Installation and Operation Instructions
Docyment 1246
Installation and Operation
Instructions for
BRUTE MAGNUM
Modulating Boiler
Model BRHHH
Modulating Water Heater
Model BRHHV
U.S. Patent No. 6,644,393
Canada Patent Pending
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
qualified in hot water boiler and heater installation and maintenance. Improper installation and/or
operation could create carbon monoxide gas in flue gases which could cause serious injury, property
damage, or death. Improper installation and/or operation will void the warranty.
AVERTISSEMENT
WARNING
Assurez-vous de bien suivres les instructions
If the information in this manual is not
données dans cette notice pour réduire au
followed exactly, a fire or explosion may
minimum le risque d’incendie ou d’explosion
result causing property damage, personal
injury or loss of life.
ou pour éviter tout dommage matériel, toute
blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
d’autres vapeurs ou liquides inflammables dans
le voisinage de cet appareil ou de tout autre
appareil.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous
servir des téléphones dansle bâtiment où vous
vous trouvez.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not
use any phone in your building.
• Immediately call your gas supplier from a
nearby phone. Follow the gas supplier's
instructions.
• Appelez immédiatement votre fournisseur de
gaz depuis un voisin. Suivez les instructions
du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de
gaz, appelez le service des incendies.
L’installation et l’entretien doivent être assurés par
un installateur ou un service d’entretien qualifié ou
par le fournisseur de gaz.
• If you cannot reach your gas supplier, call
the fire department.
Installation and service must be performed
by a qualified installer, service agency, or gas
238-49223-00A REV 4/11
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 3
Table of Contents
5.5.3 Offset ............................................................. 26
5.5.4 Throttling Range............................................ 26
5.5.5 Minimum Output Setting................................ 27
5.5.6 Integration Constant ...................................... 27
SECTION 1
General Information
1.1
1.2
1.3
1.4
1.5
1.6
Introduction...................................................... 5
Model Identification.......................................... 5
Warranty .......................................................... 6
Dimensions...................................................... 6
Locating the Appliance..................................... 6
Locating Pump-Mounted Water
5.6
5.7
5.8
Mixing System and Control............................ 28
External Control Connections........................ 29
Wiring Diagrams ............................................ 29
SECTION 6
Heater with Respect to Storage Tank(s).......... 6
Locating Pump-Mounted Boiler with
Operating Instructions
1.7
1.8
6.1
6.2
6.3
6.4
Filling the Boiler System................................ 36
Operating the Burner and Set Up.................. 36
Shutting Down the Brute Magnum................. 38
To Restart the Brute Magnum........................ 38
Respect to Return/Supply Header................... 6
Locating Appliance for Correct Vent Distance
From Outside Wall or Roof Termination........... 7
SECTION 2
SECTION 7
Venting and Combustion Air
Maintenance
2.1
Combustion Air ................................................ 8
7.1
7.2
System Maintenance..................................... 38
2.1.1 Combustion Air From Room ............................ 8
2.1.2 Intake Combustion Air...................................... 8
Appliance Maintenance and
Component Description................................. 38
2.2
2.3
Venting............................................................. 9
Locating Vent & Combustion Air Terminals...... 9
7.2.1 Burner............................................................ 40
7.2.2 Filter............................................................... 40
7.2.3 Modulating Gas Valve.................................... 40
7.2.4 Safety Gas Valve ........................................... 41
7.2.5 Manual Reset High Limit Control................... 41
7.2.6 Temperature Control...................................... 41
7.2.7 Auto Reset Temperature Limit ....................... 41
7.2.8 Mixing Control................................................ 41
7.2.9 Mixing Valves................................................. 41
7.2.10 Mixing Actuator.............................................. 42
7.2.11 Ignition Control............................................... 42
7.2.12 Ignitor / Flame Sensor Assembly................... 42
7.2.13 Transformers ................................................. 42
7.2.14 Blower............................................................ 42
7.2.15 Flow Switch.................................................... 42
7.2.16 Heat Exchanger Coils.................................... 42
7.2.17 Normally Open Vent Valve............................. 43
7.2.18 Motorized Safety Valve.................................. 43
7.2.19 Gas Pressure Switches ................................. 43
2.3.1 Horizontal Vent Terminal.................................. 9
2.3.2 Side Wall Combustion Air Terminal................ 12
2.3.3 Vertical Vent Terminal .................................... 12
2.3.4 Vertical Combustion Air Terminal................... 12
2.4
Common Vent Test – Boilers ......................... 12
SECTION 3
Gas Supply and Piping
3.1
Gas Supply and Piping.................................. 13
SECTION 4A
Water Connections – BRHHH Boiler
4A.1 Heating System Piping:
Hot Supply Connections – Boiler................... 14
4A.2 Cold Water Make-Up – Boiler........................ 14
4A.3 Freeze Protection – Boiler............................. 15
SECTION 4B
Water Connections – BRHHV Water Heater
4B.1 Water System Piping – Water Heater............ 15
4B.2 Hot Water Supply Piping – Water Heater ...... 15
4B.3 Water Flow Requirements – Water Heater.... 16
4B.4 Combined Water (potable)
SECTION 8
Troubleshooting
8.1
8.2
8.3
Sequence of Operation.................................. 43
Resolving Lockouts........................................ 44
Delayed Ignition – Possible Causes.............. 44
Heating and Space Heating........................... 18
4B.5 Freeze Protection — Water Heater ............... 19
8.3.1 High Lockup Pressure (LP Appliances)
- Occurs on Start-up ...................................... 44
8.3.2 Gas Valve Regulation .................................... 44
8.3.3 Defective Burner - Occurs on
SECTION 5
Electrical Connections
5.1
5.2
5.3
5.4
Main Power.................................................... 24
Pump Connections ........................................ 24
Temperature Control – Boiler......................... 24
Temperature Control – Water Heater............. 24
Startup or at Burner Shutdown...................... 44
8.4
8.5
8.6
Short Cycling – Boiler.................................... 44
Short Cycling – Water Heater........................ 45
High Gas Consumption.................................. 45
5.4.1 Remote Water Heater Temperature Control.. 24
5.4.2 Internal Water Heater Temperature Control... 25
SECTION 9
5.5
Temperature Control Features....................... 25
Replacement Parts
5.5.1 Temperature Setpoint .................................... 25
5.5.2 Differential Setting ......................................... 25
9.1
9.2
General Information....................................... 45
Parts List........................................................ 45
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 4
List of Tables
Table 1
Table 2
Table 3
Clearances........................................................6
Table 4
Table 5
Table 6
Table 7
Required Combustion Air Piping Material..........9
Required Venting Material.................................9
Gas Piping Sizes.............................................13
Air & Gas Orifice Differentials at Full Fire........38
Vent / Air Pipe Sizes..........................................7
Horizontal Vent and Air Terminals
for Indoor Installations.......................................8
List of Figures
Figure 1
Figure 2
Figure 3
Figure 4
Figure 5
Figure 6
Dimensional Drawing ........................................7
Combustion Air and Vent Through Roof............8
Combustion Air and Vent Through Side-Wall..10
Hydronic Piping – Multiple Boilers...................16
Hydronic Piping – Multiple Boilers (Alternate).17
Hydronic Piping – One Boiler,
Multi-Temperature System ..............................18
Internal Piping Schematic................................19
Water Heater Piping – One Heater, One Tank....20
Figure 19 Wiring Diagram Size 1200, Code B.................32
Figure 20 Wiring Diagram, Sizess 1600, 2000 and
2400, Code B ..................................................33
Figure 21 Wiring Schematic, Size 1200,
Standard and Codes A and F..........................34
Figure 22 Wiring Schematic, Sizes 1600, 2000 and
2400, Standard and Codes A and F................34
Figure 23 Wiring Schematic, Size 1200, Code B ............35
Figure 24 Wiring Schematic, Sizes 1600, 2000 and
2400, Code B ..................................................35
Figure 7
Figure 8
Figure 9
Water Heater Piping – Multiple Heaters,
One Tank.........................................................21
Figure 25 Gas/Air Test Panel...........................................37
Figure 26 Test Panel Valves............................................37
Figure 27 Gas Trains.......................................................39
Figure 28 Gas Trains.......................................................40
Figure 29 Control Panel...................................................41
Figure 30 Combustion Components................................49
Figure 31 Gas Train/Combustion Air Components..........50
Figure 32 Gas Train Components ...................................51
Figure 33 Electrical Components ....................................52
Figure 34 Heat Exchanger / Water Path Components ....53
Figure 35 Heat Exchanger / Water Path Components ....54
Figure 36 Jacket Components.........................................55
Figure 10 Water Heater Piping – One Heater,
Multiple Tanks..................................................22
Figure 11 Water Heater Piping – Multiple Heaters,
Multiple Tanks..................................................23
Figure 12 Temperature Control........................................24
Figure 13 Proprotional Control ........................................25
Figure 14 Control Parameter Graph................................26
Figure 15 Control Parameter Graph................................27
Figure 16 Control Parameter Possible Interference........28
Figure 17 Wiring Diagram, Size 1200,
Standard and Codes A and F..........................30
Figure 18 Wiring Diagram, Sizes 1600, 2000 and
2400, Standard and Codes A and F................31
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 5
improper installation.
The Brute Magnum appliance is protected
against over pressurization. A pressure relief valve is
fitted to all appliances. It is installed inside the jacket,
at the water outlet of the unit. (See Sections 4A and 4B
for instructions on how to install a relief valve outlet.)
Section 1
GENERAL INFORMATION
USING THIS MANUAL – Because the Brute
Magnum Boilers and Brute Magnum Water
Heaters are identical appliances, with the exception
of materials of manufacture, labels and ultimate
use application, this manual provides information
for the proper installation, operation and
maintenance of both products. Where differences
exist between the application of the appliances and
their operation, the sections pertinent to only one
appliance or the other will be so identified.
IMPORTANT: The inlet gas pressure to the appliance
must not exceed 13" W.C. (3.2kPa).
All installations must be made in accordance
with 1) American National Standard Z223.1/NFPA54-
Latest Edition “National Fuel Gas Code” or 2) CSA
B149.1 “Natural Gas and Propane Installation Code”
and with the requirement of the local utility or other
authorities having jurisdiction. Such applicable
requirements take precedence over the general
instructions contained herein.
All electrical wiring is to be done in accordance
with the local codes, or in the absence of local codes,
with: 1) The National Electrical Code ANSI/NFPA No.
70-latest Edition, or 2) CSA STD. C22.1 “Canadian
Electrical Code - Part 1”. This appliance must be
electrically grounded in accordance with these codes.
WARNING
The Brute Magnum hydronic, boiler or water
heater must be installed in accordance with the
procedures detailed in this manual, or the Bradford
White warranty will be voided. The installation must
conform to the requirements of the local jurisdiction
having authority, and, in the United States, to the
latest edition of the National Fuel Gas Code, ANSI
Z223.1/NFPA54. In Canada, the installation must
conform to the latest edition of CSA B149.1 Natural
Gas and Propane Gas Installation Code, and/
or local codes. Where required by the authority
having jurisdiction, the installation of Brute Magnum
boilers must conform to the Standard for Controls
and Safety Devices for Automatically Fired Boilers,
ANSI/ASME CSD-1. Any modifications to the boiler,
its gas controls, or wiring may void the warranty.
If field conditions require modifications, consult
the factory representative before initiating such
modifications.
1.2 Model Identification
Consult the rating plate on the unit. The
following information describes the model number
structure.
(1-3) Model Series Designation
B R H = Brute Magnum mid-sized commercial
(3) Model Efficiency
H = High Efficiency (condensing)
(4) Usage
H = Hydronic
V = Volume Water
(5-8) Size
1 2 0 0 = 1,200,000 BTU/hr input
1 6 0 0 = 1,600,000 BTU/hr input
2 0 0 0 = 2,000,000 BTU/hr input
2 4 0 0 = 2,400,000 BTU/hr input
1.1 Introduction
This manual provides information necessary
for the installation, operation, and maintenance of
Bradford White Brute Magnum (copper tube or
cupronickel tubes) appliances. Read it carefully before
installation.
(9) Fuel
N = Natural Gas
P = Liquid Propane
(10) Altitude
All application and installation procedures should
be reviewed completely before proceeding with the
installation. Consult the Bradford White factory, or
local factory representative, with any problems or
questions regarding this equipment. Experience has
shown that most operating problems are caused by
A = Universal Altitude (0' – 10,000') (0m – 3050m)
(11) Location
I = Indoor
(12) Firing Mode
F = Modulating
Model Designation
1
2
3
4
5
6
7
8
0
9
0
10
11
A
12
I
13
F
14
15
16
17
B
R
H
H
SERIES
H
SIZE
PUMP
USAGE
H
V
FUEL
N
P
ALTITUDE LOCATION FIRING
MODE
REVISION
HEAT
OPTIONS
EXCHANGER
R
H
1
1
2
2
2
6
0
4
0
0
0
0
0
0
0
0
A
I
1
2
X
A
B
F
N
H
F
E
F
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 6
(13) Revision
2 = Second version
(14) Heat Exchanger
appliance should be chosen with regard to the vent
pipe lengths and external plumbing. The unit shall be
installed such that the gas ignition system components
are protected from water (dripping, spraying, rain, etc.)
during operation and service (circulator replacement,
control replacement, etc.). When vented vertically, the
Brute Magnum must be located as close as practical
to a chimney or gas vent. If the vent terminal and/
or combustion air terminal terminate through a wall,
and there is potential for snow accumulation in the
local area, both terminals should be installed at an
appropriate level above grade.
E = Glass-lined steel with copper tubes
F = Glass-lined steel with cupronickel tubes
(15) Control Option Code
X = Standard, meets CSD-1 boiler standard
A = Control Pack A: CSD-1, CA, FM, IL, IRI,
Alarm Bell
B = Control Pack B: CSD-1, CA, FM, IL, LDS, MN
F = Non CSD-1
(16) Pump Options
N = Pump mounted, normal pump (standard)
H = Pump mounted, hard water pump (BRHHV)
The dimensions and requirements that are shown
in Table 1 should be met when choosing the locations
for the appliance:
1.3 Warranty
Bradford White’s Brute Magnum appliances
are covered by a limited warranty. The owner should
fill out the warranty registration card and return it to
Bradford White.
Appliance
Surface
Clearance From
Combustible Material
inches
Suggested Service
Clearance
inches
All warranty claims must be made to an
authorized Bradford White representative or directly
to the factory. Claims must include the serial number
and model (this information can be found on the rating
plate), installation date, and name of the installer.
Shipping costs are not included in the warranty
coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on
the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be
filed with the carrier. The carrier, not the shipper, is
responsible for shortages and damage to the shipment
whether visible or concealed.
Piping Side
Opposite Side
Top
1
18
1
24
36
36
1
1
Back
1
Front
Vent
1
per UL1738 venting
system supplier’s
instructions
Table 1. Clearances.
1.6 Locating Pump-Mounted Water Heater
with Respect to Storage Tank(s)
For best results the Brute Magnum water heater
should be located within 15 feet (4.6m) of the storage
tank(s). The pump is sized for 30 feet (9.1m) of piping.
Water heater pumps are sized for water hardness;
7.6 to 17 grains per gallon for normal water, greater
than 17 grains per gallon for hard water, and 1 to
7.5 grains per gallon for soft water. If the appliance
must be installed with longer piping runs, then larger
diameter pipe or tubing may be able to be used, in
some instances. Consult the factory for assistance.
1.4 Dimensions
The overall dimensions are 34.5" (88cm)
wide, 65.75" (167cm) tall, 55" (140cm) deep. Other
dimensions can be found in Figure 1.
1.5 Locating the Appliance
The Brute Magnum is for indoor installations
only.
The appliance should be located to provide
clearances on all sides for maintenance and inspection.
It should not be located in an area where leakage of
any connections will result in damage to the area
adjacent to the appliance or to lower floors of the
structure.
When such a location is not available, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance.
The appliance is design certified by CSA-
International for installation on combustible flooring;
in basements; in closets, utility rooms or alcoves.
Brute Magnum Boilers or Water Heaters must
never be installed on carpeting. The location for the
1.7 Locating Pump-Mounted Boiler with
Respect to Return/Supply Header
Brute Magnum units must be piped in primary-
secondary fashion because of the internal pump and
mixing system.
For the best results the Brute Magnum Boiler
should be located within 15 feet (4.6m) of the supply
and return headers. The pump is sized for 30 feet
(9.1m) of piping, in most cases, enough for primary-
secondary piping systems.
If the appliance must be installed with longer piping
runs, then larger diameter tubing may be able to be used,
in some instances. Consult the factory for assistance.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 7
“V”
“A”
“W”
“G” Gas Connects.
Control Packages
Vent Outlet
Connection
Air Inlet
Water
Size
Connection
Inlet/ Outlet
Connection
“B”
inches
Std & A
B & E
Nat
B & E
Nat/ LP
LP
NPT
1-1/2”
2’
inches
inches
NPT
2-1/2”
2-1/2”
3”
NPT
NPT
1-1/2’
2”
1200
1600
2000
2400
6
6
6
8
8
8
1’
34-1/4”
34-1/4”
34-1/4”
32”
1-1/2’
1-1/2’
1-1/2”
7
2”
2”
10
3”
2”
2”
Figure 1. Dimensional Drawing.
Size
Intake
Size
Exhaust
Size
Intake
Maximum Run
Exhaust
Maximum Run
1200
1600
2000
2400
6" (15 cm) dia.
8" (20 cm) dia.
8" (20 cm) dia.
8" (20 cm) dia.
6" (15 cm) dia.
6" (15 cm) dia.
7" (18 cm) dia.
10" (25 cm) dia.
50 linear feet with 5 elbows
50 linear feet with 5 elbows
50 linear feet with 5 elbows
50 linear feet with 5 elbows
50 linear feet with 5 elbows
50 linear feet with 5 elbows
50 linear feet with 5 elbows
50 linear feet with 5 elbows
Table 2. Vent / Air Pipe Sizes.
NOTE: When located on the same wall, the Brute
Magnum combustion air intake terminal must be
installed a minimum of 12" (30cm) below the exhaust
vent terminal and separated by a minimum of
36inches (91cm) horizontally.
1.8 Locating Appliance for Correct Vent
Distance From Outside Wall or
Roof Termination
The forced draft combustion air blower in the
appliance has sufficient power to vent properly when
the guidelines in Table 2 are followed.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 8
2.1.2 Intake Combustion Air
Section 2
The combustion air can be taken through the
wall, or through the roof. When taken from the wall,
it must be taken from out-of-doors by means of the
horizontal wall terminal, shown in Table 3. See Table 2
to select the appropriate diameter air pipe. When taken
from the roof, a field-supplied rain cap or an elbow
arrangement must be used to prevent entry of rain
water (see Figure 2).
VENTING AND COMBUSTION AIR
2.1 Combustion Air
Brute Magnum boilers and water heaters must
have provisions for combustion and ventilation
air in accordance with the applicable requirements
for Combustion Air Supply and Ventilation in the
National Fuel Gas Code, ANSI Z223 1; or in Canada,
the Natural Gas and Propane Installation Code, CSA
B149.1. All applicable provisions of local building
codes must also be adhered to.
A Brute Magnum unit can take combustion
air from the space in which it is installed, or the
combustion air can be ducted directly to the unit.
Ventilation air must be provided in either case.
2.1.1 Combustion Air From Room
In the United States, the most common
requirements specify that the space shall communicate
with the outdoors in accordance with method 1 or 2,
which follow. Where ducts are used, they shall be of
the same cross-sectional area as the free area of the
openings to which they connect.
Method 1: Two permanent openings, one
commencing within 12" (300mm) of the top and one
commencing within 12" (300mm) of the bottom, of
the enclosure shall be provided. The openings shall
communicate directly, or by ducts, with the outdoors
or spaces that freely communicate with the outdoors.
When directly communicating with the outdoors, or
when communicating to the outdoors through vertical
ducts, each opening shall have a minimum free area of
1 square inch per 4000 Btu/hr (550 square mm/kW) of
total input rating of all equipment in the enclosure. When
communicating to the outdoors through horizontal ducts,
each opening shall have a minimum free area of not less
than 1square inch per 2000 Btu/hr (1100 square mm/kW)
of total input rating of all equipment in the enclosure.
Method 2: One permanent opening, commencing
within 12" (300mm) of the top of the enclosure, shall
be permitted. The opening shall directly communicate
with the outdoors or shall communicate through a
vertical or horizontal duct to the outdoors or spaces
that directly communicate with the outdoors and shall
have a minimum free area of 1square inch per 3000
Btu/hr (734 square mm/kW) of the total input rating of
all equipment located in the enclosure. This opening
must not be less than the sum of the areas of all vent
connectors in the confined space.
Figure 2. Combustion Air and Vent Through Roof.
Use single-wall galvanized pipe for the
combustion air intake (see Table 4), sized per Section
1.8. Route the intake to the heater as directly as
possible. Seal all joints with tape. Provide adequate
hangers. The unit must not support the weight of the
combustion air intake pipe. Maximum linear pipe
length allowed is 50 feet (15.2m). Up to five elbows
can be used with the 50 feet of pipe. Subtract 10
allowable linear feet for every additional elbow used.
The connection for the intake air pipe is in the
back of the unit. Take the plate off the back to reveal
the collar on the filter box. Run a bead of silicone
around the collar and slide the pipe over the collar.
Secure with sheet metal screws.
Horizontal Combustion
Air Terminal
Horizontal Vent
Terminal
Size
Other methods of introducing combustion and
ventilation air are acceptable, providing they conform
to the requirements in the applicable codes listed
above.
In Canada, consult local building and safety
codes or, in absence of such requirements, follow
CAN/CGA B149.
1200
1600
2000
2400
20260701
20260703
20260703
20260703
D2004500
D2004500
D2004600
D2006200
Table 3. Horizontal Vent and Air Terminals
for Indoor Installations.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 9
A condensate drain is built into the Brute
Term
Pipe
Description
Magnum. A pressure switch monitors the condensate
drain pan, and will trip if the condensate level gets too
high. This will prevent the Brute Magnum from firing
if there is a blockage or overflow.
Single-wall galvanized steel pipe, 24 gauge
minimum (sized per section 1.9)
Joint
Sealing
Permanent duct tape or aluminum tape
Connect a clear plastic tube, minimum 3/8"
diameter, between the drain connection and a floor
drain (or condensate pump if a floor drain is not
accessible).
Insulation Not required, but recommended R5 insulation
for cold installations (consult American Society
of Heating, Refrigerating, and Air Conditioning
Engineers (ASHRAE) handbook
Table 4. Required Combustion Air Piping Material.
Caution
Condensate is mildly acidic, and may harm some
floor drains and/or pipes, particularly those that
are metal. Ensure that the drain, drainpipe,
and anything that will come in contact with the
condensate can withstand the acidity, or neutralize
the condensate before disposal. Damage caused
by failure to install a neutralizer kit or to
adequately treat condensate will not be the
manufacturer’s responsibility.
In addition to air needed for combustion, air
shall also be supplied for ventilation, including all air
required for comfort and proper working conditions
for personnel. The Brute Magnum loses less than 1
percent of its input rating to the room, but other heat
sources may be present.
2.2 Venting
The Brute Magnum is a Category IV appliance
and must be installed with a stainless steel venting
system that complies with the UL 1738 Standard
(see Table 5). It must be installed per this installation
manual and the venting system manufacturer’s
Installation Instructions. The unit’s vent can terminate
through the roof, or through an outside wall. It can be
installed through walls that are from 3" (7.6cm) to 12"
(30cm) in thickness.
A neutralizer kit is available from Bradford
White. The kit includes a condensate pump.
The condensate tray must be primed before starting
the unit. Fill the tray with water through the exhaust
vent connection on the back of the unit. Continue
filling until water flows out of the condensate drain
port. This prevents the flue gases from escaping through
the condensate drain. The condensate drain must be
installed so as to prevent accumulation of condensate.
When a condensate pump is not used, the tubing must
continuously slope downward (except for the trap loop)
toward the drain with no spiraling.
See Table 2 to select the appropriate vent pipe
diameter. The vent pipe must be pitch upward, toward
the vent terminal, so that condensate will run back to
the Brute Magnum, to drain. Route the vent pipe to
the heater as directly as possible. Seal all joints and
provide adequate hangers as required in the venting
system manufacturer’s Installation Instructions.
Horizontal portions of the venting system must be
supported to prevent sagging and may not have any
low sections that could trap condensate. The unit must
not support the weight of the vent pipe. Horizontal
runs must slope upwards not less than ¼ inch per
foot (21mm/m) from the unit to the vent terminal. Up
to five elbows can be used with the 50 feet (15.2m)
of pipe. Subtract 10 allowable linear feet for every
additional elbow used.
Consult local codes for disposal method.
Term
Description
Venting
Sealed stainless steel
system certified to UL1738.
Insulation
Not required, but recommended R5
insulation with protective cover for cold
installations (consult American Society of
Heating, Refrigerating, and Air Conditioning
Engineers (ASHRAE) handbook)
Table 5. Required Venting Material.
IMPORTANT NOTE ABOUT COMMON VENTING:
2.3 Locating Vent & Combustion Air
Terminals
2.3.1 Horizontal Vent Terminal
A single vent that is shared by multiple Brute Magnum
units MUST be engineered by a competent venting
specialist, and involves the selection of draft inducing
equipment, hardware and controls to properly
balance flue gas pressures. Do not common vent
Brute Magnum units unless the vent system
meets this requirement. Brute Magnum units are
never permitted to share a vent with Category I
appliances.
The appropriate side wall vent hood must be
used, and is listed in the installation and operation
manual. The terminal provides a means of installing
the vent piping through the building wall, and must
be located in accordance with ANSI Z223.1/NFPA 54
and applicable local codes. In Canada, the installation
must be in accordance with CSA B149.1 or .2 and
local applicable codes. Consider the following when
installing the terminal:
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 10
U.S. Installations (see note 1)
Canadian Installations (see note 2)
A= Clearance above grade, veranda, porch,
12 inches (30 cm)
12 inches (30 cm)
36 inches (91 cm)
See note 5
deck, or balcony
B= Clearance to window or door that may be
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
See note 4
opened
C= Clearance to permanently closed window
D= Vertical clearance to ventilated soffit located
above the terminal within a horizontal
distance of 2 feet (61cm) from the center line
of the terminal
See note 4
See note 5
E= Clearance to unventilated soffit
F= Clearance to outside corner
G= Clearance to inside corner
See note 4
See note 4
See note 4
See note 5
See note 5
See note 5
H= Clearance to each side of center line
3 feet (91 cm) within a height 15 feet above
the meter/regulator assembly
extended above meter/regulator assembly See note 4
I= Clearance to service regulator vent outlet
See note 4
3 feet (91 cm)
J= Clearance to nonmechanical air supply inlet
to building or the combustion air inlet to
any other appliance
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
36 inches (91 cm)
K= Clearance to a mechanical air supply inlet 3 feet (91 cm) above if within 10 feet (3 m)
6 feet (1.83 m)
horizontally
Vent termination not allowed in this location
Vent termination not allowed in this location for category IV appliances. A vent shall not
L= Clearance above paved sidewalk or paved for category IV appliances. For Category III terminate directly above a sidewalk or paved
driveway located on public property
appliances, vent must terminate at least 7
driveway that is located between two single
feet (2.13m) above the sidewalk or driveway. family dwellings and serves both dwellings.
For Category III appliances that do not violate
the previous condition, vent must terminate at
least 7 feet (2.13m) above the sidewalk or
driveway.
M= Clearance under veranda, porch, deck,
See note 4
12 inches (30 cm) (see note 3)
or balcony
Notes:
1. In accordance with the current ANSI Z223.1 / NFPA 54 National Fuel Gas Code.
2. In accordance with the current CAN/CGA-B149 Installation Codes.
3. Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.
4. For clearances not specified in ANSI Z223.1 / NFPA 54, clearance is in accordance with local installation codes and the requirements of the
gas supplier.
5. For clearances not specified in CAN/CGA-B149, clearance is in accordance with local installation codes and the requirements of the gas
supplier.
*When vent terminal is less than 10 feet (3m) horizontally
from a forced air inlet, the terminal must be at least 3 feet
(0.9m) above the air inlet.
Figure 3. Combustion Air and Vent Through Side Wall.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 11
1. The figure in this addendum shows the
requirements for mechanical vent terminal
clearances for the U.S. and Canada.
2. Vent terminals for condensing appliances or
appliances with condensing vents are not
permitted to terminate above a public walkway,
or over an area where condensate or vapor could
create a nuisance or hazard.
3. Locate the vent terminal so that vent gases cannot
be drawn into air conditioning system inlets.
4. Locate the vent terminal so that vent gases cannot
enter the building through doors, windows,
gravity inlets or other openings. Whenever
possible, locations under windows or near doors
should be avoided.
5. Locate the vent terminal so that it cannot be
blocked by snow. The installer may determine
that a vent terminal must be higher than the
minimum shown in codes, depending upon local
conditions.
6. Locate the terminal so the vent exhaust does
not settle on building surfaces or other nearby
objects. Vent products may damage such
surfaces or objects.
7. If the boiler or water heater uses ducted
combustion air from an intake terminal located
on the same wall, locate the vent terminal at least
3 feet (0.9m) horizontally from the combustion
air terminal, and locate the vent terminal at least
1 foot (0.3m) above the combustion air terminal.
wall horizontal vented gas fueled equipment. It
shall be the responsibility of the property owner
to secure the services of qualified licensed
professionals for the installation of hard-wired
carbon monoxide detectors.
a. In the event that the side wall horizontally
vented gas fueled equipment is installed in a
crawl space or an attic, the hard-wired carbon
monoxide detector with alarm and battery
back-up may be installed on the next adjacent
floor level.
b. In the event that the requirements of this
subdivision cannot be met at the time of
completion of installation, the owner shall
have a period of thirty (30) days to comply
with the above requirements; provided,
however, that during said thirty (30) day
period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE
DETECTORS
Each carbon monoxide detector as required
in accordance with the above provisions shall
comply with NFPA 720 and be ANSI/UL 2034
listed and IAS certified.
3. SIGNAGE
A metal or plastic identification plate shall be
permanently mounted to the exterior of the
building at a minimum height of eight (8) feet
above grade directly in line with the exhaust vent
terminal for the horizontally vented gas fueled
heating appliance or equipment. The sign shall
read, in print size no less than one-half (½) inch
in size, “GAS VENT DIRECTLY BELOW.
KEEP CLEAR OF ALL OBSTRUCTIONS."
From Massachusetts Rules and Regulations
248 CMR 5.08:
(a) For all side wall horizontally vented gas
fueled equipment installed in every dwelling,
building or structure used in whole or in
part for residential purposes, including those
owned or operated by the Commonwealth and
where the side wall exhaust vent termination
is less than seven (7) feet above finished grade
in the area of the venting, including but not
limited to decks and porches, the following
requirements shall be satisfied:
4. INSPECTION.
The state or local gas inspector of the side
wall horizontally vented gas fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon
monoxide detectors and signage installed in
accordance with the provisions of 248 CMR
5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is
exempt from 248 CMR 5.08(2)(a) 1 through 4:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS
At the time of installation of the side wall
horizontal vented gas fueled equipment, the
installing plumber or gasfitter shall observe that
a hard-wired carbon monoxide detector with
an alarm and battery back-up is installed on the
floor level where the gas equipment is to be
installed. In addition, the installing plumber or
gasfitter shall observe that a battery operated or
hard-wired carbon monoxide detector with an
alarm is installed on each additional level of the
dwelling, building or structure served by the side
1. The equipment listed in Chapter 10 entitled
“Equipment Not Required To Be Vented” in the
most current edition of NFPA 54 as adopted by
the Board; and
2. Product Approved side wall horizontal vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure
used in whole or in part for residential purposes.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 12
(c) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM
PROVIDED. When the manufacturer of
Product Approved side wall horizontally
vented gas equipment provides a venting
system design or venting system components
with the equipment, the instructions provided
by the manufacturer for installation of the
equipment and the venting system shall
include:
side wall. Consider the following when installing the
terminal:
1. Do not locate the air inlet terminal near a source
of corrosive chemical fumes (e.g., cleaning fluid,
chlorine compounds, etc.)
2. Locate the terminal so that it will not be subject
to damage by accident or vandalism. It must be at
least 7 feet (2.1m) above a public walkway.
3. Locate the combustion air terminal so that it
cannot be blocked by snow. The National Fuel
Gas Code requires that it be at least 12 inches
(30cm) above grade, but the installer may
determine it should be higher, depending upon
local conditions.
4. If the Brute Magnum is side-wall vented to the
same wall, locate the vent terminal at least 3
feet (0.9m) horizontally from the combustion air
terminal, and locate the vent terminal at least 1
foot (0.3m) above the combustion air terminal
(see Figure 3).
1. Detailed instructions for the installation of the
venting system design or the venting system
components; and
2. A complete parts list for the venting system
design or venting system.
(d) MANUFACTURER REQUIREMENTS –
GAS EQUIPMENT VENTING SYSTEM
NOT PROVIDED. When the manufacturer
of a Product Approved side wall horizontally
vented gas fueled equipment does not
provide the parts for venting the fuel gases,
but identifies “special venting systems”, the
following requirements shall be satisfied by
the manufacturer:
2.3.3 Vertical Vent Terminal
When the unit is vented through the roof, the
vent must extend at least 3 feet (0.9m) above the point
at which it penetrates the roof. It must extend at least
2 feet (0.6m) higher than any portion of a building
within a horizontal distance of 10 feet (3.0m), and high
enough above the roof line to prevent blockage from
snow. When the combustion air is taken from the roof,
the combustion air must terminate at least 12" (30cm)
below the vent terminal (see Figure 2).
1. The identification of each “special venting
system” shall include either the listing of the
website, phone number or manufacturer’s address
where the venting system installation instructions
can be obtained; and
2.3.4 Vertical Combustion Air Terminal
When combustion air is taken from the roof, a
field-supplied rain cap or an elbow arrangement must
be used to prevent entry of rain water (see Figure 2).
The opening on the end of the terminal must be at least
12" (30cm) above the point at which it penetrates the
roof, and high enough above the roof line to prevent
blockage from snow. When the vent terminates on the
roof, the combustion air must terminate at least 12"
(30cm) below the vent terminal.
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions
provided with that system shall include a parts
list and detailed installation instructions.
(e) A copy of all installation instructions for the
Product Approved side wall horizontally
vented gas fueled equipment, and all the
venting instructions, parts lists, and/or design
instructions for the venting system shall
remain with the appliance or equipment at the
completion of the installation.
2.4 Common Vent Test — Boilers
NOTE: This section does not describe a method for
common venting Brute Magnum units. It describes
what must be done when a unit is removed from a
common vent system. Brute Magnum units require
special vent systems and fan for common vent.
Contact the factory if you have questions about
common venting Brute Magnum units.
Contact factory with questions about venting
system installation.
When an existing boiler is removed from a
common venting system, the common venting system
is likely to be too large for proper venting of the
appliances remaining connected to it.
2.3.2 Side Wall Combustion Air Terminal
The side wall combustion air terminal (see Table
4) must be used when the heater takes air from a
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 13
At the time of removal of an existing boiler, the
as determined using the appropriate tables
following steps shall be followed with each appliance
remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system are
not in operation.
and guidelines in the National Fuel Gas Code,
ANSI Z223.1 NFPA 54 and/or CSA B149.1,
Installation Codes.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion and
other deficiencies which could cause an unsafe
condition.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the
common venting system are located and other
spaces of the building. Turn on clothes dryers
and any appliance not connected to the common
venting system. Turn on any exhaust fans, such
as range hoods and bathroom exhausts, so they
will operate at maximum speed. Do not operate a
summer exhaust fan. Close fireplace dampers.
4. Place in operation the appliance being inspected.
Follow the lighting instructions. Adjust thermostat
so appliance will operate continuously.
Section 3
GAS SUPPLY AND PIPING
3.1 Gas Supply and Piping
Gas piping should be supported by suitable
hangers or floor stands, not the appliance.
Review the following instructions before
proceeding with the installation.
1. Verify that the appliance is fitted for the
proper type of gas by checking the rating plate.
Appliances are normally equipped to operate at
elevations up to 2000 feet (610m). However,
the appliance will function properly without the
use of high altitude modification at elevations
up to 10,000 feet (3050 m).
2. The maximum inlet gas pressure must not
exceed 13" W.C. (3.2kPa). The minimum
inlet natural gas pressure is 4" W.C. (1.0kPa)
and minimum inlet propane gas pressure is 6"
(1.5kPa).
3. Refer to Table 6, size supply.
4. Run gas supply line in accordance with all
applicable codes.
5. Test for spillage at the draft hood relief opening
after 5 minutes of main burner operation. Use
the flame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance
remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans,
fireplace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so that the installation
conforms to the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Installation
Codes. When resizing any portion of the common
venting system, the common venting system
should be resized to approach the minimum size
Note: If you have a boiler/water heater with
a normally open vent valve, install a vent line
from the vent valve to an outside location
as required by your installation code or IRI
requirement. Do not remove 3/4 inch pipe
plug from the vent valve if venting from the
normally open vent valve is not required by
your installation code.
5. Locate and install manual shutoff valves in
accordance with state and local requirements.
6. A sediment trap must be provided upstream of
the gas controls.
Distance from Gas Meter or Last Stage Regulator
50-100 feet 15-31m 100-200 feet 31-61m
Size and
Gas Type
0-50 feet
2"
1-1/2"
2-1/2"
2"
0-15m
5.1cm
3.8cm
6.4cm
5.1cm
7.6cm
6.4cm
6.4cm
5.1cm
200-300 feet
61-91m
7.6cm
6.4cm
7.6cm
6.4cm
8.9cm
7.6cm
8.9cm
7.6cm
1200 natural
1200 propane
1600 natural
1600 propane
2000 natural
2000 propane
2400 natural
2400 propane
2-1/2"
2"
6.4cm
5.1cm
6.4cm
5.1cm
7.6cm
6.4cm
7.6cm
6.4cm
2-1/2"
2"
6.4cm
5.1cm
7.6cm
6.4cm
7.6cm
6.4cm
7.6cm
6.4cm
3"
2-1/2"
3"
2-1/2"
3-1/2"
3"
2-1/2"
2"
3"
3"
2-1/2"
3"
3"
2-1/2"
2-1/2"
2"
2-1/2"
3"
2-1/2"
3"
3-1/2"
3"
2-1/2"
2-1/2"
Notes:
1. These figures are based on 1/2" 0.12kPa water column pressure drop.
2. Check supply pressure and local code requirements before proceeding with work.
3. Pipe fittings must be considered when determining gas pipe sizing.
Table 6. Gas Piping Sizes.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 14
7. All threaded joints should be coated with
piping compound resistant to action of liquefied
petroleum gas.
to a drain or in a manner to prevent injury in the event
of pressure relief. Install an air purger, an air vent,
a diaphragm-type expansion tank, and a hydronic
flow check in the system supply loop. Minimum fill
pressure must be 12psig (82.7kPa). Install shutoff
valves where required by code.
8. The appliance and its individual shutoff valve
must be disconnected from the gas supply piping
during any pressure testing of that system at test
pressures in excess of 1/2 PSIG (3.45kpa).
9. The unit must be isolated from the gas supply
system by closing its individual manual shutoff
valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 PSIG (3.45kpa).
Suggested piping diagrams are shown in Figures
4, 5, and 6. These diagrams are meant only as a guide.
Components required by local codes must be properly
installed. The Brute Magnum boiler’s efficiency
is higher with lower return water temperatures.
Therefore, to get the most of low return temperature
with multiple boilers, pipe as shown in Figure 4.
The Brute Magnum boiler has an internal mixing
system that ensures that the condensation does not
occur on the finned copper heat exchanger, with
boiler return temperature down to 50°F (10°C). This
system, that consists of automatically actuated
and linked valves, is set up at the factory, and is
non-adjustable. The return water goes through the
stainless steel heat exchanger, then to the mixing
system (see Figure 7).
10. The appliance and its gas connection must be
leak tested before placing it in operation.
11. Purge all air from gas lines.
WARNING
Open flame can cause gas to ignite and result in
property damage, severe injury, or loss of life.
NOTE: The Brute Magnum appliance and all other
gas appliances sharing the gas supply line must be
firing at maximum capacity to properly measure the
inlet supply pressure. The pressure can be measured
at the supply pressure port on the gas valve. Low
gas pressure could be an indication of an undersized
gas meter, undersized gas supply lines and/or an
obstructed gas supply line. A bleed line from the
diaphragm-type automatic valve shall be vented per
local code requirements. Brute Magnum units are
equipped with low and high gas pressure switches that
are integrally vent limited. These types of devices do
not require venting to atmosphere.
If the water at the inlet of the copper heat
exchanger is less than 140°F (60°C), water from the
outlet of the copper heat exchanger will be directed
back to the inlet of the copper heat exchanger, and will
mix to bring the inlet water up to 140°F (60°C). Once
through the copper heat exchanger, the water picks up
another 20-25°F (11-14°C) (when at high fire), and
it leaves the boiler at 160-165°F (71-74°C). This hot
water is then sent to the system.
If the water at the inlet of the copper heat exchanger
is 140°F (60°C), or higher, the water will be allowed to
flow through the copper heat exchanger and directly to the
outlet of the Brute Magnum, and there will be a 20-25°F
(11-14°C) temperature rise between the inlet and outlet of
the unit, when the unit is at high fire.
The pump in the boiler is sized for the boiler’s
heat exchangers, the internal mixing system, and 30
feet of full-sized piping, with a normal number of
fittings taken into consideration. The piping must be
primary/secondary, ensuring that the boiler’s pump is
only used for the boiler, and that the system pump(s)
do not interfere with the Brute Magnum pump or
mixing system.
Section 4A
WATER CONNECTIONS —
BRUTE MAGNUM BOILER
4A.1 Heating System Piping:
Hot Supply Connections — Boiler
The minimum inlet water temperature for the
Brute Magnum is 50°F (10°C) to avoid condensing
on the copper coils.
NOTE: This appliance must be installed in a closed
pressure system with a minimum of 12 psi (82.7kPa)
static pressure at the boiler.
Hot water piping should be supported by suitable
hangers or floor stands. Do not support piping with
this appliance. Due to expansion and contraction of
copper pipe, consideration should be given to the type
of hangers used. Rigid hangers may transmit noise
through the system resulting from the piping sliding in
the hangers. It is recommended that padding be used
when rigid hangers are installed. Maintain 1" (2.5cm)
clearance to combustibles for hot water pipes.
4A.2 Cold Water Make-Up — Boiler
1. Connect the cold water supply to the inlet
connection of an automatic fill valve.
2. Install a suitable back flow preventer between the
automatic fill valve and the cold water supply.
3. Install shut off valves where required.
NOTE: The boiler, when used in connection with a
refrigeration system, must be installed so the chilled
Pipe the discharge of the relief valve (full size)
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 15
medium is piped in parallel with the boiler with
appropriate valves to prevent the chilled medium from
entering the boiler.
The boiler piping system of a hot water heating
boiler connected to heating coils located in air
handling appliances where they may be exposed to
refrigerated air circulation must be equipped with flow
control valves or other automatic means to prevent
gravity circulation of the boiler water during the
cooling cycle.
A boiler installed above radiation level, or as
required by the authority having jurisdiction, must be
provided with a low water cutoff device either as a part
of the boiler or at the time of boiler installation.
Section 4B
WATER CONNECTIONS —
BRUTE MAGNUM WATER HEATER
4B.1 Water System Piping —
Water Heater
Hot water piping should be supported by
suitable hangers or floor stands. Do not support piping
with this appliance. Due to expansion and contraction
of copper pipe, consideration should be given to the
type of hangers used. Rigid hangers may transmit
noise through the system resulting from the piping
sliding in the hangers. It is recommended that padding
be used when rigid hangers are installed.
4A.3 Freeze Protection – Boiler
The Brute Magnum can be used with several
different types of readily available storage tanks. A
pump draws water from the storage tank and pumps
the water through the heater and back into the tank.
Pump-mounted units have a circulating pump built
into the water heater.
Pipe the outlet from the heater’s relief valve
such that any discharge from the relief valve will be
conducted to a suitable place for disposal when relief
occurs. Do not reduce line size or install any valves in
this line. The line must be installed to allow complete
drainage of both the valve and the line.
Suggested piping diagrams are shown in Figures
8, 9, 10, and 11. These diagrams are meant only as a
guide. Components required by local codes must be
properly installed.
The minimum inlet water temperature for the
Brute Magnum is 50°F (10°C) to avoid condensing
on the copper coils.
Brute Magnum units are not designed to be
placed outdoors, due to the potential for condensate to
freeze in the unit.
Proper precautions for freeze protection are
recommended for boiler installations in areas where
the danger of freezing exists.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a boiler from firing. Any time a
boiler is subjected to freezing conditions, and the
boiler is not able to fire, and/or the water is not able
to circulate, there is a risk of freezing in the boiler
or in the pipes in the system. When water freezes,
it expands. This can result in bursting of pipes in the
system, or damage to the boiler, which could result in
leaking or flooding conditions.
Do not use automotive anti-freeze. Maintaining
a mixture of minimum 50% water and maximum
50% properly inhibited HVAC glycol, which contains
an antifoamant, is the preferred method of freeze
protection for Brute Magnum boilers. The percentage
of glycol used in the Brute Magnum boiler must
not exceed 50%. Typically, this mixture will
serve as burst protection for temperatures down to
approximately –35°F (-30°C).
IMPORTANT NOTES: Different glycol products
may provide varying degrees of protection. Glycol
products must be maintained properly in a heating
system, or they may become ineffective. Consult
the glycol specifications, or the glycol manufacturer,
for information about specific products, maintenance
of solutions, and set up according to your particular
conditions.
4B.2 Hot Water Supply Piping —
Water Heater
Follow the tank manufacturer’s guidelines for
completion of the hot water system connections.
NOTE: A listed temperature and pressure relief
valve listed as complying with the Standard for
Relief Valves and Automatic Gas Shutoff Devices
for Hot Water Supply Systems, 1). ANSI Z21.22
latest edition, or 2). CSA 4.4, of suitable discharge
capacity must be installed in the separate storage
tank system.
If the Brute Magnum water heater is installed in
a closed water supply system, such as one having a
backflow preventer in the cold water supply line, the
relief valve may discharge periodically, due to thermal
expansion. Means (such as a properly-sized expansion
tank) shall be provided to control thermal expansion.
Contact the water supplier or local plumbing inspector
on how to control this situation.
For installations where temperatures are
expected to fall below 15°F inside the boiler cabinet,
the actuating gas valve must be equipped with a gas
valve heater, part number R2010100. Note that some
gas trains such as the IRI option may have double
actuators, and may require 2 gas valve heaters.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 16
Figure 4. Hydronic Piping - Multiple Boilers.
tube erosion. For extremely soft or hard water, cupro-
nickel tubes are available. Contact a Bradford White
Representative if you have questions or concerns about
water quality.
The Brute Magnum water heater has an internal
mixing system that ensures that the condensation does
not occur on the finned copper heat exchanger, with
heater return temperature down to 50°F (10°C). This
system, that consists of automatically actuated
and linked valves, is set up at the factory, and is
non-adjustable. The return water goes through the
stainless steel heat exchanger, then to the mixing
system. (see Figure 7).
4B.3 Water Flow Requirements —
Water Heater
In a water heating application (an open system),
new water is constantly being introduced. With the
new water comes a fresh supply of minerals that can
be deposited on the unit’s heat exchanger. This is
commonly known as scaling. The amount of minerals
will depend upon the hardness of the water. Water can
also be aggressive, and can erode metals, including
copper, if the water is moved too quickly. Pump sizing
for the Brute Magnum water heater is based upon the
hardness of the water. The water flow is kept high
enough to prevent scaling, but low enough to prevent
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 17
Figure 5. Hydronic Piping — Multiple Boilers (Alternate).
If the water at the inlet of the copper heat
exchanger is less than 140°F (60°C), water from the
outlet of the copper heat exchanger will be directed
back to the inlet of the copper heat exchanger, and will
mix to bring the inlet water up to 140°F (60°C). Once
through the copper heat exchanger, the water picks up
another 20-25°F (11-14°C) (when at high fire), and
it leaves the boiler at 160-165°F (71-74°C). This hot
water is then sent to the system.
directly to the outlet of the Brute Magnum, and there
will be a 20-25°F (11-14°C) temperature rise between
the inlet and outlet of the unit, when the unit is at high
fire.
The pump in the heater is sized for the heater’s
heat exchangers, the internal mixing system, and 30
feet of full-sized piping, with a normal number of
fittings taken into consideration.
The minimum inlet water temperature for the
Brute Magnum is 50°F (10°C) to avoid condensing
on the copper coils.
If the water at the inlet of the copper heat
exchanger is 140°F (60°C), or higher, the water will be
allowed to flow through the copper heat exchanger and
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 18
Figure 6. Hydronic Piping — One Boiler, Multi-Temperature System.
water used for space heating.
4B.4 Combined Water (potable) Heating
and Space Heating
This water heater when used to supply potable
water shall not be connected to any heating system
or component(s) previously used with a non-potable
water heating appliance.
NOTE: These systems are not allowed in the
Commonwealth of Massachusetts.
Piping and components connected to this water
heater for the space heating application shall be
suitable for use with potable water.
When the system requires water for heating at
temperatures higher than required for other uses,
an anti-scald mixing or tempering valve shall be
installed to temper the water for those uses in order
to reduce scald hazard potential.
Toxic chemicals, such as used for boiler
treatment, shall not be introduced into the potable
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 19
4B.5 Freeze Protection – Water Heater
Brute Magnum heaters are not designed to be
placed outdoors, due to the potential for condensate to
freeze in the unit.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from firing. Any time a
heater is subjected to freezing conditions, and the
heater is not able to fire, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or flooding conditions.
For installations where temperatures are
expected to fall below 15°F inside the boiler cabinet,
the actuating gas valve must be equipped with a gas
valve heater, part number R2010100. Note that some
gas trains such as the IRI option may have double
actuators, and may require two gas valve heaters.
Figure 7. Internal Piping Schematic.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 20
Figure 8. Water Heater Piping — One Heater, One Tank.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 21
Figure 9. Water Heater Piping — Multiple Heaters, One Tank.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 22
Figure 10. Water Heater Piping — One Heater, Multiple Tanks.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 23
Figure 11. Water Heater Piping — Multiple Heaters, Multiple Tanks.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 24
Section 5
ELECTRICAL CONNECTIONS
WARNING
The appliance must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the National
Electrical Code, ANSI/NFPA 70, in the U.S. and
with latest edition of CSA C22.1 Canadian Electrical
Code, Part 1, in Canada. Do not rely on the gas
or water piping to ground the metal parts of the
boiler. Plastic pipe or dielectric unions may isolate
the boiler electrically. Service and maintenance
personnel, who work on or around the boiler, may
be standing on wet floors and could be electrocuted
by an ungrounded boiler. Electrocution can result in
severe injury or death.
Figure 12. Temperature Control.
Single pole switches, including those of safety
controls and protective devices must not be wired in a
grounded line.
measures temperature on the boiler inlet, sensing
return water temperature. Set the temperature control
for the desired return temperature. If the return water
temperature is less than 140°F (60°C), internal mixing
will keep the outlet temperature at 160-165°F (71-
74°C). If the return temperature is 140°F (60°C) or
higher, the outlet temperature of the boiler will be the
return temperature plus 20-25°F (11-14°C) when the
Brute Magnum is at high firing rate.
The manual reset high limit is on the outlet of
the Brute Magnum. Set the manual reset high limit at
about 20°F (11°C) higher than the highest expected
outlet temperature, to avoid nuisance lockouts.
All electrical connections are made in the field
wiring box that is located inside the appliance.
NOTE: All internal electrical components have been
prewired. No attempt should be made to connect
electrical wires to any other location except the wiring
box.
Wiring connections are shown in Figures 17
through24.
5.1 Main Power
Connect a properly sized and fused, 120-volt
supply to the main power switch (hot leg is connected
directly to switch). Neutral leg is connected directly to
the white wire. Ground wire can be connected to the
grounding screw in the box or on the switch.
5.4
Temperature Control – Water Heater
5.4.1 Remote Water Heater
5.2 Pump Connections
Temperature Control
The pump time delay relay will call the pump
to be energized upon a call for heat, and will keep the
pump energized for a delay period after the call for
heat has ended. The delay period is adjustable from
0.1 to 10 minutes.
The Brute Magnum water heater can be used
with a field-supplied tank aquastat, sequencing control,
or other temperature control device, which will call
the unit for heat when the temperature goes below the
controller’s setpoint. For the most efficient setting, set
the tank temperature at the lowest possible setting for
adequate hot water in the application.
Brute Magnum units have pumps that are wired
at the factory to the pump time delay system. It is
necessary to wire the pump to a separate 115V or
230V single phase circuit, per the wiring diagrams in
Figures 17 through 20.
Caution
If the tank temperature control is set too high, a
5.3 Temperature Control — Boiler
Connect boiler field interlock wires to isolated
contacts on zone valves, circulator relays, sequencing
controls (multiple boiler applications) or other
temperature controlling devices.
potential for hot water scalding may exist.
After a setting has been chosen for the tank
temperature control, set the heater temperature control
10°F (6°C) higher. The Brute Magnum temperature
control measures temperature on the heater inlet,
sensing return water temperature. If the return water
The Brute Magnum temperature control
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 25
temperature is less than 140°F (60°C), internal mixing
will keep the outlet temperature at 160-165°F (71-
74°C), and this will mix with the tank temperature
to maintain a lower temperature in the tank. If the
return temperature is 140°F (60°C) or higher, the
outlet temperature of the heater will be the return
temperature plus 20-25°F (11-14°C) when the Brute
Magnum is at high firing rate.
The manual reset high limit is on the outlet of
the Brute Magnum. Set the manual reset high limit at
about 20°F (11°C) higher than the highest expected
outlet temperature, to avoid nuisance lockouts
The offset determines where the throttling range
begins.
The throttling range is the temperature range
through which the unit will modulate from minimum
to maximum firing rate.
Important Note: These control parameters work
together. Therefore, setting one parameter may have
an affect on another. Figures 14, 15 and 16 show the
relationships between these settings. Figure 14 follows
the examples that are shown in the following sections,
and Figures 15 and 16 are examples of how the
parameters can interfere with each other.
5.4.2 Internal Water Heater
5.5.1 Temperature Setpoint
Temperature Control
The temperature setpoint is the point at which the
temperature control relay will be de-energized and the
unit’s call for heat will end. The temperature setpoint
is adjusted with the setpoint dial on the A350 control
(see Figure 13). The temperature control’s sensor is in
the inlet of the unit.
When an external control is not used, the
circulator between the heater and the storage tank
must run continuously, so that the heater’s temperature
control can detect and control the water temperature
in the storage tank. The Brute Magnum water
heater’s temperature control is adjusted to its lowest
temperature position when shipped from the factory.
This is the preferred starting point for setting the
temperature control.
The Brute Magnum temperature control measures
temperature on the heater inlet, sensing return water
temperature. If the return water temperature is less
than 140°F (60°C), internal mixing will keep the outlet
temperature at 160-165°F (71-74°C), and this will
mix with the tank temperature to maintain a lower
temperature in the tank. If the return temperature is
140°F (60°C) or higher, the outlet temperature of the
heater will be the return temperature plus 20-25°F (11-
14°C) when the Brute Magnum is at high firing rate.
The manual reset high limit is on the outlet of
the Brute Magnum. Set the manual reset high limit at
about 20°F (11°C) higher than the highest expected
outlet temperature, to avoid nuisance lockouts.
Caution
Note: Jumper must be in “Reverse Acting” mode, or unit will not
operate properly.
Should overheating occur or the gas supply fail to
shut off, turn off the manual gas control valve to the
appliance.
Figure 13. Proportional Control.
5.5.2 Differential Setting
5.5 Temperature Control Features
The Brute Magnum temperature control is
versatile and will allow the user to better match the
modulating control to the application. Settings that
can be changed are temperature setpoint, differential,
offset, throttling range, and minimum output.
The temperature setpoint is the setting at which
the unit will shut off, having satisfied the controller’s
call for heat.
The differential is the difference in temperature
settings when the temperature control’s relay is
energized and de-energized. For instance, if the
temperature setpoint is 120°F (49°C) and the
differential is 20°F (11°C), the temperature control
will call the unit to energize at 100°F (38°C). (The
differential is the setpoint minus the differential
setting) The call for heat will end when the unit
reaches its setpoint of 120°F (49°C). The Brute
Magnum differential is adjustable from 1°F to 30°F
(1°C to 17°C). In general, the differential setting for a
water heater system will be low, so that when a storage
The differential determines how far the
temperature in the Brute Magnum can fall before
energizing again.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 26
tank is drawing down, the heater will react to sustain
a minimum tank temperature. Boilers generally have
higher differentials than water heaters, to minimize
short cycling (see throttling range). The differential
is set by removing the cover of the A350 control
and adjusting the potentiometer marked “DIFF” (see
Figure 13).
through which the unit will modulate. This will tell
the controller how fast to respond to a change in
temperature. A small throttling range keeps the unit
in high fire more, and quickens the response of the
system. A larger throttling range allows the Brute
Magnum to spread its modulating range over a larger
temperature range.
Example, Imperial units: Using a temperature
setpoint of 120°F, with a 20°F differential, a 5°F
offset, and a throttling range of 10°F, the unit will
come on at 100°F and shut off at 120°F. The offset
will set the top of the throttling range 5°F under the
setpoint, which is 115°F in this example. Therefore,
the throttling range will cause the Brute Magnum to
modulate between 25% and 100% of full fire between
115°F and 105°F. Between 115°F and 120°F, the unit
will remain at low fire. Between 100°F and 105°F, the
unit will be at full fire.
5.5.3 Offset
The offset determines the temperature below the
controller’s setpoint where the throttling range begins.
It offsets the throttling range.
For instance, if the setpoint is 120°F (49°C) and
the offset is 5°F (3°C), then the unit’s throttling range
will begin at 115°F (46°C). Between 115°F (46°C) and
120°F (49°C), the Brute Magnum will be in low fire.
The offset can be adjusted between 0°F and 30°F
(0°C and 17°C) by removing the cover of the S350P
control and adjusting the Offset dial (see Figure 14).
Example, Metric units: Using a temperature
setpoint of 49°C, with a 11°C differential, a 3°C offset,
and a throttling range of 5°C, the unit will come on at
38°C and shut off at 49°C. The offset will set the top
of the throttling range 3°C under the setpoint, which is
46°C in this example. Therefore, the throttling range
will cause the Brute Magnum to modulate between
5.5.4 Throttling Range
The throttling range allows the Brute Magnum
to match the BTU demands of varying systems, by
allowing the user to choose the temperature range
Figure 14. Control Parameter Graph.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 27
Figure 15. Control Parameter Graph.
25% and 100% of full fire between 46°C and 49°C.
Between 46°C and 49°C, the unit will remain at low
fire. Between 38°C and 41°C, the unit will be at full
fire.
5.5.6 Integration Constant
The proportional control used on the Brute
Magnum has internal circuitry that helps to minimize
overshoot that can sometimes be associated with
proportional plus integral (PI) controls. There
are three field-selectable integration constants
(slow, medium and fast), and an off position on the
proportional control, which are selected with the
dipswitches on the control (see Figure 14). In most
cases, this setting will not need to be changed
Off: Switch 1 to ON position and all others to
OFF. Setting the control to the “Off” position puts the
control into proportional only operation. This is not a
recommended setting for the Brute Magnum.
Slow: Switch 2 to ON position and all others
to OFF. This is the slowest integration constant. It
allows the Brute Magnum the most time to reach its
setpoint. In most cases, this is too slow for Brute
Magnum installations.
The throttling range is adjustable between 2°F
and 30°F (1°C to 17°C). The range can be set by
removing the cover of the S350P control and adjusting
the “THROT RANGE” dial (see Figure 14).
5.5.5 Minimum Output Setting
The minimum output setting of the controller is
0% of full fire. However, the minimum output of the
Brute Magnum is limited to 25% of full fire by the
fan speed controller, to ensure proper operation of the
Brute Magnum. If a minimum desired output is higher
than 25%, the setting can be adjusted up by removing
the cover of the S350P control and adjusting the Min
Output dial (see Figure 14). Turning the dial clockwise
increases the minimum output. In most cases, this
setting should be left as shipped from the factory.
Medium: Switch 3 to ON position and all others
to OFF. The integration constant is set to “Medium”
at the factory, and in most cases, will not need to be
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 28
Figure 16. Control Parameter Possible Interference.
changed. This setting will be the best suited to most
Brute Magnum installations.
another 20-25°F (11-14°C) (when at high fire), and
it leaves the boiler at 160-165°F (71-74°C). This hot
water is then sent to the system.
Fast: Switch 4 to ON position and all others
to OFF. If the rate of system recovery to setpoint is
sluggish with the control set to medium, the “Fast”
setting may be an improvement. The “Fast” setting
will only be used when the rate of change at the sensor
is very rapid. In most cases, this setting is too fast for
the Brute Magnum.
If the water at the inlet of the copper heat
exchanger is 140°F (60°C), or higher, the water will be
allowed to flow through the copper heat exchanger and
directly to the outlet of the Brute Magnum, and there
will be a 20-25°F (11-14°C) temperature rise between
the inlet and outlet of the unit, when the unit is at high
fire.
The by-pass mixing control displays the mixed
water temperature, which is the temperature of the
water that is sent to the copper heat exchanger. This
temperature setting is locked and cannot be changed in
the field.
5.6 Mixing System and Control
The Brute Magnum has an internal mixing
system that ensures that the condensation does not
occur on the finned copper heat exchanger, with
boiler return temperature down to 70°F (21°C). This
system, that consists of automatically actuated
and linked valves, is set up at the factory, and is
non-adjustable. The return water goes through the
stainless steel heat exchanger, then to the mixing
system (see Figure 7).
By pressing and holding the two buttons on the
left of the mixing control for at least 3 seconds, the
user will access two available menus.
The first menu allows selection of the temperature
units. Pressing the two left buttons for at least 3 seconds
displays “Uni” on the screen (for units). Then “°F” is
displayed. Press the up or down arrow on the control to
change from °F to °C, or °C to °F. When the preferred
selection is displayed, press the enter (bottom left) button.
The control will then display “Add” for the second
menu. If no more buttons are pushed, the control will
automatically return to the temperature display mode.
If the water at the inlet of the copper heat
exchanger is less than 140°F (60°C), water from the
outlet of the copper heat exchanger will be directed
back to the inlet of the copper heat exchanger, and will
mix to bring the inlet water up to 140°F (60°C). Once
through the copper heat exchanger, the water picks up
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 29
The second menu “Add” has to do with the N2
located to the right of, and behind the front panel. The
terminal strip is labeled “0-10VDC +” and 0-10VDC
–” to indicate which terminal received the hot signal
(+) and which terminal receives the common signal (-)
from the controller.
address. Pressing enter when “Add” is displayed will
display “255”, which stands for 255 unique addresses.
The up and down arrows change this value, and enter
saves the value if it is changed.
Changing the “Add” value will have no affect
on the Brute Magnum, unless a communications
card as been built onto the unit. If a Brute
Magnum unit has been ordered with an optional
communications card, more menus will be active,
and the unit will come with separate instructions.
The Brute Magnum unit will modulate between
2.23V and 10V (for 25% and 100%, respectively).
Anything less than 2.23 volts will result in 25% of full
fire.
For the external control to modulate the Brute
Magnum, the selector switch on the front panel must
be in the “External Control” position.
Important Note: DO NOT MAKE/BREAK Brute
Magnum LINE VOLTAGE TO SIGNAL CALL FOR
HEAT. A “call for heat / end call for heat” MUST be
connected to the field interlock terminals. The Brute
Magnum does not recognize 0 volts as a signal to shut
off. If the call for heat is not connected between the
field interlock terminals, the Brute Magnum will remain
in low fire when it sees 0 volts as a modulating signal.
5.7 External Control Connections
Brute Magnum units are built with a selector
switch and a terminal strip to allow the Brute Magnum
to receive a
0-10VDC signal from an
external controller (such as a building automation
system or multiple boiler control).
When the selector switch is in the “Brute
Magnum Control” position, the Brute Magnum will be
modulated by the unit’s factory-mounted modulating
control.
Caution
When the switch is in the “External Control”
position, the unit look for a 0-10VDC signal from an
external (field-supplied) controller.
Brute Magnum supply voltage must not be
disengaged, except for service or isolation, or
unless otherwise instructed by procedures outlined
in this manual. To signal a call for heat, use the 24V
field-interlock, as shown in the wiring diagram(s).
To interlock the external boiler control with
the Brute Magnum, the call for heat signal MUST
be connected to the field interlock terminal strip on
the Brute Magnum (shown in Figure 29). Be sure to
remove the factory-installed jumper between the field
interlock terminals. The 0-10VDC modulating signal
MUST be connected to external control terminal strip,
Some Brute Magnum components are designed
to have constant voltage during normal operation.
If Brute Magnum supply voltage is toggled as a
call for heat signal, premature failure of these
components may result.
5.8 Wiring Diagrams
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation. Verify proper operation after servicing.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 30
Figure 17. Wiring Diagram, Size 1200, Standard and Codes A and F.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 31
Figure 18. Wiring Diagram, Sizes 1600, 2000 and 2400, Standard and Codes A and F.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 32
Figure 19. Wiring Diagram, Size 1200, Code B.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 33
Figure 20. Wiring Diagram, Sizes 1600, 2000 and 2400, Code B.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 34
Figure 22. Wiring Schematic, Models 1600, 2000 and
2400, Standard and Codes A and F.
Figure 21. Wiring Schematic, Model 1200,
Standard and Codes A and F.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 35
Figure 24. Wiring Schematic, Models 1600, 2000
and 2400, Code B.
Figure 23. Wiring Schematic, Model 1200, Code B.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 36
14. Refer to local codes and the make-up water
valve manufacturer’s instructions as to whether
the make-up water valve should be left open or
closed.
Section 6
OPERATING INSTRUCTIONS
6.1 Filling the Boiler System
1. Ensure the system is fully connected. Close all
bleeding devices and open make-up water valve.
Allow system to fill slowly.
2. If make-up water pump is employed, adjust
pressure switch on pumping system to provide
a minimum of 12 psi (81.8 kPa) at the highest
point in the heating loop.
3. If a water pressure regulator is provided on the
make-up water line, adjust the pressure regulator
to provide at least 12 psi (81.8 kPa) at the highest
point in the heating loop.
15. After placing the unit in operation, the ignition
system safety shutoff device must be tested. First,
shut off the manual gas valve, and call the unit
for heat. Main gas terminals will be energized,
attempting to light, for seven (7) seconds, and
then will de-energize. The unit will go into
lockout mode. Second, turn the power off, press
the manual reset button on the ignition control,
open the manual gas valve and allow the unit
to light. While the unit is operating, close the
manual gas valve and ensure that power to the
main gas valve has been cut.
16. Within three (3) days of start-up, recheck all air
bleeders and the expansion tank as described in
Steps 4 and 8 above.
4. Open bleeding devices on all radiation units
at the high points in the piping throughout
the system, unless automatic air bleeders are
provided at such points.
Important: The installer is responsible for
identifying to the owner/operator the location of all
emergency shutoff devices.
Note that there is an air bleed (coin vent)
located in the back of the unit, on top of the
flue collector, to bleed air from the secondary
(stainless steel) heat exchanger.
WARNING
5. Run system circulating pump for a minimum of
Do not use this appliance if any part has been
under water. Immediately call a qualified service
technician to inspect the appliance
and to replace any part of the control system and
any gas control that may have been
under water.
30 minutes with the boiler shut off.
6. Open all strainers in the circulating system,
check flow switch operation, and check for
debris. If debris is present, clean out to ensure
proper circulation.
7. Recheck all air bleeders as described in Step 4.
8. Check liquid level in expansion tank. With the
system full of water and under normal operating
pressure, the level of water in the expansion tank
should not exceed ¼ of the total, with the balance
filled with air.
9. Start up boiler according the procedure in this
manual. Operate the entire system, including the
pump, boiler, and radiation units for one (1) hour.
6.2 Operating the Burner and Set Up
The Brute Magnum modulating appliance utilizes
an advanced, state-of-the-art design. The setup must be
checked before the unit is put in operation. Problems
such as failure to start, rough ignition, strong exhaust
odors, etc. can be due to improper setup. Damage to
the boiler resulting from improper setup is not covered
by the limited warranty.
10. Recheck the water level in the expansion tank. If
the water level exceeds ¼ of the volume of the
expansion tank, open the tank drain, and drain to
that level.
11. Shut down the entire system and vent all
radiation units and high points in the system
piping, as described in Step 4.
12. Close make-up water valve and check strainer in
pressure reducing valve for sediment or debris
from the make-up water line. Reopen make-up
water valve.
13. Check gauge for correct water pressure and also
check water level in the system. If the height
indicated above the boiler insures that water is at
the highest point in the circulating loop, then the
system is ready for operation.
REQUIRED TOOLS:
Differential pressure gauge capable of reading
negative 0.01 inches W.C. (0.002kPa).
1. Using this manual, make sure the installation
is complete and fully in compliance with the
instructions.
2. Determine that the appliance and system are
filled with water and all air has been bled from
both. Open all valves.
3. Observe all warnings on the Operating
Instructions label and turn on gas and electrical
power to appliance.
4. There is a gas/air test panel to the left of the
control panel, at the front of the unit (see Figures
25 and 32). Ensure that all four valves on the test
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 37
panel are closed (see Figure 26).
5. Remove the two plugs from the + and – ports of
the air orifice taps, thread hose barbs into the
1/8" NPT connections, and attach the manometer
pressure lines to the barbs. Be sure all
connections are gas tight.
6. Switch on the appliance power switch located on
the front of the unit.
7. The Brute Magnum will enter the start sequence.
The blower and pump come on for pre-purge,
then the ignitor warm-up sequence starts and
after all safety devices are verified, the gas valve
opens. If ignition doesn’t occur, check that there
is proper gas supply. Wait 5 minutes and start the
unit again.
8. Open air orifice test port valves. Check air
orifice differential at full fire, and make note of
the differential.
9. Switch the Brute Magnum off.
10. Close air orifice valves, remove the barbs and
replace the plugs. Make sure the connections are
gas tight.
11. Remove the two plugs from the + and – ports of
the gas orifice taps, thread hose barbs into the
1/8" NPT connections, and attach the manometer
pressure lines to the barbs. Be sure all
connections are gas tight.
12. Switch on the appliance power switch located on
the front of the unit.
Figure 25. Gas/Air Test Panel.
13. The Brute Magnum will enter the start sequence.
The blower and pump come on for pre-purge,
then the ignitor warm-up sequence starts and
after all safety devices are verified, the gas valve
opens.
14. Open gas orifice test port valves. Check gas
orifice differential at full fire, and make note of
the differential.
15. Close gas orifice valves, remove the barbs and
replace the plugs. Make sure the connections are
gas tight.
Valve
Shown
Closed
16. If gas and air orifice differentials match what is
shown in Table 7, and do not differ from each
other by more than 0.1" w.c., the unit is properly
set up. If not, consult, the factory.
17. After placing the appliance in operation, the
Burner Safety Shutoff Device must be tested.
To test:
Valve
Shown
Open
(a) Close gas shutoff valve with burner
operating.
(b) The flame will go out and blower will
continue to run for the post purge cycle.
One additional attempt to light will follow
including pre-purge, ignitor on, valve/flame
on and post purge. Ignition will not occur
as the gas is off. The ignition control will
lockout, and will have to be reset before the
unit will operate.
Figure 26. Test Panel Valves.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 38
(c) Open gas shutoff valve. Restart the
Section 7
MAINTENANCE
appliance. The ignition sequence will
start again and the burner will start. The
appliance will return to its previous mode
of operation.
WARNING
Disconnect all power to the appliance before
attempting any service to the appliance. Contact
with electricity can result in severe injury or death.
Caution
Should any odor of gas be detected, or if the gas
burner does not appear to be functioning in a
normal manner, CLOSE MAIN SHUTOFF VALVE.
Do not shut off switch. Contact your heating
contractor, gas company, or factory representative.
7.1 System Maintenance
1. Lubricate the system water-circulating pump, if
required, per the instructions on the pump.
2. If a strainer is employed in a pressure reducing
valve or the piping, clean it every six months.
3. Inspect the venting system for obstruction or
leakage at least once a year. Periodically clean
the screens in the vent terminal and combustion
air terminal (when used).
Gas Type
Natural
Air Orifice
Differential
4.0 to 4.5" W.C.
(1.0 to 1.1kPa)
4.5 to 5.0" W.C.
(1.1 to 1.2kPa)
Gas Orifice
Differential
4.0 to 4.5" W.C.
(1.0 to 1.1kPa)
4.5 to 5.0" W.C.
(1.1 to 1.2kPa)
Propane
4. Keep the appliance area clear and free from
combustible materials, gasoline, and other
flammable vapors and liquids.
5. If the appliance is not going to be used for
extended periods in locations where freezing
normally occurs, it should be isolated from the
system and completely drained of all water.
6. Low water cutoffs, if installed, should be
checked every 6 months. Float type low water
cutoffs should be flushed periodically.
7. Inspect and clean the condensate collection and
disposal system yearly.
8. When a means is provided to neutralize
condensate, ensure that the condensate is being
neutralized properly.
9. Inspect flue passages, and clean with brushes/
vacuums, if necessary. Sooting in flue passages
indicates improper combustion. Determine the
cause and correct.
10. Inspect the vent system and air intake system,
and ensure that all joints are sealed properly. If
joints need to be resealed, completely remove
existing sealing material, and clean with alcohol.
Apply new sealing material, and re-assemble.
Note: Long runs of vent or combustion air piping may
reduce the air and gas differential pressures. This
is acceptable, as long as the air and gas pressure
differentials are within 0.1" (0.025kPa) w.c. of each other.
Table 7. Air and Gas Orifice Differentials at Full Fire.
6.3 Shutting Down the Brute Magnum
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. If freezing is anticipated, drain the Brute
Magnum and be sure to also protect building
piping from freezing.
This step to be performed by a qualified
service person.
6.4 To Restart the Brute Magnum
If drained, follow Section 6.1 in this manual
for proper filling and purging.
1. Switch off the main electrical disconnect switch.
2. Close all manual gas valves.
3. WAIT FIVE (5) MINUTES.
4. Set the aquastat or thermostat to its lowest
setting.
7.2 Appliance Maintenance and
Component Description
Only genuine Bradford White replacement parts
should be used.
5. Open all manual gas valves.
6. Reset all safety switches (pressure switch,
manual reset high limit, etc).
7. Set the temperature controller to the desired
temperature setting and switch on electrical
power.
Caution
8. Burner will go through a prepurge period and
ignitor warm-up period, followed by ignition.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after
servicing.
See Figures 27, 28 and 32 for location of gas
train and control components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 39
Figure 27. Gas Trains.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 40
Control Pack B Gas Train
ꢎꢁꢆꢏꢂ ꢈꢅꢄꢐ ꢊ ꢋ
ꢌ ꢂꢍꢃ ꢑꢒꢈꢏ ꢈꢁꢓ
ꢎꢁꢆꢏꢂ ꢈꢅꢄꢐ ꢊ ꢋ
ꢌ ꢂꢍꢃ ꢑꢒꢈꢏ ꢈꢁꢓ
#ꢅꢐꢚ ꢊ ꢋ
ꢙꢓꢃꢋꢋꢏꢓꢃ ꢀꢘꢅꢈꢒꢚ
ꢕꢄꢖꢕꢇꢇ ꢊ ꢋ
ꢌ ꢂꢍꢃ ꢑꢒꢈꢏ ꢈꢁꢓ
#ꢅꢐꢚ ꢊ ꢋ
ꢙꢓꢃꢋꢋꢏꢓꢃ ꢀꢘꢅꢈꢒꢚ
ꢕꢄꢖꢕꢇꢇ ꢊ ꢋ
ꢌ ꢂꢍꢃ ꢑꢒꢈꢏ ꢈꢁꢓ
ꢙꢓꢃꢋꢋꢏꢓꢃ
ꢛꢅꢇꢇꢃꢓꢃꢄꢈꢅ ꢂ
ꢜꢏ ꢃ ꢑꢋꢋꢃ! ꢂꢉ
ꢗꢁꢘ ꢊ ꢋ
ꢙꢓꢃꢋꢋꢏꢓꢃ ꢀꢘꢅꢈꢒꢚ
ꢙꢓꢃꢋꢋꢏꢓꢃ
ꢛꢅꢇꢇꢃꢓꢃꢄꢈꢅ ꢂ
ꢜꢏ ꢃ ꢑꢋꢋꢃ! ꢂꢉ
ꢗꢁꢘ ꢊ ꢋ
ꢙꢓꢃꢋꢋꢏꢓꢃ ꢀꢘꢅꢈꢒꢚ
ꢑꢅꢓ "ꢄꢂꢃꢈ
ꢜꢓ ꢄꢋꢅꢈꢅꢁꢄ
ꢎ ꢄꢏ ꢂ
ꢊ ꢋ ꢌ ꢂꢍꢃ
ꢑꢅꢓ "ꢄꢂꢃꢈ
ꢜꢓ ꢄꢋꢅꢈꢅꢁꢄ
ꢀꢁꢂꢃꢄꢁꢅꢆ ꢀ ꢇꢃꢈꢉ
ꢊ ꢋ ꢌ ꢂꢍꢃ
ꢎ ꢄꢏ ꢂ
ꢊ ꢋ ꢌ ꢂꢍꢃ
ꢙꢓꢃꢋꢋꢏꢓꢃ
ꢀꢘꢅꢈꢒꢚ
ꢀꢁꢂꢃꢄꢁꢅꢆ ꢀ ꢇꢃꢈꢉ
ꢊ ꢋ ꢌ ꢂꢍꢃ
ꢎꢁꢆꢏꢂ ꢈꢅꢄꢐ ꢊ ꢋ
ꢌ ꢂꢍꢃ ꢔꢁꢆꢅꢃꢋ
ꢙꢓꢃꢋꢋꢏꢓꢃ
ꢀꢘꢅꢈꢒꢚ
ꢊ ꢋ
ꢕꢓꢅꢇꢅꢒꢃ
ꢊ ꢋ ꢕꢓꢅꢇꢅꢒꢃ
ꢎꢁꢆꢏꢂ ꢈꢅꢄꢐ ꢊ ꢋ
ꢌ ꢂꢍꢃ ꢔꢁꢆꢉ
Figure 28. Gas Trains.
The gas and electric controls on the appliance
are engineered for long life and dependable operation,
but the safety of the equipment depends on their
proper functioning. It is strongly recommended that
a qualified service technician inspect the basic items
listed below every year.
factory parts. To access the filter, remove the unit’s
front panel. Disengage latch on top of filter box and
remove the filter box cover. Inspect the air filter. If
there is debris on the air filter, remove it from the filter
box, and wash it with mild soap and water. Ensure
that the filter is completely dry before re-installing, in
reverse order.
a. Ignition control
b. Water temperature control
c. Automatic gas valve
7.2.3 Modulating Gas Valve
d. Pressure switches
The modulating gas valve consists of a valve
body and a pressure regulating electro-hydraulic
actuator. It provides the air/gas ratio control for the
unit. It is designed to operate with supply pressures of
4-13 inches w.c. (1.0 to 3.2 kPa).
e. Blower
f.
Mixing control
7.2.1 Burner
Check the burner for debris. Remove the fan
To remove the valve actuator, shut off 120-volt
power and the gas shutoff valve. Remove the front
panel from the unit. Label the four pressure tubes
that are connected to the valve actuator, to ensure
that they will be replaced correctly and disconnect
them from the actuator. Remove the four tubes from
the barb connectors. Disconnect the 120-volt wires
from the actuator. Remove the valve actuator by taking
out the four screws, and pulling the actuator out. Re-
install in reverse order. Turn on gas shutoff valve and
120 volt power and check appliance operation and
tightness of gas valve connections.
assembly to access the burner. Remove the 6 nuts,
which hold the burner in place. Pull burner up and out.
Clean burner, if necessary, by blowing compressed air
from the outside of the burner into the center of the
burner, and wipe the inside of the burner clean with
glass cleaner. A dirty burner may be an indication
of improper combustion or dirty combustion air.
Determine the cause, and correct. Always replace the
burner gasket when replacing the burner.
7.2.2 Filter
The gas valve body will rarely have to be
The filter used in the Brute Magnum is washable
with an 83% arrestance. Since the filter is washable, it
will only need replacement in very rare cases. If filter
replacement is needed, it should only be replaced with
removed. If there is a valve problem, and it has been
determined the actuator is working properly, the gas
valve body may need to be replaced. To remove the
gas valve body, shut off 120-volt power and the gas
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 41
shutoff valve. Remove the front and right-side panels
from the unit. Disconnect the union between the valve
body and the blower. Label the four pressure tubes
that are connected to the valve actuator, to ensure
that they will be replaced correctly. Remove the
valve actuator, per the instructions above. Unscrew
the valve body from the gas train. After the valve has
been removed, replace with a new valve in the reverse
order. Turn on gas shutoff valve and 120 volt power
and check appliance operation and tightness of gas
valve connections.
7.2.4 Safety Gas Valve
The safety gas valve is a 24-volt diaphragm
valve. It is designed to operate with supply pressures
of 4-13 inches w.c. (1.0 to 3.2 kPa). To remove the gas
valve, shut off 120-volt power. Shut off the main gas
supply to the unit. Disconnect the gas supply piping
from the back of the unit. Disconnect the electrical
wires from the valve, and unscrew the gas valve from
the gas train. Re-assemble in reverse order. A bleed
line from the diaphragm type automatic valve shall be
vented per local code requirements.
7.2.5 Manual Reset High Limit Control
Figure 29. Control Panel.
The high limit switch is manual reset switch with
an adjustable set point, up to 240°F (116°C) on boiler
models and 200°F (93°C) water heater models. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull the
switch off the control panel. Replace in reverse order.
7.2.8 Mixing Control
The FX05 mixing control is the device that
controls the position of the mixing valve system. This
control is factory set, and must not be adjusted, except
for the °F or °C choice. To remove the control, unplug
the wires from the back, push on the tabs to slide the
clasping mechanism off, and pull the controller out
through the front of the panel. Replace in reverse order.
7.2.6 Temperature Control
The temperature control consists of an adjustable
electronic control and digital display module. To
replace the control or the display, shut off the 120-
volt power to the appliance. Remove the cover from
the control panel, and remove the screws from the
DIN rail clip, to which the controls are mounted. Pull
the electrical connector from the controller. Slide the
controllers from the DIN rail clip. Replace in reverse
order.
7.2.9 Mixing Valves
There are two 2-way mixing valves that are
linked and connected to a valve actuator to create the
3-way mixing system. To remove the upper right
valve, remove the actuator and then remove the 2 bolts
that connect the sheet metal to the valve. Remove the
linkage from the arm that is welded to the actuator.
Remove the four bolts on the valve, and slide the
valve out. To remove the lower left valve, remove
the 2 bolts that connect the sheet metal to the valve.
Remove the linkage from the arm that is welded to the
actuator. Remove the four bolts on the valve, and slide
the valve out. Reassemble in reverse order.
7.2.7 Auto Reset Temperature Limit
The auto reset temperature limit has a 200°F
(93°C) setting. The is mounted directly onto the Brute
Magnum header, on the inlet to the copper coil. It
senses the inlet water temperature to copper coil, and
guards against a malfunctioning mixing system. To
replace the switch, shut off the 120-volt power to the
appliance. Remove the cover from the switch to access
the mounting screws. Remove the screws, and pull the
switch off the control panel. Replace in reverse order.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 42
panel, the two side access panels, and the top jacket
panel off. (If there is enough clearance on the side, the
top may not have to be removed.) Disconnect the gas
union between the blower and gas valves. Disconnect
the filter box assembly (at the air transition) from the
blower (six 8 mm bolts). Disconnect the two Molex
electrical connectors from the top right of the blower.
Remove the four nuts from the blower flange, and
pull the blower out. Replace blower in reverse order,
ensuring that all joints are made correctly and sealed.
After replacement, ensure that the unit operates
properly, by following the set-up procedure in this
manual.
7.2.10 Mixing Actuator
The mixing actuator connects to both mixing
valves and takes its signal from the mixing control
to properly set the valves to protect the copper heat
exchanger. To remove the actuator, remove the screw
on the front to take the cover off. Disconnect the wires.
Take the 2 nuts off the U-bolt, to move the linkage
to the side, out of the way. Slide the actuator out.
Reassemble in reverse order.
7.2.11 Ignition Control
The ignition control ensures the proved
interrupted-type ignition system. It controls the
hot surface ignitor and proves that the flame signal
is appropriate for powering the gas valves. It also
controls the blower’s pre-purge and post-purge. To
replace the control, shut off the 120-volt power to the
appliance. Remove the cover from the control panel.
Remove the electrical connectors from the ignition
control. Take out the controller’s mounting screws, and
pull the controller out. Replace in reverse order.
7.2.15 Flow Switch
The Brute Magnum uses a paddle-type flow
switch to ensure that the unit has water flow before
ignition is allowed.
7.2.16 Heat Exchanger Coils
Black carbon soot buildup on the external
surfaces of the copper heat exchanger is caused by
one or more of the following; incomplete combustion,
combustion air problems, venting problems and heater
short cycling. Soot buildup or other debris on the heat
exchanger may restrict the flue passages.
7.2.12 Ignitor / Flame Sensor Assembly
The ignitor is a 110v “hot surface” type. It
is energized whenever there is a call for heat and
switched off when ignition is established and the flame
has been sensed. Ignitors with an ohms resistance over
80 ohms (tested after the ignitor has been allowed
to cool to room temperature) should be replaced. To
replace the ignitor, shut off the 120-volt power to the
appliance, disconnect the Molex connector, remove
the two mounting screws on the ignitor flange, and
pull the ignitor out. Always install a new ignitor gasket
with the replacement ignitor.
If black carbon soot buildup on the copper
exchanger is suspected, disconnect electrical supply
to the unit, and turn off the gas supply by closing
the manual gas valve on the unit. Access the heat
exchanger through the side access panels, and inspect
the finned copper tubing using a flashlight. If there is
a buildup of black carbon soot or other debris on the
heat exchanger, clean per the following:
Caution
Caution
Black carbon soot buildup on a dirty heat exchanger
can be ignited by a random spark or flame. To
prevent this from happening, dampen the soot
deposits with a wet brush or fine water spray before
servicing the heat exchanger.
Ignitor gets hot and can cause burns or injury.
7.2.13 Transformers
There are various transformers used on the Brute
Magnum units. Be sure to replace the transformers
with factory parts. These transformers are not capable
of supplying control voltage for external devices such
as zone valves, which must have their own separate
power supply. Should a transformer need replacing,
shut off the 120-volt power. Unplug the transformer
wires, remove the mounting screws and remove the
transformer. Replace transformer in the reverse order.
1. Disconnect the electrical supply to the unit.
2. Turn off the gas supply by closing the manual gas
valve on the heater.
3. Disconnect and remove the wires, conduit and
sensors from all components that are attached to
the inlet/outlet header.
4. Isolate the heat exchanger from the water supply.
5. Drain the heat exchanger from the drain located
on the bottom of the heat exchanger.
6. Disconnect the header flanges from the inlet and
outlet.
7. Remove the heat exchanger from the unit.
NOTE: The heat exchangers are heavy and may
require two people to remove to avoid personal
injury.
7.2.14 Blower
The combustion air blower is a high-pressure
centrifugal blower with a variable speed motor. The
speed of the motor is determined by the control logic,
and the 120-volt current remains on to the blower at all
times. If a blower change is required, turn off the 120-
volt power and gas supply to the unit. Take the front
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 43
8. Clean the heat exchanger: A light accumulation
of soot or corrosion on the outside of the heat
exchanger can be easily removed. Use a wire
brush to remove loose soot and scale from the
heat exchanger. Do not use water or compressed
air for cleaning.
9. NOTE: While the heat exchanger is out of the
unit, inspect the firewall refractory insulation
blocks for cracks, wear and breakage. Replace if
necessary.
10. Inspect the inside of the copper tubes for scale
buildup. Scale can build up on the inner surface
of the heat exchanger tubes, which can restrict
water flow. If the tubes show signs of scaling,
clean the internal surface. Bradford White offers
a tube cleaning kit, part number R2000700.
11. Reassemble in the reverse order.
shutoff valve and 120V power and check appliance
operation and tightness of gas valve connections.
7.2.19 Gas Pressure Switches
The high and low gas pressure switches are 24V
manual reset switches that act to cut power to the gas
valves if the gas pressure is too low or too high for
proper operation. The gas pressure switches used are
integrally vent limited, and do not require venting to
atmosphere. To remove a switch, remove the screw
on the plastic housing and pull the clear cover off.
Disconnect the two wires from the screw terminals.
Twist the switch off the pipe nipple. Reassemble in
reverse order. For natural gas, set the low gas pressure
switch to 3" w.c. For propane, set the low gas pressure
switch to 5" w.c. For natural and propane, set the high
gas pressure switch to 14".
If heat exchanger removal is necessary, consult
the factory for instructions.
NOTE: The Warranty does not cover damage
caused by lack of required maintenance, lack of
water flow, or improper operating practices.
The condensing (stainless steel) heat exchanger
is not in the firing chamber, so it will not experience
sooting. If there is fouling on the stainless steel heat
exchanger, or if it needs to be changed, contact the
factory.
Section 8
TROUBLESHOOTING
8.1 Sequence of Operation
The Brute Magnum appliance is a cold start
appliance that should start only on a call for heat from
a tank aquastat, room thermostat, zone valve end
switch or other space temperature control device.
1. Upon a call for heat,
7.2.17 Normally Open Vent Valve
Some Brute Magnum models provide a
normally open vent valve for installations with IRI
code requirements. The valve opens when power is
removed from the safety valves. And the valve closes
when the safety valves are powered. See Section 3.1
item #4 for installation instructions.
(a) The internal pump will start.
(b) The blower will begin a 15 second pre-
purge.
2. Following the prepurge cycle the hot surface
ignitor will heat and will begin a 7 second trial
for ignition. The unit is allowed three attempts
for ignition.
3. The gas valve will then be energized and low-
fire (50% of full fire) ignition will occur. The
unit will remain in a low-fire start-up period for 15
seconds.
7.2.18 Motorized Safety Valve
Control packs B and E have an additional
motorized safety valve. This valve is powered open
at the same time as the safety valve. To remove the
valve actuator, shut off the 120V power and the gas
shutoff valve. Remove the right side, or front panel.
Disconnect the 120V wires from the actuator. Remove
the valve actuator by taking out the four screws, and
pulling the actuator out. Re-install in reverse order.
Turn on gas shutoff valve and 120V power and
check appliance operation and tightness of gas valve
connections.
4. After the low-fire start time is over, the unit
will be in normal operation firing rate and will
modulate based on the heating load via the
temperature controller settings and readings.
5. The mixing system control will sense the water
temperature entering the copper heat exchanger,
and will change the positions of the mixing
valves to divert enough hot water from the
copper heat exchanger outlet back to its inlet
to keep the inlet at a minimum 140°F (60°C).
Therefore, when the return water temperature is
140°F (60°C) or lower, the outlet temperature
will be 160-165°F (71-74°C). With return
temperatures greater than 140°F (60°C), the
temperature rise across the Brute Magnum is 20-
25°F (11-14°C), when the Brute Magnum is at
high firing rate.
The gas valve body will rarely have to be
removed. If there is a valve problem, and it has been
determined the actuator is working properly, the gas
valve body may need to be replaced. To remove the
gas valve body, shut off 120V power and the gas
shutoff valve. Remove the right side and front panels.
Remove the valve actuator. Unscrew the valve body
from the gas train. After the valve has been removed,
replace with a new valve in reverse order. Turn on gas
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 44
6. When the call for heat is complete, or the unit
reaches its setpoint temperature, the gas valve
will close, and the fan will continue to run for
its 30 second post-purge. If a pump time delay
is used, the pump will continue to run for the
specified amount of time (adjustable from 0.1 to
10 minutes).
8.3 Delayed Ignition - Possible Causes
8.3.1 High Lockup Pressure (LP Appliances)
- Occurs on Start-up
High lock up pressure is the most common
cause of delayed ignitions on LP fueled appliances. It
may result from an improper second stage regulator
selection or from a faulty regulator.
8.2 Resolving Lockouts
Lock up can be detected by measuring the gas
supply pressure to the appliance at the inlet pressure
port on the gas valve. The gas supply to the appliance
must be shut off before making any connections.
To check: use a water manometer or pressure gauge
with a scale reading of at least 25 in. W.C. or 15 oz/
in2. (6.2kPa). Attach the manometer to the gas valve
inlet pressure port. Turn on the gas supply. The
Brute Magnum appliance is designed to operate with
supply pressures of 4-13 in. W.C. (2.3 - 7.5 oz/ in²)
(1.0-3.2kPa). If the supply pressure exceeds 13 in.
W.C. (7.5 oz/ in²) (3.2kPa) (with the appliance off) it
is possible that this may be the cause of the delayed
ignitions and the inlet pressure must be reset to
between 4-13 in. W.C. (2.3 – 7.5 oz/in2) (0.1-3.2kPa).
Restart the appliance and then switch it off. If the inlet
gas pressure exceeds 13 in. W.C. (7.5 oz/ in²) (3.2kPa)
after the appliance is switched off, correct the lock up
problem.
There are many causes of lockouts. The four
most common causes are: (1) inadequate gas supply,
(2) poor combustion, (3) ignitor failure (4) combustion
air.
1. Inadequate gas supply: Before proceeding, ensure
that the gas supply has not been shutoff or the LP
tank (LP boilers) is not empty. Then, restart the
boiler and observe the operational cycle. After
the pre-purge time, the unit should light. If it
does not, consult the factory.
2. Poor Combustion: Poor combustion should be
suspected if there is a strong flue gas odor. The
odor may result from an improper gas/air ratio
(high or low O or CO2). If an improper gas/air
ratio is suspect2ed, consult the factory.
3. Ignitor failure: If the boiler goes through a
normal start cycle but combustion does not
occur, ignitor failure should be suspected. Check
the ignitor by unplugging the ignitor plug and
measuring the ignitor resistance. It should be
50-80 (Ω) ohms. If the resistance is not 50-80
ohms (Ω), replace the ignitor. If the resistance is
correct, reset the boiler and check for 120 VAC
at the ignitor plug during the start cycle. If there
is no voltage, replace the faulty ignitor wire
harness.
4. Inadequate combustion air: If the boiler goes
through a normal ignition cycle, and shuts off
after the blower ramps up to full speed, an
abnormal restriction in the air intake or exhaust
system should be suspected. Check the air filter
for buildup of debris and clean filter if necessary.
Inspect all exhaust venting and intake venting for
blockages. Remove any blockages and inspect
and replace any damaged vent sections. If the
unit still continues to lockout after igniting,
consult the factory.
8.3.2 Gas Valve Regulation
Gas valve regulation problems can also cause
delayed ignitions. If gas valve regulation problems are
suspected, consult the factory. Do not attempt field
adjustment or repair.
8.3.3 Defective Burner - Occurs on Startup
or at Burner Shutdown
A defective burner can cause a delayed ignition.
If the gas supply pressure is proper, and the gas valve
is functioning properly, the burner should be inspected.
There should be no distortion or perforations in the
burner. Replace if indicated.
8.4 Short Cycling — Boiler
Because the Brute Magnum is a modulating
boiler, and its input will decrease when there is a
reduction in heating load, short cycling is greatly
reduced. If the heating load drops below the minimum
input of the boiler for an extended period, the boiler
will have a tendency to short cycle. This can be a
symptom of improper control strategy or setpoints, or
a load distribution problem. See Section 5.5 regarding
controller setup. Contact your Representative to
discuss possible remedies.
Once the reason for the lockout has been
identified and resolved you can reset the unit by
pressing the manual reset button (see Detail A in
Figure 30, Control Panel).
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 45
8.5 Short Cycling — Water Heater
Short cycling will generally occur only in
Section 9
REPLACEMENT PARTS
combination space heating and water heating
applications when the water heater is operating in the
space-heating mode. Because the Brute Magnum is a
modulating water heater and its input will reduce when
there is a reduction in heating load, short cycling is
greatly reduced. If the heating load drops below the
minimum input of the water heater for an extended
period, the water heater will have a tendency to short
cycle. If short cycling is frequently experienced,
regardless of the control’s attempt to limit it, the
heating load should be redistributed to control it. See
Section 5.5 regarding controller setup.
Only genuine Bradford White replacement parts
should be used.
9.1 General Information
To order or purchase parts for the Brute
Magnum, contact your nearest Bradford White dealer
or distributor. If they cannot supply you with what you
need, contact Customer Service (see back cover for
information).
If short cycling occurs in a water heater
application, it is probably caused by undersized
piping between the water heater and the storage tank
or by some other factor that restricts proper water
flow through the water heater. The cause should be
determined and corrected.
8.6 High Gas Consumption
Appliances operating with an improper air/
fuel ratio are very inefficient and consequently, have
very high gas consumption. Because efficiency is
high when the CO2 is high (or O2 is low), appliances
operating with low CO2 or high O2 (especially LP
appliances) consume more gas. Adjust the CO2 or O2
for optimum efficiency. If no combustion analyzing
equipment (CO2 or O2) is available then a proper
adjustment of the air/fuel ratio (CO2 or O2) can not
be accomplished. However, by briefly sniffing the
flue gases it is possible to determine if the CO2 or O2
is within the proper range. No significant flue gas
odor should be detected when combustion is proper.
A strong piercing smell indicates poor combustion
and generally a lean mixture - low CO2 or high O2 .
The CO2 should be 8 to 9% at all firing rates. Do not
attempt to correct combustion. Contact factory if the
CO2 is not within this range.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 46
9.2 Parts List
COMBUSTION COMPONENTS – See Figure 30
1200
1600
2000
2400
2
3
4
5
6
7
8
9
Base assembly
24A1200
24B2600
24A2400
24A2100
24A2200
24B2004
24B2010
24B2009
R2026800
L2012100
S2009700
24A1200
24B2600
24A2400
24A2100
24A2200
24B2004
24B2010
24B2009
R2026800
L2012000
S2009700
R2002500
16B2700
12B2005
24A2025
24A2011
24A2300
24B2012
24A2014
24A2013
S2014400
R2017100
R2017101
not used
24A9003
E2312400
24A1200
24B2600
24A2400
24A2100
24A2200
24B2004
24B2010
24B2009
R2026800
L2011900
S2009700
R2002500
20B2700
12B2005
24A2025
24A2011
24A2300
24B2012
24A2014
24A2013
S2014300
R2017200
R2017201
not used
24A9003
E2312400
24A1200
24B2600
24A2400
24A2100
24A2200
24B2004
24B2010
24B2009
R2026800
L2011800
S2009700
R2002500
24B2700
24B2005
24A2025
24A2011
24A2300
24B2012
24A2014
24A2013
S2014300
R2003100
R2003101
not used
24A9003
E2312400
Panel, top, combustion chamber
Panel, bottom, combustion chamber
Panel, left, combustion chamber
Panel, right, combustion chamber
Panel, access, combustion chamber
Support, front, fan transition
Support, rear, fan transition
10 Hardware kit, Combustion Chamber/Condenser
11 Burner
12 Burner Gasket
13 Tile kit (top & bottom of heat exchanger w/top insulation) R2002500
14 Tile support with rods
15 Tile support protective liner
16 Panel, Divider, Condenser
17 Diverter, Air Flow, Condenser
18 Cover, Flue Transition
19 Clamping Bar, Side/Top, Flue Transition
20 Clamping Bar, Short, Flue Transition
21 Clamping Bar, Long, Flue Transition
22 Heat Exchanger, Condensing
24 Heat exchanger assembly, copper
24 Heat exchanger assembly, cupro-nickel
25 Baffle, Flue
12B2700
12B2005
24A2025
24A2011
24A2300
24B2012
24A2014
24A2013
S2014400
R2013300
R2013301
12A2011
24A9003
E2312400
29 Cable, Securement, Pump/Motor
30 Pressure Switch, Differential
GAS TRAIN / COMBUSTION AIR COMPONENTS – See Figures 31 and 32
35 Gas train assembly, standard, Nat
35 Gas train assembly, standard, LP
35 Gas train assembly, control pack A, Nat
35 Gas train assembly, control pack A, LP
35 Gas train assembly, control pack B and E, Nat
35 Gas train assembly, control pack B and E, LP
36 Gas valve, safety
12B6000
12B6020
12B6400
12B6420
12B6500
12B6520
V2015800
V2014300
V2015400
V2015900
not used
not used
R2011500
not used
16B6000
16B6020
16B6400
16B6420
16B6500
16B6520
V2015700
V2014400
V2015400
V2015900
not used
not used
R2011500
not used
20B6000
20B6020
20B6400
20B6420
20B6500
20B6520
V2015700
V2014400
V2015400
not used
24B6000
24B6020
24B6400
24B6420
24B6500
24B6520
V2015700
V2014400
V2015400
V2015500
not used
not used
R2003600
not used
37 Gas valve, solenoid safety, for control packs B & E
38 Gas valve, mod valve actuator
39 Gas valve, mod valve body
39 Gas valve, mod valve body, size 2000, Nat
39 Gas valve, mod valve body, size 2000, LP
40 Gas valve, mod complete (body and actuator)
40 Gas valve, mod complete (body and actuator)
size 2000, Nat
V2015500
V2015900
not used
R2003600
40 Gas valve, mod complete (body and actuator)
size 2000, LP
not used
not used
R2011500
not used
41 Gas valve, manual (Primary)
41 Gas valve, manual (Secondary)
41 Gas valve, manual (Primary, Control Pack B & E)
42 Double valve body / Actuator
43 Double valve body
44 On/Off Actuator
45 Normally open vent valve
46 Gas orifice kit (orifice in holder), Nat
46 Gas orifice kit (orifice in holder), LP
47 Gas orifice, Nat
V2003000
V2003000
V2003200
not used
V2003200
V2003000
V2003200
not used
V2003200
V2003200
V2003200
R2019600
V2016500
V2016600
V2000100
20B6200
V2003200
V2003200
V2003300
R2019600
V2016500
V2016600
V2000100
24B6200
not used
not used
V2016600
V2000100
12B6200
12B6220
P2035500
P2041500
E0023300
E0023500
V2016600
V2000100
16B6200
16B6220
P2042700
P2043200
E0023300
E0023500
20B6220
24B6220
P2042800
P2043300
E0023300
E0023500
P2034300
P2038300
E0023300
E0023500
47 Gas orifice, LP
48 Pressure switch, high gas
49 Pressure switch, low gas
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 47
1200
1600
2000
2400
50 Tubing/Fittings (gas train repair kit)
51 Air filter box assembly (with gasket and hardware) Nat
51 Air filter box assembly (with gasket and hardware) LP
52 Air filter
53 Gasket kit, air filter
54 Air filter box cover
55 Air filter felt gasket
56 Air filter air inlet vent w / gasket
57 Blower
58 Blower gasket kit
59 Air orifice, Nat
60 Air orifice strip, LP
61 Air orifice, LP
62 Air restrictor, LP
63 Air transition (filter box to blower)
64 Blower adapter transition
65 Ignitor kit (with gasket)
66 Sight glass
R2020700
12B5000
12B5020
A2108300
R2004600
24B5300
S2010800
12B5001
A2108500
R2012200
12B5108
not used
R2020700
16B5000
16B5020
A2108300
R2004600
24B5300
S2010800
24B5001
A2108400
R2005000
16B5108
not used
16B5128
16B5221
24B6100
not used
RW2002300
F0044800
E2312300
R2020700
20B5000
20B5020
A2108300
R2004600
24B5300
S2010800
24B5001
A2108400
R2005000
20B5108
24B5128
20B5108
20B5221
24B6100
not used
R2020700
24B5000
24B5020
A2108300
R2004600
24B5300
S2010800
24B5001
A2108400
R2005000
24B5108
24B5128
24B5108
not used
12B5128
not used
12B6100
12B5201
RW2002300
F0044800
E2312300
24B6100
not used
RW2002300
F0044800
E2312300
RW2002300
F0044800
E2312300
67 Pressure switch, air
ELECTRICAL COMPONENTS – See Figure 33
70 Transformer, 115/24V, 80VA
70 Transformer, 115/24V, 150VA (Control pack B & E only) E2310400
71 Transformer, 115/230V step up
72 Transformer, 24/115 step up
73 Fuse kit, 2 Amp, 5 pack (not shown)
73 Fuse kit, 5 Amp, 5 pack (Control packs B and E) (not shown) RE2043500
74 Fuse holder (qty of 5)
30-280
30-280
E2310400
R2005400
E2306000
RE2043600
RE2043500
RE2000300
R2005600
E2311900
E2312000
RE0015900
RE2217800
E2101400
E2104000
E2306700
E2306200
E0076700
RE2077700
E2311100
E2325700
E2307200
E2039500
E2079400
E2103700
E0109200
E2056300
not used
30-280
E2310400
R2005400
E2306000
RE2043600
RE2043500
RE2000300
R2005600
E2311900
E2312000
RE0015900
RE2217800
E2101400
E2104000
E2306700
E2306200
E0076700
RE2077700
E2311100
E2325700
E2307200
E2039500
E2079400
E2103700
E0109200
E2056300
not used
30-280
E2310400
R2005400
E2306000
RE2043600
RE2043500
RE2000300
R2005600
E2311900
R2022600
RE0015900
RE2217800
E2101400
E2104000
E2306700
E2306200
E0076700
RE2077700
E2311100
E2325700
E2307200
E2039500
E2079400
E2103700
E0109200
E2056300
not used
-
E2306000
RE2043600
RE2000300
R2005600
E2311900
E2312000
RE0015900
RE2217800
E2101400
E2104000
E2306700
E2306200
E0076700
RE2077700
E2311100
E2325700
E2307200
E2039500
E2079400
E2103700
E0109200
E2056300
R2012700
A0014300
24B7001
75 Diagnostic lights kit
76 Ignition control (Single Trial)
76 Ignition control (Three Trial, Control packs F and G)
77 High limit, manual reset, RHCH boiler
77 High limit, manual reset, RHCV water heater
78 Temperature control, RHCH boiler
79 Module, proportional control
80 Timer, delay on make
81 Relay, DPDT, 24V coil
82 Relay, DPDT, 120V coil
83 Relay, EM2 kit
84 Relay, 115VAC SPST
85 Controller, Programmable, Electronic
86 Voltage regulator
87 Terminal block, 2 position
88 Terminal block, 4 position
89 Sensor, temperature control
90 Switch, toggle, 3-way SPDT
91 Switch, toggle, DPDT
92 Control signal converter
93 Bell, alarm, 24V
94 Cover, control panel top
A0014300
24B7001
A0014300
24B7001
A0014300
24B7001
95 Cover, control panel bottom
96 Enclosure, control panel
97 Voltage divider panel
24B7004
24B7002
24B7701
24B7004
24B7002
24B7701
24B7004
24B7002
24B7701
24B7004
24B7002
24B7701
98 Support, control panel bottom
99 Panel, diagnostic lights
24B7010
24B7007
24B7010
24B7007
24B7010
24B7007
24B7010
24B7007
100 Bracket, mounting, diagnostic panel
101 Standoff
24B7008
24B7010
24B7008
24B7010
24B7008
24B7010
24B7008
24B7010
102 Hardware kit, control panel
103 Bracket, support, control panel top
104 Bracket, Low water cutoff, Remote Mount
R2007600
24B7009
24B7012
R2007600
24B7009
24B7012
R2007600
24B7009
24B7012
R2007600
24B7009
24B7012
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 48
1200
1600
2000
2400
105 Switch, Low water cutoff, Manual Reset
RE2075100
RE2075100
RE2075100
RE2075100
HEAT EXCHANGER / WATER PATH – See Figures 34 and 35
110 Header cover
111 Water barrier assembly
112 Gasket, heat exchanger cover
113 Hardware kit, heat exchanger cover
12A4200
12B4100
S2011900
R2013100
16A4200
16B4100
20A4200
20B4100
24A4200
24B4100
S2012300
R2008300
RA0079000
A0002700
A0000400
RE2058300
RE2074000
R2000700
R2008400
E2315000
E2314300
R2027000
P2040501
P2040503
P2040502
P2040504
24A9200
24A9206
R2027100
A2110000
24A9214
24A9207
R2027200
A2109900
R2027300
24A1003
P2011700
P2048400
A2111400
A2111200
-
S2102500
R2023700
RA0079000
A0063600
A0001200
RE2058300
RE2074000
R2000700
R2008400
E2315000
E2314300
R2027000
P2040501
P2040508
P2040506
P2040507
24A9200
S2102600
R2023800
RA0079000
A0002700
A0000400
RE2058300
RE2074000
R2000700
R2008400
E2315000
E2314300
R2027000
P2040501
P2040509
P2040510
P2040504
24A9200
114 Gauge, temperature/pressure
115 Pressure relief valve, RHCH boiler
115 Pressure relief valve, RHCV boiler
116 Immersion well, high limit
117 Immersion well, temperature control
118 Tube cleaning kit (not shown)
119 Flow switch (with paddle)
120 Temperature Control, 100° to 200° F, SPDT
121 Temperature Sensor, 1/8" NPT
122 Low water cutoff Probe Cover/Plate
123 Pipe Assembly (condenser to valve)
124 Pipe Assembly (outlet to pump)
125 Pipe Assembly (valve to pump)
126 Pipe Assembly (coil to inlet)
127 Valve Control Arm
RA0079000
A0063600
A0001200
RE2058300
RE2074000
R2000700
R2008400
E2315000
E2314300
R2027000
P2040501
P2040505
P2040506
P2040507
24A9200
128 Valve Connection Rod
129 Control Arm Hardware Kit
130 Actuator, Valve, Electronic
131 Bracket, Support, Actuator
132 Bracket, Mounting, Actuator/Control
133 Pipe Gasket Kit
12A9206
12A9206
20A9206
R2027100
A2110000
24A9214
R2027100
A2110000
24A9214
R2027100
A2110000
24A9214
12A9207
16A9207
20A9207
R2027200
A2109900
R2027300
24A1003
P2011700
P2048400
A2112100
A2111500
A2111400
R2027200
A2109900
R2027300
24A1003
P2011700
P2048400
A2111500
A2111400
A2111200
R2027200
A2109900
R2027300
24A1003
P2011700
P2048400
A2111500
A2111400
A2111200
134 Valve, Butterfly, 2-Way
135 Pipe Hardware Kit
136 Bracket, Pipe Support
137 Nipple, Close, 2" NPT
138 Elbow, Bronze, 2-1/2" Class 150
139 Soft Water Pump Assembly
Normal Water Pump Assembly
Hard Water Pump Assembly
JACKET – See Figure 36
140 Panel, upper front access
141 Panel, lower front access
142 Panel, waterway access
143 Panel, waterway cover
144 Panel, pump cover
145 Panel, PRV access
146 Panel, rear access
147 Panel, front left
148 Panel, front right
149 Panel, rear left
150 Panel, rear right
151 Panel, common access
152 Panel, top
153 Panel, support
154 Panel, flue vent access
155 Panel, ducted air cover
156 Jacket trim kit
157 Hardware kit, jacket
158 Window, control / display
159 Window guide
24B3200
24B3300
12A3014
24B3012
24B3016
24B3019
24A3006
24B3001
24B3002
24A3003
24A3004
24B3005
24B3007
24B3008
12B3010
24B3011
R2009600
R2009700
A2108200
24B3102
R2010000
R2026400
R2026800
24B3200
24B3300
12A3014
24B3012
24B3016
24B3019
24A3006
24B3001
24B3002
24A3003
24A3004
24B3005
24B3007
24B3008
12B3010
24B3011
R2009600
R2009700
A2108200
24B3102
R2010000
R2026500
R2026900
24B3200
24B3300
20A3014
24B3012
24B3016
24B3019
24A3006
24B3001
24B3002
24A3003
24A3004
24B3005
24B3007
24B3008
20B3010
24B3011
R2009600
R2009700
A2108200
24B3102
R2010000
R2026600
R2027000
24B3200
24B3300
24B3014
24B3012
24B3016
24B3019
24A3006
24B3001
24B3002
24A3003
24A3004
24B3005
24B3007
24B3008
24B3010
24B3011
R2009600
R2009700
A2108200
24B3102
R2010000
R2026700
R2027100
160 Window latch
161 Jacket retro-fit kit (standard)
162 Jacket retro-fit kit (mounted pump)
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 49
Figure 30. Combustion Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 50
Figure 31. Gas Train/Combustion Air Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 51
ꢅꢘ
ꢅꢂ
ꢕꢀ
ꢀꢂ ꢃꢄ ꢅꢘ
ꢀꢕ
ꢅ
ꢇꢈꢉꢊꢋꢌꢉꢍꢎ
ꢀꢁꢂꢃ ꢄ ꢂꢅ ꢄ ꢂꢃ ꢄ
ꢆ ꢃ ꢁꢅ ꢇ ꢈꢂꢉꢊ ꢋ
ꢌꢂꢍ ꢎꢅꢂꢏꢃ
ꢕꢁ
ꢅꢖ
ꢀꢖ ꢃꢄ ꢅꢘ
ꢕꢀ
ꢅꢕ ꢃꢄ ꢅꢁ
ꢗꢘ
ꢅ
ꢇꢏꢐꢑꢒꢓꢔꢌꢉꢍꢎ
ꢀꢂ ꢃꢄ ꢅꢘ
ꢅꢂ
ꢀꢕ
ꢅꢗ
ꢅ
ꢇꢈꢉꢊꢋꢌꢉꢍꢎ
ꢆ ꢃ ꢁꢅ ꢇ ꢈꢂꢉꢊ ꢑ
ꢌꢂꢍ ꢎꢅꢂꢏꢃ
ꢕꢁ
ꢅꢕ ꢃꢄ ꢅꢁ
ꢀꢖ ꢃꢄ ꢅꢘ
ꢅꢖ
ꢅ
ꢇꢏꢐꢑꢒꢓꢔꢌꢉꢍꢎ
ꢅꢖ
ꢕꢀ
ꢅ
ꢇꢈꢉꢊꢋꢌꢉꢍꢎ
ꢀꢂ ꢃꢄꢅꢘ
ꢅꢅ
ꢀꢁ
ꢅꢂ
ꢗꢘ
ꢆ ꢃ ꢁꢅ ꢇ ꢈꢂꢉꢊ ꢐ ꢌꢂꢍ ꢎꢅꢂꢏꢃ
ꢅꢖ
ꢀꢁ
ꢅ
ꢇꢈꢉꢊꢋꢌꢉꢍꢎ
ꢕꢀ
ꢅꢅ
ꢀꢂ ꢃꢄ ꢅꢆ
ꢕꢁ
ꢀꢖ
ꢅꢂ
ꢗꢘ
ꢀꢖ ꢃꢄ ꢅꢘ
ꢅꢕ ꢃꢄ ꢅꢁ
ꢅ
ꢇꢏꢐꢑꢒꢓꢔꢌꢉꢍꢎ
ꢋ ꢅ ꢍꢏꢒꢓꢍ ꢚꢔꢕꢕꢛ ꢚꢜꢕꢕ ꢂꢃ ꢄ
ꢔꢕꢕꢕ ꢈꢅ ꢂꢃ ꢓ ꢘꢂꢍ
ꢕꢁ
ꢅ
ꢇꢏꢐꢑꢒꢓꢔꢌꢉꢍꢎ
ꢅꢆ ꢃꢄ ꢅꢀ
ꢅꢕ ꢃꢄ ꢅꢁ
ꢋ ꢅ ꢍꢏꢒꢓꢍ ꢔꢕꢕꢕ ꢖꢂꢁꢗꢅꢂꢇ ꢘꢂꢍ ꢂꢃ ꢄ ꢔꢙꢕꢕ
Figure 32. Gas Train Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 52
Figure 33. Electrical Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 53
Figure 34. Heat Exchanger / Water Path Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
BRADFORD WHITE CORP.
Page 54
Figure 35. Heat Exchanger / Water Path Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
Brute Magnum
Page 55
Figure 36. Jacket Components.
Download from Www.Somanuals.com. All Manuals Search And Download.
®
Bradford White Company reserves the right to change specifications, components, features, or to discontinue products without notice.
Ambler, PA 19002
Tech. Service (800) 334-3393
Service Parts (800) 538-2020
Warranty Service (800) 531-2111
Litho in U.S.A. © Bradford White 1102 Document 1246
Download from Www.Somanuals.com. All Manuals Search And Download.
|