Trane Lo User Manual

Installation  
Operation  
Maintenance  
UniTrane® Fan-Coil Room Conditioners  
Force Flo™ Cabinet Heaters  
Sizes 02-12  
Low Vertical Fan-Coils  
Sizes 03-06  
Models  
“LO” Design Sequence and Later  
April 2000  
UNT-IOM-6  
Supercedes UNT-IOM-5  
General Information  
UniTrane® fan-coil and Force Flo™ cabinet heaters units are single  
room units with load capabilities of 200 to 1200 cfmꢀ See Figure 1  
for unit componentsꢀ Fan-coil units are available as 2-pipe with or  
without electric heat (one hydronic circuit) or 4-pipe (two hydronic  
circuits)ꢀ Force Flo™ units feature 2-pipe hydronic coils, electric heat  
only, or steam onlyꢀ Also, units feature a variety of factory piping  
packagesꢀ See the Appendix on page 100 for more information on  
available factory-installed piping packagesꢀ  
Three control options are available with the UniTrane® fan-coil and  
Force Flo™ cabinet heater unitsꢀ  
1ꢀ fan mode switch  
2ꢀ Tracer® ZNꢀ010 and ZNꢀ510, ZNꢀ520  
3ꢀ terminal unit controller (TUC)  
All control options are available as unit or wall mountedꢀ Units with a  
Tracer® ZNꢀ010, ZNꢀ510, ZNꢀ520 or TUC also feature a split combina-  
tion: unit mounted fan mode switch with a wall mounted setpoint dialꢀ  
The Tracer® controllers (ZNꢀ010, ZNꢀ510 and ZNꢀ520) utilize binary  
outputs to operate 2-position control valves, supply fan/s, 2-position  
dampers, and electric heatꢀ  
The TUC utilizes binary outputs to control the fan and optional  
auxiliary heatꢀ In addition, it operates 2-position or 3 wire floating  
point control valves and the fresh air damperꢀ  
Available supply and return openings vary with each cabinet styleꢀ In  
addition, a fresh air opening with either a manual or motorized air  
damper is an available optionꢀ See pages 4-5 for available cabinet  
stylesꢀ  
Hydronic coil  
Piping package  
Control panel  
*Main drain pan  
Supply fan(s)  
Throwaway filter  
Fan motor(s)  
*Auxiliary  
drain pan  
*Featured on fan-coils only  
Figure 1. Main components of a fan-coil or cabinet heater unit.  
UNT-IOM-6  
3
Cabinet Styles  
Model B  
Vertical Cabinet  
Model C  
Horizontal Concealed  
Model D  
Horizontal Cabinet  
Model E  
Horizontal Recessed  
Model F  
Wall Hung Cabinet**  
4
UNT-IOM-6  
Model J  
Vertical Slope Top Cabinet  
M
Low Vertical Cabinet*  
Model K  
Low Vertical Concealed*  
Model M  
Inverted V
Model N  
Inverted Vertical Recessed**  
*Fan-coil only  
**Force Flo cabinet heater only  
UNT-IOM-6  
5
Each UniTrane® fan-coil and Force Flo ™ cabinet heater has a  
multiple character model number unique to that particular unitꢀ To  
determine a unit’s specific  
Model Number  
Description  
options, reference the model  
number on the unit nameplate  
on the fan scrollꢀ The unit  
nameplate also identifies the  
serial number, sales order  
number, and installation and  
operating specificationsꢀ See  
Figure 2 for the nameplate  
locationꢀ  
Reference pages 7-8 for a  
detailed explanation of the  
model numberꢀ  
Figure 2. The unit nameplate is  
on the fan scroll.  
Complete the installation checklist on page 13 to ensure proper and  
safe operationꢀ  
6
UNT-IOM-6  
Model Number Description  
J
K
L
With piping, RH  
With piping, LH  
With piping, RH, extꢀ end pocket  
With piping, RH, extꢀ end pocket  
G
Keylock panel & access door  
w/leveling feet  
Digits 1 & 2 Unit Type  
FC  
FF  
M
Digit 17 Motor  
Digit 3 Model  
A
B
Free discharge  
High static  
Digits 10 & 11 Design Sequence  
LO  
A
Vertical concealed  
Vertical cabinet  
concealed  
B
CHorizontal  
Digit 12 Inlet  
D
E
F
H
J
K
L
M
N
Horizontal cabinet  
Horizontal recessed  
Vertical wall hung*  
Vertical recessed  
Vertical slope top  
Low vertical concealed  
Low vertical cabinet  
Inverted vertical cabinet*  
Inverted vertical recessed*  
Digit 18 Coil  
A
B
Front toe space  
Front bar grille  
A
B
C4  
D
E
F
G
H
J
K
L
M
N
P
2 row cooling/heating  
3 row cooling/heating  
row  
CFront  
stamped  
louver  
cooling/heating  
D
E
F
G
H
Bottom stamped louver  
Bottom toe space  
Back duct collar  
Open return  
2 row cooling, 1 row heating  
2 row cooling, 2 row heating  
3 row cooling, 1 row heating  
2 row cooling or heating only  
3 row cooling or heating only  
4 row cooling or heating only  
2 row cooling/heating, elecꢀ heat  
3 row cooling/heating, elecꢀ heat  
4 row cooling/heating, elecꢀ heat  
Electric heat only, 1 stage  
2 row cooling/heating,  
1 row heating  
Back stamped louver  
Digit 13 Fresh Air Damper  
Digit 4 Development Sequence  
B
0
None  
A
B
Manual, bottom opening  
Manual, back opening  
CManual,  
top  
opening  
Digits 5–7 Unit Size  
D
E
F
Auto, 2 posꢀ, bottom opening  
Auto, 2 posꢀ, back opening  
Auto, 2 posꢀ top opening  
Auto, economizer,  
020  
030  
040  
060  
080  
100  
120  
200 cfm  
300 cfm  
400 cfm  
600 cfm  
800 cfm  
1000 cfm  
1200 cfm  
Q
R
2 row cooling/heating,  
2 row heating  
3 row cooling/heating,  
1 row heating  
G
bottom opening  
U
V
W
Electric heat only, 2 stage  
Electric heat only, low kw, 1 stage  
Steam coil  
H
J
K
L
Auto, economizer, back opening  
Auto, economizer, top opening  
No damper, bottom opening  
No damper, back opening  
No damper, top opening  
Digit 19 Coil Fin Series  
144  
M
Digit 8 Unit Voltage  
2
1
2
3
4
5
6
7
8
9
A
B
115/60/1  
208/60/1  
277/60/1  
230/60/1  
208/60/3  
230/6j0/3  
480/60/3  
110-120/50/1  
220-240/50/1  
220-240/50/3  
380-415/50/3  
Digit 14 Outlet  
Digit 20 Air Vent  
A
Front duct collar  
A
M
Automatic  
Manual  
B
Front bar grille  
stamped  
CFront  
louver  
D
E
F
G
H
J
Front quad grille  
Bottom duct collar  
Bottom stamped louver  
Top quad grille  
Top bar grille  
Digits 21, 22, & 23 Electric Heat kW  
[208 V kW derate in brackets]  
000  
010  
015  
020  
025  
030  
040  
045  
050  
060  
070  
075  
080  
100  
105  
110  
120  
135  
150  
None  
1ꢀ0 [0ꢀ75]  
1ꢀ5 [1ꢀ1]  
2ꢀ0 [1ꢀ5]  
2ꢀ5 [1ꢀ9]  
3ꢀ0 [2ꢀ2]  
4ꢀ0 [3ꢀ0]  
4ꢀ5 [3ꢀ3]  
5ꢀ0 [3ꢀ7]  
6ꢀ0 [4ꢀ4]  
7ꢀ0 [5ꢀ3]  
7ꢀ5 [5ꢀ7]  
8ꢀ0 [6ꢀ0]  
10ꢀ0  
Top duct collar  
Bottom bar grille  
K
Digit 9 Piping System Placement  
A
Digit 15 Color  
W/o piping, RH connꢀ,  
w/o auxꢀ drain pan  
W/o piping, LH connꢀ,  
w/o auxꢀ drain pan  
0
1
2
None  
Deluxe beige  
Soft dove  
B
3
Cameo white  
Driftwood grey  
Stone grey  
CW/o  
piping,  
RH  
connꢀ,  
4
5
6
w/ auxꢀ drain pan  
W/o piping, LH connꢀ,  
w/ auxꢀ drain pan  
W/o piping, RH connꢀ,  
w/o auxꢀ drain pan,  
extꢀ end pocket  
W/o piping, LH connꢀ,  
w/o auxꢀ drain  
W/o piping, RH connꢀ,  
w/ auxꢀ drain pan,  
extꢀ end pocket  
D
E
Rose mauve  
10ꢀ5 [7ꢀ9]  
11ꢀ0 [9ꢀ0]  
12ꢀ0  
13ꢀ5 [10ꢀ2]  
15ꢀ0  
Digit 16 Tamperproof Locks  
& Leveling Feet  
F
0
None  
A
B
Keylock panel  
Keylock access door  
panel  
G
180  
200  
18ꢀ0 [13ꢀ5]  
20ꢀ0 [15ꢀ0]  
CKeylock  
&
access  
door  
D
E
F
Leveling feet  
H
W/o piping, LH connꢀ,  
w/ auxꢀ drain pan, extꢀ end  
pocket  
Keylock panel with leveling feet  
Keylock access door  
w/leveling feet  
*Force Flo™ cabinet heater only  
UNT-IOM-6  
7
R
7” falseback  
CBall  
valve  
setter  
supply  
&T  
a8utofalseback circuit  
Digit 24 Reheat  
0
A
B
None  
Steam  
Hot water  
D
E
F
Ball valve supply & return  
w/strainers & unions  
Ball valve supply & manual circuit  
setter w/strainers & unions  
Ball valve supply & auto circuit  
setter w/strainers & unions  
Digit 40 Main Auto Circuit Setter GPM  
0
None  
0ꢀ5  
0ꢀ75  
1ꢀ0  
1ꢀ5  
2ꢀ0  
2ꢀ5  
3ꢀ0  
3ꢀ5  
4ꢀ0  
K
L
4ꢀ5  
5ꢀ0  
6ꢀ0  
7ꢀ0  
8ꢀ0  
A
B
C
D
E
F
G
H
J
M
N
P
Q
R
T
Digit 25 Disconnect Switch  
0
None  
D
With disconnect  
9ꢀ0  
10ꢀ0  
11ꢀ0  
12ꢀ0  
Digit 30 Control Type  
Digit 26 Filter  
A
Fan Speed Switch  
0
1
2
3
4
5
6
7
8
None  
1” TA  
U
CTUC  
D
E
F
TUC w/Trane ICS  
Tracer® ZNꢀ010  
Tracer® ZNꢀ510  
Tracer® ZNꢀ520  
1” TA pltdꢀ media  
1” TA + 1 extra  
1” TA pltdꢀ media + 1 extra  
1” TA + 2 extra  
1” TA pltdꢀ media + 2 extra  
1” TA + 3 extra  
1” TA pltdꢀ media + 3 extra  
Digit 41 Auxiliary Auto Circuit Setter GPM  
G
K
L
4ꢀ5  
5ꢀ0  
6ꢀ0  
7ꢀ0  
8ꢀ0  
9ꢀ0  
10ꢀ0  
11ꢀ0  
12ꢀ0  
0
None  
0ꢀ5  
0ꢀ75  
1ꢀ0  
1ꢀ5  
2ꢀ0  
2ꢀ5  
3ꢀ0  
3ꢀ5  
4ꢀ0  
A
B
C
D
E
F
G
H
J
M
N
P
Q
R
T
Digit 31 Control Options  
D
K
V
Unit mtdꢀ fan mode switch (OHML)  
Wall mtdꢀ fan mode switch (OHML)  
Unit mtdꢀ zone sensor, w/SP  
rotary, & fan mode switch  
(OAHML),  
Digit 27 Main Control Valve  
0
None  
U
A
B
C2  
D
E
F
G
H
J
2 way, 2 posꢀ, NꢀOꢀ (25 psig)  
3 way, 2 posꢀ, NꢀOꢀ (30 psig)  
way,  
W
Wall mtdꢀ zone sensor w/  
SP rotary, & fan mode switch  
(OAHML),  
2
posꢀ,  
NꢀC (25  
psig)  
3 way, 2 posꢀ, NꢀCꢀ (15 psig)  
2 way, 2 posꢀ, NꢀOꢀ (50 psig)  
3 way, 2 posꢀ, NꢀOꢀ (50 psig)  
2 way, 2 posꢀ, NꢀCꢀ (50 psig)  
3 way, 2 posꢀ, NꢀCꢀ (50 psig)  
2 way, modꢀ, Cv = 0ꢀ7 (50 psig)  
3 way, modꢀ, Cv = 0ꢀ7 (50 psig)  
2 way, modꢀ, Cv = 1ꢀ5 (50 psig)  
3 way, modꢀ, Cv = 1ꢀ5 (50 psig)  
2 way, modꢀ, Cv = 2ꢀ5 (50 psig)  
3 way, modꢀ, Cv = 2ꢀ5 (50 psig)  
2 way, modꢀ, Cv = 4ꢀ0 (50 psig)  
3 way, modꢀ, Cv = 4ꢀ0 (50 psig)  
X
Unit mtdꢀ fan mode switch, wall  
mtdꢀ setpoint dial zone sensor  
Digit 42 Subbase  
0
None  
A
B
C4”  
D
E
2” height  
3” height  
height  
5” height  
6” height  
7” height  
Digit 32-34 Future Control Options  
K
L
Digit 35 Control Function 3  
M
N
P
Q
R
F
0
2
None  
Condensate overflow detection  
Digit 43 Recessed Flange  
0
None  
Digit 36 Control Function 4  
A
Recessed flange  
0
2
None  
Low temperature detection  
Digit 28 Auxiliary Control Valve  
0
None  
Digit 44 Wallbox  
A
B
C2  
D
E
F
G
H
J
2 way, 2 posꢀ, NꢀOꢀ (25 psig)  
3 way, 2 posꢀ, NꢀOꢀ (30 psig)  
way,  
0
None  
Digits 37 & 38 Future Control Options  
ꢀ NꢀC (25 psig)  
A
Anodized  
2
posꢀ,  
3 way, 2 posꢀ, NꢀCꢀ (15 psig)  
2 way, 2 posꢀ, NꢀOꢀ (50 psig)  
3 way, 2 posꢀ, NꢀOꢀ (50 psig)  
2 way, 2 posꢀ, NꢀCꢀ (50 psig)  
3 way, 2 posꢀ, NꢀCꢀ (50 psig)  
2 way, modꢀ, Cv = 0ꢀ7 (50 psig)  
3 way, modꢀ, Cv = 0ꢀ7 (50 psig)  
2 way, modꢀ, Cv = 1ꢀ5 (50 psig)  
3 way, modꢀ, Cv = 1ꢀ5 (50 psig)  
2 way, modꢀ, Cv = 2ꢀ5 (50 psig)  
3 way, modꢀ, Cv = 2ꢀ5 (50 psig)  
2 way, modꢀ, Cv = 4ꢀ0 (50 psig)  
3 way, modꢀ, Cv = 4ꢀ0 (50 psig)  
Digit 39 Recessed Options  
0
None  
A
B
Standꢀ 5/8” recessed panel  
2” projection panel  
C2ꢀ5”  
D
E
projection  
panel  
K
L
3” projection panel  
3ꢀ5” projection panel  
4” projection panel  
4ꢀ5” projection panel  
5” projection panel  
5ꢀ5” projection panel  
6” projection panel  
2” falseback  
M
N
P
Q
R
F
G
H
J
K
L
M
N
P
3” falseback  
4” falseback  
5” falseback  
6” falseback  
Digit 29 Piping Package  
0
None  
A
B
Ball valve supply & return  
Ball valve supply & manual circuit  
setter return  
Q
8
UNT-IOM-6  
Receiving and Handling  
UniTrane® fan-coil and Force Flo™ cabinet heaters ship in individual  
cartons for maximum protection during shipment and for handling and  
storage easeꢀ Each carton has tagging information such as the  
model number, sales order number, serial number, unit size, piping  
connections, and unit style to help properly locate the unit in the floor  
planꢀ If specified, the unit will ship with tagging designated by the  
customerꢀ  
Complete the following checklist before accepting delivery of units to  
detect any shipping damageꢀ  
o
1ꢀ Inspect each piece of the shipment before accepting itꢀ  
Check for rattles, bent carton corners, or other visible indications of  
shipping damageꢀ  
o
2ꢀ If the carton appears damaged, open it immediately and  
inspect the contents before acceptingꢀ Do not refuse the shipmentꢀ  
Make specific notations concerning the damage on the freight billꢀ  
Check the unit casing, fan rotation, coils, condensate pan, filters, and  
all options or accessoriesꢀ  
o
3ꢀ Inspect the unit for concealed damage and missing compo-  
nents soon after delivery and before storingꢀ Report concealed  
damage to the delivering carrier within the allotted time after  
delivery (check with the carrier on the allotted time to submit a  
claim)ꢀ  
o
4ꢀ Do not move damaged material from the receiving location if  
possibleꢀ It is the receiver’s responsibility to provide reasonable  
evidence that concealed damage did not occur after deliveryꢀ  
o
5ꢀ Do not continue to unpack shipment if it appears damagedꢀ  
Retain all internal packing, cartons, and crateꢀ Take photos of the  
damaged material if possibleꢀ  
o
6ꢀ Notify the carrier’s terminal of damage immediately by phone  
and mailꢀ Request an immediate joint inspection of the damage by  
the carrier and consigneeꢀ  
o
7ꢀ Notify the Trane sales representative of the damage and  
arrange for repairꢀ Have the carrier inspect the damage before begin-  
ning any repairs to the unitꢀ  
UNT-IOM-6  
9
This unit is intended for indoor use onlyꢀ To protect the unit from  
damage due to the elements and prevent it from possibly becoming a  
contaminant source for IAQ problems, store the unit indoorsꢀ If indoor  
storage is not possible, the Trane Company makes the following  
provisions for outdoor storage:  
Jobsite Storage  
1ꢀ Place the unit(s) on a dry surface or raised off the ground to assure  
adequate air circulation beneath unit and to assure that no portion of  
the unit contacts standing water at any timeꢀ  
2ꢀ Cover the entire unit with a canvas tarp onlyꢀ Do not use clear,  
black or plastic tarps as they may cause excessive moisture conden-  
sation and equipment damageꢀ  
Note: Wet interior unit insulation can become an amplification site for  
microbial growth (mold), which may cause odors and health-related  
indoor air quality problemsꢀ If there is visable evidence of microbial  
growth (mold) on the interior insulation, remove and replace the  
insulation prior to operating the systemꢀ Refer to the “Inspecting and  
Cleaning the Internal Insulation” section on page 123 for more  
informationꢀ  
10  
UNT-IOM-6  
Complete the following checklist before installing the unitꢀ  
1ꢀ Clearances  
Installation  
Considerations  
o
Allow adequate space for free air circulation, service clearances,  
piping and electrical connections, and any necessary ductworkꢀ For  
specific unit dimensions, refer to the submittalsꢀ Allow clearances  
according to local and national electric codesꢀ See the following  
section on “Service Access” and refer to Figure 3 on page 12 for  
recommended service and operating clearancesꢀ Provide removable  
panels for concealed unitsꢀ  
o
2ꢀ Structural Support  
The floor should be strong enough to adequately support floor  
mounted unitsꢀ The installer is responsible to supply adequate  
support rods for installation of ceiling unitsꢀ  
o
3ꢀ Level  
If necessary, prepare the floor or ceiling to ensure the unit installation  
is level (zero tolerance) in both horizontal axis to allow proper  
operationꢀ  
Set the unit level using the chassis end panels as a reference pointꢀ  
Do not use the coil or drain pan as the reference point since the coil  
is pitched and the drain pan has an inherent positive slope to provide  
proper drainageꢀ  
o
4ꢀ Condensate Line  
A continuous pitch of 1 inch per 10 feet of condensate line run is  
necessary for adequate condensate drainageꢀ  
o
5ꢀ Wall and Ceiling Openings  
Recessed units only:  
Refer to the submittal for specific dimensions of wall or ceiling  
openings before attempting to install the unitꢀ  
Horizontal concealed units only:  
The installation of horizontal concealed units must meet the require-  
ments of the National Fire Protection Association (NꢀFPAꢀ) Stan-  
dard 90A or 90B concerning the use of concealed ceiling spaces as  
return air plenumsꢀ  
o
6ꢀ Exterior  
Touch up painted panels if necessaryꢀ If panels need paint, sanding  
is not necessaryꢀ However, clean the surface of any oil, grease, or  
dirt residue so the paint will adhereꢀ Purchase factory approved touch  
up epoxy paint from your local Trane Service Parts Center and applyꢀ  
UNT-IOM-6  
11  
Service access is available from the front on vertical units and from  
the bottom on horizontal unitsꢀ Cabinet and recessed units have  
removable front or bottom panels to allow access into the unitꢀ See  
Figure 3 for recommended service and operating clearancesꢀ  
Service  
Access  
Units have either right or left hand pipingꢀ Reference piping locations  
by facing the front of the unit (airflow discharges from the front)ꢀ The  
control panel is always on the end opposite the pipingꢀ  
The unit has a modular fan board assembly that is easy to removeꢀ  
Also, the main drain pan is easily removable for cleaningꢀ See the  
“Maintenance” section beginning on page 88 for more details on  
servicingꢀ  
8ꢀ5 inꢀ  
both sides  
12 inꢀ  
both sides  
24 inꢀ  
Vertical
Conceal
Recessed  
A
Vertical or Low  
36 inꢀ  
Vertical Cabinet  
A
3 inꢀ  
12 inꢀ  
both sides  
8ꢀ5 inꢀ  
both sides  
24 inꢀ  
C
Horizontal Concealed  
or Recessed  
28 inꢀ  
6 inꢀ  
Horizontal  
Cabinet  
B
28 inꢀ  
A- Front Access or Front Free Discharge  
B- Control Access Door  
C- Front Free Discharge  
D- Back Louvered Return  
Figure 3. Recommended Service and Operating Clearances  
12  
UNT-IOM-6  
Installation Checklist  
The following checklist is only an abbreviated guide to the detailed  
installation procedures given in this manualꢀ Use this list to ensure all  
necessary procedures are completeꢀ For more detailed information,  
refer to the appropriate sections in this manualꢀ  
WARNING: Allow rotating fan to stop before  
servicing equipment. Failure to do so may cause severe  
personal injury or death.  
!
o
o
1ꢀ Inspect the unit for shipping damageꢀ  
2ꢀ Level installation location to support the unit weight ad-  
equatelyꢀ Make all necessary wall or ceiling openings to allow  
adequate air flow and service clearancesꢀ  
o
3ꢀ Ensure the unit chassis is levelꢀ  
CAUTION: The unit must be installed level (zero  
!
tolerance) in both horizontal axis for proper operation.  
Failure to do so may result in condensate management  
problems such as standing water inside the unit. Stand-  
ing water and wet surfaces may result in microbial  
growth (mold) in the drain pan that may cause unpleasnt  
odors and serious health-related indoor air quality prob-  
lems.  
o
4ꢀ Secure the unit and any accessory items properly to the  
wall or ceiling support rodsꢀ  
o
o
5ꢀ Complete piping connections correctlyꢀ  
6ꢀ Check field sweat connections for leaks and tighten the  
valve stem packing, if necessaryꢀ  
o
7ꢀ Install the auxiliary drain pan properly under piping package  
on fan-coil unitsꢀ  
o
8ꢀ Pitch condensate drain line 1 inch drop per 10 feet of line  
run on fan-coil unitsꢀ  
UNT-IOM-6  
13  
o
unitsꢀ  
9ꢀ Complete condensate drain line connections on fan-coil  
o
10ꢀ Install automatic changeover sensor option on the  
supply water lineꢀ  
o
11ꢀ Install automatic electric heat lockout switch option on  
the supply water lineꢀ  
o
12ꢀ Install condensate overflow switch option correctly on  
the auxiliary drain panꢀ  
o
o
o
13ꢀ Install the low temperature detection device option correctlyꢀ  
14ꢀ Complete all necessary duct connectionsꢀ  
15ꢀ Complete all interconnection wiring for the wall mounted fan  
mode switch or zone sensor per the wiring schematic and guidelines  
established in the “Wall Mounted Control Interconnection Wiring”  
section on page 35ꢀ  
o
16ꢀ Install the wall mounted fan mode switch, or zone sensor  
module options properlyꢀ  
o
17ꢀ Connect electrical supply power according to the NEC and  
unit wiring diagramsꢀ  
o
19ꢀ Remove any miscellaneous debris, such as sheetrock, that  
may have infiltrated the unit during constructionꢀ  
o
20ꢀ Replace the air filter as requiredꢀ  
14  
UNT-IOM-6  
Installing the Unit  
Before beginning installation, refer to Table 1 on page 17 for unit  
weights and Figure 3 on page 12 for service and operating clearancesꢀ  
In addition, refer to the unit submittal for installation detailsꢀ  
CAUTION: Do not allow electrical wire to fall  
!
between the unit and installation surface. Failure to  
comply may cause electrical shorts or difficulty in access-  
ing wires.  
Install vertical units in an upright position using the 5/8 inch diameter  
double key slot hanger holes, located on the back of unitꢀ The hanger  
holes allow a maximum shank size of 5/16 inch diameter threaded  
rods or lag screws (installer provides)ꢀ Follow the installation proce-  
dure belowꢀ  
Vertical Units  
1ꢀ Prepare wall openings for recessed unitsꢀ Reference unit submittal  
for each unit size dimensionsꢀ  
2ꢀ If the unit has leveling legs, adjust them correctly to level unitꢀ  
3ꢀ Mark the position of the keyslot hanger holes on the wall according  
to the dimensions given in Figure 4 for each unit sizeꢀ Align the  
hole locations evenlyꢀ  
Cabinet & Concealed Units  
Size  
02  
03  
04  
06  
08  
10  
12  
L (in>)  
21 1/4  
21 1/4  
26 1/4  
35 3/4  
44 1/4  
63 1/4  
63 1/4  
L
Low Vertical Cabinet & Concealed  
Size  
03  
04  
L (in>)  
26 1/4  
35 3/4  
44 1/4  
06  
L
15ꢀ5 inꢀ  
12ꢀ19 inꢀ  
7ꢀ5 inꢀ  
Floor Level  
Floor Level  
Figure 4. Keyslot Hanger Hole Locations  
UNT-IOM-6  
15  
4ꢀ Insert the threaded rods or lag screws in the wall before setting the  
unit in placeꢀ  
5ꢀ Remove the front panel (cabinet unit only) by lifting it upwardꢀ  
6ꢀ Position the hanger holes, located on the back of the unit, over the  
rod or lag screw heads, pushing the unit downward to properly  
positionꢀ  
7ꢀ Complete piping and wiring connections, in addition to any neces-  
sary ductwork to the unit as instructed in the following sectionsꢀ  
Ensure that the auxiliary drain pan is in position on fan-coil unitsꢀ  
8ꢀ Install the front panel before starting the unitꢀ  
On cabinet units, replace the front panel by aligning the bottom tabs  
on the unit with the respective slots on the panel bottomꢀ Align the  
top edge of the unit with the panelꢀ  
On recessed units, install the front panel by aligning and locking  
together the interlocking support channel of the panel and unitꢀ While  
holding the panel against the unit, tighten the screws at the top of the  
panel until it fits tight against the unit’s frontꢀ Do not over tighten the  
screwsꢀ  
CAUTION: All unit panels and filters must be in  
place prior to unit start-up. Failure to have panels and  
filters in place may cause motor overload.  
!
Install horizontal units suspended from the ceiling using the four 5/8  
inch diameter double key slot hanger holes, located on the top of the  
unitꢀ The hanger holes allow a maximum shank size of 5/16 inch  
diameter threaded rods or lag screws (installer provided)ꢀ Follow the  
installation procedure belowꢀ  
Horizontal Units  
Note: Follow the requirements of National Fire Protection Association  
(NFPA) Standard 90A or 90B, concerning the use of concealed  
ceiling spaces as return air plenumsꢀ  
1ꢀ Prepare the ceiling opening for recessed unitsꢀ Reference the unit  
submittals for each unit size dimensionsꢀ  
16  
UNT-IOM-6  
2ꢀ Position and install the suspension rods or a suspension device  
(supplied by installer) according to the unit size dimensions in  
Figure 4 on page 15ꢀ Also refer to the weight range chart given in  
Table 1ꢀ  
3ꢀ On cabinet units, remove the bottom panel by using a 5/32 inch  
Allen wrench to unscrew fastenersꢀ Swing the panel down and lift  
outwardꢀ  
4ꢀ Level the unit by referencing the chassis end panelsꢀ Adjust the  
suspension deviceꢀ  
5ꢀ Complete piping and wiring connections, in addition to any neces  
sary ductwork as instructed in the following sectionsꢀ Ensure that  
the auxiliary drain pan is in position on fan-coil unitsꢀ  
6ꢀ Install the bottom panel before starting the unitꢀ  
7ꢀ Ensure condensate drain line is pitched 1 inch per 10 feet of pipe  
away from fan-coil unitꢀ  
Table 1ꢀ Unit Operating Weights, pounds (kg)  
Unit  
Size Models  
Cabinet  
Concealed  
Models  
Recessed  
Models  
Low Vertical  
Cabinet Models  
Low Vertical  
Concealed  
Models  
02  
03  
04  
06  
08  
10  
12  
84 (38)  
84 (38)  
68 (31)  
68 (31)  
96 (44)  
123 (56)  
131 (59)  
182 (83)  
182 (83)  
68 (31)  
68 (31)  
NA  
NA  
112 (51)  
139 (63)  
148 (67)  
NA  
96 (44)  
123 (56)  
131 (59)  
NA  
112 (51)  
139 (63)  
148 (67)  
200 (91)  
200 (91)  
78 (35)  
118 (54)  
129 (59)  
243 (110)  
243 (110)  
NA  
NA  
NA  
NA  
Note: All weights are approximateꢀ Individual weights may vary depending upon the unit’s optionsꢀ  
UNT-IOM-6  
17  
Cabinet units:  
Install the bottom panel by placing the hinged end on the unit’s hinged  
end (always at the return end of the unit)ꢀ See Figure 4 on page 15 for  
keyslot hanger hole locationsꢀ Swing the panel upward into positionꢀ  
Tighten the panel to the unit with the fasteners providedꢀ Do not over-  
tighten the fastenersꢀ  
Recessed units:  
See Figure 5 on page 19 and follow the procedure belowꢀ  
· Insert the mounting bolts through the panel brackets of the trim ring  
and secure to the hanger holes on the unitꢀ Tighten the mounting  
bolts to pull the trim ring snug against the finished ceilingꢀ  
· Install the bottom panel by placing the hinged end on the trim ring  
hinged end (always at the unit’s return end)ꢀ  
· Adjust the inner duct of the expansion collar (on units with a bottom  
return) to ensure a tight fit against the insulation located on the  
perimeter of the bottom panel’s return louverꢀ  
· Safety chain assembly: close s-hook on each end of chainꢀ Insert s-  
hooks through holes in unit and doorꢀ Close s-hook on doorꢀ  
· Insert retaining screws through bottom panel door and place  
retaining rings on screwsꢀ  
· Swing the bottom panel upward into positionꢀ Hook the safety chain  
to the bottom panel and the unitꢀ Tighten the panel to the unit with  
the fasteners providedꢀ Do not over tighten the removable front  
access panelꢀ  
CAUTION: All unit panels and filters must be in  
place prior to unit start-up. Failure to have panels and  
filters in place may cause motor overload.  
!
Note: The trim ring assembly cannot accomodate unlevel ceilingsꢀ  
18  
UNT-IOM-6  
Figure 5. Trim ring assembly installation.  
UNT-IOM-6  
19  
Startup Checklist  
o
o
1ꢀ Ensure all panels are in placeꢀ  
2ꢀ Tighten unions adequately if unit has a factory deluxe piping  
packageꢀ  
o
3ꢀ Properly vent the hydronic coil to allow water flow through the  
unitꢀ  
o
4ꢀ Set water flow to the unit properly if unit piping has the circuit  
setter valveꢀ  
o
5ꢀ Check strainers (if supplied) for debris after applying system  
waterꢀ  
o
6ꢀ Install the auxiliary drain pan and route the main drain pan  
hoses to the auxiliary drain pan on vertical fan-coil unitsꢀ  
o
o
o
7ꢀ Ensure all grille options are in placeꢀ  
8ꢀ Ensure the air filter is in placeꢀ  
9ꢀ Set the damper position to allow the fresh air requirement on  
units with a fresh air damperꢀ  
Note: Some circumstances may require the unit to run before building  
construction is completeꢀ These operating conditions may be beyond  
the design parameters of the unit and may adversely affect the unitꢀ  
Insulate all cold surfaces to prevent condensationꢀ Moisture mixed  
with accumulated dirt and organic matter may create an amplification  
site for microbial growth (mold) causing unpleasant odors and health-  
related indoor air quality (IAQ) problemsꢀ  
External Insulating  
Requirements  
The Trane Company recommends field-insulation of the following  
areas to prevent potential condensate and IAQ problems:  
1ꢀ Supply and return water piping connections  
2ꢀ Condensate drain lines and connections  
3ꢀ Fresh air intake duct connections  
4ꢀ Discharge duct connections  
5ꢀ Wall boxes  
20  
UNT-IOM-6  
Piping  
Before installing field piping to the coil, consider the following ꢀ  
Units with  
Hydronic Coil  
Connections Only  
Piping Considerations  
· All coil connections are 5/8 inch OꢀDꢀ (or 1/2 inch nominal) female  
copper connectionsꢀ  
· The supply and return piping should not interfere with the auxiliary  
drain pan or condensate lineꢀ See “Connecting the Condensate  
Drain” section on page 25 for more detailed informationꢀ  
· The installer must provide adequate piping system filtration and  
water treatmentꢀ  
· Condensate may be an issue (fan-coils only) if field piping does not  
have a control valveꢀ  
Refer to Figure 6 for supply and return header locationsꢀ  
CAUTION: When using a field supplied piping  
!
package in a fan-coil unit, allow sufficient room to install  
the auxiliary drain pan. In addition, piping package must  
not extend over edges of auxiliary drain pan.  
2-Pipe  
4-Pipe (C)  
2-Pipe  
4-Pipe (C)  
R
S
R
S
R
R
4-Pipe (H)  
4-Pipe (H)  
S
Air flow  
S
Air flow  
Right end view of coil  
Left end view of coil  
Figure 6. Supply and return header locations on the hydronic  
coil.  
Connecting field piping to coil:  
1ꢀ Slide a 1/2 inch sweat connection coupling (installer provided) onto  
the coil headersꢀ  
2ꢀ Remove the auxiliary drain pan, if it is in place, to prevent exposure  
to dripping solder or excessive temperaturesꢀ  
UNT-IOM-6  
21  
Note: For vertical fan-coil units, push the main condensate drain  
hose and overflow condensate drain hose through to the inside of the  
chassis end panel to prevent them from being burned when making  
sweat connectionsꢀ Be sure to pull the hoses back through and route  
to the auxiliary drain pan when the end panel has cooledꢀ  
3ꢀ Solder the joint using bridgit lead-free solder (ASTM B32-89) to  
provide a watertight connectionꢀ Avoid overheating factory soldered  
joints when soldering field connections to the coil to prevent  
leakage from occurringꢀ  
4ꢀ Insulate all piping to coil connections as necessary after connec-  
tions are completeꢀ  
Note: Maintain a minimum distance of one foot between the reduction  
fitting for the 1/2 inch diameter line and the fan-coil unit piping  
connectionsꢀ  
Install the auxiliary drain pan, which ships in the accessory packet  
Units with Steam  
Coils  
CAUTION: In all steam coil installations, the con-  
!
densate return connections must be at the low point of  
the coil to ensure condensate flows freely from the coil  
at all times. Failure to do so may cause physical coil  
damage from water hammer, unequal thermal stresses,  
freeze-up and/or corrosion.  
1ꢀ Make piping connections to the steam coil as shown in Figure 7ꢀ  
Cap the unused connectionꢀ  
2ꢀ The coil is already pitched within the unit to provide proper pitch to  
drain condensate out of the coilꢀ Ensure that the unit has been  
properly leveledꢀ Refer to page 13 for unit leveling instructionsꢀ  
3ꢀ Install a 1/2 inch, 15-degree swing check vacuum breaker in the  
unused condensate return tapping as close as possible to the coilꢀ  
Figure 7. Steam coil header ports. The center port is the supply  
connection. The return port is below the supply. The top port  
must be closed off.  
22  
UNT-IOM-6  
4ꢀ Vent the vacuum breaker line to atmosphere or connect it into the  
return main at the discharge side of the steam trapꢀ  
5ꢀ Pitch all steam supply and return mains down a minimum of 1 inch  
per 10 feet in the direction of flowꢀ  
6ꢀ Do not drain the steam mains or take-off through the coilsꢀ Drain  
the mains ahead of the coils through a steam trap to the return lineꢀ  
7ꢀ Overhead returns require 1 psig of pressure at the steam trap  
discharge for each 2-foot elevation to ensure continuous condensate  
removalꢀ  
8ꢀ Proper steam trap selection and installation is necessary for  
satisfactory coil performance and service lifeꢀ For installation, use the  
following steps:  
aꢀ Locate the steam trap discharge at least 12 inches below the  
condensate return connectionꢀ This provides sufficient hydrostatic  
head pressure to overcome trap losses and ensure complete conden-  
sate removalꢀ  
bꢀ Trane Company recommends using flat and thermostatic traps  
because of gravity drain and continuous discharge operationꢀ  
cꢀ Use float and thermostatic  
traps with atmospheric pressure  
gravity condensate return, with  
automatic controls or where the  
possibility of low pressure supply  
steam existsꢀ  
ST = Strainer  
FT = Float and  
thermostatic  
steam trap  
MV = Manual  
air vent  
GV= Gate valve  
VB = Vacuum  
breaker, 15°  
swing check  
valve  
dꢀ Always install strainers as  
close as possible to the trap inlet  
sideꢀ  
Reference Figure 8 for an ex-  
ample of a properly piped steam  
coilꢀ  
Figure 8. Example of typical piping to the steam coil.  
UNT-IOM-6  
23  
Before installing water piping supply and return lines to factory  
piping package, note the following itemsꢀ  
Factory Piping  
Package  
Connections  
· All piping connections are 5/8 inch OꢀDꢀ (1/2 inch nominal) female  
copper connectionsꢀ  
Piping Considerations  
· The fan-coil supply and return piping should not interfere with the  
auxiliary drain pan or condensate lineꢀ See “Connecting the  
Condensate Drain” section on page 25 for more informationꢀ  
· The installer must provide adequate piping system filtration and  
water treatmentꢀ  
· If the unit has a factory deluxe piping package, the piping includes  
a strainer with a 20 mesh size screen, which allows minimal  
protection from debrisꢀ Therefore, clean the strainer regularlyꢀ  
NOTE: Maintain a minimum distance of one foot between the  
reduction fitting for the 1/2 inch diameter line and the fan-coil piping  
connectionsꢀ  
Connecting Water Piping to  
Factory Piping Package  
1ꢀ The factory piping package ships with brackets to adequately  
support the piping during shipmentꢀ Remove these brackets before  
connecting water piping to the unitꢀ See Figure 9ꢀ  
2ꢀ Close the piping end valves to the fully open position to prevent  
damage to the valve seat during brazingꢀ  
3ꢀ Remove the auxiliary drain pan, if it is in place, to prevent expo-  
sure to dripping solder or excessive temperaturesꢀ  
4ꢀ Solder water piping connections to supply and return end  
connectionsꢀ Avoid overheating  
factory soldered joints to  
prevent the possibility of  
leakageꢀ  
5ꢀ Insulate fan-coil piping to  
auxiliary drain pan connections  
and anypiping that is not above  
the auxiliary drain panꢀ  
Figure 9. Remove the shipping  
brackets which support the  
factory piping package before  
connecting piping.  
24  
UNT-IOM-6  
The auxiliary drain pan ships loose with a fan-coil unit with factory  
pipingꢀ To install the auxiliary drain pan, insert the tabs, located on  
the side of the drain pan, into the slots located in the chassis end  
panelꢀ Slide the pan into the narrow groove section to lock into placeꢀ  
See Figures 10 and 11ꢀ Make sure the auxiliary pan is pushed all the  
way into the fully locked positionꢀ  
Installing the  
Auxiliary Drain  
Pan  
Note: The function of the auxiliary drain pan is to collect condensate  
from the main drain pan and the factory installed piping package onlyꢀ  
It also provides a convenient field connection for the condensate  
drain line for units without factory pipingꢀ Moreover, the auxiliary drain  
pan may not be adequate to collect condensate from a field-installed  
piping packageꢀ Apply additional insulation as neededꢀ  
Figure 10. Insert the auxiliary  
drain pan tabs into these slots  
in the fan-coil chassis end  
panel.  
Figure 11. The horizontal  
auxiliary drain pan in its  
installed position.  
1ꢀ De-burr the pipe end before making the connection to the drain panꢀ  
Connecting the  
Condensate Drain  
2ꢀ Connect a 7/8 inch OꢀDꢀ copper pipe or tube, with a 0ꢀ20 inch wall  
thickness, to the auxiliary drain panꢀ This should be a mechanical  
connection that allows easy removal of the auxiliary drain pan when  
servicing the piping end pocketꢀ  
3ꢀ Slide the copper pipe over the drain pan nipple and tighten the  
collar on the pipe with a hose clamp (installer supplied)ꢀ  
Maintain a continuous drain line pitch of 1 inch per 10 feet of drain line  
run to provide adequate condensate drainageꢀ Extend the drain line  
straight from the drain pan a minimum distance of 6 inches before  
making any turnsꢀ The installer must provide proper support for the  
drain line to prevent undue stress on the auxiliary drain panꢀ  
Install a secondary overflow drain line if necessary by punching out  
the overflow drain nipple on the auxiliary drain panꢀ Next, place a 3/8  
UNT-IOM-6  
25  
inch inside diameter flexible plastic tube over the nipple and secure  
with a field supplied hose clampꢀ  
Note: The installer is responsible for adequately insulating field  
pipingꢀ See the “External Insulating Requirements section on page 20  
for more informationꢀ  
The condensate overflow detection device is an option on fan-coil  
units with either a Tracer® ZNꢀ010, ZNꢀ510, ZNꢀ520 or TUC controlꢀ  
The float switch, mounting bracket, and coiled leads ship attached  
inside the piping end pocket of the unitꢀ Install the switch by placing  
the hole or slot in the bracket over the condensate overflow drain (of  
the auxiliary drain pan) with the switch float extending over the panꢀ  
Secure the drain pan by attaching the pan’s bracket with the factory  
provided clipꢀ See Figures 12 and 13ꢀ  
Condensate  
Overflow  
Detection Device  
Figure 13. Condensate  
Figure 12. Condensate  
overflow switch installed in a  
horizontal auxiliary drain pan.  
overflow switch installed in a  
vertical auxiliary drain pan.  
Two-pipe changeover units with either the Tracer® ZNꢀ010, ZNꢀ510,  
ZNꢀ520 or TUC control have an automatic changeover sensor that  
determines heating or cooling mode based on the supply water  
temperatureꢀ On units with a factory piping package, the factory  
straps the changeover sensor to the piping supply water pipeꢀ See  
Figure 14 on page 27ꢀ  
Automatic  
Changeover  
Sensor  
If the unit does not have a factory piping package, the factory at-  
taches the sensor and coiled lead wires to the piping side end panelꢀ  
The installer should attach the sensor parallel to and in direct contact  
with the supply water pipeꢀ  
Note: The installer is responsible to ensure the changeover sensor is  
installed in a location that can sense active water temperatureꢀ  
Otherwise, the unit may fail to sense the correct operating mode and  
disable temperature controlꢀ  
26  
UNT-IOM-6  
When using field supplied 3-way valves, position the changeover  
sensor upstream of the valve on the supply water pipeꢀ  
Recommendation: When using field supplied 2-way control  
valves, attach the changeover sensor in a location that will  
detect an active water temperatureꢀ The unit must always be  
able to sense the correct  
system water temperature,  
regardless of the control valve  
positionꢀ  
Note: The maximum length of  
the automatic changeover wire  
cannot exceed 10 feet from the  
control panelꢀ If the sensor  
extends beyond the unit chassis,  
use shielded conductors to  
eliminate radio frequency  
interference (RFI)ꢀ  
Figure 14. The changeover  
sensor strapped to the supply  
water pipe.  
Two-pipe fan-coil units with auxiliary electric heat have an automatic  
electric heat lockout switch that disengages the electric heat when  
hydronic heat enablesꢀ If the unit has a factory piping package and  
electric heat, the factory attaches the switch to the supply water  
pipeꢀ When the lockout switch detects the supply water temperature  
above 95° F, it disengages the  
Automatic Electric  
Heat Lockout  
Switch (Fan-coil)  
electric heatꢀ This eliminates  
electric heat and hydronic heat  
working simultaneouslyꢀ  
If the fan-coil unit does not have  
a factory piping package, the  
factory attaches the switch and  
coiled lead wires to the piping  
side end panelꢀ The installer  
should position the lockout  
switch on the supply water line of  
the unit by sliding its spring  
connector over the pipeꢀ  
See Figure 15ꢀ  
Figure 15. Units with electric  
heat have an electric heat  
lockout switch on the supply  
water pipe.  
UNT-IOM-6  
27  
The hydronic coil contains a vent, either manual or automatic, to  
release air from the unitꢀ This vent is not sufficient for venting the  
water piping system in the buildingꢀ  
Venting the Hydronic  
Coil  
Locate the coil air vent on the piping side, above the coil connections  
on the unitꢀ Perform the following steps to vent the coil after installing  
the unitꢀ See Figure 16ꢀ  
1ꢀ Pressurize the building piping system with water and vent any  
trapped air at system ventsꢀ  
2ꢀ For units with manual air vents, back the set screw out to expel air  
from the unit and then re-tighten the set screwꢀ  
The automatic air vent should require no adjustment for the coil to  
ventꢀ However, if the coil does not vent immediately, unscrew the outer  
portion of the fitting to expel air from the portꢀ  
If debris has become trapped in the vent, completely remove the outer  
portion of the fitting and cleanꢀ  
Figure 16. The hydronic coil air vent is above the coil  
connections. A horizontal unit is on the left and a vertical on  
the right.  
28  
UNT-IOM-6  
The manual circuit setter valve is an optional end valve supplied on  
the return pipe of the factory piping packageꢀ The valve allows the  
operator to regulate water flow through the hydronic coil, balance the  
water flow through the unit with other units in the piping system, and  
serves as a shutoff or end valveꢀ See Figure 17ꢀ  
Balancing The Manual  
Circuit Setter Valve  
Follow the procedure below to set maximum water flow through the  
coilꢀ  
1ꢀ Establish water flow through the coilꢀ Perform an open override of  
the valve if the control valve is closed to the coil, either manually or  
by Tracer®ꢀ  
If the piping package has 2-position, normally closed valves:  
Drive open the valve using a 24V signalꢀ  
If the piping package has 2-  
position, normally open  
valves:  
Manually drive open the valve by  
removing power to the valveꢀ  
If the piping package has  
modulating valves:  
To manually drive the valve open,  
depress the button stem on top  
of the valve and push the lever  
located on the side of the valve to  
the full open positionꢀ  
Figure 17. Manual circuit setter  
valve.  
2ꢀ For presetting, use the appropriate valve curve shown in Figure 19  
on page 30 to determine which setting is necessary to achieve the  
appropriate pressure dropꢀ  
3ꢀ Carefully remove the Schrader pressure port connection caps on  
the manual circuit setter, since they will be at the same temperature  
as the pipelineꢀ  
4ꢀ Bleed all air from the hoses and meter before reading the pressure  
dropꢀ Refer to the gauge operating instructionsꢀ  
5ꢀ Adjust the circuit setter valve by turning the valve stem until the  
appropriate pressure drop is achievedꢀ See Figure 18 on page 30ꢀ  
6ꢀ After achieving the proper setting, slightly loosen the two socket  
head cap screws and rotate the memory stop around until it  
touches the back side of the indicatorꢀ Then tighten the screws to  
UNT-IOM-6  
29  
securely set the open memory positionꢀ The memory stop indicates  
the last set open positionꢀ  
7ꢀ If using a 3-way valve: close the control valve to the coil, with the  
differential pressure meter still  
connectedꢀ This will divert flow to  
the bypass side of a 3-way valveꢀ  
Adjust the balancing fitting to  
obtain the same pressure drop  
across the circuit setter valve as  
in step 2 when the control valve  
was open to the coilꢀ  
Figure 18. Close-up view of  
manual circuit setter valve.  
Figure 19. Setting the manual circuit setter valve, differential  
pressure vs. flow.  
30  
UNT-IOM-6  
The automatic flow valve is an  
optional end valve on the return of  
the factory piping packageꢀ  
See Figure 20ꢀ The valve regu-  
lates water flow through the coil  
to a specific (gpm) flow rate, as  
ordered by the customerꢀ  
Balancing The Auto-  
matic Circuit Setter  
Valve  
The automatic flow valve controls  
to the specified flow rate, pro-  
vided that the pressure drop  
across the valve is within a  
Figure 20. Automatic circuit  
setter valve.  
certain rangeꢀ To verify that the  
valve is operating properly, remove the protective caps from the P/T  
ports and measure the pressure drop across the valve with a differen-  
tial pressure meterꢀ Carefully remove the P/T port connection caps,  
since they will be at the same temperature as the pipelineꢀ The  
reading should be within the given ranges in Table 2ꢀ If the pressure  
drop is not within the ranges listed, the valve will not control water  
flowꢀ If the valve orifice becomes clogged with debris, remove water  
from piping and then remove the cap of the valve body and push on  
the piston to dislodge any foreign matterꢀ If this is not successful,  
remove the cartridge and cleanꢀ  
Table 2ꢀ Automatic Circuit Setter Flow Rate Rangeꢀ  
Valve gpm  
0ꢀ5 to 8ꢀ0  
9 to 12  
Pressure Drop Range (psig)  
2 to 32  
5 to 50  
Replace the cartridge in the field without breaking the piping line to  
furnish a higher or lower gpmꢀ To do this, remove the water from the  
systemꢀ Remove the cap assembly containing the plug from the valve  
bodyꢀ Grasp the cartridge by the piston to removeꢀ Install a different  
spring if the pressure drop range of the valve is being changed alsoꢀ  
UNT-IOM-6  
31  
Duct Connections  
The unit’s airflow configuration varies dependent on the model and  
options orderedꢀ A one-inch duct collar is provided on units with a  
ducted return and/or discharge to attach ductwork to the unitꢀ  
The Trane Company recommends using galvanized sheet metal  
ductwork with fan-coil and cabinet heater unitsꢀ Slide the sheetmetal  
duct over the duct collar flange of the unit, seal the joint and fasten  
with sheetmetal screwsꢀ  
Note: Do not run screws through the removable front panel on con-  
cealed unitsꢀ  
Install all air ducts according to National Fire Protection Association  
standards for the Installation of Air Conditioning and Ventilating  
Systems (NFPA 90A and 90B)ꢀ  
Follow the general recommendations listed below when installing  
ductwork for the unitꢀ  
Ductwork  
Recommendations  
· Discharge ductwork should run in a straight line, unchanged in size  
or direction, for a minimum equivalent distance of 3 fan diameters  
from the unit (approximately 20 inches)ꢀ  
· When making duct turns and transitions avoid sharp turns and use  
proportional splits, turning vanes, and air scoops when necessaryꢀ  
· When possible, construct, and orient supply ductwork turns in the  
same direction as the fan rotationꢀ  
32  
UNT-IOM-6  
Electrical Connections  
Refer to the unit nameplate to obtain the minimum circuit ampacity  
(MCA) and maximum fuse size (MFS) or maximum circuit breaker  
(MCB) to properly size field supply wiring and fuses or circuit break-  
ersꢀ See Figure 2 on page 6 to reference the nameplate locationꢀ  
Refer to the unit operating voltage listed on the unit wiring schematic,  
submittal, or nameplateꢀ Reference the wiring schematic for specific  
wiring connectionsꢀ  
Supply Power  
Wiring  
!
WARNING: Hazardous voltage! Disconnect all  
electric power including remote disconnects before  
servicing. Failure to do so may cause severe personal  
injury or death.  
Wiring diagrams are attached to the unit in a plastic bag and can be  
be easily removed for referenceꢀ Wiring schematics are attached as  
follows:  
· Vertical cabinet & recessed units:  
Schematics are on the inside of the front panelꢀ See Figure 21ꢀ  
· Vertical concealed & all horizontal units:  
Locate schematics on the fan and motor panel of unitꢀ See Figure 22ꢀ  
CAUTION: Use copper conductors only! Unit  
!
terminals are not designed to accept other types of  
conductors. Failure to do so may cause damage to the  
equipment.  
Figure 21. Locate the wiring  
schematic on the inside of the  
front panel of vertical cabinet  
and recessed units.  
Figure 22. Locate the wiring  
schematic on the fan and  
motor panel of vertical  
concealed and all horizontal  
units. (This unit is turned on  
it's side.)  
UNT-IOM-6  
33  
All field wiring should conform  
to NEC and all applicable  
state and local code require-  
mentsꢀ  
The control panel box is  
always on the end opposite  
the piping connectionsꢀ  
Access the control box by  
removing the two screws that  
secure the front coverꢀ If the  
unit has a terminal unit control  
board (TUC), remove the screw  
in the top right corner of the  
panelꢀ This will allow the panel  
to pivot downward to provide  
access to the electrical  
Figure 23. The terminal unit  
control (TUC) board pivots  
downward to provide service  
access.  
componentsꢀ See Figure 23ꢀ  
WARNING: Insulate all power wire from sheetmetal  
ground. Failure to do so may cause electrical shorts  
resulting in personal injury or death.  
!
Units have one of three different connection points, depending on the  
unit type and optionsꢀ  
1ꢀ Power & ground inside of control box:  
If the unit has a fan mode switch, Tracer® ZNꢀ010 or ZNꢀ510 control  
without a disconnect switch, the power leads and capped ground  
wire are inside the control panelꢀ  
2ꢀ Power & ground inside the junction box:  
If the unit has a TUC control without a disconnect switch, the power  
leads and capped ground wire are inside the junction box on the  
control panelꢀ  
3ꢀ Power wired to switch on junction box & ground inside of junction  
box:  
If the unit has a disconnect switch, the power leads wire to the  
junction box switch on the control panelꢀ Pull the capped  
ground wire into the junction boxꢀ  
34  
UNT-IOM-6  
All sensor and input circuits are normally at or near ground (common)  
potentialꢀ When wiring sensors and other input devices to the Tracer®  
ZNꢀ010, ZNꢀ510, ZNꢀ520 or TUC, avoid creating ground loops with  
grounded conductors external to the unit control circuitꢀ Ground loops  
can affect the measurement accuracy of the controllerꢀ  
Electrical  
Grounding  
Restrictions  
CAUTION: Unit transformer IT1 provides power to  
!
fan-coil unit only. Field connections to the transformer  
IT1 may create immediate or premature unit component  
failure.  
All input/output circuits (except isolated relay contacts and optically  
isolated inputs) assume a grounded source, either a ground wire at  
the supply transformer to control panel chassis, or an installer  
supplied groundꢀ  
Note: Do not connect any sensor or input circuit to an external ground  
connectionꢀ  
The installer must provide interconnection wiring to connect wall  
mounted devices such as a fan mode switch or zone sensor moduleꢀ  
Refer to the unit wiring schematic for specific wiring details and point-  
to-point wiring connectionsꢀ Dashed lines indicate field wiring on the  
unit wiring schematicsꢀ All interconnection wiring must conform to  
NEC Class 2 wiring requirements and any state and local require-  
mentsꢀ Refer to Table 3 for the wire size range and maximum wiring  
distance for each deviceꢀ  
Wall Mounted  
Control  
Interconnection  
Wiring  
Recommendation: Do not bundle or run interconnection wiring  
in parallel with or in the same conduit with any high-voltage  
wires (110V or greater)# Exposure of interconnection wiring to  
high voltage wiring, inductive loads, or RF transmitters may  
cause radio frequency interference (RFI)# In addition, improper  
separation may cause electrical noise problems# Therefore, use  
shielded wire (Beldon 83559/83562 or equivalent) in applications  
that require a high degree of noise immunity# Connect the shield  
to the chassis ground and tape at the other end#  
Table 3ꢀ Maximum Wiring Distances, ft (m)  
Device  
Wire Size Range  
Maxꢀ Wiring Distance  
Fan Mode Switch  
14 - 22 AWG  
500 (152ꢀ4)  
Zone Sensor Module  
200 (60ꢀ96)  
16 - 22 AWG  
UNT-IOM-6  
35  
Installing Wall Mounted Controls  
Wall mounted controls, which include the fan mode switch and the  
zone sensor module, ship loose inside the unit accessory bagꢀ  
Position the controller on an inside wall 3 to 5 feet above the floor and  
and at least 18 inches from the nearest outside wallꢀ Installing the  
controller at a lower height may give the advantage of monitoring the  
temperature closer to the zone, but it also exposes the controller to  
airflow obstructionsꢀ Ensure that air flows freely over the controllerꢀ  
Avoid mounting the controller in an area subject to the following  
conditions:  
· Dead spots such as behind doors or in corners that do not allow  
free air circulationꢀ  
· Air drafts from stairwells, outside doors, or unsectioned hollow  
wallsꢀ  
· Radiant heat from the sun, fireplaces, appliances, etcꢀ  
· Airflow from adjacent zones or other unitsꢀ  
· Unheated or uncooled spaces behind the control, such as outside  
walls or unoccupied spacesꢀ  
· Concealed pipes, air ducts, or chimneys in partition spaces behind  
the controllerꢀ  
The fan mode switch ships loose inside the unit accessory bagꢀ  
Follow the steps below to install the fan mode switchꢀ  
Fan Mode Switch  
Installation  
Items needed:  
2 x 4 electrical junction box  
1ꢀRemove the brown wire if not using a field-supplied damperꢀ  
Remove the terminals, cut and strip wires as required for installationꢀ  
2ꢀLevel and position a 2 x 4 electrical junction boxꢀ Follow the  
instructions given in the “Interconnection Wiring” section and route the  
wires as shown in the wiring diagramꢀ Refer to the typical wiring  
diagram on page 101 or to the unit specific diagram on the unitꢀ  
3ꢀPosition the fan mode switch over the junction box with the two  
screws suppliedꢀ  
Figure 24. Fan Mode Switch  
36  
UNT-IOM-6  
Follow the procedure below to install the zone sensor moduleꢀ  
Reference Figure 25 on page 38 when installing the wall mounted  
zone sensorꢀ  
Zone Sensor  
Installation  
1ꢀ Note the position of the setpoint adjustment knob and gently pry  
the adjustment knob from the cover using the blade of a small  
screwdriverꢀ  
2ꢀ Insert the screwdriver blade behind the cover at the top of the  
module and carefully pry the cover away from the baseꢀ  
3ꢀ To install the zone sensor module without a junction box  
(directly to the wall):  
aꢀ Using the module base as a template, mark the the rectangular  
cutout for the control wiring and module installation holesꢀ Ensure  
the base is levelꢀ  
bꢀ Set the base aside and make the cutoutꢀ Then, drill two 3/16  
inch diameter holes approximately 1 inch deepꢀ Insert and fully  
seat the plastic anchorsꢀ  
cꢀ Pull the control wires through the cutout and attach the module  
to the wall using the screws providedꢀ  
4ꢀ To install the zone sensor module to a standard junction box:  
aꢀ Level and install a 2 inch x 4 inch junction box (installer  
supplied) vertically on the wallꢀ  
bꢀ Pull the control wires through the cutoutꢀ Attach the module to  
the wall using the screws providedꢀ  
5ꢀ Strip the insulation on the interconnection wires back 0ꢀ25 inch  
and connect to TB1ꢀ Screw down the terminal blocksꢀ  
6ꢀ Replace the zone sensor cover and adjustment knobꢀ  
Before beginning installation, follow the wiring instructions in the “Wall  
Mounted Control Interconnection Wiring” section on page 34ꢀ Also,  
refer to the unit wiring schematic for specific wiring details and point  
connectionsꢀ  
If installing a TUC zone sensor, see the TUC sections regarding  
communication wiring beginning on page 60 for more detailed informa-  
tionꢀ  
UNT-IOM-6  
37  
Wall mounted zone sensor  
Model # Digit 31 = W  
Split-mounted option:  
Wall mounted setpoint dial with unit  
mounted fan mode switch  
Model # Digit 31 = X  
Figure 25. Wall mounted zone sensor dimensions.  
Figure 26. Resistance temperature curve for the zone sensor, entering water temperature sensor,  
and discharge air sensor.  
38  
UNT-IOM-6  
Fan Mode Switch  
Manual Fan Mode Switch  
The manual fan mode switch is available for fan-coil units that do not  
have Trane factory-mounted control packagesꢀ This four-position  
switch (off-hi-med-lo) allows manual fan mode selection and is  
available unit or wall mountedꢀ  
The unit-mounted option (Digit 31 = D) operates on line voltageꢀ The  
wall-mounted option (Digit 31 = K) is low-voltage and has three 24 volt  
relays using a factory-wired transformer and relays to control the fan  
motorꢀ  
Sequence of Operations  
Off: Fan is turned off, two-position damper option spring-returns  
closedꢀ  
Hi, Med, Lo: Fan runs continuously at the selected speedꢀ The two-  
position damper option opens to an adjustable mechanical stop-  
positionꢀ  
UNT-IOM-6  
39  
®
Tracer ZN.010  
and ZN.510  
Tracer® ZN.010 and ZN.510  
The Tracer® ZNꢀ010  
is a stand-alone  
device that controls  
fan-coils and cabinet  
heatersꢀ The Tracer®  
ZNꢀ510 can be  
stand-alone or utilize  
peer-to-peer commu-  
nicationsꢀ The  
controller is easily  
accessible in the  
control end panel for  
serviceꢀ The control  
end panel is on the  
end of the unit  
Figure 27. The Tracer ZN.010 board.  
opposite the pipingꢀ  
Reference Figure 27ꢀ  
Sequence of Operations  
Off: Fan is off; control valves and fresh air damper option closeꢀ Low  
air temperature detection option is still activeꢀ  
Auto (Fan Cycling): Fan and fresh air damper cycle with control  
valve option to maintain setpoint temperatureꢀ In cooling mode, the  
fan cycles from off to medium and in heating mode it cycles from off  
to lowꢀ When no heating or cooling is required, the fan is off and the  
fresh air damper option closesꢀ  
Low/Med/High (Continuous Fan): Fan operates continuously while  
control valve option cycles to maintain setpoint temperatureꢀ Fresh  
air damper option is openꢀ  
40  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
When 24 VAC power is initially applied to the Tracer® ZNꢀ010 or  
ZNꢀ510, the following sequence occurs:  
1ꢀ All outputs are controlled offꢀ  
2ꢀ Tracer® ZNꢀ010 and ZNꢀ510 reads all input values to detemine  
initial valuesꢀ  
Operating  
Information  
Power-Up Sequence  
3ꢀ The random start time (0-25 seconds) expiresꢀ  
4ꢀ Normal operation beginsꢀ  
Both Tracer® ZNꢀ010 and ZNꢀ510 use an entering water temperature  
sampling function to test for the correct water temperature for the unit  
operating modeꢀ For all applications not involving changeover, the  
water temperature does not effect the unit operationꢀ  
Entering Water  
Temperature  
Sampling Function  
The entering water temperature sampling function opens the main  
hydronic valve, waits no more than three minutes to allow the water  
temperature to stabilize, then measures the entering water tempera-  
ture to see if the correct water temperature is availableꢀ  
The entering water must be five degrees or more above the space  
temperature to allow hydronic heating and five degrees or more below  
the space temperature to allow hydronic coolingꢀ  
If the correct water temperature is available, the unit begins normal  
heating or cooling operationꢀ If the measured entering water tempera-  
ture is too low or high, the controller closes the valve and waits 60  
minutes before attempting to sample the entering waterꢀ Reference  
Table 4ꢀ  
Table 4ꢀ Unit Mode as Related to Water Temperature  
Unit Type  
EWT Sensor Required?  
Coil Water Temperature  
· Can cool if:  
space temp - EWT ³ 5 deg F  
· Can heat if:  
2-pipe changeover  
Yes  
EWT - space temp ³ 5 deg F  
· Can cool if:  
4-pipe changeover  
Yes  
space temp - EWT ³ 5 deg F  
· Can heat if:  
EWT - space temp ³ 5 deg F  
2-pipe heating only  
2-pipe cooling only  
4-pipe heat/cool  
No  
No  
No  
Hot water assumed  
Cold water assumed  
·Cold water assumed in main coil  
·Hot water assumed in auxꢀ coil  
UNT-IOM-6  
41  
®
Tracer ZN.010  
and ZN.510  
Binary Inputs  
The factory hard wires the low temperature detection sensor to binary  
input #1 (BIP1) on the Tracer® ZNꢀ010 and ZNꢀ510ꢀ The sensor  
defaults normally closed (NꢀCꢀ), and will trip off the unit on a low  
temperature diagnostic when detecting low temperatureꢀ In addition,  
the Tracer® ZNꢀ010 and ZNꢀ510 control unit devices as listed below:  
BIP1: Low  
Temperature  
Detection  
Option  
Fan:  
Off  
Valves:  
Open  
Electric heat: Off  
Damper:  
Closed  
Note: See the “Diagnostics” section on page 50 for more informationꢀ  
BIP2: Condensate  
Overflow Detection  
Option  
The factory hard wires the condensate overflow sensor to binary input  
#2 (BIP2) on the Tracer® ZNꢀ010 and ZNꢀ510ꢀ The sensor defaults  
normally closed (NꢀCꢀ), and will trip off the unit on a condensate  
overflow diagnostic if condensate reaches the trip pointꢀ In addition,  
the Tracer® ZNꢀ010 and ZNꢀ510 control unit devices as listed below:  
Fan:  
Off  
Valves:  
Closed  
Electric heat: Of  
Reference Table 6 for the Tracer® ZNꢀ010 and ZNꢀ510’s six binary  
outputsꢀ  
Binary input #3 (BIP3) on Tracer® ZNꢀ010 and ZNꢀ510 is available for  
field- wiring an occupancy sensor, such as a binary switch or a  
timeclock, to detect occupancyꢀ The sensor can be either normally  
open or normally closedꢀ Reference Table 5 on page 43ꢀ  
BIP3: Occupancy  
Sensor  
42  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
Table 5ꢀ Occupancy Sensor State Table  
Sensor Type  
Sensor Position  
Unit Occupancy Mode  
Normally Open  
Normally Open  
Normally Closed  
Normally Closed  
Open  
Closed  
Open  
Occupied  
Unoccupied  
Unoccupied  
Occupied  
Closed  
Binary Outputs  
Table 6ꢀ Binary Outputs  
Binary Output  
BOP1  
BOP2  
BOP3  
BOP4  
Description  
Fan high speed  
Fan medium speed  
Fan low speed  
Main valve  
Pin  
J1-1  
J1-2  
J1-4  
J1-5  
J1-6  
J1-7  
BOP5  
BOP6  
Auxiliary valve/electric heat  
2-position fresh air damper  
Notes:  
1ꢀ In a four-pipe application, BOP4 is used for cooling and BOP5 is  
used for heatingꢀ  
2ꢀ If no valves are ordered with the unit, the factory default for the  
Tracer® ZNꢀ010 and ZNꢀ510 controller are:  
BOP4 configured as normally closed  
BOP5 configured as normally open  
3ꢀ If the fresh air damper option is not ordered on the unit, BOP6 will  
be configured as noneꢀ  
UNT-IOM-6  
43  
®
Tracer ZN.010  
and ZN.510  
Both Tracer® ZNꢀ010 and ZNꢀ510 accept a maximum of five analog  
inputsꢀ Reference Table 7ꢀ  
Analog Inputs  
Table 7ꢀ Analog Inputs Available  
Analog Input  
Description  
Application  
Zone  
Space temperature  
Local setpoint  
Space temperature detection  
Set  
Thumbwheel setpoint  
Zone sensor fan switch  
Fan  
Fan mode input  
Analog input 1 (AI1)  
Analog input 2 (AI2)  
Entering water temperature  
Discharge air temperature  
Entering water temperature detection  
Discharge air temperature detection  
Notes:  
1ꢀThe zone sensor, entering water temperature sensor, and the discharge air temperature sensor are  
10KW thermistorsꢀ Figure 26 on page 38 provides the resistance-temperature curve for these  
thermistorsꢀ  
2ꢀ Zone Sensor:  
Wall mounted sensors include a thermistor soldered to the sensor’s circuit board  
Unit mounted sensors include a return air sensor in the unit’s return air streamꢀ  
3ꢀ Changeover units include an entering water temperature sensorꢀ  
Zone Sensors  
The zone sensors available with the Tracer® ZNꢀ010 and ZNꢀ510  
provide up to three different inputs  
1ꢀ Space temperature measurement (10K thermistor)  
2ꢀ Local setpoint  
3ꢀ Fan mode switch  
Wall mounted zone sensors include a thermistor as a component of  
the internal printed circuit boardꢀ Unit mounted zone sensors use a  
sensor placed in the unit’s return air streamꢀ  
Each zone sensor is equipped with a thumbwheel for setpoint  
adjustmentꢀ  
Fan Mode Switch  
The zone sensor may be equipped with a fan mode switchꢀ The fan  
mode switch offers selections of off, low, medium, high, or autoꢀ  
Reference Table 8 on page 45 for fan mode operationꢀ  
44  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
The Tracer® ZNꢀ010 and ZNꢀ510 will operate in either continuous fan  
or fan cycling modeꢀ The fan cycles when the fan mode switch is  
placed in autoꢀ The fan runs continuous when placed in the high,  
medium, or low positionꢀ Use Rover™, installation and service tool,  
to change the auto defaultsꢀ  
Supply Fan  
Operation  
Table 8ꢀ Fan Mode Operation  
Heating Mode  
Cooling Mode  
Fan Mode  
Occupied  
Unoccupied  
Occupied  
Unoccupied  
Off  
Off  
Off  
Off  
Off  
Low  
Low  
Off/high (3)  
Off/high (3)  
Off/high (3)  
Low  
Off/high (3)  
Off/high (3)  
Off/high (3)  
Medium  
High  
Medium  
High  
Medium  
High  
Auto  
Continuous  
Heat default  
Off/high (3)  
Off/high (3)  
Cool default  
Off/high (3)  
Off/high (3)  
CyclingOff/heat default  
Off/cool default  
Notes:  
1ꢀ During the transition from off to any fan speed but high, Tracer® ZNꢀ010 and ZNꢀ510 automatically  
starts the fan on high speed and runs for three seconds before transitioning to the selected speed (if it  
is other than high)ꢀ This provides enough torque to start all fan motors from the off positionꢀ  
2ꢀ When the heating output is controlled off, ZNꢀ010 and ZNꢀ510 automatically controls the fan on for  
an additional 30 secondsꢀ This delay allows the fan to dissipate any residual heat from the heating source,  
such as electric heatꢀ  
3ꢀ Whenever two states are listed for the fan:  
The first state (off) applies when there is not a call for heating or coolingꢀ  
The second state (varies) applies when there is a call for heating or coolingꢀ  
The heat default is factory configured for low fan speed, and the cool default is mediumꢀ  
Table 9ꢀ Valid Operating Range and Factory Default Setpoints  
Setpoint/Parameter  
Default Setting  
Valid Operating Range  
Unoccupied cooling setpoint  
85° F  
40 to 115° F  
Occupied cooling setpoint  
Occupied Heating setpoint  
Unoccupied heating setpoint  
Cooling setpoint high limit  
Cooling setpoint low limit  
Heating setpoint high limit  
Heating setpoint low limit  
74° F  
71° F  
60° F  
110° F  
40° F  
105° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40° F  
40 to 115° F  
Power up control wait  
UNT-IOM-6  
0 sec  
0 to 240 sec  
45  
®
Tracer ZN.010  
and ZN.510  
Troubleshooting  
Green STATUS LED  
Yellow COMM LED  
Red SERVICE LED  
Figure 28. The Tracer ZN.010 board.  
LED Activity  
Red Service LED  
Table 10ꢀ Red Service LED Activity  
Red LED Blink Activity  
Description  
LED off continuously when power  
is applied to the controller  
Normal operation  
LED on continuously, even when  
power is applied to the controller  
Someone is pressing the service button or the controller has failedꢀ  
LED flashes once every second  
Use Rover™, Trane’s service tool, to restore the unit to normal  
operationꢀ Refer to the Rover™ product literature for more informationꢀ  
46  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
The green LED normally indicates whether the controller is powered  
on (24 VAC supplied)ꢀ Reference Table 11ꢀ  
Green STATUS LED  
Table 11ꢀ Green STATUS LED Activity  
Green LED Blink Activity  
Description  
LED on continuously  
Power on (normal operation)  
LED blinks once  
LED blinks twice  
Manual output test mode  
Manual output test mode, with one or more diagnos-  
tic present  
LED blinks (1/4 second on, 1/4 second  
off for 10 seconds)  
“Wink” mode  
LED off  
· Power off  
· Abnormal condition  
· Test button is pressed  
Note: The “wink” feature allows the identification of a particular controllerꢀ When sending a request from a  
device, such as Rover™, the controller will “wink” to indicate it received the signalꢀ  
Yellow COMM LED  
Table 12ꢀ Yellow COMM LED Activity  
Yellow LED Blink Activity  
Description  
LED off continuously  
The controller is not detecting any communicationꢀ  
(Normal for units in standalone applications)  
LED blinks  
The controller detects communicationꢀ  
Abnormal condition  
LED on continuously  
UNT-IOM-6  
47  
®
Tracer ZN.010  
and ZN.510  
The purpose of the manual output test sequence is to verify output  
and end device operationꢀ Use the manual output test to:  
· Verify output wiring and operation without using Rover™,  
service toolꢀ  
Manual Output  
Test  
· Force the water valve to open and balance the hydronic systemꢀ  
Note: The manual output test is not an automatic cycleꢀ You must  
press the Test button to proceed through each stepꢀ  
The controller observes all diagnostics that occur during the test  
sequenceꢀ Although an automatic diagnostic reset sequence exists  
as part of the controller’s normal operation, the automatic diagnostic  
reset feature is not active during the test sequenceꢀ  
If left in an individual test step, the controller remains in test mode  
for 60 minutes and then exits to normal operationꢀ  
Many service calls are due to unit diagnosticsꢀ The test sequence  
resets unit diagnostics and attempts to restore normal unit operation  
prior to testing the outputsꢀ If the diagnostics remain after a reset, the  
STATUS LED indicates the diagnostic condition is still present (two  
blinks)ꢀ See the Green STATUS LED section in Table 11 on page 47ꢀ  
Follow the procedure below to test the Tracer® ZNꢀ010 and ZNꢀ510  
controllerꢀ  
Manual Output Test  
Procedure  
1ꢀ Press and hold the Test button for at least two seconds (not  
exceeding 5 seconds), and then release, to start the test modeꢀ  
2ꢀ The test sequence will turn off all outputs and then attempt to clear  
all diagnosticsꢀ  
3ꢀ Press the Test button several more times (no more than once per  
second) to advance through the test sequenceꢀ  
The outputs are not subject to minimum times during the test se-  
quenceꢀ However, the test sequence only permits one step per  
second which limits minimum output timeꢀ  
The green LED is turned off when the Test button is pressedꢀ To begin  
the manual output test mode, press and hold the Test button (turning  
off the green LED) for at least two secondsꢀThe green LED will begin  
to blink, indicating the controller is in test modeꢀ  
48  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
Table 13ꢀ Test Sequence for 1-Heat /1-Cool Configurations  
Steps  
Fan  
BOP1-3  
Off  
Cool Output  
BOP4 (1)  
Off  
Heat Output  
BOP5BOP6  
Off  
Damper  
Closed  
Closed  
Closed  
Closed  
Closed  
Closed  
Open  
1ꢀ Off  
2ꢀ Fan High  
3ꢀ Fan Medium  
4ꢀ Fan Low  
5ꢀ Cool  
High  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Medium  
Low  
High  
High  
High  
6ꢀ Heat  
7ꢀ Fresh Air  
Damper (3)  
8ꢀ Exit  
(2)  
Notes:  
(1) At the beginning of step 2, the controller attempts to clear all diagnosticsꢀ  
(2) For all 1-heat/1-cool applications including 2-pipe changeover, BOP4 energizes in the cooling test  
stage and BOP5 energizes in the heat test stageꢀThis occurs even though during normal 2-pipe  
changeover operation BOP4 controls the unit valve for both cooling and heatingꢀ  
(2) After the Fresh Air Damper step, the test sequence performs the Exit stepꢀThis initiates a reset and  
attempts to return the controller to normal operationꢀ  
(3) The fresh air damper (BOP6) only energizes during this step if binary output 6 has been configured as  
a fresh air damperꢀ  
UNT-IOM-6  
49  
®
Tracer ZN.010  
and ZN.510  
Diagnostics  
Table 14ꢀ Controller Diagnostics  
Diagnostic  
Latching  
Yes/No  
Fan  
Valves  
Electꢀ Heat  
Damper  
Auxiliary  
tempꢀ failure  
No  
Enabled  
Off  
No action  
No action  
Off  
No action  
Condensate  
overflow  
Yes  
Closed  
Closed  
detection  
Entering  
water tempꢀ  
failure  
No  
Enabled  
Enabled  
Enabled  
Enabled  
Fan mode  
failure  
No  
Enabled  
Disabled  
Enabled  
Disabled  
Enabled  
Disabled  
Enabled  
Disabled  
Invalid unit  
configuration  
failure  
Yes  
Low tempꢀ  
detection  
Yes  
Off  
Open  
Off  
Closed  
Maintenance Yes  
required  
Enabled  
No action  
No action  
No action  
Setpoint  
No  
No  
Enabled  
Off  
No action  
Closed  
No action  
Off  
No action  
Closed  
Zone tempꢀ  
failure  
Notes:  
Priority Level: Diagnostics are listed in order from highest to lowest priorityꢀ The controller senses and  
records each diagnostic independently of other diagnosticsꢀ It is possible to have multiple diagnostics  
present simultaneouslyꢀ The diagnostics affect unit operation according to priority levelꢀ  
Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic  
automatically resets when the input is present and validꢀ  
Enabled: End device is allowed to run if there is a call for it to runꢀ  
Disabled: End device is not allowed to run even if there is a call for it to runꢀ  
No Action: The diagnostic has no affect on the end deviceꢀ  
50  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
There are four ways in which diagnostics are reset:  
Resetting  
Diagnostics  
1ꢀ Automatic reset by the controller  
2ꢀ By initiating a manual output test at the controller  
3ꢀ By cycling power to the controller  
4ꢀ Through Rover™, Trane’s service tool  
The controller includes an automatic diagnostic reset function which  
attempts to automatically restore the unit when a low temperature  
diagnostic occursꢀ  
Automatic Reset by  
the Controller  
Note: The controller implements the automatic diagnostic reset  
function only once every 24 hoursꢀ For the controller to increment the  
24 hour timer, you must maintain power to the controllerꢀ Cycling  
power resets all timers and countersꢀ  
After the controller detects the first special diagnostic, the unit waits  
30 minutes before invoking the automatic diagnostic reset functionꢀ  
The automatic diagnostic reset function clears the special diagnostic  
and attempts to restore the controller to normal operationꢀ The  
controller resumes normal operation until another diagnostic occursꢀ  
Note: The automatic diagnostic reset function does not operate during  
the manual output test sequenceꢀ  
If a special diagnostic occurs within 24 hours after an automatic  
diagnostic reset, the controller must be manually resetꢀ Other pos-  
sible methods of resetting diagnostics are described in the sections  
that followꢀ  
Use the controller’s Test button during installation or for troubleshoot-  
ing to verify proper end device operationꢀ Press the Test button to  
exercise all outputs in a predefined sequence, the first of which will  
attempt to reset the controller diagnostics if any are presentꢀ See  
Table 13 on page 49 for more information about the manual output  
testꢀ  
Manual Output Test  
After removing and reapplying the 24 VAC power from the board, the  
unit cycles through a power-up sequenceꢀ By default, the controller  
attempts to reset all diagnostics at power-upꢀ Diagnostics present at  
power-up and those that occur after power-up are handled according  
to Table 14 on page 50ꢀ  
Cycling Power to the  
Controller  
UNT-IOM-6  
51  
®
Tracer ZN.010  
and ZN.510  
Rover™, Trane’s service tool, can reset diagnostics present in the  
controllerꢀ For complete information about Rover™, refer to Trane  
publication EMTX-IOP-2 Rover Installation, Operation and Program-  
ming Guideꢀ  
Trane’s Service Tool,  
Rover™  
Alarm Reset  
Any device that can communicate alarm reset information can reset  
diagnostics present in the controllerꢀ  
52  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
Troubleshooting  
Table 15ꢀ Fan Outputs do not Energize  
Probable Cause  
Explanation  
Random start  
observed  
After power-up, the controller always observes a random start that varies  
between 0 and 25 secondsꢀ The controller remains off until the random start  
time expiresꢀ  
Power-up control wait  
When power-up control wait is enabled (non-zero time), the controller remains  
off until one of two conditions occurs:  
1ꢀ The controller exits power-up control wait once it receives communicated  
informationꢀ  
2ꢀ The controller exits power-up control wait once the power-up control wait  
time expiresꢀ  
Cycling fan operation  
Unoccupied operation  
When the fan mode switch is in the auto postion, the unit fan cycles off when  
there is no call for heating or coolingꢀ The heating/cooling sources cycle on or  
off periodically with the unit fan to match the capacity according to pulse-width-  
modulation (PWM) logicꢀ  
The fan cycles with capacity when the unit is in unoccupied modeꢀ This occurs  
even if the unit is in continuous fan operationꢀ While unoccupied, the fan cycles  
on or off with heating/cooling to provide varying amounts of heating or cooling to  
the spaceꢀ to match the capacity according to pulse-width-modulation  
(PWM) logicꢀ  
Fan mode off  
When using the local fan mode switch to determine the fan operation, the off  
position controls the unit fan to offꢀ  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, and  
cool) to the controllerꢀ When “off” is communicated to the controller, the unit  
controls the fan to offꢀ The unit is not capable of heating or cooling when the  
controller is in this modeꢀ  
Diagnostic present  
A specific list of diagnostics effects fan operationꢀ For more information, see the  
“Diagnostics” section on page 50ꢀ  
No power to the  
controller  
If the controller does not have power, the unit fan will not operateꢀ For the  
controller to operate normally, it must have an input voltage of 24 VACꢀ When  
the green LED is off continuously, the controller does not have sufficient power  
or the controller has failedꢀ  
Manual output test  
Unit wiring  
The controller includes a manual output test sequence to verify binary output  
operation and the associated wiringꢀ However, based on the current step in the  
test sequence, the unit fan may not be powered onꢀ Refer to the “Manual  
Output Test” section on page 51ꢀ  
The wiring between the controller outputs and the fan relays and contacts must  
be present and correct for normal fan operationꢀ Refer to the typical unit wiring  
diagrams in the Appendix of this manualꢀ  
UNT-IOM-6  
53  
®
Tracer ZN.010  
and ZN.510  
Table 16ꢀ Valves Stay Closed  
Probable Cause  
Explanation  
Normal operation  
The controller opens and closes the valves to meet the unit capacity require-  
mentsꢀ  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, and  
cool) to the controllerꢀ When off is communicated to the controller, the unit  
controls the fan to offꢀ The unit is not capable of heating or cooling when the  
controller is in this modeꢀ  
Valve override  
The controller can communicate a valve override requestꢀ This request effects  
the valve operationꢀ  
Manual output test  
The controller includes a manual output test sequence to verify analog and  
binary output operation and the associated wiringꢀ However, based on the  
current step in the test sequence, the valves may not be openꢀ Refer to the  
“Manual Output Test” section on page 51ꢀ  
Diagnostic present  
Sampling logic  
A specific list of diagnostics affects valve operationꢀ For more information, see  
the “Diagnostics” section on page 50ꢀ  
The controller includes entering water temperature sampling logic that  
automatically invokes during 2-pipe or 4-pipe changeoverꢀ It determines when  
the entering water temperature is either too cool or too hot for the desired  
heating or cooling modeꢀ Refer to the “Entering Water Temperature Sampling”  
section on page 41ꢀ  
Unit configuration  
The controller must be properly configured based on the actual installed end  
devices and applicationꢀ When the unit configuration does not match the actual  
end device, the valves may not work correctlyꢀ  
No power to the  
controller  
If the controller does not have power, the valves do not operateꢀ For the controller  
to operate normally, it must have an input voltage of 24 VACꢀ When the green  
LED is off continuously, the controller does not have sufficient power,  
or the controller has failedꢀ  
Unit wiring  
The wiring between the controller outputs and the valve(s) must be present and  
correct for normal valve operationꢀ Refer to the typical unit wiring diagrams in the  
Appendix of this manualꢀ  
54  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
Table 17ꢀ Valves Stay Open  
Probable Cause  
Explanation  
Normal operation  
The controller opens and closes the valves to meet the unit capacity require-  
mentsꢀ  
Valve override  
The controller can communicate a valve override request to affect the  
valve operationꢀ  
Manual output test  
The controller includes a manual output test sequence that verifies analog and  
binary output operation and the associated wiringꢀ However, based on the  
current step in the test sequence, the valves may be openꢀ Refer to the “Manual  
Output Test” section on page 51ꢀ  
Diagnostic present  
Sampling logic  
A specific list of diagnostics affects valve operationꢀ For more information, see  
the “Diagnostics” section on page 50ꢀ  
The controller includes entering water temperature sampling logic that automati  
cally invokes during 2-pipe or 4-pipe changeover to determine if the  
entering water temperature is correct for the unit operating modeꢀ Refer to the  
“Entering Water Temperature Sampling” section on page 41ꢀ  
Unit configuration  
Unit wiring  
The controller must be properly configured based on the actual installed end  
devices and applicationꢀ When the unit configuration does not match the actual  
end device, the valves may not work correctlyꢀ  
The wiring between the controller outputs and the valve(s) must be present and  
correct for normal valve operationꢀ Refer to the typical unit wiring diagrams in  
the Appendix of this manualꢀ  
UNT-IOM-6  
55  
®
Tracer ZN.010  
and ZN.510  
Table 18ꢀ Electric Heat Not Operating  
Probable Cause  
Explanation  
Normal operation  
The controller cycles electric heat on and off to meet the unit capacity require-  
mentsꢀ  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, cool)  
to the controllerꢀ When off is communicated to the controller, the units shuts off  
the electric heatꢀ  
Communicated disable Numerous communicated requests may disable electric heat, including an  
auxiliary heat enable input and the heat/cool mode inputꢀ Depending on the  
state of the communicated request, the unit may disable electric heatꢀ  
Manual output test  
The controller includes a manual output test sequence that verifies analog and  
binary output operation and associated output wiringꢀ However, based on the  
current step in the test sequence, the electric heat may not be onꢀ Refer to the  
“Manual Output Test” section on page 51ꢀ  
Diagnostic present  
Unit configuration  
A specific list of diagnostics affects electric heat operationꢀ For more informa-  
tion, see the “Diagnostics” section on page 50ꢀ  
The controller must be properly configured based on the actual installed end  
devices and applicationꢀ When the unit configuration does not match the actual  
end device, the electric heat may not work properlyꢀ  
No power to the  
controller  
If the controller does not have power, electric heat does not operateꢀ For the  
controller to operate normally, a 24VAC input voltage must be appliedꢀ When  
the green LED is off continuously, the controller does not have sufficient power  
or has failedꢀ  
Unit Wiring  
The wiring between the controller outputs and the electric heat contacts must  
be present and correct for normal electric heat operationꢀ Refer to the typical  
unit wiring diagrams in the Appendix of this manualꢀ  
56  
UNT-IOM-6  
®
Tracer ZN.010  
and ZN.510  
Table 19ꢀ Fresh Air Damper Stays Closed  
Probable Cause  
Explanation  
Normal operation  
The controller opens and closes the fresh air damper based on the controller’s  
occupancy mode and fan statusꢀ Normally, the fresh air damper is open during  
occupied mode when the fan is running and closed during unoccupied modeꢀ  
Warmup and cooldown The controller includes both a warmup and cooldown sequence to keep the  
fresh air damper closed during the transition from unoccupied to occupiedꢀ This  
is an attempt to bring the space under control as quickly as possibleꢀ  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, cool)  
to the controllerꢀ When off is communicated to the controller, the unit closes the  
fresh air damperꢀ  
Manual output test  
The controller includes a manual output test sequence that verifies analog and  
binary output operation and associated output wiringꢀ However, based on the  
current step in the test sequence, the fresh air damper may not be openꢀ Refer  
to the “Manual Output Test” section on Page 51ꢀ  
Diagnostic present  
Unit configuration  
A specific list of diagnostics effects fresh air damper operationꢀ For more  
information, see the “Diagnostics” section on page 50ꢀ  
The controller must be properly configured based on the actual installed end  
devices and applicationꢀ When the unit configuration does not match the actual  
end device, the damper may not work correctlyꢀ  
No power to the  
controller  
If the controller does not have power, the fresh air damper does not operateꢀ For  
the controller to operate normally, a 24 VAC input voltage must be appliedꢀ  
When the green LED is off continuously, the controller does not have sufficient  
power or has failedꢀ  
Unit wiring  
The wiring between the controller outputs and the fresh air damper must be  
present and correct for normal damper operationꢀ Refer to the typical unit wiring  
diagrams in the Appendix of this manualꢀ  
UNT-IOM-6  
57  
®
Tracer ZN.010  
and ZN.510  
Table 20ꢀ Fresh Air Damper Stays Open  
Probable Cause  
Explanation  
Normal Operation  
The controller opens and closes the fresh air damper based on the controller’s  
occupancy mode and fan statusꢀ Normally, the fresh air damper is open during  
occupied mode when the fan is running and closed during unoccupied modeꢀ  
Manual Output Test  
The controller includes a manual output test sequence that verifies analog and  
binary output operation and associated wiringꢀ However, based on the current  
step in the test sequence, the fresh air damper may be openꢀ Refer to the  
“Manual Output Test” section on page 51ꢀ  
Unit Configuration  
Unit Wiring  
The controller must be properly configured based on the actual installed end  
devices and applicationꢀ When the unit configuration does not match the actual  
end device, the damper may not work correctlyꢀ  
The wiring between the controller outputs and the fresh air damper must be  
present and correct for normal damper operationꢀ Refer to the typical unit wiring  
diagrams in the Appendix of this manualꢀ  
58  
UNT-IOM-6  
Tracer® ZN.520  
Tracer® ZN.520  
Tracer® ZNꢀ520 is a communicating or standalone deviceꢀ It is easily  
accessible in the control end panel for serviceꢀ The control end panel  
is on the end opposite the pipingꢀ  
Sequence of Operations  
OFF: Fan is off; control valve options and fresh air damper options  
closeꢀ The low air temperature detection option is still activeꢀ  
Auto: Fan speed control in the auto setting allows the modulating (3-  
wire floating point) or 2–position control valve option and three-speed  
fan to work cooperatively to meet precise capacity requirement, while  
minimizing fan speed ( motor/energy/acoustics ) and valve position  
(pump energy, chilled water reset )ꢀ As the capacity requirement  
increases at low fan speed, the water valve opensꢀ When the low fan  
speed capacity switch point is reached, the fan switches to medium  
speed and the water valve repositions to maintain an equivalent  
capacityꢀ The reverse sequence takes place with a decrease in  
required capacityꢀ  
Low/Med/High: The fan will run continuously at the selected speed  
and the valve option will cycle to meet setpointꢀ  
For Tracer® ZNꢀ520 controlled units that will interface with the Trane  
Tracer Summit® building management system, terminate the commu-  
nication wiring in the control box at the designated terminals on the  
boardꢀ Reference the unit wiring diagram or submittalsꢀ  
Tracer Summit®  
Communication  
Wiring  
Ground shields at each Tracer® ZNꢀ520, taping the opposite end of  
each shield to prevent any connection between the shield and anther  
groundꢀ Refer to Trane publication, CNT-IOP-2 Installation, Operation  
and Programming Guide, for the communication wiring diagramꢀ  
Communication wire must conform to the following specification:  
1)  
2)  
3)  
Shielded twisted pair 18 AWG  
Capacitance 23 (21-25 ) picofarads ( pF ) per foot  
Listing/Rating – 300V 150C NEC 725-2 (b) Class 2 Type  
CL2P  
4)  
Trane Part Noꢀ 400-20-28 or equivalent, available through  
Trane BAS Buying Group Accessories catalogꢀ  
UNT-IOM-6  
59  
Tracer® ZN.520  
Follow these general guidelines when installing communication  
wiring:  
1)  
2)  
Maintain a maximum 5000 ftꢀ aggregate run  
Install all communication wiring in accordance with the NEC  
and all local codesꢀ  
3)  
Solder the conductors and insulate (tape) the joint sufficiently  
when splicing communication wireꢀ Do not use wire nuts to  
make the spliceꢀ  
4)  
5)  
Do not pass communication wiring between buildings be  
cause the unit will assume different ground potentialsꢀ  
Do not run power in the same conduit or wire bundle with  
communication link wiringꢀ  
Service  
Communication  
Wiring  
Establish service communication using Rover™ service software  
connected to the Tracer® ZNꢀ520 using a twisted wire pair to one of  
the following connection pointsꢀ  
1)  
2)  
Remote zone sensor module  
Connections on the board  
This allows the technician to view and edit the Tracer® ZNꢀ520  
configuration and troubleshoot the unitꢀ However, control options  
ordered and the wiring practice followed in the field may limit the  
communication abilityꢀ  
Wall Mounted Zone  
Sensor Module  
Route interconnecting wiring from the Tracer® ZNꢀ520 to provide  
service communication at the wall-mounted zone sensor moduleꢀ  
Install wiring by referencing the unit wiring diagram and Table 3 on  
page 35 for appropriate wire sizesꢀ After wiring is complete, connect  
the communication cable (provided with the Rover service tool) to the  
telephone style RJ11 connection on the zone sensor moduleꢀ Attach  
the other end of the cable to a laptop computer running Trane Rover  
software to establish communicationꢀ  
Zone Sensors Without  
Interconnecting Wiring  
Establish service communication to the Tracer® ZNꢀ520 by wiring  
directly to the board inside the control boxꢀ Reference the unit-wiring  
diagram for the appropriate communication terminals on the boardꢀ  
Once wiring is complete, Use Trane Rover software to communicate  
to the Tracer® ZNꢀ520ꢀ  
60  
UNT-IOM-6  
Tracer® ZN.520  
Tracer® ZNꢀ520 Unit  
Start-Up  
Refer to the Trane publication, CNT-IOP-2 Installation Operation and  
Programming Guide, to operate the Tracer® ZNꢀ520 with Trane  
Integrated Comfort™ System (ICS)ꢀ The factory pre-programs the  
Tracer® ZNꢀ520 with default values to control the temperature and unit  
airflowꢀ Use Tracer Summit® building automation system or Rover™  
software to change the default valuesꢀ  
Follow the procedure below to operate the Tracer® ZNꢀ520 in a stand-  
alone operation:  
1)  
2)  
Turn power on at the disconnect switch optionꢀ  
Position the fan mode switch to either high, medium, low, or  
the auto positionꢀ  
3)  
Rotate the setpoint dial on the zone sensor module to 55 F  
for cooling or 85 F for heatingꢀ  
The appropriate control valve will actuate assuming the following  
conditions:  
1)  
Room temperature should be greater than 55 degꢀ F and less  
than 85 degꢀ F  
2)  
For a 2-pipe fan-coil unit with an automatic changeover  
sensor, the water temperature input is appropriate for the  
demand placed on the unitꢀFor example, cooling operation is  
requested and cold water (5 degrees lower than room tem  
perature) flows into the unitꢀ  
4)  
Select the correct temperature setpointꢀ  
Note: Select and enable zone sensor temperature settings to prevent  
freeze damage to unitꢀ  
Tracer®  
Communications  
Tracer® ZNꢀ520 is a Comm 5 controllerꢀ There is no need to set an  
addressꢀ Each individual board has its own unique Neuron IꢀDꢀ  
number that takes the place of dip switchesꢀ  
Tracer® ZNꢀ520  
Sequence of  
Operation  
The Tracer® ZNꢀ520 operates the fan in the following modes:  
1)  
2)  
3)  
4)  
5)  
occupied  
unoccupied  
occupied standby  
occupied bypass  
Tracer Summit with supply fan control  
UNT-IOM-6  
61  
Tracer® ZN.520  
Occupied  
When the controller is in the occupied mode, the unit attempts to  
maintain the space temperature at the active occupied heating or  
cooling setpoint, based on the measured space temperature, the  
discharge air temperature, the active setpoint, and the proportional/  
integral control algorithmꢀ The modulating control algorithm used  
when occupied or in occupied standby is described in the following  
sectionsꢀ Additional information related to the handling of the control-  
ler setpoints can be found in the previous Setpoint operation sectionꢀ  
Unoccupied Mode  
When the controller is in the unoccupied mode, the controller at-  
tempts to maintain the space temperature at the stored unoccupied  
heating or cooling setpoint, based on the measured space tempera-  
ture, the active setpoint and the control algorithm, regardless of the  
presence of a hardwired or communicated setpointꢀ Similar to other  
configuration properties of the controller, the locally stored unoccu-  
pied setpoints can be modified using Rover™ service toolꢀ  
In unoccupied mode, a simplified zone control algorithm is runꢀ During  
the cooling mode, when the space temperature is above the cool  
setpoint, the primary cooling capacity operates at 100%ꢀ If more  
capacity is needed, the supplementary cooling capacity turns on (or  
opens to 100%)ꢀ During the heating mode, when the space tempera-  
ture is below the heat setpoint, the primary heating capacity turns onꢀ  
All capacity is turned off when the space temperature is between the  
unoccupied cooling and heating setpointsꢀ Note that primary heating  
or cooling capacity is defined by unit type and whether heating or  
cooling is enabled or disabledꢀ For example, if the economizer is  
enabled and possible, it will be the primary cooling capacityꢀ If  
hydronic heating is possible, it will be the primary heating capacityꢀ  
Occupied Standby Mode  
The controller can be placed into the occupied standby mode when a  
communicated occupancy request is combined with the local  
(hardwired) occupancy binary input signalꢀ When the communicated  
occupancy request is unoccupied, the occupancy binary input (if  
present) does not affect the controller’s occupancyꢀ When the  
communicated occupancy request is occupied, the controller uses  
the local occupancy binary input to switch between the occupied and  
occupied standby modesꢀ  
During occupied standby mode, the controller’s economizer damper  
position goes to the economizer standby minimum positionꢀ The  
economizer standby minimum position can be changed using Rover  
service toolꢀ  
In the occupied standby mode, the controller uses the occupied  
62  
UNT-IOM-6  
Tracer® ZN.520  
standby cooling and heating setpointsꢀ Because the occupied  
standby setpoints typically cover a wider range than the occupied  
setpoints, the Tracer® ZNꢀ520 controller reduces the demand for  
heating and cooling the spaceꢀ Also, the outdoor air economizer  
damper uses the economizer standby minimum position to reduce  
the heating and cooling demandsꢀ  
When no occupancy request is communicated, the occupancy binary  
input switches the controller’s operating mode between occupied and  
unoccupiedꢀ When no communicated occupancy request exists, the  
unit cannot switch to occupied standby modeꢀ  
Occupied Bypass Mode  
The controller can be placed in occupied bypass mode by either  
communicating an occupancy request of Bypass to the controller or  
by using the timed override On button on the Trane zone sensorꢀ  
When the controller is in unoccupied mode, you can press the On  
button on the zone sensor to place the controller into occupied  
bypass mode for the duration of the bypass time (typically 120  
minutes)ꢀ  
Occupancy Sources  
There are four ways to control the controller’s occupancy:  
• Communicated request (usually provided by the building automation  
system or peer device)  
• By pressing the zone sensor’s timed override On button  
• Occupancy binary input  
• Default operation of the controller (occupied mode)  
A communicated request from a building automation system or  
another peer controller can change the controller’s occupancyꢀ  
However, if communication is lost, the controller reverts to the default  
operating mode (occupied) after 15 minutes (configurable, specified  
by the “receive heartbeat time”), if no local hardwired occupancy  
signal existsꢀ  
A communicated request can be provided to control the occupancy of  
the controllerꢀ Typically, the occupancy of the controller is determined  
by using time-of-day scheduling of the building automation systemꢀ  
The result of the time-of-day schedule can then be communicated to  
the unit controllerꢀ  
For complete information about the setup for Tracer Summit® applica-  
tions of this controller, see the Tracer Summit® product literatureꢀ For  
more information on the setup of another building automation system,  
UNT-IOM-6  
63  
Tracer® ZN.520  
Tracer Summit® With  
Supply Fan Control  
refer to the product-specific literature from that manufacturerꢀ  
If the unit is communicating with Tracer Summit and the supply fan  
control programming point is configured for Tracer (the factory config-  
ures as local), then Tracer Summit will control the fan regardless of  
the fan mode switch positionꢀ  
All Tracer® ZNꢀ520 lockouts (latching diagnostics) are manually reset  
whenever the fan mode switch is set to the off position or when power  
is restored to the unitꢀ The last diagnostic to occur is retained until  
the unit power is disconnectedꢀ Refer to Trane publication, CNT-IOP-2  
Tracer® ZNꢀ520 Installation Operation and Programming Guide, for  
specific instructions regarding the procedure for running the Tracer®  
ZNꢀ520ꢀ  
Cooling Operation  
The heating and cooling setpoint high and low limits are always  
applied to the occupied and occupied standby setpointsꢀ  
During the cooling mode, the Tracer® ZNꢀ520 controller attempts to  
maintain the space temperature at the active cooling setpointꢀ Based  
on the controller’s occupancy mode, the active cooling setpoint is  
one of the following:  
• Occupied cooling setpoint  
• Occupied standby cooling setpoint  
• Unoccupied cooling setpoint  
The controller uses the measured space temperature, the active  
cooling setpoint, and discharge air temperature along with the control  
algorithm to determine the requested cooling capacity of the unit (0-  
100%)ꢀ The outputs are controlled based on the unit configuration and  
the required cooling capacityꢀ To maintain space temperature control,  
the Tracer® ZNꢀ520 cooling outputs (modulating hydronic valve, 2-  
position hydronic valve, or outdoor air economizer damper) are  
controlled based on the cooling capacity outputꢀ  
The cooling output is controlled based on the cooling capacityꢀ At 0%  
capacity, all cooling capacities are off and the damper is at minimum  
positionꢀ Between 0 and 100% capacity, the cooling outputs are  
controlled according to modulating valve logic (modulating valves) or  
cycled on (2-position valves)ꢀ As the load increases, modulating  
outputs open further and binary outputs are energized longerꢀ At  
100% capacity, the cooling valve or damper is fully open (modulating  
valves) or on continuously (and 2-position valves)ꢀ  
Unit diagnostics can affect fan operation, causing occupied and  
occupied standby fan operation to be defined as abnormalꢀ Refer to  
the Troubleshooting section for more information about abnormal fan  
operationꢀ  
64  
UNT-IOM-6  
Tracer® ZN.520  
The Tracer® ZNꢀ520 controller operates the supply fan continuously  
when the controller is in the occupied and occupied standby modes,  
for either heating or coolingꢀ The controller only cycles the fan off with  
heating and cooling capacity in the unoccupied modeꢀ  
The economizer is used for cooling purposes whenever the outdoor  
temperature is below the economizer enable setpoint and there is a  
need for coolingꢀ The economizer is used first to meet the space  
demand, and other forms of cooling are used if the economizer  
cannot meet the demand aloneꢀ See modulating outdoor air damper  
operation for additional informationꢀ  
Cascade cooling control initiates a discharge air tempering function if  
the discharge air temperature falls below the discharge air tempera-  
ture control low limit, all cooling capacity is at minimum, and the  
discharge control loop determines a need to raise the discharge air  
temperatureꢀ The controller then provides heating capacity to raise  
the discharge air temperature to its low limitꢀ  
Discharge Air Tempering  
The discharge air tempering function enables when cold outdoor air is  
brought in through the outdoor air damper, causing the discharge air  
to fall below the discharge air temperature control low limitꢀ The  
controller exits the discharge air tempering function when heat  
capacity has been at 0% for five minutesꢀ  
During heating mode, the Tracer® ZNꢀ520 controller attempts to  
maintain the space temperature at the active heating setpointꢀ Based  
on the occupancy mode of the controller, the active heating setpoint  
is one of the following:  
Heating Operation  
• Occupied heating  
• Occupied standby heating  
• Unoccupied heating  
During dehumidification in the heating mode, the controller adjusts  
the heating setpoint up to the cooling setpointꢀ This reduces the  
relative humidity in the space with a minimum of energy usageꢀ  
The controller uses the measured space temperature, the active  
heating setpoint, and discharge air temperature, along with the  
control algorithm, to determine the requested heating capacity of the  
unit (0-100%)ꢀ The outputs are controlled based on the unit configura-  
tion and the required heating capacityꢀ  
UNT-IOM-6  
65  
Tracer® ZN.520  
Unit diagnostics can affect the Tracer® ZNꢀ520 controller operation,  
causing unit operation to be defined as abnormalꢀ Refer to the  
Troubleshooting section for more information about abnormal unit  
operationꢀ  
The heating output is controlled based on the heating capacityꢀ At 0%  
capacity, the heating output is off continuouslyꢀ Between 0 and 100%  
capacity, the heating output is controlled according to modulating  
valve logic (modulating valves) or cycled on (2-position valves)ꢀ As the  
load increases, modulating outputs open further and binary outputs  
are energized longerꢀ At 100% capacity, the heating valve is fully open  
(modulating valves) or on continuously (2-position valves)ꢀ  
The Tracer® ZNꢀ520 fan output(s) normally run continuously during the  
occupied and occupied standby modes, but cycle between high and  
off speeds with heating/cooling during the unoccupied modeꢀ When in  
the occupied mode or occupied standby mode and the fan speed is  
set at the high, medium, or low position, the fan runs continuously at  
the selected speedꢀ Refer to the Troubleshooting section for more  
information on abnormal fan operationꢀ  
When the unit’s supply fan is set to auto, the controller’s configura-  
tion determines the fan speed when in the occupied mode or occu-  
pied standby modeꢀ The fan runs continuously at the configured  
heating fan speed or cooling fan speedꢀ For all fan speed selections  
except off, the fan cycles off during unoccupied modeꢀ  
The economizer outdoor air damper is never used as a source of  
heatingꢀ Instead, the economizer damper (when present) is only used  
for ventilation; therefore, the damper is at the occupied minimum  
position in the occupied modeꢀ The damper control is primarily  
associated with occupied fan operationꢀ  
For multiple fan speed applications, the Tracer® ZNꢀ520 controller  
offers additional fan configuration flexibilityꢀ Separate default fan  
speeds for heating and cooling modes can be configuredꢀ The fan  
runs continuously for requested speeds (off, high, medium, or low)ꢀ  
When the fan mode switch is in the Auto position or a hardwired fan  
mode input does not exist, the fan operates at the default configured  
speedꢀ See Table 21 on page 67 for default fan configuration for heat  
and cool modeꢀ During unoccupied mode, the fan cycles between  
high speed and off with heating and cooling fan modesꢀ If the re-  
quested speed is off, the fan always remains offꢀ  
Fan Mode Operation  
During dehumidification, when the fan is on Auto, the fan speed can  
66  
UNT-IOM-6  
Tracer® ZN.520  
switch depending on the errorꢀ Fan speed increases as the space  
temperature rises above the active cooling setpointꢀ  
Table 21ꢀ Fan Configuration  
Auto fan operation  
Fan speed default  
Heating Continuous  
Off  
Low  
Medium  
High  
CoolingContinuous  
Low  
Off  
Medium  
High  
Additional flexibility built into the controller allows you to enable or  
disable the local fan switch inputꢀ The fan mode request can be either  
hardwired or communicated to the controllerꢀ When both are present,  
the communicated request has priority over the hardwired inputꢀ See  
the following tablesꢀ  
Table 22ꢀ Local fan switch disabled or not present  
Communicated fan speed input  
Fan operation  
Off  
Off  
Low  
Low  
Medium  
High  
Medium  
High  
Auto (or not present)  
Auto (fan runs at the default speed)  
Table 23ꢀ Local fan switch enabled  
Communicated  
fan speed input  
Off  
Low  
Medium  
High  
Fan switch (local)  
Fan operation  
Ignored  
Ignored  
Ignored  
Ignored  
Off  
Off  
Low  
Medium  
High  
Auto  
Low  
Medium  
High  
Auto  
Off  
Low  
Medium  
High  
Auto (configured default, determined by heat/cool mode)  
Table 24ꢀ Fan operation in heating and cooling modes  
UNT-IOM-6  
67  
Tracer® ZN.520  
Heating  
Cooling  
Fan mode  
Off  
Occꢀ Unoccꢀ  
Occꢀ  
Off  
Unoccꢀ  
Off  
Off  
Off  
Low  
Medium  
High  
Low  
Med Off/High  
High Off/High  
Off/High  
Low  
Med  
High  
Default  
fan spꢀ  
Off/High  
Off/High  
Off/High  
Off/High  
Auto (continuous) Default Off/High  
fan spꢀ  
During occupied and occupied standby modes, the fan normally is  
onꢀ For multiple speed fan applications, the fan normally operates at  
the selected or default speed (off, high, medium, or low)ꢀ When fan  
mode is auto, the fan operates at the default fan speedꢀ  
Continuous Fan  
Operation  
During unoccupied mode, the controller controls the fan offꢀ While  
unoccupied, the controller heats and cools to maintain the unoccu-  
pied heating and cooling setpointsꢀ In unoccupied mode, the fan is  
controlled on high speed only with heating or coolingꢀ  
The unit fan is always off during occupied, occupied standby, and  
unoccupied modes when the unit is off due to a diagnostic or when  
the unit is in the off mode due to the local zone sensor module, a  
communicated request, or the default fan speed (off)ꢀ  
If both a zone sensor module and communicated request exist, the  
communicated request has priorityꢀ  
Tracer® ZNꢀ520 does not support fan cycling in occupied modeꢀ The  
fan cycles between high speed and off in the unoccupied mode onlyꢀ  
The controller’s cascade control algorithm requires continuous fan  
operation in the occupied modeꢀ  
Fan Cycling  
Operation  
When a heating output is controlled off, the Tracer® ZNꢀ520 controller  
automatically holds the fan on for an additional 30 secondsꢀ This 30-  
second delay gives the fan time to blow off any residual heat from the  
heating source, such as a steam coilꢀ When the unit is heating, the  
fan off delay is normally applied to control the fan; otherwise, the fan  
off delay does not applyꢀ  
Fan Off Delay  
68  
UNT-IOM-6  
Tracer® ZN.520  
Fan Start on High Speed  
On a transition from off to any other fan speed, the Tracer® ZNꢀ520  
controller automatically starts the fan on high speed and runs the fan  
at high speed for 0ꢀ5 secondsꢀ This provides the ample torque  
required to start all fan motors from the off positionꢀ  
Tracer® ZNꢀ520 can sample the entering water temperature for all  
hydronic main coil changeover unitsꢀHydronic heating/cooling  
changeover operation requires central plant operation, and the unit  
controller must use an entering water temperature sensor to verify  
delivery of the desired water temperature from the central plantꢀ  
Entering Water  
Temperature  
Sampling Function  
When three-way valves are ordered with a Tracer® ZNꢀ520 control, the  
controller is factory-configured to disable the entering water tempera-  
ture sampling function, and the entering water sensor is mounted in  
the proper locationꢀ Disabling entering water temperature sampling  
eliminates unnecessary water flow through the main coil when three-  
way valves are usedꢀ  
The Tracer® ZNꢀ520 controller offers a control solution for two-way  
valve applications that does not require special unit considerations,  
such as those required by bleed linesꢀ The controller includes an  
entering water temperature sampling function that periodically opens  
the two-way valve to allow temporary water flow, producing reliable  
entering water temperature measurementꢀ  
Only units using the main hydronic coil for both heating and cooling  
(2-pipe changeover and 4-pipe changeover units) use the entering  
water temperature sampling functionꢀ Two-pipe changeover and 4-pipe  
changeover applications allow the main coil to be used for heating  
and for cooling; therefore, these applications require an entering water  
temperature sensorꢀ  
The entering water temperature value is useful to the unit controller  
only when heating or cooling is requiredꢀ The entering water tempera-  
ture must be five degrees above the space temperature for hydronic  
heating and five degrees below the space temperature for hydronic  
coolingꢀ When water flows normally and frequently through the coil,  
the controller does not invoke the sampling function because the  
water temperature is satisfactory for the desired heating or coolingꢀ  
The controller invokes entering water temperature sampling only when  
the measured entering water temperature is too cool to heat or too  
warm to coolꢀ Entering water is cold enough to cool when it is five  
degrees below the measured space temperatureꢀ Entering water is  
Heating or Cooling Required  
UNT-IOM-6  
69  
Tracer® ZN.520  
warm enough to heat when it is five degrees above the measured  
space temperatureꢀ  
When the controller invokes the entering water temperature sampling  
function, the unit opens the main hydronic valve for no more than  
three minutes before considering the measured entering water  
temperatureꢀ An initial stabilization period is allowed to flush the coilꢀ  
This period is equal to 30 seconds plus ½ the valve stroke timeꢀ Once  
this temperature stabilization period has expired, the controller  
compares the entering water temperature against the effective space  
temperature (either hardwired or communicated) to determine whether  
the entering water can be used for the desired heating or coolingꢀ If  
the water temperature is not usable for the desired mode, the control-  
ler continues to compare the entering water temperature against the  
effective space temperature for a maximum of three minutesꢀ  
The controller automatically disables the entering water temperature  
sampling and closes the main hydronic valve when the measured  
entering water exceeds the high entering water temperature limit (110  
F)ꢀ When the entering water temperature is warmer than 110 F, the  
controller assumes the entering water temperature is hot because it  
is unlikely the coil would drift to a high temperature unless the actual  
loop temperature was very highꢀ  
If the entering water temperature is unusable — too cool to heat or  
too warm to cool — the controller closes the hydronic valve and waits  
60 minutes before initializing another samplingꢀ If the controller  
determines the entering water temperature is valid for heating or  
cooling, it resumes normal heating/cooling control and effectively  
disables entering water temperature sampling until it is requiredꢀ  
The Tracer® ZNꢀ520 controller supports 1- or 2-stage electric heat  
operation for heatingꢀ To control the space temperature, electric heat  
is cycled to control the discharge air temperatureꢀ The rate of cycling  
is dependent upon the load in the space and the temperature of the  
incoming fresh air from the economizer (if any)ꢀTwo-pipe changeover  
units with electric heat use the electric heat only when hot water is  
not availableꢀ  
Electric Heat Operation  
Fresh Air Damper  
Options  
Manual  
Units with the manual fresh air damper option ship with the damper in  
the closed position, which is adjustable from zero to 100 percent in  
25 percent incrementsꢀ To adjust the position, first remove the air filter  
70  
UNT-IOM-6  
Tracer® ZN.520  
to expose the damper stop screw on the control panel endꢀ Relocate  
the stop screw to the appropriate positionꢀ Then loosen the stop  
screw wingnut and adjust the linkageꢀ  
Economizer Damper  
With a valid outdoor air temperature (either hardwired or communi-  
cated), Tracer® ZNꢀ520 uses the modulating economizer damper as  
the highest priority source of coolingꢀ Economizer operation is only  
possible through the use of a modulating damperꢀ  
Economizing is possible during the occupied, occupied standby,  
unoccupied, and occupied bypass modesꢀ  
The controller initiates the economizer function if the outdoor air  
temperature is cold enough to be used as free cooling capacityꢀ If the  
outdoor air temperature is less than the economizer enable setpoint  
(absolute dry bulb), the controller modulates the outdoor air damper  
(between the active minimum damper position and 100%) to control  
the amount of outdoor air cooling capacityꢀ When the outdoor air  
temperature rises 5 F above the economizer enable point, the control-  
ler disables economizing and moves the outdoor air damper back to  
its predetermined minimum position based on the current occupancy  
mode or communicated minimum damper positionꢀ  
Table 25ꢀ Relationship Between Outdoor Temperature Sensors  
and Damper Position  
Outdoor Air Tempꢀ  
None or invalid  
Failed  
Modulating Outdoor Air Damper  
Occꢀ or  
Occꢀ standby Unoccꢀ  
Occꢀ bypass  
Open to occꢀ  
minꢀposꢀ  
Open to occꢀ  
standby  
minꢀ posꢀ  
Open to occꢀ  
standby  
Closed  
Closed  
Open to occꢀ  
minꢀposꢀ  
minꢀ posꢀ  
Present and econꢀ  
feasible  
Economizing: Economizing: Open and  
min posꢀ-100% between occꢀ econꢀ only  
standby minꢀ  
posꢀ-100%  
when unit  
operating,  
closed  
otherwise  
Present and econꢀ  
not feasible  
Open tooccꢀ  
minꢀ posꢀ  
Open to occꢀ  
standby  
Closed  
minꢀ posꢀ  
UNT-IOM-6  
71  
Tracer® ZN.520  
Dehumidification  
Dehumidification is possible when mechanical cooling is available,  
the heating capacity is located in the reheat position, and the space  
relative humidity setpoint is validꢀThe controller starts dehumidifying  
the space when the space humidity exceeds the humidity setpointꢀ  
The controller continues to dehumidify until the sensed humidity falls  
below the setpoint minus the relative humidity offsetꢀThe controller  
uses the cooling and reheat capacities simultaneously to dehumidify  
the spaceꢀ While dehumidifying, the discharge air temperature is  
controlled to maintain the space temperature at the current setpointꢀ  
A typical scenario involves high humidity and high temperature load of  
the spaceꢀThe controller sets the cooling capacity to 100% and uses  
the reheat capacity to warm the discharge air to maintain space  
temperature controlꢀDehumidification may be disabled via Tracer or  
configurationꢀ  
Note: If the unit is in the unoccupied mode, the dehumidification  
routine will not operateꢀ  
Data Sharing  
Because this controller utilizes LonWorks™ technology, the control-  
ler can send or receive data (setpoint, heat/cool mode, fan request,  
space temperature, etcꢀ) to and from other controllers on the commu-  
nication link, with or without the existence of a building automation  
systemꢀ This applies to applications where multiple unit controllers  
share a single space temperature sensor (for rooms with multiple  
units but only one zone sensor) for both standalone (with communica-  
tion wiring between units) and building automation system applica-  
tionsꢀ For this application you will need to use the Rover service toolꢀ  
For more information on setup, refer to the Trane publication EMTX-  
IOP-2ꢀ  
Binary Inputs  
The Tracer® ZNꢀ520 controller has four available binary inputsꢀ Nor-  
mally, these inputs are factory-configured for the following functions:  
• Binary input 1: Low temperature detection (freezestat)  
• Binary input 2: Condensate overflow  
• Binary input 3: Occupancy/ Generic  
• Binary input 4: Fan status  
Note: The generic binary input can be used with a Tracer Summit®  
building automation system onlyꢀ  
Each binary input default configuration (including normally open/  
closed) is set at the factoryꢀHowever, you can configure each of the  
four binary inputs as normally open or normally closedꢀ The controller  
will be set properly for each factory-supplied binary input end-deviceꢀ  
When no device is connected to the input, configure the controller’s  
72  
UNT-IOM-6  
Tracer® ZN.520  
Table 26ꢀ Binary Input Configurations  
Binary  
Controller operation  
Input Description  
Configuration  
Normally closed  
Contact closed  
Normal  
Contact open  
Diagnostic  
(note 5)  
Diagnostic  
(note 5)  
BI 1  
BI 2  
BI 3  
BI 3  
BI 4  
Low temperature  
detection (Note 1)  
Condensate overflow (Note 1)  
Normally closed  
Normally open  
Normally open  
Normally open  
Normal  
Occupancy  
Unoccupied  
Normal (Note 3)  
Normal  
Occupied  
Generic binary input  
Fan status (Note 1)  
Normal  
(Note 3)  
Diagnostic  
(Note 4)  
Note 1: During low temperature, condensate overflow, and fan status diagnostics, the Tracer® ZNꢀ520  
control disables all normal unit operation of the fan, valves, and damperꢀ  
Note 2: The occupancy binary input is for standalone unit controllers as an occupied/unoccupied inputꢀ  
However, when the controller receives a communicated occupied/unoccupied request, the communicated  
request has priority over the hardwired inputꢀ  
Note 3: The generic binary input does not affect unit operationꢀ A building automation system reads this  
input as a generic binary input  
Note 4: If the fan mode input is in the off position or the controller is in the unoccupied mode with the fan  
off, the fan status input will be openꢀ A diagnostic will not be generated when the controller commands the  
fan offꢀ A diagnostic will only be generated if the fan status input does not close after one minute from  
energizing a fan output or any time the input is open for one minuteꢀ The controller waits up to one minute  
after energizing a fan output to allow the differential pressure to build up across the fanꢀ  
Note 5: The table below shows the controller’s response to low temperature detection, condensate  
overflow, and fan status diagnosticsꢀ  
input as not usedꢀ  
BIP  
Description  
Fan  
Valve  
Electric heat  
Damper  
BI 1  
BI 2  
BI 4  
Low temperature detection  
Condensate overflow  
Fan status  
Off  
Off  
Off  
Open  
Closed  
Closed  
Off  
Off  
Off  
Closed  
Closed  
Closed  
UNT-IOM-6  
73  
Tracer® ZN.520  
Binary Outputs  
Binary outputs are configured to support the following:  
• Three fan stages (when one or two fan stages are present, medium  
fan speed can be configured as exhaust fan)  
• One hydronic cooling stage  
• One hydronic heating stage (dehumidification requires this to be in  
the reheat position)  
• One DX cooling stage  
• One- or two-stage electric heat (dehumidification requires this to be  
in the reheat position)  
• Face and bypass damper  
• Modulating outdoor air damper  
• One baseboard heat stage  
Table 27ꢀ Binary Output Configuration  
Binary Output  
Configuration  
J1-1  
J1-2  
J1-3  
J1-4  
J1-5  
Fan high  
Fan medium  
Fan low  
(Key)  
Cool valve – open, or 2 position valve,  
(Note 1)  
J1-6  
J1-9  
Cool valve – close (Note 1)  
Heat valve – open, or 2 position valve, or 1st  
Electric heat stage (Note 1)  
Heat valve – close or 2nd Electric heat stage  
(Note 1)  
J1-10  
J1-11  
J1-12  
TB4-1  
TB4-2  
Fresh air damper - open  
Fresh air damper - close  
Generic / Bbaseboard heat output  
24VAC  
Note 1: For Tracer® ZNꢀ520 units configured and applied as 2-pipe  
hydronic heat/cool changeover, terminals J1-5 and J1-6 are used to  
control the primary valve for both heating and coolingꢀ For Tracer®  
ZNꢀ520 units configured and applied as 2-pipe hydronic heat/cool  
changeover with electric heat, terminals J1-5 and J1-6 are used to  
control the primary valve (for both cooling and heating), and terminals  
J1-9 and J1-10 are used only for the electric heat stageꢀ For those 2-  
pipe changeover units, electric heat will not be energized while the  
hydronic supply is hot (5 or more degrees above the space tempera-  
ture)ꢀ  
74  
UNT-IOM-6  
Tracer® ZN.520  
Analog Inputs  
Table 28ꢀ Analog Inputs  
Description  
Terminals  
Function  
Range  
Zone  
TB3-1  
Space temperature input  
5° to 122°F (-15° to 50°C)  
Ground  
Set  
TB3-2  
TB3-3  
TB3-4  
Analog ground  
Setpoint input  
Fan switch input  
NA  
40° to 115°F (4ꢀ4° to 46ꢀ1°C)  
Fan  
4821 to 4919 W (Off)  
2297 to 2342 W (Auto)  
10593 to 10807 W (Low)  
13177 to 13443 W (Medium)  
15137 to 16463 W (High)  
Ground  
TB3-6  
Analog ground  
NA  
Analog Input 1 J3-1  
J3-2  
Entering water temperature  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
Analog Input 2 J3-3  
J3-4  
Discharge air temperature  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
Analog Input 3 J3-5  
J3-6  
Fresh air temp/Generic temp  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
Analog Input 4 J3-7  
Universal Input  
Generic 4-20ma  
Humidity  
0 – 100%  
0 – 100%  
0 – 2000ppm  
CO2  
J3-8  
Analog ground  
NA  
NA  
Ground  
J3-9  
Analog ground  
Notes:  
1) The zone sensor, entering water temperature sensor, discharge air sensor, and the outside air tempera-  
ture sensor are 10KW thermistorsꢀ  
2) Zone sensor:  
Wall mounted sensors include a thermistor soldered to the sensor’s circuit boardꢀ  
Unit mounted sensors include a return air sensor in the units return air streamꢀ  
3) Changeover units include an entering water temperature sensorꢀ  
UNT-IOM-6  
75  
Tracer® ZN.520  
The Tracer® ZNꢀ520 controller accepts the following zone sensor  
module inputs:  
Zone Sensor  
• Space temperature measurement (10kW thermistor)  
• Local setpoint (either internal or external on the zone sensor  
module)  
• Fan switch  
• Timed override (On) and Cancel timed override  
• Communication jack  
Space Temperature  
Measurement  
Trane zone sensors use a 10kW thermistor to measure the space  
temperatureꢀ Typically, zone sensors are wall-mounted in the room  
and include a space temperature thermistorꢀ As an option, the zone  
sensor can be unit-mounted with a separate space temperature  
thermistor located in the unit’s return air streamꢀ If both a hardwired  
and communicated space temperature value exist, the controller  
ignores the hardwired space temperature input and uses the commu-  
nicated valueꢀ  
Zone sensors with an external setpoint adjustment (1kW) provide the  
Tracer® ZNꢀ520 controller with a local setpoint (50 to 85 F or 10 to  
29ꢀ4 C)ꢀ The external setpoint is exposed on the zone sensor’s front  
coverꢀ  
External Setpoint Adjustment  
When the hardwired setpoint adjustment is used to determine the  
setpoints, all unit setpoints are calculated based on the hardwired  
setpoint value, the configured setpoints, and the active mode of the  
controllerꢀ The hardwired setpoint is used with the controller’s occu-  
pancy mode (occupied, occupied standby, or unoccupied), the  
heating or cooling mode, the temperature deadband values, and the  
heating and cooling setpoints (high and low limits) to determine the  
controller’s active setpointꢀ  
When a building automation system or other controller communicates  
a setpoint to the controller, the controller ignores the hardwired  
setpoint input and uses the communicated valueꢀ The exception is  
the unoccupied mode, when the controller always uses the stored  
default unoccupied setpointsꢀ After the controller completes all  
setpoint calculations, based on the requested setpoint, the occu-  
pancy mode, the heating and cooling mode, and other factors, the  
calculated setpoint is validated against the following setpoint limits:  
• Heating setpoint high limit  
• Heating setpoint low limit  
• Cooling setpoint high limit  
• Cooling setpoint low limit  
76  
UNT-IOM-6  
Tracer® ZN.520  
These setpoint limits only apply to the occupied and occupied  
standby heating and cooling setpointsꢀ These setpoint limits do not  
apply to the unoccupied heating and cooling setpoints stored in the  
controller’s configurationꢀ  
When the controller is in unoccupied mode, it always uses the stored  
unoccupied heating and cooling setpointsꢀThe unit can also be  
configured to enable or disable the local (hardwired) setpointꢀ This  
parameter provides additional flexibility to allow you to apply commu-  
nicated, hardwired, or default setpoints without making physical  
changes to the unitꢀ  
Similar to hardwired setpoints, the effective setpoint value for a  
communicated setpoint is determined based on the stored default  
setpoints (which determines the occupied and occupied standby  
temperature deadbands) and the controller’s occupancy modeꢀ  
The zone sensor fan switch provides the controller with an occupied  
(and occupied standby) fan request signal (Off, Low, Medium, High,  
Auto)ꢀ If the fan control request is communicated to the controller, the  
controller ignores the hardwired fan switch input and uses the com-  
municated valueꢀ The zone sensor fan switch input can be enabled or  
disabled through configuration using the Rover service toolꢀ If the zone  
sensor switch is disabled, the controller resorts to its stored configu-  
ration default fan speeds for heating and cooling, unless the controller  
receives a communicated fan inputꢀ  
Fan Switch  
When the fan switch is in the off position, the controller does not  
control any unit capacityꢀ The unit remains powered and all outputs  
drive to the closed positionꢀUpon a loss of signal on the fan speed  
input, the controller reports a diagnostic and reverts to using the  
default fan speedꢀ  
Momentarily pressing the on button during unoccupied mode places  
the controller in occupied bypass mode for 120 minutesꢀ You can  
adjust the number of minutes in the unit controller configuration using  
Rover service toolꢀ The controller remains in occupied bypass mode  
until the override time expires or until you press the Cancel buttonꢀ  
Communication jack  
On/Cancel Buttons  
Use the RJ-11 communication as the connection point from Rover™  
service tool to the communication link—when the communication  
jack is wired to the communication link at the controllerꢀ By access-  
ing the communication jack via Rover™, you gain access to any  
controller on the linkꢀ  
UNT-IOM-6  
77  
Tracer® ZN.520  
Table 29ꢀ Zone sensor wiring connections  
TB1  
1
2
Description  
Space temperature  
Common  
3
Setpoint  
4
Fan mode  
5
6
Communications  
Communications  
The Tracer® ZNꢀ520 controller communicates via Trane’s Comm5  
protocolꢀ Typically, a communication link is applied between unit  
controllers and a building automation systemꢀ Communication also is  
possible via Rover, Trane’s service toolꢀ Peer-to-peer communication  
across controllers is possible even when a building automation  
system is not presentꢀYou do not need to observe polarity for Comm5  
communication linksꢀ  
Communications  
The controller provides six 0ꢀ25-inch quick-connect terminals for the  
Comm5 communication link connections, as follows:  
• Two terminals for communication to the board  
• Two terminals for communication from the board to the next unit  
(daisy chain)  
• Two terminals for a connection from the zone sensor back to the  
controller  
78  
UNT-IOM-6  
Tracer® ZN.520  
Diagnostics  
Table 30ꢀ Tracer® ZNꢀ520 Diagnostics  
Diagnostic  
Fan  
Other Outputs (Note 1)  
Condensate overflow  
Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Low temperature detection  
Low air flow - fan failure  
Off  
Off  
Off  
On  
Valves Open, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Enabled (Note 2), Fresh air damper  
Enabled (Note 2), electric heat Enabled (Note 2), Baseboard  
heat Off  
Space temperature failure  
Entering water temp failure  
Discharge air temp low limit  
Discharge air temp failure  
Fresh air temp failure  
Relative humidity failure  
Generic 4-20ma failure  
CO2 Input failure  
Off  
Off  
On  
On  
On  
On  
On  
On  
On  
Off  
Valves Open, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off,  
Valves Enabled, Fresh air damper Minimum position3, electric  
heat Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, Electric Heat  
Enabled, Baseboard heat Enabled  
Maintenance required  
Local fan mode failure  
Local setpoint failure  
Invalid unit configuration  
Normal – power up  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Disabled, Fresh air damper Disabled, electric heat  
Disabled, Baseboard heat Disabled  
Valves Enabled, Fresh air damper Enabled, Electric heat  
Enabled  
On  
Note 1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnosticsꢀ  
Note 2: When the entering water temperature is required but not present, the Tracer® ZNꢀ520 controller  
generates a diagnostic to indicate the sensor loss conditionꢀ The controller automatically clears the  
diagnostic once a valid entering water temperature value is present (non-latching diagnostic)ꢀ When the  
entering water temperature sensor fails, the controller prohibits all hydronic cooling operation, but allows  
the delivery of heat when heating is requiredꢀ In the Cool mode, all cooling is locked-out, but normal fan  
and outdoor air damper operation is permittedꢀ  
UNT-IOM-6  
79  
Tracer® ZN.520  
Note 3: When the outdoor air temperature sensor has failed or is not  
present, the Tracer® ZNꢀ520 controller generates a diagnostic to  
indicate the sensor loss conditionꢀ The controller automatically clears  
the diagnostic once a valid outdoor air temperature value is present  
(non-latching diagnostic)ꢀ When the outdoor air temperature sensor  
fails or is not present, the controller prohibits economizer operationꢀ  
The controller senses and records each diagnostic independently of  
other diagnosticsꢀ It is possible to have multiple diagnostics present  
simultaneouslyꢀ The diagnostics are reported in the order they occurꢀ  
Possible diagnostics include:  
• Low Temperature Detection  
• Low Air Flow - Fan Status  
• Space Temperature Failure1  
• Discharge Air Temp Failure1  
• Local Setpoint Failure1  
• CO2 Sensor Failure1  
• Condensate Overflow  
• Discharge Air Temp Limit  
• Entering Water Temp Failure1  
• Outdoor Air Temp Failure1  
• Local Fan Mode Failure1  
• Generic AIP Failure1  
• Defrosting Compressor Lockout1  
• Invalid Unit Configuration  
• Discharge air low limit  
• Humidity Input Failure1  
• Maintenance Required  
Translating Multiple  
Diagnostics  
• Generic temperature failure  
1 Non-latching diagnostics automatically reset when the input is  
present and validꢀ  
There are six ways to reset unit diagnostics:  
• Automatically by the controller  
• By initiating a manual output test at the controller  
• By cycling power to the controller  
• By using a building automation system  
• By using the Rover service tool  
• By using any other communicating device able to access the  
controller’s diagnositc reset input  
• By cycling the fan switch from off to any speed setting  
Automatically: The Tracer® ZNꢀ520 controller includes an automatic  
diagnostic reset functionꢀThis function attempts to automatically  
recover a unit when the Low Temperature Detection diagnostic  
occursꢀWhen this diagnostic occurs, the controller responds as  
defined in the Diagnostics table in the previous Summary sectionꢀ  
After the controller detects the Low Temperature Detection diagnos-  
tic, the unit waits 30 minutes before invoking the automatic diagnostic  
reset functionꢀThe automatic diagnostic reset function clears the Low  
Temperature Detection diagnostic and attempts to restore the control-  
ler to normal operationꢀThe controller resumes normal operation until  
another diagnostic occursꢀ  
Resetting  
Diagnostics  
80  
UNT-IOM-6  
Tracer® ZN.520  
If a Low Temperature Detection diagnostic recurs within 24 hours after  
an automatic diagnostic reset, you must manually reset the diagnos-  
ticꢀ See other possible methods for resetting diagnostics in this  
sectionꢀ  
Manual output test: You can use the Test button on the controller  
either during installation to verify proper end device operation or during  
troubleshootingꢀWhen you press the Test button, the controller  
exercises all outputs in a predefined sequenceꢀ The first and last  
outputs of the sequence reset the controller diagnosticsꢀ See the  
previous section for more information about the manual output testꢀ  
Cycling power: When someone turns off the controller’s 24 VAC  
power, then re-applies power, the unit cycles through a power up  
sequenceꢀBy default, the controller attempts to reset all diagnostics  
at power upꢀDiagnostics present at power up and those that occur  
after power up are handled according to the defined unit diagnostics  
sequences (see previous Diagnostics table)ꢀ  
Building automation system: Some building automation systems can  
reset diagnostics in the Tracer® ZNꢀ520 controllerꢀFor more complete  
information, refer to the product literature for the building automation  
systemꢀ  
Rover™ service tool: Rover service tool can reset diagnostics in the  
Tracer® ZNꢀ520 controllerꢀ For more complete information, refer to the  
Rover™ Installation, Operation, and Programming manualꢀ  
Diagnostic reset: Any device that can communicate the network  
variable nviRequest (enumeration “clear_alarm”) can reset diagnostics  
in the Tracer® ZNꢀ520 controllerꢀThe controller also attempts to reset  
diagnostics whenever power is cycledꢀ  
Cycling the fan switch: If the user cycles the fan speed switch from  
off to any speed, the controller resets all diagnosticsꢀDiagnostics  
may recur immediately if the problem still existsꢀ  
The green LED normally indicates whether or not the controller is  
powered on (24 VAC)ꢀ  
UNT-IOM-6  
81  
Tracer® ZN.520  
Table 31ꢀ Red Service LED Activity  
LED Operation  
LED Activity  
Description  
Red Service LED  
Off continuously after  
power is applied to the  
controllerꢀ  
Normal operation  
On continuously, even when  
power is first applied to the  
controllerꢀ  
Someone is pressing the Service  
button or the controller has failedꢀ  
LED flashes about once  
every secꢀ  
Uninstall (normal controller mode)ꢀ  
Use Rover™ service tool to restore  
normal unit operationꢀ  
Black Service push button  
Use the Service button to install the  
Tracer® ZNꢀ520 controller in a  
communication networkꢀ  
Caution: If the Service push button is held down for more  
than 15 seconds, the Tracer® ZN.520 controller will  
uninstall itself from the ICS™ communication network  
and shut down all unit operation. This mode is indicated  
by the red Service LED flashing once every second. See  
the Red Service LED section. Use Rover™ service tool to  
restore the unit to normal operation. Refer to the Rover™  
product literature for more information.  
82  
UNT-IOM-6  
Tracer® ZN.520  
Troubleshooting  
Green Status LED  
Table 32ꢀ Green Status LED activity  
Green LED activity  
On continuously  
Blinks (one blink)  
Description  
Power on (normal operation)  
The controller is in manual output test modeꢀ  
No diagnostics presentꢀ  
Blinks (2 blinks)  
The controller is in manual output test modeꢀ  
One or more diagnostics are presentꢀ  
Wink mode (Note 1)ꢀ  
LED blinks (1/4 secꢀ  
on, 1/4 secꢀ, off for  
10 sec)  
LED off  
Power is offꢀ  
Controller failureꢀ  
Test button is pressedꢀ  
Note 1: The Wink feature allows you to identify a controllerꢀ By  
sending a request from Rover service tool, you can request the  
controller to wink (blink on and off as a notification that the controller  
received the signal)ꢀ The green LED blinks (1/4 second on, 1/4  
second off for 10 seconds) during Wink modeꢀ  
Yellow Comm LED  
The yellow Comm LED blinks at the rate the controller receives  
communicationꢀ The yellow LED does not blink when the controller is  
transmitting communication dataꢀ  
Table 33ꢀ Yellow Comm LED Activity  
LED activity  
Description  
Off continuously  
The controller is not detecting any  
communicationꢀ (Normal for  
standalone applicationsꢀ)  
The controller detects communica  
tionꢀ (Normal for communicating  
applications, including data shar  
ingꢀ)  
LED blinks or flickers  
LED on continuously  
Abnormal condition or extremely  
high traffic on the linkꢀ  
The test sequence verifies outputand end device operationꢀ Use the  
manual output test to verify output wiring and actuator operation  
without using Rover™ service toolꢀ  
If the diagnostics remain after an attempt to clear diagnostics, the  
status LED indicates the diagnostic condition is still present and may  
affect the manual output testꢀSee the Green Status LED sectionꢀ  
Advancing completely through the test sequence terminates manual  
testꢀ The controller will time out if the unit remains in a single step for  
one hourꢀ  
UNT-IOM-6  
83  
Tracer® ZN.520  
The procedure for testing is:  
Manual Output Test  
1ꢀPress and hold the Test button for at least two seconds, then  
release the button to start the test modeꢀ When manual output test  
mode begins, the controller turns off all outputs and calibrates  
modulating end devices closedꢀ  
Test Sequence  
2ꢀ Press the Test button (no more than once per second) to advance  
through the test sequenceꢀ Alternatively, the manual output test can  
be controlled over the communications network by using Rover™ꢀ  
Table 34ꢀ Test Sequence  
Step  
Fan  
Main valve  
Electric heat  
or auxꢀ valve  
Fresh  
air  
damper  
Generic/  
baseboard  
heat  
J1-1  
J1-2  
J1-3  
J1-5  
J1-6  
J1-9  
J1-10 J1-11 J1-12  
TB4-1  
1: Off 1  
Off  
Off  
Off  
Off  
On  
Off  
aux: on Off  
EH: off  
On  
Off  
2
2: Fan High  
3: Fan Med  
4: Fan low  
High  
Off  
Off  
Off  
Off  
Low  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
On  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Med  
Off  
Off  
5: Main open  
High  
High  
High  
High  
Off  
6: Main close,  
EH1 on  
Off  
7: Aux open,  
EH1 on  
Exh  
Off  
8: Aux close,  
EH1 off, EH2 on,  
damper open  
9: Damper close High  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
On  
10: Generic/  
baseboard  
heat energized  
11: Exit 6  
High  
Exit  
1Upon entering manual output test mode, the controller turns off all fan and electric heat outputs and drives  
The green status LED is off when you press the Test buttonꢀTo begin  
LED Operation  
the manual output test mode, press and hold the Test button (which  
causes the green LED to go off) for at least two seconds, then  
release the buttonꢀThe green LED blinks, indicating the controller is in  
manual test modeꢀ  
84  
UNT-IOM-6  
Tracer® ZN.520  
Troubleshooting  
Table 35ꢀ Fan outputs do not energize  
Probable Cause  
Explanation  
Random start observed  
After power up, the controller always observes a random start from zero  
to 25 secondsꢀThe controller remains off until the random start time  
expiresꢀ  
Power up control wait  
Cycling fan operation  
Unoccupied operation  
When power up control wait is enabled (non-zero time), the controller  
remains off until one of two conditions occur:The controller exits power  
up control wait once it receives communicated informationꢀThe controller  
exits power up control wait once the power up control wait time expiresꢀ  
The controller operates the fan continuously when in the occupied,  
occupied standby, or occupied bypass modeꢀ When the controller is in  
the unoccupied mode, the fan is cycled between high speed and off with  
capacityꢀ  
When the controller is in the unoccupied mode, the fan is cycled  
between high speed and off with capacity to maintain zone temperature  
controlꢀ  
Fan mode off  
`
When a local fan mode switch (provided on the Trane zone sensor)  
determines the fan operation, the off position controls the unit offꢀ  
Requested mode off  
You can communicate a desired operating mode (such as off, heat,  
and cool) to the controllerꢀ When off is communicated to the controller,  
the unit controls the fan offꢀ There is no heating or coolingꢀ  
Diagnostic present  
A specific list of diagnostics affects fan operationꢀ For more information,  
see the Diagnostics sectionꢀ  
No power to the  
controller  
If the controller does not have power, the unit fan does not operateꢀ For  
the Tracer® ZNꢀ520 controller to operate normally, it must have an input  
voltage of 24 VACꢀ When the green LED is off continuously, the control  
ler does not have sufficient power or has failedꢀ  
Unit configuration  
Manual output test  
The controller must be properly configured based on the actual installed  
end devices and applicationꢀ When the unit configuration does not match  
the actual end devices, the valves may not work correctlyꢀ  
The controller includes a manual output test sequence you can use  
to verify output operation and associated output wiringꢀ However, based  
on the current step in the test sequence, the unit fan may not be onꢀ  
Refer to the Manual Output Test sectionꢀ  
Unit wiring  
The wiring between the controller outputs and the fan relays and con  
tacts must be present and correct for normal fan operationꢀ  
UNT-IOM-6  
85  
Tracer® ZN.520  
Table 36ꢀ Valves Stay Closed  
Probable Cause  
Explanation  
Requested mode off  
You can communicate a desired operating mode (such as off, heat, and  
cool) to the controllerꢀ When off is communicated to the controller, the  
unit controls the fan offꢀ There is no heating or cooling (valves are  
closed)ꢀ  
Power up control wait  
Manual output test  
When power up control wait is enabled (non-zero time), the controller  
remains off until one of two conditions occurs:The controller exits power  
up control wait once it receives communicated informationꢀThe controller  
exits power up control wait once the power up control wait time expiresꢀ  
The controller includes a manual output test sequence you can use to  
verify output operation and associated output wiringꢀ However, based on  
the current step in the test sequence, the valve(s) may not be openꢀ  
Refer to the Manual Output Test sectionꢀ  
Fan mode off  
When a local fan mode switch (provided on the Trane zone sensor)  
determines the fan operation, the off position controls the unit off and  
valves to closeꢀ  
Sampling logic  
The controller includes entering water temperature sampling logic which  
is automatically invoked during 2-pipe and 4-pipe changeover when the  
entering water temperature is either too cool or too hot for the desired  
heating or coolingꢀRefer to the Entering Water Temperature Sampling  
sectionꢀ  
Diagnostic present  
Unit configuration  
A specific list of diagnostic affects valve operationꢀ For more information,  
see the Diagnostics sectionꢀ  
The controller must be properly configured based on the actual installed  
end devices and applicationꢀ When the unit configuration does not match  
the actual end devices, the valves may not work correctlyꢀExample: A 2-  
pipe heat/cool changeover unit will not cool if the entering water tempera  
ture is too warm for cooling or if the entering water sensor is not presentꢀ  
The unit will not heat if the entering water temperature is too cool for  
heatingꢀ  
Unit wiring  
The wiring between the controller outputs and the valve(s) must be  
present and correct for normal valve operationꢀ  
Random start observed  
After power up, the controller always observes a random start from 0 to  
25 secondsꢀ The controller remains off until the random start time  
expiresꢀ  
86  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
The TUC is capable of operating  
in either a standalone application  
or interfacing with a Trane  
Tracer® systemꢀ In addition,  
Trane EveryWareä software is  
available to edit the configuration  
of the TUCꢀ  
The TUC board is easily access-  
ible on an isolation panel in the  
control panelꢀ The TUC board will  
pivot down in the control panel  
box after removing the screw on  
the top right corner of the panelꢀ  
See Figure 29ꢀ  
Figure 29. The TUC module  
board.  
TUC Sequence of Operations  
Off: Fan is off; control valve options and fresh air damper options  
closeꢀ The low air temperature detection option is still activeꢀ  
Auto: Fan speed control in the auto setting allows the modulating  
(three-wire floating point) control valve option and three-speed fan to  
work cooperatively to meet precise capacity requirements, while  
minimizing fan speed (motor/energy/acoustics) and valve position  
(pump energy/chilled water reset)ꢀ As the capacity requirement  
increases at low fan speed, the water valve opensꢀ When the low fan  
speed capacity switch point is reached, the fan switches to medium  
speed and the water valve repositions to maintain an equivalent  
capacityꢀ The reverse sequence takes place with a decrease in  
required capacityꢀ  
Low/Med/High: The fan will run continuously at the selected speed  
and the valve option will cycle to meet setpointꢀ  
UNT-IOM-6  
87  
Terminal Unit  
Control (TUC)  
For TUC controlled units that will interface with the Trane Tracer®  
system or Tracer Summit® building management system, terminate  
the communication wiring in the control box at the designated  
terminals on the low voltage terminal stripꢀ Reference the unit wiring  
schematic or submittalsꢀ  
Tracer®  
Communication  
Wiring  
Take care to maintain the correct polarity throughout the communica-  
tion wiring circuitꢀ  
Ground shields at each TUC, taping the opposite end of each shield  
to prevent any connection between the shield and another groundꢀ  
Refer to Trane publication, EMTX-IOP-1 Installation Operation and  
Programming Guide, for the communication wiring diagramꢀ  
Communication wire must conform to the following specification:  
· Shielded twisted pair 18 AWG  
· Capacitance 23 (21-25) picofarads (pF) per foot  
· Listing/Rating - 300V 150C NEC 725-2 (b) Class 2 Type  
CL2P  
· Trane Part Noꢀ 400-20-28 or equivalent, available through  
Trane BAS Buying Group Accessories catalog  
Follow these general guidelines when installing communication  
wiring:  
· Maintain a maximum 5000 ftꢀ aggregate run  
· Install all communication wiring in accordance with the  
NEC and all local codesꢀ  
· Solder the conductors and insulate (tape) the joint suffi-  
ciently when splicing communication wireꢀ Do not use wire  
nuts to make the spliceꢀ  
· Do not pass communication wiring between buildings  
because the unit will assume different ground potentialsꢀ  
· Do not run power in the same conduit or wire bundle with  
communication link wiringꢀ  
88  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Establish service communication to the TUC by connecting a twisted  
wire pair to one of the following connection pointsꢀ  
· Remote zone sensor module  
· Low voltage terminal strip inside the control panel  
This will allow the technician to view and edit the TUC configuration  
and troubleshoot the unitꢀ However, control options ordered and the  
wiring practice followed in the field may limit the communication  
abilityꢀ  
Service  
Communication  
Wiring  
Route interconnection wiring from the TUC to provide service commu-  
nication at the wall-mounted zone sensor moduleꢀ Install wiring by  
referencing the unit wiring schematic and Table 3 on page 35 for  
appropriate wire sizesꢀ After wiring is complete, connect the comm4  
port on the zone sensor module with a telephone style RJ 11 connec-  
tor (Western Electric #616 or equivalent)ꢀ Run the telephone style  
connector to a laptop computer running Trane EveryWareä software  
to establish communicationꢀ  
Wall-Mounted  
Zone Sensor  
Module  
Zone sensors without interconnecting wiring:  
Establish service communication to the TUC by wiring to the low  
voltage terminal strip inside the control boxꢀ Reference the unit wiring  
schematic for the appropriate communication terminals on the low  
voltage terminal stripꢀ Maintain the correct polarity throughout the  
communication wiring circuitꢀ  
Once wiring is complete, use Trane EveryWareä software to commu-  
nicate to the TUCꢀ The comm4 connection can be made by the  
telephone style RJ 11 connector (Western Electric #616 or equivalent)  
on the zone sensor module and the computer using EveryWareä ꢀ  
Refer to Trane publication, EMTX-IOP-1 Installation Operation Pro-  
gramming Guide, to operate the TUC with Trane Integrated Comfortsm  
System (ICS)ꢀ The factory pre-programs the TUC with default values  
to control the temperature and unit air flowꢀ Use Tracer® building  
automation system or EveryWareä software to change the default  
valuesꢀ  
Terminal Unit  
Controller Start-Up  
Follow the procedure below to operate the TUC in a stand-alone  
operationꢀ  
1ꢀ Turn power on at the disconnect switch optionꢀ  
2ꢀ Position the fan mode switch to either high, medium, low, or the  
auto positionꢀ  
UNT-IOM-6  
89  
Terminal Unit  
Control (TUC)  
3ꢀ Rotate the setpoint dial on the zone sensor module to 55° F for  
cooling or 85° F for heatingꢀ  
The appropriate control valve will actuate assuming the following  
conditions:  
· Room temperature should be greater than 55° F and less  
than 85° F  
· For a 2-pipe fan-coil unit with an automatic changeover  
sensor, the water temperature input is appropriate for the  
demand placed on the unit, eꢀgꢀ cooling operation is re-  
quested and cold water (5° F lower than room temperature  
for a TUC) flows into the unitꢀ  
4ꢀ Select the correct temperature setpointꢀ  
Note: Select and enable zone sensor temperature settings to prevent  
freeze damage to unitꢀ  
TUCs connected to a Tracer® comm 4 communication link requires a  
unique addressꢀ Use the TUC’s eight DIP switches to set the ICS  
addressꢀ The address must be in the valid range of 33 to 96ꢀ See  
Table 21 on page 63 for address settingsꢀ  
TUC Human  
Interface  
To set the ICS address, perform the following steps:  
Setting the ICS Ad-  
dress for Tracer Com-  
munications  
1ꢀ Set the DIP switches to the correct addressꢀ ON implies that the  
DIP switch is pressed towards the DIP switch numberꢀ OFF implies  
that the DIP switch is pressed towards the OPEN positionꢀ  
2ꢀ Short and hold the test input (J11 and J12) until all LEDs are  
illuminatedꢀ Remove the jumper from the test inputꢀ This sets the  
address in the TUC EEPROMꢀ  
Note: Cycling power to the TUC forces the TUC to read the DIP  
switch settings (Rev 12 TUC or higher)ꢀ The TUC firmware version  
can be read from either Tracer or Everywareꢀ Additionally, the last two  
digits of the part number printed on the sticker on the TUC 1U1  
microprocessor indicate the TUC firmware version, ie: 6200-0028-13ꢀ  
The TUC operates the fan in the following modes:  
90  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Table 37ꢀ Valid TUC Addresses  
DIP Switch Position  
DIP Switch Position  
Address 1 2 3 4 5 6 7 8  
Address 1 2 3 4 5 6 7 8  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
50  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
61  
62  
63  
64  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
65  
66  
67  
68  
69  
70  
71  
72  
73  
74  
75  
76  
77  
78  
79  
80  
81  
82  
83  
84  
85  
86  
87  
88  
89  
90  
91  
92  
93  
94  
95  
96  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X  
X X  
X
X
X
X
X
X
X X  
X X  
X X X  
X X X  
X
X
X
X
X
X
X
X
X
X
X X  
X
X
X X  
X X  
X X  
X X  
X X  
X
X
X X X  
X X X  
X X X X  
X X X X  
X X  
X X  
X X  
X X  
X X  
X X  
X X  
X X  
X X X  
X X X  
X X X  
X X X  
X
X
X
X
X
X
X
X
X
X
X X  
X
X
X
X X  
X
X
X
X
X
X X  
X X  
X X X  
X X X  
X
X
X
X
X X  
X X  
X X  
X X  
X
X
X X  
X X X X  
X X X X  
X X X X X  
X X X  
X
X X X X  
X X X X  
X X X X X  
X X X X X X  
X
X X  
X
UNT-IOM-6  
91  
Terminal Unit  
Control (TUC)  
TUC Sequence of Operation  
· Occupied  
· Unoccupied  
· Tracer® with supply fan control  
Occupied  
In the occupied mode, the factory configures the TUC for continuous  
occupied fan cycleꢀ With the fan control set to auto, the fan operates  
at the required speed to meet the cooling or heating capacityꢀ  
However, the fan will run at one set speed continuously if set in the  
high, medium, or low positionꢀ  
Unoccupied  
In the unoccupied mode, the TUC cycles the fan between off and high  
speed to satisfy the unoccupied setpointꢀ However, if the occupied  
preheat damper position is closed and the room setpoint is 3° F  
above (cool down) or 3° F below (warm-up) setpoint, the fan runs at  
high speed when exiting the unoccupied mode to occupied modeꢀ  
Also, if the occupied preheat damper position is configured as  
closed, the fan will run in high speed any time the room temperature  
falls 3° F or below room setpoint in occupied heating modeꢀ  
Tracer® with supply fan control  
If the unit is communicating with Tracer® and the supply fan control  
programming point is configured for Tracer® (the factory configures as  
local), then Tracer® will control the fan regardless of the fan mode  
switch positionꢀ  
All TUC lockouts (latching diagnostics) are manually reset whenever  
the fan mode switch is set to the off position or when power is  
restored to the unitꢀ The last diagnostic to occur is retained until the  
unit power is disconnectedꢀ Refer to Trane publication, EMTX-IOP-1  
TUC Installation Operation and Programming Guide, for specific  
instructions regarding the procedure for running the TUCꢀ  
Adjust the cooling setpoint by using either the setpoint adjustment  
knob, resetting the TUC default values, or Tracer® downloaded valuesꢀ  
The factory configures the occupied heat or cool setpoint source for  
local modeꢀ The local mode allows the local setpoint knob to deter-  
mine the cooling setpoint If using Tracer® to define the heat or cool  
setpoint source, the TUC uses the Tracer® setpointsꢀ If Tracer® is not  
communicating, the TUC will attempt to obtain the heating and  
cooling setpoint from a local sourceꢀ If there is no input from a local  
source, the TUC will resort to its default valuesꢀ  
Cooling and  
Heating Operation  
Setpoint Control  
The TUC limits the parameters of the cooling setpoint input (adjust-  
able from either the setpoint knob or Tracer® ) to prevent excessively  
92  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
high or low temperaturesꢀ In addition, the TUC calculates the heating  
setpoint equal to the cooling setpoint minus an adjustable heating  
offsetꢀ Furthermore, the heating setpoint cannot exceed a value less  
than or equal to the cooling setpointꢀ The TUC is in the cooling mode  
when the space temperature rises 1° F above the cooling setpointꢀ  
The TUC is in the heating mode when the space temperature drops 1°  
F below the heating setpointꢀ The unoccupied setpoints are typically  
widened to account for night setback and are adjustable with either  
Tracer® or EveryWareä softwareꢀ  
Off Position  
Fan Mode  
Operation  
On a stand-alone TUC with the fan mode switch in the off position, all  
normal cooling and heating functions ceaseꢀ (eꢀgꢀ The fan does not  
run, the fresh air damper option closes, and the unoccupied mode  
disablesꢀ)  
High, Medium, or Low Postion  
With the fan mode switch in the high, medium, or low position; the  
fresh air damper option and the control valve(s) operate to maintain  
setpointꢀ  
Auto Position  
As the capacity requirement increases at low fan speed, the control  
valve gradually opensꢀ The fan speed increases to medium after  
reaching the low speed capacity switch pointꢀ This causes the control  
valve to reposition to maintain capacity, gradually opening as demand  
increasesꢀ The fan speed increases to high after reaching the medium  
speed capacity switch pointꢀ This causes the control valve to reposi-  
tion to maintain output capacity, gradually opening as demand  
increasesꢀ As capacity decreases, the control valve closes until  
reaching the fan switch pointꢀ After reaching the fan switch point, the  
fan speed decreases to medium with the control valve repositioning to  
maintain constant capacityꢀ As capacity decreases, the control valve  
closes until reaching the fan switch pointꢀ After reaching the fan  
switch point, the fan speed decreases to low with the control valve  
repositioning to maintain constant capacityꢀ At low speed, the control  
valve closes incrementally as demand decreasesꢀ  
UNT-IOM-6  
93  
Terminal Unit  
Control (TUC)  
The entering water temperature sampling function allows water to  
circulate in an attempt to sense water cold enough to provide coolingꢀ  
The function uses a timer to permit the controller and the valve to fully  
open while the water circulates for 3 minutesꢀ The fan continues to run  
at the selected speedꢀ If the changeover sensor does not sense the  
correct water temperature within this 3 minute cycle, the valve closes  
and the entering water temperature sampling function will cease until  
57 minutes elapseꢀ After this time lapse, the water circulates again  
through the unit to determine if the entering water temperature indi-  
cates a call for cooling or heatingꢀ  
Entering Water  
Temperature  
Sampling Function  
Note: The entering water temperature sampling function is for units  
with 2-way valvesꢀ This function is not necessary for units with 3-way  
valves since water flows continuously through this piping configura-  
tionꢀ  
Table 38ꢀ Unit Mode as Related to Water Temperature  
Unit Type  
EWT Sensor Required?  
Coil Water Temperature  
2-pipe changeover  
Yes  
· Can cool if:  
space temp - EWT ³ 5 deg F  
· Can heat if:  
EWT - space temp ³ 5 deg F  
· Can cool if:  
space temp - EWT ³ 5 deg F  
· Can heat if:  
EWT - space temp ³ 5 deg F  
4-pipe changeover  
Yes  
2-pipe heating only  
2-pipe cooling only  
4-pipe heat/cool  
No  
No  
No  
Hot water assumed  
Cold water assumed  
· Cold water assumed in main coil  
· Hot water assumed in auxꢀ coil  
The auxiliary electric heat option allows heating when the occupied  
space requires heating but the unit still has chilled system water  
flowing through itꢀ The electric heat is also sufficient for use as the  
sole source of heat for the unitꢀ  
2-Pipe with  
Auxiliary Electric  
Heat (Fan-coils)  
The TUC utilizes a heating only output to energize electric heat if  
hydronic heat is insufficient to meet the heating requirementsꢀ This  
output responds to a demand for heat as long as the entering water  
temperature is lower than 95° FHowever, if the water temperature  
reaches 95° F or higher, the electric heat lockout switch (on the  
supply water pipe) disengages the electric heatꢀ Electric heat be-  
comes available again when the entering water temperature falls to  
65° F or lower (± 5° F)ꢀ  
94  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Note: The auxiliary electric heat option is not available with a four-pipe  
fan-coil unitꢀ  
Units with manual fresh air  
dampers ship with the damper in  
the closed position, which is  
adjustable from zero to 100  
percent in 25 percent incre-  
mentsꢀ To adjust the position,  
first remove the air filter to  
Fresh Air Damper  
Options  
Manual  
expose the damper stop screw  
on the control panel endꢀ Relo-  
Figure 30. Re-locate the damper  
stop screw to adjust the damper  
position. The factory positions  
the stop screw in the 25% open  
position.  
cate the stop screw to the  
appropriate positionꢀ Then loosen  
the stop screw wingnut and  
adjust the linkageꢀ See Figure  
30ꢀ  
Units with an auto 2-position fresh air damper ship with a stop screw  
in the 25 percent reference positionꢀ The auto damper is adjustable to  
open from zero to 50 percent in 25 percent incrementsꢀ To adjust the  
damper position, remove the air filter to expose the damper stop  
screw on the control panel endꢀ Then relocate the stop screw to the  
appropriate positionꢀ See Figure 30ꢀ  
Auto 2-Position  
Note: The open position of the damper does not correspond to the  
amount of fresh airꢀ It is the installer’s responsibility to ensure that  
the building’s minimum fresh air requirements are met while taking  
necessary precautions to protect the unit during freeze conditionsꢀ  
The economizer damper option contains a modulating, 3-wire floating  
point actuator and a damper assemblyꢀ The factory sets the damper  
at a minimum 25 percent open position by configuring the TUCꢀ This  
setting is adjustable and can be changed in the field with EveryWareä  
software or Tracerâꢀ The minimum open position is adjustable from  
zero to 100 percent in one percent incrementsꢀ  
Economizer  
The economizer fresh air damper is controlled to the minimum  
position, which the factory configuresꢀ During the occupied mode,  
economizing is enabled and the fresh air temperature is measured  
while economizingꢀ  
Economizing is enabled within the TUC configuration based on an  
editable temperature differential between the fresh air temperature and  
the zone temperatureꢀ The unit will go into economizing mode when  
UNT-IOM-6  
95  
Terminal Unit  
Control (TUC)  
the outside air temperature falls to 10° F or more below the zone  
temperatureꢀ The TUC will control the damper to a position to produce  
optimal cooling during economizingꢀ If power is interrupted or the TUC  
is turned off, the damper will spring back to the closed positionꢀ  
If the occupied preheat damper position is configured as closed (the  
factory configures as open), the fresh air damper remains closed  
during the transition from unoccupied mode to occupied mode until  
the zone temperature is within 2° F of the heating setpoint (warm-up  
sequence), or cooling setpoint (cool-down sequence)ꢀ During the  
warm-up sequence, the damper fully closes, the fan operates on high  
speed, and the heating valve drives fully open to until the zone  
temperature approaches the occupied heating setpointꢀ If the zone  
temperature falls 3° F or more below the heating setpoint during the  
occupied mode, the TUC reinitiates the warm-up sequence until the  
zone temperature is within 2° F of the heating setpointꢀ  
If during the occupied heating mode, the TUC determines that no  
heating capacity is present and the zone temperature drops 3° F  
below the heating setpoint, the TUC closes the fresh air damper  
regardless of the occupied preheat damper positionꢀ The cool-down  
sequence has a maximum duration of one hour and cannot be  
reinitiated once the unit is in occupied modeꢀ  
All units ship from the factory with the damper in the closed positionꢀ  
Note: The open position of the damper does not correspond to the  
amount of fresh air provided to the unitꢀ It is the installer’s responsi-  
bility to ensure that the building’s minimum fresh air requirements are  
met while taking the necessary freeze conditon precautions to  
protect the unitꢀ  
96  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
The low temperature detection  
option protects the unit from  
BIP4: Low  
Temperature  
Detection Option  
freezing conditions by using a  
capillary line in the coil fins to  
detect freezing conditionsꢀ The  
TUC uses the low temperature  
sensor with a normally open  
valveꢀ When the sensor detects  
temperatures below 36° F, a binary  
input turns the fan off, closes the  
fresh air damper, disables the  
electric heat, and opens the con-  
trol valveꢀ This creates a shutdown  
Figure 31. The low temperature  
sensor is a capillary tube  
inserted into the coil to detect  
freezing conditions.  
latching diagnostic that requires a reset to resume normal operationꢀ  
However, normal operation cannot resume until the water temperature  
rises to 44° FSee Figure 31ꢀLow temperature detection is active  
even when the unit is off, but the TUC must remain powered for it to  
be functionalꢀ  
The factory configures the 24V dry contact input as normally closed  
to indicate alarmꢀ However, it also can be normally open  
if using the correct switchꢀ  
Note: While the low temperature detection sensor can help minimize  
the risk of coil freeze-up, it cannot prevent this from occurring in all  
circumstancesꢀ The user is responsible to adequately protect the unit  
from freeze conditionsꢀ  
Note: The capillary line of the low temperature detection sensor is in  
the section of the hydronic coil above the fan, nearest the control  
panel boxꢀ Locate the outside air wall box or ductwork so fresh air  
has a direct path into the fanꢀ This allows the sensor to detect an  
accurate fresh air temperature and proper operation of a dual fan unitꢀ  
Failure to do this could cause the low temperature detection sensor to  
incorrectly detect a potential freezing coilꢀ  
BIP3: Condensate  
Overflow  
Detection Device  
The condensate overflow detection device protects the unit from  
condensate water overflowꢀ The switch is a float-type device located in  
the fan-coil unit’s auxiliary drain panꢀ See the “Condensate Overflow  
Switch” section and Figures 12 and 13 on page 26ꢀ  
When there is a danger of condensate water overflow from the auxil-  
iary pan, the float rises with the water level in the panꢀ When the float  
rises to over 50 percent of its travel, the control valve closesꢀ Also, a  
binary input causes the fan to turn off, the fresh air damper to close,  
UNT-IOM-6  
97  
Terminal Unit  
Control (TUC)  
and the electric heat to disableꢀ This creates an immediate shutdown  
latching diagnostic, which requires a manual or Tracerâ reset to  
resume normal operationꢀ  
However, normal operation cannot resume until the water level  
recedes to an acceptable levelꢀ The switch will close after the water  
level recedes, and the active temperature control of the unit will  
resume by an automatic resetꢀ Since both the condensate overflow  
detection and occupied/unoccupied status occupy BIP3 on the TUC  
board, only one option can be in useꢀ The factory configures the 24V  
dry contact input as normally closed to indicate an alarmꢀ However, it  
also can be normally open if using the correct switchꢀ  
The smoke input is a binary input on the TUC that is used with a  
smoke detector switch (installer supplied) to signal an alarmꢀ Config-  
ure the input to either send an alarm to Tracer® or as a shutdown  
latching diagnosticꢀ If the input is configured as a shutdown latching  
diagnostic, the TUC closes the control valve(s), shuts the fan off,  
closes the fresh air damper, and disables electric heatꢀ  
BIP4: Smoke Input  
If the input is configured to send an alarm, Tracer will issue a system  
wide shutdown for the buildingꢀ The unit will continue to run, and no  
diagnostic will register within the TUCꢀ The factory configures the  
24V dry contact input as normally closedꢀ However, it can also be  
normally open if using the correct switchꢀ  
The unit can operate in the occupied/unoccupied mode when a  
binary signal is input from an external source such as a time clock or  
Tracer® ꢀ Reference the “TUC Fan Mode Operation” section on page  
65 for the sequence of operationsꢀ This option is only available if the  
condensate overflow input is not in use (if not using Tracer®), since  
both inputs occupy the same point on the TUC boardꢀ The factory  
configures the 24V dry contact input as normally closedꢀ However, it  
can also be normally open if using the correct switchꢀ A closed  
signal indicates occupied modeꢀ  
BIP3: Occupied/  
Unoccupied Mode  
The external interlock input allows the unit to be remotely stopped  
when a binary signal is input to the TUC from an external source or  
from Tracer®ꢀ Since both external interlock and condensate overflow  
input to the same point (if not using Tracer®) on the TUC board, only  
one input can be in useꢀ The factory configures the 24V dry contact  
input as normally closed, but it can also be open if using the correct  
switchꢀ  
BIP1: External  
Interlock  
98  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
The motion detection input when used with a motion detection switch  
(installer supplied) detects the absence of motion in the space during  
the occupied modeꢀ If no motion is detected, the TUC controls the  
space to alternate heating and cooling setpoints while also controling  
the economizer damper option to the minimum positionꢀ The factory  
configures the 24V dry contact input as normally closedꢀ However, it  
can also be normally open if using the correct switchꢀ A closed signal  
indicates alarmꢀ  
BIP2: Motion  
Detection  
The autocycle test is an operating mode that activates the TUC  
outputs in a defined series of stepsꢀ This function allows the techni-  
cian to to manually exercise each TUC output by sequentially  
stepping through the 16 stages of the autocycle test  
Autocycle Test  
Note: Do not leave unit unattended while in test mode because the  
unit safety shutdowns are not functionalꢀ  
Note: During the autocycle test, the TUC ignores all unit safety  
diagnosticsꢀ Take precautions to ensure the hydronic coil is not  
subject to freezing conditionsꢀ  
CAUTION: If the TUC is left in the autocycle test  
mode, it will automatically return to normal unit opera-  
tion after 60 minutes.  
!
To place the TUC in the autocycle test mode, perform the following  
stepsꢀ Refer to Table 23 onpge 72 for details on the stagingꢀ  
1ꢀ Read and record the initial TUC addressꢀ  
2ꢀ Set the TUC DIP switch #7 to ON (address = 2)ꢀ All other switches  
should be offꢀ  
3ꢀ To automatically cycle through the stages, short and hold the TUC  
test input (short J11 and J12 together)ꢀ Continue holding the test  
input and the unit will cycle to each subsequent stage every 30  
secondsꢀ  
4ꢀ To manually step between stages, momentarily short the test input  
to advance to the next test stageꢀ  
5ꢀ When the autocycle test is complete, return the DIP switches to  
the initial positions recorded in step 1ꢀ Short the test inputs to set the  
address in the TUC EEPROMꢀ  
UNT-IOM-6  
99  
Terminal Unit  
Control (TUC)  
Table 39ꢀ Autocycle Test Staging  
Stage LEDs (1) Fan-Coil Output Exercised  
1
2
3
4
0
1
2
3
Off  
l
Fan low speed  
Fan medium speed  
Fan high speed  
Economizer/damper  
Cooling valve  
Heating valve  
Electric heat stage 1  
Electric heat stage 2  
Not used  
l
l l  
4 ¡ l  
5 ¡ l ¡ l  
6 ¡ l l ¡  
7 ¡ l l l  
8 l ¡ ¡ ¡  
9 l ¡ ¡ l  
10 l ¡ l ¡  
11 l ¡ l l  
12 l l ¡ ¡  
13 l l ¡ l  
Reheat  
Not used  
Not used  
Not used  
14 l l l ¡  
15  
Not used  
Not used  
(1) l= the LED is illuminated  
¡= the LED is off  
100  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Reading Diagnostics  
Use the TUC human interface to read the current unit diagnosticꢀ If no  
diagnostics are present, the last diagnostic appearsꢀ  
Perform the following stepsꢀ Refer to Table 23 on page 72 for staging  
detailsꢀ  
1ꢀ Read and record the initial TUC addressꢀ  
2ꢀ Set the TUC DIP switch #5 to ON (address = 8)ꢀ  
3ꢀ Short and hold the test inputꢀ  
4ꢀ The LEDs will blink to define a diagnostic codeꢀ The diagnostic  
information will be displayed in a series of three blink sequencesꢀ  
Sequence 1: When the test input is shorted continuously,  
all LEDs go off for one secondꢀ  
Sequence 2: LED #5 will light to indicate that sequence 2 is  
currently being displayedꢀ LEDs one through  
four will display the first part of the diagnostic  
codeꢀ  
Sequence 3: LED #6 will light to indicate that sequence 3 is  
currently being displayedꢀ LEDs one through  
four will display the second part of the  
diagnostic codeꢀ  
5ꢀ Refer to Table 24 on page 74 to interpret the blink sequences’  
corresponding diagnostic codeꢀ  
6ꢀ Read and record the current diagnosticꢀ Then return the DIP  
switches to the initial positions recorded in step 1ꢀ Short the test  
inputs to set the address in the TUC EEPROMꢀ  
Example: Diagnostic blink sequences for condensate overflow (8B)  
Sequence 1  
Sequence 2  
Sequence 3  
1
2
3
4
1
2
3
4
1
2
3
4
¡ ¡ ¡ ¡  
¡ ¡  
l ¡ ¡ ¡  
l ¡  
l ¡ l l  
¡ l  
¡
¡
¡
5
6
7
5
6
7
5
6
7
UNT-IOM-6  
101  
Terminal Unit  
Control (TUC)  
Table 40ꢀ Blink Sequence Corresponding Diagnostic Codes  
Sequence 1 Sequence 2 Sequence 3  
1
2
3
4
1
2
3
4
1
2
3
4
Code  
Diagnostic  
Latch  
None  
Power failure  
None  
None  
Controller failure  
None  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡  
¡ ¡ ¡ ¡ l ¡ ¡ ¡ l ¡ l l  
¡ ¡ ¡ ¡ l ¡ ¡ l l ¡ l l  
00  
8B  
9B  
None  
N/A  
Yes  
No  
Condensate overflow  
Leaving water temp  
sensor 1 failure  
Zone and supply temp  
sensor failure  
¡ ¡ ¡ ¡ l ¡ l ¡ ¡ ¡ ¡ ¡  
A0  
No  
¡ ¡ ¡ ¡ l l ¡ ¡ l ¡ ¡ ¡  
¡ ¡ ¡ ¡ l l ¡ ¡ l ¡ l l  
¡ ¡ ¡ ¡ l l ¡ ¡ l l l l  
C8  
CB  
CF  
High EWT  
No  
Low EWT  
No  
Low tempꢀ detectꢀ or  
condensate overflow  
Low discharge air temp  
Yes  
¡ ¡ ¡ ¡ l l ¡ l ¡ ¡ l l  
¡ ¡ ¡ ¡ l l ¡ l ¡ l ¡ ¡  
¡ ¡ ¡ ¡ l l ¡ l ¡ l ¡ l  
¡ ¡ ¡ ¡ l l ¡ l l l ¡ l  
¡ ¡ ¡ ¡ l l l l l ¡ ¡ ¡  
¡ ¡ ¡ ¡ l l l l l l l ¡  
D3  
D4  
D5  
DD  
F8  
FE  
Yes  
Smoke alarm  
Yes/No  
Yes/No  
No  
High dischg air temp  
Low fresh air temp  
Bad configuration  
Return air high limit  
No  
Yes  
Reading the  
Operating  
Use the human interface to read the unit operating machine stateꢀ  
Machine State  
1ꢀ Read and record the initial TUC addressꢀ  
2ꢀ Set the TUC DIP switch #5 and #8 to ON (address = 9)ꢀ The  
remaining switches will be offꢀ  
3ꢀ Short and hold the test inputꢀ  
4ꢀ The LEDs will blink to define an operating machine stateꢀ The  
operating machine state information will be displayed in a series  
of three blink sequencesꢀ  
Sequence 1: When the test input is shorted continuously all  
LEDs go off for one secondꢀ  
Sequence 2: LED #5 will light to indicate that sequence 2 is  
currently being displayedꢀ LEDs one through four will display the  
first part of the operating machine stateꢀ  
Sequence 3: LED #6 will light to indicate that sequence 3 is  
currently being displayedꢀ LEDs one through four will display the  
second part of the operating machine stateꢀ  
5ꢀ Reference Table 25 on page 75 to interpret the operating machine  
state derived from the blink sequencesꢀ  
102  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
6ꢀ Read and record the operating machine stateꢀ Return the DIP  
switches to the initial positions recorded in step 1ꢀ Short the test  
inputs to set the address in the TUC EEPROMꢀ  
Example: Operating Machine State for Standby Mode  
Sequence 1  
Sequence 2  
Sequence 3  
1
2
3
4
1
2
3
4
1
2
3
4
¡ ¡ ¡ ¡  
¡ ¡  
¡ ¡ ¡ l  
l ¡  
¡ ¡ l ¡  
¡ l ¡  
¡
¡
5
6
7
5
6
7
5
6
7
Example: Operating control mode for purge mode  
Table 41ꢀ Operating Machine State LED Sequences and Codes  
Sequence 1 Sequence 2 Sequence 3  
1
2
3
4
1
2
3
4
1
2
3
4
Code  
Machine State  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l l ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ l ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l l ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l l l ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ l ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ l l ¡  
00  
2
Manufacturing Test  
Bad Configuration  
Auto Cycle Test  
Disable  
4
6
8
Stop  
10  
12  
14  
16  
18  
20  
22  
Calibration  
Latching Diagnostic  
Freeze Shutdown  
Soft Reset  
Standby  
Cooling  
Heating  
UNT-IOM-6  
103  
Terminal Unit  
Control (TUC)  
Using the human interface, read the operating control modeꢀ  
Reading the  
Operating Control  
Mode  
1ꢀ Read and record the initial TUC addressꢀ  
2ꢀ Set the TUC DIP switch #5 and #7 to ON (address = 10)ꢀ The  
remaining switches will be offꢀ  
3ꢀ Short and hold the test inputꢀ  
4ꢀ The LEDs will blink to define an operating control modeꢀ The  
operating control mode information will be displayed in a series of  
three blink sequencesꢀ  
Sequence 1: With the test input shorted continuously, all  
LEDs go off for one secondꢀ  
Sequence 2: LED #5 will light to indicate that sequence 2 is  
currently displayedꢀ LEDs one through four  
will display the first part of the operating control  
modeꢀ  
Sequence 3: LED #6 will light to indicate that sequence 3 is  
currently being displayedꢀ LEDs one through four  
will display the second part of the operating control  
modeꢀ  
5ꢀ Refer to Table 26 on page 77 to interpret the operating control  
mode derived from the blink sequencesꢀ  
6ꢀ After reading and recording the operating control mode, return the  
DIP switches to the positions recorded in step 1ꢀ Short the test  
inputs to set the address in the TUC EEPROMꢀ  
104  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Sequence 1  
Sequence 1  
Sequence 2  
Sequence 2  
Sequence 3  
Sequence 3  
1
2
3
4
1
2
3
4
1
2
3
4
¡ ¡ ¡ ¡  
¡ ¡  
¡ ¡ ¡ ¡  
l ¡  
¡ ¡ l ¡  
¡ l ¡  
¡
¡
5
6
7
5
6
7
5
6
7
Table 42ꢀ Operating Control Mode LED Sequences and Codes  
Sequence 1 Sequence 2 Sequence 3  
1
2
3
4
1
2
3
4
1
2
3
4
Code Control  
Mode  
Definition  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡  
0
Stop  
Diagnostic, user switch,  
Tracer® command or interlock  
has stopped the unit  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡  
2
Purge  
Incorrect entering water tempꢀ  
The TUC cannot meet the  
demandꢀ There is no other  
capacity availableꢀ  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡  
4
8
Tracer®  
Override  
The TUC received a Tracer®  
verrideꢀ Follow Tracer® output  
commandsꢀ  
Precool  
Precool  
Precool  
Unoccupied cooling with  
economizer, or water;  
occupied cooling feasibility  
checkꢀ  
Unoccupied cooling with  
EWT economizer while purging  
for sampling cold waterꢀ  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ l ¡ 10  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l l ¡ ¡ 12  
Unoccupied cooling with 100%  
cool economizer with water or  
compressor augmentationꢀ  
¡ ¡ ¡ ¡ ¡ ¡ ¡ ¡ l l l ¡ 14  
Econo-  
mizer  
Occupied cooling with econo-  
mizer  
¡ ¡ ¡ ¡ ¡ ¡ ¡ l ¡ ¡ ¡ ¡ 16  
Econo-  
mizer  
EWT  
Occupied cooling with econo-  
mizer while sampling for cold  
waterꢀ  
sampling  
UNT-IOM-6  
105  
Terminal Unit  
Control (TUC)  
Table 42—Continuedꢀ Operating Control Mode LED Sequences and Codes  
Sequence 1 Sequence 2 Sequence 3  
2 3  
1
2
3
4
1
2
3
4
1
4
Code Control  
Mode  
Definition  
¡ ¡ ¡  
¡
¡ ¡ ¡ l  
¡ ¡ l ¡  
18  
Cool  
Occupied cooling with the  
water coil  
¡¡¡ ¡ ¡¡¡l ¡l¡¡  
¡¡¡ ¡ ¡¡¡l ¡ll¡  
¡¡¡ ¡ ¡¡¡l l¡¡¡  
20  
Cool  
econo-  
mize  
Occupied cooling with water  
and 100% economizer  
22  
24  
Preheat  
Unoccupied heating with hot  
water (main or auxiliary), or  
electric heatꢀ  
Preheat  
EWT  
Two-pipe only, unoccupied  
heating with electric heat  
sampling while sampling for hot waterꢀ  
¡¡¡ ¡ ¡¡¡l l¡l¡  
26  
Preheat  
electric  
heat  
Unoccupied heating with  
100% hot water (main or  
auxiliary) or with electric  
heat augmentationꢀ Or,  
unoccupied heating with  
100% main coil hot water  
with auxiliary coil hot water  
augmentationꢀ  
¡¡¡ ¡ ¡¡¡l ll¡¡  
¡¡¡ ¡ ¡¡¡l lll¡  
¡¡¡ ¡ ¡¡l¡ ¡¡¡¡  
28  
30  
32  
Heat  
Occupied heating with  
hot water (main or auxiliary  
coil)  
Occupied heating with  
electric heat  
Electric  
heat  
Heat  
electric  
heat  
Electric heat available:  
occupied heating with 100%  
hot water (main or auxiliary)  
¡¡¡ ¡ ¡¡l¡ ¡¡l¡  
34  
Electric  
heat  
EWT  
Two-pipe only, occupied  
heating with electric heat  
while purging for hot waterꢀ  
sampling  
Electric heat not available: Occupied heating with 100% main coil hot water with auxiliary coil hot water  
augmentationꢀ  
106  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Diagnostics  
Table 43ꢀ TUC Controller Diagnostics  
Diagnostic  
Latching?  
Fan  
Valves  
Electꢀ Heat  
Damper  
Dirty filter  
Yes  
No Action  
No Action  
No Action  
Off  
No Action  
Condensate  
overflow  
Yes  
Off  
Closed  
Closed  
Supply fan  
failure (if  
Yes  
Off  
Closed  
Off  
Closed  
configured as  
alarm = yes)  
Supply fan  
failure (if  
configured as  
alarm = no)  
Yes  
Yes  
No Action  
Off  
No Action  
Open  
No Action  
Off  
No Action  
Closed  
Low coil  
entering air  
temp  
Notes:  
1ꢀ  
2ꢀ  
Use a normally open hot water valve with the low coil entering air temperature sensorꢀ  
Use a normally closed chilled water valve with the condensate overflow sensorꢀ  
There are five ways in which diagnostics are reset:  
Resetting  
Diagnostics  
1ꢀ Using the zone sensor  
2ꢀ Using Everyware™, Trane’s TUC service tool  
3ꢀ By cycling power to the TUC  
4ꢀ Through Tracer 100iä or 100Lä  
5ꢀ Through Tracer Summit®  
Using the zone sensor’s fan mode switch to reset diagnostics, slide  
the fan mode switch to the off positionꢀ Then return the switch back to  
any position except offꢀ  
Using the Zone Sensor  
Connect to the communications terminal with a laptop computer  
loaded with Everywareä softwareꢀ Log on and reset the diagnostics  
from the diagnostic page of the TUC configuration screensꢀ To view  
the diagnostics prior to resetting, press the ENTER key while in the  
status section of the service summary screensꢀ  
Using  
EverywareSoftware  
UNT-IOM-6  
107  
Terminal Unit  
Control (TUC)  
Remove the 24 VAC power from the board and then reapply it to  
cycle the unit through a power-up sequenceꢀ By default, the controller  
attempts to reset all diagnostics at power-upꢀ  
Cycling Power to the  
TUC  
Using Tracer 100ior  
100L™  
The TUC editor’s reset failure point allows the user to reset controller  
diagnosticsꢀ Also, Tracer® versions 14ꢀ4 and higher provide a “+  
enter” option from the TUC service summary screens that allow  
latching diagnostic resetꢀ  
When using a Tracer Summit® system, reset the unit diagnostics with  
the reset diagnostics button on the TUC editor screenꢀ  
Using Tracer Summit®  
The unit’s operating machine state is in standby when one of the  
following conditions occurs:  
Unit Mode Listed  
as Standby  
1ꢀ Tracer® override is presentꢀ  
2ꢀ During the power-up sequence or any time when the TUC is  
calibrating its end devicesꢀ  
3ꢀ When the TUC is in the unoccupied mode and there is no call for  
heating or coolingꢀ  
4ꢀ In the occupied mode when the desired capacity is unavailableꢀ  
ie: the TUC requests a 2-pipe unit to heat, yet no hot water or electric  
heat is availableꢀ The TUC will list the unit as being in standby modeꢀ  
108  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Troubleshooting  
More detailed information about programming and operating the TUC  
board can be found in Trane publication, EMTX-IOP-1 TUC Installa-  
tion Operation and Programming Guideꢀ  
Table 44ꢀ TUC Does Not Communicate  
Probable Cause  
Explanation  
TUC is not addressed correctly  
Verify the ICS address according to Table 21 on page 63ꢀ Each TUC  
on the link requires a unique address in the range of 33 to 96ꢀ Set or  
modify the DIP switches, then short the TUC test input momentarilyꢀ  
Incorrect comm 4 wiring  
Defective TUC board  
Verify that the link is twisted pair Trane part # 400-20-28 or equiva-  
lentꢀ TUC (comm 4) wiring is polarity sensitive throughout the com-  
munication linkꢀ If possible, isolate the TUC from the rest of the ICS  
link to determine if the problem exists in the comm wiring or in the  
TUC boardꢀ  
If the previous solutions do not fix the problem, it may be necessary  
to replace the TUC boardꢀ  
Table 45ꢀ Fan Outputs not Energizing  
Probable Cause  
Explanation  
Random start enabled  
When enabled, the random start feature delays the unit start-up for  
3 to 32 seconds (configurable) after power-upꢀ  
Power-up control wait  
Cycling fan operation  
Unoccupied operation  
When enabled, the power-up control wait feature delays the TUC  
startup for two minutes after power-upꢀ This delay allows the  
Tracer® system ample time to communicate its fan control requestꢀ  
When configured to cycle with capacity, the unit fan cycles off when  
there is no call for heating or coolingꢀ The heating/cooling sources  
cycle on or off periodically with the unit fan to match the capacity  
according to pulse-width-modulation (PWM) logicꢀ  
The fan cycles with capacity when the unit is in unoccupied modeꢀ  
This occurs even if the unit is configured for continuous fan opera-  
tionꢀ While unoccupied, the fan cycles on or off with heating/  
cooling to match the capacity according to pulse-width-modulation  
(PWM) logicꢀ The TUC can be placed in unoccupied mode either  
through a Tracer® system or through BIP3 if it has been configured  
as occupied/unoccupiedꢀ  
Latching diagnostic present  
Unit disabled  
A specific list of diagnostics effects fan operationꢀ For more informa-  
tion, see the “Diagnostics” section on page 73ꢀ Latching diagnostics  
require a manual reset to restore normal unit operationꢀ  
The Tracer® system can disable the unit via a shutdown input or  
BIP1 can be configured as external interlockꢀ  
Local fan switch: off  
Using the local fan mode switch to determine fan operation, the  
“off” position on the switch controls the unit fan to offꢀ  
UNT-IOM-6  
109  
Terminal Unit  
Control (TUC)  
Table 45—Continuedꢀ Fan Outputs not Energizing  
Probable Cause  
Explanation  
No power to the TUC  
The TUC requires 24 VAC power for the unit to  
operate properlyꢀ  
Autocycle test  
Wiring  
The controller includes an auto cycle test sequence that verifies  
analog and binary output operation and associated output wiringꢀ  
However, based on the current stage in the test sequence, supply  
fan may be offꢀ Refer to the “Autocycle Test” section on page 71ꢀ  
The wiring between the controller outputs and the fan relays and  
contacts must be present and correct for normal fan operationꢀ  
Refer to the typical unit wiring diagrams on pages 105-106ꢀ  
Table 46ꢀ Valves Closed  
Probable Cause  
Explanation  
Normal operation  
unit disabled  
The valves open and close to meet unit capacity requirementsꢀ  
· The TUC may be disabled via the shutdown mode on a Tracer®  
system or if BIP1 is configured as external interlockꢀ  
· During the stop modes, the valves remain closed unless freeze  
avoidance is enabled and the fresh air temperature falls  
below the freeze avoidance setpoint (configurable)ꢀ  
· If the fresh air temperature falls below the freeze avoidance  
setpoint, the valves openꢀ The TUC enables freeze avoidance  
whenever the freeze avoidance setpoint is not zeroꢀ  
Override present  
The valves may be overridden to the closed position by either the  
Tracer® system or by Everyware™ softwareꢀ Whenever any override  
is active, the TUC drives the valves closed unless they are concur-  
rently overridden openꢀ  
Latching diagnostic presen  
Autocycle test  
A specific list of diagnostics effects valve operationꢀ For more  
information, see the “Diagnostics” section on page 73ꢀ Latching  
diagnostics require a manual reset to restore normal unit operationꢀ  
The controller includes an autocycle test sequence that verifies  
analog and binary output operation and associated output wiringꢀ  
However, based on the current stage in the test sequence, the  
valve(s) may be closedꢀ Refer to the “Human Interface” section on  
page 62ꢀ  
Maximum heating/cooling  
capacity of zero  
The Tracer® may limit the maximum heating/cooling capacity of the  
TUC from zero to 100%ꢀ When the maximum cooling capacity is  
zero, the cooling valve remains closedꢀ When the maximum heating  
capacity is zero, the heating valve remains closedꢀ  
110  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Table 46—Continuedꢀ Valves Closed  
Probable Cause  
Explanation  
Unit Configuration  
The TUC cannot control any valve outputs if the unit is configured  
for no valvesAlso, if the valve type is incorrectly configured (on/off,  
modulating analog, or 3-wire floating point), the valve(s) may not  
operate properlyꢀ  
No Power to the TUC  
Wiring  
The TUC requires a 24 VAC power for the unit to operate properlyꢀ  
The wiring between the controller outputs and the valve(s) must be  
present and correct for normal valve operationꢀ Refer to the typical  
unit wiring diagrams on pages 105-106ꢀ  
Table 47ꢀ Valves Open  
Probable Cause  
Explanation  
Normal Operation  
The valves open and close to meet unit capacity requirementsꢀ  
Override Present  
The valves may be overridden to the open position by either the  
Tracer® system or by Everyware™ softwareꢀ Whenever any  
override is active, the TUC drives the valves closed unless they are  
concurrently overridden openꢀ  
Autocycle Test  
The controller includes an autocycle test sequence that verifies  
analog and binary output operation and associated output wiringꢀ  
However, based on the current stage in the test sequence, the  
valve(s) may be openꢀ Refer to the “Autocycle Test” section on  
page 71ꢀ  
Unit Configuration  
The TUC cannot control any valve outputs if the unit is configured  
for no valvesAlso, if the valve type is incorrectly configured (on/off,  
modulating analog, or 3-wire floating point), the valve(s) may not  
operate properlyꢀ  
FreezeAvoidance  
Wiring  
When freeze avoidance is enabled (active only during stop modes)  
the TUC controls the valve(s) open whenever the fresh air tempera-  
ture is less than the freeze avoidance setpoint (configurable)ꢀ If the  
freeze avoidance setpoint is zero, this feature is disabledꢀ  
The wiring between the controller outputs and the valve(s) must be  
present and correct for normal valve operationꢀ Refer to the typical  
unit wiring diagrams on pages 105-106ꢀ  
UNT-IOM-6  
111  
Terminal Unit  
Control (TUC)  
Table 48ꢀ Electric Heat Not Operating  
Probable Cause  
Explanation  
Normal Operation  
The controller cycles electric heat on and off to meet the unit  
capacity requirementsꢀ  
Unit Disabled  
The TUC may be disabled via the shutdown mode on a Tracer®  
system or if BIP1 is configured as external interlockꢀ  
Electric Heat Control: Disable  
The electric heat may be disabled with the Tracer® systemꢀ To  
enable the electric heat, the TUC electric heat control must be set  
to the auto postionꢀ  
Maximum heating capacity of zero The Tracer® may limit the maximum heating/cooling capacity of the  
TUC from zero to 100%ꢀ When the maximum heating capacity is  
zero, the electric heat is disabledꢀ  
Latching Diagnostic Present  
A specific list of diagnostics affects electric heat operationꢀ For  
more information, see the “Diagnostics” section on page 73ꢀ  
Latching diagnostics require a manual reset to restore normal unit  
operationꢀ  
Autocycle Test  
The controller includes an autocycle test sequence that verifies  
analog and binary output operation and associated output wiringꢀ  
However, based on the current stage in the test sequence, the  
electric heat may be disabledꢀ Refer to the “Autocycle Test”  
section on page 71ꢀ  
Unit Configuration  
The TUC cannot control the electric heat output if the unit is config-  
ured for no electric heatꢀ Also, if the electric heat type is incorrectly  
configured (1 or 2 stage), the electric heat may not operate prop-  
erlyꢀ  
No Power to the TUC  
Wiring  
The TUC requires 24 VAC power for the unit to operate properlyꢀ  
The wiring between the controller outputs and the electric heat must  
be present and correct for normal electric heat operationꢀ Refer to  
the typical unit wiring diagrams on pages 105-106ꢀ  
112  
UNT-IOM-6  
Terminal Unit  
Control (TUC)  
Table 49ꢀ Fresh Air Damper Closed  
Probable Cause  
Explanation  
Normal Operation  
· The two-position fresh air damper opens under normal unit operation  
during occupied mode and closes during unoccupied modeꢀ  
· Modulating analog and 3-wire floating point economizers open to  
the minimum position (configurable) when the unit is occupied and  
modulate to meet unit capacity requirementsꢀ  
· If the minimum damper position is zero, the damper may close for  
extended periodsꢀ During the unoccupied mode, the normal fresh  
air damper position is closedꢀ  
Unit Disabled  
·Tracer® may disable via the shutdown mode on a system or if  
BIP1 is configured as external interlockꢀ  
· During the stop modes, the fresh air damper remains closedꢀ  
Override Present  
The fresh air damper may be overridden closed by either the  
Tracer® system or by Everyware™ softwareꢀ Whenever any override  
is active, the TUC drives the fresh air damper closed, unless the  
damper is concurrently overridden openꢀ  
Latching Diagnostic Present  
Autocycle Test  
Specific diagnostics affect damper operationꢀ For more information,  
see the “Diagnostics” section on page 73ꢀ Latching diagnostics  
require a manual reset to restore normal unit operationꢀ  
The controller includes an autocycle test sequence that verifies  
analog and binary output operation and associated output  
wiringꢀ However, the current test sequence stage may require the  
damper to closeꢀ Refer to the “Autocycle Test” section on page 71ꢀ  
Unit Configuration  
Warm-Up Mode  
The TUC cannot control fresh air damper outputs if the unit is config-  
ured for no fresh air damperꢀ Also, if the fresh air damper is incor-  
rectly configured (on/off, modulating analog, or 3-wire floating point),  
it may not operate properlyꢀ  
When the occupied preheat damper position is closed, the unit  
closes the fresh air damper whenever the zone temperature falls  
3° F or more below the active heating setpointꢀ The fresh air damper  
remains closed until the zone temperature is within 2° F of the  
active heating setpointꢀ  
Local Fan Switch: Off  
No Power to the TUC  
Using the local fan mode switch to determine the fan operation, the  
off position will control the unit fan off close the fresh air damperꢀ  
The TUC requires 24 VAC power for proper operationꢀ Wiring  
The wiring between the controller outputs and the fresh air damper  
must be present and correct for normal damper operationꢀ Refer to  
typical unit wiring diagrams on pages 105-106ꢀ  
Motion Detection Feature  
If motion detection is enabled and no motion is detected in the  
space (by a motion sensor wired to BIP2), the TUC will  
apply an alternate fresh air minimum damper positionꢀ  
UNT-IOM-6  
113  
Terminal Unit  
Control (TUC)  
Table 50ꢀ Fresh Air Damper Open  
Probable Cause  
Explanation  
Normal Operation  
· The two-position fresh air damper opens under normal unit opera  
tion during occupied mode and closes during unoccupied modeꢀ  
· Modulating analog and 3-wire floating point economizers open to  
the minimum position (configurable) when the unit is occupied and  
modulate to meet unit capacity requirementsꢀ  
· If the minimum damper position is zero, the damper may close  
for extended periodsꢀ During the unoccupied mode, the normal  
fresh air damper position is closedꢀ  
Override Present  
Autocycle Test  
The fresh air damper may be overridden open by either the Tracer®  
system or Everyware™ softwareꢀ Whenever any override is active,  
the TUC drives the fresh air damper closed, unless the damper is  
concurrently overridden openꢀ  
The controller includes an autocycle test sequence that verifies  
analog and binary output operation and associated output wiringꢀ  
However, the current test stage sequence may require the fresh  
air damper may be openꢀ Refer to the “Autocycle Test” section on  
page 71ꢀ  
Unit Configuration  
Wiring  
The TUC cannot control fresh air damper outputs if the unit is  
configured for no fresh air damperꢀ Also, if the fresh air damper type  
is incorrectly configured (on/off, modulating analog, or 3-wire  
floating point), it may not operate properlyꢀ  
The wiring between the controller outputs and the fresh air damper  
must be present and correct for normal damper operationꢀ Refer to  
the typical unit wiring diagrams on pages 105-106ꢀ  
Table 51ꢀ Zone Temperature Too Warm  
Probable Cause  
Explanation  
Active heating/cooling  
setpoints  
Verify that the active heating/cooling setpoints are reasonableꢀ It is  
possible for either the zone sensor or for the Tracer® system to  
send heating and cooling setpoints to the TUCꢀ Use the Tracer®  
system or Everyware™ software to determine which source is  
sending the setpointꢀ  
Wiring  
Verify the wiring of all end devices, such as valves and dampersꢀ  
Use the manual overrides or the autocycle test to verify the end  
device operationꢀ  
Manual heat mode  
sent by Tracer®  
If the Tracer® system places the TUC in manual heat mode, the TUC  
cannot switch to cool mode and therefore cannot provide cooling to  
the zoneꢀ  
Zone sensor location  
Locate the zone sensor in an area where the temperature is repre-  
sentative of the average zone temperatureꢀ  
114  
UNT-IOM-6  
Table 52ꢀ Zone Temperature Too Cool  
Probable Cause  
Explanation  
Active Heating/Cooling Setpoints Verify that the active heating/cooling setpoints are reasonableꢀ It is  
possible for either the zone sensor or for the Tracer® system to  
send heating and cooling setpoints to the TUCꢀ Use the Tracer®  
system or Everyware™ software to determine which source is  
sending the setpointꢀ  
Wiring  
Verify the wiring of all end devices, such as valves and dampersꢀ Use  
the manual overrides or the autocycle test to verify the operation of  
these end devicesꢀ  
Manual Cool Mode  
Sent by Tracer®  
If the Tracer® system places the TUC in manual cool mode, the TUC  
cannot switch to heat mode and therefore cannot provide heating to  
the zoneꢀ  
Location of the Zone Sensor  
Locate the zone sensor in an area where the temperature is represen-  
tative of the average zone temperatureꢀ  
UNT-IOM-6  
115  
Maintenance  
Listed below are the recommended maintenance schedulesꢀ Instruc-  
tions for specific maintenance procedures are given in the sections  
following the checklistꢀ  
Periodic  
Maintenance  
Checklist  
WARNING: Allow rotating fan to stop before  
servicing equipment. Failure to do so may cause severe  
personal injury or death.  
!
Monthly  
1ꢀ Inspect the unit air filtersꢀ Clean or replace dirty filtersꢀ  
Note: Building conditions may require filter change more or less  
frequentlyꢀ  
2ꢀ Check the main and auxiliary drain pans on fan-coil units to be  
sure the pans are clean and do not impede the condensate flow  
through the drain lineꢀ  
Yearly  
1ꢀ Inspect the unit cabinetry for chips or corrosionꢀ Clean or repair to  
provide unit protectionꢀ  
2ꢀ Inspect the fan wheel and housing for damageꢀ Rotate the fan  
wheel manually to be sure movement is not blocked by obstructionsꢀ  
3ꢀ Inspect the coil fins for excessive dirt or damageꢀ Remove dirt and  
straighten finsꢀ  
4ꢀ Clean and tighten all electrical connectionsꢀ  
5ꢀ Inspect the strainer option for debris trapped in the filter screenꢀ  
Change or clean air filters at least twice a yearꢀ Filters require more  
frequent care under high load or dirty air conditions since a clogged  
filter reduces airflowꢀ Table 37 on page 89 lists filter sizes for unitsꢀ  
Throwaway and pleated media filters are available for all unitsꢀ Follow  
the instructions below to replace the disposable filtersꢀ  
Maintenance  
Procedures  
Filters  
1ꢀ All models except vertical cabinets  
Remove the front panel of the vertical recessed unit and open the  
bottom panel door of the horizontal cabinet and horizontal recessed  
unit to access the filterꢀ The front panel of the vertical cabinet unit  
does not require removal to change the filterꢀ  
116  
UNT-IOM-6  
Note: Vertical recessed, horizontal cabinet, & horizontal recessed  
units with a bottom return have filter guides to secure the filter in  
positionꢀ Also, if these unit types have a fresh air opening, they  
require an additional filter for the fresh air openingꢀ  
2ꢀ Pull the two plunger spring pins inward on the filter access door  
and rotate door downwardꢀ  
3ꢀ Remove the dirty filter(s) and replace or cleanꢀ  
CAUTION: All unit panels and filters must be in  
place prior to unit start-up. Failure to have panels and  
filters in place may cause motor overload.  
!
4ꢀ Replace the front/bottom panel of the unit for cabinet and recessed  
unitsꢀ  
Table 53. Filter Sizes, in. (cm)  
Unit size  
Main Filter  
Fresh Air Filter  
(models D, E, H with  
bottom return & OA only)  
02  
1 x 8ꢀ875 x 19ꢀ125  
(2ꢀ54 x 23 x 49)  
1 x 5ꢀ5 x 19ꢀ13  
(2ꢀ54 x 13ꢀ97 x 48ꢀ59)  
03  
1 x 8ꢀ875 x 19ꢀ125  
(2ꢀ54 x 23 x 49)  
1 x 5ꢀ5 x 19ꢀ13  
(2ꢀ54 x 13ꢀ97 x 48ꢀ59)  
Low Vertical  
1 x 8ꢀ875 x 24ꢀ125  
(2ꢀ54 x 23 x 61)  
04  
1 x 8ꢀ875 x 24ꢀ125  
(2ꢀ54 x 23 x 61)  
1 x 5ꢀ5 x 24ꢀ13  
(2ꢀ54 x 13ꢀ97 x 61ꢀ29)  
Low Vertical  
1 x 8ꢀ875 x 33ꢀ625  
(2ꢀ54 x 23 x 85)  
06  
1 x 8ꢀ875 x 33ꢀ625  
(2ꢀ54 x 23 x 85)  
1 x 5ꢀ5 x 33ꢀ63  
(2ꢀ54 x 13ꢀ97 x 85ꢀ42)  
Low Vertical  
1 x 8ꢀ875 x 42ꢀ125  
(2ꢀ54 x 23 x 107)  
08  
10  
12  
1 x 8ꢀ875 x 42ꢀ125  
(2ꢀ54 x 23 x 107)  
1 x 5ꢀ5 x 42ꢀ13  
(2ꢀ54 x 13ꢀ97 x 107ꢀ0)  
1 x 8ꢀ875 x 61ꢀ125  
(2ꢀ54 x 23 x 155)  
1 x 5ꢀ5 x 61ꢀ38  
(2ꢀ54 x 13ꢀ97 x 155ꢀ91)  
1 x 8ꢀ875 x 61ꢀ125  
(2ꢀ54 x 23 x 155)  
1 x 5ꢀ5 x 61ꢀ38  
(2ꢀ54 x 13ꢀ97 x 155ꢀ91)  
UNT-IOM-6  
117  
Clean the fan-coil unit’s main and auxiliary drain pans to ensure the  
unit drains condensate properlyꢀ  
Inspecting and  
Cleaning Drain  
Pans  
Check the condensate drain pan and drain line to assure the conden-  
sate drains properly at least every six months or as dictated by  
operating experienceꢀ  
If evidence of standing water or condensate overflow exists, immedi-  
ately identify and remedy the causeꢀ Refer to Table 40 on page 99 for  
possible causes and solutionsꢀ If the drain pan contains microbial  
growth, clean and remove it immediatelyꢀ  
Clean drain pans using the following procedure:  
1ꢀ Disconnect all electrical power to the unitꢀ  
2ꢀ Don the appropriate personal protective equipment (PPE)ꢀ  
3ꢀ Remove all standing waterꢀ  
4ꢀ Use a scraper or other tool to loosen any solid matterꢀ Remove  
solid matter with a vacuum device that utilizes high efficiency particu-  
late arrestance (HEPA) filters with a minimum efficiency of 99ꢀ97% at  
0ꢀ3 micron particle sizeꢀ  
5ꢀ Thoroughly clean the contaminated area(s) with a mild bleach and  
water solution or an EPA-approved sanitizer specifically designed for  
HVAC useꢀ Carefully follow the sanitizer manufacturer’s instructions  
regarding the use of the productꢀ  
6ꢀ Immediately rinse the drain pan thoroughly with fresh water to  
prevent potential corrosion from the cleaning solution of the drain pan  
and drain line componentsꢀ  
7ꢀ Allow the unit to dry thoroughly before putting the system back into  
serviceꢀ  
8ꢀ Determine and correct the cause of the microbial contaminationꢀ  
9ꢀ Be careful that the contaminated material does not contact other  
areas of the unit or buildingꢀ Properly dispose of all contaminated  
materials and cleaning solutionꢀ  
Note: Standing water in drain pans can promote microbial growth  
(mold) which may cause unpleasant odors and health-related indoor  
air quality problemsꢀ If microbial growth (mold) is found, remove it  
immediately by cleaning and santizing the unit properly#  
118  
UNT-IOM-6  
1To remove the auxiliary drain pan, loosen the hose clamp (installer  
supplied) around the drain con-  
Auxiliary Drain Pan  
nection collar and disconnect the  
drain lineꢀ  
2ꢀ Remove the overflow drain line  
to the auxiliary drain pan if it was  
installedꢀ  
3ꢀ Remove the condensate over-  
flow switch option from the  
auxiliary drain panꢀ  
Figure 31. Insert the auxiliary  
drain pan tabs into these slots  
4ꢀ Slide the pan horizontally  
towards the end of the large  
groove of the mounting slots in  
the chassis end panel and remove  
pan from unitꢀ See Figure 31ꢀ  
in the fan-coils chassis end  
panel. A horizontal unit is  
pictured.  
CAUTION: Exercise extreme care when removing  
auxiliary drain pan. Failure to do so may cause plastic  
mounting tabs to break.  
!
Note: When replacing the main drain pan, install it correctly under the  
z-bar as pictured in Figure 32ꢀ  
Main Drain Pan  
Coil  
Side  
View  
Main Drain Pan  
Z-Bar  
Figure 32. When replacing the  
fan-coils main drain pan, install  
it correctly under the z-bar.  
UNT-IOM-6  
119  
Vertical units:  
To remove the main drain pan on  
vertical fan-coil units, disconnect  
the clips holding the pan to the  
fanboardꢀ Disconnect the main  
and overflow drain hoses and  
slide pan forward to removeꢀ See  
Figure 33ꢀ  
Figure 33. To remove the main  
drain pan on vertical fan-coil  
units, disconnect the clips  
holding the pan to the  
fanboard.  
Horizontal units:  
To remove the main drain pan on  
a horizontal fan-coil unit, peel the  
insulation from the edges of the  
pan’s underside to access the  
mounting screwsꢀ Remove the  
screws and lower the end of the  
drain pan closest to the control  
boxꢀ Remove the drain spout by  
pulling it from the hole in the  
chassis end panelꢀ See Figure  
34ꢀ  
Figure 34. To remove the main  
drain pan on horizontal fan-  
coil units, peel the insulation  
from the edges of the pans  
underside to access the  
mounting screws.  
Note: Do not operate the fan-coil unit without the main and auxiliary  
drain pans in place to prevent condensate leakageꢀ  
Make provisions to ensure adequate protection against coil freeze-upꢀ  
If the fan-coil units are not in operation, the coil/s should be vented at  
the factory vent/s and drained at the piping system drain port/sꢀ See  
Table 38 on page 94 for approximate piping package volumes for  
piping systems using ethylene glycolꢀ Table 39 on page 94 lists  
approximate hydronic coil volumesꢀ  
Winterizing the  
Coil  
It is necessary to properly prepare the units for cold weatherꢀ If a coil  
is not in use and is subject to temperatures below 32° F, drain the  
coil to prevent coil freezeupꢀ Locate the drain (installer supplied) in  
the field piping systemꢀ  
120  
UNT-IOM-6  
Coils become externally fouled as a result of normal operationꢀ Dirt on  
the coil surface reduces it’s heat transfer ability that can result in  
comfort problems, increased airflow resistance, and thus increased  
operating energy costsꢀ If the coil surface dirt becomes wet, which  
commonly occurs with cooling coils, microbial growth (mold) may  
result and potentially cause unpleasant odors and health-related  
indoor air quality problemsꢀ  
Inspecting and  
Cleaning Coils  
Inspect coils at least every six months or more frequently as dictated  
by operating experienceꢀ Required cleaning frequency depends on  
the system operating hours, filter maintenance and efficiency, and dirt  
loadꢀ The Trane Company recommends the following method of  
cleaning coils:  
1ꢀ Disconnect all electrical power to the unitꢀ  
Steam and Water  
Coils  
2ꢀ Don the appropriate personal protective equipment (PPE)ꢀ  
3ꢀ Gain access to the both sides of the unit coil sectionꢀ  
4ꢀ Use a soft brush to remove loose debris from both sides of the coilꢀ  
5ꢀ Use a steam cleaning machine, starting from the top of the coil  
and working downwardꢀ Clean the leaving air side of the coil first, then  
the entering air sideꢀ Use a block-off to prevent steam from blowing  
through the coil and into a dry section of the unitꢀ  
6ꢀ Repeat step 5 as necessaryꢀ Confirm that the drain line is open  
following completion of the cleaning processꢀ  
7ꢀ Allow the unit to dry thoroughly before putting the system back into  
serviceꢀ  
8ꢀ Straighten any coil fins that may have been damaged during the  
cleaning process with a fin rakeꢀ  
9ꢀ Replace all panels and parts and restore electrical power to the  
unitꢀ  
10ꢀ Use caution to assure that any contaminated material does not  
contact other areas of the unit or buildingꢀ Properly dispose of all  
contaminated materials and cleaning solutionꢀ  
UNT-IOM-6  
121  
Table 54. Factory Piping Package Volumes, oz. (mL)  
Piping Package  
Volume  
6 (178)  
12 (355)  
Main coil  
Auxiliary coil  
Table 55. Hydronic Coil Volumes/Heating & Cooling, gal.  
Unit Size  
Total # Rows  
Volume  
02  
1
2
3
4
ꢀ05  
ꢀ10  
ꢀ14  
ꢀ20  
03  
04  
06  
08  
10  
12  
1
2
3
4
ꢀ06  
ꢀ12  
ꢀ18  
ꢀ24  
1
2
3
4
ꢀ08  
ꢀ15  
ꢀ23  
ꢀ30  
1
2
3
4
ꢀ11  
ꢀ22  
ꢀ33  
ꢀ44  
1
2
3
4
ꢀ14  
ꢀ28  
ꢀ42  
ꢀ56  
1
2
3
4
ꢀ18  
ꢀ35  
ꢀ53  
ꢀ71  
1
2
3
4
ꢀ21  
ꢀ42  
ꢀ62  
ꢀ83  
Note: 1-row coil refers only to the 1-row heating coil in some 4-pipe  
configurationsꢀ  
122  
UNT-IOM-6  
The process of cooling and dehumidification produces condensate  
(water) which must be continuously removed from the air handling  
unitꢀ The entering air side of the cooling coil to the leaving edge of the  
drain pan is considered to be the “wet” section of the unitꢀ Other  
potentially “wet” sections are immediately downstream of a humidifier  
and/or an fresh air intake sectionꢀ  
Inspecting and  
Cleaning the  
Internal Insulation  
on Fan-Coils  
It is common for the “wet” section components, including the internal  
insulation, to become wet during normal operationꢀ Therefore, inspect  
the internal insulation in these areas periodically to assure it is clean  
and free of dirt or microbial growth (mold)ꢀ Inspect units every six  
months or more frequently if operating experience dictatesꢀ Accumu-  
lated dirt and other organic matter exposed to water or extended  
periods of high relative humidity (60% or higher) may support micro-  
bial growthꢀ Clean the insulation to prevent the unit from becoming an  
IAQ contaminant sourceꢀ  
Also, inspect internal insulation in the “dry” areas of the unit periodi-  
cally to ensure the insulation is clean and dryꢀ Wet insulation in an  
area that is normally considered to be “dry” may indicate an opera-  
tional problemꢀ Refer to Table 40 on page 99 for further informationꢀ  
Inspect the equipment a minimum of every six months or more  
frequently if operating experience dictatesꢀ When accumulated dirt  
and other organic matter is exposed to water or extended periods of  
high relative humidity (60% or higher) may support microbial growth,  
an indoor air quality contaminant sourceꢀ  
If evidence of contamination exists in either the wet or dry sections,  
take immediate action to determine and eliminate the causeꢀ Remove  
the contamination and sanitize the affected areaꢀ See Tabale 40 on  
page 99 for assistance in identifying the causeꢀ Remove and clean  
any microbial growth on a non-porous insulating surface (eꢀgꢀ closed-  
cell insulation or sheet metal surface)ꢀ  
The Trane Company recommends the following procedure for proper  
cleaning the fan-coil internal insulation and sheet metal:  
1ꢀ Disconnect all electrical power to the unitꢀ  
2ꢀ Don the appropriate personal protective equipment (PPE)ꢀ  
3ꢀ Thoroughly clean the contaminated area(s) with an EPA-approved  
sanitizer specifically designed for HVAC useꢀ Use a brush for sheet  
metal surfaces or a soft sponge on closed-cell foam surface to  
mechanically remove the microbial growthꢀ Be careful not to damage  
the non-porous surface of the insulationꢀ Carefully follow the sanitizer  
manufacturers instructions regarding personal protection and ventila-  
tionꢀ  
UNT-IOM-6  
123  
4ꢀ Rinse the affected surfaces thoroughly with fresh water and a fresh  
sponge to prevent potential corrosion of the drain pan and drain lineꢀ  
5ꢀ Ensure the drain line remains open following the cleaning processꢀ  
6ꢀ Replace all panels and parts and restore electrical power to the  
unitꢀ  
7ꢀ Allow the unit to dry completely before putting it back into serviceꢀ  
8ꢀ Do not allow any contaminated material to contact other areas of  
the unit or buildingꢀ Properly dispose of all contaminated materials  
and cleaning solutionꢀ  
Inspect the fan at least every six months or more frequently if operat-  
ing experience dictatesꢀ Clean accumulated dirt and organic matter  
on the interior fan surface immediatelyꢀ  
Inspecting and  
Cleaning the Fan  
The Trane Company recommends the following procedure for cleaning  
fan surfaces:  
1ꢀ Disconnect all electrical power to the unitꢀ  
2ꢀ Don the appropriate personal protective equipment (PPE)ꢀ  
3ꢀ Use a portable vacuum with HEPA filtration to remove loose dirt  
and organic matterꢀ The filter should be 99ꢀ97% efficient at 0ꢀ3 micron  
particle sizeꢀ  
4ꢀ If no microbial growth (mold) exists, thoroughly clean the fan and  
associated components with an industrial cleaning solutionꢀ Carefully  
follow the cleaning solution manufacturer’s instructions regarding  
personal protection and ventilation when using their productꢀ  
5ꢀ If microbial growth (mold) is present, remove the contamination  
(Step 2) and thoroughly clean the affected area with an EPA-approved  
sanitizer specifically designed for HVAC useꢀ Carefully follow the  
sanitizer manufacturer’s instructions regarding the use of the productꢀ  
6ꢀ Rinse the affected surfaces thoroughly with fresh water and a fresh  
sponge to prevent potential corrosion of metal surfacesꢀ  
124  
UNT-IOM-6  
7ꢀ Allow the unit to dry completely before putting it back into serviceꢀ  
8ꢀ Do not allow any contaminated material to contact other areas of  
the unit or buildingꢀ Properly dispose of all contaminated materials  
and cleaning solutionꢀ  
If microbial growth (mold) is present, determine the cause of the  
contamination and take action to prevent reoccuranceꢀ  
UNT-IOM-6  
125  
Follow the procedure below when replacing the coil or making repairs  
to the fan or motorꢀ  
Fan Board  
Assembly  
Removal  
WARNING: Allow rotating fan to stop before  
!
servicing equipment. Failure to do so may cause severe  
personal injury or death.  
Vertical Units  
1ꢀ Remove the front panel of cabinet and recessed unitsꢀ  
2ꢀ Pull the main and overflow drain hoses of the main drain pan into  
the inside of the fan-coil chassis end panelꢀ  
3ꢀ Remove the two fanboard  
mounting screws shown in  
Figure 35ꢀ  
4ꢀ Slide the fanboard out horizon-  
tally to removeꢀ  
Horizontal Units  
1ꢀ Open the bottom panel of  
cabinet and recessed modelsꢀ  
Figure 35. Remove the two  
mounting screws located  
under the fanboard to slide it  
out.  
2ꢀ Remove the main drain pan  
following the instructions given  
under the drain pan section above for horizontal fan-coil unitsꢀ  
3ꢀ While supporting the fanboard in place, remove the two fanboard  
mounting screws which secure the fanboard to the unitꢀ  
CAUTION: Support the fanboard when removing it  
from the unit. Failure to do so may cause personal injury.  
!
The capacitor for all unit motors can be replaced should it failꢀ  
Contact the local Trane service department to replace the motor  
capacitor in the event it failsꢀ However, the motor itself cannot be  
repaired or rewoundꢀ If the motor fails, record the model number from  
the unit nameplate and present to the local Trane Service Parts  
Center to purchase a replacementꢀ The motor bearings are perma-  
nently lubricated and do not require any further oilingꢀ  
Replacing the Motor  
126  
UNT-IOM-6  
After removing the fanboard assembly from the unit, disconnect the  
fan wheel/wheels from the motor shaft by loosening the Allen head  
setscrew on the fan wheel hub collarꢀ Next, remove the mounting  
bolts holding the fan motor plate to the mounting bracket of the  
fanboardꢀ Then remove the motor by sliding the fan shaft from the fan  
wheel hubꢀ  
During re-assembly, make certain the fan wheel(s) is/are properly  
centered in the fan housing to prevent the fan wheel from contacting  
the housing on either sideꢀ After the unit has been re-assembled,  
verify that no unusual noise or vibration is present at startupꢀ  
To order control components such as relays, contactors, transform-  
ers, low temperature detection devices, condensate overflow detec-  
tion devices, differential pressure switches, sensors, control valves  
and actuators, contact the local Trane Service Parts Centerꢀ To order,  
the Trane parts center will need the unit model number (which can be  
found on the unit nameplate), the serial number, and the part name or  
IDꢀ  
Control Device  
Replacement  
Table 56ꢀ Trouble Shooting  
Problem  
Possible Cause  
Remedy  
Drain pan is overflowing  
Standing water in drain pan  
Wet interior insulation  
Plugged drain line  
Unit not level  
Clean drain line  
Level unit  
Unit not level  
Plugged drain line  
Level unit  
Clean drain line  
Coil face velocity too high  
Drain pan leaks/overflowing  
Condensation on surfaces  
Reduce fan speed  
Repair leaks  
Insulate surfaces  
Excess dirt in unit  
Missing filters  
Filter bypass  
Replace filters  
Reduce filter bypass  
Microbial growth (mold)  
Moisture problems  
See “External Insulating  
Requirements” section  
on page 20ꢀ  
Standing water in drain pan  
See “Inspecting and cleaning  
the drain pan” section  
on page 90ꢀ  
UNT-IOM-6  
127  
Appendix  
Factory Piping  
Packages  
Automatic Circuit Setter (C)  
128  
UNT-IOM-6  
Fan Mode Switch Typical Wiring  
Diagram  
For Reference Only:  
This schematic shows typical wiring  
of a fan-coil. It is not intended for a  
basis of design or for equipment  
installation purposes in the field.  
For an as-built schematic specific to  
a particular unit, please see the  
ship-with schematic for that specific  
unit.  
Two-pipe unit without control valve  
Fan mode switch option “K”  
Wall mounted mode switch — off/  
high/med/low  
Disconnect switch  
Automatic two-position fresh air  
damper  
For reference only:  
This schematic show typical wiring of a fan-coilꢀ It is not intended for a basis of design or for equipment  
installation purposes in the fieldꢀ For an as-built schematic specific to a particular unit, please see the  
ship-with schematic for that specific unitꢀ  
UNT-IOM-6  
129  
Tracer® ZN.010 Typical Wiring Diagram  
NOTES:  
1. UNLESS OTHERWISE NOTED, ALL SWITCHES ARE  
SHOWN AT 25 C (77 F), AT ATMOSPHERIC PRESSURE, AT  
50% RELATIVE HUMIDITY, WITH ALL UTILITIES TURNED  
OFF, AND AFTER A NORMAL SHUTDOWN HAS  
OCCURRED.  
2. DASHED LINES INDICATE RECOMMENDED FIELD WIRING  
BY OTHERS. DASHED LINE ENCLOSURES AND/OR  
DASHED DEVICE OUTLINES INDICATE COMPONENTS  
PROVIDED BY THE FIELD. SOLID LINES INDICATE WIRING  
BY TRANE CO.  
3. NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC  
DESIGNATE THE LOCATION OF CONTACTS BY LINE  
NUMBER. AN UNDERLINED NUMBER INDICATES A  
NORMALLY CLOSED CONTACT.  
4. ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE  
NATIONAL ELECTRIC CODE (NEC), STATE AND LOCAL  
REQUIREMENTS.DEVICE PREFIX  
LOCATION GUIDE  
AREA LOCATION  
1
2
3
4
5
6
CONTROL PANEL  
CONTROL END  
PIPING END  
FAN SECTION  
COIL SECTION  
CUSTOMER  
For Reference Only:  
This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation  
purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that  
specific unit or contact your local Trane representative.  
Two-pipe autochangeover  
Two-position N/C control valve  
Two-position N/C fresh air damper actuator  
EWT sensor  
Condensate overflow detection  
Low temperature detection  
Unit mounted fan mode switch and setpoint dial  
Return air temperature sensor  
130  
UNT-IOM-6  
Tracer® ZN.010 Typical Wiring Diagram  
LEGEND  
DESCRIPTION  
DEVICE  
DESIG.  
1K1-3  
LINE  
NUMBER  
25-26-27  
DEVICE PREFIX  
LOCATION GUIDE  
FAN STARTERS  
AREA LOCATION  
1K4  
5HR1-2  
565-8  
3612  
1T1  
1TB1  
1TB6  
ELECTRIC HEAT CONTACTOR  
HEATING ELEMENTS  
LIMIT SWITCHES  
ELEC. HEAT AUTO LOCKOUT SWT  
TRANSFORMER  
MAIN POWER TERMINAL BLOCK  
TERMINAL STRIP  
30  
11-12  
11-12  
30  
21  
5
1
2
3
4
5
6
CONTROL PANEL  
CONTROL END  
PIPING END  
FAN SECTION  
COIL SECTION  
CUSTOMER  
1U1  
2U2  
358  
151  
159  
481  
2L2  
3L1  
THERMOSTAT MODULE  
ZONE SENSOR MODULE  
CONDENSATE OVERFLOW SW  
DISCONNECT SW  
FREEZE-STAT  
FAN MOTOR  
23  
24  
36  
3
38  
9
NOTES:  
1. UNLESS OTHERWISE NOTED, ALL  
SWITCHES ARE SHOWN AT 25 C (77 F),  
AT ATMOSPHERIC PRESSURE, AT 50%  
RELATIVE HUMIDITY, WITH ALL UTILITIES  
TURNED OFF, AND AFTER A NORMAL  
SHUTDOWN HAS OCCURRED.  
DAMPER ACTUATOR  
MAIN COIL VALVE  
32  
28  
2. DASHED LINES INDICATE  
3RT1  
AUTO CHANGE TEMP SENSOR  
34  
RECOMMENDED FIELD WIRING BY  
OTHERS. DASHED LINE ENCLOSURES  
AND/OR DASHED DEVICE OUTLINES  
INDICATE COMPONENTS PROVIDED BY  
THE FIELD. SOLID LINES INDICATE  
WIRING BY TRANE CO.  
3. NUMBERS ALONG THE RIGHT SIDE OF  
THE SCHEMATIC DESIGNATE THE  
LOCATION OF CONTACTS BY LINE  
NUMBER. AN UNDERLINED NUMBER  
INDICATES  
A
NORMALLY CLOSED  
CONTACT.  
4. ALL FIELD WIRING MUST BE IN  
ACCORDANCE WITH THE NATIONAL  
ELECTRIC CODE (NEC), STATE AND  
LOCAL REQUIREMENTS.  
For Reference Only:  
This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation  
purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that  
specific unit or contact your local Trane representative.  
Two-pipe autochangeover with electric heat  
Two-position N/O control valve  
Electric heat contactor  
Two-position N/C fresh air damper actuator  
EWT sensor  
Electric heat limit switch(es)  
Condensate overflow detection  
Low temperature detection  
Wall mounted fan mode switch, setpoint dial, zone temperature sensor, and unit mounted disconnect switch  
UNT-IOM-6  
131  
Tracer® ZN.010 Typical Wiring Diagram  
NOTES:  
1. UNLESS OTHERWISE NOTED, ALL  
SWITCHES ARE SHOWN AT 25 C (77 F),  
AT ATMOSPHERIC PRESSURE, AT 50%  
RELATIVE HUMIDITY, WITH ALL UTILITIES  
TURNED OFF, AND AFTER A NORMAL  
SHUTDOWN HAS OCCURRED.  
LEGEND  
DESCRIPTION  
DEVICE  
DESIG.  
1K1-3  
LINE  
NUMBER  
25-26-27  
FAN STARTERS  
2. DASHED LINES INDICATE  
RECOMMENDED FIELD WIRING BY  
OTHERS. DASHED LINE ENCLOSURES  
AND/OR DASHED DEVICE OUTLINES  
INDICATE COMPONENTS PROVIDED BY  
THE FIELD. SOLID LINES INDICATE  
WIRING BY TRANE CO.  
3. NUMBERS ALONG THE RIGHT SIDE OF  
THE SCHEMATIC DESIGNATE THE  
LOCATION OF CONTACTS BY LINE  
NUMBER. AN UNDERLINED NUMBER  
1T1  
1TB6  
1U1  
TRANSFORMER  
21  
23  
TERMINAL STRIP  
THERMOSTAT MODULE  
INDICATES  
CONTACT.  
A
NORMALLY CLOSED  
358  
151  
159  
2U2  
CONDENSATE OVERFLOW  
DISCONNECT SW  
LOWLIMIT  
ZONE SENSOR MODULE  
FAN SWITCH  
36  
3
4. ALL FIELD WIRING MUST BE IN  
ACCORDANCE WITH THE NATIONAL  
ELECTRIC CODE (NEC), STATE AND  
LOCAL REQUIREMENTS.  
24  
28  
9
481  
FAN MOTOR  
DEVICE PREFIX  
LOCATION GUIDE  
AREA LOCATION  
2L2  
3L1  
3L3  
DAMPER ACTUATOR  
MAIN COIL VALVE  
HEATING COIL VALVE  
32  
28  
30  
1
2
3
4
5
6
CONTROL PANEL  
CONTROL END  
PIPING END  
FAN SECTION  
COIL SECTION  
CUSTOMER  
For Reference Only:  
This schematic shows typical wiring of a fan-coil. It is not intended for a basis of design or for equipment installation  
purposes in the field. For an as-built schematic specific to a particular unit, please see the ship-with schematic for that  
specific unit or contact your local Trane representative.  
Four-pipe  
Two-position N/C cooling control valve  
Two-position N/O heating control valve  
Two-position N/C fresh air damper actuator  
Condensate overflow detection  
Low temperature detection  
Unit mounted fan mode switch,  
Wall mounted setpoint dial and zone temperature sensor  
Unit mounted disconnect switch  
132  
UNT-IOM-6  
TUC Typical Wiring Diagram  
For Reference Only:  
This schematic shows typical wiring of a fan-coil. It is not  
intended for a basis of design or for equipment installation  
purposes in the field. For an as-built schematic specific to a  
particular unit, please see the ship-with schematic for that  
specific unit or contact your local Trane representative.  
Two-pipe unit with a modulating valve  
Electric heat  
terminal unit controller  
Wall mounted zone sensor — off/auto/high/med/low  
Disconnect switch  
Automatic two-position fresh air damper  
Low temperature detection  
Condensate overflow detection  
3  
TUC Typical Wiring Diagram  
For Reference Only:  
This schematic shows typical wiring of a fan-coil. It is not  
intended for a basis of design or for equipment installation  
purposes in the field. For an as-built schematic specific to a  
particular unit, please see the ship-with schematic for that  
specific unit or contact your local Trane representative.  
Four-pipe unit with control valves (both modulating)  
terminal unit controller  
Wall mounted zone sensor — off/auto/high/med/low  
Disconnect switch  
Automatic two-position fresh air damper  
Low temperature detection  
Condensate overflow detection  
OM-6  
Literature Order Number  
File Number  
UNT-IOM-6  
PL-TD- UNT-IOM-6-4-00  
UNT-IOM-5  
Supersedes  
The Trane Company  
Stocking Location  
LaCrosse  
Worldwide Applied Systems Group  
3600 Pammel Creek Rd.  
LaCrosse, WI 54601-7599  
www.trane.com  
Since The Trane Company has a policy of continuous product improvement, it reserves the right to  
change design and specifications without notice.  
An American Standard Company  

Xerox 426 User Manual
Samsung Avmwh035ea B 0 User Manual
Panasonic Kx Fpg381 User Manual
MIELE G 843 SCVI User Manual
MAKITA GA5080R User Manual
HP 2910 User Manual
HANSGROHE AXOR CARLTON 17379XX1 User Manual
ASUS VS278 User Manual
ASUS SABERTOOTH Z170 MARK 1 User Manual
ACER ASPIRE V11 TOUCH User Manual