Honeywell Car Amplifier R4140G User Manual

R4140G  
Flame Safeguard Programming Controls  
PRODUCT DATA  
R7247C or R7476A Dynamic Self-Check Amplifier,  
when used with an ultraviolet flame detector with a  
self-checking shutter (R7247C with a C7012E or F;  
R7476A with a C7076), tests all electronic components  
in the flame detection system (amplifier and detector)  
60 to 240 times a minute during burner operation and  
shuts down the burner if the detection system fails.  
R7247B Dynamic Self-Check Amplifier, when used with  
a rectifying flame rod (which is considered fail-safe),  
or R7248B Dynamic Ampli-Check Amplifier, when used  
with a C7015A Infrared (lead sulfide) Flame Detector,  
tests the flame signal amplifier at least 150 times a  
minute during burner operation and shuts down the  
burner if the amplifier fails.  
All models feature capability of proving low fire position  
of the firing rate motor before starting ignition trials.  
Provisions for connecting preignition or start  
interlocks (depending on model) to prove the proper  
conditions for startup, and for a combustion airflow  
switch to prove airflow throughout the operating cycle.  
All models have 4-wire firing rate switching circuitry—  
firing rate can be modulated while the burner is firing,  
and the firing rate motor can be driven to both low and  
high fire positions during prepurge.  
Safe start check at startup and during prepurge. If  
flame relay 2K is holding in at startup, the programmer  
cannot be started. If a flame (or a condition simulating  
a flame) is detected during prepurge, ignition trials  
cannot be started and the programmer recycles.  
Safety shutdown occurs on failure to ignite the pilot or  
main burner, on loss of flame during the Run period,  
or if the flame detection system fails (if a self-checking  
system is used).  
APPLICATION  
The R4140G Flame Safeguard Programmers provide  
flameout protection plus automatic sequencing of the burner  
motor (blower), firing rate motor, ignition, pilot valve, and main  
fuel valve(s) for commercial and industrial burners using gas,  
oil, coal, or a combination of fuels.  
All relays are visible, labeled, and easily accessible.  
Alarm terminal is available to operate an external, line  
voltage alarm on safety shutdown.  
FEATURES  
Approvals: Underwriters Laboratories Inc. listed or  
component recognized, Canadian Standards  
Association certified, and Factory Mutual approved for  
automatic fired burners.  
The R4140 directly replaces the R4150 for most  
applications and mounts on the same Q520A Wiring  
Subbase.  
Low-high-low purge programmers.  
Contents  
Field selectable main burner flame-establishing  
period.  
Application ..........................................................................  
Features ..............................................................................  
Specifications ......................................................................  
Ordering Information ...........................................................  
Operation ............................................................................  
1
1
2
2
6
Early spark termination (five-second ignition and five-  
second pilot only) available on some models.  
Plug-in, solid state, flame signal amplifiers are color-  
coded and interchangeable to allow the use of any  
type of flame detector-flame rod, photocell, infrared  
detector, or ultraviolet detector.  
Amplifier capability includes three standard models,  
three Dynamic Self-Check models, and one Dynamic  
Ampli-Check® model.  
Wiring .................................................................................. 23  
Copyright © 1996 Honeywell Inc.  
All Rights Reserved  
60-2337-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Safety Features:  
NOTE: Allowable inrush can be up to ten times the pilot duty  
rating.  
Safe Start CheckFor the presence of a flame (or a  
condition simulating a flame) provided at startup and  
during prepurge. If the flame relay 2K is pulled in at  
startup, 2K2 is open and the programmer cannot be  
started. If the flame relay 2K pulls in during prepurge  
(before 57.5 seconds), 2K2 opens, relay 1K drops out,  
and ignition trials cannot be started. Instead, the timer  
completes its revolution and stops at the standby position  
(zero seconds). If the flame relay 2K drops out by the end  
of the cycle, the programmer restarts the system.  
Safety ShutdownIgnition transformer and all automatic  
fuel valves de-energize. The lockout switch trips and  
locks out the programmer. If used, the external alarm is  
energized. The timer completes its revolution and locks  
up at the stand-by position (zero seconds). The lockout  
switch must be manually reset to restart the system.  
Safety Shutdown occurs on:  
EXAMPLE: Pilot duty rating = 50 VA.  
At 120V, running current is:  
50  
120  
= 0.42A  
.
Maximum allowable inrush is ten times  
0.42A = 4.2A.  
Interlock Ratings:  
See Table 3.  
Table 3. Interlock Ratings.  
Requirements must be abIe to  
Failure to ignite the pilot (or first stage burner if using  
direct spark ignition).  
Failure to light the main burner (unless monitoring  
an intermittent pilot).  
Interlocks  
carry and break current to:  
Limits, Burner Controller, Ignition transformer, pilot valve,  
and Running Interlocks and main fuel valve(s).  
(including airflow switch)  
Loss of flame during the Run period.  
Failure in the flame detection system (if a self-  
checking system is used, see Table 4).  
Flame Failure Response Time2 to 4 seconds.  
Lockout Switch Timing30 seconds (nominal).  
Start or Preignition  
Interlocks  
Programmer relay 1K (5W max).  
Electrical Ratings:  
Ambient Operating Temperature Ratings:  
Minimum: Minus 40°F (minus 40°C).  
Maximum:  
Voltage and Frequency: 120 Vac (102V minimum to 132V  
maximum), 50/60 Hz.  
R4140G1114: 240 Vac, 60 Hz.  
R4140G1122: 208 Vac, 60 Hz.  
Programmer Mounting Position  
Standard Vertical (With Handle Up)  
Any Other  
+135°F (+57°C)  
NOTE: Use of a 50 Hz power supply lengthens the  
sequence timings by a factor of 1.2.  
+150°F (+66°C)  
Power Consumption (With No Loads Connected to Output  
Terminals): 13W maximum.  
Maximum Total Connected Load: 2000 VA.  
Storage Temperature Ratings:  
Minus 60°F to plus 150°F (minus 51°C to plus 66°C).  
Mounting:  
Terminal Ratings:  
3-sided Q520A1089 Wiring Subbase, or 4-sided Q520A1121  
Wiring Subbase; both have 20 knife-blade contacts (subbase  
ordered separately).  
See Table 2.  
Table 2.Terminal Ratings.  
Maximum Rating at  
Dimensions:  
See Fig. 1 and 2.  
Terminal Typical Load  
120 Vac, 60 Hz  
5 or 6 Ignition  
4.5A ignition and 50 VA pilot duty or  
Transformer/Pilot 2.5A ignition and 75 VA pilot duty  
Weight (Without Plug-in Flame Signal Amplifier and  
202050C Cover):  
4 lb, 12 oz (2.15 kg).  
Valve/First Stage  
Fuel Valve  
Flame Detection System (Ordered Separately):  
Plug-in Flame Signal Amplifier and matching Flame Detector;  
see Table 4.  
7
Main Fuel Valve(s) 250 VA pilot duty or 65 VA pilot duty  
(solenoid/motorized in parallel with motorized valve(s)  
/diaphragm) and using a total of 1150 VA locked  
Vent Valve if  
required  
rotor (inrush),460 VA to open, and  
250 VA to hold or motorized  
valve(s) using a total of 1500 VA  
locked rotor (inrush), 600 VA to  
open, and 250 VA to hold  
Approvals:  
Underwriters Laboratories Inc. Listed Section of Primary  
Safety Control (120V Models With Covers): File No.  
MP268; Guide No. MCCZ.  
Underwriters Laboratories Inc. Component Recognized  
(120V Models Without Covers): File No. MP268; Guide  
No. MCCZ2.  
Canadian Standards Association Certified: File No.  
LR1620.  
8
9
Burner Motor  
(blower)  
9.8A full load, 58.8A locked rotor  
(inrush)  
120V Alarm  
75 VA pilot duty  
50 VA pilot duty  
10, 11, 12,  
and 14  
Firing Rate  
(damper) Motor  
Contacts  
Factory Mutual Approved: Report No. 24180.  
18  
(if available)  
Ignition  
Transformer  
4.5A ignition  
3
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
LOCKOUT SWITCH  
RESET BUTTON  
47/64  
(19)  
2-3/8 (60)  
2-11/32 (60)  
35/64  
(14)  
202050C COVER  
2-5/64  
(53)  
1-51/64  
(46)  
7/8 (22) DIAMETER KNOCKOUT (2)  
13/64 (5) DIAMETER (4)  
3/8 (10) (4)  
(FOR MOUNTING ON  
4 X 4 [102 X 102] JUNCTION BOX)  
5/8 (16) (4)  
6-1/2  
(165)  
3
4
5
6
L1  
L2  
12  
13  
F
18  
17  
16  
15  
14  
9
7
3-3/8  
(86)  
10  
8
11  
G
6-5/32  
(156)  
7-3/16 (183)  
202050C COVER  
1-3/4  
(45)  
6
7/8 (22) DIAMETER  
KNOCKOUT (2)  
(152)  
31/32  
15/16  
1
(25) (2)  
(24) (2)  
5-7/8  
(149)  
1-27/32  
(47)  
3-3/8 (86)  
7 -1/16 (179)  
5-5/8  
(143)  
7-3/16 (183)  
31/32  
(25)  
1-13/32 (36)  
2-11/32 (60)  
1-13/32 (36)  
M6777  
1-3/4  
(45)  
(ON Q520A1089 3-SIDED WIRING SUBBASE)  
3/4  
(19)  
Fig. 2. Mounting dimensions of the R4140 Programmer  
on the Q520A wiring subbase in in. (mm).  
7/8 (22) DIAMETER KNOCKOUT (4)  
OPEN ON 3-SIDED Q520A1089.  
1
M6776  
Fig. 1. Mounting dimensions of the Q520A  
wiring subbase in in. (mm).  
4
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Accessories:  
R1298020 Cable; for flame detector (F lead-wire)  
installations in a high temperature environment; rated  
up to 400°F (204°C) for continuous duty; tested for  
operation up to 600V and breakdown up to 7500V.  
R1239001 High Tension Ignition Cable; for ignition  
installations in a contaminating environment; very  
resistant to severe conditions of oil, heat, and corona,  
and tested to withstand high voltages up to  
25,000V rms in a salt bath for one minute without  
breakdown; rated at 200°F (93°C) for continuous duty,  
and up to 350°F (197°C) for intermittent use.  
Q624A Solid State Spark Generator; prevents detection of  
ignition spark when properly applied with flame  
detection systems using C7027, C7035, or C7044  
Minipeeper Ultraviolet Flame Detectors. For use only  
with gas pilots.  
W136A Test Meter (includes 117053 Meter Connector  
Plug); has SPL position with damping for testing self-  
checking flame detection systems.  
117053 Meter Connector Plug (for older W136A models).  
123514A Flame Simulator (for use with R7247A  
Rectification Amplifiers).  
123514B Flame Simulator (for use with R7249A Ultraviolet  
Amplifiers).  
139695C (Series 1 and 2) Cover with reset button; heavy  
duty, metal cover for outside panel mounting.  
202050C (Series 3) Cover with reset button; heavy duty,  
metal cover for outside panel mounting.  
118760B (Series 1 and 2) Remote Reset Cover; heavy  
duty, metal cover with remote reset assembly; 120V,  
60 Hz solenoid.  
202051B (Series 3) Remote Reset Cover; heavy duty,  
metal cover with remote reset assembly; 120V, 60 Hz  
solenoid.  
R1061012 Ignition Cable; for ignition installations in a high  
temperature environment; rated at 350°F (177°C) for  
continuous duty, and up to 500°F (260°C) for  
intermittent use; tested to 25,000V.  
FSP5004 Tester; provides a quick operational check of  
most R4140 Flame Safeguard Programming Controls.  
Q520E1002 Service Tool; allows any of the programmer  
terminals to be monitored while the programmer is  
operating.  
Table 4. Flame Detection Systems  
NOTE: Neither the R414G1114 or the R4140G1122 can be used with the C7012E or F Purple Peeper Ultraviolet Flame  
Detector and with the R7247C Dynamic Self-Check Amplifier.  
Plug-In Flame Signal Amplifiers  
Self-  
Applicable Flame Detectors  
Flame Failure  
Type  
Color Checking  
Model  
Response Time Fuel  
Type  
Rectifying  
Models  
Rectification Green  
No  
R7247A  
2 to 4 sec  
Gas  
Holdersa: C7004, C7007, C7011.  
Flame Rods Complete assemblies: C7005,  
C7008, C7009, Q179.  
R7247A,  
R7247Bb  
2 to 4 sec  
Oil  
Rectifying  
Photocells  
C7003, C7010, C7013, C7014.  
c
Gas,  
Oil,  
Coal  
Ultraviolet  
(Purple  
Peeper)  
C7012A or C.  
Dynamic R7147Bb  
Self-  
Check  
2 to 4 sec  
2 to 4 sec  
2 to 4 sec  
2 to 4 sec  
Gas  
Rectifying  
Holdersa: C7004, C7007, C7011.  
Flame Rods Complete Assemblies: C7005,  
C7008, C7009, Q179.  
R7247Cd  
Gas,  
Oil,  
Coal  
Ultraviolet  
(Purple  
Peeper)  
C7012E or F  
C7015.  
Infrared  
Red  
No  
R7248A  
Gas,  
Oil,  
Coal  
Infrared  
(Lead  
Sulfide)  
Dynamic R7248Bb  
Ampli-  
Gas,  
Oil,  
Infrared  
(Lead  
C7015.  
Check®  
Coal  
Sulfide)  
Ultraviolet  
Purple  
Blue  
No  
R7249A  
2 to 4 sec  
2 to 4 sec  
Gas,  
Oil  
Ultraviolet  
(Minipeeper)  
C7027, C7035, C7044.  
C7076.  
Dynamic R7476Ad  
Self-  
Check  
Gas,  
Oil,  
Coal  
Ultraviolet  
(Adjustable  
Sensitivity)  
a Order flame rod separately; see Instructions for the holder.  
b Circuitry tests the flame signal amplifier at least 150 times a minute during burner operation and shuts down the burner if the  
amplifier fails.  
c Use only Honeywell part no. 38316 Photocell.  
d Circuitry tests all electronic components in the flame detection system (amplifier and detector) 60 to 240 times a minute during  
burner operation and shuts down the burner if the detection system fails.  
5
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
OPERATION  
Models with Preignition Interlocks  
Fig. 3 shows all contacts in the standby position (zero  
to each timer contact. Refer to Fig. 4 and the Step-by-Step  
Operation section.  
seconds). The opening and closing times are shown adjacent  
120V, 60 HZ  
POWER SUPPLY  
R4140G1007/G1015 SCHEMATIC  
(WITH/WITHOUT HEAVY DUTY COVER)  
L2  
L1  
(HOT)  
1
INTERNAL  
EXTERNAL  
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.  
A TIMER CONTACTS SNAP CLOSED.  
B CONTACTS SNAP OPEN.  
OOPENING TIME  
CCLOSING TIME  
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER  
MASTER  
SWITCH  
L1  
L2  
1
2
NUMBERS BELOW  
DESIGNATE LINE  
LOCATIONS OF  
RELAY CONTACTS.  
(UNDERLINE  
INDICATES A  
NORMALLY CLOSED  
CONTACT.)  
3
9
13  
5
8
12  
10  
3
FLAME SIGNAL  
METER JACK  
G
F
4
PLUG-IN AMPLIFIER  
5
FLAME  
DETECTOR  
6
M11B  
M9A  
7
1K  
11  
TO  
16  
17  
C-15 O-70  
C-57.5 O-109.5  
2K - 13, 9, 8  
1K - 14, 14, 11  
7
17  
2K  
TERMINAL  
TIP JACK  
M7A  
2
8
8
LS2  
2K3  
9
LS - 19, 9  
M7B  
M2B  
O-70  
C-113.5  
2K2  
C-57.5 O-111  
BURNER  
O-9.5 C-116  
LS HTR  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
LIMITS  
CONTROLLER  
1K3  
3
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
4
16  
3
5
M4A  
C-60  
O-85  
M6B  
C-50 O-80  
PREIGNITION  
INTERLOCKS  
RUNNING  
INTERLOCKS  
(INCLUDING  
AIRFLOW SWITCH)  
4
2K1  
30 SECOND  
INTERRUPTED  
PILOT/IGNITION  
6
1K1  
1K2  
M2A  
C-70  
5
7
M5B  
O-104  
C-108  
O-109.5  
MAIN FUEL  
VALVES (S)  
M3A  
TEST  
NORM  
13  
O-52 C-66  
M1B  
C-4  
8
LOW FIRE  
SWITCH  
TIMER SWITCH  
O-120  
TIMER MOTOR  
BURNER MOTOR  
(BLOWER)  
LS1  
120 V ALARM  
9
HIGH FIRE  
10  
B
R
B
R
M10A C-4 O-41  
COMMON  
11  
M10B O-4 C-45  
MODULATE  
12  
W
W
M8B O-100 C-116  
M8A C-100 O-112  
LOW FIRE  
14  
FIRING  
RATE  
SERIES 90  
CONTROLLER  
MOTOR  
6
3
4
5
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F  
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING  
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17  
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C  
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK  
DIAGRAM OF FIELD WIRING.  
FOR DIRECT SPARK IGNITION (GAS OR OIL,) A JUMPER IS INSTALLED  
BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM  
OF FIELD WIRING FOR HOOKUP.  
6
USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.  
M10149  
Fig. 3. Simplified schematic diagram of R4140G1015 Programmer.  
6
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
110  
120  
6
PREIGNITION INTERLOCKS  
PREPURGE  
5
RUN  
RUNNING INTERLOCKS (PROVEN AIRFLOW)  
PERIOD  
MAIN  
IGN  
PURGE  
TIMER DIAL  
PILOT  
TIMER  
MOTOR  
3
5
BURNER  
MOTOR  
(BLOWER)  
8
1
5
6
10 SECONDS  
30 SECONDS  
INTERRUPTED  
PILOT/IGNITION  
MAIN FUEL  
VALVE(S)  
(GAS OR OIL)  
7
HIGH FIRE POSITION  
MODULATE  
12 TO 11  
FIRING RATE  
MOTOR  
LOW FIRE POSITION  
14 TO 11  
1
10 TO 11  
SWITCHING  
LOW  
LOW  
2
2
2
2
ACTUAL  
DAMPER  
OPERATION  
4
MOTOR  
DRIVES  
DAMPER  
CLOSED  
MOTOR  
DRIVES  
DAMPER  
OPEN  
3
MOTOR DRIVES  
DAMPER CLOSED  
1
2
3
TERMINAL NUMBERS (CIRCLED).  
SLOPE DEPENDS ON MOTOR TIMING.  
TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.  
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90  
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN  
PERIOD WHILE BURNER IS FIRING).  
4
5
6
TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE  
BURNER FIRING.  
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)  
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.  
M10054  
Fig. 4.Timer sequence for R4140G1015 Programmer.  
and ignition trials cannot be started. Running interlocks  
must remain closed through the Run period or the  
system shuts down; the timer completes its revolution  
and recycles the programmer.  
Step-By-Step Operation (R4140G1015)  
Start And Prepurge  
0 secondsOn a call for heat, the burner controller  
contacts close. If the limits and preignition interlocks  
are closed and flame relay 2K is not holding in, relay 1K  
pulls in through M7B, LS2, 2K2, and the LS HTR  
(lockout switch heaterthus proving its continuity).  
15 secondsM11B closes; flame relay 2K can pull in if a  
flame (or a condition simulating a flame) is detected. If  
detected during prepurge (until 57.5 seconds), 2K pulls  
in, 2K2 opens, 1K drops out, and the system shuts  
down; the timer completes its revolution and recycles  
the programmer (if 2K dropped out).  
45 secondsM10B closes; firing rate motor drives toward  
low fire position (closed).  
52 secondsM3A opens; timer stops until the low fire  
proving switch closes; timer can be stopped by opening  
the timer switch (until 66 seconds when M3A closes  
again).  
1K1 closes and 1K2 opens, timer motor starts  
(through 1K1, M3A, and M5B), power is applied to  
terminal 8, starting the burner motor (blower); 1K3  
closes.  
Prepurge begins.  
4 secondsM10A closes, M10B opens; firing rate motor  
drives toward high fire position (open).  
M1B closes, bypassing 1K1; the timer can complete  
its revolution if shutdown occurs.  
9.5 secondsM7B opens; running interlocks must close  
(airflow must be proven) or 1K drops out, 1K3 opens,  
57.5 secondsM9A closes; the LS HTR (lockout switch  
heater) begins heating in preparation for ignition trials.  
M7A closes, bypassing the preignition interlocks.  
7
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Ignition Trials  
Run Period (Burner is Firing)  
60 secondsM4A closes; power is applied to terminals 5  
Postpurge And Stop  
and 6, energizing the ignition transformer and pilot  
valve (or main fuel valve(s) on terminal 7 if using direct  
spark ignition).  
104 secondsWhen the operating setpoint is reached, the  
burner controller contacts open; relay 1K and the main  
fuel valve(s) (terminal 7) de-energize.  
When a flame is detected, relay 2K pulls in, 2K2  
opens, and the LS HTR stops heating; 2K1 and  
2K3 close.  
1K2 closes; timer motor starts; postpurge begins.  
When the flame goes out, relay 2K drops out.  
112 secondsM8A opens; firing rate motor stops  
modulating under control of the Series 90 Controller.  
116 secondsM8B closes; firing rate motor drives toward  
low fire position (closed).  
120 secondsM1B opens; timer and burner motor stop;  
cycle ends.  
66 secondsM3A closes, bypassing the low fire switch  
and the timer switch.  
70 secondsM2B opens; pilot or ignition trial ends; a  
flame must be detected by this time (2K pulled in and  
2K1 closed) or safety shutdown occurs and the lockout  
switch trips.  
M2A closes; power is applied to terminal 7,  
energizing the main fuel valve(s).  
M11B opens; prevents 2K from pulling in after this  
time.  
Fig. 5 shows all contacts in the standby position (zero  
seconds). The opening and closing times are shown adjacent  
to each timer contact. Refer to Fig. 6 and the Step-by-Step  
Operation section.  
80 secondsM6B opens; 10 second interrupted pilot/  
ignition (terminal 5) is de-energized.  
100 secondsM4A opens; 30 second interrupted pilot/  
ignition (terminal 6) is de-energized.  
M8A closes, M8B opens; firing rate motor is  
released to modulate under control of the Series 90  
Controller.  
104 secondsM5B opens; timer stops with the system in  
the Run condition.  
8
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
120V, 60 HZ  
POWER SUPPLY  
R4140G1106 SCHEMATIC  
L2  
L1  
(HOT)  
1
INTERNAL  
EXTERNAL  
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.  
A TIMER CONTACTS SNAP CLOSED.  
B CONTACTS SNAP OPEN.  
OOPENING TIME  
CCLOSING TIME  
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER  
MASTER  
SWITCH  
1
2
L1  
L2  
NUMBERS BELOW  
3
9
13  
5
8
12  
10  
DESIGNATE LINE  
LOCATIONS  
3
RELAY CONTACTS.  
(UNDERLINE  
INDICATES A  
NORMALLY CLOSED  
CONTACT.)  
FLAME SIGNAL  
METER JACK  
G
F
4
PLUG-IN AMPLIFIER  
5
FLAME  
DETECTOR  
6
M11B  
7
M9A  
C-57.5 O-109.5  
1K  
11  
TO  
16  
17  
C-15 O-70  
2K - 16, 10, 8  
1K - 17, 17, 12  
7
17  
8
2K  
2
8
TIP JACK  
M7A  
LS2  
2K3  
9
LS - 22, 8  
M7B  
O-9.5 C-116  
M2B  
O-70  
C-113.5  
2K2  
C-57.5 O-111  
BURNER  
LS HTR  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
LIMITS  
CONTROLLER  
8
1K3  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
4
16  
3
5
M4A  
C-60  
O-85  
3
7
M6B  
C-50 O-80  
PREIGNITION  
INTERLOCKS  
RUNNING  
INTERLOCKS  
(INCLUDING  
9
2K1  
15 SECOND  
INTERRUPTED  
PILOT/IGNITION  
6
AIRFLOW SWITCH)  
1K1  
1K2  
M2A  
C-70  
O-109.5  
M5B  
O-104  
C-108  
MAIN FUEL  
VALVES (S)  
7
4
M3A  
TEST  
NORM  
13  
O-52 C-66  
M1B  
C-4  
B
LOW FIRE  
SWITCH  
5
TIMER SWITCH  
O-120  
TIMER MOTOR  
BURNER  
MOTOR  
LS1  
ALARM  
9
HIGH FIRE  
10  
B
R
B
R
M10A C-4 O-41  
COMMON  
11  
M10B O-4 C-45  
MODULATE  
12  
W
W
M8B O-100 C-116  
M8A C-100 O-112  
LOW FIRE  
14  
FIRING  
RATE  
MOTOR  
SERIES 90  
CONTROLLER  
6
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED  
1
2
TIMER SWITCH IS SHOWN IN "NORM" POSITION; IT IS OPEN IN "TEST"  
POSITION.  
5
6
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F  
USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.  
PURPLE PEPPER ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING  
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17  
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C  
DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK DIAGRAM  
OF FIELD WIRING.  
7
FOR DIRECT SPARK IGNITION (OIL OR GAS), A JUMPER IS INSTALLED  
BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK  
DIAGRAM OF FIELD WIRING FOR HOOKUP.  
8
9
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
15 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
3
4
FOR DIRECT SPARK IGNITION OR OIL, REFER TO SAMPLE BLOCK DIAGRAM  
OF FIELD WIRING FOR HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.  
SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT  
OR OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S).  
M10044  
Fig. 5. Simplified schematic diagram of R4140G1106 Programmer.  
9
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
110  
120  
6
PREIGNITION INTERLOCKS  
PREPURGE  
RUN  
PERIOD  
RUNNING INTERLOCKS (PROVEN AIRFLOW)  
MAIN  
IGN  
PURGE  
TIMER DIAL  
PILOT  
TIMER  
MOTOR  
3
5
BURNER  
MOTOR  
(BLOWER)  
8
1
5
6
10 SECONDS  
15 SECONDS  
INTERRUPTED  
PILOT/IGNITION  
MAIN FUEL  
VALVE(S)  
(GAS OR OIL)  
7
HIGH FIRE POSITION  
MODULATE  
12 TO 11  
FIRING RATE  
MOTOR  
LOW FIRE POSITION  
14 TO 11  
1
10 TO 11  
SWITCHING  
LOW  
LOW  
2
2
2
2
ACTUAL  
DAMPER  
OPERATION  
4
MOTOR  
DRIVES  
DAMPER  
CLOSED  
MOTOR  
DRIVES  
DAMPER  
OPEN  
3
MOTOR DRIVES  
DAMPER CLOSED  
1
2
3
TERMINAL NUMBERS (CIRCLED).  
SLOPE DEPENDS ON MOTOR TIMING.  
TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.  
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90  
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN  
PERIOD WHILE BURNER IS FIRING).  
4
5
6
TIMER STOPS AT 164 SECONDS FOR THE RUN PERIOD WITH  
THE BURNER FIRING.  
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)  
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.  
M10052  
Fig. 6.Timer sequence for R4140G1106 Programmer.  
Step-By-Step Operation (R4140G1106)  
Start and Prepurge  
0 secondsOn a call for heat, the burner controller  
contacts close. If the limits and preignition interlocks  
are closed and flame relay 2K is not holding in, relay 1K  
pulls in through M7B, LS2, 2K2, and the LS HTR  
(lockout switch heaterthus proving its continuity).  
or the system shuts down; the timer completes its  
revolution and recycles the programmer.  
15 secondsM11B closes; flame relay 2K can pull in if a  
flame (or a condition simulating a flame) is detected. If  
detected during prepurge (until 57.5 seconds), 2K pulls  
in, 2K2 opens, 1K drops out, and the system shuts  
down; the timer completes its revolution and recycles  
the programmer (if 2K dropped out).  
1K1 closes and 1K2 opens; timer motor starts  
(through 1K1, M3A, and M5B); power is applied to  
terminal 8, starting the burner motor (blower); 1K3  
closes.  
45 secondsM10B closes; firing rate motor drives toward  
low fire position (closed).  
Prepurge begins.  
4 secondsM10A closes, M10B opens; firing rate motor  
52 secondsM3A opens; timer stops until the low fire  
proving switch closes; timer can be stopped by opening  
the timer switch (until 66 seconds when M3A closes  
again).  
drives toward high fire position (open).  
M1B closes, bypassing 1K1; the timer can  
complete its revolution if shutdown occurs.  
9.5 secondsM7B opens; running interlocks must be  
closed (airflow must be proven) or 1K drops out, 1K3  
opens, and ignition trials cannot be started. Running  
interlocks must remain closed through the Run period  
57.5 secondsM9A closes; the LS HTR (lockout switch  
heater) begins heating in preparation for ignition trials.  
M7A closes, bypassing the preignition interlocks.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Ignition Trials  
Run Period (Burner is Firing)  
60 secondsM4A closes; power is applied to terminals 5  
and 6, energizing the ignition transformer and pilot  
valve (or main fuel valve(s) on terminal 7 If using direct  
spark ignition).  
Postpurge and Stop  
104 secondsWhen the operating setpoint is reached, the  
burner controller contacts open; relay 1K and the main  
fuel valve(s) (terminal 7) are de-energized.  
When a flame is detected, relay 2K pulls in, 2K2  
opens, and the LS HTR stops heating; 2K1 and  
2K3 close.  
1K2 closes; timer motor starts; postpurge begins.  
When the flame goes out, relay 2K drops out.  
112 secondsM8A opens; firing rate motor stops  
modulating under control of the Series 90 Controller.  
116 secondsM8B closes; firing rate motor drives toward  
low fire position (closed).  
120 secondsM1B opens; timer and burner motor stop;  
cycle ends.  
66 secondsM3A closes, bypassing the low fire switch  
and the timer switch.  
70 secondsM2B opens; pilot or ignition trial ends; a  
flame must be detected by this time (2K pulled in and  
2K1 closed) or safety shutdown occurs and the lockout  
switch trips.  
M2A closes; power is applied to terminal 7,  
energizing the main fuel valves(s).  
M11B opens; prevents 2K from pulling in after this  
time.  
Models with Start Interlocks  
Fig. 7 shows all contacts in the standby position (zero  
seconds). The opening and closing times are shown adjacent  
to each timer contact. Refer to Fig. 8 and the Step-by-Step  
Operation section.  
80 secondsM6B opens; 10 second interrupted pilot/  
ignition (terminal 5) de-energizes.  
85 secondsM4A opens; 15 second interrupted pilot/  
ignition (terminal 6) de-energizes.  
100 secondsM8A closes, M8B opens; firing rate motor is  
released to modulate under control of the Series 90  
Controller.  
104 secondsM5B opens; timer stops with the system in  
the run condition.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
120V, 60 HZ  
POWER SUPPLY  
R4140G1049 SCHEMATIC  
(WITH/WITHOUT HEAVY DUTY COVER)  
L2  
L1  
(HOT)  
1
INTERNAL  
EXTERNAL  
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.  
A TIMER CONTACTS SNAP CLOSED.  
B CONTACTS SNAP OPEN.  
OOPENING TIME  
CCLOSING TIME  
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER  
MASTER  
SWITCH  
L1  
L2  
1
2
NUMBERS BELOW  
DESIGNATE LINE  
LOCATIONS OF  
RELAY CONTACTS.  
(UNDERLINE  
INDICATES A  
NORMALLY CLOSED  
CONTACT.)  
3
9
13  
5
8
12  
10  
3
FLAME SIGNAL  
METER JACK  
G
F
4
PLUG-IN AMPLIFIER  
5
FLAME  
DETECTOR  
6
M11B  
C-15 O-70  
7
11  
TO  
TERMINAL  
8
16  
17  
7
M9A  
C-57.5 O-111  
1K  
17  
2K  
2K - 16, 10, 8  
1K - 17, 17, 12  
TIP JACK  
2
8
2K3  
BURNER  
CONTROLLER  
START  
INTERLOCK(S)  
9
LIMITS  
3
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
16  
4
LS - 22, 8  
M7B  
2K2  
O-9.5 C-116  
LS HTR  
5 SECOND  
IGNITION  
3
18  
M2B  
O-70  
C-113.5  
1K3  
M9B  
C-30  
O-65  
RUNNING INTERLOCKS  
(INCLUDING AIRFLOW SWITCH)  
5
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
M4A  
C-60  
O-85  
M6B  
C-50 O-80  
2K1  
6
30 SECOND  
INTERRUPTED  
PILOT/IGNITION  
6
1K1  
1K2  
M2A  
C-70  
O-109.5  
7
7
M5B  
O-104  
C-108  
MAIN FUEL  
VALVES (S)  
M3A  
TEST  
NORM  
O-52 C-66  
M1B  
C-4  
O-120  
13  
8
LOW FIRE  
SWITCH  
TIMER SWITCH  
TIMER MOTOR  
BURNER MOTOR  
(BLOWER)  
LS1  
120 V ALARM  
9
HIGH FIRE  
10  
B
R
B
R
M10A C-4 O-41  
COMMON  
11  
M10B O-4 C-45  
MODULATE  
12  
W
W
M8B O-100 C-116  
M8A C-100 O-112  
LOW FIRE  
14  
FIRING  
RATE  
MOTOR  
SERIES 90  
CONTROLLER  
8
IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED  
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.  
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
4
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F  
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING  
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17  
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C  
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK  
DIAGRAM OF FIELD WIRING.  
5
6
7
FOR DIRECT SPARK IGNITION (GAS OR OIL), A JUMPER IS INSTALLED  
BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM  
OF FIELD WIRING FOR HOOKUP.  
TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.  
3
USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.  
8
M10155  
Fig. 7. Simplified schematic diagram of R4140G1049 Programmer.  
12  
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
6
110  
120  
5
RUN  
PERIOD  
RUNNING INTERLOCKS (PROVEN AIRFLOW)  
IGN  
MAIN  
PURGE  
TIMER DIAL  
PREPURGE  
PILOT  
TIMER  
MOTOR  
3
5
BURNER  
MOTOR  
(BLOWER)  
8
1
18  
5 SECOND  
IGNITION  
5
6
10 SECONDS  
30 SECONDS  
INTERRUPTED  
PILOT/IGNITION  
MAIN FUEL  
VALVE(S)  
(GAS OR OIL)  
7
HIGH FIRE POSITION  
MODULATE  
FIRING RATE  
MOTOR  
SWITCHING  
LOW FIRE POSITION  
12 TO 11  
1
10 TO 11  
LOW  
LOW  
2
14 TO 11  
2
2
2
ACTUAL  
DAMPER  
OPERATION  
4
MOTOR  
DRIVES  
DAMPER  
CLOSED  
MOTOR  
DRIVES  
DAMPER  
OPEN  
3
MOTOR DRIVES  
DAMPER CLOSED  
1
2
3
TERMINAL NUMBERS (CIRCLED).  
SLOPE DEPENDS ON MOTOR TIMING.  
TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.  
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90  
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN  
PERIOD WHILE BURNER IS FIRING).  
4
5
6
TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE  
BURNER FIRING.  
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)  
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.  
M10055  
Fig. 8.Timer sequence for R4140G1049 Programmer.  
Step-By-Step Operation (R4140G1049)  
Start and Prepurge  
0 secondsOn a call for heat, the burner controller  
contacts close. If the limits and start interlock(s) are  
closed and flame relay 2K is not holding in, relay 1K  
pulls in through M7B, 2K2, the LS HTR (lockout switch  
heaterthus proving its continuity), and LS2.  
interlocks must remain closed through the Run period  
or the system shuts down; the timer completes its  
revolution and recycles the programmer.  
15 secondsM11B closes; flame relay 2K pulls in if a  
flame (or a condition simulating a flame) is detected. If  
detected during prepurge (until 57.5 seconds), 2K pulls  
in, 2K2 opens, 1K drops out, and the system shuts  
down; the timer completes its revolution and recycles  
the programmer (if 2K dropped out).  
1K1 closes and 1K2 opens; timer motor starts  
(through 1K1, M3A, and M5B); power is applied to  
terminal 8, starting the burner motor (blower); 1K3  
closes.  
Prepurge begins.  
45 secondsM10B closes; firing rate motor drives toward  
low fire position (closed).  
4 secondsM10A closes, M10B opens; firing rate motor  
drives toward high fire position (open).  
52 secondsM3A opens; timer stops until the low fire  
proving switch closes; timer can be stopped by opening  
the timer switch (until 66 seconds when M3A closes  
again).  
57.5 secondsM7A closes; the LS HTR (lockout switch  
heater) begins heating in preparation for ignition trials.  
M1B closes, bypassing 1K1; the timer can  
complete its revolution if shutdown occurs.  
9.5 secondsM7B opens; running interlocks must be  
closed (airflow must be proven) or 1K drops out, 1K3  
opens, and ignition trials cannot be started. Running  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Ignition Trials  
Run Period (Burner is Firing)  
60 secondsM4A closes; power is applied to terminals  
Postpurge and Stop  
18, 5, and 6, energizing the ignition transformer and  
pilot valve (or main fuel valve(s) on terminal 7 if using  
direct spark ignition).  
104 secondsWhen the operating setpoint is reached, the  
burner controller contacts open; relay 1K and the main  
fuel valve(s) (terminal 7) de-energize.  
When a flame is detected, relay 2K pulls in, 2K2  
opens, and the LS HTR stops heating; 2K1 and  
2K3 close.  
1K2 closes; timer motor starts; postpurge begins.  
When the flame goes out, relay 2K drops out.  
112 secondsM8A opens; firing rate motor stops  
modulating under control of the Series 90 Controller.  
116 secondsM8B closes; firing rate motor drives toward  
low fire position (closed).  
120 secondsM1B opens; timer and burner motor stop;  
cycle ends.  
65 secondsM9B opens; 5 second ignition (terminal 18)  
is de-energizes (pilot only until 70 seconds).  
66 secondsM3A closes, bypassing the low fire switch  
and the timer switch.  
70 secondsM2B opens; pilot or ignition trial ends; a  
flame must be detected by this time (2K pulled in and  
2K1 closed) or safety shutdown occurs and the lockout  
switch trips.  
Fig. 9 shows all contacts in the standby position (zero  
seconds). The opening and closing times are shown adjacent  
to each timer contact. Refer to Fig. 10 and the Step-by-Step  
Operation section.  
M2A closes; power is applied to terminal 7,  
energizing the main fuel valve(s).  
M11B opens; prevents 2K from pulling in after this  
time.  
80 secondsM6B opens; 10 second interrupted pilot/  
ignition (terminal 5) de-energizes.  
100 secondsM4A opens; 30 second interrupted pilot/  
ignition (terminal 6) de-energizes.  
M8A closes, M8B opens; firing rate motor is  
released to modulate under control of the  
Series 90 Controller.  
104 secondsM5B opens; timer stops with the system in  
the run condition.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
120V, 60 HZ  
POWER SUPPLY  
R4140G1056/G1064 SCHEMATIC  
(WITH/WITHOUT HEAVY DUTY COVER)  
L2  
L1  
(HOT)  
1
INTERNAL  
EXTERNAL  
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.  
A TIMER CONTACTS SNAP CLOSED.  
B CONTACTS SNAP OPEN.  
OOPENING TIME  
CCLOSING TIME  
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER  
MASTER  
SWITCH  
L1  
L2  
1
2
NUMBERS BELOW  
DESIGNATE LINE  
LOCATIONS OF  
RELAY CONTACTS.  
(UNDERLINE  
INDICATES A  
NORMALLY CLOSED  
CONTACT.)  
3
9
13  
5
8
12  
10  
3
FLAME SIGNAL  
METER JACK  
G
F
4
PLUG-IN AMPLIFIER  
5
FLAME  
DETECTOR  
6
M11B  
C-15 O-70  
7
11  
TO  
TERMINAL  
8
16  
17  
2K - 16, 10, 8  
1K - 17, 17, 12  
7
M7A  
C-57.5 O-111  
1K  
17  
2K  
TIP JACK  
2
8
2K3  
LS2  
BURNER  
CONTROLLER  
START  
INTERLOCK(S)  
9
LIMITS  
3
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
16  
4
LS - 22, 8  
M7B  
2K2  
O-9.5 C-116  
LS HTR  
5 SECOND  
IGNITION  
3
18  
M2B  
O-70  
C-113.5  
1K3  
M9B  
C-30  
O-65  
RUNNING INTERLOCKS  
(INCLUDING AIRFLOW SWITCH)  
5
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
6
M4A  
C-60  
O-110  
M6B  
C-50 O-80  
2K1  
INTERMITTENT  
PILOT/IGNITION  
6
1K1  
1K2  
M2A  
C-70  
O-109.5  
M5B  
O-104  
C-108  
MAIN FUEL  
VALVES (S)  
7
M3A  
TEST  
NORM  
O-52 C-66  
M1B  
C-4  
O-120  
13  
8
LOW FIRE  
SWITCH  
TIMER SWITCH  
TIMER MOTOR  
BURNER MOTOR  
(BLOWER)  
LS1  
120V ALARM  
9
HIGH FIRE  
B
R
B
R
10  
11  
12  
14  
M10A C-4 O-41  
COMMON  
MODULATE  
LOW FIRE  
M10B O-4 C-45  
W
W
M8B O-100 C-116  
M8A C-100 O-112  
FIRING  
RATE  
MOTOR  
SERIES 90  
CONTROLLER  
7
IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED  
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.  
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
4
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F  
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING  
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17  
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C  
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK  
DIAGRAM OF FIELD WIRING.  
5
6
FOR DIRECT SPARK IGNITION (GAS OR OIL), REFER TO SAMPLE  
BLOCK DIAGRAM OF FIELD WIRING FOR HOOKUP.  
USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.  
7
M10156  
TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.  
3
Fig. 9. Simplified schematic diagram of the R4140G1056 and R4140G1064 Programmers.  
15  
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
6
110  
120  
5
RUN  
PERIOD  
RUNNING INTERLOCKS (PROVEN AIRFLOW)  
IGN  
MAIN  
PURGE  
TIMER DIAL  
PREPURGE  
PILOT  
TIMER  
MOTOR  
3
5
BURNER  
MOTOR  
8
18  
5
1
(BLOWER)  
5 SECOND  
IGNITION  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
INTERMITTENT PILOT  
OR 1ST STAGE  
FUEL VALVE  
6
7
MAIN FUEL  
VALVE(S)  
(GAS OR OIL)  
HIGH FIRE POSITION  
MODULATE  
FIRING RATE  
MOTOR  
SWITCHING  
LOW FIRE POSITION  
12 TO 11  
1
10 TO 11  
LOW  
LOW  
2
14 TO 11  
2
2
2
ACTUAL  
DAMPER  
OPERATION  
4
MOTOR  
DRIVES  
DAMPER  
CLOSED  
MOTOR  
DRIVES  
DAMPER  
OPEN  
3
MOTOR DRIVES  
DAMPER CLOSED  
1
2
3
TERMINAL NUMBERS (CIRCLED).  
SLOPE DEPENDS ON MOTOR TIMING.  
TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES.  
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90  
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN  
PERIOD WHILE BURNER IS FIRING).  
4
5
6
TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE  
BURNER FIRING.  
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)  
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.  
M10056  
Fig. 10.Timer sequence for R4140G1056 and R4140G1064 Programmers.  
Step-By-Step Operation  
(R4140G1056 and R4140G1064)  
opens, and ignition trials cannot be started. Running  
Start and Prepurge  
interlocks must remain closed through the Run period  
or the system shuts down; the timer completes its  
revolution and recycles the programmer.  
0 secondsOn a call for heat, the burner controller  
contacts close. If the limits and start interlock(s) are  
closed and flame relay 2K is not holding in, relay 1K  
pulls in through M7B, 2K2, the LS HTR (lockout switch  
heaterthus proving its continuity), and LS2.  
15 secondsM11B closes; flame relay 2K can pull in if a  
flame (or a condition simulating a flame) is detected If  
detected during prepurge (until 57.5 seconds), 2K pulls  
in, 2K2 opens, 1K drops out, and the system shuts  
down; the timer completes its revolution and recycles  
the programmer (if 2K dropped out).  
45 secondsM10B closes; firing rate motor drives toward  
low fire position (closed).  
52 secondsM3A opens; timer stops until the low fire  
proving switch closes; timer can be stopped by opening  
the timer switch (until 66 seconds when M3A closes  
again).  
1K1 closes and 1K2 opens; timer motor starts  
(through 1K1, M3A, and M5B); power is applied to  
terminal 8, starting the burner motor (blower); 1K3  
closes.  
Prepurge begins.  
4 secondsM10A closes, M10B opens; firing rate motor  
drives toward high fire position (open).  
M1B closes, bypassing 1K1; the timer can  
complete its revolution if shutdown occurs.  
9.5 secondsM7B opens; running interlocks must be  
57.5 secondsM7A closes; the LS HTR (lockout switch  
heater) begins heating in preparation for ignition trials.  
closed (airflow must be proven) or 1K drops out, 1K3  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Ignition Trials  
Run Period (Burner is Firing)  
60 secondsM4A closes; power is applied to terminals  
18, 5, and 6, energizing the ignition transformer and  
pilot valve (or first stage fuel valve when using direct  
spark ignition).  
Postpurge and Stop  
104 secondsWhen the operating setpoint is reached, the  
burner controller contacts open; relay 1K, intermittent  
pilot or first stage fuel valve (terminal 6), and the main  
fuel valve(s) (terminal 7) de-energize.  
When a flame is detected, relay 2K pulls in, 2K2  
opens, and the LS HTR stops heating; 2K1 and  
2K3 close.  
1K2 closes; timer motor starts; postpurge begins.  
When the flame goes out, relay 2K drops out.  
65 secondsM9B opens; 5 second ignition (terminal 18)  
de-energizes (pilot only until 70 seconds).  
66 secondsM3A closes, bypassing the low fire switch  
and the timer switch.  
112 secondsM8A opens; firing rate motor stops  
modulating under control of the Series 90 Controller.  
116 secondsM8B closes; firing rate motor drives toward  
low fire position (closed).  
70 secondsM2B opens; pilot or ignition trial ends; a  
flame must be detected by this time (2K pulled in and  
2K1 closed) or safety shutdown occurs and the lockout  
switch trips.  
120 secondsM1B opens; timer and burner motor stop;  
cycle ends.  
Fig. 11 shows all contacts in the standby position (zero  
seconds). The opening and closing times are shown adjacent  
to each timer contact. Refer to Fig. 12 and the Step-by-Step  
Operation section.  
M2A closes; power is applied to terminal 7,  
energizing the main fuel valve(s).  
M11B opens; prevents 2K from pulling in after this  
time.  
80 secondsM6B opens; 10 second interrupted pilot/  
ignition (terminal 5) de-energizes.  
100 secondsM8A closes, M8B opens; firing rate motor is  
released to modulate under control of the Series 90  
Controller.  
104 secondsM5B opens; timer stops with the system in  
the run condition.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
120V, 60 HZ  
POWER SUPPLY  
L2  
L1  
(HOT)  
1
INTERNAL  
EXTERNAL  
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.  
A TIMER CONTACTS SNAP CLOSED.  
B CONTACTS SNAP OPEN.  
OOPENING TIME  
CCLOSING TIME  
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER  
MASTER  
SWITCH  
L1  
L2  
1
2
NUMBERS BELOW  
DESIGNATE LINE  
LOCATIONS OF  
RELAY CONTACTS.  
(UNDERLINE  
INDICATES A  
NORMALLY CLOSED  
CONTACT.)  
3
9
13  
5
8
12  
10  
3
FLAME SIGNAL  
METER JACK  
G
F
4
PLUG-IN AMPLIFIER  
5
FLAME  
DETECTOR  
6
M11B  
C-15 O-70  
7
11  
TO  
TERMINAL  
8
16  
17  
7
2K - 8, 10, 16  
1K - 12, 17, 17  
M7A  
C-67 O-168  
1K  
17  
2K  
TIP JACK  
2
8
LS2  
2K3  
BURNER  
CONTROLLER  
START  
INTERLOCK(S)  
9
LIMITS  
3
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
16  
4
LS - 8, 22,  
M7B  
2K2  
O-13.5 C-174  
LS HTR  
18  
5 SECOND  
IGNITION  
3
M2B  
O-80  
C-169  
1K3  
M9B  
M6B  
RUNNING INTERLOCKS  
(INCLUDING AIRFLOW SWITCH)  
C-40 O-75  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
M4A  
C-70  
O-110  
C-60 O-90  
2K1  
30 OR 60 SECOND  
INTERRUPTED  
PILOT/IGNITION  
6
7
1K1  
1K2  
5
5
M12B  
C-90  
O-140  
6
M5B  
O-155  
C-164  
MAIN FUEL  
VALVES (S)  
7
M3A  
M2A C-80  
O-163  
TEST  
NORM  
O-60 C-76  
M1B  
C-6  
O-180  
13  
8
LOW FIRE  
SWITCH  
TIMER SWITCH  
8
TIMER MOTOR  
BURNER MOTOR  
(BLOWER)  
LS1  
120V ALARM  
9
HIGH FIRE  
B
R
B
R
10  
11  
12  
14  
M10A C-5 O-34  
COMMON  
MODULATE  
LOW FIRE  
M10B O-5 C-40  
W
W
M8B O-148 C-174  
M8A C-148 O-168  
FIRING  
RATE  
MOTOR  
SERIES 90  
CONTROLLER  
9
A JUMPER IS INSTALLED ON THE BACK OF THE PROGRAMMER TO OBTAIN 60  
SECOND INTERRUPTED PILOT/IGNITION AT TERMINAL 6; WITHOUT JUMPER,  
IT IS 30 SECONDS.  
5
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR  
F OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING  
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17  
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C  
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE  
BLOCK DIAGRAM OF FIELD WIRING.  
FOR DIRECT SPARK IGNITION OF OIL, A JUMPER IS INSTALLED BETWEEN  
TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM OF FIELD WIRING FOR  
HOOKUP OF IGNITION AND MAIN OIL VALVE SOLENOID.  
6
7
SOME AUTHORITIES HAVING JURISDICTION PROHIBIT THE WIRING OF ANY LIMIT OR  
OPERATING CONTACTS IN SERIES WITH THE MAIN FUEL VALVE(S).  
TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.  
3
4
8
9
TIMER SWITCH IS SHOWN IN NORM POSITION; IT IS OPEN IN TEST POSITION.  
IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED  
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.  
USE A SERIES 90 MODULATING MOTOR.  
M10158  
Fig. 11. Simplified schematic diagram of R4140G1171, R4140G122 and R4140G1114 Programmers.  
18  
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
110  
120  
130  
140  
150  
160  
170  
180  
6
RUNNING INTERLOCKS (PROVEN AIRFLOW)  
MAIN  
IGN  
PREPURGE  
PURGE  
TIMER DIAL  
PILOT  
TIMER MOTOR  
5
3
BURNER  
MOTOR  
(BLOWER)  
8
1
5 SECOND  
INGITION  
18  
10 SECONDS  
5
6
6
INTERRUPTED  
PILOT/INGITION  
30 SECONDS (WITHOUT JUMPER)  
60 SECONDS (WITH JUMPER)  
MAIN FUEL  
VALVE(S)  
(GAS OR OIL)  
7
HIGH FIRE POSITION  
MODULATE  
12 TO 11  
LOW FIRE POSITION  
14 TO 11  
1
10 TO 11  
LOW  
LOW  
2
2
2
2
ACTUAL  
DAMPER  
4
MOTOR  
DRIVES  
DAMPER  
OPEN  
MOTOR  
DRIVES  
DAMPER  
CLOSED  
OPERATION  
MOTOR DRIVES  
DAMPER CLOSED  
3
3
1
TERMINAL NUMBERS (CIRCLED).  
SLOPE DEPENDS ON MOTOR TIMING.  
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90  
CONTROLLER FROM 148 TO 168 SECONDS (INCLUDING RUN  
PERIOD WHILE BURNER IS FIRING).  
4
2
3
5
6
TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING  
SWITCH CLOSES.  
TIMER STOPS FOR THE RUN PERIOD WITH THE BURNER FIRING.  
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)  
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.  
M10057  
Fig. 12.Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmers.  
Step-By-Step Operation  
(R4140G1171, R4140G1122 and R4140G1114)  
Start and Prepurge  
0 secondsOn a call for heat, the burner controller contacts  
close. If the limits and start interlock(s) are closed, relay  
1K pulls in through M7B, 2K2, the LS HTR (lockout  
switch heaterthus proving its continuity), and LS2.  
down; the timer completes its revolution and recycles  
the programmer.  
13.5 secondsM7B opens; running interlocks must be  
closed (airflow must be proven) or 1K drops out, 1K3  
opens, and ignition trials cannot be started. Running  
interlocks must remain closed through the Run period  
or the system shuts down; the timer completes its  
revolution and recycles the programmer.  
1K1 closes and 1K2 opens; timer starts (through  
M3A and M5B); power is applied to terminal 8,  
starting the burner motor (blower); 1K3 closes.  
Prepurge begins.  
5 secondsM10A closes, M10B opens; firing rate motor  
drives toward high fire position (open).  
6 secondsM1B closes, bypassing 1K1; the timer  
completes its revolution if shutdown occurs.  
10 secondsM11B closes; flame relay 2K can pull in if a  
flame (or a condition simulating a flame) is detected. If  
detected during prepurge (until 67 seconds), 2K pulls  
in, 2K2 opens, 1K drops out, and the system shuts  
40 secondsM10B closes; firing rate motor drives toward  
low fire position (closed).  
60 secondsM3A opens; timer stops until the low fire  
proving switch closes; timer can be stopped by opening  
the timer switch (until 76 seconds when M3A closes  
again).  
67 secondsM7A closes; the LS HTR (lockout switch  
heater) begins heating in preparation for ignition trials.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
148 secondsM8A closes, M8B opens; firing rate motor is  
released to modulate under control of the Series 90  
Controller.  
155 secondsM5B opens; timer stops with the system in  
the Run condition.  
Ignition Trials  
70 secondsM4A closes; power is applied to terminals  
18, 5 and 6, energizing the ignition transformer and  
pilot valve (and terminal 7, main oil valve solenoid, if  
using direct spark ignition of oil).  
When flame is detected, relay 2K pulls in, 2K2  
opens, and the LS HTR stops heating; 2K1 and  
2K3 close.  
Run Period (Burner is Firing)  
Postpurge and Stop  
75 secondsM9B opens; 5 second ignition (terminals 18)  
de-energizes (pilot only until 80 seconds).  
76 secondsM3A closes, bypassing the low fire switch  
and the timer switch.  
155 secondsWhen the operating setpoint is reached, the  
burner controller contacts open; relay 1K and the main  
fuel valve(s) (terminal 7) de-energizes.  
80 secondsM2B opens; pilot or ignition trial ends; flame  
must be detected by this time (2K pulled in and 2K1  
closed) or safety shutdown occurs and the lockout  
switch trips.  
1K2 closes; timer motor starts; postpurge begins.  
When flame goes out, relay 2K drops out.  
168 secondsM8A opens; firing rate motor stops  
modulating under control of the Series 90 Controller.  
174 secondsM8B closes; firing rate motor drives toward  
low fire position (closed).  
180 secondsM1B opens; timer and burner motor stop;  
cycle ends.  
M2A closes; power is applied to terminal 7,  
energizing the main fuel valve(s).  
M11B opens; prevents 2K from pulling in after this  
time.  
90 secondsM6B opens; 10 second interrupted pilot/  
ignition (terminal 5) de-energizes.  
110 secondsM4A opens; 30 second interrupted pilot/  
ignition (terminal 6) de-energizes if jumper was not  
installed on back of programmer.  
Fig. 13 shows all contacts in the standby position (zero  
seconds). The opening and closing times are shown adjacent  
to each timer contact. Refer to Fig. 14 and the Step-by-Step  
Operation section.  
140 secondsM12B opens; 60 second interrupted pilot/  
ignition (terminal 6) de-energizes if jumper was installed  
on back of programmer.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
120V, 60 HZ  
POWER SUPPLY  
R4140G1148 SCHEMATIC  
(WITH/WITHOUT HEAVY DUTY COVER)  
L2  
L1  
(HOT)  
1
INTERNAL  
EXTERNAL  
UNDERLINED O OR C DENOTES SNAP ACTION OF CONTACT.  
A TIMER CONTACTS SNAP CLOSED.  
B CONTACTS SNAP OPEN.  
OOPENING TIME  
CCLOSING TIME  
LS DENOTES LOCKOUT SWITCH; HTR DENOTES HEATER  
MASTER  
SWITCH  
L1  
L2  
1
2
NUMBERS BELOW  
DESIGNATE LINE  
LOCATIONS OF  
RELAY CONTACTS.  
(UNDERLINE  
INDICATES A  
NORMALLY CLOSED  
CONTACT.)  
3
9
13  
5
8
12  
10  
3
FLAME SIGNAL  
METER JACK  
G
F
4
PLUG-IN AMPLIFIER  
5
FLAME  
DETECTOR  
6
M11B  
C-15 O-70  
7
11  
TO  
TERMINAL  
8
16  
17  
7
2K - 16, 10, 8  
1K - 17, 17, 12  
M9A  
C-57.5 O-111  
1K  
17  
2K  
TIP JACK  
2
8
LS2  
2K3  
BURNER  
CONTROLLER  
START  
INTERLOCK(S)  
9
LIMITS  
3
4
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
16  
4
LS - 22, 8  
M7B  
2K2  
O-9.5 C-116  
LS HTR  
18  
5 SECOND  
IGNITION  
3
M2B  
O-70  
C-113.5  
1K3  
M9B  
C-30 O-65  
RUNNING INTERLOCKS  
(INCLUDING AIRFLOW SWITCH)  
5
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
M4A  
C-60  
O-85  
M6B  
C-50 O-80  
2K1  
6
15 SECOND  
INTERRUPTED  
PILOT/IGNITION  
6
1K1  
1K2  
M2A  
C-70  
O-109.5  
7
7
M5B  
O-104  
C-108  
MAIN FUEL  
VALVES (S)  
M3A  
TEST  
NORM  
O-52 C-66  
M1B  
C-4  
O-120  
13  
8
LOW FIRE  
SWITCH  
TIMER SWITCH  
TIMER MOTOR  
BURNER MOTOR  
(BLOWER)  
LS1  
120V ALARM  
9
HIGH FIRE  
10  
B
R
B
R
M10A C-4 O-41  
COMMON  
11  
M10B O-4 C-45  
MODULATE  
12  
W
W
M8B O-100 C-116  
M8A C-100 O-112  
LOW FIRE  
14  
FIRING  
RATE  
MOTOR  
SERIES 90  
CONTROLLER  
8
IF START INTERLOCK(S) IS NOT USED, A JUMPER IS INSTALLED  
BETWEEN TERMINALS 16 AND 4 ON THE WIRING SUBBASE.  
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION  
AS REQUIRED.  
1
2
4
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
15 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
TERMINAL 17 IS USED ONLY TO DRIVE THE SHUTTER ON A C7012E OR F  
OR A C7076A ULTRAVIOLET FLAME DETECTOR WITH SELF-CHECKING  
FEATURE. POWER TO DRIVE THE SHUTTER IS APPLIED TO TERMINAL 17  
FROM TERMINAL 8 THROUGH A SOLID STATE SWITCH IN THE R7247C  
OR R7476A DYNAMIC SELF-CHECK AMPLIFIER. REFER TO SAMPLE BLOCK  
DIAGRAM OF FIELD WIRING.  
5
6
7
FOR DIRECT SPARK IGNITION (GAS OR OIL), A JUMPER IS INSTALLED  
BETWEEN TERMINALS 6 AND 7. REFER TO SAMPLE BLOCK DIAGRAM  
OF FIELD WIRING FOR HOOKUP.  
TERMINAL 16, ON THE WIRING SUBBASE ONLY, IS USED AS A TIE POINT.  
3
USE A SERIES 90 MODULATING MOTOR IF MODULATION IS REQUIRED.  
M10157  
8
Fig. 13. Simplified schematic diagram of R4140G1148 Programmer.  
21  
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
6
110  
120  
5
RUN  
PERIOD  
RUNNING INTERLOCKS (PROVEN AIRFLOW)  
IGN  
MAIN  
PURGE  
TIMER DIAL  
PREPURGE  
PILOT  
TIMER  
MOTOR  
3
5
BURNER  
MOTOR  
(BLOWER)  
8
1
18  
5 SECOND  
IGNITION  
5
6
10 SECONDS  
15 SECONDS  
INTERRUPTED  
PILOT/IGNITION  
MAIN FUEL  
VALVE(S)  
(GAS OR OIL)  
7
HIGH FIRE POSITION  
MODULATE  
FIRING RATE  
MOTOR  
SWITCHING  
LOW FIRE POSITION  
12 TO 11  
1
10 TO 11  
LOW  
LOW  
2
14 TO 11  
2
2
2
ACTUAL  
DAMPER  
OPERATION  
4
MOTOR  
DRIVES  
DAMPER  
CLOSED  
MOTOR  
DRIVES  
DAMPER  
OPEN  
3
MOTOR DRIVES  
DAMPER CLOSED  
1
2
3
TERMINAL NUMBERS (CIRCLED).  
FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90  
CONTROLLER FROM 100 TO 112 SECONDS (INCLUDING RUN  
PERIOD WHILE BURNER IS FIRING).  
4
SLOPE DEPENDS ON MOTOR TIMING.  
5
6
TIMER STOPS AT 52 SECONDS UNTIL LOW FIRE PROVING  
SWITCH CLOSES.  
TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE  
BURNER FIRING.  
RUNNING INTERLOCKS (INCLUDING THE AIRFLOW SWITCH)  
MUST REMAIN CLOSED THROUGH THE RUN PERIOD.  
M10058  
Fig. 14.Timer sequence for R4140G1148 Programmer.  
Step-By-Step Operation (R4140G1148)  
Start and Prepurge  
0 secondsOn a call for heat, the burner controller  
contacts close. If the limits and start interlock(s) are  
closed and flame relay 2K is not holding in, relay 1K  
pulls in through M7B, 2K2, the LS HTR (lockout switch  
heaterthus proving its continuity), and LS2.  
interlocks must remain closed through the Run period  
or the system shuts down; the timer completes its  
revolution and recycles the programmer.  
15 secondsM11B closes; flame relay 2K can pull in if a  
flame (or a condition simulating a flame) is detected. If  
detected during prepurge (until 57.5 seconds), 2K pulls  
in, 2K2 opens, 1K drops out, and the system shuts  
down; the timer completes its revolution and recycles  
the programmer (if 2K drops out).  
1K1 closes and 1K2 opens; timer motor starts  
(through 1K1, M3A, and M5B); power is applied to  
terminal 8, starting the burner motor (blower); 1K3  
closes.  
Prepurge begins.  
45 secondsM10B closes; firing rate motor drives toward  
low fire position (closed).  
4 secondsM10A closes, M10B opens; firing rate motor  
drives toward high fire position (open).  
52 secondsM3A opens; timer stops until the low fire  
proving switch closes; timer can be stopped by opening  
the timer switch (until 66 seconds when M3A closes  
again).  
57.5 secondsM7A closes; the LS HTR (lockout switch  
heater) begins heating in preparation for ignition trials.  
M1B closes, bypassing 1K1; the timer can  
complete its revolution if shutdown occurs.  
9.5 secondsM7B opens; running interlocks must be  
closed (airflow must be proven) or 1K drops out, 1K3  
opens, and ignition trials cannot be started. Running  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
Ignition Trials  
Run Period (Burner is Firing)  
60 secondsM4A closes; power is applied to terminals  
18, 5 and 6, energizing the ignition transformer and  
pilot valve (or main fuel valve(s) on terminal 7 if using  
direct spark ignition).  
Postpurge and Stop  
104 secondsWhen the operating setpoint is reached, the  
burner controller contacts open; relay 1K and the main  
fuel valve(s) (terminal 7) de-energizes.  
When a flame is detected, relay 2K pulls in, 2K2  
opens, and the LS HTR stops heating; 2K1 and  
2K3 close.  
1K2 closes; timer motor starts; postpurge begins.  
When the flame goes out, relay 2K drops out.  
112 secondsM8A opens; firing rate motor stops  
modulating under control of the Series 90 Controller.  
116 secondsM8B closes; firing rate motor drives toward  
low fire position (closed).  
120 secondsM1B opens; timer and burner motor stop;  
cycle ends.  
65 secondsM9B opens; 5 second ignition (terminal 18)  
de-energizes (pilot only until 70 seconds).  
66 secondsM3A closes, bypassing the low fire switch  
and the timer switch.  
70 secondsM2B opens; pilot or ignition trial ends; a  
flame must be detected by this time (2K pulled in and  
2K1 closed) or safety shutdown occurs and the lockout  
switch trips.  
WIRING (FIG. 15 AND 16)  
M2A closes; power is applied to terminal 7,  
energizing the main fuel valve(s).  
M11B opens; prevents 2K from pulling in after this  
time.  
CAUTION  
1. Disconnect power supply before beginning wiring  
to prevent electrical shock and equipment  
damage.  
80 secondsM6B opens; 10 second interrupted pilot/  
ignition (terminal 5) de-energizes.  
85 secondsM4A opens; 15 second interrupted pilot/  
ignition (terminal 6) de-energizes.  
100 secondsM8A closes, M8B opens; firing rate motor is  
released to modulate under control of the Series 90  
Controller.  
2. Wiring must comply with all applicable local  
electrical codes, ordinances, and regulations.  
3. All wiring must be NEC Class 1 (line voltage).  
104 secondsM5B opens; timer stops with the system in  
the run condition.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
IGNITION  
TRANSFORMER  
5
JUMPER  
TO  
L2  
6
7
MAIN FUEL  
VALVE (S)  
2
WIRING  
SUBBASE  
TERMINAL  
STRIP (4)  
RUNNING  
INTERLOCKS  
(INCLUDING  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
AIRFLOW SWITCH)  
3
5
3
PREIGNITION  
INTERLOCK(S)  
5
6
30 (OR 15) SECOND  
INTERRUPTED  
PILOT/IGNITION  
18  
BURNER  
4
LIMITS  
L1  
L2  
12  
4
9
CONTROLLER  
120V ALARM  
MAIN FUEL  
VALVE(S)  
17  
16  
7
8
9
BURNER MOTOR  
(BLOWER)  
HIGH FIRE  
10  
11  
15  
14  
LOW FIRE  
SWITCH  
COMMON  
G
13  
F
RECTIFYING FLAME  
ROD, RECTIFYING  
PHOTOCELL, OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
B
B
6
R
W
R
MODULATE  
LOW FIRE  
OR  
W
WHITE  
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
BLUE  
BLUE  
SERIES 90  
CONTROLLER  
SERIES 90  
FIRING RATE  
MOTOR  
OR  
C7012A,C,E,F  
OR C7076A  
ULTRAVIOLET  
FLAME DETECTOR  
YELLOW  
1
7
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
WHITE  
WHITE  
MASTER  
SWITCH  
10  
L2  
BLACK  
BLACK  
L1  
L2  
7
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
1
C7012 OR C7076 MUST BE RATED FOR 120 V, 60Hz. TWO DETECTORS  
WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO  
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR  
INSTRUCTIONS, SEE FORM NUMBERS: 60-2046 FOR C7012A,C MODELS  
WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON  
TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR  
THE C7076A.)  
7
2
3
4
USE ALL NEC CLASS 1 WIRING.  
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD.  
30 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD (MBFEP) ON  
THE R4140G1007 and R4140G1015 MODELS; 15 SECOND MBFEP ON  
THE R4140G1106 MODEL.  
8
WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER  
ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A  
ADJUSTABLE SENSITIVITY ULTRAVIOLET FLAME DETECTORS DO NOT  
HAVE LEADWIRES.  
FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION  
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE INSET.  
5
6
FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER  
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A  
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE  
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION  
60-2306 FOR DETAILED INSTRUCTIONS.)  
TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING  
9
C7012E,F OR C7076A FLAME DETECTORS.  
M10131  
Fig. 15. Sample block diagram of field wiring for R4140G1007, R4140G1015 and R4140G1106 Programmers.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
ON MODELS WITH INTERMITTENT  
PILOT/IGNITION ON TERMINAL 6.  
FOR DIRECT SPARK IGNITION (OIL OR GAS)  
ON MODELS WITH INTERRUPTED  
PILOT/IGNITION ON TERMINAL 6  
IGNITION  
TRANSFORMER  
IGNITION  
5
5
TRANSFORMER  
JUMPER  
1ST STAGE  
FUEL VALVE  
6
7
TO  
L2  
TO  
L2  
6
MAIN FUEL  
VALVE (S)  
2ND STAGE FUEL  
VALVE (OPTIONAL)  
7
5 SECOND IGNITION  
2
WIRING  
(EARLY SPARK  
TERMINATION)  
4
SUBBASE  
TERMINAL  
STRIP (4)  
RUNNING  
INTERLOCKS  
(INCLUDING  
10 SECOND  
INTERRUPTED  
PILOT/IGNITION  
AIRFLOW SWITCH)  
5
5
3
START  
3
INTERLOCK(S)  
7
6
18  
PILOT/IGNITION  
BURNER  
CONTROLLER  
6
LIMITS  
L1  
L2  
12  
4
MAIN FUEL  
VALVE(S)  
17  
16  
7
8
4
11  
ALARM  
9
BURNER MOTOR  
(BLOWER)  
12  
HIGH FIRE  
10  
11  
15  
14  
LOW FIRE  
SWITCH  
COMMON  
G
13  
F
RECTIFYING FLAME  
ROD, RECTIFYING  
PHOTOCELL, OR  
INFRARED  
(LEAD SULFIDE)  
FLAME DETECTOR  
B
R
B
8
R
MODULATE  
LOW FIRE  
OR  
W
W
WHITE  
C7027A, C7035A, OR  
C7044A ULTRAVIOLET  
FLAME DETECTOR  
BLUE  
BLUE  
SERIES 90  
CONTROLLER  
SERIES 90  
FIRING RATE  
MOTOR  
OR  
C7012A,C,E,F  
OR C7076A  
ULTRAVIOLET  
FLAME DETECTOR  
YELLOW  
1
9
L1 (HOT)  
L2  
120V, 60 HZ  
POWER  
SUPPLY  
WHITE  
WHITE  
MASTER  
SWITCH  
10  
L2  
BLACK  
BLACK  
L1  
L2  
9
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD  
PROTECTION AS REQUIRED.  
1
8
9
FOR THE C7015A INFRARED (LEAD SULFIDE) FLAME DETECTOR, EITHER  
LEADWIRE CAN BE CONNECTED TO THE F TERMINAL. RUN THE C7015A  
LEADWIRES ALONE IN CONDUIT ALL THE WAY TO THE WIRING SUBBASE  
AND GROUND THE CONDUIT AT THE SUBBASE. (REFER TO PUBLICATION  
60-2306 FOR DETAILED INSTRUCTIONS.)  
2
3
USE ALL NEC CLASS 1 WIRING.  
IF START INTERLOCK(S) IS NOT USED, INSTALL A JUMPER  
BETWEEN TERMINALS 4 AND 16.  
4
5
5 SECOND IGNITION IS AVAILABLE ONLY ON THE R4140G1049,  
G1056, G1064, G1114, G1122, G1148, AND G1171 MODELS.  
C7012 OR C7076 MUST BE RATED FOR 120V, 60Hz. TWO DETECTORS  
WITH THE SAME MODEL NUMBER CAN BE WIRED IN PARALLEL TO  
THE SAME TERMINALS. C7076A DOES NOT HAVE LEADWIRES. (FOR  
INSTRUCTIONS SEE FORM NUMBERS; 60-2046 FOR C7012A, C MODELS  
WITH ELECTRON TUBES; 60-2044 FOR C7012E,F MODELS WITH ELECTRON  
TUBES; 60-2398 FOR C7012A,C,E,F SOLID STATE MODELS; 95-8269 FOR THE  
C7076A.) C7012E,F UV FLAME DETECTORS WITH SELF CHECKING FEATURE  
CANNOT BE USED WITH THE R4140G1122 OR R4140G1114.  
10 SECOND MAIN BURNER FLAME-ESTABLISHING PERIOD. ON R4140G114,  
G1122, G1171 FOR 60 SECOND INTERRUPTED PILOT IGNITION, INSTALL  
JUMPER (IN 4074B2V BAG ASSEMBLY) ON BACK OF PROGRAMMER  
BETWEEN SCREW TERMINALS LABELED "JUMPER TO EXTEND MAIN  
IGNITION TRIAL."  
30 SECOND INTERRUPTED PILOT/IGNITION (30 SECOND MAIN BURNER  
FLAME-ESTABLISHING PERIOD, MBFEP) ON THE R4140 AND  
R4140G1049, G1114, G1122, G1171, 15 SECOND INTERRUPTED PILOT/  
IGNITION (15 SECOND MBFEP) ON THE R4140G1148. INTERMITTENT  
PILOT/IGNITION ON THE R4140G1056, AND R4140G1064.  
6
7
10 WHITE SHUTTER LEADWIRES ARE ONLY ON THE C7012E OR F PURPLE PEEPER  
ULTRAVIOLET FLAME DETECTORS WITH SELF-CHECKING FEATURE; C7076A  
ADJUSTABLE SENSITIVITY ULTRAVILOET FLAME DETECTOR DO NOT  
HAVE LEADWIRES.  
11  
TERMINAL 17 IS USED ONLY FOR THE SHUTTER ON SELF-CHECKING  
C7012E,F OR C7076A FLAME DETECTORS.  
FOR DIRECT SPARK IGNITION (OIL OR GAS) CONNECT THE IGNITION  
TRANSFROMER AND FUEL VALVE(S) AS SHOWN IN THE APPROPRIATE INSET.  
12  
M10059  
TERMINAL 16 IS USED ONLY AS A TIE POINT.  
Fig. 16. Sample block diagram of field wiring for R4140G1049, R4140G1056, R4140G1064,  
R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmers.  
25  
60-23373  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
R4140G PARTIAL SCHEMATIC  
Optional Hookups for Two-Stage Switching or  
Intermittent Pilot/Ignition  
L2  
TO M2B, 2K1, AND L1  
1
(Nonmodulating Oil Burners)  
20 SECOND  
INTERRUPTED  
PILOT/IGNITION  
If modulation of the firing rate is not required, an R4140G can  
be used to provide two-stage switching for an oil burner; also,  
an R4140G with interrupted pilot/ignition on terminal 6 can be  
wired to provide an intermittent pilot/ignition. Refer to Fig. 17  
for the necessary wiring changes and make these changes in  
the field wiring to the Q520A Wiring Subbase.  
5
6
7
M6B  
C-50  
O-80  
M4A  
C-60  
O-100  
INTERMITTENT  
PILOT/IGNITION  
OR 1ST STAGE OIL  
VALVE SOLENOID  
2
JUMPER  
3
³ Remove all wiring from terminals 5,6,7,10,11, 12, and 14.  
· Install a jumper wire between terminals 6 and 7.  
(If using an R4140G1056 or R4140G1064, this jumper  
is not necessary.)  
M2A C-70 O-109.5  
JUMPER  
» Install a jumper wire between terminals 7 and 11.  
¿ Connect the ignition transformer between terminals 5  
and L2 (for 20 second interrupted ignition), or between  
terminals 6 and L2 (for intermittent ignition).  
´ For two-stage switching:  
10  
11  
MAIN FUEL VALVE  
OR 2ND STAGE OIL  
VALVE SOLENOID  
(ENERGIZED AT  
M10B  
O-4  
C-45  
12  
a. Connect the first stage oil valve solenoid between  
terminals 6 and L2.  
M8A C-100 O-112  
14  
100 SECONDS)  
4
2ND STAGE  
CONTROLLER  
(IF USED)  
b. Connect the second stage controller (if used) and  
second stage oil valve solenoid in series between  
terminals 12 and L2.  
REFER TO SCHEMATIC DIAGRAMS FOR COMPLETE INTERNAL WIRING  
AND CONTACT SWITCHING.  
1
2
3
²
For an intermittent pilot:  
a. Connect the intermittent pilot between terminals 6  
M4A O-85 ON THE R4140G1106, AND R4140G1148; O-110 ON THE  
R4140G1056, R4140G1064, R4140G1114, R4140G1122, AND R4140G1171.  
and L2.  
b. Connect the main fuel valve between terminals  
12 and L2.  
JUMPER IS NOT NECESSARY TO OBTAIN INTERMITTENT PILOT/IGNITION  
ON THE R4140G1056, OR R4140G1064; THESE MODELS PROVIDE  
INTERMITTENT PILOT/IGNITION ON TERMINAL 6.  
IF A 2ND STAGE CONTROLLER IS USED, THE 2ND STAGE OIL VALVE  
SOLENOID IS NOT ENERGIZED UNTIL THE 2ND STAGE CONTROLLER  
CONTACTS CLOSE.  
IMPORTANT  
The fuel valve or solenoid connected to terminal 12  
4
must not exceed the electrical rating of terminal 7.  
M10060  
NOTE: The maximum Pilot or First Stage Flame-  
Establishing Period is ten seconds.  
Fig. 17. Field wiring changes (dashed) to provide  
two-stage switching or intermittent pilot/ignition  
for a nonmodulating oil burner.  
For a description of the Ignition Trials for this hookup, refer to  
Fig. 18 and the Step-by-Step Operation section.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
R4140G FLAME SAFEGUARD PROGRAMMING CONTROLS  
TIMER  
SECONDS  
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
110  
120  
20 SECOND  
INTERRUPTED  
PILOT/IGNITION  
5
6
1
INTERRUPTED  
PILOT/IGNITION  
OR 1ST STAGE  
OIL VALVE  
2
RUN  
PERIOD  
MAIN FUEL VALVE  
OR 2ND STAGE  
OIL VALVE  
12  
3
1
2
TERMINAL NUMBERS (CIRCLED).  
3
IF A 2ND STAGE CONTROLLER IS USED, THE 2ND STAGE OIL VALVE  
IS ENERGIZED ONLY WHEN THERE IS A DEMAND FOR MORE HEAT  
AND THE 2ND STAGE CONTROLLER CONTACTS CLOSE.  
TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH THE  
BURNER FIRING.  
M10061  
Fig. 18. Partial timer sequence for optional hookups of R4140G Programmers.  
Step-By-Step Operation  
(for Two-Stage Switching or Intermittent Pilot/  
Ignition of a Nonmodulating Oil Burner)  
Ignition Trials  
60 secondsM4A closes; power is applied to terminals 5  
and 6, energizing the ignition transformer and pilot  
valve (or first stage oil valve solenoid when using two-  
stage switching).  
NOTE: If using two-stage switching with a second stage  
controller, the second stage oil valve solenoid  
energizes only when there is a demand for more  
heat and the second stage controller contacts close.  
When a flame is detected, 2K pulls in, 2K2 opens,  
and the LS HTR stops heating; 2K1 and 2K3 close.  
104 secondsM5B opens; timer stops with the system in  
70 secondM2B opens; pilot or ignition trial ends; a flame  
must be detected by this time (2K pulled in and 2K1  
closed) or safety shutdown occurs and the lockout  
switch trips.  
the run condition.  
NOTE: Intermittent pilot/ignition and all fuel valves and  
solenoids (terminals 6 and 12) de-energize when the  
Run period is complete and the main burner  
controller contacts open.  
M2A closes; power is applied to terminal 7,  
maintaining power at terminals 6 and 11 (through  
the jumpers) until the Run period is completed.  
80 secondsM6B opens: 20 second interrupted pilot/  
ignition (terminal 5) de-energizes.  
For complete installation, checkout, troubleshooting, and  
service information, refer to form 60-0770.  
100 secondsM8A closes; power is applied to terminal  
12, energizing the main fuel valve (or second stage oil  
valve solenoid when using two-stage switching).  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373  
Honeywell Asia Pacific Inc.  
Room 3213-3225  
Sun Hung Kai Centre  
No. 30 Harbour Road  
Wanchai  
Home and Building Control  
Honeywell Internationsl, Inc.  
1985 Douglas Drive North  
Golden Valley, MN 55422  
Home and Building Control  
Honeywell Limited-Honeywell Limitée  
35 Dynamic Drive  
Scarborough, Ontario  
M1V 4Z9  
Hong Kong  
Honeywell Latin American Division  
Miami Lakes Headquarters  
Honeywell Europe S.A.  
3 Avenue du Bourget  
14505 Commerce Way Suite 500  
Miami Lakes FL 33016  
B-1140 Brussels Belgium  
Printed in U.S.A. on recycled  
paper containing at least 10%  
post-consumer paper fibers.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60-23373 E.C. Rev. 8-96  

Grizzly Lathe G0657 User Manual
Grizzly Saw G0460 User Manual
Hamilton Beach Coffeemaker D45012W User Manual
Hasselblad Printer FS 3750 User Manual
Hotpoint Washer WMAQB 741 User Manual
HP Hewlett Packard Cassette Player SSL1016 User Manual
HP Hewlett Packard Stereo System 44425A User Manual
HP Hewlett Packard Switch Series 6600 User Manual
Hunter Fan Ventilation Hood 41949 01 User Manual
IBM Car Video System T120 User Manual