• Addressable conventional technology
• Maximum temperature 75°C
• Individual detector addressing by
means of optional address module
• Optional connection of remote
indicator
• Extremely flat design
• Sealed electronics
Description
The Thermal ROR Detector HT-11003 reacts to tempe- means of the optional Address Module NG60-1, each
rature changes within defined periods of time, up to a detector can be addressed individually, thus allowing to
maximum temperature of 75°C. The intelligent evaluati- display the detector address, as well as an assigned
on of these data allows the early detection of spreading element text, on a suitable fire detection control panel.
fires. The detector complies with Class BR and can be
used up to a room height of 6m.
A detector fault is indicated by a yellow flashing of the
multicoloured status LED.
Addressable conventional technology is used for alarm The detector can be attached to various bases and it
transmission to the fire detection control panel. By can be protected against theft.
Specifications
Operating voltage
Current consumption
Alarm temperature
Operating temperature
Ambient temperature
Relative humidity
Dimensions ø × H
Colour
Supply through the detector line voltage
typ. 65µA (quiescent)
75°C (maximum-heat component)
max. +65°C
-40°C to +80°C (no condensation or icing)
0 – 98% (no condensation)
100 × 36 (mm)
white
Weight
70g
Approval
VdS G204035
Order number
Order name
242032
Thermal ROR Detector/Conv./ORBIS/Apo HT-11003
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
HT-11003_DBL_LST_EN_0804.PDF • PAGE 1
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
Download from Www.Somanuals.com. All Manuals Search And Download.
|