Cornelius Beverage Dispenser Cold Beverage Dispenser User Manual

®
INTELLICARB  
Training Manual  
Release Date: April 29, 2004  
Publication Number: TP01071  
Revision Date: NA  
Revision: A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
InelliCarb Training Manual  
TABLE OF CONTENTS  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Theory of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Delivery Inspection and Unpacking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Cornelius IntelliCarb Carbonator Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Carbonator Time Out Reset Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Carbonator Relief Valve Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Mechanical Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Gate Restrictor Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8  
Ice Diverter Kit 02394 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9  
Removal and Replacement of Agitators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10  
To Remove Agitators For Cleaning (300 shown) . . . . . . . . . . . . . . . . . . . . . . . .10  
Post-Mix Valve Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Set-up Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Dimensions & Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
System Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Water Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Water Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11  
Adjusting Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Calculating Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Syrup/Concentrate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13  
Setting Ratios . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14  
Shurflo . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Shurflow Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15  
Shurflow Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Start-up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16  
Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17  
Plumbing Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18  
Flow Diagram 1xx (Six Flavor Model) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19  
Flow Diagram 1XX (Eight Flavor Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20  
Flow Diagram 2xx (Eight Flavor Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21  
Flow Diagram 2xx (Ten Flavor Models)) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22  
Flow Diagram 300 (Twelve Flavor Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23  
© 2004, IMI Cornelius Inc.  
- i -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Electrical Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Carbonator Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Wiring Diagram 1xx (120V) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Schematic 1xx . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Wiring Diagram 2xx (120V Model) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28  
Wiring Diagram 2xx (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
Wiring Diagram 2xx (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30  
Wiring Diagram 300 (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
Wiring Diagram 300 (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32  
Schematic 300 (120V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33  
Schematic 300 (220/240V Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
SHURflow Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Pumping Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Pumps in Series for Long Distances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Pump Sanitizing / Winterizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Pump Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
DOES NOT OPERATE / GAS APPLIED / DISPENSER VALVE OPEN . . .37  
OPERATES BUT WILL NOT PRIME / DISPENSER VALVE OPEN . . . . . . 37  
DOES NOT ACHIEVE SOLD-OUT WITH EMPTY B-I-B . . . . . . . . . . . . . . . 37  
AIR IN INLET AND/OR OUTLET TUBING . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
STROKES WITH DISPENSER VALVE CLOSED . . . . . . . . . . . . . . . . . . . . 37  
FLUID FROM EXHAUST OR VISIBLE WITHIN GAS INLET TUBING . . . . . 37  
GAS BLOWING FROM EXHAUST CONTINUOUSLY . . . . . . . . . . . . . . . . . 37  
Dispenser Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
Valve Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Excess Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Off Taste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Valve Stuck Open . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
No Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
Carbonator Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Solid State Carbonator Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Test Solid State Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Publication Number: TP01071  
- ii -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
InelliCarb Training Manual  
INTRODUCTION  
UNIT DESCRIPTION  
Built-in cold carbonator produces bottle-quality drinks every time  
No seasonal CO2 adjustments required for changes in water temperature  
A complete system for simplified installation  
Reduces service frequency and lowers equipment life cost  
Generates increased beverage sales and greater consumer satisfaction  
Illuminated merchandiser delivers unique, high impact marketing message  
Ice used to cool cold plate kept separate from ice dispensed into cups  
One piece ABS thermoformed plastic ice storage hopper. Durabidedesign provides durability and  
ensures all ice in the hopper is dispensable  
Unit readily accepts top mount cubers with manual ice fill capability  
THEORY OF OPERATION  
The rate of CO2 solubility increases with cold water. IntelliCarb System provides prechilled cold water  
from the cold plate and mix with CO2 in the carbonator tank. The water is introduced into the tank with a  
high volume 125gph Procon pump and high torque motor.  
The amount of carbonated water reserve is controlled by a probe mounted in the tank. The probe is  
called a liquid level probe. The liquid level probe senses the water level in the tank. Probe controls the  
pump ONand OFFcycle through the electronic board called liquid level board.  
NOTE: The probe works on a 5 M.V. D.C. current that continually reverses direction to prevent  
probe corrosion.  
DESCRIPTION  
The Enduro IntelliCarbseries of ice dispensers solves your ice and beverage service needs in a  
sanitary, space saving, economical way. Designed to be automatically filled with ice from a top mounted  
ice machine or manually filled with ice from any remote ice-making source, these dispensers will  
dispense cubes (up to 1-1/4 inch in size), cubelets, and hard-chipped or cracked ice. In addition, the units  
include beverage faucets, a cold plate, an internal carbonator tank and an external pump for the  
carbonator, and are designed to be supplied direct from syrup tanks with no additional cooling required.  
IMPORTANT: For dispensing compressed or extruded style ice, an Ice Diverter Kit must be installed on  
the dispenser, see FIGURE 13 on page 9.  
© 2004, IMI Cornelius Inc.  
- 1 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
SPECIFICATIONS  
ED150  
ED175  
ED200  
ED250  
ED300  
B=(Beverage)  
C=(Coldplate)  
H=(Internal  
Carb)  
B=(Beverage)  
C=(Coldplate)  
H=(Internal  
Carb)  
B=(Beverage)  
C=(Coldplate)  
H=(Internal  
Carb)  
B=(Beverage)  
C=(Coldplate)  
H=(Internal  
Carb)  
B=(Beverage)  
C=(Coldplate)  
H=(Internal  
Carb)  
Model  
Descriptions:  
Z=(No DripTray) Z=(No DripTray) Z=(No DripTray) Z=(No DripTray) Z=(No DripTray)  
150 Pounds  
6
175 Pounds  
8
200 Pounds  
10  
250 Pounds  
10  
300 Pounds  
12  
Ice Storage:  
Maximum  
Number of  
Faucets  
Available:  
Yes  
Yes  
Yes  
Yes  
Yes  
Built-in Cold  
Plate:  
ꢀꢁꢂꢃꢀꢃꢄꢂꢅꢆꢇꢈꢂꢆ$PSVꢆ7RWDOꢆ8QLWꢆ'UDZ  
120/1/60, 3.5 Amps Total Unit Draw  
230/1/50, 2.0 Amps Total Unit Draw  
120/1/60, 4.0  
Amps Total Unit  
Draw  
Electrical:  
230/1/50, 3.0  
Amps Total Unit  
Draw  
Outlet should be within 6 feet of dispenser.  
Width 22”  
Width 24.5”  
Width 22”  
Width 24.5”  
Deep 3011/16”  
High 395/8”  
Width 443/8”  
Deep 311/2”  
High 37”  
Deep 30--11/16Deep 30--11/16Deep 3011/16”  
High 35--5/8”  
High 35--5/8”  
High 355/8”  
Dimensions: Z--Models  
Width 22”  
ZModels  
ZModels  
Width 24--1/2”  
Deep 23--1/16”  
High 35--5/8”  
75--psig (max)  
Width 22”  
Width 241/2”  
Deep 231/16”  
High 395/8”  
75psig (max)  
Width 443/8”  
Deep 231/16”  
High 37”  
Deep 23--1/16”  
Deep 231/16”  
High 355/8”  
75psig (max)  
High 35--5/8”  
75--psig (max)  
75psig (max)  
CO2 Operating  
Pressure  
REQUIREMENTS  
Weight: counter must be level and able to support 450 lbs.  
Environment: Indoor installation only  
Temperature: 40 to 100oF  
CO2: 75 psi at unit  
Syrup: 60 psi., 0.70 -- 0.75 ounces per sec. (0.6 gpm) at unit  
Water: 60 psi at pump  
Electrical: See name plate  
DELIVERY INSPECTION AND UNPACKING  
Upon delivery inspect the unit for damage or irregularities and immediately report problems to the  
delivering carrier and file a claim with that carrier.  
Open loose parts packages and inspect parts.  
Part No.  
Description  
Qty.  
710000030  
Pump and Motor Assy  
1
4
2
1
1
1
1
1
70970  
4Legs  
70750  
Clamps  
Brush  
Drain Pan Drain Line  
Drain Line Insulation  
)LWWLQJꢆꢇꢃꢋꢆ6RFꢆ[ꢆꢇꢃꢋꢆ)SW  
)LWWLQJꢆꢇꢃꢋꢆ0SWꢆ[ꢆꢀµ%DUE  
620702201  
51774  
50335  
ꢉꢂꢊꢉꢁ  
ꢉꢀꢁꢌꢌ  
Publication Number: TP01071  
- 2 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
InelliCarb Training Manual  
INSTALLATION  
1. Locate the dispenser indoors on a level counter top.  
A. LEG OPTION  
Unpack the four (4) legs and install them into the threaded holes provided in the bottom of the  
unit. The installer must provide flexibility in the product and utility supply to permit shifting the  
position of the dispenser sufficiently to clean the area beneath it.  
B. COUNTER MOUNTING  
If counter mounted the ice drink dispenser must be sealed to the counter. The template drawing  
indicates where openings can be cut in the counter. Locate the desired position for the dispenser,  
then mark the outline dimensions on the counter using the template drawings. Cut openings in  
counter.  
Apply a continuous bead of NSF International (NSF) silastic sealant (Dow 732 or equal) approxi-  
mately 1/4--inch inside of the unit outline dimensions and around all openings. Then, position the  
unit on the counter within the outline dimensions. All excess sealant must be wiped away immedi-  
ately.  
2. The beverage tubes, drain tube and power cord are routed through the large opening in the bottom  
of the unit. See the mounting template for locating the required clearance opening in the counter for  
these utility lines.  
3. Drip tray assembly: Route the drain tube to an open drain with the end of the tube above the flood”  
level of the drain. Use the tubing, fittings, clamps, and insulation provided with the Dispenser to  
assemble the drain. The completed drain line must pitch continuously downward and contain no  
trapsor improper drainage will result. Must have a 4 inch air gap between drain line and drain.  
NOTE: This equipment must be installed with adequate backflow protection to comply with fed-  
eral, state, and local codes.  
NOTE: IMI Cornelius Inc. recommends that a water shutoff valve and water filter be installed in  
the plain water inlet supply line. A Cornelius Water Filter (P/N 313860000) and QUICK DISCON-  
NECT SET (P/N 313867000) are recommended.  
CAUTION: Check the minimum flow rate and the maximum pressure of the plain water inlet supply line.  
MINUMUM FLOW RATE MUST BE AT LEAST 125--GALLONS PER HOUR. If flow rate is less than 125-  
-gallons per hour, starving of the carbonator water pump will occur. Starving will damage the water pump  
and could cause the carbonator to time out. INCOMING PLAIN WATER INLET SUPPLY LINE WATER  
TO PUMP PRESSURE MUST REMAIN A MINIMUM OF 10--PSI BELOW THE CARBONATOR CO2  
OPERATING PRESSURE. (Example: Carbonator CO2 operating pressure is 75--PSI and the maximum  
water pressure can be no more than 65--psi, etc.). Water over pressure (higher than CO2 operating pres-  
sure) can cause carbonator flooding, malfunction, and leakage through the carbonator relief valve. If  
water is exceeding maximum pressure specifications, a Water Pressure Regulator Kit (P/N 310150000)  
or equivalent must be installed in the plain water inlet supply line. If fitting connector is not available,  
water line must be 1/2or 3/4diameter with a shut off valve within 6 feet of the dispenser.  
4. Locate the carbonator pump assembly and connect probe wires from Ice/Drink Unit and pump. Con-  
nect inlet water to pump and pump outlet to Ice/Drink Unit using 3/8--inch food--grade tubing.  
NOTE: Locate carbonator assembly within 6 feet of the dispenser. Do not lengthen the control  
board harness.  
5. Connect the beverage system product tubes as indicated in applicable Plumbing Flow Diagram, see  
page 19. This work should be done by a qualified service person.  
NOTE: Water pressure for non carbonated beverages must be 60 P.S.I. minimum.  
NOTE: See applicable Flow Diagram or Decal on the lower front of the unit for the location of  
syrup and water connections.  
6. Clean the hopper interior.  
7. Connect the two power cords to a 120 volt, 60 cycle, 3-wire grounded receptacle. For 220--240 Volt  
International Units, a 3--wire power cord is provided. An adapter plug for the particular country will  
need to be provided by the Installer.  
© 2004, IMI Cornelius Inc.  
- 3 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Drains  
Use a 1 - 1/2rigid pipe (e.g. ABS on P.V.C.) this is to prevent kinking or collapsing. Make sure to leave a  
4 inch air gap between the drain line and the floor drain.  
CORNELIUS INTELLICARB CARBONATOR ASSEMBLY  
1. Ice Drink / Drop-In Carbonator Pump & Motor Unit  
Vent to Atmosphere Check Valve  
125 G.P.H. ProCon Water Pump  
High Torque Pump Motor  
Liquid Level Control Box  
Preset CO2 Regulator (75P.S.I.)  
FIGURE 1  
Carbonator Time Out Reset Switch  
The board can be set to turn the carbonator off after three or seven minutes of continuos time. The fea-  
ture can also be disabled. See the carbonator instruction in this manual.  
Carbonator  
Time Out Reset  
Switch  
Time Out  
Selector Pins  
Liquid Level  
Control Board  
FIGURE 2  
FIGURE 3  
1. Locate carbonator assembly below dispenser no more than 6 feet away. Important: Make  
sure there is clearance for the liquid level control reset switch on the side of the control box  
to avoid accidentally tripping the switch. The control board has an internal timer to prevent the  
pump motor from running continuously. In the event of a water supply interruption or malfunction of  
the water level probe and/or motor relay circuit. If there is a time-out event, make necessary repairs  
to what caused the time out, then depress and release the reset switch to put the control board  
back in service. By moving a jumper on the control you can select either a 7 minute or 3 minute time  
out or this feature can also be disabled.  
A. Hook-up a 3/8 ID water supply line 125 G.P.H. minimum (60 psig. max.) to pump inlet. Minimum  
flowing pressure is 30 psig. Important: Tap for non-carb water supply must be upstream of  
pump inlet. Do not tap in the pump outlet.  
B. Hook-up a 3/8 (.375 ID) CO2 supply line (100 psig.) to the inlet of the pre-set CO2 regulator (75  
psig.) on the Pump & Motor base. Note: If using a bulk CO2 tank as supply, tank pressure  
regulator must be set to 100-105 psig. The regulator on the bulk tank should be a second-  
ary.  
Publication Number: TP01071  
- 4 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
InelliCarb Training Manual  
C. Initial start-up procedure for carbonated water system: Turn on the CO2 supply to the car-  
bonator tank, vent air from carbonator tank by pulling the tank relief valve. Turn on water supply to  
the pump. Connect electrical power to the pump and motor unit. Bleed the air out of the system  
by energizing a beverage valve until carbonated water is flowing from the valve.  
NOTE:If the carbonator Pump and Motor does not cycle (turn on and off) properly, check that the  
probe harness connector and ground lead are secured to the carbonator tank connection points.  
D. If service is required on Ice Drink units, it will be necessary to lower the beverage valve panel to  
gain access to the probe and ground connection. Remove the lower front panel (2 screws) from  
the cabinet and the ice chute cover (snapfit). Remove the 6 screws that secure the beverage  
panel to the cabinet. The panel can now be moved downward due to the flexibility of the beverage  
tubing to expose the carbonator tank connections.  
Carbonator Relief Valve Locations  
The carbonator tank is located behind the splash panel, on the right side of the dispenser. You will need  
to pull the relief valves to purge air from the system after the CO2 supply has been hooked up. Failure to  
do this will cause low carbonation volume and popping of the relief valves.  
Agitator  
Motor  
Relief  
Valve Ring  
Carbonator  
Tank  
Carbonator  
Tank Relief  
Valve  
FIGURE 7  
FIGURE 6  
2. Dispenser  
Ice Drink Model ED175BCH (Lower Front Panel Removed)  
Insulated Cold Plate  
Cover & Carbonator  
Tank Assembly  
Total Flex Manifold  
(with insulation)  
Total Flex Manifold  
(insulation removed)  
Cold Plate Inlets  
(3/8 Barb)  
Carb Tank CO  
Supply Line  
2
Carb. Tank Liquid  
Level Probe Harness  
FIGURE 8  
© 2004, IMI Cornelius Inc.  
- 5 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Ice Drink Model ED150/175/300 Coldplate Cover  
Ice Drink Model ED200/250 Coldplate Cover  
Liquid Level Probe  
In-line CO Check Valve  
Probe  
Ground Plate/Stud  
CO Check Valve with Ground Stud  
2
2
FIGURE 10  
FIGURE 9  
3. Total Flex System for Ice Drink Models ED150/175/200/250/300  
Total Flex Manifold (Insulation Removed)  
Water Line  
Plugs  
Retainer Clip  
Manifold Block  
FIGURE 11  
Total Flex is a system of water manifold blocks located at the front of the cold plate, adjacent to the cold  
plate inlets, for easy switch over of carbonated / non-carbonated beverage drinks. The right hand mani-  
fold block is for the beverage valves located to the right side of the ice chute, and the left block is for the  
left bank of valves. Each beverage valve on the dispenser can be set up for either carbonated or non-car-  
bonated drinks. Refer to the units plumbing diagram for the factory carbonated / non-carbonated valve  
locations. The procedure for switching carbonated / non-carbonated water lines on a beverage valve is  
as follows:  
A. Shut off the water supply to the dispenser. Depressurize and drain both the carbonated and non-  
carbonated water circuits.  
B. Remove the retainer clip (2 screws) from the manifold block. Switch the plug and water line fitting  
to their respective carbonated / non-carbonated outlet locations on the block.  
C. Replace the retainer clip. Turn on the water supply and energize the switchedvalve(s). Check  
for water leaks.  
4. Important: Route the dispensers drain line to an open drain with the end of the tube above the flood  
level of the drain. The drain line must pitch downward and contain no traps.  
5. Connect both the carbonator pump and motor unit and the dispenser to a grounded electrical sup-  
ply outlet.  
Publication Number: TP01071  
- 6 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
6. Check list for proper “finished” drink carbonation:  
A. Fill ice storage hopper with ice.  
B. Water supply must be from a continuous source (no tank supply).  
C. Use only filtered water.  
D. Supply water line to the carbonator pump must be a minimum of .375 ID.  
E. Syrup supply lines must be a minimum of .265 ID.  
F. Water inlet pressure range: 45-60 max. static psig. with a minimum flowing pressure of 30 psig.  
G. Syrup CO2 secondary regulator pressure set to 60 psig.  
H. CO2 supply must be high quality, food grade.  
I. Purge all water, carb-water, and product lines of air before brixing valves.  
J. Important: Brix valves with cold product. Allow at least 15-20 minutes for ice to cool down the  
coldplate on initial start-up before brixing the valves.  
K. Dispense at least (2) 12 oz. drinks before taking a carbonation level reading.  
L. Carbonation tester thermometer must read 32-33oF. for accurate carb-level reading. Store tester  
in ice water bath during use.  
M. Hold cup at valve nozzle for drink to be tested. Pour drink slowly down the side wall into the carb-  
tester to avoid agitation during pouring. Press vent valve once on carb-tester after tightening lid.  
N. Shake carb-tester in vertical motion until peak pressure reading is obtained. Use Pepsi chart for  
carbonation level reading.  
NOTE: Carbonator troubleshooting procedure located on page 43.  
© 2004, IMI Cornelius Inc.  
- 7 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
MECHANICAL SECTION  
GATE RESTRICTOR PLATE  
NOTE: Disconnect power to dispenser before installing, removing, or adjusting restrictor.  
ADJUSTMENT  
INSTALL PLATE  
ON STUDS AS  
SHOWN  
FIGURE 12  
Adjustment  
This plate may be adjusted as shown to reduce or increase the dispensing rate of ice, especially  
desirable when using glasses or other containers with small openings. Adjustment can be made by  
sliding up or down with nuts loosened, to obtain the desired amount of restriction.  
Publication Number: TP01071  
- 8 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
ICE DIVERTER KIT 02394  
NOTE: For dispensing Scotsman, Wilshire, and Hoshizaki compressed ice cubes:  
1. Disconnect power to dispenser.  
2. Remove Merchandiser from dispenser.  
3. Remove ice chute and discard gate restrictor.  
4. Install ice diverter on gate mounting plate as shown below.  
5. Apply RTV to back surface of ice diverter, to seal to gate mounting plate.  
6. Reinstall gasket and ice chute.  
7. Reinstall merchandiser and energize unit.  
GATE MOUNTING PLATE  
S TOR AGE HOPPE R  
FLANGE E XTE NDS  
INTO S TOR AGE HOP -  
PE R THR OUGH GATE  
OPE NING  
ICE DIVE R TE R  
ICE CHUTE  
COVE R  
APPLY R TV TO  
THIS S UR FACE TO  
S E AL TO HOPPE R  
GATE MOUNTING  
PLATE  
10 -32 WAS HE R  
GAS K E T  
ICE CHUTE  
10 -32 NUT  
FIGURE 13  
© 2004, IMI Cornelius Inc.  
- 9 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
REMOVAL AND REPLACEMENT OF AGITATORS  
To Remove Agitators For Cleaning (300 shown)  
NOTE: All other models have only one agitation Assembly.  
RIGHT HAND AGITATOR  
WITH HOLE IN UPRIGHT  
LEFT HAND  
AGITATOR  
O–RING  
COUNTERCLOCKWISE  
ROTATION  
CLOCKWISE  
ROTATION  
FRONT (VALVE SIDE) VIEW FROM TOP OF DISPENSER  
FIGURE 14  
1. Lift agitator and disc from unit.  
2. Remove O-Ring starting at notch. Warm the O-Ring with water to ease removal.  
3. Lift the plastic agitator disc off of the stainless-steel agitator.  
4. Replace by reversing steps.  
NOTE: Refer to Sanitize Procedure in the Owners Instruction for complete cleaning and sanitiz-  
ing instructions.  
Publication Number: TP01071  
- 10 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
POST-MIX VALVE SECTION  
SET-UP INSTRUCTIONS  
Concentrate valve sleeve  
has only one hole  
Syrup valve sleeve  
has six holes  
FIGURE 15  
A side water lever kit can be added to a valve allowing for  
dispensing of water without syrup or concentrate. The side  
water lever can be added to either a carbonated drink valve  
or a noncarbonated drink valve.  
Mounting  
screw  
Water  
lever  
Post-mix valves control:  
the ONOFF of syrup and water,  
the flow rates of syrup and water,  
FIGURE 16  
the mixing of the two ingredients as they pour into the  
cup, and  
in some instances - dispensed portion.  
Dimensions & Capacities  
Fast Flow............................................................................................................... 1 ½ to 3 oz./sec.  
UFB-1 ......................................................................................................................... 2 to 4 oz./sec.  
Ultra Flow .............................................................................................................. 3 to 4 ½ oz./sec.  
Operational temperature range: ......................................................... 10°C (50°F) to 43°C (110° F)  
Voltage requirements:................................................................................ 22 to 27 VAC (50/60 Hz)  
Transformer (electronic valves) ........................................................................................80 VA min.  
Operating Pressure (flowing)...............................................................................syrup = 20 psi min.  
.............................................................................................................................water = 35 psi min.  
Concentrates and juices that contain particulates must be dispensed from a juice valve.  
A slanted drip tray is necessary when using an Optifill valve.  
SYSTEM DETAILS  
Water  
Water Quality  
Water quality issues have an affect on dispensing valves. Chloramine, a combination of chlorine and  
ammonia is responsible for some degradation of rubber components. Chloramine is used in many U. S.  
water supplies. Its affects can be minimized by installing and maintaining a water filtration system.  
Ultra pure water affects the sensitivity of the Optifill™ valve. Because ultra pure water has less mineral  
content, it reduces the conductivity of the water keeping the circuit open and overfilling the beverage  
container.  
Water Flow  
The size of the orifice in the piston varies depending on whether the piston is used for syrup or water, and  
whether it is high flow or ultra flow valve.  
© 2004, IMI Cornelius Inc.  
- 11 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
NOTE: The notched water piston on the Ultra Flow and UFB-1 valve.  
results in at least one orifice in the sleeve always open. This elimi-  
nates pulsating and smooths water flow at higher flow rates.  
Notch in  
piston  
In operation the liquid flows through the knifeedged orifice in the bottom  
of the piston and then out the orifices in the sleeve. The outlet orifice size  
in the sleeve is regulated by the position of the piston. In the illustration,  
the piston is restricting approximately 1/2 of the outlet orifices.  
FIGURE 17  
UFB-1 Flow Module  
Orifice  
Sleeve  
Piston  
FIGURE 18  
Lower Fluid Pressure BUT  
Larger Orifice Openings  
Higher Fluid Pressure BUT  
Smaller Orifice Openings  
Same Volume Of  
Syrup/Water Flows  
From Orifices  
Higher Fluid  
Lower Fluid  
Pressure Pushing  
Against Piston &  
Spring  
Pressure Push-  
ing Against Pis-  
ton & Spring  
Knife  
edge  
Syrup/Water Flow  
FIGURE 19  
The position of the piston inside the sleeve is determined by the upward pressure of the liquid against the  
base of the piston and the downward pressure of the spring inside the piston (not shown here). The  
pressure of the spring is regulated by the adjusting screw.  
If the pressure of the liquid increases, the flow rate through the knifeedged orifice will increase. The  
piston is moved upward closing off more of the outlet orifices. The same flow rate is thereby maintained.  
Publication Number: TP01071  
- 12 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Adjusting Flow Rates  
Flow rates of the water and syrup are adjusted based on the desired ratio. For example: if the desired  
ratio is 5:1, then the flow rate of the water is 5 times that of the syrup.  
If the desired finished drink total flow rate is 3.0 ounces per second, then the water flow rate is 2.5 oz./  
sec and the syrup flow rate is 0.5 oz./sec. (The water at 2.5 oz./sec is five times the 0.5 oz./sec syrup flow  
rate.)  
NOTE: Always adjust water within its range.  
Water Flow Rates At Selected Ratios  
Water To Syrup  
Ratio  
Water at 1.5 oz./ Water at 3.0 oz./ Water at 3.75 oz./ Water at 4.5 oz./  
sec. Total Flow  
sec. Total Flow  
sec. Total Flow  
sec. Total Flow  
2 to 1  
3 to 1  
4 to 1  
5 to 1  
6 to 1  
7 to 1  
1.00 oz./sec.  
1.13 oz./sec.  
1.20 oz./sec.  
1.25 oz./sec.  
1.29 oz./sec.  
1.31 oz./sec.  
2.00 oz./sec.  
2.25 oz./sec.  
2.40 oz./sec.  
2.50 oz./sec.  
2.57 oz./sec.  
2.63 oz./sec.  
2.50 oz./sec.  
2.81 oz./sec.  
3.00 oz./sec.  
3.13 oz./sec.  
3.21 oz./sec.  
3.28 oz./sec.  
3.00 oz./sec.  
3.38 oz./sec.  
3.60 oz./sec.  
3.75 oz./sec.  
3.86 oz./sec.  
3.94 oz./sec.  
Calculating Flow Rates  
The most frequent ratio is 5:1. The charts above list the breakdown for many ratios and flow rates. It is  
useful to be able to calculate flow rates when a chart is not available.  
An example of calculating the water and syrup flow rates given the finished drink flow rate and the water  
to syrup ratio:  
Given:  
1. Finished Drink Flow Rate = 3.0 oz./sec.  
2. Water to Syrup Ratio = 5 to 1  
To calculate Water Flow Rate:  
1. Calculate the Total Portions = Water Portion + Syrup Portion  
(example 5 + 1 = 6)  
2. Calculate Syrup Flow Rate = Finished Drink Flow Rate ÷ Total Portions  
(example 3.0 oz./sec ÷ 6 = .5 oz./sec)  
3. Calculate Water Flow Rate = Finished Drink Flow Rate Syrup Flow Rate  
(example 3.0 oz./sec - .5 oz./sec = 2.5 oz./sec)  
Prove the calculation is correct by adding water flow rate of 2.5 oz./sec + syrup flow rate of .5 oz./sec =  
finished drink flow rate of 3.0 oz./sec.  
Water flowing at 2.5 oz./sec and syrup flowing at .5 oz./sec achieves a ratio of 5:1 and 3.0 oz./sec. flow  
rate.  
Syrup/Concentrate  
Syrup should always be precooled before setting the ratio. Syrup takes a path through the valve  
parallel to the water path. It is introduced in the block, travels through a syrup flow control, banjo, valve  
head and out the nozzle. Note, concentrate is not cooled.  
High sugar syrups are more viscous (thicker) than diet syrups and consequently have more  
pressure drop within a system. This pressure drop results in less flow at the valve and therefore a slower  
fill time. Increasing the pump pressure will help overcome the pressure drop caused by high sugar  
syrups.  
© 2004, IMI Cornelius Inc.  
- 13 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Setting Ratios  
If the ratio varies and must be adjusted often, it is probably the result of a restricted syrup  
system. It is then time to clean and sanitize the syrup tubing and cooling coils and check for other  
problems such as syrup pumps, etc.  
NOTE: Try raising the pressure on the pump before cleaning.  
Set the water flow rate first, then adjust the syrup to the desired ratio. This gives the most accurate  
valve flow setting possible. Measure the ratio and adjust the syrup flow, if necessary. This will result in  
uniform flow, better carbonation retention, and improved drink quality.  
When using a ratio cup always take these precautions to ensure accuracy:  
After installing the separator tube, open the valve to fill the syrup tube before starting the ratio test.  
Clean the cup thoroughly between tests so there is no carryover from one test to the next.  
Fill the cup to approximately 3/4 full and use approximately the same quantity for each test to ensure  
accurate settings.  
Take another sample to verify the settings.  
Ratio Cup and Syrup Separator  
FIGURE 20  
NOTE: Valve troubleshooting information is available on page 39.  
Publication Number: TP01071  
- 14 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
SHURFLO  
SHURFLOW OVERVIEW  
SHURflos Beverage Gas Pump supplies syrup under pressure to a post-mix dispenser, which mixes the  
syrup with water to an exact ratio (brix). The pump is used in conjunction with non-pressurized Bag-In-  
Box (B-I-B) containers and a bag connector (Q.D.) fitting.  
The pump can be operated on regulated CO2, nitrogen or compressed filtered air. The compressed gas  
drives the pump and is not in contact with the syrup. Separate syrup and gas chambers prevent  
contamination, foaming, and purging of the tubing when the B-I-B has emptied.  
The pump retains pressure in the outlet line, operating only when syrup is needed. When the dispenser  
valve is opened, the pump reacts to the pressure drop by operating to maintain pressure in the line.  
When the dispenser is closed, the incoming gas and output syrup pressures equalize and the pump  
stops. Actual dynamic line pressure is dependant upon system losses as outlined in the section  
"Pumping Capability".  
The automatic "sold-out" feature within the pump ensures consistent syrup delivery right up to the  
moment the B-I-B is empty. Vacuum produced by the pump evacuates the syrup within the bag. Once the  
preset vacuum point is achieved and held, incoming gas pressure to the pump is shutoff causing the  
outlet syrup pressure to drop to zero. When a new B-I-B is installed, the vacuum drops, the pump  
automatically restarts and pressurizes the system. The SHURflo Beverage Gas Pump ensures quality  
from the first drink to the last.  
Beverage Gas Pumps are intended for soda syrups and low viscosity concentrates that do not contain  
solids.  
The use of a SHURflo Juice Pump (-09) is recommended for concentrates containing soft solids, classed  
as round, up to 0.025 in. [0.6 mm] or that are of higher viscosity than soda syrups.  
When concentrates contain pulp classed as long/stringy, seed particles or are exceptionally viscous, the  
Particulate Juice Pump (-10) should be used as it can handle soft solids up to 1 /4" [6 mm] cubed.  
Standard gas pump models are for installations where geographic elevation is less than 5000 ft.[1523M].  
For elevations above 5000 ft. specific high altitude models with a reduced sold-out spring rate must be  
used to compensate for the loss in atmosheric pressure.  
For further application and model information please contact SHURflo.  
NOTE: Shurflow Troubleshooting information available on page 35.  
© 2004, IMI Cornelius Inc.  
- 15 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
SHURFLOW INSTALLATION  
As indicated on the pump, the outlet port is to be mounted up.  
Pumps are to be mounted at the same level or higher than the B-I-B. The best choice is to have the  
pump above the B-I-B.  
INLET tubing from the B-I-B to the pump use; 3/8" I.D. [10mm] minimum, heavy wall (1/8"  
[3mm]) clear, NSF listed vacuum tubing. Inlet tubing should not have excessive length. Tub-  
ing that is allowed to drape down can trap air in the B-I-B creating a potential for pump "sold-  
out" problems. The maximum vertical distance from the bottom of the B-I-B to the pump must  
not exceed 5 ft [1.5 M ]. Maximum inlet tubing length is 10 ft. [3 M ].  
If plumbing multiple B-I-Bs to a pump, B-I-B's should be "Teed" side-by-side horizontally,  
rather than one on top of the other (vertically).  
OUTLET tubing from the pump to the dispenser should be high pressure rated and NSF  
listed. Consult "Pumping Capability" (see page 2) for appropiate tubing I.D.  
Always cut CO2 and outlet tubing at least 2 ft. [.6 M] longer to provide a "service loop" so the  
B-I-B rack can be moved for cleaning or service.  
Use new (clean), 1/4" I.D. [6 mm], flexible, high pressure, braided tubing from the CO2 / air  
regulator to the pump.  
NEVER connect a transfer tank "system" in series with a B-I-B system. Syrup contaminants in  
old components may work their way through the air supply causing premature failure of the gas  
pump. Gas used to operate pumps MUST be clean and contain no contaminants (syrup, oil, rust,  
water, etc). Air compressors may be used with proper particle filters and moisture separators. Air storage  
tanks should be drained regularly. Pumps subjected to contaminated air are not covered by warranty.  
High concentrations of CO2 can be fatal as it will displace the air from non-ventilated areas.  
Pumps operated by CO2 must be in ventilated areas.  
If placed in a confined area (basement, closet, cooler box, etc.), exhaust fans capable of changing  
the room air on a continuous basis should be used.  
All tubing connections must be secured with stainless steel, stepless Oetiker clamps.  
®
Cable-tie all tubing securely to prevent kinks or sags that inhibit performance or cause damage to the  
pump fittings.  
START-UP PROCEDURE  
1. Confirm that all tubing connections are properly clamped, fittings are tight, and tubing is not kinked.  
Install bag connector to the B-I-B.  
2. Adjust gas regulator to about 20 psi. [1.4 bar] allowing the pump to stroke slowly.  
3. Operate the valve until all air trapped within the tubing has been purged.  
4. Once the air has been purged, adjust the CO2 regulator to the pressure necessary to main-  
tain the desired brix. The most efficient gas usage occurs at 40 psi. [2.8 bar]. MAXIMUM  
static gas pressure to the pump is 85 psi. [5.8 bar], minimum 20 psi. [1.4 bar].  
Flowrates that result in a stroke-rate of more than two strokes per second will decrease pump  
life. (Consult factory) Pump failure due to "overrunning" is not covered by the limited warranty.  
To prevent air from entering the system always leave the bag connector attached to the empty  
B-I-B until a new B-I-B can be installed. Air entered into the system, via air in the bags or  
vacuum leaks, may cause brix fluctuation, foaming, spitting, non-operation of the vacuum sold-  
out or pump "run-on" with the valve closed. Symptoms of this kind can lead to a misdiagnosis of the  
pump.  
Publication Number: TP01071  
- 16 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
PLUMBING  
TYPICAL INSTALLATION  
FIGURE 21. Typical Installation  
© 2004, IMI Cornelius Inc.  
- 17 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
PLUMBING LAYOUT  
Connection Legend  
3/8" Female Fir Nut  
3/8" Barb Conn  
A
B
C
1/4" Barb Conn  
3/8" Hose Barb - 3/4" NP  
1/4" Female Flr Nut  
D
E
C
Direct Conn to SUR  
Outlet on BIB Pmp  
F
B
B
C
B
B
Direct Conn to CO2  
Inlet on BIB Pmp  
G
Syr Inlet BIB Pmp  
3/4" NPT TEE  
H
I
E
A
CO2 Supply  
Carb  
Pump  
Regulator  
100 psi  
E
Regulator  
55-60 psi  
A
E
D
I
Water Filter  
D
H
BIB Syrup  
F
BIB Pump  
G
6-10 Brand  
Flavors  
F
BIB Pump  
H
G
BIB Syrup  
Tubing Legend  
3/8" Bev Tubing  
1/4" Bev Tubing  
3/8" Tycon Tubing  
FIGURE 22. Plumbing Layout  
Publication Number: TP01071  
- 18 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DOUBLE CHECK  
VALVE  
FAUCETS  
6
W1,  
VALVES 1,2,  
3,6  
OPTIONAL  
PRESSURE  
REGULATOR  
W1  
W2  
S6  
S5  
S4  
POTABLE  
WATER  
5
4
FILTER  
SUPPLY  
CARBONATOR  
PUMP  
INSTALL FOR  
NON -CARB AS  
REQUIRED  
W2,  
VALVES 4,5  
CHECK  
VALVE  
NON -CARB  
WATER  
COLDPLATE  
INLET  
S5  
S6  
S7  
S1  
S2  
S3  
CONNECTIONS  
OPTIONAL FOR  
DIET DRINKS  
OR ROOT BEER  
5-15  
PSIG  
W2  
3
2
1
PLUGGED  
S3  
S2  
S1  
75 PSI  
S3  
S2  
S1  
S7  
S6  
S5  
W1  
PRESSURE  
REGULATORS  
SYRUP TANKS  
15-50 PSIG  
COLD PLATE  
CO2  
CYLINDER  
ITEMS INSIDE BROKEN LINE  
INCLUDED WITH UNIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DOUBLE CHECK  
VALVE  
FAUCETS  
8
W1,  
VALVES 1,2,  
3,7,8  
OPTIONAL  
PRESSURE  
REGULATOR  
S8  
S7  
S6  
S5  
W1  
W2  
7
6
5
POTABLE  
WATER  
SUPPLY  
FILTER  
CARBONATOR  
PUMP  
INSTALL FOR  
NON -CARB AS  
REQUIRED  
W2,  
VALVES 4,  
5,6  
CHECK  
VALVE  
NON -CARB  
WATER  
S5  
S6  
S7  
S8  
S1  
S2  
S3  
S4  
COLDPLATE  
INLET  
CONNECTIONS  
OPTIONAL FOR  
DIET DRINKS  
OR ROOT BEER  
5-15  
PSIG  
4
3
2
1
S4  
S3  
W2  
75 PSI  
S4  
S3  
S2  
S1  
S8  
S7  
S6  
S5  
S2  
S1  
PRESSURE  
REGULATORS  
W1  
SYRUP TANKS  
15 -50 PSIG  
COLD PLATE  
CO2  
CYLINDER  
ITEMS INSIDE BROKEN LINE  
INCLUDED WITH UNIT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DOUBLE CHECK  
VALVE  
FAUCETS  
8
OPTIONAL  
PRESSURE  
REGULATOR  
W1  
VALVES 1,2  
3,6,7,8  
W1  
POTABLE  
WATER  
7
6
5
FILTER  
SUPPLY  
W2  
VALVES 4,5  
CARBONATOR  
INSTALL FOR  
NON–CARB AS  
REQUIRED  
W2  
CHECK  
VALVE  
S8  
S7  
S6  
S5  
W2  
W1  
S4  
S3  
S2  
S1  
Non–Carb Water  
COLDPLATE  
INLET  
CONNECTIONS  
4
OPTIONAL FOR  
DIET DRINKS  
OR ROOT BEER  
W2  
75 PSI  
5–15  
PSIG  
3
2
1
W1  
S1  
S2  
S3  
S4  
S5  
S6  
S7  
S8  
COLD PLATE  
SYRUP TANKS  
15–50 PSIG  
PRESSURE  
REGULATORS  
CO2  
ITEMS INSIDE BROKEN LINE  
INCLUDED WITH UNIT  
Cylinder  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
FLOW DIAGRAM 2XX (TEN FLAVOR MODELS))  
CARBONATOR  
TANK  
FAUCETS VIEWED FROM THIS SIDE  
FIGURE 26. Flow Diagram 2xx (Ten Flavor Models)  
Publication Number: TP01071  
- 22 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FAUCETS  
12  
DOUBLE CHECK  
VALVE  
COLD PLATE  
W1  
W2  
OPTIONAL  
PRESSURE  
REGULATOR  
S12  
11  
10  
POTABLE  
WATER  
S11  
S10  
SUPPLY  
FILTER  
CARBONATOR  
PUMP  
INSTALL FOR  
NON–CARB AS  
REQUIRED  
W1  
W2  
S10  
CHECK  
VALVE  
COLDPLATE  
INLET  
NON–CARB WATER  
S11  
S12  
S7  
CONNECTIONS  
S8  
S9  
TO COLDPLATE  
SYRUP INLETS  
W2  
W1  
9
S9  
8
7
S8  
S7  
FAUCETS  
6
COLD PLATE  
W1  
W2  
S6  
5
4
S5  
S4  
CO2  
75 PSI  
W1  
W2  
COLDPLATE  
INLET  
S4  
S5  
S6  
S1  
S2  
S3  
OPTIONAL FOR  
DIET DRINKS  
OR ROOT BEER  
5–15  
CONNECTIONS  
S3  
S2  
S1  
S6  
S5  
S4  
S9  
S8  
S7  
S12  
S11  
S10  
PSIG  
SYRUP TANKS  
15–50 PSIG  
PRESSURE  
REGULATORS  
W2  
W1  
3
S3  
2
1
CO2  
CYLINDER  
S2  
S1  
ITEM INSIDE BROKEN LINE  
INCLUDED WITH UNIT  
CARBONATOR TANK  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
ELECTRICAL SECTION  
Control Box Single Transformer Will Power  
up to Three Valves Simultaneously.  
Transformer  
FIGURE 28. Electrical Box 1xx Single Transformer  
One Transformer Powers the Left Bank  
FIGURE 29. Electrical Box 2xx Single Transformer  
and the Other Powers the Right Bank.  
Will Power All Valves Simultaneously.  
Transformers  
FIGURE 30. Electrical Box 2XX Dual Transformer  
Publication Number: TP01071  
- 24 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2004, IMI Cornelius Inc.  
IntelliCarb Training Manual  
CARBONATOR WIRING DIAGRAM  
© 2004, IMI Cornelius Inc.  
- 25 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
SERVICE INFORMATION  
TO HINGE  
MOTOR  
DANGER!  
ELECTRIC SHOCK HAZARD. DISCONNECT  
POWER BEFORE SERVICING UNIT.  
CCW  
AGITATOR  
MOTOR  
HEATER  
GRN  
TO BEVERAGE FAUCET  
DISPENSE  
SWITCH  
Q.C.  
GATE  
CONNECTOR  
SOLENOID  
(106VDC)  
KEY SWITCH  
T’STAT  
GRD  
115V  
SUPPLY  
N
L
LIGHT  
YELLOW  
+
- -  
RED  
BLUE  
O
W
H
I
B
L
B
L
B B B B B  
R
R
A
N
G
E
2
1
R
E
D
L
L L  
L L  
E
YELLOW  
U
E
A
C
K
A A A U U  
D
T
E
WHT  
C C C E E  
K K K  
W G  
B
L
WHITE  
H R  
ICE LEVEL  
OPTION  
I
E
A
C T E  
E N  
K
G
R
E
E
N
W
H
I
B
L
A
C
K
T
E
BLACK  
WHITE  
BLACK  
OPTIONAL  
WHITE  
BLACK  
G
R
E
E
N
W
H
I
B
L
R
E
D
R
E
D
T
E
A
C
K
BLACK  
BLACK  
BLACK  
BLACK  
RED  
PINK  
L2  
OPTIONAL  
NC  
NOCOM  
WHITE  
WHITE  
BLACK  
BLACK  
BLACK  
OPTIONAL  
PINK  
RED  
NC  
COM  
NO  
WHITE  
L1  
BLUE  
WHITE  
WHITE  
BLACK  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
SCHEMATIC 1XX  
N
L
G
TIMER  
L2  
L1  
MOTOR HEATER  
A GITATOR MOTOR  
N.O.  
N.C.  
C
VEND SWITCH  
CA PA CITOR  
RECTIFIER  
GATE  
SOLENOID  
OPTIONA L  
B A LLA ST  
OPTIONA L LIGHT  
OPTIONA L  
STA RTER  
B EVERA GE TRA NSFORMER  
OPTIONA L LOW ICE LEVEL  
LIGHT  
T’STAT  
B EVERA GE  
VA LVES  
B EVERA GE  
VA LVES  
B EVERA GE PA NEL  
FIGURE 32. Schematic 1xx  
© 2004, IMI Cornelius Inc.  
- 27 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MOTOR  
HEATER  
T’STAT  
LIGHT  
AGITATOR  
MOTOR  
Y
E
L
B
L
2
1
SERVICE INFORMATION  
BLUE  
K
GRN  
ICE LEVEL SIGNAL  
OPTION  
N
L
DANGER! ELECTRIC SHOCK HAZARD. DISCONNECT  
POWER BEFORE SERVICING UNIT.  
Q.C. CONNECTOR  
TO BEVERAGE VALVES  
TO 24V  
TRANSFORMER  
TO HINGE  
DISPENSE  
SWITCH  
GATE  
SOLENOID  
(106VDC)  
KEY SWITCH  
BLUE  
YELLOW  
OPTIONAL  
LIGHT BALLAST  
R
E
D
Y
E
L
L
B
L
W
G
R
E
E
N
B
B
L
BLACK  
RED  
B
B
G
R
E
R
E
D
H
I
L
LL  
G
R
E
E
N
G
R
E
E
N
BLACK  
A
C
K
MOTOR START  
CAPACITOR  
A
C
K
A
AA  
BEVERAGE  
BEVERAGE  
TRANSFORMER  
(OPTIONAL)  
T
E
CC  
E C  
BLACK  
O
K
KK  
N
TRANSFORMER  
W
W
H
I
(OPTIONAL)  
WHITE  
BLACK  
T
E
B B  
WHITE  
WHITE  
L
L
W
H
I
B
L
U U  
E E  
WHITE  
RECTIFIER  
A
C
K
B
L
T
E
WHITE  
BLACK  
Y
E
L
A
C
K
MOTOR  
START  
RELAY  
BLACK  
L2  
R
E
D
NC  
NC  
L
O
W
NO  
WHITE  
COM  
+
- -  
3
R
E
D
AGITATION  
TIMER  
B
L
W
H
I
W B  
W
H
I
E
B
L
B
L
B
L
B
L
L
4
H
I
2
A
C
K
OPTIONAL  
LIGHT  
STARTER  
NOCOM  
L1  
A
U
E
U
E
U
E
U
E
T
E
R
E
D
T
E
C T  
WHITE  
W
H
I
K
BLACK  
BLACK  
BLACK  
T
E
BLACK  
WHITE  
BLACK  
WHITE  
OPTIONAL  
LIGHT SOCKET  
OPTIONAL  
LIGHT SOCKET  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
WIRING DIAGRAM 2XX (220/240V MODELS)  
BLK  
FIGURE 34. Wiring Diagram 2xx (220/240V Models)  
© 2004, IMI Cornelius Inc.  
- 29 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
IntelliCarb Training Manual  
WIRING DIAGRAM 2XX (220/240V MODELS)  
G
L
N
TIMER  
L2  
L1  
RECTIFIER  
MOTOR HEATER  
AGITATOR MOTOR  
N.O.  
N.C.  
C
VEND SWITCH  
GATE  
SOLENOID  
OPTIONAL  
BALLAST  
OPTIONAL LIGHT  
OPTIONAL  
STARTER  
OPTIONAL  
BEVERAGE TRANSFORMER  
OPTIONAL ICE LEVEL  
OPTIONAL  
BEVERAGE  
VALVES  
OPTIONAL  
BEVERAGE  
VALVES  
BEVERAGE PANEL  
FIGURE 35. Wiring Diagram 2xx (220/240V Models)  
Publication Number: TP01071  
- 30 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
WIRING DIAGRAM 300 (220/240V MODELS)  
FIGURE 36. Wiring Diagram 300 (220/240V Models)  
© 2004, IMI Cornelius Inc.  
- 31 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
IntelliCarb Training Manual  
WIRING DIAGRAM 300 (220/240V MODELS)  
FIGURE 37. Wiring Diagram 300 (220/240V Models)  
Publication Number: TP01071  
- 32 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2004, IMI Cornelius Inc.  
IntelliCarb Training Manual  
SCHEMATIC 300 (120V MODELS)  
G
L
N
TIMER  
L2  
L1  
RECTIFIER  
MOTOR HEATER  
AGITATOR MOTOR  
N.O.1  
C
VEND SWITCH  
N.C.1  
CAPACITOR  
GATE  
SOLENOID  
BALLAST  
OPTIONAL LIGHT  
STARTER  
OPTIONAL  
BEVERAGE TRANSFORMER  
OPTIONAL ICE LEVEL  
OPTIONAL  
BEVERAGE  
VALVES  
BEVERAGE PANEL  
MOTOR HEATER  
AGITATOR MOTOR  
N.O.2  
C
VEND SWITCH  
N.C.2  
CAPACITOR  
GATE  
SOLENOID  
BALLAST  
OPTIONAL LIGHT  
STARTER  
OPTIONAL  
BEVERAGE TRANSFORMER  
OPTIONAL ICE LEVEL  
OPTIONAL  
BEVERAGE  
VALVES  
BEVERAGE PANEL  
FIGURE 38. Schematic 300 (120V Models)  
© 2004, IMI Cornelius Inc.  
- 33 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
SCHEMATIC 300 (220/240V MODELS)  
G
N
L
EMC  
LINE  
FILTER  
E–BOX GD.  
MOTOR HEATER  
MOTOR HEATER  
TIMER  
L2  
L1  
RECTIFIER  
GATE  
SOLENOID  
POWER  
PUSH BUTTON  
SWITCH  
N.C1  
C
VEND SWITCH  
N.O1  
AGITATOR MOTOR  
OPTIONAL  
BALLAST  
OPTIONAL LIGHT  
OPTIONAL STARTER  
OPTIONAL  
BEV. TRANSFORMER  
BEVERAGE  
KEYLOCK SWITCH  
24V  
BEV. FAUCETS  
EMC  
GATE  
SOLENOID  
N.C2  
C
VEND SWITCH  
N.O2  
AGITATOR MOTOR  
OPTIONAL BALLAST  
OPTIONAL LIGHT  
OPTIONAL STARTER  
OPTIONAL BEV. TRANSFORMER  
24V  
BEV. FAUCETS  
FIGURE 39. Schematic 300 (220/240V Models)  
Publication Number: TP01071  
- 34 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
TROUBLESHOOTING  
SHURFLOW TROUBLESHOOTING  
Pumping Capability  
The distance syrup can be delivered is  
MAXIMUM HORIZONTAL TUBING  
limited by inherent factors (restrictions) within  
the inlet & outlet sides of the beverage  
dispensing system. Due to variances in  
system configuration and equipment, an  
accurate determination of pressure drop is  
difficult. Before deciding on a systems  
tubing size, SHURflo recommends  
estimating system losses by considering the  
following:  
BY  
LENGTHS VISCOSITY  
Distances shown are intended as a guidline only.  
(cPs.=Centipose)  
1/"I.D.  
4
[6m m ]  
3/"I.D.  
8
[10m m ]  
1/"I.D.  
2
[13m m ]  
FLOW RATE  
/SEC.  
OZ.  
.5  
m L  
15 500+ 152+ 500+ 152+ 500+ 152+  
Feet Meter Feet Meter Feet Meter  
.75  
1.0  
1.5  
2.0  
2.5  
3.0  
3.5  
.5  
22.5 500  
152 500+ 152+ 500+ 152+  
138 500+ 152+ 500+ 152+  
30  
45  
453  
212  
102  
64  
Diet  
Soda  
Syrup  
(5 cPs. 3)  
65  
500+ 152+ 500+ 152+  
152 500+ 152+  
60  
500  
398  
297  
212  
500  
500  
388  
193  
127  
500  
345  
239  
127  
31  
19  
9
Syrup viscosity and temperature (coldplate,  
re-circ., etc.).  
75  
121 500  
152  
152  
152  
90  
32  
90  
65  
500  
500  
Total syrup flow rate of valve(s) connected  
to a pump.  
105  
15  
--  
--  
500  
152  
40  
24  
9
152 500+ 152+  
152 500+ 152+  
.75  
1.0  
1.5  
2.0  
.5  
22.5 133  
Standard  
Soda  
Syrup  
(20 cPs. 3)  
Inside diameter of the inlet/outlet tubing,  
fittings, bag connector, etc.  
30  
45  
79  
32  
118  
59  
500  
500  
366  
152  
152  
112  
Horizontal & vertical distance of the outlet  
tubing.  
60  
10  
3
39  
15  
129  
75  
39  
23  
16  
8
152 500+ 152+  
105 500+ 152+  
Heavy  
Soda  
Syrup  
(35 cPs. 3)  
.75  
1.0  
1.5  
22.5  
30  
Vertical tubing runs will reduce total achievable  
tubing run length. To estimate the losses within  
the vertical distance, use the chart to the  
right. Take 1% of the distance in feet [3% if  
meters]. The resulting number is multiplied by  
the vertical distance. This product is then  
subtracted from the maximum horizontal  
distance. The resulting length is the total  
horizontal/vertical (horz./vert.) tubing run that is  
obtainable for that flow rate, tubing I.D. and  
viscosity.  
53  
73  
39  
500  
425  
152  
129  
45  
26  
Distances shown are the results of tests conducted at 70°F  
[21°C] ambient with a static pressure of 85 psi. [5.8 bar] to the  
pump. All distances assume a dynamic pressure of 35 psi. [2.38  
bar] at the dispenser to maintain brix.  
For example:  
FAST FLOW VALVE  
1
/
oz./sec. [15 mL]  
2
(syrup flow only)  
3
GAS IN  
/8" I.D. [10mm]  
TUBING  
22 ft. [6.7M]  
VERTICAL  
TOTAL TUBING RUN  
HEAVY SODA  
370 ft. [113M]  
SYRUP  
3
/8" I.D. [10mm]  
TUBING (min.)  
© 2004, IMI Cornelius Inc.  
- 35 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
IntelliCarb Training Manual  
The chart indicates that heavy syrup with 1/2 oz./sec [15mL] flow-rate (per the illustration) can be  
sustained over a horizontal distance of 500 ft. [152M] when 3/8" I.D. [10mm] tubing is used.  
Feet: Take 1% of 500 ft. (500 x 1%) = 5. Which then is multiplied by the 22 ft. vertical, (22 x 5) =  
110 ft.  
Subtract this product from the 500 ft. (500 - 110) =390. The results indicate a 390 ft. tubing run  
(horz./vert.) is possible, while the example only requires a distance of 370 ft.  
Meters: Take 3% of 152M (152 x 3%) = 4.56. Which then is multiplied by the 6.7M vertical, (4.56 x  
6.7) = 30.5M.  
Subtract this product from the 152M (152-30.5)=121.5. The results indicate a 121.5M tubing run  
(horz./vert.) is possible, while the example only requires a distance of 113M.  
NOTE: Had the example above resulted in a value that was equal to, or less than the nec-  
essary total tubing run, consider a larger I.D. tubing or installation of a pump(s) in series  
using a SHURflo Vacuum Regulator.  
Pumps in Series for Long Distances  
Long tubing runs or high vertical lift can be achieved by installing pumps in series. Standard  
SHURflo Beverage pumps are not designed to have positive pressure on the inlet side. The  
SHURflo Vacuum Regulating Valve (VRV) allows the pump to receive liquid from a pressurized  
source. By positioning a VRV at the inlet of the secondary pump, incoming pressure is reduced  
to zero, permitting syrup to be drawn in under vacuum.  
SHURflo can recommend several other methods to meet the requirements for a particular installation,  
including Pressurized Inlet Pumps or Accumulators. Contact SHURflo for more information.  
FIRST  
PUMP  
TO NEXT  
VRV/PUMP  
OR  
SECOND  
PUMP  
GAS IN  
DISPENSER  
B-I-B  
VRV  
GAS TO NEXT  
PUMP  
Pump Sanitizing / Winterizing  
Sanitization of the SHURflo Beverage Gas Pump is required. The frequency of Sanitization is  
dependant on the concentrate type and its manufacturers requirements. Factors which also  
affect the frequency of this procedure are: temperature, concentrate volatility, facility conditions,  
installation and equipment. The sanitizing procedure fulfills a required 10 minute contact time  
with a 200 ppm Sodium Hypochlorite solution. Refer to SHURflo Service Bulletin #1025 for the  
N.S.F. listed sanitizing procedure for the SHURflo pump (only). Pumps that are subjected to  
freezing (below 32° F [0°C]) must be purged of fluid to prevent damage. Refer to SHURflo  
Service Bulletin #1025 for complete winterizing procedure. Refer to the equipment  
manufacturers instructions for sanitizing and winterizing procedure for carbonators, dispensers  
and tubing.  
Pumps that have been winterized and/or out of service for a period of time should be sanitized prior to  
being placed back in service.  
Never apply pressure to the pumps liquid inlet. Pressurized tanks may damage internal  
components if used to sanitize or purge fluid from the pump (operating or not).  
Publication Number: TP01071  
- 36 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Pump Troubleshooting  
DOES NOT OPERATE / GAS APPLIED / DISPENSER VALVE OPEN  
B-I-B empty or inlet tubing pinched off activating vacuum "sold-out".  
Gas regulator over-pressurizing. (Pump stalled)  
Outlet tube kinked or restricted.  
Operated without fluid for excessive period. (Dry run)  
Transfer tube and gas lines contaminated (syrup, rust, oil, etc.) [ensure clean gas supply, change  
out all contaminated pumps]  
Internal damage of control cover.  
OPERATES BUT WILL NOT PRIME / DISPENSER VALVE OPEN  
[consult Start-up Procedure for proper priming]  
Pump valves have no moisture/dry (add water/syrup to the inlet port with pump stroking slowly).  
Vacuum leaks at Q.D., barb fitting clamps, or inlet fitting o-ring.  
Debris in valve seats or warped/swollen valves.  
DOES NOT ACHIEVE SOLD-OUT WITH EMPTY B-I-B  
Vacuum leaks at Q.D., barb fitting clamps, or inlet fitting o-ring.  
Excessive amount of air in B-I-B from improper packaging.  
Air trapped in outlet tubing and/or pump fluid chambers.  
AIR IN INLET AND/OR OUTLET TUBING  
Vacuum leaks at Q.D. o-ring or barb fitting clamps.  
Vacuum leaks at inlet fitting; o-ring pinched or missing.  
Large amounts of air noticed only in the outlet tubing when pump operates (diaphragm/piston assem-  
blies ruptured).  
STROKES WITH DISPENSER VALVE CLOSED  
Air trapped in outlet tubing and/or pump fluid chambers (open outlet and purge air, check for vacuum  
leaks, or air in B-I-B).  
Debris in outlet valves or warped/swollen valves.  
FLUID FROM EXHAUST OR VISIBLE WITHIN GAS INLET TUBING  
Carbonator check valve.  
Ensure clean gas supply.  
Diaphragm/piston assemblies ruptured.  
[change out all contaminated pumps]  
GAS BLOWING FROM EXHAUST CONTINUOUSLY  
Control cover subjected to contaminated gas supply or damaged (ensure clean gas supply, change  
out all contaminated pumps).  
© 2004, IMI Cornelius Inc.  
- 37 -  
Publication Number: TP01071  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
DISPENSER TROUBLESHOOTING  
Should your unit fail to operate properly, check that there is power to the unit and that the hopper  
contains ice. If the unit does not dispense, check the following chart under the appropriate symptoms to  
aid in locating the defect.  
Trouble  
BLOWN FUSE OR CIRCUIT  
BREAKER.  
Probable Cause  
A. Short circuit in wiring  
Remedy  
A. Repair wiring.  
B. Inoperable gate solenoid.  
B. Replace gate solenoid.  
C. Inoperable agitator motor.  
A. No power.  
C. Replace agitator motor.  
A. Restore power.  
GATE DOES NOT OPEN.  
AGITATOR DOES NOT  
TURN.  
B. Bent depressor plate (does not  
actuate switch).  
B. Replace depressor plate.  
C. Inoperable dispensing switch.  
A. Inoperable gate solenoid.  
C. Replace dispensing switch.  
A. Replace gate solenoid.  
GATE DOES NOT OPEN OR  
IS SLUGGISH. AGITATOR  
TURNS.  
B. Excessive pressure against gate  
slide.  
B. Adjust gate slide.  
C. Replace rectifier.  
C. Inoperable rectifier.  
A. Stuck or bent depressor plate  
(does not release switch).  
ICE DISPENSES CONTINU-  
OUSLY.  
A. Replace depressor plate.  
B. Inoperable dispensing switch.  
C. Improper switch installation.  
B. Replace dispensing switch.  
C. Make sure switch is installed  
properly.  
A. Unplug drain.  
SLUSHY ICE. WATER IN  
HOPPER.  
A. Blocked drain.  
B. Unit not sitting level.  
B. Level the unit.  
C. Poor ice quality due to water qual- C. Correct water quality or repair ice-  
ity or icemaker problems.  
maker.  
D. Improper use of flaked ice.  
A. No 24 volts power to faucets.  
D. Call Service Person.  
BEVERAGES DO NOT DIS-  
PENSE  
A. Restore 24 volt power to faucets.  
B. No CO 2 pressure.  
A. Carbonator not operating.  
B. Restore CO 2 pressure.  
A. Repair carbonator.  
BEVERAGES TOO SWEET  
Publication Number: TP01071  
- 38 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
VALVE TROUBLESHOOTING  
Excess Foam  
Excess Foam  
Problem:  
excess foam  
Check  
product  
temperature  
Check  
system  
Temp  
?
above 40°  
below 40°  
Remove  
nozzle  
Check flow  
Clean  
?
yes  
rates  
no  
Check  
system  
Correct  
?
yes  
Clean  
no  
Problem  
corrected  
Set flow rate  
and ratio  
Problem  
corrected  
© 2004, IMI Cornelius Inc.  
- 39 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
IntelliCarb Training Manual  
Off Taste  
Off Taste  
Problem:  
off taste  
Remove  
nozzle  
Clean  
?
yes  
Check ratio  
no  
Check  
system  
Correct  
?
yes  
Clean  
no  
Problem  
corrected  
Set ratio  
Problem  
corrected  
Publication Number: TP01071  
- 40 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
Valve Stuck Open  
Valve Stuck Open  
Problem: valve  
stuck open  
Check  
solenoid  
visually  
Check for  
damaged  
banjos  
working  
?
yes  
(solenoid up)  
no  
(solenoid down)  
Undetermined  
problem call  
800-238-3600  
Damage  
?
no  
Check for  
power at  
solenoid  
yes  
Replace  
dispensing  
switch  
Replace  
banjos  
Power  
?
yes  
no  
Problem  
Problem  
corrected  
corrected  
Clean or  
replace  
solenoid  
Problem  
corrected  
© 2004, IMI Cornelius Inc.  
- 41 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
IntelliCarb Training Manual  
No Product  
No Product  
Problem:  
no product  
Check  
solenoid  
visually  
Check  
system  
Working  
?
yes  
no  
no  
Check  
voltage  
(22-27 AC)  
Check  
transformer  
Check  
resistance  
of coil  
Power  
?
yes  
no  
yes  
Replace  
switch  
Check  
switch  
Check  
system  
40 ohms  
?
no  
yes  
no  
Problem  
corrected  
Replace  
solenoid  
Problem  
corrected  
Publication Number: TP01071  
- 42 -  
© 2004, IMI Cornelius Inc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IntelliCarb Training Manual  
CARBONATOR TROUBLESHOOTING  
WARNING: Disconnect electrical power to the unit to prevent personal injury before attempting any  
internal maintenance. Only qualified personnel should service the internal components or the elec-  
trical wiring.  
If repairs to the carbonated water or the plain water systems must be made, disconnect electrical  
power to the Unit, then shut off CO2 and plain water sources. Dispense from dispensing valve until  
carbonator tank CO2 pressure has been relieved.  
Trouble  
Probable Cause  
Remedy  
CARBONATOR WILL NOT  
A. Power cord unplugged or circuit  
breaker open in panel box.  
Inoperative carbonator.  
A. Plug in power cord or reset circuit  
OPERATE.  
breaker.  
B. Call a qualified Service Person.  
A. Call a qualified Service Person.  
A. Call a qualified Service Person.  
B. Inoperative carbonator.  
A. Carbonator internal problem.  
WATER PUMP MOTOR  
WILL NOT SHUT OFF.  
ERRATIC CYCLING OF  
A. Carbonator internal problem.  
CARBONATOR.  
WATER PUMP MOTOR  
OPERATES BUT WATER  
PUMP DOES NOT PUMP  
WATER.  
A. Carbonator internal problems or a  
water supply line problem.  
A. Call a qualified Service Person.  
CARBONATOR CARBON-  
ATED WATER CAPACITY  
TOO LOW  
A. Carbonator internal problems or a  
water supply line problem.  
A. Call a qualified Service Person.  
B. Replace water filter.  
B. Water filter clogged.  
Solid State Carbonator Level Control  
MATING CONNECTION  
GREEN  
ORANGE  
RED  
GROUND  
TERMINAL  
WIRING  
HARNESS  
C
PROBE ASSY  
HI  
LO  
SHORT ELECTRODE  
LONG ELECTRODE  
CARBONATOR TANK  
CARBONATED LIQUID  
LEVEL CONTROL  
FIGURE 40  
NOTE: Carbonators that are equipped with a pump safety thermostat will have a black wire  
instead of green connected to the C terminal.  
Test Solid State Level Control  
2ND JUMP  
1. Remove all wires and:  
Carb. motor should run.  
C
1ST JUMP  
2. Jumper C to HI:  
HI ORANGE  
LO RED  
Carb. motor should stop. Do not remove jumper wire.  
3. Jumper LO to C:  
Motor should remain stopped.  
4. Remove 1st jumper from C and HI:  
Motor should remain stopped.  
FIGURE 41  
5. Remove 2nd jumper from C and LO:  
Motor should start.  
If level control passes all above test, replace probe.  
© 2004, IMI Cornelius Inc.  
- 43 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Publication Number: TP01071  
IMI Cornelius Inc.  
800-238-3600  
Download from Www.Somanuals.com. All Manuals Search And Download.  

ColdTech Refrigerator JBB 58 User Manual
Cooper Lighting Indoor Furnishings Area Luminaire User Manual
CP TECHNOLOGIES Automobile Alarm AS 9495 4P User Manual
Crest Audio Stereo Amplifier CC 1800 User Manual
Crosley Radio Camcorder Accessories AC21 User Manual
Cypress Clock CY14B101K User Manual
Dacor Convection Oven DCM24 User Manual
Dynaudio Speaker IP 24 User Manual
Fujitsu TV Mount MB2147 01 User Manual
Gigabyte Speaker System GP S7500 User Manual