning OFF the UPS while in battery mode will result in loss
of output power.
If the UPS is manually turned OFF, it must be manually restarted
after utility power is restored.
If the UPS is turned OFF by a communication signal or because the
batteries are depleted, it will operate as selected in the configuration
program for Auto-Restart (see 8.1 - GXT 2U Configuration Pro-
6.4
BATTERY RECHARGE MODE
Once utility power is restored, the UPS resumes normal operation. At
this time, the Battery Charger begins recharging.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Communications
7.0 COMMUNICATIONS
7.1
COMMUNICATIONS INTERFACE PORT
The UPStation GXT 2U UPS has a standard DB-9 serial port female
connector located on the rear of the UPS unit. Several signals are pro-
vided on this port and are assigned as follows:
Pin
1
Assignment Description
Low Battery (open collector)
2
UPS TxD (typical RS-232 levels)
UPS RxD (typical RS-232 levels)
Remote Shutdown (5-12VDC, 10-24 mA max); battery operation
Common
3
4
5
6
Remote Shutdown (short to pin 5); all modes of operation
Low Battery (open emitter)
7
8
Utility Fail (open emitter)
9
Utility Fail (open collector)
Pin Assignment
Collector to Emitter*
Open
Collector
6
7
8
9
(+)
330 Ohms
Open
Emitter
(-)
1
2
3
4
5
* Maximum voltage and current on pins 1, 7, 8, and 9 is 60VDC; 10.0 mA.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Communications
7.2
PINS 4 & 5 - REMOTE SHUTDOWN ON BATTERY
1. This pin is functional only when the UPS is in battery mode. If the
UPS is being powered by the utility, Pin 4 will ignore any signal
on this pin.
2. Pin 4 requires a 5-12 VDC signal to shutdown. This normally
comes form the serial port using Liebert’s contact closure cable. It
cannot be used with just a contact closure unless the relay is used
to switch a voltage source. A 5-12 VDC signal for 1.5 seconds or
greater is required to signal a shutdown. Signals for less than 1.5
seconds will be ignored. After Pin 4 receives a shutdown signal for
1.5 seconds, the command cannot be canceled.
3. A battery shutdown signal on Pin 4 will NOT cause an immediate
shutdown. A shutdown signal will start a 2-minute shutdown
timer. The timer cannot be stopped. After 2 minutes, the UPS will
shut down.
4. If the utility returns during the 2-minute timer countdown, the
shutdown timer will continue until the end of 2 minutes and the
UPS will turn OFF. The UPS must remain OFF for at least 10
seconds even if AC input power returns before the UPS turns
OFF. This serves to reset and restart the server.
Whether the UPS turns back ON when power is restored depends on
the auto-restart setting: enabled or disabled.
If the auto-restart is disabled, the UPS will not restart after perform-
ing the 2-minute shutdown delay.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
Communications
7.3
PINS 5 & 6 - ANY-MODE SHUTDOWN
1. Pin 6 of the 9-pin communication connector is used for “Any-Mode
Shutdown” of the UPS output. This control input may be used in
special applications to disable the UPS output power—both
Inverter and Bypass.
2. The Options tab allows the behavior of the Any-Mode Shutdown
feature to be modified. When the program opens, or the REFRESH
button is pressed, the UPS setting is read by the configuration
program and displayed.
7.3.1 Auto-Enable Output
WARNING
!
Note that when this option is selected and the UPS output is
disabled using Pin 6, the UPS output can turn on
automatically and without warning if the Pin 6 connection is
changed.
7.3.2 Pin 6 Logic
WARNING
!
DO NOT CHANGE THIS OPTION from the factory default
setting unless you are ready to install a normally-closed
connection between Pins 5 & 6. This connection must be
maintained to use the UPS or to use the configuration
program again, including the ability to change the UPS
setting back to the default setting using the configuration
program via a serial communication link.
If version 1.6 (or later) is used with an earlier GXT 2U model (with an
earlier UPS firmware version), the Any-Mode Shutdown features can-
not be changed.
If the configuration program is used with an earlier UPS model (with
an earlier UPS firmware version) that does not support the modifica-
tion of these settings, the Options tab will display a reminder of the
factory default settings. These cannot be changed.
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Communications
7.4
UPS INTELLIGENT COMMUNICATIONS
®
The UPStation GXT 2U is equipped with an Intellislot port to pro-
vide advanced communication and monitoring options.
Liebert’s MultiLink software continually monitors the UPS and can
shut down your computer or server in the event of an extended power
failure.
MultiLink can also be configured for use without the serial cable when
the Intellislot SNMP/Web card is installed in the UPS. Additionally,
MultiLink can be configured to coordinate shutdown across the net-
work with other computers running MultiLink when you purchase a
MultiLink License Kit. For more information about the Intellislot
SNMP/Web Card and MultiLink License Kits, visit the Liebert Web
sentative.
Several option cards are available for use in the Intellislot port of the
UPStation GXT 2U.
• The Intellislot SNMP/Web Card provides SNMP and Web-based
monitoring and control of the UPS across the network.
• The Intellislot MultiPort 4 Card allows you to install MultiLink
software on four computers and coordinate shutdown in the event
of a power failure.
• The Intellislot Relay Card provides dry contact relay outputs for
custom-wired applications and delivers support for built-in shut-
down for AS/400 systems.
• The Intellislot USB Card provides communication using built-in
®
®
power management software available on Microsoft Windows
2000/XP platforms.
CAUTION
!
To maintain safety (SELV) barriers and for electromagnetic
compatibility, signal cables should be segregated and run
separate from all other power cables, where applicable.
22
Download from Www.Somanuals.com. All Manuals Search And Download.
Configuration Program
8.0 CONFIGURATION PROGRAM
The configuration program included with the UPStation GXT 2U line
allows modification of several UPS settings that were previously
unavailable or required custom manufacturing. The user manual on
the configuration program disk describes the features available for
modification, as well as default settings.
NOTE
The UPS must be turned off—and not powering connected equip-
ment—before you make any changes to configuration settings.
While the UPS is in Normal Mode operation, press the OFF
button once to put the UPS into Bypass Mode.
Once the UPS is in Bypass Mode operation, press and release
the OFF button two distinct times (for about a second each
time) to turn off the UPS.
8.1
GXT 2U CONFIGURATION PROGRAM ABILITIES
• Select one of five output voltages to match voltages found around
the world.
• Enable/Disable Auto-Restart.
• Select frequency converter operation with a fixed output frequency
of 50 or 60 Hz.
• Set the Low Battery Warning alarm time from 2 to 30 minutes.
• Enable/Disable the Auto-Battery test.
• Set the Auto-Battery test to 7, 14, 21, or 28 days.
• Select the number of external battery cabinets connected to the
UPS to adjust the remaining run time calculations reported by
Liebert software products.
• Modify the shutdown setting of DB-9 pin 6 (for information on pin
NOTE
This program is compatible with UPS models beginning with
“GXT2-”, as in “GXT2-1500RT120.” It is not compatible with
earlier versions of UPStation GXT UPS.
8.1.1 What You Will Need
Using this program requires a
computer running Windows
(95 through Server 2003), as well as the configuration program disk
and serial cable included in the UPS accessory box. Use the serial cable
(beige or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) to
connect the computer to the GXT 2U UPS.
Note: The black ML9P9S contact closure communication cable is NOT
compatible with the configuration program.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
9.0 MAINTENANCE
The UPStation GXT 2U requires very little maintenance. The batter-
ies are valve-regulated, nonspillable, flame retardant, lead acid, and
should be kept charged to obtain their designed life. The UPS continu-
ously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is recommended to
plug the UPS in for at least 24 hours every four to six months to
ensure full recharge of the batteries.
The UPStation GXT 2U is designed to allow the user to safely replace
the internal batteries. Read the safety cautions before proceeding.
Contact your local dealer or Liebert representative to obtain the
appropriate replacement battery kit part number and pricing.
9.1
BATTERY REPLACEMENT
CAUTION
!
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
before replacing the batteries:
• Remove rings, watches, or other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batter-
ies.
• If the battery replacement kit is damaged in any way or
shows signs of leakage, contact your local dealer or Liebert
representative immediately.
• Do not dispose of batteries in a fire. The batteries may
explode.
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
9.1.1 Internal Battery Replacement Procedures
1. Gently remove the front plastic bezel cover from the UPS.
2. Loosen and remove the four screws on the front battery door. Lay
the battery door aside for reassembly.
Note: The 3000VA model includes a pull handle to remove this
door. It has two built-in connectors that disconnect when servicing
the battery. THIS HANDLE MUST BE REINSTALLED IN
ORDER FOR THE UPS TO OPERATE IN BATTERY MODE.
3. Gently pull battery wiring out and disconnect the two slotted
battery connectors.
4. Grasp the battery pack assembly, and pull it out of the front of the
UPS.
5. Unpack the new battery assembly taking care not to destroy the
packing. Compare new and old battery assemblies to make sure
they are the same. If so, proceed with Step 6; otherwise STOP and
contact your local dealer, Liebert representative, or the Liebert
Worldwide Support Group.
6. Line up and slide in the new replacement battery pack.
7. Reconnect the two slotted battery connectors and gently push the
battery wiring and battery pack assembly back into the UPS.
8. Reattach the front battery door with the four screws.
9. Reattach the front plastic bezel cover to the UPS.
NOTE
These are hot-swappable replacement batteries. However,
caution should be exercised because during this procedure the
load is unprotected from disturbances and power outages.
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
9.2
FUSE REPLACEMENT
CAUTION
!
Before changing the input fuse, turn off the UPS, and unplug
the supply lead from the AC input supply. Replace the fuse
with the same type and rating.
1. Remove the input fuse.
2. Locate the spare input fuse
that is included with the
UPS.
3. Insert the spare fuse into the
fuse holder, and reinstall
assembly into the UPS.
Twist by hand; rotate
clockwise until fuse holder
locks into position.
4. Reconnect the input power
cord to input AC supply.
5. Restart the UPS. The UPS is ready for normal operation.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
10.0 TROUBLESHOOTING
The information below indicates various symptoms a user may
encounter in the event the UPStation GXT 2U develops a problem.
Use this information to determine whether external factors caused the
problem and how to remedy the situation.
1. The Fault indicator will illuminate, indicating the UPS detected a
problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illu-
minated to provide a diagnostic aid to the operator, as described below:
This example shows the UPS
Fault
on bypass due to output overload.
E
BYPASS
D
UPS ON
C
B
BATTERY
A
AC
INPUT
A
B
C
D
E
Fault
AC INPUT BATTERY UPS ON BYPASS
LOAD/BATTERY
LEVEL INDICATORS
LED status
All LEDs
A LED
Diagnosis / Audible alarm
On bypass due to output overload; beep every half-second
On bypass due to overtemperature condition; beep every 4 sec.
On bypass due to DC bus overvoltage; beep every 4 sec.
On bypass due to control power supply failure; beep every 4 sec.
On bypass due to PFC failure; beep every 4 sec.
B LED
C LED
D LED
E LED
On bypass due to inverter failure; beep every 4 sec.
A&C LEDs UPS failed battery test; long beep every minute
UPS shutdown due to command from communication port
(SNMP); no beep
C&E LEDs
Battery LED Internal Battery source not available (continuous horn). Check
Flashing
battery connection, completely power down and reboot UPS.
AC LED
Flashing
Line-to-neutral reversal in the AC input power supply or a loss of
proper grounding; continuous horn and UPS will not start.
Bypass LED Utility power voltage or frequency is out of tolerance; bypass is
Flashing unavailable.
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Under fault conditions, the Fault indicators will be illuminated indefi-
nitely while battery charger is operational, or for a maximum of 5 min-
utes while battery charger is not operational.
If a problem persists, consult your local dealer, Liebert representative
or contact the Liebert Worldwide Support Group. Please have the UPS
model number and serial number available at the time of your
inquiry.
Table 1
Troubleshooting guide
Problem
Cause
Solution
Ensure UPS is OFF.
Disconnect all loads and
ensure nothing is lodged in
output receptacles. Ensure
loads are not defective or
shorted internally.
UPS fails to start
when the ON
button is pressed.
UPS is short circuited or
overloaded.
UPS is operating from
battery mode, make certain
UPS is securely plugged
into the wall receptacle.
UPS not plugged in.
UPS is operating from
battery mode. Save data
and close applications.
Replace UPS input fuse,
then restart UPS.
UPS input protection fuse
has blown/opened.
Battery indicator
LED is
illuminated.
UPS is operating from
battery mode. Save data
and close applications.
Ensure utility supply
voltage is within
Utility voltage out of UPS
input range.
acceptable limits for UPS.
Keep UPS plugged in
continuously at least 24
hours to recharge
batteries.
Batteries are not fully
charged.
Check load level display
and reduce the load on the
UPS.
UPS is overloaded.
UPS has reduced
battery time.
Replace batteries. Contact
your local dealer, Liebert
representative or the
Liebert Worldwide Support
Group for replacement
battery kit.
Batteries may not be able
to hold a full charge due to
age.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table 1
Troubleshooting guide (continued)
Problem
Cause
Solution
Check load level display
and remove non-essential
loads. Recalculate the load
and reduce number of
loads connected to UPS.
Check load equipment for
faults.
Fault and Bypass
indicator LEDs
and all load level
LEDs are
UPS overloaded or load
equipment is faulty.
illuminated.
Ensure UPS is not
overloaded, ventilation
openings not blocked, or
room ambient temperature
is not excessive. Wait 30
minutes to allow UPS to
cool, then restart UPS. If
UPS does not restart,
contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
Fault and Bypass
indicator LEDs
and diagnostic
LED A are
UPS internal fan has a
problem or UPS shutdown
due to temperature
condition. Load is on
bypass power.
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED B are
UPS requires service.
Contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
UPS internal DC bus
overvoltage.
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED C are
UPS requires service.
Contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
UPS control power supply
fault.
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED D are
UPS requires service.
Contact your local dealer,
Liebert representative or
the Liebert Worldwide
Support Group.
UPS PFC (Power Factor
Correction Circuit) fault.
illuminated.
Fault and Bypass
indicator LEDs
and diagnostic
LED E are
UPS requires service.
Contact your local dealer,
Liebert Representative or
the Liebert Worldwide
Support Group.
UPS inverter fault.
illuminated.
Fault indicator
LED and
diagnostic LED A
and C are
Replace batteries. Contact
your local dealer, Liebert
representative or the
Liebert Worldwide Support
Group.
UPS failed the battery test.
illuminated.
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table 1
Troubleshooting guide (continued)
Problem
Cause
Solution
Your UPS has received a
signal or command from
the attached computer. If
this was inadvertent,
ensure the communication
cable used is correct for
your system. For
Fault and Bypass
indicator LEDs
and diagnostic
LED C and E are
illuminated.
UPS shutdown due to a
command from the
communications port(s).
assistance, contact your
local dealer, Liebert
representative or the
Liebert Worldwide Support
Group.
UPS detected a line-to-
neutral reversal or a loss of
proper grounding;
continuous horn and UPS
will not start.This is active
only when power is first
applied to the input. Once
the UPS is running, the AC
LED will not start flashing,
even if the input wiring is
changed.
Contact a qualified
electrician to verify site
wiring.
AC LED is
flashing.
Check battery connections,
completely power down
and restart UPS.
NOTE: If the battery circuit
opens while the UPS is
running, it will be detected
when the next battery test
is performed.
Battery LED is
flashing.
Battery source is not
available; continuous horn.
The AC input powers the
PFC input and serves as
the bypass source. If the
AC is present but the
Bypass voltage is present,
but is disabled for use
because the voltage or
frequency is outside
acceptable limits.
voltage or frequency
Bypass LED is
flashing.
exceeds the acceptable
range for safe operation
with a load, the bypass will
be disabled and this LED
will flash, indicating that the
bypass is unavailable.
30
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
Table 2
Alarm conditions
Condition
Alarm
Battery Mode
(utility failure)
One short beep every 10 seconds;
more than 2 minutes of run time remaining
Two short beeps every 5 seconds;
less than 2 minutes of run time remaining
Low Battery
Output Overload
(bypass)
One short beep every half second
A one-second beep every 4 seconds
A one-second beep every 4 seconds
A one-second beep every 4 seconds
Overtemperature
(bypass)
DC Bus Overvoltage
(bypass)
Control Power Supply
Failure (bypass)
PFC Failure (bypass)
Inverter Failure
A one-second beep every 4 seconds
A one-second beep every 4 seconds
A 2-second beep every minute
Battery Test Failure
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
11.0 SPECIFICATIONS
Model Number
GXT2-500RT120
GXT2-700RT120
700VA / 490W
GXT2-1000RT120
1000VA / 700W
Model Rating
500VA/350W
DIMENSIONS - in. (mm)
Unit
W x D x H
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 21.5 x 17
(87 x 547 x 430)
Shipping
W x D x H
10.6 x 27.2 x 23
(269 x 691 x 584)
10.6 x 27.2 x 23
(269 x 691 x 584)
10.6 x 27.2 x 23
(269 x 691 x 584)
WEIGHT - lb. (kg)
Unit
48.9 (22.2)
57.7 (26.2)
48.9 (22.2)
57.7 (26.2)
49.1 (22.3)
57.9 (26.3)
Shipping
INPUT AC PARAMETERS
Voltage Range (typical)
120VAC nominal; variable based on output load
100% - 90% loading
90% -70% loading
70% -30% loading
30% - 0% loading
Frequency
80 VAC - 140 VAC
80 VAC / 140 VAC
80 VAC / 140 VAC
70 VAC / 140 VAC
60 VAC / 140 VAC
40 - 70 Hz; Auto Sensing
6 ft. attached
80 VAC / 140 VAC
80 VAC - 140 VAC
70 VAC - 140 VAC
60 VAC - 140 VAC
80 VAC / 140 VAC
70 VAC / 140 VAC
60 VAC / 140 VAC
6 ft. attached
10 ft. attached
Input Power Cord
w/ NEMA 5-15 plug w/ NEMA 5-15 plug w/ NEMA 5-15 plug
OUTPUT AC PARAMETERS
Output Receptacles
Voltage
(4) NEMA 5-15R
100/110/115/120/127 (user configurable) VAC; ±3%
50 Hz or 60 Hz
Frequency
Waveform
Sinewave
Main Mode
Overload
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
4 x 12V x 7.0 or 7.2 AH
Qty x V x Rating
Battery Mfg / Part #
Backup Time
China Storage Battery / CSB FR 1270 F2
Recharge Time
ENVIRONMENTAL
Operating Temp
Storage Temp
5 hours to 95% capacity after full discharge into 100% load
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
Operating Elevation
Storage Elevation
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
<50 dBA, at 1 meter from the rear
<45 dBA, at 1 meter from the front or sides
Audible Noise
AGENCY
Safety
UL 1778, c-UL Listed (Suitable for computer room applications)
FCC Part 15, Subpart B, Class A
RFI/EMI
Surge Immunity
Transportation
IEEE/ANSI C62.41 Category A & B
ISTA Procedure 1A
32
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Model Number
GXT2-1500RT120
GXT2-2000RT120 GXT2-3000RT120
Model Rating
1500VA / 1050W
2000VA / 1400W
3000VA / 2100W
DIMENSIONS - in. (mm)
Unit
W x D x H
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 24.2 x 17
(87 x 618 x 430)
Shipping
W x D x H
10.6 x 27.2 x 23
(269 x 691 x 584)
10.6 x 27.2 x 23
(269 x 691 x 584)
10.6 x 27.2 x 23
(269 x 691 x 584)
WEIGHT - lb. (kg)
Unit
Shipping
50.6 (23)
59.5 (27)
54 (24)
62.6 (28.4)
69 (31)
78.0 (35.4)
INPUT AC PARAMETERS
Voltage Range (typical)
100% - 90% loading
90% -70% loading
70% -30% loading
30% - 0% loading
Frequency
120 VAC nominal; variable based on output load
90 VAC / 140 VAC
90 VAC / 140 VAC 90 VAC / 140 VAC
80 VAC / 140 VAC 80 VAC / 140 VAC
70 VAC / 140 VAC 70 VAC / 140 VAC
60 VAC / 140 VAC 60 VAC / 140 VAC
40 - 70 Hz; Auto Sensing
80 VAC / 140 VAC
70 VAC / 140 VAC
60 VAC / 140 VAC
10 ft. attached
10 ft. attached
10 ft. attached
Input Power Cord
w/ NEMA 5-15 plug w/ NEMA 5-20 plug w/ NEMA L5-30 plug
OUTPUT AC PARAMETERS
(4) 5-20R T-Slot
(1) NEMA L5-30R
on 12 in cord
(4) 5-20R T-Slot,
accepts 15A plug
Output Receptacles
(4) NEMA 5-15R
Voltage
100/110/115/120/127 (user configurable) VAC; ±3%
Frequency
Waveform
50 Hz or 60 Hz
Sinewave
Main Mode Overload
BATTERY PARAMETERS
Type
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating
4 x 12V x 7.0 or 7.2 AH 4 x 12V x 9.0 AH
China Storage Battery/
CSB FR 1270 F2
6 x 12V x 9.0 AH
Panasonic / UP-VW1245P1
Yuasa / REW 45-12 FR
Battery Mfg / Part #
Backup Time
Recharge Time
ENVIRONMENTAL
Operating Temp
Storage Temp
5 hours to 95% capacity after full discharge into 100% load
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
Relative Humidity
Operating Elevation
Storage Elevation
0% to 95%, non-condensing
Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
50,000 ft. (15,000m) maximum
<50 dBA, at 1 meter
from the rear
<45 dBA, at 1 meter
from the front or sides
<55 dBA, at 1 meter
from the rear
<50 dBA, at 1 meter
from the front or sides
Audible Noise
AGENCY
Safety
RFI/EMI
UL 1778, c-UL Listed (Suitable for computer room applications)
FCC Part 15, Subpart B, Class A
Surge Immunity
Transportation
IEEE/ANSI C62.41 Category A & B
ISTA Procedure 1A
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Battery Cabinet Specifications
12.0 BATTERY CABINET SPECIFICATIONS
Model Number
GXT2-48VBATT
GXT2-72VBATT
GXT2-500RT120
GXT2-700RT120
GXT2-1000RT120
GXT2-1500RT120
GXT2-2000RT120
Used With
UPS Model
GXT2-3000RT120
DIMENSIONS - in. (mm)
Unit
W x D x H
3.5 x 21.5 x 17
(87 x 547 x 430)
3.5 x 24.2 x 17
(87 x 618 x 430)
Shipping
W x D x H
10.5 x 27.2 x 23
(268 x 692 x 585)
10.5 x 27.2 x 23
(268 x 692 x 585)
WEIGHT - lb. (kg)
Unit
65.0 (29.5)
71.1 (32.3)
93.6 (42.5)
Shipping
102.5 (46.5)
BATTERY PARAMETERS
Type
Valve-regulated, nonspillable, flame retardant, lead acid
Qty x V x Rating
2 x 4 x 12V x 7.0 or 7.2 AH
2 x 6 x 12V x 9.0 AH
China Storage Battery /
CSBFR 1270 F2
Panasonic / UP-VW1245P1
Yuasa / REW 45-12 FR
Battery Mfg / Part #
Backup Time
ENVIRONMENTAL
Operating Temp
Storage Temp
+32°F to +104°F (0°C to +40°C)
+5°F to +122°F (-15°C to +50°C)
0% to 95%, non-condensing
Relative Humidity
Operating Elevation Up to 10,000 ft. (3000m) at 104°F (40°C) without derating
Storage Elevation
50,000 ft. (15,000 m) maximum
AGENCY
UL 1778, c-UL Listed
(Suitable for computer room applications)
Safety
RFI/EMI
FCC Part 15, Subpart B, Class A
ISTA Procedure 1A
Transportation
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Battery Run Times
13.0 BATTERY RUN TIMES
Load% 500VA 700VA 1000VA 1500VA 2000VA 3000VA
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
494
181
107
83
66
53
44
36
31
28
248
115
79
58
44
35
29
24
20
191
87
48
34
25
19
16
13
144
53
38
28
20
15
12
10
56
33
26
19
14
12
10
8
7
6
168
99
78
57
42
36
30
24
21
18
392
231
182
133
98
84
70
56
49
91
46
30
21
16
11
9
8
7
5
364
184
120
84
64
44
36
32
Internal
Battery
(minutes)
12
11
8
7
17
1976
726
431
332
267
210
178
150
132
115
3953
1453
862
665
534
421
356
300
265
231
5929
2179
1293
998
801
632
534
450
398
346
7906
2906
1725
1331
1068
843
712
600
525
462
992
460
316
232
176
140
116
96
764
348
192
136
100
76
64
52
48
44
1528
696
384
272
200
152
128
104
96
576
212
152
112
80
60
48
40
32
Internal
Battery
+ 1 External
Battery
Cabinet
(minutes)
80
68
28
20
28
1984
920
632
464
352
280
232
192
160
136
2976
1380
948
696
528
420
348
288
240
204
3968
1840
1264
928
704
560
464
384
320
272
1152
424
304
224
160
120
96
80
64
56
1728
636
456
336
240
180
144
120
96
728
368
240
168
128
88
72
64
56
40
1092
552
360
252
192
132
108
96
Internal
Battery
+ 2 External
Battery
Cabinets
(minutes)
88
42
2292
1044
576
408
300
228
192
156
144
132
3056
1392
768
544
400
304
256
208
192
176
560
330
260
190
140
120
100
80
Internal
Battery
+ 3 External
Battery
Cabinets
(minutes)
70
60
84
60
84
2304
848
608
448
320
240
192
160
128
112
840
495
390
285
210
180
150
120
105
90
1456
736
480
336
256
176
144
128
112
80
Internal
Battery
+ 4 External
Battery
Cabinets
(minutes)
Note: Approximate discharge times are in minutes and at 77°F (25°C) with a 100% resistive load.
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Product Warranty Registration
14.0 PRODUCT WARRANTY REGISTRATION
To register for warranty protection:
• Visit the Quick Links section of our Web site at:
• Click on Product Warranty Registration and fill in the form.
If you have any questions, please contact us at:
US: 800-222-5877
Outside the US: 614-841-6755
36
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
POWER AVAILABILITY
USER MANUAL
UPStation GXT 2U™
Technical Support/Service
The Company
Behind the Products
Web Site
Monitoring
800-222-5877
Outside the US: 614-841-6755
With over a million installations around the
globe, Liebert is the world leader in computer
protection systems. Since its founding in
1965, Liebert has developed a complete
range of support and protection systems for
sensitive electronics:
Single-Phase UPS
800-222-5877
Outside the US: 614-841-6755
•
Environmental systems—close-control
air conditioning from 1 to 60 tons
Power conditioning and UPS with power
ranges from 300VA to more than
1000kVA
Three-Phase UPS
800-543-2378
•
Environmental Systems
800-543-2778
•
Integrated systems that provide both
environmental and power protection in a
single, flexible package
Monitoring and control—from systems
of any size or location, on-site or remote
Service and support through more than
100 service centers around the world
and a 24/7 Customer Response Center
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
•
•
Columbus, OH 43229
Italy
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD)
+39 049 9719 111
While every precaution has been taken to
ensure the accuracy and completeness of
this literature, Liebert Corporation assumes
no responsibility and disclaims all liability for
damages resulting from use of this
Fax: +39 049 5841 257
Asia
23F, Allied Kajima Bldg.
138 Gloucester Road
Wanchai
Hong Kong
+852 2 572 2201
Fax: +852 2 831 0114
information or for any errors or omissions.
© 2005 Liebert Corporation
All rights reserved throughout the world.
Specifications subject to change without
notice.
® Liebert and the Liebert logo are registered
trademarks of Liebert Corporation. All names
referred to are trademarks or registered
trademarks of their respective owners.
SL-23150 (2/05) Rev. 7
Download from Www.Somanuals.com. All Manuals Search And Download.
|