Bradford White Corp Water Heater BNTH User Manual

Installation and Operation Instructions  
Document 1243  
Installation and Operation  
Instructions for  
BRUTE ELITE  
Modulating Boiler  
Model BNTH  
Sizes 080–850 MBTU/h  
Water Heater  
Model BNTV  
Sizes 150–850 MBTU/h  
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,  
qualified in hot water boiler and heater installation and maintenance. Improper installation and/or operation  
could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or  
death. Improper installation and/or operation will void the warranty.  
AVERTISSEMENT  
WARNING  
Assurez-vous de bien suivres les instructions  
If the information in this manual is not  
données dans cette notice pour réduire au  
followed exactly, a fire or explosion may  
minimum le risque d’incendie ou d’explosion ou  
result causing property damage, personal  
pour éviter tout dommage matériel, toute  
injury or loss of life.  
blessure ou la mort.  
Ne pas entreposer ni utiliser d’essence ni  
d’autres vapeurs ou liquides inflammables dans  
le voisinage de cet appareil ou de tout autre  
appareil.  
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:  
• Ne pas tenter d’allumer d’appareils.  
• Ne touchez à aucun interrupteur. Ne pas vous  
servir des téléphones dansle bâtiment où vous  
vous trouvez.  
Do not store or use gasoline or other  
flammable vapors and liquids in the vicinity  
of this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electrical switch; do not  
use any phone in your building.  
• Immediately call your gas supplier from a  
nearby phone. Follow the gas supplier's  
instructions.  
• Appelez immédiatement votre fournisseur de  
gaz depuis un voisin. Suivez les instructions  
du fournisseur.  
• If you cannot reach your gas supplier, call  
the fire department.  
• Si vous ne pouvez rejoindre le fournisseur de  
gaz, appelez le sservice des incendies.  
Installation and service must be performed by  
a qualified installer, service agency, or gas  
supplier.  
L’installation et l’entretien doivent être assurés par  
un installateur ou un service d’entretien qualifié ou  
par le fournisseur de gaz.  
238-49220-00A REV 4/11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 3  
SECTION 9.  
SECTION 11.  
Maintenance  
Modes of Operation  
9.1  
9.2  
9.3  
Hydronic Heating Demand ............................ 40  
Hydronic Heating with Outdoor Reset ........... 40  
Hydronic Heating with Domestic Hot  
Water (DHW) Priority..................................... 40  
11.1  
11.2  
System Maintenance ..................................... 46  
Appliance Maintenance and Component  
Description .................................................... 46  
11.2.1 Burner............................................................ 46  
11.2.2 Modulating Gas Valve / Venturi ..................... 46  
11.2.3 Appliance Control .......................................... 46  
11.2.4 Ignitor Assembly ............................................ 47  
11.2.5 Flame Sensor ................................................ 47  
11.2.6 Transformer with Integral Circuit Breaker ...... 48  
11.2.7 Blower ........................................................... 48  
11.2.8 Heat Exchanger Coils.................................... 48  
11.2.9 Gas Pressure Switches (optional) ................. 49  
11.2.10 Gas Conversion............................................. 49  
9.4  
9.5  
9.6  
Hydronic Heating Using External  
Modulation Control ........................................ 40  
Hydronic Heating Using Local Lead-Lag/  
Cascading Feature ........................................ 41  
Hydronic Heating Using Local Lead-Lag/  
Cascading Feature with Indirect Hot Water ... 41  
9.7  
9.8  
9.9  
Warm Weather Shutdown ............................. 41  
Domestic Hot Water Demand (BNTV only) ... 41  
Domestic Hot Water Heating Using  
External Modulation Control .......................... 42  
9.10  
Domestic Hot Water Heating Using Local  
Section 12.  
Lead-Lag/Cascading Feature ........................ 42  
Trouble Shooting  
12.1  
12.2  
12.3  
Sequence of Operation ................................. 49  
Short Cycling ................................................. 49  
Error Codes ................................................... 49  
Section 10.  
Operating Instructions  
10.1  
10.2  
Filling the Boiler System ................................ 43  
Operating the Burner and Set Up .................. 43  
Section 13.  
Replacement Parts  
10.2.1 Burner Operation ........................................... 43  
10.2.2 Boiler Setup and Adjustment ......................... 44  
10.3  
10.4  
13.1  
13.2  
General Information....................................... 52  
Parts List ....................................................... 52  
Shutting Down Brute Elite.............................. 44  
To Restart Brute Elite .................................... 44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 4  
All installations must be made in accordance with  
1) American National Standard Z223.1/NFPA54-Latest  
Edition “National Fuel Gas Code” or 2) CSA B149.1  
“Natural Gas and Propane Installation Code” and with  
the requirement of the local utility or other authorities  
having jurisdiction. Such applicable requirements take  
precedence over the general instructions contained herein.  
All electrical wiring is to be done in accordance  
with the local codes, or in the absence of local codes,  
with: 1) The National Electrical Code ANSI/NFPA No.  
70-latest Edition, or 2) CSA STD. C22.1 “Canadian  
Electrical Code - Part 1”. This appliance must be  
electrically grounded in accordance with these codes.  
SECTION 1.  
General Information  
WARNING  
Brute Elite units must be installed in accordance with  
the procedures detailed in this manual, or the  
Bradford White warranty will be voided. The  
installation must conform to the requirements of the  
local jurisdiction having authority, and, in the United  
States, to the latest edition of the National Fuel Gas  
Code, ANSI Z223.1/NFPA54. In Canada, the  
installation must conform to the latest edition of CSA  
B149.1 Natural Gas and Propane Gas Installation  
Code, and/or local codes. Where required by the  
authority having jurisdiction, the installation of Brute  
Elite boilers must conform to the Standard for  
Controls and Safety Devices for Automatically Fired  
Boilers, ANSI/ASME CSD-1. Any modifications to the  
boiler, its gas controls, or wiring may void the  
warranty. If field conditions require modifications,  
consult the factory representative before initiating  
such modifications.  
1.2 Model Identification  
Consult the rating plate on the unit. The following  
information describes the model number structure.  
(1-3) Model Series Designation  
B N T = Brute Elite  
(4) Usage  
H = Hydronic  
V = Volume Water  
(5-7) Size  
0 8 0 = 80,000 BTU/hr input  
1 0 5 = 105,000 BTU/hr input  
1 5 0 = 150,000 BTU/hr input  
1 9 9 = 199,000 BTU/hr input  
2 1 0 = 210,000 BTU/hr input  
2 8 5 = 285,000 BTU/hr input  
3 9 9 = 399,000 BTU/hr input  
5 0 0 = 500,000 BTU/hr input  
6 0 0 = 600,000 BTU/hr input  
7 5 0 = 750,000 BTU/hr input  
8 5 0 = 850,000 BTU/hr input  
1.1 Introduction  
This manual provides information necessary for  
the installation, operation, and maintenance of Bradford  
White Brute Elite appliances. Read it carefully before  
installation.  
All application and installation procedures should  
be reviewed completely before proceeding with the  
installation. Consult the Bradford White factory, or  
local factory representative, with any problems or  
questions regarding this equipment. Experience has  
shown that most operating problems are caused by  
improper installation.  
Brute Elite is protected against over pressurization.  
A pressure relief valve is included with each Brute Elite.  
Some Brute Elites may require that the PRV be installed  
prior to filling the system. Refer to Figures 1-7 for PRV  
locations.  
(8) Fuel  
N = Natural Gas  
P = LP Gas  
(9) Options Code  
X = Standard Unit  
C = Canadian  
D = Canadian CSD-1  
J = CSD-1, FM, GAP, IL Code (size 500-850 only)  
(10) Pump Options  
N = Pump included (80-500 only)  
X = No pump (285-850)  
(11) Revision  
IMPORTANT: The inlet gas pressure to the appliance  
must not exceed 13" W.C. (3.2kPa).  
2 = Second version  
Model Nomenclature  
1
2
3
T
4
5
6
7
8
9
10  
11  
2
B
N
SERIES  
SIZE  
USAGE  
H - HYDRONIC  
FUEL  
N - NATURAL  
P - PROPANE  
OPTIONS CODE  
X - STANDARD  
C - CANADIAN  
PUMP OPTIONS  
REVISION  
2 - SECOND  
MBTU/h  
B
N
T
N - PUMP INCL.  
0
1
1
1
2
2
3
5
6
7
8
8
0
5
9
1
8
9
0
0
5
5
0
5
0
9
0
5
9
0
0
0
0
(80-500 only)  
V - VOLUME  
WATER  
X - NO PUMP  
D - CANADIAN,  
(285-850)  
CSD-1  
J - CSD-1,  
FM, GAP,  
IL (500-850 only)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 5  
Figure 1. Location of Components, Sizes 80–105.  
Figure 2. Location of Components, Sizes 150-210.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 6  
Figure 3. Location of Components, Size 285.  
Figure 4. Location of Components, Size 399.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 7  
Figure 5. Location of Components, Size 500.  
Figure 6. Location of Components, Size 600.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 8  
Figure 7. Location of Components, Sizes 750 and 850.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 9  
1.3 Appliance Overview  
1.5 Unpacking  
See Figures 1 through 7.  
The Brute Elite is shipped in a single crate with the  
following standard components packed with the  
appliance (see Figure 8):  
1.4 Warranty  
A. exhaust vent terminal (US only)  
Bradford White’s Brute Elite appliances are  
covered by a limited warranty.  
B. air intake terminal  
C. temperature/pressure gauge kit  
All warranty claims must be made to an authorized  
Bradford White representative. Claims must include the  
serial number and model (this information can be found  
on the rating plate), installation date, and name of the  
installer. Shipping costs are not included in the warranty  
coverage.  
D. circulator pump/wire harness (units with pump)  
E. CPVC exhaust pipe section (80-500) (US only)  
F. outdoor/system sensor kit  
G. flow switch kit (399-850)  
H. alternate size vent/terminal screens  
J. exhaust vent adapter CPVC/ST ST (750-850)  
K. 4x6 PVC adapter with 4x7 PVC pipe section  
(750-850) (not to be used on exhaust in Canada)  
Some accessory items may be shipped in separate  
packages. Verify receipt of all packages listed on the  
packing slip. Inspect everything for damage  
immediately upon delivery, and advise the carrier of any  
shortages or damage. Any such claims should be filed  
with the carrier. The carrier, not the shipper, is  
responsible for shortages and damage to the  
shipment whether visible or concealed.  
1. Remove all packing and tie-down materials.  
2. Check contents of the carton against items shown.  
1.6 Dimensions  
Dimensions are shown in Figure 9.  
Figure 8. Contents of Shipping Package.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 10  
CONNECTIONS  
W
L
H
AIR INLET  
VENT  
GAS  
NPT  
½
½
½
SIZE  
80  
105  
150  
IN CM  
IN  
CM  
IN CM  
IN CM  
IN CM  
25 64 19½ 49 38¼ 97  
25 64 19½ 49 38¼ 97  
25 64 19½ 49 38¼ 97  
2
2
3
3
5.1  
5.1  
7.6  
7.6  
2
2
3
3
5.1  
5.1  
7.6  
7.6  
199/210 25 64 26¾ 68 38¼ 97  
½
285  
399  
500  
600  
750  
850  
25 64 26¾ 68 38¼ 97 11 11  
25 64 31½ 80 38¼ 97 11 11  
25 64 37¾ 96 38¼ 97 11 11  
25 64 37¾ 96 38¼ 97 11 11  
¾
¾
1
1
25 64  
51 130 38¼ 97 11 17 1½  
25 64 55¼ 130 38¼ 97 11 17 1½  
Dimensions are nominal and are shown in inches, cm.  
Brute Elite is shipped with adapters for the air and vent that accept  
*
standard pipe of the proper size and type.  
A
B
C
D
E
F
G
J
K
M
N
SIZE  
IN CM  
IN CM  
IN CM  
IN CM  
IN  
CM  
IN CM  
IN CM  
IN  
CM  
IN CM  
IN  
CM  
IN CM  
80 BNTH 13½ 34 24 18¼ 46 19 10¾ 28 11¾ 30 13¾ 35  
21 53 10¾ 27 15¼ 39 13 33  
105 BNTH 13½ 34  
150 BNTH 13¼ 34 14 18¼ 46 8  
150 BNTV 13¼ 34 14 19 48 8  
210 BNTH 20½ 52 14 18¼ 46 8  
199 BNTV 20½ 52 14 19 48 8  
8
21 18¼ 46  
6
16 10¾ 28 11¾ 30 14¼ 36  
21 53  
19 14¼ 36 19½ 49  
19 14¼ 36 19½ 49  
22 15¼ 39 13 33  
19 15¼ 39 13 33  
19 15¼ 39 13 33  
10¾ 28  
10¾ 28  
17¾ 45  
17¾ 45  
19 14¼ 36 19½ 49 11¾ 30 15¼ 39 13 33  
19 14¼ 36 19½ 49 11¾ 30 15¼ 39 13 33  
285 BNTH 20¼ 52 19 19¼ 49 16 11¼ 29 13½ 34  
285 BNTV 20¼ 52 19 19¾ 50 16 11¼ 29 13½ 34  
14 36  
14 36  
15 38  
15 38  
17 43 18¾ 48 13 33  
17 43 18¾ 48 13 33  
399 BNTH 25 64 13 19¼ 49 11 14¾ 37 18½ 47 19¼ 49 16½ 42 21¾ 55 18¾ 48 13 33  
399 BNTV 25 64 13 19¾ 50 11 14¾ 37 18½ 47 19¼ 49 16½ 42 21¾ 55 18¾ 48 13 33  
500 BNTH 30¼ 77 13 19½ 50 11 15¼ 38  
500 BNTV 30¼ 77 13 19¾ 50 11 15¼ 38  
20 51 20½ 52  
20 51 20½ 52  
19 48  
19 48  
19 48  
26 66 18¾ 48 13 33  
26 66 18¾ 48 13 33  
26 66 18¾ 48 21  
600 (both) 29¾ 76  
750 (both) 35½ 90  
850 (both) 39¾ 101  
5
6
6
13 19½ 50 11  
15 19½ 50 13  
15 19½ 50 13  
15 38  
19 48 40½ 103 3¼  
19 48 44¾ 114 3½  
20 51  
3
8
8
9
19 48 30¾ 78 18¾ 48 21  
19 48 35 89 18¾ 48 21  
Figure 9. Dimensional Drawing, Sizes 80-500.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 11  
SECTION 2.  
Locating the Appliance  
SUGGESTED SERVICE ACCESS CLEARANCE  
2.1 Locating the Appliance  
APPLIANCE  
SURFACE  
INCHES  
CM  
Brute Elite is for indoor installations only.  
Left Side  
Right Side  
Top  
Back  
1
2.5  
The appliance should be located to provide  
12  
24  
6
31  
61  
15  
15  
61  
61  
clearances on all sides for maintenance and inspection.  
It should not be located in an area where leakage of any  
connections will result in damage to the area adjacent to  
the appliance or to lower floors of the structure.  
When such a location is not available, it is  
Closet, Front (285-500)  
Alcove, Front (285-500)  
Front (600-850)  
Vent  
6
24  
24  
recommended that a suitable drain pan, adequately  
drained, be installed under the appliance.  
The appliance is design certified by CSA-  
Certified by CSA for zero clearance to  
combustible materials on all sides.  
International for installation on combustible flooring; in  
basements; in closets, utility rooms or alcoves. Brute  
Elite Boilers must never be installed on carpeting.  
The location for the appliance should be chosen with  
regard to the vent pipe lengths and external plumbing  
and on a level surface. The unit shall be installed such  
that the gas ignition system components are protected  
from water (dripping, spraying, rain, etc.) during  
operation and service (circulator replacement, control  
replacement, etc.). When vented vertically, the Brute  
Elite must be located as close as practical to the vertical  
section of the vent. If the vent terminal and/or  
combustion air terminal terminate through a wall, and  
there is potential for snow accumulation in the local  
area, both terminals should be installed at an appropriate  
level above grade or the maximum expected snow line.  
The dimensions and requirements that are shown  
in Table 1 should be met when choosing the locations  
for the appliance.  
Table 1. Clearances.  
INTAKE / EXHAUST  
STANDARD MAX EQUIV.  
OPTIONAL MAX EQUIV.  
SIZE  
VENT  
FT.  
M
VENT  
FT.  
M
80  
105  
150  
2"  
2"  
3"  
40  
6.1  
3"  
100  
30.5  
40  
100  
100  
100  
100  
100  
100  
40  
6.1  
30.5  
30.5  
30  
30  
30  
30  
6.1  
6.1  
3"  
100  
100  
100  
30.5  
30  
30  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
6"  
199/210 3"  
285  
399  
500  
600  
750  
850  
4"  
4"  
4"  
4"  
4"  
4"  
40  
6"  
Installations in the U.S. require exhaust vent pipe that is a combination  
of PVC & CPVC complying with ANSI/ASTM D1785 F441 or stainless  
steel complying with UL1738. Installations in Canada require exhaust  
vent pipe that is certified to ULC S636.  
2.2 Locating Appliance for Correct Vent  
Distance from Outside Wall or  
Roof Termination  
Intake (air) pipe must be PVC or CPVC that complies with ANSI/ASTM  
D1785 F441, ABS that complies with ANSI/ASTM D1527 or  
galvanized material.  
The forced draft combustion air blower in the  
appliance has sufficient power to vent properly when  
the guidelines in Table 2 are followed.  
NOTE: When located on the same wall, the Brute Elite  
combustion air intake terminal must be installed a  
minimum of 12" below the exhaust terminal.Models 399-  
850 also require a minimum horizontal distance from  
intake to exhaust terminal of 36".  
Installer must comply fully with manufacturer's installation instructions,  
including use of minimum exhaust length CPVC, to maintain ANSI  
Z21.13 safety certification.  
Closet and alcove installations do not allow the use of PVC under any  
circumstances  
To calculate max equivalent length, measure the linear feet of the  
For concentric vent terminal kit (optional), follow  
installation instructions included with the kit.  
pipe, and add 5 feet (1.5m) for each elbow used.  
Table 2. Vent / Air Pipe Sizes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 12  
Method 1: Two permanent openings, one  
SECTION 3.  
commencing within 12" (300mm) of the top and one  
commencing within 12" (300mm) of the bottom, of the  
enclosure shall be provided. The openings shall  
communicate directly, or by ducts, with the outdoors or  
spaces that freely communicate with the outdoors.  
When directly communicating with the outdoors, or  
when communicating to the outdoors through vertical  
ducts, each opening shall have a minimum free area of 1  
square inch per 4000 Btu/hr (550 square mm/kW) of  
total input rating of all equipment in the enclosure.  
When communicating to the outdoors through  
horizontal ducts, each opening shall have a minimum  
free area of not less than 1 square inch per 2000 Btu/hr  
(1100 square mm/kW) of total input rating of all  
equipment in the enclosure.  
Venting and Combustion Air  
3.1 Combustion Air  
Brute Elite boilers and water heaters must have  
provisions for combustion and ventilation air in  
accordance with the applicable requirements for  
Combustion Air Supply and Ventilation in the National  
Fuel Gas Code, ANSI Z223 1; or in Canada, the Natural  
Gas and Propane Installation Code, CSA B149.1. All  
applicable provisions of local building codes must also  
be adhered to.  
A Brute Elite unit can take combustion air from  
the space in which it is installed, or the combustion  
air can be ducted directly to the unit. Ventilation air  
must be provided in either case.  
Method 2: One permanent opening, commencing  
within 12" (300mm) of the top of the enclosure, shall be  
permitted. The opening shall directly communicate with  
the outdoors or shall communicate through a vertical or  
horizontal duct to the outdoors or spaces that directly  
communicate with the outdoors and shall have a  
minimum free area of 1 square inch per 3000 Btu/hr  
(734 square mm/kW) of the total input rating of all  
equipment located in the enclosure. This opening must  
not be less than the sum of the areas of all vent  
connectors in the confined space.  
Other methods of introducing combustion and  
ventilation air are acceptable, providing they conform to  
the requirements in the applicable codes listed above.  
In Canada, consult local building and safety codes or,  
in absence of such requirements, follow CAN/CGA B149.  
3.1.2 Ducted Combustion Air  
3.1.1 Combustion Air From Room  
In the United States, the most common  
requirements specify that the space shall communicate  
with the outdoors in accordance with method 1 or 2,  
which follow. Where ducts are used, they shall be of the  
same cross-sectional area as the free area of the  
openings to which they connect.  
HORIZONTAL INTAKE AND EXHAUST PVC VENT TERMINAL KITS  
2" PVC  
Standard Concentric  
3" PVC  
4" PVC  
Standard  
6" PVC  
Standard  
SIZE  
Standard  
Concentric  
CA006000 CA005900 239-44069-01  
80  
105  
included optional  
included optional  
optional  
optional  
included  
included  
optional  
n/a  
optional  
optional  
optional  
optional  
optional  
n/a  
n/a  
n/a  
n/a  
n/a  
150  
199/210  
285  
399  
500  
600  
750  
850  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
The combustion air can be taken through the wall, or  
through the roof. When taken from the wall, it must be  
taken from out-of-doors by means of the horizontal wall  
terminal, shown in Table(s) 3. See Table 2 to select the  
appropriate diameter air pipe. When taken from the roof, a  
field-supplied rain cap or an elbow arrangement must be  
used to prevent entry of rain water (see Figure10).  
Use ABS, PVC, CPVC or galvanized pipe for the  
included  
included  
included  
included  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
n/a  
optional  
included  
included  
n/a  
n/a  
n/a  
n/a  
n/a  
Concentric vent terminal = 10 ft. pipe length.  
Table 3a. PVC Vent Terminal Kits.  
PRO TECH (FasNSeal)  
HEAT FAB (Saf-T-Vent)  
Z FLEX (Z-Vent)  
Flue  
SIZE  
Boiler  
Flue  
Intake Air  
Termination  
FSAIH04  
303888  
Boiler  
Adapter  
Intermediate  
Adapter  
Flue  
Intake Air  
Boiler  
Intake Air  
Adapter  
Termination  
FSBS4  
Termination Termination  
Adapter  
Termination  
2SVSTP04  
2SVSRCX04  
Termination  
9492  
399-600  
750-850  
F303759  
KB285600 9454BUREZ-1*  
9414TERM  
5400CI  
2SVSLA04  
2SVSTEX0490  
FSRC4(R.C)  
F303759  
(intake only)  
FSAIH04  
303888  
FSBS6  
Table 3b. Approved Stainless Steel Terminations and Adapters.  
INSTALLATION STANDARDS  
MATERIAL  
UNITED STATES  
CANADA  
ABS  
ANSI/ASTM D1527  
PVC, sch 40  
CPVC, sch 40  
Single wall galv. steel  
ANSI/ASTM D1785 or D2665  
ANSI/ASTM F441  
26 gauge  
Air pipe material must be chosen  
based upon the intended application of the boiler.  
Table 4. Required Combustion Air Pipe Material.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 13  
combustion air intake (see Table 4), sized per Table 2.  
Route the intake to the boiler as directly as possible. Seal  
all joints. Provide adequate hangers. The unit must not  
support the weight of the combustion air intake pipe.  
Maximum linear pipe length allowed is shown in Table 2.  
Subtract 5 allowable linear ft. (1.5m) for every elbow used.  
The connection for the intake air pipe is at the top of  
the unit (see Figure 9a or Figure 9b).  
The unit’s vent can terminate through the roof, or  
through an outside wall.  
When using PVC/CPVC for vent material, venting  
must be connected to the CPVC section included with  
Brute Elite sizes 80-600. The CPVC vent section  
included with the Brute Elite may be broken by CPVC  
fittings if necessary, but never reduced in total length.  
See Table 2 to select the appropriate vent pipe diameter.  
Vent pipe must pitch upward, toward the vent terminal,  
not less than 1/4" per foot, so that condensate will run  
back to the Brute Elite to drain. Route vent pipe to the  
heater as directly as possible. Seal all joints and provide  
adequate hangers as required in the venting system  
manufacturer’s Installation Instructions. Horizontal  
portions of the venting system must be supported to  
prevent sagging and may not have any low sections that  
could trap condensate. The unit must not support the  
weight of the vent pipe. Please see Table 2 for proper  
diameter vs. length allowed.  
In addition to air needed for combustion, air shall  
also be supplied for ventilation, including air required for  
comfort and proper working conditions for personnel.  
3.2 Venting  
WARNING  
Failure to use CPVC or stainless steel venting for the  
first 20" (285-600) / 30" (80-210) of vent material or for  
any part of the venting that is installed inside a closet  
may lead to property damage, personal injury or death.  
The proper length of this material is supplied with boiler.  
Boilers in U.S. may use pipe included with boiler.  
IMPORTANT NOTE ABOUT COMMON VENTING: A  
single vent that is shared by multiple Brute Elite units  
MUST be engineered by a competent venting  
specialist, and involves the selection of draft inducing  
equipment, hardware and controls to properly balance  
flue gas pressures. Do not common vent Brute Elite  
WARNING  
Failure to use the appropriate vent material, installation  
techniques, glues/sealants could lead to vent failure  
causing property damage, personal injury or death.  
WARNING  
All venting must be installed according to this manual  
and any other applicable local codes, including but not  
limited to, ANSI Z223.1/NFPA 54, CSA B149.1,  
CSAB149.2 and ULC-S636. Failure to follow this  
manual and applicable codes may lead to property  
damage, severe injury, or death.  
The flue temperature of the Brute Elite changes  
dramatically with changes in operating water  
temperature. Therefore, it is necessary to assess the  
application of the boiler to determine the required  
certified vent class. If the Brute Elite is installed in  
an application where the ambient temperature is  
elevated, and/or installed in a closet/alcove, CPVC or  
stainless steel material is required. If the system  
temperatures are unknown at the time of  
installation, class IIB or higher venting material is  
recommended.  
The Brute Elite is a Category IV appliance and  
may be installed with PVC and CPVC that complies  
with ANSI/ASTM D1785 F441, or a stainless steel  
venting system that complies with UL 1738 Standard  
(see Table 5).  
Figure 10. Combustion Air and Vent Through Roof.  
INSTALLATION STANDARDS  
MATERIAL  
UNITED STATES  
UL 1738  
ANSI/ASTM D178  
ANSI/ASTM F441  
CANADA  
Stainless Steel  
PVC, sch 40  
CPVC, sch 40  
Venting must be ULC-S636 certified for use as  
venting material. The venting material must be chosen  
based upon the intended application of the boiler.  
Table 5. Required Exhaust Vent Material.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 14  
units unless the vent system meets this  
one must be installed in the vent system external to the  
Brute Elite unit. A flue gas sampling port available as a  
component of the ULC S636 certified vent system is  
preferred. However, if one is not available with the  
certified vent system, Bradford White suggests using a  
tee with the branch connection sized to allow for  
insertion of a flue gas analyzer probe. The branch  
connection must be resealable with a cap or other by  
other means to ensure the vent system remains sealed  
(Figure 11).  
Consideration must be given to the placement and  
orientation of the flue gas sampling port to ensure that  
condensate is free to flow back into the Brute Elite unit  
and not collect anywhere in the vent system - including  
in the flue gas sampling port.  
An exhaust vent terminal must be installed. If an  
exhaust vent terminal is not available with the certified  
vent system, Bradford White suggests the use of a  
coupler fitting from the certified vent system into which  
the vent terminal screen, included with the Brute Elite  
and shown in the Unpacking section of the Brute Elite  
Installation & Operating Instructions, be installed. Be  
sure to install and terminate both vent and combustion  
air pipes per the Venting and Combustion Air section of  
the Brute Elite instructions.  
requirement. Brute Elite units are never permitted  
to share a vent with Category I appliances.  
A condensate drain trap is built into Brute Elite.  
Connect a 3/4" PVC pipe between the drain  
connection and a floor drain (or condensate pump if a  
floor drain is not accessible).  
The condensate drain must be installed so as to  
prevent accumulation of condensate. When a con-  
densate pump is not used, the tubing must continuously  
slope downward toward the drain with no spiraling.  
Consult local codes for disposal method.  
Caution  
Condensate is mildly acidic (pH5), and may harm  
some floor drains and/or pipes, particularly those that  
are metal. Ensure that the drain, drainpipe, and  
anything that will come in contact with the  
condensate can withstand the acidity, or neutralize  
the condensate before disposal. Damage caused by  
failure to install a neutralizer kit or to adequately  
treat condensate will not be the manufacturer’s  
responsibility.  
3.2.1 Venting Requirements Unique to  
Canada  
3.3 Locating Vent & Combustion Air  
Brute Elite boilers and water heaters are Vent  
Category IV appliances. Per the requirements of CAN/  
CSA-B149.1, only BH vent systems can be connected to  
these units and such vent systems, either ULC S636  
certified stainless steel or other ULC S636 certified BH  
vent (eg. plastics) must be installed per the vent  
manufacturer's certified installation instructions.  
As a result, two items listed in the Unpacking  
section (Figure 8) are not included with Brute Elite  
units for Canada (underlined):  
Terminals  
3.3.1 Side Wall Vent Terminal  
The appropriate Bradford White side wall vent  
terminal must be used. The terminal must be located in  
accordance with ANSI Z223.1/NFPA 54 and applicable  
local codes. In Canada, the installation must be in  
accordance with CSA B149.1 or .2 and local applicable  
codes. Consider the following when installing the  
terminal:  
A. exhaust vent terminal (not included)  
B. air intake terminal  
C. temperature/pressure gauge kit  
D. circulator pump/wire harness (units with pump)  
E. CPVC exhaust pipe section (80-500) (not incl.)  
F. outdoor/system sensor kit  
G. flow switch kit (399-850)  
H. alternate size vent/terminal screens  
J. exhaust vent adapter CPVC/ST ST (750-850)  
It is the responsibility of the appropriately licensed  
technician installing this Brute Elite unit to use ULC  
S636 certified vent material consistent with the  
requirements as described in the Venting and  
Combustion Air section.  
IMPORTANT! It is also the responsibility of the  
installer to ensure that a flue gas sampling port is  
installed in the vent system. This flue gas sampling port  
must be installed near the flue connection of the Brute  
Elite unit: within 2 feet of the flue connection. There is  
no flue gas sampling port internal to the Brute Elite, so  
Figure 11. Test Port.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 15  
1. Figure 12 shows the requirements for mechanical  
vent terminal clearances for the U.S. and Canada.  
2. Vent terminals for condensing appliances or  
appliances with condensing vents are not  
12" (30cm) away from the air inlet. Vent outlets  
for models 399-850 must be at least 12" above the  
top of the air inlet, and must be at least 36" (90cm)  
horizontally from the air inlet (see Figure 14).  
permitted to terminate above a public walkway, or  
over an area where condensate or vapor could  
create a nuisance or hazard.  
3.3.3 Vertical Vent Terminal  
When the unit is vented through the roof, the vent  
must extend at least 3 feet (0.9m) above the point at  
which it penetrates the roof. It must extend at least 2  
feet (0.6m) higher than any portion of a building within  
a horizontal distance of 10 feet (3.0m), and high enough  
above the roof line to prevent blockage from snow. The  
vent terminal included with the Brute Elite can be used  
in both vertical and horizontal applications. When the  
combustion air is taken from the roof, the combustion  
air must terminate at least 12" (30cm) below the vent  
terminal (see Figure 11).  
3. Locate the vent terminal so that vent gases cannot  
be drawn into air conditioning system inlets.  
4. Locate the vent terminal so that vent gases cannot  
enter the building through doors, windows, gravity  
inlets or other openings. Whenever possible, avoid  
locations under windows or near doors.  
5. Locate the vent terminal so that it cannot be  
blocked by snow. The installer may determine  
that a vent terminal must be higher than the  
minimum shown in codes, depending upon local  
conditions.  
6. Locate the terminal so the vent exhaust does not  
settle on building surfaces or other nearby objects.  
Vent products may damage surfaces or objects.  
7. If the boiler or water heater uses ducted  
combustion air from an intake terminal located on  
the same wall, see Figures 12-14 for proper  
spacing and orientation.  
If the vent termination is located in an area  
exposed to high winds, an optional PVC tee (the same  
diameter as the vent pipe) may be used. The tee'd vent  
termination offers greater protection from wind related  
operating issues.  
3.3.4 Vertical Combustion Air Terminal  
When combustion air is taken from the roof, a  
field-supplied rain cap or an elbow arrangement must be  
used to prevent entry of rain water (see Figure 11). The  
opening on the end of the terminal must be at least 12"  
(30cm) above the point at which it penetrates the roof,  
and high enough above the roof line to prevent blockage  
from snow. When the vent terminates on the roof, the  
combustion air must terminate at least 12" (30cm)  
below the vent terminal.  
3.3.5 Installations in the Commonwealth of  
Massachusetts  
In Massachusetts the following items are required if  
the side-wall exhaust vent termination is less than seven (7)  
feet above finished grade in the area of the venting,  
including but not limited to decks and porches. From  
Massachusetts Rules and regulations 248 CMR 5.08  
1. Installation of Carbon Monoxide Detectors  
At the time of installation of the side wall vented  
gas fueled appliance, the installing plumber or gas-  
fitter shall observe that a hard-wired carbon monox-  
ide detector with an alarm battery back-up is instal-  
led on the floor level where the gas appliance is to  
be installed. In addition, the installing plumber or  
gasfitter shall observe that a battery operated or  
hard-wired carbon monoxide detector with an alarm  
is installed on each additional level of the dwelling,  
building or structure served by the side-wall hori-  
zontally vented gas fueled equipment. It shall be the  
responsibility of the property owner to secure the  
services of qualified licensed professionals for in-  
stallation of hard-wired carbon monoxide detectors.  
a. In the event that the side-wall horizontally vented  
gas fueled equipment is installed in a crawl space or  
an attic, the hard-wired carbon monoxide with alarm  
and battery back-up may be installed on the next  
adjacent floor level.  
3.3.2 Side Wall Combustion Air Terminal  
The side wall combustion air terminal, or  
concentric terminal (see Table 3), must be used when  
the heater takes air from a side wall. Contact Bradford  
White for AL29-4C termination fittings. Consider the  
following when installing the terminal (see Figures 12-  
14):  
1. Do not locate the air inlet terminal near a source of  
corrosive chemical fumes (e.g., cleaning fluid,  
chlorine compounds, etc.)  
2. Locate the terminal so that it will not be subject to  
damage by accident or vandalism. It must be at  
least 7 feet (2.1m) above a public walkway.  
3. Locate the combustion air terminal so that it  
cannot be blocked by snow. The National Fuel Gas  
Code requires that it be at least 12 inches (30cm)  
above grade, but the installer may determine it  
should be higher, depending upon local conditions.  
4. If the Brute Elite is side-wall vented to the same  
wall, locate the vent terminal at least 1 foot (0.3m)  
above the combustion air terminal.  
5. For concentric vent, follow instructions  
included with vent kit.  
6. Multiple vent kits should be installed such that the  
horizontal distance between outlet group and inlet  
group is 36" (90cm) (see Figure 13).  
b. In the event that the requirements of the subdivi-  
sion cannot be met at the time of completion of  
installation, the owner shall have a period of thirty  
(30) days to comply with the above requirements,  
7. Vent outlet for models 80-285 must be no lower  
than the center of the air inlet, and must be at least  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 16  
U.S. Installations (see note 1)  
Canadian Installations (see note 2)  
A= Clearance above grade, veranda, porch,  
12 inches (30 cm)  
See note 6  
12 inches (30 cm)  
See note 6  
deck, or balcony  
B= Clearance to window or door that may be  
Direct vent only: 12 inches (30cm);  
Other than Direct vent: 4 ft (1.2m) below or to  
side of opening; 1 ft (30cm) above opening  
36 inches (91 cm)  
opened  
C= Clearance to permanently closed window  
See note 4  
See note 5  
See note 5  
D= Vertical clearance to ventilated soffit located  
above the terminal within a horizontal  
distance of 2 feet (61cm) from the center  
line of the terminal  
See note 4  
E= Clearance to unventilated soffit  
F= Clearance to outside corner  
G= Clearance to inside corner  
See note 4  
See note 5  
See note 4  
See note 5  
3 feet minimum  
3 feet (91cm) minimum  
H= Clearance to each side of center line  
3 feet (91 cm) within a height 15 feet  
above the meter/regulator assembly  
extended above meter/regulator assembly See note 4  
I= Clearance to service regulator vent outlet  
J= Clearance to nonmechanical air supply  
See note 4  
3 feet (91 cm)  
Direct vent only: 12" (30cm) 80-285; 36" (91cm)  
inlet to building or the combustion air inlet 399-850. Other than Direct vent: 4 ft (1.2m) below 36 inches (91 cm)  
to any other appliance  
or to side of opening; 1 ft (30cm) above opening  
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)  
6 feet (1.83 m)  
horizontally  
L= Clearance above paved sidewalk or paved Vent termination not allowed in this location  
Vent termination not allowed in this  
location for category IV appliances.  
driveway located on public property  
for category IV appliances.  
M= Clearance under veranda, porch, deck,  
See note 4  
12 inches (30 cm) (see note 3)  
or balcony  
Notes:  
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.  
2. In accordance with the current CAN/CGA-B149 Installation Codes.  
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.  
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the  
gas supplier.  
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas  
supplier.  
6. IMPORTANT: terminal must be placed such that it remains a minimum 12" above expected snow line. Local codes may have more  
specific requirements, and must be consulted.  
*When vent terminal is less than 10 feet (3m) horizontally  
from a forced air inlet, the terminal must be at least 3 feet  
(0.9m) above the air inlet.  
Figure 12. Combustion Air and Vent Through Side Wall.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 17  
one-half (1/2) inch in size: "GAS VENT DI-  
RECTLY BELOW, KEEP CLEAR OF ALL  
OBSTRUCTIONS".  
4. Inspection  
The state or local gas inspector of the side-wall  
horizontally vented gas fueled appliance shall not  
approve the installation unless, upon inspection, the  
inspector observes carbon monoxide detectors and  
signage installed in accordance with the provisions  
of 248 CMR 5.08(2)(a) 1-4.  
3.4 Common Vent Test  
NOTE: This section does not describe a method for  
common venting Brute Elite units. It describes what  
must be done when a unit is removed from a common  
vent system. Brute Elite units require special vent  
systems and fans for common vent. Contact the factory  
if you have questions about common venting Brute Elite  
units.  
When an existing boiler is removed from a  
common venting system, the common venting system is  
likely to be too large for proper venting of the  
appliances remaining connected to it.  
At the time of removal of an existing boiler, the  
following steps shall be followed with each appliance  
remaining connected to the common venting system  
placed in operation, while the other appliances  
remaining connected to the common venting system are  
not in operation.  
Figure 13. Multiple Side-Wall Terminals, Air and Vent.  
provided, however, that during said thirty (30) day  
period, a battery operated carbon monoxide detector  
with an alarm be installed.  
2. Approved Carbon Monoxide Detectors  
Each carbon monoxide detector shall comply with  
NFPA 720 and be ANSI/UL 2034 listed and IAS  
certified.  
3. Signage  
A metal or plastic identification plate shall be  
permanently mounted to the exterior of the building  
at a minimum height of eight (8) feet above grade  
directly in line with the exhaust vent terminal for  
horizontally vented gas fueled heating appliance or  
equipment. The sign shall read, in print no less than  
1. Seal any unused openings in the common venting  
system.  
2. Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion and other  
deficiencies which could cause an unsafe condition.  
Figure 14. Minimum Venting Distance.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 18  
3. Insofar as it is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system. Turn  
on any exhaust fans, such as range hoods and  
bathroom exhausts, so they will operate at  
SECTION 4.  
Gas Supply and Piping  
4.1 Gas Supply and Piping  
Gas piping should be supported by suitable  
hangers or floor stands, not the appliance.  
Review the following instructions before  
proceeding with the installation.  
maximum speed. Do not operate a summer exhaust  
fan. Close fireplace dampers.  
1. Verify that the appliance is fitted for the proper type of  
gas by checking the rating plate. Brute Elite will  
function properly without the use of high altitude  
modification at elevations up to 10,000 feet (3050 m).  
2. The maximum inlet gas pressure must not exceed  
13" W.C. (3.2kPa). The minimum inlet gas  
pressure is 4" W.C. (1.0kPa).  
3. Refer to Tables 6A, 6B, 6C and 6D to size piping.  
4. Run gas supply line in accordance with all  
applicable codes.  
5. Locate and install manual shutoff valves in  
accordance with state and local requirements.  
6. A sediment trap must be provided upstream of the  
gas controls.  
7. All threaded joints should be coated with piping  
compound resistant to action of liquefied  
petroleum gas.  
4. Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat  
so the appliance will operate continuously.  
5. Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use the  
flame of a match or candle, or smoke from a  
cigarette, cigar or pipe.  
6. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers  
and any other gas burning appliance to their  
previous conditions of use.  
7. Any improper operation of the common venting  
system should be corrected so that the installation  
conforms to the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and/or CSA B149.1, Installation  
Codes. When resizing any portion of the common  
venting system, the common venting system should  
be resized to approach the minimum size as deter-  
mined using the appropriate tables and guidelines in  
the National Fuel Gas Code, ANSI Z223.1 NFPA  
54 and/or CSA B149.1, Installation Codes.  
8. The appliance and its individual shutoff valve  
must be disconnected from the gas supply piping  
during any pressure testing of that system at test  
pressures in excess of 1/2 PSIG (3.45kPa).  
9. The unit must be isolated from the gas supply  
system by closing its individual manual shutoff  
valve during any pressure testing of the gas supply  
piping system at test pressures equal to or less than  
1/2 PSIG (3.45kPa).  
10. The appliance and its gas connection must be leak  
tested before placing it in operation.  
11. Purge all air from gas lines.  
WARNING:  
Open flame can cause gas to ignite and result in  
property damage, severe injury, or loss of life.  
NOTE: The Brute Elite appliance and all other gas  
appliances sharing the gas supply line must be firing at  
maximum capacity to properly measure the inlet supply  
pressure. The pressure can be measured at the supply  
pressure port on the gas valve. Low gas pressure could  
be an indication of an undersized gas meter, undersized  
gas supply lines and/or an obstructed gas supply line.  
Some Brute Elite units are equipped with low and high  
gas pressure switches that are integrally vent limited.  
These types of devices do not require venting to  
atmosphere.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 19  
BRUTE ELITE  
NATURAL GAS  
REQUIRED  
SECTION 5.  
Pump Requirements  
TO SIZE PIPING:  
CU FT  
/ HR.  
SIZE  
Measure linear distance from meter outlet to last  
boiler. Add total input of all boilers and divide by  
1000 to obtain cu ft / hr required. Add total  
equivalent length of fittings used according to  
Table 6B. Align total length (pipe and fittings) on  
left side column of Table 6C with highest cubic  
feet of gas required.  
80  
80  
5.1 Brute Elite Boiler Flow and Head  
105  
150  
105  
150  
Requirements (see Table 7)  
199/210 199/210  
TEMPERATURE RISE IN °F  
285  
399  
500  
600  
750  
285  
399  
500  
600  
750  
20°F  
25°F  
30°F  
35°F  
40°F  
FLOW H/L  
FLOW H/L FLOW H/L FLOW H/L FLOW H/L  
GPM FT GPM FT GPM FT GPM FT  
Notes:  
SIZE GPM FT  
Consult and confirm with Applicable Fuel Gas  
Code before beginning work. Verify gas inlet  
pressure is between 4 and 13 in W.C. before  
starting boiler.  
80  
105 10 23.1  
150 14.3 28.5 11.4 19  
7.6 14.9 6.1 10.1 5.1 7.1 4.3 5.8 3.8 4.6  
17 6.7 12.4 5.7 9.6 7.6  
9.5 13.6 8.1 11.2 7.1 8.8  
16 16.7 13.4 11.6 11.3 9.9 6.9  
8
5
850  
850  
210 20 24.1  
285 27 25.5  
399 39 28  
500 48 24  
600 58 44  
750 72 37  
850 81 33  
9
Table 6A.  
22 17.5 18 14  
15 10.5 13  
8
9
8
31 20  
38 16  
46 31  
58 23  
65 22  
25 14.5 22 11 19  
EQUIVALENT LENGTHS OF STRAIGHT PIPE FOR TYPICAL SCH 40 FITTINGS  
32 12  
38 22  
48 17  
54 15  
27  
9
24  
NOMINAL PIPE SIZE  
33 18  
41 13  
46 10  
29 15  
36 10  
FITTING 1/2"  
90° ELBOW 3.6  
3/4"  
1"  
1-1/4" 1-1/2"  
2"  
LINEAR FEET  
41  
8
4.4  
5.3  
5.2  
6.6  
6.6  
8.7  
7.4  
9.9  
8.5  
12  
TEE  
4.2  
TEMPERATURE RISE IN °C  
Table 6B.  
11°C  
14°C  
17°C  
19°C  
22°C  
FLOW H/L  
FLOW H/L FLOW H/L FLOW H/L FLOW H/L  
SIZE lpm  
m
lpm lpm lpm lpm  
m
m
m
m
SCH 40 METAL PIPE CAPACITY FOR 0.60 SPECIFIC GRAVITY NATURAL GAS  
80  
29 4.5  
23 3.1  
30 5.2  
43 5.8  
61 5.1  
83 5.3  
117 6.1  
19 2.2 16 1.8 14 1.4  
25 3.8 22 2.9 19 2.3  
36 4.1 31 3.4 27 2.7  
51 3.5 43 2.7 37 2.1  
68 4.3 57 3.2 49 2.4  
95 4.4 83 3.4 72 2.7  
@
NOMINAL PIPE SIZE 0.30" W.C. PRESSURE DROP  
105 38 7.0  
150 54 8.7  
210 76 7.3  
285 102 7.8  
399 148 8.5  
500 182 7.3  
LENGTH 1/2"  
FT  
3/4"  
1"  
1-1/4" 1-1/2"  
2"  
CUBIC FEET OF GAS PER HOUR  
20  
40  
92  
190  
130  
105  
90  
350  
245  
195  
170  
150  
730  
500  
400  
350  
305  
1100  
760  
610  
530  
460  
2100  
1450  
1150  
990  
60  
80  
100  
144 4.9 121 3.7 102 2.7 91 2.4  
600 220 13.4 174 9.4 144 6.7 125 5.5 110 4.6  
750 273 11.3 220 7.0 182 5.2 155 4.0 136 3.0  
850 307 10.1 246 6.7 204 4.6 174 3.0 155 2.4  
870  
Table 6C.  
Table 7. Water Flow Requirements.  
SCHED 40 METAL PIPE CAPACITY FOR 1.50 SPECIFIC GRAVITY  
UNDILUTED PROPANE  
@
NOMINAL PIPE SIZE 11" W.C. INLET AND 0.5" W.C. PRESSURE DROP  
5.2 Brute Elite Water Heater Flow and Head  
SIZE  
LENGTH  
20  
40  
60  
80  
100  
1/2"  
3/4"  
1"  
1-1/4" 1-1/2"  
2"  
Requirements (see Table 8)  
MAXIMUM CAPACITY IN THOUSANDS OF BTU PER HOUR  
200  
137  
110  
94  
418  
287  
231  
197  
175  
787  
541  
434  
372  
330  
1616  
1111  
892  
2422  
1664  
1337  
1144  
1014  
4664  
3205  
2574  
2203  
1952  
NORMAL WATER*  
Flow  
gpm  
H/L Temp  
feet Rise °F  
Flow  
lpm  
H/L  
m
Temp  
Size  
Rise °C  
150  
199  
285  
399  
19  
25  
36  
50  
63  
60  
68  
68  
57  
28  
33  
35  
28  
24  
35  
26  
15  
15  
15  
15  
15  
19  
21  
24  
72  
95  
98  
189  
239  
227  
257  
257  
17.4  
8.5  
10.1  
10.7  
8.5  
7.3  
10.7  
7.9  
8
8
8
8
8
11  
12  
13  
763  
84  
677  
NOTES: 1. Follow all local and national LP gas codes for line sizing and  
equipment requirements. 2. Verify that inlet gas pressure remains between  
4 and 13 inches of water column before and during operation.  
Source: ANSI Z223.1-80 National Fuel Gas Code.  
500  
600**  
750**  
850**  
Table 6D.  
*Maximum water hardness of 10 grains per gallon allowed.  
**See section 6B.6 on page 30 for pump information.  
Table 8. Brute Elite Water Heater Flow Data.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 20  
Brute Elite's efficiency is higher with lower  
return water temperatures. Therefore, to get the most  
of low return temperature with multiple boilers, pipe as  
shown in Figures 17-19.  
SECTION 6A.  
Water Connections - BNTH Boiler  
Section 6 is divided into two parts. The first is  
for BNTH models and is Section 6A. The  
second is for BNTV models and is Section 6B.  
Refer to the proper section for instructions in  
installing and piping your product. Refer to  
Table 9 for pipe sizes required.  
Brute Elite BNTH models can be ordered with or  
without a pump included.  
Brute Elite with a pump MUST be piped in a  
primary-secondary fashion (using either piping or a  
hydraulic separator) such that the pump that is mounted  
on the boiler ONLY serves the boiler.  
When the pump is supplied by Bradford White, the  
Brute Elite boiler must be located within 15 feet (4.6m)  
of the supply and return header (or the hydraulic  
separator). Pumps supplied by Bradford White are sized  
for a maximum of 30 feet (9.1m) of piping and the  
headloss of the boiler only (see Table 7).  
If longer pipe lengths are required, the pump  
should be sized for the boiler per Table 7 and for the  
piping it will serve, and should be supplied to job  
separately. Even with pumps supplied by others,  
Bradford White strongly recommends primary-  
secondary piping.  
6A.1 BNTH System Piping:  
Hot Supply Connections  
NOTE: This appliance must be installed in a closed  
pressure system with a minimum of 12 psi (82.7kPa)  
static pressure at the boiler.  
Hot water piping should be supported by suitable  
hangers or floor stands. Do not support piping with this  
appliance. Due to expansion and contraction of copper  
pipe, consideration should be given to the type of  
hangers used. Rigid hangers may transmit noise through  
the system resulting from the piping sliding in the  
hangers. It is recommended that padding be used when  
rigid hangers are installed. Maintain 1" (2.5cm)  
clearance to combustibles for hot water pipes.  
Pipe the discharge of the relief valve (full size) to  
a drain or in a manner to prevent injury in the event of  
pressure relief. Install an air purger, an air vent, a  
diaphragm-type expansion tank, and a hydronic flow  
check in the system supply loop. Minimum fill pressure  
must be 12psig (82.7kPa). Install shutoff valves where  
required by code.  
6A.2 BNTH Cold Water Make-Up  
1. Connect the cold water supply to the inlet  
connection of an automatic fill valve.  
2. Install a suitable back flow preventer between the  
automatic fill valve and the cold water supply.  
3. Install shut off valves where required.  
The boiler piping system of a hot water heating  
boiler connected to heating coils located in air handling  
appliances where they may be exposed to refrigerated  
air circulation must be equipped with flow control  
valves or other automatic means to prevent gravity  
circulation of the boiler water during the cooling cycle.  
A boiler installed above radiation level, or as  
required by the authority having jurisdiction, must be  
provided with a low water cutoff device either as a part  
of the boiler or at the time of boiler installation.  
Suggested piping diagrams are shown in Figures  
15 through 21. These diagrams are meant only as a  
guide. Components required by local codes must be  
properly installed.  
BNTH  
SIZE  
PIPE SIZE,  
INCHES  
BNTV  
SIZE  
PIPE SIZE,  
INCHES  
80  
1
1
1
1¼  
1¼  
1¼  
1½  
1½  
2
n/a  
n/a  
1¼  
1¼  
2
2
2
2
2
105  
150  
210  
285  
399  
500  
600  
750  
850  
150  
199  
285  
399  
500  
600  
750  
850  
2
2
Table 9. Water Connection Pipe Sizes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 21  
6A.3 Freeze Protection  
6A.4 BNTH Suggested Piping Schematics  
Figures 15 through 21 show suggested piping  
configurations for BNTH boilers. These diagrams are  
only meant as a guide. All components or piping  
required by local code must be installed.  
WARNING  
Glycol must not be used in domestic hot water  
applications. Refer to Section 6B.4 for instructions on  
BNTV, domestic hot water freeze protection.  
6A.5 Recognized Chemicals  
Brute Elite units are certified for indoor use only,  
and are not design-certified for placement outdoors.  
Proper precautions for freeze protection are  
recommended for boiler installations in areas where the  
danger of freezing exists.  
The following manufacturers offer glycols,  
inhibitors, and anti foamants that are suitable for use in  
the Brute Elite. Please refer to the manufacturers  
instructions for proper selection and application.  
Power outage, interruption of gas supply, failure of  
system components, activation of safety devices, etc.,  
may prevent a boiler from firing. Any time a boiler is  
subjected to freezing conditions, and the boiler is not  
able to fire, and/or the water is not able to circulate,  
there is a risk of freezing in the boiler or in the pipes  
in the system. When water freezes, it expands which  
may result in bursting of pipes, or damage to the boiler,  
which could result in leaking or flooding conditions.  
Do not use automotive antifreeze. To help prevent  
freezing, Bradford White recommends the use of  
inhibited glycol concentrations between 20% and 35%  
glycol. Typically, this concentration will serve as burst  
protection for temperatures down to approximately -5°F  
(-20°C). If temperatures are expected to be lower than -  
5°F (-20°C), glycol concentrations up to 50% can be  
used. When concentrations greater than 35% are used,  
water flow rates must be increased to maintain a 20°F  
to 25°F temperature rise through the boiler. NOTE:  
Bradford White supplied pumps are not all capable  
of maintaining the reduced temperature rise  
1. Sentinel Performance Solutions Group  
2. Hercules Chemical Company  
3. Dow Chemical Company  
required with glycol concentrations greater than  
35%. If glycol concentrations required are greater  
than 35% a field supplied pump should be used.  
IMPORTANT NOTES: Different glycol products may  
provide varying degrees of protection. Glycol products  
must be maintained properly in a heating system, or they  
may become ineffective. Consult the glycol specifications,  
or the glycol manufacturer, for information about specific  
products, maintenance of solutions, and set up according  
to your particular conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 22  
Figure 15. Hydronic Piping — Single Boiler (zoning with circulators).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 23  
Figure 16. Hydronic Piping — Single Boiler, Low Temp Radiant Space Heating using Low Loss Header and Zone Valves.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 24  
Figure 17. Hydronic Piping — Multiple Boilers (zoning with circulators).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 25  
Figure 18. Hydronic Piping — Multiple Boilers with Indirect DWH Tank Piped from System Loop.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 26  
Figure 19. Hydronic Piping — Multiple Boilers, Reverse Return, Multi-Temp Zones (zoning with circulators).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 27  
Figure 20. Hydronic Piping — Heating zones with indirect DWH tank piped with zone pumps (indirect directly off boiler).  
Boiler pump must shut down during DHW.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 28  
Figure 21. Hydronic Piping, multiple boilers with indirect DWH off one boiler. Boiler pump must shut-down during DHW.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 29  
6B.2 Piping Requirements  
SECTION 6B.  
Water piping should be supported by suitable  
hangers and floor stands. Do not support piping with the  
appliance. Due to expansion and contraction of copper  
pipe, consideration should be given to the type of  
hangers and supports used. Rigid hangers may transmit  
noise through the system resulting from piping sliding  
in the hangers. It is recommended that padding be used  
when rigid hangers are installed. Maintain 1" (2.5cm)  
clearance to combustibles for hot water pipes.  
Water Connections - BNTV Water Heater  
Section 6 is divided into two parts. The first is  
for BNTH models and is Section 6A. The  
second is for BNTV models and is Section 6B.  
Refer to the proper section for instructions in  
installing and piping your product. Refer to  
Table 9 for pipe sizes required.  
Pipe the discharge of the relief valve (full size) to  
the drain or in a manner to prevent injury in the event of  
pressure relief. Install a diaphragm-type expansion tank,  
flow check, and shutoff valves where needed or as  
required by code.  
Brute Elite 80-500 can be ordered with pumps.  
Whether the factory pumps or other pumps are installed  
the piping should be installed such that the pump  
supplies flow to the heater it is attached to only. The  
factory pumps are sized for 30 feet and 6 elbows of total  
pipe length, so the heater should be placed within 15  
feet of the tank. If longer runs are required, properly-  
sized field-supplied pumps should be used.  
6B.1 BNTV Water Quality  
BNTV water heaters must be installed in water  
conditions of 10gpg hardness or less with a pH range of  
8.2 to 9.5. Operating the BNTV in water with higher  
hardness levels will cause heat exchanger fouling,  
erosion, or corrosion leading to premature component  
failure, reduced efficiency, heat exchanger failure or  
system failure. Failure of this type will not be  
warranted. If the water in use exceeds the conditions  
recommended water softeners or other devices should  
be installed to improve water quality.  
WARNING: THIS DRAWING SHOWS  
SUGGESTED PIPING CONFIGURATION AND  
VALVING. CHECK WITH LOCAL CODES AND  
ORDINANCES FOR ADDITIONAL REQUIREMENTS.  
NOTES:  
1. Optional CWMU & Recirc. line location.  
2. Locate BNTV DHW sensor or remote aquastat well  
in lower 1/3 of tank.  
3. Back flow preventer may be required - check local codes.  
4. Thermal expansion tank may be required - check local codes.  
5. Factory mounted pumps are sized for a max pipe length of  
30' total, 6-90° elbows, full pipe size.  
6. Caution: Pump sizing must be based opon water hardness at job site.  
Figure 23. DHW Piping, One Heater, One Vertical Tank.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 30  
6B.3 Cold Water Make-Up  
6B.5 BNTV Suggested Piping Schematics  
Figures 23-26 show suggested piping  
configurations for BNTV boilers. These diagrams are  
only meant as a guide. All components or piping  
required by local code must be installed.  
The cold water make-up may be connected to the  
tank or to the inlet of the boiler as shown in Figures 23-  
26. Install back flow preventers and shut offs where  
needed or required by code.  
6B.4 Freeze Protection  
6B.6 BNTV Suggested Pumps  
Brute Elite heaters are not certified for outdoor  
installation, so the chance of freezing is minimized. In  
an event such as power outage, component failure or  
other issue when freezing is likely, the heater and  
system must be drained to avoid the risk of damage due  
to freezing. Glycol must NOT be used in volume water  
heating applications.  
Possible pumps for BNTV sizes 600-850 are  
Grundfos model TP 40-160/2B, or for size 600 (only) is  
Armstrong model E22B. See Table 8 for water flow and  
head requirements.  
NOTES:  
1. Optional CWMU & Recirc. line location.  
2. Locate BNTV DHW sensor or remote aquastat well  
in lower 1/3 of tank.  
3. Back flow preventer may be required - check local codes.  
4. Thermal expansion tank may be required - check local codes.  
5. Factory mounted pumps are sized for a max pipe length of  
30' total, 6-90° elbows, full pipe size.  
6. Caution: Pump sizing must be based opon water  
hardness at job site.  
WARNING: THIS DRAWING SHOWS  
SUGGESTED PIPING CONFIGURATION AND  
VALVING. CHECK WITH LOCAL CODES AND  
ORDINANCES FOR ADDITIONAL REQUIREMENTS.  
Figure 24. DHW Piping, One Heater, Two Vertical Tanks.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 31  
NOTES:  
1. Optional CWMU & Recirc. line location.  
2. Locate BNTV DHW sensor or remote aquastat  
well in lower 1/3 of tank.  
3. Back flow preventer may be required - check  
local codes.  
4. Thermal expansion tank may be required -  
check local codes.  
5. Factory mounted pumps are sized for a max  
pipe length of 30' total, 6-90° elbows, full pipe size.  
6. Caution: Pump sizing must be based opon  
water hardness at job site.  
WARNING: THIS DRAWING SHOWS  
SUGGESTED PIPING CONFIGURATION AND  
VALVING. CHECK WITH LOCAL CODES AND  
ORDINANCES FOR ADDITIONAL REQUIREMENTS.  
Figure 25. DHW Piping, Two Heaters, One Vertical Tank.  
NOTES:  
1. Optional CWMU & Recirc.  
line location.  
WARNING: THIS DRAWING SHOWS  
SUGGESTED PIPING CONFIGURATION AND  
VALVING. CHECK WITH LOCAL CODES AND  
ORDINANCES FOR ADDITIONAL REQUIREMENTS.  
2. Locate BNTV DHW sensor  
or remote aquastat well  
in lower 1/3 of tank.  
3. Back flow preventer may be  
required - check local codes.  
4. Thermal expansion tank may be  
required - check local codes.  
5. Factory mounted pumps are sized  
for a max pipe length of 30' total,  
6-90° elbows, full pipe size.  
6. Caution: Pump sizing must  
be based opon water  
hardness at job site.  
Figure 26. DHW Piping, Two Heaters, Two Vertical Tanks.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 32  
Important Note: DO NOT MAKE/BREAK BRUTE  
ELITE LINE VOLTAGE TO SIGNAL CALL FOR HEAT.  
A “call for heat / end call for heat” MUST be connected  
to the field interlock terminals. Some Brute Elite  
components are designed to have constant voltage  
during normal operation. If the Brute Elite's supply  
voltage is toggled as a call for heat signal, premature  
failure of these components may result.  
SECTION 7.  
Electrical Connections  
WARNING  
The appliance must be electrically grounded in  
accordance with the requirements of the authority  
having jurisdiction or, in the absence of such  
requirements, with the latest edition of the National  
Electrical Code, ANSI/NFPA 70, in the U.S. and with  
latest edition of CSA C22.1 Canadian Electrical Code,  
Part 1, in Canada. Do not rely on the gas or water piping  
to ground the metal parts of the boiler. Plastic pipe or  
dielectric unions may isolate the boiler electrically.  
Service and maintenance personnel, who work on or  
around the boiler, may be standing on wet floors and  
could be electrocuted by an ungrounded boiler.  
Electrocution can result in severe injury or death.  
Brute Elite does not recognize 4mA as a signal to shut  
off. If the call for heat is not connected between the field  
interlock terminals, Brute Elite will remain in low fire  
when it sees 4mA as a modulating signal.  
Caution  
Brute Elite supply voltage must not be disengaged,  
except for service or isolation, or unless otherwise  
instructed by procedures outlined in this manual. To  
signal a call for heat, use the 24V field-interlock, as  
shown in the wiring diagram(s).  
Single pole switches, including those of safety  
controls and protective devices must not be wired in a  
grounded line.  
7.1 Main Power  
Connect a 15A fused, 120-volt supply to the main  
power switch (hot leg is connected directly to switch).  
Neutral leg is connected directly to the white wire.  
Ground wire can be connected to the grounding lug in  
the control panel (see Table 11).  
All electrical connections are made on the terminal  
blocks that are located inside the control panel.  
NOTE: All internal electrical components have been  
prewired. No attempt should be made to connect  
electrical wires to any other location except the terminal  
blocks.  
Wiring connections are shown in Figures 29 and 30.  
Figure 27. Control Panel Layout.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 33  
7.4 Hydronic Call for Heat  
BOILER  
PUMP CONNECTIONS  
RATINGS  
Connect the call for heat to terminal block 7  
(TB7), connections labeled "T-T or interlock" in the  
control panel.  
(Boiler, System Pump and  
DHW Pump Connections)  
SIZES  
VOLTS PHASE AMPS  
80–850  
No Pump  
115V – Maximum 1HP  
or 7.4A max  
120 Single 2*  
7.5 Outdoor Air Temperature Sensor  
Connect the outdoor air temperature sensor to  
terminal block 7 (TB7), connections labeled Outdoor temp  
sensor. The outdoor air temperature sensor is used for  
warm weather shutdown and outdoor reset.  
Less  
120 Single than  
6*  
80-500  
With Pump  
115V – Maximum 1HP  
or 7.4A max  
*Minimum 15A circuit required  
Table 10. BNTH Electrical Data.  
7.6 Domestic Hot Water Connection  
Connect a DHW sensor or aquastat to terminal  
block 6 (TB6), connections labeled DHW stat. The  
aquastat or sensor will be automatically detected and  
initiate the DHW call as needed.  
WATER HEATER  
PHASE  
SIZES  
VOLTS  
AMPS  
150-500  
No pump  
120  
Single  
Single  
Single  
2*  
7.7 System Sensor (lead lag/cascading  
150-199  
With pump  
120  
120  
7*  
8*  
operation only)  
Connect the system sensor to terminal block 6  
(TB6), connections labeled system sensor. Can be used  
in a well for DHW tank applications with lead/lag.  
285-500  
With pump  
600-850  
No pump  
See Pump Rating Plate FLA  
(must be less than 7.4 FLA; 1HP or less)  
*Minimum 15A circuit required  
7.8 External Control Connections  
Connect 4-20mA signals from external controls or  
building automation systems to terminal block 7 (TB7)  
in the control panel. The connections are labeled  
"Remote Anlaog Input". When making the connections  
follow the polarity designations shown on the label.  
Table 11. BNTV Electrical Data.  
7.2 Pump Connections  
Brute Elite energizes the pump contacts upon a  
call for heat. Once the call for heat is satisfied the pump  
will remain on for the defined pump overrun time.  
7.9 Optional Field Connections  
Terminal block 8 (TB8) in the control panel can be  
used for connecting optional components, such as, low  
water cutoffs, flow switches, additional high limits and  
other field supplied devices that must be interlocked  
with the boiler. All safeties or end switches must be  
wired in series by removing the supplied jumpers.  
NOTE: System and DHW contacts are dry contacts.  
Appropriate voltage must be supplied to the System  
and DHW pumps for proper operation. Boiler pump  
contact (max 7.4 FLA) is fed by 120V (violet wire)  
internally from main power feed.  
System pump connections are located on terminal  
block 5 (TB5) in the control panel (see Figure 27). The  
system pump contacts are rated for 120Vac, 7.4 amps.  
To use the contacts, power must be supplied on one  
terminal with the other terminal wired to the pump or a  
relay controlling the pump.  
DHW pump connections are located on terminal  
block 5 (TB5) in the control panel and are rated for  
120Vac, 7.4 amps. To use the contacts, power must be  
supplied on one terminal, and the other terminal wired  
to the pump or a relay controlling the pump.  
7.10 Lead Lag/ Cascading Wiring  
Connections  
Connect each boiler in the cascade system  
together by daisy chaining each control from Modbus  
port 1 (MB1) of the first boiler to the second and so on.  
This can be done using 22awg or thicker shielded  
twisted pair wire with drain. Two twisted pairs or three  
conductors are needed.  
a.  
To daisy-chain the boilers connect a wire from Modbus  
port 1 (MB1) terminal A of the first boiler to Modbus  
port 1 (MB1) terminal A of the second boiler.  
7.3 24Vac Transformer with Integral Circuit  
b. If there are more boilers in the system connect a  
wire from Modbus port 1 terminal A of boiler 2 to  
Modbus port 1 terminal A of boiler 3.  
c. Repeat these steps until all Modbus port1 terminal  
A connections are wired.  
Breaker  
24Vac is supplied by a transformer mounted to the  
backside or underneath the control panel, depending  
upon the appliance. All 24Vac power is supplied  
through a circuit breaker that is part of the transformer.  
The transformer is then connected to terminal blocks 3  
and 4 (TB3 and TB4).  
d. Repeat the above steps for Modbus port 1 terminal  
B and C connections to complete the wiring.  
e. Connect the drain wire from the twisted pair wire  
to ground on one end of the wire only.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 34  
Figure 28. Lead-Lag / Cascading Wiring Connections.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 35  
7.11 Wiring Diagrams (see Figures 29 and 30)  
Caution  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and  
dangerous operation. Verify proper operation after  
servicing  
Figure 29. Ladder Diagram.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 36  
Figure 30. Wiring Diagram (all sizes).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 37  
Once the value is adjusted the NEXT or DONE button  
SECTION 8.  
can be pressed. The DONE button returns you to the  
Home screen. The NEXT button increments the display  
to the next item in the menu structure.  
Brute Elite Control Setup  
and Operation  
USER mode is the home screen shown on the  
control. If the display is not in USER mode wait for the  
display timeout period to be reached or press the Done  
button to return to the USER menu.  
SETUP mode is accessed by holding the up and  
down arrow keys simultaneously for 3 seconds.  
DIAGNOSTIC mode is accessed by holding the  
NEXT button for 3 seconds.  
The Brute Elite control is an integrated electronic  
control that replaces many of the individual components  
found on older appliances. The control acts as the  
ignition control, pump control, high limit and cascading/  
lead lag control and is setup using the display on the  
appliance.  
8.2 Ignition Control- Sequence of Events  
1. Call for heat  
2. Safety chain check  
3. Fan starts and waits to achieve prepurge RPM  
MENU ITEM  
DEFINITION  
F or C  
Selects temperature units  
LBTHODLOD Outdoor reset enable/disable -  
enables menu items  
LBT  
Low boiler setpoint during outdoor reset  
see Figure 29  
HOD  
LOD  
High outdoor temperature setpoint  
see Figure 29  
Low outdoor temperature setpoint  
see Figure 29  
Figure 31. Control Buttons on User Interface.  
8.1 Display Navigation  
RMT Add  
LL  
HS  
bL  
Sd  
Used for Lead/Lag (follow menus)  
The display is divided into three menu structures,  
USER, SETUP and DIAGNOSTIC. The menu structure  
and variables in each are shown in Tables 12-14. Once  
in a particular menu structure navigation consists of  
pressing the next button to scroll from item to item and  
then pressing the up and down arrows to change values.  
Lead/Lag enable/disable - enables menu items  
Hysteresis - temp range between on/off cycles  
Base Load % - input rate before next boiler fires  
Warm weather shut-down temperature  
Anti short cycle - minutes of delay between  
startup  
ASC  
bAC  
PAS  
Future use - Press DONE to exit menu.  
Future use - Press DONE to exit menu.  
MENU ITEM  
FUNCTION  
RANGE  
DEFAULT  
Outlet water Displays the current outlet 55-190°F 120°F  
temperature water temperature & allows  
the setpoint to be adjusted  
NOTE: When enabling/disabling functions, select "Done" and wait 30  
seconds before scrolling.  
Inlet water  
Displays the current inlet  
Table 13. Setup Mode Parameters.  
temperature water temperature  
MENU ITEM  
DESCRIPTION  
Delta T  
Displays the current  
temperature rise across  
the heat exchanger  
mA  
Display the flame sense signal  
Displays the current alert code  
Displays the current lockout code  
Displays outlet temperature limit  
Displays Domestic Hot Water limit setting  
Displays Stack limit setting  
Alert codes  
Lockout code  
Outlet Limit  
DHW limit  
DHW water Displays the current DHW 60-182°F 120°F  
temperature temperature & allows the  
setpoint to be adjusted  
Stack  
Displays the current stack  
temperature temperature  
Stack Limit  
Outdoor  
temperature air temperature  
LL  
Displays the current outdoor  
Min. firing rate Displays the minimum firing rate allowed  
Min. forced  
firing rate  
Max forced  
firing rate  
Rate indicator Displays a indicator of the firing rate based  
off of the fan RPM. Actual firing rate may  
vary depending upon setup.  
Allows the user to force the boiler to fire at  
the minimum firing rate  
Allows the user to force the boiler to fire at  
the maximum firing rate  
Displays the current system 60-190°F 120°F  
temperature and allows the  
setpoint to be adjusted  
Firing Rate Displays an indicator of the  
current firing rate based  
upon fan RPM. The actual  
firing rate may vary.  
Table 14. Diagnostic Mode Menu Structure.  
Table 12. User Mode Menu Structure.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 38  
4. Prepurge timer is started once the prepurge RPM is  
achieved.  
8.5 Anti-Short Cycle (ASC)  
The anti short cycle period is started whenever the  
gas valve turns off. This period is to help prevent short  
cycling. Depending upon the time selected the control  
will wait up to 10 minutes before attempting to start the  
trial for ignition sequence. The ASC time can be  
adjusted by entering setup mode.  
5. Pre ignition time of 2 seconds to check the flame  
sensor operation and status. During this period an  
intermittent spark can be seen.  
6. Trial for ignition period, 4 seconds. The direct  
spark ignition switches to constant spark for three  
seconds, during which time the gas valve is open.  
For the last second of the ignition period direct  
spark is de-energized and the flame sensor checks  
for established flame. If flame is sensed the control  
enters "Run" to satisfy the demand. If flame is not  
established the control enters a retrystarting from  
step 2. If flame has not been established in the  
appropriate number of retries the control will  
lockout with a 109 error code.  
7. Call for heat complete  
8. Gas valve off  
9. Fan and pump over run times active to purge the  
system  
This sequence is the basic operating sequence of  
the appliance whether there is a DHW, or hydronic call  
for heat.  
8.5 High Limit  
The control uses a dual thermistor sensor to  
monitor the Brute Elite's maximum temperature. The  
high limit sensor is installed in the outlet water. A dual  
thermistor sensor is used, so that the two temperatures  
can be monitored and compared to confirm accuracy.  
The control will automatically reduce the firing of the  
Brute Elite to prevent the high limit from tripping. The  
high limit setpoint is not adjustable.  
8.7 Outlet Water Temperature  
The outlet water temperature is a dual thermistor  
sensor and is limit rated. The control compares each of  
the temperature readings to determine accuracy. The  
outlet sensor is used as the primary control point for  
high limit, temperature operation, and modulation. The  
operating setpoint can be adjusted through the USER  
menu structure.  
8.3 Modulation Control  
The control uses a PID algorithm to adjust the  
firing rate of the boiler as the control point is  
8.8 Inlet Water Temperature  
The inlet water temperature uses a single  
thermistor sensor and is used to calculate the delta T of  
the system.  
approached. The goal of the control is to operate at a  
minimum firing rate to match the load on the appliance.  
This is done by using a setpoint, and on / off  
differentials. The control modulates to achieve the  
setpoint temperature, which could be several degrees  
away from the actual off point. The off point is  
calculated by adding the setpoint + off differential. The  
setpoint and differentials used in operation is dependent  
upon the call for heat being applied. If there is a DHW  
call the DHW setpoint and off differentials are used. If  
there is a hydronic call the CH setpoint and off  
differential is used. When the setpoint + off differential  
is achieved the control interrupts appliance firing until  
the water temperatures reaches the setpoint - on  
differential. Both the hydronic and DHW setpoints are  
adjustable through the USER mode menu structure.  
8.9 Heat Exchanger Temperature Rise  
The heat exchanger temperature rise is calculated  
from the outlet and inlet sensor temperatures. The result  
is displayed in the USER menu structure.  
8.10 Stack Temperature  
The stack temperature is a dual thermistor sensor  
and is limit rated. The control compares each of the  
temperature readings to determine accuracy. The stack  
sensor is used as a limiting feature to avoid excessive  
temperatures in the venting.  
8.4 Pump Control  
8.11 Domestic Hot Water Temperature  
The domestic hot water temperature sensor is used  
to monitor the DHW demand. The control uses the  
DHW sensor to control the operation and modulation  
rate of the appliance when there is a DHW demand. The  
DHW setpoint can be adjusted through the USER menu  
structure.  
The control can operate three pumps. The boiler  
pump is active anytime there is a call for heat applied to  
the control. The DHW and system pumps are active  
based upon the call and priority of the heat demand  
being supplied. When there is a hydronic call supplied  
the system pump is active. If there is a DHW call  
supplied while the hydronic call is active the system  
pump turns off and the DHW turns on. This happens  
because of domestic hot water priority, which forces the  
control to attempt to satisfy the domestic water demand  
prior to the hydronic demand. When the last heat  
demand is satisfied the boiler pump enters an overrun  
time.  
8.12 Lead Lag / Cascading  
Lead Lag/Cascading allows multiple boilers to be  
connected together and controlled from one common  
sensor input. Up to 8 boilers can be connected together  
in a single system. To setup Lead/Lag or cascading  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 39  
will help reduce the chance of short cycling.  
DANGER  
8.12.5 Lead Lag Base Load Setting  
• Water temperature over 125°F (52°C) can cause  
severe burns instantly or death from scalds.  
• Children, disabled and elderly are at hightest risk of  
being scalded.  
• See instruction manual before  
setting temperature at  
The lead lag system uses a base load setting that is  
set through the "setup" menu called "bL". The base load  
setting identifies the firing rate that the operating boiler  
must achieve before the next boiler in the system is  
allowed to operate. The default setting is 50% to avoid  
short cycling and operating the boilers at higher, less  
efficient, firing rates.  
heating appliance.  
• Feel water before  
bathing or showering.  
8.13 Boiler Pump Interrupt  
• If this appliance is used to  
produce water that could  
WARNING  
scald if too hot, such  
Failure to plumb, pump and install the appliance  
correctly when using this feature may lead to reduced  
or no water flow through the heat exchanger, causing  
premature failure of the heat exchanger, personal  
injury or death. Please consult the factory with any  
questions regarding the use of this feature.  
as domestic hot water  
use, adjust the outlet  
control (limit) or use temperature limiting valves to  
obtain a maximum water temperature of 125°F (52°C).  
operation there are several settings in the "setup" menu  
structure that must be adjusted for the specific  
installation, each is covered in the following sections.  
8.12.1 Lead Lag Setpoint  
The boiler pump interrupt feature is used in some  
applications when the boiler is being used for both  
hydronic and domestic hot water heating. The interrupt  
jumper is used to turn off the boiler pump during a  
domestic hot water demand. For this to work properly  
the system must be plumbed and pumped to allow the  
domestic hot water pump to supply the flow and head  
requirements for the boiler and indirect water heater  
together. It is not necessary to use the interrupt jumper  
in all applications. Specific modes of operation that may  
require the use of this feature are shown in Section 6.  
The lead lag setpoint is set from the "user" menu  
using the "LL" variable. This is the temperature the  
boiler is attempting to maintain at the system sensor.  
This setting doesn't control the boiler outlet  
temperature, so the water temperature at the boiler outlet  
may be much hotter than the system temperature  
setpoint. Adjust the LL setpoint to the desired operating  
temperature of the system.  
8.12.2 Lead Lag Master/Slave Selection  
In the SETUP menu structure, the "LL" menu  
allows the lead lag system to be turned on and the boiler  
to be configured as a master or slave control. In each  
lead lag system there can only be one master control, so  
proper selection is important to avoid operating issues.  
To set the boiler to lead lag "master" operation the LL  
menu should be set to "LDR". To set the boiler to slave,  
"SLA" should be selected.  
NAME  
FUNCTION  
VALUE  
CH on  
Burner demand begins when the  
5°F  
differential outlet water temperature reaches  
"Outlet water temperature setpoint"  
minus "CH on differential"  
CH off  
Burner demand ends when the  
5°F  
differential outlet water temperature reaches  
"Outlet water temperature setpoint"  
plus "CH off differential"  
8.12.3 Lead Lag Address  
DHW on  
Burner demand begins when the  
2°F  
(80-285)  
differential outlet water temperature reaches  
"Outlet water temperature setpoint"  
minus "DHW on differential"  
The Lead Lag address must be set for each boiler  
connected to the lead lag system. Each boiler must have  
a unique address selected for the system to work  
properly. Typically, the lead or master boiler should be  
set to address one and the remaining boilers should be  
set to values 2–8 depending upon how many boilers are  
installed in the system.  
5°F  
(399-850)  
DHW off  
Burner demand ends when the  
10°F  
(80-285)  
differential outlet water temperature reaches  
"Outlet water temperature setpoint"  
plus "DHW off differential"  
5°F  
(399-850)  
Pump  
overrun  
Operates the pump for the overrun  
time after the burner demand  
has ended  
Locks the boiler out when the high  
limit temperature is reached  
(requires manual reset)  
Flame signals lower than the flame  
threshold interrupt burner operation  
Time for domestic hot water priority  
1 or 5  
minutes  
8.12.4 Lead Lag Hysteresis  
The lead lag system uses a hysteresis value set in  
the setup menu, called, "HS". The hysteresis and  
setpoint values control the on and off points of the  
boiler. If the lead lag setpoint is adjusted to 120°F with  
a hysteresis value of 5°F the boiler will turn off when  
the water temperature reaches 125°F and will turn back  
on when the water temperature reaches 115°F. Set the  
hysteresis values to match the boiler to the system  
operating characteristics. Setting this value correctly  
High  
limit  
200°F  
Flame  
threshold  
DHW  
priority time  
0.8Vdc  
60 min.  
Table 15. Default Control Settings.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 40  
once the fan RPM reaches a preset level. The trial for  
ignition period follows once the start-up RPM of the fan  
is reached. The trial for ignition period lasts 4 seconds  
during which, the direct spark ignition system and gas  
valve are energized. At the end of the trial for ignition  
period the flame signal is compared with the preset  
flame threshold value. If the flame signal is higher than  
the flame threshold the Brute Elite enters "run". If the  
flame signal is below the threshold the Brute Elite  
returns to pre-purge and starts the ignition process over.  
In "run" the Brute Elite monitors the flame signal, call  
for heat, safeties, and water temperatures modulating as  
needed between 100% and 20% of rate to satisfy the call  
for heat. When a DHW demand is applied during a  
hydronic call for heat the priority feature forces the  
boiler to switch to the DHW demand for the priority  
time. The DHW priority demand forces the control to  
operate to the DHW setpoint, de-energizes the system  
pump and energizes the DHW pump.  
SECTION 9.  
Modes of Operation  
The Brute Elite control allows the boiler to operate  
in many different modes of operation. The mode must  
be selected based upon the requirements of the  
installation. The following sections describe the basic  
operation of the Brute Elite in each of the different  
modes. Familiarize yourself with each mode and how  
the operation of the boiler varies, depending upon the  
installation and inputs the control is monitoring.  
9.1 Hydronic Heating Demand  
When using the Brute Elite for hydronic heating a  
call for heat must be supplied to the "T-T or Interlock"  
terminal. Once the call is supplied the control starts the  
boiler and system pumps and begins the ignition  
process. The ignition process consists of a prepurge,  
trial for ignition, and run period. The prepurge period  
starts on a call for heat once the fan RPM reaches a  
preset level. The trial for ignition period follows once  
the start-up RPM of the fan is reached. The trial for  
ignition period lasts 4 seconds during which the direct  
spark ignition system and gas valve are energized. At  
the end of the trial for ignition period the flame signal is  
compared with the preset flame threshold value. If the  
flame signal is higher than the flame threshold the Brute  
Elite enters "run". If the flame signal is below the  
threshold the Brute Elite returns to prepurge and starts  
the ignition process over. In "run" the Brute Elite  
monitors the flame signal, call for heat, safeties, and  
water temperatures and modulates as needed between  
100% and 20% of rate to satisfy the call for heat.  
9.4 Hydronic Heating Using External  
Modulation Control  
When using the Brute Elite for hydronic heating  
with external modulation control a call for heat must be  
supplied to the "T-T or Interlock" terminal. Once the  
call is supplied the control starts the boiler and system  
pumps and begins the ignition process. The ignition  
process consists of a prepurge, trial for ignition, and run  
period. The prepurge period starts on a call for heat  
once the fan RPM reaches a preset level. The trial for  
ignition period follows once the start-up RPM of the fan  
is reached. The trial for ignition period lasts 4 seconds  
during which the direct spark ignition system and gas  
valve are energized. At the end of the trial for ignition  
period the flame signal is compared with the preset  
flame threshold value. If the flame signal is higher than  
the flame threshold the Brute Elite enters "run". If the  
flame signal is below the threshold the Brute Elite  
returns to prepurge and starts the ignition process over.  
In "run" the Brute Elite monitors the flame signal, call  
for heat, safeties, and water temperatures. The boiler  
9.2 Hydronic Heating with Outdoor Reset  
Outdoor reset varies the control point setpoint  
based on the actual outdoor temperature. The reset  
function works as shown in Figure 32. When the  
outdoor air temperature reaches the "high outdoor  
temperature setpoint (HOD), the control point setting is  
adjusted to the low boiler temperature setpoint (LBT).  
When the outdoor air temperature reaches the low  
outdoor temperature setpoint (LOD), the control  
setpoint is adjusted to the CH/Outlet water setpoint  
temperature. HOD, LOD and LBT can be adjusted by  
accessing SETUP mode. CH setpoint is adjustable from  
the USER menu structure.  
9.3 Hydronic Heating with Domestic Hot  
Water (DHW) Priority  
When using the Brute Elite for hydronic heating  
with domestic hot water priority a call for heat must be  
supplied to the "T-T or Interlock" terminal. Once the  
call is supplied the control starts the boiler and system  
pumps and begins the ignition process. The ignition  
process consists of a prepurge, trial for ignition, and run  
period. The pre-purge period starts on a call for heat  
Figure 32. Outdoor Reset Setpoint Temperatures.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 41  
setpoint is used to limit the maximum water temperature  
leaving the boiler only. The modulation rate is  
controlled by a 4-20mA (0-10Vdc using converter)  
signal supplied by an external control. When setting up  
a system using an external control care must be taken to  
set the external control algorithms to prevent the boiler  
from short cycling or "hunting " to prevent premature  
component failure.  
All three boilers will continue to fire simultaneously at  
equal input rates or…  
1. Modulation rate approaches minimum firing rate  
(20%), in which case Slave2 will first drop out,  
and then Slave1, accordingly.  
2. System temperature reaches 10F (HS- hysteresis  
value) above setpoint (e.g. 160F), in which case  
remaining boiler will shut off  
3. Any of the boilers approach its high limit tempera-  
ture the individual boiler will modulate back.  
9.5 Hydronic Heating Using Local Lead-  
Lag/Cascading Feature  
9.6 Hydronic Heating Using Local Lead-  
Lag/Cascading Feature with Indirect  
When using single or multiple Brute Elites in lead  
lag configuration, the system sensor and TT terminals of  
the Master boiler create heat demand. The TT terminals  
on the slave boilers are ignored as the demand for those  
heaters is given from the master control. The system  
sensor is also used to control the modulation rate of the  
lead lag system. (see Section 7 for wiring instructions).  
Hot Water  
When using the lead lag boiler system to provide  
indirect domestic hot water heating, the DHW demand  
should be supplied to the master boiler through the existing  
DHW terminals. The lead lag system will change the  
operating mode of the Master boiler only to supply water at  
the DHW setpoint. The remaining boilers on the system  
will continue to supply hydronic heating.  
Let’s consider the following example:  
Three Brute Elite boilers (let’s call them “Lead”,  
“Slave1” and “Slave2”) tied together via Modbus 1  
connection, with appropriate RMT Address (1, 2, 3).  
System sensor input is used to indicate common  
secondary loop temperature.  
When the system is supplying both hydronic heat and  
domestic hot water at the same time both the system pump  
and DHW pump contacts are closed, so special attention  
must be paid to allow for proper operation. During a DHW  
call, the master boiler pump may need to be turned off in  
applications serving both hydronic and domestic heating.  
This will cause the DHW pump to provide flow through  
the boiler and indirect tank (pump must be sized properly)  
when there is a DHW call. To turn off the boiler pump in  
this application the "boiler pump interrupt" jumper should  
be installed. The terminal block location is terminal block 5  
(TB5) contacts labeled "boiler pump interrupt" in the  
control panel.  
System setpoint = 150°F  
HS (hysteresis) = 10°F (default)  
BL (base load) = 50% (default)  
Anti-short-cycle = 5 minutes  
Run sequence is initiated when system temperature  
falls to 140°F (setpoint less hysteresis value). Lead  
boiler will start. All firing rates will depend on several  
application characteristics, including flow rate, system  
load, water volume, etc. Boilers will start at a rate of  
35%. If the load is such that Lead’s rate increases to  
50%, “Slave1” will go through its startup sequence and  
begin firing at 35%. At this point, both boilers (Lead  
and Slave1) will continue to respond simultaneously to  
the load/system characteristics, by modulating up or  
down together, in relation to the relative system setpoint  
and load characteristics.  
9.7 Warm Weather Shutdown  
Warm weather shutdown overrides a hydronic call  
for heat when the outdoor air temperature is greater than  
the warm weather shutdown setpoint. Warm weather  
shutdown is always active whenever there is an outdoor  
sensor attached to the control. To avoid warm weather  
shutdown the warm weather shutdown temperature  
should be increased as necessary. The warm weather  
shutdown setpoint can be adjusted in SETUP mode,  
using the SD menu.  
Scenario 1: If the system loop temperature rises  
quickly, and moves above setpoint, then the  
boilers will simultaneously drop their firing rate. If  
when reaching the point where both boilers drop  
toward their minimum firing rate (20%), then the  
first slave will drop out. Slave1 will remain  
9.8 Domestic Hot Water Demand (BNTV  
unavailable until its ASC timer has expired (5  
minutes). If the load were to increase such to drive  
all active boilers to 50% firing rate or more, during  
the ASC time, Slave2 will begin its startup se-  
quence and begin to fire at 35%, etc.  
only)  
When using the Brute Elite for DHW heating a  
call for heat must be supplied to the "DHW stat"  
terminal located on terminal block 6 (TB6). The DHW  
heating call can be from the supplied DHW sensor or  
from an aquastat. If the DHW sensor is used the heater  
operates to maintain the temperature at the DHW  
sensor. This may allow the actual heater outlet water  
temperature to exceed the DHW sensor setpoint. If an  
aquastat is used to supply the DHW demand the heaters  
Scenario 2: If the system loop temperature continues to  
drop (load increases), then the two boilers will  
increase firing rate together. At 50%, Slave2 will  
begin its firing sequence and be added to the group.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 42  
firing rate is controlled by the DHW setpoint  
The ignition process consists of a prepurge, trial for  
temperature and the water temperature at the heat  
exchanger outlet. Once the DHW call is supplied the  
control starts the boiler and DHW pumps and begins the  
ignition process. The ignition process consists of a  
prepurge, trial for ignition, and run period. The prepurge  
period starts on a call for heat once the fan RPM reaches  
a preset level. The trial for ignition period follows once  
the start-up RPM of the fan is reached. The trial for  
ignition period lasts 4 seconds during which the direct  
spark ignition system and gas valve are energized. At  
the end of the trial for ignition period the flame signal is  
compared with the preset flame threshold value. If the  
flame signal is higher than the flame threshold the Brute  
Elite enters "run". If the flame signal is below the  
threshold the Brute Elite returns to prepurge and starts  
the ignition process over. In "run" the Brute Elite  
monitors the flame signal, call for heat, safeties, and  
water temperatures modulating as needed between  
100% and 20% of rate to satisfy the call for heat.  
ignition, and run period. The prepurge period starts on a  
call for heat once the fan RPM reaches a preset level. The  
trial for ignition period follows once the start-up RPM of  
the fan is reached. The trial for ignition period lasts 4  
seconds during which the direct spark ignition system and  
gas valve are energized. At the end of the trial for ignition  
period the flame signal is compared with the preset flame  
threshold value. If the flame signal is higher than the flame  
threshold the Brute Elite enters "run". If the flame signal is  
below the threshold the Brute Elite returns to prepurge and  
starts the ignition process over. In "run" the Brute Elite  
monitors the flame signal, call for heat, safeties, and water  
temperatures. The heater setpoint is used to limit the  
maximum water temperature leaving the boiler only. The  
modulation rate is controlled by a 4-20mA (0-10Vdc using  
converter) signal supplied by an external control. When  
setting up a system using an external control care must be  
taken to set the external control algorithms to prevent the  
boiler from short cycling or "hunting " to prevent prema-  
ture component failure.  
9.9 Domestic Hot Water Heating Using  
9.10 Domestic Hot Water Heating Using  
External Modulation Control  
Local Lead-Lag/Cascading Feature  
When using multiple Brute Elites to supply  
When using the Brute Elite for DHW heating with  
external modulation control a call for heat must be supplied  
to the "T-T or Interlock" terminal. By supplying a call to  
the "T-T or interlock" terminal the operating temperature  
setpoint defaults to the hydronic heating setpoint, so all of  
the temperature adjustments must be made to the hydronic  
setpoint. Once the call is supplied, the control starts the  
boiler and system pumps and begins the ignition process.  
Domestic hot water only the heaters should be setup as  
stated in Section 8.12 “Lead/Lag Cascading,” and  
Section 9.5 “Hydronic Heating Using Local Lead/Lag  
Cascading Feature.” When the heaters are installed in  
this fashion, all of the setpoints and adjustments are  
done through the Lead Lag menus.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 43  
13. Check gauge for correct water pressure and also  
SECTION 10.  
check water level in the system. If the height  
indicated above the boiler insures that water is at  
the highest point in the circulating loop, then the  
system is ready for operation.  
Operating Instructions  
10.1 Filling the Boiler System  
1. Ensure the system is fully connected. Close all  
bleeding devices and open make-up water valve.  
Allow system to fill slowly.  
2. If make-up water pump is employed, adjust  
pressure switch on pumping system to provide a  
minimum of 12 psi (81.8 kPa) at the highest point  
in the heating loop.  
3. If a water pressure regulator is provided on the  
make-up water line, adjust the pressure regulator  
to provide at least 12 psi (81.8 kPa) at the highest  
point in the heating loop.  
4. Open bleeding devices on all radiation units at the  
high points in the piping throughout the system,  
unless automatic air bleeders are provided at such  
points.  
Note that there is an air bleed located on the left  
side of Brute Elite, on top of the water manifold.  
5. Cycle the boiler pump on and off 10 times, 10  
seconds on and 10 seconds off to remove all air  
from the heat exchanger. Then run system and  
appliance pump for a minimum of 30 minutes with  
the gas shut off.  
14. Prime condensate trap with water (not required for  
BNTH 600, 750, 850).  
15. Refer to local codes and the make-up water valve  
manufacturer’s instructions as to whether the  
make-up water valve should be left open or closed.  
16. After placing the unit in operation, the ignition  
system safety shutoff device must be tested.  
First, shut off the manual gas valve, and call the  
unit for heat. Main gas terminals will be energized,  
attempting to light, for four (4) seconds, and then  
will de-energize. The unit will go into lockout  
after the required number of trial for ignition  
periods.  
Second, turn the power off, press the manual reset  
button on the boiler control, or the user display,  
open the manual gas valve and allow the unit to  
light. While the unit is operating, close the manual  
gas valve and ensure that power to the main gas  
valve has been cut.  
17. Within three (3) days of start-up, recheck all air  
bleeders and the expansion tank as described in  
Steps 4 and 8 above.  
Important Note: The installer is responsible for  
identifying to the owner/operator the location of all  
emergency shutoff devices.  
WARNING  
Failure to remove all air from the heat exchanger  
could lead to property damage, severe injury or death.  
WARNING  
Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician  
to inspect the appliance  
6. Open all strainers in the circulating system, check  
flow switch operation (if equipped), and check for  
debris. If debris is present, clean out to ensure  
proper circulation.  
and to replace any part of the control system and any  
gas control that may have been  
7. Recheck all air bleeders as described in Step 4.  
8. Check liquid level in expansion tank. With the  
system full of water and under normal operating  
pressure, the level of water in the expansion tank  
should not exceed ¼ of the total, with the balance  
filled with air.  
9. Start up boiler according to the procedure in this  
manual. Operate the entire system, including the  
pump, boiler, and radiation units for one (1) hour.  
10. Recheck the water level in the expansion tank. If  
the water level exceeds ¼ of the volume of the  
expansion tank, open the tank drain, and drain to  
that level.  
under water.  
10.2 Operating the Burner and Set Up  
Initial setup must be checked before the unit is put  
in operation. Problems such as failure to start, rough  
ignition, strong exhaust odors, etc. can be due to  
improper setup. Damage to the boiler resulting from  
improper setup is not covered by the limited warranty.  
10.2.1 Burner Operation  
REQUIRED TOOLS: differential pressure gauge  
capable of reading negative 0.01 inches W.C. (0.002kPa),  
screw drivers, torx bits, combustion analyzer.  
1. Using this manual, make sure the installation is  
complete and in full compliance with the  
instructions and all local codes.  
11. Shut down the entire system and vent all radiation  
units and high points in the system piping, as  
described in Step 4.  
12. Close make-up water valve and check strainer in  
pressure reducing valve for sediment or debris  
from the make-up water line. Reopen make-up  
water valve.  
2. Determine that the appliance and system are filled  
with water and all air has been bled from both.  
Open all valves.  
3. Observe all warnings on the Operating Instructions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 44  
label and turn on gas and electrical power to  
in Table 16. If the CO2 is not within the range  
shown, adjustments may be made. To adjust the  
low fire CO2, locate the low fire adjuster screw  
according to the appropriate figure. Slowly make  
adjustments in 1/16 of a revolution increments  
until the CO2 is within the range identified.  
4. Repeat steps 2 and 3 to confirm that the CO2  
ranges are within the required ranges. Adjust if  
necessary.  
appliance.  
4. Brute Elite will enter the start sequence. Blower  
and pump will energize for pre-purge, then the  
ignition sequence starts. After all safety devices  
are verified, the gas valve opens. If ignition  
doesn’t occur, turn off the Brute Elite, check that  
there is proper gas supply. Wait 5 minutes and  
start the unit again.  
5. Turn Brute Elite on.  
5. Confirm that the differential pressure is still within  
the appropriate range.  
6. After placing the appliance in operation, the  
Burner Safety Shutoff Device must be tested:  
(a) Close gas shutoff valve with burner operating.  
(b) Flame will go out and blower will continue to  
run for the post purge cycle. One or three  
additional attempts to light will follow  
6. If any of the measurements cannot be adjusted  
to the specified ranges or the CO levels are  
above 150ppm when adjusted please consult the  
factory for further information.  
7. Remove the differential pressure gauge from the  
air and gas pressure taps making sure to close all  
ports after the gauge has been removed.  
including pre-purge, ignitor on, valve/flame on  
and post purge. Ignition will not occur as the  
gas is off. The ignition control will lockout.  
(c) Open gas shutoff valve. Reset the boiler  
control by pressing the RESET button on the  
control or on the display. Restart the  
WARNING  
Improper adjustment may lead to poor combustion  
quality, increasing the amount of carbon monoxide  
produced. Excessive carbon monoxide levels may  
lead to personal injury or death.  
appliance. The ignition sequence will start  
again and the burner will start. The appliance  
will return to its previous mode of operation.  
DIFFERENTIAL  
PRESSURE  
GAS TYPE  
HIGH FIRE, CO2  
LOW FIRE, CO2  
Caution  
Should any odor of gas be detected, or if the gas  
burner does not appear to be functioning in a normal  
manner, CLOSE MAIN SHUTOFF VALVE. Do not  
shut off switch. Contact your heating contractor, gas  
company, or factory representative.  
Natural  
9.0 to 8.8%  
0.5% lower than  
high fire setting  
-.005 to  
-.015" wc  
Propane  
10.0 to 9.8%  
Table 16. CO2 Range and Pressure Differential.  
10.3 Shutting Down Brute Elite  
10.2.2 Boiler Setup and Adjustment  
1. Connect a manometer capable of reading 0.01"wc  
to the gas valve locations shown in Figure 33. The  
positive side of the manometer should be  
1. Turn off the main electrical disconnect switch.  
2. Close all manual gas valves.  
3. If freezing is anticipated, drain Brute Elite and be  
sure to also protect building piping from freezing.  
All water must be removed from heat exchanger or  
damage from freezing may occur.  
connected to the location labeled “air pressure  
tap.” The negative side of the manometer should  
be connected to the location labeled "gas pressure  
tap." This differential pressure should be slightly  
negative (see Table 16).  
This step to be performed by a qualified service person.  
10.4 To Restart Brute Elite  
2. Measure the CO2/O2 in the flue products at high  
fire. The Brute Elite can be forced to high fire to  
allow for easier setup. Refer to Section 8.1, Table  
14 for instructions on how to access the forced rate  
menu. The CO2 readings should be between the  
values shown in Table 16. If the CO2 is not within the  
range shown, adjustments may be made. To adjust  
the high fire CO2, locate the high fire adjuster screw  
according to the appropriate figure. Slowly make  
adjustments in 1/16 of a revolution increments until  
the CO2 is within the range identified.  
3. Measure the CO2/O2 in the flue products at low  
fire. Brute Elite can be forced to low fire to allow  
for easier setup. Refer to Section 8.1, Table 14 for  
instructions on how to access the forced rate menu.  
CO2 readings should be between the values shown  
If drained, follow Section 10.1 in this manual  
for proper filling and purging.  
1. Turn off the main electrical disconnect switch.  
2. Close all manual gas valves.  
3. WAIT FIVE (5) MINUTES.  
4. Set the aquastat or thermostat to its lowest setting.  
5. Open all manual gas valves.  
6. Reset all safety switches (pressure switch, manual  
reset high limit, etc.).  
7. Set the temperature controller to the desired  
temperature setting and switch on electrical power.  
8. Burner will go through a prepurge period and  
ignitor warm-up period, followed by ignition.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 45  
80–285  
399  
500  
600  
750, 850  
Figure 33B. Brute Elite Gas Valves (600, 750 and 850).  
Figure 33A. Brute Elite Gas Valves (285, 399 and 500).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 46  
qualified service technician should inspect the basic  
items listed below every year:  
SECTION 11.  
Maintenance  
a. Appliance control  
b. Automatic gas valve  
c. Pressure switches  
d. Blower  
f. Flow switch  
g. Low water cutoff  
h. Burner  
WARNING  
Disconnect all power to the appliance before  
attempting any service to the appliance. Contact with  
electricity can result in severe injury or death.  
i. Heat exchanger  
e. Pump  
11.2.1 Burner  
11.1 System Maintenance  
Check the burner for debris. Remove the blower  
arm assembly to access the burner. Remove the 4 bolts  
connecting the blower to the arm (see Figure 34).  
Remove the 5 bolts, which hold the burner arm in place.  
Pull burner up and out. Clean burner, if necessary, by  
blowing compressed air from the outside of the burner  
into the center of the burner, and wipe the inside of the  
burner clean with glass cleaner. A dirty burner may be  
an indication of improper combustion or dirty  
combustion air. Determine the cause, and correct. If  
damaged, replace the burner gasket when replacing the  
burner.  
(yearly, unless otherwise noted)  
1. Lubricate the system water-circulating pump, if  
required, per the instructions on the pump.  
2. If a strainer is employed in a pressure reducing  
valve or the piping, clean it every six moBNTHs.  
3. Inspect the venting system for obstruction or  
leakage at least once a year. Periodically clean the  
screens in the vent terminal and combustion air  
terminal (when used).  
4. Keep the appliance area clear and free from  
combustible materials, gasoline, and other  
flammable vapors and liquids.  
NOTE: When installing the burner, make sure the  
flange is aligned with the mating surface, as each is  
keyed to control fit.  
5. If the appliance is not going to be used for  
extended periods in locations where freezing  
normally occurs, it should be isolated from the  
system and completely drained of all water.  
6. Low water cutoffs, if installed, should be checked  
every year. Float type low water cutoffs should be  
flushed periodically.  
7. Inspect and clean the condensate collection, float  
switch and disposal system yearly.  
8. When a means is provided to neutralize  
condensate, ensure that the condensate is being  
neutralized properly.  
9. Inspect flue passages, and clean with brushes/  
vacuums, if necessary. Sooting in flue passages  
indicates improper combustion. Determine the  
cause and correct.  
10. Inspect the vent system and air intake system, and  
ensure that all joints are sealed properly. If joints  
need to be resealed, completely remove existing  
sealing material, and clean with alcohol. Apply  
new sealing material, and reassemble.  
11.2.2 Modulating Gas Valve / Venturi  
The modulating gas valve consists of a valve body  
that incorporates the ON/OFF gas flow control and a  
negative pressure regulator. It provides the air/gas ratio  
control in combination with the venturi to the unit. It is  
designed to operate with gas supply pressure between 4  
and 13 inches w.c.. To remove the gas valve and or  
venturi, shut off the 120 Volt power supply to the  
boiler. Turn off all manual gas valves connecting the  
boiler to the main gas supply line. Remove the front  
door of the boiler to gain access to the gas valve and  
venturi. Disconnect the four (4) flange bolts connecting  
the gas manifold pipe to the gas valve. Remove the  
electrical connections to the gas valve. Remove the bolts  
connecting the venturi flange to the blower. This allows  
the entire gas valve/venturi assembly to be removed as  
an assembly to facilitate inspection and cleaning.  
After the valve has been removed, reassemble in  
reverse order making sure to include all gaskets and O-  
rings. Turn on the manual gas valves and check for gas  
leaks. Turn on the 120 Volt power. Place the unit in  
operation following the instructions in Section10. Once  
the boiler is operating check for leaks again and confirm  
all fasteners are tight.  
11.2 Appliance Maintenance and  
Component Description  
Use only genuine Bradford White replacement  
parts.  
Check appliance setup according to Section 10.  
11.2.3 Appliance Control  
Caution  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and danger-  
ous operation. Verify proper operation after servicing.  
Brute Elite has an integrated control that  
incorporates manual reset high limit control, operating  
temperature control, modulating control, ignition  
control, outdoor reset control, pump control and many  
other features. If any of these features are thought to be  
defective, please consult the factory for proper trouble  
shooting practices prior to replacing the control. If  
control replacement is required, turn off all power to the  
Brute Elite gas and electric controls are engineered  
for long life and dependable operation, but the safety of  
equipment depends on their proper functioning. Only a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 47  
appliance and shut off all manual gas valves to the  
appliance. Remove the front door to the appliance and  
the control panel plastic bezel. Remove all wire  
connections from the control board. The control board  
connections are keyed to only allow connection in the  
proper location, but proper handling techniques should  
be used to avoid damage to the wiring or connectors. To  
remove the control push in on the two tabs on the left  
side of the board to unlatch the clips from the control  
panel. Rotate the control around the fastening points on  
the right side of the control to remove the hooks from  
the control panel. To replace the control repeat the steps  
above in the reverse order making sure to connect all  
wires in the proper location. Place the appliance in  
operation following the steps outlined in Section 10.  
11.2.4 Ignitor Assembly  
ignitor assembly to the burner door. Remove and  
replace the old ignitor assembly gasket. Reinstall a new  
ignitor assembly in the reverse order if the old assembly  
is determined defective. Replace gasket if necessary.  
11.2.5 Flame Sensor  
The flame sensor is a single rod system. To replace  
the flame sensor electrode, shut off the 120 Volt power  
supply to the boiler. Turn off all manual gas valves  
connecting the boiler to the main gas supply line.  
Remove the front door of the boiler to gain access to the  
flame sensor electrode. Remove the flame sensor wire  
from the electrode. Remove the two bolts fastening the  
electrode to the burner doors. Remove and replace the  
old flame sensor gasket. Reinstall a new flame sensor  
electrode in the reverse order if the old electrode is  
determined defective.  
The ignitor assembly is a two rod system that  
Caution  
Igniters and sensors get hot and  
can cause burns or injury.  
consists of a ground rod and a sense rod. To remove the  
ignitor assembly, shut off the 120 Volt power supply to  
the appliance. Turn off all manual gas valves connecting  
the appliance to the main gas supply line. Remove the  
front door of the boiler to gain access to the ignitor  
assembly. Remove the two wires connected to the  
assembly. Then remove the two bolts connecting the  
Figure 34. Burner Service.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 48  
11.2.6 Transformer with Integral Circuit  
Caution  
Breaker  
Black carbon soot buildup on a dirty heat exchanger  
can be ignited by a random spark or flame. To  
prevent this from happening, dampen the soot  
deposits with a wet brush or fine water spray before  
servicing the heat exchanger.  
The appliance has a 24Vac transformer with  
integral 4 amp circuit breaker installed for supplying the  
control voltage required for the appliance only. The  
transformer is sized for the appliance load only and  
should not be used to supply power to additional field  
devices. If additional loads are added or a short occurs  
during installation the integral circuit breaker may trip.  
If this happens make sure to reset the circuit breaker  
prior to replacing the transformer.  
1. Shut off the 120 Volt power supply to the boiler  
2. Turn off all manual gas valves connecting the  
boiler to the main gas supply line.  
Depending upon the revision of the appliance the  
transformer may be mounted to the back or underneath  
the control panel. In either case, if the transformer must  
be replaced turn off the 120Vac power to the appliance.  
Remove the transformer wires from terminal blocks.  
Remove the fasteners holding the transformer and  
remove the transformer. Replace with a new transformer  
in reverse order.  
3. For NT 600 models only (all other sizes please  
skip to step four). NT 600 models will require the  
gas valve to be removed in order to remove the  
burner door. To do this, remove the wire  
connections from the gas valve. Remove the flange  
bolts from the gas supply pipe connected to the gas  
valve (1B). Remove the flange bolts connecting  
the gas train to the venturi (1A). Remove the gas  
train assembly keeping gaskets and o-rings.  
If the transformer is replaced with parts other than  
the OEM transformer, be sure to add circuit protection if  
it is not integral to the new transformer.  
4. Remove the four bolts connecting the blower  
flange to the burner door arm.  
5. Remove the nuts located on the outside diameter  
of the burner door to the heat exchanger.  
WARNING  
Failure to include proper circuit protection may lead  
to premature component failure, fire, injury or death.  
6. Remove the burner door/burner assembly from the  
heat exchanger.  
11.2.7 Blower  
7. Disconnect the condensate drain line.  
The combustion air blower is a high-pressure  
centrifugal blower with a variable speed motor. Speed  
of the motor is determined by the control logic. 120  
Volts remain on to the blower at all times. If a blower  
change is required, turn off the 120 Volt power and gas  
supply to the unit. Take the front panel off. Disconnect  
the 120 Volt and control signal connections from the  
blower. Disconnect the bolts connecting the venturi to  
the blower housing. Disconnect the fan outlet bolts from  
the burner door blower arm. If the fan is determined to  
be defective replace the existing fan with a new one  
reversing the steps above. Make sure to install all of the  
required O-rings and gaskets between the blower arm  
and the blower and blower face and venturi flange.  
11.2.8 Heat Exchanger Coils  
8. Attach a longer hose to drain and run to a bucket.  
9. Clean the heat exchanger by brushing light  
accumulations of soot and debris. Use a brush with  
soft bristle (non metal) to avoid damaging the  
surface of the heat exchanger tubes.  
10. Once the tubes have been brushed clean rinse the  
tubes and combustion chamber with a small  
amount of water to rinse all of the debris out of the  
bottom of the flue collector and into the longer  
condensate trap line, which is being diverted into a  
separate container.  
NOTE: The Warranty does not cover damage caused  
by lack of required maintenance, lack of water flow,  
or improper operating practices.  
Black carbon soot buildup on the external surfaces  
of the heat exchanger is caused by one or more of the  
following; incomplete combustion, combustion air  
problems, venting problems and heater short cycling.  
Soot buildup or other debris on the heat exchanger may  
restrict the flue passages.  
If black carbon soot buildup on the heat exchanger  
is suspected, disconnect electrical supply to the unit,  
and turn off the gas supply by closing the manual gas  
valve on the unit. Access the heat exchanger through the  
burner door at the front of the boiler, and inspect the  
tubing using a flashlight. If there is a buildup of black  
carbon soot or other debris on the heat exchanger, clean  
per the following:  
WARNING  
Failure to rinse the debris from the heat exchanger  
and temporary drain line may lead to clogged  
condensate lines, traps and neutralizers. Condensate  
pumps (if used) may also be damaged from the  
debris left behind, possibly causing property damage.  
11. Install all components removed in the reverse  
order to place the appliance back in operation.  
Make sure all gaskets are in place as components  
are installed. Replace any damaged gaskets. Do  
NOT reuse damaged gaskets.  
12. Place the appliance in operation according to  
Section 10 checking all gas connections for leaks.  
Confirm all fasteners are tight.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 49  
11.2.9 Gas Pressure Switches (optional)  
SECTION 12.  
The high and low gas pressure switches are 24V  
manual reset switches that act to cut power to the gas  
valves if the gas pressure is too low or too high for  
proper operation. The gas pressure switches used are  
integrally vent limited, and do not require venting to  
atmosphere. To remove a switch, remove the screw on  
the plastic housing and pull the clear cover off.  
Disconnect the two wires from the screw terminals.  
Twist the switch off the pipe nipple. Reassemble in  
reverse order. For natural gas, set the low gas pressure  
switch to 3" w.c. For propane, set the low gas pressure  
switch to 5" w.c. For natural and propane, set the high  
gas pressure switch to 14".  
Trouble Shooting  
12.1 Sequence of Operation  
Brute Elite is a cold start appliance that should  
start only on a call for heat from a tank aquastat, room  
thermostat, zone valve end switch or other space  
temperature control device.  
1. Upon a call for heat: (a) the internal pump and  
system pump will start; (b) the blower will begin a  
30 second pre-purge.  
2. Following the prepurge cycle the direct spark  
ignition will spark and will begin a 4 second trial  
for ignition. The unit is allowed one or three  
ignition retries.  
3. The gas valve will then be energized and a reduced  
rate ignition will occur. The unit will remain in a  
reduced rate start-up period for several seconds.  
4. After the reduced rate start time is over, the unit  
will be in normal operation. Firing rate will  
modulate based on the heating load via the  
temperature controller settings and readings.  
5. When the call for heat is complete, or the unit reaches  
its setpoint temperature, the gas valve will close, and  
the fan will continue to run for its 20 second post-  
purge. If a pump delay time is used, the pump will  
continue to run for the specified amount of time  
(adjustable from 0.1 to 10 minutes).  
11.2.10 Gas Conversion  
Brute Elite units can be converted from natural to  
propane gas or from propane to natural gas easily in the  
field. Some units require the addition of a gas orifice  
along with proper gas valve adjustment. Other units  
require no additional parts, only proper gas valve  
adjustment. Please contact the Bradford White factory  
for specific information regarding the gas conversion of  
an appliance. If a gas conversion is performed, the unit  
must be identified with the appropriate gas labels and a  
conversion sticker to allow technicians performing  
maintenance in the future to properly identify the gas  
type of the appliance.  
SIZE (MBTU)  
80  
KIT NUMBER  
CA006201  
CA006202  
CA006203  
CA006204  
CA006204  
CA006205  
CA006207  
CA006207  
CA006207  
CA006207  
CA006207  
12.2 Short Cycling  
Because Brute Elite is a modulating boiler, and its  
input will decrease when there is a reduction in heating  
load, short cycling is greatly reduced. If the heating load  
drops below the minimum input of the boiler for an  
extended period, the boiler will have a tendency to short  
cycle. This can be a symptom of improper control  
strategy or setpoints, or a load distribution problem.  
Brute Elite has a built-in anti-short cycle (ASC) feature.  
ASC is a timed setting that will delay the boiler start for  
a specified time after one call for heat is completed.  
ASC time may be adjusted as desired (see Section 8 for  
more information).  
105  
150  
199  
210  
285  
399  
500  
600  
750  
850  
12.3 Error Codes - See Table 18.  
Table 17. Propane Gas Conversion Kits.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 50  
CODE# PROBLEM  
PROBABLE CAUSE  
SOLUTION  
COMMON LOCKOUT CODES  
27 Internal error  
Flame rod to ground  
Faulty flame detector  
Faulty transformer  
Check wiring / probe grounded, dirty probe  
Clean or replace flame detector  
Check/correct supply line voltage; replace faulty  
transformer  
47 Flame rod to ground leakage  
49 24VAC voltage low/high  
52 Motor tachometer fault  
Faulty fan / fan wiring  
fan circuit  
Check fan harness wiring for continuity; replace faulty  
53 AC inputs phase reversed  
61 Anti short cycle  
Reverse 24V hot/neutral - use common ground  
Change ASC timer setting  
Call for heat will be held  
until timer resets  
62 Fan speed not proved  
63 LCI off  
Dirty / defective fan  
Safety chain interrupt  
Clean or replace fan; check wiring  
Check flow switch, aux high limit, LWCO, gas  
pressure switches, condensate level and correct  
problem  
69 Outlet high limit  
High limit tripped  
Determine cause: low/no flow, valves closed, settings  
and correct  
79 Outlet high limit  
80 DHW high limit  
81 Delta T inlet/outlet limit  
82 Stack limit  
Check pump, time delay, valves closed, etc. and  
correct overtemp  
High limit reached  
High limit reached  
Could be caused by high ambient temperature, or  
high return water temperature  
88 Outlet T-rise limit  
90 Heat exchanger high limit  
91 Inlet sensor fault  
High limit reached  
Diagnose / repair cause of high temperature  
92 Outlet sensor fault  
93 DHW sensor fault  
95 Stack sensor fault  
Faulty sensor or wiring  
Check wiring / replace sensor; condition can be  
caused by short  
96 OAT temperature sensor fault  
temperature sensor  
Faulty outdoor air  
is open or shorted  
Check wiring and sensor for short; replace sensor  
105 Flame detected  
out of sequence  
Flame exists at burner  
when it should not be  
Clean burner of soot or other debris that could  
maintain flame  
106 Flame lost in MFEP  
107 Flame lost early in Run  
108 Flame lost in Run  
109 Ignition failed  
Unstable flame during  
lighting / flame proving  
sequence  
Check venting, gas supply pressure, burner, fan, etc.  
Problem with ignitor, or  
other ignition-related device  
Check / replace ignitor, wiring; check for shorting  
in ignitor cable  
113 Flame circuit timeout  
Flame not established  
within expected time limit  
Check all combustion components; purge gas;  
check ignition source  
122 Lightoff rate proving failed  
123 Purge rate proving failed  
128 Fan speed failed / prepurge  
129 Fan speed failed / preignition  
130 Fan speed failed / ignition  
Fan did not reach  
expected RPM  
Check fan wiring; replace fan  
131 Fan movement detected  
during standby  
Fan should not be moving  
when not powered  
Check for common venting problems or otherwise  
forced air  
132 Fan speed failed during run  
Fan lost or gained speed  
during run sequence away  
from control spec  
Fan overheating or otherwise failing; check cable;  
replace fan  
137 ILK failed to close  
No power at interlock ILK  
Check J5 pin 1 for power - if no power, confirm  
safeties are closed  
continued next page >  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 51  
CODE# PROBLEM  
PROBABLE CAUSE  
SOLUTION  
ALERT CODES  
49 Maximum cycle count  
was reached  
Control operates correctly,  
however the cycle count will  
not increment any higher  
than 999,999 cycles  
Replace controller or adjust the count using blue display  
50 Maximum hours count  
was reached  
Control operates correctly,  
however the hours count will  
not increment any higher  
than 999,999 hours  
248 CH outdoor temperature  
was invalid  
251 CH ODR max outdoor temp-  
erature setpoint was invalid  
Confirm outdoor reset  
settings. An invalid  
adjustment has been  
made  
252 CH ODR min outdoor temp-  
erature setpoint was invalid  
253 CH ODR min water temp-  
erature setpoint was invalid  
Adjust setting to within appropriate range  
254 CH ODR temperature range  
was too small  
Increase Outdoor air temp-  
erature min and max values  
to a difference greater than  
22°F (12°C)  
(min. 12°C / 22°F)  
255 CH setpoint minus ODR  
min water temperature was  
too small (min. 12°C / 22°F)  
Increase setpoint or  
Increase Outdoor water  
temperature min and max  
values to a difference greater  
than 22°F (12°C)  
decrease min water temp.  
565 Heat exchanger T-rise limit  
was exceeded  
Heat exchanger temperature Check for correct water flow  
rise exceed  
MISCELLANEOUS  
Boiler will not stay lit  
Indicates lack of flame signal, Check flame detector wiring; clean / replace flame  
check fault code on display  
detector  
Boiler bangs, knocks, hisses  
Insufficient water flow /  
Check for proper flow, follow piping guidelines in  
pump failure; improper piping manual; replace pump; improper glycol percentage  
(see Section 4.3)  
Flame pulsates, venting  
noise or has difficulty lighting  
Insufficient / improper  
venting; dirty burner; air in  
gas line; dirty heat exchanger  
Ensure venting complies with Section 2  
980 Display error  
981 Display error  
Communication error  
between the control  
and display.  
Check wiring and connectors. Possible software  
revision incompatibility.  
Communication error  
between the control  
and display.  
Check wiring and connectors. Possible software  
revision incompatibility.  
Table 18. Error Codes.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 56  
Figure 35. Jacket Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 57  
Figure 36A. Internal Components, Sizes 80–210.  
Figure 36B. Internal Components, Sizes 285–600.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 58  
Figure 36C. Internal Components, Sizes 750-850.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 59  
Figure 37A. Gas Train Components, Sizes 80-500.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 60  
Figure 37B. Gas Train Components, Sizes 600-850.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 61  
Figure 38. Heat Exchanger Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BRADFORD WHITE CORP .  
Page 62  
Figure 39. Electrical Components.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Brut e Elit e  
Page 63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.  
®
Ambler, PA 19002  
Tech. Service (800) 334-3393  
Service Parts (800) 538-2020  
Warranty Service (800) 531-2111  
Litho in U.S.A. © Bradford White 1102 Document 1243  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Billy Goat Blower P N 440120 User Manual
Bissell Vacuum Cleaner 8930 User Manual
Bosch Appliances Water Heater GWH 1000 User Manual
Bose Headphones AM3834075 User Manual
Breville Microwave Oven BMO100 User Manual
Britax Car Seat BB0 633 00 User Manual
Broan Ventilation Hood 778WH User Manual
Brother Laptop WP 700D User Manual
Campbell Hausfeld Cordless Sander PL1565 User Manual
Casio Cash Register pcr 360 User Manual