ABB ACS580 0P User Manual

ACS580-0P  
Supplement Installation Manual for ACS580-0P  
ACS580-0P Enclosed Drives (230V, 1-100 HP; 480V, 1-200 HP;  
575, 2-150 HP)  
Supplemental Installation Manual for ACS580-0P  
3
Safety instructions  
These are the safety instructions which you  
must obey when you install and operate the  
drive and do maintenance on the drive. If you  
ignore the safety instructions, injury, death or  
damage can occur.  
• Handle the drive carefully.  
• Frames R5…R9: Lift the drive with a  
lifting device. Use the lifting eyes of the  
drive.  
• Frames R5…R9: Do not tip the drive  
over. The drive is heavy and its center of  
gravity is high. An overturning drive can  
cause physical injury.  
Use of warnings and notes in this  
manual  
Warnings tell you about conditions which can  
cause injury or death, or damage to the  
equipment. They also tell you how to prevent  
the danger. Notes draw attention to a particular  
condition or fact, or give information on a  
subject.  
The manual uses these warning symbols:  
Electricity warning tells about hazards  
from electricity which can cause injury  
or death, or damage to the equipment.  
General warning tells about  
conditions, other than those caused by  
electricity, which can cause injury or death,  
or damage to the equipment.  
Electrostatic sensitive devices  
warning tells you about the risk of  
electrostatic discharge which can cause  
damage to the equipment.  
• Beware of hot surfaces. Some parts, such  
as heatsinks of power semiconductors,  
remain hot for a while after disconnection of  
the electrical supply.  
General safety in installation,  
start-up and maintenance  
• Keep the drive in its package or protect it  
otherwise from dust and burr from drilling  
and grinding until you install it.  
These instructions are for all personnel that  
install the drive and do maintenance work on it.  
• Vacuum clean the area below the drive  
before the start-up to prevent the drive  
cooling fan from drawing the dust inside the  
drive.  
WARNING! Obey these instructions. If  
you ignore them, injury or death, or  
damage to the equipment can occur.  
• Use safety shoes with a metal toe cap to  
avoid foot injury. Wear protective gloves and  
long sleeves. Some parts have sharp edges.  
• Do not cover the air inlet and outlet when the  
drive runs.  
• Make sure that there is sufficient cooling.  
See the ACS580 Hardware Manual  
Safety instructions  
4
Supplemental Installation Manual for ACS580-0P  
(3AXD50000044794) and Quick Start Guide  
(3AXD50000049129) for more information.  
stop key on the control panel will not stop  
the drive.  
• Before you connect voltage to the drive,  
make sure that the drive covers are on.  
Keep the covers on during the operation.  
• Frames R1…R5: Do not attempt to repair a  
malfunctioning drive; contact your local  
representative for replacement or repair by  
authorized persons.  
• Before you adjust the drive operation limits,  
make sure that the motor and all driven  
equipment can operate throughout the set  
operation limits.  
• Frames R6…R9: Can be repaired by  
authorized persons.  
• Before you activate the automatic fault reset  
or automatic restart functions of the drive  
control program, make sure that no  
Electrical safety in installation,  
start-up and maintenance  
dangerous situations can occur. These  
functions reset the drive automatically and  
continue operation after a fault or supply  
break. If these functions are activated, the  
installation must be clearly marked as  
defined in IEC/EN 61800-5-1, subclause  
6.5.3, for example, “THIS MACHINE  
STARTS AUTOMATICALLY”.  
Precautions before electrical work  
These warnings are for all personnel who do  
work on the drive, motor cable or motor.  
WARNING! Frames R1 … R9: Obey  
these instructions. If you ignore them,  
injury or death, or damage to the equipment  
can occur. If you are not a qualified electrical  
professional, do not do electrical installation or  
maintenance work. Go through these steps  
before you begin any installation or  
• The maximum number of drive power-ups is  
five in ten minutes. Too frequent power-ups  
can damage the charging circuit of the DC  
capacitors.  
maintenance work.  
1. Clearly identify the work location.  
• If you have connected safety circuits to the  
drive (for example, emergency stop and  
Safe torque off), validate them at the start  
up. For the validation of the Safe Torque Off,  
see ACS580 firmware manual  
2. Disconnect all possible voltage sources.  
Lock and tag.  
• Open the main disconnector at the power  
supply of the drive.  
(3AXD50000016097 [English]). For the  
validation of other safety circuits, see the  
instructions provided with them.  
• Make sure that reconnection is not  
possible.  
Note:  
• Disconnect any external power sources  
from the control circuits  
• If you select an external source for start  
command and it is on, and the start  
command is level-triggered, the drive will  
start immediately after fault reset. See  
parameters 20.02 Ext1 start trigger type and  
20.07 Ext2 start trigger type in ACS580  
control program firmware manual  
• After you disconnect the drive, always  
wait for 5 minutes to let the intermediate  
circuit capacitors discharge before you  
continue.  
3. Protect any other energized parts in the  
work location against contact.  
(3AXD50000016097 [English]).  
4. Take special precautions when close to bare  
conductors.  
• When the control location is not set to Local  
(text Hand is not shown on the top row of the  
panel and parameter 19.19 Off mode  
disable has value Off button disabled), the  
Safety instructions  
Supplemental Installation Manual for ACS580-0P  
5
5. Measure that the installation is  
Note: For other systems, connecting the  
de-energized.  
internal EMC filter will reduce the conducted  
emission.  
• Use a multimeter with an impedance of at  
least 1 Mohm.  
• If the drive will be connected on a corner-  
grounded TN system, make sure the EMC  
filter is not connected (metal screws should  
not be installed). Connections with metal  
screws in these systems can cause danger  
or damage. See section Checking the  
compatibility with IT (ungrounded) and  
corner-grounded TN systems (North  
• Make sure that the voltage between the  
drive input power terminals (L1, L2, L3)  
and the grounding terminal (PE) is close  
to 0 V.  
Frames R1…R3: Measure the voltage  
between the drive UDC+ terminal and  
grounding terminal (PE) with one  
multimeter. As there is no UDC- terminal,  
measure the voltage between the drive  
T1/U terminal and grounding terminal  
(PE) with another multimeter. Make sure  
that the voltage difference between the  
multimeters is close to 0 V.  
America) in ACS580 Hardware Manual.  
Note: For other systems, connecting the  
internal EMC filter (using metal screws) will  
reduce the conducted emission.  
• Use all ELV (extra low voltage) circuits  
connected to the drive only within a zone of  
equipotential bonding, that is, within a zone  
where all simultaneously accessible  
conductive parts are electrically connected  
to prevent hazardous voltages appearing  
between them. You can accomplish this by a  
proper factory grounding, that is, make sure  
that all simultaneously accessible  
Frames R4…R9: Measure the voltage  
between the drive DC terminals (UDC+  
and UDC-) and the grounding terminal  
(PE) and make sure that it is close to 0 V.  
6. Install temporary grounding as required by  
the local regulations.  
conductive parts are grounded to the  
protective earth (PE) bus of the building.  
7. Ask for a permit to work from the person in  
control of the electrical installation work.  
• Do not do insulation or voltage withstand  
tests on the drive or drive modules.  
If the drive does not operate according to these  
steps, refer to the ACS580-01 Hardware  
Manual (3AXD50000044794) and Quick Start  
Guide (3AXD50000049129).  
Note:  
• The motor cable terminals of the drive are at  
a dangerous voltage when the input power  
is on, regardless of whether the motor is  
running or not.  
Additional instructions and notes  
• The DC and brake resistor terminals (UDC+,  
UDC-, R+ and R-) are at a dangerous  
voltage.  
WARNING! Obey these instructions. If  
you ignore them, injury or death, or  
damage to the equipment can occur.  
• External wiring can supply dangerous  
voltages to the terminals of relay outputs  
(RO1, RO2 and RO3).  
• If the drive will be connected on an IT  
system (ungrounded or high-resistance-  
grounded [over 30 ohms]), make sure  
neither the EMC filter nor the ground-to-  
phase varistor are connected (metal screws  
should not be installed). Connections with  
metal screws in these systems can cause  
danger or damage. See section Checking  
the compatibility with IT (ungrounded) and  
corner-grounded TN systems (North  
• The Safe torque off function does not  
remove the voltage from the main and  
auxiliary circuits. The function is not effective  
against deliberate sabotage or misuse.  
WARNING! Use a grounding wrist band  
when you handle the printed circuit  
boards. Do not touch the boards unnecessarily.  
America) in ACS580 Hardware Manual.  
Safety instructions  
6
Supplemental Installation Manual for ACS580-0P  
The boards contain components sensitive to  
electrostatic discharge.  
• install a device which automatically  
disconnects the supply if the protective  
earth conductor breaks.  
Grounding  
These instructions are for all personnel who are  
responsible for the electrical installation,  
including the grounding of the drive.  
WARNING! Obey these instructions. If  
you ignore them, injury or death, or  
equipment malfunction can occur, and  
electromagnetic interference can increase.  
• If you are not a qualified electrical  
professional, do not do grounding work.  
• Always ground the drive, the motor and  
adjoining equipment to the protective earth  
(PE) bus of the power supply. This is  
necessary for the personnel safety. Proper  
grounding also reduces electromagnetic  
emission and interference.  
• In a multiple-drive installation, connect each  
drive separately to the protective earth (PE)  
bus of the power supply.  
• Make sure that the conductivity of the  
protective earth (PE) conductors is  
sufficient. See section Power cable terminal  
and lead-through data in ACS580 Hardware  
Manual. Obey the local regulations.  
• Connect the power cable shields to the  
protective earth (PE) terminals of the drive.  
• Standard IEC/EN & UL 61800-5-1 (section  
4.3.5.5.2.) requires that as the normal touch  
current of the drive is higher than 3.5 mA AC  
or 10 mA DC, you must use a fixed  
protective earth (PE) connection. In addition,  
• install a second protective earth  
conductor of the same cross-sectional  
area as the original protective earthing  
conductor,  
or  
• install a protective earth conductor with a  
cross-section of at least 7 AWG  
(10 mm2) Cu,  
or  
Safety instructions  
Supplemental Installation Manual for ACS580-0P  
7
• Install temporary grounding to the drive  
output terminals (T1/U, T2/V, T3/W).  
Connect the output terminals together as  
well as to the PE.  
Additional instructions for  
permanent magnet motor drives  
Safety in installation, start-up and  
maintenance  
Start-up and operation:  
• Make sure the motor is not run over the  
rated speed with dynamic/positive  
displacement loads.  
These are additional warnings concerning  
permanent magnet motor drives. The other  
safety instructions in this chapter are also valid.  
WARNING! Obey these instructions. If  
you ignore them, injury or death and  
damage to the equipment can occur.  
General safety in operation  
These instructions are for all personnel that  
operate the drive.  
• Do not work on a drive when a rotating  
permanent magnet motor is connected to it.  
A rotating permanent magnet motor  
energizes the drive including its power  
terminals.  
WARNING! Obey these instructions. If  
you ignore them, injury or death, or  
damage to the equipment can occur.  
• Do not control the motor with the line side  
disconnect at the drive power supply;  
Before installation, start-up and maintenance  
work on the drive:  
instead, use the control panel start and stop  
keys or commands through the I/O terminals  
of the drive.  
• Stop the motor.  
• Disconnect the motor from the drive with a  
safety switch or by other means.  
• Give a stop command to the drive before  
you reset a fault. If you have an external  
source for the start command and the start is  
on, the drive will start immediately after the  
fault reset, unless you configure the drive for  
pulse start. See the firmware manual.  
• If you cannot disconnect the motor, make  
sure that the motor cannot rotate during  
work. Make sure that no other system, like  
hydraulic crawling drives, can rotate the  
motor directly or through any mechanical  
connection like felt, nip, rope, etc.  
• Before you activate automatic fault reset  
functions of the drive control program, make  
sure that no dangerous situations can occur.  
These functions reset the drive  
• Measure that the installation is de-  
energized.  
• Use a multimeter with an impedance of at  
least 1 Mohm.  
automatically and continue operation after a  
fault.  
• Make sure that the voltage between the  
drive output terminals (T1/U, T2/V, T3/W)  
and the grounding (PE) busbar is close to  
0 V.  
Note: When the drive is not in the Hand mode,  
the Off key on the control panel will not stop the  
drive.  
• Make sure that the voltage between the  
drive input power terminals (L1, L2, L3)  
and the grounding (PE) busbar is close to  
0 V.  
Cybersecurity disclaimer  
This product is designed to be connected to  
and to communicate information and data via a  
network interface. It is Customer’s sole  
• Make sure that the voltage between the  
drive DC terminals (UDC+, UDC-) and  
the grounding (PE) terminal is close to  
0 V.  
responsibility to provide and continuously  
ensure a secure connection between the  
product and Customer network or any other  
network (as the case may be). Customer shall  
Safety instructions  
8
Supplemental Installation Manual for ACS580-0P  
establish and maintain any appropriate  
measures (such as but not limited to the  
installation of firewalls, application of  
authentication measures, encryption of data,  
installation of anti-virus programs, etc) to  
protect the product, the network, its system and  
the interface against any kind of security  
breaches, unauthorized access, interference,  
intrusion, leakage and/or theft of data or  
information. ABB and its affiliates are not liable  
for damages and/or losses related to such  
security breaches, any unauthorized access,  
interference, intrusion, leakage and/or theft of  
data or information.  
Safety instructions  
Supplemental Installation Manual for ACS580-0PACQ580-Px  
9
Contents  
This manual is the Installation Manual for the ACS580 Drives. Complete technical  
details are available in the ACS580 Hardware manual, publication number  
3AXD50000044794. Complete programming information is available in the ACS580  
control program firmware manual, publication number 3AXD50000016097.  
To determine the type of your drive, refer to its construction code on either:  
• Serial number label attached on upper part of  
ACS580í0Pí052Aí4  
U1 3ph 400/480 VAC  
I2 62/52 A  
the top mounting plate between the mounting  
S/N * 2173303939  
holes.  
• Type code label attached to the base frame – on the side of the enclosure.  
ACS580−0P−052A−4  
Construction  
Made in USA of Foreign Parts  
code  
Input U1 3ph 400/480 VAC  
E211945  
I1 52 A  
F1 50/60 Hz  
FRAME  
ABB Oy  
Output  
U2 3ph 0...U1  
I2 52 A  
f2 0...500 Hz  
Hiomotie 13  
00380, Helsinki  
Finland  
R4  
Air cooling  
IP21 Icc 100 kA  
UL Type 1  
S/N * 2173303939  
Manufacturing  
year and week  
Contents  
10  
Supplemental Installation Manual for ACS580-0P  
ACS580-0P  
Installation  
This information is unique to ACS580 input disconnect configurations (0P or  
0P+F255). The ACS580 with Input Disconnect is an ACS580 AC adjustable  
frequency drive packaged with an input disconnect switch or circuit breaker. Refer to  
the Installation instructions on page 8, for all other information. Failure to observe  
the warnings and instructions may cause a malfunction or personal hazard.  
WARNING! Before you begin read Safety instructions on page 2.  
WARNING! When the ACS580 with Input Disconnect is connected to the line power,  
the Motor Terminals T1, T2, and T3 are live even if the motor is not running. Do not  
make any connections when the ACS580 with Input Disconnect is connected to the  
line. Disconnect and lock out power to the drive before servicing the drive. Failure to  
disconnect power may cause serious injury or death.  
1. Install wiring  
WARNING!  
• Metal shavings or debris in the enclosure can damage electrical equipment and  
create a hazardous condition. Where parts, such as conduit plates require cutting  
or drilling, first remove the part. If that is not practical, cover nearby electrical  
components to protect them from all shavings or debris.  
• Do not connect or disconnect input or output power wiring, or control wires, when  
power is applied.  
• Never connect line voltage to drive output Terminals T1, T2, and T3.  
• Do not make any voltage tolerance tests (Hi Pot or Megger) on any part of the unit.  
Disconnect motor wires before taking any measurements in the motor or motor wires.  
• Make sure that power factor correction capacitors are not connected between the  
drive and the motor.  
Horsepower Range by Voltage Range  
Base Drive  
Frame  
Enclosure Designation  
208V  
460V  
575V2  
Px1-1 & Px12-1  
Px1-2 & Px12-2  
Px1-3 & Px12-3  
Px1-4 & Px12-4  
PxB3R-1  
1 to 5 HP  
10 HP  
1 to 7.5 HP  
10 to 15 HP  
20 to 30 HP  
40 to 60 HP  
1 to 15 HP  
20 to 60 HP  
N/A  
R1  
R2  
R3  
R4  
2 to 15 HP  
20 to 30 HP  
N/A  
15 to 20 HP  
25 HP  
1 to 10 HP  
2 to 15 HP  
R1-R2  
PxB3R-2  
15 to 25 HP  
30 to 100 HP1 75 to 200 HP  
20 to 30 HP* R3-R4  
40 to 150 HP R5-R8  
PxB1-3 & PxB12-3  
1) 100 HP @ 230V.  
* Only available as ACS580 R2 Frame  
** Only available as ACS580 R3 Frame  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
11  
Connection diagrams – Vertical Packaged Drive with input disconnect  
ACS580-0P Vertical Packaged Drive units are configured for wiring access from the  
bottom only. The following figures show the layout and wiring connection points. For  
drive control wiring see . Maintain appropriate separation of control and power wires.  
ACS580  
Drive  
Motor  
Terminals  
Motor  
Ground Lug  
Fuses  
Disconnect Switch  
or Circuit Breaker  
Input  
Ground Lug  
Input Power  
Terminals  
P1/P2  
(Px1-1, Px12-1, Px1-2, Px12-2)  
ACS580-0P  
12  
Supplemental Installation Manual for ACS580-0P  
ACS580  
Drive  
Motor  
Terminals  
Motor  
Ground Lug  
Fuses  
Disconnect Switch  
or Circuit Breaker  
Input  
Terminals  
Input  
Ground Lug  
P3/P4  
(Px1-3, Px12-3, Px1-4, Px12-4)  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
13  
Connection diagrams – Box Packaged Drive with input disconnect  
ACH580 Vertical Packaged Drive units are configured for wiring access from the top  
(for UL (NEMA) Type 1 and 12) and from the bottom (for UL (NEMA) Type 3R). The  
following figures show the layout and wiring connection points. For drive control  
wiring see pages 29-41.  
Motor  
Ground Lug  
Input  
Ground Lug  
ACS580  
Drive  
User  
Power Cable  
Guide  
Input  
Terminals  
Disconnect  
Switch or  
Circuit  
Motor  
Terminals  
Breaker  
User  
Power Cable  
Guide  
Fuses  
Motor  
Ground Lug  
PB3  
(PxB1-3, PxB12-3)  
ACS580-0P  
14  
Supplemental Installation Manual for ACS580-0P  
RHTR Temperature  
HI/LO Jumper (X1)  
Heater ON  
Temperature Temperature  
Heater OFF  
Default Setting  
(X1 jumper in LO  
position)  
14.4 °C  
58 °F  
21.4 °C  
70.5 °F  
Alternate Setting  
(X1 jumper in HI  
position)  
17.8 °C  
64 °F  
24.4 °C  
76.5 °F  
The alternate (HI) setting further reduces the  
likelihood of condensate in high humidity  
environments.  
ACS580  
Drive  
Fuses  
Motor  
Terminals  
Service  
Switch  
(Optional)  
Motor  
Ground Lug  
Disconnect  
Switch or  
Circuit  
Breaker  
Input  
Terminals  
Motor  
Terminals  
T1 T2 T3  
Input  
Ground Lug  
MOV and Line Reactor  
(Optional)  
Output  
Ground Lug  
PB1/PB2  
(PxB3R-1, PxB3R-2)  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
Power connection terminals  
15  
The following tables show maximum wire size and required tightening torque for  
incoming power, grounding and motor terminals.1)“0P” represents disconnect and +F255  
option code replaces the disconnect with a circuit breaker.  
Output  
208/230 Volt  
Maximum Power Wiring Data  
Circuit  
Ratings  
Base  
Drive  
Frame  
Size  
Breaker  
(+F255)  
Disconnect  
Circuit  
Disconnect  
Switch  
Switch  
Ground Lugs  
UL (NEMA)  
Type 1 and 12  
Breaker  
Motor  
Terminals  
Type Code1  
A
HP  
UL  
UL (NEMA)  
Type 1  
and 12  
UL (NEMA)  
UL (NEMA)  
(NEMA)  
Type 1  
and 12  
Type 3R3  
Type 3R3  
ACS580-0P-04A6-2  
ACS580-0P-06A6-2  
ACS580-0P-07A5-2  
ACS580-0P-10A6-2  
ACS580-0P-017A-2  
ACS580-0P-024A-2  
4.6  
6.6  
1
1.5  
2
R1  
R1  
R1  
R1  
R1  
R2  
#10  
#10  
#10  
#10  
#10  
62 in-lbs  
62 in-lbs  
55 in-lbs  
55 in-lbs  
7.5  
0.7 ft-lbs  
10.6  
16.7  
24.2  
3
5
#6  
62 in-lbs  
#6  
62 in-lbs  
#6  
55 in-lbs  
#6  
55 in-lbs  
7.5  
#2  
#6  
1.1 ft-lbs  
50 in-lbs  
#4  
62 in-lbs  
#4  
62 in-lbs  
#4  
55 in-lbs  
#4  
55 in-lbs  
ACS580-0P-031A-2  
ACS580-0P-046A-2  
ACS580-0P-059A-2  
ACS580-0P-075A-2  
ACH580-PxR-088A-2  
ACH580-PxR-114A-2  
30.8  
46.2  
59.4  
74.8  
88  
10  
15  
20  
25  
30  
40  
50  
60  
R2  
R3  
R3  
R4  
R5  
R5  
R6  
R7  
#2  
62 in-lbs  
#2  
62 in-lbs  
#2  
55 in-lbs  
#2  
55 in-lbs  
#2  
2.6 ft-lbs  
#1  
62 in-lbs  
#1  
62 in-lbs  
#1  
55 in-lbs  
#1  
55 in-lbs  
#1/0  
62 in-lbs  
#1/0  
62 in-lbs  
#1/0  
55 in-lbs  
#1/0  
55 in-lbs  
#1  
3.0 ft-lbs  
#2/0  
124 in-lbs  
#2/0  
275 in-lbs  
#2/0  
4.1 ft-lbs  
#1/0  
124 in-lbs  
#4/0  
275 in-lbs  
114  
#3/0  
124 in-lbs  
300 MCM  
22.1 ft-lbs  
ACH580-PxR-143A-2 143  
ACH580-PxR-169A-2 169  
200 MCM  
275 in-lbs  
Consult  
Factory  
Consult  
Factory  
#1/0  
50 in-lbs  
#4/0  
124 in-lbs  
500 MCM  
29.5 ft-lbs  
2 X 500  
MCM  
274 in-lbs  
ACH580-PxR-211A-2  
211  
75  
R7  
R8  
2 X 500  
MCM  
274 in-lbs  
373  
MCM  
274 in-lbs  
2 x 300  
MCM  
29.6 ft-lbs  
ACH580-PxR-248A-2 248 1002  
1) 0P represents a disconnect with fuses. 0P+F255 represents a circuit breaker.  
2) 100 HP @ 230V.  
3) Only available for packaged drives in box enclosures.  
ACS580-0P  
16  
Supplemental Installation Manual for ACS580-0P  
Output  
Ratings  
460 Volt  
Maximum Power Wiring Data  
Circuit  
Breaker  
(+F255)  
Base  
Drive  
Frame  
Size  
Ground  
Lugs  
UL  
(NEMA)  
Type 1  
and 12  
Circuit  
Disconnect  
Switch  
UL (NEMA)  
Type 1  
and 12  
Disconnec  
t Switch  
Breaker  
Motor  
Terminals  
Type Code1  
A
HP  
UL  
UL  
UL(NEMA)  
(NEMA)  
Type 1  
and 12  
(NEMA)  
Type 3R2  
Type 3R2  
ACS580-0P-02A1-4  
ACS580-0P-03A0-4  
ACS580-0P-03A5-4  
ACS580-0P-04A8-4  
ACS580-0P-07A6-4  
ACS580-0P-012A-4  
2.1  
3
1
1.5  
2
R1  
R1  
R1  
R1  
R1  
R1  
3.5  
4.8  
7.6  
12  
#12  
62 in-lbs  
#12  
62 in-lbs  
#10  
55 in-lbs  
#10  
55 in-lbs  
#10  
0.7 ft-lbs  
3
5
7.5  
#8  
#8  
ACS580-0P-014A-4  
ACS580-0P-023A-4  
ACS580-0P-027A-4  
14  
23  
27  
10  
15  
20  
R2  
R2  
R3  
55 in-lbs  
55 in-lbs  
#10  
#10  
#6  
62 in-lbs  
62 in-lbs  
1.1 ft-lbs  
#6  
55 in-lbs  
#6  
55 in-lbs  
#2  
50 in-lbs  
#8  
62 in-lbs  
#8  
62 in-lbs  
#4  
55 in-lbs  
#4  
55 in-lbs  
#2  
ACS580-0P-034A-4  
ACS580-0P-044A-4  
34  
44  
25  
30  
R3  
R3  
2.6 ft-lbs  
#6  
#3  
#3  
62 in-lbs  
55 in-lbs  
55 in-lbs  
#6  
62 in-lbs  
#1/0  
124 in-lbs  
#2  
55 in-lbs  
#2  
55 in-lbs  
ACS580-0P-052A-4  
ACS580-0P-065A-4  
ACS580-0P-077A-4  
AC580-Px-096A-4  
AC580-Px-124A-4  
AC580-Px-156A-4  
AC580-Px-180A-4  
52  
65  
40  
50  
R4  
R4  
R4  
R5  
R6  
R7  
R7  
#1  
55 in-lbs  
#1  
55 in-lbs  
#1  
3.0 ft-lbs  
#1/0  
#1/0  
124 in-lbs 124 in-lbs  
#1/0  
55 in-lbs  
#1/0  
55 in-lbs  
77  
60  
#1/0  
124 in-lbs  
#3/0  
275 in-lbs  
#2/0  
4.1 ft-lbs  
96  
75  
#2/0  
124 in-lbs  
250 MCM  
275 in-lbs  
300 MCM  
22.1 ft-lbs  
124  
156  
180  
100  
125  
150  
#3/0  
Consult  
124 in-lbs  
Factory  
Consult  
Factory  
3 x #3/0  
250 in-lbs  
300 MCM  
275 in-lbs  
500 MCM  
29.5 ft-lbs  
#4/0  
124 in-lbs  
350  
MCM  
274 in-lbs  
2 x 500  
MCM  
274 in-lbs  
2 x 300  
MCM  
29.6 ft-lbs  
AC580-Px-240A-4  
240  
200  
R8  
1) “0P” represents a disconnect with fuses and 0P+F255 represents a circuit breaker.  
2) Only available for packaged drives in box enclosures.  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
17  
575 Volt  
Output Range  
Maximum Power Wiring Data  
Circuit  
Base  
Drive  
Frame  
Size  
Breaker  
Ground  
Circuit  
Breaker UL  
(NEMA)  
Disconnect Disconnect  
Switch UL Switch  
(+F255)  
UL  
(NEMA)  
Type 1  
and 12  
Lugs  
UL (NEMA)  
Type 1  
Motor  
Type Code1, 2  
A
HP  
(NEMA) Type UL (NEMA) Terminals  
4
4
Type 3R  
1 and 12  
Type 3R  
and 12  
#10  
#10  
ACS580-0P-02A7-6  
ACS580-0P-03A9-6  
2.7  
3.9  
2
3
R2  
R2  
62 in-lbs  
62 in-lbs  
#12  
62 in-lbs  
#12  
62 in-lbs  
#10  
55 in-lbs  
#10  
55 in-lbs  
#6  
1.1 ft-lbs  
ACS580-0P-06A1-6  
ACS580-0P-09A0-6  
ACS580-0P-011A-6  
ACS580-0P-017A-6  
ACS580-0P-022A-6  
ACS580-0P-027A-6  
ACS580-0P-032A-6  
6.1  
9
5
R2  
R2  
R2  
R2  
R3  
R3  
R3  
#10  
#10  
7.5  
10  
15  
20  
25  
30  
62 in-lbs  
62 in-lbs  
11  
17  
22  
27  
32  
#6  
62 in-lbs  
#6  
62 in-lbs  
#6  
#6  
#2  
50 in-lbs  
55 in-lbs  
55 in-lbs  
#2  
2.6 ft-lbs  
#4  
62 in-lbs  
#4  
62 in-lbs  
#4  
55 in-lbs  
#4  
55 in-lbs  
#3  
#3  
ACH580-PxR-041A-6  
ACH580-PxR-052A-63  
ACH580-PxR-062A-6  
41  
52  
62  
40  
50  
60  
R5  
R5  
R6  
62 in-lbs  
55 in-lbs  
#2/0  
4.1 ft-lbs  
#2  
62 in-lbs  
#2  
55 in-lbs  
#1  
62 in-lbs  
#1  
275 in-lbs  
300 MCM  
22.1 ft-lbs  
#1/0  
62 in-lbs  
#1/0  
275 in-lbs  
Consult  
Factory  
Consult  
Factory  
ACH580-PxR-077A-6  
77  
75  
R6  
#3/0  
#3/0  
ACH580-PxR-099A-6  
ACH580-PxR-125A-6  
99  
100  
125  
R7  
R7  
3 x #3/0  
250 in-lbs  
124 in-lbs  
275 in-lbs  
500 MCM  
29.5 ft-lbs  
250 MCM  
275 in-lbs  
125  
250 MCM  
124 in-lbs  
2 x 300  
MCM  
29.6 ft-lbs  
300 MCM  
275 in-lbs  
ACH580-PxR-144A-6  
144  
150  
R8  
1) 0P represents both a disconnect and 0P+F255 represents a circuit breaker.  
2) 0P+F255 is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye source only.  
3) 0P+F255 supports Delta network configuration.  
4) Only available with packaged box enclosures.  
ACS580-0P  
18  
Supplemental Installation Manual for ACS580-0P  
Branch circuit protection  
Input power is connected to the ACS580 through a door interlocked disconnect  
switch or circuit breaker. When connected to a 240V or 480V power source, the  
ACS580 with the circuit breaker option is suitable for use on a circuit capable of  
delivering not more than 100,000 RMS symmetrical amperes. When connected to a  
600V power source, PC configurations are suitable for use on a circuit capable of  
delivering not more than 10,000 RMS symmetrical amperes (75-150 HP), and not  
more than 25,000 RMS symmetrical amperes (2-60 HP).  
Fuses  
Note: The UL listed drive fuses in the table are provided in the purchased product.  
• Replacement fuses are required to be of the same class, current rating, and  
voltage rating. Fuses from other manufacturers can be used if they are 600V  
rated and meet the specifications given in the table.  
• Fuses with higher current rating than specified must not be used.  
208 Volt fuses for packaged drive  
Nominal Output  
208 Volt  
Range  
Internal Drive  
Fuse Rating  
External Fuse for  
Disconnect Option  
Base  
Drive  
Drive  
Packag  
Current e Power Frame  
Size  
Type Code1  
Current  
Max Current  
A
HP  
Class  
Class  
Rating  
Rating  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
400A  
400A  
ACS580-0P-04A6-2  
ACS580-0P-06A6-2  
ACS580-0P-07A5-2  
ACS580-0P-10A6-2  
ACS580-0P-017A-2  
ACS580-0P-024A-2  
ACS580-0P-031A-2  
ACS580-0P-046A-2  
ACS580-0P-059A-2  
ACS580-0P-075A-2  
ACH580-PxR-088A-2  
ACH580-PxR-114A-2  
ACH580-PxR-144A-2  
ACH580-PxR-169A-2  
ACH580-PxR-211A-2  
ACH580-PxR-248A-2  
4.6  
6.6  
1
1.5  
2
R1  
R1  
R1  
R1  
R1  
R2  
R2  
R3  
R3  
R4  
R5  
R5  
R6  
R7  
R7  
R8  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
15A  
N/A  
15A  
N/A  
7.5  
15A  
N/A  
10.6  
16.7  
24.2  
30.8  
46.2  
59.4  
74.8  
88  
3
15A  
N/A  
5
30A  
N/A  
7.5  
10  
15  
20  
25  
30  
40  
50  
60  
75  
1002  
30A  
N/A  
40A  
N/A  
80A  
N/A  
80A  
N/A  
100A  
110A  
150A  
200A  
250A  
300A  
350A  
N/A  
N/A  
114  
143  
169  
211  
248  
N/A  
N/A  
N/A  
Class J or RK1  
Class J or RK1  
1) 0P” represents a disconnect and 0P+F255 represents a circuit breaker.  
2) 100 HP @ 230V  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
460 Volt fuses for packaged drive  
19  
Nominal Output  
Range  
480 Volt  
Internal Drive  
Fuse Rating  
External Fuse for  
Disconnect Option  
Base  
Drive  
Frame  
Size  
Drive  
Current  
Package  
Power  
Type Code1  
Current  
Max Current  
Rating  
A
HP  
Class  
Class  
Rating  
ACS580-0P-02A1-4  
ACS580-0P-03A0-4  
ACS580-0P-03A5-4  
ACS580-0P-04A8-4  
ACS580-0P-07A6-4  
ACS580-0P-012A-4  
ACS580-0P-014A-4  
ACS580-0P-023A-4  
ACS580-0P-027A-4  
ACS580-0P-034A-4  
ACS580-0P-044A-4  
ACS580-0P-052A-4  
ACS580-0P-065A-4  
ACS580-0P-077A-4  
ACH580-PxR-096A-4  
ACH580-PxR-124A-4  
ACH580-PxR-156A-4  
ACH580-PxR-180A-4  
2.1  
3
1
1.5  
2
R1  
R1  
R1  
R1  
R1  
R1  
R2  
R2  
R3  
R3  
R3  
R4  
R4  
R4  
R5  
R6  
R7  
R7  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class T  
15A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
15A  
3.5  
4.8  
7.6  
12  
15A  
3
15A  
5
15A  
7.5  
10  
15  
20  
25  
30  
40  
50  
60  
75  
100  
125  
150  
15A  
14  
30A  
23  
30A  
27  
40A  
34  
Class T  
60A  
44  
Class T  
60A  
52  
Class T  
80A  
65  
Class T  
90A  
77  
Class T  
100A  
150A  
200A  
225A  
300A  
96  
Class T  
124  
156  
180  
Class T  
Class T  
Class T  
Class J  
or RK1  
ACH580-PxR-240A-4  
240  
200  
R8  
Class T  
350A  
400A Max  
1) 0P” represents a disconnect and 0P+F255 represents a circuit breaker.  
575 Volt fuses for packaged drive  
Nominal Output  
575 Volt  
Range  
Internal Drive  
Base  
External Fuse for  
Disconnect Option  
Fuse Rating  
Drive  
Package  
Power  
Drive  
Frame  
Size  
Current  
Type Code1, 2  
Current  
Rating  
Max Current  
A
HP  
Class  
Class  
Rating  
ACS580-0P-02A7-6  
ACS580-0P-03A9-6  
ACS580-0P-06A1-6  
ACS580-0P-09A0-6  
ACS580-0P-011A-6  
ACS580-0P-017A-6  
ACS580-0P-022A-6  
ACS580-0P-027A-6  
ACS580-0P-032A-6  
ACH580-PxR-041A-6  
2.7  
3.9  
3.5  
4.8  
7.6  
17  
2
3
R2  
R2  
R2  
R2  
R2  
R2  
R3  
R3  
R3  
R5  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class CC  
Class T  
15A  
15A  
15A  
15A  
30A  
30A  
40A  
40A  
40A  
50A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
6.1  
9
11  
15  
20  
25  
30  
40  
22  
27  
Class T  
32  
Class T  
41  
Class T  
ACS580-0P  
20  
Supplemental Installation Manual for ACS580-0P  
Nominal Output  
Range  
575 Volt  
Internal Drive  
Fuse Rating  
External Fuse for  
Disconnect Option  
Base  
Drive  
Frame  
Size  
Drive  
Current  
Package  
Power  
Type Code1, 2  
Current  
Max Current  
A
HP  
Class  
Class T  
Class  
Rating  
Rating  
ACH580-PxR-052A-63  
ACH580-PxR-062A-6  
ACH580-PxR-077A-6  
ACH580-PxR-099A-6  
ACH580-PxR-125A-6  
ACH580-PxR-144A-6  
ACH580-PxR-180A-4  
ACH580-PxR-240A-4  
52  
62  
50  
60  
R5  
R5  
R5  
R7  
R7  
R8  
R2  
R2  
80A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
Class T  
80A  
77  
75  
100A  
150A  
175A  
200A  
300A  
350A  
N/A  
99  
100  
125  
150  
150  
200  
N/A  
125  
144  
180  
240  
N/A  
N/A  
N/A  
Class J  
or RK1  
400A Max  
1) 0P” represents a disconnect and 0P+F255 represents a circuit breaker.  
2) ACS580-0P-xxxx-x+F255 is rated 600Y/347V unless otherwise specified. For use on a solidly grounded Wye  
source only.  
3) ACS580-0P-xxxx-x+F255 supports Delta network configuration.  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
21  
Operation  
This information is unique to ACS580 input disconnect configurations (0P). Refer to  
the Operation instructions on page 45 for all other information.  
Input disconnect configuration  
The ACS580 with Input Disconnect is an ACS580 AC adjustable frequency drive  
packaged with an input disconnect switch or circuit breaker, and with a door  
interlocked, external operating handle. The operating handle can be padlocked in  
the OFF position (padlock not supplied). Enclosure options are UL (NEMA) Type  
1UL (NEMA) Type 12 (NEMA 1 NEMA 12).  
The following is a typical power diagram.  
Disconnect Switch  
or Circuit Breaker  
Drive With Input Disconnect  
ACS580  
Drive  
3 Phase  
Input Power  
Motor  
3
3
Drive Input  
Fuse  
The following shows the front view of the ACS580 Vertical Packaged Drive  
configuration and identifies the major components.  
Type 12 Hood  
Drive Control  
Panel Behind Clear  
Door  
Drive Control  
Panel  
Operating Handle  
for Disconnect  
or Circuit Breaker  
Switch  
P1-P4  
P1-P4  
(Px1-1, Px1-2,  
Px1-3, Px1-4)  
(Px12-1, Px12-2,  
Px12-3, Px12-4)  
ACS580-0P  
22  
Supplemental Installation Manual for ACS580-0P  
Dimensions  
P1 Type 1  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
23  
P1 Type 12  
ACS580-0P  
24  
Supplemental Installation Manual for ACS580-0P  
P2 Type 1  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
25  
P2 Type 12  
ACS580-0P  
26  
Supplemental Installation Manual for ACS580-0P  
P3 Type 1  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
27  
P3 Type 12  
ACS580-0P  
28  
Supplemental Installation Manual for ACS580-0P  
P4 Type 1  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
29  
P4 Type 12  
ACS580-0P  
30  
Supplemental Installation Manual for ACS580-0P  
PB1 Type 3R  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
31  
PB2 Type 3R  
ACS580-0P  
32  
Supplemental Installation Manual for ACS580-0P  
PB3 Type 1  
ACS580-0P  
Supplemental Installation Manual for ACS580-0P  
33  
PB3 Type 12  
ACS580-0P  
34  
Supplemental Installation Manual for ACS580-0P  
[Page intentionally left blank]  
ACS580-0P  
ABB Inc.  
16250 West Glendale Drive  
New Berlin, WI 53151  
USA  
Telephone +1 800 752-0696  
Fax  
+1 262 785-0397  
Internet  

Nokia 3330 User Manual
Motorola MC50 User Manual
JVC XL FV323TN User Manual
JVC KD G201 User Manual
Jensen MR 720 User Manual
HP Hewlett Packard DAT 72 User Manual
Hamilton Beach 40618 User Manual
Cuisinart DCC 2900 User Manual
Blackberry 8700 Series User Manual
Audiovox Prestige SP11CDP User Manual