Sanyo Ch1852 User Manual

TECHNICAL & SERVICE MANUAL  
KHS0951 / CH0951  
KHS1251 / CH1251  
KHS1852 / CH1852  
FILE NO.  
Destination: U.S.A.  
SPLIT SYSTEM AIR CONDITIONER  
Indoor Model No.  
KHS0951  
Product Code No.  
1 852 069 13  
Outdoor Model No. Product Code No.  
CH0951  
CH1251  
CH1852  
1 852 069 16  
1 852 069 17  
1 852 069 18  
KHS1251  
1 852 069 14  
KHS1852-S  
1 852 069 15  
Indoor Unit  
Outdoor Unit  
KHS0951  
KHS1251  
CH0951  
CH0952  
KHS1852  
CH1852  
REFERENCE NO. SM700447  
W
Table of Contents  
Page  
1
1. OPERATING RANGE ................................................................................................................  
2. SPECIFICATIONS  
2-1. Unit Specifications............................................................................................................  
2-2. Major Component Specifications......................................................................................  
2-3. Other Component Specifications......................................................................................  
2
5
11  
3. DIMENSIONAL DATA  
3-1. Unit...................................................................................................................................  
14  
18  
4. REFRIGERANT FLOW DIAGRAM  
4-1. Refrigerant Flow Diagram.................................................................................................  
5. PERFORMANCE DATA  
5-1. Performance Charts .........................................................................................................  
5-2. Air Throw Distance Charts ...............................................................................................  
5-3. Cooling Capacity ..............................................................................................................  
5-4. Heating Capacity..............................................................................................................  
19  
22  
25  
29  
6. ELECTRICAL DATA  
6-1. Electrical Characteristics..................................................................................................  
6-2. Electric Wiring Diagrams..................................................................................................  
30  
33  
7. INSTALLATION INSTRUCTIONS  
7-1. Installation Site Selection .................................................................................................  
7-2. Remote Control Unit Installation Position.........................................................................  
7-3. Address Switches.............................................................................................................  
7-4. Recommended Wire Length and Diameter......................................................................  
42  
44  
45  
46  
8. FUNCTION  
8-1. Room Temperature Control ..............................................................................................  
8-2. Dry Operation (Dehumidification).....................................................................................  
8-3. Automatic Switching between Cooling and Heating.........................................................  
8-4. Freeze Prevention (Cooling).............................................................................................  
8-5. Overload Prevention (Heating) .........................................................................................  
8-6. Cold draft Prevention (Heating) ........................................................................................  
8-7. Defrosting Operation (Heating).........................................................................................  
8-8. Low Temperature Cutff (Heating) .....................................................................................  
47  
49  
49  
50  
50  
51  
52  
53  
9. TROUBLESHOOTING  
9-1. Check before and after troubleshooting............................................................................  
9-2. Air conditioner does not operate.......................................................................................  
9-3. Some part of air conditioner does not operate. ................................................................  
9-4. Air conditioner operates, but abnormalities are observed. ...............................................  
9-5. If a sensor is defective......................................................................................................  
54  
55  
59  
61  
63  
ii  
10. CHECKING ELECTRICAL COMPONENTS  
10-1. Measurement of Insulation Resistance ............................................................................  
10-2. Checking Continuity of Fuse on PCB Ass'y......................................................................  
10-3. Checking Motor Capacitor................................................................................................  
64  
65  
65  
11. ARRANGEMENT OF ELECTRICAL COMPONENT.................................................................  
66  
APPENDIX  
INSTRUCTION MANUAL  
iii  
1. OPERATING RANGE  
Temperature  
Indoor Air Intake Temp.  
95°F D.B. / 71°F W.B.  
67°F D.B. / 57°F W.B.  
80°F D.B. / 67°F W.B.  
— D.B. / — W.B.  
Outdoor Air Intake Temp.  
115°F D.B.  
Maximum  
Cooling  
Minimum  
67°F D.B.  
Maximum  
Heating  
75°F D.B. / 65°F W.B.  
17°F D.B. / 15°F W.B.  
Minimum  
1
2. SPECIFICATIONS  
2-1. Unit Specifications  
(1) Indoor unit  
KHS0951  
Outdoor unit CH0951  
Cooling  
Heating  
Voltage Rating  
115V 60Hz  
Performance  
Cooling  
9,100  
2.67  
Heating  
10,900  
3.19  
Capacity  
BTU/h  
kW  
Air circulation (High)  
ft3/min (m3/min)  
270 (7.65)  
103 – 126  
Moisture removal (High)  
Pints/h  
2.0  
Electrical Rating  
Available voltage range  
Running amperes  
Power input  
Cooling  
Heating  
V
A
W
8.5  
890  
91  
8.4  
890  
92  
Power factor  
%
SEER (HSPF)  
BTU/W  
A
11.0  
(6.8)  
Compressor locked rotor amperes  
Heater element  
49  
kW  
Features  
Controls / Temperature control  
Microprocessor / I.C. thermostat  
Control unit  
Timer  
Wireless remote control unit  
ON / OFF 12 hours, 1-hour OFF  
3 and Auto / 1 (Hi)  
Manual  
Fan speeds  
Indoor / Outdoor  
Airflow direction (Indoor)  
Horizontal  
Vertical  
Auto  
Air filter  
Washable  
Compressor  
Rotary (Hermetic)  
2.65 (1.20)  
Capillary tube  
38 / 34 / 32  
48  
Refrigerant / Amount charged at shipment lb. (kg)  
Refrigerant control  
Operation sound  
Indoor: Hi / Me / Lo dB-A  
Outdoor: Hi  
dB-A  
Refrigerant tubing connections  
Flare  
Max allowable tubing length at shipment  
ft. (m)  
inch (mm)  
inch (mm)  
25 (7.5)  
Refrigerant tubing  
diameter  
Narrow tube  
Wide tube  
1/4 (6.35)  
3/8 (9.52)  
Dimensions & Weight  
Indoor Unit  
Outdoor Unit  
21-1/4 (540)  
31-1/2 (800)  
11-13/32 (290)  
23-31/32 (609)  
38-5/8 (981)  
16-3/16 (411)  
75.0 (34)  
Unit dimensions  
Height  
Width  
Depth  
Height  
Width  
Depth  
Net  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
lb. (kg)  
10-5/8 (270)  
31-11/16 (805)  
6-31/32 (177)  
9-13/16 (249)  
33-21/32 (855)  
13-5/16 (338)  
17.6 (8.0)  
Package dimensions  
Weight  
Shipping  
lb. (kg)  
cu.ft (m3)  
22.0 (10.0)  
83.8 (38)  
Shipping volume  
2.51 (0.071)  
8.67 (0.246)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
2
(2) Indoor unit  
KHS1251  
Outdoor unit CH1251  
Cooling  
Heating  
Voltage Rating  
115V 60Hz  
Performance  
Cooling  
11,700  
3.43  
Heating  
12,500  
3.66  
Capacity  
BTU/h  
kW  
Air circulation (High)  
ft3/min (m3/min)  
330 (9.35)  
103 – 126  
Moisture removal (High)  
Pints/h  
3.4  
Electrical Rating  
Available voltage range  
Running amperes  
Power input  
Cooling  
Heating  
V
A
W
10.5  
1,200  
99  
10.3  
1,170  
99  
Power factor  
%
SEER (HSPF)  
BTU/W  
A
10.2  
(6.8)  
Compressor locked rotor amperes  
Heater element  
60  
kW  
Features  
Controls / Temperature control  
Microprocessor / I.C. thermostat  
Control unit  
Timer  
Wireless remote control unit  
ON / OFF 12 hours, 1-hour OFF  
3 and Auto / 1 (Hi)  
Manual  
Fan speeds  
Indoor / Outdoor  
Airflow direction (Indoor)  
Horizontal  
Vertical  
Auto  
Air filter  
Washable  
Compressor  
Rotary (Hermetic)  
2.76 (1.25)  
Capillary tube  
41 / 38 / 34  
48  
Refrigerant / Amount charged at shipment lb. (kg)  
Refrigerant control  
Operation sound  
Indoor: Hi / Me / Lo dB-A  
Outdoor: Hi  
dB-A  
Refrigerant tubing connections  
Flare  
Max allowable tubing length at shipment  
ft. (m)  
inch (mm)  
inch (mm)  
25 (7.5)  
Refrigerant tubing  
diameter  
Narrow tube  
Wide tube  
1/4 (6.35)  
1/2 (12.7)  
Dimensions & Weight  
Indoor Unit  
Outdoor Unit  
21-1/4 (540)  
31-1/2 (800)  
11-13/32 (290)  
23-31/32 (609)  
38-5/8 (981)  
16-3/16 (411)  
83.8 (38)  
Unit dimensions  
Height  
Width  
Depth  
Height  
Width  
Depth  
Net  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
lb. (kg)  
10-5/8 (270)  
31-11/16 (805)  
6-31/32 (177)  
9-13/16 (249)  
33-21/32 (855)  
13-5/16 (338)  
17.6 (8.0)  
Package dimensions  
Weight  
Shipping  
lb. (kg)  
cu.ft (m3)  
22.0 (10.0)  
92.6 (42)  
Shipping volume  
2.51 (0.071)  
8.67 (0.246)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
3
(3) Indoor unit  
KHS1852  
Outdoor unit CH1852  
Cooling  
Heating  
Voltage Rating  
230 / 208V 60Hz  
Performance  
Cooling  
17,000 / 16,500  
4.98 / 4.84  
Heating  
19,000 / 18,500  
5.75 / 5.42  
Capacity  
BTU/h  
kW  
Air circulation (High)  
ft3/min (m3/min)  
390 (11.1)  
187 – 253  
Moisture removal (High)  
Pints/h  
4.5 / 4.3  
Cooling  
Electrical Rating  
Available voltage range  
Running amperes  
Power input  
Heating  
V
A
W
7.6 / 8.1  
1,700 / 1,660  
99  
7.1 / 7.5  
1,610 / 1,540  
99  
Power factor  
%
SEER (HSPF)  
BTU/W  
A
10.5  
(6.8)  
Compressor locked rotor amperes  
Heater element  
43  
kW  
Features  
Controls / Temperature control  
Microprocessor / I.C. thermostat  
Control unit  
Timer  
Wireless remote control unit  
ON / OFF 12 hours, 1-hour OFF  
3 and Auto / 1 (Hi)  
Manual  
Fan speeds  
Indoor / Outdoor  
Airflow direction (Indoor)  
Horizontal  
Vertical  
Auto  
Air filter  
Washable  
Compressor  
Rotary (Hermetic)  
3.97 (1.80)  
Refrigerant / Amount charged at shipment lb. (kg)  
Refrigerant control  
Capillary tube  
41 / 38 / 36  
Operation sound  
Indoor: Hi / Me / Lo dB-A  
Outdoor: Hi  
dB-A  
52  
Refrigerant tubing connections  
Flare  
Max allowable tubing length at shipment  
ft. (m)  
inch (mm)  
inch (mm)  
25 (7.5)  
Refrigerant tubing  
diameter  
Narrow tube  
Wide tube  
1/4 (6.35)  
5/8 (15.88)  
Dimensions & Weight  
Indoor Unit  
Outdoor Unit  
24-19/32 (625)  
34-21/32 (880)  
12-19/32 (320)  
27-15/16 (710)  
40-9/16 (1,030)  
16-3/16 (411)  
108 (49)  
Unit dimensions  
Height  
Width  
Depth  
Height  
Width  
Depth  
Net  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
inch (mm)  
lb. (kg)  
11-7/32 (285)  
39-3/16 (995)  
7-23/32 (196)  
10-7/8 (276)  
42-1/8 (1,070)  
14-9/32 (363)  
26.5 (12.0)  
Package dimensions  
Weight  
Shipping  
lb. (kg)  
cu.ft (m3)  
33 (15.0)  
117 (53)  
Shipping volume  
3.78 (0.107)  
10.6 (0.301)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
4
2-2. Major Component Specifications  
2-2-1. Indoor Unit  
(1) Indoor unit  
KHS0951  
Control PCB  
Part No.  
Controls  
Control circuit fuse  
POW-KHS095A, POW-KHS095B  
Microprocessor  
AC 115V – 3A  
Remote Control Unit  
RCS-1HS2U  
Fan & Fan Motor  
Type  
Cross-flow  
Q’ty … Dia. and length  
inch (mm)  
W
1 … ø 3-3/4 / L24-9/32 (ø 95 / L617)  
Fan motor model … Q’ty  
Nominal output  
KFV4-21H1PA … 1P  
20  
Coil resistance (ambient temp. 68°F (20°C))  
BLU – BRN: 100.9  
BLU – PNK: 127.5  
Run capacitor  
µF  
3.5  
VAC  
180  
Flap Motor  
Type  
Stepping motor  
Model  
MP24GA1  
DC12V  
Rating  
Coil resistance (ambient temp. 77°F (25°C))  
WHT – BLU (respectively 4 wires): 380 ± 7%  
Heat Exchanger Coil  
Coil  
Aluminum plate fin / Copper tube  
Rows  
2
Fin pitch  
Face area  
inch (mm)  
ft2 (m2)  
1/16 (1.4)  
1.40 (0.130)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
5
(2) Indoor unit  
KHS1251  
Control PCB  
Part No.  
Controls  
Control circuit fuse  
POW-KHS125A / POW-KHS095B  
Microprocessor  
AC 115V – 3A  
Remote Control Unit  
RCS-1HS2U  
Fan & Fan Motor  
Type  
Cross-flow  
Q’ty … Dia. and length  
inch (mm)  
W
1 … ø 3-3/4 / L24-9/32 (ø 95 / L617)  
Fan motor model … Q’ty  
Nominal output  
KFV4-21H1PA … 1P  
20  
Coil resistance (ambient temp. 68°F (20°C))  
BLU – BRN: 100.9  
BLU – PNK: 127.5  
Run capacitor  
µF  
3.5  
VAC  
180  
Flap Motor  
Type  
Stepping motor  
Model  
MP24GA1  
DC12V  
Rating  
Coil resistance (ambient temp. 77°F (25°C))  
WHT – BLU (respectively 4 wires): 380 ± 7%  
Heat Exchanger Coil  
Coil  
Aluminum plate fin / Copper tube  
Rows  
2
Fin pitch  
Face area  
inch (mm)  
ft2 (m2)  
1/16 (1.4)  
1.40 (0.130)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
6
(3) Indoor unit  
KHS1852  
Control PCB  
Part No.  
Controls  
Control circuit fuse  
POW-KHS1852  
Microprocessor  
AC 208 / 230V – 3A  
Remote Control Unit  
RCS-1HS2U  
Fan & Fan Motor  
Type  
Cross-flow  
Q’ty … Dia. and length  
inch (mm)  
W
1 … ø 3-15/32 / L29-3/8 (ø88 / L746)  
Fan motor model … Q’ty  
Nominal output  
UF4-31D6P-S … 1P  
30  
WHT – BRN: 204.2  
WHT – PNK: 158.3  
2.0  
Coil resistance (ambient temp. 68°F (20°C))  
Run capacitor  
µF  
VAC  
440  
Flap Motor  
Type  
Stepping motor  
Model  
MP24GA2  
DC12V  
Rating  
Coil resistance (ambient temp. 77°F (25°C))  
Each terminals (1–2, 1–3, 1–4, 1–5) : 400 ± 7%  
Heat Exchanger Coil  
Coil  
Aluminum plate fin / Copper tube  
Rows  
2
Fin pitch  
Face area  
inch (mm)  
ft2 (m2)  
1/16 (1.3)  
1.68 (0.156)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
7
2-2-2. Outdoor Unit  
(1) Outdoor unit CH0951  
Control PCB  
Part No.  
POW-CH095  
Controls  
Control circuit fuse  
Compressor  
Type  
Rotary (Hermetic)  
C-1R75H2R  
750  
Compressor model  
Nominal output  
W
cc  
Compressor oil … Amount  
Coil resistance (ambient temp. 68°F (20°C))  
SUNISO 4GSD-T … 350  
C – R: 0.841  
C – S: 2.831  
External (OLR)  
MRA99111-9200  
40  
Safety devices  
Run capacitor  
Type  
Overload relay  
µF  
VAC  
400  
Crank case heater  
115V, 20W  
Fan & Fan Motor  
Type  
Propeller  
1 … 16-17/32 (ø 420)  
UE6-21BA1PA … 1  
6 … 630  
Q’ty … Dia. and length  
Fan motor model … Q’ty  
No. of poles … rpm (115V, High)  
Nominal output  
inch. (mm)  
W
20  
Coil resistance (ambient temp. 68°F (20°C))  
BLU – BRN: 45.3  
BLU – PNK: 50.5  
8
Run capacitor  
µF  
VAC  
220  
Heat Exchanger Coil  
Coil  
Aluminum plate fin / Copper tube  
Rows  
2
Fin pitch  
Face area  
inch (mm)  
ft2 (m2)  
1/16 (1.4)  
3.37 (0.313)  
External Finish  
Acrylic baked-on enamel finish  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
8
(2) Outdoor unit CH1251  
Control PCB  
Part No.  
POW-CH095  
Controls  
Control circuit fuse  
Compressor  
Type  
Rotary (Hermetic)  
C-R95H2E  
Compressor model  
Nominal output  
W
cc  
950  
Compressor oil … Amount  
Coil resistance (ambient temp. 68°F (20°C))  
SUNISO 4GSD-T … 570  
C – R: 0.576  
C – S: 3.070  
External (OLR)  
MRA98693-9200  
40  
Safety devices  
Run capacitor  
Type  
Overload relay  
µF  
VAC  
400  
Crank case heater  
115V, 20W  
Fan & Fan Motor  
Type  
Propeller  
1 … 16-17/32 (ø 420)  
UE6-21BA1PA … 1  
6 … 630  
Q’ty … Dia. and length  
Fan motor model … Q’ty  
No. of poles … rpm (115V, High)  
Nominal output  
inch. (mm)  
W
20  
Coil resistance (ambient temp. 68°F (20°C))  
BLU – BRN: 45.3  
BLU – PNK: 50.5  
8
Run capacitor  
µF  
VAC  
220  
Heat Exchanger Coil  
Coil  
Aluminum plate fin / Copper tube  
Rows  
2
Fin pitch  
Face area  
inch (mm)  
ft2 (m2)  
1/16 (1.4)  
3.37 (0.313)  
External Finish  
Acrylic baked-on enamel finish  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
9
(3) Outdoor unit CH1852  
Control PCB  
Part No.  
POW-CH095  
Controls  
Control circuit fuse  
Compressor  
Type  
Rotary (Hermetic)  
C-R132H6D  
1,300  
Compressor model  
Nominal output  
W
cc  
Compressor oil … Amount  
Coil resistance (ambient temp. 68°F (20°C))  
SUNISO 4GSD-T … 500  
C – R: 1.442  
C – S: 2.430  
External (OLR)  
MRA99117-9200  
35  
Safety devices  
Run capacitor  
Type  
Overload relay  
µF  
VAC  
400  
Crank case heater  
230V, 20W  
Fan & Fan Motor  
Type  
Propeller  
1 … 16-17/32 (ø 420)  
KFG6-51E6PA … 1  
6 … 830  
Q’ty … Dia. and length  
Fan motor model … Q’ty  
No. of poles … rpm (230V, High)  
Nominal output  
inch. (mm)  
W
50  
Coil resistance (ambient temp. 68°F (20°C))  
WHT – BRN: 102  
PNK – WHT: 199  
2
Run capacitor  
µF  
VAC  
440  
Heat Exchanger Coil  
Coil  
Aluminum plate fin / Copper tube  
Rows  
2
Fin pitch  
Face area  
inch (mm)  
ft2 (m2)  
1/16 (1.6)  
5.13 (0.477)  
External Finish  
Acrylic baked-on enamel finish  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
10  
2-3. Other Component Specifications  
2-3-1. Indoor Unit  
(1) Indoor unit  
KHS0951  
Transformer  
ATR-T4  
AC 115V, 60Hz  
19V, 0.5A  
Rating  
Primary  
Secondary  
Thermistor (Coil sensor)  
DTN-TKS131B  
Resistance  
k  
32°F (0°C) 15 ± 2%  
Thermistor (Room sensor in lamp Ass’y)  
DTN-TKS134B  
Resistance  
kΩ  
77°F (25°C) 5 ± 3%  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
(2) Indoor unit  
KHS1251  
Transformer  
ATR-T4  
AC 115V, 60Hz  
19V, 0.5A  
Rating  
Primary  
Secondary  
Thermistor (Coil sensor)  
DTN-TKS131B  
Resistance  
kΩ  
32°F (0°C) 15 ± 2%  
Thermistor (Room sensor in lamp Ass’y)  
DTN-TKS134B  
Resistance  
kΩ  
77°F (25°C) 5 ± 3%  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
(3) Indoor unit  
KHS1852  
Transformer  
ATR-T5  
AC 230V, 60Hz  
19V, 0.5A  
Rating  
Primary  
Secondary  
Thermistor (Coil sensor)  
DTN-TKS131B  
Resistance  
kΩ  
32°F (0°C) 15 ± 2%  
Thermistor (Room sensor)  
DTN-TKS142B  
Resistance  
kΩ  
77°F (25°C) 5 ± 3%  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
11  
2-3-2. Outdoor Unit  
(1) Outdoor Unit  
CH0951  
PTC Thermistor  
PS2A E20-470  
Resistance  
at 77°F (25°C)  
at 68°F (20°C)  
47 ± 25%  
Power Relay (PR)  
Coil rating  
DFU24D1-F  
DC 24V  
Coil resistance  
Contact rating  
650 ± 10%  
AC 250V, 20A  
Thermostat (Defrost thermo. 23D)  
Operating temp. °F (°C)  
TRS02-12MSR  
ON  
Diff.  
54 ± 4°F (12 ± 2°C)  
14 deg (8 deg). below  
Thermostat (Low temp. cutoff 23A)  
Operating temp. °F (°C)  
TRS02-M13MSR436  
OFF (OPEN) : 5°F (–15°C)  
ON (CLOSE) : 17°F (–8.3°C)  
4-way Valve (Solenoid coil)  
LB69001 (Coil), VH79102 (Valve)  
Coil rating  
AC 120V, 6W  
DATA SUBJECT TO CHANGE WITHOUT NOTICE  
(2) Outdoor Unit  
CH1251  
PTC Thermistor  
PS2A E20-470  
Resistance  
at 77°F (25°C)  
at 68°F (20°C)  
47 ± 25%  
Power Relay (PR)  
Coil rating  
DFU24D1-F  
DC 24V  
Coil resistance  
Contact rating  
650 ± 10%  
AC 250V, 20A  
Thermostat (Defrost thermo. 23D)  
Operating temp. °F (°C)  
TRS02-12MSR  
ON  
54 ± 4°F (12 ± 2°C)  
Diff.  
14 deg (8 deg). below  
Thermostat (Low temp. cutoff 23A)  
Operating temp. °F (°C)  
TRS02-M13MSR436  
OFF (OPEN) : 5°F (–15°C)  
ON (CLOSE) : 17°F (–8.3°C)  
4-way Valve (Solenoid coil)  
LB69001 (Coil), V26-9201 (Valve)  
Coil rating  
AC 120V, 6W  
DATA SUBJECT TO CHANGE WITHOUT NOTICE  
12  
(3) Outdoor Unit  
CH1852  
Power Relay (PR)  
Coil rating  
DFU24D1-F  
DC 24V  
Coil resistance  
Contact rating  
at 68°F (20°C)  
650 ± 10%  
AC 250V, 20A  
Thermostat (Defrost thermo. 23D)  
Operating temp. °F (°C)  
TRS02-12MSR  
ON  
Diff.  
54 ± 4°F (12 ± 2°C)  
14 deg (8 deg). below  
Thermostat (Low temp. cutoff 23A)  
Operating temp. °F (°C)  
TRS02-M13MSR436  
OFF (OPEN) : 5°F (–15°C)  
ON (CLOSE) : 17°F (–8.3°C)  
4-way Valve (Solenoid coil)  
LB69005 (Coil), V26-9201 (Valve)  
Coil rating  
AC 208-230V, 6W  
DATA SUBJECT TO CHANGE WITHOUT NOTICE  
13  
3. DIMENSIONAL DATA  
3-1. Unit  
3-1-1. Indoor Unit  
(1) Indoor unit  
KHS0951 / KHS1251  
31-11/16 (805)  
6-31/32 (177)  
Drain hose ø23/32 (18)  
Remote control unit  
2-2/5  
(61)  
25/32  
(18.5)  
2-5/16  
3-29/32  
(99.5)  
(58.5)  
*
Narrow tube ø1/4 (6.35)  
Wide tube*  
KHS0951 ø3/8 (9.52)  
KHS1251 ø1/2 (12.7)  
Center of tubing  
hole (2 places)  
Unit: inch (mm)  
14  
(2) Indoor unit  
KHS1852  
39-3/16 (995)  
7-23/32 (196)  
1/8 (3)  
Remote control unit  
2-2/5  
(61)  
25/32  
(18.5)  
(147.5)  
5-13/16  
(147.5)  
5-13/16  
Drain hose ø18  
Center of tubing  
hole (2 places)  
Narrow tube ø6.35 (1/4")  
Wide tube ø15.88 (5/8")  
Unit : inch (mm)  
15  
3-1-2. Outdoor Unit  
(1) Outdoor unit CH0951 / CH1251  
Air intake  
2-ø15/32"  
23-15/16"  
3-25/32"  
15/32"  
Air discharge  
31-2/1"  
11-13/32"  
Narrow tube service valve  
ø6.35 (1/4")  
Wide tube service valve*  
*
CH0951 ø3/8 (9.52)  
CH1251 ø1/2 (12.7)  
Unit: inch (mm)  
16  
(2) Outdoor unit CH1852  
Air intake  
4-ø15/32"  
23-15/16"  
5-11/32"  
15/32"  
Air discharge  
34-21/32"  
12-19/32"  
Narrow tube service valve  
ø6.35 (1/4")  
Wide tube service valve  
ø15.88 (5/8")  
Unit: inch (mm)  
17  
4. REFRIGERANT FLOW DIAGRAM  
4-1. Refrigerant Flow Diagram  
Indoor unit  
KHS0951 / KHS1251  
Outdoor unit CH0951 / CH1251  
Indoor unit  
Outdoor unit  
Accumulator  
Wide tube  
service  
valve  
Wide tube  
4-way  
valve  
Muffler  
O.D.  
3/8" (ø9.52 mm)  
1/2" (ø12.7 mm)  
Capillary  
tube  
Narrow  
tube  
service  
valve  
Narrow tube  
Capillary tube  
Cooling cycle  
Heating cycle  
Strainer  
O.D.  
1/4" (øø6.35 mm)  
Check  
valve  
Indoor unit  
KHS1852  
Outdoor unit CH1852  
Indoor unit  
Outdoor unit  
Accumulator  
Wide tube  
service  
valve  
Wide tube  
4-way  
valve  
Muffler  
O.D.  
5/8" (ø15.88 mm)  
Receiver  
tank  
Capillary  
tube  
Narrow  
tube  
service  
valve  
Narrow tube  
Capillary tube  
Cooling cycle  
Heating cycle  
Strainer  
O.D.  
1/4" (øø6.35 mm)  
Check  
valve  
18  
5. PERFORMANCE DATA  
5-1. Performance Charts  
Indoor Unit  
Outdoor Unit  
KHS0951  
CH0951  
Heating Characteristics  
Cooling Characteristics  
115 V  
115 V  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
13  
12  
11  
10  
9
13  
12  
11  
10  
9
80 (26.7)  
70 (21.1)  
59 (15.0)  
95 (35.0)  
80 (26.7)  
67 (19.4)  
8
8
7
7
6
6
70 80 90 100 110 120  
(21.1) (26.7) (32.2) (37.8) (43.3) (48.9)  
10 20 30 40 50 60 70 80  
(–12.2)(–6.6) (–1.1) (4.4) (10.0) (15.6) (21.1) (26.7)  
60  
(15.6)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
115 V  
115 V  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
(23.9)  
(10.5)  
340  
320  
300  
280  
260  
240  
220  
200  
180  
160  
150  
150  
140  
130  
120  
110  
100  
90  
(22.5)  
(21.1)  
(19.7)  
(18.3)  
(16.9)  
(15.5)  
(14.1)  
(12.7)  
(11.2)  
(10.5)  
(9.8)  
(9.1)  
(8.4)  
(7.7)  
(7.0)  
(6.3)  
(5.6)  
(4.9)  
(4.2)  
(3.5)  
80 (26.7)  
70 (21.1)  
59 (15.0)  
95 (35.0)  
80 (26.7)  
67 (19.4)  
80  
70  
60  
50  
70 80 90 100 110 120  
(21.1) (26.7) (32.2) (37.8) (43.3) (48.9)  
60  
(15.6)  
10 20 30 40 50 60 70 80  
(–12.2)(–6.6) (–1.1) (4.4) (10.0) (15.6) (21.1) (26.7)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
NOTE  
Overload prevention operates to protect the air conditioner when the outdoor ambient temperature reaches an  
abnormally high level while in heating mode. (Refer to 8-5. Overload prevention)  
......  
Points of Rating condition  
Black dots in above charts indicate the following rating conditions.  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Heating: Indoor air temperature 70F° D.B.  
Outdoor air temperature 95°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
19  
Indoor Unit  
Outdoor Unit  
KHS1251  
CH1251  
Heating Characteristics  
Cooling Characteristics  
115 V  
115 V  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
14  
13  
12  
11  
10  
9
14  
13  
12  
11  
10  
9
95 (35.0)  
80 (26.7)  
80 (26.7)  
70 (21.1)  
59 (15.0)  
67 (19.4)  
8
8
7
7
70 80 90 100 110 120  
(21.1) (26.7) (32.2) (37.8) (43.3) (48.9)  
10 20 30 40 50 60 70 80  
(–12.2)(–6.6) (–1.1) (4.4) (10.0) (15.6) (21.1) (26.7)  
60  
(15.6)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
115 V  
115 V  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
(23.9)  
(10.5)  
340  
320  
300  
280  
260  
240  
220  
200  
180  
160  
150  
150  
140  
130  
120  
110  
100  
90  
80 (26.7)  
70 (21.1)  
59 (15.0)  
(22.5)  
(21.1)  
(19.7)  
(18.3)  
(16.9)  
(15.5)  
(14.1)  
(12.7)  
(11.2)  
(10.5)  
(9.8)  
(9.1)  
(8.4)  
(7.7)  
(7.0)  
(6.3)  
(5.6)  
(4.9)  
(4.2)  
(3.5)  
80  
95 (35.0)  
80 (26.7)  
67 (19.4)  
70  
60  
50  
70 80 90 100 110 120  
(21.1) (26.7) (32.2) (37.8) (43.3) (48.9)  
60  
(15.6)  
10 20 30 40 50 60 70 80  
(–12.2)(–6.6) (–1.1) (4.4) (10.0) (15.6) (21.1) (26.7)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
NOTE  
Overload prevention operates to protect the air conditioner when the outdoor ambient temperature reaches an  
abnormally high level while in heating mode. (Refer to 8-5. Overload prevention)  
......  
Points of Rating condition  
Black dots in above charts indicate the following rating conditions.  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Heating: Indoor air temperature 70F° D.B.  
Outdoor air temperature 95°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
20  
Indoor Unit  
Outdoor Unit  
KHS1852  
CH1852  
Heating Characteristics  
Cooling Characteristics  
230 V  
230 V  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
Indoor inlet air  
D.B. temp. ¡F (¡C)  
12  
11  
10  
9
12  
11  
10  
9
95 (35.0)  
80 (26.7)  
67 (19.4)  
80 (26.7)  
70 (21.1)  
8
8
59 (15.0)  
7
7
6
6
5
5
70 80 90 100 110 120  
(21.1) (26.7) (32.2) (37.8) (43.3) (48.9)  
10 20 30 40 50 60 70 80  
(–12.2)(–6.6) (–1.1) (4.4) (10.0) (15.6) (21.1) (26.7)  
60  
(15.6)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
230/208 V  
230/208 V  
80 (26.7)  
Indoor inlet air  
Indoor inlet air  
(23.9)  
(22.5)  
(21.1)  
(19.7)  
(18.3)  
(16.9)  
(15.5)  
(14.1)  
(12.7)  
(11.2)  
(10.5)  
(10.5)  
340  
320  
300  
280  
260  
240  
220  
200  
180  
160  
150  
150  
140  
130  
120  
110  
100  
90  
D.B. temp. ¡F (¡C)  
D.B. temp. ¡F (¡C)  
(9.8)  
(9.1)  
(8.4)  
(7.7)  
(7.0)  
(6.3)  
(5.6)  
(4.9)  
(4.2)  
(3.5)  
70 (21.1)  
59 (15.0)  
95 (35.0)  
80 (26.7)  
67 (19.4)  
80  
70  
60  
50  
70 80 90 100 110 120  
(21.1) (26.7) (32.2) (37.8) (43.3) (48.9)  
60  
(15.6)  
10 20 30 40 50 60 70 80  
(–12.2)(–6.6) (–1.1) (4.4) (10.0) (15.6) (21.1) (26.7)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
Outdoor inlet air D.B. temp. ¡F (¡C)  
NOTE  
Overload prevention operates to protect the air conditioner when the outdoor ambient temperature reaches an  
abnormally high level while in heating mode. (Refer to 8-5. Overload prevention)  
......  
Points of Rating condition  
Black dots in above charts indicate the following rating conditions.  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Heating: Indoor air temperature 70F° D.B.  
Outdoor air temperature 95°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
21  
5-2. Air Throw Distance Chart  
(1) Indoor Unit KHS0951  
Cooling  
Room air temp. : 80¡F (26.7¡C)  
Fan speed  
:
High  
Horizontal distance (ft.)  
15 20  
0
5
10  
25  
30  
0
5
10  
15  
: Flap angle 0° ,  
: Flap angle 30°,  
: Axis air velocity 0°  
: Axis air velocity 30°  
Heating  
Room air temp. : 70¡F (21.1¡C)  
Fan speed  
:
High  
Horizontal distance (ft.)  
15 20  
0
5
10  
25  
30  
0
5
10  
15  
: Flap angle 45° ,  
: Flap angle 60° ,  
: Axis air velocity 45°  
: Axis air velocity 60°  
22  
(2) Indoor Unit KHS1251  
Cooling  
Room air temp. : 80¡F (26.7¡C)  
Fan speed  
:
High  
Horizontal distance (ft.)  
15 20  
0
5
10  
25  
30  
0
5
10  
15  
: Flap angle 0° ,  
: Flap angle 30°,  
: Axis air velocity 0°  
: Axis air velocity 30°  
Heating  
Room air temp. : 70¡F (21.1¡C)  
Fan speed  
:
High  
Horizontal distance (ft.)  
15 20  
0
5
10  
25  
30  
0
5
10  
15  
: Flap angle 45° ,  
: Flap angle 60° ,  
: Axis air velocity 45°  
: Axis air velocity 60°  
23  
(3) Indoor Unit KH1852  
Cooling  
Room air temp. : 80¡F (26.7¡C)  
Fan speed  
:
High  
Horizontal distance (ft.)  
15 20  
0
5
10  
25  
30  
0
5
10  
15  
: Flap angle 0° ,  
: Flap angle 30°,  
: Axis air velocity 0°  
: Axis air velocity 30°  
Heating  
Room air temp. : 70¡F (21.1¡C)  
Fan speed  
:
High  
Horizontal distance (ft.)  
15 20  
0
5
10  
25  
30  
0
5
10  
15  
: Flap angle 45° ,  
: Flap angle 60° ,  
: Axis air velocity 45°  
: Axis air velocity 60°  
24  
5-3. Cooling Capacity  
Indoor Unit  
Outdoor Unit  
KHS0951  
CH0951  
115V Single phase 60 Hz  
RATING CAPACITY :  
EVAPORATOR  
9,100 BTU/h  
AIR FLOW RATE:  
CONDENSER  
270 CFM  
ENT.TEMP.°F (°C)  
AMBIENT TEMP °F (°C)  
WB  
DB  
75  
85  
95  
105  
115  
(23.9)  
9,220  
0.64  
(29.4)  
8,770  
0.7  
(35.0)  
8,260  
0.76  
(40.6)  
7,690  
0.82  
(46.1)  
7,050  
0.9  
TC  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
6,720  
7,580  
8,470  
9,220  
9,220  
9,560  
0.65  
6,490  
7,350  
8,240  
8,770  
8,770  
9,140  
0.71  
6,240  
7,090  
7,990  
8,260  
8,260  
8,680  
0.77  
5,960  
6,820  
7,690  
7,690  
7,690  
8,160  
0.84  
5,650  
6,510  
7,050  
7,050  
7,050  
7,600  
0.92  
59  
(15.0)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
5,670  
6,520  
7,420  
8,270  
9,130  
9,930  
0.65  
5,470  
6,330  
7,220  
8,080  
8,930  
9,540  
0.71  
5,260  
6,120  
7,010  
7,870  
8,680  
# 9,100  
0.78  
5,020  
5,880  
6,780  
7,630  
8,160  
8,620  
0.85  
4,780  
5,630  
6,530  
7,380  
7,600  
8,090  
0.94  
63  
(17.2)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
4,610  
5,470  
6,360  
7,220  
8,080  
10,460  
0.66  
4,450  
5,300  
6,200  
7,050  
7,910  
10,090  
0.72  
4,260  
5,120  
6,010  
6,870  
7,720  
9,700  
0.79  
4,060  
4,920  
5,810  
6,670  
7,520  
9,270  
0.87  
3,850  
4,700  
5,600  
6,450  
7,310  
8,800  
0.96  
67  
(19.4)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
3,560  
4,420  
5,310  
6,170  
7,030  
10,670  
0.67  
3,420  
4,270  
5,170  
6,030  
6,880  
10,320  
0.73  
3,270  
4,120  
5,020  
5,880  
6,730  
9,960  
0.8  
3,100  
3,960  
4,860  
5,710  
6,570  
9,540  
0.89  
2,930  
3,790  
4,680  
5,540  
6,390  
9,090  
0.99  
71  
(21.7)  
CI  
75  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
3,280  
4,180  
5,030  
5,890  
3,160  
4,060  
4,910  
5,770  
3,040  
3,930  
4,790  
5,640  
2,890  
3,790  
4,640  
5,500  
2,740  
3,640  
4,490  
5,350  
(23.9)  
TC :Total Cooling Capacity (BTU/h)  
SHC:Sensible Heat Capacity (BTU/h)  
CI :Compressor Input 
(kW)  
Rating conditions are  
:Outdoor Ambient Temp.95°FDB  
:Indoor Unit Entering Air Temp.80°FDB/67°FWB  
25  
Indoor Unit  
Outdoor Unit  
KHS1251  
CH1251  
115 V Single phase 60 Hz  
RATING CAPACITY :  
EVAPORATOR  
11,700 BTU/h  
AIR FLOW RATE:  
CONDENSER  
330 CFM  
ENT.TEMP.°F (°C)  
AMBIENT TEMP °F (°C)  
WB  
DB  
75  
85  
95  
105  
(40.6)  
9,890  
1.15  
115  
(46.1)  
9,070  
1.26  
(23.9)  
11,850  
0.89  
(29.4)  
11,280  
0.98  
(35.0)  
10,620  
1.06  
TC  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
8,440  
9,450  
10,500  
11,510  
11,850  
12,300  
0.9  
8,140  
9,150  
10,200  
11,210  
11,280  
11,750  
0.99  
7,800  
8,810  
9,860  
10,620  
10,620  
11,160  
1.08  
7,430  
8,440  
9,490  
9,890  
9,890  
10,490  
1.17  
7,030  
8,040  
9,070  
9,070  
9,070  
9,770  
1.29  
59  
(15.0)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
7,180  
8,190  
9,240  
10,250  
11,260  
12,760  
0.91  
6,920  
7,920  
8,980  
9,980  
10,990  
12,260  
1
6,640  
7,640  
8,700  
9,700  
10,710  
# 11,700  
1.09  
6,320  
7,330  
8,380  
9,390  
10,400  
11,080  
1.19  
6,000  
7,000  
8,060  
9,060  
9,770  
10,400  
1.32  
63  
(17.2)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
5,910  
6,920  
7,970  
8,980  
9,980  
13,440  
0.92  
5,690  
6,700  
7,750  
8,760  
9,760  
12,980  
1.01  
5,450  
6,450  
7,500  
8,510  
9,520  
12,470  
1.11  
5,180  
6,190  
7,240  
8,250  
9,250  
11,920  
1.22  
4,900  
5,900  
6,960  
7,960  
8,970  
11,310  
1.35  
67  
(19.4)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
4,660  
5,660  
6,720  
7,720  
8,730  
13,710  
0.94  
4,470  
5,480  
6,530  
7,540  
8,540  
13,270  
1.02  
4,270  
5,280  
6,330  
7,330  
8,340  
12,800  
1.12  
4,050  
5,060  
6,110  
7,120  
8,130  
12,260  
1.25  
3,820  
4,830  
5,880  
6,890  
7,890  
11,690  
1.38  
71  
(21.7)  
CI  
75  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
4,290  
5,340  
6,350  
7,360  
4,130  
5,180  
6,190  
7,200  
3,960  
5,020  
6,020  
7,030  
3,770  
4,830  
5,830  
6,840  
3,580  
4,630  
5,640  
6,640  
(23.9)  
TC :Total Cooling Capacity (BTU/h)  
SHC:Sensible Heat Capacity (BTU/h)  
CI :Compressor Input 
(kW)  
Rating conditions are  
:Outdoor Ambient Temp.95°FDB  
:Indoor Unit Entering Air Temp.80°FDB/67°FWB  
26  
Indoor Unit  
Outdoor Unit  
KHS1852  
CH1852  
208 V Single phase 60 Hz  
RATING CAPACITY :  
EVAPORATOR  
17,000 BTU/h  
AIR FLOW RATE:  
CONDENSER  
390 CFM  
ENT.TEMP.°F (°C)  
AMBIENT TEMP °F (°C)  
WB  
DB  
75  
85  
95  
105  
115  
(23.9)  
17,220  
1.26  
(29.4)  
16,390  
1.38  
(35.0)  
15,440  
1.5  
(40.6)  
14,370  
1.62  
(46.1)  
13,180  
1.79  
TC  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
11,770  
12,960  
14,210  
15,410  
16,600  
17,870  
1.28  
11,290  
12,480  
13,730  
14,920  
16,120  
17,070  
1.4  
10,750  
11,950  
13,200  
14,390  
15,440  
16,220  
1.52  
10,170  
11,360  
12,610  
13,800  
14,370  
15,250  
1.66  
9,540  
10,730  
11,980  
13,170  
13,180  
14,200  
1.82  
59  
(15.0)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
10,190  
11,380  
12,630  
13,830  
15,020  
18,550  
1.29  
9,770  
10,960  
12,210  
13,400  
14,590  
17,820  
1.41  
9,320  
8,830  
10,030  
11,270  
12,470  
13,660  
16,100  
1.68  
8,320  
9,510  
10,760  
11,950  
13,150  
15,110  
1.86  
63  
10,520  
11,770  
12,960  
14,150  
# 17,000  
1.54  
(17.2)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
8,600  
9,790  
11,040  
12,230  
13,430  
19,530  
1.3  
8,240  
9,440  
10,680  
11,880  
13,070  
18,850  
1.42  
7,850  
7,430  
8,630  
9,880  
11,070  
12,260  
17,320  
1.72  
6,990  
8,180  
9,430  
10,620  
11,810  
16,440  
1.9  
67  
9,050  
(19.4)  
10,290  
11,490  
12,680  
18,120  
1.56  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
7,040  
8,240  
9,480  
10,680  
11,870  
19,920  
1.32  
6,740  
7,930  
9,180  
10,380  
11,570  
19,280  
1.45  
6,420  
6,080  
7,280  
8,520  
9,720  
10,910  
17,820  
1.76  
5,710  
6,910  
8,160  
9,350  
10,540  
16,980  
1.95  
71  
7,620  
(21.7)  
8,860  
10,060  
11,250  
18,600  
1.59  
CI  
75  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
6,480  
7,720  
8,920  
10,110  
6,220  
7,470  
8,660  
9,860  
5,960  
5,660  
6,900  
8,100  
9,290  
5,340  
6,590  
7,780  
8,980  
(23.9)  
7,200  
8,400  
9,590  
TC :Total Cooling Capacity (BTU/h)  
SHC:Sensible Heat Capacity (BTU/h)  
(kW)  
CI :Compressor Input 
Rating conditions are  
:Outdoor Ambient Temp.95°FDB  
:Indoor Unit Entering Air Temp.80°FDB/67°FWB  
27  
Indoor Unit  
Outdoor Unit  
KHS1852  
CH1852  
230 V Single phase 60 Hz  
RATING CAPACITY :  
EVAPORATOR  
17,000 BTU/h  
AIR FLOW RATE:  
CONDENSER  
390 CFM  
ENT.TEMP.°F (°C)  
AMBIENT TEMP °F (°C)  
WB  
DB  
75  
85  
95  
105  
115  
(23.9)  
17,220  
1.26  
(29.4)  
16,390  
1.38  
(35.0)  
15,440  
1.5  
(40.6)  
14,370  
1.62  
(46.1)  
13,180  
1.79  
TC  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
11,770  
12,960  
14,210  
15,410  
16,600  
17,870  
1.28  
11,290  
12,480  
13,730  
14,920  
16,120  
17,070  
1.4  
10,750  
11,950  
13,200  
14,390  
15,440  
16,220  
1.52  
10,170  
11,360  
12,610  
13,800  
14,370  
15,250  
1.66  
9,540  
10,730  
11,980  
13,170  
13,180  
14,200  
1.82  
59  
(15.0)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
10,190  
11,380  
12,630  
13,830  
15,020  
18,550  
1.29  
9,770  
10,960  
12,210  
13,400  
14,590  
17,820  
1.41  
9,320  
8,830  
10,030  
11,270  
12,470  
13,660  
16,100  
1.68  
8,320  
9,510  
10,760  
11,950  
13,150  
15,110  
1.86  
63  
10,520  
11,770  
12,960  
14,150  
# 17,000  
1.54  
(17.2)  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
8,600  
9,790  
11,040  
12,230  
13,430  
19,530  
1.3  
8,240  
9,440  
10,680  
11,880  
13,070  
18,850  
1.42  
7,850  
7,430  
8,630  
9,880  
11,070  
12,260  
17,320  
1.72  
6,990  
8,180  
9,430  
10,620  
11,810  
16,440  
1.9  
67  
9,050  
(19.4)  
10,290  
11,490  
12,680  
18,120  
1.56  
CI  
72(22.2)  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
SHC  
TC  
7,040  
8,240  
9,480  
10,680  
11,870  
19,920  
1.32  
6,740  
7,930  
9,180  
10,380  
11,570  
19,280  
1.45  
6,420  
6,080  
7,280  
8,520  
9,720  
10,910  
17,820  
1.76  
5,710  
6,910  
8,160  
9,350  
10,540  
16,980  
1.95  
71  
7,620  
(21.7)  
8,860  
10,060  
11,250  
18,600  
1.59  
CI  
75  
76(24.4)  
80(26.7)  
84(28.9)  
88(28.9)  
SHC  
SHC  
SHC  
SHC  
6,480  
7,720  
8,920  
10,110  
6,220  
7,470  
8,660  
9,860  
5,960  
5,660  
6,900  
8,100  
9,290  
5,340  
6,590  
7,780  
8,980  
(23.9)  
7,200  
8,400  
9,590  
TC :Total Cooling Capacity (BTU/h)  
SHC:Sensible Heat Capacity (BTU/h)  
(kW)  
CI :Compressor Input 
Rating conditions are  
:Outdoor Ambient Temp.95°FDB  
:Indoor Unit Entering Air Temp.80°FDB/67°FWB  
28  
5-4. Heating Capacity  
Indoor unit  
KHS0951 / KHS1251 / KHS1852  
Outdoor unit CH0951 / CH1251 / CH1852  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
17 20  
30  
40  
47 50  
60  
Outdoor temperature (¡F DB)  
NOTE  
1)  
… Point of rating condition  
Black dot in the chart indicates the following rating condition.  
Indoor: 70°F (21.1°C) D.B.  
Outdoor: 47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
2) Above characteristics indicate instantaneous operation, which does not take into account defrost  
operation.  
3) Fan speed: High  
4) Because this air conditioner heats a room by drawing in the heat of the outside air (heat pump system),  
the heating efficiency will fall off when the outdoor temperature is very low. If sufficient heat cannot be  
obtained with this air conditioner, use another heating appliance in conjunction with it.  
29  
6. ELECTRICAL DATA  
6-1. Electrical Characteristics  
Indoor Unit  
Outdoor Unit  
KHS0951  
CH0951  
COOLING  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor Compressor  
115V Single phase 60Hz  
Complete Unit  
Performance at  
Rating Conditions  
Running Amps.  
Power Input  
A
kW  
A
0.40  
0.034  
0.40  
0.70  
0.081  
0.70  
7.4  
0.775  
9.1  
8.5  
0.89  
10.2  
1.10  
Full Load Conditions Running Amps.  
Power Input  
kW  
0.034  
0.081  
0.985  
Rating Conditions  
: Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
Outdoor Air Temperature 95°F (35°C) D.B.  
Full Load Conditions : Indoor Air Temperature 95°F (35°C) D.B. / 70°F (21.2°C) W.B.  
Outdoor Air Temperature 115°F (46.1°C) D.B.  
HEATING  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor Compressor  
115V Single phase 60Hz  
Complete Unit  
Performance at  
Rating Conditions  
Running Amps.  
Power Input  
A
kW  
A
0.40  
0.034  
0.40  
0.70  
0.081  
0.70  
7.3  
0.775  
8.6  
8.4  
0.89  
9.7  
Full Load Conditions Running Amps.  
Power Input  
kW  
0.034  
0.081  
0.935  
1.05  
Rating Conditions  
: Indoor Air Temperature 70°F (21.1°C) D.B.  
Outdoor Air Temperature 47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
Full Load Conditions : Indoor Air Temperature 80°F (26.7°C) D.B.  
Outdoor Air Temperature 75°F (23.9°C) D.B. / 65°F (18.3°C) W.B.  
30  
Indoor Unit  
Outdoor Unit  
KHS1251  
CH1251  
COOLING  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor Compressor  
115V Single phase 60Hz  
Complete Unit  
Performance at  
Rating Conditions  
Running Amps.  
Power Input  
A
kW  
A
0.40  
0.034  
0.40  
0.70  
0.081  
0.70  
9.4  
10.5  
1.20  
12.9  
1.48  
1.085  
11.8  
Full Load Conditions Running Amps.  
Power Input  
kW  
0.034  
0.081  
1.365  
Rating Conditions  
: Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
Outdoor Air Temperature 95°F (35°C) D.B.  
Full Load Conditions : Indoor Air Temperature 95°F (35°C) D.B. / 70°F (21.2°C) W.B.  
Outdoor Air Temperature 115°F (46.1°C) D.B.  
HEATING  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor Compressor  
115V Single phase 60Hz  
Complete Unit  
Performance at  
Rating Conditions  
Running Amps.  
Power Input  
A
kW  
A
0.40  
0.034  
0.40  
0.70  
0.081  
0.70  
9.2  
10.3  
1.17  
12.0  
1.37  
1.055  
10.9  
Full Load Conditions Running Amps.  
Power Input  
kW  
0.034  
0.081  
1.255  
Rating Conditions  
: Indoor Air Temperature 70°F (21.1°C) D.B.  
Outdoor Air Temperature 47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
Full Load Conditions : Indoor Air Temperature 80°F (26.7°C) D.B.  
Outdoor Air Temperature 75°F (23.9°C) D.B. / 65°F (18.3°C) W.B.  
31  
Indoor Unit  
Outdoor Unit  
KHS1852  
CH1852  
COOLING  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor Compressor  
230 / 208V Single phase 60Hz  
Complete Unit  
Performance at  
Rating Conditions  
Running Amps.  
Power Input  
A
0.25  
kW 0.047 / 0.045 0.113 / 0.095 1.54  
0.25 0.23 0.49 0.46 8.8  
kW 0.047 / 0.045 0.113 / 0.095 1.98  
/
0.23  
0.49  
/
0.46  
6.86  
/
/
/
/
7.41  
1.52  
9.7  
7.6  
1.70  
9.5  
/
/
/
/
8.1  
1.66  
10.4  
2.12  
Full Load Conditions Running Amps.  
Power Input  
A
/
/
1.98  
2.14  
Rating Conditions  
: Indoor Air Temperature 80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
Outdoor Air Temperature 95°F (35°C) D.B.  
Full Load Conditions : Indoor Air Temperature 95°F (35°C) D.B. / 70°F (21.2°C) W.B.  
Outdoor Air Temperature 115°F (46.1°C) D.B.  
HEATING  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor Compressor  
230 / 208V Single phase 60Hz  
Complete Unit  
Performance at  
Rating Conditions  
Running Amps.  
Power Input  
A
0.25  
kW 0.047 / 0.045 0.113 / 0.095 1.45  
0.25 0.23 0.49 0.46 8.6  
kW 0.047 / 0.045 0.113 / 0.095 1.94  
/
0.23  
0.49  
/
0.46  
6.36  
/
/
/
/
6.81  
1.40  
9.4  
7.1  
1.61  
9.3  
/
/
/
/
7.5  
1.54  
10.1  
2.06  
Full Load Conditions Running Amps.  
Power Input  
A
/
/
1.92  
2.10  
Rating Conditions  
: Indoor Air Temperature 70°F (21.1°C) D.B.  
Outdoor Air Temperature 47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
Full Load Conditions : Indoor Air Temperature 80°F (26.7°C) D.B.  
Outdoor Air Temperature 75°F (23.9°C) D.B. / 65°F (18.3°C) W.B.  
32  
6-2. Electric Wiring Diagrams  
(1) Indoor unit  
KHS0951 / KHS1251  
WARNING  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
33  
(2) Indoor unit  
KHS1852  
WARNING  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
34  
(3) Outdoor unit CH0951 / CH1251  
WARNING  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
35  
(4) Outdoor unit CH1852  
WARNING  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
36  
(5) Printed circuit board  
POW-KHS095A (for KHS0951)  
Top view  
Bottom view  
37  
(6) Printed circuit board  
POW-KHS125A (for KHS1251)  
Top view  
Bottom view  
38  
(7) Printed circuit board  
POW-KHS095B (for KHS0951 and KHS1251)  
Top view  
Bottom view  
39  
(8) Printed circuit board  
POW-KHS1852 (for KHS1852)  
Top view  
Bottom view  
40  
(9) Printed circuit board  
POW-CH095 (for CH0951, CH1251 and CH1852)  
Top view  
41  
7. INSTALLATION INSTRUCTIONS  
7-1. Installation Site Selection  
7-1-1. Indoor Unit  
Indoor unit  
To prevent abnormal heat  
WARNING  
generation and the possibility  
of fire, do not place obsta-  
cles, enclosures and grilles  
in front of or surrounding the  
air conditioner in a way that  
may block air flow.  
Drain hose  
AVOID:  
Outside drainage  
direct sunlight.  
Fig. 1  
nearby heat sources that may affect performance of  
the unit.  
2" (5 cm) min.  
*6" (15 cm) min.  
2" (5 cm) min.  
*6" (15 cm) min.  
2" (5 cm) min.  
*6" (15 cm) min.  
areas where leakage of flammable gas may be  
expected.  
places where large amounts of oil mist exist.  
Front View  
*
KHS1852 only  
DO:  
Fig. 2  
select an appropriate position from which every cor-  
ner of the room can be uniformly cooled. (High on a  
wall is best.)  
Tubing length (L)  
INDOOR  
UNIT  
select a location that will hold the weight of the unit.  
Elevation  
difference (H)  
select a location where tubing and drain hose have  
the shortest run to the outside. (Fig. 1)  
OUTDOOR  
UNIT  
allow room for operation and maintenance as well as  
unrestricted air flow around the unit. (Fig. 2)  
Fig. 3a  
install the unit within the maximum elevation differ-  
ence (H) above the outdoor unit and within a total  
tubing length (L) from the outdoor unit as detailed in  
Table 1 and Fig. 3a.  
Indoor unit  
Wall  
CAUTION  
For stable operation of the  
air conditioner, do not  
install wall-mounted type  
indoor units under 5 ft.  
(1.5 m) from floor level.  
Minimum height  
from floor level  
5 ft. (1.5 m)  
Floor level  
Fig. 3b  
Table 1  
Max. Allowable Tubing  
Length at Shipment  
(ft.)  
Limit of Tubing  
Length (L)  
(ft.)  
Limit of Elevation  
Difference (H)  
(ft.)  
Required Amount of  
Additional Refrigerant  
Model  
*
(oz./ft.)  
25  
25  
50  
65  
23  
23  
a) 0.16  
b) 0.27  
9,000 BTU  
12,000/18,000 BTU  
*
If total tubing length becomes a) 25 to 50 ft. (max.), b) 25 to 65 ft. (max.) charge additional refrigerant (R22) by a) 0.16 oz./ft., b) 0.27 oz./ft.  
No additional compressor oil is necessary.  
42  
7-1-2. Outdoor Unit  
AVOID:  
Exhaust fan  
NO  
Hot air  
heat sources, exhaust fans, etc. (Fig. 4)  
Heat source  
damp, humid or uneven locations.  
DO:  
Outdoor unit  
choose a place as cool as possible.  
choose a place that is well ventilated.  
allow enough room around the unit for air intake/  
Fig. 4  
exhaust and possible maintenance. (Fig. 5a)  
Obstacle above  
CAUTION  
Min.  
Min.  
7 ft.  
(2 m)  
7 ft.  
Air intake  
Min. 6" (15 cm)  
Valve side  
Min. 10"  
(25 cm)  
(2 m)  
Install the outdoor unit above snowfall line.  
Do not place objects on or sit on the out-  
door unit. Also, never block the air  
intake/outlet or exhaust. Distortion of the  
outdoor unit or incomplete combustion  
may result.  
Min. 6"  
(15 cm)  
Air discharge  
Min. 12"  
(30 cm)  
Ground  
Do not introduce foreign matter into the air  
Min. 6 in.  
(15 cm)  
Air intake  
intake/outlet or exhaust. Do not poke them  
with such objects as a stick.  
Fig. 5a  
provide a solid base (level concrete pad, concrete  
Anchor bolts  
(4 pcs)  
´
´
block, 4 in. 16 in. (10 40 cm) beams or equal), a  
minimum of 4 in. (10 cm) above ground level to  
reduce humidity and protect the unit against possible  
water damage and decreased service life (Fig. 5b).  
Min. 4"  
(10 cm)  
Air intake  
use lug bolts or equal to bolt down unit, reducing  
vibration and noise.  
Concrete  
or equal  
Fig. 5b  
43  
7-2. Remote Control Unit Installation  
Position  
The remote control unit can be operated from either a  
non-fixed position or a wall-mounted position.  
To ensure that the air conditioner operates correctly, do  
not install the remote control unit in the following places:  
In direct sunlight  
Behind a curtain or other place where it is covered  
More than 26 ft. (8 m) away from the air conditioner  
In the path of the air conditioner’s airstream  
Where it may become extremely hot or cold  
Where it may be subject to electrical or magnetic  
interference  
Removable mounting  
7-2-1. Mounting on a Wall  
Wall  
a) Removable mounting  
1) Momentarily hold the remote control unit at the  
desired mounting position.  
Special  
mounting  
screw  
(Packed in indoor unit)  
2) Confirm that the air conditioner responds cor-  
rectly when you press keys on the remote con-  
trol from that position.  
3) After confirming correct operation, use a screw-  
driver to screw the supplied special mounting  
screw into the wall. (Fig. 6)  
Fig. 6  
4) Hang the remote control unit from the mounting  
screw.  
Non-removable mounting  
Wall  
b) Non-removable mounting  
1) Momentarily hold the remote control unit at the  
desired mounting position.  
2) Confirm that the air conditioner responds cor-  
rectly when you press keys on the remote con-  
trol from that position.  
Screw  
(Packed in indoor unit)  
3) After confirming correct operation, use a screw-  
driver to screw the mounting screw into the wall.  
(Fig. 6)  
Fig. 7  
4) Remove the remote control cover by sliding it  
downward.  
5) Remove the batteries of the remote control unit.  
6) Use a screwdriver to screw the remote control  
unit securing screw into the wall through the hole  
in the battery compartment. (Fig. 7)  
7) Replace the batteries.  
8) Again confirm that the remote control unit oper-  
ates correctly.  
44  
7-3. Address Switches  
If you are installing more than 1 indoor unit (up to 2) in  
the same room, it is necessary for you to assign each  
unit its own address so each can be operated by its own  
remote control unit. You assign the addresses by  
matching the switch positions of each indoor unit with  
the switch positions of its remote control unit. The  
switches of the remote control unit are shown in Fig. 8.  
For instance, to set up 2 indoor units, switch Unit A’s  
address switches. Then switch Unit B’s address switch-  
es. It is important that you match the switches of the air  
conditioner unit with the switches of its remote control  
unit.  
Address  
7-3-1. Finding the Address Switches  
NOTE  
Remote Control Unit  
Address switch is in “A” position at time of shipment.  
Remove the lid and unit’s 2 batteries. You can see the  
switches inside the battery compartment. (Fig. 8)  
Fig. 8  
KHS0951, KHS1251  
Be sure to turn the air con-  
WARNING  
ditioner off and disconnect  
the power before opening  
the unit.  
Risk of Electric Shock  
JP11  
Fig. 9  
7-3-2. Switch Positions for Up to 2 Units  
KHS1852  
Indoor Unit  
Remove the casing, then follow the steps below.  
a) Unscrew the cover plate of the electrical component  
box. Remove the PCB. Locate and cut the jumper  
wire. (Figs. 9 and 10)  
JP11  
Fig. 10  
b) Table 2 shows the positions you can use for up to 2  
indoor units installed in the same room. (Figs. 8, 9  
and 10)  
Table 2  
NOTE  
Indoor Unit Jumper Wire  
JP11  
Remote Control  
Address  
Unit No.  
An indoor unit cannot be remote controlled if its remote  
control unit is too far away (more than 26 ft.). If the  
remote control unit does not seem to work correctly,  
bring it closer to the unit being operated and try again.  
For this reason, if the remote control unit is to be used  
from a fixed position, operation should be checked at  
that position before mounting.  
1
2
A
B
Do not cut  
Cut  
45  
WIRING SYSTEM DIAGRAM  
CH0951, CH1251 Models  
Disconnect  
7-4. Recommended Wire Length  
and Diameter  
Regulations on wiring diameter differ from locality to  
locality. For field wiring requirements, please refer to  
your local electrical codes. Carefully observe these reg-  
ulations when carrying out the installation.  
(Inter-unit)  
INDOOR UNIT  
Terminal  
OUTDOOR UNIT  
Terminal  
switch  
(Field supply)  
Power lines  
1
2
3
4
5
6
1
2
3
4
5
6
NOTE  
Refer to the wiring system diagram (Fig. 11)  
L1  
Refer to your local codes or in the absence of local  
codes with the National Electric Code: ANSI/NFPA70.  
7
L2  
8
(Inter-unit)  
Control lines  
Grounding  
line  
G
G
G
WARNING  
CH1852 Model  
Be sure to comply with local codes on running  
Disconnect  
switch  
(Inter-unit)  
Power lines  
INDOOR UNIT  
Terminal  
OUTDOOR UNIT  
Terminal  
the wire from the outdoor unit to the indoor unit  
(size of wire and wiring method, etc.).  
(Field supply)  
Each wire must be firmly connected.  
1
2
3
4
5
6
1
2
3
4
5
6
No wire should be allowed to touch refrigerant  
tubing, the compressor, or any moving part.  
L1  
WARNING  
7
L2  
8
(Inter-unit)  
Control lines  
Grounding  
line  
G
G
G
To avoid the risk of electric shock, each air  
conditioner unit must be grounded.  
Fig. 11  
CAUTION  
Be sure to connect the power supply line to the  
outdoor unit as shown in the wiring diagram. The  
indoor unit draws its power from the outdoor  
unit.  
46  
8. FUNCTION  
8-1. Room Temperature Control  
Cooling  
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room tem-  
perature sensor in the remote control unit.  
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the  
controller in the indoor unit.  
Signal from remote control unit  
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes  
Thermo.  
OFF  
Thermo.  
ON  
Thermo.  
OFF  
Thermo.  
ON  
Thermo.  
ON  
Thermo.  
ON  
Thermo.  
OFF  
T + 2 ¡F  
set temp.  
T ¡F  
More than  
5 minutes  
5 minutes  
ON  
3 minutes  
Room temp.  
Compressor  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
OFF  
Outdoor fan  
Indoor fan  
ON  
OFF  
Set speed  
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least  
3 minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pres-  
sure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.  
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor  
operation.  
Thermo. ON : When the room temperature is above T + 2°F (T°C is set temperature).  
Compressor  
ON  
Thermo. OFF : When the room temperature is equal to or below set temperature T°F.  
Compressor  
OFF  
47  
Heating  
Room temperature control is obtained by cycling the compressor ON and OFF under control of the room tem-  
perature sensor in the remote control unit.  
The room temperature (and other information) is transmitted every 3 minutes by the remote control unit to the  
controller in the indoor unit.  
Signal from remote control unit  
More than  
3 minutes 3 minutes 3 minutes 3 minutes 3 minutes 3 minutes  
5 minutes  
Thermo.  
OFF  
Thermo.  
ON  
Thermo.  
OFF  
Thermo.  
ON  
set temp.  
T ¡F  
T – 2 ¡F  
T – 4 ¡F  
5 minutes  
5 minutes  
OFF  
Room temp.  
Compressor OFF  
ON  
ON  
ON  
OFF  
Outdoor fan OFF  
Indoor fan OFF  
ON  
OFF  
OFF  
30 seconds  
Set speed  
30 seconds  
LL  
Set speed  
OFF  
LL  
LL  
*1  
Standby lamp OFF ON  
OFF  
ON  
ON  
Indoor heat exch.  
coil temp.  
95 ¡F  
*1  
77 ¡F  
Solenoid coil  
(4 – way valve)  
ON ( Reversing cycle )  
ON  
OFF  
Operation button  
OFF  
The control circuit will not attempt to turn the compressor ON until the compressor has been OFF for at least 5  
minutes. To protect the compressor from stalling out when trying to start against the high side refrigerant pres-  
sure, the control circuit has a built-in automatic time delay to allow the internal pressure to equalize.  
As a protective measure, the control circuit switches the compressor OFF after 5 minutes or more of compressor  
operation.  
Thermo. ON : When the room temperature is below T – 2°F (T°C is set temperature).  
Compressor  
ON  
Thermo. OFF : When the room temperature is equal to or above set temperature T°F.  
Compressor  
OFF  
NOTE  
*1: Refer to "8-6 Cold Draft Prevention".  
48  
8-2. Dry Operation (Dehumidification)  
Dry operation uses the ability of the cooling cycle to remove moisture from the air, but by running at low level to  
dehumidify without greatly reducing the room temperature. The air conditioner repeats the cycle of turning ON  
and OFF automatically as shown in the chart below according to the room temperature.  
Room temp.  
Cooling operation  
T + 4 ¡F  
Dry A zone  
Compressor :  
Continuous operation  
FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation  
Set temp. T ¡F  
only while the compressor is ON.  
T – 2 ¡F  
Dry B zone  
Compressor :  
Intermittent operation (ON for 3 minutes and OFF for 9 minutes)  
FMI (indoor fan) : L (low speed) / LL (very low speed) intermittent ventilation  
only while the compressor is ON.  
Room temp. 59 ¡F  
Monitor zone  
Both the indoor and outdoor units stop.  
NOTE  
Intermittent ventilation occurs by switching the indoor fan speed between L LL.  
Dry operation does not occur when the room temperature is under 15°C, which is the monitor zone.  
When the compressor stops, the indoor fan stops as well.  
8-3. Automatic Switching between Cooling and Heating  
When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and  
the room temperature, and automatically switches to COOLING or HEATING mode to maintain the desired tem-  
perature.  
Room temp. ³ Set temp. COOL  
Room temp. < Set temp. HEAT  
This means that if the room temperature is higher than or equal to the set temperature, COOLING operation  
begins. If the room temperature is lower than the set temperature, HEATING operation begins.  
49  
8-4. Freeze Prevention (Cooling)  
This function prevents freezing of the indoor heat exchange coil.  
When the compressor has been running for 10 minutes or more and the temperature of the indoor heat  
exchange coil falls below 30°F, the control circuit stops the compressor for at least 6 minutes. The compressor  
does not start again until the temperature rises above 46°F or 6 minutes has elapsed.  
Thermo. OFF  
Room temp.  
Thermo. ON  
T + 4 ¡F  
Set temp. T ¡F  
More than  
6 minutes  
Indoor heat exch.  
coil temp.  
6 minutes  
30 ¡F  
More than  
10 minutes  
More than  
10 minutes  
Compressor  
Indoor fan  
OFF  
OFF  
ON  
ON  
ON  
ON  
Set speed  
Set speed  
8-5. Overload Prevention (Heating)  
This function prevents overheating of the indoor heat exchange coil.  
When the temperature of the indoor heat exchange coil rises above 139°F, and if the indoor fan is L (low  
speed), then the fan speed changes from L (low speed) to M (medium speed).  
When the temperature of the indoor heat exchange coil rises above 141°F, the outdoor fan stops.  
141  
139  
Indoor heat  
exch. coil  
temp. ¡F  
126  
120  
Outdoor fan  
Indoor fan  
ON  
OFF  
ON  
H or M or L  
H H, M M, L M  
Compressor  
ON  
50  
8-6. Cold draft Prevention (Heating)  
This function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat  
exchange coil have sufficiently warmed up.  
STANDBY lamp on front of the indoor unit lights up when this function is working.  
when 10 minutes has elapsed,the fan speed is automatically switched to set speed regardless of indoor heat  
exchange coil temperature.  
Max. 10minutes  
95  
Indoor heat exch.  
coil temp. (¡F)  
77  
Indoor fan  
Set speed  
OFF  
LL  
Standby lamp  
ON  
OFF  
51  
8-7. Defrosting Operation (Heating)  
Defrosting Flowchart  
Compressor ON  
Release of overload prevention  
(Outdoor fan operates.)  
Overload  
prevention works.  
Does outdoor fan  
stop?  
YES  
NO  
A
B
C
D
Integrated operating time of  
compressor is more than 3  
hours.  
Integrated operating time of  
compressor is more than 1.5  
hours.  
Outdoor fan is either operated  
or stopped for more than 10  
minutes.  
Indoor heat exchanger coil  
temperature drops 1.4¡F per  
6 minutes and it repeats  
3 times in succession.  
Is outdoor fan continuously  
operating for more than 10  
minutes?  
NO  
Thermo. OFF.  
(Compressor OFF)  
Temperature of indoor heat  
exchanger coil is below 113¡F.  
Temperature of indoor heat  
exchanger coil is below 113¡F.  
YES  
Integrated operating time of  
compressor is more than 50  
minutes.  
Temp. of indoor heat exch.  
coil immediately before thermo  
goes off is either below 113 + 7¡F  
or 136 + 7¡F (when overload  
prevention works).  
Temperature of indoor heat  
exchanger coil is below 113 +  
23¡F.  
NO  
YES  
Continuous operating time of  
compressor is more than 20  
minutes.  
Compressor keeps running for  
at least 6 minutes.  
Compressor keeps running  
for at least 6 minutes.  
Compressor keeps running for  
at least 6 minutes.  
Temperature of outdoor heat  
exchanger coil is below 48¡F.  
Defrosting begins.  
Cold-draft prevention  
Temperature of outdoor heat  
exchange coil is higher than  
Defrosting time is over 12  
minutes.  
54¡F.  
Release of defrosting  
Indoor fan runs at set speed  
when temperature of indoor  
heat exchanger reads 95¡F.  
52  
Defrosting Mode Timing Chart  
Release of defrosting  
32 seconds  
Start of defrosting  
32 seconds  
OFF  
Max. 11 minutes  
Compressor  
Outdoor fan  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
2 seconds  
ON  
2 seconds  
ON  
Solenoid coil  
(4way valve)  
OFF  
Indoor fan  
Set speed  
OFF  
Set speed  
OFF  
LL  
Standby lamp  
Indoor heat  
ON  
ON  
exch. coil  
temp.  
95¡F  
77¡F  
* 1  
Release of  
cold draft prevention  
NOTE  
*1: Refer to "8-6 Cold Draft Prevention".  
8-8. Low Temperature Cutff (Heating)  
This function protect the compressor from being damaged due to flow back of the liquid refrigerant to the com-  
pressor when the outdoor temperature is very low.  
Low ambient operation during heating can cause the outdoor heat exchanger to become super–cooled which  
may result in liquid back–flow. To protect the compressor from this condition, both compressor and outdoor fan  
stop if the outdoor temperature drops around 5°F. However, the indoor fan continues to operate even after the  
compressor has stopped. Note that standby lamp does not lights up during this period.  
Outdoor  
air temp.  
17¡F  
5¡F  
Compressor  
and  
Outdoor fan  
ON  
ON  
OFF  
Indoor fan  
ON  
OFF  
Standby lamp  
53  
9. TROUBLESHOOTING  
9-1. Check before and after troubleshooting  
WARNING  
Hazardous voltage can cause ELECTRIC SHOCK or  
DEATH. Disconnect power or turn off circuit breaker  
before you start checking or servicing.  
9-1-1. Check power supply wiring.  
Check that power supply wires are correctly connected to terminals No. 7 (L1) and No. 8 (L2) on the terminal  
plate in the outdoor unit.  
Outdoor  
unit  
Inter–unit  
power wiring  
Indoor  
unit  
1
2
3
4
5
6
1
2
3
4
5
6
7
8
Power supply :  
L1  
L2  
Single- phase, 60Hz  
115V.....CH0951,CH1251  
230/208V............CH1852  
Inter–unit  
control wiring  
G
G G  
Ground  
Ground  
9-1-2. Check inter-unit wiring.  
Check that inter-unit wiring is correctly connected to the indoor unit from the outdoor unit.  
9-1-3. Check power supply.  
Check that voltage is in specified range (±10% of the rating).  
Check that power is being supplied.  
9-1-4. Check lead wires and connectors in indoor and outdoor units.  
Check that coating of lead wires is not damaged.  
Check that lead wires and connectors are firmly connected.  
Check that wiring is correct.  
54  
9-2. Air conditioner does not operate.  
9-2-1. Circuit breaker trips (or fuse blows).  
A. When the circuit breaker is set to ON, it is tripped soon. (Resetting is not possible.)  
There is a possibility of ground fault.  
Check insulation resistance.  
If resistance value is 2M½ or less, insulation is defective (“NO”).  
2
1
1
Power supply  
wiring  
Indoor  
unit  
Outdoor  
unit  
Inter–unit  
wiring  
L2  
L1  
Power  
supply  
1
1
2
3
4
5
6
8
7
Circuit  
breaker  
2
3
4
5
6
G
G
G
Ground  
WARNING  
*
Set circuit breaker to OFF.  
Remove both power supply wires  
and inter-unit wires from terminal  
plate in outdoor unit.  
Measure insulation resistance  
of outdoor unit.  
1
Insulation of  
outdoor unit  
is defective.  
NO  
Measure insulation  
resistance of electrical  
parts in outdoor unit.  
Remove inter-unit wires from  
terminal plate in indoor unit.  
Measure insulation resistance  
of indoor unit.  
2
Insulation of  
indoor unit  
is defective.  
NO  
Measure insulation  
resistance of electrical  
parts in indoor unit.  
55  
B. Circuit breaker trips in several minutes after turning the air conditioner on.  
There is a possibility of short circuit.  
Check capacity of circuit breaker.  
Replace with suitable  
one (larger capacity).  
NO  
Capacity of circuit breaker is  
suitable.  
In case of Heating operation :  
Measure resistance of outdoor fan  
motor winding.  
Measure resistance of 4-way valve's  
winding.  
Measure resistance of compressor  
motor winding.  
9-2-2. Neither indoor nor outdoor unit runs.  
A. Power is not supplied.  
Circuit breaker  
is tripped.  
Reset breaker.  
Check power supply.  
NO  
Power is being supplied to the  
outdoor unit.  
Wait for recovery  
or contact power  
company.  
Power failure  
B. Check "OPERATION selector" switch in the indoor unit.  
YES  
Lamp Ass'y or indoor PCB Ass'y is  
defective.  
OPERATION selector switch is set  
in ON position.  
NO  
Set OPERATION selector switch  
to ON.  
56  
C. Check remote control unit.  
Try to run with another remote  
control unit.  
OK  
First remote control unit is defective.  
Check for residue buildup on  
transmitter of remote control unit.  
Clean transmitter.  
Clean receiver.  
Check for residue buildup on remote  
control receiver on front of indoor  
unit.  
D. Check fuse on the indoor PCB Ass'y.  
Measure resistance of indoor and/or  
fan motor winding.  
(FM)  
If fuse has been blown,  
Check fuse on indoor PCB Ass'y  
for continuity. (F)  
OK  
OK  
Check operation lamp to see  
if light is ON.  
Measure resistance of compressor  
motor winding.  
(CM)  
Light is OFF  
OK  
Measure resistance of primary and  
secondary winding of transformer.  
Measure coil resistance of power  
relay.  
(PR)  
(TR)  
OK  
OK  
Indoor PCB Ass'y or switch Ass'y is  
defective.  
Replace the fuse.  
E. Check TIMER on the remote control unit.  
Timer is turned ON. Check to see  
YES  
Cancel the timer mode.  
ON  
if  
control.  
is displayed on remote  
57  
9-2-3. Only outdoor unit does not run.  
A. Check setting temperature.  
COOL  
HEAT  
Is room temperature too high ?  
Is room temperature too low ?  
NO  
NO  
Try to lower setting temperature by  
temperature setting button ( button).  
Try to raise setting temperature by  
temperature setting button ( button).  
Outdoor unit still does  
not run.  
Outdoor unit still does  
not run.  
Try to run using another remote  
control unit.  
Try to run using another remote  
control unit.  
OK  
OK  
Remote control unit is defective.  
Remote control unit is defective.  
B. Check PCB Ass'y in either indoor or outdoor unit.  
Check voltage between terminals  
No. 3(+) and No. 4 at terminal plate.  
(DC 24V)  
OK  
Outdoor PCB Ass'y is defective.  
No voltage appears.  
Indoor PCB Ass'y is defective.  
9-2-4. Only indoor unit does not run.  
Indoor PCB Ass'y is defective.  
58  
9-3. Some part of air conditioner does not operate.  
9-3-1. Only indoor fan does not run.  
Check fan casing  
foreign matter on  
inside.  
Remove foreign  
matter or repair.  
Fan cannot  
be turned.  
Check fan rotation.  
Turn fan gently once or twice by  
hand.  
Fan motor burnout  
or foreign matter in  
bearings.  
Repair or replace.  
Measure resistance of indoor fan  
motor winding.  
OK  
Check fan motor capacitor.  
9-3-2. Only flap motor does not run.  
Measure resistance of flap motor  
winding.  
59  
9-3-4. Only outdoor fan does not run.  
Check fan casing  
foreign matter on  
inside.  
Remove foreign  
matter or repair.  
Fan cannot  
be turned.  
Check fan rotation.  
Turn fan gently once or twice by  
hand.  
Fan motor burnout  
or foreign matter in  
bearings.  
Repair or replace.  
Measure resistance of indoor fan  
motor winding.  
OK  
Check fan motor capacitor.  
9-3-5. Only compressor does not run.  
Check compressor motor  
capacitor.  
Measure resistance of PTC  
thermistor.  
Overload relay is working.  
YES  
Temperature of compressor  
is abnormally high.  
Measure resistance of  
compressor motor winding.  
YES  
YES  
Refrigerant gas shortage.  
NO  
Charge refrigerant gas (R22).  
Measure Power supply  
voltage.  
No  
Rotor may be locked up.  
The voltage is too low.  
Measure resistance of power  
relay.  
(PR)  
60  
9-4. Air conditioner operates, but abnormalities are observed.  
9-4-1. Operation does not switch from HEAT to COOL (or COOL to HEAT).  
Remote control unit may be defective.  
Receiver in lamp Ass'y may be  
defective.  
Measure resistance of 4–way valve's  
winding.  
COOL HEAT  
Check voltage between terminals  
No. 3(+) and No. 5 at terminal plate.  
(DC 24V)  
OK  
Outdoor PCB Ass'y is defective.  
No voltage appears.  
Indoor PCB Ass'y is defective.  
HEAT COOL  
Check voltage between terminals  
No. 3(+) and No. 5 at terminal plate.  
(0V)  
61  
9-4-2. Poor cooling or heating.  
Check position of remote control unit.  
YES  
NO  
Change position of remote  
control unit.  
• Cool or warm air from air conditioner  
reaches position directly.  
Wide and narrow tubes between  
indoor unit and outdoor unit are  
insulated.  
Insulate both wide and narrow  
tubes separately and then  
tape together.  
YES  
Temperature  
difference  
is small.  
Possibility of  
gas shortage.  
Charge refrigerant  
gas (R22).  
Measure temperature of suction and  
discharge air of air conditioner.  
Temperature difference between  
suction and discharge air is  
large enough (approx. 10 deg. or more).  
Check for clogging of air filter.  
Clean filter.  
Air filter is clogged.  
YES  
Set fan speed to either  
HIGH or MEDIUM.  
Fan speed is set to LOW.  
Reduce cooling or heating  
load or replace the air  
conditioner with larger  
capacity.  
Review cooling load estimate,  
if performance of air conditioner is  
normal.  
9-4-3. Excessive cooling or heating.  
Set temperature to higher or  
lower value using temperature  
setting buttons of the remote  
control unit.  
NO  
Set temperature is suitable.  
Remote control unit is placed where  
it can detect room temperature  
properly.  
NO  
Change position of remote  
control unit.  
62  
9-5. If a sensor is defective.  
9-5-1. Indoor coil temp. thermistor (TH1) is defective.  
A. Open  
When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect  
extremely low indoor coil temperature.  
In Cooling mode: Function of freeze prevention continues to work. That is, the controller turns both  
compressor and outdoor fan motor periodically ON and OFF for several minutes.  
(Refer to "8-3. Freeze Prevention")  
B. Short  
When thermistor is short, the air conditioner will be in the following conditions as  
the controller tries to detect extremely high indoor coil temperature.  
In Cooling mode: Function of freeze prevention will not work even when the frost builds up on indoor heat  
exchanger coil  
9-5-2. Room temp. thermistor (TH2) is defective.  
A. Open  
When thermistor opens, the air conditioner will be in the following conditions as the controller tries to detect  
extremely low room temperature.  
In Cooling mode:  
The air conditioner soon stops and will not start again. (Thermo.OFF) Neither outdoor  
fan nor compressor runs.  
B. Short  
When thermistor is short, the air conditioner will be in the following conditions as  
the controller tries to detect extremely high room temperature.  
Temperature  
sensor  
In Cooling mode:  
The air conditioner continues to operate (Thermo.ON). Both  
the outdoor fan and compressor do not stop. As a result,  
the room becomes too cold.  
Lead  
wires  
NOTE  
Definition of Open or Short Circuit of Sensor (Thermistor)  
Thermistor Structure  
Open ... A lead wire is broken or disconnected or the circuit inside the temperature sensor is open .  
Short ... The protective cover of a lead wire has been damaged, and the exposed wire is touching another metal  
part, or both lead wires have become exposed and are touching each other. Alternatively, the circuit  
inside the temperature sensor is closed.  
63  
10. CHECKING ELECTRICAL COMPONENTS  
Ground wire  
10-1. Measurement of Insulation  
Resistance  
Clip  
The insulation is in good condition if the resistance  
exceeds 2M½.  
Probe  
10-1-1.Power Supply Wires  
Insulation  
tester  
Fig. 1  
Clamp the ground wire of the power supply wires with  
the lead clip of the insulation resistance tester and  
measure the resistance by placing a probe on either of  
the power wires. (Fig. 1)  
Terminal plate  
Then measure the resistance between the ground wire  
and the other power wire. (Fig. 1)  
Probe  
10-1-2.Indoor Unit  
Clamp an aluminum plate fin or copper tube with the  
lead clip of the insulation resistance tester and mea-  
sure the resistance by placing a probe on each termi-  
nal screw on the terminal plate. (Fig. 2)  
Clip  
Copper  
tube or  
metallic part  
Insulation  
tester  
Note that the ground line terminal should be skipped  
for the check.  
Fig. 2  
10-1-3.Outdoor Unit  
Probe  
Clamp a metallic part of the unit with the lead clip of  
the insulation resistance tester and measure the resis-  
tance by placing a probe on each terminal screw where  
power supply lines are connected on the terminal plate.  
(Fig. 2)  
Clip  
Copper  
tube or  
metallic part  
10-1-4.Measurement of Insulation  
Resistance for Electrical Parts  
Insulation  
tester  
Fig. 3  
Disconnect the lead wires of the desired electric part  
from terminal plate, capacitor, etc. Similarly disconnect  
the connector. Then measure the insulation resistance.  
(Figs. 3 and 4)  
From fan motor,  
compressor and  
other parts  
Probe  
Metallic  
part  
NOTE  
Refer to Electric Wiring Diagram.  
Clip  
If the probe cannot enter the poles because the hole is  
too narrow then use a probe with a thinner pin.  
Insulation  
tester  
Fig. 4  
64  
10-2. Checking Continuity of Fuse  
on PCB Ass'y  
Fuse  
Remove the PCB Ass’y from the electrical compo-  
nent box. Then pull out the fuse from the PCB Ass’y.  
(Fig. 5)  
PCB Ass’y  
Check for continuity using a multimeter as shown in  
Fig. 6.  
Fig. 5  
10-3. Checking Motor Capacitor  
Remove the lead wires from the capacitor terminals,  
and then place a probe on the capacitor terminals as  
shown in Fig. 7. Observe the deflection of the pointer,  
setting the resistance measuring range of the multime-  
ter to the maximum value.  
Fuse  
Fig. 6  
The capacitor is “good” if the pointer bounces to a  
great extent and then gradually returns to its original  
position.  
The range of deflection and deflection time differ  
according to the capacity of the capacitor.  
Multimeter  
Compressor motor  
capacitor  
Fan motor  
capacitor  
Fig. 7  
65  
11. ARRANGEMENT OF ELECTRICAL COMPONENT  
Indoor Unit  
KHS0951 / KHS1251  
Controller B  
(PCB Ass'y B)  
Controller A  
(PCB Ass'y A)  
Transformer  
Terminal base  
1
2
3
4
5
6
G
Coil temp. thermistor  
Lamp Ass'y  
Room temp. thermistor  
Flap motor  
Indoor Unit  
KHS1852  
Fan motor capacitor  
Coil temp. thermistor  
Transformer  
Controller  
(PCB Ass'y)  
1
2
3
4
5
6
Terminal base  
G
Flap motor  
Lamp Ass'y  
Room temp. thermistor  
66  
Outdoor Unit  
CH0951 / CH1251 / CH1852  
Electric Parts  
Terminal base  
Power relay  
PTC Thermistor  
(Only for 115V models)  
Fan motor capacitor  
G
PR  
TH  
UNIT  
CONTROLLER  
20S  
FM1  
SUPPLY  
FM  
Controller (PCB Ass'y)  
Compressor motor capacitor  
Parts Layout in Unit  
Electric compornet box  
Thermostat  
(Low temp. cut-off)  
Solenoid coil  
(4-way valve)  
FM  
CM  
Compressor motor  
Crankcase heater  
Fan Motor  
Defrost thermostat  
67  
INSTRUCTION MANUAL  
APPENDIX  
KHS0951 + CH0951  
KHS1251 + CH1251  
KHS1852 + CH1852  
68  
Features  
This air conditioner is equipped with cooling, heating and drying functions. Details on these functions are  
provided below; refer to these descriptions when using the air conditioner.  
Air Sw eep Control  
Microprocessor Controlled Operation  
The interior com partm ent of the rem ote  
control unit contains several features to  
facilitate autom atic operation, easy logically  
displayed for easy use.  
This function m oves a flap up and down in the  
air outlet, directing air in a sweeping m otion  
around the room and providing com fort in  
every corner.  
Autom atic Sw itching betw een Cooling and  
Heating  
Sim ple One-touch Wireless Rem ote Control  
The rem ote control unit has several features to  
facilitate autom atic operation.  
This unit autom atically switches between  
cooling operation and heating operation  
according to the difference between the room  
tem perature and the tem perature setting.  
12-Hour ON or OFF Tim er  
This tim er can be set to autom atically turn the  
unit on or off at any tim e within a 12 hour  
period.  
Hot Start Heating System  
Right from the start, the air is warm and  
com fortable. This system prevents any cold  
blasts at the beginning while the heat pum p is  
warm ing up, or even defrosting.  
1-Hour OFF Tim er  
This tim er can be set to autom atically turn off  
the unit at any tim e after one hour.  
Autom atic Restart Function for Pow er Failure  
Even when power failure occurs, preset  
program m ed operation can be reactivated  
once power resum es.  
Night Setback  
Pressing this button changes the setting of the  
room tem perature therm ostat, allowing you to  
set the tem perature at whatever level that you  
find com fortable.  
Anti-Mold Filter  
This unit is equipped with an anti-m old filter  
that inhibits the growth of m old and bacteria.  
Autom atic and 3-step Fan Speed  
Auto/High/Medium /Low  
Optional Air Clean Filter  
An air filter that uses activated charcoal to  
elim inate unpleasant odors and clean the air is  
available (sold separately).  
If the outdoor tem perture is extream ly low , it is recom m ended  
to use another heating appliance:  
CAUTION  
When the outdoor tem perature falls to around 5°F, the com pressor stops.  
However, indoor fan continues to operate even after the com pressor has  
been stopped. In this case, to prevent room from freezing, use another  
heating appliance.  
2
OI-330-04EG  
Contents  
Page  
Features .................................................................................................................. 2  
Product Inform ation .............................................................................................. 3  
Alert Sym bols ........................................................................................................ 3  
Installation Location .............................................................................................. 4  
Electrical Requirem ents ........................................................................................ 4  
Safety Instructions ................................................................................................ 4  
Nam es of Parts ...................................................................................................... 5  
Using the Rem ote Control Unit ......................................................................... 10  
Operation with the Rem ote Control Unit......................................................... 12  
1. Autom atic Operation  
12  
............................................................................  
2. Manual Operation ................................................................................. 14  
3. Adjusting the Fan Speed ...................................................................... 15  
4. Night Setback Mode ............................................................................ 16  
Special Rem arks ................................................................................................. 18  
Using the 12-Hour ON and OFF Tim er ............................................................. 19  
Using the 1-Hour OFF Tim er.............................................................................. 20  
Adjusting the Airflow Direction ......................................................................... 21  
Operation without the Rem ote Control Unit ................................................... 22  
Care and Cleaning ................................................................................................ 22  
Tips for Energy Saving ....................................................................................... 25  
Troubleshooting ................................................................................................... 26  
Operating Range ................................................................................................. 26  
Product Information  
If you have problem s or questions concerning your Air Conditioner, you will  
need the following inform ation. Model and serial num bers are on the  
nam eplate on the bottom of the cabinet.  
Model No.  
Serial No.  
Date of purchase  
Dealer's address  
Phone num ber  
Alert Symbols  
The follow ing sym bols used in this m anual, alert you to potentially  
dangerous conditions to users, service personnel or the appliance:  
This sym bol refers to a hazard or unsafe  
practice w hich can result in severe personal  
injury or death.  
This sym bol refers to a hazard or unsafe  
CAUTION  
practice w hich can result in personal injury  
or product or property dam age.  
OI-330-03EG  
3
Installation Location  
We recom m end that this air conditioner be installed properly by  
qualified installation technicians in accordance w ith the Installation  
Instructions provided w ith the unit.  
Before installation, check that the voltage of the electric supply in your  
hom e or office is the sam e as the voltage shown on the nam eplate.  
Do not install this air conditioner w here there are fum es or flam m able  
gases, or in an extrem ely hum id space such as a greenhouse.  
Do not install the air conditioner w here excessively high heat-  
generating objects are placed.  
Avoid:  
To protect the air conditioner from heavy corrosion, avoid installing the  
outdoor unit where salty sea water can splash directly onto it or in  
sulphurous air near a spa.  
Electrical Requirements  
1. All wiring m ust conform to the local electrical codes. Consult your  
dealer or a qualified electrician for details.  
2. Each unit m ust be properly grounded with a ground (or earth) wire or  
through the supply wiring.  
3. Wiring m ust be done by a qualified electrician.  
Safety Instructions  
Read this Instruction Manual carefully before using this air conditioner.  
If you still have any difficulties or problem s, consult your dealer for  
help.  
This air conditioner is designed to give you com fortable room  
conditions. Use this only for its intended purpose as described in this  
Instruction Manual.  
Never use or store gasoline or other flam m able vapor or liquid near  
the air conditioner – it is very dangerous.  
This air conditioner has no ventilator for intaking fresh air from  
outdoors. You m ust open doors or w indow s frequently w hen you use  
gas or oil heating appliances in the sam e room , w hich  
consum e a lot of oxygen from the air. Otherw ise there is a risk of  
suffocation in an extrem e case.  
CAUTION  
Do not turn the air conditioner on and off from the pow er m ains  
sw itch. Use the ON/ OFF operation button.  
Do not stick anything into the air outlet of the outdoor unit. This is  
dangerous because the fan is rotating at high speed.  
Do not let children play w ith the air conditioner.  
Do not cool the room too m uch if babies or invalids are present.  
4
OI-330-04EG  
Names of Parts  
INDOOR UNIT  
Air intakes  
Air outlet  
Rem ote  
control  
unit  
Drain hose  
Refrigerant tubes  
OUTDOOR UNIT  
Air outlet  
This illustration is based on the external appearance of a standard m odel.  
Consequently, the shape m ay differ from that of the air conditioner which  
you have selected.  
NOTE  
This air conditioner consists of an indoor unit and an outdoor unit.  
You can control the air conditioner with the rem ote control unit.  
Air Intakes  
Air from the room is drawn into these sections and passes through  
air filters which rem ove dust.  
Air Outlet  
Air is blown out of the air conditioner through the air outlet.  
Rem ote Control Unit  
Refrigerant Tubes  
The wireless rem ote control unit controls power on/off, operation  
m ode selection, tem perature, fan speed, tim er setting, night  
setback and air sweeping.  
The indoor and outdoor units are connected by copper tubes  
through which refrigerant gas flows.  
Drain Hose  
Moisture in the room condenses and drains off through this hose.  
Outdoor (Condensing) Unit  
The outdoor unit contains the com pressor, fan m otor, heat  
exchanger coil, and other electrical com ponents.  
OI-330-05EG  
5
Unit Display and Operation Selector  
Operation selector  
INDOOR UNIT  
KHS1852  
INDOOR UNIT  
KHS0951  
KHS1251  
ON  
OFF  
ON  
TEST  
OFF  
TEST  
Operation selector  
OPERATION lam p  
TIMER lam p Rem ote control  
receiver  
OPERATION STANDBY TIMER  
Rem ote control receiver  
STANDBY lam p  
OPERATION  
TIMER  
STANDBY  
IMPORTANT  
Avoid using radio equipm ent such as m obile phones  
near (w ithin 1 m of) the indoor unit. Som e radio  
equipm ent m ay cause the unit to m alfunction.  
STANDBY lam p  
TIMER lam p  
OPERATION lam p  
If the trouble occurs, disconnect pow er and restart the  
air conditioner after a few m inutes.  
Rem ote control receiver  
This section picks up infrared signals from the rem ote control unit  
(transm itter).  
Operation selector  
ON position  
This position is for operating the air conditioner with the wireless  
rem ote control unit.  
Set the selector norm ally in this position.  
OFF position  
Switch the selector to the OFF position if you are not going to use  
the air conditioner for a few days or longer.  
The OFF position does not disconnect the pow er. Use the m ain  
pow er sw itch to turn off pow er com pletely.  
TEST position  
CAUTION  
This position is used only when servicing the air conditioner.  
Do not set at the TEST position for norm al operation.  
OPERATION lam p  
This lam p lights when the system is in the continuous HEAT,  
DRY and COOL m ode.  
TIMER lam p  
This lam p lights when the system is being controlled by the tim er.  
STANDBY lam p  
This lam p lights during the warm up period for heating and  
when the system is defrosting.  
6
OI-330-06EG  
Remote Control Unit (Display)  
Displayed when setting tem perature  
Displayed when transm itting data  
SET TEMP.  
1
ON  
HR.  
Displayed when setting tim er  
OFF  
H
Sym bols  
(1) Operation m ode  
(3) Tem perature setting  
60 – 88 °F  
When set to 82 °F ...........  
AUTO.......................................  
HEAT........................................  
MILD DRY................................  
COOL .......................................  
Current tem perature  
indication .........................  
(4) Tim er  
12-hour ON Tim er..................  
12-hour OFF Tim er.................  
1-hour OFF Tim er...................  
(5) NIGHT SETBACK....................  
ON  
OFF  
(2) Fan speed  
1HR.  
AUTO.......................................  
HIGH ........................................  
MEDIUM..................................  
LOW.........................................  
(6) Confirm ation of  
transm ission ...........................  
(7) Flap  
Angle indication .....................  
Sweep indication....................  
OI-202-09EG  
7
Remote Control Unit  
Transm itter  
SET TEMP.  
1HR.  
ON  
OFF  
Display  
ON/ OFF operation button  
1 HR. TIMER button  
H
(Cover closed)  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
TEMP. setting buttons  
MODE selector button  
FAN SPEED selector button  
FLAP button  
MODE  
FLAP FAN SPEED  
ON OFF  
TIMER ON button  
NIGHT  
TIMER OFF button  
SET button  
SETBACK  
SET CANCEL  
NIGHT SETBACK button  
ACL button  
ACL  
BATTERIES  
CANCEL button  
ADDRESS sw itch  
A
B
Battery com partm ent  
(Pull off the cover to expose the  
batteries.)  
The illustration above pictures the rem ote control unit after the cover has  
been lowered and rem oved.  
NOTE  
Transm itter  
When you press the buttons on the rem ote control unit, the  
appears in the display and the setting changes are transm itted to the  
receiver in the air conditioner.  
m ark  
Display  
Inform ation on the operating status is displayed while the rem ote control  
unit is switched on. If the unit is turned off, only the m ode that was set  
previously is still displayed.  
NIGHT SETBACK button  
For details, see “Night Setback Mode”. When you press this button in the  
DRY, COOL or HEAT m ode, the  
m ark appears in the display, and the  
rem ote control unit autom atically adjusts the set tem perature to save  
energy.  
TEMP. setting buttons  
Press the  
Press the  
button to increase the tem perature setting.  
button to reduce the tem perature setting.  
ON/ OFF operation  
button  
This button is for turning the air conditioner on and off.  
TIMER ON button  
TIMER OFF button  
: The air conditioner starts at the set tim e.  
: The air conditioner stops at the set tim e.  
ON  
OFF  
8
OI-202-10EG  
Remote Control Unit (continued)  
MODE selector button  
Green or red (AUTO)  
Use this button to select the AUTO, HEAT, DRY and COOL m ode.  
: When this setting is selected, the air conditioner calculates the  
difference between the therm ostat setting and the room  
tem perature and autom atically switches to the “COOL or  
HEAT” m ode as appropriate.  
Red (HEAT)  
Orange (DRY)  
Green (COOL)  
: The air conditioner m akes the room warm er.  
: The air conditioner reduces the hum idity in the room .  
: The air conditioner m akes the room cooler.  
FLAP button  
Press this button either to select to set the airflow direction to one of  
the six possible positions m anually, or to select the sweep function,  
which m oves the flap up and down autom atically.  
: The airflow direction can be set m anually. (six positions)  
: The flap m oves up and down autom atically.  
To switch to the sweep function ( ) when in the m anual ( ) m ode,  
hold down the FLAP button.  
NOTE  
FAN SPEED selector  
button  
: The air conditioner autom atically decides the fan speed.  
: High fan speed  
: Medium fan speed  
: Low fan speed  
1 HR. TIMER button  
(1-hour off tim er)  
: When you press this button, regardless of whether the unit is  
operating or stopped, the unit operates for one hour and then  
shuts down.  
1HR.  
ACL button (All clear)  
SET button  
Puts the rem ote control unit into pre-operation status. Always press  
this button after replacing the batteries.  
After using the TIMER ON button or TIMER OFF button to set the tim er,  
press this button to activate the new setting.  
CANCEL button  
ADDRESS sw itch  
Press this button to cancel the current tim er setting.  
The address switch changes to prevent m ixing of signals from rem ote  
control units when two Sanyo air conditioners are installed next to  
each other. Norm ally, the address switch is set to A. When switching  
the address, the rem ote control unit m ust be changed to B. For m ore  
inform ation, please contact the dealer where you m ade the purchase.  
OI-202-11EG  
9
Using the Remote Control Unit  
How to Install Batteries  
1. Slide the cover in the direction indicated by  
the arrow and rem ove it.  
2. Install two AAA alkaline batteries. Make sure  
the batteries point in the direction m arked in  
the battery com partm ent.  
ACL button  
3. Use a thin object such as the tip of a pen to  
press the ACL button.  
Cover  
The batteries last about six m onths, depending on how m uch you use  
the rem ote control unit. Replace the batteries w hen the rem ote control  
unit's display fails to light, or w hen the rem ote control cannot be used  
to change the air conditioners settings.  
Use tw o fresh leak-proof type-AAA alkaline batteries.  
In replacing batteries, follow the instructions as m entioned in the  
sub-section “How to Install Batteries”.  
NOTE  
If you do not use the rem ote control unit m ore than 1 m onth, take out  
the batteries.  
How to Use the Rem ote  
Control Unit  
When using the rem ote control unit, always point the units transm itter  
head directly at the air conditioner's receiver.  
Air conditioner  
(Indoor unit)  
Receiver  
(Transm itter head)  
Rem ote control  
unit  
Rem ote Control Unit  
Installation Position  
The rem ote control unit m ay be operated either from a non-fixed position  
or from a wall-m ounted position. To ensure that the air conditioner operates  
correctly, DO NOT install the rem ote control unit in the following places:  
DO NOT  
In direct sunlight  
Behind a curtain or other places where it is covered  
More than 26 feet (8 m ) away from the air conditioner  
In the path of the air conditioners airstream  
Where it m ay becom e extrem ely hot or cold  
Where it m ay be subject to electrical or m agnetic noise  
Where there is an obstacle between the rem ote control unit and air  
conditioner (since a check signal is sent from the rem ote control unit  
every 5 m inutes)  
10  
OI-202-12EG  
Using the Remote Control Unit (continued)  
Mounting the Rem ote  
Control Unit  
Rem ovable m ounting  
Non-rem ovable m ounting  
Wall  
Wall  
(Packed w ith  
the indoor unit)  
(Packed w ith the  
indoor unit)  
Mounting on a w all  
A. Rem ovable m ounting  
1) Mom entarily hold the rem ote control unit at the desired m ounting  
position.  
2) Confirm that the air conditioner responds correctly when you press  
keys on the rem ote control from that position.  
3) After confirm ing correct operation, use a screwdriver to screw the  
m ounting screw into the wall.  
4) Hang the rem ote control unit from the m ounting screw.  
B. Non-rem ovable m ounting  
1) Mom entarily hold the rem ote control unit at the desired m ounting  
position.  
2) Confirm that the air conditioner responds correctly when you press  
keys on the rem ote control from that position.  
3) After confirm ing correct operation, use a screwdriver to screw the  
m ounting screw into the wall.  
4) Rem ove the batteries of the rem ote control unit.  
5) Use a screwdriver to screw the rem ote control unit securing screw  
into the wall through the hole in the battery com partm ent.  
6) Replace the batteries.  
7) Again confirm that the rem ote control unit operates correctly.  
OI-202-13EG  
11  
Operation with the Remote  
Control Unit  
1. Autom atic Operation  
SET TEMP.  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
STEP 2  
FAN SPEED MODE  
FLAP  
ON  
STEP 1  
OFF  
NIGHT  
SETBACK  
SET CANCEL  
Check that the circuit breaker on the power panel is turned on and that the  
operation selector of the indoor unit is in the ON position.  
NOTE  
Once the  
m ode is selected and the unit is preset by following the steps  
below, you can have the air conditioner autom atically bring the room to the  
desired tem perature sim ply by pressing the ON/OFF operation button.  
STEP 1  
STEP 2  
Press the MODE selector to select  
Press the ON/OFF operation button.  
.
To stop the air conditioner, press the ON/OFF operation button again.  
To change the tem perature setting, press the tem perature setting  
buttons and change the setting to the desired tem perature.  
The tem perature setting changes by two degrees each tim e one of the  
TEMP. buttons is pressed.  
NOTE  
12  
OI-202-14EG  
Operation with the Remote Control Unit (continued)  
Press TEMP. to change the tem perature setting.  
To raise the tem perature  
setting  
TEMP.  
To lower the tem perature  
setting  
Although the fan speed is set autom atically, you can change the fan  
speed by pressing the FAN SPEED selector button.  
To stop the air conditioner, press the ON/OFF operation button again.  
OI-202-15EG  
13  
Operation with the Remote Control Unit (continued)  
2. Manual Operation  
SET TEMP.  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
STEP 2  
STEP 4  
STEP 3  
STEP 1  
FLAP FAN SPEED MODE  
ON OFF  
SET CANCEL  
STEP 5  
NIGHT  
SETBACK  
Check that the circuit breaker on the power panel is turned on and that the  
operation selector of the indoor unit is in the ON position.  
NOTE  
If the autom atic operation settings of the unit do not m eet your needs,  
press the setting buttons as described below and change the settings as  
desired.  
STEP 1  
Press the MODE selector button and select the  
desired m ode.  
For heating operation  
For dehum idifying operation   
For cooling operation  
STEP 2  
STEP 3  
To start the air conditioner, press the ON/OFF  
operation button.  
Press the TEMP. setting buttons to change the  
tem perature setting to the desired tem perature.  
Adjustable tem perature range:  
88 °F m ax. 60 °F m in.  
STEP 4  
NOTE  
Set the FAN SPEED selector button to the setting you  
want.  
If the fan speed is set to  
(Autom atic), the fan  
speed switches autom atically, according to the  
difference between the actual room tem perature and  
the tem perature setting.  
STEP 5  
Press the FLAP button and set the airflow direction as  
desired.  
(Refer to Adjusting the Airflow Direction” on  
page 21.)  
To stop the air conditioner, press the ON/OFF operation button again.  
14  
OI-202-16EG  
Operation with the Remote Control Unit (continued)  
This appliance has a built-in 5-m inute tim e delay circuit to ensure  
NOTE  
reliable operation. When the operation button is pressed, the  
com pressor will start running within three m inutes. In the event of  
power failure, the unit will stop. When the power is restored, the unit  
will restart autom atically after five m inutes.  
3. Adjusting the  
Fan Speed  
A. Autom atic  
Sim ply set the FAN SPEED selector button to the  
position.  
A m icrocom puter in the air conditioner autom atically controls the fan speed  
when the m ode is selected. When the air conditioner starts operating,  
the difference between the room tem perature and the set tem perature is  
detected by the m icrocom puter which then autom atically switches the fan  
speed to the m ost suitable level.  
Cooling and DRY m ode:  
When difference betw een  
room tem perature and set FAN SPEED  
tem perature is  
4 °F and over  
High  
Between 4 °F and 2 °F  
Below 2 °F  
Medium  
Low  
Heating m ode:  
When difference betw een  
room tem perature and set FAN SPEED  
tem perature is  
4 °F and over  
High  
Below 4 °F  
Medium  
B. Manual  
If you want to adjust fan speed m anually during operation, just set the FAN  
SPEED selector as desired. [ , or  
,
]
OI-202-17EG  
15  
Operation with the Remote Control Unit (continued)  
4. Night Setback Mode  
SET TEMP.  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
FLAP FAN SPEED MODE  
ON OFF  
NIGHT  
SETBACK  
SET CANCEL  
ACL  
BATTERIES  
The Night Setback Mode is used for saving energy.  
Press the NIGHT SETBACK button while the air conditioner is operating.  
The  
m ark appears in the display.  
To cancel the night setback function, press the NIGHT SETBACK button  
again.  
16  
OI-202-18EG  
Operation with the Remote Control Unit (continued)  
A. In Cooling and DRY  
Mode:  
When the night setback m ode is selected, the air conditioner  
autom atically raises the tem perature setting 2 °F when 30 m inutes  
have passed after the selection was m ade, and then another 2 °F  
after another 30 m inutes have passed, regardless of the indoor  
tem perature when night setback was selected. This enables you to  
save energy without sacrificing com fort. This function is convenient  
when gentle cooling is needed.  
(
and  
)
2 °F  
Setting  
tem perature  
2 °F  
30 m in.  
30 m in.  
Tim e  
Press the  
NIGHT SETBACK  
button  
B. In Heating Mode:  
When the night setback m ode is selected, the air conditioner  
autom atically lowers the tem perature setting 4 °F when 30 m inutes  
have passed after the selection was m ade, and then another 4 °F  
after another 30 m inutes have passed, regardless of the indoor  
tem perature when night setback was selected. This enables you to  
save energy without sacrificing com fort. This function is convenient  
when gentle heating is needed.  
(
)
Setting  
tem perature  
4 °F  
4 °F  
30 m in.  
30 m in.  
Press the  
NIGHT SETBACK  
button  
Tim e  
OI-202-19EG  
17  
Special Remarks  
``DRY'' ( ) Operation  
How it w orks?  
Once the room tem perature reaches the level that was set, the unit  
repeats the cycle of turning on and off autom atically.  
During DRY operation, the fan speed is autom atically set to LOW or  
VERY LOW; the fan speed then switches back and forth between  
LOW (for 20 seconds) and VERY LOW (for 10 seconds).  
DRY” operation is not possible if the indoor tem perature is 59°F or  
less.  
Heating ( ) Operation  
Heating perform ance  
Because this air conditioner heats a room by drawing in the heat of  
the outside air (heat pum p system ), the heating efficiency will fall off  
when the outdoor tem perature is very low. If sufficient heat cannot  
be obtained with this air conditioner, use another heating appliance  
in conjunction with it.  
Defrosting  
When the outdoor tem perature is low, frost or ice m ay form on the  
heat exchanger coil, reducing heating perform ance. When this  
happens, a m icrocom puter defrosting system operates. At the sam e  
tim e, the fan on the indoor unit stops and the STANDBY lam p  
rem ains lit until defrosting is com pleted. Heating operation restarts  
after several m inutes. (This interval will vary slightly depending  
upon the outdoor tem perature and the way in which frost form s).  
STANDBY lam p  
For several m inutes after the start of heating operation, the indoor  
fan will not start running until the indoor heat exchanger coil has  
warm ed up sufficiently. This is because the COLD DRAFT  
PREVENTION SYSTEM is operating. During this period, the  
STANDBY lam p rem ains lit.  
STANDBY lam p  
OPERATION STANDBY TIMER  
The STANDBY lam p also rem ains lit during defrosting or when the  
com pressor has been turned off by the therm ostat when the system  
is in the heating m ode.  
Upon com pletion of defrosting and when the com pressor is turned  
on again, for heating operation, the STANDBY lam p will go off  
autom atically.  
In the event of power failure, the unit will stop. When the power is  
resum ed, the unit will restart autom atically after five m inutes.  
Pow er failure  
during operation  
Clicking Sound  
Clicking sound is  
heard from the air  
conditioner  
In heating or cooling operation, any plastic parts m ay expand or  
shrink due to a sudden tem perature change. In this event, a clicking  
sound m ay occur. This is norm al, and the sound will soon disappear.  
The rem ote control unit sends the setting condition to the air  
conditioner regularly at five m inute intervals.  
Rem ote Control Unit  
18  
OI-202-18EG  
Using the 12-Hour ON and OFF  
Timer  
After the length of tim e set for TIMER ON elapses, the unit begins  
operating.  
1. TIMER ON m ode  
(Exam ple)  
The display depicted at left indicates that the air conditioner will begin  
operating in three hours.  
ON  
Setting procedure:  
H
STEP 1  
Press the MODE selector button and select the desired  
operation m ode.  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
(See “Operation with the Rem ote Control Unit,” page 14.)  
STEP 2  
Press the TIMER ON button.  
(For exam ple, to set the tim er to turn on the air  
conditioner after three hours have elapsed, press the  
TIMER ON button three tim es.)  
The tim e can be set to from one to twelve hours, in one  
hour steps.  
FLAP FAN SPEED MODE  
ON OFF  
NIGHT  
SETBACK  
SET CANCEL  
ACL  
BATTERIES  
1
2
3.......12  
STEP 3  
Press the SET button.  
The display changes im m ediately to its status previous to tim er setting,  
but the indication rem ains.  
To check the status of the tim er while it is counting down, press the SET  
button.  
ON  
Cancellation procedure: Press the CANCEL button.  
After the length of tim e set for TIMER OFF elapses, the unit stops  
operating.  
2. TIMER OFF m ode  
(Exam ple)  
The display depicted at left indicates that the air conditioner will stop  
operating in five hours.  
Setting procedure:  
OFF  
H
STEP 1  
Press the TIMER OFF button.  
ON  
OFF  
1HR.  
TIMER  
(For exam ple, to set the tim er to turn off the air  
conditioner after five hours have elapsed, press the TIMER  
OFF button five tim es.)  
TEMP.  
The tim e can be set to from one to twelve hours, in one  
hour steps.  
FLAP FAN SPEED MODE  
ON OFF  
1
2
3.......12  
NIGHT  
SETBACK  
SET CANCEL  
ACL  
BATTERIES  
STEP 2  
Press the SET button.  
The display changes im m ediately to its status previous to tim er setting,  
but the indication rem ains.  
To check the status of the tim er while it is counting down, press the SET  
button.  
OFF  
Cancellation procedure: Press the CANCEL button.  
OI-202-21EG  
19  
Using the 1-Hour OFF Timer  
1. 1-Hour OFF Tim er  
This function causes the unit to operate for one hour and then stop,  
regardless of w hether the unit is on or off w hen the button is pressed.  
The  
indicator in the display indicates that this function is operating.  
1HR.  
Setting procedure:  
Regardless of whether the unit is operating or stopped, press the 1 HR.  
TIMER button.  
1HR.  
appears in the display.  
1HR.  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
Cancellation procedure:  
Press the ON/OFF operation button to turn the unit off, wait for the unit to  
stop operating, and then press the ON/OFF operation button again. The  
1-Hour Tim er function is now cancelled and the unit operates norm ally.  
FLAP FAN SPEED MODE  
ON OFF  
NIGHT  
SETBACK  
SET CANCEL  
ACL  
BATTERIES  
If, while the 1-Hour Tim er function is operating, the 1 HR. TIMER button  
is pressed once to cancel the function and then again, the unit continues  
to operate for one hour from that point in tim e and then stops.  
NOTE  
If the 1 HR. TIMER button is pressed while the TIMER OFF function is  
operating, the OFF Tim er is cancelled and the unit stops operating one  
hour later.  
2. Com bining the 1-Hour  
OFF Tim er and 12-Hour  
ON Tim er  
By com bining the 1-Hour OFF Tim er and 12-Hour ON Tim er, it is possible to  
have the unit operate for just one hour from the present tim e, and then  
have it switch on again later at a tim e specified by you.  
(Exam ple) Having the unit operate for just one hour from the present tim e,  
and then switch on again three hours from the present tim e.  
1HR.  
ON  
Tim er setting  
ON  
OFF  
1HR.  
TIMER  
Operate  
Stop  
Operate  
TEMP.  
1 hour  
2 hours  
FLAP FAN SPEED MODE  
ON OFF  
3 hours  
NIGHT  
SETBACK  
SET CANCEL  
ACL  
BATTERIES  
Setting procedure:  
STEP 1  
STEP 2  
Press the 1 HR. TIMER button.  
Press the TIMER ON button and use the SET button to set  
the unit to turn on three hours later.  
Set the 1-Hour OFF Tim er and the 12-Hour ON Tim er sim ultaneously.  
Unless you set the 1-Hour OFF Tim er and the 12-Hour ON Tim er at the  
sam e tim e, the 1-Hour OFF Tim er m ay operate for one hour or m ore.  
NOTE  
20  
OI-202-22EG  
Adjusting the Airflow Direction  
1. Horizontal  
The horizontal airflow can be adjusted by m oving the vertical vanes with  
your hands to the left or right.  
When the hum idity is high, the vertical vanes should be in the front  
position during the cooling or dehum idifying operation. If the vertical vanes  
are positioned all of the w ay to the right or left, condensation m ay begin  
to form around the air vent and drip dow n.  
CAUTION  
2. Vertical  
The vertical airflow can be adjusted by m oving the flap with the rem ote  
control unit. Do not m ove the flap with your hands. Confirm that the rem ote  
control unit has been turned on. Use the FLAP button to set either the  
sweep function or one of the six airflow direction settings.  
(The m axim um capacity is obtained at the position at .)  
ON  
OFF  
1HR.  
TIMER  
TEMP.  
COO
an
FLAP FAN SPEED MODE  
ON OFF  
DR
NIGHT  
SETBACK  
SET CANCEL  
ACL  
BATTERIES  
A. Sw eep function  
The flap starts m oving up and down to  
deliver air over the sweep range.  
B. Setting the airflow m anually  
Referring to the above illustration, use  
the FLAP button to set the airflow  
direction within the range used during  
the heating, cooling, or dehum idifying  
operation.  
The flap autom atically closes when the unit is off.  
NOTE  
During the heating operation, the fan speed will be very low and the  
flap will be in the horizontal position (position ) until the air being  
blown out of the unit begins to warm . Once the air warm s up, the flap  
position and fan speed change to the settings specified with the rem ote  
control.  
Use the FLAP button on the rem ote control to adjust the position of the  
flap. If you m ove the flap by hand, the flap position according to the  
rem ote control and the actual flap position m ay no longer m atch. If this  
should happen, shut off the unit, wait for the flap to close, and then turn  
on the unit again; the flap position will now be norm al again.  
CAUTION  
Do not have the flap pointed down during cooling operation.  
Condensation m ay begin to form around the air vent and drip down.  
OI-202-23EG  
21  
Operation without the Remote  
Control Unit  
INDOOR UNIT  
KHS0951  
KHS1251  
If you have lost the rem ote control unit or it has trouble, follow the steps  
below.  
ON  
OFF  
TEST  
1. When the air conditioner is not running  
If you want to turn on the air conditioner, switch the operation selector to  
the OFF position, and then to the ON position.  
Operation  
selector  
The set tem perature and fan speed are autom atically set at the  
last selection before stopping.  
NOTE  
KHS1852  
2. When the air conditioner is running  
If you want to turn off the air conditioner, switch the operation selector to  
the OFF position.  
ON  
OFF  
TEST  
Operation  
selector  
Care and Cleaning  
1. For safety, be sure to turn the air conditioner off and also to  
disconnect the pow er before cleaning.  
2. Do not pour w ater on the indoor unit to clean it. This w ill dam age  
the internal com ponents and cause an electric shock hazard.  
Casing and Grille  
(Indoor Unit)  
Clean the casing and grille of the indoor unit with a vacuum cleaner brush,  
or wipe them with a clean, soft cloth.  
If these parts are stained, use a clean cloth m oistened with a m ild liquid  
detergent. When cleaning the grille, be careful not to force the vanes out of  
place.  
CAUTION  
1. Never use solvents, or harsh chem icals w hen cleaning the indoor  
unit. Do not w ipe the plastic casing using very hot w ater.  
2. Som e m etal edges and the fins are sharp and m ay cause injury if  
handled im properly; be especially careful w hen you clean these  
parts.  
3. The internal coil and other com ponents of the outdoor unit m ust  
be cleaned every year. Consult your dealer or service center.  
22  
OI-202-22EG  
Care and Cleaning (continued)  
Anti-m old filter  
The anti-m old filter behind the air intake grille should be checked and  
cleaned at least once every two weeks.  
Air intake grille  
How to rem ove the  
anti-m old filter  
1. Grasp both ends of the  
air intake grille and pull  
it out and up.  
2. Push the anti-m old  
filter up slightly, and  
then pull it down.  
Anti-m old filter  
Cleaning  
Use a vacuum cleaner to rem ove light dust. If there is sticky dust on the  
filter, wash the filter in lukewarm , soapy water, rinse it in clean water and  
dry it.  
How to replace the  
anti-m old filter  
1. With the “FRONT” m ark facing  
Air intake grille  
you, slide the anti-m old filter  
up into the unit and then lower  
the handle into the groove on  
the unit.  
2. After installing the anti-m old  
filter, press the locations  
m arked by the arrows (  
)
and close the air intake grille.  
Anti-m old  
filter  
Insert into the groove on the unit.  
OI-202-23EG  
23  
Care and Cleaning (continued)  
Air cleaning filter  
(not provided)  
The air cleaning filter rem oves dust and dirt from the air, and reduces odors  
and sm oke from tobacco.  
KHS0951/ KHS1251  
NOTE  
The air cleaning filter is not provided with the air conditioner and m ust be  
purchased separately. The first tim e that you buy the air clean filter, it is  
necessary to get the STK-ARF4B m odel with fram e. When changing the  
filter subsequently, it is only necessary to replace the filter itself (m odel  
STK-F4B). Do not throw away the filter fram e.  
KHS1852  
The air clean filter is not provided with the air conditioner and m ust be  
purchased separately.  
Ask for the STK-F4B m odel when purchasing.  
The air cleaning filter cannot rem ove harm ful gases or vapors nor ventilate  
air in the room . You m ust open doors or w indow s frequently w hen you use  
gas or oil heating appliances. Otherw ise there is a risk of suffocation in  
extrem e cases.  
Air clean filter  
The air cleaning filter needs to be  
(STK-F4B)  
How to install the air  
cleaning filter  
installed behind the anti-m old filter.  
1. Rem ove the anti-m old filter.  
2. To m ount the STK-F4B, set the  
air clean filter(sold separately)  
at the m ounting position with  
the black side facing the rear.  
To m ount the STK-ARF4B,  
m ount the air clean filter in the  
position shown in the diagram  
with the (STK-F4B) FRONT  
m arking facing the front.  
3. Reinstall the anti-m old filter, and  
KHS1852  
close the suction grill.  
Air clean filter  
(STK-ARF4B)  
In general, the filter should be  
replaced once every three  
m onths.  
NOTE  
Dirty air clean filters cannot be  
washed and reused. Purchase a  
replacem ent filter at your local  
dealer.  
KHS0951/ KHS1251  
Cleaning the m ain unit and  
rem ote control unit  
Wipe clean using a soft, dry cloth.  
To rem ove stubborn dirt, m oisten a cloth in warm water no hotter than  
104°F, wring thoroughly, and then wipe.  
The air intake grille can be rem oved in order to wash it with water.  
24  
OI-202-22EG  
Care and Cleaning (continued)  
Rem oving and rem ounting  
the air intake grille  
With the air intake grille open  
Air intake grille  
Arm  
all the way, grip both arm s  
with your hands and pull  
toward you to rem ove.  
To rem ount, hold the air  
intake grille roughly  
horizontal and push it in until  
the arm shafts fit into the  
indentations in the m ain unit,  
then fit the grille into place.  
When using a footstool or the like, be careful not to let it tip over.  
CAUTION  
Washing the grille w ith  
w ater  
Clean the grille gently using a soft sponge, or the like. Then wipe away  
any rem aining m oisture.  
Neutral detergent m ay be used to rem ove stubborn dirt. Then rinse  
thoroughly with water and wipe away any rem aining m oisture.  
Tips for Energy Saving  
Do not  
Block the air intake and outlet of the unit. If they are obstructed, the  
unit w ill not w ork w ell, and m ay be dam aged.  
Let direct sunlight into the room . Use sunshades, blinds or curtains. If  
the walls and ceiling of the room are warm ed by the sun, it will take  
longer to cool the room .  
Do  
Always try to keep the air filter clean. (Refer to “Care and Cleaning”.)  
A clogged filter will im pair the perform ance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any  
other openings closed.  
OI-202-23EG  
25  
Troubleshooting  
If your air conditioner does not work properly, first check the following points before requesting service. If it  
still does not work properly, contact your dealer or service center.  
Trouble  
Possible Cause  
Rem edy  
Air conditioner does not run 1. Power failure.  
at all.  
1. Restore power.  
2. Contact service center.  
2. Leakage circuit breaker tripped.  
3. Line voltage is too low.  
4. Operation button is OFF.  
3. Consult your electrician or dealer.  
4. Press the button again.  
5. Batteries in rem ote control unit have run 5. Replace batteries.  
down.  
OPERATION lam p flashes  
and air conditioner does not  
operate.  
Trouble in wiring system .  
Contact service center.  
Com pressor runs but soon  
stops.  
Obstruction in front of condenser coil.  
Rem ove obstruction.  
Poor cooling (or heating)  
perform ance.  
1. Dirty or clogged air filter.  
2. Heat source or m any people in room .  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge  
port.  
1. Clean air filter to im prove airflow.  
2. Elim inate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Rem ove it to ensure good airflow.  
5. Therm ostat is set too high for cooling (or 5. Set the tem perature lower (or higher).  
too low for heating).  
6. (Outdoor tem perature is too low.)  
6. (Consult your dealer or try to use a  
back-up heater.)  
Clicking sound is heard from In heating or cooling operation, any plastic This is norm al, and the sound will soon  
the air conditioner.  
parts m ay expand or shrink due to a  
sudden tem perature change. In this event,  
a clicking sound m ay occur.  
disappear.  
OPERATION lam p lights but  
outdoor unit will not run.  
1. The use of portable telephones near the  
air conditioner m ay cause disturbance to  
its norm al operation.  
1. Turn off the power then restart the air  
conditioner after 1 m inute.  
2. Consult your dealer.  
Operating Range  
The air conditioner is operable within the tem perature ranges as listed below:  
Tem perature  
Maxim um  
Minim um  
Maxim um  
Minim um  
Indoor Air Intake Tem p.  
95 °F DB/71 °F WB  
67 °F DB/57 °F WB  
80 °F DB/67 °F WB  
– DB/– WB  
Outdoor Air Intake Tem p.  
115 °F DB  
COOLING  
HEATING  
67 °F DB  
75 °F DB/65 °F WB  
17 °F DB/15 °F WB  
26  
OI-202-22EG  
For Parts or Service Contact  
SANYO FISHER SERVICE CORPORATION  
A DIVISION OF SANYO LOGISTICS CORPORATION  
1411 West 190th Street, Suite 800, Gardena, CA 90248 U.S.A.  
50 Beth Nealson Drive, Toronto, Ontario, M4H 1M6, CANADA  

Lexmark Platinum Pro900 User Manual
Linak Techline Linear Actuator Technology User Manual
Milwaukee 48 59 0255 User Manual
Oki Fax 5680 User Manual
Panasonic Super Deluxe Cu Xe9dke User Manual
Philips R6b4b260 User Manual
Schumacher Ip 95l User Manual
Schumacher Sf 4020 User Manual
Sharp Mx C312 User Manual
Toshiba Multifunctional Digital Systems 225 User Manual