LINEA by HALO  
SURFACE CHANNEL  
Grounding  
Surface Channel  
Low-voltage lighting systems do not  
require grounding when used with  
LV500 series isolated power supplies.  
Surface-mount channel is used when  
minimal size and weight are desirable.  
Typical applications for surface-mount  
are under-cabinet, in-cabinet, cove and  
strip lighting. Surface-mount consists  
of a housing with two square copper  
conductors.  
Polarity  
The lampholder adapter may be inserted  
in either orientation, simplifying  
installation and allowing greater than  
360º rotation for maximum fixture  
adjustment.  
Size  
Linea surface channel is 3/8" (9.5mm)  
high and 3/4" (19mm) wide.  
Specifications  
Surface-mount channel consists of a  
thermal plastic housing with two 10AWG  
nickel-plated copper conductors.  
Electrical capacity is:  
Finishes  
White (P), Black (MB)  
12V, 25amp, 300 Watt maximum  
24V, 25amp, 600 Watt maximum  
Connectors  
Surface channel connectors and  
feed points allow almost unlimited  
configurations. Channels may be field  
cut to any length. Channels can be  
mechanically and electrically connected  
by straight, right-angle and flexible  
joiners. Electrical feeds to surface  
channel are made using the end feed,  
conduit feed, J-box feed or T-bar feed.  
Feeds and joiners push into the end of  
the channel and are secured with a  
single screw. Electrical connections are  
assured by compression-type, nickel-  
plated brass terminal blocks.  
LV102, LV104, LV106, LV108  
LV102–2' Channel.  
Actual length 20 3/16" (513mm)  
Color Codes: P, MB  
LV104–4' Channel.  
Actual length 44 3/16" (1122mm)  
Color Codes: P, MB  
LV106–6' Channel.  
Actual length 68 3/16"(1731mm)  
Color Codes: P, MB  
LV108–8' Channel.  
Actual length 92 3/16" (2341mm)  
Color Codes: P, MB  
PLANNING A LINEA LAYOUT  
Surface Channels  
Starting Surface Channel Runs with Electronic Power Supplies (choose one)  
NOTE: Surface Channel may be up to 20’ with electronic power supplies and 40’ with magnetic power supplies.  
LV503  
LV501  
LV502  
LV503  
150W max  
120V  
Supply  
2', 4', 6', 8'  
Surface Channel  
NOTE: LV502 Canopy can be  
placed anywhere along channel  
to utilize existing power sources.  
LV502  
Power Supply  
150W max  
LV501  
Power Supply  
60W max  
Low Voltage  
Feed  
10'  
Cord  
2', 4', 6', 8' Surface Channel  
2', 4', 6', 8' Surface Channel  
LV204  
Starting and Adding to Surface Channel Runs with Magnetic Power Supplies  
Magnetic  
Power Supply  
CHANNEL  
ADDITIONAL CHANNEL  
Joiner  
Feed Point  
120V or 277V Supply  
12V or 24V Feed  
Power Supplies  
Feed Points  
Channels  
Joiners  
Additional Channels  
2’ Surface Channel  
4’ Surface Channel  
6’ Surface Channel  
8’ Surface Channel  
2’ Surface Channel  
4’ Surface Channel  
6’ Surface Channel  
8’ Surface Channel  
LV202 Straight Joiner  
LV203 Right-Angle Joiner  
LV205 Flexible Joiner  
LV200 J-Box Feed  
LV201 End Feed  
LV204 Conduit Feed  
LV206 T-Bar Feed  
LV503  
LV506  
LV507  
LV508  
LV509  
LV206 T-Bar Feed with  
up to three additional  
TB206 Terminal Blocks  
COOPER LIGHTING  
278  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Work Light 312781E User Manual
Grundig CRT Television DAVIO 15 5710 User Manual
Guardian Technologies Air Cleaner Hygia 40 User Manual
Halo Lighting System Indoor Furnishings LV102 User Manual
Hamilton Beach Slow Cooker 33590 User Manual
Health O Meter Thermometer 7605 User Manual
Heat Controller Air Conditioner BG 101G User Manual
Honeywell Barcode Reader 3580 User Manual
Honeywell Home Safety Product HMR4007 User Manual
Hotpoint Refrigerator RF175MG User Manual